T-001 TITLE SHEET
ARCHITECTURAL
A-001 GENERAL NOTES, SYMBOLOGY, AND ABBREVIATIONS
A-101 DEMOLITION PLAN - GROUND FLOOR & RENOVATION PLAN - BASEMENT
A-102 RENOVATION PLANS, ELEVATIONS AND SECTION
MECHANICAL/PLUMBING
MP-001 GENERAL NOTES AND SYMBOL LEGENDS
MP-101 GROUND FLOOR MECHANICAL & PLUMBING DEMOLITION & INSTALLATION
PLANS
MP-501 SCHEDULES
ELECTRICAL
E-001 ELECTRICAL NOTES, SYMBOL, LEGEND, & ABBREVIATIONS
E-101 PARTIAL GROUND FLOOR ELECTRICAL REMOVAL AND PLANCORNE
LL U N I V
E
R
SI
TYFOUN
D E D 5681
AD CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
Cornell University
BAKER SOUTH
BAKER SOUTH
RFD KITCHEN
RENOVATION
T-001
12309492
TITLE SHEET
FE DESIGN
JGC
3004S
APRIL 15, 2020
BAKER SOUTH RFD KITCHEN RENOVATION
BUILDING CODE SUMMARYGENERAL SYMBOLS LEGEND
EXTERIOR ELEVATION
1
1
1 1X-100
X-100
1
1
1 1 INTERIOR ELEVATION
1
X-100
SECTION MARKER
1
X-100 ENLARGED DETAIL
CONSTRUCTION KEYED NOTE
DEMOLITION KEYED NOTE
DRAWING REVISION NOTE
DRAWING INDEX
LINETYPE: TO BE PROVIDED / NEW
LINETYPE: DEMOLITION / TO BE RELOCATED
LINETYPE: EXISTING TO REMAIN
PROJECT SCOPE
The purpose of this project is to renovate the kitchen in the RFD apartment in Baker South. Included in the scope of work is to reconfigure the space and provide new
cabinets/ countertops, flooring, lighting, and heating unit. All of the existing doors will be painted and new hardware (hinges, closers. etc.) provided.
PERSPECTIVE VIEWSITE LOCATION -BAKER SOUTH 3004S
KEY PLAN -GROUND FLOOR
#
#
#
APPLICABLE CODES
2015 IEBC (ADOPTED BY NEW YORK STATE)
2015 IBC (ADOPTED BY NEW YORK STATE)
2015 IMC (ADOPTED BY NEW YORK STATE)
2015 IECC (ADOPTED BY NEW YORK STATE)
2016 SUPPLEMENT TO THE NEW YORK STATE ENERGY CONSERVATION
CONSTRUCTION CODE
2017 UNIFORM CODE SUPPLEMENT (NEW YORK STATE)
PROJECT SUMMARY
THIS PROJECT INCLUDES THE RENOVATION OF A KITCHEN, NEW
FLOORING IN HALLWAY AND PAINTING/ NEW HARDWARE ON THE
EXISTING DOORS IN THE RFD APARTMENT IN BAKER SOUTH. THE WORK
IS ALTERATION LEVEL 1 (DOORS/ FLOORING) AND LEVEL 2 FOR
(KITCHEN).
BUILDING LIMITATIONS
CONSTRUCTION CLASSIFICATION:2A
CLASSIFICATION OF HAZARDS:NONE
HIGH-RISE BUILDING:NO
EXTINGUISHING REQUIREMENT:THE EXISTING BUILDING
IS SPRINKLERED
OCCUPANCY
OCCUPANCY CLASSIFICATION:RESIDENTIAL (R-2)
BAKER SOUTH -GROUND FLOOR
1 02/14/2020 ISSUE FOR 100% SD REVIEW
2 03/24/2020 ISSUE FOR 95% REVIEW
3 04/10/2020 ISSUE FOR COORDINATED REVIEW
4 04/15/2020 ISSUE FOR CONSTRUCTION
UPDNUPWALL -EXISTING
WALL -METAL STUD/ GWB
WALL -CONCRETE
WALL -CMU
WALL -BRICK
ITEMS FOR DEMOLITION
DOOR/ WALL -EXISTING
DOOR/ WALL -NEW
DOOR/ WALL -DEMOLITION
TAG -DOOR
TAG -WINDOW
TAG -WALL
TAG -ROOM #
CENTER LINE
PHOTO REFERENCE
LEVEL MARKER
COLUMN GRID MARKER
ELEVATION MARKER
ELEVATION CHANGE ARROWS
BREAK LINE
SYMBOLS
0' -0"
101
1t
X-X
X
2B00UA
CL
1
Name
Elevation
A101 1
1
1
0
DN
UP
ABBREVIATIONS
A
&AND
@ AT
ACT ACOUSTICAL CEILING TILE
ALT ALTERNATE
ALUM ALUMINUM
AVG AVERAGE
AFF ABOVE FINISH FLOOR
B
BD BOARD
BLDG BUILDING
BOD BOTTOM OF DECK
BSMT BASEMENT
C
CG CORNER GUARDS
CJ CONTROL JOINT
CLG CEILING
CL CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONT CONTINUOUS
CORR CORRIDOR
CPT CARPET
CRS COURSE(S)
CT CERAMIC TILE
D
DEMO DEMOLITION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DO DOOR OPENING
DWG DRAWING
E
EA EACH
EJ EXPANSION JOINT
ELEC ELECTRIC
ELEV ELEVATION/ ELEVATOR
EPDM RUBBER ROOF MEMBRANE
EQ EQUAL
EX'G EXISTING
EXT EXTERIOR
F
FD FLOOR DRAIN
FDN FOUNDATION
FEC FIRE EXTINGUISHER CABINET
FFE FINISH FLOOR ELEVATION
FRP FIBER REINFORCED POLYESTER
FT FOOT/FEET
FTG FOOTING
G
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERAL
GL GLASS
GWB GYPSUM WALL BOARD
H
HC HANDICAPPED
HT HEIGHT
HM HOLLOW METAL
HR HOUR
HVAC HEATING, VENTILATING & AC
J
JAN JANITOR
L
LAV LAVATORY
LB/#POUND
LGMF LIGHT GAGE METAL FRAMING
M
MFR MANUFACTURER
MAT MATERIAL
MAX MAXIMUM
MEZZ MEZZANINE
MIN MINIMUM
MO MASONRY OPENING
MTL METAL
N
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NR NOT RATED
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OSB ORIENTER STRAND BOARD
P
+/-PLUS OR MINUS
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
Q
QTY QUANTITY
R
R RISER
RD ROOF DRAIN
REF REFRIGERATOR
REQ REQUIRED
REV REVISION
RO ROUGH OPENING
RTU ROOF TOP UNIT
S
SHTG SHEATHING
SIM SIMILAR
SF SQUARE FOOT/ FEET
SS STAINLESS STEEL
STL STEEL
STD STANDARD
T
T TREAD
T&G TONGUE & GROOVE
TEL TELEPHONE
TEMP TEMPERATURE
TOS TOP OF STEEL
TV TELEVISION
TYP TYPICAL
U
UEV UNEVEN DOORS W/ VISION PANEL
UEF UNEVEN FLUSH DOOR
V
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
W
W/O WITHOUT
WD WOOD
AREA OF WORK -
ALTERATION -
LEVEL 2 -
RECONFIGURE
OF KITCHEN
G17G AND DEMO
OF ROOM G17H G17G
G17
G17A
G17C
G17F
G17B
G17H
AREA OF WORK -
ALTERATION -
LEVEL 1 -DOORS
PAINTED AND
NEW HARDWARE
INSTALLED
AREA OF WORK -
ALTERATION -
LEVEL 1 -
REMOVAL OF
EXISTING
FLOORING AND
NEW LVT
INSTALLED
AREA OF WORK -
ALTERATION -
LEVEL 1 -DOORS
PAINTED AND
NEW HARDWARE
INSTALLED
G17E
G17DG00CF
G00CG CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
BAKER SOUTH
BAKER SOUTH
RFD KITCHEN
RENOVATION
A-001
12309492
GENERAL
NOTES,
SYMBOLOGY,
AND
ABBREVIATIONS
J. COOLBAUGH
JGC
3004S
APRIL 15, 2020
SCOPE OF WORK
1.0 REMOVE EXISTING CABINETS, COUNTERTOP, CEILING, AND APPLIANCES.
2.0 REMOVE EXISTING FLOOR AND INSTALL NEW LVT FLOORING.
3.0 PROVIDE NEW CABINETS, COUNTERTOP, AND APPLIANCES. INSTALL NEW CEILING.
4.0 CUT DOWN EXISTING PASS THRU OPENING.
GENERAL NOTES
1.0 DESIGN, CONSTRUCTION AND SAFETY SHALL CONFORM TO ALL LOCAL, STATE AND
OWNER SPECIFIC CODES, INCLUDING (BUT NOT LIMITED TO) THE NEW YORK STATE
UNIFORM FIRE PROTECTION AND BUILDING CODE, LATEST REVISION, THE NFPA 101
LIFE SAFETY CODE, LATEST REVISION, ANSI A117.1 - LATEST REVISION, OSHA, AND
ANY OTHER CODES GOVERNED BY THE JURISDICTION IN WHICH THIS PROJECT IS
BEING CONSTRUCTED.
2.0 THIS CONTRACT REQUIRES COMPLETE, FINISHED WORKABLE PROJECT OF THE
AREAS INDICATED BY THE CONTRACT DOCUMENTS, AND SHALL INCLUDE ALL
MATERIALS AND LABOR NECESSARY TO COMPLETE, REGARDLESS OF WHETHER OR
NOT ALL WORK OR EACH ITEM IS SPECIFICALLY INDICATED ON ANY OTHER
PORTION OF THE DRAWINGS AND / OR NOTES.
3.0 WHERE MATERIALS REFERENCED ON DRAWINGS, OR NECESSARY TO COMPLETE
THE WORK OF THIS CONTRACT ARE NOT SPECIFIED HEREIN, PROVIDE BEST
QUALITY MATERIALS. WHERE MATERIALS ARE INTENDED TO MATCH EXISTING,
PROVIDE CLOSEST POSSIBLE MATCH, SUBJECT TO OWNER'S APPROVAL. ALL ITEMS
AND WORK ON DRAWINGS ARE NEW, UNLESS INDICATED EXISTING. ALL WORK
WHICH HAS BEEN DAMAGED SHALL BE REPAIRED OR REPLACED AT NO COST TO
THE OWNER. WHERE ITEMS CAN NOT BE REPAIRED TO A ""NEW CONDITION"", OR
WHERE THE STRUCTURAL INTEGRITY HAS BEEN AFFECTED, ITEMS SHALL BE
REPLACED AT NO COST TO THE OWNER.
4.0 CONTRACTOR IS RESPONSIBLE TO VERIFY ALL SITE, FIELD AND BUILDING
CONDITIONS PRIOR TO SUBMITTING BIDS AND COMMENCING WORK. IF THERE ARE
ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS, NOTIFY THE
PROJECT MANAGER, WHO WILL REQUEST CLARIFICATION FROM THE
ARCHITECT/ENGINEER AND PROVIDE CLARIFICATION IN WRITING.
5.0 WHERE EXISTING CONSTRUCTION OR ITEMS HAVE BEEN INFILLED, REMOVED AND /
OR DISTURBED FOR INSTALLATION OF NEW WORK, CAUSING THE EXPOSURE OF
UNFINISHED AND/OR DAMAGED SURFACES RESULTING SURFACES AND INFILLED
SURFACES SHALL BE RECONSTRUCTED WITH MATERIALS TO MATCH FINISHED
AREAS. ALL ABANDONED OPENINGS (i.e. DUCT/PIPE REMOVALS, ETC.) AT WALLS,
ROOF OR FLOOR TO BE INFILLED SOLID.
6.0 WORK IS REQUIRED IN VARIOUS PORTIONS OF THE FACILITY TO EXECUTE WORK OF
OTHER TRADES (i.e. ELECTRICAL, MECHANICAL). ALTHOUGH NOT NECESSARILY
SHOWN ON DRAWINGS, WORK IS REQUIRED IN THESE AREAS CONSISTING OF
REMOVAL / REPLACEMENT OF CEILINGS, WALLS, FINISHES, PAVEMENT AND OTHER
CONSTRUCTION AS NECESSARY TO PERFORM WORK AND RESTORE THESE
SPACES OR AREAS TO ORIGINAL CONDITION.
7.0 GENERAL CONTRACTOR IS TO COORDINATE WORK OF ALL TRADES. SCHEDULE
WORK PROGRESS THROUGHOUT THE ENTIRE PROJECT TO PREVENT CONFLICTS
AND INTERFERENCES. OBTAIN ALL NECESSARY INFORMATION SUCH AS SIZES,
LOCATIONS, TEMPLATES, LAYOUT, DIMENSIONS AND ALL OTHER INFORMATION
NECESSARY FOR A PROPER AND WELL COORDINATED INSTALLATION. PRIOR TO
INSTALLATION OF ITEMS, VERIFY AND CONFIRM WITH EACH CONTRACTOR EXACT
LOCATION OF ALL ITEMS.
8.0 ALL PENETRATIONS (EXISTING OR NEW) THROUGH FLOORS AND FULL HEIGHT
WALLS - IN AREA OF WORK TO BE FIRE STOPPED. ALL GAPS AND JOINTS AT RATED
FLOORS, ROOFS AND WALLS TO BE FIRE & SMOKE STOPPED. GAPS AND JOINTS
INCLUDE (BUT ARE NOT LIMITED TO) TOP OF WALL TO FLOOR OR ROOF DECK, WALL
TO BEAMS, AND CONTROL OR EXPANSION JOINTS. FIRE STOPPING INCLUDES BOTH
FORM OR PACKING MATERIAL AND THE FILL, VOID OR CAVITY MATERIAL. PROVIDE
AND INSTALL LABELING REQUIRED BY CODE. LABELS SHALL INCLUDE
PENETRATION TYPE WITH UL LISTING USED, MATERIAL USED, DATE INSTALL AND
NAME OF INSTALLER.
9.0 JOBSITE WILL BE CLEANED DAILY AND DEBRIS REMOVED TO CONTAINERS OR TO
VEHICLE WHICH WILL REMOVE DEBRIS FROM CAMPUS. CONTAINERS WILL BE
REMOVED AS SOON AS FULL OR WHEN THE PROJECT HAS PROGRESSED TO A
POINT THAT A CONTAINER IS NO LONGER REQUIRED.
10.0 CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL AREAS USED TO BRING
SUPPLIES AND EQUIPMENT INTO THE PROJECT AREA. ANY DAMAGE TO AREAS
OUTSIDE THE PROJECT AREA INCLUDING BUT NOT LIMITED TO THE LOBBY AND
CORRIDOR SHALL BE REPAIRED AT NO COST TO THE OWNER.
SCALE:1/8" = 1'-0"1 CODE PLAN
0' 4' 8'16'
SCALE: 1/8"=1'-0"
1 02/14/2020 ISSUE FOR 100% SD REVIEW
2 03/24/2020 ISSUE FOR 95% REVIEW
3 04/10/2020 ISSUE FOR COORDINATED REVIEW
4 04/15/2020 ISSUE FOR CONSTRUCTION
UPDNG17
G17B
G17A
GOOCG G17F
G17E
G17C
G17D
G00CF
4
6 7
7
7
7
9
1
2
4
22
3
5
3
G17G
G17H
3
8
8' - 3"
5
B04
B03
B01
B00T
B00U B02
B00C
B00S
REMOVE UP TO 6 PANES OF
GLASS FROM TOP OF EXISTING
WINDOW (POSSIBLE
ABATEMENT NEEDED PRIOR
TO ANY REMOVAL). REMOVE
THE MUNTINS. PROVIDE
INSULATED METAL PANEL
SIMILAR TO MAPES PANEL AND
ATTACH TO EXISTING WINDOW.
SEAL ALL EDGES AROUND
PANEL AND DUCT. COLOR TBD.
COORDINATE LOCATION WITH
MECHANICAL DRAWINGS.CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
BAKER SOUTH
BAKER SOUTH
RFD KITCHEN
RENOVATION
A-101
12309492
DEMOLITION
PLAN - GROUND
FLOOR &
RENOVATION
PLAN -
BASEMENT
J. COOLBAUGH
JGC
3004S
APRIL 15, 2020
A-101 KEYED DEMOLITION NOTES
1 REMOVE EXISTING CABINETS, COUNTERTOPS AND ALL BLOCKING.
2 REMOVE EXISTING APPLIANCES.
3 REMOVE EXISTING QUARRY TILE AND SETTING BED.
4 REMOVE EXISTING GYPSUM CEILING.
5 REMOVE A PORTION OF EXISTING WALL.
6 REMOVE EXISTING WALL AND DOOR.
7 REMOVE EXISTING DOOR LEAF FOR PAINTING. REMOVE AND REINSTALL EXISTING
LOCKSET.
8 REMOVE EXISTING WOOD BASE. SALVAGE FOR REINSTALLATION AFTER NEW
FLOORING IS INSTALLED.
9 REMOVE EXISTING DOOR LEAF FOR PAINTING. REMOVE EXISTING DOOR
HARDWARE.
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
SCALE:1/4" = 1'-0"1 DEMOLITION PLAN - GROUND FLOOR
SCALE:1/4" = 1'-0"2 RENOVATION PLAN - BASEMENT
1 02/14/2020 ISSUE FOR 100% SD REVIEW
2 03/24/2020 ISSUE FOR 95% REVIEW
3 04/10/2020 ISSUE FOR COORDINATED REVIEW
4 04/15/2020 ISSUE FOR CONSTRUCTION
Ref
DW
3
A-102
A-102
4
A-102
2
5
G17
G17A
G17FGOOCG
G17E
G17B
G17C
G17D
G00CF
2
3
4 27 1/4"12"5
5
5
5
6
EX.LVTLVT
1
1
7' - 3"3' - 2"3' - 0 5/8"
V.I.F.
13' - 5 5/8" +/-
5
2
ALIGN NEW WALLS WITH
EXISTING (TYP)
PROVIDE WOOD BASE TO MATCH
EXISTING PROFILE. PROVIDE
QUARTER ROUND AROUND WALLS
AFTER THE FINISH FLOOR IS
INSTALLED.
PROVIDE WOOD BASE TO MATCH
EXISTING PROFILE. PROVIDE
QUARTER ROUND AROUND WALLS
AFTER THE FINISH FLOOR IS
INSTALLED.
3
A-102
OPENING4' - 0"A.F.F.3' - 6"PT-2 6"36"18"30"1 1/2"30"
1 1/8"
27"3"12"84"1"27"36"24"11"
1 1/2"
30"
1 1/8"
27"3"
V.I.F.
161 5/8" +/-36"OPENING48"4 1/4"8' - 3"5' - 2 5/8" +/-
NEW SOFFIT (TYP
AROUND TOP OF
CABINETS)30"18"36"6"84"3"27"27"30"1"36"1"36"5/8"
V.I.F.
161 5/8" +/-
3"27"27"30"38"12"PT-1
NEW SOFFIT (TYP
AROUND TOP OF
CABINETS)OPENING4' - 0"LIVING ROOM SIDE3' - 6"KITCHEN SIDE3' - 0"V.I.F.
3' - 1 1/2"
1" OVERHANG (TYP)
G17G G174 1/4" +/-6"CEILING HEIGHT7' - 4 1/4" +/-PROVIDE 5/8" MOISTURE RESISTANT
GYPSUM WALL BOARD ON KITCHEN SIDE
(TYP). PROVIDE BLOCKING IN WALL
WHERE BASE/ WALL CABINETS ARE TO
BE LOCATED. TAPE, SPACKLE, PRIME
AND PAINT (PT-1).
PROVIDE METAL STUD TOP TRACK.
VERIFY STUD SIZE.
PROVIDE PLYWOOD SUBCOUNTER TO
SUPPORT NEW CORIAN COUNTERTOP (TYP).
PATCH EXISTING GYPSUM WALL BOARD.
TAPE, SPACKLE, PRIME AND PAINT (PT-2).
PATCH EXISTING GYPSUM WALL BOARD.
TAPE, SPACKLE, PRIME AND PAINT (PT-2).
PROVIDE 2 1/2" 20GA METAL STUD AT 16"
O.C. AND 1/2" GYPSUM WALL BOARD
CEILING. TAPE, SPACKLE, PRIME AND
PAINT (PT-3).CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
BAKER SOUTH
BAKER SOUTH
RFD KITCHEN
RENOVATION
A-102
12309492
RENOVATION
PLANS,
ELEVATIONS AND
SECTION
J. COOLBAUGH
JGC
3004S
APRIL 15, 2020
SCALE:1/4" = 1'-0"1 RENOVATION PLAN
GENERAL NOTES:
1. FIELD VERIFY ALL DIMENSIONS PRIOR TO CABINET/APPLIANCE
INSTALLATION NOTE MINIMUM CLEARANCE REQUIREMENTS.
2. PROVIDE FILLERS AS REQUIRED TO ALLOW PROPER CLEARANCE FOR
DRAWERS, DOORS, & HARDWARE.
3. PATCH WALLS AND CEILING WITH LIKE MATERIALS AFTER THE REMOVAL
OF EQUIPMENT, DOORS, WALLS, WINDOWS, ETC. PRIME AND PAINT.
KITCHEN CABINETS AND COUNTERTOP:
CABINETS -DURA SUPREME -CRESTWOOD HUDSON DOOR IN OAK
• ALL PLYWOOD CONSTRUCTION, SOLID HARDWOOD
DOVETAILED DRAWERS
• SOFT CLOSE HINGES AND FULL EXTENSION, SOFT CLOSE
DRAWER TRACKS BY BLUM
• HARDWARE -LIBERTY 3" STEEL BAR PULL
1. SATIN NICKEL FINISH -P27507H-SN-X1
• 5-10 YEAR WARRANTY
• FULLY SEALED FINISH
• COLOR: COCOA BROWN
COUNTERTOPS -CORIAN BY DUPONT,
• 3/4" THICK WITH DOUBLE PENCIL EDGE
• 4" BACKSPLASH & SIDESPLASH
COLOR: RAIN CLOUD
PAINT:
• PT-1 -WALL PAINT KITCHEN
1. BENJAMIN MOORE, REGAL SELECT -AMERICAN WHITE –2112-70, PEARL
FINISH
• PT-2 -WALL PAINT LIVING ROOM
1. BENJAMIN MOORE, REGAL SELECT -STORMY MONDAY –211-50, PEARL
FINISH
• PT-3 -CEILING PAINT
1. BENJAMIN MOORE, REGAL SELECT –WHITE -FLAT
• PT-4 - WALL BASE, DOOR AND TRIM
1. BENJAMIN MOORE, REGAL SELECT -WHITE OPULENCE –OC-69 -SEMI-
GLOSS FINISH
FLOORING:
1. PROVIDE ARDEX OR BOSTIK SELF LEVELING UNDERLAYMENT
LUXURY VINYL PLANK:
• KITCHEN FLOOR –MOHAWK VEPID STEP STONE -S999 STORMY
NIGHTS
• ENTRY –EXTENSION FROM EXISTING
A-102 GENERAL RENOVATION NOTES
1.0 PATCH FLOORS WHERE WALLS HAVE BEEN DEMOLISHED TO MATCH EXISTING SLAB
ELEVATION AND PREP FOR NEW FLOOR FINISH. REFER TO ROOM FINISH SCHEDULE
FOR NEW FLOOR FINISHES.
2.0 ALL DIMENSIONS ARE TO THE FACE OF STUD UNLESS OTHERWISE NOTED.
SCALE:NO SCALE4INTERIOR ELEVATION - LIVING ROOM
SCALE: NO SCALE
2 INTERIOR ELEVATION #2 - KITCHEN G17G
SCALE: NO SCALE
5 INTERIOR ELEVATION #1 - KITCHEN G17G
SCALE:3/4" = 1'-0"3 WALL SECTION AT PASS-THRU
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
A-102 KEYED RENOVATION NOTES
1 PROVIDE NEW LVT FLOORING. SEE FLOORING NOTES FOR SPEC INFORMATION.
2 PROVIDE 3 5/8" METAL STUD WITH 5/8" MOISTURE RESISTANT GYPSUM WALL BOARD
CHASE WALL. TAPE, SPACKLE, PRIME AND PAINT PT-1.
3 PROVIDE NEW TALL PANTRY CABINET.
4 PATCH WALL TO MATCH EXISTING ADJACENT CONDITIONS. TAPE, SPACKLE, PRIME
AND PAINT PT-1.
5 PAINT EXISTING DOORS PT-4. REINSTALL LOCKSET AND PROVIDE NEW HINGES AS
PER HARDWARE NOTES.
6 PAINT EXISTING DOOR PT-4. PROVIDE NEW LOCKSET, HINGES, AND CLOSER AS PER
HARDWARE NOTES.
DOOR HARDWARE:
• HINGES –MCKINNEY –TA2714 –US15 (VERIFY SIZE OF EXISTING)
• STRIKE PLATE –DON JO -ANSI STRIKE (VERIFY SIZE OF EXISTING AND
COORDINATE WITH NEW LOCKSET)
• CLOSER –SARGENT -351 X UO X 15 X 90 DEG
• DOOR WRAP AROUND (ENTRY DOOR ONLY)-DON JO -WRAP AROUND (VERIFY
SIZE WITH EXISTING MORTISE LOCKSET) DOOR WILL NEED TO BE MODIFIED
FOR NEW CYLINDRICAL LOCK. PROVIDE ALL PLATES ETC. FOR CONVERSION.
SCALE: 3/4"=1'-0"
0" 1' 2' 3'6"
APPLIANCES:TO BE SUPPLIED BY SCL
• REFRIGERATOR -WHIRLPOOL, MODEL# WRF535SWHZ
• DISHWASHER -KITCHEN AID, MODEL# KDFE104HPS
• RANGE -GE, MODEL# JS760SLSS
• MICROWAVE (OVER-THE-RANGE)-GE, MODEL# PVM9005SJSS
1 02/14/2020 ISSUE FOR 100% SD REVIEW
2 03/24/2020 ISSUE FOR 95% REVIEW
3 04/10/2020 ISSUE FOR COORDINATED REVIEW
4 04/15/2020 ISSUE FOR CONSTRUCTION
CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
BAKER SOUTH
BAKER SOUTH
RFD KITCHEN
RENOVATION
MP-001
12309492
GENERAL NOTES
AND SYMBOL
LEGENDS
A. FOX
ALF
3004S
APRIL 15, 2020
MECHANICAL ABBREVIATIONS
BCU BLOWER COIL UNIT
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CC CLEAN CONDENSATE
CO CLEAN OUT
CS CLEAN STEAM
CD CONDENSATE DRAIN
EA EXHAUST AIR
EAG EXHAUST AIR GRILLE
FD FIRE DAMPER
GWR GLYCOL HEATING RETURN
GWS GLYCOL HEATING SUPPLY
HPR HIGH PRESSURE STEAM RETURN
HPS HIGH PRESSURE STEAM SUPPLY
HWR HOT WATER HEATING RETURN
HWS HOT WATER HEATING SUPPLY
LPC LOW PRESSURE CONDENSATE
LPS LOW PRESSURE STEAM
MU MAKE UP WATER
MPC MEDIUM PRESSURE CONDENSATE
MPS MEDIUM PRESSURE STEAM
NG NATURAL GAS
PCWR PROCESS CHILLED WATER RETURN
PCWS PROCESS CHILLED WATER SUPPLY
HG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
RAG RETURN AIR GRILLE
SA SUPPLY AIR
SAD SUPPLY AIR DIFFUSER
VD VOLUME DAMPER
MECHANICAL SYMBOLOGY
AIRFLOW
BACKFLOW PREVENTER
BALANCE VALVE
BALL VALVE
BOTTOM PIPE CONNECTION
BUTTERFLY VALVE
CAP OR PLUG
CHECK VALVE
CIRCULATING PUMP
DIRECTION OF FLOW
DUCT AIRFLOW
DUCT DOWN (EXHAUST OR RETURN)
DUCT DOWN (SUPPLY)
FIRE AND SMOKE DAMPER IN DUCT
FIRE DAMPER IN DUCT
FLANGE CONNECTION
FLEX CONNECTOR
FLEXIBLE CONNECTION
FLEXIBLE DUCT
FLOW METER
FLOW SWITCH
FUSIBLE LINK VALVE
GLOBE VALVE
MANUAL AIRVENT
ORIFICE METER
PIPE DOWN
PIPE UP
PIPING REDUCER (CONCENTRIC)
PIPING REDUCER (ECCENTRIC)
PRESSURE GAUGE
PRESSURE OR TEMPERATURE PETES PLUG
PRESSURE REDUCING VALVE
PRESSURE SWITCH
RECTANGULAR ELBOW
RECTANGULAR ELBOW WITH TURNING VANES
RELIEF VALVE
SMOKE DAMPER IN DUCT
SOLENOID VALVE
STANDARD BRANCH DUCT
STEAM TRAP
STRAINER (DUPLEX)
STRAINER WITH BLOWDOWN VALVE AND CAP
SUPPLY THROUGH NEXT FLOOR OR ROOF
TEMPERATURE WELL
THERMOMETER
THERMOMETER (DIAL)
TOP PIPE CONNECTION
TRIPLE DUTY VALVE
UNION CONNECTION
VACUUM BREAKER
VOLUME DAMPER IN DUCT
CONTROL SYMBOLOGY
2-WAY CONTROL VALVE, DIGITAL
2-WAY CONTROL VALVE, PNEUMATIC
3-WAY CONTROL VALVE, DIGITAL
3-WAY CONTROL VALVE, PNEUMATIC
ADDRESSABLE OUTPUT MODULE (FIRE ALARM INTERFACE)
AIRFLOW CONTROL VALVE (VENTURI OR VORTEX SHEDDING)
AVERAGING SENSOR
BINARY POINT
BUTTERFLY CONTROL DAMPER
CARBON DIOXIDE SENSOR
CONDENSATE SENSOR
CURRENT SENSOR
DEW-POINT SENSOR
DIFFERENTIAL PRESSURE SENSOR
DIFFERENTIAL PRESSURE SENSOR
ELECTRIC TO PNEUMATIC SWITCH
ELECTRIC TO PNEUMATIC TRANSDUCER
END SWITCH
FLOW ELEMENT (METER)
FLOW SENSOR
HIGH LEVEL SWITCH
HUMIDSTAT SENSOR
LIQUID IMERSION TEMPERATURE SENSOR
LOW LEVEL SWITCH
MODULATING
MOTOR
MOTOR STARTER
NETWORK COMMUNICATION POINT, BACnet MSTP
OCCUPANCY SENSOR
OPEN/CLOSE
OPPOSED BLADE CONTROL DAMPER
PARALLEL BLADE CONTROL DAMPER
PNEUMATIC THERMOSTAT
PRESSURE SENSOR
PRESSURE SWITCH
RELATIVE HUMIDITY SENSOR
RELAY
ROOM TEMPERATURE SENSOR WITH ADJUSTABLE
THERMOSTAT
ROOM TEMPERATURE SENSOR WITH OCCUPANCY
OVERRIDE
ROOM TEMPERATURE SENSOR WITH ON/OFF SWITCH
ROOM TEMPERATURE SENSOR WITH VISUAL DISPLAY
ROTATION DETECTOR
SINGLE POINT SENSOR
SMOKE DETECTOR
SPEED COMMAND
START/STOP
STATIC PRESSURE SENSOR
SWITCH
TEMPERATURE SENSOR
TEMPERATURE SENSOR
TEMPERATURE SENSOR WITH ADJUSTABLE SETPOINT
GENERAL DRAWING SYMBOLOGY
DEMOLISHED WORK
EXISTING PIPING TO REMAIN
EXISTING TO REMAIN
EXISTING WORK TO REMAIN
NEW WORK
POINT OF CONNECTION
POINT OF DISCONNECTION
CONTROL ABBREVIATIONS
AI ANALOG INPUT
AO ANALOG OUTPUT
AV ANALOG VALUE
BI BINARY INPUT
BO BINARY OUTPUT
BV BINARY VALUE
F.L. FAIL LAST
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
VFD VARIABLE FREQUENCY DRIVE
MECHANICAL SCOPE OF WORK
1.0 EXTEND DUCT TO NEW RANGE HOOD.
2.0 REPLACE EXISTING FINTUBE WITH NEW.
MECHANICAL GENERAL NOTES
1.0 ALL DUCT DIMENSIONS INDICATED ARE IN INCHES, AND ARE INSIDE FREE AND
CLEAR DIMENSIONS.
2.0 PNEUMATIC TERMINATIONS:
IF COPPER: DEMO BACK TO MAIN AND PROVIDED SOLDERED END CAP
IF POLY: DEMO BACK TO MAIN AND PROVIDE BRASS PLUG
DO NOT USE SHEETMETAL SCREW OR BEND OVER END OF COPPER TUBE.
3.0 INSTALL EQUIPMENT TO ENSURE PROPER ACCESS TO CONTROL DEVICES AND
WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE AND REPAIR.
EQUIPMENT THAT IS NOT INSTALLED WITH THIS REQUIREMENT IN MIND SHALL BE
RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIES ARE
CORRECTED.
4.0 ALL SYSTEM TESTING SHALL BE CONDUCTED PRIOR TO INSULATION,
FIREPROOFING, AND ENCLOSURE IN SHAFTS. ANY RESTORATION WORK REQUIRED
AS A RESULT OF DISTURBING FINISHES OR STRUCTURE IN ORDER TO ACCESS
SYSTEMS REQUIRING REPAIR SHALL BE AT NO COST TO THE UNIVERSITY.
5.0 CUTTING AND PATCHING: THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
CUTTING, FITTING, AND PATCHING TO COMPLETE THE WORK. WHERE EXISTING
CONSTRUCTION IS REMOVED, CAUSING AN EXPOSURE OF UNFINISHED AND/OR
DAMAGED SURFACES, RESULTING SURFACES SHALL BE RECONSTRUCTED WITH
MATERIALS TO MATCH FINISHED AREAS.
6.0 ANY FIRESTOPPING DISTURBED DURING THE COURSE OF WORK SHALL BE
REPAIRED TO MAINTAIN A 2-HOUR FIRE RATING.
7.0 TESTING AND BALANCING: THE CONTRACTOR SHALL BALANCE ALL AIR SYSTEMS
AS INDICATED. SUBMIT RESULTS OF TESTING AND BALANCING ON STANDARD TAB
CONTRACTOR'S FORMS TO THE ENGINEER FOR REVIEW. SYSTEMS SHALL BE
BALANCED TO WITHIN +/- 10% OF DESIGN VALUES. FINAL BALANCING SHALL OCCUR
AFTER ALL LEAKS IN THE BUILDING ENVELOPE HAVE BEEN IDENTIFIED AND
SEALED.
8.0 SEAL ALL PIPE, GRILLE, DIFFUSER, DUCT, CONDUIT PENETRATIONS WITH
APPROPRIATE MATERIALS (CAULK, FOAM, ETC,) THAT ARE IMPENETRABLE TO THE
CONTAINED ORGANISMS AND WITHSTAND REPEATED DECONTAMINATIONS WITH
CLEANING AGENTS.
MECHANICAL SUBMITTAL SCHEDULE
SECTION TITLE REQUIRED
230000 HEATING, VENTILATING & AIR-CONDITIONING -
230523 GENERAL DUTY VALVES FOR HVAC PIPING PRODUCT DATA
230529 HANGERS & SUPPORTS FOR HVAC PRODUCT DATA
230553 IDENTIFICATION FOR HVAC COMPONENTS PRODUCT DATA
230593 TESTING, ADJUSTING & BALANCING FOR HVAC QUALIFICATIONS, INSPECTION AND TEST REPORTS
230700 HVAC DUCT INSULATION PRODUCT DATA
230719 HVAC PIPING INSULATION PRODUCT DATA
230900 INSTRUMENTATION & CONTROL FOR HVAC PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M
232113 HYDRONIC PIPING PRODUCT DATA
233113 METAL DUCTS PRODUCT DATA
1 02/14/2020 ISSUE FOR 100% SD REVIEW
2 03/24/2020 ISSUE FOR 95% REVIEW
3 04/10/2020 ISSUE FOR COORDINATED REVIEW
4 04/15/2020 ISSUE FOR CONSTRUCTION
REF.Ref
DW UPDN1
2 1
REMOVE EXISTING
FIN TUBE AND
PREPARE PIPE FOR
NEW
34
VERIFY
DUCT IN
FIELD
FT-1
4
MP-101
PROVIDE NEW 3"x10" DUCT
FROM NEW GE EXHAUST
HOOD/MICROWAVE DOWN
THROUGH FLOOR
2
3 4
T
2TS-1
5
4
MP-101
B00U
B03
B02
B01
B04
B00T
1
GROUND FLOOR
-1' -0"
1ST FLOOR
9' -0"
BASEMENT
-11' -0"
EXHAUST
WALL CAP
6"Ø EXHAUST
3" x 10" EXHAUST DUCT CONNECTION
TO NEW MICROWAVE/EXHAUST COMBO
TRANSITION FROM RECTANGULAR
DUCT 6"Ø EXHAUST DUCT
COORDINATE NEW 6" EXHAUST DUCT
PENETRATION WITH REMOVED 4" EXHAUST
DUCT PENETRATION FROM OLD OVEN/STOVE
COORDINATE NEW 6" EXHAUST
DUCT PENETRATION WITH
REMOVED 4" EXHAUST DUCT
PENETRATION. REFERENCE
ARCHITECTURAL DRAWINGS FOR
HOW PENETRATION IS TO BE
SEALED.CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
BAKER SOUTH
BAKER SOUTH
RFD KITCHEN
RENOVATION
MP-101
12309492
GROUND FLOOR
MECHANICAL &
PLUMBING
DEMOLITION &
INSTALLATION
PLANS
A. FOX
ALF
3004S
APRIL 15, 2020
#
SCALE: 3/16"=1'-0"
0 2 4 6 12
MP-101 KEYED DEMOLITION NOTES
1 REMOVE EXISTING EXHAUST GRILLE AND CAP DUCT ABOVE CEILING.
2 REMOVE EXISTING SINK. REMOVE ASSOCIATED DRAIN/VENT AND WATER PIPE.
CAP AT FLOOR AND WALL.
