HomeMy WebLinkAbout09 22 16 - Non-Structural Metal FramingBEARDSLEY DESIGN ASSOCIATES
CORNELL NCP NON STRUCTURAL METAL FRAMING
STANDARD SPECIFICATIONS 09 22 16 PAGE 1 OF 4
NOVEMBER 2, 2012
SECTION 092216 NONSTRUCTURAL METAL FRAMING
PART 1 GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to
this Section.
1.2 SUMMARY
A. This Section includes nonloadbearing steel fra ming members for the
following applications:
1. Interior framing systems (e.g., supports for partition walls, framed soffits,
furring, etc.).
1.3 SUBMITTALS
A. Product Data: Furnish for each type of product used, include MSDS as
applicable.
1.4 QUALITY ASSURANCE
A. FireTestResponse Characteristics: For firere sistancerated assemblies
that incorporate nonloadbearing steel framing, pr ovide materials and
construction identical to those tested in assembly indicated according to
ASTM E 119 by an independent testing agency.
B. STCRated Assemblies: For STCrated assemblies, provide materials and
construction identical to those tested in assembly indicated according to
ASTM E 90 and classified according to ASTM E 413 by an independent
testing agency.
PART 2 PRODUCTS
2.1 NONLOADBEARING STEEL FRAMING, GENERAL
A. Framing Members, General: Comply with ASTM C 754 for conditions
indicated.
1. Steel Sheet Components: Comply with ASTM C 645 requirements for
metal, unless otherwise indicated.
BEARDSLEY DESIGN ASSOCIATES
CORNELL NCP NON STRUCTURAL METAL FRAMING
STANDARD SPECIFICATIONS 09 22 16 PAGE 2 OF 4
NOVEMBER 2, 2012
2. Protective Coating: ASTM A 653/A 653M, G40 (Z120), hotdip
galvanized, unless otherwise indicated.
2.2 AUXILIARY MATERIALS
A. General: Provide auxiliary materials that comply with referenced installation
standards.
1. Fasteners for Metal Framing: Of type, material, size, corrosion resistance,
holding power, and other properties required to fasten steel members to
substrates.
B. Isolation Strip at Exterior Walls: Provide one of the following:
1. AsphaltSaturated Organic Felt: ASTM D 226, Typ e I (No. 15 asphalt
felt), nonperforated.
2. Foam Gasket: Adhesivebacked, closedcell vinyl foam strips that allow
fastener penetration without foam displacement, 1/8 inch (3.2 mm) thick,
in width to suit steel stud size.
PART 3 EXECUTION
3.1 EXAMINATION
A. Examine areas and substrates, with Installer present, and including welded
hollowmetal frames, castin anchors, and structura l framing, for compliance
with requirements and other conditions affecting performance.
1. Proceed with installation only after unsatisfactory conditions have been
corrected.
3.2 INSTALLATION, GENERAL
A. Installation Standard: ASTM C 754, except comply with framing sizes and
spacing indicated.
1. Gypsum Board Assemblies: Also comply with requirements in
ASTM C 840 that apply to framing installation.
B. Install supplementary framing, and blocking to support fixtures, equipment
services, heavy trim, grab bars, toilet accessories, furnishings, or similar
construction.
C. Install bracing at terminations in assemblies.
D. Do not bridge building control and expansion joints with nonloadbearing
steel framing members. Frame both sides of joints independently.
BEARDSLEY DESIGN ASSOCIATES
CORNELL NCP NON STRUCTURAL METAL FRAMING
STANDARD SPECIFICATIONS 09 22 16 PAGE 3 OF 4
NOVEMBER 2, 2012
3.3 INSTALLING FRAMED ASSEMBLIES
A. Where studs are installed directly against exterior masonry walls or dissimilar
metals at exterior walls, install isolation strip between studs and exterior wall.
B. Install studs so flanges within framing system point in same direction.
1. Space studs as follows:
a. SingleLayer Application: 16 inches (406 mm) o.c., unless otherwise
indicated.
b. Multilayer Application: 16 inches (406 mm) o.c., unless otherwise
indicated.
C. Install tracks (runners) at floors and overhead supports. Extend framing full
height to structural supports or substrates above suspended ceilings, except
where partitions are indicated to terminate at suspended ceilings. Continue
framing around ducts penetrating partitions above ceiling.
1. SlipType Head Joints: Where framing extends to overhead structural
supports, install to produce joints at tops of framing systems that prevent
axial loading of finished assemblies.
2. Door Openings: Screw vertical studs at jambs to jamb anchor clips on
door frames; install runner track section (for cripple studs) at head and
secure to jamb studs.
a. Install two studs at each jamb, unless otherwise indicated.
b. Install cripple studs at head adjacent to each jamb stud, with a
minimum 1/2inch (12.7mm ) clearance from jamb stud to allow for
installation of control joint in finished assembly.
c. Extend jamb studs through suspended ceilings and attach to
underside of overhead structure.
3. Other Framed Openings: Frame openings other than door openings the
same as required for door openings, unless otherwise indicated. Install
framing below sills of openings to match framing required above door
heads.
4. FireResistanceRated Partitions: Install frami ng to comply with fire
resistancerated assembly indicated and support clo sures and to make
partitions continuous from floor to underside of solid structure.
5. SoundRated Partitions: Install framing to comp ly with soundrated
assembly indicated.
D. Installation Tolerance: Install each framing member so fastening surfaces
vary not more than 1/8 inch (3 mm) from the plane formed by faces of
adjacent framing.
BEARDSLEY DESIGN ASSOCIATES
CORNELL NCP NON STRUCTURAL METAL FRAMING
STANDARD SPECIFICATIONS 09 22 16 PAGE 4 OF 4
NOVEMBER 2, 2012
END OF SECTION 092216