Loading...
HomeMy WebLinkAboutAddendum 1_ADD 1 Drawings_Snee Reno for Colocation of EAS_8-14-2020SDOS1134Map RoomEXISTING GYPSUM CEILING TO REMAINREPLACE LIGHT FIXTURES WITH NEW LED FIXTURESMOTORIZED ROLLER SHADE14'-2" V.I.F.F4A5516'-4" V.I.F.6'-4" V.I.F.PROVIDE METAL FRAMING TO DECK ABOVE TO SUPPORT MICROPHONE. INSTALL MICROPHONE CEILING MOUNTING FRAME. COORDINATE WITH AV VENDOR.2'-0"PROVIDE SKYLIGHT PERFORMANCE FILM FOR ALL SLOPED GLAZINGSPEAKER HOLES IN FINISHED CEILING TO BE CUT BY GC. COORDINATE WITH AV VENDOR.LINEAR PENDANT LIGHT FIXTURELINEAR SURFACE MOUNTED LIGHT FIXTURELAY-IN DIRECT/INDIRECT LIGHT FIXTURES RECESSED CAN LIGHT FIXTURERETURN AIR GRILLESUPPLY AIR GRILLEMANUAL PROJECTION SCREENMOTORIZED PROJECTION SCREENSOFFIT MOUNTED LINEAR LIGHT FIXTURESSPRINKLER HEADEXIT SIGNFIRE DETECTOROCCUPANCY SENSORSPEAKERGYPSUM BOARD CEILING2' X 2' ACOUSTICAL PANEL CEILINGREFLECTED CEILING PLAN NOTES:1. ALL LAY-IN ACOUSTIC CEILINGS ARE 8'-8 1/2" ABOVE FINISHED FLOOR, UNLESS OTHERWISE NOTED.2. ALL GYPSUM SOFFITS AND CEILINGS ARE 8'-8" ABOVE FINISHED FLOOR, UNLESS OTHERWISE NOTED.3. MOUNT ALL SPRINKLER HEADS, ELECTRICAL DEVICES, LIGHT FIXTURES, ETC. CENTERED IN 2'X2' ACOUSTIC CEILING PANELS, UNLESS OTHERWISE NOTED.4. CENTER ACOUSTIC CEILING PANELS WITHIN FIELD AS INDICATED ON REFLECTED CEILING PLANS, PROVIDING NUMBER OF PANELS SHOWN, UNLESS OTHERWISE NOTED.5. REPAIR CEILINGS AFFECTED BY HVAC WORK.6. PROVIDE PROJECTOR MOUNT FRAMING AS NEEDED FOR INSTALL.7. REPAIR CEILINGS AFFECTED BY AV WORK. CEILING MATERIALS:LIGHT FIXTURES:OTHER:CEILING MOUNTED 2" ACOUSTICAL PANELPROJECTOR112161AComputer Lab2161Workroom2161BIT Office2149SharedWorkspace2014ToiletA4A551A4A551334 SF2160Admin Suite170 SF2160AOffice210 SF2160BChair Office117 SF2160COffice127 SF2160DOffice125 SF2102OfficeA4A551A4A551A4A551A4A551A4A551A4A551D4A551A4A551A4A551A1A551F1A551755 SF2152Classroom155 SF3116Kitchenette1140 SF3161SharedWorkspace717 SF3147SharedWorkspace59 SF3014ToiletA4A551A4A551D1A551ALTERNATE 1A1A551453 SF4122Pryor Lab296 SF4120Office55 SF4114KitchenetteQUAD POWER CORD REEL, RELOCATED FROM BRADFIELD HALLCOORDINATE FINAL LOCATION WITH OWNER PAINT EXPOSED CONCRETETYP.2'-0"8'-0"10'-0"8'-0"5'-0"2'-0"D1A5511/8" = 1'-0"F1PARTIAL FIRST FLOOR RCP - MAP ROOMWARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910NA151PARTIALREFLECTEDCEILING PLANS7/30/202011365/ COB #1921MDCORNELL UNIVERSITYConstruction DocumentsSnee Hall Renovation for Colocation of EAS112 Hollister Drive1/8" = 1'-0"A1PARTIAL SECOND FLOOR RCP1/8" = 1'-0"D6PARTIAL THIRD FLOOR RCP1/8" = 1'-0"A6PARTIAL FOURTH FLOOR RCP# Description Date1 Addendum #1 08/12/2020 FINISH NOTES:1. ALL WALLS IN WORK AREAS TO BE PAINTED W1 UNLESS OTHERWISE NOTED.2. ALL GYPSUM BOARD CEILINGS IN WORK AREAS TO BE PAINTED W3 UNLESS OTHERWISE NOTED ON REFLECTED CEILING PLAN.3. HM DOORS / FRAMES AND PAINTED WINDOW TRIM / FRAMES SHALL BE PAINTED W1B UNLESS OTHERWISE NOTED.4. ALL WALL BASE TO BE B1 UNLESS OTHERWISE NOTED.5. ALL CEILING WITHIN WORK AREAS TO BE ACP UNLESS OTHERWISE NOTED. NO TILE TO BE CUT LESS THAN 6". REFER TO RCP FOR LAYOUT6. SEE INTERIOR ELEVATIONS FOR ADDITIONAL WALL AND BASE FINISHES, TYPICAL.7. SEE REFLECTED CEILING PLAN FOR ADDITIONAL FINISH INFORMATION, TYPICAL.8. SEE INTERIOR ELEVATIONS FOR WALL TILE LAYOUT AND LOCATION, TYPICAL.9. ALL FLOORING MATERIAL AND TRANSITIONS SHALL BE CENTERED UNDER THE DOOR IN THE CLOSED POSITION UNLESS OTHERWISE NOTED.10. MISCELLANEOUS ELECTRICAL PANEL COVERS, GRILLES, ETC. TO BE PAINTED TO MATCH ADJACENT WALL SURFACES.11. NO LUXURY VINYL TILE TO BE CUT LESS THAN 6", REFER TO FINISH PLAN FOR PATTERN.12. ALL METAL UNDER-COUNTER SUPPORT BRACKETS TO BE PAINTED TO MATCH ADJACENT WALL FINISH.13. EXISTING FIN TUB HEATER COVERS TO BE ELECTROSTATICALLY PAINTED TO MATCH ADJACENT WALL SURFACES IN ALL WORK AREAS WHERE EXISTING MECHANICAL REMAINS. PROVIDE COST PER OFFICE PER UNIT PRICE 1.14. FWTP: FABRIC WRAPPED TACK PANELS, INSTALLED WITH Z-CLIPSFWTP A: 3'6" WIDEFWTP B: 6' WIDEFWTP C: 10' WIDE.SEE INTERIOR ELEVATIONS FOR HEIGHT, TYP. 15. PROVIDE EPOXY PAINT ON ALL WALLS IN TOILET ROOMS. FINISH KEY:WALLW1PAINT COLOR 1W2PAINT COLOR 2W3PAINT COLOR 3W4 PORCELAIN TILE MOSAICPORCELAIN TILESOLID SURFACECOLOR 1: UNLESS OTHERWISE NOTEDCOLOR 2: IN ROOM 1134FINISH LEGEND:FLOORF1CARPET TILE 1F2 LUXURY VINYL TILE 1F3 PORCELAIN TILE 8X8BASEB1RESILIENT BASE COLOR 1B2RESILIENT BASE COLOR 2B3PORCELAIN TILE 8X4ROOM #WALLFLOORBASEFINISH TAG11611129114911201120A1146101310251013A1012A1012103611501162A116211021102A102011241164A11641142116010351158115611401010A101010111030100210011030A1038DISPLAYDISPLAYDISPLAY DISPLAYATRIUMATRIUM1160AUPUPUPUPDNUPB1W1F11134Map RoomOUTDOORPATIOB1W1F11134Map RoomSCRAPE AND PAIN WOOD TRIMWOOD TRIMSCRAPE AND PAINTEXISTING FLOOR TILE TO REMAINEXISTING FLOOR TILE TO REMAINSCRAPE AND PAINT/REFINISH ALL WOOD SURFACES, TYP.LEVEL 5 FINISH -W1W2W2FWTP BFWTP BGMB, OFCIALTERNATE 4: MAP DISPLAY CASECOORDINATE INSTALLATION OF ARTWORK WITH OWNERSS #2SS #2WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910NA161FIRST FLOORFINISH PLAN7/30/202011365/ COB #1921YNPCORNELL UNIVERSITYConstruction DocumentsSnee Hall Renovation for Colocation of EAS112 Hollister Drive# Description Date1 Addendum #1 08/12/2020111 INTERIOR ELEVATION NOTES:1.COORDINATE ALL AV WITH AV CONTRACTOR AND OWNER2.REFER TO FINISH SCHEDULE FOR BASE MATERIAL3. OFCI: OWNER FURNISHED CONTRACTOR INSTALLED. PROVIDE BLOCKING AS NEEDED.4. PATCH, REPAIR, AND REPAINT ANY DAMAGED WALL SURFACES FROM REMOVAL OF EXISTING BLACKBOARDS, MARKERBOARDR, TACKBOARDS, TYP. 5. GMB: GLASS MARKER BOARD; OFCI. COORDINATE FINAL LOCATIONS WITH ARCHITECT.6.EXISTING TO REMAIN AND BE PROTECTED FROM DAMAGE DURING CONSTRUCTION -MB: MARKER BOARD; CB: CHALK BOARD 7.FWTP: FABRIC WRAPPED TACK PANEL8. ALL CABINETS TO BE PLASTIC LAMINATE U.O.N. 9. ALL MILLWORK IN MAPROOM 1134 TO BE WOOD 86" LCD.MOUNTING HEIGHT LOWER THANNORMAL TO ALLOW