Loading...
HomeMy WebLinkAbout27 05 00 - Basic Communications RequirementsARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 1 OF 24 JUNE 29, 2012 SECTION 27 05 00 BASIC ELECTRICAL/COMMUNICATION REQUIREMENTS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. All drawings and general provisions of Contract, including all General Conditions, Division 1 Specification Sections, and Instructions to Bidders apply to this section. B. Section 02 41 19 Selective Demolition applies, in its entirety, to this Division. It relates to demolition of abandoned voice and data cable plant, station cabling, backbone copper cables, backbone optical fiber cabling, terminal blocks, terminal enclosures, splice cases, plywood backboards, raceways, boxes etc. It relates to removal of all active cable plant that will be replaced, decommissioned and removed under this contract. It also relates to general disposal, recycling and materials to be salvaged, as called for. C. Section 09 91 23 Paints and Coatings applies to this Division, as it relates to touch up or repainting of any finished equipment, raceway, wall surface, ceiling surfaces, ceiling access panels, etc. that is opened, channeled or damaged during construction as it applies to the item being brought to “as new” condition. 1.2 SCOPE OF WORK A. Include in bid all labor, allowances, materials, tools, plant, transportation, training, equipment, insurance, temporary protection, permits, demolition, disposal, permits and fees, taxes and all necessary and related items required to provide complete and operational systems shown and described. B. The contractor shall provide with their bid a complete breakdown of materials and unit pricing for all products included in their bid. C. Include in bid all labor, allowances, transportation, sorting and separation of recycled materials, disposal, insurance, protection of furniture and furnishings, permits, fees, utility company fees, taxes and all necessary and related items. D. Cornell University requires recycling to the largest extent possible for items being removed, including but not limited to, all backbone and station copper cables, termination blocks, termination patch panels, metallic components such as cable managers, raceways, etc. ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 2 OF 24 JUNE 29, 2012 E. Minimum composition requirements and/or installation methods for the following materials and work are included in this section: 1. Miscellaneous Supports 2. Access Doors and Panels 3. Fire Stopping 4. Flashing and Sealing 5. Cutting and Patching 6. Fire Stop 7. General cable requirements 8. Removals of abandoned cable and termination equipment 9. University Services 10. Temporary Facilities 11. Cleaning 12. Existing Systems 13. Continuity of Services 14. Submittals 15. Workmanship and Warranty 16. Operation and Maintenance Manuals 17. Record Documents 1.3 SCOPE AND COORDINATION A. The job foremen for each division of work shall meet and plan the removals and new installations prior to reviewing with the owner’s representative. This shall include all requirements for Divisions 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, 23, 26,27 and 28 contract requirements. At project start?up, special attention is required for coordination and sequencing for removal of existing abandoned and in?use cable to create sufficient spare capacity in existing pathways for reuse and the logistics of extending new conduit and pathways to alternate floors to extend existing pathways and relocate Category 6 cable to alternate floors. Maintain existing voice and data ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 3 OF 24 JUNE 29, 2012 services at all times as directed. Maintain other systems as called for on the T2?Series drawings. B. Before construction work commences, the Contractor shall coordinate exact conduit and penetration requirements, slotting/patching of walls to install new concealed conduits and backboxes for flush faceplates, conduit and raceway removals methods, pathway routing and installation methods, mounting requirements for UTP faceplates, locations of new access panels, modifications of existing gypsum ceilings for installation of new access panels, dumpster positioning and fire truck and delivery access, etc. with the Owner’s Project Manager. Additionally, the Contractor shall coordinate exact storage, staging, recycling, and disposal requirements with the Project Manager. C. The Contractor shall provide the following 1. Removal of abandoned or decommissioned voice, data, horizontal and backbone cables. 2. Sorting and storage of cabling and metallic components intended for recycling. 3. Removal of patch panels in select existing racks and cabinets. 4. Removal, relocation, reuse of select ARMM backbone cables and splicing per Drawing T1?CL copper logical riser diagrams. 5. Removal of existing CIT owned optical fiber risers within buildings, per Drawing T1?FL fiber logical riser diagrams. 6. Removal of plywood backboards, plywood enclosures, cable straps, anchors, drive rings, termination blocks, surface raceways, conduit, and hardware, distribution rings, etc, typically in the old IDF/BDF closets. 7. Subcontracting of furniture and furnishings movers to allow access work locations for station cable removals, new horizontal cable placement and testing, and cutover activities. 8. Dust, dirt and water protection of furniture, walls, floors, carpets, furnishings from damage, during demolition, new construction and new cutover provisioning. Dust protection of smoke detectors. 9. Fire stopping and sealing of the insides of existing/new conduits, existing/new sleeves, holes, wall cavities and raceways for all cables removed under this contract. ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 4 OF 24 JUNE 29, 2012 10. Patching and painting of floors, walls, soffits and ceilings upon removal of all exposed wiring in offices, conference rooms, labs, corridors, chase ways, etc. for cables removed under this contract. 11. Fire stopping and patching of the insides of conduits, sleeves, raceways and wall cavities for all new vertical and horizontal pathways installed for new cabling, including all empty or spare facilities. 12. Modular jacks, machine printed labels, mounting screws, cable wrap?around labels, etc. 13. Final closing of all raceways, pull boxes, ceiling access panels after cable testing and repair work is complete. 14. Coordination of deliveries, dumpster/staging logistics and fire lane access. 15. Coordination of the new grounding riser system by the electrical contractor. Bonding equipment connections for racks, cable runways, cable sheaths, lightning protection, cable trays, primary conduit systems, backbone copper cable sheaths, and all other metallic components in the TR rooms. 16. Temporary service provisioning and shutdown coordination, as may be required for reuse of existing pathways (conduits, pullboxes and recess backboxes, etc) to provide sufficient space to install new Category 6 cabling while maintaining parallel service as directed by Owner. 17. Select removal of inactive cabling and faceplates, shutdown coordination, as may be required for reuse of existing pathways (conduits, pullboxes and recess backboxes, etc) to provide sufficient space to install new Category 6 cabling while maintaining parallel service as directed by Owner. 18. Temporary service provisioning and shutdown coordination, as may be required, for this building and the adjacent buildings affected by this work. 19. Temporary service provisioning and shutdown coordination, as may be required for reuse of existing conduits, cable ladders and IDF conduit/sleeves, affected by this work. 20. Temporary service provisioning and shutdown coordination, as may be required, for reuse of any existing conduit stub?ups and backboxes. ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 5 OF 24 JUNE 29, 2012 21. Temporary service provisioning and shutdown coordination, as may be required. This will be required for areas where existing raceway is intended to be reused. 22. Permits, inspections and associated fees. 23. Parking permits, identification badges and all associated fees. 24. Testing, labeling and Documentation of all voice, video, audio and data cables. 25. Relocation of racks, panels, wall mounted blocks, plywood panels and existing optical fiber and backbones copper cables to allow for reconfiguration of the BDF and IDF rooms and provisioning of new backbone pathways and new backbone cabling in existing IDF closets. D. The Contractor shall also provide the following 1. Category 6&6A Cable 2. Category 6&6A modular jacks 3. UTP faceplates 4. UTP faceplates, special waterproof (raintight) and in?use faceplate covers. 5. UTP Category 6 patch panels 6. Category 6 Permanent Link testing of unpatched links. 7. High pair count ARMM, 24 AWG, telephone riser cables with corrugated aluminum shield. High pair count cable splicing as called for in T1?CL riser diagram and section 27 13 00. 8. Innerduct and optical fiber cables and terminations as called for in T1?FL riser diagram and section 27 13 00.Optical fiber rack mount patch panels as indicated on the T3 drawings 9. Field installable optical connectors, bulkhead adapter packs 10. 19” Equipment Racks as indicated on the T3 drawings, for Telecommunication Rooms. 11. Cable Runways for Telecommunication rooms, as indicated on the T3 drawings. ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 6 OF 24 JUNE 29, 2012 12. 110 Voice termination blocks for riser cables and rack interconnect cables as indicated on the T3 drawings 13. Distribution rings and 188B brackets as indicated on the T3 drawings 14. Vertical and Horizontal Cable Managers for new Telecommunication rooms, as indicated on the T3 drawings 15. Misc. hardware, screws, anchors, straps, beam clamps, all?thread, nuts, washers, fabrications, etc. 16. Hook and Loop wraps for UTP cables support and dressing in TRs and inside of cable trays and large raceways. 17. Ty?wraps (where permitted, such as backbone copper cable binder groups, splice cases, etc.). 18. Firestop, fire stop pillows and patching compounds 19. Patching and painting as required, by an approved subcontractor. 20. Machine printed labels for faceplates, racks, cabinets, cables, etc. 21. Bonding, strapping, wire, cable, lugs and screws as indicated on the T3 drawings 22. Adapter brackets, radius fittings and mounting hardware for raceways, cable trays, cable runways, power poles, and modular furniture as required. 23. Permits and inspection applications and related fees. 24. Cleaning and polishing consumables for optical fibers. 25. Jet?line, pull?line, pull rope, winch rope, and measuring tape for wall?to?wall backbone conduit measurements. 26. Cable lubricants and cleaners 27. Splicing connectors, shield bond connectors, vinyl/rubber/friction tapes, encapsulant gels, grounding braid, d?Gel cleaners, test equipment and testing adapters, etc. for copper backbone cable splicing and termination, and testing. 28. Shield bond connectors, vinyl/rubber/friction tapes, encapsulant gels, break?out kits, furcation tubing, grounding braid, alcohol wipes, compressed air, polishing paper/pucks, d?Gell cleaners, ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 7 OF 24 JUNE 29, 2012 testing patch cords and adapters required for testing, etc for fiber backbone cable preparation and termination and testing. 29. Daily cleaning of TR Rooms and office and labs as called for. 30. Coordination of work and compliance with safety requirements for laboratories, animal facilities, bio?safety spaces, animal hospital operating rooms, and confined space per EH&S and OSHA standards. 1.4 REGULATIONS AND CODE COMPLIANCE A. All work and materials shall conform to and be installed, inspected and tested in accordance with the governing rules and regulations of federal, state and local governmental agencies. B. Reference to regulations, codes and standards means the latest edition, amendment and revisions to the regulations, codes and standards in effect on the date of the Contract Documents. C. The following is a list of codes and standards that will apply to this project. 1. New York State Building Code. 2. New York State Energy Conservation Construction Code. 3. New York State Department of Labor Rules and Regulations. 4. New York State Department of Health. 5. Federal Occupational Safety and Health Administration ? OSHA. 6. National Life Safety Code, NFPA 101. 7. National Electrical Code, NFPA 70. 8. Local Codes and Ordinances for the City and or Town of Ithaca. 9. NEMA Standards 10. Underwriters Laboratory (UL) 11. Factory Mutual and/or Owner’s Insurance Carrier 12. International Standards Organization (ISO) 13. New York State Education Department ? “Manual of Planning Standards” ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 8 OF 24 JUNE 29, 2012 14. ANSI/TIA/EIA ? Building Telecommunications Standards 15. BICSI Telecommunications Distribution Methods Manual 16. National Electrical Contractor Association Standards 17. National Electrical Installation Standards (NECA?NEIS) 18. Cable Tray Institute 19. TIA/EIA ? Telecommunications Standards 20. Federal Communications Commission 21. IEEE Standards, including C?2 – National Electrical Safety Code 22. Internet Engineering Task Force RFCs 23. Federal Communications Commission 24. Cornell University Design and Construction Standards, Current Edition. 25. Cornell University Environmental Health and Safety Standards. 26. NYS Public Service Commission 27. American with Disabilities Act 1.5 GLOSSARY ADA Americans with Disabilities Act AIA American Institute of Architects ANSI American National Standards Institute ASTM American Society for Testing Materials BDF Building Distribution Frame BICSI Building Industry Consulting Services International CIT Cornell’s Information Technologies Department COAM CIT Owned and Maintained Equipment DOAM Department Owned and Maintained Equipment CU Cornell University EHS Cornell’s Environmental Health and Safety Department EIA Electronic Industries Association ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 9 OF 24 JUNE 29, 2012 ELFEXT Equal Level far end cross talk FCC Federal Communications Commission FEXT Far end cross talk FM Factory Mutual Insurance Company FPC Fire Protection Contractor IEEE Institute of Electrical and Electronics Engineers IETF Internet Engineering Task Force IRI Industrial Risk Insurers ISO International Standards Organization MDF Main Distribution Frame NEC National Electrical Code NEMA National Electrical Manufacturers’ Association NECA National Electrical Contractor Association NESC National Electrical Safety Code NFPA National Fire Protection Association NEXT Near end Cross Talk NYBFU New York board of Fire Underwriters NYS/DEC New York State Department of Environmental Conservation NYS/UFBC New York State Uniform Fire Prevention and Building Code OSHA Occupational Safety and Health Administration PBX Private Branch Exchange Telephone Switches PDC Cornell’s Planning Design and Construction Department PSELFEXT Power sum equal level far end cross talk TGB Telecommunications Grounding Bus Bar TIA Telecommunications Industry Association TR Telecommunications Room UFPO Underground Facilities Protective Organization UL Underwriter’s Laboratories, Inc. 1.6 DEFINITIONS Approved / Approval Written permission to use a material or system. ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 10 OF 24 JUNE 29, 2012 As Called For Materials, equipment including the execution specified/shown in the contract documents. Code Requirements Minimum requirements. Concealed Work installed in pipe and duct shafts, chases or recesses, inside walls, above ceilings, in slabs or below grade. Design Equipment Refer to Article 1.7, BASIS OF DESIGN. Design Make Refer to Article 1.7, BASIS OF DESIGN. Equal or Equivalent Equally acceptable as determined by Owner’s Representative. Exposed Work not identified as concealed. Final Acceptance Owner acceptance of the project from Contractor upon certified by Owner’s Representative. Furnish Supply and deliver to installation location. Furnished by Others Receive delivery at job site or where called for and install. Inspection Visual observations by Owner’s site Representative. Install Mount and connect equipment and associated materials ready for use. Labeled Refers to classification by a standards agency. Make Refer to Article 1.7, BASIS OF DESIGN. Or Approved Equal Approved equal or equivalent as determined by Owner’s Representative. Owner’s representative Architect or Engineer having a contract directly with the Owner for professional services. Prime Professional Architect or Engineer having a contract directly with the Owner for professional services. Provide Furnish, install and connect ready for use. Relocate Disassemble, disconnect, and transport equipment to new locations, then clean, test, and install ready for use. Replace Remove and provide new item. Review A general contractual conformance check of specified products. Roughing Pipe, duct, conduit, equipment layout and installation. Satisfactory As specified in contract documents. ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 11 OF 24 JUNE 29, 2012 Refer to Division 1 sections for further definitions. 1.7 BASIS OF DESIGN A. The contract documents are prepared on basis of one manufacturer as "design make," even though other manufacturers' names are listed as acceptable makes. If Contractor elects to use one of the listed makes other than "design equipment," submit detailed drawings, showing that the proposed equipment from an acceptable manufacturer meets or exceeds the specifications of the design make. Show maintenance clearances, differing dimensions, service removal space required, and other pertinent revisions to the design arrangement. Make required changes in the work of other trades, at no increase in any contract. Assume responsibility for proper location of roughing and connections by other trades. If revised arrangement submittal is rejected, revise and resubmit specified "design equipment" item which conforms to contract documents. 1.8 INTENT OF DRAWINGS A. The drawings are diagrammatic, unless detailed dimensioned drawings are included. Drawings show approximate locations of equipment, racks, patch panels, cable managers, backboards, cabinets, wiring devices, pull boxes, conduits, core bores, cable trays, cable tray radius and floor penetrations, outlet locations, and fixtures. Exact locations are subject to the approval of the Owner's Representative. B. The general run of conduits, raceways, cable trays, ladder racks, backbone and horizontal pathways, underground utilities, and vertical and horizontal sleeves, indicated on the drawings, is not intended to be the exact routing. Conduit, outlet and cable designations and logical drawings, in the form of "Home Runs", indicate the designation of run, the size, general route and the quantity of cables and conductors, and the TR and BDF equipment rooms from which the homerun is served. Coordinate all horizontal and vertical pathway layout work with that of other trades and confirm cabling distance limitations for horizontal and backbone cabling will be adhered to. Coordinate all horizontal and vertical pathway layout work with that of other trades and confirm cabling bend radius and maximum pulling tension limitations will be adhered to, especially at all proposed junction box and pull box locations. 1.9 QUALITY ASSURANCE A. Manufacturers of equipment shall be firms regularly and currently engaged in the production of equipment and accessories provided. Unless otherwise noted the equipment provided for this project needs to have been in satisfactory and efficient operation on at least three (3) installations for not less than three (1) year. ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 12 OF 24 JUNE 29, 2012 B. Suppliers of equipment must have factory trained and authorized personnel for the service of all equipment provided. C. Apply and install materials, equipment, and specialties in accordance with manufacturer’s written instructions. Conflicts between the manufacturer’s instructions and the contract documents shall be referred to the Owner’s Representative for resolution. D. The contractors installers shall have been regularly engaged in the installation, termination and testing of the all equipment, cabling and devices called for in this contract for a minimum of (5) five years. E. The contractor shall engage the services of a qualified installer for the installation of access panels and cutting and patching work. F. The prime contractor is responsible for employing qualified sub? contractors to complete work where the quality assurance requirements cannot be met by the prime contractor’s full time employees. All subcontractors must be approved by the Owner. 1.10 SUBMITTALS A. Contractor’s qualifications and references B. Panduit P.S.C. certification C. Corning Cable Systems N.P.I. certification D. Complete breakdown of materials and unit pricing for all products included in their bid E. Signed Warranty. Also see 3.1 of this section F. Also refer to Refer to Section 01 33 00 – Submittal Procedures. PART 2 PRODUCTS 2.1 EQUIPMENT AND MATERIAL MINIMUM REQUIREMENTS A. Provide Materials That Meet the Following Minimum Requirements: 1. Materials shall have a flame spread rating of 25 or less and a smoke developed rating of 50 or less, in accordance with NFPA 255. 2. All equipment and material for which there is a listing service shall bear a UL label. ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 13 OF 24 JUNE 29, 2012 3. Electrical equipment and systems shall meet UL Standards and requirements of the N.E.C. This listing requirement applies to the entire assembly. Any modifications to equipment to suit the intent of the specifications shall be performed in accordance with these requirements. 4. Equipment shall meet all applicable FCC Regulations 5. All materials, unless otherwise specified, shall be new and be the standard products of the manufacturer. Used equipment or damaged material will be rejected. 6. The listing of a manufacturer as “acceptable” does not indicate acceptance of a standard or catalogued item of equipment. All equipment and systems must conform to the Specifications and meet the quality of the design make. 7. Materials used in this contract shall meet the N.Y.S. Fire, Gas and Toxicity Requirements and be listed in the directory of approved products filed under Article 15 Part 1120 of the New York State Fire Prevention and Building Code for use in New York State. 2.2 FACTORY?ASSEMBLED PRODUCTS A. Provide maximum standardization of components to reduce spare part requirements, including custom entrance end fittings and custom cable tray components. B. Manufacturers of equipment assemblies which include components made by others shall assume complete responsibility for final assembled unit. 1. All components of an assembled unit need not be products of same manufacturer. 2. Constituent parts which are alike shall be product of a single manufacturer. 3. Components shall be compatible with each other and with the total assembly for intended service. 4. Contractor shall guarantee performance of assemblies of components, and shall repair or replace elements of the assemblies as required to deliver specified performance of the complete assembly. C. Components of equipment shall bear manufacturer's name or trademark, model number and serial number on a name plate securely affixed in a ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 14 OF 24 JUNE 29, 2012 conspicuous place, or cast integral with, stamped or otherwise permanently marked upon the components of the equipment. D. Major items of equipment which serve the same function must be the same make and model. Exception will be permitted if performance requirements cannot be met. 2.3 COMPATIBILITY OF RELATED EQUIPMENT A. Equipment and materials installed shall be compatible in all respects with other items being furnished and with existing items so that a complete and fully operational system will result. 2.4 SPECIAL TOOLS A. If any part of equipment requires a special tool for assembly, adjustment or maintenance thereof and such tool is not readily available on commercial tool market, it shall be furnished by the Contractor. At the end of the project, contactor shall turn over two such tools to owner for their use in future operations and maintenance. 2.5 LIFTING ATTACHMENTS A. Provide equipment with suitable lifting attachments to enable equipment to be lifted in its normal position. Lifting attachments shall withstand any handling conditions which might be encountered without bending or distortion of shape, such as rapid lowering and braking of load. 2.6 MISCELLANEOUS SUPPORTS A. NEMA National Electrical Manufacturers’ Association Metal bars, plates, tubing, etc. shall conform ASTM standards: 1. Steel plates, shapes, bars, and grating ? ASTM A 36 2. Cold?Formed Steel Tubing ? ASTM A 500 3. Hot ? Rolled Steel Tubing ? ASTM A 501 4. Steel Pipe ? ASTM A 53, Schedule 40, welded B. Metal Fasteners shall be Zinc?coated (type, grade and class as required) 2.7 GENERAL CABLE REQUIREMENTS A. Interior Backbone optical fiber cables included in this project, passing through two or more floors shall be suitable, listed and marked for use in a riser application. Optical backbone cable shall minimally be OFNR rated ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 15 OF 24 JUNE 29, 2012 per the Current National Electric Code and shall meet all local and state codes. B. All Category 3 voice backbone cables, Category 6 & 6A horizontal cables shall be minimally CMR riser?rated per the Current National Electric Code and shall meet all local and state codes. C. Interior copper backbone cables shall be twisted 24 AWG, contain a corrugated aluminum shield and minimally be CMR rated. 2.8 FIRE STOPPING A. Fire?stopping for Openings through Fire and Smoke Rated Walls and Floor Assemblies shall be listed or classified by an approved independent testing laboratory for "Through?Penetration Fire?Stop Systems." The system shall meet the requirements of "Fire Tests of Through?Penetration Fire?Stops" designated ASTM E814. B. Fire stopping materials used on the inside of communications conduit, sleeve and cable tray penetrations through rated assemblies shall be suitable for future reentry. Reenterable putty and pillows are the preferred type products for all communication cabling installations. Curable foam sealants and caulks are not acceptable for inside sleeves and conduits for any communication cable plant installations. C. Shall be UL approved products. D. Shall conform to Section 07 84 13. PART 3 EXECUTION 3.1 WORKMANSHIP AND WARRANTY A. Workmanship shall meet or exceed industry standards and be fully guaranteed for one full year from final acceptance. B. A factory registered Panduit (PSC) and Corning Cable Systems (NPI) contractor shall complete the cable installation. The contractor shall have completed standards based product and installation training. A copy of the factory registrations shall be submitted with the proposal. C. The copper systems cabling and connectivity systems warranty shall be a Panduit Certification Plus System Warranty to guarantee total end?to?end high performance that meets application requirements. The guarantee shall include cable and connectivity components and have one point of contact for all cabling system issues. The copper cabling/connectivity system shall be warranted for a period of at least 15 years. ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 16 OF 24 JUNE 29, 2012 D. The optical fiber systems cabling and connectivity systems warranty shall be a Corning Cable Systems LANscape Network of Preferred Installers warranty to guarantee total end?to?end high performance that meets application requirements. The guarantee shall include cable and connectivity components and have one point of contact for all cabling system issues. The optical fiber system shall be warranted for a period of at least 15 years. E. The Contractor shall be responsible for and make good, without expense to the Owner, any and all defects arising during the warranty period that are due to imperfect materials, appliances, improper installation or poor workmanship. F. Cable integrity and associated terminations shall be thoroughly inspected , fully tested and guaranteed as free from defects, transpositions, opens? shorts, tight kinks, damaged jacket insulation etc. 3.2 EXISTING SYSTEMS AND CONDITIONS A. Inspect the entire work area for defects in the existing construction such as scratches, holes, damaged wall surfaces, damaged ceiling tiles, damaged furniture, etc. Submit a complete list and photographs of existing damage, to the owner prior to beginning work. If existing damage is not documented the contractor shall repair all damage to like new condition, that is determined to have been caused by the work in this contract. B. The job foremen for each division of work shall meet and plan the removals and new installations prior to reviewing with the owner’s representative. This shall include all requirements for Divisions 0, 1, 23, 26 and 27 contract requirements. At project start?up, special attention is required for coordination and sequencing for removal of existing exposed cable trough in corridors, maintain existing services, coordination of new cable tray installation requirements with regard to existing fire alarm annunciation, eye wash stations, emergency showers, door hold open devices etc. C. Before construction work commences, the Contractor shall coordinate exact conduit and penetration requirements, millwork and cabinetry modifications, conduit and raceway removals methods, pathway routing and installation methods, cable tray mounting routing and installation means and methods requirements for UTP faceplates, locations of new access panels, dumpster positioning and fire truck and delivery access, removal of raceways in advance of active cabling decommissioning, temporary service provisions for any planned reuse of existing conduit stub?ups and recessed backboxes, reuse of existing utility columns/chases in laboratories, etc. with the CIT Project Manager. Additionally, the Contractor shall coordinate exact storage, staging, ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 17 OF 24 JUNE 29, 2012 deliveries, use of freight or passenger elevators, recycling, and disposal requirements with the CIT Project Manager. 3.3 ROUGH?IN A. Due to small scale of Drawings, it is not possible to indicate all offsets, fittings, changes in elevation, etc. Verify final locations for rough?ins with field measurements and with the equipment being connected. Verify exact location and elevations at work site prior to any rough in work. DO NOT SCALE PLANS. If field conditions, details, changes in equipment or shop drawing information require a significant change to the original documents, contact the owners representative for approval before proceeding. B. All equipment locations shall be coordinated with other trades and existing conditions to eliminate interference with required clearances for equipment maintenance and inspections. 1. Where more than one trade is involved the construction of a Telecommunication Room (TR), all shall cooperate and install their own work to utilize the space equally between them in proportion to their individual requirements and as prioritized below. Refer to the T3 drawings for planning Telecommunication Room rough?in and plan and coordinate with all other trades accordingly. MOCK?UP RACKS, CABLE RUNWAYS AND MAJOR PATHWAYS ENTRY POINTS AS DIRECTED BY CIT PROJECT MANAGER, BEFORE ROUGH?IN OF ALL OTHER UTILITIES AND REVIEW WITH OWNER FOR APPROVAL TO PROCEED. Where possible, the design intent is to install the cable runways at approximately 8’ A.F.F with 12” of vertical clearance above. In general, 19” rack placement and cable runways shall be given ultimate placement preference, followed by backbone pathways and major raceways entering the TR from the corridor and floors above/below, followed by wiring and communications, followed by luminaries and lastly followed by mechanical equipment, mechanical piping and HVAC ductwork If, after installation of any equipment, piping, ducts, conduit, and boxes, it is determined that ample vertical clearance over the cable runways, maintenance and passage space has not been provided, rearrange work and/or furnish other equipment as required for ample maintenance space. Any changes in the size or location of the material or equipment supplied, which may be necessary in order to meet field conditions or in order to avoid conflicts between trades, shall be brought to the immediate attention of the Owner's Representative and approval received before such alterations are made. Coordinate work with other trades and existing conditions and determine exact routing of all cable tray, hangers, conduit, etc., before fabrication and installation. Coordinate with Architectural Drawings. Verify with Owner's ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 18 OF 24 JUNE 29, 2012 Representative exact location and mounting height of all equipment in finished areas, such as equipment racks, communication and electrical devices. Coordinate all work with the architectural reflected ceiling plans and/or existing Architecture. 2. Where horizontal pathways are installed above existing lay in ceilings, remove a section of tiles the complete length of the proposed pathway. Document all offsets, bends, box location, conflicts, obstructions, etc. required for the complete installation. Reinstall the ceiling tiles after requirements are documented and at the end of every shift. If there are existing obstacles that prevent the installation of the raceway in the general location indicated on contract documents, notify the owners representative immediately. 3. For equipment and connections provided in this contract, prepare rough?in drawings as follows: a) Existing equipment being relocated: Measure the existing equipment and prepare drawings for installation in new location. b) New equipment: Obtain equipment roughing drawings and dimensions, and then prepare rough?in drawings. 4. Where more than one trade is involved in an area, space or chase, all shall cooperate and install their own work to utilize the space equally between them in proportion to their individual requirements. In general, ductwork shall be given preference except where grading of piping becomes a problem, followed by piping then electrical wiring and communications. If, after installation of any equipment, piping, ducts, conduit, and boxes, it is determined that ample maintenance and passage space has not been provided, rearrange work and/or furnish other equipment as required for ample maintenance space. Any changes in the size or location of the material or equipment supplied, which may be necessary in order to meet field conditions or in order to avoid conflicts between trades, shall be brought to the immediate attention of the Owner's Representative and approval received before such alterations are made. C. Provide easy, safe, and code mandated clearances at equipment racks and enclosures, and other equipment requiring maintenance and operation. Contractor shall relocate existing work in the way of new construction. VISIT SITE BEFORE BIDDING TO DETERMINE SCOPE OF WORK. ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 19 OF 24 JUNE 29, 2012 D. The Contractor shall be responsible for all required locations, cutting, patching, coring and associated work for the complete cabling system at no additional cost to the Owner. 3.4 CUTTING AND PATCHING A. All cutting, patching and installation of sleeves, conduits and raceways for cabling work shall be by the Prime Contractor. The Contractor shall coordinate required penetration, sleeve, conduit raceway and cable tray locations with all other contractors, prior to the beginning the raceway work. Close coordination of relocations and penetrations into new TR rooms is critical to proper build?out and fit?out for desired layout and cable management of the new TR rooms. 3.5 CONCEALMENT A. Conceal all contract work above ceilings and in walls, below slabs, in attics, in chases in soffits, and elsewhere throughout building 3.6 FIRE?STOPPING A. Fire?stopping for Openings Through Fire and Smoke Rated Wall and Floor Assemblies: 1. Provide materials and products listed or classified by an approved independent testing laboratory for "Through?Penetration Fire?Stop Systems." The system shall meet the requirements of "Fire Tests of Through?Penetration Fire?Stops" designated ASTM E814. 2. Provide fire?stop system seals at all locations where cables pass through sleeves in rated partitions and floors. 3. The minimum required fire resistance ratings of the wall or floor assembly shall be maintained by the fire?stop system. The installation shall provide an air and watertight seal. 4. The methods used shall incorporate qualities which permit the easy removal or addition cables without drilling or use of special tools. The product shall adhere to itself to allow repairs to be made with the same material and permit the vibration, expansion and/or contraction of any items passing through the penetration without cracking, crumbling and resulting reduction in fire rating. 5. Provide the following ratings: a) Floors ? 3 Hours b) Corridor walls ? 1?2 hours ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 20 OF 24 JUNE 29, 2012 c) Smoke Partitions ? 1 hour 3.7 WATERPROOFING A. The contractor shall seal all foundation penetrating conduits and sleeves to eliminate the intrusion of moisture and gases into the building. B. Conduits with cables shall be permanently sealed by firmly packing the void around the cable with oakum and capping with 2 inches of hydraulic cement or waterproof duct seal. Obtain advance approval by owner for use of hydraulic cement to seal inside of underground conduits and ducts that have been prone to perpetual leakage and flooding. C. Spare underground conduits shall be plugged with expandable plugs, with pull?rope ring, to provide a secure and watertight fit and allow the end of the existing pull lines to be secured at the conduit entrance point. 3.8 SUPPORTS A. Provide required supports, beams, angles, hangers, rods, bases, braces, and other items to properly support contract work. Supports shall meet the approval of the Owner's Representative. Modify studs, add studs, add framing, or otherwise reinforce studs in metal stud walls and partitions as required to suit contract work. If necessary, in stud walls, provide special supports from floor to structure above. For precast Panels/Planks and Metal Decks, support communication work as determined by manufacturer and Owner's Representative. Provide heavy gauge steel mounting plates for mounting contract work. Mounting plates shall span two or more studs. Size, gauge, and strength of mounting plates shall be sufficient for equipment size, weight, and desired rigidity. 3.9 GENERAL INSTALLATIONS REQUIREMENTS A. Coordinate the installation of required supporting devices and sleeves to be set in poured?in?place concrete and other structural components, as they are constructed. B. Coordinate ordering and installation of all equipment with long lead times or having a major impact on work by other trades so as not to delay the job or impact the construction schedule. Pay close attention to equipment that must be installed prior to building enclosure. C. Where mounting heights are not detailed or dimensioned, install systems, materials and equipment to provide the maximum headroom possible. D. Set all equipment to accurate line and grade, level all equipment and align all equipment components. ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 21 OF 24 JUNE 29, 2012 E. Provide all scaffolding, rigging, hoisting and services necessary for erection and delivery of equipment and apparatus furnished into the premises. These items shall be removed from premises when no longer required. F. No equipment shall be hidden or covered up prior to inspection by the owners representative. All work that is determined to be unsatisfactory shall be corrected immediately. G. All work shall be installed level and plumb, parallel and perpendicular to other building systems and components. H. Install access panels or doors where units are concealed behind finished surfaces. 3.10 UTILITY COMPANY SERVICES A. Coordination by CIT. B. Provide grounding and bonding of copper media as required by the utility or service provider. 3.11 CORNELL UNIVERSITY SERVICES A. Cornell provides voice and data, Local Area Network, Fire Alarm Monitoring, Wide Area Network, local card access, local security systems etc. connections to all buildings in this project. Maintain all existing systems through the duration of construction. Coordinate all removals, shutdowns, service transfers with the Owner’s Representative. B. Prior to removal or relocation of any Cornell copper backbone cables (25 pair or greater) or any terminal blocks, the contractor shall test all pairs for presence of dial tone, digital telephone signal, battery, data services, special service circuits. Any suspect working circuits or any line that can be identified by telephone number shall be tagged for review by the Owner’s representative. Provide a list of locations of suspect working circuits to Owner. For pairs identified as unused in backbone cables (25 pair or greater), the contractor shall provide a soft kill (temporary partial disconnect) of every pair, whereby either the tip or ring conductor is lifted (create and open) from the terminal and a tag placed on each terminal block indicating the date and technician who performed said soft kill. A list of soft kills shall be maintained at the jobsite for routine inspection by the Owners representative and for immediate access by repair technician dispatched with trouble reports. If required by the Owner, the Contractor’s foreman shall contact the Cornell CIT project representative and the CIT helpdesk 10 minutes prior to performing soft kills so that contact information can be shared for escalation purposes. If required by the Owner, the Contractor’s foreman shall post official utility disruption notices ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 22 OF 24 JUNE 29, 2012 about the building in advance of the soft kill or possible service disruption. Soft kills shall remain intact for 7 working days before cutting and removal of each backbone cable. Soft kills shall be performed at least three days prior to any weekend or holiday so that building occupants have time to report troubles during normal working hours. C. Prior to removal or relocation of any Cornell fiber optical cables or connections the contractor shall meet and plan the working at least 5 days in advance with the Owner. Provide a list of locations of suspect working circuits to Owner. Provide a soft kill (temporary partial disconnect) of every fiber pair, whereby either the transmit or receive path is lifted (create and open) and a tag placed on each terminal block indicating the date and technician who performed said soft kill. A list of soft kills shall be maintained at the jobsite for routine inspection by the Owners representative and for immediate access by repair technician dispatched with trouble reports. If required by the Owner, the Contractor’s foreman shall contact the Cornell CIT project representative and the CIT helpdesk 10 minutes prior to performing soft kills so that contact information can be shared for escalation purposes. If required by the Owner, the Contractor’s foreman shall post official utility disruption notices about the building in advance of the soft kill or possible service disruption. Soft kills shall remain intact for 7 working days before cutting and removal of each backbone cable. Soft kills shall be performed at least three days prior to any weekend or holiday so that building occupants have time to report troubles during normal working hours. 3.12 PAINTING A. This Contract includes the following: 1. Painting required for touch?up of surfaces damaged due to the installation of Division 27 work. 2. All finished equipment surfaces damaged during construction shall be brought to “as new” condition by touch or repainting. Any rust shall be removed and primed prior to painting. 3. Patch and paint wall and floor penetrations where cabling has been installed without the use of conduits, sleeves or raceways. 4. Refer to Section 09 91 23?Painting, for additional requirements. 5. Painting as called for on Division 27 Drawings. 3.13 REMOVALS A. Where existing equipment and cable removals are called for, submit complete list to Owner's Representative. All items that Owner wishes to ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 23 OF 24 JUNE 29, 2012 shall be delivered to location directed by Owner. Items that Owner does not wish to retain shall be removed from site and legally disposed of or recycled. Removal and disposal of materials shall be in accordance with Federal, State and Local law requirements. Where equipment is called for to be relocated, contractor shall carefully remove, clean and recondition, then reinstall. Remove all abandoned cabling, wiring, equipment, supports, straps, anchors, rings, plywood, terminal block and fixtures, etc. Visit each room, janitor closet, and pipe chase, shaftway, etc. to determine total Scope of Work. B. Unless indicated otherwise on the removal drawings, completely remove all supports, straps, hangers, rings, staples, anchors, rings, tywraps, plywood, terminal blocks, fixtures, conduit raceways, fastenings to building structural systems and other devices associated with the equipment not to be reused in the new work. Seal all openings, after removal of equipment and cabling in an approved manner and in accordance with plans and specifications where specifically covered. Structural integrity of the building system shall be maintained. Reference shall also be made to the architectural, structural, mechanical, site, and electrical drawings and specifications for additional facilities to be demolished or handled. 3.14 START UP AND OWNER INSTRUCTIONS A. Before acceptance of the work, furnish necessary skilled labor to operate all systems. Instruct the Owners designated personnel on the proper operation and maintenance of systems and equipment. Obtain written acknowledgment from person instructed prior to acceptance repeat the instructions if asked to do so. Contractor is fully responsible for systems until acceptance, even though operated by Owner's personnel, unless otherwise agreed in writing. Provide, operating, maintenance and starting precautions and procedures to be followed by the Owner for operating systems and equipment. Mount the instruction in clear plastic holder on or adjacent to the equipment. B. Where supervision by a manufacturer is called for, provide manufacturer’s certified technician or engineer to supervise the startup, testing and adjustment of the equipment or system. Where two or more manufacturer’s are involved both manufacturer’s shall be present at start up. The manufacturer shall provide a written report detailing the testing and start?up including problems that occurred and their method of resolution. 3.15 CUTOVER A. The cabling contractor shall have a minimum of two (2) technicians available for on?site to assist as required with system(s) activation for each phase of construction. Duration to include a minimum of eight hours. ARCHITECHNOLOGY CORNELL – NCP BASIC COMMUNICATIONS REQUIREMENTS STANDARD SPECIFICATIONS 27 05 00 – PAGE 24 OF 24 JUNE 29, 2012 B. Activities shall include, but will not be limited to: 1. Troubleshooting of installed cable plant 2. Installation of additional cables. 3. Trouble ticket resolution 3.16 RECORD DOCUMENTS A. Prepare and provide record documents in accordance with all requirements of Sections 01 78 39 and this Section. B. In addition to those requirements provide the following: 1. Document the routing of major backbone conduit systems, location of pullboxes and junction boxes, location of backbone copper splices and wall?to?wall measurements of backbone conduit systems. 2. Document the rack and cabinet elevations of all contract installed hardware and also include Owner provided electronics and hardware that has been added to each rack or cabinet in the TR rooms prior to final acceptance. 3. Document the location of new access panels installed into permanent ceilings. END OF SECTION ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 1 OF 20 JUNE 29, 2012 SECTION 27 05 28 COMMUNICATIONS PATHWAYS PART 1 GENERAL 1.1 SUMMARY A. SCOPE 1. This section includes minimum requirements for the following: a) Interior Horizontal Cabling Communication Pathways b) Interior Backbone Cabling Communication Pathways 2. Minimum composition requirements and installation methods for the following pathways: a) Conduit b) Innerduct c) Sleeves d) Cable tray e) Cable hangers (JHooks) f) Wireways and wire troughs g) Floor Boxes h) Outlet Boxes 3. Provide all labor, materials, tools and equipment required for the complete installation of work called for in the contract documents. 4. Prior to installation and as part of the contract, relocate any device a distance of 6 feet in any direction at the request of the owner at no additional cost. This shall include all necessary conduit/s, cable, raceways, cutting, painting and patching to accomplish the modification. Also refer to Division 26 specifications. 1.2 QUALITY ASSURANCE A. All pathways and associated equipment shall be installed in a neat and workmanlike manner. All methods of construction that are not specifically described or indicated in the contract documents shall be subject to the control and approval of the Owner's Representative. Equipment and materials shall be of the quality and manufacture indicated. The equipment specified is based upon the acceptable manufacturers listed. Where "approved equal" is stated, equipment shall be equivalent in every way to that of the equipment specified and subject to approval. ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 2 OF 20 JUNE 29, 2012 B. Materials and work specified herein shall comply with the applicable requirements of: 1. National Electric Code (NFPA 70) including the following Articles: a) 318 Cable Trays b) 331 Electrical Nonmetallic tubing c) 348 Electrical metallic tubing d) 349 Flexible metallic tubing e) 350 Flexible metal conduit f) 351 – LiquidTight Flexible metal conduit and LiquidTight flexible nonmetallic conduit. g) 352A Surface Metal Raceways h) 352B Surface Nonmetallic raceways i) 353 – Multioutlet Assembly j) 354 – Underfloor raceways k) 362 Metal Wireways and nonmetallic Wireways l) 370 Outlet, Device, Pull and Junction Boxes , Conduit Bodies and Fittings m) 645 Information Technology Equipment n) 770 Optical Fiber Cables and Raceways o) 800 Communications Circuits 2. The following American National Standards Institute (ANSI) standards: a) ANSIC80.3 Specification for Electrical Metal lic Tubing, Zinccoated b) ANISIC80.2 Specification for rigid steel co nduit, enameled 3. The following Telecommunication Industry Association (TIA) standards. a) ANSI/TIA/EIA – 568C. Commercial Building Tel ecommunications Cabling Standard b) ANSI/TIA/EIA – 569B Commercial Building Stan dard for Telecommunications Pathway and Spaces c) EIA/TIA606A Administration Standard for the Telecommunications Infrastructure of Commercial Buildings ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 3 OF 20 JUNE 29, 2012 d) EIA/TIA607 –B Commercial Building Grounding and Bonding requirements for Telecommunications 4. The following BICSI guidelines a) BICSI Telecommunications Distribution Design Manual (9th edition) b) BICSI Customer Owned Outside Plant Design Manual (2nd edition) c) BICSI Telecommunications Cabling Installation Manual (2nd edition) 5. The following UL Standards: a) UL 1, 2000 Flexible Metal Electrical Condui t b) UL 3, 1999 Flexible Nonmetallic Tubing for Electric Wiring c) UL 5, 1996 Surface Metal Electrical Raceway s and Fittings d) UL 360, 1996 LiquidTight Flexible Steel Co nduit, Electrical e) UL 514B, 1996 Fittings for Conduit and Outl et Boxes. f) UL 797, 1997 Electrical Metallic Tubing g) UL 870, 1995 Electrical Wireways, Auxiliary Gutters and Associated Fittings 1.3 SUBMITTALS A. Provide product data for the following: 1. Conduit 2. Sleeves 3. Cable tray 4. Cable hangers (JHooks) 5. Wireways and wire Troughs 6. Floor Boxes 7. Outlet Boxes 8. Surface raceways 9. Cable tray accessories and specialty fittings, including panel type connectors for finished ends 10. EACH surface raceway entrance end fitting and each radius elbow / tee per T4 details drawing and this section 11. Label each submittal with a specification section and a T4 drawing detail reference ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 4 OF 20 JUNE 29, 2012 PART 2 PRODUCTS 2.1 CONDUIT A. Rigid Galvanized Steel Conduit 1. Shall be hotdipped galvanized steel, includin g threads. B. Electrical Metallic Tubing (EMT) 1. Electrical Metallic Tubing shall be electroga lvanized steel 2. Acceptable manufactures a) Triangle b) Wheatland Tube c) Allied Tube d) Steel Duct e) LTV Steel C. Flexible Metal Conduit 1. Flexible Metal Conduit shall only be permitted when used in the inside the wall cavity only. 2. Flexible Metal Conduit shall be constructed of one continuous length of spirally wound, interlocked, zinc coated strip steel. Interior surface shall be free from burrs or sharp edges 3. Acceptable manufacturers a) Anaconda b) American Flexible Conduit Co. c) OZ/Gedney d) Thomas and Betts D. Liquidtight Flexible Metal Conduit 1. Flexible Metal Conduit shall be constructed of one continuous length of spirally wound, interlocking zinc coated strip steel. Interior surfaces shall be free from burrs and sharp edges. Provide with a liquidtight jacket of flexi ble polyvinyl chloride (PVC). 2. Acceptable manufacturers: a. Allied ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 5 OF 20 JUNE 29, 2012 b. American Flexible Conduit c. Carlon d. Thomas and Betts E. Fittings 1. Rigid galvanized steel fittings shall be fully threaded and shall be of the same material as the respective raceway system. 2. Fittings for electrical metallic tubing shall be single screw indenter fittings for conduits up to 2" and double screw indenter fittings for conduits 2" and larger. 3. Fittings for flexible metal conduit shall be center stopped, insulated throat, U.L. E11852 listed 4. Fittings for liquidtight flexible metal conduit shall have zinc plated steel ferrule, compression type with sealing ring 5. Fittings for rigid nonmetallic conduit shall be solvent cemented in accordance with the manufacturer's instructions 6. Connectors shall have insulated throat up to and including 1" size. For sizes 11/4" and larger, provide plastic insulating bushing. 7. Diecast or pressure cast fittings are not per mitted. 8. Provide conduit bodies types, shapes and sizes as required to suit application and NEC requirements. Provide matching gasketed covers secured with corrosionresistant screws. 9. Conduit bodies are allowed instead of changing directions in boxes (obtain approval from construction manager). 10. Acceptable manufacturers a) O.Z. Gedney b) Steel City c) Thoams and Betts d) Copper CrouseHinds e) Carlon F. Raintight Fittings (Compression EMT) 1. Acceptable manufacturers: Bridgeport Fittings, OZ Gedney, Steel City/Thomas and Betts. 2. Design makes:. a). Bridgeport Fittings: 26xSRT Series coupler for 1” EMT trade size. ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 6 OF 20 JUNE 29, 2012 b) Bridgeport Fittings: 25XSRT Series connector for 1” EMT trade size. G. Space Saver Connector Fittings 1. Rigid galvanized steel fittings shall be fully threaded and shall be of the same material as the respective raceway system 2. Fittings for electrical metallic tubing shall be single screw indenter fittings for conduits up to 2" and double screw indenter fittings for conduits 2" and larger 3. Diecast or pressure cast fittings are not permitte d 4. Provide space saver EMT conduit connectors, in compression or set screw type as called for in the T4 detailed drawings for: cable tray, raceway entrance end fittings, and backbox connections for communication cabling – to maximize the cable bend radius, crosssectional area and cable fill ratios 5. Acceptable manufacturers: Cooper CrouseHinds , Space Saver Series 6. Design make a) #SSBC1xx Series (set screw) b) #SSC1xx Series (compression) H. Expansion Fittings 1. Provide expansion fittings with external grounding straps at building expansion joints. 2. Galvanized steel expansion joints for RGS or EMT conduit 3. Provide a minimum of 4” movement in either direction. 4. Weatherproof for outdoor applications. 5. At expansion joints in concrete pours, provide Deflection/Expansion fittings capable of movement of ¾” in all directions from the normal. I. Waterproofing Seals 1. Provide watertight expanding linktype seals f or installation between the conduit and the sleeve or core drilled hole. 2. Design Make: Link Seal, or approved equal H. Pull and Junction Boxes 1. Shall be constructed of not less than 14 gauge galvanized steel with trim for flush or surface mounting in accordance with the location to be installed. Provide screwon type covers. Boxes installed in damp or wet locations shall be of raintight construction with gasketed cover and threaded conduit hubs. In no case shall boxes be sized smaller than as indicated in Article 370 of the National Electrical Code for conduit and conductor ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 7 OF 20 JUNE 29, 2012 sizes installed. Boxes shall be NEMA approved for the environmental condition of the location where they will be installed. I. Flush floor junction boxes 1. Flush floor junction boxes shall be recessed cover boxes designed for flush mounting in masonry. 2. Provide checkered plate gasketed cover suitable for foot traffic. 2.2 SURFACE METALLIC RACEWAY A Refer to pathway schedules on T2series for addi tional surface raceway sizes, cable fill tables, and cable radius requirements. B TYPE SR2 (2400 series) 1. .875” H x 2.0”W 2. Metallic two piece raceway with single compartment. 3. Color shall be Ivory color and have a durable finish with a scratchresistant surface that can be field painted. 4. Refer to T4Series Drawings for additional informat ion and requirements. 5. Provide the following fittings: a) Entrance end fitting nominal maximum dimension s of 2.75”W x 2.75”H x 4” L. and 1” conduit knockout that can be field punched to a maximum of 1.5” and can accept the 1.5 inch locknut without clearance issues. b) Back entrance end fitting same as entrance end fitting with internal radius. c) Tee fittings to connect to SR3 (3000 Series) and SR4 (4000 Series) raceway where T section to SR2 (2400 Series) has maximum w idth equal to SR2 raceway d) Bridge fitting with radius for spanning existing raceways in varying widths from ½” to 4. e) Flat Internal and external elbows UL verified for a 2" [51mm] bend radius and exceeding the recommendations of EIA/TIA 569A. Internal or external radius control must be provided. Derate fill capacities when internal radius control is provided, as recommended by the manufacturer. f) Surface 2” x 4” or 4” x 4” boxes, with 2.25” depth as called for 6. Design Make: MonoSystems, Inc. SMS2400 series race way, SMS2457 series bridge fittings, SMS2410 series entrance end fittings, SMS 2442 and 2430 T fittings. ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 8 OF 20 JUNE 29, 2012 7. CUSTOM FITTINGS Design Make: MonoSystems, Inc . per T4 detail drawings: SMS2410C15, SMS2457B, SMS3024T, SMS2442, SMS30241, SMS2444B, etc. 8. Acceptable Manufacturers: Wiremold, Hubbell or others as submitted by contractor and preapproved by Owner. C TYPE SR3 (3000 Series) 1. 1.5” H x 2.75”W 2. Metallic two piece raceway with single compartment. 3. Color shall be Ivory color and have a durable finish with a scratchresistant surface that can be field painted. 4. Refer to T4Series Drawings for additional inf ormation and requirements. 5. Provide the following fittings: a) Entrance end fitting nominal maximum dimens ions of 3.7”W x 3.75”W x 4” L. and 2” conduit knockout that can be field punched to a maximum of 2.5” and can accept the 2.5 inch locknut without clearance issues. b) Back entrance end fitting same as entrance end fitting with internal radius. c) Tee fittings to connect to SR2 (2400 Series) raceway where T section to SR2 has maximum width equal to SR2 raceway d) Flat Internal and external elbows UL verified for a 2" [51mm] bend radius and exceeding the recommendations of EIA/TIA 569A using internal or external radius components. Internal or external radius control must be provided. Derate fill capacities when internal radius control is provided, as recommended by the manufacturer. 6. Design Make: MonoSystems, Inc. SMS3000 series raceway, with SMS3009, SMS3010 and SMS3018 fittings. 7. CUSTOM FITTINGS a) Design Make: MonoSystems, Inc. per T4 detail drawings: SMS3057B, SMS3024T, SMS3018R2, SMS30241, SMS3082, SMS3014R2, etc. 8. Acceptable Manufacturers: Wiremold, Hubbell or others as submitted by contractor and pre approved by Owner. D. TYPE SR4 and SR4d (4000 Series) 1. 1.75” H x 4.75”W 2. Metallic two piece raceway with single or divided compartment as called for on plans. 3. Color shall be Ivory color and have a durable finish with a scratchresistant surface that can be field painted. ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 9 OF 20 JUNE 29, 2012 4. Provide the following fittings: a) Entrance end fitting nominal maximum dimens ions of 4.75”W x 3”H x 4” L. and 2” conduit knockout that can be field punched to a maximum of 2.5” and can accept the 2.5 inch locknut without clearance issues. b) Back entrance end fitting same as entrance end fitting with internal radius. c) T fittings to connect to SR2 (2400 Series) r aceway where T section to SR2 has maximum width equal to SR2 raceway d) Flat Internal and external elbows with fiber optic radius 5. Design Make: MonoSystems, Inc. SMS4200 Series raceway, with SMS4205 SMS4214FO, SMS4211FO and SMS4209FO fittings. 6. CUSTOM FITTINGS a) Design Make: MonoSystems, Inc. per T4 detai l drawings: SMS2442, SMS42053, etc. 7. Acceptable Manufacturers: Wiremold, Hubbell or others as submitted by contractor and preapproved by Owner. E. TYPE SR7 (700 Series) 1. Onepiece raceway 2. Color shall be Ivory color and have a durable finish with a scratchresistant surface that can be field painted. 3. Utilized for wall mounted phones and miscellaneous branch circuit power only. 4. Provide internal and external 90 degree fittings with radius. 5. Provide miscellaneous boxes, extension rings, fittings and supports designed and manufactured by the raceway manufacturer as required making a complete job. 6. Design Make: Mono Systems SMS700 7. Acceptable Manufacturers: Wiremold, Hubbell or others as submitted by contractor and preapproved by Owner... 2.3 SLEEVES A. See EMT requirements 2.4 GROUNDING BUSHINGS A. Shall be provided for all conduits 2” and larger and longer than 10ft and shall be bonded to the MTGB or TGB in the TR. 1. Shall facilitate a bonding path for all Sleeves and conduits back to Telecommunication Ground bar’s in each TR. ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 10 OF 20 JUNE 29, 2012 2. Bushing shall provide protection for cables from damage. B. Design Make 1. Arlington 2.5 WIRE MESH CABLE TRAY A Cable Tray Finish: Carbon Steel with Zink plating. B. Cable tray will consist of continuous, rigid, welded steel wire mesh cable management system, to allow continuous ventilation of cables and maximum dissipation of heat, with UL Classified splices where tray acts as Equipment Grounding Conductor (EGC). Wire mesh cable tray will have continuous Safe/T/Edge T/welded top side wire to protect cable insulation and installers. C. Provide splices, supports, and other fittings necessary for a complete, continuously grounded system. 1. Mesh: 2 x 4 inches (50 x 100 mm). 2. Straight Section Lengths: 118 inches (3,000 mm). 3. Wire Diameter: Patented design includes varying wire sizes to meet application oad requirements; to optimize tray strength; and to allow tray to remain lightweight. 4. Safe/T/Edge: Patented Safe/T/Edge technology on side wire to protect cable insulation and installers’ hands. 5. Fittings: Wire mesh cable tray fittings are field/fabricated from straight tray sections, in accordance with manufacturer’s instructions and Item 2.3. 6. CF Series Cable Tray Size: 7. Depth: Cable tray shall be available in the following depths: a) [1 inch (30 mm)] b) [2 inches (54 mm)] ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 11 OF 20 JUNE 29, 2012 c) [4 inches (105 mm)] d) [6 inches (150 mm)] 8. Width: Cable tray width will be available in the following widths: a) [2 inches (50 mm)] b) [4 inches (100 mm)] c) [6 inches (150 mm)] d) [8 inches (200 mm)] e) [12 inches (300 mm)] f) [18 inches (450 mm)] g) [20 inches (500 mm)] h) [24 inches (600 mm)] 9. Length: Cable tray section length will be 118 inches (3000mm) unless otherwise shown on drawings. D. Support cable tray as recommended by manufacture. Provide a safety loading factor of 1.5 for uniformly distributed loads when supported as a simple span in accordance with the NEMA standard listed. E. Refer to pathway schedules for Cable Tray sizing and types additional requirements F. Refer to program standard detail Drawing for additional Cable Tray details and requirements G. Design Makes: Legrand Cablofil Wire Mesh H. Acceptable Manufacturers: 1. Cooper B/line Flextray 2. Approved equal 2.6 ENCLOSED CABLE TRAY A. Solid Bottom Cable Trays shall be one piece construction bottom and sides. Provide all required fittings for a complete system. Refer to ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 12 OF 20 JUNE 29, 2012 drawings T4 Series detailed drawings for additional requirements B. Standard length of 10’/0” per section. C. All cable trays shall be provided with flanged lay/on covers. Covers shall be a maximum of 5’ in length. Provide shorter sections of cover at beam crossings and pull box connections. D. Wrap around type bolted connector to connect tray sections. E. Minimum inside radius of horizontal elbows shall be 12 in. Provide special radius elbows where required for field conditions or as called for. Horizontal and Vertical bends for solid bottom trays shall have solid bottoms Support cable tray as recommended by manufacture. Provide a safety loading factor of 1.5 for uniformly distributed loads when supported as a simple span in accordance with the NEMA standard listed. G. Cable tray, cover, and all supporting devices shall be painted to match existing surroundings when exposed, Cable tray shall not be painted when exposed in mechanical and Telecommunication Rooms (TR’s), as called for on the T2 series drawings. When required, cable tray and cover shall be painted by the manufacture with a baked on finish. Provide color sample with submittal. H. Provide panel connector type end fitting to finish open ends of cable trays at Telecommunication Rooms I. Provide screw/on covers for vertical section of cable trays and secure upon cable placement J. Provide cable support mounting means in all vertical section of cable trays K. Refer to T2/Series Drawing pathway schedules for Cable Tray sizing and types additional requirements L. Refer to AT/CU standard installation details for additional Cable Tray details and requirements ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 13 OF 20 JUNE 29, 2012 M. Design Makes: LeGrand Fiber Trough Cable Tray, Wiremold SpecMate Series, or Monno/Systems Steel L series for new cable. N. Acceptable Manufacturers: Approved equal 2.7 CABLE HANGERS ( JHOOK) A. Provide prefabricated, zinc coated, carbon steel hangers designed specifically for UTP and Optical Fiber cable installations. B. Hangers shall have open top, rolled edges and a 3” or 4” minimum diameter loop. C. Provide beam clamps, rod fasteners, flange clips and brackets as job conditions require. D. Design Make CADDY CAT CM E. Refer to AT/CU standard installation details for additional Cable hanger pathway (J/Hook) details and requirements 2.8 SUPPORTING DEVICES A. Supports, support hardware and fasteners shall be protected with zinc coating or treatment of equivalent corrosion resistance using approved alternative treatment, finish or inherent material characteristic. Products used fin outdoor applications shall be hot dipped galvanized. B. Provide clevis hangers, riser clamps, conduit straps, threaded c clamps with retainers, ceiling trapeze hangers, wall brackets and spring steel clamps as applicable. C. 14 gauge UChannel systems with 9/16 inch diame ter holes at a minimum of 1 7/8 inches on center in the top surface. Provide fittings and accessories that match and mate channel. D. Provide carbon steel or wedge or sleeve type expansion anchors, steel springhead toggle bolts and heattreated steel power driven threaded stud f astening equipment as required by construction types. E. Provided field fabricated supporting devices such as angles, channels, pipe supports, etc. All fabricated supports shall be of metal construction as called for in 2.1. PART 3 EXECUTION 3.1 CONDUIT A. Conduit: 1. Electrical Metallic Tubing, Rigid Metal Conduit and Flexible metal conduit is are allowed Conduit types. ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 14 OF 20 JUNE 29, 2012 2. Install with a minimum of bends and offsets. Bends shall not kink or destroying the interior cross section of the raceway. Factory made bends shall be used for raceway’s 1" trade size and larger. Bends radius shall be 6 times the internal diameter for conduit sizes up to 2 inches. A conduit greater than 2 inch shall have bend radius at least 10 times the diameter of the conduit. 3. Runs exceeding 100 feet or 180 degrees total bends shall be broken with suitable sized pull or splice boxes. (LB or similar conduit fittings are not acceptable for runs of riser cables. Verify applicability before installing such fitting 4. Do not locate riser pull boxes at bends without prior review and approval by owner. Where possible use instead sweeps for the bend and locate in a straight pull nearby. 5. Conduit runs to work areas shall not loop through one communication outlet to feed another outlet. 6. Conduits shall be sized to accept 50% future growth; sizing shall account for fire code capacity restrictions. 7. Plug the ends of each roughedin raceway with an approved cap or disc to prevent the entrance of foreign materials during construction. 8. Secure within three feet of each outlet box, junction box, cabinet or fitting. 9. Provide a poly pull line in all "Spare" or "Empty" conduit runs to facilitate future installation of cables. 10. Install raceways in concrete floor slabs as follows: a) All conduits in concrete floor slabs shall be rigid galvanized steel with concrete tight threaded fittings. b) Provide expansion fittings where conduits cross building expansion joints. c) Install conduit below the reinforcing mesh. d) Locate conduits to provide a minimum of 1” of concrete around conduit. e) Obtain approval from the Owner's Representative prior to installing conduit larger than 1" trade size in concrete slabs. f) Wherever a cluster of four(4) or more condui ts rise out of floor exposed, provide neatly formed 4in. high concrete envelope, with ch amfered edges, around raceways. 11. Provide conduit supports based on the following table: Conduit Trade Size Type of Run Horizontal Spacing in Feet Vertical Spacing in Feet ½”, ¾” Concealed 7 10 ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 15 OF 20 JUNE 29, 2012 1”, 1 ¼” Concealed 8 10 1 ½”, & LARGER Concealed 10 10 ½”, ¾” Exposed 5 7 1”, 1 ¼” Exposed 7 8 1 ½” & larger Exposed 10 10 12. Where conduits puncture roof, install pitch pockets as required in order that the roof warranty is maintained. 13. Conduit System Installation: a) Cable in exterior, above grade locations: Rigid Galvanized Steel b) Interior locations: Electrical Metallic Tubing c) Cable below grade: PVC Schedule 40 14. Identification: Clearly label conduit at exposed ends indicating closet or outlet where conduit terminates and the length of the conduit. Label pull boxes indicating destination of conduits entering and exiting. 15. Include intra and interbuilding raceways. I ncluding conduits, sleeves and trays for the placement of cables from the communications center to communications closets, from the communications center to the entrance room or space and from communication center to communication center in different building in a campus environment. B. Conduit fill shall be as follows: Trade Size Area of Conduit (square inches) 1 Cable 53% Fill (sq. in.) 2 Cables 31% Fill (sq. in.) 3 Cables & Over 40% Fill (sq. in.) ¾” 0.53 0.28 0.16 0.21 1” 0.87 0.46 0.27 0.35 1 ¼” 1.51 0.80 0.47 0.60 1 ½” 2.05 1.09 0.64 0.82 ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 16 OF 20 JUNE 29, 2012 2” 3.39 1.80 1.05 1.36 2 ½” 4.82 2.56 1.49 1.93 3” 7.45 3.95 2.31 2.98 3 ½” 9.96 5.28 3.09 3.98 4” 12.83 6.80 3.98 5.13 5” 20.15 10.68 6.25 8.06 C. Backbone pathways shall be in the form of 4” conduits or sleeves between the main communication equipment rooms and spaces and closets shall be provided as shown on drawings: D. Fire stop all pathways as called for in 27 05 00. E. All backbone conduits shall be marked with 1” reflective tape every 25 feet. Coordinate color with owner. F. Pull boxes shall be marked with 1” wide reflective tape. G. Stub out conduits into closets only enough to attach connector and bushings, vertical conduits shall rise a minimum of 6 inches above the finished floor. H. Bush all conduit ends. I. Conduits shall be concealed except in the following areas: 1. Mechanical Rooms 2. Electric Rooms 3. Manufacturing areas 4. Garage or maintenance areas 5. Unfinished basements or crawl spaces 6. Telecommunications rooms 7. Utility chaseways J. Do not install raceways adjacent to hot surfaces or in wet areas. ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 17 OF 20 JUNE 29, 2012 K. Install conduits to edges of access boxes so as to maximize the total number of conduits that can be routed through the pull box. L. Provide expansion fittings with external grounding straps at building expansion joints. M. Do not install conduit horizontally in concrete or block partitions. N. Arrange neatly to permit access to the raceway, outlet, pull, and junction boxes, and work installed by other trades. O. If it is necessary to burn holes through webs of beams or girders, call such points to the attention of the Owner's Representative and receive written approval both as to location and size of hole before proceeding with work. All holes shall be burned no larger than absolutely necessary. If allowed, the contractor shall arrange for and receive a burn permit per University standards, requirements or as directed. P. Core drill, sleeve, and fire stop all penetrations through existing floors. Q. Support all raceways with malleable iron pipe clamps or other approved method. In exterior or wet locations, provide minimum ¼” air space between raceway and wall. Secure raceway within 3 ft. of each outlet box, junction box, cabinet or fitting. R. Install junction and pull boxes in readily accessible locations. Equipment, piping, ducts and the like shall not block access to boxes. Provide all necessary junction or pull boxes required due to field conditions and size as required by the National Electrical Code. S. Conduits shall be installed with a pull string with a minimum test rating of 200lbs. 3.2 SLEEVES A. Support, fire stop and size as per drawing 3.3 CABLE TRAYS A. Cable Tray routing shown on the plans is diagrammatical only. Contractor shall field verify all routes and potential existing utility/structural conflicts. Contractor to verify all major tiein points, floor penetrations, existing ceiling access panels, ceiling elevations, existing mechanical ductwork and equipment, existing sleeves and corridor wall penetrations that may conflict with the new cable tray installation, etc. prior to the start of construction. Coordinate proposed routing changes and offsets with the owner in advance. All routing changes shall be at no additional cost to the contract. B. Hang Cable tray using threaded, galvanized rod hangers, with rods extended through support steel and double nutted. Size support member within load rating of member section; and without visible deflection. Install cable tray level and straight. C. Provide seismic bracing as required by code. D. Provide stiffeners to prevent lateral movement and stabilize cable tray. Provide minimally one stiffener assembly per vertical support (threaded rod). E. A minimum of 12” headroom shall be provided above all cable trays. ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 18 OF 20 JUNE 29, 2012 F A minimum of 18” side clearance shall be provided for all cable trays. G. Provide aluminum body expansion connectors at building expansion joints. Minimum 4in. movements, greater if expansion movement conditions warrant. H. Provide external grounding strap at expansion joints, sleeves, crossovers and at other locations where tray continuity is interrupted. I. Provide necessary elbows, tees, crosses, risers, offsets, fittings, reducers, connectors, clamps, rod suspension, trapeze hangers, etc., as required to make a complete job, coordinate with the manufacturer. J. Provide (1) 6” long piece of ½” EMT conduit or snap on covers on each threaded rod hanger to prevent scoring of cable insulation when cable is pulled in. 3.4 CABLE HANGERS (JHOOKS) A. Provide cable hangers a maximum of 3’ on center wherever cable tray or conduit is not present for support low voltage cabling. B. Ceiling ties and rods shall not be used to hang cable or cable supports without the approval of the Owner. C. Load hangers as recommended by the manufacturer. Provide hangers side by side on a common bracket where cable quantities require. D. Do not install cables loose above lockin type, drywall or plaster ceilings. E. Cables shall be installed at least 3 in. above the ceiling tiles and shall not touch the ceiling. F. Do not support cable from ceiling system tie wires or grid in fire rated systems. G. Provide a minimum of 2 spare bracket mounted hangers in new construction. 3.5 FLOOR BOXES A. Floor outlet boxes shall be installed flush with finished floor, adjust level and tilt as required. Where finished floor is terrazzo, provide boxes specifically designed for installation in terrazzo. Where floors are to receive carpet, provide floor outlet with carpet flange. B. Furniture layout. Provide coordination drawings for approval. 3.6 BOXES AND CABINETS A. Consider location of outlets shown on drawings as approximate only. Study architectural, electrical, process piping, mechanical, plumbing, structural, roughingin, etc., drawings and note surrounding areas in which each outlet is to be located. Locate outlet so that when fixtures, motors, cabinets, equipment, etc., are placed in position, outlet will serve its desired purpose. Where conflicts are noted between drawings, contact Owner's Representative for decision prior to installation. ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 19 OF 20 JUNE 29, 2012 B. Outlet boxes in separate rooms shall not be installed "backtoback" without the approval of the Owner's Representative. C. Outlet boxes shall be sized to accommodate the wiring device(s) to be installed. D. Outlet boxes installed in plaster, gypsum board or wood paneled walls shall be installed with raised plaster covers or raised tile covers. E. Outlet boxes installed in tile, brick or concrete block walls shall be installed with extradeep type raised tile covers or shall be 31/2" deep box es with square corners and dimensions to accommodate conductors installed. F. Surface ceiling mounted outlet boxes shall be minimum 4" square, 11/2" deep, galvanized sheet metal. G. Surface wall mounted metallic outlet boxes shall be cast type boxes having threaded or compression type threadless hubs. Exterior boxes shall be cast type with threaded hubs and gasketed cover plates secured by nonferrous screws . H. Where structural or other interference prevent compliance with mounting heights listed, consult Owner's Representative for approval to change location before installation. I. Where communications outlets are shown on, behind, below or above furniture or millwork. Verify the exact location and mounting height with the project coordinator. The electrical contractor shall be responsible for moving all communications outlets that are in conflict with furniture or millwork, including cutting, patching and painting, at no cost to the owner J. Pull boxes shall have a distance between each raceway entry inside the box and the opposite wall of the box of at least 6 times the tradesize diameter of the largest raceway, this distance being increased by the sum of the trade size diameters of the other raceways on the same wall of the box and have a distance between the nearest edges of each raceway enclosing the same conductor of at least 6 times the trade size diameter of the raceway or 6 times the trade size diameter of the larger raceway if they are of different sizes. K. Install outlet boxes as per sizes indicated on the drawings and in the specifications. 3.7 SUPPORTING DEVICES A. Hangers and Supports: 1. Provide steel angles, channels and other materials necessary for the proper support of wallmounted cabinets, racks, panels, etc. 2. Cabinets, large pull boxes, and cable support boxes shall be secured to ceiling and floor slab and not supported from conduits. Small equipment boxes, etc., as approved by Owner's Representative, may be supported on walls. Racks for support of conduit and heavy equipment shall be secured to building construction by substantial structural supports. 3.8 FURNITURE RACEWAYS A. Furniture Pathways Shall comply with UL 1286 and NEC Article 605. ARCHITECHNOLOGY CORNELL – NCP COMMUNICATIONS SYSTEM PATHWAYS STANDARD SPECIFICATIONS 27 05 28 – PAGE 20 OF 20 JUNE 29, 2012 B. It shall be the contractors responsibility to verify the furniture layout and communication outlet with respect to the furniture. Obtain approved shop drawings from the architect detailing furniture heights, cable openings etc.. Prior to roughing in the outlet box verify height and location for all communication outlets near furniture or cabinetry. Boxes roughed in the wrong location shall be relocated at the contractors expense. C. Provide a concealed transition from outlet box to furniture. 3.9 GENERAL A. Support raceways from building construction. Do not support raceways from ductwork, piping, or equipment hangers. B. Support outlet, pull, and junction boxes independently from building construction. Do not support from raceways. C. Coordinate all raceway runs with other trades. D. All open raceways shall be installed a minimum of 6 in. away from any light fixture or other source of EMI (Electromagnetic interference). E. All horizontal pathways shall be bonded and grounded per the NEC Article 250. F. In all cases horizontal pathways shall be sized for a minimum of 50% future growth. END OF SECTION ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 1 OF 23 JUNE 29, 2012 SECTION 27 05 53 TESTING, IDENTIFICATION AND ADMINISTRATION PART 1– GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, tools, and equipment required for the complete installation of work called for in the Contract Documents 1.2 SCOPE A. This section includes the minimum requirements for the testing, certification administration and identification of backbone and horizontal cabling. B. This section includes minimum requirements for the following: 1. Contractor Qualifications 2. Tester Calibrations / Factory Requirements 3. UTP testing and testers 4. Labels and labeling 5. Reports 6. Documentation 7. Record Copy and As9Builts 8. Test and Acceptance 9. Warranty 1.3 QUALITY ASSURANCE A. All testing procedures, testers and identification and administration work specified shall comply with applicable requirements of: 1. ANSI/TIA/EIA – 6069A Administration Standards. 2. ANSI/TIA/EIA – 569A Pathway and Spaces 3. ANSI/TIA/EIA – 5689C.0 Generic Telecommunications Cabling For Customer Premises 4. ANSI/TIA/EIA – 5689B.2 Balanced Twisted9Pair Cabling Components and Testing ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 2 OF 23 JUN 29, 2012 ` 5. ANSI/TIA/EIA – 5689B.3 Optical Fiber Cabling Component Standard and Testing 6. 7. ANSI/TIA/EIA – 5269x Standard Test Procedures for Fiber Optic Systems 8. ANSI/TIA/EIA – 526914A Power Loss Measurements of Install Multimode Fiber Cable Plant 9. ANSI/TIA/EIA – 52697 Measurement of Optical Loss of Installed Singlemode Fiber Cable Plant 10. ANSI/TIA/EIA – 5989A Optical Fiber Cable Color Coding 11. ANSI/TIA/EIA – 5049x FOCIS x Documents for Fiber Optic Connector Intermateability Standards 12. TIA/EIA9J9STD9037 Commercial Building Grounding (Earthing) and Bonding Requirements for Telecommunications 13. ISO/IEC 11801 Information Technology 9 Generic Cabling for Customer Premises 14. BICSI TDMM Telecommunications Distribution Methods Manual, current edition 1.4 SUBMITTALS A. Manufacturers catalog sheets and specifications for each cable testers, test heads and adapter cords and latest version of software applicable for each tester planned for use. B. Provide written factory calibration recommendation letter and factory recommended field calibration intervals with bid. C. Provide signed manufacturer factory calibration certification for each copper and fiber tester owned at time of bid response as a submittal. Certification shall have serial number, date and version of software of each tester. D. For each UTP field tester planned for use on this project, provide a letter from the tester manufacturer and the connectivity/cable manufacturers indicating compatibility and compliance to Category 6 permanent link and the Category 6, channel tests with the products identified for use on this project and the warranty requirements called for by the manufacturers. Contractor shall provide testers and equipment that fully conform to Panduit’s testing requirements for system warranty as specified in the Approved Category 6 Test Lead/Cord Adapters document, at: http://www.panduit.com/products/SpecificationGuides/068804.pdf ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 3 OF 23 JUN 29, 2012 ` E. Sample documentation from previous job for administration, test results and as9built drawings. F. At time of testing, provide a factory calibration certificate for each tester used and include these in each test report binder at the completion of the project. G. Test reports (submit prior to substantial completion punch list is performed) H. Two copies on compact disks containing all summary reports, full plot data test results, tester software tools required to view and inspect and print any selection of the test reports, spreadsheets, end to end reports and as built drawings called for at the completion of job.. The database for the completed job shall be stored and delivered on CD9ROM including the software tools required to view, inspect, and print any selection of test reports. I. Technician certificates for successful completion of training for each of the field testers proposed to be used in this project. J. Two copies in binder format and two copies on compact disks containing all digital photographs called for at the completion of the job. K. Refer to Section 01340 – “Shop Drawings, Product Data” and 27 05 00 for additional requirements. PART 2 9 PRODUCTS 2.1 VERIZON CIRCUIT IDENTIFICATION AND TESTING A. Not Included in this project 2.2 OPTICAL FIBER CABLE A. Field test instruments for multimode fiber cabling shall meet the requirements of ANSI/TIA/EIA95269149A. B. Field test instruments for multimode fiber cabling shall meet the requirements of ANSI/TIA/EIA952697. C. Multimode optical fiber light source 1. Provide 850nm and 1300nm +/9 20 nm wavelength LED light sources 2. Spectral width of sources shall be </= 50nm for 850nm wavelengths and </= 140nm for 1300nm wavelengths. 3. The output of the light source shall be 8 MW for 62.5um core optical fiber ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 4 OF 23 JUN 29, 2012 ` 4. Output Stability +/9 0.40 dB from 0 to 50 degrees C 5. Long Term output stability +/9 0.10dB at 25 degrees C 6. Power shall be from rechargeable Ni9Cad batteries 7. Connector types shall include: SMA, FC, ST and SC 8. Design make: Siecor Light source 9. Acceptable Manufacturers: a) Fluke b) Wavetek c) Lantek d) AMP NetConnect e) Corning Cable Systems D. Single mode optical fiber light source 1. Provide 1300nm and 1500nm +/9 20 nm wavelength Laser light sources 2. Output Stability +/9 0.40 dB from 0 to 50 degrees C 3. Long Term output stability +/9 0.10dB at 25 degrees C 4. Power shall be from rechargeable Ni9Cad batteries 5. Connector types shall include: SMA, FC, ST and SC 6. Design make: Siecor OS9200D 7. Acceptable Manufacturers: a) Fluke b) Meson c) AMP NetConnect d) Corning Cable Systems E. Optical Power Meter 1. Calibrates against the National Institute of Standards and Technology (NIST) standard. 2. Provide 850nm, 1300nm and 1500nm +/9 20 nm wavelength test capability 3. Measurement range shall be from 10 to 960 dBm ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 5 OF 23 JUN 29, 2012 ` 4. Accuracy shall be +/9 5% at 0 to 950dBm and +/9 10% 10 to 0dBm and 950 to960 dBm. 5. Resolution shall be 0.1 dB 6. Connector types shall include: SMA, FC, ST and SC 7. Design make: Siecor OM9100F 8. Acceptable Manufacturers: a) Fluke b) Meson c) AMP NetConnect d) Corning Cable Systems F. Optical Time Domain Reflectometer (OTDR) 1. Dual selectable wavelength: 850/1300 nm for multimode 2. Dual selectable wavelength: 1310/1550 nm for singlemode 3. Selectable cable index of refraction. 4. Visual fault locator for continuity checks and dead zone fault protection. 5. Display and printer connection for hard9copy documentation 6. Equipped with launch jumper cable of sufficient length to offset entry” deadzone”. 2.3 100 OHM UTP TEST EQUIPMENT A. GENERAL 1. Field test instruments shall meet the requirements of ANSI/TIA/EIA95689B.2 Annex B and Annex I. 2. Test equipment used under this contract shall be from manufacturers that have a minimum of 5 years experience in producing field test equipment. 3. Manufacturers must be ISO 9001 certified. 4. All test tools of a given type shall be from the same manufacturer, and have compatible electronic results output. 5. Test adapter cables/test heads must be approved by the manufacturer of the test ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 6 OF 23 JUN 29, 2012 ` equipment, for the specific cable and connectivity product used on this project. Adapters from other sources are not acceptable. Obtain written confirmation that the test heads and adapter planned fro use are proper and also obtain a written confirmation from the wire and connectivity manufactures that they also agree with the test heads and adapter selection chosen by the tester manufacturer. 6. Baseline accuracy of the test equipment must exceed TIA Level IIIe, as indicated by independent laboratory testing. 7. A level IIIe test unit is required to verify category 6 performance for both Category 6 permanent link and channel performance. 8. Test equipment must be capable of certifying Category 5, 5e, and 6 links. 9. Test equipment must have a dynamic range of at least 100 dB to minimize measurement uncertainty. 10. Test equipment must be capable of storing full frequency sweep data for all tests and printing color graphical reports for all swept measurements. 11. Test equipment must include S9Band time domain diagnostics for NEXT and return loss (TDNXT and TDRL) for accurate and efficient troubleshooting. 12. Test equipment must be capable of running individual NEXT, return loss, etc measurements in addition to autotests. Individual tests increase productivity when diagnosing faults. 13. Test equipment must include a library of cable types by major manufacturer. 14. Test equipment must store at least 1000 Category 6 or 6 autotests in internal memory. 15. Test equipment must be able to internally group autotests and cables in project folders for good records management. 16. Test equipment must include technology for support of advanced measurements. 17. Test equipment must make swept frequency measurements in compliance with TIA standards. 18. The measurement reference plane of the test equipment shall start immediately at the output of the test equipment interface connector. There shall not be a time domain dead zone of any distance that excludes any part of the link from the measurement. 19. The basic tests required are: ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 7 OF 23 JUN 29, 2012 ` a) · Wire Map b) · Length c) · Attenuation d) · NEXT (Near end crosstalk) e) · Return Loss f) · ELFEXT Loss g) · Propagation Delay h) · Delay skew i) · PSNEXT (Power sum near9end crosstalk loss) j) · PSELFEXT (Power sum equal level far9end crosstalk loss) 20. Shall be able to test cable for compliance with all of the following standards: a) TIA Category 6: Permanent Link and Channel b) ISO/IEC 11801 and EN 50173 Class C, D and E: Link c) ISO/IEC 11801 and EN 50173 Class C, D and E: Permanent Link or Channel d) Aus/NZ Class C and D: Basic Link or Channel e) STP cabling, (IBM Type 1, 150 ohm) f) ANSI TP9PMD IEEE 802.3 10BASE5, 10BASE2: Ethernet with coaxial cabling g) IEEE 802.3 10BASE9T, 100BASE9TX, 1000BASE9T: Ethernet with twisted pair cabling IEEE 802.5: Token Ring, 4 Mbps or 16 Mbps 21. Shall perform the following tests as a minimum: a) NEXT, NEXT @ Remote b) Wire Map c) Characteristic Impedance d) Length e) DC Loop Resistance f) Propagation Delay Return Loss (RL), RL @ Remote g) Delay Skew h) Attenuation i) Attenuation9to9Crosstalk Ratio (ACR), ACR @ Remote j) Power Sum ACR, PSACR @ Remote k) ELFEXT, ELFEXT @ Remote l) Power Sum ELFEXT, PSELFEXT @ Remote m) Power Sum NEXT, PSNEXT @ Remote 22. Shall use injector for complete wire mapping and TDR for determining cable length. 23. Shall measure NEXT for all six pair combinations and Attenuation on all four pairs from 1.0 to 350 MHz. 24. Design Make: Fluke “DSP 4000 or 4300 series” ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 8 OF 23 JUN 29, 2012 ` 25. Acceptable Manufacturers: a) Agilent b) WaveTek c) Lantek d) Wirescope 2.4 LABELS A. Shall meet the legibility, defacement, exposure and adhesion requirements of UL 969. B. Shall be preprinted or laser printed type. Handwritten labels are not acceptable. C. Where used for cable marking provide vinyl substrate with a white printing area and a clear “tail” that self laminates the printed area when wrapped around the cable. If cable jacket is white, provide cable label with printing area that is any other color than white, preferably orange or yellow – so that the labels are easily distinguishable. D. Where insert type labels are used provide clear plastic cover over label. Acceptable Manufacturers: 1. WH Brady 2. Panduit 3. Ideal: PART 3 9 EXECUTION 3.1 COPPER CABLE TEST A. A level IIIe test unit is required to verify category 6 performances, shall be updated with the latest version of tester software at time of testing and shall be factory tested/calibrated within one of time of testing. Provide copies of factory certification for each tester owned at time of bid response as a submittal. At time of testing, provide a factory calibration certificate for tester used and include these in each test report binder at the completion of the project. B Visually inspect all cables, cable reels, and shipping cartons to detect possible cable damage incurred during shipping and transport. Visibly damaged goods are to be returned to the supplier and replaced at no additional cost to the Owner. C. If post9manufacture performance data has been supplied by the manufacturer of cables or connecting hardware, copies of such data are to be kept for inclusion in the Documentation for final Record Copy deliverables and made available to the Owner upon request. ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 9 OF 23 JUN 29, 2012 ` D. Test 100% of installed backbone copper cabling for 1. Wire Map 2. Length E. Provide documentation in hardcopy and electronic formats, organized the same as outlined in 27 05 53, Sections 3.5.W “Third Party Verification” and Section 3.6 “Test Documentation” of this section. 3.2 OPTICAL FIBER CABLE TESTING A. All fiber testing shall be performed on all fibers in the completed end to end system. B. Comply with Tier9two testing as defined in TSB9140. which included loss and length testing with an optical loss test set (OLTS) and also an OTDR trace of the installed cable plant. By incorporating the proposed two9tier testing method, installers have the most complete picture of the fiber installation and network owners have proof of a quality installation C. Testing shall consist of an end to end power meter test performed per EIA/TIA94559 53A. The system loss measurements shall be provided at 850 and/or 1300 nanometers for multimode fibers and 1310 and/or 1550 nanometers for single mode fibers. These tests also include continuity checking of each fiber. D. There shall be no splices unless clearly called for. E. Test all fibers with launch and far end cable of sufficient length for the OTDR to be able to see through all installed connectors. F. Localized attenuation shall not exceed 0.5 dB at any point. G. Backbone multimode fiber shall be tested in one direction at both 850nm and 1300 nm in accordance with ANSI/EIA/TIA9526914A method B. H. Backbone single mode fiber shall be tested in one direction at both 1310nm and 1550. I. For horizontal cabling system using multimode optical fiber, attenuation shall be measured in one direction at either 850 nanometer (nm) or 1300 nm using an LED light source and power meter. J. Backbone multimode fiber cabling shall be tested at both 850 nm and 1300 nm (or 1310 and 1550 nm for singlemode) in one direction. K. Test set9up and performance shall be conducted in accordance with ANSI/EIA/TIA9 526914 Standard, Method B. L. Where links are combined to complete a circuit between devices, the Contractor shall test each link from end to end to ensure the performance of the system. ONLY BASIC LINK TEST IS REQUIRED. The contractor can optionally install patch ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 10 OF 23 JUN 29, 2012 ` cords to complete the circuit and then test the entire channel. The test method shall be the same used for the test described above. The values for calculating loss shall be those defined in the ANSI/TIA/EIA Standard. M. Attenuation testing shall be performed with a stable launch condition using two9meter jumpers to attach the test equipment to the cable plant. The light source shall be left in place after calibration and the power meter moved to the far end to take measurements. N. Backbone Cable 1. Test the cable on the reel for continuity before installing it, to insure no damage was done in shipment from the manufacturer to the job site. 2. After installation and termination, test each segment of the cable plant individually as it is installed, to insure each connector and cable is good. 3. Link attenuation is the only required field test except for the patched runs in the campus backbone system where an OTDR test will be required. Use launch cables at each end and provide print outs showing all connectors. OTDR will also be required to determine bad connections or damage when the link attenuation test fails. 4. Maximum localized attenuation allowed is 2dB. 5. Backbone multimode fiber shall be tested in one direction at both 850nm and 1300 nm in accordance with ANSI/EIA/TIA9526914A method B. 6. Backbone single mode fiber shall be tested in one direction at both 1310nm and 1550 nm in accordance with ANSI/EIA/TIA9526914A method A.1. 7. Multimode fiber shall conform to the following: 850 nm: Length (meters) Attenuation ( dB) 500 3.5 1000 5.5 1500 7.5 2000 9.0 1300 nm: Length (meters) Attenuation ( dB) 500 2.2 1000 3.0 1500 3.8 2000 4.5 ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 11 OF 23 JUN 29, 2012 ` 8. Single Mode Fiber shall conform to the following (note: taken at 1550nm) Inside: Length (meters) Attenuation ( dB) 500 2.0 1000 2.5 1500 3.0 2000 3.5 2500 4.0 3000 4.5 Outside: Length (meters) Attenuation ( dB) 500 1.8 1000 2.0 1500 2.2 2000 2.5 2500 2.8 3000 3.0 O. Documentation 1. Provide attenuation and cable length test results for all installed cable pairs. 3.3 TEST REPORTS A. Provide documentation in hardcopy and electronic formats, organized the same as outlined in 27 05 53, Sections 3.5.W “Data Reporting and Accuracy” and Section 3.6 “Test Documentation” of this section. 3.4 100 OHM UTP CABLE TESTING GENERAL A. Every cabling link shall be tested in accordance with the field test specifications defined in ANSI/TIA/EIA95689B.291 “Transmission Performance Specifications for 49pair 100Ω Category 6 Cabling and as defined in the Manufacturer warranty requirements. Refer to item 1.4 submittals for additional information. B. Trained technicians who have successfully attended an appropriate training program and have obtained a certificate as proof thereof shall execute the tests. C. The test equipment shall comply with the accuracy requirements for level IIIe field testers as defined in ANSI/TIA/EIA95689B.291. The tester including the appropriate interface adapter must meet the specified accuracy requirements. The accuracy requirements for the permanent link test configuration (baseline accuracy plus adapter contribution) are specified in Table B.2 of Annex B of the TIA Cat 6 Standard. (Table ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 12 OF 23 JUN 29, 2012 ` B.3 in this TIA document specifies the accuracy requirements for the Channel configuration. D. The tester shall be within the calibration period recommended by the vendor in order to achieve the vendor9specified measurement accuracy. E. The tester interface adapters must be of high quality and the cable shall not show any twisting or kinking resulting from coiling and storing of the tester interface adapters. In order to deliver optimum accuracy, preference is given to a permanent link interface adapter for the tester that can be calibrated to extend the reference plane of the Return Loss measurement to the permanent link interface. The contractor shall provide proof that the interface has been calibrated within the period recommended by the vendor. To ensure that normal handling on the job does not cause measurable Return Loss change, the adapter cord cable shall not be of twisted9pair construction. F. A Pass or Fail result for each parameter is determined by comparing the measured values with the specified test limits for that parameter. The test result of a parameter shall be marked with an asterisk (*) when the result is closer to the test limit than the accuracy of the field tester. The field tester manufacturer must provide documentation as an aid to interpret results marked with asterisks. G. All cables and termination hardware shall be 100% tested for defects in installation and to verify cabling system performance under installed conditions according to the requirements of ANSI/TIA/EIA95689B. H. All pairs of each installed cable shall be verified prior to system acceptance. Any defect in the cabling system installation including but not limited to cable, connectors, feed through couplers, patch panels, and connector blocks shall be repaired or replaced in order to ensure 100% useable conductors in all cables installed. The testing parameters called for in this section shall apply for up to 90 meters of horizontal cable, a work area equipment cord, an RJ45 outlet and 2 cross connect connections in the closet. The test parameters shall include Wire Map, Length, Attenuation and NEXT Wire Map 1. The wire map test shall verify pair to pin termination at each end and check for connectivity errors. Wire Map shall report Pass if the wiring of each wire9 pair from end to end is determined to be correct. The Wire Map results shall include the continuity of the shield connection if present The wire map shall indicate the following for each of the eight conductors: a) Continuity to the remote end b) Shorts between any two or more conductors c) Crossed pairs d) Reversed Pairs e) Split Pairs ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 13 OF 23 JUN 29, 2012 ` f) Any other miswiring Cable Length The field tester shall be capable of measuring length of all pairs of a basic link or channel based on the propagation delay measurement and the average value for NVP. The physical length of the link shall be calculated using the pair with the shortest electrical delay. This length figure shall be reported and shall be used for making the Pass/Fail decision. The Pass/Fail criteria are based on the maximum length allowed for the Permanent Link configuration (90 meters – 295 feet) plus 10% to allow for the variation and uncertainty of NVP. 2. The set9up configuration of the NVP shall be based solely on the NVP value of the cable specified in the approved cable submittal for this project. Insulation characteristics and twist rate of the wire pair influence NVP in minor ways and is dependent on the specific manufacturer. Typically, an ‘average’ value for NVP is published for all four wire9pairs in a data cable. Insertion Loss (Attenuation) Insertion Loss is a measure of signal loss in the permanent link or channel. The term “Attenuation” has been used to designate “Insertion Loss.” Insertion Loss shall be tested from 1 MHz through 250 MHz in maximum step size of 1 MHz. It is preferred to measure insertion loss at the same frequency intervals as NEXT Loss in order to provide a more accurate calculation of the Attenuation9to9Crosstalk ratio (ACR) parameter. Minimum test result documentation (summary report and full plot data, in format and quantities called for): Identify the worst wire pair (1 of 4 possible). The test results for the worst wire pair must show the highest attenuation value measured (worst case), the frequency at which this worst case value occurs, and the test limit value at this frequency. NEXT Loss Pair9to9pair near9end crosstalk loss (abbreviated as NEXT Loss) shall be tested for each wire pair combination from each end of the link (a total of 12 pair combinations). This parameter is to be measured from 1 through 250 MHz. NEXT Loss measures the crosstalk disturbance on a wire pair at the end from which the disturbance signal is transmitted (near9end) on the disturbing pair. The maximum step size for NEXT Loss measurements shall not exceed the maximum step size defined in the standard as shown in Table 1, column 2. 3. Minimum test results documentation (summary report and full plot data, in format and quantities called for): Identify the wire pair combination that exhibits the worst case NEXT margin and the wire pair combination that exhibits the worst value of NEXT (worst case). ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 14 OF 23 JUN 29, 2012 ` 4. NEXT is to be measured from each end of the link9under9test. These wire pair combinations must be identified for the tests performed from each end. Each reported case should include the frequency at which it occurs as well as the test limit value at this frequency. Frequency Range (MHz) Maximum Step Sixe (MHz) 1 – 31.25 0.15 31.26 – 100 0.25 100 – 250 0.50 250 9 350 1.00 TABLE 1 PSNEXT Loss Power Sum NEXT Loss shall be evaluated and reported for each wire pair from both ends of the link under9test (a total of eight results). PSNEXT Loss captures the combined near9end crosstalk effect (statistical) on a wire pair when all other pairs actively transmit signals. Like NEXT this test parameter must be evaluated from 1 through 250 MHz and the step size may not exceed the maximum step size defined in the standard as shown in Table 1, column 2. Minimum test results documentation (summary report and full plot data, in format and quantities called for): Identify the wire pair that exhibits the worst9case margin and the wire pair that exhibits the worst value for PSNEXT. These wire pairs must be identified for the tests performed from each end. Each reported case should include the frequency at which it occurs as well as the test limit value at this frequency. ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 15 OF 23 JUN 29, 2012 ` ELFEXT Loss, pair to pair Pair9to9pair FEXT Loss shall be measured for each wire9pair combination from both ends of the link under9test. FEXT Loss measures the crosstalk disturbance on a wire pair at the opposite end (far9end) from which the transmitter emits the disturbing signal on the disturbing pair. FEXT is measured to compute ELFEXT Loss that must be evaluated and reported in the test results. ELFEXT measures the relative strength of the far9end crosstalk disturbance relative to the attenuated signal that arrives at the end of the link. This test yields 24 wire pair combinations. ELFEXT is to be measured from 1 through 250 MHz and the maximum step size for FEXT Loss measurements shall not exceed the maximum step size defined in the standard as in Table 1, column 2. Minimum test results documentation (summary report and full plot data, in format and quantities called for): Identify the wire pair combination that exhibits the worst9case margin and the wire pair combination that exhibits the worst value for ELFEXT. These wire pairs must be identified for the tests performed from each end. Each reported case should include the frequency at which it occurs as well as the test limit value at this frequency. PSELFEXT Loss Power Sum ELFEXT is a calculated parameter that combines the effect of the FEXT disturbance from three wire pairs on the fourth one. This test yields eight wire9pair combinations. Each wire9pair is evaluated from 1 through 250 MHz in frequency increments that do not exceed the maximum step size defined in the standard as shown in Table 1, column 2. Minimum test results documentation (summary report and full plot data, in format and quantities called for):): Identify the wire pair that exhibits the worst pair combinations must be identified for the tests performed from each end. Each reported case should include the frequency at which it occurs as well as the test limit value at this frequency. Return Loss Return Loss (RL) measures the total energy reflected on each wire pair. Return Loss is to be measured from both ends of the link9under9test for each wire pair. This parameter is also to be measured form 1 through 250 MHz in frequency increments that do not exceed the maximum step size defined in the standard as shown in Table 1, column 2. Minimum test results documentation (summary report and full plot data, in format and quantities called for): Identify the wire pair that exhibits the worst9case margin and the wire pair that exhibits the worst value for Return Loss. These wire pairs must be identified for the tests performed from each end. Each reported case should include ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 16 OF 23 JUN 29, 2012 ` the frequency at which it occurs as well as the test limit value at this frequency ACR (Attention to crosstalk ratio) This parameter is not demanded by the standard but may be required in order to obtain the premise wiring manufacturer’s warranty]. ACR provides an indication of bandwidth for the two wire9pair network applications. ACR is a computed parameter that is analogous to ELFEXT and expresses the signal to noise ratio for a two wire9 pair system. This calculation yields 12 combinations – six from each end of the link. Minimum test results documentation (summary results): Identify the wire pair combination that exhibits the worst9case margin and the wire pair combination that exhibits the worst value for ACR. These wire pair combinations must be identified for the tests performed from each end. Each reported case should include the frequency at which it occurs as well as the test limit value at this frequency PSACR NOTE: This parameter is not required by the standard but may be required in order to obtain the premise wiring vendor’s warranty. Provide as required for Manufacturer Warranty. The Power Sum version of ACR is based on PSNEXT and takes into account the combined NEXT disturbance of all adjacent wire pairs on each individual pair. This calculation yields eight combinations –one for each wire pair from both ends of the link. Minimum test results documentation (summary results): Identify the wire pair that exhibits the worst9case margin and the wire pair that exhibits the worst value for PSACR. These wire pairs must be identified for the tests performed from each end. Each reported case should include the frequency at which it occurs as well as the test limit value at this frequency. Propagation Delay Propagation delay is the time required for the signal to travel from one of the link to the other. This measurement is to be performed for each of the four wire pairs. Minimum test results documentation (summary report and full plot data, in format and quantities called for): Identify the wire pair with the worst9case propagation delay. The report shall include the propagation delay value measured as well as the test limit value Delay Skew (as defined in TIA/EIA95689B.1; Section 11.2.4.11) This parameter shows the difference in propagation delay between the four wire pairs. The pair with the shortest propagation delay is the reference pair with a delay skew value of zero. ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 17 OF 23 JUN 29, 2012 ` Minimum test results documentation (summary report and full plot data, in format and quantities called for): Identify the wire pair with the worst9case propagation delay (the longest propagation delay). The report shall include the delay skew value measured as well as the test limit value. DATA REPORTING AND ACCURACY The test results information for each link shall be recorded in the memory of the field tester upon completion of the test. The test results records saved by the tester shall be transferred into a Windows™9 based database utility that allows for the maintenance, inspection and archiving of these test records. A guarantee must be made that the measurement results are transferred to the PC unaltered, i.e., “as saved in the tester” at the end of each test and that these results cannot be modified at a later time. The database for the completed job shall be stored and delivered on CD9ROM including the software tools required to view, inspect, organized, manage and print any selection of test reports. The detailed test result data to be provided in the electronic database for each tested link must contain the frequency9dependent test parameters, the value measured at every frequency during the test is stored. The PC9 resident database program must be able to process the stored results to display and print a color graph of the measured parameters. The PC9resident software must also provide a summary numeric format in which some critical information is provided numerically as defined by the summary results (minimum numeric test results documentation) as outlined above for each of the test parameters. A paper copy of the test results shall be provided that lists all the links that have been tested with the following SUMMARY REPORT information: a) The identification of the link in accordance with the naming convention defined in the overall system documentation b) The overall Pass/Fail evaluation of the link9under9test including the NEXT Headroom (overall worst case) number c) The date and time the test results were saved in the memory of the tester 5. General Information to be provided in the electronic data base with the test results information for each link: a) The identification of the customer site as specified by the end9user b) The identification of the link in accordance with the naming convention defined in the overall system documentation c) The overall Pass/Fail evaluation of the link9under9test d) The name of the standard selected to execute the stored test results e) The cable type and the value of NVP used for length calculations ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 18 OF 23 JUN 29, 2012 ` f) The date and time the test results were saved in the memory of the tester g) The brand name, model and serial number of the tester h) The identification of the tester interface i) The revision of the tester software and the revision of the test standards database in the tester j) The test results information must contain the information on each of the required test parameters listed in this section of the specifications 6. General: a Pass or Fail result for each parameter shall be determined by the allowable limits for each parameter. If the test result of a parameter is closer to the test limit than the accuracy of the tester it shall be marked with an asterisk. Data at all measured points shall be uploaded to a P.C. and printed on a laser printer. 7. Wire Map: Wire map tests shall be marked “Pass” if wiring is determined correct. 8. Length: Test results shall be provided in meters and marked “Pass or Fail” based on the length vs. allowable length. 9. Submit copies in binder format and on compact disks containing all summary reports, full plot data test results, tester software tools required to view and inspect and print any selection of the test reports, spreadsheets, end to end reports and as built drawings called for at the completion of job. 3.5 THIRD PARTY VERIFICATION A. Owner’s representative shall be invited to witness field testing. The representative shall be notified of the start date of the testing phase 5 business days before testing commences. B. Owner’s representative may select a random sample of 1% of the installed links. The representative (or his authorized delegate) shall test these randomly selected links and the results are to be stored as called for in this section. The results obtained shall be compared to the data provided by the installation contractor. If more than 2% of the sample results differ in terms of the pass/fail determination, the installation contractor under supervision of the Owner’s representative shall repeat 100% testing and the cost shall be borne by the installation contractor. 3.6 TEST DOCUMENTATION A. Provide test report documentation in a hard copy summary report, by TR, in a three9 ring binder, within 1 week prior to cutover of any phase of the project. Provide full plot data for any failures and any marginal passes and place yellow posted note affixed to each related printed page of the binder for review with Owner. Correct any deficiencies as direct by the Owner. ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 19 OF 23 JUN 29, 2012 ` B. The three9ring binder shall be clearly marked on the outside front cover and spine with the words “Test Results”, the project name, building name, Cornell assigned facility code number, the date of completion (month and year) and the Contractors name and address. A tab shall be provided for each TR and the test results organized by TR. The test reports in each TR tabbed section shall be sorted (before printing) by Patch Panel and port for each TR. C. Provide two CD’s with summary report, full plot data, test report within 1 week after the completion of the project. The disks shall placed into CD sleeves and placed into a three9ring binder clearly marked on the outside front cover and spine with the words “Test Results”, the project name, building name, Cornell assigned facility code number the date of completion (month and year) and the Contractors name and address. The electronic test results shall be sorted by TR into proper folders to match the heading of tabs in the tree ring binders. Also include in the binder, the summary information provided in A. above and the full plot data for any previous failures or marginal passes that have been corrected – with an explanation of the corrective action and the signature of the technician and the foreman. D. The binder and electronic folder/files shall divided by major heading tabs (or in the case of electronic files, be placed into a folders structure similar to the hardcopy tests of this section). E. Major heading tabs (folders) shall be divided into Horizontal and Backbone (both fiber and copper backbone). Each shall be further sectioned by test type and by TR and rack as applicable. F. For copper backbone, test all terminated, spliced, relocated or transferred pairs – two weeks before intended cutover. Test all pairs, end9to9end and record hand written results on the test sheet provided on the last page of this section. Coordinate access to the Central Office end of the backbone cable for end9to9end testing, as required, 1 week in advance with the CIT project manager. Correct deficiencies as directed by Owner and provide a minimum of 99% good pairs, for backbone cables.\ G. Provide updated cable schedules with all deviations, including all change order, field authorizations, moves, adds and changes. Include all cable ID changes, panel and port changes in each TR, room number changes, etc. 3.7 IDENTIFICATION & RECORDS A. Confirm specific labeling requirements with customer’s project manager prior cable installation or termination, even if detailed in the T4 drawings. 1. Pathways (a) Coordinate and identify all communication pullboxes per 27 05 28. 2. TR Rooms and Equipment Spaces ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 20 OF 23 JUN 29, 2012 ` (a) Coordinate and identify all communication racks and cabinet using a Letter designation (A,B,C etc.) as called on the T3 plans. (b) Coordinate and identify all communication patch panels using a Letter designation (A,B,C etc.) as called on the T3 plans and the cable schedules or as directed by the Owner (c) Coordinate and identify all voice patch panels using descriptor as designated by the Owner. These typically involved designators such as VPP9A, etc. 3. Cables (a) Label cables using the conventions identified in the cable schedules. The contractor shall review all labeling requirements before cable rough9in begins. (b) Provide written records in computer generated, table format for all cables, with the as9built drawings. (c) Update or generate cable schedules for all cable installed. (d) Update T2 drawings to reflect all field modifications and change orders. 4. Optical Fiber (a) Provide laser printed label for each fiber cable at the BDF, as directed by Owner. (b) The label shall be identical at both ends. 5. Station Outlets (a) Provide TIA 6069A compliant insert with clear plastic label cover on faceplates. Orient label and text per horizontal or vertical plate orientation and provide the maximum font size allowable. Align cable ID with specific modular jack and provide maximum fonts sizes and spacing between ID’s on the same label to provide desired alignment. (b) Provide a machine generated, preferably a laser printed, label in the insert. ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 21 OF 23 JUN 29, 2012 ` (c) Labels shall match the cable identifier called for on the drawings, cable schedules and as depicted in the detail faceplate and outlet drawings. ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 22 OF 23 JUN 29, 2012 ` Project Site: __________________________________ 1.1 BACKBONE COOPER CABLE TEST RECORD Date of test: ________________ Project Manager: _________________________ Cable Number:________Cable Count:_______From:_____________________To:____________________ Tested From:__________________________Tested To:____________________________(end locations) Testing Company:______________________________Technician:_____________________________ Splicing Company:_____________________________Cable Placement Company:__________________________ BACKBONE CABLING Pair Color Pair # Test Results Pair # Test Results Pair # Test Results Pair # Test Results BL9W ______01 26 51 76 O9W 2 27 52 77 GR9W 3 28 53 78 BR9W 4 29 54 79 SL9W 5 30 55 80 BL9R 6 31 56 81 O9R 7 32 57 82 GR9R 8 33 58 83 BR9R 9 34 59 84 SL9R 10 35 60 85 BL9BK 11 36 61 86 O9BK 12 37 62 87 GR9BK 13 38 63 88 BR9BK 14 39 64 89 SL9BK 15 40 65 90 BL9Y 16 41 66 91 O9Y 17 42 67 92 GR9Y 18 43 68 93 BR9Y 19 44 69 94 SL9Y 20 45 70 95 BL9V 21 46 71 96 O9V 22 47 72 97 GR9V 23 48 73 98 BR9V 24 49 74 99 SL9V 25 50 75 _____00 ARCHITECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 23 OF 23 JUN 29, 2012 ` END OF SECTION TEST RESULTS – Abbreviations to use in the columns above: 1) Pair is Good = OK 5) Tip Ground =T.G. 2) Ring Side Open =R.S.O. 6) Shorted Pair =S.P. 3) Tip Side Open =T.S.O. 7) Split Pair=SPL (ex. For tip side of #5 and #17 =T.of#5w/T. of #17 4) Ring Ground =R.G. 8) Reverse Sides =REV ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 1 OF 18 JUNE 29, 2012 SECTION 27 11 00 TELECOMMUNICATION ROOMS AND SPACES PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, tools, and equipment required for the complete installation of work called for in the Contract Documents. B. This section includes the minimum requirements for equipment and cable installations in telecommunication rooms (TRs). The following equipment is described in this section: 1. Floor Mounted Racks 2. Equipment Shelves 3. Cable Management 4. Fiber Patch Panels 5. Patch Panels 6. Termination Blocks 7. Cable Runway 8. Cable Supports 9. Grounding and Bonding 10. Hook and Loop Wraps 11. Power Strips 12. Firestop 13. PVC=25 pair rack interconnect cable C. If this document and any of the documents listed above are in conflict, then the more stringent requirement shall apply. All documents listed are believed to be the most current releases of the documents. The Contractor has the responsibility to determine and adhere to the most recent release when developing the proposal for installation. D. This document does not replace any code, either partially or wholly. The contractor must be aware of local codes that may impact this project. ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 2 OF 18 JUNE 29, 2012 1.2 QUALITY ASSURANCE A. All equipment rooms shall be installed in a neat and workmanlike manner. All methods of construction that are not specifically described or indicated in the Contract Documents shall be subject to the control and approval of the Owners representative. Equipment and materials shall be of the quality and manufacture indicated. The equipment specified is based on the acceptable manufacturers listed. Where "approved equal” is stated, equipment shall be equivalent in every way to that of the equipment specified, and subject to approval. B. Materials and work specified herein shall comply with the applicable requirements of: 1. ANSI/TIA=568=C 2. ANSI/NECA/BICSI 568=2006 3. ANSI/TIA=569=B 4. ANSI/TIA=606=A 5. ANSI/TIA=607=B 6. Underwriters Laboratory 7. Federal Communications Commission 8. NFPA 70 – 2002 9. BICSI “Telecommunications Distribution Method Manual”, current edition. 10. NEMA=250 11. EIA 310=D 12. Section 26 05 26. 1.3 1.3 SUBMITTALS A. Provide product data for the following, ONLY if deviating from the exact design make/part number or if a specific part number is not provided in the contract documents. 1. Floor Mounted Racks 2. Cable Management ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 3 OF 18 JUNE 29, 2012 3. Fiber Patch Panels 4. Patch Panels 5. Termination Blocks 6. Cable Runway 7. Cable Supports 8. Grounding and Bonding 9. Hook and Loop Wraps 10. Power Strips 11. Firestop 12. PVC=25 pair rack interconnect cable B. Provide sample faceplate(s) of every style of faceplate planned for this project, in the colors as called for. C. Provide sample surface mounted outlet box(s) planned for this project, to confirm proper mounting and radius control. Coordinate with Division 26. D. `Provide sample labeling from handheld printers owner by contractor or intended to be used on this project, with labels as detailed on the drawings, specified in the cable schedules for each different type of faceplate to be used. Also provide labels for each style patch panel to be used, as detailed on the drawings, specified in the cable schedules for each different type of patch panel to be used (48 port UTP, 24 port UTP, and fiber patch panels) E. Also refer to Refer to Section 01 33 00 – Submittal Procedures. PART 2 PRODUCTS 2.1 FLOOR MOUNTED RACKS A. Racks shall meet the following physical specifications: 1. 19” rack mounting space. 2. 7 foot high. 3. Aluminum construction, factory paint black in color. 4. 15” deep base with four (4) ¾” bolt down holes. ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 4 OF 18 JUNE 29, 2012 B. Rack shall have double sided 12/24 tapped holes and 5/8”,5/8”, ½” standard EIA hole pattern. C. Design Make: Chatsworth Products Inc., black D. Acceptable Manufacturers: 1. Panduit 2. B=Line 3. Others as approved by Owner 2.2 CABLE MANAGEMENT A. Provide rack mounted horizontal and vertical cable management for all horizontal, backbone and patch cables. B. Panels shall have front and back channels with hinged covers. C. Cable management panels shall be plastic and have integral wire retaining fingers, radius fingers for maintaining proper bend radius for Category 6 and optical fiber cables. D. Management panels shall mount to any standard 19” rack and include all required mounting brackets and screws. E. Provide 2RU horizontal cable managers, in both open and closed configurations, as called for on the T3 drawings. F. Provide vertical cable manager as shown on the T3 drawings. Provide end panel cap for vertical cable manager furthest from the wall. G. Design Makes: 1. Vertical = Panduit WMPVHC45E, in black, as called for on the T3 drawings. Size: 7'H X 6"W X 13.8"D FRONT/REAR with covers. 2. Vertical = Panduit PRV8, 10 PATCHRUNNER Series, in black, as called for on the T3 drawings. FRONT/REAR. 3. Vertical = Panduit PRSHD8, 10 PATCHRUNNER single metal door, for each PRV Patchrunner, called for on the T3 drawings. Use *” wide version when 2 horizontal racks are side by side. 4. Horizontal Closed Cable Manager = Panduit WMPH2E Series, supplied with removable covers. Two rack units (2RU) in height typical, as called for on the T3 drawings. ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 5 OF 18 JUNE 29, 2012 5. Horizontal Open Cable Manager = Panduit CMPHH2 Series, 3”x5” front only D=ring style, 2RU in height typical, as called for on the T3 drawings. 2.3 FIBER PATCH PANEL A. Shall be rack mounted as called for on the T3 Series rack elevations, program standard detail drawings and T1=FL Series fiber logical riser drawings. B. Shall be constructed with 16 gauge steel. C. Provide adapter panels with duplex SC couplers, mounted in housing, for all fiber cables installed. D. Rack mounted housings shall have splice organizer drawers that are removable or held open at 30 degree angle and translucent latching hinged front cover, as called for. E. Wall mounted housings shall have a lockable hinged door enclosing the cable loop and termination section and a latchable hinged door enclosing the connector section of the housing. F. Organizer drawers and wall mount cabinets shall come complete with routing rings for cable management and cable tie=down bars for support of main cable. G. Shall accommodate 48, 72 or 96 fibers as called for on the T3 drawing rack elevations and drawings. 1. Design make: Design makes: a) Corning Cable Systems Closet Connector Housings #CCH= 04U and #CCH=02U and PCH=01U Series as called for on drawings: T1=FL,T3 and program standard detail drawings. b) Corning Cable Systems 12=Fiber SC Duplex Panels for Multi=Mode strands #CCH=CP12=91 and blank filler panels for unused spaces. c) Corning Cable Systems 12=Fiber SC Duplex Panels for Single=Mode strands #CCH=CP12=59 and blank filler panels for unused spaces. 2.4 PATCH PANELS A. Patch Panels, for Category 6/6A connectivity 1. Physical Characteristics ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 6 OF 18 JUNE 29, 2012 a) Panels shall be made of 16ga cold rolled steel with a black powder coat finish in 24, 48, and 96 port configurations. b) Panels shall accommodate a minimum of 24 ports for each rack mount space (1rms = 44.5 mm [1.75 in.]). c) Panels shall be manufactured with a rolled=edge at the top and bottom for stiffness. d) Panels shall accept Panduit Mini=Com modules for UTP, Optical Fiber, Audio and Video connectivity, which snap in and out for easy moves, adds and changes without re= termination of the cabling. Panels shall allow front access to installed modules. e) Panels shall mount to standard EIA 19” or 23” racks (with optional extender brackets. f) 48 port panels shall be supplied with 8 factory installed CFPLM6BL snap=in faceplates that readily accept TX6 Mini= Com jack modules. g) Panels shall have port identification capability (Machine generated) on both the front and rear of the panel. Front port identification on the 48 port panels shall be located between the rows of jacks. h) Panels shall terminate and arrange for modules in group of four (4). i) Panels shall feature vertical panel ID label holders. j) Labeling options to include laser printable paper and adhesive labels. k) Design Makes: 1) Mini=Com M6 Style Modular Faceplate Patch Panel = Panduit # CPPL48WBLY. 2) Mini=Com M6 Style Modular Angled Faceplate Patch Panel = Panduit # CPPLA48WBLY. 3) Acceptable Manufacturers: Others as approved only by Owner. B. Category 5e Voice Patch Panels 1. Physical Characteristics ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 7 OF 18 JUNE 29, 2012 a) Shall exceed ANSI/TIA=568=C.2 Category 5e and ISO11801 Class D standards b) Each port shall be 100% tested to ensure NEXT and return loss performance and is individually serialized to support traceability c) Shall utilize 110 termination on back panel d) Each port contains a label that is color coded for Universal T568A/T568B wiring scheme. e) Terminates 4 pair, 22 = 24 AWG, 100 ohm, solid or stranded twisted pair cable f) Mount to standard EIA 19" rack. g) Write=on areas for port and panel identification available h) Can be clearly identified with labels and icons i) Design Makes: 1) Panduit # NK5EEP48P, 48=port 2RU panels, per T3 drawing, used with 1=pair connections, per RJ=45 port. 2) Acceptable Manufacturers: Others as approved only by Owner. 3) Panduit # NK5EPP24P, 24=port 1RU panel, per T3 drawing, used with 4=pair terminations/connections, per RJ=45 port. 4) Acceptable Manufacturers: Others as approved only by Owner. 2.5 TERMINATION BLOCKS A. Provide 110=300 pair wall mounted termination blocks as called for on T3 detail drawings. B. Provide 110=100 pair wall mounted termination blocks as called for on T3 detail drawings for wall terminate fire alarm cables. C. Provide color coded designation strips, and clear covers for all blocks per the Owner’s direction. D. Provide distribution ring backboard between blocks as per detail drawings. E. Design Makes: ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 8 OF 18 JUNE 29, 2012 1. Systimax #110AW2=100 Wiring block with legs 2. Systimax #110AW2=300 Wiring block with legs 3. Systimax #110C=5, 5=pair clips, for all backbone copper risers 4. Systimax #188B1 metal backboard with distribution rings F. Acceptable Manufacturers: 1. Others as approved only by Owner. 2.6 CABLE RUNWAY A. Provide horizontal cable runway from wall to rack for horizontal cable support. B. Provide vertical cable runway from all sleeves, conduits and cable trays to the equipment racks for horizontal and backbone cable support inside the Telecommunication Room (TR). C. Cable runways shall have hollow side bars nominally 3/8” thick by 1 ½ “ H with rungs 9” on center to all TR’s. D. Provide connecting hardware to suit installation and provide a first class installation. This shall include, but not be limited to, standard rack=to= runways mounting plate for each 19” rack, wall angle support brackets, junction kits in various vertical and horizontal configurations, reducing fittings, radius fitting and cable drop outs, grounding kits, bonding kits, etc. E. Include all hardware for securing trays to each other, to the rack and to the wall F. Supply optional cable retaining posts per Section 3.4 of this section or called for on the T3 drawings. Chatsworth 11252=7xx series. G. Provide cable radius fittings as shown and called for on the T3 drawings. H. Provide one=tier or two=tier cable runways system, per T3 drawings. I. Provide cable drop out (waterfall) fittings as shown and called for on the T3 drawings, that are the next size smaller in width than the cable runways they are fastened to. (i.e 12” waterfall for 18” cable runway). J. Design make: Chatsworth Telco=Style Cable Runway System – hollow side bar for all TR’s. K. Acceptable manufacturers, only as approved in advance by Owner ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 9 OF 18 JUNE 29, 2012 1. B=Line 2. Homaco 3. Newton Instrument Company 2.7 BACK BOARDS A. Provided by General Contractor and the installation coordinated by Division 26 and 27 contractors. B. Refer to additional Division 1 requirements, A3=Series drawings and T3= Series drawings. 2.8 CABLE SUPPORTS A. Velcro=type Hooks and Loop Wraps 1. Refer to Section 27 15 00 section 3.1 for additional requirements. B. Metal backboards for 110=Style Blocks 1. Provide systimax “D” ring metal backboards between 110 style blocks as shown on the drawings or as called for. 2. Design Make: systimax 188B backboard. C. Two=Hole straps for high pair count copper cables and innerducts 1. Refer to Section 27 13 00 requirements and design makes and installation requirements. D. Distribution rings for plywood backboard cable routing 1. Provide wall mounted “D” rings for wall mounted vertical and horizontal cable management as shown on the drawings or as called for. 2. Design Make: Senior Industries =SI=4754 = cross connect wiring, SI= 4755 Vertical and Horizontal Category 6 cable. 3. Acceptable manufacturers: a) Allen Tel b) Gardner Bender ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 10 OF 18 JUNE 29, 2012 2.9 GROUNDING AND BONDING A. Provide standards compliant and code compliant Telecommunications Bonding Backbone (TBB). This backbone shall be used to ground all telecommunications cable shields, equipment, racks, cabinets, raceways, and other associated hardware that has the potential to act as a current carrying conductor. B. Provide standards compliant and code compliant telecommunications main grounding bus bar (TMGB). The main entrance facility/equipment room in each building shall be equipped with a telecommunications main grounding bus bar (TMGB). Each telecommunications room shall be provided with a telecommunications ground bus bar (TGB). The TMGB shall be connected to the building electrical entrance grounding facility. The intent of this system is to provide a grounding system that is equal in potential to the building electrical ground system. Therefore, ground loop current potential is minimized between telecommunications equipment and the electrical system to which it is attached. C. The Contractor shall bond all racks, metallic backboards, cable sheaths, metallic strength members, splice cases, cable trays, ladder runways, metallic conduits, metallic raceways, lightning protectors, etc. entering or residing in the TR room(s) to the respective TGB or TMGB using a minimum #6 AWG stranded copper bonding conductor and two hole compression connectors with ANSI compliant hole pattern. D. All wires used for telecommunications grounding purposes shall be identified with a green insulation. Non=insulated wires shall be identified at each termination point with a wrap of green tape. All cables and busbars shall be identified and labeled in accordance drawing details, ANSI/TIA= 607=B, Section 27 05 00 and the Cornell University Design and Construction Standards. E. Provide one 19” grounding bus Bar for each equipment rack in each TR, even if not specifically called for on the drawings. The T3 drawings typically identify the equipment on the rack elevation drawing (typically Rack 1 and possibly Rack 3). F. Use paint piercing screws and/or washers at racks on all finished surfaces (vertical racks, ladder racking etc) G. Installation and termination of the main bonding conductor to the building service entrance ground shall be performed by a licensed electrical contractor. H. Refer to E4 Grounding Riser Drawing, E4 TGB details, T3=series drawings AT Standard Detail 27 05 26 01=02 and specification section 27 05 00 for additional information. ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 11 OF 18 JUNE 29, 2012 I. Installation and termination of the main bonding conductor to the building service entrance ground shall be performed by a licensed electrical contractor. J. Contractor shall coordinate the exact positioning of the TGB in each Telecommunication Room with the T3=Series drawings, the Owner and the Division 26 contractor, in the field in advance. 2.10 POWER STRIPS A. Shall meet U.L. 1363 and 1449 requirements. B. Provide two horizontal rack mount powerstrips for each Equipment Rack in each TR, even if not specifically called for on the drawings. The T3 drawings typically identify the equipment on the rack elevation drawing (typically Rack 1 and possibly Rack 3). C. Provide transformer spacing in 1RU height with a minimum of six (6) 20Amp NEMA 5=20R standard 20A, 125VAC receptacles. Each power strip shall be equipped with a minimum 15’ long plug ended cord = 125VAC, 20Amp, single phase, 2=pole, 3=wire grounding, NEMA 5=20P cord and standard plug. D. Each power strip shall be provided with optional surge suppression to block excessive voltage rated at 600V with UL1449 rating. E. Maximum Surge Current: 36,000 Amps (12,000 Amps L=N, 12,000 Amps L=G, 12,000 Amps N=G) F. Integral Protection indication to show the status of the unit. G. Do not provide toggle switch that can accidentally get bumped off, unless it has a switch guard over the switch. 1. Design Make: Wiremold R5BZ20=15, or approved equal. H. Approved Manufacturers: 1. Chatsworth 2. SGL Waber / Tripp Lite 3. Middle Atlantic Products 2.11 FLOOR MOUNT CABINET A. Floor mount cabinets shall meet the following physical specifications: 1. 19” equipment mounting section and hinged locking front door. ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 12 OF 18 JUNE 29, 2012 2. 2500 lb weight capacity 3. Overall dimensions = Hx22”Wx25”D 4. Height as shown on T3 drawings 5. Heavy steel construction, factory paint black in color. B. Design Make Middle Atlantic ERK=19 series 2.12 WALL MOUNT CABINET A. Wall mount cabinets shall meet the following physical specifications: 1. 3 section cabinets include wall mount section with conduit knockouts, 19” equipment mounting section and hinged locking front door. 2. 2500 lb weight capacity 3. Overall dimensions = Hx22”Wx26”D 4. 24” usable depth. 5. Height as shown on T3 drawings 6. Heavy steel construction, factory paint black in color. B. Design Make Middle Atlantic DWR series PART 3 EXECUTION 3.1 FLOOR MOUNTED RACKS A. Coordinate rack positioning and mock=up with other trades. Refer to 27 05 00 Part 3 Mock=Up section for additional coordination requirements B. All racks shall be anchored to the floor, with large heavy duty gauge fender washers and four anchor bolts. C. Provide vertical and horizontal cable management in the front and back. D. Mount rack a minimum of 36” from wall when orientated parallel to wall and tight to wall (after allowing for vertical cable managers) when perpendicular to wall. Coordinate rack placement with existing and proposed conditions. E. Ground the bottom of each rack to the TGB equipment ground bar with a #6 green copper wire. Provide aggressive cutting Type=B internal/external ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 13 OF 18 JUNE 29, 2012 tooth lock washer. Torque properly to provide an acceptable bonded joint, for each nut to cut primed and painted surfaces. Refer to American Standard ASA B27.1=1965. These washers shall be used on all painted equipment racks, cable ladders, cable tray in TR’s. F. Coordinate with other utilities, trades and cable runway provisioning as required. Layout, mock=up all racks and cable runways for Owner review, alteration and approval before proceeding with any fabrication, especially in the basement BDF. G. Coordinate the relocation of existing equipment, power, conduits and cabling as directed by Owner. Provide necessary provisions and alterations to allow proper relocation without disruption of services. Refer to T2 and T3 Series removal plans. H. Alter, modify, or fabricate existing 19” equipment racks, shown for relocation to properly fit into the BDF room as indicated. Coordinate rework of existing service loops of fiber as directed by CIT. Coordinate with other utilities, trades and cable runway provisioning as required. 3.2 CABLE MANAGEMENT A. Provide racked mounted 2RU (3.5”) open and closed horizontal cable managers as shown. B. Install vertical cable managers, at the ends of each rack and between the racks, as shown on the T3 drawings. Provide closed end cap on exposed vertical end panels and provide rear hinged door (both items are accessories). C. Provide at least one 2RU horizontal cable manager for each 24 port or 48 UTP port panel and fiber patch panel installed, even if not specifically detailed on the drawings. 3.3 CABLE SUPPORTS A. Provide “D” rings 2 ft. on center for all exposed vertical cable runs terminated or routed exposed on the plywood backboards. B. Keep horizontal wall mounted cable runs to a minimum. In general horizontal runs shall be supported by overhead cable runway or overhead ladder runway. C. Provide cable brackets 4’ on center supported to building structure for all cable runs above ceilings where cable tray is not called for. D. Provide Velcro=type Hooks and Loop Wraps. Refer to Section 27 15 00 section 3.1 for additional requirements. ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 14 OF 18 JUNE 29, 2012 E. Provide vertically mount cable runways or channel, affixed to floor and wall as applicable, where called for to support cables in a vertical plane. Provide hook and loop cable wraps for such situations, on 18” centers. 3.4 CABLE RUNWAY A. Install as shown on the drawings B. Secure rack to walls and to the top of the equipment racks. C. Provide elevated riser kits as called for on the T3 drawings. D. Ground and bond all sections of runways. E. Provide waterfalls and radius bends for proper cable routing and support, even if not specifically detailed on the drawings. F. When sleeves, conduits and cable tray enter a TR at a height of more than 2’ above the highest horizontal cable runways in a TR, provide wall mounted vertical cable runways section up to meet each horizontal pathway entering the TR and provide proper radius control and vertical cable support and fastening with hook and loop fasteners as called for elsewhere in this section. G. Provide optional cable retaining posts, 6” in height minimum with rubber end caps, that mount directly to cable runway side stringers, color to match cable runway provided. Provide a minimum of twelve (12) per TR room, even if not called out on the drawings and install per Owner’s direction. Chatsworth 10596 series. H. Ground the bottom of each rack to the TGB equipment ground bar with a #6 green copper wire. Provide aggressive cutting Type=B internal/external tooth lock washer. Torque properly to provide an acceptable bonded joint, for each nut to cut primed and painted surfaces. Refer to American Standard ASA B27.1=1965. These washers shall be used on all painted equipment racks, cable ladders, cable tray in TR’s. I. Coordinate cable runway positioning and mock=up with other trades. Refer to 27 05 00 Part 3 Mock=Up section for additional coordination requirements. 3.5 MISCELLANEOUS REQUIREMENTS A. Provide cable runway from overhead sleeve locations in closets to equipment racks and punch down block locations, in both the horizontal and vertical orientation so that cables can be supported on at least 2’ centers. ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 15 OF 18 JUNE 29, 2012 B. Provide reusable, hook and loop wrap strips as the primary means for organizing all voice, data and coaxial cables station and patch cables in TR’s. Refer to 27 15 00, section 3.1 for additional requirements. C. All cables shall be neatly “dressed out” in equipment rooms. Cables to be neatly bundled and dressed to their respective panels or blocks. Each panel or block shall be fed by an individual bundle separated and dressed back to the point of cable entrance into the rack or frame. D. Each cable shall be clearly labeled on the cable jacket behind the patch panel at a location that can be viewed without removing the bundle support ties. Cables labeled within a bundle, where the label is obscured from view shall not be acceptable. E. Install factory supplied patch panel labels, in the corresponding T568A configuration, in all Category 6 UTP patch panels, BEFORE beginning to terminate cables. Cables terminated onto a patch panel without said port label strip shall not be acceptable. F. Install factory supplied patch panel labels, in the corresponding T568B configuration for all Category 5e voice interconnect patch panels, BEFORE beginning to terminate cables. Cables terminated onto a patch panel without said port label strip shall not be acceptable G. Fire Stop all sleeves and conduit openings at time or removal of existing abandoned cables and again at time of cable installation, as called for. 3.6 WALL TERMINATION BLOCKS A. Installed on plywood backboard so that top of block is 6’ AFF maximum. B. Pair untwist at the termination shall not exceed 3.18mm (0.125”). C. Also refer to UTP backbone called termination and labeling requirements in this section. D. The cable jacket shall be maintained as close as possible to the termination point. E. DO NOT MOUNT WALL MOUNTED TERMINATION BLOCKS WITH DRYWALL TYPE SCREWS. F. Mount Blocks with steel, zinc plated 5/16" slotted hex head #10 x 3/4" drill screws. Part #Metallics DS181 or equal. ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 16 OF 18 JUNE 29, 2012 3.7 GROUNDING AND BONDING A. Provide pre=drilled tin plated copper bus bar, with standard NEMA bolt hole sizing and spacing for connectors being used, in all telecommunication rooms. B. All connectors and clamps shall be mechanical type made of silicon bronze. C. Terminals shall be solderless compression type 2=hole lugs, copper long= barrel NEMA two bolt, and compliant with program standard detail drawings = TGB detail D. Provide #6 AWG conductor from the bus bar to the electrical system equipment ground. E. Bond the ground bar in the main Telecommunication Equipment Room (TR) to dedicated communications equipment electrical panelboard(s). F. Bond metallic equipment racks and cabinets to the ground bar. Bond racks in a bus or parallel configuration. Series connections are not acceptable. G. Bond the shield of shielded cable to the ground bar in communications rooms and spaces. H. Bond all backbone conduits and metallic raceways entering each TR to the ground bar in each communications rooms. I. Use an insulation=removal tool to remove the correct amount of jacket from the wire, as determined by the size of the connector and the gauge of the wire. J. Use a compression tool equipped with a die that matches the compression lug connector body, as recommended by the manufacturer. Leave approximately 6mm (o.25 inches) of copper showing between the end of the insulation on the wire and the end of the connector that the wire in insert into. K. Ensure that a minimum bend radius of eight times the conductor outside diameter is maintained where the wire changes direction. 3.8 PATCH PANELS. A. Patch Panels – Category 6 1. Panels shall be installed to provide minimal signal impairment by preserving wire pair twists as closely as possible to the point of ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 17 OF 18 JUNE 29, 2012 mechanical termination. The amount of untwisting in a pair as a result of termination to the patch panel shall be no greater than 0.5 inches (13 mm) 2. Panels shall be installed according to manufacturer’s instructions and properly mounted to a rack, cabinet, bracket or other appropriate mounting device. 3. Panels shall be installed such that cables terminated to the panel can maintain minimum bend radius of at least 4 times the cable diameter into the IDC contacts. 4. Cables shall be terminated on the panels such that there is no tension on the conductors in the termination contacts. a) Panels shall be properly labeled on front and back with the cable number and port connections for each port, as per cable schedule drawings. 5. All cables shall be neatly “dressed out” in equipment rooms. Cables to be neatly bundled and dressed to their respective panels or blocks. Each panel or block shall be fed by an individual bundle separated and dressed back to the point of cable entrance into the rack or frame. 6. Each cable shall be clearly labeled on the cable jacket behind the patch panel at a location that can be viewed without removing the bundle support ties. Cables labeled within a bundle, where the label is obscured from view shall not be acceptable. 7. Install factory supplied patch panel labels, in the corresponding T568A configuration, in all Category 6 UTP patch panels, BEFORE beginning to terminate cables. Cables terminated onto a patch panel without said port label strip shall not be acceptable\ 8. Install factory supplied patch panel labels, in the corresponding T568B configuration for all Category 5e VOICE interconnect patch panels, BEFORE beginning to terminate cables. Cables terminated onto a patch panel without said port label strip shall not be acceptable 9. Pair untwist at the termination shall not exceed 3.18mm (0.125”). 10. The cable jacket shall be maintained as close as possible to the termination point. 11. Terminate all Category 6 patch panels with wiring scheme T568A ARCHITECHNOLOGY CORNELL – NCP TELECOMMUNICATION ROOMS AND SPACES STANDARD SPECIFICATIONS 27 11 00 – PAGE 18 OF 18 JUNE 29, 2012 12. Terminate all Category 5e voice interconnect patch panels with wiring scheme T568B. Terminate 1 pair per port except for the last 6 ports in a patch panel which should be terminated 4 pairs per port.(Reference CU standard detail 27 13 43 01 for further information). 3.9 CLEANING A. Pre=acceptance cleaning 1. In all TR spaces = a through sweeping, vacuuming, and wet mopping/sponging shall be preformed, on a daily basis or less frequently as directed by Owner. Cleaning shall include floors, rafters, floor joists, exposed structural members, walls, ladder trays, tops of cabinets/racks, existing/new passive and active components, per manufacturer recommendations. 2. All non=metallic cable managers and snap covers shall be wiped clean, both inside and outside of front, including rear channels. All clear covers and doors shall be cleaned, both front and rear per manufacturer recommendations. 3. All non=metallic cable managers and snap covers shall be wiped clean, both inside and outside of front, including rear channels. All clear covers and doors shall be cleaned, both front and rear per manufacturer recommendations. 4. Inside of fiber optic enclosure and patch panels shall be blown clean of settled dust. Said cleaning shall be performed for all new construction projects or where gypsum sanding has been performed. 5. All scraps, boxes, spools, pull=line and trash shall be removed and properly disposed of. 6. All residual cable lubricant shall be cleaned from floors and walls with an appropriate degreaser. END OF SECTION ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 1 OF 26 JUNE 29. 2012 SECTION 27 13 00 BACKBONE CABLING PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, tools, and equipment required for the complete installation of work called for in the Contract Documents. 1.2 SCOPE A. Backbone cabling includes copper and optical fiber cabling between the Main Telecommunications Room (MTR) and subsequent Intermediate Telecommunications rooms (ITR’s). B. This section includes minimum requirements for the following: 1. Inside Plant (ISP) a) Optical Fiber Cable b) Innerducts c) Split Innerducts d) Optical Fiber Connectors e) Optical fiber splices f) Shielded UTP Copper Cable g) Clamps h) Bonding Braid i) Shield Bond Connectors j) Splicing Modules k) Splicing Tapes 1.3 QUALITY ASSURANCE A. All cable shall be installed in a neat and workmanlike manner. All methods of construction that are not specifically described or indicated in the contract documents shall be subject to the control and approval of the Owner's Representative. Equipment and materials shall be of the quality and manufacture indicated. The equipment specified is based upon the ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 2 OF 26 JUNE 29. 2012 acceptable manufacturers listed. Where "approved equal" is stated, equipment shall be equivalent in every way to that of the equipment specified and subject to approval. B. Materials and work specified herein shall comply with the applicable requirements of: 1. ANSI/TIA – 568>C 2. ANSI/TIA – 569>B 3. NFPA 70 > 2002 4. BICSI Telecommunications Distribution Methods Manual, current edition 5. FCC 47 CFR 68 6. NEMA > 250 7. NEC > Articles 725,760, 770 and 800 8. IEEE C2 National Electrical Safety Code (2002) 9. ISO/IEC 11801 10. ANSI/TIA/EIA 607 11. ANSI/TIA/EIA 606>A (2002 or newer) 12. ANSI/NECA/BICSI 568 (2006 edition) C. The optical fiber cable plant shall be used to support Gigabit and 10> Gaigbit Ethernet networks. D. If this document and any of the documents listed above are in conflict, then the more stringent requirement shall apply. All documents listed are believed to be the most current releases of the documents. The Contractor has the responsibility to determine and adhere to the most recent release when developing the proposal for installation. 1.4 SUBMITTALS A. Manufacturers catalog sheets, specifications and installation instructions for all cable, connecting hardware and patch cables. B. Termination details for all cable types. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 3 OF 26 JUNE 29. 2012 C. List of three (3) installations of equivalent or larger systems that have been installed within the past two (2) years and have been operating satisfactorily for a minimum of one year. (Include names and phone numbers of references). D. Cable Test Reports (at substantial completion). E. Cable tension reports for optical fiber pulls backbone pulls over 200’and any optical fiber installed in existing underground/under slab conduits, per drawings T1>PL and T1>FL. F. Also refer to Refer to Section 01 33 00 – Submittal Procedures. PART 2 PRODUCTS 2.1 INTERIOR GRADE OPTICAL FIBER CABLE FOR BUILDING BACKBONES A. Cable shall be riser rated and meet the requirements Flame Test: UL 910 (NFPA 262>1994) B. Fiber Characteristics 1. All fibers in the cable must be usable fibers and meet required specifications. 2. All optical fibers shall be sufficiently free of surface imperfections and inclusions to meet the optical, mechanical, and environmental requirements of this specification. 3. Each optical fiber shall consist of a doped silica core surrounded by a concentric glass cladding. The fiber shall be a matched clad design. 4. All optical fibers shall be proof tested by the fiber manufacturer at a minimum of 100 kpsi. 5. The fiber shall be coated with a dual layer acrylate protective coating. The coating shall be in physical contact with the cladding surface. 6. The coated fiber shall have a layer of Teflon placed between the dual layer acrylate coating of the optical fiber and the thermoplastic buffer. The diameter of the thermoplastic buffer coating shall be 900 ± 50 mm. 7. The fiber coating and buffer shall be removable with commercially available stripping tools in a single pass. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 4 OF 26 JUNE 29. 2012 C. The multimode fiber utilized in the cable specified herein shall meet EIA/TIA>492AAAA>1989, "Detail Specification for 62.5 mm Core Diameter/125 mm Cladding Diameter Class Ia Multimode, Graded Index Optical Waveguide Fibers." 1. Core diameter: 62.5 ± 3.0 mm. 2. Cladding diameter: 125.0 ± 2.0 mm. 3. Core>to>Cladding Offset: £ 3.0 mm. 4. Cladding non>circularity: £ 2.0 %. 5. Core non>circularity: £ 6.0 %. 6. Coating Diameter: 245 ± 10 mm 7. Graded index 8. Numerical Aperture: 0.275 ± 0.015. 9. Attenuation Uniformity: There shall be no point discontinuities greater than 0.2 dB at either 850 nm or 1300 nm. D. The non>dispersion shifted single>mode fiber utilized in the cable specified herein shall conform to the following specifications: 1. Typical Core Diameter: 8.3 mm. 2. Cladding Diameter: 125.0 ± 1.0 mm. 3. Core>to>Cladding Offset: £ 0.6 mm. 4. Cladding Non>Circularity: £ 1.0%. 5. Coating Diameter: 245 ± 10 mm. 6. Attenuation Uniformity> No point discontinuity greater than 0.1 dB at either 1310 nm or 1550 nm. 7. Attenuation at the Water Peak> The attenuation at 1383 ± 3 nm shall not exceed 2.1 dB/km. 8. Cutoff Wavelength> The cabled fiber cutoff wavelength shall be < 1260 nm. 9. Mode Field Diameter: 9.30 ± 0.50 mm at 1310 nm ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 5 OF 26 JUNE 29. 2012 10. ± 1.00 mm at 1550 nm 11. Zero Dispersion Wavelength (lo)> 1301.5 nm £ lo £ 1321.5 nm. 12. Zero Dispersion Slope (So)> £ 0.092 ps/(nm²·km). 13. Fiber Curl: > 4.0 m radius of curvature. E. Fiber Parameters 1. (Multimode only) The minimum normalized bandwidth of multimode optical fibers shall be ³ 200z km at 850 nm and ³ 500 MHz km at 1300 nm. 2. (Single>mode) The maximum dispersion shall be £ 3.2 ps/(nm km) from 1285 nm to 1330 nm and shall be < 18 ps/(nm km) at 1550 nm. 3. All fibers in the cable shall meet the requirements of this specification. 4. The attenuation specification shall be a maximum attenuation for each fiber at 23 ± 5°C. 5. The attenuation of the cabled fiber shall be uniformly distributed throughout its length such that there are no discontinuities greater than 0.1 dB at 1310 nm/1550 nm (single>mode) or 0.2 dB at 850 nm/1300 nm (multimode) in any one kilometer length of fiber. F. Physical Characteristics 1. Riser and Plenum Cables up to 24 Fibers: a) The fibers may be stranded around a dielectric central member and surrounded by layered aramid yarns. The aramid yarns shall serve as the tensile strength member of the cable. b) A ripcord shall be applied between the aramid yarns and the outer jacket to facilitate jacket removal. c) The outer jacket shall be extruded over the aramid yarns for physical and environmental protection. 2. Riser and Plenum Cables with 24 to 72 Fibers: a) The buffered fibers shall be grouped in six fiber subunits. In each subunit, the individual fibers shall be stranded around a ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 6 OF 26 JUNE 29. 2012 dielectric central member and surrounded by layered aramid yarns. b) A ripcord shall be incorporated in the subunit design to facilitate access to the individual fibers. c) The subunit jacket shall be extruded over the aramid yarns for additional physical and environmental protection. d) The subunits shall be stranded around a dielectric central member. e) A ripcord shall be inserted beneath the outer jacket to facilitate jacket removal. f) The outer jacket shall be extruded around the units for physical and environmental protection. 3. Strength Members: a) The strength member shall be a high modulus aramid yarn. b) The aramid yarns shall be helically stranded around the buffered fibers. c) Non>toxic, non>irritant talc shall be applied to the yarn to allow the yarns to be easily separated from the fibers and the jacket. 4. Cable Jacket: a) The jacket shall be continuous, free from pinholes, splits, blisters, or other imperfections. b) The jacket shall have a consistent, uniform thickness; jackets extruded under high pressure are not acceptable. c) The jacket shall be smooth, as is consistent with the best commercial practice. 5. The jacket shall provide the cable with a tough, flexible, protective coating, able to withstand the stresses expected in normal installation and service. 6. The cable and subunit jacket color shall be orange for cables containing multimode fibers. The cable and subunit jacket color shall be yellow for cables containing single>mode fibers. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 7 OF 26 JUNE 29. 2012 7. For cables with more than two fibers, the cable jacket shall be designed for easy removal without damage to the optical fibers by incorporating a ripcord under each cable jacket. Non>toxic, non> irritant talc shall be applied to the aramid yarns to allow the yarns to be easily separated from the fibers and the jacket. 8. The nominal thickness of the cable outer jacket shall be sufficient to provide adequate cable protection while meeting the mechanical, flammability, and environmental test requirements of this document over the life of the cable. 9. The cable shall be all>dielectric. G. Identification 1. The individual fibers shall be color coded for identification. The optical fiber color coding shall be in accordance with ANSI/TIA>598, "Color Coding of Fiber Optic Cables." The coloring material shall be stable over the temperature range of the cable, shall not be susceptible to migration, and shall not affect the transmission characteristics of the optical fibers. Color coded buffered fibers shall not adhere to one another. When fibers are grouped into individual units, each unit shall be numbered on the unit jacket for identification. The number shall be repeated at regular intervals. 2. The outer cable jacket shall be marked with the manufacturer's name or file number, date of manufacture, fiber type, flame rating, listing mark, and sequential length markings every two feet. The marking shall be in contrasting color to the cable jacket. H. Additional Requirements 1. The storage temperature range for the cable on the original shipping reel shall be >40°C to +70°C. The installation/operating temperature range for plenum cables shall be 0°C to +70°C. Testing shall be in accordance with FOTP>3. 2. Crush Resistance > The cable shall withstand a minimum compressive load of 89 N/cm (50 lbf/in) applied uniformly over the length of the compression plate. The cable shall be tested in accordance with FOTP>41, "Compressive Loading Resistance of Fiber Optic Cables." While under compressive load, the fibers shall not experience an attenuation change greater than 0.4 dB at 1550 nm (single>mode) or greater than 0.6 dB at 1300 nm (multimode). After the compressive load is removed, the fibers shall not experience an attenuation change greater than 0.2 dB at 1550 nm (single>mode) or greater than 0.4 dB at 1300 nm (multimode). ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 8 OF 26 JUNE 29. 2012 3. Impact Resistance > The cable shall withstand a minimum of 20 impact cycles. The cable shall be tested in accordance with FOTP> 25, "Repeated Impact Testing of Fiber Optic Cables and Cable Assemblies." The fibers shall not experience an attenuation change greater than 0.2 dB at 1550 nm (single>mode) or greater than 0.4 dB at 1300 nm (multimode). 4. Cyclic Flexing > The cable shall withstand 25 mechanical flexing cycles at a rate of 30 ± 1 cycles per minute. The cable shall be tested in accordance with FOTP>104, "Fiber Optic Cable Cyclic Flexing Test." The fibers shall not experience an attenuation change greater than 0.2 dB at 1550 nm (single>mode) or greater than 0.4 dB at 1300 nm (multimode). 5. Flammability > All cables shall comply with the requirements of the National Electrical CodeÒ (NECÒ), Article 770. Plenum cables (OFNP) shall pass UL>910. 6. Design Make: Corning Cable Systems, MIC Riser Cable Series, OFNR rated (or plenum if required by field conditions), standard or hybrid make>up with 62.5/125 multimode and single mode as called for on the T1>FL logical riser drawings, per below. Contractor shall confirm these part number as correct and fully compliant to meeting the requirements of the contract documents before ordering. 7. Indoor, OFNR Rated 12SM/6MM – Part # 018X81>331XX>24 8. Indoor, OFNR Rated 6SM > Part # 006E81>31131>24 2.2 INNER DUCT A. Shall be constructed of a PVC Riser rated or plenum rated plastic as required. B. For riser installations, shall meet NEC 770>53 requirements. C. Shall be .75 ”, 1" or 1.25" in diameter as called for on the drawings or as directed by Owner. D. Shall be white or orange in color. E. Shall have a maximum flame rating of UL 910. F. Design Make: Carlon DF4X1C (with pull rope) G. Acceptable Manufacturers: 1. Endot ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 9 OF 26 JUNE 29. 2012 2. Dura>Line 3. Arnco 2.3 OPTICAL FIBER CABLE CONNECTORS A. Backbone optical fiber connectors shall be duplex 568SC type. B. The terminations shall comply with the following standards: 1. TIA/EIA>604>3 Fiber Optic Connector Intermateability Standard, FOCIS>3 (Type SC) 2. EIA/TIA>4750000B Generic Specifications for Fiber Optic Connectors 3. EIA/TIA>455>A Standard Test Procedures for Optical Fibers, Cables, Transducers, Sensors, Connecting and Terminating Devices, and Other Fiber Optic Components (FOTPs) C. Connector Characteristics. 1. Strain relief: The connector shall provide a strain relief mechanism for installation on a single fiber cable that contains strength elements. The fiber within the body of the connector shall be isolated mechanically from cable tension, bending and twisting. 2. The connector shall have an optical axial pull strength of 2.2 N at 0 degree angle and an optical off axial pull strength of 2.2 N at a 90 degree angle, with a maximum 0.5 dB increase in attenuation for both tests when tested in accordance with ANSI/EIA/TIA>455>6B. 3. The maximum optical attenuation per each mated field installed 568SC connector pair shall not exceed 0.5 dB. 4. Shall have a return loss greater than or equal to 20 dB for multimode fiber and greater than or equal to 26 dB for single mode fiber. D. The connectors shall sustain a minimum of 500 mating cycles without degrading this performance. E. Intermateability: The connector shall be designed in compliance with the appropriate TIA FOCIS document. F. Installation rate: The connector shall be installable on 900 Tm buffered fiber in 1 minute or less total time. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 10 OF 26 JUNE 29. 2012 G. Installation polishing: The connector shall not require polishing of the endface in the field. Connectors shall have a factory>polished fiber stub in the connector ferrule. H. Installation type: The connector installation shall not require the use of epoxies. I. Fiber protection: The connector crimp>on mechanism shall protect the bare fiber from the ingress of air or waterborne contaminants and shall secure the fiber in the ferrule micro>hole. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 11 OF 26 JUNE 29. 2012 J. Performance Requirements. Multimode Testing Max delta change Final Measurement FOTP>171 METHOD B1 METHOD B1 REQ.: <.75dB N/A 0.11 dB TYP 0.19 dB MAX FOTP 107 RETURN LOSS REQ.: <>20dB N/A >42.5 dB TYP >36.3 dB MIN FOTP>2 IMPACT 8 DROPS/ 1.5 M N/A 0.14 dB IL >41.3 dB RL FOTP>1 FLEX 0.5 KG N/A 0.18 dB IL >41.3 dB RL FOTP>36 TWIST 15 N AT 0 º N/A 0.20 dB IL >41.2 dB RL FOTP>6 CABLE RETENTION 66 N AT 0 º 0.06 dB 0.20 dB IL >41.2 dB RL FOTP>6 CABLE RETENTION 19.4 N AT 90 º 0.06 dB 0.19 dB IL >41.2 dB RL FOTP>185 COUPLING MECH 33 N AT 0 º N/A 0.13 dB IL >41.5 dB RL FOTP>21 DURABILITY 500 CYCLES N/A dB IL >36.3 dB RL FOTP>4 TEMP LIFE 60ºC/ 14 DAYS 0.01 dB 0.08 dB IL >39.0 dB RL FOTP>5 HUMIDITY 4 DAYS @ 95% 0.15 dB .09 dB IL >38.9 dB RL FOTP>188 LOW TEMP. >10 ºC/4 DAYS 0.22 dB 0.13 dB IL >42.3 dB RL ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 12 OF 26 JUNE 29. 2012 Single Mode Testing Max delta change Final Measurement FOTP>171 METHOD B1 INSERTION LOSS N/A dB TYP 0.52 dB MAX FOTP 107 RETURN LOSS N/A >44.4 dB TYP >36.2 dB MIN FOTP>2 IMPACT 8 DROPS/ 1.5 M N/A dB IL >40.6 dB RL FOTP>1 FLEX 0.5 KG N/A 0.40 dB IL >40.1 dB RL FOTP>36 TWIST 15 N AT 0 º N/A 0.37 dB IL >40.2 dB RL FOTP>6 CABLE RETENTION 66 N AT 90 º 0.20 dB 0.39 dB IL >42.3 dB RL FOTP>6 CABLE RETENTION 19.4 N AT 90 º 0.11 dB 0.34 dB IL >43.2 dB RL FOTP>185 COUPLING MECH 33 N AT 0 º N/A 0.37 dB IL >45.0 dB RL FOTP>21 DURA> BILITY 500 CYCLES N/A 0.35 dB IL >40.5 dB RL FOTP>4 TEMP LIFE 60ºC/ 14 DAYS 0.24 dB 0.29 dB IL >44.2 dB RL FOTP>5 HUMIDITY 4 DAYS @95% 0.10 dB 0.30 dB IL >43.9 dB RL FOTP>188 LOW TEMP. >10 ºC 0.18 dB 0.29 dB IL >44.1 dB RL K. Design Makes: 1. Multi>Mode, SC, Ceramic Tip, CamLite UniCamSeries Corning Cable Systems > # 95>000>41 2. Single>Mode, SC, Ceramic Tip, CamLite UniCam Series Corning Cable Systems > # 95>200>41 2.4 OPTICAL FIBER SPLICES A. Splices are not allowed, unless called for on the drawings to tie>in to existing backbone splice enclosures. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 13 OF 26 JUNE 29. 2012 B. Should fiber be broken during installation the entire run shall be replaced. 2.5 SHIELDED UTP COPPER CABLE (BETWEEN TRS) A. Backbone copper cables shall consist of 24 AWG, groups of 25 pair thermoplastic insulated copper conductors following the ANSI/ICEA S>80> 576 color code. The 25 pair groups shall be bound together and covered by a protective sheath consisting of an overall thermoplastic jacket and one layer of dielectric material applied over the core. B. The cable shall be listed and marked for its use as required by article 800 of the current NEC code. Provide ARMM/CMR rated cable. C. Backbone cables shall be used for telephone systems only and shall be third party verified Category 3. D. Transmission Characteristics: 1. The resistance of any conductor, measured in accordance with ASTM D 4566 shall not exceed 9.38 ohms per 100m at 20 degrees C. 2. The resistance unbalance between the two conductors of any pair shall not exceed 5%. 3. The mutual capacitance of any pair shall not exceed 6.6 nF per 100m. 4. The capacitance unbalance to ground at 1 kHz of any pair shall not exceed 330 pF per 100m. 5. The characteristic impedance shall be 100 ohm +/> 15% from 1 kHz to 16 MHz. 6. The attenuation shall meet the requirements of the horizontal cable specified in section 27 15 00. 7. The insulation between each conductor and the core shield shall be capable of withstanding a minimum dc potential of 5 kV for 3 seconds. 8. The propagation delay of any pair at 10 MHz should not exceed 5.7 ns/m. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 14 OF 26 JUNE 29. 2012 9. The Power Sum NEXT loss shall meet the following: Frequency (MHz) NEXT loss (dB) 0.150 53 0.772 43 1.0 41 4.0 32 8.0 27 10.0 26 16.0 23 E. Shall be of size indicated on the drawings. F. Shall consist of a core of 24 AWG solid annealed copper conductors, color coded in accordance with telephone industry standards. G. Transmission Characteristics: 1. The nominal resistance of any conductor shall not exceed 27.3 ohms per 1000 feet at 20 degrees C. 2. The mutual capacitance of any pair shall not exceed 15.7 nF per 1000 feet at 1 kHz. 3. The maximum attenuation at 1.0 MHz shall not exceed 6.8 dB per 1000 feet. 4. The characteristic impedance shall be 100 ohm +/> 15% from 1 kHz to 16 MHz. H. Conductors shall be twisted to form pairs. Cable having more that 25 pairs shall be assembled in units, each individually identified by color coded unit binders. I. The core shall be covered with a plastic tape. J. The core and tape shall be overlaid with a corrugated shield applied longitudinally with overlap using the following materials: 1. .008 inch coated aluminum 2. .005 inch copper 3. Shall be bonded to outer jacket to form an ALVYN sheath. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 15 OF 26 JUNE 29. 2012 K. The outer jacket shall consist of a fire retardant sheath that meets NEC low flame requirements. L. Cable shall be suitable, listed and marked for use in a riser application. (CMR) M. Manufacturer’s cable code, pair size, manufacturing plant location, month and year or manufacture shall be marked on cable every two feet. N. Design Make: Essex xxxx024EAA (xxxx=number of pairs) size and quantity indicated on the T1>CL and T3 drawings. O. Acceptable Manufacturers: 1. General Cable 2. Norcom / CDT > Belden 3. Superior / Essex 2.6 UNSHIELDED UTP COPPER CABLE (VPP TO WALL) A. Backbone copper interconnect cables shall consist of 24 AWG, 25 pair thermoplastic insulated copper conductors following the ANSI/ICEA S>80> 576 color code. The 25 pair group shall be bound together and covered by a protective sheath consisting of an overall thermoplastic jacket and one layer of dielectric material applied over the core. B. The cable shall be listed and marked for its use as required by article 800 of the 2005 NEC. Provide CM rated cable for interconnect cables routed within a TR, generally between the wall mounted termination field(s) and the Rack mounted voice patch panels. C. Backbone cables shall be used for telephone systems only and shall be third party verified Category 3. D. Transmission Characteristics: 1. The resistance of any conductor, measured in accordance with ASTM D 4566 shall not exceed 9.38 ohms per 100m at 20 degrees C. 2. The resistance unbalance between the two conductors of any pair shall not exceed 5%. 3. The mutual capacitance of any pair shall not exceed 6.6 nF per 100m. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 16 OF 26 JUNE 29. 2012 4. The capacitance unbalance to ground at 1 kHz of any pair shall not exceed 330 pF per 100m. 5. The characteristic impedance shall be 100 ohm +/> 15% from 1 kHz to 16 MHz. 6. The attenuation shall meet the requirements of the horizontal cable specified in section 27 15 00. 7. The propagation delay of any pair at 10 MHz should not exceed 5.7 ns/m. 8. The Power Sum NEXT loss shall meet the following: Frequency (MHz) NEXT loss (dB) 0.150 53 0.772 43 1.0 41 4.0 32 8.0 27 10.0 26 16.0 23 E. Shall be of size and quantity indicated on the drawings. F. Shall consist of a core of 24 AWG solid annealed copper conductors, color coded in accordance with telephone industry standards. G. Transmission Characteristics: 1. The nominal resistance of any conductor shall not exceed 27.3 ohms per 1000 feet at 20 degrees C. 2. The mutual capacitance of any pair shall not exceed 15.7 nF per 1000 feet at 1 kHz. 3. The maximum attenuation at 1.0 MHz shall not exceed 6.8 dB per 1000 feet. 4. The characteristic impedance shall be 100 ohm +/> 15% from 1 kHz to 16 MHz. H. Conductors shall be twisted to form pairs. I. Cable shall be suitable, listed and marked for general use (CM) per the NEC code. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 17 OF 26 JUNE 29. 2012 J. Manufacturer’s cable code, pair size, manufacturing plant location, month and year or manufacture shall be marked on cable every two feet. K. Design Make: Mohawk >3NP25P24>GY PVC > jacketed 25>pair in size to be used for backboard to voice patch panel interconnect cabling, in quantities indicated on the T3 drawings. L. Acceptable Manufacturers: 1. General Cable 2. Norcom / CDT > Belden 3. Superior / Essex 2.7 SPLICING ENCLOSURES A. Backbone copper closures shall consist of a black solid or split PVC sleeve as indicated on the drawings. B. Minimum inside diameter shall be a minimum of 9” diameter (127mm). C. Minimum inside length shall be 26" (660mm). D. Actual sizes shall be indicated on the drawings. Otherwise, closure to be sized to accommodate the maximum number of cable pairs to be spliced and the type of connector to be used for splicing. E. Closure shall be flame retardant. F. Closure shall be re>enterable. G. When assembled with properly sized end caps, bushing, plugs and clamps, the closure shall be air and water tight. H. Design Make: 1. 3M KB Series or approved equal. 2.8 BONDING HARNESSES A. Shall be used to ground the shields of the spliced cables. B. Bonding harness shall be 14 AWG and sized according to closure. C. Adhere to all manufacturer installation guidelines. D. Design Make: ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 18 OF 26 JUNE 29. 2012 1. 3M or approved equal 2.9 SPLICING MODULES A. Crimping process shall strip the installation from the wire and trim the excess wire. B. The module shall create a gas tight connection. C. All modules shall have test entry ports on the front side of the module. D. Straight splicing modules shall have a yellow cover and body top and the base and body bottom shall be dark gold. E. Pluggable/Bridge splicing modules shall have a transparent cover, the body top and bottom shall be blue and the insulator shall be red. F. Design Make: 1. Straight Splicing Modules > 3M # 4000>C 2. Pluggable/Bridge Splicing Modules – 3M # 4005>CBM/TR 3. 3M UY2 wire connectors may be used for small pair count splices, pending owner approval. 2.10 SPLICING TAPES A. Shall be all weather, Vinyl Plastic material. B. Shall resist: 1. Water 2. Acids 3. Alkalies C. Shall be flame retardant D. Shall not be affected by sunlight. E. Shall release smoothly in zero weather and will not ooze adhesive in hot climates. F. Design Make: 1. 3M Scotch 88T Series ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 19 OF 26 JUNE 29. 2012 2.11 BONDING CONNECTORS A. Shall consist of a base and upper member, two securing nuts and a plastic shoe to aid connector installation and protect the conductors. B. Base and upper members shall be made of tin plated tempered brass, slightly curved so as to exert a continuous spring form on sheath and shield after clamping. C. Design Make: 1. 3M Part # 4460 – S Shield Bond Connector for cables of greater than 100 pair. 2. 3M Part # 4460 – D Shield Bond Connector for cables of less than 100 pair. 2.12 GROUNDING BRAID A. Shall be a flat tin plated copper braid conductor. B. Shall have eyelets at regular intervals. C. Eyelets shall fit shield connector studs up to 6 mm (1/4") in diameter. 2.13 2.14 EXPANDABLE CONDUIT PLUGS A. Seal all open underground and telecommunications conduits entering and existing the building and the BDF. B. For spare conduits, provide expandable conduit plugs with rope tie rings to seal spare conduits and tie off any existing pull>string or existing pull>lines. This shall include conduits for CIT cables and Verizon conduits. C. Design Make: Osburn Associates, Condux International or approved equal PART 3 EXECUTION 3.1 INSTALLATION A. OPTICAL FIBER CABLE 1. General a) Interior cable installed shall be in metallic conduit. Do not install with UTP or coax cables. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 20 OF 26 JUNE 29. 2012 b) Interior cable installed in pass>through existing IDF closets, shall be protected with metallic U>Guard. Refer to drawing T1>PL and T1>FL for additional requirements. Temporary float existing backbone cable and termination blocks from plywood walls to allow order and straight installation of backbone cables and U>Guard. c) Maintain polarization for entire system as described in ANSI/EIA/TIA>568>A section 12.7.1. d) Cable shall be continuous. Splices are not allowed. 2. Cable Pulling a) Adhere to all manufacturers’ requirements regarding pulling tension, allowable lubricants and bending radius. b) Provide cable pullers designed to suit field conditions. (i.e. horizontal vault pulls, vertical pulls and 45 degree pulls) c) Use cable guides with aluminum adapters sized for the 1 ¼” cells. Provide extensions, sheaves and adapters as required by the installation conditions. d) Use directional pulling swivels as conditions require. e) Use Line Tension meter during cable pull to provide accurate measurements of the force exerted on a cable as it is installed. The meter shall have a programmable overload set point with an audible and visual indication of an overload condition. The meter shall have controls to disengage the cable puller if an overload occurs. Provide chart recorded documentation of the cable pull for the owner’s records. f) Provide cable racks in manholes to support cable. g) Provide a minimum 20 foot service loop at the BDF, TR and IDF locations. 3.2 INNER DUCTS AND SPIRAL WRAPS A. Innerduct shall be placed with entrance cable for fiber optic installations. B. Innerduct shall be provided for all interior building optical fiber cables, in a minimum of 1” diameter. Place innerduct inside EMT conduits that have been provided. Place a spare pull>line in during installation of the innerduct. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 21 OF 26 JUNE 29. 2012 C. Support exposed innerduct in riser closets, TR’s, IDF’s and BDF’s on a minimum 3’ centers with 2>hole straps on plywood backboards, or supports approved by owner. D. Support exposed innerduct in riser closets, TR’s, IDF’s and BDF’s on a minimum 3’ centers with 1.5” wide hook and loop straps on ladder racks, cable runways or on or in racks and cabinets. E. Provide split innerduct or split spiral wrap on exposed cable sheaths at racks, cabinets and fiber splice bays and patch panels. Also refer to 17110 for spriral wraps. F. Provide split innerduct, larger than the outside diameter of solid innerduct used, when fiber cable is exposed in riser closets, TR’s, EF’s, IDF’s, BDF’s, pullboxes and maintenance holes. Fiber shall not be left exposed when solid innerduct is not continuous. G. Provide innerduct or split innerduct to conceal existing fiber that is called for to remain or be relocated within TR’s and BDF’s as directed by Owner. 3.3 RACK INTERCONNECT CABLES A. Review wall mount house cable block to modular patch panel interconnection termination requirement in the field with Owner, for all PVC>25 pair interconnect cables in the TR rooms, before rough>in of cables. Provide ample cable slack for proper dressing of cables at termination points. B. DO NOT mix the Category 6 cables and the PVC>25 cable in the vertical cable managers. C. Terminate ONE pair on pins 4 and 5 of each RJ>45 modular on every 48> port of the voice patch panels, as indicated on the T3 drawing. D. Terminate FOUR pairs per each RJ>45 modular on the one 24>port of the voice patch panel, as indicated on the T3 drawing. E. Review wall mount house cable block to modular patch panel interconnection termination requirement in the field with Owner, for all PVC>25 pair interconnect cables in the TR rooms >> before rough>in of backbone copper cables. Provide ample cable slack for proper dressing of cables at termination points and provide shield bond connectors at all cable sheath opening. F. PVC>25 pair cable shall be routed between the wall 110>300 termination block, onto the cable runways down to the 48>port and 24>port Category 3 RJ45 voice patch panels as called for. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 22 OF 26 JUNE 29. 2012 G. Route PVC>25 cable down center void of between the two vertical cable manager installed to create a separate channel for these cables. DO NOT mix the Category 6 cables, patch cords or the PVC>25 cable in a common vertical cable manager. H. Test all terminated conductors at each RJ>45 port of each voice patch panel.. Multi>pair cables shall be replaced if they contain more than 1% bad pairs that can not be repaired via re>terminating. Use test sheet provided in 27 05 53 for backbone copper test results. Provide test results. I. Neatly wrap the unused 25 pair slack around both ends of the PVC>25 jacket and do not cut the pair short. J. Label, dress and bundle each cable with a cable number and the corresponding patch panel number/port range at both ends, in a fashion that the cable number is facing forward and readily seen and allow for the 25 pair slack wrap. K. Neatly bundle and securely fasten PVC>25 pair cable along plywood backboards on maximum 1’ centers. L. Neatly bundle and securely fasten PVC>25 pair cable along cable runways and vertical cable managers with hook>and>loop Velcro>type straps on maximum 1’ centers. 3.4 SHIELDED UTP CABLE A. UTP backbone cables shall be installed in conduit. B. Placement of underground cables shall conform to REA 644 Cable Standards. C. Cables above drywall ceilings shall be installed in conduit. Cables in exposed areas other than communications equipment rooms shall be installed in conduit or surface raceway. D. Do not install with optical fiber cable or any other cable type, unless approved in advance by Owner. E. Provide cable management as called for in section 27 11 00. F. Label termination blocks and lightning protector bases with the pair counts indicated on the T1>Series Copper Logical riser drawings. G. For 66>styleblocks, label or stencil every fifth pair of each termination block with the appropriate cable count and provide 5th pair identification lines on block or designation strips. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 23 OF 26 JUNE 29. 2012 H. For 110>styleblocks, provide color code plastic designation strips/covers with the appropriate cable count indicated on every row of the block. Provide 5th pair identification lines on block or designation strips. I. The contractor shall replace the cable if damaged during installation. J. Test all riser cable pairs. Multi>pair cables shall be replaced if they contain more than 1% bad pairs that can not be repaired via re>terminating. Use test sheet provided in 27 05 53 for backbone copper test results. Provides test results K. 110>Cross connect label designation strips shall be color>coded as directed by the Owner as follows: Description Color C.O. Circuits PBX Circuits Auxiliary Circuits Yellow Wiring to Work Station White Back Bone Riser Cable Blue Tie Lines Yellow L. Review splicing and termination requirements with Owner before rough>in of backbone copper cables greater than 100 pairs. Provide ample cable slack for proper dressing of cables at termination and splicing locations. Do not cut backbone cable greater than 300 pairs before onsite approval of means and methods with Owner. M. Secure all ARMM cables to wall within 12" of all splice enclosures N. Test, label and document as per section 27 05 53. O. Backbone cables shall be installed separately from horizontal distribution cables P. A pull cord (nylon; 1/8" minimum) shall be co>installed with all backbone cables installed in a conduit. Q. All backbone cables shall be securely fastened to the sidewall of the TR on each floor. R. Backbone cables spanning more than three floors shall be securely attached at the top of the cable run with a wire mesh grip and on alternating floors or as required by local codes. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 24 OF 26 JUNE 29. 2012 3.5 RISER CLOSURES A. In vault environment or other horizontally installations support splice closure or cable at both end racks or steps > Condux cable racks series #83801>00 (14 hole or longer) and Condux cable steps series #83806 (4" or longer). B. In other horizontally installations support spliced cable at both ends of splice enclosures with snug fitting 2>hole straps. C. Provide mounting kindorf type channels to secure splice enclosures to walls. D. Secure all Riser closures to wall kindorf channels with heavy duty black ty> wraps. 3.6 SPLICING A. Fold back method of splicing is required for all new splices. B. Ends of unused binder groups shall be staggered, cleared and encapsulated in HYSOL Series CK capping kits. C. Terminal counts shall be installed as per the drawings and may not be split or multiplied. D. Binder group and color code integrity shall be maintained. E. Provide striped nylon cable ties and identify binder groups on both sides of sheath opening and at all other sheath openings and at termination points. F. The quantity of bad pairs per sheath of 100 pairs or more shall not exceed 1% of the total pair count. G. Use 3M 4053 Cover Removal Tool to remove bases and covers. H. Use 3M 4053>PM Separation Tool to separate 4005>DPM modules from any other module. I. All cable pairs shall be free of electrical opens, shorts (within and between pairs), polarity reversals, transpositions, and the presence of AC voltage, from the Telecommunication Rooms to the termination hardware at the main crossconnect frame. All defects must be corrected. 3.7 SPLICING TAPES A. Tape all entries to vault and riser closures to prevent water, insects or rodents from entering splice enclosure. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 25 OF 26 JUNE 29. 2012 3.8 BONDING CONNECTORS A. Install Bonding Connectors so as not to damage the conductors in the cable. 3.9 GROUNDING BRAID A. Adhere to all manufacturer installation guidelines. 3.10 GROUNDING AND BONDING A. The contractor shall provide a Telecommunications Bonding Backbone (TBB). This backbone shall be used to ground all telecommunications cable shields, equipment, racks, cabinets, raceways, and other associated hardware that has the potential to act as a current carrying conductor. The TBB shall be installed independent of the building's electrical and building ground and shall be designed in accordance with the recommendations contained in the ANSI/TIA/EIA>607>B Telecommunications Bonding and Grounding Standard. B. The main entrance facility/equipment room in each building shall be equipped with a telecommunications main grounding bus bar (TMGB). Each telecommunications room shall be provided with a telecommunications ground bus bar (TGB). The TMGB shall be connected to the building electrical entrance grounding facility. The intent of this system is to provide a grounding system that is equal in potential to the building electrical ground system. Therefore, ground loop current potential is minimized between telecommunications equipment and the electrical system to which it is attached. C. All racks, metallic backboards, cable sheaths, metallic strength members, splice cases, backbone conduits, cable trays, cable runways, etc. entering or residing in the TR or ER shall be grounded by the Division 27 contractor to the respective TGB or TMGB using a minimum #6 AW G stranded copper bonding conductor and compression connectors. D. All wires used for telecommunications grounding purposes shall be identified with a green insulation. Non>insulated wires shall be identified at each termination point with a wrap of green tape. All cables and busbars shall be identified and labeled in accordance E>Series drawing details, TIA 606A and Sections 16450 and 27 05 53. E. Refer to 26 05 26, and E>Series drawings for additional requirements. F. Coordinate work with the Division 26 Electrical contractor. ARCHITECHNOLOGY CORNELL – NCP BACKBONE CABLING STANDARD SPECIFICATIONS 27 13 00 – PAGE 26 OF 26 JUNE 29. 2012 3.11 GROUNDING SYSTEM A. The TBB shall be designed and/or approved by a qualified PE, licensed in the state that the work is to be performed. The TBB shall adhere to the recommendations of the TIA/EIA>607>B standard, and shall be installed in accordance with best industry practice. B. Installation and termination of the main bonding conductor to the building service entrance ground shall be performed by a licensed electrical contractor. C. The Division 27 contractor shall bond all cable sheaths, racks, cabinets, cable runways, backbone conduits, cable trays, etc. to the TGB provided in each TR, IDF, BDF and MDF as called for. D. Refer to 26 05 26, and E>Series drawings for additional requirements. E. Coordinate work with the Division 26 Electrical contractor. END OF SECTION Fax: 585.424.4239 115 METRO PARK ROCHESTER, NY 14623 www.archi-technology.com PHONE: 585.424.1952 ISSUE DATE: PROJECT MANAGER: DRAWN BY: CHECKED BY: AT-27052819 SC,CP - SURFACE RACEWAY TO CEILING, CONDUIT TO PULLBOX AT STANDARD DETAILS ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 1 OF 21 JUNE 29, 2012 SECTION 27 15 00 HORIZONTAL CABLING PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, tools, and equipment required for the complete installation of work called for in the Contract Documents. Unless noted otherwise all work included in this section is included in the data cable contract. B. Prior to installation and as part of the contract, relocate any device a distance of 6 feet in any direction at the request of the owner, at no additional cost. This shall include all necessary conduit, cable, raceways, painting and patching to accomplish the modification. Also refer to Division 26. C. Refer to Appendix A of the specifications for the Proposed Cable Schedule. D. Refer to section 27 05 00 section 1.2 for additional requirements as it relates to removal of existing cables to free up space in existing pathways intended for reuse for new Category 6 installations. 1.2 SCOPE A. Horizontal cabling includes Category 6 UTP from the Telecommunications Rooms (TR) to the outlets as shown on the plans and called for in the cable schedules (refer to Appendix). The horizontal cabling includes all horizontal cables, mechanically terminated jacks/inserts and faceplates in the work area and the mechanical termination in the TR. B. This section includes minimum requirements for the following: 1. Unshielded Twisted Pair Cable 2. Connecting Hardware 3. Cable Terminations 4. Faceplates 1.3 QUALITY ASSURANCE A. All cable shall be installed in a neat and workmanlike manner. All methods of construction that are not specifically described or indicated ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 2 OF 21 JUNE 29, 2012 in the contract documents shall be subject to the control and approval of the Owner's Representative. Equipment and materials shall be of the quality and manufacture indicated. The equipment specified is based upon the acceptable manufacturers listed. Where "approved equal" is stated, equipment shall be equivalent in every way to that of the equipment specified and subject to approval B. Strictly adhere to all Category 6 (BICSI and TIA) and manufacturer recommended installation practices when installing high performance cabling. C. All methods of construction that are not specifically described or indicated in the Contract Documents shall be subject to the control and approval of Cornell University. D. Equipment and materials shall be of the quality and Manufacturer indicated. E. Provide with the submittals, documentation from an independent testing agency indicating that the complete assembly including cable and termination hardware has been tested and meets the performance criteria called for. F. Materials and work specified herein shall comply with the applicable requirements of: 1. ANSI/TIA – 568C 2. ANSI/TIA – 569B 3. ANSI/TIA – 606A 4. ISO/IEC 11801– 2002 (or newer edition) 5. NFPA 70 – 2002 (or newer edition) 6. BICSI Telecommunications Distribution Methods Manual, current edition 7. Cornell University Design and Construction Standards, current Edition 8. National Electrical Installation Standards (ANSI/NECA/BICSI 568, 2006) 9. FCC 47 CFR 68 10. NEMA 250 ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 3 OF 21 JUNE 29, 2012 11. NEC Articles 770, 800,810. 12. ADA, Americans with Disabilities Act. 1.4 SUBMITTALS A. Manufacturers catalog sheets, specifications and installation instructions for all cable, connecting hardware and patch cords B. Evidence of manufacturer’s certification to install and warrant Panduit UTP, copper backbone and Corning optical fiber cables and housings. C. Termination details for all cable types. D. List of three (3) installations of equivalent or larger systems that have been installed within the past two (2) years and have been operating satisfactorily for a minimum of one year. (Include names and phone numbers of references at the site of installation) E. Cable Test Reports (prior to hardware/software installation). F. Also refer to Section 27 05 00 Basic Communication Requirements G. Also refer to Refer to Section 01 33 00 – Submittal Procedures. PART 2 PRODUCTS 2.1 100 OHM UNSHIELDED TWISTED PAIR CABLE A. Shall be Category 6A type cabling, compliant with the requirements of the most current ANSI/TIA 568C standard, for all w ireless locations . B. Shall be Category 6 type cable, compliant with the requirements of the most current ANSI/TIA 568C standard, for all other locations. C. Shall be independently verified to comply with ANSI/TIA 568C.21. D. An ISO 9002 Certified Manufacturer shall make the cable. E. Cable shall be UL LISTED. F. Physical Characteristics: 1. Shall meet applicable requirements of ANSI/ICEA S80576 and NEC. 2. Conductor shall be 24 AWG solid bare annealed copper. ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 4 OF 21 JUNE 29, 2012 3. Category 6A: Outer jacket color shall be green or as directed by Owner. 4. Category 6: Outer jacket color shall be blue or as directed by Owner. 5. Category marking shall be printed every one foot. Footage indicators shall also be providing on jacket. 6. The diameter of the insulated conductor shall be .023 in. maximum. 7. Shall consist of (4) 2226 AWG twisted pairs. 8. Shall be suitable for the environment in which they are to be installed. 9. The color coding of pairs shall be: Pair 1 WBL; BL Pair 2 WO; 0 Pair 3 WG; G Pair 4 WBR; BR 10. The overall diameter of the cable shall be less than 0.250 inches. 11. The ultimate breaking strength measured in accordance with ASTM D 4565 shall be 400 N minimum. 12. Cable shall withstand a bend radius of 1 inch at 20 degrees Celsius without jacket or insulation cracking. 13. Cable shall be third party verified to meet ANSI/TIA 568C.21, Category 6 requirements. G. Transmission Characteristics: 1. Cable shall be ANSI/TIA568C.21 and ISO/IEC 11 801 category 6 compliant. 2. Attenuation shall be measured in accordance with TIA/EIA 568B.21 and shall be maximum of 19.8dB @ 100 MHz. 3. Cable shall exhibit positive PSACR above 250 MHz. 4. Cable shall be tested & characterized to 500 MHz. ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 5 OF 21 JUNE 29, 2012 5. Cable shall be UL LISTED. ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 6 OF 21 JUNE 29, 2012 a) Cable shall exhibit a NEXT loss of at least the following: Frequency MHz NEXT dB 1.0 78 4.0 69 10.0 63 16.0 60 20.0 58 31.25 55 62.5 51 100.0 48 200 44 250 42 b) Cable shall exhibit ELFEXT loss of at least the following: Frequency MHz ELFEXT dB 1.0 75 4.0 63 10.0 55 16.0 51 20.0 49 31.25 45 62.5 39 100.0 35 200 29 250 27 ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 7 OF 21 JUNE 29, 2012 c) Cable shall exhibit Attenuation loss of less than the following: Frequency MHz Attenuation dB 1.0 2.0 4.0 3.8 10.0 6.0 16.0 7.6 20.0 8.5 31.25 10.7 62.5 15.4 100.0 19.8 200 29.0 250 32.58 d) Cable shall exhibit a return loss according to the following: Frequency MHz Return Loss (dB) 1 20.0 4 23.0 10 25.0 16 25.0 20 25.0 31.25 23.6 32.5 21.5 100 20.1 200 18.0 250 17.3 ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 8 OF 21 JUNE 29, 2012 H. Design Make: 1. CAT6 Riser Rated CommScope/SYSTIMAX 1071E, 4p air, CMR Riser rated with blue jacket. 2. CAT6 Plenum CommScope/SYSTIMAX 2071E, 4pair, CMP Plenum rated with blue jacket. 3. CAT6A Riser CommScope/SYSTIMAX 1091B, 4pair, CMR Riser rated with green jacket. 4. CAT6A Plenum CommScope/SYSTIMAX 2091B, 4pair, CMP Plenum rated with green jacket. I. Acceptable Manufacturers: 1. Berk Tek Lanmark 1000 2. Panduit GenSPEED 6000 2.2 GENERAL REQUIREMENTS FOR CONNECTING HARDWARE 100 OHM UTP A. Physical Characteristics 1. Each UTP cable will be terminated at the outlet with a MiniCom Executive Series 8 position 8 wire Category 6 or 6A RJ45 modular jack. 2. Jacks shall be 8 position unkeyed 3. The manufacturer shall have conducted performance testing at the component level by a UL certified testing laboratory, and include Active Live Channel Testing to insure manufacture and performance quality. 4. Jack housings shall be high impact 94 V0 rated thermoplastic 5. Jack modules shall have a temperature rating of 10 °C (14°F) to 60°C (140 °F) in conformance with ANSI/TIA568C 6. Jack modules shall be used in all work areas and shall exceed the connector requirements of the ANSI/TIA Category 6 or 6A standard. 7. Jack modules shall be 100% tested to ensure NEXT performance. ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 9 OF 21 JUNE 29, 2012 8. Jack modules shall be universal in design, including complying with the intermateability standard IEC 606037 for backward compatibility. 9. Category 6 modules shall have UL and CSA approval. 10. The modules shall be able to be reterminated a minimum of 10 times. 11. The modules shall have ETL verified Category 6 performance and ISO Class E performance (as defined in ISO/IEC 11801) in both the basic and channel links. They shall be universal in design, accepting six or eightpair modular plugs w ithout damage to the outer module contacts. 12. Jack modules shall have a designation indicating Category 6 or 6A compliance. Jack module shall also have a date code and a complete catalog number and abbreviated series numbers indicated on each module. 13. Jacks shall utilize a paired punch down sequence. Cable pair twists shall be maintained up to the IDC, terminating all conductors adjacent to its pair mate to better maintain pair characteristics designed by the cable manufacturer. 14. The module shall snap into all MiniCom outlets and patch panels. 15. Jacks shall terminate 2226 AWG unshielded twis ted pair cable, stranded or solid conductors. 16. Jacks shall terminate insulated conductors with outside diameters up to .050” 17. Jacks shall be compatible with single conductor 110 impact termination tools. 18. Jacks shall include translucent wire termination/retention stuffer cap, that holds terminated wires in place, provides positive locking latch to proper conductor strain relief on the cable jacket, and allow the conductors to be visually inspected in the assembled housing can ensure cable twists can be maintained to within 1/8” (3.18mm). 19. Jack modules shall be compatible with ANSI/TIA 606A color code labeling and each module shall include a label marked with both T568A and T568B wiring schemes. ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 10 OF 21 JUNE 29, 2012 20. The jack module shall include an identification to signify Category 6, 330 MHz performance. 21. Meets FCC Part 68 Subpart F; contacts plated with 50 microinches of gold. 22. Jack modules shall be manufactured in the USA B. Jack modules shall be UL LISTED 1863 and CSA certified. C. Jack modules shall be made by an ISO 9002 Certified Manufacturer. D. Jack modules installed in a 4connector channel with a category 6 patch panel and category 6 patch cords, all from the same manufacturer and designed to be installed together, along with a qualified category 6 cable shall meet or exceed the channel requirements of the ANSI/TIA568C ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 11 OF 21 JUNE 29, 2012 E. Jack modules installed in a 4connector channel configured as described in section d above, shall exhibit a worst pair channel NEXT loss of at least the following, and be fully compliant with the manufacturer performance requirements for the warranty specified and meets or exceed the permanent link and channel requirements of the ANSI/TIA568C.1 Standard. Frequency NEXT MHz dB 1.0 65.0 4.0 63.0 8.0 58.2 10.0 56.6 16.0 53.2 20.0 51.6 25.0 50.0 31.25 48.4 62.5 43.4 100.0 39.9 200.0 34.8 250.0 33.1 ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 12 OF 21 JUNE 29, 2012 F. Jack modules installed in a 4connector channel configured as described in section d above, shall exhibit a worst pair channel PSNEXT loss of at least the following, and be fully compliant with the manufacturer performance requirements for the warranty specified and meets or exceed the permanent link and channel requirements of the ANSI/TIA568C.1 Standard. Frequency PSNEXT MHz DB 1.0 62.0 4.0 60.5 8.0 55.6 10.0 54.0 16.0 50.6 20.0 49.0 25.0 47.3 31.25 45.7 62.5 40.6 100.0 37.1 200.0 31.9 250.0 30.2 ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 13 OF 21 JUNE 29, 2012 G. Jack modules installed in a 4connector channel configured as described in section d above, shall exhibit a worst pair channel Insertion Loss of not more than the following, and be fully compliant with the manufacturer performance requirements for the warranty specified and meets or exceed the permanent link and channel requirements of the ANSI/TIA568C.1 Standard. Frequency Insertion LOSS MHz DB 1.0 2.1 4.0 4.0 8.0 5.7 10.0 6.3 16.0 8.0 20.0 9.0 25.0 10.1 31.25 11.4 62.5 16.5 100.0 21.3 200.0 31.5 250.0 35.9 ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 14 OF 21 JUNE 29, 2012 H. Jack modules installed in a 4connector channel configured as described in section d above, shall exhibit a worst pair channel ELFEXT loss of at least the following, and be fully compliant with the manufacturer performance requirements for the warranty specified and meets or exceed the permanent link and channel requirements of the ANSI/TIA568C.1 Standard. Frequency ELFEXT MHz DB 1.0 63.3 4.0 51.2 8.0 45.2 10.0 43.3 16.0 39.2 20.0 37.2 25.0 35.3 31.25 33.4 62.5 27.3 100.0 23.3 200.0 17.2 250.0 15.3 ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 15 OF 21 JUNE 29, 2012 I. Jack modules installed in a 4connector channel configured as described in section d above, shall exhibit a worst pair channel PSELFEXT loss of at least the following, and be fully compliant with the manufacturer performance requirements for the warranty specified and meets or exceed the permanent link and channel requirements of the ANSI/TIA568C.1 Standard. Frequency PSELFEXT MHz DB 1.0 60.3 4.0 48.2 8.0 42.2 10.0 40.3 16.0 36.2 20.0 34.2 25.0 32.3 31.25 30.4 62.5 24.3 100.0 20.3 200.0 14.2 250.0 12.3 ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 16 OF 21 JUNE 29, 2012 J. Jack modules installed in a 4connector channel configured as described in section d above, shall exhibit a channel return loss of at least the following, and be fully compliant with the manufacturer performance requirements for the warranty specified and meets or exceed the permanent link and channel requirements of the ANSI/TIA 568C.1 Standard. Frequency Return Loss MHz DB 1.0 19.0 4.0 19.0 8.0 19.0 10.0 19.0 16.0 18.0 20.0 17.5 25.0 17.0 31.25 16.5 62.5 14.0 100.0 12.0 200.0 9.0 250.0 8.0 K. Jack modules installed in a 4connector channel shall exhibit a delay skew of not more than 50 ns/100 m between 1 and 250 MHz. L. Modular Jack Design Make: 1. CAT6 Panduit MiniCom TX6 Plus Jack Module TP Series, Electric Ivory (or color to match existing conditions or as called for Panduit # CJ688TPEI Series. Confirm wiring s cheme with Owner for all Category 6 terminations. 2. CAT6A Panduit MiniCom TX6A Plus Jack Module T P Series, Electric Ivory (or color to match existing conditions or as called ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 17 OF 21 JUNE 29, 2012 for Panduit # CJ688TGEI Series. Confirm wiring s cheme with Owner for all Category 6 terminations. 2.3 FACEPLATE DESIGN MAKES AND OPTIONS A. Double Gang – Panduit CBEEI2G Minicom executive series, 8 module, Ivory B. Single Gang Vertical – series. Panduit # CBEE1 C. Box/Surface Mount, 2 module Panduit # CBXJ2EIA D. Bezel Insert Sloped 2 Module Space Ivory Panduit # CHS2EIX (10pk) E. Bezel Insert Flat Blank 2 Module Wide Ivory Panduit # CHB2EIX F. Single Gang Horizontal four port – Panduit #CFPHSL4EI series 12 Port MUTOA – Panduit #CBXF12EIAYRefer to requireme nts on program standard detail drawings for recessed, surface boxes and surface raceway outlet configurations and sloped bezel versus flat bezel arrangements. I. Blank plates matching existing plastic ivory communication faceplates – to be provide by Telecommunication Contractor for all existing unused flush backboxes and all surface raceway openings where cable are removed under this contract. 2.4 WALL PHONE JACK ASSEMBLY A. Shall be constructed of stainless steel B. Shall have permanently affixed steel mounting studs designed to mate with corresponding telephone base plate or adapter. C. Shall mount to single gang outlet box, surface box or to wall directly. D. Shall be wired to wiring scheme as directed by Owner. E. Rated for CAT 6 including testing. F. Shall be 8position and 8conductor. G. Design Make: Panduit KWP6PYas approved by Owner. H. Acceptable Manufacturers: 1. Suttle Appartus/CSI 2. Lucent/Avaya ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 18 OF 21 JUNE 29, 2012 3. CommScope/Systimax 2.5 PATCH CORDS, CATEGORY 6 – TO BE PROVIDED BY THE OWNER (CIT/NCS FIELD SERVICES GROUP). 2.6 TELEPHONE LINE CORDS – TO BE PROVIDED BY THE OW NER (CIT/NCS FIELD SERVICES GROUP). 2.7 VOICE CROSS CONNECT AND FRAME WIRE – TO BE PROVIDED BY THE OWNER (CIT/NCS FIELD SERVICES GROUP). PART 3 EXECUTION 3.1 INSTALLATION A. UTP Cable: 1. All exposed wiring shall be installed in surface metal raceway, conduit, and enclosed cable tray, except within TR’s. 2. All wiring above ceilings shall be installed in cable tray, conduit, raceway or limited use of jHooks as called for. 3. Shall be installed to provide minimal signal impairment by preserving wire pair twists as closely as possible to the point of mechanical termination. The amount of untwisting in a pair as a result of termination shall be no greater than 0.5 inches (13 mm). 4. Shall be installed according to manufacturer’s instructions. 5. Shall be installed such that cables can maintain minimum bend radius of at least 4 times the cable diameter. Cables shall be terminated in such a way that there is no tension on the conductors in the termination contacts 6. Shall be installed in one continuous length unless specified in the contract document. 7. The Contractor shall be responsible for replacing all cables that do not pass required bandwidth and throughput tests. 8. Maximum length shall be 90 meters, TR termination to WAO termination. 9. Cable shall have no physical defects such as cuts, tears or bulges in the outer jacket. Cables with defects shall be replaced. ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 19 OF 21 JUNE 29, 2012 10. Install cable in neat and workmanlike manner. Neatly bundle, support and tie all cable in closets, in both the vertical and horizontal plane. Leave sufficient cable for 90o sweeps at all vertical drops. 11. Provide reusable velcrotype hook and loop stra ps in each rear vertical channel. Reusable straps shall be of varying sizes (each allowing 50% spare future expansion) and of adequate quantity to secure cable bundles at least every 4 rack units 12. Provide reusable velcrotype hook and loop stra ps in each horizontal of overhead ladder rack/cable runway. Reusable straps shall be of varying sizes (each allowing 50% spare future expansion) and of adequate quantity to secure cable bundles at least every 3’ in straight runs and at least every 12” in radius turns and waterfalls. 13. Provide reusable velcrotype hook and loop stra ps in each vertical run of ladder rack/cable runway. Reusable straps shall be of varying sizes (each allowing 50% spare future expansion) and of adequate quantity to secure cable bundles at least every 12”. 14. Maintain the following clearances from EMI sources. a) Power cable 6 in. b) Fluorescent Lights 12 in. c) Transformers 36 in. 15. Adhere to TIA standard requirements regarding pulling tension and allowable lubricants. 16. Do not install Category 6 or 6A cable with more than 110N (25 lbs) pull force, as specified in ANSI/TIA and BICSI TDDM practices. Utilize appropriate cable lubricant in sufficient quantity to reduce pulling friction to acceptable levels on: long pulls inside conduit, pulls of multiple cables into a single small bore conduit, on conduit runs greater than 100 lineal feet with bends of opposing directions, and in conduit runs that exceed 180 degrees of accumulated bends. Use of tensile rated cords (i.e. fishing line) should be used for difficult or questionable pulls to judge to go/nogo condition of the conduit and pull ing setup. 17. Care must be taken so that the cable does not bend at any location to a radius less than ten times the diameter of the cable. A cable feeder guide or rollers of suitable dimensions ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 20 OF 21 JUNE 29, 2012 should be used between the cable reel and the face of the duct to protect the cable and guide it into the duct as it is pulled off the reel. 18. As the cable is pulled off the reel, it should be carefully watched and inspected for sheath defects. If defects are noticed, the pulling operation should be stopped immediately and the Engineer promptly notified of the defect. Kinks and/or other irregularities in the cable sheath should be removed or corrected as directed by the engineer. 19. Cable jackets that are chaffed or burned exposing internal conductor insulation or have bare conductors shall be replaced, not spliced 20. Test, label and document as called for. 21. Firestop the interior of fire rated assembly openings where sleeves, conduits, raceways, cable trays or cables are installed through a fire barrier. B. UTP MODULAR JACKS 1. All cables shall be terminated with modular jacks that snap into a faceplate mounted on a wall outlet box, surface raceways or power pole. 2. Outlet boxes shall be secured to building with mechanical fasteners. Adhesive fasteners are not allowed. 3. Jacks shall be installed to provide minimal signal impairment by preserving wire pair twists as close as possible to the point of mechanical termination. The amount of untwisted in a pair as a result of termination to the jack shall be no greater than 0.5 inches (13mm). 4. Jacks shall be installed according to manufacturer’s instructions and properly mounted in plates, frames, housings or other appropriate mounting device. 5. Jacks shall be installed such that cables terminated to the jacks maintain minimum bend radius of at least 4 times the cable diameter into the IDC contacts. Cables shall be terminated on jacks such that there is no tension on the conductors in the termination contacts. 6. All extra openings to be filled with blank inserts. ARCHITECHNOLOGY CORNELL – NCP HORIZONTAL REQUIREMENTS STANDARD SPECIFICATIONS 27 15 00 – PAGE 21 OF 21 JUNE 29, 2012 7. Terminate cable per EIA/TIA T568B standard pin assignments. C. FIRESTOPPING 1. Firestop all sleeves and conduit openings after each cable installation are roughedin and complete. 2. Never leave breaches in two and three hour rated assemblies open for more than a 24 hour period. 3. Provide firestopping as called for in Section 07840 and Section 27 05 00 END OF SECTION Fax: 585.424.4239 115 METRO PARK ROCHESTER, NY 14623 www.archi-technology.com PHONE: 585.424.1952 ISSUE DATE: PROJECT MANAGER: DRAWN BY: CHECKED BY: AT-27052823 SC,CP/SW - SURAFCE RACEWAY TO CEILING, SURFACE THROUGH WALL AT STANDARD DETAILS