Statler Hall CCB Dean's Suite Renovation
Page 1 CORNELL UNIVERSITY STATLER HALL CCB FACILITIES CONTRACTS DEAN’S SUITE RENOVATIONS 121 HUMPHREYS SERVICE BUILDING ITHACA, NEW YORK 14853-3701 ADDENDUM NO. 1 AUGUST 4, 2016 This Addendum contains changes to the requirements of the Contract Documents and Specifications. Such changes are to be incorporated into the Construction Documents and shall apply to the work with the same meaning and force as if they had been included in the original document. Wherever this Addendum modifies a portion of a paragraph of the specifications or a portion of any Drawing, the remainder of the Paragraph or Drawing shall remain in force. NOTE: Provisions of all Contract Documents apply. Item 1. Section 09 26 00 ADD the following paragraph: 2.4 SOUND ATTENUATION BLANKETS 1. Mineral Fiber Batt Insulation: Flexible or semi-rigid preformed batt or blanket, complying with ASTM C665 Type 1; unfaced flame spread index of 0 (zero) when tested in accordance with ASTM E84. a. Size: 16 inches b. Thickness: 3 ½ inches c. Friction fit 2. Manufacturers: a. Thermafiber, Inc.; SAFB: www.thermafiber.com b. Johns Manville; MinWool Sound Attenuation Fire Batts: www.jm.com c. ROXUL, Inc; ComfortBatt: www.roxul.com Item 2. Drawing A-101 Refer to GENERAL NOTES ADD “5. All furniture and systems furnishings will be removed by Owner prior to start of Work.” Item 3. Drawing A-101 Refer to 1/A-101 FIRST FLOOR PLAN DELETE reference to existing furniture to remain in Waiting 176 and A. D. Office 174A. The Owner will remove and store the furniture for the duration of construction and will reinstall once the Work is completed. CORNELL UNIVERSITY STATLER HALL CCB FACILITIES CONTRACTS DEAN’S SUITE RENOVATIONS Page 2 Item 4. Drawing A-101 Refer to 2/A-101 DEMOLITION PLAN Partition between Office 174F and Office 174G shall be demolished in its entirety. Item 5. Drawing A-101 Refer to 5/A-101 – PARTITION TYPES ADD the following note to Partition Type 1: “Provide 3 ½” mineral wool batts equal to THERMAFIBER Sound Attenuation Fire Blankets (SAFB). Seal top and bottom of partition to existing structure with acoustic sealant.” Item 6. Drawing A-103 Refer to 2/A-103 – DOOR JAMB – HM @ METAL STUD MODIFY Jamb Type J1 as indicated below: Item 7. Drawing A-102 REPLACE Drawing A-102 with attached drawing A-102, including Revision 1, dated August 4, 2016. Item 8. Drawing A-104 REPLACE Drawing A-104 with attached drawing A-104, including Revision 1, dated August 4, 2016. Item 9. RFI Questions and Clarifications See attached RFI Log (Items 1 – 7) CORNELL UNIVERSITY STATLER HALL CCB FACILITIES CONTRACTS DEAN’S SUITE RENOVATIONS Page 3 Attachments: Revised Full Size Drawings, A-102 and A-104 RFI Log (Items 1 – 7) ****END OF ADDENDUM**** STATLER HALL CCB DEAN'S SUITE RENOVATIONS Date: August 4, 2016 RFI Form RFI/Page/ Response Dwg./Spec./Rep.Section/Design Team Index Number Paragraph/Topic RFI Response 1 Drawing A-101 Sound Attenuation Blankets Drawing A-101 Detail 5 Partition Types does not call out insulation or sound attenuation blankets but Drawing A-103 Detail 6 does for the soffit above the ceiling. Is this correct that the Dean’s Offices and meeting room walls do not get sound attenuation? Partitions are required to be filled with sound attenuation blankets. Refer to Addendum 1, Item 1, Item 5, and Item 6. 2 Pre-Bid Meeting Existing furniture Furniture will be removed by Owner prior to start of work. Refer to Addendum 1, Item 2 3 Pre-Bid Meeting Details for casework Intent is to keep existing as much as possible and to provide new work to match existing. 4 Pre-Bid Meeting Temporary barrier in corridor for work associated with wall panel installation. Cones and warning signs will be sufficient protection and separation of occupants from contractor's work. 5 Pre-Bid Meeting Staging area Staging will take place within the work area. Space for a dumpster will also be availabe. Location to be determined. 6 Pre-Bid Meeting Loading dock on east side of building can be used Loading dock on east side of building can be used but contractor is advised to limit or avoid 6:00AM - 9:30 AM, Mon, Tues, and Thurs when hotel operations are busiest. Contractor must stay with delivery truck at all times while docking. 7 Pre-Bid Meeting Parking One parking place will be reserved in the Statler lot for the contractor's superintendent. All others will need to find parking on campus in areas designated for use by visitors. 1 A-102 2 A-102 3'-0"1'-8"2'-6"3'-0"1'-8"1'-3"1'-3"COPIER BY OWNER 18" DEEP MICROWAVE CABINET 3'-0"3'-0"2'-11" VIF 3'-0". VIF 3'-0".EXISTING7'-2"OPEN TO WAITING AREA BEYOND OPEN TO RECEIVE UNDERCOUNTER REFRIGERATOR (NIC) - PROVIDE PAINT AND WALL BASE AT ALL SIDES OF OPENING REPLACE EX. WOOD PANELS WITH REGLETS TO MATCH EXISTING AT AREAS WHERE DAMAGED FOLLOWING COUNTERTOP REMOVALS 2'-0"RELOCATE SALVAGED UPPER CABINETS SOLID SURFACE COUNTERTOPS (TYP THIS ELEVATION) MATCH HEIGHT OF EXISTING REGLET (TYP) ± 1'-11"1'-0"3'-0" PROVIDE ADJUSTABLE SHELF (TYP WHERE INDICATED IN ELEVATIONS) 262728 EXISTING STOREFRONT HARDWOOD VENEER PLYWOOD WALL PANEL SYSTEM; MATCH EXISTING IN WAITING 176 10'-0"7'-2"1'-0"1'-0"EXISTING RUBBER BASE 8 A-102 8 A-102 SIM 3/8" x 3/8" ALUM REGLET (TYP)3'-0"1'-8"SOLID SURFACE COUNTERTOP OVER 3/4" MDF MICROWAVE SHELF W/ FINISH SIDES AND BACK TO MATCH CASEWORK 1'-6" 1'-0" EXISTING 2'-6" EXISTING GWB AND METAL STUD FRAMING EXIST HDWD VENEER PANEL SYSTEM OVER GWB EXISTING GWB & METAL STUD FRAMING EXISTING REGLET & HDWD NOSING SOLID SURFACE OVER 3/4" PLYWOOD COUNTERTOP2'-6"1'-8"3'-0"ADJUSTABLE SHELF ADJUSTABLE SHELF 5/8" GWB 2'-6" HWD NOSING ALUM REGLET 2 1/2" METAL STUD FRAMING EXISTING HDWD VENEER PANEL OVER GWB REMOVE BACK PANEL OF EXISTING CABINET AND INSTALL 5/8" GWB 9 A-102 HDWD PANEL SYSTEM EACH SIDE 1K 3'-0"1'-10"3'-0"FILLER PANEL (TYP BOTH SIDES) SOLID SURFACE (C1) COUNTERTOP WITH 1/4 ROUND TOP WOOD BASE (B1) ADJUSTABLE SHELF (TYP) 2'-0"4'-0" 4'-0"2'-0" J H G CENTERLINE 5'-6"3'-0"- --- OPEN SHELVING BEYOND 2'-6"4'-0"HARDWOOD VENEER PLYWOOD WALL PANEL SYSTEM AT DISPLAY WALL WITH REGLET REVEALS RETURN PLYWOOD VENEER SYSTEM TO WALL AT DISPLAY WALL BASE (TYP BOTH SIDES) PROVIDE REGLET AT CORNERS SOLID SURFACE COUNTER/CAP AT WALL PROJECTION - PROVIDE 1" OVERHANG AT WALL EDGE 2'-6"6'-2" PT-4PT-4 PT-3 PROVIDE 1" X 2" SOLID HARDWOOD CAP AT CEILING (FINISH TO MATCH CASEWORK) RESIN PANEL SYSTEM (R-1) SHELF BRACKETS AT MID-SPAN SOLID SURFACE COUNTERTOP SOLID SURFACE COUNTERTOP 1'-6"5'-8"1'-6" ONE ADJUSTABLE SHELF (TYP) FILLER PANEL GLAZED SCREEN WITH TRANSLUCENT FILM 7 A-102 2 A-104 5"2'-6"WOOD BASE WOOD PANELING SS-1 SOLID HWD CAP G CONTRACTOR'S OPTION: HOOK AND LOOP OR PANEL CLIP FASTENING SYSTEM 3/4" HWD VENEER PANEL EXISTING GWB AND STUD WALL ALUM REGLET 3/8"3/8" WOOD BLOCKING 3/8"3/8" HDWD TRIM 3/4" HDWD VENEER PLYWOOD HDWD NOSING 5/8" GWB EXISTING METAL STUD FRAMING EX. HDWD PANEL SYSTEM Beardsley Design Associates Architecture, Engineering, Landscape Architecture, D.P.C. ©Filename:no. revision description by date Project Number: Drawn By: Designed By: Reviewed By: WARNING Any alterations to this document not conforming to section 7307. New York State Education Law are strictly prohibited. 320 West Main Street Malone, NY 12953 518.483.1585 5789 Widewaters Pkwy Dewitt, NY 13214 315.472.6980 64 South Street Auburn, NY 13021 315.253.7301 AUBURN MALONE SYRACUSE 8/4/2016 8:04:10 AMC:\Projects\AG_16063_V2016_ll.rvtARCHITECTURAL CORNELL UNIVERSITYITHACA, NEW YORKA-102 July, 20 2016 INTERIOR ELEVATIONS, DETAILS, AND FINISH SCHEDULE Renovations for the CCB Dean's Suite at Statler Hall130 Statler Drive, Ithaca, New York 14853Submission DVJ/NRH 16063 LL DVJ 2016 SCALE: 1/4" = 1'-0" 3 ELEVATION AT BUILT-IN CASEWORK SCALE: 1/4" = 1'-0" 4 CORRIDOR ELEVATION SCALE: 1 1/2" = 1'-0" 1 Section 1 SCALE: 1 1/2" = 1'-0" 2 Section 2 INTERIOR FINISH LEGEND MARK MATERIAL MANUFACTURER SERIES / COLOR COMMENTS BASE B-1 WOOD -- MAPLE TO MATCH EXISTING. TYP 4" HIGH. VIF. B-2 RUBBER JOHNSONITE SILVER GREY WG 55 TYP 4" FLOORING F-1 CARPET - BROADLOOM SHAW CONTRACT SWITCH 5A205 - GAZE 03530 WALL COVERINGS R-1 RESIN LUMICOR SILVER TWILIGHT - LUMICLEAR FRONT AND BACK GLOSS FINISH WALL / PAINT FINISH PT-1 PAINT BENJAMIN MOORE SEASHELL OC-120 AT ALL EXISTING GWB SOFFITS AND WINDOW HEADS PT-2 PAINT BENJAMIN MOORE OZARK SHADOW - AC-26 AT ALL FAN COILS & HM FRAMES PT-3 PAINT BENJAMIN MOORE CHANTILLY LACE - OC-65 PT-4 PAINT BENJAMIN MOORE CORNELL'S RED PT-5 PAINT BENJAMIN MOORE GRAY OWL - OC-52 CASEWORK CW-1 WOOD -- SPECIES MAPLE TO MATCH EXISTING COUNTER C-1 SOILD SURFACE FORMICA LUNA CONCRETE 781 CEILING ACT-1 ACOUSTICAL CEILING TILE ARMSTRONG ULTIMA 1912 ROOM FINISH SCHEDULE ROOM FLOOR FINISH BASE FINISH WALL FINISH CASEWORK FINISH WINDOW TREATMENT COMMENTSROOM NO. ROOM NAME 174 OPEN OFFICE F-1 B-1, B-2 PT-3, PT-1 MAPLE OWNER 174A A.D. OFF. F-1 B-2 PT-5 MAPLE OWNER 174B MEETING RM. F-1 B-2 PT-3, PT-4 MAPLE OWNER 174C DEAN'S OFF. F-1 B-2 PT-5, PT-4 MAPLE OWNER 174D DEAN'S OFF. F-1 B-2 PT-5, PT-4 MAPLE OWNER 176 WAITING F-1 B-2 PT-3 MAPLE N/A SCALE: 1/4" = 1'-0" 5 CASEWORK AT MEETING RM. SCALE: 1/4" = 1'-0" 6 ELEVATION AT MEETING RM./ OPEN OFFICE 1 ADDENDUM 1 08.04.16 SCALE: 3/4" = 1'-0" 7 WOOD PANELING AT MEETING ROOM SCALE: 3" = 1'-0" 8 WOOD PANEL DETAIL SCALE: 1 1/2" = 1'-0" 9 PLAN DETAIL AT CASEWORK 1 1 1 1 H G 26 A-102 3 1 A-102 2 A-102 A-1024 1 A-104 16'-10 1/2" R 9'-0" - --- OPEN SHELVING THIS SIDE OPEN SHELVING THIS SIDE; PROVIDE SUPPORT AT MID-SPAN2'-1"7'-10 1/2"CLEAR3'-0"DESKTOP SUPPORT AT MID-SPAN (TYP OF TWO) 2 HOUR SHAFT WALL AT CHASE - TIE TO EXISTING WALL PROVIDE FINISHED 1" X 2" HARDWOOD CAP TRIM AT TOP OF WALL WHERE WALL MEETS CEILING SYSTEM A-104 3 RESIN PANELS 7'-6"FIELD VERIFY CONDITION OF SHAFT PATCH TO MAINTAIN CONTINUITY OF SHAFT ALL AROUND 2 A-104 10 1/4"ALCOVE BELOW 3'-6 1/2" A-104 4 First Floor 100'-0"4'-0"1"6"2" SOLID SURFACE OVER 3/4" PLYWOOD 1 1/2"3/4"3'-6"1/4" THICK TRANSLUCENT RESIN PANEL SYSTEM 5/8" GWB OVER 1/2" PLYWOOD EACH SIDE WOOD BASE 3 5/8" METAL STUDS AT 1-4" OC EXISTING WOOD SUBFLOOR EXISTING CONCRETE FLOOR 1" SS STAND-OFF FASTENERS. BARREL LENGTH 1" SS STAND-OFF FASTENERS 1 A-104 1"3'-0"1/2"3'-6"4'-0"1/2" LUMICOR RESIN PANELS. TYPICAL DIMENSIONS INDICATED VIF. SS-1 WOOD BASE First Floor 100'-0" 26 2'-6"1/2" SOLID SURFACE OVER 3/4" PLYWOOD 3/4" HARDWOOD PLYWOOD VERTICAL SUPPORT AT MID-SPAN; PROVIDE HDWD NOSING AT EXPOSED EDGE 12 GA. STEEL PLATE DESK SUPPORT BRACKET W/ POWDERCOAT FINISH; ALIGN W/ EXISTING STUDS 5/8" GWB 3 5/8" METAL STUDS AT 1'-4" OC PROVIDE ALCOVE FOR OWNER-INSTALLED 42W x 18D x 42H STORAGE CABINET 1"1'-6 1/2"5/8"3 5/8" 3/4" 5 1/2"2'-1" WOOD BASE BETWEEN BASE CABINETS EXISTING WALL BEYOND EXISTING WALL ADD BLOCKING AS NECESSARY TO SUPPORT COUNTER 4'-0"1'-3"1'-9" PROVIDE THREE GROMMETS; ALIGN WITH POWER/DATA LOCATIONS BELOW 3'-6 5/8"5 3/8"WOOD BASE EACH SIDE OF ALCOVE RUBBER BASE WITHIN ALCOVE NOTE: COORDINATE FINAL ALCOVE DIMENSIONS WITH OWNER-INSTALLED STORAGE CABINET 1"5 A-104 8" X 4" X 1/4" BASE PLATE ANCHORED TO CONCRETE BELOW FINISHED FLOOR SS STAND-OFF FASTERNERS 1/4" THICK TRANSLUCENT RESIN PANEL SYSTEM 3 5/8" METAL STUD FRAMING HSS 3 1/2 X 3 1/2 X 3/16 First Floor 100'-0" EXIST. CONCRETE REMOVE EXISTING RAISED WOOD FLOOR AS NECESSARY TO INSTALL STEEL TUBE; PATCH TO MATCH EXISTING AND BLEND SMOOTHLY WITH ADJACENT SURFACES (2) 1/2" DIA ANCHOR BOLTS ALIGN W/ CENTER LINE OF HSS 8" X 4" X 1/4" STEEL BASE PLATE CONT. FILLET WELD TO HSS HSS 3 1/2 X 3 1/2 X 3/16 4"4" Beardsley Design Associates Architecture, Engineering, Landscape Architecture, D.P.C. ©Filename:no. revision description by date Project Number: Drawn By: Designed By: Reviewed By: WARNING Any alterations to this document not conforming to section 7307. New York State Education Law are strictly prohibited. 320 West Main Street Malone, NY 12953 518.483.1585 5789 Widewaters Pkwy Dewitt, NY 13214 315.472.6980 64 South Street Auburn, NY 13021 315.253.7301 AUBURN MALONE SYRACUSE 8/4/2016 8:04:11 AMC:\Projects\AG_16063_V2016_ll.rvtARCHITECTURAL CORNELL UNIVERSITYITHACA, NEW YORKA-104 July, 20 2016 BUILT IN DESK AND WALL DETAILS Renovations for the CCB Dean's Suite at Statler Hall130 Statler Drive, Ithaca, New York 14853Submission DVJ/NRH 16063 LL DVJ 2016 SCALE: 1/4" = 1'-0" A FIRST FLOOR PLAN PARTIAL SCALE: 1 1/2" = 1'-0" 1 HALF WALL DETAIL 1 ADDENDUM 1 08.04.16 SCALE: 1/2" = 1'-0" 3 RESIN PANEL ELEVATION INSTALL FASTENERS PER MANUFACTURER'S INSTRUCTIONS 4 PER PANEL (TYP) SCALE: 1 1/2" = 1'-0" 2 DESKTOP & COUNTER DETAIL - REVISED SCALE: 1 1/2" = 1'-0" 4 PLAN DETAIL AT STRUCTURAL TUBE SCALE: 1 1/2" = 1'-0" 5 SECTION AT STRUCTURAL TUBE 1 1 1 1 STATLER HALL CCB DEAN’S SUITE RENOVATIONS Project Manual & Specifications July 20, 2016 Owner Cornell University Ithaca, NY 14853 Architect Beardsley Architects + Engineers 64 South Street Auburn, NY 13021 Renovations for the CODE-REQUIRED 01 45 33-6 CCB Dean’s at Statler Hall SPECIAL INSPECTIONS AND PROCEDURES July 20, 2016 SPECIAL INSPECTION NON-CONFORMANCE REPORT NO. DATE: ___________________________ TO: CC: Contractor: FROM: ___________________________, Special Inspector PROJECT: PART I: REFERENCE SPECIAL INSPECTION REPORT NO. (Attach copy of report) DESCRIPTION OF NON-CONFORMANCE: RDP RESPONSE: (PROVIDE ATTACHMENTS IF NECESSARY) RDP SIGNATURE ____________________________________ DATE__________________ IS RE-INSPECTION BY SPECIAL INSPECTOR REQUIRED □ YES □ NO PART II: CONTRACTOR VERIFICATION (To be completed by either the [General Contractor or Construction Manager] or Subcontractor and returned to the Special Inspector and the RDP.) I verify that as of the date listed, the non-conforming item noted above has been corrected as required. Date Completed By (Contractor’s Site Representative) Renovations for the CODE-REQUIRED 01 45 33-7 CCB Dean’s at Statler Hall SPECIAL INSPECTIONS AND PROCEDURES July 20, 2016 AGENT’S FINAL REPORT OF SPECIAL INSPECTIONS Project Name: Special Inspector: Location: Agent: Special Inspector’s Project: Agent’s Project: To the best of my information, knowledge, and belief, the Special Inspections or testing required for this project and designated for this Agent in the Statement of Special Inspections (which includes the Schedule of Special Inspections) submitted for permit have been performed and discovered discrepancies have been reported and resolved other than the following: Comments: [Attach continuation sheets if required to complete description of uncorrected discrepancies.] Respectfully submitted, Agent of the Special Inspector ______________________________________________ (Type or print name) ______________________________________________ Signature Date ______________________________________________ Address ______________________________________________ City, State, Zip Design Professional Seal or Certification Renovations for the CODE-REQUIRED 01 45 33-8 CCB Dean’s at Statler Hall SPECIAL INSPECTIONS AND PROCEDURES July 20, 2016 FINAL REPORT OF SPECIAL INSPECTIONS AND STRUCTURAL OBSERVATIONS Project Name: Registered Design Professionals Location: Architecture: Name Address Owner: CORNELL UNIVERSITY Owner’s Address: Structural Engineering: Name Address Special Inspector: Name Address To the best of my information, knowledge, and belief, the Special Inspections required for this project and itemized in the Statement of Special Inspections (which includes the Schedule of Special Inspections) submitted for permit have been performed and discovered discrepancies have been reported and resolved other than the following: Comments: [Attach continuation sheets if required to complete description of uncorrected discrepancies.] Interim reports submitted prior to this final report form a basis for and are to be considered an integral part of this final report. Agent’s Final Reports of Special Inspections are attached and are also a part of this Final Report. Respectfully submitted, Special Inspector ______________________________________________ (Type or print name) ______________________________________________ Signature Date ***END OF SECTION 01 45 33*** Professional Seal CHAPTER 1: GENERAL REQUIREMENTS THE PROVISIONS OF THE 2010 EXISTING BUILDING CODE OF NEW YORK STATE SHALL APPLY TO THIS PROJECT OCCUPANCY CLASSIFICATION GROUP B - BUSINESS CHAPTER 3: PRESCRIPTIVE COMPLIANCE METHOD ALTERATIONS AND REPAIRS ARE NONSTRUCTURAL, MADE OF THE SAME MATERIALS OF WHICH THE BUILDING IS CONSTRUCTED; THEY DO NOT ADVERSELY AFFECT ANY STRUCTURAL MEMBER OR FIRE-RESISTIVE RATING OF ANY PART OF THE BUILDING ENERGY CONSERVATION MEASURES IN EXISTING BUILDINGS SHALL IN CONFORMANCE WITH SECTION 101 OF THE ENERGY CONSERVATION CONSTRUCTION CODE OF NEW YORK STATE. ALTERATIONS AND REPAIRS TO ELECTRICAL, MECHANICAL, AND PLUMBING SYSTEMS CONFORM TO APPLICABLE REQUIREMENTS OF THE CODE WITHOUT REQUIRING THE EXISTING INSTALLATIONS TO COMPLY WITH ALL OF THE REQUIREMENTS OF THIS STANDARD. ALTERATIONS OR REPAIRS SHALL NOT CAUSE THE EXISTING INSTALLATION TO BECOME UNSAFE, HAZARDOUS OR OVERLOADED. THE AREA OF ALTERATION WORK COMPLIES WITH CHAPTER 11 OF THE BUILDING CODE OF NEW YORK STATE AND ICC/ANSI A117.1 CHAPTER 4: CLASSIFICATION OF WORK: ALTERATION - LEVEL 2 THE WORK INCLUDES THE RECONFIGURATION OF SPACE, THE ADDITION AND ELIMINATION OF DOORS, AND THE RECONFIGURATION OR EXTENSION OF SYSTEMS. CHAPTER 7 – ALTERATIONS LEVEL 2. ALL NEWLY INSTALLED INTERIOR FINISHES COMPLY WITH THE FLAME SPREAD REQUIREMENTS OF THE BUILDING CODE OF NEW YORK STATE: CLASS C: FLAME SPREAD 76-200; SMOKE DEVELOPED 0-450 NEW CARPETING COMPLIES WITH THE RADIANT FLUX REQUIREMENTS OF THE BUILDING CODE OF NEW YORK STATE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES COMPLY WITH THE REQUIREMENTS OF THE BUILDING CODE OF NEW YORK STATE. THE EXISTING AUTOMATIC SPRINKLER SYSTEM IS MODIFIED TO ACCOMMODATE THE RECONFIGURATION OF SPACE AND IS INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE BUILDING CODE OF NEW YORK STATE. THE EXISTING AUTOMATIC FIRE DETECTION SYSTEM IS MODIFIED TO ACCOMMODATE THE RECONFIGURATION OF SPACE AND IS INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THE CODE AND NFPA 72. THE EXISTING MEANS OF EGRESS IS NOT IMPACTED OR ALTERED AND IS IN COMPLIANCE WITH APPLICABLE PROVISIONS OF THE CODE. CODE REVIEW 1. 2. 3. 4.beardsley project number:Set no:Owner Architect Beardsley Architects + Engineers Filename:64 South Street Auburn, NY 13021 315.253.7301 Beardsley Design Associates Architecture, Engineering, Landscape Architecture, D.P.C. ©7/20/2016 11:55:16 AMC:\Projects\AG_16063_V2016_dvj.rvtJuly, 20 2016 16063Renovations for the CCB Dean's Suite at Statler Hall CORNELL UNIVERSITY 130 Statler Drive, Ithaca, New York 14853 Submission STATLER HALL 2016 DRAWING LIST NUMBER NAME ALL TRADES G-000 COVER SHEET ARCHITECTURAL A-101 FIRST FLOOR PLANS A-102 INTERIOR ELEVATIONS, DETAILS, AND FINISH SCHEDULE A-103 STOREFRONT AND DOOR DETAILS, TYPES & SCHEDULE A-104 BUILT IN DESK AND WALL DETAILS FIRE PROTECTION F-101 FIRST FLOOR PLANS MECHANICAL M-101 SYMBOLS, ABBREVIATIONS, SCHEDULES, DETAILS AND SCHEMATIC M-102 FIRST FLOOR PLUMBING AND MECHANICAL PLANS ELECTRICAL E-101 LIGHTING AND POWER PLAN SITE LOCATION MAP WORK AREA F F F F OS1 OS1 OS1 OS1 F OS1 OSOS1 OS F K J H G 25 26 27 E8 E 28 WINDOW HEADS & SOFFITS PROVIDE PT-1 FINISH AT PT-1 PT-1 WINDOW HEADS & SOFFITS PROVIDE PT-1 FINISH AT MODIFY EXISTING SUSPENDED ACOUSTIC CEILING SYSTEM TO ACCOMMODATE NEW LIGHT FIXTURE K J H G 25 26 27 E8 E 28 REMOVE DOORS, SHELVING, AND CABINET DIVIDERS REMOVE COUNTERTOP AND BUILT-IN CASEWORK - SALVAGE UPPER CABINETS TO REUSE REMOVE DOOR, FRAME, AND HARDWARE - SALVAGE FOR REUSE AND REINSTALLATION (SEE PLAN) REMOVE SHELVING AND CASEWORK REMOVE WALL TO ACCOMMODATE NEW WORKSTATION VIF 5'-10" +/-± 3'-9 3/4" RECESSED LIGHT FIXTURE UNIVERSAL MOUNT EXIT LIGHT OS1 OCCUPANCY SENSOR CEILING LEGEND SUPPLY DIFFUSER RETURN GRILLE SPRINKLER HEAD FIRE-RATED HORIZONTAL SHAFT ASSEMBLY (1-HOUR UNLESS NOTED OTHERWISE) ACT CEILING - 2X2 ACT-1 ARMSTRONG ULTIMA 1912 CEILING TAG9'-0"1 PT-1 TYPE HEIGHT AFF FINISH F FIRE ALARM NOTIFICATION APPLIANCE REMOVE ALL CARPET AND PREPARE SUBSTRATE TO RECEIVE NEW FINISH FLOORING. REMOVE ALL DOORS, FRAMES, WALLS, ETC. AS INDICATED ON THE PLAN UNLESS DESIGNATED FOR REUSE. TURN DOORS, FRAMES, & HARDWARE OVER TO OWNER. PROTECT ALL FIXED ELECTRICAL, MECHANICAL, PLUMBING, CASEWORK, AND DOORS FROM DAMAGE. PROVIDE TEMPORARY SUPPORT FOR ALL ELECTRICAL, DUCTWORK, & PIPING, TO REMAIN IN PLACE. REMOVE SUSPENDED CEILING SYSTEMS THROUGHOUT. REMOVE ALL VINYL WALL COVERING AND PREPARE RESULTING SUBSTRATE TO RECEIVE NEW WALL FINISH AS SCHEDULED. DEMOLITION NOTES REMOVE ALL SHELVING, AND ALL OTHER MISCELLANEOUS WALL-MOUNTED ITEMS AND TURN OVER TO OWNER. SALVAGE MATERIAL AND EQUIPMENT TO OWNER AS NOTED OR AS DIRECTED BY THE OWNER'S REPRESENTATIVE. OWNER RESERVES THE RIGHT TO CLAIM ITEMS SCHEDULED FOR DEMOLITION. OWNER SHALL IDENTIFY THE ITEMS THEY REQUIRE TO BE SALVAGED. SALVAGING BY THE CONTRACTOR SHALL INCLUDE ALL ASSOCIATED DISCONNECTS, REMOVALS OF INTACT ASSEMBLIES, THEIR PROTECTION, ORGANIZING AND RELOCATION IN THE WORK AREA . THE CONTRACTOR SHALL REMOVE AND STORE THESE ITEMS IN AN AREA AS DIRECTED BY THE OWNER'S REPRESENTATIVE. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. HAZARDOUS MATERIALS ARE NOT EXPECTED TO BE PRESENT IN THE EXISTING CONSTRUCTION INDICATED TO BE DEMOLISHED. A REPORT OF THE PRESENCE OF KNOWN HAZARDOUS MATERIALS IS AVAILABLE FROM THE OWNER FOR THE CONTRACTOR'S REVIEW. ALL CONTRACTORS SHALL EXAMINE THE REPORT TO BECOME FAMILIAR WITH LOCATIONS WHERE HAZARDOUS MATERIAL MAY POTENTIALLY BE ENCOUNTERED. DO NOT DISTURB MATERIAL SUSPECTED OF CONTAINING HAZARDOUS MATERIALS. IF IN THE COURSE OF THE WORK SUSPECT MATERIALS ARE ENCOUNTERED, THE CONTRACTOR SHALL STOP REMOVALS AND IMMEDIATELY NOTIFY THE OWNER'S PROJECT REPRESENTATIVE AND ARCHITECT. THE EXTENT OF DEMOLITION IS GENERALLY INDICATED ON THE CONTRACT DOCUMENTS BUT MAY NOT REPRESENT ALL DEMOLITION REQUIRED TO ACCOMMODATE THE WORK. DEMOLITION REQUIRED TO PROVIDE A FULL AND COMPLETE FINISHED PROJECT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. WHEREVER REMOVALS OCCUR, CONTRACTOR SHALL PATCH ALL ADJACENT DAMAGED WALLS, FINISHES, ETC. TO A SMOOTH AND EVEN FINISH TO BLEND SMOOTHLY WITH ADJACENT SURFACES. GENERAL NOTES 1. 2. 3. 4. 5. EXISTING CONDITIONS ARE TAKEN FROM FIELD OBSERVATION AND PRIOR CONSTRUCTION DOCUMENTS WHEN AVAILABLE. ALL EXISTING DIMENSIONS ARE APPROXIMATE AND SUBJECT TO CONTRACTOR'S VERFIFICATION. EVERY ATTEMPT HAS BEEN MADE TO INDICATE PERTINENT EXISTING UTILITIES AND WALL CONDITIONS AS ACCURATELY AS POSSIBLE FROM EXISTING SURVEYS, DRAWINGS AND OTHER DATA. PRIOR TO THE BID OPENING, THE CONTRACTOR SHALL WALK THE JOB SITE AND SATISFY THEMSELVES WITH REGARD TO EXISTING CONDITIONS. THE ARCHITECT SHALL BE CONSULTED WHEN ANY QUESTIONS ARISE RELATIVE TO MATERIALS OR CONDITIONS THAT ARE NOT SPECIFICALLY SHOWN OR SPECIFIED. THE CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR ALL ACCESSORIES AND ITEMS REQUIRED FOR A COMPLETE AND PROPER INSTALLATION PER THE MANUFACTURER'S RECOMMENDATIONS. WHEREVER NEW BACKER ROD AND/OR SEALANT IS TO BE USED THE CONTRACTOR SHALL REMOVE ALL LOOSE DEBRIS, DIRT, AND FINES FROM THE JOINT AND PROVIDE SURFACE PREPARATION AS REQUIRED TO ENSURE A PROPER BOND. WHEN, DURING THE COURSE OF WORK, EXISTING CONSTRUCTION THAT IS INDICATED AS REMAINING IS DAMAGED, THE CONTRACTOR SHALL REPAIR OR REPLACE WITH MATCHING MATERIAL AT NO EXPENSE TO THE OWNER. REPAIR OR REPLACEMENT METHODS AND MATERIALS SHALL BE SUBJECT TO THE ARCHITECT'S APPROVAL. RETAIN GWB SOFFITS AT ALL WINDOWS OPEN OFFICE 174 OFFICE 174C OFFICE 174D OFFICE 174E OFFICE 174F OFFICE 174G OFFICE 174H WAITING 176 OFFICE 174A 1 3 5/8" METAL STUDS AT 16" OC, WITH ONE LAYER OF 5/8" TYPE 'X' GWB EACH SIDE METAL STUDS GYPSUM WALL BOARD 5/8"3 5/8"5/8" 2 FIRE RATING: 2HR FIRE TEST: U415 2 1/2" C-H METAL STUDS AT 16" OC WITH TWO (2) LAYERS 1/2" TYPE "X" GWB ROOM SIDE AND ONE (1) LAYER OF 1" GWB LINER PANEL AT SHAFT SIDE GYPSUM WALL BOARD 2 1/2" C-H STUDS 1"2 1/2" GYPSUM WALL BOARD K J H G 25 26 27 E8 E 28 A.D. OFF. 174A 16'-4"6'-0" WAITING 176 OPEN OFFICE 174 18'-0"BUILT-IN DESK TOP A-1024 HDWD PLYWOOD VENEER WALL SYSTEM 13'-4" DEAN'S OFF. 174C DEAN'S OFF. 174D MEETING RM. 174B 174B 174D 174C A-103 5 A-104 A 1 1 1 COUNTER ABOVE DESK TOP 2 PATCH EXISTING WALLS AS REQUIRED FOLLOWING REMOVALS (TYP THROUGHOUT) EXISTING FURNITURE TO REMAIN - COORDINATE REMOVAL AND REINSTALLATION WITH OWNER'S PROJECT REPRESENTATIVE PT-4 AT WALL PT-2 (TYP AT ALL FAN COILS) PT-3 AT WALL SURFACES ABOVE AND BELOW COUNTER NOTE: PROVIDE PT-5 AT ALL WALLS UNLESS NOTED OTHERWISE PT-2 (TYP AT ALL HM FRAMES) A-104 3 5'-2"Beardsley Design Associates Architecture, Engineering, Landscape Architecture, D.P.C. ©Filename:no. revision description by date Project Number: Drawn By: Designed By: Reviewed By: WARNING Any alterations to this document not conforming to section 7307. New York State Education Law are strictly prohibited. 320 West Main Street Malone, NY 12953 518.483.1585 5789 Widewaters Pkwy Dewitt, NY 13214 315.472.6980 64 South Street Auburn, NY 13021 315.253.7301 AUBURN MALONE SYRACUSE 7/20/2016 11:55:14 AMC:\Projects\AG_16063_V2016_dvj.rvtARCHITECTURAL CORNELL UNIVERSITYITHACA, NEW YORKA-101 July, 20 2016 FIRST FLOOR PLANSRenovations for the CCB Dean's Suite at Statler Hall130 Statler Drive, Ithaca, New York 14853Submission DVJ/NRH 16063 LL DVJ 2016 PLAN NORTH 0'8'4'16'24' SCALE : 1/8" = 1'-0" SCALE: 1/8" = 1'-0" 3 REFLECTED CEILING PLAN SCALE: 1/8" = 1'-0" 2 DEMOLITION PLAN SCALE: 1" = 1'-0" 5 PARTITION TYPES SCALE: 1/8" = 1'-0" 1 FIRST FLOOR PLAN 1 A-102 2 A-102 3'-0"1'-8"2'-6"3'-0"1'-8"1'-3"1'-3"COPIER BY OWNER 18" DEEP MICROWAVE CABINET 3'-0"3'-0"2'-11" VIF 3'-0". VIF 3'-0".EXISTING7'-2"OPEN TO WAITING AREA BEYOND OPEN TO RECEIVE UNDERCOUNTER REFRIGERATOR (NIC) - PROVIDE PAINT AND WALL BASE AT ALL SIDES OF OPENING REPLACE EX. WOOD PANELS WITH REGLETS TO MATCH EXISTING AT AREAS WHERE DAMAGED FOLLOWING COUNTERTOP REMOVALS 2'-0"RELOCATE SALVAGED UPPER CABINETS SOLID SURFACE COUNTERTOPS (TYP THIS ELEVATION) MATCH HEIGHT OF EXISTING REGLET (TYP) ± 1'-11"1'-0"3'-0" PROVIDE ADJUSTABLE SHELF (TYP WHERE INDICATED IN ELEVATIONS) 262728 EXISTING STOREFRONT HARDWOOD VENEER PLYWOOD WALL PANEL SYSTEM 10'-0"ALIGN W/ STOREFRONT7'-2"3'-0"1'-8"2'-6"SOLID SURFACE COUNTERTOP OVER 3/4" MDF 3/4" HDWD PLYWOOD VENEER 3/4" HDWD VENEER PLYWOOD W/ 3/4" HDWD NOSING (VERTICAL) MICROWAVE SHELF W/ FINISH SIDES AND BACK TO MATCH CASEWORK 95/256" 1'-6" 1'-0" 2'-6" 5/8" GWB HARDWD NOSING ALUM REGLET 2 1/2" METAL STUD FRAMING 3/4" HDWD VENEER PANEL SOLID SURFACE OVER 3/4" PLYWOOD COUNTERTOP 1'-8"3'-0"ADJUSTABLE SHELF ADJUSTABLE SHELF 5/8" GWB 2'-6" DRAWER HWD NOSING ALUM REGLET 2 1/2" METAL STUD FRAMING 3/4" HWD VENEER PANEL 1K 3'-0"1'-10"3'-0"FILLER PANEL (TYP BOTH SIDES) SOLID SURFACE (C1) COUNTERTOP WITH 1/4 ROUND TOP WOOD BASE (B1) ADJUSTABLE SHELF (TYP) 2'-0"4'-0" 4'-0"2'-0" J H G CENTERLINE 5'-6"3'-0"2 A-104 OPEN SHELVING BEYOND 2'-6"4'-0"HARDWOOD VENEER PLYWOOD WALL PANEL SYSTEM AT DISPLAY WALL WITH REGLET REVEALS RETURN PLYWOOD VENEER SYSTEM TO WALL AT DISPLAY WALL BASE (TYP BOTH SIDES) PROVIDE REGLET AT CORNERS SOLID SURFACE COUNTER/CAP AT WALL PROJECTION - PROVIDE 1" OVERHANG AT WALL EDGE 2'-6"6'-2" PT-4PT-4 PT-3 PROVIDE 1" X 2" SOLID HARDWOOD CAP AT CEILING (FINISH TO MATCH CASEWORK) RESIN PANEL SYSTEM (R-1) SHELF BRACKETS AT MID-SPAN SOLID SURFACE COUNTERTOP SOLID SURFACE COUNTERTOP 1'-6"5'-8"1'-6" ONE ADJUSTABLE SHELF (TYP) FILLER PANEL GLAZED SCREEN WITH TRANSLUCENT FILM 7 A-102 5"2'-6"WOOD BASE WOOD PANELING SS-1 SOLID HWD CAP EXISTING WALL TO REMAIN HOOK AND LOOP FASTENING SYSTEM 3/4" HWD VENEER PANEL ALIGN TO STUDS AS NECESSARY TO SUPPORT VENEER PANEL ALUM REGLET 3/8"3/8" BLOCKING AS REQ. Beardsley Design Associates Architecture, Engineering, Landscape Architecture, D.P.C. ©Filename:no. revision description by date Project Number: Drawn By: Designed By: Reviewed By: WARNING Any alterations to this document not conforming to section 7307. New York State Education Law are strictly prohibited. 320 West Main Street Malone, NY 12953 518.483.1585 5789 Widewaters Pkwy Dewitt, NY 13214 315.472.6980 64 South Street Auburn, NY 13021 315.253.7301 AUBURN MALONE SYRACUSE 7/20/2016 2:32:54 PMC:\Projects\AG_16063_V2016_dvj.rvtARCHITECTURAL CORNELL UNIVERSITYITHACA, NEW YORKA-102 July, 20 2016 INTERIOR ELEVATIONS, DETAILS, AND FINISH SCHEDULE Renovations for the CCB Dean's Suite at Statler Hall130 Statler Drive, Ithaca, New York 14853Submission DVJ/NRH 16063 LL DVJ 2016 0'8'4'16'24' SCALE : 1/8" = 1'-0" SCALE: 1/4" = 1'-0" 3 ELEVATION AT BUILT-IN CASEWORK SCALE: 1/4" = 1'-0" 4 CORRIDOR ELEVATION SCALE: 1 1/2" = 1'-0" 1 Section 1 SCALE: 1 1/2" = 1'-0" 2 Section 2 INTERIOR FINISH LEGEND MARK MATERIAL MANUFACTURER SERIES / COLOR COMMENTS BASE B-1 WOOD -- MAPLE TO MATCH EXISTING. TYP 4" HIGH. VIF. B-2 RUBBER JOHNSONITE SILVER GREY WG 55 TYP 4" FLOORING F-1 CARPET - BROADLOOM SHAW CONTRACT SWITCH 5A205 - GAZE 03530 WALL COVERINGS R-1 RESIN LUMICOR SILVER TWILIGHT - LUMICLEAR FRONT AND BACK GLOSS FINISH WALL / PAINT FINISH PT-1 PAINT BENJAMIN MOORE SEASHELL OC-120 AT ALL EXISTING GWB SOFFITS AND WINDOW HEADS PT-2 PAINT BENJAMIN MOORE OZARK SHADOW - AC-26 AT ALL FAN COILS & HM FRAMES PT-3 PAINT BENJAMIN MOORE CHANTILLY LACE - OC-65 PT-4 PAINT BENJAMIN MOORE CORNELL'S RED PT-5 PAINT BENJAMIN MOORE GRAY OWL - OC-52 CASEWORK CW-1 WOOD -- SPECIES MAPLE TO MATCH EXISTING COUNTER C-1 SOILD SURFACE FORMICA LUNA CONCRETE 781 CEILING ACT-1 ACOUSTICAL CEILING TILE ARMSTRONG ULTIMA 1912 ROOM FINISH SCHEDULE ROOM FLOOR FINISH BASE FINISH WALL FINISH CASEWORK FINISH WINDOW TREATMENT COMMENTSROOM NO. ROOM NAME 174 OPEN OFFICE F-1 B-1, B-2 PT-3, PT-1 MAPLE OWNER 174A A.D. OFF. F-1 B-2 PT-5 MAPLE OWNER 174B MEETING RM. F-1 B-2 PT-3, PT-4 MAPLE OWNER 174C DEAN'S OFF. F-1 B-2 PT-5, PT-4 MAPLE OWNER 174D DEAN'S OFF. F-1 B-2 PT-5, PT-4 MAPLE OWNER 176 WAITING F-1 B-2 PT-3 MAPLE N/A SCALE: 1/4" = 1'-0" 5 CASEWORK AT MEETING RM. SCALE: 1/4" = 1'-0" 6 ELEVATION AT MEETING RM./ OPEN OFFICE SCALE: 3/4" = 1'-0" 7 WOOD PANELING AT MEETING ROOM SCALE: 3" = 1'-0" 8 WOOD PANEL PLAN DETAIL 2526 6 A-103 PROVIDE WINDOW FILM WITH GRADATION AT TOP AND BOTTOM OF AREA INDICATED BASIS OF DESIGN: 3M FASARA LONTANO GRADATION 2'-0"4'-0"1'-6"3'-3"WOOD BASE (B1) 9 A-103 9 A-103 7 A-103 8 A-103 8 A-103 DIMENSIONALLY DISTORTED - REFER TO PLAN GLAZED PANELS AT SEGMENTED CURVE MAY APPEAR PT-1 FINISH AT EXISTING WINDOW HEADS AND SOFFITS TO REMAIN PROVIDE SEALANT (TYP AT ALL SIDES OF FRAME) 3 ANCHORS PER JAMB EXISTING HOLLOW METAL FRAMEJAMB TYPE J1 ABBREVIATIONS SS - SINGLE SWING F - FLUSH DOOR HM - HOLLOW METAL PT - PAINT WD - WOOD T - TEMPERED MFR - MANUFACTURER K J 26 6 A-103 6'-2"R 6'-2" SEGMENTED CURVE6'-4 5/8"6'-5" PROVIDE GLAZED INTERIOR WALL AND DOOR ASSEMBLY BASIS OF DESIGN: CRL CLEAR VIEW SERIES FRAMELESS GLASS WALL OFFICE SYSTEM A-102 5 174B 6 ALIGN FACES OF WALLS PROVIDE CLEAR COPOLYMER STRIP AT GLASS-TO-GLASS JOINTS (TYP) A-103 8 A-103 8 A-103 8 A-103 8 VIF16'-4" ±4'-0"6'-5" 2'-9"6'-2"4 1/2"FEATURE WALL PROJECTION BELOW PT-4 (TYPICAL AT BOTH SIDES OF WALL) 7 A-102 First Floor 100'-0" Second Floor 110'-4 1/2" J EXISTING BEAM AND COLUMN CONSTRUCTION TO REMAIN EXISTING CONSTRUCTION BEYOND TO REMAIN7'-10"VIF± 2'-6 1/2"15/16" CEILING WALL ANGLE - RUN CONTINUOUSLY PAST COLUMN COORD CEILING TYPES WITH REFLECTED CEILING PLAN SHORTEN WALL AND PROVIDE SEALANT AT EDGES OF FINISHES WHERE WALL INTERSECTS BEAM GLAZED INTERIOR WALL AND DOOR ASSEMBLY FLOOR FINISHES AND BASE AS SCHEDULED 3 5/8" METAL STUD WITH ONE (1) LAYER 5/8" TYPE "X" GWB ON EACH SIDE - FILL CAVITY WITH SOUND ATTENUATION BATT INSULATION DOOR SILL AT PIVOT DOOR SILL AT LOCK BOTTOM DOOR PATCH FITTING W/ INSERT 1/2" MONOLITHIC, TEMPERED GLASS ADJUSTABLE FREE SWINGING FLOOR PIVOT 1/2" MONOLITHIC, TEMPERED GLASS BOTTOM DOOR LOCK PATCH KEEPER FIN. FLOOR FIN. FLOOR 3/8"NET DOOR HEIGHTROUGH OPENING DIMENSION3/8"NET DOOR HEIGHTROUGH OPENING DIMENSIONEXISTING CONCRETE SLAB EXISTING RAISED WOOD FLOOR SYSTEM EXISTING CONCRETE SLAB EXISTING RAISED WOOD FLOOR SYSTEM SIDELITE AT WALL DOOR JAMB AT WALL (J2) SIDELITE GLASS JOINT 1" DEEP U-CHANNEL 1/2" MONOLITHIC, TEMPERED GLASS PERPENDICULAR WALL BOTTOM DOOR PATCH FITTING W/ INSERT ADJUSTABLE FREE SWINGING FLOOR PIVOT PIVOT 1/2" MONOLITHIC, TEMPERED GLASS 1" DEEP U-CHANNEL 1/2" MONOLITHIC, TEMPERED GLASS CLEAR COPOLYMER STRIP FOR 180° GLASS TO GLASS JOINT 1/2" MONOLITHIC, TEMPERED GLASS DOOR HANDLE, STYLE AS SPECIFIED CONSULT CUSTOMER SERVICE SPECIALIST FOR OPTIONS.1" DEEP U-CHANNEL 1/2" MONOLITHIC, TEMPERED GLASS CLEAR COPOLYMER STRIP FOR 90° ABUTMENT GLASS TO WALL JOINT END CAP NET SIDELITE WIDTH ROUGH OPENING DIMENSION 1/8" NET DOOR WIDTH DOOR OPENING1/8" 2 5/8" 6 7/16" ROUGH OPENING DIMENSION SIDELITE GLASS DIMENSION 1/8" SIDELITE GLASS DIMENSION NET DOOR WIDTH 1/8" COORD DIMENSIONS WITH MANUFACTURER NET SIDELITE WIDTH DOOR OPENING DOOR JAMB AT SIDELITE (J3)2"SIDELITE HEAD DETAIL SIDELITE SILL DETAIL 1/2" MONOLITHIC, TEMPERED GLASS 1" DEEP U-CHANNEL ROLL-IN GLAZING GASKET 1/2" MONOLITHIC, TEMPERED GLASS 1/4" THICK x 1/2" WIDE x 4" LONG NEOPRENE SETTING BLOCK FASTENER 1-1/2" DEEP U-CHANNEL ROLL-IN GLAZING GASKET FASTENER CEILING AND FRAMING - COORD WITH WALL SECTIONS AND PLANS FIN. FLOOR NET SIDELITE HEIGHTROUGH OPENING DIMENSIONNET SIDELITE HEIGHTROUGH OPENING DIMENSION1/4"±SHIM AS REQ'D1"1"1 1/2"1" EXISTING CONCRETE SLAB EXISTING RAISED WOOD FLOOR SYSTEM Beardsley Design Associates Architecture, Engineering, Landscape Architecture, D.P.C. ©Filename:no. revision description by date Project Number: Drawn By: Designed By: Reviewed By: WARNING Any alterations to this document not conforming to section 7307. New York State Education Law are strictly prohibited. 320 West Main Street Malone, NY 12953 518.483.1585 5789 Widewaters Pkwy Dewitt, NY 13214 315.472.6980 64 South Street Auburn, NY 13021 315.253.7301 AUBURN MALONE SYRACUSE 7/20/2016 11:55:15 AMC:\Projects\AG_16063_V2016_dvj.rvtARCHITECTURAL CORNELL UNIVERSITYITHACA, NEW YORKA-103 July, 20 2016 STOREFRONT AND DOOR DETAILS, TYPES & SCHEDULERenovations for the CCB Dean's Suite at Statler Hall130 Statler Drive, Ithaca, New York 14853Submission DVJ/NRH 16063 LL DVJ 2016 0'8'4'16'24' SCALE : 1/8" = 1'-0" SCALE: 1/4" = 1'-0" 1 ELEVATION OF STOREFRONT DOOR SCHEDULE NUMBERFROM ROOM TO ROOM DOORS FRAMES GLASS THRESHOLDHARDWARE GROUPCOMMENTSTYPEWIDTHHEIGHTMATERIALFINISHELEVATIONMATERIALFINISHJAMB TYPEINCLUDEDTYPE174B OPEN OFFICE MEETING RM. SS 3'-0" 7'-6" AL/GLASS MFR 1/A-103 AL MFR J2/J3 Yes T - MFR DOOR HEIGHT TO MATCH HEIGHT OF GLASS PARTITION 174C OPEN OFFICE DEAN'S OFF. SS 3'-0" 7'-0" WD STAIN EXIST HM PT-2 J1 - - - SALVAGED DOOR, FRAME AND HARDWARE TO BE REINSTALLED 174D OPEN OFFICE DEAN'S OFF. SS 3'-0" 7'-0" WD STAIN EXIST HM PT-2 J1 - - - SALVAGED DOOR, FRAME AND HARDWARE TO BE REINSTALLED SCALE: 3" = 1'-0" 2 DOOR JAMB - HM @ METAL STUD SCALE: 1/4" = 1'-0" 5 PLAN DETAIL AT GLASS WALL SCALE: 3/4" = 1'-0" 6 TYPICAL SECTION AT GLASS WALL SCALE: 6" = 1'-0" 7 Glass Wall Details - Door Sill SCALE: 6" = 1'-0" 8 PLAN DETAILS AT GLASS WALL SCALE: 6" = 1'-0" 9 DETAILS AT GLASS WALL SIDELITE HEAD AND SILL H G 26 A-102 3 1 A-102 2 A-102 A-1024 1 A-104 16'-4" R 9'-0" 2 A-104 OPEN SHELVING THIS SIDE OPEN SHELVING THIS SIDE2'-1"7'-10 1/2"CLEAR3'-0"DESKTOP SUPPORT AT MID-SPAN (TYP OF TWO) 2 HOUR SHAFT WALL AT CHASE - TIE TO EXISTING WALL --- - PROVIDE FINISHED 1" X 2" HARDWOOD CAP TRIM AT TOP OF WALL WHERE WALL MEETS CEILING SYSTEMEQEQA-104 3 RESIN PANELS A-102 87'-6"FIELD VERIFY CONDITION OF SHAFT PATCH TO MAINTAIN CONTINUITY OF SHAFT ALL AROUND First Floor 100'-0"4'-0"1"6"2" SOLID SURFACE OVER 3/4" PLYWOOD 1 1/2"3/4"3'-6"1/4" THICK TRANSLUCENT RESIN PANEL SYSTEM 5/8" GWB OVER 1/2" PLYWOOD EACH SIDE WOOD BASE 3 5/8" METAL STUDS AT 1-4" OC EXISTING WOOD SUBFLOOR EXISTING CONCRETE FLOOR 1" SS STAND-OFF FASTENERS. BARREL LENGTH 1" SS STAND-OFF FASTENERS First Floor 100'-0" 26 2'-6"1'-6"2'-1" SOLID SURFACE OVER 3/4" PLYWOOD 3/4" HARDWOOD PLYWOOD VERTICAL SUPPORT AT 2'-0" OC MAX; PROVIDE HDWD NOSING AT EXPOSED EDGE 12 GA. STEEL PLATE DESK SUPPORT BRACKET W/ POWDERCOAT FINISH; ALIGN EXISTING STUDS 2'-8" OC MAX 5/8" GWB 3 5/8" METAL STUDS AT 1'4" OC 3/4" HARDWOOD PLYWOOD 1"1" WOOD BASE EACH SIDE EXISTING WALL BEYOND EXISTING WALL ADD BLOCKING AS NECESSARY TO SUPPORT COUNTER4'-0"1'-3"1'-9" PROVIDE THREE GROMMETS; ALIGN WITH POWER/DATA LOCATIONS BELOW 1 A-104 1"3'-0"1/2"3'-6"4'-0"1/2" LUMICOR RESIN PANELS. TYPICAL DIMENSIONS INDICATED VIF. SS-1 WOOD BASE Beardsley Design Associates Architecture, Engineering, Landscape Architecture, D.P.C. ©Filename:no. revision description by date Project Number: Drawn By: Designed By: Reviewed By: WARNING Any alterations to this document not conforming to section 7307. New York State Education Law are strictly prohibited. 320 West Main Street Malone, NY 12953 518.483.1585 5789 Widewaters Pkwy Dewitt, NY 13214 315.472.6980 64 South Street Auburn, NY 13021 315.253.7301 AUBURN MALONE SYRACUSE 7/20/2016 11:55:16 AMC:\Projects\AG_16063_V2016_dvj.rvtARCHITECTURAL CORNELL UNIVERSITYITHACA, NEW YORKA-104 July, 20 2016 BUILT IN DESK AND WALL DETAILS Renovations for the CCB Dean's Suite at Statler Hall130 Statler Drive, Ithaca, New York 14853Submission DVJ/NRH 16063 LL DVJ 2016 SCALE: 1/4" = 1'-0" A FIRST FLOOR PLAN PARTIAL SCALE: 1 1/2" = 1'-0" 1 HALF WALL DETAIL SCALE: 1 1/2" = 1'-0" 2 DESKTOP & COUNTER DETAIL SCALE: 1/2" = 1'-0" 3 RESIN PANEL ELEVATION INSTALL FASTENERS PER MANUFACTURER'S INSTRUCTIONS 4 PER PANEL (TYP) FIRE PROTECTION SYMBOL LEGEND - NEW PIPE SYSTEM PIPING - CONCEALED PENDENT SPRINKLER - PIPE RISE ABOVE - DROP FROM BOTTOM OF PIPE - PIPE TURNS DOWN - PIPE CAP/PLUG - CEILING SUPPLY DIFFUSER (SHOWN FOR REFERENCE ONLY) - CEILING EXHAUST/RETURN DIFFUSER (SHOWN FOR REFERENCE ONLY) - EXISTING PIPE SYSTEM PIPING - EQUIPMENT TO BE REMOVED - ABOVE FINISHED FLOOR ELEVATION - POINT OF CONNECTION OR DISCONNECTION AFF PROVIDE MODIFICATIONS TO AN EXISTING WET PIPE TYPE FIRE SPRINKLER SYSTEM SERVING EXISTING OFFICE AREA. COORDINATE WITH EH&S AND ITHACA FIRE DEPARTMENT PRIOR TO SHUT DOWN AND DRAINING OF EXISTING SPRINKLER SYSTEM ZONE SERVING EXISTING OFFICE AREA. COORDINATE AND PERFORM WORK IN A MANNER WHICH MINIMIZES SPRINKLER SYSTEM IMPAIRMENT IN THE AREAS. DEVELOP PLAN INDICATING EXTENT AND EXPECTED DURATION OF SYSTEM IMPAIRMENT AND REVIEW WITH EH&S AND ITHACA FIRE DEPARTMENT. WHILE EXISTING SYSTEM PIPING AS INDICATED IS BASED ON PREVIOUS CONTRACT DRAWINGS, SUBCONTRACTOR IS RESPONSIBLE FOR FINAL VERIFICATION OF ALL LOCATIONS AND SIZES. PIPING AS SHOWN OR INDICATED IS DIAGRAMMATIC. SUBCONTRACTOR IS RESPONSIBLE FOR FINAL SPRINKLER SYSTEM PIPE LAYOUT AND COORDINATION WITH ALL EXISTING CONDITIONS AND OTHER TRADES. REMOVE EXISTING WET PIPE SYSTEM BRANCH LINE, PIPING, FITTINGS, SPRINKLERS, AND ASSOCIATED HANGERS INDICATED. PROVIDE CONNECTION TO EXISTING WET PIPE SYSTEM AT CROSS MAINS AND/OR BRANCH LINES. PROVIDE ALL PIPING FITTINGS, HANGERS AND SPRINKLERS REQUIRED TO MAKE ALTERATIONS INDICATED AND INSTALL IN ACCORDANCE WITH REQUIREMENTS OF NFPA 13 AND SPECIFICATIONS. PROVIDE FIRE STOPPING AT EXISTING PIPE PENETRATIONS THROUGH EXISTING MASONRY CONSTRUCTION AT COLUMN LINE 10. PROVIDE FIRE STOPPING LEFT FROM REMOVALS. TEST MODIFIED SYSTEM IN ACCORDANCE WITH NFPA 13 AND 25 REQUIREMENTS. FIRE PROTECTION GENERAL NOTES 1. 2. 3. 4. 5. 6. 7. 8. SECTION 21 13 13 - WET-PIPE FIRE SPRINKLER SYSTTEM PART 1 - GENERAL 1.1 PERFORMANCE REQUIREMENTS A.PROVIDE MODIFICATION TO AN EXISTING WET-PIPE SPINKLER SYSTEM. B.STANDARD-PRESSURE PIPING SYSTEM COMPONENTS: LISTED FOR 175-PSIG (1200-KPA) MINIMUM WORKING PRESSURE. C.DESIGN SPINKLER SYSTEM(S) USING INDICATED PIPE SIZES AND PERFORMANCE REQUIREMENTS AND DESIGN CRITERIA INDICATED. D. SPINKLER SYSTEM DESIGN SHALL BE APPROVED BY AUTHORITIES HAVING JURISDICTION. 1.SPRINKLER OCCUPANCY HAZARD CLASSIFICATIONS: a.OFFICES: LIGHT HAZARD. 1.2 SUBMITTALS A.PRODUCT DATA: FOR EACH TYPE OF PRODUCT INDICATED. INCLUDE RATED CAPACITIES, OPERATING CHARACTERISTICS, AND FURNISHED SPECIALTIES AND ACCESSORIES. B.SHOP DRAWINGS: FOR WET-PIPE SPRINKLER SYSTEMS. INCLUDE PLANS, ELEVATIONS, SECTIONS, DETAILS, TRADE COORDINATION AND ATTACHMENTS TO OTHER WORK. PREPARE IN ACCORDANCE WITH NFPA 13 FOR APPROVAL BY AUTHORITY HAVING JURISDICTION. C.FIELD TEST REPORTS AND CERTIFICATES: INCLUDE "CONTRACTOR'S MATERIAL AND TEST CERTIFICATE FOR ABOVE GROUND PIPING." 1.2 PROJECT CONDITIONS A.INTERRUPTION OF EXISTING SPRINKLER SERVICE: DO NOT INTERRUPT SPRINKLER SERVICE TO FACILITY UNLESS PERMITTED UNDER THE FOLLOWING CONDITIONS AND THEN ONLY AFTER ARRANGING TO PROVIDE TEMPORARY SPRINKLER SERVICE ACCORDING TO REQUIREMENTS INDICATED: 1.NOTIFY EH&S AND ITHACA FIRE DEPARTMENT NO FEWER THAN TWO DAYS IN ADVANCE OF PROPOSED INTERRUPTION OF SPRINKLER SERVICE. PART 2 - PRODUCTS 2.1 STEEL PIPE AND FITTINGS A. STANDARD WEIGHT, SCHEDULE 40, BLACK-STEEL PIPE: ASTM A53/A53M, TYPE F, GRADE A. PIPE ENDS MAY BE FACTORY OR FIELD FORMER TO MATCH JOINING METHOD. B.BLACK-STEEL PIPE NIPPLES: ASTM A733, MADE OF ASTM A53/A53M, STANDARD WEIGHT, SEAMLESS STEEL PIPE WITH THREADED ENDS. C. UNCOATED, GRAY-IRON THREADED FITTINGS: ASME B16.4, CLASS 125, STANARD PATTERN. D. UNCOATED, GRAY-IRON THREADED FITTINGS: ASME B16.4, CLASS 125, STANARD PATTERN. E.GROOVED-JOINT, STEEL-PIPE APPURTENANCES: 1.UNCOATED, GROOVED-END FITTINGS FOR STEEL PIPING: ASTM A47/A47M, MALLEABLE IRON CASTING OR ASTM A536, DUCTILE-IRON CASTING; WITH DIMENSIONS MATCHING STEEL PIPE. 2. GROOVED-END-PIPE COUPLINGS FOR STEEL PIPING: AWWA C606 AND UL 213, RIGID PATTEN, UNLESS OTHERWISE INDICATED, FOR STEEL-PIPE DIMENSIONS. INCLUDE FERROUS HOUSING SECTIONS, EPDM-RUBBER GASKET, AND BOLTS AND NUTS. 2.2 SPRINKLER SPECIALTY PIPE FITTINGS A.BRANCH OUTLET FITTINGS: 1.STANDARD: UL 213 2.PRESSURE RATING: 175 PSIG (1200 KPA) MINIMUM. 3. BODY MATERIAL: DUCTILE-IRON HOUSING WITH EPDM SEALS AND BOLTS AND NUTS. 4. TYPE: MECHANICAL-T AND CROSS FITTINGS. 5.BRANCH OUTLETS: GROOVED, PLAIN-END PIPE, OR THREADED. 2.3 SPRINKLERS A.AUTOMATIC CONCEALED TYPE PENDENT SPRINKLERS WITH QUICK RESPONSE TYPE HEAT-RESPONSIVE ELEMENT: 1.CHARACTERISTICS: NOMINAL 1/2-INCH (12.7-MM) ORIFICE WITH DISCHARGE COEFFICIENT K OF 5.6, AND FOR "ORDINARY" TEMPERATURE CLASSIFICATION RATING. B.SPRINKLER PLATE FINISHES: 1.WHITE. PART 3 - EXECUTION 3.1 PIPING INSTALLATION A.LOCATIONS AND ARRANGEMENTS: DRAWING PLANS AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING. INSTALL PIPING AS INDICATED, AS FAR AS PRACTICAL. B.PIPING STANDARD: COMPLE WITH REQUIREMENTS FOR INSTALLATION OF SPRINKLER PIPING IN NFPA 13. 3.2 FIELD QUALITY CONTROLS A.TEST AND INSPECTIONS: 1.CONDUCT TESTING WITH EH&S AND ITHACA FIRE DEPARTMENT. SCHEDULE TESTING THROUGH DAN PHILLIPS AT EH&S. 2.LEAK TEST: AFTER INSTALLATION, CHARGE SYSTEMS AND TEST FOR LEAKS. REPAIR LEAKS AND RETEST UNTIL NO LEAKS EXIST. 3.TEST, AND INSPECT SPINKLER SYSTEMS ACCORDING TO NFPA 13, "SYSTEMS ACCEPTANCE" CHAPTER. B.SPRINKLER PIPING SYSTEM WILL BE CONSIDERED DEFECTIVE IF IT DOES NOT PASS TESTS AND INSPECTIONS. C.PREPARE TEST AND INSPECTION REPORTS. 3.3 CLEANING A.CLEAN DIRT AND DEBRIS FROM SPRINKLERS. B.REMOVE AND REPLACE SPRINKLERS WITH PAINT OTHER THAN FACTORY FINISH. K J H G 25 26 27 E8 E 28 EX 2" 8'-3" AFFEX. 1 1/4" EX. 1" EX. 1" EX. 1 1/4" EX. 1" EX. 1"EX. 1" K J H G 25 26 27 E8 E 28 EX 2" 8'-3" AFF EX. 1 1/4" 1 1/4" 1" 1" 1" 1" 1 1/4"1" 1" ARM-OVERS TO CENTER OF CEILING TILE (TYP) Beardsley Design Associates Architecture, Engineering, Landscape Architecture, D.P.C. ©Filename:no. revision description by date Project Number: Drawn By: Designed By: Reviewed By: WARNING Any alterations to this document not conforming to section 7307. New York State Education Law are strictly prohibited. MALONE 320 West Main Street Malone, NY 12953 518.483.1585 SYRACUSE 5789 Widewaters Pkwy Dewitt, NY 13214 315.472.6980 AUBURN 64 South Street Auburn, NY 13021 315.253.7301 7/18/2016 3:42:52 PMC:\Projects\MG_16063_V2016_naf.rvtFIRE PROTECTION CORNELL UNIVERSITYF-101 07.20.2016 FIRST FLOOR PLANSRenovations for the CCB Dean's Suite at Statler Hall130 Stalter Drive, Ithaca, New York 14853ITHACA, NEW YORKSubmission NAF 16063 - GAH 2016 SCALE: 1/8" = 1'-0" A FIRST FLOOR FIRE PROTECTION DEMOLITION PLAN SCALE: 1/8" = 1'-0" B FIRST FLOOR FIRE PROTECTION ALTERATION PLAN 0'8'4'16'24' SCALE : 1/8" = 1'-0" COIL BALANCING VALVE ISOLATION VALVE (TYPICAL) RETURN PIPINGSUPPLY PIPING STRAINER BLOWDOWN WITH BRASS HOSE CONNECTION, CAP WITH CHAIN COIL DRAIN WITH BRASS HOSE CONNECTION, CAP AND CHAIN (TYPICAL) UNION (TYPICAL) PRESSURE/TEMPERTURE TEST PORT (TYP OF 2) MANUAL AIR VENT NOTE: 1. PROVIDE DRAIN PAN AND TRAP ON CHILLED WATER COILS ONLY. STANDARD RADIUS ELBOWSHORT RADIUS ELBOW WITH TWO VANES SHORT RADIUS ELBOW WITH ONE VANE 1/3 W R 2/3 W W R SHALL BE EQUAL TO OR GREATER THAN 1/3 W R SHALL BE EQUAL TO OR GREATER THAN W R SHALL BE EQUAL TO OR GREATER THAN 1/6 W 1/2 W 1/3 W 1/6 W R W W R NOTES: 1. MAKE THE INTERIOR SURFACE OF ALL RADIUS ELBOWS ROUND 2. MAKE ALL STANDARD RADIUS ELBOWS SHOWN ON PLANS SHORT RADIUS ELBOWS. ALL SHORT RADIUS ELBOWS HAVE VANES, AND VANES ARE CONSTRUCTED, SUPPORTED AND FASTENED IN ACCORDANCE WITH SMACNA VANE VANE MOUNTING FLANGE (TYP OF 2) VIBRATION ISOLATOR BUSHING OR RUBBER IN SHEAR ISOLATIONS INLET DUCTFLEXIBLE CONNECTOR (TYPICAL) FAN CASING OUTLET DUCT HANGER SUPPORT RODS TO BUILDING STRUCTURE. REFER TO STRUCTURAL DRAWINGS FOR CONNECTION TO FLOOR SLAB (TYPICAL OF 4) T - VOLUME DAMPER - CENTERED TRANSITION - SQUARE TO ROUND TRANSITION - RADIUS ELBOW - MITERED ELBOW WITH TURNING VANES - BRANCH TAKEOFF - CEILING RETURN GRILLE - THERMOSTAT - 4 - WAY CEILING SUPPLY DIFFUSER - MOTORIZED EQUIPMENT DESIGNATION - DIFFUSER/GRILLE DESIGNATION - KEYED NOTE MECHANICAL SYMBOLS MECHANICAL ABBREVIATIONS NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE NOT NECESSARILY USED NECK SIZE CFM ###-# TYPE - - CONNECT TO EXISTING - DISCONNECT FROM EXISTING - EQUIPMENT REMOVAL APD CFM CHR CHS CW EF EX HWR HWS IN MAX MIN NC RA SA VAV VD W WG - AIR PRESSURE DROP - CUBIC FEET PER MINUTE - CHILLED WATER RETURN - CHILLED WATER SUPPLY - COLD WATER - EXHAUST FAN - EXISTING - HOT WATER RETURN - HOT WATER SUPPLY - INCH - MAXIMUM - MINIMUM - NOISE CRITERIA - RETURN AIR - SUPPLY AIR - VARIABLE AIR VOLUME - VOLUME DAMPER - WATTS - WATER GAUGE - DISABLE THE SUPPLY FAN AND CLOSE THE COOLING COIL CONTROL VALVE. - CYCLE THE HEATING COIL CONTROL VALVE TO MAINTAIN THE SPACE TEMPERATURE SENSOR SETPOINT. - IF THE SPACE TEMPERATURE SHOULD FALL MORE THAN 4^F BELOW THE SPACE SENSOR SETPOINT, CYCLE THE SUPPLY FAN ON TO MAINTAIN TEMPERATURE. - OPERATE SUPPLY CONTINUOUSLY, SUBJECT TO A UNIT MOUNTED HI/LO SPEED ELECTOR SWITCH, CLOSE THE COOLING COIL CONTROL VALVE, AND CYCLE THE HEATING COIL CONTROL VALVE TO MAINTAIN A DISCHARGE AIR TEMPERATURE OF 110^F UNTIL SPACE TEMPERATURE RISES TO WITHIN 2 DEGREES OF ITS OCCUPIED SETPOINT. - OPERATE THE SUPPLY FAN CONTINUOUSLY SUBJECT TO THE UNIT MOUNTED HI/LO SPEED SELECTOR SWITCH. - ON A CALL FOR HEATING BY THE SPACE TEMPERATURE SENSOR, CLOSE THE COOLING COIL CONTROL VALVE TO MAINTAIN SPACE TEMPERATURE SETPOINT. - ON A CALL FOR COOLING BY THE SPACE SENSOR, CLOSE THE HEATING COIL CONTROL VALVE, AND CYCLE THE COOLING COIL CONTROL VALVE TO MAINTAIN THE SPACE TEMPERATURE SETPOINT. - ACTIVATION OF THE FIRE ALARM SYSTEM. - EQUIPMENT FAILURE. - RETURN THE SYSTEM TO THE UNOCCUPIED CYCLE WHENEVER ANY OF THE FOLLOWING OCCUR: - UPON SHUTDOWN OF THE SYSTEM, IDENTIFY THE FAILURE MODE AND NOTIFY THE BUILDING CONTROL SYSTEM OF THE ALARM CONDITION. 0A HEATINGCOILSA S/S HWSHWRC/OSTATUS COOLINGCOILCHSCHRC/O DA T PROVIDE THE FOLLOWING SEQUENCE OF OPERATION BY THE BUILDING CONTROL SYSTEM: UNOCCUPIED CYCLE: WARM-UP CYCLE: OCCUPIED CYCLE: UNIT SHUTDOWN: PROVIDE THE FOLLOWING SEQUENCE OF OPERATION BY THE BUILDING CONTROL SYSTEM: - INTERLOCK THE EXHAUST FAN WITH THE OCCUPANCY SENSOR. PROVIDE 60 SECOND, (ADJUSTABLE) DELAY FOR FAN SHUT OFF. OS Beardsley Design Associates Architecture, Engineering, Landscape Architecture, D.P.C. ©Filename:no. revision description by date Project Number: Drawn By: Designed By: Reviewed By: WARNING Any alterations to this document not conforming to section 7307. New York State Education Law are strictly prohibited. MALONE 320 West Main Street Malone, NY 12953 518.483.1585 SYRACUSE 5789 Widewaters Pkwy Dewitt, NY 13214 315.472.6980 AUBURN 64 South Street Auburn, NY 13021 315.253.7301 7/18/2016 3:41:29 PMC:\Projects\MG_16063_V2016_naf.rvtMECHANICAL CORNELL UNIVERSITYM-101 07.20.2016 SYMBOLS, ABBREVIATIONS, SCHEDULES, DETAILS AND SCHEMATIC Renovations for the CCB Dean's Suite at Statler Hall130 Stalter Drive, Ithaca, New York 14853ITHACA, NEW YORKSubmission NAF 16063 PES NAF 2016 0'8'4'16'24' SCALE : 1/8" = 1'-0" SCALE: NONE 2 FOUR PIPE FAN COIL UNIT PIPING DETAIL SCALE: NONE 1 RADIUS ELBOW DETAIL EXISTING FAN COIL UNIT SCHEDULE (FOR REFERENCE ONLY) EXISTING LOCATION REVISED LOCATION CFM COOLING COIL (45°F EWT) HEATING COIL (160°F EWT) ELECTRICAL DATA DESIGN BASIS NOTES SENSE MBH TOTAL MBH EAT (DB/WB) GPM PD MBH EAT (°F) GPM LAT (°F) VOLT PH WATTS OFFICE 174 TURNED OVER TO OWNER - - - - - - - - - - - - - - - OFFICE 174A AD OFFICE 174A 400 5.9 5.9 74/62 1.0 2.1 12.3 65 1.2 93.5 277 1 130 CARRIER 42VB4 1 COPY 174C TURNED OVER TO OWNER - - - - - - - - - - - - - - - OFFICE 174D DEAN'S OFFICE 174C 400 5.9 5.9 74/62 1.0 2.1 12.3 65 1.2 93.5 277 1 130 CARRIER 42VB4 1 OFFICE 174E OPEN OFFICE 174 300 4.1 4.7 74/67 0.78 1.8 7.2 75 0.5 96.8 277 1 105 CARRIER 42VB3 1 OFFICE 174F OPEN OFFICE 174 300 4.1 4.7 74/67 0.78 1.8 7.2 75 0.5 96.8 277 1 105 CARRIER 42VB3 1 OFFICE 174G DEAN'S OFFICE 174D 300 4.1 4.7 74/67 0.78 1.8 7.2 75 0.5 96.8 277 1 105 CARRIER 42VB3 1 OFFICE 174H MEETING ROOM 174B 600 8.4 9.3 74/65 1.5 1.3 13.9 75 1.0 96 277 1 255 CARRIER 42VB5 1 WAITING 176 WAITING 176 800 8.2 10.3 74/63 1.7 3.4 16.5 75 1.0 93.7 277 1 260 CARRIER 42VB6 1 DIFFUSER AND REGISTERS SCHEDULE TYPE DESCRIPTION MAX NC MATERIAL FINISH DESIGN BASIS NOTES R1 PERFORATED RETURN DIFFUSER 15 STEEL BAKED ENAMEL WHITE TITUS PAR 1 NOTES: 1. REFER TO DRAWINGS FOR LOCATIONS, NECK SIZE, AND CFM. EXHAUST FAN SCHEDULE (EF) UNIT LOCATION SERVICE CFM ESP (IN WG) DRIVE TYPE FAN TYPE FAN RPM MAX SONE LEVEL MOTOR DATA DEISGN BASIS NOTESRPM VOLT PH HP (WATTS) EF-1 OPEN OFFICE 174 DEAN'S OFFICE 174C 100 0.25 DIRECT INLINE 984 3.8 1725 115 1 1/4 LOREN COOK 90SQN17DEC 1,2,3,4,5 NOTES: 1. PROVIDE FACTORY MOUNTED DISCONNECT. 2. PROVIDE INSULATED FAN HOUSING. 3. PROVIDE VIBRATION ISOLATORS. 4. PROVIDE THE MANUFACTURER'S STANDARD FLEXIBLE CONNECTORS. 5. PROVIDE WITH FACTORY MOUNTED FAN SPEED CONTROLLER. SCALE: NONE 6 INLINE EXHAUST FAN DETAIL EXISTING TERMINAL UNIT SCHEDULE (FOR REFERENCE ONLY) UNIT MIN MAX CFM RANGE EXISTING CFM REVISED CFM APPROXIMATE UNIT SIZE (IN)INLET SIZE MIN INLET SP NC RATING DEISGN BASIS NOTESL W H CAV-1 0/300 200 200 18 12 8 5"ø 1.0 25 TITUS ESV-3100 1 VAV-2 300/450 300 300 18 12 8 6"ø 1.0 21 TITUS ESV-3100 1 NOTES: 1. REBALANCE TERMINAL UNIT TO REVISED CFM. NOTE: 1. FOR INFORMATIONAL PURPOSES ONLY. SCALE: NONE 3 FAN COIL UNIT CONTROL SCHEMATIC (FOR REFERENCE ONLY) SCALE: NONE 5 EXHAUST FAN CONTROL SCHEMATIC NOTE: 1. FAN COIL UNIT IS EXISTING TO REMAIN. VERIFY THAT FAN COIL UNIT CONTROL SYSTEM IS OPERATIONAL AND FUNCTIONS PROPERLY PER DETAIL 3 ON DRAWING M-101 PRIOR TO PROJECT COMPLETION. K J H G 25 26 27 E8 E 28 T T T TT T T T11 1 1 1 2 2 1 1 2 1 1 1 EX 8x6 SAEX 8x6 SA EX 12x8 SA EX CAV-1 4 5 3 3 EXISTING FCU TO REMAIN (TYP OF 4) EX. 12x8 EA TO EX. EF EX 22x8 SA EX. 8x6 SA EX. 8x8 SA EX. 8x6 RA (TYP OF 2) EX. 6x6 SA EX. 8x8 SA EX. 6x6 SA EX. VAV-2 EX. 8x6 SA EX. 6x6 SA EX. 8x8 SA EX. 12x8 SA EX CAV-1 EX. 14x8 SA EX. 12x28 SA UP EX. 10x16 SA DN EX. 10x20 RA UP EX. 10x16 RA DN EX. CAV-1 6 6 6 K J H G 25 26 27 E8 E 28 TT T T EXISTING FAN COIL UNIT (TYP OF 4) 6"ø SA EX100 6"ø R1100 22x22 22x8 EA 12x12 EA 12x12 EA W/WWM EX. 8x6 SA EX. 8x6 SA 6"ø SA EX. 12x8 SA EX. CAV-1 EX100 6"ø EX100 22x22 EX.12x8 EA TO EX. EF EX. 22x8 EA 22x8 EA EX. 22x8 SA EX. 10x6 SA EX100 8"ø (TYP OF 2) EX200 22x22 EF-1 EX100 EX50 22x22 6"ø (TYP OF 2) 6"ø SA (TYP OF 2) WAITING 176 A.D. OFF. 174A MEETING RM. 174B DEAN'S OFF. 174C OPEN OFFICE 174 DEAN'S OFF. 174D 1 1 1 1 1 1 6"ø SA EX50 6"ø 1 EX150 22x22 1 EX150 8"ø 1 3 3 3 2 EX50 22x22 T 3 22x8 SA 22x8 RA 22x8 RA W/WWM 1 EX. VAV-2 EX. CAV-1 K J H G 25 26 27 E8 E 28 DEAN'S OFF. 174C DEAN'S OFF. 174D OPEN OFFICE 174 MEETING RM. 174B A.D. OFF. 174A WAITING 176 1/2" CW DROP WITHIN WALL CAVITY TO ICE MAKER OUTLET BOX 1/2" CW EX. CW32 1 4 5 Beardsley Design Associates Architecture, Engineering, Landscape Architecture, D.P.C. ©Filename:no. revision description by date Project Number: Drawn By: Designed By: Reviewed By: WARNING Any alterations to this document not conforming to section 7307. New York State Education Law are strictly prohibited. MALONE 320 West Main Street Malone, NY 12953 518.483.1585 SYRACUSE 5789 Widewaters Pkwy Dewitt, NY 13214 315.472.6980 AUBURN 64 South Street Auburn, NY 13021 315.253.7301 7/18/2016 3:41:29 PMC:\Projects\MG_16063_V2016_naf.rvtMECHANICAL CORNELL UNIVERSITYM-102 07.20.2016 FIRST FLOOR PLUMBING AND MECHANICAL PLANSRenovations for the CCB Dean's Suite at Statler Hall130 Stalter Drive, Ithaca, New York 14853ITHACA, NEW YORKSubmission NAF 16063 PES NAF 2016 DEMOLITION KEYED NOTES REMOVE EXISTING CEILING DIFFUSER/GRILLE DURING CEILING DEMOLITION, CLEAN AND PREPARE TO REINSTALL INTO NEW CEILING. REFER TO PLAN B ON DRAWING M-102 FOR DIFFUSER/GRILLE LOCATIONS. REMOVE EXISTING CEILING DIFFUSER AND TURN OVER TO OWNER. CAP DUCT RUNOUT WITH SHEET METAL AND SEAL AIRTIGHT. REMOVE EXISTING FAN COIL UNIT AND TURN OVER TO OWNER. CUT AND CAP HOT AND CHILLED WATER PIPING TO FAN COIL UNIT BELOW FLOOR AND PATCH FLOOR TO MATCH EXISTING CONDITIONS. REMOVE EXISTING FAN COIL UNIT AND STORE FOR ALTERATION WORK. CUT AND CAP HOT AND CHILLED WATER PIPING TO FAN COIL UNIT BELOW FLOOR AND PATCH FLOOR TO MATCH EXISTING CONDITIONS. REMOVE EXISTING CAV-1 AND DISCONNECT HOT WATER PIPING TO IT. CAP HOT WATER PIPING TO UNIT. TURN CAV-1 OVER TO OWNER. REMOVE AND STORE THERMOSTAT FOR INSTALLATION IN NEW PARTITION. 1 2 3 4 5 6 ALTERATION KEYED NOTES REINSTALL EXISTING DIFFUSER/GRILLE IN NEW CEILING. INSTALL EXISTING FAN COIL UNIT REMOVED FROM OFFICE 174H. PROVIDE 3/4" HOT WATER/CHILLED WATER PIPING. CONNECT RELOCATED FAN COIL UNIT TO EXISTING HOT WATER/CHILLED WATER MAIN IN CEILING BELOW. ROUTE CONDENSATE TO NEAREST EXISTING CONDENSATE DRAIN LINE MAIN IN CEILING SPACE BELOW. FIELD VERIFY EXACT LOCATION OF PIPING IN SPACE BELOW. INSTALL EXISTING THERMOSTAT AND CONNECT TO EXISTING FAN COIL UNITS. VERIFY PROPER OPERATION OF UNIT. GENERAL NOTES CHILLED WATER AND HOT WATER PIPING MAINS ARE LOCATED BELOW FIRST FLOOR SLAB. CONTRACTOR IS RESPONSIBLE TO REPLACE ANY CEILING FINISHES DAMAGED DURING INSTALLATION OF PIPING. FAN COIL UNITS ARE FULLY FUNCTIONAL AND OPERATIONAL. CONTRACTOR RESPONSIBLE TO ENSURE FAN COIL UNITS ARE FULLY FUNCTIONAL AND OPERATIONAL UPON COMPLETION OF WORK. CONTRACTOR RESPONSIBLE TO REPLACE ANY FAN COIL UNIT COVERS DAMAGED DURING REMOVAL AND/OR INSTALLATION. CONTRACTOR TO TURN OVER TO OWNER UNUSED EQUIPMENT AND/OR CONTROLS NOT USED. 1 2 3 1. 2. 3. 4. SCALE: 1/8" = 1'-0" A FIRST FLOOR MECHANICAL DEMOLITION PLAN SCALE: 1/8" = 1'-0" B FIRST FLOOR MECHANICAL ALTERATION PLAN 0'8'4'16'24' SCALE : 1/8" = 1'-0" PLAN NORTH PLAN NORTH SCALE: 1/8" = 1'-0" C FIRST FLOOR PLUMBING ALTERATION PLAN PLAN NORTH ALTERATION KEYED NOTES PROVIDE 1/2" NIBCO BRONZE BALL VALVE OR DESIGN EQUAL. PROVIDE COPPER PIPE, FITTINGS AND ACCESSORIES FOR COLD WATER SYSTEM ALTERATION WORK. PROVIDE ICE MAKER OUTLET BOX. PROVIDE SIOUX CHIEF 696 SERIES 1/4" ICE MAKER OUTLET BOX WITH SHOCK ARRESTOR OR DESIGN EQUAL. PROVIDE 1/4" FLEX TUBING FROM ICE MAKER BOX TO FUTURE COFFEE MAKER. PROVIDE 1/2" COLD WATER PIPING CONNECTION TO EXISTING DOMESTIC WATER PIPING LOCATED ABOVE CEILING LEVEL. 1 2 3 4 PLUMBING GENERAL NOTES PROVIDE PREPRINTED PIPE LABELS ON ALL DOMESTIC COLD WATER PIPING. FIELD VERIFY EXACT ROUTING TO ELIMINATE CONFLICTS WITH EXISTING CONDITIONS. 1. 2. 5 DJJDDDDDDJ JDDDDDDDDDDJ JDJFFFBJOSOSOS1OS1OS1OS1OS1OSOS1OSDDDDDDJ JDFFJDDDDFFDDDDDDDDMDFDF1234ABC56DREMOVE DEVICE, BOX ANDCONDUIT TO ACCESSIBLECEILING SPACE. BRANCHCIRCUITING REMAINS FORREUSE AT NEW LOCATION.1231234ABC56DA.D. OFF.174AOPEN OFFICE174A AAAAAA AAAA A A AAAAEMEMEMEMEMAAAAAAAA AAAWAITING176MEETING RM.174BDEAN'S OFF.174CDEAN'S OFF.174DDDD33abaaaaaaaabbbbbbbbbbbbDAAAAAAAAA A AAAAAA A AAaAaAaAEXISTING FIXTURE REMAINSBBBBCONNECT FIXTURES TOEXISTING CORRIDOR CONTROLSCONNECT LIGHTING FIXTURESTO EXISTING GENERALLIGHTING SWITCH ANDEXISTING OCCUPANCYSENSORaabbab11234ABC56DMOUNT DEVICESAT 60" AFF FORTV DISPLAYMOUNT DEVICESAT 60" AFF FORTV DISPLAYMICROWAVEOUTLETAT 66" AFF7GFCI6MODIFY/EXTEND EXISTINGBRANCH CIRCUIT TO NEW LOCATIONMOUNT DEVICESAT 60" AFF FORTV DISPLAY554443338822EF-11WAITING176A.D. OFF.174AMEETING RM.174BDEAN'S OFF.174COPEN OFFICE174DEAN'S OFF.174D88112CEILING MOUNT DEVICE42"AFF3342"AFF4REFRIGERATOR6POWERaLIGHTING3GRID T-BAR REPLACEMENT LIGHT FIXTURE; A - INDICATES FIXTURE TYPEa INDICATES SWITCH DESIGNATIONRECESSED MOUNT WALL WASH LIGHT FIXTUREUNIVERSAL MOUNT EXIT LIGHT; FILL INDICATES FACE, ARROWS INDICATEDIRECTION OF TRAVEL TO EXITSINGLE POLE SWITCH; "a" INDICATES SWITCH CONTROLS FIXTURE WITH THESAME DESIGNATION. MOUNT AT 3'- 6" AFF UNLESS NOTED OTHERWISESINGLE POLE SWITCH. MOUNT AT 3'- 6" AFF UNLESS NOTED OTHERWISETHREE-WAY SWITCH; MOUNT AT 3'- 6" AFF UNLESS NOTED OTHERWISEDUPLEX CONVENIENCE RECEPTACLE (NEMA 5-20R); MOUNT AT 1'- 6" AFFUNO; # INDICATES PANEL/CIRCUIT NUMBERDUPLEX RECEPTACLE, GROUND FAULT CIRCUIT INTERRUPTER TYPE; MOUNTAT 1'- 6" AFF UNLESS NOTED OTHERWISE; # INDICATES PANEL/CIRCUIT NUMBERGFCI##DOUBLE DUPLEX CONVENIENCE RECEPTACLE (NEMA 5-20R); MOUNT AT 1'-6" AFF UNLESS NOTED OTHERWISEJUNCTION OR PULL BOXMOTOR#JMABBREVIATIONSAFF- ABOVE FINISH FLOORAWG- AMERICAN WIRE GAUGEEMT- ELECTRIC METAL TUBINGEX- EXISTINGEHS- ENVIRONMENTAL, HEALTH AND SAFETYGND- GROUNDGRS- GALVANIZED RIGID STEELGWB- GYPSUM WALL BOARD (SHEET ROCK)JB- JUNCTION BOXMAX- MAXIMUMMIN - MINIMUMTYP- TYPICALUNO- UNLESS NOTED OTHERWISEFIRE ALARM NOTIFICATION APPLIANCE (AUDIO/VISUAL)PROVIDE DEVICE COMPATIBLE WITH EXISTING SYSTEM.FIRE ALARM NOTIFICATION APPLIANCE (VISUAL ONLY);PROVIDE DEVICE COMPATIBLE WITH EXISTING SYSTEMFFDDIMMER SWITCH; MOUNT AT 3'- 6" AFF UNLESS NOTED OTHERWISECOMMUNICATIONSWALL MOUNTED DATA OUTLET: MOUNT AT 1'-6" AFF UNLESS NOTEDOTHERWISE. COORDINATE LOCATIONS AND REQUIREMENTS WITH OWNER.PROVIDE 1" CONDUIT TO COMMUNICATIONS ROOM.CABLES AND TERMINATIONS ARE BY OWNER.DFIRE ALARMaAOS1CEILING MOUNTED OCCUPANCY SENSORWORK AREAELECTRIC ROOMCOMMUNICATIONS ROOMBeardsley Design Associates Architecture, Engineering, Landscape Architecture, D.P.C. ©Filename:no. revision description by dateProject Number:Drawn By:Designed By:Reviewed By:WARNINGAny alterations to this document notconforming to section 7307. New YorkState Education Law are strictly prohibited.MALONE320 West Main StreetMalone, NY 12953518.483.1585SYRACUSE5789 Widewaters PkwyDewitt, NY 13214315.472.6980AUBURN64 South StreetAuburn, NY 13021315.253.73012016-07-19 12:27:23C:\Projects\EG_16063_V2016_bwb.rvtELECTRICALCORNELL UNIVERSITYE-101JULY 20, 2016LIGHTING AND POWER PLANRenovations for the CCB Dean's Suite at Statler Hall130 Statler Drive, Ithaca, New York 14853SubmissionBWB16063-BWB20160'8'4'16'24'SCALE : 1/8" = 1'-0"SCALE: 1/8" = 1'-0"ALIGHTING AND POWER DEMOLITION PLANSCALE: 1/8" = 1'-0"BLIGHTING PLANSCALE: 1/8" = 1'-0"CPOWER PLAN1.CONNECT NEW LIGHTING FIXTURES TO EXISTING BRANCH CIRCUIT(S) SERVING AREA.2.CONNECT EMERGENCY LIGHTS AND EXIT SIGNS TO EXISTING BRANCH CIRCUIT AHEADOF ALL CONTROLSLIGHT FIXTURE SCHEDULETYPE DESCRIPTION MOUNTING LAMPS DRIVER DESIGN BASISAPPROVEDMANUFACTURERS REMARKSA CEILINGINTEGRATED WITHDIFFUSING LENSRECESSED LED - MIN 2000 LUMENS UNIVERSAL VOLTAGEDIMMINGJLC TECHTBSL-HW-4-24-D-A-WAPPROVED EQUALSARE ACCEPTABLEPROVIDE EMERGENCY DRIVERFOR FIXTURES SHOW WITH "EM"B LINEAR RECESSEDWALL WASHRECESSED LED - 1700 LUMENS UNIVERSAL VOLTAGEDIMMINGDAY-BRITEWLRN17L835-2-UNVAPPROVED EQUALSARE ACCEPTABLEPROVIDE ALL CEILING WORKNECESSARY FOR INSTALLATIONX LED ACRYLIC EXITSIGNCEILING LED WITH RED TEXT UNIVERSAL VOLTAGE COMPASS LIGHITNGCEL SERIESAPPROVED EQUALSARE ACCEPTABLEPROVIDE WITH TEST SWITCH PERCORNELL STANDARDS1.PROVIDE CIRCUITING AS SHOWN. CIRCUIT NUMBERS SHOWN ARE INTENDED TOIDENTIFY DEVICES CIRCUITED TOGETHER ONLY AND DO NOT NECESSARILYCORRESPOND TO ACTUAL POSITIONS IN A PANELBOARD. COORDINATE WITHDEMOLITION AND OWNER TO IDENTIFY PANEL LOCATIONS AND SPACE FORCIRCUITING INDICATED.2.UNLESS NOTED OTHERWISE, PROVIDE SURFACE RACEWAY FOR DEVICES ONEXISTING WALLS. FEED DEVICES FROM BELOW WHERE SURFACE RACEWAYIS REQUIRED.3.CONNECT FIRE ALARM NOTIFICATION APPLIANCES TO EXISTING NOTIFICATIONAPPLIANCE BRANCH CIRCUIT.POWER KEYED NOTES:CUT WALL TO MOUNT DEVICE AS REQUIRED. PATCH SURFACE TOMATCH EXISTING.CONNECT FAN COIL UNIT TO EXISTING CIRCUITING. MODIFY/EXTEND ASREQUIRED.MATCH EXISTING DEVICE MOUNTING HEIGHT ABOVE COUNTER.EXHAUST FAN. PROVIDE 2#12 AND 1#12 GND IN 3/4" CONDUIT. CONNECT TOFACTORY MOUNTED DISCONNECT. PROVIDE OCCUPANCY SENSOR ROOMCONTROL COORDINATE WITH MECHANICAL FOR REQUIREMENTS.11.PROVIDE TEMPORARY HEAT DETECTION PRIOR TO THE REMOVAL/RELOCATION OF SPRINKLERS.TEST DEVICES WITH EHS PRIOR TO ANY SPRINKLER SYSTEM WORK.2DEMOLITION KEYED NOTES:APPROXIMATE LOCATION OF FAN COIL UNIT. REMOVE BRANCH WIRINGAND RACEWAY BACK TO SOURCEAPPROXIMATE LOCATION OF FAN COIL UNIT. TAG EXISTING CIRCUITINGFOR REUSE.REMOVE FLOOR BOX. PATCH FLOOR TO MATCH EXISTING.12POWER NOTES:DEMOLITION NOTES:LIGHTING NOTES:3LIGHTING KEYED NOTES:PROVIDE 120V OCCUPANCY SENSOR FOR EXHAUST FAN. COORDINATEREQUIREMENTS WITH UNIT PROVIDED.1341.POWER AND LIGHTING CIRCUITS SHALL NOT BE INSTALLED IN THESAME CONDUIT.2.LIGHTING FIXTURES SHALL NOT BE USED AS RACEWAYS. ALL LIGHTFIXTURES SHALL BE CONNECTED TO A JUNCTION BOX WITH A LIGHTFIXTURE TAP THAT DOES NOT EXCEED 6' IN LENGTH.3.THE GROUND WIRES FOR THE LIGHTING AND POWER CIRCUITS SHALLBE BONDED TO ALL JUNCTION BOXES INSTALLED IN THE CONDUITSYSTEM.4.ALL LIGHT FIXTURES SHALL BE BONDED TO THE GROUND WIRE.5.ALL JUNCTION BOXES FOR POWER AND LIGHTING CONDUIT SYSTEMSLOCATED ABOVE CEILING SYSTEMS SHALL HAVE CIRCUIT DESIGNATIONSMARKED ON THE JUNCTION BOX COVER PLATES.6.PROVIDE TYPEWRITTEN PANEL SCHEDULE AT THE PANELBOARDS AFTER THEELECTRICAL WORK IS COMPLETED. INCLUDE ON PANEL SCHEDULEINFORMATION FOR EXISTING BRANCH CIRCUITS.7.UNLESS NOTED OTHERWISE, ALL RECEPTACLE BRANCH CIRCUITS SHALLCONSIST OF 2 #12 AND 1 #12 GND.8.ALL PENETRATIONS THROUGH FIRE/SMOKE BARRIERS SHALL BE FIRESTOPPEDIMMEDIATELY AFTER PENETRATION IS MADE. TEMPORARY FIRE STOPPING ISREQUIRED IF WORK IS NOT COMPLETE AT TIME OF PENETRATION.FIRESTOPPING MUST MEET RATING OF WALLS.9.REPAIR/PATCH TO MATCH ALL SURFACES (WALL, FLOORS, CEILINGS, ETC.)DISTURBED DUE TO THIS WORK. PAINT EXPOSED CONDUITS TO MATCHADJACENT SURFACES.10.COORDINATE FIRE ALARM SHUTDOWNS WITH OWNER.11.PROVIDE PULL STRING IN ALL EMPTY CONDUITS FOR FUTURE USE..GENERAL NOTESPLANNORTHSCALE: 1" = 50'-0"DKEY PLAN0'25'50'100'150'SCALE : 1" = 50'-0"