HomeMy WebLinkAboutBinder1191920202021212121202020201919
191920202021212121202020201919
191920202021212121202020201919
191920202021212121202020201919
1919202020212121212020202019191919
212020202021
2121212121212121212121212121
CB CB
CB CB
CB CB
CB CBCB
CBCB
CB CBSTANDS
SCOREBOARD
ATHLETIC FIELD
FP
POSTS
PARKING
POSTS
PARKING
PARKING
PLATFORM
PARKING
PARKING AREA
PAVED
PAVED
PAVED
PAVED
UNPAVED
UNPAVED PARKING
TENNIS COURT
TENNIS COURT
TENNIS COURTS
SS
S
RHODES
HALL
2051
HOY ROAD
CAMPUS ROAD
COLLEGE AVENUEOAK AVENUE
DRYDEN ROADAREA OF WORK
AREA OF WORK CORNE
LL U N I V
E
R
SI
TYFOUN
D E D 5681
AD CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
Cornell University
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
T-001
11874770
TITLE SHEET
FE DESIGN
EWK
2051
APRIL 8, 2020
RHODES HALL UPS REPLACEMENT
SITE LOCATION -RHODES HALL
KEY PLAN -PENTHOUSE LEVEL BUILDING CODE SUMMARY
APPLICABLE CODES
2015 EXISTING IBC ADOPTED BY NEW YORK STATE
PROJECT SUMMARY
THIS PROJECT INCLUDES THE REPLACEMENT OF TWO UPS SYSTEMS. THE
WORK IS ALTERATION LEVEL 2.
BUILDING LIMITATIONS
CONSTRUCTION CLASSIFICATION:1A
CLASSIFICATION OF HAZARDS:NONE
HIGH-RISE BUILDING:NO
EXTINGUISHING REQUIREMENT:THE EXISTING BUILDING
IS SPRINKLERED
OCCUPANCY
OCCUPANCY CLASSIFICATION:BUSINESS (B)
DRAWING INDEX
PROJECT SCOPE
THIS PROJECT INCLUDES THE REPLACEMENT OF THE EXISTING 300KVA UPS SYSTEM WITH A NEW 275KVA UPS SYSTEM, REPLACING AN AUTOMATIC
TRANSFER SWITCH AND ADDING PANELBOARDS FOR DISTRIBTUTION AND FOR TOTAL BYPASS OF UPS, BATTERIES AND SBM. ALSO INCLUDED IN THE
SCOPE IS THE REMOVAL OF EXISTING CONCRETE PADS.
GENERAL SYMBOLS LEGEND
EXTERIOR ELEVATION
1
1
1 1X-100
X-100
1
1
1 1 INTERIOR ELEVATION
1
X-100
SECTION MARKER
1
X-100 ENLARGED DETAIL
CONSTRUCTION KEYED NOTE
DEMOLITION KEYED NOTE
DRAWING REVISION NOTE#
LINETYPE: TO BE PROVIDED / NEW
LINETYPE: DEMOLITION / TO BE RELOCATED
LINETYPE: EXISTING TO REMAIN
#
#
T-001 TITLE SHEET
S-001 GENERAL NOTES, ABBREVIATIONS, AND LEGEND
S-101 PENTHOUSE FLOOR PLAN
S-401 DETAILS
F-001 SYMBOL LIST, GENERAL NOTES AND ABBREVIATION LIST
F-101 PARTIAL PENTHOUSE FIRE PROTECTION REMOVAL PLAN
F-102 BASEMENT FIRE PROTECTION PLAN
F-103 PARTIAL PENTHOUSE FIRE PROTECTION PLAN
F-501 FIRE PROTECTION DETAILS
F-601 FIRE PROTECTION RISER DIAGRAM
E-001 GENERAL NOTES AND SYMBOL LEGENDS
E-101 EXISTING AND PHASE 1 PLANS
E-102 PHASE 2 PLAN
E-103 PHASE 3 PLAN AND PERSPECTIVE
E-104 PENTHOUSE PATH OF TRAVEL
E-301 PHASE 1 ONE-LINE DIAGRAM
E-302 PHASE 2 ONE-LINE DIAGRAM
E-303 PHASE 3 ONE-LINE DIAGRAM
E-304 FINAL ONE-LINE DIAGRAM
E-305 CONTROL RISER DIAGRAM
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION
MATERIAL
N.S. GROUT
STEEL PIECES AND ERECTION PLANS
POST-INSTALLED ANCHORS
REQUIRED SUBMITTALS
SCHEDULE /
SHOP DWGS
PRODUCT
DATA
INSPECTIONS
& TESTS
X
X
X X
X
WIDE FLANGE MEMBERS A992, Fy = 50 KSI
STRUCTURAL STEEL GRADES
HSS RECTANGULAR MEMBERS
CHANNELS AND ANGLES
A500 GRADE B, Fy = 46 KSI
A36, Fy = 36 KSI
HSS ROUND MEMBERS A500 GRADE B, Fy = 42 KSI
PLATES A572, Fy = 50 KSI
PIPES A53, Fy = 35 KSI
THREADED RODS F1554 GRADE 36, Fy = 36 KSI
W_X__ STEEL BEAM OF SIZE W_X__
STEEL BEAM WITH BEARING PLATE TYPE #
BP#
COLUMN UP/DOWN
NEW STEEL COLUMN
W_X__ EXIST. STEEL BEAM OF SIZE W_X__
EXIST. STEEL COLUMN
150 PSF INCLUDING EQUIPMENT
75 PSF PLUS LOADS FROM
SPECIFIC EQUIPMENT LAYOUT
200 PSF INCLUDING
EQUIPMENT
GROUND SNOW LOAD, Pg 40 PSF
FLAT-ROOF SNOW LOAD, Pf 31 PSF
SNOW LOAD IMPORTANCE FACTOR, Is 1.10
THERMAL FACTOR, Ct 1.0
DRIFT SURCHARGE LOAD, Pd N/A
SNOW DRIFT WIDTH, w N/A
BASIC DESIGN WIND SPEED, V 119 MPH
WIND EXPOSURE CATEGORY B
RISK CATEGORY III
INTERNAL PRESSURE COEFFICIENT, GCpi +/-0.18
MWRFS DESIGN PRESSURE COEFFICIENT, qz N/A
C&C DESIGN PRESSURE COEFFICIENT, qcc N/A
SEISMIC IMPORTANCE FACTOR, Ie 1.25
Ss 0.15g
S1 0.05g
ASSUMED SOIL SITE CLASS D
SDS 0.160g
SD1 0.08g
SEISMIC DESIGN CATEGORY B
SEISMIC FORCE-RESISTING SYSTEM(S)N/A
BASE SHEAR, V N/A
SEISMIC RESPONSE COEFFICIENT, CS N/A
RESPONSE MODIFICATION COEFFICIENT, R N/A
RAIN INTENSITY, i
DESIGN PARAMETERS
2.35 INCHES/HOUR
ALLOWABLE STRESS DESIGN WIND SPEED 92 MPH
SOIL DESIGN PRESSURE N/A
ANALYSIS PROCEDURE N/A
EXPOSURE FACTOR, Ce 1.0
SLOPE FACTOR, Cs N/ASNOW
WINDSEISMICCORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
S-001
11874770
GENERAL
NOTES,
ABBREVIATIONS,
AND LEGEND
Q. OLSEN
QO
2051
APRIL 8, 2020
CODES
1. PERFORM ALL CONSTRUCTION IN ACCORDANCE WITH THE 2020 NEW YORK
STATE BUILDING CODE AND CITY OF ITHACA AMENDMENTS REFERENCING THE
FOLLOWING CODES AND STANDARDS:
A. ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE
B. ASCE7-16 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER
STRUCTURES WITH SUPPLEMENT NO. 1
C. 2018 INTERNATIONAL EXISTING BUILDING CODE (IEBC)
D. 2018 INTERNATIONAL BUILDING CODE (IBC)
DEFLECTION CRITERIA
1. GRAVITY LOAD DEFLECTION CRITERIA:
A. TOTAL LOAD: L/240
B. LIVE LOAD: L/360
DESIGN LOADS
1.DEAD LOADS PER THE EXISTING DRAWINGS
A. EXISTING CONCRETE ON METAL DECK: 77 PSF
B. CEILING: 5 PSF
C. MEP: 5 PSF
D. 3”NORMAL WEIGHT CONCRETE TOPPING 38 PSF
2.ADDITIONAL DEAD LOADS:
A. EXISTING STRUCTURAL STEEL FRAMING: 7 PSF
3.LIVE LOADS:
A. THE ELECTRICAL ROOM HAS A LIVE LOAD RATING OF 150 PSF PER THE
EXISTING DRAWINGS. SEE LIVE LOAD MAP FOR CHANGES.
B. BATTERY CABINET: 4678 LBS (PER CABINET)
C. UPS: 2150 LBS (PER UPS)
D. SBM: 700 LBS
STRUCTURAL STEEL
1. ALL STRUCTURAL STEEL SHALL BE ASTM FABRICATED AND ERECTED IN
ACCORDANCE WITH AISC "STEEL CONSTRUCTION MANUAL" AND ALL WORK
SHALL COMPLY WITH AISC "CODE OF STANDARD PRACTICE FOR STEEL
BUILDINGS AND BRIDGES."
2. GRADES OF STRUCTURAL STEEL TO BE PER TABLE THIS SHEET U.O.N.
3. ALL BOLTED CONNECTIONS TO BE MADE WITH A325 OR A490 TYPE N HIGH
STRENGTH BOLTS UNLESS GALVANIZED BOLTS ARE SPECIFIED. WHERE
GALVANIZED BOLTS ARE SPECIFIED ON THE DRAWINGS, GALVANIZED BOLTS
SHALL CONFORM TO ASTM A153, CLASS C AND SHALL BE HOT-DIP GALVANIZED
.
4. ALL NUTS SHALL MEET REQUIREMENTS OF ASTM A-563 DH OR ASTM A-194 2H.
5. ALL WASHERS SHALL MEET REQUIREMENTS OF ASTM F-436.
6. ALL BOLT HOLES IN STEEL MEMBERS SHALL BE 1/16" LARGER IN DIAMETER THAN
THE NOMINAL SIZE OF THE BOLT USED, U.N.O. ON DRAWINGS.
7. WELDING SHALL MEET THE REQUIREMENTS OF OF THE "STRUCTURAL WELDING
CODE" AWS D1.1-2006. ELECTRODES SHALL HAVE A MINIMUM TENSILE
STRENGTH OF 70 KSI AND BE LOW-HYDROGEN TYPE. THE LENGTH OF WELD
SPECIFIED ON THE DRAWINGS IS THE MINIMUM EFFECTIVE LENGTH OF THE
WELD. ALL WELDS TO BE A MINIMUM 1/4" FILLET WELD U.N.O. ON DRAWINGS.
8. ALL INTERIOR STEEL SHALL BE PAINTED IN THE SHOP WITH DEVGUARD 4360 OR
APPROVED EQUAL U.N.O. ON THE DRAWINGS.
9. ALL STEEL SHALL BE INSTALLED WITH CAMBER UP EXCEPT WHERE NOTED
OTHERWISE ON DRAWINGS AND AT CANTILEVERS WHERE STEEL SHALL BE
INSTALLED WITH CAMBER DOWN.
10. NO FABRICATION SHALL PROCEED PRIOR TO SHOP DRAWING APPROVAL. SHOP
DRAWINGS MARKED "REJECTED" OR "REVISE AND RESUBMIT" MAY NOT BE
FABRICATED WITHOUT ADDITIONAL CHANGES BEING MADE.
11. DEVELOPMENT OF STRUCTURAL STEEL SHOP DRAWINGS SHALL BE
SUPERVISED BY A NEW YORK STATE-REGISTERED PROFESSIONAL ENGINEER
AND SHALL INCLUDE DETAILS FOR APPLICATIONS AND ASSEMBLY OF ALL
STRUCTURAL MEMBERS; INCLUDE DETAILS OF CUTS, CONNECTIONS, HOLES,
AND OTHER PERTINENENT DATA; AND INDICATE WELDS BY STANDARD AWS 2.1
SYMBOLS SHOWING SIZE, LENGTH, AND TYPE OF EACH WELD. SHOP DRAWINGS
SHALL BE SUBMITTED TO ARCHITECT FOR APPROVAL PRIOR TO FABRICATION.
12. SPLICING OF STRUCTURAL MEMBERS WHERE NOT DETAILED ON THE CONTRACT
DOCUMENTS IS PROHIBITED WITHOUT PRIOR APPROVAL OF THE STRUCTURAL
ENGINEER AS TO LOCATION, TYPE OF SPLICE, AND CONNECTION TO BE MADE.
POST-INSTALLED ANCHORS
1. UNLESS NOTED OTHERWISE ON DRAWINGS, THE FOLLOWING EPOXIES ARE TO
BE USED WITH THE FOLLOWING BASE MATERIALS FOR ADHESIVE ANCHORS:
A. CAST IN PLACE AND PRECAST CONCRETE –HILTI HIT HY 200 R, POWERS
AC200+, OR POWERS AC100+ GOLD
B. CONCRETE MASONRY UNITS –HILTI HIT HY 270 OR POWERS AC100+
GOLD
2. EXPANSION ANCHORS TO BE STAINLESS STEEL. MANUFACTURER OF
EXPANSION ANCHORS TO BE HILTI OR POWERS (DEWALT) OR APPROVED
EQUAL. SUBMIT EXPANSION ANCHOR PRODUCT DATA FOR APPROVAL BY
STRUCTURAL ENGINEER OF RECORD PRIOR TO INSTALLATION.
TESTING & INSPECTIONS
1. OWNER SHALL RETAIN THE SERVICES OF AN INSPECTION AGENCY TO PERFORM
THE FOLLOWING SERVICES. ADDITIONAL INSPECTIONS SHALL BE PROVIDED IN
ACCORDANCE WITH LOCAL CODE REQUIREMENTS.
2. ALL NEW BOLTED CONNECTIONS SHALL BE VISUAL INSPECTED FOR
CONFORMANCE WITH INDUSTRY STANDARDS FOR INSTALLTION AND FOR
CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS.
3. ALL NEW STRUCTURAL WELDS MUST BE VISUALLY INSPECTED FOR
CONFORMATIONS WITH INDUSTRY STANDARDS FOR INSTALLATION AND FOR
CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS. IF THE WELDERS DO
NOT HAVE AWS CERTIFICATION, ALL OF THE STRUCTURAL WELDS MUST BE
TESTED WITH 100% MAGNETIC PARTICLE TESTING TO CONFIRM THE WELDS
MEET THE MINIMUM STRENGTH REQUIREMENTS FOR THE CONNECTIONS.
STRUCTURAL GENERAL NOTESLIVE LOAD MAP
STRUCTURAL LEGEND
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION
1 2 3
E
D
C
1 2 3
E
D
C7' - 6 5/8"7' - 6 5/8"7' - 6 5/8"1 5' - 2 1/4"
5' - 10 3/4"
6' - 7 1/4"
7' - 3 3/4"
(E) W12X16 BELOW
(E) W12X16 BELOW
BEAMS EXTEND
3" PAST GRIDLINE
BEAMS EXTEND
3" PAST GRIDLINE
1/2" GAP BETWEEN
ENDS OF BEAMS,
TYP. ABOVE
EXISTING BEAMS
(E) W36X150 BELOW
(E) W36X150 BELOW (E) W21X50 BELOW(E) W24X55 BELOWCORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
S-101
11874770
PENTHOUSE
FLOOR PLAN
Q. OLSEN
JD
2051
APRIL 8, 2020
SCALE:1/4" = 1'-0"1 NEW FRAMING ABOVE SLAB
0 2 4 8
SCALE: 1/4"=1'-0"
GENERAL NOTES
1. EXISTING BATTERY CABINETS CAN REMAIN IN PLACE WHEN STEEL IS
INSTALLED.
2. REMOVE TWO EXISTING BATTERY CABINETS PRIOR TO INSTALLATION OF TWO
NEW CABINETS. REMOVE REMAINING TWO EXISTING BATTERY CABINETS PRIOR
TO INSTALLATION OF FINAL TWO NEW CABINETS. THIS IS CRITICAL FOR THE
LOAD OF THE CABINETS TO NOT EXCEED THE CAPACITY OF THE STRUCTURAL
FRAMING. WHEN BATTERIES ARE BROUGHT INTO THE ROOM, THEY MUST BE
BROUGHT IN WITH ONLY A SINGLE LAYER OF BATTERIES ON THE PALLET. IF THE
CONTRACTOR WISHES TO TRANSPORT THE BATTERIES IN A DIFFERENT WAY,
THE ENGINEER OF RECORD MUST APPROVE FIRST.
3. SEE ELECTRICAL DRAWINGS FOR THE EXACT LAYOUT OF THE BATTERY
CABINETS. THE CABINETS MUST BE CENTERED BETWEEN GRIDS D AND E. THE
CABINETS MUST BE CENTERED ON THE NEW STEEL BEAMS IN THE EAST-WEST
DIRECTION.
4. SEE ELECTRICAL DRAWINGS FOR CONCRETE EQUIPMENT PADS TO BE
REMOVED IN THE 1-2/D-E BAY MUST BE REMOVED PRIOR TO THE INSTALLATION
OF THE BATTERY CABINETS. THE CONCRETE PADS IN THE 1-2/C-D BAY MUST BE
REMOVED PRIOR THE UPS & SBM INSTALLATIONS. CONTRACTOR TO PROTECT
EXISTING STRUCTURAL SLAB DURING DEMO OF CONCRETE EQUIPMENT PADS.
5. CONTRACTOR TO REVIEW SEQUENCE OF DEMO AND INSTALLATION WITH
STRUCTURAL ENGINEER PRIOR TO BEGINNING DEMO AND INSTALLATION.
THERE ARE LIMITED OPTIONS FOR TEMPORARY SHORING BECAUSE OF THE
SERVER ROOM LOCATED DIRECTLY BELOW. SEE THE LIVE LOAD MAP ON S-001
FOR THE MAXIMUM LOADS THAT CAN BE PLACED ON THE FLOOR IN EACH AREA
WITHOUT ANY SHORING BEING REQUIRED. THESE LOADS ASSUME THE
CONCRETE EQUIPMENT PADS HAVE ALREADY BEEN REMOVED.
S-100 KEYED CONSTRUCTION NOTES
1 12 NEW W8 X 31 BEAMS TO BE INSTALLED SO THAT THE BOTTOM OF THE STEEL IS
1 ½” ABOVE THE TOP OF THE SLAB.
#
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION
NEW BATTERY
CABINET MAXIMUM 1/2" GAP BETWEEN ENDS OF BEAMS
FLOOR
1/2" Ø EXPANSION ANCHORS
EMBEDDED A MINIMUM OF 2"
INTO EXISTING CONCRETE
1' - 1"
3"3"
3'-2" X 1'-1" X 1/2" STEEL
PLATE WITH FOUR (4)
EXPANSION ANCHORS
1/2" Ø EXPANSION ANCHORS
EMBEDDED A MINIMUM OF 2"
INTO EXISTING CONCRETE
ANCHORS TO ONLY BE
LOCATED AT BEARING
PLATES (12 ANCHORS
IN TOTAL)
3 3/4"3"
3'-2" X 6-3/4" X 1/2" STEEL
PLATE WITH TWO (2)
EXPANSION ANCHORS
3/4"
3/16"
NEW BATTERY
CABINET
1/2" Ø EXPANSION ANCHORS
EMBEDDED A MINIMUM OF 2"
INTO EXISTING CONCRETE
1/2" Ø EXPANSION ANCHORS
EMBEDDED A MINIMUM OF 2"
INTO EXISTING CONCRETE
HOLES IN PLATE FOR
ANCHORS TO BE 3/4" Ø
3' - 2"
1"1"
1/2" THICK X 3'-2" LONG
STEEL PLATE. WIDTH
VARIES, SEE OTHER
DETAILS THIS SHEET
PROVIDE 3/4"X1" SLOT IN
BOTTOM FLANGE OF BEAM
WHERE IT BEARS ON PLATE.
WELD BEAM TO PLATE.
3/16"3/16"
WELD BEAM TO PLATEWELD BEAM TO PLATE CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
S-401
11874770
DETAILS
Q. OLSEN
JD
2051
APRIL 8, 2020
SCALE:1 1/2" = 1'-0"3 TYPICAL BEARING CONNECTION MIDDLE
SCALE:1 1/2" = 1'-0"1 TYPICAL BEARING CONNECTION AT END
SCALE:1 1/2" = 1'-0"2 TYPICAL BEARING CONNECTION SECTION
SCALE: 1-1/2"=1'-0"
6 1 20 3
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION
ARCHIVE BAR CODEITHACA, NEW YORK
Rhodes Hall
UPS Replacement
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
P11874770
DATE:
FACILITY:
DESIGN:
DRAWN:
TMT
TMT
2051
April 8, 2020
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONSCORNELLUNIV
E
RSI
TYFOUN
DE D 5681AD
FACILITIES
ENGINEERING
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
GHD Project #11205715
GHD Consulting Services Inc.
5788 Widewaters Pkwy
Syracuse NY 13214 USA
T 1 315 802 0260 F 1 315 802 0450
RHODES HALL
ISSUE FOR 95% REVIEW103/20/20
100% FOR CONSTRUCTION204/08/20
F-001
SYMBOL LIST,
GENERAL NOTES
AND
ABBREVIATION
LIST
FIRE PROTECTION SYMBOL LIST
MANUAL PULL STATION. MOUNTING HEIGHT: +48" AFF (TO CENTER)
SMOKE SENSOR, PHOTOELECTRIC, CEILING MOUNTED
FIRE ALARM CONTROL PANEL
FIRE ALARM GENERAL NOTES:
1.THE SYSTEM SHALL INCLUDE ALL WIRING, RACEWAYS, PULL BOXES, TERMINAL CABINETS, OUTLET AND MOUNTING BOXES,
CONTROL EQUIPMENT, ALARM, AND SUPERVISORY SIGNAL INITIATING DEVICES, ALARM NOTIFICATION APPLIANCES, INTERFACE
EQUIPMENT, AND OTHER ACCESSORIES AND MISCELLANEOUS ITEMS INCLUDING SOFTWARE, SYSTEM PROGRAMMING, TESTING
AND CONSTRUCTION PERMITS REQUIRED FOR A COMPLETE OPERATING SYSTEM EVEN THOUGH EACH ITEM IS NOT
SPECIFICALLY MENTIONED OR DESCRIBED. PROVIDE SYSTEM COMPLETE AND READY FOR OPERATION. THE SYSTEM MUST
COMPLY WITH THE 2015 INTERNATIONAL BUILDING CODE (IBC) WITH THE 2017 NYS UNIFORM CODE SUPPLEMENT.
2.PROVIDE ALL WIRING FROM APPLIANCE TERMINAL TO APPLIANCE TERMINAL. PROVIDE CONDUCTORS THAT ARE TERMINATED,
SPLICED, OR OTHERWISE INTERRUPTED IN ANY ENCLOSURE, CABINET, MOUNTING, OR JUNCTION BOX CONNECTED TO
SCREW-TYPE TERMINAL BLOCKS. WIRE NUTS AND SIMILAR DEVICES ARE PROHIBITED.
3.PROVIDE ALL FIRE ALARM CIRCUITS SUPERVISED UNLESS NOTED OTHERWISE, AS FOLLOWS IN ACCORDANCE WITH NFPA 72
(2013):
·INITIATING DEVICE CIRCUITS (IDC)- CLASS B
·NOTIFICATION APPLIANCE CIRCUITS (NAC)- CLASS B, SYNCHRONIZED
·SIGNALING LINE CIRCUITS (SLC)- CLASS B
4.PROVIDE SMOKE DETECTORS A MINIMUM OF 3 FEET FROM EXISTING AIR DIFFUSERS.
5.PROVIDE VISUAL WARNING STROBE/AUDIBLE NOTIFICATION APPLIANCES TO ACHIEVE MAXIMUM AUDIBILITY AND VISIBILITY IN
ACCORDANCE WITH NFPA 72 GUIDELINES. PROVIDE CARE IN LOCATING VISUAL WARNING STROBE APPLIANCES TO ENSURE
VISIBILITY AND AVOID OBSTRUCTIONS.
6.LABEL ALL ADDRESSABLE INPUT/OUTPUT FIRE ALARM COVER PLATES AND APPLIANCES (INCLUDING HORNS, STROBES, SMOKE
SENSORS, HEAT SENSORS, MANUAL PULL STATIONS, ADDRESSABLE MODULES, ETC.) WITH THEIR ADDRESS UTILIZING A
LABELING MACHINE. HAND WRITTEN LABELS MUST NOT BE USED. ADDRESS MUST INCLUDE NAC OR SLC NUMBER FOLLOWED BY
APPLIANCE NUMBER. EACH SLC FIELD APPLIANCE ADDRESS MUST MATCH THE FIRE ALARM DISPLAY ADDRESS.
7.UNLESS OTHERWISE NOTED THE PROJECT ELECTRICAL CONDUIT STANDARD IS ELECTRICAL METALLIC TUBING (EMT) AND
PROVIDED THROUGHOUT THE PROJECT. PROVIDE ALL WIRING IN CONDUIT WHERE WIRES WOULD OTHERWISE BE EXPOSED.
WIRING MAY BE CONCEALED WITHIN WALLS AND CEILINGS WHERE APPLICABLE.
8.FLEXIBLE METAL CONDUIT (FMC) IS LIMITED TO 5 FEET AND SECURED PER THE NATIONAL ELECTRIC CODE (2014). FMC IS
PERMITTED FOR DEVICES LOCATED ON FIRE SUPPRESSION EQUIPMENT ONLY SUCH AS FLOW/PRESSURE SWITCHES,
SOLENOIDS AND TAMPER SWITCHES.
9.PROVIDE CONDUIT AS UNOBTRUSIVELY AS POSSIBLE, AS CLOSE AS POSSIBLE TO FLOOR/ CEILING SLAB AND PARALLEL AND AT
RIGHT ANGLES TO STRUCTURAL ELEMENTS.
10.PROVIDE ELECTRICAL BOXES AS FOLLOWS: UNLESS OTHERWISE NOTED PROVIDE CAST METAL BELL TYPE BOXES WITH
THREADED HUBS ON EXPOSED WORK, EXCEPT WHERE FACTORY BOXES ARE PROVIDED. CONCEALED BOXES MAY BE STAMPED
STEEL BOXES. PROVIDE TERMINAL CABINETS OF SOLID WALL CONSTRUCTION WITH NO FACTORY CONDUIT KNOCK OUTS.
11.PAINT ALL CONDUIT, FIRE ALARM JUNCTION BOXES AND COVERS RED IN UNFINISHED AREAS.
12.CORE DRILL PENETRATIONS IN MASONRY WALLS AND FLOOR/CEILING SLABS.
13.BOTH EXPOSED AND CONCEALED CONDUIT INCLUDING RISERS UP TO 2 INCHES IN DIAMETER MUST UTILIZE COMPRESSION
TYPE STEEL FITTINGS AND CONNECTORS. UNLESS OTHERWISE NOTED PROVIDE ALL CONDUIT 3/4 INCH MINIMUM TRADE SIZE.
PROVIDE VERTICAL RISERS ONE INCH DIAMETER MINIMUM. PROVIDE PLENUM RATED WIRING CONDUCTORS (TYPE FPLP) WHEN
FLEX CONDUIT IS UTILIZED. PROVIDE SOLID COPPER WIRING CONDUCTORS INSTALLED IN CONDUIT FOR THE FOLLOWING
CIRCUITS (AT MINIMUM):
·FIRE ALARM INITIATING DEVICE CIRCUITS (IDC) - 14/2 AWG
·FIRE ALARM SIGNALING LINE CIRCUITS (SLC) - 16/2 AWG TWISTED PAIR
·FIRE ALARM VISUAL NOTIFICATION APPLIANCES - 12/2 AWG.
·120 VAC - PRIMARY POWER - NO. 12 AWG, THHN/THWN 600VAC INSULATED
PROVIDE ALL WIRING UL LISTED FOR ITS INTENDED USE.
14.SECURE ALL NECESSARY CONSTRUCTION PERMITS, INSPECTIONS AND FINAL SYSTEM ACCEPTANCE.
15.CONTRACT DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY AND USED IN CONJUNCTION TO OBTAIN COMPLETE
CONSTRUCTION INFORMATION. CONTRACTOR MUST COORDINATE ALL DRAWINGS AND SPECIFICATIONS PRIOR TO
COMMENCING WORK.
16.VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE CONCERNING THE WORK BEFORE PROCEEDING WITH EITHER
FABRICATION OR INSTALLATION OF WORK. LOCATION OF EQUIPMENT IS APPROXIMATE. VERIFY THE LOCATION OF ALL SYSTEM
COMPONENTS.
17.AVOID ALL CONFLICTS WITH EXISTING LIGHT FIXTURES, HVAC DIFFUSERS, GRILLES, DUCTS, CONDUIT AND OTHER PIPING OR
OTHER OBSTRUCTIONS ENCOUNTERED. COORDINATE ALL WORK WITH FIELD CONDITIONS.
18.DO NOT CUT OR PATCH STRUCTURAL WORK IN A MANNER THAT WOULD RESULT IN A REDUCTION OF LOAD-CARRYING OR
LOAD-DEFLECTION RATIO.
19.PROVIDE ACCEPTANCE TESTING OF THE FIRE ALARM SYSTEM IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS.
20."PROVIDE" MEANS CONTRACTOR MUST FURNISH NEW AND INSTALL COMPLETE AND READY FOR INTENDED USE.
F
FACP
S
P
F
H FIRE ALARM HORN/STROBE
FIRE ALARM REMOTE ANNUNCIATOR PANELANN
FIRE FIGHTER PHONEP
SUPERVISED CONTROL VALVE
CHECK VALVE
PREACTION VALVE
UPRIGHT SPRINKLER
SPRINKLER PIPE
AIR COMPRESSORAC
FIRE ALARM 2-HOUR CI CABLE IN CONDUIT
EXISTING UPRIGHT SPRINKLER
EXISTING SPRINKLER PIPE
EXISTING TO REMAINEX
HYDROGEN GAS DETECTORH
EXISTING ELECTRICAL POWER PANELELECEX
G
H GAS DETECTION HORN/STROBE, RED STROBE, HIGH/LOW TONE
ADDRESSABLE RELEASING CONTROL PANELRCP
SOLENOID VALVESV
WATERFLOW SWITCHWF
TAMPER SWITCHTS
LOW AIR SUPERVISORY SWITCHLA
ADDRESSABLE OUTPUT MODULE
ADDRESSABLE INPUT MODULEAIM
AOM
ADDRESSABLE RELAYAR
END OF LINE RESISTOREOL
CONNECT TO EXISTING
REMOVE DEVICE AND ASSOCIATED EQUIPMENT
TRANSIENT VOLTAGE SURGE SUPPRESSIONTVSS
FULL-PORT BALL VALVE
VELOMETERV
DN
LOUVERS LOUVERS LOUVERS LOUVERSLOUVE
R
S
80003
80046 80047
80061
80064
80060
801
802
801A
804
807
809
811
80062
S
P
S
P
S
P
S
P
FH EXPEX
PEX
ELECELECEX EX
ARCHIVE BAR CODEITHACA, NEW YORK
Rhodes Hall
UPS Replacement
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
P11874770
DATE:
FACILITY:
DESIGN:
DRAWN:
TMT
TMT
2051
April 8, 2020
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONSCORNELLUNIV
E
RSI
TYFOUN
DE D 5681AD
FACILITIES
ENGINEERING
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
GHD Project #11205715
GHD Consulting Services Inc.
5788 Widewaters Pkwy
Syracuse NY 13214 USA
T 1 315 802 0260 F 1 315 802 0450
RHODES HALL
ISSUE FOR 95% REVIEW103/20/20
100% FOR CONSTRUCTION204/08/20
PARTIAL PENTHOUSE
FIRE PROTECTION REMOVAL PLAN
SCALE: 3/16" = 1'-0"0
SCALE 3/16"=1'-0" AT ORIGINAL SIZE
8'-0"6'-0"4'-0"2'-0"
GENERAL NOTES:
A.
1
KEYED NOTES:
EXISTING BUILDING FIRE ALARM HORN/STROBE AND FIRE PHONE SHALL REMAIN.
EXISTING SMOKE DETECTORS LOCATED WITHIN THE ENERGY STORAGE SYSTEM ROOM AND
ASSOCIATED CONDUIT AND WIRING SHALL BE REMOVED.
F-101
PARTIAL
PENTHOUSE
FIRE
PROTECTION
REMOVAL PLAN
DN
DN
DN
KEY PLAN
NO SCALE
AREA OF
WORK
1
1
UP
UP
RAMP UP
B0069
B10
B20
B0064
B0066
B50
B0067
B0068
B60
B0073
B0071
B0072
B0020
B0021
B0070
B0004
B0003
B0074
B0065
B40
B30
B0075
B18B31
B33
B35
B37
B0063
B0062
B0061
F
A
C
P
ANNANNEX
EX
EXFACP
ARCHIVE BAR CODEITHACA, NEW YORK
Rhodes Hall
UPS Replacement
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
P11874770
DATE:
FACILITY:
DESIGN:
DRAWN:
TMT
TMT
2051
April 8, 2020
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONSCORNELLUNIV
E
RSI
TYFOUN
DE D 5681AD
FACILITIES
ENGINEERING
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
GHD Project #11205715
GHD Consulting Services Inc.
5788 Widewaters Pkwy
Syracuse NY 13214 USA
T 1 315 802 0260 F 1 315 802 0450
RHODES HALL
ISSUE FOR 95% REVIEW103/20/20
100% FOR CONSTRUCTION204/08/20
BASEMENT FIRE PROTECTION PLAN
SCALE: 3/32" = 1'-0"
0
SCALE 3/32"=1'-0" AT ORIGINAL SIZE
16'-0"12'-0"8'-0"4'-0"
GENERAL NOTES:
A.
B.
C.
INSTALL ALL CONDUIT EXPOSED IN AREAS WITH NO FINISHED CEILINGS UNLESS OTHERWISE
NOTED.
INSTALL ALL WIRING AND CONDUIT WITH THE REQUIRED SUPPORT/HANGERS. INSTALL ALL
SUPPORTS FROM THE BUILDING STRUCTURE.
FIRE STOP ALL PENETRATIONS THROUGH RATED WALLS, FLOORS AND CEILINGS.
F-102
BASEMENT
FIRE
PROTECTION
PLAN
EXISTING FIRE PUMP
LOCATION FOR HYDRAULIC
CALCULATION PURPOSES
EXISTING 6-INCH
STANDPIPE
FIRE ALARM CONDUIT UP TO
PENTHOUSE FIRE ALARM SUBPANEL
KEYED NOTES:
2-HOUR CIRCUIT INTEGRITY FIRE ALARM CABLING SHALL BE INSTALLED WITHIN EMT CONDUIT.
LOCATION OF VERTICAL CONDUIT RUNS SHALL BE COORDINATED WITH BUILDING
PERSONNEL. IF A COMMON VERTICAL CONDUIT LOCATION IS FOUND, IT SHALL BE UTILIZED.
PROVIDE NEW FCI E3 FACP ADJACENT TO THE EXISTING FCI 72C FACP TO RECEIVE ALARM,
SUPERVISORY AND TROUBLE SIGNALS FROM THE PENTHOUSE RELEASING PANEL AND
REPORTING ALARM SIGNALS THROUGH THE EXISTING MAIN FACP TO THE CAMPUS CENTRAL
STATION AT BARTON HALL. PROVIDE AN ADDRESSABLE MODULE AND RECIRCUIT ONE
EXISTING BASEMENT FLOOR FIRE ALARM ZONE THROUGH IT TO THE NEW FACP. CONNECT
THE NEW FACP TO THE NEW SPARE ZONE IN THE EXISTING FACP.
1
2
2
1
2
3
3
DN
FH EXPEX
FH
F
H
F
H
ACRCPFH
HH
H
ELECELECEX EX
PEX
HH S
P
GH
GH
G
H
GH
GH
G
H
F
F
F
WF
AIM
LA
AIM
TS
AIM
S
P
S P
S
P
S
P
S
P
F
H
AIM
FH
FH
F
H
ARCHIVE BAR CODEITHACA, NEW YORK
Rhodes Hall
UPS Replacement
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
P11874770
DATE:
FACILITY:
DESIGN:
DRAWN:
TMT
TMT
2051
April 8, 2020
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONSCORNELLUNIV
E
RSI
TYFOUN
DE D 5681AD
FACILITIES
ENGINEERING
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
GHD Project #11205715
GHD Consulting Services Inc.
5788 Widewaters Pkwy
Syracuse NY 13214 USA
T 1 315 802 0260 F 1 315 802 0450
RHODES HALL
ISSUE FOR 95% REVIEW103/20/20
100% FOR CONSTRUCTION204/08/20
PARTIAL PENTHOUSE
FIRE PROTECTION PLAN
SCALE: 1/8" = 1'-0"
GENERAL NOTES:
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
KEYED NOTES:
PROVIDE ADDRESSABLE FIRE ALARM RELEASING CONTROL PANEL. SEE RISER DIAGRAM ON
DRAWING F-600.
2-HOUR CIRCUIT INTEGRITY CABLING FIRE ALARM WIRING SHALL BE INSTALLED WITHIN EMT
CONDUIT.
POWER PANEL ELP-P SHALL BE UTILIZED FOR POWER FOR FIRE PROTECTION DEVICES, I.E.
FIRE ALARM CONTROL PANEL, AIR COMPRESSOR, MONITORING EQUIPMENT (WATERFLOW
SWITCH, SUPERVISORY SWITCH, TAMPER SWITCH), SOLENOID VALVE.
LOCATION OF VERTICAL CONDUIT RUNS SHALL BE COORDINATED WITH BUILDING
PERSONNEL. IF A COMMON VERTICAL CONDUIT LOCATION IS FOUND, IT SHALL BE UTILIZED.
HYDROGEN GAS DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
INSTRUCTIONS AND SHALL BE PROGRAMMED TO A SENSITIVITY OF 12.5% OF THE LOWER
FLAMMABILITY LIMIT OF HYDROGEN GAS. MANUFACTURER REPRESENTATIVE SHALL FIELD
VERIFY THAT HYDROGEN DETECTOR SPACING WILL BE EFFECTIVE.
MAIN DRAIN AND INSPECTOR'S TEST DISCHARGE SHALL BE COORDINATED WITH EXISTING
DRAIN RISER. CAPACITY OF EXISTING DRAIN TO BE UTILIZED SHALL BE CONFIRMED.
PROVIDE ADDRESSABLE INPUT MODULE ABOVE OR ADJACENT TO CELLWATCH CONTROL
UNIT. INPUT MODULE SHALL SUPERVISE CU RELAY OUTPUT #5 (WARNING).
PROVIDE FLUSHING FULL-PORT BALL VALVE ON EACH BRANCH LINE MATCHING THE SIZE OF
THE BRANCH LINE PIPING.
PROVIDE THREE 2-1/2" FLUSHING FULL PORT BALL VALVES ON THE END OF THE 6-INCH
SUPPLY MAIN.
PREACTION VALVE DRAIN PIPING SHALL BE ROUTED DOWN TO THE FLOOR BELOW THEN TO
THE EXISTING DRAIN RISER.
PROVIDE A COMPLETE AUTOMATIC FIRE ALARM SYSTEM IN ACCORDANCE WITH THE 2020
BUILDING CODE OF NEW YORK STATE AND NFPA 72 (2016) FOR THE ENERGY STORAGE
SYSTEM ROOM.
PROVIDE A COMPLETE AUTOMATIC PREACTION SPRINKLER SYSTEM IN ACCORDANCE WITH
THE 2020 BUILDING CODE OF NEW YORK STATE AND NFPA 13 (2016) FOR THE ENERGY
STORAGE SYSTEM ROOM.
PIPING AS SHOWN IS DIAGRAMMATIC, NOT ALL PIPING/FITTINGS ARE INDICATED.
CONTRACTOR IS RESPONSIBLE FOR FINAL SPRINKLER SYSTEM PIPE SIZING/LAYOUT,
SPRINKLER HYDRAULIC CALCULATIONS, AND COORDINATION WITH LIGHT FIXTURES/FIRE
ALARM DEVICES, DUCTWORK AND DIFFUSERS.
FINAL PIPE SIZING SHALL BE DETERMINED BY CONTRACTOR HYDRAULIC CALCULATIONS
SUBJECT TO APPROVAL BY ENGINEER.
MAXIMUM SPRINKLER COVERAGE AREA SHALL BE 120 SQ.FT.
SPRINKLER DESIGN CRITERIA IS AS FOLLOWS: 0.30GPM/SQ.FT. OVER THE ENTIRETY OF THE
ESS ROOM, 100 GPM HOSE STREAM DEMAND AT TOP OF STANDPIPE & 400 GPM AT WATER
SUPPLY SOURCE.
INSTALL ALL CONDUIT EXPOSED IN AREAS WITH NO FINISHED CEILINGS UNLESS OTHERWISE
NOTED.
INSTALL ALL WIRING AND CONDUIT WITH THE REQUIRED SUPPORT/HANGERS. INSTALL ALL
SUPPORTS FROM THE BUILDING STRUCTURE.
INSTALL ALL INITIATING DEVICES IN A MANNER THAT PROVIDES ACCESSIBILITY FOR PERIODIC
INSPECTION, TESTING AND MAINTENANCE.
FIRE STOP ALL PENETRATIONS THROUGH RATED WALLS, FLOORS AND CEILINGS.
ALL PIPE SIZES SHALL BE SCHEDULE 40 BLACK STEEL WITH THREADED FITTINGS.
SPRINKLERS SHALL BE LOCATED A MINIMUM OF 24 INCHES FROM THE SIDE OF HVAC
DIFFUSERS.
ALL SPRINKLER PIPING SHALL BE PITCHED BACK TO THE PREACTION VALVE TO ALLOW FOR
PROPER DRAINAGE AND TO ELIMINATE THE POSSIBILITY OF TRAPPED WATER.
SPRINKLER SUPPLY MAIN AND BRANCH PIPING SHALL BE ROUTED DIRECTLY BELOW THE
STRUCTURAL I-BEAMS WITH VERTICAL PIPING UP TO THE DECK FOR EACH UPRIGHT
SPRINKLER.
F-103
PARTIAL
PENTHOUSE
FIRE
PROTECTION
PLAN
0
SCALE 3/16"=1'-0" AT ORIGINAL SIZE
8'-0"6'-0"4'-0"2'-0"
DN
DN
DN
KEY PLAN
NO SCALE
AREA OF
WORK
EXISTING 6-INCH
STANDPIPE
6"
6"
6"
FIRE ALARM
CONDUIT DOWN
TO BASEMENT
6-INCH PREACTION VALVE ASSEMBLY
(SEE DETAIL 1 "PREACTION FIRE
SPRINKLER VALVE" ON DRAWING F-500)
EXISTING 2-INCH MAIN
DRAIN DISCHARGE
ENERGY STORAGE
SYSTEM LOCATIONS
TYP.