3 DISCONNECT EXISTING WATER LINE TO DISH WASHER AND PREPARE FOR
RECONNECTION TO NEW DISHWASHER.
4
DISCONNECT EXISTING COLD WATER PIPING TO SINK AND UNDER COUNTER
INSTANT HOT WATER HEATER. DISCONNECT DRAIN FROM SINK. PREPARE DRAIN
AND WATER PIPING FOR RECONNECTION TO NEW SINK.
SCALE:3/16" = 1'-0"1 GROUND FLOOR MECHANICAL DEMOLITION PLAN
SCALE:3/16" = 1'-0"3 GROUND FLOOR MECHANICAL INSTALLATION PLAN
SCALE:3/16" = 1'-0"2 BASEMENT MECHANICAL PLAN
SCALE:NO SCALE4MICROWAVE/EXHAUST HOOD COMBO EXHAUST DUCT LAYOUT
MP-101 KEYED CONSTRUCTION NOTES
1 REFERENCE DETAIL 4/MP-101 FOR COMBINATION MICROWAVE/EXHAUST HOOD
EXHAUST DUCT LAYOUT.
2
PROVIDE NEW CONTROL VALVE (CV-1) FOR NEW RUNTAL. PROVIDE LOCAL
CONTROL VIA THE TEMPERATURE SENSOR MOUNTED TO THE WALL. PROVIDE NEW
BALANCE VALVE (BV-1) AND ISOLATE FINTUBE WITH ISOLATION VALVES (V-1).
3 RECONNECT DRAIN, DOMESTIC HOT AND COLD WATER PIPING TO THE SINK AND
FAUCET.
4
CONNECT UNDER COUNTER INSTANT WATER HEATER TO COLD WATER PIPING.
WATER HEATER SHALL BE PROVIDED BY THE OWNER AND INSTALLED BY THE
CONTRACTOR. CONFIRM WATER HEATER MODEL AND MANUFACTURER WITH
OWNER PRIOR TO PIPING INSTALLATION.
5 RECONNECT DRAIN AND WATER SUPPLY TO DISHWASHER. PROVIDE PROPER
CHECK VALVES TO PROTECT CITY WATER PIPING.
#
SEQUENCE OF OPERATION
SYSTEM DESCRIPTION
FINTUBE RADIATION (FT-1)
GENERAL
SYSTEM SHALL BE CONTROLLED MANUALLY AND LOCALLY.
ALL SETPOINTS SHALL BE ADJUSTABLE.
DESIGN INTENT: THE NEW FINTUBE (FT-1), LOCATED IN THE KITCHEN, SHALL BE
CONTROLLED LOCALLY BY THE NEW TEMPERATURE SENSOR (TS-1), LOCATED AS
SHOWN IN THE DRAWINGS. THE OTHER FINTUBE WITHIN THE APARTMENT SHALL
CONTINUE TO BE CONTROLLED AS IS.
SETPOINTS
SPACE HEATING TEMPERATURE SETPOINTS:
OCCUPIED:72°F +/-2°F
ZONE TEMPERATURE CONTROL
OCCUPIED HEATING: THE FINTUBE CONTROL VALVE SHALL MODULATE AS NECESSARY
TO MAINTAIN EXISTING HEATING SETPOINT.
1 02/14/2020 ISSUE FOR 100% SD REVIEW
2 03/24/2020 ISSUE FOR 95% REVIEW
3 04/10/2020 ISSUE FOR COORDINATED REVIEW
4 04/15/2020 ISSUE FOR CONSTRUCTION
CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
BAKER SOUTH
BAKER SOUTH
RFD KITCHEN
RENOVATION
MP-501
12309492
SCHEDULES
A. FOX
ALF
3004S
APRIL 15, 2020
DUCT SCHEDULE AND SPECIFICATIONS
SERVICE PRESSURE CLASS SEAL CLASS LEAKAGE CLASS DUCT MATERIAL LINING DUCT INSULATION
EXHAUST RECTANGULAR, CONCEALED 2" POS A 6 G90 GALVANIZED NONE NONE
EXHAUST ROUND, CONCEALED 2" POS A 3 G90 GALVANIZED NONE NONE
CONTROL VALVE SCHEDULE & SPEC
TAG MANF VALVE MODEL OPERATOR MODEL
SIZE
(IN)CV CAPACITY
(GPM)
MAX PD
(PSIG)TYPE NOTES
CV-1 BELIMO CCV-B210 TF24-SR-T US 1/2 1.2 0.5 4
2-WAY, PROPORTIONAL,
NON-SPRING RETURN FAIL LAST
FINTUBE RADIATION SCHEDULE
TAG LOCATION BOD MANF BOD MODEL
TUBE DIA
(IN)
HEAT OUTPUT
(BTUH/LF)
RUNTAL LENGTH
(LF)
TOTAL OUTPUT
(BTUH)
FLOW RATE
(GPM)
ENT AIR TEMP
(˚ F)
AVG WATER TEMP
(˚ F)NOTES
FT-1 G17
RUNTAL
RADIATORS UF-4 1/2" NTP 930 3 2,790 0.5 170 190 1
SPECS:
1 ACCEPTABLE MANUFACTURERS: BELIMO, VSI
2 ELECTRIC INPUT: 4-20mA OR 0-10VDC
3 2-WAY VALVES: EQUAL PERCENTAGE FLOW CHARACTERISTIC.
4 CONSTRUCTION: CHARACTERIZING DISK, FORGED BRASS, NICKEL PLATED BODY, STAINLESS STEEL BALL AND STEM, FIBERGLASS
REINFORCED PTFE SEAT.
5 RATINGS: 400 PSI PRESSURE, 0-212 F MEDIA TEMPERATURE RANGE.
6 ALL CONTROL WIRING SHALL BE INSTALLED IN CONDUIT.
CONTROL WIRING SHALL BE UNSPLICED FROM THE CONTROLLER TO THE SENSOR OR DEVICE.
CONTROL WIRING SHALL NOT BE ROUTED IN THE SAME RACEWAY AS POWER WIRING.
CONTROL WIRING SHALL BE COLOR CODED AND LABELED AT ALL POINTS OF TERMINATION.
NOTES:
1 RUNTAL PROVIDED BY OWNER, INTALLED BY CONTRACTOR.
SPECS:
1 HEAT OUTPUT INDICATED IS THE OUTPUT AT STANDARD RATING CONDITIONS CORRECTED FOR WATER VELOCITY, ENTERING AIR TEMPERATURES, AND
MOUNTING HEIGHTS, AS REQUIRED.
2 ACCESSORIES: END TRIM, INSIDE CORNER, OUTSIDE CORNER, END ENCLOSURE, ACCESS PANEL.
3 INSTALL IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.
PLUMBING & HVAC PIPE AND FITTING SCHEDULE AND SPECIFICATIONS
PIPE SERVICE ABBREVIATION PIPE SIZE MATERIAL FITTINGS JOINT INSULATION
DOMESTIC COLD WATER DCW 1/2" - 6" ASTM B88 TYPE L COPPER ASTM B16.22 STD WROUGHT COPPER ASTM B32 SOLDER 1", FIBERGLASS OR FLEXIBLE ELASTOMERIC
DOMESTIC HOT WATER DHW 1/2" - 6" ASTM B88 TYPE L COPPER ASTM B16.22 STD WROUGHT COPPER ASTM B32 SOLDER 1", FIBERGLASS OR FLEXIBLE ELASTOMERIC
SANITARY WASTE / VENT SAN / V ALL SIZES
ASTM A74, ASTM A888 SERVICE WEIGHT CAST IRON
ASTM D 1784, 1785 & 2665 PVC SCHEDULE 40 PIPE
ASTM A74, ASTM A888 CAST IRON NO-HUB
ASTM D 1784, 1785 & 2665 PVC SCHEDULE 40 SOLID WALL PIPE
ASTM C1277 NEOPRENE GASKET SS BANDS
ASTM D 2564 SOLVENT CEMENT, ASTM F 6, ASTM F 656 PRIMER
NA
HEATING HOT WATER HWS / R 1-1/4" & BELOW ASTM B88 TYPE L COPPER ASTM B16.22 STD WROUGHT COPPER ASTM B32 SOLDER 1-1/2",PRE-FORMED MINERAL FIBERGLASS, ASTM C547 TYPE I
SPECS:
1 SOLDER FILLER METALS: ASTM B32, LEAD-FREE ALLOYS. INCLUDE WATER FLUSHABLE FLUX ACCORDING TO ASTM B813.
2 DIELECTRIC FITTINGS: USE FLANGES OR COUPLINGS. UNIONS ARE UNACCEPTABLE.
3 INSTALL ESCUTCHEONS FOR PENETRATIONS OF WALLS, CEILING, AND FLOORS
4 INSTALL PLUMBING SYSTEMS TO FACILITATE SERVICE, MAINTENANCE AND REPAIR OR REPLACEMENT OF COMPONENTS.
5 ALL WASTE PIPING SHALL BE PITCHED AT 1/8" PER FOOT. ALL SUPPLY PIPING SHALL BE PITCHED BACK TOWARDS CONNECTION TO THE ROOM ENTRANCE.
6 PROVIDE VAPOR RETARDER ON PIPING INSULATION SYSTEMS CARRYING FLUIDS WITH AN OPERATING TEMPERATURE LOWER THAN 60 ⁰F.
7 DO NOT ENCLOSE, COVER OR PUT PLUMBING PIPING SYSTEMS INTO OPERATION UNTIL IT HAS BEEN INSPECTED AND APPROVED BY THE AUTHORITIES HAVING JURISDICTION.
8 LEAVE NEW, ALTERED, EXTENDED, OR REPLACED DOMESTIC WATER PIPING UNCOVERED AND UNCONCEALED UNTIL IT HAS BEEN TESTED. EXPOSE WORK THAT WAS COVERED OR CONCEALED BEFORE IT WAS TESTED.
9 ALL INSULATION AND ADHESIVE SHALL HAVE A MAXIMUM FLAME-SPREAD INDEX OF 25 AND A MAXIMUM SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED IN ACCORDANCE WITH ASTM E84.
10 TESTING OF DOMESTIC WATER PIPING:
CAP AND SUBJECT DOMESTIC WATER PIPING TO STATIC WATER PRESSURE OF 50 PSIG ABOVE OPERATING PRESSURE, WITHOUT EXCEEDING PRESSURE RATING OF PIPING SYSTEM MATERIALS.
ISOLATE TEST SOURCE AND ALLOW TO STAND FOR FOUR HOURS. LEAKS AND LOSS IN TEST PRESSURE CONSTITUTE DEFECTS THAT MUST BE REPAIRED.
REPAIR LEAKS AND DEFECTS WITH NEW MATERIALS AND RETEST PIPING UNTIL SATISFACTORY RESULTS ARE OBTAINED.
11 TESTING OF DOMESTIC WASTE AND VENT PIPING:
CAP AND SUBJECT DOMESTIC WASTE AND VENT PIPING TO STATIC WATER PRESSURE OF 10 FEET HEAD PRESSURE ABOVE HIGHEST POINT OF SYSTEM UNDERGOING TEST.
ISOLATE TEST SOURCE AND ALLOW TO STAND UNTIL SYSTEM CAN BE VISUALLY INSPECTED BY AUTHORITY HAVING JURISDICTION. LEAKS CONSTITUTE DEFECTS THAT MUST BE REPAIRED.
REPAIR LEAKS AND DEFECTS WITH NEW MATERIALS AND RETEST PIPING UNTIL SATISFACTORY RESULTS ARE OBTAINED.
12 CLEANING AND DISINFECTION OF POTABLE WATER SYSTEMS:
FLUSH PIPING SYSTEM WITH CLEAN, POTABLE WATER UNTIL DIRTY WATER DOES NOT APPEAR AT OUTLETS.
FILL SYSTEM WITH WATER/CHLORINE SOLUTION WITH AT LEAST 50 PPM OF CHLORINE. ISOLATE WITH VALVES AND ALLOW TO STAND FOR 24 HOURS. DRAIN TO SANITARY.
FLUSH SYSTEM WITH CLEAN, POTABLE WATER UNTIL NO TSP REMAINS IN WATER COMING FROM SYSTEM.
SUBMIT WATER SAMPLES IN STERILE BOTTLES TO AUTHORITIES HAVING JURISDICTION. REPEAT PROCEDURE IF BIOLOGICAL EXAMINATION SHOWS EVIDENCE OF CONTAMINATION.
13 INSTALL UNIONS IN PIPING, NPS 2 AND SMALLER, ADJACENT TO VALVES, AT FINAL CONNECTIONS OF EQUIPMENT, AND ELSEWHERE AS INDICATED.
SPECS:
1 ALL DUCTWORK AND ACCESSORIES SHALL BE FABRICATED AND INSTALLED IN COMPLIANCE WITH THE LATEST ISSUE OF SMACNA'S HVAC DUCT
CONSTRUCTION STANDARDS -METAL AND FLEXIBLE.
2 CONSTRUCT TEES, BENDS, AND ELBOWS WITH RADIUS OF NOT LESS THAN 1.0 TIMES THE WIDTH OF DUCT ON CENTER LINES.
3 INCREASE DUCT SIZES GRADUALLY, AND IN COMPLIANCE WITH FIGURE 4-7 OF SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS -METAL AND
FLEXIBLE.
4 SEALANTS AND GASKETS: SURFACE BURNING CHARACTERISTICS SHALL BE A MAXIMUM FLAME-SPREAD INDEX OF 25, AND MAXIMUM SMOKE-
DEVELOPED INDEX OF 50 WHEN TESTED TO UL 723.
5 REMOVE SURFACE CONTAMINANTS AND DEPOSITS FROM DUCTWORK AND EQUIPMENT PRIOR TO TESTING.
6 LEAK TESTING OF DUCTWORK SHALL BE IN ACCORDANCE WITH SMACNA'S HVAC AIR DUCT LEAKAGE TEST MANUAL.
CONTROL DEVICE SCHEDULE
TAG DESCRIPTION
MANUFACTURER
(BOD)
MODEL
(BOD)NOTES
TS-1 TEMPERATURE
SENSOR AUTOMATED LOGIC RS PRO
10 KΩ THERMISTER, 0.4 ˚F RESOLUTION, ±0.5 ˚F ACCURACY, WITH
MANUFACTURERS STANDARD LOCKING COVER, EXPOSED WARMER/COOLER
SETPOINT ADJUSTMENT, ALPHA-NUMERIC DISPLAY OF TEMPERATURE,
OCCUPANCY OVERRIDE, AND CONNECTION HEAD FOR WIRING CONNECTION,
TWISTED SHIELDED PAIR CABLE. RTD ACCEPTABLE IN LIEU OF THERMISTER.
SPECS:
1 MOUNT WALL TEMPERATURE SENSOR PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
PIPING ACCESSORIES SCHEDULE AND SPECIFICATIONS
TAG DEVICE
MANUFACTURER
(BOD)
MODEL
(BOD)PRESSURE RATING SPECIFICATIONS
BV-1 BALANCE VALVE 1/2 INCH BELL & GOSSETT
CB SERIES,
CB1/2 200 PSIG @ 250 DEGF
0.5 GPM RANGE, BRONZE, BALL OR PLUG TYPE BODY WITH CALIBRATED ORIFICE OR VENTURI; GLASS AND CARBON
FILLED TFE OR EPDM SEAT RINGS, EPDM STEM O-RING, WITH INTEGRAL SEALS FOR PORTABLE DIFFERENTIAL PRESSURE
METER, WITH LEVEL HANDLE AND MEMORY STOP TO RETAIN SET POSITION.
V-1 SHUT-OFF BALL VALVE WATTS B6000-SS 300 PSIG WOG MSS SP-110, 2-PIECE, STANDARD PORT, BRONZE BODY, 316 SS BALL & STEM, PTFE OR TFE SEAT
1 02/14/2020 ISSUE FOR 100% SD REVIEW
2 03/24/2020 ISSUE FOR 95% REVIEW
3 04/10/2020 ISSUE FOR COORDINATED REVIEW
4 04/15/2020 ISSUE FOR CONSTRUCTION
ABBREVIATIONS
A - AMPERE
AFC - ABOVE FINISHED CEILING
AFF - ABOVE FINISHED FLOOR
AIC - AMPS INTERRUPTING CAPACITY
BLDG - BUILDING
C - CONDUIT
CKT - CIRCUIT
CL - CENTERLINE
DWG - DRAWING
E - EXISTING TO REMAIN
EC - ELECTRICAL CONTRACTOR
EM - EMERGENCY
EMT - ELECTRICAL METALLIC TUBING
FVNR - FULL VOLTAGE NON-REVERSING
G - GROUND
GC - GENERAL CONTRACTOR
GFI - GROUND FAULT INTERRUPTER
JB - JUNCTION BOX
KVA - KILOVOLTAMPERES
KW - KILOWATT
MC - MECHANICAL CONTRACTOR
MCB - MAIN CIRCUIT BREAKER
MCW - MICROWAVE
MDP - MAIN DISTRIBUTION PANEL
MLO - MAIN LUG ONLY
P - POLE
PH - PHASE
PVC - POLYVINYL CHLORIDE
R - REMOVE
RE - REPLACE EXISTING
REL - RELOCATED
RI - REMOVE AND REINSTALL
RL - RELOCATE EXISTING
RM - ROOM
UTV - UNDERVOLTAGE TRIP
V - VOLT
W - WIRE
WP - WEATHER PROOF
XFMR - TRANSFORMER
ELECTRICAL NOTES
1. ALL WORK SHALL BE PERFORMED AND INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF THE CORNELL UNIVERSITY ELECTRICAL
STANDARDS. THE NATION ELECTRIC CODE(NFPA 70) AND ANY GOVERNING CODES AND STANDARDS HAVING JURISDICTION.
2. REFER TO CORNELL ELECTRICAL STANDARDS FOR ALL SPECIFICATION REQUIREMENTS.
3. ALL EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH ARTICLE 250 OF THE NATIONAL ELECTRIC CODE.
4. CONTRACTORS SHALL PAY FOR AND SECURE ALL PERMITS AND UNDERWRITERS CERTIFICATES.
5. PRIOR TO BID, THE CONTRACTOR SHALL VISIT THE SITE TO FAMILIARIZE HIMSELF WITH THE EXISTING FIELD CONDITIONS. HIS BID SHALL
INCLUDE THE FURNISHING AND INSTALLATION OF ALL LABOR, TOOLS, MATERIAL, EQUIPMENT, SERVICES AND RELATED ACCESSORIES
NECESSARY FOR THE COMPLETE INSTALLATION OF THE ELECTRICAL WORK SHOWN ON THE DRAWINGS AND REQUIRED BY CODE.
6. THE ELECTRICAL CONTRACTOR SHALL FURNISH ALL METERS, INSTRUMENTS, CABLE CONNECTION, EQUIPMENT, OR APPARATUS ESSAY FOR
MAKING ALL TESTS.
7. THE CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL EQUIPMENT AND SYSTEMS AGAINST HARMFUL EXPOSURE OR ACCUMULATION OF
DUST/MOISTURE, CORROSION OR OTHER FORMS OF DAMAGE. CLEAN AND RESTORE DAMAGED FINISHES.
8. CONTRACTOR SHALL COORDINATE PROJECT WORK WITH ALL TRADES AND ASSIST IN SCHEDULING WITH ALL TRADES.
9. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, PATCHING, AND REFINISHING OF WORK AREA RELATED TO ELECTRICAL PROJECT
WORK. RESTORE AREA TO ORIGINAL CONDITION.
10. CONTRACTOR IS RESPONSIBLE FOR REMOVAL OF ALL WASTE MATERIALS IN A LAWFUL MANNER AND LEAVE THE SITE FREE OF ALL DEBRIS.
11. THE TERM "PROVIDE" DENOTES TO FURNISH AND INSTALL.
12. THE TERM "WIRING" DENOTES WRING AND RACEWAY.
13. UNLESS OTHERWISE NOTED, WHERE A DEVICE OR WIRING IS REMOVED, THE CONTRACTOR SHALL DISCONNECT AND REMOVE THE
ASSOCIATED WIRING AND CONTROLS.
14. WHERE A DEVICE IS RELOCATED, DISCONNECT, REMOVE AND STORE THE NOTED DEVICE. EXISTING WIRING SHALL REMAIN. PROVIDE
RELOCATION OF DEVICE PER CONSTRUCTION SCHEDULE. RECONNECT TO EXISTING WIRING. EXTEND WIRING AS REQUIRED, MATCH EXISTING.
15. THE CONTRACTOR IS RESPONSIBLE FOR MAINTAINING SERVICE TO THE BALANCE OF ANY EXISTING CIRCUITS THAT ARE AFFECTED BY THIS
PROJECT AND THAT EXTEND OUT OF THE PROJECT AREA. EXTEND WIRING AS REQUIRED, MATCH EXISTING.
16. COORDINATE ALL DEMOLITION WORK WITH CORNELL UNIVERSITY PRIOR TO ANY SHUTDOWNS OR REMOVAL OF DEVICES AND/OR WIRING.
17. COORDINATE ALL COMMUNICATIONS WORK WITH CORNELL UNIVERSITY I/T GROUP.
18. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COMPLETING A PANEL WALK DOWN FOR EACH PANEL BEING AFFECTED FOR THIS PROJECT
TO DETERMINE REQUIREMENTS AND COORDINATE SHUTDOWNS WITH CORNING.
ELECTRICAL SYMBOLS LEGEND
SYMBOL DESCRIPTION
J JUNCTION BOX
UNDER CABINET LIGHT FIXTURE
RECESSED CAN LIGHT FIXTURE
RECEPTACLE
GFCI RECEPTACLE
SMOKE DETECTOR
DATA OUTLET
THREE WAY SWITCH
OCCUPANY SENSOR
3
HEAT DETECTOR
135
BUILDING WIRE AND CABLE
A. PROVIDE PRODUCTS AS FOLLOWS:
1. SOLID CONDUCTOR FOR FEEDERS AND BRANCH CIRCUITS 10 AWG AND SMALLER.
2. STRANDED CONDUCTORS FOR CONTROL CIRCUITS.
3. CONDUCTOR NOT SMALLER THAN #12 AWG FOR POWER AND LIGHTING CIRCUITS.
4. CONDUCTOR NOT SMALLER THAN #16 AWG FOR CONTROL CIRCUITS.
5. 10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS LONGER THAN 75 FEET.
6. 10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS LONGER THAN 200 FEET.
B. WIRING METHODS: PROVIDE THE FOLLOWING WIRING METHODS:
1. CONCEALED DRY INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN INSULATION, IN
RACEWAY.
2. ABOVE ACCESSIBLE CEILINGS: USE ONLY BUILDING WIRE, TYPE THHN/THWN INSULATION, IN RACEWAY.
3. WET OR DAMP INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN INSULATION, IN
RACEWAY.
4. UNDERGROUND LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN INSULATION, IN RACEWAY.
C. WIRE AND CABLE ROUTING INDICATED IS APPROXIMATE UNLESS DIMENSIONED. INCLUDE WIRE AND CABLE
LENGTHS WITHIN 10 FT OF LENGTH SHOWN.
D. COMPLETELY AND THOROUGHLY SWAB RACEWAY BEFORE INSTALLING WIRE.
E. NEATLY TRAIN AND LACE WIRING INSIDE BOXES, EQUIPMENT, AND PANELBOARDS.
F. SPECIAL TECHNIQUES--BUILDING WIRE IN RACEWAY:
1. PULL CONDUCTORS INTO RACEWAY AT SAME TIME.
2. INSTALL BUILDING WIRE 4 AWG AND LARGER WITH PULLING EQUIPMENT.
G. SPECIAL TECHNIQUES - CABLE:
1. PROTECT EXPOSED CABLE FROM DAMAGE.
2. SUPPORT CABLES ABOVE ACCESSIBLE CEILING, USING SPRING METAL CLIPS OR CABLE TIES TO SUPPORT
CABLES FROM STRUCTURE OR CEILING SUSPENSION SYSTEM. DO NOT REST CABLE ON CEILING PANELS.
3. USE SUITABLE CABLE FITTINGS AND CONNECTORS.
H. SPECIAL TECHNIQUES - DIRECT BURIAL CABLE:
1. TRENCH AND BACKFILL FOR DIRECT BURIAL CABLE INSTALLATION. INSTALL WARNING TAPE ALONG ENTIRE
LENGTH OF DIRECT BURIAL CABLE, WITHIN 3 INCHES OF GRADE.
2. USE SUITABLE DIRECT BURIAL CABLE FITTINGS AND CONNECTORS.
I. SPECIAL TECHNIQUES - WIRING CONNECTIONS:
1. CLEAN CONDUCTOR SURFACES BEFORE INSTALLING LUGS AND CONNECTORS.
2. MAKE SPLICES, TAPS, AND TERMINATIONS TO CARRY FULL AMPACITY OF CONDUCTORS WITH NO
PERCEPTIBLE TEMPERATURE RISE.
3. TAPE UNINSULATED CONDUCTORS AND CONNECTORS WITH ELECTRICAL TAPE TO 150 PERCENT OF
INSULATION RATING OF CONDUCTOR.
4. INSTALL SPLIT BOLT CONNECTORS OR MULTI-TAP BLOCKS FOR COPPER CONDUCTOR SPLICES AND TAPS, 6
AWG AND LARGER.
5. INSTALL SOLDERLESS PRESSURE CONNECTORS WITH INSULATING COVERS FOR COPPER CONDUCTOR
SPLICES AND TAPS, 8 AWG AND SMALLER.
6. INSTALL INSULATED SPRING WIRE CONNECTORS WITH PLASTIC CAPS FOR COPPER CONDUCTOR SPLICES
AND TAPS, 10 AWG AND SMALLER.
7. TERMINATE EXISTING ALUMINUM CONDUCTORS WITH TIN-PLATED, ALUMINUM-BODIED COMPRESSION
CONNECTORS ONLY. FILL WITH ANTI-OXIDANT COMPOUND BEFORE INSTALLING CONDUCTOR.
8. INSTALL SUITABLE REDUCING CONNECTORS OR MECHANICAL CONNECTOR ADAPTORS FOR CONNECTING
ALUMINUM CONDUCTORS TO COPPER CONDUCTORS.
J. GROUND CONDUCTORS:
1. FOR 6 AWG AND SMALLER: GREEN.
2. FOR 4 AWG AND LARGER: IDENTIFY WITH GREEN TAPE AT BOTH ENDS AND VISIBLE POINTS INCLUDING
JUNCTION BOXES.
K. ALL WIRING SHALL BE #12 CU UNLESS SPECIFIED OTHERWISE.
ELECTRICAL SPECIFICATIONS
A. ALL ELECTRICAL WORK TO CONFORM TO:
1. NFPA 70 (NATIONAL ELECTRIC CODE) - CURRENT VERSION
2. NECA (NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION) - STANDARD OF INSTALLATION
3. NETA ATS (INTERNATIONAL ELECTRICAL TESTING ASSOCIATION) - ACCEPTANCE TESTING SPECIFICATIONS
FOR ELECTRICAL POWER DISTRIBUTION EQUIPMENT AND SYSTEMS.
4. NFPA 72 (NATIONAL FIRE PROTECTION ASSOCIATION - NATIONAL FIRE ALARM CODE).
5. ALL APPLICABLE LOCAL CODES.
B. ALL WORK SHOWN ON THIS DRAWING IS THE RESPONSIBILITY OF THE CONTRACTOR, UNLESS CLEARLY
INDICATED AS PART OF ANOTHER PRIME CONTRACT.
C. PROVIDE TEMPORARY POWER REQUIRED FOR ALL TRADES.
D. MATCH OWNERS EXISTING STANDARD EQUIPMENT.
E. COORDINATE WORK TO MINIMIZE OUTAGE DURATION.
F. OBTAIN ALL REQUIRED PERMITS & INSPECTIONS.
G. PROVIDE FOR ELECTRICAL INSPECTIONS AND SUBMIT REPORTS TO THE OWNER.
H. SUBMIT O&M MANUALS TO OWNER UPON COMPLETION OF WORK.
I. PROVIDE TRAINING SESSION FOR DESIGNATED MAINTENANCE PERSONNEL.
J. PROVIDE SUBMITTALS FOR ALL ELECTRICAL EQUIPMENT, EXCLUDING WIRE, CONDUIT, AND FASTENERS.
1. HANDHOLES.
2. PANELBOARDS - SHOP DRAWINGS (INDICATE OUTLINE AND SUPPORT POINT DIMENSIONS, VOLTAGE, MAIN
BUS AMPACITY, INTEGRATED SHORT CIRCUIT AMPERE RATING, CIRCUIT BREAKER AND FUSIBLE
SWITCH ARRANGEMENT AND SIZES) AND CATALOG DATA SHOWING SPECIFIED FEATURES OF STANDARD
PRODUCTS.
3. ENCLOSED SWITCHES - SWITCH RATINGS AND ENCLOSURE DIMENSIONS.
4. DEVICES - MANUFACTURER'S CATALOG INFORMATION SHOWING DIMENSIONS, COLORS, AND
CONFIGURATIONS.
5. LUMINAIRES (INCLUDING EMERGENCY & EXIT FIXTURES) - CATALOG INFORMATION SHOWING DIMENSIONS,
RATINGS, AND PERFORMANCE DATA.
K. SELECT MATERIALS, SIZES, AND TYPES OF ANCHORS, FASTENERS, AND SUPPORTS TO CARRY LOADS OF
EQUIPMENT AND RACEWAY, INCLUDING WEIGHT OF WIRE AND CABLE IN RACEWAY.
GROUNDING SYSTEMS
A. GROUNDING SYSTEM RESISTANCE: 25 OHMS.
B. GROUNDING SYSTEMS:
1. MECHANICAL CONNECTORS: BRONZE CONNECTORS, SUITABLE FOR GROUNDING AND BONDING
APPLICATIONS, IN CONFIGURATIONS REQUIRED FOR PARTICULAR INSTALLATION.
C. EXOTHERMIC CONNECTIONS: EXOTHERMIC MATERIALS, ACCESSORIES, AND TOOLS FOR PREPARING AND MAKING
PERMANENT FIELD CONNECTIONS BETWEEN GROUNDING SYSTEM COMPONENTS.
D. WIRE: STRANDED COPPER.
E. GROUNDING ELECTRODE CONDUCTOR: SIZE TO MEET NFPA 70 AND LOCAL MUNICIPALITY REQUIREMENTS.
F. INSTALLATION:
1. EQUIPMENT GROUNDING CONDUCTOR: INSTALL SEPARATE, INSULATED CONDUCTOR WITHIN EACH FEEDER
AND BRANCH CIRCUIT RACEWAY. TERMINATE EACH END ON SUITABLE LUG, BUS, OR BUSHING.
2. DO NOT FASTEN SUPPORTS TO PIPES, DUCTS, MECHANICAL EQUIPMENT, OR CONDUIT.
3. OBTAIN PERMISSION FROM ARCHITECT/ENGINEER BEFORE USING POWDER-ACTUATED ANCHORS OR
DRILLING OR CUTTING STRUCTURAL MEMBERS.
HANGERS AND SUPPORTS
A. ANCHORS & FASTENERS TO BE CORROSION RESISTANT.
B. ANCHOR AND FASTEN ELECTRICAL PRODUCTS TO BUILDING ELEMENTS AND FINISHES AS FOLLOWS:
1. CONCRETE STRUCTURAL ELEMENTS: PROVIDE EXPANSION ANCHORS.
2. STEEL STRUCTURAL ELEMENTS: PROVIDE BEAM CLAMPS AND SPRING STEEL CLIPS.
3. CONCRETE SURFACES: PROVIDE EXPANSION ANCHORS.
4. HOLLOW MASONRY, PLASTER, AND GYPSUM BOARD PARTITIONS: PROVIDE TOGGLE BOLTS AND HOLLOW
WALL FASTENERS.
5. SOLID MASONRY WALLS: PROVIDE EXPANSION ANCHORS.
6. SHEET METAL: PROVIDE SHEET METAL SCREWS.
7. WOOD ELEMENTS: PROVIDE WOOD SCREWS.
C. SUPPORTS:
1. FABRICATE SUPPORTS FROM STRUCTURAL STEEL OR FORMED STEEL MEMBERS. RIGIDLY WELD MEMBERS
OR INSTALL HEXAGON HEAD BOLTS TO PRESENT NEAT APPEARANCE WITH ADEQUATE
STRENGTH AND RIGIDITY. INSTALL SPRING LOCK WASHERS UNDER NUTS.
2. INSTALL SURFACE MOUNTED CABINETS AND PANELBOARDS WITH MINIMUM OF FOUR ANCHORS.
3. IN WET AND DAMP LOCATIONS INSTALL STEEL CHANNEL SUPPORTS TO STAND CABINETS AND
PANELBOARDS 1 INCH OFF WALL.
4. INSTALL SHEET METAL CHANNEL TO BRIDGE STUDS ABOVE AND BELOW CABINETS AND PANELBOARDS
RECESSED IN HOLLOW PARTITIONS.
EXISTING WORK
A. PRIOR TO CONSTRUCTION & INSTALLATION, CONTRACTOR TO VERIFY EXISTING CONDITIONS AND NOTIFY
ARCHITECT/ENGINEER OF CONFLICTS OR CONDITIONS WHICH INTERFERE WITH INSTALLATION AS SET FORTH IN
CONTRACT DOCUMENTS.
B. CONTRACTOR RESPONSIBLE FOR ALL NEW FLOOR OPENINGS, EXCAVATIONS, AND PENETRATIONS,UNLESS
SPECIFICALLY NOTED. UNLESS SPECIFICALLY NOTED, UPON COMPLETION, ALL PENETRATIONS TO BE
SEALED TO MAINTAIN FIRE RATING AS SPECIFIED ON ARCHITECTURAL DRAWINGS.
C. ALL CUTTING AND PATCHING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR, UNLESS CLEARLY INDICATED
AS PART OF ANOTHER PRIME CONTRACT.
D. COORDINATE ANY NEW ROOF PENETRATIONS WITH THE OTHER TRADES.
E. REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE NEW CONSTRUCTION.
F. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND EXTENSION WORK.
G. MAINTAIN ACCESS TO EXISTING BOXES AND OTHER INSTALLATIONS REMAINING ACTIVE AND REQUIRING ACCESS.
MODIFY INSTALLATION OR PROVIDE ACCESS PANEL.
H. EXTEND EXISTING RACEWAY AND BOX INSTALLATIONS USING MATERIALS AND METHODS COMPATIBLE WITH
EXISTING ELECTRICAL INSTALLATIONS, OR AS SPECIFIED.
I. CLEAN AND REPAIR EXISTING COMPONENTS TO REMAIN OR TO BE REINSTALLED.
J. PROVIDE ACCESS TO EXISTING WIRING CONNECTIONS REMAINING ACTIVE AND REQUIRING ACCESS. MODIFY
INSTALLATION OR INSTALL ACCESS PANEL.
K. EXTEND EXISTING CIRCUITS USING MATERIALS AND METHODS COMPATIBLE WITH EXISTING ELECTRICAL
INSTALLATIONS, OR AS SPECIFIED.
L. RING OUT CIRCUITS IN EXISTING PANEL AFFECTED BY THE WORK. WHERE ADDITIONAL CIRCUITS ARE NEEDED,
REUSE CIRCUITS AVAILABLE FOR REUSE. INSTALL NEW BREAKERS.
M. TAG UNUSED CIRCUITS AS SPARE AND SWITCH BREAKER TO THE "OFF" POSITION.
N. WHERE EXISTING CIRCUITS ARE INDICATED TO BE REUSED, USE SENSING MEASURING DEVICES TO VERIFY
CIRCUITS FEEDING PROJECT AREA OR ARE NOT IN USE.
O. PROVIDE NEW UPDATED DIRECTORIES WHERE MORE THAN THREE CIRCUITS HAVE BEEN MODIFIED OR REWIRED.
P. IDENTIFY SALVAGE ITEMS IN COOPERATION WITH OWNER. REMOVE AND PROTECT ITEMS TO BE SALVAGED AND
TURN OVER TO OWNER.
Q. CAREFULLY REMOVE EQUIPMENT, MATERIALS, OR FIXTURES WHICH ARE TO BE REUSED.
MINOR ELECTRICAL DEMOLITION
A. DEMOLITION DRAWINGS ARE BASED ON CASUAL FIELD OBSERVATION AND EXISTING RECORD DOCUMENTS.
REPORT DISCREPANCIES TO ARCHITECT/ENGINEER BEFORE DISTURBING EXISTING INSTALLATION.
B. CEASE OPERATIONS IMMEDIATELY WHEN STRUCTURE APPEARS TO BE IN DANGER AND NOTIFY
ARCHITECT/ENGINEER. DO NOT RESUME OPERATIONS UNTIL DIRECTED.
C. VERIFY WIRING AND EQUIPMENT INDICATED TO BE DEMOLISHED SERVE ONLY ABANDONED FACILITIES.
D. PROVIDE TEMPORARY EGRESS SIGNAGE AND EMERGENCY LIGHTING.
E. DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS SCHEDULED FOR REMOVAL. REMOVE
CONDUIT, WIRE, BOXES, AND FASTENING DEVICES TO AVOID ANY INTERFERENCE WITH NEW INSTALLATION.
F. INSTALL TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING
CONSTRUCTION.
G. REMOVE EXPOSED ABANDONED WIRE, CABLE, CONDUIT, GROUNDING AND BONDING COMPONENTS, FASTENERS
AND SUPPORTS, AND ELECTRICAL IDENTIFICATION COMPONENTS, INCLUDING ABANDONED COMPONENTS
ABOVE ACCESSIBLE C CEILING FINISHES. CUT EMBEDDED CONDUITS AND SUPPORT ELEMENTS FLUSH WITH
WALLS AND FLOORS. PATCH SURFACES DAMAGED BY REMOVAL OF EXISTING COMPONENTS.
