HomeMy WebLinkAboutHollister Hall - Third Floor Classroom AV Upgrades Room 366NJS RFG H-000 SYMBOLS LIST - HVAC GENERAL NOTES & DUCT CONTINUED DOUBLE LINE RECTANGULAR T T E PNEUMATIC/ELECTRIC THERMOSTAT AIR FLOW NTS NOT TO SCALE PIPE ANCHOR (DBL) PIPE GUIDE CFM CUBIC FEET PER MINUTE EXPANSION COMPENSATOR WITH GUIDES AD ACCESS DOOR PRE-FAB EXPANSION LOOP P.C.PLUMBING CONTRACTOR STRAINER N.O.NORMALLY OPEN PRESSURE GAUGE DSD DUCT SMOKE DETECTOR THERMOMETER H HUMIDISTAT UNION AIR VENTV ROUND DUCT - IN INCHES12" TT THERMOSTATIC TRAP SQUARE TO ROUND TRANSITION FT FLOAT & THERMOSTATIC TRAP UP OR DOWN RETURN DUCT TURNING 24x12 10x8 DN UP DN UP TD THERMODYNAMIC TRAP10"14" TEE CONICAL 8"18"ROUND BRANCH ROUND MAIN SUPPLY/RETURN BT BUCKET TRAP REGISTER OR GRILLE RETURN OR EXHAUST DIRECTION OF FLOW VOLUME DAMPER BBD BOILER BLOW DOWN CWS CHILLED WATER SUPPLY CWR CHILLED WATER RETURN D DRAIN FUEL OIL FILLFOF FUEL OIL GAUGEFOG FOS FUEL OIL SUPPLY FOR FUEL OIL RETURN FOV FUEL OIL TANK VENT G GAS GLYCOL SUPPLYGS GLYCOL RETURNGR HWS HOT WATER SUPPLY HWR HOT WATER RETURN HG HOT GAS LPS LOW PRESSURE STEAM LPC LOW PRESSURE CONDENSATE MPS MEDIUM PRESSURE STEAM MPC MEDIUM PRESSURE CONDENSATE HPS HIGH PRESSURE STEAM HPC HIGH PRESSURE CONDENSATE PC PUMPED CONDENSATE RD REFRIGERANT DISCHARGE RL REFRIGERANT LIQUID RS REFRIGERANT SUCTION VAC VACUUM CW DOMESTIC COLD WATER EXISTING WORK TO BE REMOVED SINGLE LINE PIPE OR DUCT CONTINUED ROUND DUCT CONTINUED DOUBLE LINE PIPE OR MBH THOUSAND BTU/HOUR (E)EXISTING FPM FEET PER MINUTE AFF ABOVE FINISHED FLOOR G.C.GENERAL CONTRACTOR E.C.ELECTRICAL CONTRACTOR N.C.NORMALLY CLOSED S TEMPERATURE SENSOR DUCT TAKEOFFSSINGLE LINE DOUBLE LINE UP OR DOWN SUPPLY DUCT TURNING 24x12 10x8 DN UPUPDN 10x88x6 24x1214x8 TAP 6" BOOT RECTANGULAR BRANCH RECTANGULAR MAIN SUPPLY/RETURN 10"14" 8"18"ROUND BRANCH ROUND MAIN SUPPLY/RETURN LATERAL SUPPLY DIFFUSER, REGISTER OR GRILLE FLEXIBLE DUCTWORK COMPRESSED AIRA CAP OR PLUG ELBOW DOWN ELBOW UP AAD AUTOMATIC AIR DAMPER FD FIRE DAMPER SD SMOKE DAMPER BDD BACK DRAFT DAMPER M MOTORIZED DAMPER BALL VALVE GATE VALVE CHECK VALVE BALANCING VALVE BUTTERFLY VALVE SAFETY RELIEF VALVE PRESSURE REDUCING VALVEPRV PRESSURE/TEMPERATURE TEST PLUG HVAC SYMBOL LIST (L)ACOUSTIC THERMAL LINING - 1•" THICK (2L)ACOUSTIC THERMAL LINING - 2" THICK M.C.MECHANICAL CONTRACTOR W/W WALL TO WALL T G S THERMOSTAT/SENSOR WITH GUARDG DUCT SECTION - SUPPLY DUCT SECTION - RETURN WIDTH A x DEPTH B A B R R DIRECTION OF AIRFLOW RISE IN DUCT - IN D D DIRECTION OF AIRFLOW DROP IN DUCT - IN 10x824x1214" TAP 6" BOOT ROUND BRANCH RECTANGULAR MAIN SUPPLY/RETURN8" BG BLAST GATE FIN TUBE RADIATION VALANCE A B C C = CFM B = NECK SIZE A = TYPE REGISTER, GRILLE OR DIFFUSER TAG A B C D D = HEATING GPM C = COOLING GPM B = COIL SIZE A = TYPE VALANCE TAG POINT OF CONNECTION POINT OF DISCONNECTION BOTTOM TAP TRIPLE DUTY VALVETD GLOBE VALVE SUCTION DIFFUSERSD CAP AND CHAIN DRAIN VALVE WITH HOSE CONNECTION, FC FLEX CONNECTOR - DUCTWORK DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL FLEXIBLE CONNECTOR - PIPING A B C C = MINIMUM CFM B = MAXIMUM CFM A = UNIT NO. AIR TERMINAL UNIT TAG (OPTION 2) FO AxB DUCT SECTION - FLAT OVAL (FO) V VENT WATER FLOW SENSOR VSD BASE MOUNTED PUMP IN LINE PUMP WELL PNEUMATIC ACTUATOR AVERAGING SENSOR VARIABLE SPEED DRIVE COOLING COIL C C PROBE SENSOR E ELECTRIC ACTUATOR AIR FLOW SENSOR FS A S F R P DO DI AI AO DIGITAL INPUT (GENERAL) DIGITAL OUTPUT (GENERAL) ANALOG INPUT (GENERAL) ANALOG OUTPUT (GENERAL) ALARM STATUS FLOW SWITCH RELAY PRESSURE SWITCH DIFFERENTIAL STATIC FZ EXHAUST AIR OUTSIDE AIR RETURN AIR FREEZE-STAT EA OA RA SA (OPPOSED BLADE) AUTOMATIC AIR DAMPER HUMIDIFIER DISPERSIAN TUBE REGISTER OR GRILLE THREE WAY THROW SUPPLY DIFFUSER, REGISTER OR GRILLE TWO WAY THROW SUPPLY DIFFUSER, REGISTER OR GRILLE ONE WAY THROW SUPPLY DIFFUSER, E P PE CT C O S S DE H F P P I E I CURRENT TRANSDUCER START/STOP ENABLE/DISABLE ELECTRICAL INTERFACE H C HEATING COIL FILTER S TRANSDUCER ELECTRIC/PNEUMATIC TRANSDUCER ELECTRONIC/ELECTRIC OR RELAY ELECTRIC/PNEUMATIC SWITCH OR RELAY PNEUMATIC/ELECTRIC SWITCH PRESSURE TRANSMITTER (DUCT MOUNTED) HUMIDITY SENSOR FLOW TRANSMITTER G B GAS BURNER PRESSURE TRANSMITTER DIFFERENTIAL STATICP OPEN/CLOSE OR PIPE MOUNTED) TEMPERATURE SENSOR (DUCT (PARALLEL BLADE) AUTOMATIC AIR DAMPER M I ELECTRONIC INTERFACE H HUMIDIFIER ES END SWITCH SYMBOL DESCRIPTION SYMBOL DESCRIPTION FD/SD COMBINATION FIRE AND SMOKE DAMPER DOUBLE WALL LINED DUCT- 3" THICK MTHWS MEDIUM TEMPERATURE HOT WATER SUPPLY (COGEN) MTHWR MEDIUM TEMPERATURE HOT WATER RETURN (COGEN) CO2 CARBON DIOXIDE TRANSMITTER M FLOW METER OS OCCUPANCY SENSOR M MOISTURE SENSOR SW SOFTEN WATER HRWS HRWR TCS FAN COIL UNIT COOLING SUPPLY TCR FAN COIL UNIT COOLING RETURN THS FAN COIL UNIT HEATING SUPPLY THR FAN COIL UNIT HEATING RETURN SF RF EF SUPPLY AIR FAN RETURN AIR FAN EXHAUST AIR FAN CO CARBON MONOXIDE TRANSMITTER E E ELECTRONIC CONTROL VALVE (3-WAY) ELECTRONIC CONTROL VALVE (2-WAY) B C D D = GPM C = ENCLOSURE LENGTH B = FIN TUBE LENGTH FT-A = TYPE RADIANT CEILING PANEL TAG FIN TUBE RADIATION/ FT-A RADIANT CEILING PANEL PS TS TEMPERATURE SENSOR PRESSURE SENSOR A AIR TERMINAL UNIT AND TAG (OPTION 1) AIR TERMINAL UNIT X"LAB AIR VALVE FACTORY ATTENUATOR AIR TERMINAL UNIT WITH X" FACTORY SOUND ATTENUATOR LAB AIR VALVE WITH SERVICE CLEARANCE P PRESSURE SWITCH CO CARBON MONOXIDE DETECTOR CONDENSING UNIT WATER SUPPLYCS CR CONDENSING UNIT WATER RETURN FILTER BANK S TEMPERATURE SENSOR WITH SETPOINT ADJUSTMENT SA S TEMPERATURE SENSOR WITH OCCUPANCY OVERRIDE OV S D S F TEMPERATURE SENSOR WITH VISUAL DISPLAY TEMPERATURE SENSOR WITH FAN ON/OFF SWITCH AV ANALOG VALUE MOD MODULATING BACS THERMOWELL MOTOR BINARY POINT ANALOG POINT BI BINARY INPUT BO BINARY OUTPUT AV ANALOG VALUE BV BINARY VALUE VARIABLE FREQUENCY DRIVEVFD F.L.FAIL LAST T ROOM TEMPERATURE SENSOR WITH SETPOINT ADJUSTMENT sa ROOM TEMPERATURE SENSOR WITH OCCUPANCY OVERRIDE Tov Td ROOM TEMPERATURE SENSOR WITH VISUAL DISPLAY Tf ROOM TEMPERATURE SENSOR WITH FAN ON/OFF SWITCH SINGLE POINT SENSOR CURRENT SENSORCS SD RD ROTATION DETECTOR SMOKE DETECTOR THREE WAY CONTROL VALVE, PNEUMATIC CONTROL VALVE, PNEUMATIC MODULATINGMOD SC SPEED COMMAND COM NETWORK COMMUNICATION INTERFACE POINT, BACnet MSTP MS MOTOR STARTER AOM ADDRESSABLE OUTPUT MODULE (FIRE ALARM INTERFACE) T LIQUID IMMERSION TEMPERATURE SENSOR T TEMPERATURE SENSOR RH RELATIVE HUMIDITY SENSOR DP DEW POINT SENSOR C CONDENSATE SENSOR BUTTERFLY CONTROL DAMPER HI HI LEVEL SWITCH LOW LOW LEVEL SWITCH P PRESSURE SWITCH SP STATIC PRESSURE SENSOR FZ LOW LIMIT TEMPERATURE SWITCH 2-WAY CONTROL VALVE, DIGITAL 3-WAY CONTROL VALVE, DIGITAL VENTURI AIRFLOW CONTROL VALVE SUPPLY AIR A SIGNAL IN OUT SIGNAL AIR IN SIGNAL ELECTRIC TO PNEUMATIC SWITCH E P A IN SIGNAL OUT SIGNAL AIR IN HOSE ELECTRIC TO PNEUMATIC TRANSDUCER TRANSFORMER HEAT RECOVERY WATER SUPPLY HEAT RECOVERY WATER RETURN GENERAL NOTES: MATERIAL AND FINISH ALL EXISTING DUCTWORK OR PIPE PENETRATIONS THROUGH FLOORS AND WALLS AFTER DEMOLITION. UNLESS SHOWN ON THE ARCHITECTURAL DRAWINGS, IT IS THE RESPONSIBILITY OF THIS CONTRACT TO PATCH WITH LIKE THE MOUNTING HEIGHT FOR ALL ROOM THERMOSTATS OR SENSORS SHALL BE 48 IN. TO TOP OF THE COVER. CONTRACT. NO EQUIPMENT, PIPING OR DUCTWORK SHALL BE ABANDONED IN PLACE UNLESS OTHERWISE NOTED ON THE DRAWINGS. CONTROL PNEUMATIC TUBING AND ACCESSORIES TO BE DISCONNECTED AND REMOVED BUT IS THE REQUIREMENTS UNDER THIS MISCELLANEOUS PIPING, PIPING ACCESSORIES, SUPPORTS, CONTROLS, CONTROL ACCESSORIES, CONTROL WIRING, CONDUIT, AND THE DEMOLITION DRAWINGS SHOW IN GENERAL MAJOR EQUIPMENT AND PIPING REMOVALS. THE INTENT IS NOT TO IDENTIFY ALL MATERIALS AT NO ADDITIONAL COST TO THE OWNER. CONTRACTORS WORK IS THE RESPONSIBILITY OF THE CONTRACTOR TO REPAIR AND/OR REPLACE WITH SIMILAR OR LIKE DAMAGE TO EXISTING SYSTEMS (EQUIPMENT, PIPING, CONTROLS AND ACCESSORIES) SHOWN TO REMAIN AS A RESULT OF THE COSTS DUE TO CONTRACTORS FAILURE TO VERIFY EXISTING CONDITIONS AND DIMENSIONS. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BID. NO ALLOWANCE WILL BE MADE FOR ADDITIONAL EXISTING CONDITIONS ARE TAKEN FROM FIELD OBSERVATIONS AND PRIOR CONSTRUCTION DOCUMENTS AND ARE NOT GUARANTEED. SENSORS SHALL BE INSTALLED IN ALIGNMENT WITH ELECTRICAL, FIRE, AND OTHER DEVICES WHEN LOCATED ON COMMON WALLS. WALK THROUGH WITH THE ARCHITECT/ENGINEER TO LOCATE SENSOR LOCATIONS PRIOR TO INSTALLATION. THE TEMPERATURE AND SPACE MOUNTED CARBON DIOXIDE DETECTORS WITH THE ARCHITECT/ENGINEER. THE CONTRACTOR SHALL SCHEDULE A IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE THE LOCATIONS OF ALL ROOM TEMPERATURE SENSORS PERSONNEL IN SHUTTING DOWN, DRAINING, VENTING, ECT. OF SYSTEM TO FACILITATE THE INTENDED WORK. ALL SHUT DOWNS WILL OCCUR DURING NIGHTS OR WEEKENDS. THE CONTRACTOR SHALL ASSIST THE UNIVERSITY WATER, HOT WATER, STEAM, ETC. SYSTEMS WITH CORNELL UNIVERSITY FACILITY PERSONNEL FOR TIE-IN CONNECTIONS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE ALL SHUTDOWNS OF AIR HANDLING, CHILLED OF THE SYSTEM COMPLETELY. THE SYSTEMS. DRAINS SHALL BE PROVIDED AT ALL LOW POINTS WITHIN THE PIPING SYSTEMS TO FACILITATE DRAINING AT AREAS WITHIN THE PIPING SYSTEMS THAT COULD ACCUMULATE OR TRAP AIR PREVENTING PROPER OPERATION OF SYSTEMS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE AIR VENTS AT ALL SYSTEM HIGH POINTS AND IT IS NOT THE INTENT OF THE DRAWINGS TO SHOW ALL AIR VENTS OR DRAINS FOR THE INSTALLATION OF THE PIPING SEALANT ON BOTH SIDES OF WALL PENETRATION TO REDUCE NOISE TRANSMISSION. SHALL BE FIRE/SMOKE STOPPED. ALL PENETRATIONS THROUGH NON RATED WALLS SHALL BE SEALED WITH A NON-HARDENING SYSTEMS INCLUDING, BUT NOT LIMITED TO, EQUIPMENT, PIPING, ETC.. ALL PENETRATIONS THROUGH RATED WALLS AND FLOORS ALL NEW PENETRATIONS THROUGH WALLS, FLOORS AND ROOFS SHALL BE PROVIDED FOR INSTALLATION OF MECHANICAL PROPER LEGAL MANNER. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO DISPOSE OF ALL DEMOLITION DEBRIS AND MATERIALS OFF SITE IN A J. I. H. G. F. E. D. C. B. A.3/12/2015 2:03:59 PMJAD REVISIONS no.date by description ALL RIGHTS RESERVED © ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS 387 East Main Street Rochester, NY 14604-2107 Voice: 585.232.8300 Fax: 585.232.9221 w w w . s w b r . c o m DRAWING TITLE proj. no. checked proj. mgr. drawn by STATUS: DRAWING NO. PROJECT: CLIENT: ISSUE DATE: ROCHESTER, N E W Y O R K CONSULTANT: ENGINEERING P.C. MECHANICAL/ELECTRICAL ENGINEERING CONSULTANTS ROCHESTER, NEW YORK 14604 (585) 288-5590 FAX: (585) 288-0233 M/E Project: 150166 150 NORTH CHESTNUT STREET ROCHESTER BUFFALO SYRACUSE CAPITAL DISTRICT ROOM RENOVATIONS UPGRADES & MINOR OF '49 CLASSROOM A/V HOLLISTER HALL CLASS ENGINEERING COLLEGE OF CORNELL UNIVERSITY - 15365.00 10/22/2015 DOCUMENTS 100% CONSTRUCTION NJS RFG H-100 NORTH SCALE: 1/4"=1'-0"0 2'4'8' PARTIAL 3RD FLOOR PLAN - HVAC DEMOLITION T 1" HWS DOWN (E)ƒ"HWS UP; 1" HWR DOWN (E)1‚"HWR UP; 1" HWR DOWN (E)1‚"HWR UP; 1" HWS DOWN (E)ƒ"HWS UP; ƒ" HWR DOWN (E)1"HWR UP; (E)FT 1" HWS DOWN (E)ƒ"HWS UP; DEMOLITION NOTES: 1 (E)FT 1 (E)FT 1 (E)FT 2 RETURN AIR DUCT (E)17x14 ABANDONED SUPPLY AIR DUCT (E)17x14 ABANDONED 3 3 1 DEMOLITION PLAN - HVAC PARTIAL 3RD FLOOR DISCONNECTION. AND CEILING PENETRATION. PROVIDE SHEETMETAL CAP AT EACH POINT OF DISCONNECT AND REMOVE ABANDONED SUPPLY AND RETURN AIR RISER AT FLOOR ACCESSORIES. DISCONNECT AND REMOVE TEMPERATURE SENSOR, CONTROLS AND CONTROLS REFER TO FIN RADIATION PIPING DEMOLITION DETAILS FOR FURTHER REQUIREMENTS. ELEMENT AND ALL ASSOCIATED TUBING BETWEEN NEWLY INSTALLED SHUTOFF VALVES. BRACKETS AND ACCESSORIES COMPLETE. DISCONNECT AND REMOVE FIN RADIATION DISCONNECT AND REMOVE FIN RADIATION ENCLOSURE, ALL ASSOCIATED MOUNTING 3 2 13/12/2015 2:03:59 PMJAD REVISIONS no.date by description ALL RIGHTS RESERVED © ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS 387 East Main Street Rochester, NY 14604-2107 Voice: 585.232.8300 Fax: 585.232.9221 w w w . s w b r . c o m DRAWING TITLE proj. no. checked proj. mgr. drawn by STATUS: DRAWING NO. PROJECT: CLIENT: ISSUE DATE: ROCHESTER, N E W Y O R K CONSULTANT: ENGINEERING P.C. MECHANICAL/ELECTRICAL ENGINEERING CONSULTANTS ROCHESTER, NEW YORK 14604 (585) 288-5590 FAX: (585) 288-0233 M/E Project: 150166 150 NORTH CHESTNUT STREET ROCHESTER BUFFALO SYRACUSE CAPITAL DISTRICT ROOM RENOVATIONS UPGRADES & MINOR OF '49 CLASSROOM A/V HOLLISTER HALL CLASS ENGINEERING COLLEGE OF CORNELL UNIVERSITY - 15365.00 10/22/2015 DOCUMENTS 100% CONSTRUCTION 362 366 368 NJS RFG H-200 NORTH SCALE: 1/4"=1'-0"0 2'4'8' PARTIAL 3RD FLOOR PLAN - HVAC PLAN - HVAC PARTIAL 3RD FLOOR DRAWING NOTES: 1 EF-1 10x8S1 2 12x10 300 2 FD FC (E)FT 3 8'-0" W/W 1.0 FT-A S3 8'-0" W/W 1.0 FT-A 3 8'-0" W/W 1.0 FT-A ƒ" HWR DN (E)1"HWR UP 1" HWS DN (E)ƒ"HWS UP 1" HWR DN (E)1‚"HWR UP 1" HWS DN (E)ƒ"HWS UP 1" HWR DN (E)1‚"HWR UP 1" HWS DN (E)ƒ"HWS UP 3 2 1 DETAIL FOR FURTHER REQUIREMENTS. ABOVE NEW SEATING RISER. PIPE PER DETAIL. REFER TO FIN RADIATION PIPING AND ALL OTHER ASSOCIATED ACCESSORIES. MOUNT TOP OF ENCLOSURE 2'-0" PROVIDE NEW FIN TUBE RADIATION, TUBING, ENCLOSURE, MOUNTING BRACKETS AS POSSIBLE ABOVE DOOR. CONNECT 10x8 EXHAUST DUCT TO 12x10 PLENUM. PROVIDE A 12x10 PLENUM CONNECTED TO THE 12x10 GRILLE, MOUNTED AS HIGH DUCTWORK, DUCTWORK ACCESSORIES, CONTROLS AND CONTROLS ACCESSORIES. PROVIDE SCHEDULED EXHAUST FAN EF-1 MOUNTED IN ELECTRICAL 361, ASSOCIATED3/12/2015 2:03:59 PMJAD REVISIONS no.date by description ALL RIGHTS RESERVED © ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS 387 East Main Street Rochester, NY 14604-2107 Voice: 585.232.8300 Fax: 585.232.9221 w w w . s w b r . c o m DRAWING TITLE proj. no. checked proj. mgr. drawn by STATUS: DRAWING NO. PROJECT: CLIENT: ISSUE DATE: ROCHESTER, N E W Y O R K CONSULTANT: ENGINEERING P.C. MECHANICAL/ELECTRICAL ENGINEERING CONSULTANTS ROCHESTER, NEW YORK 14604 (585) 288-5590 FAX: (585) 288-0233 M/E Project: 150166 150 NORTH CHESTNUT STREET ROCHESTER BUFFALO SYRACUSE CAPITAL DISTRICT ROOM RENOVATIONS UPGRADES & MINOR OF '49 CLASSROOM A/V HOLLISTER HALL CLASS ENGINEERING COLLEGE OF CORNELL UNIVERSITY - 15365.00 10/22/2015 DOCUMENTS 100% CONSTRUCTION 359 362 368 369365363 CLASSROOM 366 ELECTRICAL 361 300CA NJS RFG H-300 SCHEMATICS CONTROL SCALE: NONE EFEA S S CT EF-05 EXHAUST FAN EA ELECTRICAL 361 EXHAUST CONTROL AND SYSTEM SUMMARY sa d AI T SETPOINT AV BO BI 1 SCALE: NONE 2 AO F.L. ov SCHEDULEPOINT NAME POINT STARTER MOTOR WITHFAN POINTSHARDWARE POINTSSOFTWARE GRAPHIC ONSHOWN NOTES BI BO AI AO AV BV SCH TREND ALARM BACS EMCS DESCRIPTION START/STOP MOTORFAN X X X STATUS MOTORFAN X X X FAILURE X SENSOR CURRENTVIA SETPOINT TEMPERATURESPACE X X X TEMPERATURESPACE X X X SETPOINT FROM F DEG 4+/-X DESCRIPTIONSYSTEM SYSTEM FAN EXHAUST 361ELECTRICAL GENERAL (BACS). SYSTEMCONTROL AND AUTOMATION BUILDING THE THROUGH CONTROLLED BE SHALLSYSTEM ADJUSTABLE. BE SHALL SETPOINTSALL SETPOINTS F O 80OCCUPIED: F O 80UNOCCUPIED: CONTROL FANEXHAUST WORKSTATION. OPERATOR'S AT INDICATED BESHALL MESSAGE FAILURE MOTOR FAN A SWITCH, CURRENT BY SENSED ASCOMMAND TO EQUAL NOT IS STATUS FAN IF SPACE. THE WITHIN LOCATEDSENSOR TEMPERATURE SPACE A BY SENSED AS (ADJ)F O 0 8 OF SETPOINTEXCEEDING TEMPERATURE SPACE ON BASED ENERGIZED BE SHALL FAN EXHAUSTTHE CONTROLOCCUPIED/UNOCCUPIED SETPOINT. EXCEEDSTEMPERATURE SPACE UNLESS OFF BE SHALL FAN EXHAUST THE EXCEEDED, IS DURATIONTIME WHEN (ADJ). MINUTES (15) FIFTEEN FOR OPERATE SHALL AND STARTSHALL FAN EXHAUST THE ACTIVATED IS MODE OCCUPIED THE IF FEATURE.OVERRIDE OCCUPIED/UNOCCUPIED AN WITH PROVIDED BE SHALL SENSOR SPACETHE sa d AI T SETPOINT AV BI OS DESCRIPTIONSYSTEM RADIATION TUBEFIN GENERAL (BACS). SYSTEMCONTROL AND AUTOMATION BUILDING THE THROUGH CONTROLLED BE SHALLSYSTEM ADJUSTABLE. BE SHALL SETPOINTSALL WEEK. PER SCHEDULES DAILY DIFFERENTSEVEN FOR SYSTEM THE STOPPING AND STARTING OF CAPABLE BE SHALL BACSTHE SETPOINTS SETPOINTS: TEMPERATURE HEATINGSPACE F O 68OCCUPIED: UNOCCUPIED:64 O F MON-FRI PM, 8 TO AM 6 SCHEDULE: OCCUPANCYZONE OCCUPANCYSPACE SCHEDULE. DAY OF TIME A ON BASED DETERMINED BE SHALL OCCUPANCYZONE MINUTES. 30 OFPERIOD A FOR SENSED NOT IS OCCUPANCY WHEN UNOCCUPIED TO BACKINDEX SHALL ZONE THE OCCUPANCY. OF DURATION THE FOR OCCUPIED TOINDEXED BE SHALL ZONE THE SENSOR, OCCUPANCY THE VIA DETERMINED ASPERIOD, UNOCCUPIED SCHEDULED THE DURING OCCUPIED BECOMES SPACE THEIF CONTROL TEMPERATUREZONE SCHEDULE. PROGRAMMED A ON BASED DETERMINED BE SHALL SETPOINTSTEMPERATURE SETPOINT. TEMPERATUREHEATING OCCUPIED AN MAINTAIN TO MODULATE SHALL VALVE CONTROL HEATINGZONE RADIANT THE SETPOINT, TEMPERATURE HEATING OCCUPIED THE BELOWFALLS TEMPERATURE ZONE THE AND OCCUPIED IS SPACE THE IF HEATING:OCCUPIED SYSTEM. THIS FOR IMPLIMENTED BE NOT SHALL SETBACK:OCCUPIED SETPOINT. TEMPERATURE HEATING UNOCCUPIED THEMAINTAIN TO MODULATE SHALL VALVE CONTROL HEATING ZONE RADIANT THESETPOINT, TEMPERATURE HEATING UNOCCUPIED THE BELOW FALLSTEMPERATURE ZONE THE AND UNOCCUPIED IS SPACE THE IF HEATING:UNOCCUPIED CLASSROOM 366 FIN RADIATION CONTROL AND SYSTEM SUMMARY SCHEDULEPOINT NAMEPOINT RADIATION BASEBOARD W/ UNIT COIL FAN ONLYCOOLING POINTSHARDWARE POINTSSOFTWARE GRAPHIC ONSHOWN NOTES BI BO AI AO AV BV SCH TREND ALARM BACS EMCS DESCRIPTION COMMAND POSITION VALVE CONTROL TUBEFIN X X X 3) OF (TYP. LASTFAIL OCCUPANCYSPACE X X X PLANS FLOOR TOREFER SETPOINT TEMPERATURESPACE X X X TEMPERATURESPACE X X X SETPOINT FROM F DEG 4+/-X SCALE: NONE 3 STEAM LOAD SHED MATRIX STEAM LOAD SHED MATRIX CONTROL POINT LOAD SHED 1 LOAD SHED 2 LOAD SHED 3 LOAD SHED 4 LOAD SHED 5 LOAD SHED 6 STEAM STEAM STEAM STEAM STEAM STEAM ZONE CONTROL NON-RESEARCH SPACES INDEX SPACE TO UNOCCUPIED MODE INDEX TEMPERATURE SET POINT TO 60 DEG F3/12/2015 2:03:59 PMJAD REVISIONS no.date by description ALL RIGHTS RESERVED © ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS 387 East Main Street Rochester, NY 14604-2107 Voice: 585.232.8300 Fax: 585.232.9221 w w w . s w b r . c o m DRAWING TITLE proj. no. checked proj. mgr. drawn by STATUS: DRAWING NO. PROJECT: CLIENT: ISSUE DATE: ROCHESTER, N E W Y O R K CONSULTANT: ENGINEERING P.C. MECHANICAL/ELECTRICAL ENGINEERING CONSULTANTS ROCHESTER, NEW YORK 14604 (585) 288-5590 FAX: (585) 288-0233 M/E Project: 150166 150 NORTH CHESTNUT STREET ROCHESTER BUFFALO SYRACUSE CAPITAL DISTRICT ROOM RENOVATIONS UPGRADES & MINOR OF '49 CLASSROOM A/V HOLLISTER HALL CLASS ENGINEERING COLLEGE OF CORNELL UNIVERSITY - 15365.00 10/22/2015 DOCUMENTS 100% CONSTRUCTION NJS RFG SCALE: NONE HOT WATER RISER HWR EXISTING RISER HWS EXISTING SCALE: NONE HOT WATER RISER HWR EXISTING RISER HWS EXISTING ROOMS 362 & 366 WALL BETWEEN ENCLOSURE NEW CAP & CHAIN. CONNECTION, W/HOSE END ƒ" DRAIN VALVE VALVE CONTROL NEW VALVE BALANCE NEW1 2 2 21 5 3 4 3 4 5 1 21 2 2 CAP & CHAIN. CONNECTION, W/HOSE END ƒ" DRAIN VALVE 2 43 FIN RADIATION PIPING DETAIL FIN RADIATION PIPING DETAIL SCALE: NONE HOT WATER VALVE CONTROL EXISTING ENCLOSURE EXISTING RISER HWR EXISTING RISER HWS EXISTING 6 6 2 2 3 VALVE CONTROL EXISTING 4 1 2 SCALE: NONE HOT WATER RISER HWR EXISTING RISER HWS EXISTING 6 6 22 3 4 1 2 ROOMS 362 & 366 WALL BETWEEN VALVE BALANCE ROOM 366 EXISTING 5 VALVE BALANCE ROOM 362 EXISTING VALVE CONTROL ROOM 366 EXISTING 5 VALVE CONTROL ROOM 362 EXISTING ENCLOSURE ROOM 366 EXISTING 5 ENCLOSURE ROOM 362 EXISTING2 5 1 2 DETAIL DEMOLITION NOTES: FIN RADIATION PIPING DEMOLITION DETAIL FIN RADIATION PIPING DEMOLITION DETAIL DETAIL NOTES: FOR MINIMAL SHUTDOWN TIME. OF FIN TUBE RADIATION AND ASSOCIATED VALVING AND ACCESSORIES PROVIDE AND INSTALL NEW SHUT OFF VALVES PRIOR TO DEMOLITION TO GPM LISTED. PIPE PER DETAIL. PROVIDE NEW BALANCE VALVE IN FIN TUBE RADIATION ENCLOSURE. BALANCE ENCLOSURE. PIPE PER DETAIL. PROVIDE AND INSTALL NEW CONTROL VALVE IN NEW FIN TUBE RADIATION DDC CONTROL SYSTEM. IN FIN TUBE RADIATION ENCLOSURE. CONNECT SENSOR TO EXISTING CONTROL WIRING AND CONNECT TO NEW CONTROL VALVE LOCATED PROVIDE AND INSTALL NEW TEMPERATURE SENSOR. PROVIDE ALL NEW NECESSARY PIPING MODIFICATIONS REQUIRED TO MAKE TIE-IN. CONNECT NEW TUBING TO EXISTING AT INDICATED POINT. MAKE ALL OF ENCLOSURE 2'-0" ABOVE NEW SEATING RISER. PIPE PER DETAIL. BRACKETS AND ALL OTHER ASSOCIATED ACCESSORIES. MOUNT TOP PROVIDE NEW FIN TUBE RADIATION, TUBING, ENCLOSURE, MOUNTING 6 5 4 3 2 1 EXISTING TO REMAIN. DISCONNECT AND REMOVE BALANCE VALVE. DISCONNECT AND REMOVE CONTROL VALVE. BETWEEN NEWLY INSTALLED SHUTOFF VALVES. DISCONNECT AND REMOVE FIN RADIATION ELEMENT AND ALL ASSOCIATED TUBING BRACKETS AND ACCESSORIES COMPLETE. DISCONNECT AND REMOVE FIN RADIATION ENCLOSURE, ALL ASSOCIATED MOUNTING 5 4 3 2 1 5 5 5 5 H-400 ROOM 366 ROOM 366 & 362 ROOM 366 ROOM 366 & 362 ROOM 366 NEW ENCLOSURE VALVE ROOM 366 NEW BALANCE VALVE ROOM 366 NEW CONTROL ROOM 362 VALVE CONTROL EXISTING ROOM 362 ENCLOSURE EXISTING ROOM 362 VALVE BALANCE EXISTING SCALE: NONE SLIP JOINT FIRE DAMPER CONSTRUCTION FIRE RATED 'S TO WALL DO NOT BOLT RECTANGULAR DUCT ROUND/FLAT OVAL OR TYPE PER SPECIFICATIONS ACCESS DOOR: SIZE AND FIRE DAMPER INSTALLATION DETAIL INSTALLATION DETAIL STANDARD AND UL LISTING AS PER CURRENT SMACNA OVERSIZED WALL OPENING ANGLE FASTENING, AND ANGLE SIZE AND GAUGE, SLEEVE MATERIAL GAUGE, C. B. A. DETAIL NOTES: AND UL LISTING INSTALLATION DETAIL. OPENING PROTOCOL DETAIL FIG. 3-1 (FIRE DAMPER GUIDE) AS WELL AS MANUFACTURER THE EXISTING WALL PENETRATION AND FRAMING AS PER SMACNA FIRE DAMPER EXISTING WALLS, THIS CONTRACTOR IS REQUIRED TO REFRAME AND RECONSTRUCT FOR FIRE DAMPERS TO BE PROVIDED IN EXISTING OR NEW DUCTS PENETRATING FOR DOUBLE WALL DUCT, USE INSULATION END CAP AND INSULATE SLEEVE. HORIZONTAL AND 80% FREE AREA DAMPER INSTALLATION SIMILAR. 