CORNELL – NCP SECURITY MANAGEMENT SYSTEM
STANDARD SPECIFICATIONS 28 07 10 – PAGE 1 OF 6
JUNE 29, 2012
SECTION 28 07 10
SECURITY MANAGEMENT SYSTEMS
PART 1 GENERAL
1.1 SUMMARY
A. This document includes a general description, functional requirements,
operational characteristics, and criteria for the Security Management
System (SMS).
1.2 REFERENCES
A. The Codes and Regulations listed below form a part of this specification to
the extent referenced. Work shall be performed in accordance with the
applicable international, federal, state, and local codes or standards
current at the commencement of installation. The following list
summarizes applicable standards:
1. UL 294, UL 1076, ULC
2. CE
3. FCC – Part 15, Part 68
4. NFPA 70, NEC
5. IEEE, RS 170 variable standard
6. IEEE, NTSC (color camera broadcast)
7. PAL (color camera broadcast, Europe)
8. CCIR (monochrome standard, Europe)
9. Microsoft® Open Database Connectivity (ODBC) interface)
10. ISO Software Coding Standards for C++ and C##
11. RoHS
B. Where more than one code or regulation is applicable, the more stringent
shall apply.
C. Cable installation, identification and termination shall be performed in
.addition to the applicable codes above.
ARCHITECHNOLOGY
CORNELL – NCP SECURITY MANAGEMENT SYSTEM
STANDARD SPECIFICATIONS 28 07 10 – PAGE 2 OF 6
JUNE 29, 2012
1.3 SECURITY MANAGEMENT SYSTEM DESCRIPTION
A. The Security Management System (SMS) outlined in this section and
detailed in Part 2 of this document is the key central component for
managing physical security and the bridge between physical and logical
security for this project. The system shall provide a variety of integral
functions including the ability to regulate access and egress; provide
identification credentials; monitor, track and interface alarms; and view,
record and store digital surveillance video linked to SMS events.
B. The SMS shall utilize a single seamlessly integrated relational database
for all functions utilizing a fully multitasking m ultithreading Microsoft
Windows 2000/2003 or Windows XP Operating System. The SMS shall be
written so that all modules (Access Control, Alarm Monitoring, ID /
Credential Management, Visitor Management, Asset Management and
Digital Video Management) are developed and built from a unified single
32bit source code set.
C. Upgrades or expansion of the SMS to a larger size system in scale shall
not require installation of a different and or new SMS application or require
the administrator/operator to learn a different and or new interface from
the previous version.
D. The SMS software shall be written to Microsoft's published standards for
User Interface Design, Secure Coding Practices and Database
Implementation Guidelines (Microsoft® Open Database Connectivity
(ODBC) interface).
E. The SMS software shall be written to ISO Standards on Software
Development for C++ and C##.
F. The SMS shall be able to seamlessly interface with and monitor intelligent
system controllers, reader interface modules, I/O panels, burglar alarm
panels, burglar alarm panel receivers, biometric devices, personal
protection devices, intercom systems, and digital video recorders
approved for use by the SMS manufacturer.
G. The SMS shall be able to communicate with intelligent system controllers
via RS485, RS232, TCPIP/Ethernet and Dialup via Modem.
H. All tasks shall be accessible from any compatible client workstation on the
network utilizing one or all of the following:
1. Traditional client server architecture
2. Ntier architecture where the SMS shall support the expansion of
the system architecture and allow for enduser depl oyment based
upon their system architectural needs. The SMS shall allow but not
ARCHITECHNOLOGY
CORNELL – NCP SECURITY MANAGEMENT SYSTEM
STANDARD SPECIFICATIONS 28 07 10 – PAGE 3 OF 6
JUNE 29, 2012
require the separation of the database, application server, web
server and client interface. The system shall require that all
connections to the database are performed through a trusted link
from the client or internet browser interface.
3. Centralized distribution (publishing) of applications using Windows
Terminal Server and Citrix on Windows, Unix, Linux or Apple
Macintosh based systems through any compatible internet browser
application and/or by means of a mobile computing platform using a
wearable computer, Tablet PC or PDA device.
1.4 QUALITY ASSURANCE
A. Manufacturer Qualifications
1. Manufacturer of the SMS shall be an established organization with
referenced and documented experience delivering and maintaining
Security Management Systems of equal or higher sophistication
and complexity as compared to the system detailed in this
specification.
2. SMS Manufacturer’s manufacturing facilities shall be certified ISO
9000:2000 operations, utilize ISO9000:2000 manufac turing
procedures and maintain their ISO certifications.
3. SMS Manufacturer shall employ at a minimum the following
methods for QA of component and assembly devices.
a) Visual inspection of devices shall be performed to verify
assembly according to defined procedures. End of line
operational tests shall be performed to ensure product
functionality has been correctly configured. A system burnin
period shall be utilized to screen for early life failures of
electronic components.
4. Individual functionality and system level regression testing shall be
performed to ensure compliance with product specifications. Single
and multiple unit system tests shall be performed to mimic enduser
installation configurations. Automated hardware and software
testing shall be utilized to evaluate system performance under
published operational loads and shall be compared to published
system capabilities.
B. Bidder Qualifications
1. At the time of the bid, the bidder shall have satisfactorily completed
projects similar size, scope and complexity as the system detailed
in this specification. The bidder shall furnish written proof of
ARCHITECHNOLOGY
CORNELL – NCP SECURITY MANAGEMENT SYSTEM
STANDARD SPECIFICATIONS 28 07 10 – PAGE 4 OF 6
JUNE 29, 2012
experience from three (3) references and proof of current
accreditation/certification by the manufacturer for required training
for sales/installation/service of the SMS and associated devices.
2. The bidder shall also be a factory authorized local service
organization that shall carry a complete stock of parts and provide
maintenance for the SMS and related systems under this contract.
Local shall be defined as an area in a 50 mile radius of installed
location.)
PART 2 PRODUCTS
2.1 MANUFACTURERS
A. SMS Hardware and Software
1. Design Make: Best Access (now Stanley) BASIS
2.2 SECURITY MANAGEMENT SYSTEM SERVER (EXISTING)
A. All card access components shall be compatible with the Universities
existing HeadEnd Database server. The existing ser ver supports Best
Access systems’ BASIS software.
2.3 SECURITY MANAGEMENT SYSTEM CLIENT WORKSTATION (EXISTING)
A. All card access components shall be compatible with the Universities
existing Client workstations. The existing workstations support Best
Access systems’ BASIS software.
2.4 SMS SOFTWARE CAPABILITIES
A. The SMS Software shall support an unlimited number of card readers,
input points, video cameras, door monitoring points, and relay outputs.
The SMS database server shall support an unlimited number of
cardholders, visitors, and assets limited only by the available memory on
the ISC. The database server shall also support an unlimited number of
system events and System Operator transactions in the history file limited
only by available hard disk space. Client Workstations shall be limited only
by the limitations of the operating system server software.
2.5 SMS SOFTWARE FUNCTIONALITY
A. Existing CIT SMS Client workstation to allow the following:
1. Local history review of CIT Card History.
2. Receipt of alarms located in the CIT area.
ARCHITECHNOLOGY
CORNELL – NCP SECURITY MANAGEMENT SYSTEM
STANDARD SPECIFICATIONS 28 07 10 – PAGE 5 OF 6
JUNE 29, 2012
PART 3 EXECUTION
3.1 SECURITY MANAGEMENT SYSTEM
A. Installation:
1. Install all equipment and materials in accordance with the
recommendations of the manufacturer.
B. Programming of the system shall include the following tasks:
1. Coordinate all system programming and configuration with the
facility’s security maintenance staff.
2. Programming system configuration parameters (hardware and
software, reader/circuit numbers, communication parameters).
3. Programming operational parameters such as the card holder
database, time zones, access levels and reader definitions.
4. Programming passcodes according to the authorities and functions
defined by the Owner.
5. Other system programming tasks required by the Owner. These
additional programming requirements shall be coordinated between
the Owner, security maintenance staff and the contractor.
C. Testing:
1. Operational Testing: The contractor shall perform thorough
operational testing and verify that all system components are fully
operational.
2. Hardcopy System Printout: The contractor shall submit a hard
copy system printout of all components tested and certify 100
percent operation indicating all devices/panels/units have passed
the test criteria set forth by the manufacturer.
3.2 COMMISSIONING
A. The contractor shall certify completion in writing and schedule the
commissioning walkthrough. The contractor shall p rovide all the tools
and personnel needed to conduct an efficient commissioning process.
3.3 WARRANTY
A. Provide a one year parts and labor warranty on all equipment and
software in this section.
ARCHITECHNOLOGY
CORNELL – NCP SECURITY MANAGEMENT SYSTEM
STANDARD SPECIFICATIONS 28 07 10 – PAGE 6 OF 6
JUNE 29, 2012
END OF SECTION
ARCHITECHNOLOGY
CORNELL – NCP ACCESS CONTROL
STANDARD SPECIFICATIONS 28 13 00 – PAGE 1 OF 10
JUNE 29,2012
SECTION 28 13 00
ACCESS CONTROL
PART 1 GENERAL
1.1 SUMMARY
A. This document includes a general description, functional requirements,
operational characteristics, and criteria for Card Access Equipment (CAE).
1.2 REFERENCES
A. The Codes and Regulations listed below form a part of this specification to
the extent referenced. Work shall be performed in accordance with the
applicable international, federal, state, and local codes or standards
current at the commencement of installation. The following list
summarizes applicable standards:
1. UL 294, UL 1076, ULC
2. CE
3. FCC – Part 15, Part 68
4. NFPA 70, NEC
5. Microsoft® Open Database Connectivity (ODBC) interface)
6. ISO Software Coding Standards for C++ and C##
7. RoHS
B. Where more than one code or regulation is applicable, the more stringent
shall apply.
1.3 SECURITY MANAGEMENT SYSTEM DESCRIPTION
A. The Security Management System (SMS) is outlined in section 28 07 10.
This section lists the equipment needed to obtain the card access
functionality of the SMS system.
1.4 QUALITY ASSURANCE
A. Manufacturer Qualifications
1. Manufacturer of the Card Access Equipment shall be an
established organization with referenced and documented
experience delivering and maintaining Security Management
ARCHITECHNOLOGY
CORNELL – NCP ACCESS CONTROL
STANDARD SPECIFICATIONS 28 13 00 – PAGE 2 OF 10
JUNE 29,2012
Systems of equal or higher sophistication and complexity as
compared to the system detailed in this specification.
2. CAE Manufacturer’s manufacturing facilities shall be certified ISOD
9000:2000 operations, utilize ISOD9000:2000 manufacturing
procedures and maintain their ISO certifications.
3. CAE Manufacturer shall employ at a minimum the following
methods for QA of component and assembly devices.
a) Visual inspection of devices shall be performed to verify
assembly according to defined procedures. End of line
operational tests shall be performed to ensure product
functionality has been correctly configured. A system burnDin
period shall be utilized to screen for early life failures of
electronic components.
4. Individual functionality and system level regression testing shall be
performed to ensure compliance with product specifications. Single
and multiple unit system tests shall be performed to mimic endDuser
installation configurations. Automated hardware and software
testing shall be utilized to evaluate system performance under
published operational loads and shall be compared to published
system capabilities.
B. Bidder Qualifications (Stanley Security Systems currently maintains the
existing card access systems for CIT)
1. At the time of the bid, the bidder shall have satisfactorily completed
projects similar size, scope and complexity as the system detailed
in this specification. The bidder shall furnish written proof of
experience from three (3) references and proof of current
accreditation/certification by the manufacturer for required training
for sales/installation/service of the SMS and associated devices.
2. The bidder shall also be a factory authorized local service
organization that shall carry a complete stock of parts and provide
maintenance for the SMS and related systems under this contract.
Local shall be defined as an area in a (**X) mile radius of installed
location.)
PART 2 PRODUCTS
2.1 MANUFACTURERS
A. SMS Field Hardware:
ARCHITECHNOLOGY
CORNELL – NCP ACCESS CONTROL
STANDARD SPECIFICATIONS 28 13 00 – PAGE 3 OF 10
JUNE 29,2012
1. Best Access
B. Card Readers
1. HID
2.2 INTELLIGENT SYSTEM CONTROLLER (ISC)
A. The Intelligent System Controller (ISC) shall link the SMS Software to all
“downDstream” field hardware components (Reader Interface Modules,
Input Control Modules and Output Control Modules). The ISC shall
provide full distributed processing of access control / Alarm Monitoring
rules and operations. A fully loaded and configured ISC with shall respond
in less than oneDhalf (0.5) second to grant or deny access to cardholder.
B. The ISC shall continue to function normally (standDalone) in the event that
it loses communication with the SMS software. While in this offDline state,
the ISC shall make access granted/denied decisions and maintain a log of
the events that have occurred. Events shall be stored in local memory,
and then uploaded automatically to the SMS database after
communication has been restored.
C. In addition, the ISC shall incorporate the following features:
1. UL 294, ULC, and CE Certified
2. Support for Host Communications Speed of 38,400 bps
3. Support for Direct Connect, Remote Dial Up, or Local Area Network
(LAN) Connection
4. Support for up to .5 MB of OnDBoard Memory
5. LAN Support shall utilize RJ45 (10/100baseT) Ethernet Interface or
Token Ring 4 MB connectivity
6. Flash Memory for real time program updates and overall host
communications
7. Support for four 2 wire downstream ports, two 4 wire downstream
ports, or combination one 4 wire downstream port and two 2 wire
downstream ports. Downstream ports shall be for connecting card
readers and data gathering and output control panels via RSD485
multiDdrop wiring configuration
8. Memory storage of up to 12,500 cardholders with 4 MB memory
expansion.
ARCHITECHNOLOGY
CORNELL – NCP ACCESS CONTROL
STANDARD SPECIFICATIONS 28 13 00 – PAGE 4 OF 10
JUNE 29,2012
9. Initial base memory download between ISC with standard memory
from the SMS shall require no more than ten (10) seconds
10. Support for up to 16 devices consisting of RIMs, ICMs, and OCMs
in any combination desired with a maximum of 8 I/OCM devices per
ISC
11. Support of multiple card technologies
12. Supervised Communications between ISC and SMS Software
13. AES 128 bit Symmetrical Block Encryption conforming to the FIPSD
197 standard between ISC and SMS Software communications
driver.
14. Multi – drop support for up to eight ISCs per SMS communications
port
15. Support of up to eight card formats and facility codes
16. Support for SEIWG card formats
17. RSD485 Full Duplex, UL 1076 Grade AA communication channel to
the SMS headDend
18. Integration to other manufacturer’s card readers
19. Uninterruptible Power Supply (UPS) with battery backup for 2 hours
20. 32Dbit Microprocessor
21. Biometric Interface Support
22. An ISC downstream serial port shall multiDdrop 16 access control
field hardware devices using an RSD485 UL 1076 Grade A
communication format allowing a distance of 4,000 feet using
Belden 9842 cable or equivalent
23. 12 VAC or 12 VDC input power
24. Issue Code Support for both Magnetic and Wiegand Card Formats
25. Individual Shunt Times (ADA Requirement)
26. Up to Nine Digit PIN Codes
27. Downstream serial RSD232 device support
28. Status LEDs for normal component and communication status
ARCHITECHNOLOGY
CORNELL – NCP ACCESS CONTROL
STANDARD SPECIFICATIONS 28 13 00 – PAGE 5 OF 10
JUNE 29,2012
29. RoHS Compliance
30. Support for RSD485 over CAT 5, 6e cable
2.3 INPUT CONTROL MODULE (ICM)
A. The Input Control Module shall provide 16 UL 1076 Grade B, A or AA
alarm input zones and monitor / report line fault conditions, alarm
conditions, power faults and tampers. Status LEDs shall provide
information about the sixteen alarm zone inputs, cabinet tamper, and
power fault.
B. In addition, the ICM shall incorporate the following features:
1. UL 294, ULC, and CE Certified
2. Alarm contact status scanning at up to 180 times per second for
each zone
3. Eight configuration DIP switches to assign unit addresses and
communications speed
4. Elevator control support for 128 floors
5. Variable resistor values for line supervision
6. A low power CMOS microprocessor
7. Filtered data for noise rejection to prevent false alarms
8. Up to 16 Grade B, A, or AA Supervised Inputs in any Combination
9. 12 or 24 VDC Input Power
10. 2 Form C 5A, 30 VDC Contacts for load switching
11. 2 dedicated inputs for tamper and power status
12. RoHS Compliance
13. Support for RSD485 over CAT 5, 6e cable
2.4 OUTPUT CONTROL MODULE (OCM)
A. The Output Control Modules shall provide 16 FormDC 5A 30 VDC relay
contacts for load switching. The relays shall be configurable for failDsafe or
failDsecure operation. Each relay shall support “On” “Off” and “Pulse”
1. 12 or 24 VDC input power
ARCHITECHNOLOGY
CORNELL – NCP ACCESS CONTROL
STANDARD SPECIFICATIONS 28 13 00 – PAGE 6 OF 10
JUNE 29,2012
2. Two dedicated digital inputs for tamper and power failure status
3. RSD485 communications, multiDdropped (2Dwire or 4Dwire RSD485)
4. Up to 16 OCMs per Intelligent System Controller
5. Onboard termination jumpers
6. DIP switch selectable addressing
7. Status LEDs for communication to the host, heartbeat and relay
status
8. Elevator control, support for 64 floors
9. RoHS Compliance
10. Support for RSD485 over CAT 5, 6e cable
2.5 SINGLE READER INTERFACE MODULE (SRI)
A. The SRI shall provide an interface between the ISC and authentication
devices. The SRI must operate with any authentication device that
produces a standard Wiegand, Data 1 / Data 0) or Clock and Data
communication output.
B. In addition the SRI shall incorporate the following features:
1. 12 or 24 VDC power supply
2. Reader communications (Clock/Data or Wiegand Data1/Data0) D
more than 150 different readers approved for use
3. Two FormDC relay outputs (5 A Door Strike and 1 A Aux relays)
4. Up to 16 different card formats (8 card and 8 asset)
5. Issue code support for Magnetic and Wiegand formats
6. Door contact Open or Closed, Supervised or NonDsupervised
7. REX pushDbutton monitor D Supervised or NonDsupervised
8. Strike Control output
9. Dedicated tamper and power failure circuits
10. Bicolor or two wire status LED support
ARCHITECHNOLOGY
CORNELL – NCP ACCESS CONTROL
STANDARD SPECIFICATIONS 28 13 00 – PAGE 7 OF 10
JUNE 29,2012
11. Beeper control
12. Support for offline reader access mode
13. Elevator control, support for 64 floors
14. UL 294 listed and CE approved
15. RoHS Compliance
16. Support for RSD485 over CAT 5, 6e cable
2.6 DUAL READER INTERFACE MODULE (DRI)
A. The DRI shall provide a dual interface between the ISC and authentication
devices. The DRI must operate with any authentication device that
produces a standard Wiegand (Data 1 / Data 0 or Clock and Data)
communication output.
B. In addition the DRI shall incorporate the following features:
1. 12 or 24 VDC power supply
2. Reader communications (Clock/Data or Wiegand Data1/Data0) D
more than 150 different readers approved for use
3. Six FormDC 5 A at 30 VDC relay outputs
4. Up to 16 different formats (8 card and 8 asset)
5. Issue code support for Magnetic and Wiegand formats
6. Door contact supervision (Open/Closed)
7. REX pushDbutton monitor
8. Strike Control output
9. BiDcolor status LED support and 2Dwire LED support
10. Beeper control
11. Dedicated tamper and power failure circuits
12. Support for offline reader access mode
13. Onboard jumpers for termination
14. Onboard jumpers for 5 VDC or 12 VDC reader support
ARCHITECHNOLOGY
CORNELL – NCP ACCESS CONTROL
STANDARD SPECIFICATIONS 28 13 00 – PAGE 8 OF 10
JUNE 29,2012
15. Elevator control, native support for 6 floors
16. DIP switch selectable addressing
17. UL 294 listed and CE approved
18. RoHS Compliance
19. Support for RSD485 over CAT 5, 6e cable
2.7 CARDS
A. The system will be operated with the University’s’ existing HID compatible
proximity cards.
2.8 CARD READER LOCK (CRL)
A. HID compatible 125Khz proximity reader
B. Compatible with cards, reader interface module and SMS software
C. Green/red – valid/void leds
D. Mortise lock
E. New Locks shall be Seargent Lever (LL)
F. Locks shall be storeroom locks (04)
G. Shall accommodate Best small format 7 pin interchangeable core prefix 70
for Best.
H. Locks shall be fail secure
I. Tamper resistant mounting
J. Integral request to exit door position switch and solenoid controlled lock
K. Read range 6”
L. Shall be installed by a Harmony certified installer
M. Sargent Harmony series
2.9 DOOR CONTACTS (DC)
A. Integral to CRL on new doors
B. Flush mount
ARCHITECHNOLOGY
CORNELL – NCP ACCESS CONTROL
STANDARD SPECIFICATIONS 28 13 00 – PAGE 9 OF 10
JUNE 29,2012
C. Form c contact
D. Magnetic strength suitable for metal doors and frames.
E. Door Contacts shall be Sentrol 1078
2.10 MORTISE MOUNT ELECTRONIC EPT (NEW DOORS)
A. Used for flush mount wired connections to the Card Reader Lock on new
doors.
B. 12 conducter #22 awg with Electrolinx connectors.
C. Magnetic strength suitable for metal doors and frames.
D. Design Make: Securitron ELDCEPT Power Transfer
2.11 SURFACE MOUNT ELECTRONIC EPT (EXISTING DOORS)
A. Used for surface mount wired connections to the Card Reader Lock on
existing doors.
B. Use preDterminated quick connect (McKinney ElectroLynx) plugDandDplay
kit with 15’ of cable
Specify Keedex part #: KDDL38A24 door to frame power transfer flex
conduit with box at each end. Cut connectors off one end of ElectroLynx
cable, fish raw cable end from the lock to the ceiling space and leave coil
for Stanley Technician to connect to power.
PART 3 EXECUTION
3.1 SECURITY MANAGEMENT SYSTEM
A. Installation:
1. Install all equipment and materials in accordance with the
recommendations of the manufacturer.
2. Provide all wiring as required by the manufacturer. Provide plenum
rated cable as required.
B. Programming of the system shall include the following tasks:
1. Coordinate all system programming and configuration with the
facility’s security maintenance staff.
2. Programming system configuration parameters (hardware and
software, reader/circuit numbers, communication parameters).
ARCHITECHNOLOGY
CORNELL – NCP ACCESS CONTROL
STANDARD SPECIFICATIONS 28 13 00 – PAGE 10 OF 10
JUNE 29,2012
3. Programming operational parameters such as the card holder
database, time zones, access levels and reader definitions.
4. Programming passcodes according to the authorities and functions
defined by the Owner.
5. Other system programming tasks required by the Owner. These
additional programming requirements shall be coordinated between
the Owner, security maintenance staff and the contractor.
C. Testing:
1. Operational Testing: The contractor shall perform thorough
operational testing and verify that all system components re fully
operational.
2. HardDcopy System Printout: The contractor shall submit a hardD
copy system printout of all components tested and certify 100
percent operation indicating all devices/panels/units have passed
the test criteria set forth by the manufacturer.
3.2 CARD READER
A. Install card readers in locations shown on plans. Install readers past the
swing of the door.
B. Provide surface mount back boxes only where needed. Where possible
provide flush mount back boxes that can be covered by the card reader.
When needed the door jam or a hallow wall can be used as the junction
point for the card reader connections.
3.3 COMMISSIONING
A. The contractor shall certify completion in writing and schedule the
commissioning walkDthrough. The contractor shall provide all the tools
and personnel needed to conduct an efficient commissioning process.
3.4 WARRANTY
A. Provide a 1 year parts and labor warranty for all equipment and software
provided in this section.
END OF SECTION
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-07841302
CONCRETE FLOOR FIRESTOP
PENETRATION DETAIL
(CONDUIT SLEEVE)
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-07841303
CONCRETE FLOOR FIRESTOP
PENETRATION DETAIL
(CONTINUOUS CONDUIT)
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052801
WIRE MESH CABLE TRAY -
CEILING MOUNT
INSTALLATION
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052802
CABLE TRAY - WALL
PENETRATION
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052803
WIRE MESH CABLE TRAY -
SECODARY CONDUIT
INSTALLATION
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052804
WIRE MESH CABLE TRAY -
BACKBONE CONDUIT
INSTALLATION
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052805
TYPICAL PRIMARY/BACKBONE
PATHWAY PULLBOX
INSTALLATION DETAIL
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052806
PULLBOX PB-M AND PB-L
MOUNTING DETAIL FOR
INACCESSIBLE CEILINGS
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052807
CABLE TRAY TO BOX / FLOOR
CONNECTOR FOR A TR
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052808
FULLY ENCLOSED CABLE TRAY
CONNECTION DETAIL
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052809
CONDUIT TO FULLY
ENCLOSED CABLE TRAY
CONNECTION DETAIL
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052810
MISC. FULLY ENCLOSED
CABLE TRAY / RUNWAY ENDS
DETAIL
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052811
4" CONDUIT TO FULLY
ENCLOSED CABLE TRAY
CONNECTION DETAIL
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052812
CONDUIT TO FULLY
ENCLOSED CABLE TRAY
CONNECTION DETAIL
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052813
4" CONDUIT TO FULLY
ENCLOSED CABLE TRAY
CONNECTION DETAIL
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052814
4" CONDUIT TO FULLY
ENCLOSED CABLE TRAY
CONNECTION DETAIL
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052815
VERTICAL TO HORIZONTAL
FULLY ENCLOSED CABLE TRAY
DETAIL
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052816
FW,JT - FISH WALL, J-HOOK
TO CABLE TRAY
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052817
SH,JT - SURFACE RACEWAY
TO HALLWAY, J-HOOK TO
CABLE TRAY
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052818
SC,CP - SURFACE RACEWAY
TO CEILING, CONDUIT TO
PULLBOX
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052820
SC,CP - SURFACE RACEWAY
TO CEILING, CONDUIT TO
PULLBOX
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052821
SH,CP - SURFACE RACEWAY
TO HALLWAY, CONDUIT TO
PULLBOX
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052822
SH - SURFACE RACEWAY TO
HALLWAY
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052822
SH - SURFACE RACEWAY TO
HALLWAY
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052824
SC - SURFACE RACEWAY TO
HALLWAY DETAIL
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052825
SH - SURFACE RACEWAY TO
HALLWAY DETAIL
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052826
TYPICAL SR-2 SURFACE
RACEWAY INSTALLATION
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052827
TYPICAL ETR SR-4D DIVIDED
SURFACE RACEWAY OUTLET
INSTALLATION
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052828
TYPICAL ETR SR-4D DIVIDED
SURFACE RACEWAY OUTLET
INSTALLATION
:(;7(16,21
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052829
TYPICAL ETR SR-3 SURFACE
RACEWAY OUTLET
INSTLLATION
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052830
TYPICAL SURFACE RACEWAY
BRIDGE INSTALLATION
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052831
TYPICAL RECESSED OR
SURFACE MOUNTED CONDUIT
INSTALLATION
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052832
TYPICAL HORIZONTAL
CONDUIT/JUNCTION BOX
INSTALLATION
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052833
TYPICAL SURFACE CONDUIT
INSTALLATION
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052834
TYPICAL SURFACE CONDUIT
INSTALLATION
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052835
TYPICAL RECESSED BACKBOX
/ CONDUIT DETAILS
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052836
RECESSED CONDUIT VIA (2)
0.75" FLEX CONDUITS DETAIL
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052837
COMMUNICATIONS POWER
POLE DETAIL
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052839
TYPICAL WAP INSTALLATION
(OPEN CEILING)
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052840
WIRELESS CEILING
ENCLOSURE DETAIL
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052842
TYPICAL WAP INSTALLATION
(WALL MOUNT)
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052845
TYPICAL WALL MOUNTED
TELEPHONE OUTLET
INSTALLATION (SR-2 OR
RECESSED CONDUIT)
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052846
TYPICAL WALL MOUNTED
TELEPHONE OUTLET - NEW
WORK RECESSED
INSTALLATION
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052847
TYPICAL ELEVATOR / ENERGY
MANAGEMENT CONNECTION
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052849
CABLE TRAY - EZ-PATH
INSTALLATION
AT STANDARD DETAILS
Fax: 585.424.4239
115 METRO PARK ROCHESTER, NY 14623
www.archi-technology.com
PHONE: 585.424.1952
ISSUE DATE:
PROJECT MANAGER:
DRAWN BY:
CHECKED BY:
AT-27052850
FW (FISH WALL) OUTLET
INSTALLATION
AT STANDARD DETAILS