HomeMy WebLinkAboutUpson HallCORNELL UNIVERSITY FACILITIES CONTRACTS 121 HUMPHREYS SERVICE BUILDING ITHACA, NEW YORK 14853-3701 UPSON HALL ROOM 472 LABORATORY RENOVATION ADDENDUM NO. 1 April 8, 2019 This Addendum contains changes to the requirements of the Contract Documents and Specifications. Such changes arc to be incorporated into the Construction Documents and shall apply to the work with the same meaning and force as if they had been included in the original document. Wherever this Addendum modifies a portion of a paragraph of the specifications or a portion of any Drawing, the remainder of the Paragraph or Drawing shall remain in force. NOTE: Provisions of all Contract Documents apply. DRAWINGS Item 1. Drawing A -I 10, Keyed Equipment List Number 10 DELETE Equipment Name: LENS 150 Additive Manufacturing Controlled Atmosphere System; Manufacturer: OPTOMEC; Model No: LENS 150" REPLACE with Equipment Name: X -Series Laser MetalDeposition System; Manufacturer: Formalloy LLC; Model No: X-222 Itcrn 2. Drawing A -I 10, Kcycd Equipment List Number 10a DELETE Equipment Name: LENS 150 Powder Feeder; Manufacturer: OPTOMEC; Model No: LENS 150 REPLACE with Equipment Name: Formfeed Powder Feeder; Manufacturer: Formalloy LLC; Model No: X-222 Item 3. Drawing A-410 REVISE Detail 5 - Interior Elevation of GENERAL LAB — SOUTH ELEVATION, per Sketch AD -1-A1, attached. Item 4. Drawing A-410 REPLACE Detail 8 - Interior Elevation of GENERAL LAB — EAST ELEVATION, per Sketch AD -1-A1, attached. Upson Hall Room 472 Laboratory Renovation Addendum No. 1 April 8, 2019 Page 2 Item 5. Drawing M-110, New Work Kcy Note #5 DELETE in its entirety. REPLACE with Connect new supply duct to existing supply duct riser with boot connection. Provide new fire/smoke damper, coordinate with FA and elec. trades. Coordinate the final location of the f/s damper with Cornell Enviromnental Health and Safety (EHS). Verify final location through shop drawing review or an onsite verification with EHS personnel. Item 6. Drawing P-1 10 ADD Detail 3, Compressed Air Regulator per attached sketch AD -1-P1. Item 7. Drawing EP -110 DELETE electrical connections for "Lens 450" equipinent REPLACE with electrical connections for "X-Scrics Machine" in Atomizer Room 472B as shown on Sketch AD -1 -El, attached. Item 8. Drawing E-501 REVISE "Panelboard PP -472B" schedule to reflect equipment revisions in Atomizer Room 4728 as shown on Sketch AD -I -E2, attached. Attachments: Sketches: AD -1-A1, AD -1-P1, AD -1-E1, and AD -1-E2 ****END OF ADDENDUM**** ro ria 2 0 SVVBR Project #18695.00 cn CD Cq C6 0. 41. pvsuel4P-ZLVwj umdfl li3w00 00.56981. \LLOZ sleP011 l!Ad le001-1.1.3 HIVd3113 3 8 ("5 SWBR Project #18695.00 \ Cornell University Z < Ex5 < CL CL ' ) gb:90:11 640Z/2/6 L2J vu'ApoomioLldolsAID—d314-ZL4LJJ ueH uosdn dtyg698L \stuatunoomdSpodysJasnVO :Hltid 3113 7 cq. t-4 Gr) - .0) Z \t. ;LT (-4 0 w >" Ct Z NIM LU Z/3 03 I- = I t I<) CD = C 7:1 m W ,,,, E ,t 20 < a. z. X 0 wp —41 co Z cr. E,74,44,.:,=444,,,,E4E.E4'444"Et uF w NV (6 L610Z/2/6 InrCzJarl-d3ini-ZaureilieH uosdfl 00`5692lyspnwnnolPzion slasnvO :Hrdd ii 1.5:RZ 4 6 LON/ 4 P'YOZ.,,n-d9141ZIV WHIHuosdn 00g6981-ASlueurrooCVZien \SJasill,3 ,H_LVd 3113 These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©309 South Franklin Street Syracuse NY 13202315 488 5635 | syracuse@swbr.comFILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:RevisionsSWBR Project #3/6/2019 9:05:02 AMC:\1-Local Revit Models 2017\18695.00 Cornell Upson Hall Rm 472_dylans.rvt18695.00DMKSCover SheetSDFYSG-000Bid DocumentsCornell UniversityUpson Hall Room 472 LaboratoryRenovation124 Hoy Rd, Ithaca, NY 14850March 5, 2019124 Hoy Rd, Ithaca, NY 14850March 5, 2019Upson Hall Room 472Laboratory RenovationBid Documents18695.00124 Hoy Rd, Ithaca, NY 14850Aerial PhotographLocation MapUPSON HALLUPSON HALLCAMPUS RDHOY RDARCHITECT & STRUCTURAL ENGINEER:SWBR309 SOUTH FRANKLIN STSYRACUSE, NY 13202315 488 5635SYRACUSE@SWBR.COMMECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION ENGINEERERDMAN ANTHONY145 CULVER ROAD, SUITE 200ROCHESTER, NY 14620585 427 8888 CLIENTCORNELL UNIVERSITYFACILITIES AND CAMPUS SERVICESHUMPHREYS SERVICE BUILDINGITHACA, NEW YORK 14853-3701DRAWING INDEXGENERALG-000 Cover SheetG-001 General Notes and LegendG-002 Code Compliance Drawings and Fire Safety PlansARCHITECTURALA-110 Partial Fourth Floor, Demo and Reflected Ceiling PlanA-410 Interior ElevationsA-501 Details, Schedules and SpecificationsFIRE PROTECTIONFA-110 Partial Fire Alarm Fourth Floor PlansFP-001 Fire Protection Symbols, Notes & AbbreviationsFP-110 Partial Fire Protection Fourth Floor PlansPLUMBINGP-001 Plumbing Symbols, Notes & AbbreviationsP-110 Partial Plumbing Fourth Floor PlansMECHANICALM-001 Mechanical Symbols, Notes & AbbreviationsM-110 Partial Mechanical Fourth Floor PlansM-500 Mechanical SchedulesM-501 Mechanical DetailsMP-110 Partial Mechanical Piping Fourth Floor PlanMI-600 BMS Controls Legend & NotesMI-601 Controls Schematic Room 472A & BMI-602 Controls Schematic Room 472MI-603 Controls Points List Room 472ELECTRICALE-001 Electrical Symbols, Notes & AbbreviationsE-501 Electrical Schedules & DetailsEL-110 Partial Lighting Fourth Floor PlansEP-110 Partial Power Fourth Floor PlansET-110 Partial Telecom Fourth Floor Plans GYPSUM BOARD / METAL STUD SERIES PARTITIONS3 5/8" METAL STUDS AT 16" O.C.(1) LAYER 5/8" GYPSUM BOARD AT ROOM SIDE ONLY.LEGENDINDICATES PARTITION TYPEINDICATES PARTITION HEIGHT ABOVEFINISHED FLOOR:"X" AFCPARTITION TO X" ABOVEFINISHED CEILINGUFCPARTITION TO UNDERSIDE OF FINISHED CEILINGX'-X"WHERE HEIGHT IS NOTED,CONSTRUCT WALL TO THATHEIGHT INCLUDING TOP OFWALL CAP4 7/8"3 5/8" METAL STUDS AT 16" O.C.(1) LAYER 5/8 " GYPSUM BOARD EACH SIDE.STC RATING: 49 (WITH INSULATION)A3UNBALANCED SERIES PARTITIONS4 1/4"U8XX**#WALLINDICATES PARTITION TYPEINDICATES FIRE RATED WALL & RATING OF WALL CONSTRUCTION IN HOURS SEE KEY ON CODE COMPLIANCE PLAN###ALL STUD PARTITIONS NOT INDICATED WITH APARTITION TYPE SHALL BE TYPE A-3, WITH SOUND ATTENUATION BLANKETSPARTITIONS WITH SOUND ATTENUATION BLANKETS:GYPSUM BOARD TO BE "TYPE X" UNLESS OTHERWISE NOTEDALL PARTITIONS ARE TO BE TO THE UNDERSIDE OF DECK UNLESS OTHERWISE NOTEDDIMENSIONS SHOWN FOR EACH PARTITION DESCRIPTION INDICATE FACE-TO-FACETHICKNESS OF MATERIALS LISTED FOR THAT PARTITIONPROVIDE LISTED U.L. FIRE-RESISTANT JOINT ASSEMBLIES @ TOP OFALL WALLS INDICATED TO BE FIRE-RESISTANT RATEDTHE TOP OF ALL PARTITIONS FRAMED AGAINST THE UNDERSIDE OFSTRUCTURES SHALL HAVE PROVISIONS FOR DEFLECTION & RESTRAINTPROVIDE CONTROL JOINTS IN GYPSUM BOARD WALLS & CEILINGS. FOR CEILINGS: • INSTALL CONTROL JOINT IN AREAS EXCEEDING 2500SF. • SPACE CONTROL JOINTS NOT MORE THAN 50 FEET O.C.• INSTALL CONTROL JOINTS WHERE CEILING FRAMING OR FURRING CHANGES DIRECTION. FOR PARTITIONS AND FURRING: • INSTALL CONTROL JOINTS IN PARTITIONS AND WALL FURRING RUNS EXCEEDING 30 FT.• SPACE CONTROL JOINTS NOT MORE THAN 30 FT O.C. • INSTALL CONTROL JOINTS IN FURRED ASSEMBLIES WHERE JOINTS OCCUR IN BASE SUBSTRATE OF EXTERIOR WALLS. CONTROL JOINTS IN FIRE-RESISTANT CONSTRUCTION REQUIRE FIRE-RATED JOINT SYSTEMS OR SPECIAL DETAILING. FOR STUD CONSTRUCTION NOT EXTENDING TO THE STRUCTURE, PROVIDEDIAGONAL BRACING FROM TOP OF WALL TO STRUCTURE ABOVE. INSTALLAT 12'-0" MAX SPACING AND @ EACH DOOR JAMBREFER TO CODE COMPLIANCE PLANS FOR PARTITION FIRE RESISTANCE RATINGS.GYPSUM BOARD JOINT TREATMENT IN CONCEALED SPACES SHALL BE FIRE FIRE TAPED. UNLESS OTHERWISE INDICATED IN A SPECIFIC UL DESIGN, JOINTS SHALL BE TAPED, AND JOINTS AND FASTENER HEADS COVERED WITH ONE COAT OF JOINT COMPOUND. BASE LAYERS IN MULTI-LAYER SYSTEMS ARE NOT REQUIRED TO HAVE JOINTS OR FASTENER HEADS TAPED OR COVERED WITH JOINT COMPOUND. GENERAL PARTITION NOTES:A.B.C.D.E.F.G.H.I.J.K.GENERAL NOTES:ALL GENERAL NOTES PERTAIN TO ALL ARCHITECTURAL (A-SERIES) DRAWINGS IN THIS SET.WHERE DIFFERENT FLOORING MATERIALS MEET, AND A SPECIFIC TRANSITION DETAIL IS NOT INDICATED, PREPARE SUBSTRATE WITH A TRANSITION HEIGHT BUILD UP USING TROWELABLE LEVELING AND PATCHING COMPOUND TO PRODUCE A FLUSH SMOOTH CONDITION. TROWEL MATERIAL FOR A MINIMUM DISTANCE OF 2 FEET FROM A FEATHER EDGE CONDITION UP TO A MAXIMUM SINGLE LAYER APPLICATION THICKNESS OF 1/2". FOR APPLICATIONS THICKER THAN 1/2", PLACE MATERIAL IN SUCCESSIVE LAYERS, SCORING PREVIOUS LAYER, UP TO A MAXIMUM THICKNESS OF 1".PROVIDE CONCEALED STEEL STUD BLOCKING OR 4" x 18 GA CONTINUOUS STEEL STRAPPINGATTACHED TO FACE OF STUDS BEHIND ALL WALL MOUNTED ITEMS SUCH AS: WALL CABINETS,SHELVING, COAT RODS, GRAB BARS, HANDRAILS, TOILET ACCESSORIES, ETC. SEE INTERIOR ELEVATIONS & FURNITURE PLANS FOR ADDITIONAL INFORMATION AND SCOPEFLOOR FINISH TRANSITIONS/CHANGES SHALL OCCUR BELOW THE DOORDIMENSIONS LOCATING INTERIOR PARTITIONS ARE TO THE FACE OF WALL (EXCLUDING FINISHMATERIALS SUCH AS - BUT NOT LIMITED TO: CERAMIC TILE, AND WOOD PANELING) UNLESS NOTEDOTHERWISE. SEE PARTITION SCHEDULE FOR WALL THICKNESSALL EXISTING DIMENSIONS ARE APPROXIMATE AND FOR CONTRACTORS VERIFICATIONS. IFDISCREPANCIES ARISE, NOTIFY THE ARCHITECT (AND/OR CONSTRUCTION MANAGER) PRIORTO PROCEEDING WITH THE WORK THAT MAY BE EFFECTED BY THE DIMENSION CHANGEEVERY ATTEMPT HAS BEEN MADE TO INDICATE PERTINENT EXISTING UTILITIES AND CONDITIONSAS ACCURATELY AS POSSIBLE FROM EXISTING SURVEYS, DRAWINGS AND OTHER DATA. PRIORTO THE BID OPENING, CONTRACTORS SHALL WALK THE JOB SITE AND SATISFY THEMSELVESTO EXISTING CONDITIONS. THE ARCHITECT SHALL BE CONSULTED WHEN ANY QUESTIONARISES RELATIVE TO MATERIALS NOT SPECIFICALLY SHOWN OR SPECIFIEDALL EXISTING WORK (CEILINGS, FLOORS, WALLS, PARTITIONS, FINISHES, ETC.) DISTURBED BY NEW CONSTRUCTION, INCLUDING MECHANICAL, PLUMBING, AND ELECTRICAL, SHALL BE PATCHED AND REPAIRED TO RESTORE SURFACES TO THE ORIGINAL CONDITION AFTER INSTALLATION OF OTHER WORKPENETRATIONS THROUGH FIRE-RESISTANT CONSTRUCTION SHALL BE BUILT IN ACCORDANCEWITH U.L. LISTED THROUGH-PENETRATION FIRESTOP SYSTEMS. SEE CODE COMPLIANCE PLANFOR PARTITION LOCATIONS.1.2.3.4.5.6.7.8.9.PROVIDE SOUND ATTENUATION BLANKETS IN ALL CAVITY SPACES IN WALL FULL HEIGHTTHICKNESS OF BLANKETS IN STUD WALLS SHALL BE EQUAL TO THICKNESS OF CAVITY TO NEAREST 1/2", UNLESS INDICATED OTHERWISEPARTITIONS TO BE SEALED @ THE PERIMETER, BEHIND CONTROL JOINTS, AROUND OPENINGS AND AT ALL PENETRATIONS WITH EACH LAYER OF BOARD TO RECEIVE A BEAD OF SEALANTSEE WALL TYPE DESCRIPTIONS FOR CONDITIONS REQUIRING MINERAL FIBER SAFING INSULATION BATTS1.2.3.4.7 1/4"6" METAL STUDS AT 24" O.C.(1) LAYER 5/8 " GYPSUM BOARD EACH SIDE.A6309 South Franklin Street Syracuse NY 13202315 488 5635 | rochester@swbr.comThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©FILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions3/6/2019 9:05:02 AMC:\1-Local Revit Models 2017\18695.00 Cornell Upson Hall Rm 472_dylans.rvt18695.00DMKSGeneral Notes andLegendsSDFYSG-001Bid DocumentsCornell UniversityUpson Hall Room 472 LaboratoryRenovation124 Hoy Rd, Ithaca, NY 14850March 5, 2019AB Anchor boltA/C Air condition(ing) (ed)ACC AccessibleACCU Air cooled condensing unitACI American Concrete InstituteACT Acoustical ceiling tileACM Asbestos containing materialACOUS PNL Acoustical panelACS PNL Access panelADDL AdditionalADJ Adjustable, adjacentADH AdhesiveAFF Above finished floorAGGR AggregateAHU Air handling unitAISC American Institute of Steel ConstructionAISI American Iron and Steel InstituteALT AlternateALUM AluminumANOD AnodizedAPPROX ApproximateARCH Architect(ural)ARD Auxillary roof drainASD Allowable stress designASTM American Society for Testing and MaterialsAWP Acoustical wall panelAWS American Welding SocietyBAT BattenB/B Back to backB BD Base boardBCNYS Building Code of New York StateBITUM BituminousBD BoardBLDG BuildingBLKG BlockingBM Beam, BenchmarkBOT BottomBR BedroomBRG BearingBRZ BronzeBSMT BasementBTWN BetweenBUR Built up roofingBW Both waysCCTV Closed circuit televisionCAB CabinetCB Catch basin, Corner beadCH BD ChalkboardCEM CementCF Contractor furnishedCFMF Cold-formed metal framingCF/CI Contractor furnished/ Contractor installedCF/OI Contractor furnished/ Owner installedCG Corner guardCH Coat hookCI Cast ironCIP Cast in place, Cast iron pipeCJ Control jointCL CenterlineCLG CeilingCLO ClosetCLR Clear, ColorCMT Ceramic mosaic tileCMU Concrete masonry unitCNTR CounterCO Cleanout, Cased opening, CompanyCOL ColumnCONC ConcreteCONF ConferenceCONN Connect(ion)CONSTR ConstructionCONT Continue(ous)CONTR Contract(or)COORD CoordinateCPT CarpetCSJ Construction jointCSK Counter sunkCT Ceramic tile, Count, Current transformerCTR CenterCW Cold water piping, Casement windowCU CubicCUH Cabinet unit heaterCU YD Cubic yardD Deep, DepthD Penny (nail)db Bar diameterDBL DoubleDEFS Direct-applied exterior finish systemDEG DegreeDEMO DemolitionDEPT DepartmentDET DetailDF Drinking fountainDIA OR ø DiameterDIAG Diagonal, DiagramDIM DimensionDIFF DiffuserDIR DirectionDISP DispenserDIV DivisionDMPF Damp proofingDL Dead loadDN DownDO DittoDR Door, DriveDS DownspoutDW DishwasherDWVDrainage waste & ventDWGDrawingDWLDowelEEastEAEachEBCNYSExisting Building Code of New York StateECElectrical contractorEFEach faceEIFSExterior insulation and finish systemEJExpansion jointELASElastomericELElevationELECElectric(al)ELEVElevatorEMEntry mat, Expanded metalEMEREmergencyENCLEnclosureENGREngineerEOSEdge of slabEPElectric panelEQEqualEQUIPEquipmentESEmergency showerETCEt ceteraETRExisting to remainEWEach wayEWCElectric water coolerEXISTExistingEXCExcavation, ExcavateEXPExpand, ExpansionEXTExterior, External, ExtinguisherF/FFace to faceFAAPFire alarm annunciator panelFACPFire alarm control panelFDFloor drainFDTNFoundationFEFire extinguisherFECFire extinguisher cabinetFHCFire hose cabinetFINFinish(ed)FIXTFixtureFLASHFlashingFLEXFlexibleFLOURFluorescentFLGFlooring, flangeFOFinished openingFPFire protection, FireproofFRTWFire retardant treated woodFTFoot, FeetFTGFootingFTRFinned tube radiationFURNFurnace, Furniture, FurnishFUTFutureFWCFabric wall coveringGAGageGALGallonGALVGalvanizedGBGrab barGCGeneral contract(or)GFRCGlass fiber reinforced concreteGFRGGlass fiber reinforced gypsumGLGlass, Ground levelGL BLKGlass blockGLU LAMGlued laminated beamGRGrade, GrossGWTGlazed wall tileGYPGypsumGYP BDGypsum boardGYP PLASGypsum plasterHBHose bibbHCHollow core, Hose cabinetHCPHandicappedHDWHardwareHDWDHardwoodHMHollow metalHOHold openHORIZHorizontalHPHigh point, HorsepowerHRHourHSSHollow structural sectionHTHeightHTGHeatingHTRHeaterHVACHeating, ventilating and air conditioningHWHot waterHYDHydrantIDInside diameterINInchesINCLIncludedINCANDIncandescentINFOInformationINSULInsulationINTERMIntermediateINTInteriorJANJanitorJSTJoistJTJointKIP1000 PoundsKITKitchenKOKnockoutKPLKick plateLLiter, AngleLAMLaminate(d)LAULaundryLAVLavatoryLBPoundLBLLabelLDLoadLFLinear feet (foot)LHLeft hand, Latent heatLINLinearLKRLockerLLLive loadLLHLong leg horizontalLLVLong leg verticalLOCLocationLRFDLoad & resistance factor designLTLightLTGLightingLWCLight-weight concreteMACHMachineMAINTMaintenanceMASMasonryMATLMaterialMAXMaximumMCMechanical contractorMCBMetal corner beadMDOMedium density overlayMDFMedium density fiberboardMECHMechanicalMEPMechanical, electrical, plumbing and fire protectionMEZZMezzanineMFRManufacturerMHManholeMMMillimeterMIFRCMastic/intumescent fire-resistive coatingMINMinimumMISCMiscellaneousMLWKMillworkMOMasonry openingMRK BDMarker boardMTDMountedMTLMetalMULLMullionNNorthNATNaturalNCOMBLNoncombustibleNICNot in contractNO OR #NumberNOMNominalNORMNormalNRCNoise reduction coefficientNTSNot to scaleNWCNormal weight concreteO/OOut to outOAOverall, Outside airOCOn centerODOutside diameterOF/CIOwner furnished, Contactor installedOF/OIOwner furnished, Owner installedOFDOverflow drainOFFOfficeOHOpposite handOH DROverhead (coiling) doorOPNGOpeningOPPOppositeOPTOptional, OptimumOZOuncePAPublic addressPBDParticleboardPCPlumbing contractor, Portland cementPCCPrecast concretePCTPorcelain ceramic tilePEDPedestalPENDPendantPERPeriodPERFPerforatedPGBDPeg boardPLPlate, Property linePLFPonds per linear footPLAMPlastic laminatePLASPlasterPLBPlumbingPLYWDPlywoodPNLPanelPOLPolishedPORCPorcelainPOSPositive, PositionPPTPressure-preservative treatedPRPairPREFABPrefabricatePREFINPrefinishPREPPreparationPROJProjectPROJ SCRN Projection screenPSFPounds per square footPSIPounds per square inchPTPaint, Post tensionPTNPartitionPVCPolyvinyl chloride (plastic)PVGPavingQTQuarry tileQTRQuarterQTYQuantityRRiser, Radius, Thermal resistanceRBRubber base, Resilient baseRCPReinforced concrete pipe, Reflected ceiling planRDRoof drain, RoadRECRecessedREFRefrigeratorREFLReflectREGRegister, RegulationREINFReinforcedREQDRequiredRESILResilientREVRevisionRFResilient flooringRFGRoofingRHRight hand, Roof hatchRMRoomRORough openingROWRight of wayRTURoof top unitRVRoof ventRWBRubber wall baseSSouthSABSound attenuation battsSANSanitarySCSolid core, Shading coefficientSCHEDScheduleSEALSealer on floor (finish)SECTSectionSFSquare foot, Safety factorSFRMSprayed fire-resistiveMaterialSGTStructural glazed tileSHTSheetSHRShowerSIMSimilarSOGSlab on gradeSPStandpipe, Sump pitSPASpacesSPKRSpeakerSPECSpecificationSQSquareSRDSecondary roof drainSSService sinkSSMSolid surface materialSSPStainless steel pipeSSTStainless steelSTStainSTAStationSTCSound transmission classSTDStandardSTIFFStiffenerSTLSteelSTORStorageSTRStraight, StringersSTRUCTStructuralSUSPSuspendedSVSheet vinylSYSquare yardTTreadT/Top ofT&BTop and bottomT&GTongue and grooveTELTelephoneTHRESThresholdTEMPTemporaryTERTerrazzoTHKThick(ness)TK BDTack boardTMPDTemperedTOCTop of concreteTOMTop of masonryTOPOTopography, TopographicTOSTop of steelTOWTop of wallTPDToilet paper dispenserTSTATThermostatTVTelevisionTYPTypicalUHeat transfer coefficientUCUndercutUCLUnder cabinet lightingUGNDUndergroundUHUnit heaterULUnderwriter's laboratoriesUNEXUnexcavatedUNFINUnfinishedUONUnless otherwise notedUTILUtilityUVUnit ventilatorVARNVarnish(ed)VBVinyl baseVCTVinyl composition tileVENTVentilationVERTVerticalVESTVestibuleVIFVerify in fieldVINVinylVOLVolumeVRVapor retarderVTVinyl tileV SHTVinyl sheetVWCVinyl wall coveringWWestW/WithWCWater closet, Wall coveringW/OWithoutWDWoodWDWWindowWFWide flangeWD GDWood guardWHWater heaterWIWrought ironWMWire meshWPWaterproofing, Working pointWRWater repellent, weather resistantW RECPTWaste receptacleWSCTWainscotWTWeight, Watertight, Water tableWWFWelded wire fabricXByYDYardC12AC12A-XXX1432XSCALE: X"=1'-0"Title112BA18'-0" AFF1Batt insulationRigid insulationWood blocking (intermittent) StoneGravel or crushed stoneWood framing (continuous)Finish woodSteel - large scaleSteel - small scalePlywoodConcreteConcrete masonry unitBrick(Other metals as noted)View titleBuilding / wall section cutDetail - blow upExterior elevationInterior elevations1011Partition typeRoom numberDoor numbersWindow typeRevisionORORUndisturbed earth001100A001Structural gridViewing directionDetail no.Drawing no.Detail no.Drawing no.Drawing no.Elevation no.Plan key noteDemolition key noteCeiling type and heightDrawing symbols(Other metals as noted)A-XXXXA-XXXXGypsum, sand, mortarA-XXXXDrawing no.Elevation no.Detail no.Detail section cutDetail no.DRAWING NO.A-XXXXViewing directionAccessibilityAccessible unitV/HAUVisual / hearing accommodation unitMaterial symbolsArchitectural / Structural abbreviations E2E2E1E1E1FPE1FP111FP1FPFEE2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2E2FEE2E2E2E2E2E2E2E2E2E2E2E2E2E2E2LIFE SAFETY LEGEND: COMMON PATH OF EGRESS TRAVEL (NOT TO EXCEED 100 FEET) EGRESS ACCESS TRAVEL DISTANCE (NOT TO EXCEED 300 FEET)CPOE = X'-X"EATD = X'-X"EEXIT. MAINTAIN OPERATIONAL AT ALL TIMES DURING CONSTRUCTION.STORAGEROOM NAMEACCESSIBLE ELEMENTPER ICC/ANSI A117.1-2003NOTE: BUILDING IS FULLY SPRINKLEREDEXISTING 2-HOUR RATED FIRE BARRIEREXISTING 1-HOUR RATED FIRE BARRIEREXISTING 1-HOUR RATED FIRE PARTITION1-HOUR RATED FIRE BARRIER1-HOUR RATED FIRE PARTITIONNOTE: AT EXISTING FIRE BARRIERS/PARTITIONS, REFER TO 'A' SERIES DRAWINGS FOR WORK REQUIRED TO MAKE COMPLIANT. CONTRACTOR SHALL VERIFY IN FIELD THE CONTINUITY OF EXISTING RATED ASSEMBLIES FOLLOWING SELECTIVE DEMOLITION. CODE COMPLIANCE PLAN GENERAL NOTESTHE FOLLOWING BUILDING AND ACCESSIBILITY CODES AND STANDARDS ARE APPLICABLE TO THIS PROJECT:1.A.B.C.D.E.F. G.H.I.J.K.L.M.2015 INTERNATIONAL BUILDING CODE2015 INTERNATIONAL EXISTING BUILDING CODE2015 INTERNATIONAL FIRE CODE2015 INTERNATIONAL PLUMBING CODE2015 INTERNATIONAL MECHANICAL CODE2015 INTERNATIONAL FUEL GAS CODE2017 NEW YORK STATE UNIFORM CODE SUPPLEMENTNATIONAL ELECTRICAL CODE, NFPA 70 - 2014 EDITION AS REFERENCED BY THE NYS CODES ABOVE.ICC/ANSI A117.1, ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES - 2009 EDITION AS REFERENCED BY THE NYS CODES ABOVE.U.S. DEPARTMENT OF JUSTICE, 2010 AMERICANS WITH DISABILITIES ACT (ADA) STANDARDS FOR ACCESSIBLE DESIGN.2015 INTERNATIONAL ENERGY CONSERVATION CODE2013 ASHRAE 90.12016 ENERGY CODE SUPPLEMENTCODE COMPLIANCE DRAWINGS ARE INTENDED TO ASSIST IN THE PERMIT PROCESS AND TO PROVIDE GENERAL INFORMATION TO THE CONTRACTORS WITH RESPECT TO LIFE-SAFETY PROVISIONS WITHIN THE IMMEDIATE EXTENTS OF THE PROJECT. THESE DRAWINGS SHOULD NOT BE USED TO DETERMINE THE SCOPE OF OTHER WORK SPECIFICALLY INDICATED ELSEWHERE IN THE DOCUMENTS. THESE DRAWINGS SHALL BE USED FOR THE LOCATIONS OF FIRE-RESISTANT RATED WALL CONSTRUCTION.2.REFERENCE FCNYS CHAPTER 33 FOR FIRE SAFETY PROVISIONS DURING CONSTRUCTION, DEMOLITION AND ALTERATION OPERATIONS.3.WHEN THE PREFIX "E" IS INDICATED ON THE CODE COMPLIANCE FLOOR PLAN, IT DENOTES EXISTING WALL CONSTRUCTION WITH A PRESUMED FIRE-RESISTANCE RATING OF THE TYPE INDICATED. LOCATIONS ARE BASED ON CURRENT CODE REQUIREMENTS. THE ACTUAL CONDITIONS IN THE FIELD HAVE NOT BEEN VERIFIED TO CONFIRM COMPLIANCE. NEW PENETRATIONS REQUIRE FIRESTOP SYSTEMS FOR THE HOURLY RATING INDICATED.PENETRATIONS THROUGH FIRE-RESISTANT CONSTRUCTION SHALL BE BUILT IN ACCORDANCE WITH U.L. LISTED THROUGH-PENETRATION FIRESTOP SYSTEMS. SEE CODE COMPLIANCE PLAN FOR FIRE-RATED PARTITION LOCATIONS. 4.5.BUILDING DATA AND CODE COMPLIANCECLASSIFICATIONS OF BUILDING, AS SPECIFIED IN THE 2015 EDITION OF THE BUILDING CODE OF NEW YORK STATE ARE AS FOLLOWS:BUILDING DATA:CONSTRUCTION CLASSIFICATION:IB (ASSUMED)BUILDING OCCUPANCY CLASSIFICATION:B [BUSINESS], A-3 [ASSEMBLY] FIRE PROTECTION SYSTEM:FULLY SPRINKLEREDRENOVATION AREA:915 SFCONTROL AREA:SOUTH WING (FOURTH FLOOR)EXISTING 2 HR FIRE BARRIER SEPARATIONEXISTING FLOOR ASSEMBLY:2 HR FIRE-RATEDALTERATION CLASSIFICATIONS OF WORK, AS SPECIFIED IN THE 2015 EDITION OF THE BUILDING CODE OF THE NEW YORK STATE ARE AS FOLLOWS:ALTERATION - LEVEL 2LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION OF DOORS AND WINDOWS, THE RECONFIGURATION OR THE EXTENSION OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL SYSTEM. LEVEL 2 ALTERATIONS SHALL ALSO COMPLY WITH THE REQUIREMENTS OF A LEVEL 1 ALTERATIONS.LEVEL 1 ALTERATIONS INCLUDE THE REMOVAL AND REPLACEMENT OR THE COVERING OF EXISTING MATERIALS, ELEMENTS, EQUIPMENT, OR FIXTURES USING NEW MATERIALS, ELEMENTS, EQUIPMENT, OR FIXTURES THAT SERVE THE SAME PURPOSE. FIRE RESISTANCE RATING SCHEDULE FOR BUILDING ELEMENTSCONSTRUCTION CLASSIFICATION TYPE IB . ADDITIONAL FIRE-RESISTANCE REQUIREMENTS THROUGHOUT THE BUILDING ARE BASED ON OCCUPANCY. REFER TO CODE COMPLIANCE PLANS AND G-SERIES DRAWINGS FOR MORE INFORMATION.DESCRIPTIONTEST REFERENCECOMMENTSFIRE RESISTANCEREQUIRED RATING / HR STRUCTURAL FRAME INCLUDING COLUMNS, GIRDERS AND BEAMS2BEARING WALLS:2FLOOR CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS2ROOF CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS12NOTE: THIS TABLE INDICATES MINIMUM BUILDING FIRE RESISTANCE REQUIREMENTS BASED ON CONSTRUCTION CLASSIFICATION AND IN ACCORDANCE WITH NYSBC TABLE 601. NON-BEARING WALLS & PARTITIONS:00FIRE RESISTANCEPROVIDED RATING / HR EXISTING0INTERIOR EXISTING ASSEMBLY; POURED CONCRETE FLOOR SLAB EXISTING ASSEMBLYEXTERIORINTERIOREXTERIOR EXISTING ASSEMBLY EXISTINGN/AN/AN/AEXISTINGEXISTING ASSEMBLY; PROTECTED STRUCTURAL STEEL EXISTINGN/AEXISTINGEXISTINGEXISTINGEXISTINGPROJECT WORK AREA. SEE ENLARGED PLAN 2/G-002 FOR ROOM INFORMATION.CPOE= 79'-0"EATD=96'-0"HATCH INDICATES CONTROL AREA(1 OF 2)CONTROL AREA(2 OF 2)DE568375 SFGENERAL LAB472359 SFATOMIZER ROOM472B1CACCESSIBLE WORKSPACE(FRONT APPROACH)ACCESSIBLE FUME HOOD (ADJUSTABLE HEIGHT)ACCESSIBLE SINK AND EYE WASH (FRONT APPROACH)PROJECT WORK AREAFLASER ROOM472A3' - 0"EXIST 2HR RATED SHAFTWALL ASSEMBLY309 South Franklin Street Syracuse NY 13202315 488 5635 | rochester@swbr.comThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©FILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions3/6/2019 9:05:06 AMC:\1-Local Revit Models 2017\18695.00 Cornell Upson Hall Rm 472_dylans.rvt18695.00DMKSCode ComplianceDrawings and FireSafety PlansSDFYSG-002Bid DocumentsCornell UniversityUpson Hall Room 472 LaboratoryRenovation124 Hoy Rd, Ithaca, NY 14850March 5, 2019 1" = 20'-0"1FOURTH FLOOR PLAN - CODE COMPLIANCE 3/16" = 1'-0"2PARTIAL FOURTH FLOOR CODE PLANNORTH FEDEEM SHOWERUTILITY TABLE (2'-6" x 5'-0")568A-4101234A-4105678A-41091012114723467EXIST ACCESS PANEL375 SFGENERAL LAB472359 SFATOMIZER ROOM472B1A1C1B8410+/-1' - 8"14' - 10 1/4"14' - 0 5/8"472A472BEXIST EYEWASH WANDCLASS D FIRE EXTINGUISHER5B5A3A-50110' - 0"2' - 7"13A-410F121 SFLASER ROOM472AEXIST FAN COIL ACCESS PANELA61610A16A9217A17B17C17CCUP SINKREINSTALL SALVAGED SHELVING3' - 0"3' - 0"3' - 0"ALIGN 2' - 7"+/-8' - 2 7/8"+/-8' - 8 7/8"+/-9' - 4 1/4"EXIST STATIC DISSIPATIVE RESILIENT FLOORING, TYPFH-2FH-1ACID CAB.FLAM. CAB.EXIST FAN COIL ACCESS PANELEXIST 2HR RATED SHAFTWALL CONSTRUCTION.APPROXIMATE LOCATION OF MECHANICAL REMOVALS, REFER TO MECHANICAL DRAWINGS. PATCH AND REPAIR OPENING TO MAINTAIN FIRE RESISTANCE RATING. APPROXIMATE LOCATION OF MECHANICAL REMOVALS, REFER TO MECHANICAL DRAWINGS. PATCH AND REPAIR OPENING TO MAINTAIN FIRE RESISTANCE RATING. DE568E11' - 1"E11' - 1"E11' - 1"E11' - 1"E11' - 1"E8' - 3"359 SFATOMIZER ROOM472B375 SFGENERAL LAB472(ETR)(ETR)(ETR)(ETR)(ETR)F121 SFLASER ROOM472ASOFFIT 9'-5" (ETR)SOFFIT 9'-5" (ETR)SOFFIT 9'-5" (ETR)SOFFIT 9'-5" (ETR)SOFFIT 9'-5" (ETR)SOFFIT 9'-5" (ETR)SOFFIT 9'-5" (ETR)RELOCATE EXIST LINEAR LIGHT FIXTURE, REFER TO ELECTRICALEXIST ACT CEILING AT HALLWAY; REMOVE AND REINSTALL AS REQUIRED TO PERFORM MECHANICAL WORK. REFER TO MECHANICAL DRAWINGS.EXIST GYP BD SOFFIT TO REMAINEXIST ACT CEILING AT OFFICE; REMOVE AND REINSTALL AS REQUIRED TO PERFORM MECHANICAL WORK. REFER TO MECHANICAL DRAWINGS.EXIST GYP BD CEILING TO REMAINOFFICECORRIDORELECTRICALLABORATORYDE568REMOVE & SALVAGE EXIST WALL MOUNTED SHELVING AND SURFACE RACEWAY. PATCH REPAIR AND PREP EXIST GYP BD TO MATCH EXIST ADJACENT. SHELVING TO BE REINSTALLED, SEE PLAN 2/A-110.REMOVE & SALVAGE OVERHEAD CARRIER (UNISTRUT). TURN OVER TO OWNER. PATCH REPAIR AND PREP EXIST GYP BD TO MATCH EXIST ADJACENT.REMOVE & SALVAGE EXIST WALL MOUNTED SHELVING AND SURFACE RACEWAY. TURN OVER TO OWNER. PATCH REPAIR AND PREP EXIST GYP BD TO MATCH EXIST ADJACENT.EXIST CASEWORK AND PLUMBING TO REMAIN. PROVIDE TEMPORARY PROTECTION DURING DEMOLITION AND CONSTRUCTION.15' - 0"9' - 0"NOTE: EXIST FLOORING AND BASE TO REMAIN. PROVIDE TEMPORARY PROTECTION DURING DEMOLITION AND CONSTRUCTION.GENERAL NOTES:1. ALL FLOORS, WALLS, CEILINGS, AND OTHER SURFACES THAT ARE TO REMAIN ARE TO BE PATCHED, REPAIRED, AND REFINISHED PRIOR TO FINISH INSTALLATION. ALL SURFACES ARE TO BE RESTORED TO THEIR ORIGINAL CONDITION AND/OR MATCH THE ADJACENT SURFACES.2. FIRESTOP ALL FLOOR PENETRATIONS (USED/UNUSED/ABANDONED) WITH 2 HR UL LISTED PENETRATION FIRESTOPPING.3. FOR ALL OWNER FURNISHED / CONTRACTOR INSTALLED EQUIPMENT: CONTRACTOR TO MOVE FROM GROUND FLOOR TO WORKSPACE AND INSTALL.4. PROPOSED WALL PARTITIONS TO BE FRAMED TO UNDERSIDE OF EXIST CEILING/DECK. GYP BD TO BE INSTALLED AROUND EXISTING UTILITIES TO REMAIN (I.E. PIPING, CONDUIT, ETC.) AND FINISHED NEATLY OR PROVIDE ESCUTCHEONS.GENERAL DEMOLITION NOTES:1. EVERY ATTEMPT HAS BEEN MADE TO DOCUMENT PERTINENT EXISTING CONDITIONS FROM EXISTING DRAWINGS AND LIMITED FIELD INSPECTION. PRIOR TO THE SUBMISSION OF BIDS, CONTRACTORS SHALL WALK THE SITE AND SATISFY THEMSELVES TO EXISTING VISUAL CONDITIONS. THE ARCHITECT SHALL BE CONSULTED WHEN ANY QUESTION ARISES RELATIVE TO MATERIALS AND CONDITIONS NOT SPECIFICALLY SHOWN OR SPECIFIED.2. ALL EXISTING WORK (CEILING, FLOORS, WALLS, FINISHES, ETC.) DISTURBED BY NEW CONSTRUCTION SHALL BE PATCHED AND REFINISHED. PATCHING AND FINISH WORK IS THE REPAIR WORK REQUIRED TO RESTORE SURFACES TO THE ORIGINAL CONDITION AND/ OR MATCHING THE ADJACENT SURFACES. MISCELLANEOUS FINISH REQUIREMENTS TO WALL, FLOOR AND CEILING IN AREAS AFFECTED BY DEMOLITION HAVE NOT BEEN TOTALLY INCORPORATED INTO THE ROOM FINISH SCHEDULE. REFER TO THE DEMOLITION, FLOOR AND REFLECTED CEILING PLANS FOR ADDITIONAL CUTTING, PATCHING AND REFINISHING WORK SCOPE.3. THE EXISTING FIRE-RESISTANT CONSTRUCTION MUST BE MAINTAINED OR MADE TO COMPLY WITH THE REQUIREMENTS AS ESTABLISHED BY THIS CONTRACT. SEE THE CODE COMPLIANCE PLANS FOR THE FIRE RESISTANT RATINGS OF EXISTING AND NEW CONSTRUCTION.4. CARE SHALL BE TAKEN TO LIMIT IMPACT OF CONSTRUCTION ON THE SURROUNDING OCCUPANTS AND OPERATIONS DURING THE PROJECT. SAFE LEGAL PASSAGES SHALL BE PROVIDED FOR ALL BUILDING OCCUPANTS DURING ALL THE PHASES OF THIS PROJECT.5. WHEN EXISTING CONSTRUCTION WHICH IS TO REMAIN IS DAMAGED DURING THE COURSE OF CONSTRUCTION AS A RESULT OF CONTRACTOR'S WORK, IT SHALL BE REPAIRED AND/OR REPLACED WITH SIMILAR OR LIKE MATERIALS, SUBJECT TO ARCHITECT'S APPROVAL AND WITHOUT COMPENSATION.6. 'REMOVE' IS DEFINED AS DETACH FROM EXISTING CONSTRUCTION AND LEGALLY DISPOSE OF OFF-SITE UNLESS INDICATED TO BE SALVAGED OR REINSTALLEDUPSON HALLNORTHRCP LEGENDGYP BD SOFFITGENERAL NOTES1. ALL EXPOSED GYPSUM BOARD CEILINGS AND SOFFITS TO BE PAINTED WITH PT-12. SEE ELECTRICAL DRAWINGS FOR LIGHT FIXTURE SPECIFICATIONSCEILING TYPESEEXISTING TO REMAIN LINEAR LIGHT FIXTURE309 South Franklin Street Syracuse NY 13202315 488 5635 | rochester@swbr.comThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©FILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions3/6/2019 10:01:46 AMC:\1-Local Revit Models 2017\18695.00 Cornell Upson Hall Rm 472_dylans.rvt18695.00DMKSPartial Fourth Floor,Demo and ReflectedCeiling PlanSDFYSA-110Bid DocumentsCornell UniversityUpson Hall Room 472 LaboratoryRenovation124 Hoy Rd, Ithaca, NY 14850March 5, 2019 1/4" = 1'-0"2ROOM 472 FLOOR PLANEQUIPMENT LISTNUMBERQUANTITYEQUIPMENT NAMEMANUFACTURERMODEL NO.OWNERFURNISHEDOWNERINSTALLEDCONTRACTORFURNISHEDCONTRACTORINSTALLED1A1FURNACE + ATOMIZERARCASTARC 200 WITH ATOMIZERXX1B1POWER SUPPLYARCASTINT-0110XX1C1PACKAGED HEAT EXCHANGERARCASTXX21OPENSLM-EX WORKSTATIONUNIVERSALTECHNOLOGYCORPORATIONOPENSLM-EXWORKSTATIONXX31GLOVE BOXVACUUM TECHNOLOGYINC.SUPER GLOVE BOXXX42OPTICAL TABLESTHOR LABCUSTOM SIZE: 5'-10" x 3'-10"XX5A15'-0" FUME HOODMOTT7371010XX5B16'-0" FUME HOODMOTT7471010XX61POLISHING EQUIPMENTBUEHLERECOMET 250 PRO GRINDERPOLISHERXX71YTTERBIUM FIBER LASERIPG PHOTONICSYLR-500-AC-Y14XX81COMPACT PULSED ND: YAG LASERQUANTEL LASERQ-SMART 850XX91FLAMMABLE CABINETGLOBAL INDUSTRIAL298541XX101LENS 150 ADDITIVE MANUFACTURINGCONTROLLED ATMOSPHERE SYSTEMOPTOMECLENS 150XX10A1LENS 150 POWDER FEEDEROPTOMECLENS 150XX112DEFEATABLE ACCESS CONTROL KIT(SEE ELEVATIONS FOR LOCATIONS)LASER SAFETYSYSTEMSLSS2388XX122EMERGENCY CRASH MODULE (SEEELEVATIONS FOR LOCATIONS)LASER SAFETYSYSTEMSLSS2383XX131LASER WARNING MODULE (SEEELEVATIONS FOR LOCATION)LASER SAFETYSYSTEMSLSS2380XX141INTERLOCK CONTROL MODULE (SEEELEVATIONS FOR LOCATION)LASER SAFETYSYSTEMSLSS2381XX152LASER / SHUTTER INTERFACEMODULE (SEE ELEVATIONS FORLOCATIONS)LASER SAFETYSYSTEMSLSS2384XX161WIRE EDM MAIN MACHINESEEPELW90-1 WEDMXX16A1WIRE EDM COOLING CIRCULATORSEEPELW90-1 WEDMXX17A112 CYLINDERS (4X3) - BARRICADE -GAS CYLINDER RACKUSA SAFETYBR4X3FSXX17B12 CYLINDERS - WALL MOUNT -STAINLESS STEEL - GAS CYLINDERBRACKETUSA SAFETYGB200SSFSXX17C21 CYLINDER - 2 RESTRAINTS - GASCYLINDER STANDUSA SAFETYGR175FSXX#INDICATES EQUIPMENT KEYNOTE 1/4" = 1'-0"3ROOM 472 RCP 1/4" = 1'-0"1ROOM 472 DEMOLITION PLANKEYPLAN 21010A17C101A1B472BGAS DISTRIBUTIONCLASS D FIRE EXTINGUISHER921AMANIFOLDGAS DISTRIBUTION16917AEXIST ACCESS PANEL2' - 6"EXIST PIPE CHASE13A-410161016A3472A472B'LASER IN-USE' LIGHTED SIGNAGEKEYPAD1112133' - 4"4' - 0"5' - 0"17B7' - 0"EMERGENCY SHOWER1' - 6"9"9"WALL MOUNTED SAFETY GLASSES HOLDEREXIST FAN COIL ACCESS PANEL3' - 6"2' - 10"LABORATORY CASEWORK2' - 10"5B5A62' - 6"1' - 8"2' - 10"4' - 0"3' - 0"3' - 0"3' - 0"3' - 0"2' - 0"2' - 0"6' - 0"5' - 0"ACID CAB.FLAM. CAB.9' - 0"EXIST CABINETRY TO REMAINEPOXY COUNTERTOP WITH BACK & SIDE SPLASH (BOTH ENDS) 3A-5013' - 6"SURFACE MOUNTED RACEWAY, REFER TO ELECTRICALHEIGHTADJUSTHEIGHTADJUSTCUP SINK(1) REMOVABLE BASE CABINET ON CASTERS; WALL BASE TO EXTEND BACK ALONG ADJACENT CABINETS AND BACK WALLSIDE SPLASHFULL DEPTH ADJUSTABLE SHELVES, TYPCOUNTERTOP SUPPORTLABORATORY CASEWORKLABORATORY CASEWORK472841' - 6"1' - 0"1' - 0"4' - 8"6' - 8"SURFACE MOUNTED RACEWAY, SEE ELECTRICAL1' - 4"4784472A11CONTROL MODULE11PUSH TO EXIT1412158"3' - 4"8"3' - 4"CABLE PASS THRU PLATE ABOVE TABLE4741' - 6"4' - 8"1' - 0"1' - 0"3' - 0"3' - 0"3' - 0"6' - 8"SURFACE MOUNTED RACEWAY, SEE ELECTRICALREINSTALL SALVAGED SHELVING47154' - 0"1' - 6"1' - 0"1' - 0"4' - 8"6' - 8"SURFACE MOUNTED RACEWAY, SEE ELECTRICAL1' - 4"CABLE PASS THRU PLATE ABOVE TABLELEVEL 05+46' - 2"LEVEL 04+34' - 4"DEATOMIZER ROOM472BGENERAL LAB472Hybrid Lab - CSRobotics/Guest572Hybrid Lab - FutureHire37211' - 10"TYP9' - 5"TYP11' - 1"1' - 4"7' - 5 5/8"7 1/4"8' - 4"4 7/8"10' - 9 1/8"F16' - 0"16' - 0"EXIST CONC FRAMING (4TH FLOOR AND BELOW)6"EXIST STRUCTURAL STEEL FRAMING (5TH FLOOR AND ROOF)EXIST PIPE ENCLOSUREEXIST GYP BD SOFFITS TO REMAIN, TYPEXIST PARTITION TO REMAINEXIST CONC FLOOR SLABLASER ROOM472AREINSTALL SALVAGED SHELVINGEXIST GYP CLG, TYP309 South Franklin Street Syracuse NY 13202315 488 5635 | rochester@swbr.comThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©FILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions3/6/2019 9:05:00 AMC:\1-Local Revit Models 2017\18695.00 Cornell Upson Hall Rm 472_dylans.rvt18695.00DMKSInterior ElevationsSDFYSA-410Bid DocumentsCornell UniversityUpson Hall Room 472 LaboratoryRenovation124 Hoy Rd, Ithaca, NY 14850March 5, 2019 1/4" = 1'-0"1ATOMIZER ROOM - WEST ELEVATION 1/4" = 1'-0"2ATOMIZER ROOM - NORTH ELEVATION 1/4" = 1'-0"3ATOMIZER ROOM - EAST ELEVATION 1/4" = 1'-0"4ATOMIZER ROOM - SOUTH ELEVATION 1/4" = 1'-0"5GENERAL LAB - SOUTH ELEVATION 1/4" = 1'-0"6GENERAL LAB - WEST ELEVATION 1/4" = 1'-0"7GENERAL LAB - NORTH ELEVATION 1/4" = 1'-0"8GENERAL LAB - EAST ELEVATION 1/4" = 1'-0"9LASER ROOM - EAST ELEVATION 1/4" = 1'-0"10LASER ROOM - NORTH ELEVATION 1/4" = 1'-0"11LASER ROOM - SOUTH ELEVATION 1/4" = 1'-0"12LASER ROOM - WEST ELEVATION 1/4" = 1'-0"13SECTION 2" TYPSEE SCHEDSEE SCHEDULE2"12" TYPSEE SCHEDSEE SCHEDULE2"2DOUBLE MTL STUD AT JAMBS, TYPICALDOORHM WRAPPED FRAME W/ GYP BD RETURNS AND MTL STUD ANCHORS2"PLANSEE FLRPARTITION TYPE AS SCHED.J1TYP.11/16"MIN.7/16"4"WALL WHERE APPLICABLE5/8" TYP1. MISCELLANEOUS FINISH REQUIREMENTS TO WALLS, FLOORS & CEILINGS IN AREAS AFFECTED BY DEMO HAVE NOT BEEN TOTALLY INCORPORATED INTO THE ROOM FINISH SCHEDULE. REFER TO DEMOLITION, FLOOR & REFLECTED CEILING PLANS FOR EXTENT OF "CUTTING & PATCHING". PATCHING SHALL BE THE REPAIR WORK REQUIRED TO RESTORE SURFACES TO THE ORIGINAL CONDITION AND/OR MATCHING THE ADJACENT SURFACES.2. FLOORING TO RUN BENEATH ANY OPEN SPACES IN ROOMS, INCLUDING ADA CABINETS & APPLIANCES. 3. IN THE ROOM FINISH SCHEDULE - IN ANY ROW OR COLUMN "-" or "ETR" INDICATES THERE ARE NO CHANGES OR NEW FINISHES; EXISTING TO REMAIN.4. PAINT ALL EXPOSED HVAC, PLUMBING & ELECTRICAL CONSTRUCTION TO MATCH ADJACENT OR BACKGROUND SURFACES UNLESS OTHERWISE NOTED, INCLUDING BUT NOT LIMITED TO STEEL GRILLES, DIFFUSERS, REGISTERS, AND LOUVERS. 5. DO NOT PAINT OPERATIONAL COMPONENTS OF SYSTEMS INCLUDING BUT NOT LIMITED TO SPRINKLER HEADS, FIRE, SMOKE, OR HEAT DETECTORS.6. PAINT HOLLOW METAL FRAMES & DOORS UNLESS OTHERWISE INDICATED. FINISH FRAMES & DOORS THE SAME ON BOTH SIDES UNLESS INDICATED AS A SPLIT FINISH.7. ALL GYPSUM BOARD CEILINGS TO BE FLAT FINISH UNLESS OTHERWISE NOTED.GENERAL FINISH NOTESFINISH LEGENDRUBBER BASE (RB)RB-1ALLSTATE RUBBER, COVE RUBBER BASE, 4" HIGH, COLOR: #D49 PAINT (PT)PT-1BENJAMIN MOORE - LOW VOC, COLOR: SNOW WHITE(WHITE), SHEEN: EGGSHELL(WALLS), FLAT(CEILINGS AND SOFFITS)PT-2BENJAMIN MOORE - LOW VOC, COLOR: WINTER SOLSTICE 1605(MED GRAY), SHEEN: SEMI-GLOSSEPOXY COUNTERTOP (EC)EC-1DURCON, EPOXY RESIN WORKS, COLOR: GRAYMETAL CASEWORKMOTT MANUFACTURING, SCIENCE LABORATORY FURNITURE, COLOR: TBD FROM MANUFACTURERS STANDARD LINEFGLAZING TYPES:S-11/4" SAFETY GLASSG6"6"SEE DOORSCHEDULESEE DOOR SCHEDULE10"5' - 6"8"SEE DOORSCHEDULESEE DOOR SCHEDULES-1REMARKS: 1. PROVIDE EYE-LEVEL SAFETY DECALS ON FULL HEIGHT GLASS TO MATCH BUILDING STANDARD. 1' - 6"1' - 1"2' - 10"1' - 8"2' - 6"STEEL WALL CABINET,REFER TO ELEVATIONSFASTEN WALL CABINET DIRECT TO EXIST MTL STUD FRAMINGSTEEL BASE CABINET, REFER TO ELEVATIONSEXIST FINISH FLOOR1" EPOXY RESIN W/ BACKSPLASH AND SIDESPLASH WHERE INDICATED2' - 7"SCHEDULED BASE7' - 0"4"LAB CASEWORK TO MATCH EXISTING BY MOTT; WOOD DOOR/DRAWER FACES, STEEL CABINET BODIESSOLID WOOD DOORSFRONT ELEVATIONWORKSURFACEWORKSURFACESEE ELEVATIONSRECEPTACLELIGHT SWITCHRECEPTACLECA, SEE FUME HOOD SCHEDULE FOR LOCATION SAFETY MONITOR/ ALARM(1) 5' - 0" AND (1) 6' - 0"SECTIONREMOVABLE ACCESS PANELAIRFOILLIGHT ENCLOSURE2' - 8" +/- OVERALLWATER, SEE FUME HOOD SCHEDULE FOR LOCATION MAX2' - 0"3" x 6" CUPSINK 5' - 0"2' - 10"5/8"5"5"2 1/4"3 3/4"2 1/2" DIA HOLE, TYP 2 PLACES1' - 4"2 7/16"1 1/2" DIA HOLE, TYP 2 PLACESR0.56 +/- 0.12 AT TOP SURFACE, TYP 4 CORNERS7 3/4"+/- 2'-2"3/8" TYPCOORDINATE DIMENSION TO AVOID FRAME BELOWCUP SINKSPECIFICATIONS:SECTION 12 36 53 LABORATORY WORK SURFACES1. PRODUCT: EPOXY RESIN WORK SURFACEA. BASIS OF DESIGN MANUFACTURER: DURCON, INCORPORATED2. MATERIAL: SOLID EPOXY RESINA. SHEETS CAST FROM MODIFIED EPOXY RESIN AND NON-ASBESTOS INERT FILLER.B. SHEET MONOLITHIC THROUGHOUT WITHOUT SURFACE COATING APPLICATION.3. COLOR: GRAY4. FABRICATION: EPOXY RESIN WORK SURFACEA. THICKNESS: 1"B. EDGE TREATMENT: 1/8" BEVEL WITH DRIP GROOVEC. CORNER TREATMENT: EXPOSED CORNERS SHALL BE EASED SLIGHTLY FOR SAFETY.D. BACK AND END SPLASHES:a. SUPPLIED LOOSE FOR FIELD INSTALLATION.b. SAME MATERIAL AND THICKNESS AS WORK SURFACE.c. 4" HIGH UNLESS OTHERWISE NOTED.d. TOP-MOUNTED END SPLASH WHERE WORK SURFACES ABUT ADJACENT CONSTRUCTION AND AT LOCATIONS INDICATED ON DRAWINGS.E. JOINTS: AS INDICATED ON DRAWINGS, MAXIMUM 1/8" BONDED WITH EPOXY GROUT.F. SINK CUTOUTS: AS INDICATED ON DRAWINGS, ROUTED FOR DROP-IN SINK.G. ALLOWABLE TOLERANCES:a. SQUARE: PLUS OR MINUS 1/64" FOR EACH 12" OF LENGTH.b. LOCATION OF CUTOUTS AND DRILLED OPENINGS: PLUS OR MINUS 1/8" OF DESIGN DIMENSION.c. SIZE OF CUTOUTS AND DRILLED OPENINGS: PLUS 1/8" OR MINUS 0".5. FABRICATION: EPOXY RESIN CUPSINKSA. BASIS OF DESIGN: TS05B. SHAPE: OVALSECTION 09 29 00 GYPSUM BOARD1. PRODUCT: MOISTURE- AND MOLD-RESISTANT GYPSUM BOARDA. MANUFACTURER: USGB. PRODUCT: FIBEROCK AQUA-TOUGHC. CORE: a. 5/8", TYPE XD. LONG EDGES: TAPEREDSECTION 09 22 16 NON-STRUCTURAL METAL FRAMING1. STUDS AND RUNNERS: ASTM C 645A. MIN BASE-METAL THICKNESS: 0.027"a. EQUIVALENT COATINGS AND METAL THICKNESS (DIMPLED STEEL) STUDS WILL NOT BE ALLOWED.B. DEPTH: AS INDICATED ON DRAWINGSC. PROTECTIVE COATING: ASTM A 653/A 653M, G40, HOT-DIP GALVANIZEDSECTION 12 35 51 LABORATORY CASEWORK1. PRODUCT: CABINETSA. MANUFACTURER: MOTT MANUFACTURINGB. PRODUCT: ARCHITECTURAL OVERLAY CABINETS WITH WOOD VENEER FRONTS.C. CABINETSa. CABINET SIDES - 18 GAb. TOP RAILS - 14 GAc. DOOR FRONTS - 18 GAd. RUBBER BUMPERS / SILENCERSe. ADJUSTABLE SHELVES - 20 GAf. PULLS: 4" STAINLESS STEEL WIRE PULLg. HINGES: STAINLESS STEEL OVERLAY HINGESh. WOOD VENEER: AWI PREMIUM BIRCH, ROTARY SLICED, BOOK MATCH, NATURAL(CLEAR) FINISHi. STEEL FINISH: POWDER COATEDD. BASE CABINETa. REMOVABLE BACK - 20GAb. REAR RAIL - 16GAc. DRAWER RUNNER SUPPORT - 14 GA GALVANIZEDd. DRAWER LINER - 20 GAe. ROLLER CATCHESf. 