HomeMy WebLinkAbout016.0_E-301 PHASE 1 ONE LINE DIAGRAME N
L
BATTERY BATTERY
TO MV SWITCH
600AF800AS 400AF600AS 500AF800AS 400AF600AS 400AF600AS 500AF1200AS 400AF600AS 500AF800AS 800AF1600AS
4000AF4000AS
800AF
500AT
800AF
500AT
800AF
600AT
E N
L
800A/3P800A/3P
800A/3P 800A/3P800A/3P
800AF1600AS 400AF600AS 500AF800AS 400AF600AS 400AF600AS 500AF800AS ---AF600AS 500AF1200AS
4000AF4000AS 3000AF3000AS
2500-KVA
PRI: 13.2-KV
SEC: 480Y/277V
2500-KVA
PRI: 13.2-KV
SEC: 480Y/277V
GUNIT 800-KW
800AF
400AT
800AF
400AT
800AF
400AT
SPARE
800AF
400AT
800AF
400AT
800AF
400AT
SPARE
DP-MG1 SECT 1
800A, 480/277V, 3Ø, 4W
DP-MG1 SECT 2
800A, 480/277V, 3Ø, 4W
DP-MG2 SECT 2
800A, 480/277V, 3Ø, 4W
DP-MG2 SECT 1
800A, 480/277V, 3Ø, 4W
SPACESPACESPACESPACESPACESPACESPACESPACESPACESPACESPACESPACE
DP-CC62
400A, 480/277V, 3Ø, 4W
DP-CC72
400A, 480/277V, 3Ø, 4W
DP-CC61
400A, 480/277V, 3Ø, 4W
DP-CC71
400A, 480/277V, 3Ø, 4W
SPARE
SS-B2 4000A
480/277V, 3Ø, 4W
SS-B1 4000A
480/277V, 3Ø, 4W
DS-EG 1200A
480/277V, 3Ø, 4W
ATS-3
ATS-5
UPS MODULE #1
300KVA
#1 #2
EXISTING 800A SBM CABINET
SPACE
BATTERY BATTERY
UPS MODULE #2
300KVA
#3 #4
MBP
CBS
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
J. BOX #1
J. BOX #2
J. BOX #1
J. BOX #1
UPS #2
BREAKER
UPS #1
BREAKER
1
2
1
3
4
5
(3) SETS 4-250 KCMIL
(3) SETS 4-250 KCMIL
(3) SETS 4-250 KCMIL(2) SETS 4-250 KCMIL
(2) SETS 4-250 KCMIL
4
CB-1 CB-1
500A/3P
UPS MODULE #1
275KVA
UPS MODULE #2
275KVA
NEW 500A SBM CABINET
500A/3P 500A/3P
(2) SETS OF 3-250KCMIL
& 1-#2 GND IN 3" EMT
600A/3P
600A/3P
500A/3P
500A/3P 500A/3P
GLOBAL BYPASS
DISTRIBTION PANEL
500A/3P500A/3P
800AF
400AT
1000AF
1200AT
500A/3P 500A/3P600A/3P
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-#350 KCMIL
& 1-#1 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
(2) SETS OF 3-#250 KCMIL
& 1-#2 GND IN 3" EMT
RECTIFIER DISTRIBUTION PANEL
480V, 3Ø, 3W 65KAIC
480V, 3Ø,
3W, 65KAIC
2
CD
DC
BA
AB
SKRU A
SKRU C
500A/3P
480V, 3Ø, 3W 65KAIC
MBP (NO)
MIS (NC)
MOB 1 MOB 2MOB 1LB1
SIS (NC)
GBB (NO)
60A/3P
SPD 120KA CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
136 HOY ROAD
RHODES HALL
UPS
REPLACEMENT
E-301
11874770
PHASE 1
ONE-LINE
DIAGRAM
E. REICHARD
ETR
2051
April 8, 2020
SCALE: NO SCALE
1 ONE-LINE DIAGRAM PHASE 1
E-301 KEYED PHASE 1 NOTES
1 PROVIDE EATON 600 AMP RECTIFIER DISTRIBUTION PANEL. PROVIDE CONDUIT
FROM PANEL TO ATS-5 LOCATION. CONDUIT AND CONDUCTORS TO BE TERMINATED
IN NEXT PHASE.
2 PROVIDE TWO (2) EATON 9395HP 275KVA/275KW UPS MODULES FOR PARALLEL
REDUNDANT SYSTEM. PROVIDE CONDUIT AND CONDUCTORS FOR UPS RECTIFIER
AND BYPASS FEEDS FROM RECTIFIER DISTRIBUTION PANEL TO BOTH UPS
MODULES.
3 PROVIDE EATON SBM PARALLEL TIE CABINET WITH TWO BREAKER MAINTENANCE
BYPASS. PROVIDE CONDUIT AND CONDUCTORS FROM UPS MODULES TO THE SBM
CABINET.
4 PROVIDE NEW EATON 1200A GLOBAL BYPASS PANELBOARD. PROVIDE CONDUIT
AND CONDUCTORS FROM THE SBM CABINET TO THE GLOBAL BYPASS PANEL.
5 PROVIDE CONDUIT FROM GLOBAL BYPASS PANELBOARD TO ABOVE EXISTING SBM
BYPASS CABINET. CONDUIT AND CONDUCTORS TO BE TERMINATED AT PHASE 3.
#
1 08/16/19 ISSUE FOR DD REVIEW
2 03/20/20 ISSUE FOR 95% REVIEW
3 05/05/20 ISSUE FOR COORDINATED REVIEW
4 04/08/20 ISSUE FOR CONSTRUCTION