5 SCHEDULEFAN NO.UNIT LOCATION SERVICE CHARACTERISTICSFAN CHARACTERISTICSMOTOR No. MODEL &MANUFACTURER TYPE CFM WC)(In. S.P. RPM FAN (FPM) VELOCITY OUTLETMAX. SONES DRIVE HP VOLTS PHASE STARTER EF-1 361ELECTRICAL 361ELECTRICAL CEILING 300 0.5 1205 911 3.5 -135W 115 1 MANUAL GC-520 MODELCOOK SCALE: NONE 6 SCHEDULES WATER HOT - SCHEDULERADIATION TYPEUNIT )(BTUH/LF CAPACITY F)(DEG. TEMP WATER AVERAGE F)(DEG. TEMP. AIRENT. F) (DEG.TEMP. WATERENT. F) (DEG.TEMP. WATERLVG. FLUID ELEMENTHEATING ENCLOSURE No. MODEL &MANUFACTURER REMARKS (In.) SIZE TUBE (In.) SIZE FIN TIERS FT. FINS/ HEIGHT WIDTH TOP TOHEIGHT MOUNTING FT-A 1085 170 65 180 160 WATERHOT 3/4"4"x4"1 52 18"5.25"23" RVT-44-C1-H MODELROSEMEX SCHEDULE DIFFUSER AND GRILLEREGISTER TYPE APPLICATION MATERIAL FINISH No. MODEL &MANUFACTURER REMARKS 1 SUPPLY STEEL WHITE OMNI MODELTITUS 2 SUPPLY STEEL WHITE 272RL MODELTITUS A RETURN STEEL WHITE 350RL MODELTITUS HVAC DETAILS & SCHEDULES - 3/12/2015 2:03:59 PMJAD REVISIONS no.date by description ALL RIGHTS RESERVED © ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS 387 East Main Street Rochester, NY 14604-2107 Voice: 585.232.8300 Fax: 585.232.9221 w w w . s w b r . c o m DRAWING TITLE proj. no. checked proj. mgr. drawn by STATUS: DRAWING NO. PROJECT: CLIENT: ISSUE DATE: ROCHESTER, N E W Y O R K CONSULTANT: ENGINEERING P.C. MECHANICAL/ELECTRICAL ENGINEERING CONSULTANTS ROCHESTER, NEW YORK 14604 (585) 288-5590 FAX: (585) 288-0233 M/E Project: 150166 150 NORTH CHESTNUT STREET ROCHESTER BUFFALO SYRACUSE CAPITAL DISTRICT ROOM RENOVATIONS UPGRADES & MINOR OF '49 CLASSROOM A/V HOLLISTER HALL CLASS ENGINEERING COLLEGE OF CORNELL UNIVERSITY - 15365.00 10/22/2015 DOCUMENTS 100% CONSTRUCTION CTV MRG E-000 LIST & GENERAL NOTES ELECTRICAL SYMBOLS ,DASHED LIGHT IS EXISTING TO BE REMOVED. EXISTING ELECTRICAL OR EQUIPMENT OR DEVICE, ,RELOCATED. EXISTING TO REMAIN OR EXISTING TO BE EXISTING WIRING OR EQUIPMENT, SOLID LIGHT IS HEAVY SOLID IS NEW, SYMBOL DESCRIPTION GENERAL CONSTRUCTION SYMBOLS EXISTING DEVICE TO REMAIN(E) EXISTING DEVICE TO BE RELOCATED (ER) SYMBOL DESCRIPTION FIRE ALARM RATE OF RISE HEAT DETECTOR H VISUAL SIGNAL DEVICEF SPEAKER/STROBE ALARM SIGNALF SYMBOL DESCRIPTION LUMINAIRES SWITCHING DESIGNATION. SCHEDULE, LOWER CASE LETTER INDICATES LETTERS INDICATE FIXTURE TYPE ON CEILING MOUNTED LUMINAIRE. UPPER CASE SWITCHING DESIGNATION. SCHEDULE, LOWER CASE LETTER INDICATES LETTERS INDICATE FIXTURE TYPE ON WALL MOUNTED LUMINAIRE. UPPER CASE CEILING MOUNTED EXIT LUMINAIRE WALL MOUNTED EXIT LUMINAIRE FA d FA d SYMBOL DESCRIPTION BASIC MATERIALS AND METHODS ELECTRICAL SYMBOLS LIST J JUNCTION BOX COMPLETE CONNECTION TO EQUIPMENT LP-404 FOR RACEWAY TYPE. TO MATCH HOMERUN. REFER TO SPEC'S BRANCH CIRCUIT WIRING SIZE AND NUMBER EG., IN ƒ" C, UNLESS NOTED OTHERWISE. SHALL BE 20 AMP, 120 VOLT, 2-#12, 1-#12 EQUALS NUMBER OF CIRCUITS. CIRCUIT INDICATE CIRCUITS. NUMBER OF ARROWS NUMBERS INDICATE PANEL. NUMBERS HOME RUN TO PANELBOARD. LETTERS/ X - MATCH EQUIPMENT CAP T - TWISTLOCK SUBSCRIPT INDICATES TYPE: PROVIDE CORD AND CAP. EQUIPMENT BEING FURNISHED BY OTHERS. BRANCH CIRCUIT AND/OR MATCH CAP ON AND NEMA CONFIGURATION AS REQUIRED BY PROPER VOLTAGE, CLASS, CURRENT RATING SPECIAL PURPOSE RECEPTACLE. PROVIDE SWITCHES LETTERS EQUALS NO. OF GANGED a,b,c - SWITCHING DESIGNATIONS NUMBER OF OS - OCCUPANCY SENSOR 3 - THREE WAY SWITCH INDICATE TYPE: ON FIXTURE SCHEDULE, SUBSCRIPTS TOGGLE SWITCH, VOLTAGE AS INDICATED 3 a,b,c OS UNLESS NOTED OTHERWISE. CIRCUIT TO SINGLE POLE CIRCUIT BREAKER(S), SOLID HALF ARROW(S) INDICATES 120 VOLT UNLESS NOTED OTHERWISE. CIRCUIT TO MULTI-POLE CIRCUIT BREAKER, SOLID FULL ARROW INDICATES 208 VOLT SYMBOL DESCRIPTION AND CONTROL POWER DISTRIBUTION EQUIPMENT AND CONTROL SCHEDULE FOR SIZE. MOTOR CONNECTION. REFER TO ELECTRIC M 208/120 VOLT PANELBOARD U - ULTRASONIC SUBSCRIPTS INDICATE TYPE: (DUAL TECHNOLOGY WITH 360° VIEW) CEILING MOUNTED OCCUPANCY SENSOR W WITH BATTERY PACK WALL MOUNTED EMERGENCY LUMINAIRE EXISTING TEL/DATA DROP MOUNTING HEIGHT & MISC. INFO. 1 DESIGNATION PANEL TYPICAL FOR ALL DEVICES AND HOMERUNS GFI NUMBER INDICATES CIRCUIT NUMBER NUMBER CIRCUIT IDENTIFICATION BRANCH CIRCUITING SWITCH LEG FIXTURE TYPE a B NUMBER INDICATES CIRCUIT2 NOTE: 1 NLGP-B CIRCUIT BREAKER GROUND FAULT INTERRUPTING MLO MAIN LUG ONLY MICRO AFF CB GFI MCB EG EQUIPMENT GROUND FCU FAN COIL UNIT AFG AWG AMERICAN WIRE GAGE ABOVE FINISHED GRADE ABBREVIATIONS UOI OFCI WP TSP UC OC TWISTED SHIELDED PAIR UNLESS OTHERWISE INDICATED OWNER FURNISHED, CONTRACTOR INSTALLED CLG.CEILING A.AMPERE EXIST.EXISTING MAIN CIRCUIT BREAKER GND. KW. GROUND KILOWATT ABBREV. C. HP. CONDUIT ABOVE FINISHED FLOOR PH.PHASE PNL.PANEL REFRIG. TYP. SP.SPACE POLE SW. 4 W.WIRE 3P.15A. ABBREV. P. PP REFRIGERATOR POWER PANEL SWITCH TYPICAL WEATHERPROOF MOUNTED UNDER COUNTER HEIGHT MOUNTED OVER COUNTER HEIGHT P = POLE A = AMPERE DESCRIPTION NIC NOT IN CONTRACT LS LIFE SAFETY BRANCH CR EQ CRITICAL BRANCH EQUIPMENT BRANCH HORSEPOWER MICROWAVE DESCRIPTION VOLTV. VAV VARIABLE AIR VOLUME TMGB TELECOMMUNICATIONS MAIN GROUND BAR BMGB BUILDING MAIN GROUND BAR GENERAL DEMOLITION NOTES: GENERAL NOTES: L. K. J. I. H. G. F. E. D. C. B. A. TRACK LIGHTING WALL PHONE FINISHED FLOOR FINISHED CEILING TEL/COMM RECEPTACLE 1'-6" 4'-0" HORN/LIGHT EXIT WARNING & SIGNAL FIXTURE/SIGNS CENTERED ABOVE DOOR LIGHT SWITCH 46" STATION PULL 96" AFF TO TOP OF LENS LENS AND MAXIMUM OF MIN 80" AFF TO BOTTOM OF DEVICE TOP OF MAX 4'-0" COUNTER MAX. 1'-6" ABOVE 3' FROM EDGE OF BASE MAX. 2.THE ABOVE MOUNTING HEIGHTS SHALL BE ADHERED TO UNLESS SPECIFICALLY NOTED OR DETAILED OTHERWISE ON THE DRAWINGS OR SPECIFICATIONS THE ABOVE MOUNTING HEIGHTS SHALL BE USED FOR REFERENCE TO NEAREST BLOCK OR BRICK MOUNTING HEIGHTS TO CENTER OF OUTLETS UNLESS OTHERWISE NOTED. IN MASONRY CONSTRUCTION COURSING 1. DETAIL NOTES: T-STAT 4'-0" RAISE/LOWER SWITCH D FLOURESCENT STRIP LIGHT IS CALLED TO BE DEMOLISHED. ELECTRICAL CONTRACTOR TO REMOVE ALL TEL/DATA WIRING BACK TO SOURCE WHERE A DEVICE OR EQUIPMENT EQUIPMENT WILL OPERATE PROPERLY. AFTER RENOVATING EXISTING ELECTRICAL WORK, THE CONTRACTOR SHALL INSURE THAT ALL REMAINING AND NEW OUTSIDE OF THE SCOPE OF WORK. OF DEMOLITION, CONTRACTOR SHALL FIELD VERIFY ALL BRANCH CIRCUITS AND MAINTAIN THOSE CIRCUITS THAT EXTEND DISCONNECT AND REMOVE PANEL, FEEDERS AND BRANCH CIRCUITS BACK TO POINT OF SOURCE PRIOR TO THE START BUT ARE AFFECTED BY THE DEMOLITION OR NEW CONSTRUCTION. WALLS AND CEILINGS. MAINTAIN THE CONTINUITY OF BRANCH CIRCUIT WIRING TO ANY AREAS WHICH ARE TO REMAIN COMPLETELY BACK TO THE PANELBOARD. THE CONTRACTOR SHALL NOT ABANDON BRANCH CIRCUIT WIRING IN EXISTING BRANCH CIRCUIT WIRING TO DEVICES IN AREAS OF DEMOLITION SHALL BE DISCONNECTED, MADE SAFE AND REMOVED DISCONNECT, MAKE SAFE AND REMOVE ALL TEMPORARY AND ABANDONED WIRE WITHIN THE SPACE. IN ACCORDANCE WITH THE PLANS AND/OR AS DIRECTED AFTER COMPLETION OF OTHER TRADE'S WORK IN THAT AREA. AND STORE ANY OR ALL ELECTRICAL ITEMS IN PATH OF WORK, REINSTALLING AND RECONNECTING SAME AS REQUIRED, IN ANY AREA REQUIRING THE PERFORMANCE OF ANY TRADE'S WORK, THIS CONTRACTOR SHALL CAREFULLY REMOVE TO BE REUSED, SHALL BE CUT OFF FLUSH WITH SLAB LEVEL WITH CONCRETE. ALL EXISTING CONDUITS STUBBED THROUGH FLOOR SERVING ITEMS TO BE REMOVED AND NOT SHOWN OR REQUIRED AND FEEDERS PASSING THROUGH AND SERVING UNDISTURBED AREAS (SHOWN OR NOT SHOWN). MAINTAIN AND RESTORE, IF INTERRUPTED BY REMOVALS OR IN PATH OF NEW CONSTRUCTION, ALL CIRCUITS, CONDUITS DEMOLITION. SAFE ANY EQUIPMENT TO BE REMOVED BY OTHERS. COORDINATE REMOVAL OF EQUIPMENT WITH OTHER TRADES PRIOR TO SHALL BE REUSED AS DETERMINED BY CONTRACTOR. ALL UNUSED CONDUITS SHALL BE REMOVED. DISCONNECT AND MAKE DRAWINGS SHALL BE DISCONNECTED AND REMOVED UNLESS NOTED OTHERWISE. WALLBOXES, BACKBOXES AND CONDUIT FEEDERS AND CONDUITS BACK TO POINT OF SOURCE UNLESS OTHERWISE NOTED. ALL ITEMS SHOWN ON THE DEMOLITION THE EXISTING ELECTRICAL EQUIPMENT AND DEVICES WITHIN DEMOLITION AREA SHALL BE DEMOLISHED ALONG WITH ALL OTHER PERIODS. APPROVAL TO BE IN WRITING. DISCRETION OF THE FIRE DEPARTMENT AND THE OWNER'S REPRESENTATIVE, BUT MUST BE PLACED BACK ON LINE DURING RENOVATION MAY BE DISCONNECTED FROM SERVICE DURING THE HOURS THE CONTRACTOR IS WORKING, AT THE EXISTING FIRE ALARM SYSTEM SHALL BE KEPT OPERATIONAL DURING THE CONSTRUCTION PERIOD THE BUILDING UNDER NOT ALL DEVICES TERMINATIONS, JUNCTION BOXES AND WIRING HAVE BEEN SHOWN. WORK. PARTICULAR CARE SHALL BE TAKEN TO AVOID CREATING HAZARD OR CAUSING DISRUPTION IN ADJOINING AREAS. AND CAP ALL SERVICE LINES TO BE DISCONNECTED FOR THOSE SERVICES WHICH NORMALLY ARE INCLUDED IN HIS FIELD OF CONTRACTOR SHALL PARTICIPATE IN SURVEY OF THE EXISTING ELECTRICAL SYSTEMS. THE CONTRACTOR SHALL DISCONNECT UNFAMILIARITY WITH SITE CONDITIONS THAT ARE VISIBLE OR READILY CONSTRUED BY EXPERIENCED OBSERVERS. THIS THAT WILL AFFECT THE DEMOLITION WORK. NO COMPENSATION WILL BE GRANTED FOR ADDITIONAL WORK CAUSED BY AND ARE NOT GUARANTEED. PRIOR TO SUBMITTING BID, VISIT SITE AND IDENTIFY EXISTING CONDITIONS AND DIFFICULTIES EXISTING CONDITIONS ARE TAKEN FROM FIELD OBSERVATIONS AND PRIOR CONSTRUCTION DOCUMENTS WHEN AVAILABLE SCHEDULED THROUGH CUSTOMER SERVICE WITH AT LEAST 24 HOURS NOTICE BEFORE WORK IS TO BE STARTED. COORDINATE ALL SHUTDOWNS WITH UNIVERSITY PRIOR TO DEMOLITION. ALL FIRE ALARM SHUTDOWNS SHALL BE COORDINATE PHASING OF WORK WITH OWNER'S REPRESENTATIVE. NEW WORK. PROTECT BUILDING AND FURNISHINGS FROM DAMAGE. THE CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL AND REPLACEMENT OF EXISTING CONSTRUCTION IN THE WAY OF AS POSSIBLE, SUBJECT TO THE OWNERS APPROVAL. OF THE CONTRACTOR'S WORK, IT SHALL BE REPAIRED AND/OR REPLACED WITH SIMILAR OR LIKE MATERIALS, AS MUCH WHEN EXISTING CONSTRUCTION, WHICH IS TO REMAIN, IS DAMAGED DURING THE COURSE OF DEMOLITION AS A RESULT WALL MOUNTED SPEAKER CEILING MOUNTED SPEAKERS S CS# RL O. N. M. L. K. J. I. H. G. F. E. D. C. B. A. COMMENCEMENT OF ANY DEVICE ROUGH-IN FOR FINALIZATION OF ALIGNMENTS. CONTRACTOR TO SCHEDULE AND COORDINATE PROJECT WALKTHROUGH WITH ARCHITECT AND ENGINEER PRIOR TO ALL ELECTRICAL DEVICES (RECEPTACLES, SWITCHES, FIRE ALARM, ETC.) SHALL BE ALIGNED HORIZONTALLY AND VERTICALLY. PROVIDE PULLBOX FOR EVERY 180° OF BENDS FOR TEL/DATA AND 360° OF BENDS FOR POWER CONDUITS. ALL CONDUITS AND SUPPORTS SHALL BE AS TIGHT TO DECK AS POSSIBLE. DESIGN STANDARDS. AS CITED BY THE FIRE CODE OF NEW YORK STATE, BUILDING CODE OF NEW YORK STATE AND CORNELL UNIVERSITY ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE REFERENCE STANDARD EDITION OF NFPA CODES, TO CIRCUIT(S) AS INDICATED. PROVIDE CONDUIT/WIRING (CIRCUITING) AND REQUIRED EQUIPMENT CONNECTIONS TO ALL DEVICES/EQUIPMENT. CONNECT SEPARATE NEUTRALS (CIRCUITS SHALL NOT SHARE NEUTRALS). SAME EQUIPMENT GROUND) FOR EACH 20 AMPERE CIRCUIT UNLESS OTHERWISE NOTED. ALL CIRCUITS SHALL HAVE CIRCUITING TO DEVICES/EQUIPMENT SHALL BE 2-#12AWG & 1-#12EG (MULTIPLE HOME RUNS IN SAME CONDUIT MAY SHARE AND NOT GREATER THAN 96 INCHES ABOVE THE FINISHED FLOOR. FIRE ALARM SIGNALING APPLIANCES SHALL BE MOUNTED SUCH THAT THE ENTIRE LENS IS NOT LESS THAN 80 INCHES PROVIDE NYLON PULLSTRING IN ALL EMPTY CONDUITS. MINIMUM CONDUIT SIZE SHALL BE 3/4" FOR POWER CIRCUITS UOI. TO CONSTRUCTION. COORDINATE EXACT LOCATION OF ALL CONDUIT ROUTES, EQUIPMENT AND DEVICES WITH EXISTING CONDITIONS PRIOR MAINTAIN SERVICE CLEARANCES OF ALL EQUIPMENT. NON RATED PENETRATIONS. ALL FIRE RATINGS SHALL BE MAINTAINED. UTILIZE REMOVABLE FIRESTOPPING MATERIAL AT CABLE TRAY PENETRATIONS. PROVIDE ACOUSTICAL SEALANT FOR ALL SLEEVE AND SEAL ALL WALL AND FLOOR PENETRATIONS. PROVIDE FIRESTOPPING FOR ALL FIRE-RATED PENETRATIONS. MANUAL PULL STATIONF A1 A2 TO AV RACK MANAGED SWITCH & (1)2" CONDUIT FOR AV PANEL, (1)1" CONDUIT FOR TEL/DATA TO PROVIDE (1)3/4" CONDUIT FOR POWER TO (3) UNSHIELDED RJ-45 (5) SHIELDED RJ-45 (1) XLR(F) FOR: AV CONNECTION PLATES (3) DATA (1) QUAD RECEPTACLE POKE THROUGH - WIREMOLD 8AT TO AV RACK MANAGED SWITCH & (1)2" CONDUIT FOR AV PANEL, (1)1" CONDUIT FOR TEL/DATA TO PROVIDE (1)3/4" CONDUIT FOR POWER TO (2) UNSHIELDED RJ-45 (2) SHIELDED RJ-45 FOR: AV CONNECTION PLATES (3) DATA (1) QUAD RECEPTACLE POKE THROUGH - WIREMOLD 8AT SWITCH IN ELEC RM 361. TERMINATE IN FACEPLATE AND MANAGED PROVIDE ONE(1) CAT 6A UTP CABLE, MANAGED SWITCH IN ELEC RM 361. BOX. 1" EMT CONDUIT EXTENDED TO WAP - WALL MOUNT AT 90"AFF 4"x2"x 1-3/4" MANAGED SWITCH IN ELEC RM 361. 46"AFF. PROVIDE (1) CAT 6 CABLE TO FOR DATA/VOICE. WALL MOUNT AT IDF (UNLESS OTHERWISE NOTED) AND 1" CONDUIT EXTENDED TO NEAREST W - SINGLE GANG BACK BOX WITH MUD RING MANAGED SWITCH IN ELEC RM 361. PULL (3) CAT 6 CABLES TERMINATE AT OTHERWISE NOTED) FOR DATA/VOICE. EXTENDED TO NEAREST AV RACK (UNLESS FACEPLATE WITH TRIPLEX DESIGN. 1" CONDUIT 4"x4"x2.5D" BOX WITH A 2-GANG MUD RING & DATA DROP TV- COORD. MOUNTING HEIGHT WITH ARCH. SUBSCRIPTS INDICATE TYPE: DUPLEX RECEPTACLE, 20 AMP, 125 VOLT # INDICATES STATION NUMBER LIGHTING CONTROL STATION SOURCE CONTROLLING DIMMER SWITCH, MATCH TYPE TO LIGHTING 3/12/2015 2:03:59 PMJAD REVISIONS no.date by description ALL RIGHTS RESERVED © ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS 387 East Main Street Rochester, NY 14604-2107 Voice: 585.232.8300 Fax: 585.232.9221 w w w . s w b r . c o m DRAWING TITLE proj. no. checked proj. mgr. drawn by STATUS: DRAWING NO. PROJECT: CLIENT: ISSUE DATE: ROCHESTER, N E W Y O R K CONSULTANT: ENGINEERING P.C. MECHANICAL/ELECTRICAL ENGINEERING CONSULTANTS ROCHESTER, NEW YORK 14604 (585) 288-5590 FAX: (585) 288-0233 M/E Project: 150166 150 NORTH CHESTNUT STREET ROCHESTER BUFFALO SYRACUSE CAPITAL DISTRICT ROOM RENOVATIONS UPGRADES & MINOR OF '49 CLASSROOM A/V HOLLISTER HALL CLASS ENGINEERING COLLEGE OF CORNELL UNIVERSITY - 15365.00 10/22/2015 DOCUMENTS 100% CONSTRUCTION CTV MRG E-100 NORTH E-100 1 SCALE: 1/4"=1'-0"0 2'4'8' PARTIAL 3RD FLOOR PLAN DEMOLITION - LIGHTING LIGHTING PLAN DEMOLITION - PARTIAL 3RD FLOOR a a a b b b ccc d b x x x y y y z z z D x,y,z a,b,c,d x,y,z a,b,c,d 3L2-9 (E) (E) (E) GENERAL NOTES: A.SALVAGE ALL EXISTING CIRCUITS FOR REUSE. 10 3L1-9 7 3L2-9 10 3L1-9 (225A) 3L1-9 3/12/2015 2:03:59 PMJAD REVISIONS no.date by description ALL RIGHTS RESERVED © ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS 387 East Main Street Rochester, NY 14604-2107 Voice: 585.232.8300 Fax: 585.232.9221 w w w . s w b r . c o m DRAWING TITLE proj. no. checked proj. mgr. drawn by STATUS: DRAWING NO. PROJECT: CLIENT: ISSUE DATE: ROCHESTER, N E W Y O R K CONSULTANT: ENGINEERING P.C. MECHANICAL/ELECTRICAL ENGINEERING CONSULTANTS ROCHESTER, NEW YORK 14604 (585) 288-5590 FAX: (585) 288-0233 M/E Project: 150166 150 NORTH CHESTNUT STREET ROCHESTER BUFFALO SYRACUSE CAPITAL DISTRICT ROOM RENOVATIONS UPGRADES & MINOR OF '49 CLASSROOM A/V HOLLISTER HALL CLASS ENGINEERING COLLEGE OF CORNELL UNIVERSITY - 15365.00 10/22/2015 DOCUMENTS 100% CONSTRUCTION 359 362 366 368 369365363361 300TA351 300CA CTV MRG E-101 NORTH E-101 1 SCALE: 1/4"=1'-0"0 2'4'8' PARTIAL 3RD FLOOR PLAN DEMOLITION - POWER & SPECIAL SYSTEMS SPECIAL SYSTEMS DEMOLITION - POWER & PARTIAL 3RD FLOOR PLAN S S S SSS CLG.CLG. q r s JJ 3L2-9 CONTROLS CLG. FAN F (ER) S S J q,r,s (E) (E) (ER) (ER)(ER)(ER) (ER) (ER) 2 2 2 2 (E)(E) 1 1 B. A. GENERAL NOTES: DEMOLITION NOTES: TURN OVER ALL AV EQUIPMENT TO OWNER. SLAVAGE ALL EXISTING CIRCUITS FOR REUSE. 1 REUSE IN NEW ROOM LAYOUT. CEILING FAN AND CONTROLS SHALL BE SALVAGED FOR PROVIDE NEW DEVICE AND COVER PLATE. RECEPTACLE TO BE EXTENDED TO NEW WALL COVERING. 2 13,15 3L2-9 12,14 3L2-9 8 3L2-9 10 3L2-9 7 3L2-9 30 3L1-9 30 3L1-9 5 3L2-9 9,11 3L2-9 30 3L1-9 1" EMT (225A) 3L1-93/12/2015 2:03:59 PMJAD REVISIONS no.date by description ALL RIGHTS RESERVED © ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS 387 East Main Street Rochester, NY 14604-2107 Voice: 585.232.8300 Fax: 585.232.9221 w w w . s w b r . c o m DRAWING TITLE proj. no. checked proj. mgr. drawn by STATUS: DRAWING NO. PROJECT: CLIENT: ISSUE DATE: ROCHESTER, N E W Y O R K CONSULTANT: ENGINEERING P.C. MECHANICAL/ELECTRICAL ENGINEERING CONSULTANTS ROCHESTER, NEW YORK 14604 (585) 288-5590 FAX: (585) 288-0233 M/E Project: 150166 150 NORTH CHESTNUT STREET ROCHESTER BUFFALO SYRACUSE CAPITAL DISTRICT ROOM RENOVATIONS UPGRADES & MINOR OF '49 CLASSROOM A/V HOLLISTER HALL CLASS ENGINEERING COLLEGE OF CORNELL UNIVERSITY - 15365.00 10/22/2015 DOCUMENTS 100% CONSTRUCTION 359 362 366 368 369365363361 300TA351 300CA CTV MRG E-200 NORTH E-200 1 SCALE: 1/4"=1'-0"0 2'4'8' LIGHTING PLAN NEW WORK - PARTIAL 3RD FLOOR PARTIAL 3RD FLOOR PLAN NEW WORK - LIGHTING DRAWING NOTES: (E) 3L2-9 3L1-9-225A (E) (E) b L1 a L1 a L1 a L1 b L1 b L1 b L1 c L1 c L1 d L1 d L1 d L1 d L1 c L1 c L1 b L1 b L1 b L1 c L1 d L1 OS OS OS 1 X1 1 X1 EM 5 EM 5 CS3 CS2CS1 L3 e L3 e 3 4 3 T1 L2 L2 L2 1 2 3 4 5 CONNECT TO NEAREST RECEPTACLE CIRCUIT ABOVE CEILING. CONTROL DEVICE SHALL BE MOUNTED BELOW SCREEN. DEVICE SHALL BE SURFACE MOUNTED ON BLOCK WALL IN CUSTOM FINISHED BACK BOX. WALL PACK LOCATIONS. EMERGENCY BATTERY PACK CIRCUIT. EXTEND AS REQUIRED TO NEW EMERGENCY PROVIDE NEW EMERGENCY BATTERY PACK LIGHTS AND CONNECT INTO EXISTING MOUNTED LOCATIONS. CIRCUITING AS REQUIRED FROM EXISTING WALL MOUNTED LOCATION TO NEW CEILING PROVIDE NEW EXIT SIGNS CONNECTED TO SALVAGED EXIT SIGN CIRCUIT. EXTEND 2 2 f E. D. C. B. A. GENERAL NOTES: CONTROLS. AND EXTEND LIGHTING BRANCH CIRCUIT AS REQUIRED FOR NEW LIGHTING LAYOUT AND ALL LIGHTING SHALL BE FED FROM SALVAGED LIGHTING CIRCUIT #9 IN PANEL 3L1-9. REWORK REFER TO DRAWING E-201 FOR ROUTING OF RACEWAY WITHIN ROOM. DEMOLITION. PROVIDE (1)120V CIRCUIT TO FEED THE C2N-SDC FROM A CIRCUIT MADE SPARE DURING THE SAME CIRCUITS AS THE LIGHTING ZONES THAT ARE BEING FED FROM THAT COMPONENT. ALL 120V POWER REQUIREMENTS FOR THE LIGHTING CONTROL SYSTEM SHALL COME FROM THERE SHALL BE NO EXPOSED RACEWAYS WITHIN THE PROJECT AREA. REFER TO LIGHTING CONTROL DIAGRAM ON E-600. f T1 L23/12/2015 2:03:59 PMJAD REVISIONS no.date by description ALL RIGHTS RESERVED © ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS 387 East Main Street Rochester, NY 14604-2107 Voice: 585.232.8300 Fax: 585.232.9221 w w w . s w b r . c o m DRAWING TITLE proj. no. checked proj. mgr. drawn by STATUS: DRAWING NO. PROJECT: CLIENT: ISSUE DATE: ROCHESTER, N E W Y O R K CONSULTANT: ENGINEERING P.C. MECHANICAL/ELECTRICAL ENGINEERING CONSULTANTS ROCHESTER, NEW YORK 14604 (585) 288-5590 FAX: (585) 288-0233 M/E Project: 150166 150 NORTH CHESTNUT STREET ROCHESTER BUFFALO SYRACUSE CAPITAL DISTRICT ROOM RENOVATIONS UPGRADES & MINOR OF '49 CLASSROOM A/V HOLLISTER HALL CLASS ENGINEERING COLLEGE OF CORNELL UNIVERSITY - 15365.00 10/22/2015 DOCUMENTS 100% CONSTRUCTION 359 362 368 369365363 300TA351 CLASSROOM 366 ELECTRICAL 361 300CA CTV MRG E-201 NORTH E-201 1 SCALE: 1/4"=1'-0"0 2'4'8' PARTIAL 3RD FLOOR PLAN NEW WORK - POWER & SPECIAL SYSTEMS SPECIAL SYSTEMS NEW WORK - POWER & PARTIAL 3RD FLOOR PLAN (ER) (E) 3L2-9 3L1-9-225A (E) CLG. CLG. A2 A1 FF WAP WAP TV TV M (ER)(ER) CR F DRAWING NOTES: 7 M R/L (ER) CONTROLS CLG. FAN q,r,s (ER)q (ER)r (ER)s7 1 1 1 7 7 1 GENERAL NOTES: 1 2 3 4 5 6 7 8 9 10 11 12 13 (BY OTHERS) AV RACK 13 JJ 8 12 (E)(E) 4 5 CLG. 6 6 54 CLG. J J J J J SCREEN PROJECTION 11 11 1010 9 1010 3 22 14 15 16 16 3L3-9 17 15 15 15 14 20 11 12 13 14 1 17 14 2 3 4 5 6 7 8 9 10 15 3L3-9 18 18 EF-1 19 19 DC DC DRI PS PTPT EED EEDRTERTE FAR 20 21 21 J J J J J J J J J J J J J J J J 22 23 24 25 26 26 26 26 26 22 23 23 23 23 22 22 22 24 24 24 24 25 25 25 25 JJ 27 27 27 28 28 28 29 29 29 29 29 1" CONDUIT TO PASS THROUGH. STUBBED UP INTO FURNITURE LEG DIRECTLY ABOVE. CORE SHALL BE 1-1/4" TO ALLOW FOR PROVIDE A JUNCTION BOX IN THE CEILING SPACE OF THE SECOND FLOOR WITH A 1" CONDUIT FEED UP TO MICROPHONES AT TABLES. LARGER FEED BACK TO AV RACK TO JUNCTION BOX IN CEILING SPACE OF SECOND FLOOR FOR PROVIDE A 1" CONDUIT IN CEILING SPACE OF SECOND FLOOR TO CONNECT JUNCTION BOX OF ROOM 261 AND THEN ROUTE UP THROUGH CORES IN FLOOR TO BACK OF AV RACK IN ROOM 361. PROVIDE A 2" CONDUIT FROM JUNCTION BOX IN CEILING SPACE OF SECOND FLOOR TO ELECTRICAL FURNITURE LEG WILL BE LOCATED. PROVIDE A JUNCTION BOX IN RAISED FLOOR SYSTEM DIRECTLY BELOW WHERE THE MICROPHONE BOX BELOW TABLE LEG FOR MICROPHONES. PROVIDE 1" CONDUIT FROM JUNCTION BOX IN SECOND FLOOR CEILING SPACE TO JUNCTION BOX BELOW TABLE LEG FOR POWER. PROVIDE 3/4" CONDUIT FROM JUNCTION BOX IN SECOND FLOOR CEILING SPACE TO JUNCTION JUNCTION BOX LOCATED IN CEILING SPACE OF SECOND FLOOR BELOW FOR MICROPHONES. JUNCTION BOX LOCATED IN CEILING SPACE OF SECOND FLOOR BELOW FOR POWER. TO 4" CONDUITS ACROSS CORRIDOR. PROVIDE (2) 2" CONDUITS FROM ABOVE ACCESSIBLE CEILING TO AV RACK. ROUTE ADJACENT PROJECTION SCREEN SHALL BE FED FROM CIRCUIT 20 IN PANEL 3L3-9. MANAGED NETWORK SWITCH COMES DOWN FROM ELECTRIC ROOM ABOVE. LOCATION WHERE 2" CONDUIT FOR FIBER CONNECTION FROM TELE/DATA ROOM TO WITHIN ELECTRICAL ROOM 361. PROVIDE A MANUAL MOTOR STARTER WITH RELAY TO CONTROL NEW FAN. LOCATE ENTIRE PANEL WITH 20A-1P CIRCUIT BREAKERS. ROOM 361. PROVIDE A 100A FEEDER FROM PANEL 3L2-9 USING 4-#2, 1-#8EG, 1-1/2"C. PROVIDE PROVIDE A NEW 100A, MLO, 22KAIC, 30 CIRCUIT PANEL ON WEST WALL AT NORTH END OF 22KAIC CIRCUIT BREAKER IN EXISTING SQUARE D PANEL. REMOVE CIRCUIT BREAKERS 10,12,14 AND TURN OVER TO OWNER. PROVIDE A NEW 100A-3P, CIRCUIT AS REQUIRED. RECEPTACLES SHALL BE FED FROM CIRCUIT #8 IN PANEL 3L2-9. REWORK AND EXTEND CIRCUIT AS REQUIRED. TV RECEPTACLE SHALL BE FED FROM CIRCUIT #10 IN PANEL 3L1-9. REWORK AND EXTEND IN FIELD. PROVIDE (6) 2" CORES FOR AV WIRING ADJACENT TO AV RACK. COORDINATE FINAL LOCATION PROVIDE (2) 4" CONDUITS WITH PULL LINES FOR AV WIRING. IN FIELD WITH SCREEN MOUNTS. PROVIDE 2" CONDUIT TO ABOVE ACCESSIBLE CEILING. PROVIDE DEVICES WITHIN CHIEF PAC525 WALL BOX (BOX BY EC). COORDINATE MOUNTING HEIGHT PROVIDE SINGLE GANG JUNCTION BOX AT 105" AFF WITH 1" CONDUIT TO ACCESSIBLE CEILING SPACE. PROVIDE SINGLE GANG JUNCTION BOX AT 99" AFF WITH 1" CONDUIT TO ACCESSIBLE CEILING SPACE. PROVIDE (2)4" WALL BOXES FOR AV WITH 1" CONDUIT TO ROOM BELOW CEILING SPACE. PROVIDED WITH THE PREWIRED FURNITURE. COORDINATE LOCATION OF FURNITURE LEGS IN FIELD. BELOW WHERE THE POWERED FURNITURE LEG WILL BE LOCATED TO CONNECT THE MC CABLE CORE SHALL BE 1" IN DIAMETER. PROVIDE A JUNCTION BOX IN RAISED FLOOR SYSTEM DIRECTLY PROVIDED BETWEEN CEILING SPACE OF FLOOR BELOW AND JUNCTION BOX MOUNTED BELOW TABLE LEG. CONDUIT UP TO JUNCTION BOX MOUNTED BELOW FURNITURE LEG. NO JUNCTION BOXES SHALL BE POWER CONNECTION TO PRE WIRED TABLES LOCATION. PROVIDE CORE THROUGH FLOOR TO ROUTE EXTEND EXISTING DEVICES TO NEW WALL COVERING. PROVIDE NEW DEVICE AND COVER PLATE. CIRCUIT AS REQUIRED. RECEPTACLES SHALL BE FED FROM CIRCUIT #5 IN PANEL 3L2-9. REWORK AND EXTEND PROVIDE CONNECTION TO DUPLEX RECEPTACLES IN AV CEILING BOX (BOX BY OTHERS). MOUNT IN CEILING AV BOX (BOX BY OTHERS). PROVIDE 3/4" CONDUIT WITH WIRING PER MANUFACTURERS REQUIREMENTS. MATCH WALL FROM CEILING TO DEVICE. DEVICE SHALL BE SURFACE MOUNTED. PROVIDE WIREMOLD 700 SERIES RACEWAY PAINTED TO TO CONNECT THE MC CABLE PROVIDED WITH THE PREWIRED FURNITURE. LOCATION. CORE SHALL BE 1-1/4" IN DIAMETER. PROVIDE A JUNCTION BOX IN CEILING SPACE BELOW POWER CONNECTION TO PRE WIRED TABLES LOCATION. COORDINATE CORING OF FLOOR WITH LEG ELECTRICAL DRAWINGS. AND BE DONE BY GC. SIZES AND QUANTITY OF CORES SHALL BE PER FLOOR CORING LOCATIONS SHALL BE PER ARCHITECTURAL DRAWINGS PROVIDE CONDUIT BUSHINGS ON ENDS OF ALL CONDUITS. CIRCUITING HAS BEEN MODIFIED. PROVIDE UPDATED TYPED PANEL DIRECTORIES FOR ALL PANELS WHERE CALLED FOR. AV WIRING TO BE INSTALLED IN D-RINGS/J-HOOKS WHERE CONDUIT IS NOT NOTED. CIRCUIT NUMBERS AS INDICATED. ALL CIRCUITS SHALL BE FED FROM PANEL 3L3-9 UNLESS OTHERWISE DRAWING E-601 FOR MORE INFORMATION ADDITIONAL INFORMATION. REFER TO CABLE PULLING SCHEDULE ON TO AV DOCUMENTS INCLUDED WITHIN THIS SET FOR REFERENCE FOR EC SHALL PULL ALL AV CABLES FURNISHED BY AV CONTRACTOR. REFER IN AV RACK. ALL NEW DATA SHALL BE ROUTED BACK TO MANAGED SWITCH MOUNTED FOR FINAL LOCATION OF AV JUNCTION BOXES. REFER TO AV DRAWINGS AND COORDINATE WITH AV CONTRACTOR I. H. G. F. E. C. B. A.3/12/2015 2:03:59 PMJAD REVISIONS no.date by description ALL RIGHTS RESERVED © ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS 387 East Main Street Rochester, NY 14604-2107 Voice: 585.232.8300 Fax: 585.232.9221 w w w . s w b r . c o m DRAWING TITLE proj. no. checked proj. mgr. drawn by STATUS: DRAWING NO. PROJECT: CLIENT: ISSUE DATE: ROCHESTER, N E W Y O R K CONSULTANT: ENGINEERING P.C. MECHANICAL/ELECTRICAL ENGINEERING CONSULTANTS ROCHESTER, NEW YORK 14604 (585) 288-5590 FAX: (585) 288-0233 M/E Project: 150166 150 NORTH CHESTNUT STREET ROCHESTER BUFFALO SYRACUSE CAPITAL DISTRICT ROOM RENOVATIONS UPGRADES & MINOR OF '49 CLASSROOM A/V HOLLISTER HALL CLASS ENGINEERING COLLEGE OF CORNELL UNIVERSITY - 15365.00 10/22/2015 DOCUMENTS 100% CONSTRUCTION 359 362 368 369365363 300TA351 CLASSROOM 366 ELECTRICAL 361 300CA CTV MRG E-202 NORTH 0 2'4'8' 1 SCALE: 1/4"=1'-0" PLANS FLOOR AND PENTHOUSE PARTIAL EXISTING 4TH E-202 PARTIAL 4TH FLOOR AND PENTHOUSE PLANS NEW WORK - POWER & SPECIAL SYSTEMS 1 2 3 4 DRAWING NOTES: 1 LOCATION WHERE 2" CONDUIT COMES UP FROM 4TH FLOOR BELOW. ABOVE. COORDINATE FINAL LOCATION IN FIELD. LOCATION WHERE 2" CONDUIT WILL GO UP INTO TELE/DATA ROOM PROPOSED ROUTING OF 2" CONDUIT FOR FIBER. CEILING SPACE OF 4TH FLOOR. NETWORK SWITCH COMES UP FROM ELECTRIC ROOM BELOW AND TO LOCATION WHERE 2" CONDUIT FOR FIBER CONNECTION TO MANAGED 2 3 4 A. GENERAL NOTES: FIBER IS INSTALLED BY CIT. PATHWAY IS INSTALLED BY EC.3/12/2015 2:03:59 PMJAD REVISIONS no.date by description ALL RIGHTS RESERVED © ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS 387 East Main Street Rochester, NY 14604-2107 Voice: 585.232.8300 Fax: 585.232.9221 w w w . s w b r . c o m DRAWING TITLE proj. no. checked proj. mgr. drawn by STATUS: DRAWING NO. PROJECT: CLIENT: ISSUE DATE: ROCHESTER, N E W Y O R K CONSULTANT: ENGINEERING P.C. MECHANICAL/ELECTRICAL ENGINEERING CONSULTANTS ROCHESTER, NEW YORK 14604 (585) 288-5590 FAX: (585) 288-0233 M/E Project: 150166 150 NORTH CHESTNUT STREET ROCHESTER BUFFALO SYRACUSE CAPITAL DISTRICT ROOM RENOVATIONS UPGRADES & MINOR OF '49 CLASSROOM A/V HOLLISTER HALL CLASS ENGINEERING COLLEGE OF CORNELL UNIVERSITY - 15365.00 10/22/2015 DOCUMENTS 100% CONSTRUCTION DN UP DN 156 473 147 471 148 469 148 467 198 465 190 463 473 472 417 470 449 468 434 466 1321 464 772 462 718 452 254 455 259 453A 251 453 519 451 247 450 149 425 179 400T 193 422 202 423 148 421 148 419 1322 420 3246 400CA 145 400SA 62 400JB 50 400JA 44 400E 98 450A 95 461 4P0UWELLOPEN1549UPDN4P0S274P0157 CTV MRG E-500 AND RISER DIAGRAM ELECTRICAL DETAILS J SCALE: NONE MOUNTED LUMINAIRES TYPICAL BRANCH CIRCUIT WIRING FOR CEILING ƒ" EMT ƒ" EMT TYPICAL LUMINAIRE 6' LENGTH CONDUIT MAXIMUM 1/2" FLEXIBLE METAL 6' LENGTH CONDUIT MAXIMUM 1/2" FLEXIBLE METAL SCALE: NONE TYPICAL RECEPTACLE IDENTIFICATION PANEL NUMBER BRANCH BREAKER NUMBER 1-CBLP-2-SHB#32 THE PLANS. NUMBER AS SHOWH ON THE SAME CIRCUIT AND NOT NECESSARILY SHALL BE AS INSTALLED CIRCUIT INFORMATION SUFFICIENT. ACTUAL WILL NOT BE FACTORY ADHESIVE USING CONTACT CEMENT. ADHERE TO COVERPLATE COLOR WITH OWNER, DYMO LABEL, VERIFY RECEPTACLES HORIZONTALLY MOUNTED OR TO LEFT OF OUTLET ON GROUNDING PIN ON TOP 1-CBLP-2-SHB#32TYPICAL C. B. A. DETAIL NOTES: ENGRAVING ON THE RECEPTACLE COVERPLATE STATING "UPS POWER". FOR RECEPTACLES WHICH ARE FED FROM UPS POWER ALSO PROVIDE TO REDUCE SOUND TRANSMISSION. OUTLETS BACK TO BACK. INSTALL IN ADJACENT STUD CAVITIES, DO NOT INSTALL RECEPTACLES, COMPUTER OR TELEPHONE CONNECT TO GROUND BUS IN PANEL. PROVIDE GREEN GROUND WIRE IN ALL RECEPTACLE CIRCUITS. ARCHITECT FOR ALL OTHERS. 2. AS SELECTED BY 1. RED FOR EMERGENCY SHALL BE: RECEPTACLE COLOR FIRE ALARM CONTROL PANEL FACP INTERFACE USER DISTRIBUTION PROGRAM SOFTWARE HARDWARE/ IDC'S SUPPLY POWER BATTERY TS F TS S H (INITIATING DEVICES) INPUTS AND EMERGENCY CONTROLS) (NOTIFICATION APPLIANCES OUTPUTS NAC'S CKT CITY F F FAN SHUTDOWN DH STATION OR CONTROL DEPARTMENT FIRE FAAP PRINTER F PHONE FIGHTER FIRE INTERFACE OR PC CRT/KBD W/BYPASS RELAYS AUX GAA ECCP DSD DSD RTS RTS SCALE: NONE TYPICAL FIRE ALARM CONTROL PANEL SD FROM LIFE SAFETY PANEL EMERGENCY CIRCUITS DEDICATED 120V 1 2 3 E-500 E-500 E-500 FIRE ALARM NOTES: J. I. H. G. F. E. D. C. B. A. elevator controller. Addressable monitor devices shall be located adjacent to monitored device. Addressable control devices shall be located within 3 feet of the controlled device, such as ventilation fan or accessible and conspicuous location. Remote Test Stations for Duct Detectors and Beam Detectors: Mount approximately 5 feet high in an 5 feet in height to panel display readout. All panels shall have 36 inches of working clearance in front of panel. Fire Alarm Control Panels, Annunciator Panels, Warden Stations, etc.: Mount in accessible location approximately below ceiling. Audible Notification Appliances: Top of device not less than 90 inches above floor or not less than 6 inches visible to persons entering the floor from the exit stair. appliances in corridors. Locate an appliance opposite each access door to an exit stair so that it will be not more than 15 feet from end of the corridor, with a separation not greater than 100 feet between above the floor. Depending on ceiling height, higher mounting is preferred. Visible appliances shall be located Visual and Combination Audible/Visual Notification Appliances: The entire lens shall be within 80 inches-96 inches detector shall be installed within 2 feet of each sprinkler head. Elevator Shutdown: If sprinkler heads are located in the elevator machine room or hoistway top, one heat elevator recall are only required where the top of the hoistway is sprinklered.) detectors shall be no more than 21 feet from centerline of elevator door. (Hoistway smoke detectors for Elevator Recall: Elevator recall shall be by lobby, machine room, and hoistway smoke detectors only. Lobby not more than 5 feet from door. release. Smoke detectors, which are provided for door release only, shall be on the centerline of doorway and Door Release: Smoke detection providing area coverage on either side of the doors may be used for door conditions and give reasons for coverage design.) (If design conditions other than smooth ceilings or ceiling heights over 12 feet are encountered, show reflected ceiling plan. Provide a spacing of 3 feet or more from supply and return diffusers. Coordinate trades by means of the 0.7 times the detector spacing. Spacing is 30 feet for smoke detectors and 50 feet for heat detectors. Spot Type Heat and Smoke Detectors: For smooth ceilings, all points on the ceiling shall have a detector within and accessible. entrance to an exit. Locate on the latch side of door, if possible. Boxes are to be conspicuous, unobstructed, Manual Fire Alarm Boxes: Mounting height 42-48 inches to handle. Locate no more than 5 feet from the Fire Alarm Mounting and Spacing Guide 10. 9. 8. 7. 6. 5. 4. 3. 2. 1. PROVIDE DEVICE LABELING AS PER CORNELL UNIVERSITY STANDARD 16721-2.11. ALL NEW DEVICES SHALL BE ADDRESSABLE. PROVIDED. NOT ALL EXISTING DEVICES AND EQUIPMENT ARE SHOWN FOR CLARITY OF NEW WORK TO BE ANNUNCIATOR. THE SIGNAL SHALL INDICATE "OFF NORMAL CONDITION." GENERATOR SHALL HAVE A REMOTE SIGNAL DEVICE TIED INTO THE FIRE ALARM ANNUNCIATOR. THE ALARM SHALL INDICATE "ENGINE RUNNING". GENERATOR SHALL HAVE A REMOTE SIGNAL DEVICE TIED INTO THE FIRE ALARM PROVIDE ALL INTERCONNECTING WIRING, ADDRESSABLE MODULES, ETC. ROOMS FOR SHUNT TRIP CONTROL OF THE DISCONNECT SWITCHES SERVING THE ELEVATORS. PROVIDE CONTROL RELAY MODULES FOR HEAT DETECTORS LOCATED IN ELEVATOR MACHINE PUMP RUNNING, FIRE PUMP FAULT AND FIRE PUMP POWER LOSS. PROVIDE MONITOR MODULES FOR INDICATION AT FIRE ALARM CONTROL PANEL OF THE FIRE REFER TO FLOOR PLANS FOR EQUIPMENT LOCATIONS. SMOKE DETECTORS AND ELEVATOR CONTROLLER, ETC. NOT ALL INTERCONNECTING WIRING IS INDICATED, i.e. AS BETWEEN ELEVATOR LOBBY SYSTEM AND DEVICES HAVE BEEN INSTALLED AND TESTED. ANY EXISTING FIRE ALARM SYSTEM DEVICES SHALL REMAIN IN OPERATION UNTIL THE NEW COMPLETE SYSTEM AS REQUIRED BY SYSTEM MANUFACTURER. TO INDICATE ROUTING OR QUANTITY OF WIRES REQUIRED. PROVIDE WIRING FOR A WIRING INDICATED ON THE RISER DIAGRAM IS DIAGRAMMATIC ONLY. IT IS NOT INTENDED LETTERING INDICATING "FIRE ALARM SYSTEM". ALL FIRE ALARM SYSTEM JUNCTION BOXES SHALL BE PAINTED RED WITH STENCIL AND OPERATIONAL SYSTEM. ADDITIONAL TERMINAL CABINETS, BOOSTERS, ETC. AS REQUIRED TO PROVIDE A COMPLETE DEVICES AND MINIMUM QUANTITIES OF TERMINAL CABINETS & POWER BOOSTERS. PROVIDE THE FIRE ALARM RISER DENOTES THE GENERAL ARRANGEMENT OF THE SYSTEM WITH TYPICAL CIRCUITS. FOR EASY IDENTIFICATION OF INITIATING, INDICATING AND AUXILIARY CONTROL WIRING COLOR CODES SHALL BE CONSISTENT THROUGHOUT THE SYSTEM AND SHALL ALLOW OPENS, OR SHORTS. ALL WIRING SHALL BE CHECKED AND TESTED TO ENSURE THAT THERE ARE NO GROUNDS, DIRECTLY OPPOSITE ITS TERMINAL. CONDUCTORS IN CABINETS SHALL BE FORMED AND HARNESSED SO THAT EACH DROPS OFF AA. Z. Y. X. V. U. T. S. R. Q. P. O. N. M. L. K. MARKERS". IN CONDUIT CONTAINING MORE THAN ONE WIRE SHALL BE LABELED ON EACH END WITH "E-Z TRANSPOSING OR CHANGING COLOR CODING OF WIRES IS NOT PERMITTED. ALL CONDUCTORS TO ENSURE POSITIVE GROUNDING THROUGHOUT THE ENTIRE SYSTEM. ALL CONDUIT, MOUNTING BOXES AND PANELS SHALL BE HUNG AND FASTENED WITH FITTINGS ANY OTHER FIRE ALARM SYSTEM WIRING IN A COMMON CONDUIT. AND CONTROL WIRING (FAN SHUTDOWN, ETC.) IN SEPARATE CONDUIT. DO NOT RUN WITH ALL LOW VOLTAGE FIRE ALARM CIRCUITS MAY OCCUPY A COMMON CONDUIT. RUN AC POWER PROVIDE ADDITIONAL DETECTORS WHERE REQUIRED. SPACE DETECTORS IN ACCORDANCE WITH THE MANUFACTURERS RECOMMENDED DISTANCE. DIRECTORY. BREAKER SHALL BE CLEARLY MARKED "FIRE ALARM CIRCUIT CONTROL" IN THE PANELBOARD PANELBOARD TO CONTROL PANELS, TERMINAL CABINETS, ETC. AS REQUIRED. THE CIRCUIT PROVIDE 120V, 20A DEDICATED BRANCH CIRCUITS FROM THE LOCAL AREA LIFE SAFETY IDENTIFICATION. TESTING. ALL OTHER FIRE ALARM JUNCTION BOXES SHALL BE MARKED FOR FACP AND OTHER PANELS SHALL BE MOUNTED WITH CLEARANCES FOR OBSERVATION AND WRAP OVER ITSELF, PROTECTING THE WRITING. TAPE. THE TAPE SHALL BE LONG ENOUGH SO WHEN WRAPPED ROUND THE CABLE IT WILL INSTALLATION. LABELING IS TO BE DONE WITH PERMANENT MARKERS ON CLEAR MYLAR RECORD OF THE IDENTIFICATION AND USE OF EACH ABLE MUST BE MADE AT THE TIME OF CABLING MUST BE UNIQUELY IDENTIFIED AND LABELED, AND A PERMANENT, ACCURATE APPLY. ACCORDANCE WITH EQUIPMENT MANUFACTURERS RECOMMENDATIONS AND ALL CODES THAT MAY ALL FIRE ALARM SYSTEM RACEWAY SIZES AND CIRCUITRY REQUIREMENTS SHALL BE IN SPECIFICATION FOR ADDITIONAL FIRE ALARM SYSTEM REQUIREMENTS. ALL WIRING SHALL BE CLASS A WIRING. REFER TO SECTION 283102 OF THE FLOOR PLANS. DEVICES SHOWN ARE DIAGRAMMATICALLY ONLY. FOR EXACT LOCATIONS AND QUANTITIES SEE (E) (E) (E) BATTERIES TROUBLE TROUBLE IN CASE OF FIRE EVACUATE BUILDING AND CALL THE FIRE DEPARTMENT!!! ALARM 1 ALARM 2 PREALARM TROUBLE PREALARM ALARM 2 ALARM 1 ALARM ALARMALARMALARM ALARM ALARMALARM FACP ALARM TROUBLE TROUBLE ALARM TROUBLE ALARM TROUBLE TROUBLE TROUBLE TROUBLE TROUBLE ALARM TROUBLE ALARM TROUBLE ALARM TROUBLE ALARM TROUBLE ALARM TROUBLE ALARM TROUBLE ALARM TROUBLE ALARM TROUBLE ALARM PREALARM ALARM 2 ALARM 1 ALARM 1 ALARM 2 PREALARM TROUBLE TROUBLETROUBLETROUBLE TROUBLETROUBLE ALARM TROUBLE ALARMALARM TROUBLE TROUBLE TROUBLE ALARM TROUBLE ALARM TROUBLE ALARM TROUBLE ALARM ALARM ALARM CORRIDOR CIRCUIT 120V, 20A 3 REFER TO FLOOR PLAN FOR EXACT QUANTITY OF DEVICES AND LOCATIONS. THIRD FLOOR (E)(E)(E)(E) FOR DIAGRAMMATIC PURPOSES ONLY. SCALE: NONE 1 2 FIRE ALARM DRAWING NOTES: 3 FIRE ALARM DIAGRAMMATIC RISER DIAGRAM - NEW WORK F F F F F 4 4 PROJECT AREAS (366 SUITE) 1 E-500 4 FCI 72C EXISTING 3 AMP CIRCUIT. SYSTEM ON THIRD FLOOR WHERE READINGS WERE TAKEN AS ONLY 2 AMPS OF LOAD ON AN THE NEW FIRE ALARM DEVICE LOAD IS APPROXIMATELY .32 AMPS TOTAL. CONNECT TO EXISTING IT IS ACCEPTABLE TO EXTEND OFF OF EXISTING HARDWIRED ZONE OF FIRE ALARM SYSTEM. NOT USED. FIRE ALARM HARDWIRED CIRCUIT EXTENDING BACK TO MAIN FIRE ALARM CONTROL PANEL.3/12/2015 2:03:59 PMJAD REVISIONS no.date by description ALL RIGHTS RESERVED © ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS 387 East Main Street Rochester, NY 14604-2107 Voice: 585.232.8300 Fax: 585.232.9221 w w w . s w b r . c o m DRAWING TITLE proj. no. checked proj. mgr. drawn by STATUS: DRAWING NO. PROJECT: CLIENT: ISSUE DATE: ROCHESTER, N E W Y O R K CONSULTANT: ENGINEERING P.C. MECHANICAL/ELECTRICAL ENGINEERING CONSULTANTS ROCHESTER, NEW YORK 14604 (585) 288-5590 FAX: (585) 288-0233 M/E Project: 150166 150 NORTH CHESTNUT STREET ROCHESTER BUFFALO SYRACUSE CAPITAL DISTRICT ROOM RENOVATIONS UPGRADES & MINOR OF '49 CLASSROOM A/V HOLLISTER HALL CLASS ENGINEERING COLLEGE OF CORNELL UNIVERSITY - 15365.00 10/22/2015 DOCUMENTS 100% CONSTRUCTION CTV MRG E-501 A DETAIL NOTES: ACCESS TO CARD 120VAC TO CARD ACCESS TO CARD ACCESS SCALE: NONE A. DEVICES AS INDICATED ON PLANS. PROVIDE ACCESS CONTROL GENERAL NOTES: CEILING LINE •" CONDUIT DETAIL NOTES: SCALE: NONE CR A DS VERIFY DIM.INFORMATION ON DETAIL #1 THIS DRAWING. PLANS FOR ALL REQUIRED COMPONENTS FOR DOOR AND ADDITIONAL AND GENERIC DOOR HARDWARE REQUIREMENTS. REFER TO FLOOR DETAIL IS TO BE USED FOR MOUNTING HEIGHTS, CONDUIT SIZES SIDE OF DOOR COVER ON SECURE 10"X 10"X 2.5" BOX WITH SCALE: NONE CARD ACCESS RISER DIAGRAM GENERAL NOTES: A. B. C. D. E. G. DRAWING NOTES: 1 F. J 2 J EED PT FARDC CR PS JEED RTEDC DOOR ELEVATION TYPICAL WIRING DIAGRAM H. (ON NON-SECURE SIDE) CARD READER DRI BY ELECTRICAL CONTRACTOR. DIVISION 8 CONTRACTOR. WIRING TO CARD READER CARD READER FURNISHED BY AND INSTALLED BY THIRD FLOOR FOURTH FLOOR SECOND FLOOR FIRST FLOOR 3 1 2 ELECTRIC RM 361 BCP (E) 366A DOOR 366B DOOR 3L3-9 IN RM 161 TO ACCESS PANEL HEIGHT REQUIREMENTS GENERIC DETAILSHOWING MOUNTING DIAGRAMS CARD READER DRI 3 6-#18ga FOR NON-CARD READER DOOR 12-#18ga FOR CARD READER DOOR ELECTRIC RM 100UB ELECTRIC RM 200JA 3 2 2 1 ELECTRIC RM B00JB BASEMENT 4 4 ELECTRIC ROOMS. IS LOCATED IN ELECTRIC ROOM B00JB. PROVIDE VERTICAL CONDUIT CONNECTION VIA STACKED PROVIDE CONNECTION FROM FIRE ALARM RELEASE TO FIRE ALARM PANEL. FIRE ALARM PANEL FIRESTOPPING AT EACH LOCATION. CONTROL VIA ELECTRIC ROOMS. COORDINATE PENETRATION LOCATIONS IN FIELD. PROVIDE PROVIDE 1" CONDUIT AND WIRING (2 PAIR 18 GUAGE COPPER)DOWN TO CARD ACCESS HEAD END REFER TO DOOR HARDWARE SEQUENCE OF OPERATION FOR ADDITIONAL REQUIREMENTS. PROVIDE CONDUIT AND CONTROL WIRING TO HEAD END ACCESS CONTROL EQUIPMENT. PROVIDE PS AND DRI WITHIN CABINET MODEL LNL-OLS120ACTX. 3L3-9. PROVIDE 20A-1P CIRCUIT BREAKER. UTILIZE (2) #12AWG, (1) #12EG, 3/4" CONDUIT. PROVIDE DEDICATED 20A-1P 120VAC BRANCH CIRCUIT TO POWER SUPPLY. UTILIZE PANELBOARD (E)FACP PT AND SMART CARDS AND LOCK SET AS PER HARDWARE SCHEDULE. (1) ENCLOSURE CABINETS FOR BATTERIES BAS-CTX, (4) WIRE & READER - COMBINATION PROXIMITY (2) POWER SUPPLIES[(1)12V 4 AMP POWER, (1)24V 4 AMP POWER], (3) BATTERIES - 12V 7 AMP POWER, THE CARD READER SYSTEM SHALL INCLUDE AT A MINIMUM (1) 1320 DUAL DOOR CONTROLLERS, REFER TO DETAILS THIS SHEET FOR DOOR ELEVATION DETAILS AND ADDITIONAL REQUIREMENTS. AS REQUIRED BY THE SYSTEM MANUFACTURER. NUMBER OF POWER SUPPLIES SHOWN IS DIAGRAMMATIC. PROVIDE QUANTITY OF POWER SUPPLIES LOCATIONS. COORDINATE EXACT LOCATIONS IN FIELD WITH ENGINEER. A COMPLETE, FUNCTIONAL SYSTEM. RIM'S SHALL BE INSTALLED IN CONCEALED YET ACCESSIBLE OR THE FLOOR PLANS. PROVIDE QUANTITY AND TYPE (DUAL) OF RIM'S AS REQUIRED FOR DOOR CONTROLLERS (DUAL READER INTERFACE MODULE-DRI) ARE NOT SHOWN ON THE RISER DIAGRAM PROVIDE ALL CABLING PER THE SYSTEM MANUFACTURER REQUIREMENTS. ALL DEVICES. ON THE RISER DIAGRAM. FLOOR PLANS DO NOT SHOW EXACT QUANTITIES AND LOCATIONS OF SYSTEM AS REQUIRED BY SYSTEM MANUFACTURER. ALL DEVICES MAY NOT BE INDICATED INDICATE ROUTING OR QUANTITIES OF WIRES REQUIRED. PROVIDE WIRING FOR A COMPLETE WIRING INDICATED ON THE RISER DIAGRAM IS DIAGRAMMATIC ONLY, AND IS NOT INTENDED TO ETC. AS REQUIRED BY THIS CONTRACT FOR A COMPLETE SYSTEM. PRIOR TO SUBMITTALS. PROVIDE ALL DEVICES, WIRING, CONDUIT, SOFTWARE, PROGRAMMING, SCHEDULES. COORDINATE ALL DOOR OPERATIONS WITH CONTRACT DOCUMENTS AND ARCHITECT 281300, FINISH HARDWARE SPECIFICATION SECTION, AND THE ARCHITECTURAL DOOR HARDWARE CONTROL SYSTEM AS INDICATED BY THESE ELECTRICAL DRAWINGS, SPECIFICATION SECTION IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO PROVIDE A FULLY FUNCTIONAL ACCESS DASHED LINE WEIGHT INDICATES DEVICE PROVIDED BY OTHERS. RTE3/12/2015 2:03:59 PMJAD REVISIONS no.date by description ALL RIGHTS RESERVED © ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS 387 East Main Street Rochester, NY 14604-2107 Voice: 585.232.8300 Fax: 585.232.9221 w w w . s w b r . c o m DRAWING TITLE proj. no. checked proj. mgr. drawn by STATUS: DRAWING NO. PROJECT: CLIENT: ISSUE DATE: ROCHESTER, N E W Y O R K CONSULTANT: ENGINEERING P.C. MECHANICAL/ELECTRICAL ENGINEERING CONSULTANTS ROCHESTER, NEW YORK 14604 (585) 288-5590 FAX: (585) 288-0233 M/E Project: 150166 150 NORTH CHESTNUT STREET ROCHESTER BUFFALO SYRACUSE CAPITAL DISTRICT ROOM RENOVATIONS UPGRADES & MINOR OF '49 CLASSROOM A/V HOLLISTER HALL CLASS ENGINEERING COLLEGE OF CORNELL UNIVERSITY - 15365.00 10/22/2015 DOCUMENTS 100% CONSTRUCTION CTV MRG E-600 SCHEDULES ELECTRICAL 5(2W + GND) CLS-C6 120 VAC 4-WIRE 0-10V DIMMING NORMAL 120-277V 120 VAC NORMAL 120-277V 120 VAC NORMAL 120-277V CLS-EXP-DIMFLV 120 VAC 4-WIRE 0-10V DIMMING NORMAL 120-277V 4-WIRE 0-10V DIMMING NA CLS-EXP-DIMFLV 120 VAC 4-WIRE 0-10V DIMMING NORMAL 120-277V 4-WIRE 0-10V DIMMING NA CLS-EXP-DIMFLV 120 VAC 4-WIRE 0-10V DIMMING NORMAL 120-277V 4-WIRE 0-10V DIMMING NA 2-8 BUTTONS 2-8 BUTTONS 1.08 WATTS 1.08 WATTS CRESNET-P-TLPLENUM PN: CRESNET-NP-TLNON-PLENUM PN: W/SHIELD (BY E.C.) (1) TWISTED PAIR 22AWG (1) PAIR #18AWG, "CRESNET" CABLE: 1 (BY E.C.) (1) SHIELD (1) TWISTED PAIR 18AWG CABLE: 3 COORDINATED WITH ARCHITECT. ALL PHYSICAL DEVICE LOCATIONS TO BE POWER SUPPLIES CAN BE ADDED TO INCREASE LENGTH OF HOME RUNS. USE THE CALCULATOR SHOWN TO DETERMINE MAXIMUM WIRE RUN LENGTH. INSTALLATION NEEDS. EACH HOME RUN NOT TO EXCEED 20 CRESNET DEVICES. POWER DRAW. DAISY CHAIN AND OR STAR TOPOLOGIES ARE PERMITTED TO SUIT LENGTH OF CRESNET WIRING RUNS ARE LIMITED TO # OF DEVICES AND CRESNET CAT5E ETHERNET CABLE: 4 (BY E.C.) DB-9 CONNECTOR (1) SHIELD (1) TWISTED PAIR 22AWG RS-232 CABLE: 2 WIRE TYPES: REQUIREMENTS TO MEET LOAD SUITABLE GAUGE WIRE 5 MAXIMUM CABLE LENGTH EQUATION: L < 40,000 R x P P = Cresnet Power usage of entire run 1.6 Ohms for Cresnet High Power Certified wire R = 6 Ohms for Cresnet Certified wire or L = Maximum Length of run in feet from power sourceWhere SEE CRESNET WIRING INSTRUCTIONS, DWG. 02.3, FOR FULL DETAILS. ALL WIRE RUNS ARE TYPE 1, CRESNET, UNLESS OTHERWISE NOTED. DISTANT END OF THE CONTROL CABLE RUN. VOLTAGE WHEN MEASURED AT THE MOST "MIN VOLTS" IS THE MINIMUM ALLOWABLE ** DISCUSSING WITH THE PROJECT ENGINEER. 3.5 TIMES. DO NOT EXCEED 1000' WITHOUT INCREASES THIS DISTANCE BY APPROXIMATELY USING CRESNET "HIGH-POWER" CABLE MAY NOT BE EXCEEDED WITH CRESNET CABLE. "MAX LENGTH" IS THE LENGTH, IN FEET, THAT *(NOT ALL TYPES ARE USED ON ALL PROJECTS) SEE PLANS SEE PLANS SEE PLANS SEE PLANS SEE PLANS CS2 CS3 ABOVE FINISHED CEILING CS1 SCALE: 1/4"=1'-0" CLS-EXP-DIMFLV CLS-EXP-DIM-U CLS-EXP-DIM-U ELVD ELVD ZONE b ZONE a ZONE c ZONE e ZONE d ZONE f CLS-C6 (I-LUX) CONTROLLER ID: BACK BOX:4-GANG 3.5"DEEP STD LOCATION: DWG: FROM "LOCAL DEVICES" CONN. 1 H N FEED: NORMAL VOLTAGE: 120V CONTROL: OUTPUT: EXPANSION MODULE iLUX CLS-EXP-DIM H N FEED: VOLTAGE: DWG.#: CLS-EXP-DIM LOAD LOAD TYPE: H N CONTROL: OUTPUT: EXPANSION MODULE iLUX CLS-EXP-DIM H N FEED: VOLTAGE: DWG.#: CLS-EXP-DIM LOAD LOAD TYPE: H N CONTROL: OUTPUT: EXPANSION MODULE iLUX CLS-EXP-DIM H N FEED: VOLTAGE: DWG.#: CLS-EXP-DIM LOAD LOAD TYPE: H N CONTROL: OUTPUT: EXPANSION MODULE iLUX CLS-EXP-DIMFLV H N FEED: VOLTAGE: DWG.#: CLS-EXP-DIMFLV LOAD LOAD TYPE: BALLAST: SW H - N + CONTROL: OUTPUT: EXPANSION MODULE iLUX CLS-EXP-DIMFLV H N FEED: VOLTAGE: DWG.#: CLS-EXP-DIMFLV LOAD LOAD TYPE: BALLAST: SW H - N + CONTROL: OUTPUT: EXPANSION MODULE iLUX CLS-EXP-DIMFLV H N FEED: VOLTAGE: DWG.#: CLS-EXP-DIMFLV LOAD LOAD TYPE: BALLAST: SW H - N + DWG. #: C2N-CBD-P LOCATION: STATION ID: C2N-CBD-P DWG. #: C2N-CBD-P LOCATION: STATION ID: C2N-CBD-P STATION ID: LOCATION: DWG. #: GLS-ODT-C-CN GLS-ODT-C-CN STATION ID: LOCATION: DWG. #: GLS-ODT-C-CN GLS-ODT-C-CN DWG. #: C2N-SDC LOCATION: STATION ID: C2N-SDC FEED: 120VAC TO DEVICES CRESTRON C2N-SDC DOWN UP DOWN UP NET NET PWR NET SETUP 24 Y Z G 24 Y Z G 1 LIGHTING CONTROL DIAGRAM STATION ID: LOCATION: DWG. #: GLS-ODT-C-CN GLS-ODT-C-CN SCHEDULELUMINAIRE TYPE DESCRIPTION AND SIZEFIXTURE LAMP BALLAST VOLTAGE/ RDIFFUSE REFLECTOR/ NUMBER MODEL AND MANUFACTURERAPPROVED NOTES L1 3.75" BE SHALL DEPTHFIXTURE MAXIMUM DIMMABLE. TROFFER, LED RECESSED1'X4'LED DRIVER 0-10V120V LU14A-3542-G1-120-1D-WPINNACLE:1,2 EM TEST REMOTE WITH PACK BATTERYEMERGENCY LED 120V DLMW-SD MODEL:SIMKAR 1 X1 TEST REMOTE AND BATTERY INTEGRAL WITH SIGN EXITLED LED 120V SLEDBRW-SD MODEL:SIMKAR 1 T1 TRACKLED 120V LT-X-X MODEL: LIGHTINGCONTECH 1 L2 HEAD TRACK LED MINIDIMMABLE 14WLED 120V DIFFUSER FLOOD CTL8051-H-F-35-D-X-X MODEL: LIGHTINGCONTECH 1 L3 4" X 3" WASH, WALL LINEARRECESSED LED 120V EX3-WW-N-35-8-AC48G1-120-1D-WPINNACLE: NOTES:GENERAL RCP. ARCHITECTURAL WITH TYPES MOUNTING COORDINATEA. NOTES:REFERENCE COLOR. FOR ARCHITECT WITH COORDINATE1. SIZE. GRID FOR RCP ARCHITECTURAL WITH COORDINATE2. GLILUX-DKP-DKP-3OS-RS232-AV A. GENERAL NOTES: VERIFY THE MODULES ARE COMPATIBLE WITH FIXTURE SUPPLIED. VERIFY ALL DIMMING MODULES WITH SUBMITTED LIGHTING PACKAGE. CLS-C6 (I-LUX) CONTROLLER ID: BACK BOX:4-GANG 3.5"DEEP STD LOCATION: DWG: FROM "LOCAL DEVICES" CONN. 1 H N FEED: NORMAL VOLTAGE: 120V 1 RACK IN RM 361 TO AV EQUIPMENT CRESNET INTERFACE3/12/2015 2:03:59 PMJAD REVISIONS no.date by description ALL RIGHTS RESERVED © ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS 387 East Main Street Rochester, NY 14604-2107 Voice: 585.232.8300 Fax: 585.232.9221 w w w . s w b r . c o m DRAWING TITLE proj. no. checked proj. mgr. drawn by STATUS: DRAWING NO. PROJECT: CLIENT: ISSUE DATE: ROCHESTER, N E W Y O R K CONSULTANT: ENGINEERING P.C. MECHANICAL/ELECTRICAL ENGINEERING CONSULTANTS ROCHESTER, NEW YORK 14604 (585) 288-5590 FAX: (585) 288-0233 M/E Project: 150166 150 NORTH CHESTNUT STREET ROCHESTER BUFFALO SYRACUSE CAPITAL DISTRICT ROOM RENOVATIONS UPGRADES & MINOR OF '49 CLASSROOM A/V HOLLISTER HALL CLASS ENGINEERING COLLEGE OF CORNELL UNIVERSITY - 15365.00 10/22/2015 DOCUMENTS 100% CONSTRUCTION CTV MRG E-601 SCHEDULE AV CABLE PULLING A. GENERAL NOTES: DETAILED INFORMATION ON PULL LOCATIONS. TO AV SOLUTIONS DRAWINGS PROVIDED AS REFERENCE TO THIS SET FOR MORE CABLE PULL SCHDULES. CABLES SHALL BE FURNISHED BY AV SOLUTIONS. REFER ELECTRICAL CONTRACTOR SHALL PULL ALL CABLES NOTED IN THE ADJACENT 3/12/2015 2:03:59 PMJAD REVISIONS no.date by description ALL RIGHTS RESERVED © ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS 387 East Main Street Rochester, NY 14604-2107 Voice: 585.232.8300 Fax: 585.232.9221 w w w . s w b r . c o m DRAWING TITLE proj. no. checked proj. mgr. drawn by STATUS: DRAWING NO. PROJECT: CLIENT: ISSUE DATE: ROCHESTER, N E W Y O R K CONSULTANT: ENGINEERING P.C. MECHANICAL/ELECTRICAL ENGINEERING CONSULTANTS ROCHESTER, NEW YORK 14604 (585) 288-5590 FAX: (585) 288-0233 M/E Project: 150166 150 NORTH CHESTNUT STREET ROCHESTER BUFFALO SYRACUSE CAPITAL DISTRICT ROOM RENOVATIONS UPGRADES & MINOR OF '49 CLASSROOM A/V HOLLISTER HALL CLASS ENGINEERING COLLEGE OF CORNELL UNIVERSITY - 15365.00 10/22/2015 DOCUMENTS 100% CONSTRUCTION ELECTRICAL & TELECOM SYMBOLS WALL MOUNTED CEILING MOUNTED FLOOR BOX MOUNTED DESCRIPTION