HomeMy WebLinkAboutDrawings_Uris Hall Basement Lab Renovation INDEXEDCB
CB
CB
CB
CB CB
CB CB
CB CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CBCB
CB
CB
CB
CB
CB
CB
CB
CBCB
CBCB
CB
CB
CB
CB
CB
CB
CBCB
CBCB CB
CB
CB
CB
CB
CB
CB CB
SP
SP
SS
S
SIGN
MONUMENT PLATFORM
UP
UP
UP UP
UP
UP
UP UP
TOWER ROAD
URIS HALL
2087
EAST AVENUECAMPUS ROAD
B52
B50A
B48
B46
B44 B44A
B39A B39
B50
B00UF
B00UH
EXTERIOR ELEVATION
1
X-100
X-100
1
1 INTERIOR ELEVATION
1
X-100
SECTION MARKER
1
X-100 ENLARGED DETAIL
CONSTRUCTION KEYED NOTE
DEMOLITION KEYED NOTE
DRAWING REVISION NOTE
LINETYPE: TO BE PROVIDED / NEW
LINETYPE: DEMOLITION / TO BE RELOCATED
LINETYPE: EXISTING TO REMAIN
#
#
#
1
1
1
11
T-001 TITLE SHEET
ARCHITECTURAL
A-001 GENERAL NOTES, SYMBOLOGY, ABBREVIATIONS, CODE DATA AND EGRESS
PLAN
A-101 DEMOLITION AND RENOVATION FLOOR PLANS
A-102 DEMOLITION AND RENOVATION REFLECTED CEILING PLANS
MECHANICAL
M-001 MECHANICAL GENERAL NOTES AND SYMBOL LEGENDS
M-101 MECHANICAL DEMOLITION AND RENOVATION REFLECTED CEILING PLANS
M-501 MECHANICAL SCHEDULES
ELECTRICAL
E-001 ELECTRICAL NOTES, SYMBOL LEGEND, & ABBREVIATIONS
E-101 PARTIAL BASEMENT FLOOR ELECTRICAL PLAN
E-600 ELECTRICAL SCHEDULESCORNE
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
Cornell University
109 TOWER ROAD
URIS HALL
BASEMENT LAB
RENOVATION
T-001
12390202
TITLE SHEET
FE DESIGN
RLH
2087
JUNE 5, 2020
URIS HALL BASEMENT LAB RENOVATION
BUILDING CODE SUMMARYGENERAL SYMBOLS LEGEND
DRAWING INDEX
PROJECT SCOPE
THE PURPOSE OF THIS PROJECT IS TO RENOVATE EXISTING BASEMENT LEVEL SPACES WITHIN URIS HALL TO CREATE A NEW BSL2 (BIOSAFETY LEVEL 2)
CERTIFIABLE LAB AND ANCILLARY SPACES.
AREAS OF WORK INCLUDE:
*B52 (VIVARIUM, HOUSING AND TRANSFER) -REMOVAL AND REPLACEMENT OF HARD CEILING AS REQUIRED TO FACILITATE NEW MECHANICALS,
NEW HARD-DUCTED BIOSAFETY CABINET, AND STRUCTURAL SUPPORT FOR VENTILATED MOUSE CAGE RACKS.
*B50A (BSL2, VIVARIUM, SURGERY) -GAS SCAVENGING SURGICAL SNORKEL, REMOVAL AND REPLACEMENT OF HARD CEILING AS REQUIRED TO
FACILITATE NEW MECHANICALS, SURGICAL LAMP, NEW ELECTRICAL POWER.
*B48 (BSL2, VIVARIUM, PROCEDURES) -NEW ELECTRICAL POWER.
*B46, B44, B44A -NEW ELECTRICAL POWER.
*B39, B39A -REMOVAL AND REPLACEMENT OF HARD CEILING AS REQUIRED TO FACILITATE NEW MECHANICALS, OPTIONAL NEW ETHERNET,
NEW ELECTRICAL POWER.
PERSPECTIVE VIEWSITE LOCATION -URIS HALL
KEY PLAN -BASEMENT LEVEL
AREAS OF WORK
APPLICABLE CODES
2020 NYS BUILDING CODE
2020 NYS EXISTING BUILDING CODE
2020 NYS FIRE CODE
2020 NYS PLUMBING CODE
2020 NYS MECHANICAL CODE
2020 NYS ENERGY CONSERVATION CODE
2009 ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
2010 AMERICANS WITH DISABILITY ACT (ADA)
PROJECT SUMMARY
THIS PROJECT INCLUDES THE RENOVATION OF (514) SF OF (LAB SPACE &
MICROSCOPE ROOM). THE WORK IS ALTERATION LEVEL (2) (CITY OF
ITHACA).
ALTERATION LEVEL 2:
LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE,
THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE
RECONFIGURATION OR EXTENTION OF ANY SYSTEM, OR THE INSTALLATION
OF ANY ADDITIONAL EQUIPMENT.
AN EXISTING BUILDING OR PORTION THEREOF SHALL NOT BE ALTERED SUCH
THAT THE BUILDING BECOMES LESS SAFE THAN ITS EXISTING CONDITIONS.
BUILDING LIMITATIONS
CONSTRUCTION CLASSIFICATION:2B
CLASSIFICATION OF HAZARDS:NONE
HIGH-RISE BUILDING:NO
EXTINGUISHING REQUIREMENT:THE EXISTING SPACE WITHIN
THE BUILDING IS SPRINKLERED
OCCUPANCY
OCCUPANCY CLASSIFICATION:NON-SEPARATED MIXED
"HIGHER EDUCATION LABORATORY
SUITES" AND "BUSINESS (B)"
1 04/03/20 ISSUE FOR DD REVIEW
2 05/19/20 ISSUE FOR COORDINATED REVIEW
3 06/05/20 ISSUE FOR CONSTRUCTION
1B
UP
UP
UP UP
WALL -EXISTING
WALL -METAL STUD/ GWB
WALL -CONCRETE
WALL -CMU
WALL -BRICK
ITEMS FOR DEMOLITION
DOOR/ WALL -EXISTING
DOOR/ WALL -NEW
DOOR/ WALL -DEMOLITION
TAG -DOOR
TAG -WINDOW
TAG -WALL
TAG -ROOM #
CENTER LINE
PHOTO REFERENCE
LEVEL MARKER
COLUMN GRID MARKER
ELEVATION MARKER
ELEVATION CHANGE ARROWS
BREAK LINE
SYMBOLS
0' -0"
101
1t
X-X
X
2B00UA
CL
1
Name
Elevation
A101 1
1
1
0
DN
UP
ABBREVIATIONS
A
&AND
@ AT
ACT ACOUSTICAL CEILING TILE
ALT ALTERNATE
ALUM ALUMINUM
AVG AVERAGE
AFF ABOVE FINISH FLOOR
B
BD BOARD
BLDG BUILDING
BOD BOTTOM OF DECK
BSMT BASEMENT
C
CG CORNER GUARDS
CJ CONTROL JOINT
CLG CEILING
CL CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONT CONTINUOUS
CORR CORRIDOR
CPT CARPET
CRS COURSE(S)
CT CERAMIC TILE
D
DEMO DEMOLITION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DO DOOR OPENING
DWG DRAWING
E
EA EACH
EJ EXPANSION JOINT
ELEC ELECTRIC
ELEV ELEVATION/ ELEVATOR
EPDM RUBBER ROOF MEMBRANE
EQ EQUAL
EX'G EXISTING
EXT EXTERIOR
F
FD FLOOR DRAIN
FDN FOUNDATION
FEC FIRE EXTINGUISHER CABINET
FFE FINISH FLOOR ELEVATION
FRP FIBER REINFORCED POLYESTER
FT FOOT/FEET
FTG FOOTING
G
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERAL
GL GLASS
GWB GYPSUM WALL BOARD
H
HC HANDICAPPED
HT HEIGHT
HM HOLLOW METAL
HR HOUR
HVAC HEATING, VENTILATING & AC
J
JAN JANITOR
L
LAV LAVATORY
LB/#POUND
LGMF LIGHT GAGE METAL FRAMING
M
MFR MANUFACTURER
MAT MATERIAL
MAX MAXIMUM
MEZZ MEZZANINE
MIN MINIMUM
MO MASONRY OPENING
MTL METAL
N
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NR NOT RATED
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OSB ORIENTER STRAND BOARD
P
+/-PLUS OR MINUS
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
Q
QTY QUANTITY
R
R RISER
RD ROOF DRAIN
REF REFRIGERATOR
REQ REQUIRED
REV REVISION
RO ROUGH OPENING
RTU ROOF TOP UNIT
S
SHTG SHEATHING
SIM SIMILAR
SF SQUARE FOOT/ FEET
SS STAINLESS STEEL
STL STEEL
STD STANDARD
T
T TREAD
T&G TONGUE & GROOVE
TEL TELEPHONE
TEMP TEMPERATURE
TOS TOP OF STEEL
TV TELEVISION
TYP TYPICAL
U
UEV UNEVEN DOORS W/ VISION PANEL
UEF UNEVEN FLUSH DOOR
V
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
W
W/O WITHOUT
WD WOOD
B52
B50A
B48
B46
B44 B44A
B39A
B39
B50
B32
B00UF
B00UH
LEGEND
PATH OF EGRESS
2 HR FIRE RESISTANCE RATED
CONSTRUCTION
176'100'
162'
128'
118'
111'
99'
91'
80'
111'INDICATES MAX. TRAVEL
DISTANCE TO EXIT
AREA OF WORK
FUME HOOD CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
109 TOWER ROAD
URIS HALL
BASEMENT LAB
RENOVATION
A-001
12390202
GENERAL
NOTES,
SYMBOLOGY,
ABBREVIATIONS,
CODE DATA AND
EGRESS PLAN
R. HERKO
RLH
2087
JUNE 5, 2020
SCOPE OF WORK
1.0 REMOVE CEILING MATERIAL AND FRAMING AS REQUIRED TO INSTALL NEW
MECHANCIAL WORK
2.0 INSTALL NEW CEILING MATERIAL AND FRAMING.
3.0 PATCH & REPAIR CEILINGS WHERE LIGHTS REMOVED & NEW INSTALLED
4.0 TAPE, PRIME & PAINT NEW CEILING. PAINT EXISTING WALLS & CEILINGS.
GENERAL NOTES
1.0 DESIGN, CONSTRUCTION AND SAFETY SHALL CONFORM TO ALL LOCAL, STATE AND
OWNER SPECIFIC CODES, INCLUDING (BUT NOT LIMITED TO) THE NEW YORK STATE
UNIFORM FIRE PROTECTION AND BUILDING CODE, LATEST REVISION, THE NFPA 101
LIFE SAFETY CODE, LATEST REVISION, ANSI A117.1 - LATEST REVISION, OSHA, AND
ANY OTHER CODES GOVERNED BY THE JURISDICTION IN WHICH THIS PROJECT IS
BEING CONSTRUCTED.
2.0 THIS CONTRACT REQUIRES COMPLETE, FINISHED WORKABLE PROJECT OF THE
AREAS INDICATED BY THE CONTRACT DOCUMENTS, AND SHALL INCLUDE ALL
MATERIALS AND LABOR NECESSARY TO COMPLETE, REGARDLESS OF WHETHER OR
NOT ALL WORK OR EACH ITEM IS SPECIFICALLY INDICATED ON ANY OTHER
PORTION OF THE DRAWINGS AND / OR NOTES.
3.0 WHERE MATERIALS REFERENCED ON DRAWINGS, OR NECESSARY TO COMPLETE
THE WORK OF THIS CONTRACT ARE NOT SPECIFIED HEREIN, PROVIDE BEST
QUALITY MATERIALS. WHERE MATERIALS ARE INTENDED TO MATCH EXISTING,
PROVIDE CLOSEST POSSIBLE MATCH, SUBJECT TO OWNER'S APPROVAL. ALL ITEMS
AND WORK ON DRAWINGS ARE NEW, UNLESS INDICATED EXISTING. ALL WORK
WHICH HAS BEEN DAMAGED SHALL BE REPAIRED OR REPLACED AT NO COST TO
THE OWNER. WHERE ITEMS CAN NOT BE REPAIRED TO A ""NEW CONDITION"", OR
WHERE THE STRUCTURAL INTEGRITY HAS BEEN AFFECTED, ITEMS SHALL BE
REPLACED AT NO COST TO THE OWNER.
4.0 CONTRACTOR IS RESPONSIBLE TO VERIFY ALL SITE, FIELD AND BUILDING
CONDITIONS PRIOR TO SUBMITTING BIDS AND COMMENCING WORK. IF THERE ARE
ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS, NOTIFY THE
PROJECT MANAGER, WHO WILL REQUEST CLARIFICATION FROM THE
ARCHITECT/ENGINEER AND PROVIDE CLARIFICATION IN WRITING.
5.0 WHERE EXISTING CONSTRUCTION OR ITEMS HAVE BEEN INFILLED, REMOVED AND /
OR DISTURBED FOR INSTALLATION OF NEW WORK, CAUSING THE EXPOSURE OF
UNFINISHED AND/OR DAMAGED SURFACES RESULTING SURFACES AND INFILLED
SURFACES SHALL BE RECONSTRUCTED WITH MATERIALS TO MATCH FINISHED
AREAS. ALL ABANDONED OPENINGS (i.e. DUCT/PIPE REMOVALS, ETC.) AT WALLS,
ROOF OR FLOOR TO BE INFILLED SOLID.
6.0 WORK IS REQUIRED IN VARIOUS PORTIONS OF THE FACILITY TO EXECUTE WORK OF
OTHER TRADES (i.e. ELECTRICAL, MECHANICAL). ALTHOUGH NOT NECESSARILY
SHOWN ON DRAWINGS, WORK IS REQUIRED IN THESE AREAS CONSISTING OF
REMOVAL / REPLACEMENT OF CEILINGS, WALLS, FINISHES, PAVEMENT AND OTHER
CONSTRUCTION AS NECESSARY TO PERFORM WORK AND RESTORE THESE
SPACES OR AREAS TO ORIGINAL CONDITION.
7.0 GENERAL CONTRACTOR IS TO COORDINATE WORK OF ALL TRADES. SCHEDULE
WORK PROGRESS THROUGHOUT THE ENTIRE PROJECT TO PREVENT CONFLICTS
AND INTERFERENCES. OBTAIN ALL NECESSARY INFORMATION SUCH AS SIZES,
LOCATIONS, TEMPLATES, LAYOUT, DIMENSIONS AND ALL OTHER INFORMATION
NECESSARY FOR A PROPER AND WELL COORDINATED INSTALLATION. PRIOR TO
INSTALLATION OF ITEMS, VERIFY AND CONFIRM WITH EACH CONTRACTOR EXACT
LOCATION OF ALL ITEMS.
8.0 ALL PENETRATIONS (EXISTING OR NEW) THROUGH FLOORS AND FULL HEIGHT
WALLS - IN AREA OF WORK TO BE FIRE STOPPED. ALL GAPS AND JOINTS AT RATED
FLOORS, ROOFS AND WALLS TO BE FIRE & SMOKE STOPPED. GAPS AND JOINTS
INCLUDE (BUT ARE NOT LIMITED TO) TOP OF WALL TO FLOOR OR ROOF DECK, WALL
TO BEAMS, AND CONTROL OR EXPANSION JOINTS. FIRE STOPPING INCLUDES BOTH
FORM OR PACKING MATERIAL AND THE FILL, VOID OR CAVITY MATERIAL. PROVIDE
AND INSTALL LABELING REQUIRED BY CODE. LABELS SHALL INCLUDE
PENETRATION TYPE WITH UL LISTING USED, MATERIAL USED, DATE INSTALL AND
NAME OF INSTALLER.
9.0 JOBSITE WILL BE CLEANED DAILY AND DEBRIS REMOVED TO CONTAINERS OR TO
VEHICLE WHICH WILL REMOVE DEBRIS FROM CAMPUS. CONTAINERS WILL BE
REMOVED AS SOON AS FULL OR WHEN THE PROJECT HAS PROGRESSED TO A
POINT THAT A CONTAINER IS NO LONGER REQUIRED.
10.0 CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL AREAS USED TO BRING
SUPPLIES AND EQUIPMENT INTO THE PROJECT AREA. ANY DAMAGE TO AREAS
OUTSIDE THE PROJECT AREA INCLUDING BUT NOT LIMITED TO THE LOBBY AND
CORRIDOR SHALL BE REPAIRED AT NO COST TO THE OWNER.
SCALE:1/16" = 1'-0"1 BASEMENT LEVEL - CODE EGRESS PLAN
1 04/03/20 ISSUE FOR DD REVIEW
2 05/19/20 ISSUE FOR COORDINATED REVIEW
3 06/05/20 ISSUE FOR CONSTRUCTION
39A 39
B52
B50AB50
B48
B46
B44AB44
B52
B50AB50
B48
B46
B44AB44
BSC
CAGE
RACK
CAGE
RACK
1
2
A1
3
3
33
3
3
3
5' - 0"5' - 6"1' - 6"4 5
6
6
6
4
4 +/- 15' - 1"+/- 9' - 0"+/- 9' - 6"+/- 9' - 5"+/- 9' - 6"+/- 9' - 6"+/- 6' - 7 3/8"
+/- 8' - 7 3/8"+/- 6' - 0"
+/- 8' - 0"
39A 39
3 3
A-101 KEYED RENOVATION NOTES
1 NEW ANIMAL CAGE RACK SUPPLIED BY OWNER AND INSTALLED BY GENERAL
CONTRACTOR. GENERAL CONTRACTOR TO TRANSPORT NEW UNIT FROM LOADING
DOCK TO WORK AREA AND ASSEMBLE IF REQUIRED. CONNECTIONS TO
MECHANICAL DUCTWORK BY MECHANICAL CONTRACTOR (REFER TO MECHANICAL
DRAWINGS) AND ELECTRIC BY ELECTRICAL CONTRACTOR (REFER TO ELECTRICAL
DRAWINGS)
2 BIOSAFETY CABINET SUPPLIED BY OWNER AND INSTALLED BY GENERAL
CONTRACTOR. GENERAL CONTRACTOR TO TRANSPORT NEW UNIT FROM LOADING
DOCK TO WORK AREA AND ASSEMBLE IF REQUIRED. MECHANICAL CONTRACTOR
TO MAKE CONNECTIONS TO DUCTWORK (REFER TO MECHANICAL DRAWINGS) AND
ELECTRICAL CONNECTIONS BY ELECTRICAL CONTRACTOR (REFER TO ELECTRICAL
DRAWINGS).
3 GENERAL CONTRACTOR TO PREP AND PAINT ALL WALLS, DOOR FRAME AND
CEILING WITH BENJAMIN MOORE COROTECH PRE-CATALYSED WATERBORNE
EPOXY SEMI-GLOSS (V341) – COLOR WHITE. PROTECT EXISTING DOORS, WALL
BUMPER RAILS AND FLOORING.
4 ADA CLEARANCE AREA
5 ADA T-TURN CLEARANCE AREA
6 EXISTING METAL BUMPER RAIL TO REMAIN - TYP.
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
SCALE:1/4" = 1'-0"3 ROOM B39 - B39A DEMOLITION PLAN
SCALE:1/4" = 1'-0"1 ROOM B52 - B44A DEMOLITION PLAN
SCALE:1/4" = 1'-0"2 ROOM B52 - B44A RENOVATION PLAN
SCALE:1/4" = 1'-0"4 ROOM B39 - B39A RENOVATION PLAN CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
109 TOWER ROAD
URIS HALL
BASEMENT LAB
RENOVATION
A-101
12390202
DEMOLITION AND
RENOVATION
FLOOR PLANS
R. HERKO
EWK
2087
JUNE 5, 2020
1 04/03/20 ISSUE FOR DD REVIEW
2 05/19/20 ISSUE FOR COORDINATED REVIEW
3 06/05/20 ISSUE FOR CONSTRUCTION
1515VS
VS
VS
151515VS
15B52
B50A
B50
B46
B44AB44
1
1
B48
B52
B50A
B50
B48
B46
B44AB44
1
2
2
2
1
2
2
3
3
4
4 5
5
39A 39
11
39A 39
1 1 CORN E LL U N I V
E
R
SI
TYFOU
N
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
109 TOWER ROAD
URIS HALL
BASEMENT LAB
RENOVATION
A-102
12390202
DEMOLITION AND
RENOVATION
REFLECTED
CEILING PLANS
R. HERKO
EWK
2087
JUNE 5, 2020
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
SCALE:1/4" = 1'-0"1 ROOM B52 - B44A DEMOLITION REFLECTED CEILING PLAN
SCALE:1/4" = 1'-0"2 ROOM B52 - B44A RENOVATION REFLECTED CEILING PLAN
SCALE:1/4" = 1'-0"3 ROOM B39-39A DEMOLITION REFLECTED CEILING PLAN
SCALE:1/4" = 1'-0"4 ROOM B39-39A RENOVATION REFLECTED CEILING PLAN #
#A-102 KEYED DEMOLITION NOTES
1 REMOVE EXISTING HARD CEILING THROUGHOUT TO ACCESS MECHANICALS.
CONTRACTOR TO TAKE PRECAUTIONS NOT TO DAMAGE EXISTING SPRAY APPLIED
FIREPROOFING TO DECK ABOVE. ANY DAMAGE FROM REMOVALS WILL REQUIRE
REPAIR BY THE CONTRACTOR.
A-102 KEYED RENOVATION NOTES
1 NEW 5/8" GYPSUM WALL BOARD CEILING. TAPED, SPACKLED AND PAINTED.
COORDINATE NEW LIGHTING, MECHANICAL DIFFUSERS AND ACCESS PANELS.
PAINT CEILING WITH BENJAMIN MOORE COROTECH PRE-CATALYSED WATERBORNE
EPOXY SEMI-GLOSS (V341) – COLOR WHITE. PROTECT EXISTI
2 EXISTING CEILING TO BE PATCHED, AND REPAIRED WHERE LIGHTING FIXTURES
HAVE BEEN REMOVED. PAINT CEILING WITH BENJAMIN MOORE COROTECH
PRE-CATALYSED WATERBORNE EPOXY SEMI-GLOSS (V341) – COLOR WHITE.
PROTECT EXISTING DOORS, WALL BUMPER RAILS AND FLOORING.
3 GC/ MECHANICAL CONTRACTOR TO COORDINATE LOCATION OF NEW 24"x24"
ACCESS PANEL WITHIN REACH OF MANUAL BALANCING DAMPERS.
4 COORDINATE FIRE PROTECTION SPRINKLER HEADS / ESCUTHEONS WITH FIRE
PROTECTION WORK.
5 COORDINATE INSTALLATION OF SMOKE DETECTORS WITH CEILING WORK & FIRE
PROTECTION WORK.
DEMOLITION GENERAL NOTES:
DEMOLITION SCHEDULE SHOULD BE COORDINATED WITH CORNELL UNIVERSITY AND
CLASS SCHEDULES TO AVOID DISRUPTION OF STUDENTS AND TEACHERS. NO HEAVY
CONSTRUCTION SUCH AS BUT NOT LIMITED TO: CORE DRILLING, HAMMERING, BLOCK
REMOVAL, SANDING, GRINDING, SAW CUTTING, ETC. BETWEEN 9:00AM AND 5:00 PM ON
DAYS WHEN CLASSES ARE IN SESSION ABOVE OR BELOW WORK.
PATCH AND REPAIR WITH LIKE MATERIAL TO A SMOOTH FINISH AT ALL REMOVED LIGHTS,
ELECTRICAL BOXES, PIPING, HANGERS, MECHANICAL EQUIPMENT, EXISTING HOLES,
ETC.. SEE MECHANICAL, ELECTRICAL, AND PLUMBING DEMOLITION DRAWINGS. FIELD
VERIFY ALL EXISTING CONDITIONS @ FLOORS, WALLS, AND CEILINGS.
REMOVE ALL UNUSED OR ABANDONED CONDUIT, PIPING, HANGERS, CABLES,
ELECTRICAL BOXES, MECHANICAL EQUIPMENT, ETC. ON THE CEILINGS AND WALLS AND
COLUMNS, COORDINATE WITH CORNELL UNIVERSITY AND MECHANICAL, ELECTRICAL,
AND PLUMBING DEMOLITION DRAWINGS.
COORDINATE WITH ELECTRICAL, STRUCTURAL, AND PLUMBING DRAWINGS FOR
ADDITIONAL SAW CUTTING OF EXISTING CONCRETE SLAB, FOR CONDUIT, MECHANICAL
DUCTWORK, PIPING LINES ETC..
1 04/03/20 ISSUE FOR DD REVIEW
2 05/19/20 ISSUE FOR COORDINATED REVIEW
3 06/05/20 ISSUE FOR CONSTRUCTION
CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
109 TOWER ROAD
URIS HALL
BASEMENT LAB
RENOVATION
M-001
12390202
MECHANICAL
GENERAL NOTES
AND SYMBOL
LEGENDS
E. KOLACKI
EWK
2087
JUNE 5, 2020
MECHANICAL ABBREVIATIONS
BCU BLOWER COIL UNIT
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CC CLEAN CONDENSATE
CO CLEAN OUT
CS CLEAN STEAM
CD CONDENSATE DRAIN
EA EXHAUST AIR
EAG EXHAUST AIR GRILLE
FD FIRE DAMPER
GWR GLYCOL HEATING RETURN
GWS GLYCOL HEATING SUPPLY
HPR HIGH PRESSURE STEAM RETURN
HPS HIGH PRESSURE STEAM SUPPLY
HWR HOT WATER HEATING RETURN
HWS HOT WATER HEATING SUPPLY
LPC LOW PRESSURE CONDENSATE
LPS LOW PRESSURE STEAM
MU MAKE UP WATER
MPC MEDIUM PRESSURE CONDENSATE
MPS MEDIUM PRESSURE STEAM
NG NATURAL GAS
PCWR PROCESS CHILLED WATER RETURN
PCWS PROCESS CHILLED WATER SUPPLY
HG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
RAG RETURN AIR GRILLE
SA SUPPLY AIR
SAD SUPPLY AIR DIFFUSER
VD VOLUME DAMPER
MECHANICAL SYMBOLOGY
AIRFLOW
BACKFLOW PREVENTER
BALANCE VALVE
BALL VALVE
BOTTOM PIPE CONNECTION
BUTTERFLY VALVE
CAP OR PLUG
CHECK VALVE
CIRCULATING PUMP
DIRECTION OF FLOW
DUCT AIRFLOW
DUCT DOWN (EXHAUST OR RETURN)
DUCT DOWN (SUPPLY)
FIRE AND SMOKE DAMPER IN DUCT
FIRE DAMPER IN DUCT
FLANGE CONNECTION
FLEX CONNECTOR
FLEXIBLE CONNECTION
FLEXIBLE DUCT
FLOW METER
FLOW SWITCH
FUSIBLE LINK VALVE
GLOBE VALVE
MANUAL AIRVENT
ORIFICE METER
PIPE DOWN
PIPE UP
PIPING REDUCER (CONCENTRIC)
PIPING REDUCER (ECCENTRIC)
PRESSURE GAUGE
PRESSURE OR TEMPERATURE PETES PLUG
PRESSURE REDUCING VALVE
PRESSURE SWITCH
RECTANGULAR ELBOW
RECTANGULAR ELBOW WITH TURNING VANES
RELIEF VALVE
SMOKE DAMPER IN DUCT
SOLENOID VALVE
STANDARD BRANCH DUCT
STEAM TRAP
STRAINER (DUPLEX)
STRAINER WITH BLOWDOWN VALVE AND CAP
SUPPLY THROUGH NEXT FLOOR OR ROOF
TEMPERATURE WELL
THERMOMETER
THERMOMETER (DIAL)
TOP PIPE CONNECTION
TRIPLE DUTY VALVE
UNION CONNECTION
VACUUM BREAKER
VOLUME DAMPER IN DUCT
CONTROL SYMBOLOGY
2-WAY CONTROL VALVE, DIGITAL
2-WAY CONTROL VALVE, PNEUMATIC
3-WAY CONTROL VALVE, DIGITAL
3-WAY CONTROL VALVE, PNEUMATIC
ADDRESSABLE OUTPUT MODULE (FIRE ALARM INTERFACE)
AIRFLOW CONTROL VALVE (VENTURI OR VORTEX SHEDDING)
AVERAGING SENSOR
BINARY POINT
BUTTERFLY CONTROL DAMPER
CARBON DIOXIDE SENSOR
CONDENSATE SENSOR
CURRENT SENSOR
DEW-POINT SENSOR
DIFFERENTIAL PRESSURE SENSOR
DIFFERENTIAL PRESSURE SENSOR
ELECTRIC TO PNEUMATIC SWITCH
ELECTRIC TO PNEUMATIC TRANSDUCER
END SWITCH
FLOW ELEMENT (METER)
FLOW SENSOR
HIGH LEVEL SWITCH
HUMIDSTAT SENSOR
LIQUID IMERSION TEMPERATURE SENSOR
LOW LEVEL SWITCH
MODULATING
MOTOR
MOTOR STARTER
NETWORK COMMUNICATION POINT, BACnet MSTP
OCCUPANCY SENSOR
OPEN/CLOSE
OPPOSED BLADE CONTROL DAMPER
PARALLEL BLADE CONTROL DAMPER
PNEUMATIC THERMOSTAT
PRESSURE SENSOR
PRESSURE SWITCH
RELATIVE HUMIDITY SENSOR
RELAY
ROOM TEMPERATURE SENSOR WITH ADJUSTABLE
THERMOSTAT
ROOM TEMPERATURE SENSOR WITH OCCUPANCY
OVERRIDE
ROOM TEMPERATURE SENSOR WITH ON/OFF SWITCH
ROOM TEMPERATURE SENSOR WITH VISUAL DISPLAY
ROTATION DETECTOR
SINGLE POINT SENSOR
SMOKE DETECTOR
SPEED COMMAND
START/STOP
STATIC PRESSURE SENSOR
SWITCH
TEMPERATURE SENSOR
TEMPERATURE SENSOR
TEMPERATURE SENSOR WITH ADJUSTABLE SETPOINT
GENERAL DRAWING SYMBOLOGY
DEMOLISHED WORK
EXISTING PIPING TO REMAIN
EXISTING TO REMAIN
EXISTING WORK TO REMAIN
NEW WORK
POINT OF CONNECTION
POINT OF DISCONNECTION
CONTROL ABBREVIATIONS
AI ANALOG INPUT
AO ANALOG OUTPUT
AV ANALOG VALUE
BI BINARY INPUT
BO BINARY OUTPUT
BV BINARY VALUE
F.L. FAIL LAST
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
VFD VARIABLE FREQUENCY DRIVE
MECHANICAL SCOPE OF WORK
1.0 THIS PROJECT MODIFIES THE EXISTING HVAC SYSTEM TO ROOMS B48, B50, B50A
AND B52 TO PROVIDE BSL-1/2 PROCEDURE, SURGICAL, AND ANIMAL HOLDING
ROOMS.
2.0 OWNER WILL PROVIDE THE BIOLOGICAL SAFETY CABINET.
3.0 OWNER WILL PROVIDE THE CAGE RACK AND ACCESSORY SUPPLY AND EXHAUST
BLOWER PACKS.
4.0 WORK INCLUDES MODIFICATIONS TO THE DUCT, HYDRONIC PIPING AND CONTROL
SYSTEMS.
5.0 PROVIDE TEST AND BALANCE SERVICES.
MECHANICAL GENERAL NOTES
1.0 ALL DUCT DIMENSIONS INDICATED ARE IN INCHES, AND ARE INSIDE FREE AND
CLEAR DIMENSIONS.
2.0 PNEUMATIC TERMINATIONS:
IF COPPER: DEMO BACK TO MAIN AND PROVIDED SOLDERED END CAP
IF POLY: DEMO BACK TO MAIN AND PROVIDE BRASS PLUG
DO NOT USE SHEETMETAL SCREW OR BEND OVER END OF COPPER TUBE.
3.0 INSTALL EQUIPMENT TO ENSURE PROPER ACCESS TO CONTROL DEVICES AND
WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE AND REPAIR.
EQUIPMENT THAT IS NOT INSTALLED WITH THIS REQUIREMENT IN MIND SHALL BE
RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIES ARE
CORRECTED.
4.0 ALL SYSTEM TESTING SHALL BE CONDUCTED PRIOR TO INSULATION,
FIREPROOFING, AND ENCLOSURE IN SHAFTS. ANY RESTORATION WORK REQUIRED
AS A RESULT OF DISTURBING FINISHES OR STRUCTURE IN ORDER TO ACCESS
SYSTEMS REQUIRING REPAIR SHALL BE AT NO COST TO THE UNIVERSITY.
5.0 CUTTING AND PATCHING: THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
CUTTING, FITTING, AND PATCHING TO COMPLETE THE WORK. WHERE EXISTING
CONSTRUCTION IS REMOVED, CAUSING AN EXPOSURE OF UNFINISHED AND/OR
DAMAGED SURFACES, RESULTING SURFACES SHALL BE RECONSTRUCTED WITH
MATERIALS TO MATCH FINISHED AREAS.
6.0 ANY FIRESTOPPING DISTURBED DURING THE COURSE OF WORK SHALL BE
REPAIRED TO MAINTAIN A 2-HOUR FIRE RATING.
7.0 TESTING AND BALANCING: THE CONTRACTOR SHALL BALANCE ALL AIR SYSTEMS
AS INDICATED. SUBMIT RESULTS OF TESTING AND BALANCING ON STANDARD TAB
CONTRACTOR'S FORMS TO THE ENGINEER FOR REVIEW. SYSTEMS SHALL BE
BALANCED TO WITHIN +/- 10% OF DESIGN VALUES. FINAL BALANCING SHALL OCCUR
AFTER ALL LEAKS IN THE BUILDING ENVELOPE HAVE BEEN IDENTIFIED AND
SEALED.
8.0 SEAL ALL PIPE, GRILLE, DIFFUSER, DUCT, CONDUIT PENETRATIONS WITH
APPROPRIATE MATERIALS (CAULK, FOAM, ETC,) THAT ARE IMPENETRABLE TO THE
CONTAINED ORGANISMS AND WITHSTAND REPEATED DECONTAMINATIONS WITH
CLEANING AGENTS.
9.0 SPACES ARE DESIGNED FOR BSL-2 LEVELS. VERIFY THAT ALL PIPING, CONDUIT,
DUCTWORK AND OTHER WALL PENETRATIONS IN THE PROJECT AREA ARE
AIRTIGHT. SEAL ALL NON-COMPLIANT PENETRATIONS. PERFORM A GLYCOL
SMOKE TEST AFTER ALL PENETRATIONS ARE SEALED TO CONFIRM PROPER
AIRTIGHTNESS AND ROOM PRESSURIZATION.
10.0 THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT
OF SYSTEMS AND WORK INCLUDED IN THE CONTRACT. SPACE ABOVE THE
CEILINGS AND THE MECHANICAL ROOMS IS TIGHT. VERIFY ALL FIELD CONDITIONS
PRIOR TO SUBMITTING EQUIPMENT AND SHOP DRAWINGS. IF THERE ARE ANY
DESCREPANCIES BETWEEN THE DRAWINGS AND FIELD CONDITIONS, NOTIFY THE
PROJECT MANAGER FOR A CLARIFICATION PRIOR TO PROCEEDING WITH WORK.
11.0 THE EXISTING ALC SE6104 CONTOLLERS SERVING THE SPACES ARE LOCATED IN
MECHANICAL ROOM B00UJ. ALL REPLACEMENT AIR VALVES ARE TO RECONNECT
TO THE EXISTING CONTROLLERS. SEQUENCES OF OPERATION ARE EXISTING,
MODIFIED ONLY AS NEEDED TO PROGRAM NEW AIRFLOW SETPOINTS.
12.0 COORDINATE WITH THE GC FOR REMOVAL AND RESTORATION OF EXISTING HARD
CEILINGS NECESSARY TO ACCESS DUCTWORK ABOVE. PROVIDE NEW CEILING
MOUNTED ACCESS DOORS AS NEEDED TO REACH ALL BALANCING AND CONTROL
DEVICES. COORDINATE LOCATIONS WITH EXISTING FEATURES.
13.0 BALANCE ALL AIRFLOWS/WATERFLOWS IN THE WORK AREA TO THE FLOWS
INDICATED ON THE SCHEDULES.
14.0 DEMONSTRATE TO THE ENGINEER OF RECORD AND DESIGNATED OWNERS
REPRESENTATIVE ALL SEQUENCES OF OPERATION ARE CONTROLLING TO THE
DESIGN INTENT.
15.0 SCHEDULE A PRE-INSTALLATION MEETING TO REVIEW WITH THE OWNERS
REPRESENTATIVES FINAL EQUPIMENT LOCATIONS PRIOR TO INSTALLATION.
16.0 ALL DUCT DIMENSIONS INDICATED ARE IN INCHES, AND ARE INSIDE FREE AND
CLEAR DIMENSIONS.
17.0 THIS CONTRACT REQUIRES A COMPLETE, FINISHED, WORKABLE PROJECT WITHIN
THE AREAS INDICATED ON THE CONTRACT DOCUMENTS, AND SHALL INCLUDE ALL
LABOR, MATERIALS, EQUIPMENT AND SERVICES NECESSARY TO COMPLETE
INSTALLATION OF THE SYSTEMS INDICATED, REGARDLESS OF WHETHER OR NOT
ALL WORK OR EACH ITEM IS SPECIFICALLY INDICATED ON ANY PORTION OF THE
DRAWINGS AND/OR NOTES.
18.0 WHERE MATERIALS REFERENCED ON DRAWINGS, OR NECESSARY TO COMPLETE
THE WORK OF THIS CONTRACT ARE NOT SPECIFIED HEREIN, THEN ASSUME THAT
THE HIGHEST QUALITY MATERIALS ARE TO BE USED. APPROVAL SHALL BE GAINED
BY OWNERS AUTHORIZED AGENT PRIOR TO INSTALLATION OF SAID MATERIAL.
MECHANICAL SUBMITTAL SCHEDULE
SECTION TITLE REQUIRED
230000 HEATING, VENTILATING & AIR-CONDITIONING -
230523 GENERAL DUTY VALVES FOR HVAC PIPING PRODUCT DATA
230593 TESTING, ADJUSTING & BALANCING FOR HVAC QUALIFICATIONS, INSPECTION AND TEST REPORTS
230700 HVAC INSULATION PRODUCT DATA
230719 HVAC PIPING & EQUIPMENT INSULATION PRODUCT DATA
230900 INSTRUMENTATION & CONTROL FOR HVAC PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M,
SCHEMATIC CONTROL DIAGRAMS, ARCHITECTURE DIAGRAM,
SEQUENCES OF OPERATION, BILL OF MATERIALS, CONTROL
VALVE SCHEDULE
230920 ANALOG LABORATORY CONTROL PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M
232113 HYDRONIC PIPING PRODUCT DATA
233100 DUCTWORK PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M,
SHOP CONSTRUCTION STANDARDS, SHOP DRAWINGS
233300 AIR DUCT ACCESSORIES PRODUCT DATA
233700 AIR OUTLETS AND INLETS PRODUCT DATA
238200 TERMINAL HEATING AND COOLING UNITS PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M
1 04/03/20 ISSUE FOR DD REVIEW
2 05/19/20 ISSUE FOR COORDINATED REVIEW
3 06/05/20 ISSUE FOR CONSTRUCTION
B52
B50AB50
B48
B00UH
AV-S-B50
3
AV-S-B52 AV-S-B48
3 4
3
5
6
7
B52
B50AB50
B48
B00UH
AV-S-B50
3
AV-S-B52 AV-S-B48
4 5
6 7
VD
VD
9
11
12
13
9
VDVDVD14x8
6ø6ø12x8
14x6
14x6(E)14 15
14 15
14 151415
5
3
53
10
8
BSC
CAGE
RACK
CAGE
RACK
16
16
16
16
B00UF
2
AV-E-B50
AV-E-B48
1 2
AV-E-B52
1
B00UF
2
AV-E-B50
AV-E-B48
1 2
AV-E-B52
1
0' 4' 8'16'
SCALE: 1/8"=1'-0"CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
109 TOWER ROAD
URIS HALL
BASEMENT LAB
RENOVATION
M-101
12390202
MECHANICAL
DEMOLITION AND
RENOVATION
REFLECTED
CEILING PLANS
E. KOLACKI
EWK
2087
JUNE 5, 2020
SCALE:1/4" = 1'-0"1 ROOM B52-B44A MECHANICAL DEMOLITION RCP
SCALE:1/4" = 1'-0"2 ROOM B52-B44A MECHANICAL RENOVATION RCP
#
#
M-101 KEYED DEMOLITION NOTES
1 REMOVE EXHAUST AIR VALVE AND PREPARE DUCTWORK FOR INSTALLATION OF
NEW EXHAUST AIR VALVE.
2 DISCONNECT CONTROLS FROM AIR VALVE AND PERFORM WORK AS NEEDED TO
RECONNECT NEW AIR VALVE.
3 REMOVE SUPPLY AIR VALVE AND PREPARE DUCTWORK FOR INSTALLATION OF NEW
SUPPLY AIR VALVE.
4 REMOVE DUCT MOUNTED REHEAT COIL AND PIPING FIT-OUT COMPONENTS.
PREPARE FOR INSTALLATION OF NEW REHEAT COIL.
5 PREPARE EXHAUST DUCT FOR CONNECTION OF NEW SNORKEL EXHAUST.
6 REMOVE SUPPLY AIR DIFFUSER AND DUCTWORK TO POINT INDICATED. PREPARE
DUCTWORK FOR EXTENSION TO NEW SUPPLY AIR DIFFUSER.
7 REMOVE EXHAUST AIR GRILLE AND DUCTWORK TO POINT INDICATED. PREPARE
DUCTWORK FOR EXTENSION TO EQUIPMENT.
M-101 KEYED CONSTRUCTION NOTES
1 PROVIDE NEW EXHAUST AIR VALVE AND MAKE NECESSARY TRANSITIONS TO
CONNECT TO EXISTING DUCTWORK.
2 CONNECT NEW EXHAUST AIR VALVE TO EXISTING ZONE CONTROLLER.
RECONNECT THE FOLLOWING CONTROL POINTS- AO: EAV DAMPER COMMAND, AI:
EAV AIRFLOW FEEDBACK, AI: EAV DAMPER POSITION.
3 PROVIDE NEW SUPPLY AIR VALVE AND MAKE NECESSARY TRANSITIONS TO
CONNECT TO EXISTING DUCTWORK.
4 PROVIDE NEW REHEAT COIL AND MAKE NECESSARY TRANSITIONS TO CONNECT TO
EXISTING DUCTWORK AND CONTROL SYSTEM. PROVIDE A NEW DISCHARGE AIR
TEMPERATURE SENSOR AND RECONNECT THE FOLLOWING CONTROL POINTS- AO:
CONTROL VALVE COMMAND, AI: RHC DISCHARGE AIR TEMPERATURE.
5 CONNECT NEW SUPPLY AIR VALVE TO EXISTING ZONE CONTROLLER. RECONNECT
THE FOLLOWING CONTROL POINTS- AO: SAV DAMPER COMMAND, AI: SAV AIRFLOW
FEEDBACK, AI: SAV DAMPER POSITION.
6 PROVIDE NEDERMAN MODEL FX2-ORIG-D100-L2400-UP-LOW SNORKEL ARM (PART
NO 70605444). MOUNT TO DECK ABOVE CEILING WITH MECHANICAL EXPANSION
ANCHORS. COORDINATE SNORKEL ARM MOUNTING BRACKET AND HEIGHT IN FIELD
WITH OWNER AND EXISTING FEATURES LOCATED ABOVE THE CEILING PRIOR TO
SUBMITTAL AND INSTALLATION. SEAL PENETRATION THROUGH CEILING AIRTIGHT.
EXPECT TO RELOCATE AND PROVIDE OFFSETS IN EXISTING 14x6 EXHAUST DUCT AS
NEEDED TO FIND A CLEAR PATH TO THE DECK FOR THE BRACKET AND EXHAUST
DUCT. PROVIDE FOLLOWING ACCESSORIES:
-BRACKET KIT (PART NO 70377042)
-DUCT CONNECTOR (PART NO 70377040)
-CEILING COVER PLATE (PART NO 70502644
-COMBI HOOD (PART NO 70500144)
7 EXTEND 4-INCH ROUND EXHAUST DUCT TO BOTTOM OF EXISTING 14x6 EXHAUST
DUCT. PROVIDE 45 DEGREE TAP WITH VOLUME DAMPER AT CONNECTION TO MAIN.
8 EXTEND 14x6 DUCT AS INDICATED. PROVIDE A 45 DEGREE TAP WITH VOLUME
DAMPER ON BOTTOM OF DUCT AND EXTEND 12” ROUND DUCT TO NEW SUPPLY AIR
DIFFUSER.
9 PROVIDE 6” DUCT CONNECTION AT CAGE RACK THIMBLE CONNECTION. EXTEND TO
NEW BRANCH AND PROVIDE VOLUME DAMPER.
10 CONNECT TO EXISTING 12x8 DUCT AND IMMEDIATELY ROLL DOWN UNDER
ADJACENT EXHAUST DUCT, TRANSITIONING TO 14X8.
11 CONNECT 10-INCH ROUND TO BSC THIMBLE CONNECTION BELOW CEILING. EXTEND
UP TO NEW 14x8 DUCT. PROVIDE 14x8 LOW LEAKAGE DAMPER TO BE USED TO
BALANCE AIRFLOW (BOD RUSKIN CD50 OPPOSED BLADE LOW PROFILE)
12 ROLL UP DUCT TO MAKE FINAL CONNECTION.
13 INSTALL EXHAUST DUCT VOLUME DAMPERS SO THAT THEY CAN BE REACHED
WITHIN ONE 24x24 ACCESS PANEL.
14 ENSURE ALL PENETRATIONS ARE AIRTIGHT. SEAL ALL NON-COMPLIANT
PENETRATIONS. PERFORM GLYCOL SMOKE TEST TO CONFIRM PROPER
AIRTIGHTNESS AND ROOM PRESSURIZATION.
15 BALANCE ALL AIRFLOWS/ WATERFLOWS TO THE FLOWS INDICATED ON SCHEDULE
SHEET M-501.
16 COORDINATE WITH GENERAL CONTRACTOR FOR WORK TO RESTORE HARD
CEILING.
SCALE:1/4" = 1'-0"3 ROOM B00UF MECHANICAL DEMOLITION RCP
SCALE:1/4" = 1'-0"4 ROOM B00UF MECHANICAL RENOVATION RCP
1 04/03/20 ISSUE FOR DD REVIEW
2 05/19/20 ISSUE FOR COORDINATED REVIEW
3 06/05/20 ISSUE FOR CONSTRUCTION
CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
109 TOWER ROAD
URIS HALL
BASEMENT LAB
RENOVATION
M-501
12390202
MECHANICAL
SCHEDULES
E. KOLACKI
EWK
2087
JUNE 5, 2020DUCTWORK AND ACCESSORIES SCHEDULE
DUCT
SERVICE LOCATION PRESSURE
CLASS
SEAL
CLASS
LEAKAGE CLASS DUCT
MATERIAL
DUCT
LINING
INSULATION
FINISH
RECT ROUND MIN R-VALUE MATERIAL FIELD JACKET
VAPOR
RETARDER
SUPPLY CONNECTION TO MAIN, AIR VALVE INLET, MECHANICAL ROOM 6" POS A 6 3 A NONE R-6 W NONE YES NONE
SUPPLY AIR VALVE OUTLET, MECHANICAL ROOM, ABOVE CEILINGS 2" POS A 6 3 A NONE R-6 W NONE YES NONE
EXHAUST AIR VALVE INLET, MECHANICAL ROOM, ABOVE CEILINGS 3" NEG A 6 3 A NONE N/A N/A NONE NO NONE
EXHAUST AIR VALVE OUTLET, CONNECTION TO MAIN, MECHANICAL ROOM 6" NEG A 6 3 A NONE N/A N/A NONE NO NONE
AIR BALANCE SCHEDULE
ROOM
NUMBER
ROOM DIMENSIONS DESCRIPTION CURRENT FUTURE NOTESAREA (SF) HEIGHT (FT)SA (CFM) EA (CFM) XFER (CFM) ACH SA (CFM) EA (CFM) XFER (CFM) ACH
B48 129 8 CAGE RACK 1 0 45 43.3 0 45 43.3 1,3,4,5
CAGE RACK 2 0 45 0 45
BSC 0 655 0 655
BS 2 HOLDING - TOTAL 545 745 -200 545 745 -200
B50 57 8 FROM B00CH 100 0 N/A 100 0 N/A 8
FROM B48 0 100 0 100
FROM B50A 100 0 0 100
FROM B52 0 100 0 100
FROM CENTRAL SYSTEM 0 100 200 0
BSL2 ANTE ROOM - TOTAL 200 200 0 300 300 0
B50A 82 8 SNORKEL ARM 0 120 20.1 0 120 22.4 1,2
GENERAL EXHAUST 0 0 0 125
BSL1(2) SURGERY 220 120 100 145 245 -100
B52 134 8 BSL2 PROCEDURE 280 480 -200 26.9 280 480 -200 26.9 1,6
NOTES:
1.NEGATIVE TRANSFER (XFER) INDICATES A NEGATIVELY PRESSURIZED ROOM. POSITIVE TRANSFER (XFER) INDICATES A POSITIVELY PRESSURIZED ROOM.
2.SURGERY WILL BE UNDER BSL1 INITIALLY, WITH CONVERSION TO BSL2 IN FUTURE.
3.BIOLOGICAL SAFETY CABINET WILL BE CLASS II, TYPE A2, THIMBLE CONNECTED TO EXHAUST SYSTEM.
4.CAGE RACK EXHAUST BLOWERS TO BE THIMBLE CONNECTED TO EXHAUST SYSTEM.
5.AIR CHANGES EXCEED THE RECOMMENDED 10-15 MINIMUM DUE TO BSC.
6.THE NIH RECOMMENDS A MINIMUM VENTILATION RATE OF 15 ACH IN ANIMAL PROCEDURE ROOMS. EXPECTED COOLING LOAD EXCEEDS THE ACH REQUIREMENTS.
7.THE NIH RECOMMENDS A MINIMUM VENTILATION RATE OF 20 ACH IN ANIMAL SURGICAL ROOMS.
8.THE 100 CFM "SUPPLY AIR" FROM B00CH IS WHAT IS MAINTAINING THE ANTE ROOM NEGATIVE TO THE CORRIDOR.
REGISTER, GRILLE, AND DIFFUSER SCHEDULE
UNIT NO SERVES BOD MFR BOD MODEL AIRFLOW CFM PANEL SIZE NECK SIZE TYPE MATERIAL MOUNTING FINISH NOTES
SAD-1 B48 KRUEGER TADSS 545 24" x 48" 12"Ø RADIAL FLOW DIFFUSER STAINLESS STEEL DUCT MOUNT WHITE 90º AIR PATTERN
LABORATORY AIRFLOW CONTROL DEVICE SCHEDULE
UNIT NO SERVES SUPPLY EXHAUST BOD MFR BOD MODEL SIZE
BASC SETPOINTS FACTORY RANGE MIN ΔPt (IN
WC)DAMPER POSITION NOTESMAX (CFM) MIN (CFM) MAX (CFM) MIN (CFM)
AV-S-B48 BSL2 HOLDING X ACCUTROL AVC6308-05-ISW 1-8 545 545 800 0 0.3 N.O. 2,3,4
AV-E-B48 BSL2 HOLDING X ACCUTROL AVC6310-05-SW 1-10 745 745 1300 0 0.3 N.O. 2,3
AV-S-B50 BSL1 SURGERY / ANTE ROOM X ACCUTROL AVC6308-05-ISW 1-8 345 220 800 0 0.3 N.O. 1,2,3,4
AV-E-B50 BSL1 SURGERY / ANTE ROOM X ACCUTROL AVC6308-05-SW 1-8 245 120 800 0 0.3 N.O. 1,2,3
AV-S-B52 BSL2 PROCEDURE X ACCUTROL AVC6308-05-ISW 1-8 280 280 800 0 0.3 N.O. 2,3,4
AV-E-B52 BSL2 PROCEDURE X ACCUTROL AVC6308-05-SW 1-8 480 800 800 0 0.3 N.O. 2,3
NOTES:
1.THE BACS SETPOINTS ARE MEANT TO REPRESENT MAX/MIN FOR CURRENT AND FUTURE AIRFLOWS FOR THE PURPOSES OF SELECTION THE PROPER AIR VALVE. THESE AIR VALVES ARE NOT TO BE
PROGRAMMED FOR VARIABLE FLOW. REFER TO THE AIR BALANCE SCHEDULE FOR INITIAL AIRFLOW SETPOINTS.
2.ALL VALVES TO BE 316 STAINLESS STEEL CONSTRUCTION.
3.PROVIDE TIGHT SHUT OFF.
4.PROVIDE INSULATION.
REHEAT COIL SCHEDULE
TAG SERVES
COIL SIZE TOTAL
CAPACITY
(BTUH)
AIR SIDE WATER SIDE
W (IN) H (IN)
FLOW RATE
(CFM)
ENT AIR TEMP
(ºF)
LVG AIR TEMP
(ºF)
PRESSURE
DROP (IN WC)
FLOW RATE
(GPM)
ENT WATER
TEMP (ºF)
LVG WATER
TEMP (ºF)
PRESSURE DROP
(FT WC)
BALANCE
VALVE
CONTROL
VALVE
RHC-5 B48 12 12 12949 545 55 77 0.15 MAX 0.9 130 100 2.0 MAX NOTE 9 NOTE 10
NOTES:
1.ACCEPTABLE MANUFACTURERS: AEROFIN, CARRIER, HEATCRAFT, McQUAY, TEMTROL, TRANE.
2.RATINGS: ARI 410, INDUSTRY STANDARD FOR FORCED CIRCULATION AIR COOLING AND AIR HEATING COILS
3.FINS: ALUMINUM, 10 FPI MAXIMUM
4.HEADERS: NON-FERROUS CONSTRUCTION
5.FRAME: STAINLESS STEEL
6.COIL SHALL BE PIPED IN COUNTERFLOW ARRANGEMENT.
7.PIPING SHALL BE ARRANGED TO ALLOW SERVICE AND MAINTENANCE.
8.SPACE IN THE MECHANICAL ROOM IS TIGHT. VERIFY EXISTING CONDITIONS PRIOR TO SUBMITTAL.
9.BALANCE VALVE: BELL&GOSSETT CB SERIERS, CB 3/4
10.CONTROL VALVE: BELIMO CCV-B210 TF24-SR US, 1/2-INCH VALVE SIZE, 1.2 CV, 2-WAY MODULATING CONTROL, SPRING RETURN NORMALLY CLOSED
11.INSTALL LEVEL AND PLUMB PER MANUFACTURER'S RECOMMENDED INSTRUCTIONS AND SMACNA STANDARDS.
HVAC PIPE AND FITTING SCHEDULE AND SPECIFICATIONS
PIPE SERVICE ABBREVIATION PIPE SIZE PIPE MATERIAL FITTINGS JOINTS
INSULATION FINISHTHICK (IN) MATERIAL FIELD JACKET VAPOR RETARDER
HEATING HOT WATER: 105 - 200 ˚F HWS&R 1-1/4" & BELOW A AA,AB A1,A2 1.5 MFG-1 NONE NO NONE
SPECS:
1.PIPING MATERIALS
A: ASTM B88 TYPE L COPPER
2.FITTINGS
AA: ASME B16.22 WROUGHT COPPER SOLDER
AB: ASME B16.22 WROUGHT COPPER VIEGA PRESS SEAL
3.JOINING MATERIALS
A1: ASTM B2 SOLDER, LEAD FREE, 95 Su / 5 Sb OR 95.5 Sn / 4 Cu / 0.5 Ag
A2: EPDM SEAL
DIELECTRIC FITTINGS: USE FLANGES OR COUPLINGS.
4.INSULATION, ASTM E84 MAX FLAME-SPREAD INDEX OF 25; MAX SMOKE-DEVELOPED INDEX OF 50
MFG-1: PRE-FORMED MINERAL FIBERGLASS, ASTM C547 TYPE I, ASTM C1136, ASJ-SSL, K-VALUE OF 0.25-0.29 @ 125F MEAN TEMP
5.PIPING ACCESSORIES
UNIONS: PROVIDE ADJACENT TO VALVES AND EQUIPMENT TO ALLOW SERVICE AND MAINTENANCE WITHOUT NEEDING A SYSTEM SHUTDOWN.
ISOLATION VALVES: TWO-PIECE BRONZE BALL WITH 316SS BALL AND STEM. APOLLO 70-140/240; NIBCO T/S-580-70-66, WATTS B6000/6001-SS
PRESSURE/ TEMPERATURE TEST PORTS: TRERICE D3770, EPDM (NORDEL) SEAT
STRAINERS: WYE-PATTERN WITH NIPPLE AND BALL VALVE IN BLOWDOWN CONNECTION. PROVIDE AT INLET OF CONTROL VALVES.
AIR VENTS: BELL&GOSSETT MODEL 87. PROVIDE AT ALL HIGH POINTS IN PIPING SYSTEM AND COIL CONNECTIONS.
DRAIN VALVES: INSTALL AT ALL LOW POINTS OF PIPING SYSTEM AND COIL CONNECTIONS.
6.PIPE LABELS: PRINTED PLASTIC WITH CONTACT-TYPE, PERMANENT ADHESIVE BACKING AND DIRECTIONAL ARROWS
SPECS:
1.COMPLY WITH SMACNA HVAC DUCT CONSTRUCTION STANDARDS
2.DUCT MATERIALS
A: ASTM A653, G90 GALVANIZED SHEET STEEL
3.FITTINGS: PER SMACNA HVAC DUCT CONSTRUCTION STANDARDS
RECTANGULAR ELBOWS: TYPE RE1 RADIUS ELBOW, TYPE RE2 SQUARE THROAT ELBOW WITH VANES
ROUND ELBOWS: MINIMUM R/D = 1
BRANCH CONNECTIONS/TAPS: 45 DEGREE ENTRY
4.SEALANTS: UL723 MAX FLAME-SPREAD INDEX OF 25; MAX SMOKE-DEVELOPED INDEX OF 50
5.ACCESSORIES
MANUAL VOLUME DAMPERS: WITH LOCKING HAND QUANDRANT HANDLE, PROVIDE AT BRANCH CONNECTIONS/TAPS
ACCESS DOORS: SUITABLE FOR PRESSURE CLASS AND INSULATION THICKNESS. PROVIDE ON BOTH SIDES OF COIL.
6.INSULATION, ASTM E84 MAX FLAME-SPREAD INDEX OF 25; MAX SMOKE-DEVELOPED INDEX OF 50
W: FLEXIBLE GLASS FIBER WRAP, ASTM C553, FSK JACKET WITH KRAFT VAPOR BARRIER FACING, K-VALUE OF 0.22 -0.29 BTU-IN/HR-FT²-˚F @ 75 ˚F, 0.75 PCF
1 04/03/20 ISSUE FOR DD REVIEW
2 05/19/20 ISSUE FOR COORDINATED REVIEW
3 06/05/20 ISSUE FOR CONSTRUCTION
ABBREVIATIONS
A - AMPERE
AFC - ABOVE FINISHED CEILING
AFF - ABOVE FINISHED FLOOR
AIC - AMPS INTERRUPTING CAPACITY
BLDG - BUILDING
C - CONDUIT
CKT - CIRCUIT
CL - CENTERLINE
DWG - DRAWING
E - EXISTING TO REMAIN
EC - ELECTRICAL CONTRACTOR
EM - EMERGENCY
EMT - ELECTRICAL METALLIC TUBING
FVNR - FULL VOLTAGE NON-REVERSING
G - GROUND
GC - GENERAL CONTRACTOR
GFI - GROUND FAULT INTERRUPTER
JB - JUNCTION BOX
KVA - KILOVOLTAMPERES
KW - KILOWATT
MC - MECHANICAL CONTRACTOR
MCB - MAIN CIRCUIT BREAKER
MDP - MAIN DISTRIBUTION PANEL
MLO - MAIN LUG ONLY
P - POLE
PH - PHASE
PVC - POLYVINYL CHLORIDE
R - REMOVE
RE - REPLACE EXISTING
REL - RELOCATED
RI - REMOVE AND REINSTALL
RL - RELOCATE EXISTING
RM - ROOM
UTV - UNDERVOLTAGE TRIP
V - VOLT
W - WIRE
WP - WEATHER PROOF
XFMR - TRANSFORMER
ELECTRICAL NOTES
1. ALL WORK SHALL BE PERFORMED AND INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF THE CORNELL UNIVERSITY ELECTRICAL
STANDARDS. THE NATION ELECTRIC CODE(NFPA 70) AND ANY GOVERNING CODES AND STANDARDS HAVING JURISDICTION.
2. REFER TO CORNELL UNIVERSITY ELECTRICAL STANDARDS FOR ALL SPECIFICATION REQUIREMENTS.
3. ALL EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH ARTICLE 250 OF THE NATIONAL ELECTRIC CODE.
4. CONTRACTORS SHALL PAY FOR AND SECURE ALL PERMITS AND UNDERWRITERS CERTIFICATES.
5. PRIOR TO BID, THE CONTRACTOR SHALL VISIT THE SITE TO FAMILIARIZE HIMSELF WITH THE EXISTING FIELD CONDITIONS. HIS BID SHALL
INCLUDE THE FURNISHING AND INSTALLATION OF ALL LABOR, TOOLS, MATERIAL, EQUIPMENT, SERVICES AND RELATED ACCESSORIES
NECESSARY FOR THE COMPLETE INSTALLATION OF THE ELECTRICAL WORK SHOWN ON THE DRAWINGS AND REQUIRED BY CODE.
6. THE ELECTRICAL CONTRACTOR SHALL FURNISH ALL METERS, INSTRUMENTS, CABLE CONNECTION, EQUIPMENT, OR APPARATUS ESSAY FOR
MAKING ALL TESTS.
7. THE CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL EQUIPMENT AND SYSTEMS AGAINST HARMFUL EXPOSURE OR ACCUMULATION OF
DUST/MOISTURE, CORROSION OR OTHER FORMS OF DAMAGE. CLEAN AND RESTORE DAMAGED FINISHES.
8. CONTRACTOR SHALL COORDINATE PROJECT WORK WITH ALL TRADES AND ASSIST IN SCHEDULING WITH ALL TRADES.
9. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, PATCHING, AND REFINISHING OF WORK AREA RELATED TO ELECTRICAL PROJECT
WORK. RESTORE AREA TO ORIGINAL CONDITION.
10. CONTRACTOR IS RESPONSIBLE FOR REMOVAL OF ALL WASTE MATERIALS IN A LAWFUL MANNER AND LEAVE THE SITE FREE OF ALL DEBRIS.
11. THE TERM "PROVIDE" DENOTES TO FURNISH AND INSTALL.
12. THE TERM "WIRING" DENOTES WRING AND RACEWAY.
13. UNLESS OTHERWISE NOTED, WHERE A DEVICE OR WIRING IS REMOVED, THE CONTRACTOR SHALL DISCONNECT AND REMOVE THE
ASSOCIATED WIRING AND CONTROLS.
14. WHERE A DEVICE IS RELOCATED, DISCONNECT, REMOVE AND STORE THE NOTED DEVICE. EXISTING WIRING SHALL REMAIN. PROVIDE
RELOCATION OF DEVICE PER CONSTRUCTION SCHEDULE. RECONNECT TO EXISTING WIRING. EXTEND WIRING AS REQUIRED, MATCH EXISTING.
15. THE CONTRACTOR IS RESPONSIBLE FOR MAINTAINING SERVICE TO THE BALANCE OF ANY EXISTING CIRCUITS THAT ARE AFFECTED BY THIS
PROJECT AND THAT EXTEND OUT OF THE PROJECT AREA. EXTEND WIRING AS REQUIRED, MATCH EXISTING.
16. COORDINATE ALL DEMOLITION WORK WITH CORNELL UNIVERSITY PRIOR TO ANY SHUTDOWNS OR REMOVAL OF DEVICES AND/OR WIRING.
17. COORDINATE ALL COMMUNICATIONS WORK WITH CORNELL UNIVERSITY I/T GROUP.
18. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COMPLETING A PANEL WALK DOWN FOR EACH PANEL BEING AFFECTED FOR THIS PROJECT
TO DETERMINE REQUIREMENTS AND COORDINATE SHUTDOWNS WITH CORNELL UNIVERSITY.
ELECTRICAL SYMBOLS LEGEND
SYMBOL DESCRIPTION
RECEPTACLE
QUADRUPLEX RECEPTACLE
GFCI RECEPTACLE
J JUNCTION BOX
THREE WAY SWITCH
OCCUPANY SENSOR
3
OS OCCUPANY SENSOR
RED LIGHT SWITCH
R
2" X 4' LIGHT FIXTURE
2' x 2' LIGHT FIXTURE
ROUND RED LENSED LIGHT FIXTURE
R
HEAT DETECTOR
135
H
SMOKE DETECTOR
FIRE ALARM HORN
FIRE ALARM PULL STATION
DATA OUTLET
F
LS LIGHT LEVEL SENSOR
BUILDING WIRE AND CABLE
A. PROVIDE PRODUCTS AS FOLLOWS:
1. SOLID CONDUCTOR FOR FEEDERS AND BRANCH CIRCUITS 10 AWG AND SMALLER.
2. STRANDED CONDUCTORS FOR CONTROL CIRCUITS.
3. CONDUCTOR NOT SMALLER THAN #12 AWG FOR POWER AND LIGHTING CIRCUITS.
4. CONDUCTOR NOT SMALLER THAN #16 AWG FOR CONTROL CIRCUITS.
5. 10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS LONGER THAN 75 FEET.
6. 10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS LONGER THAN 200 FEET.
B. WIRING METHODS: PROVIDE THE FOLLOWING WIRING METHODS:
1. CONCEALED DRY INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN INSULATION, IN
RACEWAY.
2. ABOVE ACCESSIBLE CEILINGS: USE ONLY BUILDING WIRE, TYPE THHN/THWN INSULATION, IN RACEWAY.
3. WET OR DAMP INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN INSULATION, IN
RACEWAY.
4. UNDERGROUND LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN INSULATION, IN RACEWAY.
C. WIRE AND CABLE ROUTING INDICATED IS APPROXIMATE UNLESS DIMENSIONED. INCLUDE WIRE AND CABLE
LENGTHS WITHIN 10 FT OF LENGTH SHOWN.
D. COMPLETELY AND THOROUGHLY SWAB RACEWAY BEFORE INSTALLING WIRE.
E. NEATLY TRAIN AND LACE WIRING INSIDE BOXES, EQUIPMENT, AND PANELBOARDS.
F. SPECIAL TECHNIQUES--BUILDING WIRE IN RACEWAY:
1. PULL CONDUCTORS INTO RACEWAY AT SAME TIME.
2. INSTALL BUILDING WIRE 4 AWG AND LARGER WITH PULLING EQUIPMENT.
G. SPECIAL TECHNIQUES - CABLE:
1. PROTECT EXPOSED CABLE FROM DAMAGE.
2. SUPPORT CABLES ABOVE ACCESSIBLE CEILING, USING SPRING METAL CLIPS OR CABLE TIES TO SUPPORT
CABLES FROM STRUCTURE OR CEILING SUSPENSION SYSTEM. DO NOT REST CABLE ON CEILING PANELS.
3. USE SUITABLE CABLE FITTINGS AND CONNECTORS.
H. SPECIAL TECHNIQUES - DIRECT BURIAL CABLE:
1. TRENCH AND BACKFILL FOR DIRECT BURIAL CABLE INSTALLATION. INSTALL WARNING TAPE ALONG ENTIRE
LENGTH OF DIRECT BURIAL CABLE, WITHIN 3 INCHES OF GRADE.
2. USE SUITABLE DIRECT BURIAL CABLE FITTINGS AND CONNECTORS.
I. SPECIAL TECHNIQUES - WIRING CONNECTIONS:
1. CLEAN CONDUCTOR SURFACES BEFORE INSTALLING LUGS AND CONNECTORS.
2. MAKE SPLICES, TAPS, AND TERMINATIONS TO CARRY FULL AMPACITY OF CONDUCTORS WITH NO
PERCEPTIBLE TEMPERATURE RISE.
3. TAPE UNINSULATED CONDUCTORS AND CONNECTORS WITH ELECTRICAL TAPE TO 150 PERCENT OF
INSULATION RATING OF CONDUCTOR.
4. INSTALL SPLIT BOLT CONNECTORS OR MULTI-TAP BLOCKS FOR COPPER CONDUCTOR SPLICES AND TAPS, 6
AWG AND LARGER.
5. INSTALL SOLDERLESS PRESSURE CONNECTORS WITH INSULATING COVERS FOR COPPER CONDUCTOR
SPLICES AND TAPS, 8 AWG AND SMALLER.
6. INSTALL INSULATED SPRING WIRE CONNECTORS WITH PLASTIC CAPS FOR COPPER CONDUCTOR SPLICES
AND TAPS, 10 AWG AND SMALLER.
7. TERMINATE EXISTING ALUMINUM CONDUCTORS WITH TIN-PLATED, ALUMINUM-BODIED COMPRESSION
CONNECTORS ONLY. FILL WITH ANTI-OXIDANT COMPOUND BEFORE INSTALLING CONDUCTOR.
8. INSTALL SUITABLE REDUCING CONNECTORS OR MECHANICAL CONNECTOR ADAPTORS FOR CONNECTING
ALUMINUM CONDUCTORS TO COPPER CONDUCTORS.
J. GROUND CONDUCTORS:
1. FOR 6 AWG AND SMALLER: GREEN.
2. FOR 4 AWG AND LARGER: IDENTIFY WITH GREEN TAPE AT BOTH ENDS AND VISIBLE POINTS INCLUDING
JUNCTION BOXES.
K. ALL WIRING SHALL BE #12 CU UNLESS SPECIFIED OTHERWISE.
ELECTRICAL SPECIFICATIONS
A. ALL ELECTRICAL WORK TO CONFORM TO:
1. NFPA 70 (NATIONAL ELECTRIC CODE) - CURRENT VERSION
2. NECA (NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION) - STANDARD OF INSTALLATION
3. NETA ATS (INTERNATIONAL ELECTRICAL TESTING ASSOCIATION) - ACCEPTANCE TESTING SPECIFICATIONS
FOR ELECTRICAL POWER DISTRIBUTION EQUIPMENT AND SYSTEMS.
4. NFPA 72 (NATIONAL FIRE PROTECTION ASSOCIATION - NATIONAL FIRE ALARM CODE).
5. ALL APPLICABLE LOCAL CODES.
B. ALL WORK SHOWN ON THIS DRAWING IS THE RESPONSIBILITY OF THE CONTRACTOR, UNLESS CLEARLY
INDICATED AS PART OF ANOTHER PRIME CONTRACT.
C. PROVIDE TEMPORARY POWER REQUIRED FOR ALL TRADES.
D. MATCH OWNERS EXISTING STANDARD EQUIPMENT.
E. COORDINATE WORK TO MINIMIZE OUTAGE DURATION.
F. OBTAIN ALL REQUIRED PERMITS & INSPECTIONS.
G. PROVIDE FOR ELECTRICAL INSPECTIONS AND SUBMIT REPORTS TO THE OWNER.
H. SUBMIT O&M MANUALS TO OWNER UPON COMPLETION OF WORK.
I. PROVIDE TRAINING SESSION FOR DESIGNATED MAINTENANCE PERSONNEL.
J. PROVIDE SUBMITTALS FOR ALL ELECTRICAL EQUIPMENT, EXCLUDING WIRE, CONDUIT, AND FASTENERS.
1. HANDHOLES.
2. PANELBOARDS - SHOP DRAWINGS (INDICATE OUTLINE AND SUPPORT POINT DIMENSIONS, VOLTAGE, MAIN
BUS AMPACITY, INTEGRATED SHORT CIRCUIT AMPERE RATING, CIRCUIT BREAKER AND FUSIBLE
SWITCH ARRANGEMENT AND SIZES) AND CATALOG DATA SHOWING SPECIFIED FEATURES OF STANDARD
PRODUCTS.
3. ENCLOSED SWITCHES - SWITCH RATINGS AND ENCLOSURE DIMENSIONS.
4. DEVICES - MANUFACTURER'S CATALOG INFORMATION SHOWING DIMENSIONS, COLORS, AND
CONFIGURATIONS.
5. LUMINAIRES (INCLUDING EMERGENCY & EXIT FIXTURES) - CATALOG INFORMATION SHOWING DIMENSIONS,
RATINGS, AND PERFORMANCE DATA.
K. SELECT MATERIALS, SIZES, AND TYPES OF ANCHORS, FASTENERS, AND SUPPORTS TO CARRY LOADS OF
EQUIPMENT AND RACEWAY, INCLUDING WEIGHT OF WIRE AND CABLE IN RACEWAY.
GROUNDING SYSTEMS
A. GROUNDING SYSTEM RESISTANCE: 25 OHMS.
B. GROUNDING SYSTEMS:
1. MECHANICAL CONNECTORS: BRONZE CONNECTORS, SUITABLE FOR GROUNDING AND BONDING
APPLICATIONS, IN CONFIGURATIONS REQUIRED FOR PARTICULAR INSTALLATION.
C. EXOTHERMIC CONNECTIONS: EXOTHERMIC MATERIALS, ACCESSORIES, AND TOOLS FOR PREPARING AND MAKING
PERMANENT FIELD CONNECTIONS BETWEEN GROUNDING SYSTEM COMPONENTS.
D. WIRE: STRANDED COPPER.
E. GROUNDING ELECTRODE CONDUCTOR: SIZE TO MEET NFPA 70 AND LOCAL MUNICIPALITY REQUIREMENTS.
F. INSTALLATION:
1. EQUIPMENT GROUNDING CONDUCTOR: INSTALL SEPARATE, INSULATED CONDUCTOR WITHIN EACH FEEDER
AND BRANCH CIRCUIT RACEWAY. TERMINATE EACH END ON SUITABLE LUG, BUS, OR BUSHING.
2. DO NOT FASTEN SUPPORTS TO PIPES, DUCTS, MECHANICAL EQUIPMENT, OR CONDUIT.
3. OBTAIN PERMISSION FROM ARCHITECT/ENGINEER BEFORE USING POWDER-ACTUATED ANCHORS OR
DRILLING OR CUTTING STRUCTURAL MEMBERS.
HANGERS AND SUPPORTS
A. ANCHORS & FASTENERS TO BE CORROSION RESISTANT.
B. ANCHOR AND FASTEN ELECTRICAL PRODUCTS TO BUILDING ELEMENTS AND FINISHES AS FOLLOWS:
1. CONCRETE STRUCTURAL ELEMENTS: PROVIDE EXPANSION ANCHORS.
2. STEEL STRUCTURAL ELEMENTS: PROVIDE BEAM CLAMPS AND SPRING STEEL CLIPS.
3. CONCRETE SURFACES: PROVIDE EXPANSION ANCHORS.
4. HOLLOW MASONRY, PLASTER, AND GYPSUM BOARD PARTITIONS: PROVIDE TOGGLE BOLTS AND HOLLOW
WALL FASTENERS.
5. SOLID MASONRY WALLS: PROVIDE EXPANSION ANCHORS.
6. SHEET METAL: PROVIDE SHEET METAL SCREWS.
7. WOOD ELEMENTS: PROVIDE WOOD SCREWS.
C. SUPPORTS:
1. FABRICATE SUPPORTS FROM STRUCTURAL STEEL OR FORMED STEEL MEMBERS. RIGIDLY WELD MEMBERS
OR INSTALL HEXAGON HEAD BOLTS TO PRESENT NEAT APPEARANCE WITH ADEQUATE
STRENGTH AND RIGIDITY. INSTALL SPRING LOCK WASHERS UNDER NUTS.
2. INSTALL SURFACE MOUNTED CABINETS AND PANELBOARDS WITH MINIMUM OF FOUR ANCHORS.
3. IN WET AND DAMP LOCATIONS INSTALL STEEL CHANNEL SUPPORTS TO STAND CABINETS AND
PANELBOARDS 1 INCH OFF WALL.
4. INSTALL SHEET METAL CHANNEL TO BRIDGE STUDS ABOVE AND BELOW CABINETS AND PANELBOARDS
RECESSED IN HOLLOW PARTITIONS.
EXISTING WORK
A. PRIOR TO CONSTRUCTION & INSTALLATION, CONTRACTOR TO VERIFY EXISTING CONDITIONS AND NOTIFY
ARCHITECT/ENGINEER OF CONFLICTS OR CONDITIONS WHICH INTERFERE WITH INSTALLATION AS SET FORTH IN
CONTRACT DOCUMENTS.
B. CONTRACTOR RESPONSIBLE FOR ALL NEW FLOOR OPENINGS, EXCAVATIONS, AND PENETRATIONS,UNLESS
SPECIFICALLY NOTED. UNLESS SPECIFICALLY NOTED, UPON COMPLETION, ALL PENETRATIONS TO BE
SEALED TO MAINTAIN FIRE RATING AS SPECIFIED ON ARCHITECTURAL DRAWINGS.
C. ALL CUTTING AND PATCHING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR, UNLESS CLEARLY INDICATED
AS PART OF ANOTHER PRIME CONTRACT.
D. COORDINATE ANY NEW ROOF PENETRATIONS WITH THE OTHER TRADES.
E. REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE NEW CONSTRUCTION.
F. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND EXTENSION WORK.
G. MAINTAIN ACCESS TO EXISTING BOXES AND OTHER INSTALLATIONS REMAINING ACTIVE AND REQUIRING ACCESS.
MODIFY INSTALLATION OR PROVIDE ACCESS PANEL.
H. EXTEND EXISTING RACEWAY AND BOX INSTALLATIONS USING MATERIALS AND METHODS COMPATIBLE WITH
EXISTING ELECTRICAL INSTALLATIONS, OR AS SPECIFIED.
I. CLEAN AND REPAIR EXISTING COMPONENTS TO REMAIN OR TO BE REINSTALLED.
J. PROVIDE ACCESS TO EXISTING WIRING CONNECTIONS REMAINING ACTIVE AND REQUIRING ACCESS. MODIFY
INSTALLATION OR INSTALL ACCESS PANEL.
K. EXTEND EXISTING CIRCUITS USING MATERIALS AND METHODS COMPATIBLE WITH EXISTING ELECTRICAL
INSTALLATIONS, OR AS SPECIFIED.
L. RING OUT CIRCUITS IN EXISTING PANEL AFFECTED BY THE WORK. WHERE ADDITIONAL CIRCUITS ARE NEEDED,
REUSE CIRCUITS AVAILABLE FOR REUSE. INSTALL NEW BREAKERS.
M. TAG UNUSED CIRCUITS AS SPARE AND SWITCH BREAKER TO THE "OFF" POSITION.
N. WHERE EXISTING CIRCUITS ARE INDICATED TO BE REUSED, USE SENSING MEASURING DEVICES TO VERIFY
CIRCUITS FEEDING PROJECT AREA OR ARE NOT IN USE.
O. PROVIDE NEW UPDATED DIRECTORIES WHERE MORE THAN THREE CIRCUITS HAVE BEEN MODIFIED OR REWIRED.
P. IDENTIFY SALVAGE ITEMS IN COOPERATION WITH OWNER. REMOVE AND PROTECT ITEMS TO BE SALVAGED AND
TURN OVER TO OWNER.
Q. CAREFULLY REMOVE EQUIPMENT, MATERIALS, OR FIXTURES WHICH ARE TO BE REUSED.
MINOR ELECTRICAL DEMOLITION
A. DEMOLITION DRAWINGS ARE BASED ON CASUAL FIELD OBSERVATION AND EXISTING RECORD DOCUMENTS.
REPORT DISCREPANCIES TO ARCHITECT/ENGINEER BEFORE DISTURBING EXISTING INSTALLATION.
B. CEASE OPERATIONS IMMEDIATELY WHEN STRUCTURE APPEARS TO BE IN DANGER AND NOTIFY
ARCHITECT/ENGINEER. DO NOT RESUME OPERATIONS UNTIL DIRECTED.
C. VERIFY WIRING AND EQUIPMENT INDICATED TO BE DEMOLISHED SERVE ONLY ABANDONED FACILITIES.
D. PROVIDE TEMPORARY EGRESS SIGNAGE AND EMERGENCY LIGHTING.
E. DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS SCHEDULED FOR REMOVAL. REMOVE
CONDUIT, WIRE, BOXES, AND FASTENING DEVICES TO AVOID ANY INTERFERENCE WITH NEW INSTALLATION.
F. INSTALL TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING
CONSTRUCTION.
G. REMOVE EXPOSED ABANDONED WIRE, CABLE, CONDUIT, GROUNDING AND BONDING COMPONENTS, FASTENERS
AND SUPPORTS, AND ELECTRICAL IDENTIFICATION COMPONENTS, INCLUDING ABANDONED COMPONENTS
ABOVE ACCESSIBLE C CEILING FINISHES. CUT EMBEDDED CONDUITS AND SUPPORT ELEMENTS FLUSH WITH
WALLS AND FLOORS. PATCH SURFACES DAMAGED BY REMOVAL OF EXISTING COMPONENTS.
H. DISCONNECT ABANDONED CIRCUITS AND OUTLETS AND REMOVE ABANDONED RACEWAY, OUTLETS, BOXES,
WIRE, AND CABLE INCLUDING ABOVE ACCESSIBLE CEILING FINISHES. CUT RACEWAY FLUSH WITH WALLS AND
FLOORS, AND PATCH SURFACES. REMOVE CONCEALED ABANDONED RACEWAY TO ITS SOURCE.
I. RECONNECT EQUIPMENT BEING DISTURBED BY RENOVATION WORK AND REQUIRED FOR CONTINUED SERVICE TO
NEAREST AVAILABLE PANEL. REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE
NEW CONSTRUCTION.
J. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND EXTENSION WORK.
K. CLEAN AND REPAIR EXISTING EQUIPMENT TO REMAIN (AFFECTED BY THE SCOPE OF THE PROJECT) OR TO BE
REINSTALLED.
L. PROTECT AND RETAIN POWER TO EXISTING ACTIVE EQUIPMENT REMAINING.
M. CAP ABANDONED EMPTY CONDUIT AT BOTH ENDS AND MARK AS SPARE.
RACEWAY AND BOXES
A. PROVIDE RACEWAY AND BOXES LOCATED AS INDICATED, AND AT OTHER LOCATIONS REQUIRED FOR SPLICES,
TAPS, WIRE PULLING, EQUIPMENT CONNECTIONS, AND COMPLIANCE WITH REGULATORY REQUIREMENTS.
RACEWAY AND BOXES ARE SHOWN IN APPROXIMATE LOCATIONS UNLESS DIMENSIONED. PROVIDE RACEWAY
TO COMPLETE WIRING SYSTEM.
B. UNDERGROUND MORE THAN 5 FEET OUTSIDE FOUNDATION WALL: PROVIDE SCHEDULE 80 PVC. PROVIDE CAST
METAL BOXES OR NONMETALLIC HANDHOLES WHERE REQUIRED.
C. UNDERGROUND WITHIN 5 FEET FROM FOUNDATION WALL: PROVIDE RIGID STEEL CONDUIT OR THICKWALL
NONMETALLIC CONDUIT (SCHEDULE 80 PVC). PROVIDE CAST METAL OR NONMETALLIC BOXES.
D. IN OR UNDER SLAB ON GRADE: PROVIDE THICK WALL NONMETALLIC CONDUIT. PROVIDE CAST OR NONMETALLIC
METAL BOXES.
E. OUTDOOR LOCATIONS, ABOVE GRADE: PROVIDE RIGID STEEL CONDUIT. PROVIDE CAST METAL OR NONMETALLIC
OUTLET, PULL, AND JUNCTION BOXES.
F. IN SLAB ABOVE GRADE: PROVIDE THICKWALL NONMETALLIC CONDUIT. PROVIDE CAST NONMETALLIC BOXES.
G. WET AND DAMP LOCATIONS: PROVIDE THICKWALL NONMETALLIC CONDUIT. PROVIDE CAST METAL OR
NONMETALLIC OUTLET, JUNCTION, AND PULL BOXES. PROVIDE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS.
H. CONCEALED DRY LOCATIONS: PROVIDE ELECTRICAL METALLIC TUBING. PROVIDE SHEET-METAL BOXES. PROVIDE
FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS. PROVIDE HINGED ENCLOSURE FOR LARGE PULL BOXES.
I. MINIMUM RACEWAY SIZE: 3/4 INCH UNLESS OTHERWISE SPECIFIED.
J. ARRANGE RACEWAY AND BOXES TO MAINTAIN HEADROOM AND PRESENT NEAT APPEARANCE. GROUP RELATED
RACEWAY; SUPPORT USING CONDUIT RACK; PROVIDE SPACE ON EACH FOR 25 PERCENT ADDITIONAL RACEWAYS.
K. RACEWAY ROUTING IS SHOWN IN APPROXIMATE LOCATIONS UNLESS DIMENSIONED. ROUTE TO COMPLETE
WIRING SYSTEM.
L. DO NOT SUPPORT RACEWAY WITH WIRE, PERFORATED PIPE STRAPS, CEILING SUPPORT WIRES OR OTHER
PIPING SYSTEMS.
M. ROUTE EXPOSED & ABOVE ACCESSIBLE CEILINGS RACEWAY PARALLEL AND PERPENDICULAR TO WALLS.
N. DO NOT CROSS CONDUITS IN SLAB.
O. INSTALL NO MORE THAN EQUIVALENT OF THREE 90 DEGREE BENDS BETWEEN BOXES. INSTALL CONDUIT BODIES
TO MAKE SHARP CHANGES IN DIRECTION, AS AROUND BEAMS. INSTALL FACTORY ELBOWS FOR BENDS IN METAL
CONDUIT LARGER THAN 2 INCH SIZE.
P. AVOID MOISTURE TRAPS; INSTALL JUNCTION BOX WITH DRAIN FITTING AT LOW POINTS IN CONDUIT SYSTEM.
Q. INSTALL FITTINGS TO ACCOMMODATE EXPANSION AND DEFLECTION WHERE RACEWAY CROSSES SEISMIC,
CONTROL AND EXPANSION JOINTS.
R. INSTALL SUITABLE PULL STRING OR CORD IN EACH EMPTY RACEWAY EXCEPT SLEEVES AND NIPPLES.
S. CLOSE ENDS AND UNUSED OPENINGS IN WIREWAY.
T. INSTALL PULL BOXES AND JUNCTION BOXES ABOVE ACCESSIBLE CEILINGS AND IN UNFINISHED AREAS ONLY.
U. IN ACCESSIBLE CEILING AREAS: INSTALL OUTLET AND JUNCTION BOXES NO MORE THAN 6 INCHES FROM CEILING
ACCESS PANEL OR FROM REMOVABLE RECESSED LUMINAIRE.
V. LOCATE FLUSH MOUNTING BOX IN MASONRY WALL TO REQUIRE CUTTING OF MASONRY UNIT CORNER ONLY.
COORDINATE MASONRY CUTTING TO ACHIEVE NEAT OPENING.
W. DO NOT INSTALL FLUSH MOUNTING BOX BACK-TO-BACK IN WALLS; INSTALL WITH MINIMUM 6 INCHES SEPARATION.
INSTALL WITH MINIMUM 24 INCHES SEPARATION IN ACOUSTIC RATED WALLS.
X. DO NOT FASTEN BOXES TO CEILING SUPPORT WIRES OR OTHER PIPING SYSTEMS.
Y. SUPPORT BOXES INDEPENDENTLY OF CONDUIT.
Z. USE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS.
AA. SET FLOOR BOXES LEVEL AND FLUSH WITH FINISH FLOORING MATERIAL
AB. INSTALL CONDUIT TO PRESERVE FIRE RESISTANCE RATING OF PARTITIONS AND OTHER ELEMENTS.
AC. ROUTE CONDUIT THROUGH ROOF OPENINGS FOR PIPING AND DUCTWORK OR THROUGH SUITABLE ROOF JACK WITH
PITCH POCKET
AD. ALIGN ADJACENT WALL MOUNTED OUTLET BOXES FOR SWITCHES, THERMOSTATS, AND SIMILAR DEVICES.
WALL PLATES
A. MANUFACTURERS:
1. PASS & SEYMOUR LEGRAND.
2. TAYMAC 20510 (WEATHERPROOF-IN-USE).
3. HUBELL (BELL/RACO).
4. LEVITON.
5. GENERAL ELECTRIC.
B. INSTALL DECORATIVE PLATES ON SWITCH, RECEPTACLE, AND BLANK OUTLETS IN FINISHED AREAS. DECORATIVE COVER
PLATE: NYLON.
C. INSTALL JUMBO SIZE PLATES FOR OUTLETS INSTALLED IN MASONRY WALLS. JUMBO COVER PLATE: NYLON.
D. WEATHERPROOF COVER PLATE (RECEPTACLE): IMPACT RESISTANT PLASTIC PLATE WITH HINGED AND GASKETED DEVICE
COVER. COVER TO BE RATED FOR WET LOCATION WHILE IN USE, AND TO BE LOCKABLE.
E. WEATHERPROOF COVER PLATE (SWITCH): GASKETED CAST METAL PLATE WITH HINGED AND GASKETED DEVICE COVER OR
LEVER SWITCH MECHANISM. (P&S CA-31G/HUBBELL/BELL/RACO 5125 OR EQUAL)
F. KITCHEN AREAS: 302/430 STAINLESS STEEL, WEATHERPROOF FOR STARTUPS.
G. INSTALL GALVANIZED (STAMPED) STEEL PLATES ON OUTLET BOXES AND JUNCTION BOXES IN UNFINISHED AREAS, ABOVE
ACCESSIBLE CEILINGS, AND ON SURFACE MOUNTED OUTLETS.
H. INSTALL DEVICES PLUMB AND LEVEL.
I. INSTALL SWITCHES WITH OFF POSITION DOWN.
J. INSTALL RECEPTACLES WITH GROUNDING POLE ON TOP, OR TO THE LEFT (IF MOUNTED HORIZONTALLY.
K. CONNECT WIRING DEVICE GROUNDING TERMINAL TO OUTLET BOX WITH BONDING JUMPER AND BRANCH CIRCUIT
EQUIPMENT GROUNDING CONDUCTOR.
L. CONNECT WIRING DEVICES BY WRAPPING SOLID CONDUCTOR AROUND SCREW TERMINAL. INSTALL STRANDED
CONDUCTOR FOR BRANCH CIRCUITS 10 AWG AND SMALLER. WHEN STRANDED CONDUCTORS ARE USED IN LIEU OF SOLID,
USE CRIMP ON FORK TERMINALS FOR DEVICE TERMINATIONS. DO NOT PLACE BARE STRANDED CONDUCTORS DIRECTLY
UNDER DEVICE SCREWS.
M. ADJUST DEVICES AND WALL PLATES TO BE FLUSH AND LEVEL.CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
109 TOWER ROAD
URIS HALL
BASEMENT LAB
RENOVATION
E-001
2200272.03
ELECTRICAL
NOTES, SYMBOL
LEGEND, &
ABBREVIATIONS
RDH
MPS
2087
06/05/2020
CEX
^^
ELSIOR
^^^^^^
077 4 2 5L
E
D
ESNECI
FORP ROISS LAN EENIGNERANDYD.HE
A
RDSTATE O F NEW
Y
ORK
B 15VS
VS
VS
B 1515VS
15Room
B48
Room
B50A
Room
B50
Room
B52
BOOCH1212
Room
B52
Room
B50A
Room
B50
Room
B48
BOOCH1212
30
LPE-M-BA
LS
LS
LS
+60 AFF
A2 A2
A2
A2
A2
A2A2 A3
A3
32
LPE-M-BA
Room
39A
Room
39
BOOCH
1212
Room
39
Room
39A
BOOCH
1212LS
A2 A3 A2 A2
34
LPE-M-BA
GENERAL DRAWING NOTES:
CONTRACTOR TO TRACE OUT EXISTING CIRCUITS AND UPDATE PANEL SCHEDULES ACCORDINGLY.
ELECTRICAL CONTRACTOR RESPONSIBLE FOR COMPLETING A PANEL WALK DOWN FOR EACH PANEL BEING
AFFECTED FOR THIS PROJECT TO DETERMINE REQUIREMENTS AND COORDINATE SHUTDOWNS.
UNLESS OTHERWISE NOTED, EXISTING CONDITIONS ARE SHOWN IN GRAYSCALED, DEMOLITION WORK IS
SHOWN IN BOLD AND DASHED, PROJECT WORK SHOWN IN BOLD. PROVIDE NEW WORK AS SHOWN.
CONTRACTOR TO PROVIDE, TEST, AND TERMINATE ALL NETWORK DROPS IDENTIFIED AS NEW WORK. PROVIDE
(2) CONNECTIONS AT EACH FACEPLATE. ALL NETWORK WIRING TO RUN TO CLOSET LOCATED IN ROOM
G30(REFER TO KEYPLANS)
PROVIDE RECESSED BOXES AND RACEWAYS IN NEW WALL.
ALL NEW WIRING AND DEVICES TO BE INSTALLED RECESSED TO FACILITATE WASH DOWN. ALL NEW
RECEPTACLES TO BE WEATHER PROOF AND GASKETED COVERS.
CONTRACTOR TO MATCH EXISTING RECEPTACLE HEIGHT UNLESS OTHERWISE NOTED.
A.
B.
C.
D.
E.
F.
G.
B22 B24
B20 B26
B39 B39A
B48
B50A
B52
B50
B55
DISCONNECT EXISTING LIGHT FIXTURES. SAVE CIRCUIT AND WIRING TO RE-CONNECT TO NEW
LIGHT FIXTURES.
DISCONNECT EXISTING LIGHT LEVEL CONTROL SENSOR. SAVE WIRING TO RE-CONNECT TO NEW
LIGHTING CONTROL SENSOR.
1
DEMOLITION KEYED NOTES:
TYPICAL ALL SHEETS," KEYNOTES ARE COMMON FOR ALL SHEETS" EACH KEYNOTE MAY NOT APPEAR
IN PLANS ON EVERY SHEET.
2
1
2
KEYED NOTES:
TYPICAL ALL SHEETS," KEYNOTES ARE COMMON FOR ALL SHEETS" EACH KEYNOTE MAY NOT APPEAR
IN PLANS ON EVERY SHEET.
3
EXTEND WIRING TO CONNECT TYPE A2 FIXTURES TO EXISTING SWITCHING AND CIRCUITING.
PROVIDE ADDITIONAL SWITCH FOR TYPE A3 VIVARIUM FIXTURES AND CONNECT TO EXISTING
CIRCUIT.
PROVIDE RECEPTACLES FOR SURGERY LIGHT.
PROVIDE NEW LIGHTING SENSOR (KELE-MK7-B-CCF-0/5) AND TIE BACK TO EXISTING SYSTEM TO
MAINTAIN EXISTING CONTROL SCHEME.
1/4" = 1'-0"E-101
1 PARTIAL BASEMENT ELECTRICAL REMOVAL PLAN B48, B50, B50A, B52
1/4" = 1'-0"E-101
2 PARTIAL BASEMENT ELECTRICAL PLAN B48, B50, B50A, B52
N N
0'2'4'8'0'2'4'8'
1/4" = 1'-0"E-101
4 PARTIAL BASEMENT ELECTRICAL REMOVAL PLAN B39,B39A
1/4" = 1'-0"E-101
5 PARTIAL BASEMENT ELECTRICAL PLAN B39, B39A
N
0'2'4'8'
N
0'2'4'8'
1" = 30'-0"E-101
3 ELECTRICAL PANEL KEY PLAN
N
AREA OF WORK
AREA OF WORK
AREA OF WORK
APBK
APBD
LPE-M-BA
APBC
2
1 1
2
1
1
1
2
2
2
1
13
1
3
1
3
APS-BA
APS-BB
1
1 CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
109 TOWER ROAD
URIS HALL
BASEMENT LAB
RENOVATION
E-101
2200272.03
PARTIAL
BASEMENT
FLOOR
ELECTRICAL
PLAN
NOT USED
MPS
2087
06/05/2020
3
CEX
^^
ELSIOR
^^^^^^
077 4 2 5L
E
D
ESNECI
FORP ROISS LAN EENIGNERANDYD.HE
A
RDSTATE O F NEW
Y
ORKA3
34
LPE-M-BA
1
3
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
PANEL NAME: LPE-M-BA
LOCATION: XXXXX
RATING: 225A
MAIN: 225A MLO
ELECTRICAL PANEL SCHEDULE
LPE-M-BA
SERVICE: 120/208V/3PH/4W
MOUNTING: RECESSED
FEED: XXXXX
kAIC RATING: XXXXX
CKT LOAD DESIGNATION
BREAKER
TRIP/POLES
LOAD
WATTS PHASE CKTLOAD
WATTS
BREAKER
TRIP/POLES LOAD DESIGNATION
LIGHTING CORRIDOR E-G-H 20A/1P
RECEPTACLES CORRIDOR I 20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
40A/3P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P LIGHTING B-38, B-38A
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
UNKNOWN
UNKNOWN
LIGHTING GROUND EAST CORRIDOR
LIGHTING 1ST EAST CORRIDOR
LIGHTING 2ND EAST CORRIDOR
LIGHTING 3RD EAST CORRIDOR
LIGHTING 4TH EAST CORRIDOR
LIGHTING ELEVATOR NORTH
LIGHTING ELEVATOR SOUTH
RECEPTACLES B04
LIGHTING N.E. STAIRWELL
LIGHTING N.W. STAIRWELL
LIGHTING FREIGHT ELEVATOR
PLUGMOLD B06
EXHAUST FAN 14
PLUGMOLD B06
SPARE
SPARE SPARE
SPARE
SPARE
SPACE
SPARE
SPARE
UNDERGROUND CIR. CENTER B43
RECEPTACLE SOUTH WALL RM. B48
RECEPTACLES ROOM B48, & B50A
SPACE RECEPTACLE NORTH WALL RM. 39A
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
LIGHT FIXTURE SCHEDULE
TYPE LAMP DESCRIPTION MANUFACTURER MODEL # MOUNTING COMMENTS
A2 LED 1X4 KENALL SIMPLESEAL #HSES014-50L40K-DCC-DV-5F-5H-SYM SURFACE MOUNT
A3 LED 1X4 RED LIGHT KENALL SIMPLESEAL #CSES014-23R-40K8-DIM1-DV-5F-5H-SYM-AMF SURFACE MOUNT CORN E
LL U N I V
E
R
SI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
109 TOWER ROAD
URIS HALL
BASEMENT LAB
RENOVATION
E-600
2200272.03
ELECTRICAL
SCHEDULES
Designer
MPS
2087
06/05/2020
CEX
^^
ELSIOR
^^^^^^
077 4 2 5L
E
D
ESNECI
FORP ROISS LAN EENIGNERANDYD.HE
A
RDSTATE O F NEW
Y
ORK