HomeMy WebLinkAboutADD 1_Bartels Hall Fire Alarm Replace_10-14-2020AttCORNELL UNIVERSITY BARTELS HALL FACILITIES CONTRACTS FIRE ALARM REPLACEMENT 121 HUMPHREYS SERVICE BUILDING ITHACA, NEW YORK 14853-3701 ADDENDUM NO. 1 October 14, 2020 This Addendum contains changes to the requirements of the Contract Documents and Specifications. Such changes are to be incorporated into the Construction Documents and shall apply to the work with the same meaning and force as if they had been included in the original document. Wherever this Addendum modifies a portion of a paragraph of the specifications or a portion of any Drawing, the remainder of the Paragraph or Drawing shall remain in force. NOTE: Provisions of all Contract Documents apply. Item 1. Attached is the Pre-Bid Sign-in Sheet for reference only. DRAWINGS Item 2. Drawing E-001, General Notes ADD
18.0 The Basis of Design for this project is a Gamewell/FCI E3 Series network addressable fire control unit and UL listed peripheral devices as noted on Drawing E-401, Material List.
If another fire alarm manufacturer is specified other than the Basis of Design, the fire alarm supplier shall provide onsite end user training for Cornell University’s fire alarm technicians, as well as testing and inspection personnel.
Item 3. Below is the PreBid Documentation BOX link: “Bartels Hall Fire Alarm Replacement Pre-Bid Walkthrough & Addendum Items”: https://cornell.box.com/s/33rpec6nf0vg5vqnxhaulb32cbuly3re Item 4. DELETE Drawing E-100 in its entirety. REPLACE with revised E-100, attached. Item5. DELETE Drawing E-101 in its entirety. REPLACE with revised E-101, attached. Item 6. DELETE Drawing E-102 in its entirety. REPLACE with revised E-102, attached.
Bartels Hall Fire Alarm Replacement Addendum No. 1 October 14, 2020 Page 2
Item 7. DELETE Drawing E-103 in its entirety. REPLACE with revised E-103, attached. Item 8. RFI Questions and Clarifications See attached RFI Log (Items 1 – 3) Attachments: Pre-Bid Sign-in Sheet Drawings: E-100, E-101, E-102, E-103 RFI Log (Items 1-3) ****END OF ADDENDUM****
PROJECT: Bartels Hall Fire Alarm Replacement
DATE: October 8, 2020 via Zoom Meeting PRE-BID MEETING 9:00AM
Name Firm E-Mail Address Telephone Fax #
Hung Tran Cornell-Facilities Engineering hpt4@cornell.edu 607-279-3524
Sherrie Joseph Cornell - Facilities Contracts sam7@cornell.edu
Wendy Hackett Cornell - Facilities Contracts wjh6@cornell,edu 607-255-0120 607-254-4567
Matt Labosky Blanding Electric mlabosky@blandingelectric.com
Jon Rigdon Matco Electric jrigdon@matcoelectric.com
Matt McDonald O'Connell Electric matthew.mcdonald@oconnellelectri.com
Deb Melanson Cornell - Project Management dem5@cornell.edu
Dan Smith John Mills Electric
Tim McGee West Fire Systems, Inc.tmcgee@westfiresystems.com
John Whitmore Schueler-Haas Electric jwhitmore@schuler-haas.com
Kelly Davis Cornell - eBuilder Support kmu2@cornell.edu 1-888-288-5717
Chris Kiehle Cornell University - SCL cak226@cornell.edu
UP
UPUP
UPUP
B16
B18
B20
B22
B24
B26
B28
B30
B32
B34
B36
B38
B0027
B0026
B0042
B17
B21
B23
B0028
B31
B33
B39
B0046
B0001B0066
B0063
B0053
B0065
B0040
B07
B07A
B0068
B0069
B0062
B0061
B06
B06A
B0052
B01
B01A
B0003 B0004
B0002
B0060
B46A
B46
B46C B46D
B51
B42
B47B
B47A
B49
B44
B40
B0055
B40A
B0056 B45
B41 B43
B46B
B47C
B47
B0064
B0054
B0031
B0030
B0051
B07B
B07C
B0021
B0022
B0023
B0025
B0024
B0020
B0067
B0029
B0020A
B0024A
B0063
B0053
B0065 B0062
B0061
B0052
B0002
B0060
B0064
B0054 B0051FS
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
SS
S
S
S
S
FFFFFFS
FF
F FFROLLING
DOOR
S S S H
H
ELEV.FF
E-100
1
F
WP
S
ELEV.