DOWN TO INSPECTOR TEST CONNECTION. SEE
DETAIL 5 "INSPECTOR TEST DETAIL" ON DRAWING
F-500. DRAIN TO EXISTING STAIRWELL DRAIN RISER.
TYP.
3
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
ARCHIVE BAR CODEITHACA, NEW YORK
Rhodes Hall
UPS Replacement
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
P11874770
DATE:
FACILITY:
DESIGN:
DRAWN:
TMT
TMT
2051
April 8, 2020
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONSCORNELLUNIV
E
RSI
TYFOUN
DE D 5681AD
FACILITIES
ENGINEERING
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
GHD Project #11205715
GHD Consulting Services Inc.
5788 Widewaters Pkwy
Syracuse NY 13214 USA
T 1 315 802 0260 F 1 315 802 0450
RHODES HALL
ISSUE FOR 95% REVIEW103/20/20
100% FOR CONSTRUCTION204/08/20
F-501
FIRE
PROTECTION
DETAILS
6-INCH FROM FIRE
PROTECTION WATER
SUPPLY
SUPERVISED CONTROL
VALVE WITH TAMPER
SWITCH WIRED TO ESS
ROOM SUBPANEL
LOW AIR PRESSURE
SUPERVISORY SWITCH
WIRED TO ESS ROOM
SUBPANEL
AUTO AIR
MAINTENANCE DEVICE
PRESSURE
GAUGE (TYPICAL)
FINISHED FLOOR
CHECK VALVE
TO PREACTION
SYSTEM
6-INCH PREACTION
VALVE
AIR COMPRESSOR
MANUAL EMERGENCY RELEASE DEVICE
PRESSURE OPERATED RELIEF VALVE
CONCRETE BASE WITH
BASE ELBOW
MAIN DRAIN DISCHARGE
WITH 45° ELBOW 24" ±
ABOVE EXISTING CAPABLE
PLUMBING DRAIN
EXTERIOR WALL
DRAIN CUP
STRAINER ORIFICE CHECK VALVE
WATERFLOW
SWITCH
ELECTRIC RELEASE
SOLENOID VALVE
STRAINER
DRDR DRNO SCALE
PREACTION FIRE SPRINKLER VALVE
TO ESS ROOM
SUBPANEL
AI
AR
R
SLC TO NEXT DEVICE
120v SHUNT TRIP POWER
SLC TO NEXT DEVICE
EMT (TYPICAL)
ADDRESSABLE LOAD CONTROL FIELD
RELAY WITH 24DC COIL AND 2 SETS
OF NORMALLY OPEN AND NORMALLY
CLOSED (DPDT) CONTACTS RATED AT
120 VAC, 4 AMPS, INDUCTIVE.
ADDRESSABLE RELAY
AI
AR
R
SLC TO NEXT DEVICE
120v SHUNT TRIP POWER TO BATTERY CHARGING
SHUNT TRIP CIRCUIT BREAKER
SLC TO NEXT DEVICE
EMT (TYPICAL)
SEE NOTES 1 & 2
BATTERY CHARGING SHUNT TRIP
CONTROL CIRCUIT INTERFACE
POINT
ADDRESSABLE LOAD CONTROL FIELD
RELAY WITH 24DC COIL AND 2 SETS
OF NORMALLY OPEN AND NORMALLY
CLOSED (DPDT) CONTACTS RATED AT
120 VAC, 4 AMPS, INDUCTIVE.
ADDRESSABLE INTERFACE
MODULE ADDRESSABLE RELAY
GENERAL NOTES:
A.PROVIDE MINIMUM 305X305X100MM DEEP NEMA 1 TERMINAL BOX WITH SCREW COVER (CONTRACTOR SHALL
VERIFY REQUIRED BOX SIZE). LABEL "FIRE ALARM BATTERY CHARGER SHUNT TRIP CONNECTION" WITH
ASSOCIATED ELEVATOR NUMBERS.
B.LOCATE TERMINAL BOX, WITHIN THREE FEET OF ASSOCIATED SHUNT TRIP CIRCUIT BREAKER/DISCONNECT
DEVICE.
NO SCALE
BATTERY CHARGER POWER SHUNT TRIP DETAIL
1
2
3
4
5
6
10
11
WATERFLOW SWITCH
AC POWER FAILURE
LOW BATTERY
OPEN CIRCUIT
GROUND CIRCUIT
NOTIFICATION APPLIANCE CIRCUIT OPEN OR SHORT
A ACTUATE COMMON ALARM SIGNAL INDICATOR ATRELEASING CONTROL PANELACTUATE COMMON SUPERVISORY SIGNAL INDICATORAT RELEASING CONTROL PANELACTUATE COMMON TROUBLE SIGNAL INDICATORAT RELEASING CONTROL PANELSOUND INTERNAL BUZZER AT RELEASING CONTROLPANEL (RCP)TEXT MESSAGE DISPLAY DEVICE TYPE & LOCATIONOF THE ACTIVATING DEVICES ON LCD OFRELEASING CONTROL PANEL (RCP)TRANSMIT FIRE ALARM SIGNAL TO BUILDING FACPACTIVATE GAS DETECTION AUDIBLE/VISUALNOTIFICATION APPLIANCES (RED STROBES)OPEN PREACTION SOLENOID VALVEB C D E F G H I
CONTROL UNIT ANNUNCIATION
SYSTEM OUTPUT
INDICATING/CONTROLLED DEVICES
SYSTEM INPUTS
INITIATING DEVICES
NOTIFICATION
FIRE PROTECTION SYSTEM INPUT/OUTPUT MATRIX
9
J KTRANSMIT SUPERVISORY SIGNAL TO BUILDINGFACPCONTROL FUNCTIONS
NO SCALE
FIRE PROTECTION SYSTEM INPUT/OUTPUT MATRIX
7
8
PREACTION SMOKE DETECTOR
TAMPER SWITCH
LOW AIR PRESSURE SWITCH
HYDROGEN GAS DETECTOR
MANUAL PULL STATION OPEN PREACTION SPRINKLER VALVESHUNT BATTERY CHARGING1
F-500
2
F-500
4
F-500
ROD SIZE (A)
B
C
RODTAKE-OUT (D)MIN. THREADLENGTH (E)PIPE
SIZE A B C
212
12
5916 4
3 634 478
4 71316 512
5 9116 618
6 10716 61516
12
ALL SIZES ARE IN INCHES
2
12
412 314
112 4 3
114 3716 2916
1 21316 218
34 2716 17 8
12 38 218 11116
8 1234 838
38
38
38
38
38
38
38
38
5810 1514 91316
5812 1758 11316
D
3116
31516
438
5
51116
212
214
11316
13 8
118
1516
718
838
91116
E
3
212
212
312
312
312
212
212
212
212
212
212
212
212
MINIMUM ONE FULL
THREAD OF ROD
MUST BE EXPOSED
CLEVIS HANGER
ALL-THREAD ROD
CROSS BOLT
CLEVIS BOLT SPACER
NO SCALE
PIPE SUPPORT DETAIL3
F-500
FINISHED
FLOOR
1" BALL VALVE NOT OVER
7'-0" ABOVE FINISHED FLOOR
BRANCH LINE
RETURN BEND FOR
PREACTION SYSTEM
EXTERIOR BUILDING WALL
NO SCALE
INSPECTOR TEST DETAIL5
F-500
TEMPORARY CONNECTION
PLUG VALVE END WHEN
NOT IN USE
12 CELLWATCH BATTERY MONITORING SYSTEM FAILURE
TO EXISTING STAIRWELL
DRAIN RISER
13 SUPPLY AIR DUCT VELOMETER - VELOCITY DROP
ARCHIVE BAR CODEITHACA, NEW YORK
Rhodes Hall
UPS Replacement
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
P11874770
DATE:
FACILITY:
DESIGN:
DRAWN:
TMT
TMT
2051
April 8, 2020
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONSCORNELLUNIV
E
RSI
TYFOUN
DE D 5681AD
FACILITIES
ENGINEERING
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
GHD Project #11205715
GHD Consulting Services Inc.
5788 Widewaters Pkwy
Syracuse NY 13214 USA
T 1 315 802 0260 F 1 315 802 0450
RHODES HALL
ISSUE FOR 95% REVIEW103/20/20
100% FOR CONSTRUCTION204/08/20
FIRE PROTECTION RISER DIAGRAM
SCALE: NO SCALE
F-601
FIRE
PROTECTION
RISER
DIAGRAM
BASEMENT
PENTHOUSE
FACP ANN
ANN
RCP
IDC - ESS ROOM ALARM
IDC - ESS ROOM SUPRVISORY
EX
TVSS
1
RISER DIAGRAM KEYED NOTES:
TO 120 VAC POWER SOURCE
24 VDC POWER FROM RCP
POWER CIRCUIT TO EACH HYDROGEN GAS DETECTOR
HYDROGEN GAS DETECTION ALARM IDC
HYDROGEN GAS DETECTION TROUBLE/FAULT IDC
ESS ROOM SIGNALING LINE CIRCUIT
TO BATTERY CHARGING SHUNT TRIP
HYDROGEN GAS DETECTION NOTIFICATION APPLIANCE CIRCUIT
EXISTING BUILDING NOTIFICATION APPLIANCE CIRCUIT
EXTEND EXISTING BUILDING NOTIFICATION APPLIANCE CIRCUIT FOR NEW DEVICES
PROVIDE CONTROL PANEL ADJACENT TO EXISTING BUILDING FIRE ALARM CONTROL PANEL
TO RECEIVE ALARM, SUPERVISORY AND TROUBLE SIGNALS FROM THE PENTHOUSE
RELEASING PANEL AND REPORTING ALARM SIGNAL THROUGH THE BUILDING FIRE ALARM
CONTROL PANEL TO THE CAMPUS CENTRAL STATION.
2
3
4
5
6
1
AOM AIM AIM AIM
SV TS LA WF
S
P
S
P
S
P
S
P
AIM AIM
H
H
H
2
3
4
5
S
P
S
P
S
P
S
P
6
AOM AIM
AR2
7
7
G
H
8
8
IDC - GAS DETECTION ALARM
IDC - ESS ROOM TROUBLE
F
H
F
H
G
H
G
H
G
H
EOL EX EX F
H
F
H
EOL
9
10
EOL EOL EOL EOL
EOLEOL
EOL
10
9
F
EX
EX
FACP
11
11
CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
E-001
11874770
GENERAL NOTES
AND SYMBOL
LEGENDS
E. REICHARD
ETR
2051
APRIL 8, 2020
ELECTRICAL SCOPE OF WORK
1.0 THIS PROJECT INCLUDES THE REPLACEMENT OF THE EXISTING 300KVA UPS
SYSTEM WITH A NEW EATON 275KVA UPS SYSTEM, ADDING A MANUAL TRANSFER
SWITCH FOR TOTAL BYPASS OF UPS, BATTERIES AND SBM. THE UPS, SBM,
RECTIFIER PANEL AND GLOBAL BYPASS PANEL ARE TO BE PURCHASED FROM
EATON AS A COMPLETE SYSTEM. THE CONTACT JIM CAVANAUGH AT SYRATEC
EATON FOR QUOTE INFORMATION AND ORDERING OF EQUIPMENT - 315-263-0077.
ALSO INCLUDED IN THE SCOPE IS THE REMOVAL OF EXISTING CONCRETE PADS.
ELECTRICAL LEGEND
LIGHTING LEGEND
MOTOR
1'x4' LUMINAIRE
HARDWIRED EQUIPMENT CONNECTION
P-1A12
HOMERUN TO PANEL P-1A, CIRCUIT #12. FED
FROM 20A -1P BREAKER IS INTENDED UNLESS
NOTED OTHERWISE. RUN GREEN WIRE GROUND
FOR ALL CIRCUITS. PROVIDE ONE GROUND PER
CIRCUIT.
EMERGENCY POWER OFF (EPO)
GROUND ROD ELECTRODE
DUPLEX RECEPTACLE WITH GFCI PROTECTION
DUPLEX RECEPTACLE WITH AFCI PROTECTION
QUAD RECEPTACLE
LINETYPES LEGEND
SPECIAL RECEPTACLE5-30R
PANELBOARD
JUNCTION BOX
B = INSTALLED IN BASEBOARD
TR = INSTALLED IN WOOD TRIM/CASEWORK/WAINSCOTT
SR = SURFACE RACEWAY
WP = WEATHERPROOF
AC = AIR CONDITIONER
X
DUPLEX RECEPTACLE:
DOUBLE DUPLEX RECEPTACLE
MOTOR STARTER
J
2'x4' LUMINAIRE
CEILING MOUNTED LUMINAIRE
EM LIGHTING BATTERY UNIT
COMBO EXIT SIGN/EM LIGHTING BATTERY UNIT
SINGLE FACE, WALL MOUNT EXIT SIGN
DOUBLE FACE, WALL MOUNT EXIT SIGN
SINGLE FACE, CEILING MOUNT EXIT SIGN
DOUBLE FACE, CEILING MOUNT EXIT SIGN
LIGHT SWITCH:
SAFETY SWITCH (NON-FUSED)
SAFETY SWITCH (FUSED)
X 3 = 3-WAY SWITCH
4 = 4-WAY SWITCH
D = DIMMER SWITCH
O = WALL SWITCH OCCUPANCY SENSOR
V = WALL SWITCH VACANCY SENSOR
W = WIRELESS SWITCH
S = WIRELESS SCENE SWITCH
WIRELESS OCCUPANCY SENSOR
WIRELESS DAYLIGHT SENSOR
OS W
DS
1'x2' LUMINAIRE
FIRE ALARM LEGEND
FIRE ALARM CONTROL PANEL
BATTERY CABINET
WATER FLOW SWITCH
MUXPAD
REMOTE ANNUNCIATOR
D = DUCT SMOKE DETECTOR
R = RELAY BASE
BR = BEAM RECEIVER
BT = BEAM TRANSMITTER
SB = SOUNDER BASE
SMOKE DETECTOR:
TAMPER SWITCH
AUDIBLE NOTIFICATION APPLIANCE
FACP
BATT
MUX
FAA
NAC PANELNAC
MANUAL PULL STATIONF
S X
F = FIXED TEMPERATURE
R = RATE OF RISE
R/F = COMBINATION RISE/FIXED TEMPERATURE
HEAT DETECTOR:
H X
CARBON MONOXIDE DETECTORCO
AM
F
XXcd
C
FS
F
S
XXcd
C
TS
ADDRESSABLE MODULE
XXcd = CANDELA
C = CEILING
COMBO A/V NOTIFICATION APPLIANCE:
XXcd = CANDELA
C = CEILING
VISUAL NOTIFICATION APPLIANCE:
SUPPRESSION SYSTEM
ELECTRICAL ABBREVIATIONS
AC AIR CONDITIONER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT INTERRUPTER
AMM ADDRESSABLE MONITOR MODULE
AOM ADDRESSABLE OUTPUT MODULE
ARB AUXILIARY RELAY BOARD
ATS AUTOMATIC TRANSFER SWITCH
B BASEBOARD
BKR BREAKER
C CONDUIT
CD CANDELA
CKT CIRCUIT
CR CONTROL RELAY
EC ELECTRICAL CONTRACTOR
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF STATION
FAA FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FSD FIRE SMOKE DAMPER
GAA GENERATOR ALARM ANNUNCIATOR
GFI GROUND FAULT INTERRUPTER
GND GROUND
HP HORSEPOWER
KW KILOWATT
LC LIGHTING CONTACTOR
LFMC LIQUID TIGHT FLEXIBLE METALLIC CONDUIT
LTG LIGHTING
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUG ONLY
MTS MANUAL TRANSFER SWITCH
NAC NOTIFICATION APPLIANCE CIRCUIT
NIC NOT IN CONTRACT
OE OVERHEAD ELECTRIC
PC PHOTOCELL
PM PLUGMOLD
PP POWER PANEL
PVC POLYVINYL CHLORIDE CONDUIT
RGS RIGID GALVANIZED STEEL CONDUIT
SR SURFACE RACEWAY
ST SHUNT TRIP
TM THERMAL MAGNETIC
TR TRIM/CASEWORK/WAINSCOTT
TSP TWISTED SHIELDED PAIR
TYP TYPICAL
UE UNDERGROUND ELECTRIC
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VA VOLT AMPS
WP WATERPROOF
UNDERGROUND ELECTRICUE
UNDERGROUND LIGHTINGUL
OVERHEAD ELECTRICOE
TO BE PROVIDED
DEMOLITION / TO BE RELOCATED
EXISTING TO REMAIN
UNDERGROUND TELCOUC
MOUNTING HEIGHTS
CARD READER 48" TOP OF BOX
LIGHT SWITCH 48" TOP OF BOX
RECEPTACLE 18" TOP OF BOX
DATA OUTLET 18" TOP OF BOX
TV OUTLET 84" TOP OF BOX
PHONE OUTLET 48" TOP OF BOX
SAFETY SWITCH 60" CENTERLINE OF HANDLE
MOTOR STARTER 60" CENTERLINE OF HANDLE
PANELBOARD 72" TOP OF PANELBOARD
MANUAL PULL STATION 48" OPERABLE HANDLE
NOTIFICATION APPLIANCE 80" BOTTOM OF LENS
DOOR HOLD OPEN COORDINATE IN FIELD
EM BATTERY UNIT 96" BOTTOM OF UNIT
EM REMOTE UNIT 102" BOTTOM OF UNIT
EXIT SIGN 96" BOTTOM OF UNIT
LIGHT POLE WITH LED LUMINAIRES, REFER TO
PLANS FOR NUMBER AND CONFIGURATION OF
HEADS
GENERAL ELECTRICAL NOTES
1.0 ELECTRICAL SCHEMATICS INDICATED ON CONTRACT DOCUMENTS ARE
DIAGRAMMATIC. IT IS NOT THE INTENT TO SHOW EXACT OR MOST EFFICIENT
ROUTING. VERIFY ALL DIMENSIONS AND FIELD CONDITIONS ON SITE. ANY
CONFLICTS BETWEEN CONSTRUCTION DOCUMENTS AND FIELD CONDITIONS SHALL
BE BROUGHT TO CORNELL'S PROJECT MANAGER FOR RESOLUTION BEFORE WORK
PROCEEDS.
2.0 ASSURE PUBLIC AND WORKER SAFETY AT ALL TIMES. PROTECT ADJOINING AREAS
FROM DAMAGE AND DUST. REMOVE ALL DEBRIS FROM SITE AND DISPOSE OF
WASTE MATERIAL IN A SAFE MANNER. KEEP THE PREMISES FREE OF DEBRIS FROM
THE EXECUTION OF WORK. DELIVER A FINAL PRODUCT THAT IS CLEAN AND
OPERABLE.
3.0 FIRE STOP ELECTRICAL PENETRATIONS THROUGH FIRE RATED WALLS AND/OR
FLOORS WITH MATERIAL EQUAL IN RATING TO THE CONSTRUCTION OF THE
MATERIAL PENETRATED.
4.0 WORK SHALL BE COMPLETED AS SPECIFIED AND INDICATED ON CONTRACT
DOCUMENTS. ANY SUGGESTED ALTERNATE MANUFACTURER OR METHOD OF
INSTALLATION SHALL BE SUBMITTED TO PROJECT ENGINEER FOR APPROVAL
PRIOR TO ORDERING ANY MATERIALS OR COMMENCING EXECUTION OF WORK.
5.0 GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLE 250. PROVIDE
EQUIPMENT GROUND CONDUCTOR WITH EACH BRANCH CIRCUIT INDICATED ON
CONTRACT DOCUMENTS. EQUIPMENT GROUND CONDUCTOR SHALL BE ROUTED
WITH ASSOCIATED PHASE CONDUCTORS.
6.0 PROVIDE A NEW TYPED PANELBOARD DIRECTORY FOR EACH PANELBOARD. LABEL
ALL NEW DEVICE FACEPLATES WITH SOURCE AND CIRCUIT NUMBER. PROVIDE
PERMANENT LABEL ON SWITCHING DEVICES INDICATING EQUIPMENT SERVICE AND
INVENTORY NUMBERS. COORDINATE EQUIPMENT INVENTORY NUMBERS WITH
CORNELL UNIVERSITY'S MECHANICAL SHOP, 255-8667.
7.0 CIRCUITS RATED 20-AMP, 120 VOLT SHALL CONTAIN SEPARATE NEUTRAL
CONDUCTORS.
8.0 CONDUCTORS SHALL BE A MINIMUM OF 12AWG, STRANDED COPPER, 600VAC, 90
DEGREE C, TYPE THHN/THWN-2 FOR DRY AREAS AND XHHW/THWN-2 FOR WET
AREAS.
9.0 CONDUITS SHALL BE A MINIMUM OF 3/4 INCHES DIAMETER. CONDUITS SHALL BE
ELECTRICAL METALLIC TUBING (EMT) AND SURFACE MOUNTED UNLESS NOTED
OTHERWISE.
10.0 AIC RATING OF NEW CIRCUIT BREAKERS SHALL MATCH RATING OF RESPECTIVE
PANELBOARD. SIZE AS INDICATED.
11.0 PROVIDE PULL STRING THROUGH NEW CONDUIT AND BOXES. PROVIDE SUPPORT
HANGERS FOR CONDUIT AS NEEDED.
12.0 INSTALL RACEWAY SYSTEMS ENSURING PROPER ACCESS TO EQUIPMENT AND
DEVICES AND WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE AND
REPAIR. RACEWAYS THAT ARE NOT INSTALLED WITH THIS REQUIREMENT IN MIND
SHALL BE RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIES
ARE CORRECTED.
GENERAL ELECTRICAL DEMOLITION NOTES
1.0 ELECTRICAL EQUIPMENT SHOWN DASHED ON DEMOLITION DRAWINGS, INCLUDING
ASSOCIATED ANCHORS, SUPPORTS, STRAPS, BOXES, FITTINGS, AND OTHER
APPURTENANCES NOT SHOWN, SHALL BE DISCONNECTED AND REMOVED.
REMOVE ASSOCIATED BRANCH CIRCUITRY TO SOURCE, UNLESS NOTED
OTHERWISE.
2.0 EXISTING RACEWAYS AND DEVICE BACKBOXES NOT INTERFERRING WITH NEW
WORK SHALL BE REUSED WHERE POSSIBLE.
3.0 PROVIDE JUNCTION BOXES, RACEWAYS, AND WIRING TO MODIFY/EXTEND EXISTING
SYSTEMS AND CIRCUITS FED DOWNSTREAM OF ELECTRICAL EQUIPMENT SHOWN
TO BE DEMOLISHED.
4.0 CUT DEMOLISHED CONDUITS INSTALLED THRU WALLS AND FLOORS FLUSH WITH
THE SURFACE AND PATCH PENETRATIONS (FIRESTOP IF LOCATED ON A FIRE
RATED SURFACE). PATCH AND PAINT SURFACES IN EXPOSED AREAS TO MATCH
SURROUNDING MATERIALS, FINISHES, AND COLORS.
5.0 PROVIDE BLANK COVERPLATES ON UNUSED BACKBOXES REMAINING FROM
DEMOLITION NOT SPECIFIED TO BE INFILLED.
6.0 EXISTING EQUIPMENT SHOWN TO REMAIN SHALL BE PROTECTED DURING
CONSTRUCTION.
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION
UPS SYSTEM DESCRIPTION
THE UPS SYSTEM IS A REDUNDANT SYSTEM WITH TWO MODULES THAT BACK EACH OTHER UP IN CASE OF FAILURE. THE
ENTIRE SYSTEM FROM EATON CONSISTS OF THE FOLLOWING COMPONENTS:
1. TWO (2) EATON UPS 9395HP 275 UPM’S WITH WEB/SNMP, CAN BRIDGE & INDUSTRIAL RELAY CARD
2. FOUR (4) EATON VRLA BATTERY CABINETS –TWO (2) FOR EACH UPS (12.1 MINUTES FULL LOAD RUNTIME)
3. PARALLEL TIE CABINET WITH 2 BREAKER MAINTENANCE BYPASS (AKA SBM)
4. CELLWATCH BATTERY MONITORING WITH THERMAL RUNAWAY AND THERMAL CABINET SENSOR
5. GLOBAL BYPASS PANEL
6. RECTIFIER DISTRIBUTION PANEL WITH SURGE PROTECTION
IT IS THE CONTRACTOR ’S RESPONSIBILITY TO PROVIDE THIS SYSTEM AND EQUIPMENT ALONG WITH THE POWER AND
CONTROL WIRING AND TERMINATIONS BETWEEN ALL THE COMPONENTS EXCEPT THE CELL WATCH WIRING TO THE BATTERY
CABINETS WHICH IS BY EATON. THE CONTRACTOR PROVIDES ALL CONDUIT INSTALLATIONS.
IN ADDITION TO THE UPS’S PROVIDING REDUNDANCY TO ONE ANOTHER, THERE ARE TWO BYPASS OPTIONS FOR THE SYSTEM.
THE BYPASS IN THE SBM ALLOWS THE BYPASS OF THE UPS AND THE GLOBAL BYPASS ALLOWS THE UPS’S, SBM AND ATS’S TO
BE BYPASSED ALL AT ONE TIME.
THE SBM BYPASS CONFIGURATION IS AN INTERLOCK SCHEME FOR CLOSED TRANSITION (MAKE BEFORE BREAK) BETWEEN
THE MIS AND MBP BREAKERS WHICH CONSISTS OF A TWO-KEY INTERLOCK WITH A SOLENOID RELEASE AND INDICATOR LAMP.
REFER TO THE ONE-LINE DIAGRAMS FOR INTERLOCK DESIGNATIONS.
THE GLOBAL BYPASS CONFIGURATION IS ALSO A TWO KEY INTERLOCK SCHEME FOR CLOSED TRANSITION (MAKE BEFORE
BREAK) BETWEEN THE GBB AND SIS BREAKERS WITH SOLENOID KEY RELEASE AND INDICATOR LAMP. IN ORDER FOR A
TRANSFER TO OCCUR BETWEEN GBB AND SIS, THE ATS-3 NORMALLY OPEN CONTACT MUST CLOSE WHEN THE ATS-3 IS IN
EMERGENCY FEED POSITION, AND THE MBP BREAKER IN THE SBM TIE CABINET IS CLOSED (VIA THE N.O. AUXILIARY CONTACT).
REFER TO THE ONE-LINE DIAGRAMS FOR INTERLOCK DESIGNATIONS.
EXISTING
UPS
EXISTING
UPS
EXISTING
SBM
EXISTING
BATTERIES
SUB
SS-B1
ATS-3
ATS-2
ATS-5
DP-MG1
DP-MG2
EXISTING
OVERHEAD
J-BOX #1
EXISTING
OVERHEAD
J-BOX #2
SUB
SS-B2
LINE OF BEAM
OVERHEAD
TO GENERATOR ROOM
3" EMT
4" EMT
1
2
D
E
F
C
F.8
G
4321
SUB
SS-B1
SUB
SS-B2
NEW
UPS #1
NEW UPS BATTERIES
(STORE OUTSIDE
ELECTRICAL ROOM)NEW
UPS #2NEW
SBM
NEW GLOBAL
BYPASS PANEL
LINE OF BEAM
OVERHEAD
ATS-3
ATS-2
ATS-5
EXISTING
OVERHEAD
J-BOX #1
1
2
3
4
5
6
7
NEW
RECTIFIER
PANEL
D
E
F
C
F.8
G
4321
DP-MG1
DP-MG2
8
8
2
NEW CELL WATCH
COTROL/IBMU
ENCLOSURES
ELP-P
9 CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
E-101
11874770
EXISTING AND
PHASE 1 PLANS
E. REICHARD
ETR
2051
April 8, 2020
0 4 8 16
SCALE: 1/8"=1'-0"
SCALE:1/8" = 1'-0"1 PENTHOUSE EXISTING FLOOR PLAN
SCALE:1/8" = 1'-0"2 PENTHOUSE PHASE 1 FLOOR PLAN
#
#E-101 KEYED DEMOLITION NOTES
1 REMOVE EXISTING CONCRETE PADS. WET CONCRETE AND TENT AREA TO MINIMIZE
DUST AND KEEP EXISTING EQUIPMENT CLEAN. SMOOTH FLOOR DOWN TO MATCH
EXISTING FLOOR. WIPE DOWN AND CLEAN EQUIPMENT FROM ANY DUST CREATED
FROM THE CONCRETE REMOVAL.
2 REMOVE EXISTING CONCRETE PAD FROM NORTH EDGE TO EDGE OF EXISTING SBM
TO ALLOW FOR PLACEMENT OF STRUCTURAL BEAMS ACROSS THE FLOOR.
E-101 KEYED CONSTRUCTION NOTES
1 INSTALL BEAMS ON FLOOR IN LOCATION INDICATED. REFER TO STRUCTURAL
DRAWING FOR BEAM AND INSTALLATION DETAILS.
2 PROVIDE EATON 600 AMP RECTIFIER DISTRIBUTION PANEL. PANEL TO BE
INSTALLED IN FRONT OF HORIZONTAL BEAM TO ALLOW FOR CONDUIT
INSTALLATION IN/OUT OF TOP OF ENCLOSURE. INSTALL ON FLOOR MOUNTED
STEEL STRUT. PROVIDE CONDUIT FROM PANEL TO ATS-5 LOCATION. CONDUIT AND
CONDUCTORS TO BE TERMINATED IN NEXT PHASE. REFER TO ONE-LINE DIAGRAM
FOR CONDUIT AND CONDUCTOR SIZES.
3 PROVIDE TWO (2) EATON 9395HP 275KVA/275KW UPS MODULES FOR PARALLEL
REDUNDANT SYSTEM. INSTALL MODULES DIRECTLY ON FINISHED FLOOR. PROVIDE
CONDUIT AND CONDUCTORS FOR UPS RECTIFIER AND BYPASS FEEDS FROM
RECTIFIER DISTRIBUTION PANEL TO BOTH UPS MODULES. REFER TO ONE-LINE
DIAGRAM FOR CONDUIT AND CONDUCTOR SIZES.
4 PROVIDE EATON SBM PARALLEL TIE CABINET WITH TWO BREAKER MAINTENANCE
BYPASS IN LOCATION INDICATED. CABINET TO BE INSTALLED IN FRONT OF
HORIZONTAL BEAM TO ALLOW FOR CONDUIT INSTALLATION IN/OUT OF TOP OF
CABINET. PROVIDE CONDUIT AND CONDUCTORS FROM UPS MODULES TO THE SBM
CABINET. REFER TO ONE-LINE DIAGRAM FOR CONDUIT AND CONDUCTOR SIZES.
5 PROVIDE NEW EATON 1200A GLOBAL BYPASS PANELBOARD. PANEL TO BE
INSTALLED IN FRONT OF HORIZONTAL BEAM TO ALLOW FOR CONDUIT
INSTALLATION IN/OUT OF TOP OF ENCLOSURE. PROVIDE CONDUIT AND
CONDUCTORS FROM THE SBM CABINET TO THE GLOBAL BYPASS PANEL. REFER TO
ONE-LINE DIAGRAM FOR CONDUIT AND CONDUCTOR SIZES.
6 PROVIDE CONDUIT FROM GLOBAL BYPASS PANELBOARD TO ABOVE EXISTING SBM
BYPASS CABINET. CONDUIT AND CONDUCTORS TO BE TERMINATED AT PHASE 3.
REFER TO ONE-LINE DIAGRAM FOR CONDUIT AND CONDUCTOR SIZES.
7 PROVIDE UPS VRLA BATTERIES FOR UPS MODULES. STORE OUTSIDE OF
ELECTRICAL ROOM DURING CONSTRUCTION AND INSTALL BATTERIES IN PHASES
IDENTIFIED.
8 PROVIDE TWO 3” EMT CONDUITS WITH PULL STRING FROM GLOBAL BYPASS
PANELBOARD TO EACH PANEL DP-MG1 AND PANEL DP-MG2 FOR FUTURE FEEDS.
PROVIDE TWO NEW SPECTRA RMS SKHA36AT0800 BREAKER WITH 500A PLUG,
PADLOCK AND HARDWARE MOUNTING KITS. TURN BREAKERS OVER TO THE
FACILITY FOR FUTURE INSTALLATION.
9 PROVIDE CELLWATCH CONTROL PANEL AND IBMU IN LOCATION INDICATED. MOUNT
ON STRUT AT 5’ AFF. PROVIDE NEMA 5-20R RECEPTACLE ON WALL FOR
CELLWATCH/IBMU POWER. PROVIDE 2-#12 & 1#12 THHN GND IN ¾” EMT FROM PANEL
ELP-P 20A SPARE BREAKER IN CIRCUIT SPACE #4 TO RECEPTACLE. PROVIDE 500VA
UPS WITH MINIMUM 15 MINUTE RUNTIME ON WALL NEXT TO RECEPTACLE AND PLUG
INTO RECEPTACLE. PROVIDE POWER TO CONTROL PANEL/IBMU FROM 500VA UPS
WITH 12-2 SO TYPE CORD AND PROVIDE NEMA 5-15P PLUG.
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION
SUB
SS-B1
SUB
SS-B2
EXISTING
OVERHEAD
J-BOX #2
NEW
UPS #1
NEW
UPS #2
UPS #1
3" EMT
LINE OF BEAM
OVERHEAD
NEW
12"X12"X6"
OVERHEAD
J-BOX #3
NEW SBM
NEW
GLOBAL
WRAP
PANEL
ATS-3
ATS-2
ATS-5
EXISTING
OVERHEAD
J-BOX #1
1
2
3 4
5
6
7
8
9
10
11
5
7
5
4
D
E
F
C
F.8
G
4321 5 6
NEW 24"x24"
PULL BOX
PANEL DS-EG
SECTION 2
GENERATOR ROOM
PANEL DS-EG
SECTION 1
12"x12"
WIREWAY
12
13
14
15
16
3
6
7
11
12
12
12
14
NEW CELL
WATCH &
IBMU
#
0 4 8 16
SCALE: 1/8"=1'-0"CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
E-102
11874770
PHASE 2 PLAN
E. REICHARD
ETR
2051
APRIL 8, 2020
SCALE:1/8" = 1'-0"1 PENTHOUSE PHASE 2 FLOOR PLAN
E-102 KEYED CONSTRUCTION NOTES
1 OPEN UPS #2 CIRCUIT BREAKER IN UPS MODULE.
2 OPEN UPS #2 BATTERY CIRCUIT BREAKER TO DISCONNECT BATTERY POWER.
3 OPEN 500A BREAKER IN PANEL DS-EG IN GENERATOR ROOM FOR EMERGENCY
FEED TO ATS #5. LOCK BREAKER IN OPEN POSITION.
4 OPEN 500A FUSED SWITCH IN SWITCHBOARD SS-B2 FOR NORMAL FEED TO ATS #5.
LOCK SWITCH IN OPEN POSITION.
5 DISCONNECT CONDUCTORS FROM LINE SIDE OF UPS #2. REMOVE CONDUIT AND
CONDUCTORS BACK ATS-5.
6 START GENERATOR AND SWITCH ATS-3 TO EMERGENCY POWER. OPEN 500A
SWITCH IN SWITCHBOARD SS-B2 FOR NORMAL FEED TO ATS-3.
7 OPEN 4000A MAIN SWITCH IN SS-B2. TIE SWITCH TO REMAIN OPEN. WHILE BUSS IS
DE-ENERGIZED, REMOVE AND DISPOSE OF EXISTING 2 SETS OF 250 KCMIL
CONDUCTORS FROM ATS-5 BACK TO SS-B2. DISCONNECT REMAINING POWER AND
CONTROL CONDUCTORS AND SAVE FOR REUSE. REMOVE AND DISPOSE OF ATS-5
AND REPLACE WITH A 600 AMP CLOSED TRANSITION ATS (NEW ATS-5). RECONNECT
POWER AND CONTROL CONDUCTORS SAVED FROM REMOVAL.
8 PROVIDE NEW CONDUCTORS FROM SWITCH IN SS-B2 TO ATS-5. REFER TO
ONE-LINE DIAGRAM FOR CONDUCTOR SIZES. REUSE EXISTING 3” CONDUIT.
REPLACE THE 500 AMP FUSES WITH 600 AMP FUSES (TYPE KRP-C). SWITCH TO
REMAIN LOCKED OPEN.
9 MAKE FINAL CONDUIT AND CONDUCTOR CONNECTIONS FROM RECTIFIER POWER
PANEL TO NEW ATS-5.
10 CLOSE MAIN SWITCH AND RE-ENERGIZE SS-B2.
11 CLOSE 500 AMP SWITCH FOR ATS-3. TRANSFER ATS-3 BACK TO NORMAL POWER.
12 PROVIDE CONDUIT AND CONDUCTORS FROM GLOBAL BYPASS PANEL TO PANEL
DS-EG FOR NEW BYPASS FEED. INSTALL CONDUIT AND CONDUCTOR INTO
GENERATOR ROOM PRIOR TO SHUTDOWN. REFER TO ONE-LINE DIAGRAM FOR
CONDUIT AND CONDUCTOR SIZES. FINAL CONNECTIONS AND TERMINATIONS TO BE
MADE DURING EMERGENCY POWER SHUTDOWN.
13 OPEN GENERATOR BREAKER. DISCONNECT AND REMOVE THE 2 SETS OF EXISTING
EMERGENCY FEEDERS BETWEEN ATS-5 AND THE 500 AMP BREAKER IN PANEL
DS-EG. REMOVE 500 AMP BREAKER AND SAVE FOR BYPASS FEEDER CONNECTION.
SHUNT WIRING CIRCUIT TO REMAIN FOR USE WITH NEW BREAKER. PROVIDE 600
AMP SPECTRA RMS BREAKER WITH SHUNT TRIP IN PLACE OF 500 AMP BREAKER.
CONNECT SHUNT WIRING TO NEW BREAKER SHUNT LEADS. PROVIDE NEW FEEDER
FROM 600 AMP BREAKER TO ATS-5. PROVIDE 12”X12”X6’ WIREWAY BETWEEN PANEL
SECTIONS OF DS-EG. REINSTALL 500 AMP BREAKER WITH LUGS FACING WIREWAY.
EXTEND SHUNT CIRCUITRY TO THE 500A BREAKER SHUNT LEADS AS NECESSARY.
FINALIZE FEED FROM GLOBAL BYPASS PANEL AND TERMINATE TO THE 500 AMP
BREAKER. DURING THIS TIME THE BUILDING WILL BE WITHOUT GENERATOR POWER
AND CANNOT HAVE OCCUPANTS. COORDINATE THIS EMERGENCY POWER
SHUTDOWN WITH THE FACILITY.
14 CLOSE GENERATOR BREAKER AND 600 AMP BREAKER IN PANEL DS-EG. CLOSE 600
AMP FUSED SWITCH FOR NORMAL POWER TO ATS-5.
15 REMOVE AND DISPOSE OF BATTERIES #3 AND #4 FOR EXISTING UPS #2.
16 INSTALL NEW BATTERIES #3 AND #4 FOR NEW UPS MODULE #2. PROVIDE CONDUIT
AND CONDUCTORS FROM BATTERY CABINET TO UPS MODULE. CLOSE RECTIFIER
PANEL MAIN BREAKER AND 600A BREAKER FEEDING UPS #2 AND PERFORM LOAD
TEST PRIOR TO TRANSFERRING BUILDING LOAD TO UPS. BREAKERS FOR UPS #1 TO
REMAIN OPEN UNTIL LOAD TEST IS TO BE PERFORMED.
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION
SUB
SS-B1
SUB
SS-B2
LINE OF BEAM
OVERHEAD
NEW
UPS #1
NEW
UPS #2
3" EMT
ATS-3
ATS-5
EXISTING
OVERHEAD
J-BOX #1
2
3
4
5 6
7 8
9
10
11
1
D
E
F
C
F.8
G
4321 5 6
12
6
8
11
11
NEW GLOBAL
BYPASS PANEL
NEW SBM
NEW UPS
NEW BATTERY
CABINETS
NEW
ATS-5
ATS-3
NEW RECTIFIER
DISTRIBUTION
PANEL
NEW BEAMS
ON FLOOR CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
E-103
11874770
PHASE 3 PLAN
AND
PERSPECTIVE
E. REICHARD
EWK
2051
APRIL 8, 2020
0 4 8 16
SCALE: 1/8"=1'-0"
SCALE:1/8" = 1'-0"1 PENTHOUSE PHASE 3 FLOOR PLAN
SCALE:2 PERSPECTIVE VIEW FINAL
E-103 KEYED CONSTRUCTION NOTES
1 EXERCISE BREAKERS MBP/MIS MULTIPLE TIMES PRIOR TO MAKING THE CUT OVER
TO NEW FEED. OPEN MBP CIRCUIT BREAKER IN EXISITING SBM CABINET.
2 OPEN THE MAIN SWITCH FOR SS-B1. OPEN THE 800 AMP SWITCH AT SS-B1 TO THE
ALTERNATE BYPASS FEED TO MBP. REMOVE CONDUIT AND CONDUCTORS BACK TO
SWITCH AND DISPOSE OF. CLOSE MAIN SWITCH TO RE-ENERGIZE SS-B1.
3 FINALIZE THE INSTALLATION OF THE CONDUIT AND CONDUCTORS FROM THE
GLOBAL BYPASS PANEL TO THE EXISTING SBM. CONNECT FEED TO THE MBP
CIRCUIT BREAKER IN THE EXISTING SBM CABINET.
4 CLOSE MOB2 CIRCUIT BREAKER IN NEW SBM CABINET. CLOSE RECTIFIER PANEL
MAIN BREAKER AND BREAKERS FEEDING UPS #2.
5 CLOSE MBP CIRCUIT BREAKER IN EXISITING SBM CABINET, OPEN MIS BREAKER TO
TRANSFER LOAD TO NEW UPS #2.
6 OPEN CBS BREAKER IN THE EXISTING SBM CABINET. OPEN FBP AND CBP
BREAKERS. START GENERATOR AND TRANSFER ATS-3 AND ATS-5 TO EMERGENCY
POWER. OPEN MAIN SWITCH TO SS-B2. OPEN 800 AMP SWITCH, REMOVE AND
DISPOSE OF STATIC BYPASS FEED BACK TO SS-B1. CLOSE MAIN SWITCH TO SS-B2
AND LABEL SWITCH “SPARE”. TRANSFER ATS-3 AND ATS-5 BACK TO NORMAL
POWER.
7 OPEN NORMAL FEED TO ATS-3 AT SS-B2 AND EMERGENCY FEED AT DS-EG. OPEN
UPS #1 BATTERY AND OUTPUT BREAKER. DISCONNECT THE NEUTRAL CONDUCTOR
FROM BOTH FEEDS IN THE ATS AND CAP.
8 DISCONNECT AND REMOVE EXISTING UPS #1 CONDUIT AND CONDUCTORS FROM
UPS #1 TO EXISTING SBM. REMOVE CONDUIT AND CONDUCTORS FROM UPS #1 TO
ATS-3.
9 PROVIDE CONDUIT AND CONDUCTORS FROM ATS-3 TO NEW 500 AMP SBM BYPASS
BREAKER. REFER TO ONELINE DIAGRAM FOR CONDUIT AND CONDUCTOR SIZES.
