HomeMy WebLinkAbout016.0_E-301 PHASE 1 ONE LINE DIAGRAME N L BATTERY BATTERY TO MV SWITCH 600AF800AS 400AF600AS 500AF800AS 400AF600AS 400AF600AS 500AF1200AS 400AF600AS 500AF800AS 800AF1600AS 4000AF4000AS 800AF 500AT 800AF 500AT 800AF 600AT E N L 800A/3P800A/3P 800A/3P 800A/3P800A/3P 800AF1600AS 400AF600AS 500AF800AS 400AF600AS 400AF600AS 500AF800AS ---AF600AS 500AF1200AS 4000AF4000AS 3000AF3000AS 2500-KVA PRI: 13.2-KV SEC: 480Y/277V 2500-KVA PRI: 13.2-KV SEC: 480Y/277V GUNIT 800-KW 800AF 400AT 800AF 400AT 800AF 400AT SPARE 800AF 400AT 800AF 400AT 800AF 400AT SPARE DP-MG1 SECT 1 800A, 480/277V, 3Ø, 4W DP-MG1 SECT 2 800A, 480/277V, 3Ø, 4W DP-MG2 SECT 2 800A, 480/277V, 3Ø, 4W DP-MG2 SECT 1 800A, 480/277V, 3Ø, 4W SPACESPACESPACESPACESPACESPACESPACESPACESPACESPACESPACESPACE DP-CC62 400A, 480/277V, 3Ø, 4W DP-CC72 400A, 480/277V, 3Ø, 4W DP-CC61 400A, 480/277V, 3Ø, 4W DP-CC71 400A, 480/277V, 3Ø, 4W SPARE SS-B2 4000A 480/277V, 3Ø, 4W SS-B1 4000A 480/277V, 3Ø, 4W DS-EG 1200A 480/277V, 3Ø, 4W ATS-3 ATS-5 UPS MODULE #1 300KVA #1 #2 EXISTING 800A SBM CABINET SPACE BATTERY BATTERY UPS MODULE #2 300KVA #3 #4 MBP CBS (2) SETS OF 3-#350 KCMIL & 1-#1 GND IN 3" EMT J. BOX #1 J. BOX #2 J. BOX #1 J. BOX #1 UPS #2 BREAKER UPS #1 BREAKER 1 2 1 3 4 5 (3) SETS 4-250 KCMIL (3) SETS 4-250 KCMIL (3) SETS 4-250 KCMIL(2) SETS 4-250 KCMIL (2) SETS 4-250 KCMIL 4 CB-1 CB-1 500A/3P UPS MODULE #1 275KVA UPS MODULE #2 275KVA NEW 500A SBM CABINET 500A/3P 500A/3P (2) SETS OF 3-250KCMIL & 1-#2 GND IN 3" EMT 600A/3P 600A/3P 500A/3P 500A/3P 500A/3P GLOBAL BYPASS DISTRIBTION PANEL 500A/3P500A/3P 800AF 400AT 1000AF 1200AT 500A/3P 500A/3P600A/3P (2) SETS OF 3-#350 KCMIL & 1-#1 GND IN 3" EMT (2) SETS OF 3-#350 KCMIL & 1-#1 GND IN 3" EMT (2) SETS OF 3-#250 KCMIL & 1-#2 GND IN 3" EMT (2) SETS OF 3-#250 KCMIL & 1-#2 GND IN 3" EMT (2) SETS OF 3-#250 KCMIL & 1-#2 GND IN 3" EMT (2) SETS OF 3-#250 KCMIL & 1-#2 GND IN 3" EMT (2) SETS OF 3-#250 KCMIL & 1-#2 GND IN 3" EMT RECTIFIER DISTRIBUTION PANEL 480V, 3Ø, 3W 65KAIC 480V, 3Ø, 3W, 65KAIC 2 CD DC BA AB SKRU A SKRU C 500A/3P 480V, 3Ø, 3W 65KAIC MBP (NO) MIS (NC) MOB 1 MOB 2MOB 1LB1 SIS (NC) GBB (NO) 60A/3P SPD 120KA CORN E LL U N I V E R SI TYFOU N D E D 5681AD FACILITIES ENGINEERING ARCHIVE BAR CODEITHACA, NEW YORK ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 136 HOY ROAD RHODES HALL UPS REPLACEMENT E-301 11874770 PHASE 1 ONE-LINE DIAGRAM E. REICHARD ETR 2051 April 8, 2020 SCALE: NO SCALE 1 ONE-LINE DIAGRAM PHASE 1 E-301 KEYED PHASE 1 NOTES 1 PROVIDE EATON 600 AMP RECTIFIER DISTRIBUTION PANEL. PROVIDE CONDUIT FROM PANEL TO ATS-5 LOCATION. CONDUIT AND CONDUCTORS TO BE TERMINATED IN NEXT PHASE. 2 PROVIDE TWO (2) EATON 9395HP 275KVA/275KW UPS MODULES FOR PARALLEL REDUNDANT SYSTEM. PROVIDE CONDUIT AND CONDUCTORS FOR UPS RECTIFIER AND BYPASS FEEDS FROM RECTIFIER DISTRIBUTION PANEL TO BOTH UPS MODULES. 3 PROVIDE EATON SBM PARALLEL TIE CABINET WITH TWO BREAKER MAINTENANCE BYPASS. PROVIDE CONDUIT AND CONDUCTORS FROM UPS MODULES TO THE SBM CABINET. 4 PROVIDE NEW EATON 1200A GLOBAL BYPASS PANELBOARD. PROVIDE CONDUIT AND CONDUCTORS FROM THE SBM CABINET TO THE GLOBAL BYPASS PANEL. 5 PROVIDE CONDUIT FROM GLOBAL BYPASS PANELBOARD TO ABOVE EXISTING SBM BYPASS CABINET. CONDUIT AND CONDUCTORS TO BE TERMINATED AT PHASE 3. # 1 08/16/19 ISSUE FOR DD REVIEW 2 03/20/20 ISSUE FOR 95% REVIEW 3 05/05/20 ISSUE FOR COORDINATED REVIEW 4 04/08/20 ISSUE FOR CONSTRUCTION