3/8" THREADED LEVELER PLATE - 11 GAg. DRAWER WITH INTEGRAL SIDES & BACK - 18 GA OR 20 GAh. ENCLOSED TOE SPACE - 18 GAE. UPPER CABINETa. BACK - 18 GAb. TOP - 18 GAc. BOTTOM - 18 GAd. SHELF SUPPORT - 18 GAe. FRONT STIFFENER - 18 GAf. FALSE BOTTOM - 20 GAg. SOLID WOOD DOORSSECTION 07 92 00 JOINT SEALANTS1. PRODUCT: SANITARY MILDEW RESISTANT SILICONE SEALANTA. MANUFACTURER: PECORAB. PRODUCT: PECORA 898C. COLOR: TO BE SELECTED FROM MANUFACTURER'S FULL RANGESECTION 08 11 13 HOLLOW METAL DOORS AND FRAMES1. HEAVY DUTY INTERIOR DOORS AND FRAMES PER SDI 250.8, LEVEL 2A. PHYSICAL PERFORMANCE: LEVEL B PER SDI A250.4B. DOORS:a. TYPE: AS INDICATED IN SCHEDULEb. THICKNESS: 1 3/4 INCHc. FACE: UNCOATED STEEL SHEET, MINIMUM 0.042 INCHd. EDGE: MODEL 2, FULL FLUSHe. CORE: MANUFACTURER'S STANDARD; POLYURETHANE OR MINERAL BOARDf. VISION LITE: AS INDICATED IN SCHEDULEC. FRAMES:a. MATERIALS: UNCOATED STEEL SHEET, MINIMUM THICKNESS OF 0.053 INCHb. CONSTRUCTION: KNOCK DOWNc. EXPOSED FINISH: PRIMESECTION 11 53 13 LABORATORY FUME HOODS1. PRODUCT: FUME HOODA. ACCEPTABLE MANUFACTURERS & PRODUCTS (PROVIDE ONE OF THE FOLLOWING,NO SUBSTITUTIONS): a. BASIS-OF-DESIGN: MOTT PRO RESTRICTED BY-PASS - COMBINATION SASH, MOTT 5' SAFEGUARD BENCH LABORATORY HOOD, 32.7" EXTERIOR, MODEL #7371010; MOTT 6' SAFEGUARD BENCH LABORATORY HOOD, 32.7" EXTERIOR, MODEL # 7471010.b. BEDCOLAB: FULLY ACCESSIBLE FUME HOOD, BALANCED AIR, VAV MODEL VBH.c. JAMESTOWN: F-100 SERIES ISOLATOR GEN-5 d. KEWAUNEE: SUPREME AIR H05e. LABCONCO: PROTECTOR PREMIERB. TYPE: FULLY ACCESSIBLE RESTRICTED BY-PASS.C. CONTAINMENT: AVERAGE FACE VELOCITY 100 FPM +/-10% WITH SASHES AT 18-INCHES OPEN WHEN TESTED ACCORDING TO ASHRAE 110 AT A RELEASE RATE OF 4.0 L/MIN.D. MATERIALS:a. FRP SURROUND; ALL STEEL COMPONENTS TO BE POWDER COATED (GLACIER WHITE).b. WORKSURFACE: GRAY EPOXY #9521520 (REFER TO DETAIL).E. SASH: VERTICAL TRAVEL OR COMBINATION (MOTT ONLY); TEMPERED SAFETY GLASS; COUNTER WEIGHTED AND BALANCED; PULLEY SYSTEM; STAINELESS STEEL SASH STOPS; SASH ALARM BY BACS CONTRACTOR.F. ELECTRICAL FIXTURES (PROVIDE ALL WIRING WITHIN HOOD):a. FLUORESCENT LIGHT AND TUBES WITH SWITCHb. DUPLEX, 115 VAC / 60 HZ / 20A / GFCIG. SERVICE FIXTURES (ADA COMPLIANT LEVER HANDLE REMOTE CONTROL VALVES); PROVIDE ALL FIXTURES AND PIPING ON AND WITHIN HOOD:a. COLD WATER (RIGHT SIDE; REFER TO FUME HOOD SCHEDULE)b. COMPRESSED AIR (LEFT OR RIGHT SIDE REFER TO FUME HOOD SCHEDULE) H. SINK: CUP SINK, REFER TO SECTION 12 36 53I. OTHER FEATURES: AERODYNAMIC AIRFOIL BYPASS WITH SPILL TROUGH.J. BASE/STAND: ADJUSTABLE HEIGHT, MANUAL LIFT BASE STAND. SECTION 11 60 00 LABORATORY EQUIPMENT1. PRODUCT: ACID STORAGE CABINETA. MANUFACTURER: DURCONB. PRODUCT: MODEL #DCM 12-91 OR APPROVED EQUAL2. PRODUCT: SOLVENT STORAGE CABINETA. MANUFACTURER: DURCONB. PRODUCT: MODEL #DBT 12-90 OR APPROVED EQUAL3. PRODUCT: SAFETY GLASSES HOLDER, A. MANUFACTURER: BRADY WORLDWIDEPRODUCT: MODEL #43395 OR APPROVED EQUALSECTION 08 80 00 GLAZING1. GLASS PRODUCTSA. FULLY TEMPERED FLOAT GLASS: ASTM C 1048, KIND FT (FULLY TEMPERED), CONDITION A (UNCOATED) UNLESS OTHERWISE INDICATED, TYPE I, CLASS I (CLEAR), QUALITY Q3.2. GLASS SCHEDULE:A. MONOLITHIC-GLASS (TYPE S-1)a. CLEAR FULLY TEMPERED FLOAT GLASSb. THICKNESS: 6.0 MMc. PROVIDE SAFETY LABELING, 16CFR1201, CATEGORYII.SECTION 28 10 00 LASER SAFETY SYSTEM1. BASIS OF DESIGN MANUFACTURER: LASER SAFETY SYSTEMS2. COMPONENTS:A. DEFEATABLE ACCESS CONTROL KITB. EMERGENCY CRASH MODULEC. LASER WARNING MODULED. INTERLOCK CONTROL MODULEE. LASER/SHUTTER INTERFACE MODULE3. PROVIDE ALL HARDWARE REQUIRED FOR FULLY FUNCTIONAL SYSTEM INCLUDING: CABLING, DOOR CLOSURE SENSOR, SWITCHES, MAGNETIC DOOR LOCK AND MOUNTING HARDWARE.4. SUBMITTALS: PROVIDE PRODUCT DATA, COORDINATION SUBMITTALS, O&M MANUAL AND WARRANTY INFORMATION. 309 South Franklin Street Syracuse NY 13202315 488 5635 | rochester@swbr.comThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©FILE PATH:SWBR Project NumberChecked By:Project Manager:Drawn By:Revisions3/6/2019 9:22:52 AMC:\1-Local Revit Models 2017\18695.00 Cornell Upson Hall Rm 472_dylans.rvt18695.00DMKSDetails, Schedules andSpecificationsSDFYSA-501Bid DocumentsCornell UniversityUpson Hall Room 472 LaboratoryRenovation124 Hoy Rd, Ithaca, NY 14850March 5, 2019FRAME ELEVATIONSDOOR JAMB TYPESDOOR SCHEDULEDOOR #DOORFRAMEHARDWARELABELTHRESHOLDREMARKSDOOR #LEAFSSIZETYPEMATERIALFINISHGLASSELEVATIONTYPEMATERIALFINISHWIDTHHEIGHTTHICKLEVEL 04472A13' - 0"7' - 0"1 3/4"FHMPT-2-1J1HMPT-2--472A472B24' - 6"7' - 0"1 3/4"GHMPT-2S-12J1HMPT-2--1472BROOM FINISH SCHEDULEROOMNUMBERROOM NAMEFLOORBASEWALLCEILINGFINISHREMARKSROOMNUMBERMATERIAL/FINISHMATERIAL/FINISHNORTHSOUTHEASTWESTMATERIALFINISHMATERIALFINISHMATERIALFINISHMATERIALFINISHLEVEL 04472GENERAL LABETRRB-1ETRPT-1GYPPT-1ETRPT-1ETRPT-1PT-1472472ALASER ROOMETRRB-1GYPPT-1GYPPT-1GYPPT-1GYPPT-1PT-1472A472BATOMIZER ROOMETRRB-1GYPPT-1ETRPT-1GYPPT-1ETRPT-1PT-1472BDOOR ELEVATIONS 3/4" = 1'-0"3SECTION @ METAL LAB CASE WORK, TYP 3/4" = 1'-0"1FUME HOOD DETAILS 3/4" = 1'-0"2FUME HOOD PLAN DETAILLABORATORY FUME HOOD SCHEDULEKeynoteNumberPurposeExhaustTypeDepthWidthSashConfigurationLinerMaterialCupsinkService 1Service 2Service 3Service 4Additional RequirementsFH-1ADAVAV37.7"5' - 0"REFER TO SPECFRPRIGHTCA (RIGHT)DUPLEX RECEPTACLE (EACH SIDE)--CONTRACTOR TO PROVIDE AIR FLOW MONITOR AND ALARM FOR SASHFH-2ADAVAV37.7"6' - 0"REFER TO SPECFRP-CA (LEFT)DUPLEX RECEPTACLE (EACH SIDE)--CONTRACTOR TO PROVIDE AIR FLOW MONITOR AND ALARM FOR SASHINDICATES KEYNOTE#DOOR HARDWARE SCHEDULE Ƨ 1 2 Ƨ D SD ACM Ƨ D RTS RTS SD ACM (ETR) 5 3 4 5 5 5 375 SF GENERAL LAB 472 359 SF ATOMIZER ROOM 472B 121 SF LASER ROOM 472A SD ACM Ƨ D RTS (ETR) ACM 1 2 4 5 5 3 These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:44 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 BRW PARTIAL FIRE ALARM FOURTH FLOOR PLANS AT DU FA-110 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 1/4" = 1'-0" 1 ROOM 472 DEMOLITION PLAN - FIRE ALARM 1/4" = 1'-0" 2 ROOM 472 NEW WORK PLAN - FIRE ALARM #DEMOLITION KEY NOTES 1. CAREFULLY DISCONNECT AND REMOVE EXISTING FIRE ALARM DEVICE NOTIFICATION DEVICE AND SAVE FOR RELOCATION. 2. DISCONNECT AND REMOVE EXISTING FIRE ALARM DEVICE AND TURN OVER TO OWNER. 3. DISCONNECT AND REMOVE EXISTING SMOKE DAMPER BRANCH CIRCUITING AND ASSOCIATED ADDRESSABLE FIRE ALARM CONTROL MODULE AND DUCT SMOKE DETECTOR TO ACCOMMODATE NEW DUCTWORK. SAVE AND PROTECT DUCT SMOKE DETECTOR AND CONTROL MODULE FOR REUSE. 4. CAREFULLY DISCONNECT AND REMOVE DUCT SMOKE DETECTOR TO ACCOMMODATE DUCTWORK MODIFICATIONS. SAVE AND PROTECT DUCT SMOKE DETECTOR FOR REUSE. 5. DISCONNECT AND REMOVE DUCT SMOKE DETECTOR, ASSOCIATED REMOTE TEST STATION AND SMOKE DAMPER CONTROL MODULE TO ACCOMMODATE SMOKE DAMPER REMOVAL. DISCONNECT AND REMOVE POWER AND FIRE ALARM BRANCH CIRCUITING BACK TO NEAREST NON-AFFECTED DEVICE. NEW WORK KEY NOTES 1. PROVIDE ADDRESSABLE FIRE ALARM CONTROL MODULE TO DENERGIZE MAGNETIC LOCK ON LASER ROOM DOOR IN THE EVENT OF A FIRE ALARM. 2. RE-INSTALL EXISTING ADDRESSABLE FIRE ALARM CONTROL MODULE AND EXTEND EXISTING BRANCH CIRCUITING TO NEW SMOKE DAMPER. RECONNECT EXISTING FIRE ALARM BRANCH CIRCUITING TO CONTROL MODULE. 3. RE-INSTALL EXISTING DUCT SMOKE DETECTOR AND RECONNECT TO EXISTING FIRE ALARM BRANCH CIRCUITING. PROVIDE NEW SAMPLING TUBE TO ACCOMMODATE NEW DUCTWORK DEPTH. 4. RELOCATE EXISTING FIRE ALARM NOTIFICATION DEVICE TO LOCATION SHOWN. EXTEND AND RECONNECT EXISTING FIRE ALARM BRANCH CIRCUITING TO NEW DEVICE LOCATION. 5. PROVIDE NEW FIRE ALARM NOTIFICATION DEVICE AT LOCATION SHOWN. # ABOVEABV ABOVE FINISHED FLOORAFF ACCESS DOORAD ACID RESISTANT WASTEARW ACID VENTAV ALARM ALM AQUASTAT AQST ARCHITECT(URAL)ARCH ARCHITECT/ENGINEER A/E AREA DRAIN ADRN AUTOMATIC AUTO AUTOMATIC AIR VENT AAV BACK WATER VALVE BWV BACKFLOW PREVENTER BFP BALANCING VALVE BAL V BALL VALVE BV BATHTUB BT BELOW BLW BELOW FINISHED FLOOR BFF BRAKE HORSEPOWER BHP BRITISH THERMAL UNIT BTU BRITISH THERMAL UNITS (1000) PER HOUR MBH BRITISH THERMAL UNITS PER HOUR BTUH BUILDING BLDG BUTTERFLY VALVE BFV BY OWNER BO CATCH BASIN CB CHECK VALVE CKVA CIRCULATING PUMP CP CLEAN OUT CO COLD WATER CW COMPRESSED AIR CA COMPRESSOR COMP CONDENSATE DRAIN CD CONNECTION CONN CONTRACT LIMIT LINE CLL CONTRACTOR CONTR CONTROL VALVE CV CYCLE CY DECK PLATE CLEAN-OUT DPCO DEIONIZED WATER DIW DETAIL DTL DISTILLED WATER DI DIAMETER DIA DISHWASHER DWSH DOWN DN DRAIN DR DRAWING DWG DRINKING FOUNTAIN DF DRY WELL DRW ELECTRIC(AL)ELEC ELECTRIC WATER COOLER EWC ELECTRIC WATER HEATER EWH EMERGENCY SHOWER EMSHR EMERGENCY EYEWASH EMEW ENGINEER ENGR ENTERING WATER TEMPERATURE EWT EQUIPMENT EQPM EXISTING (E) EXPANSION TANK ET EXTERIOR EXT FACTORY MUTUAL FM FEET (FOOT)FT FIRE PROTECTION FP FLOOR CLEANOUT FCO FLOOR DRAIN FD FLOOR SINK FS FLOW SWITCH FS FULL LOAD AMPS FLA GAGE (GAUGE) GA GALLON GAL GALLONS PER DAY GPD GALLONS PER HOUR GPH GALLONS PER MINUTE GPM GAS G GATE VALVE GV GREASE TRAP GT GREASE INTERCEPTOR GI GENERAL CONTRACTOR GC HAND SINK HSNK HERTZ HZ HIGH PRESSURE GAS HPG HOSE BIBB HB HORSEPOWER HP HOT WATER HW INCH(ES)IN INCHES WATER COLUMN IN WC INDIRECT WASTE IW INSIDE DIAMETER ID INSULATION INSUL INVERT INV IRON PIPE SIZE IPS KILOWATT KW KILOWATT HOUR KWH LAVATORY LAV LEAVING WATER TEMPERATURE LWT LIQUEFIED PETROLEUM GAS LPG LOCKED ROTOR AMPS LRA MANHOLE MH MANUFACTURER MFR MATCHLINE ML MECHANICAL MECH METER M MIXING VALVE MV MINIMUM CIRCUIT AMPACITY MCA MOP SINK MSNK MOTOR CONTROL CENTER MCC NATURAL GAS NG NITROGEN N NON-FREEZE HOSE BIBB NFHB NORMALLY CLOSED NC NORMALLY OPEN NO NOT TO SCALE NTS OUTSIDE DIAMETER OD OVERFLOW ROOF DRAIN ORD OXYGEN OXY PHASE PH PLUMBING PLBG PNEUMATIC PNEU POUNDS PER SQUARE INCH PSI POUNDS PER SQUARE INCH ABSOLUTE PSIA POUNDS PER SQUARE INCH GAGE PSIG PRESSURE DROP PD PRESSURE REDUCING VALVE PRV PRESSURE TEMPERATURE RELIEF VALVE PTRV PROJECT PROJ PUMP P PUMP DISCHARGE LINE PD RAIN WATER LEADER RWL REDUCED PRESSURE ZONE RPZ REQUIRED REQD REVOLUTIONS PER MINUTE RPM RISER R ROOF DRAIN RD RUNNING LOAD AMPS RLA SANITARY SAN SANITARY SEWER SS SCHEDULE SCHED SECTION SECT SERVICE SINK SS SHOWER SHR SINK SNK SLEEVE SLV SPECIFICATIONS SPEC SQUARE FOOT SQ FT SQUARE INCH SQ IN STAINLESS STEEL SS STAND PIPE SP STORAGE TANK ST STORM DRAIN ST TEMPERATURE TEMP THERMOSTATIC MIXING VALVE TMV TRAP T TRAP PRIMER TP TRENCH DRAIN TD TYPICAL TYP UNLESS OTHERWISE NOTED UON UTILITY UTIL URINAL URN VACUUM VAC VACUUM BREAKER VB VALVE V VARIABLE FREQUENCY DRIVE VFD VEMT (SANITARY)V VENT TROUGH ROOF VTR VERIFY IN FIELD VIF VOLT V WALL HYDRANT WH WALL CLEAN-OUT WCO WATER CLOSET WC WATER HAMMER ARRESTOR WHA WATER HEATER WH WIRE MESH SCREEN WMS FIRE PROTECTION ABBREVIATIONS P D OR OR POINT OF CONNECTION POINT OF DISCONNECTION FIRE PROTECTION SYMBOLS -VALVES AND SPECIALTIES FIRE PROTECTION NOTES A. THE AUTOMATIC SPRINKLER SYSTEMS WITHIN THIS FACILITY SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH NFPA-13. ALL FIRE SUPPRESSION SYSTEMS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE FIRE CODE OF NEW YORK STATE. B. ALL PIPE SIZES AND HYDRAULIC NODES SHOWN ARE FOR REFERENCE ONLY. FIRE PROTECTION CONTRACTOR TO PERFORM HYDRAULIC CALCULATIONS TO DETERMINE FINAL PIPE SIZES. C. THE CONTRACTOR SHALL COORDINATE WITH ALL TRADES AND COMPLY WITH ALL OBSTRUCTION REQUIREMENTS AS DESCRIBED WITHIN NFPA-13. D. THE CONTRACTOR SHALL VISIT THE SITE AND REVIEW EXISTING CONDITIONS AND MAKE ALLOWANCE FOR ANY EXISTING CONDITIONS PRIOR TO SUBMITTING BID. E. ALL COMPONENTS OF AUTOMATIC SPRINKLER SYSTEM SHALL BE LISTED FOR USE IN FIRE SUPPRESSION SYSTEMS AND BE LISTED BY UNDERWRITERS LABORATORIES (UL) AND FM GLOBAL (FM) GENERAL NOTES A. THIS LEGEND IS FOR THE CONTRACTOR'S REFERENCE ONLY. NOT ALL SYMBOLS AND/OR ABBREVIATIONS MAY APPLY TO THIS PARTICULAR PROJECT. ANY ADDITIONS OR OMISSIONS FROM THIS LEGEND SHEET DOES NOT IMPLY INCLUSION AND/OR EXCLUSION OF ANY PARTICULAR ITEMS FROM THE PROJECT. B. THE PLANS ARE DIAGRAMMATIC AND INDICATE ONLY THE SIZE AND GENERAL ARRANGEMENT OF PIPING/DUCTWORK AND EQUIPMENT. EXACT LOCATION OF ALL ELEMENTS SHALL BE DETERMINED AS WORK PROGRESSES, IN COOPERATION AND COORDINATION WITH THE WORK OF ALL TRADES. THEY ARE NOT INTENDED TO SHOW EVERY ITEM OF WORK OR MINOR PIECE OF EQUIPMENT. CONTRACTOR SHALL FURNISH AND INSTALL WITHOUT ADDITIONAL REMUNERATION ANY COMPONENT NECESSARY TO COMPLETE THE SYSTEM IN ACCORDANCE WITH THE BEST PRACTICE OF THE TRADE. C. ITEMS OF WORK OR EQUIPMENT SHOWN ON THE DRAWINGS ONLY, OR CALLED FOR IN THE SPECIFICATIONS ONLY, SHALL BE FURNISHED AND INSTALLED IN THE SAME MANNER AS IF THEY APPEARED ON BOTH THE DRAWINGS AND IN THE SPECIFICATIONS. D. DRAWINGS DO NOT INDICATE ALL OFFSETS, CHANGES IN ELEVATIONS, ETC. WHICH MAY BE REQUIRED. THE CONTRACTOR SHALL MAKE SUCH CHANGES IN PIPING/DUCTWORK AND LOCATION OF EQUIPMENT, ETC. TO ACCOMMODATE WORK, OBSTACLES, AND WORK OF OTHER TRADES/CONTRACTORS. E. INSTALL EQUIPMENT AND PIPING/DUCTWORK TO AVOID INTERFERENCE WITH THE OPERATION, SERVICE, AND MAINTENANCE OF EQUIPMENT. F. ALL COSTS FOR CUTTING, PATCHING AND PAINTING OF EXISTING WALLS, CEILINGS AND FLOORS TO ACCOMMODATE THE INSTALLATION OF WORK SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR UNLESS INDICATED OTHERWISE. MATERIALS FOR THE RESTORATION OF EXISTING SURFACES SHALL MATCH THE EXISTING SURFACES. G. PIPES AND/OR DUCTS PENETRATING FIRE WALLS AND FLOORS SHALL BE FIRESTOPPED USING UL APPROVED MATERIALS. REFER TO THE ARCHITECTURAL DRAWINGS FOR FIRE WALL AND FLOOR LOCATIONS. H. ALL PHYSICAL ATTRIBUTES OF EQUIPMENT AND DEVICES ARE BASED ON THOSE MANUFACTURERS LISTED IN THE SPECIFICATIONS AND/OR THE EQUIPMENT SCHEDULES. THE RESPECTIVE CONTRACTORS ARE RESPONSIBLE FOR ALL CHANGES BROUGHT ABOUT BY THE USE OF ITEMS BY OTHER MANUFACTURERS IF THOSE ITEMS DO NOT MATCH THE PHYSICAL ATTRIBUTES OF THE MANUFACTURERS LISTED. GENERAL DEMOLITION NOTES A. THE DEMOLITION PLANS AND NOTES HAVE BEEN PREPARED TO ASSIST THE CONTRACTORS IN IDENTIFYING THE AREAS AND ITEMS OF DEMOLITION AND RENOVATION ASSOCIATED WITH THIS PROJECT. THE INFORMATION PROVIDED IS NOT MEANT TO BE ALL-INCLUSIVE IN TERMS OF LISTING EACH AND EVERY SPECIFIC TASK TO BE PERFORMED. EACH CONTRACTOR WILL THOROUGHLY EXAMINE ALL CONTRACT DOCUMENTS PRIOR TO PERFORMING ANY WORK. B. DEMOLITION WORK INCLUDES, BUT IS NOT LIMITED TO, THE ITEMS INDICATED ON THE DEMOLITION DRAWINGS AND DESCRIBED IN THE DEMOLITION NOTES. THE EXTENT OF THE DEMOLITION WORK WILL INCLUDE ALL WORK REQUIRED TO COMPLETE THE PROJECT AND ENSURE W HETHER OR NOT THE WORK IS INDICATED ON THE DRAWINGS. C. EACH CONTRACTOR SHALL THOROUGHLY EXAMINE AND VERIFY ALL EXISTING CONDITIONS BEFORE PERFORMING ANY WORK AND IMMEDIATELY NOTIFY THE OWNER, IN WRITING, OF ANY DISCREPANCIES WITH THE DRAWINGS. D. ALL ITEMS NOTED TO BE REMOVED TO BE DISPOSED OF OFF-SITE BY RESPECTIVE CONTRACTORS, UNLESS NOTED OTHERWISE. WHERE INDICATED ON THE DRAWINGS AND/OR IN THE NOTES AS SALVAGE, THE CONTRACTOR SHALL CAREFULLY REMOVE INDICATED ITEMS AND STORE THEM WHERE DIRECTED BY THE OWNER. E. THE OWNER HAS THE OPTION TO RETAIN POSSESSION OF ANY REMOVED MATERIALS OR EQUIPMENT. ALL SUCH ITEMS SHALL BE CAREFULLY REMOVED AND STORED AT THE SITE BY THE CONTRACTOR WHERE DIRECTED BY THE OWNER. ANY MATERIALS OR EQUIPMENT NOT RETAINED BY THE OWNER WILL BECOME THE PROPERTY OF THE CONTRACTOR AND PROMPTLY REMOVED FROM SITE. F. REFER TO ARCHITECTURAL, ELECTRICAL, AND MECHANICAL DRAWINGS FOR DEMOLITION WORK BY RESPECTIVE CONTRACTORS. EACH CONTRACTOR IS RESPONSIBLE FOR ALL DEMOLITION ASSOCIATED WITH HIS CONTRACT AND SCOPE OF WORK. EACH CONTRACTOR IS RESPONSIBLE TO PATCH AND/OR REPAIR ANY AND ALL CONSTRUCTION AFFECTED BY HIS DEMOLITION. THE EXTENT OF PATCH AND REPAIR SHALL BE AS REQUIRED TO RECEIVE THE SCHEDULED NEW WORK. ALL CONTRACTORS ARE RESPONSIBLE FOR COORDINATION OF WORK WITH OTHER CONTRACTORS BEFORE PERFORMING ANY WORK. G. ALL PATCH AND REPAIR WORK SHALL BE PERFORMED USING MATERIALS THAT MATCH THE EXISTING ADJACENT CONSTRUCTION. WHERE PATCHING EXISTING MASONRY WALLS OR INFILLING BETWEEN WALLS WITH MASONRY TO MATCH EXISTING, "TOOTH-IN" NEW MASONRY TO EXISTING. H. EACH CONTRACTOR IS RESPONSIBLE TO PROTECT ALL EXISTING CONSTRUCTION SCHEDULED TO REMAIN. EACH CONTRACTOR IS RESPONSIBLE TO PATCH AND/OR REPAIR ANY AND ALL CONSTRUCTION AFFECTED BY THEIR DEMOLITION. EACH CONTRACTOR SHALL PATCH (SUBSTRATE AND FINISHED SURFACES) ANY EXISTING FINISHES AFFECTED BY THEIR RESPECTIVE WORK. I. EXISTING CONDITIONS INDICATED ARE OBTAINED FROM AVAILABLE SOURCES (EXISTING DRAWINGS, FIELD SURVEYS, ETC.) AND ARE NOT GUARANTEED TO BE TRUE AND EXACT. CONTRACTOR(S) SHALL FIELD VERIFY EXISTING CONDITIONS AND NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH THE AFFECTED PORTION OF THE WORK. J. REMOVAL IN ITS ENTIRETY INCLUDES HANGERS, ELECTRICAL, CONTROLS, ETC., TO LEAVE A LIKE NEW OR MATCHING EXISTING CONDITION. K.THIS CONTRACTOR SHALL INVESTIGATE THE IMPACTS OF DEMOLITION TO THE SOUROUNDING SPACES PRIOR TO DEMOLITION ACTIVITIES. THIS CONTRACTOR IS RESPONSIBLE TO COORDINATE DEMOLITION ACTIVITY AND PROVIDE NOTICE OF DISRUPTIVE ACTIVITIES TO THE OWNER PRIOR TO STARTING ANY DEMOLITION WORK UPRIGHT SPRINKLER HEAD - 3/4" NPT, 8.0 K, ORDINARY TEMPERATURE FLOW SWITCH LISTED INDICATING VALVE WITH TAMPER SWITCH SIDEWALL SPRINKLER HEAD - 1/2" NPT, 5.6 K, ORDINARY TEMPERATURE CHROME PLATED SEMI-RECESSED PENDANT SPRINKLER HEAD, UNLESS NOTED OTHERWISE - 1/2" NPT, 5.6 K, ORDINARY TEMPERATURE CONCEALED PENDANT SPRINKLER HEAD - 1/2" NPT, 5.6 K, ORDINARY TEMPERATURE CHECK VALVE STRAINER MIXING VALVE GAS COCK GLOBE VALVE CAP REDUCER WALL HYDRANT HOSE BIBB ROOF DRAIN FLOOR DRAIN UNION PIPE ANCHOR (PA) PIPE GUIDE (PG) CIRCULATING PUMP PRESSURE GAUGE THERMOMETER METER SHUT-OFF VALVE (GATE, BALL, BUTTERFLY, ETC.) RELIEF VALVE (X INDICATES P -PRESSURE WATER HAMMER ARRESTOR (X INDICATES PDI SIZE) FLEXIBLE CONNECTOR PRESSURE/TEMPERATURE TAP DIRECTION OF FLOW DIRECTION OF DOWNWARD PITCH CLEANOUT (FLOOR/WALL) BACKFLOW PREVENTER (BFP) ELBOW -TURNED UP ELBOW -TURNED DOWN BRANCH CONNECTION -TOP BRANCH CONNECTION -BOTTOM BALANCING VALVE (X INDICATES GPM) SHUT-OFF VALVE IN RISER M P P PT WHA-X WH HB X X T -TEMPERATURE PT -COMBINATION PRESS./TEMP.) PIPING SYMBOLS -VALVES AND SPECIALTIES These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:46 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 AST FIRE PROTECTION SYMBOLS, NOTES & ABBREVIATIONS AT LY FP-001 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 375 SF GENERAL LAB 472 359 SF ATOMIZER ROOM 472B 121 SF LASER ROOM 472A 4"FP 2"FP 1 1/4"FP 1 1/4"FP 1 1/4"FP 1 1/4"FP S2 2"FP UP/DN These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:47 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 AST PARTIAL FIRE PROTECTION FOURTH FLOOR PLANS AT LY FP-110 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 1/4" = 1'-0" 2 ROOM 472 NEW WORK PLAN - FIRE PROTECTION GENERAL NOTES: 1. EXISTING PROJECT AREA IS FULLY SPRINKLERED. IT IS THE INTENT OF THIS PROJECT TO MAINTAIN THIS LEVEL OF PROTECTION 2. HYDRAULICALLY DESIGN TO MAINTAIN NFPA-13 ORDINARY HAZARD GROUP II, 0.20 GPM/SF OVER REMOTE 1,500 SF AREA. 3. COORDINATE HEAD AND PIPING LOCATIONS WITH OTHER TRADES. 4. PIPING SHOWN IS EXISTING. MODIFY AS REQUIRED TO COORDINATE WITH OTHER TRADES. FULL COVERAGE SHALL BE MAINTAINED. PROJECT AREA 1.THE DEMOLITION PLANS AND NOTES HAVE BEEN PREPARED TO ASSIST THE CONTRACTORS IN IDENTIFYING THE AREAS AND ITEMS OF DEMOLITION AND RENOVATION ASSOCIATED WITH THIS PROJECT. THE INFORMATION PROVIDED IS NOT MEANT TO BE ALL-INCLUSIVE IN TERMS OF LISTING EACH AND EVERY SPECIFIC TASK TO BE PERFORMED. EACH CONTRACTOR WILL THOROUGHLY EXAMINE ALL CONTRACT DOCUMENTS PRIOR TO PERFORMING ANY WORK. 2.DEMOLITION WORK INCLUDES, BUT IS NOT LIMITED TO, THE ITEMS INDICATED ON THE DEMOLITION DRAWINGS AND DESCRIBED IN THE DEMOLITION NOTES. THE EXTENT OF THE DEMOLITION WORK WILL INCLUDE ALL WORK REQUIRED TO COMPLETE THE PROJECT AND ENSURE WHETHER OR NOT THE WORK IS INDICATED ON THE DRAWINGS. 3.EACH CONTRACTOR SHALL THOROUGHLY EXAMINE AND VERIFY ALL EXISTING CONDITIONS BEFORE PERFORMING ANY WORK AND IMMEDIATELY NOTIFY THE ARCHITECT, IN WRITING, OF ANY DISCREPANCIES WITH THE DRAWINGS. 4.ANY WORK PERFORMED AS PART OF THIS CONTRACT REQUIRING OR ALTERATION WILL BE THE RESPONSIBILITY OF THE RESPECTIVE CONTRACTOR. 5.ALL ITEMS NOTED TO BE REMOVED TO BE DISPOSED OF OFF-SITE BY RESPECTIVE CONTRACTORS, UNLESS NOTED OTHERWISE. WHERE INDICATED ON THE DRAWINGS AND/OR IN THE NOTES AS SALVAGE AND DELIVER TO OWNER. THE CONTRACTOR WILL CAREFULLY REMOVE INDICATED ITEMS AND STORE THEM WHERE DIRECTED BY THE OWNER. 6.THE OWNER HAS THE OPTION TO RETAIN POSSESSION OF ANY REMOVED MATERIALS OR EQUIPMENT. ALL SUCH ITEMS SHALL BE CAREFULLY REMOVED AND STORED AT THE SITE BY THE CONTRACTOR WHERE DIRECTED BY THE OWNER. ANY MATERIALS OR EQUIPMENT NOT RETAINED BY THE OWNER WILL BECOME THE PROPERTY OF THE CONTRACTOR AND PROMPTLY REMOVED FROM SITE. 7.ANY CONTRACTOR REMOVING OR MODIFYING MATERIAL CONTAINING ASBESTOS OR SUSPECTED OF CONTAINING ASBESTOS WILL NOTIFY THE OWNER AT ONCE AND STOP REMOVAL. IDENTIFICATION AND/OR REMOVAL OF ASBESTOS CONTAINING MATERIAL WILL BE THE RESPONSIBILITY OF THE OWNER. 8.REFER TO ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, TECHNOLOGY AND PLUMBING DRAWINGS FOR DEMOLITION WORK BY RESPECTIVE CONTRACTORS. EACH CONTRACTOR IS RESPONSIBLE FOR ALL DEMOLITION ASSOCIATED WITH HIS CONTRACT AND SCOPE OF WORK. EACH CONTRACTOR IS RESPONSIBLE TO PATCH AND/OR REPAIR ANY AND ALL CONSTRUCTION AFFECTED BY HIS DEMOLITION. THE EXTENT OF PATCH AND REPAIR SHALL BE AS REQUIRED TO RECEIVE THE SCHEDULED NEW WORK. ALL CONTRACTORS ARE RESPONSIBLE FOR COORDINATION OF WORK WITH OTHER CONTRACTORS BEFORE PERFORMING ANY WORK. 9.ALL PATCH AND REPAIR WORK SHALL BE PERFORMED USING MATERIALS THAT MATCH THE EXISTING ADJACENT CONSTRUCTION. WHERE PATCHING EXISTING MASONRY WALLS OR INFILLING BETWEEN WALLS WITH MASONRY TO MATCH EXISTING, "TOOTH-IN" NEW MASONRY TO EXISTING. 10.EACH CONTRACTOR IS RESPONSIBLE TO PROTECT ALL EXISTING CONSTRUCTION SCHEDULED TO REMAIN. EACH CONTRACTOR IS RESPONSIBLE TO PATCH AND/OR REPAIR ANY AND ALL CONSTRUCTION AFFECTED BY THEIR DEMOLITION. EACH CONTRACTOR SHALL PATCH (SUBSTRATE AND FINISHED SURFACES) ANY EXISTING FINISHES AFFECTED BY THEIR RESPECTIVE WORK. 11.EXISTING CONDITIONS INDICATED ARE OBTAINED FROM AVAILABLE SOURCES (EXISTING DRAWINGS, FIELD SURVEYS, ETC.) AND ARE NOT GUARANTEED TO BE TRUE AND EXACT. CONTRACTOR(S) SHALL FIELD VERIFY EXISTING CONDITIONS AND NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH THE AFFECTED PORTION OF THE WORK. 12.REMOVAL IN ITS ENTIRETY INCLUDES HANGERS, ELECTRICAL, CONTROLS, ETC., TO LEAVE A LIKE NEW OR MATCHING EXISTING CONDITION. 13. THIS CONTRACTOR SHALL INVESTIGATE THE IMPACTS OF DEMOLITION TO THE SOUROUNDING SPACES PRIOR TO DEMOLITION ACTIVITIES. THIS CONTRACTOR IS RESPONSIBLE TO COORDINATE DEMOLITION ACTIVITY AND PROVIDE NOTICE OF DISRUPTIVE ACTIVITIES TO THE OWNER PRIOR TO STARTING ANY DEMOLITION WORK. DEMOLITION NOTES 1. CONTRACTORS ARE URGED TO INSPECT THE SITE BEFORE SUBMITTING A BID PROPOSAL TO ENSURE KNOWLEDGE OF PROJECT REQUIREMENTS AND SITE CONDITIONS. IF NO CLARIFICATION IS REQUESTED, IT WILL BE CONSIDERED THAT THE CONTRACTORS ARE IN FULL UNDERSTANDING OF PROJECT REQUIREMENTS. 2. PROVIDE LABOR, SUPERVISION, EQUIPMENT, MATERIALS, AND SERVICES REQUIRED FOR THE COMPLETE INSTALLATION OF THIS WORK IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE, AND LOCAL CODES, AUTHORITIES HAVING JURISDICTION, AND STANDARDS INCLUDING BUT NOT LIMITED TO THE LATEST ADOPTED VERSIONS OF ASHRAE, IBC, IPC, IFGC, NEC, NFPA, AND SMACNA. 3. NOTHING CONTAINED IN THE SPECIFICATIONS OR SHOWN ON THE DRAWINGS SHALL BE CONSTRUED TO BE IN CONFLICT WITH ANY STATE OR LOCAL CODES, ORDINANCES OR REGULATIONS. 4. THE USE OF THE WORD "PROVIDE" SHALL MEAN TO FURNISH, INSTALL AND CONNECT, READY TO USE. 5. THE USE OF THE WORD "FURNISH" SHALL MEAN TO PROCURE AND DELIVER TO THE SITE. 6. THE USE OF THE WORD "INSTALL" SHALL MEAN TO PHYSICALLY PLACE INTO SERVICE AND CONNECT, READY TO USE. 7. EQUIPMENT AND MATERIALS SHALL BE INSTALLED BY SKILLED TRADESMEN, FAMILIAR WITH THE COMPONENTS TO BE INSTALLED, AND IN ACCORDANCE WITH BEST PRACTICES OF THE INDUSTRY. 8. THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE ONLY THE GENERAL ARRANGEMENT OF PIPING, DUCTWORK, CONDUITS, EQUIPMENT, ETC. ITEMS OF WORK OR EQUIPMENT SHOWN ON THE DRAWINGS ONLY, OR CALLED FOR IN THE SPECIFICATIONS ONLY, SHALL BE FURNISHED AND INSTALLED IN THE SAME MANNER AS IF THEY APPEARED ON BOTH DRAWINGS AND THE SPECIFICATIONS. 9. BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, FITTINGS, AND ACCESSORIES THAT MAY BE REQUIRED. THIS CONTRACTOR SHALL CAREFULLY EXAMINE THE ARCHITECTURAL, STRUCTURAL, HEATING, VENTILATING AND AIR-CONDITIONING, ELECTRICAL, PLUMBING, AND OTHER PROJECT DOCUMENTS AS MAY BE NECESSARY FOR PROPER OPERATION OR INSTALLATION AND SHALL PROVIDE OFFSETS, FITTINGS, AND ACCESSORIES TO MEET PROJECT CONDITIONS. 10. DISCREPANCIES BETWEEN DRAWINGS OR BETWEEN DRAWINGS AND SPECIFICATIONS SHALL BE REPORTED TO PROFESSIONAL IN WRITING. OBTAIN WRITTEN INSTRUCTIONS FROM PROFESSIONAL AS TO THE MANNER IN WHICH TO PROCEED. NO DEPARTURES FROM THE PROJECT DOCUMENTS SHALL BE MADE WITHOUT PRIOR WRITTEN ACCEPTANCE BY THE PROFESSIONAL. ALL PHYSICAL ATTRIBUTES OF EQUIPMENT AND DEVICES ARE BASED ON THOSE MANUFACTURERS LISTED IN THE SPECIFICATIONS AND/OR THE EQUIPMENT SCHEDULES. THE RESPECTIVE CONTRACTORS ARE RESPONSIBLE FOR ALL CHANGES BROUGHT ABOUT BY THE USE OF ITEMS BY OTHER MANUFACTURERS IF THOSE ITEMS DO NOT MATCH THE PHYSICAL ATTRIBUTES OF THE MANUFACTURERS LISTED. 11. THE FIRE RESISTANCE RATINGS OF ALL WALLS, PARTITIONS, FLOORS, STEEL, ETC. SHALL BE MAINTAINED. THE APPLICATION OF PRODUCTS AND/OR DEVICES INTENDED TO MAINTAIN THESE RATINGS SHALL BE SUBMITTED FOR REVIEW AND INSTALLED PER MANUFACTURER'S INSTRUCTIONS. 12. IN ORDER TO AVOID DELAY IN THE PROJECT SCHEDULE, AND THE POSSIBLE INSTALLATION OF NON-SPECIFIED MATERIALS, THE CONTRACTOR IS RESPONSIBLE FOR ORDERING ALL PRODUCTS IN A TIMELY FASHION. IF A DELAY OCCURS DUE TO NEGLIGENCE ON PART OF THE CONTRACTOR, ANY FINANCIAL BURDEN ENCOUNTERED WILL BE THE RESPONSIBILITY OF THE CONTRACTOR. 