HomeMy WebLinkAboutMP-101ROOM
312
ROOM
30002
ROOM
312B
REMOVE EXISTING KITCHEN
EXHAUST HOOD AND
ASSOCIATED SUPPORTS.
EXISTING FIRE SUPPRESSION SYSTEM TO REMAIN.
DISCONNECT FIRE SUPPRESSION PIPING AT HOOD
AND PREPARE FOR RECONNECTION TO THE NEW
HOOD. PULL STATION AND EMERGENCY GAS
VALVE TO REMAIN.
REMOVE EXISTING DUCTWORK AND
EXHAUST FAN.
CLEAN GREASE DUCT LOCATED IN
CHIMNEY PRIOR TO CAPPING.
CAP AND SEAL ABANDONED GREASE DUCT
AT THE TOP OF THE CHIMNEY AND AT
CHIMNEY PENETRATION AIR/WATER TIGHT.14x12 (E)16x20 (E)
EXISTING CHIMNEY
EXISTING DRY PIPE
FIRE PROTECTION
SYSTEM
EXISTING GENERAL
EXHAUST EQUIPMENT
AND DUCTWORK
2
MP-401
ROOM
312 ROOM
30002
ROOM
312B
24x8 TRANSITION TO
12x8 UP TO ATTIC
14" DIAMETER, REDUCED CLEARANCE
PRE-MANUFACTURED GREASE DUCT
UP TO ATTIC
TIE INTO EXISTING 1-1/4" NATURAL
GAS LINE. RUN UP WALL INTO ATTIC
TO SERVE NEW KITCHEN MAKE UP
AIR UNIT
1
KEH-1 4
MP-401
SAD-1
550 CFM
12x12 SA
UP TO ATTIC
ANSUL SYSTEM (E)
T
KITCHEN TEMPERATURE SENSOR
PROVIDED BY KITCHEN HOOD
MANUFACUTER AND INSTALLED BY
MECHANICAL CONTRACTOR
2
2
3
4
S
2
MP-401
IL-01
14"Ø EA UP TO KEF-1
14" TOOLESS
ACCESS DOOR
5
2" V
14"Ø UP FROM KEH-1
4
MP-401
12x12 SA
16x16 SA
12x12 DOWN TO DIFFUSER
1-1/4" NG DN TO KITCEHN
HMAU-1
8x12 SA
6
12x12 ACCESS
DOOR
4
7
INTAKE LOUVER
EXTERIOR 3.5" X 3/4" TRIM
BOARD AROUND LOVER
OPENING. PRIME AND PAINT
TO MATCH EXISTING
WINDOW TRIM
EXISTING WOOD SIDING
AND SHEATHING
EXTERIOR 3.5" X 3/4" TRIM
BOARD AROUND LOVER
OPENING. PRIME AND PAINT
TO MATCH EXISTING
WINDOW TRIM
(2) 2X10 HEADER
PROVIDE BACKER ROD AND
SEALANT AROUND LOUVER
PITCH DUCT DOWN
TO LOUVER
CAULK AND SEAL SEAM
AIR/WATER TIGHT ALL
AROUND
WALL SLEEVE
W/STANDING
SEAMS ON SIDES
AND TOP
WALL SLEEVE
(2) 2X10 SILL
BIRD SCREEN
ACCESS
DOOR
ACCESS DOOR
CEILING
BATT
INSULATION
12" BATT
INSULATION
SHEET METAL
SHROUD
6"X6" PLATE
CORD FOR PULLING
INSULATION OUT OF SHROUD
THREE 2" LAYERS OF R10
POLYSTYRENE RIGID
INSULATION0' - 6"MINPROTECT THE EDGE CORNE LL U N IV
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
N
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
PHI SIGMA SIGMA, 14 SOUTH AVE
KITCHEN HOOD
EXHAUST
RENOVATION
MP-101
11191594
MECHANICAL
AND PLUMBING
PLANS
P. OCKENFELS
PCO
4724
JULY 15, 2019
0 2 4 8
SCALE: 1/4"=1'-0"
SCALE:1/4" = 1'-0"1 THIRD FLOOR - HVAC DEMOLITION PLAN
SCALE:1/4" = 1'-0"2 ATTIC - HVAC & PLUMBING DEMOLITION
SCALE:1/4" = 1'-0"3 THIRD FLOOR - NEW HVAC & PLUMBING PLAN
SCALE:1/4" = 1'-0"4 ATTIC - NEW MECANICAL & PLUMBING PLAN
MP-101 KEYED CONSTRUCTION NOTES
1
CONNECT ANSUL SYSTEM TO PRE-PIPED KITCHEN EXHAUST HOOD ANSUL PIPING.
THE GRIDDLE FIRE SUPPRESSION NOZZLE WILL REQUIRE FIELD PIPING. REFER TO
DETAILS.
2 PATCH & PAINT GYP CEILING TO MATCH EXISTING
3 ANSUL SYSTEM PIPING SIZED PER MANUFACTURER'S RECOMMENDATION
4
PROVIDE A 12”x12” FIRE RATED ACCESS DOOR. THIS ACCESS DOOR SHALL BE
UTILIZED TO RUN HOT WATER AND VACUUM LINES INTO THE ATTIC FOR DUCT
CLEANING PURPOSES. PROVIDE A SHEET METAL SHROUD AROUND THE ACCESS
DOOR TO HOLD BACK THE BATT INSULATION IN THE ATTIC. TERMINATE THE SHEET
METAL 6” ABOVE THE ATTIC INSULATION. PROVIDE A GUARD ON THE ATTIC SIDE OF
THE SHEET METAL SHROUD TO PROTECT FROM CUTTING ANY HOSES OR VACUUM
LINES USED BY THE CLEANING CONTRACTOR.
5
PROVIDE MANUAL GAS SHUT-OFF VALVE W/ PLUGGED 1/8” NPT, GROUND JOINT
UNION W/ BRASS SEAT, AND 3” (MIN) SEDIMENT TRAP. REFER TO MANUFACTURE’S
INSTALLATION INSTRUCTIONS.
6 GREASE DUCTWORK LOCATED IN THE ATTIC SHALL BE WRAPPED WITH INSULATION
TO PRESERVE THE COLD ATTIC DESIGN.
7
INSTALL NEW FIBERGLASS BATT INSULATION WHERE DISTURBED BY
CONSTRUCTION OPERATIONS. PROVIDE 8” BATT INSULATION BETWEEN 8” ATTIC
FLOOR FRAMING MEMBERS, PLUS A SECOND LAYER OF 12” FIBERGLASS BATT
INSULATION ABOVE AND PERPENDICULAR TO FRAMING MEMBERS.
#
SCALE:NO SCALEALOUVER DETAIL
SCALE: NO SCALE
B ACCESS DOOR TO ATTIC
1 5/31/19 ISSUE FOR 50% REVIEW
2 7/10/19 ISSUE FOR COORDINATED REVIEW
3 7/15/19 ISSUE FOR CONSTRUCTION