AC DUPLEX OUTLET AC QUAD OUTLET NETWORK DATA JACK TELEPHONE JACK NETWORK DATA/TELEPHONE COMBO JACK CABLE TELEVISION JACK JUNCTION BOX HARD WIRED POWER TO LOW VOLTAGE CONTROLLER AUDIO VISUAL SYMBOLS SPEAKER (CEILING MOUNTED) SPEAKER (WALL MOUNTED) MICROPHONE (CEILING MOUNTED) ARCHITECTURAL SYMBOLS DETAIL INDICATOR ELEVATION INDICATOR KEYNOTE E1 AV201 D1 AV501 01 INDEX OF DRAWINGS DRAWING #DRAWING NAME AV-001 COVER PAGE: GENERAL NOTES, LEGEND & RESPONSIBILITY CHART AV-101 FLOOR PLAN - EQUIPMENT LOCATIONS AV-102 FLOOR PLAN - ELECTRICAL & TELECOM AV-104 REFLECTED CEILING PLAN - EQUIPMENT LOCATIONS AV-105 REFLECTED CEILING PLAN - ELECTRICAL & TELECOM AV-701 VIDEO SIGNAL SINGLE LINE DIAGRAM AV-702 AUDIO SIGNAL SINGLE LINE DIAGRAM AV-703 CONTROL & DATA SIGNAL SINGLE LINE DIAGRAM RESPONSIBILITY CHART PROVIDED BY:INSTALLED BY:A.V.C.G.C.FURN. INS.CLIENTOTHEREXISTINGN/AA.V.C.G.C.FURN. INS.CLIENTOTHEREXISTINGN/ACEILING MOUNTED EQUIPMENT PROJECTION SCREEN PROJECTION SCREEN CEILING MOUNT STRUCTURE PROJECTION SCREEN LOW VOLTAGE SWITCH PROJECTOR PROJECTOR CEILING TILE STORAGE BOX PROJECTOR MOUNT FLAT PANEL DISPLAY (CONFIDENCE MONITOR) FLAT PANEL CEILING TILE STORAGE BOX FLAT PANEL DISPLAY CEILING MOUNT PLATE/STRUCTURE FLAT PANEL DISPLAY MOUNT CEILING SPEAKERS P/T/Z CAMERAS (FRONT AND REAR OF ROOM) P/T/Z CAMERA MOUNT/SAFETY BRACKET (REAR OF ROOM) P/T/Z CAMERA CEILING (SOFFIT) BLOCKING (FRONT OF ROOM) P/T/Z CAMERA CEILING MOUNTS (FRONT OF ROOM) WIRELESS MIC ANTENNAS WALL MOUNTED EQUIPMENT FLAT PANEL DISPLAYS FLAT PANEL DISPLAYS WALL MOUNT BLOCKING FLAT PANEL DISPLAYS RECESSED WALL CUTOUTS FLAT PANEL DISPLAYS MOUNT FLAT PANEL DISPLAYS WALL BOXES WALL SPEAKERS WALL SPEAKERS MOUNT WALL SPEAKERS MOUNT BLOCKING ASSISTIVE LISTENING IR EMITTER FLOOR EQUIPMENT FLOOR BOXES FLOOR BOXES AV INPUT PLATES TABLE EQUIPMENT TABLE BOX (INSTRUCTOR'S TABLE) TABLE BOX AV INPUT PLATE (INSTRUCTOR'S TABLE) TABLE MICROPHONES (STUDENT TABLES) TABLE MICROPHONE CABLE ACCESS TABLE PENETRATIONS RACK EQUIPMENT EQUIPMENT RACK EQUIPMENT RACK ROOM WALL FAN RACK AV EQUIPMENT VTC CODEC MANAGED NETWORK SWITCH LECTERN EQUIPMENT LECTERN DESKTOP COMPUTER LOCAL MONITOR LOCAL MONITOR MOUNT GOOSENECK MICROPHONE DOCUMENT CAMERA CABLES LOW VOLTAGE AV CABLES & CONNECTORS ELECTRICAL & CABLE PATH AC POWER OUTLETS PROJECTION SCREEN HARD WIRED POWER CONNECTION NETWORK DATA JACKS DATA & TELEPHONE NETWORK INFRASTRUCTURE & SERVICE BACK BOXES/JUNCTION BOXES/LOW VOLTAGE CUT-IN RINGS CEILING MOUNTED J-HOOKS CONDUITS & PULL STRINGS PROGRAMMING AV CONTROL SYSTEM PROGRAMMING DSP PROGRAMMING LIGHTING SYSTEM PROGRAMMING LIGHTING LIGHTING DIMMING SYSTEM LIGHTING DIMMING LOW VOLTAGE CONTROLLER TRACK LIGHTING FIXTURES ARCHITECTURAL & FURNITURE MILLWORK/TABLE PENETRATIONS & MODIFICATIONS FLOOR PENETRATIONS & MODIFICATIONS CEILING GRID/TILE MODIFICATIONS VENTILATION ABBREVIATIONS AC ALTERNATING CURRENT LAN LOCAL AREA NETWORK AFC ABOVE FINISHED CEILING LV LOW VOLTAGE AFF ABOVE FINISHED FLOOR LVC LOW VOLTAGE CONTROLLER ALT ALTERNATIVE MFR MANUFACTURER ANT ANTENNA MIC MICROPHONE APX APPROXIMATE MISC MISCELLANEOUS ASC ABOVE SUSPENDED CEILING MWK MILLWORK AUD AUDIO NIC NOT IN CONTRACT AVC AUDIO VISUAL CONTRACTOR NTS NOT TO SCALE BB BLACKBOARD OC ON-CENTER C CEILING OFE OWNER FURNISHED EQUIPMENT CB CEILING BOX PROJ PROJECTOR CATV CABLE TELEVISION R RIGHT DB DECIBEL RACK EQUIPMENT RACK DC DIRECT CURRENT RCP REFLECTED CEILING PLAN DIAM DIAMETER REC RECESSED DIM DIMENSION REF REFERENCE DP DEPTH REV REVISION DTL DETAIL RF RADIO FREQUENCY EC ELECTRICAL CONTRACTOR RX RECEIVE EDID EXTENDED DISPLAY ID DATA S SURFACE EL ELEVATION SCH SCHEDULE ELEC ELECTRIC SCRN PROJECTION SCREEN EQ EQUAL SEC SECTION EXIST EXISTING SPEC SPECIFICATION FB FLOOR BOX SPKR SPEAKER FL FLOOR SW SWITCH FURN INS FURNITURE INSTALLERS TBD TO BE DETERMINED FUT FUTURE TD THROW DISTANCE GC GENERAL CONTRACTOR TX TRANSMIT HV HIGH VOLTAGE TYP TYPICAL HVAC HEATING & COOLING SYSTEMS VIF VERIFY IN FIELD IR INFRARED VOL VOLUME IWE INCLUDED WITH EQUIPMENT W WALL J JUNCTION BOX WB WALL BOX KO KNOCK OUT WHB WHITEBOARD L LEFT WHIP ELECTRICAL FIXTURE WHIP CONNECTORS 1/4"B 1/4" TIP-RING-SLEEVE BALANCED PHNX PHOENIX (CAPTIVE SCREW) 1/4"U 1/4" TIP-SLEEVE UNBALANCED RCA RCA 3.5MM 3.5MM STEREO AUDIO RJ45 UNSHIELDED RJ45 DB9 9-PIN DSUB SERIAL SRJ45 SHIELDED RJ45 DP DISPLAY PORT TB THUNDERBOLT DVI-A DVI DIGITAL TERM TERMINAL BLOCK DVI-D DVI DIGITAL USB-A USB STANDARD TYPE A FCON F-TYPE COAX USB-B USB STANDARD TYPE B HDMI HDMI USB-C USB STANDARD TYPE C IEC IEC POWER VGA 15-PIN DSUB VGA IR INFRARED EMITTER VISCA SONY VISCA 8-PIN MINI-DIN MDP MINI DISPLAY PORT XLR XLR GENERAL NOTES GENERAL NOTES 1.ALL SIZE, DIMENSION AND LOCATION INFORMATION MUST BE VERIFIED ON ARCHITECTURAL DRAWINGS, IF VALUES CONFLICT, ARCHITECTURAL DRAWINGS TAKE PRECEDENCE. 2.ALL BACK BOX AND OUTLET MEASUREMENTS ARE DRAWN TO VERTICAL CENTER, UNLESS OTHERWISE NOTED. 3.MOTORIZED PROJECTION SCREENS WILL BE PROVIDED BY A.V.C AND INSTALLED BY G.C. UNLESS OTHERWISE NOTED. SCREEN LOW VOLTAGE CONTROLLER WILL BE INSTALLED BY E.C. AND MUST BE MOUNTED ABOVE FINISHED CEILING IN ACCESSIBLE LOCATION. 4.CONSTRUCTION WORK SHOWN IN THESE DRAWINGS IS THE RESPONSIBILITY OF THE G.C. UNLESS OTHERWISE NOTED. 5.NOT ALL SYMBOLS, ABBREVIATIONS AND CONNECTORS DESCRIBED ON THIS LEGEND PAGE APPEAR IN THESE DRAWINGS. 6.QUANTITIES SHOWN ON AV DETAIL AND AV SCHEDULE DRAWINGS SHALL BE CONFIRMED BY EACH DISCIPLINE. DISCREPANCIES SHOULD BE REFERRED TO THE ARCHITECT. ELECTRICAL & TELECOM NOTES 1.ALL CABLE PATH, CIRCUIT, ROUTING AND LOCATION INFORMATION MUST BE VERIFIED ON ELECTRICAL DRAWINGS. IF VALUES CONFLICT, ELECTRICAL DRAWINGS TAKE PRECEDENCE. 2.ALL ELECTRICAL WORK SHALL ABIDE BY NATIONAL AND LOCAL ELECTRICAL CODE. IF CODES CONFLICT, THE STRICTER OF THE TWO SHALL BE FOLLOWED. 3.ALL ELECTRICAL, NETWORK DATA AND TELEPHONE EQUIPMENT SHOWN IN THESE DRAWINGS WILL BE PROVIDED AND INSTALLED BY THE E.C., AND/OR TELECOM CONTRACTOR, UNLESS OTHERWISE NOTED. 4.E.C. SHALL PROVIDE AND INSTALL ALL CONDUIT, PULL BOXES, JUNCTION BOXES, LOW VOLTAGE CUT-IN RINGS, FLOOR BOXES, PLATES, PANELS, ENCLOSURES, POWER CIRCUITS, POWER CABLE AND POWER CONNECTIONS, UNLESS OTHERWISE NOTED. CUSTOM AV PANELS SHALL BE PROVIDED AND INSTALLED BY THE A.V.C., UNLESS OTHERWISE NOTED. 5.AC OUTLETS AND DATA/TEL JACKS SHOWN ON THESE DRAWINGS ARE FOR AV PURPOSES. REFER TO ELECTRICAL DRAWINGS FOR OTHER AC AND TELECOM NEEDS. 6.VERIFY FLOOR BOX LOCATION AND CONTENTS WITH ARCHITECT PRIOR TO INSTALLATION. 7.ALL CIRCUITS POWERING AUDIO VISUAL EQUIPMENT SHALL BE DERIVED FROM THE SAME ELECTRICAL PHASE, BE DEDICATED STRICTLY TO AV DEVICES, HAVE ISOLATED GROUNDS TERMINATING AT A SINGLE POINT IN THE ASSOCIATED SUBPANEL, AND BE PROTECTED BY 20 AMP BREAKERS PER CIRCUIT, UNLESS OTHERWISE NOTED. 8.HIGH VOLTAGE CIRCUITS POWERING AUDIO VISUAL EQUIPMENT SHALL NOT BE RUN IN CLOSE PROXIMITY TO OR SHARE CIRCUITS POWERING MOTORIZED EQUIPMENT, LIGHTING SYSTEM DIMMERS OR ANY OTHER INDUCTIVE ELECTRICAL LOADS. 9.ALL LOW VOLTAGE CABLES EXPOSED IN PLENUM SPACES MUST BE PLENUM RATED CABLE. 10.CONDUIT RUNS TO BE APPROVED ON SITE BY THE AUDIO VISUAL CONTRACTOR. 11.CONDUIT PULL BOXES SHALL BE PLACED AFTER 180 DEGREES OF BENDS AND/OR EVERY 100 FEET. 12.CONDUIT MATERIAL SHALL BE RIGID OR EMT STEEL CONDUIT (NOT FLEXIBLE, PVC OR ALUMINUM), ENDS SHALL BE FITTED WITH INSULATED BUSHINGS AND PULL STRING LEFT IN ALL CONDUIT. 13.CONDUIT CONTAINING AUDIO VISUAL CABLING SHALL NOT CONTAIN POWER OR DATA CABLING. AV SIGNAL CONDUIT SHALL BE SEPARATED FROM CONDUIT CONTAINING POWER CABLING BY AT LEAST 12". POWER CONDUIT MUST CROSS AV SIGNAL CONDUIT AT 90 DEGREE ANGLES. 14.BEND RADIUS FOR CONDUIT SIZED 2" OR LESS SHALL BE NO LESS THAN 6 TIMES THE INTERNAL DIAMETER. CONDUIT SIZED LARGER THAN 2" SHALL HAVE A BEND RADIUS NO LESS THAN 10 TIMES THE INTERNAL DIAMETER. AUDIO VISUAL INSTALLATION NOTES 1.ALL AUDIO VISUAL EQUIPMENT, CABLING, DEVICE MOUNTING AND TERMINATIONS SHOWN IN THESE DRAWINGS WILL BE PROVIDED AND INSTALLED BY THE AUDIO VISUAL CONTRACTOR, UNLESS OTHERWISE NOTED. 2.ALL LOW VOLTAGE CABLES EXPOSED IN PLENUM SPACES MUST BE PLENUM RATED CABLE. 3.ALL CABLES SHALL BE LABELED ON EACH END WITH WIRE ID #, AND SIGNAL SOURCE/DESTINATION. LAMINATED, VINYL CABLE LABELS SHALL BE USED. 4.ALL CONNECTION PLATE JACKS SHALL BE LABELED WITH ENGRAVING OR PRINTED LABELS. 5.RJ45 CONNECTORS SHALL BE TERMINATED USING THE T568B WIRING STANDARD. 6.VELCRO STRIPS SHALL BE USED TO SECURE CATX CABLES, NOT PLASTIC ZIP TIES. 7.POWER AND AV SIGNAL CABLES SHALL BE ROUTED ON SEPARATE SIDES OF THE EQUIPMENT RACK. RACK CABLING SHALL INCLUDE SERVICE LOOPS FOR EQUIPMENT REMOVAL AND SERVICING. 8.ALL AV DEVICES INSTALLED ON WALLS OR CEILING SHALL BE SECURED TO STRUCTURAL BLOCKING OR HARD DECK CEILING WITH SAFETY TETHERS. TVTVTV JJJ LV S S M AV-001 THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. $//5,*+765(6(59('‹ 29 JANIVAR DRIVE ITHACA, NY 14850 607-592-5370 WWW.TOMEIAV.COM MIKE@TOMEIAV.COM 15365.00 Checker AV COVER PAGE SDF TOMEI 90% CONSTRUCTION DOCUMENTS CORNELL UNIVERSITY - COLLEGE OF ENGINEERING HOLLISTER HALL CLASS OF '49 CLASSROOM A/V UPGRADES & MINOR ROOM RENOVATIONS 08/21/2015 REVISIONS no.date by description RECESSED IN WALL: 80" FLAT PANEL DISPLAY FLAT PANEL DISPLAY MOUNT FLAT PANEL DISPLAY WALL BOX PROGRAM SPEAKER PODIUM AV EQUIPMENT RACK ABOVE DOOR: WALL COOLING FAN SCREEN DROP S RECESSED IN WALL: 80" FLAT PANEL DISPLAY FLAT PANEL DISPLAY MOUNT FLAT PANEL DISPLAY WALL BOX PROGRAM SPEAKER ASSISTIVE LISTENING SYSTEM IR EMITTER S FLUSH IN TABLE: CABLE CUBBYTABLE MIC (TYP. OF 24) AV-101 THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. $//5,*+765(6(59('‹ TOMEI AV CONSULTING LLC 29 JANIVAR DRIVE ITHACA, NY 14850 607-592-5370 WWW.TOMEIAV.COM MIKE@TOMEIAV.COM 15365.00 Checker FLOOR PLAN - AV EQUIPMENT LOCATIONS SDF MCT 90% CONSTRUCTION DOCUMENTS CORNELL UNIVERSITY - COLLEGE OF ENGINEERING HOLLISTER HALL CLASS OF '49 CLASSROOM A/V UPGRADES & MINOR ROOM RENOVATIONS 08/21/2015 F1 FLOOR PLAN - AV EQUIPMENT LOCATIONS SCALE: 1/4" = 1'-0" REVISIONS no.date by description J004 1-GANG 48" AFF SCREEN SWITCH FB FB001 FLOOR BOX 120V AC DUPLEX OUTLET (3) DATA JACKS AV CONNECTOR PLATES: (1) XLR(F) (5) SHIELDED RJ-45 (3) UNSHIELDED RJ-45 J J FB FB002 FLOOR BOX 120V AC DUPLEX OUTLET (3) DATA JACKS AV CONNECTOR PLATES: (2) SHIELDED RJ-45 (2) UNSHIELDED RJ-45 J J005 1-GANG 105" AFF P/T/Z CAMERA J J008 1-GANG 105" AFF P/T/Z CAMERA J J009 1-GANG 120V AC DUPLEX OUTLET FLAT PANEL DISPLAY WALL BOX J006 1-GANG 120V AC DUPLEX OUTLET FLAT PANEL DISPLAY WALL BOX POWER OUTLET ??" AFF WALL COOLING FAN JJ J001-J003 (2) 4" WALL BOXES (2) 120V 20A QUAD POWER OUTLETS 18" AFF EQUIPMENT RACK J J 1" HOLE DRILLED IN TABLE UNDER TABLE MIC (TYP. OF 24) S J J010 1-GANG 105" AFF PROGRAM SPEAKER J J011 1-GANG 105" AFF PROGRAM SPEAKER J J007 1-GANG 99" AFF ALS IR EMITTER S CIRCLED TABLE MICS CONFLICT WITH POP-UP POWER MODULE LOCATIONS (TYP. OF 2) SEE ELECTRICAL DRAWINGS FOR MIC CABLE ACCESS FLOOR PENETRATIONS UNDER STUDENT TABLES AV-102 THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. $//5,*+765(6(59('‹ TOMEI AV CONSULTING LLC 29 JANIVAR DRIVE ITHACA, NY 14850 607-592-5370 WWW.TOMEIAV.COM MIKE@TOMEIAV.COM 15365.00 Checker FLOOR PLAN - AV ELECTRICAL & TELECOM SDF MCT 90% CONSTRUCTION DOCUMENTS CORNELL UNIVERSITY - COLLEGE OF ENGINEERING HOLLISTER HALL CLASS OF '49 CLASSROOM A/V UPGRADES & MINOR ROOM RENOVATIONS 08/21/2015 F2 FLOOR PLAN - AV ELECTRICAL & TELECOM SCALE: 1/4" = 1'-0" REVISIONS no.date by description 2 9' - 4"2 9' - 4" 2 9' - 4" 1 10' - 5 3/4" 1 10' - 5 3/4" 3 9' - 2" 3 9' - 2" S S S S S S S S WIRELESS MIC ANTENNA (TYP.OF 2)PROJECTION SCREEN CEILING SPEAKER (TYP.OF 8) CEILING TILE STORAGE BOX/MOUNT PROJECTOR CEILING TILE STORAGE BOX CONFIDENCE MONITOR CONFIDENCE MONITOR MOUNT P/T/Z CAMERA P/T/Z CAMERA (TYP.OF 2) AV-104 THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. $//5,*+765(6(59('‹ TOMEI AV CONSULTING LLC 29 JANIVAR DRIVE ITHACA, NY 14850 607-592-5370 WWW.TOMEIAV.COM MIKE@TOMEIAV.COM 15365.00 Checker RCP - AV EQUIPMENT LOCATIONS SDF MCT 90% CONSTRUCTION DOCUMENTS CORNELL UNIVERSITY - COLLEGE OF ENGINEERING HOLLISTER HALL CLASS OF '49 CLASSROOM A/V UPGRADES & MINOR ROOM RENOVATIONS 08/21/2015 R1 REFLECTED CEILING PLAN - AV EQUIPMENT LOCATIONS SCALE: 1/4" = 1'-0" REVISIONS no.date by description 2 9' - 4"2 9' - 4" 2 9' - 4" 1 10' - 5 3/4" 1 10' - 5 3/4" 3 9' - 2" 3 9' - 2" S S S S S S S S 120V AC DUPLEX OUTLET CEILING TILE STORAGE BOX 120V AC DUPLEX OUTLET CEILING TILE STORAGE BOX LV LVC001 120V AC HARD WIRED TERMINATION PROJECTION SCREEN AV-105 THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. $//5,*+765(6(59('‹ TOMEI AV CONSULTING LLC 29 JANIVAR DRIVE ITHACA, NY 14850 607-592-5370 WWW.TOMEIAV.COM MIKE@TOMEIAV.COM 15365.00 Checker RCP - AV ELECTRICAL & TELECOM SDF MCT 90% CONSTRUCTION DOCUMENTS CORNELL UNIVERSITY - COLLEGE OF ENGINEERING HOLLISTER HALL CLASS OF '49 CLASSROOM A/V UPGRADES & MINOR ROOM RENOVATIONS 08/21/2015 R2 REFLECTED CEILING PLAN - AV ELECTRICAL & TELECOM SCALE: 1/4" = 1'-0" REVISIONS no.date by description FROM USB TRANSMITTER 1 IN USB OUT USB EXTENDER RECEIVER 1 RJ45 USB-A GEFEN EXT-USB2.0-LR USB DVI OUT DESKTOP PC USB-A DVI AUDIO OUT 3.5MM DELL OPTIPLEX 7010 MATRIX SWITCHER INPUT 1 DMC-4K-C SRJ45 CRESTRON DM-MD16X16 TO VC CODEC IN 1 DM IN HDMI OUT DM SCALER/RECEIVER SRJ45 HDMI CRESTRON DM-RMC-4K-SCALER-C HDMI IN PROJECTOR HDMI EPSON G6770WU HDMI IN HDMI OUT DM TRANSMITTER HDMI HDMI AUDIO IN3.5MM CRESTRON DM-TX-201-C DM OUT SRJ45 OUTPUTS 1-2 DMC-4K-CO-HD DM IN DM OUT 1 SRJ45 SRJ45DM OUT 2 DVI IN USB LOCAL ANNOTATION MONITOR DVI USB-B SMART PODIUM SP518-NB TO DESKTOP PC USBUSB-AFROM SMART PODIUM MONITOR IN USB OUT USB EXTENDER RECEIVER 2 RJ45 USB-A GEFEN EXT-USB2.0-LR HDMI OUT DOCUMENT CAMERA HDMI WOLFVISION VZ-8PLUS4 HDMI IN DM OUT DM TRANSMITTER HDMI SRJ45 CRESTRON DM-TX-201-C IN USB OUT USB EXTENDER RECEIVER 3 RJ45 USB-A GEFEN EXT-USB2.0-LR USB HDMI OUTUSB-A HDMI VGA OUT VGA LAPTOP (OFE) HDMI IN DM OUT DM TRANSMITTER HDMI SRJ45 PC (VGA) INVGA CRESTRON DM-TX-401-C MINI DISPLAY PORT OUT MDP AUDIO OUT 3.5MM DISPLAY PORT INDP AUDIO IN LRCA AUDIO IN RRCA SDI OUT P/T/Z CAMERA BNC PANASONIC AW-HE40SW SDI OUT P/T/Z CAMERA BNC PANASONIC AW-HE40SW SDI OUT P/T/Z CAMERA BNC PANASONIC AW-HE40SW HDMI OUT WIRELESS PRESENTATION HDMI CRESTRON AM100 AIRMEDIA HDMI IN 1 HDMI OUT 1 VIDEO CONFERENCE CODEC HDMI HDMI HDMI OUT 2 HDMI CISCO SX80 HDMI IN 2HDMI FROM MATRIX SWITCHER OUT 5 FROM HDMI SCALER 1 INPUT 2 DMC-4K-C SRJ45 DM IN INPUT 3 DMC-4K-C SRJ45 DM IN INPUT 4 DMC-4K-C SRJ45 DM IN INPUT 5 DMC-SDI BNC SDI IN INPUT 8 DMC-4K-HD HDMI HDMI IN INPUT 6 DMC-SDI BNC SDI IN INPUT 7 DMC-SDI BNC SDI IN INPUT 9 DMC-4K-HD HDMI HDMI IN INPUT 10 DMC-4K-HD HDMI HDMI IN DM IN HDMI OUT DM SCALER/RECEIVER SRJ45 HDMI CRESTRON DM-RMC-4K-SCALER-C HDMI IN CONFIDENCE MONITOR HDMI NEC E425 DM IN HDMI OUT DM SCALER/RECEIVER SRJ45 HDMI CRESTRON DM-RMC-4K-SCALER-C HDMI IN FLAT PANEL DISPLAY HDMI SHARP LC-80LE661U DM IN HDMI OUT DM SCALER/RECEIVER SRJ45 HDMI CRESTRON DM-RMC-4K-SCALER-C HDMI IN FLAT PANEL DISPLAY HDMI SHARP LC-80LE661U OUTPUTS 3-4 DMC-4K-CO-HD DM OUT 1 SRJ45 SRJ45DM OUT 2 OUTPUTS 5-6 DMC-HDO HDMI OUT 1 HDMI RCAAUDIO OUT L RCAAUDIO OUT R HDMIHDMI OUT 2 TO DSP 3 IN 4 ON AV-702 TO DSP 3 IN 5 ON AV-702 HDMI IN HDMI OUT HDMI SCALER 1 HDMI HDMI CRESTRON HD-SCALER-HD-E TO VC CODEC IN 2 OUTPUTS 7-8 DMC-HDO HDMI OUT 1 HDMI OUT 2 HDMI HDMI IN HDMI OUT HDMI SCALER 3 HDMI HDMI CRESTRON HD-SCALER-HD-E HDMI IN USB WEB CONFERENCING CODEC HDMI USB-B VADDIO AV BRIDGE CONFERENCE USB 1 PC 1 USB SWITCHER USB-B EXTRON SW4 USB PLUS USB 2 PC 2 USB-B USB 3 PC 3USB-A USB-B USB 4 PC 4 USB IN OUT USB EXTENDER TRANSMITTER 1 USB-B RJ45 GEFEN EXT-USB2.0-LR TO USB RECEIVER 1 FROM USB TRANSMITTER 2 FROM USB TRANSMITTER 3 USB IN OUT USB EXTENDER TRANSMITTER 2 USB-B RJ45 GEFEN EXT-USB2.0-LR TO USB RECEIVER 2 USB IN OUT USB EXTENDER TRANSMITTER 3 USB-B RJ45 GEFEN EXT-USB2.0-LR TO USB RECEIVER 3 USB HDMI OUTUSB-A HDMI VGA OUT VGA LAPTOP (OFE) HDMI IN DM OUT DM TRANSMITTER HDMI SRJ45 PC (VGA) INVGA CRESTRON DM-TX-401-C MINI DISPLAY PORT OUT MDP AUDIO OUT 3.5MM DISPLAY PORT INDP AUDIO IN LRCA AUDIO IN RRCA LECTERN INSTRUCTOR'S TABLE CEILING EQUIPMENT RACK CEILING FRONT WALL INPUT 12 EMPTY INPUT 13 EMPTY INPUT 14 EMPTY INPUT 15 EMPTY INPUT 16 EMPTY OUTPUTS 11-12 EMPTY OUTPUTS 13-14 EMPTY OUTPUTS 15-16 EMPTY INPUT 11 EMPTY OUTPUTS 9-10 EMPTY AV-701 THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. $//5,*+765(6(59('‹ 29 JANIVAR DRIVE ITHACA, NY 14850 607-592-5370 WWW.TOMEIAV.COM MIKE@TOMEIAV.COM 15365.00 Checker VIDEO SIGNAL SINGLE LINE DIAGRAM SDF MCT 90% CONSTRUCTION DOCUMENTS CORNELL UNIVERSITY - COLLEGE OF ENGINEERING HOLLISTER HALL CLASS OF '49 CLASSROOM A/V UPGRADES & MINOR ROOM RENOVATIONS 08/21/2015 REVISIONS no.date by description FROM DSP 1 OUT 4 INPUT 1 OUTPUT 1 AUDIO DSP 1 PHNX BIAMP TESIRA FORTE AVB VI INPUT 2 OUTPUT 2 INPUT 3 OUTPUT 3 INPUT 4 OUTPUT 4 PHNX PHNX PHNX PHNX PHNX PHNX PHNX INPUT 5 OUTPUT 5 PHNX INPUT 6 OUTPUT 6 INPUT 7 OUTPUT 7 INPUT 8 OUTPUT 8 PHNX PHNXPHNX PHNX PHNX INPUT 9 VOIP PHNX INPUT 10 AVB INPUT 11 CONTROL INPUT 12 PHNX PHNX PHNX PHNX PHNX PHNX SHURE MX392/C TABLE MIC LINE IN LINE OUT WEB CONFERENCING CODEC XLR VADDIO AV BRIDGE CONFERENCE XLR INPUT 1 OUTPUT 1 AUDIO DSP 2 BIAMP TESIRA FORTE AVB CI INPUT 2 OUTPUT 2 INPUT 3 OUTPUT 3 INPUT 4 OUTPUT 4 PHNX PHNX PHNX PHNX INPUT 5 OUTPUT 5 INPUT 6 OUTPUT 6 INPUT 7 OUTPUT 7 INPUT 8 OUTPUT 8 PHNX PHNX PHNX PHNX INPUT 9 AVB PHNX INPUT 10 CONTROL INPUT 11 INPUT 12 PHNX PHNXPHNX PHNX PHNX INPUT 1 OUTPUT 1 AUDIO DSP 3 BIAMP TESIRA FORTE AVB CI INPUT 2 OUTPUT 2 INPUT 3 OUTPUT 3 INPUT 4 OUTPUT 4 PHNX PHNX PHNX PHNX INPUT 5 OUTPUT 5 INPUT 6 OUTPUT 6 INPUT 7 OUTPUT 7 INPUT 8 OUTPUT 8 PHNX PHNX PHNX INPUT 9 AVB PHNX INPUT 10 CONTROL INPUT 11 INPUT 12 PHNX SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC TERMSHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC SHURE MX392/C TABLE MIC XLRSHURE MX412/C GOOSENECK MIC OUTPUT 1 WIRELESS MIC RECEIVER XLR SHURE ULXD4D OUTPUT 2 XLR FROM MATRIX SWITCH OUT 5L ON AV-701 FROM MATRIX SWITCH OUT 5R ON AV-701 FROM DSP 1 OUT 5 LINE IN 1 LINE OUT 1 VIDEO CONFERENCE CODEC PHNX CISCO SX80 PHNX TO WEB CONFERENCING CODEC LINE IN TO VIDEO CONFERENCE CODEC LINE IN 1 TO MANAGED SWITCH PORT 3 ON AV-703 CH 1 IN CH 1 70V OUT AMPLIFIER PHNX CRESTRON AMP-3210T CH 2 IN CH 2 8-OHM OUT CH 3 IN CH 3 8-OHM OUT PHNX PHNX PHNX PHNX PHNX IN 70V CEILING SPEAKER TANNOY CVS 6 OUT TERM TERM IN 70V CEILING SPEAKER TANNOY CVS 6 OUT TERM TERM IN 70V CEILING SPEAKER TANNOY CVS 6 OUT TERM TERM IN 70V CEILING SPEAKER TANNOY CVS 6 OUT TERM TERM IN 70V CEILING SPEAKER TANNOY CVS 6 OUT TERM TERM IN 70V CEILING SPEAKER TANNOY CVS 6 OUT TERM TERM IN 70V CEILING SPEAKER TANNOY CVS 6 OUT TERM TERM IN 70V CEILING SPEAKER TANNOY CVS 6 OUT TERM IN 8-OHM WALL SPEAKER JBL CONTROL 28-WH TERM IN 8-OHM WALL SPEAKER JBL CONTROL 28-WH TERM INPUT 1 RF OUT ASSISTIVE LISTENING TRANSMITTER BNC LISTEN LT-82-01 POWER OUT XLR SRJ45 RF IN ASSISTIVE LISTENING IR EMITTER LISTEN LA-140-GY POWER IN BNC SRJ45 PORT 1 PORT 13 AVB SWITCH NETGEAR GS724T AVB PORT 2 PORT 14 PORT 3 PORT 15 PORT 4 PORT 16 RJ45 RJ45 PORT 5 PORT 17 PORT 6 PORT 18 PORT 7 PORT 19 PORT 8 PORT 20 PORT 9 PORT 21 PORT 10 PORT 22 PORT 11 PORT 23 PORT 12 PORT 24 RJ45 RJ45 RJ45 RJ45 RJ45 FROM MANAGED SWITCH PORT 23 ON AV-703 STUDENT TABLES LECTERN CEILINGEQUIPMENT RACK FRONT WALL TERM TERM TERM TERM TERM TERM TERM TERM TERM TERM TERM TERM TERM TERM TERM TERM TERM TERM TERM TERM TERM TERM TERM ANTENNA A IN ANTENNA B IN BNC BNC OUTPUT W.LESS MIC ANTENNA EXTENDER BNC SHURE UA830 OUTPUT W.LESS MIC ANTENNA EXTENDER BNC SHURE UA830 CEILING AV-702 THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. $//5,*+765(6(59('‹ TOMEI AV CONSULTING LLC 29 JANIVAR DRIVE ITHACA, NY 14850 607-592-5370 WWW.TOMEIAV.COM MIKE@TOMEIAV.COM 15365.00 Checker AUDIO SIGNAL SINGLE LINE DIAGRAM SDF TOMEI 90% CONSTRUCTION DOCUMENTS CORNELL UNIVERSITY - COLLEGE OF ENGINEERING HOLLISTER HALL CLASS OF '49 CLASSROOM A/V UPGRADES & MINOR ROOM RENOVATIONS 08/21/2015 REVISIONS no.date by description COM 1 CONTROL PROCESSOR PHNX CRESTRON PRO3 COM 2 COM 3 PHNX COM 4 COM 5 RELAY 1 RELAY 2 PHNX PHNX RELAY 3 PHNX RELAY 4 RELAY 5 PHNX PHNX RELAY 6 RELAY 7 RELAY 8 CRESNET PHNX CONTROL SUBNET LAN RJ45 RJ45 RS-232 USB SWITCHER EXTRON SW4 USB PLUS PHNX REMOTE 1 AMPLIFIER CRESTRON AMP-3210T REMOTE 2 REMOTE 3 PHNX PHNX PHNX LVC RELAY 1 PROJECTION SCREEN DALITE ADVANTAGE DELUXE ELEC. LVC RELAY 2 TERM TERM RELAY 1 PROJECTION SCREEN SWITCH TERM DALITE RELAY 2 TERM CRESNET LIGHTING SYSTEM CONTROLLER CRESTRON CLS-C6 PHNX LAN WIRELESS PRESENTATION CRESTRON AM100 AIRMEDIA RJ45 LAN DM OUTPUT 1 MATRIX SWITCHER SRJ45 CRESTRON DM-MD16X16 DM OUTPUT 2 DM OUTPUT 3 DM OUTPUT 4 RJ45 SRJ45 SRJ45 SRJ45 DM IN RS-232 DM SCALER/RECEIVER SRJ45 PHNX CRESTRON DM-RMC-4K-SCALER-C RS-232 PROJECTOR DB9 EPSON G6770WU DM IN RS-232 DM SCALER/RECEIVER SRJ45 PHNX CRESTRON DM-RMC-4K-SCALER-C RS-232 CONFIDENCE MONITOR DB9 NEC E425 DM IN RS-232 DM SCALER/RECEIVER SRJ45 PHNX CRESTRON DM-RMC-4K-SCALER-C RS-232 FLAT PANEL DISPLAY DB9 SHARP LC-80LE661U DM IN RS-232 DM SCALER/RECEIVER SRJ45 PHNX CRESTRON DM-RMC-4K-SCALER-C RS-232 FLAT PANEL DISPLAY DB9 SHARP LC-80LE661U LAN/POE P/T/Z CAMERA PANASONIC AW-HE40SW RJ45 LAN/POE P/T/Z CAMERA PANASONIC AW-HE40SW RJ45 LAN/POE P/T/Z CAMERA PANASONIC AW-HE40SW RJ45 NETWORK WEB CONFERENCING CODEC VADDIO AV BRIDGE CONFERENCE RJ45 RS-232 VIDEO CONFERENCE CODEC CISCO SX80 LAN DB9 RJ45 LAN/POE TOUCH PANEL CRESTRON TSW-1050-B-S RJ45 LAN DOCUMENT CAMERA WOLFVISION VZ-8PLUS4 RJ45 LAN LIGHTING CONTROL SYSTEM ????? RJ45 PORT 1 PORT 13 MANAGED SWITCH RJ45 ????? RJ45 PORT 14 RJ45 PORT 15 RJ45 PORT 16 RJ45 PORT 17 RJ45 PORT 18 RJ45 PORT 19 RJ45 PORT 20 RJ45 PORT 21 RJ45 PORT 22 PORT 23 RJ45 PORT 24 RJ45 TO VIDEO CONFERENCE CODEC LAN PORT TO AVB SWITCH PORT 5 ON AV-702 FROM MANAGED SWITCH PORT 22 PORT 2RJ45 PORT 3RJ45 PORT 4 PORT 5 PORT 6 PORT 7 PORT 8 PORT 9 PORT 10 PORT 11 PORT 12 FIBERFIBER FROM DSP 1 VOIP PORT ON AV-702 FIBER CONNECTION TO CAMPUS NETWORK EQUIPMENT RACK CEILINGFRONT WALL CEILING FRONT WALL LECTERN EQUIPMENT RACK ROOM RJ45FROM LECTERN PC DATA JACK RJ45FROM LECTERN LAPTOP DATA JACK RJ45FROM LECTERN SPARE DATA JACK RJ45FROM INSTRUCTOR'S TABLE LAPTOP DATA JACK RJ45FROM INSTRUCTOR'S TABLE SPARE DATA JACK RJ45FROM INSTRUCTOR'S TABLE SPARE DATA JACK CEILING COM 6 AV-703 THESE DOCUMENTS AND ALL THE IDEAS, ARRANGEMENTS, DESIGNS AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE OWNED BY AND REMAIN THE PROPERTY OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C. AND NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE SPECIFIC WRITTEN PERMISSION OF SWBR ARCHITECTURE, ENGINEERING & LANDSCAPE ARCHITECTURE, P.C.. $//5,*+765(6(59('‹ 29 JANIVAR DRIVE ITHACA, NY 14850 607-592-5370 WWW.TOMEIAV.COM MIKE@TOMEIAV.COM 15365.00 Checker CONTROL & DATA SIGNAL SINGLE LINE DIAGRAM SDF TOMEI 90% CONSTRUCTION DOCUMENTS CORNELL UNIVERSITY - COLLEGE OF ENGINEERING HOLLISTER HALL CLASS OF '49 CLASSROOM A/V UPGRADES & MINOR ROOM RENOVATIONS 08/21/2015 REVISIONS no.date by description