13. DIMENSIONS, CLEARANCES, AND LOCATIONS OF EQUIPMENT AND MATERIALS SHALL BE FIELD VERIFIED PRIOR TO ORDERING, PROCURING AND FURNISHING SAME. 14. NO EXTRA COMPENSATION OR CHARGES WILL BE ACCEPTED DUE TO DIFFERENCES BETWEEN THE ACTUAL MEASUREMENTS AND THOSE INDICATED ON THE PLAN. THOROUGHLY COORDINATE WORK WITH SITE CONDITIONS AND OTHER TRADES, DETERMINE EXACT ROUTE AND LOCATION OF EACH DUCT, PIPE, CONDUIT, ETC. BEFORE FABRICATION AND INSTALLATION. 15. THE CONTRACTOR SHALL PROVIDE AND INSTALL ACCESS PANELS, WHETHER INDICATED ON THE CONTRACT DOCUMENTS OR NOT, WHERE REQUIRED TO PROVIDE ACCESS TO THEIR INSTALLATIONS. ACCESS PANELS SHALL MATCH THE FIRE RESISTANCE RATING OF THE PARTITION THAT THEY ARE BEING INSTALLED. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL ACCESS PANELS WITH THE ARCHITECT AND WITH OTHER TRADES TO AVOID DUPLICATION. 16. INSTALL WORK SUBSTANTIALLY AS INDICATED. VERIFY LOCATIONS AND ELEVATIONS ON JOB SITE. DO NOT DIRECTLY SCALE DRAWINGS. MAKE NECESSARY CHANGES IN ELEVATION, FITTINGS, OR OFFSETS TO ACCOMMODATE OBSTACLES OR INTERFERENCES. 17. CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR DAMAGE TO THE BUILDING, PIPING OR EQUIPMENT THAT IS THE RESULT OF WORK FOR INSTALLATION OF THIS CONTRACT. 18. THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR PATCH AND REPAIR OF ALL SURFACES TO MATCH EXISTING MATERIALS AND ADJACENT FINISHES ASSOCIATED WITH INSTALLATION/REMOVAL OF THIS WORK UNLESS SPECIFICALLY NOTED OTHERWISE. 19. WORK SHALL BE COMPLETED TO MAINTAIN ALL NECESSARY AND REQUIRED CLEARANCES, ACCESSES, AND OPENINGS, SUCH THAT FULL FUNCTIONALITY, PROPER OPERATION, AND REPAIR AND MAINTENANCE ARE ENSURED. 20. WHERE DEVICE HEIGHT OF 48" OCCURS AT POINT OF CHANGE OF FINISH, THE DEVICE SHALL BE LOWERED TO OCCUR IN ONE FINISH OR CONFORM TO ADA STANDARDS. 21. WHERE DEVICE OCCURS IN BRICK, TILE, OR BLOCK WALLS, THEY SHALL BE MOUNTED AT A VERTICAL MASONRY JOINT & IN THE BOTTOM HORIZONTAL JOINT, CLOSEST TO THE MOUNTING HEIGHT. 22. UNLESS OTHERWISE NOTED, ALL MOUNTING HEIGHT DIMENSIONS LISTED ARE TO THE CENTER LINE OF THE BOX OR DEVICE. 23. NOT ALL ABBREVIATIONS & SYMBOLS MAY APPLY TO THIS PROJECT. 24. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE LABELED AND LISTED BY A CERTIFIED TESTING LABORATORY OR AGENCY. 25. DRAWINGS REPRESENT THE SCOPE OF WORK IN GENERAL ARRANGEMENT FORM AND ARE INTENDED TO SHOW GENERAL ROUTING AND REQUIRED SIZES/CAPACITIES OF SYSTEM COMPONENTS. GENERAL NOTES AB ABOVE AD ACCESS DOOR OR AREA DRAIN ADP APPARATUS DEW POINT AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AFUE ANNUAL FUEL UTILIZATION EFFICIENCY AGA AMERICAN GAS ASSOCIATION AHJ AUTHORITY HAVING JURISDICTION AHU AIR HANDLING UNIT AMB AMBIENT AMP AMPERES ANSI AMERICAN NATIONAL STANDARDS INSTITUTE APD AIR PRESSURE DROP ASHRAE AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS AST ABOVE GROUND STORAGE TANK ATC AUTOMATIC TEMPERATURE CONTROL ATCC AUTOMATIC TEMPERATURE CONTROLS CONTRACTOR AVG AVERAGE AWG AMERICAN WIRE GAGE AWT AVERAGE WATER TEMPERATURE AWWA AMERICAN WATER WORKS ASSOCIATION BAS BUILDING AUTOMATION SYSTEM BF BLIND FLANGE BFF BELOW FINISH FLOOR BS BIRDSCREEN BDD BACKDRAFT DAMPER BT BATHTUB BTU BRITISH THERMAL UNIT BTUH BRITISH THERMAL UNITS PER HOUR BHP BRAKE HORSEPOWER CA COMMISSIONING AGENT OR AUTHORITY CCO CEILING CLEANOUT CFM CUBIC FEET PER MINUTE CI CAST IRON CLG CEILING CO CLEANOUT CONN CONNECTION CONT CONTINUATION COP COEFFICIENT OF PERFORMANCE CPVC CHLOROL POLYVINYL CHLORIDE CU CONDENSING UNIT CU FT CUBIC FEET CU IN CUBIC INCH CW DOMESTIC COLD WATER CW(F) DOMESTIC COLD WATER (FILTERED) °C DEGREES CELSIUS °F DEGREES FAHRENHEIT ø DIAMETER D DRYER, APPLIANCE DB DRY BULB DBP DOMESTIC BOOSTER PUMP DEMO DEMOLITION DF DRINKING FOUNTAIN DHRP DOMESTIC HOT WATER RETURN PUMP DIR DIRECT DN DOWN DCW DOMESTIC COLD WATER DCWS DOMESTIC COLD WATER SYSTEM DHW DOMESTIC HOT WATER DHWS DOMESTIC HOT WATER SYSTEM DHC DOMESTIC HOT WATER RECIRCULATION DHCS DOMESTIC HOT WATER RECIRCULATION SYSTEM DP DOMESTIC PUMP DR DRAIN DWG DRAWING DWH DOMESTIC WATER HEATER DX DIRECT EXPANSION (E)EXISTING E/A EXHAUST AIR EAT ENTERING AIR TEMPERATURE EC ELECTRICAL CONTRACTOR EER ENERGY EFFICIENCY RATIO EFF EFFICIENCY ELEV ELEVATION ELEV ELEVATOR EQUIP EQUIPMENT ESP EXTERNAL STATIC PRESSURE ETR EXISTING TO REMAIN EWC ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER EWT ENTERING WATER TEMPERATURE EXT. F&B EXTERNAL FACE & BYPASS EXP EXPANSION FA FREE AREA FAS FIRE ALARM SYSTEM FC FLEXIBLE CONNECTION FCO FLOOR CLEANOUT FD FLOOR DRAIN OR FIRE DAMPER FLA FULL LOAD AMPERES FLR FLOOR FMS FACILITY MANAGEMENT SYSTEM FOS FUEL OIL SUPPLY FOR FUEL OIL RETURN FPC FIRE PROTECTION CONTRACTOR FPI FINS PER INCH FPM FEET PER MINUTE FPS FEET PER SECOND FPS FIRE PROTECTION SYSTEM FS FLOOR SINK FT FEET OR FOOT FT LB FOOT POUND GA GAUGE GAL GALLONS GALV GALVANIZED GC GENERAL CONTRACTOR GCO GRADE CLEANOUT GI GREASE INTERCEPTOR GPH GALLONS PER HOUR GPM GALLONS PER MINUTE GWH GAS WATER HEATER H HUMIDITY HB HOSE BIBB HC HEATING CONTRACTOR HD HEAD HGT HEIGHT HP HORSEPOWER HR HOUR(S) PLUMBING ABBREVIATIONS HUM HUMIDIFIER HW DOMESTIC HOT WATER HZ HERTZ IBC INTERNATIONAL BUILDING CODE ID INSIDE DIAMETER IFGC INTERNATIONAL FUEL GAS CODE IN INCHES IN WC INCHES WATER COLUMN INV INVERT IN WG INCHES WATER GAGE IPC INTERNATIONAL PLUMBING CODE IW INDIRECT WASTE JC JANITORS CLOSET JS JANITORS SINK KW KILOWATT KWH KILOWATT HOUR LxWxD LENGTH x WIDTH x DEPTH LAT LEAVING AIR TEMPERATURE L LAVATORY LAV LAVATORY LBS POUNDS LF LINEAR FEET LD LINEAR DIFFUSER LPG LIQUID PROPANE GAS LRA LOCKED ROTOR AMPERES LWT LEAVING WATER TEMPERATURE M/A MIXED AIR MAX MAXIMUM MBH 1,000 BTUH MMBH 1,000,000 BTUH MC MECHANICAL CONTRACTOR MFR MANUFACTURER MIN MINIMUM MR MOP RECEPTOR MS MOP SINK MTD MOUNTED N/A NOT APPLICABLE NC NORMALLY CLOSED NEC NATIONAL ELECTRIC CODE NFPA NATIONAL FIRE PROTECTION ASSOCIATION NIC NOT IN CONTRACT NG NATURAL GAS NO NORMALLY OPEN NP NON-POTABLE NTS NOT TO SCALE O/A OUTSIDE AIR OD OUTSIDE DIAMETER OD OVERFLOW DRAIN OED OPEN END DUCT OZ OUNCE P PUMP PC PLUMBING CONTRACTOR PD PRESSURE DROP PH PHASE PPM PARTS PER MILLION PRV PRESSURE REDUCING VALVE PSI POUNDS PER SQUARE INCH PSIG POUNDS PER SQUARE INCH GAUGE PT PRESSURE/TEMPERATURE TEST PORT PVC POLYVINYLCHLORIDE R/A RETURN AIR RD ROOF DRAIN REQ'D REQUIRED RH RELATIVE HUMIDITY RLA RUNNING LOAD AMPS RPM REVOLUTIONS PER MINUTE RX REMOVE EXISTING S SINK SATC SUSPENDED ACOUSTICAL TILE CEILING SF SQUARE FEET S/FD SMOKE/FIRE DAMPER SH SHOWER SI SOLIDS INTERCEPTOR SK SINK SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION SSK SERVICE SINK SST STAINLESS STEEL SP STATIC PRESSURE T TEMPERATURE TBR TO BE REMOVED TCC TEMPERATURE CONTROL CONTRACTOR TD TRENCH DRAIN THA TOTAL HEAT ADDED TP TEST PORT TSP TOTAL STATIC PRESSURE TSTAT THERMOSTAT TT TEMPERATURE TRANSMITTER TYP TYPICAL TW TEMPERED WATER (85 DEG. F) UNO UNLESS NOTED OTHERWISE UST UNDERGROUND STORAGE TANK UR URINAL V VENT VAC VACUUM VAV VARIABLE AIR VOLUME VBF VENT BELOW FLOOR VRV VARIABLE REFRIGERANT VOLUME VTR VENT THROUGH ROOF W WASHER, APPLIANCE OR WASTE WB WET BULB WC WATER CLOSET WCO WALL CLEANOUT WH WALL HYDRANT WHA WATER HAMMER ARRESTOR WPD WATER PRESSURE DROP YCO YARD CLEANOUT YD YARD DRAIN YH YARD HYDRANT PLUMBING SYMBOL LEGEND CONNECT TO EXISTING 1 A101 REFERENCE DRAWING 1 A101 DETAIL NUMBER DIRECTION INDICATOR DISCONNECT EXISTING FLOW ARROW DETAIL DESIGNATION SECTION DESIGNATION REFERENCE DRAWING DETAIL NUMBER GATE VALVE PLAN VIEW PRESSURE REGULATING VALVE BUTTERFLY VALVE BALL VALVE CHECK VALVE BACKFLOW PREVENTER GLOBE VALVE PLUG VALVE BALANCING VALVE PRESSURE RELIEF VALVE STRAINER DOUBLE LINE SANITARY VENTV 2-WAY VALVE 3-WAY VALVE MIXING VALVE FLOW SWITCH PRESSURE SWITCH WATER HAMMER ARRESTOR THERMOMETER PRESSURE GAUGE AUTOMATIC AIR VENT UNION PIPE CAP SOLENOID VALVE TRIPLE DUTY VALVE CIRCULATING PUMP ROOF DRAIN FLOOR DRAIN FLOOR SINK FLOOR CLEANOUT PIPE BREAK TEMPERED WATER NON-POTABLE WATER DOMESTIC HOT WATER RECIRCULATION DOMESTIC HOT WATER DOMESTIC COLD WATERDCWS EXISTING (LIGHT SOLID LINE)EX DEMO (DASHED HEAVY LINE)DEMO NATURAL GAS LIQUID PROPANE GAS STORM DRAIN OVERFLOW STORM DRAINSD DHWS DHWR NPW TW SAN OSD G LPG VENTURI FLOW METER PLAN VIEW PIPE ANCHOR PIPE GUIDE DOUBLE LINE FLANGED CONNECTION NON-FREEZE WALL HYDRANT HOSE BIBB EXPANSION LOOP COMPRESSED AIRCA METER FLEXIBLE PIPE CONNECTION PIPE DROP WALL CLEANOUT PIPE UP CONCENTRIC INCREASER/REDUCER ECCENTRIC INCREASER/REDUCER P D ACID WASTEAW ACID VENTAV These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:58 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 CWC PLUMBING SYMBOLS, NOTES & ABBREVIATIONS AT CSH P-001 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 375 SF GENERAL LAB 472 359 SF ATOMIZER ROOM 472B 121 SF LASER ROOM 472A A A 1"CW 1"HW 3/4"HWC 1-1/2"V 1"CW 1"HW 3/4"HWC 1"CW 1"HW 3/4"HWC 3/4"CAFUME HOOD @ ADA HEIGHT, 30" AFF. FUME HOOD @ NON-ADA HEIGHT, 36" AFF. FLEXIBLE EXHAUST DUCT (TYP.) DETAIL NOTES: 1. PROVIDE 2" DRUM TRAP. PROVIDE SUFFICIENT PIPE ON INLET TO ALLOW 6" OF WORK SURFACE ADJUSTMENT. 2. PROVIDE 1-1/2" DRAIN FROM CUP SINK. PROVIDE SUFFICIENT TAILPIECE ON OUTLET TO ALLOW FOR 6" OF WORK SURFACE ADJUSTMENT. DRAIN IS TO BE SLEEVED WITHIN THE 2" INLET PIPE PROVIDED ON THE DRUM TRAP. 3. 2" DRAIN, ROUTE BEHIND UNIT IN CHASE SPACE AND CONNECT TO SINK DRAIN. 4. PROVIDE 1-1/2" ACID VENT SERVING CUP SINK DRAIN. CONNECT TO NEAREST VENT. SERVICE AS INDICATED ON PLANS. COORDINATE WITH VENT FROM ADJACENT LABORATORY FIXTURES. 5. DOMESTIC COLD WATER CONNECTION. PROVIDE BRASS/STAINLESS STEEL FLEXIBLE CONNECTION TO PRE-PIPED LABORATORY DOMESTIC WATER SERVICE AT FUME HOOD. 6. PROVIDE PVC WRAPPED INSULATION ON ALL PIPING ROUTED UNDER FUME. 1 1 2 2 3 34 4 5 5 55 DUCT COLLAR (TYP.) These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/6/2019 12:36:35 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 CWC PARTIAL PLUMBING FOURTH FLOOR PLANS AT CSH P-110 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 1/4" = 1'-0" 1 ROOM 472 NEW WORK PLAN - PLUMBING NEW WORK KEY NOTES 1. PROVIDE 1/2" CA TO FUME HOOD. 2. PROVIDE 1/2" CW(F) TO FUME HOOD CUP SINK. 3. PROVIDE 1/2" CW(F) TO POLISHER 4. CONNECT 3/4" CW TO EXISTING PIPING UNDER SINK. PROVIDE WATER FILTER WF-1 AND CONNECT TO NEW EQUIPMENT. 5. PROVIDE 3/4" CW AND 3/4" HW TO NEW MIXING VALVE MV-1 FROM EXISTING TAPS. 6. PROVIDE 1" TW TO EMERGENCY SHOWER ES-1. PROPERLY SUPPORT PIPING AND FIXTURE AND COORDINATE INSTALLATION OF PULL HANDLE TO ENSURE OPERATION. 7. PROVIDE 1 1/2" DRAIN FROM POLISHER. CONNECT TO NEW 2" DRAIN FROM FUMEHOOD. PROVIDE CHEMICAL RESISTANT T- STRAINER IN AN ACCESSIABLE LOCATION. MCMASTER-CARR #8680T18 BASIS OF DESIGN. 8. PROVIDE 1/2" ARGON PIPING FROM REGULATOR ASSEMBLY TO TOOL CONNECTION. COORDINATE PIPE ROUTE WITH FINAL EQUIPMENT LOCATION. 9. PROVIDE 1/2" CA FROM EXISTING SERVICE TO SUPPLY CONNECTIONS AT FUME HOODS. ROUTE PIPING THROUGH EXISTING CABINETS. 10. PROVIDE 2" DRAIN FROM FUME HOOD TO EXISTING DRAIN RISER LOCATED IN WALL. #LEGEND: CA -COMPRESSED AIR CW -DOMESTIC COLD WATER HW -DOMESTIC HOT WATER CW(F) -DOMESTIC COLD WATER (FILTERED) TW -TEMPERED WATER (85 DEG. F) PLUMBING FIXTURE SCHEDULE FIXTURE DESCRIPTION ACCESSORIES ES-1 DRENCH SHOWER BASIS OF DESIGN BRADLEY S19-120A MV-1 EMERGENCY MIXING VALVE. BASIS OF DESIGN BRADLEY EFX-20 1. ANSI Z358.1 2. LIQUID FILLED THERMOMETER 3. FACTORY SET TO 85 DEG. F 1. HORIZONTAL SUPPLY 2. PLASTIC SHOWER HEAD W/SS SHROUD 3. ANSI Z358.1 1 1 2 4 7 6 5 MV-1 P PES-1 3 8 8 8 P 9 P WF-1 CULLIGAN US-3 ULTRA FILTRATION UNDERSINK WATER SYSTEM 1. BUILT-IN BRACKET, 2. US-3-R FILTER CARTRIDGE 12" = 1'-0" 2 ADA FUME HOOD INSTALLATION DETAIL 8 10 1. ANY PHYSICAL INSTALLATION MODIFICATIONS DUE TO FIELD CONDITIONS SHALL BE RESOLVED BY THE MECHANICAL CONTRACTOR IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE MECHANICAL ENGINEER. 2. THIS CONTRACTOR SHALL PROVIDE ALL MISCELLANEOUS STEEL AND SUPPORTS TO SUSPEND DUCTWORK AND EQUIPMENT. 3. ALL EQUIPMENT SHALL BE INSTALLED WITH VIBRATION ISOLATORS. 4. THIS CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT TO ENSURE A COMPLETE SYSTEM. 5. THIS CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER TRADES. 6. THE MECHANICAL CONTRACTOR SHALL SEAL ALL HIS RESPECTIVE WALL AND ROOF PENETRATIONS. 7. THE MECHANICAL CONTRACTOR SHALL PAY FOR ALL FEES AND PERMITS AS NECESSARY TO COMPLETE THE INSTALLATION. 8. THE MECHANICAL CONTRACTOR SHALL PROVIDE MANUAL AIR VENTS AT ALL HIGH POINTS IN HYDRONIC SYSTEMS AND AT EACH UNIT TO FACILITATE MANUAL VENTING. PROVIDE 3/4" HOSE END DRAINS, (WITH CAP & CHAIN), AT ALL LOW POINTS TO FACILITATE DRAINAGE. 9. ALL REFRIGERATION PIPING SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS, ALL PIPE SIZES SHALL BE PER MANUFACTURER'S REQUIREMENTS BASED ON PROPOSED PIPE ROUTING AND EQUIPMENT LOCATIONS. 10. ALL REFRIGERANT PIPING SHALL BE PITCHED A MINIMUM OF 1/2" IN 10'-0" IN THE DIRECTION OF THE REFRIGERANT FLOW. 11. ALL PIPE PENETRATIONS THROUGH CHASES, WALLS, OR FLOORS WHICH ARE FIRE- RATED SHALL BE PROPERLY SEALED TO MAINTAIN RATING. 12. ALL DUCTS THAT PENETRATE CHASES, WALLS, OR FLOORS WHICH ARE FIRE-RATED SHALL BE INSTALLED WITH FIRE DAMPERS IN ACCORDANCE WITH NFPA 90A. THIS APPLIES EVEN IF THEY ARE NOT SPECIFICALLY SHOWN ON THE DRAWINGS. 13. COORDINATION DRAWINGS AT NOT LESS THAN A 1/4" PER FOOT. SHOWING THE PROPOSED EQUIPMENT ARE REQUIRED FOR ALL AREAS AND SHALL BE REVIEWED BY ALL TRADES PRIOR TO SUBMISSION TO THE PROFESSIONAL. 