HomeMy WebLinkAboutE-102HMAU-1 KEF-1 PANEL LNP-11 J 1 FIRE ALARM PANEL HOOD CONTROL PANEL J LIGHT FIXTURE JUNCTION BOXES IN HOOD 4 5 6 7 J LNP-11/2 LNP-11/19,21 2 3 4 4 5 E-102 KEYED CONSTRUCTION NOTES 1 PROVIDE NEW JUNCTION BOX, 2-#12 & 1-#12 GND IN 3/4" EMT TO CONTROL PANEL CONNECTION ON NEW HOOD. CONNECT TO EXISTING CONDUCTORS SAVED FROM REMOVAL OF LIGHTING CIRCUIT. 2 PROVIDE 2-#12 & 1-#12 GND THHN IN ¾” FROM PANEL LNP-11 TO NEW MAKEUP AIR UNIT HMAU-1 VIA UNIT MOUNTED DISCONNECT SWITCH. 3 PROVIDE 2-#12 & 1-#12 GND THHN IN ¾” FROM PANEL LNP-11 TO NEW EXHAUST FAN EF-1 VIA UNIT MOUNTED DISCONNECT SWITCH. 4 PROVIDE #18 TSP IN 1/2” EMT CONDUIT FROM PRIMARY CONTROL PANEL TO EACH FAN FOR CONTROL. 5 PROVIDE 2-#12 IN ½” EMT FROM CONTROL PANEL TO HMAU-1 FOR SUPPLY FAN INTERLOCK. 6 PROVIDE 2-#12 & 1-#12 GND THHN IN 1/2" LFMC FROM CONTROL PANEL TO J-BOX ON TOP OF HOOD FOR HOOD LIGHT FIXTURE POWER. 7 PROVIDE 2-#14 IN ½” CONDUIT FROM EXISTING SUPPRESSION SYSTEM TO HOOD PANEL CONTACTS FOR FIRE SYSTEM MICROSWITCH. # 0 2 4 8 SCALE: 1/4"=1'-0"CORNE LL U N IV E R SI TYFOUN DE D 5681AD FACILITIES ENGINEERING N ARCHIVE BAR CODEITHACA, NEW YORK ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 PHI SIGMA SIGMA, 14 SOUTH AVE KITCHEN HOOD EXHAUST RENOVATION E-102 11191594 INSTALLATION PLANS E. Reichard ETR 4724 JULY 15, 2019 SCALE:1/4" = 1'-0"1 3RD FLOOR PARTIAL ELECTRICAL PLAN SCALE:1/4" = 1'-0"2 ATTIC INSTALLATION PLAN TOTAL AMPS:5 A 5 A TOTAL LOAD:600 VA 600 VA 23 EXISTING LOAD 20 1 0 0 -- -- --24 21 ---- -- 0 0 2 20 EXISTING LOAD 22 19 HMAU-1 20 2 600 0 -- -- --20 17 ---- -- 0 0 2 20 SPARE 18 15 GFCI ABOVE CTR/RT OF SINK 20 2 0 0 -- -- --16 13 ---- -- 0 0 2 20 UNDERCABINET REC/MICRO 14 11 EXISTING LOAD 20 2 0 0 -- -- --12 9 ---- -- 0 0 2 20 EXISTING LOAD 10 7 EXISTING LOAD 20 2 0 0 -- -- --8 5 EXISTING LOAD 20 1 0 0 2 20 EXISTING LOAD 6 3 EXISTING LOAD 20 1 0 0 1 20 EXISTING LOAD 4 1 EXISTING LOAD 20 1 0 600 1 20 KEF-1 2 CKT DESCRIPTION TRIP POLES A B POLES TRIP DESCRIPTION CKT ENCLOSURE:NEMA 1 MOUNTING:Surface WIRES:3 MAINS RATING:100 A FED FROM:PHASE:1 MAINS TYPE:MLO LOCATION:ROOM 312A VOLTS:120/240V AIC RATING:10KAIC PANEL LNP-11 1 5/31/19 ISSUE FOR 50% REVIEW 2 7/10/19 ISSUE FOR COORDINATED REVIEW 3 7/15/19 ISSUE FOR CONSTRUCTION NOTE: ALL NEW DESIGNATIONS SHOWN IN BOLD.