HomeMy WebLinkAboutOlin Chemical LabPAVED PARKING
PAVED
PARKING
UNPAVED PARKING
UNPAVED PARKING
SS
S
FP
SIGN
CB
CB
CB
CB
CB
CB
CB
CB CBCB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
191920202021212121202020201919
191920202021212121202020201919
191920202021212121202020201919
191920202021212121202020201919
191920202021212121202020201919
19
19
21
20202020
21
21212121212121
212121
21212121
UP
UP
DNUP
UP
DN
UPDN
OLIN HALL
2024
CAMPUS ROAD
COLLEGE AVE.HOY ROADCORNE
LL U N I V
E
R
SI
TYFOUN
D E D 5681
AD CORNE
LL U N I V
E
RSI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
N
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
Cornell University
OLIN HALL
OLIN HALL ROOM
204 LAB
RENOVATION
T-001
11982592
TITLE SHEET
FE DESIGN
JD
2024
DECEMBER 16, 2019
OLIN HALL ROOM 204 LAB RENOVATION
GENERAL
T-001 TITLE SHEET
ARCHITECTURAL
A-000 CODE COMPLIANCE PLAN, GENERAL NOTES
A-101 DEMOLITION AND RENOVATION PLAN
A-601 EQUIPMENT MATRIX
MECHANICAL
M-001 GENERAL NOTES AND SYMBOL LEGENDS
M-101 ROOM 204 DEMOLITION AND NEW WORK
ELECTRICAL
E-001 GENERAL NOTES AND SYMBOL LEGENDS
E-101 RENOVATION PLANS
SITE LOCATION -OLIN HALL
KEY PLAN -SECOND FLOOR
AREA OF WORK
BUILDING CODE SUMMARY
APPLICABLE CODES
2015 INTERNATIONAL BUILDING CODE*
2015 INTERNATIONAL EXISTING BUILDING CODE*
2015 INTERNATIONAL FIRE CODE*
2015 INTERNATIONAL PLUMBING CODE*
2015 INTERNATIONAL MECHANICAL CODE*
2015 INTERNATIONAL ENERGY CONSERVATION CODE*
* INCLUDING 2016 AND 2017 NYS UNIFORM CODE SUPPLEMENTS
2009 ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
2010 AMERICANS WITH DISABILITY ACT (ADA)
PROJECT SUMMARY
THIS PROJECT INCLUDES THE RENOVATION OF 384 SF OF LAB SPACE.
THE WORK IS ALTERATION LEVEL 2.
ALTERATION LEVEL 2:
LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE,
THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE
RECONFIGURATION OR EXTENTION OF ANY SYSTEM, OR THE INSTALLATION
OF ANY ADDITIONAL EQUIPMENT.
AN EXISTING BUILDING OR PORTION THEREOF SHALL NOT BE ALTERED
SUCH THAT THE BUILDING BECOMES LESS SAFE THAN ITS EXISTING
CONDITIONS.
BUILDING LIMITATIONS
CONSTRUCTION CLASSIFICATION:1A
CLASSIFICATION OF HAZARDS:NONE
HIGH-RISE BUILDING: NO
EXTINGUISHING REQUIREMENT:THE EXISTING BUILDING
IS SPRINKLERED
OCCUPANCY
OCCUPANCY CLASSIFICATION:BUSINESS (B)
AREA OF WORK
DRAWING INDEX
PROJECT SCOPE
THE PURPOSE OF THIS PROJECT IS TO PROVIDE FOR THE FIT-OUT OF ROOM 204 WITH RESEARCHER-FURNISHED LAB EQUIPMENT.
PERSPECTIVE VIEW
GENERAL SYMBOLS LEGEND
EXTERIOR ELEVATION
1
1
1 1X-100
X-100
1
1
1 1 INTERIOR ELEVATION
1
X-100
SECTION MARKER
1
X-100
ENLARGED DETAIL
#CONSTRUCTION KEYED NOTE
DEMOLITION KEYED NOTE#
DRAWING REVISION NOTE#
LINETYPE: TO BE PROVIDED / NEW
LINETYPE: DEMOLITION / TO BE RELOCATED
LINETYPE: EXISTING TO REMAIN
1 9/30/2019 ISSUE FOR PROGRESS SET REVIEW
2 10/25/2019 ISSUE FOR 50% CD REVIEW
3 11/26/2019 ISSUE FOR 95% CD REVIEW
4 12/03/2019 ISSUE FOR COORDINATED REVIEW
5 12/16/2019 ISSUE FOR CONSTRUCTION
200UR
111
31
178
361
373
49538554
378
555559
397382
535
300
522
153
245
840
507
251
516
505
291
249
319
320
318
318
317
320
320
155
252340
524
830
523
370
129
211
300
125
241
555
713
20
14
14
19
16
16
27
5498
7294
1120
26
26
107107
75
28
28
2932 1910
1342
367
165
263
200CC
200SC
200EA
201A
201B
201
202
203205
206
208
207209
210212
211
215
214
216218
222
230
228
224
232
244
246
248
250
252
254
256
258
260260A
274
270
276
278
278A
275A275
275B
265C
265B
265
267
255
255B
200SB
200EB
200TA
200UC
200JC
200JB
200TB
226
245
200JA
200UA
200UB
200SA
265A
200CA
200CB
255A
200SD
200SE
230A 230B
UP
UP
DNUP
UP
DN
UPDN
206A
95
101
A101
1
1
1 1
0
Name
Elevation
101
X-X
X
1t
DN
WALL -EXISTING
WALL -METAL STUD/ GWB
WALL -CONCRETE
WALL -CMU
WALL -BRICK
ITEMS FOR DEMOLITION
DOOR/ WALL -EXISTING
DOOR/ WALL -NEW
DOOR/ WALL -DEMOLITION
TAG -DOOR
TAG -WINDOW
TAG -WALL
TAG -ROOM #
CENTER LINE
PHOTO REFERENCE
LEVEL MARKER
COLUMN GRID MARKER
ELEVATION MARKER
UP
ELEVATION CHANGE ARROWS
BREAK LINE
SYMBOLS
0' -0"
1-HOUR FIRE SEPARATION
2-HOUR FIRE SEPARATION
ABBREVIATIONS
A
&AND
@ AT
ACT ACOUSTICAL CEILING TILE
ALT ALTERNATE
ALUM ALUMINUM
AVG AVERAGE
AFF ABOVE FINISH FLOOR
B
BD BOARD
BLDG BUILDING
BOD BOTTOM OF DECK
BSMT BASEMENT
C
CG CORNER GUARDS
CJ CONTROL JOINT
CLG CEILING
CL CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONT CONTINUOUS
CORR CORRIDOR
CPT CARPET
CRS COURSE(S)
CT CERAMIC TILE
D
DEMO DEMOLITION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DO DOOR OPENING
DWG DRAWING
E
EA EACH
EJ EXPANSION JOINT
ELEC ELECTRIC
ELEV ELEVATION/ ELEVATOR
EPDM RUBBER ROOF MEMBRANE
EQ EQUAL
EX'G EXISTING
EXT EXTERIOR
F
FD FLOOR DRAIN
FDN FOUNDATION
FEC FIRE EXTINGUISHER CABINET
FFE FINISH FLOOR ELEVATION
FRP FIBER REINFORCED POLYESTER
FT FOOT/FEET
FTG FOOTING
G
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERAL
GL GLASS
GWB GYPSUM WALL BOARD
H
HC HANDICAPPED
HT HEIGHT
HM HOLLOW METAL
HR HOUR
HVAC HEATING, VENTILATING & AC
J
JAN JANITOR
L
LAV LAVATORY
LB/#POUND
LGMF LIGHT GAGE METAL FRAMING
M
MFR MANUFACTURER
MAT MATERIAL
MAX MAXIMUM
MEZZ MEZZANINE
MIN MINIMUM
MO MASONRY OPENING
MTL METAL
N
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NR NOT RATED
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OSB ORIENTER STRAND BOARD
P
+/-PLUS OR MINUS
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PI PRINCIPAL INVESTIGATOR
Q
QTY QUANTITY
R
R RISER
RD ROOF DRAIN
REF REFRIGERATOR
REQ REQUIRED
REV REVISION
RO ROUGH OPENING
RTU ROOF TOP UNIT
S
SHTG SHEATHING
SIM SIMILAR
SF SQUARE FOOT/ FEET
SS STAINLESS STEEL
STL STEEL
STD STANDARD
T
T TREAD
T&G TONGUE & GROOVE
TEL TELEPHONE
TEMP TEMPERATURE
TOS TOP OF STEEL
TV TELEVISION
TYP TYPICAL
U
UEV UNEVEN DOORS W/ VISION PANEL
UEF UNEVEN FLUSH DOOR
V
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
W
W/O WITHOUT
WD WOOD
AREA OF WORK
66' TRAVEL DISTANCE
TO EXIT (IBC 1017.2:
MAX 300' WITH
SPRINKLER SYSTEM)CORNE
LL U N I V
E
RSI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
OLIN HALL
OLIN HALL ROOM
204 LAB
RENOVATION
A-000
11982592
CODE
COMPLIANCE
PLAN,
GENERAL
NOTES
N.HACHMANN
NH
2024
DECEMBER 16, 2019
SCOPE OF WORK
1.0 REMOVE AND/OR MODIFY EXISTING CASEWORK TO CREATE SPACE FOR NEW
EQUIPMENT. PATCH SURFACES AS NEEDED TO MATCH ADJACENT SURFACES.
GENERAL NOTES
1.0 DESIGN, CONSTRUCTION AND SAFETY SHALL CONFORM TO ALL LOCAL, STATE AND
OWNER SPECIFIC CODES, INCLUDING (BUT NOT LIMITED TO) THE NEW YORK STATE
UNIFORM FIRE PROTECTION AND BUILDING CODE, LATEST REVISION, THE NFPA 101
LIFE SAFETY CODE, LATEST REVISION, ANSI A117.1 - LATEST REVISION, OSHA, AND
ANY OTHER CODES GOVERNED BY THE JURISDICTION IN WHICH THIS PROJECT IS
BEING CONSTRUCTED.
2.0 THIS CONTRACT REQUIRES COMPLETE, FINISHED WORKABLE PROJECT OF THE
AREAS INDICATED BY THE CONTRACT DOCUMENTS, AND SHALL INCLUDE ALL
MATERIALS AND LABOR NECESSARY TO COMPLETE, REGARDLESS OF WHETHER OR
NOT ALL WORK OR EACH ITEM IS SPECIFICALLY INDICATED ON ANY OTHER
PORTION OF THE DRAWINGS AND / OR NOTES.
3.0 WHERE MATERIALS REFERENCED ON DRAWINGS, OR NECESSARY TO COMPLETE
THE WORK OF THIS CONTRACT ARE NOT SPECIFIED HEREIN, PROVIDE BEST
QUALITY MATERIALS. WHERE MATERIALS ARE INTENDED TO MATCH EXISTING,
PROVIDE CLOSEST POSSIBLE MATCH, SUBJECT TO OWNER'S APPROVAL. ALL ITEMS
AND WORK ON DRAWINGS ARE NEW, UNLESS INDICATED EXISTING. ALL WORK
WHICH HAS BEEN DAMAGED SHALL BE REPAIRED OR REPLACED AT NO COST TO
THE OWNER. WHERE ITEMS CAN NOT BE REPAIRED TO A ""NEW CONDITION"", OR
WHERE THE STRUCTURAL INTEGRITY HAS BEEN AFFECTED, ITEMS SHALL BE
REPLACED AT NO COST TO THE OWNER.
4.0 CONTRACTOR IS RESPONSIBLE TO VERIFY ALL SITE, FIELD AND BUILDING
CONDITIONS PRIOR TO SUBMITTING BIDS AND COMMENCING WORK. IF THERE ARE
ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS, NOTIFY THE
PROJECT MANAGER, WHO WILL REQUEST CLARIFICATION FROM THE
ARCHITECT/ENGINEER AND PROVIDE CLARIFICATION IN WRITING.
5.0 WHERE EXISTING CONSTRUCTION OR ITEMS HAVE BEEN INFILLED, REMOVED AND /
OR DISTURBED FOR INSTALLATION OF NEW WORK, CAUSING THE EXPOSURE OF
UNFINISHED AND/OR DAMAGED SURFACES RESULTING SURFACES AND INFILLED
SURFACES SHALL BE RECONSTRUCTED WITH MATERIALS TO MATCH FINISHED
AREAS. ALL ABANDONED OPENINGS (i.e. DUCT/PIPE REMOVALS, ETC.) AT WALLS,
ROOF OR FLOOR TO BE INFILLED SOLID.
6.0 WORK IS REQUIRED IN VARIOUS PORTIONS OF THE FACILITY TO EXECUTE WORK OF
OTHER TRADES (i.e. ELECTRICAL, MECHANICAL). ALTHOUGH NOT NECESSARILY
SHOWN ON DRAWINGS, WORK IS REQUIRED IN THESE AREAS CONSISTING OF
REMOVAL / REPLACEMENT OF CEILINGS, WALLS, FINISHES, PAVEMENT AND OTHER
CONSTRUCTION AS NECESSARY TO PERFORM WORK AND RESTORE THESE
SPACES OR AREAS TO ORIGINAL CONDITION.
7.0 GENERAL CONTRACTOR IS TO COORDINATE WORK OF ALL TRADES. SCHEDULE
WORK PROGRESS THROUGHOUT THE ENTIRE PROJECT TO PREVENT CONFLICTS
AND INTERFERENCES. OBTAIN ALL NECESSARY INFORMATION SUCH AS SIZES,
LOCATIONS, TEMPLATES, LAYOUT, DIMENSIONS AND ALL OTHER INFORMATION
NECESSARY FOR A PROPER AND WELL COORDINATED INSTALLATION. PRIOR TO
INSTALLATION OF ITEMS, VERIFY AND CONFIRM WITH EACH CONTRACTOR EXACT
LOCATION OF ALL ITEMS.
8.0 ALL PENETRATIONS (EXISTING OR NEW) THROUGH FLOORS AND FULL HEIGHT
WALLS - IN AREA OF WORK TO BE FIRE STOPPED. ALL GAPS AND JOINTS AT RATED
FLOORS, ROOFS AND WALLS TO BE FIRE & SMOKE STOPPED. GAPS AND JOINTS
INCLUDE (BUT ARE NOT LIMITED TO) TOP OF WALL TO FLOOR OR ROOF DECK, WALL
TO BEAMS, AND CONTROL OR EXPANSION JOINTS. FIRE STOPPING INCLUDES BOTH
FORM OR PACKING MATERIAL AND THE FILL, VOID OR CAVITY MATERIAL. PROVIDE
AND INSTALL LABELING REQUIRED BY CODE. LABELS SHALL INCLUDE
PENETRATION TYPE WITH UL LISTING USED, MATERIAL USED, DATE INSTALL AND
NAME OF INSTALLER.
9.0 JOBSITE WILL BE CLEANED DAILY AND DEBRIS REMOVED TO CONTAINERS OR TO
VEHICLE WHICH WILL REMOVE DEBRIS FROM CAMPUS. CONTAINERS WILL BE
REMOVED AS SOON AS FULL OR WHEN THE PROJECT HAS PROGRESSED TO A
POINT THAT A CONTAINER IS NO LONGER REQUIRED.
10.0 CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL AREAS USED TO BRING
SUPPLIES AND EQUIPMENT INTO THE PROJECT AREA. ANY DAMAGE TO AREAS
OUTSIDE THE PROJECT AREA INCLUDING BUT NOT LIMITED TO THE LOBBY AND
CORRIDOR SHALL BE REPAIRED AT NO COST TO THE OWNER.
SCALE: 1/16" = 1'-0"
1 CODE COMPLIANCE PLAN - SECOND FLOOR
BUILDING CODE SUMMARY
APPLICABLE CODES
2015 INTERNATIONAL BUILDING CODE*
2015 INTERNATIONAL EXISTING BUILDING CODE*
2015 INTERNATIONAL FIRE CODE*
2015 INTERNATIONAL PLUMBING CODE*
2015 INTERNATIONAL MECHANICAL CODE*
2015 INTERNATIONAL ENERGY CONSERVATION CODE*
* INCLUDING 2016 AND 2017 NYS UNIFORM CODE SUPPLEMENTS
2009 ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
2010 AMERICANS WITH DISABILITY ACT (ADA)
PROJECT SUMMARY
THIS PROJECT INCLUDES THE RENOVATION OF 384 SF OF LAB SPACE.
THE WORK IS ALTERATION LEVEL 2.
ALTERATION LEVEL 2:
LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE,
THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE
RECONFIGURATION OR EXTENTION OF ANY SYSTEM, OR THE INSTALLATION
OF ANY ADDITIONAL EQUIPMENT.
AN EXISTING BUILDING OR PORTION THEREOF SHALL NOT BE ALTERED
SUCH THAT THE BUILDING BECOMES LESS SAFE THAN ITS EXISTING
CONDITIONS.
BUILDING LIMITATIONS
CONSTRUCTION CLASSIFICATION:1A
CLASSIFICATION OF HAZARDS:SEE MAQ
HIGH-RISE BUILDING:NO
EXTINGUISHING REQUIREMENT:THE EXISTING BUILDING
IS SPRINKLERED
OCCUPANCY
OCCUPANCY CLASSIFICATION:BUSINESS (B)
1 10/25/2019 ISSUED FOR 50% CD REVIEW
2 11/26/2019 ISSUED FOR 95% CD REVIEW
3 12/03/2019 ISSUED FOR COORDINATED REVIEW
4 12/16/2019 ISSUED FOR CONSTRUCTION
1
2
3
4
65
22
3
3
65
204
32 4
5 6 7
3' - 5"E8aE8aE7aE7a E9aE9a E4aE4a E5aE5a
E3aE3a
E6aE6a
E11aE11a
E10aE10a
E1aE1a
E2aE2a
8
5' - 0"4' - 6"3' - 6".9
E1c
1
1 CORNE
LL U N I V
E
RSI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
N
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
OLIN HALL
OLIN HALL ROOM
204 LAB
RENOVATION
A-101
11982592
DEMOLITION
AND
RENOVATION
PLAN
N.HACHMANN
NH
2024
DECEMBER 16, 2019
A-101 RENOVATION KEY NOTES
1 REINSTALL SUSPENDED CEILING SYSTEM AFTER THE COMPLETION OF
MECHANICAL, ELECTRICAL, AND PLUMBING WORK. REPLACE ANY DAMAGED PIECES
WITH NEW ACOUSTICAL CEILING PANELS AND GRID TO MATCH EXISTING.
2 AFTER REMOVAL OF WALL MOUNTED ITEMS, PATCH WALL AND TOUCH UP PAINT TO
MATCH ADJACENT.
3 PAINT MISCELLANEOUS PIPING AND CONDUIT TO MATCH WALL COLOR.
4 COORDINATE WITH MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION
DRAWINGS.
5 EXISTING CASEWORK AND FUME HOOD TO REMAIN UNLESS NOTED OTHERWISE.
6 SEE MECHANICAL PLAN FOR EQUIPMENT INFORMATION.
7 FIRESTOP ANY WALL PENETRATIONS TO ADJACENT ROOMS AND CORRIDOR TO
MAINTAIN ONE-HOUR FIRE RATING.
8 TABLE PROVIDED BY LAB OWNER.
9 PROVIDE METAL END PANEL TO MATCH EXISTING CABINETRY FINISH.
#
A-101 DEMOLITION KEY NOTES
1 HAZARDOUS MATERIALS ARE NOT EXPECTED. ALERT OWNER IF ENCOUNTERING
SUSPICIOUS MATERIAL. OWNER WILL PERFORM REMOVAL OF ASBESTOS AND PCB
CONTAINING MATERIAL.
2 MODIFY EXISTING CABINETRY TO REMOVE COMPONENTS WHERE NOTED. AT
EXISTING SINK LOCATION, CUT COUNTERTOP AND FINISH EDGE TO MATCH
EXISTING. COORDINATE WITH MEPFP DRAWINGS.
3 REMOVE EXISTING LOOSE EQUIPMENT AND FURNITURE AND TURN OVER TO
OWNER.
4 CAREFULLY REMOVE WALL MOUNTED ITEMS AND SALVAGE FOR REINSTALLATION
AS DIRECTED BY OWNER.
5 CAREFULLY REMOVE THE PORTION OF THE EXISTING SUSPENDED CEILING
SYSTEM AS REQUIRED TO PERFORM MECHANICAL, ELECTRICAL, PLUMBING, AND
FIRE PROTECTION WORK. SALVAGE FOR REINSTALLATION AFTER COMPLETION OF
MEPFP WORK.
6 SEE MEPFP DRAWINGS FOR REMOVAL OF MEPFP EQUIPMENT AND COORDINATE
ACCORDINGLY.
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
SCALE: 1/4" = 1'-0"
1 DEMOLITION PLAN - ROOM 204
SCALE: 1/4" = 1'-0"
2 RENOVATION PLAN - ROOM 204
SCALE: 1/4" = 1'-0"
3 REFLECTED CEILING PLAN - ROOM 204
SCALE:5 3D - ROOM 204 FROM NORTHWEST
SCALE:4 3D - ROOM 204 FROM SOUTHEAST
LABORATORY EQUIPMENT LIST
TAG ROOM
FURNISHED
BY
RIGGED
AND
MOUNTED
BY
DESCRIPTION
BASIS OF DESIGN
LOCATION
DIMENSIONS
WEIGHT
(LBS)
CONTRACTOR PROVIDED SERVICES
MANUFACTURER MODEL
WIDTH
(IN)
DEPTH
(IN)
HEIGHT
(IN)
E1a 204 OWNER OWNER LIQUID CHROMATOGRAPH MASS SPECTROMETER AGILENT G6545 UHD ACCURATE-MASS BENCH 48.0 30.0 76.0 400 EXHAUST DUCTWORK, POWER (SERVED
BY E11 UPS)
E1b 204 OWNER OWNER COMPUTER - - BENCH - - - - SERVED BY E11 UPS
E1c 204 OWNER OWNER BENCH - - FLOOR 84.0 36.0 25.0 - -
E2a 204 OWNER OWNER NITROGEN GENERATOR PARKER NITROFLOW FLOOR 12.2 35.4 27.6 204 SERVED BY E11 UPS
E3a 204 OWNER OWNER -86°C FREEZER EPPENDORF PREMIUM U410 FLOOR 31.5 33.5 76.0 617 SERVED BY E11 UPS
E4a 204 OWNER OWNER EXISTING TO BE RELOCATED - UNDER COUNTER -20°C FREEZER - - FLOOR - - - - -
E5a 204 OWNER OWNER EXISTING TO BE RELOCATED - UNDER COUNTER 4°C REFRIGERATOR - - FLOOR - - - - -
E6a 204 OWNER OWNER POWERPAC POWER SUPPLY BIO-RAD POWERPAC BASIC BENCH 8.3 9.6 2.6 2.4 -
E7a 204 OWNER OWNER INCUBATOR SHAKER EPPENDORF INNOVA 42R BENCH 22 29.7 32.8 267 -
E8a 204 OWNER OWNER INCUBATOR THERMOFISHER 3110 BENCH 21.3 25.0 39.5 400 -
E9a 204 OWNER OWNER CENTRIFUGE EPPENDORF 5910 R BENCH 28.4 26.0 14.6 240 -
E10a 204 OWNER OWNER MILLI Q WATER PURIFICATION SYSTEM EMD MILLIPORE BENCH 13.0 19.0 19.7 62 PLUGS INTO EXISTING RECEPTACLE
E11a 204 OWNER OWNER UNINTERRUPTIBLE POWER SUPPLY AMETEK POWERVAR 42060-113R FLOOR 9.8 28.3 32.5 266 -
SUBMITTAL REGISTRY
SPECIFICATION
SECTION TITLE CATEGORY
099123 INTERIOR PAINTING PRODUCT DATA
1 10/25/2019 ISSUED FOR 50% CD REVIEW
2 11/26/2019 ISSUED FOR 95% CD REVIEW
3 12/03/2019 ISSUED FOR COORDINATED REVIEW
4 12/16/2019 ISSUED FOR CONSTRUCTION
CORNE
LL U N I V
E
RSI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
OLIN HALL
OLIN HALL ROOM
204 LAB
RENOVATION
A-601
11982592
EQUIPMENT
MATRIX
N.HACHMANN
NH
2024
DECEMBER 16, 2019
LABORATORY EQUIPMENT MATRIX
TAG ROOM STATUS FURNISHED BY
RIGGED AND
MOUNTED BY
INSTALLATION
INSTRUCTIONS/
CHECKLIST
DESCRIPTION
BASIS OF DESIGN
LOCATION
DIMENSIONS
WEIGHT
(LBS)
ELECTRICAL HOUSE LABORATORY PLUMBING SYSTEMS
CYLINDER
GASES
OPERATING ENVIRONMENT
REQUIREMENTS HEAT
GENERATION
(BTUH)
EXHAUST
CFM
CONTRACTOR PROVIDED SERVICES
MANUFACTURER MODEL
WIDTH
(IN)
DEPTH
(IN)
HEIGHT
(IN)VOLT PH
H
Z
RATING
(KW, W,
VA, A,
HP)
RECEPTACLE
NEMA RATING GROUND EMERGENCY
POWER DCW DHW
LAB
DRAIN
LAB
VENT RODI
GAS
PROP
ANE
VAC CA (85
PSI)CA LP TEMP
°F
HUMIDITY
%
VIBRATION
SENSITIVE
E1a 204 - OWNER OWNER YES
LIQUID CHROMATOGRAPH
MASS SPECTROMETER AGILENT G6545 UHD
ACCURATE-MASS BENCH 48.0 30.0 76.0 400 208 1 60 2850 W 6-15R - YES - - - - - - - - -
YES
(NOTE 1)YES 9,640 25
EXHAUST DUCTWORK, POWER
(SERVED BY E11 UPS)
E1b 204 - OWNER OWNER N/A COMPUTER - - BENCH - - - - 120 1 60 - - - YES - - - - - - - - - - - - NO 325 0 SERVED BY E11 UPS
E1c 204 - OWNER OWNER N/A BENCH - - FLOOR 84.0 36.0 25.0 - - - - - - -N/A - - - - - - - - - - - - NO - 0 -
E2a 204 - OWNER OWNER YES NITROGEN GENERATOR PARKER NITROFLOW FLOOR 12.2 35.4 27.6 204 110 1 60 1265 W 5-20R - YES - - - - - - - -- -
41-
104°F
80% @
87.8°F NO 5,756 0
SERVED BY E11 UPS
E3a 204 - OWNER OWNER YES -86°C FREEZER EPPENDORF PREMIUM U410 FLOOR 31.5 33.5 76.0 617 208 1 60 8 A 6-15R - YES - - - - - - - - - -NO 2220 0 SERVED BY E11 UPS
E3b 204 - CONTRACTOR CONTRACTOR N/A ELECTRICAL CABLE/CORD
REFER TO ELEC
DWGS
REFER TO ELEC
DWGS WALL - - - - 208 1 60 - 6-15R - YES - - - - - - - - - - - - NO - 0
POWER, SERVED BY E11 UPS
REFER TO ELECTRICAL DRAWINGS
E4a 204 EXISTING OWNER OWNER NO
EXISTING TO BE RELOCATED
- UNDER COUNTER -20°C
FREEZER
- - FLOOR - - - - 120 1 60 2.2 A 5-20R - NO - - - - - - - - - - NO 871 0
-
E4b 204 - CONTRACTOR CONTRACTOR N/A RECEPTACLE
REFER TO ELEC
DWGS
REFER TO ELEC
DWGS WALL - - - - 120 1 60 - 5-20R - NO - - - - - - - - - - - - NO - 0
POWER, REFER TO ELECTRICAL
DRAWINGS
E5a 204 EXISTING OWNER OWNER NO
EXISTING TO BE RELOCATED
- UNDER COUNTER 4°C
REFRIGERATOR
- - FLOOR - - - - 120 1 60 2.2 A 5-20R - NO - - - - - - - - - - NO 871 0
-
E5b 204 - CONTRACTOR CONTRACTOR N/A RECEPTACLE
REFER TO ELEC
DWGS
REFER TO ELEC
DWGS WALL - - - - 120 1 60 - 5-20R - NO - - - - - - - - - - - - NO - 0
POWER, REFER TO ELECTRICAL
DRAWINGS
E6a 204 - OWNER OWNER YES POWERPAC POWER SUPPLY BIO-RAD POW ERPAC BASIC BENCH 8.3 9.6 2.6 2.4 120 1 60 75 W 5-20R - YES - - - -- - - - - - NO - 0 -
E6b 204 - CONTRACTOR CONTRACTOR N/A RECEPTACLE
REFER TO ELEC
DWGS
REFER TO ELEC
DWGS WALL - - - - 120 1 60 - 5-20R - YES - - - - - - - - - - - - NO - 0
POWER, REFER TO ELECTRICAL
DRAWINGS
E7a 204 - OWNER OWNER YES INCUBATOR SHAKER EPPENDORF INNOVA 42R BENCH 22 29.7 32.8 267 120 1 60 1800 W 5-20R - NO - - - - - - - - -- NO 344 0 -
E7b 204 - CONTRACTOR CONTRACTOR N/A RECEPTACLE
REFER TO ELEC
DWGS
REFER TO ELEC
DWGS WALL - - - - 120 1 60 - 5-20R - NO - - - - - - - - - - - - NO - 0
POWER, REFER TO ELECTRICAL
DRAWINGS
E8a 204 - OWNER OWNER YES INCUBATOR THERMOFISHER 3110 BENCH 21.3 25.0 39.5 400 115 1 60 432 W 5-20R - NO - - - - - - - - - - NO 344 0 -
E8b 204 - CONTRACTOR CONTRACTOR N/A RECEPTACLE
REFER TO ELEC
DWGS
REFER TO ELEC
DWGS WALL - - - - 120 1 60 - 5-20R - NO - - - - - - - - - - - - NO - 0
POWER, REFER TO ELECTRICAL
DRAWINGS
E9a 204 - OWNER OWNER YES CENTRIFUGE EPPENDORF 5910 R BENCH 28.4 26.0 14.6 240 120 1 60 1650 W 5-20R - NO - - - - - - - - - - NO - 0 -
E9b 204 - CONTRACTOR CONTRACTOR N/A RECEPTACLE
REFER TO ELEC
DWGS
REFER TO ELEC
DWGS WALL - - - - 120 1 60 - 5-20R - NO - - - - - - - - - - - - NO - 0
POWER, REFER TO ELECTRICAL
DRAWINGS
E10a 204 - OWNER OWNER NO
MILLI Q WATER
PURIFICATION SYSTEM EMD MILLIPORE BENCH 13.0 19.0 19.7 62 115 1 60 - 5-20R GFCI - NO - - - - - - - - - - NO - 0
PLUGS INTO EXISTING RECEPTACLE
E10b 204 EXISTING - - N/A EXISTING RECEPTACLE
REFER TO ELEC
DWGS
REFER TO ELEC
DWGS WALL - - - - 120 1 60 - 5-20R GFCI - NO - - - - - - - - - - - - NO - 0
-
E11a 204 - OWNER OWNER NO
UNINTERRUPTIBLE POWER
SUPPLY AMETEK POWERVAR 42060-113R FLOOR 9.8 28.3 32.5 266 208 1 60
6000
VA 6-50R - YES - - - - - - - - - - NO 2,530 0
-
E11b 204 - CONTRACTOR CONTRACTOR N/A ELECTRICAL CABLE/CORD REFER TO ELEC
DWGS
REFER TO ELEC
DWGS CABLE - - - - 208 1 60 - 6-50R - YES - - - - - - - - - - - - NO - 0
POWER, REFER TO ELECTRICAL
DRAWINGS
1 12/16/2019 ISSUED FOR CONSTRUCTION
NOTES:
1) CYLINDER GAS, IN SMALL QUANTITY, PROVIDED BY LAB OWNER
2) ITEMS 3b, 4b, 5b, 6b, 7b, 8b, 9b, 10b, & 11b HAVE BEEN INCLUDED ON THIS MATRIX BUT ARE NOT TAGGED ON THE ELECTRICAL DRAWINGS.
CORNE
LL U N I V
E
RSI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
OLIN HALL
OLIN HALL ROOM
204 LAB
RENOVATION
M-001
11982592
GENERAL
NOTES AND
SYMBOL
LEGENDS
P. OCKENFELS
PCO
2024
DECEMBER 16, 2019
MECHANICAL ABBREVIATIONS
BCU BLOWER COIL UNIT
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CC CLEAN CONDENSATE
CO CLEAN OUT
CS CLEAN STEAM
CD CONDENSATE DRAIN
EA EXHAUST AIR
EAG EXHAUST AIR GRILLE
FD FIRE DAMPER
GWR GLYCOL HEATING RETURN
GWS GLYCOL HEATING SUPPLY
HPR HIGH PRESSURE STEAM RETURN
HPS HIGH PRESSURE STEAM SUPPLY
HWR HOT WATER HEATING RETURN
HWS HOT WATER HEATING SUPPLY
LPC LOW PRESSURE CONDENSATE
LPS LOW PRESSURE STEAM
MU MAKE UP WATER
MPC MEDIUM PRESSURE CONDENSATE
MPS MEDIUM PRESSURE STEAM
NG NATURAL GAS
PCWR PROCESS CHILLED WATER RETURN
PCWS PROCESS CHILLED WATER SUPPLY
HG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
RAG RETURN AIR GRILLE
SA SUPPLY AIR
SAD SUPPLY AIR DIFFUSER
VD VOLUME DAMPER
MECHANICAL SYMBOLOGY
AIRFLOW
BACKFLOW PREVENTER
BALANCE VALVE
BALL VALVE
BOTTOM PIPE CONNECTION
BUTTERFLY VALVE
CAP OR PLUG
CHECK VALVE
CIRCULATING PUMP
DIRECTION OF FLOW
DUCT AIRFLOW
DUCT DOWN (EXHAUST OR RETURN)
DUCT DOWN (SUPPLY)
FIRE AND SMOKE DAMPER IN DUCT
FIRE DAMPER IN DUCT
FLANGE CONNECTION
FLEX CONNECTOR
FLEXIBLE CONNECTION
FLEXIBLE DUCT
FLOW METER
FLOW SWITCH
FUSIBLE LINK VALVE
GLOBE VALVE
MANUAL AIRVENT
ORIFICE METER
PIPE DOWN
PIPE UP
PIPING REDUCER (CONCENTRIC)
PIPING REDUCER (ECCENTRIC)
PRESSURE GAUGE
PRESSURE OR TEMPERATURE PETES PLUG
PRESSURE REDUCING VALVE
PRESSURE SWITCH
RECTANGULAR ELBOW
RECTANGULAR ELBOW WITH TURNING VANES
RELIEF VALVE
SMOKE DAMPER IN DUCT
SOLENOID VALVE
STANDARD BRANCH DUCT
STEAM TRAP
STRAINER (DUPLEX)
STRAINER WITH BLOWDOWN VALVE AND CAP
SUPPLY THROUGH NEXT FLOOR OR ROOF
TEMPERATURE WELL
THERMOMETER
THERMOMETER (DIAL)
TOP PIPE CONNECTION
TRIPLE DUTY VALVE
UNION CONNECTION
VACUUM BREAKER
VOLUME DAMPER IN DUCT
GENERAL DRAWING SYMBOLOGY
DEMOLISHED WORK
EXISTING PIPING TO REMAIN
EXISTING TO REMAIN
EXISTING WORK TO REMAIN
NEW WORK
POINT OF CONNECTION
POINT OF DISCONNECTION
CONTROL ABBREVIATIONS
AI ANALOG INPUT
AO ANALOG OUTPUT
AV ANALOG VALUE
BI BINARY INPUT
BO BINARY OUTPUT
BV BINARY VALUE
F.L. FAIL LAST
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
VFD VARIABLE FREQUENCY DRIVE
MECHANICAL SCOPE OF WORK
1.0 REMOVE DOMESTIC HOT WATER, COLD WATER, RO, AND LAB WASTE PIPING
SERVING THE SINK.
2.0 PROVIDE EXHAUST DUCT WITH BLAST GATE DAMPER TO SERVE TO MASS
SPECTROMETER.
3.0 PERFORM PRE-CONSTRUCTION AND POST-CONSTRUCTION AIR BALANCING ON THE
EXHAUST DUCTWORK SERVING LAB 204. DOCUMENT EXHAUST AIRFLOWS AT THE
24”X24” GENERAL EXHAUST AIR GRILLE WHILE THE FUME HOOD IS AT MAXIMUM
SASH HEIGHT AND MINIMUM SASH HEIGHT. DOCUMENT EXHAUST AIRFLOWS AT
THE 4” DUCT, SERVING THE MASS SPECTROMETER, WHILE THE FUME HOOD IS AT
MAXIMUM SASH HEIGHT AND MINIMUM SASH HEIGHT. BALANCE THE 4” MASS
SPECTROMETER EXHAUST DUCT TO A MINIMUM OF 25 CFM WHEN THE FUME HOOD
SASH IS IN THE MAXIMUM POSITION.
DUCT SCHEDULE AND SPECIFICATIONS
DUCT
SERVICE
LOCATION PRESSURE CLASS SEAL CLASS DUCT MATERIAL LINING
INSULATION
MIN R-VALUE MATERIAL FIELD JACKET FINISH
EXHAUST: LAB 3" NEG A STAINLESS STEEL NONE NONE - - NONE
NOTES:
1. ALL DUCTWORK AND ACCESSORIES SHALL BE FABRICATED AND INSTALLED IN COMPLIANCE WITH THE LATEST ISSUE OF SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS -METAL
AND FLEXIBLE.
2. CONSTRUCT TEES, BENDS, AND ELBOWS WITH RADIUS OF NOT LESS THAN 1.0 TIMES THE WIDTH OF DUCT ON CENTER LINES.
3. WHERE RECTANGULAR ELBOWS ARE USED, PROVIDE AIR FOIL TYPE TURNING VANES.
4. INCREASE DUCT SIZES GRADUALLY, AND IN COMPLIANCE WITH FIGURE 4-7 OF SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS -METAL AND FLEXIBLE. BRANCH CONNECTIONS
SHALL BE MADE WITH A 45 DEGREE ENTRY. STRAIGHT TEES ARE NOT ACCEPTABLE.
5. SEALANTS AND GASKETS: SURFACE BURNING CHARACTERISTICS SHALL BE A MAXIMUM FLAME-SPREAD INDEX OF 25, AND MAXIMUM SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED
TO UL 723.
6. REMOVE SURFACE CONTAMINANTS AND DEPOSITS FROM DUCTWORK AND EQUIPMENT PRIOR TO TESTING AND BALANCING.
7. PROVIDE ESCUSION PLATE WHERE DUCT PENETRATES THROUGH THE CEILING, PROVIDE MANUAL BLAST DAMPER BELOW THE CEILING FOR VOLUME CONTROL.
DUCT ACCESSORIES SCHEDULE
TAG DESCRIPTION
BASIS OF DESIGN
SIZE MATERIALMANUFACTURER MODEL
BG-1 STAINLESS STEEL, HEAVY DUTY 12 GA BODY AND BLADE BLASTGATE BGG04C 4"ø-4"ø 304 STAINLESS STEEL
VD
FRAMES: 16 GA GALVANIZED STEEL, HAT-SHAPED, MITERED AND WELDED CORNERS
BLADES: 16 GA GALVANIZED STEEL, MULTIPLE BLADE, OPPOSED-BLADE DESIGN
BLADE AXLE: GALVANIZED STEEL
BEARINGS: MOLDED SYNTHETIC
OPTIONS: LOCKING HAND QUADRANT
FRAMES: 20 GA GALVANIZED STEEL
BLADES: 20 GA GALVANIZED STEEL
BLADE AXLE: GALVANIZED STEEL
BEARINGS: MOLDED SYNTHETIC
OPTIONS: LOCKING HAND QUADRANT
RUSKIN MD35 16"x10"-16"x10" GALVANIZED STEEL
MECHANICAL SUBMITTAL SCHEDULE
SECTION TITLE REQUIRED
230529 HANGERS & SUPPORTS FOR HVAC PRODUCT DATA
230593 TESTING, ADJUSTING & BALANCING FOR HVAC QUALIFICATIONS, INSPECTION AND TEST REPORTS
233100 DUCTWORK PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M
233300 AIR DUCT ACCESSORIES PRODUCT DATA
FIELD VERIFY
MECHANICAL GENERAL NOTES
1.0 DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT
OF SYSTEMS AND WORK INCLUDED IN THE CONTRACT. CONTRACTOR SHALL
FIELD VERIFY ALL DIMENSIONS. IF DIMENSIONS OR CONDITIONS ARE FOUND
TO BE IN CONFLICT WITH THE DRAWINGS, THE CONTRACTOR SHALL
IMMEDIATELY REFER THE CONFLICT TO THE ENGINEER.
2.0 UTILITY SHUTDOWNS: SHUTDOWN OF ANY BUILDING UTILITY SYSTEM SHALL
BE COORDINATED WITH CUSTOMER SERVICE AT PH: 607-255-5322. THE
CONTRACTOR SHALL BEAR THE COST OF THE UTILITY SHUTDOWN.
SCHEDULE WORK TEN DAYS IN ADVANCE AND NOTIFY THE OWNER'S
REPRESENTATIVE TO COORDINATE BUILDING FUNCTIONS WITH THE
BUILDING COORDINATOR.
3.0 ALL PENETRATIONS THROUGH FULL HEIGHT WALLS ARE TO BE FIRESTOPPED
IN ACCORDANCE WITH UL STANDARDS. ALL GAPS AND JOINTS AT RATED
FLOORS, ROOFS AND WALLS ARE TO BE FIRE AND SMOKE STOPPED. CAPS
AND JOINTS INCLUDE (BUT ARE NOT LIMITED TO) TOP OF WALL TO FLOOR OR
ROOF DECK, WALL TO BEAMS, AND CONTROL OR EXPANSION JOINTS.
FIRESTOPPING INCLUDES BOTH FORM OR PACKING MATERIAL AND THE FILL,
VOID OR CAVITY MATERIAL.
4.0 INSTALL EQUIPMENT TO ENSURE PROPER ACCESS AND WITH SUFFICIENT SPACE TO
PERFORM ROUTINE MAINTENANCE AND
REPAIR. EQUIPMENT THAT IS NOT INSTALLED WITH THIS REQUIREMENT IN
MIND SHALL BE RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL
DEFICIENCIES ARE CORRECTED.
5.0 ALL SYSTEM TESTING SHALL BE CONDUCTED PRIOR TO INSULATION,
FIREPROOFING, AND ENCLOSURE IN SHAFTS. ANY RESTORATION WORK
REQUIRED AS A RESULT OF DISTURBING FINISHES OR STRUCTURE IN ORDER
TO ACCESS SYSTEMS REQUIRING REPAIR SHALL BE AT NO COST TO THE
UNIVERSITY.
6.0 VERIFY FINAL EQUIPMENT/FIXTURE LOCATIONS FOR ROUGHING-IN.
7.0 ANY FIRESTOPPING DISTURBED DURING THE COURSE OF WORK SHALL BE
REPAIRED TO MAINTAIN A 2-HOUR FIRE RATING.
8.0 CUTTING AND PATCHING: THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
CUTTING, FITTING, AND PATCHING TO COMPLETE THE WORK. WHERE EXISTING
CONSTRUCTION IS REMOVED, CAUSING AN EXPOSURE OF UNFINISHED AND/OR
DAMAGED SURFACES, RESULTING SURFACES SHALL BE RECONSTRUCTED WITH
MATERIALS TO MATCH FINISHED AREAS.
1 9/30/2019 ISSUE FOR PROGRESS SET REVIEW
2 10/25/2019 ISSUE FOR 50% CD REVIEW
3 11/26/2019 ISSUE FOR 95% CD REVIEW
4 12/03/2019 ISSUE FOR COORDINATED REVIEW
5 12/16/2019 ISSUE FOR CONSTRUCTION
204
1
EXHAUST
AIR VAV
TB-55 (E)
25 CFM
MINIMUM
E1a
4" DIA
12" DIA.
VD
204
REMOVE SINK AND
ASSOCIATED PIPING
AND FIXTURES.
1 CORNE
LL U N I V
E
RSI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
N
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.FCS.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
OLIN HALL
OLIN HALL ROOM
204 LAB
RENOVATION
M-101
11982592
ROOM 204
DEMOLITION
AND NEW
WORK
P. OCKENFELS
PCO
2024
DECEMBER 16, 2019
0 2 4 8
SCALE: 1/4"=1'-0"
SCALE:1/4" = 1'-0"2 2ND FLOOR NEW
SCALE:1/4" = 1'-0"1 2ND FLOOR DEMOLITION
M-101 KEYED CONSTRUCTION NOTES
1
4" ROUND EXHAUST AIR DROP ADJACENT TO THE MASS SPECTROMETER.
TERMINATE 12" BELOW CEILING WITH BLAST GATE. COORDINATE EXACT LOCATION
WITH LAB OWNER. PROVIDE ESCUTCHEON AT CEILING PENETRATION.
#
M-101 KEYED DEMOLITION NOTES
1
DISCONNECT AND REMOVE EXISTING SINK, TRIM AND ALL ASSOCIATED PIPING.
REMOVE EXISTING SANITARY, VENT, DOMESTIC AND RO WATER PIPING BACK TO
MAINS AND CAP.
#
1 9/30/2019 ISSUE FOR PROGRESS SET REVIEW
2 10/25/2019 ISSUE FOR 50% CD REVIEW
3 11/26/2019 ISSUE FOR 95% CD REVIEW
4 12/03/2019 ISSUE FOR COORDINATED REVIEW
5 12/16/2019 ISSUE FOR CONSTRUCTION
CORNELLUNIVER S IT Y F O U NDED5681ADFACILITIESENGINEERINGARCHIVE BAR CODEITHACA, NEW YORKARCH/STRUCT:CIVIL/ENV:ELECTRICAL:MECHANICAL:DATE:FACILITY:DESIGN:DRAWN:WWW.FCS.CORNELL.EDUIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION.WARNINGREVISIONSARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING201 HUMPHREYS SERVICE BLDGITHACA, NEW YORK 14853-3701OLIN HALLOLIN HALL ROOM204 LABRENOVATIONE-00111982592GENERALNOTES ANDSYMBOLLEGENDSM. SCHOLENOMPS2024DECEMBER 16, 2019GENERAL ELECTRICAL NOTES1.0 ELECTRICAL SCHEMATICS INDICATED ON CONTRACT DOCUMENTS AREDIAGRAMMATIC. IT IS NOT THE INTENT TO SHOW EXACT OR MOST EFFICIENTROUTING. VERIFY ALL DIMENSIONS AND FIELD CONDITIONS ON SITE. ANYCONFLICTS BETWEEN CONSTRUCTION DOCUMENTS AND FIELD CONDITIONS SHALLBE BROUGHT TO CORNELL'S PROJECT MANAGER FOR RESOLUTION BEFORE WORKPROCEEDS.2.0 ASSURE PUBLIC AND WORKER SAFETY AT ALL TIMES. PROTECT ADJOINING AREASFROM DAMAGE AND DUST. REMOVE ALL DEBRIS FROM SITE AND DISPOSE OFWASTE MATERIAL IN A SAFE MANNER. KEEP THE PREMISES FREE OF DEBRIS FROMTHE EXECUTION OF WORK. DELIVER A FINAL PRODUCT THAT IS CLEAN ANDOPERABLE.3.0 FIRE STOP ELECTRICAL PENETRATIONS THROUGH FIRE RATED WALLS AND/ORFLOORS WITH MATERIAL EQUAL IN RATING TO THE CONSTRUCTION OF THEMATERIAL PENETRATED.4.0 WORK SHALL BE COMPLETED AS SPECIFIED AND INDICATED ON CONTRACTDOCUMENTS. ANY SUGGESTED ALTERNATE MANUFACTURER OR METHOD OFINSTALLATION SHALL BE SUBMITTED TO PROJECT ENGINEER FOR APPROVALPRIOR TO ORDERING ANY MATERIALS OR COMMENCING EXECUTION OF WORK.5.0 GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLE 250. PROVIDEEQUIPMENT GROUND CONDUCTOR WITH EACH BRANCH CIRCUIT INDICATED ONCONTRACT DOCUMENTS. EQUIPMENT GROUND CONDUCTOR SHALL BE ROUTEDWITH ASSOCIATED PHASE CONDUCTORS.6.0 PROVIDE A NEW TYPED PANELBOARD DIRECTORY FOR EACH PANELBOARD. LABELALL NEW DEVICE FACEPLATES WITH SOURCE AND CIRCUIT NUMBER. PROVIDEPERMANENT LABEL ON SWITCHING DEVICES INDICATING EQUIPMENT SERVICE ANDINVENTORY NUMBERS. COORDINATE EQUIPMENT INVENTORY NUMBERS WITHCORNELL UNIVERSITY'S MECHANICAL SHOP, 255-8667.7.0 CIRCUITS RATED 20-AMP, 120 VOLT SHALL CONTAIN SEPARATE NEUTRALCONDUCTORS.8.0 CONDUCTORS SHALL BE A MINIMUM OF 12AWG, STRANDED COPPER, 600VAC, 90DEGREE C, TYPE THHN/THWN-2 FOR DRY AREAS AND XHHW/THWN-2 FOR WETAREAS.9.0 CONDUITS SHALL BE A MINIMUM OF 3/4 INCHES DIAMETER. CONDUITS SHALL BEELECTRICAL METALLIC TUBING (EMT) AND SURFACE MOUNTED UNLESS NOTEDOTHERWISE.10.0 AIC RATING OF NEW CIRCUIT BREAKERS SHALL MATCH RATING OF RESPECTIVEPANELBOARD. SIZE AS INDICATED.11.0 PROVIDE PULL STRING THROUGH NEW CONDUIT AND BOXES. PROVIDE SUPPORTHANGERS FOR CONDUIT AS NEEDED.12.0 INSTALL RACEWAY SYSTEMS ENSURING PROPER ACCESS TO EQUIPMENT ANDDEVICES AND WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE ANDREPAIR. RACEWAYS THAT ARE NOT INSTALLED WITH THIS REQUIREMENT IN MINDSHALL BE RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIESARE CORRECTED.ELECTRICAL SCOPE OF WORK1.0 DEMO EXISTING ELECTRICAL OUTLETS AND CIRCUITRY THAT ARE NO LONGERNEEDED.2.0 PROVIDE DEDICATED ELECTRICAL CIRCUITS FOR THE PROPOSED NEW OWNERPROVIDED EQUIPMENT.3.0 PROVIDE EMERGENCY CIRCUIT TO OWNER PROVIDED UPS FOR NEW OWNERPROVIDED EQUIPMENT AS REQUIRED.ELECTRICAL LEGENDLIGHTING LEGENDMOTOR1'x4' LUMINAIREHARDWIRED EQUIPMENT CONNECTIONP-1A12HOMERUN TO PANEL P-1A, CIRCUIT #12. FED FROM 20A -1P BREAKER IS INTENDED UNLESS NOTED OTHERWISE. RUN GREEN WIRE GROUND FOR ALL CIRCUITS. PROVIDE ONE GROUND PER CIRCUIT.EMERGENCY POWER OFF (EPO)GROUND ROD ELECTRODEDUPLEX RECEPTACLE WITH GFCI PROTECTIONDUPLEX RECEPTACLE WITH AFCI PROTECTIONQUAD RECEPTACLELINETYPES LEGENDSIMPLEX RECEPTACLE: NEMA 5-20RPANELBOARDJUNCTION BOXB = INSTALLED IN BASEBOARDTR = INSTALLED IN WOOD TRIM/CASEWORK/WAINSCOTTSR = SURFACE RACEWAYWP = WEATHERPROOFAC = AIR CONDITIONERPP = POWER PENDANT OUTLET BOXDUPLEX RECEPTACLE: DOUBLE DUPLEX RECEPTACLEMOTOR STARTERJ2'x4' LUMINAIRECEILING MOUNTED LUMINAIREEM LIGHTING BATTERY UNITCOMBO EXIT SIGN/EM LIGHTING BATTERY UNITSINGLE FACE, WALL MOUNT EXIT SIGNDOUBLE FACE, WALL MOUNT EXIT SIGNSINGLE FACE, CEILING MOUNT EXIT SIGNDOUBLE FACE, CEILING MOUNT EXIT SIGNLIGHT SWITCH:SAFETY SWITCH (NON-FUSED)SAFETY SWITCH (FUSED)X3 = 3-WAY SWITCH4 = 4-WAY SWITCHD = DIMMER SWITCHO = WALL SWITCH OCCUPANCY SENSORV = WALL SWITCH VACANCY SENSORW = WIRELESS SWITCHS = WIRELESS SCENE SWITCHWIRELESS OCCUPANCY SENSORWIRELESS DAYLIGHT SENSOROSWDS1'x2' LUMINAIREFIRE ALARM LEGENDFIRE ALARM CONTROL PANELBATTERY CABINETWATER FLOW SWITCHMUXPADREMOTE ANNUNCIATORD = DUCT SMOKE DETECTORR = RELAY BASEBR = BEAM RECEIVERBT = BEAM TRANSMITTERSB = SOUNDER BASESMOKE DETECTOR: TAMPER SWITCHAUDIBLE NOTIFICATION APPLIANCEFACPBATTMUXFAANAC PANELNACMANUAL PULL STATIONFSXF = FIXED TEMPERATURER = RATE OF RISER/F = COMBINATION RISE/FIXED TEMPERATUREHEAT DETECTOR: HXCARBON MONOXIDE DETECTORCOAMFXXcdCFSFSXXcdCTSADDRESSABLE MODULEXXcd = CANDELAC = CEILINGCOMBO A/V NOTIFICATION APPLIANCE: XXcd = CANDELAC = CEILINGVISUAL NOTIFICATION APPLIANCE:SUPPRESSION SYSTEMELECTRICAL ABBREVIATIONSAC AIR CONDITIONERAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAFI ARC FAULT INTERRUPTERAMM ADDRESSABLE MONITOR MODULEAOM ADDRESSABLE OUTPUT MODULEARB AUXILIARY RELAY BOARDATS AUTOMATIC TRANSFER SWITCHB BASEBOARDBKR BREAKERC CONDUITCD CANDELACKT CIRCUITCR CONTROL RELAYEC ELECTRICAL CONTRACTOREMT ELECTRICAL METALLIC TUBINGEPO EMERGENCY POWER OFF STATIONFAA FIRE ALARM ANNUNCIATOR PANELFACP FIRE ALARM CONTROL PANELFSD FIRE SMOKE DAMPERGAA GENERATOR ALARM ANNUNCIATORGFI GROUND FAULT INTERRUPTERGND GROUNDHP HORSEPOWERKW KILOWATTLC LIGHTING CONTACTORLFMC LIQUID TIGHT FLEXIBLE METALLIC CONDUITLTG LIGHTINGMCB MAIN CIRCUIT BREAKERMLO MAIN LUG ONLYMTS MANUAL TRANSFER SWITCHNAC NOTIFICATION APPLIANCE CIRCUITNIC NOT IN CONTRACTOE OVERHEAD ELECTRICPC PHOTOCELLPM PLUGMOLDPP POWER PANELPPO PENDANT POWER OUTLETPVC POLYVINYL CHLORIDE CONDUITRGS RIGID GALVANIZED STEEL CONDUITSR SURFACE RACEWAYST SHUNT TRIPTM THERMAL MAGNETICTR TRIM/CASEWORK/WAINSCOTTTSP TWISTED SHIELDED PAIRTYP TYPICALUE UNDERGROUND ELECTRICUON UNLESS OTHERWISE NOTEDUPS UNINTERRUPTIBLE POWER SUPPLYV VOLTSVA VOLT AMPSWP WATERPROOFUNDERGROUND ELECTRICUEUNDERGROUND LIGHTINGULOVERHEAD ELECTRICOETO BE PROVIDEDDEMOLITION / TO BE RELOCATEDEXISTING TO REMAINUNDERGROUND TELCOUCMOUNTING HEIGHTSCARD READER 48" TOP OF BOXLIGHT SWITCH 48" TOP OF BOXRECEPTACLE 18" TOP OF BOXDATA OUTLET 18" TOP OF BOXTV OUTLET 84" TOP OF BOXPHONE OUTLET 48" TOP OF BOXSAFETY SWITCH 60" CENTERLINE OF HANDLEMOTOR STARTER 60" CENTERLINE OF HANDLEPANELBOARD 72" TOP OF PANELBOARDMANUAL PULL STATION 48" OPERABLE HANDLENOTIFICATION APPLIANCE 80" BOTTOM OF LENSDOOR HOLD OPEN COORDINATE IN FIELDEM BATTERY UNIT 96" BOTTOM OF UNITEM REMOTE UNIT 102" BOTTOM OF UNITEXIT SIGN 96" BOTTOM OF UNITLIGHT POLE WITH LED LUMINAIRES, REFER TO PLANS FOR NUMBER AND CONFIGURATION OFHEADSGENERAL ELECTRICAL DEMOLITION NOTES1.0 ELECTRICAL EQUIPMENT SHOWN DASHED ON DEMOLITION DRAWINGS, INCLUDINGASSOCIATED ANCHORS, SUPPORTS, STRAPS, BOXES, FITTINGS, AND OTHERAPPURTENANCES NOT SHOWN, SHALL BE DISCONNECTED AND REMOVED.REMOVE ASSOCIATED BRANCH CIRCUITRY TO SOURCE, UNLESS NOTEDOTHERWISE.2.0 EXISTING RACEWAYS AND DEVICE BACKBOXES NOT INTERFERRING WITH NEWWORK SHALL BE REUSED WHERE POSSIBLE.3.0 PROVIDE JUNCTION BOXES, RACEWAYS, AND WIRING TO MODIFY/EXTEND EXISTINGSYSTEMS AND CIRCUITS FED DOWNSTREAM OF ELECTRICAL EQUIPMENT SHOWNTO BE DEMOLISHED.4.0 CUT DEMOLISHED CONDUITS INSTALLED THRU WALLS AND FLOORS FLUSH WITHTHE SURFACE AND PATCH PENETRATIONS (FIRESTOP IF LOCATED ON A FIRERATED SURFACE). PATCH AND PAINT SURFACES IN EXPOSED AREAS TO MATCHSURROUNDING MATERIALS, FINISHES, AND COLORS.5.0 PROVIDE BLANK COVERPLATES ON UNUSED BACKBOXES REMAINING FROMDEMOLITION NOT SPECIFIED TO BE INFILLED.6.0 EXISTING EQUIPMENT SHOWN TO REMAIN SHALL BE PROTECTED DURINGCONSTRUCTION.SPECIAL RECEPTACLE: NEMA CONFIGURATION NEXT TO SYMBOL OR IN EQUIPMENT SCHEDULE5-30R1 9/30/2019 ISSUE FOR PROGRESS SET REVIEW2 10/25/2019 ISSUE FOR 50% CD REVIEW3 11/26/2019 ISSUE FOR 95% CD REVIEW4 12/03/2019 ISSUE FOR COORDINATED REVIEW5 12/16/2019 ISSUE FOR CONSTRUCTION
DNUP202204206206ALP2A11ELP2ASD2E-1012E-1013200CB208210212211209207205203201A2016FLEPP-2HELP-2HLP-2LPP-28204PPOPPOLP2A11111222231UNDER ELECTRIC PANEL1204-86° FREEZERWATER PURIFICATION SYSTEMPPOPPOELECTROPHORESIS SYSTEM4° FRIDGELP2A113PPO14E5a2E2aE9aE7aE4aE6aE1aE3a5INCUBATOR SHAKER CENTRIFUGE-20° FREEZER1E8aINCUBATOR 711E11aE10aOWNER PROVIDED MASS SPECOWNER PROVIDED NITROGEN GENERATOREMTEMTTO LEPP-2NEMA 6-15R FOR -86° FREEZERPOWER PENDANT OUTLET BOX WITH STRAIN RELIEF MOUNTED FROM EXISTING RACEWAY. CIRCUIT FROM 40A/2P CIRCUIT BREAKER IN PANEL LEPP-2. EXISTING CEILING MOUNTED RACEWAY CABLE/CORD GRIP STRAIN RELIEF CABLE/CORD GRIP STRAIN RELIEF NEMA 6-50R RECEPTACLE OWNER PROVIDED UPSOWNER PROVIDED FREEZERSURFACE RACEWAYEXISTING CEILINGNEMA 6-15P PLUG FOR FREEZERJUNCTION BOXCORNELLUNIVER S IT Y F O U NDED5681ADFACILITIESENGINEERINGNARCHIVE BAR CODEITHACA, NEW YORKARCH/STRUCT:CIVIL/ENV:ELECTRICAL:MECHANICAL:DATE:FACILITY:DESIGN:DRAWN:WWW.FCS.CORNELL.EDUIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION.WARNINGREVISIONSARCHITECTURAL, STRUCTURAL, CIVIL, ENVIRONMENTAL, MECHANICAL, AND ELECTRICAL ENGINEERING201 HUMPHREYS SERVICE BLDGITHACA, NEW YORK 14853-3701OLIN HALLOLIN HALL ROOM204 LABRENOVATIONE-10111982592RENOVATIONPLANSM. SCHOLENOMPS2024DECEMBER 16, 2019#E-101 KEYED DEMOLITION NOTES1 DISCONNECT AND REMOVE EXISTING OUTLET. REMOVE EXISTING CIRCUIT BACK TOSOURCE.2 EXISTING WALL MOUNTED STEEL RACEWAY SIMILAR TO WIREMOLD 3000 TOREMAIN. VERIFY IN FIELD.3 EXISTING CEILING MOUNTED STEEL RACEWAY SIMILAR TO WIREMOLD 4000 TOREMAIN. VERIFY IN FIELD.0 4 816SCALE: 1/8"=1'-0"SCALE:1/8" = 1'-0"12ND FLOOR PARTIAL FLOOR PLANSCALE:1/4" = 1'-0"2LAB 204 DEMOLITION PLANSCALE:1/4" = 1'-0"3LAB 204 RENOVATION PLANE-101 KEYED CONSTRUCTION NOTES1 PROVIDE DEDICATED NEMA RECEPTACLE IN EXISTING RACEWAY AND BRANCHCIRCUIT FROM EXISTING SPARE 20A/1P CIRCUIT BREAKER IN PANEL LP2A11. REFERTO EQUIPMENT SCHEDULE FOR NEMA RATING AND CIRCUIT INFORMATION.PROVIDE ¾” EMT CONDUIT FROM SURFACE RACEWAY TO ELECTRIC PANEL.2 PROVIDE 8/3 SOOW BLACK 90C, 40 AMP, 600V HEAVY DUTY RUBBER CABLE ANDPOWER PENDANT OUTLET BOX WITH NEMA 6-50R RECEPTACLE AND STRAIN RELIEFFOR NEW UPS. PROPERLY SIZE STRAIN RELIEF FOR CEILING RACEWAY ANDOUTLET BOX CONNECTION. CONNECT TO EMERGENCY BRANCH CIRCUIT FROMNEW 40A/2P CIRCUIT BREAKER IN EMERGENCY PANEL LEPP-2 IN EXISTING CEILINGMOUNTED RACEWAY. CIRCUIT WITH 2#8 AWG & 1#8 AWG GROUND CONDUCTORS IN¾” EMT CONDUIT. COORDINATE CORD LENGTH IN FIELD WITH EQUIPMENT ANDOWNER. RECEPTACLE COLOR SHALL BE RED.3 PROVIDE DEDICATED NEMA 6-15R RECEPTACLE FOR FREEZER IN SURFACEMOUNTED RACEWAY SIMILAR TO WIREMOLD 3000 SERIES STEEL RACEWAY.EXTEND TO ABOVE CEILING TO JUNCTION BOX FOR CONNECTION TO CIRCUIT FROMUPS. CIRCUIT WITH 2#12 AWG & 1#12 AWG GROUND CONDUCTORS. RUN CIRCUIT IN¾” EMT CONDUIT FROM RACEWAY JUNCTION BOX ABOVE CEILING OVER TOEXISTING CEILING MOUNTED SURFACE RACEWAY. RECEPTACLE COLOR SHALL BERED.4 PROVIDE 12/3 SOOW BLACK 90C, 20 AMP, 600V HEAVY DUTY RUBBER CABLE WITHNEMA 6-15P PLUG AND STRAIN RELIEF FOR FREEZER CIRCUIT. PROPERLY SIZESTRAIN RELIEF FOR CEILING RACEWAY CONNECTION. SPLICE SOOW CABLE TOFREEZER OUTLET CIRCUIT IN CEILING RACEWAY AND PLUG SOOW CABLE INTO NEWUPS NEMA 6-15R RECEPTACLE. COORDINATE CORD LENGTH IN FIELD WITHEQUIPMENT AND OWNER. PLUG COLOR SHALL BE RED.5 PROVIDE TWO (2) NEMA 5-20R DUPLEX RECEPTACLES IN EXISTING RACEWAYCIRCUITED FROM ONE EMERGENCY BRANCH CIRCUIT. CIRCUIT WITH 2#10 & 1#10AWG GND CU CONDUCTORS FROM EXISTING SPARE 20A/1P CIRCUIT BREAKER INPANEL LEPP-2. PROVIDE ¾” EMT CONDUIT FROM SURFACE RACEWAY TO ELECTRICPANEL. RECEPTACLE COLOR SHALL BE RED.6 PROVIDE 1-40A/2P CIRCUIT BREAKER FOR OWNER PROVIDED UPS. REMOVE 2EXISTING 1P SPARE CIRCUIT BREAKERS IN EXISTING PANEL TO MAKE ROOM FORNEW 2P CIRCUIT BREAKER. MATCH EXISTING PANEL TYPE AND AIC RATINGS.7 PROVIDE TWO (2) NEMA 5-20R DUPLEX RECEPTACLES IN EXISTING RACEWAYCIRCUITED FROM ONE BRANCH CIRCUIT. CIRCUIT WITH 2#12 & 1#12 AWG GND CUCONDUCTORS FROM EXISTING SPARE 20A/1P CIRCUIT BREAKER IN PANEL LP2A11.PROVIDE ¾” EMT CONDUIT FROM SURFACE RACEWAY TO ELECTRIC PANEL.8 PROVIDE 1 SPARE 1” EMT CONDUIT FROM PANEL LEPP-2 TO ABOVE CEILING IN LAB204 FOR FUTURE USE. PROVIDE PULL STRING IN EMPTY RACEWAY.0 2 4 8SCALE: 1/4"=1'-0"#EQUIPMENT ELECTRIC CONNECTION SCHEDULELABEL DESCRIPTION EQUIPMENT MANUFACTURERROOMNO.PANEL OCPRATING(kW, W,VA, A, HP)VOLTAGE PHASE WIRE & CONDUITRECEPTACLEQUANTITYNOTESNEMA RATINGE1a LC/MS LIQUID CHROMATOGRAPH MASS SPECTROMETER AGILENT 6500 SERIES 204 LEPP-2 - 2850 W 208 1 -6-15R 2 CONNECT TO UPSE2a NITROGEN GENERATORPEAK SCIENTIFIC NM32LA 204 LEPP-2 - 1265 W 110 1 -5-20R 1 CONNECT TO UPSE3a FREEZER (-86° C)EPPENDORF U410 204 LEPP-2 - 8 A 208 1 -6-15R 1 CONNECT TO UPSE4a UNDERCOUNTER -20°C FREEZER EXISTING 204 LP2A11 20A/1P 2.2 A 120 1 2#12&1#12GND IN 3/4" EMT 5-20R 1 DEDICATED CIRCUITE5a UNDERCOUNTER 4°C REFRIGERATOR EXISTING 204 LP2A11 20A/1P 2.2 A 120 1 2#12&1#12GND IN 3/4" EMT 5-20R 1 DEDICATED CIRCUITE6a ELECTROPHORESIS POWER SUPPLY BIO RAD POWERPAC BASIC 204 LP2A11 20A/1P 75 W 120 1 2#12&1#12GND IN 3/4" EMT 5-20R 1E7a INCUBATOR SHAKERINNOVA 42R 204 LP2A11 20A/1P 1800 W 120 1 2#12&1#12GND IN 3/4" EMT 5-20R 1 DEDICATED CIRCUITE8a INCUBATORTHERMOFISHER 3110 204 LP2A11 20A/1P 432 W 115 1 2#12&1#12GND IN 3/4" EMT 5-20R 2 PROVIDE ONE (1) DEDICATED CIRCUIT FOR 2 OUTLETSE9a CENTRIFUGEEPPENDORF 5910R 204 LP2A11 20A/1P 1650 W 120 1 2#12&1#12GND IN 3/4" EMT 5-20R 1 DEDICATED CIRCUITE10a MILLI Q WATER PURIFICATION SYSTEM EMD MILLIPORE 204 LP2A11 20A/1P - 115 1 2#12&1#12GND IN 3/4" EMT 5-20R GFCI 1 THIS CAN PLUG INTO EXISTING RECEPTACLEE11a UNINTERRUPTIBLE POWER SUPPLY POWERVAR 204 LEPP-2 40A/2P 6000VA 208 1 2#8 & 1#8 GND IN 3/4" EMT 6-50R 1 DEDICATED CIRCUITSCALE:NO SCALE4UPS - EMERGENCY CIRCUIT ELEVATION DETAIL1 9/30/2019 ISSUE FOR PROGRESS SET REVIEW2 10/25/2019 ISSUE FOR 50% CD REVIEW3 11/26/2019 ISSUE FOR 95% CD REVIEW4 12/03/2019 ISSUE FOR COORDINATED REVIEW5 12/16/2019 ISSUE FOR CONSTRUCTION