Rhodes Hall
UPS Replacement
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
P11874770
DATE:
FACILITY:
DESIGN:
DRAWN:
TMT
TMT
2051
April 8, 2020
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONSCORNELLUNIV
E
RSI
TYFOUN
DE D 5681AD
FACILITIES
ENGINEERING
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
GHD Project #11205715
GHD Consulting Services Inc.
5788 Widewaters Pkwy
Syracuse NY 13214 USA
T 1 315 802 0260 F 1 315 802 0450
RHODES HALL
ISSUE FOR 95% REVIEW103/20/20
100% FOR CONSTRUCTION204/08/20
PARTIAL PENTHOUSE
FIRE PROTECTION PLAN
SCALE: 1/8" = 1'-0"
GENERAL NOTES:
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
KEYED NOTES:
PROVIDE ADDRESSABLE FIRE ALARM RELEASING CONTROL PANEL. SEE RISER DIAGRAM ON
DRAWING F-600.
2-HOUR CIRCUIT INTEGRITY CABLING FIRE ALARM WIRING SHALL BE INSTALLED WITHIN EMT
CONDUIT.
POWER PANEL ELP-P SHALL BE UTILIZED FOR POWER FOR FIRE PROTECTION DEVICES, I.E.
FIRE ALARM CONTROL PANEL, AIR COMPRESSOR, MONITORING EQUIPMENT (WATERFLOW
SWITCH, SUPERVISORY SWITCH, TAMPER SWITCH), SOLENOID VALVE.
LOCATION OF VERTICAL CONDUIT RUNS SHALL BE COORDINATED WITH BUILDING
PERSONNEL. IF A COMMON VERTICAL CONDUIT LOCATION IS FOUND, IT SHALL BE UTILIZED.
HYDROGEN GAS DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
INSTRUCTIONS AND SHALL BE PROGRAMMED TO A SENSITIVITY OF 12.5% OF THE LOWER
FLAMMABILITY LIMIT OF HYDROGEN GAS. MANUFACTURER REPRESENTATIVE SHALL FIELD
VERIFY THAT HYDROGEN DETECTOR SPACING WILL BE EFFECTIVE.
MAIN DRAIN AND INSPECTOR'S TEST DISCHARGE SHALL BE COORDINATED WITH EXISTING
DRAIN RISER. CAPACITY OF EXISTING DRAIN TO BE UTILIZED SHALL BE CONFIRMED.
PROVIDE ADDRESSABLE INPUT MODULE ABOVE OR ADJACENT TO CELLWATCH CONTROL
UNIT. INPUT MODULE SHALL SUPERVISE CU RELAY OUTPUT #5 (WARNING).
PROVIDE FLUSHING FULL-PORT BALL VALVE ON EACH BRANCH LINE MATCHING THE SIZE OF
THE BRANCH LINE PIPING.
PROVIDE THREE 2-1/2" FLUSHING FULL PORT BALL VALVES ON THE END OF THE 6-INCH
SUPPLY MAIN.
PREACTION VALVE DRAIN PIPING SHALL BE ROUTED DOWN TO THE FLOOR BELOW THEN TO
THE EXISTING DRAIN RISER.
PROVIDE A COMPLETE AUTOMATIC FIRE ALARM SYSTEM IN ACCORDANCE WITH THE 2020
BUILDING CODE OF NEW YORK STATE AND NFPA 72 (2016) FOR THE ENERGY STORAGE
SYSTEM ROOM.
PROVIDE A COMPLETE AUTOMATIC PREACTION SPRINKLER SYSTEM IN ACCORDANCE WITH
THE 2020 BUILDING CODE OF NEW YORK STATE AND NFPA 13 (2016) FOR THE ENERGY
STORAGE SYSTEM ROOM.
PIPING AS SHOWN IS DIAGRAMMATIC, NOT ALL PIPING/FITTINGS ARE INDICATED.
CONTRACTOR IS RESPONSIBLE FOR FINAL SPRINKLER SYSTEM PIPE SIZING/LAYOUT,
SPRINKLER HYDRAULIC CALCULATIONS, AND COORDINATION WITH LIGHT FIXTURES/FIRE
ALARM DEVICES, DUCTWORK AND DIFFUSERS.
FINAL PIPE SIZING SHALL BE DETERMINED BY CONTRACTOR HYDRAULIC CALCULATIONS
SUBJECT TO APPROVAL BY ENGINEER.
MAXIMUM SPRINKLER COVERAGE AREA SHALL BE 120 SQ.FT.
SPRINKLER DESIGN CRITERIA IS AS FOLLOWS: 0.30GPM/SQ.FT. OVER THE ENTIRETY OF THE
ESS ROOM, 100 GPM HOSE STREAM DEMAND AT TOP OF STANDPIPE & 400 GPM AT WATER
SUPPLY SOURCE.
INSTALL ALL CONDUIT EXPOSED IN AREAS WITH NO FINISHED CEILINGS UNLESS OTHERWISE
NOTED.
INSTALL ALL WIRING AND CONDUIT WITH THE REQUIRED SUPPORT/HANGERS. INSTALL ALL
SUPPORTS FROM THE BUILDING STRUCTURE.
INSTALL ALL INITIATING DEVICES IN A MANNER THAT PROVIDES ACCESSIBILITY FOR PERIODIC
INSPECTION, TESTING AND MAINTENANCE.
FIRE STOP ALL PENETRATIONS THROUGH RATED WALLS, FLOORS AND CEILINGS.
ALL PIPE SIZES SHALL BE SCHEDULE 40 BLACK STEEL WITH THREADED FITTINGS.
SPRINKLERS SHALL BE LOCATED A MINIMUM OF 24 INCHES FROM THE SIDE OF HVAC
DIFFUSERS.
ALL SPRINKLER PIPING SHALL BE PITCHED BACK TO THE PREACTION VALVE TO ALLOW FOR
PROPER DRAINAGE AND TO ELIMINATE THE POSSIBILITY OF TRAPPED WATER.
SPRINKLER SUPPLY MAIN AND BRANCH PIPING SHALL BE ROUTED DIRECTLY BELOW THE
STRUCTURAL I-BEAMS WITH VERTICAL PIPING UP TO THE DECK FOR EACH UPRIGHT
SPRINKLER.
F-103
PARTIAL
PENTHOUSE
FIRE
PROTECTION
PLAN
0
SCALE 3/16"=1'-0" AT ORIGINAL SIZE
8'-0"6'-0"4'-0"2'-0"
DN
DN
DN
KEY PLAN
NO SCALE
AREA OF
WORK
EXISTING 6-INCH
STANDPIPE
6"
6"
6"
FIRE ALARM
CONDUIT DOWN
TO BASEMENT
6-INCH PREACTION VALVE ASSEMBLY
(SEE DETAIL 1 "PREACTION FIRE
SPRINKLER VALVE" ON DRAWING F-500)
EXISTING 2-INCH MAIN
DRAIN DISCHARGE
ENERGY STORAGE
SYSTEM LOCATIONS
TYP.
DOWN TO INSPECTOR TEST CONNECTION. SEE
DETAIL 5 "INSPECTOR TEST DETAIL" ON DRAWING
F-500. DRAIN TO EXISTING STAIRWELL DRAIN RISER.