HomeMy WebLinkAboutMORRILL HALL B06 LINGUISTICS LAB RENOVATION 100% CD SETCB
CB
CB
CB
CB
CB
CB
CB
CB
CBCBCBCB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CBCB
MONUMENT PLATFORM
FP
SIGN
180210
187 272
412
249
151
646
70390
53
178
333
80
109
18
199
485 244
1047
28
27
160
189
383
B09B12
B13 B14
B11
B15
B10
B00UD
B00S
B00UC
B00UE
B00UB
B00L
B00E
B00CA
B04B06
B07A B08
B01
B02
B07B
B07
B00UA B00J
NOACCESS
NOACCESS
UP
DN
DN
DN
DN
AREA OF WORK
MORRILL
HALL
2001
EXTERIOR ELEVATION
1
X-100
X-100
1
1 INTERIOR ELEVATION
1
X-100
SECTION MARKER
1
X-100 ENLARGED DETAIL
CONSTRUCTION KEYED NOTE
DEMOLITION KEYED NOTE
DRAWING REVISION NOTE
LINETYPE: TO BE PROVIDED / NEW
LINETYPE: DEMOLITION / TO BE RELOCATED
LINETYPE: EXISTING TO REMAIN
#
#
#
1
1
1
11
AREA OF WORK
T-001 TITLE SHEET
ARCHITECTURAL
A-001 GENERAL NOTES, SYMBOLOGY, ABBREVIATIONS AND CODE COMPLIANCE PLAN
A-101 DEMOLITION, RENOVATION, AND REFLECTED CEILING PLANS
A-601 SCHEDULES
MECHANICAL
M-001 GENERAL NOTES AND SYMBOL LEGENDS
M-101 BASEMENT MECHANICAL REMOVAL & CONSTRUCTION PLANS & CONTROLS
M-501 SCHEDULES & DETAILS
ELECTRICAL
E-001 GENERAL NOTES AND SYMBOL LEGENDS
E-101 ELECTRICAL DEMOLITION & RENOVATION PLANS
E-501 SCHEDULES
FIRE PROTECTION
FP-101 FIRE PROTECTION REMOVAL & INSTALLATION PLANS & SCHEDULESCORNE
LL U N I V
E
R
SI
TYFOUN
D E D 5681
AD CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
Cornell University
159 CENTRAL AVE
ITHACA, NEW YORK 14850
MORRILL HALL
B06 LINGUISTICS
LAB RENOVATION
T-001
12715689
TITLE SHEET
FE DESIGN
JGC
2001
SEPTEMBER 14, 2020
MORRILL HALL B06 LINGUISTICS LAB RENOVATION
BUILDING CODE SUMMARY
APPLICABLE CODES
2020 NYS BUILDING CODE
2020 NYS EXISTING BUILDING CODE
2020 NYS FIRE CODE
2020 NYS PLUMBING CODE
2020 NYS MECHANICAL CODE
2020 NYS ENERGY CONSERVATION CODE
2009 ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
2010 AMERICANS WITH DISABILITY ACT (ADA)
PROJECT SUMMARY
THIS PROJECT INCLUDES THE RENOVATION OF 485 SF OF LABORATORY AND
OFFICE SPACES.
ALTERATION LEVEL 2:
LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE,
THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE
RECONFIGURATION OR EXTENSION OF ANY SYSTEM, OR THE INSTALLATION
OF ANY ADDITIONAL EQUIPMENT. AN EXISTING BUILDING OR PORTION
THEREOF SHALL NOT BE ALTERED SUCH THAT THE BUILDING BECOMES
LESS SAFE THAN ITS EXISTING CONDITIONS.
BUILDING LIMITATIONS
CONSTRUCTION CLASSIFICATION:3B
CLASSIFICATION OF HAZARDS:NONE
HIGH-RISE BUILDING:NO
EXTINGUISHING REQUIREMENT:THE EXISTING BUILDING
IS FULLY SPRINKLERED
OCCUPANCY
OCCUPANCY CLASSIFICATION:ASSEMBLY (A-3)/ BUSINESS (B)
GENERAL SYMBOLS LEGEND
DRAWING INDEX
PROJECT SCOPE
THE PURPOSE OF THIS PROJECT IS TO RENOVATE THE CURRENT GRAD SPACE (ROOM B06) IN MORRILL HALL AND TURN THE ROOM INTO A LINGUISTICS
LABORATORY. THE MAJORITY OF DEMOLITION AND NEW WORK TAKES PLACE IN ROOM B06, WITH SOME UPGRADES TO THE MECHANICAL, ELECTRICAL,
AND FIRE PROTECTION SYSTEM AS IDENTIFIED IN THIS SET OF DOCUMENTS.
SITE LOCATION -MORRILL HALL 2001
KEY PLAN -BASEMENT
1 08/07/2020 ISSUE FOR 50% REVIEW
2 09/08/2020 ISSUE FOR 95% COORDINATED REVIEW
3 09/14/2020 ISSUE FOR CONSTRUCTION
B09B12
B13 B14
B11
B15
B10
B00UD
B00S
B00UC
B00UE
B00UB
B00L
B00E
B00CA
B04B06
B07A B08
B01
B02
B07B
B07
B00UA B00J
ACCESS
NO
ACCESS
UP
DN
DN
DN
DN
WALL -EXISTING
WALL -METAL STUD/ GWB
WALL -CONCRETE
WALL -CMU
WALL -BRICK
ITEMS FOR DEMOLITION
DOOR/ WALL -EXISTING
DOOR/ WALL -NEW
DOOR/ WALL -DEMOLITION
TAG -DOOR
TAG -WINDOW
TAG -WALL
TAG -ROOM #
CENTER LINE
PHOTO REFERENCE
LEVEL MARKER
COLUMN GRID MARKER
ELEVATION MARKER
ELEVATION CHANGE ARROWS
BREAK LINE
SYMBOLS
0' -0"
101
1t
X-X
X
2B00UA
CL
1
Name
Elevation
A101 1
1
1
0
DN
UP
ABBREVIATIONS
A
&AND
@ AT
ACT ACOUSTICAL CEILING TILE
ALT ALTERNATE
ALUM ALUMINUM
AVG AVERAGE
AFF ABOVE FINISH FLOOR
B
BD BOARD
BLDG BUILDING
BOD BOTTOM OF DECK
BSMT BASEMENT
C
CG CORNER GUARDS
CJ CONTROL JOINT
CLG CEILING
CL CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONT CONTINUOUS
CORR CORRIDOR
CPT CARPET
CRS COURSE(S)
CT CERAMIC TILE
D
DEMO DEMOLITION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DO DOOR OPENING
DWG DRAWING
E
EA EACH
EJ EXPANSION JOINT
ELEC ELECTRIC
ELEV ELEVATION/ ELEVATOR
EPDM RUBBER ROOF MEMBRANE
EQ EQUAL
EX'G EXISTING
EXT EXTERIOR
F
FD FLOOR DRAIN
FDN FOUNDATION
FEC FIRE EXTINGUISHER CABINET
FFE FINISH FLOOR ELEVATION
FRP FIBER REINFORCED POLYESTER
FT FOOT/FEET
FTG FOOTING
G
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERAL
GL GLASS
GWB GYPSUM WALL BOARD
H
HC HANDICAPPED
HT HEIGHT
HM HOLLOW METAL
HR HOUR
HVAC HEATING, VENTILATING & AC
J
JAN JANITOR
L
LAV LAVATORY
LB/#POUND
LGMF LIGHT GAGE METAL FRAMING
M
MFR MANUFACTURER
MAT MATERIAL
MAX MAXIMUM
MEZZ MEZZANINE
MIN MINIMUM
MO MASONRY OPENING
MTL METAL
N
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NR NOT RATED
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OSB ORIENTER STRAND BOARD
P
+/-PLUS OR MINUS
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
Q
QTY QUANTITY
R
R RISER
RD ROOF DRAIN
REF REFRIGERATOR
REQ REQUIRED
REV REVISION
RO ROUGH OPENING
RTU ROOF TOP UNIT
S
SHTG SHEATHING
SIM SIMILAR
SF SQUARE FOOT/ FEET
SS STAINLESS STEEL
STL STEEL
STD STANDARD
T
T TREAD
T&G TONGUE & GROOVE
TEL TELEPHONE
TEMP TEMPERATURE
TOS TOP OF STEEL
TV TELEVISION
TYP TYPICAL
U
UEV UNEVEN DOORS W/ VISION PANEL
UEF UNEVEN FLUSH DOOR
V
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
W
W/O WITHOUT
WD WOOD
INSTALL METAL STUDS
TO UNDERSIDE OF
DECK
METAL STUDS
@ 16" O.C.
METAL RUNNER
CHANNEL SECURED
TO FLOOR
WALL BASE AS
SCHEDULED
WIDTH DIMENSION
VARIES REFER TO
PLAN
5/8" ACOUSTIC GYP.
WALLBOARD
UNDERSIDE OF
METAL DECK ABOVE
ACOUSTIC CEILING
SYSTEM AS
SCHEDULED
CONT. ACOUSTICAL
SEALANT EA. SIDE
ACOUSTIC INSULATION
AS REQUIRED, REFER
TO PARTITION
SCHEDULE
SLIP CLIP STUD
VERTICALS TO TRACK
FOR SLIDING
ATTACHMENT
DEFLECTION TRACK
FASTENED TO DECK
ACOUSTIC INSULATION
AS REQUIRED
GYP. WALLBOARD ON MET. STUDS, ABOVE CEILING
1 1/2" = 1'-0"VERTICAL SPANREFER TO GENERAL NOTE 96"2'-0" TYP.
EA. SIDE
3 5/8", 20 GA METAL STUD
BRACING AT 6' -0" O.C.
UNDERSIDE OF
METAL
DECK ABOVE
ALTERNATE GYP. WALLBOARD ON MET. STUDS ABOVE CEILING
1 1/2" = 1'-0"6"REFER TO GENERAL NOTESVERTICAL SPANMETAL STUDS
@ 16" O.C.
METAL RUNNER
CHANNEL SECURED
TO FLOOR
WALL BASE AS
SCHEDULED
WIDTH DIMENSION
VARIES REFER TO
PLAN
5/8" ACOUSTIC GYP.
WALLBOARDACOUSTIC CEILING
SYSTEM AS
SCHEDULED
CONT. ACOUSTICAL
SEALANT EA. SIDE
ACOUSTIC INSULATION
AS REQUIRED
ACOUSTIC INSULATION
AS REQUIRED
2'-0" TYP.
EA. SIDE
B06A
B06B
TRAVEL DISTANCE TO EXIT: 122 FEET
(IBC 1017.2: MAX 300' WITH
SPRINKLER SYSTEM)
AREA OF WORK CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
159 CENTRAL AVE
ITHACA, NEW YORK 14850
MORRILL HALL
B06 LINGUISTICS
LAB RENOVATION
A-001
12715689
GENERAL
NOTES,
SYMBOLOGY,
ABBREVIATIONS
AND CODE
COMPLIANCE
PLAN
J. COOLBAUGH
JGC
2001
SEPTEMBER 14, 2020
SCOPE OF WORK
1.0 SALVAGE EXISTING DOOR AND REMOVE EXISTING FRAME/WALL.
2.0 REMOVE EXISTING CEILING AND CARPET/ BASE.
3.0 PROVIDE NEW GYPSUM WALL BOARD AND STUD WALLS AS SHOWN.
4.0 PROVIDE NEW DOORS/ FRAMES, CEILING SYSTEM AND CARPET.
GENERAL NOTES
1.0 DESIGN, CONSTRUCTION AND SAFETY SHALL CONFORM TO ALL LOCAL, STATE AND
OWNER SPECIFIC CODES, INCLUDING (BUT NOT LIMITED TO) THE NEW YORK STATE
UNIFORM FIRE PROTECTION AND BUILDING CODE, LATEST REVISION, THE NFPA 101
LIFE SAFETY CODE, LATEST REVISION, ANSI A117.1 - LATEST REVISION, OSHA, AND
ANY OTHER CODES GOVERNED BY THE JURISDICTION IN WHICH THIS PROJECT IS
BEING CONSTRUCTED.
2.0 THIS CONTRACT REQUIRES COMPLETE, FINISHED WORKABLE PROJECT OF THE
AREAS INDICATED BY THE CONTRACT DOCUMENTS, AND SHALL INCLUDE ALL
MATERIALS AND LABOR NECESSARY TO COMPLETE, REGARDLESS OF WHETHER OR
NOT ALL WORK OR EACH ITEM IS SPECIFICALLY INDICATED ON ANY OTHER
PORTION OF THE DRAWINGS AND / OR NOTES.
3.0 WHERE MATERIALS REFERENCED ON DRAWINGS, OR NECESSARY TO COMPLETE
THE WORK OF THIS CONTRACT ARE NOT SPECIFIED HEREIN, PROVIDE BEST
QUALITY MATERIALS. WHERE MATERIALS ARE INTENDED TO MATCH EXISTING,
PROVIDE CLOSEST POSSIBLE MATCH, SUBJECT TO OWNER'S APPROVAL. ALL ITEMS
AND WORK ON DRAWINGS ARE NEW, UNLESS INDICATED EXISTING. ALL WORK
WHICH HAS BEEN DAMAGED SHALL BE REPAIRED OR REPLACED AT NO COST TO
THE OWNER. WHERE ITEMS CAN NOT BE REPAIRED TO A ""NEW CONDITION"", OR
WHERE THE STRUCTURAL INTEGRITY HAS BEEN AFFECTED, ITEMS SHALL BE
REPLACED AT NO COST TO THE OWNER.
4.0 CONTRACTOR IS RESPONSIBLE TO VERIFY ALL SITE, FIELD AND BUILDING
CONDITIONS PRIOR TO SUBMITTING BIDS AND COMMENCING WORK. IF THERE ARE
ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS, NOTIFY THE
PROJECT MANAGER, WHO WILL REQUEST CLARIFICATION FROM THE
ARCHITECT/ENGINEER AND PROVIDE CLARIFICATION IN WRITING.
5.0 WHERE EXISTING CONSTRUCTION OR ITEMS HAVE BEEN INFILLED, REMOVED AND /
OR DISTURBED FOR INSTALLATION OF NEW WORK, CAUSING THE EXPOSURE OF
UNFINISHED AND/OR DAMAGED SURFACES RESULTING SURFACES AND INFILLED
SURFACES SHALL BE RECONSTRUCTED WITH MATERIALS TO MATCH FINISHED
AREAS. ALL ABANDONED OPENINGS (i.e. DUCT/PIPE REMOVALS, ETC.) AT WALLS,
ROOF OR FLOOR TO BE INFILLED SOLID.
6.0 WORK IS REQUIRED IN VARIOUS PORTIONS OF THE FACILITY TO EXECUTE WORK OF
OTHER TRADES (i.e. ELECTRICAL, MECHANICAL). ALTHOUGH NOT NECESSARILY
SHOWN ON DRAWINGS, WORK IS REQUIRED IN THESE AREAS CONSISTING OF
REMOVAL / REPLACEMENT OF CEILINGS, WALLS, FINISHES, PAVEMENT AND OTHER
CONSTRUCTION AS NECESSARY TO PERFORM WORK AND RESTORE THESE
SPACES OR AREAS TO ORIGINAL CONDITION.
7.0 GENERAL CONTRACTOR IS TO COORDINATE WORK OF ALL TRADES. SCHEDULE
WORK PROGRESS THROUGHOUT THE ENTIRE PROJECT TO PREVENT CONFLICTS
AND INTERFERENCES. OBTAIN ALL NECESSARY INFORMATION SUCH AS SIZES,
LOCATIONS, TEMPLATES, LAYOUT, DIMENSIONS AND ALL OTHER INFORMATION
NECESSARY FOR A PROPER AND WELL COORDINATED INSTALLATION. PRIOR TO
INSTALLATION OF ITEMS, VERIFY AND CONFIRM WITH EACH CONTRACTOR EXACT
LOCATION OF ALL ITEMS.
8.0 ALL PENETRATIONS (EXISTING OR NEW) THROUGH FLOORS AND FULL HEIGHT
WALLS - IN AREA OF WORK TO BE FIRE STOPPED. ALL GAPS AND JOINTS AT RATED
FLOORS, ROOFS AND WALLS TO BE FIRE & SMOKE STOPPED. GAPS AND JOINTS
INCLUDE (BUT ARE NOT LIMITED TO) TOP OF WALL TO FLOOR OR ROOF DECK, WALL
TO BEAMS, AND CONTROL OR EXPANSION JOINTS. FIRE STOPPING INCLUDES BOTH
FORM OR PACKING MATERIAL AND THE FILL, VOID OR CAVITY MATERIAL. PROVIDE
AND INSTALL LABELING REQUIRED BY CODE. LABELS SHALL INCLUDE
PENETRATION TYPE WITH UL LISTING USED, MATERIAL USED, DATE INSTALL AND
NAME OF INSTALLER.
9.0 JOBSITE WILL BE CLEANED DAILY AND DEBRIS REMOVED TO CONTAINERS OR TO
VEHICLE WHICH WILL REMOVE DEBRIS FROM CAMPUS. CONTAINERS WILL BE
REMOVED AS SOON AS FULL OR WHEN THE PROJECT HAS PROGRESSED TO A
POINT THAT A CONTAINER IS NO LONGER REQUIRED.
10.0 CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL AREAS USED TO BRING
SUPPLIES AND EQUIPMENT INTO THE PROJECT AREA. ANY DAMAGE TO AREAS
OUTSIDE THE PROJECT AREA INCLUDING BUT NOT LIMITED TO THE LOBBY AND
CORRIDOR SHALL BE REPAIRED AT NO COST TO THE OWNER.
NOT TO SCALE1WALL DETAILS
SCALE:1/8" = 1'-0"2 CODE COMPLIANCE PLAN - BASEMENT
1 08/07/2020 ISSUE FOR 50% REVIEW
2 09/08/2020 ISSUE FOR 95% COORDINATED REVIEW
3 09/14/2020 ISSUE FOR CONSTRUCTION
0' 4' 8'16'
SCALE: 1/8"=1'-0"
B07
B04
B07B
B00CA
1
2
3
5
V.I.F.
3' - 11 3/4"
5
5
4
2 1' - 0" MIN.23' - 4 3/8"1' - 6 7/8"11"1' - 0" MIN.5' - 9 5/8" +/-1' - 0" MIN.8' - 2 1/2"3' - 8 7/8"1' - 0" MIN.2
2
5
8' - 7 1/4"3 5/8"6' - 5 5/8"3 5/8"6' - 0 3/4"3 5/8"F.O. EX WALL4' - 1"1
12
9
B06
B07
B00CA
B04
B07B
B06A
B06B
13' - 6"3 5/8"
F.O. EX WALL TO STUD
9' - 6 3/4"B06AB06B B06FROM F.O. EX WALL TO STUD
10' - 2"3 5/8"
FROM F.O. EX WALL TO STUD
12' - 10 3/4"
3
5
3
2
3
3
3
10
10 2
3
4 CLEAR3' - 6"2
11
12
12
12
11
11
11
11
11
11
13
14
14
14
14
PRELIMINARY
LAYOUT FOR
TOP OF WALL
BRACING.
COORDINATE
IN FIELD.
8
8
8
6
B07
B00CA
B07B
B04
B06
7
7' - 7 1/2"
7' - 7 1/2"
7' - 7 1/2"
7' - 7 1/2"
EX. SPRINKLER PIPE
IN EX. SOFFIT.
PROVIDE BLOCKING
FOR NEW WALL.
PROVIDE 3 1/2"
ACOUSTICAL
INSULATION
ABOVE CEILING/
WALLS, SEE
DETAIL 1/A-001.CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
159 CENTRAL AVE
ITHACA, NEW YORK 14850
MORRILL HALL
B06 LINGUISTICS
LAB RENOVATION
A-101
12715689
DEMOLITION,
RENOVATION,
AND REFLECTED
CEILING PLANS
J. COOLBAUGH
JGC
2001
SEPTEMBER 14, 2020
A-101 KEYED RENOVATION NOTES
1 REINSTALL SALVAGED DOOR AND HARDWARE IN NEW HOLLOW METAL FRAME.
REFER TO DOOR SCHDULED FOR MORE INFORMATION.
2 PROVIDE ONE LAYER OF 5/8" GYPSUM WALL BOARD OVER ONE LAYER OF 5/8"
SILENT FX GYPSUM WALL BOARD (BY CERTAINTEED OR APPROVED EQUAL)
ATTACHED TO EXISTING METAL STUDS. PROVIDE 3 1/2" ACOUSTIC BATT INSULATION
BETWEEN EXISTING STUDS, IF NOT CURRENTLY PRESENT.
3 PROVIDE 3 5/8” 20GA METAL STUDS AT 16” O.C. WITH 5/8" SILENT FX GYPSUM WALL
BOARD (BY CERTAINTEED OR APPROVED EQUAL) BOTH SIDE OF WALL AND 3 1/2"
ACOUSTIC BATT INSULATION. EXTEND WALL 6” ABOVE FINISH CEILING.
4 PROVIDE 3 5/8” 20GA METAL STUDS AT 16” O.C. WITH 5/8" SILENT FX GYPSUM WALL
BOARD (BY CERTAINTEED OR APPROVED EQUAL) ONE SIDE OF WALL AND 3 1/2"
ACOUSTIC BATT INSULATION. EXTEND WALL 6” ABOVE FINISH CEILING.
5 PROVIDE ONE LAYER OF 5/8" SILENT FX GYPSUM WALL BOARD (BY CERTAINTEED
OR APPROVED EQUAL) ATTACHED TO EXISTING METAL STUDS. PROVIDE 3 1/2"
ACOUSTIC BATT INSULATION BETWEEN EXISTING STUDS.
6 PROVIDE USG MARS HIGH NRC/ HIGH CAC CEILING TILES AND USG DX/ DXL GRID.
7 MODIFY EXISTING OPEN HEAD TO PROVIDE A 7' - 0" HEIGHT. PATCH ALL AREAS WITH
NEW GYPSUM WALL BOARD AND PAINT TO MATCH EXISTING.
8 PROVIDE USG MARS HIGH NRC/ HIGH CAC CEILING TILES AND USG DX/ DXL GRID.
PROVIDE 3 1/2" OF BATT INSULATION AT EACH NEW WALL FOR AT LEAST 2' - 0".
REFER TO DETAIL ON A-001 FOR MORE INFORMATION ABOUT THE SOUND BATT.
9 PATCH EXISTING WALL WITH LIKE THICKNESS AND MATERIALS. MATCH EXISTING
ADJACENT CONDITIONS.
10 PROVIDE 3 5/8” 20GA METAL STUDS AT 16” O.C. WITH ONE LAYER OF 5/8" GYPSUM
WALL BOARD OVER ONE LAYER OF 5/8" SILENT FX GYPSUM WALL BOARD (BY
CERTAINTEED OR APPROVED EQUAL) ONE SIDE OF WALL AND 3 1/2" ACOUSTIC
BATT INSULATION. EXTEND WALL 6” ABOVE FINISH CEILING.
11 EXISTING WALL TO REMAIN. PATCH EXISTING WALL TO MATCH EXISTING ADJACENT
CONDITIONS WHERE ITEMS WERE REMOVED.
12 PATCH EXISTING WALL TO MATCH EXISTING ADJACENT CONDITIONS WHERE BLOCK
WAS INSTALLED.
13 FILL ALL VOIDS IN EXISTING CONCRETE/ MASONRY WALL WITH MINERIAL WOOL.
THIS INCLUDES ALL PENETRATIONS IN WALL.
14 PROVIDE NEW CARPET TILE AND VINYL BASE. COLOR AS SELECTED BY OWNER.
#
A-101 KEYED DEMOLITION NOTES
1 SALVAGE EXISTING DOOR AND HARDWARE FOR REUSE IN NEW FRAME. REMOVE
EXISTING FRAME AND WALL. WALL TO BE REMOVED TO A HEIGHT OF 7' - 0".
2 REMOVE EXISTING GYPSUM WALL BOARD TO THE DIMENSION GIVEN TO PROVIDE
BLOCKING FOR NEW WALL.
3 REMOVE EXISTING CEILING SYSTEM IN ITS ENTIRITY.
4 REMOVE EXISTING CARPET AND BASE IN ITS ENTIRITY.
5 REMOVE EXISTING GYPSUM WALL BOARD. EXISTING STUDS TO REMAIN.
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
SCALE:1/4" = 1'-0"1 DEMOLITION PLAN
SCALE:1/4" = 1'-0"2 RENOVATION PLAN
SCALE:1/4" = 1'-0"3 REFLECTED CEILING PLAN
A-101 GENERAL DEMOLITION NOTES
1.0 FIELD VERIFY ALL DIMENSIONS PRIOR TO THE START OF DEMOLITION.
10.CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS PRIOR TO THE START OF
DEMOLITION.
2.0 COORDINATE REMOVALS WITH ALL ASSOCIATED TRADES PRIOR TO DEMOLITION.
3.0 REPAIR ANY DAMAGED SUSTAINED TO ADJACENT EXISTING CONDITIONS DURING
THE REMOVAL OF EXISTING BUILDING ELEMENTS.
A-101 GENERAL RENOVATION NOTES
1.0 PATCH FLOORS WHERE WALLS HAVE BEEN DEMOLISHED TO MATCH EXISTING SLAB
ELEVATION AND PREP FOR NEW FLOOR FINISH. REFER TO ROOM FINISH SCHEDULE
FOR NEW FLOOR FINISHES.
2.0 ALL DIMENSIONS ARE TO THE FACE OF STUD UNLESS OTHERWISE NOTED.
3.0 ALL WALLS ARE TO BE SANDED, PRIMED AND PAINTED (2 COATS). PATCH ALL
EXISTING WALLS TO REMAIN PRIOR TO PRIMING AND PAINTING.
4.0 RUN NEW JAMB STUDS AT DOORS TO DECK. PROVIDE DEFLECTION TRACK.
PROVIDE METAL STUD KICKERS EVERY 6' - 0" O.C.
3' - 0"6' - 8"3' - 0"6' - 8"F F-1 CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
159 CENTRAL AVE
ITHACA, NEW YORK 14850
MORRILL HALL
B06 LINGUISTICS
LAB RENOVATION
A-601
12715689
SCHEDULES
J. COOLBAUGH
JGC
2001
SEPTEMBER 14, 2020
SUBMITTAL REGISTRY
SECTION DESCRIPTION
03 54 00 - CAST UNDERLAYMENT FLOOR LEVELER
07 92 00 - SEALANTS
08 11 13 - HOLLOW METAL DOORS AND FRAMES DOORS AND FRAMES
08 71 00 - DOOR HARDWARE LOCKSETS, HINGES, AND CLOSERS
09 68 13 - TILE CARPETING CARPET TILE AND VINYL BASE
09 91 23 - INTERIOR PAINTING LATEX PAINT FOR WALLS, DOORS AND FRAMES
ROOM FINISH SCHEDULE
NUMBER
FLOOR
BASE
WALLS CEILING
KEYED NOTESMAT FIN
NORTH SOUTH EAST WEST
MAT FINMAT FIN MAT FIN MAT FIN MAT FIN
B00CA EX CONC. EX CT/ CPT-2 EX CT/ VB EX GYP - EX GYP/ GYP PT-1 - - EX GYP PT-1 EX/ ACT -
B06 EX CONC. CPT-1 VB EX GYP/ GYP PT-1 GYP PT-1 EX GYP/ GYP PT-1 EX GYP PT-1 ACT -
B06A EX CONC. CPT-1 VB GYP PT-1 GYP PT-1 GYP PT-1 GYP PT-1 ACT -
B06B EX CONC. CPT-1 VB GYP PT-1 GYP PT-1 GYP PT-1 GYP PT-1 ACT -
DOOR / HARDWARE SCHEDULE
DOOR
DOOR FRAME
FIRE RATINGHARDWARE DETAILS
NOTESDOOR LOCATION HAND
PANEL SIZE
ELEVATION TYPEMATERIALFINISHELEVATION TYPEMATERIALFINISHHEAD DIM.HINGES MCKINNEY TA2714 4.5 X 4.5 X 26D SARGENT 8205 X LNL X 26D X RHSARGENT 8205 X LNL X 26D X LHRESTRICTED CYLINDER PROVIDED BY THE EN ZONES LOCKSMITHNGP 107NA X ADJUSTABLE PERIMETER SEALS X DOOR PERIMETERNGP 420NA X DOOR WIDTH INSTALL HALF MORTICECLOSER SARGENT 351 X O X EN X 120 DEGREE WALL BUMPERS DCI 3211T X US26DSILENCERS DCI 8SHEAD JAMB# OF PANELSWIDTHHEIGHTTHICKNESSB06 B00CA TO B06 LH (1) 3' - 0" 6' - 8" 1 3/4" EX EX PT-2 F-1 HM PT-2 2" - EX EX EX EX - - EX 1 3 1
B06A B06 TO B06A RH (1) 3' - 0" 6' - 8" 1 3/4" F HM PT-2 F-1 HM PT-2 2" - 3 1 - 1 1 1 1 1 3 2
B06B B06 TO B06B LH (1) 3' - 0" 6' - 8" 1 3/4" F HM PT-2 F-1 HM PT-2 2" - 3 - 1 1 1 1 1 1 3 2
NOT TO SCALE1DOOR & FRAME ELEVATIONS NOTES:
1. DOOR B06, REINSTALL EXISTING DOOR AND HARDWARE.
2. INSTALL THE AUTO DOOR BOTTOM HALF MORTICE.
1 08/07/2020 ISSUE FOR 50% REVIEW
2 09/08/2020 ISSUE FOR 95% COORDINATED REVIEW
3 09/14/2020 ISSUE FOR CONSTRUCTION
PT-1 PAINT -INTERIOR WALLS:
BENJAMIN MOORE, COLOR: 912 "LINEN WHITE"
INTERIOR WALLS: EGGSHELL
PT-2 PAINT -DOOR & FRAMES -MATCH EXISTING COLOR
BENJAMIN MOORE, COLOR: XXXX "XXX", SEMI-GLOSS
CPT-1 CARPET TILE -PRO-CARPET -TBD
CPT-2 CARPET TILE -PRO-CARPET -TBD
VB VINYL BASE -TBD
ACT -USG MARS HIGH NRC/ HIGH CAC SQUARE EDGE CEILING TILE WITH USG DX/ DXL GRID
CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
159 CENTRAL AVE
ITHACA, NEW YORK 14850
MORRILL HALL
B06 LINGUISTICS
LAB RENOVATION
M-001
12715689
GENERAL NOTES
AND SYMBOL
LEGENDS
A. FOX
ALF
2001
SEPTEMBER 14, 2020
MECHANICAL ABBREVIATIONS
BCU BLOWER COIL UNIT
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CC CLEAN CONDENSATE
CO CLEAN OUT
CS CLEAN STEAM
CD CONDENSATE DRAIN
EA EXHAUST AIR
EAG EXHAUST AIR GRILLE
FD FIRE DAMPER
GWR GLYCOL HEATING RETURN
GWS GLYCOL HEATING SUPPLY
HPR HIGH PRESSURE STEAM RETURN
HPS HIGH PRESSURE STEAM SUPPLY
HWR HOT WATER HEATING RETURN
HWS HOT WATER HEATING SUPPLY
LPC LOW PRESSURE CONDENSATE
LPS LOW PRESSURE STEAM
MU MAKE UP WATER
MPC MEDIUM PRESSURE CONDENSATE
MPS MEDIUM PRESSURE STEAM
NG NATURAL GAS
PCWR PROCESS CHILLED WATER RETURN
PCWS PROCESS CHILLED WATER SUPPLY
HG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
RAG RETURN AIR GRILLE
SA SUPPLY AIR
SAD SUPPLY AIR DIFFUSER
VD VOLUME DAMPER
MECHANICAL SYMBOLOGY
AIRFLOW
BACKFLOW PREVENTER
BALANCE VALVE
BALL VALVE
BOTTOM PIPE CONNECTION
BUTTERFLY VALVE
CAP OR PLUG
CHECK VALVE
CIRCULATING PUMP
DIRECTION OF FLOW
DUCT AIRFLOW
DUCT DOWN (EXHAUST OR RETURN)
DUCT DOWN (SUPPLY)
FIRE AND SMOKE DAMPER IN DUCT
FIRE DAMPER IN DUCT
FLANGE CONNECTION
FLEX CONNECTOR
FLEXIBLE CONNECTION
FLEXIBLE DUCT
FLOW METER
FLOW SWITCH
FUSIBLE LINK VALVE
GLOBE VALVE
MANUAL AIRVENT
ORIFICE METER
PIPE DOWN
PIPE UP
PIPING REDUCER (CONCENTRIC)
PIPING REDUCER (ECCENTRIC)
PRESSURE GAUGE
PRESSURE OR TEMPERATURE PETES PLUG
PRESSURE REDUCING VALVE
PRESSURE SWITCH
