031815 CLARA DICKSON CONFORMED SET
N:\915706\Conformed Drawings\P001 Conformed.dwg, 3/18/2015 3:29:36 PM, N81 Cornell University Clara Dickson Hall -Waste & Storm Line Replacement December 31, 2014 -Construction Documents SYMBOLS LIST & ABBREVIATIONS SYMBOLS DESCRIPTION ABBR. — — — — EXISTING WORK TO BE REMOVED (BOLD DASHED LINE) EXISTING WORK TO REMAIN (LIGHT SOLID LINE) NEW WORK (BOLD SOLID LINE) PATCH CONCRETE FLOOR ABOVE GROUND q .a . . COLD WATER CW BELOW GROUND (OUTDOORS) PVC SDR 35 BELL & SPIGOT CONFORMING TO ASTM D3034 WITH STIFFNESS VALUE OF 46 HOT WATER HW BELOW GROUND (INDOORS) CERAMIC TILE HOT WATER CIRCULATING LINE HWC — SAN SANITARY OR WASTE PIPING SAN — — V — — VENT PIPING V STORM PIPING ST — ST 0 CONNECT TO EXISTING REMOVE TO THIS POINT % PIPE DROP OR DOWN ) PIPE RISE OR UP 0 4 TOP CONNECTION —(I) BOTTOM CONNECTION VINYL TILE CAP OR PLUG C CLEANOUT, WALL CLEANOUT CO, WCO 1 P—TRAP X) O (E) FCO EXISTING FLOOR CLEANOUT EXISTING TO REMAIN EX, EXIST. — (E) FLOOR DRAIN FLD, FD ® o PLUMBING CONTRACTOR PC GENERAL CONTRACTOR GC ASBESTOS CONTAINING MATERIAL ACM SHOWER SH WATER CLOSET WC LAVATORY LAV KITCHENETTE SINK KS DRINKING FOUNTAIN DF GALLONS PER MINUTE GPM CAST IRON PIPE CI BOTTOM OF PIPE BOP ABOVE FINISHED FLOOR AFF FINISHED FLOOR ELEVATION FFE 1Q RISER NUMBER (EXAMPLE 15) SS (2636A) NUMBER IN PARENTHESES INDICATES ROOM SERVED BY STACK HATCHING LEGEND HATCH PATTERN DESCRIPTION r................. -1 I•••••••••'•'•'•'•'• •'•'•'• •'•••••'1 SAWCUT CONCRETE FLOOR SLAB, REMOVE CONCRETE JOINTS PATCH CONCRETE FLOOR ABOVE GROUND q .a . . NO HUB FITTINGS CHARLOTTE HEAVY DUTY 4 BAND S/S CLAMP W/NEOPRENE GASKET 80 IN LB TYPE BELOW GROUND (OUTDOORS) PVC SDR 35 BELL & SPIGOT CONFORMING TO ASTM D3034 WITH STIFFNESS VALUE OF 46 COMPATIBLE WITH PIPE, PUSH—ON TYPE GASKETS CONFORMING TO ASTM F477 BELOW GROUND (INDOORS) CERAMIC TILE PVC FITTINGS CONFORMING TO ASTM D2665 PURPLE PRIMER & SOLVENT CEMENT FOR PVC PIPE CONFORMING TO ASTM D2564 CARPET TILE .' VINYL TILE VINYL SHEET (LINOLEUM) GRADE CLEANOUT. SEE DETAIL FINISHED GRADE\ BRONZE PLUG C 4" SOIL PIPE GASKET 4" TAPPED BOSS FOR BRASS PLUG 4" CAST IRON SOIL PIPE CLEANOUT STACK --y PLUMBING WORK TO BE PERFORMED BY CITY OF ITHACA LICENSED PLUMBER & INSPECTED BY THE CITY OF ITHACA. PULL PERMIT TO INSTALL DRAIN, TRAP, & CLEANOUT. 8" OR 6" REFER TO PLANS FLOW 6"0 - FRESH AIR INLET IN LAWN OR PLANTING AREA ,�- — 4" CAST IRON SOIL PIPE 6" SANITARY SEWER n114110 Chi ma Wari Cooperative pha 'nma end House riphamme' Cooperatiu eL Pi Delta I Ps D Ila Akwekon HRS J@rom Hoy Deltaa Tamm WAIT AVENUE Kam pa e Dl iwe inoti ay Hall. RAWLINGS GREEN Rise Hall aro a 0 nte CRADIT FARM DRIVE Fuentes Obs ory ctric Plan ntercul ural ripham = r Foot ' ri N cRSI'C`f AV1r1,1UE Tjaden Sibley all Hall Martha Va Renssel fest-Home arage SITE LOCATION PLAN NOT TO SCALE PIPING SCHEDULE SERVICE LOCATION PIPING FITTINGS JOINTS STORM, SANITARY & VENT ABOVE GROUND SERVICE WEIGHT HUB CAST IRON NO HUB FITTINGS CHARLOTTE HEAVY DUTY 4 BAND S/S CLAMP W/NEOPRENE GASKET 80 IN LB TYPE BELOW GROUND (OUTDOORS) PVC SDR 35 BELL & SPIGOT CONFORMING TO ASTM D3034 WITH STIFFNESS VALUE OF 46 COMPATIBLE WITH PIPE, PUSH—ON TYPE GASKETS CONFORMING TO ASTM F477 BELOW GROUND (INDOORS) SCHEDULE 40 PVC DWV CONFORMING TO ASTM D1785 & D2665 PVC FITTINGS CONFORMING TO ASTM D2665 PURPLE PRIMER & SOLVENT CEMENT FOR PVC PIPE CONFORMING TO ASTM D2564 FLOOR DRAIN SCHEDULE TAG DESCRIPTION MAKE & MODEL LOCATION NOTES FD -1 GENERAL SERVICE FLOOR DRAIN, DUCO CAST IRON BODY AND GRATE, SEDIMENT BUCKET. PROVIDE P—TRAP. JAY R SMITH MODEL 2210 SUMP BASINS EXTENSION TYPE CLEANOUT, DUCO CAST IRON, W/RAISED HEAD CLOSURE PLUG, SERVICE WEIGHT. 4,l 6" CAST IRON SINGLE VENTED BUILDING TRAP OUTDOOR TYPICAL BUILDING TRAP WITH FRESH AIR INLET DETAIL NOT TO SCALE CLEANOUT SCHEDULE TYPE DESCRIPTION MAKE & MODEL NOTES FCO CAST IRON FLOOR CLEANOUT WITH ROUND ADJUSTABLE SCORIATED SECURED NICKEL BRONZE TOP, TAPER THREAD AND BRONZE PLUG. JAY R SMITH MODEL 4033L OR EQUAL BY ZURN PROVIDE CARPET CLAMPING FLANGE IN CARPET AREAS CO EXTENSION TYPE CLEANOUT, DUCO CAST IRON, W/RAISED HEAD CLOSURE PLUG, SERVICE WEIGHT. JAY R SMITH SERIES 4280 OR EQUAL BY ZURN WCO WALL CLEANOUT — CAST IRON SPIGOT FERRULE WITH BRONZE TAPER THREAD PLUG, STAINLESS STEEL ROUND COVER AND SCREW JAY R SMITH MODEL 4422C OR EQUAL BY ZURN LAWN GRADE CAST IRON EXTENSION LENGTH VARIES, SEE PLANS AND ELEVATIONS b 4" 6" �-- 6" CONCRETE PAD CAST IRON CLEANOUT WITH BRONZE PLUG, JAY R. SMITH MODEL NO. 4281 ROUND, FLANGED HOUSING WITH HEAVY DUTY CAST IRON COVER, JAY R. SMITH SERIES 4250 CAST IRON PIPE OUTDOOR GRADE CLEANOUT DETAIL NOT TO SCALE a ADJUSTABLE TOP AND FRAME CARPET DRAWING LIST CONTRACT DRAWINGS: P001 P100 P101 P102 P200 P201 P202 TITLE SHEET, SYMBOLS, SCHEDULES, NOTES & DETAILS UNDERFLOOR PIPING REMOVAL PLAN - NORTH UNDERFLOOR PIPING REPLACEMENT PLAN - NORTH FINISHES REPLACEMENT PLAN - NORTH UNDERFLOOR PIPING REMOVAL PLAN - SOUTH UNDERFLOOR PIPING REPLACEMENT PLAN - SOUTH FINISHES REPLACEMENT PLAN - SOUTH EXISTING CONDITION DRAWINGS - FOR INFORMATION ONLY: P301 P302 P303 P304 P305 P306 EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING FIRST FLOOR PLUMBING PLAN SOUTH FIRST FLOOR PLUMBING PLAN - NORTH SECOND FLOOR PLUMBING PLAN - SOUTH SECOND FLOOR PLUMBING PLAN NORTH THIRD FLOOR PLUMBING PLAN - SOUTH THIRD FLOOR PLUMBING PLAN - NORTH 4000 PSI READY MIX CONCRETE, ASSUME 5" THICKNESS #4 DOWELS —12" LONG 6" EMBEDMENT, 3' OC ON EACH SIDE 5"± IF OVER 4 FEET DEEP LAY BACK SHORE TRENCH IN ACCORDANCE WITH REQUIREMENTS OF OSHA STANDARD 1926, CONSTRUCTION, LOCAL LAWS. / I \ ADD #1 ss\ OR,/jj\//\/\\/\\/\//\\//\\//\\//\\//\\//\\/\\//\\//\\// AND j \j\�j�j\\�j • RUN OF CRUSHED LIMESTONE < COMPACTED IN 12" LIFTS OR PEA GRAVEL OR NYS DOT #1A CRUSHED STONE WITH A PLATE TAMPER IN 12 INCH LIFTS: FLOWABLE FILL SHALL NOT BE ACCEPTABLE IN PLACE OF COMPACTED OR CONSOLIDATED STONE: DEPTH VARIES SEE PLAN 1\ADD #1 SANITARY OR STORM LINE. SEE PLAN FOR SIZE 4" MINIMUM PIPE BEDDING TYPICAL BACKFILL & FLOOR PATCH DETAIL /11, U NOT TO SCALE NOT TO SCALE FLOOR SLAB • A 4 • • a• • f 1 a A. • •a• A FLOOR FLOOR CLEANOUT DETAIL 5 NOT TO SCALE P001 GROUND FLOOR P00 P001 1\ADD #1 EXISTING CAST IRON ABOVE FLOOR CONNECT TO EXISTING PROVIDE CLEANOUT AT BASE OF EACH RISER 6" MIN. PVC ABOVE FLOOR I PHASE: YEAR1&2 YEAR1&2 YEAR1&2 YEAR1&2 YEAR 2 YEAR 2 YEAR 2 a. \/ \/ \ \/ \ \/ \ \ \i \/ \ \i \ \i \ \ PLUMBING NOTES 1. ALL WORK SHALL CONFORM TO CORNELL UNIVERSITY DESIGN AND CONSTRUCTION STANDARDS FOR QUALITY, MATERIALS AND WORKMANSHIP. 2. ALL WORK SHALL CONFORM TO THE EXISTING BUILDING CODE OF NEW YORK STATE (EBCNYS). ALL PLUMBING WORK IN THE PROJECT AREA SHALL CONFORM TO PLUMBING CODE OF NEW YORK STATE (PCNYS), THE FIRE CODE OF NEW YORK STATE (FCNYS), AND THE ENERGY CONSERVATION CONSTRUCTION CODE OF NEW YORK STATE (ECCNYS). THESE DRAWINGS WERE PREPARED UNDER THE 2010 VERSIONS OF THE AFOREMENTIONED CODES. CONFIRM WITH THE CITY OF ITHACA THE PREVAILING CODE VERSION AT THE TIME OF PERMIT ISSUE AND COMPLY WITH THE PROVISION OF THE CURRENTLY APPLICABLE CODE AT THE TIME OF PERMIT ISSUE. 3. ALL WORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE REQUIREMENTS OF THE OCCUPATIONAL HEALTH AND SAFETY ACT (OSHA) AS AMENDED AND THE REQUIREMENTS OF THE NEW YORK STATE DEPARTMENT OF LABOR. 4. CONFORM TO ALL UTILITY COMPANY RULES AND REGULATIONS. 5. BUILDING PERMIT: CONTRACTOR SHALL OBTAIN A BUILDING PERMIT BEFORE STARTING WORK. CONTRACTOR SHALL PAY ALL PERMIT EXPENSES. 6. THE PROJECT OCCURS WITHIN THE CITY OF ITHACA. CONTRACTOR SHALL HAVE A VALID MASTER PLUMBER LICENSE AND SHALL PROVIDE A CITY OF ITHACA PLUMBING PERMIT, INSPECTION AND CERTIFICATE OF COMPLETION. THE CONTRACTOR SHALL PAY ALL FEES. 7. THIS PROJECT INCLUDES SAW CUTTING SLAB, HAND EXCAVATION AROUND PIPE, REMOVAL AND REPLACEMENT OF UNDERFLOOR PIPE AND RESTORATION OF SURROUNDING CONSTRUCTION AND FINISHES. REFER TO DRAWINGS AND SPECIFICATION FOR ADDITIONAL SCOPE OF WORK. 8. PROVIDE DETAILED SUBMITTALS FOR ALL MATERIALS AND EQUIPMENT PROVIDED UNDER THIS PROJECT. 9. PROVIDE OPERATION AND MAINTENANCE INFORMATION FOR ALL MATERIALS, EQUIPMENT AND SYSTEM PROVIDED UNDER THIS PROJECT. SEE SPECIFICATIONS. 10. CLARA DICKSON HALL MAY BE OCCUPIED BY STAFF AND SUMMER PROGRAMS IN THE BUILDING DURING THE CONSTRUCTION PERIOD. WATER SERVICES WILL BE REQUIRED BY THE STAFF AND CONTRACTORS. PROVIDE TEMPORARY SERVICES AS REQUIRED. COORDINATE SHUTDOWN OF ONE SIDE OF THE BUILDING AT A TIME. 11. PROVIDE SIGNED, DATED, CONTRACTOR AS—BUILT DRAWINGS FOR ALL WORK PROVIDED UNDER THIS PROJECT. MAINTAIN ONE SET OF CONSTRUCTION DRAWINGS DENOTING ANY FIELD CHANGES WHICH ARE MADE AS THE WORK OF THE PROJECT PROGRESSES. KEEP THESE UPDATED. ENGINEER SHALL BE PERMITTED TO BORROW, PHOTOCOPY AND RETURN THESE DRAWINGS AT INTERVALS THROUGH THE PROJECT. 12. NO WORK OF ASBESTOS OR HAZARDOUS MATERIAL ABATEMENT OR REMOVAL IS INCLUDED UNDER THIS CONTRACT. CONTACT OWNER IF SUSPECTED ASBESTOS MATERIAL ARE ENCOUNTERED. 13. INSPECTION: NOTIFY CITY OF ITHACA PLUMBING CODE COMPLIANCE OFFICER AND PETERSON GUADAGNOLO ENGINEERS A MINIMUM OF 48 HOURS PRIOR TO TESTING PLUMBING LINES. CONTINUOUS PLASTIC WARNING TAPE LOCATED 12" BELOW GRADE AND ON TOP OF 12" LAYER ABOVE SEWER. TAPE SHALL BE 6" WIDE & LABELED "SANITARY SEWER". RE—SEED LAWNS COMPACTED SELECT NATIVE MATERIAL LAY BACK OR SHORE A DEPTH VARIES ADD #1 TRENCH IN ACCORDANCE WITH REQUIREMENTS OF OSHA STANDARD 1926, CONSTRUCTION, AND LOCAL LAWS. EPDXY GROUT PVC BELOW FLOOR / 8 a PVC -CAST IRON PIPE CONNECTION DETAIL NOT TO SCALE PIPE SLEEVE CRUSHED STONE NYS DOT TYPE 1A OR 1 ABOVE PIPE, COMPACT IN 6" LIFTS. ONE PIPE DIAMETER MINIMUM. 0 0 L1.1 a SEWER LINE TYPICAL SANITARY TRENCH DETAIL - UNDER GRASS NOT TO SCALE STEEL SEALING AND ANCHORING COLLAR WELDED TO SLEEVE CENTER PIPE IN SLEEVE SEAL WATERTIGHT WITH MASTIC OR ASPHALT ADD #1 SEAL SLEEVE WITH TIGHTLY PACKED FIBERGLASS OR 'LINK—SEAL' Pr STANDARD WEIGHT STEEL PIPE SLEEVE NON—SHRINK GROUT OR EPDXY GROUT NOTE: PIPE SLEEVE FOR EXTERIOR WALL ABOVE OR BELOW GRADE CORE DRILL HOLE AS REQUIRED ESCUTCHEON (NOT REQUIRED IN UNFINISHED SPACES) INTERIOR WALL SURFACE EXTERIOR WALL PIPE SLEEVE DETAIL 7 NOT TO SCALE P001 CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. g THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE 00 — a 0 ci co a �O) 3i 0 W 0• 4 r _) .0 4)0 O.0 3� O 0 0 3/18/15 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Revision CONFORMED DRAWINGS c a 2O rig""2"cin"2" mi. E — 4 Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. o C14151 Drawing No. P001 YEAR 1&2 Sheet No. 1 of 7 2. PIPING SHOWN ON DRAWINGS HAS BEEN DEVELOPED FROM PROJECT RECORD DRAWINGS AND FIELD VERIFIED TO THE GREATEST EXTENT POSSIBLE. CONTRACTOR SHALL VERIFY IN FIELD ALL LOCATIONS PRIOR TO REMOVAL OF WALLS AND SAW CUTTING OF FLOC) PI' OUTING WAS DEVELOPED FROM AS BUILDS DRAWINGS AND WAS FURTHER INSPECTED WITH TV AND PREVIOUSLY EXCAVATED AT THREE LOCATIONS. CONTRACTOR MAY ASSUME PIPING ROUTING SHOWN IS ACCURATE. 3. REMOVE, STORE AND REINSTALL PLUMBING FIXTURES AS NOTED ON DRAWINGS. 4. CONTRACTOR SHALL REMOVE GWB, PLASTER AND CONCRETE BLOCK WALLS AS SHOWN ON DRAWINGS TO FACILITATE PIPE REPLACEMENT. 5. CONTRACTORS SHALL BE RESPONSIBLE TO PROTECT ABOVE—GROUND PIPING SYSTEMS AND SURROUNDING BUILDING SURFACES I.E. FLOORS, WALLS, ETC. CONTRACTOR SHALL REPLACE ANY PIPE INSULATION, ABOVE GROUND PIPE, AND REPAIR ANY SURFACES DAMAGED IN THE PERFORMANCE OF THIS PROJECT. 6. FOR BASIS OF BIDDING, ASSUME FLOOR SAW CUTS WILL NOT ENCOUNTER ANY IN SLAB CONDUITS. 7. LOCATION OF DUMPSTER SHALL BE ADJACENT TO COLUMN LINE 69 AND MINIMUM 10 FEET FROM BUILDING. LOCATION SHALL BE COORDINATED WITH CORNELL PROJECT MANAGER. DUMPSTER SHALL BE SCREENED FROM VIEW ON THE ROAD SIDE WITH 6' HIGH PEDESTAL METAL FENCING WITH GREEN SIGHT COVERS. ANCHOR FENCING TO MINIMIZE OVERTURNING DUE TO WIND. N:\915706\Conformed Drawings\P100 YR 1 Conformed.dwg, 3/18/2015 3:30:18 PM, N81 ADD #1 1\ADD #1 SINGLE ROOM CLOSET 2" VENT UP 3" UP TO FD 116371 BATHROOM 2" SAN UP TO LAVS 16211 SINGLE ROOM 1063 DATA SINGLE ROOM 3" SAN UP TO WC 11643 I SINGLE ROOM REMOVE PORTION OF WIRE LATH AND PLASTER WALL. 2" SAN UP TO SH (TYP 2�, ■' REMOVE C.I. SAN MIN. 6" ABOVE FLOOR SLAB. (TYP) (1635 SINGLE ROOM 4" UP 631B) SINGLE ROOM 116311 SINGLE ROOM (2629B) 11627 SINGLE SINGLE ROOM ROOM REMOVE PORTION OF WIRE LATH AND PLASTER WALL 116251 SINGLE ROOM SINGLE ROOM 1621A CLOSET " UP (2625B) 162301 CLOSET EXISTING HUB DRAIN TO REMAIN LIGHT BULB ROOM 1635A1 CLOSET 163101 CLOSET 1629A CLOSET 162701 CLOSET 1625A SINK ROOM CLOSET T B.O.P. 25"± BELOW SLAB ---- 4; -- -- 1031 — SAN C±DRRIOOR- 4" (E) SAN B.O.P. 15"± BELOW SLAB (E)FC0 UP 1005 STAIR CO \ 4" UP _622 STACK 116191 BIKE STORAGE 3" UP 116221 MCLLU DEN EXIST NG PIPE —TO REMAIN (2630B) SAWCUT FLOOR REFER TO REMOVAL NOTE 1 (TYP.) 11618 STORAGE OWNER WILL RELOCATE EQUIPMENT AWAY FROM WORK AREA. 0 116191 STORAGE 116451 DOUBLE ROOM 110091 STAIR KITCHEN 1 of REMOVAL NOTES: 1. IN AREAS SHOWN, SAWCUT FLOOR, REMOVE CONCRETE SLAB AND HAND EXCAVATE AROUND SANITARY LINE. REMOVE PIPE AS INDICATED ON DRAWINGS. REMOVE RISERS MINIMUM OF 6" ABOVE FLOOR SLAB. \ADD #1 414) A\ADD #1 11675 SINGLE ROOM 1673 I SINGLE ROOM 116711 SINGLE ROOM 16691 SINGLE ROOM 116671 SINGLE ROOM 4" UP (2 (2670) _ 116651 SINGLE SINGLE ROOM ROOM REMOVE PORTION OF WIRE LATH AND PLASTER WALL. 116611 SINGLE ROOM 116591 SINGLE ROOM 11648 EXISTING PIPE STORAGE TO I REMAIN MAINTENANCE 1675A CLOSET CLOSET CLOSET 1669AI CLOSET 166301 CLOSET CLOSET EXISTING PIPE TO REMAIN 116151 RECREATION ROOM CORRIDOR 4" UP (2636A) EMOVE UTILITY SINK, STORE FOR REINSTALLATION J I VISFI�C REMOVE PORTIONI OF WIRE LATH AND PLASTER WALL 11662 EXIST B.O.P. 31" ± BELOW SLAB SUMP PIT WITH PUMP USE CARE TO AVOID DAMAGING PAVEMENTS, TREES AND BUILDING FINISHES. CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORATION OF DAMAGED AREAS. IF PROPER CARE IS EMPLOYED, RESTORATION MAY BE LIMITED TO TOPSOIL AND SEED. 11674 DOUBLE ROOM 1-1/2" SAN UP TO LAV (1679) 2"VENT UP (TO REMPIN) 116501 \EXISTING 2"PUMP DISCHARGE UP (TO REMAIN) 3" UP TO FD (TO REMAIN) MECHANICAL ROOM REMOVE AND REPLACE FLOOR DRAIN AT BOTTOM OF SUMP 2" TO SH (TYP) EXISTING SUMP TO REMAIN 3" SAN UP TO WC (TYP 3) 1-1/2" SAN UP TO LAVS (1679) 115391 STORAGE REMOVE PORTION OF WIRE LATH AND PLASTER WALL EXIST. STORM MANHOLE HADD #1 EXIST. SANITARY MANHOLE PULL 6" EXISTING PIPE OUT OF EXISTING MANHOLE. INSERT MAIN PIPE AND REPAIR OPENING AND BENCH WALLS WITH NON—SHRINK GROUT. REMOVE HOUSE TRAP, CLEANOUT & FRESH AIR INLET LOCKER ROOM REMOVE CERAMIC TILE WALL FOR ACCESS TO WATER PIPING EXIST B.O.P. 45.5" ± BELOW B CAREFULLY REMOVE TILE SHOWER FLOORS. REPAIR SCHLUTER WATERPROOF SYSTEM. COORDINATE WORK W/EXISTING ELECTRIC/DATA OUTLETS REMOVE DRAINS, AND PIPING SERVING SHOWERS IN ROOM 1538 ADD #1 6 SIDE (NORTH) , 5 SIDE (SOUTH) OWNER WILL RELOCATE RESTROOM LOCKERS OUT OF WORK AREA. INVERT ELEVATION TO MATCH EXISTING. ASSUME 48" BELOW FINISHED FLOOR. BREAK —ReeM— — — — 1 2"ST UP 11535 PROJECT ROOM 110271 CORRIDOR SPRINKLER ROOM MECHANICAL ROOM FCO SERVICE ELEVATOR 000F HYDRAULIC ELEVATOR (44 "S RISER 110281 RECEIVING 5"ST RISER 10280 — 51 SAWCUTFLOOR REFER TO REMOVAL NOTE 1 (TYP.) YEAR 1 WORK YEAR 2 WORK 6 SIDE (NORTH) 5 SIDE (SOUTH) UNDERFLOOR PIPING REMOVAL PLAN - NORTH SCALE: 1/8" = 1'-0 1 /8" = 1 0 1 3 5 *I/ NOTE YEAR 2 WORK IS SHOWN FOR REFERENCE PURPOSES ONLY, AND IS NOT INCLUDED IN THE CURRENT SCOPE OF WORK. 9 11 13 15 I MI MN N I■ NI MI = 6 SIDE NORTH 5 SIDE SOUTH CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. g THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY g IT IS A VIOLATION OF THE 0 0 - a 0 c. Ala � a) W c 0 •- L. v/ .1c CD O. V 7.7 * >/ 7 7 ., 0 3/18/15 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Revision CONFORMED DRAWINGS d Cz Project/Sheet Title 1 Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P100 YEAR1&2 Sheet No. 2 of 7 N:\915706\Conformed Drawings\P101 YR 1 UF 6 SIDE Conformed.dwg, 3/18/2015 3:30:41 PM, N81 PLUMBING FIXTURE SCHEDULE PF # FIXTURE ABBREV SYMBOL HOT COLD WASTE VENT REMARKS MOUNTING HEIGHT MAKE & MODEL US -1 UTILITY SINK US 1/2" 1/2" 3" 1 1/2" UTILITY SINK— REINSTALL EXISTING SINK. PROVIDE P—TRAP AND FAUCET. FAUCET— BRASS CONSTRUCTION, 8" CENTERS, BRASS VALVE BODIES, VACUUM BREAKER, INTEGRAL SUPPLY & CHECK VALVES, WALL BRACE, PAIL HOOK, HOSE END SPOUT. METAL LEVER HANDLES, AMERICAN STANDARD 8354.112. P—TRAP— TRAP WITH STRAINER, WALL OUTLET. THREADED 3" INSIDE FOR CAST IRON SERVICE SINK. AMERICAN STANDARD 7798.030 MS -1 MOP SINK MS 1/2" 3" 1 1/2" FLOOR MOUNTED RECEPTACLE— 24"x24"x10"H MOLDED STONE, FIAT MODEL MSB -2424 FAUCET— BRASS CONSTRUCTION, 8" CENTERS, BRASS VALVE BODIES, VACUUM BREAKER, INTEGRAL SUPPLY & CHECK VALVES, WALL BRACE, PAIL HOOK, HOSE END SPOUT. METAL LEVER HANDLES, AMERICAN STANDARD 8354.112. PROVIDE BLOCKING FOR FAUCET MOUNTING. ACCESSORIES— PROVIDE STAINLESS STEEL WALL GUARDS, CAPS ON ALL CURBS, MOP HANGER, HOSE & HOSE BRACKET, INTEGRAL SS CAST DRAIN BODY AND SS COMBINATION DOME STRAINER AND LINT BASKET 01/2" 3" SAN UP TO WC 4" UP 0 FCO 1639 SINGLE ROOM 1639A CLOSET 2" VEN UP 3" UP TO FD 116371 '8* BATHROOM 2" SAN UP TO LAVS SINGLE ROOM 110631 (1641 SINGLE ROOM 3" SAN UP TO WC PROVIDE FCO (TYP.) REFER TO DETAIL REPLACE SUMMER 2012 2" SAN U TO SH (TYP 2) 11643 I SINGLE ROOM CLOSE 116381 116351 SINGLE ROOM 4" UP (2631B)(5 dfu) 11633 SINGLE ROOM 11631 I SINGLE ROOM SINGLE ROOM 11627 I SINGLE ROOM 11625 SINGLE ROOM (1623 I SINGLE ROOM j621A CLOSET HT BULB ROOM 1635A1 CLOSET 4" UP (2629B) 5 dfu) 1631A( UP(2625B) (5 dfu) CLOSET CLOSET 1627A1 1623A CLOSET (10 dfu) 3' CLOSET 110641 SINK ROOM CLOSET SLOPE ®1 8" PER 'FT. - MIN. B.O.P. 25"± BELOW SLAB " 203 dfu 183 dfu) 4" 178 dfu " 173 dfu 116191 TC MECHANICAL (203 dfu)5 110051 STAIR PATCH CONCRETE FLOOR SLAB CO \ 4" UP 15 622 STACK REPLACED (156 dfu) DECEMBER 2012 PATCH CONCRETE FLOOR SLAB(TYP) (3644c6 dfu) 11645 5"(209 dfu) UP 1 2630B) (5 dfu) 16221 MCLLU DEN TIE INTO EXI TING RISER ABOVE FLOOR (TYP) REFER TO DETAIL 1622A1 CLOSET STORAGE 11619 STORAGE DOUBLE ROOM 110091 STAIR KITCHEN 116751 SINGLE ROOM SINGLE ROOM (1671 I SINGLE ROOM SINGLE ROOM 1673A1 SINGLE ROO 4" UP (2670) (8 dfu) 116651 SINGLE ROOM SINGLE ROOM 116611 SINGLE ROOM REPLACED DECEMBER 2012 11648 STORAGE SINGLE ROOM 11647 MAINTENANCE CLOSET CLOSET CLOSET 1665A CLOSET 1663AI CLOSET 1661A1 CLOSET 1659AI CLOSET 11615 RECREATION ROOM 257 df (E)SAN (226 dfu)5" " 249 dfu) EX 2" PUMP DISCHARGE — RECONNECT TO SAN RISER AT 1ST FLOOR _)1 EXCAVATE LAWN AREA TO INSTALL BUILDING TRAP & PIPE. BACK FILL AND RESEED REFER TO DETAIL 1-1 /2" SAN UP DOUBLE ROOM 1-1/2" SAN UP TO LAV (1679) PIPING IN ROOM 1679 REPLACED SUMMER 2012 3" SAN UP TO WC (TYP 3) EXIST. STORM MANHOLE 4" UP (_679 WC, 2673A WC & TUB) (100 dfu) SINK ROOM C01 US -1 REINSTALL UTILITY SINK. PROVIDE NEW P—TRAP AND FAUCET REFER TO PLUMBING FIXTURE SCHEDULE PATCH CONCRET FLOOR EXIST B.O.P. 31" ± BELOW SLAB 4" UP (2636A) (13 dfu) 298 dfu) REMOVE AND REPLACE SHOWER FLOORS & WATER PROOFING CONNECTORS TO THE WALL (21 dfu) CO 11650 MECHANICAL ROOM EXISTING SUMP PROVIDE FLOOR DRAIN AT BOTTOM 2" TO SH (TYP) OF SUMP PATCH CONCRETE FLOOR SLAB (TYP) TO LAVS (1679) st....mvv.40616. 3"UP_ TO MS ��� .��vaip'�3awe� s .� • F 0 6 LOCKER ROOM 6 (424 dfu) FOR 1ST FLR WORK IN THIS AREA REFER TO EXIST. SANITARY—I MANHOLE ADD #1 PROVIDE BUILDING TRAP. REFER TO DETAIL PROVIDE PIPE SLEEVE REFER TO DETAIL EXIST B.O.P. 45.5" ± BELOW REMOVE EXISTING 6" SANITARY THROUGH BUILDING CONCRETE FOUNDATION WALL. IF HOLE IS OVERSIZED, PROVIDE PIPE SLEEVE PER DETAIL 7/P001 AND SEAL WITH NON—SHRINK GROUT. IF OPENING IS CLEAN AND CORRECT SIZE, INSERT PIPE AND SEAL WITH NON—SHRINK GROUT. 6 SIDE (NORTH) MIMS Milli IMMO MINIM 011111111111 5 SIDE (SOUTH) EXTEND NEW STORM OUTSID OF BUILDING AND CONNECT TO EXISTING TO STORM MANHOLE PATCH CONCRETE FLOOR SLAB (TYP) < .4" 15371 BREAK RQOM PROJECT ROOM {000H1 { 0000 CORRIDOR HOT WAT R TANK 15341 MECHANICAL ROOM 110411 SERVICE ELEVATOR HYDRAULIC ELEVATOR "S 5"S _3"ST FCO FCO L '1 YEAR 1 WORK YEAR 2 WORK 6 SIDE (NORTH) 111111111111 MM. MIMI SWIM 5 SIDE (SOUTH) 1 UNDERFLOOR PIPING REPLACEMENT PLAN - NORTH P101 SCALE: 1/8" = 1'-0" X60; �QT EXISTING I-� HW&CW ''hk 116791 MEN'S BATH ROOM OO J 11539 STORAGE Q CONNECT TO EXISTING HW & CW AND VENT 110271 CORRIDOR A/` -----PROVIDE MOP SINK, FAUCET & MS -1 1 ACCESSORIES REFER TO PLUMBING FIXTURE SCHEDULE THIS DRAWING 3" SAN 1538 MEN'S LOCKER ROOM PARTIAL FIRST FLOOR PLAN SCALE: 1 /8" = 1'-0" 1 0 1 1/8" = 1,_0» 3 5 9 11 NOTES: 1. REPLACE UNDERFLOOR SANITARY & STORM PIPING AS INDICATED ON DRAWINGS. REFER TO PIPE SCHEDULE FOR PIPE MATERIALS. 2. BACKFILL AND PATCH CONCRETE FLOOR. REFER TO DETAIL 1 /P001 AND SPECIFICATIONS. 3. PROVIDE NEW FLOOR CLEANOUTS AS INDICATED ON THE DRAWINGS. 4. BOTTOM OF PIPE (B.O.P.) ELEVATIONS SHOWN WERE MEASURED DURING THE CAMERA INSPECTION AND JETTING ON JUNE 6, 2012 AND AS NOTED ON CONTRACTOR AS—BUILT DRAWINGS FOR THE SUMMER 2012 "6" SIDE ONLY BATHROOM RENOVATION PROJECT. 5. PROVIDE EXTERIOR BUILDING TRAP AS NOTED ON PLANS. 6. PROVIDE CLEANOUT AT THE BASE OF EACH RISER REFER TO DETAIL 6/P001 7. CONTRACTORS SHALL BE RESPONSIBLE TO PROTECT ABOVE— GROUND PIPING SYSTEMS AND SURROUNDING BUILDING SURFACES I.E. FLOORS, WALLS, ETC. CONTRACTOR SHALL REPLACE ANY PIPE INSULATION, ABOVE GROUND PIPE, AND REPAIR ANY SURFACES DAMAGED IN THE PERFORMANCE OF THIS PROJECT. 8. REFER TO FINISHES REPLACEMENT PLANS FOR WALLS TO BE REPLACED. CONTRACTOR MAY ASSUME THAT AT LOCATION WERE RISERS ARE ADJACENT TO BUILDING COLUMN FOUNDATIONS, NEW PIPING WILL BE INSTALLED WITHOUT DISTURBANCE OR REWORK OF EXISTING STRUCTURAL FOUNDATIONS. ADD #1 NOTE YEAR 2 WORK IS SHOWN FOR REFERENCE PURPOSES ONLY, AND IS NOT INCLUDED IN THE CURRENT SCOPE OF WORK. 13 15 1 MN M 1111 11111 1■ — N KEY PLAN NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW. IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE 00 0 —a co = i c G) c O) 3 _ W 0) 0� i. 3 ala C (1) ON 0 0 vi 4) c c (1,) 0 E E a) 0 3/18/15 I Drown K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Revision CONFORMED DRAWINGS 6 z \ C r:4 1 Scale AS SHOWN Date 12/31/14 Drown K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P101 YEAR1&2 Sheet No. 3 of 7 6 SIDE (NORTH) 5 SIDE (SOUTH) X83, NO FINISHES WORK REQUIRED FOR ROOM 1637 3" SAN TO WC 11639 SINGLE ROOM 1639A1 CLOSET 2" VEN1 UP 3" UP TO FD UP 4" UP 0 FCO BATHROOM 2" SAN UP TO LAVS SINGLE ROOM 1063 DATA NOTES: 1. THIS DRAWING IS INTENDED TO SHOW RESTORATION OF FINISHES ONLY. REFER TO DRAWINGS P100 & P101 FOR PIPING REPLACEMENT WORK. 2. CONTRACTOR SHALL RESTORE SURROUNDING FINISHES AFTER REPLACEMENT OF UNDERFLOOR PIPING. WORK INCLUDES REPLACEMENT OF CARPET, CERAMIC TILE AND VINYL TILE IN LOCATIONS SHOWN ON DRAWINGS. REPLACE STUD/ SHEETROCK AND CONCRETE BLOCK WALLS AS NOTED ON PLANS AND AS REQUIRED TO RESTORE TO PRECONSTRUCTION CONDITION. ALL WALLS IN CONSTRUCTION AREA SHALL BE PAINTED, COLOR SELECTED BY OWNER. SINGLE ROOM 3" SAN UP TO WC REPAIR WIRE LATH & PLASTER WALL (TYP.) REFER TO DETAI . 1643 2" SAN UP TO SH (TYP 2) 16351 SINGLE ROOM SINGLE ROOM 116311 SINGLE ROOM " UP (26316) CARPET TILES (26296) 116291 11627 1 SINGLE SINGLE ROOM OM REPAIR WIRELATH& PLASTER WALL CARPET TILES 1625 SINGLE ROOM SINGLE ROOM 1621A CLOSET " UP(2625B) CLOSET SINGLE ROOM 1635A1 SINK ROOM CLOSET CLOSET (E)FCO 11619 1 TC MECHANICAL 11005 I STAIR CONCRETE FLOOR 116191 164881 BIKE STORAGE MCLLU DEN 11618 STORAGE CARPET TILES 26306) CLOSET 11619 STORAGE 11645 I DOUBLE ROOM STAIR 116171 KITCHEN 2" UP TO SINK (1647) 11675 SINGLE ROOM SINGLE ROOM SINGLE ROOM 11669 1 SINGLE ROOM REPA R WIRE LATH & PLASTER WALL SINGLE ROOM 4" UP (2670) _- 11665 1 SINGLE ROOM SINGLE ROOM 116611 SINGLE ROOM 11659 1 SINGLE ROOM REPLACED DECEMBER 2012 STORAGE 1675A CLOSET RECREATION ROOM (E)SAN OPEN & REPAIR WALL AT RISER REPAIR WIRE LATH & PLASTER WALL ONCRETE FLOOR CARPET TILES YY REPAIR WALL BASE AS REQUIRED 4" UP (2636A) PIPING IN ROOM 1 DOUBLE REPLACED SUMME ROOM 1 —1 /2" SAN --� UP TO LAV (1679) OPEN & REPAIR WALL AT RISER 3" SAN UP TO WC (TYP 3) 1-1/2" SAN UP TO LAVS (1679) CERAMIC TILE 0 :R SCHLUTER WATERPROOF MEMBRANE FCO 2" TO SH (TYP) 115391 STORAGE CARPET TILE ERAMIC TILE VINYL TILE MECHANICAL ROOM CONCRETE FLOOR • ►-p' • Ilit P ij► /* pit 0 2"SAN UP FCO TO EX. 3b SHOWERS REPAIR WIRE LATH & PLASTER WALL VINYL TILE REPAIR WALL BASE AS REQUIRED CARPET TILE 115371 BREAK ROOM REPAIR WALL BASE AS REQUIRED — VINYL TILE REPAIR WALL BASE AS REQUIRED YEAR 1 WORK CONCRETE FLOOR PROJECT ROOM 100081 11027 1 CORRIDOR REFER TO DWG P201 FOR WORK IN THIS AREA 11 534 1 MECHANICAL ROOM FCO 110411 SERVICE ELEVATOR 1009F CONCRETE FLOOR HYDRAULIC ELEVATOR HUB DRAIN "S RISE YEAR 2 WORK 11111111111111 6 SIDE (NORTH) 5 SIDE (SOUTH) FINISHES REPLACMENT PLAN — NORTH SCALE: 1 /8" = 1'-0" /8" GWB 3-5/8" METAL STUD (16" 0.C.) METAL STUD WIRE LATH 1/2" - 5/8" PLASTER WIRE STUD n WIRE LATH WALL REPLACEMENT DETAILS NOT TO SCALE 1/8" = 1'- 1 0 1 3 1 ME e M ME 1■ ME M 7 11 13 NOTE YEAR 2 WORK IS SHOWN FOR REFERENCE PURPOSES ONLY, AND IS NOT INCLUDED IN THE CURRENT SCOPE OF WORK. 6 SIDE NORTH 5 SIDE SOUTH 15 KEY PLAN NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. A VIOLATION OF THE 1- O 0 -a 0 Ci o)• a W O) 0 uw 0) 0 A, W y -c • o 0.v a) CO w 0 cii N c 0i c a) at 0. CaJ Ea)a) E 0 0 CI 3/18/15 I Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON 0 N CC CONFORMED DRAWINGS z C r4 0 1 O 0023 Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P102 YEAR1&2 Sheet No. 4 of 7 N:\915706\Conformed Drawings\P200 YR 2 UF Conformed.dwg, 3/18/20152:52:31 PM, N81 6 SIDE (NORTH) , 5 SIDE (SOUTH) /114 MECHANICAL ROOM 110411 I000FI SERVICE HYDRAULIC ELEVATOR ELEVATOR I iYEAR 2 WOIhK I�CONTINUED ON REMOVE GWB WALL "S RISER JFCO /77 h028 RECEIVING 5"ST RISER DWG P100 mito mei SAWCUT FLOOR, REFER TO lop] REMOVAL NOTE 1 (TYP.) COR DOR I028A1 EMOVE WITH SO ORM FD COVER I T 1 IoouE1 CAP ABANDONED PIPE - h527 —.FST --- --1.- 1 1 LAUNDRY 5" STORM RISER COORDINATE WORK WITH EXISTING FIRE ALARM DEVICE ABANDONED PIPE TO REMAIN u (-4" SAN U 11025 CORRIDOR STORM FLOOR s& CLEANOUTS CAPPED OFF AT FLOOR EXIST SANITARY MANHOLE L 4" SAN UP TO FD (TYP. 4) LINT TRAP (TO REMAIN) 110251 CORRIDOR LAUNDRY UNDERFLOOR PIPING TO REMAIN EXIST GENERATOR �2"ST UP SAWCUT FLOOR, REFER TO REMOVAL NOTE 1 (TYP.) INT TRAP UNDERFLOO (TO REMAIN LAUNDRY PIPING EXIST GENERATOR PAD REMOVE FRESH AIR INLET EXIST STORM MANHOLE '$1 REMOVE GWB WALL FOR REPLACEMENT OF PIPE COORDINATE WORK WITH EXI TING TELEPHONE/DATA & ELECTRIC OUTLETS REMOVE F COUNTER & SINKS, STORE A \D REINSTA1}L. REMOVE, STORE AND REINSTALL WATER CLOSETS EXTEND NEW STORM OUTSIDE BUILDING 1100TD1 WOMEN ioouol X38 51 6 SIDE (NORTH) 5 SIDE (SOUTH) /71 J 0248 CORRIDOR 4" SANUP (_579 UMP DISCHARGE UP EXIST SUMP TO REMAIN SUMP PIT WITH PUMP (TO REMAIN) 11523 I OFFICE 115211 �:MUL I—PURPOSE 1::::: R00M I521AI BREAK ROOM NNN:N,NN, REMOVE FLOOR DRAIN AT BOTTOM OF SUMP l J 115221 EQUIPMENT ROOM 4" SAN UP (2550A) ]oouc MECHANICAL ROOM O4" SAN UP (2573 FIR ALLOW FOR REMOVAL & REINSTALLATION ELECTRICAL OUTLETS 3" SAN UP (2570):, I1 REMOVE GWB WALL FOR REPLACEMENT OF PIPE OVE GWB WALL REPLACEMENT PIPE EXISTING (TO REMAIN) // COMPUTER CENTER REMOVE CASEWORK & SINK, STORE AND REINSTALL 1524 PASSAGE 4" FD 115201 4" SAN UP5 (2536A) O I504A1 ADMIN. SUPPORT DINING SERVICES 115191 OFFICE 115181 OFFICE OFFICE 115181 VESTIBULE I514AI 110231 ORIENTATION RA KITCHEN REMOVE BLOCK WALL STORAGE 00081 GENERATOR ROOM ACCESS PIPE TR UGH EIISTING ACCESS DOOR ALLOW FOR REMOVAL' 5 & REINSTALLATION OFA--' 3 ELECTRICAL OUTLET OFFICE REMOVE PLASTER CH FOR REPLACEMENT 0 CONFERENCE ROOM SE = PIPE 11509 RHA OFFICES I509A1 MECH. ROOM 11505 I 11022 11502 I RESOURCE ROOM VESTIBULE 11020 ECORNOR REMOVE BLOCK WALL FOR REPLACEMENT OF PIPE OFFICE OFFICE h516 I DIRECTOS OFFICE 11512 I REMOVE LATH 8c PO N OF WIRE PLAST WALL OFFICE 11506 OFFICE OFFICE RECEPTION 2" VENT UP REMOVE BLOCK WALL FOR R :PLACEMENT OF REMOVE GWB WALL h 524 OFFICE REMOVE, STORE AND REINSTALL WATER CLOSETS SAN UP SAN UP 25B) VESTIBULE 15018 OFFICE OFFICE REMOVE COUNTER & SINKS, STORE AND REINSTALL COORDINATE WALL REMOVAL/REPAIR WITH GFCI OUTLETS (TYP. 2) ALLOW FOR REMOVAL & REINSTALLATION OF WIREMOLD ELECTRICAL OUTLETS UNDERFLOOR PIPING REMOVAL PLAN - SOUTH 7 11 13 15 I Ell Ell IIIII I II Ell Ell Ell REMOVAL NOTES: 1. IN AREAS SHOWN, SAWCUT FLOOR, REMOVE CONCRETE SLAB AND HAND EXCAVATE AROUND SANITARY LINE. REMOVE PIPE AS INDICATED ON DRAWINGS. REMOVE RISERS MINIMUM OF 6" ABOVE FLOOR SLAB. 2. PIPING SHOWN ON DRAWINGS HAS BEEN DEVELOPED FROM PROJECT RECORD DRAWINGS AND FIELD VERIFIED TO THE GREATEST EXTENT POSSIBLE. CONTRACTOR SHALL VERIFY IN FIELD ALL LOCATIONS PRIOR TO REMOVAL OF WALLS AND SAW CUTTING OF FLOOR. 3. REMOVE, STORE AND REINSTALL PLUMBING FIXTURES AS NOTED ON DRAWINGS. 4. CONTRACTOR SHALL REMOVE GWB, PLASTER AND CONCRETE BLOCK WALLS AS SHOWN ON DRAWINGS TO FACILITATE PIPE REPLACEMENT. 5. CONTRACTORS SHALL BE RESPONSIBLE TO PROTECT ABOVE—GROUND PIPING SYSTEMS AND SURROUNDING BUILDING SURFACES I.E. FLOORS, WALLS, ETC. CONTRACTOR SHALL REPLACE ANY PIPE INSULATION, ABOVE GROUND PIPE, AND REPAIR ANY SURFACES DAMAGED IN THE PERFORMANCE OF THIS PROJECT. FOR INFORMATION ONLY THIS DRAWING CONTAINS YEAR 2 WORK, WHICH IS FOR REFERENCE PURPOSES ONLY, AND IS NOT INCLUDED IN THE CURRENT SCOPE OF WORK. 6 SIDE NORTH 5 SIDE SOUTH KEY PLAN NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY o :3 °"c wc; 0 la LU: CI] = iota C "co:°: > -Z( 0 1473 CL 3 17 / 1/0 so t. tir t- 0 tg lal 41.1 III CO NI Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Revision CONFORMED DRAWINGS 0 LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE Project/Sheet Title 1 Piso aR • 4 o 5 Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No C14151 Drawing No. P200 YEAR 2 Sheet No. 5 of 7 N:\915706\Conformed Drawings\P201 YR 2 UF 5 SIDE Conformed.dwg, 3/18/2015 2:52:59 PM, N81 6 SIDE (NORTH) / r 5 SIDE (SOUTH) II X34 MECHANICAL ROOM FCO 11041 SERVICE ELEVATOR 1000F HYDRAULIC YEAR 2 WORK ELEVATOR CONTINUED ON ,_ar. DWG P101 PATCH CO NCRETE OOR ABANDONED 11025 CORRIDOR TORM FLOOR 110281 RECEIVING 5"ST RISER PATCH CONCRETE FLOOR CONNECT TO RISER ABOVE FLOOR TYP. 1 1028A1 10217A]Al CORRIDOR PA FL PIPE 10011E1 4" SAN UP (2589 & 2689) (28 dfu) REMOVE AND REPLACE GWB ENCLOSURE FOR REPLACEMENT OF PIPE PROVIDE STRUCTURAL SUPPORT TO GENERATOR PAD DURING EXCACATION. EXIST GENERATOR —� 2'V UP 4" SAN UP TO FD (TYP. 4) FCO\ S CLEANOUTS CAPPED OFF AT FLOOR 11025 I CORRIDOR 111 1 LINT TRAP EXTEND NEW OUTSIDE OF B EXIST GENERATOR PAD TO REMAIN TORM ILDING " (42 dfu) PROVIDE BUILDING TRAP. REFER TO DETAIL `4 ) 3 P001 EXIST SANITARY MANHOLE PROVIDE PIPE SLEEVE REFER TO DETAIL 4" (70 dfu) EXISTING LINT TRAP & LAUNDRY UNDERFLOOR PIPING TO REMAIN - ® '45 `40 6 SIDE (NORTH) MIME 5 SIDE (SOUTH) EXCAVATE LAWN AREA TO INSTALL BUILDING TRAP AND PIPE. DO NOT UNDERMINE GENERATOR PAD. BACK EXIST STORM FILL AND RESEED REFER TO DETAIL MANHOLE 13-- .» 2" (350 dfu) 6" (280 dfu) 100 UDI WOMEN REINSTALL LAVATORIES (TYP. 3) PAT H CONCRET FLO u R (TYP) REINSTALL WATER CLOSET (TYP. 3 C011 - PUMP DISC ARGE UP CORRIDOR 4" SAN UP 579 PROVIDE FLOOR RAIN , SUMP PIT WITH PUMP- \ XIST SUMP 115231 OFFICE I -PURPOSE ROOM -SLOE € 178" PER FT. MIN. 11522 EXIST EQUIPMENT ROOM looucl MECHANICAL ROOM REPLACE GWB WALL FCO 115041 COMPUTER CENTER 3" SAN UP (2570) REINSTALL SINK & CASEWORK (220 dfu) 6" REPLACE GWB WALL 213 dfu) ." PASSAGE (198 dfu)5 7*.—, SLOPE' 0 1/8" PER FT. MIN. 98 dfu) 5" 1504A 115201 ADMIN. SUPPORT OFFICE 115181 OFFICE OFFICE 115101 DINING SERVICES PATCH CONCRETE FLOOR VESTIBULE 1514A1 '1� TIE INTO EXIST. RISER ABOVE FLOOR (TYP) REFER TO l000BI GENERATOR ROOM 115081 11023 I PASIGF ORIENTATION 188 dfu)5" Em 115114 RA KITCHEN 15048 STORAGE OFFICE CONFERENCE ROOM 115091 RHA OFFICES 1509A MECH. ROOM 11505 I COPY ROOM PATCH CONCRETE FLOOR (160 dfu)4" 11022 I VESTIBULE RESOURCE ROOM (177 dfu) 4" (11 dfu) 4" 115261 OFFICE PROVIDE FLOOR CLEANOUT (TYP. REFER TO C DETAIL PATCH CONCRETE FLOOR (To'P) DIRECTOR'S OFFICE 11512 OFFICE OFFICE 2" VENT UP 115241 OFFICE REINS L WATER CLOSETS 3" SAN UP TO WC UNISEX TOILET 1-1/2" 11 SAN UP O4 SAN UP (2 25B) VESTIBULE 1501A OFFICE 1502AI OFFICE REINSTALL SINKS & CASEWORK UNDERFLOOR PIPING REPLACEMENT PLAN -SOUTH SCALE: 1/8" = 1'-0" 1 /8" 1 0 1 5 7 9 11 13 15 O MI I NM I■ N NOTES: 1. REPLACE UNDERFLOOR SANITARY ON DRAWINGS. REFER TO PIPE 2. BACKFILL AND PATCH CONCRETE 1/P001 AND SPECIFICATIONS. 3. PROVIDE NEW FLOOR CLEANOUTS AS INDICATED ON THE DRAWINGS 4. PROVIDE EXTERIOR BUILDING TRAP AS NOTED ON PLANS. 5. PROVIDE CLEANOUT AT THE BASE OF EACH RISER REFER TO DETAIL 6/P001 6. ALL PIPE SHALL BE SLOPED AT 1/8" PER FOOT MINIMUM 4" AND ABOVE, AND 1/4" PER FOOT MINIMUM SMALLER THAN 4". & STORM PIPING AS INDICATED SCHEDULE FOR PIPE MATERIALS. FLOOR. REFER TO DETAIL 7. CONTRACTORS SHALL BE RESPONSIBLE TO PROTECT ABOVE GROUND PIPING SYSTEMS AND SURROUNDING BUILDING SURFACES I.E. FLOORS, WALLS, ETC. CONTRACTOR SHALL REPLACE ANY PIPE INSULATION, ABOVE GROUND PIPE, AND REPAIR ANY SURFACES DAMAGED IN THE PERFORMANCE OF THIS PROJECT. 8. REFER TO FINISHES REPLACEMENT PLANS FOR WALLS TO BE REPLACED. FOR INFORMATION ONLY THIS DRAWING CONTAINS YEAR 2 WORK, WHICH IS FOR REFERENCE PURPOSES ONLY, AND IS NOT INCLUDED IN THE CURRENT SCOPE OF WORK. L 6 SIDE NORTH 5 SIDE SOUTH 2 KEY PLAN P201 NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY IT IS A VIOLATION OF THE O 0 -a 0 cc CO 0 ID dam' 03 0) d' 0W N 0 >- ▪ y ra CD .• 43� N 7:-Z L y CO _. W 0 at.0 cia v d^- cn 3� r4 T1 c N. m N c 0 Cs. 0e 2 8 a) a) cric a) a.E 0 v-- M Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON 0 0 .N 0 Cr CONFORMED DRAWINGS 0 Z C 1 catt' ck$ 0 c.) ca Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P201 YEAR 2 Sheet No. 6 of 7 N:\915706\Conformed Drawings\P202 YR 2 FIN 5 SIDE Conformed.dwg, 3/18/2015 2:57:54 PM, N81 6 SIDE (NORTH) 5 SIDE (SOUTH) 115341 CONCRETE MECHANICAL FROOM LOO FC0 TANK PROVIDE STUD/SHEETROCK WALL 110281 RECEIVING 5" ST RISER 110411 SERVICE ELEVATOR RISER 1000F1 HYDRAULIC ELEVATOR 1o27A1 VINYL TILE CORRIDOR "1 * — 6 SIDE (NORTH) 5 SIDE (SOUTH) CONCRETE FLOOR\ STORM 1 SOLID C WITH ER 000E1 VINYL TILE 115271 LAUNDRY PROVIDE STUD/SHEETROCK WALL 5" STORM RISER CORRIDOR STORM FLOOR •AINS& CLEANOUTS CAPPED OFF AT FLOOR '45 4" SAN UP TO FD (TYP. 4)-1 LINT TRAP 11025 Wilipp2Pia r../ ISM RIK WW1 ipil•Proco.c.) /8" GWB 3-5/8" � METAL STUD 111 METAL STUD WIRE LATH 1/2" — 5/8" PLASTER WIRE STUD WIRE LATH 2 WALL REPLACEMENT DETAILS P202 NOT TO SCALE DEPTH VARIES (MATCH EXISTING) CONCRETE BLOCK 3/8" GROUT • AINT ROOM SIDE NOTES: 1. THIS DRAWING IS INTENDED TO SHOW RESTORATION OF FINISHES ONLY. REFER TO DRAWINGS P200 & P201 FOR PIPING REPLACEMENT WORK. 2. CONTRACTOR SHALL RESTORE SURROUNDING FINISHES AFTER REPLACEMENT OF UNDERFLOOR PIPING. WORK INCLUDES REPLACEMENT OF CARPET, CERAMIC TILE AND VINYL TILE IN LOCATIONS SHOWN ON DRAWINGS. REPLACE STUD/ SHEETROCK AND CONCRETE BLOCK WALLS AS NOTED ON PLANS AND AS REQUIRED TO RESTORE TO PRECONSTRUCTION CONDITION. ALL WALLS IN CONSTRUCTION AREA SHALL BE PAINTED, COLOR SELECTED BY OWNER. 3 CONCRETE BLOCK WALL REPLACEMENT SECTION DETAIL NOT TO SCALE 48, EXISTING LINT TRAP & LAUNDRY UNDERFLOOR PIPING CONTINUED ON P200 PROVIDE STUD/SHEETROCK WALL CERAMIC TILE CARPET TILE UMP DISC RGE UP 0 4" SAN UP (2573 FIR 115041 COMPUTER CENTER PROVIDE STUD/SHEETROCK WALL REMOVE & REINSTALL SINK AND CASEWORK REPAIR WALLS CARPET TILE 1504A1 115201 ADMIN. SUPPORT 4" SAN UP (2530B) PROVIDE PATCH OF 150481 CONCR E BLOCK WALL STORAGE REPAIR WALL BASE AT PIPING CROSSING (TYP) CARPET RHA OFFICES TILE 1509A1 MECH. ROOM CONCRETE FLOOR --1 COPY CARPET TILE ROOM PROVIDE STUD/SHEETROCK WALL (TYP) REFER TO, RESOURCE ROOM 150281 OFFICE CARPET TILE OFFICE PROVIDE PATCH OF CONCRETE BLOCK WALL REPAIR WIRE LATH & PLASTER WALL 1-1/2"0 SAN UP PROVIDE PATCH OF CONCRETE BLOCK WALL REFER TO DETAIL 4" SAN UP (2525B) 110211 VESTIBULE 1501A1 OFFICE OFFICE PROVIDE STUD/SH ROCK WALL FINISHES REPLACEMENT PLAN - SOUTH SCALE: 1 /8" = 1'-0" 1 /8" = " FOR INFORMATION ONLY THIS DRAWING CONTAINS YEAR 2 WORK, WHICH IS FOR REFERENCE PURPOSES ONLY, AND IS NOT INCLUDED IN THE CURRENT SCOPE OF WORK. 1 0 1 3 5 7 9 11 13 15 1 E - — e 1 ■ = O MN 6 SIDE NORTH 5 SIDE SOUTH 4 KEY PLAN %i P202 NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE O C� — a 0 c L co a) Ti) 3 _ ( W CO• •e. Y/ - A+- W C) 4D 0 av 0 0 ! L. ri d' a (Ni CU Q o » cm a) m z W35. 3 :J so 8 a) a) •c c a) 0 a) a) 3"IIR� PROl�G e caM 00o Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Revision CONFORMED DRAWINGS ciZ 1 Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P202 YEAR 2 Sheet No. 7 of 7 N:\915706\Conformed Drawings\P301_P302.dwg, 3/18/2015 2:58:36 PM, N81 6 SIDE (NORTH) 5 SIDE (SOUTH) I,VVI VI SERVICE ELEVATOR HYDRAULIC ELEVATOR 110111111111111 5' ST UP & DN SAN PIPE (SERVES RM 26 6 SIDE (NORTH) MINN 5 SIDE (SOUTH) RECEIVING CORRIDOR 5" ST UP & DN STAIR ROOF AT 2ND FLOOR LEVEL 4" SAN DN (2589 & 2689) hooud 15271 4 SAN UP T. WC SAN PIPE (SERVES 'M 2589) 11025 1 CORRIDOR 2" VENT UP 5" ST UP & DN 115271 a LAUNDRY 3"SN UP TO F 1111111110 111111111 111111111111 2" SAN UP TO SH (TYP 2) 2" ST UP TO RD 44 FOR INFORMATION ONLY THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES PIPE AT CEILING (TYP.) 10251 CORRIDOR (100TD 4" SAN UP & DN (_579 & 2573 FIR) 1-1/2" SAN UP TO TUB 2" PU DISCHA CORRIDOR 3" SA UP TO WC 115231 MULTI-PU ROO BREAK ROOM OFFICE PASSAGE MECHANICAL ROOM EXISTING SPLIT SYSTEM AIR CONDITIONER WITH INTEGRALI CONDENSATE PUMP (TYP). EXISTING SINK DRAIN PUMP 3 SAN UP TO FD 3" VENT STACK 11520 2" SAN UP 111 TO SH 1 15221 EQUIPMENT ROOM 4" SAN DN (2550A) AD FOR CO AGAIN. SUPPORT COMPUTER CENTER EXISTING 3/4" AC DRAIN ABOVE CEILING PASSAGE —4" SAN UP (2536A) 1-1/2" SAN UP TO SINK h 504A1 15141 DINING SERVICES EXISTING DRAIN HUB 11519 OFFICE 115181 OFFICE 115171 OFFICE VESTIBULE OFFICE 115091 PASSAGE ORIENTATION RA KITCHEN 4' SAN DN (2530B) STORAGE 2" SA GENERATOR ROOM 2" SAN UP 115131 OFFICE 3" SAN UP TO WC 11509 RHA OFFICES 1509/ MECH. ROOM 3" U TO W0 COPY ROOM 3" SAN TO FD CONFERENCE ROOM VESTIBULE 4" SAN UP&DN (_522 STACK) 3" SAN UP (_522 SH STA 115021 CORRIDOR LOWER LOBBY OFFICE OFFICE 115161 DIRECTOR'S OFFICE 115121 OFFICE OFFICE 115011 11502d OFFICE RECEPTION 115241 4 4" SAN DN (2529B) 1-1/2" SAN UP OFFICE 4" SAN DN (2525B) UNISEX TOILET 1 1 021 1 VESTIBULE h501A1 OFFICE 11502A1 OFFICE EXISTING FIRST FLOOR PLUMBING PLAN - SOUTH SCALE: 1/8" = 1'-0" /8" 1 0 1 3 5 7 9 11 13 15 1 _ 1E1 all MI 1 1 IN 1 e 6 SIDE NORTH 5 SIDE SOUTH CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW. IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE O 6 SIDE (NORTH) 5 SIDE (SOUTH) Po war 118111181111111. lawmais 11639 SINGLE ROOM h6394 CLOSET f 116411 SINGLE ROOM 116414 CLOSET 116431 SINGLE ROOM 11643A CLOSET ft 2" V DN 3" SAN 116751 SINGLE ROOM 116754 CLOSET 116731 SINGLE ROOM 116734 CLOSET 16711 SINGLE ROOM 116741 116691 SINGLE ROOM 116714 CLOSET h 669 CLOSET c\--1-1/2" UP (SINK -2673) 4'" SAN UP & DN (_679 SH STACK) DOUBLE 3"SAN TO ROOM WC (2673A) 1-1/2" SAN UP TO TUB (2673A) 116671 SINGLE ROOM h 665A1 CLOSET 116651 SINGLE ROOM 116791 3"SAN UP TO WC 11535 PROJECT ROOM 2"SAN UP TO SH (TYP 2) 11534 MEN'S BATH ROOM O 3"SAN UP TO FO 46701 SINK ROOM 116681 STORA 11538 MEN'S LOCKER ROOM ill2"SAN UP • TO LAVS (2673A) 4" SAN UP & DN (_679 WC STACK) 11539 STORAGE 4" VENT STACK 2"SAN UP TO LAVS CONTINUED N MECHANICAL DRAWING 102 ROOM 5" ST UP & DN SAN PIPE (SERVES RM 26 PIPE AT CEILING TYP. I r 8 z 2" VENT UP 11041 3" N UP FD 2"SAN UP TO UR SERVICE ELEVATOR 115371 BREAK ROOM SPRINKLER ROOM 11000E HYDRAULIC ELEVATOR 15361 I� 31"SAN UP TO WC CORRIDOR — 2" V UP 116631 SINGLE ROOM 110291 F 16634 CLOSET L 116611 SINGLE ROOM 116591 SINGLE ROOM R 2"SAN UP TO SH t�I 116621 4" STORAGE " 116594 CLOSET 1645 DOUBLE ROOM 116471 STORAGE ■ • 1-1/2'V (1637 BATHROOM 4" SAN DN (2631 B) 116381 LINEN CLOSET LIe 1-1/2" SAN UP TO LAV 11635 SINGLE ROOM 4" SAN UP TO WC 1-1/2" SAN O UP TO TUB \ CLOSET h 6354 L1-1/2" SANT I UP TO LAV 10081 STAIR UP INN 4" SAN DN (2636A) 2" SAN UP TO LAVS CO 116484 STORAGE 4" SAN DN ' (2670 & 2650A) 2" SAN UP TO LAVS (2650A) -- 4" SAN UP TO WC (TYP 3) 1027 CORRIDOR 0 `�i�2"STDN 1100001 HOT WATER TANK mammal 110271 CORRIDOR 2" ST UP TO RD 111111111111111 MEM 6 SIDE (NORTH) 5 SIDE (SOUTH) —3" SAN UP 4" SAN UP TO WC 116331 SINGLE ROOM 11631 SINGLE ROOM 110311 CORRIDOR 4" SAN DN (2629B) 1629 SINGLE ROOM 1-1/2" SAN UP TO TUB h 6294 CLOSET 1627 SINGLE ROOM h627A1 CLOSET 4" SAN UP TO WC 116251 SINGLE ROOM 4" SAN DN (2625B) 116254 CLOSET 16231 SINGLE ROOM 116234 CLOSET 4" WC SAN STACK 16211 SINGLE ROOM 1621A, CLOSET 10641 SINK ROOM 4" SAN DN 1063 DATA 3" SAN UP 110621 TC (_622 STACK) (_622 SH STACK) MECHANICAL 4" SAN UP TO WC IPE AT CEILING TYP. 1-1/2" SAN UP TO TUB BIKE STORAGE 4" SAN UP TO WC i-2"PUMP DISCHARGE DIN 116501 MECHANICAL ROOM 4" SAN DN (2630B) 116480 2" SAN UP TO LAV EXISTING FIRST FLOOR PLUMBING PLAN - NORTH SCALE: 1 /8" = 1'-0" 1 1 /2" SAN —� UP TO SINK (2624) 3" SAN UP TO WC (TYP 3) 23" SAN UP TO FD 116221 MCLLU DEN 2" SAN UP TO LAVS h 6224 CLOSET C 4" SAN UP (LAV&SH STACK) 116181 STORAGE • . 1 2" SAN UP TO SH (TYP 3) 3" SAN UP TO FD 110621 ATC 2" SAN UP TO ' SH (TYP 3) 110091 STAIR II UP J 11619 STORAGE 116171 KITCHEN 11615 RECREATION ROOM 1/8" = 1,_0„ FOR 1NFORMATION ONLY THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES 1 0 1 3 5 9 11 13 15 I E e E E 1■ Es m ME CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. 5 THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY A DESCRIPTION OF THE ALTERATION. IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE 0 0 c 3/18/15 I Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Revision CONFORMED DRAWINGS Z C 9, 8 8 crz4 ,.T.4 r..7.4 cl.) '14 '11.41 g a ....4 Q" 0.4 w 3 O�U c.- 1 Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P302 Sheet No. 2 of 6 N:\915706\Conformed Drawings\P303_P304.dwg, 3/18/2015 2:59:32 PM, N81 6 SIDE (NORTH) 5 SIDE (SOUTH) �21 12597 COMPLEX CONGRESS 5" ST UP ROOF DRAIN • (25951 STUDY 12595 STUDY 125931 STUDENT STAFF 126924! CLOSET SINGLE ROOM 5" ST UP & DN 5" ST DN 1 20101 STAIR 4"SAN DN 1 3"V UP _ ''41iL. 5" ST UP & DN 12591 DOUBLE ROOM 12591E CLOSET r 120001 STORAGE 3"SAN DN 125914! CLOSET 1 kAl II FD 2"V DN 2" SAN DN (TYP 2) 1 12589 BATH ROOM L 2587 SINGLE ROOM 1258741 CLOSET 125851 SINGLE ROOM 125854 / CLOSET 2"SAN UP 12583] SINGLE ROOM 125834! 2594 (259241 CLOSET 2"SAN DN 2" V RISE 120271 CORRIDOR CLOSET l i 3"SAN UP PIPE AT CEILING TYP. 2"SAN UP 12581 k581d CLOSET FACULTY -IN - RESIDENCE 125941 PROGRAM LOUNGE 25921 SINGLE ROOM RD 555 VESTIBULE 12590A CLOSET (25901 SINGLE ROOM 125884 CLOSET 125881 SINGLE ROOM 125864! CLOSET > 2586 SINGLE ROOM - 1 K564� CLOSET CLOSET 125844! 4" VENT 1-1/2" SAN DN 125734 FACULTY -IN - RESIDENCE 12.573E CLOSET 125730 FACULTY -IN - RESIDENCE '•• 12038] CORRIDOR 125810! OS€t �� 2584 DOUBLE ROOM 12573d BATH ROOM 3"V UP & DN O 0 O 0 1-1/2" J -SAN DN 0 125734 4" SAN STACK (_579) 3" SAN DN /\_ 125824 CLOSET 125824! CLOSET 2"SAN 2"VRI 1 FACULTY -IN - RESIDENCE N 125821 DOUBLE ROOM i I F I 2"V UP—o 125701 BATH ROOM 2"V DN 12571 DOUBLE ROOM 110 RD 6 SIDE (NORTH) 0 0 0 5 SIDE (SOUTH) 4" SAN DN (TYP 3) 2" V UP 2025 VESTIBULE 1255041 WOMENS TOILET 20041 STAIR 3 2" SAN DN DN 3" SAN DN 12027 CORRIDOR 12569 SINGLE ROOM 120261 125501 TOILET ROOM VESTIBULE 0 0 2" SAN DN 2" V UP 125371 LOUNGE 12401 LI ING ROM 4" SAN DN (TYP 2) 2"VUP 2" SAN DN 12535 STUDY 12533 GROUP STUDY 25381 PANTRY 0 0 12536 BIKE ROOM 12.5368 MENS TOILET 120031 STAIR 11 UP A 12024 PASSAG 125341 SINK ROOM L 12532 STORAGE 530 PRIVATE BATH 2"VUP 12530 BED ROOM 2" SAN DN wig gri CLOSET 15304 CLOSET 2" SAN DN 2"VUP 125301 3"SAN DN LIVING ROOM 2" V DN 120231 CORRIDOR 125311 RHD 125314 BED ROOM 1 2"VUP 125290 BED ROOM 4" SAN DN '529; PRIVATE BATH 12529E1 HALL 125294 CLOSET 1529d CLOSET 120221 VESTIBULE FOR INFORMATION ONLY THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES 25021 SINGLE ROOM 125024! CLOSET 125044! CLOSET 12504 SINGLE ROOM 12506 SINGLE ROOM 125068 CLOSET 2508] SINGLE ROOM 1250841 CLOSET 2" SAN DN UP 120011 STAIR 1 2" V UP 2" SAN UP 125261 SINGLE ROOM PIPE AT CEILING TYP. 125291 LIVING ROOM 1252601 CLOSET rii`mmil 1 1 1/2" SAN DN 12527 2" SAN DN' 25241 KITCHEN 3" UP ATO WCO H 4" V U CUSTODIAL 2" V UP 0 125254! CLOSET 4" SAN DN 125251 PROGRAM 5254 ASST. PRIVATE BATH 0 0 0 0 r-°'4\2" SAN DN i 125234 CLOSET 12523 SINGLE ROOM 125221 BATH/TOILET ROOM R EU1U 4" SAN .. 3" SAN UP&DN UP&DN CORRIDOR 120201 125211 --- HOUSE MAID CLOSET J EXISTING SECOND FLOOR PLUMBING PLAN - SOUTH SCALE: 1/8" = 1'-0" 151911 CLOSET 3" SAN D 125191 DOUBLE ROOM 5194 CLOSET 12501 SINGLE ROOM 125014! CLOSET 125030 CLOSET 12503 SINGLE ROOM 1250541 CLOSET 12505 SINGLE ROOM 125074 CLOSET 12507! SINGLE ROOM 125094! CLOSET�� \ v 12509 SINGLE ROOM s 12511 SINGLE ROOM CLOSET 125134 CLOSET \ v 125131 SINGLE ROOM 125151 SINGLE ROOM 51544 CLOSET J 127171 DOUBLE ROOM 1251744 CLOSET 12.51701 CLOSET 1 /8" = 1'-O" 1 0 1 5 9 11 13 15 I s — M1 1■is L 6 SIDE NORTH 5 SIDE SOUTH 2 KEY PLAN P303 NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. 5 THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. LAW- FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE O 0 - a 0 C i co 5 • _ 0 W c O ._ N�•+ L. 3 - av 4.1 ci 3/18/15 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Revision CONFORMED DRAWINGS 1 E • '41 o Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P303 Sheet No. 3 of 6 z z 0. 0 N N 8 3 0. a MI 0 m 0 w 8 0 0 ti 0 rn z 6 SIDE (NORTH) 5 SIDE (SOUTH) 244 19 r 12677 SINGLE ROOM 12675 DOUBLE ROOM 126731 LIVING ROOM I 1-1/2" SAN DN 2" SAN UP TO SH DRAIN TYP. 5 126791 DOUBLE ROOM O 0 O 0 1267501 LOSET 126734 LOSET 4" SAN UP & DN (_679 SH STACK) b 11111111111 • 3" UP TO FD 'Z' 3" SAN DN 12679d CLOSET 126794 CLOSET PIPE AT CEILING TYP. 3" SAN UP (_679 LAV STACK) TYP. 3 12675E CLOSET TOIL 1 12028 CORRIDOR 2" SAN UP TO SH DRAIN TYP. 3 2 SAN DN CLOS 3" UP --�. TO FD TYP. 2 12681 DOUBLE ROOM . 12671 12670 12669A CLOSE 126691 SINGLE ROOM 4" SAN DN BATH ROOM © 3" FD . 0 1=i 1-1/2" SAN DN 126801 DOUBLE ROOM 4" SAN UP & DN (_679 WC STACK) CLOSET CLOSET 681 CLOSET 126831 SINGLE ROOM 12683A CLOSET 126851 SINGLE ROOM 126850 CLOSET 126871 SINGLE ROOM 2"SAN DN 126874 CLOSET 3"SAN DN 12691 RHD -11111111111- - 125971 COMPLEX CONGRESS 5" ST UP ROOF DRAIN 1268981 CLOSET 4" VENT STACK 682 CLOSET 126821 DOUBLE ROOM CLOSET 12654 HOUSE MAID CLOSET 2 2" VENT SH DRAIN 12006 STAIR 3N 1 12031 FOYER 12652 CONTROL OFFICE 12633 STUDY ROOM 4" SAN DN (TYP. 3) 1268601 CLOSET 12686 SINGLE ROOM 2595 CTI IfY • 5" ST UP & DN 5" ST DN 1 1268801 CLOSET 12688 SINGLE ROOM 1269041 CLOSET 2690 SINGLE ROOM 126924 CLOSET 126921 SINGLE ROOM RD 12594 120301 VESTIBULE 6 SIDE (NORTH) 5 SIDE (SOUTH) 12650 TOILET ROOM VESTIBULE :®O 12650A WOMENS TOILET 12635 ARD OFFICE (2637 LOUNGE 2" SAN DN 2" V RISE 12032 PASSAGE 1-1/2" 1S AN DN 126311 ARD 12631E1 CLOSET 1-1/2" SAN DN 1-1/2" SAN DN 12631d CLOSET 111 „2"VUP . 1263101 BED a ROOM 4" SAN DN '631: PRIVATE BATH 629: PRIVATE BATH 4" SAN DN 1262901 BED ROOM 2"V UP 1 • 12629d inICLOSET 12629E HALL 12629E CLOSET 126291 LIVING ROOM 120081 STAIR 1 DN 120341 CORRIDOR 126321 STORAGFi 2"VUP 1263001 BED ROOM 4" SAN DN PRIVATE BATH r 126304 HALL 12630C CLOSET 12630E1 CLOSET 1- 2630 LIVING ROOM 1-1/2" SAN DN 120331 VESTIBULE • UP II 12007 STAIR 2N 2" SAN DN 2" V RISE 12636 TOILET ROOM VESTIBULE 126381 PANTRY 1263641 MENS TOILET 4" SAN DN 12640 LIVING ROOM EXISTING SCALE: 1/8" = 1'-0" SECOND FLOOR PLUMBING PLAN - NORTH 4" SAN DN 12627 LINEN CLOSET 12626A CLOSET 126261 PRIVATE BATH 12625] RESIDENT ADVISOR 2" V UP 129250] CLOSET 12623 SINGLE ROOM 12623 CLOSET 4"VUP SINGLE ROOM 3 SAN UP & D 126240 CLOSET 12624 KITCHENETTE 126191 DOUBLE ROOM 3" SAN UP & DN 126211 HOUSE MAID CLOSET 12619E CLOSET 1261901 CLOSET 4" SAN UP & DN (WC STACK) 64 0 Q 3" FD 3" STAC 126221 TOILET/BATH ROOM 126171 DOUBLE ROOM 126174 CLOSET 617E CLOSET 4" SAN UP & DN (SH STACK) r g 3" FD 0 3 0 -3" SAN UP & DN • • • V RISER 4" SAN UP & DN (_622 LAV & SH STACK) UP 11 _1 126081 SINGLE ROOM 126084 CLOSET 1260601 CLOSET 12606 SINGLE ROOM 26041 SINGLE ROOM 1260401 CLOSET 12602 SINGLE ROOM 1260201 CLOSET 126158 CLOSET 126151 SINGLE ROOM 126131 SINGLE ROOM 12611 SINGLE ROOM 126091 SINGLE ROOM CLOSET 126074 126071 SINGLE ROOM 12605 SINGLE ROOM CLOSET 12603A CLOSET 2603 SINGLE ROOM 1260101 CLOSET 126011 SINGLE ROOM FOR INFORMA11ON ONLY THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES 1/8" = V_0„ 1 6 SIDE NORTH 5 SIDE SOUTH KEY PLAN NOT TO SCALE 1 0 1 3 5 7 9 11 13 15 CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. 1 al NM E E 1 I E 1 THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE O 0 a co = i co a) 5 C) 3 i (� W 0 L.wR N W -c as o av • 0 O L N co L h 01 V _ DI ca. ao�@% Z c(n o a) o a— oaa,03 o 0 THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES 1/8" = V_0„ 1 6 SIDE NORTH 5 SIDE SOUTH KEY PLAN NOT TO SCALE 1 0 1 3 5 7 9 11 13 15 CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. 1 al NM E E 1 I E 1 THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY IF ALTERED, THE ALTERING PROFESSIONAL SHALL AFFIX THEIR SEAL AND THE NOTATION "ALTERED BY", FOLLOWED BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION AND A DESCRIPTION OF THE ALTERATION. LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE O 0 a co = i co a) 5 C) 3 i (� W 0 L.wR N W -c as o av • 0 O L N co L h 01 V _ DI ca. ao�@% Z c(n o a) o a— oaa,03 o 0 3/18/15 I Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON C 0 .y Cr CONFORMED DRAWINGS oCZ rT w c°1-4) a ck3 O� Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P304 Sheet No. 4 of 6 N:\915706\Conformed Drawings1P305 P306.dwg, 3/18/2015 3:01:03 PM, N81 6 SIDE (NORTH) ------ 5 SIDE (SOUTH) 0 ROOF DRAINAGE DOWNSPOUT 5" CI ST DN ROOF RD (UNDER PAVERS) 5" CI ST DN 13011 STAIRS ELEVATOR LOBBY — --inn 12010 STAIR PROGRAM IOUNGF 1 IN; PROGRAM LOUNGE 0 ROOF DRAINAGE DOWNSPOUT 13591 SINGLE ROOM 135891 SINGLE ROOM 135871 SINGLE ROOM 3585 SINGLE ROOM 2" SAN UP & DN 13583 SINGLE ROOM F-2" V 3" SAN UP & DN 2" V 2" SAN UP & DN J 2" —I 5 • 1 f p3 FD "FD® 2" V 1 3577 SINGLE ROOM 3" SAN UP & DN L • 31 ■ .44111111111 13579 BATH - TOILET 3"FD 0 135921 SINGLE ROOM 13590 SINGLE ROOM 135881 SINGLE ROOM 135861 SINGLE ROOM J 13584 SINGLE ROOM 4" V RISER MIN (3V82] SINGLE ROOM 13580 SINGLE ROOM 4" SAN UP & DN 2"VUP&DN 3" SAN UP & DN 3575 SINGLE ROOM 135731 SINGLE ROOM 135711 SINGLE ROOM • 3569 INGLE OOM 135681 TRASH ROOM 6 SIDE (NORTH) 5 SIDE (SOUTH) 0_ (-2" V RISER — 3" SAN UP 135661 INK '11 (30041 & DN STAIR 3 135621 DOUBLE ROOM 135671 SINGLE ROOM 135651 SINGLE ROOM 135631 SINGLE ROOM 2"VDN—�^ 3560] SINGLE ROOM vr." 3561 SINGLE ROOM 135591 SINGLE ROOM r_2"VDN 135581 SINGLE ROOM 135561 SINGLE ROOM 3557 STORAGE 13549 SINGLE ROOM 3547 SINGLE ROOM 13545 SINGLE ROOM 135431 SINGLE ROOM 13541 SINGLE ROOM 1 3539 SINGLE ROOM 135541 DOUBLE ROOM 1 135521 SINGLE ROOM 135501 SINGLE ROOM 130031 STAIR D UP 2" SAN DN 1 ) " V RISE, 135461 CUSTODIAL "-2" SAN UP & DN FOR INFORMA11ON ONLY THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES 135021 SINGLE ROOM 13504 SINGLE ROOM 35011 SINGLE ROOM 1 35061 SINGLE ROOM 35081 SINGLE ROOM 1 13503 SINGLE ROOM 135051 SINGLE ROOM 135071 SINGLE ROOM 3" SAN UP&DN 135341 KITCHENETTE —. (NOTE: FOURTH & FIFTH FLOOR SIMILAR) 13536 STORAGE 3537 DOUBLE ROOM 135351 SINGLE ROOM 2" V DN 135321 SINGLE ROOM 2"VUP 13530] SINGLE ROOM 13533 SINGLE ROOM 13531 SINGLE ROOM PIPE AT CEILING TYP. 135281 SINGLE ROOM 135261 SINGLE ROOM 0 2" V-1' 0 0 0( 2" V 13522 BATH - TOILET UP 2"VUP&DN -3" SAN UP &• DN 1 1 1 1 1 130011 STAIR • 2" SAN UP & DN -v .O 4" V UP & DN 13529 SINGLE ROOM 135271 SINGLE ROOM 35251 SINGLE ROOM 35231 SINGLE ROOM I1 3" FD 4" SAN UP & DN I I� 3" SAN UP&DN 13520 CUSTODIAL EXISTING THIRD FLOOR PLUMBING PLAN - SOUTH SCALE: 1/8" = 1'-0" 1 135211 DOUBLE ROOM 13509 SINGLE ROOM 3511 SINGLE ROOM 135131 SINGLE ROOM 135151 SINGLE ROOM SINGLE ROOM 135191 SINGLE ROOM 1 /8" If 1 0 1 3 5 11 13 15 II M 11.11 I■ — O M 6 SIDE NORTH 5 SIDE SOUTH KEY PLAN NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HERON AS REQUIRED BY LAW. LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE O 0 - a 0 C i 0 • O) 3i C5 W 0) 0!A - L. A` W C 4) 0 av J_ 40 o CI LO 03 M Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Revision CONFORMED DRAWINGS z C 1 1 0-1 0-4 Ooh Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P305 Sheet No. 5 of 6 N:\915706\Conformed Drawings\P305 P306.dwg, 3/18/2015 3:01:24 PM, N81 6 SIDE (NORTH) 11 MEM 5 SIDE (SOUTH) SINGLE ROOM SINGLE ROOM DOUBLE ROOM DOUBLE ROOM SINGLE ROOM SINGLE ROOM 2"V RISER SINGLE ROOM SINGLE ROOM 2" V DN SINGLE ROOM 136271 SINGLE ROOM 13625 SINGLE ROOM 2" V DN SINGLE ROOM 2"V RISER r3" SAN UP 13617 SINGLE ROOM 13636 ELEC PANELS SINK ROOM SINGLE ROOM 36151 SINGLE ROOM 4" V RISER 4"SAN UP & D SINGLE ROOM 3613 SINGLE ROOM 2" V RISER 136471 SINGLE ROOM STORAGE . nn 136321 SINGLE ROOM SINGLE ROOM 136281 SINGLE ROOM SINGLE ROOM 3" SAN UP & DN SINGLE ROOM 2' V RISER 130071 STAIRS 5 4" SAN UP& DN (LAV & SH STACK) 3" V RISER SINGLE ROOM 13609 SINGLE ROOM 136501 SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM 136671 SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM 136591 SINGLE ROOM 36571 13607 SINGLE ROOM STORAGE ROOM 13606 SINGLE ROOM 13605 SINGLE ROOM 2"VUP& DN 3"VU & DN 130061 STAIRS 4 4" SAN UP & DN _679 SH STACK SINGLE ROOM 136031 SINGLE ROOM 136801 TRASH ROOM 136601 SINGLE ROOM SINGLE ROOM SINGLE ROOM 136541 DOUBLE ROOM 4" SAN UP & D RISER 4" SAN UP & DN _679 W STACK 136021 SINGLE ROOM SINGLE ROOM 3" SAN UP & DN 3" FD 136791 SINGLE ROOM 4"VUP & DN 13682 SINGLE ROOM 3" SAN UP & DN 13683 SINGLE ROOM 13684 SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM SINGLE ROOM 13690 SINGLE ROOM ROOF 11111111.-111111.11-111111111111-01111F ROOF DRAINAGE DOWNSPOUT 5" CI ST DN ELEVATOR LOBBY 6 SIDE (NORTH) 5 SIDE (SOUTH) (NOTE: FOURTH & FIFTH FLOOR SIMILAR) � EXISTING THIRD FLOOR PLUMBING PLAN - NORTH P306 SCALE: 1/8" = 1'-0" FOR 1NFORMA11ON ONLY THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES 1 /8" = 1'-0" 1 0 1 3 7 9 11 13 15 MI al NM N I■ I = MN 6 SIDE NORTH 5 SIDE SOUTH KEY PLAN NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC. SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE 0 0 0 -a ci co a) 3 i 0 W C 0) 0 2.) •ir - av 8 L O c a) E 0 co .'2i 0 THIS DRAWING SHOWS EXISTING CONDITIONS AND IS INTENDED FOR USE AS REFERENCE ONLY. WORK TO BE PERFORMED FOR THIS PROJECT IS SHOWN ON DRAWING P001 AND DRAWINGS OF THE P100 & P200 SERIES 1 /8" = 1'-0" 1 0 1 3 7 9 11 13 15 MI al NM N I■ I = MN 6 SIDE NORTH 5 SIDE SOUTH KEY PLAN NOT TO SCALE CONFORM TO INDICATED DIMENSIONS RATHER THAN DIMENSIONS SCALED FROM DRAWING. GRAPHIC. SCALE PROVIDED HEREIN FOR GENERAL INFORMATION AND TO CONFIRM WHEN DRAWING SIZE HAS BEEN REDUCED OR INCREASED IN REPRODUCTION. THIS STATEMENT IS PROVIDED HEREIN AS REQUIRED BY LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ENGINEER TO ALTER THIS DOCUMENT IN ANY WAY. IT IS A VIOLATION OF THE 0 0 0 -a ci co a) 3 i 0 W C 0) 0 2.) •ir - av 8 L O c a) E 0 co .'2i 0 3/18/15' Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Revision CONFORMED DRAWINGS z C Scale AS SHOWN Date 12/31/14 Drawn K.A. SNYDER H. JUNUZOVIC Designed K.A. SNYDER Checked P.A. PETERSON Project No. C14151 Drawing No. P306 Sheet No. 6 of 6