HomeMy WebLinkAbout002.0_S-001 GENERAL NOTES ABBREV.MATERIAL N.S. GROUT STEEL PIECES AND ERECTION PLANS POST-INSTALLED ANCHORS REQUIRED SUBMITTALS SCHEDULE / SHOP DWGS PRODUCT DATA INSPECTIONS & TESTS X X X X X WIDE FLANGE MEMBERS A992, Fy = 50 KSI STRUCTURAL STEEL GRADES HSS RECTANGULAR MEMBERS CHANNELS AND ANGLES A500 GRADE B, Fy = 46 KSI A36, Fy = 36 KSI HSS ROUND MEMBERS A500 GRADE B, Fy = 42 KSI PLATES A572, Fy = 50 KSI PIPES A53, Fy = 35 KSI THREADED RODS F1554 GRADE 36, Fy = 36 KSI W_X__ STEEL BEAM OF SIZE W_X__ STEEL BEAM WITH BEARING PLATE TYPE # BP# COLUMN UP/DOWN NEW STEEL COLUMN W_X__ EXIST. STEEL BEAM OF SIZE W_X__ EXIST. STEEL COLUMN 150 PSF INCLUDING EQUIPMENT 75 PSF PLUS LOADS FROM SPECIFIC EQUIPMENT LAYOUT 200 PSF INCLUDING EQUIPMENT GROUND SNOW LOAD, Pg 40 PSF FLAT-ROOF SNOW LOAD, Pf 31 PSF SNOW LOAD IMPORTANCE FACTOR, Is 1.10 THERMAL FACTOR, Ct 1.0 DRIFT SURCHARGE LOAD, Pd N/A SNOW DRIFT WIDTH, w N/A BASIC DESIGN WIND SPEED, V 119 MPH WIND EXPOSURE CATEGORY B RISK CATEGORY III INTERNAL PRESSURE COEFFICIENT, GCpi +/-0.18 MWRFS DESIGN PRESSURE COEFFICIENT, qz N/A C&C DESIGN PRESSURE COEFFICIENT, qcc N/A SEISMIC IMPORTANCE FACTOR, Ie 1.25 Ss 0.15g S1 0.05g ASSUMED SOIL SITE CLASS D SDS 0.160g SD1 0.08g SEISMIC DESIGN CATEGORY B SEISMIC FORCE-RESISTING SYSTEM(S)N/A BASE SHEAR, V N/A SEISMIC RESPONSE COEFFICIENT, CS N/A RESPONSE MODIFICATION COEFFICIENT, R N/A RAIN INTENSITY, i DESIGN PARAMETERS 2.35 INCHES/HOUR ALLOWABLE STRESS DESIGN WIND SPEED 92 MPH SOIL DESIGN PRESSURE N/A ANALYSIS PROCEDURE N/A EXPOSURE FACTOR, Ce 1.0 SLOPE FACTOR, Cs N/ASNOW WINDSEISMICCORN E LL U N I V E R SI TYFOU N D E D 5681AD FACILITIES ENGINEERING ARCHIVE BAR CODEITHACA, NEW YORK ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 136 HOY ROAD RHODES HALL UPS REPLACEMENT S-001 11874770 GENERAL NOTES, ABBREVIATIONS, AND LEGEND Q. OLSEN QO 2051 APRIL 8, 2020 CODES 1. PERFORM ALL CONSTRUCTION IN ACCORDANCE WITH THE 2020 NEW YORK STATE BUILDING CODE AND CITY OF ITHACA AMENDMENTS REFERENCING THE FOLLOWING CODES AND STANDARDS: A. ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE B. ASCE7-16 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES WITH SUPPLEMENT NO. 1 C. 2018 INTERNATIONAL EXISTING BUILDING CODE (IEBC) D. 2018 INTERNATIONAL BUILDING CODE (IBC) DEFLECTION CRITERIA 1. GRAVITY LOAD DEFLECTION CRITERIA: A. TOTAL LOAD: L/240 B. LIVE LOAD: L/360 DESIGN LOADS 1.DEAD LOADS PER THE EXISTING DRAWINGS A. EXISTING CONCRETE ON METAL DECK: 77 PSF B. CEILING: 5 PSF C. MEP: 5 PSF D. 3”NORMAL WEIGHT CONCRETE TOPPING 38 PSF 2.ADDITIONAL DEAD LOADS: A. EXISTING STRUCTURAL STEEL FRAMING: 7 PSF 3.LIVE LOADS: A. THE ELECTRICAL ROOM HAS A LIVE LOAD RATING OF 150 PSF PER THE EXISTING DRAWINGS. SEE LIVE LOAD MAP FOR CHANGES. B. BATTERY CABINET: 4678 LBS (PER CABINET) C. UPS: 2150 LBS (PER UPS) D. SBM: 700 LBS STRUCTURAL STEEL 1. ALL STRUCTURAL STEEL SHALL BE ASTM FABRICATED AND ERECTED IN ACCORDANCE WITH AISC "STEEL CONSTRUCTION MANUAL" AND ALL WORK SHALL COMPLY WITH AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES." 2. GRADES OF STRUCTURAL STEEL TO BE PER TABLE THIS SHEET U.O.N. 3. ALL BOLTED CONNECTIONS TO BE MADE WITH A325 OR A490 TYPE N HIGH STRENGTH BOLTS UNLESS GALVANIZED BOLTS ARE SPECIFIED. WHERE GALVANIZED BOLTS ARE SPECIFIED ON THE DRAWINGS, GALVANIZED BOLTS SHALL CONFORM TO ASTM A153, CLASS C AND SHALL BE HOT-DIP GALVANIZED . 