10 DISCONNECT AND REMOVE EXISTING UPS #2 CONDUIT AND CONDUCTORS FROM
UPS #2 TO EXISTING SBM.
11 REMOVE AND DISPOSE OF UPS #1 AND ITS BATTERIES. REMOVE AND DISPOSE OF
UPS #2. DISCONNECT AND REMOVE 3/4" COMMUNICATION CONDUITS BETWEEN
EXISTING UPS #1 AND UPS #2. DISCONNECT AND REMOVE THE COMMUNICATION
CONDUCTORS FROM ATS-5 TO EXISTING UPS/SBM. REMOVE CONDUIT BACK TO
ATS-5. REFER TO CONTROL RISER FOR THE NEW CONDUIT AND CONTROL WIRING
FROM ATS-5 TO THE NEW UPS’S AND SBM.
12 INSTALL NEW BATTERIES FOR UPS #1. PROVIDE CONDUIT AND CONDUCTORS FROM
BATTERIES TO UPS MODULE. CLOSE RECTIFIER PANEL BREAKERS FEEDING UPS #1.
TRANSFER ATS-3 AND ATS-5 TO EMERGENCY POWER, SWITCH SBM INTO BYPASS.
OPEN BREAKERS IN RECTIFIER PANEL FEEDING UPS #2. PERFORM LOAD TESTING
ON UPS #1. ONCE COMPLETE, CLOSE BREAKERS IN RECTIFIER PANEL FEEDING UPS
#2, CLOSE MOB1 BREAKER. SWITCH BACK TO UPS POWER AND TRANSFER ATS-3
AND ATS-5 TO NORMAL POWER.
#
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION
EQUIPMENT PATH OF TRAVEL
GENERATOR ROOM
D
E
F
C
F.8
G
4321 5 6
B
7
REMOVE AND REINSTALL
CMU BELOW DOUBLE DOOR
TO BRING EQUIPMENT IN AND
OUT OF ELECTRICAL ROOM.CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
E-104
11874770
PENTHOUSE
PATH OF TRAVEL
E. REICHARD
ETR
2051
APRIL 8, 2020
SCALE:1/8" = 1'-0"1 PENTHOUSE FLOOR PLAN PATH OF TRAVEL
0 4 8 16
SCALE: 1/8"=1'-0"
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION
E N
L
BATTERY BATTERY
TO MV SWITCH
600AF800AS 400AF600AS 500AF800AS 400AF600AS 400AF600AS 500AF1200AS 400AF600AS 500AF800AS 800AF1600AS
4000AF4000AS
800AF
500AT
800AF
500AT
800AF
600AT
E N
L
800A/3P800A/3P
800A/3P 800A/3P800A/3P
800AF1600AS 400AF600AS 500AF800AS 400AF600AS 400AF600AS 500AF800AS ---AF600AS 500AF1200AS
4000AF4000AS 3000AF3000AS
2500-KVA
PRI: 13.2-KV
SEC: 480Y/277V
2500-KVA
PRI: 13.2-KV
SEC: 480Y/277V
GUNIT 800-KW
800AF
400AT
800AF
400AT
800AF
400AT
SPARE
800AF
400AT
800AF
400AT
800AF
400AT
SPARE
DP-MG1 SECT 1
800A, 480/277V, 3Ø, 4W
DP-MG1 SECT 2
800A, 480/277V, 3Ø, 4W
DP-MG2 SECT 2
800A, 480/277V, 3Ø, 4W
DP-MG2 SECT 1
800A, 480/277V, 3Ø, 4W
SPACESPACESPACESPACESPACESPACESPACESPACESPACESPACESPACESPACE
DP-CC62
400A, 480/277V, 3Ø, 4W
DP-CC72
400A, 480/277V, 3Ø, 4W
DP-CC61
400A, 480/277V, 3Ø, 4W
DP-CC71
400A, 480/277V, 3Ø, 4W
SPARE
SS-B2 4000A
480/277V, 3Ø, 4W
SS-B1 4000A
480/277V, 3Ø, 4W
DS-EG 1200A
480/277V, 3Ø, 4W
ATS-3
ATS-5
UPS MODULE #1
300KVA
#1 #2
EXISTING 800A SBM CABINET
SPACE
BATTERY BATTERY
UPS MODULE #2
300KVA
#3 #4
MBP
CBS
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
J. BOX #1
J. BOX #2
J. BOX #1
J. BOX #1
UPS #2
BREAKER
UPS #1
BREAKER
1
2
1
3
4
5
(3) SETS 4-250 KCMIL
(3) SETS 4-250 KCMIL
(3) SETS 4-250 KCMIL(2) SETS 4-250 KCMIL
(2) SETS 4-250 KCMIL
4
CB-1 CB-1
500A/3P
UPS MODULE #1
275KVA
UPS MODULE #2
275KVA
NEW 500A SBM CABINET
500A/3P 500A/3P
(2) SETS OF 3-250KCMIL
& 1-#2 GND IN 3" EMT
600A/3P
600A/3P
500A/3P
500A/3P 500A/3P
GLOBAL BYPASS
DISTRIBTION PANEL
500A/3P500A/3P
800AF
400AT
1000AF
1200AT
500A/3P 500A/3P600A/3P
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
RECTIFIER DISTRIBUTION PANEL
480V, 3Ø, 3W 65KAIC
480V, 3Ø,
3W, 65KAIC
2
CD
DC
BA
AB
SKRU A
SKRU C
500A/3P
480V, 3Ø, 3W 65KAIC
MBP (NO)
MIS (NC)
MOB 1 MOB 2MOB 1LB1
SIS (NC)
GBB (NO)
60A/3P
SPD 120KA CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
E-301
11874770
PHASE 1
ONE-LINE
DIAGRAM
E. REICHARD
ETR
2051
April 8, 2020
SCALE: NO SCALE
1 ONE-LINE DIAGRAM PHASE 1
E-301 KEYED PHASE 1 NOTES
1 PROVIDE EATON 600 AMP RECTIFIER DISTRIBUTION PANEL. PROVIDE CONDUIT
FROM PANEL TO ATS-5 LOCATION. CONDUIT AND CONDUCTORS TO BE TERMINATED
IN NEXT PHASE.
2 PROVIDE TWO (2) EATON 9395HP 275KVA/275KW UPS MODULES FOR PARALLEL
REDUNDANT SYSTEM. PROVIDE CONDUIT AND CONDUCTORS FOR UPS RECTIFIER
AND BYPASS FEEDS FROM RECTIFIER DISTRIBUTION PANEL TO BOTH UPS
MODULES.
3 PROVIDE EATON SBM PARALLEL TIE CABINET WITH TWO BREAKER MAINTENANCE
BYPASS. PROVIDE CONDUIT AND CONDUCTORS FROM UPS MODULES TO THE SBM
CABINET.
4 PROVIDE NEW EATON 1200A GLOBAL BYPASS PANELBOARD. PROVIDE CONDUIT
AND CONDUCTORS FROM THE SBM CABINET TO THE GLOBAL BYPASS PANEL.
5 PROVIDE CONDUIT FROM GLOBAL BYPASS PANELBOARD TO ABOVE EXISTING SBM
BYPASS CABINET. CONDUIT AND CONDUCTORS TO BE TERMINATED AT PHASE 3.
#
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION
E N
L
BATTERY BATTERY
TO MV SWITCH
600AF800AS 400AF600AS 500AF800AS 400AF600AS 400AF600AS 400AF600AS 500AF800AS 800AF1600AS
4000AF4000AS
E N
L
800A/3P800A/3P
800A/3P 800A/3P800A/3P
800AF1600AS 400AF600AS 500AF800AS 400AF600AS 400AF600AS 500AF800AS ---AF600AS 500AF1200AS
4000AF4000AS 3000AF3000AS
2500-KVA
PRI: 13.2-KV
SEC: 480Y/277V
2500-KVA
PRI: 13.2-KV
SEC: 480Y/277V
800AF
400AT
800AF
400AT
800AF
400AT
SPARE
800AF
400AT
800AF
400AT
800AF
400AT
SPARE
DP-MG1 SECT 1
800A, 480/277V, 3Ø, 4W
DP-MG1 SECT 2
800A, 480/277V, 3Ø, 4W
DP-MG2 SECT 2
800A, 480/277V, 3Ø, 4W
DP-MG2 SECT 1
800A, 480/277V, 3Ø, 4W
SPACESPACESPACESPACESPACESPACESPACESPACESPACESPACESPACESPACE
DP-CC62
400A, 480/277V, 3Ø, 4W
DP-CC72
400A, 480/277V, 3Ø, 4W
DP-CC61
400A, 480/277V, 3Ø, 4W
DP-CC71
400A, 480/277V, 3Ø, 4W
SPARE
SS-B2 4000A
480/277V, 3Ø, 4W
SS-B1 4000A
480/277V, 3Ø, 4W
ATS-3
NEW
ATS-5
UPS MODULE #1
300KVA
#1 #2
EXISTING 800A SBM CABINET
SPACE
UPS MODULE #2
300KVA
#3 #4
MBP
CBSMIS
FBP CBP
EXISTING J-BOX #1
BATTERY BATTERY
1
2
3
4
5
6
7
8
9
10
11
(3) SETS 4-250 KCMIL
(3) SETS 4-250 KCMIL
12
CB-1
BATTERY BATTERY
CB-1
500A/3P
500A/3P
UPS MODULE #1
275KVA
UPS MODULE #2
275KVA
NEW 500A SBM CABINET
500A/3P 500A/3P
600A/3P 600A/3P
500A/3P
500A/3P 500A/3P600A/3P
500A/3P 500A/3P
GLOBAL BYPASS
DISTRIBTION PANEL
500A/3P500A/3P
800AF
400AT
800AF
500AT
800AF
500AT
800AF
600AT
800AF
600AT
GUNIT 800-KW
DS-EG 1200A
480/277V, 3Ø, 4W
1000AF
1200AT
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-250KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250
KCMIL & 1-#2 GND IN
3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#350 KCMIL &
1-#1 GND IN EXISTING 3" EMT
(2) SETS OF 3-#350 KCMIL &
1-#1 GND IN EXISTING 3" EMT
(3) SETS 4-250 KCMIL
EXISTING J-BOX #1
#3 #4
13
14
15
16
(2) SETS OF 2-#500
KCMIL & 1-#2 GND IN
3" EMT
14
14
13
6
6
12
RECITIFIER DISTRIBUTION PANEL
600AF1200AS
8
CD
DC
BA
AB
SKRU ASKRU C
MBP (NO)
MIS (NC)
MOB 2MOB 1LB1SIS (NC)
GBB (NO)CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
E-302
11874770
PHASE 2
ONE-LINE
DIAGRAM
E. REICHARD
ETR
2051
APRIL 8, 2020
SCALE: NO SCALE
1 ONE-LINE DIAGRAM PHASE 2
#E-302 KEYED PHASE 2 NOTES
1 OPEN UPS #2 CIRCUIT BREAKER IN UPS MODULE.
2 OPEN UPS #2 BATTERY CIRCUIT BREAKER TO DISCONNECT BATTERY POWER.
3 OPEN 500A BREAKER IN PANEL DS-EG IN GENERATOR ROOM FOR EMERGENCY
FEED TO ATS #5. LOCK BREAKER IN OPEN POSITION.
4 OPEN 500A FUSED SWITCH IN SWITCHBOARD SS-B2 FOR NORMAL FEED TO ATS #5.
LOCK SWITCH IN OPEN POSITION.
5 DISCONNECT CONDUCTORS FROM LINE AND LOAD SIDE OF UPS #2. REMOVE
CONDUIT AND CONDUCTORS BACK ATS-5.
6 START GENERATOR AND SWITCH ATS-3 TO EMERGENCY POWER. OPEN 500A
SWITCH IN SWITCHBOARD SS-B2 FOR NORMAL FEED TO ATS-3.
7 OPEN 4000A MAIN SWITCH IN SS-B2. TIE SWITCH TO REMAIN OPEN. WHILE BUSS IS
DE-ENERGIZED, REMOVE AND DISPOSE OF EXISTING 2 SETS OF 250 KCMIL
CONDUCTORS FROM ATS-5 BACK TO SS-B2. REMOVE AND DISPOSE OF ATS-5 AND
REPLACE WITH A 600 AMP CLOSED TRANSITION ATS (NEW ATS-5).
8 PROVIDE NEW CONDUCTORS FROM SWITCH IN SS-B2 TO ATS-5. REUSE EXISTING 3”
CONDUIT. REPLACE THE 500 AMP FUSES WITH 600 AMP FUSES (TYPE KRP-C).
RETURN OLD FUSES TO CORNELL. SWITCH TO REMAIN LOCKED OPEN.
9 MAKE FINAL CONDUIT AND CONDUCTOR CONNECTIONS FROM RECITFIER POWER
PANEL TO NEW ATS-5.
10 CLOSE MAIN SWITCH AND RE-ENERGIZE SS-B2.
11 CLOSE 500 AMP SWITCH FOR ATS-3. TRANSFER ATS-3 BACK TO NORMAL POWER.
12 PROVIDE CONDUIT AND CONDUCTORS FROM GLOBAL BYPASS PANEL TO PANEL
DS-EG FOR NEW BYPASS FEED. INSTALL CONDUIT AND CONDUCTOR INTO
GENERATOR ROOM PRIOR TO SHUTDOWN. FINAL CONNECTIONS AND
TERMINATIONS TO BE MADE DURING EMERGENCY POWER SHUTDOWN.
13 OPEN GENERATOR BREAKER. DISCONNECT AND REMOVE THE 2 SETS OF EXISTING
EMERGENCY FEEDERS BETWEEN ATS-5 AND THE 500 AMP BREAKER IN PANEL
DS-EG. REMOVE 500 AMP BREAKER AND SAVE FOR BYPASS FEEDER CONNECTION.
SHUNT WIRING CIRCUIT TO REMAIN FOR USE WITH NEW BREAKER. PROVIDE 600
AMP SPECTRA RMS BREAKER WITH SHUNT TRIP IN PLACE OF 500 AMP BREAKER.
CONNECT SHUNT WIRING TO NEW BREAKER SHUNT LEADS. PROVIDE NEW FEEDER
FROM 600 AMP BREAKER TO ATS-5. PROVIDE 12”X12”X6’ WIREWAY BETWEEN PANEL
SECTIONS OF DS-EG. REINSTALL 500 AMP BREAKER WITH LUGS FACING WIREWAY.
EXTEND SHUNT CIRCUITRY TO THE 500A BREAKER SHUNT LEADS AS NECESSARY.
FINALIZE FEED FROM GLOBAL BYPASS PANEL AND TERMINATE TO THE 500 AMP
BREAKER. DURING THIS TIME THE BUILDING WILL BE WITHOUT GENERATOR POWER
AND CANNOT HAVE OCCUPANTS. COORDINATE THIS EMERGENCY POWER
SHUTDOWN WITH THE FACILITY.
14 CLOSE GENERATOR BREAKER AND 600 AMP BREAKER IN PANEL DS-EG. CLOSE 600
AMP FUSED SWITCH FOR NORMAL POWER TO ATS-5.
15 REMOVE AND DISPOSE OF BATTERIES #3 AND #4 FOR EXISTING UPS #2.
16 INSTALL NEW BATTERIES #3 AND #4 FOR NEW UPS MODULE #2. PROVIDE CONDUIT
AND CONDUCTORS FROM BATTERY CABINET TO UPS MODULE. CLOSE RECTIFIER
PANEL MAIN BREAKER AND 600A BREAKER FEEDING UPS #2 AND PERFORM LOAD
TEST PRIOR TO TRANSFERRING BUILDING LOAD TO UPS. BREAKERS FOR UPS #1 TO
REMAIN OPEN UNTIL LOAD TEST IS TO BE PERFORMED.
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION
E N
L
BATTERY BATTERY
TO MV SWITCH
600AF800AS 400AF600AS 500AF800AS 400AF600AS 400AF600AS 500AF1200AS 400AF600AS 500AF800AS 800AF1600AS
4000AF4000AS
E N
L
800AF1600AS 400AF600AS 500AF800AS 400AF600AS 400AF600AS 500AF800AS ---AF600AS 500AF1200AS
4000AF4000AS 3000AF3000AS
2500-KVA
PRI: 13.2-KV
SEC: 480Y/277V
2500-KVA
PRI: 13.2-KV
SEC: 480Y/277V
800AF
400AT
800AF
400AT
800AF
400AT
SPARE
800AF
400AT
800AF
400AT
800AF
400AT
SPARE
DP-MG1 SECT 1
800A, 480/277V, 3Ø, 4W
DP-MG1 SECT 2
800A, 480/277V, 3Ø, 4W
DP-MG2 SECT 2
800A, 480/277V, 3Ø, 4W
DP-MG2 SECT 1
800A, 480/277V, 3Ø, 4W
SPACESPACESPACESPACESPACESPACESPACESPACESPACESPACESPACESPACE
DP-CC62
400A, 480/277V, 3Ø, 4W
DP-CC72
400A, 480/277V, 3Ø, 4W
DP-CC61
400A, 480/277V, 3Ø, 4W
DP-CC71
400A, 480/277V, 3Ø, 4W
SPARE
SS-B2 4000A
480/277V, 3Ø, 4W
SS-B1 4000A
480/277V, 3Ø, 4W
ATS-3
UPS MODULE #1
300KVA
#1 #2
SPACE
EXISTING J-BOX #1
ATS-5
(2) SETS OF 3-250KCMIL
& 1-#2 GND IN 3" EMT
(3) SETS 4-250 KCMIL
(2) SETS OF 3-350KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-350KCMIL &
1-#1 GND IN 3" EMT
(3) SETS 4-250 KCMIL
1
2
2
3
4
5 6
7
7
7
7
8
9
10
11
12
BATTERY BATTERY
CB-1
BATTERY BATTERY
CB-1
500A/3P
UPS MODULE #1
300KVA
UPS MODULE #2
300KVA
NEW 500A SBM CABINET
500A/3P 500A/3P
600A/3P 600A/3P
500A/3P
500A/3P 500A/3P600A/3P
800A/3P800A/3P
800A/3P 800A/3P800A/3P
MBP
CBSMIS
FBP CBP
8
12
500A/3P 500A/3P
GLOBAL BYPASS
DISTRIBTION PANEL
500A/3P500A/3P
800AF
400AT
800AF
500AT
800AF
500AT
800AF
600AT
800AF
600AT
GUNIT 800-KW
DS-EG 1200A
480/277V, 3Ø, 4W
1000AF
1200AT
#1 #2 #3 #4
(2) SETS OF 3-250KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-250KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-500KCMIL
& 1-#1/0 GND IN 4" EMT
(3) SETS 4-250 KCMIL
(2) SETS OF 3-250KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#350 KCMIL &
1-#1 GND IN EXISTING 3" EMT
(3) SETS 4-250 KCMIL
RECITIFIER DISTRIBUTION PANEL
(2) SETS OF 2-#500
KCMIL & 1-#2 GND IN
3" EMT
11
2
CD
DC
BA
AB
SKRU ASKRU C
500A/3P
MBP (NO)
MIS (NC)
MOB 2MOB 1LB1
SIS (NC)
GBB (NO)CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
E-303
11874770
PHASE 3
ONE-LINE
DIAGRAM
E. REICHARD
ETR
2051
APRIL 8, 2020
SCALE: NO SCALE
1 ONE-LINE DIAGRAM PHASE 3
E-303 KEYED PHASE 3 NOTES
1 EXERCISE BREAKER MBP MULTIPLE TIMES PRIOR TO MAKING THE CUT OVER TO
NEW FEED. OPEN MBP CIRCUIT BREAKER IN EXISITING SBM CABINET.
2 OPEN THE MAIN SWITCH FOR SS-B1. OPEN THE 800 AMP SWITCH AT SS-B1 TO THE
ALTERNATE BYPASS FEED TO MBP. PULL CONDUCTORS BACK TO SWITCH AND
DISPOSE OF. CLOSE MAIN SWITCH TO RE-ENERGIZE SS-B1.
3 FINALIZE THE INSTALLATION OF THE CONDUIT AND CONDUCTORS FROM THE
GLOBAL BYPASS PANEL TO THE EXISTING SBM. CONNECT FEED TO THE MBP
CIRCUIT BREAKER IN THE EXISTING SBM CABINET.
4 CLOSE MOB2 CIRCUIT BREAKER IN NEW SBM CABINET. CLOSE RECTIFIER PANEL
MAIN BREAKER AND BREAKERS FEEDING UPS #2.
5 CLOSE MBP CIRCUIT BREAKER IN EXISITING SBM CABINET, OPEN MIS BREAKER TO
TRANSFER LOAD TO NEW UPS #2.
6 OPEN CBS BREAKER IN THE EXISTING SBM CABINET. OPEN FBP AND CBP
BREAKERS. START GENERATOR AND TRANSFER ATS-3 AND ATS-5 TO EMERGENCY
POWER. OPEN MAIN SWITCH TO SS-B2. OPEN 800 AMP SWITCH, REMOVE AND
DISPOSE OF STATIC BYPASS FEED BACK TO SS-B1. CLOSE MAIN SWITCH TO SS-B2
AND LABEL SWITCH “SPARE”. TRANSFER ATS-3 AND ATS-5 BACK TO NORMAL
POWER.
7 OPEN NORMAL FEED TO ATS-3 AT SS-B2 AND EMERGENCY FEED AT DS-EG. OPEN
UPS #1 BATTERY AND OUTPUT BREAKER. DISCONNECT THE NEUTRAL CONDUCTOR
FROM BOTH FEEDS IN THE ATS AND CAP.
8 DISCONNECT AND REMOVE UPS #1 CONDUIT AND CONDUCTORS FROM UPS #1 TO
EXISTING SBM. REMOVE CONDUIT AND CONDUCTORS FROM UPS #1 TO ATS-3.
9 PROVIDE CONDUIT AND CONDUCTORS FROM ATS-3 TO NEW 500 AMP SBM BYPASS
BREAKER.
10 DISCONNECT AND REMOVE EXISTING UPS #2 CONDUIT AND CONDUCTORS FROM
UPS #2 TO EXISTING SBM.
11 REMOVE AND DISPOSE OF UPS #1 AND ITS BATTERIES. REMOVE AND DISPOSE OF
UPS #2.
12 INSTALL NEW BATTERIES FOR UPS #1. PROVIDE CONDUIT AND CONDUCTORS FROM
BATTERIES TO UPS MODULE. CLOSE RECTIFIER PANEL BREAKERS FEEDING UPS #1.
TRANSFER ATS-3 AND ATS-5 TO EMERGENCY POWER, SWITCH SBM INTO BYPASS.
OPEN BREAKERS IN RECTIFIER PANEL FEEDING UPS #2. PERFORM LOAD TESTING
ON UPS #1. ONCE COMPLETE, CLOSE BREAKERS IN RECTIFIER PANEL FEEDING UPS
#2, CLOSE MOB1 BREAKER. SWITCH BACK TO UPS POWER AND TRANSFER ATS-3
AND ATS-5 TO NORMAL POWER.
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION
E N
L
TO MV SWITCH
600AF
800AS
400AF
600AS
500AF
800AS
400AF
600AS
400AF
600AS
600AF
1200AS
400AF
600AS
500AF
800AS
800AF
1600AS
4000AF
4000AS
800AF
400AT
800AF
500AT
800AF
500AT
800AF
600AT
800AF
600AT
E N
L
800A/3P
800A/3P
800AF
1600AS
400AF
600AS
500AF
800AS
400AF
600AS
400AF
600AS
500AF
800AS
---AF
600AS
500AF
1200AS
4000AF
4000AS
3000AF
3000AS
2500-KVA
PRI: 13.2-KV
SEC: 480Y/277V
2500-KVA
PRI: 13.2-KV
SEC: 480Y/277V
GUNIT 800-KW
800AF
400AT
800AF
400AT
800AF
400AT
SPARE
800AF
400AT
800AF
400AT
800AF
400AT
SPARE
DP-MG1 SECT 1
800A, 480/277V, 3Ø, 4W
DP-MG1 SECT 2
800A, 480/277V, 3Ø, 4W
DP-MG2 SECT 2
800A, 480/277V, 3Ø, 4W
DP-MG2 SECT 1
800A, 480/277V, 3Ø, 4W
SPACESPACESPACESPACESPACESPACESPACESPACESPACESPACESPACESPACE
DP-CC62
400A, 480/277V, 3Ø, 4W
DP-CC72
400A, 480/277V, 3Ø, 4W
DP-CC61
400A, 480/277V, 3Ø, 4W
DP-CC71
400A, 480/277V, 3Ø, 4W
SPARE
SS-B2 4000A
480/277V, 3Ø, 4W
SS-B1 4000A
480/277V, 3Ø, 4W
SS-B1 1200A
480/277V, 3Ø, 4W
ATS-3 NEW
ATS-5
SPACE
BATTERY BATTERY
CB-1
BATTERY BATTERY
CB-1
500A/3P
500A/3P
UPS MODULE #1
275KVA
UPS MODULE #2
275KVA#1 #2
NEW 500A SBM CABINET
500A/3P 500A/3P
#3 #4
MBP
MIS
800A/3P
800A/3P 800A/3P
EXISTING 800A SBM CABINET
CBS
600A/3P 600A/3P 600A/3P
SPARESPARE
RECTIFIER DISTRIBUTION PANEL
500A/3P
500A/3P 500A/3P
GLOBAL BYPASS
DISTRIBTION PANEL
500A/3P
1000AF
1200AT
500A/3P
500A/3P 500A/3P
(3) SETS 4-250 KCMIL
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-250KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#350 KCMIL &
1-#1 GND IN EXISTING 3" EMT(2) SETS OF 3-#350 KCMIL &
1-#1 GND IN EXISTING 3" EMT
(3) SETS 4-250 KCMIL
CD
DC
BA
AB
SKRU A
SKRU C MBP (NO)
MIS (NC)
MOB 2MOB 1LB1
SIS (NC)
GBB (NO)CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
E-304
11874770
FINAL ONE-LINE
DIAGRAM
E. REICHARD
ETR
2051
APRIL 8, 2020
SCALE:12" = 1'-0"1 ONE-LINE DIAGRAM FINAL
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION
E N
L
E N
L
ATS-3 NEW
ATS-5
BATTERY BATTERY
CB-1
BATTERY BATTERY
CB-1
500A/3P
500A/3P
UPS MODULE #1
300KVA
UPS MODULE #2
300KVA#1 #2
500A SBM CABINET
500A/3P 500A/3P
#3 #4
500A/3P500A/3P 500A/3P
GLOBAL BYPASS
DISTRIBTION PANEL
500A/3P500A/3P
CD
DC
BA
AB
SKRU A
SKRU C
J
CA
CD4CD2
CB1
CD1
CE1 CE2
CB
CD3
CF
CB2
CC
CA1
CG CG
TO COL. D1 TO COL. D1
CW CW
IBMU
CELL
WATCH
PANEL CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
E-305
11874770
CONTROL RISER
DIAGRAM
E. REICHARD
ETR
2051
April 8, 2020
SCALE:12" = 1'-0"1 CONTROL RISER DIAGRAM
CONTROL WIRING LEGEND
CA 1 - #14 TWISTED PAIR IN ½” EMT
CA1 1 - #14 TWISTED PAIR IN ½” EMT
CB 2 - #14 TWISTED PAIR IN ½” EMT (CB1 & CB2)
CB1 1 - #14 TWISTED PAIR IN ½” EMT
CB2 1 - #14 TWISTED PAIR IN ½” EMT
CC 1 - #20 TWISTED SHIELDED PAIR INSIDE UPS CABINETS
CD1 2 - #14 TWISTED PAIR IN ½” EMT
CD2 2 - #14 TWISTED PAIR IN ½” EMT WITH CD1
CD3 2 - #14 TWISTED PAIR IN ½” EMT
CD4 2 - #14 TWISTED PAIR IN ½” EMT WITH CD3
CE1 6 - #14 TWISTED PAIR IN ¾” EMT
CE2 6 - #14 TWISTED PAIR IN ¾” EMT
CF 1 - #14 TWISTED PAIR IN ½” EMT
CG CAT6 IN 3/4" EMT W/BUSHING AT END - CAT6 BY CORNELL (COORDINATE WITH RICK
POLARO)
CW 1" EMT WITH PULLSTRING FROM EACH BATTERY SET TO CELLWATCH PANEL.
PROVIDE 1" EMT WITH PULL STRING BETWEEN IBMU AND CELLWATCH CONTROL
PANEL. EATON TO PULL CONTROL WIRING AND TERMINATE.
NOTE: REFER TO WIRE CHARTS IN SPECIFICATIONS FOR ADDITIONAL INFORMATION
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION