HomeMy WebLinkAbout23 33 16 Fire DampersBEARDSLEY DESIGN ASSOCIATES
CORNELL – NCP FIRE DAMPERS
STANDARD SPECIFICATIONS 23 33 16 – PAGE 1 OF 4
MARCH 29, 2013
SECTION 233316 -- FIRE DAMPERS
PART 1 GENERAL
1.1 RELATED DOCUMENTS:
A. The Contract Drawings and the General Provisions of the Contract,
including the General Conditions of the Contract for Construction,
Supplementary Conditions, Special Conditions and Division 1
Specification Sections apply to the work of this Section.
B. The Work of the Section 23 01 00 - Mechanical Basic Materials and
Methods applies to the Work of this Section.
1.2 WORK INCLUDED:
A. Provide a complete, operating, tested, functioning, documented fire
damper and combination fire and smoke damper system including all
work shown, specified, or required for proper system operation.
1.3 SUBMITTALS:
A. Provide product data for each fire damper, combination fire and smoke
damper, relief grill, wall frame and media filter assembly.
B. Provide wiring diagrams: For power, signal, and control wiring.
PART 2 PRODUCTS
2.1 FIRE DAMPER AND SLEEVE ASSEMBLY:
A. 1- ½ hour U.L. classified static fire damper. Frame: 20 gauge galvanized
steel channel. 24 gauge galvanized curtain type blades outside
airstream, except when located behind grille where blades may be inside
airstream.
B. Provide 212 F fusible link.
C. Each fire damper shall include a steel sleeve of length to suit application
and retaining angles furnished by the damper manufacturer.
D. Provide space fusible links.
E. Manufacturer and Model: Ruskin, Air Balance Inc. or equal.
BEARDSLEY DESIGN ASSOCIATES
CORNELL – NCP FIRE DAMPERS
STANDARD SPECIFICATIONS 23 33 16 – PAGE 2 OF 4
MARCH 29, 2013
2.2 COMBINATION FIRE AND SMOKE DAMPERS:
A. 1-1/2 hour UL classified static combination fire and smoke damper. 16
gauge galvanized steel frame. 16 gauge galvanized multiple V-groove or
airfoil blade type. Class I leakage rating.
B. Heat-Responsive Device: 212° F Electric fuse link and switch package,
factory installed, rated.
C. Smoke Detector: Integral, factory wired for single-point connection.
D. Mounting Sleeve: Factory installed, galvanized sheet steel; length to
suite wall application.
E. Manufacturer: Ruskin Company, Greenheck Fan Corporation, Air
Balance Inc. or equal.
2.3 FIRE DAMPER /FIRE SMOKE DAMPER ACCESS DOOR:
A. Provide 12” x 12” minimum duct access door at location suitable to reset
curtain and replace fusible link or reset actuator. Duct access doors shall
be hinged one side. They shall be gasketed and shall include a minimum
of two camlock latches.
B. Enlarge access doors as required in large ducts or difficult to reach areas
so that a fusible link can be readily replaced.
PART 3 EXECUTION
3.1 FIRE DAMPERS AND COMBINATION FIRE AND SMOKE DAMPERS:
A. Install in strict accordance with the manufacturer's printed installation
instructions and with the locations and details shown on the Plans.
3.2 DUCT ACCESS DOORS:
A. Locate in the general locations shown on the Plans or adjacent to and
close enough to fire damper or combination fire smoke damper to allow
resetting the fire damper curtain and replacement of the fusible link. Mark
each access door "Fire Damper Access" in black permanent marker.
3.3 PRE-PUNCH LIST REVIEW:
A. The Contractor shall perform a pre-punch list review and shall verify the
following for each fire damper and combination fire and smoke damper:
1. Fire/smoke damper installed at each location shown on the Plans.
2. Installed in accordance with manufacturer's instructions.
3. Sleeve installed and fire/smoke damper anchored to sleeve
BEARDSLEY DESIGN ASSOCIATES
CORNELL – NCP FIRE DAMPERS
STANDARD SPECIFICATIONS 23 33 16 – PAGE 3 OF 4
MARCH 29, 2013
properly.
4. Angles anchored to sleeve and free floating in general
construction.
5. U.L. clearances between sleeve and general construction to avoid
binding damper in a fire due to expansion of the metal against a
tight opening.
6. Angles overlap general construction of opening by 1” minimum.
7. Duct access doors are installed and are located properly to allow
resetting damper curtain replacing fusible link.
8. Duct access doors are accessible through the general
construction.
3.4 ENGINEER'S ACCESSIBILITY TEST:
A. The Engineer shall, at his/her option, sever up to 5% of the fusible links on fire
dampers but in no case less than two or more than ten so that the Contractor can
demonstrate the ease with which the duct access doors allow re-setting of fire
dampers and replacement of fusible links.
B. The locations for these tests shall be at the sole discretion of the Engineer and
Owner.
C. The Contractor shall provide spare fusible links and shall demonstrate the
replacement of fusible links and re-setting of dampers.
D. If in the judgment of the Engineer, acting as the Owner's representative, the
access is not adequate to allow proper fire dampers servicing, the Contractor
shall install additional access doors as required to allow proper servicing of the
fire dampers.
3.5 SPARE FUSIBLE LINKS
A. Provide five (5) spare fusible links at each temperature rating. Submit to
Engineer and obtain a receipt.
END OF SECTION 23 33 16
BEARDSLEY DESIGN ASSOCIATES
CORNELL – NCP FIRE DAMPERS
STANDARD SPECIFICATIONS 23 33 16 – PAGE 4 OF 4
MARCH 29, 2013
[ PAGE LEFT INTENTIONALLY BLANK ]