Loading...
HomeMy WebLinkAbout26 01 00 - Electrical General ProvisionsBEARDSLEY DESIGN ASSOCIATES CORNELL – NCP ELECTRICAL GENERAL PROVISIONS STANDARD SPECIFICATIONS 26 01 00 PAGE 1 of 3 JUNE 29, 2012 SECTION 260100 ELECTRICAL GENERAL PROVISIONS PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. The Contract Drawings and the General Provisions of the Contract, including the General Conditions of the Contract for Construction, Supplementary Conditions, Special Conditions and Division 1 Specification Sections apply to the work of this Division. 1.2 SUMMARY: A. This Section includes general administrative and procedural requirements for Division 26, Electrical work. 1.3 DIVISION 26 6 DESCRIPTION: A. The technical specifications of this Contract are arranged for the convenience of the Owner and Contractor into Divisions of work. The work of Division 26, Electrical, is further described in Specification Sections of the 26000 Series and on contract drawings of the "E" series. B. The organization of this work into Divisions shall not relieve the Prime Contractor from providing all of the work shown on the complete set of drawings or specified in the complete set of Specifications, whether or not the individual subcontractors correctly identify their respective responsibilities. 1.4 OTHER DIVISION SPECIFICATIONS APPLICABLE TO THIS WORK: A. To the extent that the work of this Division or Contract includes the work of other trades, the Contractor for this Division shall adhere to the requirements of other specification sections. All General Construction work shall be performed in accordance with the provisions of the appropriate Division. All mechanical work shall be performed in accordance with appropriate Division 23 Sections. 1.5 WORK INCLUDED: The work of this Division shall include providing all materials, labor, services, permits and related work to furnish a complete, operating, tested, functioning, documented Electrical System including all work shown, specified or required for proper system operation including but not limited to the following: A. Provide Demolition and Removal of Existing Circuits, Devices, and Fixtures, Where Shown, Including Removal of All Debris from Site and Proper Disposal of Same. B. Provide Additions and/or Modifications to Existing Electrical Panelboards. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP ELECTRICAL GENERAL PROVISIONS STANDARD SPECIFICATIONS 26 01 00 PAGE 2 of 3 JUNE 29, 2012 C. Provide Basic Materials and Methods. D. Provide Electrical Equipment Identification. E. Provide Equipment and Conductor Identification. F. Provide Electrical Coordination Drawings. G. Provide Motor Starters and Disconnects where required. H. Provide Grounding System where shown. I. Provide New Lighting Fixtures Including Appurtenances. J. Provide Conduits, Boxes, Raceways for New Branch Circuits. K. Provide Additions and/or Modifications to the Existing Fire Alarm System L. Provide Testing of Equipment and Conductors. M. Provide Relocations of Equipment and Lighting Fixtures Where Shown. N. Provide Certificate of Compliance and Fees for Permits and Inspections. O. Provide Openings in Existing and New Construction as Required for the Work of this Division. Provide Fire Seal for All Penetrations. P. Provide Sleeves and Inserts Q. Provide Maintenance of System until Final Acceptance. R. Provide Cooperation and Coordination with Owners Telecom. Vendors. S. Provide Owner's Operation Instruction 1.6 SUBMITTALS: A. Provide Shop Drawings for the following: 1. Fire Alarm System Devices 2. Lighting Fixtures 3. Panels and Circuit Breakers 4. Smoke Detectors and Fire/Smoke Dampers 1.7 RELATED WORK NOT INCLUDED: A. The Owner’s telecommunication vendor shall install cabling and faceplates for telephone, computer and television and audio visual. Final terminations shall be performed by Owner's vendors. 1.8 ALTERNATES / ALLOWANCES: A. Refer to Division 01 for a description regarding alternates/allowances, if applicable. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP ELECTRICAL GENERAL PROVISIONS STANDARD SPECIFICATIONS 26 01 00 PAGE 3 of 3 JUNE 29, 2012 1.9 PERMITS AND INSPECTIONS: Division 26 shall be responsible to apply for, obtain and meet the requirements of all permits and inspections required by jurisdictions for the work of Division 26. Division 26 shall pay all fees associated with these permits and inspections. 1.10 CODE RULES AND ENGINEER INSPECTIONS: A. The electrical installation shall meet the requirements of the National Electrical Code and of the National Fire Protection Association. In addition, all state, municipal or other codes, rules or regulations applicable to the work shall be followed. B. Final inspection of the complete electrical system shall be performed prior to final payments. PART 2 PRODUCTS 2.1 See Applicable Division 26 Section. PART 3 EXECUTION 3.1 See Applicable Division 26 Sections END OF SECTION 26 01 00 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP ELECTRICAL GENERAL PROVISIONS STANDARD SPECIFICATIONS 26 01 00 PAGE 1 of 3 JUNE 29, 2012 SECTION 260100 ELECTRICAL GENERAL PROVISIONS PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. The Contract Drawings and the General Provisions of the Contract, including the General Conditions of the Contract for Construction, Supplementary Conditions, Special Conditions and Division 1 Specification Sections apply to the work of this Division. 1.2 SUMMARY: A. This Section includes general administrative and procedural requirements for Division 26, Electrical work. 1.3 DIVISION 26 6 DESCRIPTION: A. The technical specifications of this Contract are arranged for the convenience of the Owner and Contractor into Divisions of work. The work of Division 26, Electrical, is further described in Specification Sections of the 26000 Series and on contract drawings of the "E" series. B. The organization of this work into Divisions shall not relieve the Prime Contractor from providing all of the work shown on the complete set of drawings or specified in the complete set of Specifications, whether or not the individual subcontractors correctly identify their respective responsibilities. 1.4 OTHER DIVISION SPECIFICATIONS APPLICABLE TO THIS WORK: A. To the extent that the work of this Division or Contract includes the work of other trades, the Contractor for this Division shall adhere to the requirements of other specification sections. All General Construction work shall be performed in accordance with the provisions of the appropriate Division. All mechanical work shall be performed in accordance with appropriate Division 23 Sections. 1.5 WORK INCLUDED: The work of this Division shall include providing all materials, labor, services, permits and related work to furnish a complete, operating, tested, functioning, documented Electrical System including all work shown, specified or required for proper system operation including but not limited to the following: A. Provide Demolition and Removal of Existing Circuits, Devices, and Fixtures, Where Shown, Including Removal of All Debris from Site and Proper Disposal of Same. B. Provide Additions and/or Modifications to Existing Electrical Panelboards. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP ELECTRICAL GENERAL PROVISIONS STANDARD SPECIFICATIONS 26 01 00 PAGE 2 of 3 JUNE 29, 2012 C. Provide Basic Materials and Methods. D. Provide Electrical Equipment Identification. E. Provide Equipment and Conductor Identification. F. Provide Electrical Coordination Drawings. G. Provide Motor Starters and Disconnects where required. H. Provide Grounding System where shown. I. Provide New Lighting Fixtures Including Appurtenances. J. Provide Conduits, Boxes, Raceways for New Branch Circuits. K. Provide Additions and/or Modifications to the Existing Fire Alarm System L. Provide Testing of Equipment and Conductors. M. Provide Relocations of Equipment and Lighting Fixtures Where Shown. N. Provide Certificate of Compliance and Fees for Permits and Inspections. O. Provide Openings in Existing and New Construction as Required for the Work of this Division. Provide Fire Seal for All Penetrations. P. Provide Sleeves and Inserts Q. Provide Maintenance of System until Final Acceptance. R. Provide Cooperation and Coordination with Owners Telecom. Vendors. S. Provide Owner's Operation Instruction 1.6 SUBMITTALS: A. Provide Shop Drawings for the following: 1. Fire Alarm System Devices 2. Lighting Fixtures 3. Panels and Circuit Breakers 4. Smoke Detectors and Fire/Smoke Dampers 1.7 RELATED WORK NOT INCLUDED: A. The Owner’s telecommunication vendor shall install cabling and faceplates for telephone, computer and television and audio visual. Final terminations shall be performed by Owner's vendors. 1.8 ALTERNATES / ALLOWANCES: A. Refer to Division 01 for a description regarding alternates/allowances, if applicable. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP ELECTRICAL GENERAL PROVISIONS STANDARD SPECIFICATIONS 26 01 00 PAGE 3 of 3 JUNE 29, 2012 1.9 PERMITS AND INSPECTIONS: Division 26 shall be responsible to apply for, obtain and meet the requirements of all permits and inspections required by jurisdictions for the work of Division 26. Division 26 shall pay all fees associated with these permits and inspections. 1.10 CODE RULES AND ENGINEER INSPECTIONS: A. The electrical installation shall meet the requirements of the National Electrical Code and of the National Fire Protection Association. In addition, all state, municipal or other codes, rules or regulations applicable to the work shall be followed. B. Final inspection of the complete electrical system shall be performed prior to final payments. PART 2 PRODUCTS 2.1 See Applicable Division 26 Section. PART 3 EXECUTION 3.1 See Applicable Division 26 Sections END OF SECTION 26 01 00 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 1 of 19 JUNE 29, 2012 SECTION 260101 BASIC MATERIALS AND METHODS PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. The Contract Documents and the General Provisions of the Contract, including the General Conditions of the Contract for Construction, Supplementary Conditions, Special Conditions and Division 1 Specification Sections apply to the Work of this Section. 1.2 WORK INCLUDED: A. Provide Basic Materials and Methods as follows: 1. Conduit 2. Conduit Fittings 3. Sleeves, Inserts and Openings 4. Support Systems 5. Wireways/Wire Troughs 6. Outlet, Junction and Pull Boxes 7. Conductors 8. Conductor Splicing Materials 9. Wiring Devices 10. Conductor Pulling Lubricant 11. Miscellaneous Painting 12. Waterproofing, Caulking and Sealing 13. Protection and Storage of Materials and the work 14. Lighting 15. Panelboards 16. Grounding 17. Telecommunication ground bar 1.3 SUBMITTALS A. Provide submittals for the following: 1. Wiring Devices 2. Panelboards 3. Transformers PART 2 PRODUCTS 2.1 MATERIALS – GENERAL: BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 2 of 19 JUNE 29, 2012 A. Conductors shall be annealed copper; 98% conductivity. B. Minimum size conductors for general wiring shall be #12. 2.2 CONDUCTORS: A. Conductors: 1. Conductors shall be annealed copper, 98 percent conductivity. 2. Grounding conductor shall have green color coded insulation. 3. Signal circuits shall be color coded using solid colors with contrasting tracer color lines. 4. Panel feeders shall be copper conductors unless otherwise shown. 5. Aluminum conductors shall not be acceptable. B. INSULATION: 1. 600 volts rating for building feeders and branch circuits. 2. 300 volts rating for signal systems operating at 50 volts or less. 3. # 12 through # 8 AWG: dry locations, use type THWN. 4. # 6 and larger in normally dry locations type THWN. 5. # 12 AWG and larger: under buildings, slab on grade, steam tunnels, crawlspaces, boiler rooms, pump house, kitchen, mechanical rooms, use type THWN. Make: Anaconda, General Cable, Rome Cable, Circle, General Electric, Essex, Okonite, BrandBRex. 2.3 CONDUCTOR SPLICING MATERIALS: A. Wires #8 and smaller: PreBinsulated solderless connectors. B. Wires #6 through #4/0: Compression or split bolt type connectors as manufactured by Dossert, Burndy, or T & B. C. Wires larger than #4/0: Compression or split bolt type connectors with minimum two pressure points per conductor. D. Wire connectors or splicing means installed on conductors for direct burial shall be UL listed for such. 2.4 CONDUCTOR PULLING LUBRICANT: A. The cable lubricant shall meet the following performance specifications: 1. When subjected to a 100 lbs./ft. Normal force, between (type) cable and (type) conduit, the lubricated cable system shall have a BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 3 of 19 JUNE 29, 2012 coefficient of kinetic friction less than .25 (pulling force greater than lbs./ft.) 2. The lubricant shall be U.L. (or CSA) listed. 3. When used on high voltage cable, the lubricant shall not affect the volume resistivity of any semiBconducting jacket or insulation shield present. The volume resistivity of the semiBconducting material shall at no time increase more than 100% when tested via the ICEA TB25B425 method, 90 degrees centigrade exposure, 7 day test, readings made at 23 degrees centigrade daily. 4. The lubricant shall not affect the tensile/elongation properties of the cable jacket more than existing ICEA/NEMA aging specifications allow. 5. The lubricant shall contain no waxes, greases, silicones, or polyalkylene glycol oils or waxes. B. Manufacturer: Polywater J. American Polywater Corporation, P.O. Box 53, Stillwater, Minnesota 55082. 2.5 CONDUIT: A. Flexible Conduit: 1. Steel interlock type, galvanized, with galvanized steel fittings. 2. Complies with NEC Article 350 and U.L. standards for flexible conduit. 3. Flex conduit to only be used for light fixture and motor connection, whips no more than 6’ in length. 4. Make: Galflex or acceptable manufacturer. B. Electrical Metallic Tubing (EMT) 1. EMT shall be low carbon steel, with set screw type, concrete tight fittings. 2. Exterior shall be galvanized by electrolytic process and extra coat provided by bright dip in zinc chromate solution. 3. Interior shall be coated with baked plating process. 4. Make: Cerro, Republic, Allied Tube, Youngstown, Wheatland or acceptable manufacturer. C. Rigid Metallic Conduit (RGS) 1. Rigid galvanized steel, hot dipped threaded type. 2. Galvanized threaded malleable iron fittings. 3. Make: Cerro, Republic, Allied Tube, Youngstown, Wheatland acceptable manufacturer. 2.6 CONDUIT FITTINGS: A. EMT: BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 4 of 19 JUNE 29, 2012 1. All fittings shall be U.L. listed steel or malleable iron. 2. Branch circuit conduits larger than 1” diameter and conduits containing feeders serving panelboards shall have grounding type bushings. 3. Set screw type fittings, Concrete tight as manufactured by Neer, OZ Gedney, Bridgeport or acceptable manufacturer. 4. Compression connectors, squeeze type Efcor or acceptable manufacturer. B. Flexible: 1. Fittings shall be UL listed steel or mallable iron. 2. Fittings for flexible steel conduits shall be squeeze type as manufactured by Thomas and Betts, Steel City or Appleton. C. Liquidtight: 1. Fittings shall be malleable iron, tapered hub threads, with safeB edge ground cone and double bevel sealing ring. 2. Fittings for liquid tight flexible conduits shall be screwBin type manufactured by Thomas and Betts Company or Pittsburgh Standard Conduit Company. D. Rigid Conduit: 1. Bushings for metal conduit terminations shall be the nylon insulated type throat, with grounding type locknut ahead of bushing. 2. Die cast zincBalloy and pressure cast and indenter type fittings shall not be approved. Provide steel or malleable iron only. 3. Conduit hubs shall be as manufactured by Myers Electric Products, Inc., Raco, T&B, General Electric Company or acceptable manufacturer. E. Die cast, pressure cast, potted metal or similar type fittings shall not be used. 2.7 CONDUIT SUPPORT SYSTEMS: A. Trapeze type hangers: 1. Steel horizontal members and threaded hanger rods. 2. Rods shall not be less than ½" diameter. 3. Make: Kindorf GB953 Series, or acceptable manufacturer in Unistrut or BBline complete with all necessary bolts, screws, angles, anchors, connection plates, straps, etc., as required to perform the necessary functions. B. Conduit Clamps and Supports: 1. Steel hangers and threaded hex nuts. 2. Kindorf CB149 series or acceptable manufacturer in Unistrut or BB BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 5 of 19 JUNE 29, 2012 line complete with all necessary bolts, screws, angles, anchors, connection plates, straps, etc as required to perform the necessary functions. 2.8 OUTLET, JUNCTION AND PULLBOXES: A. Types: 1. Galvanized, stamped steel shall be provided when recessed in construction or exposed on walls and ceilings in dry areas. 2. Deep condulet style with hubs, or Myers hubs for exposed work in damp area or wet location or for weatherproof type outlets. 3. Large pullboxes shall require 14 gauge galvanized steel, fold and weld construction; with 14 gauge galvanized and gasketed steel cover secured in place by galvanized sheet metal screws on maximum 10 inches centers. All cut edges to be free of burrs. 4. Provide cast iron, gasketed, watertight boxes where installed in earth, surface mounted outdoors, where threaded connection is needed. B. Size: Provide as required for number and size of conduit and conductors. Coordinate depth to suit wall depth and construction. Use special forms and designs as required for outlet facilities. C. Covers: Provide design and style to suit outlet box and electric facility. Provide for all unused or nonBdesignated boxes. NEMA 1, 12, 3R, rating for area environment and use watertight cover with gasket for exterior boxes. D. Fixture Studs: Use 3/8 inch studs and securely fastened to support fixtures. E. Make: Appleton, CrouseBHinds, O.Z. Gedney, National, Steel City, Raco, PyleBNational. 2.9 SLEEVES, INSERTS AND OPENINGS: A. "LinkBseal" assembly as manufactured by Thunderline (see Execution for locations). B. Schedule 40 steel pipe, packed with fire barrier wool and caulk (see Execution for locations). C. Fire barrier wool and caulk. No sleeve necessary (see Execution for locations). D. Where 3 hour fire rating is required, use split collar fire seal with sleeve. 2.10 WIRE WAYS AND WIRE TROUGH: BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 6 of 19 JUNE 29, 2012 A. Use hinged cover type wire way with provisions for full layBin along the entire length of run. B. Wire way shall be steel, enclosed with gray enamel finish. C. Use JK sectional NEMA dust resistant, oil tight type where subjected to moisture, in pump rooms, mechanical, electric and fan rooms, exterior wall, shops, maintenance shop, and similar locations. D. Knockouts along runs. E. Provide all elbows, tees, pullboxes, fittings, hangers, reducers, supports, etc., to meet installation requirements. F. Size as shown on drawings or code size where not noted. G. Make: Square D "Square Duct" or acceptable manufacturer by Hoffman, General Electric, Meco. 2.11 WIRING DEVICES: A. Receptacle, Duplex: 1. Grounding type, parallel blade with standard or grounding caps, high strength nylon construction. 2. For side or back wiring, with break off strip for two circuit wiring. 3. U.L. listed, 20 amp circuit rating, NEMA type 5B20R. 4. Extra hard use specification grade. 5. Make: Pass & Seymour PT5362A or acceptable manufacturer. B. Switches, Local: 1. Toggle operated A.C. type. 2. Specification grade, slow make, slow break. 3. 20 amperes at 120V rating. 4. Make: Sierra, ArrowBHart, circle F, Slater, P&S, Hubbell HBL 1221L single pole, HBL 1223L three way, Hubbell HBL 1224 four way or acceptable manufacturer. 2.12 CEILING PLATES A. Round ceiling plate, white finish, steel, to cover existing castBinBplace ceiling boxes. B. Mulberry Model 40430 or acceptable manufacturer. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 7 of 19 JUNE 29, 2012 2.13 WARRANTY: A. Provide one year manufacturer's warranty on all equipment, materials and products. Where shown or specified, provide manufacturer's extended warranty. 2.14 PANELBOARDS: A. Panelboards shall be type “Lighting and Power Distribution”, with 22,000 AIC interrupting rating unless noted otherwise. Load centers shall not be permitted. Panelboards shall be fully rated and shall include main breakers, and type written circuit directory. 2.15 DRYBTYPE TRANSFORMERS A. Transformers shall be NEMA Type TPB1, dryBtype, copper windings, with 5 secondary taps, suitable for wall or floor mounting; size and voltage as shown on Drawings. PART 3 EXECUTION 3.1 COLOR CODING AND NUMBERING: A. Color coding for branch circuits and feeders. 1. 120/208 volt, 3 phase, 4 wire Wye system. a. Phase A – Black b. Phase B – Red c. Phase C – Blue d. Neutral – White e. Grounding Conductor – Green 2. 277/480 volt, 3 phase, 4 wire, Wye system a. Phase A – Brown b. Phase B – Orange c. Phase C – Yellow d. Neutral – Gray e. Grounding Conductor – Green 3. 120/240 volt, 3 phase, 4 wire, Delta system a. Phase A – Black b. Phase B – Orange (wild leg) c. Phase C – Blue d. Neutral – White e. Grounding Conductor – Green 4. Identify grounded (neutral) conductors in accordance with NEC BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 8 of 19 JUNE 29, 2012 Article 200 when it is shared or common raceways and enclosures B. Number code all control and instrumentation wiring at termination points. 3.2 SPARE RECEPTACLES A. Provide four (4) additional spare TVSS receptacles. 3.3 LAYING OUT WORK A. Conform to Section 013100 – Project Coordination 3.4 MISCELLANEOUS PAINTING: A. Conform to Section 099123 – Interior Painting B. Conform to Section 011000 – Summary of Work C. Conform to Section 011200 – Multiple Contract Summary D. Conform to Section 017329 – Cutting and Patching 3.5 EQUIPMENT INSTALLATION: A. Conform to Section 013100 – Project Coordination B. Conform to Section 014000 – Quality Control Service 3.6 NOISE AND VIBRATION: A. Install all equipment to be free of transmission of noise and vibration to occupied spaces. Arrange isolated equipment so that it does not contact members of the building structure, ceiling grids, piping, conduits or ductwork. B. Provide replacement at no cost to the Owner of any pump, motor, motor starter, or lighting fixture, transformer, UPS system, other equipment which in the opinion of the Engineers produces excessive vibration or noise. 3.7 ADJUSTING AND INITIAL LUBRICATION: A. Conform to Section 014000 – Quality Control Services BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 9 of 19 JUNE 29, 2012 3.8 EQUIPMENT CHECKOUT AND TESTING: A. Conform to Section 014000 – Quality Control Services 3.9 CONDUITS: A. General: 1. Securely support conduit from building construction, separately from outlets and boxes which are secured to the building. Supports shall be spaced at intervals of eight (8) feet maximum or as required by NEC code. 2. Conduit runs shall be concealed unless otherwise specified. Do not expose in finished room unless specifically permitted. 3. Conduit runs shall be exposed in electrical, mechanical and fan rooms. 4. Conduit runs shall be installed neatly and parallel to ceilings, walls, and floors. 5. All conduits and fittings on exposed work shall be secured by means of metal clips on back plates. 6. Avoid installation adjacent to hot surfaces. Raceways shall be spaced from heat sources as follows: a. Steam: no conduit within 12 inches of outside surface of insulation. b. Hot water piping: 6 inches minimum from outside surface of insulation. 7. Provide one pull box or junction box per three 90 bends in any one conduit run. 8. Plug openings until wire is installed and ream conduit joints and ends before installation. Wires shall not be pulled until conduit system is completed in all details. 9. Conduits feeding panelboards; pull boxes. a. Terminations at each pullbox, panelboard and switch board shall have double locknut (one inside and one outside) b. Provide a minimum of two 1 inch conduit stubs from each flush mounted panelboard to an accessible ceiling space above the panel, in an adjacent area or at the ceiling line. 10. Conduit terminating in gasketed enclosures shall be terminated with conduit hubs or Myers hubs. 11. Avoid installing conduits in water or where excessive moisture exists. For conduits terminating to boxes in wet areas, use Myers hub fittings. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 10 of 19 JUNE 29, 2012 B. EMT: 1. Use in dry locations for concealed or exposed work. C. Liquidtight Conduit: 1. Use for terminating connection for motors, compressors, air conditioners, sound equipment and dry type transformers. 2. Provide proper fittings with insulated throats. Provide green wire ground. 3. Use Liquidtight conduit and fittings in outdoor locations and in pump rooms, garages, elevator pits and other locations subjected to moisture. 4. Use for all motor transformer terminations and other equipment where vibration is present. D. Flexible Conduit: 1. Install as terminating connection for motors, compressors, air conditioners, sound equipment and dry type transformers in dry areas as shown or scheduled. 2. Install green wire ground in all flexible conduit. 3. Flex conduit to be used only for light fixtures and motor connections, whips no more than 6’ in length. E. RGS: 1. Use in dry locations for concealed or exposed work where shown. 2. Use in or under concrete pours. 3. Use where exposed to weather. 4. Where run in earth and below slab on grade, encase conduit in 1B 1/2” concrete envelope unless otherwise noted. 5. Use where noted on drawings. 3.10 CABLE LUBRICATION AND LUBRICANT: 1. The cable jacket and/or conduit walls shall be completely lubricated when cable is pulled into conduit. The lubricant shall be applied immediately before or during the pull. 2. Minimum quantities of lubricant are as follows: a. 1 quart of lubricant per 100 feet of 1 inch conduit. b. 2 quarts of lubricant per 100 feet of 2 inch conduit. c. 3 quarts of lubricant per 100 feet of 3 inch conduit. d. 1 gallon of lubricant per 100 feet of 4 inch conduit. 3. This quantity shall be increased as needed for difficult pulling situations BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 11 of 19 JUNE 29, 2012 (high temperatures, multiple bends, poorly placed conduit, etc.) 4. Cable attachments for pulling shall be patent cable grips, or other devices subject to the Owner's approval. In using woven basket type grips on covered cable, care shall be taken to avoid damage to the cable and seal, which shall be marked up and maintained during cable installation. Difficult pulling is not anticipated; if unduly difficult pulling occurs, the Contractor shall check pull required and suspend further pulling until further procedure has been approved by the Owner. Maximum pull tension shall not exceed recommended value for the cable when measured by tension dynamometer. 5. Cable pulling during low temperatures is subject to review by the Owner and shall be discontinued when, in the Owner's and Engineers opinion, the cable may be damaged. 6. The Contractor shall keep records of all cables pulled, meggered and terminated. Exact lengths of cables installed shall be supplied to the Owner. 3.11 CONDUIT FITTINGS: A. EMT: 1. Provide EMT connector and nylon bushing at all EMT plain end terminations for power, CATV, communications and computer. 2. Use set screw type, concrete tight indoors, dry locations. 3. Use compression connectors, squeeze type in wet locations. B. RGS: 1. Provide galvanized steel locknuts at each termination unless hubs are used. 2. Use sealing locknuts for all wet/damp areas. 3. Use grounding type locknuts for rigid terminations not equipped with grounding bushings. 3.12 CONDUIT HANGERS: A. General: 1. Investigate thoroughly, Architectural and Shop Drawings related to work, to determine how equipment, fixtures, piping, ductwork, etc, are to be supported, mounted or suspended. Provide extra steel, bolts, inserts, pipe stand brackets, or any other items required for proper support. Provide supporting accessories where required, whether or not shown on the drawings. Where directed, furnish drawings showing supports, etc., for approval. 2. Conduit hanger rods in areas where hot dipped galvanized conduit is installed shall be galvanized steel, sprayed with one coat of BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 12 of 19 JUNE 29, 2012 Rustoleum paint. 3. Size support member within load rating of member section, and without visible deflection. 4. Mount conduit on top of support member unless space considerations prevent installation; use conduit clamps. 5. Provide channels for racking up conduit, trapeze, suspensions, cable racks, panel racks, etc., as shown and as required and provide pouredBinBplace inserts for supporting channels. B. Conduit Clamps: 1. Single conduits shall be supported by means of oneBhole pipe clamps in combination with oneBscrew back plates to raise conduits from the surface. C. Trapeze Hangers: 1. Multiple runs of conduits shall be supported by means of trapeze hangers, keeping conduits as high as possible with minimal beads and offsets in height. 3.13 SURFACE RACEWAYS: A. Surface Raceways: 1. Blank cover raceways shall be provided where shown, or as approved in advance by the Engineer. 2. Secure to structure at 5 foot intervals. 3. All surface boxes to be independently secured to structure. 4. Provide separate green grounding wire within each surface raceway and extend back to ground of serving panelboard. 5. Paint all raceways to match adjacent walls. 3.14 CONDUCTOR SPLICING MATERIALS: A. Splices and connections for lighting and receptacles shall be made in accessible outlets, pullboxes or junction boxes. B. Insulate all splices, taps and connections for lighting and receptacles with U.L. labeled gauge plastic tape or molded composition caps. C. Splices shall not be made except where called for by the drawings, or where specifically permitted by the Owner. Where splices are permitted, they shall be made in a neat, workmanlike and approved manner by those specialized in this class of work, close attention being paid to all splices with particular attention to splices on higher voltages. Splices shall be made by the Contractor for each type of wire or cable in accordance with instruction issued by Cable Manufacturers and the Owner. Before splicing, insulated cables shall have conductor insulation stepped and bound or penciled for recommended distances back from BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 13 of 19 JUNE 29, 2012 splices to provide a long leakage path. After splicing, insulation equal to that on the spliced conductors shall be applied at each splice. In baring conductors for splices, care shall be taken to avoid nicking strands. 3.15 CONDUCTORS: A. All wire and cable shall be installed in an approved raceway. B. Provide wire and cable in conduit for all feeders, motor circuits, lighting circuits, receptacle circuits, equipment circuits, etc., as shown on drawings. C. Coil slack wire at outlets, inside the outlet boxes and seal the outlet opening with cardboard or fiber plug to prevent entrance of concrete plaster or paint. Provide separate neutrals for all single phase circuits. D. Tag all feeders, subfeeders, special system wiring and control wiring in each pullbox/gutter space, denoting points of origin/termination of wires. E. Install a maximum of 3 phase and one neutral conductor in any one feeder or branch circuit conduit unless otherwise directed by Engineer. F. Provide supports for conductors in vertical raceways in accordance with NEC, Article 300B19. G. Flexible conduit used as connection to any equipment shall contain separate green grounding wire run back to ground bus of serving panelboard. H. Provide #12 AWG minimum size for branch circuit and emergency system wiring, #14 AWG minimum size for signal circuits. I. All wires #12 and larger and wiring to motor or other fixed equipment shall be stranded type. J. Provide #10 minimum size for branch circuit run which exceed 100 feet; unless otherwise directed. K. The neutral wire shall be identified throughout the system. Feeders shall be identified at the source and at all boxes with panel make and phase (A,B,C). L. Included in the work covered under this section is the cutting or drilling of entrance holes into enclosures, equipment terminal boxes and outlet boxes for entrance of cable not in conduit, as well as the work of cutting and drilling of holes in miscellaneous plates located in the path of cable runs. Entrance holes for cable shall be installed around cable, as part of the work of installing cable, sealing bushings, CrouseBHinds type: "CGB" or Owner approved equal, or conduit bushings where these alone are BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 14 of 19 JUNE 29, 2012 permissible. The work shall also include the work of packing or sealing at conduit bushings after cables are pulled, using unoiled Oakum and JM DuxBseal or Owner approved equal. M. Cables shall be formed to avoid sharp bends or edges of conduit bushings upon entering or leaving conduit terminations, and insulated wiring to approximately six inch intervals between conduit and terminals. Where outlet box, cabinet, cubicle, switchgear or other terminal points for cable are equipped with cable or wiring trays, troughs or gutters. Contractor shall pull sufficient length of each cable to permit neat arrangement of all entering cables, with leads formed and cabled or clamped as each conductor is brought to its terminal connection. No tangle box work will be accepted. N. Where reasonable practicable , the minimum radius to which an insulated conductor is bent, whether permanently or temporarily during installation, shall be ten times the diameter over the outer covering. O. Making terminal connections shall be included as part of the work, except as specifically noted. At points where the conductor and cable insulation will be terminated, terminations shall be made in a neat, workmanlike and approved manner by men specialized in this class of work, particular attention being given to higher voltage terminations, shielded conductor terminations and coaxial cable terminations. Terminations shall be made by the Contractor for each type of wire or cable in accordance with instructions issued by the Owner. Spare cables shall be trimmed, taped and bundled neatly within the cabinet so their presence will not interfere with connected terminations. They shall be trimmed to a length such that they can be made up and connected to the farthest terminal block within the cabinet. P. Before any cable terminal connections are made, conductors shall be rung out. Connections shall be made according to wiring diagrams. Polarity or phasing shall be checked before final connections are made, and corrections of polarity, phasing or rotation shall be made without additional cost to the Owner. Q. Control cable terminations shall be made in accordance with wiring diagrams, using wire numbers established by the Owner for the various control circuits. It is the intent that the Contractor shall terminate the cables which he installs, except as specifically noted. R. When control cables are to be fanned out and cabled together with cord, Contractor shall make connections to terminal blocks, and test equipment for proper operation before cables are corded together. If there is any question as to proper connection, the Contractor shall make temporary connection with sufficient length of cable so that cable can be switched to another terminal, without splicing cable. S. After pulling and splicing but before making cable terminal connections, the Contractor shall expose ends, clear each conductor, and make the BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 15 of 19 JUNE 29, 2012 required Megger test on all circuits except lighting circuits. Contractor shall test cables for motors, power, and control, with a Megger insulation testing instrument (Associated Research, Inc., Megohmmeter) before equipment is energized. In the event insulation is deficient, repeat Megger testing shall be accomplished after corrective measures have been applied. Extreme care shall be exercised in meggering so as not to put excessive voltage on instrumentation and electronic equipment and thereby damage such devices. The Contractor shall megger all power feed cables for 10 to 15 sec., at 4000 volts on apparatus rated 2500 volts, 1000 volts on apparatus rated 550 volts to 2500 volts and 500 volts on apparatus rated less than 500 volts. The cable shall be meggered first on the reel before pulling and then again on a cableBbyBcable basis after being cut and pulled. T. A check shall be made of all external and internal wiring for loose connections, cable sizing and proper terminations per the elementary and connection drawings listed and attached with specification. U. All wiring systems shall be thoroughly checked before placing the system in service, for grounds, short circuits and conformity to wiring diagrams. 3.16 CONDUCTOR CIRCUITING: A. Lighting, receptacles and special circuits: 1. Lighting circuits: provide lighting arrangement as shown or 15 amperes maximum per circuit where not otherwise shown. 2. Receptacle circuits: provide 5 convenience outlets maximum per circuit unless otherwise shown or specified. 3. Special receptacle circuits: provide as indicated on drawings and as specified under special items of equipment and provide separate green conductor for grounding receptacles to panel ground bus. This includes UPS dedicate single receptacle for Telecommunication Rooms. B. Power and Control Circuits: 1. General requirements: a. Provide all power wiring. Install in conduit and make all connections to disconnect switches, motor controllers, motor and other items of electrical equipment shown on drawing details and schedules. b. Provide control wiring only as shown on electric equipment schedule and plan details. Install in conduit and make connections to motors, motor controllers, control devices, etc., including the mounting of all control devices furnished by others. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 16 of 19 JUNE 29, 2012 c. Verify exact location and rating of all motors, controllers, control devices, etc., with other contractors before roughing. d. Power and control wiring may be combined in common conduit by increasing conductor or conduit sizes as required by code. e. Provide minimum working clearances as required by NEC Article 110B16 and as shown on the drawings. 2. Wiring diagrams: a. Any wiring diagrams shown on drawings for hookup of equipment furnished by others, are approximate and are for bidding purposes only b. Obtain wiring diagrams, certified correct for the job, from respective Contractor for all equipment and systems furnished by them. c. Install all work in accordance with certified wiring diagrams. 3. Control devices: a. Do not accept control devices from other Contractors unless they are properly tagged and furnished with circuiting information. 3.17 LIGHTING CIRCUIT CONTROL DEVICES AND RECEPTACLES: A. All devices shall be mounted within a steel box. B. All receptacles shall be mounted with box aligned in a vertical direction with ground slot at bottom of receptacle. In those areas where vertical space is not available such as under fin radiation, cabinets and above backsplash, mount horizontally with ground slot at right. C. Provide circuit identification of lighting junction boxes and wall switches in each Telecommunication room as called for 3.18 WALL PLATES: A. Submit samples as requested by Architect/Engineer. B. Provide special plates fabricated for devices shown ganged together at one location and provide special engraving for switch plates covering special utility switches as shown on drawings. C. Special finish plates will be required where so noted on drawings or included in specifications. Sample of finishes will be furnished to Architect/Engineer for approval when so requested. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 17 of 19 JUNE 29, 2012 D. Provide blank matching coverplates for outlets not used. E. Coverplates for telephone, dimmer controls, etc., shall match device plates in each area. 3.19 OUTLET, JUNCTION AND PULLBOXES: A. Flush recessed wherever possible and securely supported from building construction. B. Where outlet boxes are installed in exposed block walls, locate at corner of block. Locate conduit as required to meet block conditions. Coordinate with other Divisions. C. Identify junction boxes for particular service such as power, lighting, grounding, fire alarm, etc. Label with suitable tags or use stencil lettering. D. Locate where shown or required for outlet facilities and where shown or required for installing wire or cable. Make accessible after completion of construction; Electric Contractor shall be responsible for coordination with other divisions. Junction and pullboxes shall not be located in finished room unless specifically permitted. E. Mounting height of boxes shall be as scheduled. 3.20 PREVENTION OF CORROSION: A. Protect all metallic materials against corrosion. B. Aluminum shall not be used in contact earth nor embedded in concrete. Where connected to dissimilar metal, protect by approved fittings and treatment. C. Hot dip galvanize all ferrous metal materials such as bolts, braces, boxes, bodies, clamps, fittings, guards, nuts, pins, rods, shims, washers, and miscellaneous parts which are not made of corrosionBresistant steel. Use stainless steel fasteners in wet locations and out of doors. D. Galvanized in accordance with ASTM AB123 or AB153. 3.21 PAINTING: A. General Requirements: 1. Painting shall be provided as outlined hereafter. 2. Clean all surfaces of moisture, rust, plaster, dirt, dust, and foreign matter before painting. 3. Apply full even coats as required to provide acceptable finish. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 18 of 19 JUNE 29, 2012 4. Apply finish coat just before final acceptance. 5. Protect all other surfaces with drop cloths. masking tape, etc. 6. Protect equipment and internal parts with making tape. 7. Factory enamelBfinished equipment not to be painted, EXCEPT when rusted or otherwise damaged; then paint as directed or if specifically called for hereinafter. 8. Appearance to be approved; repaint if required. B. Paint all work of this division in the following areas: 1. Boiler Room, Mechanical Equipment Rooms, Electrical Equipment Rooms, Penthouses, Fan Rooms, all work of this contract exposed to the weather, and where specifically called for. a. Bare pipes, conduit, supports, all supports, mounting boards/panels, metal jackets, etc., also paint equipment not supplied with factory finished surface. 1) First Coat: Pratt and Lambert "Effecto" primer unless equipment supplied with factory prime coat. 2) Second Coat: Pratt and Lambert "Effecto" enamel. 3) Color as selected by engineer/architect. 4) Additional coats as required. 3.22 FIRESTOPPING, WATERPROOFING, CAULKING AND SEALING: A. Opening Through Fire/Smoke Walls and Floors: 1. Install work per NFPA. 2. Provide sleeves for ducts and pipe anchor duct sleeves with angle iron. 3. Comply with Division 078413 – Penetrating Firestopping 3.23 TESTS: A. General: 1. Perform all operations required for the complete testing of all systems, equipment and related work as shown on drawings or specified herein and in accordance with all applicable requirements of the specifications. 2. Before final acceptance, all specified tests shall be completed to the satisfaction of the Engineer or his representative, who shall be sole judge of the acceptability of such tests and who may direct the performance of any such additional tests as he deems necessary in order to determine the acceptability of the systems, equipment, material and workmanship. Any additional tests BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 26 01 01 PAGE 19 of 19 JUNE 29, 2012 required by the Engineer will be made at no additional costs to Owner. 