MECH.
F
S S
S
S S
FF
F
F
F
S
MAIN
ELECTRIC
ROOM
INDICATES EXISTING SPRINKLER
HEAD (TYPICAL ON DRAWING)
INDICATES EXISTING FIRE ALARM
DEVICE (TYPICAL ON DRAWING)
ALL COMBO NOTIFICATION
APPLIANCES ARE
SPEAKER/STROBE DEVICES
TS TS
TS
TS
FS
FS
FS
FS
TS
EXISTING FIRE ALARM
CONTROL PANEL.
SEE PHOTO.
EXISTING VOICE EVACUATION
ALARM BOX. SEE PHOTO CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
E-100
12675138
BUILDING 2631
EXISTING AND
PHASE 2
BASEMENT FIRE
ALARM PLAN
H. TRAN
JD
2631, 2631A
SEPTEMBER 18, 2020
0' 4' 8'16'
SCALE: 1/8"=1'-0"
SCALE:1/16" = 1'-0"2 FULL BASEMENT PLAN 0' 8' 16' 32'
SCALE: 1/16"=1'-0"
GENERAL NOTES
1. PHASE 1, PROVIDE NEW FIRE ALARM SYSTEM. PHASE 2, REMOVE THE EXISTING
FIRE ALARM SYSTEM. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN
OPERATIONAL DURING THE INSTALLATION OF THE NEW SYSTEM.
2. PHASE 2, REMOVE EXISTING FIRE ALARM DEVICES AND ASSOCIATED WIRING AND
RACEWAYS COMPLETELY BACK TO SOURCE. PROVIDE ELECTRICAL IVORY BLANK
PLATES OVER EXISTING BACK BOXES.
SCALE:1/8" = 1'-0"1 PARTIAL BASEMENT PLAN
ROOM B0064 -FIRE ALARM PANEL &
VOICE EVACUATION ALARM BOX
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION
122A
122A
102
10065
10045 10021
10011
103B
103A
103
10060
10061
108
10022
10066
110
10047
112D
112C
112B
10067
112A
101
10043 10044
10003 1000410050
10012
10042 10041
10001 10002
112
10052
10040
1000810007
1000610005
10053
10051
10046
10062
DISPLAY CASECONCESSION STAND122
104 106
10064
10048
SEE BASEMENT
PLAN
10014
112E
112F
112G
UP
UPDN
UP
UP DN
DN
DN
DN UP DNUP
UP UP
UP
DN
UP
UP
UP UPUPUP10068
115A
115B
115
10054
10015
10014
UP
UP
1M12
DN
BUILDING 2631A FIRST FLOOR
LOCATION OF MEZZANINE
FF
S
S
S
F FFF
S
S
J
FS
J
FS
J
FS
J
FS
S
FIRE SHUTTER
TYPICAL
J
FIRE
SHUTTER
S
S
S
S
J
FIRE
SHUTTERFF
H
S
FSTS
H
FA TERMINAL BOX
S S S
S ELEV.
F F
S SFAA
EXISTING FA ANNUNCIATION
PANEL. SEE PHOTO.
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S S S
F
FF
F FF
F
F
SSSS
D
D
F
F
FJ
FIRE
SHUTTER FF
S
S
S
S FF
S
S
F FF
F F
WG
WG
F
WG
S
H
FS
TS
H
S
S
EXISTING SPRINKLER HEAD
(TYPICAL ON DRAWING)
WG
INDICATES EXISTING SPRINKLER
HEAD (TYPICAL ON DRAWING)
INDICATES EXISTING FIRE ALARM
DEVICE (TYPICAL ON DRAWING)WG
WG
ALL COMBO NOTIFICATION
APPLIANCES ARE HORNS/STROBES
EXISTING VOICE EVACUATION
ALARM BOX
EXISTING VOICE EVACUATION
ALARM BOX
EXISTING VOICE EVACUATION
ALARM BOX
EXISTING FIRE DEPARTMENT
VOICE EVACUATION ALARM
BOX. TO BE REMOVED
(PHASE 2)
EXISTING KNOCK BOX
LYNAH RINK
1
ALL COMBO NOTIFICATION
APPLIANCES IN BARTELS ARE
SPEAKER/STROBE DEVICES CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
E-101
12675138
BUILDING 2631
AND 2631A
EXISTING AND
PHASE 2 FIRST
FLOOR FIRE
ALARM PLAN
H. TRAN
JD
2631, 2631A
SEPTEMBER 18, 2020
SCALE:1/16" = 1'-0"1 1ST FLOOR
GENERAL NOTES
1. PHASE 1, PROVIDE NEW FIRE ALARM SYSTEM. PHASE 2, REMOVE THE EXISTING
FIRE ALARM SYSTEM. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN
OPERATIONAL DURING THE INSTALLATION OF THE NEW SYSTEM.
2. PHASE 2, REMOVE EXISTING FIRE ALARM DEVICES AND ASSOCIATED WIRING AND
RACEWAYS COMPLETELY BACK TO SOURCE. PROVIDE ELECTRICAL IVORY BLANK
PLATES OVER EXISTING BACK BOXES.
SCALE:1/8" = 1'-0"2 BUILDING 2631 MEZZANINE
0' 8' 16' 32'
SCALE: 1/16"=1'-0"
0' 4' 8' 16'
SCALE: 1/8"=1'-0"
FA ANNUNCIATION PANEL
E-101 KEYED DEMOLITION NOTES
1 REMOVE EXISTING VOICE EVACUATION ALARM BOX AND ASSOCIATED DEVICES AND
WIRING COMPLETELY. PROVIDE A WHITE BLANK PLATE OVER EXISTING BACK BOX.
#
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION
20011 20012
2001520016
20045 20047
20062 20067
20065 20066
20068
202 204 206 208 210 212
214
215
218
222 224 226
227
228 230 232
240
241
242244
213 217 219 221 223
20040
225 20060
20049 20048
243
2000620005
OPEN TO BELOW OPEN TO BELOW
10013
OPEN TO BELOW
OPEN TO BELOW
OPEN TO BELOW
DN
DN DN
DN DN
DN
UPUP
DN
DN
DN
DN
UP
1M115A
1M115DN
DN
V V40'40'
40'40'
V V
40'
40'
40'
BD
BD
BD40'
40'BD
BD
BD
40'
FF
BEAM DETECTOR
TYPICAL
SSSSS
FS
FS
FSTS
TS
TS S
S
S
S
S
S
S
S
S
D
S
D
S D S
D
S
D
S
S
S S
S
S
S
S D S
D
S
S
D S D
S
H H
FFF FFF
FS TS
FS TSFF
FFFF
F
F
S D
S SHAFT
S ELEV.
S
F
SSS
F
CLG.F
CLG.
S
EXISTING SPRINKLER HEAD
(TYPICAL ON DRAWNG)
WALL
INDICATES EXISTING FIRE ALARM
DEVICE (TYPICAL ON DRAWNG)
ALL COMBO NOTIFICATION
APPLIANCES ARE HORNS/STROBES
SPEAKER (TYPICAL)
ALL COMBO NOTIFICATION
IN BARTELS APPLIANCES ARE
SPEAKER/STROBE DEVICES
0' 8' 16' 32'
SCALE: 1/16"=1'-0"CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
E-102
12675138
BUILDING 2631
AND 2631A
EXISTING AND
PHASE 2
SECOND FLOOR
FIRE ALARM
PLAN
H. TRAN
JD
2631, 2631A
SEPTEMBER 18, 2020
SCALE:1/16" = 1'-0"1 2ND FLOOR BUILDING 2631A MEZZANINE
GENERAL NOTES
1. PHASE 1, PROVIDE NEW FIRE ALARM SYSTEM. PHASE 2, REMOVE THE EXISTING
FIRE ALARM SYSTEM. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN
OPERATIONAL DURING THE INSTALLATION OF THE NEW SYSTEM.
2. PHASE 2, REMOVE EXISTING FIRE ALARM DEVICES AND ASSOCIATED WIRING AND
RACEWAYS COMPLETELY BACK TO SOURCE. PROVIDE ELECTRICAL IVORY BLANK
PLATES OVER EXISTING BACK BOXES.
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION
3P0063
3P0062
3P0017
3P00153P0016
DN DN
UP
DN
ROOFFF
BD
BD
BD
BD
BD
BD
BEAM DETECTOR
TYPICAL
VVVV
VVVV
S WP
S WP
STAIR VENT
SHAFT VENT
SMOKE HATCH
TYPICAL
S WP
S WP
STAIR VENT
SHAFT VENT
S WP
S WP
HOISTWAY
SHAFT VENT
S
D S
D
S
D
S
D
S
D
H H FS
TSFF
S
D
S
D
S
D
S
D
H
H
FS TS
F
FBDBD
H H
INDICATES EXISTING SPRINKLER
HEAD (TYPICAL ON DRAWING)
INDICATES EXISTING FIRE ALARM
DEVICE (TYPICAL ON DRAWNG)
SPEAKER (TYPICAL)
1
1
1
1 1
1
ALL COMBO NOTIFICATION
IN BARTELS APPLIANCES ARE
SPEAKER/STROBE DEVICES CORNE LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
554 CAMPUS ROAD
BARTELS HALL
FIRE ALARM
REPLACEMENT
E-103
12675138
BUILDING 2631
EXISTING AND
PHASE 2 THIRD
FLOOR FIRE
ALARM PLAN
H. TRAN
JD
2631, 2631A
SEPTEMBER 18, 2020
SCALE:1/16" = 1'-0"1 3RD FLOOR
0' 8' 16' 32'
SCALE: 1/16"=1'-0"
GENERAL NOTES
1. PHASE 1, PROVIDE NEW FIRE ALARM SYSTEM. PHASE 2, REMOVE THE EXISTING
FIRE ALARM SYSTEM. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN
OPERATIONAL DURING THE INSTALLATION OF THE NEW SYSTEM.
2. PHASE 2, REMOVE EXISTING FIRE ALARM DEVICES AND ASSOCIATED WIRING AND
RACEWAYS COMPLETELY BACK TO SOURCE. PROVIDE ELECTRICAL IVORY BLANK
PLATES OVER EXISTING BACK BOXES.
E-103 KEYED DEMOLITION NOTES
1 REMOVE EXISTING DETECTOR AND ASSOCIATED WIRING COMPLETELY BACK TO
SOURCE. MODIFY VENT TO BE OPERATED MANUALLY.
#
1 06/29/20 ISSUE FOR DD REVIEW
2 08/14/20 ISSUE FOR 50% REVIEW
3 09/18/20 ISSUE FOR CONSTRUCTION
Date: October 14, 2020
RFI Form
RFI/Page/
Response Dwg./Spec./Rep.Section/Design Team
Index Number Paragraph/Topic RFI Response
1 General Ceiling Types &
Heights
Please provide ceiling Types and Heights for each
area. If I remember correctly the Common areas are all
sheetrock ceilings.
See Addendum No. 1, Item 3.
See floor plans, reflected ceiling plans (A151,
A152, A153, A154, A155,
2631A_Friedman_Ceiling Plan) and ceiling
photos.
2 General EMT vs Wiremold
Please provide Locations of Utility area's and any
other areas where EMT can be used. Will it be allowed
in open bar joist ceilings like Rooms 101, 112 and
115? If so will be have to paint EMT to match ceiling?
See Addedum No. 1, Items 4 thru Item 7.
3 General Divided 2400
Wiremold
Can Divided 2400 Wiremold be utilized to carry the
initiating and strobe circuit on one side & the speaker
circuit on the other side?
The SLC initiating circuit and the 70Vrms
speaker circuits cannot reside in the same
raceway. A split 2400 Series with the SLC
initiating circuit on one side and the 70Vrms
speaker circuit on the other side will work.
You can run the strobe circuit and 70Vrms
speaker circuits in the same raceway. You can
run the strobe circuit and SLC initiating
circuits in the same raceway.
PROJECT: Bartels Hall Fire Alarm Replaceme