RECTANGULAR ELBOW
RECTANGULAR ELBOW WITH TURNING VANES
RELIEF VALVE
SMOKE DAMPER IN DUCT
SOLENOID VALVE
STANDARD BRANCH DUCT
STEAM TRAP
STRAINER (DUPLEX)
STRAINER WITH BLOWDOWN VALVE AND CAP
SUPPLY THROUGH NEXT FLOOR OR ROOF
TEMPERATURE WELL
THERMOMETER
THERMOMETER (DIAL)
TOP PIPE CONNECTION
TRIPLE DUTY VALVE
UNION CONNECTION
VACUUM BREAKER
VOLUME DAMPER IN DUCT
CONTROL SYMBOLOGY
2-WAY CONTROL VALVE, DIGITAL
2-WAY CONTROL VALVE, PNEUMATIC
3-WAY CONTROL VALVE, DIGITAL
3-WAY CONTROL VALVE, PNEUMATIC
ADDRESSABLE OUTPUT MODULE (FIRE ALARM INTERFACE)
AIRFLOW CONTROL VALVE (VENTURI OR VORTEX SHEDDING)
AVERAGING SENSOR
BINARY POINT
BUTTERFLY CONTROL DAMPER
CARBON DIOXIDE SENSOR
CONDENSATE SENSOR
CURRENT SENSOR
DEW-POINT SENSOR
DIFFERENTIAL PRESSURE SENSOR
DIFFERENTIAL PRESSURE SENSOR
ELECTRIC TO PNEUMATIC SWITCH
ELECTRIC TO PNEUMATIC TRANSDUCER
END SWITCH
FLOW ELEMENT (METER)
FLOW SENSOR
HIGH LEVEL SWITCH
HUMIDSTAT SENSOR
LIQUID IMERSION TEMPERATURE SENSOR
LOW LEVEL SWITCH
MODULATING
MOTOR
MOTOR STARTER
NETWORK COMMUNICATION POINT, BACnet MSTP
OCCUPANCY SENSOR
OPEN/CLOSE
OPPOSED BLADE CONTROL DAMPER
PARALLEL BLADE CONTROL DAMPER
PNEUMATIC THERMOSTAT
PRESSURE SENSOR
PRESSURE SWITCH
RELATIVE HUMIDITY SENSOR
RELAY
ROOM TEMPERATURE SENSOR WITH ADJUSTABLE
THERMOSTAT
ROOM TEMPERATURE SENSOR WITH OCCUPANCY
OVERRIDE
ROOM TEMPERATURE SENSOR WITH ON/OFF SWITCH
ROOM TEMPERATURE SENSOR WITH VISUAL DISPLAY
ROTATION DETECTOR
SINGLE POINT SENSOR
SMOKE DETECTOR
SPEED COMMAND
START/STOP
STATIC PRESSURE SENSOR
SWITCH
TEMPERATURE SENSOR
TEMPERATURE SENSOR
TEMPERATURE SENSOR WITH ADJUSTABLE SETPOINT
GENERAL DRAWING SYMBOLOGY
DEMOLISHED WORK
EXISTING PIPING TO REMAIN
EXISTING TO REMAIN
EXISTING WORK TO REMAIN
NEW WORK
POINT OF CONNECTION
POINT OF DISCONNECTION
CONTROL ABBREVIATIONS
AI ANALOG INPUT
AO ANALOG OUTPUT
AV ANALOG VALUE
BI BINARY INPUT
BO BINARY OUTPUT
BV BINARY VALUE
F.L. FAIL LAST
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
VFD VARIABLE FREQUENCY DRIVE
MECHANICAL SCOPE OF WORK
1.0 RECONFIGURE DIFFUSERS FOR NEW LINGUISTICS LABS (B06A & B06B).
2.0 PROVIDE NEW VAV SERVING THE TWO NEW LINGUISTICS LABS.
MECHANICAL GENERAL NOTES
1.0 ALL DUCT DIMENSIONS INDICATED ARE IN INCHES, AND ARE INSIDE FREE AND
CLEAR DIMENSIONS.
2.0 PNEUMATIC TERMINATIONS:
IF COPPER: DEMO BACK TO MAIN AND PROVIDED SOLDERED END CAP
IF POLY: DEMO BACK TO MAIN AND PROVIDE BRASS PLUG
DO NOT USE SHEETMETAL SCREW OR BEND OVER END OF COPPER TUBE.
3.0 INSTALL EQUIPMENT TO ENSURE PROPER ACCESS TO CONTROL DEVICES AND
WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE AND REPAIR.
EQUIPMENT THAT IS NOT INSTALLED WITH THIS REQUIREMENT IN MIND SHALL BE
RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIES ARE
CORRECTED.
4.0 ALL SYSTEM TESTING SHALL BE CONDUCTED PRIOR TO INSULATION,
FIREPROOFING, AND ENCLOSURE IN SHAFTS. ANY RESTORATION WORK REQUIRED
AS A RESULT OF DISTURBING FINISHES OR STRUCTURE IN ORDER TO ACCESS
SYSTEMS REQUIRING REPAIR SHALL BE AT NO COST TO THE UNIVERSITY.
5.0 CUTTING AND PATCHING: THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
CUTTING, FITTING, AND PATCHING TO COMPLETE THE WORK. WHERE EXISTING
CONSTRUCTION IS REMOVED, CAUSING AN EXPOSURE OF UNFINISHED AND/OR
DAMAGED SURFACES, RESULTING SURFACES SHALL BE RECONSTRUCTED WITH
MATERIALS TO MATCH FINISHED AREAS.
6.0 ANY FIRESTOPPING DISTURBED DURING THE COURSE OF WORK SHALL BE
REPAIRED TO MAINTAIN A 2-HOUR FIRE RATING.
7.0 TESTING AND BALANCING: THE CONTRACTOR SHALL BALANCE ALL AIR SYSTEMS
AS INDICATED. SUBMIT RESULTS OF TESTING AND BALANCING ON STANDARD TAB
CONTRACTOR'S FORMS TO THE ENGINEER FOR REVIEW. SYSTEMS SHALL BE
BALANCED TO WITHIN +/- 10% OF DESIGN VALUES. FINAL BALANCING SHALL OCCUR
AFTER ALL LEAKS IN THE BUILDING ENVELOPE HAVE BEEN IDENTIFIED AND
SEALED.
8.0 SEAL ALL PIPE, GRILLE, DIFFUSER, DUCT, CONDUIT PENETRATIONS WITH
APPROPRIATE MATERIALS (CAULK, FOAM, ETC,) THAT ARE IMPENETRABLE TO THE
CONTAINED ORGANISMS AND WITHSTAND REPEATED DECONTAMINATIONS WITH
CLEANING AGENTS.
2 08/07/20 ISSUE FOR 50% REVIEW
3 08/31/20 ISSUE FOR COORDINATED REVIEW
4 09/14/20 ISSUE FOR CONSTRUCTION
B00UB
B06
B07
B04
48x10 SA (E)48x10 SA (E)48x10 RA (E)26x10 RA (E)48x10 SA (E)14X6 RA (E)
1
DISCONNECT AT
EXISTING SUPPLY
DUCT
48X14 RA (E)48X14 RA (E)1
1
2
2
T
3
4
B00UB
B06
B07
B04
48x10 SA (E)48x10 SA (E)48x10 RA48x10 SA (E)T
T
1
1
2
2
2
3
48X14 RA (E)48X14 RA (E)SD-2
SD-2
SD-1
SD-1
RG-1
VAV-B06
PROVIDE ACCOUSTIC
INSULATION AROUND
OUTSIDE OF DUCTWORK (AS
SHOWN WITH DOTTED LINE)
OFFSET ABOVE
SUPPLY DUCT
OFFSET DOWN
BETWEEN SUPPLY
DUCT AND BEAM
RG-1 2
RG-2
14"X6" RA (E)
4
B06A
B06B
5
6
VD
VD
VD
VD
7
8
2" HWS/R
(E)
8
CV-RHC1
T
9
CV-FTB06
SYSTEM DESCRIPTION
RHC-1 (E)
VAV-B06
GENERAL
SYSTEM SHALL BE CONTROLLED THROUGH THE BUILDING AUTOMATION AND CONTROL
SYSTEM (BACS).
ALL SETPOINTS SHALL BE ADJUSTABLE.
THE BACS SHALL BE CAPABLE OF STARTING AND STOPPING THE SYSTEM FOR SEVEN
DIFFERENT DAILY SCHEDULES PER WEEK.
THE BACS SHALL BE CAPABLE OF RETAINING ITS PROGRAMMING AND TIME SETTING
DURING A LOSS OF POWER FOR AT LEAST TEN HOURS.
EXISTING LGR IS LOCATED IN THE BASEMENT MECHANICAL ROOM..
DESIGN INTENT: THE NEW VAV (VAV-B06) AND ASSOCIATED REHEAT COIL (RHC-B06)
SHALL CONTROL THE AIR BEING DELIVERED TO SPACES B06A AND B06B. EACH SPACE
SHALL UTILIZE A WALL MOUNTED, COMBINATION TEMPERATURE SENSOR/OCCUPANCY
SENSOR. THE WALL MOUNTED TEMPERATURE SENSORS SHALL BE AVERAGED TO
DETERMINE SPACE TEMPERATURE. IN THE EVENT THAT ONE SPACE IS OCCUPIED AND
THE OTHER IS NOT, THE TEMPERATURE SENSOR IN THE OCCUPIED SPACE SHALL BE
SOLELY USED TO DETERMAINE SPACE TEMPERATURE.
SETPOINTS
SPACE COOLING TEMPERATURE SETPOINTS:
OCCUPIED:72°F +/-2°F
UNOCCUPIED:75°F +/-4°F
SPACE HEATING TEMPERATURE SETPOINTS:
OCCUPIED:72°F +/-2°F
UNOCCUPIED:70°F +/-4°F
ZONE OCCUPANCY SCHEDULE: 6 AM TO 8 PM, MON-FRI
SPACE OCCUPANCY
ZONE OCCUPANCY SHALL BE DETERMINED BASED ON A TIME OF DAY SCHEDULE AND
OCCUPANCY SENSORS.
ZONE TEMPERATURE CONTROL
OCCUPIED HEATING B06: THE FIN TUBE IS THE MAIN SOURCE OF HEAT IN B06. THE FIN
TUBE CONTROL VALVES SHALL MODULATE AS NECESSARY TO MAINTAIN OCCUPIED
HEATING SETPOINT. IF THE TEMPERATURE DROPS BELOW SETPOINT, REHEAT COIL
(RHC-1) CONTROL VALVE SHALL MODULATE AS NECESSARY TO MEET AND MAINTAIN
SETPOINT.
OCCUPIED HEATING B06A & B06B: IF THE TEMPERATURE DROPS BELOW HEATING
SETPOINT, THE REHEAT COIL CONTROL VALVE SHALL MODULATE AT NECESSARY TO
MEET AND MAINTAIN SETPOINT.
OCCUPIED COOLING B06: SPACE COOLING SHALL BE PER EXISTING SEQUENCE.
