HomeMy WebLinkAboutDrawings_Uris Hall Basement Lab Renovation INDEXEDCB CB CB CB CB CB CB CB CB CB CB CB CB CB CB CB CB CB CB CB CBCB CB CB CB CB CB CB CB CBCB CBCB CB CB CB CB CB CB CBCB CBCB CB CB CB CB CB CB CB CB SP SP SS S SIGN MONUMENT PLATFORM UP UP UP UP UP UP UP UP TOWER ROAD URIS HALL 2087 EAST AVENUECAMPUS ROAD B52 B50A B48 B46 B44 B44A B39A B39 B50 B00UF B00UH EXTERIOR ELEVATION 1 X-100 X-100 1 1 INTERIOR ELEVATION 1 X-100 SECTION MARKER 1 X-100 ENLARGED DETAIL CONSTRUCTION KEYED NOTE DEMOLITION KEYED NOTE DRAWING REVISION NOTE LINETYPE: TO BE PROVIDED / NEW LINETYPE: DEMOLITION / TO BE RELOCATED LINETYPE: EXISTING TO REMAIN # # # 1 1 1 11 T-001 TITLE SHEET ARCHITECTURAL A-001 GENERAL NOTES, SYMBOLOGY, ABBREVIATIONS, CODE DATA AND EGRESS PLAN A-101 DEMOLITION AND RENOVATION FLOOR PLANS A-102 DEMOLITION AND RENOVATION REFLECTED CEILING PLANS MECHANICAL M-001 MECHANICAL GENERAL NOTES AND SYMBOL LEGENDS M-101 MECHANICAL DEMOLITION AND RENOVATION REFLECTED CEILING PLANS M-501 MECHANICAL SCHEDULES ELECTRICAL E-001 ELECTRICAL NOTES, SYMBOL LEGEND, & ABBREVIATIONS E-101 PARTIAL BASEMENT FLOOR ELECTRICAL PLAN E-600 ELECTRICAL SCHEDULESCORNE LL U N I V E R SI TYFOUN D E D 5681AD CORN E LL U N I V E R SI TYFOU N D E D 5681AD FACILITIES ENGINEERING ARCHIVE BAR CODEITHACA, NEW YORK ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 Cornell University 109 TOWER ROAD URIS HALL BASEMENT LAB RENOVATION T-001 12390202 TITLE SHEET FE DESIGN RLH 2087 JUNE 5, 2020 URIS HALL BASEMENT LAB RENOVATION BUILDING CODE SUMMARYGENERAL SYMBOLS LEGEND DRAWING INDEX PROJECT SCOPE THE PURPOSE OF THIS PROJECT IS TO RENOVATE EXISTING BASEMENT LEVEL SPACES WITHIN URIS HALL TO CREATE A NEW BSL2 (BIOSAFETY LEVEL 2) CERTIFIABLE LAB AND ANCILLARY SPACES. AREAS OF WORK INCLUDE: *B52 (VIVARIUM, HOUSING AND TRANSFER) -REMOVAL AND REPLACEMENT OF HARD CEILING AS REQUIRED TO FACILITATE NEW MECHANICALS, NEW HARD-DUCTED BIOSAFETY CABINET, AND STRUCTURAL SUPPORT FOR VENTILATED MOUSE CAGE RACKS. *B50A (BSL2, VIVARIUM, SURGERY) -GAS SCAVENGING SURGICAL SNORKEL, REMOVAL AND REPLACEMENT OF HARD CEILING AS REQUIRED TO FACILITATE NEW MECHANICALS, SURGICAL LAMP, NEW ELECTRICAL POWER. *B48 (BSL2, VIVARIUM, PROCEDURES) -NEW ELECTRICAL POWER. *B46, B44, B44A -NEW ELECTRICAL POWER. *B39, B39A -REMOVAL AND REPLACEMENT OF HARD CEILING AS REQUIRED TO FACILITATE NEW MECHANICALS, OPTIONAL NEW ETHERNET, NEW ELECTRICAL POWER. PERSPECTIVE VIEWSITE LOCATION -URIS HALL KEY PLAN -BASEMENT LEVEL AREAS OF WORK APPLICABLE CODES 2020 NYS BUILDING CODE 2020 NYS EXISTING BUILDING CODE 2020 NYS FIRE CODE 2020 NYS PLUMBING CODE 2020 NYS MECHANICAL CODE 2020 NYS ENERGY CONSERVATION CODE 2009 ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES 2010 AMERICANS WITH DISABILITY ACT (ADA) PROJECT SUMMARY THIS PROJECT INCLUDES THE RENOVATION OF (514) SF OF (LAB SPACE & MICROSCOPE ROOM). THE WORK IS ALTERATION LEVEL (2) (CITY OF ITHACA). ALTERATION LEVEL 2: LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENTION OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. AN EXISTING BUILDING OR PORTION THEREOF SHALL NOT BE ALTERED SUCH THAT THE BUILDING BECOMES LESS SAFE THAN ITS EXISTING CONDITIONS. BUILDING LIMITATIONS CONSTRUCTION CLASSIFICATION:2B CLASSIFICATION OF HAZARDS:NONE HIGH-RISE BUILDING:NO EXTINGUISHING REQUIREMENT:THE EXISTING SPACE WITHIN THE BUILDING IS SPRINKLERED OCCUPANCY OCCUPANCY CLASSIFICATION:NON-SEPARATED MIXED "HIGHER EDUCATION LABORATORY SUITES" AND "BUSINESS (B)" 1 04/03/20 ISSUE FOR DD REVIEW 2 05/19/20 ISSUE FOR COORDINATED REVIEW 3 06/05/20 ISSUE FOR CONSTRUCTION 1B UP UP UP UP WALL -EXISTING WALL -METAL STUD/ GWB WALL -CONCRETE WALL -CMU WALL -BRICK ITEMS FOR DEMOLITION DOOR/ WALL -EXISTING DOOR/ WALL -NEW DOOR/ WALL -DEMOLITION TAG -DOOR TAG -WINDOW TAG -WALL TAG -ROOM # CENTER LINE PHOTO REFERENCE LEVEL MARKER COLUMN GRID MARKER ELEVATION MARKER ELEVATION CHANGE ARROWS BREAK LINE SYMBOLS 0' -0" 101 1t X-X X 2B00UA CL 1 Name Elevation A101 1 1 1 0 DN UP ABBREVIATIONS A &AND @ AT ACT ACOUSTICAL CEILING TILE ALT ALTERNATE ALUM ALUMINUM AVG AVERAGE AFF ABOVE FINISH FLOOR B BD BOARD BLDG BUILDING BOD BOTTOM OF DECK BSMT BASEMENT C CG CORNER GUARDS CJ CONTROL JOINT CLG CEILING CL CENTER LINE CLR CLEAR CMU CONCRETE MASONRY UNIT COL COLUMN CONC CONCRETE CONF CONFERENCE CONT CONTINUOUS CORR CORRIDOR CPT CARPET CRS COURSE(S) CT CERAMIC TILE D DEMO DEMOLITION DF DRINKING FOUNTAIN DIA DIAMETER DIM DIMENSION DN DOWN DO DOOR OPENING DWG DRAWING E EA EACH EJ EXPANSION JOINT ELEC ELECTRIC ELEV ELEVATION/ ELEVATOR EPDM RUBBER ROOF MEMBRANE EQ EQUAL EX'G EXISTING EXT EXTERIOR F FD FLOOR DRAIN FDN FOUNDATION FEC FIRE EXTINGUISHER CABINET FFE FINISH FLOOR ELEVATION FRP FIBER REINFORCED POLYESTER FT FOOT/FEET FTG FOOTING G GA GAGE GALV GALVANIZED GC GENERAL CONTRACTOR GEN GENERAL GL GLASS GWB GYPSUM WALL BOARD H HC HANDICAPPED HT HEIGHT HM HOLLOW METAL HR HOUR HVAC HEATING, VENTILATING & AC J JAN JANITOR L LAV LAVATORY LB/#POUND LGMF LIGHT GAGE METAL FRAMING M MFR MANUFACTURER MAT MATERIAL MAX MAXIMUM MEZZ MEZZANINE MIN MINIMUM MO MASONRY OPENING MTL METAL N NA NOT APPLICABLE NIC NOT IN CONTRACT NR NOT RATED NTS NOT TO SCALE O OC ON CENTER OD OUTSIDE DIAMETER OPNG OPENING OSB ORIENTER STRAND BOARD P +/-PLUS OR MINUS PSF POUNDS PER SQUARE FOOT PSI POUNDS PER SQUARE INCH PT PRESSURE TREATED Q QTY QUANTITY R R RISER RD ROOF DRAIN REF REFRIGERATOR REQ REQUIRED REV REVISION RO ROUGH OPENING RTU ROOF TOP UNIT S SHTG SHEATHING SIM SIMILAR SF SQUARE FOOT/ FEET SS STAINLESS STEEL STL STEEL STD STANDARD T T TREAD T&G TONGUE & GROOVE TEL TELEPHONE TEMP TEMPERATURE TOS TOP OF STEEL TV TELEVISION TYP TYPICAL U UEV UNEVEN DOORS W/ VISION PANEL UEF UNEVEN FLUSH DOOR V VCT VINYL COMPOSITION TILE VIF VERIFY IN FIELD W W/O WITHOUT WD WOOD B52 B50A B48 B46 B44 B44A B39A B39 B50 B32 B00UF B00UH LEGEND PATH OF EGRESS 2 HR FIRE RESISTANCE RATED CONSTRUCTION 176'100' 162' 128' 118' 111' 99' 91' 80' 111'INDICATES MAX. TRAVEL DISTANCE TO EXIT AREA OF WORK FUME HOOD CORN E LL U N I V E R SI TYFOU N D E D 5681AD FACILITIES ENGINEERING ARCHIVE BAR CODEITHACA, NEW YORK ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 109 TOWER ROAD URIS HALL BASEMENT LAB RENOVATION A-001 12390202 GENERAL NOTES, SYMBOLOGY, ABBREVIATIONS, CODE DATA AND EGRESS PLAN R. HERKO RLH 2087 JUNE 5, 2020 SCOPE OF WORK 1.0 REMOVE CEILING MATERIAL AND FRAMING AS REQUIRED TO INSTALL NEW MECHANCIAL WORK 2.0 INSTALL NEW CEILING MATERIAL AND FRAMING. 3.0 PATCH & REPAIR CEILINGS WHERE LIGHTS REMOVED & NEW INSTALLED 4.0 TAPE, PRIME & PAINT NEW CEILING. PAINT EXISTING WALLS & CEILINGS. GENERAL NOTES 1.0 DESIGN, CONSTRUCTION AND SAFETY SHALL CONFORM TO ALL LOCAL, STATE AND OWNER SPECIFIC CODES, INCLUDING (BUT NOT LIMITED TO) THE NEW YORK STATE UNIFORM FIRE PROTECTION AND BUILDING CODE, LATEST REVISION, THE NFPA 101 LIFE SAFETY CODE, LATEST REVISION, ANSI A117.1 - LATEST REVISION, OSHA, AND ANY OTHER CODES GOVERNED BY THE JURISDICTION IN WHICH THIS PROJECT IS BEING CONSTRUCTED. 2.0 THIS CONTRACT REQUIRES COMPLETE, FINISHED WORKABLE PROJECT OF THE AREAS INDICATED BY THE CONTRACT DOCUMENTS, AND SHALL INCLUDE ALL MATERIALS AND LABOR NECESSARY TO COMPLETE, REGARDLESS OF WHETHER OR NOT ALL WORK OR EACH ITEM IS SPECIFICALLY INDICATED ON ANY OTHER PORTION OF THE DRAWINGS AND / OR NOTES. 3.0 WHERE MATERIALS REFERENCED ON DRAWINGS, OR NECESSARY TO COMPLETE THE WORK OF THIS CONTRACT ARE NOT SPECIFIED HEREIN, PROVIDE BEST QUALITY MATERIALS. WHERE MATERIALS ARE INTENDED TO MATCH EXISTING, PROVIDE CLOSEST POSSIBLE MATCH, SUBJECT TO OWNER'S APPROVAL. ALL ITEMS AND WORK ON DRAWINGS ARE NEW, UNLESS INDICATED EXISTING. ALL WORK WHICH HAS BEEN DAMAGED SHALL BE REPAIRED OR REPLACED AT NO COST TO THE OWNER. WHERE ITEMS CAN NOT BE REPAIRED TO A ""NEW CONDITION"", OR WHERE THE STRUCTURAL INTEGRITY HAS BEEN AFFECTED, ITEMS SHALL BE REPLACED AT NO COST TO THE OWNER. 4.0 CONTRACTOR IS RESPONSIBLE TO VERIFY ALL SITE, FIELD AND BUILDING CONDITIONS PRIOR TO SUBMITTING BIDS AND COMMENCING WORK. IF THERE ARE ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS, NOTIFY THE PROJECT MANAGER, WHO WILL REQUEST CLARIFICATION FROM THE ARCHITECT/ENGINEER AND PROVIDE CLARIFICATION IN WRITING. 5.0 WHERE EXISTING CONSTRUCTION OR ITEMS HAVE BEEN INFILLED, REMOVED AND / OR DISTURBED FOR INSTALLATION OF NEW WORK, CAUSING THE EXPOSURE OF UNFINISHED AND/OR DAMAGED SURFACES RESULTING SURFACES AND INFILLED SURFACES SHALL BE RECONSTRUCTED WITH MATERIALS TO MATCH FINISHED AREAS. ALL ABANDONED OPENINGS (i.e. DUCT/PIPE REMOVALS, ETC.) AT WALLS, ROOF OR FLOOR TO BE INFILLED SOLID. 6.0 WORK IS REQUIRED IN VARIOUS PORTIONS OF THE FACILITY TO EXECUTE WORK OF OTHER TRADES (i.e. ELECTRICAL, MECHANICAL). ALTHOUGH NOT NECESSARILY SHOWN ON DRAWINGS, WORK IS REQUIRED IN THESE AREAS CONSISTING OF REMOVAL / REPLACEMENT OF CEILINGS, WALLS, FINISHES, PAVEMENT AND OTHER CONSTRUCTION AS NECESSARY TO PERFORM WORK AND RESTORE THESE SPACES OR AREAS TO ORIGINAL CONDITION. 7.0 GENERAL CONTRACTOR IS TO COORDINATE WORK OF ALL TRADES. SCHEDULE WORK PROGRESS THROUGHOUT THE ENTIRE PROJECT TO PREVENT CONFLICTS AND INTERFERENCES. OBTAIN ALL NECESSARY INFORMATION SUCH AS SIZES, LOCATIONS, TEMPLATES, LAYOUT, DIMENSIONS AND ALL OTHER INFORMATION NECESSARY FOR A PROPER AND WELL COORDINATED INSTALLATION. PRIOR TO INSTALLATION OF ITEMS, VERIFY AND CONFIRM WITH EACH CONTRACTOR EXACT LOCATION OF ALL ITEMS. 8.0 ALL PENETRATIONS (EXISTING OR NEW) THROUGH FLOORS AND FULL HEIGHT WALLS - IN AREA OF WORK TO BE FIRE STOPPED. ALL GAPS AND JOINTS AT RATED FLOORS, ROOFS AND WALLS TO BE FIRE & SMOKE STOPPED. GAPS AND JOINTS INCLUDE (BUT ARE NOT LIMITED TO) TOP OF WALL TO FLOOR OR ROOF DECK, WALL TO BEAMS, AND CONTROL OR EXPANSION JOINTS. FIRE STOPPING INCLUDES BOTH FORM OR PACKING MATERIAL AND THE FILL, VOID OR CAVITY MATERIAL. PROVIDE AND INSTALL LABELING REQUIRED BY CODE. LABELS SHALL INCLUDE PENETRATION TYPE WITH UL LISTING USED, MATERIAL USED, DATE INSTALL AND NAME OF INSTALLER. 9.0 JOBSITE WILL BE CLEANED DAILY AND DEBRIS REMOVED TO CONTAINERS OR TO VEHICLE WHICH WILL REMOVE DEBRIS FROM CAMPUS. CONTAINERS WILL BE REMOVED AS SOON AS FULL OR WHEN THE PROJECT HAS PROGRESSED TO A POINT THAT A CONTAINER IS NO LONGER REQUIRED. 10.0 CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL AREAS USED TO BRING SUPPLIES AND EQUIPMENT INTO THE PROJECT AREA. ANY DAMAGE TO AREAS OUTSIDE THE PROJECT AREA INCLUDING BUT NOT LIMITED TO THE LOBBY AND CORRIDOR SHALL BE REPAIRED AT NO COST TO THE OWNER. SCALE:1/16" = 1'-0"1 BASEMENT LEVEL - CODE EGRESS PLAN 1 04/03/20 ISSUE FOR DD REVIEW 2 05/19/20 ISSUE FOR COORDINATED REVIEW 3 06/05/20 ISSUE FOR CONSTRUCTION 39A 39 B52 B50AB50 B48 B46 B44AB44 B52 B50AB50 B48 B46 B44AB44 BSC CAGE RACK CAGE RACK 1 2 A1 3 3 33 3 3 3 5' - 0"5' - 6"1' - 6"4 5 6 6 6 4 4 +/- 15' - 1"+/- 9' - 0"+/- 9' - 6"+/- 9' - 5"+/- 9' - 6"+/- 9' - 6"+/- 6' - 7 3/8" +/- 8' - 7 3/8"+/- 6' - 0" +/- 8' - 0" 39A 39 3 3 A-101 KEYED RENOVATION NOTES 1 NEW ANIMAL CAGE RACK SUPPLIED BY OWNER AND INSTALLED BY GENERAL CONTRACTOR. GENERAL CONTRACTOR TO TRANSPORT NEW UNIT FROM LOADING DOCK TO WORK AREA AND ASSEMBLE IF REQUIRED. CONNECTIONS TO MECHANICAL DUCTWORK BY MECHANICAL CONTRACTOR (REFER TO MECHANICAL DRAWINGS) AND ELECTRIC BY ELECTRICAL CONTRACTOR (REFER TO ELECTRICAL DRAWINGS) 2 BIOSAFETY CABINET SUPPLIED BY OWNER AND INSTALLED BY GENERAL CONTRACTOR. GENERAL CONTRACTOR TO TRANSPORT NEW UNIT FROM LOADING DOCK TO WORK AREA AND ASSEMBLE IF REQUIRED. MECHANICAL CONTRACTOR TO MAKE CONNECTIONS TO DUCTWORK (REFER TO MECHANICAL DRAWINGS) AND ELECTRICAL CONNECTIONS BY ELECTRICAL CONTRACTOR (REFER TO ELECTRICAL DRAWINGS). 3 GENERAL CONTRACTOR TO PREP AND PAINT ALL WALLS, DOOR FRAME AND CEILING WITH BENJAMIN MOORE COROTECH PRE-CATALYSED WATERBORNE EPOXY SEMI-GLOSS (V341) – COLOR WHITE. PROTECT EXISTING DOORS, WALL BUMPER RAILS AND FLOORING. 4 ADA CLEARANCE AREA 5 ADA T-TURN CLEARANCE AREA 6 EXISTING METAL BUMPER RAIL TO REMAIN - TYP. # 0' 2' 4' 8' SCALE: 1/4"=1'-0" SCALE:1/4" = 1'-0"3 ROOM B39 - B39A DEMOLITION PLAN SCALE:1/4" = 1'-0"1 ROOM B52 - B44A DEMOLITION PLAN SCALE:1/4" = 1'-0"2 ROOM B52 - B44A RENOVATION PLAN SCALE:1/4" = 1'-0"4 ROOM B39 - B39A RENOVATION PLAN CORN E LL U N I V E R SI TYFOU N D E D 5681AD FACILITIES ENGINEERING ARCHIVE BAR CODEITHACA, NEW YORK ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 109 TOWER ROAD URIS HALL BASEMENT LAB RENOVATION A-101 12390202 DEMOLITION AND RENOVATION FLOOR PLANS R. HERKO EWK 2087 JUNE 5, 2020 1 04/03/20 ISSUE FOR DD REVIEW 2 05/19/20 ISSUE FOR COORDINATED REVIEW 3 06/05/20 ISSUE FOR CONSTRUCTION 1515VS VS VS 151515VS 15B52 B50A B50 B46 B44AB44 1 1 B48 B52 B50A B50 B48 B46 B44AB44 1 2 2 2 1 2 2 3 3 4 4 5 5 39A 39 11 39A 39 1 1 CORN E LL U N I V E R SI TYFOU N D E D 5681AD FACILITIES ENGINEERING ARCHIVE BAR CODEITHACA, NEW YORK ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 109 TOWER ROAD URIS HALL BASEMENT LAB RENOVATION A-102 12390202 DEMOLITION AND RENOVATION REFLECTED CEILING PLANS R. HERKO EWK 2087 JUNE 5, 2020 0' 2' 4' 8' SCALE: 1/4"=1'-0" SCALE:1/4" = 1'-0"1 ROOM B52 - B44A DEMOLITION REFLECTED CEILING PLAN SCALE:1/4" = 1'-0"2 ROOM B52 - B44A RENOVATION REFLECTED CEILING PLAN SCALE:1/4" = 1'-0"3 ROOM B39-39A DEMOLITION REFLECTED CEILING PLAN SCALE:1/4" = 1'-0"4 ROOM B39-39A RENOVATION REFLECTED CEILING PLAN # #A-102 KEYED DEMOLITION NOTES 1 REMOVE EXISTING HARD CEILING THROUGHOUT TO ACCESS MECHANICALS. CONTRACTOR TO TAKE PRECAUTIONS NOT TO DAMAGE EXISTING SPRAY APPLIED FIREPROOFING TO DECK ABOVE. ANY DAMAGE FROM REMOVALS WILL REQUIRE REPAIR BY THE CONTRACTOR. A-102 KEYED RENOVATION NOTES 1 NEW 5/8" GYPSUM WALL BOARD CEILING. TAPED, SPACKLED AND PAINTED. COORDINATE NEW LIGHTING, MECHANICAL DIFFUSERS AND ACCESS PANELS. PAINT CEILING WITH BENJAMIN MOORE COROTECH PRE-CATALYSED WATERBORNE EPOXY SEMI-GLOSS (V341) – COLOR WHITE. PROTECT EXISTI 2 EXISTING CEILING TO BE PATCHED, AND REPAIRED WHERE LIGHTING FIXTURES HAVE BEEN REMOVED. PAINT CEILING WITH BENJAMIN MOORE COROTECH PRE-CATALYSED WATERBORNE EPOXY SEMI-GLOSS (V341) – COLOR WHITE. PROTECT EXISTING DOORS, WALL BUMPER RAILS AND FLOORING. 3 GC/ MECHANICAL CONTRACTOR TO COORDINATE LOCATION OF NEW 24"x24" ACCESS PANEL WITHIN REACH OF MANUAL BALANCING DAMPERS. 4 COORDINATE FIRE PROTECTION SPRINKLER HEADS / ESCUTHEONS WITH FIRE PROTECTION WORK. 5 COORDINATE INSTALLATION OF SMOKE DETECTORS WITH CEILING WORK & FIRE PROTECTION WORK. DEMOLITION GENERAL NOTES: DEMOLITION SCHEDULE SHOULD BE COORDINATED WITH CORNELL UNIVERSITY AND CLASS SCHEDULES TO AVOID DISRUPTION OF STUDENTS AND TEACHERS. NO HEAVY CONSTRUCTION SUCH AS BUT NOT LIMITED TO: CORE DRILLING, HAMMERING, BLOCK REMOVAL, SANDING, GRINDING, SAW CUTTING, ETC. BETWEEN 9:00AM AND 5:00 PM ON DAYS WHEN CLASSES ARE IN SESSION ABOVE OR BELOW WORK. PATCH AND REPAIR WITH LIKE MATERIAL TO A SMOOTH FINISH AT ALL REMOVED LIGHTS, ELECTRICAL BOXES, PIPING, HANGERS, MECHANICAL EQUIPMENT, EXISTING HOLES, ETC.. SEE MECHANICAL, ELECTRICAL, AND PLUMBING DEMOLITION DRAWINGS. FIELD VERIFY ALL EXISTING CONDITIONS @ FLOORS, WALLS, AND CEILINGS. REMOVE ALL UNUSED OR ABANDONED CONDUIT, PIPING, HANGERS, CABLES, ELECTRICAL BOXES, MECHANICAL EQUIPMENT, ETC. ON THE CEILINGS AND WALLS AND COLUMNS, COORDINATE WITH CORNELL UNIVERSITY AND MECHANICAL, ELECTRICAL, AND PLUMBING DEMOLITION DRAWINGS. COORDINATE WITH ELECTRICAL, STRUCTURAL, AND PLUMBING DRAWINGS FOR ADDITIONAL SAW CUTTING OF EXISTING CONCRETE SLAB, FOR CONDUIT, MECHANICAL DUCTWORK, PIPING LINES ETC.. 1 04/03/20 ISSUE FOR DD REVIEW 2 05/19/20 ISSUE FOR COORDINATED REVIEW 3 06/05/20 ISSUE FOR CONSTRUCTION CORN E LL U N I V E R SI TYFOUN D E D 5681AD FACILITIES ENGINEERING ARCHIVE BAR CODEITHACA, NEW YORK ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 109 TOWER ROAD URIS HALL BASEMENT LAB RENOVATION M-001 12390202 MECHANICAL GENERAL NOTES AND SYMBOL LEGENDS E. KOLACKI EWK 2087 JUNE 5, 2020 MECHANICAL ABBREVIATIONS BCU BLOWER COIL UNIT CHWR CHILLED WATER RETURN CHWS CHILLED WATER SUPPLY CC CLEAN CONDENSATE CO CLEAN OUT CS CLEAN STEAM CD CONDENSATE DRAIN EA EXHAUST AIR EAG EXHAUST AIR GRILLE FD FIRE DAMPER GWR GLYCOL HEATING RETURN GWS GLYCOL HEATING SUPPLY HPR HIGH PRESSURE STEAM RETURN HPS HIGH PRESSURE STEAM SUPPLY HWR HOT WATER HEATING RETURN HWS HOT WATER HEATING SUPPLY LPC LOW PRESSURE CONDENSATE LPS LOW PRESSURE STEAM MU MAKE UP WATER MPC MEDIUM PRESSURE CONDENSATE MPS MEDIUM PRESSURE STEAM NG NATURAL GAS PCWR PROCESS CHILLED WATER RETURN PCWS PROCESS CHILLED WATER SUPPLY HG REFRIGERANT HOT GAS RL REFRIGERANT LIQUID RS REFRIGERANT SUCTION RAG RETURN AIR GRILLE SA SUPPLY AIR SAD SUPPLY AIR DIFFUSER VD VOLUME DAMPER MECHANICAL SYMBOLOGY AIRFLOW BACKFLOW PREVENTER BALANCE VALVE BALL VALVE BOTTOM PIPE CONNECTION BUTTERFLY VALVE CAP OR PLUG CHECK VALVE CIRCULATING PUMP DIRECTION OF FLOW DUCT AIRFLOW DUCT DOWN (EXHAUST OR RETURN) DUCT DOWN (SUPPLY) FIRE AND SMOKE DAMPER IN DUCT FIRE DAMPER IN DUCT FLANGE CONNECTION FLEX CONNECTOR FLEXIBLE CONNECTION FLEXIBLE DUCT FLOW METER FLOW SWITCH FUSIBLE LINK VALVE GLOBE VALVE MANUAL AIRVENT ORIFICE METER PIPE DOWN PIPE UP PIPING REDUCER (CONCENTRIC) PIPING REDUCER (ECCENTRIC) PRESSURE GAUGE PRESSURE OR TEMPERATURE PETES PLUG PRESSURE REDUCING VALVE PRESSURE SWITCH RECTANGULAR ELBOW RECTANGULAR ELBOW WITH TURNING VANES RELIEF VALVE SMOKE DAMPER IN DUCT SOLENOID VALVE STANDARD BRANCH DUCT STEAM TRAP STRAINER (DUPLEX) STRAINER WITH BLOWDOWN VALVE AND CAP SUPPLY THROUGH NEXT FLOOR OR ROOF TEMPERATURE WELL THERMOMETER THERMOMETER (DIAL) TOP PIPE CONNECTION TRIPLE DUTY VALVE UNION CONNECTION VACUUM BREAKER VOLUME DAMPER IN DUCT CONTROL SYMBOLOGY 2-WAY CONTROL VALVE, DIGITAL 2-WAY CONTROL VALVE, PNEUMATIC 3-WAY CONTROL VALVE, DIGITAL 3-WAY CONTROL VALVE, PNEUMATIC ADDRESSABLE OUTPUT MODULE (FIRE ALARM INTERFACE) AIRFLOW CONTROL VALVE (VENTURI OR VORTEX SHEDDING) AVERAGING SENSOR BINARY POINT BUTTERFLY CONTROL DAMPER CARBON DIOXIDE SENSOR CONDENSATE SENSOR CURRENT SENSOR DEW-POINT SENSOR DIFFERENTIAL PRESSURE SENSOR DIFFERENTIAL PRESSURE SENSOR ELECTRIC TO PNEUMATIC SWITCH ELECTRIC TO PNEUMATIC TRANSDUCER END SWITCH FLOW ELEMENT (METER) FLOW SENSOR HIGH LEVEL SWITCH HUMIDSTAT SENSOR LIQUID IMERSION TEMPERATURE SENSOR LOW LEVEL SWITCH MODULATING MOTOR MOTOR STARTER NETWORK COMMUNICATION POINT, BACnet MSTP OCCUPANCY SENSOR OPEN/CLOSE OPPOSED BLADE CONTROL DAMPER PARALLEL BLADE CONTROL DAMPER PNEUMATIC THERMOSTAT PRESSURE SENSOR PRESSURE SWITCH RELATIVE HUMIDITY SENSOR RELAY ROOM TEMPERATURE SENSOR WITH ADJUSTABLE THERMOSTAT ROOM TEMPERATURE SENSOR WITH OCCUPANCY OVERRIDE ROOM TEMPERATURE SENSOR WITH ON/OFF SWITCH ROOM TEMPERATURE SENSOR WITH VISUAL DISPLAY ROTATION DETECTOR SINGLE POINT SENSOR SMOKE DETECTOR SPEED COMMAND START/STOP STATIC PRESSURE SENSOR SWITCH TEMPERATURE SENSOR TEMPERATURE SENSOR TEMPERATURE SENSOR WITH ADJUSTABLE SETPOINT GENERAL DRAWING SYMBOLOGY DEMOLISHED WORK EXISTING PIPING TO REMAIN EXISTING TO REMAIN EXISTING WORK TO REMAIN NEW WORK POINT OF CONNECTION POINT OF DISCONNECTION CONTROL ABBREVIATIONS AI ANALOG INPUT AO ANALOG OUTPUT AV ANALOG VALUE BI BINARY INPUT BO BINARY OUTPUT BV BINARY VALUE F.L. FAIL LAST N.C. NORMALLY CLOSED N.O. NORMALLY OPEN VFD VARIABLE FREQUENCY DRIVE MECHANICAL SCOPE OF WORK 1.0 THIS PROJECT MODIFIES THE EXISTING HVAC SYSTEM TO ROOMS B48, B50, B50A AND B52 TO PROVIDE BSL-1/2 PROCEDURE, SURGICAL, AND ANIMAL HOLDING ROOMS. 2.0 OWNER WILL PROVIDE THE BIOLOGICAL SAFETY CABINET. 3.0 OWNER WILL PROVIDE THE CAGE RACK AND ACCESSORY SUPPLY AND EXHAUST BLOWER PACKS. 4.0 WORK INCLUDES MODIFICATIONS TO THE DUCT, HYDRONIC PIPING AND CONTROL SYSTEMS. 5.0 PROVIDE TEST AND BALANCE SERVICES. MECHANICAL GENERAL NOTES 1.0 ALL DUCT DIMENSIONS INDICATED ARE IN INCHES, AND ARE INSIDE FREE AND CLEAR DIMENSIONS. 2.0 PNEUMATIC TERMINATIONS: IF COPPER: DEMO BACK TO MAIN AND PROVIDED SOLDERED END CAP IF POLY: DEMO BACK TO MAIN AND PROVIDE BRASS PLUG DO NOT USE SHEETMETAL SCREW OR BEND OVER END OF COPPER TUBE. 3.0 INSTALL EQUIPMENT TO ENSURE PROPER ACCESS TO CONTROL DEVICES AND WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE AND REPAIR. EQUIPMENT THAT IS NOT INSTALLED WITH THIS REQUIREMENT IN MIND SHALL BE RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIES ARE CORRECTED. 4.0 ALL SYSTEM TESTING SHALL BE CONDUCTED PRIOR TO INSULATION, FIREPROOFING, AND ENCLOSURE IN SHAFTS. ANY RESTORATION WORK REQUIRED AS A RESULT OF DISTURBING FINISHES OR STRUCTURE IN ORDER TO ACCESS SYSTEMS REQUIRING REPAIR SHALL BE AT NO COST TO THE UNIVERSITY. 5.0 CUTTING AND PATCHING: THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING, FITTING, AND PATCHING TO COMPLETE THE WORK. WHERE EXISTING CONSTRUCTION IS REMOVED, CAUSING AN EXPOSURE OF UNFINISHED AND/OR DAMAGED SURFACES, RESULTING SURFACES SHALL BE RECONSTRUCTED WITH MATERIALS TO MATCH FINISHED AREAS. 6.0 ANY FIRESTOPPING DISTURBED DURING THE COURSE OF WORK SHALL BE REPAIRED TO MAINTAIN A 2-HOUR FIRE RATING. 7.0 TESTING AND BALANCING: THE CONTRACTOR SHALL BALANCE ALL AIR SYSTEMS AS INDICATED. SUBMIT RESULTS OF TESTING AND BALANCING ON STANDARD TAB CONTRACTOR'S FORMS TO THE ENGINEER FOR REVIEW. SYSTEMS SHALL BE BALANCED TO WITHIN +/- 10% OF DESIGN VALUES. FINAL BALANCING SHALL OCCUR AFTER ALL LEAKS IN THE BUILDING ENVELOPE HAVE BEEN IDENTIFIED AND SEALED. 8.0 SEAL ALL PIPE, GRILLE, DIFFUSER, DUCT, CONDUIT PENETRATIONS WITH APPROPRIATE MATERIALS (CAULK, FOAM, ETC,) THAT ARE IMPENETRABLE TO THE CONTAINED ORGANISMS AND WITHSTAND REPEATED DECONTAMINATIONS WITH CLEANING AGENTS. 9.0 SPACES ARE DESIGNED FOR BSL-2 LEVELS. VERIFY THAT ALL PIPING, CONDUIT, DUCTWORK AND OTHER WALL PENETRATIONS IN THE PROJECT AREA ARE AIRTIGHT. SEAL ALL NON-COMPLIANT PENETRATIONS. PERFORM A GLYCOL SMOKE TEST AFTER ALL PENETRATIONS ARE SEALED TO CONFIRM PROPER AIRTIGHTNESS AND ROOM PRESSURIZATION. 10.0 THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED IN THE CONTRACT. SPACE ABOVE THE CEILINGS AND THE MECHANICAL ROOMS IS TIGHT. VERIFY ALL FIELD CONDITIONS PRIOR TO SUBMITTING EQUIPMENT AND SHOP DRAWINGS. IF THERE ARE ANY DESCREPANCIES BETWEEN THE DRAWINGS AND FIELD CONDITIONS, NOTIFY THE PROJECT MANAGER FOR A CLARIFICATION PRIOR TO PROCEEDING WITH WORK. 11.0 THE EXISTING ALC SE6104 CONTOLLERS SERVING THE SPACES ARE LOCATED IN MECHANICAL ROOM B00UJ. ALL REPLACEMENT AIR VALVES ARE TO RECONNECT TO THE EXISTING CONTROLLERS. SEQUENCES OF OPERATION ARE EXISTING, MODIFIED ONLY AS NEEDED TO PROGRAM NEW AIRFLOW SETPOINTS. 12.0 COORDINATE WITH THE GC FOR REMOVAL AND RESTORATION OF EXISTING HARD CEILINGS NECESSARY TO ACCESS DUCTWORK ABOVE. PROVIDE NEW CEILING MOUNTED ACCESS DOORS AS NEEDED TO REACH ALL BALANCING AND CONTROL DEVICES. COORDINATE LOCATIONS WITH EXISTING FEATURES. 13.0 BALANCE ALL AIRFLOWS/WATERFLOWS IN THE WORK AREA TO THE FLOWS INDICATED ON THE SCHEDULES. 14.0 DEMONSTRATE TO THE ENGINEER OF RECORD AND DESIGNATED OWNERS REPRESENTATIVE ALL SEQUENCES OF OPERATION ARE CONTROLLING TO THE DESIGN INTENT. 15.0 SCHEDULE A PRE-INSTALLATION MEETING TO REVIEW WITH THE OWNERS REPRESENTATIVES FINAL EQUPIMENT LOCATIONS PRIOR TO INSTALLATION. 16.0 ALL DUCT DIMENSIONS INDICATED ARE IN INCHES, AND ARE INSIDE FREE AND CLEAR DIMENSIONS. 17.0 THIS CONTRACT REQUIRES A COMPLETE, FINISHED, WORKABLE PROJECT WITHIN THE AREAS INDICATED ON THE CONTRACT DOCUMENTS, AND SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES NECESSARY TO COMPLETE INSTALLATION OF THE SYSTEMS INDICATED, REGARDLESS OF WHETHER OR NOT ALL WORK OR EACH ITEM IS SPECIFICALLY INDICATED ON ANY PORTION OF THE DRAWINGS AND/OR NOTES. 18.0 WHERE MATERIALS REFERENCED ON DRAWINGS, OR NECESSARY TO COMPLETE THE WORK OF THIS CONTRACT ARE NOT SPECIFIED HEREIN, THEN ASSUME THAT THE HIGHEST QUALITY MATERIALS ARE TO BE USED. APPROVAL SHALL BE GAINED BY OWNERS AUTHORIZED AGENT PRIOR TO INSTALLATION OF SAID MATERIAL. MECHANICAL SUBMITTAL SCHEDULE SECTION TITLE REQUIRED 230000 HEATING, VENTILATING & AIR-CONDITIONING - 230523 GENERAL DUTY VALVES FOR HVAC PIPING PRODUCT DATA 230593 TESTING, ADJUSTING & BALANCING FOR HVAC QUALIFICATIONS, INSPECTION AND TEST REPORTS 230700 HVAC INSULATION PRODUCT DATA 230719 HVAC PIPING & EQUIPMENT INSULATION PRODUCT DATA 230900 INSTRUMENTATION & CONTROL FOR HVAC PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M, SCHEMATIC CONTROL DIAGRAMS, ARCHITECTURE DIAGRAM, SEQUENCES OF OPERATION, BILL OF MATERIALS, CONTROL VALVE SCHEDULE 230920 ANALOG LABORATORY CONTROL PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 232113 HYDRONIC PIPING PRODUCT DATA 233100 DUCTWORK PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M, SHOP CONSTRUCTION STANDARDS, SHOP DRAWINGS 233300 AIR DUCT ACCESSORIES PRODUCT DATA 233700 AIR OUTLETS AND INLETS PRODUCT DATA 238200 TERMINAL HEATING AND COOLING UNITS PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M 1 04/03/20 ISSUE FOR DD REVIEW 2 05/19/20 ISSUE FOR COORDINATED REVIEW 3 06/05/20 ISSUE FOR CONSTRUCTION B52 B50AB50 B48 B00UH AV-S-B50 3 AV-S-B52 AV-S-B48 3 4 3 5 6 7 B52 B50AB50 B48 B00UH AV-S-B50 3 AV-S-B52 AV-S-B48 4 5 6 7 VD VD 9 11 12 13 9 VDVDVD14x8 6ø6ø12x8 14x6 14x6(E)14 15 14 15 14 151415 5 3 53 10 8 BSC CAGE RACK CAGE RACK 16 16 16 16 B00UF 2 AV-E-B50 AV-E-B48 1 2 AV-E-B52 1 B00UF 2 AV-E-B50 AV-E-B48 1 2 AV-E-B52 1 0' 4' 8'16' SCALE: 1/8"=1'-0"CORN E LL U N I V E R SI TYFOUN D E D 5681AD FACILITIES ENGINEERING ARCHIVE BAR CODEITHACA, NEW YORK ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 109 TOWER ROAD URIS HALL BASEMENT LAB RENOVATION M-101 12390202 MECHANICAL DEMOLITION AND RENOVATION REFLECTED CEILING PLANS E. KOLACKI EWK 2087 JUNE 5, 2020 SCALE:1/4" = 1'-0"1 ROOM B52-B44A MECHANICAL DEMOLITION RCP SCALE:1/4" = 1'-0"2 ROOM B52-B44A MECHANICAL RENOVATION RCP # # M-101 KEYED DEMOLITION NOTES 1 REMOVE EXHAUST AIR VALVE AND PREPARE DUCTWORK FOR INSTALLATION OF NEW EXHAUST AIR VALVE. 2 DISCONNECT CONTROLS FROM AIR VALVE AND PERFORM WORK AS NEEDED TO RECONNECT NEW AIR VALVE. 3 REMOVE SUPPLY AIR VALVE AND PREPARE DUCTWORK FOR INSTALLATION OF NEW SUPPLY AIR VALVE. 4 REMOVE DUCT MOUNTED REHEAT COIL AND PIPING FIT-OUT COMPONENTS. PREPARE FOR INSTALLATION OF NEW REHEAT COIL. 5 PREPARE EXHAUST DUCT FOR CONNECTION OF NEW SNORKEL EXHAUST. 6 REMOVE SUPPLY AIR DIFFUSER AND DUCTWORK TO POINT INDICATED. PREPARE DUCTWORK FOR EXTENSION TO NEW SUPPLY AIR DIFFUSER. 7 REMOVE EXHAUST AIR GRILLE AND DUCTWORK TO POINT INDICATED. PREPARE DUCTWORK FOR EXTENSION TO EQUIPMENT. M-101 KEYED CONSTRUCTION NOTES 1 PROVIDE NEW EXHAUST AIR VALVE AND MAKE NECESSARY TRANSITIONS TO CONNECT TO EXISTING DUCTWORK. 2 CONNECT NEW EXHAUST AIR VALVE TO EXISTING ZONE CONTROLLER. RECONNECT THE FOLLOWING CONTROL POINTS- AO: EAV DAMPER COMMAND, AI: EAV AIRFLOW FEEDBACK, AI: EAV DAMPER POSITION. 3 PROVIDE NEW SUPPLY AIR VALVE AND MAKE NECESSARY TRANSITIONS TO CONNECT TO EXISTING DUCTWORK. 4 PROVIDE NEW REHEAT COIL AND MAKE NECESSARY TRANSITIONS TO CONNECT TO EXISTING DUCTWORK AND CONTROL SYSTEM. PROVIDE A NEW DISCHARGE AIR TEMPERATURE SENSOR AND RECONNECT THE FOLLOWING CONTROL POINTS- AO: CONTROL VALVE COMMAND, AI: RHC DISCHARGE AIR TEMPERATURE. 5 CONNECT NEW SUPPLY AIR VALVE TO EXISTING ZONE CONTROLLER. RECONNECT THE FOLLOWING CONTROL POINTS- AO: SAV DAMPER COMMAND, AI: SAV AIRFLOW FEEDBACK, AI: SAV DAMPER POSITION. 6 PROVIDE NEDERMAN MODEL FX2-ORIG-D100-L2400-UP-LOW SNORKEL ARM (PART NO 70605444). MOUNT TO DECK ABOVE CEILING WITH MECHANICAL EXPANSION ANCHORS. COORDINATE SNORKEL ARM MOUNTING BRACKET AND HEIGHT IN FIELD WITH OWNER AND EXISTING FEATURES LOCATED ABOVE THE CEILING PRIOR TO SUBMITTAL AND INSTALLATION. SEAL PENETRATION THROUGH CEILING AIRTIGHT. EXPECT TO RELOCATE AND PROVIDE OFFSETS IN EXISTING 14x6 EXHAUST DUCT AS NEEDED TO FIND A CLEAR PATH TO THE DECK FOR THE BRACKET AND EXHAUST DUCT. PROVIDE FOLLOWING ACCESSORIES: -BRACKET KIT (PART NO 70377042) -DUCT CONNECTOR (PART NO 70377040) -CEILING COVER PLATE (PART NO 70502644 -COMBI HOOD (PART NO 70500144) 7 EXTEND 4-INCH ROUND EXHAUST DUCT TO BOTTOM OF EXISTING 14x6 EXHAUST DUCT. PROVIDE 45 DEGREE TAP WITH VOLUME DAMPER AT CONNECTION TO MAIN. 8 EXTEND 14x6 DUCT AS INDICATED. PROVIDE A 45 DEGREE TAP WITH VOLUME DAMPER ON BOTTOM OF DUCT AND EXTEND 12” ROUND DUCT TO NEW SUPPLY AIR DIFFUSER. 9 PROVIDE 6” DUCT CONNECTION AT CAGE RACK THIMBLE CONNECTION. EXTEND TO NEW BRANCH AND PROVIDE VOLUME DAMPER. 10 CONNECT TO EXISTING 12x8 DUCT AND IMMEDIATELY ROLL DOWN UNDER ADJACENT EXHAUST DUCT, TRANSITIONING TO 14X8. 11 CONNECT 10-INCH ROUND TO BSC THIMBLE CONNECTION BELOW CEILING. EXTEND UP TO NEW 14x8 DUCT. PROVIDE 14x8 LOW LEAKAGE DAMPER TO BE USED TO BALANCE AIRFLOW (BOD RUSKIN CD50 OPPOSED BLADE LOW PROFILE) 12 ROLL UP DUCT TO MAKE FINAL CONNECTION. 13 INSTALL EXHAUST DUCT VOLUME DAMPERS SO THAT THEY CAN BE REACHED WITHIN ONE 24x24 ACCESS PANEL. 14 ENSURE ALL PENETRATIONS ARE AIRTIGHT. SEAL ALL NON-COMPLIANT PENETRATIONS. PERFORM GLYCOL SMOKE TEST TO CONFIRM PROPER AIRTIGHTNESS AND ROOM PRESSURIZATION. 15 BALANCE ALL AIRFLOWS/ WATERFLOWS TO THE FLOWS INDICATED ON SCHEDULE SHEET M-501. 16 COORDINATE WITH GENERAL CONTRACTOR FOR WORK TO RESTORE HARD CEILING. SCALE:1/4" = 1'-0"3 ROOM B00UF MECHANICAL DEMOLITION RCP SCALE:1/4" = 1'-0"4 ROOM B00UF MECHANICAL RENOVATION RCP 1 04/03/20 ISSUE FOR DD REVIEW 2 05/19/20 ISSUE FOR COORDINATED REVIEW 3 06/05/20 ISSUE FOR CONSTRUCTION CORN E LL U N I V E R SI TYFOUN D E D 5681AD FACILITIES ENGINEERING ARCHIVE BAR CODEITHACA, NEW YORK ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 109 TOWER ROAD URIS HALL BASEMENT LAB RENOVATION M-501 12390202 MECHANICAL SCHEDULES E. KOLACKI EWK 2087 JUNE 5, 2020DUCTWORK AND ACCESSORIES SCHEDULE DUCT SERVICE LOCATION PRESSURE CLASS SEAL CLASS LEAKAGE CLASS DUCT MATERIAL DUCT LINING INSULATION FINISH RECT ROUND MIN R-VALUE MATERIAL FIELD JACKET VAPOR RETARDER SUPPLY CONNECTION TO MAIN, AIR VALVE INLET, MECHANICAL ROOM 6" POS A 6 3 A NONE R-6 W NONE YES NONE SUPPLY AIR VALVE OUTLET, MECHANICAL ROOM, ABOVE CEILINGS 2" POS A 6 3 A NONE R-6 W NONE YES NONE EXHAUST AIR VALVE INLET, MECHANICAL ROOM, ABOVE CEILINGS 3" NEG A 6 3 A NONE N/A N/A NONE NO NONE EXHAUST AIR VALVE OUTLET, CONNECTION TO MAIN, MECHANICAL ROOM 6" NEG A 6 3 A NONE N/A N/A NONE NO NONE AIR BALANCE SCHEDULE ROOM NUMBER ROOM DIMENSIONS DESCRIPTION CURRENT FUTURE NOTESAREA (SF) HEIGHT (FT)SA (CFM) EA (CFM) XFER (CFM) ACH SA (CFM) EA (CFM) XFER (CFM) ACH B48 129 8 CAGE RACK 1 0 45 43.3 0 45 43.3 1,3,4,5 CAGE RACK 2 0 45 0 45 BSC 0 655 0 655 BS 2 HOLDING - TOTAL 545 745 -200 545 745 -200 B50 57 8 FROM B00CH 100 0 N/A 100 0 N/A 8 FROM B48 0 100 0 100 FROM B50A 100 0 0 100 FROM B52 0 100 0 100 FROM CENTRAL SYSTEM 0 100 200 0 BSL2 ANTE ROOM - TOTAL 200 200 0 300 300 0 B50A 82 8 SNORKEL ARM 0 120 20.1 0 120 22.4 1,2 GENERAL EXHAUST 0 0 0 125 BSL1(2) SURGERY 220 120 100 145 245 -100 B52 134 8 BSL2 PROCEDURE 280 480 -200 26.9 280 480 -200 26.9 1,6 NOTES: 1.NEGATIVE TRANSFER (XFER) INDICATES A NEGATIVELY PRESSURIZED ROOM. POSITIVE TRANSFER (XFER) INDICATES A POSITIVELY PRESSURIZED ROOM. 2.SURGERY WILL BE UNDER BSL1 INITIALLY, WITH CONVERSION TO BSL2 IN FUTURE. 3.BIOLOGICAL SAFETY CABINET WILL BE CLASS II, TYPE A2, THIMBLE CONNECTED TO EXHAUST SYSTEM. 4.CAGE RACK EXHAUST BLOWERS TO BE THIMBLE CONNECTED TO EXHAUST SYSTEM. 5.AIR CHANGES EXCEED THE RECOMMENDED 10-15 MINIMUM DUE TO BSC. 6.THE NIH RECOMMENDS A MINIMUM VENTILATION RATE OF 15 ACH IN ANIMAL PROCEDURE ROOMS. EXPECTED COOLING LOAD EXCEEDS THE ACH REQUIREMENTS. 7.THE NIH RECOMMENDS A MINIMUM VENTILATION RATE OF 20 ACH IN ANIMAL SURGICAL ROOMS. 8.THE 100 CFM "SUPPLY AIR" FROM B00CH IS WHAT IS MAINTAINING THE ANTE ROOM NEGATIVE TO THE CORRIDOR. REGISTER, GRILLE, AND DIFFUSER SCHEDULE UNIT NO SERVES BOD MFR BOD MODEL AIRFLOW CFM PANEL SIZE NECK SIZE TYPE MATERIAL MOUNTING FINISH NOTES SAD-1 B48 KRUEGER TADSS 545 24" x 48" 12"Ø RADIAL FLOW DIFFUSER STAINLESS STEEL DUCT MOUNT WHITE 90º AIR PATTERN LABORATORY AIRFLOW CONTROL DEVICE SCHEDULE UNIT NO SERVES SUPPLY EXHAUST BOD MFR BOD MODEL SIZE BASC SETPOINTS FACTORY RANGE MIN ΔPt (IN WC)DAMPER POSITION NOTESMAX (CFM) MIN (CFM) MAX (CFM) MIN (CFM) AV-S-B48 BSL2 HOLDING X ACCUTROL AVC6308-05-ISW 1-8 545 545 800 0 0.3 N.O. 2,3,4 AV-E-B48 BSL2 HOLDING X ACCUTROL AVC6310-05-SW 1-10 745 745 1300 0 0.3 N.O. 2,3 AV-S-B50 BSL1 SURGERY / ANTE ROOM X ACCUTROL AVC6308-05-ISW 1-8 345 220 800 0 0.3 N.O. 1,2,3,4 AV-E-B50 BSL1 SURGERY / ANTE ROOM X ACCUTROL AVC6308-05-SW 1-8 245 120 800 0 0.3 N.O. 1,2,3 AV-S-B52 BSL2 PROCEDURE X ACCUTROL AVC6308-05-ISW 1-8 280 280 800 0 0.3 N.O. 2,3,4 AV-E-B52 BSL2 PROCEDURE X ACCUTROL AVC6308-05-SW 1-8 480 800 800 0 0.3 N.O. 2,3 NOTES: 1.THE BACS SETPOINTS ARE MEANT TO REPRESENT MAX/MIN FOR CURRENT AND FUTURE AIRFLOWS FOR THE PURPOSES OF SELECTION THE PROPER AIR VALVE. THESE AIR VALVES ARE NOT TO BE PROGRAMMED FOR VARIABLE FLOW. REFER TO THE AIR BALANCE SCHEDULE FOR INITIAL AIRFLOW SETPOINTS. 2.ALL VALVES TO BE 316 STAINLESS STEEL CONSTRUCTION. 3.PROVIDE TIGHT SHUT OFF. 4.PROVIDE INSULATION. REHEAT COIL SCHEDULE TAG SERVES COIL SIZE TOTAL CAPACITY (BTUH) AIR SIDE WATER SIDE W (IN) H (IN) FLOW RATE (CFM) ENT AIR TEMP (ºF) LVG AIR TEMP (ºF) PRESSURE DROP (IN WC) FLOW RATE (GPM) ENT WATER TEMP (ºF) LVG WATER TEMP (ºF) PRESSURE DROP (FT WC) BALANCE VALVE CONTROL VALVE RHC-5 B48 12 12 12949 545 55 77 0.15 MAX 0.9 130 100 2.0 MAX NOTE 9 NOTE 10 NOTES: 1.ACCEPTABLE MANUFACTURERS: AEROFIN, CARRIER, HEATCRAFT, McQUAY, TEMTROL, TRANE. 2.RATINGS: ARI 410, INDUSTRY STANDARD FOR FORCED CIRCULATION AIR COOLING AND AIR HEATING COILS 3.FINS: ALUMINUM, 10 FPI MAXIMUM 4.HEADERS: NON-FERROUS CONSTRUCTION 5.FRAME: STAINLESS STEEL 6.COIL SHALL BE PIPED IN COUNTERFLOW ARRANGEMENT. 7.PIPING SHALL BE ARRANGED TO ALLOW SERVICE AND MAINTENANCE. 8.SPACE IN THE MECHANICAL ROOM IS TIGHT. VERIFY EXISTING CONDITIONS PRIOR TO SUBMITTAL. 9.BALANCE VALVE: BELL&GOSSETT CB SERIERS, CB 3/4 10.CONTROL VALVE: BELIMO CCV-B210 TF24-SR US, 1/2-INCH VALVE SIZE, 1.2 CV, 2-WAY MODULATING CONTROL, SPRING RETURN NORMALLY CLOSED 11.INSTALL LEVEL AND PLUMB PER MANUFACTURER'S RECOMMENDED INSTRUCTIONS AND SMACNA STANDARDS. HVAC PIPE AND FITTING SCHEDULE AND SPECIFICATIONS PIPE SERVICE ABBREVIATION PIPE SIZE PIPE MATERIAL FITTINGS JOINTS INSULATION FINISHTHICK (IN) MATERIAL FIELD JACKET VAPOR RETARDER HEATING HOT WATER: 105 - 200 ˚F HWS&R 1-1/4" & BELOW A AA,AB A1,A2 1.5 MFG-1 NONE NO NONE SPECS: 1.PIPING MATERIALS A: ASTM B88 TYPE L COPPER 2.FITTINGS AA: ASME B16.22 WROUGHT COPPER SOLDER AB: ASME B16.22 WROUGHT COPPER VIEGA PRESS SEAL 3.JOINING MATERIALS A1: ASTM B2 SOLDER, LEAD FREE, 95 Su / 5 Sb OR 95.5 Sn / 4 Cu / 0.5 Ag A2: EPDM SEAL DIELECTRIC FITTINGS: USE FLANGES OR COUPLINGS. 4.INSULATION, ASTM E84 MAX FLAME-SPREAD INDEX OF 25; MAX SMOKE-DEVELOPED INDEX OF 50 MFG-1: PRE-FORMED MINERAL FIBERGLASS, ASTM C547 TYPE I, ASTM C1136, ASJ-SSL, K-VALUE OF 0.25-0.29 @ 125F MEAN TEMP 5.PIPING ACCESSORIES UNIONS: PROVIDE ADJACENT TO VALVES AND EQUIPMENT TO ALLOW SERVICE AND MAINTENANCE WITHOUT NEEDING A SYSTEM SHUTDOWN. ISOLATION VALVES: TWO-PIECE BRONZE BALL WITH 316SS BALL AND STEM. APOLLO 70-140/240; NIBCO T/S-580-70-66, WATTS B6000/6001-SS PRESSURE/ TEMPERATURE TEST PORTS: TRERICE D3770, EPDM (NORDEL) SEAT STRAINERS: WYE-PATTERN WITH NIPPLE AND BALL VALVE IN BLOWDOWN CONNECTION. PROVIDE AT INLET OF CONTROL VALVES. AIR VENTS: BELL&GOSSETT MODEL 87. PROVIDE AT ALL HIGH POINTS IN PIPING SYSTEM AND COIL CONNECTIONS. DRAIN VALVES: INSTALL AT ALL LOW POINTS OF PIPING SYSTEM AND COIL CONNECTIONS. 6.PIPE LABELS: PRINTED PLASTIC WITH CONTACT-TYPE, PERMANENT ADHESIVE BACKING AND DIRECTIONAL ARROWS SPECS: 1.COMPLY WITH SMACNA HVAC DUCT CONSTRUCTION STANDARDS 2.DUCT MATERIALS A: ASTM A653, G90 GALVANIZED SHEET STEEL 3.FITTINGS: PER SMACNA HVAC DUCT CONSTRUCTION STANDARDS RECTANGULAR ELBOWS: TYPE RE1 RADIUS ELBOW, TYPE RE2 SQUARE THROAT ELBOW WITH VANES ROUND ELBOWS: MINIMUM R/D = 1 BRANCH CONNECTIONS/TAPS: 45 DEGREE ENTRY 4.SEALANTS: UL723 MAX FLAME-SPREAD INDEX OF 25; MAX SMOKE-DEVELOPED INDEX OF 50 5.ACCESSORIES MANUAL VOLUME DAMPERS: WITH LOCKING HAND QUANDRANT HANDLE, PROVIDE AT BRANCH CONNECTIONS/TAPS ACCESS DOORS: SUITABLE FOR PRESSURE CLASS AND INSULATION THICKNESS. PROVIDE ON BOTH SIDES OF COIL. 6.INSULATION, ASTM E84 MAX FLAME-SPREAD INDEX OF 25; MAX SMOKE-DEVELOPED INDEX OF 50 W: FLEXIBLE GLASS FIBER WRAP, ASTM C553, FSK JACKET WITH KRAFT VAPOR BARRIER FACING, K-VALUE OF 0.22 -0.29 BTU-IN/HR-FT²-˚F @ 75 ˚F, 0.75 PCF 1 04/03/20 ISSUE FOR DD REVIEW 2 05/19/20 ISSUE FOR COORDINATED REVIEW 3 06/05/20 ISSUE FOR CONSTRUCTION ABBREVIATIONS A - AMPERE AFC - ABOVE FINISHED CEILING AFF - ABOVE FINISHED FLOOR AIC - AMPS INTERRUPTING CAPACITY BLDG - BUILDING C - CONDUIT CKT - CIRCUIT CL - CENTERLINE DWG - DRAWING E - EXISTING TO REMAIN EC - ELECTRICAL CONTRACTOR EM - EMERGENCY EMT - ELECTRICAL METALLIC TUBING FVNR - FULL VOLTAGE NON-REVERSING G - GROUND GC - GENERAL CONTRACTOR GFI - GROUND FAULT INTERRUPTER JB - JUNCTION BOX KVA - KILOVOLTAMPERES KW - KILOWATT MC - MECHANICAL CONTRACTOR MCB - MAIN CIRCUIT BREAKER MDP - MAIN DISTRIBUTION PANEL MLO - MAIN LUG ONLY P - POLE PH - PHASE PVC - POLYVINYL CHLORIDE R - REMOVE RE - REPLACE EXISTING REL - RELOCATED RI - REMOVE AND REINSTALL RL - RELOCATE EXISTING RM - ROOM UTV - UNDERVOLTAGE TRIP V - VOLT W - WIRE WP - WEATHER PROOF XFMR - TRANSFORMER ELECTRICAL NOTES 1. ALL WORK SHALL BE PERFORMED AND INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF THE CORNELL UNIVERSITY ELECTRICAL STANDARDS. THE NATION ELECTRIC CODE(NFPA 70) AND ANY GOVERNING CODES AND STANDARDS HAVING JURISDICTION. 2. REFER TO CORNELL UNIVERSITY ELECTRICAL STANDARDS FOR ALL SPECIFICATION REQUIREMENTS. 3. ALL EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH ARTICLE 250 OF THE NATIONAL ELECTRIC CODE. 4. CONTRACTORS SHALL PAY FOR AND SECURE ALL PERMITS AND UNDERWRITERS CERTIFICATES. 5. PRIOR TO BID, THE CONTRACTOR SHALL VISIT THE SITE TO FAMILIARIZE HIMSELF WITH THE EXISTING FIELD CONDITIONS. HIS BID SHALL INCLUDE THE FURNISHING AND INSTALLATION OF ALL LABOR, TOOLS, MATERIAL, EQUIPMENT, SERVICES AND RELATED ACCESSORIES NECESSARY FOR THE COMPLETE INSTALLATION OF THE ELECTRICAL WORK SHOWN ON THE DRAWINGS AND REQUIRED BY CODE. 6. THE ELECTRICAL CONTRACTOR SHALL FURNISH ALL METERS, INSTRUMENTS, CABLE CONNECTION, EQUIPMENT, OR APPARATUS ESSAY FOR MAKING ALL TESTS. 7. THE CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL EQUIPMENT AND SYSTEMS AGAINST HARMFUL EXPOSURE OR ACCUMULATION OF DUST/MOISTURE, CORROSION OR OTHER FORMS OF DAMAGE. CLEAN AND RESTORE DAMAGED FINISHES. 8. CONTRACTOR SHALL COORDINATE PROJECT WORK WITH ALL TRADES AND ASSIST IN SCHEDULING WITH ALL TRADES. 9. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, PATCHING, AND REFINISHING OF WORK AREA RELATED TO ELECTRICAL PROJECT WORK. RESTORE AREA TO ORIGINAL CONDITION. 10. CONTRACTOR IS RESPONSIBLE FOR REMOVAL OF ALL WASTE MATERIALS IN A LAWFUL MANNER AND LEAVE THE SITE FREE OF ALL DEBRIS. 11. THE TERM "PROVIDE" DENOTES TO FURNISH AND INSTALL. 12. THE TERM "WIRING" DENOTES WRING AND RACEWAY. 13. UNLESS OTHERWISE NOTED, WHERE A DEVICE OR WIRING IS REMOVED, THE CONTRACTOR SHALL DISCONNECT AND REMOVE THE ASSOCIATED WIRING AND CONTROLS. 14. WHERE A DEVICE IS RELOCATED, DISCONNECT, REMOVE AND STORE THE NOTED DEVICE. EXISTING WIRING SHALL REMAIN. PROVIDE RELOCATION OF DEVICE PER CONSTRUCTION SCHEDULE. RECONNECT TO EXISTING WIRING. EXTEND WIRING AS REQUIRED, MATCH EXISTING. 15. THE CONTRACTOR IS RESPONSIBLE FOR MAINTAINING SERVICE TO THE BALANCE OF ANY EXISTING CIRCUITS THAT ARE AFFECTED BY THIS PROJECT AND THAT EXTEND OUT OF THE PROJECT AREA. EXTEND WIRING AS REQUIRED, MATCH EXISTING. 16. COORDINATE ALL DEMOLITION WORK WITH CORNELL UNIVERSITY PRIOR TO ANY SHUTDOWNS OR REMOVAL OF DEVICES AND/OR WIRING. 17. COORDINATE ALL COMMUNICATIONS WORK WITH CORNELL UNIVERSITY I/T GROUP. 18. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COMPLETING A PANEL WALK DOWN FOR EACH PANEL BEING AFFECTED FOR THIS PROJECT TO DETERMINE REQUIREMENTS AND COORDINATE SHUTDOWNS WITH CORNELL UNIVERSITY. ELECTRICAL SYMBOLS LEGEND SYMBOL DESCRIPTION RECEPTACLE QUADRUPLEX RECEPTACLE GFCI RECEPTACLE J JUNCTION BOX THREE WAY SWITCH OCCUPANY SENSOR 3 OS OCCUPANY SENSOR RED LIGHT SWITCH R 2" X 4' LIGHT FIXTURE 2' x 2' LIGHT FIXTURE ROUND RED LENSED LIGHT FIXTURE R HEAT DETECTOR 135 H SMOKE DETECTOR FIRE ALARM HORN FIRE ALARM PULL STATION DATA OUTLET F LS LIGHT LEVEL SENSOR BUILDING WIRE AND CABLE A. PROVIDE PRODUCTS AS FOLLOWS: 1. SOLID CONDUCTOR FOR FEEDERS AND BRANCH CIRCUITS 10 AWG AND SMALLER. 2. STRANDED CONDUCTORS FOR CONTROL CIRCUITS. 3. CONDUCTOR NOT SMALLER THAN #12 AWG FOR POWER AND LIGHTING CIRCUITS. 4. CONDUCTOR NOT SMALLER THAN #16 AWG FOR CONTROL CIRCUITS. 5. 10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS LONGER THAN 75 FEET. 6. 10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS LONGER THAN 200 FEET. B. WIRING METHODS: PROVIDE THE FOLLOWING WIRING METHODS: 1. CONCEALED DRY INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN INSULATION, IN RACEWAY. 2. ABOVE ACCESSIBLE CEILINGS: USE ONLY BUILDING WIRE, TYPE THHN/THWN INSULATION, IN RACEWAY. 3. WET OR DAMP INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN INSULATION, IN RACEWAY. 4. UNDERGROUND LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN INSULATION, IN RACEWAY. C. WIRE AND CABLE ROUTING INDICATED IS APPROXIMATE UNLESS DIMENSIONED. INCLUDE WIRE AND CABLE LENGTHS WITHIN 10 FT OF LENGTH SHOWN. D. COMPLETELY AND THOROUGHLY SWAB RACEWAY BEFORE INSTALLING WIRE. E. NEATLY TRAIN AND LACE WIRING INSIDE BOXES, EQUIPMENT, AND PANELBOARDS. F. SPECIAL TECHNIQUES--BUILDING WIRE IN RACEWAY: 1. PULL CONDUCTORS INTO RACEWAY AT SAME TIME. 2. INSTALL BUILDING WIRE 4 AWG AND LARGER WITH PULLING EQUIPMENT. G. SPECIAL TECHNIQUES - CABLE: 1. PROTECT EXPOSED CABLE FROM DAMAGE. 2. SUPPORT CABLES ABOVE ACCESSIBLE CEILING, USING SPRING METAL CLIPS OR CABLE TIES TO SUPPORT CABLES FROM STRUCTURE OR CEILING SUSPENSION SYSTEM. DO NOT REST CABLE ON CEILING PANELS. 3. USE SUITABLE CABLE FITTINGS AND CONNECTORS. H. SPECIAL TECHNIQUES - DIRECT BURIAL CABLE: 1. TRENCH AND BACKFILL FOR DIRECT BURIAL CABLE INSTALLATION. INSTALL WARNING TAPE ALONG ENTIRE LENGTH OF DIRECT BURIAL CABLE, WITHIN 3 INCHES OF GRADE. 2. USE SUITABLE DIRECT BURIAL CABLE FITTINGS AND CONNECTORS. I. SPECIAL TECHNIQUES - WIRING CONNECTIONS: 1. CLEAN CONDUCTOR SURFACES BEFORE INSTALLING LUGS AND CONNECTORS. 2. MAKE SPLICES, TAPS, AND TERMINATIONS TO CARRY FULL AMPACITY OF CONDUCTORS WITH NO PERCEPTIBLE TEMPERATURE RISE. 3. TAPE UNINSULATED CONDUCTORS AND CONNECTORS WITH ELECTRICAL TAPE TO 150 PERCENT OF INSULATION RATING OF CONDUCTOR. 4. INSTALL SPLIT BOLT CONNECTORS OR MULTI-TAP BLOCKS FOR COPPER CONDUCTOR SPLICES AND TAPS, 6 AWG AND LARGER. 5. INSTALL SOLDERLESS PRESSURE CONNECTORS WITH INSULATING COVERS FOR COPPER CONDUCTOR SPLICES AND TAPS, 8 AWG AND SMALLER. 6. INSTALL INSULATED SPRING WIRE CONNECTORS WITH PLASTIC CAPS FOR COPPER CONDUCTOR SPLICES AND TAPS, 10 AWG AND SMALLER. 7. TERMINATE EXISTING ALUMINUM CONDUCTORS WITH TIN-PLATED, ALUMINUM-BODIED COMPRESSION CONNECTORS ONLY. FILL WITH ANTI-OXIDANT COMPOUND BEFORE INSTALLING CONDUCTOR. 8. INSTALL SUITABLE REDUCING CONNECTORS OR MECHANICAL CONNECTOR ADAPTORS FOR CONNECTING ALUMINUM CONDUCTORS TO COPPER CONDUCTORS. J. GROUND CONDUCTORS: 1. FOR 6 AWG AND SMALLER: GREEN. 2. FOR 4 AWG AND LARGER: IDENTIFY WITH GREEN TAPE AT BOTH ENDS AND VISIBLE POINTS INCLUDING JUNCTION BOXES. K. ALL WIRING SHALL BE #12 CU UNLESS SPECIFIED OTHERWISE. ELECTRICAL SPECIFICATIONS A. ALL ELECTRICAL WORK TO CONFORM TO: 1. NFPA 70 (NATIONAL ELECTRIC CODE) - CURRENT VERSION 2. NECA (NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION) - STANDARD OF INSTALLATION 3. NETA ATS (INTERNATIONAL ELECTRICAL TESTING ASSOCIATION) - ACCEPTANCE TESTING SPECIFICATIONS FOR ELECTRICAL POWER DISTRIBUTION EQUIPMENT AND SYSTEMS. 4. NFPA 72 (NATIONAL FIRE PROTECTION ASSOCIATION - NATIONAL FIRE ALARM CODE). 5. ALL APPLICABLE LOCAL CODES. B. ALL WORK SHOWN ON THIS DRAWING IS THE RESPONSIBILITY OF THE CONTRACTOR, UNLESS CLEARLY INDICATED AS PART OF ANOTHER PRIME CONTRACT. C. PROVIDE TEMPORARY POWER REQUIRED FOR ALL TRADES. D. MATCH OWNERS EXISTING STANDARD EQUIPMENT. E. COORDINATE WORK TO MINIMIZE OUTAGE DURATION. F. OBTAIN ALL REQUIRED PERMITS & INSPECTIONS. G. PROVIDE FOR ELECTRICAL INSPECTIONS AND SUBMIT REPORTS TO THE OWNER. H. SUBMIT O&M MANUALS TO OWNER UPON COMPLETION OF WORK. I. PROVIDE TRAINING SESSION FOR DESIGNATED MAINTENANCE PERSONNEL. J. PROVIDE SUBMITTALS FOR ALL ELECTRICAL EQUIPMENT, EXCLUDING WIRE, CONDUIT, AND FASTENERS. 1. HANDHOLES. 2. PANELBOARDS - SHOP DRAWINGS (INDICATE OUTLINE AND SUPPORT POINT DIMENSIONS, VOLTAGE, MAIN BUS AMPACITY, INTEGRATED SHORT CIRCUIT AMPERE RATING, CIRCUIT BREAKER AND FUSIBLE SWITCH ARRANGEMENT AND SIZES) AND CATALOG DATA SHOWING SPECIFIED FEATURES OF STANDARD PRODUCTS. 3. ENCLOSED SWITCHES - SWITCH RATINGS AND ENCLOSURE DIMENSIONS. 4. DEVICES - MANUFACTURER'S CATALOG INFORMATION SHOWING DIMENSIONS, COLORS, AND CONFIGURATIONS. 5. LUMINAIRES (INCLUDING EMERGENCY & EXIT FIXTURES) - CATALOG INFORMATION SHOWING DIMENSIONS, RATINGS, AND PERFORMANCE DATA. K. SELECT MATERIALS, SIZES, AND TYPES OF ANCHORS, FASTENERS, AND SUPPORTS TO CARRY LOADS OF EQUIPMENT AND RACEWAY, INCLUDING WEIGHT OF WIRE AND CABLE IN RACEWAY. GROUNDING SYSTEMS A. GROUNDING SYSTEM RESISTANCE: 25 OHMS. B. GROUNDING SYSTEMS: 1. MECHANICAL CONNECTORS: BRONZE CONNECTORS, SUITABLE FOR GROUNDING AND BONDING APPLICATIONS, IN CONFIGURATIONS REQUIRED FOR PARTICULAR INSTALLATION. C. EXOTHERMIC CONNECTIONS: EXOTHERMIC MATERIALS, ACCESSORIES, AND TOOLS FOR PREPARING AND MAKING PERMANENT FIELD CONNECTIONS BETWEEN GROUNDING SYSTEM COMPONENTS. D. WIRE: STRANDED COPPER. E. GROUNDING ELECTRODE CONDUCTOR: SIZE TO MEET NFPA 70 AND LOCAL MUNICIPALITY REQUIREMENTS. F. INSTALLATION: 1. EQUIPMENT GROUNDING CONDUCTOR: INSTALL SEPARATE, INSULATED CONDUCTOR WITHIN EACH FEEDER AND BRANCH CIRCUIT RACEWAY. TERMINATE EACH END ON SUITABLE LUG, BUS, OR BUSHING. 2. DO NOT FASTEN SUPPORTS TO PIPES, DUCTS, MECHANICAL EQUIPMENT, OR CONDUIT. 3. OBTAIN PERMISSION FROM ARCHITECT/ENGINEER BEFORE USING POWDER-ACTUATED ANCHORS OR DRILLING OR CUTTING STRUCTURAL MEMBERS. HANGERS AND SUPPORTS A. ANCHORS & FASTENERS TO BE CORROSION RESISTANT. B. ANCHOR AND FASTEN ELECTRICAL PRODUCTS TO BUILDING ELEMENTS AND FINISHES AS FOLLOWS: 1. CONCRETE STRUCTURAL ELEMENTS: PROVIDE EXPANSION ANCHORS. 2. STEEL STRUCTURAL ELEMENTS: PROVIDE BEAM CLAMPS AND SPRING STEEL CLIPS. 3. CONCRETE SURFACES: PROVIDE EXPANSION ANCHORS. 4. HOLLOW MASONRY, PLASTER, AND GYPSUM BOARD PARTITIONS: PROVIDE TOGGLE BOLTS AND HOLLOW WALL FASTENERS. 5. SOLID MASONRY WALLS: PROVIDE EXPANSION ANCHORS. 6. SHEET METAL: PROVIDE SHEET METAL SCREWS. 7. WOOD ELEMENTS: PROVIDE WOOD SCREWS. C. SUPPORTS: 1. FABRICATE SUPPORTS FROM STRUCTURAL STEEL OR FORMED STEEL MEMBERS. RIGIDLY WELD MEMBERS OR INSTALL HEXAGON HEAD BOLTS TO PRESENT NEAT APPEARANCE WITH ADEQUATE STRENGTH AND RIGIDITY. INSTALL SPRING LOCK WASHERS UNDER NUTS. 2. INSTALL SURFACE MOUNTED CABINETS AND PANELBOARDS WITH MINIMUM OF FOUR ANCHORS. 3. IN WET AND DAMP LOCATIONS INSTALL STEEL CHANNEL SUPPORTS TO STAND CABINETS AND PANELBOARDS 1 INCH OFF WALL. 4. INSTALL SHEET METAL CHANNEL TO BRIDGE STUDS ABOVE AND BELOW CABINETS AND PANELBOARDS RECESSED IN HOLLOW PARTITIONS. EXISTING WORK A. PRIOR TO CONSTRUCTION & INSTALLATION, CONTRACTOR TO VERIFY EXISTING CONDITIONS AND NOTIFY ARCHITECT/ENGINEER OF CONFLICTS OR CONDITIONS WHICH INTERFERE WITH INSTALLATION AS SET FORTH IN CONTRACT DOCUMENTS. B. CONTRACTOR RESPONSIBLE FOR ALL NEW FLOOR OPENINGS, EXCAVATIONS, AND PENETRATIONS,UNLESS SPECIFICALLY NOTED. UNLESS SPECIFICALLY NOTED, UPON COMPLETION, ALL PENETRATIONS TO BE SEALED TO MAINTAIN FIRE RATING AS SPECIFIED ON ARCHITECTURAL DRAWINGS. C. ALL CUTTING AND PATCHING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR, UNLESS CLEARLY INDICATED AS PART OF ANOTHER PRIME CONTRACT. D. COORDINATE ANY NEW ROOF PENETRATIONS WITH THE OTHER TRADES. E. REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE NEW CONSTRUCTION. F. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND EXTENSION WORK. G. MAINTAIN ACCESS TO EXISTING BOXES AND OTHER INSTALLATIONS REMAINING ACTIVE AND REQUIRING ACCESS. MODIFY INSTALLATION OR PROVIDE ACCESS PANEL. H. EXTEND EXISTING RACEWAY AND BOX INSTALLATIONS USING MATERIALS AND METHODS COMPATIBLE WITH EXISTING ELECTRICAL INSTALLATIONS, OR AS SPECIFIED. I. CLEAN AND REPAIR EXISTING COMPONENTS TO REMAIN OR TO BE REINSTALLED. J. PROVIDE ACCESS TO EXISTING WIRING CONNECTIONS REMAINING ACTIVE AND REQUIRING ACCESS. MODIFY INSTALLATION OR INSTALL ACCESS PANEL. K. EXTEND EXISTING CIRCUITS USING MATERIALS AND METHODS COMPATIBLE WITH EXISTING ELECTRICAL INSTALLATIONS, OR AS SPECIFIED. L. RING OUT CIRCUITS IN EXISTING PANEL AFFECTED BY THE WORK. WHERE ADDITIONAL CIRCUITS ARE NEEDED, REUSE CIRCUITS AVAILABLE FOR REUSE. INSTALL NEW BREAKERS. M. TAG UNUSED CIRCUITS AS SPARE AND SWITCH BREAKER TO THE "OFF" POSITION. N. WHERE EXISTING CIRCUITS ARE INDICATED TO BE REUSED, USE SENSING MEASURING DEVICES TO VERIFY CIRCUITS FEEDING PROJECT AREA OR ARE NOT IN USE. O. PROVIDE NEW UPDATED DIRECTORIES WHERE MORE THAN THREE CIRCUITS HAVE BEEN MODIFIED OR REWIRED. P. IDENTIFY SALVAGE ITEMS IN COOPERATION WITH OWNER. REMOVE AND PROTECT ITEMS TO BE SALVAGED AND TURN OVER TO OWNER. Q. CAREFULLY REMOVE EQUIPMENT, MATERIALS, OR FIXTURES WHICH ARE TO BE REUSED. MINOR ELECTRICAL DEMOLITION A. DEMOLITION DRAWINGS ARE BASED ON CASUAL FIELD OBSERVATION AND EXISTING RECORD DOCUMENTS. REPORT DISCREPANCIES TO ARCHITECT/ENGINEER BEFORE DISTURBING EXISTING INSTALLATION. B. CEASE OPERATIONS IMMEDIATELY WHEN STRUCTURE APPEARS TO BE IN DANGER AND NOTIFY ARCHITECT/ENGINEER. DO NOT RESUME OPERATIONS UNTIL DIRECTED. C. VERIFY WIRING AND EQUIPMENT INDICATED TO BE DEMOLISHED SERVE ONLY ABANDONED FACILITIES. D. PROVIDE TEMPORARY EGRESS SIGNAGE AND EMERGENCY LIGHTING. E. DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS SCHEDULED FOR REMOVAL. REMOVE CONDUIT, WIRE, BOXES, AND FASTENING DEVICES TO AVOID ANY INTERFERENCE WITH NEW INSTALLATION. F. INSTALL TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. G. REMOVE EXPOSED ABANDONED WIRE, CABLE, CONDUIT, GROUNDING AND BONDING COMPONENTS, FASTENERS AND SUPPORTS, AND ELECTRICAL IDENTIFICATION COMPONENTS, INCLUDING ABANDONED COMPONENTS ABOVE ACCESSIBLE C CEILING FINISHES. CUT EMBEDDED CONDUITS AND SUPPORT ELEMENTS FLUSH WITH WALLS AND FLOORS. PATCH SURFACES DAMAGED BY REMOVAL OF EXISTING COMPONENTS. H. DISCONNECT ABANDONED CIRCUITS AND OUTLETS AND REMOVE ABANDONED RACEWAY, OUTLETS, BOXES, WIRE, AND CABLE INCLUDING ABOVE ACCESSIBLE CEILING FINISHES. CUT RACEWAY FLUSH WITH WALLS AND FLOORS, AND PATCH SURFACES. REMOVE CONCEALED ABANDONED RACEWAY TO ITS SOURCE. I. RECONNECT EQUIPMENT BEING DISTURBED BY RENOVATION WORK AND REQUIRED FOR CONTINUED SERVICE TO NEAREST AVAILABLE PANEL. REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE NEW CONSTRUCTION. J. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND EXTENSION WORK. K. CLEAN AND REPAIR EXISTING EQUIPMENT TO REMAIN (AFFECTED BY THE SCOPE OF THE PROJECT) OR TO BE REINSTALLED. L. PROTECT AND RETAIN POWER TO EXISTING ACTIVE EQUIPMENT REMAINING. M. CAP ABANDONED EMPTY CONDUIT AT BOTH ENDS AND MARK AS SPARE. RACEWAY AND BOXES A. PROVIDE RACEWAY AND BOXES LOCATED AS INDICATED, AND AT OTHER LOCATIONS REQUIRED FOR SPLICES, TAPS, WIRE PULLING, EQUIPMENT CONNECTIONS, AND COMPLIANCE WITH REGULATORY REQUIREMENTS. RACEWAY AND BOXES ARE SHOWN IN APPROXIMATE LOCATIONS UNLESS DIMENSIONED. PROVIDE RACEWAY TO COMPLETE WIRING SYSTEM. B. UNDERGROUND MORE THAN 5 FEET OUTSIDE FOUNDATION WALL: PROVIDE SCHEDULE 80 PVC. PROVIDE CAST METAL BOXES OR NONMETALLIC HANDHOLES WHERE REQUIRED. C. UNDERGROUND WITHIN 5 FEET FROM FOUNDATION WALL: PROVIDE RIGID STEEL CONDUIT OR THICKWALL NONMETALLIC CONDUIT (SCHEDULE 80 PVC). PROVIDE CAST METAL OR NONMETALLIC BOXES. D. IN OR UNDER SLAB ON GRADE: PROVIDE THICK WALL NONMETALLIC CONDUIT. PROVIDE CAST OR NONMETALLIC METAL BOXES. E. OUTDOOR LOCATIONS, ABOVE GRADE: PROVIDE RIGID STEEL CONDUIT. PROVIDE CAST METAL OR NONMETALLIC OUTLET, PULL, AND JUNCTION BOXES. F. IN SLAB ABOVE GRADE: PROVIDE THICKWALL NONMETALLIC CONDUIT. PROVIDE CAST NONMETALLIC BOXES. G. WET AND DAMP LOCATIONS: PROVIDE THICKWALL NONMETALLIC CONDUIT. PROVIDE CAST METAL OR NONMETALLIC OUTLET, JUNCTION, AND PULL BOXES. PROVIDE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS. H. CONCEALED DRY LOCATIONS: PROVIDE ELECTRICAL METALLIC TUBING. PROVIDE SHEET-METAL BOXES. PROVIDE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS. PROVIDE HINGED ENCLOSURE FOR LARGE PULL BOXES. I. MINIMUM RACEWAY SIZE: 3/4 INCH UNLESS OTHERWISE SPECIFIED. J. ARRANGE RACEWAY AND BOXES TO MAINTAIN HEADROOM AND PRESENT NEAT APPEARANCE. GROUP RELATED RACEWAY; SUPPORT USING CONDUIT RACK; PROVIDE SPACE ON EACH FOR 25 PERCENT ADDITIONAL RACEWAYS. K. RACEWAY ROUTING IS SHOWN IN APPROXIMATE LOCATIONS UNLESS DIMENSIONED. ROUTE TO COMPLETE WIRING SYSTEM. L. DO NOT SUPPORT RACEWAY WITH WIRE, PERFORATED PIPE STRAPS, CEILING SUPPORT WIRES OR OTHER PIPING SYSTEMS. M. ROUTE EXPOSED & ABOVE ACCESSIBLE CEILINGS RACEWAY PARALLEL AND PERPENDICULAR TO WALLS. N. DO NOT CROSS CONDUITS IN SLAB. O. INSTALL NO MORE THAN EQUIVALENT OF THREE 90 DEGREE BENDS BETWEEN BOXES. INSTALL CONDUIT BODIES TO MAKE SHARP CHANGES IN DIRECTION, AS AROUND BEAMS. INSTALL FACTORY ELBOWS FOR BENDS IN METAL CONDUIT LARGER THAN 2 INCH SIZE. P. AVOID MOISTURE TRAPS; INSTALL JUNCTION BOX WITH DRAIN FITTING AT LOW POINTS IN CONDUIT SYSTEM. Q. INSTALL FITTINGS TO ACCOMMODATE EXPANSION AND DEFLECTION WHERE RACEWAY CROSSES SEISMIC, CONTROL AND EXPANSION JOINTS. R. INSTALL SUITABLE PULL STRING OR CORD IN EACH EMPTY RACEWAY EXCEPT SLEEVES AND NIPPLES. S. CLOSE ENDS AND UNUSED OPENINGS IN WIREWAY. T. INSTALL PULL BOXES AND JUNCTION BOXES ABOVE ACCESSIBLE CEILINGS AND IN UNFINISHED AREAS ONLY. U. IN ACCESSIBLE CEILING AREAS: INSTALL OUTLET AND JUNCTION BOXES NO MORE THAN 6 INCHES FROM CEILING ACCESS PANEL OR FROM REMOVABLE RECESSED LUMINAIRE. V. LOCATE FLUSH MOUNTING BOX IN MASONRY WALL TO REQUIRE CUTTING OF MASONRY UNIT CORNER ONLY. COORDINATE MASONRY CUTTING TO ACHIEVE NEAT OPENING. W. DO NOT INSTALL FLUSH MOUNTING BOX BACK-TO-BACK IN WALLS; INSTALL WITH MINIMUM 6 INCHES SEPARATION. INSTALL WITH MINIMUM 24 INCHES SEPARATION IN ACOUSTIC RATED WALLS. X. DO NOT FASTEN BOXES TO CEILING SUPPORT WIRES OR OTHER PIPING SYSTEMS. Y. SUPPORT BOXES INDEPENDENTLY OF CONDUIT. Z. USE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS. AA. SET FLOOR BOXES LEVEL AND FLUSH WITH FINISH FLOORING MATERIAL AB. INSTALL CONDUIT TO PRESERVE FIRE RESISTANCE RATING OF PARTITIONS AND OTHER ELEMENTS. AC. ROUTE CONDUIT THROUGH ROOF OPENINGS FOR PIPING AND DUCTWORK OR THROUGH SUITABLE ROOF JACK WITH PITCH POCKET AD. ALIGN ADJACENT WALL MOUNTED OUTLET BOXES FOR SWITCHES, THERMOSTATS, AND SIMILAR DEVICES. WALL PLATES A. MANUFACTURERS: 1. PASS & SEYMOUR LEGRAND. 