HomeMy WebLinkAbout26 05 26 GroundingBEARDSLEY DESIGN ASSOCIATES
CORNELL – NCP GROUNDING
STANDARD SPECIFICATIONS 26 05 26 – PAGE 1 of 5
MARCH 29, 2013
SECTION 260526 - GROUNDING
PART 1 GENERAL
1.1 RELATED DOCUMENTS
A. The Contract Drawings and the General Provisions of the Contract,
including the General Conditions of the Contract for Construction,
Supplementary Conditions, Special Conditions and Division 1
Specification Sections apply to the work of this Section.
B. The Work of Section 26 01 01 - Electrical Basic Materials and Methods
applies to the Work of this Section.
1.2 WORK INCLUDED:
A. Provide a complete, operating, tested, functioning, documented
grounding system including all work shown, specified, or required for
proper system operation.
B. All grounding and grounding circuitry shall equal or exceed the
requirements of NEC, latest issue, Article 250.
C. The raceway system which includes all metal conduit, wireways,
pullboxes, junction boxes, bus ducts, built-up enclosures, enclosures,
motor frames, etc., shall be made to form a continuous, conducting
permanent ground circuit of the lowest practical impedance to enhance
the safe conduction of ground fault currents and to prevent objectionable
differences in voltage between metal non-load current carrying parts of
the electrical system.
D. In addition to the raceway system ground, an additional green wire
ground shall be run in each raceway, sized for the largest circuit in the
raceway.
E. Telecommunications ground system consists of telecommunications
ground bar (TGB) in all ITR’s and MTR’s. Refer to drawing for TGB type
and location. Minimum #6 grounding riser between each ITR and MTR
per riser diagram on drawings. Bonding in each ITR and MTR shall be
from the TGB in each room to the following: network equipment racks
and cabinets, cable runways, cable trays, metallic cable sheaths and
raised floor system (if existing).
1.3 SUBMITTALS:
A. Provide product data for each type of ground bar and associated ground
lugs, at a minimum.
BEARDSLEY DESIGN ASSOCIATES
CORNELL – NCP GROUNDING
STANDARD SPECIFICATIONS 26 05 26 – PAGE 2 of 5
MARCH 29, 2013
1.4 DEFINITIONS:
A. Earth: interpreted as absolute ground, a theoretical location of zero
electrical potential.
B. Ground: interpreted as a made conducting connection to earth by
employing such devices as a driven metal rod, a buried metal plate, a
metallic water pipe, etc., or any multiple or combination of these devices,
and the conductors which may interconnect any of the foregoing.
C. System ground: interpreted as a low impedance made conducting
ground plane or system, with a conducting connection to ground,
established for the benefit of a particular electrical system or related
systems.
PART 2 PRODUCTS
2.1 CONDUCTORS:
A. All exposed grounding conductors such as bars, straps, cables, flexible
jumpers, braids, shunts, etc., shall be bare copper unless specifically
noted or approved otherwise.
B. Cable size shall be as required by NEC Code, Section 250, stranded, soft
drawn or soft annealed, unless otherwise shown on plans or specified.
C. Cable insulation type and color shall be as shown or as specified.
D. Manufacturer to be same as specified in Section 260101 - Basic Materials
and Methods.
2.2 CONNECTORS, CLAMPS, TERMINALS:
A. Mechanical connectors and clamps shall be silicon bronze.
B. Solderless compression terminals shall be copper, long-barrel, two-bolt.
C. Make: Anderson, Burndy, Penn-Union, T&B, approved for use intended.
2.3 SOLDER:
A. Solder prohibited for connections, except for high voltage cable metallic
tape shields.
2.4 MOLDED FUSION WELDS:
A. Process shall be "Cadweld," "Metalweld," "Thermoweld."
BEARDSLEY DESIGN ASSOCIATES
CORNELL – NCP GROUNDING
STANDARD SPECIFICATIONS 26 05 26 – PAGE 3 of 5
MARCH 29, 2013
2.5 HARDWARE:
A. All hardware shall be silicon bronze alloy.
B. Make: "Durium," "Everdur."
PART 3 EXECUTION
3.1 INSTALLATION, GENERAL:
A. Bare copper bars, cables, fittings, etc., shall not be installed in cinder fill
nor shall be covered with soil containing cinders or other corrosive
material.
B. Cables shall be installed with enough slack to prevent breaking stresses.
C. All grounding conductors subject to mechanical damage shall be
protected by rigid steel conduit or other suitable steel guards and in all
cases where so protected shall be permanently and effectively grounded
to said enclosure at each end of its length.
D. Where grounding conductors pass through floor slabs, walls, etc., and are
not encased in metal conduit, they shall be sleeved in fiber, or approved
non-metallic conduit.
E. All equipment ground bus, ground pads, frames, enclosures, etc., shall
have surfaces at point of connection thoroughly cleaned and brightened
just prior to actually making the connection. Touch-up damaged painted
surfaces.
F. Splices in wire or cable grounding conductors are prohibited.
3.2 INSTALLATION, RACEWAY SYSTEMS:
A. All metal supports, cable trays, messenger cables, frames, brackets,
races, etc., for any part of the raceway system, panels, switches, boxes,
starters, controls, etc., which are not rigidly secured to and in contact with
the raceway system, or which are subject to vibration and loosening, shall
be bonded to the raceway system, the size of the bonding conductor in
accordance with NEC Table 250-94.
B. Termination of rigid conduit at all boxes, cabinets, and enclosures shall
be made up tightly with a double locknut arrangement and a bushing,
bushings being of the insulated type where required by NEC.
C. Conduit which runs to or from all boxes, cabinets, or enclosures having
BEARDSLEY DESIGN ASSOCIATES
CORNELL – NCP GROUNDING
STANDARD SPECIFICATIONS 26 05 26 – PAGE 4 of 5
MARCH 29, 2013
concentric or eccentric knockouts which partially perforate the metal
around the conduit and hence impair the continuity of system ground
circuits shall be provided with bonding jumpers sized in accordance with
NEC Table 250-95 connected between a grounding type bushing/locknut
on the conduit and a ground bus or stud inside the box, cabinet, or
enclosure and attached thereto.
D. Conduit expansion joints and telescoping sections of metal raceways
shall be provided with bonding jumpers sized in accordance with NEC
Table 250-95.
E. Where flexible metallic conduit or liquid tight conduit is used, a bonding
jumper shall be provided, sized in accordance with NEC Table 250-95.
F. All non-metallic runs of conduit or raceway shall be provided with a
system ground conductor sized according to Table 250-95.
G. Where conduit enters or leaves any electrical enclosure with removable
coverplates, provide conduit grounding bushings and bonding jumpers
sized in accordance with NEC Table 250-95 between the grounding
bushings and the enclosure rigid frame or ground bus.
H. The ground conductors contained in the interstices of interlocked armor
cable shall be connected to ground at every splice and termination point.
3.3 INSTALLATION, ATTACHMENT TO STRUCTURAL STEEL:
A. Location of attachment bonds of ground conductors shall be at points not
subject to mechanical damage, but if possible where accessible for
inspection.
B. Attach preferably by molded fusion welding process.
C. Where welding is prohibited, attach by bolting, 7/16 inch hole in steel, 3/8
inch silicon bronze bolt, bolt end peened, steel surface bright and flat prior
to bolting, just prior to bolting contact surfaces lightly coated with Vaseline
or "NO-OX-ID-A Special."
3.4 INSTALLATION, SECONDARY ELECTRICAL SYSTEMS:
A. The neutral conductor of each and every low voltage, single or polyphase,
system or distribution system, except special isolated double insulated
systems, shall be solidly connected at one point only; at the main
secondary switchgear; to system ground and shall be sized for current
carrying capacity, not to be less than the following, which are listed in
preferential order:
a. As shown or specified.
b. As required by NEC, latest issue, Table 250-95.
BEARDSLEY DESIGN ASSOCIATES
CORNELL – NCP GROUNDING
STANDARD SPECIFICATIONS 26 05 26 – PAGE 5 of 5
MARCH 29, 2013
c. Not less than 25 percent of the transformer full load current or
main protective device rating, whichever is greater, based on
NEMA standard bus size.
B. Provide equipment grounding conductor, green colored insulation, with
phase conductors, to primary side of all transformers rated 600 volts or
less circuited to case and secondary neutral bushing, to motors, to motor
control equipment, and to all convenience outlets, insulation shall be
same type as phase conductors.
C. Transformer secondary neutral bushings shall also to be circuited to
nearest metallic water pipe, building steel, or ground rod.
END OF SECTION 26 05 26