HomeMy WebLinkAbout143112 Clara DicksonCornell Universit
v
Clara Dickson Hall -Waste & Storm Line Replacement
December 31, 2014 -Construction Documents
SYMBOLS LIST & ABBREVIATIONS
SYMBOLS
DESCRIPTION
ABBR.
— -- — —
EXISTING WORK TO BE REMOVED (BOLD DASHED LINE)
EXISTING WORK TO REMAIN (LIGHT SOLID LINE)
NEW WORK (BOLD SOLID LINE)
PATCH CONCRETE FLOOR
ABOVE GROUND
SERVICE WEIGHT
NO—HUB CAST IRON
COLD WATER
CW
BELOW GROUND
(OUTDOORS)
PVC SDR 35 BELL &
SPIGOT CONFORMING TO
ASTM D3034 WITH
STIFFNESS VALUE OF 46
HOT WATER
HW
BELOW GROUND
(INDOORS)
CERAMIC TILE
HOT WATER CIRCULATING LINE
HWC
—
SAN
SANITARY OR WASTE PIPING
SAN
— — V — —
VENT PIPING
V
STORM PIPING
ST
— ST
0
CONNECT TO EXISTING
iirl
REMOVE TO THIS POINT
PIPE DROP OR DOWN
PIPE RISE OR UP
CARPET TILE
0
TOP CONNECTION
BOTTOM CONNECTION
(I)
VINYL TILE
CAP OR PLUG
E
CLEANOUT, WALL CLEANOUT
CO, WCO
I
P—TRAP
DO
O (E) FCO
EXISTING FLOOR CLEANOUT
EXISTING TO REMAIN
EX, EXIST.
(E)
FLOOR DRAIN
FLD, FD
® 0
PLUMBING CONTRACTOR
PC
GENERAL CONTRACTOR
GC
ASBESTOS CONTAINING MATERIAL
ACM
SHOWER
SH
WATER CLOSET
WC
LAVATORY
LAV
KITCHENETTE SINK
KS
DRINKING FOUNTAIN
DF
GALLONS PER MINUTE
GPM
CAST IRON PIPE
CI
BOTTOM OF PIPE
BOP
ABOVE FINISHED FLOOR
AFF
FINISHED FLOOR ELEVATION
FFE
11,5
RISER NUMBER (EXAMPLE 15)
SS
(2636A)
NUMBER IN PARENTHESES INDICATES ROOM
SERVED BY STACK
HATCHING LEGEND
HATCH PATTERN
DESCRIPTION
r.................:1
I.••••'•••'•'•'•' ' ' ' '•'•'•••••'I
SAWCUT CONCRETE FLOOR SLAB, REMOVE CONCRETE
JOINTS
PATCH CONCRETE FLOOR
ABOVE GROUND
SERVICE WEIGHT
NO—HUB CAST IRON
NO HUB FITTINGS
CHARLOTTE HEAVY DUTY
4 BAND S/S CLAMP
W/NEOPRENE GASKET
80 IN LB TYPE
BELOW GROUND
(OUTDOORS)
PVC SDR 35 BELL &
SPIGOT CONFORMING TO
ASTM D3034 WITH
STIFFNESS VALUE OF 46
COMPATIBLE WITH PIPE,
PUSH—ON TYPE
GASKETS CONFORMING
TO ASTM F477
BELOW GROUND
(INDOORS)
CERAMIC TILE
PVC FITTINGS CONFORMING
TO ASTM D2665
PURPLE PRIMER &
SOLVENT CEMENT FOR
PVC PIPE CONFORMING
TO ASTM 02564
CARPET TILE
VINYL TILE
VINYL SHEET (LINOLEUM)
GRADE CLEANOUT. SEE DETAIL
FINISHED GRADE-.
BRONZE PLUG—
C
4" SOIL PIPE GASKET -
4" TAPPED BOSS --.y
FOR BRASS PLUG
4" CAST IRON SOIL
PIPE CLEANOUT STACK
PLUMBING WORK TO BE
PERFORMED BY CITY OF ITHACA
LICENSED PLUMBER &
INSPECTED BY THE CITY OF
ITHACA. PULL PERMIT TO
INSTALL DRAIN, TRAP, &
CLEANOUT.
FLOW
8" OR 6"
REFER TO
PLANS
6"0
1:
FRESH AIR INLET
IN LAWN OR
PLANTING AREA
4" CAST IRON
SOIL PIPE
(-6" SANITARY SEWER
`---��
"lima
Chi
i•ma
Wari
Cooperative
'jd House
Akwekon
Robe f u cel
HRS Jrom
Ho+
pha
nrna
:h•
Pi DeltalPs
Dellta...
Delta
Prospect of Delta
Whit .:: Wait
WAIT AVENUE
alio
ina
es
Hall
curs
(radu it
ssi•,
(Latinoti
RAWLINGS
GREEN
Risle
Hall
Caro
ente
CRADIT FARM DRIVE
Fu -rtesn
Obs ' ; = o
1<
,cutc Plan
_RsI TY
5 ixY •l i�,ja�
Tjaden Slbiey
all Hall
SITE
Martha Va'
enssel
arage
PA
LOCATION PLAN
NOT TO SCALE
PIPING SCHEDULE
SERVICE
LOCATION
PIPING
FITTINGS
JOINTS
STORM,
SANITARY
& VENT
ABOVE GROUND
SERVICE WEIGHT
NO—HUB CAST IRON
NO HUB FITTINGS
CHARLOTTE HEAVY DUTY
4 BAND S/S CLAMP
W/NEOPRENE GASKET
80 IN LB TYPE
BELOW GROUND
(OUTDOORS)
PVC SDR 35 BELL &
SPIGOT CONFORMING TO
ASTM D3034 WITH
STIFFNESS VALUE OF 46
COMPATIBLE WITH PIPE,
PUSH—ON TYPE
GASKETS CONFORMING
TO ASTM F477
BELOW GROUND
(INDOORS)
SCHEDULE 40 PVC DWV
CONFORMING TO ASTM
D1785 & D2665
PVC FITTINGS CONFORMING
TO ASTM D2665
PURPLE PRIMER &
SOLVENT CEMENT FOR
PVC PIPE CONFORMING
TO ASTM 02564
FLOOR DRAIN SCHEDULE
TAG
DESCRIPTION
MAKE & MODEL
LOCATION
NOTES
FD -1
GENERAL SERVICE FLOOR DRAIN, DUCO CAST IRON
BODY AND GRATE, SEDIMENT BUCKET. PROVIDE
P—TRAP.
JAY R SMITH MODEL 2210
SUMP BASINS
EXTENSION TYPE CLEANOUT, DUCO CAST IRON,
W/RAISED HEAD CLOSURE PLUG, SERVICE WEIGHT.
6" CAST IRON
SINGLE VENTED
BUILDING TRAP
OUTDOOR TYPICAL BUILDING TRAP
WITH FRESH AIR INLET DETAIL 3
NOT TO SCALE
P001
CLEANOUT SCHEDULE
TYPE
DESCRIPTION
MAKE & MODEL
NOTES
FCO
CAST IRON FLOOR CLEANOUT WITH ROUND
ADJUSTABLE SCORIATED SECURED NICKEL BRONZE
TOP, TAPER THREAD AND BRONZE PLUG.
JAY R SMITH MODEL 4033E
OR EQUAL BY ZURN
PROVIDE CARPET
CLAMPING FLANGE IN
CARPET AREAS
CO
EXTENSION TYPE CLEANOUT, DUCO CAST IRON,
W/RAISED HEAD CLOSURE PLUG, SERVICE WEIGHT.
JAY R SMITH SERIES
4280 OR EQUAL BY ZURN
WCO
WALL CLEANOUT — CAST IRON SPIGOT FERRULE WITH
BRONZE TAPER THREAD PLUG, STAINLESS STEEL ROUND
COVER AND SCREW
JAY R SMITH MODEL 4422C
OR EQUAL BY ZURN
GRADE
CAST IRON EXTENSION
LENGTH VARIES, SEE
PLANS AND ELEVATIONS --�`
4"
6"
LAWN
d/d,-d-d
Ate-- 6" CONCRETE PAD
CAST IRON CLEANOUT WITH
BRONZE PLUG, JAY R. SMITH
MODEL NO. 4281
ROUND, FLANGED HOUSING WITH
HEAVY DUTY CAST IRON COVER,
JAY R. SMITH SERIES 4250
CAST IRON PIPE
OUTDOOR GRADE
CLEANOUT DETAIL
NOT TO SCALE
ADJUSTABLE TOP
AND FRAME
CARPET
5"
DRAWING LIST
CONTRACT DRAWINGS:
P001
P100
P101
P102
P200
P201
P202
TITLE SHEET, SYMBOLS, SCHEDULES, NOTES & DETAILS
UNDERFLOOR PIPING REMOVAL PLAN - NORTH
UNDERFLOOR PIPING REPLACEMENT PLAN - NORTH
FINISHES REPLACEMENT PLAN - NORTH
UNDERFLOOR PIPING REMOVAL PLAN - SOUTH
UNDERFLOOR PIPING REPLACEMENT PLAN - SOUTH
FINISHES REPLACEMENT PLAN - SOUTH
EXISTING CONDITION DRAWINGS - FOR INFORMATION ONLY:
P301
P302
P303
P304
P305
P306
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
4000 PSI READY MIX CONCRETE,
ASSUME 5" THICKNESS
FIRST FLOOR PLUMBING PLAN - SOUTH
FIRST FLOOR PLUMBING PLAN - NORTH
SECOND FLOOR PLUMBING PLAN - SOUTH
SECOND FLOOR PLUMBING PLAN - NORTH
THIRD FLOOR PLUMBING PLAN - SOUTH
THIRD FLOOR PLUMBING PLAN - NORTH
#4 DOWELS —12" LONG
6" EMBEDMENT,
3' OC ON EACH SIDE
IF OVER 4 FEET DEEP LAY BACK OR \\ \\\/
i \/
STANDARDAffill U 1926,NTS OF OSHA CONSTRUCTION, AND \/, ././. ,. ,�%i�,. , A� ,A ,;�%%r��%i�\%�\%i /A%
LOCAL LAWS. #
SHORE TRENCH IN ACCORDANCE
SANITARY OR STORM
LINE. SEE PLAN FOR
SIZE
RUN OF CRUSHED LIMESTONE
COMPACTED IN 12" LIFTS
STONE DUST
4" MINIMUM
PIPE BEDDING
DEPTH VARIES
SEE PLAN
TYPICAL BACKFILL & FLOOR PATCH DETAIL
NOT TO SCALE
NOT TO SCALE
z
4•
4 .
FLOOR SLAB
FLOOR CLEANOUT DETAIL
NOT TO SCALE
GROUND
FLOOR
P001
P001
EXISTING CAST IRON
ABOVE FLOOR
CONNECT
TO EXISTING 0
PROVIDE CLEANOUT AT
BASE OF EACH RISER
6" MIN. PVC ABOVE FLOOR
A
r
PVC BELOW FLOOR
PHASE:
YEAR1&2
YEAR 1&2
YEAR1&2
YEAR1&2
YEAR 2
YEAR 2
YEAR 2
//
//
//
//
//
//
//
//
//.
PLUMBING NOTES
1. ALL WORK SHALL CONFORM TO CORNELL UNIVERSITY DESIGN AND
CONSTRUCTION STANDARDS FOR QUALITY, MATERIALS AND
WORKMANSHIP.
2. ALL WORK SHALL CONFORM TO THE EXISTING BUILDING CODE OF NEW YORK
STATE (EBCNYS). ALL PLUMBING WORK IN THE PROJECT AREA SHALL CONFORM
TO PLUMBING CODE OF NEW YORK STATE (PCNYS), THE FIRE CODE OF NEW
YORK STATE (FCNYS), AND THE ENERGY CONSERVATION CONSTRUCTION CODE OF
NEW YORK STATE (ECCNYS). THESE DRAWINGS WERE PREPARED UNDER THE
2010 VERSIONS OF THE AFOREMENTIONED CODES. CONFIRM WITH THE CITY OF
ITHACA THE PREVAILING CODE VERSION AT THE TIME OF PERMIT ISSUE AND
COMPLY WITH THE PROVISION OF THE CURRENTLY APPLICABLE CODE AT THE
TIME OF PERMIT ISSUE.
3. ALL WORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE REQUIREMENTS
OF THE OCCUPATIONAL HEALTH AND SAFETY ACT (OSHA) AS AMENDED AND THE
REQUIREMENTS OF THE NEW YORK STATE DEPARTMENT OF LABOR.
4. CONFORM TO ALL UTILITY COMPANY RULES AND REGULATIONS.
5. BUILDING PERMIT: CONTRACTOR SHALL OBTAIN A BUILDING PERMIT
BEFORE STARTING WORK. CONTRACTOR SHALL PAY ALL
PERMIT EXPENSES.
6. THE PROJECT OCCURS WITHIN THE CITY OF ITHACA. CONTRACTOR SHALL HAVE
A VALID MASTER PLUMBER LICENSE AND SHALL PROVIDE A CITY OF ITHACA
PLUMBING PERMIT, INSPECTION AND CERTIFICATE OF COMPLETION. THE
CONTRACTOR SHALL PAY ALL FEES.
7. THIS PROJECT INCLUDES SAW CUTTING SLAB, HAND EXCAVATION AROUND PIPE,
REMOVAL AND REPLACEMENT OF UNDERFLOOR PIPE AND RESTORATION OF
SURROUNDING CONSTRUCTION AND FINISHES. REFER TO DRAWINGS AND
SPECIFICATION FOR ADDITIONAL SCOPE OF WORK.
8. PROVIDE DETAILED SUBMITTALS FOR ALL MATERIALS AND EQUIPMENT PROVIDED
UNDER THIS PROJECT.
9. PROVIDE OPERATION AND MAINTENANCE INFORMATION FOR ALL MATERIALS,
EQUIPMENT AND SYSTEM PROVIDED UNDER THIS PROJECT. SEE SPECIFICATIONS.
10. CLARA DICKSON HALL MAY BE OCCUPIED BY STAFF AND SUMMER
PROGRAMS IN THE BUILDING DURING THE CONSTRUCTION PERIOD. WATER
SERVICES WILL BE REQUIRED BY THE STAFF AND CONTRACTORS.
PROVIDE TEMPORARY SERVICES AS REQUIRED. COORDINATE SHUTDOWN
OF ONE SIDE OF THE BUILDING AT A TIME.
11. PROVIDE SIGNED, DATED, CONTRACTOR AS—BUILT DRAWINGS FOR ALL
WORK PROVIDED UNDER THIS PROJECT. MAINTAIN ONE SET OF
CONSTRUCTION DRAWINGS DENOTING ANY FIELD CHANGES WHICH ARE
MADE AS THE WORK OF THE PROJECT PROGRESSES. KEEP THESE
UPDATED. ENGINEER SHALL BE PERMITTED TO BORROW, PHOTOCOPY AND
RETURN THESE DRAWINGS AT INTERVALS THROUGH THE PROJECT.
12. NO WORK OF ASBESTOS OR HAZARDOUS MATERIAL ABATEMENT OR
REMOVAL IS INCLUDED UNDER THIS CONTRACT. CONTACT OWNER IF
SUSPECTED ASBESTOS MATERIAL ARE ENCOUNTERED.
13. INSPECTION: NOTIFY CITY OF ITHACA PLUMBING CODE COMPLIANCE
OFFICER AND PETERSON GUADAGNOLO ENGINEERS A MINIMUM OF 48
HOURS PRIOR TO TESTING PLUMBING LINES.
CONTINUOUS PLASTIC WARNING TAPE
LOCATED 12" BELOW GRADE AND ON TOP
OF 12" LAYER ABOVE SEWER. TAPE SHALL
BE 6" WIDE & LABELED "SANITARY SEWER".
RE—SEED LAWNS
d d �d d14•
COMPACTED SELECT
NATIVE MATERIAL
LAY BACK OR SHORE
TRENCH IN ACCORDANCE
WITH REQUIREMENTS OF
OSHA STANDARD 1926,
CONSTRUCTION, AND
LOCAL LAWS.
EPDXY GROUT
z �
PVC -CAST IRON PIPE
CONNECTION DETAIL
NOT TO SCALE
PIPE SLEEVE
DEPTH VARIES
/ CRUSHED STONE
,,/i,, ABOVE PIPE COMPACT
0
�
TYPICAL SANITARY
ARIES (TYP)
SEWER
LINE
TRENCH DETAIL - UNDER GRASS
NOT TO SCALE
STEEL SEALING AND
ANCHORING COLLAR
WELDED TO SLEEVE
CENTER PIPE
IN SLEEVE
SEAL SLEEVE WITH TIGHTLY
PACKED FIBERGLASS OR
'LINK—SEAL'
Or AV ABM/ AMP' AMMEMEMEMMEOM
SEAL WATERTIGHT WITH
MASTIC OR ASPHALT
/////////////Ammar ///////////MEM
I
Pir
STANDARD WEIGHT STEEL PIPE
SLEEVE
NON—SHRINK GROUT
OR EPDXY GROUT
NOTE:
PIPE SLEEVE FOR EXTERIOR
WALL ABOVE OR BELOW GRADE
CORE DRILL HOLE
AS REQUIRED
ESCUTCHEON (NOT REQUIRED IN
UNFINISHED SPACES)
INTERIOR WALL SURFACE
EXTERIOR WALL
PIPE SLEEVE DETAIL.
NOT TO SCALE
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW.
"ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION.
IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION
IT IS A VIOLATION OF THE
00
— a
0
ci
e
3 i
(� W
0•
e.L
�c
00
av
a)
C
}
2
m
V)
ra
W
tp
IL.
1ID
tI
r�0 31a
•
IPem,
�� GG
W
4,
0
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
0
N
co
r
d
z
EM4
P.T.4
z
rig
a2.1 F.
ck$
Faia.7
Ooh
ra3414
Project/Sheet Title
TITLE
Scale
AS SHOWN
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Project No.
C14151
Drawing No.
P001
YEAR1&2
Sheet No. 1 of 7
N:\915706\Drawings\P100 YR 1.dwg, 12/31/2014 9:19:48 AM, N62
(0119.
11639
SINGLE
ROOM
2" VENT
UP
3" UP
TO FD
3" SAN
TO WC
UP
4" UP
0 FCO
116371
BATHROOM
2" SAN UP
TO LAVS
46
SINGLE
ROOM
3" SAN UP
TO WC
SINGLE
ROOM
1643A
CLOSET
B.O.P. 25"±
BELOW SLAB
REMOVE
PORTION
OF WIRE
LATH
AND
PLASTER
WALL
2" SAN U
TO SH
(TYP 2
HT BULB
ROOM
■' REMOVE C.I. SAN
MIN. 6" ABOVE FLOOR
SLAB. (TYP)
SINGLE
ROOM
4" UP
(2631 B)
CLOSET
SINGLE
ROOM
SINGLE
ROOM
(2629B)
CORRIDOR -
16310
CLOSET
SINGLE SINGLE
ROOM ROOM
REMOVE PORTION
OF WIRE LATH AND
PLASTER WALL
1629A
CLOSET
CLOSET
11625
SINGLE
ROOM
" UP (2625B;
CLOSET
SINGLE
ROOM
16230
CLOSET
116211
SINGLE
ROOM
CLOSET
EXISTING HUB
DRAIN TO
REMAIN
110641
SINK
ROOM
B.O.P. 1V)±
BELOW SLAB
(E) FC0
1
10631
DATA
TC
MECHANICAL
STAIR
1648B
BIKE
STORAGE
16221
MCLLU
DEN
EXIST NG PIPE
—TO REMAIN
4" UP 1
(2630B)
SAWCUT FLOOR REFER TO
REMOVAL NOTE 1 (TYP.)
STORAGE
STORAGE
DOUBLE
ROOM
11009
STAIR
KITCHEN
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
11669
SINGLE
ROOM
11667
SINGLE
ROOM
4" UP
(2670) _
SINGLE SINGLE
ROOM ROOM
REMOVE PORTION OF WIRE LATH
AND PLASTER WALL.
SINGLE
ROOM
11659
SINGLE
ROOM
EXISTING PIPE STORAGE
TO REMAIN
11647
MAINTENANCE
1675A1
CLOSET
1673A1
CLOSET
671A
CLOSET
1669A
CLOSET
CLOSET
CLOSET
EXISTING PIPE
TO REMAIN
116151
RECREATION
ROOM
16741
DOUBLE
ROOM
1-1/2" SAN
UP TO LAV
(1679)
Q3" UP
(167 i MS)
4" UP
(_679)WC
3" SAN UP TO
WC (TYP 3)
1-1/2" SAN UP
TO LAVS (1679)
EMOVE UTILITY
SINK, STORE FOR
REINSTALLATION II
JIVttNVC
REMOVE PORTION OF WIRE
LATH AND PLASTER WALL.
2" VENT UP
(TO REI 4IN)
CORRIDOR
116621
STORAGE
.4" SAN UP t..�......
TO WC (2670)
•:1.....�
EXIST
B.O.P. 31" ±
BELOW SLAB
SUMP PIT
WITH PUMP
116501
MECHANICAL
ROOM
4
(2636A)
EXISTING 2"PUMP
DISCHARGE UP
(TO REMAIN)
3" UP TO FD
(TO REMAIN)
STORAGE
REMOVE PORTION OF r........
WIRE LATH AND I....1::::
ManPLASTER WALL.
11(}27=
K:.
EXIST. STORM
MANHOLE
EXIST. SANITARY
MANHOLE
—Z F.A.I.
•
REMOVE HOUSE TRAP,
CLEANOUT & FRESH
AIR INLET
LOCKER ROOM
CAREFULLY REMOVE
11LE SHOWER FLOORS.
REPAIR SCHLUTER
WATERPROOF SYSTEM.
COORDINATE WORK W/EXISTING
ELECTRIC/DATA OUTLETS
REMOVE CERAMIC
TILE WALL FOR
ACCESS TO WATER
PIPING
:.:�
EXIST
B.O.P. 45.5" ±
BELOW
15371
BREAK
fZ813M--
6 SIDE (NORTH)
5 SIDE (SOUTH)
r
17-
EMOVE DRAINS,
AND PIPING
SERVING SHOWERS
IN ROOM 1538
SAWCUT FLOOR REFER TO
REMOVAL NOTE 1 (TYP.)
YEAR 1 WORK
PROJECT
ROOM
2"ST UP
CORRIDOR
11534
MECHANICAL
ROOM
SERVICE
ELEVATOR
1000F
HYDRAULIC
ELEVATOR
11028
RECEIVING
5"ST RISER
RISER
j0280
YEAR 2 WORK
6 SIDE (NORTH)
5 SIDE (SOUTH)
REMOVE AND REPLACE
FLOOR DRAIN AT
BOTTOM OF SUMP
EXISTING SUMP
TO REMAIN
UNDERFLOOR PIPING. REMOVAL PLAN - NORTH
SCALE: 1/8" = 1'-0"
1 /8"
1 0 1
5 7 9 11 13 15
l
1■
REMOVAL NOTES:
1. IN AREAS SHOWN, SAWCUT FLOOR, REMOVE CONCRETE SLAB AND
HAND EXCAVATE AROUND SANITARY LINE. REMOVE PIPE AS
INDICATED ON DRAWINGS. REMOVE RISERS MINIMUM OF 6"
ABOVE FLOOR SLAB.
2. PIPING SHOWN ON DRAWINGS HAS BEEN DEVELOPED FROM
PROJECT RECORD DRAWINGS AND FIELD VERIFIED TO THE
GREATEST EXTENT POSSIBLE. CONTRACTOR SHALL VERIFY IN FIELD
ALL LOCATIONS PRIOR TO REMOVAL OF WALLS AND SAW CUTTING
OF FLOOR.
3. REMOVE, STORE AND REINSTALL PLUMBING FIXTURES AS NOTED
ON DRAWINGS.
4. CONTRACTOR SHALL REMOVE GWB, PLASTER AND CONCRETE
BLOCK WALLS AS SHOWN ON DRAWINGS TO FACILITATE PIPE
REPLACEMENT.
5. CONTRACTORS SHALL BE RESPONSIBLE TO PROTECT
ABOVE—GROUND PIPING SYSTEMS AND SURROUNDING BUILDING
SURFACES I.E. FLOORS, WALLS, ETC. CONTRACTOR SHALL
REPLACE ANY PIPE INSULATION, ABOVE GROUND PIPE, AND REPAIR
ANY SURFACES DAMAGED IN THE PERFORMANCE OF THIS PROJECT.
