HomeMy WebLinkAbout019.0_E-304 FINAL ONE LINE DIAGRAME N
L
TO MV SWITCH
600AF
800AS
400AF
600AS
500AF
800AS
400AF
600AS
400AF
600AS
600AF
1200AS
400AF
600AS
500AF
800AS
800AF
1600AS
4000AF
4000AS
800AF
400AT
800AF
500AT
800AF
500AT
800AF
600AT
800AF
600AT
E N
L
800A/3P
800A/3P
800AF
1600AS
400AF
600AS
500AF
800AS
400AF
600AS
400AF
600AS
500AF
800AS
---AF
600AS
500AF
1200AS
4000AF
4000AS
3000AF
3000AS
2500-KVA
PRI: 13.2-KV
SEC: 480Y/277V
2500-KVA
PRI: 13.2-KV
SEC: 480Y/277V
GUNIT 800-KW
800AF
400AT
800AF
400AT
800AF
400AT
SPARE
800AF
400AT
800AF
400AT
800AF
400AT
SPARE
DP-MG1 SECT 1
800A, 480/277V, 3Ø, 4W
DP-MG1 SECT 2
800A, 480/277V, 3Ø, 4W
DP-MG2 SECT 2
800A, 480/277V, 3Ø, 4W
DP-MG2 SECT 1
800A, 480/277V, 3Ø, 4W
SPACESPACESPACESPACESPACESPACESPACESPACESPACESPACESPACESPACE
DP-CC62
400A, 480/277V, 3Ø, 4W
DP-CC72
400A, 480/277V, 3Ø, 4W
DP-CC61
400A, 480/277V, 3Ø, 4W
DP-CC71
400A, 480/277V, 3Ø, 4W
SPARE
SS-B2 4000A
480/277V, 3Ø, 4W
SS-B1 4000A
480/277V, 3Ø, 4W
SS-B1 1200A
480/277V, 3Ø, 4W
ATS-3 NEW
ATS-5
SPACE
BATTERY BATTERY
CB-1
BATTERY BATTERY
CB-1
500A/3P
500A/3P
UPS MODULE #1
275KVA
UPS MODULE #2
275KVA#1 #2
NEW 500A SBM CABINET
500A/3P 500A/3P
#3 #4
MBP
MIS
800A/3P
800A/3P 800A/3P
EXISTING 800A SBM CABINET
CBS
600A/3P 600A/3P 600A/3P
SPARESPARE
RECTIFIER DISTRIBUTION PANEL
500A/3P
500A/3P 500A/3P
GLOBAL BYPASS
DISTRIBTION PANEL
500A/3P
1000AF
1200AT
500A/3P
500A/3P 500A/3P
(3) SETS 4-250 KCMIL
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-250KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#350 KCMIL &
1-#1 GND IN EXISTING 3" EMT(2) SETS OF 3-#350 KCMIL &
1-#1 GND IN EXISTING 3" EMT
(3) SETS 4-250 KCMIL
CD
DC
BA
AB
SKRU A
SKRU C MBP (NO)
MIS (NC)
MOB 2MOB 1LB1
SIS (NC)
GBB (NO)CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
E-304
11874770
FINAL ONE-LINE
DIAGRAM
E. REICHARD
ETR
2051
APRIL 8, 2020
SCALE:12" = 1'-0"1 ONE-LINE DIAGRAM FINAL
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION