HomeMy WebLinkAboutTeagle Hall, Ward Center_Electric Service Upgrades_DwgsCBCBCBCBSTANDSFPATHLETIC FIELDS/PSCOREBOARDCBCBCBCBCBCBCBCBCBCBCBCBCBCBCBCBCBCBCBCBCBCBCBCBCBCBCBCBSSS2121 2121212121 21212121212121 21 20202020211919191920202020212121212020201919191920202020212121212020201919191920202020212121212020201919191920202020212121212020201919191920202020212121212020201919CAMPUS ROADH O Y R O A D
COLLEGE AVEEAST AVEGARDEN AVENCORNELLUNIVERSITYFOUNDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FORANY PERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT ORENGINEER, TO ALTER THIS DOCUMENT IN ANYWAY. IF THIS DOCUMENT IS ALTERED, THEALTERING ARCHITECT OR ENGINEER SHALL AFFIXTO SUCH DOCUMENT HIS SEAL AND THENOTATION "ALTERED BY" FOLLOWED BY HISSIGNATURE, THE DATE OF SUCH ALTERATION,AND A SPECIFIC DESCRIPTION OF THEALTERATION.WARNING:Ithaca, New YorkDATE:FACILITY:DESIGN:DRAWN:ARCHIVE BAR CODEARCH/STRUCT:CIVIL/ENV:ELECTRICAL:MECHANICAL:Cornell UniversityIthaca, New YorkHumphreys Service Building; Ithaca, N.Y.Architectural & Structural, Civil &Environmental, Mechanical and ElectricalEngineeringFacilities EngineeringPROJECT SCOPETeagle Hall & Ward CenterT-001TITLE SHEETTeagle Hall & Ward Center Electric Service UpgradesFE DESIGNmps2061, 2611APRIL 24, 20179569712Teagle Hall & Ward Center ElectricService UpgradesDRAWING LISTT-001 TITLE SHEETE-000 SCOPE OF WORK, GENERAL NOTES, SYMBOLOGY, ABBREVIATIONS AND SCHEDULESE-100 WARD CENTER EXISTING AND PHASE 1 ELECTRICAL WORK PLANSE-101 WARD CENTER PHASES 2 AND 3 ELECTRICAL WORK PLANSE-102 WARD CENTER DETAILSE-200 TEAGLE HALL EXISTING AND PHASE 1 ELECTRIC WORK PLANSE-201 TEAGLE HALL PHASES 2 AND 3 ELECTRIC WORK PLANSE-202 TEAGLE HALL PHASE 4 WORK PLAN AND DETAILSE-203 TEAGLE HALL LIGHTING & GROUNDING PLANSE-204 TEAGLE HALL DETAILSE-300 TEAGLE HALL ISOMETRIC PLANSProvide electric service upgrades for Teagle Hall andWard Center including new transformers, primary switches andtransformer secondary protection.WARD CENTERSITE PLAN - TEAGLE HALL & WARD CENTERTEAGLEHALLREVISIONS1 3/2/17 ISSUE FOR DD REVIEW2 4/3/17 ISSUE FOR 75% CD REVIEW3 4/12/17 ISSUE FOR COORDINATED REVIEW4 4/24/16 ISSUE FOR CONSTRUCTION
NCORNELLUNIVERSITYFOUNDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FORANY PERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT ORENGINEER, TO ALTER THIS DOCUMENT IN ANYWAY. IF THIS DOCUMENT IS ALTERED, THEALTERING ARCHITECT OR ENGINEER SHALL AFFIXTO SUCH DOCUMENT HIS SEAL AND THENOTATION "ALTERED BY" FOLLOWED BY HISSIGNATURE, THE DATE OF SUCH ALTERATION,AND A SPECIFIC DESCRIPTION OF THEALTERATION.WARNING:Ithaca, New YorkDATE:FACILITY:DESIGN:DRAWN:ARCHIVE BAR CODEARCH/STRUCT:CIVIL/ENV:ELECTRICAL:MECHANICAL:Teagle Hall & Ward CenterE-000SCOPE OF WORK,GENERAL NOTES,SYMBOLOGY,ABBREVIATIONSAND SCHEDULESTeagle Hall & Ward Center Electric Service UpgradesE. REICHARDmps2061,2611APRIL 24, 20179569712ELECTRICAL LEGENDLIGHTING LEGENDDEMOLITION KEYED NOTECONSTRUCTION KEYED NOTEMOTOR1'x4' LUMINAIREHARDWIRED EQUIPMENT CONNECTIONP-1A12HOMERUN TO PANEL P-1A, CIRCUIT #12. FEDFROM 20A - 1P BREAKER IS INTENDED UNLESSNOTED OTHERWISE. RUN GREEN WIRE GROUNDFOR ALL CIRCUITS. PROVIDE ONE GROUND PERCIRCUIT.EMERGENCY POWER OFF (EPO)GROUND ROD ELECTRODEDUPLEX RECEPTACLE WITH GFCI PROTECTIONDUPLEX RECEPTACLE WITH AFCI PROTECTIONQUAD RECEPTACLELINETYPES LEGEND##SPECIAL RECEPTACLE5-30RPANELBOARDJUNCTION BOXB = INSTALLED IN BASEBOARDTR = INSTALLED IN WOOD TRIM/CASEWORK/WAINSCOTTSR = SURFACE RACEWAYWP = WEATHERPROOFAC = AIR CONDITIONERXDUPLEX RECEPTACLE:DOUBLE DUPLEX RECEPTACLEMOTOR STARTERJ2'x4' LUMINAIRECEILING MOUNTED LUMINAIREEM LIGHTING BATTERY UNITCOMBO EXIT SIGN/EM LIGHTING BATTERY UNITSINGLE FACE, WALL MOUNT EXIT SIGNDOUBLE FACE, WALL MOUNT EXIT SIGNSINGLE FACE, CEILING MOUNT EXIT SIGNDOUBLE FACE, CEILING MOUNT EXIT SIGNLIGHT SWITCH:SAFETY SWITCH (NON-FUSED)SAFETY SWITCH (FUSED)X3 = 3-WAY SWITCH4 = 4-WAY SWITCHD = DIMMER SWITCHO = WALL SWITCH OCCUPANCY SENSORV = WALL SWITCH VACANCY SENSORW = WIRELESS SWITCHS = WIRELESS SCENE SWITCHWIRELESS OCCUPANCY SENSORWIRELESS DAYLIGHT SENSOROSWDS1'x2' LUMINAIREFIRE ALARM LEGENDFIRE ALARM CONTROL PANELBATTERY CABINETWATER FLOW SWITCHMUXPADREMOTE ANNUNCIATORD = DUCT SMOKE DETECTORR = RELAY BASEBR = BEAM RECEIVERBT = BEAM TRANSMITTERSB = SOUNDER BASESMOKE DETECTOR:TAMPER SWITCHAUDIBLE NOTIFICATION APPLIANCEFACPBATTMUXFAANAC PANELNACMANUAL PULL STATIONFSXF = FIXED TEMPERATURER = RATE OF RISER/F = COMBINATION RISE/FIXED TEMPERATUREHEAT DETECTOR:HXCARBON MONOXIDE DETECTORCOAMFXXcdCFSFSXXcdCTSADDRESSABLE MODULEXXcd = CANDELAC = CEILINGCOMBO A/V NOTIFIFICATION APPLIANCE:XXcd = CANDELAC = CEILINGVISUAL NOTIFICATION APPLIANCE:SUPPRESSION SYSTEMGENERAL SYMBOLS LEGENDEXTERIOR ELEVATION1111E-100E-1001111INTERIOR ELEVATION1E-100BUILDING SECTION1E-100ENLARGED DETAILELECTRICAL ABBREVIATIONSAC AIR CONDITIONERAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAFI ARC FAULT INTERRUPTERAMM ADDRESSABLE MONITOR MODULEAOM ADDRESSABLE OUTPUT MODULEARB AUXILIARY RELAY BOARDATS AUTOMATIC TRANSFER SWITCHB BASEBOARDBKR BREAKERC CONDUITCD CANDELACKT CIRCUITCR CONTROL RELAYEC ELECTRICAL CONTRACTOREMT ELECTRICAL METALLIC TUBINGEPO EMERGENCY POWER OFF STATIONFAA FIRE ALARM ANNUNCIATOR PANELFACP FIRE ALARM CONTROL PANELFSD FIRE SMOKE DAMPERGAA GENERATOR ALARM ANNUNCIATORGFI GROUND FAULT INTERRUPTERGND GROUNDHP HORSEPOWERKW KILOWATTLC LIGHTING CONTACTORLFMC LIQUID TIGHT FLEXIBLE METALLIC CONDUITLTG LIGHTINGMCB MAIN CIRCUIT BREAKERMLO MAIN LUG ONLYMTS MANUAL TRANSFER SWITCHNAC NOTIFICATION APPLIANCE CIRCUITNIC NOT IN CONTRACTOE OVERHEAD ELECTRICPC PHOTOCELLPM PLUGMOLDPP POWER PANELPVC POLYVINYL CHLORIDE CONDUITRGS RIGID GALVANIZED STEEL CONDUITSR SURFACE RACEWAYST SHUNT TRIPTM THERMAL MAGNETICTR TRIM/CASEWORK/WAINSCOTTTSP TWISTED SHIELDED PAIRTYP TYPICALUE UNDERGROUND ELECTRICUON UNLESS OTHERWISE NOTEDUPS UNINTERRUPTIBLE POWER SUPPLYV VOLTSVA VOLT AMPSWP WATERPROOFUNDERGROUND ELECTRICUEUNDERGROUND LIGHTINGULOVERHEAD ELECTRICOETO BE PROVIDEDDEMOLITION / TO BE RELOCATEDEXISTING TO REMAINUNDERGROUND TELCOUCMOUNTING HEIGHTSCARD READER 48" TOP OF BOXLIGHT SWITCH 48" TOP OF BOXRECEPTACLE 18" TOP OF BOXDATA OUTLET 18" TOP OF BOXTV OUTLET 84" TOP OF BOXPHONE OUTLET 48" TOP OF BOXSAFETY SWITCH 60" CENTERLINE OF HANDLEMOTOR STARTER 60" CENTERLINE OF HANDLEPANELBOARD 72" TOP OF PANELBOARDMANUAL PULL STATION 48" OPERABLE HANDLENOTIFICATION APPLIANCE 80" BOTTOM OF LENSDOOR HOLD OPEN COORDINATE IN FIELDEM BATTERY UNIT 96" BOTTOM OF UNITEM REMOTE UNIT 102" BOTTOM OF UNITEXIT SIGN 96" BOTTOM OF UNITGENERAL NOTES1.0 ELECTRICAL SCHEMATICS INDICATED ON CONTRACT DOCUMENTS AREDIAGRAMMATIC. IT IS NOT THE INTENT TO SHOW EXACT OR MOST EFFICIENTROUTING. VERIFY ALL DIMENSIONS AND FIELD CONDITIONS ON SITE. ANYCONFLICTS BETWEEN CONSTRUCTION DOCUMENTS AND FIELD CONDITIONS SHALLBE BROUGHT TO CORNELL'S PROJECT MANAGER FOR RESOLUTION BEFORE WORKPROCEEDS.2.0 ASSURE PUBLIC AND WORKER SAFETY AT ALL TIMES. PROTECT ADJOINING AREASFROM DAMAGE AND DUST. REMOVE ALL DEBRIS FROM SITE AND DISPOSE OFWASTE MATERIAL IN A SAFE MANNER. KEEP THE PREMISES FREE OF DEBRIS FROMTHE EXECUTION OF WORK. DELIVER A FINAL PRODUCT THAT IS CLEAN ANDOPERABLE.3.0 FIRE STOP ELECTRICAL PENETRATIONS THROUGH FIRE RATED WALLS AND/ORFLOORS WITH MATERIAL EQUAL IN RATING TO THE CONSTRUCTION OF THEMATERIAL PENETRATED.4.0 WORK SHALL BE COMPLETED AS SPECIFIED AND INDICATED ON CONTRACTDOCUMENTS. ANY SUGGESTED ALTERNATE MANUFACTURER OR METHOD OFINSTALLATION SHALL BE SUBMITTED TO PROJECT ENGINEER FOR APPROVAL PRIORTO ORDERING ANY MATERIALS OR COMMENCING EXECUTION OF WORK.5.0 GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLE 250. PROVIDEEQUIPMENT GROUND CONDUCTOR WITH EACH BRANCH CIRCUIT INDICATED ONCONTRACT DOCUMENTS. EQUIPMENT GROUND CONDUCTOR SHALL BE ROUTEDWITH ASSOCIATED PHASE CONDUCTORS.6.0 PROVIDE A NEW TYPED PANELBOARD DIRECTORY FOR EACH PANELBOARD. LABELALL NEW DEVICE FACEPLATES WITH SOURCE AND CIRCUIT NUMBER. PROVIDEPERMANENT LABEL ON SWITCHING DEVICES INDICATING EQUIPMENT SERVICE ANDINVENTORY NUMBERS. COORDINATE EQUIPMENT INVENTORY NUMBERS WITHCORNELL UNIVERSITY'S MECHANICAL SHOP, 255-8667.7.0 CIRCUITS RATED 20-AMP, 120 VOLT SHALL CONTAIN SEPARATE NEUTRALCONDUCTORS.8.0 CONDUCTORS SHALL BE A MINIMUM OF 12AWG, STRANDED COPPER, 600VAC, 90DEGREE C, TYPE THHN/THWN-2 FOR DRY AREAS AND XHHW/THWN-2 FOR WETAREAS.9.0 CONDUITS SHALL BE A MINIMUM OF 3/4 INCHES DIAMETER. CONDUITS SHALL BEELECTRICAL METALLIC TUBING (EMT) AND SURFACE MOUNTED UNLESS NOTEDOTHERWISE.10.0 AIC RATING OF NEW CIRCUIT BREAKERS SHALL MATCH RATING OF RESPECTIVEPANELBOARD. SIZE AS INDICATED.11.0 PROVIDE PULL STRING THROUGH NEW CONDUIT AND BOXES. PROVIDE SUPPORTHANGERS FOR CONDUIT AS NEEDED.12.0 INSTALL RACEWAY SYSTEMS ENSURING PROPER ACCESS TO EQUIPMENT ANDDEVICES, AND WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE ANDREPAIR. RACEWAYS THAT ARE NOT INSTALLED WITH THIS REQUIREMENT IN MINDSHALL BE RELOCATED AT NO EXPENSE TO THE OWNER UNTIL DEFICIENCIES ARECORRECTED.13.0 CONTACT DIG SAFELY NEW YORK (1-800-962-7962) AND CORNELL FACILITIES (CHUCKPORTER 607-255-6646) FOR UNDEGROUND UTILITY LOCATING PRIOR TO ALLUNDERGROUND WORK BEING PERFORMED.SCOPE OF WORK1.0 PROVIDE ELECTRIC SERVICE UPGRADES FOR TEAGLE HALL AND WARD CENTERINCLUDING NEW TRANSFORMERS, PRIMARY SWITCHES AND TRANSFORMERSECONDARY PROTECTION.REVISIONS1 3/2/17 ISSUE FOR DD REVIEW2 4/3/17 ISSUE FOR 75% CD REVIEW3 4/12/17 ISSUE FOR COORDINATED REVIEW4 4/24/16 ISSUE FOR CONSTRUCTIONLUMINAIRE SCHEDULETYPE DESCRIPTION MOUNTING SIZE MANUFACTURER CATALOG NO. VOLTAGE DRIVER LUMENS WATTAGE COLOR TEMP NOTESA1 4 FT LINEAR SURFACEMOUNTED INDUSTRIAL LEDSURFACE 46.5"X1.5"X2" LITHONIA MNSL MV M6 120/277 ELECTRONIC 2100 24 4000KA2 2 FT WALL MOUNTED SURFACE 24"X4.75"X3.75" LITHONIA WL2 08L MVOLT LP835NESPDT7 SC120/277 ELECTRONIC 800 7.5 3500KEM EMERGENCY WALL PACK SURFACE 12"X4.5"X3" SIMKAR DLMW-SD 120/277 - - 1.6 - SELFDIAGNOSTICSDOOR / HARDWARE SCHEDULEDOORDOOR FRAMEFIRE RATINGUNEVEN PAIR 3'-0" ACTIVE X 2'-0" NON ACTIVEHARDWAREPANEL SIZEMATERIALMATERIALHINGES MCKINNEY TA2714 X 4 1/2" X 4 1/2" X 26D X NRPSELF LATCHING FLUSH BOLTS DCI 845 METAL DOORLOCKSET SARGENT 8237 X LNL X 26DSARGENT 12-8913 x F x ETL x LHRB x 26D x 36"RESTRICTED CYLINDER PROVIDED BY THE CORNELL UNIVERSITY LOCKS SHOPDOOR COORDINATORS DCI # 600MOUNTING BRACKET DCI 600D SERIESCLOSER SARGENT 351 X U X ENSILENCERS DCI 8SWIDTHHEIGHTTHICKNESSB00UB 5' - 0" 7' - 0" 1 3/4" HM HM 1.5 HR Y 6 1 1 1 1 2 2B00UC 5' - 0" 7' - 0" 1 3/4" HM HM 3 HR Y 6 1 1 1 2 2
B09B11B17DN120/208V, 1000 AMPSWITCHBOARD480V, 200 AMPDISCONNECT SWITCHESWIREWAY208V BUS DUCTEXISTING13.2kV, 400ASWITCH TO BEUSED ASJUNCTION BOXEXISTING 13.2KV/480V/208VTRANSFORMER BANK WITHPCB CONTAINING OILEXISTING13.2KV SWITCHEXISTING 200A, 480V 3ØDISCONNECT SWITCHES1000A, 120/208V SWITCHBOARDPRI: 13.2KVSEC: 480VPRI: 13.2KVSEC: 208V600A/3P600A/3P600A/3P600A/3P600A/3P225A/3P800A/3P750KVAEXISTING BUS DUCTTO MH 65SWITCH 65ATOANNABELTAYLORSPTOMH65BSWITCHEXISTING 480VDISCONNECTSWITCHES1000A, 120/208V SWITCHBOARDPRI: 13.2KVSEC: 480VPRI: 13.2KVSEC: 208VTX-1FM APPROVED225 KVA13.2 KV:208/120V750KVA600A/3P600A/3P600A/3P600A/3P225A/3P600A/3P800A/3P800A, 208V, 3ØENCLOSEDCIRCUITBREAKER CB-118 KAIC MIN100A, 480V, 3ØENCLOSEDCIRCUITBREAKER CB-410 KAIC MIN100A, 480V, 3ØENCLOSEDCIRCUITBREAKER CB-310 KAIC MINEXISTING BUS DUCTEXISTING13.2KV SWITCHTO MH 65SWITCH 65ATOANNABELTAYLORSPTOMH65BSWITCH1891011121314999150A, 208V, 3ØENCLOSEDCIRCUIT BREAKERCB-2 18 KAIC MINTX-245 KVAPRI: 208VSEC: 480V1324-#1/0'S & 1-#6GND IN 2" RMC2 SETS OF 4-#600 &1-#1/0 GND IN 4" RMC4-#1/0'S & 1-#6GND IN 2" EMT4-#3 and 1-#8GNDin 1-1/2" EMT4-#3 & 1-#8GNDIN 1-1/2" EMT3-#2/0 AND 1-#2/0GND IN 4" RMCJUNCTION BOXJUNCTION BOXCASCADILLA CREEKWARDCENTERAREA OF WORK120/208V, 1600 AmpSwitchboard120/208V, 1000 AMPSWITCHBOARD480V, 200 AMPDISCONNECTSWITCHESEXISTINGWIREWAYEXISTING 208V BUS DUCTEXISTING13.2kV SWITCHTO BE USED ASJUNCTION BOXFM APPROVEDNEW OIL-FILLED13.2kV-120/208VTRANSFORMER45KVA 208V-480VTRANSFORMEREXISTINGWIREWAYNEW WIREWAYB09B11B17100A, 480V ENCLOSEDCIRCUIT BREAKERS CB-3, CB-4800A, 208V, 3Ø ENCLOSEDCIRCUIT BREAKER CB-150A, 208V, 3Ø ENCLOSEDCIRCUIT BREAKER CB-2CONCRETE PAD6" BOLLARDSTYPICAL1234578TX-29996TX-11011121314NCORNELLUNIVERSITYFOUNDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FORANY PERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT ORENGINEER, TO ALTER THIS DOCUMENT IN ANYWAY. IF THIS DOCUMENT IS ALTERED, THEALTERING ARCHITECT OR ENGINEER SHALL AFFIXTO SUCH DOCUMENT HIS SEAL AND THENOTATION "ALTERED BY" FOLLOWED BY HISSIGNATURE, THE DATE OF SUCH ALTERATION,AND A SPECIFIC DESCRIPTION OF THEALTERATION.WARNING:Ithaca, New YorkDATE:FACILITY:DESIGN:DRAWN:ARCHIVE BAR CODEARCH/STRUCT:CIVIL/ENV:ELECTRICAL:MECHANICAL:Teagle Hall & Ward CenterE-100WARD CENTEREXISTING ANDPHASE 1ELECTRICALWORK PLANSTeagle Hall & Ward Center Electric Service UpgradesE. REICHARDmps2061APRIL 24, 20179569712SCALE: 1/4" = 1'-0"1WARD PARTIAL BASEMENT POWER PLAN - EXISTINGREVISIONS1 3/2/17 ISSUE FOR DD REVIEW2 4/3/17 ISSUE FOR 75% CD REVIEW3 4/12/17 ISSUE FOR COORDINATED REVIEW4 4/24/16 ISSUE FOR CONSTRUCTION0 2 4 8SCALE: 1/4"=1'-0"0 2 4 8SCALE: 1/4"=1'-0"SCALE: NO SCALE2WARD PARTIAL ONE-LINE DIAGRAM - EXISTINGSCALE: NO SCALE4WARD PARTIAL ONE-LINE DIAGRAM - PHASE 1WARD CENTER KEY PLANE-100 PHASE 1 - KEYED NOTES1 PROVIDE 225KVA, 13.2KV/208Y TRANSFORMER TX-1 ON CONCRETE PAD IN LOCATIONINDICATED.2 PROVIDE TWO (2) 24”X24”X12” WEATHERPROOF JUNCTION BOXES ON EXTERIORWALL.3 PROVIDE CONDUIT DUCT BANK FROM TRANSFORMER TO JUNCTION BOXES IN THEAREAWAY IN LOCATION INDICATED. SAW CUT PAVEMENT TO ROUTE THE CONDUITDUCTBANK. BACKFILL AND PATCH THE PAVEMENT.4 PROVIDE 6” CONCRETE BOLLARDS IN LOCATIONS INDICATED.5 PROVIDE CONDUITS ALONG WALL, CORE THROUGH WALL ABOVE THE DOOR ANDINSTALL CONDUIT INTO THE ELECTRICAL ROOM IN FRONT OF SWITCH.6 PROVIDE TEMPORARY PLYWOOD BARRIER FOR TRANSFORMER BANK. BARRIERSHALL EXTEND ENTIRELY AROUND TRANSFORMERS AND 2 FEET ABOVE EXPOSEDBUSHINGS.7 PROVIDE CABLE TRAY IN LOCATION INDICATED. MOUNT FROM CEILING AND EXTENDFROM THE END OF THE EXISTING CABLE TRAY.8 PROVIDE 45KVA TRANSFORMER TX-2 AND CONCRETE PAD.9 PROVIDE ENCLOSED CIRCUIT BREAKERS CB-1, CB-2, CB-3, CB-4 IN LOCATIONSSHOWN.10 PROVIDE LOW VOLTAGE CONDUITS FROM ABOVE DOOR TO THE CABLE TRAY ANDFROM CABLE TRAY TO ENCLOSURES FOR CIRCUIT BREAKERS CB-1 AND CB-2.PROVIDE CONDUCTORS FROM TRANSFORMER TX-1 SECONDARY TO ENCLOSEDCIRCUIT BREAKERS CB-1 AND CB-2 VIA CONDUIT AND CABLE TRAY ROUTING.11 PROVIDE CONDUIT AND CONDUCTORS FROM ENCLOSED CIRCUIT BREAKER CB-2 TOTRANSFORMER TX-2 PRIMARY.12 PROVIDE CONDUIT AND CONDUCTORS FROM TRANSFORMER TX-2 SECONDARY TOENCLOSED CIRCUIT BREAKERS CB-3 AND CB-4.13 PROVIDE CONDUIT FROM ENCLOSED CIRCUIT BREAKERS CB-3 AND CB-4 UP WALL TOTHE EXISTING CABLE TRAY. EXISTING CONDUCTORS FROM THE TRANSFORMERSECONDARY TO THE 480V DISCONNECT SWITCHES WILL BE RECONNECTED TO THEENCLOSED CIRCUIT BREAKERS TO FEED THE EXISTING DISCONNECT SWITCHESDURING THE SHUTDOWN IN CONSTRUCTION PHASE 2 (SEE E-101).14 PROVIDE 15KV CONDUCTORS FROM TRANSFORMER TX-1 THROUGH JUNCTION BOXAND INTO THE ELECTRIC ROOM, LEAVING SLACK IN THE JUNCTION BOX. PROVIDEDEAD BREAK ELBOW CONNECTIONS AT THE TRANSFORMER. COIL ENOUGHCONDUCTOR LENGTH FOR SPLICING BY THE CORNELL LINE CREW INSIDE OF THEEXISTING SWITCH.#E-100 GENERAL NOTES1.0 REFER TO ONELINE DIAGRAMS FOR ALL CONDUIT AND CONDUCTOR SIZES.2.0 CONTRACTOR TO VERIFY EXISTING PHASE ROTATION (CW OR CCW).SCALE: 1/4" = 1'-0"3WARD PARTIAL BASEMENT POWER PLAN - PHASE 1
1000A, 120/208V SWITCHBOARDTX-1FM APPROVED225 KVA13.2 KV:208/120V600A/3P600A/3P600A/3P600A/3P225A/3P600A/3P800A/3P150A, 208V, 3ØENCLOSED CIRCUITBREAKER CB-2800A, 208V, 3ØENCLOSED CIRCUITBREAKER CB-1EXISTING 200A, 480V 3ØDISCONNECT SWITCHESEXISTING 13.2KV SWITCHTO BE USED AS JUNCTION BOX.CONNECTIONS TO BE MADE BYCORNELL LINE CREWEXISTING BUS DUCTTO MH 65SWITCH 65ATOANNABELTAYLORSPTOMH65BSWITCH1PRI: 13.2KVSEC: 480VPRI: 13.2KVSEC: 208V750KVA23246100A, 480V, 3ØENCLOSEDCIRCUITBREAKER CB-43-#2/0 AND 1-#6G IN 4" RMC2 SETS OF 4-600'S AND 1-#1/0GIN 4" EMT (TO CABLE TRAY)TX-245 KVAPRI: 208VSEC: 480V100A, 480V, 3ØENCLOSEDCIRCUITBREAKER CB-3JUNCTION BOXJUNCTION BOX55CASCADILLA CREEKWARDCENTERAREA OF WORK120/208V, 1600 AmpSwitchboard480V, 200 AmpDisconnect Switches120/208V, 1000 AMPSWITCHBOARD480V, 200 AmpDISCONNECTSWITCHESEXISTINGWIREWAYEXISTING 208VBUS DUCTEXISTING13.2kV SWITCHTO BE USED ASJUNCTION BOX45KVA 208V-480VTRANSFORMEREXISTINGWIREWAYB09B11B17100A, 480V ENCLOSEDCIRCUIT BREAKERS CB-3, CB-4800A, 208V, 3Ø ENCLOSEDCIRCUIT BREAKER CB-1150A, 208V, 3ØENCLOSED CIRCUITBREAKER CB-2CONCRETE PAD7TX-2FM APPROVEDNEW OIL-FILLED13.2kV-120/208VTRANSFORMERTX-1480V, 200 AmpDisconnect Switches120/208V, 1000 AMPSWITCHBOARD480V, 200 AmpDISCONNECTSWITCHESEXISTINGWIREWAYEXISTING 208VBUS DUCTEXISTING13.2kV SWITCHTO BE USED ASJUNCTION BOX45KVA 208V-480VTRANSFORMER TX-2EXISTINGWIREWAYB09B11B17CONCRETE PAD42133434A2A2A2100A, 480V ENCLOSEDCIRCUIT BREAKERS CB-3, CB-4800A, 208V, 3Ø ENCLOSEDCIRCUIT BREAKER CB-1150A, 208V, 3Ø ENCLOSEDCIRCUIT BREAKER CB-2FM APPROVEDNEW OIL-FILLED13.2kV-120/208VTRANSFORMERTX-11000A, 120/208V SWITCHBOARDTX-245 KVAPRI: 208VSEC: 480V600A/3P600A/3P600A/3P600A/3P225A/3P600A/3P800A/3P150A, 208V, 3ØENCLOSED CIRCUITBREAKER CB-2100A, 480V, 3ØENCLOSED CIRCUITBREAKER CB-4100A, 480V, 3ØENCLOSED CIRCUITBREAKER CB-3EXISTING 200A, 480V 3ØDISCONNECT SWITCHESEXISTING13.2KV SWITCHTO BE USED ASJUNCTION BOXEXISTING BUS DUCTTO MH 65SWITCH 65ATOANNABELTAYLORSPTOMH65BSWITCHPRI: 13.2KVSEC: 480VPRI: 13.2KVSEC: 208V750KVATX-1FM APPROVED225 KVA13.2 KV:208/120V800A, 208V, 3ØENCLOSED CIRCUITBREAKER CB-12JUNCTION BOXJUNCTION BOXNCORNELLUNIVERSITYFOUNDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FORANY PERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT ORENGINEER, TO ALTER THIS DOCUMENT IN ANYWAY. IF THIS DOCUMENT IS ALTERED, THEALTERING ARCHITECT OR ENGINEER SHALL AFFIXTO SUCH DOCUMENT HIS SEAL AND THENOTATION "ALTERED BY" FOLLOWED BY HISSIGNATURE, THE DATE OF SUCH ALTERATION,AND A SPECIFIC DESCRIPTION OF THEALTERATION.WARNING:Ithaca, New YorkDATE:FACILITY:DESIGN:DRAWN:ARCHIVE BAR CODEARCH/STRUCT:CIVIL/ENV:ELECTRICAL:MECHANICAL:Teagle Hall & Ward CenterE-101WARD CENTERPHASES 2 AND 3ELECTRICALWORK PLANSTeagle Hall & Ward Center Electric Service UpgradesE. REICHARDmps2061APRIL 24, 20179569712REVISIONS1 3/2/17 ISSUE FOR DD REVIEW2 4/3/17 ISSUE FOR 75% CD REVIEW3 4/12/17 ISSUE FOR COORDINATED REVIEW4 4/24/16 ISSUE FOR CONSTRUCTIONSCALE: NO SCALE2WARD PARTIAL ONE-LINE DIAGRAM - PHASE 2WARD CENTER KEY PLANE-101 PHASE 2 - KEYED NOTES1 CORNELL LINE CREW TO OPEN THE FEEDER FOR WARD CENTER ON SWITCH 65A ATMANHOLE 65. SHUTDOWN DURATION – 4 TO 8 HOURS.2 DISCONNECT AND REMOVE PRIMARY AND SECONDARY CONDUCTORS FROM THEEXISTING TRANSFORMER BANK. REMOVE SECONDARY CONDUCTORS FROM THE208V BUS DUCT. SAVE THE CONDUCTORS FEEDING THE 480V DISCONNECTS ANDROUTE THEM INTO THE CONDUITS PREVIOUSLY INSTALLED TO ENCLOSED CIRCUITBREAKERS CB-3 AND CB-4.3 CORNELL LINE CREW TO PROVIDE CONDUIT ELBOW AT THE EXISTING SWITCH ANDPULL COILED 15KV CABLE INTO SWITCH. CORNELL LINE CREW TO SPLICE THEFEEDER IN THE EXISTING SWITCH TO THE 15KV CABLE FEEDING THE TRANSFORMERTX-1.4 PROVIDE