6 SIDE NORTH
5 SIDE SOUTH
KEY PLAN
NOT TO SCALE
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY
IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION.
LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY.
IT IS A VIOLATION OF THE
O 0
Cco
ic
AI 5
• c
0 W
C 0)
o Era
�(0)
-c
o
0.0
8
1n
a)
CTIC
c
0.
0-3
ani
E
a)
4.0
0
0
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Revision
d
z
r:4
w
Scale
AS SHOWN
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Project No.
C14151
Drawing No.
P100
YEAR1&2
Sheet No. 2 of 7
N:\915706\Drawings\P101 YR 1 UF 6 SIDE.dwg, 12/31/2014 9:30:23 AM, N62
PLUMBING FIXTURE SCHEDULE
PF #
_ FIXTURE
ABBREV
SYMBOL
= HOT
COLD
WASTE
VENT
REMARKS
MOUNTING HEIGHT
MAKE & MODEL
US -1
UTILITY SINK
US
1/2"
1/2"
3"
1 1/2"
UTILITY SINK— REINSTALL EXISTING SINK. PROVIDE P—TRAP AND FAUCET.
FAUCET— BRASS CONSTRUCTION, 8" CENTERS, BRASS VALVE BODIES, VACUUM BREAKER, INTEGRAL SUPPLY & CHECK VALVES, WALL BRACE,
PAIL HOOK, HOSE END SPOUT. METAL LEVER HANDLES, AMERICAN STANDARD 8354.112.
P—TRAP— TRAP WITH STRAINER, WALL OUTLET. THREADED 3" INSIDE FOR CAST IRON SERVICE SINK. AMERICAN STANDARD 7798.030
MS -1
MOP SINK
MS
1/2"
1/2"
3"
1 1/2"
FLOOR MOUNTED
RECEPTACLE— 24"x24"x10"H MOLDED STONE, FIAT MODEL MSB -2424
FAUCET— BRASS CONSTRUCTION, 8" CENTERS, BRASS VALVE BODIES, VACUUM BREAKER, INTEGRAL SUPPLY & CHECK VALVES, WALL BRACE, PAIL HOOK,
HOSE END SPOUT. METAL LEVER HANDLES, AMERICAN STANDARD 8354.112. PROVIDE BLOCKING FOR FAUCET MOUNTING.
ACCESSORIES— PROVIDE STAINLESS STEEL WALL GUARDS, CAPS ON ALL CURBS, MOP HANGER, HOSE & HOSE BRACKET, INTEGRAL SS CAST DRAIN BODY
AND SS COMBINATION DOME STRAINER AND LINT BASKET
O
SINGLE
ROOM
1641
SINGLE
ROOM
PROVIDE FCO (TYP.)
REFER TO DETAIL
3" SAN UP
TO WC
2" VENT
UPS
3" UP
TO FD
REPLACED
SUMMER
2012
3" SAN
TO WC
UP
4" UP
0 FCO
BATHROOM
2" SAN UP
TO LAVS
2" SAN U
TO SH
(TYP 2)7
(16351
SINGLE
ROOM
116331
SINGLE
ROOM
116291
SINGLE
ROOM
SINGLE
ROOM
116251
SINGLE
ROOM
116231
SINGLE
ROOM
SINGLE
ROOM
1
10631
DATA
162101
CLOSET
116431
SINGLE
ROOM
B.O.P. 25"±
BELOW SLAB
LII HT BULB
ROOM
4" UP
(26318)(5 dfu)
1635A
CLOSET
1631A1
CLOSET
1629A1
CLOSET
162701
CLOSET
SLOPE CO 1 /8" PER FT. MIN.
" UP(26258)
(5 dfu)
CLOSET
1623A
CLOSET
(10 dfu)
SINK
ROOM
5"(203 dfu
183 dfu)
4(178 dfu
4(173 dfu)
4" (166 dfu)
116191
TC
MECHANICAL
(71
(203 dfu)5 moo,
116751
SINGLE
ROOM
116731
SINGLE
ROOM
167501
CLOSET
1673A
CLOSET
116711
SINGLE
ROOM
EXCAVATE LAWN AREA TO INSTALL
BUILDING TRAP & PIPE. BACK FILL
AND RESEED REFER TO DETAILS 1-1/2" SAN UP
TO LAVS (1679)
116741
DOUBLE
ROOM
1-1/2" SAN
UP TO LAV
(1679)
4" UP (_679 WC,
2673A WC & TUB)
(100 dfu)
PIPING IN ROOM 1679
REPLACED SUMMER
2012
3" SAN UP TO
WC (TYP 3)
EXIST. STORM
MANHOLE
EXIST. SANITARY
MANHOLE
"
PROVIDE BUILDING
TRAP. REFER TO
DETAIL
3
P001
TO STORM
MANHOLE
116691
SINGLE
ROOM
1671A1
CLOSET I CLOSET
1669A
257 dfu)
116671
116651
SINGLE
ROOM
SINGLE
ROOM
166301
CLOSET
SINGLE
ROOM
SINGLE
ROOM
PATCH CONCRETE
FLOOR SLAB(TYP)
116451
DOUBLE
ROOM
REPLACED
DECEMBER
2012
116471
MAINTENANCE
110051
STAIR
REINSTALL UTILITY SINK. PROVIDE
SINK 1 NEW P—TRAP AND FAUCET REFER
ROOM TO PLUMBING FIXTURE SCHEDULE
C01 UP70
US -1 j : �� �'114 " VENT 6UP MS)
298 dfu)■" REMOVE AND REPLACE SHOWER
FLOORS & WATER PROOFING
' CONNECTORS TO THE WALL
411 "FAAcaikp
2" TO SH
(TYP)
115391
SAWCUT
FLOOR
PATCH
CONCRET
FLOOR
6"(249 dfu)
116621
(E)SAN (226 dfu) 5"•
(3644(6 dfu)
5" (209 dfu)
EXIST
B.O.P. 31" ±
BELOW SLAB
11648
STORAGE
4" UP
2630B)
(5 dfu)
PATCH CONCRETE
FLOOR SLAB
16488
BIKE
STORAGE
TIE INTO EXISTING RISER ABOVE
FLOOR (TYP) REFER TO DETAIL
CO \
154 UP
_622 STACK
REPLACED (156 dfu)
DECEMBER
2012 ii
MCLLU
DEN
1622A1
CLOSET 7
CO
EX 2" PUMP DISCHARGE -
RECONNECT TO SAN RISER
AT 1ST FLOOR
116501
MECHANICAL
ROOM
A
63;
FOR 1ST FLR WORK
IN THIS AREA REFER
TO
LOCKER ROOM (424 dfu)
PROVIDE PIPE SLEEVE
REFER TO DETAIL it
EXIST
B.O.P. 45.5" ±
BELOW SLAB
EXTEND NEW STORM OUTSID
OF BUILDING AND CONNECT
TO EXISTING
PATCH CONCRETE
FLOOR SLAB (TYP)
BREAK
RQOM
115361
2"ST UP
PROJECT
ROOM
100081
CORRIDOR
HOT WAT
TANK
6 SIDE (NORTH)
— — —
5 SIDE (SOUTH)
1534
MECHANICAL
ROOM
FCO
110411
SERVICE
ELEVATOR
k
"S
HYDRAULIC
ELEVATOR
�3"ST
FCO
i ='1n
FCO
L �1
•
•
•
al°
PATCH CONCRETE
FLOOR SLAB (TYP)
YEAR 1 WORK
YEAR 2 WORK
4" UP
(2636A)
(13 dfu)
6 SIDE (NORTH)
M 11011111111111 11.11111111111 111111111011 -
5 SIDE (SOUTH)
EXISTING SUMP
PROVIDE FLOOR
DRAIN AT BOTTOM
OF SUMP
FD -1
UNDERFLOOR PIPING REPLACEMENT PLAN — NORTH
SCALE: 1/8" = 1'-0"
EXISTING
o� IJ HW&CW -\
MEN'S _1
BATH ROOM
116791
0 0
(1539
STORAGE
CONNECT TO EXISTING
HW & CW AND VENT
110271
CORRIDOR
PROVIDE MOP SINK, FAUCET &
MS -1 1 ACCESSORIES REFER TO PLUMBING
FIXTURE SCHEDULE THIS DRAWING
3" SAN 1
115381
MEN'S
LOCKER ROOM
PARTIAL FIRST FLOOR PLAN
SCALE: 1/8" = 1'-0"
116181
STORAGE
STAIR
116151
116191
116191
STORAGE
RECREATION
ROOM
116171
KITCHEN
1/8" = 1'—O"
1 0 1
7 9 11 13 15
1 N — e11111
1■ — E N
NOTES:
1. REPLACE UNDERFLOOR SANITARY & STORM PIPING AS INDICATED
ON DRAWINGS. REFER TO PIPE SCHEDULE FOR PIPE MATERIALS.
2. BACKFILL AND PATCH CONCRETE FLOOR. REFER TO DETAIL
1/P001 AND SPECIFICATIONS.
3. PROVIDE NEW FLOOR CLEANOUTS AS INDICATED ON THE
DRAWINGS.
4. BOTTOM OF PIPE (B.O.P.) ELEVATIONS SHOWN WERE MEASURED
DURING THE CAMERA INSPECTION AND JETTING ON JUNE 6,
2012 AND AS NOTED ON CONTRACTOR AS—BUILT DRAWINGS FOR
THE SUMMER 2012 "6" SIDE ONLY BATHROOM RENOVATION
PROJECT.
5. PROVIDE EXTERIOR BUILDING TRAP AS NOTED ON PLANS.
6. PROVIDE CLEANOUT AT THE BASE OF EACH RISER REFER TO
DETAIL 6/P001
7. CONTRACTORS SHALL BE RESPONSIBLE TO PROTECT ABOVE—
GROUND PIPING SYSTEMS AND SURROUNDING BUILDING SURFACES
I.E. FLOORS, WALLS, ETC. CONTRACTOR SHALL REPLACE ANY PIPE
INSULATION, ABOVE GROUND PIPE, AND REPAIR ANY SURFACES
DAMAGED IN THE PERFORMANCE OF THIS PROJECT.
8. REFER TO FINISHES REPLACEMENT PLANS FOR WALLS TO BE
REPLACED.
6 SIDE NORTH
5 SIDE SOUTH
KEY PLAN
NOT TO SCALE
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY
IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION.
LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY.
IT IS A VIOLATION OF THE
O 0
—a
0
Ci
• a)
03 O) 1-
C cu O
4-1
Wm
cN
4-1
hew
C Q
O >
N ,�
T-7 Z
L m
4011
C mato 1a v Nnd- c
1
37
0
cu
c
c
a)
0.
5
a)
a)
-.
0
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
c
0
.0,
ce
d
z
a
1
,,4
FT"
Scale
AS SHOWN
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Project No.
C14151
Drawing No.
P1O1
YEAR1&2
Sheet No. 3 of 7
NO FINISHES WORK REQUIRED
FOR ROOM 1637
1639
SINGLE
ROOM
163941
CLOSET
2" VEN
UP
3" UP
TO FD
1637 1
BATHROOM
2" SAN UP
TO LAVS
SINGLE
ROOM
1063
11641 1
SINGLE
ROOM
3" SAN UP
TO WC
`83,
REPAIR WIRE LATH &
PLASTER WALL (TYP.)
REFER TO DETAI
164141
CLOSET
REPLACE
SUMMER
2012
2" SAN UP
TO SH
(TYP 2)
SINGLE
ROOM
11633
SINGLE
ROOM
SINGLE
ROOM
(26293)
16291
SINGLE SINGLE
ROOM OM
REPAIR WIRE LATH &
PLASTER WALL
CARPET TILES
1625
SINGLE
ROOM
1623
SINGLE
ROOM
1621AI
CLOSET
UP(2625B)
1623A
CLOSET
SINGLE
ROOM
CLOSET
VINY
TILE
163541
CLOSET
1631A
CLOSET
162941
CLOSET
CLOSET
1625A!
CLOSET
10641
SINK
ROOM
NOTES:
1. THIS DRAWING IS INTENDED TO SHOW RESTORATION OF
FINISHES ONLY. REFER TO DRAWINGS P100 & P101 FOR
PIPING REPLACEMENT WORK.
2. CONTRACTOR SHALL RESTORE SURROUNDING FINISHES AFTER
REPLACEMENT OF UNDERFLOOR PIPING. WORK INCLUDES
REPLACEMENT OF CARPET, CERAMIC TILE AND VINYL TILE IN
LOCATIONS SHOWN ON DRAWINGS. REPLACE STUD/ SHEETROCK
AND CONCRETE BLOCK WALLS AS NOTED ON PLANS AND AS
REQUIRED TO RESTORE TO PRECONSTRUCTION CONDITION. ALL
WALLS IN CONSTRUCTION AREA SHALL BE PAINTED, COLOR
SELECTED BY OWNER.
97
(E)FC0
TC
MECHANICAL
1005
STAIR
CONCRETE
FLOOR
164881
BIKE
STORAGE
MCLLU
DEN
CARPET TILES
26303)
1622A
11618
STORAGE
CLOSET
1619
STORAGE
1645
DOUBLE
ROOM
11617
KITCHEN
2" UP TO
SINK (1647)
11675
SINGLE
ROOM
11673
SINGLE
ROOM
116711
SINGLE
ROOM
11669
SINGLE
ROOM
REPA R WIRE LATH &
PLASTER WALL
SINGLE
ROOM
4" UP 4:
(2670)
11665 1
SINGLE
ROOM
11663
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
REPLACED
DECEMBER
2012
CLOSET
167341
CLOSET
CLOSET
166941
CLOSET
CLOSET
1663AI
CLOSET
166141
CLOSET
1659AI
CLOSET
11647
MAINTENANCE
ONCRETE
FLOOR
11648 1
STORAGE
(E)SAN —�
i1
ONCRETE FLOOR
CARPET TILES
REPAIR WALL BASE
AS REQUIRED
ONCRETE
(2636A)
PIPING IN ROOM 1
DOUBLE REPLACED SUMME
ROOM
1-1/2" SAN
UP TO LAV
(1679)
CERAMIC TILE 0 R
SCHLUTER
WATERPROOF
MEMBRANE FCO
VINYL TILE
116501
MECHANICAL
ROOM
CONCRETE
FLOOR
UP
79 SH)
OPEN & REPAIR
WALL AT RISER
3" SAN UP TO
WC (TYP 3)
1-1/2" SAN UP
TO LAVS (1679)
11679 1 2"
2" TO SH
(TYP)
3" UP
TO FD
STORAGE
CARPET TILE
ERAMIC TILE
LOCKER ROOM
2"SAN UP
TO EX.
SHOWERS
A
• titat-A&4t4t1 to ���������t�nni&4������������������mi'04 Ai min
is ■'6�
►�V41
ri►
►4►4
111
s
VINYL TILE
REPAIR WIRE LATH &
PLASTER WALL
REPAIR WALL BASE
AS REQUIRED
CARPET TILE
115371
REPAIR WALL BASE
AS REQUIREDNM MI
---
VINYL TILE
REPAIR WALL BASE
AS REQUIRED YEAR 1 WORK
CONCRETE
FLOOR
YEAR 2 WORK
11536
11535
PROJECT
ROOM
1000HI
100001
11027
CORRIDOR
HOT WATT
TANK
1534
REFER TO DWG MECHANICAL
P201 FOR WORK ROOM
IN THIS AREA � FCO
6 SIDE (NORTH) . ^
5 SIDE (SOUTH)
110411
CONCRETE
FLOOR
SERVICE
ELEVATOR
S7l, RISE
mom—
6 SIDE (NORTH)
5 SIDE (SOUTH)
FINISHES REPLACMENT PLAN - NORTH
SCALE: 1/8" = 1'-0"
/8" GWB
3-5/8"
METAL STUD
(16" 0.C.)
WIRE LATH
1/2" — 5/8" PLASTER
WIRE STUD
METAL STUD WIRE LATH
2 WALL REPLACEMENT DETAILS
P102 NOT TO SCALE
1 /8" =
ff
6 SIDE NORTH
5 SIDE SOUTH
1 0 1 3 5 7 9 11 13 15
KEY PLAN
NOT TO SCALE
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEA
ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY.
IT IS A VIOLATION OF THE
O 0
—a
01)
0
• i
a)
• a)
3 i
(� W
_.
O ._
3
- c
WO
av
v
a)
a)
c
c
a)
cn
0.
E
a)
E
a)
a>
0
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Revision
d
z
z
;7,
c‘')
'ing
°i?
z
o1�
Scale
AS SHOWN
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Project Na. C14151
Drawing No.
P102
YEAR1&2
Sheet No. 4 of 7
N:1915706\Drawings \P200 YR 2.dwg, 12/31/2014 9:01:33 AM, N62
6 SIDE (NORTH) /
MOM 5 SIDE (SOUTH)
MECHANICAL
ROOM
FCO
:
10411
SERVICE
ELEVATOR
1000F1
HYDRAULIC
ELEVATOR
1 „.-YEAR 2 WORK
�CONTINUED ON
mon minim
REMOVE GWB
WALL
"S1, RISEN
FCC`+
11028
RECEIVING
5"ST RISER
J FCO
DWG P100
MINIM
SAWCUT FLOOR, REFER TO
IOTA REMOVAL NOTE 1 (TYP.)
CORRIDOR
1
j028A1
REMOVE
WITH SOLI
TORM FD
COVER
)000E1
4" SAN UP
(2589)
-E-ST----1.---
1 '
I
I
I
4" SAN U
CAP
ABANDONED
PIPE
115271
LAUNDRY
5" STORM
RISER
a
COORDINATE WORK WITH
EXISTING FIRE ALARM DEVICE
EXIST
SANITARY
MANHOLE
FOR
R: LACEMENT
0 PIPE
ABANDONED PIPE
TO REMAIN
110251
CORRIDOR
STORM FLOOR
AtNS &
CLEANOUTS CAPPED
OFF AT FLOOR
7 --LINT TRAP
(TO REMAIN)
LAUNDRY UNDERFLOOR
PIPING TO REMAIN
EXIST
GENERATOR —�
EXIST STORM
MANHOLE /35 \
4,
REMOVE FRESH
AIR INLET
EXIST
GENERATOR PAD
z
110251
CORRIDOR
-2"ST UP
SAWCUT FLOOR, REFER TO
REMOVAL NOTE 1 (TYP.)
INT TRAP & LAUNDRY
UNDERFLOOR PIPING
(TO REMAIN
1
6 SIDE (NORTH)
NMI= MINIM NMI
5 SIDE (SOUTH)
REMOVE GWB WALL FOR
REPLACEMENT OF PIPE
REMOVE, STORE AND
REINSTALL WATER CLOSETS
EXTEND NEW
STORM OUTSIDE
BUILDING
)00TDl
WOMEN
COORDINATE WORK WITH EXI TING
TELEPHONE/DATA & ELECTRIC OUTLETS
REMOVE COUNTER & SINKS,
STORE \D REINSTAIL
® Im
Ioouol
,-PUMP
DISCI-ARGE
UP
EXIST SUMP
TO REMAIN
CORRIDOR
4" SAN UP 579
115231
115211
SUMP PIT
WITH PUMP
(TO REMAIN)
::]:MUL"I-PURPOSE
is-: ROOM
OFFICE
j521A1
BREAK
ROOM
iNN:\,\NN
REMOVE FLOOR DRAIN
AT BOTTOM OF SUMP
O4" SAN UP
(2573 FIR
ALLOW FOR REMOVAL
& REINSTALLATION
ELECTRICAL OUTLETS
F
REMOVE GWB WALL
FOR REPLACEMENT
OF PIPE
Hifl_____1520 l
ADMIN.
SUPPORT
REMOVE GWB WALL
FO REPLACEMENT
0 PIPE
11522
EQUIPMENT
ROOM
.Xy:
4" SAN UP
(2550A)
-3" SAN UP (2570):YA �� }
I'1
REMOVE CASEWORK
& SINK, STORE AND
REINSTALL
99
11524
PASSAGE
4"
000cl
MECHANICAL
ROOM
115101
DINING
SERVICES
EXISTING
(TO REMAIN)
FD
//
\-4"SAN UP
(2536A) O
)-#
(1504
COMPUTER
CENTER
11519
OFFICE
OFFICE
11 51 7 1
OFFICE
15181
VESTIBULE
(514A1
ORIENTATION
115114
RA
KITCHEN
0, 4" SAN UP REMOVE BLOCK
(25306) \ ( WALL
115031
1504B1
STORAGE
100081
GENERATOR
ROOM
ALLOW FOR REMOVAL5
& REINSTALLATION OF` ---
3 ELECTRICAL OUTLET
115131
OFFICE
REMOVE PLASTER
FOR REPLACEMEN
CONFERENCE
ROOM
SE
PIPE
RHA
OFFICES
)509A1
MECH.
ROOM
15051
VESTIBULE
11502
RESOURCE
ROOM
1 11—CORRIDOR
REMOVE BLOCK WALL
FOR REPLACEMENT OF PIPE
OFFICE
OFFICE
DIRECTOR'S
OFFICE
115121
REMOVE P0• •N OF WIRE
LATH & LAST ' WALL
FFICE
2" VENT UP
REMO
FOR 1
E BLOCK WALL
EPLACEM OF
115101
OFFICE
11506
OFFICE
OFFICE
RECEPTION
REMOVE
GWB WALL
115241
OFFICE
REMOVE, STORE AND
REINSTALL WATER CLOSETS
00TB
UNISEX
T3" SAN UP
TO WC
1-1/2" 11
SAN UP
REMOVE COUNTER & SINKS,
\ STORE AND REINSTALL
`t..— COORDINATE WALL
.04 SAN UP
. (2 25B)
ALLOW FOR REMOVAL &
REINSTALLATION OF WIREMOLD
ELECTRICAL OUTLETS
1021
VESTIBULE
I501A
OFFICE
j502AI
OFFICE
REMOVAL/REPAIR WITH GFCI
OUTLETS (TYP. 2)
UNDERFLOOR PIPING REMOVAL PLAN - SOUTH
SCALE: 1/8" = 1'-0"
1/8" = 1'-0"
1 0 1 3 5 7 9 11 13 15
I Mil EMI MI—
I • — — —
REMOVAL NOTES:
1. IN AREAS SHOWN, SAWCUT FLOOR, REMOVE CONCRETE SLAB AND
HAND EXCAVATE AROUND SANITARY UNE. REMOVE PIPE AS
INDICATED ON DRAWINGS. REMOVE RISERS MINIMUM OF 6"
ABOVE FLOOR SLAB.
2. PIPING SHOWN ON DRAWINGS HAS BEEN DEVELOPED FROM
PROJECT RECORD DRAWINGS AND FIELD VERIFIED TO THE
GREATEST EXTENT POSSIBLE. CONTRACTOR SHALL VERIFY IN FIELD
ALL LOCATIONS PRIOR TO REMOVAL OF WALLS AND SAW CUTTING
OF FLOOR.
3. REMOVE, STORE AND REINSTALL PLUMBING FIXTURES AS NOTED
ON DRAWINGS.
4. CONTRACTOR SHALL REMOVE GWB, PLASTER AND CONCRETE
BLOCK WALLS AS SHOWN ON DRAWINGS TO FACILITATE PIPE
REPLACEMENT.
5. CONTRACTORS SHALL BE RESPONSIBLE TO PROTECT
ABOVE -GROUND PIPING SYSTEMS AND SURROUNDING BUILDING
SURFACES I.E. FLOORS, WALLS, ETC. CONTRACTOR SHALL
REPLACE ANY PIPE INSULATION, ABOVE GROUND PIPE, AND REPAIR
ANY SURFACES DAMAGED IN THE PERFORMANCE OF THIS PROJECT.
6 SIDE NORTH
5 SIDE SOUTH
KEY PLAN
NOT TO SCALE
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
g
THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY
IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION.
LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY.
IT IS A VIOLATION OF THE
0th
-a
0
C5 G)
03 5
3 _
0 W
_. c
0 •-
�
11-
c
O
av
1-1
.1
c
t0
n
Ltf
M
74
ai
c
0
0.
H
v
a)
C
c
a)
Q.
E
a)
n3
E
a)
0
0
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Revision
d
z
1
r$0
dR
w
010
ta/Si
0-4 c'''3
Ooh
Scale
AS SHOWN
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Project No. C14151
Drawing No.
P200
YEAR 2
Sheet No. 5 of 7
N:\915706\Drawings\P201 YR 2 UF 5 SIDE.dwg, 12/31/2014
6 SIDE (NORTH)
5 SIDE (SOUTH)
�8.
�2,
IIJJ41
MECHANICAL
ROOM FCO
11041
SERVICE
ELEVATOR
000E1
HYDRAULIC
ELEVATOR
YEAR 2 WORK
CONTINUED ON
DWG P101
11028
RECEIVING
5"ST RISER
, rJ
CONNECT TO RISER
ABOVE FLOOR TYP.
1
10TA1
COR DOR
PATCH
CONCRETE
FLOOR
PATCH
CONCRETE
FLOOR
1028AI
REMOVE AND REPLACE
GWB ENCLOSURE FOR
REPLACEMENT OF PIPE
115271
CORRIDOR
STORM FLOOR
S &
CLEANOUTS CAPPED
OFF AT FLOOR
4.15
6 SIDE (NORTH)
5 SIDE (SOUTH)
4" SAN UP
TO FD
(TYP. 4)—
LINT
TRAP
11025
CORRIDOR
PROVIDE STRUCTURAL SUPPORT
TO GENERATOR PAD DURING
EXCACATION.
EXIST
GENERATOR --\,1/4
EXTEND NEW
OUTSIDE OF B
EXIST
GENERATOR PAD
TO REMAIN
TORM
ILDING
4" (42 dfu)
PROVIDE BUILDING TRAP. REFER
TO DETAIL
PROVIDE PIPE
SLEEVE
REFER TO
DETAIL
4" (70 dfu)
EXISTING LINT TRAP &
LAUNDRY UNDERFLOOR PIPING
TO REMAIN
EXIST SANITARY
MANHOLE
EXCAVATE LAWN AREA TO INSTALL
BUILDING TRAP AND PIPE. DO NOT
UNDERMINE GENERATOR PAD. BACK
EXIST STORM FILL AND RESEED REFER TO DETAIL
MANHOLE /-
2„ (350 dfu)
6"(280 dfu)
WOMEN
100081
REINSTALL LAVATORIES
(TYP. 3)
PAT H CONCRET
FLO R (TYP)
REINSTALL WATER CLOSET (TYP. 3
Co I -
10248
PUMPII
DISCH RGE
UP
CORRIDOR
4" SAN UP 579
PROVIDE FLOOR
DRAIN
(228 dfu) 6"
SUMP PIT
WITH PUMP—.
EXIST SUMP
115231
OFFICE
115211
I -PURPOSE
ROOM
-SLOPE 1/8" PER FT. MIN.
PASSAGE
115221
EXIST
EQUIPMENT
ROOM
1 oouCI
MECHANICAL
ROOM
REPLACE
GWB WALL FCO
3" SAN UP (2570)
�1
(220 dfu) 6"
REPLACE
GWB WALL
REINSTALL
SINK &
CASEWORK
115041
COMPUTER
CENTER
213 dfu) •"
11524
PASSAGE
(198 dfu)5
74 SLOPE ® 1/8 PER FT. MIN.
198 dfu) 5"
115201
ADIAN.
SUPPORT
15191
OFFICE
11518
OFFICE
11517
1510
4" SAN UP
(2536A)
(10 dfu)
1504A1
DINING
SERVICES
PATCH CONCRETE
FLOOR
OFFICE
11518 1
VESTIBULE
1514A
TIE INTO EXIST. RISER
ABOVE FLOOR (TYP)
REFER TO
`��
15081
110231
PASSS,GF
ORIENTATION
RA
KITCHEN
GENERATOR
ROOM
188 dfu)5"
OFFICE
CONFERENCE
ROOM
110221
4" (5 dfu
11509
RHA
OFFICES
PATCH CONCRETE
FLOOR
(172 dfu) I 1
4" 1 �►�
VESTIBULE
SLOPE O' 1/8"' PER FT. MIN.
(177 dfu) 4"
PATCH CONCRETE
FLOOR (TYP)
(5 dfu 4
11526
1509AI
MECH.
ROOM
11505
COPY
ROOM
(160 dfu)4"
• FCO
4..
411020
CORRIDOR,
4 (167 dfu)itt#• 1<: 11111
(7dfu)4" ,�
Y�, ZCAAI
115021
RESOURCE
ROOM
OFFICE
DIRECTOR'S
OFFICE
1512
OFFICE
15101
OFFICE
OFFICE
RECEPTION
2" VENT UP
115241
OFFICE
REINS WATER
CLOSETS
3" SAN UP
TO WC
100T81
UNISEX
TOILET
11
SAN UP
1-1/2"
O4 SAN UP
(2 25B)
VESTIBULE
1501A
OFFICE
1502A
OFFICE
REINSTALL
SINKS &
CASEWORK
UNDERFLOOR PIPING REPLACEMENT PLAN - SOUTH
SCALE: 1/8" = 1'-0"
1/8 =
"
1 0 1 3
7 9 11 13 15
MI E E E
■ — I 1
NOTES:
1. REPLACE UNDERFLOOR SANITARY & STORM PIPING AS INDICATED
ON DRAWINGS. REFER TO PIPE SCHEDULE FOR PIPE MATERIALS.
2. BACKFILL AND PATCH CONCRETE FLOOR. REFER TO DETAIL
1/P001 AND SPECIFICATIONS.
3. PROVIDE NEW FLOOR CLEANOUTS AS INDICATED ON THE DRAWINGS
4. PROVIDE EXTERIOR BUILDING TRAP AS NOTED ON PLANS.
5. PROVIDE CLEANOUT AT THE BASE OF EACH RISER REFER TO
DETAIL 6/P001
6. ALL PIPE SHALL BE SLOPED AT 1/8" PER FOOT MINIMUM 4" AND
ABOVE, AND 1/4" PER FOOT MINIMUM SMALLER THAN 4".
7. CONTRACTORS SHALL BE RESPONSIBLE TO PROTECT ABOVE
GROUND PIPING SYSTEMS AND SURROUNDING BUILDING SURFACES
I.E. FLOORS, WALLS, ETC. CONTRACTOR SHALL REPLACE ANY PIPE
INSULATION, ABOVE GROUND PIPE, AND REPAIR ANY SURFACES
DAMAGED IN THE PERFORMANCE OF THIS PROJECT.
8. REFER TO FINISHES REPLACEMENT PLANS FOR WALLS TO BE
REPLACED.
6 SIDE NORTH
5 SIDE SOUTH
KEY PLAN
NOT TO SCALE
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY
IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION.
IT IS A VIOLATION OF THE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY.
00
154
ci
c
co 5
(� W
C 0)
(1,",0c
W 0
0.
a)
c
O
CO
LU
t0
I
8
Zr)
a)
c
a)
a
N
E
a)
1
4)
0
0
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Revision
d
z
w
aL4
'1114
O
0_4 w
3
Ooh
Scale
AS SHOWN
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Pa's Na. C14151
Drawing No.
P201
YEAR 2
Sheet No. 6 of 7
6 SIDE (NORTH)
5 SIDE (SOUTH)
414
A of
115341
CONCRETE MECHANICAL
FLOOD- ROOM FCO <
110411
SERVICE
ELEVATOR
PROVIDE
STUD/SHEETROCK WALL
11028
RECEIVING
5"ST RISER.
icait
O•
"S
RISER
1001E1
HYDRAULIC
ELEVATOR
TANK
FCN
.4..
e a •e•*•••••••Co ♦•♦
5"
4
CONCRETE ' 14
FLOOR aai`
f ° .
°al .
1.
I. 1,
3"ST
1028A1
1q7A VINYL TILE
CORRIDOR
\`-STORM FD WITH
SOLID COVER
slat m
�3,
c
000E
5
�t—
0,4" SAN UP
(2589)
VINYL TILE
2"V UP
ST
•��e
e,
C7
115271
LAUNDRY
PROVIDE
STUD/SHEETROCK WALL
5" STORM
ISER
I
4" SAN U
4" SAN UP
TO FD
(TYP. 4)m
FCO
"ST
4"
4"
4.V*400••v♦
EXISTING LINT TRAP &
LAUNDRY UNDERFLOOR PIPING
CONTINUED
ON P200
PROVIDE
STUD/SHEETROCK WALL
ST
T
110251
CORRIDOR
STORM FLOOR
AtNS &
CLEANOUTS CAPPED
OFF AT FLOOR
—4"
LINT
TRAP T
26 1/2" HIGH
KNEE WALL CORRIDOR
11025
\--VINYL TILE
F53 HIGH WALL
I I
CARPET
TII F
CERAMIC TILE
Ii
OOTD
WOMEN
VINYL TILE
100081
MECH
REPAIR WALL AT RISER
CO TION (TYP)
Fco •ei0''ei�,4Pee•wfrfrw
e_e_e_e_e_e��.e, ee_�
115231
OFFICE
15231
PASSAGE'
4" SAN UP -� .....
%
(2573 FIR APT) . "
PROVIDE STUD/SHEETROCK WALL
CARPET
TILE
•
4" SAN UP (_579)
.. MULTI-PURPOSE'
':>ROOM
4"ST: 1J:,
-3" V
—
CARPET
TILE
38
6 SIDE (NORTH)
5 SIDE (SOUTH)
VINYL TILE
,-PUMP
DISCHARGE
UP
lif/8" GWB
3-5/8"
METAL STUD
(16" 0.C.)
111
WIRE LATH
1/2" - 5/8" PLASTER
WIRE STUD
METAL STUD WIRE LATH
WALL REPLACEMENT DETAILS
NOT TO SCALE
•• ••
eee�ieO�eiei�
/eee,eeee♦
•ss�s— •e��
• 521A eeeee•
BREA
ROO
• ,
FCO
:<. SAN • 'a
"':.:PROVIDE STUD/SHEETROCK. WALL
•
15221
e.', �'•`:'•EQUIPMENT::•':•;:
1e ROOM
e
•
:. •. 4" SAN UP;
•
•
"•.`.•}..;'•.,' 3" SAN UP (2570)
z. .
--REMOVE & REINSTALL
SINK AND CASEWORK
REPAIR WALLS
1520
ADMIN.
SUPPORT
T
11518
VESTIBULE
11519)
OFFICE
115241
PASSAGE
115181
OFFICE
CARPET
TILE -
0 :•
SUMP PIT
WITH PUMP
_1�
CONCRETE FLOOR --J
loouc
MECHANICAL
ROOM
1
•'
FCO
SAN ..
•
y"S
EXIST TO REMAIN
11510
: DINING '
`:•'SERVICES •.
1514A
CARPET TILE
00ue1
GENERATOR
ROOM
VINYL TILE
0
CARPET
TILE
110221
ORIENTATION •✓ ' • "•.•
".
VESTIBULE
G
4" SAN UP O
(2536A)
`-- CONCRETE
FLOOR
110231
PASSAGE
•
115116
RA
KITCHEN
-VINYL
SHEET
T�
0, 4" SAN UP
(2530B)
PROVIDE PATCH OF
LT
CONCRETE BLOCK WALL
DEPTH VARIES
i --
(MATCH EXISTING)
CONCRETE BLOCK
AINT ROOM SIDE
NOTES:
1. THIS DRAWING IS INTENDED TO SHOW RESTORATION OF
FINISHES ONLY. REFER TO DRAWINGS P200 & P201 FOR
PIPING REPLACEMENT WORK.
2. CONTRACTOR SHALL RESTORE SURROUNDING FINISHES AFTER
REPLACEMENT OF UNDERFLOOR PIPING. WORK INCLUDES
REPLACEMENT OF CARPET, CERAMIC TILE AND VINYL TILE IN
LOCATIONS SHOWN ON DRAWINGS. REPLACE STUD/ SHEETROCK
AND CONCRETE BLOCK WALLS AS NOTED ON PLANS AND AS
REQUIRED TO RESTORE TO PRECONSTRUCTION CONDITION. ALL
WALLS IN CONSTRUCTION AREA SHALL BE PAINTED, COLOR
SELECTED BY OWNER.
/ 3 l CONCRETE BLOCK WALL REPLACEMENT SECTION DETAIL
NOT TO SCALE
115131
OFFICE
REPAIR PLASTER
WALL CHASE
CONFERENCE •
'..•ROOM ,;...,:
•
• :
REPAIR WALL BASE AT
PIPING CROSSING (TYP)
'•' -CARPET
•:..1• `: TILE
•
115091
RHA
OFFICES
4
1509A1
MECH.
ROOM
CONCRETE
FLOOR
SAN
115051
COPY
CARPET TILE -•h ROOM
115041
COMPUTER
CENTER
FCO'
S
110201 • .::' ..:
CORRIDOR' <•••'
•
:11526 f'
•`11524
OFFICE
OFFICE
•
3" SAN UP
TO WC
UNISEX
TOILET
CERAMIC TILE
FCO
•
2 VENT UP
11516
DIRECTOR'S
OFFICE
CARPET
%4" SAN UP
(2529B)
OFFICE ••
CARPET
TILE
3" SAN
OFFICE
PROVIDE PATCH
OF CONCRETE
BLOCK WALL
11503
STORAGE
Fu FCO
11501
15048
PROVIDE STUD/SHEETROCK
WALL (TYP) REFER T0,
4" SAN UP
(_522 STACK)
CARPET
TILE
RECEPTION
REPAIR WIRE LATH &
PLASTER WALL
SAN UP
PROVIDE PATCH OF
CONCRETE BLOCK WALL
REFER TO DETAIL
FINISHES REPLACEMENT PLAN - SOUTH
() 4" SAN UP
PROVIDE STUD/SH
ROCK WALL
11021
VESTIBULE
2
P202
11502
RESOURCE
ROOM
i 500
OFFICE
150281
OFFICE
1502A1
OFFICE
9 11 13 15
I NM 1111 Ell 1111
I • Ell Ell Ell
6 SIDE NORTH
5 SIDE SOUTH
KEY PLAN
NOT TO SCALE
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY
IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION.
LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY.
IT IS A VIOLATION OF THE
co
111
co
1-1
CO
1
,$k
.13
rL.•0
'114
0
cs)
)c7,4
Scale
AS SHOWN
Date
12/31/14
Drawn
KA. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Project No
C14151
Drawing No.
P2O2
YEAR 2
Sheet No. 7 of 7
N:\915706\Drawings\P301_P302.dwg, 12/31/2014 9:
6 SIDE (NORTH)
5 SIDE (SOUTH)
SERVICE
ELEVATOR
HYDRAULIC
ELEVATOR
I in is
5' ST UP & DN
SAN PIPE
(SERVES RM 26
110281
6 SIDE (NORTH)
5 SIDE (SOUTH)
RECEIVING
CORRIDOR
5" ST UP & DN
STAIR
ROOF AT 2ND
FLOOR LEVEL
ho28PI
4" SAN DN
(2589 & 2689)
hooUE
hooUE
15271
4 SAN UP
Ti WC
SAN PIPE
(SERVES 'M 2589)
CORRIDOR
2" VENT UP
11527
LAUNDRY
3"SN UP
TO F
2" ST UP TO RD
44
5" STUP&DN
II 11A111111111
C-- 2" SAN UP
TO SH (TYP 2)
FOR INFORMA11ON ONLY
THIS DRAWING SHOWS EXISTING CONDITIONS AND
IS INTENDED FOR USE AS REFERENCE ONLY.
WORK TO BE PERFORMED FOR THIS PROJECT IS
SHOWN ON DRAWING P001 AND DRAWINGS OF
THE P100 & P200 SERIES
PIPE AT CEILING
(TYP.)
110251
CORRIDOR
hooud
4" SAN UP&DN
(_579 & 2573 FIR)
1-1/2" SAN
UP TO TUB
h0240
2" PU
DISCHA
CORRIDOR
3" SA UP
TO WC
MULTI—PU
ROO
h521A
BREAK
ROOM
OFFICE
MECHANICAL
ROOM
EXISTING SPLIT SYSTEM AIR
CONDITIONER WITH INTEGRALI
CONDENSATE PUMP (TYP).
EXISTING
SINK DRAIN
PUMP
3 SAN UP
TO FD
3" VENT
STACK
115201
AEMN.
SUPPORT
2" SAN UP
TO SH
3" SAN DN
(2570)
3" SAN UP
TO WC
115221
EQUIPMENT
ROOM
4" SAN DN
(2550A)
AD FOR CO
115041
COMPUTER
CENTER
EXISTING 3/4" AC
DRAIN ABOVE CEILING
PASSAGE
4" SAN UP
(2536A)
1-1/2" SAN UP
TO SINK
DINING
SERVICES
EXISTING
DRAIN HUB
OFFICE
115181
OFFICE
OFFICE
VESTIBULE
OFFICE
11508
110231
PASSAGE
ORIENTATION
RA
KITCHEN
4' SAN DN
(2530B)
h 50481
11503
STORAGE
2" SA
GENERATOR
ROOM
2" SAN UP
115131
OFFICE
3" SAN UP
TO WC
RHA
OFFICES
CONFERENCE
ROOM
h5o9A1
PIPE AT CEILING
(TYP.)
MECH.
ROOM
3" U
TO W0
COPY
ROOM
3" SAN
TO FD
VESTIBULE
110211
11 020 1
4" SAN UP&DN
(_522 STACK)
3" SAN UP
(_522 SH STA
15021
CORRIDOR
LOWER
LOBBY
OFFICE
OFFICE
4" SAN UP
4" SAN UP
DIRECTOR'S
OFFICE
115121
OFFICE
11506
OFFICE
OFFICE
RECEPTION
115241
4 4" SAN DN
(2529B)
1-1/2" SAN UP
OFFICE
4" SAN DN
(25258)
UNISEX
TOILET
110211
VESTIBULE
OFFICE
115024
OFFICE
o
EXISTING FIRST FLOOR PLUMBING PLAN - SOUTH
SCALE: 1/8" = V-0"
1 0 1
1/8" = 1'-0"
3
5
7
11 13
15
1 _ — E INN
1■ = E
5 SIDE SOUTH
2
KEY PLAN
P301
NOT TO SCALE
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW.
IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION.
Q
LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THS DOCUMENT IN ANY
IT IS A VIOLATION OF THE
00
-a
0
Ci
cm 00
• 5)
• C
0
0)
o• �
Wv+
4.0c
4) o
av
•
M 4)
co a)
tp C
• c
a
ai
oE
aa)
N .CD
I- a)
Philip A. Peterson
NYS PE LICENSE # 59561
N
0
0
a
THIS DRAWING SHOWS EXISTING CONDITIONS AND
IS INTENDED FOR USE AS REFERENCE ONLY.
WORK TO BE PERFORMED FOR THIS PROJECT IS
SHOWN ON DRAWING P001 AND DRAWINGS OF
THE P100 & P200 SERIES
PIPE AT CEILING
(TYP.)
110251
CORRIDOR
hooud
4" SAN UP&DN
(_579 & 2573 FIR)
1-1/2" SAN
UP TO TUB
h0240
2" PU
DISCHA
CORRIDOR
3" SA UP
TO WC
MULTI—PU
ROO
h521A
BREAK
ROOM
OFFICE
MECHANICAL
ROOM
EXISTING SPLIT SYSTEM AIR
CONDITIONER WITH INTEGRALI
CONDENSATE PUMP (TYP).
EXISTING
SINK DRAIN
PUMP
3 SAN UP
TO FD
3" VENT
STACK
115201
AEMN.
SUPPORT
2" SAN UP
TO SH
3" SAN DN
(2570)
3" SAN UP
TO WC
115221
EQUIPMENT
ROOM
4" SAN DN
(2550A)
AD FOR CO
115041
COMPUTER
CENTER
EXISTING 3/4" AC
DRAIN ABOVE CEILING
PASSAGE
4" SAN UP
(2536A)
1-1/2" SAN UP
TO SINK
DINING
SERVICES
EXISTING
DRAIN HUB
OFFICE
115181
OFFICE
OFFICE
VESTIBULE
OFFICE
11508
110231
PASSAGE
ORIENTATION
RA
KITCHEN
4' SAN DN
(2530B)
h 50481
11503
STORAGE
2" SA
GENERATOR
ROOM
2" SAN UP
115131
OFFICE
3" SAN UP
TO WC
RHA
OFFICES
CONFERENCE
ROOM
h5o9A1
PIPE AT CEILING
(TYP.)
MECH.
ROOM
3" U
TO W0
COPY
ROOM
3" SAN
TO FD
VESTIBULE
110211
11 020 1
4" SAN UP&DN
(_522 STACK)
3" SAN UP
(_522 SH STA
15021
CORRIDOR
LOWER
LOBBY
OFFICE
OFFICE
4" SAN UP
4" SAN UP
DIRECTOR'S
OFFICE
115121
OFFICE
11506
OFFICE
OFFICE
RECEPTION
115241
4 4" SAN DN
(2529B)
1-1/2" SAN UP
OFFICE
4" SAN DN
(25258)
UNISEX
TOILET
110211
VESTIBULE
OFFICE
115024
OFFICE
o
EXISTING FIRST FLOOR PLUMBING PLAN - SOUTH
SCALE: 1/8" = V-0"
1 0 1
1/8" = 1'-0"
3
5
7
11 13
15
1 _ — E INN
1■ = E
5 SIDE SOUTH
2
KEY PLAN
P301
NOT TO SCALE
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW.
IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION.
Q
LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THS DOCUMENT IN ANY
IT IS A VIOLATION OF THE
00
-a
0
Ci
cm 00
• 5)
• C
0
0)
o• �
Wv+
4.0c
4) o
av
•
M 4)
co a)
tp C
• c
a
ai
oE
aa)
N .CD
I- a)
Philip A. Peterson
NYS PE LICENSE # 59561
N
0
0
a
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
(flecked
P.A. PETERSON
c
0
1
0
Z
1
„T.,
.?.1
ca)
14
'14 g
a
a °e''
0-4 W
3
o �U
c
1
Scale
AS SHOWN
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
(flecked
P.A. PETERSON
Project No. C14151
Drawing No.
P301
Sheet No. 1 of 6
THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW.
THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION.
LI)
z
C9
N
CL
w
2
1-
m
Li)
O
J
O
w
cc
LLJQ
z
0
0
z
w
1-
0
z
J
v)
cc
w
1-
Q
J
1
(1)J
z
0
(7
N
O
a
O
Z
w
J
w
1-
0
w
w
J
U-
00
—a
0
M
cos
3_
0w
CV. 3
0)
• u)
+� c
CD
a.
1-1
CO
tp
N
1n
N
c
.0'
c
a)
0'
0.
0)
E
0
0
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Revision
d
Z
a
z
z
z
w
0
0
0
N
1—
w
J
0
U.1
w
z
z
w
0
w
z
w
U
J
w
O
z
O
w
0
w
w
0
z
0
U
O
V)
a.O
w
IT IS A VIOLATION OF THE
N:\915706\Drawings\P3012302.dwg, 12/31/2014 9:4
6 SIDE (NORTH)
5 SIDE (SOUTH)
16391
SINGLE
ROOM
1-1/2"V
116394
CLOSE
BATHROOM
1-1/2" SAN
UP TO LAV
SINGLE
ROOM
4" SAN
UP TO WC
SINGLE
ROOM
h641P1
SINGLE
ROOM
CLOSET
116434
CLOSET
4" SAN DN
(26318)
11081
LINEN
CLOSET
SINGLE
ROOM
4" SAN
UP TO
1-1/2" SAN
UP TO TUB
I�
1-1/2" SAN
UP TO LAV
SINGLE
ROOM
16311
SINGLE
ROOM
116291
SINGLE
ROOM
1-1/2" SAN
UP TO TUB
SINGLE
ROOM
SINGLE
ROOM
116231
SINGLE
ROOM
16218
CLOSET
4" SAN DN
(2625B)
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
h 6270
CLOSET
1162501
SINK
ROOM
CLOSET
110311
4" SAN DN
(2629B)
CORRIDOR
4" WC SAN
STACK
4" SAN DN
(_622 STACK)
3" SAN UP
110621
TC
(_622 SH STACK) MECHANICAL
110081
STAIR
3" SAN UP TO
WC (TYP 3)
4" SAN
UP TO WC
3" SAN UP
IPE AT CEILING TYP.