USERS TO REACH THE TOPOF THE IMAGE.SEE AV DRAWINGS FOR EXACT LOCATIONGMB, OFCIALIGN TO CENTER OF WALL4'-0"4'-0"EQEQ4'-0"4'-0"ALIGN WITH TOP OF SCREEN36"MOTORIZED ROLLER SHADEAV EQUIPMENT VENTED CABINETWOOD TOP RAIL TO MATCH EXISTINGF6A2513'-6"WOOD COLUMNWOOD COLUMND1A552EXISTING SHELVING TO REMAIND1A552A3A552D1A552WOOD CABINETS WITH SOLID SURFACE COUNTERTOP, COLOR 2. WOOD FINISH TO MATCH ADJACENT WALL CAP.RE-PAINT EXISTING HANDRAILSWHEELCHAIR LIFT80" MIN80" MINA251F6SimEXISTING SHELVING, TO REMAIN.MOTORIZED ROLLER SHADEA551F435 3/4"43 1/2"37 3/4"CURVED PORTION OF WALLA552D7SimEQ.EQ.MOTORIZED ROLLER SHADEWHEELCHAIR LIFTWOOD TOP RAIL TO MATCH EXISTINGF6A251RUBBER STAIR NOSING, TYP.B1A251WOOD COLUMNWOOD COLUMNREPAIR AND FIILL DAMAGE FROM REMOVAL OF EXISTING LIGHT FIXTURENEW LIGHT FIXTUREA552A3AV EQUIPMENT VENTED CABINETMOTORIZED ROLLER SHADEA551F4SKYLIGHT PERFORMANCE FILM ON SLOPED GLAZING C6A552ALL MAP DISPLAY WORK ALTERNATE 4A552D7SimFIRST FLOOR100' -0"LOWER LEVELMAP ROOM96' -6"V.I.F.A251D1EXISTING STAIR TO REMAIN3-5/8" CFMF5/8" GYPSUM BOARD6" CFMF5/8" PLYWOODFLOOR FINISHWOOD RAIL3'-6"3'-0"1/2"5 1/2"5"5/8" GYPSUM BOARD3-5/8" CFMFWOOD BLOCKING AS REQUIRED5/4 WOOD RAILING CAP TO MATCH EXISTING1/4" RADIUS TYP.EQ.EQ.F6A2514" 3'-0" 4"A251F2EDGE OF EXISTING STAIRWHEELCHAIR LIFTAUTOMATIC GATE BY WHEELCHAIR LIFT MAN.PLATFORM INFILLC6A552EXISTING WOOD RAILEQ.EQ.EXISTING SOFFIT ABOVEEXISTING WOOD RAIL BELOWWHEELCHAIR LIFT WALL BELOWMETAL COLUMN FRAMING AS REQUIRED5/4 WOOD TO MATCH EXISTINGF1A2511/4" RADIUS TYP.1/2"1/2"1/2"1/2"EXISTING RAIL DIMENSIONEXISTING SOFFIT ABOVEEXISTING WOOD TOP RAILMETAL COLUMN FRAMING AS REQUIRED5/4 WOOD TO MATCH EXISTINGEXISTING STAIRCARPETRUBBER STAIR NOSINGWARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A251FIRST FLOORINTERIORELEVATIONS &DETAILS7/30/202011365/ COB #1921MDCORNELL UNIVERSITYConstruction DocumentsSnee Hall Renovation for Colocation of EAS112 Hollister Drive1/4" = 1'-0"D7MAP ROOM - NORTH ELEVATION1/4" = 1'-0"B7MAP ROOM - SOUTH ELEVATION1/4" = 1'-0"A3MAP ROOM - EAST ELEVATION AT WHEELCHAIR LIFT1/4" = 1'-0"D3MAP ROOM - WEST ELEVATION1/4" = 1'-0"A7LOWER MAP ROOM - NORTH ELEVATION1/4" = 1'-0"B3MAP ROOM - EAST ELEVATION 23/4" = 1'-0"F6LIFT PLATFORM3" = 1'-0"D1WOOD RAIL DETAIL1/4" = 1'-0"F4WHEELCHAIR LIFT3" = 1'-0"F2WOOD COLUMN DETAIL3" = 1'-0"F1WOOD COLUMN SECTION3" = 1'-0"B1STAIR NOSING# Description Date1 Addendum #1 08/12/2020111 SDOS1134Map RoomEXISTING GYPSUM CEILING TO REMAINREPLACE LIGHT FIXTURES WITH NEW LED FIXTURESMOTORIZED ROLLER SHADE14'-2" V.I.F.F4A5516'-4" V.I.F.6'-4" V.I.F.PROVIDE METAL FRAMING TO DECK ABOVE TO SUPPORT MICROPHONE. INSTALL MICROPHONE CEILING MOUNTING FRAME. COORDINATE WITH AV VENDOR.2'-0"PROVIDE SKYLIGHT PERFORMANCE FILM FOR ALL SLOPED GLAZINGSPEAKER HOLES IN FINISHED CEILING TO BE CUT BY GC. COORDINATE WITH AV VENDOR.LINEAR PENDANT LIGHT FIXTURELINEAR SURFACE MOUNTED LIGHT FIXTURELAY-IN DIRECT/INDIRECT LIGHT FIXTURES RECESSED CAN LIGHT FIXTURERETURN AIR GRILLESUPPLY AIR GRILLEMANUAL PROJECTION SCREENMOTORIZED PROJECTION SCREENSOFFIT MOUNTED LINEAR LIGHT FIXTURESSPRINKLER HEADEXIT SIGNFIRE DETECTOROCCUPANCY SENSORSPEAKERGYPSUM BOARD CEILING2' X 2' ACOUSTICAL PANEL CEILINGREFLECTED CEILING PLAN NOTES:1. ALL LAY-IN ACOUSTIC CEILINGS ARE 8'-8 1/2" ABOVE FINISHED FLOOR, UNLESS OTHERWISE NOTED.2. ALL GYPSUM SOFFITS AND CEILINGS ARE 8'-8" ABOVE FINISHED FLOOR, UNLESS OTHERWISE NOTED.3. MOUNT ALL SPRINKLER HEADS, ELECTRICAL DEVICES, LIGHT FIXTURES, ETC. CENTERED IN 2'X2' ACOUSTIC CEILING PANELS, UNLESS OTHERWISE NOTED.4. CENTER ACOUSTIC CEILING PANELS WITHIN FIELD AS INDICATED ON REFLECTED CEILING PLANS, PROVIDING NUMBER OF PANELS SHOWN, UNLESS OTHERWISE NOTED.5. REPAIR CEILINGS AFFECTED BY HVAC WORK.6. PROVIDE PROJECTOR MOUNT FRAMING AS NEEDED FOR INSTALL.7. REPAIR CEILINGS AFFECTED BY AV WORK. CEILING MATERIALS:LIGHT FIXTURES:OTHER:CEILING MOUNTED 2" ACOUSTICAL PANELPROJECTOR112161AComputer Lab2161Workroom2161BIT Office2149SharedWorkspace2014ToiletA4A551A4A551334 SF2160Admin Suite170 SF2160AOffice210 SF2160BChair Office117 SF2160COffice127 SF2160DOffice125 SF2102OfficeA4A551A4A551A4A551A4A551A4A551A4A551D4A551A4A551A4A551A1A551F1A551755 SF2152Classroom155 SF3116Kitchenette1140 SF3161SharedWorkspace717 SF3147SharedWorkspace59 SF3014ToiletA4A551A4A551D1A551ALTERNATE 1A1A551453 SF4122Pryor Lab296 SF4120Office55 SF4114KitchenetteQUAD POWER CORD REEL, RELOCATED FROM BRADFIELD HALLCOORDINATE FINAL LOCATION WITH OWNER PAINT EXPOSED CONCRETETYP.2'-0"8'-0"10'-0"8'-0"5'-0"2'-0"D1A5511/8" = 1'-0"F1PARTIAL FIRST FLOOR RCP - MAP ROOMWARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910NA151PARTIALREFLECTEDCEILING PLANS7/30/202011365/ COB #1921MDCORNELL UNIVERSITYConstruction DocumentsSnee Hall Renovation for Colocation of EAS112 Hollister Drive1/8" = 1'-0"A1PARTIAL SECOND FLOOR RCP1/8" = 1'-0"D6PARTIAL THIRD FLOOR RCP1/8" = 1'-0"A6PARTIAL FOURTH FLOOR RCP# Description Date1 Addendum #1 08/12/2020 FINISH NOTES:1. ALL WALLS IN WORK AREAS TO BE PAINTED W1 UNLESS OTHERWISE NOTED.2. ALL GYPSUM BOARD CEILINGS IN WORK AREAS TO BE PAINTED W3 UNLESS OTHERWISE NOTED ON REFLECTED CEILING PLAN.3. HM DOORS / FRAMES AND PAINTED WINDOW TRIM / FRAMES SHALL BE PAINTED W1B UNLESS OTHERWISE NOTED.4. ALL WALL BASE TO BE B1 UNLESS OTHERWISE NOTED.5. ALL CEILING WITHIN WORK AREAS TO BE ACP UNLESS OTHERWISE NOTED. NO TILE TO BE CUT LESS THAN 6". REFER TO RCP FOR LAYOUT6. SEE INTERIOR ELEVATIONS FOR ADDITIONAL WALL AND BASE FINISHES, TYPICAL.7. SEE REFLECTED CEILING PLAN FOR ADDITIONAL FINISH INFORMATION, TYPICAL.8. SEE INTERIOR ELEVATIONS FOR WALL TILE LAYOUT AND LOCATION, TYPICAL.9. ALL FLOORING MATERIAL AND TRANSITIONS SHALL BE CENTERED UNDER THE DOOR IN THE CLOSED POSITION UNLESS OTHERWISE NOTED.10. MISCELLANEOUS ELECTRICAL PANEL COVERS, GRILLES, ETC. TO BE PAINTED TO MATCH ADJACENT WALL SURFACES.11. NO LUXURY VINYL TILE TO BE CUT LESS THAN 6", REFER TO FINISH PLAN