HomeMy WebLinkAbout010.0_F-601 FIRE PROTECTION RISER DIAGRAMARCHIVE BAR CODEITHACA, NEW YORK
Rhodes Hall
UPS Replacement
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
P11874770
DATE:
FACILITY:
DESIGN:
DRAWN:
TMT
TMT
2051
April 8, 2020
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONSCORNELLUNIV
E
RSI
TYFOUN
DE D 5681AD
FACILITIES
ENGINEERING
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
GHD Project #11205715
GHD Consulting Services Inc.
5788 Widewaters Pkwy
Syracuse NY 13214 USA
T 1 315 802 0260 F 1 315 802 0450
RHODES HALL
ISSUE FOR 95% REVIEW103/20/20
100% FOR CONSTRUCTION204/08/20
FIRE PROTECTION RISER DIAGRAM
SCALE: NO SCALE
F-601
FIRE
PROTECTION
RISER
DIAGRAM
BASEMENT
PENTHOUSE
FACP ANN
ANN
RCP
IDC - ESS ROOM ALARM
IDC - ESS ROOM SUPRVISORY
EX
TVSS
1
RISER DIAGRAM KEYED NOTES:
TO 120 VAC POWER SOURCE
24 VDC POWER FROM RCP
POWER CIRCUIT TO EACH HYDROGEN GAS DETECTOR
HYDROGEN GAS DETECTION ALARM IDC
HYDROGEN GAS DETECTION TROUBLE/FAULT IDC
ESS ROOM SIGNALING LINE CIRCUIT
TO BATTERY CHARGING SHUNT TRIP
HYDROGEN GAS DETECTION NOTIFICATION APPLIANCE CIRCUIT
EXISTING BUILDING NOTIFICATION APPLIANCE CIRCUIT
EXTEND EXISTING BUILDING NOTIFICATION APPLIANCE CIRCUIT FOR NEW DEVICES
PROVIDE CONTROL PANEL ADJACENT TO EXISTING BUILDING FIRE ALARM CONTROL PANEL
TO RECEIVE ALARM, SUPERVISORY AND TROUBLE SIGNALS FROM THE PENTHOUSE
RELEASING PANEL AND REPORTING ALARM SIGNAL THROUGH THE BUILDING FIRE ALARM
CONTROL PANEL TO THE CAMPUS CENTRAL STATION.
2
3
4
5
6
1
AOM AIM AIM AIM
SV TS LA WF
S
P
S
P
S
P
S
P
AIM AIM
H
H
H
2
3
4
5
S
P
S
P
S
P
S
P
6
AOM AIM
AR2
7
7
G
H
8
8
IDC - GAS DETECTION ALARM
IDC - ESS ROOM TROUBLE
F
H
F
H
G
H
G
H
G
H
EOL EX EX F
H
F
H
EOL
9
10
EOL EOL EOL EOL
EOLEOL
EOL
10
9
F
EX
EX
FACP
11
11