HomeMy WebLinkAboutE-001CORNE LL U N IV
E
R
SI
TYFOUN
DE D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
PHI SIGMA SIGMA, 14 SOUTH AVE
KITCHEN HOOD
EXHAUST
RENOVATION
E-001
11191594
GENERAL
NOTES AND
SYMBOL
LEGENDS
E. REICHARD
ETR
4724
JULY 15, 2019
GENERAL ELECTRICAL NOTES
1.0 ELECTRICAL SCHEMATICS INDICATED ON CONTRACT DOCUMENTS ARE
DIAGRAMMATIC. IT IS NOT THE INTENT TO SHOW EXACT OR MOST EFFICIENT
ROUTING. VERIFY ALL DIMENSIONS AND FIELD CONDITIONS ON SITE. ANY
CONFLICTS BETWEEN CONSTRUCTION DOCUMENTS AND FIELD CONDITIONS SHALL
BE BROUGHT TO CORNELL'S PROJECT MANAGER FOR RESOLUTION BEFORE WORK
PROCEEDS.
2.0 ASSURE PUBLIC AND WORKER SAFETY AT ALL TIMES. PROTECT ADJOINING AREAS
FROM DAMAGE AND DUST. REMOVE ALL DEBRIS FROM SITE AND DISPOSE OF
WASTE MATERIAL IN A SAFE MANNER. KEEP THE PREMISES FREE OF DEBRIS FROM
THE EXECUTION OF WORK. DELIVER A FINAL PRODUCT THAT IS CLEAN AND
OPERABLE.
3.0 FIRE STOP ELECTRICAL PENETRATIONS THROUGH FIRE RATED WALLS AND/OR
FLOORS WITH MATERIAL EQUAL IN RATING TO THE CONSTRUCTION OF THE
MATERIAL PENETRATED.
4.0 WORK SHALL BE COMPLETED AS SPECIFIED AND INDICATED ON CONTRACT
DOCUMENTS. ANY SUGGESTED ALTERNATE MANUFACTURER OR METHOD OF
INSTALLATION SHALL BE SUBMITTED TO PROJECT ENGINEER FOR APPROVAL
PRIOR TO ORDERING ANY MATERIALS OR COMMENCING EXECUTION OF WORK.
5.0 GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLE 250. PROVIDE
EQUIPMENT GROUND CONDUCTOR WITH EACH BRANCH CIRCUIT INDICATED ON
CONTRACT DOCUMENTS. EQUIPMENT GROUND CONDUCTOR SHALL BE ROUTED
WITH ASSOCIATED PHASE CONDUCTORS.
6.0 PROVIDE A NEW TYPED PANELBOARD DIRECTORY FOR EACH PANELBOARD. LABEL
ALL NEW DEVICE FACEPLATES WITH SOURCE AND CIRCUIT NUMBER. PROVIDE
PERMANENT LABEL ON SWITCHING DEVICES INDICATING EQUIPMENT SERVICE AND
INVENTORY NUMBERS. COORDINATE EQUIPMENT INVENTORY NUMBERS WITH
CORNELL UNIVERSITY'S MECHANICAL SHOP, 255-8667.
7.0 CIRCUITS RATED 20-AMP, 120 VOLT SHALL CONTAIN SEPARATE NEUTRAL
CONDUCTORS.
8.0 CONDUCTORS SHALL BE A MINIMUM OF 12AWG, STRANDED COPPER, 600VAC, 90
DEGREE C, TYPE THHN/THWN-2 FOR DRY AREAS AND XHHW/THWN-2 FOR WET
AREAS.
9.0 CONDUITS SHALL BE A MINIMUM OF 3/4 INCHES DIAMETER. CONDUITS SHALL BE
ELECTRICAL METALLIC TUBING (EMT) AND SURFACE MOUNTED UNLESS NOTED
OTHERWISE.
10.0 AIC RATING OF NEW CIRCUIT BREAKERS SHALL MATCH RATING OF RESPECTIVE
PANELBOARD. SIZE AS INDICATED.
11.0 PROVIDE PULL STRING THROUGH NEW CONDUIT AND BOXES. PROVIDE SUPPORT
HANGERS FOR CONDUIT AS NEEDED.
12.0 INSTALL RACEWAY SYSTEMS ENSURING PROPER ACCESS TO EQUIPMENT AND
DEVICES AND WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE AND
REPAIR. RACEWAYS THAT ARE NOT INSTALLED WITH THIS REQUIREMENT IN MIND
SHALL BE RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIES
ARE CORRECTED.
ELECTRICAL SCOPE OF WORK
1.0 PROVIDE POWER, CONTROL AND FIRE ALARM TO SUPPORT THE REPLACEMENT OF
THE EXISTING KITCHEN HOOD EXHAUST.
ELECTRICAL LEGEND
LIGHTING LEGEND
MOTOR
1'x4' LUMINAIRE
HARDWIRED EQUIPMENT CONNECTION
P-1A12
HOMERUN TO PANEL P-1A, CIRCUIT #12. FED
FROM 20A -1P BREAKER IS INTENDED UNLESS
NOTED OTHERWISE. RUN GREEN WIRE GROUND
FOR ALL CIRCUITS. PROVIDE ONE GROUND PER
CIRCUIT.
EMERGENCY POWER OFF (EPO)
GROUND ROD ELECTRODE
DUPLEX RECEPTACLE WITH GFCI PROTECTION
DUPLEX RECEPTACLE WITH AFCI PROTECTION
QUAD RECEPTACLE
LINETYPES LEGEND
SPECIAL RECEPTACLE5-30R
PANELBOARD
JUNCTION BOX
B = INSTALLED IN BASEBOARD
TR = INSTALLED IN WOOD TRIM/CASEWORK/WAINSCOTT
SR = SURFACE RACEWAY
WP = WEATHERPROOF
AC = AIR CONDITIONER
X
DUPLEX RECEPTACLE:
DOUBLE DUPLEX RECEPTACLE
MOTOR STARTER
J
2'x4' LUMINAIRE
CEILING MOUNTED LUMINAIRE
EM LIGHTING BATTERY UNIT
COMBO EXIT SIGN/EM LIGHTING BATTERY UNIT
SINGLE FACE, WALL MOUNT EXIT SIGN
DOUBLE FACE, WALL MOUNT EXIT SIGN
SINGLE FACE, CEILING MOUNT EXIT SIGN
DOUBLE FACE, CEILING MOUNT EXIT SIGN
LIGHT SWITCH:
SAFETY SWITCH (NON-FUSED)
SAFETY SWITCH (FUSED)
X 3 = 3-WAY SWITCH
4 = 4-WAY SWITCH
D = DIMMER SWITCH
O = WALL SWITCH OCCUPANCY SENSOR
V = WALL SWITCH VACANCY SENSOR
W = WIRELESS SWITCH
S = WIRELESS SCENE SWITCH
WIRELESS OCCUPANCY SENSOR
WIRELESS DAYLIGHT SENSOR
OS W
DS
1'x2' LUMINAIRE
FIRE ALARM LEGEND
FIRE ALARM CONTROL PANEL
BATTERY CABINET
WATER FLOW SWITCH
MUXPAD
REMOTE ANNUNCIATOR
D = DUCT SMOKE DETECTOR
R = RELAY BASE
BR = BEAM RECEIVER
BT = BEAM TRANSMITTER
SB = SOUNDER BASE
SMOKE DETECTOR:
TAMPER SWITCH
AUDIBLE NOTIFICATION APPLIANCE
FACP
BATT
MUX
FAA
NAC PANELNAC
MANUAL PULL STATIONF
S X
F = FIXED TEMPERATURE
R = RATE OF RISE
R/F = COMBINATION RISE/FIXED TEMPERATURE
HEAT DETECTOR:
H X
CARBON MONOXIDE DETECTORCO
AM
F
XXcd
C
FS
F
S
XXcd
C
TS
ADDRESSABLE MODULE
XXcd = CANDELA
C = CEILING
COMBO A/V NOTIFICATION APPLIANCE:
XXcd = CANDELA
C = CEILING
VISUAL NOTIFICATION APPLIANCE:
SUPPRESSION SYSTEM
ELECTRICAL ABBREVIATIONS
AC AIR CONDITIONER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT INTERRUPTER
AMM ADDRESSABLE MONITOR MODULE
AOM ADDRESSABLE OUTPUT MODULE
ARB AUXILIARY RELAY BOARD
ATS AUTOMATIC TRANSFER SWITCH
B BASEBOARD
BKR BREAKER
C CONDUIT
CD CANDELA
CKT CIRCUIT
CR CONTROL RELAY
EC ELECTRICAL CONTRACTOR
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF STATION
FAA FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FSD FIRE SMOKE DAMPER
GAA GENERATOR ALARM ANNUNCIATOR
GFI GROUND FAULT INTERRUPTER
GND GROUND
HP HORSEPOWER
KW KILOWATT
LC LIGHTING CONTACTOR
LFMC LIQUID TIGHT FLEXIBLE METALLIC CONDUIT
LTG LIGHTING
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUG ONLY
MTS MANUAL TRANSFER SWITCH
NAC NOTIFICATION APPLIANCE CIRCUIT
NIC NOT IN CONTRACT
OE OVERHEAD ELECTRIC
PC PHOTOCELL
PM PLUGMOLD
PP POWER PANEL
PVC POLYVINYL CHLORIDE CONDUIT
RGS RIGID GALVANIZED STEEL CONDUIT
SR SURFACE RACEWAY
ST SHUNT TRIP
TM THERMAL MAGNETIC
TR TRIM/CASEWORK/WAINSCOTT
TSP TWISTED SHIELDED PAIR
TYP TYPICAL
UE UNDERGROUND ELECTRIC
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VA VOLT AMPS
WP WATERPROOF
UNDERGROUND ELECTRICUE
UNDERGROUND LIGHTINGUL
OVERHEAD ELECTRICOE
TO BE PROVIDED
DEMOLITION / TO BE RELOCATED
EXISTING TO REMAIN
UNDERGROUND TELCOUC
MOUNTING HEIGHTS
CARD READER 48" TOP OF BOX
LIGHT SWITCH 48" TOP OF BOX
RECEPTACLE 18" TOP OF BOX
DATA OUTLET 18" TOP OF BOX
TV OUTLET 84" TOP OF BOX
PHONE OUTLET 48" TOP OF BOX
SAFETY SWITCH 60" CENTERLINE OF HANDLE
MOTOR STARTER 60" CENTERLINE OF HANDLE
PANELBOARD 72" TOP OF PANELBOARD
MANUAL PULL STATION 48" OPERABLE HANDLE
NOTIFICATION APPLIANCE 80" BOTTOM OF LENS
DOOR HOLD OPEN COORDINATE IN FIELD
EM BATTERY UNIT 96" BOTTOM OF UNIT
EM REMOTE UNIT 102" BOTTOM OF UNIT
EXIT SIGN 96" BOTTOM OF UNIT
LIGHT POLE WITH LED LUMINAIRES, REFER TO
PLANS FOR NUMBER AND CONFIGURATION OF
HEADS
GENERAL ELECTRICAL DEMOLITION NOTES
1.0 ELECTRICAL EQUIPMENT SHOWN DASHED ON DEMOLITION DRAWINGS, INCLUDING
ASSOCIATED ANCHORS, SUPPORTS, STRAPS, BOXES, FITTINGS, AND OTHER
APPURTENANCES NOT SHOWN, SHALL BE DISCONNECTED AND REMOVED.
REMOVE ASSOCIATED BRANCH CIRCUITRY TO SOURCE, UNLESS NOTED
OTHERWISE.
2.0 EXISTING RACEWAYS AND DEVICE BACKBOXES NOT INTERFERRING WITH NEW
WORK SHALL BE REUSED WHERE POSSIBLE.
3.0 PROVIDE JUNCTION BOXES, RACEWAYS, AND WIRING TO MODIFY/EXTEND EXISTING
SYSTEMS AND CIRCUITS FED DOWNSTREAM OF ELECTRICAL EQUIPMENT SHOWN
TO BE DEMOLISHED.
4.0 CUT DEMOLISHED CONDUITS INSTALLED THRU WALLS AND FLOORS FLUSH WITH
THE SURFACE AND PATCH PENETRATIONS (FIRESTOP IF LOCATED ON A FIRE
RATED SURFACE). PATCH AND PAINT SURFACES IN EXPOSED AREAS TO MATCH
SURROUNDING MATERIALS, FINISHES, AND COLORS.
5.0 PROVIDE BLANK COVERPLATES ON UNUSED BACKBOXES REMAINING FROM
DEMOLITION NOT SPECIFIED TO BE INFILLED.
6.0 EXISTING EQUIPMENT SHOWN TO REMAIN SHALL BE PROTECTED DURING
CONSTRUCTION.
1 5/31/19 ISSUE FOR 50% REVIEW
2 7/10/19 ISSUE FOR COORDINATED REVIEW
3 7/15/19 ISSUE FOR CONSTRUCTION