H. DISCONNECT ABANDONED CIRCUITS AND OUTLETS AND REMOVE ABANDONED RACEWAY, OUTLETS, BOXES,
WIRE, AND CABLE INCLUDING ABOVE ACCESSIBLE CEILING FINISHES. CUT RACEWAY FLUSH WITH WALLS AND
FLOORS, AND PATCH SURFACES. REMOVE CONCEALED ABANDONED RACEWAY TO ITS SOURCE.
I. RECONNECT EQUIPMENT BEING DISTURBED BY RENOVATION WORK AND REQUIRED FOR CONTINUED SERVICE TO
NEAREST AVAILABLE PANEL. REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE
NEW CONSTRUCTION.
J. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND EXTENSION WORK.
K. CLEAN AND REPAIR EXISTING EQUIPMENT TO REMAIN (AFFECTED BY THE SCOPE OF THE PROJECT) OR TO BE
REINSTALLED.
L. PROTECT AND RETAIN POWER TO EXISTING ACTIVE EQUIPMENT REMAINING.
M. CAP ABANDONED EMPTY CONDUIT AT BOTH ENDS AND MARK AS SPARE.
FIRE ALARM SYSTEM
A. SYSTEM DESCRIPTION: NONCODED ADDRESSABLE SYSTEM, WITH AUTOMATIC SENSITIVITY CONTROL OF
CERTAIN SMOKE DETECTORS AND MULTIPLEXED SIGNAL TRANSMISSION, DEDICATED TO FIRE-ALARM SERVICE
ONLY.
B. SUBMITTALS
1. PRODUCT DATA: FOR EACH TYPE OF PRODUCT INDICATED.
2. SHOP DRAWINGS: FOR FIRE-ALARM SYSTEM. INCLUDE PLANS, ELEVATIONS, SECTIONS, DETAILS, AND
ATTACHMENTS TO OTHER WORK.
C. FIELD QUALITY-CONTROL REPORTS
1. OPERATION AND MAINTENANCE DATA: FOR FIRE-ALARM SYSTEMS AND COMPONENTS TO INCLUDE IN
EMERGENCY, OPERATION, AND MAINTENANCE MANUALS.
D. INSTALLER QUALIFICATIONS:
1. PERSONNEL SHALL BE TRAINED AND CERTIFIED BY MANUFACTURER FOR INSTALLATION OF UNITS.
2. INSTALLATION SHALL BE BY PERSONNEL CERTIFIED BY NICET AS FIRE-ALARM LEVEL II TECHNICIAN.
E. OBTAIN FIRE-ALARM SYSTEM FROM SINGLE SOURCE FROM SINGLE MANUFACTURER. ELECTRICAL
COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED
TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION.
F. FIRE-ALARM SIGNAL INITIATION SHALL BE BY ONE OR MORE OF THE FOLLOWING DEVICES:
1. MANUAL STATIONS.
2. HEAT DETECTORS.
3. SMOKE DETECTORS.
4. AUTOMATIC SPRINKLER SYSTEM WATER FLOW.
G. CONTINUOUSLY OPERATE ALARM NOTIFICATION APPLIANCES.
H. IDENTIFY ALARM AT FIRE-ALARM CONTROL UNIT AND REMOTE ANNUNCIATORS.
I. TRANSMIT AN ALARM SIGNAL TO THE REMOTE ALARM RECEIVING STATION
J. GENERAL REQUIREMENTS FOR FIRE-ALARM CONTROL UNIT:
1. FIELD-PROGRAMMABLE, MICROPROCESSOR-BASED, MODULAR, POWER-LIMITED DESIGN WITH ELECTRONIC
MODULES, COMPLYING WITH UL 864 AND LISTED AND LABELED BY AN NRTL.
2. ADDRESSABLE CONTROL CIRCUITS FOR OPERATION OF MECHANICAL EQUIPMENT.
3. ALPHANUMERIC DISPLAY AND SYSTEM CONTROLS: ARRANGED FOR INTERFACE BETWEEN HUMAN
OPERATOR AT FIRE-ALARM CONTROL UNIT AND A ADDRESSABLE SYSTEM COMPONENTS
INCLUDING ANNUNCIATION AND SUPERVISION. DISPLAY ALARM, SUPERVISORY, AND COMPONENT STATUS
MESSAGES AND THE PROGRAMMING AND CONTROL MENU.
4. KEYPAD: ARRANGED TO PERMIT ENTRY AND EXECUTION OF PROGRAMMING, DISPLAY, AND CONTROL
COMMANDS AND TO INDICATE CONTROL COMMANDS TO BE ENTERED INTO THE SYSTEM FOR CONTROL OF
SMOKE-DETECTOR SENSITIVITY AND OTHER PARAMETERS.
K. ADDRESSABLE INITIATION DEVICES THAT COMMUNICATE DEVICE IDENTITY AND STATUS.
L. SMOKE SENSORS SHALL ADDITIONALLY COMMUNICATE SENSITIVITY SETTING AND ALLOW FOR ADJUSTMENT OF
SENSITIVITY AT FIRE-ALARM CONTROL UNIT.
M. TEMPERATURE SENSORS SHALL ADDITIONALLY TEST FOR AND COMMUNICATE THE SENSITIVITY RANGE OF THE
DEVICE.
N. ANNUNCIATOR AND DISPLAY: LIQUID-CRYSTAL TYPE, 1 LINE(S) OF 40 CHARACTERS, MINIMUM.
O. INITIATING DEVICE, NOTIFICATION APPLIANCE, AND SIGNALING LINE CIRCUITS: NFPA 72, CLASS B.
P. AUTOMATICALLY TRANSMIT ALARM, SUPERVISORY, AND TROUBLE SIGNALS TO A REMOTE ALARM STATION.
Q. GENERAL REQUIREMENTS FOR MANUAL FIRE-ALARM BOXES: COMPLY WITH UL 38. BOXES SHALL BE FINISHED
IN RED WITH MOLDED, RAISED-LETTER OPERATING INSTRUCTIONS IN CONTRASTING COLOR; SHALL SHOW
VISIBLE INDICATION OF OPERATION; AND SHALL BE MOUNTED ON RECESSED OUTLET BOX. IF INDICATED AS
SURFACE MOUNTED, PROVIDE MANUFACTURER'S SURFACE BACK BOX.
R. DOUBLE-ACTION MECHANISM REQUIRING TWO ACTIONS TO INITIATE AN ALARM, PULL-LEVER] TYPE; WITH
INTEGRAL ADDRESSABLE MODULE ARRANGED TO COMMUNICATE MANUAL-STATION STATUS (NORMAL, ALARM,
OR TROUBLE) TO FIRE-ALARM CONTROL UNIT.
S. STATION RESET: KEY- OR WRENCH-OPERATED SWITCH.
T. GENERAL REQUIREMENTS FOR SYSTEM SMOKE DETECTORS:
1. INTEGRAL ADDRESSABLE MODULE: ARRANGED TO COMMUNICATE DETECTOR STATUS (NORMAL, ALARM,
OR TROUBLE) TO FIRE-ALARM CONTROL UNIT.
2. BASE MOUNTING: DETECTOR AND ASSOCIATED ELECTRONIC COMPONENTS SHALL BE MOUNTED IN A
TWIST-LOCK MODULE THAT CONNECTS TO A FIXED BASE. PROVIDE TERMINALS IN THE FIXED BASE
FOR CONNECTION TO BUILDING WIRING.
3. SELF-RESTORING: DETECTORS DO NOT REQUIRE RESETTING OR READJUSTMENT AFTER ACTUATION TO
RESTORE THEM TO NORMAL OPERATION.
4. INTEGRAL VISUAL-INDICATING LIGHT: LED TYPE INDICATING DETECTOR HAS OPERATED AND POWER-ON
STATUS.
5. PHOTOELECTRIC SMOKE DETECTORS:
6. DETECTOR ADDRESS SHALL BE ACCESSIBLE FROM FIRE-ALARM CONTROL UNIT AND SHALL BE ABLE TO
IDENTIFY THE DETECTOR'S LOCATION WITHIN THE SYSTEM AND ITS SENSITIVITY SETTING.
U. AN OPERATOR AT FIRE-ALARM CONTROL UNIT, HAVING THE DESIGNATED ACCESS LEVEL, SHALL BE ABLE TO
MANUALLY ACCESS THE FOLLOWING FOR EACH DETECTOR:
1. PRIMARY STATUS.
2. DEVICE TYPE.
3. PRESENT AVERAGE VALUE.
4. PRESENT SENSITIVITY SELECTED.
5. SENSOR RANGE (NORMAL, DIRTY, ETC.).
V. HEAT DETECTORS, GENERAL REQUIREMENTS FOR HEAT DETECTORS: COMPLY WITH UL 521.
W. REMOTE ANNUNCIATOR
1. ANNUNCIATOR FUNCTIONS SHALL MATCH THOSE OF FIRE-ALARM CONTROL UNIT FOR ALARM,
SUPERVISORY, AND TROUBLE INDICATIONS. MANUAL SWITCHING FUNCTIONS SHALL MATCH THOSE OF
FIRE-ALARM CONTROL UNIT, INCLUDING ACKNOWLEDGING, SILENCING, RESETTING, AND TESTING.
2. MOUNTING: FLUSH CABINET, NEMA 250, TYPE 1.
3. DISPLAY TYPE AND FUNCTIONAL PERFORMANCE: ALPHANUMERIC DISPLAY AND LED INDICATING LIGHTS
SHALL MATCH THOSE OF FIRE-ALARM CONTROL UNIT. PROVIDE CONTROLS TO ACKNOWLEDGE, SILENCE,
RESET, AND TEST FUNCTIONS FOR ALARM, SUPERVISORY, AND TROUBLE SIGNALS.
X. EQUIPMENT INSTALLATION
1. COMPLY WITH NFPA 72 FOR INSTALLATION OF FIRE-ALARM EQUIPMENT.
2. INSTALL WALL-MOUNTED EQUIPMENT, WITH TOPS OF CABINETS NOT MORE THAN 72 INCHES (1830 MM)
ABOVE THE FINISHED FLOOR.
Y. LOCATE DETECTORS NOT CLOSER THAN 3 FEET (1 M) FROM AIR-SUPPLY DIFFUSER OR RETURN-AIR OPENING.
Z. LOCATE DETECTORS NOT CLOSER THAN 12 INCHES (300 MM) FROM ANY PART OF A LIGHTING FIXTURE.
AA. FIRE-ALARM CONTROL UNIT: SURFACE MOUNTED, WITH TOPS OF CABINETS NOT MORE THAN 72 INCHES (1830
MM) ABOVE THE FINISHED FLOOR.
AB. GROUND FIRE-ALARM CONTROL UNIT AND ASSOCIATED CIRCUITS; COMPLY WITH IEEE 1100. INSTALL A
GROUND WIRE FROM MAIN SERVICE GROUND TO FIRE-ALARM CONTROL UNIT.
AC. ENGAGE A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE TO TRAIN OWNER'S MAINTENANCE
PERSONNEL TO ADJUST, OPERATE, AND MAINTAIN FIRE-ALARM SYSTEM.
RACEWAY AND BOXES
A. PROVIDE RACEWAY AND BOXES LOCATED AS INDICATED, AND AT OTHER LOCATIONS REQUIRED FOR SPLICES, TAPS,
WIRE PULLING, EQUIPMENT CONNECTIONS, AND COMPLIANCE WITH REGULATORY REQUIREMENTS. RACEWAY AND
BOXES ARE SHOWN IN APPROXIMATE LOCATIONS UNLESS DIMENSIONED. PROVIDE RACEWAY TO COMPLETE WIRING
SYSTEM.
B. UNDERGROUND MORE THAN 5 FEET OUTSIDE FOUNDATION WALL: PROVIDE SCHEDULE 80 PVC. PROVIDE CAST METAL
BOXES OR NONMETALLIC HANDHOLES WHERE REQUIRED.
C. UNDERGROUND WITHIN 5 FEET FROM FOUNDATION WALL: PROVIDE RIGID STEEL CONDUIT OR THICKWALL NONMETALLIC
CONDUIT (SCHEDULE 80 PVC). PROVIDE CAST METAL OR NONMETALLIC BOXES.
D. IN OR UNDER SLAB ON GRADE: PROVIDE THICK WALL NONMETALLIC CONDUIT. PROVIDE CAST OR NONMETALLIC METAL
BOXES.
E. OUTDOOR LOCATIONS, ABOVE GRADE: PROVIDE RIGID STEEL CONDUIT. PROVIDE CAST METAL OR NONMETALLIC OUTLET,
PULL, AND JUNCTION BOXES.
F. IN SLAB ABOVE GRADE: PROVIDE THICKWALL NONMETALLIC CONDUIT. PROVIDE CAST NONMETALLIC BOXES.
G. WET AND DAMP LOCATIONS: PROVIDE THICKWALL NONMETALLIC CONDUIT. PROVIDE CAST METAL OR NONMETALLIC OUTLET,
JUNCTION, AND PULL BOXES. PROVIDE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS.