2. TAYMAC 20510 (WEATHERPROOF-IN-USE). 3. HUBELL (BELL/RACO). 4. LEVITON. 5. GENERAL ELECTRIC. B. INSTALL DECORATIVE PLATES ON SWITCH, RECEPTACLE, AND BLANK OUTLETS IN FINISHED AREAS. DECORATIVE COVER PLATE: NYLON. C. INSTALL JUMBO SIZE PLATES FOR OUTLETS INSTALLED IN MASONRY WALLS. JUMBO COVER PLATE: NYLON. D. WEATHERPROOF COVER PLATE (RECEPTACLE): IMPACT RESISTANT PLASTIC PLATE WITH HINGED AND GASKETED DEVICE COVER. COVER TO BE RATED FOR WET LOCATION WHILE IN USE, AND TO BE LOCKABLE. E. WEATHERPROOF COVER PLATE (SWITCH): GASKETED CAST METAL PLATE WITH HINGED AND GASKETED DEVICE COVER OR LEVER SWITCH MECHANISM. (P&S CA-31G/HUBBELL/BELL/RACO 5125 OR EQUAL) F. KITCHEN AREAS: 302/430 STAINLESS STEEL, WEATHERPROOF FOR STARTUPS. G. INSTALL GALVANIZED (STAMPED) STEEL PLATES ON OUTLET BOXES AND JUNCTION BOXES IN UNFINISHED AREAS, ABOVE ACCESSIBLE CEILINGS, AND ON SURFACE MOUNTED OUTLETS. H. INSTALL DEVICES PLUMB AND LEVEL. I. INSTALL SWITCHES WITH OFF POSITION DOWN. J. INSTALL RECEPTACLES WITH GROUNDING POLE ON TOP, OR TO THE LEFT (IF MOUNTED HORIZONTALLY. K. CONNECT WIRING DEVICE GROUNDING TERMINAL TO OUTLET BOX WITH BONDING JUMPER AND BRANCH CIRCUIT EQUIPMENT GROUNDING CONDUCTOR. L. CONNECT WIRING DEVICES BY WRAPPING SOLID CONDUCTOR AROUND SCREW TERMINAL. INSTALL STRANDED CONDUCTOR FOR BRANCH CIRCUITS 10 AWG AND SMALLER. WHEN STRANDED CONDUCTORS ARE USED IN LIEU OF SOLID, USE CRIMP ON FORK TERMINALS FOR DEVICE TERMINATIONS. DO NOT PLACE BARE STRANDED CONDUCTORS DIRECTLY UNDER DEVICE SCREWS. M. ADJUST DEVICES AND WALL PLATES TO BE FLUSH AND LEVEL.CORN E LL U N I V E R SI TYFOUN D E D 5681AD FACILITIES ENGINEERING ARCHIVE BAR CODEITHACA, NEW YORK ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 109 TOWER ROAD URIS HALL BASEMENT LAB RENOVATION E-001 2200272.03 ELECTRICAL NOTES, SYMBOL LEGEND, & ABBREVIATIONS RDH MPS 2087 06/05/2020 CEX ^^ ELSIOR ^^^^^^ 077 4 2 5L E D ESNECI FORP ROISS LAN EENIGNERANDYD.HE A RDSTATE O F NEW Y ORK B 15VS VS VS B 1515VS 15Room B48 Room B50A Room B50 Room B52 BOOCH1212 Room B52 Room B50A Room B50 Room B48 BOOCH1212 30 LPE-M-BA LS LS LS +60 AFF A2 A2 A2 A2 A2 A2A2 A3 A3 32 LPE-M-BA Room 39A Room 39 BOOCH 1212 Room 39 Room 39A BOOCH 1212LS A2 A3 A2 A2 34 LPE-M-BA GENERAL DRAWING NOTES: CONTRACTOR TO TRACE OUT EXISTING CIRCUITS AND UPDATE PANEL SCHEDULES ACCORDINGLY. ELECTRICAL CONTRACTOR RESPONSIBLE FOR COMPLETING A PANEL WALK DOWN FOR EACH PANEL BEING AFFECTED FOR THIS PROJECT TO DETERMINE REQUIREMENTS AND COORDINATE SHUTDOWNS. UNLESS OTHERWISE NOTED, EXISTING CONDITIONS ARE SHOWN IN GRAYSCALED, DEMOLITION WORK IS SHOWN IN BOLD AND DASHED, PROJECT WORK SHOWN IN BOLD. PROVIDE NEW WORK AS SHOWN. CONTRACTOR TO PROVIDE, TEST, AND TERMINATE ALL NETWORK DROPS IDENTIFIED AS NEW WORK. PROVIDE (2) CONNECTIONS AT EACH FACEPLATE. ALL NETWORK WIRING TO RUN TO CLOSET LOCATED IN ROOM G30(REFER TO KEYPLANS) PROVIDE RECESSED BOXES AND RACEWAYS IN NEW WALL. ALL NEW WIRING AND DEVICES TO BE INSTALLED RECESSED TO FACILITATE WASH DOWN. ALL NEW RECEPTACLES TO BE WEATHER PROOF AND GASKETED COVERS. CONTRACTOR TO MATCH EXISTING RECEPTACLE HEIGHT UNLESS OTHERWISE NOTED. A. B. C. D. E. F. G. B22 B24 B20 B26 B39 B39A B48 B50A B52 B50 B55 DISCONNECT EXISTING LIGHT FIXTURES. SAVE CIRCUIT AND WIRING TO RE-CONNECT TO NEW LIGHT FIXTURES. DISCONNECT EXISTING LIGHT LEVEL CONTROL SENSOR. SAVE WIRING TO RE-CONNECT TO NEW LIGHTING CONTROL SENSOR. 1 DEMOLITION KEYED NOTES: TYPICAL ALL SHEETS," KEYNOTES ARE COMMON FOR ALL SHEETS" EACH KEYNOTE MAY NOT APPEAR IN PLANS ON EVERY SHEET. 2 1 2 KEYED NOTES: TYPICAL ALL SHEETS," KEYNOTES ARE COMMON FOR ALL SHEETS" EACH KEYNOTE MAY NOT APPEAR IN PLANS ON EVERY SHEET. 3 EXTEND WIRING TO CONNECT TYPE A2 FIXTURES TO EXISTING SWITCHING AND CIRCUITING. PROVIDE ADDITIONAL SWITCH FOR TYPE A3 VIVARIUM FIXTURES AND CONNECT TO EXISTING CIRCUIT. PROVIDE RECEPTACLES FOR SURGERY LIGHT. PROVIDE NEW LIGHTING SENSOR (KELE-MK7-B-CCF-0/5) AND TIE BACK TO EXISTING SYSTEM TO MAINTAIN EXISTING CONTROL SCHEME. 1/4" = 1'-0"E-101 1 PARTIAL BASEMENT ELECTRICAL REMOVAL PLAN B48, B50, B50A, B52 1/4" = 1'-0"E-101 2 PARTIAL BASEMENT ELECTRICAL PLAN B48, B50, B50A, B52 N N 0'2'4'8'0'2'4'8' 1/4" = 1'-0"E-101 4 PARTIAL BASEMENT ELECTRICAL REMOVAL PLAN B39,B39A 1/4" = 1'-0"E-101 5 PARTIAL BASEMENT ELECTRICAL PLAN B39, B39A N 0'2'4'8' N 0'2'4'8' 1" = 30'-0"E-101 3 ELECTRICAL PANEL KEY PLAN N AREA OF WORK AREA OF WORK AREA OF WORK APBK APBD LPE-M-BA APBC 2 1 1 2 1 1 1 2 2 2 1 13 1 3 1 3 APS-BA APS-BB 1 1 CORN E LL U N I V E R SI TYFOUN D E D 5681AD FACILITIES ENGINEERING ARCHIVE BAR CODEITHACA, NEW YORK ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 109 TOWER ROAD URIS HALL BASEMENT LAB RENOVATION E-101 2200272.03 PARTIAL BASEMENT FLOOR ELECTRICAL PLAN NOT USED MPS 2087 06/05/2020 3 CEX ^^ ELSIOR ^^^^^^ 077 4 2 5L E D ESNECI FORP ROISS LAN EENIGNERANDYD.HE A RDSTATE O F NEW Y ORKA3 34 LPE-M-BA 1 3 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 PANEL NAME: LPE-M-BA LOCATION: XXXXX RATING: 225A MAIN: 225A MLO ELECTRICAL PANEL SCHEDULE LPE-M-BA SERVICE: 120/208V/3PH/4W MOUNTING: RECESSED FEED: XXXXX kAIC RATING: XXXXX CKT LOAD DESIGNATION BREAKER TRIP/POLES LOAD WATTS PHASE CKTLOAD WATTS BREAKER TRIP/POLES LOAD DESIGNATION LIGHTING CORRIDOR E-G-H 20A/1P RECEPTACLES CORRIDOR I 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 40A/3P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P LIGHTING B-38, B-38A 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P 20A/1P A B C A B C A B C A B C A B C A B C A B C UNKNOWN UNKNOWN LIGHTING GROUND EAST CORRIDOR LIGHTING 1ST EAST CORRIDOR LIGHTING 2ND EAST CORRIDOR LIGHTING 3RD EAST CORRIDOR LIGHTING 4TH EAST CORRIDOR LIGHTING ELEVATOR NORTH LIGHTING ELEVATOR SOUTH RECEPTACLES B04 LIGHTING N.E. STAIRWELL LIGHTING N.W. STAIRWELL LIGHTING FREIGHT ELEVATOR PLUGMOLD B06 EXHAUST FAN 14 PLUGMOLD B06 SPARE SPARE SPARE SPARE SPARE SPACE SPARE SPARE UNDERGROUND CIR. CENTER B43 RECEPTACLE SOUTH WALL RM. B48 RECEPTACLES ROOM B48, & B50A SPACE RECEPTACLE NORTH WALL RM. 39A SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE LIGHT FIXTURE SCHEDULE TYPE LAMP DESCRIPTION MANUFACTURER MODEL # MOUNTING COMMENTS A2 LED 1X4 KENALL SIMPLESEAL #HSES014-50L40K-DCC-DV-5F-5H-SYM SURFACE MOUNT A3 LED 1X4 RED LIGHT KENALL SIMPLESEAL #CSES014-23R-40K8-DIM1-DV-5F-5H-SYM-AMF SURFACE MOUNT CORN E LL U N I V E R SI TYFOUN D E D 5681AD FACILITIES ENGINEERING ARCHIVE BAR CODEITHACA, NEW YORK ARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: DATE: FACILITY: DESIGN: DRAWN: WWW.FCS.CORNELL.EDU IT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING REVISIONS ARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING 201 HUMPHREYS SERVICE BLDG ITHACA, NEW YORK 14853-3701 109 TOWER ROAD URIS HALL BASEMENT LAB RENOVATION E-600 2200272.03 ELECTRICAL SCHEDULES Designer MPS 2087 06/05/2020 CEX ^^ ELSIOR ^^^^^^ 077 4 2 5L E D ESNECI FORP ROISS LAN EENIGNERANDYD.HE A RDSTATE O F NEW Y ORK