HomeMy WebLinkAbout020.0_E-305 CONTROL RISER DIAGRAME N
L
E N
L
ATS-3 NEW
ATS-5
BATTERY BATTERY
CB-1
BATTERY BATTERY
CB-1
500A/3P
500A/3P
UPS MODULE #1
300KVA
UPS MODULE #2
300KVA#1 #2
500A SBM CABINET
500A/3P 500A/3P
#3 #4
500A/3P500A/3P 500A/3P
GLOBAL BYPASS
DISTRIBTION PANEL
500A/3P500A/3P
CD
DC
BA
AB
SKRU A
SKRU C
J
CA
CD4CD2
CB1
CD1
CE1 CE2
CB
CD3
CF
CB2
CC
CA1
CG CG
TO COL. D1 TO COL. D1
CW CW
IBMU
CELL
WATCH
PANEL CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
E-305
11874770
CONTROL RISER
DIAGRAM
E. REICHARD
ETR
2051
April 8, 2020
SCALE:12" = 1'-0"1 CONTROL RISER DIAGRAM
CONTROL WIRING LEGEND
CA 1 - #14 TWISTED PAIR IN ½” EMT
CA1 1 - #14 TWISTED PAIR IN ½” EMT
CB 2 - #14 TWISTED PAIR IN ½” EMT (CB1 & CB2)
CB1 1 - #14 TWISTED PAIR IN ½” EMT
CB2 1 - #14 TWISTED PAIR IN ½” EMT
CC 1 - #20 TWISTED SHIELDED PAIR INSIDE UPS CABINETS
CD1 2 - #14 TWISTED PAIR IN ½” EMT
CD2 2 - #14 TWISTED PAIR IN ½” EMT WITH CD1
CD3 2 - #14 TWISTED PAIR IN ½” EMT
CD4 2 - #14 TWISTED PAIR IN ½” EMT WITH CD3
CE1 6 - #14 TWISTED PAIR IN ¾” EMT
CE2 6 - #14 TWISTED PAIR IN ¾” EMT
CF 1 - #14 TWISTED PAIR IN ½” EMT
CG CAT6 IN 3/4" EMT W/BUSHING AT END - CAT6 BY CORNELL (COORDINATE WITH RICK
POLARO)
CW 1" EMT WITH PULLSTRING FROM EACH BATTERY SET TO CELLWATCH PANEL.
PROVIDE 1" EMT WITH PULL STRING BETWEEN IBMU AND CELLWATCH CONTROL
PANEL. EATON TO PULL CONTROL WIRING AND TERMINATE.
NOTE: REFER TO WIRE CHARTS IN SPECIFICATIONS FOR ADDITIONAL INFORMATION
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION