HomeMy WebLinkAboutMilstein Hall - Mechanical UpgradesB07 B0040 B0001 B0044 B0020 B0021 B0060B0061 B0063 B0062 B0064 B04 B02 B0042 B0066 B0007 B10 B0043 B0070 B01 B0004 LOWER PART OF LECTURE RM 101 OPEN TO ABOVE 231 267 372 366 632 121 105 253 169 25 1,615 74 1,183 85 55 45 4,676 63 75 2,375 67 UP UP UP UP UP UP UP UP BENCH BENCHUP UP AREA OF WORK Milstein Hall **Remnants of former Morse Chemical lab in this area; soil may contain chemical and heavy metal residuals. Contact EH&Sprior to any subsurface work.** UP CB CB CB CB CB PROJECT LOCATION CORNE LL U N I V E R SI TYFOUN D E D 5681 AD 105 N. Tioga Street, Suite 200 Ithaca, NY 14850 607-319-4136 labellapc.com DRAWING NAME: It is a violation of New York Education Law Article 145 Sec.7209, for any person, unless acting under the direction of a licensed architect, professional engineer, or land surveyor, to alter an item in any way. If an item bearing the seal of an architect, engineer, or land surveyor is altered; the altering architect, engineer, or land surveyor shall affix to the item their seal and notation "altered by" followed by their signature and date of such alteration, and a specific description of the alteration. DRAWING NUMBER: DATE: ISSUED FOR: DRAWN BY: REVIEWED BY: PROJECT NUMBER: Cornell University 9/20/2019 9:17:13 AMC:\Users\msnyder\Documents\Revit Local Files\2190823 Milstein Hall Mech_R19_MSnyder.rvtG001 COVER SHEET MMJ EJL 09/20/19 CONSTRUCTION 2190823 ITHACA, N.Y. 14853-3701 MILSTEIN HALL MECH UPGRADES CORNELL UNIVERSITY MILSTEIN HALL © 2019 LaBella Associates MILSTEIN HALL MECH UPGRADES DRAWING LIST Sheet Number Sheet Name Sheet Issue Date Revision Number G001 COVER SHEET 09/20/19 A101 PARTIAL PLANS AND ELEVATIONS 09/20/19 M001 MECHANICAL LEGEND SHEET 09/20/19 M010 BASEMENT MECHANICAL DEMOLITION PLAN 09/20/19 M101 BASEMENT MECHANICAL PLAN 09/20/19 M501 MECHANICAL DETAILS AND SCHEDULES 09/20/19 M701 MECHANICAL CONTROLS 09/20/19 F101 BASEMENT FIRE PROTECTION PLANS 09/20/19 E101 PARTIAL BASEMENT ELECTRICAL REMOVAL AND POWER PLAN 09/20/19 SITE LOCATION - MILSTEIN HALL KEY PLAN - BASEMENT SCOPE OF WORK GENERAL SYMBOLS LEGEND DRAWING INDEX BUILDING CODE SUMMARY APPLICABLE CODES - 2015 (EXISTING) IBC (ADOPTED BY NEW YORK STATE) - 2015 IPC - 2015 IMC - 2014 NEC LINETYPE: TO BE PROVIDED / NEW LINETYPE: DEMOLITION / TO BE RELOCATED LINETYPE: EXISTING TO REMAIN POINT OF CONNECTION POINT OF DISCONNECTION # #DEMOLITION KEYED NOTE CONSTRUCTION KEYED NOTE DRAWING REVISION NOTE# ENLARGED DETAIL 1 X-100 SECTION MARKER 1 X-100 1 X-100 INTERIOR ELEVATION X-100 EXTERIOR ELEVATION THE SCOPE OF THIS PROJECT IS TO EXPAND THE FOOTPRINT OF THE EXISTING MODEL ASSEMBLY STUDIO IN CORNELL’S MILSTEIN HALL AND ADJUST THE VENTILATION AND MECHANICAL SYSTEMS TO MATCH. ARCHITECTURAL: THE PARTITION WALL BETWEEN THE EXISTING MODEL ASSEMBLY STUDIO AND CORRIDOR IS BEING REMOVED AND REWORKED INTO AN ENTRY VESTIBULE. A PORTION OF THE SOUTH FACING CURTAIN WALL MULLION AND GLAZING WILL BE MODIFIED TO ACCEPT A NEW EXHAUST LOUVER. MECHANICAL: THE EXISTING AIR HANDLING UNIT WILL BE REPLACED. A NEW EXHAUST FAN WITH FILTER BANK WILL BE INSTALLED AS WELL AS A NEW LOUVER IN THE SOUTH CURTAIN WALL. THE HEATING SOURCE AT THE AIR HANDLER WILL BE MAINTAINED AS HOT WATER TO MATCH THE EXISTING SYSTEM. ASSOCIATED CONTROLS WILL BE ADDED AND ADAPTED FROM THE EXISTING BUILDING MANAGEMENT SYSTEM. THERE IS NO ANTICIPATED PLUMBING SCOPE OF WORK. FIRE PROTECTION: THE EXISTING NFPA 13 WET-PIPE FIRE SUPPRESSION SYSTEM SHALL REMAIN AND BE ADAPTED AS NECESSARY FOR PROPER COVERAGE OF THE SPACE. THERE WILL BE NO ADDITIONAL SPRINKLER HEADS ADDED TO THE EXISTING SYSTEM. ELECTRICAL: MODIFY EXISTING AND ADD NEW CIRCUITRY AS NECESSARY TO SUPPORT MECHANICAL. PROVIDE SUPPLEMENTAL LIGHTING, SWITCHING AND OUTLETS TO MATCH EXISTING. Revisions NO: DATE: DESCRIPTION: BRANCH OFF TOP OF PIPE PIPE TURNED UP PIPE TURNED DOWN BRANCH OFF BOTTOM OF PIPE REDUCER PIPE BREAK BALL VALVE BUTTERFLY VALVE GATE VALVE DRAWING SYMBOLS ANGLE VALVE CHECK VALVE BALANCE VALVE SHUT OFF VALVE (GATE, BALL, OR BUTTERFLY - REFER TO SPECS) MOTOR OR SOLENOID CONTROL VALVE (3-WAY) STEAM TRAP MOTOR OR SOLENOID CONTROL VALVE PRESSURE REDUCING VALVE TRIPLE DUTY VALVE RELIEF VALVE STRAINER UNION PRESSURE GAUGE PUMP EQUIPMENT TO BE REMOVED KEYNOTE SECTION CALLOUT NEW CONNECTION TO EXISTING REMOVE TO THIS POINT) DEMOLITION KEYNOTE DETAIL NUMBER RETURN AIR SUPPLY AIR DUCT (DIMENSIONS SHOWN IN DUCT. DIMENSIONS IN INCHES.) DUCT SECTION - EXHAUST AIR DUCT SECTION - SUPPLY AIR DUCT SECTION - RETURN AIR 14" ROUND DUCT VOLUME DAMPER DUCT (DIMENSIONS SHOWN BY LEADER. DIMENSIONS IN INCHES.) 14" Ø MITERED ELBOW W/ TURNING VANES INSULATED DUCT (DIM. IS INTERNAL) EXHAUST GRILLE REGISTER OR GRILLE - TOP NUMBER REPRESENTS TAG, SEE SCHEDULE; BOTTOM NUMBER REPRESENTS CFM. RETURN GRILLE DIFFUSER - LETTER REPRESENTS TAG, SEE SCHEDULE; NUMBER REPRESENTS CFM SUPPLY DIFFUSER T S H THERMOSTAT SENSOR HUMIDISTAT APPLICABLE CODES ABBREVIATIONS % AC ADJ AFF AFG ALT AMB AMP ANSI APPROX AVG BFP BHP BLDG BO BSMT BTU BV CAP CIP CLG CLR CO COL CONN CONC CONT CU FT CV DCDA DCV DCW DEMO DHW DIA DIP DWH DWV DWG (E) ENGR EQ EST ETR EWH EWT EX EXIST EXP EXT °F PERCENT ALTERNATING CURRENT ADJACENT ABOVE FINISHED FLOOR ABOVE FINISHED GRADE ALTERNATE AMBIENT AMPERE (AMP,AMPS) AMERICAN NATIONAL STANDARD INSTITUTE APPORXIAMTE (LY) AVERAGE BACKFLOW PREVENTER BRAKE HORSEPOWER BUILDING BOTTOM OF BASEMENT BRITISH THERMAL UNIT BALANCING VALVE CAPACITY CAST IRON PIPE CEILING CLEAR CLEANOUT or CARBON MONOXIDE COLUMN CONNECTION CONCRETE CONTINUOUS CUBIC FEET VALVE FLOW COEFFICIENT DOUBLE CHECK DETECTOR ASSEMBLY DETECTOR CHECK VALVE DOMESTIC COLD WATER DEMOLISH or DEMOLITION DOMESTIC HOT WATER DIAMETER DUCTILE IRON PIPE DOMESTIC WATER HEATER DRAIN, WASTE, & VENT DRAWING EXISTING ENGINEER EQUAL ESTIMATED EXISTING TO REMAIN ELECTRIC WATER HEATER ENTERING WATER TEMPERATURE EXISTING EXISTING EXPANSION EXTERIOR DEGREES FAHRENHEIT FA FIN FL FLA FPM FPS FT FUT GA GAL GC GPM GPD GPH HD HG HORIZ HP HPC HPS HR HVAC HZ ID IN INSUL INT IPS INV KW KWH LBS LF LG LOC LPC LPS LRA LWT MATL MAX MBH MECH MFG MIN MISC MOCP MPC MPS MTG N/A NC FREE AREA FINISHED FLOOR FULL LOAD AMPS FEET PER MINUTE FEET PER SECOND FOOT OR FEET FUTURE GAGE OR GAUGE GALLONS GENERAL CONTRACTOR GALLONS PER MINUTE GALLONS PER DAY GALLONS PER HOUR HEAD MERCURY HORIZONTAL HORSEPOWER HIGH PRESSURE CONDENSATE HIGH PRESSURE STEAM HOUR HEATING, VENTILATING, AND AIR CONDITIONING FREQUENCY DIAMTER, INSIDE INCH INSULATION INTERIOR IRON PIPE SIZE INVERT KILOWATT KILOWATT HOUR POUNDS LINEAR FEET LENGTH LOCATION LOW PRESSURE CONDENSATE LOW PRESSURE STEAM LOCKED ROTOR AMPS LEAVING WATER TEMPERATURE MATERIAL MAXIMUM BTU PER HOUR (THOUSAND) MECHANICAL MANUFACTURER MINIMUM MISCELLANEOUS MAXIMUM OVERCURRENT PROTECTION MEDIUM PRESSURE CONDENSATE MEDIUM PRESSURE STEAM MOUNTING NOT APPLICABLE NORMALLY CLOSED NIC NO NPT NRS NTS OC OD OS&Y PC PLBG PH PRESS PSF PSI PSIG PRV RCVR RECIRC RHW RO RPDA RPM RPZ SCH SPEC SPLY SQ SQ FT SQ IN STD SUCT T'STAT TBD TC TD TEMP TMV TO TYP V VAC VAR VEL VIF VOL W W/ W/O WCO WHA WM WPD WT WWP NOT IN CONTRACT NORMALLY OPEN NATIONAL PIPE TREAD NON-RISING STEM NOT TO SCALE ON CENTER DIAMETER, OUTSIDE OUTSIDE SCREW AND YOKE PLUMBING CONTRACTOR PLUMBING PHASE (ELECTRICAL) PRESSURE POUNDS PER SQUARE FOOT POUNDS PER SQUARE INCH PSI GUAGE PRESSURE REDUCING VALVE RECEIVER RECIRCULATE HOT WATER RE-CIRCULATION ROUGH OPENING REDUCED-PRESSURE DETECTOR ASSY. REVOLUTIONS PER MINUTE REDUCED-PRESSURE ZONE STEAM CAPTURE HOOD SPECIFICATION SUPPLY SQUARE SQUARE FOOT (FEET) SQUARE INCH (INCHES) STANDARD SUCTION THERMOSTAT TO BE DETERMINED TEMPERATURE CONTROL CONTRACTOR TEMPERATURE DIFFERENCE TEMPERATURE THERMOSTATIC MIXING VALVE TOP OF TYPICAL VOLT VACUUM VARIABLE VELOCITY VERIFY IN FIELD VOLUME WATT WITH WITH OUT WALL CLEANOUT WATER HAMMER ARRESTER WATER METER WATER PRESSURE DROP WEIGHT WORKING WATER PRESSURE NOTE: SOME ABBREVIATIONS MAY NOT BE USED ON DRAWINGS 1 8 750 A 125 18/8 18/8 18/8 1 M-2 A M-2 A M EQUIPMENT DESIGNATIONS HC HP HWP HX PHC L PRV VAV UH CA AHU CFP CC B CHP CH CT CP CAV EF FT FCU CUH AS CRU CV VD R CRAC DHW ET FB PRG HU MAU P PPU RTU RCP UV WS CU ACU AD BDD MD VFD EXISTING DUCTWORK, PIPE, EQUIPMENT NEW DUCTWORK, PIPE, EQUIPMENT DUCTWORK, PIPE, EQUIPMENT TO BE REMOVED CHWS GHR CHILLED WATER SUPPLY GLYCOL HOT WATER RETURN CHILLED WATER RETURNCHWR HPLS HPLR HEAT PUMP LOOP SUPPLY HEAT PUMP LOOP RETURN GLYCOL HOT WATER SUPPLY GHS HPC CA NG C HIGH PRESSURE CONDENSATE COMPRESSED AIR NATURAL GAS CONDENSATE VAC VACUUM HPS HIGH PRESSURE STEAM LPC LOW PRESSURE CONDENSATE LPS LOW PRESSURE STEAM MPC MPS MEDIUM PRESSURE STEAM RHL REFRIGERANT H/L PRESSURE RL RS REFRIGERANT LIQUID REFRIGERANT SUCTION SV STEAM VENT CD CONDENSATE DRAIN CTR CTS COOLING TOWER RETURN COOLING TOWER SUPPLY HWS HWR HOT WATER SUPPLY HOT WATER RETURN DN DIRECTION OF FLOW DIRECTION OF PITCH MU MAKE-UP WATER PC PUMPED CONDENSATE HOT WATER PUMP HEAT PUMP HEATING COIL HEAT EXCHANGER PREHEAT COIL LOUVER PRESSURE REDUCING VALVE VARIABLE AIR VOLUME BOX UNIT HEATER AIR COMPRESSOR COOLING COIL BOILER AIR HANDLING UNIT CHEMICAL FEED PUMP COOLING TOWER CHILLER CONDENSATE PUMP CHILLED WATER PUMP EXHAUST FAN CONSTANT AIR VOLUME BOX FINNED TUBE FAN COIL UNIT CABINET UNIT HEATER AIR SEPARATOR CONDENSATE RETURN UNIT CONTROL VALVE VOLUME DAMPER REGISTER COMPUTER ROOM UNIT DOMESTIC WATER HEATER EXPANSION TANK FILTER BOX GAS PRESSURE REGULATOR HUMIDIFIER MAKE UP AIR UNITS PUMP PUMPING PACKAGED UNIT ROOF TOP UNIT RADIANT CEILING PANEL UNIT VENTILATOR WATER SOFTENER CONDENSING UNIT AIR CONDITIONING UNIT ACCESS DOOR BACK DRAFT DAMPER MOTORIZED DAMPER VARIABLE SPEED DRIVE FIRE DAMPER SD SMOKE DAMPER F/S COMBINATION FIRE / SMOKE DAMPER AD AD AD ACCESS DOOR TO BE LOCATED ON MOST ACCESSIBLE SIDE OF DUCT ACCESS DOOR TO BE LOCATED ON MOST ACCESSIBLE SIDE OF DUCT ACCESS DOOR TO BE LOCATED ON MOST ACCESSIBLE SIDE OF DUCT FD WALL OR DUCT MOUNTED SUPPLY GRILLE WALL OR DUCT MOUNTED RETURN OR EXHAUST GRILLE VRF FAN COIL CASSETTE UNIT MOTOR OPERATED DAMPER FLEX DUCT NOTE: SOME ABBREVIATIONS MAY NOT BE USED ON DRAWINGS BUILDING CODE OF NEW YORK STATE MECHANICAL CODE OF NEW YORK STATE FIRE CODE OF NEW YORK STATE PLUMBING CODE OF NEW YORK STATE ENERGY CONSERVATION CODE OF NEW YORK STATE ACCESSIBLE AND USABLE BUILDING AND FACILITIES-CABO/ANSI A117.1 NATIONAL ELECTRIC CODE NATIONAL FIRE CODE NFPA 13 1 2 3 4 5 6 7 8 NOTE: NOT ALL SYMBOLS, ABBREVIATIONS AND EQUIPMENT DESIGNATIONS MAY APPLY TO THIS PARTICULAR PROJECT. ANY ADDITIONS OR OMISSIONS FROM THIS LEGEND SHEET DOES NOT IMPLY INCLUSION AND/ OR EXCLUSIONS OF ANY PARTICULAR ITEM FROM THIS PROJECT. MEDIUM PRESSURE CONDENSATE GENERAL NOTES C02 CARBON DIOXIDE SENSOR IW INDIRECT WASTE 18" x 8" FLAT OVAL DUCT18/8 VD 105 N. Tioga Street, Suite 200 Ithaca, NY 14850 607-319-4136 labellapc.com DRAWING NAME: It is a violation of New York Education Law Article 145 Sec.7209, for any person, unless acting under the direction of a licensed architect, professional engineer, or land surveyor, to alter an item in any way. If an item bearing the seal of an architect, engineer, or land surveyor is altered; the altering architect, engineer, or land surveyor shall affix to the item their seal and notation "altered by" followed by their signature and date of such alteration, and a specific description of the alteration. DRAWING NUMBER: DATE: ISSUED FOR: DRAWN BY: REVIEWED BY: PROJECT NUMBER:9/20/2019 9:00:40 AMC:\Users\mjeffery\Documents\Revit Local Files\2190823 Milstein Hall Mech_R19_mjeffery.rvtM001 MECHANICAL LEGEND SHEET MMJ EJL 09/20/19 CONSTRUCTION 2190823 ITHACA, N.Y. 14853-3701 MILSTEIN HALL MECH UPGRADES CORNELL UNIVERSITY MILSTEIN HALL © 2019 LaBella Associates DUCTWORK GENERAL NOTES 1 HVAC CONTRACTOR TO PROVIDE CRANE AND NECESSARY EQUIPMENT TO HOIST ROOF MOUNTED HVAC EQUIPMENT FROM SITE TO FINAL ROOF LOCATION. GENERAL CONTRACTOR TO PROVIDE ALL ROOF PENETRATIONS REQUIRED TO ACCOMMODATE HVAC EQUIPMENT OPENINGS AND SET CURBS. HVAC CONTRACTOR TO COORDINATE EXACT LOCATION OF PENETRATIONS WITH G.C. AND SHALL ASSIST WITH SETTING ALL HVAC EQUIPMENT ROOF CURBS. HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR TEMPORARY CAP OF ALL ROOF PENETRATIONS IN INTERIM FROM TIME PENETRATIONS ARE COMPLETE TO TIME EQUIPMENT IS SET ON ROOF CURBS. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR FLASHING ALL EQUIPMENT CURBS AND OTHER HVAC RELATED ROOF PENETRATIONS. HVAC CONTRACTOR SHALL REMOVE AND DISPOSE OF TEMPORARY CAP WHEN EQUIPMENT IS SET IN PLACE. 2 PROVIDE 45 DEGREE SHOE-TAP FITTING AND VOLUME DAMPER AT ALL BRANCH DUCT TAKE-OFFS (TOP, SIDE AND BOTTOM) FOR SUPPLY, RETURN AND EXHAUST AIR, UNLESS SHOWN OR NOTED OTHERWISE. VOLUME DAMPERS SHALL BE OMITTED FROM VAV INLET BRANCH DUCTWORK. 3 COORDINATE HVAC INSTALLATION WITH STRUCTURE, CEILING, LIGHTING, CONDUIT, HEATING AND DOMESTIC PIPING, STORM AND SANITARY DRAIN PIPING (ALL TRADES). PREPARE AND SUBMIT FULL COORDINATION DRAWINGS FOR APPROVAL BY ENGINEER PRIOR TO ORDERING MATERIALS AND/OR BEGINNING CONSTRUCTION. 4 INSULATE OR LINE DUCTWORK AS SPECIFIED IN THE MECHANICAL INSULATION AND METAL DUCTS SPECIFICATIONS OR NOTED ON DRAWINGS. NOTE THAT DUCT SIZES SHOWN ON DRAWINGS ARE INSIDE NET CLEAR DIMENSIONS. 5 ALL 90 DEGREE RECTANGULAR ELBOWS AND DUCTWORK TEES SHALL BE HARD MITERED WITH FACTORY TURNING VANES. TURNING VANES SHALL BE OMITTED FROM AIR TRANSFER DUCT ELBOWS. 6 ALL DUCTWORK PASSING THROUGH NON-FIRE RATED WALLS TO BE SEALED AROUND PERIMETER (BOTH SIDES) WITH DRYWALL JOINT COMPOUND OR APPROVED EQUAL. 7 HVAC CONTRACTOR TO PROVIDE ALL WALL & ROOF PENETRATIONS 8"x8" OR SMALLER. ALL PENETRATIONS LARGER THAN 8"x8" IS THE RESPONSIBILITY OF THE G.C. COORDINATE ALL 8"x8" OR LARGER PENETRATION LOCATIONS WITH G.C. LINTELS (BY G.C.) REFER TO STRUCTURAL DRAWINGS FOR LINTEL SCHEDULE. PENETRATIONS AND LINTEL LOCATIONS TO BE COORDINATED WITH G.C. AND DOCUMENTED ON COORDINATION DRAWINGS. 8 BALANCING CONTRACTOR TO SET MINIMUM OUTSIDE AIR DAMPER POSITION TO MEET VENTILATION AIR QUANTITIES REQUIRED AS SHOWN ON PLANS OR LISTED IN EQUIPMENT SCHEDULES. 9 ALL SUPPORT OF EQUIPMENT, DUCTWORK AND ASSOCIATED DISTRIBUTION SERVICES SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE BUILDING CODE OF NEW YORK STATE. THE DISCIPLINE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE STRUCTURAL STEEL WHERE REQUIRED IN ORDER TO SUPPORT EQUIPMENT, DUCTWORK AND ASSOCIATED DISTRIBUTION SERVICES WHERE THE BUILDING STRUCTURE SPACING IS TOO GREAT TO ALLOW DIRECT SUPPORT. THE DISCIPLINE CONTRACTOR SHALL BE RESPONSIBLE FOR CONFIRMATION OF ALL SUPPORTS AND SHALL OBTAIN THE PROFESSIONAL SERVICE OF A STRUCTURAL ENGINEER LICENSED IN THE STATE OF NEW YORK AND FURNISH SEALED DRAWINGS AND DETAILS ILLUSTRATING SUCH SUPPORTS AND COMPLIANCE METHODS. 