Loading...
HomeMy WebLinkAbout27 05 53 Testing Identification and AdministrationARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 1 OF 23 MARCH 29, 2013 SECTION 27 05 53 TESTING, IDENTIFICATION AND ADMINISTRATION PART 1– GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, tools, and equipment required for the complete installation of work called for in the Contract Documents 1.2 SCOPE A. This section includes the minimum requirements for the testing, certification administration and identification of backbone and horizontal cabling. B. This section includes minimum requirements for the following: 1. Contractor Qualifications 2. Tester Calibrations / Factory Requirements 3. UTP testing and testers 4. Labels and labeling 5. Reports 6. Documentation 7. Record Copy and As-Builts 8. Test and Acceptance 9. Warranty 1.3 QUALITY ASSURANCE A. All testing procedures, testers and identification and administration work specified shall comply with applicable requirements of: 1. ANSI/TIA/EIA – 606-A Administration Standards. 2. ANSI/TIA/EIA – 569A Pathway and Spaces 3. ANSI/TIA/EIA – 568-C.0 Generic Telecommunications Cabling For Customer Premises 4. ANSI/TIA/EIA – 568-B.2 Balanced Twisted-Pair Cabling Components and Testing ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 2 OF 23 MARCH 29, 2013 ` 5. ANSI/TIA/EIA – 568-B.3 Optical Fiber Cabling Component Standard and Testing 6. 7. ANSI/TIA/EIA – 526-x Standard Test Procedures for Fiber Optic Systems 8. ANSI/TIA/EIA – 526-14A Power Loss Measurements of Install Multimode Fiber Cable Plant 9. ANSI/TIA/EIA – 526-7 Measurement of Optical Loss of Installed Singlemode Fiber Cable Plant 10. ANSI/TIA/EIA – 598-A Optical Fiber Cable Color Coding 11. ANSI/TIA/EIA – 504-x FOCIS x Documents for Fiber Optic Connector Intermateability Standards 12. TIA/EIA-J-STD-037 Commercial Building Grounding (Earthing) and Bonding Requirements for Telecommunications 13. ISO/IEC 11801 Information Technology - Generic Cabling for Customer Premises 14. BICSI TDMM Telecommunications Distribution Methods Manual, current edition 1.4 SUBMITTALS A. Manufacturers catalog sheets and specifications for each cable testers, test heads and adapter cords and latest version of software applicable for each tester planned for use. B. Provide written factory calibration recommendation letter and factory recommended field calibration intervals with bid. C. Provide signed manufacturer factory calibration certification for each copper and fiber tester owned at time of bid response as a submittal. Certification shall have serial number, date and version of software of each tester. D. For each UTP field tester planned for use on this project, provide a letter from the tester manufacturer and the connectivity/cable manufacturers indicating compatibility and compliance to Category 6 permanent link and the Category 6, channel tests with the products identified for use on this project and the warranty requirements called for by the manufacturers. Contractor shall provide testers and equipment that fully conform to Panduit’s testing requirements for system warranty as specified in the Approved Category 6 Test Lead/Cord Adapters document, at: http://www.panduit.com/products/SpecificationGuides/068804.pdf ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 3 OF 23 MARCH 29, 2013 ` E. Sample documentation from previous job for administration, test results and as-built drawings. F. At time of testing, provide a factory calibration certificate for each tester used and include these in each test report binder at the completion of the project. G. Test reports (submit prior to substantial completion punch list is performed) H. Two copies on compact disks containing all summary reports, full plot data test results, tester software tools required to view and inspect and print any selection of the test reports, spreadsheets, end to end reports and as built drawings called for at the completion of job.. The database for the completed job shall be stored and delivered on CD-ROM including the software tools required to view, inspect, and print any selection of test reports. I. Technician certificates for successful completion of training for each of the field testers proposed to be used in this project. J. Two copies in binder format and two copies on compact disks containing all digital photographs called for at the completion of the job. K. Refer to Section 01340 – “Shop Drawings, Product Data” and 27 05 00 for additional requirements. PART 2 - PRODUCTS 2.1 VERIZON CIRCUIT IDENTIFICATION AND TESTING A. Not Included in this project 2.2 OPTICAL FIBER CABLE A. Field test instruments for multimode fiber cabling shall meet the requirements of ANSI/TIA/EIA-526-14-A. B. Field test instruments for multimode fiber cabling shall meet the requirements of ANSI/TIA/EIA-526-7. C. Multimode optical fiber light source 1. Provide 850nm and 1300nm +/- 20 nm wavelength LED light sources 2. Spectral width of sources shall be </= 50nm for 850nm wavelengths and </= 140nm for 1300nm wavelengths. 3. The output of the light source shall be 8 MW for 62.5um core optical fiber ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 4 OF 23 MARCH 29, 2013 ` 4. Output Stability +/- 0.40 dB from 0 to 50 degrees C 5. Long Term output stability +/- 0.10dB at 25 degrees C 6. Power shall be from rechargeable Ni-Cad batteries 7. Connector types shall include: SMA, FC, ST and SC 8. Design make: Siecor Light source 9. Acceptable Manufacturers: a) Fluke b) Wavetek c) Lantek d) AMP NetConnect e) Corning Cable Systems D. Single mode optical fiber light source 1. Provide 1300nm and 1500nm +/- 20 nm wavelength Laser light sources 2. Output Stability +/- 0.40 dB from 0 to 50 degrees C 3. Long Term output stability +/- 0.10dB at 25 degrees C 4. Power shall be from rechargeable Ni-Cad batteries 5. Connector types shall include: SMA, FC, ST and SC 6. Design make: Siecor OS-200D 7. Acceptable Manufacturers: a) Fluke b) Meson c) AMP NetConnect d) Corning Cable Systems E. Optical Power Meter 1. Calibrates against the National Institute of Standards and Technology (NIST) standard. 2. Provide 850nm, 1300nm and 1500nm +/- 20 nm wavelength test capability 3. Measurement range shall be from 10 to -60 dBm ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 5 OF 23 MARCH 29, 2013 ` 4. Accuracy shall be +/- 5% at 0 to -50dBm and +/- 10% 10 to 0dBm and -50 to-60 dBm. 5. Resolution shall be 0.1 dB 6. Connector types shall include: SMA, FC, ST and SC 7. Design make: Siecor OM-100F 8. Acceptable Manufacturers: a) Fluke b) Meson c) AMP NetConnect d) Corning Cable Systems F. Optical Time Domain Reflectometer (OTDR) 1. Dual selectable wavelength: 850/1300 nm for multimode 2. Dual selectable wavelength: 1310/1550 nm for singlemode 3. Selectable cable index of refraction. 4. Visual fault locator for continuity checks and dead zone fault protection. 5. Display and printer connection for hard-copy documentation 6. Equipped with launch jumper cable of sufficient length to offset entry” deadzone”. 2.3 100 OHM UTP TEST EQUIPMENT A. GENERAL 1. Field test instruments shall meet the requirements of ANSI/TIA/EIA-568-B.2 Annex B and Annex I. 2. Test equipment used under this contract shall be from manufacturers that have a minimum of 5 years experience in producing field test equipment. 3. Manufacturers must be ISO 9001 certified. 4. All test tools of a given type shall be from the same manufacturer, and have compatible electronic results output. 5. Test adapter cables/test heads must be approved by the manufacturer of the test ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 6 OF 23 MARCH 29, 2013 ` equipment, for the specific cable and connectivity product used on this project. Adapters from other sources are not acceptable. Obtain written confirmation that the test heads and adapter planned fro use are proper and also obtain a written confirmation from the wire and connectivity manufactures that they also agree with the test heads and adapter selection chosen by the tester manufacturer. 6. Baseline accuracy of the test equipment must exceed TIA Level IIIe, as indicated by independent laboratory testing. 7. A level IIIe test unit is required to verify category 6 performance for both Category 6 permanent link and channel performance. 8. Test equipment must be capable of certifying Category 5, 5e, and 6 links. 9. Test equipment must have a dynamic range of at least 100 dB to minimize measurement uncertainty. 10. Test equipment must be capable of storing full frequency sweep data for all tests and printing color graphical reports for all swept measurements. 11. Test equipment must include S-Band time domain diagnostics for NEXT and return loss (TDNXT and TDRL) for accurate and efficient troubleshooting. 12. Test equipment must be capable of running individual NEXT, return loss, etc measurements in addition to autotests. Individual tests increase productivity when diagnosing faults. 13. Test equipment must include a library of cable types by major manufacturer. 14. Test equipment must store at least 1000 Category 6 or 6 autotests in internal memory. 15. Test equipment must be able to internally group autotests and cables in project folders for good records management. 16. Test equipment must include technology for support of advanced measurements. 17. Test equipment must make swept frequency measurements in compliance with TIA standards. 18. The measurement reference plane of the test equipment shall start immediately at the output of the test equipment interface connector. There shall not be a time domain dead zone of any distance that excludes any part of the link from the measurement. 19. The basic tests required are: ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 7 OF 23 MARCH 29, 2013 ` a) · Wire Map b) · Length c) · Attenuation d) · NEXT (Near end crosstalk) e) · Return Loss f) · ELFEXT Loss g) · Propagation Delay h) · Delay skew i) · PSNEXT (Power sum near-end crosstalk loss) j) · PSELFEXT (Power sum equal level far-end crosstalk loss) 20. Shall be able to test cable for compliance with all of the following standards: a) TIA Category 6: Permanent Link and Channel b) ISO/IEC 11801 and EN 50173 Class C, D and E: Link c) ISO/IEC 11801 and EN 50173 Class C, D and E: Permanent Link or Channel d) Aus/NZ Class C and D: Basic Link or Channel e) STP cabling, (IBM Type 1, 150 ohm) f) ANSI TP-PMD IEEE 802.3 10BASE5, 10BASE2: Ethernet with coaxial cabling g) IEEE 802.3 10BASE-T, 100BASE-TX, 1000BASE-T: Ethernet with twisted pair cabling IEEE 802.5: Token Ring, 4 Mbps or 16 Mbps 21. Shall perform the following tests as a minimum: a) NEXT, NEXT @ Remote b) Wire Map c) Characteristic Impedance d) Length e) DC Loop Resistance f) Propagation Delay Return Loss (RL), RL @ Remote g) Delay Skew h) Attenuation i) Attenuation-to-Crosstalk Ratio (ACR), ACR @ Remote j) Power Sum ACR, PSACR @ Remote k) ELFEXT, ELFEXT @ Remote l) Power Sum ELFEXT, PSELFEXT @ Remote m) Power Sum NEXT, PSNEXT @ Remote 22. Shall use injector for complete wire mapping and TDR for determining cable length. 23. Shall measure NEXT for all six pair combinations and Attenuation on all four pairs from 1.0 to 350 MHz. 24. Design Make: Fluke “DSP 4000 or 4300 series” ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 8 OF 23 MARCH 29, 2013 ` 25. Acceptable Manufacturers: a) Agilent b) WaveTek c) Lantek d) Wirescope 2.4 LABELS A. Shall meet the legibility, defacement, exposure and adhesion requirements of UL 969. B. Shall be preprinted or laser printed type. Handwritten labels are not acceptable. C. Where used for cable marking provide vinyl substrate with a white printing area and a clear “tail” that self laminates the printed area when wrapped around the cable. If cable jacket is white, provide cable label with printing area that is any other color than white, preferably orange or yellow – so that the labels are easily distinguishable. D. Where insert type labels are used provide clear plastic cover over label. Acceptable Manufacturers: 1. WH Brady 2. Panduit 3. Ideal: PART 3 - EXECUTION 3.1 COPPER CABLE TEST A. A level IIIe test unit is required to verify category 6 performances, shall be updated with the latest version of tester software at time of testing and shall be factory tested/calibrated within one of time of testing. Provide copies of factory certification for each tester owned at time of bid response as a submittal. At time of testing, provide a factory calibration certificate for tester used and include these in each test report binder at the completion of the project. B Visually inspect all cables, cable reels, and shipping cartons to detect possible cable damage incurred during shipping and transport. Visibly damaged goods are to be returned to the supplier and replaced at no additional cost to the Owner. C. If post-manufacture performance data has been supplied by the manufacturer of cables or connecting hardware, copies of such data are to be kept for inclusion in the Documentation for final Record Copy deliverables and made available to the Owner upon request. ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 9 OF 23 MARCH 29, 2013 ` D. Test 100% of installed backbone copper cabling for 1. Wire Map 2. Length E. Provide documentation in hardcopy and electronic formats, organized the same as outlined in 27 05 53, Sections 3.5.W “Third Party Verification” and Section 3.6 “Test Documentation” of this section. 3.2 OPTICAL FIBER CABLE TESTING A. All fiber testing shall be performed on all fibers in the completed end to end system. B. Comply with Tier-two testing as defined in TSB-140. which included loss and length testing with an optical loss test set (OLTS) and also an OTDR trace of the installed cable plant. By incorporating the proposed two-tier testing method, installers have the most complete picture of the fiber installation and network owners have proof of a quality installation C. Testing shall consist of an end to end power meter test performed per EIA/TIA-455- 53A. The system loss measurements shall be provided at 850 and/or 1300 nanometers for multimode fibers and 1310 and/or 1550 nanometers for single mode fibers. These tests also include continuity checking of each fiber. D. There shall be no splices unless clearly called for. E. Test all fibers with launch and far end cable of sufficient length for the OTDR to be able to see through all installed connectors. F. Localized attenuation shall not exceed 0.5 dB at any point. G. Backbone multimode fiber shall be tested in one direction at both 850nm and 1300 nm in accordance with ANSI/EIA/TIA-526-14A method B. H. Backbone single mode fiber shall be tested in one direction at both 1310nm and 1550. I. For horizontal cabling system using multimode optical fiber, attenuation shall be measured in one direction at either 850 nanometer (nm) or 1300 nm using an LED light source and power meter. J. Backbone multimode fiber cabling shall be tested at both 850 nm and 1300 nm (or 1310 and 1550 nm for singlemode) in one direction. K. Test set-up and performance shall be conducted in accordance with ANSI/EIA/TIA- 526-14 Standard, Method B. L. Where links are combined to complete a circuit between devices, the Contractor shall test each link from end to end to ensure the performance of the system. ONLY BASIC LINK TEST IS REQUIRED. The contractor can optionally install patch ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 10 OF 23 MARCH 29, 2013 ` cords to complete the circuit and then test the entire channel. The test method shall be the same used for the test described above. The values for calculating loss shall be those defined in the ANSI/TIA/EIA Standard. M. Attenuation testing shall be performed with a stable launch condition using two-meter jumpers to attach the test equipment to the cable plant. The light source shall be left in place after calibration and the power meter moved to the far end to take measurements. N. Backbone Cable 1. Test the cable on the reel for continuity before installing it, to insure no damage was done in shipment from the manufacturer to the job site. 2. After installation and termination, test each segment of the cable plant individually as it is installed, to insure each connector and cable is good. 3. Link attenuation is the only required field test except for the patched runs in the campus backbone system where an OTDR test will be required. Use launch cables at each end and provide print outs showing all connectors. OTDR will also be required to determine bad connections or damage when the link attenuation test fails. 4. Maximum localized attenuation allowed is 2dB. 5. Backbone multimode fiber shall be tested in one direction at both 850nm and 1300 nm in accordance with ANSI/EIA/TIA-526-14A method B. 6. Backbone single mode fiber shall be tested in one direction at both 1310nm and 1550 nm in accordance with ANSI/EIA/TIA-526-14A method A.1. 7. Multimode fiber shall conform to the following: 850 nm: Length (meters) Attenuation ( dB) 500 3.5 1000 5.5 1500 7.5 2000 9.0 1300 nm: Length (meters) Attenuation ( dB) 500 2.2 1000 3.0 1500 3.8 2000 4.5 ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 11 OF 23 MARCH 29, 2013 ` 8. Single Mode Fiber shall conform to the following (note: taken at 1550nm) Inside: Length (meters) Attenuation ( dB) 500 2.0 1000 2.5 1500 3.0 2000 3.5 2500 4.0 3000 4.5 Outside: Length (meters) Attenuation ( dB) 500 1.8 1000 2.0 1500 2.2 2000 2.5 2500 2.8 3000 3.0 O. Documentation 1. Provide attenuation and cable length test results for all installed cable pairs. 3.3 TEST REPORTS A. Provide documentation in hardcopy and electronic formats, organized the same as outlined in 27 05 53, Sections 3.5.W “Data Reporting and Accuracy” and Section 3.6 “Test Documentation” of this section. 3.4 100 OHM UTP CABLE TESTING GENERAL A. Every cabling link shall be tested in accordance with the field test specifications defined in ANSI/TIA/EIA-568-B.2-1 “Transmission Performance Specifications for 4-pair 100Ω Category 6 Cabling and as defined in the Manufacturer warranty requirements. Refer to item 1.4 submittals for additional information. B. Trained technicians who have successfully attended an appropriate training program and have obtained a certificate as proof thereof shall execute the tests. C. The test equipment shall comply with the accuracy requirements for level IIIe field testers as defined in ANSI/TIA/EIA-568-B.2-1. The tester including the appropriate interface adapter must meet the specified accuracy requirements. The accuracy requirements for the permanent link test configuration (baseline accuracy plus adapter contribution) are specified in Table B.2 of Annex B of the TIA Cat 6 Standard. (Table ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 12 OF 23 MARCH 29, 2013 ` B.3 in this TIA document specifies the accuracy requirements for the Channel configuration. D. The tester shall be within the calibration period recommended by the vendor in order to achieve the vendor-specified measurement accuracy. E. The tester interface adapters must be of high quality and the cable shall not show any twisting or kinking resulting from coiling and storing of the tester interface adapters. In order to deliver optimum accuracy, preference is given to a permanent link interface adapter for the tester that can be calibrated to extend the reference plane of the Return Loss measurement to the permanent link interface. The contractor shall provide proof that the interface has been calibrated within the period recommended by the vendor. To ensure that normal handling on the job does not cause measurable Return Loss change, the adapter cord cable shall not be of twisted-pair construction. F. A Pass or Fail result for each parameter is determined by comparing the measured values with the specified test limits for that parameter. The test result of a parameter shall be marked with an asterisk (*) when the result is closer to the test limit than the accuracy of the field tester. The field tester manufacturer must provide documentation as an aid to interpret results marked with asterisks. G. All cables and termination hardware shall be 100% tested for defects in installation and to verify cabling system performance under installed conditions according to the requirements of ANSI/TIA/EIA-568-B. H. All pairs of each installed cable shall be verified prior to system acceptance. Any defect in the cabling system installation including but not limited to cable, connectors, feed through couplers, patch panels, and connector blocks shall be repaired or replaced in order to ensure 100% useable conductors in all cables installed. The testing parameters called for in this section shall apply for up to 90 meters of horizontal cable, a work area equipment cord, an RJ45 outlet and 2 cross connect connections in the closet. The test parameters shall include Wire Map, Length, Attenuation and NEXT Wire Map 1. The wire map test shall verify pair to pin termination at each end and check for connectivity errors. Wire Map shall report Pass if the wiring of each wire- pair from end to end is determined to be correct. The Wire Map results shall include the continuity of the shield connection if present The wire map shall indicate the following for each of the eight conductors: a) Continuity to the remote end b) Shorts between any two or more conductors c) Crossed pairs d) Reversed Pairs e) Split Pairs ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 13 OF 23 MARCH 29, 2013 ` f) Any other miswiring Cable Length The field tester shall be capable of measuring length of all pairs of a basic link or channel based on the propagation delay measurement and the average value for NVP. The physical length of the link shall be calculated using the pair with the shortest electrical delay. This length figure shall be reported and shall be used for making the Pass/Fail decision. The Pass/Fail criteria are based on the maximum length allowed for the Permanent Link configuration (90 meters – 295 feet) plus 10% to allow for the variation and uncertainty of NVP. 2. The set-up configuration of the NVP shall be based solely on the NVP value of the cable specified in the approved cable submittal for this project. Insulation characteristics and twist rate of the wire pair influence NVP in minor ways and is dependent on the specific manufacturer. Typically, an ‘average’ value for NVP is published for all four wire-pairs in a data cable. Insertion Loss (Attenuation) Insertion Loss is a measure of signal loss in the permanent link or channel. The term “Attenuation” has been used to designate “Insertion Loss.” Insertion Loss shall be tested from 1 MHz through 250 MHz in maximum step size of 1 MHz. It is preferred to measure insertion loss at the same frequency intervals as NEXT Loss in order to provide a more accurate calculation of the Attenuation-to-Crosstalk ratio (ACR) parameter. Minimum test result documentation (summary report and full plot data, in format and quantities called for): Identify the worst wire pair (1 of 4 possible). The test results for the worst wire pair must show the highest attenuation value measured (worst case), the frequency at which this worst case value occurs, and the test limit value at this frequency. NEXT Loss Pair-to-pair near-end crosstalk loss (abbreviated as NEXT Loss) shall be tested for each wire pair combination from each end of the link (a total of 12 pair combinations). This parameter is to be measured from 1 through 250 MHz. NEXT Loss measures the crosstalk disturbance on a wire pair at the end from which the disturbance signal is transmitted (near-end) on the disturbing pair. The maximum step size for NEXT Loss measurements shall not exceed the maximum step size defined in the standard as shown in Table 1, column 2. 3. Minimum test results documentation (summary report and full plot data, in format and quantities called for): Identify the wire pair combination that exhibits the worst case NEXT margin and the wire pair combination that exhibits the worst value of NEXT (worst case). ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 14 OF 23 MARCH 29, 2013 ` 4. NEXT is to be measured from each end of the link-under-test. These wire pair combinations must be identified for the tests performed from each end. Each reported case should include the frequency at which it occurs as well as the test limit value at this frequency. Frequency Range (MHz) Maximum Step Sixe (MHz) 1 – 31.25 0.15 31.26 – 100 0.25 100 – 250 0.50 250 - 350 1.00 TABLE 1 PSNEXT Loss Power Sum NEXT Loss shall be evaluated and reported for each wire pair from both ends of the link under-test (a total of eight results). PSNEXT Loss captures the combined near-end crosstalk effect (statistical) on a wire pair when all other pairs actively transmit signals. Like NEXT this test parameter must be evaluated from 1 through 250 MHz and the step size may not exceed the maximum step size defined in the standard as shown in Table 1, column 2. Minimum test results documentation (summary report and full plot data, in format and quantities called for): Identify the wire pair that exhibits the worst-case margin and the wire pair that exhibits the worst value for PSNEXT. These wire pairs must be identified for the tests performed from each end. Each reported case should include the frequency at which it occurs as well as the test limit value at this frequency. ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 15 OF 23 MARCH 29, 2013 ` ELFEXT Loss, pair to pair Pair-to-pair FEXT Loss shall be measured for each wire-pair combination from both ends of the link under-test. FEXT Loss measures the crosstalk disturbance on a wire pair at the opposite end (far-end) from which the transmitter emits the disturbing signal on the disturbing pair. FEXT is measured to compute ELFEXT Loss that must be evaluated and reported in the test results. ELFEXT measures the relative strength of the far-end crosstalk disturbance relative to the attenuated signal that arrives at the end of the link. This test yields 24 wire pair combinations. ELFEXT is to be measured from 1 through 250 MHz and the maximum step size for FEXT Loss measurements shall not exceed the maximum step size defined in the standard as in Table 1, column 2. Minimum test results documentation (summary report and full plot data, in format and quantities called for): Identify the wire pair combination that exhibits the worst-case margin and the wire pair combination that exhibits the worst value for ELFEXT. These wire pairs must be identified for the tests performed from each end. Each reported case should include the frequency at which it occurs as well as the test limit value at this frequency. PSELFEXT Loss Power Sum ELFEXT is a calculated parameter that combines the effect of the FEXT disturbance from three wire pairs on the fourth one. This test yields eight wire-pair combinations. Each wire-pair is evaluated from 1 through 250 MHz in frequency increments that do not exceed the maximum step size defined in the standard as shown in Table 1, column 2. Minimum test results documentation (summary report and full plot data, in format and quantities called for):): Identify the wire pair that exhibits the worst pair combinations must be identified for the tests performed from each end. Each reported case should include the frequency at which it occurs as well as the test limit value at this frequency. Return Loss Return Loss (RL) measures the total energy reflected on each wire pair. Return Loss is to be measured from both ends of the link-under-test for each wire pair. This parameter is also to be measured form 1 through 250 MHz in frequency increments that do not exceed the maximum step size defined in the standard as shown in Table 1, column 2. Minimum test results documentation (summary report and full plot data, in format and quantities called for): Identify the wire pair that exhibits the worst-case margin and the wire pair that exhibits the worst value for Return Loss. These wire pairs must be identified for the tests performed from each end. Each reported case should include ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 16 OF 23 MARCH 29, 2013 ` the frequency at which it occurs as well as the test limit value at this frequency ACR (Attention to crosstalk ratio) This parameter is not demanded by the standard but may be required in order to obtain the premise wiring manufacturer’s warranty]. ACR provides an indication of bandwidth for the two wire-pair network applications. ACR is a computed parameter that is analogous to ELFEXT and expresses the signal to noise ratio for a two wire- pair system. This calculation yields 12 combinations – six from each end of the link. Minimum test results documentation (summary results): Identify the wire pair combination that exhibits the worst-case margin and the wire pair combination that exhibits the worst value for ACR. These wire pair combinations must be identified for the tests performed from each end. Each reported case should include the frequency at which it occurs as well as the test limit value at this frequency PSACR NOTE: This parameter is not required by the standard but may be required in order to obtain the premise wiring vendor’s warranty. Provide as required for Manufacturer Warranty. The Power Sum version of ACR is based on PSNEXT and takes into account the combined NEXT disturbance of all adjacent wire pairs on each individual pair. This calculation yields eight combinations –one for each wire pair from both ends of the link. Minimum test results documentation (summary results): Identify the wire pair that exhibits the worst-case margin and the wire pair that exhibits the worst value for PSACR. These wire pairs must be identified for the tests performed from each end. Each reported case should include the frequency at which it occurs as well as the test limit value at this frequency. Propagation Delay Propagation delay is the time required for the signal to travel from one of the link to the other. This measurement is to be performed for each of the four wire pairs. Minimum test results documentation (summary report and full plot data, in format and quantities called for): Identify the wire pair with the worst-case propagation delay. The report shall include the propagation delay value measured as well as the test limit value Delay Skew (as defined in TIA/EIA-568-B.1; Section 11.2.4.11) This parameter shows the difference in propagation delay between the four wire pairs. The pair with the shortest propagation delay is the reference pair with a delay skew value of zero. ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 17 OF 23 MARCH 29, 2013 ` Minimum test results documentation (summary report and full plot data, in format and quantities called for): Identify the wire pair with the worst-case propagation delay (the longest propagation delay). The report shall include the delay skew value measured as well as the test limit value. DATA REPORTING AND ACCURACY The test results information for each link shall be recorded in the memory of the field tester upon completion of the test. The test results records saved by the tester shall be transferred into a Windows™- based database utility that allows for the maintenance, inspection and archiving of these test records. A guarantee must be made that the measurement results are transferred to the PC unaltered, i.e., “as saved in the tester” at the end of each test and that these results cannot be modified at a later time. The database for the completed job shall be stored and delivered on CD-ROM including the software tools required to view, inspect, organized, manage and print any selection of test reports. The detailed test result data to be provided in the electronic database for each tested link must contain the frequency-dependent test parameters, the value measured at every frequency during the test is stored. The PC- resident database program must be able to process the stored results to display and print a color graph of the measured parameters. The PC-resident software must also provide a summary numeric format in which some critical information is provided numerically as defined by the summary results (minimum numeric test results documentation) as outlined above for each of the test parameters. A paper copy of the test results shall be provided that lists all the links that have been tested with the following SUMMARY REPORT information: a) The identification of the link in accordance with the naming convention defined in the overall system documentation b) The overall Pass/Fail evaluation of the link-under-test including the NEXT Headroom (overall worst case) number c) The date and time the test results were saved in the memory of the tester 5. General Information to be provided in the electronic data base with the test results information for each link: a) The identification of the customer site as specified by the end-user b) The identification of the link in accordance with the naming convention defined in the overall system documentation c) The overall Pass/Fail evaluation of the link-under-test d) The name of the standard selected to execute the stored test results e) The cable type and the value of NVP used for length calculations ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 18 OF 23 MARCH 29, 2013 ` f) The date and time the test results were saved in the memory of the tester g) The brand name, model and serial number of the tester h) The identification of the tester interface i) The revision of the tester software and the revision of the test standards database in the tester j) The test results information must contain the information on each of the required test parameters listed in this section of the specifications 6. General: a Pass or Fail result for each parameter shall be determined by the allowable limits for each parameter. If the test result of a parameter is closer to the test limit than the accuracy of the tester it shall be marked with an asterisk. Data at all measured points shall be uploaded to a P.C. and printed on a laser printer. 7. Wire Map: Wire map tests shall be marked “Pass” if wiring is determined correct. 8. Length: Test results shall be provided in meters and marked “Pass or Fail” based on the length vs. allowable length. 9. Submit copies in binder format and on compact disks containing all summary reports, full plot data test results, tester software tools required to view and inspect and print any selection of the test reports, spreadsheets, end to end reports and as built drawings called for at the completion of job. 3.5 THIRD PARTY VERIFICATION A. Owner’s representative shall be invited to witness field testing. The representative shall be notified of the start date of the testing phase 5 business days before testing commences. B. Owner’s representative may select a random sample of 1% of the installed links. The representative (or his authorized delegate) shall test these randomly selected links and the results are to be stored as called for in this section. The results obtained shall be compared to the data provided by the installation contractor. If more than 2% of the sample results differ in terms of the pass/fail determination, the installation contractor under supervision of the Owner’s representative shall repeat 100% testing and the cost shall be borne by the installation contractor. 3.6 TEST DOCUMENTATION A. Provide test report documentation in a hard copy summary report, by TR, in a three- ring binder, within 1 week prior to cutover of any phase of the project. Provide full plot data for any failures and any marginal passes and place yellow posted note affixed to each related printed page of the binder for review with Owner. Correct any deficiencies as direct by the Owner. ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 19 OF 23 MARCH 29, 2013 ` B. The three-ring binder shall be clearly marked on the outside front cover and spine with the words “Test Results”, the project name, building name, Cornell assigned facility code number, the date of completion (month and year) and the Contractors name and address. A tab shall be provided for each TR and the test results organized by TR. The test reports in each TR tabbed section shall be sorted (before printing) by Patch Panel and port for each TR. C. Provide two CD’s with summary report, full plot data, test report within 1 week after the completion of the project. The disks shall placed into CD sleeves and placed into a three-ring binder clearly marked on the outside front cover and spine with the words “Test Results”, the project name, building name, Cornell assigned facility code number the date of completion (month and year) and the Contractors name and address. The electronic test results shall be sorted by TR into proper folders to match the heading of tabs in the tree ring binders. Also include in the binder, the summary information provided in A. above and the full plot data for any previous failures or marginal passes that have been corrected – with an explanation of the corrective action and the signature of the technician and the foreman. D. The binder and electronic folder/files shall divided by major heading tabs (or in the case of electronic files, be placed into a folders structure similar to the hardcopy tests of this section). E. Major heading tabs (folders) shall be divided into Horizontal and Backbone (both fiber and copper backbone). Each shall be further sectioned by test type and by TR and rack as applicable. F. For copper backbone, test all terminated, spliced, relocated or transferred pairs – two weeks before intended cutover. Test all pairs, end-to-end and record hand written results on the test sheet provided on the last page of this section. Coordinate access to the Central Office end of the backbone cable for end-to-end testing, as required, 1 week in advance with the CIT project manager. Correct deficiencies as directed by Owner and provide a minimum of 99% good pairs, for backbone cables.\ G. Provide updated cable schedules with all deviations, including all change order, field authorizations, moves, adds and changes. Include all cable ID changes, panel and port changes in each TR, room number changes, etc. 3.7 IDENTIFICATION & RECORDS A. Confirm specific labeling requirements with customer’s project manager prior cable installation or termination, even if detailed in the T4 drawings. 1. Pathways (a) Coordinate and identify all communication pullboxes per 27 05 28. 2. TR Rooms and Equipment Spaces ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 20 OF 23 MARCH 29, 2013 ` (a) Coordinate and identify all communication racks and cabinet using a Letter designation (A,B,C etc.) as called on the T3 plans. (b) Coordinate and identify all communication patch panels using a Letter designation (A,B,C etc.) as called on the T3 plans and the cable schedules or as directed by the Owner (c) Coordinate and identify all voice patch panels using descriptor as designated by the Owner. These typically involved designators such as VPP-A, etc. 3. Cables (a) Label cables using the conventions identified in the cable schedules. The contractor shall review all labeling requirements before cable rough-in begins. (b) Provide written records in computer generated, table format for all cables, with the as-built drawings. (c) Update or generate cable schedules for all cable installed. (d) Update T2 drawings to reflect all field modifications and change orders. 4. Optical Fiber (a) Provide laser printed label for each fiber cable at the BDF, as directed by Owner. (b) The label shall be identical at both ends. 5. Station Outlets (a) Provide TIA 606-A compliant insert with clear plastic label cover on faceplates. Orient label and text per horizontal or vertical plate orientation and provide the maximum font size allowable. Align cable ID with specific modular jack and provide maximum fonts sizes and spacing between ID’s on the same label to provide desired alignment. (b) Provide a machine generated, preferably a laser printed, label in the insert. ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 21 OF 23 MARCH 29, 2013 ` (c) Labels shall match the cable identifier called for on the drawings, cable schedules and as depicted in the detail faceplate and outlet drawings. ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 22 OF 23 MARCH 29, 2013 ` Project Site: __________________________________ 1.1 BACKBONE COOPER CABLE TEST RECORD Date of test: ________________ Project Manager: _________________________ Cable Number:________Cable Count:_______From:_____________________To:____________________ Tested From:__________________________Tested To:____________________________(end locations) Testing Company:______________________________Technician:_____________________________ Splicing Company:_____________________________Cable Placement Company:__________________________ BACKBONE CABLING Pair Color Pair # Test Results Pair # Test Results Pair # Test Results Pair # Test Results BL-W ______01 26 51 76 O-W 2 27 52 77 GR-W 3 28 53 78 BR-W 4 29 54 79 SL-W 5 30 55 80 BL-R 6 31 56 81 O-R 7 32 57 82 GR-R 8 33 58 83 BR-R 9 34 59 84 SL-R 10 35 60 85 BL-BK 11 36 61 86 O-BK 12 37 62 87 GR-BK 13 38 63 88 BR-BK 14 39 64 89 SL-BK 15 40 65 90 BL-Y 16 41 66 91 O-Y 17 42 67 92 GR-Y 18 43 68 93 BR-Y 19 44 69 94 SL-Y 20 45 70 95 BL-V 21 46 71 96 O-V 22 47 72 97 GR-V 23 48 73 98 BR-V 24 49 74 99 SL-V 25 50 75 _____00 ARCHI-TECHNOLOGY CORNELL – NCP TESTING<IDENTIFICATION & ADMINISTRATION STANDARD SPECIFICATIONS 27 05 53 – PAGE 23 OF 23 MARCH 29, 2013 ` END OF SECTION TEST RESULTS – Abbreviations to use in the columns above: 1) Pair is Good = OK 5) Tip Ground =T.G. 2) Ring Side Open =R.S.O. 6) Shorted Pair =S.P. 3) Tip Side Open =T.S.O. 7) Split Pair=SPL (ex. For tip side of #5 and #17 =T.of#5w/T. of #17 4) Ring Ground =R.G. 8) Reverse Sides =REV