OCCUPIED COOLING B06A & B06B: SPACE COOLING SHALL BE PER EXISTING
SEQUENCE.
UNOCCUPIED HEATING B06: THE FIN TUBE IS THE MAIN SOURCE OF HEAT IN B06. THE
FIN TUBE CONTROL VALVES SHALL MODULATE AS NECESSARY TO MAINTAIN
UNOCCUPIED HEATING SETPOINT. IF THE TEMPERATURE DROPS BELOW SETPOINT,
REHEAT COIL (RHC-1) CONTROL VALVE SHALL MODULATE AS NECESSARY TO MEET
AND MAINTAIN SETPOINT.
UNOCCUPIED HEATING B06A & B06B: IF THE TEMPERATURE DROPS BELOW SETPOINT,
THE REHEAT COIL CONTROL VALVE SHALL MODULATE AT NECESSARY TO MEET AND
MAINTAIN SETPOINT.
UNOCCUPIED COOLING: SPACE COOLING SHALL BE PER EXISTING SEQUENCE.
SEQUENCE OF OPPERATIONBACnet / ARCNET
OR BACnet / MSTP
AV: FLOW FEEDBACK (CFM)
AV: POSITION FEEBACK (%)
AV: FLOW SETPOINT (CFM)MOD
AO
COM
AV
SETPOINT
AI
T
T
AI
sa
d
VAV-B06
FROM AHU-1
B06A B06BB06
AV
SETPOINT
T
AI
sa
d
AV
SETPOINT
T
AI
sa
d
RHC-B06
THERMOSTATS TO
INCLUDE
OCCUPANCY
SENSOR (TYPICAL
FOR ALL).
F.L.
AO
F.L.
AO
CV-B06
F.L.
AO
CV-RHC1
RHC-1 (E)CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
159 CENTRAL AVE
ITHACA, NEW YORK 14850
MORRILL HALL
B06 LINGUISTICS
LAB RENOVATION
M-101
12715689
BASEMENT
MECHANICAL
REMOVAL &
CONSTRUCTION
PLANS &
CONTROLS
A. FOX
alf
2001
SEPTEMBER 14, 2020
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
M-101 KEYED DEMOLITION NOTES
1 REMOVE EXISTING DUCT AND DIFFUSERS
2 DISCONNECT HOT WATER SUPPLY AND RETURN FROM EXISTING REHEAT COIL AND
PREPARE FOR RECONNECTION TO NEW VAV/REHEAT COIL.
3 DISCONNECT AND REMOVE EXISTING JOHNSON CONTROLS THERMOSTAT.
REPLACE WITH NEW.
4 DISCONNECT AND REMOVE EXISTING FIN TUBE CONTROL VALVE AND REPLACE
WITH NEW. FIELD VERIFY LOCATION. PRIOR TO REMOVING VALVE, PRE-READ GPM
FOR BALANCING OF NEW VALVE.
#M-101 KEYED RENOVATION NOTES
1
PROVIDE NEW WALL MOUNTED THERMOSTAT (BOD: AUTOMATED LOGIC ZSPRO-M).
AVERAGE THERMOSTATS. OCCUPANCY SENSOR (INTEGRATED IN THERMOSTAT)
SHALL DICTATE THERMOMETER PRIORITY.
2 PROVIDE NEW SUPPLY AIR DIFFUSER AND RETURN AIR GRILLES. COORDINATE
NEW DIFFUSERS AND GRILLED WITH REFLECTED CEILING PLAN.
3 PROVIDE NEW VAV TO SERVE B06A AND B06B.
4 PROVIDE NEW WALL MOUNTED THERMOSTAT (BOD: AUTOMATED LOGIC ZS PRO-M).
MAINTAIN EXISTING LOGIC AND SEQUENCE OF OPERATION.
5
RECONNECT EXISTING 3/4" REHEAT COIL PIPING TO NEW REHEAT COIL.
REFERENCE DETAIL 2 ON M-501 FOR COMPONENTS AND INSTALLATION. VERIFY
EXISTING PIPE SIZES IN FIELD.
6 CONNECT NEW RETURN DUCT TO RETURN MAIN.
7 CONNECT NEW SUPPLY DUCT TO EXISTING SUPPLY MAIN.
8 REPLACE EXISTING CONTROL VALVE WITH NEW CONTROL VALVE. BALANCE TO 1.5
GPM.
9 REPLACE EXISTING FIN TUBE CONTROL VALVE WITH NEW. VERIFY LOCATION AND
SIZE IN FIELD.
SCALE:1/4" = 1'-0"1 BASEMENT MECHANICAL REMOVAL PLAN
SCALE:1/4" = 1'-0"2 BASEMENT MECHANICAL CONSTRUCTION PLAN
CONTROL AND ALARM POINTS SCHEDULE
B06, B06A & B06B ZONE CONTROL
HARDWARE POINTS SOFTWARE POINTS SHOW
ON
GRAPHIC
NOTESBI BO AI AO AV BV SCH TREND
ALARM
BACS EMCS DESCRIPTION
REHEAT COIL VALVE POSITION
COMMAND X X X
5 ˚F ΔT ACROSS COIL WITH VALVE
COMMANDED CLOSED X FAIL LAST
REHEAT COIL LEAVING AIR
TEMPERATURE X X X SINGLE POINT
SENSOR
ZONE TEMPERATURE SETPOINT X X X
ZONE TEMPERATURE X X X +/- 4 ˚F FROM SETPOINT X
VAV DAMPER POSITION COMMAND X X X
VAV AIRFLOW FEEDBACK (CFM) X X X 10% FLOW DEVIATION FROM SETPOINT X
BACnet MSTP
NETWORK POINT
VAV AIRFLOW SETPOINT (CFM) X X X BACnet MSTP
NETWORK POINT
VAV POSITION FEEDBACK (%) X X X VALVE COMMAND ≠ FEEDBACK X
BACnet MSTP
NETWORK POINT
BASEBOARD RADIATION CONTROL
VALVE POSITION COMMAND X X X FAIL LAST
NOT TO SCALE3B06, B06A &B06B ZONE CONTROL
2 08/07/20 ISSUE FOR 50% REVIEW
3 08/31/20 ISSUE FOR COORDINATED REVIEW
4 09/14/20 ISSUE FOR CONSTRUCTION
SUPPLY RETURN
ISOLATION VALVE (V-1)
BALANCE
VALVE
(BV-B06)
PRESSURE/TEMPERATURE
TEST PORT (PT-1)
MANUAL
AIR VENT
(AV-1)
REHEAT COIL
(RHC-B06)
STRAINER BLOWDOWN
WITH BRASS HOSE
CONNECTION, CAP WITH
CHAIN (S-1)COIL DRAIN WITH
BRASS HOSE
CONNECTION, CAP
AND CHAIN (TYP.)
CONTROL
VALVE CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
159 CENTRAL AVE
ITHACA, NEW YORK 14850
MORRILL HALL
B06 LINGUISTICS
LAB RENOVATION
M-501
12715689
SCHEDULES &
DETAILS
A. FOX
ALF
2001
SEPTEMBER 14, 2020
DUCT SCHEDULE AND SPECIFICATIONS
SERVICE PRESSURE CLASS SEAL CLASS LEAKAGE CLASS DUCT MATERIAL LINING DUCT INSULATION
SUPPLY RECTANGULAR, CONCEALED 2" POS A 1" POS G90 GALVANIZED NONE TYPE A
RETURN RECTANGULAR, CONCEALED 2" NEG A 1" NEG G90 GALVANIZED NONE NONE
SUPPLY RECTANGULAR, CONCEALED (EXISTNG MAIN-NOTED ON FLOOR
PLAN)
NA NA NA NA NA TYPE E
PIPING ACCESSORIES SCHEDULE AND SPECIFICATIONS
TAG DEVICE
BOD
MANUFACTURER MODEL PRESSURE RATING SPECIFICATIONS
BV-B06 BALANCE VALVE 1 INCH BELL & GOSSETT CB SERIES, CB 1 200 PSIG @ 250 DEGF 1.5 - 6.0 GPM RANGE, BRONZE, BALL OR PLUG TYPE BODY WITH CALIBRATED ORIFICE OR VENTURI; GLASS AND CARBON FILLED
TFE OR EPDM SEAT RINGS, EPDM STEM O-RING, WITH INTEGRAL SEALS FOR PORTABLE DIFFERENTIAL PRESSURE METER, WITH
LEVEL HANDLE AND MEMORY STOP TO RETAIN SET POSITION.
V-1 SHUT-OFF BALL VALVE WATTS B6000-SS 300 PSIG WOG MSS SP-110, 2-PIECE, STANDARD PORT, BRONZE BODY, 316 SS BALL & STEM, PTFE OR TFE SEAT
PT-1 PRESSURE/TEMPERATURE
TEST PORT
TRERICE D3769 500 PSIG @ 200 DEGF COLD/CHILLED WATER SERVICE: BRASS BODY & CAP, 1/2 NPT CONNECTION, NEOPRENE SEAT, GASKETED AND THREADED CAP
WITH RETENTION CHAIN
S-1 STRAINER, WYE PATTERN WATTS SERIES 777 200 PSIG @ 210 DEGF
WOG
BRONZE BODY, #20 MESH 304 STAINLESS STEEL SCREEN, THREAD OR SWEAT CONNECTION.
AV-1 AIR VENT BELL & GOSSETT MODEL 87 150 PSIG BRASS BODY, NON-FERROUS INTERNALS
CV-B06 CONTROL VALVE BELIMO B210, 1/2", 1.2 CV NA TF24-SR US BELIMO ACTUATOR, 2-WAY PROPORTIONAL, SPRING RETURN
CV-RHC1 CONTROL VALVE BELIMO B210, 1/2", 1.2 CV NA TF24-SR US BELIMO ACTUATOR, 2-WAY PROPORTIONAL, SPRING RETURN
CV-FTB06 CONTROL VALVE BELIMO B210, 1/2", 1.2 CV NA TF24-SR US BELIMO ACTUATOR, 2-WAY PROPORTIONAL, SPRING RETURN
DIFFUSER SCHEDULE
MARK SERVES MANUFACTURER MODEL
FACE SIZE
(IN)
NECK SIZE
(IN)
AIRFLOW
(IN)
TYPE
(IN)MOUNTING NOTES
RG-1 B06A, B06B TITUS TDC 24X24 8 100 CFM
LOUVERED
FACE LAYIN CEILING
RG-2 B06 TITUS TDC 24X24 8 100 CFM
LOUVERED
FACE LAYIN CEILING
SD-1 B06A, B06B TITUS TDC 24X24 8 100 CFM
LOUVERED
FACE LAYIN CEILING
SD-2 B06 TITUS TDC 24X24 8 100 CFM
LOUVERED
FACE LAYIN CEILING
VAV BOX W/REHEAT COIL SCHEDULE & SPECS
UNIT NO. SERVES VALVE TYPE MANF BOD MODEL BOD UNIT SIZE
AIR SIDE REHEAT COIL
NOTESMAX CFM MIN CFM
MIN ΔPt
(IN WC)
DAMPER
POSITION
FLOW
RATE
(GPM)
WATER
PRESSURE
DROP
(FT WC)
BALANCE
VALVE
CONTROL
VALVE
VAV-B06 B06A, B06B SUPPLY NAILOR D31RW 5 200 0 0.1 N.O. 1.5 1.5 BV-BO6 CV-B06
SPECS:
1 ALL DUCTWORK AND ACCESSORIES SHALL BE FABRICATED AND INSTALLED IN COMPLIANCE WITH THE LATEST ISSUE OF SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS -METAL AND FLEXIBLE.
2 CONSTRUCT TEES, BENDS, AND ELBOWS WITH RADIUS OF NOT LESS THAN 1.0 TIMES THE WIDTH OF DUCT ON CENTER LINES.
3 WHERE RECTANGULAR ELBOWS ARE USED, PROVIDE AIR FOIL TYPE TURNING VANES.
4 INCREASE DUCT SIZES GRADUALLY, AND IN COMPLIANCE WITH FIGURE 4-7 OF SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS -METAL AND FLEXIBLE.
BRANCH CONNECTIONS SHALL BE MADE WITH A 45 DEGREE ENTRY. STRAIGHT TEES ARE NOT ACCEPTABLE.
5 SEALANTS AND GASKETS: SURFACE BURNING CHARACTERISTICS SHALL BE A MAXIMUM FLAME-SPREAD INDEX OF 25, AND MAXIMUM SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED TO UL 723.
6 ALL MANUAL BALANCING DAMPERS SHALL BE PROVIDED WITH LOCKING HAND QUADRANT.
7 ACCESS DOORS SHALL BE GALVANIZED SHEETMETAL WITH INSULATION FILL AND THICKNESS AS INDICATED FOR DUCT PRESSURE CLASS.
ACCESS DOORS SHALL BE INSTALLED IN THE FOLLOWING LOCATIONS: BOTH SIDES OF DUCT COILS, ADJACENT TO FIRE/SMOKE DAMPERS IN ORDER TO RESET OR REINSTALL FUSIBLE LINKS, AND AS
INDICATED.
8 CONNECT DIFFUSERS TO SUPPLY DUCTS WITH MAXIMUM OF 36-INCHES OF FLEXIBLE DUCT CLAMPED OR STRAPPED IN PLACE.
9 PROVIDE FLEXIBLE CONNECTORS TO CONNECT DUCTS TO EQUIPMENT.
10 INSTALL VOLUME DAMPERS AT POINTS ON SUPPLY, RETURN, AND EXHAUST SYSTEMS WHERE BRANCHES EXTEND FROM LARGER DUCTS.
11 REMOVE SURFACE CONTAMINANTS AND DEPOSITS FROM DUCTWORK AND EQUIPMENT PRIOR TO TESTING AND BALANCING.
12 ALL INSULATION AND ADHESIVE SHALL HAVE A MAXIMUM FLAME-SPREAD INDEX OF 25 AND A MAXIMUM SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED IN ACCORDANCE WITH ASTM E84.
TYPE A INSULATION: MINERAL FIBERGLASS BLANKET, ASTM C553 TYPE I, ASTM C1136 TYPE I FACTORY APPLIED FSK JACKET, K-VALUE BETWEEN 0.22 -0.29 BTU-IN/HR-FT²-˚F @ 75 ˚F, 0.75 PCF.
TYPE E INSULATION: ACOUSTICAL DUCT LAGGING, STC 29
VAV SPECS:
1 ACCEPTABLE MANUFACTURERS: ANEMOSTAT, KRUEGER, NAILOR, TITUS, TRANE, PRICE
2 RATINGS: ARI 880, INDUSTRY STANDARD FOR AIR TERMINALS.
3 CONFIGURATION: PRESSURE INDEPENDENT, CONTROLLER PROVIDED AND MOUNTED IN FIELD.
4 CASING: 22 GA ZINC COATED STEEL.
5 LINING (CU STANDARD): 1/2 INCH, 1.5 PCF FIBERGLASS INSULATION COMPLYING WITH UL 181, UL 723, NFPA 90A, ASTM E84, ASTM C665, WITH PERFORATED METAL LINER.
6 AIRFLOW SENSOR: MULTI-POINT, CROSS CONFIGURATION, CENTER AVERAGING, LOCATED AT INLET OF ASSEMBLY, +/-5% ACCURACY.
7 DAMPER: HEAVY GAUGE GALVANIZED STEEL, PERIPHERAL GASKET, SOLID STEEL, SHAFT, SELF LUBRICATED BEARINGS, MAX LEAKAGE OF 2% AIRFLOW WHEN TESTED FULLY CLOSED AT 3-INCH
INLET STATIC PRESSURE.
8 ACCESS: REMOVABLE PANELS ON BOTTOM OR SIDE PERMITTING ACCESS TO AIR VALVE DAMPER, WITH AIRTIGHT GASKET AND QUARTER TURN LATCHES.
9 INSTALLATION: LEVEL & PLUMB, PER NFPA 90A, SMACNA DUCT CONSTRUCTION STANDARDS, AND MANUFACTURERS RECOMMENDED INSTRUCTIONS.
REHEAT COIL SPECS:
1 1/2-IN COPPER TUBING WITH MECHANICALLY BONDED ALUMINUM FINS.
2 SUPPLY PIPING TO COIL TO BE PIPED WITH SHUT OFF VALVE, STRAINER, CONTROL VALVE AND UNION.
3 RETURN PIPING TO COIL TO BE PIPED WITH SHUT-OFF VALVE, BALANCING VALVE, AND UNION.
4 COIL SHALL BE PIPED IN COUNTERFLOW ARRANGEMENT.
5 PIPING SHALL BE ARRANGED TO ALLOW SERVICE AND MAINTENANCE.
NOT TO SCALE1REHEAT COIL PIPING DETAIL
SPECS:
1 ACCEPTABLE MANUFACTURERS: ANEMOSTAT, CARNES, KRUEGER, PRICE, TITUS
2 MATERIAL: STEEL, ALUMINUM
3 FINISH: WHITE
2 08/07/20 ISSUE FOR 50% REVIEW
3 08/31/20 ISSUE FOR COORDINATED REVIEW
4 09/14/20 ISSUE FOR CONSTRUCTION
CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
159 CENTRAL AVE
ITHACA, NEW YORK 14850
MORRILL HALL
B06 LINGUISTICS
LAB RENOVATION
E-001
12715689
GENERAL NOTES
AND SYMBOL
LEGENDS
H. TRAN
JD
2001
SEPTEMBER 14, 2020
ELECTRICAL SUBMITTAL SCHEDULE
MATERIAL
SCHEDULE/
SHOP
DWGS.
PRODUCT
DATA SAMPLES
INSPECTIONS
& TESTS O&M DATA WARRANTIES
LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING SIZE MANUFACTURER CATALOG NO. VOLTAGE BALLAST LAMPS WATTAGE FINISH
L1 SERIES 17 LED 3' WALL MOUNT 4"W x 4.7"H FINELITE S17-LED-VCF-PF-3'-S-835-120V-SC-OBO 120V LED 21 W WHITE
L2 SERIES 17 LED 4' WALL MOUNT 4"W x 4.7"H FINELITE S17-LED-VCF-PF-4'-S-835-120V-SC-OBO 120V LED 28 W WHITE
GENERAL ELECTRICAL NOTES
1.0 ELECTRICAL SCHEMATICS INDICATED ON CONTRACT DOCUMENTS ARE
DIAGRAMMATIC. IT IS NOT THE INTENT TO SHOW EXACT OR MOST EFFICIENT
ROUTING. VERIFY ALL DIMENSIONS AND FIELD CONDITIONS ON SITE. ANY
CONFLICTS BETWEEN CONSTRUCTION DOCUMENTS AND FIELD CONDITIONS SHALL
BE BROUGHT TO CORNELL'S PROJECT MANAGER FOR RESOLUTION BEFORE WORK
PROCEEDS.
2.0 ASSURE PUBLIC AND WORKER SAFETY AT ALL TIMES. PROTECT ADJOINING AREAS
FROM DAMAGE AND DUST. REMOVE ALL DEBRIS FROM SITE AND DISPOSE OF
WASTE MATERIAL IN A SAFE MANNER. KEEP THE PREMISES FREE OF DEBRIS FROM
THE EXECUTION OF WORK. DELIVER A FINAL PRODUCT THAT IS CLEAN AND
OPERABLE.
3.0 FIRE STOP ELECTRICAL PENETRATIONS THROUGH FIRE RATED WALLS AND/OR
FLOORS WITH MATERIAL EQUAL IN RATING TO THE CONSTRUCTION OF THE
MATERIAL PENETRATED.
4.0 WORK SHALL BE COMPLETED AS SPECIFIED AND INDICATED ON CONTRACT
DOCUMENTS. ANY SUGGESTED ALTERNATE MANUFACTURER OR METHOD OF
INSTALLATION SHALL BE SUBMITTED TO PROJECT ENGINEER FOR APPROVAL
PRIOR TO ORDERING ANY MATERIALS OR COMMENCING EXECUTION OF WORK.
5.0 GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLE 250. PROVIDE
EQUIPMENT GROUND CONDUCTOR WITH EACH BRANCH CIRCUIT INDICATED ON
CONTRACT DOCUMENTS. EQUIPMENT GROUND CONDUCTOR SHALL BE ROUTED
WITH ASSOCIATED PHASE CONDUCTORS.
6.0 PROVIDE A NEW TYPED PANELBOARD DIRECTORY FOR EACH PANELBOARD. LABEL
ALL NEW DEVICE FACEPLATES WITH SOURCE AND CIRCUIT NUMBER. PROVIDE
PERMANENT LABEL ON SWITCHING DEVICES INDICATING EQUIPMENT SERVICE AND
INVENTORY NUMBERS. COORDINATE EQUIPMENT INVENTORY NUMBERS WITH
CORNELL UNIVERSITY'S MECHANICAL SHOP, 255-8667.
7.0 CIRCUITS RATED 20-AMP, 120 VOLT SHALL CONTAIN SEPARATE NEUTRAL
CONDUCTORS.
8.0 CONDUCTORS SHALL BE A MINIMUM OF 12AWG, STRANDED COPPER, 600VAC, 90
DEGREE C, TYPE THHN/THWN-2 FOR DRY AREAS AND XHHW/THWN-2 FOR WET
AREAS.
9.0 CONDUITS SHALL BE A MINIMUM OF 3/4 INCHES DIAMETER. CONDUITS SHALL BE
ELECTRICAL METALLIC TUBING (EMT) AND SURFACE MOUNTED UNLESS NOTED
OTHERWISE.
10.0 AIC RATING OF NEW CIRCUIT BREAKERS SHALL MATCH RATING OF RESPECTIVE
PANELBOARD. SIZE AS INDICATED.
11.0 PROVIDE PULL STRING THROUGH NEW CONDUIT AND BOXES. PROVIDE SUPPORT
HANGERS FOR CONDUIT AS NEEDED.
12.0 INSTALL RACEWAY SYSTEMS ENSURING PROPER ACCESS TO EQUIPMENT AND
DEVICES AND WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE AND
REPAIR. RACEWAYS THAT ARE NOT INSTALLED WITH THIS REQUIREMENT IN MIND
SHALL BE RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIES
ARE CORRECTED.