3. All protective equipment shall be actuated in a manner that clearly demonstrates their work ability and operation. 4. Demonstrate the ability of each and every piece of equipment to meet the design and operating requirements indicated on the drawings. 5. The inspection and test by the Owner or Engineer of any articles or lots thereof , or failure to inspect and accept or reject any article or lots thereof, shall not relieve the Contractor from any responsibility regarding defects or other failure to meet the Specification requirements which may be discovered prior to final acceptance. Except as otherwise provided in the Specification, final acceptance shall be conclusive except as regards any latent defects, fraud, or such gross mistakes as amount to fraud. 6. Acceptance to the material and/or equipment and the waiving of test thereof, shall in no way relieve the Contractor of the responsibility for furnishing material and/or equipment meeting the requirements of these Specifications. END OF SECTION 26 01 01 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP GROUNDING STANDARD SPECIFICATIONS 26 05 26 – PAGE 1 of 5 JUNE 29, 2012 SECTION 260526 GROUNDING PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Contract Drawings and the General Provisions of the Contract, including the General Conditions of the Contract for Construction, Supplementary Conditions, Special Conditions and Division 1 Specification Sections apply to the work of this Section. B. The Work of Section 26 01 01 4 Electrical Basic Materials and Methods applies to the Work of this Section. 1.2 WORK INCLUDED: A. Provide a complete, operating, tested, functioning, documented grounding system including all work shown, specified, or required for proper system operation. B. All grounding and grounding circuitry shall equal or exceed the requirements of NEC, latest issue, Article 250. C. The raceway system which includes all metal conduit, wireways, pullboxes, junction boxes, bus ducts, built4up enclosures, enclosures, motor frames, etc., shall be made to form a continuous, conducting permanent ground circuit of the lowest practical impedance to enhance the safe conduction of ground fault currents and to prevent objectionable differences in voltage between metal non4load current carrying parts of the electrical system. D. In addition to the raceway system ground, an additional green wire ground shall be run in each raceway, sized for the largest circuit in the raceway. E. Telecommunications ground system consists of telecommunications ground bar (TGB) in all ITR’s and MTR’s. Refer to drawing for TGB type and location. Minimum #6 grounding riser between each ITR and MTR per riser diagram on drawings. Bonding in each ITR and MTR shall be from the TGB in each room to the following: network equipment racks and cabinets, cable runways, cable trays, metallic cable sheaths and raised floor system (if existing). 1.3 SUBMITTALS: A. Provide product data for each type of ground bar and associated ground lugs, at a minimum. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP GROUNDING STANDARD SPECIFICATIONS 26 05 26 – PAGE 2 of 5 JUNE 29, 2012 1.4 DEFINITIONS: A. Earth: interpreted as absolute ground, a theoretical location of zero electrical potential. B. Ground: interpreted as a made conducting connection to earth by employing such devices as a driven metal rod, a buried metal plate, a metallic water pipe, etc., or any multiple or combination of these devices, and the conductors which may interconnect any of the foregoing. C. System ground: interpreted as a low impedance made conducting ground plane or system, with a conducting connection to ground, established for the benefit of a particular electrical system or related systems. PART 2 PRODUCTS 2.1 CONDUCTORS: A. All exposed grounding conductors such as bars, straps, cables, flexible jumpers, braids, shunts, etc., shall be bare copper unless specifically noted or approved otherwise. B. Cable size shall be as required by NEC Code, Section 250, stranded, soft drawn or soft annealed, unless otherwise shown on plans or specified. C. Cable insulation type and color shall be as shown or as specified. D. Manufacturer to be same as specified in Section 260101 4 Basic Materials and Methods. 2.2 CONNECTORS, CLAMPS, TERMINALS: A. Mechanical connectors and clamps shall be silicon bronze. B. Solderless compression terminals shall be copper, long4barrel, two4bolt. C. Make: Anderson, Burndy, Penn4Union, T&B, approved for use intended. 2.3 SOLDER: A. Solder prohibited for connections, except for high voltage cable metallic tape shields. 2.4 MOLDED FUSION WELDS: A. Process shall be "Cadweld," "Metalweld," "Thermoweld." BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP GROUNDING STANDARD SPECIFICATIONS 26 05 26 – PAGE 3 of 5 JUNE 29, 2012 2.5 HARDWARE: A. All hardware shall be silicon bronze alloy. B. Make: "Durium," "Everdur." PART 3 EXECUTION 3.1 INSTALLATION, GENERAL: A. Bare copper bars, cables, fittings, etc., shall not be installed in cinder fill nor shall be covered with soil containing cinders or other corrosive material. B. Cables shall be installed with enough slack to prevent breaking stresses. C. All grounding conductors subject to mechanical damage shall be protected by rigid steel conduit or other suitable steel guards and in all cases where so protected shall be permanently and effectively grounded to said enclosure at each end of its length. D. Where grounding conductors pass through floor slabs, walls, etc., and are not encased in metal conduit, they shall be sleeved in fiber, or approved non4metallic conduit. E. All equipment ground bus, ground pads, frames, enclosures, etc., shall have surfaces at point of connection thoroughly cleaned and brightened just prior to actually making the connection. Touch4up damaged painted surfaces. F. Splices in wire or cable grounding conductors are prohibited. 3.2 INSTALLATION, RACEWAY SYSTEMS: A. All metal supports, cable trays, messenger cables, frames, brackets, races, etc., for any part of the raceway system, panels, switches, boxes, starters, controls, etc., which are not rigidly secured to and in contact with the raceway system, or which are subject to vibration and loosening, shall be bonded to the raceway system, the size of the bonding conductor in accordance with NEC Table 250494. B. Termination of rigid conduit at all boxes, cabinets, and enclosures shall be made up tightly with a double locknut arrangement and a bushing, bushings being of the insulated type where required by NEC. C. Conduit which runs to or from all boxes, cabinets, or enclosures having BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP GROUNDING STANDARD SPECIFICATIONS 26 05 26 – PAGE 4 of 5 JUNE 29, 2012 concentric or eccentric knockouts which partially perforate the metal around the conduit and hence impair the continuity of system ground circuits shall be provided with bonding jumpers sized in accordance with NEC Table 250495 connected between a grounding type bushing/locknut on the conduit and a ground bus or stud inside the box, cabinet, or enclosure and attached thereto. D. Conduit expansion joints and telescoping sections of metal raceways shall be provided with bonding jumpers sized in accordance with NEC Table 250495. E. Where flexible metallic conduit or liquid tight conduit is used, a bonding jumper shall be provided, sized in accordance with NEC Table 250495. F. All non4metallic runs of conduit or raceway shall be provided with a system ground conductor sized according to Table 250495. G. Where conduit enters or leaves any electrical enclosure with removable coverplates, provide conduit grounding bushings and bonding jumpers sized in accordance with NEC Table 250495 between the grounding bushings and the enclosure rigid frame or ground bus. H. The ground conductors contained in the interstices of interlocked armor cable shall be connected to ground at every splice and termination point. 3.3 INSTALLATION, ATTACHMENT TO STRUCTURAL STEEL: A. Location of attachment bonds of ground conductors shall be at points not subject to mechanical damage, but if possible where accessible for inspection. B. Attach preferably by molded fusion welding process. C. Where welding is prohibited, attach by bolting, 7/16 inch hole in steel, 3/8 inch silicon bronze bolt, bolt end peened, steel surface bright and flat prior to bolting, just prior to bolting contact surfaces lightly coated with Vaseline or "NO4OX4ID4A Special." 3.4 INSTALLATION, SECONDARY ELECTRICAL SYSTEMS: A. The neutral conductor of each and every low voltage, single or polyphase, system or distribution system, except special isolated double insulated systems, shall be solidly connected at one point only; at the main secondary switchgear; to system ground and shall be sized for current carrying capacity, not to be less than the following, which are listed in preferential order: a. As shown or specified. b. As required by NEC, latest issue, Table 250495. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP GROUNDING STANDARD SPECIFICATIONS 26 05 26 – PAGE 5 of 5 JUNE 29, 2012 c. Not less than 25 percent of the transformer full load current or main protective device rating, whichever is greater, based on NEMA standard bus size. B. Provide equipment grounding conductor, green colored insulation, with phase conductors, to primary side of all transformers rated 600 volts or less circuited to case and secondary neutral bushing, to motors, to motor control equipment, and to all convenience outlets, insulation shall be same type as phase conductors. C. Transformer secondary neutral bushings shall also to be circuited to nearest metallic water pipe, building steel, or ground rod. END OF SECTION 26 05 26 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP ELECTRICAL EQUIPMENT IDENTIFICATION STANDARD SPECIFICATIONS 26 05 53 – PAGE 1 of 4 JUNE 29, 2012 SECTION 260553 ELECTRICAL EQUIPMENT IDENTIFICATIO N PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. The Contract Drawings and the General Provisions of the Contract, including the General Conditions of the Contract for Construction, Supplementary Conditions, Special Conditions and Division 1 Specification Sections apply to the work of this Section. B. The Work of Section 26 01 01 8 Electrical Basic Materials and Methods applies to the Work of this Section. 1.2 WORK INCLUDED: A. Provide a complete, operating, tested, functioning, documented Electrical Equipment Identification System including all work shown, specified, or required for proper system operation. B. Under this Section provide equipment and circuit identification as follows: 1. Typewritten panel directories with duplicates on As8Built Drawings, for all new or existing altered panels. 2. Panelboard nameplates 3. Panelboard breaker identification tags 4. Telecom Ground Bar nameplates and identification tags, for all new or modified bars. 5. Telecom Grounding Riser Conductor nameplates and identification tags, for all new or modified risers. 6. Wiring color code 7. Wiring labeling 8. Junction box marking (Incl. Telecom Branch circuits and Lighting) 9. UPS and convenience power receptacles (Incl. Telecom Branch circuits) 10. Motor starter/disconnect nameplates 11. New Fire Alarm devices 12. New Fire Alarm junction box covers paint to Owner’s color code. 13. Panelboard voltage marking 1.3 RELATED WORK SPECIFIED ELSEWHERE: A. Factory produced panelboard nameplates included in Section 26 24 16. B. Color code for conductors provided in Section 26 01 01. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP ELECTRICAL EQUIPMENT IDENTIFICATION STANDARD SPECIFICATIONS 26 05 53 – PAGE 2 of 4 JUNE 29, 2012 1.4 SUBMITTALS: A. Provide product data for each new Telecom Ground Bar nameplates, per drawing A4. PART 2 PRODUCTS 2.1 IDENTIFICATION MATERIALS: A. Legend Plates: 1. Two ply, 1/16” thick flexible plastic legend plates, front etched with minimum 3/16” Gothic letters. Provide adhesive backing and a minimum of two 5/32” diameter screw holes. Plate size shall be minimum 1” x 3”. Multi8layer, non8conductive material, machine8 engraved with proper designation. 2. C & M Name Shop, Syracuse, or acceptable manufacturer. 3. Stick on computer printed labels shall not be accepted. B. Stencils: 1. Die cut, capital letters. 2. Letters 3/8” minimum height. C. Wire Markers: 1. Adhesive backed mylar or fabric material with printed markings. 2. Brady or equivalent. D. Voltage Markers 1. Voltage markers shall be bright orange with black letters. Brady Style B (181/8” by 481/2”) or acceptable manufacturer. Examples: Three Phase Single Phase Three Phase 208 volts 240 volts 480 volts 120 volts 120 volts 277 volts PART 3 EXECUTION 3.1 IDENTIFICATION, GENERAL: A. Equipment name and number as shown on Drawings to be used for equipment identification. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP ELECTRICAL EQUIPMENT IDENTIFICATION STANDARD SPECIFICATIONS 26 05 53 – PAGE 3 of 4 JUNE 29, 2012 B. Disconnect switches, starters, control, etc., serving utilized equipment shall be labeled on front cover. C. All duplex receptacles, single UPS receptacles, light switches/circuits, Telecom Ground Bars, Telelcom grounding conductors and lugs, fire initiation devices, etc, serving any equipment in Telecommunication rooms, shall be labeled with machine printed wrap around labels, with panel and C/B information. . D. All Telecom Ground Bars and Telelcom grounding conductors in Telecommunication rooms, shall be labeled with legend plated, as described in this section. E. Step8down transformers shall be labeled with primary/secondary voltages. F. Utilized equipment which does not have service voltage clearly indicated shall also be labeled by the Contractor, as directed by the Engineer. G. Starters or control panels with interlock shall be provided with a warning sign to indicate separate control voltage and may be energized. Warning sign shall be mounted inside enclosure. 3.2 IDENTIFICATION MARKERS: A. Securely fastened to equipment to be identified with adhesive material and plated screws. B. Locate on front of equipment to be identified in neat manner, plumb and true. C. All power supply equipment; i.e., branch circuit breakers, equipment disconnect switches, motor starters, etc. to be labeled to identify function and/or load served. 3.3 STENCILED LABELS: A. To be used only on equipment in unfinished areas. B. Obtain Engineer's approval. C. Locate on front of equipment to be identified in neat manner, plumb and true. 3.4 WIRE MARKERS: A. Install approximately 2” from wire ends. B. All wiring to be identified via labeling at all ends, in junction and pull boxes, in panelboards, at equipment terminations, at terminal boards BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP ELECTRICAL EQUIPMENT IDENTIFICATION STANDARD SPECIFICATIONS 26 05 53 – PAGE 4 of 4 JUNE 29, 2012 and/or cabinets. Wiring to be identified for continuity. 3.5 DIRECTORIES: A. Typewritten only; handwritten not acceptable. B. Install in a manner to be legible but protected from physical damage under conditions of normal use. C. Room names to be referenced on directory along with load supplied. 3.6 MATERIALS TO BE LABELED: A. Directories: Update existing panelboards to include new load served. END OF SECTION 26 05 53 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP MOTOR STARTERS AND DISCONNECTS STANDARD SPECIFICATIONS 26 29 10 – PAGE 1 of 3 JUNE 29, 2012 SECTION 262910 MOTOR STARTERS & DISCONNECTS PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. The Contract Drawings and the General Provisions of the Contract, including the General Conditions of the Contract for Construction, Supplementary Conditions, Special Conditions and Division 1 Specification Sections apply to the work of this Section. B. The Work of Section 26 01 01 5 Electrical Basic Materials and Methods applies to the Work of this Section. 1.2 WORK INCLUDED: A. Provide motor starters and disconnects, including all work shown, specified, or required for proper system operation. 1.3 REFERENCE STANDARDS: A. The combination starters and protection devices in this specification shall be designed and manufactured according to latest revision of the following standards (unless otherwise noted). 1. ANSI/NFPA 70 5 National Electrical Code. 5 Latest issue 2. CSA C22.2 No. 14 5 Industrial Control Equipment. 5 Latest issue 3. NEMA ICS 2 5 Industrial Control and Systems: Controllers, Contactors and Overload Relays, Rated Not More than 2000 Volts AC or 750 Volts DC. 5 Latest issue 4. UL 508 5 Industrial Control Equipment. 5 Latest issue 1.4 SUBMITTALS A. Provide submittals for the following: 1. Disconnect Switches 2. Starters PART 2 PRODUCTS 2.1 MANUFACTURERS: A. All products in this section shall be by General Electric Company, Square D or Cutler5Hammer. These Manufacturers are University Standard, no other Manufacturers shall be accepted. 2.2 CLASSIFICATION/ASSEMBLY: BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP MOTOR STARTERS AND DISCONNECTS STANDARD SPECIFICATIONS 26 29 10 – PAGE 2 of 3 JUNE 29, 2012 A. All products to be heavy duty grade classification, NEMA type as scheduled on drawings. General duty products not accepted. B. All products shall be factory assembled and wired and shall be UL approved. Assemblies fabricated by Contractor shall not be accepted. C. Units shall be horsepower rated for load served, current rating and poles as shown on plans. 2.3 DISCONNECT SWITCHES (NON5FUSIBLE): A. Visible blade with dual color, red/black position indicator. Unit shall be padlockable in "off" position. B. Unit shall be the heavy5duty version. C. Where shown provide auxiliary interlock kits. D. Rating: 600 Volts for all loads served. E. Make: Square D Class 3110 or acceptable manufacturer in G.E. or Cutler5Hammer. 2.4 DISCONNECT SWITCHES (FUSIBLE): A. Visible blade with dual color, red/black position indicator. Unit shall be padlockable in "off" position. B. Unit shall be the heavy5duty version. C. Provide motor overload elements and fuse clips for Class R fuses. D. Where shown provide auxiliary interlock. E. Rating: 240 Volts for 208 and 240 Volt loads. 600 Volts for loads above 240 volts. F. Make: Square D Class 3110 or acceptable manufacturer in G.E. or Cutler5Hammer. 2.5 MANUAL MOTOR STARTERS: A. Motor control switch and Motor overload element in single enclosure. B. Make Square D class 2510 or acceptable manufacturer in GE or Cutler5 Hammer. 2.6 COMBINATION MAGNETIC MOTOR STARTER/FUSIBLE DISCONNECT SWITCH: BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP MOTOR STARTERS AND DISCONNECTS STANDARD SPECIFICATIONS 26 29 10 – PAGE 3 of 3 JUNE 29, 2012 A. Provide motor overload elements and fuse clips for Class R fuses. B. Visible blade with dual color, red/black position indicator. Unit shall be padlockable in "off" position. C. Parts subject to wear or arching shall be removable and replaceable. D. Where shown provide auxiliary interlock kits. E. Provide 24 or 120 volt control transformer as shown and 24 or 120 volt contactor coil, provide fuses for transformer. F. Provide cover mounted HOA switch. G. Make: Square D Class 8538 or acceptable manufacturer in GE or Cutler5 Hammer. 2.7 FUSES: A. Dual Element, time delay. B. Type and size as required. C. Make: Buss Fustron, Shawmut Gould, or Brush Reliance. PART 3 EXECUTION 3.1 INSTALLATION: A. Mount Manual Motor Starters, Magnetic Motor Starters and Disconnects on substantial mount frames provided by the Electrical Contractor, with clearances according to the NEC. B. Circuit according to the NEC. END SECTION 26 29 10 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP LIGHTING STANDARD SPECIFICATIONS 26 51 00 – PAGE 1 of 5 JUNE 29, 2012 SECTION 265100 LIGHTING PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. The Contract Drawings and the General Provisions of the Contract, including the General Conditions of the Contract for Construction, Supplementary Conditions, Special Conditions and Division 1 Specification Sections apply to the work of this Section. B. The Work of Section 26 01 01 6 Electrical Basic Materials and Methods applies to the Work of this Section. 1.2 WORK INCLUDED: A. Provide a complete, operating, tested, functioning, documented lighting system including all Work shown, specified, or required for proper system operation. B. Provide lighting fixtures, lenses, globes, hangers, supports, lamps and appurtenances to provide a complete lighting system. C. Provide emergency light battery units, and accessories where shown. D. Relocate fixtures where shown. E. Refer to Electrical New Work Drawings and E4 Drawing Schedules, typical. 1.3 SUBMITTALS: A. Provide product data for each luminaire assembly to be provided and all light switched, as called or. PART 2 PRODUCTS: 2.1 GENERAL: A. All fixtures of the same type shall be by the same manufacturer. B. All lamps of the same type shall be by the same manufacturer. Lamps shall be appropriate for the actual ballast furnished and shall be tested and certified for operation by the ballast manufacturer. 2.2 FIXTURES: A. Schedule (See E4 Drawings). BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP LIGHTING STANDARD SPECIFICATIONS 26 51 00 – PAGE 2 of 5 JUNE 29, 2012 2.3 FLUORESCENT LAMPS: A. All fluorescent lamps shall be energy saving type and color temperature as scheduled. B. Lamps shall be low mercury type. 2.4 BALLASTS: A. All ballasts shall be of the PCB free type. B. All ballasts shall be of the energy saving type, as scheduled, 56 watts input typ. 26lamp T8. PART 3 EXECUTION 3.1 FIXTURES: A. Securely support all fixtures in accordance with manufacturer's installation instructions and U.L. or ETL listing information. B. Location: 1. Evenly proportioned in room, except adjusted to conform with ceiling pattern as described below and except where otherwise shown or dimensioned. 2. Edges of fixtures parallel with walls. C. Plaster frames: 1. Provide for all recessed fixtures in wet type ceilings. 2. Install in cooperation with other trades. D. Mounting: 1. All fixtures must hang true to vertical, free from finger marks, flaws, scratches, dents or other imperfections. 2. Take care when hanging fixtures not to deface in any way, ceilings or walls. 3. Install continuous rows of fixtures in straight line; all fixtures at same level. Fixtures must not be rotated about longitudinal axis with respect to one another. 4. Mount surface fixtures tight to surface without distorting it. 5. Provide proper mounting equipment and trim for recessed fixtures to adapt them to the ceiling or wall construction and to prevent light leaks around trim. 6. Provide special means for supporting fixtures as hereinafter BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP LIGHTING STANDARD SPECIFICATIONS 26 51 00 – PAGE 3 of 5 JUNE 29, 2012 specified, as shown on plans, or as required. 7. All stem mounted fixtures shall be hung level from self6aligning hangers in canopies; all stems shall be constructed of formed and stamped sheet metal, no cast or "pot metal" parts shall be accepted. 8. Securely support all ceiling fixtures, hangers, and outlet boxes from structural members, not from ceiling members. In addition the fixtures shall be securely fastened to framing members of the ceiling in order to meet NEC, Article 410616B. Lock clip, wirelashing or leveling supports shall be acceptable means. 9. Plastic inserts not permitted. 10. Outlet boxes shall not be supported by conduit. 11. Supports for each fixture shall be capable of supporting 4 times fixture weight. Use 1/4 inch threaded rod, fender washer, and double nuts. 12. Exterior fixtures shall be installed with non6ferrous metal screws finished to match the fixture. 13. Fixtures shall be supported from building structure and using supports as follows (minimum requirements): a. Ceiling surface mounted: 1) 1’ x 4’ 6 two supports. 2) 1’ x 8’ 6 three supports. 3) 2 ‘x 4’ 6 two supports. 4) 4’ x 4’ 6 four supports. 14. Provide special extra wide toggle bolt support, 10” wide toggle, Paine Company #400, mounted above existing plaster ceilings where approved by Engineer and noted on Plans. E. Mechanical coordination: 1. Coordinate location of all hangers in rooms without ceilings with ductwork, plumbing piping, sprinkler piping, etc. 2. Make all necessary offsets and extensions so that stems and fixtures avoid beams, pipes, ducts, etc. 3. Where fixtures are located below heating, ventilation and air conditioning units, or ductwork and piping, provide trapeze hangers around obstruction and suspend fixture from trapeze hanger. Do not suspend from duct. F. Architectural coordination: 1. Locate all hangers at intersections of joints or at centers of blocks in rooms with acoustical tile or other patterned type of ceiling materials. 2. Space continuous row fixtures to conform to corresponding joint intersections. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP LIGHTING STANDARD SPECIFICATIONS 26 51 00 – PAGE 4 of 5 JUNE 29, 2012 3. Coordinate all ceiling layouts and obtain Engineer's approval before proceeding. 4. Heights of fixtures not scheduled will be furnished on application to Engineer. 5. Contractor is specifically required to verify ceiling construction and report in writing any discrepancies between the ceiling type and the fixture type before releasing fixtures for manufacture. G. Care of fixtures: 1. Remove, and replace with new, all broken glassware, plastic or fixtures damaged before final acceptance at no additional expense to Owner. 2. No allowance made for breakage or theft before final acceptance. 3. Immediately prior to occupancy, damp6clean all diffusers, glassware, fixture trims, reflectors, lamps, and replace burned6out lamps. H. Wiring: 1. Fixture shall not be used as a raceway except as allowed in NEC, Article 410631. 2. Wiring to fixture shall be 90° Centigrade minimum. 3.2 LAMPS: A. All lamps for new fixtures shall be installed new. Provide spare lamps as required to allow replacement of flickering or bad lamps. Provide labor and material to replace any failed lamp during the one (1) year warrantee period. In the event that more than 10% of the lamps in a particular room or lot fail within twelve (12) months of Project completion or earlier, the Contractor shall replace all lamps which were provided for that room or lot. Contractor shall provide all labor and materials for this work at no cost to the Owner, and shall compensate the Owner for his personnel who provide access for the Contractor. B. Clean all fixtures and lamps prior to requesting punch list. 3.3 BALLASTS: A. Install in accordance with manufacturer's instruction. Provide labor and material to replace any failed ballast during one (1) year warranty period. In the event that more than 10% of the ballasts in any particular room, lot or type of fixture fail within twelve (12) months of Project completion or earlier, the Contractor shall replace all ballasts which were provided for that room or lot or type of fixture. The Contractor shall provide all labor and materials for this work at no cost to the Owner, and shall compensate the Owner for his personnel who provide access for the Contractor. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP LIGHTING STANDARD SPECIFICATIONS 26 51 00 – PAGE 5 of 5 JUNE 29, 2012 END OF SECTION 26 51 00 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 1 of 8 JUN 29, 2012 SECTION 266000 FIRE ALARM IMPROVEMENTS PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. The Contract Drawings and the General Provisions of the Contract, including the General Conditions of the Contract for Construction, Supplementary Conditions, Special Conditions and Division 1 Specification Sections apply to the work of this Division. B. The Work of the Sections 26 01 00 6 Electrical Basic Materials and Methods apply to the Work of this Section. 1.2 FIRE ALARM SYSTEM INSTALLER REQUIREMENTS: A. The installation of major fire alarm system renovations and new fire alarm and detection systems shall be performed by a qualified individual certified as either a National Institute for Certification in Engineering Technologies (NICET) Fire Alarm Systems Level III (minimum), or as a Licensed Professional Engineer. 1.3 WORK INCLUDED: The work of this Section shall include providing all materials, labor, services, permits and related work to furnish a complete, operating, tested, functioning, documented Fire Alarm improvements and modifications and additions to existing fire alarm System for Cornell University including all work shown, specified or required for proper system operation including but not limited to the following: A. Field verifications of existing conditions and associated demolition and removal of existing circuits, devices, and fixtures, where shown, removal of all debris from site and proper disposal of same. B. Confirmation that the existing system can support new device(s) Provide new hardware and appropriate and compatible system detection devices throughout the building as shown on the AMEP electrical drawings. C. Provide and install new conduit pathways and boxes for new fire alarm circuiting as shown on drawings. Extend existing fire alarm initiating circuit to new smoke detector. D. Provide equipment and conductor identification. All new fire alarm equipment shall match existing fire alarm manufacturer within the building. E. Provide testing of equipment and conductors. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 2 of 8 JUN 29, 2012 F. Provide openings in existing and new construction as required for the work of this division. G. Provide maintenance of system in good condition until final acceptance. H. Provide Submittals, Shop Drawings and Coordination Drawings. I. Provide As6Built (Record Drawings) for the following: 1. Fire Alarm System Equipment and Devices J. Provide Reprogramming (with designators approved by Owner), testing, and modification to existing fire alarm panel(s). K. Provide startup, testing and troubleshooting services as required. L. Provide one year warranty from date of final acceptance. M. Provide owner training. N. Provide O&M document submission and “As6Built” Drawings. 1.4 SUBMITTALS A. To ensure compliance with the intent of this standard, all new fire alarm and detection system final designs and associated contract submittals shall be reviewed by CU Facilities Engineering (FE) and Environmental Health & Safety (EH&S). B. One (1) copy of each new project fire alarm system submittal shall be sent to both the CU FE Electrical Section and EH&S for review and comment prior to releasing final approved submittals to the contractor. Submittals shall contain the following information: 1. Product information for all installed components; 2. System riser diagram with typical equipment and device connection and labeling; NOTE that a detailed system/device connection diagram is NOT required until the completion of the project (as a complete “As6Built”). 3. Wire color coding table and/or schedule; 4. System battery stand6by calculations; 5. Special system requirements; 6. System labeling materials and methods as described in this section. C. At completion of the project, Contractor shall provide a complete set of fire alarm “As6Built” drawings that includes the following information prior to the closeout of the project: 1. New Initiating device locations; BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 3 of 8 JUN 29, 2012 2. Special systems interface locations; 3. Complete fire alarm riser diagram that depicts wiring between FACP and all new fire alarm system components. Such detail shall include all major equipment and their locations (approved room number designation), zone/loop wiring connections to initiating devices, SNAC wiring to notification appliances, and interconnections to other special systems as designed per this standard. 4. Circuit breaker locations for all fire alarm panels and accessory panels that receive building power. Locations shall include room number in which the power panel is located, as well as the breaker number that serves the equipment. D. The Owner or his designated representative shall approve all equipment submittals. E. Administrative Requirements a) Provide product data for each type of smoke/heat detector planned for use, at a minimum. F. General Requirements: 1. Manufacturer's original catalog data and descriptive information shall be supplied for all major components of the equipment to be supplied. 2. Suppliers' qualifications shall be supplied indicating years in business, service policies, warranty definitions, and a list of similar installations. 3. Contractor qualifications shall be supplied indicating years in business and prior experience with installations that include the type of equipment that is to be supplied. 4. All pertinent information shall be supplied regarding the reliability and operation of the equipment to be supplied. 5. Delivery dates of the equipment to be supplied shall be furnished. 6. Installation and final test/acceptance dates of the equipment shall be supplied. 7. Sufficient information shall be supplied so that the exact function of each installed device is known. 8. Provide battery stand6by calculations showing total stand6by power needed to meet the system requirements as specified. G. Other than Specified Equipment: Equipment other than specified shall be considered for approval provided the following is submitted in writing by the Electrical Contractor to the Engineer ten (10) days before the bid date: BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 4 of 8 JUN 29, 2012 1. Complete lists, descriptions and drawings of materials to be used. 2. A complete list of current drain requirements during normal supervisory conditions, trouble conditions and alarm conditions. 3. Battery stand6by calculations showing total stand6by power needed to meet the system requirements as specified. H. Substituted Equipment: If equipment other than that specified is supplied, it shall be the Contractor's obligation to submit the appropriate documentation and all the Engineer sufficient time to consider the equality of the substituted items. I. Satisfying the Entire Intent of these Specifications: 1. It is the Contractor's responsibility to meet the entire intent of these Specifications. Deviations from the specified items shall be at the risk of the Contractor 2. All costs for removal, relocation, or replacement of a substituted item shall be at the risk of the Contractor. 1.5 AGENCY APPROVALS: A. All equipment shall be listed by Underwriters Laboratories, Inc. or approved by Factory Mutual or as accepted by the authority having jurisdiction. B. The modified fire alarm system in its entirety shall be in compliance with all applicable fire and electrical codes and comply with the requirements of the local authority having jurisdiction over said systems. C. Accessory components as required shall be catalogued by the manufacturer and U.L. listed to operate with the manufacture’s control pane. 1.6 SPECIFIC U.L. PROVISIONS: A. The system shall comply with the applicable provisions of the following U.L. Standards and Classifications: 1. #864, Control Units for Fire Protective Signaling Systems. 2. UOJZ, Control Units, System. 3. UOXX, Control Unit Accessories, System. 1.7 SPECIFIC NFPA STANDARDS: A. The system shall comply with the applicable provision of the following current National Fire Protection Association (NFPA) standards: BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 5 of 8 JUN 29, 2012 1. NFPA 71 2. NFPA 72 National Fire Alarm Code 3. NFPA 90 A 4. NFPA 101 Life Safety Code 1.8 CODES AND STANDARDS: A. The Fire Alarm and Detection System shall comply with all local and state codes with no exception. B. The Fire Alarm Contractor shall be a licensed New York State Fire Alarm and Detection System Installer. 1.9 CONTRACTOR REQUIREMENTS: A. The Contractor providing modifications to the fire alarm and detection system shall be licensed per Article 6 D of the New York State General Business Law. PART 2 PRODUCTS 2.1 EQUIPMENT MATERIAL AND GENERAL REQUIREMENTS: A. All equipment furnished for this project shall be new and unused. All components and systems shall be designed for uninterrupted duty. All equipment, materials, accessories, devices and other facilities covered by this specification or noted on contract drawings and installation specifications shall be the best suited for the intended use and shall be provided by a single manufacturer. If any of the equipment provided under this Specification is provided by different manufactures, then that equipment shall be recognized as compatible by both manufacturers, and "Listed" as such by Underwriters’ Laboratories. B. System installation and operations shall be verified by the manufacturer’s representative and a verification certificate presented upon completion. The manufacturer’s representative shall be responsible for an on6site demonstration of the operation of the system and initial staff training as required by the Consulting Engineer. C. The system shall be capable of detecting the electrical location of each intelligent device. 2.2 SMOKE DETECTOR6PHOTOELECTRIC: A. Smoke Detectors – Spot Type BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 6 of 8 JUN 29, 2012 1. Smoke detectors shall be of the low profile, solid state, photoelectric or ionization type and shall be compatible for use in addressable, zoned, and combination addressable and zoned systems. 2. Smoke detectors shall be compatible for use in Style D (Class A) and Style B (Class B) circuits. (Note: Special power supplies or compensating devices shall not be required for smoke detectors to properly operate in circuits containing other Style D and Style B initiating devices. Also, Style B (Class B) smoke detectors shall not be used in initiating circuits unless provided with a separate 24 VDC control power supply.) 2.3 MOUNTING BASE6STANDARD DETECTOR: A. Standard detector mounting base suitable for mounting on 4" octagon and 4" square box or wiremold surface ceiling box. Base shall contain no electronics, support all detector types and have following minimum requirements: 1. Removal of respective detector shall not affect communications with other detectors. 2. Terminal connections shall be made on room side of the base. Bases which must be removed to gain access to the terminals shall not be accepted. B. Design Make (typical): Simplex Grinnell TrueAlert # 409869xxx Series, 2 or 46wire to match existing system, or as directed (field verify). C. Design Make (typical): EST Model SIGA6SB, or as directed to match existing (field verify). 2.4 SYSTEM IDENTIFICATION / LABELING A. Initiating, notification, signaling, and other fire alarm system wiring, circuits, and conductors shall be color coded and identified by number at termination points (i.e., control panels, remote annunciators, etc.) and splice points (i.e., junction boxes, splice boxes, etc.). Wiring shall be consistent throughout the system with no color changes on individual loops from the FACP. B. Junction and splice boxes containing fire alarm system wiring, circuits, and conductors shall have red covers and marked “FIRE ALARM” in 3/4" (three6quarter inch) white letters. C. Fire alarm equipment supplied with 120 VAC power shall be labeled with the panel source information, including panel name, room number and source breaker number. D. End6of6line resistors in two6wire systems shall be located at the fire alarm control panel, if feasible; otherwise, end6of6line resistors shall be installed in designated junction boxes with red covers and marked in accordance BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 7 of 8 JUN 29, 2012 with the specifications of this section. PART 3 EXECUTION 3.1 GENERAL: A. Any drilling/work that may create a nuisance fire alarm shall be scheduled at least 24 hours in advance with Cornell customer service for a fire protection system shutdown. Shutdown will be performed by Cornell EH&S staff. Contractor shall not disable any fire protection equipment without EH&S approval/assistance. B. Prior to construction within any room containing an existing smoke detector, coordinate with system vendor to temporarily replace the smoke detector with a heat detector, and test/re6program the system as required. Schedule the vendor in advance to avoid project delays. At completion of room construction, coordinate with vendor to replace heat detector with smoke detector, and test/re6program the system as required, in the presence of Cornell EH&S / IFD. C. Conform to Division 26 Specifications for installation and execution of work. 3.2 WIRING: A. For fire alarm use, wire and cable shall be U.L. listed and a minimum of 18 AWG as required by local codes and authority having jurisdiction. Provide twisted/shielded wire for communication circuits. All fire alarm and detection circuits shall be in conduit. B. Raceways containing conductors identified as "Fire Protective Alarm System". Conductors shall not contain any other conductors and no AC current carrying conductors shall be allowed in the same raceway with the D.C. Fire alarm detection and signaling conductors. 3.3 INSTALLER'S RESPONSIBILITIES: A. The installer shall field verify existing conditions/systems and coordinate the installation of the fire alarm equipment with the manufacturer or his authorized distributor. B. All conductors and wiring shall be installed according to the manufacturer's recommendations. C. It shall be the installer's responsibility to coordinate with the supplier, regarding the correct wiring procedures before installing any conduits or conductors. 3.4 INSTALLATION OF SYSTEM COMPONENTS: A. System components shall be installed in accordance with the latest BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 8 of 8 JUN 29, 2012 revisions of the appropriate NFPA pamphlets, the requirements contained herein, National Electrical Code, local and state regulations, the requirements of the fire department, and other applicable authorities have jurisdiction. B. Low energy U.L. listed fire protective signaling circuit cable with 105° C insulation may be used when allowed by the local authority having jurisdiction, however, all conductors shall be in conduit. C. Installer shall verify that smoke detectors are mounted not less than three (3) feet from air supply diffusers. 3.5 GUARANTEE AND FINAL TEST: A. General: 1. The Contractor shall guarantee all equipment and wiring free from inherent mechanical and electrical defects for one year (365 days) from the date of final acceptance. B. Final Test: Before the installation shall be considered completed and acceptable by the Owner, a test on the system shall be performed as follows: 1. The Contractor's job foreman, in the presence of a representative of the manufacturer, a representative from Cornell EH&S, and the fire department shall operate each new building fire alarm device to ensure proper operation of the device, and correct annunciation at the control panel, the remote annunciator and building alarms. 2. One half of all tests shall be performed on battery stand6by power. 3. When the testing has been completed to the satisfaction of both the Contractor's job foreman and the representatives of the manufacturer and Owner, a notarized letter co6signed by each attesting to the satisfactory completion of said testing shall be forwarded to the Engineer and the fire department. 4. The Contractor shall leave the fire alarm system in proper working order, and without additional expense to the Owner, shall replace any defective materials or equipment provided by him under this Contract, within one year (365 days) from the date of final acceptance by the Owner. 5. Prior to final test the fire department must be notified in accordance with local requirements. END OF SECTION 26 60 00