1-1/2" SAN h648B
UP TO TUB BIKE
STORAGE
1-1/2" SAN
UP TO SINK
(2624)
MCLLU
DEN
3" SAN UP
TO FD
2" SAN
UP TO LAV
2" SAN
UP TO LAVS
CLOSET
2" SAN UP TO
SH (TYP 3)
STORAGE
DOUBLE
ROOM
4" SAN DN
(2630B)
4" SAN UP
(LAV&SH STACK)
110091
STAIR
KITCHEN
SNGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
SNGLE
ROOM
SINGLE
ROOM
16611
SINGLE
ROOM
h 64801
STORAGE
SINGLE
ROOM
STORAGE
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
h 665A
CLOSET
1166304
2" SAN
UP TO
LAVS
CLOSET
CLOSET
CLOSET
4" SAN UP
TO WC
16151
RECREATION
ROOM
°k_1-1/2" UP
(SINK -2673)
4" SA DN
(2636
2"PUMP DISCHARGE D
4" SAN UP & DN
(_679 SH STACK)
SINK
ROOM
2"SAN UP
TO SH
1166
STORAGE
DOUBLE
ROOM
3"SAN TO
WC (2673A)
1-1/2" SAN
UP TO TUB 2673A
2"SAN UP
TO LAVS
(2673A)
4" SAN DN
(2670 & 2650A)
2" SAN
UP TO
LAVS
(2650A)
11650
MECHANICAL
ROOM
4" SAN UP & D
(_679 WC STACK
4" SAN UP TO
WC TYP 3
MEN'S
BATH ROOM
STORAGE
CORRIDOR
4" VENT
STACK
MEN'S
LOCKER ROOM
BREAK
ROOM
2"SAN UP
TO LAVS
PIPE AT CEILING TYP.
3"SAN UP
TO WC
PROJECT
ROOM
N UP
• FD
2"SAN UP
TO UR
e --•k.„,.2" ST DN
52
2"SAN UP
TO SH
(TYP 2) 2" VENT
115341 CONTINUED •
MECHANICAL DRAWING " 102
ROOM UP
5"STUP&DN
111 SAN PIPE
(SERVES RM 26:-9)
h000F1
SPRINKLER
ROOM
hooud
1102)1
CORRIDOR
HOT WATER
TANK
10411
SERVICE
ELEVATOR
11000F
52
2" ST UP TO RD
HYDRAULIC
ELEVATOR
MEI
6 SIDE (NORTH)
5 SIDE (SOUTH)
EXISTING FIRST FLOOR PLUMBING PLAN -NORTH
SCALE: 1 /8" = 1'-0"
1 /8" = 1'-0"
FOR AIFORMATION ONLY
THIS DRAWING SHOWS EXISTING CONDITIONS AND
IS INTENDED FOR USE AS REFERENCE ONLY.
WORK TO BE PERFORMED FOR THIS PROJECT IS
SHOWN ON DRAWING P001 AND DRAWINGS OF
THE P100 & P200 SERIES
1 0 1
3
5
7
9
11
6 SIDE NORTH
5 SIDE SOUTH
J tJ
13
15
1
1■
KEY PLAN
NOT TO SCALE
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
1
Pg
Scale
AS SHOWN
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Project No. C14151
Drawing No.
P3O2
Sheet No. 2 of 6
N:\915706\Drawings\P303_P304.dwg, 12/31/2014 9:50:21 AM, N62
6 SIDE (NORTH)
5 SIDE (SOUTH)
4Q
1
2597
COMPLEX
CONGRESS
5" ST UP
ROOF DRAIN
25951
STUDY
125951
STUDY
125931
STUDENT
STAFF
5" ST
UP & DN
5" ST DN
4"SAN DN
3"V UP
5" ST UP & DN
125911
DOUBLE ROOM
125910
CLOSET
r
2010
STAIR
SINGLE
7\ /\_ ROOM
12692A
CLOSET
RD
3"SAN DN
1200001
STORAGE
125914
CLOSET
L
Adis
II FD
2"V DN
2" SAN DN
(TYP 2)
12589
- BATH
ROOM
125871
SINGLE
ROOM
1258741
CLOSET
125851
SINGLE
ROOM
125850
CLOSET
2"SAN UP
12583
SINGLE
ROOM
12583A
CLOSET
125941
125941
PROGRAM
LOUNGE
1
0
0
VESTIBULE
12592/1
CLOSET
2"SAN DN
2" V RISE
120271
CORRIDOR
3"SAN UP
PIPE AT CEILING TYP.
125811
125810
CLOSET
FACULTY -IN -
RESIDENCE
125921
SINGLE
ROOM
0
RD
/4� 0
I2590Pl
CLOSET
125901
SINGLE
ROOM
1256801
CLOSET
2588
SINGLE
ROOM
12586/1
CLOSET >
12586
SINGLE
ROOM
124E
CLOSET CLOSET
J
4" VENT
2"SAN UP
1-1/2"
SAN DN
12573
FACULTY -IN
RESIDENCE
12573
FACULTY -IN -
RESIDENCE
1257311
CLOSET
120381
CORRIDOR
125810]
CLOS€F
C
12573d
BATH
ROOM
J L
3"V UP
& DN
00
00
1-1/2"
isSAN DN
0 125730
1
0
12584
DOUBLE
ROOM
4" SAN
STACK (_579)
(25821
DOUBLE
ROOM
3" SAN DN
/"\_
125824
CLOSET
12582A
CLOSET
a r-2"SAN
2" V RI
v .L
FACULTY -IN -
RESIDENCE
N
FD
2"V UP -
12570
BATH
ROOM
2"V DN
125711
DOUBLE
ROOM
.
6 SIDE (NORTH)
5 SIDE (SOUTH)
5
12004
STAIR 3
2" SAN DN
4" SAN DN
(TYP 3)
f L J�L�L
12552
CONTROL
OFFICE
DN
3" SAN DN
12027
CORRIDOR
12569
SINGLE
ROOM
2"VUP
12025
VESTIBULE
120261
1255011
WOMENS
TOILET
2550
TOILET ROOM
VESTIBULE
0
2" SAN DN
2"V UP
125371
LOUNGE
12401
LI ING
ROM
4" SAN DN
(TYP 2)
2"VUP
2" SAN DN
125351
STUDY
125331
GROUP
STUDY
12538
PANTRY
0
(2536
BIKE
ROOM
2536/1
MENS
TOILET
it
2003
STAIR 2
UP
12024
PASSAG
125341
SINK
ROOM
125321
STORAGE
530
PRIVATE
BATH
2" V UP
12530
BED
ROOM
2" SAN DN
125300
CLOSET
125300
CLOSET
2" SAN DN
2"VUP
25301
3"SAN DN LIVING
ROOM
2" V DN
120231
CORRIDOR
12531
RHD
125314
BED
ROOM
2" V UP
1252901
BED
ROOM
4" SAN DN
'529:
PRIVATE
BATH
2529E1
HALL
125290
CLOSET
125290
CLOSET
2022
VESTIBULE
FOR INFORMA11ON ONLY
THIS DRAWING SHOWS EXISTING CONDITIONS AND
IS INTENDED FOR USE AS REFERENCE ONLY.
WORK TO BE PERFORMED FOR THIS PROJECT IS
SHOWN ON DRAWING P001 AND DRAWINGS OF
THE P100 & P200 SERIES
125021
SINGLE
ROOM
250201
CLOSET
1250441
CLOSET
125041
SINGLE
ROOM
125061
SINGLE
ROOM
125064
CLOSET
12508
SINGLE
ROOM
12508/1
CLOSET
2" SAN DN
UP
120011
STAIR 1
2"V UP
2" SAN DN
2" SAN
125261
SINGLE
ROOM
PIPE AT CEILING TYP.-----y
12529
LIVING
ROOM
Gil
12526
CLOSET
1 1/2"
SAN DN
125271
125241
KITCHEN
3" UP
J TO WCO
0 � 0 0 0
°.4`2" SAN DN
25221
BATH/TOILET
ROOM
4" V U
CUSTODIAL
2" V UP
12525A
CLOSET
1
4" SAN DN
1525:
PRIVATE
BATH
12525
PROGRAM
ASST.
12523/1
CLOSET
125231
SINGLE
ROOM
UI
1-1
�4" SANh �._ 3" SAN
UP&DN UP&DN
CORRIDOR
120201
12521
F--7 HOUSE MAID
):(I CLOSET
EXISTING SECOND FLOOR PLUMBING PLAN - SOUTH
SCALE: 1 /8" = 1'-0"
12519E
CLOSET
3" SAN D
125191
DOUBLE
ROOM
CLOSET
125011
SINGLE
ROOM
1250141
CLOSET
12503/1
CLOSET
125031
SINGLE
ROOM
1250541
CLOSET
\ Y
125051
SINGLE
ROOM
1250701
CLOSET
125071
SINGLE
ROOM
125094
CLOSET
2509
SINGLE
ROOM
12511
SINGLE
ROOM
CLOSET
12513A1
CLOSET
\ v
125131
SINGLE
ROOM
(25151
SINGLE
ROOM
1251591
CLOSET
127171
DOUBLE
ROOM
12517E
CLOSET
12517A
CLOSET
1 /8" = 1'-O"
1 0 1
3
7 9 11 13 15
1 M 011111
1■ 1
L
6 SIDE NORTH
5 SIDE SOUTH
2 KEY PLAN
P303
NOT TO SCALE
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW.
LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY.
IT IS A VIOLATION OF THE
d1
8
so o r-1 i
N c
1 1 C
,�-1 Q
CU ��z
ifi
v0) O a)
ea
to I— N
CNGR 373
* it ''o
f:::
"3-
,0, --
.e0,
73"F I R PC046C
I
0
0
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
0
70
d
z
1
c7
649
t )4
`a'
0 oz
1
Scale
AS SHOWN
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Project No. C14151
Drawing No.
P3O3
Sheet No. 3 of 6
00
-a
0
C
C5 a)
3 _
0 W
0)
O
N
L.N
+� c
WO
av
1-4
1 �
r-1
N M
Q L
O >' Ln
rl
031 N
m Z 4)
V) V) O
CEI —C
W U Q.
V
N
c
4)
fl.
a
E
0)
0
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Revision
0
z
a
>a
z
Z
w
U
0
0
N
S
1-
Q
O
w
w
Z
z
w
0
w
z
w
0
J
L.
0
z
0
0
w
0
w
1-
cc
w
0
Z
w
J
O
cc
d
w
IT IS A VIOLATION OF THE
N:\915706\Drawings\P303_P304.dwg, 12/31/2014 9:
1
6 SIDE (NORTH)
5 SIDE (SOUTH)
\9�
1-1/2"
SAN DN
1-1/2"
SAN DN
1
CLOSET
STUDY
ROOM
12619
DOUBLE
ROOM
DOUBLE ROOM
PRIVATE
BATH
4" SAN DN
625
PRIVATE
BATH
83 I
82 P
111
1-1/2"
1SAN DN
BED
ROOM
4" SAN DN
PRIVATE
BATH
BED ROOM
2" V UP
CLOSET
12629C
CLOSET
126294
LIVING 4" SAN DN
ROOM
LINEN
CLOSET
26251
RESIDENT
ADVISOR
2"VUP
CLOSET
3" SAN UP & DN
CLOSET
12623A
CLOSET
2621
HOUSE MAID
�LOSET
126351
ARD
OFFICE
120321
CORRIDOR
4"VUP
126191
CLOSET
619A1
CLOSET CLOSET
4" SAN UP & DN
PASSAGE
STACK)
4" SAN UP & DN
(SH STACK)
CLOSET
SINGLE
ROOM
CLOSET
CLOSET
SINGLE
ROOM
CLOSET
BED ROOM
LIVING
ROOM
1-1/2"
SAN DN
VESTIBULE
SINGLE
ROOM
3" SAN UP & D
KITCHENETTE
CLOSET
SINGLE
ROOM
0
3" SAN UP & DN
V RISER
4" SAN UP & DN
(_622 LAV & SH STACK)
STAIR 2N
1
LOUNGE
T
12677
12669A
CLOSE
SINGLE
ROOM
DOUBLE
ROOM
12669
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
CLOSET
2" SAN DN
2" V RISE
FOYER
CLOSET
126754
CLOSET
SINGLE
ROOM
SINGLE
ROOM
1-1/2"
SAN DN
LOSET
LIVING
ROOM
120281
CORRIDOR
HOUSE MAID
CLOSET
�J
TOILET ROOM
VESTIBULE
4" SAN DN
4" SAN DN
(TYP. 3)
SINGLE
ROOM
126031
SINGLE
ROOM
CLOSET
2" SAN UP
TO SH DRAIN
TYP. 5
DOUBLE
ROOM
'b 3" SAN DN
CLOSET
1-1/2"
SAN DN
PIPE AT CEILING TYP.
