EXISTING 1-5/8" U—TRACK MTL. CHANNELS (BEYOND) 12 GA. WIRE TIES SUSPENDED FROM STRUCT. ABOVE (ALL FOUR CORNERS) 2-1/2" MTL. FRAMING CHANNELS. SPAN BETWEEN EXISTING SUPPORTS (4—SIDES) 5/8" TYPE "X" GWB CONTINUOUS AROUND PERIMETER THREADED FASTENERS TO MTL. FRAMING EXISTING (RATED) CEILING ASSEMBLY. CEILING TILE ADHERED TO 1/2" GYPSUM BOARD NAILED TO 7/8" ALUM. V—GROOVE CHANNELS REMOVE AND REPLACE CEILING TILES AS REQUIRED FOR ACCESS PANEL INSTALLATION/RESTORATION ACCESS PANEL 2'-0" x 2-0" DOOR TYPICAL NOTE: SEE T2—xx.CA_CP DRAWINGS FOR ADDITIONAL LOCATIONS. PROVIDE ALL COSTS IN BASE BID. NEW ACCESS PANEL - EXISTING GWB CEILING Scale: NONE GENERAL NOTES 1. REFER TO DRAWING AMEP—GEN. J:\ PROJECTS—Ithaca\ 2011\ 11103 CORNELL — NCP\Stimson 201 1\CAD\ 11103-2011--AMEP.dwci SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED TO: ARCH El (30X42 IN.) r 9,Pin 1110 115 METRO PHONE: ‘ ARCHITECHNOLOGY, LLC www.archi-technology.com PARK ROCHESTER, NY 14623 585.424.1952 Fax: 585.424.4239 r—I 1-1 0 NI 1 __I < II II .__I U) ce UJ Z D 1 >--- Z z 0 < U) U Z < 1 (f) LLI cxZ U CLIENT: /Lig NETWORK 4. Cornell University CONNECTIVITY PROJECT z o CD 06/29/12 CONSTRUCTION DOCUMENTS 00 DD 100% DD SUBMISSION 50 DD 05/10/12 50% DD SUBMISSION 20 SD 1 1/09 1 20% SD SUBMISSION PSD 09/30/11 PRELIMINARY SD SUBMISSION MARK DATE DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/12 ‹b,0 14......10; .c,OF NEpy k op N. cz, 0 'i- a- $Y`..- 063153 N.0/ SIOWk AT PROJECT NO:11103-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL CHECKED BY: JLB PROJECT MANAGER: DPB SHEET TITLE: ARCHITECTURAL DETAILS A4 June 21, 2012 PLOT DATE MOTOR STARTER WITH ON—OFF—AUTOMATIC CONTROL SWITCH CHILLED WATER BOOSTER PUMP P-1 00CB - UP B06A B00CC 806 0 8088 00SF UP UP B10 BOOSE BOOCD UP L B00SB B03 UP BOOCC B10A B11 UP B00SA PANEL LPP-2, SPARE -1, VIA 2—#10 AWG WITH 1—#10 AWG GROUND IN 3/4" CONDUIT EXCAVATED AREA NO ROOMS EX. PANEL LPP-2 EX. PANEL LPP-1 PROVIDE 3—POLE 60A BREAKER AT POSITION 37-39-41. MOVE BRANCH CIRCUIT WIRING PRESENTLY LOCATED AT POSITION 37 TO POSITION 35. 165' -, BASEMENT - AMEP AREAS OF WORK 1 204 202 206A Scale: 1/16" = 1'-0" 206 201 201A 210B 21 OA 200CA 210C 210 216E ; 2160 216C 200CB 205 209 213 IIA 211 1M15 158' II 2.19C 6A 218 219 SECOND FLOOR - AMEP AREAS OF WORK 4 Scale: 1/16" = 1'-0" J1\PROJECTS—Ithaca\2011\11103 CORNELL — NCP \Stir' son 2011\CAD \11103-2011--T1—SZ,dwg UP N 004 G14B G14 EX. SMOKE DETECTOR 003A 018 025 G00CA G00UD 027 G24 DN 175' GROUND FLOOR - AMEP AREAS OF WORK Scale: 1/16" = 1'-0" THIRD FLOOR - AMEP AREAS OF WORK Scale: 1/16" = 1'-0" SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED T01 ARCH El (30X42 IN,) 101 107 103 104 105 106 100CD UP 100CE 118C 118B 100CA 118A 118 P 119 T 167' FIRST FLOOR - AMEP AREAS OF WORK Scale: 1/16" = 1'-0" ROOF ROOF 412 400CA 413 157' ROOF FOURTH FLOOR - AMEP AREAS OF WORK Scale: 1/16" = 1'-0" 1 `l`qA dime 115 METRO PHONE: 1TL_ ECHNOLOGY, www. arch i -technology. corn PARK ROCHESTER, NY 14623 585.424.1952 Fax: 585.424.4239 CORNELL UNIVERSITY STIMSON HALL - 2011 ITHACA, NY CLIENT: INN Illi. Cornell University PROJECT e NETWORK 11uu1 r CONNECTIVITY me, CD 06/29/ 12 CONSTRUCTION DOCUMENTS 100 DD 100% DD SUBMISSION 50 DD 05/10/12 50% DD SUBMISSION 20 SD 11/09/11 20% SD SUBMISSION PSD 09/30/11 PRELIMINARY SD SUBMISSION MARK DATE DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/12 G3 et e0,0 .*_OF NEW r~ 1 #i °63153 ��` RoF; , sioNP�� AT PROJECT NO: 11103-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL CHECKED BY: JLB PROJECT MANAGER: DPB SHEET TITLE: AMEP-AREAS OF WORK T1-AMEP 0 co0a- PLOT DATE: June 28, 2012 NETWORK CONNECTIVITY PR JECT TI PROJECT SITE PLAN N ALL •-• 2011 ROCKEFEL 201 111111111I', /21 OCI IBRARY 0 7A ANDREW DICKSON WHITE HOUSE 2006 PLATFORM OLIN UBRARY 2047 jSTIMSON HALL 111011 11. '7 2011 '141 TOWER ROAD PAVED PARKING PUS ST 2088 JAPROJECTS-Ithaca12011111103 CORNELL - NCP\Stimson 2011\CAD\11103-2011--T-COVER.dwg DRAWING INDEX DRAWING DESCRIPTION T -COVER DRAWING INDEX AND PROJECT SITE PLAN T -GEN STANDARD SYMBOLS, NOTES, ABBREVIATIONS (T -SERIES) Ti T1 -SZ TR SERVING ZONES, PLAN VIEWS AND BLDG. SEC I ION VIEW T1 -PL PATHWAYS LOGICAL RISER DIAGRAMS T1 -CL COPPER LOGICAL RISER DIAGRAMS Ti -FL FIBER LOGICAL RISER DIAGRAMS T2 T2-9.CA CP BASEMENT PATHWAYS AND CABLING T2-G.CA_CP GROUND FLOOR PATHWAYS AND CABLING T2-1 .CA_CP FIRST FLOOR PATHWAYS AND CABLING T2-2.CA CP SECOND FLOOR PATHWAYS AND CABLING T2-3.CA_CP THIRD FLOOR PATHWAYS AND CABLING T2-4.CA_CP FOURTH FLOOR PATHWAYS AND CABLING T3 T3 -GA MTR-GA ENLARGED PLANS AND ELEVATIONS AMEP AMEP-GEN GENERAL NOTES, SYMBOLS AND ABBREVIATIONS (AMEP SERIES) T1-AMEP AMEP-AREAS OF WORK AMEP-GA MTR-GA PARTIAL PLANS AND KEYNOTES A4 ARCHITECTURAL DETAILS M4 MECHANICAL DE I AILS E4 ELECTRICAL DETAILS SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED TO: ARCH El (30X42 IN.) of . 115.nrw mi pAIM limor ARCHI-TECHNOLOGY, LLC 1 www.archi-technology.com ROCHESTER, NY 14623 Fax: 585.424.4239 115 METRO PARK PHONE: 585.424.1952 II 1.1.1 I- CD _I < LJJ > Z __I Z ce U Z Z 0 ‹e V) U Z < I -- (f) CLIENT: -----------M,,,‘ 6- 0 , VI NETWORK . p Cornell University PROJECT -4 111111 ',r.-. CONNECTIVITY CD 06/29/12 CONSTRUCTION DOCUMENTS 100 DD 06/15/12 100% DD SUBMISSION 50 DD 05/10/12 50% DD SUBMISSION 20 SD 11/09/11 20% SD SUBMISSION PSD 09/30/11 PRELIMINARY SD SUBMISSION MARK DATE DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/12 0 AU , 4 ' ,,, 1,1 • , ' , a 4 01 -PI AT PROJECT NO: 11103-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL CHECKED BY: JLB PROJECT MANAGER: DPB SHEET TITLE: DRAWING INDEX AND PROJECT SITE PLAN T_COVER 4 PLOT BY: dbro LV 0 PLOT DATE: GENERAL PROJECT NOTES A. REFER TO A-, E-, AND M -SERIES DRAWINGS FOR AMEP SYMBOLS AND ABBREVIATIONS. B. REFER TO SPECIFICATION (SPEC) SECTION: DIVISION (DIV) 01 WORK UNDER CONTRACT. C. THIS INFORMATION REPRESENTS EXISTING CONDITIONS BASED ON ORIGINAL DRAWINGS AND OBSERVED SITE CONDITIONS. THE CONTRACTOR SHALL FIELD VERIFY EXACT ROUTING, DIMENSIONS AND QUANTITIES. THE CONTRACTOR SHALL DISCONNECT, REMOVE AND RECYCLE/DISPOSE OF ALL EXISTING CABLING AND DEVICES THAT ARE NOT SCHEDULED FOR REUSE. D. RACEWAY, CONDUIT, CABLING AND ELECTRICAL/MECHANICAL PATHS ARE SHOWN FOR REFERENCE ONLY. EACH CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND SHALL DETERMINE BEST PATHS FOR NEW INSTALLATION THAT WILL CAUSE THE LEAST DISTURBANCE TO OCCUPIED SURROUNDINGS AND BUILDING OPERATIONS (INCLUDING EVENING CLASSES). E EACH CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND PERFORM EXPLORATORY INVESTIGATIONS FOR CONCEALED CONDITIONS AS REQUIRED. EQUIPMENT LOCATIONS AND ROUTES ARE APPROXIMATE AND MINOR ADJUSTMENTS TO THE INSTALLATION WILL BE REQUIRED TO AVOID CONFLICTS WITH EXISTING EQUIPMENT, APPARATUS, AND OCCUPANTS' FURNITURE AND PERSONAL BELONGINGS. F ALL DRAWINGS ARE SCHEMATIC IN NATURE. THE CONTRACTOR SHALL PROVIDE OFFSETS, ENTRANCE END FITTINGS, RADIUS FITTINGS, HANGERS, ANCHORS, SUPPORT, WIRING AND ACCESSORIES NECESSARY FOR A COMPLETE, OPERATIONAL INSTALLATION. G. IT IS THE RESPONSIBILITY OF EACH CONTRACTOR TO COORDINATE WORK SHOWN ON THEIR CONTRACT DOCUMENTS WITH THE WORK OF OTHER TRADES PRIOR TO SCHEDULING, SHUTDOWN, DEMOLITION, FABRICATION OR INSTALLATION OF ANY WORK OR EQUIPMENT. EQUIPMENT OR DEVICES THAT CANNOT CHANGE LOCATION SHALL TAKE PRECEDENCE OVER THOSE THAT CAN CHANGE LOCATION. H. ALL TRADES AND CONTRACTS ARE RESPONSIBLE TO REVIEW SITE-SPECIFIC CLASSROOM SCHEDULING (DAILY AND WEEKLY), SPECIAL EVENTS/CONFERENCES, UNIVERSITY ACADEMIC CALENDARS, UNIVERSITY CLOSING AND HOLIDAYS. FACTOR WORK SCHEDULING AND MANPOWER LOADING IN SUCH A WAY SO AS TO MINIMIZE STUDENT AND STAFF DISRUPTIONS. PROVIDE SCHEDULES AND ONGOING PROGRESS REPORT SUBMITTALS FOR DEMOLITION AND NEW CONSTRUCTION AS CALLED FOR. REFER TO DIV 01 - SUBMITTAL PROCEDURES, AND DIV 01 - PROJECT MEETINGS SPECIFICATION SECTIONS. J. ALL TRADES AND CONTRACTS ARE RESPONSIBLE FOR THEIR OWN DEMOLITION, TEMPORARY FACILITIES, SAFETY PROGRAMS, PATCHING, PAINTING, FIRESTOP, TRASH REMOVAL/DISPOSAL, ROUTINE CLEANING, SPECIAL TELECOMMUNICATION ROOM CLEANING AND FINAL CLEANING, AS CALLED FOR. REFER TO SPEC SECTIONS IN DIV 01 THROUGH AND INCLUDING DIV 09 AS APPLICABLE. K. WHEN DRY CUTTING PLASTER, GYPSUM, CONCRETE MASONRY UNITS OR PLYWOOD - PROVIDE APPROPRIATE DUST AND NOISE CONTROL TEMPORARY PARTITIONS AND MAINTAIN EGRESS AND FIRE ALARM SYSTEM OPERATION. PROVIDE ZIP -WALL DUST BARRIERS OR OTHER APPROPRIATE PROTECTION TO LOCALIZE CLEANUP AND MINIMIZE THE EXTENTS OF FIRE ALARM SHUTDOWNS AND PREVENT FALSE FIRE ALARMS FOR SMALL SCALE CUTTING AND DEMOLITION. WHERE GENERAL CONSTRUCTION WILL CREATE DUST AND DEBRIS, THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR FURNITURE, FURNISHINGS AND EQUIPMENT. L. "ERL" ADJACENT TO A DEVICE, FIXTURE OR PIECE OF EQUIPMENT INDICATES AN EXISTING ITEM TO BE RELOCATED. DISCONNECT AND REMOVE THE ITEM. REMOVE ALL UNNECESSARY RACEWAY AND WIRING. REINSTALL AND RECONNECT ITEM AS REQUIRED. M. "ETR" ADJACENT TO A DEVICE, FIXTURE OR PIECE OF EQUIPMENT INDICATES EXISTING ITEM TO REMAIN. MAINTAIN EXISTING CONNECTIONS TO EQUIPMENT UNLESS NOTED OTHERWISE. N. PROVIDE QUALIFIED TRADES PERSON OR CONTRACTOR TO RESTORE FINISHED WALLS, CEILING AND FLOORS TO ORIGINAL CONDITION AS CALLED FOR IN DIV 01 - CUTTING AND PATCHING. 0. WHERE GENERAL CONSTRUCTION WILL CREATE DUST AND POTENTIAL FALSE SMOKE DETECTOR SIGNALS, THE CONTRACTOR SHALL COORDINATE FIRE ALARM SYSTEM SHUTDOWNS WITH CORNELL EH&S. VISIT SITE PRIOR TO SUBMITTING WRITTEN SHUTDOWN REPORT - TO CONFIRM EXISTING SMOKE DETECTOR LOCATION AND OWNERS' DEVICE/ZONE ADDRESS WITH RESPECT TO LOOK -AHEAD WORK SCHEDULE. REFER TO EXISTING FIRE ALARM DEVICE SCHEDULE, AS APPLICABLE. FALSE FIRE ALARMS CAUSED BY CONSTRUCTION DUST WILL NOT BE TOLERATED. CONTRACTORS ARE RESPONSIBLE TO PAY FOR ANY FINES IMPOSED BY ITHACA/CAYUGA HEIGHTS FIRE DEPARTMENT FOR UNNECESSARY FALSE FIRE ALARMS. P. RESTORE AND MAINTAIN AREA FIRE RESISTANCE RATING OF FLOOR AND WALLS. RESTORE AND MAINTAIN AREA SMOKE BARRIERS RATING OF WALLS AND SOFFITS WITH SIMILAR MATERIALS AS CALLED FOR IN DIV 01 - CUTTING AND PATCHING. ALSO REFER TO SPEC SECTION DIV 07 - PENETRATION FIRESTOPPING. Q. FIRESTOP ALL NEW AND EXISTING TELECOM WALL PENETRATIONS AND CONDUIT SLEEVES TO MAINTAIN AREA FIRE RESISTANCE RATING. R. MAINTAIN EXISTING SERVICES AT ALL TIMES DURING NORMAL BUILDING OPERATIONS. PROVIDE TEMPORARY SERVICES AS REQUIRED, OR AS DIRECTED. EXISTING DATA/COMMUNICATIONS CABLE AND OUTLETS SHALL REMAIN DURING THE INSTALLATION OF NEW CABLING AND DEVICES TO MINIMIZE DOWN TIME. COORDINATE CUTOVER TO NEW SYSTEM WITH PROJECT MANAGER. REFER TO SPEC SECTION 27 - COMMISSIONING. S. ALL TRADES AND CONTRACTS SHALL REPAIR DAMAGED CEILINGS (ANY TYPE), REPLACE LAY -IN CEILING TILES AND GRID WHERE NOTCHED OR DAMAGED FOR EXISTING REMOVALS OR NEW INSTALLATIONS, AS CALLED FOR IN DIV 01 - CUTTING AND PATCHING. REFER TO EXISTING CEILING SCHEDULE ON NEW WORK T2 DRAWINGS. T PROVIDE BLANK COVERS, FIRE SEAL, CUTTING, AND PATCHING AS REQUIRED TO REPAIR HOLES, UNPAINTED AREAS, OR OTHER PHYSICAL DEFECTS CAUSED BY THE REMOVAL AND INSTALLATION OF EQUIPMENT AND DEVICES. U. PROVIDE ELECTRONIC SUBMITTAL(S) ON ACTUAL PRODUCTS USED VIA PROJECT WEBSITE. INCLUDE COPY OF APPROVED SUBMITTAL WITH CLOSE-OUT DOCUMENTS (IN HARD COPY 0/M MANUAL), REFER TO SECTIONS: 01 33 00 - SUBMITTALS; 01 78 39 - RECORD DOCUMENTS; AND 01 77 00 - PROJECT CLOSEOUT AS APPLICABLE. V. DIVISION 27 CONTRACTOR SCOPE: FOR ALL EXISTING SR -4 RACEWAY, THOROUGHLY WIPE DIRT AND DUST FREE FROM ALL REUSED EXISTING SR -4 SERIES RACEWAYS, REMOVE METAL FILINGS FROM INSIDE RACEWAYS AT ALL CONDUIT CONNECTIONS. WHEN RACEWAY IS SHARED WITH ELECTRIC, PROVIDE/MAINTAIN METALLIC SEPARATION BARRIERS, PER NEC CODE. AT LOCATIONS WITH EXISTING ROUND MODULAR OR 4 -PRONG OUTLETS, REMOVE/REPLACE EXISTING SR -4 COVER WITH NEW DEVICE COVER TO CLOSE THE OPEN HOLE (AND PRIME AND PAINT TO MATCH). AT LOCATIONS WITH EXISTING OPENINGS IN EXISTING SR -4, REMOVE/REPLACE EXISTING SR -4 COVER WITH NEW DEVICE COVER TO CLOSE THE OPEN HOLE (AND PRIME AND PAINT TO MATCH). REPLACE EXISTING BENT/DAMAGED OR MISSING SR -4 COVERS (ASSUME 10' OF NEW COVER FOR EVERY 150' OF EXISTING RACEWAY, EVEN IF NOT SPECIFICALLY INDICATED ON THE DRAWINGS). W. CUTOVER OF ACTIVE BACKBONE SERVICES TO BE PERFORMED BY CIT FIELD SERVICES UNLESS OTHERWISE NOTED. END OF NOTES GENERAL REMOVAL NOTES A. AFTER VOICE/DATA CUTOVER, REMOVE EXISTING SURFACE MOUNTED COMMUNICATION OUTLETS AND ASSOCIATED CABLING UNLESS OTHERWISE NOTED TO REMAIN. PATCH AND PAINT AS CALLED FOR. PROVIDE BLANK COVER PLATE TO MATCH EXISTING AS REQUIRED. B. AFTER VOICE/DATA CUTOVER, AT EXISTING RECESSED COMMUNICATION OUTLETS PROVIDE BLANK COVER PLATE. REMOVE ALL ASSOCIATED CABLING IN ITS ENTIRETY. PROVIDE BLANK COVER PLATE ON ALL EXISTING UNUSED OPENINGS AS WELL. SURFACE FOR REUSE, REMOVE EXISTING COMMUNICATIONS I�11 /'. TI/'��� 1��+ �A!'•rl")1 T C` AND OLD C. WHEN EXISTING SURFACE RACEWAY IS CALLED TO REMAIN REUSE, COMMUNICATIONS 1 ACEI LAZES AND CABLING IN THEIR ENTIRETY, AFTER VOICE/DATA CUTOVER, AS CALLED FOR. PROVIDE BLANK PLATE OR REPLACEMENT COVER SECTIONS TO CONCEAL OPENINGS. D. RECYCLE REMOVED METALLIC COMPONENTS, RACEWAYS AND CABLING TO THE GREATEST EXTENT POSSIBLE. COORDINATE DUMPSTER LOCATION IN ADVANCE WITH THE PROJECT MANAGER. E. AFTER VOICE/DATA CUTOVER, REMOVE EXISTING CABLING BACK TO SOURCE. REMOVE ALL ASSOCIATED ANCHORS, TERMINAL BLOCKS, AND SPLICE CASES. COORDINATE THE CUTOVER OF ALL REMAINING SYSTEMS WITH THE PROJECT MANAGER. F AFTER VOICE/DATA CUTOVER, DISCONNECT AND REMOVE TERMINAL BLOCKS, ENCLOSURE, PLYWOOD BACKBOARD, AND ALL ASSOCIATED CABLING IN THEIR ENTIRETY. PRIOR TO REMOVAL, THE CONTRACTOR SHALL TEST ALL PAIRS FOR SERVICE. COORDINATE THE CUTOVER OF ALL REMAINING SYSTEMS WITH THE PROJECT MANAGER. PATCH AND PAINT WALLS TO MATCH EXISTING AREA IN CORRIDORS AND OFFICE AREAS. G. DISCONNECT AND REMOVE ALL EXISTING DEVICES/WIRING SHOWN FOR REMOVAL, BACK TO SOURCE. MAKE ALL CONNECTIONS NECESSARY TO MAINTAIN EXISTING SYSTEMS WHERE PARTIAL DEMOLITION IS REQUIRED DUE TO SCHEDULING. H. REPLACE CEILING TILES AND CEILING GRID, TO MATCH EXISTING, WHERE NOTCHED FOR EXISTING CONDUITS AND RACEWAYS THAT ARE CALLED TO BE REMOVED. END OF NOTES GENERAL NEW WORK NOTES A. CABLE TRAY, CONDUIT AND RACEWAY ROUTING SHOWN IS DIAGRAMMATIC ONLY. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS AND ROUTE PATHWAYS TO AVOID MECHANICAL AND STRUCTURAL CONFLICTS. NOT ALL REQUIRED JUNCTION BOXES AND OFFSETS ARE SHOWN, PROVIDE OFFSETS AND PULLBOXES AS REQUIRED. B. CONTRACTOR SHALL REMOVE AND REPLACE SPLINE CEILINGS TO ACCESS WORK AREAS AS INDICATED ON THE T2-x.CP_CA DRAWINGS. CONTRACTOR SHALL ALSO PROVIDE ACCESS PANELS AT ALL NEW PULLBOXES INSTALLED IN SPLINE CEILINGS. C. WHERE EXISTING PATHWAYS ARE TO REMAIN AND BE REUSED, THE CONTRACTOR SHALL RE -SUPPORT AND PROVIDE RADIUS FITTINGS AS NEEDED TO ENSURE COMPLIANCE WITH SPECIFICATIONS AND UNIVERSITY STANDARDS. D. A PULLBOX SHALL BE INSTALLED FOR RACEWAYS, SIZED AS INDICATED, IN RACEWAY INCREMENTS OF 100 FEET, AND WHEN THE ACCUMULATIVE BEND RADII IS EQUIVALENT TO 180 DEGREES. INSTALL CONDUITS THROUGH PULLBOXES ONLY AS DEPICTED ON STANDARD DETAILS, AND T2-x.CA_CP SERIES DRAWINGS. E. LOCATIONS OF PULLBOXES SHOWN ARE APPROXIMATE - PULLBOXES SHALL BE LOCATED IN AN AREA THAT IS READILY ACCESSIBLE. FIELD VERIFY THE EXACT LOCATIONS. F. THE USE OF CONDUIT BODIES (SMART LB'S) THAT HAVE BUILT-IN BEND RADIUS CONTROL DESIGNED FOR TELECOMMUNICATIONS APPLICATIONS ARE PERMITTED IN ALL COPPER, FIBER AND UTP RISER CONDUITS USED FOR TELECOMMUNICATIONS PATHWAYS. G. THE PULLING TENSION OF UTP CABLES SHALL NOT EXCEED 25 LBS PER CABLE. PROVIDE ADDITIONAL INSTALLERS AT CORNERS AND UTILIZE APPROVED LUBRICANT AS REQUIRED. H. COORDINATE THE ROUTING OF ALL PATHWAYS WITH EXISTING DUCT WORK, PIPING, ELECTRICAL CONDUITS, AND OTHER EXISTING OBSTRUCTIONS. I. PROVIDE ALL REQUIRED OFFSETS, FABRICATION AND FITTINGS REQUIRED FOR THE INSTALLATION OF CABLE TRAY, CONDUIT, SURFACE RACEWAY, AND CABLE RUNWAY. J. CABLE TRAY AND CONDUIT SHALL BE INSTALLED CONCEALED UNLESS OTHERWISE NOTED. K. PAINT EXPOSED CONDUITS, SUPPORTS, PULLBOXES, ETC. REFER TO DIV 09 - INTERIOR PAINTING. END OF NOTES GENERAL DRAWING NOTES -EXISTING CONDITIONS/REMOVALS- A. ITEMS SHOWN GRAYSCALE ARE EXISTING TO REMAIN UNLESS SPECIFIED OTHERWISE. B. ITEMS SHOWN DASHED -BOLD ARE TO BE REMOVED UNLESS SPECIFIED OTHERWISE. C. EXISTING CONDITIONS HAVE BEEN DOCUMENTED TO THE EXTENT POSSIBLE AT TIME OF SURVEY. TRUST BUT VERIFY ALL EXISTING CONDITIONS ARE AS INDICATED ON "T" SERIES DRAWINGS. REDLINE ON RECORD DRAWINGS ANY DEVIATIONS. END OF NOTES GENERAL DRAWING NOTES -HORIZONTAL CABLING - A. ITEMS SHOWN BOLD ARE NEW WORK UNLESS SPECIFIED OTHERWISE. B. ITEMS SHOWN IN GRAYSCALE ARE EXISTING TO REMAIN UNLESS SPECIFIED OTHERWISE. C. PROVIDE MANUFACTURER ENGINEERED SOLUTION FOR SMOKE AND FIRE STOPS. D. REFER TO DRAWINGS T1 -CL, T1 -FL, T3-xx, AND SPECIFICATIONS 27 13 00, 27 15 00, 27 05 00, 27 05 53 FOR ADDITIONAL REQUIREMENTS. E. PROVIDE CAT 6A CABLING FOR ALL OUTLETS LOCATIONS WITH A WAP OUTLET DESCRIPTOR. PROVIDE CAT 6 CABLING FOR ALL OTHER OUTLET LOCATIONS WITH NEW CABLING INDICATED. F. ALL NEW CAT 6 AND CAT 6A CABLING SHALL BE NON PLENUM CMR RATED. G. BACKBONE CABLING AND HORIZONTAL CABLING SHALL NOT OCCUPY THE SAME CONDUIT / CABLE TRAY UNLESS APPROVED BY OWNER. END OF NOTES GENERAL DRAWING NOTES -PATHWAYS- A. ITEMS SHOWN BOLD ARE NEW WORK UNLESS SPECIFIED OTHERWISE. B. ITEMS SHOWN IN GRAYSCALE ARE EXISTING TO REMAIN UNLESS SPECIFIED OTHERWISE. C. REFER TO DRAWINGS T2-x.CA_CP AND T1 -PL FOR HORIZONTAL PATHWAYS. D. REFER TO A-, M-, E -SERIES DRAWINGS FOR ADDITIONAL REQUIREMENTS. E. REFER TO T1 -PL DRAWING FOR ADDITIONAL REQUIREMENTS. F. PATCH/FIRESTOP ALL EXISTING AND NEW CONDUIT CABLE PENETRATIONS IN CORRIDOR WALLS. G. REMOVE LIGHTS AS REQUIRED TO ACCESS ABOVE CEILING LOCATIONS. REPORT ANY EXISTING DAMAGED OR NON -OPERATIONAL LIGHTS TO OWNER'S REPRESENTATIVE PRIOR TO LIGHT REMOVAL. H. EMT TO BE USED IN ALL NEW CONDUIT INSTALLATIONS IF POSSIBLE. FLEX CONDUIT TO BE USED AS LAST RESORT IF FIELD CONDITIONS PREVENT USE OF EMT. IF FLEX CONDUIT IS TO BE USED, IT SHALL BE INCREASED TO ONE TRADE SIZE LARGER THAN REQUIRED FOR EMT. I PROVIDE BUSHINGS FOR ALL CONDUIT ENDS INSIDE EXISTING & NEW PULLBOXES. J. RE -CONNECT ANY EXISTING CONDUIT BEING REUSED THAT HAS SEPARATED FROM FITTING. K. PERMANENT LABEL NEAT AND LEGIBLE, ALL NEW AND EXISTING PULLBOX COVERS WITH "COMMUNICATIONS ONLY". L. ALL NEW RACEWAY TO BE METALLIC UNLESS OTHERWISE NOTED. M. PROVIDE SPACE SAVER CONDUIT CONNECTORS IN NEW OUTLET BOXES, RACEWAYS AND PULLBOXES. REFER TO SECTION 27 05 28. N. WHERE INDICATED ON THE DRAWINGS, PAINT EXPOSED CONDUITS, SUPPORTS, PULLBOXES, ETC. WHERE INSTALLED IN FINISHED (PUBLIC) NON-MECHANICAL AREAS. REFER TO DIV 09, INTERIOR PAINTING. 0. ALL OUTLETS THAT ARE CALLED TO BE RECESS MOUNTED SHOULD BE IN A DOUBLE GANG BOX. ALL OUTLETS THAT ARE FED VIA SR -2 RACEWAY SHOULD BE ASSUMED TO BE SINGLE GANG SURFACE MOUNT OUTLET BOXES UNLESS OTHERWISE NOTED. P. FOR ALL EMERGENCY AND WALL PHONE LOCATIONS THAT CALL FOR SURFACE RACEWAYS ASSUME SR -7 AND ASSOCIATED FITTINGS. Q. ALL EXISTING AND NEW PATHWAYS THAT ARE 2" AND I ARGER,, AND I ONCER THAN 10' SHALL.. BE BONDED. R. ALL CABLE TRAYS SHALL BE ELECTRICALLY CONTINUOUS. COMMUNICATIONS PATHWAYS THAT END IN CLOSE PROXIMITY TO THE CABLE TRAY SHALL BE BONDED TO THE CABLE TRAY. S. ALL PATHWAYS TERMINATING IN THE MTR\ITR SHALL BE BONDED TO THE TMGB\TGB. T. CABLES SUPPORTED IN J HOOKS SHALL FOLLOW THE .) HOOK MANUFACTURERS REQUIREMENTS FOR MOUNTING, SPACING, AND FILL CAPACITY. U. COORDINATE ALL PENETRATIONS AND ANCHORS NEEDED IN PLASTER CEILINGS AND WALLS WITH ASBESTOS ABATEMENT CONTRACTOR. (ASBESTOS CONTRACTOR SHALL PROVIDE ALL PENETRATIONS AND ANCHORS IN PLASTER WALLS AND CEILINGS.) END OF NOTES ACCESS CONTROL SYMBOLS LEGEND CARD READER LOCK DOOR CONTACT (POSITION SWITCH) SRI SINGLE INPUT READER INTERFACE MODULE El DUAL INPUT READER INTERFACE MODULE INTELLIGENT SYSTEM CONTROLLER (CONTROL PANEL) PATHWAY SCHEDULE - NEW WORK ® CABLE FILL BASED ON CABLE OD G = 0.24 DESIGNATION DESCRIPTION MANUFACTURER PART NO. APPROXIMATE OUTSIDE DIMENSION APPROXIMATE INSIDE DIMENSION CABLE FILL CAPACITY* MIN. BEND RADIUS SUSPENDED GYPSUM CEILING .75" C = CONDUIT SEE SPEC. SECTION 27 05 28 .75" DIA. 4 4.5" CIT 1" C 1" DIA. 7 6" COMMUNICATIONS RISER RATED CABLE - NEC 1.25" C 1.25" DIA. 13 7.5" DEMARC 1.5" C 1.5" DIA. 18 9" DEPARTMENT OWNED AND MAINTAINED 2"C 2" DIA. 29 12" EM 2.5" C 2.5" DIA. 51 25" "ERL" ADJACENT TO A DEVICE, FIXTURE OR PIECE OF EQUIPMENT INDICATES AN EXISTING ITEM TO BE RELOCATED. DISCONNECT AND REMOVE THE ITEM. REMOVE ALL UNNECESSARY RACEWAY AND WIRING. REINSTALL AND RECONNECT ITEM AS REQUIRED. MAINTAIN SERVICES AS CALLED FOR. 3" C 3" DIA. 78 30" FACP 4" C 4" DIA. 130 40" FUME HOOD GWB GYPSUM WALL BOARD SR -1 NOT USED ITR INTERMEDIATE TELECOMMUNICATIONS ROOM SR -2 ** SURFACE RACEWAY SEE SPEC. SECTION 27 05 28 2400 SERIES SEE SPEC. SECTION 27 05 28 12 LS LIFE SAFETY SR -3 ** SURFACE RACEWAY 3000 SERIES 32 OFNR SR -4 ** SURFACE RACEWAY 4000 SERIES 63 PULL BOX SR -4D ** SURFACE RACEWAY (DIVIDED) 4000D SERIES 30 SM SR -5 ** SURFACE RACEWAY 5400 SERIES 32 PUBLIC TELEPHONE COMPANY (VERIZON) SR -6 ** SURFACE RACEWAY 6000 SERIES 140 TIA SR -6D ** SURFACE RACEWAY (DIVIDED) 6000D SERIES 63 TYPICAL SR -7 SURFACE RACEWAY 700 SERIES 2 UTP UNSHIELDED TWISTED PAIR VIF CT -A WIRE MESH TRAY SEE SPEC. SECTION 27 05 28 4"x6" 211 CT -B 2"x12" 211 CTC2"x18" 316 CT -D 2"x24" 419 CT -E 4"x12" 419 CT -F 4"x18" 632 CT -G ENCLOSED TRAY SEE SPEC. SECTION 27 05 28 4"x12" 419 CT -H UNUSED 4"x6" 211 CT -X ENCLOSED TRAY SEE SPEC. SECTION 27 05 28 6"X6" 316 CT -Y UNUSED 3"X12" 316 CT -Z 4"X12" 419 NOTES: O 40% MAXIMUM FILL FOR CATEGORY 6 INDICATED (PER TIA / EIA 569-A). - CAT6A CABLING HAS AN OD OF 0.285. - REDUCE FILL RATIO BY 6% FOR EACH 90° BEND - ENSURE THAT FILL RATIOS ARE NOT EXCEEDED = 3/4" CONDUIT SHALL ONLY BE ALLOWED AS SPECIFICALLY NOTED ON DRAWINGS. ** REDUCE CAPACITY BY 50% FOR THE FOLLOWING CONDITIONS: - WHEN CONNECTORS ARE MOUNTED WITHIN RACEWAY - WHEN NON -RADIUS FITTINGS RESTRICT CROSS-SECTIONAL AREA - WHEN RACEWAY IS DIVIDED AND SHARED WITH ELECTRIC ALTER EXISTING SURFACE RACEWAY TO PROVIDE AT LEAST TWO 16" SECTIONS OF REMOVABLE COVERS TO ALLOW CABLE ROUGH -IN WITHOUT CONFLICT WITH EXISTING FURNITURE CONFIGURATIONS. ALSO REFER TO GENERAL NOTE "Z" ON T -GEN DRAWING FOR ADDITIONAL SCOPE FOR SURFACE RACEWAYS. WHERE REQUIRED BY RACEWAY CAPACITY, OR AS DIRECTED, PROVIDE SURFACE MOUNT EXTENSION BOX ON EXISTING RACEWAY OPENING TO PROVIDE ADEQUATE CAPACITY AND BEND RADIUS. ALSO REFER TO RACEWAY DERATING REQUIREMENTS AT LEFT. WHERE REQUIRED BY RACEWAY CAPACITY, OR AS DIRECTED, PROVIDE RETROFIT ENTRANCE END FI I I ING OR ALTER EXISTING BACKFED CONDUIT WITH A NEW SPACE SAVER CONNECTOR TO PROVIDE ADEQUATE CAPACITY AND BEND RADIUS FOR NEW CABLING. ALSO REFER TO RACEWAY DERATING REQUIREMENTS AT LEFT. FIELD VERIFY EXISTING CONDITIONS AND PROPOSE ALTERATIONS THAT MINIMIZE SERVICE DISRUPTION DURATION. PROVIDE ALL TEMPORARY PROVISIONS TO MAINTAIN EXISTING SERVICES. CONDUIT AND CABLE TRAY TO BE ROUTED CONCEALED UNLESS OTHERWISE NOTED. CEILING SCHEDULE ® SUSPENDED LAY -IN CEILING 0 OPEN CEILING 0 SPLINE CEILING ® SUSPENDED PLASTER CEILING 0 SUSPENDED PLASTER CEILING 0 SUSPENDED GYPSUM CEILING ABBREVIATIONS ACM ASBESTOS CONTAMINATED MATERIAL AP ACCESS PANEL AHJ AUTHORITY HAVING JURISDICTION AWG AMERICAN WIRE GAUGE ARMM ARMORED RISER 24AWG MULTIPAIR CABLE BDF BUILDING DISTRIBUTION FRAME BICSI BUILDING INDUSTRY CONSULTING SERVICES INTERNATIONAL BSC BIO -SAFETY CABINET CCTV CLOSED CIRCUIT TELEVISION CIT CORNELL INFORMATION TECHNOLOGIES CMP COMMUNICATIONS PLENUM RATED CABLE - NEC CMR COMMUNICATIONS RISER RATED CABLE - NEC CTR CIT SUPPORTED EQUIPMENT CABINET WITH ZONE CABLING DDC DIRECT DIGITAL CONTROL SYSTEM DEMARC VERIZON DEMARCATION POINT DN DOWN DOM DEPARTMENT OWNED AND MAINTAINED EF ENTRANCE FACILITY EH&S ENVIRONMENTAL HEALTH AND SAFETY EM EMERGENCY PHONE EMS ENERGY MANAGEMENT SYSTEM ERL "ERL" ADJACENT TO A DEVICE, FIXTURE OR PIECE OF EQUIPMENT INDICATES AN EXISTING ITEM TO BE RELOCATED. DISCONNECT AND REMOVE THE ITEM. REMOVE ALL UNNECESSARY RACEWAY AND WIRING. REINSTALL AND RECONNECT ITEM AS REQUIRED. MAINTAIN SERVICES AS CALLED FOR. ETR "ETR" ADJACENT TO A DEVICE, FIXTURE OR PIECE OF EQUIPMENT INDICATES AN EXISTING ITEM TO REMAIN. MAINTAIN EXISTING CONNECTIONS TO EQUIPMENT UNLESS OTHERWISE NOTED. EV ELEVATOR PHONE FACP FIRE ALARM CONTROL PANEL FO/OF FIBER OPTIC / OPTICAL FIBER FH FUME HOOD GWB GYPSUM WALL BOARD IEEE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS ITR INTERMEDIATE TELECOMMUNICATIONS ROOM JB JUNCTION BOX LAN LOCAL AREA NETWORK LEC LOCAL EXCHANGE CARRIER / TELCO LS LIFE SAFETY MM MULTI -MODE OPTICAL FIBER MTR MAIN TELECOMMUNICATIONS ROOM OFNR OPTICAL FIBER NON-METALLIC STRENGTH RISER RATED OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION PB PULL BOX PP PATCH PANEL RAP REMOTEANNUNCIATION P..AN..EI_ SM SINGLE -MODE OPTICAL FIBER TC TELECOMMUNICATIONS CONTRACTOR TELCO PUBLIC TELEPHONE COMPANY (VERIZON) TGB TELECOMMUNICATION GROUND BUS BAR TMGB TELECOMMUNICATIONS MAIN GROUNDING BAR TIA TELECOMMUNICATION INDUSTRY ASSOCIATION TR TELECOMMUNICATIONS ROOM TYP TYPICAL UNO UNLESS NOTED OTHERWISE UPS UNINTERRUPTIBLE POWER SUPPLY UTP UNSHIELDED TWISTED PAIR VIF VERIFY IN FIELD VOM VERIZON OWNED AND MAINTAINED WAP WIRELESS ACCESS POINT TELECOM SYMBOLS LEGEND (REV. 02/12) DEMO EXISTING NEW DESCRIPTION IAI ® TELECOM OUTLET - FLOOR BOX T ® TELECOM OUTLET - CEILING MOUNTED <4 <-1 4111-1 TELECOM OUTLET - WALL MOUNTED CONDUITS - SIZE AS INDICATED -u- -J- J -HOOKS - WHERE INDICATED CONDUIT WITH BUSHINGS - TYPE & SIZE AS t INDICATED PULLBOX: X = SIZE: PBX PB -x PB x (S) SMALL, (M) MEDIUM, (L) LARGE LxWxH LxWxH LxWxH LxWxH = DIMENSIONS IN INCHES El CTR T EQUIPMENT CABINET WITH ZONE CABLING AAP] 21 ® ACCESS PANEL - CEILING MOUNT xsR-# ®sR-# sR-4 VERTICAL RACEWAY - DOWN (SR -2 UNO) HsR-# BsR-# : SR -IF VERTICAL RACEWAY - UP (SR -2 UNO) Mcr-x ►1CT-x ►Zlcr-x VERTICAL CABLE TRAY - DOWN I4cr-x HCT-X Bcr-x VERTICAL CABLE TRAY - UP • • • CONDUIT/SLEEVE - UP .:, 0 0 CONDUIT/SLEEVE - DOWN ii o 0 CONDUIT/SLEEVE - THRU (BETWEEN FLOORS) DESCRIPTION RACEWAY - SIZED PER PATHWAY ® i SR-# I ®SCHEDULE AT PROJECT NO: 11103-2011 SCHEDULE DRAWN BY: LP/EL HORIZONTAL CABLE TRAY - SIZED PER CT -X CT -X SHEET TITLE; STANDARD SYMBOLS, NOTES, ABBREVIATIONS (T -SERIES) T -GEN PATHWAY SCHEDULE Dal IIII 1111 CABLE RUNWAY T 1�1 SPLICE CASE P I is COMMUNICATIONS POWER POLE SERVING ZONE OR MTR/ITR BOUNDARY CTR SERVING ZONE BOUNDARY NEW / EXISTING OUTLET SUBSCRIPT KEY (REFER TO ADDITIONAL DESCRIPTORS THIS DRAWING) �xXzAi YY "A" ROOM LOCATION CODE "#" EXISTING OUTLET NOTE "xx" EXISTING PATHWAY TYPE TO BE REUSED "yy" OUTLET DESCRIPTOR "zz" NEW PATHWAY TYPE '!-R^ NEW PATHWAY TYPE KEY CC CONDUIT TO CEILING CF CONDUIT TO FLOOR CH CONDUIT TO HALL CL CONDUIT TO CLOSET CI CONDUIT HOMERUN TO ITR/MTR CP CONDUIT TO PULLBOX CT CONDUIT TO CABLE TRAY FW FISHABLE WALL JP J -HOOK TO PULLBOX JS J -HOOK TO SLEEVE JT J -HOOK TO CABLE TRAY PT PULLBOX TO CABLE TRAY SC SURFACE RACEWAY TO CEILING SF SURFACE RACEWAY TO FLOOR SH SURFACE RACEWAY TO HALL (RACEWAY THROUGH ROOM TO HALLWAY PRIMARY HORIZONTAL PATHWAY) SW SURFACE THROUGH WALL DOB NEW DEVICE OPENING IN EXISTING SURFACE RACEWAY, WITH BLANK PLATE (MATCH EXISTING COLOR) NOTE: PROVIDE MINIMUM 1" CONDUIT UNLESS NOTED OTHERWISE. INCREASE SIZE AS REQUIRED PER CABLE FILL CHART. NOTE: PROVIDE MINIMUM SIZE METALLIC RACEWAY BASED ON CABLE FILL CHART UNLESS NOTED OTHERWISE. NOTE: ASSUME PATHWAY TYPE "CP" UNLESS NOTED OTHERWISE. OUTLET DESCRIPTOR KEY ##" HEIGHT ABOVE FINISHED FLOOR (AFF) - EXAMPLE: 48" BAC BUILDING ACCESS CONTROLLER EM EMERGENCY TELEPHONE OUTLET EV ELEVATOR TELEPHONE LINE CONNECTION EMS ENERGY MANAGEMENT FACP FIRE ALARM CONTROL PANEL P WALL MOUNTED PAY -PHONE OUTLET W WALL MOUNTED TELEPHONE OUTLET TO BE MOUNTED AT 48" AFF WAP WIRELESS ACCESS POINT - REFER TO DETAIL AT -27052839. EXISTING OUTLET NOTE KEY A " EXISTING DEVICE OR OPENING WITH LEGACY CABLING. REMOVE CABLING, PAINT/PATCH OR PROVIDE BLANK AS APPLICABLE. z EXISTING ONE -GANG BOX AND PATHWAYS TO BE REUSED AS INDICATED. MAINTAIN EXISTING SERVICES UNTIL AFTER CUTOVER, THEN REMOVE CABLING. EXISTING 1WO-GANG BOX AND PATHWAYS TO BE REUSED AS INDICATED. MAINTAIN EXISTING SERVICES UNTIL AFTER CUTOVER, THEN REMOVE CABLING. EXISTING OUTLET LOCATION IN SURFACE RACEWAY. PATHWAYS TO BE REUSED AS INDICATED. MAINTAIN ANY EXISTING SERVICE UNTIL AFTER CUTOVER, THEN REMOVE CABLING. PROVIDE DEVICE BRACKETS AS REQUIRED. EXISTING PATHWAYS, BOXES, RACEWAYS AND CAT.5, CAT.5E OR CAT.6 CABLES TO REMAIN. EXISTING PATHWAYS, BOXES AND RACEWAYS TO REMAIN. COORDINATE SHUTDOWN AND CONDUIT/CABLE REWORK TO RELOCATE FROM EXISTING TR TO NEW TR PER T1 -PL, T1 -SZ AND APPENDIX A. REASSIGN CABLE PANEL/PORTS AS CALLED FOR. CABLING SYMBOLS LEGEND 2B -1O1 --Ai CABLE IDENTIFICATION LABEL: 2B COMMUNICATIONS EQUIPMENT ROOM 101 MASTER LOCATION CODE A ROOM LOCATION CODE 1 POSITION 1 J:\PROJECTS-Ithaca\2011\ 11103 CORNELL - NCP\Stimson 2011\ CAD\ 1 1 103-201 1--T-GEN.dwo SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED TO: ARCH El (30X42 IN.) was pi1 46A6 115 METRO PHONE: ARCHI-TECHNOLOGY, LLC www.archi-technology.com PARK ROCHESTER, NY 14623 585.424.1952 Fax: 585.424.4239 2011 ITHACA, NY CLIENT: — Cornell University CONNECTIVITY PROJECT NETWORK w, CD 06/29/12 CONSTRUCTION DOCUMENTS 100 DD 06/15/12 100% DD SUBMISSION 50 DD 05/10/12 50% DD SUBMISSION 20 SD 11/09/11 20% SD SUBMISSION PSD 09/30/11 PRELIMINARY SD SUBMISSION MARK DATE DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/12 s>5r � AT PROJECT NO: 11103-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL CHECKED BY: JLB PROJECT MANAGER: DPB SHEET TITLE; STANDARD SYMBOLS, NOTES, ABBREVIATIONS (T -SERIES) T -GEN PIPE PROVIDE ESCUTCHEON PLATES AT ALL PIPE PENETRATIONS EXPOSED TO VIEW, SIZE ESCUTCHEON AROUND INSULATION ON INSULATED PIPE AND AROUND PIPE ON UNISULATED PIPES NON -FIRE RATED WALL SLEEVE WHERE REQUIRED BY SPECIFICATIONS PIPE INSULATION - RUN INSULATION CONTINUOUS THROUGH WALL OPENING. PROVIDE 1" CLEARANCE ALL AROUND NON FIRE RATED WALL PIPE PENETRATION Scale: NONE PIPE PROVIDE ESCUTCHEON PLATES AT ALL PIPE PENETRATIONS EXPOSED TO VIEW. SIZE ESCUTCHEON AROUND INSULATION ON INSULATED PIPE AND AROUND PIPE ON UNISULATED PIPES v Nallimaser•-"ailL FIRE RATED WALL SLEEVE WHERE REQUIRED BY SPECIFICATIONS PIPE INSULATION - BUTT TIGHT TO FIRESTOPPING SYSTEM PROVIDE FIRESTOPPING SYSTEM PER SPECIFICATIONS FIRE RATED WALL PIPE PENETRATION UScale: NONE CONCRETE DECK EXPANSION SHIELDS CONCRETE ANCHORS NOTE: REFER TO SPECIFICATION FOR REQUIRED ANCHOR CONFIGURATION. WASHER (TYPICAL) EXPANSION NAILS CONCRETE ANCHOR DEVICE DETAIL Scale: NONE SHUTOFF VALVE CIRCUIT SL I I ER CHWS&R (ETR) BUILDING CHILLED WATER PUMPS (ETR) BOOS 808A P-1 SHUTOFF VALVE B10 BOOCD REFER TO DRAWING M4 FOR PUMP SCHEDULE. 1800C (�00SD BOOSA B00CC UP it N n 2047A 3/4" CHWS&R BOOUB 3/4" CHWS&R UP TO FCU -1 J:\PROJECTS—Ithaca\2011\11103 CORNELL — NCP\Stimson 2011\CAD\11103-2011--AMEP.dwq BASEMENT 2B - MECHANICAL - NEW WORK Scale: 1/4" = 1'-O" 0 2' 4' 8' { PROVIDE INSULATION SHIELD & INSERT FOR ALL PIPING HANGER RODS CHANNEL OR ANGLE SIDE VIEW TRAPEZE HANGER HANGER ROD INSULATION HANGER ROD INSULATION INSULATION SHIELD AT HANGER PROVIDE HIGH COMPRESSIVE STRENGTH INSUL INSERT BETWEEN PIPE & INSULATION SHIELD ADJUSTABLE CLEVIS HANGER WELD SADDLE ADJUSTABLE ROLLER HANGER NOTE: REFER TO PROJECT SPECIFICATION FOR ROD DIAMETER, END CONDITION (CLAMP, ANCHOR, ETC.) HANGER TYPES, AND CONFIGURATION. 4 I PIPE HANGER Scale: NONE FLOW BALANCING VALVE MANUAL AIR VENT MV STRAINER — ISOLATION VALVE (TYPICAL) AIR FLOW COIL PETE'S PLUGS (TYPICAL) UNION/FLANGE (TYPICAL) THERMOMETER (TYPICAL) f' DRAIN w/HOSE END NOTES: 1. PIPING TO ALLOW REMOVAL OF COIL WITHOUT REMOVING PIPING BEYOND UNIONS OR FLANGES. 2. FOR UNITS WITH MORE THAN ONE SECTION, PROVIDE FLOW BALANCER, UNIONS/FLANGES, FLEXIBLE CONNECTORS, DRAINS AND AIR VENTS FOR EACH COIL. TWO-WAY CONTROL VALVE COIL PIPING DETAIL Scale: NONE STRAINER ISOLATION - VALVE (TYPICAL) RETURN Ili -PRESSURE GAUGE (0#-100# PSI) 1/4" T -SUPPLY TRIPLE DUTY VALVE UNION (TYPICAL) CIRCULATING PUMP SCALES ON THIS DRAWING ACCURATE WHEN PLOIILD TO: ARCH El (30X42 IN.) INLINE PUMP DIAGRAM DETAIL 6� Scale: NONE GENERAL NOTES REFER TO DRAWING AMEP—GEN. COOLING COIL DRAIN SEE PLANS FOR CONTINUATION NOTE: L =INCH (MINIMUM) H =INCH PLUS THE TOTAL UNIT STATIC PRESSURE AT WORST CASE (LOADED FILTERS) UNDER POSITIVE PRESSURE COOLING COIL. DRAIN SEE PLANS FOR CONTINUATION —\ ‚N - CONNECT TO EXISTING COOLING COIL CONDENSATE DRAIN NOTE: L = H + J + PIPE DIAMETER H - 1 INCH FOR EACH INCH OF NEGATIVE PRESSURE* + 1 INCH J= CONNECT TO EXISTING COOLING COIL CONDENSATE DRAIN * NEGATIVE PRFSURE - UNIT RTATIG )RESS1:RE AT Wl1RgT CASE (LOADED FILTERS) MINUS EXTERNAL PRESSURE UNDER NEGATIVE PRESSURE TYPICAL COOLING COIL DRAIN Scale: NONE UNIT LOCATION AIRFLOW ELECTRICAL CHILLED WATER COIL PUMP HEAD (FT HD) MOTOR (WATTS) V PH FLA EDB EWB LDB LWB TOTALMBH SENSIBLEMBH EWT LWT GPM FLUIDPD MANUF/MAKE NOTES FCU -1 MTR-2BA 310 (62) 115 1 1.2 75 63 55 54 11 9 52 62 1.8 4.0 EMI WCP-15 1,2,3,4 05/10/12 50% DD SUBMISSION 20 SD 11/09/11 20% SD SUBMISSION PSD 09/30/11 PRELIMINARY SD SUBMISSION MARK DATE DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/12 NOTES: 1. PROVIDE UNIT MOUNTED CONTROLS. 2. PROVIDE WASHABLE FILTER. 3. PROVIDE CONDENSATE PUMP. 4. EWT = 52' F DURING WINTER MONTHS. EWT = 47' F DURING SUMMER MONTHS. NEW CHILLED WATER FAN COIL UNIT SCHEDULE Scale: NONE UNIT LOCATION SERVICE PUMP TYPE MEDIA PUMP HEAD (FT HD) PUMP FLOW (GPM) FLUID TEMP (F) MOTOR DATA DESIGN BASIS VOLT PH HP NOTES P-1 MECH. RM. ITR—GA BOOSTER PUMP CHILLED WATER 15 1.8 45 120 1 1/12 BELL & PL-3GO0SSETT _ CD 06/29 12 CONSTRUCTION DOCUMENTS 100 DD 100% DD SUBMISSION 50 DD NEW BOOSTER PUMP SCHEDULE Scale: NONE =xi RPARCHITECHNOLOGY, 115 METRO PHONE: LLC www.archi-technology.com PARK ROCHESTER, NY 14623 585.424.1952 Fax: 585.424.4239 STIMSON HALL - 2011 ITHACA, NY CLIENT: Cornell University CONNECTIVITY PROJECT (p gi NETWORK CD 06/29 12 CONSTRUCTION DOCUMENTS 100 DD 100% DD SUBMISSION 50 DD 05/10/12 50% DD SUBMISSION 20 SD 11/09/11 20% SD SUBMISSION PSD 09/30/11 PRELIMINARY SD SUBMISSION MARK DATE DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/12 co er �pRoF., ,c�oF NEw k -04' DN.CU0 t� X63153 s',oNP�� AT PROJECT NO: 11103-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL CHECKED BY: JLB PROJECT MANAGER: DPB SHEET TITLE: MECHANICAL DETAILS M4 J PH. C PH. B 3AN 3OAD SCH _E NAME LOCATION SOURCE NOTES: SE RATED HINGED TRIM Il COMPUTER GRADE 200% NEUTRAL FEED-THRU LUGS SUB FEED LUGS SUB -FEED BREAKER ❑ ISOLATED GND BUS RATING (AMPS) CP TRGA MTR-BA MCB 60A MLO PH/WIRE VOLTAGE MOUNTING KAIC DESIGN MAKE NEMA TYPE 3/4 120/208 SURFACE 22 CKT NO DESCRIPTION BREAKER 5 7 9 UPS REECEPTACLE RECEPTACLES 17 19 ACCESS CONTROL SYSTEM SPARE SPARE SPARE SPARE SPARE SPARE SPARE 23 SPARE SPARE 20/1 20/1 20/1 20/1 20/1 20/1 20/1 20/1 20/1 20/1 20/1 20/1 PH. A 1.8 KVA LOAD 0.7 KVA LOAD PH. A PH. B PH. C BREAKER DESCRIPTION CKT NO 1.8 20/1 UPS RECEPTACLE 2 0.2 20/1 ECU -1 4 20/1 SPARE 6 20/1 SPARE 8 20/1 SPARE 10 20/1 SPARE 12 20/1 SPARE 14 20/1 SPARE 16 20/1 SPARE 18 20/1 SPARE 20 20/1 SPARE 22 20/1 SPARE 24 ELECTRICAL PANELBOARD SCHEDULE FOURTH FLOOR THIRD FLOOR SECOND FLOOR FIRST FLOOR GROUND FLOOR BASEMENT ELECTRICAL CONSTRL CTION KEYED NOTES: E1 PROVIDE #6 AWG GROUNDING CONDUCTOR TO ANTI—STATIC FLOOR PIGTAIL. POWER & GROUNDING SYSTEM RISER DIAGRAM Scale: NONE FIXTURE LAMPS TYPE DESCRIPTION VOLTS MANUFACTURER & CATALOG NUMBER QTY. WATTS LAMP CODE REMARKS EM TWIN HEAD EMERGENCY LIGHTING UNIT 120/277 McPHILBEN CFX6 2 5 HALOGEN NOTES: 1. NOT USED. LIGHTING FIXTURE SCHEDULE Scale: NONE GB OR TGB LABEL 0 0 0 0 0 0 PROVIDE ENGRAVED TAG FOR EACH GROUNDING CONDUCTOR, BOTH ENDS AND AT EXPOSED PASS THROUGH MECHANICAL SPACES AND AT ENTRANCES/EXITS TO SHAFTWAYS, TYPICAL. DIV. 26 CONTRACTOR TO PROVIDE INSULATED TIN PLATED TELECOM SYSTEM GROUND BUS BAR. HOLE CENTERS TO MATCH LUG CONFIGURATION AND EIA/TIA 607 STANDARDS. REFER TO SECTIONS 260526 and 271100. TMGB — ERICO/ERITECH # TMGB—A20L27PT TGB — ERICO/ERITECH # TGB—A20L12PT INSULATORS. 5/8" LOCKWASHERS. WALL MOUNTING BRACKET. 5/8-11X1" H.H.C.S. BOLTS. DIV. 26 CONTRACTOR TO PROVIDE LONG BARREL COMPRESSION LUG, TWO BOLT, COMPRESSION LUG (BURNDY HYLUG YAZ SERIES) OR EQUAL. PROVIDE A MINIMUM OF EIGHT (8) SPARE LUGS WITH 5/16" HOLES FOR FUTURE USE BY OWNER. DRILL AND TAP AS REQUIRED. SCRUFF BAR AND PROVIDE ANTIOXIDANT AS CALLED FOR. REFER TO SECTIONS 260526 and 271100. TELECOMMUNICATIONS GROUND BAR (TMGB,TGB) DETAIL Scale: NONE GENERAL NOTES 1. REFER TO DRAWING AMEP—GEN. FOURTH FLOOR THIRD FLOOR SECOND FLOOR FIRST FLOOR GROUND FLOOR BASEMENT I J:\PROJECTS-Ithaca\2011\11103 CORNELL - NCP\Stimson 2011\CAD\11103-2011--AMEP.dwo SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED TO: ARCH El (30X42 IN.) Ell pip & 115 METRO PHONE: ARCHI-TECHNOLOGY, LLC www.archi-technology.com PARK ROCHESTER, NY 14623 585.424.1952 Fax: 585.424.4239 PROVIDE 60A/3P BREAKER AT POSITION 37-39-41. MOVE BRANCH CIRCUIT WIRING PRESENTLY LOCATED AT POSITION 37 TO POSITION 35. 1_, 1_, o J W z D z 1—#2 AWG IN o < U Z Q i- _ (I) ~ Ct o U CLIENT: Cornell University PROJECT 3/4"CONDUIT WITH 60A/3P PANEL CP 'PA CONNECTIVITY `` : - 6 AWG MTR—GA REAKER TRGA VIM ' .1 RM. G23 #6 AWG CD 06/29/12 CONSTRUCTION DOCUMENTS 100 DD 100% DD SUBMISSION 50 DD (4) #6 AWG WITH 50% DD SUBMISSION 20 SD 11/09/11 t PSD 09/30/11 (1) #8 AWG GROUND MARK DATE DESCRIPTION EX. ISSUE DATE: 06/29/12 ��;�pNDN.co��.p1- < �) '. . .OFNEwk '< ' IN 1" CONDUIT AT PROJECT NO: 11103-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL GROUND PROJECT MANAGER: DPB SHEET TITLE: ELECTRICAL DETAILS E4 ELECTRIC ROOM MDP EX. PANEL LPP-1 BOOUB ELECTRICAL CONSTRL CTION KEYED NOTES: E1 PROVIDE #6 AWG GROUNDING CONDUCTOR TO ANTI—STATIC FLOOR PIGTAIL. POWER & GROUNDING SYSTEM RISER DIAGRAM Scale: NONE FIXTURE LAMPS TYPE DESCRIPTION VOLTS MANUFACTURER & CATALOG NUMBER QTY. WATTS LAMP CODE REMARKS EM TWIN HEAD EMERGENCY LIGHTING UNIT 120/277 McPHILBEN CFX6 2 5 HALOGEN NOTES: 1. NOT USED. LIGHTING FIXTURE SCHEDULE Scale: NONE GB OR TGB LABEL 0 0 0 0 0 0 PROVIDE ENGRAVED TAG FOR EACH GROUNDING CONDUCTOR, BOTH ENDS AND AT EXPOSED PASS THROUGH MECHANICAL SPACES AND AT ENTRANCES/EXITS TO SHAFTWAYS, TYPICAL. DIV. 26 CONTRACTOR TO PROVIDE INSULATED TIN PLATED TELECOM SYSTEM GROUND BUS BAR. HOLE CENTERS TO MATCH LUG CONFIGURATION AND EIA/TIA 607 STANDARDS. REFER TO SECTIONS 260526 and 271100. TMGB — ERICO/ERITECH # TMGB—A20L27PT TGB — ERICO/ERITECH # TGB—A20L12PT INSULATORS. 5/8" LOCKWASHERS. WALL MOUNTING BRACKET. 5/8-11X1" H.H.C.S. BOLTS. DIV. 26 CONTRACTOR TO PROVIDE LONG BARREL COMPRESSION LUG, TWO BOLT, COMPRESSION LUG (BURNDY HYLUG YAZ SERIES) OR EQUAL. PROVIDE A MINIMUM OF EIGHT (8) SPARE LUGS WITH 5/16" HOLES FOR FUTURE USE BY OWNER. DRILL AND TAP AS REQUIRED. SCRUFF BAR AND PROVIDE ANTIOXIDANT AS CALLED FOR. REFER TO SECTIONS 260526 and 271100. TELECOMMUNICATIONS GROUND BAR (TMGB,TGB) DETAIL Scale: NONE GENERAL NOTES 1. REFER TO DRAWING AMEP—GEN. FOURTH FLOOR THIRD FLOOR SECOND FLOOR FIRST FLOOR GROUND FLOOR BASEMENT I J:\PROJECTS-Ithaca\2011\11103 CORNELL - NCP\Stimson 2011\CAD\11103-2011--AMEP.dwo SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED TO: ARCH El (30X42 IN.) Ell pip & 115 METRO PHONE: ARCHI-TECHNOLOGY, LLC www.archi-technology.com PARK ROCHESTER, NY 14623 585.424.1952 Fax: 585.424.4239 IIS 1_, 1_, o J W z D z J Q I > z z o < U Z Q i- _ (I) ~ Ct o U CLIENT: Cornell University PROJECT o' u0,8 8 NETWORK IMP 'PA CONNECTIVITY CD 06/29/12 CONSTRUCTION DOCUMENTS 100 DD 100% DD SUBMISSION 50 DD 05/10/12 50% DD SUBMISSION 20 SD 11/09/11 20% SD SUBMISSION PSD 09/30/11 PRELIMINARY SD SUBMISSION MARK DATE DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/12 ��;�pNDN.co��.p1- < . .OFNEwk '< ' 063153 V..1 <$' AT PROJECT NO: 11103-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL CHECKED BY: JLB PROJECT MANAGER: DPB SHEET TITLE: ELECTRICAL DETAILS E4 PLOT BY: pba 0 0 H- 0 a_ GENERAL NOTES FOR ALL TRADES: REFER TO DRAWING "T -GEN" FOR PROJECT NOTES AND ABBREVIATIONS APPLICABLE TO ALL DRAWINGS AND CONTRACTS. REFER TO TABLES ON THIS PAGE FOR DRAWING SYMBOLS AND ABBREVIATIONS PER TRADE. . REFER TO AMEP-xx DRAWINGS FOR GENERAL NOTES AND KEYED NOTES SPECIFIC TO TRADE. . THIS INFORMATION REPRESENTS EXISTING CONDITIONS BASED ON ORIGINAL DRAWINGS AND OBSERVED SITE CONDITIONS. NOT ALL ELECTRICAL/MECHANICAL EQUIPMENT IS SHOWN. THE CONTRACTOR SHALL FIELD VERIFY EXACT ROUTING, DIMENSIONS AND QUANTITIES. . REFER TO MECHANICAL, ELECTRICAL AND COMMUNICATION DRAWINGS FOR ADDITIONAL DEMOLITION AND RENOVATION WITHIN THE INDICATED WORK AREAS. . REFER TO T2-x.CA_CP DRAWINGS FOR CEILING ACCESS PANEL LOCATIONS. REFER TO DRAWING T3-xx DRAWINGS FOR ADDITIONAL COORDINATION REQUIREMENTS. . GENERAL CONSTRUCTION CONTRACTOR SHALL PERFORM ALL WORK AS SHOWN ON AMEP DRAWINGS, UNLESS NOTED OTHERWISE. REFER TO SPECIFICATIONS 011x00 FOR ADDITIONAL INFORMATION. . REFER TO THE PROJECT MANUAL/TECHNICAL SPECIFICATION SECTIONS FOR ADDITIONAL PRODUCT AND/OR EXECUTION REQUIREMENTS TO SUPPLEMENT INFORMATION CONTAINED ON THE DRAWINGS. . CUTTING AND PATCHING OF OPENINGS IN EXISTING BUILDING CONSTRUCTION SHALL BE DONE IN A MANNER WHICH DOES NOT IMPAIR THE STRUCTURAL INTEGRITY OF THE CONSTRUCTION AND MAINTAINS ALL REQUIRED FIRE RATINGS. PATCHING SHALL INCLUDE ALL OPENINGS LEFT IN EXISTING CONSTRUCTION DUE TO DEMOLITION WORK. ALL PATCHED SURFACES ARE TO BE RESTORED AS CLOSELY AS POSSIBLE TO THE ORIGINAL CONDITIONS. ALL PATCHED AREAS REQUIRING PAINT SHALL RECEIVE TWO PRIMER COATS AND TWO FINISH COATS. MATERIALS USED FOR PATCHING SHALL MATCH EXISTING ADJACENT MATERIALS IN BOTH TYPE AND QUALITY. NEW ELECTRICAL AND MECHANICAL SYSTEMS WHICH PENETRATE NEW AND EXISTING FIRE RATED FLOORS, WALLS AND OTHER ASSEMBLIES SHALL BE FIRESTOPPED. IN AREAS ACCESSIBLE TO THE PUBLIC, FIRESTOP SYSTEMS SHALL BE SELECTED, INSTALLED AND FINISHED TO THE QUALITY OF ADJACENT SURFACES OF BUILDING CONSTRUCTION BEING PENETRATED. REFER TO SPECIFICATION 078413 FOR ADDITIONAL INFORMATION. ALL PLAN DIMENSIONS ARE TO FACE OF PARTITION ASSEMBLY OR FINISH SURFACE (EXCLUDING PLYWOOD BACKBOARDS). . CONTRACTOR IS TO VERIFY ALL DRAWING DIMENSIONS IN THE FIELD FOR ACCURACY. . PROVIDE SOFT COPY SUBMITTAL(S) ON ACTUAL PRODUCTS USED. INCLUDE COPY OF APPROVED SUBMITTAL WITH CLOSE OUT DOCUMENTS (IN HARD COPY 0/M MANUAL), REFER TO SECTIONS: 013300 - SUBMITTALS; 017839 - RECORD DOCUMENTS; AND 017700 - PROJECT CLOSEOUT AS APPLICABLE. . ANY DRILLING, CUTTING ETC. WORK THAT MAY CREATE A NUISANCE FIRE ALARM, NEEDS TO BE SCHEDULED 24 HOURS IN ADVANCE WITH CUSTOMER SERVICE FOR A FIRE PROTECTION SYSTEM SHUTDOWN. SHUTDOWN WILL BE PERFORMED BY EH&S (ENVIRONMENTAL HEALTH AND SAFETY) STAFF. CONTRACTOR WILL NOT DISABLE ANY FIRE PROTECTION EQUIPMENT WITHOUT EH&S APPROVAL/ASSISTANCE. . ALL NEW SMOKE DETECTORS AND OTHER FIRE ALARM INITIATION/NOTIFICATION DEVICES WILL NEED TO BE TESTED BY EH&S AND AHJ (AUTHORITY HAVING JURISDICTION) FOR PROPER OPERATION OF DEVICE, DAMPER AND EXHAUST FAN SHUTDOWN. ARCHITECTURAL GENERAL NOTES: A. CLEAN ALL ROOMS DUST FREE FOLLOWING COMPLETION OF DEMOLITION AND PATCHING WORK. PROVIDE FIRESTOPPING IN ACCORDANCE WITH SPECIFICATION SECTION 078413 WHERE ITEMS (INCLUDING CABLE TRAYS, PIPES, CONDUIT, FRAMING MEMBERS AND DUCTS) PENETRATE BOTH NEW AND EXISTING FIRE RATED PARTITIONS. FIRE RATED PARTITIONS ARE INDICATED ON ARCHITECTURAL DRAWINGS. FOR SMOKE, FIRE, OR FIRE/SMOKE DAMPERS, TREAT PENETRATION IN ACCORDANCE WITH DAMPER MANUFACTURER'S PRINTED DIRECTIONS. USE OF FIRESTOPPING WILL INVALIDATE UL LISTING OF DAMPER. C. SEAL PENETRATIONS OF BOTH NEW AND EXISTING NON -RATED PARTITIONS INCLUDING CABLE TRAYS, PIPES, CONDUIT, FRAMING MEMBERS AND DUCTS. PROVIDE ELASTOMERIC SEALANT AT GYPSUM WALLBOARD PARTITIONS. PROVIDE MORTAR/GROUT FOR PIPES AND CONDUIT THROUGH MASONRY PARTITIONS. PROVIDE ELASTOMERIC SEALANT AT EXTERIOR WALLS. ( REMOVALS INDICATED AS DASHED LINES q) AIR FLOW ❑ O NEW WALL TYPE - REFER TO KEYED NOTES FOR CONSTRUCTION )CXXXXXXXXXY 0 -' ROOM NUMBER AFF ### DUPLEX RECEPTACLE OUTLET, 20 AMPERE, 120 VOLT, TOP OF BOX AT 24" AFF UNLESS OTHERWISE NOTED. NEW TO EXISTING CONNECTION LIGHTING FIXTURE, FLUORESCENT, CEILING MOUNTED, INDUSTRIAL/STRIP EXISTING DOOR TO REMAIN DUCT — DOWN — POSITIVE PRESSURE____64 DOUBLE DUPLEX RECEPTACLE OUTLET, 20 AMPERE, 120 VOLT, TOP OF BOX AT 24" AFF UNLESS OTHERWISE NOTED. iN DOOR NUMBER (NEW OR EXISTING) © A NEW DOOR AND FRAME 20 AMPERE, 277 VOLT, SINGLE POLE AC SWITCH, TOP OF BOX AT 48" AFF DEFINITION OF SUBSCRIPTS: 2 TWO POLE SWITCH 3 THREE WAY SWITCH 4 FOUR WAY SWITCH M FRACTIONAL HORSEPOWER, MANUAL MOTOR STARTER W/ THERMAL OVERLOADS abc LOWER CASE LETTER(S) SIGNIFY SWITCHING DESIGNATIONS, QUANTITY OF LETTERS EQUALS QUANTITY OF GANGED SWITCHES. AWG BRANCH CIRCUIT HOMERUN, SUBSCRIPT INDICATES PANELBOARD & CIRCUIT DESIGNATION, QUANTITY OF ARROWHEADS DENOTES QUANTITY OF BRANCH CIRCUITS. PROVIDE GREEN GROUND WIRE AND ONE NEUTRAL PER PHASE CONDUCTOR IN EACH CIRCUIT. PROTECT EACH CIRCUIT WITH A 20 AMPERE, 1—POLE OVERCURRENT DEVICE. UNLESS OTHERWISE INDICATED, MINIMUM WIRE SIZE SHALL BE #10 THHN. /---. PP1/3 INDICATES 2 -HOUR RATED FIRE SEPARATION sit I INDICATES 1 -HOUR RATED FIRE SEPARATION 0 CEILING ACCESS PANEL i AP ATV ATMOSPHERIC 2 } ARCHITECTURAL SYMBOLS LEGEND 1 Scale: NONE I -VAC GENERAL NOTES: A. VERIFY ALL EXISTING CONDITIONS. EQUIPMENT LOCATIONS SHOWN ARE APPROXIMATE AND MINOR ADJUSTMENTS TO THE INSTALLATION MAY BE REQUIRED TO AVOID CONFLICTS WITH EXISTING EQUIPMENT AND APPARATUS - EXISTING BRANCH CIRCUITS ARE FROM RECORD DRAWINGS, AND MAY VARY. B. FIELD VERIFY ALL EXISTING CONDITIONS AND DETERMINE THE BEST PATH FOR NEW INSTALLATIONS THAT WILL CAUSE THE LEAST DISTURBANCE TO OCCUPIED SURROUNDINGS. PATHWAYS THAT ARE ROUTED THROUGH MECHANICAL ROOMS, UTILITY ROOMS, STORAGE CLOSETS, ETC. ARE FAVORABLE TO DISTURBANCES IN OCCUPIED AREAS. C. INSTALL ALL EQUIPMENT IN STRICT CONFORMANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS AND RECOMMENDATIONS. D. COORDINATE THE WORK SHOWN ON THESE DRAWINGS WITH THE WORK OF ALL OTHER TRADES PRIOR TO THE FABRICATION OR INSTALLATION OF ANY WORK. EQUIPMENT AND DEVICES THAT CANNOT CHANGE LOCATION SHALL TAKE PRECEDENCE OVER THOSE THAT CAN CHANGE. E. THESE DRAWINGS ARE SCHEMATIC IN NATURE. PROVIDE ALL OFFSETS, HANGERS, ANCHORS, SUPPORTS, WIRING AND ACCESSORIES FOR A COMPLETE, OPERATIONAL INSTALLATION. F. WHERE CEILINGS ARE REMOVED TO ACCOMMODATE NEW TELECOM ROOMS, PROVIDE SUPPORT(S) FOR ALL REMAINING MECHANICAL PIPING, DUCTWORK, MISCELLANEOUS EQUIPMENT, ETC. NOT BEING REMOVED. ALL UNUSED EQUIPMENT & APPURTENANCES SHALL BE REMOVED AND PROPERLY DISPOSED OF. G. ALL EXISTING AND NEW PIPING, DUCTWORK, MECHANICAL EQUIPMENT IN TELECOM ROOMS SHALL BE CLEANED FREE OF DUST/DEBRIS AFTER WALL DEMOLITION AND AFTER WALL RECONSTRUCTION/PATCHING. MECHANICAL SYMBOLS LEGEND Scale: NONE ELECTRICAL GENERAL NOTES: A. VERIFY ALL EXISTING CONDITIONS. EQUIPMENT LOCATIONS SHOWN ARE APPROXIMATE AND MINOR ADJUSTMENTS TO THE INSTALLATION MAY BE REQUIRED TO AVOID CONFLICTS WITH EXISTING EQUIPMENT AND APPARATUS - EXISTING BRANCH CIRCUITS ARE FROM RECORD DRAWINGS, AND MAY VARY. FIELD VERIFY ALL EXISTING CONDITIONS AND SHALL DETERMINE THE BEST PATH FOR NEW INSTALLATIONS THAT WILL CAUSE THE LEAST DISTURBANCE TO OCCUPIED SURROUNDINGS. PATHWAYS THAT ARE ROUTED THROUGH MECHANICAL ROOMS, UTILITY ROOMS, STORAGE CLOSETS, ETC. ARE FAVORABLE TO DISTURBANCES IN OCCUPIED AREAS, ALL NEW LUMINAIRES SHALL BE INSTALLED AT A MINIMUM HEIGHT OF 9'-6" AFF UNLESS OTHERWISE NOTED. C. COORDINATE MOUNTING HEIGHT OF ALL NEW POWER OUTLETS WITH THE TELECOMMUNICATIONS SYSTEMS EQUIPMENT ELEVATION DRAWINGS/DETAILS. D. COORDINATE ALL REQUIRED POWER AND FIRE ALARM SHUTDOWNS WITH THE OWNER. PROVIDE MINIMUM 1 WEEK ADVANCE NOTICE. E. WHERE CEILINGS ARE REMOVED TO ACCOMMODATE NEW TELECOM ROOMS, PROVIDE SUPPORT(S) FOR ALL REMAINING ELECTRICAL CONDUITS, DEVICES, EQUIPMENT, ETC. NOT BEING REMOVED. ALL UNUSED EQUIPMENT SHALL BE REMOVED AND PROPERLY DISPOSED OF. F. ALL EXISTING AND NEW CONDUIT AND ELECTRICAL EQUIPMENT IN TELECOM ROOMS SHALL BE CLEANED FREE OF DUST/DEBRIS AFTER WALL DEMOLITION AND AFTER WALL RECONSTRUCTION/ PATCHING. G. PROVIDE GROUNDING IDENTIFICATION AS CALLED FOR. PROVIDE TAGS ON GROUND CONDUCTOR IN ALL SPACES AS DIRECTED AND SHOWN ON GROUNDING DETAIL. H. DURING CONSTRUCTION, PROVIDE HEAT DETECTORS IN TELECOM ROOMS. AT SUBSTANTIAL COMPLETION AND AFTER FINAL CLEANING, CHANGE HEAT DETECTOR TO SMOKE DETECTOR. I. ALL FIRE ALARM SYSTEM DEVICES SHALL BE TESTED BY EH&S AND AHJ FOR PROPER OPERATION OF DETECTOR, DAMPER, AND FAN SHUTDOWN. DUCT — UP — NEGATIVE PRESSURE q) AIR FLOW ❑ O PIPING SYMBOLS ACCU 0 -' g AFF ABOVE FINISH FLOOR DUPLEX RECEPTACLE OUTLET, 20 AMPERE, 120 VOLT, TOP OF BOX AT 24" AFF UNLESS OTHERWISE NOTED. NEW TO EXISTING CONNECTION LIGHTING FIXTURE, FLUORESCENT, CEILING MOUNTED, INDUSTRIAL/STRIP '." DUCT — DOWN — POSITIVE PRESSURE____64 DOUBLE DUPLEX RECEPTACLE OUTLET, 20 AMPERE, 120 VOLT, TOP OF BOX AT 24" AFF UNLESS OTHERWISE NOTED. AIR ..'<: © A AT 20 AMPERE, 277 VOLT, SINGLE POLE AC SWITCH, TOP OF BOX AT 48" AFF DEFINITION OF SUBSCRIPTS: 2 TWO POLE SWITCH 3 THREE WAY SWITCH 4 FOUR WAY SWITCH M FRACTIONAL HORSEPOWER, MANUAL MOTOR STARTER W/ THERMAL OVERLOADS abc LOWER CASE LETTER(S) SIGNIFY SWITCHING DESIGNATIONS, QUANTITY OF LETTERS EQUALS QUANTITY OF GANGED SWITCHES. AWG BRANCH CIRCUIT HOMERUN, SUBSCRIPT INDICATES PANELBOARD & CIRCUIT DESIGNATION, QUANTITY OF ARROWHEADS DENOTES QUANTITY OF BRANCH CIRCUITS. PROVIDE GREEN GROUND WIRE AND ONE NEUTRAL PER PHASE CONDUCTOR IN EACH CIRCUIT. PROTECT EACH CIRCUIT WITH A 20 AMPERE, 1—POLE OVERCURRENT DEVICE. UNLESS OTHERWISE INDICATED, MINIMUM WIRE SIZE SHALL BE #10 THHN. /---. PP1/3 DUCT — DOWN — NEGATIVE PRESSURE SMD VENT 0 CAPPED DUCT i © ATV ATMOSPHERIC O FIRE ALARM SYSTEM SMOKE DETECTOR CHWS POWER PANEL HD AIR CHWS&R PANEL DUCT — UP THRU ROOF — NEGATIVE PRESSURE CARD READER LOCK illji` ip CA COMPRESSED DN TGB DUCT TRANSITION FROM RECTANGULAR TO ROUND DRAWING DRAIN EXHAUST AIR EAT DUCT — UP THRU ROOF — POSITIVE PRESSURE il,; 1 � CD CONDENSATE EF CHILLED WATER RETURN EH&S DUCT — UP — POSITIVE PRESSURE EFF SRI DUCT TRANSITION FROM RECTANGULAR TO RECTANGULAR EMERGENCY TMGB CHWR ERL EXISTING TO BE RELOCATED SUPPLY & RETURN MOTOR STARTER ESP DUCT SIZE — FIRST FIGURE IS SIZE SHOWN CHWS&R CHILLED WATER EWB ENTERING WET BULB (F) CHWS CHILLED WATER SUPPLY rELBOW SQUARE THROAT RADIUS EXP — El DOOR CONTACT (POSITION SWITCH) FLEXIBLE CONNECTION FIRE ALARM COLD WATER FIRE ALARM CONTROL PANEL FCU DCW DOMESTIC FIRE DAMPER FLA FULL LOAD AMPS HOT WATER RETURN FEET PER MINUTE ACOUSTICALLY LINED DUCTWORK COMBINATION FIRE/SMOKE DAMPER FT OR ' FEET (OF HEAD) SQUARE TO ROUND BRANCH DUCT DHR DOMESTIC GALLONS PER MINUTE GYP GYPSUM BOARD HM HOLLOW METAL HP HORSEPOWER DHW DOMESTIC HOT WATER HWR HOT WATER RETURN FLEXIBLE DUCT HOT WATER SUPPLY HWS&R HOT WATER SUPPLY & RETURN IP NATURAL GAS G JUNCTION BOX KD HOT WATER RETURN -11.–"r1 VOLUME DAMPER HWR LEAVING AIR TEMPERATURE (F) LDB LEAVING DRY BULB LWB DUCT WYE LWT SUPPLY HWS HOT WATER MBH RECTANGULAR ELBOW WITH TURNING VANES MCA PIPING MCB MAIN CIRCUIT BREAKER OR SP SPRINKLER MINIMUM NC NORMALLY CLOSED NO NORMALLY OPEN 0 PIPING RISE r PREFINISHED PH PHASE PLAS i (--. RADIUS ELBOW (MIN R/W = 1.5) PT PIPING DROP PW PLYWOOD 0 RETURN AIR OS DIGITAL SENSOR RF RETURN FAN CAPPED PIPE REFRIGERANT LIQUID CEILING GRILLE (G) REGISTER (R) REFRIGERANT SUCTION RRT RUBBER REDUCER STRIP THRESHOLD SA SUPPLY AIR SC --ii-- OF FLUID FLOW O THERMOSTAT STAIN TO MATCH EXISTING DIRECTION TELECOMMUNICATIONS GROUNDING BUSBAR TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR TYP CEILING DIFFUSER (D) V PITCH PIPING DOWN OG THERMOSTAT OR SENSOR WITH GUARD VB H VCT DN VD 46 -SHUT OFF VALVE O SPRINKLER HEAD (CEILING) WOOD Vi SHUT OFF VALVE XFMR DOOR LOUVER OR UNDERCUT • SPRINKLER HEAD (ABOVE CEILING) --L /n1 PUMP ii'� OF DISCONNECT v R DUCT RISE IN ELEVATIONPOINT D DUCT DROP IN ELEVATION D MECHANICAL SYMBOLS LEGEND Scale: NONE ELECTRICAL GENERAL NOTES: A. VERIFY ALL EXISTING CONDITIONS. EQUIPMENT LOCATIONS SHOWN ARE APPROXIMATE AND MINOR ADJUSTMENTS TO THE INSTALLATION MAY BE REQUIRED TO AVOID CONFLICTS WITH EXISTING EQUIPMENT AND APPARATUS - EXISTING BRANCH CIRCUITS ARE FROM RECORD DRAWINGS, AND MAY VARY. FIELD VERIFY ALL EXISTING CONDITIONS AND SHALL DETERMINE THE BEST PATH FOR NEW INSTALLATIONS THAT WILL CAUSE THE LEAST DISTURBANCE TO OCCUPIED SURROUNDINGS. PATHWAYS THAT ARE ROUTED THROUGH MECHANICAL ROOMS, UTILITY ROOMS, STORAGE CLOSETS, ETC. ARE FAVORABLE TO DISTURBANCES IN OCCUPIED AREAS, ALL NEW LUMINAIRES SHALL BE INSTALLED AT A MINIMUM HEIGHT OF 9'-6" AFF UNLESS OTHERWISE NOTED. C. COORDINATE MOUNTING HEIGHT OF ALL NEW POWER OUTLETS WITH THE TELECOMMUNICATIONS SYSTEMS EQUIPMENT ELEVATION DRAWINGS/DETAILS. D. COORDINATE ALL REQUIRED POWER AND FIRE ALARM SHUTDOWNS WITH THE OWNER. PROVIDE MINIMUM 1 WEEK ADVANCE NOTICE. E. WHERE CEILINGS ARE REMOVED TO ACCOMMODATE NEW TELECOM ROOMS, PROVIDE SUPPORT(S) FOR ALL REMAINING ELECTRICAL CONDUITS, DEVICES, EQUIPMENT, ETC. NOT BEING REMOVED. ALL UNUSED EQUIPMENT SHALL BE REMOVED AND PROPERLY DISPOSED OF. F. ALL EXISTING AND NEW CONDUIT AND ELECTRICAL EQUIPMENT IN TELECOM ROOMS SHALL BE CLEANED FREE OF DUST/DEBRIS AFTER WALL DEMOLITION AND AFTER WALL RECONSTRUCTION/ PATCHING. G. PROVIDE GROUNDING IDENTIFICATION AS CALLED FOR. PROVIDE TAGS ON GROUND CONDUCTOR IN ALL SPACES AS DIRECTED AND SHOWN ON GROUNDING DETAIL. H. DURING CONSTRUCTION, PROVIDE HEAT DETECTORS IN TELECOM ROOMS. AT SUBSTANTIAL COMPLETION AND AFTER FINAL CLEANING, CHANGE HEAT DETECTOR TO SMOKE DETECTOR. I. ALL FIRE ALARM SYSTEM DEVICES SHALL BE TESTED BY EH&S AND AHJ FOR PROPER OPERATION OF DETECTOR, DAMPER, AND FAN SHUTDOWN. ELECTRICAL SYMBOLS LEGEND Scale: NONE ABBREVIATION LIGHTING FIXTURE, CEILING MOUNTED q) SINGLE RECEPTACLE OUTLET, 20 AMPERE DEDICATED U.P.S. CIRCUIT, 120 VOLT, TOP OF BOX AT 24" AFF SURFACE MOUNTED ON PLYWOOD UNLESS OTHERWISE NOTED. ❑ O AIR CONDITIONING ACCU LIGHTING FIXTURE, WALL MOUNT 4 9 g AFF ABOVE FINISH FLOOR DUPLEX RECEPTACLE OUTLET, 20 AMPERE, 120 VOLT, TOP OF BOX AT 24" AFF UNLESS OTHERWISE NOTED. I i LIGHTING FIXTURE, FLUORESCENT, CEILING MOUNTED, INDUSTRIAL/STRIP '." DOUBLE DUPLEX RECEPTACLE OUTLET, 20 AMPERE, 120 VOLT, TOP OF BOX AT 24" AFF UNLESS OTHERWISE NOTED. APD EM LIGHTING FIXTURE 1771 APPROXIMATELY AT 20 AMPERE, 277 VOLT, SINGLE POLE AC SWITCH, TOP OF BOX AT 48" AFF DEFINITION OF SUBSCRIPTS: 2 TWO POLE SWITCH 3 THREE WAY SWITCH 4 FOUR WAY SWITCH M FRACTIONAL HORSEPOWER, MANUAL MOTOR STARTER W/ THERMAL OVERLOADS abc LOWER CASE LETTER(S) SIGNIFY SWITCHING DESIGNATIONS, QUANTITY OF LETTERS EQUALS QUANTITY OF GANGED SWITCHES. AWG BRANCH CIRCUIT HOMERUN, SUBSCRIPT INDICATES PANELBOARD & CIRCUIT DESIGNATION, QUANTITY OF ARROWHEADS DENOTES QUANTITY OF BRANCH CIRCUITS. PROVIDE GREEN GROUND WIRE AND ONE NEUTRAL PER PHASE CONDUCTOR IN EACH CIRCUIT. PROTECT EACH CIRCUIT WITH A 20 AMPERE, 1—POLE OVERCURRENT DEVICE. UNLESS OTHERWISE INDICATED, MINIMUM WIRE SIZE SHALL BE #10 THHN. /---. PP1/3 BRITISH THERMAL UNIT SMD MOTION DETECTOR, WALL SWITCH TYPE 0 JUNCTION BOX, SURFACE MOUNT CFM CUBIC FEET PER MINUTE CONC DISCONNECT SWITCH O FIRE ALARM SYSTEM SMOKE DETECTOR CHWS POWER PANEL HD FIRE ALARM SYSTEM HEAT DETECTOR CHWS&R PANEL CRL CARD READER LOCK db TELECOMMUNICATIONS GROUNDING BUS BAR DIA, 0 CARD READER LOCK DN TGB DWG DRAWING CRL EXHAUST AIR EAT ENTERING AIR TEMPERATURE EDB ENTERING DRY BULB EER TELECOMMUNICATIONS MAIN GROUNDING BUS BAR EF EXHAUST FAN EH&S SINGLE INPUT READER INTERFACE MODULE EFF SRI EM EMERGENCY TMGB ENERGY MANAGEMENT SYSTEM ERL EXISTING TO BE RELOCATED ERM MOTOR STARTER ESP DUAL INPUT READER INTERFACE MODULE ETR EXISTING TO REMAIN EWB ENTERING WET BULB (F) DRI ENTERING WATER TEMPERATURE (F) EX./EXIST EXISTING EXP — El DOOR CONTACT (POSITION SWITCH) ELECTRICAL SYMBOLS LEGEND Scale: NONE ABBREVIATION DESCRIPTION A AMPERE AC AIR CONDITIONING ACCU AIR COOLED CONDENSING UNIT AD ACCESS DOOR AFF ABOVE FINISH FLOOR AHJ AUTHORITY HAVING JURISDICTION AHU AIR HANDLING UNIT AL ALUMINUM SILL APD AIR PRESSURE DROP " WG APPROX APPROXIMATELY AT ALUMINUM THRESHOLD AWG AMERICAN WIRE GAUGE BTU BRITISH THERMAL UNIT BOP BOTTOM OF PIPE BTUH BRITISH THERMAL UNITS PER HOUR CFM CUBIC FEET PER MINUTE CONC CONCRETE CMU CONCRETE MASONRY UNIT CHWS CHILLED WATER SUPPLY CHWR CHILLED WATER RETURN CHWS&R CHILLED WATER SUPPLY & RETURN CRL CARD READER LOCK db DRY BULB (F) DIA, 0 DIAMETER DN DOWN DWG DRAWING EA EXHAUST AIR EAT ENTERING AIR TEMPERATURE EDB ENTERING DRY BULB EER ENERGY EFFICIENCY RATIO EF EXHAUST FAN EH&S ENVIRONMENTAL HEALTH & SAFETY EFF EFFICIENCY EM EMERGENCY EMS ENERGY MANAGEMENT SYSTEM ERL EXISTING TO BE RELOCATED ERM EXISTING TO BE REMOVED ESP EXTERNAL STATIC PRESSURE ETR EXISTING TO REMAIN EWB ENTERING WET BULB (F) EWT ENTERING WATER TEMPERATURE (F) EX./EXIST EXISTING EXP EXPOSED 'F DEGREES FAHRENHEIT FA FIRE ALARM FACP FIRE ALARM CONTROL PANEL FCU FAN COIL UNIT FD FIRE DAMPER FLA FULL LOAD AMPS FPM FEET PER MINUTE FSD COMBINATION FIRE/SMOKE DAMPER FT OR ' FEET (OF HEAD) GC GENERAL CONSTRUCTION CONTRACTOR GPM GALLONS PER MINUTE GYP GYPSUM BOARD HM HOLLOW METAL HP HORSEPOWER HVAC HEATING, VENTILATION & AIR CONDITIONING HWR HOT WATER RETURN HWS HOT WATER SUPPLY HWS&R HOT WATER SUPPLY & RETURN IP INTERIOR PAINT JB JUNCTION BOX KD KNOCK -DOWN FRAME KW KILOWATTS LAT LEAVING AIR TEMPERATURE (F) LDB LEAVING DRY BULB LWB LEAVING WET BULB LWT LEAVING WATER TEMPERATURE (F) MAX MAXIMUM MBH THOUSAND BTUH MCA MINIMUM CIRCUIT AMPACITY MCB MAIN CIRCUIT BREAKER MDP MAIN DISTRIBUTION PANEL MIN MINIMUM NC NORMALLY CLOSED NO NORMALLY OPEN PD PRESSURE DROP PF PREFINISHED PH PHASE PLAS PLASTER PSI POUNDS PER SQUARE INCH PT PAINT TO MATCH EXISTING PW PLYWOOD RA RETURN AIR RB RUBBER BASE/SILL RF RETURN FAN RL REFRIGERANT LIQUID RS REFRIGERANT SUCTION RRT RUBBER REDUCER STRIP THRESHOLD SA SUPPLY AIR SC SEALED CONCRETE SRI SINGLE READER INTERFACE CARD READER ST STAIN TO MATCH EXISTING TGB TELECOMMUNICATIONS GROUNDING BUSBAR TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR TYP TYPICAL V VOLT VAV VARIABLE AIR VOLUME VB VINYL BASE VCT VINYL COMPOSITION TILE VD VOLUME DAMPER VEL VELOCITY WD WOOD WMP WIRE MESH PARTITION XFMR TRANSFORMER 1 ABBREVIATIONS Scale: NONE J:\PROJECTS-Ithaca\2011\11103 CORNELL - NCP\Stimson 2011\CAD\11103-2011 --AMEP-GEN.dwd SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED TO: ARCH El (30X42 IN.) teIWO F &� 115 PHONE: METRO � ARC H I -TECH N OLOGY, LLC www.archi-technology.com PARK ROCHESTER, NY 14623 585.424.1952 Fax: 585.424.4239 /16 I)BEARDSLEY DESIGN ASSOCIATES Architecture, Engineering, Landscape Architecture, P.C. Ph 315.478.6980 5789 Widewaters Parkway Fax 315.472.3523 Dewitt, New York 13214 1$ -mail BDAB*Beardsiey.csm T TI cD N J < z Z O <e �i cc1 U L Q to F- LLI / Z LLJ Z t O U CLIENT: Cornell University CONNECTIVITY PROJECT 00 ego, o NETWORK tI ii r a CD 06/29/12 CONSTRUCTION DOCUMENTS 100 DD 100% DD SUBMISSION 50 DD 05/10/12 50% DD SUBMISSION 20 SD 11/09/11 20% SD SUBMISSION PSD 09/30/11 PRELIMINARY SD SUBMISSION MARK DATE DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/12 .0-k4 <bp ,cOF NEW Y N. Co, ° I- 063153 2 iii..; c..;.' WV.' AT PROJECT NO: 11103-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL CHECKED BY: JLB PROJECT MANAGER: DPB SHEET TITLE: GENERAL NOTES, SYMBOLS AND ABBREVIATIONS (AMEP SERIES) AMEP-GEN June 21, 2012 PLOT DATE 8'-1 7/8" 11111111111110 I 11111•111111111 I 1111111111111111111 I G23 G16 GROUND FLOOR IDF (ROOM G23) ARCHITECTURAL - EXISTING / DEMO Scale: 1/4" = 1'-0" 0 2' 4' 8'-1 7/8" 1111111111.111111 I 511111.111111111 I I 2111111111111111 0111111111111111 I I 111111111111111 G23 G16 GROUND FLOOR MTR-GA (ROOM G23) ARCHITECTURAL - NEW WORK Scale: 1/4" = 1'-0" 0 2' 4' 8' ARCHITECTURAL - GENERAL NOTES & CONSTRUCTION <EYED NOTES: A. EXISTING CORRIDOR WALLS REQUIRE A 1—HOUR FIRE RATING PER THE BUILDING CODE OF NEW YORK STATE. FIRE RATING IS INDICATED ON FLOOR PLAN. B. REFER TO DRAWING A4 FOR DETAILS. Al REMOVE EXISTING CARPET. 0 INFILL EXISTING 2'-2" x 5'-9" WINDOW OPENING IN PARTITION WITH 2 1/2" 1 HOUR RATED SHAFTWALL ASSEMBLY. 5/8" GYPSUM WALLBOARD, 2 1/2" SHAFTWALL STUD, 1" GYPSUM UNER PANEL. PAINT NEW PARTITION TO MATCH EXISTING ON ITR ROOM SIDE. PAINT BACK SIDE OF EXISTING GLASS WITH BLACK PAINT. WINDOW TO REMAIN IN PLACE ON CORRIDOR SIDE. A3 PROVIDE ANTI—STATIC VINYL COMPOSITION TILE FLOOR AND RUBBER BASE. PROVIDE RUBBER TRANSITION STRIP AT EXPOSED EDGE UNDER DOOR. A4 PROVIDE 3/4" AC PLYWOOD ON WALLS INDICATED ON PLAN. PRIME AND PAINT WITH FIRE RETARDANT, LIGHT GREY PAINT ON ALL SURFACES AND EDGES. PLYWOOD TO BE 8 FEET HIGH AND MOUNTED 6 INCHES ABOVE FLOOR. SECURE TO WALL WITH COUNTERSUNK FASTENERS 24 INCHES ON CENTER MAXIMUM, EACH WAY. ANCHOR TO STUDS WITH SCREWS. ANCHOR TO CONCRETE OR MASONRY WITH EXPANSION ANCHORS. A5 PROVIDE DOOR SWEEP. FOR 1" GAP OR LESS PROVIDE PEMKO #293100CNB, FOR GREATER THAN 1" GAP PROVIDE PEMKO #18137CNB, CLEAR ANODIZED ALUMINUM WITH GREY NYLON BRUSH INSERT. A6 PROVIDE ROOM SIGNAGE TO MATCH EXISTING BUILDING SIGNAGE. SIGN TEXT AS DIRECTED. 0 PROVIDE DOOR HARDWARE FOR ELECTRIFIED CONNECTION TO ACCESS CONTROL SYSTEM: CARD READER LOCK SET: SARGENT HARMONEY LOCKSET, 8200 HARMONY SERIES H1, MATCH ADJACENT FINISH ACCOMMODATE 7 PIN INTERCHANGEABLE BEST CORE. MORTISE LOCK ALL LOCKS TO BE STOREROOM LOCKS (04) FAIL SECURE HARMONY LOCKSETS TO BE INSTALLED BY A CERTIFIED INSTALLER. KEEDEX PART NO. K—DL38A24 DOOR TO FRAME POWER TRANSFER FLEX CONDUIT. McKINNEY ELECTROLYNX RETROFIT CABLE FOR THE DOOR FRAME. SIZE 15'-2". STRIKES: PROVIDE WROUGHT BOXES AND STRIKES WITH PROPER LIP LENGTH TO PROTECT TRIM BUT NOT TO PROTECT MORE THAN 1/8" BEYOND TRIM, FRAME OR INACTIVE LEAF. WHERE REQUIRED, PROVIDE OPEN BACK STRIKE AND PROTECTED TO ALLOW PRACTICAL AND SECURE OPERATION. SARGENT ALUMINUM DOOR CLOSER: SERIES 351. FIRE RATED DOORS REQUIRE SARGENT FIRE RATED CLOSERS. FIRE RATED DOORS: ANYONE DRILLING OR CUTTING A FIRE RATED DOOR MUST BE CERTIFIED. ALL HARDWARE TO BE SATIN CHROME. (US26D) UNLESS NOTED OTHERWISE NOTE: REFER TO DRAWING A4 FOR DETAILS AND SCHEDULES AS APPLICABLE. DRAIN PIPE (ETR) \I - CHWS&R AND HWS&R (ETR) REMOVE EXHAUST FAN ON/OFF SWITCH. 7 TN REMOVE EX. HWS&R AND CHWS&R BACK TO POINT OF DISCONNECT AND CAP. REMOVE FLOOR MOUNTED FAN COIL UNIT AND ASSOCIATED PIPING. U G16j G23 GROUND FLOOR IDF (ROOM G23) MECHANICAL - EXISTING / REMOVALS Scale: 1/4" = 1'-0" LIGHT SWITCH (ETR) 0 2' 4' 8' E6 EXHAUST FAN E6 CONTROLLER EXHAUST FAN G16 GROUND FLOOR IDF (ROOM G23) ELECTRICAL - EXISTING / REMOVALS Scale: 1/4" = 1'-0" 0 2' 4' 8' J:\PROJECTS-Ithaca12011\11103 CORNELL - NCP\Stimson 20111CAD111103-2011--T3-G.dwg DRAIN PIPE (ETR) 7 ti CAPPED PIPES I CHWS&R ANC HWS&R (ETR) 3/4" CONDENSATE 22x8 (ETR) Cl 6 0239, FCU -1 3/4" CHWS&R ON GROUND FLOOR MTR-GA (ROOM G23) MECHANICAL - NEW WORK Scale: 1/4" = 1'-0" 0 2' LIGHT SWITCH (ETR) CP TRGA,3 4' 8' 0 DS G16 CP TRGA,4 PROVIDE NEW PANEL GROUND FLOOR MTR-GA (ROOM G23) 6, ELECTRICAL - NEW WORK Scale: 1/4" = 1'-0" 0 2' 4' 8' MIEMBEIMMIMMEMI -IVAC & SPRINKLER SYSTEM CONSTRUCTION KEYED NOTES: 0 REMOVE EXHAUST FAN AND ASSOCIATED SPEED CONTROLLER. CAP EX. 22x8 DUCT. 0 PROVIDE NEW HIGH SIDEWALL FAN COIL UNIT. PROVIDE MOUNTING BRACKET SPACER TO ALLOW FOR INSTALLATION OF CHWS&R AND CONDENSATE PIPING. REFER TO DRAWING M4 FOR UNIT SCHEDULE. 0 PROVIDE CAGES FOR SPRINKLERS. VOTE: REFER TO DRAWING M4 FOR DETAILS AND SCHEDULES AS APPLICABLE. ELECTRICAL CONSTRUCTION KEYED NOTES: E1 REMOVE EXISTING RECEPTACLES, CONDUCTORS AND SURFACE METAL RACEWAY TO FIRST ACCESSIBLE JUNCTION BOX. LABEL AND TAPE CONDUCTORS WITH NAME OF ABANDONED CIRCUIT. E2 RE—POSITION EX. LIGHT FIXTURE. E3 2-20A DUPLEX RECEPTACLES IN COMMON BOX, EACH FED FROM DIFFERENT CIRCUIT, AT 18" (UNLESS NOTED OTHERWISE). E4 PROVIDE CONVENIENCE OUTLETS AS INDICATED. PROVIDE (1) 20A/1 P BREAKER, WITH 3—#12 AWG CONDUCTORS, 3/4" CONDUIT. MOUNT AT 24" AFF UNLESS NOTED OTHERWISE. Ea PROVIDE (2) 20A/1 P BREAKERS, WITH 6—#10 AWG CONDUCTORS, AND 1" CONDUIT. E6 REMOVE EX. EXHAUST FAN, CONTROLS AND ASSOCIATED RACEWAY TO FIRST ACCESSIBLE JUNCTION BOX. TAPE AND LABEL CONDUCTORS WITH NAME OF ABANDONED CIRCUIT. E7 PROVIDE NEW TMGB PER DETAIL ON E4. E8 PROVIDE EM LIGHT, CONNECT TO UNSWITCHED LEG OF EXISTING LIGHTING CIRCUIT. E9 EXTEND EXISTING FIRE ALARM INITIATING CIRCUIT TO NEW SMOKE DETECTOR AND TO FIRE/SMOKE DAMPER. PROVIDE ALL SHUT DOWNS, TIE—INS AND VERIFICATIONS OF EXISTING ADDESSABLE SYSTEM TO MAKE SURE THE SYSTEM CAN SUPPORT NEW DEVICE(S). PROVIDE TESTING, REPROGRAMMING AND MODIFICATION TO EXISTING FIRE ALARM PANEL AND REMOTE ANNUNCIATORS TO SHOW NEW DEVICE(S). SMOKE DETECTOR SHALL BE INSTALLED AT HIGHEST POINT IN THE CEILING. REMOVE BRANCH CIRCUIT WIRING TO EX. FAN COIL UNIT. REMOVE CONDUCTORS AND RACEWAY TO FIRST ACCESSIBLE JUNCTION BOX. LABEL AND TAPE CONDUCTORS WITH NAME OF ABANDONED CIRCUIT. PROVIDE 2—#10 AWG WITH 1—#10 AWG GROUND FROM FAN COIL UNIT TO PUMP P-1 STARTER IN BASEMENT. CONNECT CONDUCTORS SO THAT WHEN FAN COIL UNIT AUXILIARY RELAY IS ENERGIZED, PUMP P-1 OPERATES WHEN STARTER IS IN AUTOMATIC. PROVIDE POWER CIRCUIT FOR ACCESS CONTROL INTERFACE MODULE / DOOR LOCK. NOTE: REFER TO DRAWING E4 FOR DETAILS AND SCHEDULES AS APPLICABLE. SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED TO: ARCH El (30X42 IN.) GENERAL NOTES: A. REFER TO DRAWING AMEP—GEN FOR GENERAL NOTES. REFER TO DRAWING T3—GA FOR ADDITIONAL COORDINATION REQUIREMENTS. KEY PLAN IMPARCHI-TECHNOLOGY, 115 METRO PHONE: LLC www.archi-technology.com PARK ROCHESTER, NY 14623 585.424.1952 Fax: 585.424.4239 STIMSON HALL - 2011 ITHACA, NY CLIENT: 0, d9RiIp Cornell University PROJECT • NETWORK CONNECTIVITY CD 06/29/12 CONSTRUCTION DOCUMENTS 100 DD 100% DD SUBMISSION 50 DD 05/10/12 50% DD SUBMISSION 20 SD 11/09/11 20% SD SUBMISSION PSD 09/30/11 PRELIMINARY SD SUBMISSION MARK DATE DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/12 co. tO'SY . .,oF NEW - .,,ot%0 N. c-kwU O <, p�'O ti SI©NPS 1p: AT PROJECT NO: 11103-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL CHECKED BY: JLB PROJECT MANAGER: DPB SHEET TITLE: MTR-GA PARTIAL PLANS AND KEYNOTES AMEP-GA a, L L a J a_ MOTOR STARTER WITH ON—OFF—AUTOMATIC CONTROL SWITCH CHILLED WATER BOOSTER PUMP P-1 1 a B00CB U 806A D B00CC B06 PANEL LPP-2, SPARE -1, VIA 2—#10 AWG WITH 1—#10 AWG GROUND IN 3/4" CONDUIT 808 B08B B08A UP E B00SF \yl UP B10 800SE BOOCD 800CE UP L B00SB V UP B00CC 803 BOOCA B05 801A B01 Li B07 B10A B11 B00SD U DN to 2047A UP ZOOSA Ot*.: BOOUB EXCAVATED AREA NO ROOMS EX. PANEL LPP-2 EX. PANEL LPP-1 PROVIDE 3—POLE 60A BREAKER AT POSITION 37-39-41. MOVE BRANCH CIRCUIT WIRING PRESENTLY LOCATED AT POSITION 37 TO POSITION 35. 0) 165' 204 202 206A BASEMENT - AMEP AREAS OF WORK Scale: 1/16" = 1'-0" 206 203 201 201A MINIM 20181 205 209 213 211 210B 210A 210C 200CA D 1111111111111 MEM 2005 J L UP 210 vL_ 1M15 210D 210E 158' 215 215A 216F 217 i 216E 2160 200CB CLOSET 219A 219B 219C T - 216C 216 216A 218 219 SECOND FLOOR - AMEP AREAS OF WORK Scale: 1/16" = 1'-0" UP 004 [01 G02 014B G14 ON BOOSB-3 GOOCA 005 EX. SMOKE DETECTOR B00SF BM 08 ON NEIN MUNN 111.1111 11111111 BM10 DN 800SE 7-1 4 2047A MTR—GA DN UP ` ON G00SD G24E G24B G24C 000CD G24D G24A G24 G00UC GOOUB G03 1 GO3A 001 UP \11-1 G00CC COOSA UP I MOM G15 G17 ON 175' All St —® G23 • 0'16 G18 GOOUA GOOCA 025 G00UD G27 ON UP 'venf6otion GROUND FLOOR - AMEP AREAS OF WORK Scale: 1/16" = 1'-0" THIRD FLOOR - AMEP AREAS OF WORK Scale: 1/16" = 1'-0" 71111111111 102 101 104 103 107 ■11111111111111 NNS OS 105 106 IUI III 100TB 0 41 0 100TA A \r... 1►� 100CD ON P 100SA 100CE 100SD 0M15 100CA 4N, 118C 118D 1188 100CB 116 118A 118 UP 1M15 119 167' FIRST FLOOR - AMEP AREAS OF WORK Scale: 1/16" = 1'-0" ROOF 412 ROOF • DN ON mom ENNIEN swag 111111•11 =as moo T= 400CA 40008 400S 413 Axiom PAIIIMMW 157' ROOF FOURTH FLOOR - AMEP AREAS OF WORK Scale: 1/16" = 1'-0" J:\PROJECTS—Ithaca\2011\11103 CORNELL — NCP\Stirnson 2011\CAD\11103-2011--T1—SZidwg SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED TO: ARCH El (30X42 IN,) RP ARCHITECHNOLOGY, LLC www.archi-technoiogy.com 115 METRO PARK ROCHESTER, NY 14623 PHONE: 585.424.1952 Fax: 585.424.4239 z >4- 4(c' U I H 11111111111111111111111111111111 1111111111111 11111111111111111111111111111111 1111111111111 111111 100 DD 50DD 20 SD PSD MARK MI= 05/10/12 11/09/11 09/30/11 DATE CONSTRUCTION DOCU 100% DD SUBMISSION 50% DD SUBMISSION 20% SD SUBMISSION PRELIMINARY SD SUBMISSION DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/12 AT PROJECT NO: 11103-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL CHECKED BY: JLB PROJECT MANAGER: DPB SHEET TITLE: AMEP-AREAS OF WORK T1—AMEP PLOT BY: dbrow PLOT DATE: June 28, 2012 CO NI El..1 1,,,J R NETWORK CONNECTIVITY PR•JECT N ALL 11 T I PROJECT SITE PLAN GOL WIN SMITH HALL 2013 ROCKEFELL 201 at - man .141 111, OC I IBRARY 0 7A ANDREW DICKSON WHITE HOUSE 2006 IlllI Ill. PLATFORM OLIN LIBRARY 2047 TOWER ROAD PAVED PARKING PUS ST 2088 d DRAWING INDEX DRAWING DESCRIPTION T -COVER DRAWING INDEX AND PROJECT SITE PLAN T -GEN STANDARD SYMBOLS, NOTES, ABBREVIATIONS (T -SERIES) {s NI 1 __IJ < >-- Ti Ti -SZ Z Z TR SERVING ZONES, PLAN VIEWS AND BLDG. SECTION VIEW Ti -PL PATHWAYS LOGICAL RISER DIAGRAMS T1 -CL ®%WIr' rel COPPER LOGICAL RISER DIAGRAMS Tl -FL :1 FIBER LOGICAL RISER DIAGRAMS T2 T2-B.CA CP I BASEMENT PATHWAYS AND CABLING T2-G.CA CP GROUND FLOOR PATHWAYS AND CABLING T2-1.CA CP FIRST FLOOR PATHWAYS AND CABLING T2-2.CA_CP SECOND FLOOR PATHWAYS AND CABLING T2-3.CA_CP CD THIRD FLOOR PATHWAYS AND CABLING T2-4.CA_CP 100 DD FOURTH FLOOR PATHWAYS AND CABLING 100% DD SUBMISSION T3 T3 -GA 50% DD SUBMISSION MTR-GA ENLARGED PLANS AND ELEVATIONS 11/09/11 AMEP AMEP-GEN 09/30/11 GENERAL NOTES, SYMBOLS AND ABBREVIATIONS (AMEP SERIES) Tl-AMEP DATE AMEP-AREAS OF WORK AMEP-GA CONSTRUCTION DOCUMENTS MTR-GA PARTIAL PLANS AND KEYNOTES A4 ARCHITECTURAL DETAILS I M4 NO: 111.03-2011 MECHANICAL DtIAILS E4 DRAWN ELECTRICAL DETAILS J:\PROJECTS-Ithaca\2011\11103 CORNELL - NCP\Stimson 2011\CAD\11103-2011--T-COVER.dwg SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED TO: ARCH El (30X42 IN.) ism RPARCHITECHNOLOGY, 115 METRO PHONE: LLC www.archi-technolo9Y .corn PARK ROCHESTER, NY 14623 585.424.1952 Fax: 585.424.4239 1-1 {s NI 1 __IJ < >-- I I V) cc W > Z J J W Z oC 0 U Z Z 0 'Q cn U Z < F- (1) CLIENT: Cornell University PROJECT ®%WIr' rel � NETWORK :1 T z XV CONNECTIVITY CD 06/29/12 CONSTRUCTION DOCUMENTS 100 DD 06/15/12 100% DD SUBMISSION 50 DD 05/10/12 50% DD SUBMISSION 20 SD 11/09/11 20% SD SUBMISSION PSD 09/30/11 PRELIMINARY SD SUBMISSION MARK DATE DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/ 12 .�' .. 41 AT PROJECT NO: 111.03-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL CHECKED BY: JLB PROJECT MANAGER: DPB SHEET DRAWING AND TITLE: INDEX PROJECT SITE PLAN GENERAL PROJECT NOTES A. REFER TO A-, E-, AND M -SERIES DRAWINGS FOR AMEP SYMBOLS AND ABBREVIATIONS. B. REFER TO SPECIFICATION (SPEC) SECTION: DIVISION (DIV) 01 WORK UNDER CONTRACT. C. THIS INFORMATION REPRESENTS EXISTING CONDITIONS BASED ON ORIGINAL DRAWINGS AND OBSERVED SITE CONDITIONS. THE CONTRACTOR SHALL FIELD VERIFY EXACT ROUTING, DIMENSIONS AND QUANTITIES. THE CONTRACTOR SHALL DISCONNECT, REMOVE AND RECYCLE/DISPOSE OF ALL EXISTING CABLING AND DEVICES THAT ARE NOT SCHEDULED FOR REUSE. D. RACEWAY, CONDUIT, CABLING AND ELECTRICAL/MECHANICAL PATHS ARE SHOWN FOR REFERENCE ONLY. EACH CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND SHALL DETERMINE BEST PATHS FOR NEW INSTALLATION THAT WILL CAUSE THE LEAST DISTURBANCE TO OCCUPIED SURROUNDINGS AND BUILDING OPERATIONS (INCLUDING EVENING CLASSES). E. EACH CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND PERFORM EXPLORATORY INVESTIGATIONS FOR CONCEALED CONDITIONS AS REQUIRED. EQUIPMENT LOCATIONS AND ROUTES ARE APPROXIMATE AND MINOR ADJUSTMENTS TO THE INSTALLATION WILL BE REQUIRED TO AVOID CONFLICTS WITH EXISTING EQUIPMENT, APPARATUS, AND OCCUPANTS' FURNITURE AND PERSONAL BELONGINGS. F. ALL DRAWINGS ARE SCHEMATIC IN NATURE. THE CONTRACTOR SHALL PROVIDE OFFSETS, ENTRANCE END FITTINGS, RADIUS FITTINGS, HANGERS, ANCHORS, SUPPORT, WIRING AND ACCESSORIES NECESSARY FOR A COMPLETE, OPERATIONAL INSTALLATION. G. IT IS THE RESPONSIBILITY OF EACH CONTRACTOR TO COORDINATE WORK SHOWN ON THEIR CONTRACT DOCUMENTS WITH THE WORK OF OTHER TRADES PRIOR TO SCHEDULING, SHUTDOWN, DEMOLITION, FABRICATION OR INSTALLATION OF ANY WORK OR EQUIPMENT. EQUIPMENT OR DEVICES THAT CANNOT CHANGE LOCATION SHALL TAKE PRECEDENCE OVER THOSE THAT CAN CHANGE LOCATION. H. ALL TRADES AND CONTRACTS ARE RESPONSIBLE TO REVIEW SITE-SPECIFIC CLASSROOM SCHEDULING (DAILY AND WEEKLY), SPECIAL EVENTS/CONFERENCES, UNIVERSITY ACADEMIC CALENDARS, UNIVERSITY CLOSING AND HOLIDAYS. FACTOR WORK SCHEDULING AND MANPOWER LOADING IN SUCH A WAY SO AS TO MINIMIZE STUDENT AND STAFF DISRUPTIONS. I. PROVIDE SCHEDULES AND ONGOING PROGRESS REPORT SUBMITTALS FOR DEMOLITION AND NEW CONSTRUCTION AS CALLED FOR. REFER TO DIV 01 - SUBMITTAL PROCEDURES, AND DIV 01 - PROJECT MEETINGS SPECIFICATION SECTIONS. J. ALL TRADES AND CONTRACTS ARE RESPONSIBLE FOR THEIR OWN DEMOLITION, TEMPORARY FACILITIES, SAFETY PROGRAMS, PATCHING, PAINTING, FIRESTOP, TRASH REMOVAL/DISPOSAL, ROUTINE CLEANING, SPECIAL TELECOMMUNICATION ROOM CLEANING AND FINAL CLEANING, AS CALLED FOR. REFER TO SPEC SECTIONS IN DIV 01 THROUGH AND INCLUDING DIV 09 AS APPLICABLE. K. WHEN DRY CUTTING PLASTER, GYPSUM, CONCRETE MASONRY UNITS OR PLYWOOD - PROVIDE APPROPRIATE DUST AND NOISE CONTROL TEMPORARY PARTITIONS AND MAINTAIN EGRESS AND FIRE ALARM SYSTEM OPERATION. PROVIDE ZIP -WALL DUST BARRIERS OR OTHER APPROPRIATE PROTECTION TO LOCALIZE CLEANUP AND MINIMIZE THE EXTENTS OF FIRE ALARM SHUTDOWNS AND PREVENT FALSE FIRE ALARMS FOR SMALL SCALE CUTTING AND DEMOLITION. WHERE GENERAL CONSTRUCTION WILL CREATE DUST AND DEBRIS, THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR FURNITURE, FURNISHINGS AND EQUIPMENT. L. "ERL" ADJACENT TO A DEVICE, FIXTURE OR PIECE OF EQUIPMENT INDICATES AN EXISTING ITEM TO BE RELOCATED. DISCONNECT AND REMOVE THE ITEM. REMOVE ALL UNNECESSARY RACEWAY AND WIRING. REINSTALL AND RECONNECT ITEM AS REQUIRED. M. "ETR" ADJACENT TO A DEVICE, FIXTURE OR PIECE OF EQUIPMENT INDICATES EXISTING ITEM TO REMAIN. MAINTAIN EXISTING CONNECTIONS TO EQUIPMENT UNLESS NOTED OTHERWISE. N. PROVIDE QUALIFIED TRADES PERSON OR CONTRACTOR TO RESTORE FINISHED WALLS, CEILING AND FLOORS TO ORIGINAL CONDITION AS CALLED FOR IN DIV 01 - CUTTING AND PATCHING. 0. WHERE GENERAL CONSTRUCTION WILL CREATE DUST AND POTENTIAL FALSE SMOKE DETECTOR SIGNALS, THE CONTRACTOR SHALL COORDINATE FIRE ALARM SYSTEM SHUTDOWNS WITH CORNELL EH&S. VISIT SITE PRIOR TO SUBMITTING WRITTEN SHUTDOWN REPORT - TO CONFIRM EXISTING SMOKE DETECTOR LOCATION AND OWNERS' DEVICE/ZONE ADDRESS WITH RESPECT TO LOOK -AHEAD WORK SCHEDULE. REFER TO EXISTING FIRE ALARM DEVICE SCHEDULE, AS APPLICABLE. FALSE FIRE ALARMS CAUSED BY CONSTRUCTION DUST WILL NOT BE TOLERATED. CONTRACTORS ARE RESPONSIBLE TO PAY FOR ANY FINES IMPOSED BY ITHACA/CAYUGA HEIGHTS FIRE DEPARTMENT FOR UNNECESSARY FALSE FIRE ALARMS. P. RESTORE AND MAINTAIN AREA FIRE RESISTANCE RATING OF FLOOR AND WALLS. RESTORE AND MAINTAIN AREA SMOKE BARRIERS RATING OF WALLS AND SOFFITS WITH SIMILAR MATERIALS AS CALLED FOR IN DIV 01 - CUTTING AND PATCHING. ALSO REFER TO SPEC SECTION DIV 07 - PENETRATION FIRESTOPPING. Q. FIRESTOP ALL NEW AND EXISTING TELECOM WALL PENETRATIONS AND CONDUIT SLEEVES TO MAINTAIN AREA FIRE RESISTANCE RATING. R. MAINTAIN EXISTING SERVICES AT ALL TIMES DURING NORMAL BUILDING OPERATIONS. PROVIDE TEMPORARY SERVICES AS REQUIRED, OR AS DIRECTED. EXISTING DATA/COMMUNICATIONS CABLE AND OUTLETS SHALL REMAIN DURING THE INSTALLATION OF NEW CABLING AND DEVICES TO MINIMIZE DOWN TIME. COORDINATE CUTOVER TO NEW SYSTEM WITH PROJECT MANAGER. REFER TO SPEC SECTION 27 - COMMISSIONING. S. ALL TRADES AND CONTRACTS SHALL REPAIR DAMAGED CEILINGS (ANY TYPE), REPLACE LAY -IN CEILING TILES AND GRID WHERE NOTCHED OR DAMAGED FOR EXISTING REMOVALS OR NEW INSTALLATIONS, AS CALLED FOR IN DIV 01 - CUTTING AND PATCHING. REFER TO EXISTING CEILING SCHEDULE ON NEW WORK T2 DRAWINGS. T. PROVIDE BLANK COVERS, FIRE SEAL, CUTTING, AND PATCHING AS REQUIRED TO REPAIR HOLES, UNPAINTED AREAS, OR OTHER PHYSICAL DEFECTS CAUSED BY THE REMOVAL AND INSTALLATION OF EQUIPMENT AND DEVICES. U. PROVIDE ELECTRONIC SUBMITTAL(S) ON ACTUAL PRODUCTS USED VIA PROJECT WEBSITE. INCLUDE COPY OF APPROVED SUBMITTAL WITH CLOSE-OUT DOCUMENTS (IN HARD COPY 0/M MANUAL), REFER TO SECTIONS: 01 33 00 - SUBMITTALS; 01 78 39 - RECORD DOCUMENTS; AND 01 77 00 - PROJECT CLOSEOUT AS APPLICABLE. V. DIVISION 27 CONTRACTOR SCOPE: FOR ALL EXISTING SR -4 RACEWAY, THOROUGHLY WIPE DIRT AND DUST FREE FROM ALL REUSED EXISTING SR -4 SERIES RACEWAYS, REMOVE METAL FILINGS FROM INSIDE RACEWAYS AT ALL CONDUIT CONNECTIONS. WHEN RACEWAY IS SHARED WITH ELECTRIC, PROVIDE/MAINTAIN METALLIC SEPARATION BARRIERS, PER NEC CODE. AT LOCATIONS WITH EXISTING ROUND MODULAR OR 4 -PRONG OUTLETS, REMOVE/REPLACE EXISTING SR -4 COVER WITH NEW DEVICE COVER TO CLOSE THE OPEN HOLE (AND PRIME AND PAINT TO MATCH). AT LOCATIONS WITH EXISTING OPENINGS IN EXISTING SR -4, REMOVE/REPLACE EXISTING SR -4 COVER WITH NEW DEVICE COVER TO CLOSE THE OPEN HOLE (AND PRIME AND PAINT TO MATCH). REPLACE EXISTING BENT/DAMAGED OR MISSING SR -4 COVERS (ASSUME 10' OF NEW COVER FOR EVERY 150' OF EXISTING RACEWAY, EVEN IF NOT SPECIFICALLY INDICATED ON THE DRAWINGS). W. CUTOVER OF ACTIVE BACKBONE SERVICES TO BE PERFORMED BY CIT FIELD SERVICES UNLESS OTHERWISE NOTED. END OF NOTES GENERAL REMOVAL NOTES A. AFTER VOICE/DATA CUTOVER, REMOVE EXISTING SURFACE MOUNTED COMMUNICATION OUTLETS AND ASSOCIATED CABLING UNLESS OTHERWISE NOTED TO REMAIN. PATCH AND PAINT AS CALLED FOR. PROVIDE BLANK COVER PLATE TO MATCH EXISTING AS REQUIRED. B. AFTER VOICE/DATA CUTOVER, AT EXISTING RECESSED COMMUNICATION OUTLETS PROVIDE BLANK COVER PLATE. REMOVE ALL ASSOCIATED CABLING IN ITS ENTIRETY. PROVIDE BLANK COVER PLATE ON ALL EXISTING UNUSED OPENINGS AS WELL. C. WHEN EXISTING SURFACE RACEWAY IS CALLED TO REMAIN FOR REUSE, REMOVE EXISTING XISri G COMMUNICAIONS FACEPLATES AND OLD CABLING IN THEIR ENTIRETY, AFTER VOICE/DATA CUTOVER, AS CALLED FOR. PROVIDE BLANK PLATE OR REPLACEMENT COVER SECTIONS TO CONCEAL OPENINGS. D. RECYCLE REMOVED METALLIC COMPONENTS, RACEWAYS AND CABLING TO THE GREATEST EXTENT POSSIBLE. COORDINATE DUMPSTER LOCATION IN ADVANCE WITH THE PROJECT MANAGER. E. AFTER VOICE/DATA CUTOVER, REMOVE EXISTING CABLING BACK TO SOURCE. REMOVE ALL ASSOCIATED ANCHORS, TERMINAL BLOCKS, AND SPLICE CASES. COORDINATE THE CUTOVER OF ALL REMAINING SYSTEMS WITH THE PROJECT MANAGER. F. AFTER VOICE/DATA CUTOVER, DISCONNECT AND REMOVE TERMINAL BLOCKS, ENCLOSURE, PLYWOOD BACKBOARD, AND ALL ASSOCIATED CABLING IN THEIR ENTIRETY. PRIOR TO REMOVAL, THE CONTRACTOR SHALL TEST ALL PAIRS FOR SERVICE. COORDINATE THE CUTOVER OF ALL REMAINING SYSTEMS WITH THE PROJECT MANAGER. PATCH AND PAINT WALLS TO MATCH EXISTING AREA IN CORRIDORS AND OFFICE AREAS. G. DISCONNECT AND REMOVE ALL EXISTING DEVICES/WIRING SHOWN FOR REMOVAL, BACK TO SOURCE. MAKE ALL CONNECTIONS NECESSARY TO MAINTAIN EXISTING SYSTEMS WHERE PARTIAL DEMOLITION IS REQUIRED DUE TO SCHEDULING. H. REPLACE CEILING TILES AND CEILING GRID, TO MATCH EXISTING, WHERE NOTCHED FOR EXISTING CONDUITS AND RACEWAYS THAT ARE CALLED TO BE REMOVED. END OF NOTES GENERAL NEW WORK NOTES A. CABLE TRAY, CONDUIT AND RACEWAY ROUTING SHOWN IS DIAGRAMMATIC ONLY. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS AND ROUTE PATHWAYS TO AVOID MECHANICAL AND STRUCTURAL CONFLICTS. NOT ALL REQUIRED JUNCTION BOXES AND OFFSETS ARE SHOWN, PROVIDE OFFSETS AND PULLBOXES AS REQUIRED. B. CONTRACTOR SHALL REMOVE AND REPLACE SPLINE CEILINGS TO ACCESS WORK AREAS AS INDICATED ON THE T2-x.CP_CA DRAWINGS. CONTRACTOR SHALL ALSO PROVIDE ACCESS PANELS AT ALL NEW PULLBOXES INSTALLED IN SPLINE CEILINGS. C. WHERE EXISTING PATHWAYS ARE TO REMAIN AND BE REUSED, THE CONTRACTOR SHALL RE -SUPPORT AND PROVIDE RADIUS FITTINGS AS NEEDED TO ENSURE COMPLIANCE WITH SPECIFICATIONS AND UNIVERSITY STANDARDS. D. A PULLBOX SHALL BE INSTALLED FOR RACEWAYS, SIZED AS INDICATED, IN RACEWAY INCREMENTS OF 100 FEET, AND WHEN THE ACCUMULATIVE BEND RADII IS EQUIVALENT TO 180 DEGREES. INSTALL CONDUITS THROUGH PULLBOXES ONLY AS DEPICTED ON STANDARD DETAILS, AND T2-x.CA_CP SERIES DRAWINGS. E. LOCATIONS OF PULLBOXES SHOWN ARE APPROXIMATE - PULLBOXES SHALL BE LOCATED IN AN AREA THAT IS READILY ACCESSIBLE. FIELD VERIFY THE EXACT LOCATIONS. F. THE USE OF CONDUIT BODIES (SMART LB'S) THAT HAVE BUILT-IN BEND RADIUS CONTROL DESIGNED FOR TELECOMMUNICATIONS APPLICATIONS ARE PERMITTED IN ALL COPPER, FIBER AND UTP RISER CONDUITS USED FOR TELECOMMUNICATIONS PATHWAYS. G. THE PULLING TENSION OF UTP CABLES SHALL NOT EXCEED 25 LBS PER CABLE. PROVIDE ADDITIONAL INSTALLERS AT CORNERS AND UTILIZE APPROVED LUBRICANT AS REQUIRED. H. COORDINATE THE ROUTING OF ALL PATHWAYS WITH EXISTING DUCT WORK, PIPING, ELECTRICAL CONDUITS, AND OTHER EXISTING OBSTRUCTIONS. I. PROVIDE ALL REQUIRED OFFSETS, FABRICATION AND FITTINGS REQUIRED FOR THE INSTALLATION OF CABLE TRAY, CONDUIT, SURFACE RACEWAY, AND CABLE RUNWAY. CABLE TRAY AND CONDUIT SHALL BE INSTALLED CONCEALED UNLESS OTHERWISE NOTED. PAINT EXPOSED CONDUITS, SUPPORTS, PULLBOXES, ETC. REFER TO DIV 09 - INTERIOR PAINTING. J. K. END OF NOTES GENERAL DRAWING NOTES -EXISTING CONDITIONS/REMOVALS- A. ITEMS SHOWN GRAYSCALE ARE EXISTING TO REMAIN UNLESS SPECIFIED OTHERWISE. B. ITEMS SHOWN DASHED -BOLD ARE TO BE REMOVED UNLESS SPECIFIED OTHERWISE. C. EXISTING CONDITIONS HAVE BEEN DOCUMENTED TO THE EXTENT POSSIBLE AT TIME OF SURVEY. TRUST BUT VERIFY ALL EXISTING CONDITIONS ARE AS INDICATED ON "T" SERIES DRAWINGS. REDLINE ON RECORD DRAWINGS ANY DEVIATIONS. END OF NOTES GENERAL DRAWING NOTES -HORIZONTAL CABLING - A. ITEMS SHOWN BOLD ARE NEW WORK UNLESS SPECIFIED OTHERWISE. B. ITEMS SHOWN IN GRAYSCALE ARE EXISTING TO REMAIN UNLESS SPECIFIED OTHERWISE. C. PROVIDE MANUFACTURER ENGINEERED SOLUTION FOR SMOKE AND FIRE STOPS. D. REFER TO DRAWINGS T1 -CL, T1 -FL, T3-xx, AND SPECIFICATIONS 27 13 00, 27 15 00, 27 05 00, 27 05 53 FOR ADDITIONAL REQUIREMENTS. E. PROVIDE CAT 6A CABLING FOR ALL OUTLETS LOCATIONS WITH A WAP OUTLET DESCRIPTOR. PROVIDE CAT 6 CABLING FOR ALL OTHER OUTLET LOCATIONS WITH NEW CABLING INDICATED. F. ALL NEW CAT 6 AND CAT 6A CABLING SHALL BE NON PLENUM CMR RATED. G. BACKBONE CABLING AND HORIZONTAL CABLING SHALL NOT OCCUPY THE SAME CONDUIT / CABLE TRAY UNLESS APPROVED BY OWNER. END OF NOTES GENERAL DRAWING NOTES -PATHWAYS- A. PATHWAYS - A. ITEMS SHOWN BOLD ARE NEW WORK UNLESS SPECIFIED OTHERWISE. B. ITEMS SHOWN IN GRAYSCALE ARE EXISTING TO REMAIN UNLESS SPECIFIED OTHERWISE. C. REFER TO DRAWINGS T2-x.CA_CP AND T1 -PL FOR HORIZONTAL PATHWAYS. D. REFER TO A-, M-, E -SERIES DRAWINGS FOR ADDITIONAL REQUIREMENTS. E. REFER TO T1 -PL DRAWING FOR ADDITIONAL REQUIREMENTS. F. PATCH/FIRESTOP ALL EXISTING AND NEW CONDUIT CABLE PENETRATIONS IN CORRIDOR WALLS. G. REMOVE LIGHTS AS REQUIRED TO ACCESS ABOVE CEILING LOCATIONS. REPORT ANY EXISTING DAMAGED OR NON -OPERATIONAL LIGHTS TO OWNER'S REPRESENTATIVE PRIOR TO LIGHT REMOVAL. H EMT TO BE USED IN ALL NEW CONDUIT INSTALLATIONS IF POSSIBLE. FLEX CONDUIT TO BE USED AS LAST RESORT IF FIELD CONDITIONS PREVENT USE OF EMT. IF FLEX CONDUIT IS TO BE USED, IT SHALL BE INCREASED TO ONE TRADE SIZE LARGER THAN REQUIRED FOR EMT. I. PROVIDE BUSHINGS FOR ALL CONDUIT ENDS INSIDE EXISTING & NEW PULLBOXES. J RE -CONNECT ANY EXISTING CONDUIT BEING REUSED THAT HAS SEPARATED FROM FITTING. K. PERMANENT LABEL NEAT AND LEGIBLE, ALL NEW AND EXISTING PULLBOX COVERS WITH "COMMUNICATIONS ONLY". L ALL NEW RACEWAY TO BE METALLIC UNLESS OTHERWISE NOTED. M. PROVIDE SPACE SAVER CONDUIT CONNECTORS IN NEW OUTLET BOXES, RACEWAYS AND PULLBOXES. REFER TO SECTION 27 05 28. N WHERE INDICATED ON THE DRAWINGS, PAINT EXPOSED CONDUITS, SUPPORTS, PULLBOXES, ETC. WHERE INSTALLED IN FINISHED (PUBLIC) NON-MECHANICAL AREAS. REFER TO DIV 09, INTERIOR PAINTING. 0. ALL OUTLETS THAT ARE CALLED TO BE RECESS MOUNTED SHOULD BE IN A DOUBLE GANG BOX. ALL OUTLETS THAT ARE FED VIA SR -2 RACEWAY SHOULD BE ASSUMED TO BE SINGLE GANG SURFACE MOUNT OUTLET BOXES UNLESS OTHERWISE NOTED. P. FOR ALL EMERGENCY AND WALL PHONE LOCATIONS THAT CALL FOR SURFACE RACEWAYS ASSUME SR -7 AND ASSOCIATED FITTINGS. Q. ALL EXISTING AND NEW PATHWAYS THAT ARE 2" AND I ARGER, AND I Nf 10' FR THAN SHALL BE BONDED. 0 R. ALL CABLE TRAYS SHALL BE ELECTRICALLY CONTINUOUS. COMMUNICATIONS PATHWAYS THAT END IN CLOSE PROXIMITY TO THE CABLE TRAY SHALL BE BONDED TO THE CABLE TRAY. S ALL PATHWAYS TERMINATING IN THE MTR\ITR SHALL BE BONDED TO THE TMGB\TGB. T CABLES SUPPORTED IN J HOOKS SHALL FOLLOW THE J HOOK MANUFACTURERS REQUIREMENTS FOR MOUNTING, SPACING, AND FILL CAPACITY. U. COORDINATE ALL PENETRATIONS AND ANCHORS NEEDED IN PLASTER CEILINGS AND WALLS WITH ASBESTOS ABATEMENT CONTRACTOR. (ASBESTOS CONTRACTOR SHALL PROVIDE ALL PENETRATIONS AND ANCHORS IN PLASTER WALLS AND CEILINGS.) END OF NOTES ACCESS CONTROL SYMBOLS LEGEND El CARD READER LOCK Ei DOOR CONTACT (POSITION SWITCH) SRI SINGLE INPUT READER INTERFACE MODULE DRI DUAL INPUT READER INTERFACE MODULE INTELLIGENT SYSTEM CONTROLLER (CONTROL PANEL) PATHWAY SCHEDULE - NEW WORK CABLE FILL BASED ON CABLE OD Q = 0.24 DESIGNATION DESCRIPTION MANUFACTURER PART NO. APPROXIMATE OUTSIDE DIMENSION APPROXIMATE INSIDE DIMENSION CABLE FILL CAPACITY* MIN. BEND RADIUS ,75" C = CONDUIT SEE SPEC. SECTION 27 05 28 .75" DIA. 4 4.5" 1" C 1" DIA. 7 6" 1.25" C 1.25" DIA. 13 7.5" 1.5" C 1.5" DIA. 18 9" 2" C 2" DIA. 29 12" 2.5" C 2.5" DIA. 51 25" 3" C 3" DIA. 78 30" 4" C 4" DIA. 130 40" ETR SR -1 NOT USED ELEVATOR PHONE SR -2 ** SURFACE RACEWAY SEE SPEC. SECTION 27 05 28 2400 SERIES SEE SPEC. SECTION 27 05 28 12 GWB SR -3 ** SURFACE RACEWAY 3000 SERIES 32 SR -4 ** SURFACE RACEWAY 4000 SERIES 63 SR -4D ** SURFACE RACEWAY (DIVIDED) 4000D SERIES 30 SR -5 ** SURFACE RACEWAY 5400 SERIES 32 SR -6 ** SURFACE RACEWAY 6000 SERIES 140 SR -6D ** SURFACE RACEWAY (DIVIDED) 6000D SERIES 63 SR -7 SURFACE RACEWAY 700 SERIES 2 SINGLE -MODE OPTICAL FIBER CTA MESH TRAY SEE SPEC. SECTION 27 05 28 4"x6" 211 TELECOMMUNICATION GROUND BUS BAR CT -B 2"x12" 211 CT-CWIRE 2"x18" 316 CT -D 2"x24" 419 CTE 4"x12" 419 CT -F 4"x18" 632 CT -G ENCLOSED TRAY SEE SPEC. SECTION 27 05 28 4"x12" 419 CT -H UNUSED 4"x6" 211 CT -X ENCLOSED TRAY SEE SPEC. SECTION 27 05 28 6"X6" 316 CT -Y UNUSED 3"X12" 316 CT -Z 4"X12" 419 NOTES: ' 40% MAXIMUM FILL FOR CATEGORY 6 INDICATED (PER TIA / EIA 569-A). - CAT6A CABLING HAS AN OD OF 0.285. - REDUCE FILL RATIO BY 6% FOR EACH 90° BEND - ENSURE THAT FILL RATIOS ARE NOT EXCEEDED 3/4" CONDUIT SHALL ONLY BE ALLOWED AS SPECIFICALLY NOTED ON DRAWINGS. ** REDUCE CAPACITY BY 50% FOR THE FOLLOWING CONDITIONS: - WHEN CONNECTORS ARE MOUNTED WITHIN RACEWAY - WHEN NON -RADIUS FITTINGS RESTRICT CROSS-SECTIONAL AREA - WHEN RACEWAY IS DIVIDED AND SHARED WITH ELECTRIC ALTER EXISTING SURFACE RACEWAY TO PROVIDE AT LEAST TWO 16" SECTIONS OF REMOVABLE COVERS TO ALLOW CABLE ROUGH -IN WITHOUT CONFLICT WITH EXISTING FURNITURE CONFIGURATIONS. ALSO REFER TO GENERAL NOTE "Z" ON T -GEN DRAWING FOR ADDITIONAL SCOPE FOR SURFACE RACEWAYS. WHERE REQUIRED BY RACEWAY CAPACITY, OR AS DIRECTED, PROVIDE SURFACE MOUNT EXTENSION BOX ON EXISTING RACEWAY OPENING TO PROVIDE ADEQUATE CAPACITY AND BEND RADIUS. ALSO REFER TO RACEWAY DERATING REQUIREMENTS AT LEFT. WHERE REQUIRED BY RACEWAY CAPACITY, OR AS DIRECTED, PROVIDE RETROFIT ENTRANCE END FI I i ING OR ALTER EXISTING BACKFED CONDUIT WITH A NEW SPACE SAVER CONNECTOR TO PROVIDE ADEQUATE CAPACITY AND BEND RADIUS FOR NEW CABLING. ALSO REFER TO RACEWAY DERATING REQUIREMENTS AT LEFT. FIELD VERIFY EXISTING CONDITIONS AND PROPOSE ALTERATIONS THAT MINIMIZE SERVICE DISRUPTION DURATION. PROVIDE ALL TEMPORARY PROVISIONS TO MAINTAIN EXISTING SERVICES. CONDUIT AND CABLE TRAY TO BE ROUTED CONCEALED UNLESS OTHERWISE NOTED. CEILING SCHEDULE OA SUSPENDED LAY -IN CEILING BO OPEN CEILING CO SPLINE CEILING OD SUSPENDED PLASTER CEILING O SUSPENDED PLASTER CEILING FO SUSPENDED GYPSUM CEILING ABBREVIATIONS ACM ASBESTOS CONTAMINATED MATERIAL AP ACCESS PANEL AHJ AUTHORITY HAVING JURISDICTION AWG AMERICAN WIRE GAUGE ARMM ARMORED RISER 24AWG MULTIPAIR CABLE BDF BUILDING DISTRIBUTION FRAME BICSI BUILDING INDUSTRY CONSULTING SERVICES INTERNATIONAL BSC BIO -SAFETY CABINET CCTV CLOSED CIRCUIT TELEVISION CIT CORNELL INFORMATION TECHNOLOGIES CMP COMMUNICATIONS PLENUM RATED CABLE - NEC CMR COMMUNICATIONS RISER RATED CABLE - NEC CTR CIT SUPPORTED EQUIPMENT CABINET WITH ZONE CABLING DDC DIRECT DIGITAL CONTROL SYSTEM DEMARC VERIZON DEMARCATION POINT DN DOWN DOM DEPARTMENT OWNED AND MAINTAINED EF ENTRANCE FACILITY EH&S ENVIRONMENTAL HEALTH AND SAFETY EM EMERGENCY PHONE EMS ENERGY MANAGEMENT SYSTEM ERL "ERL" ADJACENT TO A DEVICE, FIXTURE OR PIECE OF EQUIPMENT INDICATES AN EXISTING ITEM TO BE RELOCATED. DISCONNECT AND REMOVE THE ITEM. REMOVE ALL UNNECESSARY RACEWAY AND WIRING. REINSTALL AND RECONNECT ITEM AS REQUIRED. MAINTAIN SERVICES AS CALLED FOR. ETR "ETR" ADJACENT TO A DEVICE, FIXTURE OR PIECE OF EQUIPMENT INDICATES AN EXISTING ITEM TO REMAIN. MAINTAIN EXISTING CONNECTIONS TO EQUIPMENT UNLESS OTHERWISE NOTED. EV ELEVATOR PHONE FACP FIRE ALARM CONTROL PANEL FO/OF FIBER OPTIC / OPTICAL FIBER FH FUME HOOD GWB GYPSUM WALL BOARD IEEE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS ITR INTERMEDIATE TELECOMMUNICATIONS ROOM JB JUNCTION BOX LAN LOCAL AREA NETWORK LEC LOCAL EXCHANGE CARRIER / TELCO LS LIFE SAFETY MM MULTI -MODE OPTICAL FIBER MTR MAIN TELECOMMUNICATIONS ROOM OFNR OPTICAL FIBER NON-METALLIC STRENGTH RISER RATED OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION PB PULL BOX PP PATCH PANEL R P RFMOTE ARI I I C ATI P I R N N AN N SM SINGLE -MODE OPTICAL FIBER TC TELECOMMUNICATIONS CONTRACTOR TELCO PUBLIC TELEPHONE COMPANY (VERIZON) TGB TELECOMMUNICATION GROUND BUS BAR TMGB TELECOMMUNICATIONS MAIN GROUNDING BAR TIA TELECOMMUNICATION INDUSTRY ASSOCIATION TR TELECOMMUNICATIONS ROOM TYP TYPICAL UNO UNLESS NOTED OTHERWISE UPS UNINTERRUPTIBLE POWER SUPPLY UTP UNSHIELDED TWISTED PAIR VIE VERIFY IN FIELD VOM VERIZON OWNED AND MAINTAINED WAP WIRELESS ACCESS POINT TELECOM SYMBOLS LEGEND (REV. 02/12) DEMO EXISTING NEW DESCRIPTION STIMSON HALL - 2011 ITHACA, NY E la W TELECOM OUTLET - FLOOR BOX © 0 0) TELECOM OUTLET - CEILING MOUNTED < <F1 47 TELECOM OUTLET - WALL MOUNTED CONDUITS SIZE AS INDICATED - -J- -J- J -HOOKS - WHERE INDICATED CONDUIT WITH BUSHINGS - TYPE & SIZE AS C ] C C 3 INDICATED PULLBOX: X = SIZE: PB—X PB—X PB x (5) SMALL, (M) MEDIUM, (L) LARGE LxWxH LxWxH LxWxH LxWxH = DIMENSIONS IN INCHES El CTR CTR EQUIPMENT CABINET WITH ZONE CABLING CD LPI AP 100 DD fl ACCESS PANEL - CEILING MOUNT xsR-# ®sR-# ...sR-1 VERTICAL RACEWAY - DOWN (SR -2 UNO) HsRfi HsR-# sR-4 VERTICAL RACEWAY -- UP (SR -2 UNO) Nc'r-x CT -X ►ulcr-x VERTICAL CABLE TRAY - DOWN Hcr-x Z CT -X HCT-X VERTICAL CABLE TRAY - UP • S S CONDUIT/SLEEVE - UP 0 0 0 CONDUIT/SLEEVE - DOWN 4 Q O CONDUIT/SLEEVE - THRU (BETWEEN FLOORS) HORIZONTAL RACEWAY - SIZED PER PATHWAY 1:230 I sR-# I SCHEDULE HORIZONTAL CABLE TRAY - SIZED PER CT -X CT -x PATHWAY SCHEDULE OWNER PROJECT NO: 754 l HI 1 1 1 1 CABLE RUNWAY 0 SPLICE CASE PROJECT MANAGER: DPB Kai ■ P COMMUNICATIONS POWER POLE SERVING ZONE OR MTR/ITR BOUNDARY CTR SERVING ZONE BOUNDARY NEW / EXISTING OUTLET SUBSCRIPT KEY (REFER TO ADDITIONAL DESCRIPTORS THIS DRAWING) "A" ROOM LOCATION CODE "" EXISTING OUTLET NOTE "xx" EXISTING PATHWAY TYPE TO BE REUSED "yy" OUTLET DESCRIPTOR "zz" NEW PATHWAY TYPE IXXzAI ri '!-�J NEW PATHWAY TYPE KEY CC CONDUIT TO CEILING CF CONDUIT TO FLOOR CH CONDUIT TO HALL CL CONDUIT TO CLOSET CI CONDUIT HOMERUN TO ITR/MTR CP CONDUIT TO PULLBOX CT CONDUIT TO CABLE TRAY FW FISHABLE WALL JP J -HOOK TO PULLBOX JS J -HOOK TO SLEEVE JT J -HOOK TO CABLE TRAY PT PULLBOX TO CABLE TRAY SC SURFACE RACEWAY TO CEILING SF SURFACE RACEWAY TO FLOOR SH SURFACE RACEWAY TO HALL (RACEWAY THROUGH ROOM TO HALLWAY PRIMARY HORIZONTAL PATHWAY) SW SURFACE THROUGH WALL DOB NEW DEVICE OPENING IN EXISTING SURFACE RACEWAY, WITH BLANK PLATE (MATCH EXISTING COLOR) NOTE: PROVIDE MINIMUM 1" CONDUIT UNLESS NOTED OTHERWISE. INCREASE SIZE AS REQUIRED PER CABLE FILL CHART. NOTE: PROVIDE MINIMUM SIZE METALLIC RACEWAY BASED ON CABLE FILL CHART UNLESS NOTED OTHERWISE. NOTE: ASSUME PATHWAY TYPE "CP" UNLESS NOTED OTHERWISE. OUTLET DESCRIPTOR KEY ##" HEIGHT ABOVE FINISHED FLOOR (AFF) - EXAMPLE: 48" BAC BUILDING ACCESS CONTROLLER EM EMERGENCY TELEPHONE OUTLET EV ELEVATOR TELEPHONE LINE CONNECTION EMS ENERGY MANAGEMENT FACP FIRE ALARM CONTROL PANEL P WALL MOUNTED PAY -PHONE OUTLET W WALL MOUNTED TELEPHONE OUTLET TO BE MOUNTED AT 48" AFF WAP WIRELESS ACCESS POINT - REFER TO DETAIL AT -27052839. EXISTING OUTLET NOTE KEY A " EXISTING DEVICE OR OPENING WITH LEGACY CABLING. REMOVE CABLING, PAINT/PATCH OR PROVIDE BLANK AS APPLICABLE. A EXISTING ONE -GANG BOX AND PATHWAYS TO BE REUSED AS INDICATED. MAINTAIN EXISTING SERVICES UNTIL AFTER CUTOVER, THEN REMOVE CABLING. EXISTING 1WO-GANG BOX AND PATHWAYS TO BE REUSED AS INDICATED. MAINTAIN EXISTING SERVICES UNTIL AFTER CUTOVER, THEN REMOVE CABLING. n EXISTING OUTLET LOCATION IN SURFACE RACEWAY. PATHWAYS TO BE REUSED AS INDICATED. MAINTAIN ANY EXISTING SERVICE UNTIL AFTER CUTOVER, THEN REMOVE CABLING. PROVIDE DEVICE BRACKETS AS REQUIRED. EXISTING PATHWAYS, BOXES, RACEWAYS AND CAT.5, CAT.5E OR CAT.6 CABLES TO REMAIN. n EXISTING PATHWAYS, BOXES AND RACEWAYS TO REMAIN. COORDINATE SHUTDOWN AND CONDUIT/CABLE REWORK TO RELOCATE FROM EXISTING TR TO NEW TR PER T1 -PL, T1 -SZ AND APPENDIX A. REASSIGN CABLE PANEL/PORTS AS CALLED FOR. CABLING SYMBOLS LEGEND 2B -101-A1 CABLE IDENTIFICATION LABEL: 2B COMMUNICATIONS EQUIPMENT ROOM 101 MASTER LOCATION CODE A ROOM LOCATION CODE 1 POSITION J:\PROJECTS-Ithaca\2011\ 11103 CORNELL - NCP\Stimson 201 1 \CAD\ 11103-2011--T-GEN.dwci SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED TO: ARCH El (30X42 IN.) Otilij MO 115 METRO PHONE: ARCHITECHNOLOGY, LLC . www.archi-technology.com PARK ROCHESTER, NY 14623 585.424.1952 Fax: 585.424.4239 STIMSON HALL - 2011 ITHACA, NY CLIENT: Cornell University PROJECT NETWORK rill • o� — = _ CONNECTIVITY CD 06/29/1z CONSTRUCTION DOCUMENTS 100 DD 06/15/12 100% DD SUBMISSION 50 DD 05/10/12 50% DD SUBMISSION 20 SD 1 1/09/11 20% SD SUBMISSION PSD 09/30/11 PRELIMINARY SD SUBMISSION MARK DATE DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/12 ' AT PROJECT NO: 11103-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL CHECKED BY: JLB PROJECT MANAGER: DPB SHEET TITLE: STANDARD SYMBOLS, N ABBREVIATIONS (T -SERIES) PROVIDE ESCUTCHEON PLATES AT ALL PIPE PENETRATIONS EXPOSED TO VIEW. SIZE ESCUTCHEON AROUND INSULATION ON INSULATED PIPE AND AROUND PIPE ON UNISULATED PIPES NON -FIRE RATED WALL SLEEVE WHERE REQUIRED BY SPECIFICATIONS P\\\\\\\\ \ \\ \ \\\\\\ \.\\\\\\\\\\ \ \\\\\\\y PIPE PIPE INSULATION - RUN INSULATION CONTINUOUS THROUGH WALL OPENING. / / PROVIDE 1" CLEARANCE ALL AROUND NON FIRE RATED WALL PIPE PENETRATION Scale: NONE PROVIDE ESCUTCHEON PLATES AT ALL PIPE PENETRATIONS EXPOSED TO VIEW. SIZE ESCUTCHEON AROUND INSULATION ON INSULATED PIPE AND AROUND PIPE ON UNISULATED PIPES FIRE RATED WALL SLEEVE WHERE REQUIRED BY SPECIFICATIONS /\\\\\\\\:><XX\\\\\ WA Q PIPE PIPE INSULATION - BUTT TIGHT TO FIRESTOPPING SYSTEM S •"D \\\\\\\y PROVIDE FIRESTOPPING SYSTEM PER SPECIFICATIONS FIRE RATED WALL PIPE PENETRATION Scale: NONE I I ' CONCRETE DECK EXPANSION SHIELDS CONCRETE ANCHORS NOTE: REFER TO SPECIFICATION FOR REQUIRED ANCHOR CONFIGURATION. WASHER (TYPICAL) EXPANSION NAILS CONCRETE ANCHOR DEVICE DETAIL Scale: NONE SHUTOFF VALVE CIRCUIT SETTER CHWS&R (ETR) BUILDING CHILLED WATER PUMPS (ETR) BOOS 808A P- SHUTOFF VALVE B1O BOOCD REFER TO DRAWING M4 FOR PUMP SCHEDULE. BI OA BOOSA BOOCC 3/4" CHWS&R BOOUB 3/4" CHWS&R UP TO FCU -1 BASEMENT 2B - MECHANICAL - NEW WORK 10 Scale: 1/4" = 1'-0" J:\PROJECTS-Ithaca\2011\11103 CORNELL - NCP\Stimson 2011\CAD\11103-2011--AMEP.dwa 0 2` 4` 8' PROVIDE INSULATION \ SHIELD & INSERT FOR ALL PIPING HANGER RODS CHANNEL OR ANGLE SIDE VIEW TRAPEZE HANGER HANGER ROD INSULATION HANGER ROD INSULATION INSULATION SHIELD AT HANGER PROVIDE HIGH COMPRESSIVE STRENGTH INSUL INSERT BETWEEN PIPE & INSULATION SHIELD ADJUSTABLE CLEVIS HANGER WELD SADDLE ADJUSTABLE ROLLER HANGER NOTE: REFER TO PROJECT SPECIFICATION FOR ROD DIAMETER, END CONDITION (CLAMP, ANCHOR, ETC.) HANGER TYPES, AND CONFIGURATION. PIPE HANGER Scale: NONE FLOW BALANCING VALVE t U MANUAL AIR VENT MV \\._FETE'S PLUGS (TYPICAL) UNION/FLANGE (TYPICAL) THERMOMETER (TYPICAL) f DRAIN w/HOSE END AIR FLOW COIL STRAINER - ISOLATION VALVE (TYPICAL) NOTES: 1. PIPING TO ALLOW REMOVAL OF COIL WITHOUT REMOVING PIPING BEYOND UNIONS OR FLANGES. 2. FOR UNITS WITH MORE THAN ONE SECTION, PROVIDE FLOW BALANCER, UNIONS/FLANGES, FLEXIBLE CONNECTORS, DRAINS AND AIR VENTS FOR EACH COIL. TWO-WAY CONTROL VALVE COIL PIPING DETAIL 5 Scale: NONE STRAINER i ISOLATION VALVE (TYPICAL) RETURN 1/4" PRESSURE GAUGE (0#-100# PSI) lid.. SUPPLY TD- TRIPLE DUTY VALVE UNION (TYPICAL) 'CIRCULATING PUMP SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED TO: ARCH El (30X42 IN.) INLINE PUMP DIAGRAM DETAIL Scale: NONE GENERAL NOTES REFER TO DRAWING AMEP-GEN. COOLING COIL DRAIN SEE PLANS FOR CONTINUATION NOTE: L =INCH (MINIMUM) H =INCH PLUS THE TOTAL UNIT STATIC PRESSURE AT WORST CASE (LOADED FILTERS) UNDER POSITIVE PRESSURE COOLING COIL DRAIN SEE PLANS FOR CONTINUATION - CONNECT TO EXISTING COOLING COIL CONDENSATE DRAIN NOTE: L = H + J + PIPE DIAMETER H = 1 INCH FOR EACH INCH OF NEGATIVE PRESSURE* + 1 INCH J = 'H CONNECT TO EXISTING COOLING COIL CONDENSATE DRAIN * Nc ATIVE PRESSURE "C: A UNIT STATIC TRESSURE= AT WORST I V B l i t l l Y L I i-- � CASE (LOADED FILTERS) MINUS EXTERNAL PRESSURE UNDER NEGATIVE PRESSURE TYPICAL COOLING COIL DRAIN Scale: NONE UNIT LOCATION AIRFLOW ELECTRICAL CHILLED WATER COIL PUMP HEAD (FT HD) MOTOR (WATTS) V PH FLA EDB EWB LDB LWB TOTAL MBH SENSIBLE MBH EWT LWT GPM FLUID PD MANUF/MAKE NOTES FCU -1 MTR-2BA 310 (62) 115 1 1.2 75 63 55 54 11 9 52 62 1.8 4.0 EMI WCP-15 1,2,3,4 NOTES: 1. PROVIDE UNIT MOUNTED CONTROLS. 2. PROVIDE WASHABLE FILTER. 3. PROVIDE CONDENSATE PUMP. 4. EWT = 52' F DURING WINTER MONTHS. CO3 EWT = 47' F DURING SUMMER MONTHS. NEW CHILLED WATER FAN COIL UNIT SCHEDULE Scale: NONE UNIT LOCATION SERVICE PUMP TYPE MEDIA PUMP HEAD (FT HD) PUMP FLOW (GPM) FLUID TEMP (F) MOTOR DATA DESIGN BASIS VOLT PH HP NOTES P-1 MECH. RM. ITR -GA BOOSTER PUMP CHILLED WATER 15 1.8 45 120 1 1/12 BELL & GOSSETT PL -30 - NEW BOOSTER PUMP SCHEDULE Seale: NONE mak ``p ARCHITECHNOLOGY, LLC www.archi-technology.com 115 METRO PARK ROCHESTER, NY 14623 PHONE: 585.424.1952 Fax: 585.424.4239 z Q U z CLIENT: Cornell University NETWORK CONNECTIVITY PROJECT CD 06/2 / 12 CONSTRUCTION DOCUMENTS 100 DD 100% DD SUBMISSION 50 DD 05/10/12 50% DD SUBMISSION 20 SD 11/09/11 20% SD SUBMISSION PSD 09/30/11 PRELIMINARY SD SUBMISSION MARK DATE DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/12 AT PROJECT NO: 1103-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL CHECKED BY: JLB PROJECT MANAGER: DPB SHEET TITLE: MECHANICAL DETAILS M4 COD 06/ 29/ 12 10DD 50 DD 05/10/12 20 SD 11 /111 PSD 09/30/1 MARK DATE/09 iS T RUC T ION DOCUMENTS 100% DD SUBMISSION 50% DD SUBMISSION 20% SD SUBMISSION PRELIMINARY SD SUBMISSION DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/12 AT PROJECT NO: 11.03-2011 OWNER PROJECT NO: DRAWN BY: CHECKED BY: PROJECT MANAGER: 754 P/EL JLB DPB grim 4164,ARCHI-TECHNOLOGY, LLC www.archi-technology.com 115 METRO PARK ROCHESTER, NY 14623 PHONE: 585.424.1952 Fax: 585.424.4239 r -I CD N J Q 2 (40 z 0 } Z a U Z H CLIENT: Cornell University NETWORK CONNECTIVITY PROJECT a 0- CNI 0.4 1\\ L30AU S NAME LOCATION SOURCE NOTES: SE RATED HINGED TRIM COMPUTER GRADE n 200% NEUTRAL FEED-THRU LUGS SUB FEED LUGS SUB -FEED BREAKER fl ISOLATED GND BUS RATI VG (AMPS) CP TRGA MTR-BA MCB MLO PH/WIRE VO LTAG E MOUNTING KAIC DESIGN MAKE NEMA TYPE 60A 3/4 120/208 SURFACE 22 CKT NO DESCRIPTION BREAKER KVA LOAD PH. A PH. B PH. C KVA LOAD PH. A PH. B PH. C BREAKER DESCRIPTION CKT NO 3 5 UPS REECEPTACLE RECEPTACLES ACCESS CONTROL SYSTEM 20/1 1.8 20/1 0.7 20/1 .01 7 9 11 13 15 17 19 21 SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE 20/1 20/1 20/1 20/1 20/1 20/1 20/1 20/1 23 SPARE 20/1 1.8 20/1 UPS RECEPTACLE 2 0.2 20/1 ECU -1 4 20/1 SPARE 6 20/1 SPARE 8 20/1 SPARE 10 20/1 SPARE 12 20/1 SPARE 14 20/1 SPARE 16 20/1 SPARE 18 20/1 SPARE 20 20/1 SPARE 22 20/1 SPARE 24 ELECTRICAL PANELBOARD SCHEDULE Scale: NONE FOURTH FLOOR THIRD FLOOR SECOND FLOOR FIRST FLOOR GROUND FLOOR BASEMENT GENERAL NOTES 1. REFER TO DRAWING AMEP—GEN. FOURTH FLOOR THIRD FLOOR SECOND FLOOR PROVIDE 60A/3P BREAKER AT POSITION 37-39-41. MOVE BRANCH CIRCUIT WIRING PRESENTLY LOCATED AT POSITION 37 TO POSITION 35. FIRST FLOOR 1—#2 AWG IN 3/4" CONDUIT WI TH 60A/3P REAKER PANEL CP TRGA ED • 6 AWG I MTR—GA RM. G23 #6 AWG EX. GROUND 1 MDP EX. PANEL LPP-1 (4) #6 AWG WITH (1) #8 AWG GROUND IN 1" CONDUIT ELECTRIC ROOM BOOUB GROUND FLOOR BASEMENT ELECTRICAL CONSTRUCTION KEYED NOTES: E1 PROVIDE #6 AWG GROUNDING CONDUCTOR TO ANTI—STATIC FLOOR PIGTAIL. POWER & GROUNDING SYSTEM RISER DIAGRAM Scale: NONE FIXTURE TYPE LAMPS DESCRIPTION VOLTS MANUFACTURER & CATALOG NUMBER QTY. WATTS LAMP CODE REMARKS EM TWIN HEAD EMERGENCY LIGHTING UNIT 120/277 McPHILBEN CFX6 2 5 HALOGEN NOTES 1. NOT USED. LIGHTING FIXTURE SCHEDULE Scale: NONE TMGB OR TGB LABEL 0 0 0 0 0 PROVIDE ENGRAVED TAG FOR EACH GROUNDING CONDUCTOR, BOTH ENDS AND AT EXPOSED PASS THROUGH MECHANICAL SPACES AND AT ENTRANCES/EXITS TO SHAFTWAYS, TYPICAL. DIV. 26 CONTRACTOR TO PROVIDE INSULATED TIN PLATED TELECOM SYSTEM GROUND BUS BAR. HOLE CENTERS TO MATCH LUG CONFIGURATION AND EIA/TIA 607 STANDARDS. REFER TO SECTIONS 260526 and 271100. TMGB — ERICO/ERITECH # TMGB—A2OL27PT TGB — ERICO/ERITECH # TGB—A20L12PT INSULATORS. 5/8" LOCKWASHERS. WALL MOUNTING BRACKET. 5/8-11X1'' H.H.C.S. BOLTS. DIV. 26 CONTRACTOR TO PROVIDE LONG BARREL COMPRESSION LUG, TWO BOLT, COMPRESSION LUG (BURNDY HYLUG YAZ SERIES) OR EQUAL. PROVIDE A MINIMUM OF EIGHT (8) SPARE LUGS WITH 5/16" HOLES FOR FUTURE USE BY OWNER. DRILL AND TAP AS REQUIRED. SCRUFF BAR AND PROVIDE ANTIOXIDANT AS CALLED FOR. REFER TO SECTIONS 260526 and 271100. TELECOMMUNICATIONS GROUND BAR (TMGB,TGB) DETAIL Scale: NONE J:\PROJECTS—Ithaca\2011 \ 11103 CORNELL — NCP\Stimson 2011 \CAD\ 11103-2011--AMEP.dwq SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED TO: ARCH El (30X42 IN.) SHEET TITLE: ELECTRICAL DETAILS E4 GENERAL NOTES FOR ALL TRADES: . REFER TO DRAWING "T—GEN" FOR PROJECT NOTES AND ABBREVIATIONS APPLICABLE TO ALL DRAWINGS AND CONTRACTS. REFER TO TABLES ON THIS PAGE FOR DRAWING SYMBOLS AND ABBREVIATIONS PER TRADE. . REFER TO AMEP—xx DRAWINGS FOR GENERAL NOTES AND KEYED NOTES SPECIFIC TO TRADE. . THIS INFORMATION REPRESENTS EXISTING CONDITIONS BASED ON ORIGINAL DRAWINGS AND OBSERVED SITE CONDITIONS. NOT ALL ELECTRICAL/MECHANICAL EQUIPMENT IS SHOWN. THE CONTRACTOR SHALL FIELD VERIFY EXACT ROUTING, DIMENSIONS AND QUANTITIES. . REFER TO MECHANICAL, ELECTRICAL AND COMMUNICATION DRAWINGS FOR ADDITIONAL DEMOLITION AND RENOVATION WITHIN THE INDICATED WORK AREAS. . REFER TO T2—x.CA_CP DRAWINGS FOR CEILING ACCESS PANEL LOCATIONS. REFER TO DRAWING T3—xx DRAWINGS FOR ADDITIONAL COORDINATION REQUIREMENTS. . GENERAL CONSTRUCTION CONTRACTOR SHALL PERFORM ALL WORK AS SHOWN ON AMEP DRAWINGS, UNLESS NOTED OTHERWISE. REFER TO SPECIFICATIONS 011x00 FOR ADDITIONAL INFORMATION. . REFER TO THE PROJECT MANUAL/TECHNICAL SPECIFICATION SECTIONS FOR ADDITIONAL PRODUCT AND/OR EXECUTION REQUIREMENTS TO SUPPLEMENT INFORMATION CONTAINED ON THE DRAWINGS. CUTTING AND PATCHING OF OPENINGS IN EXISTING BUILDING CONSTRUCTION SHALL BE DONE IN A MANNER WHICH DOES NOT IMPAIR THE STRUCTURAL INTEGRITY OF THE CONSTRUCTION AND MAINTAINS ALL REQUIRED FIRE RATINGS. PATCHING SHALL INCLUDE ALL OPENINGS LEFT IN EXISTING CONSTRUCTION DUE TO DEMOLITION WORK. ALL PATCHED SURFACES ARE TO BE RESTORED AS CLOSELY AS POSSIBLE TO THE ORIGINAL CONDITIONS. ALL PATCHED AREAS REQUIRING PAINT SHALL RECEIVE TWO PRIMER COATS AND TWO FINISH COATS. MATERIALS USED FOR PATCHING SHALL MATCH EXISTING ADJACENT MATERIALS IN BOTH TYPE AND QUALITY. . NEW ELECTRICAL AND MECHANICAL SYSTEMS WHICH PENETRATE NEW AND EXISTING FIRE RATED FLOORS, WALLS AND OTHER ASSEMBLIES SHALL BE FIRESTOPPED. IN AREAS ACCESSIBLE TO THE PUBLIC, FIRESTOP SYSTEMS SHALL BE SELECTED, INSTALLED AND FINISHED TO THE QUALITY OF ADJACENT SURFACES OF BUILDING CONSTRUCTION BEING PENETRATED. REFER TO SPECIFICATION 078413 FOR ADDITIONAL INFORMATION. . ALL PLAN DIMENSIONS ARE TO FACE OF PARTITION ASSEMBLY OR FINISH SURFACE (EXCLUDING PLYWOOD BACKBOARDS). . CONTRACTOR IS TO VERIFY ALL DRAWING DIMENSIONS IN THE FIELD FOR ACCURACY. . PROVIDE SOFT COPY SUBMITTAL(S) ON ACTUAL PRODUCTS USED. INCLUDE COPY OF APPROVED SUBMITTAL WITH CLOSE OUT DOCUMENTS (IN HARD COPY 0/M MANUAL), REFER TO SECTIONS: 013300 — SUBMITTALS; 017839 — RECORD DOCUMENTS; AND 017700 — PROJECT CLOSEOUT AS APPLICABLE. N. ANY DRILLING, CUTTING ETC. WORK THAT MAY CREATE A NUISANCE FIRE ALARM, NEEDS TO BE SCHEDULED 24 HOURS IN ADVANCE WITH CUSTOMER SERVICE FOR A FIRE PROTECTION SYSTEM SHUTDOWN. SHUTDOWN WILL BE PERFORMED BY EH&S (ENVIRONMENTAL HEALTH AND SAFETY) STAFF. CONTRACTOR WILL NOT DISABLE ANY FIRE PROTECTION EQUIPMENT WITHOUT EH&S APPROVAL/ASSISTANCE. 0. ALL NEW SMOKE DETECTORS AND OTHER FIRE ALARM INITIATION/NOTIFICATION DEVICES WILL NEED TO BE TESTED BY EH&S AND AHJ (AUTHORITY HAVING JURISDICTION) FOR PROPER OPERATION OF DEVICE, DAMPER AND EXHAUST FAN SHUTDOWN. ARCHITECTURAL GENERAL NOTES: A. CLEAN ALL ROOMS DUST FREE FOLLOWING COMPLETION OF DEMOLITION AND PATCHING WORK. B. PROVIDE FIRESTOPPING IN ACCORDANCE WITH SPECIFICATION SECTION 078413 WHERE ITEMS (INCLUDING CABLE TRAYS, PIPES, CONDUIT, FRAMING MEMBERS AND DUCTS) PENETRATE BOTH NEW AND EXISTING FIRE RATED PARTITIONS. FIRE RATED PARTITIONS ARE INDICATED ON ARCHITECTURAL DRAWINGS. FOR SMOKE, FIRE, OR FIRE/SMOKE DAMPERS, TREAT PENETRATION IN ACCORDANCE WITH DAMPER MANUFACTURER'S PRINTED DIRECTIONS. USE OF FIRESTOPPING WILL INVALIDATE UL LISTING OF DAMPER. C. SEAL PENETRATIONS OF BOTH NEW AND EXISTING NON—RATED PARTITIONS INCLUDING CABLE TRAYS, PIPES, CONDUIT, FRAMING MEMBERS AND DUCTS. PROVIDE ELASTOMERIC SEALANT AT GYPSUM WALLBOARD PARTITIONS. PROVIDE MORTAR/GROUT FOR PIPES AND CONDUIT THROUGH MASONRY PARTITIONS. PROVIDE ELASTOMERIC SEALANT AT EXTERIOR WALLS. ( REMOVALS INDICATED AS DASHED LINES ("I) �T SINGLE RECEPTACLE OUTLET, 20 AMPERE DEDICATED U.P.S. CIRCUIT, 120 VOLT, TOP OF BOX AT 24" AFF SURFACE MOUNTED ON PLYWOOD UNLESS OTHERWISE NOTED. AIR FLOW NEW WALL TYPE — REFER TO KEYED NOTES FOR CONSTRUCTION PIPING SYMBOLS lial 0 AD ROOM NUMBER #% ### TO EXISTING CONNECTION ISZ-S; DUCT — DOWN — POSITIVE PRESSURE-0NEW EXISTING DOOR TO REMAIN AIR 20 AMPERE, 277 VOLT, SINGLE POLE AC SWITCH, TOP OF BOX AT 48" AFF DEFINITION OF SUBSCRIPTS: 2 TWO POLE SWITCH 3 THREE WAY SWITCH 4 FOUR WAY SWITCH M FRACTIONAL HORSEPOWER, MANUAL MOTOR STARTER W/ THERMAL OVERLOADS abc LOWER CASE LETTER(S) SIGNIFY SWITCHING DESIGNATIONS, QUANTITY OF LETTERS EQUALS QUANTITY OF GANGED SWITCHES. 100 DOOR NUMBER (NEW OR EXISTING) APPROX SMD NEW DOOR AND FRAME 0 JUNCTION BOX, SURFACE MOUNT DUCT — DOWN — NEGATIVE PRESSURE BTU INDICATES 2—HOUR RATED FIRE SEPARATION sommo I mimmimi INDICATES 1—HOUR RATED FIRE SEPARATION FIRE ALARM SYSTEM SMOKE DETECTOR CEILING ACCESS PANEL ATV AP FIRE ALARM SYSTEM HEAT DETECTOR CONCRETE ARCHITECTURAL SYMBOLS LEGEND Scale: NONE HVAC GENERAL NOTES: A. VERIFY ALL EXISTING CONDITIONS. EQUIPMENT LOCATIONS SHOWN ARE APPROXIMATE AND MINOR ADJUSTMENTS TO THE INSTALLATION MAY BE REQUIRED TO AVOID CONFLICTS WITH EXISTING EQUIPMENT AND APPARATUS — EXISTING BRANCH CIRCUITS ARE FROM RECORD DRAWINGS, AND MAY VARY. B. FIELD VERIFY ALL EXISTING CONDITIONS AND DETERMINE THE BEST PATH FOR NEW INSTALLATIONS THAT WILL CAUSE THE LEAST DISTURBANCE TO OCCUPIED SURROUNDINGS. PATHWAYS THAT ARE ROUTED THROUGH MECHANICAL ROOMS, UTILITY ROOMS, STORAGE CLOSETS, ETC. ARE FAVORABLE TO DISTURBANCES IN OCCUPIED AREAS. C. INSTALL ALL EQUIPMENT IN STRICT CONFORMANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS AND RECOMMENDATIONS. D. COORDINATE THE WORK SHOWN ON THESE DRAWINGS WITH THE WORK OF ALL OTHER TRADES PRIOR TO THE FABRICATION OR INSTALLATION OF ANY WORK. EQUIPMENT AND DEVICES THAT CANNOT CHANGE LOCATION SHALL TAKE PRECEDENCE OVER THOSE THAT CAN CHANGE. E. THESE DRAWINGS ARE SCHEMATIC IN NATURE. PROVIDE ALL OFFSETS, HANGERS, ANCHORS, SUPPORTS, WIRING AND ACCESSORIES FOR A COMPLETE, OPERATIONAL INSTALLATION. F. WHERE CEILINGS ARE REMOVED TO ACCOMMODATE NEW TELECOM ROOMS, PROVIDE SUPPORT(S) FOR ALL REMAINING MECHANICAL PIPING, DUCTWORK, MISCELLANEOUS EQUIPMENT, ETC. NOT BEING REMOVED. ALL UNUSED EQUIPMENT & APPURTENANCES SHALL BE REMOVED AND PROPERLY DISPOSED OF. G. ALL EXISTING AND NEW PIPING, DUCTWORK, MECHANICAL EQUIPMENT IN TELECOM ROOMS SHALL BE CLEANED FREE OF DUST/DEBRIS AFTER WALL DEMOLITION AND AFTER WALL RECONSTRUCTION/PATCHING. MECHANICAL SYMBOLS LEGEND C3 --) Scale: NONE ELECTRICAL GENERAL NOTES: A. VERIFY ALL EXISTING CONDITIONS. EQUIPMENT LOCATIONS SHOWN ARE APPROXIMATE AND MINOR ADJUSTMENTS TO THE INSTALLATION MAY BE REQUIRED TO AVOID CONFLICTS WITH EXISTING EQUIPMENT AND APPARATUS — EXISTING BRANCH CIRCUITS ARE FROM RECORD DRAWINGS, AND MAY VARY. B. FIELD VERIFY ALL EXISTING CONDITIONS AND SHALL DETERMINE THE BEST PATH FOR NEW INSTALLATIONS THAT WILL CAUSE THE LEAST DISTURBANCE TO OCCUPIED SURROUNDINGS. PATHWAYS THAT ARE ROUTED THROUGH MECHANICAL ROOMS, UTILITY ROOMS, STORAGE CLOSETS, ETC. ARE FAVORABLE TO DISTURBANCES IN OCCUPIED AREAS, ALL NEW LUMINAIRES SHALL BE INSTALLED AT A MINIMUM HEIGHT OF 9'-6" AFF UNLESS OTHERWISE NOTED. C. COORDINATE MOUNTING HEIGHT OF ALL NEW POWER OUTLETS WITH THE TELECOMMUNICATIONS SYSTEMS EQUIPMENT ELEVATION DRAWINGS/DETAILS. D. COORDINATE ALL REQUIRED POWER AND FIRE ALARM SHUTDOWNS WITH THE OWNER. PROVIDE MINIMUM 1 WEEK ADVANCE NOTICE. E. WHERE CEILINGS ARE REMOVED TO ACCOMMODATE NEW TELECOM ROOMS, PROVIDE SUPPORT(S) FOR ALL REMAINING ELECTRICAL CONDUITS, DEVICES, EQUIPMENT, ETC. NOT BEING REMOVED. ALL UNUSED EQUIPMENT SHALL BE REMOVED AND PROPERLY DISPOSED OF. F. ALL EXISTING AND NEW CONDUIT AND ELECTRICAL EQUIPMENT IN TELECOM ROOMS SHALL BE CLEANED FREE OF DUST/DEBRIS AFTER WALL DEMOLITION AND AFTER WALL RECONSTRUCTION/ PATCHING. G. PROVIDE GROUNDING IDENTIFICATION AS CALLED FOR. PROVIDE TAGS ON GROUND CONDUCTOR IN ALL SPACES AS DIRECTED AND SHOWN ON GROUNDING DETAIL. H. DURING CONSTRUCTION, PROVIDE HEAT DETECTORS IN TELECOM ROOMS. AT SUBSTANTIAL COMPLETION AND AFTER FINAL CLEANING, CHANGE HEAT DETECTOR TO SMOKE DETECTOR. 1. ALL FIRE ALARM SYSTEM DEVICES SHALL BE TESTED BY EH&S AND AHJ FOR PROPER OPERATION OF DETECTOR, DAMPER, AND FAN SHUTDOWN. D ❑ O DUCT — UP — NEGATIVE PRESSURE— ("I) �T SINGLE RECEPTACLE OUTLET, 20 AMPERE DEDICATED U.P.S. CIRCUIT, 120 VOLT, TOP OF BOX AT 24" AFF SURFACE MOUNTED ON PLYWOOD UNLESS OTHERWISE NOTED. AIR FLOW LIGHTING FIXTURE, WALL MOUNT PIPING SYMBOLS lial 0 AD LIGHTING FIXTURE, FLUORESCENT, CEILING MOUNTED, INDUSTRIAL/STRIP #% ABOVE FINISH FLOOR TO EXISTING CONNECTION ISZ-S; DUCT — DOWN — POSITIVE PRESSURE-0NEW AIR HANDLING UNIT AIR 20 AMPERE, 277 VOLT, SINGLE POLE AC SWITCH, TOP OF BOX AT 48" AFF DEFINITION OF SUBSCRIPTS: 2 TWO POLE SWITCH 3 THREE WAY SWITCH 4 FOUR WAY SWITCH M FRACTIONAL HORSEPOWER, MANUAL MOTOR STARTER W/ THERMAL OVERLOADS abc LOWER CASE LETTER(S) SIGNIFY SWITCHING DESIGNATIONS, QUANTITY OF LETTERS EQUALS QUANTITY OF GANGED SWITCHES. © A APPROX SMD MOTION DETECTOR, WALL SWITCH TYPE 0 JUNCTION BOX, SURFACE MOUNT DUCT — DOWN — NEGATIVE PRESSURE BTU VENT DISCONNECT SWITCH CAPPED DUCT FIRE ALARM SYSTEM SMOKE DETECTOR © ATV ATMOSPHERIC FIRE ALARM SYSTEM HEAT DETECTOR CONCRETE PANEL CONCRETE MASONRY UNIT CHWS COMPRESSED AIR TELECOMMUNICATIONS GROUNDING BUS BAR CHILLED WATER RETURN DUCT — UP THRU ROOF — NEGATIVE PRESSURE CHILLED WATER SUPPLY & RETURN 111 1 CA TGB DIAMETER DUCT TRANSITION FROM RECTANGULAR TO ROUND CD CONDENSATE DRAIN DRAWING TELECOMMUNICATIONS MAIN GROUNDING BUS BAR DUCT — UP THRU ROOF — POSITIVE PRESSURE EAT ENTERING AIR TEMPERATURE SINGLE INPUT READER INTERFACE MODULE ENTERING DRY BULB SRI ENERGY EFFICIENCY RATIO EF CHILLED WATER RETURN X ENVIRONMENTAL HEALTH & SAFETY DUCT — UP — POSITIVE PRESSURED EFFICIENCY 22E TRANSITION FROM RECTANGULAR TO RECTANGULAR CHWR ENERGY MANAGEMENT SYSTEM ERL WATER SUPPLY & RETURN ERM DRI DUCT SIZE — FIRST FIGURE IS SIZE SHOWN CHWS&R CHILLED EXISTING TO REMAIN — El DOOR CONTACT (POSITION SWITCH) CHILLED WATER SUPPLY r EXISTING SQUARE THROAT RADIUS ELBOW EXPOSED 'F CH WS FA FIRE ALARM FACP FLEXIBLE CONNECTION FCU DOMESTIC COLD WATER FD FIRE DAMPER FLA FULL LOAD AMPS DCW FEET PER MINUTE FSD COMBINATION FIRE/SMOKE DAMPER FT OR ' $ GC DOMESTIC HOT WATER RETURN GPM GALLONS PER MINUTE GYP GYPSUM BOARD ACOUSTICALLY LINED DUCTWORK HOLLOW METAL HP HORSEPOWER SQUARE TO ROUND BRANCH DUCT DHR HWR HOT WATER RETURN -- HOT WATER SUPPLY HWS&R HOT WATER IP INTERIOR PAINT JB JUNCTION BOX KD KNOCK—DOWN FRAME DHW DOMESTIC LAT LEAVING AIR TEMPERATURE (F) FLEXIBLE DUCT LEAVING DRY BULB LWB LEAVING WET BULB LWT NATURAL GAS MAX ,,! C G THOUSAND BTUH MCA HOT WATER RETURN MCB MAIN CIRCUIT BREAKER VOLUME DAMPER HWR MIN • NC NORMALLY CLOSED NO £ PD DUCT WYE PF WATER SUPPLY PH PHASE HWS HOT PSI POUNDS PER SQUARE INCH RECTANGULAR ELBOW WITH TURNING VANES PAINT TO MATCH EXISTING PIPING PLYWOOD RA 'r OR SP SPRINKLER Q PIPING RISE r REFRIGERANT LIQUID RS REFRIGERANT SUCTION RRT RUBBER REDUCER STRIP THRESHOLD SA rrE RADIUS ELBOW (MIN R/W = 1.5) SEALED CONCRETE PIPING DROP SINGLE READER INTERFACE CARD READER ST H TGB TELECOMMUNICATIONS GROUNDING BUSBAR OTS DIGITAL SENSOR_ TYP TYPICAL CAPPED PIPE VOLT CEILING GRILLE (G) REGISTER (R) VARIABLE AIR VOLUME VB VINYL BASE VCT t VD ---,F-- DIRECTION OF FLUID FLOW T 0 THERMOSTAT WOOD WMP WIRE MESH PARTITION XFMR TRANSFORMER CEILING DIFFUSER (D) PITCH PIPING DOWN TOG THERMOSTAT OR SENSOR WITH GUARDDN • IV SHUT OFF VALVE 0 SPRINKLER HEAD (CEILING) XISHUT OFF VALVE DOOR LOUVER OR UNDERCUT • SPRINKLER HEAD (ABOVE CEILING) 1C)1 W) PUMP NA POINT OF DISCONNECT R DUCT RISE IN ELEVATION m D DUCT DROP IN ELEVATION MECHANICAL SYMBOLS LEGEND C3 --) Scale: NONE ELECTRICAL GENERAL NOTES: A. VERIFY ALL EXISTING CONDITIONS. EQUIPMENT LOCATIONS SHOWN ARE APPROXIMATE AND MINOR ADJUSTMENTS TO THE INSTALLATION MAY BE REQUIRED TO AVOID CONFLICTS WITH EXISTING EQUIPMENT AND APPARATUS — EXISTING BRANCH CIRCUITS ARE FROM RECORD DRAWINGS, AND MAY VARY. B. FIELD VERIFY ALL EXISTING CONDITIONS AND SHALL DETERMINE THE BEST PATH FOR NEW INSTALLATIONS THAT WILL CAUSE THE LEAST DISTURBANCE TO OCCUPIED SURROUNDINGS. PATHWAYS THAT ARE ROUTED THROUGH MECHANICAL ROOMS, UTILITY ROOMS, STORAGE CLOSETS, ETC. ARE FAVORABLE TO DISTURBANCES IN OCCUPIED AREAS, ALL NEW LUMINAIRES SHALL BE INSTALLED AT A MINIMUM HEIGHT OF 9'-6" AFF UNLESS OTHERWISE NOTED. C. COORDINATE MOUNTING HEIGHT OF ALL NEW POWER OUTLETS WITH THE TELECOMMUNICATIONS SYSTEMS EQUIPMENT ELEVATION DRAWINGS/DETAILS. D. COORDINATE ALL REQUIRED POWER AND FIRE ALARM SHUTDOWNS WITH THE OWNER. PROVIDE MINIMUM 1 WEEK ADVANCE NOTICE. E. WHERE CEILINGS ARE REMOVED TO ACCOMMODATE NEW TELECOM ROOMS, PROVIDE SUPPORT(S) FOR ALL REMAINING ELECTRICAL CONDUITS, DEVICES, EQUIPMENT, ETC. NOT BEING REMOVED. ALL UNUSED EQUIPMENT SHALL BE REMOVED AND PROPERLY DISPOSED OF. F. ALL EXISTING AND NEW CONDUIT AND ELECTRICAL EQUIPMENT IN TELECOM ROOMS SHALL BE CLEANED FREE OF DUST/DEBRIS AFTER WALL DEMOLITION AND AFTER WALL RECONSTRUCTION/ PATCHING. G. PROVIDE GROUNDING IDENTIFICATION AS CALLED FOR. PROVIDE TAGS ON GROUND CONDUCTOR IN ALL SPACES AS DIRECTED AND SHOWN ON GROUNDING DETAIL. H. DURING CONSTRUCTION, PROVIDE HEAT DETECTORS IN TELECOM ROOMS. AT SUBSTANTIAL COMPLETION AND AFTER FINAL CLEANING, CHANGE HEAT DETECTOR TO SMOKE DETECTOR. 1. ALL FIRE ALARM SYSTEM DEVICES SHALL BE TESTED BY EH&S AND AHJ FOR PROPER OPERATION OF DETECTOR, DAMPER, AND FAN SHUTDOWN. D ❑ O LIGHTING FIXTURE, CEILING MOUNTED ("I) �T SINGLE RECEPTACLE OUTLET, 20 AMPERE DEDICATED U.P.S. CIRCUIT, 120 VOLT, TOP OF BOX AT 24" AFF SURFACE MOUNTED ON PLYWOOD UNLESS OTHERWISE NOTED. 4 4 9 LIGHTING FIXTURE, WALL MOUNT q DUPLEX RECEPTACLE OUTLET, 20 AMPERE, 120 VOLT, TOP OF BOX AT 24" AFF UNLESS OTHERWISE NOTED. AD LIGHTING FIXTURE, FLUORESCENT, CEILING MOUNTED, INDUSTRIAL/STRIP #% ABOVE FINISH FLOOR DOUBLE DUPLEX RECEPTACLE OUTLET, 20 AMPERE, 120 VOLT, TOP OF BOX AT 24" AFF UNLESS OTHERWISE NOTED. ISZ-S; EM LIGHTING FIXTURE AIR HANDLING UNIT AL 20 AMPERE, 277 VOLT, SINGLE POLE AC SWITCH, TOP OF BOX AT 48" AFF DEFINITION OF SUBSCRIPTS: 2 TWO POLE SWITCH 3 THREE WAY SWITCH 4 FOUR WAY SWITCH M FRACTIONAL HORSEPOWER, MANUAL MOTOR STARTER W/ THERMAL OVERLOADS abc LOWER CASE LETTER(S) SIGNIFY SWITCHING DESIGNATIONS, QUANTITY OF LETTERS EQUALS QUANTITY OF GANGED SWITCHES. /,--- . PP 1/3 BRANCH CIRCUIT HOMERUN, SUBSCRIPT INDICATES PANELBOARD & CIRCUIT DESIGNATION, QUANTITY OF ARROWHEADS DENOTES QUANTITY OF BRANCH CIRCUITS. PROVIDE GREEN GROUND WIRE AND ONE NEUTRAL PER PHASE CONDUCTOR IN EACH CIRCUIT. PROTECT EACH CIRCUIT WITH A 20 AMPERE, 1—POLE OVERCURRENT DEVICE. UNLESS OTHERWISE INDICATED, MINIMUM WIRE SIZE SHALL BE #10 THHN. APPROX SMD MOTION DETECTOR, WALL SWITCH TYPE 0 JUNCTION BOX, SURFACE MOUNT AMERICAN WIRE GAUGE BTU BRITISH THERMAL UNIT DISCONNECT SWITCH 0 FIRE ALARM SYSTEM SMOKE DETECTOR BRITISH THERMAL UNITS PER HOUR POWER PANEL HD FIRE ALARM SYSTEM HEAT DETECTOR CONCRETE PANEL CONCRETE MASONRY UNIT CHWS CHILLED WATER SUPPLY TELECOMMUNICATIONS GROUNDING BUS BAR CHILLED WATER RETURN CARD READER LOCK CHILLED WATER SUPPLY & RETURN CRL CARD READER LOCK db TGB DIA, 0 DIAMETER DN DOWN DWG DRAWING TELECOMMUNICATIONS MAIN GROUNDING BUS BAR EXHAUST AIR EAT ENTERING AIR TEMPERATURE SINGLE INPUT READER INTERFACE MODULE ENTERING DRY BULB SRI ENERGY EFFICIENCY RATIO EF TMGB EH&S ENVIRONMENTAL HEALTH & SAFETY EFF EFFICIENCY MOTOR STARTER EMERGENCY DUAL INPUT READER INTERFACE MODULE ENERGY MANAGEMENT SYSTEM ERL EXISTING TO BE RELOCATED ERM DRI ESP EXTERNAL STATIC PRESSURE ETR EXISTING TO REMAIN — El DOOR CONTACT (POSITION SWITCH) ELECTRICAL SYMBOLS LEGEND Scale: NONE ABBREVIATION DESCRIPTION A AMPERE AC AIR CONDITIONING ACCU AIR COOLED CONDENSING UNIT AD ACCESS DOOR AFF ABOVE FINISH FLOOR AHJ AUTHORITY HAVING JURISDICTION AHU AIR HANDLING UNIT AL ALUMINUM SILL APD AIR PRESSURE DROP " WG APPROX APPROXIMATELY AT ALUMINUM THRESHOLD AWG AMERICAN WIRE GAUGE BTU BRITISH THERMAL UNIT BOP BOTTOM OF PIPE BTUH BRITISH THERMAL UNITS PER HOUR CFM CUBIC FEET PER MINUTE CONC CONCRETE CMU CONCRETE MASONRY UNIT CHWS CHILLED WATER SUPPLY CHWR CHILLED WATER RETURN CHWS&R CHILLED WATER SUPPLY & RETURN CRL CARD READER LOCK db DRY BULB (F) DIA, 0 DIAMETER DN DOWN DWG DRAWING EA EXHAUST AIR EAT ENTERING AIR TEMPERATURE EDB ENTERING DRY BULB EER ENERGY EFFICIENCY RATIO EF EXHAUST FAN EH&S ENVIRONMENTAL HEALTH & SAFETY EFF EFFICIENCY EM EMERGENCY EMS ENERGY MANAGEMENT SYSTEM ERL EXISTING TO BE RELOCATED ERM EXISTING TO BE REMOVED ESP EXTERNAL STATIC PRESSURE ETR EXISTING TO REMAIN EWB ENTERING WET BULB (F) EWT ENTERING WATER TEMPERATURE (F) EX./EXIST EXISTING EXP EXPOSED 'F DEGREES FAHRENHEIT FA FIRE ALARM FACP FIRE ALARM CONTROL PANEL FCU FAN COIL UNIT FD FIRE DAMPER FLA FULL LOAD AMPS FPM FEET PER MINUTE FSD COMBINATION FIRE/SMOKE DAMPER FT OR ' FEET (OF HEAD) GC GENERAL CONSTRUCTION CONTRACTOR GPM GALLONS PER MINUTE GYP GYPSUM BOARD HM HOLLOW METAL HP HORSEPOWER HVAC HEATING, VENTILATION & AIR CONDITIONING HWR HOT WATER RETURN HWS HOT WATER SUPPLY HWS&R HOT WATER SUPPLY & RETURN IP INTERIOR PAINT JB JUNCTION BOX KD KNOCK—DOWN FRAME KW KILOWATTS LAT LEAVING AIR TEMPERATURE (F) LDB LEAVING DRY BULB LWB LEAVING WET BULB LWT LEAVING WATER TEMPERATURE (F) MAX MAXIMUM MBH THOUSAND BTUH MCA MINIMUM CIRCUIT AMPACITY MCB MAIN CIRCUIT BREAKER MDP MAIN DISTRIBUTION PANEL MIN MINIMUM NC NORMALLY CLOSED NO NORMALLY OPEN PD PRESSURE DROP PF PREFINISHED PH PHASE PLAS PLASTER PSI POUNDS PER SQUARE INCH PT PAINT TO MATCH EXISTING PW PLYWOOD RA RETURN AIR RB RUBBER BASE/SILL RF RETURN FAN RL REFRIGERANT LIQUID RS REFRIGERANT SUCTION RRT RUBBER REDUCER STRIP THRESHOLD SA SUPPLY AIR SC SEALED CONCRETE SRI SINGLE READER INTERFACE CARD READER ST STAIN TO MATCH EXISTING TGB TELECOMMUNICATIONS GROUNDING BUSBAR TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR TYP TYPICAL V VOLT VAV VARIABLE AIR VOLUME VB VINYL BASE VCT VINYL COMPOSITION TILE VD VOLUME DAMPER VEL VELOCITY WD WOOD WMP WIRE MESH PARTITION XFMR TRANSFORMER ABBREVIATIONS Scale: NONE J:\PROJECTS—Ithaca\2011\ 11103 CORNELL — NCP\Stimson 201 1 \CAD\ 1 1 1 03-201 1--AMEP—GEN.dwd SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED TO: ARCH El (30X42 IN.) WM elm& 115 METRO PHONE: ARCHI-TECHNOLOGY, LLC www.archi-technology.com PARK ROCHESTER, NY 14623 585.424.1952 Fax: 585.424.4239 A BEARDSLEY DESIGN I iiro ASSOCIATES Architecture, Engineering, Landscape Architecture, P.C. Ph 315.472.6988 x789 Widewaters Parkway Fax 315.472.3523 Dewitt, New York 13214 Waiaf Bl?A@Beardsley.cam ,...J r T—I C CN —J Q I >- z z 4 0 Q rn v1 U Z Q iF- F-1 W z D _i W Z ce 0 U CLIENT: Cornell University PROJECT ®4 NETWORK CONNECTIVITY CD 06/29/12 CONSTRUCTION DOCUMENTS 100 DD 100% DD SUBMISSION 50 DD 05/10/12 50% DD SUBMISSION 20 SD 11/09/11 20% SD SUBMISSION PSD 09/30/11 PRELIMINARY SD SUBMISSION MARK DATE DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/ 12 S.sPJ 4 ,OF NE{NY 0ND N. coo ° %f ©6315'3 �� siotv- AT PROJECT NO: 11.103-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL CHECKED BY: JLB PROJECT MANAGER: DPB SHEET TITLE: GENERAL NOTES l SYMBOLS AND ABBREVIATIONS (AMEP SERIES) PLOT DATE: June 21, 2012 18`-1 7/8" 7 I E I - I - I - N G23 016 GROUND FLOOR IDF (ROOM G23) ARCHITECTURAL -EXISTING / DEMO Scale: 1/4" = 1'-0" 0 2' 4' 8' 8'-1 7/8" 1111.11111111111 I 1111111111.1111 I 7 co I I MIMMIIMMMIMIMMI 016 GROUND FLOOR MTR-GA (ROOM G23) ARCHITECTURAL - NEW WORK Scale: 1/4" = 1'-0" 0 2' 4' 8' ARCHITECTURAL - GENERAL NOTES & CONSTRUCTION KEYED NOTES: A. EXISTING CORRIDOR WALLS REQUIRE A 1—HOUR FIRE RATING PER THE BUILDING CODE OF NEW YORK STATE. FIRE RATING IS INDICATED ON FLOOR PLAN. B. REFER TO DRAWING A4 FOR DETAILS. REMOVE EXISTING CARPET. INFILL EXISTING 2'-2" x 5'-9" WINDOW OPENING IN PARTITION WITH 2 1/2" 1 HOUR RATED SHAFTWALL ASSEMBLY. 5/8" GYPSUM WALLBOARD, 2 1/2" SHAFTWALL STUD, 1" GYPSUM LINER PANEL. PAINT NEW PARTITION TO MATCH EXISTING ON ITR ROOM SIDE. PAINT BACK SIDE OF EXISTING GLASS WITH BLACK PAINT. WINDOW TO REMAIN IN PLACE ON CORRIDOR SIDE. 0 PROVIDE ANTI—STATIC VINYL COMPOSITION TILE FLOOR AND RUBBER BASE. PROVIDE RUBBER TRANSITION STRIP AT EXPOSED EDGE UNDER DOOR. 0 PROVIDE 3/4" AC PLYWOOD ON WALLS INDICATED ON PLAN. PRIME AND PAINT WITH FIRE RETARDANT, LIGHT GREY PAINT ON ALL SURFACES AND EDGES. PLYWOOD TO BE 8 FEET HIGH AND MOUNTED 6 INCHES ABOVE FLOOR. SECURE TO WALL WITH COUNTERSUNK FASTENERS 24 INCHES ON CENTER MAXIMUM, EACH WAY. ANCHOR TO STUDS WITH SCREWS. ANCHOR TO CONCRETE OR MASONRY WITH EXPANSION ANCHORS. 0 PROVIDE DOOR SWEEP. FOR 1" GAP OR LESS PROVIDE PEMKO #29310OCNB, FOR GREATER THAN 1" GAP PROVIDE PEMKO #18137CNB, CLEAR ANODIZED ALUMINUM WITH GREY NYLON BRUSH INSERT. PROVIDE ROOM SIGNAGE TO MATCH EXISTING BUILDING SIGNAGE. SIGN TEXT AS DIRECTED. PROVIDE DOOR HARDWARE FOR ELECTRIFIED CONNECTION TO ACCESS CONTROL SYSTEM: CARD READER LOCK SET: SARGENT HARMONEY LOCKSET, 8200 HARMONY SERIES H1, MATCH ADJACENT FINISH ACCOMMODATE 7 PIN INTERCHANGEABLE BEST CORE. MORTISE LOCK ALL LOCKS TO BE STOREROOM LOCKS (04) FAIL SECURE HARMONY LOCKSETS TO BE INSTALLED BY A CERTIFIED INSTALLER. KEEDEX PART NO. K—DL38A24 DOOR TO FRAME POWER TRANSFER FLEX CONDUIT. McKINNEY ELECTROLYNX RETROFIT CABLE FOR THE DOOR FRAME. SIZE 15'-2". STRIKES: PROVIDE WROUGHT BOXES AND STRIKES WITH PROPER LIP LENGTH TO PROTECT TRIM BUT NOT TO PROTECT MORE THAN 1/8" BEYOND TRIM, FRAME OR INACTIVE LEAF. WHERE REQUIRED, PROVIDE OPEN BACK STRIKE AND PROTECTED TO ALLOW PRACTICAL AND SECURE OPERATION. SARGENT ALUMINUM DOOR CLOSER: SERIES 351. FIRE RATED DOORS REQUIRE SARGENT FIRE RATED CLOSERS. FIRE RATED DOORS: ANYONE DRILLING OR CUTTING A FIRE RATED DOOR MUST BE CERTIFIED. ALL HARDWARE TO BE SATIN CHROME. (US26D) UNLESS NOTED OTHERWISE NOTE: REFER TO DRAWING A4 FOR DETAILS AND SCHEDULES AS APPLICABLE. DRAIN PIPE (ETR) REMOVE EXHAUST FAN ON/OFF SWITCH. 7 \I - CHWS&R AND HWS&R (ETR) REMOVE EX. HWS&R AND CHWS&R BACK TO POINT OF DISCONNECT AND CAP. REMOVE FLOOR MOUNTED FAN COIL UNIT AND ASSOCIATED PIPING. G161 GROUND FLOOR IDF (ROOM G23) MECHANICAL -EXISTING / REMOVALS Scale: 1/4" = 1'-O" LIGHT SWITCH (ETR) 0 2' 4' 8' EXHAUST FAN CONTROLLER E6 EXHAUST FAN ---TIS LFCU alr L -t (ETR) E2 E2 1414 E1 34,4 , -IL G23 016 GROUND FLOOR IDF (ROOM G23) ELECTRICAL -EXISTING / REMOVALS Scale: 1/4" = 1'-0" 0 2' 4' 8' DRAIN PIPE (ETR) 7 7 CAPPED PIPES �1 CHWS&R AND HWS&R (E l 3/4" CONDENSATE ) J 22x8 (ETR) 1016 3 3/4" CHWS&R DN GROUND FLOOR MTR-GA (ROOM G23) MECHANICAL - NEW WORK Scale: 1/4" = 1'-0" 0 2' 4' LIGHT SWITCH (ETR) CP TRGA,3 8' 016 PROVIDE NEW PANEL GROUND FLOOR MTR-GA (ROOM G23) ELECTRICAL - NEW WORK Scale: 1/4" = 1'-0" 0 2' 4' 8' -IVAC & SPRINKLER SYSTEM CONSTRUCTION KEYED NOTES: Mt REMOVE EXHAUST FAN AND ASSOCIATED SPEED CONTROLLER. CAP EX. 22x8 DUCT. 0 PROVIDE NEW HIGH SIDEWALL FAN COIL UNIT. PROVIDE MOUNTING BRACKET SPACER TO ALLOW FOR INSTALLATION OF CHWS&R AND CONDENSATE PIPING. REFER TO DRAWING M4 FOR UNIT SCHEDULE. M3 PROVIDE CAGES FOR SPRINKLERS. NOTE: REFER TO DRAWING M4 FOR DETAILS AND SCHEDULES AS APPLICABLE. ELECTRICAL CONSTRUCTION KEYED NOTES: E1 REMOVE EXISTING RECEPTACLES, CONDUCTORS AND SURFACE METAL RACEWAY TO FIRST ACCESSIBLE JUNCTION BOX. LABEL AND TAPE CONDUCTORS WITH NAME OF ABANDONED CIRCUIT. E2 RE—POSITION EX. LIGHT FIXTURE. E3 2-20A DUPLEX RECEPTACLES IN COMMON BOX, EACH FED FROM DIFFERENT CIRCUIT, AT 18" (UNLESS NOTED OTHERWISE). E4 PROVIDE CONVENIENCE OUTLETS AS INDICATED. PROVIDE (1) 20A/1 P BREAKER, WITH 3—#12 AWG CONDUCTORS, 3/4" CONDUIT. MOUNT AT 24" AFF UNLESS NOTED OTHERWISE. 0 PROVIDE (2) 20A/1P BREAKERS, WITH 6—#10 AWG CONDUCTORS, AND 1" CONDUIT. E6 REMOVE EX. EXHAUST FAN, CONTROLS AND ASSOCIATED RACEWAY TO FIRST ACCESSIBLE JUNCTION BOX. TAPE AND LABEL CONDUCTORS WITH NAME OF ABANDONED CIRCUIT. E7 PROVIDE NEW TMGB PER DETAIL ON E4. E8 PROVIDE EM LIGHT, CONNECT TO UNSWITCHED LEG OF EXISTING LIGHTING CIRCUIT. E9 EXTEND EXISTING FIRE ALARM INITIATING CIRCUIT TO NEW SMOKE DETECTOR AND TO FIRE/SMOKE DAMPER. PROVIDE ALL SHUT DOWNS, TIE—INS AND VERIFICATIONS OF EXISTING ADDESSABLE SYSTEM TO MAKE SURE THE SYSTEM CAN SUPPORT NEW DEVICE(S). PROVIDE TESTING, REPROGRAMMING AND MODIFICATION TO EXISTING FIRE ALARM PANEL AND REMOTE ANNUNCIATORS TO SHOW NEW DEVICE(S). SMOKE DETECTOR SHALL BE INSTALLED AT HIGHEST POINT IN THE CEILING. REMOVE BRANCH CIRCUIT WIRING TO EX. FAN COIL UNIT. REMOVE CONDUCTORS AND RACEWAY TO FIRST ACCESSIBLE JUNCTION BOX. LABEL AND TAPE CONDUCTORS WITH NAME OF ABANDONED CIRCUIT. PROVIDE 2—#10 AWG WITH 1—#10 AWG GROUND FROM FAN COIL UNIT TO PUMP P-1 STARTER IN BASEMENT. CONNECT CONDUCTORS SO THAT WHEN FAN COIL UNIT AUXILIARY RELAY IS ENERGIZED, PUMP P-1 OPERATES WHEN STARTER IS IN AUTOMATIC. PROVIDE POWER CIRCUIT FOR ACCESS CONTROL INTERFACE MODULE / DOOR LOCK. NOTE: REFER TO DRAWING E4 FOR DETAILS AND SCHEDULES AS APPLICABLE. GENERAL NOTES: A. REFER TO DRAWING AMEP—GEN FOR GENERAL NOTES. REFER TO DRAWING T3—GA FOR ADDITIONAL COORDINATION REQUIREMENTS. KEY PLAN J:\PROJECTS-Ithaca12011\11103 CORNELL - NCP\Stimson 2011\CAD\11103-2011--T3-G.dwg SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED TO: ARCH El (30X42 IN.) IMAM gig ARCHI-TECHNOLOGY, LLC 41iiiii/ www.archi-technology.com 115 METRO PARK ROCHESTER, NY 14623 PHONE: 585.424.1952 Fax: 585.424.4239 } Z Q U 2 H CLIENT: uN© rir Cornell University NETWORK CONNECTIVITY PROJECT CD 06/29/12 CONSTRUCTION DOCUMENTS 100 DD 100% DD SUBMISSION 50 DD 05/10/12 50% DD SUBMISSION 20 SD 11/09/11 20% SD SUBMISSION PSD 09/30/11 PRELIMINARY SD SUBMISSION MARK DATE DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/12 AT PROJECT NO: 11103-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL CHECKED BY: JLB PROJECT MANAGER: DPB SHEET TITLE: MTR-GA PARTIAL PLANS AND KEYNOTES AMEP-GA PLOT BY: pbarrie PLOT DATE: June 21, 2012 J:\ PROJECTS—Ithaca\ 2011 \ 11103 CORNELL — NCP\Stimson 2011 \CAD\ 1 1103-2011 --AMEP.dwQ SCALES ON THIS DRAWING ACCURATE WHEN PLOTTED TO: ARCH El (30X42 IN.) EXISTING 1-5/8" U—TRACK MTL. CHANNELS (BEYOND) #12 GA. WIRE TIES SUSPENDED FROM STRUCT. ABOVE / (ALL FOUR CORNERS) —1/2" MTL. FRAMING CHANNELS. SPAN BETWEEN EXISTING SUPPORTS (4—SIDES) 5/8" TYPE "X" GWB CONTINUOUS AROUND PERIMETER THREADED FASTENERS TO MTL. FRAMING EXISTING (RATED) CEILING ASSEMBLY. CEILING TILE ADHERED TO 1/2" GYPSUM BOARD NAILED TO 7/8" ALUM. V—GROOVE CHANNELS REMOVE AND REPLACE CEILING TILES AS REQUIRED FOR ACCESS PANEL INSTALLATION/RESTORATION ACCESS PANEL 2'-0" x 2-0" DOOR TYPICAL NOTE: SEE T2—xx.CA_CP DRAWINGS FOR ADDITIONAL LOCATIONS. PROVIDE ALL COSTS IN BASE BID. NEW ACCESS PANEL — EXISTING GWB CEILING Scale: NONE GENERAL NOTES 1. REFER TO DRAWING AMEP—GEN. rti,niiin MO4 &nil/ 115 METRO PHONE: ARCH -TECHNOLOGY, LLC wwwarchi-technology.corn PARK ROCHESTER, NY 14623 585.424.1952 Fax: 585.424.4239 I- T—I T—I 0 NI 1 J < I Z z 0 c=e (i) U 2 < i i -- II (f) c: UJ II z D ._J LLI z 0 U CLIENT: , thiug, Cornell University PROJECT CONNECTIVITY NETWORK 0). CD 06/29/12 CONSTRUCTION DOCUMENTS 100 DD 100% DD SUBMISSION 50 DD 05/10/12 50% DD SUBMISSION 20 SD 11/09/11 20% SD SUBMISSION PSD 09/30/1 1 PRELIMINARY SD SUBMISSION MARK DATE DESCRIPTION CONSTRUCTION DOCUMENTS ISSUE DATE: 06/29/12 co <k- ( ' <<`,0,0 ..OF NEw D N. cij -1%oN- 0 't. . '-....- , cr 063i5,S g iii.. sciNt" AT PROJECT NO: 11103-2011 OWNER PROJECT NO: 754 DRAWN BY: LP/EL CHECKED BY: J B PROJECT MANAGER: DPB SHEET TITLE: ARCHITECTURAL DETAILS A4