ELECTRICAL SCOPE OF WORK
1.0 PROVIDE ELECTRICAL SUPPORTS TO RENOVATE ROOM B06
ELECTRICAL LEGEND
LIGHTING LEGEND
MOTOR
1'x4' LUMINAIRE
HARDWIRED EQUIPMENT CONNECTION
P-1A
12
HOMERUN TO PANEL P-1A, CIRCUIT #12. FED
FROM 20A -1P BREAKER IS INTENDED UNLESS
NOTED OTHERWISE. RUN GREEN WIRE GROUND
FOR ALL CIRCUITS. PROVIDE ONE GROUND PER
CIRCUIT.
EMERGENCY POWER OFF (EPO)
GROUND ROD ELECTRODE
DUPLEX RECEPTACLE WITH GFCI PROTECTION
DUPLEX RECEPTACLE WITH AFCI PROTECTION
QUAD RECEPTACLE
LINETYPES LEGEND
SPECIAL RECEPTACLE5-30R
PANELBOARD
JUNCTION BOX
B = INSTALLED IN BASEBOARD
TR = INSTALLED IN WOOD TRIM/CASEWORK/WAINSCOTT
SR = SURFACE RACEWAY
WP = WEATHERPROOF
AC = AIR CONDITIONER
DUPLEX RECEPTACLE:
DOUBLE DUPLEX RECEPTACLE
MOTOR STARTER
J
2'x4' LUMINAIRE
CEILING MOUNTED LUMINAIRE
EM LIGHTING BATTERY UNIT
COMBO EXIT SIGN/EM LIGHTING BATTERY UNIT
SINGLE FACE, WALL MOUNT EXIT SIGN
DOUBLE FACE, WALL MOUNT EXIT SIGN
SINGLE FACE, CEILING MOUNT EXIT SIGN
DOUBLE FACE, CEILING MOUNT EXIT SIGN
LIGHT SWITCH:
SAFETY SWITCH (NON-FUSED)
SAFETY SWITCH (FUSED)
3 = 3-WAY SWITCH
4 = 4-WAY SWITCH
D = DIMMER SWITCH
O = WALL SWITCH OCCUPANCY SENSOR
V = WALL SWITCH VACANCY SENSOR
W = WIRELESS SWITCH
S = WIRELESS SCENE SWITCH
WIRELESS OCCUPANCY SENSOR
WIRELESS DAYLIGHT SENSOR
OS
DS
1'x2' LUMINAIRE
FIRE ALARM LEGEND
FIRE ALARM CONTROL PANEL
BATTERY CABINET
WATER FLOW SWITCH
MUXPAD
REMOTE ANNUNCIATOR
D = DUCT SMOKE DETECTOR
R = RELAY BASE
BR = BEAM RECEIVER
BT = BEAM TRANSMITTER
SB = SOUNDER BASE
SMOKE DETECTOR:
TAMPER SWITCH
AUDIBLE NOTIFICATION APPLIANCE
FACP
BATT
MUX
FAA
NAC PANELNAC
MANUAL PULL STATIONF
S X
F = FIXED TEMPERATURE
R = RATE OF RISE
R/F = COMBINATION RISE/FIXED TEMPERATURE
HEAT DETECTOR:
H X
CARBON MONOXIDE DETECTORCO
AM
F
XXcd
C
FS
F
S
XXcd
C
TS
ADDRESSABLE MODULE
XXcd = CANDELA
C = CEILING
COMBO A/V NOTIFICATION APPLIANCE:
XXcd = CANDELA
C = CEILING
VISUAL NOTIFICATION APPLIANCE:
SUPPRESSION SYSTEM
ELECTRICAL ABBREVIATIONS
AC AIR CONDITIONER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT INTERRUPTER
AMM ADDRESSABLE MONITOR MODULE
AOM ADDRESSABLE OUTPUT MODULE
ARB AUXILIARY RELAY BOARD
ATS AUTOMATIC TRANSFER SWITCH
B BASEBOARD
BKR BREAKER
C CONDUIT
CD CANDELA
CKT CIRCUIT
CR CONTROL RELAY
EC ELECTRICAL CONTRACTOR
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF STATION
FAA FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FSD FIRE SMOKE DAMPER
GAA GENERATOR ALARM ANNUNCIATOR
GFI GROUND FAULT INTERRUPTER
GND GROUND
HP HORSEPOWER
KW KILOWATT
LC LIGHTING CONTACTOR
LFMC LIQUID TIGHT FLEXIBLE METALLIC CONDUIT
LTG LIGHTING
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUG ONLY
MTS MANUAL TRANSFER SWITCH
NAC NOTIFICATION APPLIANCE CIRCUIT
NIC NOT IN CONTRACT
OE OVERHEAD ELECTRIC
PC PHOTOCELL
PM PLUGMOLD
PP POWER PANEL
PVC POLYVINYL CHLORIDE CONDUIT
RGS RIGID GALVANIZED STEEL CONDUIT
SR SURFACE RACEWAY
ST SHUNT TRIP
TM THERMAL MAGNETIC
TR TRIM/CASEWORK/WAINSCOTT
TSP TWISTED SHIELDED PAIR
TYP TYPICAL
UE UNDERGROUND ELECTRIC
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VA VOLT AMPS
WP WATERPROOF
UNDERGROUND ELECTRICU
E
UNDERGROUND LIGHTINGUL
OVERHEAD ELECTRICO
E
TO BE PROVIDED
DEMOLITION / TO BE RELOCATED
EXISTING TO REMAIN
UNDERGROUND TELCOU
C
MOUNTING HEIGHTS
CARD READER 48" TOP OF BOX
LIGHT SWITCH 48" TOP OF BOX
RECEPTACLE 18" TOP OF BOX
DATA OUTLET 18" TOP OF BOX
TV OUTLET 84" TOP OF BOX
PHONE OUTLET 48" TOP OF BOX
SAFETY SWITCH 60" CENTERLINE OF HANDLE
MOTOR STARTER 60" CENTERLINE OF HANDLE
PANELBOARD 72" TOP OF PANELBOARD
MANUAL PULL STATION 48" OPERABLE HANDLE
NOTIFICATION APPLIANCE 80" BOTTOM OF LENS
DOOR HOLD OPEN COORDINATE IN FIELD
EM BATTERY UNIT 96" BOTTOM OF UNIT
EM REMOTE UNIT 102" BOTTOM OF UNIT
EXIT SIGN 96" BOTTOM OF UNIT
LIGHT POLE WITH LED LUMINAIRES, REFER TO
PLANS FOR NUMBER AND CONFIGURATION OF
HEADS
GENERAL ELECTRICAL DEMOLITION NOTES
1.0 ELECTRICAL EQUIPMENT SHOWN DASHED ON DEMOLITION DRAWINGS, INCLUDING
ASSOCIATED ANCHORS, SUPPORTS, STRAPS, BOXES, FITTINGS, AND OTHER
APPURTENANCES NOT SHOWN, SHALL BE DISCONNECTED AND REMOVED.
REMOVE ASSOCIATED BRANCH CIRCUITRY TO SOURCE, UNLESS NOTED
OTHERWISE.
2.0 EXISTING RACEWAYS AND DEVICE BACKBOXES NOT INTERFERRING WITH NEW
WORK SHALL BE REUSED WHERE POSSIBLE.
3.0 PROVIDE JUNCTION BOXES, RACEWAYS, AND WIRING TO MODIFY/EXTEND EXISTING
SYSTEMS AND CIRCUITS FED DOWNSTREAM OF ELECTRICAL EQUIPMENT SHOWN
TO BE DEMOLISHED.
4.0 CUT DEMOLISHED CONDUITS INSTALLED THRU WALLS AND FLOORS FLUSH WITH
THE SURFACE AND PATCH PENETRATIONS (FIRESTOP IF LOCATED ON A FIRE
RATED SURFACE). PATCH AND PAINT SURFACES IN EXPOSED AREAS TO MATCH
SURROUNDING MATERIALS, FINISHES, AND COLORS.
5.0 PROVIDE BLANK COVERPLATES ON UNUSED BACKBOXES REMAINING FROM
DEMOLITION NOT SPECIFIED TO BE INFILLED.
6.0 EXISTING EQUIPMENT SHOWN TO REMAIN SHALL BE PROTECTED DURING
CONSTRUCTION.
WIRELESS ACCESS POINTWL
DATA/PHONE
1 08/07/20 ISSUE FOR 50% REVIEW
4 09/08/20 ISSUE FOR COORDINATED REVIEW
5 09/14/20 ISSUE FOR CONSTRUCTION
SSS
SOS
OS
(4)
(2)
(2)WL
WIREMOLD 4000
WIREMOLD 4000
TO REMAIN
EXISTING DATA BOX
TYPICAL ON DWG.
EXISTING WIRELESS
ACCESS POINT
4
6
3
5
6
2
1
7
7
7
3
8
3
3
3
6
3
4
2
2
3
6
3
1
5
5
3
3
L1
L2
L1
L2
L2
L2
L1
L2
L2 3(2)
(WL)
(2)
(2)
7
7
7
7
7 8
7
7 CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
159 CENTRAL AVE
ITHACA, NEW YORK 14850
MORRILL HALL
B06 LINGUISTICS
LAB RENOVATION
E-101
12715689
ELECTRICAL
DEMOLITION &
RENOVATION
PLANS
H. TRAN
JD
2001
SEPTEMBER 14, 2020
#
SCALE: 3/16"=1'-0"
0' 2' 4' 6'12'
E-101 KEYED DEMOLITION NOTES
1 EXISTING FIRE ALARM STROBE TO BE RELOCATED.
2 REMOVE EXISTING SURFACE MOUNTED LUMINAIRE. EXISTING LIGHTING CIRCUITRY
SHALL BE RE-USED. TYPICAL ON DRAWING.
3 REMOVE EXISTING WIREMOLD 4000 AND ASSOCIATED RECEPTACLES. EXISTING
POWER WIRING SHALL BE RE-USED.
4 PULL EXISTING PHONE/DATA CABLES BACK TO J-BOX ABOVE CEILING. EXISTING
CABLES SHALL BE RE-USED. TAG & LABEL THE CABLES.
5 EXISTING CIT DATA J-BOX ABOVE CEILING TO REMAIN.
6 REMOVE EXISTING OCCUPANCY SENSOR AND ASSOCIATED CONDUIT AND WIRING
COMPLETELY.
7 EXISTING SHEET ROCK ON THIS SIDE OF WALL TO BE REPLACED BY OTHERS.
ELECTRICAL CONTRACTOR TO REMOVE AND REINSTALL AT THE SAME LOCATION.
TAG & LABEL THE CABLES.
8 REMOVE AN EXISTING RECEPTACLE LOCATED A FEW INCHES BELOW CEILING.
#E-101 KEYED RENOVATION NOTES
1 RELOCATE EXISTING FIRE ALARM STROBE TO THIS LOCATION.
2 PROVIDE NEW FIRE ALARM STROBE. CIRCUIT TO THE EXISTING FIRE ALARM
STROBE CIRCUIT IN THIS ROOM. TESTING OF THE DEVICE WITH CORNELL EH&S AS
REQUIRED.
3 PROVIDE A NEW WALL MOUNTED LUMINAIRE. CIRCUIT TO EXISTING LIGHTING
CIRCUITRY AND NEW LIGHT SWITCH AS INDICATED. MOUNT AT 6" BELOW THE
CEILING AND CENTER TO WALL.
4 REPLACE THE EXISTING (2) LIGHT SWITCHES W/ ONE LIGHT SWITCH. REPLACE
EXISTING FACEPLATE AS REQUIRED.
5 PROVIDE NEW DIMMING SWITCH TO CONTROL THE LIGHTING IN ROOM.
6 PROVIDE SURFACE MOUNT LIGHT SWITCH. RACEWAY ON EXISTING WALL SHALL BE
WIREMOLD 700.
7 CIRCUIT NEW RECESS MOUNT RECEPTACLE INDICATED TO EXISTING RECEPTACLE
CIRCUITRY IN ROOM. SEE DEMOLITION NOTE #3. STAGGER BOXES IN WALL AND
PROVIDE ACOUSTICAL SEALANT AROUND THEM.
8 FROM THE LOCATION SHOWN, PROVIDE A SINGLE GANG RECESS BOX. FROM BOX,
PROVIDE 1" EMT TO THE EXISTING DATA J-BOX ABOVE CEILING. PULL (2) EXISTING
DATA CABLES WITH JACKS AND INSTALL AT THE BOX. FACEPLATE TO MATCH THE
EXISTING DATA FACEPLATES IN ROOM. LABEL THE JACKS TO MATCH EXISTING.
SEE DEMOLITION NOTE 4. PROVIDE TESTING FOR THE EXISTING CABLES AS
REQUIRED.
SCALE:3/16" = 1'-0"1 DEMOLITION
SCALE:3/16" = 1'-0"2 LIGHTING AND FIRE ALARM
SCALE:3/16" = 1'-0"3 POWER AND DATA
1 08/07/20 ISSUE FOR 50% REVIEW
4 09/08/20 ISSUE FOR COORDINATED REVIEW
5 09/14/20 ISSUE FOR CONSTRUCTION
B06
B07
B08
B07
B06
B06A
B06B
B08
SP-1
(TYPICAL
FOR ALL)
1
1"
1"
1"
1"
1"
2
2
2
2
N
KEYNOTE DEMOLITION
KEYNOTE NEW WORK
NORTH ARROW
X" (E)
X"
X"
NEW PIPING
EXISTING PIPING
EXISTING EQUIPMENT
PIPING TO BE REMOVED
POINT OF CONNECTION
CAP OR PLUG
PITCH PIPING (DOWN)
EXISTING
POINT OF DISCONNECTION
RECESSED PENDENT SPRINKLER
PENDENT SPRINKLER
UPRIGHT SPRINKLER
#
D
PIPE UP
TOP PIPE CONNECTION
BOTTOM PIPE CONNECTION
PIPE DOWN
(E)
#AWS AUTOMATIC WET STANDPIPE
F
EXIST EXISTING
WET FIRE PIPING
FHV FIRE HOSE VALVE
FP FIRE PROTECTION
MWS MANUAL WET STANDPIPE
LPD LOW POINT DRAIN
ITC INSPECTORS TEST CONNECTION
STP
SUSP
STAND PIPE
SUSPENDED
PIV POST INDICATOR VALVE
TS TAMPER PROOF SWITCH
WSR WET SPRINKLER RISER
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
159 CENTRAL AVE
ITHACA, NEW YORK 14850
MORRILL HALL
B06 LINGUISTICS
LAB RENOVATION
FP-101
12715689
FIRE
PROTECTION
REMOVAL &
INSTALLATION
PLANS &
SCHEDULES
T. JORDAN
ALF
2001
SEPTEMBER 14, 2020
SCALE:1/4" = 1'-0"1 BASEMENT FIRE PROTECTION REMOVAL PLAN
SCALE:1/4" = 1'-0"3 BASEMENT FIRE PROTECTION CONSTRUCTION PLAN
FIRE PROTECTION ACCESSORIES SCHEDULE
TAG DEVICE
MANUFACTURER
(BOD)
MODEL
(BOD)
PRESSURE
/
TEMPERAT
URE
RATING
SPECIFICATIONS
SP-1 SEMI-RECESSED PENDENT RELIABLE FIFR56 155⁰F
QUICK RESPONSE, 1/2" THREADED, 5.6 K FACTOR, CHROME
FINISH, 175 PSIG WORKING PRESSURE, UL & FM APPROVALS
FIRE PROTECTION PIPE & FITTING SCHEDULE AND SPECIFICATIONS1
PIPE
SERVICE55
ABBREVIATION5
5
PIPE
SIZE55 MATERIAL55 FITTINGS55 JOINT55 FINISH
WET
SPRINKLER
PIPING
SP
2" &
SMALLER
2-1/2" &
ABOVE
ASTM A53,
TYPE F, SCH
40 BLACK
ASME B16.3 MALLEABLE IRON, CLASS 125 AND 300
ASME B16.4 CAST IRON, CLASS 125 AND 250
ASME B16.11 FORGED STEEL
ASTM A47 MALLEABLE IRON
ASTM A536 DUCTILE IRON
ASTM A47 MALLEABLE IRON
ASTM A536 DUCTILE IRON
ASME B16.1 CAST IRON
ASME B16.9 WROUGHT STEEL
ASME B16.25 ENDS FOR PIPE, VALVES, FLANGES, FITTINGS
ASME B16.5 STEEL
ASME B16.11 FORGED STEEL
THREADED
THREADED
THREADED
GROOVED
GROOVED
GROOVED
GROOVED
FLANGED
BUTTWELD
BUTTWELD
FLANGED
SOCKET WELD
NOT TO SCALE2FIRE PROTECTION ABBREVIATIONS AND SYMBOLOGY
FIRE PROTECTION GENERAL NOTES
1.0 IT IS THE INTENT OF THESE DRAWINGS TO PROVIDE MODIFICATIONS TO THE
MORRILL HALL SPRINKLER SYSTEM.
2.0 PRIOR TO ALTERATIONS, THE SPRINKLER CONTRACTOR SHALL FIELD VERIFY
EXTENT OF ALTERATION AND NEW WORK, WITH REGARD TO EXISTING CONDITIONS
AT PIPE PENETRATIONS THROUGH FLOORS, WALLS, CEILINGS AND SOFFITS.
3.0 ALL SPRINKLER COMPONENTS SHALL BE UNDERWRITER'S LABORATORIES (UL) AND
FACTORY MUTUAL (FM) APPROVED.
4.0 NEW SPRINKLER SYSTEM PIPING SHALL BE INSTALLED ABOVE CEILINGS AS
SHOWN ON PLANS. PIPING AND HANGER ASSEMBLIES SHALL BE UN-PAINTED.
5.0 THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE ONLY THE GENERAL
ARRANGEMENT OF THE ITEMS INCLUDED IN THE FIRE PROTECTION WORK. AS
SUCH, CONTRACTOR SHALL PROVIDE A COMPLETE SPRINKLER SYSTEM IN STRICT
ACCORDANCE WITH THE REQUIREMENTS OF FM GLOBAL STANDARDS, THE NFPA
13-INSTALLATION OF FIRE PROTECTION SYSTEMS, THE NEW YORK STATE BUILDING
CODES, THE NEW YORK STATE FIRE CODES, LOCAL CODES, AND GOVERNING
AUTHORITIES. THE DESIGN OF FIRE PROTECTION SYSTEMS TO WITHSTAND SEISMIC
EVENTS SHALL BE IN ACCORDANCE WITH THE CRITERIA DEVELOPED BY THE NFPA.
6.0 CONTRACTOR SHALL REQUEST SPRINKLER SYSTEM SHUTDOWNS THROUGH
CORNELL CUSTOMER SERVICE (607.255.5322) A MINIMUM OF TEN (10) DAYS PRIOR
TO THE SHUTDOWN DATE. THE CONTRACTOR SHALL BEAR THE COST OF THE
UTILITY SHUTDOWN. NOTIFY THE OWNER'S REPRESENTATIVE TO COORDINATE
BUILDING FUNCTIONS WITH THE BUILDING COORDINATOR.
7.0 COORDINATE THE EXACT LOCATION OF SPRINKLERS, EQUIPMENT, AND DEVICES
WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL AND ALL OTHER TRADES
DRAWINGS PRIOR TO ROUGH-IN AND INSTALLATION.
8.0 SPRINKLER PIPING SHALL BE ARRANGED TO DRAIN THROUGH THE MAIN DRAIN
VALVE WHENEVER PRACTICAL. ALL TRAPPED SECTIONS OF PIPE, EXCEPT THOSE
SUPPLYING A SINGLE SPRINKLER, SHALL BE PROVIDED WITH A DRUM-DRIP
ASSEMBLY.
9.0 PENETRATIONS THROUGH CONCRETE FLOORS AND WALLS SHALL BE MADE WITH
GALVANIZED PIPE SLEEVES. ALL PENETRATIONS SHALL CONTAIN FIRE STOPPING
WITH A FIRE RATING EQUAL TO THAT OF THE AREA BEING PENETRATED.
10.0 SPRINKLER PIPING SHALL BE LABELED.
11.0 AFTER ALL WORK HAS BEEN COMPLETED, ACCEPTANCE TESTING SHALL BE
SCHEDULED THROUGH EH&S, AND SHALL BE WITNESSED BY EH&S AND CITY OF
ITHACA REPRESENTATIVES.
12.0 HYDROSTATIC TEST SHALL BE PERFORMED AT SYSTEM PRESSURE FOR A PERIOD
OF 2-HOURS. A REPRESENTATIVE OF ENVIRONMENTAL HEALTH AND SAFETY SHALL
WITNESS HYDROSTATIC TESTING OF THE NEW PIPING INSTALLATIONS AND
ALTERATIONS. THE AUTHORITY HAVING JURISDICTION (ITHACA FIRE DEPARTMENT)
REQUIRES THAT ONE OF THEIR REPRESENTATIVES WITNESSES HYDROSTATIC
TESTING AND FLUSHING. ADVANCE NOTICE AND SCHEDULING IS REQUIRED
THROUGH EH&S.
13.0 ANY FIRESTOPPING DISTURBED DURING THE COURSE OF WORK SHALL BE
REPAIRED TO MAINTAIN A 2-HOUR FIRE RATING.
FP-101 KEYED RENOVATION NOTES
1 COORDINATE SPRINKLER HEAD LOCATIONS WITH THE REFELECTED CEILING PLAN.
2
PROVIDE SPRINKLER PIPING SIZES SHOWN ON THE DRAWING. HOWEVER, IF
EXISTING PIPES ARE LARGER THAN 1", THEN PROVIDE NEW PIPING THE SAME SIZE
AS EXISTING.
2 08/07/20 ISSUE FOR 50% REVIEW
3 08/31/20 ISSUE FOR COORDINATED REVIEW
4 09/14/20 ISSUE FOR CONSTRUCTION