CONDUCTORS FROM LOAD SIDE OF ENCLOSED CIRCUIT BREAKER CB-1THROUGH CONDUIT AND INTO CABLE TRAY. TERMINATE CONDUCTORS TO THEEXISTING LUG CONNECTION IN THE 208V BUS DUCT.5 CONTRACTOR TO VERIFY PHASE ROTATION. IF ROTATION IS VERIFIED CORRECTLY,CONTRACTOR TO CLOSE CB-1. IF NECESSARY, CORNELL LINE CREW TO SWAPCABLES ON PRIMARY SIDE OF TX-1.6 CORNELL LINE CREW SHALL CLOSE THE SWITCHWAY IN MANHOLE 65 FOR THEFEEDER TO WARD CENTER, THEN CLOSE SWITCHWAY AND ENERGIZE THETRANSFORMER TX-1.7 CONTACT CORNELL EHS TO SAMPLE TRANSFORMERS PRIOR TO DISPOSAL. TESTINGRESULTS WILL REQUIRE A MINIMUM OF 2 WEEKS.E-101 PHASE 3 - KEYED NOTES1 REMOVE EXISTING CMU IN FRONT OF DOOR TO FACILITATE REMOVAL OF EXISTINGTRANSFORMERS. AFTER REMOVAL, PROVIDE CMU IN PLACE WHERE PREVIOUSLYREMOVED.2 PROVIDE REMOVAL OF PCB TRANSFORMER OIL AND REMOVE THREE EXISTING250KVA TRANSFORMERS AND COORDINATE THE DISPOSAL OF THE TRANSFORMERSWITH AN APPROVED ENVIRONMENTAL SERVICE PROVIDER. REMOVAL PROCESSMUST BE WITNESSED BY CORNELL ENVIRONMENTAL HEALTH AND SAFETY.3 DISCONNECT AND REMOVE EXISTING WALL MOUNTED LIGHT FIXTURES; EXISTINGCONDUIT, CONDUCTORS AND JUNCTION BOXES TO REMAIN.4 PROVIDE WALL MOUNTED LIGHT FIXTURE IN LOCATION INDICATED AT 7’ AFF.MODIFY/EXTEND EXISTING BRANCH CIRCUIT AND RECONNECT. MATCH EXISTINGWIRE AND CONDUIT.##SCALE: 1/4" = 1'-0"1WARD PARTIAL BASEMENT POWER PLAN - PHASE 20 2 4 8SCALE: 1/4"=1'-0"0 2 4 8SCALE: 1/4"=1'-0"SCALE: 1/4" = 1'-0"3WARD PARTIAL BASEMENT POWER PLAN - PHASE 3SCALE: NO SCALE4WARD PARTIAL ONE-LINE DIAGRAM - PHASE 3
5/8" X 8' COPPER GROUNDROD. TOP OF ROD 1'-0"BELOW GRADE, TYPICAL#4 BARS 12" O.C.EACH WAY2#4 BARS ALL AROUND PERIMETER 18" 10"#3/0 BARE STRANDED COPPERGROUNDING CONDUCTOR, TYPICAL.CONNECT TO GROUND PAD INTRANSFORMER.PORTION OF OPENINGFOR PRIMARY CONDUITSPORTION OF OPENINGFOR SECONDARY CONDUITSNYSDOT 304.12 TYPE 2 SUB-BASEUNDISTURBED OR COMPACTEDSUB-GRADE 6 " 6 " 54" 3 1/2" 17" 75" 68"NOTES:1.CONCRETE 4500 PSI @ 28 DAYS, W/C = 0.45, AIR = 6 +/-1%2.DEFORMED BARS - ASTM A-615, GRADE 40.3.TOP SURFACE SHALL BE TROWEL FINISHED.4.3/4 " CHAMFER ALL EXPOSED EDGES, INCLUDING OPENING.5.VERIFY ALL DIMENSIONS BASED ON APPROVED SHOP DRAWINGS.6.PROVIDE GROUNDING PER 2/E-102.SAW CUT ACROSS EXISTING ROADWAYS,SIDEWALKS AND/OR PARKING LOTS.FINAL GRADEROADWAY - REFER TO DETAIL 4/E-102.GRASS-RESEEDTOP SOIL - 6" MINIMUMCOMPACTED DEPTHTRACEABLE ELECTRICWARNING TAPE, 12"BELOW GRADECOMPACTED, NATIVE BACKFILL(TRENCH SPOIL) THAT IS CLEAN,UNIFORM, AND FREE OF DEBRIS (NOSTONES LARGER THAN 2")RMC CONDUIT - REFER TO PLANSFOR SIZE AND QUANTITYUNDISTURBED SOILSEAL ALL JOINTS CREATED BY ASPHALT PAVEMENT REPAIRSWITH HOT-APPLIED RUBBERIZED ASPHALT CRACK SEALER.24" MIN. ROAD18" MIN. GRASS4" MINIMUM SAND ALL SIDES 7 1/2" 7 1/2" 7 1/2"NEUTRAL BUSGROUND BUSX2X1X3X0H1H2H3EGC13.2KV DELTA PRIMARY208Y/120V SECONDARY225 KVATRANSFORMERSEE ONE-LINE FORCONDUCTOR SIZESSEE ONE-LINEFOR CONDUCTORSIZESTO 208V BUS DUCT800A50A800A ENCLOSEDCIRCUIT BREAKER.208V DELTA PRIMARY480V WYE SECONDARY45 KVATRANSFORMERNEUTRAL BUSGROUND BUSTO 480VDISCONNECT100A100A ENCLOSEDCIRCUIT BREAKERNEUTRAL BUSGROUND BUSTO 480VDISCONNECT100A100A ENCLOSEDCIRCUIT BREAKERX2X1X3X0H1H2H3SEE ONE-LINEFOR CONDUCTORSIZESGROUNDINGELECTRODESYSTEM ATTRANSFORMERPAD#3/0 GROUNDINGELECTRODECONDUCTOR#3/0 CU MAIN BONDINGJUMPER (MBJ)TO EXISTINGGROUNDINGELECTRODECONDUCTORWALL MOUNTEDGROUND BAR#8 GEC#8 GEC#8 GECSEE ONE-LINE FORCONDUCTOR SIZES#8 SYSTEM BONDINGJUMPER (SBJ)#8 SBJSEE ONE-LINEFOR CONDUCTORSIZESGROUND BUSGROUND PADNEUTRAL BUSGROUND PAD#3/0 GROUNDINGELECTRODECONDUCTOR(GEC)#8 GECNOTE:REMOVE ANY EXISTING BONDING JUMPERSAT THE EXISTING 208V SWITCHBOARDAND EXISTING 480V DISCONNECT SWITCHES.#8/0 CU(MBJ)#3/0 CU GECEXOTHERMIC WELD#3/0 CU GROUNDINGELECTRODECONDUCTOREXOTHERMICWELD2" COMPACTED NYSDOT TYPE 6F TOP4" COMPACTED NYSDOT TYPE 3 BINDERCOMPACTED SUB-GRADE15" COMPACTED TYPE 4 SUBBASE (NYSDOT TEM 304.14)TACK COAT ALL VERTICAL SURFACES (NYSDOT SECTION 407)3' - 0"6"3' - 0"INSTALL 6" DIAMETER "IDEAL SHIELD" OVERALL BOLLARDS, BLACK UNLESS OTHERWISESPECIFIED. AVAILABLE AT (313) 842-7290 ORWWW.IDEALSHIELD.COM6 5/8" O.D. STEEL PIPE BOLLARDFILLED WITH CONCRETESLOPE CONCRETESEAL JOINT WITH RUBBERIZED ASPHALTCRACK FILLER OR POLYURETHANECAULK, FLUSH WITH ADJACENT PAVEMENTISOLATION JOINTAIR ENTRAINED CONCRETE BASE1' - 6"NCORNELLUNIVERSITYFOUNDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FORANY PERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT ORENGINEER, TO ALTER THIS DOCUMENT IN ANYWAY. IF THIS DOCUMENT IS ALTERED, THEALTERING ARCHITECT OR ENGINEER SHALL AFFIXTO SUCH DOCUMENT HIS SEAL AND THENOTATION "ALTERED BY" FOLLOWED BY HISSIGNATURE, THE DATE OF SUCH ALTERATION,AND A SPECIFIC DESCRIPTION OF THEALTERATION.WARNING:Ithaca, New YorkDATE:FACILITY:DESIGN:DRAWN:ARCHIVE BAR CODEARCH/STRUCT:CIVIL/ENV:ELECTRICAL:MECHANICAL:Teagle Hall & Ward CenterE-102WARD CENTERDETAILSTeagle Hall & Ward Center Electric Service UpgradesE. REICHARDmps2061APRIL 24, 20179569712SCALE: NO SCALE1TRANSFORMER CONCRETE PAD DETAILSCALE: NO SCALE3CONDUIT TRENCH DETAILREVISIONS1 3/2/17 ISSUE FOR DD REVIEW2 4/3/17 ISSUE FOR 75% CD REVIEW3 4/12/17 ISSUE FOR COORDINATED REVIEW4 4/24/16 ISSUE FOR CONSTRUCTIONSCALE: NO SCALE2WARD TRANSFORMER GROUNDING DETAILSSCALE: NO SCALE4HEAVY DUTY ASPHALT PAVEMENT RESTORATION DETAILSCALE: NO SCALE5BOLLARD IN PAVEMENT DETAIL
JJCBCBCBUP1200A ENCLOSEDBREAKERSCHOELKOPF MEMORIALDISCONNECT SWITCH13.2KV/208VTRANSFOMERBANK13.2KV/480VTRANSFOMERBANKNEW 15.5KV3 WAYSWITCHEXISTING15.5KV3 WAYSWITCHTEMPORARY480V/208VTRANSFORMER3-15kV, 600A DEADBREAK 3-WAYJUNCTIONS MOUNTED AT 45°EXISTINGLADDER TRAYEXISTINGLADDER TRAY3E-204NEW LADDER TRAYELECTRICB00UBTUNNELB00DSTAIRB00SAREAWAYB00UDTEAGLE ROWINGMACHINEDISCONNECTSWITCH208V, 1200APOWER PANELEXISTINGMETERSTO REMAINTEMPORARY 1200AF/480AT, 600V,3Ø ENCLOSED CIRCUIT BREAKEREXISTINGTO REMAIN556791011TX-3134EXISTINGPANEL B-1EXISTINGPANEL PB-12KK2EXISTINGTO REMAINSCHOELKOPFMEMORIALTEAGLEROWINGMACHINE400A200A1,200ATEMPORARY300kVA XFMRPRI: 480V/277VSEC: 208Y/120VEXISTING 3-167kVA XFMR13.2kV: 208Y/120VEXISTING 3-167kVA XFMR13.2kV:480Y/277V67TEMPORARY1200AF/480AT, 600V,3Ø ENCLOSEDCIRCUIT BREAKER35 KAIC MINEXISTING 15.5-KV 3-WAYOIL-FILLED SWITCH15kV, 600A DEADBREAK 3-WAYJUNCTIONS MOUNTED AT 45°,TYPICAL OF 3 (1 PER PHASE)NEW 15.5-KV 3-WAYOIL-FILLED SWITCH8911TX-31200A208V PANELBOARD3-#2/0 & 1-#6G 15KV CONDUCTORS2 SETS OF 4 -#250'S &1-#2 GND IN 2 1/2" EMT122 SETS OF 4 -#250'S &1-#2 GND IN 2 1/2" EMTMANHOLEMH-14PARKING GARAGE &SCHOELLKOPF LIGHTSEXISTING ILR LOOP SWITCHMANHOLEMH-14A3 SETS OF 4 -#600'S & 1-#3/0 GND IN 4" CONDUIT480V208VEXISTING 3-167kVA XFMR13.2kV:480Y/277VEXISTING 15.5-KV 3-WAY SWITCHSCHOELKOPFMEMORIALTEAGLEROWINGMACHINE400A200A1,200AEXISTING 3-167kVA XFMR13.2kV: 208Y/120V1200A208V PANELBOARDMANHOLEMH-14PARKING GARAGE &SCHOELLKOPF LIGHTSEXISTING ILR LOOP SWITCHMANHOLEMH-14ATEAGLE ROWINGMACHINEDISCONNECTSWITCH1200A ENCLOSEDBREAKERSCHOELKOPF MEMORIALDISCONNECT SWITCH13.2KV/208VTRANSFOMERBANK13.2KV/480VTRANSFOMERBANKEXISTING15.5KV3 WAYSWITCH208V, 1200APOWER PANELEXISTINGLADDER TRAYEXISTINGLADDER TRAYELECTRICB00UBXFMR VAULTB00UCTUNNELB00CSTAIRB00SAREAWAYB00UDEXISTINGTO REMAINEXISTINGMETERSTO REMAINEXISTINGPANEL B-1EXISTINGPANEL PB-1EXISTINGTO REMAINCAMPUS ROADTEAGLEHALLGARDEN AVENCORNELLUNIVERSITYFOUNDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FORANY PERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT ORENGINEER, TO ALTER THIS DOCUMENT IN ANYWAY. IF THIS DOCUMENT IS ALTERED, THEALTERING ARCHITECT OR ENGINEER SHALL AFFIXTO SUCH DOCUMENT HIS SEAL AND THENOTATION "ALTERED BY" FOLLOWED BY HISSIGNATURE, THE DATE OF SUCH ALTERATION,AND A SPECIFIC DESCRIPTION OF THEALTERATION.WARNING:Ithaca, New YorkDATE:FACILITY:DESIGN:DRAWN:ARCHIVE BAR CODEARCH/STRUCT:CIVIL/ENV:ELECTRICAL:MECHANICAL:Teagle Hall & Ward CenterE-200TEAGLE HALLEXISTING ANDPHASE 1 ELECTRICWORK PLANSTeagle Hall & Ward Center Electric Service UpgradesE. REICHARDmps2611APRIL 24, 20179569712REVISIONS1 3/2/17 ISSUE FOR DD REVIEW2 4/3/17 ISSUE FOR 75% CD REVIEW3 4/12/17 ISSUE FOR COORDINATED REVIEW4 4/24/16 ISSUE FOR CONSTRUCTIONSCALE: 1/4" = 1'-0"3TEAGLE PARTIAL BASEMENT POWER PLAN - PHASE 10 2 4 8SCALE: 1/4"=1'-0"SCALE: NO SCALE4TEAGLE PARTIAL ONE-LINE DIAGRAM - PHASE 1E-200 GENERAL NOTES1.0 THE NEW 15.5KV, 3-WAY SWITCH AND TRANSFORMERS SHALL BE LOWEREDTHROUGH THE AREAWAY. THE TOP OF THE AREAWAY HAS A REMOVABLE GRATETHAT ALLOWS ACCESS. CONTRACTOR TO VERIFY RIGGING REQUIREMENTS ANDNECESSITY OF CRANE.SCALE: NO SCALE2TEAGLE PARTIAL ONE-LINE DIAGRAM - EXISTINGSCALE: 1/4" = 1'-0"1TEAGLE PARTIAL BASEMENT POWER PLAN - EXISTINGE-200 PHASE 1 - KEYED NOTES1 DISCONNECT AND REMOVE EXISITNG LOUVER.2 DISCONNECT AND RELOCATE EXISTING LIGHT SWITCHES TO FACILITATE WALLDEMOLITION. REROUTE CIRCUIT AS REQUIRED AND SURFACE MOUNT IN NEWLOCATION AS INDICATED.2 DISCONNECT AND RELOCATE EXISTING LIGHT SWITCHES TO FACILITATE WALLDEMOLITION. REROUTE CIRCUIT AS REQUIRED AND SURFACE MOUNT IN NEWLOCATION AS INDICATED.3 REMOVE EXISITNG DOORS AND SECTION OF CMU WALL AS INDICATED.4 PROVIDE TEMPORARY 3/4" PLYWOOD DOOR WITH HASP AND KEYED MRB-13PADLOCK.5 PROVIDE TEMPORARY PLYWOOD BARRIER FOR BOTH TRANSFORMER BANKS.BARRIER SHALL EXTEND ENTIRELY AROUND TRANSFORMERS AND 2 FEET ABOVEEXPOSED BUSHINGS.6 CONTRACTOR TO FURNISH 600 AMP DEADBREAK 3-WAY JUNCTIONS (3 TOTAL) TO BEINSTALLED BY CORNELL LINE CREW IN LOCATION SHOWN.7 INSTALL 3-WAY SWITCH FURNISHED BY CORNELL.8 CONTRACTOR TO FURNISH 15KV CABLE AND 600AMP DEAD BREAK ELBOWS (15TOTAL) TO CONNECT 3-WAY JUNCTION TO THE NEW 3-WAY SWITCH. CORNELL TOINSTALL CABLE AND DEAD BREAK ELBOWS FROM 3-WAY JUNCTION TO NEW SWITCH.9 PROVIDE TEMPORARY 300KVA, 480V WYE PRIMARY, 208V WYE SECONDARYTRANSFORMER TX-3. MOUNT TRANSFORMER 18 INCHES ABOVE THE NEW 3-WAYSWITCH. PROVIDE 1 5/8’ STEEL CHANNEL STRUT SUPPORT FOR TRANSFORMER.REFER TO DETAIL ON DRAWING E-203 FOR ADDITIONAL MOUNTING INFORMATION.10 PROVIDE 12 INCH LADDER TRAY IN LOCATION INDICATED. PROVIDE TRAY MOUNTEDTO WALL AT 10 FEET ABOVE FLOOR.11 PROVIDE ENCLOSED 1200 AMP, P FRAME BREAKER WITH AMMETER TRIP UNIT AND “A”RATING PLUG. MOUNT ENCLOSED CIRCUIT BREAKER ON STEEL CHANNEL FRAME INLOCATION INDICATED. THE ENCLOSED CIRCUIT BREAKER WILL BE USED FORPRIMARY PROTECTION FOR THE TEMPORARY TRANSFORMER.12 PROVIDE CONDUCTORS FROM ENCLOSED CIRCUIT BREAKER TO PRIMARY SIDE OFTHE TEMPORARY TRANSFORMER. THE ENCLOSED CIRCUIT BREAKER PLUG SETTINGSHALL BE SET AT .4 (480 AMPS) FOR THIS PHASE.0 2 4 8SCALE: 1/4"=1'-0"TEAGLE HALL KEY PLAN#PHASE 1 DESCRIPTION1.0 INSTALL NEW 15.5KV SWITCH, 3 POINT JUNCTIONS AND TEMPORARY TRANSFORMERWITH PROTECTION PRIOR TO FIRST PLANNED POWER OUTAGE.
JCBCBCBUPJTEAGLE ROWINGMACHINE DISCONNECTSWITCH1200AENCLOSEDBREAKERSCHOELLKOPF MEMORIALDISCONNECT SWITCH13.2KV/480VTRANSFOMERBANKNEW 15.5KV3 WAYSWITCHEXISTING15.5KV3 WAYSWITCHTEMPORARY480V/208VTRANSFORMER208V, 1200APOWER PANELNEW DRY TYPE13.2KV/208VTRANSFOMER1200A, 208V, 3ØENCLOSEDCIRCUIT BREAKERELECTRICB00UBXFMR VAULTB00UCTUNNELB00CSTAIRB00SAREAWAYB00UDJTEMPORARY 1200AF/1200AT, 600V,3Ø ENCLOSED CIRCUIT BREAKEREXISTINGTO REMAIN3-15kV, 600A DEADBREAK 3-WAYJUNCTIONS MOUNTED AT 45°EXISTINGLADDER TRAYEXISTINGLADDER TRAYNEW LADDER TRAY1TX-1351615799138EXISTINGMETERSTO REMAINEXISTINGPANEL B-1EXISTINGPANEL PB-1NEW PRECASTCONCRETE PADTEAGLEROWINGMACHINE400A200A1,200ATEMPORARY300kVA XFMRPRI: 480V/277VSEC: 208Y/120VTEMPORARY1200AF/1200AT,600V, 3ØENCLOSEDCIRCUIT BREAKEREXISTING 15.5-KV 3-WAY SWITCHNEW 15.5-KV 3-WAY SWITCH1200A208V PANELBOARDMANHOLEMH-14PARKING GARAGE &SCHOELLKOPF LIGHTSEXISTING ILR LOOP SWITCHMANHOLEMH-14ASCHOELLKOPFMEMORIALTX-3300kVAXFMR13.2:208Y/120VTX-11200A, 208V, 3ØENCLOSEDCIRCUIT BREAKER20 KAIC MIN3 -#2/0'S & 1-6 GNDIN 4" CONDUIT1011715141433 SETS OF 4 -#600'S & 1-3/0 GNDIN 4" CONDUITEXISTING 3-167kVA XFMR13.2kV:480Y/277V1612103 SETS OF 4 -#600'S & 1-3/0 GND IN 4" CONDUIT129561 SET OF 4 -#600'S &1-#3 GND IN 3" EMT2131 SET OF 4 -#4/0'S & 1-#6 GND IN 2 1/2" EMT480V208VCAMPUS ROADTEAGLEHALLGARDEN AVETEMPORARY 1200AF/480AT, 600V,3Ø ENCLOSED CIRCUIT BREAKERELECTRICB00UBXFMR VAULTB00UCTUNNELB00CSTAIRB00SAREAWAYB00UDTEAGLE ROWINGMACHINEDISCONNECTSWITCH1200A ENCLOSEDBREAKERSCHOELKOPF MEMORIALDISCONNECT SWITCH13.2KV/208VTRANSFOMERBANK13.2KV/480VTRANSFOMERBANKEXISTING15.5KV3 WAYSWITCH208V, 1200APOWER PANELEXISTINGLADDER TRAYEXISTINGTO REMAINEXISTINGMETERSTO REMAIN3-15kV, 600A DEADBREAK 3-WAYJUNCTIONS MOUNTED AT 45°EXISTINGLADDER TRAYNEW LADDER TRAYTEMPORARY480V/208VTRANSFORMER5EXISTINGPANEL B-1EXISTINGPANEL PB-1SCHOELKOPFMEMORIALTEAGLEROWINGMACHINE400A200A1,200ATEMPORARY300kVA XFMRPRI: 480V/277VSEC: 208Y/120VTEMPORARY1200AF/480AT,600V, 3ØENCLOSEDCIRCUIT BREAKEREXISTING 3-167kVA XFMR13.2kV: 208Y/120VEXISTING 3-167kVA XFMR13.2kV:480Y/277VEXISTING 15.5-KV 3-WAY SWITCH215kV, 600A DEADBREAK 3-WAYJUNCTIONS MOUNTED AT 45°,TYPICAL OF 3 (1 