10 THE ABOVE GENERAL NOTES APPLY TO ALL HVAC CONSTRUCTION DOCUMENT DRAWINGS. PIPING GENERAL NOTES 1 COORDINATE HVAC PIPING INSTALLATION WITH DUCTWORK, STRUCTURE, CEILING, LIGHTING, CONDUIT, HEATING AND DOMESTIC PIPING, STORM AND SANITARY DRAIN PIPING (ALL TRADES). PREPARE AND SUBMIT FULL COORDINATION DRAWINGS FOR APPROVAL BY ENGINEER PRIOR TO ORDERING MATERIALS AND/OR BEGINNING CONSTRUCTION. 2 PROVIDE ALL PIPING PENETRATIONS THROUGH WALLS, FLOORS AND DECKS REQUIRED WHERE SHOWN. SEAL ALL EXTERIOR WALL PENETRATIONS WEATHER TIGHT. 3 ALL PIPING PASSING THROUGH WALLS TO BE FIRE STOPPED AND SEALED AROUND PERIMETER WITH DRYWALL JOINT COMPOUND OR APPROVED EQUAL. 4 HVAC CONTRACTOR IS RESPONSIBLE FOR DRAINING, FILLING WITH WATER/CHEMICALS, AND AIR REMOVAL ASSOCIATED WITH ALL PIPING WORK. 5 THE ABOVE GENERAL NOTES APPLY TO ALL HVAC CONSTRUCTION DOCUMENT DRAWINGS. Revisions NO: DATE: DESCRIPTION: B0044 B09 B0046 267 2762 1032 UP UP T 14Ø 6Ø 12Ø 6Ø 6Ø 6Ø 8Ø8Ø 0 0 134134 134 134 12/12 12/16VD VD VD VD VD VD VD VDVD 1 3 2 EXISTING IN-FLOOR RADIATION TO REMAIN. TYP. EXISTING 67"x28" LOUVER TO REMAIN. 1 1 5 DEMOLITION NOTES: REMOVE AHU AND ALL ASSOCIATED DUCTWORK. DEMO AND REMOVE EXISTING AHU OA CONNECTION TO LOUVER. EXISTING 67"x28" LOUVER TO REMAIN. REMOVE EXISTING TEMPERATURE SENSOR AND HOLD ON SITE FOR REINSTALLATION. MAINTAIN EXISTING CONTROL WIRE. DEMO AND REMOVE FENCE ENCLOSURE. COORDINATE WITH ARCHITECTURAL. DEMO AND REMOVE EXISTING 1 1/4" HWS AND HWR AT ISOLATION VALVE. SEE M101 FOR INSTALLATION PLAN AND NOTES. REMOVE AND RELOCATE EYEWASH. REMOVE PIPING AS NECESSARY FOR RELOCATION. 1 2 3 4 5 4 1 3 105 N. Tioga Street, Suite 200 Ithaca, NY 14850 607-319-4136 labellapc.com DRAWING NAME: It is a violation of New York Education Law Article 145 Sec.7209, for any person, unless acting under the direction of a licensed architect, professional engineer, or land surveyor, to alter an item in any way. If an item bearing the seal of an architect, engineer, or land surveyor is altered; the altering architect, engineer, or land surveyor shall affix to the item their seal and notation "altered by" followed by their signature and date of such alteration, and a specific description of the alteration. DRAWING NUMBER: DATE: ISSUED FOR: DRAWN BY: REVIEWED BY: PROJECT NUMBER:9/20/2019 9:00:45 AMC:\Users\mjeffery\Documents\Revit Local Files\2190823 Milstein Hall Mech_R19_mjeffery.rvtM010 BASEMENT MECHANICAL DEMOLITION PLAN MMJ EJL 09/20/19 CONSTRUCTION 2190823 ITHACA, N.Y. 14853-3701 MILSTEIN HALL MECH UPGRADES CORNELL UNIVERSITY MILSTEIN HALL © 2019 LaBella Associates 1/4" = 1'-0"M010 1 BASEMENT DUCTWORK DEMOLITION PLAN 1/2" = 1'-0"M010 2 BASEMENT PIPING DEMOLITION PLAN Revisions NO: DATE: DESCRIPTION: B0044 B0046 267 1032 UP UP T VD VD 36/10 EA 1 477 RELOCATED TEMPERATURE SENSOR EF-1 14Ø SA CUH-1 T EXISTING FIN TUBE ACTUATOR TO REMAIN VD VD L-1 54"x18" 1 477 28/10 EA FB-1 2 M M 4 1 VD A 331 A 331 A 331 A 331 A 331 16Ø SA 10Ø SA 24/12 SA 24/12 SA BLANK-OFF AND INSULATE REMAINING LOUVER FACE. EXISTING 67"x28" LOUVER 48"x28" INSULATED PLENUM BEHIND LOUVER WITH MOTORIZED DAMPER AND ACCESS DOOR. BLANK-OFF AND INSULATE REMAINING LOUVER FACE BEHIND COLUMN. 2 702 30/20 RA 5 2FLEX DUCT TRANSITION DUCT TO 24"x12" TIGHT TO DECK ABOVE. M AHU-5 AD AD FLEX DUCT FLEX DUCT 14/39 RA UP FROM AHU-5 14/39 MOTORIZED DAMPER VD VD VD 1 477 1 477 20/10 14/10 VD 1288 7 8 8 A 331 3 2 1 1/4" GHR 1 1/4" GHS AHU-5 STRAINER CONTROL VALVE BALANCING VALVE (7.1 GPM) 6 KEY NOTES: PROVIDE NEW LOUVER AND INSTALL IN NEW MULLION FRAME. REFER TO ARCHITECTURAL. COORDINATE WIRE MESH FENCE AS NECESSARY TO MAINTAIN CLEARANCE FOR NEW AHU DUCT AND PIPING AS SHOWN. CONNECT NEW 1 1/4" GWS/R PIPING TO EXISTING 1 1/4" GWS/R PIPING BELOW. REBALANCE FLOW TO EXISTING AHU TO 7.1 GPM. PROVIDE ANY NECESSARY RECALIBRATION OF EXISTING CENTRAL PUMPING SYSTEM PRESSURE DIFFERENTIAL. PROVIDE NEW OA DUCT CONNECTION TO EXISTING LOUVER. PROVIDE AND INSTALL MOTORIZED DAMPER IN FACE OF DUCT CONNECTION. EXTEND TO NEW AHU-5. TRANSITION 30"x20" RETURN AIR GRILLE TO FULL SIZE RA OPENING AT AHU-5. FRAME WIRE MESH FENCE AROUND DUCT. PROVIDE PIPE AND TRIM AT COIL CONNECTION PER DETAIL 5/M501. RELOCATE EYEWASH. MAINTAIN REQUIRED CLEARANCES FOR EYEWASH. PROVIDE TEMPERED WATER PIPING, DOMESTIC WATER PIPING AND SANITARY PIPING AS REQUIRED FOR RELOCATION. REFER TO M100, GENERAL PIPING NOTES FOR SPECIFICATIONS. REFER TO 6/M501 FOR INSTALLATION DETAIL. COORDINATE DUCTWORK WITH EXISTING SPRINKLER LOCATIONS. MAINTAIN REQUIRED CLEARANCES FROM SPRINKLER HEADS. 1 2 3 4 5 6 7 8 GENERAL PIPING NOTES: 1.) IF EXISTING CONSTRUCTION IS DAMAGED DURING WORK BY THIS CONTRACTOR, REPAIR AND/OR REPLACE WITH SIMILAR OR LIKE MATERIALS AS MUCH AS POSSIBLE, SUBJECT TO ENGINEERS APPROVAL. 2.) COORDINATE WORK SCHEDULE AND SHUTDOWNS WITH THE OWNER AND OTHER TRADES PRIOR TO DEMOLITION. 3.) ALL EXISTING PIPING TO REMAIN SHALL BE RECONNECTED TO ACTIVE SERVICE PIPING. 4.) ALL PIPING TO BE REMOVED, SHALL BE REMOVED BACK TO ACTIVE PIPING AND CAPPED. VALVE AND CAP ALL WATER PIPING. REMOVE ALL INACTIVE PIPING UNLESS NOTED. 5.) PLUG HOLES IN EXISTING CONSTRUCTION LEFT BY THE REMOVAL OF PIPING OR EQUIPMENT. MAINTAIN ANY FIRE/SMOKE RATINGS. USE UL LISTED FIRE STOP ASSEMBLIES. SUBMIT ON ASSEMBLIES TO BE USED. 6.) REMOVE EXISTING CONSTRUCTION IN THE WAY OF NEW WORK. PROTECT BUILDING AND FURNISHINGS FROM DAMAGE. 7.) COORDINATE ALL WORK WITH OTHER TRADES. 8.) ALL PLUMBING SYSTEMS SHALL COMPLY WITH THE CURRENT EDITION OF THE ICC PLUMBING CODE, NY STATE SUPPLEMENT TO THE CODE AND THE REQUIREMENTS OF THE AHJ. 9.) DOMESTIC AND TEMPERED WATER PIPE FITTINGS AND WETTED MATERIALS TO BE IN COMPLIANCE WITH NSF-61 10.) PLUMBING PIPE, ACCESSORIES AND EQUIPMENT SHALL BE INSTALLED ACCORDING TO THE MANUFACTURERS INSTRUCTIONS. 11.) FLUSHING AND DISINFECTION FOR DOMESTIC WATER AND EMERGENCY WATER PIPING IS TO BE PERFORMED IN ACCORDANCE WITH THE ICC PLUMBING CODE, THE REQUIREMENTS OF THE AHJ AND CORNING STANDARD PIPING SPECIFICATION. 12.) PROVIDE SUBMITTALS FOR THE FOLLOWING ITEMS: a. MIXING VALVE ASSEMBLY. b. DOMESTIC WATER PIPE AND FITTINGS. c. VALVES, BALANCE VALVES, STOPS AND SUPPLY TUBES. d. EMERGENCY FIXTURES AND FITTINGS, FLOW SWITCH, ETC. e. PIPE SUPPORTS AND STRUTS. f. PIPE INSULATION. g. REDLINE RECORD DRAWINGS. 13.) DOMESTIC HOT AND COLD WATER PIPING: DRAWN -TEMPER WROUGHT COPPER TUBE, ASTM B 88, TYPE K WITH WROUGHT COPPER FITTINGS. SOLDER JOINT USING LEAD FREE SOLDER CONTAINING 96% TIN, 4% SILVER, FLUX AND SOLDER SHALL BE NSF-61 LISTED. 14.) DOMESTIC HOT AND COLD WATER VALVES TO BE 2 PIECE, BRONZE BODY, FULL PORT, BALL VALVES WITH SS BALL AND STEM, NSF 61 COMPLIANT. VALVES MAY BE THREADED OR SOLDERED END CONNECTION. PROVIDE LOCKING LATCH LEVER. VALVES TO BE APOLLO SERIES 77-CLF-240-27 OR APPROVED EQUAL. 15.) HANGERS AND PIPE SUPPORTS TO BE PROVIDED AT THE SPACING NOTED IN THE ICC PLUMBING CODE. PROVIDE SWAY BRACING WHERE STRAIGHT LENGTH IS GREATER THAN 20 FEET. 105 N. Tioga Street, Suite 200 Ithaca, NY 14850 607-319-4136 labellapc.com DRAWING NAME: It is a violation of New York Education Law Article 145 Sec.7209, for any person, unless acting under the direction of a licensed architect, professional engineer, or land surveyor, to alter an item in any way. If an item bearing the seal of an architect, engineer, or land surveyor is altered; the altering architect, engineer, or land surveyor shall affix to the item their seal and notation "altered by" followed by their signature and date of such alteration, and a specific description of the alteration. DRAWING NUMBER: DATE: ISSUED FOR: DRAWN BY: REVIEWED BY: PROJECT NUMBER:9/20/2019 9:00:51 AMC:\Users\mjeffery\Documents\Revit Local Files\2190823 Milstein Hall Mech_R19_mjeffery.rvtM101 BASEMENT MECHANICAL PLAN MMJ EJL 09/20/19 CONSTRUCTION 2190823 ITHACA, N.Y. 14853-3701 MILSTEIN HALL MECH UPGRADES CORNELL UNIVERSITY MILSTEIN HALL © 2019 LaBella Associates 1/4" = 1'-0"M101 1 BASEMENT DUCTWORK PLAN 1/2" = 1'-0"M101 2 BASEMENT PIPING PLAN Revisions NO: DATE: DESCRIPTION: MAIN SUPPLY DUCT PLAN VIEW EXHAUST AND/OR RETURN BRANCH DUCT PLAN VIEW MAIN RETURN OR EXHAUST DUCT BRANCH DUCT (TO ROOM) BRANCH DUCT (FROM ROOM) 45° 45°W W W 4" MIN 8" MAX SUPPLY BRANCH DUCT TAKE-OFF W 4" MIN 8" MAX FLEXIBLE CONNECTION (TYP 2) (DUROLON) HANG EXHAUST FAN FROM EXISTING STRUCTURE. WITH ELASTOMETRIC ISOLATION HANGERS PROVIDE ADDITIONAL CROSS MEMBERS AS REQUIRED TO POSITION HANGERS. TRANSITIONS AS REQUIRED (TYP 2) PROVIDE DUCT ACCESS DOOR NOTES 1/4W', 4" MINIMUM VOLUME DAMPER WITH LOCKING TYPE INDICATOR QUADRANT AND SADDLE TO CLEAR INSULATION CLINCH COLLAR USE FOR SYMBOL WHERE BRANCH DUCT AIR QUANTITY IS LESS THAN 1000 CFM. NOT TO BE USED AS SUBSTITUTE FOR ELBOW 1. 2. BRANCH DUCT 3/8" SQUARE ROD END BEARING MAIN DUCT WSUPPLY AIR FLOW RETURN/EXHAUST AIR FLOW ..45.00°DUCT MOUNTED DIFFUSER EXISTING CURTAIN WALL SYSTEM PROVIDE CAULK & SEALANT ALL AROUND BIRD SCREEN IN REMOVABLE FRAME (WHEN SCHEDULED) L-1 PROVIDE LOUVER PER SCHEDULE EXHAUST DUCT PER PLANS PROVIDE FASTENERS, 6" O.C. (MIN.) OR PER MANUFACTURERS RECOMMENDATIONS M ACCESS DOOR W/ REMOVABLE INSULATION. INSTALL ACCESS DOOR IN PLENUM OR DUCT, WHICHEVER IS CLOSER TO DAMPER. 3/4" BULKHEAD FITTING W/ DRAIN VALVE, HOSE-END CONNECTION W/ CHAIN & CAP. REWORKED MULLION. REFER TO ARCH. MOTORIZED DAMPER INSULATED PLENUM FILTER BOX SCHEDULE MANUFACTURER FILTER TYPE DEPTH EFFICIENCY HOUSING DIMENSIONS HOUSING MATERIAL REMARK FB-1 UNIT ID MODEL V-BANK GLIDE/PACK CAMFIL FARR PLEATED 2"MERV 8 15.25"Hx48"Wx28"D 16 GA GALV. NOTES: 1.PROVIDE DUAL ACCESS DOORS, SOFT SEAL AND CAM-LATCH HANDLES. EXISTING HWS HEATING COILBALANCING VALVE, TYPICAL FLEXIBLE CONNECTION, TYPICAL UNION, TYPICAL. EXISTING HWR 2-WAY, NORMALLY OPEN, TEMPERATURE CONTROL VALVE. MANUAL AIR VENT THERMOMETER, TYPICAL BALL VALVE, TYPICAL M DRAIN VALVE W/ HOSE-END CONNECTION, CHAIN AND CAP. 1/2" TEPID WATER EXISTING MIXING VALVE FINISHED FLOOR 3'-0" MAXIMUM DRAIN OPEN TO FLOOR RELOCATED EYE/FACE WASH UNIT REMOVE AND RELOCATE EMERGENCY EYEWASH STATION. INSTALL NEW PIPING AS REQUIRED. 105 N. Tioga Street, Suite 200 Ithaca, NY 14850 607-319-4136 labellapc.com DRAWING NAME: It is a violation of New York Education Law Article 145 Sec.7209, for any person, unless acting under the direction of a licensed architect, professional engineer, or land surveyor, to alter an item in any way. If an item bearing the seal of an architect, engineer, or land surveyor is altered; the altering architect, engineer, or land surveyor shall affix to the item their seal and notation "altered by" followed by their signature and date of such alteration, and a specific description of the alteration. DRAWING NUMBER: DATE: ISSUED FOR: DRAWN BY: REVIEWED BY: PROJECT NUMBER:9/20/2019 9:00:56 AMC:\Users\mjeffery\Documents\Revit Local Files\2190823 Milstein Hall Mech_R19_mjeffery.rvtM501 MECHANICAL DETAILS AND SCHEDULES MMJ EJL 09/20/19 CONSTRUCTION 2190823 ITHACA, N.Y. 14853-3701 MILSTEIN HALL MECH UPGRADES CORNELL UNIVERSITY MILSTEIN HALL © 2019 LaBella Associates NOT TO SCALEM501 3 DUCT - TYPICAL DUCTWORK DETAILS REGISTER AND GRILLE SCHEDULE No. NECK SIZE FACE SIZE SERVICE MATERIAL DAMPER FINISH MOUNTING USE DESCRIPTION MANUFACTURER MODEL NOTES 1 12"x8" 14"x10" EXHAUST STEEL NONE WHITE SURFACE EXHAUST 1/2"x1/2" EGGCRATE TITUS 50F 2 30"x20" 32"x22" RETURN STEEL OBD WHITE SURFACE RETURN 35 DEG SINGLE DEFLECTION W/ 1/2" SPACING TITUS 355RL NOT TO SCALEM501 1 IN-LINE EXHAUST FAN DETAIL NOT TO SCALEM501 2 DUCT MOUNTED DIFFUSER DETAIL EXHAUST FAN SCHEDULE No. LOCATION SERVICE TYPE CFM ESP (in.) Electrical Data MANUFACTURER MODEL NOTESHP Volt/Hz/PH EF-1 B0046 GENERAL INLINE 1432 0.5" 1/3 208/60/1 GREENHECK BCF-208 1 ELECTRIC CABINET UNIT HEATER SCHEDULE No. LOCATION TYPE CFM CAP (MBH) V/Hz/Ph KW AMPS MOUNTING MANUFACTURER MODEL NOTES CUH-1 VESTIBULE CABINET UNIT HEATER 250 --- 208/60/3 5.0 14.0 WALL QMARK CU9350 LOUVER SCHEDULE No. LOCATION SERVICE CFM SIZE WIDTH FA (ft²) APD (in.) BIRD SCREEN MATERIAL FINISH MANUFACTURER MODEL NOTES L-1 B0046 EXHAUST 1432 18 54 2.88 0.5" 3/4" AL MILL GREENHECK ESD-435 1,2,3 NOT TO SCALEM501 4 WALL LOUVER W/ PLENUM DETAIL NOTES: 1.PROVIDE WITH INSULATED MOTORIZED DAMPER. 2.PROVIDE WITH 3/4" BIRDSCREEN. 3.PROVIDE FRAME WITH GLAZING ADAPTER. NOTES: 1.PROVIDE WITH NON-FUSED DISCONNECT SWITCH AND START/STOP RELAY. AIR HANDLING UNIT SCHEDULE (HOT WATER) No. SERVICE LOCATION MIN OA CFM SUPPLY FAN SUPPLY FAN MOTOR HEATING COIL - 180 DEG EWT MANUFACTURER MODEL NOTESCFM ESP (in.) TSP (in.) TYPE RPM BHP RPM HP VOLTS PHASE MCA MOCP EAT LAT LWT GPM ROWS APD (in.) PD (ft) AHU-5 SUPPLY (HEATING ONLY) B09 1288 1990 0.75 1.15 FORWARD CURVED 1242 0.8 1800 1.5 208 3 5.6 10 72.09 26 147 7.1 2 0.14 0.2 CARRIER 39MN NOT TO SCALEM501 5 2-WAY MODULATING VALVE HOT WATER HEATING COIL PIPING SUPPLY GRILLE SCHEDULE No. NECK SIZE (Dia.) FACE SIZE MATERIAL DAMPER MOUNTING FINISH USE DESCRIPTION MANUFACTURER MODEL NOTES A 12"x6" 14"x8" STEEL NONE SURFACE WHITE SUPPLY DOUBLE DEFLECTION, W/ 1 1/4" SPACING TITUS 112RL NOTES: 1.PROVIDE WITH VFD ON FAN MOTOR. 2.PROVIDE WITH 4" STEEL BASE RAIL. 3.PROVIDE FRAME WITH 2-STAGE FILTER. 2" PLEATED MERV 8 PRE-FILTER AND 4" MERV 13 FINAL FILTER. NOT TO SCALEM501 6 EMERGENCY EYEWASH STATION AND THERMOSTATIC MIXING VALVE DETAIL Revisions NO: DATE: DESCRIPTION: EF-1 EXHAUST FAN EF-1 SEQUENCE OF OPERATIONS THIS FAN SHALL OPERATED WITH AHU-5 TO PROVIDE EXHAUST AIRFLOW TO THE SHOP SPACE. ENABLE/DISABLE SIGNAL OF THE EXHAUST FAN SHALL BE INTERLOCKED WITH THE AIR HANDLING UNIT (AHU-5). UPON DETECTION OF OCCUPANCY IN THE SPACE (REFER TO AHU-5 SEQUENCE OF OPERATIONS), THE EXHAUST AIR MOTORIZED DAMPER AT LOUVER L-1 SHALL OPEN AND THE END SWITCH SHALL PROVIDE A SIGNAL BACK TO THE BUILDING MANAGEMENT SYSTEM. UPON A SIGNAL FROM THE END SWITCH, THE EXHAUST FAN SHALL ENGAGE TO FLOW A CONSTANT VOLUME OF EXHAUST AIR FROM THE SPACE. SUPPLY AIR TEMPERATURE SHALL NOT BE ALLOWED TO DROP BELOW 68 DEGREES (ADJUSTABLE) IN HEATING SEASON. IF OCCUPANCY IS NOT DETECTED IN THE SPACE FOR 30 MINUTES (ADJUSTABLE) AFTER BEING ENABLED, THE EXHAUST FAN (AND AIR HANDLING UNIT) SHALL DISENGAGE AND THE RESPECTIVE LOUVER DAMPERS SHALL CLOSE. SAFETIES / ALARMS: WHEN THE EXHAUST FAN IS ENGAGED TO OPERATE AND DOES NOT PROVE STATUS WITHIN 5 MINUTES, AN ALARM SHALL BE GENERATED AT THE BUILDING MANAGEMENT SYSTEM USER WORK STATION. 