HomeMy WebLinkAboutADD 1_Duffield 330 Lab Reno_10-6-2020CORNELL UNIVERSITY DUFFIELD HALL FACILITIES CONTRACTS 330 LAB RENOVATIONS
121 HUMPHREYS SERVICE BUILDING ITHACA, NEW YORK 14853-3701 ADDENDUM NO. 1 October 6, 2020 This Addendum contains changes to the requirements of the Contract Documents and Specifications. Such changes are to be incorporated into the Construction Documents and shall apply to the work with the same
meaning and force as if they had been included in the original document. Wherever this Addendum modifies a portion of a paragraph of the specifications or a portion of any Drawing, the remainder of the Paragraph or Drawing shall remain in force.
NOTE: Provisions of all Contract Documents apply.
Item 1. ADD Section 01 21 00 – Allowances, attached. Item 2. ADD Section 01 23 00 – Alternates, attached. Item 3. Drawing A-101 ADD the following clarification to the end of Keyed Renovation Notes 5, 7, 10, 15, and 16: “Wood species to be maple. Door veneers to be Plain Sliced.” Item 4. Drawing A-101 DELETE Keyed Renovation Notes 17, 18, and 19 to remove scope from this project. The
College of Engineering will purchase lab chairs/stools directly. Item 5. Drawing A-101, Keyed Renovation Note 20
DELETE in its entirety. REPLACE with: 20. In work area, inspect existing partitions up to deck, and floor penetrations to the floor below (second floor) and above (penthouse). Patch any larger openings with 5/8” gypsum drywall Type X, and use appropriate fire stopping material to fill any other open penetrations to confirm fire rating as indicated on code compliance plan A-001. Item 6. Drawing A-101, Door / Hardware Schedule ADD the following width to door 330-1: 3’-0” (active leaf) + 2’-0”
Duffield Hall 330 Lab Renovations Addendum No. 1
October 6, 2020 Page 2
Item 7. Drawing P-001, Plumbing Piping Schedule and Specifications “Lab Waste and Vent”
• DELETE Fittings information “ASTM A162 316L Stainless Steel” REPLACE with “ASTM D4101 POLYPROPYLENE”
• DELETE Joint information “Compression” REPLACE with “Mechanical” Item 8. Drawing M-001, Mechanical General Notes ADD 8. Coordinate closely with the building manager and arrange for necessary system shut downs associated with connection to building central systems. Particularly, the central general
exhaust system, exhaust fans EX-5 and EX-6. Item 9. DELETE drawing M-101 in its entirety. REPLACE with drawing M-101R1, attached.
Item 10. DELETE drawing M-501 in its entirety. REPLACE with drawing M-501R1, attached. Item 11. DELETE drawing E-101 in its entirety. REPLACE with drawing E-101R1, attached. Item 12. RFI Questions and Clarifications See attached RFI Log (Items 1-2)
Attachments: Section 01 21 00 Allowances Section 01 23 00 Alternates
M-101R1 - Partial Third And Fourth Floor Mechanical Plans M-501R1 - Schedules And Details E-101R1 - Power, Data, Lighting, And Fire Alarm Partial Third Floor Plan
RFI Log (Items 1-2) ****END OF ADDENDUM****
CORNELL UNIVERSITY SECTION 01 21 00 Ithaca, New York ALLOWANCES
ADDENDUM NO. 1 ALLOWANCES 01 21 00-1 October 6, 2020
SECTION 01 21 00 ALLOWANCES
1.0 GENERAL
1.1 RELATED DOCUMENTS
A. This Section describes Allowances to be carried in the Base Bid by the Contractor.
B. Drawings and general provisions of the Contract, including General Conditions and other Division 01 Specification Sections, apply to this Section.
C. The Specification Section containing the pertinent requirements of materials and methods to achieve the Work described herein. Selected materials and equipment are specified in the Contract Documents by allowances.
1.2 SUMMARY
A. Definition: An allowance is an amount determined by the Owner or calculated by the Contractor based on given quantities and stated on the Bid Proposal Submission Form.
B. Certain items are specified in the Contract Documents by allowances. Allowances have been established in lieu of additional requirements and to defer selection of actual materials and
equipment to a later date when direction will be provided to the Contractor. Items covered by these allowances shall be supplied for such amounts and by such persons as the Owner may direct. All uses of the allowances will require the prior written approval of the Owner
via a Field Change Authorization.
C. Types of Allowances may include:
1. Lump Sum Allowance
2. Unit Price Allowance
1.3 SELECTION AND PURCHASE
A. At the earliest practical date after award of the Contract, advise the Architect of the date when final selection and purchase of each product or system described by an allowance must be completed to avoid delaying the Work. The Contractor shall provide the Owner fourteen (14) calendar days minimum notification of date.
B. At the Owner’s request, the Contractor shall obtain proposals for each allowance for use in making final selections. The Contractor shall include recommendations that are relevant to performing the work.
C. The Contractor shall purchase products and systems selected by the Architect and Owner from the designated supplier.
CORNELL UNIVERSITY SECTION 01 21 00 Ithaca, New York ALLOWANCES
ADDENDUM NO. 1 ALLOWANCES 01 21 00-2 October 6, 2020
1.4 SUBMITTALS
A. Submit proposals for purchase of products or systems included in allowances, in the form specified for Change Orders.
B. Submit invoices or delivery slips to show actual quantities of materials delivered to the site for use in fulfillment of each allowance.
C. Submit time sheets and other documentation to show labor hours and cost for installation of allowance items that include installation as part of the allowance.
D. Coordinate and process submittals for allowance items in the same manner as for other portions of the work.
1.5 COORDINATION
A. Coordinate related Work and modify or adjust adjacent Work as necessary to ensure that Work affected by each accepted allowance is complete and fully integrated into the Project.
B. The Contractor shall include the dollar value of each scheduled allowance number as a separate line item in the Schedule of Values and identify each allowance with Section number 01 21 00.
C. The Owner shall provide the Contractor with a Field Change Authorization prior to proceeding with the Work of an allowance.
1.6 LUMP SUM AND UNIT PRICE ALLOWANCES
A. Allowances shall include cost to the Contractor of specific products and materials ordered by the Owner or selected by the Architect under allowance and shall include applicable taxes, freight, and delivery to the Project site.
B. Included as part of each allowance are miscellaneous devices, accessory objects or similar items incidental to or required for a complete installation whether or not mentioned as part of the allowance.
C. Unless otherwise indicated, Contractor’s cost for receiving and handling at Project site, labor, installation, overhead and profit, and similar costs related to products and materials ordered by the Owner or selected by the Architect under allowance shall be included as part of the
Contract Sum and not part of the allowance.
D. Unused Materials: Return unused materials purchased under an allowance to the manufacturer or supplier for credit to the Owner, after installation has been completed and
accepted.
1. If requested by the Owner, retain and prepare unused materials for storage by the Owner. Deliver unused material to Owner’s storage space as directed.
CORNELL UNIVERSITY SECTION 01 21 00 Ithaca, New York ALLOWANCES
ADDENDUM NO. 1 ALLOWANCES 01 21 00-3 October 6, 2020
1.7 ADJUSTMENT OF ALLOWANCES
A. Allowance Adjustment: To adjust allowance amounts and scope of work, prepare a Change Order proposal based on the difference between purchase amount and the allowance,
multiplied by final measurement of work-in-place where applicable. If applicable, include reasonable allowances for cutting losses, tolerances, mixing wastes, normal product imperfections, and similar margins.
1. Include installation costs in purchase amount only where indicated as part of the allowance.
2. Prepare explanation and documentation to substantiate distribution of overhead costs and other margins claimed.
3. Submit substantiation of a change in scope of work, if any, claimed in Change Order related to unit-cost allowance.
4. Owner reserves the right to establish the quantity of work-in-place by independent quantity survey, measure, or count.
B. Submit claims for increased costs because of a change in scope or nature of the allowance described in the Contract Documents, whether for the purchase order amount or Contractor’s handling, labor, installation, or overhead and profit. Submit claims in accordance with
General Conditions – Changes in Work within twenty-one (21) days of receipt of Field Change Authorization authorizing work to proceed. The Owner will reject claims submitted later than twenty-one (21) days after such authorization.
1. Do not include Contractor’s or subcontractor’s indirect expenses in the Change Order cost amount unless it is clearly shown that the nature or extent of work has changed from what could have been foreseen from information in the Contract Documents.
2. No change to Contractor’s indirect expenses is permitted for selection of higher or lower priced materials or systems of the same scope and nature as originally indicated.
2.0 PRODUCTS – NOT USED
3.0 EXECUTION
3.1 EXAMINATION
A. Examine products covered by an allowance promptly on delivery for damage or defects. Return damaged or defective products to manufacturer for replacement.
CORNELL UNIVERSITY SECTION 01 21 00 Ithaca, New York ALLOWANCES
ADDENDUM NO. 1 ALLOWANCES 01 21 00-4 October 6, 2020
3.2 PREPARATION
A. Coordinate materials and their installation for each allowance with related materials and installations to ensure that each allowance item is completely integrated and interfaced with
related work.
3.3 SCHEDULE OF ALLOWANCES
A. Allowance No. 1: Lump Sum Allowance: Include the sum of $3,000.00 to cover the work identified in keyed renovation note 20 on drawing A-101.
***END OF SECTION 01 21 00**
CORNELL UNIVERSITY SECTION 01 23 00 Ithaca, New York ALTERNATES
ADDENDUM NO. 1 ALTERNATES 01 23 00-1 October 6, 2020
SECTION 01 23 00 ALTERNATES
1.0 GENERAL
1.1 RELATED DOCUMENTS
A. This Section describes the changes to be made under each Alternative.
B. The Specification Section containing the pertinent requirements of materials and methods to achieve the Work described herein.
1.2 DESCRIPTION OF REQUIREMENTS
A. Definition: An alternate is an amount proposed by Bidders and stated on the Bid Proposal Submission Form and in the eBuilder Bid Module for certain items that may be added to or deducted from the Base Bid amount if the Owner decides to accept a corresponding change in either the amount of construction to be completed, or in the product, materials, equipment,
systems or installation methods described in the Contract Documents. Alternates shall include all overhead, profit and other expenses, including bond costs, in connection therewith.
B. Coordination: Coordinate related Work and modify or adjust adjacent Work as necessary to ensure that Work affected by each accepted alternate is complete and fully integrated into the Project.
C. Notification: Immediately following Contract award, prepare and distribute to each party involved, notification of the status of each alternate. Indicate whether alternates have been accepted, rejected or deferred for consideration at a later date. Include a complete description of negotiated modifications to alternates.
D. Schedule: A "Schedule of Alternates" is included at the end of this Section. Include as part of each alternate, miscellaneous devices, accessory objects or similar items incidental to or required for a complete installation whether or not mentioned as part of the alternate.
2.0 PRODUCTS – NOT USED
3.0 EXECUTION
3.1 SCHEDULE OF ALTERNATES
A. ALTERNATE NO. 1
Deduct Alternate: Remove the scope associated with the door and frame replacement of Door 330-1 and leave the associated existing conditions as they currently are.
***END OF SECTION 01 23 00***
1
1 1
2
2
2
2
2
24x8 EA 48x18 EA42x1812x12
SA DUCT MAIN
ABOVE CORRIDOR
CEILING (E)
EA DUCT MAIN
IN UTILITY
CORRIDOR (E)
EG-330 (E)
SD1-330 (E)
SD2-330 (E)
SD3-330 (E)
SD4-330 (E)3
VAV-53 (D)
VAV-54 (D)
ROOM TS (E)
2
1" HWS
1" HWR
330
4
4
4
4
5
5
EAV (E)
4
6
6
4
EAV-330-1
4' ADA FUME
HOOD EAV-330-2
24x8 EA(E)48x18 EA(E)1344 CFM
1130 CFM
1
130 CFM
2
4 150 CFM
6ø EA 6ø EA8ø EA
12ø EA6495 CFM
16x12 EA
EAV-330-3
742x18SAV-330-1
RHC-330
8
9
14
9
E8 LASER CUTTER
E4 VACUUM PUMP
2
E3 VACUUM PUMP
1
E11
ELECTROSPINNING
STATION
E12 3D PRINTER
E9 MILL
350 CFM
8ø 10x68ø 8ø10
11
EAV-330-4
9
VD VD
12
13
328 CFM
13
328 CFM
13
328 CFM
5
136 CFM
SD5-330 SD1-330 (E)
SD2-330 (E)
SD3-330 (E)
SD4-330 (E)
15
329 CFM
16
10ø8øVD VD
VD
18x14
10
12
3
M-101R1
6ø EA VD
10ø
6ø
26
ROOM TS (E)
3
1" HWS 1" HWR
2
M-501R1
MANUAL
VENTILATION
SHUTOFF
SWITCH
27
16ø
8ø
28 200 CFM
VD
VD
24x8
29
30100 CFM
10ø
6ø 6øVD
37
34
20x16 EA
35
24X16
SA (E)
32
10 35
35
FUME
HOOD (E)
12ø EA
31 32
12ø EA(E)
31
6" VAC
EXHAUST (E)
6" VAC
EXHAUST (E)
33
18x14
36
35 EAV (E)
8ø
36
35
FD-1
FD-2
FD-3
FD-4
FSD-1
FSD-2
2" VAC
2" VAC10ø
2 38
38
38
4
6
M-501R1
4
VD
10ø EA3RD FLOOR
34' -0"
PENTHOUSE LEVEL
50' -0"
3RD FLOOR
34' -0"
VAC
N2
CA
17 ADA
FUME
HOOD
18
19
20
21
22
23
25
241 1/2" LV1/2" DCW1 1/4" RODI1 1/4" RODI1/2" CA1/2" N23/4" VAC10ø8ø
1-1/2" LW4" LW (E)
DCW
RODI
COORDINATION NOTE:
HOOD (PROVIDED BY OTHERS) TO BE PROVIDED WITH
INTERNAL PLUMBING, VALVES, AND FIXTURES FROM THE
FACTORY MEETING SPECIFICATIONS AS OUTLINED ON THE
PLUMBING PLANS. INTERNAL PLUMBING TO INCLUDE THE
FOLLOWING:
-VAC
-N2 WITH HOOD MOUNTED REGULATOR ASSEMBLY
-CA WITH HOOD MOUNTED REGULATOR ASSEMBLY
-DCW WITH VACUUM BREAKER AND GOOSENECK TO CUPSINK
-RODI WITH VACUUM BREAKER AND GOOSENECK TO CUPSINK
28
37
10ø EA90x48 EAEX-5
EX-6
EXHAUST
DISCHARGE
STACK (E)
EXHAUST PLENUM (E)
MECHANICAL
ROOM
40060 CORN E LL U N I V
E
RSI
TYFOU
N
D E D 5681
AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
343 CAMPUS ROAD
ITHACA, NEW YORK 14850
DUFFIELD HALL
330 LAB
RENOVATIONS
M-101R1
12672500
PARTIAL THIRD
AND FOURTH
FLOOR
MECHANICAL
PLANS
E. LEPORE
TRF
2000
SEPTEMBER 4, 2020
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
M-101R1 KEYED DEMOLITION NOTES
1 DISCONNECT AND REMOVE EXISTING GENERAL EXHAUST AIR VALVE AND
ASSOCIATED ACCESSORIES. REMOVE PORTION OF EXHAUST DUCTWORK TO
PREPARE FOR RECONNECTION.
