Rhodes Hall
UPS Replacement
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
P11874770
DATE:
FACILITY:
DESIGN:
DRAWN:
TMT
TMT
2051
April 8, 2020
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONSCORNELLUNIV
E
RSI
TYFOUN
DE D 5681AD
FACILITIES
ENGINEERING
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
GHD Project #11205715
GHD Consulting Services Inc.
5788 Widewaters Pkwy
Syracuse NY 13214 USA
T 1 315 802 0260 F 1 315 802 0450
RHODES HALL
ISSUE FOR 95% REVIEW103/20/20
100% FOR CONSTRUCTION204/08/20
BASEMENT FIRE PROTECTION PLAN
SCALE: 3/32" = 1'-0"
0
SCALE 3/32"=1'-0" AT ORIGINAL SIZE
16'-0"12'-0"8'-0"4'-0"
GENERAL NOTES:
A.
B.
C.
INSTALL ALL CONDUIT EXPOSED IN AREAS WITH NO FINISHED CEILINGS UNLESS OTHERWISE
NOTED.
INSTALL ALL WIRING AND CONDUIT WITH THE REQUIRED SUPPORT/HANGERS. INSTALL ALL
SUPPORTS FROM THE BUILDING STRUCTURE.
FIRE STOP ALL PENETRATIONS THROUGH RATED WALLS, FLOORS AND CEILINGS.
F-102
BASEMENT
FIRE
PROTECTION
PLAN
EXISTING FIRE PUMP
LOCATION FOR HYDRAULIC
CALCULATION PURPOSES
EXISTING 6-INCH
STANDPIPE
FIRE ALARM CONDUIT UP TO
PENTHOUSE FIRE ALARM SUBPANEL
KEYED NOTES:
2-HOUR CIRCUIT INTEGRITY FIRE ALARM CABLING SHALL BE INSTALLED WITHIN EMT CONDUIT.
LOCATION OF VERTICAL CONDUIT RUNS SHALL BE COORDINATED WITH BUILDING
PERSONNEL. IF A COMMON VERTICAL CONDUIT LOCATION IS FOUND, IT SHALL BE UTILIZED.
PROVIDE NEW FCI E3 FACP ADJACENT TO THE EXISTING FCI 72C FACP TO RECEIVE ALARM,
SUPERVISORY AND TROUBLE SIGNALS FROM THE PENTHOUSE RELEASING PANEL AND
REPORTING ALARM SIGNALS THROUGH THE EXISTING MAIN FACP TO THE CAMPUS CENTRAL
STATION AT BARTON HALL. PROVIDE AN ADDRESSABLE MODULE AND RECIRCUIT ONE
EXISTING BASEMENT FLOOR FIRE ALARM ZONE THROUGH IT TO THE NEW FACP. CONNECT
THE NEW FACP TO THE NEW SPARE ZONE IN THE EXISTING FACP.
1
2
2
1
2
3
3