14. ALL DUCTWORK, EQUIPMENT, PIPING, ETC. SHALL BE INSTALLED ABOVE THE FINISHED CEILING UNLESS SPECIFICALLY NOTED OTHERWISE. MECHANICAL NOTES 1. ALL DUCTWORK SIZES NOTED ARE FREE AREA SIZES. 2. TURNING VANES SHALL BE PROVIDED IN ALL RECTANGULAR DUCT ELBOWS. 3. BALANCING DAMPERS SHALL BE PROVIDED AT ALL DUCT BRANCHES. 4. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING INSTALLATION OF AIR DEVICES WITHIN THE CEILING GRID WITH LIGHTING FIXTURES, SPRINKLER HEADS, ETC. 5. LENGTH OF FLEXIBLE DUCT BRANCHES SHALL NOT EXCEED 7'-0" MAXIMUM. ADDITIONAL LENGTH FOR INDIVIDUAL CONNECTIONS SHALL BE RIGID ROUND SHEET METAL DUCTWORK. 6. FLEXIBLE DUCT SHALL NOT BE ACCEPTABLE FOR EXHAUST FAN INSTALLATIONS. 7. DUCTWORK SIZES ARE DEFINITE AND LOCATIONS ARE APPROXIMATE. MECHANICAL CONTRACTOR CAN MAKE MINOR DUCTWORK SIZE REVISIONS TO ACCOMMODATE AVAILABLE SPACE. SIZING SHALL BE BASED ON A MAXIMUM OF .08" PRESSURE LOSS PER 100' (STATIC PRESSURE), AND A MAXIMUM 1100 FPM AIR VELOCITY. DUCTWORK SYSTEMS SHALL BE SIZED BASED ON HVAC FAN STATIC PRESSURE AND FAN DUTY POINTS. DUCTWORK NOTES OUTDOOR AMBIENT CONDITIONS: WINTER = -5°F DB SUMMER = 88° DB, 73°F WB INDOOR CONDITIONS: HEATING = 70°F COOLING = 75°F CODES: 2015 INTERNATIONAL MECHANICAL CODE DESIGN PARAMETERS 1. CONTRACTORS ARE URGED TO INSPECT THE SITE BEFORE SUBMITTING A BID PROPOSAL TO ENSURE KNOWLEDGE OF PROJECT REQUIREMENTS AND SITE CONDITIONS. IF NO CLARIFICATION IS REQUESTED, IT WILL BE CONSIDERED THAT THE CONTRACTORS ARE IN FULL UNDERSTANDING OF PROJECT REQUIREMENTS. 2. PROVIDE LABOR, SUPERVISION, EQUIPMENT, MATERIALS, AND SERVICES REQUIRED FOR THE COMPLETE INSTALLATION OF THIS WORK IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE, AND LOCAL CODES, AUTHORITIES HAVING JURISDICTION, AND STANDARDS INCLUDING BUT NOT LIMITED TO THE LATEST ADOPTED VERSIONS OF ASHRAE, IBC, IPC, IFGC, NEC, NFPA, AND SMACNA. 3. NOTHING CONTAINED IN THE SPECIFICATIONS OR SHOWN ON THE DRAWINGS SHALL BE CONSTRUED TO BE IN CONFLICT WITH ANY STATE OR LOCAL CODES, ORDINANCES OR REGULATIONS. 4. THE USE OF THE WORD "PROVIDE" SHALL MEAN TO FURNISH, INSTALL AND CONNECT, READY TO USE. 5. THE USE OF THE WORD "FURNISH" SHALL MEAN TO PROCURE AND DELIVER TO THE SITE. 6. THE USE OF THE WORD "INSTALL" SHALL MEAN TO PHYSICALLY PLACE INTO SERVICE AND CONNECT, READY TO USE. 7. EQUIPMENT AND MATERIALS SHALL BE INSTALLED BY SKILLED TRADESMEN, FAMILIAR WITH THE COMPONENTS TO BE INSTALLED, AND IN ACCORDANCE WITH BEST PRACTICES OF THE INDUSTRY. 8. THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE ONLY THE GENERAL ARRANGEMENT OF PIPING, DUCTWORK, CONDUITS, EQUIPMENT, ETC. ITEMS OF WORK OR EQUIPMENT SHOWN ON THE DRAWINGS ONLY, OR CALLED FOR IN THE SPECIFICATIONS ONLY, SHALL BE FURNISHED AND INSTALLED IN THE SAME MANNER AS IF THEY APPEARED ON BOTH DRAWINGS AND THE SPECIFICATIONS. 9. BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, FITTINGS, AND ACCESSORIES THAT MAY BE REQUIRED. THIS CONTRACTOR SHALL CAREFULLY EXAMINE THE ARCHITECTURAL, STRUCTURAL, HEATING, VENTILATING AND AIR-CONDITIONING, ELECTRICAL, PLUMBING, AND OTHER PROJECT DOCUMENTS AS MAY BE NECESSARY FOR PROPER OPERATION OR INSTALLATION AND SHALL PROVIDE OFFSETS, FITTINGS, AND ACCESSORIES TO MEET PROJECT CONDITIONS. 10. DISCREPANCIES BETWEEN DRAWINGS OR BETWEEN DRAWINGS AND SPECIFICATIONS SHALL BE REPORTED TO PROFESSIONAL IN WRITING. OBTAIN WRITTEN INSTRUCTIONS FROM PROFESSIONAL AS TO THE MANNER IN WHICH TO PROCEED. NO DEPARTURES FROM THE PROJECT DOCUMENTS SHALL BE MADE WITHOUT PRIOR WRITTEN ACCEPTANCE BY THE PROFESSIONAL. ALL PHYSICAL ATTRIBUTES OF EQUIPMENT AND DEVICES ARE BASED ON THOSE MANUFACTURERS LISTED IN THE SPECIFICATIONS AND/OR THE EQUIPMENT SCHEDULES. THE RESPECTIVE CONTRACTORS ARE RESPONSIBLE FOR ALL CHANGES BROUGHT ABOUT BY THE USE OF ITEMS BY OTHER MANUFACTURERS IF THOSE ITEMS DO NOT MATCH THE PHYSICAL ATTRIBUTES OF THE MANUFACTURERS LISTED. 11. THE FIRE RESISTANCE RATINGS OF ALL WALLS, PARTITIONS, FLOORS, STEEL, ETC. SHALL BE MAINTAINED. THE APPLICATION OF PRODUCTS AND/OR DEVICES INTENDED TO MAINTAIN THESE RATINGS SHALL BE SUBMITTED FOR REVIEW AND INSTALLED PER MANUFACTURER'S INSTRUCTIONS. 12. IN ORDER TO AVOID DELAY IN THE PROJECT SCHEDULE, AND THE POSSIBLE INSTALLATION OF NON-SPECIFIED MATERIALS, THE CONTRACTOR IS RESPONSIBLE FOR ORDERING ALL PRODUCTS IN A TIMELY FASHION. IF A DELAY OCCURS DUE TO NEGLIGENCE ON PART OF THE CONTRACTOR, ANY FINANCIAL BURDEN ENCOUNTERED WILL BE THE RESPONSIBILITY OF THE CONTRACTOR. 13. DIMENSIONS, CLEARANCES, AND LOCATIONS OF EQUIPMENT AND MATERIALS SHALL BE FIELD VERIFIED PRIOR TO ORDERING, PROCURING AND FURNISHING SAME. 14. NO EXTRA COMPENSATION OR CHARGES WILL BE ACCEPTED DUE TO DIFFERENCES BETWEEN THE ACTUAL MEASUREMENTS AND THOSE INDICATED ON THE PLAN. THOROUGHLY COORDINATE WORK WITH SITE CONDITIONS AND OTHER TRADES, DETERMINE EXACT ROUTE AND LOCATION OF EACH DUCT, PIPE, CONDUIT, ETC. BEFORE FABRICATION AND INSTALLATION. 15. THE CONTRACTOR SHALL PROVIDE AND INSTALL ACCESS PANELS, WHETHER INDICATED ON THE CONTRACT DOCUMENTS OR NOT, WHERE REQUIRED TO PROVIDE ACCESS TO THEIR INSTALLATIONS. ACCESS PANELS SHALL MATCH THE FIRE RESISTANCE RATING OF THE PARTITION THAT THEY ARE BEING INSTALLED. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL ACCESS PANELS WITH THE ARCHITECT AND WITH OTHER TRADES TO AVOID DUPLICATION. 16. INSTALL WORK SUBSTANTIALLY AS INDICATED. VERIFY LOCATIONS AND ELEVATIONS ON JOB SITE. DO NOT DIRECTLY SCALE DRAWINGS. MAKE NECESSARY CHANGES IN ELEVATION, FITTINGS, OR OFFSETS TO ACCOMMODATE OBSTACLES OR INTERFERENCES. 17. CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR DAMAGE TO THE BUILDING, PIPING OR EQUIPMENT THAT IS THE RESULT OF WORK FOR INSTALLATION OF THIS CONTRACT. 18. THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR PATCH AND REPAIR OF ALL SURFACES TO MATCH EXISTING MATERIALS AND ADJACENT FINISHES ASSOCIATED WITH INSTALLATION/REMOVAL OF THIS WORK UNLESS SPECIFICALLY NOTED OTHERWISE. 19. WORK SHALL BE COMPLETED TO MAINTAIN ALL NECESSARY AND REQUIRED CLEARANCES, ACCESSES, AND OPENINGS, SUCH THAT FULL FUNCTIONALITY, PROPER OPERATION, AND REPAIR AND MAINTENANCE ARE ENSURED. 20. WHERE DEVICE HEIGHT OF 48" OCCURS AT POINT OF CHANGE OF FINISH, THE DEVICE SHALL BE LOWERED TO OCCUR IN ONE FINISH. 21. WHERE DEVICE OCCURS IN BRICK, TILE, OR BLOCK WALLS, THEY SHALL BE MOUNTED AT A VERTICAL MASONRY JOINT & IN THE BOTTOM HORIZONTAL JOINT, CLOSEST TO THE MOUNTING HEIGHT. 22. UNLESS OTHERWISE NOTED, ALL MOUNTING HEIGHT DIMENSIONS LISTED ARE TO THE CENTER LINE OF THE BOX OR DEVICE. 23. NOT ALL ABBREVIATIONS & SYMBOLS MAY APPLY TO THIS PROJECT. 24. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE LABELED AND LISTED BY A CERTIFIED TESTING LABORATORY OR AGENCY. 25. DRAWINGS REPRESENT THE SCOPE OF WORK IN GENERAL ARRANGEMENT FORM AND ARE INTENDED TO SHOW GENERAL ROUTING AND REQUIRED SIZES/CAPACITIES OF SYSTEM COMPONENTS. GENERAL NOTES AB ABOVE AD ACCESS DOOR OR AREA DRAIN ADP APPARATUS DEW POINT AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AFUE ANNUAL FUEL UTILIZATION EFFICIENCY AGA AMERICAN GAS ASSOCIATION AHJ AUTHORITY HAVING JURISDICTION AHU AIR HANDLING UNIT AMB AMBIENT AMP AMPERES ANSI AMERICAN NATIONAL STANDARDS INSTITUTE APD AIR PRESSURE DROP ASHRAE AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS AST ABOVE GROUND STORAGE TANK ATC AUTOMATIC TEMPERATURE CONTROL ATCC AUTOMATIC TEMPERATURE CONTROLS CONTRACTOR AVG AVERAGE AWG AMERICAN WIRE GAGE AWT AVERAGE WATER TEMPERATURE AWWA AMERICAN WATER WORKS ASSOCIATION BAS BUILDING AUTOMATION SYSTEM BD BALANCING DAMPER BF BLIND FLANGE BS BIRDSCREEN BDD BACKDRAFT DAMPER BTU BRITISH THERMAL UNIT BTUH BRITISH THERMAL UNITS PER HOUR BHP BRAKE HORSEPOWER CA COMMISSIONING AGENT OR AUTHORITY CCO CEILING CLEANOUT CFM CUBIC FEET PER MINUTE CI CAST IRON CLG CEILING CONN CONNECTION CONT CONTINUATION CONV CONVECTOR COP COEFFICIENT OF PERFORMANCE CU CONDENSING UNIT CU FT CUBIC FEET CU IN CUBIC INCH CW COLD WATER °C DEGREES CELSIUS °F DEGREES FAHRENHEIT ø DIAMETER D DRYER, APPLIANCE DB DRY BULB DBP DOMESTIC BOOSTER PUMP DF DRINKING FOUNTAIN DHRP DOMESTIC HOT WATER RETURN PUMP DIR DIRECT DN DOWN DP DOMESTIC PUMP DR DRAIN DWG DRAWING DX DIRECT EXPANSION (E)EXISTING E/A EXHAUST AIR EAT ENTERING AIR TEMPERATURE EC ELECTRICAL CONTRACTOR EER ENERGY EFFICIENCY RATIO EFF EFFICIENCY ELEV ELEVATION ESP EXTERNAL STATIC PRESSURE ETR EXISTING TO REMAIN EWC ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER EWT ENTERING WATER TEMPERATURE EXT. F&B EXTERNAL FACE & BYPASS EXP EXPANSION FA FREE AREA FAS FIRE ALARM SYSTEM FC FLEXIBLE CONNECTION FD FLOOR DRAIN OR FIRE DAMPER FLA FULL LOAD AMPERES FLR FLOOR FMS FACILITY MANAGEMENT SYSTEM FOS FUEL OIL SUPPLY FOR FUEL OIL RETURN FPC FIRE PROTECTION CONTRACTOR FPI FINS PER INCH FPM FEET PER MINUTE FPS FIRE PROTECTION SYSTEM FS FLOOR SINK FT FEET OR FOOT FT LB FOOT POUND GA GAUGE GAL GALLONS GALV GALVANIZED GC GENERAL CONTRACTOR GI GREASE INTERCEPTOR GPH GALLONS PER HOUR GPM GALLONS PER MINUTE GRD GRILLES, REGISTERS, & DIFFUSERS GWH GAS WATER HEATER MECHANICAL ABBREVIATIONS H HUMIDITY HC HEATING CONTRACTOR HD HEAD HGT HEIGHT HP HORSEPOWER HR HOUR(S) HUM HUMIDIFIER HW HOT WATER HZ HERTZ ID INSIDE DIAMETER IN WC INCHES WATER COLUMN INV INVERT IN WG INCHES WATER GAGE IW INDIRECT WASTE JS JANITORS SINK KW KILOWATT KWH KILOWATT HOUR LxWxD LENGTH x WIDTH x DEPTH LAT LEAVING AIR TEMPERATURE L LAVATORY LAV LAVATORY LF LINEAR FEET LD LINEAR DIFFUSER LBS POUNDS LRA LOCKED ROTOR AMPERES LWT LEAVING WATER TEMPERATURE M/A MIXED AIR MAX MAXIMUM MBH 1,000 BTUH MMBH 1,000,000 BTUH MC MECHANICAL CONTRACTOR MD MOTORIZED DAMPER MFR MANUFACTURER MIN MINIMUM MOD MOTOR OPERATED DAMPER MR MOP RECEPTOR MTD MOUNTED N/A NOT APPLICABLE NC NORMALLY CLOSED NIC NOT IN CONTRACT NG NATURAL GAS NO NORMALLY OPEN NP NON-POTABLE NTS NOT TO SCALE O/A OUTSIDE AIR OD OUTSIDE DIAMETER OR OVERFLOW DRAIN OED OPEN END DUCT OZ OUNCE P PUMP PC PLUMBING CONTRACTOR PD PRESSURE DROP PH PHASE PPM PARTS PER MILLION PRV PRESSURE REDUCING VALVE PSI POUNDS PER SQUARE INCH PSIG POUNDS PER SQUARE INCH GAUGE PT PRESSURE/TEMPERATURE TEST PORT PVC POLYVINYLCHLORIDE R/A RETURN AIR RD ROOF DRAIN REQ'D REQUIRED RH RELATIVE HUMIDITY RLA RUNNING LOAD AMPS RPM REVOLUTIONS PER MINUTE RX REMOVE EXISTING S SINK S/A SUPPLY AIR SATC SUSPENDED ACOUSTICAL TILE CEILING SF SQUARE FEET S/FD SMOKE/FIRE DAMPER SH SHOWER SI SOLIDS INTERCEPTOR SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION SP STATIC PRESSURE T TEMPERATURE TBR TO BE REMOVED TCC TEMPERATURE CONTROL CONTRACTOR TD TRENCH DRAIN THA TOTAL HEAT ADDED TP TEST PORT TSP TOTAL STATIC PRESSURE TSTAT THERMOSTAT TT TEMPERATURE TRANSMITTER TYP TYPICAL UNO UNLESS NOTED OTHERWISE UST UNDERGROUND STORAGE TANK UR URINAL V VENT VAV VARIABLE AIR VOLUME VBF VENT BELOW FLOOR VRV VARIABLE REFRIGERANT VOLUME VTR VENT THROUGH ROOF W WASHER, APPLIANCE OR WASTE WB WET BULB WC WATER CLOSET WPD WATER PRESSURE DROP HVAC SYMBOL LEGEND CONNECT TO EXISTING DISCONNECT EXISTING SUPPLY AIRFLOW RETURN/ EXHAUST AIRFLOW DUCT SECTION, EXHAUST DUCT SECTION, RETURN OR RELIEF AIR DUCT SECTION, SUPPLY OR OUTDOOR AIR SUPPLY AIR DEVICE RETURN/ EXHAUST AIR DEVICE RECTANGULAR ELBOW, MITERED WITH TURNING VANES VOLUME DAMPER FIRE & SMOKE DAMPER, PROVIDE ACCESS DOOR WHERE SHOWN THERMOSTAT CHANGE OF DIRECTION, RISE (R), DROP (D) DUCT ACCESS DOOR FLEX DUCT DUCT TRANSITIONS, RECTANGULAR T R D DUCT TRANSITION, RECTANGULAR TO ROUND 24x18 DUCT, WIDTH x HEIGHT (E)24x18 EXISTING DUCT TO REMAIN, WIDTH x HEIGHT EXISTING DUCT TO BE REMOVED, WIDTH x HEIGHT24x18 DUCT, ROUND DIAMETER SIZE24ø AD VD 1. THE DEMOLITION PLANS AND NOTES HAVE BEEN PREPARED TO ASSIST THE CONTRACTORS IN IDENTIFYING THE AREAS AND ITEMS OF DEMOLITION AND RENOVATION ASSOCIATED WITH THIS PROJECT. THE INFORMATION PROVIDED IS NOT MEANT TO BE ALL-INCLUSIVE IN TERMS OF LISTING EACH AND EVERY SPECIFIC TASK TO BE PERFORMED. EACH CONTRACTOR WILL THOROUGHLY EXAMINE ALL CONTRACT DOCUMENTS PRIOR TO PERFORMING ANY WORK. 2. DEMOLITION WORK INCLUDES, BUT IS NOT LIMITED TO, THE ITEMS INDICATED ON THE DEMOLITION DRAWINGS AND DESCRIBED IN THE DEMOLITION NOTES. THE EXTENT OF THE DEMOLITION WORK WILL INCLUDE ALL WORK REQUIRED TO COMPLETE THE PROJECT AND ENSURE WHETHER OR NOT THE WORK IS INDICATED ON THE DRAWINGS. 3. EACH CONTRACTOR SHALL THOROUGHLY EXAMINE AND VERIFY ALL EXISTING CONDITIONS BEFORE PERFORMING ANY WORK AND IMMEDIATELY NOTIFY THE ARCHITECT, IN WRITING, OF ANY DISCREPANCIES WITH THE DRAWINGS. 4. ANY WORK PERFORMED AS PART OF THIS CONTRACT REQUIRING OR ALTERATION WILL BE THE RESPONSIBILITY OF THE RESPECTIVE CONTRACTOR. 5. ALL ITEMS NOTED TO BE REMOVED TO BE DISPOSED OF OFF-SITE BY RESPECTIVE CONTRACTORS, UNLESS NOTED OTHERWISE. WHERE INDICATED ON THE DRAWINGS AND/OR IN THE NOTES AS SALVAGE AND DELIVER TO OWNER. THE CONTRACTOR WILL CAREFULLY REMOVE INDICATED ITEMS AND STORE THEM WHERE DIRECTED BY THE OWNER. 6. THE OWNER HAS THE OPTION TO RETAIN POSSESSION OF ANY REMOVED MATERIALS OR EQUIPMENT. ALL SUCH ITEMS SHALL BE CAREFULLY REMOVED AND STORED AT THE SITE BY THE CONTRACTOR WHERE DIRECTED BY THE OWNER. ANY MATERIALS OR EQUIPMENT NOT RETAINED BY THE OWNER WILL BECOME THE PROPERTY OF THE CONTRACTOR AND PROMPTLY REMOVED FROM SITE. 7. ANY CONTRACTOR REMOVING OR MODIFYING MATERIAL CONTAINING ASBESTOS OR SUSPECTED OF CONTAINING ASBESTOS WILL NOTIFY THE OWNER AT ONCE AND STOP REMOVAL. IDENTIFICATION AND/OR REMOVAL OF ASBESTOS CONTAINING MATERIAL WILL BE THE RESPONSIBILITY OF THE OWNER. 