3" SAN UP
(_679 LAV STACK)
TYP.
12681E[
CLOS
3" UP
TO FD
TYP. 2
126801
CONTROL
OFFICE
VESTIBULE
WOMENS
TOILET
2" SAN DN
2" V RISE
LIVING
ROOM
26021
CLOSET
CLOSET
SINGLE
ROOM
SINGLE
ROOM
DOUBLE
ROOM
4" SAN UP & DN
(_679 WC STACK)
DOUBLE
ROOM
CLOSET
4" VENT
STACK
111
CLOSET
CLOSET
126831
SINGLE
ROOM
DOUBLE
ROOM
CLOSET
CLOSET
CLOSET
2685A1
CLOSET
686t1
CLOSET CLOSET
SINGLE
ROOM
SINGLE
ROOM
2"SAN DN
CLOSET
12688A1
CLOSET
126861
SINGLE
ROOM
126881
SINGLE
ROOM
12689
CLOSET
126904
SINGLE
ROOM
CLOSET
26921
SINGLE
ROOM
12692A
CLOSET
RD
53
125971
COMPLEX
CONGRESS
5" ST
UP & DN
5" ST UPTTO
ROOF DRAIN
125941
r
12595
CTI IDY
5" ST DN
6 SIDE (NORTH)
5 SIDE (SOUTH)
EXISTING SECOND FLOOR PLUMBING PLAN - NORTH
SCALE: 1 /8" = 1'-0"
FOR 1NFORMA11ON ONLY
THIS DRAWING SHOWS EXISTING CONDITIONS AND
IS INTENDED FOR USE AS REFERENCE ONLY.
WORK TO BE PERFORMED FOR THIS PROJECT IS
SHOWN ON DRAWING P001 AND DRAWINGS OF
THE P100 & P200 SERIES
1/8" = 1,_0„
1 0 1
3
5
/////
6 SIDE NORTH
5 SIDE SOUTH
9 11 13 15
1 MI
1■ 1111 — E
KEY PLAN
NOT TO SCALE
THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW.
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
a
1
Cs,
a
0
Uw
Oz.
co 2
cn
2
a
Scale
AS SHOWN
THIS DRAWING SHOWS EXISTING CONDITIONS AND
IS INTENDED FOR USE AS REFERENCE ONLY.
WORK TO BE PERFORMED FOR THIS PROJECT IS
SHOWN ON DRAWING P001 AND DRAWINGS OF
THE P100 & P200 SERIES
1/8" = 1,_0„
1 0 1
3
5
/////
6 SIDE NORTH
5 SIDE SOUTH
9 11 13 15
1 MI
1■ 1111 — E
KEY PLAN
NOT TO SCALE
THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW.
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
a
1
Cs,
a
0
Uw
Oz.
co 2
cn
2
a
Scale
AS SHOWN
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Project No.
C14151
Drawing No.
P304
Sheet No. 4 of 6
N:\9157061Drawings\P305 P306.dwg, 12/31/2014 9:51:19 AM, N62
6 SIDE (NORTH)
5 SIDE (SOUTH)
J-1
-NM___,-_,- -
ROOF DRAINAGE
DOWNSPOUT
5" CI ST DN
6 SIDE (NORTH)
Me
5 SIDE (SOUTH)
ELEVATOR
LOBBY
RD
(UNDER
PAVERS)
PROGRAM
LOUNGE
PROGRAM
IOUNCE
120101
STAIR
STAIRS
5" CI ST DN
ROOF DRAINAGE
DOWNSPOUT
13591
SINGLE
ROOM
135921
SINGLE
ROOM
13589
SINGLE
ROOM
135901
SINGLE
ROOM
135871
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
FOR AIFORMATION ONLY
THIS DRAWING SHOWS EXISTING CONDITIONS AND
IS INTENDED FOR USE AS REFERENCE ONLY.
WORK TO BE PERFORMED FOR THIS PROJECT IS
SHOWN ON DRAWING P001 AND DRAWINGS OF
THE P100 & P200 SERIES
2" SAN UP
Sc DN
13583
SINGLE
ROOM
SINGLE
ROOM
4" V RISER
SINGLE
ROOM
3" SAN UP
& DN
2" V
2" SAN UP
& DN
SINGLE
ROOM
4" SAN UP
& DN
135771
BATH -
TOILET
SINGLE
ROOM
2"VUP&DN
135681
TRASH
ROOM
DOUBLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
( 35561
SINGLE
ROOM
3" SAN UP & DN
3" SAN UP & DN
135541
DOUBLE
ROOM
13004
STAIR
3
3" SAN UP
& DN
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
13571
SINGLE
ROOM
INGLE
OOM
13567
SINGLE
ROOM
SINGLE
ROOM
135631
SINGLE
ROOM
SINGLE
ROOM
13559
135571
STORAGE
SINGLE
ROOM
13549)
11111111
1 3541
11111
135451
1111
pp 1,
IIIII
135431 _
11
11
11
11 3541
SINGLE
ROOM il
1111
1 IP
135391
SINGLE
ROOM
LIME
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
(NOTE: FOURTH Sc FIFTH FLOOR SIMILAR)
13003
STAIR
2
rim
11
III�I
3504
SINGLE 135031
ROOM SINGLE
I ROOM
t — —
I
� 3506 � , 3505
11111
111
135021
SINGLE
ROOM
135011
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
135071
SINGLE
ROOM
130011
STAIR
1
SINGLE
ROOM
2" SAN
UP&DN
3" SAN
UP&DN
3" SAN UP&DN
2" SAN DN
1 r V RISE
PIPE AT CEILING TYP.
135461
CUSTODIAL
KITCHENETTE
13532
SINGLE
ROOM
2"VUP
135301
SINGLE
ROOM
13528
SINGLE
ROOM
13526
SINGLE
ROOM
135221
BATH -
TOILET
11111
11111
1111
111111
11
Nrall 13511
SINGLE
ROOM
1111
2" SAN
UP & DN
4" V UP & DN
135361
STORAGE
CUSTODIAL
SINGLE
ROOM
135151
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
DOUBLE
ROOM
135211
DOUBLE
ROOM
13519
SINGLE
ROOM
/ t l EXISTING THIRD FLOOR PLUMBING PLAN - SOUTH
SCALE: 1/8" = 1'—O"
1 0 1
1 /8" = 1'-0"
3
5
7
11
13 15
I MI e NIII
I INN INN INN
C
}
6 SIDE NORTH
5 SIDE SOUTH
2 KEY PLAN
P305
NOT TO SCALE
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW.
IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION.
LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY.
IT IS A VIOLATION OF THE
00
-a
c
3 _
0 W
c 0)
0
it)
0 U)
-c
4)O
av
0
(.4
C
c
a)
0.
E
fa
E
a)
N
0
0
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
c
0
a,
ce
d
z
8
*9-7
Scale
AS SHOWN
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Project No. C14151
Drawing No.
P3O5
Sheet No. 5 of 6
N:\915706\Drawings1P305 P306.dwg, 12/31/2014 9:51
6 SIDE (NORTH)
MIN MN 1111=
5 SIDE (SOUTH)
SINGLE
ROOM
SINGLE
ROOM
DOUBLE
ROOM
136211
DOUBLE
ROOM
13641
SINGLE
ROOM
SINGLE
ROOM
2"V RISER
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
2"VDN
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
V DN
SINGLE
ROOM
36361
ELEC
PANELS
SINGLE
ROOM
SINGLE
ROOM
4" V RISER
36201
SINK
ROOM
4"SAN UP & D
STORAGE
136321
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
2" V RISER
SINGLE
ROOM
SINGLE
ROOM
3" SAN
UP & DN
SINGLE
ROOM
13007]
STAIRS
5
2' V RISER
4" SAN UP& DN
(LAV & SH STACK)
136501
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
SINGLE
ROOM
4" SAN UP & DN
_679 SH STACK
SINGLE
ROOM
SINGLE
ROOM
13663
SINGLE
ROOM
2"VUP& DN
STAIRS
4
SINGLE
ROOM
13659
SINGLE
ROOM
STORAGE
ROOM
136521
SINGLE
ROOM
2"VUP&DN
136771
SINGLE
ROOM
4" SAN
UP&D
36801
TRASH
ROOM
13662
2"VUP& DN
DOUBLE 2" V UP & DN
ROOM
SINGLE
ROOM
13658
SINGLE
ROOM
SINGLE
ROOM
13654
DOUBLE
ROOM
RISER
4" SAN UP & DN
_679 WC STACK
3" SAN
UP & DN
SINGLE
ROOM
�I ] 36131
SINGLE
ROOM
r
99
11
136111
ROOM
11
3009 111 13609
SINGLE
U P S SIRS ROOM
1111101 6 11111
11
(3608 136071
SINGLE —
ROOM SINGLE
ROOM
36061 . 13605]
SINGLE SINGLE
ROOM ROOM
_ 111
It
000M — 13603
SINGLE SINGLE
ROOM ROOM
3602 - 36011
SINGLEIP SINGLE
ROOM ROOM
3" V RISER
u I'
136791
SINGLE
ROOM
4"VUP
& DN
136821
SINGLE
ROOM
SINGLE
ROOM
13684
SINGLE
ROOM
36851
SINGLE
ROOM
13686
SINGLE
ROOM
136881
SINGLE
ROOM
ROOF
SINGLE
ROOM
SINGLE
ROOM
1111111111 -411•11 -411111M -IMM -
ROOF DRAINAGE -
DOWNSPOUT
5" CI ST DN
ELEVATOR
LOBBY
6 SIDE (NORTH)
5 SIDE (SOUTH)
(NOTE: FOURTH & FIFTH FLOOR SIMILAR)
EXISTING THIRD FLOOR PLUMBING PLAN - NORTH
SCALE: 1/8" = 1'-0"
1 /8" = 1'—
FOR IlVFORMAIION ONLY
THIS DRAWING SHOWS EXISTING CONDITIONS AND
IS INTENDED FOR USE AS REFERENCE ONLY.
WORK TO BE PERFORMED FOR THIS PROJECT IS
SHOWN ON DRAWING P001 AND DRAWINGS OF
THE P100 & P200 SERIES
1 0 1
3 5 7 9 11 13
15
1 INNI
1■
6 SIDE NORTH
5 SIDE SOUTH
KEY PLAN
NOT TO SCALE
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW.
IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION.
LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY.
IT IS A VIOLATION OF THE
O t�
—a
0
• Cl)
co a
es5
(� W
c
0•
N
•
- c
4f o
a. co
1-1
M
co
'-4
0
s
a)
1
0
0
THIS DRAWING SHOWS EXISTING CONDITIONS AND
IS INTENDED FOR USE AS REFERENCE ONLY.
WORK TO BE PERFORMED FOR THIS PROJECT IS
SHOWN ON DRAWING P001 AND DRAWINGS OF
THE P100 & P200 SERIES
1 0 1
3 5 7 9 11 13
15
1 INNI
1■
6 SIDE NORTH
5 SIDE SOUTH
KEY PLAN
NOT TO SCALE
CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM
DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO
CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION.
THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW.
IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION.
LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY.
IT IS A VIOLATION OF THE
O t�
—a
0
• Cl)
co a
es5
(� W
c
0•
N
•
- c
4f o
a. co
1-1
M
co
'-4
0
s
a)
1
0
0
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Revision
z
r:4
1
Scale
AS SHOWN
Date
12/31/14
Drawn
K.A. SNYDER H. JUNUZOVIC
Designed
K.A. SNYDER
Checked
P.A. PETERSON
Project No. C14151
Drawing No.
P3O6
Sheet No. 6 of 6