HomeMy WebLinkAbout009.0_F-501 FIRE PROTECTION DETAILSARCHIVE BAR CODEITHACA, NEW YORK
Rhodes Hall
UPS Replacement
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
P11874770
DATE:
FACILITY:
DESIGN:
DRAWN:
TMT
TMT
2051
April 8, 2020
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONSCORNELLUNIV
E
RSI
TYFOUN
DE D 5681AD
FACILITIES
ENGINEERING
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
GHD Project #11205715
GHD Consulting Services Inc.
5788 Widewaters Pkwy
Syracuse NY 13214 USA
T 1 315 802 0260 F 1 315 802 0450
RHODES HALL
ISSUE FOR 95% REVIEW103/20/20
100% FOR CONSTRUCTION204/08/20
F-501
FIRE
PROTECTION
DETAILS
6-INCH FROM FIRE
PROTECTION WATER
SUPPLY
SUPERVISED CONTROL
VALVE WITH TAMPER
SWITCH WIRED TO ESS
ROOM SUBPANEL
LOW AIR PRESSURE
SUPERVISORY SWITCH
WIRED TO ESS ROOM
SUBPANEL
AUTO AIR
MAINTENANCE DEVICE
PRESSURE
GAUGE (TYPICAL)
FINISHED FLOOR
CHECK VALVE
TO PREACTION
SYSTEM
6-INCH PREACTION
VALVE
AIR COMPRESSOR
MANUAL EMERGENCY RELEASE DEVICE
PRESSURE OPERATED RELIEF VALVE
CONCRETE BASE WITH
BASE ELBOW
MAIN DRAIN DISCHARGE
WITH 45° ELBOW 24" ±
ABOVE EXISTING CAPABLE
PLUMBING DRAIN
EXTERIOR WALL
DRAIN CUP
STRAINER ORIFICE CHECK VALVE
WATERFLOW
SWITCH
ELECTRIC RELEASE
SOLENOID VALVE
STRAINER
DRDR DRNO SCALE
PREACTION FIRE SPRINKLER VALVE
TO ESS ROOM
SUBPANEL
AI
AR
R
SLC TO NEXT DEVICE
120v SHUNT TRIP POWER
SLC TO NEXT DEVICE
EMT (TYPICAL)
ADDRESSABLE LOAD CONTROL FIELD
RELAY WITH 24DC COIL AND 2 SETS
OF NORMALLY OPEN AND NORMALLY
CLOSED (DPDT) CONTACTS RATED AT
120 VAC, 4 AMPS, INDUCTIVE.
ADDRESSABLE RELAY
AI
AR
R
SLC TO NEXT DEVICE
120v SHUNT TRIP POWER TO BATTERY CHARGING
SHUNT TRIP CIRCUIT BREAKER
SLC TO NEXT DEVICE
EMT (TYPICAL)
SEE NOTES 1 & 2
BATTERY CHARGING SHUNT TRIP
CONTROL CIRCUIT INTERFACE
POINT
ADDRESSABLE LOAD CONTROL FIELD
RELAY WITH 24DC COIL AND 2 SETS
OF NORMALLY OPEN AND NORMALLY
CLOSED (DPDT) CONTACTS RATED AT
120 VAC, 4 AMPS, INDUCTIVE.
ADDRESSABLE INTERFACE
MODULE ADDRESSABLE RELAY
GENERAL NOTES:
A.PROVIDE MINIMUM 305X305X100MM DEEP NEMA 1 TERMINAL BOX WITH SCREW COVER (CONTRACTOR SHALL
VERIFY REQUIRED BOX SIZE). LABEL "FIRE ALARM BATTERY CHARGER SHUNT TRIP CONNECTION" WITH
ASSOCIATED ELEVATOR NUMBERS.
B.LOCATE TERMINAL BOX, WITHIN THREE FEET OF ASSOCIATED SHUNT TRIP CIRCUIT BREAKER/DISCONNECT
DEVICE.
NO SCALE
BATTERY CHARGER POWER SHUNT TRIP DETAIL
1
2
3
4
5
6
10
11
WATERFLOW SWITCH
AC POWER FAILURE
LOW BATTERY
OPEN CIRCUIT
GROUND CIRCUIT
NOTIFICATION APPLIANCE CIRCUIT OPEN OR SHORT
A ACTUATE COMMON ALARM SIGNAL INDICATOR ATRELEASING CONTROL PANELACTUATE COMMON SUPERVISORY SIGNAL INDICATORAT RELEASING CONTROL PANELACTUATE COMMON TROUBLE SIGNAL INDICATORAT RELEASING CONTROL PANELSOUND INTERNAL BUZZER AT RELEASING CONTROLPANEL (RCP)TEXT MESSAGE DISPLAY DEVICE TYPE & LOCATIONOF THE ACTIVATING DEVICES ON LCD OFRELEASING CONTROL PANEL (RCP)TRANSMIT FIRE ALARM SIGNAL TO BUILDING FACPACTIVATE GAS DETECTION AUDIBLE/VISUALNOTIFICATION APPLIANCES (RED STROBES)OPEN PREACTION SOLENOID VALVEB C D E F G H I
CONTROL UNIT ANNUNCIATION
SYSTEM OUTPUT
INDICATING/CONTROLLED DEVICES
SYSTEM INPUTS
INITIATING DEVICES
NOTIFICATION
FIRE PROTECTION SYSTEM INPUT/OUTPUT MATRIX
9
J KTRANSMIT SUPERVISORY SIGNAL TO BUILDINGFACPCONTROL FUNCTIONS
NO SCALE
FIRE PROTECTION SYSTEM INPUT/OUTPUT MATRIX
7
8
PREACTION SMOKE DETECTOR
TAMPER SWITCH
LOW AIR PRESSURE SWITCH
HYDROGEN GAS DETECTOR
MANUAL PULL STATION OPEN PREACTION SPRINKLER VALVESHUNT BATTERY CHARGING1
F-500
2
F-500
4
F-500
ROD SIZE (A)
B
C
RODTAKE-OUT (D)MIN. THREADLENGTH (E)PIPE
SIZE A B C
212
12
5916 4
3 634 478
4 71316 512
5 9116 618
6 10716 61516
12
ALL SIZES ARE IN INCHES
2
12
412 314
112 4 3
114 3716 2916
1 21316 218
34 2716 17 8
12 38 218 11116
8 1234 838
38
38
38
38
38
38
38
38
5810 1514 91316
5812 1758 11316
D
3116
31516
438
5
51116
212
214
11316
13 8
118
1516
718
838
91116
E
3
212
212
312
312
312
212
212
212
212
212
212
212
212
MINIMUM ONE FULL
THREAD OF ROD
MUST BE EXPOSED
CLEVIS HANGER
ALL-THREAD ROD
CROSS BOLT
CLEVIS BOLT SPACER
NO SCALE
PIPE SUPPORT DETAIL3
F-500
FINISHED
FLOOR
1" BALL VALVE NOT OVER
7'-0" ABOVE FINISHED FLOOR
BRANCH LINE
RETURN BEND FOR
PREACTION SYSTEM
EXTERIOR BUILDING WALL
NO SCALE
INSPECTOR TEST DETAIL5
F-500
TEMPORARY CONNECTION
PLUG VALVE END WHEN
NOT IN USE
12 CELLWATCH BATTERY MONITORING SYSTEM FAILURE
TO EXISTING STAIRWELL
DRAIN RISER
13 SUPPLY AIR DUCT VELOMETER - VELOCITY DROP