HomeMy WebLinkAboutE-102HMAU-1
KEF-1
PANEL LNP-11
J
1
FIRE ALARM
PANEL
HOOD CONTROL
PANEL
J
LIGHT FIXTURE
JUNCTION BOXES
IN HOOD
4 5
6
7
J
LNP-11/2
LNP-11/19,21
2
3
4
4
5
E-102 KEYED CONSTRUCTION NOTES
1 PROVIDE NEW JUNCTION BOX, 2-#12 & 1-#12 GND IN 3/4" EMT TO CONTROL PANEL
CONNECTION ON NEW HOOD. CONNECT TO EXISTING CONDUCTORS SAVED FROM
REMOVAL OF LIGHTING CIRCUIT.
2 PROVIDE 2-#12 & 1-#12 GND THHN IN ¾” FROM PANEL LNP-11 TO NEW MAKEUP AIR
UNIT HMAU-1 VIA UNIT MOUNTED DISCONNECT SWITCH.
3 PROVIDE 2-#12 & 1-#12 GND THHN IN ¾” FROM PANEL LNP-11 TO NEW EXHAUST FAN
EF-1 VIA UNIT MOUNTED DISCONNECT SWITCH.
4 PROVIDE #18 TSP IN 1/2” EMT CONDUIT FROM PRIMARY CONTROL PANEL TO EACH
FAN FOR CONTROL.
5 PROVIDE 2-#12 IN ½” EMT FROM CONTROL PANEL TO HMAU-1 FOR SUPPLY FAN
INTERLOCK.
6 PROVIDE 2-#12 & 1-#12 GND THHN IN 1/2" LFMC FROM CONTROL PANEL TO J-BOX ON
TOP OF HOOD FOR HOOD LIGHT FIXTURE POWER.
7 PROVIDE 2-#14 IN ½” CONDUIT FROM EXISTING SUPPRESSION SYSTEM TO HOOD
PANEL CONTACTS FOR FIRE SYSTEM MICROSWITCH.
#
0 2 4 8
SCALE: 1/4"=1'-0"CORNE LL U N IV
E
R
SI
TYFOUN
DE D 5681AD
FACILITIES
ENGINEERING
N
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
PHI SIGMA SIGMA, 14 SOUTH AVE
KITCHEN HOOD
EXHAUST
RENOVATION
E-102
11191594
INSTALLATION
PLANS
E. Reichard
ETR
4724
JULY 15, 2019
SCALE:1/4" = 1'-0"1 3RD FLOOR PARTIAL ELECTRICAL PLAN
SCALE:1/4" = 1'-0"2 ATTIC INSTALLATION PLAN
TOTAL AMPS:5 A 5 A
TOTAL LOAD:600 VA 600 VA
23 EXISTING LOAD 20 1 0 0 -- -- --24
21 ---- -- 0 0 2 20 EXISTING LOAD 22
19 HMAU-1 20 2 600 0 -- -- --20
17 ---- -- 0 0 2 20 SPARE 18
15 GFCI ABOVE CTR/RT OF SINK 20 2 0 0 -- -- --16
13 ---- -- 0 0 2 20 UNDERCABINET REC/MICRO 14
11 EXISTING LOAD 20 2 0 0 -- -- --12
9 ---- -- 0 0 2 20 EXISTING LOAD 10
7 EXISTING LOAD 20 2 0 0 -- -- --8
5 EXISTING LOAD 20 1 0 0 2 20 EXISTING LOAD 6
3 EXISTING LOAD 20 1 0 0 1 20 EXISTING LOAD 4
1 EXISTING LOAD 20 1 0 600 1 20 KEF-1 2
CKT DESCRIPTION TRIP POLES A B POLES TRIP DESCRIPTION CKT
ENCLOSURE:NEMA 1
MOUNTING:Surface WIRES:3 MAINS RATING:100 A
FED FROM:PHASE:1 MAINS TYPE:MLO
LOCATION:ROOM 312A VOLTS:120/240V AIC RATING:10KAIC
PANEL LNP-11
1 5/31/19 ISSUE FOR 50% REVIEW
2 7/10/19 ISSUE FOR COORDINATED REVIEW
3 7/15/19 ISSUE FOR CONSTRUCTION
NOTE: ALL NEW DESIGNATIONS SHOWN IN BOLD.