FOR PATTERN.12. ALL METAL UNDER-COUNTER SUPPORT BRACKETS TO BE PAINTED TO MATCH ADJACENT WALL FINISH.13. EXISTING FIN TUB HEATER COVERS TO BE ELECTROSTATICALLY PAINTED TO MATCH ADJACENT WALL SURFACES IN ALL WORK AREAS WHERE EXISTING MECHANICAL REMAINS. PROVIDE COST PER OFFICE PER UNIT PRICE 1.14. FWTP: FABRIC WRAPPED TACK PANELS, INSTALLED WITH Z-CLIPSFWTP A: 3'6" WIDEFWTP B: 6' WIDEFWTP C: 10' WIDE.SEE INTERIOR ELEVATIONS FOR HEIGHT, TYP. 15. PROVIDE EPOXY PAINT ON ALL WALLS IN TOILET ROOMS. FINISH KEY:WALLW1PAINT COLOR 1W2PAINT COLOR 2W3PAINT COLOR 3W4 PORCELAIN TILE MOSAICPORCELAIN TILESOLID SURFACECOLOR 1: UNLESS OTHERWISE NOTEDCOLOR 2: IN ROOM 1134FINISH LEGEND:FLOORF1CARPET TILE 1F2 LUXURY VINYL TILE 1F3 PORCELAIN TILE 8X8BASEB1RESILIENT BASE COLOR 1B2RESILIENT BASE COLOR 2B3PORCELAIN TILE 8X4ROOM #WALLFLOORBASEFINISH TAG11611129114911201120A1146101310251013A1012A1012103611501162A116211021102A102011241164A11641142116010351158115611401010A101010111030100210011030A1038DISPLAYDISPLAYDISPLAY DISPLAYATRIUMATRIUM1160AUPUPUPUPDNUPB1W1F11134Map RoomOUTDOORPATIOB1W1F11134Map RoomSCRAPE AND PAIN WOOD TRIMWOOD TRIMSCRAPE AND PAINTEXISTING FLOOR TILE TO REMAINEXISTING FLOOR TILE TO REMAINSCRAPE AND PAINT/REFINISH ALL WOOD SURFACES, TYP.LEVEL 5 FINISH -W1W2W2FWTP BFWTP BGMB, OFCIALTERNATE 4: MAP DISPLAY CASECOORDINATE INSTALLATION OF ARTWORK WITH OWNERSS #2SS #2WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910NA161FIRST FLOORFINISH PLAN7/30/202011365/ COB #1921YNPCORNELL UNIVERSITYConstruction DocumentsSnee Hall Renovation for Colocation of EAS112 Hollister Drive# Description Date1 Addendum #1 08/12/2020111 INTERIOR ELEVATION NOTES:1.COORDINATE ALL AV WITH AV CONTRACTOR AND OWNER2.REFER TO FINISH SCHEDULE FOR BASE MATERIAL3. OFCI: OWNER FURNISHED CONTRACTOR INSTALLED. PROVIDE BLOCKING AS NEEDED.4. PATCH, REPAIR, AND REPAINT ANY DAMAGED WALL SURFACES FROM REMOVAL OF EXISTING BLACKBOARDS, MARKERBOARDR, TACKBOARDS, TYP. 5. GMB: GLASS MARKER BOARD; OFCI. COORDINATE FINAL LOCATIONS WITH ARCHITECT.6.EXISTING TO REMAIN AND BE PROTECTED FROM DAMAGE DURING CONSTRUCTION -MB: MARKER BOARD; CB: CHALK BOARD 7.FWTP: FABRIC WRAPPED TACK PANEL8. ALL CABINETS TO BE PLASTIC LAMINATE U.O.N. 9. ALL MILLWORK IN MAPROOM 1134 TO BE WOOD 86" LCD.MOUNTING HEIGHT LOWER THANNORMAL TO ALLOW USERS TO REACH THE TOPOF THE IMAGE.SEE AV DRAWINGS FOR EXACT LOCATIONGMB, OFCIALIGN TO CENTER OF WALL4'-0"4'-0"EQEQ4'-0"4'-0"ALIGN WITH TOP OF SCREEN36"MOTORIZED ROLLER SHADEAV EQUIPMENT VENTED CABINETWOOD TOP RAIL TO MATCH EXISTINGF6A2513'-6"WOOD COLUMNWOOD COLUMND1A552EXISTING SHELVING TO REMAIND1A552A3A552D1A552WOOD CABINETS WITH SOLID SURFACE COUNTERTOP, COLOR 2. WOOD FINISH TO MATCH ADJACENT WALL CAP.RE-PAINT EXISTING HANDRAILSWHEELCHAIR LIFT80" MIN80" MINA251F6SimEXISTING SHELVING, TO REMAIN.MOTORIZED ROLLER SHADEA551F435 3/4"43 1/2"37 3/4"CURVED PORTION OF WALLA552D7SimEQ.EQ.MOTORIZED ROLLER SHADEWHEELCHAIR LIFTWOOD TOP RAIL TO MATCH EXISTINGF6A251RUBBER STAIR NOSING, TYP.B1A251WOOD COLUMNWOOD COLUMNREPAIR AND FIILL DAMAGE FROM REMOVAL OF EXISTING LIGHT FIXTURENEW LIGHT FIXTUREA552A3AV EQUIPMENT VENTED CABINETMOTORIZED ROLLER SHADEA551F4SKYLIGHT PERFORMANCE FILM ON SLOPED GLAZING C6A552ALL MAP DISPLAY WORK ALTERNATE 4A552D7SimFIRST FLOOR100' -0"LOWER LEVELMAP ROOM96' -6"V.I.F.A251D1EXISTING STAIR TO REMAIN3-5/8" CFMF5/8" GYPSUM BOARD6" CFMF5/8" PLYWOODFLOOR FINISHWOOD RAIL3'-6"3'-0"1/2"5 1/2"5"5/8" GYPSUM BOARD3-5/8" CFMFWOOD BLOCKING AS REQUIRED5/4 WOOD RAILING CAP TO MATCH EXISTING1/4" RADIUS TYP.EQ.EQ.F6A2514" 3'-0" 4"A251F2EDGE OF EXISTING STAIRWHEELCHAIR LIFTAUTOMATIC GATE BY WHEELCHAIR LIFT MAN.PLATFORM INFILLC6A552EXISTING WOOD RAILEQ.EQ.EXISTING SOFFIT ABOVEEXISTING WOOD RAIL BELOWWHEELCHAIR LIFT WALL BELOWMETAL COLUMN FRAMING AS REQUIRED5/4 WOOD TO MATCH EXISTINGF1A2511/4" RADIUS TYP.1/2"1/2"1/2"1/2"EXISTING RAIL DIMENSIONEXISTING SOFFIT ABOVEEXISTING WOOD TOP RAILMETAL COLUMN FRAMING AS REQUIRED5/4 WOOD TO MATCH EXISTINGEXISTING STAIRCARPETRUBBER STAIR NOSINGWARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A251FIRST FLOORINTERIORELEVATIONS &DETAILS7/30/202011365/ COB #1921MDCORNELL UNIVERSITYConstruction DocumentsSnee Hall Renovation for Colocation of EAS112 Hollister Drive1/4" = 1'-0"D7MAP ROOM - NORTH ELEVATION1/4" = 1'-0"B7MAP ROOM - SOUTH ELEVATION1/4" = 1'-0"A3MAP ROOM - EAST ELEVATION AT WHEELCHAIR LIFT1/4" = 1'-0"D3MAP ROOM - WEST ELEVATION1/4" = 1'-0"A7LOWER MAP ROOM - NORTH ELEVATION1/4" = 1'-0"B3MAP ROOM - EAST ELEVATION 23/4" = 1'-0"F6LIFT PLATFORM3" = 1'-0"D1WOOD RAIL DETAIL1/4" = 1'-0"F4WHEELCHAIR LIFT3" = 1'-0"F2WOOD COLUMN DETAIL3" = 1'-0"F1WOOD COLUMN SECTION3" = 1'-0"B1STAIR NOSING# Description Date1 Addendum #1 08/12/2020111 MB,EXISTING TO REMAINCBEXISTING TO REMAINCBEXISTING TO REMAINCBEXISTING TO REMAINFWTP,EXISTING TO REMAINCBEXISTING TO REMAINFLAT PANEL DISPLAYOPCI, INSTALL BLOCKING AND MOUNTCOORDINATE EXACT LOCATION WITH AVC & OWNERFLAT PANEL DISPLAYOPCI, INSTALL BLOCKING AND MOUNTCOORDINATE EXACT LOCATION WITH AVC & OWNER41"GMB, OFCI6'-0"4'-0"GMB, OFCI4'-0"4'-0"6'-0"4'-0"GMB, OFCIINTERIOR ELEVATION NOTES:1.COORDINATE ALL AV WITH AV CONTRACTOR AND OWNER2.REFER TO FINISH SCHEDULE FOR BASE MATERIAL3. OFCI: OWNER FURNISHED CONTRACTOR INSTALLED. PROVIDE BLOCKING AS NEEDED.4. PATCH, REPAIR, AND REPAINT ANY DAMAGED WALL SURFACES FROM REMOVAL OF EXISTING BLACKBOARDS, MARKERBOARDR, TACKBOARDS, TYP. 5. GMB: GLASS MARKER BOARD; OFCI. COORDINATE FINAL LOCATIONS WITH ARCHITECT.6.EXISTING TO REMAIN AND BE PROTECTED FROM DAMAGE DURING CONSTRUCTION -MB: MARKER BOARD; CB: CHALK BOARD 7.FWTP: FABRIC WRAPPED TACK PANEL8. ALL CABINETS TO BE PLASTIC LAMINATE U.O.N. 9. ALL MILLWORK IN MAPROOM 1134 TO BE WOOD GMB, OFCI GMB, OFCI3'-0"4'-0"3'-0"4'-0"52"40"EXISTING CHALKBOARD PAINT TO BE REMOVED.OWNER RPOVIDED SLATE CB TO BE INSTALLEDWALL ON DIAGONALGMB, OFCI4'-0"5'-0"GMB, OFCI5'-0"4'-0"WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A253INTERIORELEVATIONS -OFFICEROOMS7/30/202011365/ COB #1921MDCORNELL UNIVERSITYConstruction DocumentsSnee Hall Renovation for Colocation of EAS112 Hollister Drive1/4" = 1'-0"D3ROOM 2102A - EAST ELEVATION1/4" = 1'-0"F6ROOM 2108 - EAST ELEVATION1/4" = 1'-0"F7ROOM 2124 - NORTH ELEVATION1/4" = 1'-0"D7ROOM 2126 - NORTH ELEVATION1/4" = 1'-0"C7ROOM 2130 - NORTH ELEVATION1/4" = 1'-0"B7ROOM 2134 - NORTH ELEVATION1/4" = 1'-0"C3ROOM 2160B - SOUTH ELEVATION1/4" = 1'-0"C6ROOM 2116 - EAST ELEVATION1/4" = 1'-0"D9ROOM 4120 - EAST ELEVATION1/4" = 1'-0"C9ROOM 4120 - SOUTH ELEVATION1/4" = 1'-0"D4ROOM 2108 - SOUTH ELEVATION1/4" = 1'-0"A3ROOM 2116 - SOUTH ELEVATION1/4" = 1'-0"B8ROOM 2142 - EAST ELEVATION1/4" = 1'-0"A4ROOM 2120 - NORTH ELEVATION1/4" = 1'-0"B4ROOM 2118 - SOUTH ELEVATION# Description Date1 Addendum #1 08/12/20201 METAL FRAMING AS REQUIRED(EXTEND TO UNDERSIDE OF STRUCTURE)1/2" GYPSUM BOARD ON SUSPENSION SYSTEMEXISTING ACP TO REMAIN6"SEE WALL TYPETHICKNESS VARIESRECESSED LIGHT FIXTURE AS SPECIFIEDMETAL FRAMING AS REQUIRED(EXTEND TO UNDERSIDE OF STRUCTURE)1/2" GYPSUM BOARD ON SUSPENSION SYSTEMWALL TILECEMENTITIOUS BACKER BOARDMETAL WALL STUDTYP.3"FACE OF PARTITIONLEAVE 6" MIN. BETWEEN SCREEN DROP & WALL PROJECTION SCREEN ENCLOSUREACOUSTIC CEILING PANELSON SUSPENSION GRID SYSTEM 18" X 1 5/8" X 1 5/8" SLOTTED CHANNEL (PROVIDED BY GC) ABLE TO HOLD GROSS WEIGHT OF SCREEN PER MANUFACTURER CUT SHEET PLUS SAFETY FACTIOR OF FIVE. NOTE: COORDINATE PROJECTIONSCREEN LOCATION WITH AV DRAWINGS6" MIN3/8" THREADED RODLENGTH TBD IN FIELDEXISTING SOFFIT, ADD BLOCKING AND PATCHING AS REQUIREDREMOVABLE CLOSURESHADE BRACKETALUMINUM CLOSUREHEM BARSEE WALL TYPEVARIESMETAL FRAMING AS REQUIRED (EXTEND TO UNDERSIDE OF STRUCTURE)5/8" GYPSUM WALL BOARD1/2" GYPSUM CEILING BOARD15/16" SHADOW REVEAL TRANSITION MOLDINGWALLNEW CEILING SYSTEM AS INDICATED (SEE RCP)SUPPORT FROM STRUCTURE1/2"5/8" GYPSUM BOARD3-5/8" METAL STUDBATT INSULATION5/8" GYPSUM BOARD3-5/8" METAL STUDBATT INSULATIONEXISTING STRUCTURAL WAFFLERIB TO RIB, V.I.F.WARNING: It is a violation of New York State Law for any person, unless acting under the direction of a licensed Architect, to alter this document in any way. If a document bearing the seal of an Architect is altered, the altering Architect shall affix to such document his seal and the notation "altered by" followed by his signature, the date of such alteration, and a specific description of the alteration.DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910A551RCP DETAILS7/30/202011365/ COB #1921MDCORNELL UNIVERSITYConstruction DocumentsSnee Hall Renovation for Colocation of EAS112 Hollister Drive3" = 1'-0"D1CEILING AT KITCHENETTE3" = 1'-0"A1LIGHT FIXTURE AT RESTROOM SOFFIT DETAIL1 1/2" = 1'-0"F1MOTORIZED ROLLER SHADE RECESS DETAIL3" = 1'-0"F4ROLLER SHADE DETAIL3" = 1'-0"A4RCP TRANSITION DETAIL1 1/2" = 1'-0"D4WALL HEAD AT BAFFLE# Description Date1 Addendum #1 08/12/20201 DESIGN DATA NOTES DEAD LOADS: PORTION OF ABOVE DEAD LOAD CONSIDERED FOR MECHANICAL EQUIPMENT AND PIPING SUSPENDED FROM STRUCTURAL FRAMING: SEISMIC LOADS:5. ROOF: ROOF: 4. GENERAL:1. 55 psf SUPERIMPOSED 8 psf 7.STRUCTURAL MATERIAL STRENGTHS: STRUCTURAL AND MISCELLANEOUS STEEL: ROLLED STEEL C, S, M, MC, AND HP SHAPES ROLLED STEEL PLATES, BARS, AND ANGLES - ASTM A 36 OR ASTM A 572, GRADE 50 - ASTM A 36 OR ASTM A 572, GRADE 50 EXISTING CONCRETE CURBS:f'c = 4,000 psi 2020 BUILDING CODE OF NEW YORK STATE (BCNYS)DESIGN PROVISIONS RISK CATEGORY TERRAIN/EXPOSURE CATEGORY SEE S-001 FOR ADDITIONAL WIND LOAD DATA FOR SKYLIGHT COMPONENTS AND CLADDING. NET UPLIFT LOAD ON SKYLIGHT COMPONENTS SHALL BE DETERMINED BY DEDUCTING 8 psf DEAD LOAD FROM THE TABULATED ROOF WIND LOADS FOR COMPONENTS AND CLADDING. NET UPLIFT VALUE SHALL BE A MINIMUM OF 16 psf. 110 mph 85 mph 0.85 1.0 0.85 ENCLOSED ± 0.18 70 feet ULTIMATE WIND SPEED (3 SECOND GUST) (Vult): NOMINAL WIND SPEED (3 SECOND GUST) (Vasd): DIRECTIONALITY FACTOR (kd): TOPOGRAPHIC FACTOR (Kzt): GUST EFFECT FACTOR (G): ENCLOSURE CLASSIFICATION: INTERNAL PRESSURE COEFFICIENT (GCpi): HEIGHT OF MAIN ROOF: CODE COMPLIANCE FOR EXISTING STRUCTURES:2. DESIGN PROVISIONS COMPLIANCE METHOD (EBCNYS) ALTERATION LEVEL 2CLASSIFICATION OF WORK (EBCNYS) 2020 EXISTING BUILDING CODE OF NEW YORK STATE (EBCNYS) WORK AREA THE FOLLOWING GRAVITY LOAD CARRYING ELEMENTS HAVE BEEN EVALUATED BASED ON THE LIVE LOAD AND DEAD LOAD REQUIREMENTS DESCRIBED BELOW: EXISTING CONCRETE ROOF BEAMS, PAN JOISTS, AND ROOF CURB. EXISTING STRUCTURAL ELEMENTS RESISTING LATERAL LOADS ARE NO LESS CONFORMING TO THE PROVISIONS OF THE 2020 BCNYS WITH RESPECT TO EARTHQUAKE AND WIND DESIGN THAN THEY WERE PRIOR TO THIS WORK. THE BUILDING IS IN CONFORMANCE WITH THE LAW IN EXISTENCE AT THE TIME THE BUILDING WAS CONSTRUCTED. THEREFORE LATERAL LOADS HAVE NOT BEEN EVALUATED FOR THIS STRUCTURE. LIVE LOADS : FLOORS AND ROOFS HAVE BEEN DESIGNED TO SUPPORT THE UNIFORMLY DISTRIBUTED LIVE LOAD OR THE CONCENTRATED LIVE LOADS NOTED BELOW, WHICHEVER PRODUCED THE GREATER LOAD EFFECTS. UNIFORMLY DISTRIBUTED LIVE LOADS: ROOF: (CONCENTRATED LOADS SHALL BE LIMITED TO THOSE WHICH INDUCE MOMENTS AND SHEARS IN MEMBERS NOT GREATER THAN THOSE INDUCED BY THE NOTED UNIFORMLY DISTRIBUTED LOADS.) SITE CLASS: SHORT-PERIOD DESIGN ACCELERATION (Sds): ONE-SECOND DESIGN ACCELERATION (Sd1): SHORT PERIOD MAPPED SPECTRAL RESPONSE (Ss): ONE-SECOND MAPPED SPECTRAL RESPONSE (S1): SEISMIC DESIGN CATEGORY: IMPORTANCE FACTOR (Ie): D ASSUMED 0.127 0.073 0.119 0.045 B 1.0 UNIFORM GROUND SNOW LOAD (Pg) UNIFORM FLAT-ROOF SNOW LOAD (Pf) SNOW EXPOSURE FACTOR (Ce) THERMAL FACTOR (Ct) IMPORTANCE FACTOR (Is) (DRIFTED, UNBALANCED, AND SLOPED-ROOF SLIDING SNOW IN ACCORDANCE WITH AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE) STANDARD 7-16. SEE 1/S001 FOR LOADING DIAGRAM.) 40 psf 28 psf 1.0 1.0 1.1 3. 6. III C WIND LOADS: EXISTING CONCRETE BEAMS AND JOISTS :f'c = 4,000 psi REINFORCING STEEL FOR EXISTING CONCRETE: ASTM A 615, Fy = 60 ksi 1 1 1. DIMENSIONS TO, OF, AND IN EXISTING STRUCTURE SHALL BE VERIFIED IN FIELD BY CONTRACTOR. 2. DO NOT SCALE DRAWINGS. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY DISCREPANCIES IN DIMENSIONS BETWEEN EXISTING CONDITIONS AND/OR ARCHITECTURAL DRAWINGS AND THE STRUCTURAL DRAWINGS. 3. DO NOT CHANGE SIZE OR SPACING OF STRUCTURAL ELEMENTS. 4. DETAILS SHOWN ARE TYPICAL; SIMILAR DETAILS APPLY TO SIMILAR CONDITIONS UNLESS OTHERWISE INDICATED. 5. THE NOTES ON THIS DRAWING ARE TYPICAL UNLESS OTHERWISE INDICATED. 6. CONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING OF PROPOSED DEVIATIONS OR SUBSTITUTIONS FROM DIMENSIONS, MATERIALS, OR EQUIPMENT SHOWN ON THE DRAWINGS AND MAKE ONLY THOSE DEVIATIONS OR SUBSTITUTIONS ACCEPTED BY ENGINEER. 7. THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS FOR CONSTRUCTION SAFETY. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION SAFETY. 8. LOCATE REINFORCEMENT IN EXISTING STRUCTURAL CONCRETE SLABS AND JOISTS USING NON-DESTRUCTIVE METHODS PRIOR TO DRILLING HOLES FOR POST-INSTALLED ANCHORS. DO NOT DRILL INTO AND DAMAGE EXISTING REINFORCEMENT. NOTIFY ENGINEER IF ANCHOR LOCATIONS CONFLICT WITH EXISTING REINFORCEMENT. GENERAL NOTES - DENOTES DRIFTED SNOW LOADS IN ADDITION TO FLAT SNOW LOADS SHOWN. 1. 2. NOTES:SEEPLAN(PSF)SEE PLAN FLAT SNOW LOAD DRIFTED SNOW LOAD EFFECTIVE WIND AREA (sf) DESIGN WIND PRESSURE FOR EXTERIOR SKYLIGHT MATERIALS 36.3 PRESSURE (psf)PRESSURE (psf) EFFECTIVE WIND AREA (sf) POSITIVE NEGATIVE BASIC WIND : Vult = 110 mph EXPOSURE: C H (ft) = 70 K = 1zt 34.8 1-10 -76.4 1-10 20 -70.2 33.2 30.8 50 -64.0 100 -61.0 29.6 27.1 200 -54.8 500 -48.7 20 50 100 200 500 2 1 3 4 5 6 7 8 9 10 11 ABCDEFGHJKLM 2 1 3 4 5 6 7 8 9 10 11 ABCDEFGHJKLM PENTHOUSE LEVEL HIGH ROOF FLAT SL = 31 psf ROOF LEVEL LOW ROOF FLAT SL = 31 psf 12' - 4"12' - 4"12' - 6"12' - 6"60 psf DRIFT CASE 160 psf60 psf60 psf DRIFT CASE 2 NOTES: 1. DRIFT CASE 2 NOT CONSIDERED SIMULTANEOUSLY WITH DRIFT CASE 1. 2. DRIFT CASE 1 SHALL BE APPLIED SIMULTANEOUSLY WITH AND IN ADDITION TO 31 PSF UNIFORM SNOW LOAD ON SKYLIGHT. OUTLINE OF MAIN ROOF OUTLINE OF HIGH ROOF 1 1 1 STRUCTURAL OBSERVATION NOTES • INITIAL LAYOUT AND INSTALLATION OF POST-INSTALLED ANCHORS. • ERECTION OF SKYLIGHT FRAMES. • COMPLETION OF THE STRUCTURAL SYSTEM. • OTHER TIMES AS REQUIRED DUE TO FIELD CONDITIONS OR SPECIAL CONSTRUCTION TYPES. 1. THE REGISTERED DESIGN PROFESSIONAL WILL MAKE VISITS TO THE SITE AT APPROPRIATE INTERVALS FOR THE PURPOSE OF OBSERVING THE CONSTRUCTION FOR GENERAL CONFORMANCE WITH THE CONTRACT DOCUMENTS. THE FOLLOWING LIST INCLUDES SOME APPROPRIATE TIMES FOR VISITING THE SITE. THE CONTRACTOR SHALL NOTIFY THE REGISTERED DESIGN PROFESSIONAL AT LEAST 48 HOURS PRIOR TO PERFORMING THESE ACTIVITIES SO THAT SITE VISITS CAN BE SCHEDULED. 2. THE REGISTERED DESIGN PROFESSIONAL MAY VISIT THE SITE AT TIMES OTHER THAN THOSE LISTED IN NOTE 1. 3. THE REGISTERED DESIGN PROFESSIONAL WILL PREPARE A FIELD OBSERVATION REPORT FOR EACH SITE VISIT MADE TO OBSERVE CONSTRUCTION. PART II OF EACH REPORT IS FOR CONTRACTOR VERIFICATION AND IS MANDATORY. PART II MUST BE COMPLETED (SIGNED BY THE CONTRACTOR VERIFYING THAT THE REQUIRED ACTION WAS TAKEN AND LISTING THE DATE COMPLETED) AND RETURNED TO THE ENGINEER IN A TIMELY MANNER. 1. THE OWNER WILL ENGAGE THE SERVICES OF A QUALIFIED SPECIAL INSPECTOR FOR THIS PROJECT, WHO WILL PROVIDE AND/OR COORDINATE INSPECTION AND TESTING REQUIREMENTS AS NECESSARY IN ACCORDANCE WITH THE PROVISIONS OF CHAPTER 17 OF THE BCNYS. 2. THE REGISTERED DESIGN PROFESSIONAL HAS PREPARED A STATEMENT OF SPECIAL INSPECTIONS, WHICH INCLUDES SPECIFICATION 014533, AND THE SCHEDULE OF SPECIAL INSPECTIONS. THESE DOCUMENTS WILL BE SUBMITTED WITH THE CONTRACT DOCUMENTS AND THE APPLICATION FOR BUILDING PERMIT TO THE CODE ENFORCEMENT OFFICIAL. 3. SPECIAL INSPECTIONS AND TESTING SHALL BE CONTINUOUS OR PERIODIC DURING THE PERFORMANCE OF THE WORK, AS NOTED. 4. THE SPECIAL INSPECTOR SHALL SUBMIT INTERIM REPORTS AND, AT THE COMPLETION OF SPECIAL INSPECTIONS, A FINAL STATEMENT OF SPECIAL INSPECTIONS. REPORTS SHALL BE STAMPED AND SIGNED BY A PROFESSIONAL ENGINEER. 5. THE SPECIAL INSPECTOR SHALL NOTIFY THE CONTRACTOR IMMEDIATELY OF DISCREPANCIES. SUBSEQUENT REPORTS SHALL NOTE WHEN AND HOW DEFICIENCIES WERE CORRECTED. THE SPECIAL INSPECTOR SHALL NOTIFY THE REGISTERED DESIGN PROFESSIONAL AND THE CODE ENFORCEMENT OFFICIAL OF DISCREPANCIES WHICH HAVE NOT BEEN CORRECTED. 6. THE CONTRACTOR SHALL COOPERATE WITH THE SPECIAL INSPECTOR INCLUDING ADVANCE NOTIFICATION OF REQUIRED INSPECTION OR TEST, INCIDENTAL LABOR, AND SAFE ACCESS TO THE WORK AREAS, AND ACCESS TO CONTRACT DOCUMENTS SO THAT INSPECTIONS AND TESTING MAY BE PERFORMED WITHOUT HINDRANCE. 7. THE SPECIAL INSPECTION PROGRAM SHALL IN NO WAY RELIEVE THE CONTRACTOR OF THE OBLIGATION TO PERFORM THE WORK IN ACCORDANCE WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS OR FROM IMPLEMENTING AN EFFECTIVE QUALITY CONTROL PROGRAM. 8. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. SPECIAL INSPECTION NOTES 4592 JORDAN ROAD SKANEATELES FALLS, NY 13153 p 315.685.4732 www.ryanbiggs.com DATE: PROJECT: OTHER: DRAWN BY: A B C D E F G A B C D E F 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 12526 REVISION ADDENDUM 1 DATE 08/12/2020 S001 DESIGN DATA AND GENERAL NOTES 07/30/2020 1921 RMS CORNELL UNIVERSITYConstruction DocumentsSnee Hall Renovation for Colocation ofEASS001 ABBREVIATIONS LEGEND ADJ ADJACENT EXT EXTERIOR PE PROFESSIONAL ENGINEER L ANGLE EOD EDGE OF DECK PERP PERPENDICULAR APPROX APPROXIMATE EOS EDGE OF SLAB PLF POUNDS PER LINEAL ARCH ARCHITECT FD FLOOR DRAIN FOOT ARCHITECTURAL FDN FOUNDATION PSF POUNDS PER SQUARE B/ BOTTOM OF FTG FOOTING FOOT BLDG BUILDING GA GAUGE PSI POUNDS PER SQUARE BRG BEARING GALV GALVANIZED INCH BP BASE PLATE HSS HOLLOW STEEL SECTION PCF POUNDS PER CUBIC CANT CANTILEVER HORIZ HORIZONTAL FOOT CJ CONTROL, HI HIGH PC PRECAST CONTRACTION, HP HIGH POINT PSL PARALLEL STRAND CONSTRUCTION JOINT HVAC HEATING/VENTILATING/ LUMBER CMU CONCRETE MASONRY INFO INFORMATION R RADIUS UNIT(S) INT INTERIOR RD ROOF DRAIN CONC CONCRETE INV INVERT RDP REGISTERED DESIGN CONT CONTINUOUS K KIPS PROFESSIONAL COL COLUMN LG LONG REQD REQUIRED CFMF COLD-FORMED LLH LONG LEG HORIZONTAL REINF REINFORCING OR METAL FRAMING LLV LONG LEG VERTICAL REINFORCED COORD COORDINATE LOC LOCATION REV REVISION OR REVISED DIA DIAMETER LW LIGHT WEIGHT RO ROUGH OPENING DIM DIMENSION LVL LAMINATED VENEER SIM SIMILAR DN DOWN LUMBER SPA SPACE do DITTO LO LOW STD STANDARD DWG DRAWING MANUF MANUFACTURER SF SQUARE FEET EA EACH MAX MAXIMUM SS STAINLESS STEEL EF EACH FACE MECH MECHANICAL STL STEEL EJ EXPANSION JOINT MIN MINIMUM SQ SQUARE ELEC ELECTRICAL MISC MISCELLANEOUS T/ TOP OF EL ELEVATION MO MASONRY OPENING TYP TYPICAL ELEV ELEVATOR NA NOT APPLICABLE UNO UNLESS NOTED ENGR ENGINEER NIC NOT IN CONTRACT OTHERWISE EMBD EMBEDDED NOM NOMINAL VERT VERTICAL EQ EQUAL NW NORMAL WEIGHT VIF VERIFY IN FIELD EQUIP EQUIPMENT OC ON CENTER W/ WITH ES EACH SIDE OD OUTSIDE DIAMETER WP WORK POINT EW EACH WAY OPNG OPENING WWR WELDED WIRE EXIST EXISTING OPP OPPOSITE REINFORCEMENT PAF POWDER ACTUATED WCJ WALL CONTROL OR FASTENER CONSTRUCTION JOINT SCALE: 1/16" = 1'-0"S001 1 ROOF SNOW LOADING PLAN ISSUE:DATE:DRAWN BY:CHECKED BY:SCALE:PROJECT NO.SHEET TITLESHEETDRAWING NO.ALTERATION OF THIS DOCUMENTEXCEPT BY A LICENSED DESIGNPROFESSIONAL, IS A VIOLATION OFNEW YORK STATE EDUCATIONAL LAW.OFFS ENGINEERING,DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044Enter address hereR:\Revit MEP 2012\Templates\S&A_Mechanical.rte10/5/2011 4:16:29 PMOwnerProject NameSK-M201/01/2019AuthorCheckerProject NumberUnnamedMARK DATE DESCRIPTION??PLAN DETAILBUILDING SECTIONDETAIL NUMBERSHEET NUMBER WHERE DETAIL IS LOCATEDDETAIL NUMBERSHEET NUMBER WHERE DETAIL IS LOCATEDEXTENT OF DETAILEXTENT OF DETAILA1B1C1D1E1A2B2C2D2E2A3B3C3D3E3A4B4C4D4E4A5B5C5D5E5A6B6C6D6E6DETAIL NUMBERDETAIL SCALEDETAIL NAMEDETAIL NUMBERPLAN SETUPSHEET NUMBER WHERE DETAIL IS LOCATEDCAUTION: THESE DOCUMENTS WERE DIGITALLY PRODUCED AND/OR REPRODUCED. CONFIRM REDUCTION OR MAGNIFICATION USING DIMENSIONAL 3"-LONG LINE IN TITLE BARS. IF SCALING DRAWINGS FOR APPROXIMATE DIMENSIONS, ALTERNATE ARCHITECTURAL SCALES MAY BE USED AS FOLLOWS:DOCUMENT REDUCTION/MAGNIFICATION SCALEIF LINE MEASURES 2”(67% COPY):USE 3/16th SCALE ON 1/8”=1’-0”DWGUSE 3/8th SCALE ON 1/4”=1’-0”DWGIF LINE MEASURES 1.5”(50% COPY):USE 1/16th SCALE ON 1/8”=1’-0”DWGUSE 31/8th SCALE ON 1/4”=1’-0”DWG3"3"????XXXX" = X"NOTES:FSCFINISHED FLOOR1'-6"1'-6"1'-6"DUPLEX RECEPTACLEDESK TOPTELEPHONEDATA OUTLET2'-0"EXTERIOR DUPLEXRECEPTACLE4'-0"DUPLEX RECEPTACLEMECH RMLIGHT SWITCH4'-0"PBGYM DOOR PUSHBUTTONFSEE NOTE 3FIRE ALARMPULLSTATIONWALL MOUNTEDTELEPHONE/INTERCOM PHONESEE NOTE 3F5'-0"DISCONNECTSWITCH6'-0"PANELBOARDFIRE ALARMA/V DEVICEFIRE ALARMVISUAL DEVICESEE NOTE 4EMERGENCYLIGHTCLOCKINTERCOMSPEAKERSEE NOTE 51. IN LOCATIONS WHERE SIMILAR DEVICES ARE MOUNTED AT THE SAME HEIGHT DEVICES SHALL BE PROPERLY "GANGED" AND SHALL HAVE ASINGLE COVER PLATE.2. IN LOCATIONS WHERE DIFFERENT DEVICES ARE MOUNTED AT DIFFERENT HEIGHTS WITHIN FOUR FEET OF ONE ANOTHER. DEVICES SHALL BE MOUNTED SUCH THAT THEY HAVE A COMMON CENTER LINE. IF THERE ARE THREE OR MORE DEVICES THE CONTRACTOR SHALL REQUEST A DETAIL FROM THE ARCHITECT.3. 42" MINIMUM TO 48" MAXIMUM AND WITHIN 5FT FROM DOOR. 4. 80" OR, AT SHALLOW CEILING INSTALLATIONS, WITHIN 6" OF FINISHED CEILING. VERIFY WITH ENGINEER.5. 90" AFF, OR, AT SHALLOW CEILING INSTALLATIONS, TOP OF UNIT WITHIN 6" OF FINISHED CEILING.SEE NOTE 3A.REFER TO ARCHITECTURAL DRAWINGS FOR EXTENT OF BASE BID NEW CONSTRUCTION AND RENOVATED AREAS, PHASING REQUIREMENTS AND ALTERNATES.PROVIDE MATERIALS AND LABOR FOR COMPLETE, FUNCTIONAL SYSTEMS. COORDINATE WIRING AND CONNECTION REQUIREMENTS FOR EQUIPMENT. MATERIALS, EQUIPMENT, CONDUCTORS, WIRING DEVICES, ETC. SHALL BE NEW AND UL-LISTED, SUITABLE FOR LOCATION AND FUNCTION.COORDINATE EXACT LOCATION OF ELECTRICAL BOXES AND RACEWAY PRIOR TO ROUGH-IN. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS.PROVIDE TEMPORARY POWER AND LIGHTING. PROVIDE TEMPORARY ELECTRICAL CIRCUITRY AND CONNECTIONS AS REQUIRED TO MAINTAIN SERVICES.VERIFY SCOPE AND PHASING OF DEMOLITION WORK FOR AREAS TO BE ABATED AND RENOVATED. PROTECT EXISTING CIRCUITRY SERVING ADJACENT AREA/EQUIPMENT WHICH WILL REMAIN IN USE. PROVIDE SUPPORT AND TEMPORARY CONNECTIONS/RE-ROUTING AS REQUIRED. REFER TO ARCHITECTURAL DRAWINGS INDICATING REMOVAL SCOPE OF WORK. CONTRACTOR FOR DIVISION 26 SHALL DISCONNECT AND REMOVE BRANCH CIRCUITRY, LIGHT FIXTURES, WIRING DEVICES, CLOCKS, SPEAKERS, TELEPHONES AND RESPECTIVE SYSTEM WIRING/CABLING COMPLETE. REMOVALS SHALL INCLUDE ALL ELECTRICAL COMPONENTS IN/ON WALLS THAT ARE TO BE REMOVED. MAINTAIN CIRCUITRY TO EQUIPMENT AND DEVICES THAT ARE TO REMAIN.FIRE STOP PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS WITH FIRE STOP MATERIAL EQUAL IN RATING TO THE CONSTRUCTION OF WHICH IT IS PENETRATING. SOUND TRANSFERENCE: FLUSH WALL MOUNTED ELECTRICAL BOXES MOUNTED IN COMMON WALLS BETWEEN ADJACENT ROOMS, SHALL BE INSTALLED INDEPENDENT OF EACH OTHER; EACH WITH SEPARATE CONDUIT RISER(S). NIPPLING OF FLUSH WALL MOUNTED ELECTRICAL BOXES NOT ALLOWED. WHERE ELECTRICAL BOXES ARE MOUNTED BACK TO BACK, PROVIDE INSULATION BETWEEN BOXES. GROUNDING REQUIREMENTS1. ALL GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLES 250.2. ALL INSULATED GROUND CONDUCTORS SHALL BE GREEN. PROVIDE EQUIPMENT GROUND CONDUCTOR FOR EACH BRANCH CIRCUIT.3. PROVIDE GROUNDING PER EQUIPMENT MANUFACTURER REQUIREMENTS.CONNECTIONS TO EQUIPMENT FURNISHED BY OTHERS:1. VARIOUS PIECES OF EQUIPMENT WILL BE FURNISHED TO THE PROJECT SITE AND INSTALLED BY OTHER DIVISIONS.2. PROVIDE ROUGHING-IN AND FINAL CONNECTIONS AS REQUIRED IN ACCORDANCE WITH EQUIPMENT INSTALLATION INSTRUCTIONS.3. BEFORE PROCEEDING WITH THE WORK, OBTAIN FULL INFORMATION REGARDING ROUGH-IN MEASUREMENTS, EQUIPMENT LAYOUTS, ELEVATIONS, TRIM BEING FURNISHED, AND OTHER NECESSARY DATA.4. UPON REQUEST, CONSTRUCTION MANAGER WILL PROVIDE THIS DIVISION WITH DIAGRAMS, PHOTOGRAPHS, DRAWINGS, AND/OR SPECIFICATIONS AND OTHER COMPLETE DESCRIPTIVE DATA. DO NOT ROUGH WITHOUT APPROVED LAYOUT FROM CONSTRUCTION MANAGER.5. PROVIDE ACCESSORIES SO THAT CONNECTIONS MAY BE MADE IN A MANNER THAT SHALL MEET ALL REGULATIONS AND CODES.6. SEE APPROPRIATE SECTIONS OF THIS DIVISION'S SPECIFICATIONS FOR MATERIALS AND METHODS.USE OF SHALLOW FLUSH MOUNT ELECTRICAL BOXES SHALL BE PERMITTED WHERE DEPTH OF WALL CAVITY/FURRING IS LESS THAN 2 1/2" AS INDICATED ON ARCHITECTURAL DRAWINGS.CONCEAL ALL ADDED CONDUITS, EXPOSED CONDUIT INSTALLATION IS UNACCEPTABLE UNLESS PRIOR APPROVAL IS GIVEN BY ARCHITECT. ANY EXPOSED CONDUIT INSTALLATION SHALL BE PAINTED TO MATCH ADJACENT WALL FINISH.REFER TO T SERIES AV DRAWINGS AND COORIDINATE ELECTRICAL REQUIREMENTS.B.GENERAL NOTESC.D.E.F.G.H.I.J.J.X1X2EXIT SIGN LIGHT FIXTURE WITH CONNECTION TO EMERGENCY POWER. COORDINATE TYPE AND MOUNTING. PROVIDE ARROWS WHERE INDICATED. DESCRIPTIONSYMBOLLIGHTING SYMBOLSDLED LIGHT FIXTURE, SUBSCRIPT D = FIXTURE TYPE, REFER TOSPECIFICATIONS AND LIGHT FIXTURE SCHEDULE.EMTVFCAFFACGNFGFGROUND FAULT INTERUPT DEVICENON-FUSEDGROUNDABOVE FINISHED FLOORVARIABLE FREQUENCY CONTROLLERABOVE COUNTER - 6"ABOVE COUNTERTOP OR BACKSPLASHELECTRIC METALLIC TUBINGEWCELECTRIC WATER COOLERED13aSNIGHT LIGHTNLAT UNITAUFIRE SMOKE DAMPER. PROVIDE CONNECTIONS AS INDICATEDFSOS1PCPANELBOARD, 208/120V - SURFACE MOUNTEDBRANCH CIRCUIT HOMERUN: 2 #12, 1 #12G, 1/2"C TO PANELBOARD CIRCUIT NUMBER AS INDICATED UNLESS OTHERWISE NOTED.B1 / 12 = PANEL NAME / CIRCUIT NUMBERDESCRIPTIONSYMBOLABBREVIATIONSPHOTOCELL.WALL MOUNTED OCCUPANCY SENSOR, 1 = TYPE, REFER TOSPECIFICATIONS.WALL SWITCH, 3 = THREEWAY, a = FOR LIGHTING FIXTUREMARKED SAME.CEILING MOUNTED OCCUPANCY SENSOR, 3 = TYPE, REFER TOSPECIFICATIONS.SYMBOLGENERAL SYMBOLSREFERS TO KEYED DEMOLITION NOTE ON RESPECTIVE DRAWINGDESCRIPTIONDESCRIPTIONCOMBINATION MAGNETIC STARTERFUSED DISCONNECT SWITCHNON-FUSED DISCONNECT SWITCHSYMBOLSECONDARY SERVICE SYMBOLSPANELBOARD, 208/120V - RECESSED MOUNTEDMOTOR CONNECTION. EQUIPMENT AND CIRCUITRY AS INDICATED ON PLANS AND KEYED TO ELECTRICAL EQUIPMENT AND CONTROL SCHEDULE OR AS OTHERWISE NOTED.SFFFFIRE ALARM CONNECTION. SUBSCRIPT IDENTIFIES TYPE:FS - FIRE SMOKE DAMPER CONNECTIONFA - FIRE ALARM SHUTDOWN OF EQUIPMENTFIRE ALARM SYSTEM ANNUNCIATOR PANELSYMBOLFIRE ALARM SYSTEM CONTROL PANEL (FACP)FIRE ALARM SYMBOLSDESCRIPTIONFIRE ALARM SYSTEM THERMAL DETECTORFIRE ALARM SYSTEM MANUAL PULL STATIONFIRE ALARM SYSTEM SMOKE DETECTORFIRE ALARM SYSTEM SMOKE DETECTOR, DUCT MOUNTFIRE ALARM SYSTEM COMBINATION VISUAL AND AUDIBLEINDICATING DEVICE, WALL MOUNTED. STROBE INTENSITY 75CANDELAS, UNLESS INDICATED OTHERWISE. SUBSCRIPTS: WP - WEATHERPROOF, WG - WIREGUARDFIRE ALARM SYSTEM VISUAL (ONLY) INDICATING APPLIANCE, WALL MOUNTED, INTENSITY 75 CANDELA UNLESS INDICATED OTHERWISEFACPFAAFSWPFIRE ALARM SYSTEM - BEAM DETECTOR TYPE, TRANSMITTERTRBRDUPLEX RECEPTACLE OUTLET, WALL MOUNTED / ABOVE COUNTER MOUNTEDACG.F.C.I. DUPLEX RECEPTACLE OUTLET, WALL MOUNTED / ABOVE COUNTER MOUNTEDGF/ACGFDOUBLE DUPLEX RECEPTACLE OUTLET, WALL MOUNTED / ABOVE COUNTER MOUNTEDACWEATHERPROOF DUPLEX RECEPTACLE OUTLETWPFLUSH FLOOR MOUNTED DOUBLE DUPLEX RECEPTACLE OUTLETISOLATED GROUND DUPLEX RECEPTACLE OUTLETIGSPECIAL PURPOSE RECEPTACLE OUTLET, NEMA CONFIGURATION TO MATCH PLUGBRANCH CIRCUITRY: 2 #12, 1 #12G, 1/2"C UNLESS OTHERWISE NOTEDB1/12FFIRE ALARM SYSTEM COMBINATION VISUAL AND AUDIBLEINDICATING DEVICE, CEILING MOUNTED. STROBE INTENSITY 75CANDELAS, UNLESS INDICATED OTHERWISE. SUBSCRIPTS: WP - WEATHERPROOF, WG - WIREGUARDFIRE ALARM SYSTEM VISUAL (ONLY) INDICATING APPLIANCE, CEILING MOUNTED, INTENSITY 75 CANDELA UNLESS INDICATED OTHERWISEFDUPLEX RECEPTACLE OUTLET, SURACE MOUNTED FIRE ALARM SYSTEM - BEAM DETECTOR TYPE, RECEIVERSSDEVICE SYMBOLSDESCRIPTIONSYMBOLFIRE ALARM SYSTEM - SPRINKLER FLOW SWITCHFSFIRE ALARM SYSTEM - SPRINKLER TAMPER SWITCHTSDSD4 PORT (QUAD) USB CHARGER OUTLET WAPDESCRIPTIONSYMBOLVOICE/DATA SYMBOLSDATA OUTLET, WALL MOUNTED(2) CAT 6 CABLES / (2) RJ-45 JACKS UNLESS NOTED OTHERWISETYPE WAP (WIRELESS ACESS POINT) DATA OUTLET, CEILING MOUNTED(1) CAT 6A CABLE / (1) RJ-45 JACKWALL PHONE - (1) CAT 6 CABLE / (1) RJ-45 JACKE1REFERS TO KEYED NOTE ON RESPECTIVE DRAWINGHP-012FIRE ALARM SYSTEM MAGNETIC DOOR HOLD OPENETREXISTING TO REMAIN3OSSFIRE ALARM SYSTEM SMOKE DETECTOR, ELEVATOR RECALLRJJUNCTION BOXAUTOMATIC TRANSFER SWITCHATSPANELBOARD, 480/277V - SURFACE MOUNTEDPANELBOARD, 480/277V - RECESSED MOUNTEDDIMMER SWITCHJMS - CEILING MOUNTED, FLUSH, DOUBLE-GANG JUNCTION BOX FOR MOTORIZED SCREEN. COORDINATE LOCATION WITH AV CONTRACTOR AND ARCHITECT. XXDATA OUTLET FOR AV EQUIPMENT, WALL MOUNTED AT 18" AFF, UNLESS NOTED OTHERWISE(4) CAT 6 CABLES / (4) RJ-45 JACKS UNLESS NOTED OTHERWISEAV/4SS - WALL MOUNTED, FLUSH, SINGLE-GANG JUNCTION BOX FOR PROJECTOR SCREEN SWITCH. MOUNT AT 45" AFF COORDINATE LOCATION WITH AV CONTRACTOR AND ARCHITECT. DATA OUTLET FOR AV EQUIPMENT, WALL MOUNTED AT 78" AFF UNLESS NOTED OTHERWISE(2) CAT 6 CABLES / (2) RJ-45 JACKS UNLESS NOTED OTHERWISEAV/2AL -ASSISTIVE LISTENING TRANSMITTERAV -AUDIO VISUAL INTERFACEFP -FLAT PANEL DISPLAYPB -AV PANEL BOXCP -CONTROL PANELSCEILING MOUNTED SPEAKER.1FS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#19100DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910E001DRAWINGINDEX,SCHEDULES,SYMBOL LISTS& NOTES7/30/20201921ASC/JLRCORNELL UNIVERSITYConstruction DocumentsSnee Hall Renovation for Colocation ofEASELECTRICAL DRAWING INDEXNUMBER NAMEREVISIONS# DATEE001 DRAWING INDEX, SCHEDULES, SYMBOL LISTS & NOTES 1 8/12/20ED101 FIRST FLOOR DEMOLITION PLANED102 SECOND FLOOR DEMOLITION PLANED103 THIRD FLOOR DEMOLITION PLANED104 FOURTH FLOOR DEMOLITION PLANED105 ROOF DEMOLITION PLANE101 FIRST FLOOR POWER & SYSTEMS PLAN 1 8/12/20E102 SECOND FLOOR POWER & SYSTEM PLAN 1 8/12/20E103 THIRD FLOOR POWER & SYSTEMS PLANE104 FOURTH FLOOR POWER & SYSTEMS PLANE151 FIRST FLOOR LIGHTING PLANE152 SECOND FLOOR LIGHTING PLANE153 THIRD FLOOR LIGHTING PLANE154 FOURTH FLOOR LIGHTING PLANE500 SCHEDULES & DIAGRAMSTO THE BEST OF THE ENGINEER'S PROFESSIONAL JUDGEMENT, THE DESIGN OF THIS PROJECT CONFORMS TO ALL APPLICABLE PORTIONS OF THE FOLLOWING:THE 2020 NEW YORK STATE UNIFORM FIRE PREVENTION AND BUILDING CODETHE 2020 NEW YORK STATE ENERGY CONSERVATION CODE FOLLOWING THE COMPLIANCE PATH MARKED BELOW:ANSI / ASHRAE / IESNA 90.1IECC CHAPTER 4 [CE] PRESCRIPTIVE PROVISIONS (SECTIONS C402, C403, C404, C405, AND ONE OF THE SIX OPTIONS IN SECTION C406 AS NOTED BELOW:MORE EFFICIENT HVAC PERFORMANCE IN ACCORDANCE WITH SECTION C406.2.REDUCED LIGHTING POWER DENSITY SYSTEM IN ACCORDANCE WITH SECTION C406.3.ENHANCED LIGHTING CONTROL IN ACCORDANCE WITH SECTION C406.4.ON-SITE SUPPLY OF RENEWABLE ENERGY IN ACCORDANCE WITH SECTION C406.5.PROVISION OF A DEDICATED OUTDOOR AIR SYSTEM FOR CERTAIN HVAC EQUIPMENT IN ACCORDANCE WITH SECTION C406.6.HIGH-EFFICIENCY SERVICE WATER HEATING IN ACCORDANCE WITH SECTION C406.7.TOTAL BUILDING PERFORMANCE PROVISIONS (SECTION C407)THE BUILDING STANDARD OF THE NEW YORK STATE EDUCATION DEPARTMENTTHE 2014 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND OUTPATIENT FACILITIESALL SYMBOLS SHOWN ARE NOT NECESSARILY USEDSCALE: NOT TO SCALEE001A3DEVICE MOUNTING HEIGHTSRevision ScheduleName DateADDENDUM 1 8/12/20 SSSJJJJJJJJJJJFFFACPCROSOSJJOUTDOORPATIOCL57" AFFADOAUTO DOOR OPERATOR WITH INTERIOR PUSH PLATES AND EXTERIOR CARD READER AND PUSH PLATE. REFER TO DETAIL ON DWG E50018" AFFPB FP57"AFFAL116"AFF57" AFFFP66"AFF66"AFF (2)PROVIDE POWER TO WHEEL CHAIR LIFT IN ACCORDANCE TO MANUFACTURERS SPECIFICATIONSSUN SHADE CONTROLSUN SHADE CONTROLSUN SHADE LOW VOLTAGE POWER CONNECTION303072"AFF72"AFF (2)Map Room1134EX. PANELL10A45" AFFCP3" DEEP 2-GANGJ-BOX18" AFFAVRELOCATEDWAP11E2E21A. VERIFY EXACT LOCATION OF RECEPTACLES & DATA OUTLETS WITH ARCHITECT, ARCHITECT'S ELEVATION DRAWINGS, AV CONSULTANT AND TA-SERIES DRAWINGS PRIOR TO ROUGH-IN.B. PROVIDE SEPARATE NEUTRAL AND GROUND CONDUCTOR FOR EACH BRANCH CIRCUIT INDICATED.C. VERIFY EXACT LOCATION OF LIGHT FIXTURES WITH ARCHITECT AND ARCHITECT'S REFLECTED CEILING PLANS AND ELEVATION DRAWINGS PRIOR TO ROUGH-IN.D. CIRCUIT LIGHT FIXTURES TOGETHER WITH 2#10, #10E.G. - 1/2" CONDUIT, UNLESS NOTED OTHERWISE.E. UNLESS OTHERWISE INDICATED, AT ROOMS/LOCATIONS WHERE DIMMING SWITCHES ARE INDICATED PROVIDE 0-10V DIMMING / LIGHTING CONTROL. COORDINATE THE 0-10V DIMMING CONTROL WITH THE 0-10V LED DRIVERS AT LIGHT FIXTURES.F. NEW CABLING WILL ROUTE TO EXISTING CIT INFRASTRUCTURE.G. EXISTING CABLE TRAYS AND PULLBOXES SHALL REMAIN ACCESSIBLE.GENERAL NOTESFS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#19100DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910E101FIRST FLOORPOWER &SYSTEMS PLAN7/30/20201921ASC/JLRCORNELL UNIVERSITYConstruction DocumentsSnee Hall Renovation for Colocation ofEAS3"SCALE: 1/8" = 1'-0"E1011ELEC FIRST FLOOR POWER & SYSTEMS PLANELECTRICAL KEYED NOTESE2 REFER TO DETAIL NUMBER TWO "CHIEF PAC526" ON DRAWING TA551.1Revision ScheduleName DateADDENDUM 1 8/12/20 REF.SSSSSSJJJJJJJJJssFFFFFFFFFFFFFJJJComputer Lab2161AShared Workspace2149Workroom2161IT Office2161BOffice2116Office2112Office2108Toilet2014FP56" AFFAV18" AFFAV18" AFF56" AFF(2) 56" AFFPB18"AFF(8)RECEPTACLE IN CEILING FOR PROJECTORGFIACGFIAC36"AFF(2)(2)(6)66" AFFFP53"AFF53"AFF(2) 53"AFFAV18"AFFAV108" AFFCP45" AFFAV18" AFFClassroom2152Admin Suite2160Office2160AOffice2160COffice2160DChair Office2160B(2)(4)(4)(2)303030303030303030303030(6)PANEL L2LBL2LB/1L2LB/2L2LB/3L2LB/4PANEL L2L1L2L1/6 L2L1/5 L2L1/4L2L1/8L2L1/3L2L1/7L2L1/1Office2118Office2120FCU-1-2120FCU-1-2118Office2102CONNECT TO EXISTING ROOM CIRCUIT30WP/GFL2L1/9CONNECT TO EXISTING ROOM CIRCUITCONNECT TO EXISTING ROOM CIRCUITEX.PANELL20AEX. PANELH20ACIRCUIT TO SECOND FLOOR PANEL THAT FEEDS EXISTING CORRIDOR RECEPTACLESEX. PANELL2LCL2L1/11Shared Office2122Corridor200118" AFFAV45" AFFPROJECTION SWITCHL2L1/10POWER TO MOTORIZED PROJECTION SCREENWAPWAPWAPEX. PANELL2LAEX. PANELH2LAEX. PANELDL2LA11E2A. VERIFY EXACT LOCATION OF RECEPTACLES & DATA OUTLETS WITH ARCHITECT, ARCHITECT'S ELEVATION DRAWINGS, AV CONSULTANT AND TA-SERIES DRAWINGS PRIOR TO ROUGH-IN.B. PROVIDE SEPARATE NEUTRAL AND GROUND CONDUCTOR FOR EACH BRANCH CIRCUIT INDICATED.C. VERIFY EXACT LOCATION OF LIGHT FIXTURES WITH ARCHITECT AND ARCHITECT'S REFLECTED CEILING PLANS AND ELEVATION DRAWINGS PRIOR TO ROUGH-IN.D. CIRCUIT LIGHT FIXTURES TOGETHER WITH 2#10, #10E.G. - 1/2" CONDUIT, UNLESS NOTED OTHERWISE.E. UNLESS OTHERWISE INDICATED, AT ROOMS/LOCATIONS WHERE DIMMING SWITCHES ARE INDICATED PROVIDE 0-10V DIMMING / LIGHTING CONTROL. COORDINATE THE 0-10V DIMMING CONTROL WITH THE 0-10V LED DRIVERS AT LIGHT FIXTURES.F. NEW PANEL L2LB: PROVIDE 100A MLO 208/120V, 3PH, 4W WITH 12-20A/1P CIRCUIT BREAKERS. PROVIDE FEEDER 4#6, #10, 1"C FROM EXISTING 50A/3P CIRCUIT BREAKER IN PANEL DL2LA.G. NEW PANEL L2L1: PROVIDE 225 MLO, 208/120V, 3PH, 4W WITH 24 - 20A/1P CIRCUIT BREAKERS. PROVIDE FEEDER (4#1/0, #6, - 1 1/2"C). ADD 150A/3P CIRCUIT BREAKER IN EXISTING PANEL DL2LA.GENERAL NOTESFS ENGINEERING, DPC721 E. Genesee StreetSyracuse, NY 13210Tel: 315-471-4013Fax: 315-471-4044FS#19100DATE:PROJECT:OTHER:DRAWN BY:ABCDEFGABCDEF1234567891012345678910E102SECONDFLOOR POWER& SYSTEMPLAN7/30/20201921ASC/JLRCORNELL UNIVERSITYConstruction DocumentsSnee Hall Renovation for Colocation ofEAS3"SCALE: 1/8" = 1'-0"E1021ELEC SECOND FLOOR POWER & SYSTEMS PLANRECONNECT TO EXISTING CIRCUITELECTRICAL KEYED NOTESE2 REFER TO DETAIL NUMBER TWO "CHIEF PAC526" ON DRAWING TA551.1Revision ScheduleName DateADDENDUM 1 8/12/20