Rhodes Hall
UPS Replacement
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
P11874770
DATE:
FACILITY:
DESIGN:
DRAWN:
TMT
TMT
2051
April 8, 2020
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONSCORNELLUNIV
E
RSI
TYFOUN
DE D 5681AD
FACILITIES
ENGINEERING
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
GHD Project #11205715
GHD Consulting Services Inc.
5788 Widewaters Pkwy
Syracuse NY 13214 USA
T 1 315 802 0260 F 1 315 802 0450
RHODES HALL
ISSUE FOR 95% REVIEW103/20/20
100% FOR CONSTRUCTION204/08/20
F-001
SYMBOL LIST,
GENERAL NOTES
AND
ABBREVIATION
LIST
FIRE PROTECTION SYMBOL LIST
MANUAL PULL STATION. MOUNTING HEIGHT: +48" AFF (TO CENTER)
SMOKE SENSOR, PHOTOELECTRIC, CEILING MOUNTED
FIRE ALARM CONTROL PANEL
FIRE ALARM GENERAL NOTES:
1.THE SYSTEM SHALL INCLUDE ALL WIRING, RACEWAYS, PULL BOXES, TERMINAL CABINETS, OUTLET AND MOUNTING BOXES,
CONTROL EQUIPMENT, ALARM, AND SUPERVISORY SIGNAL INITIATING DEVICES, ALARM NOTIFICATION APPLIANCES, INTERFACE
EQUIPMENT, AND OTHER ACCESSORIES AND MISCELLANEOUS ITEMS INCLUDING SOFTWARE, SYSTEM PROGRAMMING, TESTING
AND CONSTRUCTION PERMITS REQUIRED FOR A COMPLETE OPERATING SYSTEM EVEN THOUGH EACH ITEM IS NOT
SPECIFICALLY MENTIONED OR DESCRIBED. PROVIDE SYSTEM COMPLETE AND READY FOR OPERATION. THE SYSTEM MUST
COMPLY WITH THE 2015 INTERNATIONAL BUILDING CODE (IBC) WITH THE 2017 NYS UNIFORM CODE SUPPLEMENT.
2.PROVIDE ALL WIRING FROM APPLIANCE TERMINAL TO APPLIANCE TERMINAL. PROVIDE CONDUCTORS THAT ARE TERMINATED,
SPLICED, OR OTHERWISE INTERRUPTED IN ANY ENCLOSURE, CABINET, MOUNTING, OR JUNCTION BOX CONNECTED TO
SCREW-TYPE TERMINAL BLOCKS. WIRE NUTS AND SIMILAR DEVICES ARE PROHIBITED.
3.PROVIDE ALL FIRE ALARM CIRCUITS SUPERVISED UNLESS NOTED OTHERWISE, AS FOLLOWS IN ACCORDANCE WITH NFPA 72
(2013):
·INITIATING DEVICE CIRCUITS (IDC)- CLASS B
·NOTIFICATION APPLIANCE CIRCUITS (NAC)- CLASS B, SYNCHRONIZED
·SIGNALING LINE CIRCUITS (SLC)- CLASS B
4.PROVIDE SMOKE DETECTORS A MINIMUM OF 3 FEET FROM EXISTING AIR DIFFUSERS.
5.PROVIDE VISUAL WARNING STROBE/AUDIBLE NOTIFICATION APPLIANCES TO ACHIEVE MAXIMUM AUDIBILITY AND VISIBILITY IN
ACCORDANCE WITH NFPA 72 GUIDELINES. PROVIDE CARE IN LOCATING VISUAL WARNING STROBE APPLIANCES TO ENSURE
VISIBILITY AND AVOID OBSTRUCTIONS.
6.LABEL ALL ADDRESSABLE INPUT/OUTPUT FIRE ALARM COVER PLATES AND APPLIANCES (INCLUDING HORNS, STROBES, SMOKE
SENSORS, HEAT SENSORS, MANUAL PULL STATIONS, ADDRESSABLE MODULES, ETC.) WITH THEIR ADDRESS UTILIZING A
LABELING MACHINE. HAND WRITTEN LABELS MUST NOT BE USED. ADDRESS MUST INCLUDE NAC OR SLC NUMBER FOLLOWED BY
APPLIANCE NUMBER. EACH SLC FIELD APPLIANCE ADDRESS MUST MATCH THE FIRE ALARM DISPLAY ADDRESS.
7.UNLESS OTHERWISE NOTED THE PROJECT ELECTRICAL CONDUIT STANDARD IS ELECTRICAL METALLIC TUBING (EMT) AND
PROVIDED THROUGHOUT THE PROJECT. PROVIDE ALL WIRING IN CONDUIT WHERE WIRES WOULD OTHERWISE BE EXPOSED.
WIRING MAY BE CONCEALED WITHIN WALLS AND CEILINGS WHERE APPLICABLE.
8.FLEXIBLE METAL CONDUIT (FMC) IS LIMITED TO 5 FEET AND SECURED PER THE NATIONAL ELECTRIC CODE (2014). FMC IS
PERMITTED FOR DEVICES LOCATED ON FIRE SUPPRESSION EQUIPMENT ONLY SUCH AS FLOW/PRESSURE SWITCHES,
SOLENOIDS AND TAMPER SWITCHES.
9.PROVIDE CONDUIT AS UNOBTRUSIVELY AS POSSIBLE, AS CLOSE AS POSSIBLE TO FLOOR/ CEILING SLAB AND PARALLEL AND AT
RIGHT ANGLES TO STRUCTURAL ELEMENTS.
10.PROVIDE ELECTRICAL BOXES AS FOLLOWS: UNLESS OTHERWISE NOTED PROVIDE CAST METAL BELL TYPE BOXES WITH
THREADED HUBS ON EXPOSED WORK, EXCEPT WHERE FACTORY BOXES ARE PROVIDED. CONCEALED BOXES MAY BE STAMPED
STEEL BOXES. PROVIDE TERMINAL CABINETS OF SOLID WALL CONSTRUCTION WITH NO FACTORY CONDUIT KNOCK OUTS.
11.PAINT ALL CONDUIT, FIRE ALARM JUNCTION BOXES AND COVERS RED IN UNFINISHED AREAS.
12.CORE DRILL PENETRATIONS IN MASONRY WALLS AND FLOOR/CEILING SLABS.
13.BOTH EXPOSED AND CONCEALED CONDUIT INCLUDING RISERS UP TO 2 INCHES IN DIAMETER MUST UTILIZE COMPRESSION
TYPE STEEL FITTINGS AND CONNECTORS. UNLESS OTHERWISE NOTED PROVIDE ALL CONDUIT 3/4 INCH MINIMUM TRADE SIZE.
PROVIDE VERTICAL RISERS ONE INCH DIAMETER MINIMUM. PROVIDE PLENUM RATED WIRING CONDUCTORS (TYPE FPLP) WHEN
FLEX CONDUIT IS UTILIZED. PROVIDE SOLID COPPER WIRING CONDUCTORS INSTALLED IN CONDUIT FOR THE FOLLOWING
CIRCUITS (AT MINIMUM):
·FIRE ALARM INITIATING DEVICE CIRCUITS (IDC) - 14/2 AWG
·FIRE ALARM SIGNALING LINE CIRCUITS (SLC) - 16/2 AWG TWISTED PAIR
·FIRE ALARM VISUAL NOTIFICATION APPLIANCES - 12/2 AWG.
·120 VAC - PRIMARY POWER - NO. 12 AWG, THHN/THWN 600VAC INSULATED
PROVIDE ALL WIRING UL LISTED FOR ITS INTENDED USE.
14.SECURE ALL NECESSARY CONSTRUCTION PERMITS, INSPECTIONS AND FINAL SYSTEM ACCEPTANCE.
15.CONTRACT DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY AND USED IN CONJUNCTION TO OBTAIN COMPLETE
CONSTRUCTION INFORMATION. CONTRACTOR MUST COORDINATE ALL DRAWINGS AND SPECIFICATIONS PRIOR TO
COMMENCING WORK.
16.VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE CONCERNING THE WORK BEFORE PROCEEDING WITH EITHER
FABRICATION OR INSTALLATION OF WORK. LOCATION OF EQUIPMENT IS APPROXIMATE. VERIFY THE LOCATION OF ALL SYSTEM
COMPONENTS.
17.AVOID ALL CONFLICTS WITH EXISTING LIGHT FIXTURES, HVAC DIFFUSERS, GRILLES, DUCTS, CONDUIT AND OTHER PIPING OR
OTHER OBSTRUCTIONS ENCOUNTERED. COORDINATE ALL WORK WITH FIELD CONDITIONS.
18.DO NOT CUT OR PATCH STRUCTURAL WORK IN A MANNER THAT WOULD RESULT IN A REDUCTION OF LOAD-CARRYING OR
LOAD-DEFLECTION RATIO.
19.PROVIDE ACCEPTANCE TESTING OF THE FIRE ALARM SYSTEM IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS.
20."PROVIDE" MEANS CONTRACTOR MUST FURNISH NEW AND INSTALL COMPLETE AND READY FOR INTENDED USE.
F
FACP
S
P
F
H FIRE ALARM HORN/STROBE
FIRE ALARM REMOTE ANNUNCIATOR PANELANN
FIRE FIGHTER PHONEP
SUPERVISED CONTROL VALVE
CHECK VALVE
PREACTION VALVE
UPRIGHT SPRINKLER
SPRINKLER PIPE
AIR COMPRESSORAC
FIRE ALARM 2-HOUR CI CABLE IN CONDUIT
EXISTING UPRIGHT SPRINKLER
EXISTING SPRINKLER PIPE
EXISTING TO REMAINEX
HYDROGEN GAS DETECTORH
EXISTING ELECTRICAL POWER PANELELECEX
G
H GAS DETECTION HORN/STROBE, RED STROBE, HIGH/LOW TONE
ADDRESSABLE RELEASING CONTROL PANELRCP
SOLENOID VALVESV
WATERFLOW SWITCHWF
TAMPER SWITCHTS
LOW AIR SUPERVISORY SWITCHLA
ADDRESSABLE OUTPUT MODULE
ADDRESSABLE INPUT MODULEAIM
AOM
ADDRESSABLE RELAYAR
END OF LINE RESISTOREOL
CONNECT TO EXISTING
REMOVE DEVICE AND ASSOCIATED EQUIPMENT
TRANSIENT VOLTAGE SURGE SUPPRESSIONTVSS
FULL-PORT BALL VALVE
VELOMETERV