Loading...
HomeMy WebLinkAbout26 60 00 - Fire Alarm System ImprovementsBEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 1 of 8 NOVEMBER 2, 2012 SECTION 266000 FIRE ALARM IMPROVEMENTS PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. The Contract Drawings and the General Provisions of the Contract, including the General Conditions of the Contract for Construction, Supplementary Conditions, Special Conditions and Division 1 Specification Sections apply to the work of this Division. B. The Work of the Sections 26 01 00 4 Electrical Basic Materials and Methods apply to the Work of this Section. 1.2 FIRE ALARM SYSTEM INSTALLER REQUIREMENTS: A. The installation of major fire alarm system renovations and new fire alarm and detection systems shall be performed by a qualified individual certified as either a National Institute for Certification in Engineering Technologies (NICET) Fire Alarm Systems Level III (minimum), or as a Licensed Professional Engineer. 1.3 WORK INCLUDED: The work of this Section shall include providing all materials, labor, services, permits and related work to furnish a complete, operating, tested, functioning, documented Fire Alarm improvements and modifications and additions to existing fire alarm System for Cornell University including all work shown, specified or required for proper system operation including but not limited to the following: A. Field verifications of existing conditions and associated demolition and removal of existing circuits, devices, and fixtures, where shown, removal of all debris from site and proper disposal of same. B. Confirmation that the existing system can support new device(s) Provide new hardware and appropriate and compatible system detection devices throughout the building as shown on the AMEP electrical drawings. C. Provide and install new conduit pathways and boxes for new fire alarm circuiting as shown on drawings. Extend existing fire alarm initiating circuit to new smoke detector. D. Provide equipment and conductor identification. All new fire alarm equipment shall match existing fire alarm manufacturer within the building. E. Provide testing of equipment and conductors. BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 2 of 8 NOVEMBER 2, 2012 F. Provide openings in existing and new construction as required for the work of this division. G. Provide maintenance of system in good condition until final acceptance. H. Provide Submittals, Shop Drawings and Coordination Drawings. I. Provide As4Built (Record Drawings) for the following: 1. Fire Alarm System Equipment and Devices J. Provide Reprogramming (with designators approved by Owner), testing, and modification to existing fire alarm panel(s). K. Provide startup, testing and troubleshooting services as required. L. Provide one year warranty from date of final acceptance. M. Provide owner training. N. Provide O&M document submission and “As4Built” Drawings. 1.4 SUBMITTALS A. To ensure compliance with the intent of this standard, all new fire alarm and detection system final designs and associated contract submittals shall be reviewed by CU Facilities Engineering (FE) and Environmental Health & Safety (EH&S). B. One (1) copy of each new project fire alarm system submittal shall be sent to both the CU FE Electrical Section and EH&S for review and comment prior to releasing final approved submittals to the contractor. Submittals shall contain the following information: 1. Product information for all installed components; 2. System riser diagram with typical equipment and device connection and labeling; NOTE that a detailed system/device connection diagram is NOT required until the completion of the project (as a complete “As4Built”). 3. Wire color coding table and/or schedule; 4. System battery stand4by calculations; 5. Special system requirements; 6. System labeling materials and methods as described in this section. C. At completion of the project, Contractor shall provide a complete set of fire alarm “As4Built” drawings that includes the following information prior to the closeout of the project: 1. New Initiating device locations; BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 3 of 8 NOVEMBER 2, 2012 2. Special systems interface locations; 3. Complete fire alarm riser diagram that depicts wiring between FACP and all new fire alarm system components. Such detail shall include all major equipment and their locations (approved room number designation), zone/loop wiring connections to initiating devices, SNAC wiring to notification appliances, and interconnections to other special systems as designed per this standard. 4. Circuit breaker locations for all fire alarm panels and accessory panels that receive building power. Locations shall include room number in which the power panel is located, as well as the breaker number that serves the equipment. D. The Owner or his designated representative shall approve all equipment submittals. E. Administrative Requirements a) Provide product data for each type of smoke/heat detector planned for use, at a minimum. F. General Requirements: 1. Manufacturer's original catalog data and descriptive information shall be supplied for all major components of the equipment to be supplied. 2. Suppliers' qualifications shall be supplied indicating years in business, service policies, warranty definitions, and a list of similar installations. 3. Contractor qualifications shall be supplied indicating years in business and prior experience with installations that include the type of equipment that is to be supplied. 4. All pertinent information shall be supplied regarding the reliability and operation of the equipment to be supplied. 5. Delivery dates of the equipment to be supplied shall be furnished. 6. Installation and final test/acceptance dates of the equipment shall be supplied. 7. Sufficient information shall be supplied so that the exact function of each installed device is known. 8. Provide battery stand4by calculations showing total stand4by power needed to meet the system requirements as specified. G. Other than Specified Equipment: Equipment other than specified shall be considered for approval provided the following is submitted in writing by the Electrical Contractor to the Engineer ten (10) days before the bid date: BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 4 of 8 NOVEMBER 2, 2012 1. Complete lists, descriptions and drawings of materials to be used. 2. A complete list of current drain requirements during normal supervisory conditions, trouble conditions and alarm conditions. 3. Battery stand4by calculations showing total stand4by power needed to meet the system requirements as specified. H. Substituted Equipment: If equipment other than that specified is supplied, it shall be the Contractor's obligation to submit the appropriate documentation and all the Engineer sufficient time to consider the equality of the substituted items. I. Satisfying the Entire Intent of these Specifications: 1. It is the Contractor's responsibility to meet the entire intent of these Specifications. Deviations from the specified items shall be at the risk of the Contractor 2. All costs for removal, relocation, or replacement of a substituted item shall be at the risk of the Contractor. 1.5 AGENCY APPROVALS: A. All equipment shall be listed by Underwriters Laboratories, Inc. or approved by Factory Mutual or as accepted by the authority having jurisdiction. B. The modified fire alarm system in its entirety shall be in compliance with all applicable fire and electrical codes and comply with the requirements of the local authority having jurisdiction over said systems. C. Accessory components as required shall be catalogued by the manufacturer and U.L. listed to operate with the manufacture’s control pane. 1.6 SPECIFIC U.L. PROVISIONS: A. The system shall comply with the applicable provisions of the following U.L. Standards and Classifications: 1. #864, Control Units for Fire Protective Signaling Systems. 2. UOJZ, Control Units, System. 3. UOXX, Control Unit Accessories, System. 1.7 SPECIFIC NFPA STANDARDS: A. The system shall comply with the applicable provision of the following current National Fire Protection Association (NFPA) standards: BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 5 of 8 NOVEMBER 2, 2012 1. NFPA 71 2. NFPA 72 National Fire Alarm Code 3. NFPA 90 A 4. NFPA 101 Life Safety Code 1.8 CODES AND STANDARDS: A. The Fire Alarm and Detection System shall comply with all local and state codes with no exception. B. The Fire Alarm Contractor shall be a licensed New York State Fire Alarm and Detection System Installer. 1.9 CONTRACTOR REQUIREMENTS: A. The Contractor providing modifications to the fire alarm and detection system shall be licensed per Article 6 D of the New York State General Business Law. PART 2 PRODUCTS 2.1 EQUIPMENT MATERIAL AND GENERAL REQUIREMENTS: A. All equipment furnished for this project shall be new and unused. All components and systems shall be designed for uninterrupted duty. All equipment, materials, accessories, devices and other facilities covered by this specification or noted on contract drawings and installation specifications shall be the best suited for the intended use and shall be provided by a single manufacturer. If any of the equipment provided under this Specification is provided by different manufactures, then that equipment shall be recognized as compatible by both manufacturers, and "Listed" as such by Underwriters’ Laboratories. B. System installation and operations shall be verified by the manufacturer’s representative and a verification certificate presented upon completion. The manufacturer’s representative shall be responsible for an on4site demonstration of the operation of the system and initial staff training as required by the Consulting Engineer. C. The system shall be capable of detecting the electrical location of each intelligent device. 2.2 SMOKE DETECTOR4PHOTOELECTRIC: A. Smoke Detectors – Spot Type BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 6 of 8 NOVEMBER 2, 2012 1. Smoke detectors shall be of the low profile, solid state, photoelectric or ionization type and shall be compatible for use in addressable, zoned, and combination addressable and zoned systems. 2. Smoke detectors shall be compatible for use in Style D (Class A) and Style B (Class B) circuits. (Note: Special power supplies or compensating devices shall not be required for smoke detectors to properly operate in circuits containing other Style D and Style B initiating devices. Also, Style B (Class B) smoke detectors shall not be used in initiating circuits unless provided with a separate 24 VDC control power supply.) 2.3 MOUNTING BASE4STANDARD DETECTOR: A. Standard detector mounting base suitable for mounting on 4" octagon and 4" square box or wiremold surface ceiling box. Base shall contain no electronics, support all detector types and have following minimum requirements: 1. Removal of respective detector shall not affect communications with other detectors. 2. Terminal connections shall be made on room side of the base. Bases which must be removed to gain access to the terminals shall not be accepted. B. Design Make (typical): Simplex Grinnell TrueAlert # 409849xxx Series, 2 or 44wire to match existing system, or as directed (field verify). C. Design Make (typical): EST Model SIGA4SB, or as directed to match existing (field verify). 2.4 SYSTEM IDENTIFICATION / LABELING A. Initiating, notification, signaling, and other fire alarm system wiring, circuits, and conductors shall be color coded and identified by number at termination points (i.e., control panels, remote annunciators, etc.) and splice points (i.e., junction boxes, splice boxes, etc.). Wiring shall be consistent throughout the system with no color changes on individual loops from the FACP. B. Junction and splice boxes containing fire alarm system wiring, circuits, and conductors shall have red covers and marked “FIRE ALARM” in 3/4" (three4quarter inch) white letters. C. Fire alarm equipment supplied with 120 VAC power shall be labeled with the panel source information, including panel name, room number and source breaker number. D. End4of4line resistors in two4wire systems shall be located at the fire alarm control panel, if feasible; otherwise, end4of4line resistors shall be installed in designated junction boxes with red covers and marked in accordance BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 7 of 8 NOVEMBER 2, 2012 with the specifications of this section. PART 3 EXECUTION 3.1 GENERAL: A. Any drilling/work that may create a nuisance fire alarm shall be scheduled at least 24 hours in advance with Cornell customer service for a fire protection system shutdown. Shutdown will be performed by Cornell EH&S staff. Contractor shall not disable any fire protection equipment without EH&S approval/assistance. B. Prior to construction within any room containing an existing smoke detector, coordinate with system vendor to temporarily replace the smoke detector with a heat detector, and test/re4program the system as required. Schedule the vendor in advance to avoid project delays. At completion of room construction, coordinate with vendor to replace heat detector with smoke detector, and test/re4program the system as required, in the presence of Cornell EH&S / IFD. C. Conform to Division 26 Specifications for installation and execution of work. 3.2 WIRING: A. For fire alarm use, wire and cable shall be U.L. listed and a minimum of 18 AWG as required by local codes and authority having jurisdiction. Provide twisted/shielded wire for communication circuits. All fire alarm and detection circuits shall be in conduit. B. Raceways containing conductors identified as "Fire Protective Alarm System". Conductors shall not contain any other conductors and no AC current carrying conductors shall be allowed in the same raceway with the D.C. Fire alarm detection and signaling conductors. 3.3 INSTALLER'S RESPONSIBILITIES: A. The installer shall field verify existing conditions/systems and coordinate the installation of the fire alarm equipment with the manufacturer or his authorized distributor. B. All conductors and wiring shall be installed according to the manufacturer's recommendations. C. It shall be the installer's responsibility to coordinate with the supplier, regarding the correct wiring procedures before installing any conduits or conductors. 3.4 INSTALLATION OF SYSTEM COMPONENTS: A. System components shall be installed in accordance with the latest BEARDSLEY DESIGN ASSOCIATES CORNELL – NCP FIRE ALARM SYSTEM IMPROVEMENTS STANDARD SPECIFICATIONS 26 60 00 – PAGE 8 of 8 NOVEMBER 2, 2012 revisions of the appropriate NFPA pamphlets, the requirements contained herein, National Electrical Code, local and state regulations, the requirements of the fire department, and other applicable authorities have jurisdiction. B. Low energy U.L. listed fire protective signaling circuit cable with 105° C insulation may be used when allowed by the local authority having jurisdiction, however, all conductors shall be in conduit. C. Installer shall verify that smoke detectors are mounted not less than three (3) feet from air supply diffusers. 3.5 GUARANTEE AND FINAL TEST: A. General: 1. The Contractor shall guarantee all equipment and wiring free from inherent mechanical and electrical defects for one year (365 days) from the date of final acceptance. B. Final Test: Before the installation shall be considered completed and acceptable by the Owner, a test on the system shall be performed as follows: 1. The Contractor's job foreman, in the presence of a representative of the manufacturer, a representative from Cornell EH&S, and the fire department shall operate each new building fire alarm device to ensure proper operation of the device, and correct annunciation at the control panel, the remote annunciator and building alarms. 2. One half of all tests shall be performed on battery stand4by power. 3. When the testing has been completed to the satisfaction of both the Contractor's job foreman and the representatives of the manufacturer and Owner, a notarized letter co4signed by each attesting to the satisfactory completion of said testing shall be forwarded to the Engineer and the fire department. 4. The Contractor shall leave the fire alarm system in proper working order, and without additional expense to the Owner, shall replace any defective materials or equipment provided by him under this Contract, within one year (365 days) from the date of final acceptance by the Owner. 5. Prior to final test the fire department must be notified in accordance with local requirements. END OF SECTION 26 60 00