PER PHASE)NEW 15.5-KV 3-WAY SWITCH3451200A208V PANELBOARD2 SETS OF 4 -#250'S &1-#2 GND IN 2 1/2" CONDUIT1PROVIDE CRIMPCONNECT WITH COLDSHRINK6MANHOLEMH-14PARKING GARAGE &SCHOELLKOPF LIGHTSEXISTING ILR LOOP SWITCHMANHOLEMH-14A1480V208VNCORNELLUNIVERSITYFOUNDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FORANY PERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT ORENGINEER, TO ALTER THIS DOCUMENT IN ANYWAY. IF THIS DOCUMENT IS ALTERED, THEALTERING ARCHITECT OR ENGINEER SHALL AFFIXTO SUCH DOCUMENT HIS SEAL AND THENOTATION "ALTERED BY" FOLLOWED BY HISSIGNATURE, THE DATE OF SUCH ALTERATION,AND A SPECIFIC DESCRIPTION OF THEALTERATION.WARNING:Ithaca, New YorkDATE:FACILITY:DESIGN:DRAWN:ARCHIVE BAR CODEARCH/STRUCT:CIVIL/ENV:ELECTRICAL:MECHANICAL:Teagle Hall & Ward CenterE-201TEAGLE HALLPHASES 2 AND 3ELECTRIC WORKPLANSTeagle Hall & Ward Center Electric Service UpgradesE. REICHARDmps2611APRIL 24, 20179569712REVISIONS1 3/2/17 ISSUE FOR DD REVIEW2 4/3/17 ISSUE FOR 75% CD REVIEW3 4/12/17 ISSUE FOR COORDINATED REVIEW4 4/24/16 ISSUE FOR CONSTRUCTION0 2 4 8SCALE: 1/4"=1'-0"SCALE: 1/4" = 1'-0"3TEAGLE PARTIAL BASEMENT POWER PLAN - PHASE 30 2 4 8SCALE: 1/4"=1'-0"SCALE: NO SCALE4TEAGLE PARTIAL ONE-LINE DIAGRAM - PHASE 3TEAGLE HALL KEY PLANSCALE: 1/4" = 1'-0"1TEAGLE PARTIAL BASEMENT POWER PLAN - PHASE 2SCALE: NO SCALE2TEAGLE PARTIAL ONE-LINE DIAGRAM - PHASE 2E-201 PHASE 2 - KEYED NOTES1 CORNELL LINE CREW SHALL OPEN THE SWITCH WAY FOR TEAGLE HALL AT ILRSWITCH AND DISCONNECT THE EXISTING 13.2KV FEEDER CONNECTION FROM THEEXISTING 3-WAY SWITCH, RE-TERMINATE USING 600 AMP DEAD BREAK ELBOWS ANDCONNECT THE CABLES TO THE 3-WAY JUNCTIONS. OUTAGE #1 DURATION: 4-8HOURS.2 PROVIDE CONDUCTORS FROM THE SECONDARY OF THE 480V TRANSFORMER BANKTO THE TEMPORARY ENCLOSED CIRCUIT BREAKER.3 PROVIDE CONDUCTORS FROM THE TEMPORARY TRANSFORMER SECONDARY TO THECABLE TRAY ABOVE THE AREA WAY. THE CABLES WILL BE EXTENDED TO THEEXISTING 208V SECONDARY CONDUCTORS FOR THE TEMPORARY 208V FEED. LEAVEENOUGH SLACK ON THE CONDUCTORS TO REACH THE EXISTING SECONDARYCABLES OF THE 208V TRANSFORMER BANK ONCE THE TRANSFORMERS AREREMOVED.4 OPEN THE SWITCH WAY ON THE EXISTING 3-WAY SWITCH FEEDING THE 208VTRANSFORMER BANK. DISCONNECT AND REMOVE PRIMARY AND SECONDARYCONDUCTORS FROM THE 208V TRANSFORMER BANK. REMOVE THE METERING CT’SAND SAVE FOR REUSE ON THE TEMPORARY FEEDERS. CONNECT THE TEMPORARYFEEDER FROM THE TEMPORARY TRANSFORMER TO THE EXISTING 208V SECONDARYCONDUCTORS AND INSTALL THE METERING CT’S ON THE CONDUCTORS. REMOVETHE PRIMARY CONDUCTORS FROM THE EXISTING 3-WAY SWITCH. OUTAGE #2DURATION:4-8 HOURS.5 REMOVE THE EXISTING 208V TRANSFORMER BANK.6 CONTACT CORNELL EHS TO SAMPLE TRANSFORMERS PRIOR TO DISPOSAL. TESTINGRESULTS WILL REQUIRE A MINIMUM OF 2 WEEKS.#E-201 PHASE 3 - KEYED NOTES1 PROVIDE 13.2KV/208V, 300KVA DRY TYPE TRANSFORMER TX-1 IN LOCATIONINDICATED ON A PRECAST CONCRETE PAD.2 PROVIDE MEDIUM VOLTAGE CABLE FROM NEW 3-WAY SWITCH TO DRY TYPETRANSFORMER VIA THE CABLE TRAY. PROVIDE 5” CONDUIT FROM THETRANSFORMER ENCLOSURE UP TO CABLE TRAY. PROVIDE BUSHING AT TOP OFCONDUIT.3 PROVIDE ENCLOSED 1200 AMP, P FRAME BREAKER WITH AMMETER TRIP UNIT AND “A”RATING PLUG. MOUNT ENCLOSED CIRCUIT BREAKER ON STEEL CHANNEL FRAME INLOCATION INDICATED. THE ENCLOSED CIRCUIT BREAKER WILL BE USED FORSECONDARY PROTECTION FOR TRANSFORMER TX-2. THE ENCLOSED CIRCUITBREAKER PLUG SETTING SHALL BE SET AT 1 (1200 AMPS).4 PROVIDE CONDUCTORS FROM THE TRANSFORMER SECONDARY TO THE ENCLOSEDCIRCUIT BREAKER VIA THE CABLE TRAY. PROVIDE CONDUIT FROM BOTHENCLOSURES UP TO CABLE TRAY. PROVIDE BUSHING AT TOP OF CONDUITS.5 PROVIDE 32"X32"X10" JUNCTION BOX ON THE WALL ABOVE THE EXISTING ENCLOSEDCIRCUIT BREAKER AND NEXT TO THE EXISTING 208V PANEL.6 PROVIDE CONDUCTORS FROM THE ENCLOSED CIRCUIT BREAKER TO THE CABLETRAY AND THROUGH THE WALL INTO THE 32"X32"X10" JUNCTION BOX ABOVE THEEXISTING 1200AMP ENCLOSED CIRCUIT BREAKER. PROVIDE CONDUIT FROMENCLOSED CIRCUIT BREAKER UP TO CABLE TRAY. PROVIDE BUSHING AT TOP OFCONDUIT. COIL ENOUGH SLACK AT THE JUNCTION BOX TO TERMINATE THECONDUCTORS INSIDE THE EXISTING 208V PANEL.7 OPEN THE SWITCH WAY FEEDING THE EXISTING 13.2KV/480V TRANSFORMER BANKAND DISCONNECT THE TEMPORARY FEED FOR THE TEMPORARY TRANSFORMER.REMOVE METERING CT'S FROM TEMPORARY FEED AND INSTALL IN CABLE TRAY ONSECONDARY CONDUCTORS. OUTAGE #3 DURATION:8 HOURS.9 CUT THE SIDE OF THE PANEL AND JUNCTION BOX TO ALLOW FOR CABLE ENTRY.PROVIDE GASKETING ALONG THE EDGES OF THE OPENINGS TO PROTECT THECABLES. INSTALL THE NEW FEEDER CONDUCTORS IN THE 208V PANEL.10 DISCONNECT THE TEMPORARY ENCLOSED CIRCUIT BREAKER FROM THE 480V BANKAND THE TEMPORARY TRANSFORMER.11 DISCONNECT THE CONDUCTORS ON THE EXISTING 480V BANK SECONDARY THATFEED THE 400A SCHOELLKOPF AND 200A ROWING MACHINE DISCONNECT SWITCHES.SAVE THE CONDUCTORS TO SPLICE WITH THE TEMPORARY FEED.12 PROVIDE TEMPORARY CONDUCTORS FROM THE 208V SECONDARY OFTRANSFORMER TX-1 TO THE 208V SIDE OF THE TEMPORARY TRANSFORMER TX-3 VIATHE TEMPORARY ENCLOSED CIRCUIT BREAKER. THE TEMPORARY ENCLOSEDCIRCUIT BREAKER PLUG SETTING SHALL BE SET AT 1 (1200 AMPS) FOR THIS PHASE.PROVIDE CONDUCTORS FROM THE 480V SIDE OF TX-3 TO THE EXISTINGCONDUCTORS THAT FEED THE 400A SCHOELLKOPF AND 200A ROWING MACHINEDISCONNECT SWITCHES. RELOCATE THE METERING CT'S TO THE TEMPORARYFEEDERS FOR THE 480V DISCONNECTS.13 CONTRACTOR TO VERIFY PHASE ROTATION. IF ROTATION IS VERIFIED CORRECTLY,CONTRACTOR TO CLOSE THE SWITCH WAY FEEDING THE NEW 13.2KV/208V DRY TYPETRANSFORMER. IF NECESSARY, CORNELL LINE CREW TO SWAP CABLES ONINCOMING SIDE OF THE 3 WAY SWITCH.14 DISCONNECT AND REMOVE THE EXISTING 15.5KV 3-WAY SWITCH FROM THE 3-WAYJUNCTION.15 REMOVE AND PROPERLY DISPOSE THE EXISTING 15.5KV 3-WAY SWITCH ANDASSOCIATED CONDUCTORS.16 REMOVE AND PROPERLY DISPOSE THE EXISTING 13.2KV/480V TRANSFORMER BANK.COORDINATE DISPOSAL OF THE TRANSFORMERS WITH AN APPROVEDENVIRONMENTAL SERVICE PROVIDER. REMOVAL PROCESS MUST BE WITNESSED BYCORNELL ENVIRONMENTAL HEALTH AND SAFETY.#PHASE 2 DESCRIPTION1.0 FIRST OUTAGE TO CONNECT NEW 15.5KV LOOP SWITCH AND CONNECT TEMPORARYTRANSFORMER FOR 208V POWER.PHASE 3 DESCRIPTION1.0 REMOVE TEMPORARY FEED FOR 208V DIISTRIBUTION, PROVIDE CONNECTIONS FROMNEW 208V TRANSFORMER AND PROVIDE CONNECTIONS FOR TEMPORARY 480VDISTRIBUTION TO FACILITATE INSTALLATION OF NEW 480V TRANSFORMER.REMOVEEXISTING 15.5KV SWITCH AND THE THREE 13.2KV TO 480V BANK OF TRANSFORMERS.