H. CONCEALED DRY LOCATIONS: PROVIDE ELECTRICAL METALLIC TUBING. PROVIDE SHEET-METAL BOXES. PROVIDE FLUSH
MOUNTING OUTLET BOX IN FINISHED AREAS. PROVIDE HINGED ENCLOSURE FOR LARGE PULL BOXES.
I. MINIMUM RACEWAY SIZE: 3/4 INCH UNLESS OTHERWISE SPECIFIED.
J. ARRANGE RACEWAY AND BOXES TO MAINTAIN HEADROOM AND PRESENT NEAT APPEARANCE. GROUP RELATED RACEWAY;
SUPPORT USING CONDUIT RACK; PROVIDE SPACE ON EACH FOR 25 PERCENT ADDITIONAL RACEWAYS.
K. RACEWAY ROUTING IS SHOWN IN APPROXIMATE LOCATIONS UNLESS DIMENSIONED. ROUTE TO COMPLETE WIRING SYSTEM.
L. DO NOT SUPPORT RACEWAY WITH WIRE, PERFORATED PIPE STRAPS, CEILING SUPPORT WIRES OR OTHER PIPING SYSTEMS.
M. ROUTE EXPOSED & ABOVE ACCESSIBLE CEILINGS RACEWAY PARALLEL AND PERPENDICULAR TO WALLS.
N. DO NOT CROSS CONDUITS IN SLAB.
O. INSTALL NO MORE THAN EQUIVALENT OF THREE 90 DEGREE BENDS BETWEEN BOXES. INSTALL CONDUIT BODIES TO MAKE
SHARP CHANGES IN DIRECTION, AS AROUND BEAMS. INSTALL FACTORY ELBOWS FOR BENDS IN METAL CONDUIT LARGER
THAN 2 INCH SIZE.
P. AVOID MOISTURE TRAPS; INSTALL JUNCTION BOX WITH DRAIN FITTING AT LOW POINTS IN CONDUIT SYSTEM.
Q. INSTALL FITTINGS TO ACCOMMODATE EXPANSION AND DEFLECTION WHERE RACEWAY CROSSES SEISMIC, CONTROL AND
EXPANSION JOINTS.
R. INSTALL SUITABLE PULL STRING OR CORD IN EACH EMPTY RACEWAY EXCEPT SLEEVES AND NIPPLES.
S. CLOSE ENDS AND UNUSED OPENINGS IN WIREWAY.
T. INSTALL PULL BOXES AND JUNCTION BOXES ABOVE ACCESSIBLE CEILINGS AND IN UNFINISHED AREAS ONLY.
U. IN ACCESSIBLE CEILING AREAS: INSTALL OUTLET AND JUNCTION BOXES NO MORE THAN 6 INCHES FROM CEILING ACCESS
PANEL OR FROM REMOVABLE RECESSED LUMINAIRE.
V. LOCATE FLUSH MOUNTING BOX IN MASONRY WALL TO REQUIRE CUTTING OF MASONRY UNIT CORNER ONLY. COORDINATE
MASONRY CUTTING TO ACHIEVE NEAT OPENING.
W. DO NOT INSTALL FLUSH MOUNTING BOX BACK-TO-BACK IN WALLS; INSTALL WITH MINIMUM 6 INCHES SEPARATION. INSTALL
WITH MINIMUM 24 INCHES SEPARATION IN ACOUSTIC RATED WALLS.
X. DO NOT FASTEN BOXES TO CEILING SUPPORT WIRES OR OTHER PIPING SYSTEMS.
Y. SUPPORT BOXES INDEPENDENTLY OF CONDUIT.
Z. USE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS.
AA. SET FLOOR BOXES LEVEL AND FLUSH WITH FINISH FLOORING MATERIAL
AB. INSTALL CONDUIT TO PRESERVE FIRE RESISTANCE RATING OF PARTITIONS AND OTHER ELEMENTS.
AC. ROUTE CONDUIT THROUGH ROOF OPENINGS FOR PIPING AND DUCTWORK OR THROUGH SUITABLE ROOF JACK WITH PITCH
POCKET.
AD. ALIGN ADJACENT WALL MOUNTED OUTLET BOXES FOR SWITCHES, THERMOSTATS, AND SIMILAR DEVICES.
WALL PLATES
A. MANUFACTURERS:
1. PASS & SEYMOUR LEGRAND.
2. TAYMAC 20510 (WEATHERPROOF-IN-USE).
3. HUBELL (BELL/RACO).
4. LEVITON.
5. GENERAL ELECTRIC.
B. INSTALL DECORATIVE PLATES ON SWITCH, RECEPTACLE, AND BLANK OUTLETS IN FINISHED AREAS. DECORATIVE COVER
PLATE: NYLON.
C. INSTALL JUMBO SIZE PLATES FOR OUTLETS INSTALLED IN MASONRY WALLS. JUMBO COVER PLATE: NYLON.
D. WEATHERPROOF COVER PLATE (RECEPTACLE): IMPACT RESISTANT PLASTIC PLATE WITH HINGED AND GASKETED DEVICE
COVER. COVER TO BE RATED FOR WET LOCATION WHILE IN USE, AND TO BE LOCKABLE.
E. WEATHERPROOF COVER PLATE (SWITCH): GASKETED CAST METAL PLATE WITH HINGED AND GASKETED DEVICE COVER OR
LEVER SWITCH MECHANISM. (P&S CA-31G/HUBBELL/BELL/RACO 5125 OR EQUAL)
F. KITCHEN AREAS: 302/430 STAINLESS STEEL, WEATHERPROOF FOR STARTUPS.
G. INSTALL GALVANIZED (STAMPED) STEEL PLATES ON OUTLET BOXES AND JUNCTION BOXES IN UNFINISHED AREAS, ABOVE
ACCESSIBLE CEILINGS, AND ON SURFACE MOUNTED OUTLETS.
H. INSTALL DEVICES PLUMB AND LEVEL.
I. INSTALL SWITCHES WITH OFF POSITION DOWN.
J. INSTALL RECEPTACLES WITH GROUNDING POLE ON TOP, OR TO THE LEFT (IF MOUNTED HORIZONTALLY.
K. CONNECT WIRING DEVICE GROUNDING TERMINAL TO OUTLET BOX WITH BONDING JUMPER AND BRANCH CIRCUIT
EQUIPMENT GROUNDING CONDUCTOR.
L. CONNECT WIRING DEVICES BY WRAPPING SOLID CONDUCTOR AROUND SCREW TERMINAL. INSTALL STRANDED
CONDUCTOR FOR BRANCH CIRCUITS 10 AWG AND SMALLER. WHEN STRANDED CONDUCTORS ARE USED IN LIEU OF SOLID,
USE CRIMP ON FORK TERMINALS FOR DEVICE TERMINATIONS. DO NOT PLACE BARE STRANDED CONDUCTORS DIRECTLY
UNDER DEVICE SCREWS.
M. ADJUST DEVICES AND WALL PLATES TO BE FLUSH AND LEVEL.CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
BAKER SOUTH
BAKER SOUTH
RFD KITCHEN
RENOVATION
E001
12309492
ELECTRICAL
NOTES, SYMBOL
LEGEND, &
ABBREVIATIONS
R. HEARD
MPS
3004S
APRIL 15, 2020
1 02/14/2020 ISSUE FOR 100% SD REVIEW
2 03/24/2020 ISSUE FOR 95% REVIEW
3 04/10/2020 ISSUE FOR COORDINATED REVIEW
4 04/15/2020 ISSUE FOR CONSTRUCTION
JJ J
Ref
DW
J
DD
3
3
F
GENERAL DRAWING NOTES:
CONTRACTOR TO TRACE OUT EXISTING CIRCUITS AND UPDATE PANEL SCHEDULES ACCORDINGLY.
ELECTRICAL CONTRACTOR RESPONSIBLE FOR COMPLETING A PANEL WALK DOWN FOR EACH PANEL BEING
AFFECTED FOR THIS PROJECT TO DETERMINE REQUIREMENTS AND COORDINATE SHUTDOWNS.
UNLESS OTHERWISE NOTED, EXISTING CONDITIONS ARE SHOWN IN GRAYSCALED, DEMOLITION WORK IS
SHOWN IN BOLD AND DASHED, PROJECT WORK SHOWN IN BOLD. PROVIDE NEW WORK AS SHOWN.
PROVIDE ARC FAULT PROTECTION FOR ALL CIRCUITS IN ACCORDANCE WITH NEC ARTICLE 210.12 (A) & (B).
EXPOSED CONDUIT IS NOT ACCEPTABLE. PROVIDE WIREMOLD WHERE EXPOSED/SURFACE WIRING IS
REQUIRED.
A.
B.
C.
D.
E.
REMOVE EXISTING THREE-WAY SWITCH. WIRING TO BE RE-WORKED TO FUNCTION AS SINGLE
POLE SWITCH TO CONTROL LIGHTS IN ENTRYWAY.
REMOVE EXISTING THREE-WAY AND WIRING SAVE BOX LOCATION IF FEASEABLE TO RELOCATE
DINING AREA SWITCHES.
REMOVE FAN SWITCH AND WIRING TO CLEAR AREA. SAVE WIRING TO EXTEND TO NEW FAN HOOD.
REMOVE EXISTING DEVICE/FIXTURE SAVE LOCATION AND WIRING TO PROVIDE NEW
DEVICE/FIXTURE.
REMOVE EXISTING DINING AREA DIMMER SWITCHES AND RE-WORK WIRING TO NEW LOCATION AS
INDICATED, SWITCHES TO BE REPLACED WITH ON/OFF SWITCHES.
REMOVE DEVICE/FIXTURE AND WIRING TO CLEAR AREA.
REMOVE DEVICE/FIXTURE AND WIRING TO CLEAR AREA.
1
DEMOLITION KEYED NOTES:
TYPICAL ALL SHEETS," KEYNOTES ARE COMMON FOR ALL SHEETS" EACH KEYNOTE MAY NOT APPEAR
IN PLANS ON EVERY SHEET.
2
3
4
5
6
7
EXTEND WIRING AND CONNECT NEW LIGHT FIXTURES AND SWITCHING TO EXISTING CIRCUIT.
EXTEND WIRING AND MODIFY SWITCHING AS REQUIRED.
EXTEND WIRING AND CONNECT NEW RECEPTACLES TO EXISTING CIRCUITS. UNLESS OTHERWISE
NOTED, MOUNT ABOVE COUNTER.
EXTEND WIRING AND CONNECT NEW FIRE ALARM DEVICES TO EXISTING WIRING.
EXTEND WIRING AND CONNECT NEW HOOD FAN TO EXISTING CIRCUIT.
EXTEND WIRING AND CONNECT NEW DISHWASHER TO EXISTING CIRCUIT.
EXTEND WIRING AND CONNECT NEW RANGE UNIT TO EXISTING CIRCUIT.
EXTEND WIRING AND CONNECT NEW RECEPTACLES TO EXISTING CIRCUITS. UNLESS OTHERWISE
NOTED, MOUNT ABOVE COUNTER. REFRIDGERATOR AND MICROWAVE TO BE ON DEDICATED
CIRCUITS.
1
2
KEYED NOTES:
TYPICAL ALL SHEETS," KEYNOTES ARE COMMON FOR ALL SHEETS" EACH KEYNOTE MAY NOT APPEAR
IN PLANS ON EVERY SHEET.
3
4
5
6
7
+44 AFF
GFI
+66 AFF
MCW
HOOD FAN
B
B
A
A
A
A
+44 AFF
GFI
+66 AFF
MCW
HOOD FAN
B
B
UC GFI
A A
A
A
A
AA
D
EXISTING
CIRCUIT CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
BAKER SOUTH
BAKER SOUTH
RFD KITCHEN
RENOVATION
E101
12309492
ELECTRICAL
REMOVAL AND
POWER PLAN
R. HEARD
MPS
3004S
APRIL 15, 2020
1/2" = 1'-0"E101
1 ELECTRICAL REMOVAL PLAN
NN
0'2'4'8'0'2'4'8'
1
4
4
4
4
3
2
44
664
5
4
4
4
4 4
7
6
4
LIGHT FIXTURE SCHEDULE
TYPE LAMP DESCRIPTION MANUFACTURER MODEL # MOUNTING COMMENTS
A LED RECESSED CAN HALO #HLBSL4069FS351EMW RECESSED
B LED UNDER CABINET LIGHT COLOR KINETICS CAT#523-000027-96 120-000065-00 108-000035-00 WALL/CABINET
1/2" = 1'-0"E101
2 POWER PLAN
1
1
1
1
1
1
1
1
2
22
2
2
2
4
7
6
2
5
2
1
33
1
7
1
1 02/14/2020 ISSUE FOR 100% SD REVIEW
2 03/24/2020 ISSUE FOR 95% REVIEW
3 04/10/2020 ISSUE FOR COORDINATED REVIEW
4 04/15/2020 ISSUE FOR CONSTRUCTION