Loading...
HomeMy WebLinkAbout23 01 00 - Mechanical Basic Materials and Methods BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP MECHANICAL BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 23 01 00 – PAGE 1 OF 9 JUNE 29, 2012 SECTION 230100 MECHANICAL BASIC MATERIALS & METH ODS PART 1 GENERAL 1.1 DIVISION 23 DESCRIPTION: The Technical Specifications of this Contract are arranged for the convenience of the Owner and Contractor into divisions of work. The Work of Division 23, Mechanical, is further described in Specification Sections of the 23 00 00 Series and Contractor Contract Drawings of the "M" and “AMEP” series. The organization of this Work into Divisions shall not relieve the Prime Contractor from providing all of the work shown on the complete set of drawings or specified in the complete set of Specifications, whether or not the individual subcontractors correctly identify their respective responsibilities. 1.2 OTHER DIVISION SPECIFICATIONS APPLICABLE TO THIS WORK: To the extent that the Work of this Division or Contract includes the work of other trades, the Contractor for this division shall adhere to the requirements of other Specification Sections. All General Construction work shall be performed in accordance with the provisions of the appropriate Division 02 through Division 26 Sections. 1.3 WORK INCLUDED: A. Provide Mechanical Basic Materials and Methods B. Provide Access Doors or Access Panels C. Provide Fire Wall Sealant D. Provide Hangers, Riser Clamps, Attachments and Rods E. Provide Identification Systems F. Provide Sleeves G. Provide Miscellaneous Painting H. Provide Equipment Installation I. Provide Firestop to Restore Penetrations and Smoke/Fire Barrier Assemblies J. Provide Noise and Vibration Free Installation K. Provide Adjustment and Initial Lubrication L. Provide Maintenance of systems in good condition until final acceptance. M. Provide Permits and Inspections. N. Provide Testing, Adjusting and Balancing (pre and post construction) BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP MECHANICAL BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 23 01 00 – PAGE 2 OF 9 JUNE 29, 2012 1.4 PERMITS AND INSPECTIONS: Division 23 shall be responsible to apply for, obtain and meet the requirements of all permits and inspections required by authorities having jurisdiction for the work of Division 23. Division 23 shall pay all fees associated with these permits and inspections. 1.5 LAWS AND REGULATIONS: Division 23 shall conform with all Federal, State, County, and Municipal Laws, Ordinances and Regulations. Comply with the Occupational Safety and Health Act (OSHA). 1.6 CONTRACTOR EXAMINATION OF THE SITE: It shall be the responsibility of each prospective Contractor to visit the project site and to examine existing conditions. The Contractor shall be responsible to include under this Division all effort, materials, supplies, temporary installations and other work to relocate, remove or modify existing work as required to complete the work of this Division. 1.7 PLANS AND SPECIFICATIONS: A. It shall be the responsibility of the Contractor to examine the complete project documents including Plans and Specifications thoroughly prior to bid and to notify the Architect/Engineer of any uncertainties or apparent omission, conflicts, or discrepancies between the Plans and Specifications. In any case of a conflict between the Plans and Specifications or between two Specification sections it shall be assumed that the larger capacity or quantity, or higher quality, shall govern until a determination can be made by the Architect/Engineer. B. Plans and Specifications are of abbreviated form. Omitted words or phrases shall be inferred. C. Plans and Specifications are complementary. Provide all work which is either shown or specified or both. D. Where provided on the drawings, typical details shall be assumed to be applied to each installation of the equipment whether or not specifically identified at each point in the Plans. E. The Division 23 Contractor shall assume that all work on the Mechanical Drawings is included in his work unless specifically noted otherwise. 1.8 DEFINITIONS: Where used in the Plans and Specifications the following words and BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP MECHANICAL BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 23 01 00 – PAGE 3 OF 9 JUNE 29, 2012 corresponding definitions shall apply: MSS: Manufacturer’s Standardization Society of the Valve and Fitting Industry Inc. Provide Contractor shall supply, install, startu p, and maintain until final acceptance. Furnish Same definition as Provide. New Work occurring as part of this Project, usuall y employed on a drawing to distinguish from existing work. All work shown on the drawings shall be assumed to be new unless specifically identified as existing. Exist Existing work. Shown Shown on the Plans. Specified Specified on the Technical Specificati ons. HV The Contractor performing the Division 23 He ating and Ventilation work. In the Plans and Specifications, the works "By Div 23" and "By HV" or "By H&V" shall be considered synonymous. Elect or EC the Contractor performing the Divisio n 23 work. In the Plans and Specifications, the work "By Div 26", "By EC" and "By Elect" shall be considered synonymous. Plumb or Plumbing or Plg The Contractor perform ing the Division 23 Plumbing work. In the Plans and Specifications, the words "By Plumb" or "By Plumbing" or "By Plg" shall be considered synonymous. FP The Contractor performing the Division 23 Fi re Protection. In the Plans and Specifications, the words "By Div 23 FP" or "By FP" shall be considered synonymous. 1.9 RELATED WORK NOT INCLUDED: A. Cost of water and electricity for construction by Cornell University. B. Electrical connections by Electrical Contractor specifically shown in their Contract. The Division 26 Contractor is responsible only for the electrical connections included under Division 26 and the electrical drawings. Division 23 Contractor shall provide all other electrical work necessary for satisfactory operation of equipment furnished under Division 23. 1.10 REGULATIONS GOVERNING ASBESTOS: A. The Owner has reported that he has investigated the project site for asbestos containing materials and has scheduled remediation activities if BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP MECHANICAL BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 23 01 00 – PAGE 4 OF 9 JUNE 29, 2012 required. This does not guarantee that the site is 100% asbestos free. B. If any material which appears to possibly contain asbestos is encountered, the Contractor shall: C. Conform to the procedures identified in Section 01 35 23 – Owner Safety Requirements’ (especially, but not limited too, Paragraph 1.3). D. Refer to Section 011000 – Summary of Work, item 1.5 Work By Owner. PART 2 PRODUCTS 2.1 ACCESS DOORS: A. Size 24” x 24” unless otherwise noted. It is to be noted that various type frame are required for specific wall and ceiling finish. Any door having an area exceeding 324 square inches shall have two (2) camlocks. Milcor or approved equal. B. Rating 1. Access doors for shafts shall be 3 hour fire rated. 2. Access doors for dropped ceilings do not require rating. 3. Access doors in corridor wall shall be 11/2 hou r rated. 2.2 FIRE WALL SEALANT: A. Refer to Section 078413 – Penetration Firestop B. Provide product data submittal. 2.3 HANGERS, RISER CLAMPS, ATTACHMENTS AND RODS: A. Hangers 1. Regular: Adjustable clevis type, black steel construction, MSS Type 1. 2. With Insulation Shield: Adjustable clevis type, black steel construction, galvanized steel saddle welded to lower strap, MSS Type 40, of length recommended by manufacturer to prevent crushing insulation. B. Riser clamps 1. Riser clamps shall be of steel construction, twopiece type, MSS Type 42. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP MECHANICAL BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 23 01 00 – PAGE 5 OF 9 JUNE 29, 2012 C. Attachments 1. CClamps: Clamps shall be of steel construction with locking nut, MSS Type 23. 2. Beam Clamps: Beam clamp shall be of malleable iron construction, MSS Type 21. D. Hanger Rod 1. Hanger rod shall be steel, full threaded type. 2. Rods: Pipe Sizes Rod Diameter Up to 2” 3/8” 2½ to 3” ½” 4” and 5” 5/8” E. Floor Supports 1. Floor support hanger devices shall not be used. F. Wall Hangers 1. Angle iron or unistrut type wall brackets shall not be used. 2.4 IDENTIFICATION SYSTEMS: A. Equipment Labels: 1. Small: Labels shall be adhesive backed plastic tape with embossed letters in contrasting color. Tape shall be 3/8” wide. 2. Large: Labels shall be adhesive backed plastic tape with embossed letters in contrasting color. Tape shall be ¾” wide. 3. Make: Seton Name Plate Company. 2.5 SLEEVES: A. Sheet Metal Sleeves: 10 gauge, galvanized sheet metal, round tube closed with welded longitudinal joint. . B. Steel Sleeves: Schedule 40 galvanized, welded steel pipe, ASTM A53, Grade A. PART 3 EXECUTION BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP MECHANICAL BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 23 01 00 – PAGE 6 OF 9 JUNE 29, 2012 3.1 LAYING OUT WORK: A. The Plans are in part diagrammatic. Contractor shall verify roughin dimensions with fixture Shop Drawings and with the Architectural Plans. Conform to dimensions shown on the Plans in preference to scaling from the mechanical drawings. Provide all fittings and appurtenances required for proper system operation. B. Contractor shall allow for thickness of finishes when roughing in his work. He shall not rough without obtaining accepted Shop Drawings for the actual equipment to be installed. C. Due to the scale of drawings, it is not possible to indicate all offsets, fittings, changes in elevation, etc. which may be required. Make all such changes in piping, ductwork, conduit system, location of equipment, etc., to accommodate work to obstacles encountered, at no increase in compensation. If requested, submit at least five (5) copies of drawings detailing all major deviations or changes. All changes must be approved before installing. D. Plans show general arrangement of piping and connections. Install work substantially as indicated. Verify exact locations and elevations on job. Before installing work, consult other Plans, details and Contractors to determine headroom and work interferences. Examine Architectural Plans for exact location of equipment, fixtures and outlets. Where not definitely located, obtain information from Architect. E. Thoroughly coordinate work with that of other Contractors. Raise piping and drip where necessary. Vent all air pockets in water piping, even though not so indicated. Determine exact route and/or location of each pipe before fabrication and installation. Furnish in writing to Architect, any information necessary to permit work of other trades to be installed properly and without delay. Maintain maximum head room. If plumbing work cannot be installed at least 7’0” above the f loor (in mechanical spaces or basement and higher in finished spaces dependent on ceiling height), consult with the Engineers and obtain approval before proceeding. If directed by Architect or Engineers, prepare composite drawings and sections (scale not less than ¼” = 1’), clearly showing installation of work in relation to work of other trades. F. Should Architect's details, field conditions, change in equipment or Shop Drawing information necessitate an important rearrangement, report same to Engineers and obtain approval before proceeding. G. Install piping, etc. to avoid interferences with removal of coils, filters, belt guards or any operating part of all systems, or operation of overhead or swinging doors. Maintain easy and safe access to valves, controllers, motor starters, and other equipment requiring frequent operation. Maintain opening of access doors, switch boxes, motor starters, panel BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP MECHANICAL BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 23 01 00 – PAGE 7 OF 9 JUNE 29, 2012 boards, etc. Maintain a clear walking space. H. No compensation awarded for extra work because above precautions have not been followed. In event of conflicts, Engineer's decision is final. Contractor fully responsible for unauthorized changes. 3.2 MISCELLANEOUS PAINTING: A. Paint all hangers and exposed or unpainted or ungalvanized iron work in the Plumbing Systems with two brush coats of black rust preventative paint. Touch up any damaged surfaces of factory painted equipment. 3.3 EQUIPMENT INSTALLATION: A. It is required of each equipment manufacturer, through the Contractor, to carefully check Plans and Specifications as same affect their particular equipment. Report to Engineers, any discrepancies or contradictions as applied to their particular equipment which prevents proper functioning, servicing, etc. before or at the time when Shop Drawings are submitted. Furnish manufacturer's printed installation instructions for each piece of equipment. Thoroughly instruct contractors' personnel on job, exactly how their equipment shall be installed, connected, lubricated, started up, operated, etc., so that all factory instructions are rigidly followed. B. Install, test, start and operate all equipment only as instructed by manufacturer and in presence of manufacturer's representative, as directed. Follow instructions of manufacturer as noted above. Provide mockup installation of certain typical equipment, if required, such as fixtures, chair carriers, countersinks, etc. as directed, and obtain Architect's and Engineer's approval before proceeding with actual installation of same. C. Contractor shall provide as recommended by manufacturer all necessary incidental valves, fittings, piping, wiring, etc., not supplied by manufacturer or other Contractors, for proper apparatus operation Contractor shall provide accurate information to other Contractors for required services to equipment, such as water supply and waste connections, masonry openings, wiring requirements, etc. Such information shall be complete and correct for particular job. D. If required by Engineers, contractor shall submit satisfactory evidence that equipment, systems, etc. have been installed strictly in accordance with manufacturer's recommendations, have been properly aligned, are properly adjusted, have been properly tested, lubricated, balanced, etc. E. As soon as installed, lubricate and leave in good working order, all motors, bearings, etc., in accordance with manufacturer's instructions. F. Lubrication Chart Provide 81/2” x 11” lubrica tion chart, typed in capital BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP MECHANICAL BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 23 01 00 – PAGE 8 OF 9 JUNE 29, 2012 letters, mounted in wood frame under clear plastic. Hang were directed. Heating Contractor shall provide chart listing all motors. Other Contractors supply information on motors furnished by them. G. List following information: 1. Name and location of equipment. 2. Type of lubrication recommended by manufacturer. 3. Lubrication period recommended by manufacturer. 3.4 EQUIPMENT CHECKOUT AND TESTING: A. Notify Engineers when installation(s) is/are ready for testing, as specified with ample time in advance. Provide all metered and unmetered services, tools, equipment and manpower necessary to perform tests. B. Perform all equipment testing as specified as recommended by manufacturer and directed by Engineers. Demonstrate that all operating and safety devices are in proper working order. C. Perform necessary operating and pressure testing for all piping and equipment which shall be: buried underground, before backfilling; installed in or under slabs, before pouring; buried in building walls, before being buried and installed above furred ceilings before ceiling installation. 3.5 ACCESS DOORS: A. Provide where indicated and where required for access to all equipment. 3.6 HANGERS AND SUPPORTS: A. All components shall be selected for a minimum safety factor of 5. B. All rigid hanger assemblies shall provide for vertical movement after installation by means of threaded adjustment. C. Hanger rods shall be subjected to tensile loads only. Where axial or lateral movement is anticipated, suitable linkages shall be provided. D. Support units from the building structural system, NOT from metal roof decks. E. All units, including pipe attachments, structural attachments, hanger rods, bracing, all necessary accessories and their installation shall be in accordance with NFPA 13 Installation of Sprinkler Systems, latest issue. 3.7 IDENTIFICATION SYSTEMS (General Installation Requirements): A. Coordination: Where identification is to be applied to surfaces which BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP MECHANICAL BASIC MATERIALS AND METHODS STANDARD SPECIFICATIONS 23 01 00 – PAGE 9 OF 9 JUNE 29, 2012 require insulation, painting or other covering or finish, including valve tags in finished mechanical spaces, install identification after completion of covering and painting. B. Equipment: 1. General: Install engraved plastic laminate sign or plastic equipment marker on or near each major item of mechanical equipment and each operational device, as specified herein if not otherwise specified for each item or device. Provide signs for the following general categories of equipment and operational devices. a. Pumps, fans, and similar motordriven units. 2. Lettering Size: Minimum ¼” high lettering for name of unit where viewing distance is less than 2’ 0”, ½” high for d istances up to 6’ 0”, and proportionately larger lettering for greater distances. Provide secondary lettering ½ to ¾ of size of principal lettering. 3. Test of Signs: In addition to name of identified unit, provide lettering to distinguish between multiple units, inform operator of operational requirements, indicate safety and emergency precautions, and warn of hazards and improper operations. END OF SECTION 23 01 00 BEARDSLEY DESIGN ASSOCIATES CORNELLNCP WETPIPE SPRINKLER SYSTEMS STANDARD SPECIFICATIONS 21 13 13 – PAGE 1 OF 9 June 29, 2012 SECTION 211313 WETPIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.1 DEFINITIONS A. StandardPressure Sprinkler Piping: Wetpipe sp rinkler system piping designed to operate at working pressure of 175 psig (1200 kPa) maximum. 1.2 SYSTEM DESCRIPTIONS A. WetPipe Sprinkler System: Automatic sprinklers are attached to piping containing water and that is connected to water supply through alarm valve. Water discharges immediately from sprinklers when they are opened. Sprinklers open when heat melts fusible link or destroys frangible device. 1.3 PERFORMANCE REQUIREMENTS A. StandardPressure Piping System Component: List ed for 175psig (1200 kPa) minimum working pressure. B. Delegated Design: Design sprinkler system(s), modifications including comprehensive engineering analysis by a qualified licensed Fire Sprinkler Contractor, using performance requirements and design criteria indicated. C. Sprinkler system design shall be approved by authorities having jurisdiction. 1. Sprinkler Occupancy Hazard Classifications: a. Telecom Equipment Rooms: Ordinary Hazard, Group 1. b. Corridor, Lobbies, General Offices: Light Hazard. 2. Minimum Density for AutomaticSprinkler Piping D esign: a. OrdinaryHazard, Group 1 Occupancy: 0.15 gpm ov er 1500sq. ft. or entire area if less than 1500 sq. ft. b. Light Hazard: 0.10 gpm over 1500 sq. ft, or entire area if less than 1500 sq. ft. 3. Maximum Protection Area per Sprinkler: Per UL listing. 4. Maximum Protection Area per Sprinkler: a. Telecon Equipment Rooms: 130 sq. ft. (12.1 sq. m). b. Other Areas: According to NFPA 13 recommendations unless otherwise indicated. BEARDSLEY DESIGN ASSOCIATES CORNELLNCP WETPIPE SPRINKLER SYSTEMS STANDARD SPECIFICATIONS 21 13 13 – PAGE 2 OF 9 June 29, 2012 5. Total Combined HoseStream Demand Requirement: According to NFPA 13 unless otherwise indicated: a. LightHazard Occupancies: 100 gpm (6.3 L/s) for 30 minutes. b. OrdinaryHazard Occupancies: 250 gpm (15.75 L/s ) for 60 to 90 minutes. 1.4 SUBMITTALS A. Product Data: For each type of product indicated. 1. Equipment a. Provide manufacturer’s catalog data for each separate piece of equipment which indicates the name of the manufacturer of each item of equipment, with data highlighted to indicate model, size, options, etc. proposed for installation. B. Shop Drawings: For wetpipe sprinkler systems. Include plans, elevations, sections, details, and attachments to other work. Provide layout drawing of the complete automatic sprinkler system modifications indicating relationship of all other items including HVAC equipment, lighting fixtures, structural members and all other significant items of all piping. Complete details and sections as required to clearly define and clarify the design including details of each type of riser assembly and pipe hangers. C. DelegatedDesign Submittal: For sprinkler syste ms indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation. D. Qualification Data: For qualified Installer. E. Approved Sprinkler Piping Drawings: Working plans, prepared according to NFPA 13, that have been approved by authorities having jurisdiction, including hydraulic calculations if applicable. F. Field Test Reports and Certificates: Indicate and interpret test results for compliance with performance requirements and as described in NFPA 13. Include "Contractor's Material and Test Certificate for Aboveground Piping." G. Field qualitycontrol reports. H. Operation and Maintenance Data: For sprinkler specialties to include in emergency, operation, and maintenance manuals. 1.5 QUALITY ASSURANCE A. Installer Qualifications: BEARDSLEY DESIGN ASSOCIATES CORNELLNCP WETPIPE SPRINKLER SYSTEMS STANDARD SPECIFICATIONS 21 13 13 – PAGE 3 OF 9 June 29, 2012 1. Installer's responsibilities include designing, fabricating, and installing sprinkler system modifications and providing services needed to assume engineering responsibility. a. Engineering Responsibility: Preparation of working plans, calculations, and field test reports by a qualified licensed Fire Sprinkler Contractor. B. NFPA Standards: Sprinkler system equipment, specialties, accessories, installation, and testing shall comply with the following: 1. NFPA 13, "Installation of Sprinkler Systems." 1.6 PROJECT CONDITIONS A. Interruption of Existing Sprinkler Service: Do not interrupt sprinkler service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary sprinkler service according to requirements indicated: 1. Notify Construction Manager and/or Owner no fewer than two days in advance of proposed interruption of sprinkler service. 2. Do not proceed with interruption of sprinkler service without Construction Manager's written permission. 1.7 COORDINATION A. Coordinate layout and installation of sprinklers with other construction that penetrates ceilings, including light fixtures, HVAC equipment, and partition assemblies. 1.8 EXTRA MATERIALS A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Spare Sprinklers: Provide to Owner the number of sprinklers required by NFPA 13 and sprinkler wrench. Include spares of each type of sprinkler used on Project. PART 2 PRODUCTS 2.1 STEEL PIPE AND FITTINGS A. Schedule 40, BlackSteel Pipe: ASTM A 53/A 53M, Type E, Grade B. Pipe ends may be factory, shop fabrication or field formed to match joining method. BEARDSLEY DESIGN ASSOCIATES CORNELLNCP WETPIPE SPRINKLER SYSTEMS STANDARD SPECIFICATIONS 21 13 13 – PAGE 4 OF 9 June 29, 2012 B. BlackSteel Pipe Nipples: ASTM A 733, made of A STM A 53/A 53M, standardweight, seamless steel pipe with threaded ends. C. Uncoated, Steel Couplings: ASTM A 865, threaded. D. Uncoated, GrayIron Threaded Fittings: ASME B16 .4, Class 125, standard pattern. E. Malleable or DuctileIron Unions: UL 860. F. CastIron Flanges: ASME 16.1, Class 125. G. Steel Flanges and Flanged Fittings: ASME B16.5, Class 150. H. Steel Welding Fittings: ASTM A 234/A 234M and ASME B16.9. I. GroovedJoint, SteelPipe Appurtenances: 1. Pressure Rating: 175 psig (1200 kPa) minimum. 2. Uncoated, GroovedEnd Fittings for Steel Piping: ASTM A 47/A 47M, malleableiron casting or ASTM A 536, ductileiron casting; with dimensions matching steel pipe. 3. GroovedEndPipe Couplings for Steel Piping: AW WA C606 and UL 213, rigid pattern, unless otherwise indicated, for steelpipe dimensions. Include ferrous housing sections, EPDMrubber gaske t, and bolts and nuts. J. For buildings with existing sprinkler systems, which use galvanized steel piping, new piping shall be galvanized 2.2 PIPING JOINING MATERIALS A. PipeFlange Gasket Materials: AWWA C110, rubber , flat face, 1/8 inch (3.2 mm) thick or ASME B16.21, nonmetallic and asbestos free. 1. Class 125, CastIron Flanges and Class 150, Bron ze FlatFace Flanges: Fullface gaskets. B. Metal, PipeFlange Bolts and Nuts: ASME B18.2.1 , carbon steel unless otherwise indicated. 2.3 TRIM AND DRAIN VALVES A. General Requirements: 1. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing. BEARDSLEY DESIGN ASSOCIATES CORNELLNCP WETPIPE SPRINKLER SYSTEMS STANDARD SPECIFICATIONS 21 13 13 – PAGE 5 OF 9 June 29, 2012 2. Pressure Rating: 175 psig (1200 kPa) minimum. 3. Types: Angle, ball, and globe 2.4 SPRINKLER SPECIALTY PIPE FITTINGS A. Branch Outlet Fittings: 1. Standard: UL 213. 2. Pressure Rating: 175 psig (1200 kPa) minimum. 3. Body Material: Ductileiron housing with EPDM s eals and bolts and nuts. 4. Type: MechanicalT and cross fittings. 5. Configurations: Snapon and strapless, ductile iron housing with branch outlets. 6. Size: Of dimension to fit onto sprinkler main and with outlet connections as required to match connected branch piping. 7. Branch Outlets: Grooved, plainend pipe, or thr eaded. B. Adjustable Drop Nipples: 1. Standard: UL 1474. 2. Pressure Rating: 250 psig (1725 kPa) minimum. 3. Body Material: Steel pipe with EPDMrubber Ori ng seals. 4. Size: Same as connected piping. 5. Length: Adjustable. 6. Inlet and Outlet: Threaded. 2.5 SPRINKLERS A. General Requirements: 1. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing. 2. Pressure Rating for Automatic Sprinklers: 175 psig (1200 kPa) minimum. B. Automatic Sprinklers with HeatResponsive Elemen t: BEARDSLEY DESIGN ASSOCIATES CORNELLNCP WETPIPE SPRINKLER SYSTEMS STANDARD SPECIFICATIONS 21 13 13 – PAGE 6 OF 9 June 29, 2012 1. Nonresidential Applications: UL 199. 2. Characteristics: Nominal 1/2inch (12.7mm) ori fice with Discharge Coefficient K of 5.6, and for "Ordinary" temperature classification rating unless otherwise indicated or required by application. 3. For buildings with existing sprinkler systems, provide the same make and model sprinkler heads that are used in the building. C. Sprinkler Finishes: 1. Chrome plated. 2. Bronze. 3. Factory painted finish where required to match existing. D. Sprinkler Escutcheons: Materials, types, and finishes for the following sprinkler mounting applications. Escutcheons for concealed, flush, and semi recessedtype sprinklers are specified with sprinkl ers. 1. Ceiling Mounting: Chromeplated steel, one piec e, flat or Chromeplated steel, two piece, with 1inch (25mm) vertical adju stment or Plastic, white finish, one piece, flat. 2. Sidewall Mounting: Chromeplated steel or Plast ic, white finish, either one or two piece. E. Sprinkler Guards: 1. Standard: UL 199. 2. Type: Wire cage with fastening device for attaching to sprinkler. 2.6 DRY SPRINKLER ASSEMBLY A. Dry sprinkler assembly shall be of the sidewall type as indicated. Assembly shall include an integral escutcheon. Maximum length shall not exceed maximum indicated in UL Fire Prot Dir. Sprinklers shall have a polished chrome finish. 2.7 SLEEVES A. CastIron Wall Pipe Sleeves: Cast of fabricated of cast iron and equivalent to ductileiron pressure pipe, with plain ends and int egral waterstop unless otherwise indicated. B. Galvanized –SteelSheet Sleeves: 0.0239inch (0 .6 mm) minimum thickness, round tube closed with welded longitudinal joint. BEARDSLEY DESIGN ASSOCIATES CORNELLNCP WETPIPE SPRINKLER SYSTEMS STANDARD SPECIFICATIONS 21 13 13 – PAGE 7 OF 9 June 29, 2012 2.8 GROUT A. Standard: ASTM C 1107, Grade B, posthardening and volume adjusting, dry, hydrauliccement grout. B. Characteristics: Nonshrink, and recommended for interior and exterior applications. C. Design Mix: 5000 psi (34MPa), 28day compressi ve strength. D. Packaging: Premixed and factor packaged. PART 3 EXECUTION 3.1 PIPING INSTALLATION A. Locations and Arrangements: Drawing plans, schematics, and diagrams indicate general location and arrangement of piping. Install piping as indicated, as far as practical. 1. Deviations from approved working plans for piping require written approval from authorities having jurisdiction. File written approval with Architect before deviating from approved working plans. B. Piping Standard: Comply with requirements for installation of sprinkler piping in NFPA 13. C. Use listed fittings to make changes in direction, branch takeoffs from mains, and reductions in pipe sizes. D. Install unions adjacent to each valve in pipes NPS 2 (DN 50) and smaller. E. Install hangers and supports for sprinkler system piping according to NFPA 13. Comply with requirements for hanger materials in NFPA 13. F. Install sleeves for piping penetrations of walls and ceilings. G. Install escutcheons for piping penetrations of walls and ceilings. 3.2 JOINT CONSTRUCTION A. Install couplings, unions, nipples, and transition and special fittings that have finish and pressure ratings same as or higher than system's pressure rating for aboveground applications unless otherwise indicated. B. Ream ends of pipes and remove burrs. Bevel plain ends of steel pipe. C. Remove scale, slag, dirt, and debris from inside and outside of pipes and fittings before assembly. BEARDSLEY DESIGN ASSOCIATES CORNELLNCP WETPIPE SPRINKLER SYSTEMS STANDARD SPECIFICATIONS 21 13 13 – PAGE 8 OF 9 June 29, 2012 D. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows: 1. Apply appropriate tape or thread compound to external pipe threads. 2. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged. E. SteelPiping, CutGrooved Joints: Cut squareed ge groove in end of pipe according to AWWA C606. Assemble coupling with housing, gasket, lubricant, and bolts. Join steel pipe and grooved end fittings according to AWWA C606 for steelpipe joints. F. SteelPiping, RollGrooved Joints: Roll rounded edge groove in end of pipe according to AWWA C606. Assemble coupling with housing, gasket, lubricant, and bolts. Join steel pipe and grooved end fittings according to AWWA C606 for steelpipe grooved joints. 3.3 VALVE AND SPECIALTIES INSTALLATION A. Install drain valves according to NFPA 13 and authorities having jurisdiction. 3.4 SPRINKLER INSTALLATION A. Install sprinklers in suspended ceilings in center of narrow dimension of acoustical ceiling panels. 3.5 FIELD QUALITY CONTROL A. Perform tests and inspections. B. Tests and Inspections: 1. Leak Test: After installation, charge systems and test for leaks. Repair leaks and retest until no leaks exist. 2. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. C. Sprinkler piping system will be considered defective if it does not pass tests and inspections. D. Prepare test and inspection reports. 3.6 CLEANING A. Clean dirt and debris from sprinklers. BEARDSLEY DESIGN ASSOCIATES CORNELLNCP WETPIPE SPRINKLER SYSTEMS STANDARD SPECIFICATIONS 21 13 13 – PAGE 9 OF 9 June 29, 2012 B. Remove and replace sprinklers with paint other than factory finish. END OF SECTION 211313 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC GENERAL PROVISIONS STANDARD SPECIFICATIONS 23 01 01 – PAGE 1 OF 4 JUNE 29, 2012 SECTION 230101 HVAC GENERAL PROVISIONS PART 1 GENERAL 1.1 SUMMARY: This Section includes general administrative and procedural requirements for Division 23, Heating and Ventilation work. 1.2 DIVISION 23 6 DESCRIPTION: The technical specifications of this Contract are arranged for the convenience of the Owner and Contractor into Divisions of work. The work of Division 23, HVAC, is further described in Specification Sections of the 23 01 00 Series and on contract drawings of the "M series. The organization of this work into Divisions shall not relieve the prime Contractor from providing all of the work shown on the complete set of drawings or specified in the complete set of Specifications, whether or not the individual subcontractors correctly identify their respective responsibilities. 1.3 OTHER DIVISION SPECIFICATIONS APPLICABLE TO THIS WORK: To the extent that the work of this Division or Contract includes the work of other trades, the Contractor for this Division shall adhere to the requirements of other specification sections. All General Construction work shall be performed in accordance with the provisions of the appropriate Division 02 through Division 09 Sections. All electrical work shall be performed in accordance with appropriate Division 26 Sections. 1.4 WORK INCLUDED: The work of this Division shall include providing all materials, labor, services, permits and related work to furnish a complete, operating, tested, functioning, documented HVAC System including all work shown, specified or required for proper system operation including but not limited to the following: A. Provide Basic Materials and Methods. B. Provide Mechanical Coordination Drawings. C. Provide Exhaust Fans where shown. D. Provide Ductwork where shown. E. Provide Fire Dampers and Fire/Smoke Dampers where shown. F. Provide demolition and removal of existing equipment, ductwork and piping where shown, removal of all debris from site and proper disposal of same. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC GENERAL PROVISIONS STANDARD SPECIFICATIONS 23 01 01 – PAGE 2 OF 4 JUNE 29, 2012 G, Provide revision of ductwork piping and provide new ductwork and piping as shown on mechanical drawings. Provide liner and flexible ductwork as shown. H. Provide and install duct access panels in duct as shown. I. Provide and install new diffusers, registers and grilles. J. Provide insulation. K. Provide air balance at completion of project, provide final report. L. Provide maintenance of system in good condition until final acceptance. M. Provide openings in existing and new construction as required for the work of this division. N. Provide fan coil units where shown. O. Provide split6system air conditioning units where shown. P. Provide piping where shown. 1.5 SUBMITTALS A. Provide Shop Drawings for the following: 1. Ductwork, supply, return and flexible 2. Registers, diffusers and grilles (air devices) 3. Volume, Fire dampers, fire/smoke dampers 4. Motorized dampers 5. Access Panels 6. Insulation 7. Ductwork Coordination drawings, 8. Mechanical Coordination drawings 9. Exhaust Fans. 10. Controls, as required 11. Piping 12. Fan coil units 13. Split6system air conditioning units 14. Pre6construction & final construction testing and balancing report. B. Provide Owner's Operation Instruction C. Provide Operation and Maintenance Manuals 6 four (4) copies D. Provide Warranty Documents 1.6 RELATED WORK NOT INCLUDED: A. Asbestos removal is not included in the work of this contract. See Section 013529. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC GENERAL PROVISIONS STANDARD SPECIFICATIONS 23 01 01 – PAGE 3 OF 4 JUNE 29, 2012 PART 2 PRODUCTS 2.1 GENERAL: A. Provide products as specified in Division 23. PART 3 EXECUTION 3.1 GENERAL: A. Conform to Division 23 Specifications for installation and execution of work. END OF SECTION 230101 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC GENERAL PROVISIONS STANDARD SPECIFICATIONS 23 01 01 – PAGE 4 OF 4 JUNE 29, 2012 [ PAGE LEFT INTENTIONALLY BLANK ] BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP TESTING ADJUSTING AND BALANCING STANDARD SPECIFICATIONS 23 05 93 – PAGE 1 OF 11 JUNE 29, 2012 SECTION 230593 TESTING, ADJUSTING AND BALANCING PART 1 GENERAL 1.1 RELATED DOCUMENTS: The general provisions of the Contract, including General and Supplementary Conditions and Division 1 General Requirements, apply to the work specified in this Section. 1.2 SCOPE: A. This section includes all labor and materials necessary to test, adjust, and balance in accordance with design criteria the equipment and components of systems included in Division 23 as follows: 1. Air Distribution 2. Equipment Performance 1.3 SUBMITTALS: Provide the Following: A. Preconstruction testing & balancing report. B. Final testing & balancing report. 1.4 QUALIFICATIONS: B. Work included in this section must be performed by an AABC or NEBB certified independent testing and balancing contractor or an Owner approved TAB contractor who shall test, adjust and balance the air and water systems for this project. C. Owner approved acceptable testing and balancing agencies (no others): 1. Air Systems Balancing and Testing Service, Inc., West Henrietta, NY 585?334?7710. 2. Balance Technologies, LaFayette, NY, 315?677?7769. 3. AD&M Testing and Balancing, 3 E. Bihrwood Dr., West Seneca, NY 14224, 716?677?0980) 4. Mechanical Testing, Inc., Schenectady, NY 518?374?9440. 1.5 TEST REPORT: A. The balancing agency shall prepare a written report which shall include diagrams and descriptions of procedures together with all recorded test data. Report shall be submitted in bound volumes for a permanent record. Submit four copies of report. A set of contract drawings shall BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP TESTING ADJUSTING AND BALANCING STANDARD SPECIFICATIONS 23 05 93 – PAGE 2 OF 11 JUNE 29, 2012 also be submitted with the report. Drawings shall have each air device, flow fitting, fan, and traverse location identified in red ink by a number which shall match identification numbers utilized in the balancing report. B. Submit two (2) copies of preliminary report within 15 working days after completion of tests of individual systems. Submit four (4) copies of final report within 15 working days after completion of all final adjustments. PART 2 PRODUCTS 2.1 TEST INSTRUMENTS: A. Use instruments of equal or better quality than those described in the technical portions of Associated Air Balance Council National Standards for Field Measurements and Instrumentation Vol. 2, No. 12173 “Total System Balance”. B. Instruments used for balancing air and water systems must have been calibrated within a period of 6 months prior to balancing. Submit with balancing report, model number and calibration date of all instruments utilized. C. List in the report types, serial numbers, and dates of calibration of all instruments used in the final air and water balance tests. D. Instruments shall include, as a minimum, the following items of equipment: 1. Pressure gauges and fittings. 2. Dry bulb and wet bulb thermometers. 3. Contact pyrometer. 4. Portable flow meter and, if required, orifice plates. 5. Pitot tube and manometers. 6. Alnor Velometer with attachments. 7. Amprobe. 8. Tachometer. 9. Special wrenches and tools. 10. Anemometer. E. Provide suitable ladders and safety equipment. PART 3 EXECUTION 3.1 EXAMINATION A. Examine the Contract Documents to become familiar with Project requirements and to discover conditions in systems' designs that may preclude proper TAB of systems and equipment. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP TESTING ADJUSTING AND BALANCING STANDARD SPECIFICATIONS 23 05 93 – PAGE 3 OF 11 JUNE 29, 2012 B. Examine systems for installed balancing devices, such as test ports, gage cocks, thermometer wells, flow?control devices, balancing valves and fittings, and manual volume dampers. Verify that locations of these balancing devices are accessible. C. Examine the approved submittals for HVAC systems and equipment. D. Examine design data including HVAC system descriptions, statements of design assumptions for environmental conditions and systems' output, and statements of philosophies and assumptions about HVAC system and equipment controls. E. Examine equipment performance data including fan and pump curves. 1) Relate performance data to Project conditions and requirements, including system effects that can create undesired or unpredicted conditions that cause reduced capacities in all or part of a system. 2) Calculate system?effect factors to reduce performance ratings of HVAC equipment when installed under conditions different from the conditions used to rate equipment performance. To calculate system effects for air systems, use tables and charts found in AMCA 201, "Fans and Systems," or in SMACNA's "HVAC Systems ? Duct Design." Compare results with the design data and installed conditions. F. Examine system and equipment installations and verify that field quality? control testing, cleaning, and adjusting specified in individual Sections have been performed. G. Examine test reports specified in individual system and equipment Sections. H. Examine HVAC equipment and filters and verify that bearings are greased, belts are aligned and tight, and equipment with functioning controls is ready for operation. I. Examine terminal units, such as variable?air?volume boxes, and verify that they are accessible and their controls are connected and functioning. J. Examine strainers. Verify that startup screens are replaced by permanent screens with indicated perforations. K. Examine three?way valves for proper installation for their intended function of diverting or mixing fluid flows. L. Examine system pumps to ensure absence of entrained air in the suction piping. M. Examine operating safety interlocks and controls on HVAC equipment. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP TESTING ADJUSTING AND BALANCING STANDARD SPECIFICATIONS 23 05 93 – PAGE 4 OF 11 JUNE 29, 2012 N. Report deficiencies discovered before and during performance of TAB procedures. Observe and record system reactions to changes in conditions. Record default set points if different from indicated values. 3.2 PREPARATION A. Prepare a TAB plan that includes strategies and step?by?step procedures. B. Complete system?readiness checks and prepare reports. Verify the following: 1) Permanent electrical?power wiring is complete. 2) Hydronic systems are filled, clean, and free of air. 3) Automatic temperature?control systems are operational. 4) Equipment and duct access doors are securely closed. 5) Balance, smoke, and fire dampers are open. 6) Isolating and balancing valves are open and control valves are operational. 7) Ceilings are installed in critical areas where air?pattern adjustments are required and access to balancing devices is provided. 8) Windows and doors can be closed so indicated conditions for system operations can be met. 3.3 TEST PROCEDURE: A. System may be tested in increments when approved by the Architect/Engineer. B. When testing and balancing involve the building temperature control systems, cooperate with the University to achieve the desired results. C. At the time of the final inspection, recheck in the presence and at the request of the Architect/Engineer not to exceed 10 percent of the previously recorded readings from the certified report selected at the discretion of the Architect/Engineer. D. Permanently mark the settings of valves, dampers, and other adjustment devices so that adjustment can be restored if disturbed at any time. E. Perform all tests in accordance with Associated Air Balance Council (AABC) or NEBB standard procedures. Any deviations from same must be submitted and approved. F. Should the basic system or any of its component fail to meet requirements, and thereby make the testing and balancing work invalid, notify the Architect/Engineer and stop the tests until such time that the failure is corrected. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP TESTING ADJUSTING AND BALANCING STANDARD SPECIFICATIONS 23 05 93 – PAGE 5 OF 11 JUNE 29, 2012 3.4 PROCEDURES FOR TESTING, ADJUSTING, AND BALANCING EXISTING SYSTEMS A. Perform a preconstruction inspection of existing equipment that is to remain and be reused. 1) Measure and record the operating speed, airflow, and static pressure of each fan. 2) Measure motor voltage and amperage. Compare the values to motor nameplate information. 3) Measure and record the water flow, impeller size, pump head, hp, break hp and location on manufacturer’s pump curve for each pump. 4) Check the refrigerant charge. 5) Check the condition of filters. 6) Check the condition of coils. 7) Check the operation of the drain pan and condensate?drain trap. 8) Check bearings and other lubricated parts for proper lubrication. 9) Report on the operating condition of the equipment and the results of the measurements taken. Report deficiencies. B. Before performing testing and balancing of existing systems, inspect existing equipment that is to remain and be reused to verify that existing equipment has been cleaned and refurbished. Verify the following: 1) New filters are installed. 2) Coils are clean and fins combed. 3) Drain pans are clean. 4) Fans are clean. 5) Bearings and other parts are properly lubricated. 6) Deficiencies noted in the preconstruction report are corrected. C. Perform testing and balancing of existing systems to the extent that existing systems are affected by the renovation work. 1) Compare the indicated airflow of the renovated work to the measured fan airflows, and determine the new fan speed and the face velocity of filters and coils. 2) Compare the additional water flow required for the renovated work to the measured pump flows, and determine the new pump flow, amperage, voltage, rpm, and pump head. 3) Verify that the indicated airflows of the renovated work result in filter and coil face velocities and fan speeds that are within the acceptable limits defined by equipment manufacturer. 4) Verify that the additional water flow for the renovated work results in pump operation that is within the acceptable limits defined by equipment manufacturer. 5) If calculations increase or decrease the air flow rates and water flow rates by more than 5 percent, make equipment adjustments to achieve the calculated rates. If increase or decrease is 5 percent or less, equipment adjustments are not required. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP TESTING ADJUSTING AND BALANCING STANDARD SPECIFICATIONS 23 05 93 – PAGE 6 OF 11 JUNE 29, 2012 6) Balance each air outlet. 3.5 GENERAL: A. Review plans and specifications of systems to be tested and balanced to confirm that the arrangement, instrumentation and balancing devices will permit the system to be balanced and tested in the manner described in this section. Report to the Architect/Engineer in writing, prior to start of any system construction, any devices which need to be added or any phases of the design which need to be modified to permit the fulfillment of this work. Assume responsibility for all devices required for proper balancing beyond those defined by the contract documents, and not reported by the contractor prior to physical start of construction. B. Conduct balancing and testing in accordance with technical portions of the Associated Air Balancing Council “National Standards for Field Measurements and Instrumentation” Vol. 2, No. 12173 “Total System Balance” latest edition, or NEBB Procedural Standards for Testing and Balancing latest edition. C. Provide all labor, testing equipment, and materials required to conduct tests and balance systems (pre and post construction). Include all costs in base bid and form of proposal. D. The Testing, Adjusting, and Balancing Contractor shall be responsible for providing all duct test holes as may be required for testing and balancing of systems. E. Systems shall be operated at least 4 hours after stabilized operating conditions have been established before conducting capacity tests. All filters and strainers shall be in place. Start up strainers shall be removed. Capacity and performance tests of equipment and systems shall be performed only after balancing is complete. F. Submit for approval, a test procedure plan for variable air volume systems and other variable flow systems. Indicate diversity conditions and test modes for systems operating with diversities. G. Permanently mark the balanced position of all balancing valves and dampers. 3.6 SYSTEM CHECKOUT: A. Prior to the start of balancing, perform a system functional test. B. Lubricate and check all dampers. C. Verify that all fire dampers and fire/smoke dampers are open and links are in place. D. Check that backdraft and automatic dampers operate correctly. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP TESTING ADJUSTING AND BALANCING STANDARD SPECIFICATIONS 23 05 93 – PAGE 7 OF 11 JUNE 29, 2012 E. Check that all access doors are closed. F. Check that all valves are open. G. Check for proper belt tension and alignment on fan drivers. H. Check for proper fan rotation. I. Check that all motors and fan bearings have been lubricated. J. Confirm that motors, damper motors and valves are wired and that proper overload heaters and fuses are installed. K. Label in 1" black block letters on fan and pump housings fan name/numbers or pump name/numbers. Designation shall correspond to those on the drawings. L. Mark proper rotation on a permanent portion of the fan. 3.7 AIR DISTRIBUTION SYSTEMS: A. All air distribution systems including supply, return, outdoor, relief and exhaust ductwork shall be tested and balanced. B. Where an existing system cannot be properly balanced or equipment tested due to adverse conditions such as inability to properly adjust fan speeds, improperly sized motors, excessively noisy equipment, malfunctioning controls, dirty filters, inaccessibility, and similar items, furnish to the Architect/Engineer in writing, within seven (7) days of discovery, a list of the conditions which preclude proper execution of the work. C. Make openings in ducts required for pitot tube insertion and seal those openings with snap?in plugs or specially approved seals for grease ducts and lab ducts. Neatly remove duct insulation as required for test. D. Specific testing and balancing procedures shall include: 1. Test and adjust speed of all air apparatus. 2. Test and record motor make, horsepower, rpm, volts, phase, hertz and amperage. 3. Make Pitot tube traverse of main ducts and obtain design air quantity at fans. 4. Test and record system static pressures, suction, and discharge as well as pressure drops across each system element; i.e., fans, filters, coils, louvers, air blenders, dampers, etc. 5. Test and adjust systems for design supply, outside, relief, exhaust, and return air quantities. Test CFM at fans and adjust all fan systems to +10% to ?5% of design flow. 6. Adjust all main and branch ducts for supply, return and exhaust BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP TESTING ADJUSTING AND BALANCING STANDARD SPECIFICATIONS 23 05 93 – PAGE 8 OF 11 JUNE 29, 2012 air. Set and “mark” all volume dampers. Identify, test, and adjust each air device (grille, register, diffuser, etc.) to within 10% of design quantities. 7. Test, adjust and verify operation of unit heaters, cabinet heaters, exhaust fans, etc., in accordance with AABC or NEBB Standard procedures. Record results. 8. For each static pressure controller, establish and record setpoint; record controller offset. 9. For each air flow measuring device, verify and record flow; record measuring device offset. 10. Verify that all smoke and fire dampers are open during normal operating mode and operate properly at shutdown. 11. Set automatic operated dampers to operate as required to achieve balance conditions. 12. Lubricate all dampers and linkages. 13. Record all fan, motor, drive, sheave and belt nameplate information. E. Provide duct leakage tests. Submit test results to Architect/Engineer immediately (within 10 days) upon completion of each test and include copies of all results with balancing report test conditions and results for each section of duct tested. Include diagrams if required to define tested sections. 3.8 REPORTING: A. Initial Construction?Phase Report: Based on examination of the Contract Documents as specified in "Examination" Article, prepare a report on the adequacy of design for systems' balancing devices. Recommend changes and additions to systems' balancing devices to facilitate proper performance measuring and balancing. Recommend changes and additions to HVAC systems and general construction to allow access for performance measuring and balancing devices. B. Status Reports: Prepare biweekly progress reports to describe completed procedures, procedures in progress, and scheduled procedures. Include a list of deficiencies and problems found in systems being tested and balanced. Prepare a separate report for each system and each building floor for systems serving multiple floors. 3.9 REPORT A. General: Prepare a certified written report; tabulate and divide the report into separate sections for tested systems and balanced systems. 1) Include a certification sheet at the front of the report's binder, signed and sealed by the certified testing and balancing engineer. 2) Include a list of instruments used for procedures, along with proof of calibration. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP TESTING ADJUSTING AND BALANCING STANDARD SPECIFICATIONS 23 05 93 – PAGE 9 OF 11 JUNE 29, 2012 B. Final Report Contents: In addition to certified field?report data, include the following: 1) Pump curves. 2) Fan curves. 3) Manufacturers' test data. 4) Location, size and airflow of each grille, register or diffuser. 5) Field test reports prepared by system and equipment installers. 6) Other information relative to equipment performance; do not include Shop Drawings and product data. C. General Report Data: In addition to form titles and entries, include the following data: 1) Title page. 2) Name and address of the TAB contractor. 3) Project name. 4) Project location. 5) Architect's name and address. 6) Engineer's name and address. 7) Contractor's name and address. 8) Report date. 9) Signature of TAB supervisor who certifies the report. 10) Table of Contents with the total number of pages defined for each section of the report. Number each page in the report. 11) Summary of contents including the following: a) Indicated versus final performance. b) Notable characteristics of systems. c) Description of system operation sequence if it varies from the Contract Documents. 12) Nomenclature sheets for each item of equipment. 13) Data for terminal units, including manufacturer's name, type, size, and fittings. 14) Notes to explain why certain final data in the body of reports vary from indicated values. D. Fan Test Reports: For supply, return, and exhaust fans, include the following: 1) Fan Data: a) System identification. b) Location. c) Make and type. d) Model number and size. e) Manufacturer's serial number. f) Arrangement and class. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP TESTING ADJUSTING AND BALANCING STANDARD SPECIFICATIONS 23 05 93 – PAGE 10 OF 11 JUNE 29, 2012 g) Sheave make, size in inches (mm), and bore. h) Center?to?center dimensions of sheave, and amount of adjustments in inches (mm). 2) Motor Data: a) Motor make, and frame type and size. b) Horsepower and rpm. c) Volts, phase, and hertz. d) Full?load amperage and service factor. e) Sheave make, size in inches (mm), and bore. f) Center?to?center dimensions of sheave, and amount of adjustments in inches (mm). g) Number, make, and size of belts. 3) Test Data (Indicated and Actual Values): a) Total airflow rate in cfm (L/s). b) Total system static pressure in inches wg (Pa). c) Fan rpm. d) Discharge static pressure in inches wg (Pa). e) Suction static pressure in inches wg (Pa). E. Round, Flat?Oval, and Rectangular Duct Traverse Reports: Include a diagram with a grid representing the duct cross?section and record the following: 1) Report Data: a) System and air?handling?unit number. b) Location and zone. c) Traverse air temperature in deg F (deg C). d) Duct static pressure in inches wg (Pa). e) Duct size in inches (mm). f) Duct area in sq. ft. (sq. m). g) Indicated air flow rate in cfm (L/s). h) Indicated velocity in fpm (m/s). i) Actual air flow rate in cfm (L/s). j) Actual average velocity in fpm (m/s). k) Barometric pressure in psig (Pa). F. Pump Test Reports: Calculate impeller size by plotting the shutoff head on pump curves and include the following: 1) Unit Data: a) Unit identification. b) Location. c) Service. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP TESTING ADJUSTING AND BALANCING STANDARD SPECIFICATIONS 23 05 93 – PAGE 11 OF 11 JUNE 29, 2012 d) Make and size. e) Model number and serial number. f) Water flow rate in gpm (L/s). g) Water pressure differential in feet of head or psig (kPa). h) Required net positive suction head in feet of head or psig (kPa). i) Pump rpm. j) Impeller diameter in inches (mm). k) Motor make and frame size. l) Motor horsepower and rpm. m) Voltage at each connection. n) Amperage for each phase. o) Full?load amperage and service factor. p) Seal type. 2) Test Data (Indicated and Actual Values): a) Static head in feet of head or psig (kPa). b) Pump shutoff pressure in feet of head or psig (kPa). c) Actual impeller size in inches (mm). d) Full?open flow rate in gpm (L/s). e) Full?open pressure in feet of head or psig (kPa). f) Final discharge pressure in feet of head or psig (kPa). g) Final suction pressure in feet of head or psig (kPa). h) Final total pressure in feet of head or psig (kPa). i) Final water flow rate in gpm (L/s). j) Voltage at each connection. k) Amperage for each phase. G. Instrument Calibration Reports: 1) Report Data: a) Instrument type and make. b) Serial number. c) Application. d) Dates of use. e) Dates of calibration. 3.10 INSPECTIONS A. Initial Inspection: 1. After testing and balancing are complete, operate each system and randomly check measurements to verify that the system is operating according to the final test and balance readings documented in the final report. END OF SECTION 23 05 93 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP DUCT INSULATION STANDARD SPECIFICATIONS 23 07 13 –PAGE 1 OF 7 JUNE 29, 2012 SECTION 230713 DUCT INSULATION PART 1 GENERAL 1.1 SUBMITTALS A. Product Data: Provide for each type of product indicated. Include thermal conductivity, water1vapor permeance thickness, and jackets (both factory1 and field1applied if any). 1.2 QUALITY ASSURANCE A. Installer Qualifications: Skilled mechanics who have successfully completed an apprenticeship program or another craft training program certified by the Department of Labor, Bureau of Apprenticeship and Training. PART 2 PRODUCTS 2.1 INSULATION THICKNESS AND TYPES A. All supply and return ductwork in non1conditioned spaces shall be insulated as follows: 1. Exposed Ductwork: 1.51inches rigid fiberglass board, 3.0 pounds per cubic foot density, to a minimum R1value of 5, complete with a factory applied reinforced aluminum foil vapor barrier, suitably anchored and sealed at all points. 2. Concealed Ductwork: 1.51inches fiberglass blanket, 0.75 pounds per cubic foot density, to a minimum R1value of 5, complete with a factory applied vapor barrier, suitably anchored and sealed at all points B. The use of flexible elastomeric insulation on ductwork is permitted as an acceptable alternative to fiberglass. Insulation shall be adhered to 100% of the duct surface area. C. Preferred Manuafacturers 1. Johns Manville 2. Knauf 3. Owens Corning 4. Armacell, LLC 2.2 ADHESIVES A. Materials shall be compatible with insulation materials, jackets, and substrates and for bonding insulation to itself and to surfaces to be insulated unless otherwise indicated. B. Flexible Elastomeric Adhesive: Comply with MIL1A124179A, Type II, Class I. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP DUCT INSULATION STANDARD SPECIFICATIONS 23 07 13 –PAGE 2 OF 7 JUNE 29, 2012 1. For indoor applications, use adhesive that has a VOC content of 50 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 2. Use adhesive that complies with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small1 Scale Environmental Chambers," including 2004 Addenda. C. Mineral1Fiber Adhesive: Comply with MIL1A13316C, Class 2, Grade A. 1. For indoor applications, use adhesive that has a VOC content of 80 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 2. Use adhesive that complies with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small1 Scale Environmental Chambers," including 2004 Addenda. D. ASJ Adhesive, and FSK Jacket Adhesive: Comply with MIL1A13316C, Class 2, Grade A for bonding insulation jacket lap seams and joints. 1. For indoor applications, use adhesive that has a VOC content of 50 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 2. Use adhesive that complies with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small1 Scale Environmental Chambers," including 2004 Addenda. 2.3 MASTICS A. Materials shall be compatible with insulation materials, jackets, and substrates; comply with MIL1PRF119565C, Type II. 1. For indoor applications, use mastics that have a VOC content of 50 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). B. Vapor1Barrier Mastic: Water based; suitable for indoor use on below ambient services. 1. Water1Vapor Permeance: ASTM E 96/E 96M, Procedure B, 0.013 perm (0.009 metric perm) at 431mil (1.091mm) dry film thickness. 2. Service Temperature Range: Minus 20 to plus 180 deg F (Minus 29 to plus 82 deg C). 3. Solids Content: ASTM D 1644, 58 percent by volume and 70 percent by weight. 4. Color: White. 2.4 TAPES A. FSK Tape: Foil1face, vapor1retarder tape matching factory1applied jacket with acrylic adhesive; complying with ASTM C 1136. 1. Width: 3 inches (75 mm). 2. Thickness: 6.5 mils (0.16 mm). BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP DUCT INSULATION STANDARD SPECIFICATIONS 23 07 13 –PAGE 3 OF 7 JUNE 29, 2012 3. Adhesion: 90 ounces force/inch (1.0 N/mm) in width. 4. Elongation: 2 percent. 5. Tensile Strength: 40 lbf/inch (7.2 N/mm) in width. 6. FSK Tape Disks and Squares: Precut disks or squares of FSK tape. 2.5 SECUREMENTS A. Insulation Pins and Hangers: 1. Cupped1Head, Capacitor1Discharge1Weld Pins: Copper1 or zinc1coated steel pin, fully annealed for capacitor1discharge welding, 0.1061inch1 (2.61 mm1) diameter shank, length to suit depth of insulation indicated with integral 111/21inch (381mm) galvanized carbon1steel washer. 2. Metal, Adhesively Attached, Perforated1Base Insulation Hangers: Baseplate welded to projecting spindle that is capable of holding insulation, of thickness indicated, securely in position indicated when self1 locking washer is in place. Comply with the following requirements: a. Baseplate: Perforated, galvanized carbon1steel sheet, 0.030 inch (0.76 mm) thick by 2 inches (50 mm) square. b. Spindle: Copper1 or zinc1coated, low1carbon steel, fully annealed, 0.1061inch1 (2.61mm1) diameter shank, length to suit depth of insulation indicated. c. Adhesive: Recommended by hanger manufacturer. Product with demonstrated capability to bond insulation hanger securely to substrates indicated without damaging insulation, hangers, and substrates. 3. Insulation1Retaining Washers: Self1locking washers formed from 0.0161 inch1 (0.411mm1) thick, galvanized1steel sheet, with beveled edge sized as required to hold insulation securely in place but not less than 111/2 inches (38 mm) in diameter. a. Protect ends with capped self1locking washers incorporating a spring steel insert to ensure permanent retention of cap in exposed locations. B. Staples: Outward1clinching insulation staples, nominal 3/41inch1 (191mm1) wide, stainless steel or Monel. PART 3 EXECUTION 3.1 GENERAL INSTALLATION REQUIREMENTS A. Install insulation materials, accessories, and finishes with smooth, straight, and even surfaces; free of voids throughout the length of ducts and fittings. B. Install accessories compatible with insulation materials and suitable for the service. Install accessories that do not corrode, soften, or otherwise attack insulation or jacket in either wet or dry state. C. Install insulation with longitudinal seams at top and bottom of horizontal runs. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP DUCT INSULATION STANDARD SPECIFICATIONS 23 07 13 –PAGE 4 OF 7 JUNE 29, 2012 D. Install multiple layers of insulation with longitudinal and end seams staggered. E. Keep insulation materials dry during application and finishing. F. Install insulation with tight longitudinal seams and end joints. Bond seams and joints with adhesive recommended by insulation material manufacturer. G. Install insulation with least number of joints practical. H. Where vapor barrier is indicated, seal joints, seams, and penetrations in insulation at hangers, supports, anchors, and other projections with vapor1 barrier mastic. 1. Install insulation continuously through hangers and around anchor attachments. 2. For insulation application where vapor barriers are indicated, extend insulation on anchor legs from point of attachment to supported item to point of attachment to structure. Taper and seal ends at attachment to structure with vapor1barrier mastic. 3. Install insert materials and install insulation to tightly join the insert. Seal insulation to insulation inserts with adhesive or sealing compound recommended by insulation material manufacturer. I. Apply adhesives, mastics, and sealants at manufacturer's recommended coverage rate and wet and dry film thicknesses. J. Install insulation with factory1applied jackets as follows: 1. Draw jacket tight and smooth. 2. Cover circumferential joints with 31inch1 (751mm1) wide strips, of same material as insulation jacket. Secure strips with adhesive and outward clinching staples along both edges of strip, spaced 4 inches (100 mm) o.c. 3. Overlap jacket longitudinal seams at least 111/2 inches (38 mm). Clean and dry surface to receive self1sealing lap. Staple laps with outward clinching staples along edge at 2 inches (50 mm) o.c. a. For below ambient services, apply vapor1barrier mastic over staples. 4. Cover joints and seams with tape, according to insulation material manufacturer's written instructions, to maintain vapor seal. 5. Where vapor barriers are indicated, apply vapor1barrier mastic on seams and joints and at ends adjacent to duct flanges and fittings. K. Cut insulation in a manner to avoid compressing insulation more than 75 percent of its nominal thickness. L. Finish installation with systems at operating conditions. Repair joint separations and cracking due to thermal movement. M. Repair damaged insulation facings by applying same facing material over damaged areas. Extend patches at least 4 inches (100 mm) beyond damaged areas. Adhere, staple, and seal patches similar to butt joints. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP DUCT INSULATION STANDARD SPECIFICATIONS 23 07 13 –PAGE 5 OF 7 JUNE 29, 2012 3.2 INSTALLATION OF MINERAL1FIBER INSULATION A. Blanket Insulation Installation on Ducts and Plenums: Secure with adhesive and insulation pins. 1. Apply adhesives according to manufacturer's recommended coverage rates per unit area, for 100 percent coverage of duct and plenum surfaces. 2. Apply adhesive to entire circumference of ducts and to all surfaces of fittings and transitions. 3. Install cupped1head, capacitor1discharge1weld pins on sides and bottom of horizontal ducts and sides of vertical ducts as follows: a. On duct sides with dimensions 18 inches (450 mm) and smaller, place pins along longitudinal centerline of duct. Space 3 inches (75 mm) maximum from insulation end joints, and 16 inches (400 mm) o.c. b. On duct sides with dimensions larger than 18 inches (450 mm), place pins 16 inches (400 mm) o.c. each way, and 3 inches (75 mm) maximum from insulation joints. Install additional pins to hold insulation tightly against surface at cross bracing. c. Pins may be omitted from top surface of horizontal, rectangular ducts and plenums. d. Do not overcompress insulation during installation. e. Impale insulation over pins and attach speed washers. f. Cut excess portion of pins extending beyond speed washers or bend parallel with insulation surface. Cover exposed pins and washers with tape matching insulation facing. 4. For ducts and plenums with surface temperatures below ambient, install a continuous unbroken vapor barrier. Create a facing lap for longitudinal seams and end joints with insulation by removing 2 inches (50 mm) from one edge and one end of insulation segment. Secure laps to adjacent insulation section with 1/21inch (131mm) outward1clinching staples, 1 inch (25 mm) o.c. Install vapor barrier consisting of factory1 or field1applied jacket, adhesive, vapor1barrier mastic, and sealant at joints, seams, and protrusions. a. Repair punctures, tears, and penetrations with tape or mastic to maintain vapor1barrier seal. b. Install vapor stops for ductwork and plenums operating below 50 deg F (10 deg C) at 181foot (5.51m) intervals. Vapor stops shall consist of vapor1barrier mastic applied in a Z1shaped pattern over insulation face, along butt end of insulation, and over the surface. Cover insulation face and surface to be insulated a width equal to two times the insulation thickness, but not less than 3 inches (75 mm). 5. Overlap unfaced blankets a minimum of 2 inches (50 mm) on longitudinal seams and end joints. At end joints, secure with steel bands spaced a maximum of 18 inches (450 mm) o.c. 6. Install insulation on rectangular duct elbows and transitions with a full insulation section for each surface. Install insulation on round and flat1 oval duct elbows with individually mitered gores cut to fit the elbow. 7. Insulate duct stiffeners, hangers, and flanges that protrude beyond insulation surface with 61inch1 (1501mm1) wide strips of same material BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP DUCT INSULATION STANDARD SPECIFICATIONS 23 07 13 –PAGE 6 OF 7 JUNE 29, 2012 used to insulate duct. Secure on alternating sides of stiffener, hanger, and flange with pins spaced 6 inches (150 mm) o.c. B. Board Insulation Installation on Ducts and Plenums: Secure with adhesive and insulation pins. 1. Apply adhesives according to manufacturer's recommended coverage rates per unit area, for 100 percent coverage of duct and plenum surfaces. 2. Apply adhesive to entire circumference of ducts and to all surfaces of fittings and transitions. 3. Install either capacitor1discharge1weld pins and speed washers or cupped1 head, capacitor1discharge1weld pins on sides and bottom of horizontal ducts and sides of vertical ducts as follows: a. On duct sides with dimensions 18 inches (450 mm) and smaller, place pins along longitudinal centerline of duct. Space 3 inches (75 mm) maximum from insulation end joints, and 16 inches (400 mm) o.c. b. On duct sides with dimensions larger than 18 inches (450 mm), space pins 16 inches (400 mm) o.c. each way, and 3 inches (75 mm) maximum from insulation joints. Install additional pins to hold insulation tightly against surface at cross bracing. c. Pins may be omitted from top surface of horizontal, rectangular ducts and plenums. d. Do not overcompress insulation during installation. e. Cut excess portion of pins extending beyond speed washers or bend parallel with insulation surface. Cover exposed pins and washers with tape matching insulation facing. 4. For ducts and plenums with surface temperatures below ambient, install a continuous unbroken vapor barrier. Create a facing lap for longitudinal seams and end joints with insulation by removing 2 inches (50 mm) from one edge and one end of insulation segment. Secure laps to adjacent insulation section with 1/21inch (131mm) outward1clinching staples, 1 inch (25 mm) o.c. Install vapor barrier consisting of factory1 or field1applied jacket, adhesive, vapor1barrier mastic, and sealant at joints, seams, and protrusions. a. Repair punctures, tears, and penetrations with tape or mastic to maintain vapor1barrier seal. b. Install vapor stops for ductwork and plenums operating below 50 deg F (10 deg C) at 181foot (5.51m) intervals. Vapor stops shall consist of vapor1barrier mastic applied in a Z1shaped pattern over insulation face, along butt end of insulation, and over the surface. Cover insulation face and surface to be insulated a width equal to two times the insulation thickness, but not less than 3 inches (75 mm). 5. Install insulation on rectangular duct elbows and transitions with a full insulation section for each surface. Groove and score insulation to fit as closely as possible to outside and inside radius of elbows. Install insulation on round and flat1oval duct elbows with individually mitered gores cut to fit the elbow. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP DUCT INSULATION STANDARD SPECIFICATIONS 23 07 13 –PAGE 7 OF 7 JUNE 29, 2012 6. Insulate duct stiffeners, hangers, and flanges that protrude beyond insulation surface with 61inch1 (1501mm1) wide strips of same material used to insulate duct. Secure on alternating sides of stiffener, hanger, and flange with pins spaced 6 inches (150 mm) o.c. END OF SECTION 230713 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 1 OF 18 JUNE 29, 2012 SECTION 230719 HVAC PIPING INSULATION PART 1 GENERAL 1.1 SUBMITTALS A. Product Data: Provide for each type of product indicated. Include thermal conductivity, water4vapor permeance thickness, and jackets (both factory and field applied if any). 1.2 QUALITY ASSURANCE A. Installer Qualifications: Skilled mechanics who have successfully completed an apprenticeship program or another craft training program certified by the Department of Labor, Bureau of Apprenticeship and Training. B. Surface4Burning Characteristics: For insulation and related materials, as determined by testing identical products according to ASTM E 84, by a testing and inspecting agency acceptable to authorities having jurisdiction. Factory label insulation and jacket materials and adhesive, mastic, tapes, and cement material containers, with appropriate markings of applicable testing agency. 1. Insulation Installed Indoors: Flame4spread index of 25 or less, and smoke4developed index of 50 or less. 2. Insulation Installed Outdoors: Flame4spread index of 75 or less, and smoke4developed index of 150 or less. 1.3 DELIVERY, STORAGE, AND HANDLING A. Packaging: Insulation material containers shall be marked by manufacturer with appropriate ASTM standard designation, type and grade, and maximum use temperature. 1.4 COORDINATION A. Coordinate sizes and locations of supports, hangers, and insulation shields. B. Coordinate clearance requirements with piping Installer for piping insulation application. PART 2 PRODUCTS 2.1 INSULATION MATERIALS A. Comply with requirements in "Piping Insulation Schedule, General," "Indoor Piping Insulation Schedule," "Outdoor, Aboveground Piping Insulation Schedule," articles for where insulating materials shall be applied. B. Products shall not contain asbestos, lead, mercury, or mercury compounds. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 2 OF 18 JUNE 29, 2012 C. Products that come in contact with stainless steel shall have a leachable chloride content of less than 50 ppm when tested according to ASTM C 871. D. Insulation materials for use on austenitic stainless steel shall be qualified as acceptable according to ASTM C 795. E. Foam insulation materials shall not use CFC or HCFC blowing agents in the manufacturing process. F. Cellular Glass: Inorganic, incombustible, foamed or cellulated glass with annealed, rigid, hermetically sealed cells. Factory4applied jacket requirements are specified in "Factory4Applied Jackets" Article. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Pittsburgh Corning Corporation; Foamglas. 2. Block Insulation: ASTM C 552, Type I. 3. Special4Shaped Insulation: ASTM C 552, Type III. 4. Board Insulation: ASTM C 552, Type IV. 5. Preformed Pipe Insulation without Jacket: Comply with ASTM C 552, Type II, Class 1. 6. Preformed Pipe Insulation with Factory4Applied ASJ: Comply with ASTM C 552, Type II, Class 2. 7. Factory fabricate shapes according to ASTM C 450 and ASTM C 585. G. Flexible Elastomeric Insulation: Closed4cell, sponge4 or expanded4rubber materials. Comply with ASTM C 534, Type I for tubular materials. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Aeroflex USA, Inc.; Aerocel. b. Armacell LLC; AP Armaflex. c. K4Flex USA; Insul4Lock, Insul4Tube, and K4FLEX LS. H. Mineral4Fiber, Preformed Pipe Insulation: 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Fibrex Insulations Inc.; Coreplus 1200. b. Johns Manville; Micro4Lok. c. Knauf Insulation; 10004Degree Pipe Insulation. d. Manson Insulation Inc.; Alley4K. e. Owens Corning; Fiberglas Pipe Insulation. 2. Type I, 850 deg F (454 deg C) Materials: Mineral or glass fibers bonded with a thermosetting resin. Comply with ASTM C 547, Type I, Grade A, with factory4applied ASJ. Factory4applied jacket requirements are specified in "Factory4Applied Jackets" Article. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 3 OF 18 JUNE 29, 2012 2.2 INSULATING CEMENTS A. Mineral4Fiber Insulating Cement: Comply with ASTM C 195. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Ramco Insulation, Inc.; Super4Stik. B. Expanded or Exfoliated Vermiculite Insulating Cement: Comply with ASTM C 196. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Ramco Insulation, Inc.; Thermokote V. C. Mineral4Fiber, Hydraulic4Setting Insulating and Finishing Cement: Comply with ASTM C 449. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Ramco Insulation, Inc.; Ramcote 1200 and Quik4Cote. 2.3 ADHESIVES A. Materials shall be compatible with insulation materials, jackets, and substrates and for bonding insulation to itself and to surfaces to be insulated unless otherwise indicated. B. Cellular4Glass Adhesive: Two4component, thermosetting urethane adhesive containing no flammable solvents, with a service temperature range of minus 100 to plus 200 deg F (minus 73 to plus 93 deg C). 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Foster Brand, Specialty Construction Brands, Inc., a business of H. B. Fuller Company; 81484. 2. For indoor applications, use adhesive that has a VOC content of 50 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 3. Use adhesive that complies with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small4 Scale Environmental Chambers," including 2004 Addenda. C. Flexible Elastomeric Adhesive: Comply with MIL4A424179A, Type II, Class I. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Aeroflex USA, Inc.; Aeroseal. b. Armacell LLC; Armaflex 520 Adhesive. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 4 OF 18 JUNE 29, 2012 c. Foster Brand, Specialty Construction Brands, Inc., a business of H. B. Fuller Company; 85475. d. K4Flex USA; R4373 Contact Adhesive. 2. For indoor applications, use adhesive that has a VOC content of 50 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 3. Use adhesive that complies with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small4 Scale Environmental Chambers," including 2004 Addenda. D. Mineral4Fiber Adhesive: Comply with MIL4A43316C, Class 2, Grade A. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Childers Brand, Specialty Construction Brands, Inc., a business of H. B. Fuller Company; CP4127. b. Eagle Bridges 4 Marathon Industries; 225. c. Foster Brand, Specialty Construction Brands, Inc., a business of H. B. Fuller Company; 85460/85470. d. Mon4Eco Industries, Inc.; 22425. 2. For indoor applications, use adhesive that has a VOC content of 80 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 3. Use adhesive that complies with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small4 Scale Environmental Chambers," including 2004 Addenda. E. ASJ Adhesive, and FSK Jacket Adhesive: Comply with MIL4A43316C, Class 2, Grade A for bonding insulation jacket lap seams and joints. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Childers Brand, Specialty Construction Brands, Inc., a business of H. B. Fuller Company; CP482. b. Eagle Bridges 4 Marathon Industries; 225. c. Foster Brand, Specialty Construction Brands, Inc., a business of H. B. Fuller Company; 85450. d. Mon4Eco Industries, Inc.; 22425. 2. For indoor applications, use adhesive that has a VOC content of 50 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 3. Use adhesive that complies with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small4 Scale Environmental Chambers," including 2004 Addenda. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 5 OF 18 JUNE 29, 2012 2.4 MASTICS A. Materials shall be compatible with insulation materials, jackets, and substrates; comply with MIL4PRF419565C, Type II. 1. For indoor applications, use mastics that have a VOC content of 50 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). B. Vapor4Barrier Mastic: Water based; suitable for indoor use on below4ambient services. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Foster Brand, Specialty Construction Brands, Inc., a business of H. B. Fuller Company; 30480/30490. b. Vimasco Corporation; 749. 2. Water4Vapor Permeance: ASTM E 96/E 96M, Procedure B, 0.013 perm (0.009 metric perm) at 434mil (1.094mm) dry film thickness. 3. Service Temperature Range: Minus 20 to plus 180 deg F (Minus 29 to plus 82 deg C). 4. Solids Content: ASTM D 1644, 58 percent by volume and 70 percent by weight. 5. Color: White. 2.5 LAGGING ADHESIVES A. Description: Comply with MIL4A43316C, Class I, Grade A and shall be compatible with insulation materials, jackets, and substrates. 1. For indoor applications, use lagging adhesives that have a VOC content of 50 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 2. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Childers Brand, Specialty Construction Brands, Inc., a business of H. B. Fuller Company; CP450 AHV2. b. Foster Brand, Specialty Construction Brands, Inc., a business of H. B. Fuller Company; 30436. c. Vimasco Corporation; 713 and 714. 3. Fire4resistant, water4based lagging adhesive and coating for use indoors to adhere fire4resistant lagging cloths over pipe insulation. 4. Service Temperature Range: 0 to plus 180 deg F (Minus 18 to plus 82 deg C). 5. Color: White. 2.6 SEALANTS A. Joint Sealants: BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 6 OF 18 JUNE 29, 2012 1. Joint Sealants for Cellular4Glass Products, Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Childers Brand, Specialty Construction Brands, Inc., a business of H. B. Fuller Company; CP476. b. Eagle Bridges 4 Marathon Industries; 405. c. Foster Brand, Specialty Construction Brands, Inc., a business of H. B. Fuller Company; 30445. d. Mon4Eco Industries, Inc.; 44405. e. Pittsburgh Corning Corporation; Pittseal 444. B. FSK and Metal Jacket Flashing Sealants: 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Childers Brand, Specialty Construction Brands, Inc., a business of H. B. Fuller Company; CP476. b. Eagle Bridges 4 Marathon Industries; 405. c. Foster Brand, Specialty Construction Brands, Inc., a business of H. B. Fuller Company; 95444. d. Mon4Eco Industries, Inc.; 44405. 2. Materials shall be compatible with insulation materials, jackets, and substrates. 3. Fire4 and water4resistant, flexible, elastomeric sealant. 4. Service Temperature Range: Minus 40 to plus 250 deg F (Minus 40 to plus 121 deg C). 5. Color: Aluminum. 6. For indoor applications, use sealants that have a VOC content of 420 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 7. Use sealants that comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small4 Scale Environmental Chambers," including 2004 Addenda. C. ASJ Flashing Sealants, and Vinyl, PVDC, and PVC Jacket Flashing Sealants: 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Childers Brand, Specialty Construction Brands, Inc., a business of H. B. Fuller Company; CP476. 2. Materials shall be compatible with insulation materials, jackets, and substrates. 3. Fire4 and water4resistant, flexible, elastomeric sealant. 4. Service Temperature Range: Minus 40 to plus 250 deg F (Minus 40 to plus 121 deg C). 5. Color: White. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 7 OF 18 JUNE 29, 2012 6. For indoor applications, use sealants that have a VOC content of 420 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 7. Use sealants that comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small4 Scale Environmental Chambers," including 2004 Addenda. 2.7 FACTORY4APPLIED JACKETS A. Insulation system schedules indicate factory4applied jackets on various applications. When factory4applied jackets are indicated, comply with the following: 1. ASJ: White, kraft4paper, fiberglass4reinforced scrim with aluminum4foil backing; complying with ASTM C 1136, Type I. 2. FSK Jacket: Aluminum4foil, fiberglass4reinforced scrim with kraft4paper backing; complying with ASTM C 1136, Type II. 2.8 FIELD4APPLIED JACKETS A. Field4applied jackets shall comply with ASTM C 921, Type I, unless otherwise indicated. B. FSK Jacket: Aluminum4foil4face, fiberglass4reinforced scrim with kraft4paper backing. C. PVC Jacket: High4impact4resistant, UV4resistant PVC complying with ASTM D 1784, Class 163544C; thickness as scheduled; roll stock ready for shop or field cutting and forming. Thickness is indicated in field4applied jacket schedules. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Johns Manville; Zeston. b. P.I.C. Plastics, Inc.; FG Series. c. Proto Corporation; LoSmoke. d. Speedline Corporation; SmokeSafe. 2. Adhesive: As recommended by jacket material manufacturer. 3. Color: White. 4. Factory4fabricated fitting covers to match jacket if available; otherwise, field fabricate. a. Shapes: 454 and 904degree, short4 and long4radius elbows, tees, valves, flanges, unions, reducers, end caps, soil4pipe hubs, traps, mechanical joints, and P4trap and supply covers for lavatories. D. Self4Adhesive Outdoor Jacket: 604mil4 (1.54mm4) thick, laminated vapor barrier and waterproofing membrane for installation over insulation located aboveground outdoors; consisting of a rubberized bituminous resin on a crosslaminated polyethylene film covered with white aluminum4foil facing. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 8 OF 18 JUNE 29, 2012 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Polyguard Products, Inc.; Alumaguard 60. 2.9 TAPES A. ASJ Tape: White vapor4retarder tape matching factory4applied jacket with acrylic adhesive, complying with ASTM C 1136. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. ABI, Ideal Tape Division; 428 AWF ASJ. b. Avery Dennison Corporation, Specialty Tapes Division; Fasson 0836. c. Compac Corporation; 104 and 105. d. Venture Tape; 1540 CW Plus, 1542 CW Plus, and 1542 CW Plus/SQ. 2. Width: 3 inches (75 mm). 3. Thickness: 11.5 mils (0.29 mm). 4. Adhesion: 90 ounces force/inch (1.0 N/mm) in width. 5. Elongation: 2 percent. 6. Tensile Strength: 40 lbf/inch (7.2 N/mm) in width. 7. ASJ Tape Disks and Squares: Precut disks or squares of ASJ tape. B. FSK Tape: Foil4face, vapor4retarder tape matching factory4applied jacket with acrylic adhesive; complying with ASTM C 1136. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. ABI, Ideal Tape Division; 491 AWF FSK. b. Avery Dennison Corporation, Specialty Tapes Division; Fasson 0827. c. Compac Corporation; 110 and 111. d. Venture Tape; 1525 CW NT, 1528 CW, and 1528 CW/SQ. 2. Width: 3 inches (75 mm). 3. Thickness: 6.5 mils (0.16 mm). 4. Adhesion: 90 ounces force/inch (1.0 N/mm) in width. 5. Elongation: 2 percent. 6. Tensile Strength: 40 lbf/inch (7.2 N/mm) in width. 7. FSK Tape Disks and Squares: Precut disks or squares of FSK tape. 2.10 SECUREMENTS A. Bands: 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. ITW Insulation Systems; Gerrard Strapping and Seals. b. RPR Products, Inc.; Insul4Mate Strapping, Seals, and Springs. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 9 OF 18 JUNE 29, 2012 2. Stainless Steel: ASTM A 167 or ASTM A 240/A 240M, Type 304; 0.015 inch (0.38 mm) thick, 1/2 inch (13 mm) wide with wing seal. 3. Aluminum: ASTM B 209 (ASTM B 209M), Alloy 3003, 3005, 3105, or 5005; Temper H414, 0.020 inch (0.51 mm) thick, 1/2 inch (13 mm) wide with wing seal. B. Staples: Outward4clinching insulation staples, nominal 3/44inch4 (194mm4) wide, stainless steel or Monel. PART 3 EXECUTION 3.1 EXAMINATION A. Examine substrates and conditions for compliance with requirements for installation tolerances and other conditions affecting performance of insulation application. 1. Verify that systems to be insulated have been tested and are free of defects. 2. Verify that surfaces to be insulated are clean and dry. 3. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 PREPARATION A. Surface Preparation: Clean and dry surfaces to receive insulation. Remove materials that will adversely affect insulation application. B. Surface Preparation: Clean and prepare surfaces to be insulated. Before insulating, apply a corrosion coating to insulated surfaces as follows: 1. Carbon Steel: Coat carbon steel operating at a service temperature between 32 and 300 deg F (0 and 149 deg C) with an epoxy coating. Consult coating manufacturer for appropriate coating materials and application methods for operating temperature range. C. Coordinate insulation installation with the trade installing heat tracing. Comply with requirements for heat tracing that apply to insulation. D. Mix insulating cements with clean potable water; if insulating cements are to be in contact with stainless4steel surfaces, use demineralized water. 3.3 GENERAL INSTALLATION REQUIREMENTS A. Install insulation materials, accessories, and finishes with smooth, straight, and even surfaces; free of voids throughout the length of piping including fittings, valves, and specialties. B. Install insulation materials, forms, vapor barriers or retarders, jackets, and thicknesses required for each item of pipe system as specified in insulation system schedules. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 10 OF 18 JUNE 29, 2012 C. Install accessories compatible with insulation materials and suitable for the service. Install accessories that do not corrode, soften, or otherwise attack insulation or jacket in either wet or dry state. D. Install insulation with longitudinal seams at top and bottom of horizontal runs. E. Install multiple layers of insulation with longitudinal and end seams staggered. F. Do not weld brackets, clips, or other attachment devices to piping, fittings, and specialties. G. Keep insulation materials dry during application and finishing. H. Install insulation with tight longitudinal seams and end joints. Bond seams and joints with adhesive recommended by insulation material manufacturer. I. Install insulation with least number of joints practical. J. Where vapor barrier is indicated, seal joints, seams, and penetrations in insulation at hangers, supports, anchors, and other projections with vapor4 barrier mastic. 1. Install insulation continuously through hangers and around anchor attachments. 2. For insulation application where vapor barriers are indicated, extend insulation on anchor legs from point of attachment to supported item to point of attachment to structure. Taper and seal ends at attachment to structure with vapor4barrier mastic. 3. Install insert materials and install insulation to tightly join the insert. Seal insulation to insulation inserts with adhesive or sealing compound recommended by insulation material manufacturer. 4. Cover inserts with jacket material matching adjacent pipe insulation. Install shields over jacket, arranged to protect jacket from tear or puncture by hanger, support, and shield. K. Apply adhesives, mastics, and sealants at manufacturer's recommended coverage rate and wet and dry film thicknesses. L. Install insulation with factory4applied jackets as follows: 1. Draw jacket tight and smooth. 2. Cover circumferential joints with 34inch4 (754mm4) wide strips, of same material as insulation jacket. Secure strips with adhesive and outward clinching staples along both edges of strip, spaced 4 inches (100 mm) o.c. 3. Overlap jacket longitudinal seams at least 141/2 inches (38 mm). Install insulation with longitudinal seams at bottom of pipe. Clean and dry surface to receive self4sealing lap. Staple laps with outward clinching staples along edge at 2 inches (50 mm) o.c. a. For below4ambient services, apply vapor4barrier mastic over staples. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 11 OF 18 JUNE 29, 2012 4. Cover joints and seams with tape, according to insulation material manufacturer's written instructions, to maintain vapor seal. 5. Where vapor barriers are indicated, apply vapor4barrier mastic on seams and joints and at ends adjacent to pipe flanges and fittings. M. Cut insulation in a manner to avoid compressing insulation more than 75 percent of its nominal thickness. N. Finish installation with systems at operating conditions. Repair joint separations and cracking due to thermal movement. O. Repair damaged insulation facings by applying same facing material over damaged areas. Extend patches at least 4 inches (100 mm) beyond damaged areas. Adhere, staple, and seal patches similar to butt joints. 3.4 PENETRATIONS A. Insulation Installation at Roof Penetrations: Install insulation continuously through roof penetrations. 1. Seal penetrations with flashing sealant. 2. For applications requiring only indoor insulation, terminate insulation above roof surface and seal with joint sealant. For applications requiring indoor and outdoor insulation, install insulation for outdoor applications tightly joined to indoor insulation ends. Seal joint with joint sealant. 3. Extend jacket of outdoor insulation outside roof flashing at least 2 inches (50 mm) below top of roof flashing. 4. Seal jacket to roof flashing with flashing sealant. B. Insulation Installation at Aboveground Exterior Wall Penetrations: Install insulation continuously through wall penetrations. 1. Seal penetrations with flashing sealant. 2. For applications requiring only indoor insulation, terminate insulation inside wall surface and seal with joint sealant. For applications requiring indoor and outdoor insulation, install insulation for outdoor applications tightly joined to indoor insulation ends. Seal joint with joint sealant. 3. Extend jacket of outdoor insulation outside wall flashing and overlap wall flashing at least 2 inches (50 mm). 4. Seal jacket to wall flashing with flashing sealant. C. Insulation Installation at Interior Wall and Partition Penetrations (That Are Not Fire Rated): Install insulation continuously through walls and partitions. D. Insulation Installation at Fire4Rated Wall and Partition Penetrations: Install insulation continuously through penetrations of fire4rated walls and partitions. E. Insulation Installation at Floor Penetrations: 1. Pipe: Install insulation continuously through floor penetrations. 2. Seal penetrations through fire4rated assemblies. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 12 OF 18 JUNE 29, 2012 3.5 GENERAL PIPE INSULATION INSTALLATION A. Requirements in this article generally apply to all insulation materials except where more specific requirements are specified in various pipe insulation material installation articles. B. Insulation Installation on Fittings, Valves, Strainers, Flanges, and Unions: 1. Install insulation over fittings, valves, strainers, flanges, unions, and other specialties with continuous thermal and vapor4retarder integrity unless otherwise indicated. 2. Insulate pipe elbows using preformed fitting insulation or mitered fittings made from same material and density as adjacent pipe insulation. Each piece shall be butted tightly against adjoining piece and bonded with adhesive. Fill joints, seams, voids, and irregular surfaces with insulating cement finished to a smooth, hard, and uniform contour that is uniform with adjoining pipe insulation. 3. Insulate tee fittings with preformed fitting insulation or sectional pipe insulation of same material and thickness as used for adjacent pipe. Cut sectional pipe insulation to fit. Butt each section closely to the next and hold in place with tie wire. Bond pieces with adhesive. 4. Insulate valves using preformed fitting insulation or sectional pipe insulation of same material, density, and thickness as used for adjacent pipe. Overlap adjoining pipe insulation by not less than two times the thickness of pipe insulation, or one pipe diameter, whichever is thicker. For valves, insulate up to and including the bonnets, valve stuffing4box studs, bolts, and nuts. Fill joints, seams, and irregular surfaces with insulating cement. 5. Insulate strainers using preformed fitting insulation or sectional pipe insulation of same material, density, and thickness as used for adjacent pipe. Overlap adjoining pipe insulation by not less than two times the thickness of pipe insulation, or one pipe diameter, whichever is thicker. Fill joints, seams, and irregular surfaces with insulating cement. Insulate strainers so strainer basket flange or plug can be easily removed and replaced without damaging the insulation and jacket. Provide a removable reusable insulation cover. For below4ambient services, provide a design that maintains vapor barrier. 6. Insulate flanges and unions using a section of oversized preformed pipe insulation. Overlap adjoining pipe insulation by not less than two times the thickness of pipe insulation, or one pipe diameter, whichever is thicker. 7. Cover segmented insulated surfaces with a layer of finishing cement and coat with a mastic. Install vapor4barrier mastic for below4ambient services and a breather mastic for above4ambient services. Reinforce the mastic with fabric4reinforcing mesh. Trowel the mastic to a smooth and well4 shaped contour. 8. For services not specified to receive a field4applied jacket except for flexible elastomeric and polyolefin, install fitted PVC cover over elbows, tees, strainers, valves, flanges, and unions. Terminate ends with PVC end caps. Tape PVC covers to adjoining insulation facing using PVC tape. 9. Stencil or label the outside insulation jacket of each union with the word "union." Match size and color of pipe labels. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 13 OF 18 JUNE 29, 2012 C. Insulate instrument connections for thermometers, pressure gages, pressure temperature taps, test connections, flow meters, sensors, switches, and transmitters on insulated pipes. Shape insulation at these connections by tapering it to and around the connection with insulating cement and finish with finishing cement, mastic, and flashing sealant. D. Install removable insulation covers at locations indicated. Installation shall conform to the following: 1. Make removable flange and union insulation from sectional pipe insulation of same thickness as that on adjoining pipe. Install same insulation jacket as adjoining pipe insulation. 2. When flange and union covers are made from sectional pipe insulation, extend insulation from flanges or union at least two times the insulation thickness over adjacent pipe insulation on each side of flange or union. Secure flange cover in place with stainless4steel or aluminum bands. Select band material compatible with insulation and jacket. 3. Construct removable valve insulation covers in same manner as for flanges, except divide the two4part section on the vertical center line of valve body. 4. When covers are made from block insulation, make two halves, each consisting of mitered blocks wired to stainless4steel fabric. Secure this wire frame, with its attached insulation, to flanges with tie wire. Extend insulation at least 2 inches (50 mm) over adjacent pipe insulation on each side of valve. Fill space between flange or union cover and pipe insulation with insulating cement. Finish cover assembly with insulating cement applied in two coats. After first coat is dry, apply and trowel second coat to a smooth finish. 5. Unless a PVC jacket is indicated in field4applied jacket schedules, finish exposed surfaces with a metal jacket. 3.6 INSTALLATION OF CELLULAR4GLASS INSULATION A. Insulation Installation on Straight Pipes and Tubes: 1. Secure each layer of insulation to pipe with wire or bands and tighten bands without deforming insulation materials. 2. Where vapor barriers are indicated, seal longitudinal seams, end joints, and protrusions with vapor4barrier mastic and joint sealant. 3. For insulation with factory4applied jackets on below4ambient services, do not staple longitudinal tabs. Instead, secure tabs with additional adhesive as recommended by insulation material manufacturer and seal with vapor4 barrier mastic and flashing sealant. B. Insulation Installation on Pipe Flanges: 1. Install preformed pipe insulation to outer diameter of pipe flange. 2. Make width of insulation section same as overall width of flange and bolts, plus twice the thickness of pipe insulation. 3. Fill voids between inner circumference of flange insulation and outer circumference of adjacent straight pipe segments with cut sections of cellular4glass block insulation of same thickness as pipe insulation. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 14 OF 18 JUNE 29, 2012 4. Install jacket material with manufacturer's recommended adhesive, overlap seams at least 1 inch (25 mm), and seal joints with flashing sealant. C. Insulation Installation on Pipe Fittings and Elbows: 1. Install preformed sections of same material as straight segments of pipe insulation when available. Secure according to manufacturer's written instructions. 2. When preformed sections of insulation are not available, install mitered sections of cellular4glass insulation. Secure insulation materials with wire or bands. D. Insulation Installation on Valves and Pipe Specialties: 1. Install preformed sections of cellular4glass insulation to valve body. 2. Arrange insulation to permit access to packing and to allow valve operation without disturbing insulation. 