CBCBCBUPJJCAMPUS ROADTEAGLEHALLGARDEN AVETEAGLE ROWINGMACHINE DISCONNECTSWITCHSCHOELKOPF MEMORIALDISCONNECT SWITCHNEW DRY TYPE13.2KV/480VTRANSFOMERNEW 15.5KV3 WAYSWITCHTEMPORARY480V/208VTRANSFORMER208V, 1200APOWER PANELNEW DRY TYPE13.2KV/208VTRANSFOMERELECTRICB00UBXFMR VAULTB00UCTUNNELB00CSTAIRB00SAREAWAYB00UDEXISTINGLADDER TRAY3-15kV, 600A DEADBREAK 3-WAYJUNCTIONS MOUNTED AT 45°1200A, 600V, 3ØENCLOSEDCIRCUIT BREAKERTEMPORARY 1200AF/1200AT, 600V,3Ø ENCLOSED CIRCUIT BREAKEREXISTINGTO REMAINEXISTINGLADDER TRAYJ1TX-14789101112T13EXISTINGMETERSTO REMAINEXISTINGPANEL B-1,SQ.-D, 225A,MLO, 42 CKT,10 KAICEXISTINGPANEL PB-11414TX-2EXISTINGTO REMAINB00UCB00UBTEMPORARY300kVA XFMR480V/277V:208Y/120V480V208VTX-391200A, 208V, 3ØENCLOSEDCIRCUITBREAKERTX-1300kVAXFMR13.2:208Y/120VTEMPORARY1200AF/1200AT,600V, 3ØENCLOSEDCIRCUIT BREAKER8SCHOELKOPFMEMORIALTEAGLEROWINGMACHINE350A200A5471300kVAXFMR13.2:480Y/277V2TX-23 -#2/0'S & 1-6 GND IN 4" CONDUIT634 -#500'S & 1-#3 GND IN 3" EMT4 -#4/0'S & 1-#6 GNDIN 2 1/2" EMT1200A208V PANELBOARD32"x32"x8"JUNCTION BOXNEW 15.5-KV 3-WAY SWITCHMANHOLEMH-14PARKING GARAGE &SCHOELLKOPF LIGHTSEXISTING ILR LOOP SWITCHMANHOLEMH-14APROVIDE INSULATED CAPS,1 PER PHASE (3 TOTAL)SCHOELKOPFMEMORIALTEAGLEROWINGMACHINE350A200A1200A, 208V, 3ØENCLOSEDCIRCUITBREAKERNEW 15.5-KV 3-WAY SWITCH300kVAXFMR13.2:208Y/120V300kVAXFMR13.2:480Y/277V1200A208V PANELBOARD32"x32"x8"JUNCTION BOXTX-1TX-2MANHOLEMH-14PARKING GARAGE &SCHOELLKOPF LIGHTSEXISTING ILR LOOP SWITCHMANHOLEMH-14A15kV, 600A DEADBREAK 3-WAYJUNCTIONS MOUNTED AT 45°,TYPICAL OF 3 (1 PER PHASE)4 -#500'S & 1-#3 GND IN 3" EMT4 -#4/0'S & 1-#6 GNDIN 2 1/2" EMT3 -#2/0'S & 1-6 GNDIN 4" CONDUIT3 SETS OF 4 -#600'S & 1-3/0 GND IN 4" CONDUITAREAWAYB00UDXFMR VAULTB00UCSTAIRB00STUNNELB00CTEAGLE ROWINGMACHINE DISCONNECTSWITCHSCHOELKOPF MEMORIALDISCONNECT SWITCHNEW DRY TYPE13.2KV/480VTRANSFOMERNEW 15.5KV3 WAYSWITCH208V, 1200APOWER PANELNEW DRY TYPE13.2KV/208VTRANSFOMER1200A, 600V, 3Ø ENCLOSEDCIRCUIT BREAKERELECTRICB00UBJEXISTINGTO REMAINSCHOELKOPF MEMORIALDISCONNECT SWITCH3-15kV, 600A DEADBREAK 3-WAYJUNCTIONS MOUNTED AT 45°EXISTINGLADDER TRAYEXISTINGLADDER TRAYNEW LADDER TRAYTX-1TX-2EXISTINGMETERSTO REMAINEXISTINGPANEL B-1EXISTINGPANEL PB-1EXISTINGTO REMAINNCORNELLUNIVERSITYFOUNDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FORANY PERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT ORENGINEER, TO ALTER THIS DOCUMENT IN ANYWAY. IF THIS DOCUMENT IS ALTERED, THEALTERING ARCHITECT OR ENGINEER SHALL AFFIXTO SUCH DOCUMENT HIS SEAL AND THENOTATION "ALTERED BY" FOLLOWED BY HISSIGNATURE, THE DATE OF SUCH ALTERATION,AND A SPECIFIC DESCRIPTION OF THEALTERATION.WARNING:Ithaca, New YorkDATE:FACILITY:DESIGN:DRAWN:ARCHIVE BAR CODEARCH/STRUCT:CIVIL/ENV:ELECTRICAL:MECHANICAL:Teagle Hall & Ward CenterE-202TEAGLE HALLPHASE 4 WORKPLAN AND DETAILSTeagle Hall & Ward Center Electric Service UpgradesE. REICHARDmps2611APRIL 24, 20179569712REVISIONS1 3/2/17 ISSUE FOR DD REVIEW2 4/3/17 ISSUE FOR 75% CD REVIEW3 4/12/17 ISSUE FOR COORDINATED REVIEW4 4/24/16 ISSUE FOR CONSTRUCTIONTEAGLE HALL KEY PLANSCALE: 1/4" = 1'-0"1TEAGLE PARTIAL BASEMENT POWER PLAN - PHASE 4SCALE: NO SCALE2TEAGLE PARTIAL ONE-LINE DIAGRAM - PHASE 40 2 4 8SCALE: 1/4"=1'-0"SCALE: NO SCALE4TEAGLE PARTIAL ONE-LINE DIAGRAM - FINALSCALE: 1/4" = 1'-0"3TEAGLE PARTIAL BASEMENT POWER PLAN - FINALE-202 PHASE 4 - KEYED NOTES1 PROVIDE 300KVA, 13.2KV/480V DRY TYPE TRANSFORMER TX-2 IN LOCATIONINDICATED.2 PROVIDE CONDUCTORS FROM NEW 15.5KV 3-WAY SWITCH TO 13.2KV PRIMARY OFTHE NEW 300KVA TRANSFORMER.3 PROVIDE CONDUCTORS FROM 480V SECONDARY OF 300KVA TRANSFORMER FORTHE 400A SCHOELLKOPF AND 200A ROWING MACHINE DISCONNECT SWITCHES.INSTALL THE CABLE INTO THE CABLE TRAY ABOVE AND PROVIDE ENOUGH SLACK TOPULL THROUGH THE WALL AND INTO THE DISCONNECT SWITCHES.4 OPEN THE SWITCH WAY FEEDING THE NEW 13.2KV/208V DRY TYPE TRANSFORMER.DISCONNECT THE TEMPORARY FEED TO TRANSFORMER TX-3 AND CLOSE SWITCH TORE-ENERGIZE 208V PANEL. OUTAGE #4 DURATION: 4 HOURS.5 DISCONNECT AND REMOVE THE EXISTING CONDUCTORS FROM TRANSFORMER TX-3TO THE DISCONNECT SWITCHES.6 PROVIDE CONDUCTORS FROM TRANSFORMER TX-2 480V SECONDARY TO THEDISCONNECT SWITCHES. REMOVE THE METERING CT'S FROM THE TEMPORARYFEEDERS AND INSTALL THEM ON THE SECONDARY CONDUCTORS FOR THE 480VDISCONNECT SWITCHES. PROVIDE NEW 350 AMP FUSES IN THE SCHOELLKOPFDISCONNECT SWITCH.7 CONTRACTOR TO VERIFY PHASE ROTATION. IF ROTATION IS VERIFIED CORRECTLY,CLOSE THE SWITCH WAY FEEDING THE NEW 13.2KV/480V DRY TYPE TRANSFORMER.IF NECESSARY, CORNELL LINE CREW TO SWAP CABLES ON NEW 15.5KV SWITCHPRIOR TO CLOSING.8 DISCONNECT AND REMOVE THE TEMPORARY ENCLOSED CIRCUIT BREAKER. TURNBREAKER AND ENCLOSURE OVER TO CORNELL UTILITIES. CONTRACTOR TO DELIVERENCLOSURE AND BREAKER TO R5 WAREHOUSE ON PALM ROAD.9 DISCONNECT AND REMOVE THE TEMPORARY 300KVA, 480V/208V TRANSFORMERFROM WALL AND TURN OVER TO CORNELL UTILITIES. CONTRACTOR TO DELIVERTRANSFORMER TO R5 WAREHOUSE ON PALM ROAD. REMOVE STRUT SUPPORTFROM WALL.10 REMOVE TEMPORARY DOOR.11 PROVIDE NEW SECTION OF CMU WALL AND UNEQUAL THREE FOOT AND TWO FOOTDOORS WITH FRAME IN LOCATIONS INDICATED. PROVIDE PANIC HARDWARE WITHTRANSFORMER VAULT 3 FOOT DOOR. DOORS AND FRAME TO TRANSFORMER VAULTTO BE 3 HOUR RATED. DOORS AND FRAME TO ELECTRICAL ROOM TO BE 1 1/5 HOURRATED. CYLINDERS TO BE PROVIDED BY CORNELL LOCK SHOP.12 PROVIDE 54” X 36” COMBINATION LOUVER/DAMPER IN EXISTING OPENING EQUAL TOGREENHECK MODEL ECD-601. MANUFACTURER SHALL FURNISH OPTIONAL ELECTRICMOTOR ACTUATOR EQUAL TO BELIMO MODEL AFBUP. CONTRACTOR SHALL FRAMEEXISTING OPENING AND INSTALL LOUVER (CENTERED) IN EXISTING OPENING.PROVIDE ADDITIONAL SUPPORT AS REQUIRED TO SUPPORT THE LOUVER/DAMPER.REMAINING OPENING SHALL BE INFILLED WITH NON-INSULATED BLANK OFF PANEL.BLANK OFF PANEL SHALL MATCH FINISH AND CONSTRUCTION OF LOUVER.13 PROVIDE 120V TEMPERATURE SENSOR EQUAL TO JOHNSON CONTROLS MODEL A421.TEMPERATURE SENSOR SETPOINT SHALL BE 40°F. UPON A DROP IN SPACETEMPERATURE BELOW 40°F, COMBINATION LOUVER/DAMPER SHALL BE COMMANDEDTO THE FULL CLOSED POSITION. UPON A RISE IN SPACE TEMPERATURE ABOVE 40°F,COMBINATION LOUVER/DAMPER SHALL BE COMMANDED TO THE FULL OPENPOSITION. INSTALL TEMPERATURE SENSOR ON INTERIOR WALL.14 PROVIDE 20A, 120V, 1P CIRCUIT BREAKER IN PANEL B-1 (SPACE #37) AND CIRCUITNEW LOUVER/DAMPER ACTUATOR THROUGH 30A, 120V SINGLE PHASE LOCKABLEMANUAL STARTER/DISCONNECT TOGGLE SWITCH WITH 2#12 AWG & 1#12 AWG GNDCONDUCTORS IN 3/4" EMT CONDUIT. MATCH EXISTING PANEL TYPE AND AIC RATING.0 2 4 8SCALE: 1/4"=1'-0"#PHASE 4 DESCRIPTION1.0 REMOVE TEMPORARY FEED FOR 208V DISTRIBUTION, PROVIDE CONNECTIONS FROMNEW 208V TRANSFORMER AND PROVIDE CONNECTIONS FOR TEMPORARY 480VDISTRIBUTION TO FACILITATE INSTALLATION OF NEW 480V TRANSFORMER.
CBCBCBUPAREAWAYB00UDXFMR VAULTB00UCSTAIRB00STUNNELB00C11112ELECTRICB00UBEM1EM AREAWAYB00UDXFMR VAULTB00UCSTAIRB00STUNNELB00C1111P23A1bA1bA1aA1aabELECTRICB00UBEMEM
1CAMPUS ROADTEAGLEHALLGARDEN AVE208V GROUND BAR480V GROUND BARXFMR VAULTB00UCELECTRICB00UBAREAWAYB00UDTUNNELB00CSTAIRB00SEGECTX-1TX-2TOLADDERTRAYDOOR FRAME112EGEC2TO LADDER TRAYECBTEAGLE ROWINGMACHINE 480VDISCONNECTSWITCHSCHOELKOPF 480VDISCONNECT SWITCHNCORNELLUNIVERSITYFOUNDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FORANY PERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT ORENGINEER, TO ALTER THIS DOCUMENT IN ANYWAY. IF THIS DOCUMENT IS ALTERED, THEALTERING ARCHITECT OR ENGINEER SHALL AFFIXTO SUCH DOCUMENT HIS SEAL AND THENOTATION "ALTERED BY" FOLLOWED BY HISSIGNATURE, THE DATE OF SUCH ALTERATION,AND A SPECIFIC DESCRIPTION OF THEALTERATION.WARNING:Ithaca, New YorkDATE:FACILITY:DESIGN:DRAWN:ARCHIVE BAR CODEARCH/STRUCT:CIVIL/ENV:ELECTRICAL:MECHANICAL:Teagle Hall & Ward CenterE-203TEAGLE HALLLIGHTING &GROUNDINGPLANSTeagle Hall & Ward Center Electric Service UpgradesE. REICHARDmps2611APRIL 24, 20179569712REVISIONS1 3/2/17 ISSUE FOR DD REVIEW2 4/3/17 ISSUE FOR 75% CD REVIEW3 4/12/17 ISSUE FOR COORDINATED REVIEW4 4/24/16 ISSUE FOR CONSTRUCTIONSCALE: 1/4" = 1'-0"1TEAGLE PARTIAL BASEMENT DEMO LIGHTING PLANSCALE: 1/4" = 1'-0"2TEAGLE PARTIAL BASEMENT NEW LIGHTING PLANE-203 LIGHTING DEMO KEYED NOTES1 DISCONNECT AND REMOVE EXISTING LIGHT FIXTURE. TAG EXISTING CIRCUIT FORREUSE.2 DISCONNECT AND REMOVE EXISTING LIGHT SWITCH. REMOVE CIRCUIT BACK TONEAREST JUNCTION BOX AND TAG FOR REUSE. PROVIDE BLANK COVERPLATE OVEREXISTING BACKBOX.E-203 LIGHTING KEYED NOTES1 PROVIDE LIGHT FIXTURE INDICATED, MODIFY/EXTEND EXISTING LIGHTING CIRCUITSAVED DURING DEMOLITION AND RECONNECT.2 PROVIDE 20A, 120V LIGHT SWITCH WITH PILOT LIGHT FOR XFMR VAULT LIGHTINGCONTROL.3 PROVIDE 20A, 120V LIGHT SWITCH FOR ELECTRICAL ROOM LIGHTING CONTROL.TEAGLE HALL KEY PLAN##0 2 4 8SCALE: 1/4"=1'-0"0 2 4 8SCALE: 1/4"=1'-0"SCALE: 1/4" = 1'-0"3TEAGLE PARTIAL BASEMENT NEW GROUNDING PLANE-203 GROUNDING KEYED NOTES1 PROVIDE 4" X 20" X 1/4" COPPER GROUND BAR WITH WALL MOUNTING BRACKETS ANDINSULATORS. MOUNT AT 24" AFF. CONNECT AS INDICATED ON DETAIL 1/E-204.2 APPROXIMATE LOCATION OF THE EXISTING GROUNDING ELECTRODE CONDUCTOR(EGEC).#0 2 4 8SCALE: 1/4"=1'-0"
FIRST FLOOR13' - 6"LOW VOLTAGE300 KVA TEMP.TRANSFORMER,2,000 LBS.L4x4x3/85/8" DIAM. HILTIHAS ROD (6" MINEMBED.) W/ HITHY-200L5x5x3/8C6x8.2, COORDINATEBOLT HOLE SIZE &SPACING WITHTRANSFORMERBASE ANCHOR LAYOUT3/16 5NOTE: PROVIDE (2)BRACKETSEA. SIDE OFTRANSFORMER1 1/2"8"3' - 10"1 1/2"4"4"3/163 SIDES TYPPROVIDE 3/8" FILLERPL. AS NEEDEDTHIS LOCATIONBETWEEN ANGLESGALVANIZEDSTEEL GUSSETCONNECTORFLOORNEW 12 INCHLADDER TRAYEXISTINGCONCRETEWALL4"4"8"4"1/2" DIA. LOK BOLT AS (TYPE 340 STAINLESS)BY POWERS. MIN. EMBEDMENT 1-1/2".MIN. EDGE DISTANCE 4" (4 PER BRACKET)1-5/8" GALVANIZED STEELCHANNEL STRUT EVERY 3 FEET.1-5/8" GALVANIZED STEELCHANNEL STRUT.1-5/8" GALVANIZEDSTEEL CHANNEL STRUT.CLOSED ANGLE CONNECTOR.PROVIDE 1/2' GALVANIZED STRUTBOLTS AND CHANNEL NUTS TOFASTEN TO FRAME. TYPICAL OF ALLCONNECTORS.CLOSED ANGLE CONNECTORNEUTRAL BUSGROUND BUSX2X1X3X0H1H2H3EGC13.2KV DELTA PRIMARY208Y/120V SECONDARY300 KVATRANSFORMER1200A ENCLOSEDCIRCUITBREAKER.SEE ONE-LINE FORCONDUCTOR SIZESSEE ONE-LINEFOR CONDUCTORSIZESTO 208V PANELNEUTRAL BUSGROUND BUSX2X1X3X0H1H2H313.2KV DELTA PRIMARY480Y/277V SECONDARY300 KVATRANSFORMER480V DISCONNECTSEE ONE-LINE FORCONDUCTOR SIZESSEE ONE-LINEFOR CONDUCTORSIZESTO SCHOELLKOPFNEUTRAL BUSGROUND BUS480V DISCONNECTTO ROWING MACHINE1200A200A#2 CU MAIN BUILDING JUMPER350A#1/0 CU MAINBONDING JUMPER480V GROUND BAR208V GROUND BAR#1/0 CU GROUNDINGELECTRODE CONDUCTOR#2 CU GROUNDINGELECTRODE CONDUCTOR#3/0 CU GROUNDINGELECTRODE CONDUCTOR#3/0 CU GROUNDINGELECTRODE CONDUCTOR#3/0 CU GROUNDINGELECTRODE CONDUCTOR(GEC)TO EXISTINGGROUNDINGELECTRODECONDUCTOR#3/0 CU GROUNDINGELECTRODE CONDUCTORTO EXISTINGGROUNDINGELECTRODECONDUCTOR#3/0 CU GROUNDINGELECTRODE CONDUCTOR(GEC)#250 KCMIL CUMAIN BONDINGJUMPEREGCNOTE:REMOVE ANY EXISTING BONDING JUMPERSAT THE EXISTING 208V SWITCHBOARDAND EXISTING 480V DISCONNECT SWITCHES.NCORNELLUNIVERSITYFOUNDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FORANY PERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT ORENGINEER, TO ALTER THIS DOCUMENT IN ANYWAY. IF THIS DOCUMENT IS ALTERED, THEALTERING ARCHITECT OR ENGINEER SHALL AFFIXTO SUCH DOCUMENT HIS SEAL AND THENOTATION "ALTERED BY" FOLLOWED BY HISSIGNATURE, THE DATE OF SUCH ALTERATION,AND A SPECIFIC DESCRIPTION OF THEALTERATION.WARNING:Ithaca, New YorkDATE:FACILITY:DESIGN:DRAWN:ARCHIVE BAR CODEARCH/STRUCT:CIVIL/ENV:ELECTRICAL:MECHANICAL:Teagle Hall & Ward CenterE-204TEAGLE HALLDETAILSTeagle Hall & Ward Center Electric Service UpgradesE. REICHARDmps2611APRIL 24, 20179569712REVISIONS1 3/2/17 ISSUE FOR DD REVIEW2 4/3/17 ISSUE FOR 75% CD REVIEW3 4/12/17 ISSUE FOR COORDINATED REVIEW4 4/24/16 ISSUE FOR CONSTRUCTIONSCALE: NO SCALE3TRANSFORMER MOUNTING DETAILSCALE: 1" = 1'-0"2CABLE TRAY MOUNTING DETAILSCALE: 1" = 1'-0"1TEAGLE TRANSFORMER GROUNDING DETAILSTEMPORARY
NCORNELLUNIVERSITYFOUNDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FORANY PERSON, UNLESS ACTING UNDER THEDIRECTION OF A LICENSED ARCHITECT ORENGINEER, TO ALTER THIS DOCUMENT IN ANYWAY. IF THIS DOCUMENT IS ALTERED, THEALTERING ARCHITECT OR ENGINEER SHALL AFFIXTO SUCH DOCUMENT HIS SEAL AND THENOTATION "ALTERED BY" FOLLOWED BY HISSIGNATURE, THE DATE OF SUCH ALTERATION,AND A SPECIFIC DESCRIPTION OF THEALTERATION.WARNING:Ithaca, New YorkDATE:FACILITY:DESIGN:DRAWN:ARCHIVE BAR CODEARCH/STRUCT:CIVIL/ENV:ELECTRICAL:MECHANICAL:Teagle Hall & Ward CenterE-300TEAGLE HALLISOMETRIC PLANSTeagle Hall & Ward Center Electric Service UpgradesE. REICHARDcmw2611APRIL 24, 20179569712REVISIONS1 3/2/17 ISSUE FOR DD REVIEW2 4/3/17 ISSUE FOR 75% CD REVIEW3 4/12/17 ISSUE FOR COORDINATED REVIEW4 4/24/16 ISSUE FOR CONSTRUCTIONSCALE: NO SCALE1ISOMETRIC VIEW - PHASE 1SCALE: NO SCALE2ISOMETRIC VIEW - PHASE 2SCALE: NO SCALE3ISOMETRIC VIEW - PHASE 3SCALE: NO SCALE4ISOMETRIC VIEW - PHASE 4NOTES:1.REFER TO PHASE DRAWING E-202 FOR MORE INFORMATION.2.REFER TO DRAWING E-000 FOR LINETYPE INFORMATIONNOTES:1.REFER TO PHASE DRAWING E-202 FOR MORE INFORMATION.2.REFER TO DRAWING E-000 FOR LINETYPE INFORMATIONNOTES:1.REFER TO PHASE DRAWING E-200 FOR MORE INFORMATION.2.REFER TO DRAWING E-000 FOR LINETYPE INFORMATIONNOTES:1.REFER TO PHASE DRAWING E-201 FOR MORE INFORMATION.2.REFER TO DRAWING E-000 FOR LINETYPE INFORMATION