HomeMy WebLinkAbout23 37 13 - Diffusers Registers and GrillesBEARDSLEY DESIGN ASSOCIATES
CORNELL NCP DIFFUSERS, REGISTERS, AND GRILLES
STANDARD SPECIFICATIONS 23 37 13 PAGE 1 OF 2
NOVEMBER 2, 2012
SECTION 233713 DIFFUSERS, REGISTERS, AND GRILLES
PART 1 GENERAL
1.1 SUBMITTALS
A. Product Data: For each type of product indicated, provide the following:
1. Data Sheet: Indicate materials of construction, finish, and mounting
details; and performance data including throw and drop, staticpressure
drop, and noise ratings.
2. Diffuser, Register, and Grille Schedule: Indicate drawing designation,
room location, quantity, model number, size, and accessories furnished.
PART 2 PRODUCTS
2.1 REGISTERS AND GRILLES
A. Register Grille:
1. Provide product by one of the following:
a. Anemostat Products; a Mestek company.
b. Price Industries.
c. Titus.
d. Tuttle & Bailey.
2. Material: Steel.
3. Finish: Baked enamel, white.
4. Face Blade Arrangement: Horizontal spaced 1/2 inch apart.
5. Core Construction: Integral.
6. Frame: 11/4 inches wide.
7. Mounting: Countersunk screw.
8. Accessories
a. Steel opposedblade damper with screwdriver slot operator
b. Filter
B. Fixed Lattice Face Plate :
1. Provide product by one of the following:
a. Anemostat Products; a Mestek company.
b. Price Industries.
c. Titus.
d. Tuttle & Bailey.
2. Material: Steel, 12 gauge.
3. Finish: Baked enamel, white.
4. Face Arrangement: 13/16" square holes on 1" centers.
BEARDSLEY DESIGN ASSOCIATES
CORNELL NCP DIFFUSERS, REGISTERS, AND GRILLES
STANDARD SPECIFICATIONS 23 37 13 PAGE 2 OF 2
NOVEMBER 2, 2012
2.2 SOURCE QUALITY CONTROL
A. Verification of Performance: Rate diffusers, registers, and grilles according to
ASHRAE 70, "Method of Testing for Rating the Performance of Air Outlets
and Inlets."
PART 3 EXECUTION
3.1 EXAMINATION
A. Examine areas where diffusers, registers, and grilles are to be installed for
compliance with requirements for installation tolerances and other conditions
affecting performance of equipment.
B. Proceed with installation only after unsatisfactory conditions have been
corrected.
3.2 INSTALLATION
A. Install diffusers, registers, and grilles level and plumb.
B. Ceiling/WallMounted Outlets and Inlets: Drawin gs indicate general
arrangement of ducts, fittings, and accessories. Air outlet and inlet locations
have been indicated to achieve design requirements for air volume, noise
criteria, airflow pattern, throw, and pressure drop. Make final locations where
indicated, as much as practical. For units installed in layin ceiling panels,
locate units in the center of panel. Where architectural features or other
items conflict with installation, notify Architect for a determination of final
location.
C. Install diffusers, registers, and grilles with airtight connections to ducts and to
allow service and maintenance of dampers, air extractors, and fire dampers.
3.3 ADJUSTING
A. After installation, adjust diffusers, registers, and grilles to air patterns
indicated, or as directed, before starting air balancing.
END OF SECTION 23 37 13