3. Install insulation to flanges as specified for flange insulation application. 3.7 INSTALLATION OF FLEXIBLE ELASTOMERIC INSULATION A. Seal longitudinal seams and end joints with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated. B. Insulation Installation on Pipe Flanges: 1. Install pipe insulation to outer diameter of pipe flange. 2. Make width of insulation section same as overall width of flange and bolts, plus twice the thickness of pipe insulation. 3. Fill voids between inner circumference of flange insulation and outer circumference of adjacent straight pipe segments with cut sections of sheet insulation of same thickness as pipe insulation. 4. Secure insulation to flanges and seal seams with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated. C. Insulation Installation on Pipe Fittings and Elbows: 1. Install mitered sections of pipe insulation. 2. Secure insulation materials and seal seams with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated. D. Insulation Installation on Valves and Pipe Specialties: 1. Install preformed valve covers manufactured of same material as pipe insulation when available. 2. When preformed valve covers are not available, install cut sections of pipe and sheet insulation to valve body. Arrange insulation to permit access to packing and to allow valve operation without disturbing insulation. 3. Install insulation to flanges as specified for flange insulation application. 4. Secure insulation to valves and specialties and seal seams with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 15 OF 18 JUNE 29, 2012 3.8 INSTALLATION OF MINERAL4FIBER INSULATION A. Insulation Installation on Straight Pipes and Tubes: 1. Secure each layer of preformed pipe insulation to pipe with wire or bands and tighten bands without deforming insulation materials. 2. Where vapor barriers are indicated, seal longitudinal seams, end joints, and protrusions with vapor4barrier mastic and joint sealant. 3. For insulation with factory4applied jackets on below4ambient surfaces, do not staple longitudinal tabs. Instead, secure tabs with additional adhesive as recommended by insulation material manufacturer and seal with vapor4 barrier mastic and flashing sealant. B. Insulation Installation on Pipe Flanges: 1. Install preformed pipe insulation to outer diameter of pipe flange. 2. Make width of insulation section same as overall width of flange and bolts, plus twice the thickness of pipe insulation. 3. Fill voids between inner circumference of flange insulation and outer circumference of adjacent straight pipe segments with mineral4fiber blanket insulation. 4. Install jacket material with manufacturer's recommended adhesive, overlap seams at least 1 inch (25 mm), and seal joints with flashing sealant. C. Insulation Installation on Pipe Fittings and Elbows: 1. Install preformed sections of same material as straight segments of pipe insulation when available. 2. When preformed insulation elbows and fittings are not available, install mitered sections of pipe insulation, to a thickness equal to adjoining pipe insulation. Secure insulation materials with wire or bands. D. Insulation Installation on Valves and Pipe Specialties: 1. Install preformed sections of same material as straight segments of pipe insulation when available. 2. When preformed sections are not available, install mitered sections of pipe insulation to valve body. 3. Arrange insulation to permit access to packing and to allow valve operation without disturbing insulation. 4. Install insulation to flanges as specified for flange insulation application. 3.9 FIELD4APPLIED JACKET INSTALLATION A. Where glass4cloth jackets are indicated, install directly over bare insulation or insulation with factory4applied jackets. 1. Draw jacket smooth and tight to surface with 24inch (504mm) overlap at seams and joints. 2. Embed glass cloth between two 0.0624inch4 (1.64mm4) thick coats of lagging adhesive. 3. Completely encapsulate insulation with coating, leaving no exposed insulation. B. Where FSK jackets are indicated, install as follows: BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 16 OF 18 JUNE 29, 2012 1. Draw jacket material smooth and tight. 2. Install lap or joint strips with same material as jacket. 3. Secure jacket to insulation with manufacturer's recommended adhesive. 4. Install jacket with 141/24inch (384mm) laps at longitudinal seams and 34 inch4 (754mm4) wide joint strips at end joints. 5. Seal openings, punctures, and breaks in vapor4retarder jackets and exposed insulation with vapor4barrier mastic. C. Where PVC jackets are indicated, install with 14inch (254mm) overlap at longitudinal seams and end joints; for horizontal applications. Seal with manufacturer's recommended adhesive. 1. Apply two continuous beads of adhesive to seams and joints, one bead under lap and the finish bead along seam and joint edge. D. Where metal jackets are indicated, install with 24inch (504mm) overlap at longitudinal seams and end joints. Overlap longitudinal seams arranged to shed water. Seal end joints with weatherproof sealant recommended by insulation manufacturer. Secure jacket with stainless4steel bands 12 inches (300 mm) o.c. and at end joints. 3.10 FINISHES A. Pipe Insulation with ASJ, Glass4Cloth, or Other Paintable Jacket Material: 1. Flat Acrylic Finish: Two finish coats over a primer that is compatible with jacket material and finish coat paint. Add fungicidal agent to render fabric mildew proof. a. Finish Coat Material: Interior, flat, latex4emulsion size. B. Flexible Elastomeric Thermal Insulation: After adhesive has fully cured, apply two coats of insulation manufacturer's recommended protective coating. C. Color: Final color as selected by Architect. Vary first and second coats to allow visual inspection of the completed Work. D. Do not field paint aluminum or stainless4steel jackets. 3.11 PIPING INSULATION SCHEDULE, GENERAL A. Acceptable preformed pipe and tubular insulation materials and thicknesses are identified for each piping system and pipe size range. If more than one material is listed for a piping system, selection from materials listed is Contractor's option. B. Items Not Insulated: Unless otherwise indicated, do not install insulation on the following: 1. Drainage piping located in crawl spaces. 2. Underground piping. 3. Chrome4plated pipes and fittings unless there is a potential for personnel injury. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 17 OF 18 JUNE 29, 2012 3.12 INDOOR PIPING INSULATION SCHEDULE A. Condensate and Equipment Drain Water below 60 Deg F (16 Deg C): 1. All Pipe Sizes: Insulation shall be one of the following: a. Cellular Glass: 141/2 inches (38 mm) thick. b. Flexible Elastomeric: 3/4 inch (19 mm) thick. c. Mineral4Fiber, Preformed Pipe Insulation, Type I: 1/2 inch (13 mm) thick. B. Chilled Water, 40 Deg F (5 Deg C) and below: 1. NPS 3 (DN 80) and Smaller: Insulation shall be one of the following: a. Cellular Glass: 2 inches (50 mm) thick. 2. NPS 4 (DN 100) to NPS 12 (DN 300): Insulation shall be one of the following: a. Cellular Glass: 2 inches (50 mm) thick. b. Mineral4Fiber, Preformed Pipe, Type I, 2 inches (50 mm) thick. C. Chilled Water above 40 Deg F (5 Deg C): 1. NPS 12 (DN 300) and Smaller: Insulation shall be one of the following: a. Cellular Glass: 141/2 inches (38 mm) thick. b. Flexible Elastomeric: 1 inch (25 mm) thick. c. Mineral4Fiber, Preformed Pipe, Type I: 141/2 inches (38 mm) thick. D. Refrigerant Suction and Liquid Piping: 1. All Pipe Sizes: Insulation shall be one of the following: a. Cellular Glass: 141/2 inches (38 mm) thick. b. Flexible Elastomeric: 1 inch (25 mm) thick. c. Mineral4Fiber, Preformed Pipe Insulation, Type I: 1 inch (25 mm) thick. E. Refrigerant Suction and Liquid Flexible Tubing: 1. All Pipe Sizes: Insulation shall be the following: a. Flexible Elastomeric: 1 inch (25 mm) thick. 3.13 OUTDOOR, ABOVEGROUND PIPING INSULATION SCHEDULE A. Chilled Water: 1. All Pipe Sizes: Insulation shall be one of the following: a. Cellular Glass: 3 inches (75 mm) thick. b. Flexible Elastomeric: 3 inches (75 mm) thick. c. Mineral4Fiber, Preformed Pipe Insulation, Type I: 3 inches (75 mm) thick. B. Refrigerant Suction and Liquid Piping: 1. All Pipe Sizes: Insulation shall be one of the following: a. Cellular Glass: 2 inches (50 mm) thick. b. Flexible Elastomeric: 2 inches (50 mm) thick. c. Mineral4Fiber, Preformed Pipe Insulation, Type I: 2 inches (50 mm) thick. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HVAC PIPING INSULATION STANDARD SPECIFICATIONS 23 07 19 – PAGE 18 OF 18 JUNE 29, 2012 C. Refrigerant Suction and Liquid Flexible Tubing: 1. All Pipe Sizes: Insulation shall be the following: a. Flexible Elastomeric: 2 inches (50 mm) thick. 3.14 INDOOR, FIELD4APPLIED JACKET SCHEDULE A. Install jacket over insulation material. For insulation with factory4applied jacket, install the field4applied jacket over the factory4applied jacket. B. If more than one material is listed, selection from materials listed is Contractor's option. C. Piping, Concealed: 1. PVC: 20 mils (0.5 mm) thick. 2. Aluminum, Smooth: 0.020 inch (0.51 mm) thick. D. Piping, Exposed: 1. PVC: 20 mils (0.5 mm) thick. 3.15 OUTDOOR, FIELD4APPLIED JACKET SCHEDULE A. Install jacket over insulation material. For insulation with factory4applied jacket, install the field4applied jacket over the factory4applied jacket. B. If more than one material is listed, selection from materials listed is Contractor's option. C. Piping, Concealed: 1. PVC: 30 mils (0.8 mm) thick. 2. Aluminum, Smooth: 0.032 inch (0.81 mm) thick. D. Piping, Exposed: 1. PVC: 30 mils (0.8 mm) thick. 2. Painted Aluminum, Smooth with Z4Shaped Locking Seam: 0.032 inch (0.81 mm) thick. END OF SECTION 230719 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HYDRONIC PIPING STANDARD SPECIFICATIONS 23 21 13 – PAGE 1 OF 7 JUNE 29, 2012 SECTION 232113 HYDRONIC PIPING PART 1 GENERAL 1.1 DEFINITIONS A. MSS: Manufacturer’s Standardization Society of the Valve and Fitting Industry. B. DWV: Drain, Waste and Vent C. PTFE: Polytetrafluoroethylene. 1.2 SUBMITTALS A. Product Data: Provide for each type of the following: 1. Copper Pipe 2. Steel Pipe 1.3 QUALITY ASSURANCE A. Installer Qualifications: 1. Installers of Pressure8Sealed Joints: Installers shall be certified by the pressure8seal joint manufacturer as having been trained and qualified to join piping with pressure8seal pipe couplings and fittings. B. Steel Support Welding: Qualify processes and operators according to AWS D1.1/D1.1M, "Structural Welding Code 8 Steel." C. Welding: Qualify processes and operators according to ASME Boiler and Pressure Vessel Code: Section IX. 1. Comply with provisions in ASME B31 Series, "Code for Pressure Piping." 2. Certify that each welder has passed AWS qualification tests for welding processes involved and that certification is current. PART 2 PRODUCTS 2.1 COPPER TUBE AND FITTINGS A. Drawn8Temper Copper Tubing: ASTM B 88, Type L B. Wrought8Copper Fittings: ASME B16.22. 1. Grooved8End Copper Fittings: ASTM B 75 (ASTM B 75M), copper tube or ASTM B 584, bronze casting. 2. Grooved8End8Tube Couplings: Rigid pattern, unless otherwise indicated; gasketed fitting. Ductile8iron housing with keys matching pipe and fitting grooves, prelubricated EPDM gasket rated for minimum 230 deg F (110 deg C) for use with housing, and steel bolts and nuts. C. Copper or Bronze Pressure8Seal Fittings: BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HYDRONIC PIPING STANDARD SPECIFICATIONS 23 21 13 – PAGE 2 OF 7 JUNE 29, 2012 1. Housing: Copper. 2. O8Rings and Pipe Stops: EPDM. 3. Tools: Manufacturer's special tools. 4. Minimum 2008psig (13798kPa) working8pressure rating at 250 deg F (121 deg C). D. Wrought8Copper Unions: ASME B16.22. 2.2 STEEL PIPE AND FITTINGS A. Steel Pipe: ASTM A 53/A 53M, black steel with plain ends; type, grade, and wall thickness as indicated in Part 3 "Piping Applications" Article. B. Wrought8Steel Fittings: ASTM A 234/A 234M, wall thickness to match adjoining pipe. C. Wrought Cast8 and Forged8Steel Flanges and Flanged Fittings: ASME B16.5, including bolts, nuts, and gaskets of the following material group, end connections, and facings: 1. Material Group: 1.1. 2. End Connections: Butt welding. 3. Facings: Raised face. D. Steel Pipe Nipples: ASTM A 733, made of same materials and wall thicknesses as pipe in which they are installed. 2.3 JOINING MATERIALS A. Pipe8Flange Gasket Materials: Suitable for chemical and thermal conditions of piping system contents. 1. ASME B16.21, nonmetallic, flat, asbestos free, 1/88inch (3.28mm) maximum thickness unless thickness or specific material is indicated. a. Full8Face Type: For flat8face, Class 125, cast8iron and cast8bronze flanges. b. Narrow8Face Type: For raised8face, Class 250, cast8iron and steel flanges. B. Flange Bolts and Nuts: ASME B18.2.1, carbon steel, unless otherwise indicated. C. Solder Filler Metals: ASTM B 32, lead8free alloys. Include water8flushable flux according to ASTM B 813. D. Brazing Filler Metals: AWS A5.8, BCuP Series, copper8phosphorus alloys for joining copper with copper; or BAg81, silver alloy for joining copper with bronze or steel. E. Welding Filler Metals: Comply with AWS D10.12/D10.12M for welding materials appropriate for wall thickness and chemical analysis of steel pipe being welded. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HYDRONIC PIPING STANDARD SPECIFICATIONS 23 21 13 – PAGE 3 OF 7 JUNE 29, 2012 F. Gasket Material: Thickness, material, and type suitable for fluid to be handled and working temperatures and pressures. 2.4 DIELECTRIC FITTINGS A. General Requirements: Assembly of copper alloy and ferrous materials with separating nonconductive insulating material. Include end connections compatible with pipes to be joined. B. Dielectric Unions: 1. Description: a. Standard: ASSE 1079. b. Pressure Rating: 150 psig (1035 kPa). c. End Connections: Solder8joint copper alloy and threaded ferrous. C. Dielectric Flanges: 1. Description: a. Standard: ASSE 1079. b. Factory8fabricated, bolted, companion8flange assembly. c. Pressure Rating: Minimum at 180 deg F (82 deg C), 150 psig (1035 kPa). d. End Connections: Solder8joint copper alloy and threaded ferrous; threaded solder8joint copper alloy and threaded ferrous. D. Dielectric8Flange Insulating Kits: 1. Description: a. Nonconducting materials for field assembly of companion flanges. b. Pressure Rating: 150 psig (1035 kPa). c. Gasket: Neoprene or phenolic. d. Bolt Sleeves: Phenolic or polyethylene. e. Washers: Phenolic with steel backing washers. E. Dielectric Nipples: 1. Description: a. Standard: IAPMO PS 66 b. Electroplated steel nipple. complying with ASTM F 1545. c. Pressure Rating: 300 psig (2070 kPa) at 225 deg F (107 deg C). d. End Connections: Male threaded or grooved. e. Lining: Inert and noncorrosive, propylene. 2.5 VALVES A. Automatic Flow8Control Valves: 1. Basis8of8Design Product: a. Flow Design Inc. b. Griswold Controls. 2. Body: Brass or ferrous metal. 3. Piston and Spring Assembly: Stainless steel, tamper proof, self cleaning, and removable. 4. Combination Assemblies: Include bonze or brass8alloy ball valve. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HYDRONIC PIPING STANDARD SPECIFICATIONS 23 21 13 – PAGE 4 OF 7 JUNE 29, 2012 5. Identification Tag: Marked with zone identification, valve number, and flow rate. 6. Size: Same as pipe in which installed. 7. Performance: Maintain constant flow, plus or minus 5 percent over system pressure fluctuations. 8. Minimum CWP Rating: 175 psig (1207 kPa). 9. Maximum Operating Temperature: 200 deg F (93 deg C). PART 3 EXECUTION 3.1 PIPING APPLICATIONS A. Chilled8water piping, aboveground, NPS 2 (DN 50) and smaller, shall be the following: 1. Type L, drawn8temper copper tubing, wrought8copper fittings, and soldered brazed or pressure8seal joints. B. Chilled8water piping, aboveground, NPS 281/2 (DN 65) and larger, shall be the following: 1. Schedule 40 steel pipe, wrought8steel fittings and wrought8cast or forged8 steel flanges and flange fittings, and welded and flanged joints. 2. RTRP and RTRF with adhesive or flanged joints. C. Glycol cooling8water piping, aboveground, NPS 2 (DN 50) and smaller, shall be the following: 1. Type L, drawn8temper copper tubing, wrought8copper fittings, and soldered brazed or pressure8seal joints. D. Glycol cooling8water piping, aboveground, NPS 281/2 (DN 65) and larger, shall be the following: 1. Schedule 40 steel pipe, wrought8steel fittings and wrought8cast or forged8 steel flanges and flange fittings, and welded and flanged joints. E. Condensate8Drain Piping: Type M, drawn8temper copper tubing, wrought8 copper fittings, and soldered joints. 3.2 PIPING INSTALLATIONS A. Drawing plans, schematics, and diagrams indicate general location and arrangement of piping systems. Indicate piping locations and arrangements if such were used to size pipe and calculate friction loss, expansion, pump sizing, and other design considerations. Install piping as indicated unless deviations to layout are approved on Coordination Drawings. B. Install piping in concealed locations, unless otherwise indicated and except in equipment rooms and service areas. C. Install piping indicated to be exposed and piping in equipment rooms and service areas at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HYDRONIC PIPING STANDARD SPECIFICATIONS 23 21 13 – PAGE 5 OF 7 JUNE 29, 2012 D. Install piping above accessible ceilings to allow sufficient space for ceiling panel removal. E. Install piping to permit valve servicing. F. Install piping at indicated slopes. G. Install piping free of sags and bends. H. Install fittings for changes in direction and branch connections. I. Install piping to allow application of insulation. J. Select system components with pressure rating equal to or greater than system operating pressure. K. Install groups of pipes parallel to each other, spaced to permit applying insulation and servicing of valves. L. Install drains, consisting of a tee fitting, NPS 3/4 (DN 20) ball valve, and short NPS 3/4 (DN 20) threaded nipple with cap, at low points in piping system mains and elsewhere as required for system drainage. M. Install piping at a uniform grade of 0.2 percent upward in direction of flow. N. Reduce pipe sizes using eccentric reducer fitting installed with level side up. O. Install branch connections to mains using mechanically formed tee fittings in main pipe, with the branch connected to the bottom of the main pipe. For up8 feed risers, connect the branch to the top of the main pipe. P. Install unions in piping, NPS 2 (DN 50) and smaller, adjacent to valves, at final connections of equipment, and elsewhere as indicated. Q. Install flanges in piping, NPS 281/2 (DN 65) and larger, at final connections of equipment and elsewhere as indicated. 3.3 HANGERS AND SUPPORTS A. Install the following pipe attachments: 1. Adjustable steel clevis hangers for individual horizontal piping less than 20 feet (6 m) long. 2. Adjustable roller hangers and spring hangers for individual horizontal piping 20 feet (6 m) or longer. 3. Pipe Roller: MSS SP858, Type 44 for multiple horizontal piping 20 feet (6 m) or longer, supported on a trapeze. 4. Spring hangers to support vertical runs. 5. Provide copper8clad hangers and supports for hangers and supports in direct contact with copper pipe. B. Install hangers for steel piping with the following maximum spacing and minimum rod sizes: BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HYDRONIC PIPING STANDARD SPECIFICATIONS 23 21 13 – PAGE 6 OF 7 JUNE 29, 2012 HANGERS MAXIMUM SPAN MINIMUM ROD SIZE NPS 281/2 11 feet 3/8 inch NPS 3 12 feet 3/8 inch C. Install hangers for drawn8temper copper piping with the following maximum spacing and minimum rod sizes: HANGERS MAXIMUM SPAN MINIMUM ROD SIZE NPS ¾ 5 feet ¼ inch NPS 1 6 feet ¼ inch NPS 181/2 8 feet 3/8 inch NPS 2 8 feet 3/8 inch 3.4 PIPE JOINT CONSTRUCTION A. Join pipe and fittings according to the following requirements and Division 23 Sections specifying piping systems. B. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe. C. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before assembly. D. Soldered Joints: Apply ASTM B 813, water8flushable flux, unless otherwise indicated, to tube end. Construct joints according to ASTM B 828 or CDA's "Copper Tube Handbook," using lead8free solder alloy complying with ASTM B 32. E. Brazed Joints: Construct joints according to AWS's "Brazing Handbook," "Pipe and Tube" Chapter, using copper8phosphorus brazing filler metal complying with AWS A5.8. F. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows: 1. Apply appropriate tape or thread compound to external pipe threads unless dry seal threading is specified. 2. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged. Do not use pipe sections that have cracked or open welds. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HYDRONIC PIPING STANDARD SPECIFICATIONS 23 21 13 – PAGE 7 OF 7 JUNE 29, 2012 G. Welded Joints: Construct joints according to AWS D10.12/D10.12M, using qualified processes and welding operators according to Part 1 "Quality Assurance" Article. H. Flanged Joints: Select appropriate gasket material, size, type, and thickness for service application. Install gasket concentrically positioned. Use suitable lubricants on bolt threads. I. Pressure8Sealed Joints: Use manufacturer8recommended tool and procedure. Leave insertion marks on pipe after assembly. 3.5 FIELD QUALITY CONTROL A. Prepare hydronic piping according to ASME B31.9 and as follows: 1. Leave joints, including welds, uninsulated and exposed for examination during test. 2. Flush hydronic piping systems with clean water; then remove and clean or replace strainer screens. 3. Isolate equipment from piping. If a valve is used to isolate equipment, its closure shall be capable of sealing against test pressure without damage to valve. Install blinds in flanged joints to isolate equipment. 4. Install safety valve, set at a pressure no more than one8third higher than test pressure, to protect against damage by expanding liquid or other source of overpressure during test. B. Perform the following tests on hydronic piping: 1. Use ambient temperature water as a testing medium unless there is risk of damage due to freezing. Another liquid that is safe for workers and compatible with piping may be used. 2. While filling system, use vents installed at high points of system to release air. Use drains installed at low points for complete draining of test liquid. 3. Subject piping system to hydrostatic test pressure that is not less than 1.5 times the system's working pressure. Test pressure shall not exceed maximum pressure for any vessel, pump, valve, or other component in system under test. Verify that stress due to pressure at bottom of vertical runs does not exceed 90 percent of specified minimum yield strength or 1.7 times "SE" value in Appendix A in ASME B31.9, "Building Services Piping." 4. After hydrostatic test pressure has been applied for at least 10 minutes, examine piping, joints, and connections for leakage. Eliminate leaks by tightening, repairing, or replacing components, and repeat hydrostatic test until there are no leaks. 5. Prepare written report of testing. END OF SECTION 232113 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HYDRONIC PUMPS STANDARD SPECIFICATIONS 23 21 23 – PAGE 1 OF 4 JUNE 29, 2012, 2012 SECTION 232123 HYDRONIC PUMPS PART 1 GENERAL 1.1 DEFINITIONS A. Buna"N: Nitrile rubber. B. EPT: Ethylene propylene terpolymer. 1.2 ACTION SUBMITTALS A. Product Data: For each type of pump. Include certified performance curves and rated capacities, operating characteristics, furnished specialties, final impeller dimensions, and accessories for each type of product indicated. Indicate pump's operating point on curves. PART 2 PRODUCTS 2.1 CLOSE"COUPLED, IN"LINE CENTRIFUGAL PUMPS A. Basis"of"Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following: 1. Armstrong Pumps Inc. 2. Grundfos Pumps Corporation. 3. ITT Corporation; Bell & Gossett. 4. Patterson Pump Co. B. Description: Factory"assembled and "tested, centrifugal, overhung"impeller, close"coupled, in"line pump as defined in HI 1.1"1.2 and HI 1.3; designed for installation with pump and motor shafts mounted horizontally or vertically. C. Pump Construction: 1. Casing: Radially split, cast iron, with threaded gage tappings at inlet and outlet, replaceable bronze wear rings, and threaded companion"flange connections. 2. Impeller: 30% glass filled noryl. 3. Pump Shaft: Steel, with copper"alloy shaft sleeve. 4. Seal: Mechanical seal consisting of carbon rotating ring against a ceramic seat held by a stainless"steel spring. 5. Pump Bearings: Permanently lubricated ball bearings. D. Motor: Single speed and rigidly mounted to pump casing. 1. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HYDRONIC PUMPS STANDARD SPECIFICATIONS 23 21 23 – PAGE 2 OF 4 JUNE 29, 2012, 2012 2. Comply with NEMA designation, temperature rating, service factor, and efficiency requirements for motors specified in Division 23 Section "Common Motor Requirements for HVAC Equipment." a. Enclosure: Open, dripproof. 2.2 ELECTRONICALLY COMMUTATED PUMPS A. Basis"of"Design Product: Subject to compliance with requirements, provide product indicated on Drawings > or comparable product by one of the following: 1. Armstrong Pumps Inc. 2. ITT Corporation; Bell & Gossett. 3. Patterson Pump Co. B. Description: Factory"assembled and "tested, with a proportional pressure control, which automatically adjusts the pump performance continuously and automatically to the requirements of the system. C. Pump Construction: 1. Body: Cast Iron 2. O"ring: EPRM 3. Impeller: Nylon/PPO 4. Pump Bearings: Carbon/alumina ceramic. D. Motor: Shaft"less spherical electronically commutated, permanent magnet motor (ECM/PMM). 1. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 2. Comply with NEMA designation, temperature rating, service factor, and efficiency requirements for motors specified in Division 23 Section "Common Motor Requirements for HVAC Equipment." PART 3 EXECUTION 3.1 EXAMINATION A. Examine equipment foundations and anchor"bolt locations for compliance with requirements for installation tolerances and other conditions affecting performance of the Work. B. Examine roughing"in for piping systems to verify actual locations of piping connections before pump installation. C. Examine foundations and inertia bases for suitable conditions where pumps are to be installed. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HYDRONIC PUMPS STANDARD SPECIFICATIONS 23 21 23 – PAGE 3 OF 4 JUNE 29, 2012, 2012 D. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 PUMP INSTALLATION A. Install pumps to provide access for periodic maintenance including removing motors, impellers, couplings, and accessories. B. Independently support pumps and piping so weight of piping is not supported by pumps and weight of pumps is not supported by piping. C. Equipment Mounting: Install in"line pumps with continuous"thread hanger rods and elastomeric hangers of size required to support weight of in"line pumps. 3.3 ALIGNMENT A. Engage a factory"authorized service representative to perform alignment service. B. Comply with requirements in Hydronics Institute standards for alignment of pump and motor shaft. Add shims to the motor feet and bolt motor to base frame. Do not use grout between motor feet and base frame. C. Comply with pump and coupling manufacturers' written instructions. D. After alignment is correct, tighten foundation bolts evenly but not too firmly. Completely fill baseplate with nonshrink, nonmetallic grout while metal blocks and shims or wedges are in place. After grout has cured, fully tighten foundation bolts. 3.4 CONNECTIONS A. Where installing piping adjacent to pump, allow space for service and maintenance. B. Connect piping to pumps. Install valves that are same size as piping connected to pumps. C. Install suction and discharge pipe sizes equal to or greater than diameter of pump nozzles. D. Install pressure gages on pump suction and discharge or at integral pressure" gage tapping, or install single gage with multiple"input selector valve. E. Connect wiring according to Division 26 Section "Low"Voltage Electrical Power Conductors and Cables." BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP HYDRONIC PUMPS STANDARD SPECIFICATIONS 23 21 23 – PAGE 4 OF 4 JUNE 29, 2012, 2012 3.5 STARTUP SERVICE A. Engage a factory"authorized service representative to perform startup service. 1. Complete installation and startup checks according to manufacturer's written instructions. 2. Check piping connections for tightness. 3. Clean strainers on suction piping. 4. Perform the following startup checks for each pump before starting: a. Verify bearing lubrication. b. Verify that pump is free to rotate by hand and that pump for handling hot liquid is free to rotate with pump hot and cold. If pump is bound or drags, do not operate until cause of trouble is determined and corrected. c. Verify that pump is rotating in the correct direction. 5. Start motor. 6. Open discharge valve slowly. END OF SECTION 232123 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP REFRIGERANT PIPING STANDARD SPECIFICATIONS 23 23 00 – PAGE 1 OF 4 JUNE 29, 2012 SECTION 232300 REFRIGERANT PIPING PART 1 GENERAL 1.1 SUBMITTALS A. Product Data: Provide for each type of valve and refrigerant piping specialty indicated. Include pressure drop, based on manufacturer's test data, for the following: 1. Copper tube. 1.2 QUALITY ASSURANCE A. Welding: Qualify procedures and personnel according to ASME Boiler and Pressure Vessel Code: Section IX, "Welding and Brazing Qualifications." B. Comply with ASHRAE 15, "Safety Code for Refrigeration Systems." C. Comply with ASME B31.5, "Refrigeration Piping and Heat Transfer Components." 1.3 PRODUCT STORAGE AND HANDLING A. Store piping in a clean and protected area with end caps in place to ensure that piping interior and exterior are clean when installed. 1.4 COORDINATION A. Coordinate size and location of roof curbs, equipment supports, and roof penetrations. PART 2 PRODUCTS 2.1 PERFORMANCE REQUIREMENTS A. Line Test Pressure for Refrigerant R?410A: 1. Suction Lines for Air?Conditioning Applications: 300 psig (2068 kPa). 2. Suction Lines for Heat?Pump Applications: 535 psig (3689 kPa). 3. Liquid Lines: 535 psig (3689 kPa). 2.2 REFRIGERANTS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Atofina Chemicals, Inc. 2. DuPont Company; Fluorochemicals Div. 3. Honeywell, Inc.; Genetron Refrigerants. 4. INEOS Fluor Americas LLC. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP REFRIGERANT PIPING STANDARD SPECIFICATIONS 23 23 00 – PAGE 2 OF 4 JUNE 29, 2012 B. ASHRAE 34, R?410A: Pentafluoroethane/Difluoromethane. 2.3 COPPER TUBE AND FITTINGS A. Copper Tube: ASTM B 280, Type ACR. B. Wrought?Copper Fittings: ASME B16.22. C. Wrought?Copper Unions: ASME B16.22. D. Brazing Filler Metals: AWS A5.8. E. Flexible Connectors: 1. Body: Tin?bronze bellows with woven, flexible, tinned?bronze?wire? reinforced protective jacket. 2. End Connections: Socket ends. 3. Offset Performance: Capable of minimum 3/4?inch (20?mm) misalignment in minimum 7?inch? (180?mm?) long assembly. 4. Pressure Rating: Factory test at minimum 500 psig (3450 kPa). 5. Maximum Operating Temperature: 250 deg F (121 deg C). PART 3 EXECUTION 3.1 PIPING APPLICATIONS FOR REFRIGERANT R?410A A. Suction Lines NPS 1?1/2 (DN 40) and Smaller Copper, Type ACR, annealed?temper tubing and wrought?copper fittings with brazed joints. B. Liquid Lines Copper, Type ACR, annealed? or drawn?temper tubing and wrought?copper fittings with brazed joints. 3.2 PIPING INSTALLATION A. Drawing plans, schematics, and diagrams indicate general location and arrangement of piping systems; indicated locations and arrangements were used to size pipe and calculate friction loss, expansion, pump sizing, and other design considerations. Install piping as indicated unless deviations to layout are approved on Shop Drawings. B. Install refrigerant piping according to ASHRAE 15. C. Install piping in concealed locations unless otherwise indicated and except in equipment rooms and service areas. D. Install piping indicated to be exposed and piping in equipment rooms and service areas at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise. E. Install piping above accessible ceilings to allow sufficient space for ceiling panel removal. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP REFRIGERANT PIPING STANDARD SPECIFICATIONS 23 23 00 – PAGE 3 OF 4 JUNE 29, 2012 F. Install piping adjacent to machines to allow service and maintenance. G. Install piping free of sags and bends. H. Install fittings for changes in direction and branch connections. I. Select system components with pressure rating equal to or greater than system operating pressure. J. Install piping as short and direct as possible, with a minimum number of joints, elbows, and fittings. K. Arrange piping to allow inspection and service of refrigeration equipment. Install valves and specialties in accessible locations to allow for service and inspection. Install access doors or panels if valves or equipment requiring maintenance is concealed behind finished surfaces. L. Install refrigerant piping in protective conduit where installed belowground. M. Install refrigerant piping in rigid or flexible conduit in locations where exposed to mechanical injury. N. Slope refrigerant piping as follows: 1. Install horizontal suction lines with a uniform slope downward to compressor. 2. Install traps and double risers to entrain oil in vertical runs. 3. Liquid lines may be installed level. O. Install piping with adequate clearance between pipe and adjacent walls and hangers or between pipes for insulation installation. P. Install sleeves for piping penetrations of walls, ceilings, and floors. Q. Install sleeve seals for piping penetrations of concrete walls and slabs. 3.3 HANGERS AND SUPPORTS A. Install the following pipe attachments: 1. Adjustable steel clevis hangers for individual horizontal runs less than 20 feet (6 m) long. 2. Roller hangers and spring hangers for individual horizontal runs 20 feet (6 m) or longer. 3. Pipe Roller: MSS SP?58, Type 44 for multiple horizontal piping 20 feet (6 m) or longer, supported on a trapeze. 4. Spring hangers to support vertical runs. B. Install hangers for copper tubing with the following maximum spacing and minimum rod sizes: 1. NPS 1/2 (DN 15): Maximum span, 60 inches (1500 mm); minimum rod size, 1/4 inch (6.4 mm). BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP REFRIGERANT PIPING STANDARD SPECIFICATIONS 23 23 00 – PAGE 4 OF 4 JUNE 29, 2012 2. NPS 5/8 (DN 18): Maximum span, 60 inches (1500 mm); minimum rod size, 1/4 inch (6.4 mm). 3. NPS 1 (DN 25): Maximum span, 72 inches (1800 mm); minimum rod size, 1/4 inch (6.4 mm). C. Support multifloor vertical runs at least at each floor. 3.4 FIELD QUALITY CONTROL A. Perform tests and inspections and prepare test reports. B. Tests and Inspections: 1. Comply with ASME B31.5, Chapter VI. 2. Test refrigerant piping, specialties, and receivers. Isolate compressor, condenser, evaporator, and safety devices from test pressure if they are not rated above the test pressure. 3. Test high? and low?pressure side piping of each system separately at not less than the pressures indicated in Part 1 "Performance Requirements" Article. a. Fill system with nitrogen to the required test pressure. b. System shall maintain test pressure at the manifold gage throughout duration of test. c. Test joints and fittings with electronic leak detector or by brushing a small amount of soap and glycerin solution over joints. d. Remake leaking joints using new materials, and retest until satisfactory results are achieved. 3.5 SYSTEM CHARGING A. Charge system per manufacturer’s written instructions END OF SECTION 23 23 00 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP METAL DUCTS STANDARD SPECIFICATIONS 23 31 13 – PAGE 1 OF 14 JUNE 29, 2012 SECTION 233113 METAL DUCTS PART 1 GENERAL 1.1 SUBMITTALS A. Product Data: Provide for each type of the following products: 1. Liners and adhesives. 2. Sealants and gaskets. B. Provide Shop Drawings as Follows: 1. Fabrication, assembly, and installation, including plans, elevations, sections, components, and attachments to other work. 2. Factory5 and shop5fabricated ducts and fittings. 3. Duct layout indicating sizes, configuration, liner material, and static5 pressure classes. 4. Elevation of top of ducts. 5. Fittings. 6. Seam and joint construction. 7. Penetrations through fire5rated and other partitions. 8. Equipment installation based on equipment being used on Project. 9. Locations for duct accessories, including dampers, turning vanes, and access doors and panels. 10. Hangers and supports, including methods for duct and building attachment and vibration isolation. C. Field quality5control reports. 1.2 QUALITY ASSURANCE A. Welding Qualifications: Qualify procedures and personnel according to [AWS D1.1/D1.1M, "Structural Welding Code 5 Steel," for hangers and supports.] [AWS D1.2/D1.2M, "Structural Welding Code 5 Aluminum," for aluminum supports.] [AWS D9.1M/D9.1, "Sheet Metal W elding Code," for duct joint and seam welding.] B. Welding Qualifications: Qualify procedures and personnel according to the following: 1. AWS D1.1/D1.1M, "Structural Welding Code 5 Steel," for hangers and supports. 2. AWS D1.2/D1.2M, "Structural Welding Code 5 Aluminum," for aluminum supports. 3. AWS D9.1M/D9.1, "Sheet Metal Welding Code," for duct joint and seam welding. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP METAL DUCTS STANDARD SPECIFICATIONS 23 31 13 – PAGE 2 OF 14 JUNE 29, 2012 C. ASHRAE Compliance: Applicable requirements in ASHRAE 62.1, Section 5 5 "Systems and Equipment" and Section 7 5 "Construction and System Start5 Up." D. ASHRAE/IESNA Compliance: Applicable requirements in ASHRAE/IESNA 90.1, Section 6.4.4 5 "HVAC System Construction and Insulation." PART 2 PRODUCTS 2.1 PERFORMANCE REQUIREMENTS A. Structural Performance: Duct hangers and supports shall withstand the effects of gravity loads and stresses within limits and under conditions described in SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible". B. Airstream Surfaces: Surfaces in contact with the airstream shall comply with requirements in ASHRAE 62.1. 2.2 SINGLE5WALL RECTANGULAR DUCTS AND FITTINGS A. General Fabrication Requirements: Comply with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible" based on indicated static5 pressure class unless otherwise indicated. B. Transverse Joints: Select joint types and fabricate according to SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Figure 251, "Rectangular Duct/Transverse Joints," for static5pressure class, applicable sealing requirements, materials involved, duct5support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible." C. Longitudinal Seams: Select seam types and fabricate according to SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Figure 252, "Rectangular Duct/Longitudinal Seams," for static5pressure class, applicable sealing requirements, materials involved, duct5support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible." D. Elbows, Transitions, Offsets, Branch Connections, and Other Duct Construction: Select types and fabricate according to SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Chapter 4, "Fittings and Other Construction," for static5pressure class, applicable sealing requirements, materials involved, duct5support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible." E. Longitudinal Seams: Select seam types and fabricate according to SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Figure 252, "Rectangular Duct/Longitudinal Seams," for static5pressure class, applicable sealing requirements, materials involved, duct5support intervals, BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP METAL DUCTS STANDARD SPECIFICATIONS 23 31 13 – PAGE 3 OF 14 JUNE 29, 2012 and other provisions in SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible." 2.3 SINGLE5WALL ROUND[ AND FLAT5OVAL] DUCTS AND FITTINGS A. General Fabrication Requirements: Comply with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Chapter 3, "Round, Oval, and Flexible Duct," based on indicated static5pressure class unless otherwise indicated. 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. Lindab Inc. b. McGill AirFlow LLC. c. SEMCO Incorporated. d. Sheet Metal Connectors, Inc. e. Spiral Manufacturing Co., Inc. B. Flat5Oval Ducts: Indicated dimensions are the duct width (major dimension) and diameter of the round sides connecting the flat portions of the duct (minor dimension). C. Transverse Joints: Select joint types and fabricate according to SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Figure 351, "Round Duct Transverse Joints," for static5pressure class, applicable sealing requirements, materials involved, duct5support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible." D. Longitudinal Seams: Select seam types and fabricate according to SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Figure 352, "Round Duct Longitudinal Seams," for static5pressure class, applicable sealing requirements, materials involved, duct5support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible." E. Tees and Laterals: Select types and fabricate according to SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Figure 355, "90 Degree Tees and Laterals," and Figure 356, "Conical Tees," for static5 pressure class, applicable sealing requirements, materials involved, duct5 support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible." 2.4 SHEET METAL MATERIALS A. General Material Requirements: Comply with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible" for acceptable materials, material thicknesses, and duct construction methods unless otherwise indicated. Sheet metal materials shall be free of pitting, seam marks, roller marks, stains, discolorations, and other imperfections. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP METAL DUCTS STANDARD SPECIFICATIONS 23 31 13 – PAGE 4 OF 14 JUNE 29, 2012 B. Galvanized Sheet Steel: Comply with ASTM A 653/A 653M. 1. Galvanized Coating Designation: G60. 2. Finishes for Surfaces Exposed to View: Mill phosphatized. C. Tie Rods: Galvanized steel, 1/45inch (65mm) minimum diameter for lengths 36 inches (900 mm) or less; 3/85inch (105mm) minimum diameter for lengths longer than 36 inches (900 mm). 2.5 DUCT LINER A. Fibrous5Glass Duct Liner: Comply with ASTM C 1071, NFPA 90A, or NFPA 90B; and with NAIMA AH124, "Fibrous Glass Duct Liner Standard." 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. CertainTeed Corporation; Insulation Group. b. Johns Manville. c. Knauf Insulation. d. Owens Corning. e. Maximum Thermal Conductivity: 1) Type I, Flexible: 0.27 Btu x in./h x sq. ft. x deg F (0.039 W/m x K) at 75 deg F (24 deg C) mean temperature. 2) Type II, Rigid: 0.23 Btu x in./h x sq. ft. x deg F (0.033 W/m x K) at 75 deg F (24 deg C) mean temperature. 2. Antimicrobial Erosion5Resistant Coating: Apply to the surface of the liner that will form the interior surface of the duct to act as a moisture repellent and erosion5resistant coating. Antimicrobial compound shall be tested for efficacy by an NRTL and registered by the EPA for use in HVAC systems. 3. Water5Based Liner Adhesive: Comply with NFPA 90A or NFPA 90B and with ASTM C 916. a. For indoor applications, use adhesive that has a VOC content of 80 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24). b. Adhesive shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small5Scale Environmental Chambers." B. Shop Application of Duct Liner: Comply with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Figure 7511, "Flexible Duct Liner Installation." 1. Adhere a single layer of indicated thickness of duct liner with at least 90 percent adhesive coverage at liner contact surface area. Attaining indicated thickness with multiple layers of duct liner is prohibited. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP METAL DUCTS STANDARD SPECIFICATIONS 23 31 13 – PAGE 5 OF 14 JUNE 29, 2012 2. Apply adhesive to transverse edges of liner facing upstream that do not receive metal nosing. 3. Butt transverse joints without gaps, and coat joint with adhesive. 4. Fold and compress liner in corners of rectangular ducts or cut and fit to ensure butted5edge overlapping. 5. Do not apply liner in rectangular ducts with longitudinal joints, except at corners of ducts, unless duct size and dimensions of standard liner make longitudinal joints necessary. 6. Secure liner with mechanical fasteners 4 inches (100 mm) from corners and at intervals not exceeding 12 inches (300 mm) transversely; at 3 inches (75 mm) from transverse joints and at intervals not exceeding 18 inches (450 mm) longitudinally. 2.6 SEALANT AND GASKETS A. General Sealant and Gasket Requirements: Surface5burning characteristics for sealants and gaskets shall be a maximum flame5spread index of 25 and a maximum smoke5developed index of 50 when tested according to UL 723; certified by an NRTL. B. Water5Based Joint and Seam Sealant: 1. Application Method: Brush on. 2. Solids Content: Minimum 65 percent. 3. Shore A Hardness: Minimum 20. 4. Water resistant. 5. Mold and mildew resistant. 6. VOC: Maximum 75 g/L (less water). 7. Maximum Static5Pressure Class: 105inch wg (2500 Pa), positive and negative. 8. Service: Indoor or outdoor. 9. Substrate: Compatible with galvanized sheet steel (both PVC coated and bare), stainless steel, or aluminum sheets. C. Flange Gaskets: Butyl rubber, neoprene, or EPDM polymer with polyisobutylene plasticizer. D. Round Duct Joint O5Ring Seals: 1. Seal shall provide maximum leakage class of 3 cfm/100 sq. ft. at 15inch wg (0.14 L/s per sq. m at 250 Pa) and shall be rated for 105inch wg (25005 Pa) static5pressure class, positive or negative. 2. EPDM O5ring to seal in concave bead in coupling or fitting spigot. 3. Double5lipped, EPDM O5ring seal, mechanically fastened to factory5 fabricated couplings and fitting spigots. 2.7 HANGERS AND SUPPORTS A. Hanger Rods for Noncorrosive Environments: Cadmium5plated steel rods and nuts. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP METAL DUCTS STANDARD SPECIFICATIONS 23 31 13 – PAGE 6 OF 14 JUNE 29, 2012 B. Strap and Rod Sizes: Comply with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Table 551 (Table 551M), "Rectangular Duct Hangers Minimum Size," and Table 552, "Minimum Hanger Sizes for Round Duct." C. Steel Cables for Galvanized5Steel Ducts: Galvanized steel complying with ASTM A 603. D. Steel Cable End Connections: Cadmium5plated steel assemblies with brackets, swivel, and bolts designed for duct hanger service; with an automatic5locking and clamping device. E. Duct Attachments: Sheet metal screws, blind rivets, or self5tapping metal screws; compatible with duct materials. F. Trapeze and Riser Supports: 1. Supports for Galvanized5Steel Ducts: Galvanized5steel shapes and plates. 2.8 MANUAL VOLUME DAMPERS A. Standard, Steel, Manual Volume Dampers: 1. Suitable for horizontal or vertical applications. 2. Frames: a. Hat5shaped, galvanized5steel channels, 0.0645inch (1.625mm) minimum thickness. b. Mitered and welded corners. c. Flanges for attaching to walls and flangeless frames for installing in ducts. 3. Blades: a. Multiple or single blade. b. Parallel5 or opposed5blade design. c. Stiffen damper blades for stability. d. Galvanized5steel, 0.064 inch (1.62 mm) thick. 4. Blade Axles: Galvanized steel. 5. Bearings: a. Molded synthetic. b. Dampers in ducts with pressure classes of 35inch wg (750 Pa) or less shall have axles full length of damper blades and bearings at both ends of operating shaft. B. Damper Hardware: 1. Zinc5plated, die5cast core with dial and handle made of 3/325inch5 (2.45 mm5) thick zinc5plated steel, and a 3/45inch (195mm) hexagon locking nut. 2. Include center hole to suit damper operating5rod size. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP METAL DUCTS STANDARD SPECIFICATIONS 23 31 13 – PAGE 7 OF 14 JUNE 29, 2012 3. Include elevated platform for insulated duct mounting. 2.9 TURNING VANES A. Manufactured Turning Vanes for Metal Ducts: Curved blades of galvanized sheet steel; support with bars perpendicular to blades set; set into vane runners suitable for duct mounting. 1. Acoustic Turning Vanes: Fabricate airfoil5shaped aluminum extrusions with perforated faces and fibrous5glass fill. B. General Requirements: Comply with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible"; Figures 453, "Vanes and Vane Runners," and 454, "Vane Support in Elbows." C. Vane Construction: Single wall for ducts up to 48 inches (1200 mm) wide and double wall for larger dimensions. 2.10 DUCT5MOUNTED ACCESS DOORS A. Duct5Mounted Access Doors: Fabricate access panels according to SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible"; Figures 752 (752M), "Duct Access Doors and Panels," and 753, "Access Doors 5 Round Duct." 1. Door: a. Double wall, rectangular. b. Galvanized sheet metal with insulation fill and thickness as indicated for duct pressure class. c. Hinges and Latches: 15by515inch (255by5255mm) butt or piano hinge and cam latches. d. Fabricate doors airtight and suitable for duct pressure class. 2. Frame: Galvanized sheet steel, with bend5over tabs and foam gaskets. 3. Number of Hinges and Locks: a. Access Doors Less Than 12 Inches (300 mm) Square: No hinges and two sash locks. b. Access Doors up to 18 Inches (460 mm) Square: Two hinges and two sash locks. c. Access Doors up to 24 by 48 Inches (600 by 1200 mm): Three hinges and two compression latches with outside and inside handles. d. Access Doors Larger Than 24 by 48 Inches (600 by 1200 mm): Four hinges and two compression latches with outside and inside handles. 2.11 FLEXIBLE CONNECTORS A. Materials: Flame5retardant or noncombustible fabrics. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP METAL DUCTS STANDARD SPECIFICATIONS 23 31 13 – PAGE 8 OF 14 JUNE 29, 2012 B. Coatings and Adhesives: Comply with UL 181, Class 1. C. Metal5Edged Connectors: Factory fabricated with a fabric strip 351/2 inches (89 mm) wide attached to 2 strips of 253/45inch5 (705mm5) wide, 0.0285inch5 (0.75mm5) thick, galvanized sheet steel or 0.0325inch5 (0.85mm5) thick aluminum sheets. Provide metal compatible with connected ducts. D. Indoor System, Flexible Connector Fabric: Glass fabric double coated with neoprene. 1. Minimum Weight: 26 oz./sq. yd. (880 g/sq. m). 2. Tensile Strength: 480 lbf/inch (84 N/mm) in the warp and 360 lbf/inch (63 N/mm) in the filling. 3. Service Temperature: Minus 40 to plus 200 deg F (Minus 40 to plus 93 deg C). E. Outdoor System, Flexible Connector Fabric: Glass fabric double coated with weatherproof, synthetic rubber resistant to UV rays and ozone. 1. Minimum Weight: 24 oz./sq. yd. (810 g/sq. m). 2. Tensile Strength: 530 lbf/inch (93 N/mm) in the warp and 440 lbf/inch (77 N/mm) in the filling. 3. Service Temperature: Minus 50 to plus 250 deg F (Minus 45 to plus 121 deg C). PART 3 EXECUTION 3.1 DUCT INSTALLATION A. Drawing plans, schematics, and diagrams indicate general location and arrangement of duct system. Indicated duct locations, configurations, and arrangements were used to size ducts and calculate friction loss for air5 handling equipment sizing and for other design considerations. Install duct systems as indicated unless deviations to layout are approved on Shop Drawings and Coordination Drawings. B. Install ducts according to SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible" unless otherwise indicated. C. Install round [ and flatoval ] ducts in maximum practical lengths. D. Install ducts with fewest possible joints. E. Install factory5 or shop5fabricated fittings for changes in direction, size, and shape and for branch connections. F. Unless otherwise indicated, install ducts vertically and horizontally, and parallel and perpendicular to building lines. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP METAL DUCTS STANDARD SPECIFICATIONS 23 31 13 – PAGE 9 OF 14 JUNE 29, 2012 G. Install ducts close to walls, overhead construction, columns, and other structural and permanent enclosure elements of building. H. Install ducts with a clearance of 1 inch (25 mm), plus allowance for insulation thickness. I. Route ducts to avoid passing through transformer vaults and electrical equipment rooms and enclosures. J. Where ducts pass through non5fire5rated interior partitions and exterior walls and are exposed to view, cover the opening between the partition and duct or duct insulation with sheet metal flanges of same metal thickness as the duct. Overlap openings on four sides by at least 151/2 inches (38 mm). K. Where ducts pass through fire5rated interior partitions and exterior walls, install fire dampers. L. Protect duct interiors from moisture, construction debris and dust, and other foreign materials.[ Comply with SMACNA's "IAQ Guidelines for Occupied Buildings Under Construction," Appendix G, "Duct Cleanliness for New Construction Guidelines."] 3.2 INSTALLATION OF EXPOSED DUCTWORK A. Protect ducts exposed in finished spaces from being dented, scratched, or damaged. B. Trim duct sealants flush with metal. Create a smooth and uniform exposed bead. Do not use two5part tape sealing system. C. Grind welds to provide smooth surface free of burrs, sharp edges, and weld splatter. When welding stainless steel with a No. 3 or 4 finish, grind the welds flush, polish the exposed welds, and treat the welds to remove discoloration caused by welding. D. Maintain consistency, symmetry, and uniformity in the arrangement and fabrication of fittings, hangers and supports, duct accessories, and air outlets. E. Repair or replace damaged sections and finished work that does not comply with these requirements. 3.3 DUCT SEALING A. Seal ducts for leakage classes in table below: DUCT TYPE LEAKAGE CLASS, CFM/100 ft at 1” wg Metal (flexible excluded) Round and Flat Oval [3] BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP METAL DUCTS STANDARD SPECIFICATIONS 23 31 13 – PAGE 10 OF 14 JUNE 29, 2012 Rectangular [6] Flexible [6] B. Note: Leakage classes for specific applications may be specified elsewhere in this specification. MINIMUM DUCT SEAL LEVELA DUCT TYPE Duct Location Supply <2 in. w.c.b >2 in. w.c.b. Exhaust Return Outdoor A A C A Unconditioned Spaces B A C B Conditioned Spacesc C B B C a See description of seal levels below. b Duct design static pressure classification. c Includes indirectly conditioned spaces such as return air plenums. C. Longitudinal seams are joints oriented in the direction of airflow. Transverse joints are connections of two duct sections oriented perpendicular to airflow. Duct wall penetrations are openings made by any screw fastener, pipe, rod, or wire. Spiral lock seams in a round or flat oval duct need not be sealed. All other connections are considered transverse joints, including but not limited to spin5ins, taps, and other branch connections, access door frames and jambs, duct connections to equipment, etc. 3.4 HANGER AND SUPPORT INSTALLATION A. Comply with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Chapter 5, "Hangers and Supports." B. Building Attachments: Concrete inserts, powder5actuated fasteners, or structural5steel fasteners appropriate for construction materials to which hangers are being attached. 1. Where practical, install concrete inserts before placing concrete. 2. Install powder5actuated concrete fasteners after concrete is placed and completely cured. 3. Use powder5actuated concrete fasteners for standard5weight aggregate concretes or for slabs more than 4 inches (100 mm) thick. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP METAL DUCTS STANDARD SPECIFICATIONS 23 31 13 – PAGE 11 OF 14 JUNE 29, 2012 4. Do not use powder5actuated concrete fasteners for lightweight5aggregate concretes or for slabs less than 4 inches (100 mm) thick. 5. Do not use powder5actuated concrete fasteners for seismic restraints. C. Hanger Spacing: Comply with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Table 551 (Table 551M), "Rectangular Duct Hangers Minimum Size," and Table 552, "Minimum Hanger Sizes for Round Duct," for maximum hanger spacing; install hangers and supports within 24 inches (610 mm) of each elbow and within 48 inches (1200 mm) of each branch intersection. D. Hangers Exposed to View: Threaded rod and angle or channel supports. E. Support vertical ducts with steel angles or channel secured to the sides of the duct with welds, bolts, sheet metal screws, or blind rivets; support at each floor and at a maximum intervals of 16 feet (5 m). F. Install upper attachments to structures. Select and size upper attachments with pull5out, tension, and shear capacities appropriate for supported loads and building materials where used. 3.5 CONNECTIONS A. Make connections to equipment with flexible connectors. B. Comply with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible" for branch, outlet and inlet, and terminal unit connections. 3.6 PAINTING A. Paint interior of metal ducts that are visible through registers and grilles and that do not have duct liner. Apply one coat of flat, black, latex paint over a compatible galvanized5steel primer. 3.7 FIELD QUALITY CONTROL A. Perform tests and inspections. B. Leakage Tests: 1. Comply with SMACNA's "HVAC Air Duct Leakage Test Manual." Submit a test report for each test. 2. Test the following systems: a. Supply Ducts with a Pressure Class of 25Inch wg (500 Pa) or Higher: Test representative duct sections totaling no less than 50 percent of total installed duct area for each designated pressure class. b. Return Ducts with a Pressure Class of 25Inch wg (500 Pa) or Higher: Test representative duct sections totaling no less than 50 percent of total installed duct area for each designated pressure class. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP METAL DUCTS STANDARD SPECIFICATIONS 23 31 13 – PAGE 12 OF 14 JUNE 29, 2012 c. Exhaust Ducts with a Pressure Class of 25Inch wg (500 Pa) or Higher: Test representative duct sections totaling no less than 50 percent of total installed duct area for each designated pressure class. 3. Disassemble, reassemble, and seal segments of systems to accommodate leakage testing and for compliance with test requirements. 4. Test for leaks before applying external insulation. 5. Conduct tests at static pressures equal to maximum design pressure of system or section being tested. If static5pressure classes are not indicated, test system at maximum system design pressure. Do not pressurize systems above maximum design operating pressure. 6. Give seven days' advance notice for testing. C. Duct system will be considered defective if it does not pass tests and inspections. D. Prepare test and inspection reports. 3.8 DUCT CLEANING A. Clean new and existing duct system(s) before testing, adjusting, and balancing. B. Use service openings for entry and inspection. 1. Create new openings and install access panels appropriate for duct static5 pressure class if required for cleaning access. Provide insulated panels for insulated or lined duct. Patch insulation and liner as recommended by duct liner manufacturer. 2. Disconnect and reconnect flexible ducts as needed for cleaning and inspection. 3. Remove and reinstall ceiling to gain access during the cleaning process. C. Clean the following components by removing surface contaminants and deposits: 1. Air outlets and inlets (registers, grilles, and diffusers). 2. Supply, return, and exhaust fans including fan housings, plenums (except ceiling supply and return plenums), scrolls, blades or vanes, shafts, baffles, dampers, and drive assemblies. 3. Coils and related components. 4. Return5air ducts, dampers, actuators, and turning vanes except in ceiling plenums and mechanical equipment rooms. 5. Supply5air ducts, dampers, actuators, and turning vanes. 6. Dedicated exhaust and ventilation components and makeup air systems. 3.9 START UP A. Air Balance: Comply with requirements in Division 23 Section "Testing, Adjusting, and Balancing for HVAC." BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP METAL DUCTS STANDARD SPECIFICATIONS 23 31 13 – PAGE 13 OF 14 JUNE 29, 2012 3.10 DUCT SCHEDULE A. Supply Duct Pressure Class: 1. Pressure Class: Positive 25inch wg (500 Pa). B. Return Duct Pressure Class: 1. Pressure Class: Positive or negative 25inch wg (500 Pa). C. Exhaust Duct Pressure Class: 1. Ducts Connected to Fans Exhausting (ASHRAE 62.1, Class 1 and 2) Air: a. Pressure Class: Negative 25inch wg (500 Pa). D. Elbow Configuration: 1. Rectangular Duct: Comply with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Figure 452, "Rectangular Elbows." a. Velocity 1000 fpm (5 m/s) or Lower: 1) Radius Type RE 1 with minimum 0.5 radius5to5diameter ratio. 2) Mitered Type RE 4 without vanes. b. Velocity 1000 to 1500 fpm (5 to 7.6 m/s): 1) Radius Type RE 1 with minimum 1.0 radius5to5diameter ratio. 2) Radius Type RE 3 with minimum 0.5 radius5to5diameter ratio and two vanes. 3) Mitered Type RE 2 with vanes complying with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Figure 453, "Vanes and Vane Runners," and Figure 454, "Vane Support in Elbows." c. Velocity 1500 fpm (7.6 m/s) or Higher: 1) Radius Type RE 1 with minimum 1.5 radius5to5diameter ratio. 2) Radius Type RE 3 with minimum 1.0 radius5to5diameter ratio and two vanes. 3) Mitered Type RE 2 with vanes complying with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Figure 453, "Vanes and Vane Runners," and Figure 454, "Vane Support in Elbows." 2. Round Duct: Comply with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Figure 354, "Round Duct Elbows." a. Minimum Radius5to5Diameter Ratio and Elbow Segments: Comply with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Table 351, "Mitered Elbows." Elbows with less than 905 degree change of direction have proportionately fewer segments. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP METAL DUCTS STANDARD SPECIFICATIONS 23 31 13 – PAGE 14 OF 14 JUNE 29, 2012 1) Velocity 1000 fpm (5 m/s) or Lower: 0.5 radius5to5diameter ratio and three segments for 905degree elbow. 2) Velocity 1000 to 1500 fpm (5 to 7.6 m/s): 1.0 radius5to5diameter ratio and four segments for 905degree elbow. 3) Velocity 1500 fpm (7.6 m/s) or Higher: 1.5 radius5to5diameter ratio and five segments for 905degree elbow. 4) Radius5to Diameter Ratio: 1.5. b. Round Elbows, 12 Inches (305 mm) and Smaller in Diameter: Stamped or pleated. c. Round Elbows, 14 Inches (356 mm) and Larger in Diameter: Standing seam. E. Branch Configuration: 1. Rectangular Duct: Comply with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Figure 456, "Branch Connection." a. Rectangular Main to Rectangular Branch: 455degree entry. b. Rectangular Main to Round Branch: Spin in. 2. Round and Flat Oval: Comply with SMACNA's "HVAC Duct Construction Standards 5 Metal and Flexible," Figure 355, "90 Degree Tees and Laterals," and Figure 356, "Conical Tees." Saddle taps are permitted in existing duct. a. Velocity 1000 fpm (5 m/s) or Lower: 905degree tap. b. Velocity 1000 to 1500 fpm (5 to 7.6 m/s): Conical tap. c. Velocity 1500 fpm (7.6 m/s) or Higher: 455degree lateral. END OF SECTION 23 31 13 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE DAMPERS STANDARD SPECIFICATIONS 23 33 16 – PAGE 1 OF 4 JUNE 29, 2012 SECTION 233316 FIRE DAMPERS PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. The Contract Drawings and the General Provisions of the Contract, including the General Conditions of the Contract for Construction, Supplementary Conditions, Special Conditions and Division 1 Specification Sections apply to the work of this Section. B. The Work of the Section 23 01 00 6 Mechanical Basic Materials and Methods applies to the Work of this Section. 1.2 WORK INCLUDED: A. Provide a complete, operating, tested, functioning, documented fire damper and combination fire and smoke damper system including all work shown, specified, or required for proper system operation. 1.3 SUBMITTALS: A. Provide product data for each fire damper, combination fire and smoke damper, relief grill, wall frame and media filter assembly. B. Provide wiring diagrams: For power, signal, and control wiring. PART 2 PRODUCTS 2.1 FIRE DAMPER AND SLEEVE ASSEMBLY: A. 16 ½ hour U.L. classified static fire damper. Frame: 20 gauge galvanized steel channel. 24 gauge galvanized curtain type blades outside airstream, except when located behind grille where blades may be inside airstream. B. Provide 212 F fusible link. C. Each fire damper shall include a steel sleeve of length to suit application and retaining angles furnished by the damper manufacturer. D. Provide space fusible links. E. Manufacturer and Model: Ruskin, Air Balance Inc. or equal. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE DAMPERS STANDARD SPECIFICATIONS 23 33 16 – PAGE 2 OF 4 JUNE 29, 2012 2.2 COMBINATION FIRE AND SMOKE DAMPERS: A. 161/2 hour UL classified static combination fire and smoke damper. 16 gauge galvanized steel frame. 16 gauge galvanized multiple V6groove or airfoil blade type. Class I leakage rating. B. Heat6Responsive Device: 212° F Electric fuse link and switch package, factory installed, rated. C. Smoke Detector: Integral, factory wired for single6point connection. D. Mounting Sleeve: Factory installed, galvanized sheet steel; length to suite wall application. E. Manufacturer: Ruskin Company, Greenheck Fan Corporation, Air Balance Inc. or equal. 2.3 FIRE DAMPER /FIRE SMOKE DAMPER ACCESS DOOR: A. Provide 12” x 12” minimum duct access door at location suitable to reset curtain and replace fusible link or reset actuator. Duct access doors shall be hinged one side. They shall be gasketed and shall include a minimum of two camlock latches. B. Enlarge access doors as required in large ducts or difficult to reach areas so that a fusible link can be readily replaced. PART 3 EXECUTION 3.1 FIRE DAMPERS AND COMBINATION FIRE AND SMOKE DAMPERS: A. Install in strict accordance with the manufacturer's printed installation instructions and with the locations and details shown on the Plans. 3.2 DUCT ACCESS DOORS: A. Locate in the general locations shown on the Plans or adjacent to and close enough to fire damper or combination fire smoke damper to allow resetting the fire damper curtain and replacement of the fusible link. Mark each access door "Fire Damper Access" in black permanent marker. 3.3 PRE6PUNCH LIST REVIEW: A. The Contractor shall perform a pre6punch list review and shall verify the following for each fire damper and combination fire and smoke damper: 1. Fire/smoke damper installed at each location shown on the Plans. 2. Installed in accordance with manufacturer's instructions. 3. Sleeve installed and fire/smoke damper anchored to sleeve BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE DAMPERS STANDARD SPECIFICATIONS 23 33 16 – PAGE 3 OF 4 JUNE 29, 2012 properly. 4. Angles anchored to sleeve and free floating in general construction. 5. U.L. clearances between sleeve and general construction to avoid binding damper in a fire due to expansion of the metal against a tight opening. 6. Angles overlap general construction of opening by 1” minimum. 7. Duct access doors are installed and are located properly to allow resetting damper curtain replacing fusible link. 8. Duct access doors are accessible through the general construction. 3.4 ENGINEER'S ACCESSIBILITY TEST: A. The Engineer shall, at his/her option, sever up to 5% of the fusible links on fire dampers but in no case less than two or more than ten so that the Contractor can demonstrate the ease with which the duct access doors allow re6setting of fire dampers and replacement of fusible links. B. The locations for these tests shall be at the sole discretion of the Engineer and Owner. C. The Contractor shall provide spare fusible links and shall demonstrate the replacement of fusible links and re6setting of dampers. D. If in the judgment of the Engineer, acting as the Owner's representative, the access is not adequate to allow proper fire dampers servicing, the Contractor shall install additional access doors as required to allow proper servicing of the fire dampers. 3.5 SPARE FUSIBLE LINKS A. Provide five (5) spare fusible links at each temperature rating. Submit to Engineer and obtain a receipt. END OF SECTION 23 33 16 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE DAMPERS STANDARD SPECIFICATIONS 23 33 16 – PAGE 4 OF 4 JUNE 29, 2012 [ PAGE LEFT INTENTIONALLY BLANK ] BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP CENTRIFUGAL HVAC FANS STANDARD SPECIFICATIONS 23 34 16 – PAGE 1 OF 5 JUNE 29, 2012 SECTION 233416 CENTRIFUGAL HVAC FANS PART 1 GENERAL 1.1 SUBMITTALS A. Product Data: Provide the following: 1. Include rated capacities, furnished specialties, and accessories for each fan. 2. Certified fan performance curves with system operating conditions indicated. 3. Certified fan sound7power ratings. 4. Motor ratings and electrical characteristics, plus motor and electrical accessories. 5. Material thickness and finishes, including color charts. 6. Dampers, including housings, linkages, and operators. 7. Vibration Isolators 8. Operation and Maintenance Data: For centrifugal fans to include in emergency, operation, and maintenance manuals. PART 2 PRODUCTS 2.1 PERFORMANCE REQUIREMENTS A. AMCA Compliance: 1. Comply with AMCA performance requirements and bear the AMCA7 Certified Ratings Seal. 2. Operating Limits: Classify according to AMCA 99. B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 2.2 INLINE CENTRIFUGAL FANS (BELT DRIVE) A. Basis7of7Design Product: Subject to compliance with requirements, provide Loren Cook Model SQI or a comparable product by one of the following: 1. Chicago Blower Corporation. 2. Cincinnati Fan. 3. New York Blower Company (The). B. Description: 1. Factory7fabricated, 7assembled, 7tested, and 7finished, belt7driven centrifugal fans consisting of housing, wheel, fan shaft, bearings, motor, drive assembly, and support structure. 2. Deliver fans as factory7assembled units, to the extent allowable by shipping limitations. 3. Factory7installed and 7wired disconnect switch. C. Disconnect Switches: BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP CENTRIFUGAL HVAC FANS STANDARD SPECIFICATIONS 23 34 16 – PAGE 2 OF 5 JUNE 29, 2012 1. NEMA rated: 1 2. Positive electrical shut7off. D. Housings: 1. Formed panels to make curved7scroll housings with shaped cutoff. 2. Panel Bracing: Steel angle7 or channel7iron member supports for mounting and supporting fan scroll, wheel, motor, and accessories. 3. Horizontally split, bolted7flange housing. 4. Spun inlet cone with flange. 5. Outlet flange. 6. Constructed of steel and coated with permatector. 7. Housing and bearing supports shall be constructed of welded steel members to prevent vibration and to rigidly support the shaft and bearing assembly balancing up to a minimum of 10 horsepower. E. Housing Supports and Drive Frame: 1. Housing supports are constructed of structural steel with formed flanges. 2. Drive frame is welded steel which supports the shaft and bearings and reinforcement for the housing. 3. Pivoting motor plate with adjusting screws to make belt tensioning operations. 4. Prepunched mounting holes for installation. 5. Drive frame is coated with Permatector. F. Backward7Inclined Wheels: 1. Non7overloading, backward inclined centrifugal wheel. 2. Constructed of aluminum. 3. Single7width7single7inlet construction with curved inlet flange, backplate, and fastened to shaft with set screws. 4. Welded or riveted to flange and backplate; cast7iron or cast7steel hub riveted to backplate. 5. Statically and dynamically balanced. 6. The wheel cone and fan inlet will be matched and shall have precise running tolerances for maximum performance and operating efficiency. G. Grease7Lubricated Shaft Bearings: 1. Self7aligning, pillow7block7type, tapered roller bearings with double7 locking collars and two7piece, cast7iron housing. 2. Ball7Bearing Rating Life: L50 at 200,000 hours. H. Belt Drives: 1. Factory mounted, with adjustable alignment and belt tensioning. 2. Fan Pulleys: Cast iron or cast steel with split, tapered bushing; dynamically balanced at factory. Keyed and securely attached to wheel and motor shafts. 3. Motor Pulleys: Adjustable pitch for use with motors through 5 hp; fixed pitch for use with larger motors. Select pulley so pitch adjustment is at the middle of adjustment range at fan design conditions. 4. Belts: Oil resistant, nonsparking, and nonstatic; matched sets for multiple belt drives. 5. Readily accessible for maintenance. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP CENTRIFUGAL HVAC FANS STANDARD SPECIFICATIONS 23 34 16 – PAGE 3 OF 5 JUNE 29, 2012 6. Belt Guards: Fabricate to comply with OSHA and SMACNA requirements of diamond7mesh wire screen welded to steel angle frame or equivalent, prime coated. Secure to fan or fan supports without short circuiting vibration isolation. Include provisions for adjustment of belt tension, lubrication, and use of tachometer with guard in place. 7. Motor Mount: Adjustable for belt tensioning. I. Motors: 1. Motor enclosures: Open dripoff. 2. Motors are permanently lubricated, sealed, heavy duty ball bearing type furnished at the specific voltage, phase, and enclosure. J. Accessories: 1. Access for Inspection, Cleaning, and Maintenance: Comply with requirements in ASHRAE 62.1. 2. Companion Flanges: Rolled flanges for duct connections of same material as housing. 3. Galvanized frames with prepunched mounting holes. 4. Integral backdraft dampers. 5. Balanced for minimal resistance to flow. 6. Inlet Screens: For non ducted fans; grid screen of same material as housing. 7. Vibration isolators. 2.3 INLINE CENTRIFUGAL FANS (DIRECT DRIVE) A. Basis7of7Design Product: Subject to compliance with requirements, provide Loren Cook Model SQI or a comparable product by one of the following: 1. Chicago Blower Corporation. 2. Cincinnati Fan. 3. New York Blower Company (The). B. Description: 1. Factory7fabricated, 7assembled, 7tested, and 7finished, direct7driven centrifugal fans consisting of housing, wheel, fan shaft, bearings, motor, drive assembly, and support structure. 2. Deliver fans as factory7assembled units, to the extent allowable by shipping limitations. 3. Factory7installed and 7wired disconnect switch. C. Disconnect Switches: 1. NEMA rated: 1 2. Positive electrical shut7off. D. Housings: 1. Formed panels to make curved7scroll housings with shaped cutoff. 2. Panel Bracing: Steel angle7 or channel7iron member supports for mounting and supporting fan scroll, wheel, motor, and accessories. 3. Horizontally split, bolted7flange housing. 4. Spun inlet cone with flange. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP CENTRIFUGAL HVAC FANS STANDARD SPECIFICATIONS 23 34 16 – PAGE 4 OF 5 JUNE 29, 2012 5. Outlet flange. 6. Constructed of steel and coated with permatector. 7. Housing and bearing supports shall be constructed of welded steel members to prevent vibration and to rigidly support the shaft and bearing assembly balancing up to a minimum of 10 horsepower. E. Housing Supports and Drive Frame: 1. Housing supports are constructed of structural steel with formed flanges. 2. Drive frame is welded steel which supports the shaft and bearings and reinforcement for the housing. 3. Prepunched mounting holes for installation. 4. Drive frame is coated with Permatector. F. Backward7Inclined Wheels: 1. Non7overloading, backward inclined centrifugal wheel. 2. Constructed of aluminum. 3. Single7width7single7inlet construction with curved inlet flange, backplate, and fastened to shaft with set screws. 4. Welded or riveted to flange and backplate; cast7iron or cast7steel hub riveted to backplate. 5. Statically and dynamically balanced. 6. The wheel cone and fan inlet will be matched and shall have precise running tolerances for maximum performance and operating efficiency. G. Motors: 1. Motors are permanently lubricated, sealed, heavy duty ball bearing type furnished at the specific voltage, phase, and enclosure. H. Accessories: 1. Access for Inspection, Cleaning, and Maintenance: Comply with requirements in ASHRAE 62.1. 2. Companion Flanges: Rolled flanges for duct connections of same material as housing. 3. Galvanized frames with prepunched mounting holes. 4. Integral backdraft dampers. 5. Balanced for minimal resistance to flow. 6. Inlet Screens: For non ducted fans; grid screen of same material as housing. 7. Vibration isolators. 8. Provide variable speed controller. PART 3 EXECUTION 3.1 INSTALLATION A. Install centrifugal fans level and plumb. B. Disassemble and reassemble units, as required for moving to the final location, according to manufacturer's written instructions. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP CENTRIFUGAL HVAC FANS STANDARD SPECIFICATIONS 23 34 16 – PAGE 5 OF 5 JUNE 29, 2012 C. Lift and support units with manufacturer's designated lifting or supporting points. D. Equipment Mounting: Install continuous7thread hanger rods and spring vibration hangers with vertical7limit stop of size required to support weight of centrifugal fans. E. Install units with clearances for service and maintenance. 3.2 FIELD QUALITY CONTROL A. Testing Agency: Engage a qualified testing agency to perform tests and inspections. B. Manufacturer's Field Service: Engage a factory7authorized service representative to test and inspect components, assemblies, and equipment installations, including connections. C. Perform the following tests and inspections[ with the assistance of a factory7 authorized service representative]: 1. Verify that shipping, blocking, and bracing are removed. 2. Verify that unit is secure on mountings and supporting devices and that connections to ducts and electrical components are complete. Verify that proper thermal7overload protection is installed in motors, starters, and disconnect switches. 3. Verify that cleaning and adjusting are complete. 4. Disconnect fan drive from motor, verify proper motor rotation direction, and verify fan wheel free rotation and smooth bearing operation. Reconnect fan drive system, align and adjust belts, and install belt guards. 5. Adjust belt tension. 6. Adjust damper linkages for proper damper operation. 7. Verify lubrication for bearings and other moving parts. 8. Verify that manual and automatic volume control and fire and smoke dampers in connected ductwork systems are in fully open position. 9. See Division 23 Section "Testing, Adjusting, and Balancing For HVAC" for testing, adjusting, and balancing procedures. 10. Remove and replace malfunctioning units and retest as specified above. D. Prepare test and inspection reports. END OF SECTION 23 34 16 BEARDSLEY DESIGN ASSOCIATES CORNELL NCP DIFFUSERS, REGISTERS, AND GRILLES STANDARD SPECIFICATIONS 23 37 13 PAGE 1 OF 2 JUNE 29, 2012 SECTION 233713 DIFFUSERS, REGISTERS, AND GRILLES PART 1 GENERAL 1.1 SUBMITTALS A. Product Data: For each type of product indicated, provide the following: 1. Data Sheet: Indicate materials of construction, finish, and mounting details; and performance data including throw and drop, staticpressure drop, and noise ratings. 2. Diffuser, Register, and Grille Schedule: Indicate drawing designation, room location, quantity, model number, size, and accessories furnished. PART 2 PRODUCTS 2.1 REGISTERS AND GRILLES A. Register Grille: 1. Provide product by one of the following: a. Anemostat Products; a Mestek company. b. Price Industries. c. Titus. d. Tuttle & Bailey. 2. Material: Steel. 3. Finish: Baked enamel, white. 4. Face Blade Arrangement: Horizontal spaced 1/2 inch apart. 5. Core Construction: Integral. 6. Frame: 11/4 inches wide. 7. Mounting: Countersunk screw. 8. Accessories a. Steel opposedblade damper with screwdriver slot operator b. Filter B. Fixed Lattice Face Plate : 1. Provide product by one of the following: a. Anemostat Products; a Mestek company. b. Price Industries. c. Titus. d. Tuttle & Bailey. 2. Material: Steel, 12 gauge. 3. Finish: Baked enamel, white. 4. Face Arrangement: 13/16" square holes on 1" centers. BEARDSLEY DESIGN ASSOCIATES CORNELL NCP DIFFUSERS, REGISTERS, AND GRILLES STANDARD SPECIFICATIONS 23 37 13 PAGE 2 OF 2 JUNE 29, 2012 2.2 SOURCE QUALITY CONTROL A. Verification of Performance: Rate diffusers, registers, and grilles according to ASHRAE 70, "Method of Testing for Rating the Performance of Air Outlets and Inlets." PART 3 EXECUTION 3.1 EXAMINATION A. Examine areas where diffusers, registers, and grilles are to be installed for compliance with requirements for installation tolerances and other conditions affecting performance of equipment. B. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. Install diffusers, registers, and grilles level and plumb. B. Ceiling/WallMounted Outlets and Inlets: Drawin gs indicate general arrangement of ducts, fittings, and accessories. Air outlet and inlet locations have been indicated to achieve design requirements for air volume, noise criteria, airflow pattern, throw, and pressure drop. Make final locations where indicated, as much as practical. For units installed in layin ceiling panels, locate units in the center of panel. Where architectural features or other items conflict with installation, notify Architect for a determination of final location. C. Install diffusers, registers, and grilles with airtight connections to ducts and to allow service and maintenance of dampers, air extractors, and fire dampers. 3.3 ADJUSTING A. After installation, adjust diffusers, registers, and grilles to air patterns indicated, or as directed, before starting air balancing. END OF SECTION 23 37 13 BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP SPLITSYSTEM AIRCONDITIONERS STANDARD SPECIFICATIONS 23 81 26 – PAGE 1 OF 6 JUNE 29, 2012 SECTION 238126 SPLITSYSTEM AIRCONDITIONERS PART 1 GENERAL 1.1 SUBMITTALS A. Product Data: Provide for each type of product indicated. Include rated capacities, operating characteristics, and furnished specialties and accessories. Include performance data in terms of capacities, outlet velocities, static pressures, sound power characteristics, motor requirements, and electrical characteristics. B. Shop Drawings: Include plans, elevations, sections, details, and attachments to other work. 1. Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection. 2. Wiring Diagrams: For power, signal, and control wiring. C. Samples for Initial Selection: For units with factoryapplied color finishes. D. Field qualitycontrol reports. E. Operation and Maintenance Data: For splits ystem airconditioning units to include in emergency, operation, and maintenance manuals. F. Warranty: Sample of special warranty. 1.2 QUALITY ASSURANCE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. B. ASHRAE Compliance: 1. Fabricate and label refrigeration system to comply with ASHRAE 15, "Safety Standard for Refrigeration Systems." 2. ASHRAE Compliance: Applicable requirements in ASHRAE 62.1, Section 4 "Outdoor Air Quality," Section 5 "Sys tems and Equipment," Section 6 " Procedures," and Section 7 "Constru ction and System StartUp." C. ASHRAE/IESNA Compliance: Applicable requirements in ASHRAE/IESNA 90.1. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP SPLITSYSTEM AIRCONDITIONERS STANDARD SPECIFICATIONS 23 81 26 – PAGE 2 OF 6 JUNE 29, 2012 1.3 COORDINATION A. Coordinate sizes and locations of concrete bases with actual equipment provided. Cast anchorbolt inserts into bases. Concrete, rei nforcement, and formwork are specified in Division 03 Section "CastinPlace Con crete." B. Coordinate sizes and locations of roof curbs, equipment supports, and roof penetrations with actual equipment provided. 1.4 WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of splitsystem airco nditioning units that fail in materials or workmanship within specified warranty period. 1. Warranty Period: a. For Compressor: Five year(s) from date of Substantial Completion. b. For Parts: Five year(s) from date of Substantial Completion. PART 2 PRODUCTS 2.1 MANUFACTURERS A. BasisofDesign Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following: 1. Daikin 2. Friedrich Air Conditioning Company. 3. Koldwave, Inc.; a Mestek company. 4. Lennox International Inc. 5. Mitsubishi Electric HVAC Advanced Products Division. 6. SANYO HVAC 7. Trane; a business of Ingersol Rand 8. YORK; a Johnson Controls company. 2.2 INDOOR UNITS 5 TONS (18 kW) OR LESS A. Cassette Type EvaporatorFan Components: 1. Chassis: Galvanized steel, 24" x 24" square unit suspended from structure with fourway grille fixed to bottom of cabinet. 2. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins and thermalexpansion valve. Comply with AHRI 210/240. 3. Fan: Direct drive, centrifugal. 4. Fan Motors: a. Multitapped, multispeed with internal thermal protection and permanent lubrication. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP SPLITSYSTEM AIRCONDITIONERS STANDARD SPECIFICATIONS 23 81 26 – PAGE 3 OF 6 JUNE 29, 2012 b. Enclosure type: Totally enclosed, fan cooled. c. NEMA Premium (TM) efficient motors as defined in NEMA MGI. d. Controllers, electrical devices & wiring: Comply with requirements for electrical devices & connections specified in Division 26 sections. 5. Airstream Surfaces: Surfaces in contact with the airstream shall comply with requirements in ASHRAE 62.1. 6. Filters: Permanent, cleanable. 7. Condensate Drain Pans: a. Fabricated with one percent slope in at least two planes to collect condensate from cooling coils (including coil piping connections, coil headers, and return bends), and to direct water toward drain connection. 1) Depth: A minimum of 1" deep. b. Singlewall, stainlesssteel sheet. c. Drain Connection: Located at lowest point of pan and sized to prevent overflow. Terminate with threaded nipple on one end of pan. 8. Accessories: a. Provide mini condensate pump where specified on drawings. Field installed b. Provide fully insulated full port ball valve with service port installed in each refrigerant line at each indoor unit. c. Provide auxillary condensate detection device that is a field installed accessory in addition to any factory installed condensate detection devices. B. WallMounted, EvaporatorFan Components: 1. Cabinet: Enameled steel with removable panels on front and ends in white color finish, and discharge drain pans with drain connection. 2. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins and thermalexpansion valve. Comply with AHRI 210/240. 3. Fan: Direct drive, centrifugal. 4. Fan Motors: a. Multitapped, multispeed with internal thermal protection and permanent lubrication. b. Enclosure Type: Totally enclosed, fan cooled. c. NEMA Premium (TM) efficient motors as defined in NEMA MG 1. d. Controllers, Electrical Devices, and Wiring: Comply with requirements for electrical devices and connections specified in Division 26 Sections. 5. Airstream Surfaces: Surfaces in contact with the airstream shall comply with requirements in ASHRAE 62.1. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP SPLITSYSTEM AIRCONDITIONERS STANDARD SPECIFICATIONS 23 81 26 – PAGE 4 OF 6 JUNE 29, 2012 6. Condensate Drain Pans: a. Fabricated with one percent slope in at least two planes to collect condensate from cooling coils (including coil piping connections, coil headers, and return bends) and humidifiers, and to direct water toward drain connection. 1) Depth: A minimum of 1 inch (25 mm) deep. b. Singlewall, stainlesssteel sheet. c. Drain Connection: Located at lowest point of pan and sized to prevent overflow. Terminate with threaded nipple on one end of pan. d. PanTop Surface Coating: Asphaltic waterproofin g compound. 7. Accessories: a. Provide mini condensate pump where specified on drawings. Field installed. b. Provide fully insulated full port ball valve with service port installed in each refrigerant line at each indoor unit. c. Provide auxillary condensate detection device that is a field installed accessory in addition to any factory installed condensate detection devices. 2.3 OUTDOOR UNITS (5 TONS (18 kW) OR LESS) A. AirCooled, CompressorCondenser Components: 1. Casing: Steel, finished with baked enamel in color selected by Architect, with removable panels for access to controls, weep holes for water drainage, and mounting holes in base. Provide brass service valves, fittings, and gage ports on exterior of casing. 2. Compressor: Hermetically sealed with crankcase heater and mounted on vibration isolation device. Compressor motor shall have thermal and currentsensitive overload devices, start capacitor , relay, and contactor. a. Compressor Type: Scroll, inverter driver. b. Variable speed compressor motor with manualrese t highpressure switch and automaticreset lowpressure switch. c. Refrigerant Charge: R410A. d. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins and liquid subcooler. Comply with AHRI 210/240. 3. HeatPump Components: Reversing valve and lowt emperatureair cutoff thermostat. 4. Fan: Aluminumpropeller type, directly connecte d to motor. 5. Motor: Permanently lubricated, with integral thermaloverload protection. 6. Low Ambient Kit: Permits operation down to 0 deg F (17 deg C). 7. Mounting Base: Polyethylene. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP SPLITSYSTEM AIRCONDITIONERS STANDARD SPECIFICATIONS 23 81 26 – PAGE 5 OF 6 JUNE 29, 2012 2.4 ACCESSORIES A. Thermostat: Wall mounted to control compressor and evaporator fan, with the following features: 1. Liquidcrystal display indicating temperature, s etpoint temperature, time setting, operating mode, and fan speed. 2. Fanspeed selection including auto setting. 3. On/off, cool, heat & auto operation mode. B. Automaticreset timer to prevent rapid cycling o f compressor. C. Refrigerant Line Kits: Softannealed copper suc tion and liquid lines factory cleaned, dried, pressurized, and sealed; factoryin sulated suction & liquid lines with flared fittings at both ends. 1. Drain Hose: For condensate. PART 3 EXECUTION 3.1 INSTALLATION A. Install units level and plumb. B. Install evaporatorfan components using manufact urer's standard mounting devices securely fastened to building structure. C. Install groundmounted, compressorcondenser com ponents on 4inch (100 mm) thick, reinforced concrete base that is 4 inch es (100 mm) larger, on each side, than unit. Concrete, reinforcement, and formwork are specified in Division 03 Section "CastinPlace Concrete." Coord inate anchor installation with concrete base. D. Anchor units to supports with removable, cadmiumplated fasteners. E. Install compressorcondenser components on restr ained, spring isolators with a minimum static deflection of 1 inch (25 mm). F. Install and connect precharged refrigerant tubing to component's quickconnect fittings. Install tubing to allow access to unit. 3.2 CONNECTIONS A. Piping installation requirements are specified in other Division 23 Sections. Drawings indicate general arrangement of piping, fittings, and specialties. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP SPLITSYSTEM AIRCONDITIONERS STANDARD SPECIFICATIONS 23 81 26 – PAGE 6 OF 6 JUNE 29, 2012 B. Where piping is installed adjacent to unit, allow space for service and maintenance of unit. 3.3 FIELD QUALITY CONTROL A. Manufacturer's Field Service: Engage a factory authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections. B. Perform tests and inspections. 1. Manufacturer's Field Service: Engage a factory authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing. C. Tests and Inspections: 1. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist. 2. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation. 3. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. D. Remove and replace malfunctioning units and retest as specified above. E. Prepare test and inspection reports. 3.4 STARTUP SERVICE A. Engage a factoryauthorized service representati ve to perform startup service. 1. Complete installation and startup checks according to manufacturer's written instructions. 3.5 DEMONSTRATION A. Engage a factoryauthorized service representati ve to train Owner's maintenance personnel to adjust, operate, and maintain units. END OF SECTION 23 81 26 BEARDSLEY DESIGN ASSOCIATES CORNELL NCP FAN COIL UNITS STANDARD SPECIFICATIONS 23 82 19 – PAGE 1 OF 5 JUNE 29, 2012 SECTION 238219 FAN COIL UNITS PART 1 GENERAL 1.1 SUBMITTALS A. Product Data: Provide rated capacities, operating characteristics, furnished specialties, and accessories. B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection. 1. Wiring Diagrams: Power, signal, and control wiring. C. Operation and Maintenance Data: For fancoil un its to include in emergency, operation, and maintenance manuals. Maintenance schedules and repair part lists for motors, coils, integral controls, and filters. D. Warranty: Special warranty specified in this Section. 1.2 QUALITY ASSURANCE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. B. ASHRAE Compliance: Applicable requirements in ASHRAE 62.1, Section 5 "Systems and Equipment" and Section 7 "Constructi on and Startup." C. ASHRAE/IESNA 90.1 Compliance: Applicable requirements in ASHRAE/IESNA 90.1, Section 6 "Heating, Ventilatin g, and Air Conditioning." 1.3 COORDINATION A. Coordinate layout and installation of fancoil u nits and suspension system components with other construction that penetrates or is supported by ceilings, including light fixtures, HVAC equipment, firesuppressionsystem components, cable trays, and partition assemblies. 1.4 WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of condensing units that fail in materials or workmanship within specified warranty period. 1. Failures include, but are not limited to, the following: a. Compressor failure. b. Condenser coil leak. 2. Warranty Period: Five years from date of Substantial Completion. BEARDSLEY DESIGN ASSOCIATES CORNELL NCP FAN COIL UNITS STANDARD SPECIFICATIONS 23 82 19 – PAGE 2 OF 5 JUNE 29, 2012 1.5 EXTRA MATERIALS A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. FanCoilUnit Filters: Furnish two spare filter s for each filter installed. PART 2 PRODUCTS 2.1 MANUFACTURERS A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection: B. In the FanCoilUnit Schedule where titles below are column or row headings that introduce lists, the following requirements apply to product selection: 1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, manufacturers specified. 2. Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers specified. 3. BasisofDesign Product: The design for each fa ncoil unit is based on the product named. Subject to compliance with requirements, provide either the named product or a comparable product by one of the other manufacturers specified. 2.2 FANCOIL UNITS A. Acceptable Manufacturers: 1. Carrier Corporation. 2. DunhamBush. 3. McQuay International. 4. Trane. 5. USA Coil & Air. 6. YORK International Corporation 7. ENVIROTEC B. Description: Factorypackaged and tested units rated according to ARI 440, ASHRAE 33, and UL 1995. C. Coil Section Insulation: 1inch (25mm) thick, coated glass fiber or foil covered, closedcell foam complying with ASTM C 107 1 and attached with adhesive complying with ASTM C 916. 1. FireHazard Classification: Insulation and adhe sive shall have a combined maximum flamespread index of 25 and smoke developed index of 50 when tested according to ASTM E 84. 2. Airstream Surfaces: Surfaces in contact with the airstream shall comply with requirements in ASHRAE 62.1. BEARDSLEY DESIGN ASSOCIATES CORNELL NCP FAN COIL UNITS STANDARD SPECIFICATIONS 23 82 19 – PAGE 3 OF 5 JUNE 29, 2012 D. Main and Auxiliary Drain Pans: Stainless steel. Fabricate pans and drain connections to comply with ASHRAE 62.1. E. Chassis: Galvanized steel where exposed to moisture. F. Cabinet: Steel with bakedenamel finish in manu facturer's standard paint color as selected by Architect. 1. Horizontal Unit Bottom Panels: Fastened to unit with cam fasteners and hinge and attached with safety chain; with integral stamped discharge grilles. G. Filters: Minimum arrestance according to ASHRAE 52.1, and a minimum efficiency reporting value (MERV) according to ASHRAE 52.2. 1. Pleated CottonPolyester Media: 90 percent arre stance and 7 MERV. H. Hydronic Coils: Copper tube, with mechanically bonded aluminum fins spaced no closer than 0.1 inch (2.5 mm), rated for a minimum working pressure of 200 psig (1378 kPa) and a maximum enteringwater temperature of 220 deg F (104 deg C). Include manual air vent and drain valve. I. Fan and Motor Board: Removable. 1. Fan: Forward curved, double width, centrifugal; directly connected to motor. Thermoplastic or paintedsteel wheels, and aluminum, painted steel, or galvanizedsteel fan scrolls. 2. Motor: Permanently lubricated, multispeed; resiliently mounted on motor board. 3. Wiring Termination: Connect motor to chassis wiring with plug connection. J. Factory, Hydronic Piping Package: ASTM B 88, Type L copper tube with wroughtcopper fittings and brazed joints. Label p iping to indicate service, inlet, and outlet. 1. Twoway, modulating control valve for chilledwa ter coil. 2. Hose Kits: Minimum 400psig (2758kPa) working pressure, and operating temperatures from 33 to 211 deg F. Tag hose kits to equipment designations. a. Length: 24 inches (600 mm) maximum. b. Minimum Diameter: Equal to fancoilunit connec tion size. 3. TwoPiece Ball Valves: Bronze body with fullpo rt, chromeplated bronze ball; PTFE or TFE seats; and 600psig (4140kPa) mi nimum CWP rating and blowoutproof stem. 4. CalibratedOrifice Balancing Valves: Bronze bod y, ball type; 125psig (860kPa) working pressure, 250deg F maximum operating temperature; with calibrated orifice or venturi, connections for portable differential pressure meter with integral seals, threaded ends, and equipped with a memory stop to retain set position. 5. Automatic FlowControl Valve: Brass or ferrous metal body; 300psig (2070kPa) working pressure at 250 deg F , with rem ovable, corrosion resistant, tamperproof, selfcleaning piston spring ; factory set to maintain BEARDSLEY DESIGN ASSOCIATES CORNELL NCP FAN COIL UNITS STANDARD SPECIFICATIONS 23 82 19 – PAGE 4 OF 5 JUNE 29, 2012 constant indicated flow with plus or minus 10 percent over differential pressure range of 2 to 80 psig (13.8 to 552 kPa). 6. YPattern Hydronic Strainers: Castiron body (A STM A 126, Class B); 125psig (860kPa) working pressure; with threaded connections, bolted cover, perforated stainlesssteel basket, and botto m drain connection. Include minimum NPS 1/2 hoseend, fullport, balltype blowdown valve in drain connection. 7. WroughtCopper Unions: ASME B16.22. 8. Risers: ASTM B 88, Type L copper pipe with hose and ball valve for system flushing. K. Basic Unit Controls: 1. Control voltage transformer. 2. Wallmounting thermostat with the following feat ures: a. Cooloff switch. b. Fan onauto switch. c. Fanspeed switch. d. Degree F indication. 3. Wallmounting temperature sensor. L. Electrical Connection: Factory wire motors and controls for a single electrical connection. PART 3 EXECUTION 3.1 EXAMINATION A. Examine areas to receive fancoil units for comp liance with requirements for installation tolerances and other conditions affecting performance. B. Examine roughingin for piping and electrical co nnections to verify actual locations before fancoilunit installation. C. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. Install fancoil units level and plumb. B. Install fancoil units to comply with NFPA 90A. C. Suspend fancoil units from structure with elast omeric hangers. Provide vibration isolator bushing or rubber in shear isolators. D. Verify locations of thermostats, and other exposed control sensors with Drawings and room details before installation. Install devices 60 inches (1525 mm) above finished floor. BEARDSLEY DESIGN ASSOCIATES CORNELL NCP FAN COIL UNITS STANDARD SPECIFICATIONS 23 82 19 – PAGE 5 OF 5 JUNE 29, 2012 E. Install new filters in each fancoil unit within two weeks after Substantial Completion. 3.3 CONNECTIONS A. Piping installation requirements are specified in other Division 23 Sections. Drawings indicate general arrangement of piping, fittings, and specialties. Specific connection requirements are as follows: 1. Install piping adjacent to machine to allow service and maintenance. 2. Connect piping to fancoilunit factory hydronic piping package. Install piping package if shipped loose. 3. Connect condensate drain to indirect waste. a. Install condensate trap of adequate depth to seal against the pressure of fan. Install cleanouts in piping at changes of direction. B. Connect wiring according to Division 26 Section "LowVoltage Electrical Power Conductors and Cables." 3.4 FIELD QUALITY CONTROL A. Manufacturer's Field Service: Engage a factory authorized service representative to inspect fieldassembled component s and equipment installation, including connections, and to assist in field testing. Report results in writing. B. Perform the following field tests and inspections and prepare test reports: 1. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation. 2. Operate electric heating elements through each stage to verify proper operation and electrical connections. 3. Test and adjust controls and safety devices. Replace damaged and malfunctioning controls and equipment. C. Remove and replace malfunctioning units and retest as specified above. 3.5 ADJUSTING A. Adjust initial temperature set points. B. Occupancy Adjustments: When requested within 12 months of date of Substantial Completion, provide onsite assistance in adjusting system to suit actual occupied conditions. Provide up to two visits to Project during other than normal occupancy hours for this purpose. 3.6 DEMONSTRATION A. Engage a factoryauthorized service representati ve to train Owner's maintenance personnel to adjust, operate, and maintain fancoil units. END OF SECTION 238219