3 M ES 4 1SS MS 2CS DAMPER END SWITCH2-WAY DAMPER ACTUATOR NEW EX LOUVER L-1 2-WAY ISOLATION DAMPER EA H L5 FB-1 N.O. SUPPLY AIR SUPPLY FAN RETURN AIR HC GHWR GHWS AIR HANDLING UNIT AHU-5 SEQUENCE OF OPERATIONS OCCUPIED / UNOCCUPIED MODE: OCCUPIED / UNOCCUPIED MODE SHALL BE ESTABLISHED BASED ON INPUT FROM THE SPACE OCCUPANCY SENSOR. IN THE UNOCCUPIED MODE THE OUTSIDE AIR DAMPERS SHALL CLOSE, THE FANS SHALL STOP (AHU-5 AND EF-1), AND THE SPACE HEATING SET-POINT SHALL BE SET AT 60 °F (ADJUSTABLE). RADIATION HEAT SHALL MODULATE AS THE PRIMARY SOURCE OF HEAT TO MAINTAIN UNOCCUPIED HEATING SETPOINT TEMPERATURE. IF SPACE TEMPERATURE CONTINUES TO DROP, THE SUPPLY FAN (AHU-5) SHALL START AND RUN WITH THE OUTSIDE AIR DAMPER CLOSED. THE HOT WATER CONTROL VALVE SHALL MODULATE OPEN UNTIL SPACE TEMPERATURE IS SATISFIED. THE FAN SHALL THEN STOP. EXHAUST FAN EF-1 SHALL BE DISENGAGED DURING UNOCCUPIED MODE, WHEN THE OUTSIDE AIR DAMPER IS CLOSED. FAN CONTROL: THE SUPPLY FAN SHALL RUN CONTINUOUSLY DURING THE OCCUPIED MODE. THE SUPPLY FAN VSD SHALL BE ADJUSTED TO MAINTAIN CONSTANT PRESSURE DOWNSTREAM OF THE FILTERS TO MAINTAIN CONSTANT VOLUME AIR FLOW AS THE FILTER STATIC PRESSURE BUILDS UP. THE EXHAUST FAN EF-1 SHALL BE INTERLOCKED TO RUN WITH AHU-5 IN THE OCCUPIED MODE, ONLY WHEN THE OUTSIDE AIR DAMPER IS OPEN. EF-1 DOES NOT RUN IF AHU-5 SUPPLY AIR FAN IS NOT ENGAGED. THE SUPPLY AIR FAN SHALL ONLY ENGAGE UPON PROOF OF RETURN AIR OR OUTSIDE AIR OPEN END-SWITCH. HEATING CONTROL: THE EXISTING PERIMETER RADIATION HEAT SHALL ACT AS THE PRIMARY MODE OF HEAT WITH THE RADIATION CONTROL VALVE MODULATING AS NECESSARY TO MAINTAIN SPACE TEMPERATURE. IF SPACE TEMPERATURE CONTINUES TO DROP DURING UNOCCUPIED MODE, THE SUPPLY FAN (AHU-5) SHALL ENGAGE AND RUN WITH THE OUTSIDE AIR DAMPER CLOSED. AHU-5 HOT WATER COIL CONTROL VALVE SHALL MODULATE OPEN UNTIL SPACE TEMPERATURE IS SATISFIED. THE FAN SHALL DISENGAGE UPON SATISFYING THE SPACE TEMPERATURE SETPOINT. DURING OCCUPIED MODE, THE PERIMETER RADIATION HEAT SHALL ACT AS THE PRIMARY MODE OF HEAT WITH THE FANS (AHU-5 AND EF-1) IN OPERATION AND THE OUTSIDE AIR DAMPER OPEN. IF THE SPACE TEMPERATURE CONTINUES TO DROP WITH THE RADIATION VALVE FULL OPEN, AHU-5 HOT WATER COIL CONTROL VALVE SHALL MODULATE OPEN AS NECESSARY TO SATISFY THE SPACE TEMPERATURE SETPOINT ALONG WITH THE RADIATION HEAT. FILTER MONITORING: THE BMS SHALL MONITOR THE FILTER DIFFERENTIAL PRESSURE AND GENERATE AN ALARM WHEN PRESSURE DROP EXCEEDS THE DIRTY RATING OF THE FILTER. THIS PROCESS SHALL BE MAINTAINED FOR BOTH PRE-FILTER AND FINAL FILTER. TRENDING AND ALARMS: THE BUILDING MANAGEMENT SYSTEM SHALL TREND THE HOT WATER COIL CONTROL VALVE POSITION, AHU-5 SUPPLY FAN STATUS AND VFD SETPOINT, SPACE TEMPERATURE SETPOINT AND PRE-FILTER PRESSURE DIFFERENTIAL. THE AHU-5 SUPPLY AIR FAN SHALL SHUT DOWN AND AN ALARM SHALL BE GENERATED AT THE BMS USER WORK STATION IF THE SPACE TEMPERATURE IS BELOW THE HEATING SETPOINT TEMPERATURE BY 5 DEGREES FOR LONGER THAN 5 MINUTES (ADJUSTABLE). IF THE SUPPLY AIR DISCHARGE TEMPERATURE DROPS BELOW 50 DEGREES (ADJUSTABLE), OR THE FREEZE STAT ACTIVATES, THE UNIT SHALL BE COMMANDED INTO THE UNOCCUPIED MODE AND AN ALARM SHALL BE GENERATED AT THE BMS USER WORKSTATION. WHEN ANY SENSED OUTPUT DIFFERS FROM ITS COMMANDED STATE, AN ALARM SHALL BE GENERATED BY THE BMS SYSTEM.2M8ALARM T 7 T 4 3 M 5 M EXISTING WALL LOUVER T 12 10S/S 11STATUS 9SPEED 1 M N.C.OUTSIDE AIR T 13 EXISTING FTR EXISTING CONTROL VALVE VFD ES 6 HL14 HL15 OCC 16 105 N. Tioga Street, Suite 200 Ithaca, NY 14850 607-319-4136 labellapc.com DRAWING NAME: It is a violation of New York Education Law Article 145 Sec.7209, for any person, unless acting under the direction of a licensed architect, professional engineer, or land surveyor, to alter an item in any way. If an item bearing the seal of an architect, engineer, or land surveyor is altered; the altering architect, engineer, or land surveyor shall affix to the item their seal and notation "altered by" followed by their signature and date of such alteration, and a specific description of the alteration. DRAWING NUMBER: DATE: ISSUED FOR: DRAWN BY: REVIEWED BY: PROJECT NUMBER:9/20/2019 9:01:00 AMC:\Users\mjeffery\Documents\Revit Local Files\2190823 Milstein Hall Mech_R19_mjeffery.rvtM701 MECHANICAL CONTROLS MMJ EJL 09/20/19 CONSTRUCTION 2190823 ITHACA, N.Y. 14853-3701 MILSTEIN HALL MECH UPGRADES CORNELL UNIVERSITY MILSTEIN HALL © 2019 LaBella Associates NOT TO SCALEM701 1 EF-1 CONTROLS DETAIL NOT TO SCALEM701 2 AHU-5 CONTROLS DETAIL 1) REFER TO PLANS FOR ROOM TEMPERATURE SENSOR LOCATIONS NOTES: DV = DIGITAL VALUE AI = ANALOG INPUT, AO = ANALOG OUTPUT, DI = DIGITAL INPUT, DO = DIGITAL OUTPUT, AV =... ABBREVIATION KEY: MILSTEIN HALL - CONTROLS POINTS LIST - AHU-5 POINT # POINT DESCRIPTION HARWARE POINTS SOFTWARE POINTS NOTESAIAODIDOAVDVSCHEDALARMTREND 1 FIN TUBE CONTROL VALVE (EXISTING) X X 2 RETURN AIR DAMPER X 3 HEATING COIL VALVE X X 4 SPACE TEMPERATURE X X 5 OSA DAMPER X 6 DAMPER END SWITCH X 7 SUPPLY AIR TEMPERATURE X X 8 SUPPLY FAN ALARM X X 9 SUPPLY FAN SPEED X X 10 SUPPLY FAN START/STOP X 11 SUPPLY FAN STATUS X 12 LOW LIMIT THERMOSTAT X X 13 MIXED AIR TEMPERATURE X 14 PRE-FILTER DIFFERENTIAL PRESSURE X X X 15 POST-FILTER DIFFERENTIAL PRESSURE X X X 16 SPACE OCCUPANCY SENSOR X 1) REFER TO PLANS FOR ROOM TEMPERATURE SENSOR LOCATIONS NOTES: DV = DIGITAL VALUE AI = ANALOG INPUT, AO = ANALOG OUTPUT, DI = DIGITAL INPUT, DO = DIGITAL OUTPUT, AV = ANALOG VALUE ABBREVIATION KEY: MILSTEIN HALL - CONTROLS POINTS LIST - EF-1 POINT # POINT DESCRIPTION HARWARE POINTS SOFTWARE POINTS NOTESAIAODIDOAVDVSCHEDALARMTREND 1 FAN S/S X X 2 FAN RUN STATUS X X FAILURE - VIA MOTOR CONTACT 3 MOTORIZED DAMPER X 4 DAMPER END SWITCH X 5 FILTER BOX DIFFERENTIAL PRESSURE X Revisions NO: DATE: DESCRIPTION: B0046 1032 UP G G G GGG G B0046 1032 UP G G G GGG G REMOVE SPRINKLER PIPING AND SPRINKLER HEADS. REMOVE SPRINKLER PIPING AND SPRINKLER HEADS. CAP SPRINKLER PIPING. CAP SPRINKLER PIPING. 105 N. Tioga Street, Suite 200 Ithaca, NY 14850 607-319-4136 labellapc.com DRAWING NAME: It is a violation of New York Education Law Article 145 Sec.7209, for any person, unless acting under the direction of a licensed architect, professional engineer, or land surveyor, to alter an item in any way. If an item bearing the seal of an architect, engineer, or land surveyor is altered; the altering architect, engineer, or land surveyor shall affix to the item their seal and notation "altered by" followed by their signature and date of such alteration, and a specific description of the alteration. DRAWING NUMBER: DATE: ISSUED FOR: DRAWN BY: REVIEWED BY: PROJECT NUMBER:9/20/2019 9:01:05 AMC:\Users\mjeffery\Documents\Revit Local Files\2190823 Milstein Hall Mech_R19_mjeffery.rvtF101 BASEMENT FIRE PROTECTION PLANS MMJ EJL 09/20/19 CONSTRUCTION 2190823 ITHACA, N.Y. 14853-3701 MILSTEIN HALL MECH UPGRADES CORNELL UNIVERSITY MILSTEIN HALL © 2019 LaBella Associates 1/4" = 1'-0"F101 1 BASEMENT FIRE PROTECTION REMOVAL PLAN 1/4" = 1'-0"F101 2 BASEMENT FIRE PROTECTION PLAN Revisions NO: DATE: DESCRIPTION: G G G G G G G GGG GG GG G GG GG G GCAM CAMCAMJ 15 15 15 F F 15 B0044 B09 B0046 267 2762 1032 UP UP J J J DR DR CAMCAMCAMJJJ J 15 15 15 15 F F 15 B0044 B09 B0046 267 2762 1032 UP UP B0044 B09 B0046 267 2762 1032 UP UP CUH-1 EF-1 5,7 APL-BB-SEC 2 9,11,13 APL-BB-SEC 2 AHU-5 EXISTING SWITCHING AND LIGHTING CIRCUIT A A A A EXISTING 105 N. Tioga Street, Suite 200 Ithaca, NY 14850 607-319-4136 labellapc.com DRAWING NAME: It is a violation of New York Education Law Article 145 Sec.7209, for any person, unless acting under the direction of a licensed architect, professional engineer, or land surveyor, to alter an item in any way. If an item bearing the seal of an architect, engineer, or land surveyor is altered; the altering architect, engineer, or land surveyor shall affix to the item their seal and notation "altered by" followed by their signature and date of such alteration, and a specific description of the alteration. DRAWING NUMBER: DATE: ISSUED FOR: DRAWN BY: REVIEWED BY: PROJECT NUMBER:9/19/2019 9:44:55 AME101 PARTIAL BASEMENT ELECTRICAL REMOVAL AND POWER PLAN MPS RDH 09/20/19 CONSTRUCTION 2190823 ITHACA, N.Y. 14853-3701 MILSTEIN HALL MECH UPGRADES CORNELL UNIVERSITY MILSTEIN HALL © 2019 LaBella Associates 3/16" = 1'-0"E101 1 BASEMENT ELECTRICAL PLAN 3/16" = 1'-0"E101 2 BASEMENT ELECTRICAL REMOVAL PLAN EQUIPMENT CONNECTION SCHEDULE DESIGNATION LOCATION DESCRIPTION LOAD VOLTAGE PHASE POWER SOURCE CIRCUIT NUMBER PROTECTIVE DEVICE RATING (A) NUMBER OF POLES CONDUCTORS & CONDUIT CONTROLLER TYPE CONTROLLER SIZE CONTROLLER ACCESSORIES DISCONNECT NOTES AHU-5 B09 AIR HANDLING UNIT 5.6A 208 V 3 10 3 EXISTING N/A N/A N/A N/A CUH-1 B09 CABINET UNIT HEATER 5KW 208 V 3 APL-BB-SEC 2 9,11,13 20 3 3 #12, 1 #12 G IN 3/4" C. THERMOSTAT N/A N/A N/A EF-1 VESTIBULE EXHAUST FAN 3.2A 208 V 1 APL-BB-SEC 2 5,7 15 2 3 #12, 1 #12 G IN 3/4" C. N/A N/A N/A 30A 1/3 HP LIGHT FIXTURE SCHEDULE TYPE LAMP MOUNTING DESCRIPTION MANUFACTURER MODEL # COMMENTS A LED SURFACE 4' INDUSTRIAL STRIP LUMAX CNLED35L4K48-9FAF GENERAL NOTES: A. NEW CIRCUITS TO APL-BB SEC 2 TO BE ROUTED TO EXISTING SPARE CONDUITS IN BACK CORNER THEN TO ELECTRICAL ROOM. KEYED NOTES: REMOVE EXISTING EXIT SIGNAGE AND WIRING BACK TO SOURCE. REMOVE EXISTING FIRE ALARM NOTIFICATION DEVICE AND WIRING BACK TO SOURCE. REMOVE EXISTING RECEPTACLE AND WIRING BACK TO SOURCE. RELOCATE EXISTING WALL MOUNTED JUNCTION BOX TO CEILING. SAVE WIRING TO EXTEND TO NEW LOCATION. REWORK EXISTING SWITCHING FOR LIGHTS TO CONNECT TO ADJACENT CORRIDOR CONTROLS. DISCONNECT EXISTING AIR HANDLING UNIT. SAVE CIRCUIT TO EXTEND AND RE- CONNECT TO REPLACEMENT UNIT. 1 2 3 4 5 1 2 4 4 4 3 3 3 5 EXISTING EXISTING 6 6 Revisions NO: DATE: DESCRIPTION: