HomeMy WebLinkAbout143112 Clara DicksonCornell Universit v Clara Dickson Hall -Waste & Storm Line Replacement December 31, 2014 -Construction Documents SYMBOLS LIST & ABBREVIATIONS SYMBOLS DESCRIPTION ABBR. — -- — — EXISTING WORK TO BE REMOVED (BOLD DASHED LINE) EXISTING WORK TO REMAIN (LIGHT SOLID LINE) NEW WORK (BOLD SOLID LINE) PATCH CONCRETE FLOOR ABOVE GROUND SERVICE WEIGHT NO—HUB CAST IRON COLD WATER CW BELOW GROUND (OUTDOORS) PVC SDR 35 BELL & SPIGOT CONFORMING TO ASTM D3034 WITH STIFFNESS VALUE OF 46 HOT WATER HW BELOW GROUND (INDOORS) CERAMIC TILE HOT WATER CIRCULATING LINE HWC — SAN SANITARY OR WASTE PIPING SAN — — V — — VENT PIPING V STORM PIPING ST — ST 0 CONNECT TO EXISTING iirl REMOVE TO THIS POINT PIPE DROP OR DOWN PIPE RISE OR UP CARPET TILE 0 TOP CONNECTION BOTTOM CONNECTION (I) VINYL TILE CAP OR PLUG E CLEANOUT, WALL CLEANOUT CO, WCO I P—TRAP DO O (E) FCO EXISTING FLOOR CLEANOUT EXISTING TO REMAIN EX, EXIST. (E) FLOOR DRAIN FLD, FD ® 0 PLUMBING CONTRACTOR PC GENERAL CONTRACTOR GC ASBESTOS CONTAINING MATERIAL ACM SHOWER SH WATER CLOSET WC LAVATORY LAV KITCHENETTE SINK KS DRINKING FOUNTAIN DF GALLONS PER MINUTE GPM CAST IRON PIPE CI BOTTOM OF PIPE BOP ABOVE FINISHED FLOOR AFF FINISHED FLOOR ELEVATION FFE 11,5 RISER NUMBER (EXAMPLE 15) SS (2636A) NUMBER IN PARENTHESES INDICATES ROOM SERVED BY STACK HATCHING LEGEND HATCH PATTERN DESCRIPTION r.................:1 I.••••'•••'•'•'•' ' ' ' '•'•'•••••'I SAWCUT CONCRETE FLOOR SLAB, REMOVE CONCRETE JOINTS PATCH CONCRETE FLOOR ABOVE GROUND SERVICE WEIGHT NO—HUB CAST IRON NO HUB FITTINGS CHARLOTTE HEAVY DUTY 4 BAND S/S CLAMP W/NEOPRENE GASKET 80 IN LB TYPE BELOW GROUND (OUTDOORS) PVC SDR 35 BELL & SPIGOT CONFORMING TO ASTM D3034 WITH STIFFNESS VALUE OF 46 COMPATIBLE WITH PIPE, PUSH—ON TYPE GASKETS CONFORMING TO ASTM F477 BELOW GROUND (INDOORS) CERAMIC TILE PVC FITTINGS CONFORMING TO ASTM D2665 PURPLE PRIMER & SOLVENT CEMENT FOR PVC PIPE CONFORMING TO ASTM 02564 CARPET TILE VINYL TILE VINYL SHEET (LINOLEUM) GRADE CLEANOUT. SEE DETAIL FINISHED GRADE-. BRONZE PLUG— C 4" SOIL PIPE GASKET - 4" TAPPED BOSS --.y FOR BRASS PLUG 4" CAST IRON SOIL PIPE CLEANOUT STACK PLUMBING WORK TO BE PERFORMED BY CITY OF ITHACA LICENSED PLUMBER & INSPECTED BY THE CITY OF ITHACA. PULL PERMIT TO INSTALL DRAIN, TRAP, & CLEANOUT. FLOW 8" OR 6" REFER TO PLANS 6"0 1: FRESH AIR INLET IN LAWN OR PLANTING AREA 4" CAST IRON SOIL PIPE (-6" SANITARY SEWER `---�� "lima Chi i•ma Wari Cooperative 'jd House Akwekon Robe f u cel HRS Jrom Ho+ pha nrna :h• Pi DeltalPs Dellta... Delta Prospect of Delta Whit .:: Wait WAIT AVENUE alio ina es Hall curs (radu it ssi•, (Latinoti RAWLINGS GREEN Risle Hall Caro ente CRADIT FARM DRIVE Fu -rtesn Obs ' ; = o 1< ,cutc Plan _RsI TY 5 ixY •l i�,ja� Tjaden Slbiey all Hall SITE Martha Va' enssel arage PA LOCATION PLAN NOT TO SCALE PIPING SCHEDULE SERVICE LOCATION PIPING FITTINGS JOINTS STORM, SANITARY & VENT ABOVE GROUND SERVICE WEIGHT NO—HUB CAST IRON NO HUB FITTINGS CHARLOTTE HEAVY DUTY 4 BAND S/S CLAMP W/NEOPRENE GASKET 80 IN LB TYPE BELOW GROUND (OUTDOORS) PVC SDR 35 BELL & SPIGOT CONFORMING TO ASTM D3034 WITH STIFFNESS VALUE OF 46 COMPATIBLE WITH PIPE, PUSH—ON TYPE GASKETS CONFORMING TO ASTM F477 BELOW GROUND (INDOORS) SCHEDULE 40 PVC DWV CONFORMING TO ASTM D1785 & D2665 PVC FITTINGS CONFORMING TO ASTM D2665 PURPLE PRIMER & SOLVENT CEMENT FOR PVC PIPE CONFORMING TO ASTM 02564 FLOOR DRAIN SCHEDULE TAG DESCRIPTION MAKE & MODEL LOCATION NOTES FD -1 GENERAL SERVICE FLOOR DRAIN, DUCO CAST IRON BODY AND GRATE, SEDIMENT BUCKET. PROVIDE P—TRAP. JAY R SMITH MODEL 2210 SUMP BASINS EXTENSION TYPE CLEANOUT, DUCO CAST IRON, W/RAISED HEAD CLOSURE PLUG, SERVICE WEIGHT. 6" CAST IRON SINGLE VENTED BUILDING TRAP OUTDOOR TYPICAL BUILDING TRAP WITH FRESH AIR INLET DETAIL 3 NOT TO SCALE P001 CLEANOUT SCHEDULE TYPE DESCRIPTION MAKE & MODEL NOTES FCO CAST IRON FLOOR CLEANOUT WITH ROUND ADJUSTABLE SCORIATED SECURED NICKEL BRONZE TOP, TAPER THREAD AND BRONZE PLUG. JAY R SMITH MODEL 4033E OR EQUAL BY ZURN PROVIDE CARPET CLAMPING FLANGE IN CARPET AREAS CO EXTENSION TYPE CLEANOUT, DUCO CAST IRON, W/RAISED HEAD CLOSURE PLUG, SERVICE WEIGHT. JAY R SMITH SERIES 4280 OR EQUAL BY ZURN WCO WALL CLEANOUT — CAST IRON SPIGOT FERRULE WITH BRONZE TAPER THREAD PLUG, STAINLESS STEEL ROUND COVER AND SCREW JAY R SMITH MODEL 4422C OR EQUAL BY ZURN GRADE CAST IRON EXTENSION LENGTH VARIES, SEE PLANS AND ELEVATIONS --�` 4" 6" LAWN d/d,-d-d Ate-- 6" CONCRETE PAD CAST IRON CLEANOUT WITH BRONZE PLUG, JAY R. SMITH MODEL NO. 4281 ROUND, FLANGED HOUSING WITH HEAVY DUTY CAST IRON COVER, JAY R. SMITH SERIES 4250 CAST IRON PIPE OUTDOOR GRADE CLEANOUT DETAIL NOT TO SCALE ADJUSTABLE TOP AND FRAME CARPET 5" DRAWING LIST CONTRACT DRAWINGS: P001 P100 P101 P102 P200 P201 P202 TITLE SHEET, SYMBOLS, SCHEDULES, NOTES & DETAILS UNDERFLOOR PIPING REMOVAL PLAN - NORTH UNDERFLOOR PIPING REPLACEMENT PLAN - NORTH FINISHES REPLACEMENT PLAN - NORTH UNDERFLOOR PIPING REMOVAL PLAN - SOUTH UNDERFLOOR PIPING REPLACEMENT PLAN - SOUTH FINISHES REPLACEMENT PLAN - SOUTH EXISTING CONDITION DRAWINGS - FOR INFORMATION ONLY: P301 P302 P303 P304 P305 P306 EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING 4000 PSI READY MIX CONCRETE, ASSUME 5" THICKNESS FIRST FLOOR PLUMBING PLAN - SOUTH FIRST FLOOR PLUMBING PLAN - NORTH SECOND FLOOR PLUMBING PLAN - SOUTH SECOND FLOOR PLUMBING PLAN - NORTH THIRD FLOOR PLUMBING PLAN - SOUTH THIRD FLOOR PLUMBING PLAN - NORTH #4 DOWELS —12" LONG 6" EMBEDMENT, 3' OC ON EACH SIDE IF OVER 4 FEET DEEP LAY BACK OR \\ \\\/ i \/ STANDARDAffill U 1926,NTS OF OSHA CONSTRUCTION, AND \/, ././. ,. ,�%i�,. , A� ,A ,;�%%r��%i�\%�\%i /A% LOCAL LAWS. # SHORE TRENCH IN ACCORDANCE SANITARY OR STORM LINE. SEE PLAN FOR SIZE RUN OF CRUSHED LIMESTONE COMPACTED IN 12" LIFTS STONE DUST 4" MINIMUM PIPE BEDDING DEPTH VARIES SEE PLAN TYPICAL BACKFILL & FLOOR PATCH DETAIL NOT TO SCALE NOT TO SCALE z 4• 4 . FLOOR SLAB FLOOR CLEANOUT DETAIL NOT TO SCALE GROUND FLOOR P001 P001 EXISTING CAST IRON ABOVE FLOOR CONNECT TO EXISTING 0 PROVIDE CLEANOUT AT BASE OF EACH RISER 6" MIN. PVC ABOVE FLOOR A r PVC BELOW FLOOR PHASE: YEAR1&2 YEAR 1&2 YEAR1&2 YEAR1&2 YEAR 2 YEAR 2 YEAR 2 // // // // // // // // //. PLUMBING NOTES 1. ALL WORK SHALL CONFORM TO CORNELL UNIVERSITY DESIGN AND CONSTRUCTION STANDARDS FOR QUALITY, MATERIALS AND WORKMANSHIP. 2. ALL WORK SHALL CONFORM TO THE EXISTING BUILDING CODE OF NEW YORK STATE (EBCNYS). ALL PLUMBING WORK IN THE PROJECT AREA SHALL CONFORM TO PLUMBING CODE OF NEW YORK STATE (PCNYS), THE FIRE CODE OF NEW YORK STATE (FCNYS), AND THE ENERGY CONSERVATION CONSTRUCTION CODE OF NEW YORK STATE (ECCNYS). THESE DRAWINGS WERE PREPARED UNDER THE 2010 VERSIONS OF THE AFOREMENTIONED CODES. CONFIRM WITH THE CITY OF ITHACA THE PREVAILING CODE VERSION AT THE TIME OF PERMIT ISSUE AND COMPLY WITH THE PROVISION OF THE CURRENTLY APPLICABLE CODE AT THE TIME OF PERMIT ISSUE. 3. ALL WORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE REQUIREMENTS OF THE OCCUPATIONAL HEALTH AND SAFETY ACT (OSHA) AS AMENDED AND THE REQUIREMENTS OF THE NEW YORK STATE DEPARTMENT OF LABOR. 4. CONFORM TO ALL UTILITY COMPANY RULES AND REGULATIONS. 5. BUILDING PERMIT: CONTRACTOR SHALL OBTAIN A BUILDING PERMIT BEFORE STARTING WORK. CONTRACTOR SHALL PAY ALL PERMIT EXPENSES. 6. THE PROJECT OCCURS WITHIN THE CITY OF ITHACA. CONTRACTOR SHALL HAVE A VALID MASTER PLUMBER LICENSE AND SHALL PROVIDE A CITY OF ITHACA PLUMBING PERMIT, INSPECTION AND CERTIFICATE OF COMPLETION. THE CONTRACTOR SHALL PAY ALL FEES. 7. THIS PROJECT INCLUDES SAW CUTTING SLAB, HAND EXCAVATION AROUND PIPE, REMOVAL AND REPLACEMENT OF UNDERFLOOR PIPE AND RESTORATION OF SURROUNDING CONSTRUCTION AND FINISHES. REFER TO DRAWINGS AND SPECIFICATION FOR ADDITIONAL SCOPE OF WORK. 8. PROVIDE DETAILED SUBMITTALS FOR ALL MATERIALS AND EQUIPMENT PROVIDED UNDER THIS PROJECT. 9. PROVIDE OPERATION AND MAINTENANCE INFORMATION FOR ALL MATERIALS, EQUIPMENT AND SYSTEM PROVIDED UNDER THIS PROJECT. SEE SPECIFICATIONS. 10. CLARA DICKSON HALL MAY BE OCCUPIED BY STAFF AND SUMMER PROGRAMS IN THE BUILDING DURING THE CONSTRUCTION PERIOD. WATER SERVICES WILL BE REQUIRED BY THE STAFF AND CONTRACTORS. PROVIDE TEMPORARY SERVICES AS REQUIRED. COORDINATE SHUTDOWN OF ONE SIDE OF THE BUILDING AT A TIME. 11. PROVIDE SIGNED, DATED, CONTRACTOR AS—BUILT DRAWINGS FOR ALL WORK PROVIDED UNDER THIS PROJECT. MAINTAIN ONE SET OF CONSTRUCTION DRAWINGS DENOTING ANY FIELD CHANGES WHICH ARE MADE AS THE WORK OF THE PROJECT PROGRESSES. KEEP THESE UPDATED. ENGINEER SHALL BE PERMITTED TO BORROW, PHOTOCOPY AND RETURN THESE DRAWINGS AT INTERVALS THROUGH THE PROJECT. 12. NO WORK OF ASBESTOS OR HAZARDOUS MATERIAL ABATEMENT OR REMOVAL IS INCLUDED UNDER THIS CONTRACT. CONTACT OWNER IF SUSPECTED ASBESTOS MATERIAL ARE ENCOUNTERED. 13. INSPECTION: NOTIFY CITY OF ITHACA PLUMBING CODE COMPLIANCE OFFICER AND PETERSON GUADAGNOLO ENGINEERS A MINIMUM OF 48 HOURS PRIOR TO TESTING PLUMBING LINES. CONTINUOUS PLASTIC WARNING TAPE LOCATED 12" BELOW GRADE AND ON TOP OF 12" LAYER ABOVE SEWER. TAPE SHALL BE 6" WIDE & LABELED "SANITARY SEWER". RE—SEED LAWNS d d �d d14• COMPACTED SELECT NATIVE MATERIAL LAY BACK OR SHORE TRENCH IN ACCORDANCE WITH REQUIREMENTS OF OSHA STANDARD 1926, CONSTRUCTION, AND LOCAL LAWS. EPDXY GROUT z � PVC -CAST IRON PIPE CONNECTION DETAIL NOT TO SCALE PIPE SLEEVE DEPTH VARIES / CRUSHED STONE ,,/i,, ABOVE PIPE COMPACT 0 � TYPICAL SANITARY ARIES (TYP) SEWER LINE TRENCH DETAIL - UNDER GRASS NOT TO SCALE STEEL SEALING AND ANCHORING COLLAR WELDED TO SLEEVE CENTER PIPE IN SLEEVE SEAL SLEEVE WITH TIGHTLY PACKED FIBERGLASS OR 'LINK—SEAL' Or AV ABM/ AMP' AMMEMEMEMMEOM SEAL WATERTIGHT WITH MASTIC OR ASPHALT /////////////Ammar ///////////MEM I Pir STANDARD WEIGHT STEEL PIPE SLEEVE NON—SHRINK GROUT OR EPDXY GROUT NOTE: PIPE SLEEVE FOR EXTERIOR WALL ABOVE OR BELOW GRADE CORE DRILL HOLE AS REQUIRED ESCUTCHEON (NOT REQUIRED IN UNFINISHED SPACES) INTERIOR WALL SURFACE EXTERIOR WALL PIPE SLEEVE DETAIL. NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW. "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION IT IS A VIOLATION OF THE 00 — a 0 ci e 3 i (� W 0• e.L �c 00 av a) C } 2 m V) ra W tp IL. 1ID tI r�0 31a • IPem, �� GG W 4, 0 Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON 0 N co r d z EM4 P.T.4 z rig a2.1 F. ck$ Faia.7 Ooh ra3414 Project/Sheet Title TITLE Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P001 YEAR1&2 Sheet No. 1 of 7 N:\915706\Drawings\P100 YR 1.dwg, 12/31/2014 9:19:48 AM, N62 (0119. 11639 SINGLE ROOM 2" VENT UP 3" UP TO FD 3" SAN TO WC UP 4" UP 0 FCO 116371 BATHROOM 2" SAN UP TO LAVS 46 SINGLE ROOM 3" SAN UP TO WC SINGLE ROOM 1643A CLOSET B.O.P. 25"± BELOW SLAB REMOVE PORTION OF WIRE LATH AND PLASTER WALL 2" SAN U TO SH (TYP 2 HT BULB ROOM ■' REMOVE C.I. SAN MIN. 6" ABOVE FLOOR SLAB. (TYP) SINGLE ROOM 4" UP (2631 B) CLOSET SINGLE ROOM SINGLE ROOM (2629B) CORRIDOR - 16310 CLOSET SINGLE SINGLE ROOM ROOM REMOVE PORTION OF WIRE LATH AND PLASTER WALL 1629A CLOSET CLOSET 11625 SINGLE ROOM " UP (2625B; CLOSET SINGLE ROOM 16230 CLOSET 116211 SINGLE ROOM CLOSET EXISTING HUB DRAIN TO REMAIN 110641 SINK ROOM B.O.P. 1V)± BELOW SLAB (E) FC0 1 10631 DATA TC MECHANICAL STAIR 1648B BIKE STORAGE 16221 MCLLU DEN EXIST NG PIPE —TO REMAIN 4" UP 1 (2630B) SAWCUT FLOOR REFER TO REMOVAL NOTE 1 (TYP.) STORAGE STORAGE DOUBLE ROOM 11009 STAIR KITCHEN SINGLE ROOM SINGLE ROOM SINGLE ROOM 11669 SINGLE ROOM 11667 SINGLE ROOM 4" UP (2670) _ SINGLE SINGLE ROOM ROOM REMOVE PORTION OF WIRE LATH AND PLASTER WALL. SINGLE ROOM 11659 SINGLE ROOM EXISTING PIPE STORAGE TO REMAIN 11647 MAINTENANCE 1675A1 CLOSET 1673A1 CLOSET 671A CLOSET 1669A CLOSET CLOSET CLOSET EXISTING PIPE TO REMAIN 116151 RECREATION ROOM 16741 DOUBLE ROOM 1-1/2" SAN UP TO LAV (1679) Q3" UP (167 i MS) 4" UP (_679)WC 3" SAN UP TO WC (TYP 3) 1-1/2" SAN UP TO LAVS (1679) EMOVE UTILITY SINK, STORE FOR REINSTALLATION II JIVttNVC REMOVE PORTION OF WIRE LATH AND PLASTER WALL. 2" VENT UP (TO REI 4IN) CORRIDOR 116621 STORAGE .4" SAN UP t..�...... TO WC (2670) •:1.....� EXIST B.O.P. 31" ± BELOW SLAB SUMP PIT WITH PUMP 116501 MECHANICAL ROOM 4 (2636A) EXISTING 2"PUMP DISCHARGE UP (TO REMAIN) 3" UP TO FD (TO REMAIN) STORAGE REMOVE PORTION OF r........ WIRE LATH AND I....1:::: ManPLASTER WALL. 11(}27= K:. EXIST. STORM MANHOLE EXIST. SANITARY MANHOLE —Z F.A.I. • REMOVE HOUSE TRAP, CLEANOUT & FRESH AIR INLET LOCKER ROOM CAREFULLY REMOVE 11LE SHOWER FLOORS. REPAIR SCHLUTER WATERPROOF SYSTEM. COORDINATE WORK W/EXISTING ELECTRIC/DATA OUTLETS REMOVE CERAMIC TILE WALL FOR ACCESS TO WATER PIPING :.:� EXIST B.O.P. 45.5" ± BELOW 15371 BREAK fZ813M-- 6 SIDE (NORTH) 5 SIDE (SOUTH) r 17- EMOVE DRAINS, AND PIPING SERVING SHOWERS IN ROOM 1538 SAWCUT FLOOR REFER TO REMOVAL NOTE 1 (TYP.) YEAR 1 WORK PROJECT ROOM 2"ST UP CORRIDOR 11534 MECHANICAL ROOM SERVICE ELEVATOR 1000F HYDRAULIC ELEVATOR 11028 RECEIVING 5"ST RISER RISER j0280 YEAR 2 WORK 6 SIDE (NORTH) 5 SIDE (SOUTH) REMOVE AND REPLACE FLOOR DRAIN AT BOTTOM OF SUMP EXISTING SUMP TO REMAIN UNDERFLOOR PIPING. REMOVAL PLAN - NORTH SCALE: 1/8" = 1'-0" 1 /8" 1 0 1 5 7 9 11 13 15 l 1■ REMOVAL NOTES: 1. IN AREAS SHOWN, SAWCUT FLOOR, REMOVE CONCRETE SLAB AND HAND EXCAVATE AROUND SANITARY LINE. REMOVE PIPE AS INDICATED ON DRAWINGS. REMOVE RISERS MINIMUM OF 6" ABOVE FLOOR SLAB. 2. PIPING SHOWN ON DRAWINGS HAS BEEN DEVELOPED FROM PROJECT RECORD DRAWINGS AND FIELD VERIFIED TO THE GREATEST EXTENT POSSIBLE. CONTRACTOR SHALL VERIFY IN FIELD ALL LOCATIONS PRIOR TO REMOVAL OF WALLS AND SAW CUTTING OF FLOOR. 3. REMOVE, STORE AND REINSTALL PLUMBING FIXTURES AS NOTED ON DRAWINGS. 4. CONTRACTOR SHALL REMOVE GWB, PLASTER AND CONCRETE BLOCK WALLS AS SHOWN ON DRAWINGS TO FACILITATE PIPE REPLACEMENT. 5. CONTRACTORS SHALL BE RESPONSIBLE TO PROTECT ABOVE—GROUND PIPING SYSTEMS AND SURROUNDING BUILDING SURFACES I.E. FLOORS, WALLS, ETC. CONTRACTOR SHALL REPLACE ANY PIPE INSULATION, ABOVE GROUND PIPE, AND REPAIR ANY SURFACES DAMAGED IN THE PERFORMANCE OF THIS PROJECT. 6 SIDE NORTH 5 SIDE SOUTH KEY PLAN NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE O 0 Cco ic AI 5 • c 0 W C 0) o Era �(0) -c o 0.0 8 1n a) CTIC c 0. 0-3 ani E a) 4.0 0 0 Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Revision d z r:4 w Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P100 YEAR1&2 Sheet No. 2 of 7 N:\915706\Drawings\P101 YR 1 UF 6 SIDE.dwg, 12/31/2014 9:30:23 AM, N62 PLUMBING FIXTURE SCHEDULE PF # _ FIXTURE ABBREV SYMBOL = HOT COLD WASTE VENT REMARKS MOUNTING HEIGHT MAKE & MODEL US -1 UTILITY SINK US 1/2" 1/2" 3" 1 1/2" UTILITY SINK— REINSTALL EXISTING SINK. PROVIDE P—TRAP AND FAUCET. FAUCET— BRASS CONSTRUCTION, 8" CENTERS, BRASS VALVE BODIES, VACUUM BREAKER, INTEGRAL SUPPLY & CHECK VALVES, WALL BRACE, PAIL HOOK, HOSE END SPOUT. METAL LEVER HANDLES, AMERICAN STANDARD 8354.112. P—TRAP— TRAP WITH STRAINER, WALL OUTLET. THREADED 3" INSIDE FOR CAST IRON SERVICE SINK. AMERICAN STANDARD 7798.030 MS -1 MOP SINK MS 1/2" 1/2" 3" 1 1/2" FLOOR MOUNTED RECEPTACLE— 24"x24"x10"H MOLDED STONE, FIAT MODEL MSB -2424 FAUCET— BRASS CONSTRUCTION, 8" CENTERS, BRASS VALVE BODIES, VACUUM BREAKER, INTEGRAL SUPPLY & CHECK VALVES, WALL BRACE, PAIL HOOK, HOSE END SPOUT. METAL LEVER HANDLES, AMERICAN STANDARD 8354.112. PROVIDE BLOCKING FOR FAUCET MOUNTING. ACCESSORIES— PROVIDE STAINLESS STEEL WALL GUARDS, CAPS ON ALL CURBS, MOP HANGER, HOSE & HOSE BRACKET, INTEGRAL SS CAST DRAIN BODY AND SS COMBINATION DOME STRAINER AND LINT BASKET O SINGLE ROOM 1641 SINGLE ROOM PROVIDE FCO (TYP.) REFER TO DETAIL 3" SAN UP TO WC 2" VENT UPS 3" UP TO FD REPLACED SUMMER 2012 3" SAN TO WC UP 4" UP 0 FCO BATHROOM 2" SAN UP TO LAVS 2" SAN U TO SH (TYP 2)7 (16351 SINGLE ROOM 116331 SINGLE ROOM 116291 SINGLE ROOM SINGLE ROOM 116251 SINGLE ROOM 116231 SINGLE ROOM SINGLE ROOM 1 10631 DATA 162101 CLOSET 116431 SINGLE ROOM B.O.P. 25"± BELOW SLAB LII HT BULB ROOM 4" UP (26318)(5 dfu) 1635A CLOSET 1631A1 CLOSET 1629A1 CLOSET 162701 CLOSET SLOPE CO 1 /8" PER FT. MIN. " UP(26258) (5 dfu) CLOSET 1623A CLOSET (10 dfu) SINK ROOM 5"(203 dfu 183 dfu) 4(178 dfu 4(173 dfu) 4" (166 dfu) 116191 TC MECHANICAL (71 (203 dfu)5 moo, 116751 SINGLE ROOM 116731 SINGLE ROOM 167501 CLOSET 1673A CLOSET 116711 SINGLE ROOM EXCAVATE LAWN AREA TO INSTALL BUILDING TRAP & PIPE. BACK FILL AND RESEED REFER TO DETAILS 1-1/2" SAN UP TO LAVS (1679) 116741 DOUBLE ROOM 1-1/2" SAN UP TO LAV (1679) 4" UP (_679 WC, 2673A WC & TUB) (100 dfu) PIPING IN ROOM 1679 REPLACED SUMMER 2012 3" SAN UP TO WC (TYP 3) EXIST. STORM MANHOLE EXIST. SANITARY MANHOLE " PROVIDE BUILDING TRAP. REFER TO DETAIL 3 P001 TO STORM MANHOLE 116691 SINGLE ROOM 1671A1 CLOSET I CLOSET 1669A 257 dfu) 116671 116651 SINGLE ROOM SINGLE ROOM 166301 CLOSET SINGLE ROOM SINGLE ROOM PATCH CONCRETE FLOOR SLAB(TYP) 116451 DOUBLE ROOM REPLACED DECEMBER 2012 116471 MAINTENANCE 110051 STAIR REINSTALL UTILITY SINK. PROVIDE SINK 1 NEW P—TRAP AND FAUCET REFER ROOM TO PLUMBING FIXTURE SCHEDULE C01 UP70 US -1 j : �� �'114 " VENT 6UP MS) 298 dfu)■" REMOVE AND REPLACE SHOWER FLOORS & WATER PROOFING ' CONNECTORS TO THE WALL 411 "FAAcaikp 2" TO SH (TYP) 115391 SAWCUT FLOOR PATCH CONCRET FLOOR 6"(249 dfu) 116621 (E)SAN (226 dfu) 5"• (3644(6 dfu) 5" (209 dfu) EXIST B.O.P. 31" ± BELOW SLAB 11648 STORAGE 4" UP 2630B) (5 dfu) PATCH CONCRETE FLOOR SLAB 16488 BIKE STORAGE TIE INTO EXISTING RISER ABOVE FLOOR (TYP) REFER TO DETAIL CO \ 154 UP _622 STACK REPLACED (156 dfu) DECEMBER 2012 ii MCLLU DEN 1622A1 CLOSET 7 CO EX 2" PUMP DISCHARGE - RECONNECT TO SAN RISER AT 1ST FLOOR 116501 MECHANICAL ROOM A 63; FOR 1ST FLR WORK IN THIS AREA REFER TO LOCKER ROOM (424 dfu) PROVIDE PIPE SLEEVE REFER TO DETAIL it EXIST B.O.P. 45.5" ± BELOW SLAB EXTEND NEW STORM OUTSID OF BUILDING AND CONNECT TO EXISTING PATCH CONCRETE FLOOR SLAB (TYP) BREAK RQOM 115361 2"ST UP PROJECT ROOM 100081 CORRIDOR HOT WAT TANK 6 SIDE (NORTH) — — — 5 SIDE (SOUTH) 1534 MECHANICAL ROOM FCO 110411 SERVICE ELEVATOR k "S HYDRAULIC ELEVATOR �3"ST FCO i ='1n FCO L �1 • • • al° PATCH CONCRETE FLOOR SLAB (TYP) YEAR 1 WORK YEAR 2 WORK 4" UP (2636A) (13 dfu) 6 SIDE (NORTH) M 11011111111111 11.11111111111 111111111011 - 5 SIDE (SOUTH) EXISTING SUMP PROVIDE FLOOR DRAIN AT BOTTOM OF SUMP FD -1 UNDERFLOOR PIPING REPLACEMENT PLAN — NORTH SCALE: 1/8" = 1'-0" EXISTING o� IJ HW&CW -\ MEN'S _1 BATH ROOM 116791 0 0 (1539 STORAGE CONNECT TO EXISTING HW & CW AND VENT 110271 CORRIDOR PROVIDE MOP SINK, FAUCET & MS -1 1 ACCESSORIES REFER TO PLUMBING FIXTURE SCHEDULE THIS DRAWING 3" SAN 1 115381 MEN'S LOCKER ROOM PARTIAL FIRST FLOOR PLAN SCALE: 1/8" = 1'-0" 116181 STORAGE STAIR 116151 116191 116191 STORAGE RECREATION ROOM 116171 KITCHEN 1/8" = 1'—O" 1 0 1 7 9 11 13 15 1 N — e11111 1■ — E N NOTES: 1. REPLACE UNDERFLOOR SANITARY & STORM PIPING AS INDICATED ON DRAWINGS. REFER TO PIPE SCHEDULE FOR PIPE MATERIALS. 2. BACKFILL AND PATCH CONCRETE FLOOR. REFER TO DETAIL 1/P001 AND SPECIFICATIONS. 3. PROVIDE NEW FLOOR CLEANOUTS AS INDICATED ON THE DRAWINGS. 4. BOTTOM OF PIPE (B.O.P.) ELEVATIONS SHOWN WERE MEASURED DURING THE CAMERA INSPECTION AND JETTING ON JUNE 6, 2012 AND AS NOTED ON CONTRACTOR AS—BUILT DRAWINGS FOR THE SUMMER 2012 "6" SIDE ONLY BATHROOM RENOVATION PROJECT. 5. PROVIDE EXTERIOR BUILDING TRAP AS NOTED ON PLANS. 6. PROVIDE CLEANOUT AT THE BASE OF EACH RISER REFER TO DETAIL 6/P001 7. CONTRACTORS SHALL BE RESPONSIBLE TO PROTECT ABOVE— GROUND PIPING SYSTEMS AND SURROUNDING BUILDING SURFACES I.E. FLOORS, WALLS, ETC. CONTRACTOR SHALL REPLACE ANY PIPE INSULATION, ABOVE GROUND PIPE, AND REPAIR ANY SURFACES DAMAGED IN THE PERFORMANCE OF THIS PROJECT. 8. REFER TO FINISHES REPLACEMENT PLANS FOR WALLS TO BE REPLACED. 6 SIDE NORTH 5 SIDE SOUTH KEY PLAN NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE O 0 —a 0 Ci • a) 03 O) 1- C cu O 4-1 Wm cN 4-1 hew C Q O > N ,� T-7 Z L m 4011 C mato 1a v Nnd- c 1 37 0 cu c c a) 0. 5 a) a) -. 0 Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON c 0 .0, ce d z a 1 ,,4 FT" Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P1O1 YEAR1&2 Sheet No. 3 of 7 NO FINISHES WORK REQUIRED FOR ROOM 1637 1639 SINGLE ROOM 163941 CLOSET 2" VEN UP 3" UP TO FD 1637 1 BATHROOM 2" SAN UP TO LAVS SINGLE ROOM 1063 11641 1 SINGLE ROOM 3" SAN UP TO WC `83, REPAIR WIRE LATH & PLASTER WALL (TYP.) REFER TO DETAI 164141 CLOSET REPLACE SUMMER 2012 2" SAN UP TO SH (TYP 2) SINGLE ROOM 11633 SINGLE ROOM SINGLE ROOM (26293) 16291 SINGLE SINGLE ROOM OM REPAIR WIRE LATH & PLASTER WALL CARPET TILES 1625 SINGLE ROOM 1623 SINGLE ROOM 1621AI CLOSET UP(2625B) 1623A CLOSET SINGLE ROOM CLOSET VINY TILE 163541 CLOSET 1631A CLOSET 162941 CLOSET CLOSET 1625A! CLOSET 10641 SINK ROOM NOTES: 1. THIS DRAWING IS INTENDED TO SHOW RESTORATION OF FINISHES ONLY. REFER TO DRAWINGS P100 & P101 FOR PIPING REPLACEMENT WORK. 2. CONTRACTOR SHALL RESTORE SURROUNDING FINISHES AFTER REPLACEMENT OF UNDERFLOOR PIPING. WORK INCLUDES REPLACEMENT OF CARPET, CERAMIC TILE AND VINYL TILE IN LOCATIONS SHOWN ON DRAWINGS. REPLACE STUD/ SHEETROCK AND CONCRETE BLOCK WALLS AS NOTED ON PLANS AND AS REQUIRED TO RESTORE TO PRECONSTRUCTION CONDITION. ALL WALLS IN CONSTRUCTION AREA SHALL BE PAINTED, COLOR SELECTED BY OWNER. 97 (E)FC0 TC MECHANICAL 1005 STAIR CONCRETE FLOOR 164881 BIKE STORAGE MCLLU DEN CARPET TILES 26303) 1622A 11618 STORAGE CLOSET 1619 STORAGE 1645 DOUBLE ROOM 11617 KITCHEN 2" UP TO SINK (1647) 11675 SINGLE ROOM 11673 SINGLE ROOM 116711 SINGLE ROOM 11669 SINGLE ROOM REPA R WIRE LATH & PLASTER WALL SINGLE ROOM 4" UP 4: (2670) 11665 1 SINGLE ROOM 11663 SINGLE ROOM SINGLE ROOM SINGLE ROOM REPLACED DECEMBER 2012 CLOSET 167341 CLOSET CLOSET 166941 CLOSET CLOSET 1663AI CLOSET 166141 CLOSET 1659AI CLOSET 11647 MAINTENANCE ONCRETE FLOOR 11648 1 STORAGE (E)SAN —� i1 ONCRETE FLOOR CARPET TILES REPAIR WALL BASE AS REQUIRED ONCRETE (2636A) PIPING IN ROOM 1 DOUBLE REPLACED SUMME ROOM 1-1/2" SAN UP TO LAV (1679) CERAMIC TILE 0 R SCHLUTER WATERPROOF MEMBRANE FCO VINYL TILE 116501 MECHANICAL ROOM CONCRETE FLOOR UP 79 SH) OPEN & REPAIR WALL AT RISER 3" SAN UP TO WC (TYP 3) 1-1/2" SAN UP TO LAVS (1679) 11679 1 2" 2" TO SH (TYP) 3" UP TO FD STORAGE CARPET TILE ERAMIC TILE LOCKER ROOM 2"SAN UP TO EX. SHOWERS A • titat-A&4t4t1 to ���������t�nni&4������������������mi'04 Ai min is ■'6� ►�V41 ri► ►4►4 111 s VINYL TILE REPAIR WIRE LATH & PLASTER WALL REPAIR WALL BASE AS REQUIRED CARPET TILE 115371 REPAIR WALL BASE AS REQUIREDNM MI --- VINYL TILE REPAIR WALL BASE AS REQUIRED YEAR 1 WORK CONCRETE FLOOR YEAR 2 WORK 11536 11535 PROJECT ROOM 1000HI 100001 11027 CORRIDOR HOT WATT TANK 1534 REFER TO DWG MECHANICAL P201 FOR WORK ROOM IN THIS AREA � FCO 6 SIDE (NORTH) . ^ 5 SIDE (SOUTH) 110411 CONCRETE FLOOR SERVICE ELEVATOR S7l, RISE mom— 6 SIDE (NORTH) 5 SIDE (SOUTH) FINISHES REPLACMENT PLAN - NORTH SCALE: 1/8" = 1'-0" /8" GWB 3-5/8" METAL STUD (16" 0.C.) WIRE LATH 1/2" — 5/8" PLASTER WIRE STUD METAL STUD WIRE LATH 2 WALL REPLACEMENT DETAILS P102 NOT TO SCALE 1 /8" = ff 6 SIDE NORTH 5 SIDE SOUTH 1 0 1 3 5 7 9 11 13 15 KEY PLAN NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEA ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE O 0 —a 01) 0 • i a) • a) 3 i (� W _. O ._ 3 - c WO av v a) a) c c a) cn 0. E a) E a) a> 0 Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Revision d z z ;7, c‘') 'ing °i? z o1� Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project Na. C14151 Drawing No. P102 YEAR1&2 Sheet No. 4 of 7 N:1915706\Drawings \P200 YR 2.dwg, 12/31/2014 9:01:33 AM, N62 6 SIDE (NORTH) / MOM 5 SIDE (SOUTH) MECHANICAL ROOM FCO : 10411 SERVICE ELEVATOR 1000F1 HYDRAULIC ELEVATOR 1 „.-YEAR 2 WORK �CONTINUED ON mon minim REMOVE GWB WALL "S1, RISEN FCC`+ 11028 RECEIVING 5"ST RISER J FCO DWG P100 MINIM SAWCUT FLOOR, REFER TO IOTA REMOVAL NOTE 1 (TYP.) CORRIDOR 1 j028A1 REMOVE WITH SOLI TORM FD COVER )000E1 4" SAN UP (2589) -E-ST----1.--- 1 ' I I I 4" SAN U CAP ABANDONED PIPE 115271 LAUNDRY 5" STORM RISER a COORDINATE WORK WITH EXISTING FIRE ALARM DEVICE EXIST SANITARY MANHOLE FOR R: LACEMENT 0 PIPE ABANDONED PIPE TO REMAIN 110251 CORRIDOR STORM FLOOR AtNS & CLEANOUTS CAPPED OFF AT FLOOR 7 --LINT TRAP (TO REMAIN) LAUNDRY UNDERFLOOR PIPING TO REMAIN EXIST GENERATOR —� EXIST STORM MANHOLE /35 \ 4, REMOVE FRESH AIR INLET EXIST GENERATOR PAD z 110251 CORRIDOR -2"ST UP SAWCUT FLOOR, REFER TO REMOVAL NOTE 1 (TYP.) INT TRAP & LAUNDRY UNDERFLOOR PIPING (TO REMAIN 1 6 SIDE (NORTH) NMI= MINIM NMI 5 SIDE (SOUTH) REMOVE GWB WALL FOR REPLACEMENT OF PIPE REMOVE, STORE AND REINSTALL WATER CLOSETS EXTEND NEW STORM OUTSIDE BUILDING )00TDl WOMEN COORDINATE WORK WITH EXI TING TELEPHONE/DATA & ELECTRIC OUTLETS REMOVE COUNTER & SINKS, STORE \D REINSTAIL ® Im Ioouol ,-PUMP DISCI-ARGE UP EXIST SUMP TO REMAIN CORRIDOR 4" SAN UP 579 115231 115211 SUMP PIT WITH PUMP (TO REMAIN) ::]:MUL"I-PURPOSE is-: ROOM OFFICE j521A1 BREAK ROOM iNN:\,\NN REMOVE FLOOR DRAIN AT BOTTOM OF SUMP O4" SAN UP (2573 FIR ALLOW FOR REMOVAL & REINSTALLATION ELECTRICAL OUTLETS F REMOVE GWB WALL FOR REPLACEMENT OF PIPE Hifl_____1520 l ADMIN. SUPPORT REMOVE GWB WALL FO REPLACEMENT 0 PIPE 11522 EQUIPMENT ROOM .Xy: 4" SAN UP (2550A) -3" SAN UP (2570):YA �� } I'1 REMOVE CASEWORK & SINK, STORE AND REINSTALL 99 11524 PASSAGE 4" 000cl MECHANICAL ROOM 115101 DINING SERVICES EXISTING (TO REMAIN) FD // \-4"SAN UP (2536A) O )-# (1504 COMPUTER CENTER 11519 OFFICE OFFICE 11 51 7 1 OFFICE 15181 VESTIBULE (514A1 ORIENTATION 115114 RA KITCHEN 0, 4" SAN UP REMOVE BLOCK (25306) \ ( WALL 115031 1504B1 STORAGE 100081 GENERATOR ROOM ALLOW FOR REMOVAL5 & REINSTALLATION OF` --- 3 ELECTRICAL OUTLET 115131 OFFICE REMOVE PLASTER FOR REPLACEMEN CONFERENCE ROOM SE PIPE RHA OFFICES )509A1 MECH. ROOM 15051 VESTIBULE 11502 RESOURCE ROOM 1 11—CORRIDOR REMOVE BLOCK WALL FOR REPLACEMENT OF PIPE OFFICE OFFICE DIRECTOR'S OFFICE 115121 REMOVE P0• •N OF WIRE LATH & LAST ' WALL FFICE 2" VENT UP REMO FOR 1 E BLOCK WALL EPLACEM OF 115101 OFFICE 11506 OFFICE OFFICE RECEPTION REMOVE GWB WALL 115241 OFFICE REMOVE, STORE AND REINSTALL WATER CLOSETS 00TB UNISEX T3" SAN UP TO WC 1-1/2" 11 SAN UP REMOVE COUNTER & SINKS, \ STORE AND REINSTALL `t..— COORDINATE WALL .04 SAN UP . (2 25B) ALLOW FOR REMOVAL & REINSTALLATION OF WIREMOLD ELECTRICAL OUTLETS 1021 VESTIBULE I501A OFFICE j502AI OFFICE REMOVAL/REPAIR WITH GFCI OUTLETS (TYP. 2) UNDERFLOOR PIPING REMOVAL PLAN - SOUTH SCALE: 1/8" = 1'-0" 1/8" = 1'-0" 1 0 1 3 5 7 9 11 13 15 I Mil EMI MI— I • — — — REMOVAL NOTES: 1. IN AREAS SHOWN, SAWCUT FLOOR, REMOVE CONCRETE SLAB AND HAND EXCAVATE AROUND SANITARY UNE. REMOVE PIPE AS INDICATED ON DRAWINGS. REMOVE RISERS MINIMUM OF 6" ABOVE FLOOR SLAB. 2. PIPING SHOWN ON DRAWINGS HAS BEEN DEVELOPED FROM PROJECT RECORD DRAWINGS AND FIELD VERIFIED TO THE GREATEST EXTENT POSSIBLE. CONTRACTOR SHALL VERIFY IN FIELD ALL LOCATIONS PRIOR TO REMOVAL OF WALLS AND SAW CUTTING OF FLOOR. 3. REMOVE, STORE AND REINSTALL PLUMBING FIXTURES AS NOTED ON DRAWINGS. 4. CONTRACTOR SHALL REMOVE GWB, PLASTER AND CONCRETE BLOCK WALLS AS SHOWN ON DRAWINGS TO FACILITATE PIPE REPLACEMENT. 5. CONTRACTORS SHALL BE RESPONSIBLE TO PROTECT ABOVE -GROUND PIPING SYSTEMS AND SURROUNDING BUILDING SURFACES I.E. FLOORS, WALLS, ETC. CONTRACTOR SHALL REPLACE ANY PIPE INSULATION, ABOVE GROUND PIPE, AND REPAIR ANY SURFACES DAMAGED IN THE PERFORMANCE OF THIS PROJECT. 6 SIDE NORTH 5 SIDE SOUTH KEY PLAN NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. g THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE 0th -a 0 C5 G) 03 5 3 _ 0 W _. c 0 •- � 11- c O av 1-1 .1 c t0 n Ltf M 74 ai c 0 0. H v a) C c a) Q. E a) n3 E a) 0 0 Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Revision d z 1 r$0 dR w 010 ta/Si 0-4 c'''3 Ooh Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P200 YEAR 2 Sheet No. 5 of 7 N:\915706\Drawings\P201 YR 2 UF 5 SIDE.dwg, 12/31/2014 6 SIDE (NORTH) 5 SIDE (SOUTH) �8. �2, IIJJ41 MECHANICAL ROOM FCO 11041 SERVICE ELEVATOR 000E1 HYDRAULIC ELEVATOR YEAR 2 WORK CONTINUED ON DWG P101 11028 RECEIVING 5"ST RISER , rJ CONNECT TO RISER ABOVE FLOOR TYP. 1 10TA1 COR DOR PATCH CONCRETE FLOOR PATCH CONCRETE FLOOR 1028AI REMOVE AND REPLACE GWB ENCLOSURE FOR REPLACEMENT OF PIPE 115271 CORRIDOR STORM FLOOR S & CLEANOUTS CAPPED OFF AT FLOOR 4.15 6 SIDE (NORTH) 5 SIDE (SOUTH) 4" SAN UP TO FD (TYP. 4)— LINT TRAP 11025 CORRIDOR PROVIDE STRUCTURAL SUPPORT TO GENERATOR PAD DURING EXCACATION. EXIST GENERATOR --\,1/4 EXTEND NEW OUTSIDE OF B EXIST GENERATOR PAD TO REMAIN TORM ILDING 4" (42 dfu) PROVIDE BUILDING TRAP. REFER TO DETAIL PROVIDE PIPE SLEEVE REFER TO DETAIL 4" (70 dfu) EXISTING LINT TRAP & LAUNDRY UNDERFLOOR PIPING TO REMAIN EXIST SANITARY MANHOLE EXCAVATE LAWN AREA TO INSTALL BUILDING TRAP AND PIPE. DO NOT UNDERMINE GENERATOR PAD. BACK EXIST STORM FILL AND RESEED REFER TO DETAIL MANHOLE /- 2„ (350 dfu) 6"(280 dfu) WOMEN 100081 REINSTALL LAVATORIES (TYP. 3) PAT H CONCRET FLO R (TYP) REINSTALL WATER CLOSET (TYP. 3 Co I - 10248 PUMPII DISCH RGE UP CORRIDOR 4" SAN UP 579 PROVIDE FLOOR DRAIN (228 dfu) 6" SUMP PIT WITH PUMP—. EXIST SUMP 115231 OFFICE 115211 I -PURPOSE ROOM -SLOPE 1/8" PER FT. MIN. PASSAGE 115221 EXIST EQUIPMENT ROOM 1 oouCI MECHANICAL ROOM REPLACE GWB WALL FCO 3" SAN UP (2570) �1 (220 dfu) 6" REPLACE GWB WALL REINSTALL SINK & CASEWORK 115041 COMPUTER CENTER 213 dfu) •" 11524 PASSAGE (198 dfu)5 74 SLOPE ® 1/8 PER FT. MIN. 198 dfu) 5" 115201 ADIAN. SUPPORT 15191 OFFICE 11518 OFFICE 11517 1510 4" SAN UP (2536A) (10 dfu) 1504A1 DINING SERVICES PATCH CONCRETE FLOOR OFFICE 11518 1 VESTIBULE 1514A TIE INTO EXIST. RISER ABOVE FLOOR (TYP) REFER TO `�� 15081 110231 PASSS,GF ORIENTATION RA KITCHEN GENERATOR ROOM 188 dfu)5" OFFICE CONFERENCE ROOM 110221 4" (5 dfu 11509 RHA OFFICES PATCH CONCRETE FLOOR (172 dfu) I 1 4" 1 �►� VESTIBULE SLOPE O' 1/8"' PER FT. MIN. (177 dfu) 4" PATCH CONCRETE FLOOR (TYP) (5 dfu 4 11526 1509AI MECH. ROOM 11505 COPY ROOM (160 dfu)4" • FCO 4.. 411020 CORRIDOR, 4 (167 dfu)itt#• 1<: 11111 (7dfu)4" ,� Y�, ZCAAI 115021 RESOURCE ROOM OFFICE DIRECTOR'S OFFICE 1512 OFFICE 15101 OFFICE OFFICE RECEPTION 2" VENT UP 115241 OFFICE REINS WATER CLOSETS 3" SAN UP TO WC 100T81 UNISEX TOILET 11 SAN UP 1-1/2" O4 SAN UP (2 25B) VESTIBULE 1501A OFFICE 1502A OFFICE REINSTALL SINKS & CASEWORK UNDERFLOOR PIPING REPLACEMENT PLAN - SOUTH SCALE: 1/8" = 1'-0" 1/8 = " 1 0 1 3 7 9 11 13 15 MI E E E ■ — I 1 NOTES: 1. REPLACE UNDERFLOOR SANITARY & STORM PIPING AS INDICATED ON DRAWINGS. REFER TO PIPE SCHEDULE FOR PIPE MATERIALS. 2. BACKFILL AND PATCH CONCRETE FLOOR. REFER TO DETAIL 1/P001 AND SPECIFICATIONS. 3. PROVIDE NEW FLOOR CLEANOUTS AS INDICATED ON THE DRAWINGS 4. PROVIDE EXTERIOR BUILDING TRAP AS NOTED ON PLANS. 5. PROVIDE CLEANOUT AT THE BASE OF EACH RISER REFER TO DETAIL 6/P001 6. ALL PIPE SHALL BE SLOPED AT 1/8" PER FOOT MINIMUM 4" AND ABOVE, AND 1/4" PER FOOT MINIMUM SMALLER THAN 4". 7. CONTRACTORS SHALL BE RESPONSIBLE TO PROTECT ABOVE GROUND PIPING SYSTEMS AND SURROUNDING BUILDING SURFACES I.E. FLOORS, WALLS, ETC. CONTRACTOR SHALL REPLACE ANY PIPE INSULATION, ABOVE GROUND PIPE, AND REPAIR ANY SURFACES DAMAGED IN THE PERFORMANCE OF THIS PROJECT. 8. REFER TO FINISHES REPLACEMENT PLANS FOR WALLS TO BE REPLACED. 6 SIDE NORTH 5 SIDE SOUTH KEY PLAN NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. IT IS A VIOLATION OF THE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. 00 154 ci c co 5 (� W C 0) (1,",0c W 0 0. a) c O CO LU t0 I 8 Zr) a) c a) a N E a) 1 4) 0 0 Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Revision d z w aL4 '1114 O 0_4 w 3 Ooh Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Pa's Na. C14151 Drawing No. P201 YEAR 2 Sheet No. 6 of 7 6 SIDE (NORTH) 5 SIDE (SOUTH) 414 A of 115341 CONCRETE MECHANICAL FLOOD- ROOM FCO < 110411 SERVICE ELEVATOR PROVIDE STUD/SHEETROCK WALL 11028 RECEIVING 5"ST RISER. icait O• "S RISER 1001E1 HYDRAULIC ELEVATOR TANK FCN .4.. e a •e•*•••••••Co ♦•♦ 5" 4 CONCRETE ' 14 FLOOR aai` f ° . °al . 1. I. 1, 3"ST 1028A1 1q7A VINYL TILE CORRIDOR \`-STORM FD WITH SOLID COVER slat m �3, c 000E 5 �t— 0,4" SAN UP (2589) VINYL TILE 2"V UP ST •��e e, C7 115271 LAUNDRY PROVIDE STUD/SHEETROCK WALL 5" STORM ISER I 4" SAN U 4" SAN UP TO FD (TYP. 4)m FCO "ST 4" 4" 4.V*400••v♦ EXISTING LINT TRAP & LAUNDRY UNDERFLOOR PIPING CONTINUED ON P200 PROVIDE STUD/SHEETROCK WALL ST T 110251 CORRIDOR STORM FLOOR AtNS & CLEANOUTS CAPPED OFF AT FLOOR —4" LINT TRAP T 26 1/2" HIGH KNEE WALL CORRIDOR 11025 \--VINYL TILE F53 HIGH WALL I I CARPET TII F CERAMIC TILE Ii OOTD WOMEN VINYL TILE 100081 MECH REPAIR WALL AT RISER CO TION (TYP) Fco •ei0''ei�,4Pee•wfrfrw e_e_e_e_e_e��.e, ee_� 115231 OFFICE 15231 PASSAGE' 4" SAN UP -� ..... % (2573 FIR APT) . " PROVIDE STUD/SHEETROCK WALL CARPET TILE • 4" SAN UP (_579) .. MULTI-PURPOSE' ':>ROOM 4"ST: 1J:, -3" V — CARPET TILE 38 6 SIDE (NORTH) 5 SIDE (SOUTH) VINYL TILE ,-PUMP DISCHARGE UP lif/8" GWB 3-5/8" METAL STUD (16" 0.C.) 111 WIRE LATH 1/2" - 5/8" PLASTER WIRE STUD METAL STUD WIRE LATH WALL REPLACEMENT DETAILS NOT TO SCALE •• •• eee�ieO�eiei� /eee,eeee♦ •ss�s— •e�� • 521A eeeee• BREA ROO • , FCO :<. SAN • 'a "':.:PROVIDE STUD/SHEETROCK. WALL • 15221 e.', �'•`:'•EQUIPMENT::•':•;: 1e ROOM e • :. •. 4" SAN UP; • • "•.`.•}..;'•.,' 3" SAN UP (2570) z. . --REMOVE & REINSTALL SINK AND CASEWORK REPAIR WALLS 1520 ADMIN. SUPPORT T 11518 VESTIBULE 11519) OFFICE 115241 PASSAGE 115181 OFFICE CARPET TILE - 0 :• SUMP PIT WITH PUMP _1� CONCRETE FLOOR --J loouc MECHANICAL ROOM 1 •' FCO SAN .. • y"S EXIST TO REMAIN 11510 : DINING ' `:•'SERVICES •. 1514A CARPET TILE 00ue1 GENERATOR ROOM VINYL TILE 0 CARPET TILE 110221 ORIENTATION •✓ ' • "•.• ". VESTIBULE G 4" SAN UP O (2536A) `-- CONCRETE FLOOR 110231 PASSAGE • 115116 RA KITCHEN -VINYL SHEET T� 0, 4" SAN UP (2530B) PROVIDE PATCH OF LT CONCRETE BLOCK WALL DEPTH VARIES i -- (MATCH EXISTING) CONCRETE BLOCK AINT ROOM SIDE NOTES: 1. THIS DRAWING IS INTENDED TO SHOW RESTORATION OF FINISHES ONLY. REFER TO DRAWINGS P200 & P201 FOR PIPING REPLACEMENT WORK. 2. CONTRACTOR SHALL RESTORE SURROUNDING FINISHES AFTER REPLACEMENT OF UNDERFLOOR PIPING. WORK INCLUDES REPLACEMENT OF CARPET, CERAMIC TILE AND VINYL TILE IN LOCATIONS SHOWN ON DRAWINGS. REPLACE STUD/ SHEETROCK AND CONCRETE BLOCK WALLS AS NOTED ON PLANS AND AS REQUIRED TO RESTORE TO PRECONSTRUCTION CONDITION. ALL WALLS IN CONSTRUCTION AREA SHALL BE PAINTED, COLOR SELECTED BY OWNER. / 3 l CONCRETE BLOCK WALL REPLACEMENT SECTION DETAIL NOT TO SCALE 115131 OFFICE REPAIR PLASTER WALL CHASE CONFERENCE • '..•ROOM ,;...,: • • : REPAIR WALL BASE AT PIPING CROSSING (TYP) '•' -CARPET •:..1• `: TILE • 115091 RHA OFFICES 4 1509A1 MECH. ROOM CONCRETE FLOOR SAN 115051 COPY CARPET TILE -•h ROOM 115041 COMPUTER CENTER FCO' S 110201 • .::' ..: CORRIDOR' <•••' • :11526 f' •`11524 OFFICE OFFICE • 3" SAN UP TO WC UNISEX TOILET CERAMIC TILE FCO • 2 VENT UP 11516 DIRECTOR'S OFFICE CARPET %4" SAN UP (2529B) OFFICE •• CARPET TILE 3" SAN OFFICE PROVIDE PATCH OF CONCRETE BLOCK WALL 11503 STORAGE Fu FCO 11501 15048 PROVIDE STUD/SHEETROCK WALL (TYP) REFER T0, 4" SAN UP (_522 STACK) CARPET TILE RECEPTION REPAIR WIRE LATH & PLASTER WALL SAN UP PROVIDE PATCH OF CONCRETE BLOCK WALL REFER TO DETAIL FINISHES REPLACEMENT PLAN - SOUTH () 4" SAN UP PROVIDE STUD/SH ROCK WALL 11021 VESTIBULE 2 P202 11502 RESOURCE ROOM i 500 OFFICE 150281 OFFICE 1502A1 OFFICE 9 11 13 15 I NM 1111 Ell 1111 I • Ell Ell Ell 6 SIDE NORTH 5 SIDE SOUTH KEY PLAN NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE co 111 co 1-1 CO 1 ,$k .13 rL.•0 '114 0 cs) )c7,4 Scale AS SHOWN Date 12/31/14 Drawn KA. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No C14151 Drawing No. P2O2 YEAR 2 Sheet No. 7 of 7 N:\915706\Drawings\P301_P302.dwg, 12/31/2014 9: 6 SIDE (NORTH) 5 SIDE (SOUTH) SERVICE ELEVATOR HYDRAULIC ELEVATOR I in is 5' ST UP & DN SAN PIPE (SERVES RM 26 110281 6 SIDE (NORTH) 5 SIDE (SOUTH) RECEIVING CORRIDOR 5" ST UP & DN STAIR ROOF AT 2ND FLOOR LEVEL ho28PI 4" SAN DN (2589 & 2689) hooUE hooUE 15271 4 SAN UP Ti WC SAN PIPE (SERVES 'M 2589) CORRIDOR 2" VENT UP 11527 LAUNDRY 3"SN UP TO F 2" ST UP TO RD 44 5" STUP&DN II 11A111111111 C-- 2" SAN UP TO SH (TYP 2) FOR INFORMA11ON ONLY THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES PIPE AT CEILING (TYP.) 110251 CORRIDOR hooud 4" SAN UP&DN (_579 & 2573 FIR) 1-1/2" SAN UP TO TUB h0240 2" PU DISCHA CORRIDOR 3" SA UP TO WC MULTI—PU ROO h521A BREAK ROOM OFFICE MECHANICAL ROOM EXISTING SPLIT SYSTEM AIR CONDITIONER WITH INTEGRALI CONDENSATE PUMP (TYP). EXISTING SINK DRAIN PUMP 3 SAN UP TO FD 3" VENT STACK 115201 AEMN. SUPPORT 2" SAN UP TO SH 3" SAN DN (2570) 3" SAN UP TO WC 115221 EQUIPMENT ROOM 4" SAN DN (2550A) AD FOR CO 115041 COMPUTER CENTER EXISTING 3/4" AC DRAIN ABOVE CEILING PASSAGE 4" SAN UP (2536A) 1-1/2" SAN UP TO SINK DINING SERVICES EXISTING DRAIN HUB OFFICE 115181 OFFICE OFFICE VESTIBULE OFFICE 11508 110231 PASSAGE ORIENTATION RA KITCHEN 4' SAN DN (2530B) h 50481 11503 STORAGE 2" SA GENERATOR ROOM 2" SAN UP 115131 OFFICE 3" SAN UP TO WC RHA OFFICES CONFERENCE ROOM h5o9A1 PIPE AT CEILING (TYP.) MECH. ROOM 3" U TO W0 COPY ROOM 3" SAN TO FD VESTIBULE 110211 11 020 1 4" SAN UP&DN (_522 STACK) 3" SAN UP (_522 SH STA 15021 CORRIDOR LOWER LOBBY OFFICE OFFICE 4" SAN UP 4" SAN UP DIRECTOR'S OFFICE 115121 OFFICE 11506 OFFICE OFFICE RECEPTION 115241 4 4" SAN DN (2529B) 1-1/2" SAN UP OFFICE 4" SAN DN (25258) UNISEX TOILET 110211 VESTIBULE OFFICE 115024 OFFICE o EXISTING FIRST FLOOR PLUMBING PLAN - SOUTH SCALE: 1/8" = V-0" 1 0 1 1/8" = 1'-0" 3 5 7 11 13 15 1 _ — E INN 1■ = E 5 SIDE SOUTH 2 KEY PLAN P301 NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW. IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. Q LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THS DOCUMENT IN ANY IT IS A VIOLATION OF THE 00 -a 0 Ci cm 00 • 5) • C 0 0) o• � Wv+ 4.0c 4) o av • M 4) co a) tp C • c a ai oE aa) N .CD I- a) Philip A. Peterson NYS PE LICENSE # 59561 N 0 0 a THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES PIPE AT CEILING (TYP.) 110251 CORRIDOR hooud 4" SAN UP&DN (_579 & 2573 FIR) 1-1/2" SAN UP TO TUB h0240 2" PU DISCHA CORRIDOR 3" SA UP TO WC MULTI—PU ROO h521A BREAK ROOM OFFICE MECHANICAL ROOM EXISTING SPLIT SYSTEM AIR CONDITIONER WITH INTEGRALI CONDENSATE PUMP (TYP). EXISTING SINK DRAIN PUMP 3 SAN UP TO FD 3" VENT STACK 115201 AEMN. SUPPORT 2" SAN UP TO SH 3" SAN DN (2570) 3" SAN UP TO WC 115221 EQUIPMENT ROOM 4" SAN DN (2550A) AD FOR CO 115041 COMPUTER CENTER EXISTING 3/4" AC DRAIN ABOVE CEILING PASSAGE 4" SAN UP (2536A) 1-1/2" SAN UP TO SINK DINING SERVICES EXISTING DRAIN HUB OFFICE 115181 OFFICE OFFICE VESTIBULE OFFICE 11508 110231 PASSAGE ORIENTATION RA KITCHEN 4' SAN DN (2530B) h 50481 11503 STORAGE 2" SA GENERATOR ROOM 2" SAN UP 115131 OFFICE 3" SAN UP TO WC RHA OFFICES CONFERENCE ROOM h5o9A1 PIPE AT CEILING (TYP.) MECH. ROOM 3" U TO W0 COPY ROOM 3" SAN TO FD VESTIBULE 110211 11 020 1 4" SAN UP&DN (_522 STACK) 3" SAN UP (_522 SH STA 15021 CORRIDOR LOWER LOBBY OFFICE OFFICE 4" SAN UP 4" SAN UP DIRECTOR'S OFFICE 115121 OFFICE 11506 OFFICE OFFICE RECEPTION 115241 4 4" SAN DN (2529B) 1-1/2" SAN UP OFFICE 4" SAN DN (25258) UNISEX TOILET 110211 VESTIBULE OFFICE 115024 OFFICE o EXISTING FIRST FLOOR PLUMBING PLAN - SOUTH SCALE: 1/8" = V-0" 1 0 1 1/8" = 1'-0" 3 5 7 11 13 15 1 _ — E INN 1■ = E 5 SIDE SOUTH 2 KEY PLAN P301 NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW. IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. Q LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THS DOCUMENT IN ANY IT IS A VIOLATION OF THE 00 -a 0 Ci cm 00 • 5) • C 0 0) o• � Wv+ 4.0c 4) o av • M 4) co a) tp C • c a ai oE aa) N .CD I- a) Philip A. Peterson NYS PE LICENSE # 59561 N 0 0 a Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER (flecked P.A. PETERSON c 0 1 0 Z 1 „T., .?.1 ca) 14 '14 g a a °e'' 0-4 W 3 o �U c 1 Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER (flecked P.A. PETERSON Project No. C14151 Drawing No. P301 Sheet No. 1 of 6 THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW. THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. LI) z C9 N CL w 2 1- m Li) O J O w cc LLJQ z 0 0 z w 1- 0 z J v) cc w 1- Q J 1 (1)J z 0 (7 N O a O Z w J w 1- 0 w w J U- 00 —a 0 M cos 3_ 0w CV. 3 0) • u) +� c CD a. 1-1 CO tp N 1n N c .0' c a) 0' 0. 0) E 0 0 Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Revision d Z a z z z w 0 0 0 N 1— w J 0 U.1 w z z w 0 w z w U J w O z O w 0 w w 0 z 0 U O V) a.O w IT IS A VIOLATION OF THE N:\915706\Drawings\P3012302.dwg, 12/31/2014 9:4 6 SIDE (NORTH) 5 SIDE (SOUTH) 16391 SINGLE ROOM 1-1/2"V 116394 CLOSE BATHROOM 1-1/2" SAN UP TO LAV SINGLE ROOM 4" SAN UP TO WC SINGLE ROOM h641P1 SINGLE ROOM CLOSET 116434 CLOSET 4" SAN DN (26318) 11081 LINEN CLOSET SINGLE ROOM 4" SAN UP TO 1-1/2" SAN UP TO TUB I� 1-1/2" SAN UP TO LAV SINGLE ROOM 16311 SINGLE ROOM 116291 SINGLE ROOM 1-1/2" SAN UP TO TUB SINGLE ROOM SINGLE ROOM 116231 SINGLE ROOM 16218 CLOSET 4" SAN DN (2625B) CLOSET CLOSET CLOSET CLOSET CLOSET h 6270 CLOSET 1162501 SINK ROOM CLOSET 110311 4" SAN DN (2629B) CORRIDOR 4" WC SAN STACK 4" SAN DN (_622 STACK) 3" SAN UP 110621 TC (_622 SH STACK) MECHANICAL 110081 STAIR 3" SAN UP TO WC (TYP 3) 4" SAN UP TO WC 3" SAN UP IPE AT CEILING TYP. 1-1/2" SAN h648B UP TO TUB BIKE STORAGE 1-1/2" SAN UP TO SINK (2624) MCLLU DEN 3" SAN UP TO FD 2" SAN UP TO LAV 2" SAN UP TO LAVS CLOSET 2" SAN UP TO SH (TYP 3) STORAGE DOUBLE ROOM 4" SAN DN (2630B) 4" SAN UP (LAV&SH STACK) 110091 STAIR KITCHEN SNGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM SNGLE ROOM SINGLE ROOM 16611 SINGLE ROOM h 64801 STORAGE SINGLE ROOM STORAGE CLOSET CLOSET CLOSET CLOSET CLOSET h 665A CLOSET 1166304 2" SAN UP TO LAVS CLOSET CLOSET CLOSET 4" SAN UP TO WC 16151 RECREATION ROOM °k_1-1/2" UP (SINK -2673) 4" SA DN (2636 2"PUMP DISCHARGE D 4" SAN UP & DN (_679 SH STACK) SINK ROOM 2"SAN UP TO SH 1166 STORAGE DOUBLE ROOM 3"SAN TO WC (2673A) 1-1/2" SAN UP TO TUB 2673A 2"SAN UP TO LAVS (2673A) 4" SAN DN (2670 & 2650A) 2" SAN UP TO LAVS (2650A) 11650 MECHANICAL ROOM 4" SAN UP & D (_679 WC STACK 4" SAN UP TO WC TYP 3 MEN'S BATH ROOM STORAGE CORRIDOR 4" VENT STACK MEN'S LOCKER ROOM BREAK ROOM 2"SAN UP TO LAVS PIPE AT CEILING TYP. 3"SAN UP TO WC PROJECT ROOM N UP • FD 2"SAN UP TO UR e --•k.„,.2" ST DN 52 2"SAN UP TO SH (TYP 2) 2" VENT 115341 CONTINUED • MECHANICAL DRAWING " 102 ROOM UP 5"STUP&DN 111 SAN PIPE (SERVES RM 26:-9) h000F1 SPRINKLER ROOM hooud 1102)1 CORRIDOR HOT WATER TANK 10411 SERVICE ELEVATOR 11000F 52 2" ST UP TO RD HYDRAULIC ELEVATOR MEI 6 SIDE (NORTH) 5 SIDE (SOUTH) EXISTING FIRST FLOOR PLUMBING PLAN -NORTH SCALE: 1 /8" = 1'-0" 1 /8" = 1'-0" FOR AIFORMATION ONLY THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES 1 0 1 3 5 7 9 11 6 SIDE NORTH 5 SIDE SOUTH J tJ 13 15 1 1■ KEY PLAN NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. 1 Pg Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P3O2 Sheet No. 2 of 6 N:\915706\Drawings\P303_P304.dwg, 12/31/2014 9:50:21 AM, N62 6 SIDE (NORTH) 5 SIDE (SOUTH) 4Q 1 2597 COMPLEX CONGRESS 5" ST UP ROOF DRAIN 25951 STUDY 125951 STUDY 125931 STUDENT STAFF 5" ST UP & DN 5" ST DN 4"SAN DN 3"V UP 5" ST UP & DN 125911 DOUBLE ROOM 125910 CLOSET r 2010 STAIR SINGLE 7\ /\_ ROOM 12692A CLOSET RD 3"SAN DN 1200001 STORAGE 125914 CLOSET L Adis II FD 2"V DN 2" SAN DN (TYP 2) 12589 - BATH ROOM 125871 SINGLE ROOM 1258741 CLOSET 125851 SINGLE ROOM 125850 CLOSET 2"SAN UP 12583 SINGLE ROOM 12583A CLOSET 125941 125941 PROGRAM LOUNGE 1 0 0 VESTIBULE 12592/1 CLOSET 2"SAN DN 2" V RISE 120271 CORRIDOR 3"SAN UP PIPE AT CEILING TYP. 125811 125810 CLOSET FACULTY -IN - RESIDENCE 125921 SINGLE ROOM 0 RD /4� 0 I2590Pl CLOSET 125901 SINGLE ROOM 1256801 CLOSET 2588 SINGLE ROOM 12586/1 CLOSET > 12586 SINGLE ROOM 124E CLOSET CLOSET J 4" VENT 2"SAN UP 1-1/2" SAN DN 12573 FACULTY -IN RESIDENCE 12573 FACULTY -IN - RESIDENCE 1257311 CLOSET 120381 CORRIDOR 125810] CLOS€F C 12573d BATH ROOM J L 3"V UP & DN 00 00 1-1/2" isSAN DN 0 125730 1 0 12584 DOUBLE ROOM 4" SAN STACK (_579) (25821 DOUBLE ROOM 3" SAN DN /"\_ 125824 CLOSET 12582A CLOSET a r-2"SAN 2" V RI v .L FACULTY -IN - RESIDENCE N FD 2"V UP - 12570 BATH ROOM 2"V DN 125711 DOUBLE ROOM . 6 SIDE (NORTH) 5 SIDE (SOUTH) 5 12004 STAIR 3 2" SAN DN 4" SAN DN (TYP 3) f L J�L�L 12552 CONTROL OFFICE DN 3" SAN DN 12027 CORRIDOR 12569 SINGLE ROOM 2"VUP 12025 VESTIBULE 120261 1255011 WOMENS TOILET 2550 TOILET ROOM VESTIBULE 0 2" SAN DN 2"V UP 125371 LOUNGE 12401 LI ING ROM 4" SAN DN (TYP 2) 2"VUP 2" SAN DN 125351 STUDY 125331 GROUP STUDY 12538 PANTRY 0 (2536 BIKE ROOM 2536/1 MENS TOILET it 2003 STAIR 2 UP 12024 PASSAG 125341 SINK ROOM 125321 STORAGE 530 PRIVATE BATH 2" V UP 12530 BED ROOM 2" SAN DN 125300 CLOSET 125300 CLOSET 2" SAN DN 2"VUP 25301 3"SAN DN LIVING ROOM 2" V DN 120231 CORRIDOR 12531 RHD 125314 BED ROOM 2" V UP 1252901 BED ROOM 4" SAN DN '529: PRIVATE BATH 2529E1 HALL 125290 CLOSET 125290 CLOSET 2022 VESTIBULE FOR INFORMA11ON ONLY THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES 125021 SINGLE ROOM 250201 CLOSET 1250441 CLOSET 125041 SINGLE ROOM 125061 SINGLE ROOM 125064 CLOSET 12508 SINGLE ROOM 12508/1 CLOSET 2" SAN DN UP 120011 STAIR 1 2"V UP 2" SAN DN 2" SAN 125261 SINGLE ROOM PIPE AT CEILING TYP.-----y 12529 LIVING ROOM Gil 12526 CLOSET 1 1/2" SAN DN 125271 125241 KITCHEN 3" UP J TO WCO 0 � 0 0 0 °.4`2" SAN DN 25221 BATH/TOILET ROOM 4" V U CUSTODIAL 2" V UP 12525A CLOSET 1 4" SAN DN 1525: PRIVATE BATH 12525 PROGRAM ASST. 12523/1 CLOSET 125231 SINGLE ROOM UI 1-1 �4" SANh �._ 3" SAN UP&DN UP&DN CORRIDOR 120201 12521 F--7 HOUSE MAID ):(I CLOSET EXISTING SECOND FLOOR PLUMBING PLAN - SOUTH SCALE: 1 /8" = 1'-0" 12519E CLOSET 3" SAN D 125191 DOUBLE ROOM CLOSET 125011 SINGLE ROOM 1250141 CLOSET 12503/1 CLOSET 125031 SINGLE ROOM 1250541 CLOSET \ Y 125051 SINGLE ROOM 1250701 CLOSET 125071 SINGLE ROOM 125094 CLOSET 2509 SINGLE ROOM 12511 SINGLE ROOM CLOSET 12513A1 CLOSET \ v 125131 SINGLE ROOM (25151 SINGLE ROOM 1251591 CLOSET 127171 DOUBLE ROOM 12517E CLOSET 12517A CLOSET 1 /8" = 1'-O" 1 0 1 3 7 9 11 13 15 1 M 011111 1■ 1 L 6 SIDE NORTH 5 SIDE SOUTH 2 KEY PLAN P303 NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW. LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE d1 8 so o r-1 i N c 1 1 C ,�-1 Q CU ��z ifi v0) O a) ea to I— N CNGR 373 * it ''o f::: "3- ,0, -- .e0, 73"F I R PC046C I 0 0 Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON 0 70 d z 1 c7 649 t )4 `a' 0 oz 1 Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P3O3 Sheet No. 3 of 6 00 -a 0 C C5 a) 3 _ 0 W 0) O N L.N +� c WO av 1-4 1 � r-1 N M Q L O >' Ln rl 031 N m Z 4) V) V) O CEI —C W U Q. V N c 4) fl. a E 0) 0 Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Revision 0 z a >a z Z w U 0 0 N S 1- Q O w w Z z w 0 w z w 0 J L. 0 z 0 0 w 0 w 1- cc w 0 Z w J O cc d w IT IS A VIOLATION OF THE N:\915706\Drawings\P303_P304.dwg, 12/31/2014 9: 1 6 SIDE (NORTH) 5 SIDE (SOUTH) \9� 1-1/2" SAN DN 1-1/2" SAN DN 1 CLOSET STUDY ROOM 12619 DOUBLE ROOM DOUBLE ROOM PRIVATE BATH 4" SAN DN 625 PRIVATE BATH 83 I 82 P 111 1-1/2" 1SAN DN BED ROOM 4" SAN DN PRIVATE BATH BED ROOM 2" V UP CLOSET 12629C CLOSET 126294 LIVING 4" SAN DN ROOM LINEN CLOSET 26251 RESIDENT ADVISOR 2"VUP CLOSET 3" SAN UP & DN CLOSET 12623A CLOSET 2621 HOUSE MAID �LOSET 126351 ARD OFFICE 120321 CORRIDOR 4"VUP 126191 CLOSET 619A1 CLOSET CLOSET 4" SAN UP & DN PASSAGE STACK) 4" SAN UP & DN (SH STACK) CLOSET SINGLE ROOM CLOSET CLOSET SINGLE ROOM CLOSET BED ROOM LIVING ROOM 1-1/2" SAN DN VESTIBULE SINGLE ROOM 3" SAN UP & D KITCHENETTE CLOSET SINGLE ROOM 0 3" SAN UP & DN V RISER 4" SAN UP & DN (_622 LAV & SH STACK) STAIR 2N 1 LOUNGE T 12677 12669A CLOSE SINGLE ROOM DOUBLE ROOM 12669 SINGLE ROOM SINGLE ROOM SINGLE ROOM CLOSET 2" SAN DN 2" V RISE FOYER CLOSET 126754 CLOSET SINGLE ROOM SINGLE ROOM 1-1/2" SAN DN LOSET LIVING ROOM 120281 CORRIDOR HOUSE MAID CLOSET �J TOILET ROOM VESTIBULE 4" SAN DN 4" SAN DN (TYP. 3) SINGLE ROOM 126031 SINGLE ROOM CLOSET 2" SAN UP TO SH DRAIN TYP. 5 DOUBLE ROOM 'b 3" SAN DN CLOSET 1-1/2" SAN DN PIPE AT CEILING TYP. 3" SAN UP (_679 LAV STACK) TYP. 12681E[ CLOS 3" UP TO FD TYP. 2 126801 CONTROL OFFICE VESTIBULE WOMENS TOILET 2" SAN DN 2" V RISE LIVING ROOM 26021 CLOSET CLOSET SINGLE ROOM SINGLE ROOM DOUBLE ROOM 4" SAN UP & DN (_679 WC STACK) DOUBLE ROOM CLOSET 4" VENT STACK 111 CLOSET CLOSET 126831 SINGLE ROOM DOUBLE ROOM CLOSET CLOSET CLOSET 2685A1 CLOSET 686t1 CLOSET CLOSET SINGLE ROOM SINGLE ROOM 2"SAN DN CLOSET 12688A1 CLOSET 126861 SINGLE ROOM 126881 SINGLE ROOM 12689 CLOSET 126904 SINGLE ROOM CLOSET 26921 SINGLE ROOM 12692A CLOSET RD 53 125971 COMPLEX CONGRESS 5" ST UP & DN 5" ST UPTTO ROOF DRAIN 125941 r 12595 CTI IDY 5" ST DN 6 SIDE (NORTH) 5 SIDE (SOUTH) EXISTING SECOND FLOOR PLUMBING PLAN - NORTH SCALE: 1 /8" = 1'-0" FOR 1NFORMA11ON ONLY THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES 1/8" = 1,_0„ 1 0 1 3 5 ///// 6 SIDE NORTH 5 SIDE SOUTH 9 11 13 15 1 MI 1■ 1111 — E KEY PLAN NOT TO SCALE THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW. CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. a 1 Cs, a 0 Uw Oz. co 2 cn 2 a Scale AS SHOWN THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES 1/8" = 1,_0„ 1 0 1 3 5 ///// 6 SIDE NORTH 5 SIDE SOUTH 9 11 13 15 1 MI 1■ 1111 — E KEY PLAN NOT TO SCALE THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW. CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. a 1 Cs, a 0 Uw Oz. co 2 cn 2 a Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P304 Sheet No. 4 of 6 N:\9157061Drawings\P305 P306.dwg, 12/31/2014 9:51:19 AM, N62 6 SIDE (NORTH) 5 SIDE (SOUTH) J-1 -NM___,-_,- - ROOF DRAINAGE DOWNSPOUT 5" CI ST DN 6 SIDE (NORTH) Me 5 SIDE (SOUTH) ELEVATOR LOBBY RD (UNDER PAVERS) PROGRAM LOUNGE PROGRAM IOUNCE 120101 STAIR STAIRS 5" CI ST DN ROOF DRAINAGE DOWNSPOUT 13591 SINGLE ROOM 135921 SINGLE ROOM 13589 SINGLE ROOM 135901 SINGLE ROOM 135871 SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM FOR AIFORMATION ONLY THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES 2" SAN UP Sc DN 13583 SINGLE ROOM SINGLE ROOM 4" V RISER SINGLE ROOM 3" SAN UP & DN 2" V 2" SAN UP & DN SINGLE ROOM 4" SAN UP & DN 135771 BATH - TOILET SINGLE ROOM 2"VUP&DN 135681 TRASH ROOM DOUBLE ROOM SINGLE ROOM SINGLE ROOM ( 35561 SINGLE ROOM 3" SAN UP & DN 3" SAN UP & DN 135541 DOUBLE ROOM 13004 STAIR 3 3" SAN UP & DN SINGLE ROOM SINGLE ROOM SINGLE ROOM 13571 SINGLE ROOM INGLE OOM 13567 SINGLE ROOM SINGLE ROOM 135631 SINGLE ROOM SINGLE ROOM 13559 135571 STORAGE SINGLE ROOM 13549) 11111111 1 3541 11111 135451 1111 pp 1, IIIII 135431 _ 11 11 11 11 3541 SINGLE ROOM il 1111 1 IP 135391 SINGLE ROOM LIME SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM (NOTE: FOURTH Sc FIFTH FLOOR SIMILAR) 13003 STAIR 2 rim 11 III�I 3504 SINGLE 135031 ROOM SINGLE I ROOM t — — I � 3506 � , 3505 11111 111 135021 SINGLE ROOM 135011 SINGLE ROOM SINGLE ROOM SINGLE ROOM 135071 SINGLE ROOM 130011 STAIR 1 SINGLE ROOM 2" SAN UP&DN 3" SAN UP&DN 3" SAN UP&DN 2" SAN DN 1 r V RISE PIPE AT CEILING TYP. 135461 CUSTODIAL KITCHENETTE 13532 SINGLE ROOM 2"VUP 135301 SINGLE ROOM 13528 SINGLE ROOM 13526 SINGLE ROOM 135221 BATH - TOILET 11111 11111 1111 111111 11 Nrall 13511 SINGLE ROOM 1111 2" SAN UP & DN 4" V UP & DN 135361 STORAGE CUSTODIAL SINGLE ROOM 135151 SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM DOUBLE ROOM 135211 DOUBLE ROOM 13519 SINGLE ROOM / t l EXISTING THIRD FLOOR PLUMBING PLAN - SOUTH SCALE: 1/8" = 1'—O" 1 0 1 1 /8" = 1'-0" 3 5 7 11 13 15 I MI e NIII I INN INN INN C } 6 SIDE NORTH 5 SIDE SOUTH 2 KEY PLAN P305 NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW. IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE 00 -a c 3 _ 0 W c 0) 0 it) 0 U) -c 4)O av 0 (.4 C c a) 0. E fa E a) N 0 0 Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON c 0 a, ce d z 8 *9-7 Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P3O5 Sheet No. 5 of 6 N:\915706\Drawings1P305 P306.dwg, 12/31/2014 9:51 6 SIDE (NORTH) MIN MN 1111= 5 SIDE (SOUTH) SINGLE ROOM SINGLE ROOM DOUBLE ROOM 136211 DOUBLE ROOM 13641 SINGLE ROOM SINGLE ROOM 2"V RISER SINGLE ROOM SINGLE ROOM SINGLE ROOM 2"VDN SINGLE ROOM SINGLE ROOM SINGLE ROOM V DN SINGLE ROOM 36361 ELEC PANELS SINGLE ROOM SINGLE ROOM 4" V RISER 36201 SINK ROOM 4"SAN UP & D STORAGE 136321 SINGLE ROOM SINGLE ROOM SINGLE ROOM 2" V RISER SINGLE ROOM SINGLE ROOM 3" SAN UP & DN SINGLE ROOM 13007] STAIRS 5 2' V RISER 4" SAN UP& DN (LAV & SH STACK) 136501 SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM 4" SAN UP & DN _679 SH STACK SINGLE ROOM SINGLE ROOM 13663 SINGLE ROOM 2"VUP& DN STAIRS 4 SINGLE ROOM 13659 SINGLE ROOM STORAGE ROOM 136521 SINGLE ROOM 2"VUP&DN 136771 SINGLE ROOM 4" SAN UP&D 36801 TRASH ROOM 13662 2"VUP& DN DOUBLE 2" V UP & DN ROOM SINGLE ROOM 13658 SINGLE ROOM SINGLE ROOM 13654 DOUBLE ROOM RISER 4" SAN UP & DN _679 WC STACK 3" SAN UP & DN SINGLE ROOM �I ] 36131 SINGLE ROOM r 99 11 136111 ROOM 11 3009 111 13609 SINGLE U P S SIRS ROOM 1111101 6 11111 11 (3608 136071 SINGLE — ROOM SINGLE ROOM 36061 . 13605] SINGLE SINGLE ROOM ROOM _ 111 It 000M — 13603 SINGLE SINGLE ROOM ROOM 3602 - 36011 SINGLEIP SINGLE ROOM ROOM 3" V RISER u I' 136791 SINGLE ROOM 4"VUP & DN 136821 SINGLE ROOM SINGLE ROOM 13684 SINGLE ROOM 36851 SINGLE ROOM 13686 SINGLE ROOM 136881 SINGLE ROOM ROOF SINGLE ROOM SINGLE ROOM 1111111111 -411•11 -411111M -IMM - ROOF DRAINAGE - DOWNSPOUT 5" CI ST DN ELEVATOR LOBBY 6 SIDE (NORTH) 5 SIDE (SOUTH) (NOTE: FOURTH & FIFTH FLOOR SIMILAR) EXISTING THIRD FLOOR PLUMBING PLAN - NORTH SCALE: 1/8" = 1'-0" 1 /8" = 1'— FOR IlVFORMAIION ONLY THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES 1 0 1 3 5 7 9 11 13 15 1 INNI 1■ 6 SIDE NORTH 5 SIDE SOUTH KEY PLAN NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW. IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE O t� —a 0 • Cl) co a es5 (� W c 0• N • - c 4f o a. co 1-1 M co '-4 0 s a) 1 0 0 THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES 1 0 1 3 5 7 9 11 13 15 1 INNI 1■ 6 SIDE NORTH 5 SIDE SOUTH KEY PLAN NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW. IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE O t� —a 0 • Cl) co a es5 (� W c 0• N • - c 4f o a. co 1-1 M co '-4 0 s a) 1 0 0 Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Revision z r:4 1 Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P3O6 Sheet No. 6 of 6