HomeMy WebLinkAboutE-101PANEL LNP-11
PANEL LNP-11/19,21
1
2
4
PANEL LNP-11/19,21 VIA
MOTOR STARTER IN KITCHEN
3 CORNE LL U N IV
E
R
SI
TYFOUN
DE D 5681AD
FACILITIES
ENGINEERING
N
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
PHI SIGMA SIGMA, 14 SOUTH AVE
KITCHEN HOOD
EXHAUST
RENOVATION
E-101
11191594
DEMOLITION
PLANS
E. Reichard
ETR
4724
JULY 15, 2019
#E-101 KEYED DEMOLITION NOTES
1 DISCONNECT AND REMOVE EXISTING LIGHTING CIRCUIT BACK TO SWITCH ON
WALL. REMOVE SWITCH AND SAVE CIRCUITRY FOR REUSE WITH NEW CONTROL
PANEL.
2 DISCONNECT AND REMOVE EXISTING CIRCUIT FOR HOOD EXHAUST FAN STARTER
BACK TO PANEL.
3 DISCONNECT AND REMOVE EXISTING CIRCUIT FOR EXHAUST FAN AND FLOOR
MOUNTED DISCONNECT SWITCH BACK TO PANEL VIA STARTER IN KITCHEN.
4 DISCONNECT AND REMOVE CONDUCTORS FROM DETECTION DEVICES IN HOOD.
REMOVE CONDUIT AND CONDUCTORS FROM HOOD BACK TO SUPPRESSION
SYSTEM ON WEST WALL. NEW HOOD DETECTION SYSTEM AND SUPPRESSION
DEVICES TO BE CONNECTED TO THE EXISTING SYSTEM.
0 2 4 8
SCALE: 1/4"=1'-0"
SCALE:1/4" = 1'-0"1 3RD FLOOR REMOVAL PLAN
SCALE:1/4" = 1'-0"2 ATTIC REMOVAL PLAN
1 5/31/19 ISSUE FOR 50% REVIEW
2 7/10/19 ISSUE FOR COORDINATED REVIEW
3 7/15/19 ISSUE FOR CONSTRUCTION