4. ALL NUTS SHALL MEET REQUIREMENTS OF ASTM A-563 DH OR ASTM A-194 2H. 5. ALL WASHERS SHALL MEET REQUIREMENTS OF ASTM F-436. 6. ALL BOLT HOLES IN STEEL MEMBERS SHALL BE 1/16" LARGER IN DIAMETER THAN THE NOMINAL SIZE OF THE BOLT USED, U.N.O. ON DRAWINGS. 7. WELDING SHALL MEET THE REQUIREMENTS OF OF THE "STRUCTURAL WELDING CODE" AWS D1.1-2006. ELECTRODES SHALL HAVE A MINIMUM TENSILE STRENGTH OF 70 KSI AND BE LOW-HYDROGEN TYPE. THE LENGTH OF WELD SPECIFIED ON THE DRAWINGS IS THE MINIMUM EFFECTIVE LENGTH OF THE WELD. ALL WELDS TO BE A MINIMUM 1/4" FILLET WELD U.N.O. ON DRAWINGS. 8. ALL INTERIOR STEEL SHALL BE PAINTED IN THE SHOP WITH DEVGUARD 4360 OR APPROVED EQUAL U.N.O. ON THE DRAWINGS. 9. ALL STEEL SHALL BE INSTALLED WITH CAMBER UP EXCEPT WHERE NOTED OTHERWISE ON DRAWINGS AND AT CANTILEVERS WHERE STEEL SHALL BE INSTALLED WITH CAMBER DOWN. 10. NO FABRICATION SHALL PROCEED PRIOR TO SHOP DRAWING APPROVAL. SHOP DRAWINGS MARKED "REJECTED" OR "REVISE AND RESUBMIT" MAY NOT BE FABRICATED WITHOUT ADDITIONAL CHANGES BEING MADE. 11. DEVELOPMENT OF STRUCTURAL STEEL SHOP DRAWINGS SHALL BE SUPERVISED BY A NEW YORK STATE-REGISTERED PROFESSIONAL ENGINEER AND SHALL INCLUDE DETAILS FOR APPLICATIONS AND ASSEMBLY OF ALL STRUCTURAL MEMBERS; INCLUDE DETAILS OF CUTS, CONNECTIONS, HOLES, AND OTHER PERTINENENT DATA; AND INDICATE WELDS BY STANDARD AWS 2.1 SYMBOLS SHOWING SIZE, LENGTH, AND TYPE OF EACH WELD. SHOP DRAWINGS SHALL BE SUBMITTED TO ARCHITECT FOR APPROVAL PRIOR TO FABRICATION. 12. SPLICING OF STRUCTURAL MEMBERS WHERE NOT DETAILED ON THE CONTRACT DOCUMENTS IS PROHIBITED WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER AS TO LOCATION, TYPE OF SPLICE, AND CONNECTION TO BE MADE. POST-INSTALLED ANCHORS 1. UNLESS NOTED OTHERWISE ON DRAWINGS, THE FOLLOWING EPOXIES ARE TO BE USED WITH THE FOLLOWING BASE MATERIALS FOR ADHESIVE ANCHORS: A. CAST IN PLACE AND PRECAST CONCRETE –HILTI HIT HY 200 R, POWERS AC200+, OR POWERS AC100+ GOLD B. CONCRETE MASONRY UNITS –HILTI HIT HY 270 OR POWERS AC100+ GOLD 2. EXPANSION ANCHORS TO BE STAINLESS STEEL. MANUFACTURER OF EXPANSION ANCHORS TO BE HILTI OR POWERS (DEWALT) OR APPROVED EQUAL. SUBMIT EXPANSION ANCHOR PRODUCT DATA FOR APPROVAL BY STRUCTURAL ENGINEER OF RECORD PRIOR TO INSTALLATION. TESTING & INSPECTIONS 1. OWNER SHALL RETAIN THE SERVICES OF AN INSPECTION AGENCY TO PERFORM THE FOLLOWING SERVICES. ADDITIONAL INSPECTIONS SHALL BE PROVIDED IN ACCORDANCE WITH LOCAL CODE REQUIREMENTS. 2. ALL NEW BOLTED CONNECTIONS SHALL BE VISUAL INSPECTED FOR CONFORMANCE WITH INDUSTRY STANDARDS FOR INSTALLTION AND FOR CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS. 3. ALL NEW STRUCTURAL WELDS MUST BE VISUALLY INSPECTED FOR CONFORMATIONS WITH INDUSTRY STANDARDS FOR INSTALLATION AND FOR CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS. IF THE WELDERS DO NOT HAVE AWS CERTIFICATION, ALL OF THE STRUCTURAL WELDS MUST BE TESTED WITH 100% MAGNETIC PARTICLE TESTING TO CONFIRM THE WELDS MEET THE MINIMUM STRENGTH REQUIREMENTS FOR THE CONNECTIONS. STRUCTURAL GENERAL NOTESLIVE LOAD MAP STRUCTURAL LEGEND 1 08/16/19 ISSUE FOR DD REVIEW 2 03/20/20 ISSUE FOR 95% REVIEW 3 05/05/20 ISSUE FOR COORDINATED REVIEW 4 04/08/20 ISSUE FOR CONSTRUCTION