2 REMOVE EXISTING SUPPLY AIR VALVE, REHEAT COIL PIPING, REHEAT COIL
CONTROL VALVE, ASSOCIATED ACCESSORIES, AND PORTION OF SUPPLY AIR
DUCTWORK AS REQUIRED FOR THE RENOVATIONS.
3 DISCONNECT AND RETAIN EXISTING SUPPLY AIR DIFFUSER. HOLD ON SITE FOR
REINSTALLATION.
4 DISCONNECT AND REMOVE PORTION OF EXISTING SUPPLY AIR DUCT SERVING
UTILITY CORRIDOR AS REQUIRED TO PREP FOR FIRE DAMPER INSTALLATION.
RETAIN EXISTING SUPPLY AIR GRILLE FOR REINSTALLATION.
5 DISCONNECT AND REMOVE EXISTING EXHAUST AIR DUCT ATTENUATOR
6 DISCONNECT AND REMOVE PORTION OF EXISTING EXHAUST AIR DUCT AS
REQUIRED TO INSTALL FIRE DAMPER IN WALL.
#M-101R1 KEYED RENOVATION NOTES
1 PROCESS EXHAUST DROP DOWN TO EXHAUST ENCLOSURE. PROVIDE BLAST GATE
DAMPER AND BALANCE TO AIRFLOW SPECIFIED. ENCLOSURE PROVIDED BY
OTHERS.
2 DROP 2" 304 STAINLESS STEEL VACUUM PUMP EXHAUST PIPE DOWN TO VACUUM
PUMP. REFER TO DETAIL 6/M-501R1.
3 CONNECT TO EXISTING REHEAT HOT WATER PIPING AND EXTEND 3/4" HOT WATER
SUPPLY AND HOT WATER RETURN TO REHEAT COIL. PROVIDE PIPING PER DETAIL
AND BALANCE FLOW PER SCHEDULE.
4 6" EXHAUST DUCT DROP TO SNORKEL ARM WITH 14" SNORKEL HOOD. BASIS OF
DESIGN - MONOXIVENT MODEL MNX-CDH-100. SERVES 3D PRINTER AND FINISHING
STATION. PROVIDE WITH BLAST GATE DAMPER. REFER TO DETAIL 2/M-501.
5 SOLDERING IRON. LOCATION SHOWN FOR TEMPORARY STORAGE. WHEN IN USE,
SOLDERING PROCESS TO BE PERFORMED INSIDE ONE OF THE EXHAUSTED
ENCLOSURES OR THE FUME HOOD.
6 10" DIA EXHAUST DROP DOWN TO ADA FUME HOOD. PROVIDE BLAST GATE DAMPER.
CONNECT TO HOOD WITH FLEXIBLE METAL DUCT. REFER TO DETAIL 3/M-101. FUME
HOOD PROVIDED BY OTHERS
7 PROVIDE 8"DIA RIGID METAL DUCT ALONG WALL DOWN TO LASER. PROVIDE FLEX
DUCT CONNECTION AT LASER. 3 FOOT MAX LENGTH OF FLEX.
8 PROVIDE SUPPLY AIR VALVE AND REHEAT COIL. CONNECT DIGITAL CONTROL TO
BMS.
9 PROVIDE EXHAUST AIR VALVE. CONNECT DIGITAL CONTROL TO BMS.
10 PROVIDE 1-1/2 HR STATIC RATED FIRE DAMPER, TYPE B, AT RATED WALL
PENETRATION. PROVIDE RETAINING ANGLE AND INSTALL PER UL LISTED
INSTALLATION INSTRUCTIONS.
11 FUME FILTER/FAN COMBINATION - FUMEX MODEL FA5. FUME FILTER/FAN BY
OTHERS. MECHANICAL CONTRACTOR TO PROVIDE DUCT AND CONTROL
CONNECTIONS. PROVIDE FLEX DUCT CONNECTIONS AT THE FUME FILTER/FAN 3'
MAX LENGTH FLEX ON INLET AND OUTLET. POWER BY ELECTRICAL CONTRACTOR.
12 EXHAUSTED ENCLOSURE PROVIDED BY OWNER. PROVIDE GLYCOL SMOKE TEST.
AFTER APPROVED TESTING AND BALANCING OF THE PROCESS EXHAUST, CONTACT
EHS, MECHANICAL ENGINEER, BALANCER AND CONTROLS CONTRACTOR WITH TWO
WEEKS NOTICE TO SCHEDULE A GLYCOL SMOKE TEST OF THE EXHAUSTED
ENCLOSURE TO VERIFY THE CAPTURE VELOCITY. PROVIDE VIDEO DOCUMENTING
OF GLYCOL SMOKE TEST. UNSATISFACTORY TESTING WILL REQUIRE REBALANCING
OF THE ENCLOSURE AT THE TIME OF TESTING. INCREASE EXHAUST AIRFLOW AND
CAPTURE VELOCITY AS NECESSAR FOR A SATISFACTORY TEST. SIGN-OFF BY EHS
AND ENGINEER IS REQUIRED AT THE CONCLUSION OF THIS TEST.
13 REBALANCE EXISTING CEILING SUPPLY DIFFUSER TO 328 CFM.
14 PROVIDE NEW FUME HOOD EXHAUST AIR VALVE AND CONNECT TO EXISTING
BUILDING AUTOMATION AND CONTROL SYSTEM. PROVIDE FUME HOOD
CONTROLLER AND SASH POSITION SENSORS.
15 REINSTALL EXISTING CEILING SUPPLY DIFFUSER. PROVIDE WITH MANUAL
BALANCING DAMPER AND BALANCE TO AIRFLOW SHOWN.
16 TRANSITION TO RECTANGULAR NECK DIFFUSER. MODULAR CORE, 2-WAY
DIFFUSER. ADJUST CORE FOR AIR PATTERN SHOWN.
17 REFER TO ARCHITECTURAL DRAWINGS FOR ADA ACCESSIBLE FUME HOOD AND
ADJUSTABLE BASE.
18 FUME HOOD WORK SURFACE SHALL BE 36-INCHES ABOVE FINISH FLOOR FOR
NON-ADA HEIGHT AND 30-INCHES ABOVE FINISH FLOOR FOR ADA HEIGHT.
19 PROVIDE 1-1/2" DRUM TRAP. PROVIDE SUFFICIENT PIPE ON INLET TO ALLOW 6" OF
WORKSURFACE ADJUSMENT.
20 PROVIDE 1-1/4" DRAIN FROM CUP SINK. PROVIDE SUFFICIENT TAILPIECEON OUTLET
TO ALLOW FOR 6" OF WORK SURFACE ADJUSTMENT. DRAIN IS TO BE SLEEVED
WITHIN THE 1-1/2" INLET PIPE PROVIDED ON THE DRUM TRAP.
21 CONNECT 1-1/2" DRAIN TO LAB WASTE PIPING ABOVE SECOND FLOOR CEILING.
CORE DRILL OPENING THROUGH THIRD FLOOR SLAB AS REQUIRED TO ROUTE
PIPING TO SECOND FLOOR. PROVIDE 2-HR RATED PENETRATION SYSTEM. FIELD
VERIFY PENETRATION LOCATION AND COORDINATE WITH EXISTING
STRUCTURE/UTILITES. CUP SINK AND HOOD BY OTHERS.
22 PROVIDE 1-1/4" VENT SERVING CUP SINK DRAIN. ROUTE PIPING ALONG WALL
ADJACENT TO FUME HOOD AND CONNECT TO EXISTING 2" LAB VENT PIPING ABOVE
CEILING.
23 COORDINATE INSTALLATION OF DUCT WITH SUSPENDED LAY-IN ACOUSTICAL
CEILING SYSTEM. PROVIDE OPENING THROUGH TILE/GRID SUFFICIENT FOR THE
ROUNE ROUND DUCTWORK PENETRATION.
24 FLEXIBLE EXHAUST DUCT SHALL BE FLEXHAUST BENDWAY-PLUS OR EQUAL, 316Ti
STAINLESS STEEL, 10-INCH ROUND NOMINAL DIMENSION.
25 FUME HOOD LAB SERVICES CONNECTIONS. PROVIDE STAINLESS STEEL FLEXIBLE
CONNECTIONS TP PRE-PIPED
26 PROVIDE DUCT ACCESS DOOR AT REHEAT COIL FOR INSPECTION AND
MAINTENANCE.
27 PROVIDE MANUAL VENTILATION SHUTOFF SWITCH, BASIS OF DESIGN PILLA
ELECTRICAL ST120. SWITCH SHALL BE LABELED "VENTILATION SYSTEM
EMERGENCY SHUTOFF". CONNECT TO CONTROLS OF ALL SUPPLY AND EXHAUST
AIR VALVES SERVING 330. CONTROL CONTRACTOR TO PROVIDE LOW VOLTAGE
CONTROL WIRE ALONG WALL SURFACE INSIDE ROOM 330. SURFACE RACEWAY
SHALL BE WIREMOLD 700. FIRESTOP CONDUIT PENETRATION IN WALL AND
MAINTAIN WALL RATING.
28 DROP 8" DIA EXHAUST AIR DUCT DOWN TO FLOOR. TERMINATE 12" AFF WITH 1/2"
ALUMINUM MESH. BALANCE TO 200 CFM WITH GENERAL EXHAUST VALVE IS SET TO
MAX FLOW PER AIRFLOW SCHEDULE.
29 CONTROL CONTRACTOR TO PROVIDE THE LASER POWER RELAY CAT. NO. RIBU1C
AT LOCATION SHOWN. COORDINATE WITH THE ELECTRICAL CONTRACTOR TO RUN
NEAREST 120V POWER TO THE DEVICE. LOW VOLTAGE WIRING BY THE CONTROL
CONTRACTOR. SURFACE REACEWAY FOR THE 120V POWER SHALL BE A WIREMOLD
700.
30 DROP 6" DIA SUPPLY AIR DUCT DOWN TO FLOOR. TERMINATE 12" AFF WITH 1/2"
ALUMINUM MESH. BALANCE TO 100 CFM WHEN SUPPLY VALVE IS SET TO MAX FLOW
PER AIRFLOW SCHEDULE.
31 PROVIDE RATED DUCT WRAP SYSTEM ON 12" EXHAUST DUCT, FIREMASTER
FASTWRAP OR EQUAL. INSTALL ONE LAYER PER MANUFACTURER'S UL LISTED
INSTALLATION INSTRUCTIONS.
32 INSTALL FIRE RATED THROUGH PENETRATION SYSTEM PER DETAIL 3/M-501R1
33 PROVIDE HOUSING AND FIRE WRAP EXISTING EXHAUST VALVE. PROVIDE ACCESS
TO ACTUATOR AND CONTROLS. REFER TO DETAIL 5/M-501R1.
34 PROVIDE 24x16, 1-1/2 HR STATIC RATED FIRE DAMPER, TYPE A. INSTALL WITH
RETAINING ANGLE AND PER UL LISTED INSTRUCTIONS. REINSTALL SUPPLY GRILLE.
35 PROVIDE DUCT ACCESS TO FIRE DAMPER.
36 PROVIDE 1-1/2 HR COMBINATION FIRE SMOKE DAMPER, CLASS I LEAKAGE. PROVIDE
WITH RETAINING ANGLE AND 120V ACTUATOR. CIRCUIT TO NEAREST 120V POWER.
WIRE TO EXISTING AREA SMOKE DETECTION SYSTEM AND FIRE ALARM CONTROL
PANEL. REFER TO ELECTRICAL DRAWINGS FOR CONNECTIONS TO FIRE ALARM
SYSTEM.
37 PROVIDE OPENING IN EXISTING CONCRETE DECK AS REQUIRED TO EXTEND
STAINLESS STEEL EXHAUST DUCT UP TO PENTHOUSE. INSTALL FIRE RATED
THROUGH PENETRATION SYSTEM PER DETAIL 4/M-501.
38 2" 304 STAINLESS STEEL EXHAUST PIPE AND FITTINGS, BUTT WELD ENDS, SERIES
23, 0.065" WALL THICKNESS, MKS MODEL 100314306 OR EQUAL.
SCALE:1/4" = 1'-0"1 PARTIAL THIRD FLOOR HVAC DEMOLITION PLAN
SCALE:1/4" = 1'-0"2 PARTIAL THIRD FLOOR HVAC CONSTRUCTION PLAN
SCALE:1/2" = 1'-0"3 ADA FUME HOOD ELEVATION
1 07/24/2020 ISSUE FOR DD REVIEW
2 08/14/2020 ISSUE FOR 90% CD REVIEW
3 09/4/2020 ISSUE FOR CONSTRUCTION
4 10/06/20 ISSUE FOR ADDENDUM NO. 1
0' 1' 2' 4'
SCALE: 1/2"=1'-0"
4
SCALE:1/8" = 1'-0"4 PARTIAL FOURTH FLOOR HVAC CONSTRUCTION PLAN
4
GENERAL NOTE:
ALL PIPE AND DUCT WALL PENETRATIONS ARE TO
BE FIRE STOPPED OR PROTECTED BY THE
APPROPIRATE LIFE-SAFETY DAMPERS AS
INDICATED.
4
4
4
4
SUPPLY RETURN
ISOLATION
VALVE (TYP. OF 2)
BALANCING
VALVE
PRESSURE/TEMPERATURE
TEST PORT (TYP. OF 2)
MANUAL
AIR VENT
COIL
CV-330-RH
3RD FLOOR
34' -0"
3RD FLOOR
34' -0"
6" EA ON WALL
4" CONNECTION
WALL MOUNTING
BRACKET
4" LOCAL EXHAUST
EXTRACTION ARM.
BASIS OF DESIGN -
MONOXIVENT MODEL
MHX-CDH-100
WALL (E)
LAB BENCH
(E)
CEILING (E)
14" DOME HOOD
EXTRACTION ARM COORDINATION:
OFFSET LOCATION OF WALL BRACKET AND
EXTRACTION ARM MOUNTING AS
RECOMMENDED BY THE MANUFACTURER AND
AS NECESSARY FOR PROPER REACH OF THE
HOOD TO THE 3D PRINTER AND FINISHING
STATION.
FIELD/SHOP FABRICATED
ENCLOSURE. SHEET STEEL
MIN 24 GA.
ONE LAYER OF FIRE RATED DUCT
ENCLOSURE WRAP. FIREMASTER
FASTWRAP OR EQUAL.
12ø EA
12" DIA FUME
HOOD EA (E)
EXHAUST AIR VALVE
SERVING 328 (E)
CONTROL PANEL (E)
RATED ACCESS DOOR TO CONTROL
PANEL AND ACTUATOR. FACTORY
PROVIDED, UL LISTED OR FIELD
FABRICATED ACCORDING TO DUCT WRAP
MANUFACTURER'S UL LISTED
INSTRUCTIONS.
2" 304 SS
BLAST GATE
VACUUM PUMP
(BY OTHERS)
FLEX TUBING,
PITCH DOWN
(BY OTHERS)
WORK SURFACE
3/4" THREADED SIGHT
GLASS. JOHN C. ERNST
MODEL 120 OR EQUAL
3/4" THREADED BALL VALVE.
MILWAUKEE MODEL 20SS OR EQUAL
2" WELDED 304 SS
VAC PUMP EXHAUST
PIPE
2" FLANGED OUTLET CORN E LL U N I V
E
RSI
TYFOU
N
D E D 5681
AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
343 CAMPUS ROAD
ITHACA, NEW YORK 14850
DUFFIELD HALL
330 LAB
RENOVATIONS
M-501R1
12672500
SCHEDULES AND
DETAILS
E. LEPORE
TRF
2000
SEPTEMBER 4, 2020
DUCT SCHEDULE AND SPECIFICATIONS
SERVICE PRESSURE CLASS SEAL CLASS LEAKAGE CLASS DUCT MATERIAL LINING DUCT INSULATION
SUPPLY, RECTANGULAR, EXPOSED, AHU - VAV (EXPOSED IN UTILITY
CORRIDOR)
4" POS A 6 G90 GALVANIZED NONE MIN R-6, TYPE B, WITH VAPOR RETARDER, PAINT
SUPPLY, RECTANGULAR, CONCEALED (ABOVE DROP CEILING)4" POS A 6 G90 GALVANIZED NONE MIN R-6, TYPE A WITH VAPOR RETARDER
SUPPLY, RECTANGULAR, CONCEALED, TERMINAL UNIT - OUTLET 2" POS A 6 G90 GALVANIZED NONE MIN R-6, TYPE A WITH VAPOR RETARDER
SUPPLY, ROUND, CONCEALED, TERMINAL UNIT - OUTLET 2" POS A 3 G90 GALVANIZED NONE MIN R-6, TYPE A WITH VAPOR RETARDER
EXHAUST: LABORATORY - ACCESSIBLE LOCATIONS AND RISERS 4" NEG A RECT 6/ROUND 3 316 STAINLESS STEEL, WELDED NONE N/A
EXHAUST: FUME HOOD - CONNECTION OF DUCT TO MAIN 4" NEG A RECT 6/ROUND 3 316 STAINLESS STEEL, WELDED NONE N/A
AIRFLOW SCHEDULE
LAB
ROOM DIMENSIONS EXHAUST AIR
SUPPLY
POINT
OCC SASH OPEN
(100 FPM)
OCC SASH OPEN
(80 FPM)
OCC SASH
CLOSED
UNOCC SASH
FULL
UNOCC SASH
OPEN
UNOCC SASH
CLOSED ALL MODESAREA (SF) HEIGHT (FT) EXHAUST POINT VALVE
OCC SASH OPEN (100
FPM)
OCC SASH OPEN
(80 FPM)
OCC SASH
CLOSED
OCC LASER
OFF
UNOCC SASH
FULL
UNOCC
SASH OPEN
UNOCC SASH
CLOSED
330 536 10 4' ADA FUME HOOD EAV-330-1 495 CFM 395 CFM 140 CFM 190 CFM 495 CFM 322 CFM 140 CFM SAV-330 1549 CFM 1549 CFM 1549 CFM 747 CFM 574 CFM 574 CFM -200 CFM
GENERAL EXHAUST EAV-330-2 150 CFM 250 CFM 505 CFM 805 CFM 50 CFM 50 CFM 50 CFM
PROCESS EXHAUST EAV-330-3 754 CFM 754 CFM 754 CFM 754 CFM 402 CFM 402 CFM 402 CFM
LASER EXHAUST EAV-330-4 350 CFM 350 CFM 350 CFM 0 CFM 0 CFM 0 CFM 0 CFM
TOTAL LAB 1749 CFM 1749 CFM 1749 CFM 1749 CFM 947 CFM 774 CFM 774 CFM
CONTROL VALVE SCHEDULE & SPEC
TAG BOD MANF
BOD VALVE
MODEL SERVICE VALVE TYPE
VALVE SIZE
(IN)CV ACTUATOR MODEL CONTROL
CAPACITY
(GPM)PD (PSIG) FAIL POS
CV-330-RH1 BELIMO CCV - B213 RHC-330-1 2-WAY 1/2 1.9 TR24-SR-T US MOD 2.2 1.3 F.L.
1. ACCEPTABLE MANUFACTURERS: BELIMO, VSI
2. ELECTRIC INPUT: 4-20mA OR 0-10VDC
3. 2-WAY VALVES: EQUAL PERCENTAGE FLOW CHARACTERISTIC
4. CONSTRUCTION: CHARACTERIZING DISK, FORGED BRASS, NICKEL PLATED BODY, STAINLESS STEEL BALL AND STEM, FIBERGLASS REINFORCED PTFE SEAT
5. RATINGS: 400 PSI PRESSURE, 0-212 F MEDIA TEMPERATURE RANGE
6. ALL CONTROL WIRING SHALL BE INSTALLED IN CONDUIT.
7. CONTROL WIRING SHALL BE UNSPLICED FROM THE CONTROLLER TO THE SENSOR OR DEVICE.
8. CONTROL WIRING SHALL NOT BE ROUTED IN THE SAME RACEWAY AS POWER WIRING.
9. CONTROL WIRING SHALL BE COLOR CODED AND LABELED AT ALL POINTS OF TERMINATION.
10. TEST EACH POINT THROUGH IT FULL OPERATING RANGE TO VERIFY THAT SAFETY AND OPERATING CONTROL SET POINTS ARE AS REQUIRED.
11. TEST EACH CONTROL LOOP TO VERIFY STABLE MODE OF OPERATION AND COMPLIANCE WITH SEQUENCE OF OPERATION. ADJUST PID ACTIONS AS REQUIRED.
12. THE BACS CONTRACTOR SHALL ISSUE A REPORT UPON PROJECT COMPLETION STATING THAT THE SYSTEM IS COMPLETE, HAS BEEN ADJUSTED, AND HAS HAD ALL HARDWARE AND
SOFTWARE FUNCTIONS VERIFIED, THAT ALL ANALOG CONTROL LOOPS ARE TUNED, AND IS OPERATING IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. ANY DEVIATIONS FROM
SPECIFIED SETTINGS OR OPERATIONS NECESSITATED DURING SYSTEM ADJUSTMENT SHALL BE SPECIFICALLY NOTED.
AIR VALVE SCHEDULE & SPECS
TAG # SERVES SUP EXH
BASIS OF DESIGN
SIZE
DESIGN CFM ΔPT @
MAX
DESIGN
CFM
REHEAT COIL
TAG
DAMPER
POSITIONMANF MODEL MAX MIN
EAV-330-1 330 LAB - FUME HOOD X ACCUVALVE AVC6308-05-WS 8" 495 140 0.6 N.O.
EAV-330-2 330 LAB - GENERAL EXH X ACCUVALVE AVC6310-05-WS 10" 805 50 0.6 N.O.
EAV-330-3 330 LAB - PROCESS X ACCUVALVE AVC6310-05-WS 10" 804 402 0.6 N.O.
SAV-330-1 330 LAB - SUPPLY AIR X ACCUVALVE AVC6414-05-IWS 14" 1549 574 0.6 RHC-330 N.C.
EAV-330-4 330 LAB - LASER X ACCUVALVE AVC6408-05-WS 8" 350 80 0.6 N.O.
1. THE AIRFLOW DEVICES SHALL BE CALIBRATED AT THE FACTORY TO THE FULL RANGE OF RECOMMENDED AIRFLOWS. ACTUAL AIRFLOWS WILL BE SET IN SOFTWARE.
2. SETPOINTS REPRESENT FUME HOOD FACE VELOCITY AT 100 FPM. FINAL SETPOINTS WILL BE ADJUSTED IF FACE VELOCITIES ARE REDUCED TO 80 FPM AS A RESULT OF FUME
HOOD TESTING AND CERTIFICATION.
3. ACCEPTABLE MANUFACTURERS: ACCUTROL
4. CONFIGURATION: PRESSURE INDEPENDENT.
5. SUPPLY VALVE BODY: 16GA ALUMINUM, INSULATED.
6. HOOD EXHAUST VALVE BODY: 20 GA 316 STAINLESS STEEL.
7. INSTALLATION: LEVEL AND PLUMB, PER NFPA 90A, SMACNA DUCT CONSTRUCTION STANDARDS, AND MANUFACTURERS RECOMMENCED INSTRUCTIONS.
8. PROVIDE ALL VALVES WITH TIGHT SHUT-OFF OPTION.
1. ALL DUCTWORK AND ACCESSORIES SHALL BE FABRICATED AND INSTALLED IN COMPLIANCE WITH THE LATEST ISSUE OF SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS -METAL AND FLEXIBLE.
2. CONSTRUCT TEES, BENDS, AND ELBOWS WITH RADIUS OF NOT LESS THAN 1.0 TIMES THE WIDTH OF DUCT ON CENTER LINES.
3. WHERE RECTANGULAR ELBOWS ARE USED, PROVIDE AIR FOIL TYPE TURNING VANES
4. INCREASE DUCT SIZES GRADUALLY, AND IN COMPLIANCE WITH FIGURE 4-7 OF SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS -METAL AND FLEXIBLE.
5. BRANCH CONNECTIONS SHALL BE MADE WITH A 45 DEGREE ENTRY. STRAIGHT TEES ARE NOT ACCEPTABLE.
6. SEALANTS AND GASKETS: SURFACE BURNING CHARACTERISTICS SHALL BE A MAXIMUM FLAME-SPREAD INDEX OF 25, AND MAXIMUM SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED TO UL 723.
7. ALL MANUAL BALANCING DAMPERS SHALL BE PROVIDED WITH LOCKING HAND QUADRANT.
8. ACCESS DOORS SHALL MATCH DUCT MATERIAL WITH INSULATION FILL AND THICKNESS AS INDICATED FOR DUCT PRESSURE CLASS.
9. ACCESS DOORS SHALL BE INSTALLED IN THE FOLLOWING LOCATIONS: BOTH SIDES OF DUCT COILS IN ORDER TO RESET OR REINSTALL FUSIBLE LINKS, AND AS INDICATED.
10. INSTALL VOLUME DAMPERS AT POINTS ON SUPPLY AND EXHAUST SYSTEMS WHERE BRANCHES EXTEND FROM LARGER DUCTS.
11. PAINT ALL DUCTWORK EXPOSED TO VIEW IN OCCUPIED AREAS TO MATCH SURROUNDING FINISH.
12. REMOVE SURFACE CONTAMINANTS AND DEPOSITS FROM DUCTWORK AND EQUIPMENT PRIOR TO TESTING AND BALANCING.
13. LEAK TESTING OF DUCTWORK SHALL BE IN ACCORDANCE WITH SMACNA'S HVAC AIR DUCT LEAKAGE TEST MANUAL.
14. ALL DUCTS DESIGNED TO OPERATE AT STATIC PRESSURES IN EXCESS OF 3-INCHES WG (POS OR NEG) SHALL BE TESTED. TEST SHALL BE WITNESSED BY A DESIGNATED CORNELL REPRESENTATIVE AND THE PROJECT
ENGINEER OF RECORD. 25% OF DUCTS DESIGNED TO OPERATE AT STATIC PRESSURES 3-INCHES AND BELOW SHALL BE TESTED.
ACCEPTANCE CRITERIA: INTERIOR SUPPLY, RETURN AND GENERAL EXHAUST: 5% SYSTEM LEAKAGE TESTED AT 1.25 TIMES THE EXPECTED OPERATING STATIC PRESSURE.
ACCEPTANCE CRITERIA: INTERIOR LABORATORY EXHAUST SYSTEMS: 2% SYSTEM LEAKAGE TESTED AT 1.25 TIMES THE EXPECTED OPERATING STATIC PRESSURE.
AN AIR DUCT LEAKAGE TEST SUMMARY SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO FINAL PROJECT ACCEPTANCE.
15. ALL INSULATION AND ADHESIVE SHALL HAVE A MAXIMUM FLAME-SPREAD INDEX OF 25 AND A MAXIMUM SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED IN ACCORDANCE WITH ASTM E84.
16. INSULATION TYPE A: MINERAL FIBERGLASS BLANKET, ASTM C553 TYPE I, ASTM C1136 TYPE I FACTORY APPLIED FSK JACKET, K-VALUE BETWEEN 0.22 -0.29 BTU-IN/HR-FT²-˚F @ 75 ˚F, 0.75 PCF
1. COORDINATE WITH CORNELL EH&S DURING FUME HOOD TESTING AND CERTIFICATION. REDUCTION IN THE FUME HOOD FACE VELOCITY TO 80 FPM MAY BE POSSIBLE.
HVAC PIPE AND FITTING SCHEDULE AND SPECIFICATIONS
PIPE SERVICE ABBREVIATION PIPE SIZE MATERIAL FITTINGS JOINT INSULATION
HEATING HOT WATER HWS&R 1-1/2" & BELOW ASTM B88 TYPE L COPPER ASTM B16.22 STD WROUGHT COPPER ASTM B32 SOLDER 1", TYPE A WITH VAPOR RETARDER
GRILLE SCHEDULE
MARK SERVES MANUFACTURER (BOD) MODEL (BOD) TYPE AIRFLOW DUCT SIZE SPECIFICATIONS
SD4-330 (E) LAB 330 EXISTING EXISTING EXISTING 329 CFM 10ø EXISTING
SD5-330 LAB 330 KRUEGER SERIES 51240 MODULAR CORE 136 CFM 6ø 24"X24" PANEL SIZE, 8"X8" NECK, ALUMINUM WITH WHITE FINISH
1. ACCEPTABLE MANUFACTURERS: ANEMOSTAT, CARNES, KRUEGER, PRICE, TITUS.
REHEAT COIL SCHEDULE
TAG
COIL SIZE WxH
(IN)ROWS
TOTAL CAPACITY
(BTUH)
AIR SIDE WATER SIDE
FLOW RATE (CFM)
ENT AIR TEMP
(˚F)
LVG AIR TEMP
(˚F)
AIR PRESSURE DROP
(IN WC)
FOW RATE
(GPM)
ENT WATER TEMP
(˚F)
LVG WATER
TEMP(˚F)
WATER PRESSURE DROP (FT
WC)
RHC-330 24x12 2 33,458 1549 55 75 0.55 2.2 130 100 3.0
1. ACCEPTABLE MANUFACTURERS: GREENHECK, ANEMOSTAT, KRUEGER, NAILOR, TITUS, TRANE, PRICE TO COORDINATE WITH AIR TERMINAL BOX.
2. RATINGS: ARI 410, INDUSTRY STANDARD FOR FORCED CIRCULATION AIR COOLING AND AIR HEATING COILS
3. 1/2-IN COPPER TUBING WITH MECHANICALLY BONDED ALUMINUM FINS.
4. SUPPLY PIPING TO COIL TO BE PIPED WITH SHUT OFF VALVE, STRAINER, CONTROL VALVE AND UNION.
5. RETURN PIPING TO COIL TO BE PIPED WITH SHUT-OFF VALVE, BALANCING VALVE, AND UNION.
6. COIL SHALL BE PIPED IN COUNTERFLOW ARRANGEMENT.
7. PIPING SHALL BE ARRANGED TO ALLOW SERVICE AND MAINTENANCE.
NOT TO SCALE1REHEAT COIL PIPING DETAIL
1 07/24/2020 ISSUE FOR DD REVIEW
2 08/14/2020 ISSUE FOR 90% CD REVIEW
3 09/4/2020 ISSUE FOR CONSTRUCTION
4 10/06/20 ISSUE FOR ADDENDUM NO. 1
SCALE:1/2" = 1'-0"2 EXTRACTION ARM DETAIL
FIRE AND SMOKE DAMPER SCHEDULE
TAG LOCATION MANF BOD MODEL BOD TYPE SIZE WxH (IN)
TEMP RATING
(DEG F)
FIRE RATING SMOKE RATING
NOTESHOURS UL HOURS UL
FD-1 LAB 330 GREENHECK FD-150 STATIC, TYPE A 24x16 165 1-1/2 1-1/2 N/A N/A GALVANIZED, FUSIBLE LINK, VERTICAL MOUNTING
FD-2 LAB 330 GREENHECK SSFD-150X16 STATIC, TYPE B 20x16 165 1-1/2 1-1/2 N/A N/A 304 STAINLESS STEEL, FUSIBLE LINK, VERTICAL MOUNTING
FD-3 LAB 330 GREENHECK SSFD-150X16 STATIC, TYPE B 12X12 165 1-1/2 1-1/2 N/A N/A 304 STAINLESS STEEL, FUSIBLE LINK, VERTICAL MOUNTING
FD-4 LAB 330 GREENHECK SSFD-150X16 STATIC, TYPE CR 8 165 1-1/2 1-1/2 N/A N/A 304 STAINLESS STEEL, FUSIBLE LINK, VERTICAL MOUNTING
FSD-1 LAB 330 GREENHECK FSD-311 COMBINATION FIRE SMOKE 18x14 165 1-1/2 1-1/2 1-1/2 1-1/2 GALVANIZED STEEL, ACTUATED, VERTICAL MOUNTING
FSD-2 LAB 330 GREENHECK FSD-311 COMBINATION FIRE SMOKE 8 165 1-1/2 1-1/2 1-1/2 1-1/2 GALVANIZED STEEL, ACTUATED, VERTICAL MOUNTING
1. ACCEPTABLE MANUFACTURERS: GREENHECK, NAILOR, RUSKIN
2. RATINGS: UL 555
3. FRAME: 20 GAUGE STEEL CHANNEL, WITH MITERED AND INTERLOCKING CORNERS
4. MOUNTING SLEEVE: FACTORY FURNISHED, MINIMUM 20 GAUGE.
5. BLADES: 24 GAUGE THICKNESS.
6. INSTALLATION: INSTALL FIRE DAMPERS IN ACCORDING TO UL LISTING AND MANUFACTURERS RECOMMENDED INSTRUCTIONS.
7. PROVIDE ACCESS TO FUSIBLE LINK, EITHER WITH DUCT ACCESS DOOR, OR THRU THE WALL GRILLE
4
NOT TO SCALE3RATED WALL DUCT PENETRATION DETAIL
NOT TO SCALE4RATED FLOOR DUCT PENETRATION DETAIL
4
4
SCALE:1/2" = 1'-0"5 VALVE ACCESS ENCLOSURE DETAIL
ENCLOSURE NOTES:
FABRICATED CUSTOM ENCLOSURE TO HOUSE
THE EXISTING FUME HOOD EXHAUST VALVE
SERVING ROOM 328. THE PURPOSE OF THIS
ENCLOSURE IS TO MAINTAIN OPERATION AND
ACCESS TO THE EXHAUST VALVE
SCALE:1/2" = 1'-0"6 VACUUM PUMP CONNECTION DETAIL
4
4
4
3
3 F330
2
1
OS
OS
S
330
4
3
8
8
330
(3)
(3)
(3)
(3)
(3)
(3)
(3)(3)(3)
(3)(3)
WIREMOLD 4000
WIREMOLD 4000
WIREMOLD 4000
EXISTING PHONE JACK
EXISTING PANEL
LPP-312, 208Y/120V
EXISTING PENDANT
POWER & DATA
RACEWAY
1
2
5
6
GFCI GFCI GFCI GFCI
7
9
COMBINATION
FIRE SMOKE
DAMPER
9
COMBINATION
FIRE SMOKE
DAMPER
4
4
NOTE: IN ADDITION TO THE REMOTE TEST
STATION AND STATUS ANNUNCIATION FOR THE
SMOKE DETECTOR, A REMOTE TEST STATION
AND STATUS ANNUNCIATION SHOULD BE
PROVIDED FOR THE DAMPER AS WELL.CORN E LL U N I V
E
RSI
TYFOU
N
D E D 5681
AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
343 CAMPUS ROAD
ITHACA, NEW YORK 14850
DUFFIELD HALL
330 LAB
RENOVATIONS
E-101R1
12672500
POWER, DATA,
LIGHTING, AND
FIRE ALARM
PARTIAL THIRD
FLOOR PLAN
H. TRAN
JD
2000
SEPTEMBER 4, 2020
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
E-101 KEYED DEMOLITION NOTES
1 REMOVE LUMINAIRE AS INDICATED AND RETURN LUMINAIRE TO THE OWNER.
MODIFIED EXISTING LIGHTING AS REQUIRED.
2 DURING CONSTRUCTION, PROVIDE A TEMPORARY HEAT DETECTOR IN THIS ROOM.
SCALE:1/4" = 1'-0"1 PARTIAL THIRD FLOOR DEMOLITION
SCALE:1/4" = 1'-0"2 PARTIAL THIRD FLOOR LIGHTING AND FIRE ALARM
SCALE:1/4" = 1'-0"3 PARTIAL THIRD FLOOR POWER & DATA
E-101 KEYED RENOVATION NOTES
1 AT 18" AFF TO TOP OF BOX, PROVIDE A SURFACE MOUNT RECEPTACLE. CIRCUIT
THE RECEPTACLE TO THE NEW FUME HOOD CIRCUITRY. SURFACE RACEWAY
SHALL BE WIREMOLD 700.
2 NEW ADA FUME HOOD BY OTHERS. ELECTRICAL CONTRACTOR TO PROVIDE
POWER CONNECTION. CIRCUIT TO A SPARE 20A/1P CIRCUIT BREAKER LOCATED IN
EXISTING PANEL LPP-312. CONDUIT CONNECTED TO THE FUME HOOD SHALL BE
FLEXIBLE CONDUIT WITH (2) 12 AWG & (1) 12 AWG GROUND.
3 PROVIDE A NEW SURFACE MOUNT LIGHT SWITCH TO CONTROL THE TWO EXISTING
LUMINAIRES LOCATED IN THE NEW CURTAIN. MODIFY THE EXISTING LIGHTING
CIRCUIT AS REQUIRED. CIRCUIT THE LIGHTING SWITCH TO THE EXISTING LIGHTING
CIRCUITRY. SURFACE RACEWAY ON WALL SHALL BE WIREMOLD 700.
4 THE CONTRACTOR TO PURCHASE A TOTAL OF 6 DARK AMBER UV BLOCKING TUBE
GUARD W/ END CAPS CAT. NO. PLAS-T8UVA FROM 1000BULBS.COM. PROVIDE THE
EXISTING LAMPS WITH THE TUBE GUARDS.
5 REPLACE EXISTING RECEPTACLES WITH NEW GFCI RECEPTACLES.
6 AT 18" AFF TO TOP OF BOX PROVIDE A NEW SURFACE MOUNT RECEPTACLE.
CIRCUIT THE RECEPTACLE TO A SPARE 20A/1P CIRCUIT BREAKER LOCATED IN
EXISTING PANEL LPP-312. PROVIDE (2) #12 AWG AND (1) #12 AWG GROUND IN 3/4"
EMT AS REQUIRED.
7 LASER SAFETY LINE VOLTAGE RELAY INSTALL BY THE CONTROL CONTRACTOR.
ELECTRICAL CONTRACTOR TO PROVIDE 120V POWER CONNECTION. CIRCUIT TO
NEAREST 120V RECEPTACLE CIRCUIT. RACEWAY ON WALL SHALL BE WM 700.
8 REMOVE, STORE, AND REINSTALL CEILING MOUNTED EQUIPMENT AS REQUIRED
DURING CEILING REMOVAL TO ACCOMMODATE MECHANICAL WORK.
9 COMBINATION FIRE SMOKE DAMPER WITH REMOTE TEST SWITCH WITH
OPEN/CLOSE INDICATOR LIGHTS BY MECHANICAL CONTRACTOR. ELECTRICAL TO
PROVIDE 120V POWER CONNECTION AND FIRE ALARM CONNECTION. CIRCUIT THE
ACTUATOR TO NEAREST 120V POWER CIRCUITRY. REFER TO FIRE/SMOKE DAMPER
CONTROL CIRCUIT WIRING ON THIS SHEET FOR FIRE ALARM WORK
REQUIREMENTS. REFER TO MECHANICAL DRAWINGS FOR FIRE SMOKE DAMPER.
#
1 07/24/2020 ISSUE FOR DD REVIEW
2 08/14/2020 ISSUE FOR 90% REVIEW
3 09/04/2020 ISSUE FOR CONSTRUCTION
4 10/06/20 ISSUE FOR ADDENDUM NO. 1
SCALE:NO SCALE4FIRE/SMOKE DAMPER CONTROL CIRCUIT WIRING DIAGRAM
4
4
PROJECT: Duffield Hall 330 Lab Renovations Date: October 6, 2020
RFI Form
RFI/Page/
Response Dwg./Spec./Rep.Section/Design Team
Index Number Paragraph/Topic RFI Response
1 A-101 What species are the wood items (oak, maple, etc.)?See Addendum 1, Item 3.
2 P-001 Lab waste and vent piping calls for polyproplyne schedule 40
pipe with stainless steel compression fittings, is this correct?"
See Addendum 1, Item 7.