8. REFER TO ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, TECHNOLOGY AND PLUMBING DRAWINGS FOR DEMOLITION WORK BY RESPECTIVE CONTRACTORS. EACH CONTRACTOR IS RESPONSIBLE FOR ALL DEMOLITION ASSOCIATED WITH HIS CONTRACT AND SCOPE OF WORK. EACH CONTRACTOR IS RESPONSIBLE TO PATCH AND/OR REPAIR ANY AND ALL CONSTRUCTION AFFECTED BY HIS DEMOLITION. THE EXTENT OF PATCH AND REPAIR SHALL BE AS REQUIRED TO RECEIVE THE SCHEDULED NEW WORK. ALL CONTRACTORS ARE RESPONSIBLE FOR COORDINATION OF WORK WITH OTHER CONTRACTORS BEFORE PERFORMING ANY WORK. 9. ALL PATCH AND REPAIR WORK SHALL BE PERFORMED USING MATERIALS THAT MATCH THE EXISTING ADJACENT CONSTRUCTION. WHERE PATCHING EXISTING MASONRY WALLS OR INFILLING BETWEEN WALLS WITH MASONRY TO MATCH EXISTING, "TOOTH-IN" NEW MASONRY TO EXISTING. 10. EACH CONTRACTOR IS RESPONSIBLE TO PROTECT ALL EXISTING CONSTRUCTION SCHEDULED TO REMAIN. EACH CONTRACTOR IS RESPONSIBLE TO PATCH AND/OR REPAIR ANY AND ALL CONSTRUCTION AFFECTED BY THEIR DEMOLITION. EACH CONTRACTOR SHALL PATCH (SUBSTRATE AND FINISHED SURFACES) ANY EXISTING FINISHES AFFECTED BY THEIR RESPECTIVE WORK. 11. EXISTING CONDITIONS INDICATED ARE OBTAINED FROM AVAILABLE SOURCES (EXISTING DRAWINGS, FIELD SURVEYS, ETC.) AND ARE NOT GUARANTEED TO BE TRUE AND EXACT. CONTRACTOR(S) SHALL FIELD VERIFY EXISTING CONDITIONS AND NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH THE AFFECTED PORTION OF THE WORK. 12. REMOVAL IN ITS ENTIRETY INCLUDES HANGERS, ELECTRICAL, CONTROLS, ETC., TO LEAVE A LIKE NEW OR MATCHING EXISTING CONDITION. 13. THIS CONTRACTOR SHALL INVESTIGATE THE IMPACTS OF DEMOLITION TO THE SOUROUNDING SPACES PRIOR TO DEMOLITION ACTIVITIES. THIS CONTRACTOR IS RESPONSIBLE TO COORDINATE DEMOLITION ACTIVITY AND PROVIDE NOTICE OF DISRUPTIVE ACTIVITIES TO THE OWNER PRIOR TO STARTING ANY DEMOLITION WORK. GENERAL DEMOLITION NOTES BALL VALVE DEMO (DASHED-HEAVY LINE) EXISTING (LIGHT SOLID LINE) CHILLED WATER SUPPLY CHILLED WATER RETURN PROCESS CHILLED WATER SUPPLY PROCESS CHILLED WATER RETURN (E) CWS CWR PCHWS PCHWR TEMPERATURE SENSORS D P HEATING WATER SUPPLY HEATING WATER RETURN HWS HWR RE-HEAT HEATING WATER SUPPLY RE-HEAT HEATING WATER RETURN RHHWS RHHWR SUPPLY/EXHAUST VAV TERMINAL UNIT SUPPLY/EXHAUST VALVE DUCT AND EQUIPMENT TO BE REMOVED These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:49 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 CWC MECHANICAL SYMBOLS, NOTES & ABBREVIATIONS AT CSH M-001 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 F/SF/SF/S24x8 12x814x822x8EA 12x8EA12x8SA 22x8 12x8 12x8SACR 14x8 14x814x812x8 CD CD CD D D D D CD CD CD VAVE 4-13 VAVS 4-21 VAVE 4-14 VAVE 4-16 VAVS 4-22 VAVE 4-15 1 1 2 3 4 3 5 5 6 1 3 5 D CD 7 7 9 8 10 EXISTING FCU AD EXISTING DUCT SMOKE DETECTOR EXISTING DUCT SMOKE DETECTOR11F/S375 SF GENERAL LAB 472 359 SF ATOMIZER ROOM 472B 121 SF LASER ROOM 472A 22x8EA 12x8EA12x8SA 12x8SACR VAVE 4-13 VAVS 4-21 EAV-1 EAV-2 SAV-1 EAV-3 RH-1 RH-3 RH-2 8x6 14x8 10x8 4ø 4ø 10x8 8ø 8x8 8x814x814x824x8 30x8 30x8 36x8 24x8 P P P P 10x86ø 10ø 10ø 24x12 30x8 VD VD VD VD VD VD VD VD VD 12x8S-2 12"ø 705 F/S 8ø S-2 12"ø 705 S-1 8"ø 185 FCU-3 8x8R-1 8"ø 120 10x8 R-2 18x10 200 R-1 6"ø 140 R-1 8"ø 120 S-1 8"ø 165 S-1 8"ø 185 14x812x8 1 1 1 1 2 3 3 4 5 6 7 88 FCU-2 FCU-1 4ø DUCT SHAFT 5 44X20 EAD UP/DN 18X18 RAD UP/DN 54X20 SAD UP/DN 10 EXISTING FCU AD 11 6ø 4ø 4ø SVAV-1 EVAV-1 SVAV-2 EVAV-2 6ø T T T 12 PROVIDE FIRE RATED INSULATION ON NEW EXHAUST DUCT. EXISTING FCU EXISTING FCU These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:52 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 CWC PARTIAL MECHANICAL FOURTH FLOOR PLANS AT CSH M-110 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 1/4" = 1'-0" 1 ROOM 472 DEMOLITION PLAN - DUCTWORK & MECHANICAL PIPING 1/4" = 1'-0" 2 ROOM 472 NEW WORK PLAN - DUCTWORK #DEMOLITION KEY NOTES 1. REMOVE EXISTING VAVE UNIT AND ASSOCIATED ACCESSORIES AND CONTROLS. COORDINATE WITH OTHER TRADES FOR POWER DISCONNNECT AND REMOVAL. TURN UNIT OVER TO CORNELL UNIVERSITY. 2. REMOVE EXISTING VAVS UNIT AND ASSOCIATED ACCESSORIES AND CONTROLS. COORDINATE WITH OTHER TRADES FOR POWER DISCONNNECT AND REMOVAL. TURN UNIT OVER TO CORNELL UNIVERSITY. 3. REMOVE EXISTING EXHAUST DUCTWORK, HANGERS AND ASSOCIATED ACCESSORIES BACK TO POINT SHOWN AND PREPARE FOR NEW CONNECTION. 4. REMOVE EXISTING SUPPLY DUCTWORK, HANGERS AND ASSOCIATED ACCESSORIES BACK TO POINT SHOWN AND PREPARE FOR NEW CONNECTION. 5. REMOVE EXISTING EXHAUST DUCTORK, TAPS, EXHAUST GRILLES, HANGERS AND ASSOCIATED ACCESSORIES. 6. REMOVE EXISTING SUPPLY DUCTWORK, SUPPLY DIFFUSERS, HANGERS AND ASSOCIATED ACCESSORIES. 7. REMOVE EXISTING FIRE/SMOKE DAMPER. COORDINATE WITH OTHER TRADES FOR POWER DISCONNECT AND REMOVAL. 8. DISCONNECT EXISTING SUPPLY AIR DIFFUSER AND SAVE FOR RELOCATION. REFER TO NEW WORK PLAN THIS SHEET FOR NEW LOCATION. 9. COORDINATE RELOCATION OF FIRE/SMOKE DAMPER CONTROL BOXES, AND NEW DUCT INSTALLATION. 10. REMOVE EXISTING ACCESS PANEL IN EXISTING DUCT. 11. COORDINATE REMOVAL AND REINSTALLATION OF DUCT SMOKE DETECTOR WITH OTHER TRADES. NEW WORK KEY NOTES 1. INSTALL AIR VALVE WITH THE CONTROL BOX FACING TOWARD THE FLOOR FOR MAINTENANCE ACCESS. 2. ROUTE 14x4 EXHAUST DUCT DOWN IN NEW WALL. LOCATE BOTTOM OF RETURN GRILLE 6" A.F.F. 3. FIELD COORDINATE EXHAUST DUCT DROP WITH FINAL EQUIPMENT PLACEMENT PROVIDE BLAST GATE ON VERTICAL DROP IN LOCATION WHERE IS IT ACCESSABLE TO USER. BALANCE TO 50 CFM. 4. FIELD COORDINATE EXHAUST DROP WITH FINAL EQUIPMENT PLACEMENT. PROVIDE BLAST GATE ON VERTICAL DROP IN LOCATION WHERE IT IS ACCESSABLE TO USER. BALANCE TO 200 CFM. 5. CONNECT NEW SUPPLY DUCT TO EXISTING SUPPLY DUCT RISER WITH BOOT CONNECTION. PROVIDE NEW FIRE/SMOKE DAMPER, COORDINATE WITH FA AND ELEC. TRADES. 6. RECONNECT EXISTING 12x8 SUPPLY DUCT TO NEW 36x8 SUPPLY DUCT. 7. CONNECT NEW EXHAUST DUCT TO EXISTING 44X20 EXHAUST DUCT RISER. 8. PROVIDE STAINLESS STEEL EXHAUST DUCT FROM FUME HOOD CONNECTION TO 24x12 EXHAUST DUCT BRANCH. 9. COORDINATE FIRE PIPE RELOCATION FOR CLEARENCE TO NEW ACCESS DOOR. 10. NEW LOCATION OF RELOCATED DUCT SMOKE DETECTOR. 11. PROVIDE NEW 24"x12" HINGED ACCESS DOOR IN BOTTOM OF DUCT FOR ACCESS TO FS DAMPER. 12. ANY CLEARANCE BETWEEN FIRE RATED WALL AND EXHAUST AIR DUCT SHALL BE FILLED WITH FIRE RESISTANT PACKING ON ALL SIDES TO MAINTAIN FIRE RATING. # SUPPLY AIR VALVE SCHEDULE UNIT TAG SERVE VALVE QTY. MOUNTING POSITION FACTORY OCCUPIED SET POINT UNOCCUPIED MAX INLET PRESSURE AT MAX CFM (IN. WC) INLET SIZE (IN.) RAD N.C. AT 1" S.P. 125 Hz DISC. N.C. AT 1" S.P. 125 Hz MANUFACTURER & MODEL NOTES MAX CFM MIN CFM MAX CFM MIN CFM MAX CFM MIN CFM SAV-1 GENERAL LAB 1 HORIZONTAL 1,461 180 1,310 310 1,310 180 0.3 12 43 58 ACCUTROL AVC6100 1,2,3,4 NOTES: 1. PROVIDE HIGH SPEED ELECTRIC ACTUATION. 2. UNIT TO BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS. 3. ACTUATOR TO FAIL NORMALLY CLOSED. 4. PROVIDE OPTION FOR TIGHT SHUT OFF. EXHAUST AIR VALVE SCHEDULE UNIT TAG SERVE VALVE QTY. MOUNTING POSITION FACTORY OCCUPIED SET POINT UNOCCUPIED MAX INLET PRESS AT MAX CFM IN. WC INLET SIZE (IN.) RAD N.C. AT 1" S.P. 125 Hz DISC. N.C. AT 1" S.P. 125 Hz MANUFACTURER & MODEL NOTES MAX CFM MIN CFM MAX CFM MIN CFM MAX CFM MIN CFM EAV-1 5' FUME HOOD 1 HORIZONTAL 1,056 120 630 90 630 90 0.3 10 51 61 ACCUTROL AVC6100 1,2,4,5 EAV-2 6' FUME HOOD 1 HORIZONTAL 1,056 120 780 110 780 110 0.3 10 51 62 ACCUTROL AVC6100 1,2,4,5 EAV-3 GENERAL LAB 1 HORIZONTAL 254 30 210 30 0 0 0.3 6 32 50 ACCUTROL AVC6100 1,3,4,5 NOTES: 1. UNIT TO BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS. 2. ACTUATOR TO FAIL NORMALLY OPEN. 3. ACUATOR TO FAIL NORMALLY CLOSED. 4. PROVIDE HIGH SPEED ELECTRIC ACTUATION. 5. ROVIDE OPTION FOR TIGHT SHUT OFF. FAN COIL UNIT SCHEDULE UNIT TAG LOCATION CFM SPEED MOTOR COOLING COIL 47°F E.W.T. MANUFACTURER & MODEL NOTES(QTY.) HP VOLTS/P H/HZ MCA TOTAL SENS.GPM ROWS P.D. FT. HD CHW dT E.A.T L.A.T. BTUH BTUH DB WB DB WB FCU-1 LASER ROOM 560 MED (1) 1/4 208/1/60 2 12,264 12,264 1.70 5 2.9 14 75.0 58.4 55.0 50.2 JOHNSON CONTROLS FHX-D09 1,2,3,4,5,6,7,8,11 FCU-2 ATOMIZER ROOM 1,825 MED (2) 1/3 208/1/60 6.75 40,823 40,823 5.70 6 6.8 14 75.0 58.4 54.5 49.9 JOHNSON CONTROLS FNX-20 1,2,3,4,5,6,9,10,11 FCU-3 ATOMIZER ROOM 1,825 MED (2) 1/3 208/1/60 6.75 40,823 40,823 5.70 6 6.8 14 75.0 58.4 54.5 49.9 JOHNSON CONTROLS FNX-20 1,2,3,4,5,6,9,10,11 NOTES: 1. MOTORS TO BE ELECTRICALLY COMMUTATED, BRUSHLESS DC-TYPE. 2. PROVIDE UNITS WITH FACOTRY MOUNTED DISCONNECT SWITCH. 3. PROVIDE UNITS WITH 1" THROWAWAY MERV 8 FILTER. 4. PROVIDE INTERNALLY INSULATED CABINET WITH 1/2" FIBERGLASS INSULATION AND INSULATION PACKAGE FOR COIL AND CONDENSATE PAN SECTION. 5. CONTROLS TO BE PROVIDED BY OTHERS. 6. PROVIDE STAINLESS STEEL EXTENDED DRAIN PAN AND INSTALL THE WHOLE CONTROL VALVE OVER THE PAN. 7. PROVIDE SUPPLY AND RETURN STAMPED LOUVER GRILLE. 8. PROVIDE BOTTOM RETURN. 9. PROVIDE DOUBLE DEFELCTION SUPPLY GRILLE. 10. PROVIDE REAR RETURN, WITH OPEN DUCT COLLAR. 11. PROVIDE CONDENSATE OVERFLOW SWITCH IN THE PRIMARY DRAIN PAN AND TIE ALARM INTO BMS. REGISTER, GRILL & DIFFUSER SCHEDULE UNIT TAG FACE SIZE FACE LOCATION MATERIAL FINISH USE MANUFACTURER & MODEL NOTES S-1 24x24 SEE PLAN STEEL BY ARCH. SUPPLY KRUEGER PLQ 1,2 S-2 24x48 SEE PLAN ALUMINUM BY ARCH. SUPPLY KRUEGER TAD 1,5 R-1 24x24 SEE PLAN STEEL BY ARCH. EXHAUST KRUEGER PLQ 1 R-2 18x10 SEE PLAN STEEL BY ARCH. EXHAUST KRUEGER S80 3,4 NOTES: 1. SEE PLANS FOR NECK SIZE. 2. VOLUME DAMPER TO BE INSTALLED ON ALL BRANCH DUCTS SERVING EACH SUPPLY DIFFUSER. 3. SURFACE MOUNT FRAME. 4. 35° HORIZONTAL BLADE SIDEWALL RETURN 5. 180° DISCHARGE AIR PATTERN VAV SUPPLY AIR TERMINAL UNITS UNIT TAG SERVE OCCUPIED CFM UNOCCUPIED CFM INLET SIZE FACTORY MAX. NC MIN. INLET PRESSURE (IN WC) MANUFACTURER & MODEL NOTESMAX CFM MIN CFM SVAV-1 LASER ROOM 165 95 4 400 45 29 0.30 PRICE SDV5 1,2,3,4 SVAV-2 ATOMIZER ROOM 370 150 6 550 65 22 0.30 PRICE SDV5 1,2,3,4 NOTES: 1. UNIT TO BE CONTROLLED BY VACANCY SENSOR . 2. CONTROLS TO BE SUPPLIED BY THE BACS CONTRACTOR. 3. UNIT TO BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS. 4. PROVIDE INTEGRAL AIR FLOW SENSOR. VAV EXHAUST AIR TERMINAL UNITS SCHEDULE UNIT TAG SERVE OCCUPIED CFM UNOCCUPIED CFM INLET SIZE FACTORY MAX. NC MIN. INLET PRESSURE (IN WC) MANUFACTURER & MODEL NOTESMAX CFM MIN CFM EVAV-1 LASER ROOM 140 70 4 400 45 29 1 PRICE SDEV5 1,2 EVAV-2 ATOMIZER ROOM 420 200 6 550 65 29 1 PRICE SDEV5 1,2 NOTES: 1. CONTROLS TO BE SUPPLIED BY THE BACS CONTRACTOR. 2. UNIT TO BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS. HOT WATER REHEAT COIL SCHEDULE UNIT TAG SERVE EAT (°F) LAT (°F)CFM MBH APD IN. H2O EWT (°F) LWT (°F)GPM WPD (FT. HD) WIDTH (IN) HEIGHT (IN) FACE VEL. (FPM) ROWS FINS/IN MANUFACTURER & MODEL RH-1 GENERAL LAB 55 70.0 1,410 24,014 0.19 130 99.9 1.60 1.50 36 9.0 649 1 13 DAIKIN RH-2 LASER ROOM 55 75.6 165 3,722 0.19 130 109.4 0.40 0.20 8 6.0 495 2 10 DAIKIN RH-3 ATOMIZER 55 80.1 370 8,774 0.17 130 99.9 0.60 0.30 12 9.0 427 2 12 DAIKIN These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:52 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 CWC MECHANICAL SCHEDULES AT CSH M-500 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 SUPPLY AIR RETURN / EXHAUST AIR BRANCH DUCT MAIN DUCT TAPERED CONNECTION 45deg ANGLE OR CONICAL CONNECTION (IF ROUND) VOLUME DAMPER FUME HOOD @ ADA HEIGHT, 30" AFF. FUME HOOD @ NON-ADA HEIGHT, 36" AFF. ADA FUME HOOD WITH HEIGHT ADJUSTABLE 12" FLEXIABLE EXHAUST DUCT TO EXHAUST VALVE COMPRESS 6"MINIMUM 3" OF STRAIGHT DUCT TO REMAIN ABOVE CEILING WHILE EXTENDED. PROVIDE CHROME GROMMET AROUND CEILING OPENING TO GUIDE DUCTWORK CHROME GROMMET AROUND BOTH SIDES OF THE CEILING. STAINLESS STEEL DUCT NORMAL FULLY RAISED.STAINLESS STEEL DUCT NORMAL FULLY EXTENDED. PROVIDE 12" FLEXIBLE PVC EXHAUST DUCT NORMAL FULL EXTEND TO BE MIN. OF 36" LENGTH. DUCT SHALL MEET UL 94V-0 FOR FLAME RETARDANCE. MANUFACTURED BY MCMASTER CARR MODEL# 5666K93 OR ENGINEER APPROVED EQUAL. 18" SECTION OF DUCT 2 GAGES HEAVIER 18" SECTION OF DUCT 2 GAGES HEAVIERDUCT ANCHOR DUCT ANCHOR DAMPER CONTROLLER CONTROLLER EXHAUST OR SUPPLY BOX R = D 1.5 x D MIN. 3D MIN 3D MAINTAIN FULL SIZE OF DUCT LIP TO AIR VALVE. REDUCE AT INLET. DAMPER PETE'S PLUG (TYP) MANUAL AIR VENT STRAINER WITH BLOWDOWN BALL VALVE AND CAP. UNION (TYP) 3/4" COIL DRAIN VALVE WITH HOSE END CONNECTION AND CAP. CONTROL VALVEISOLATION BALL VALVE (TYP) SUPPLY RETURN BALANCE VALVE HEATING COIL SLAB SHEET METAL SCREW DUCT FINISHED FLOOR SUPPORT DUCT FROM SLAB ABOVE METAL HANGER (LOAD NOT TO EXCEED 50 LBS.) NOTES: 1. DUCTS SHALL NOT BE HUNG FROM OR SUPPORTED BY HUNG CEILING. 2. FOR DUCTS NOT EXCEEDING 2 SQ. FT. IN CROSS-SECTIONAL AREA, HANGERS SHALL BE OF METAL NOT LESS THAN 16 GA. 3. FOR DUCTS LARGER THAN 2 SQ. FT. IN CROSS-SECTIONAL AREA, HANGERS SHALL BE OF METAL NOT LESS THAN 12 GA. 4. HANGERS FOR ALL DUCTS SHALL BE TURNED UNDER AND FASTENED TO THE BOTTOM OF DUCT AS SHOWN ABOVE. 5. WHERE CROSS-SECTIONAL AREA OF DUCT EXCEEDS 8 SQ. FT., HANGERS SHALL BE SPACED NOT MORE THAN 4 FT. ON CENTERS. 6. ON DUCTS OVER 48" WIDE, BOTTOM SHALL BE BRACED BY ANGLE. FOR CROSS-SECTIONAL AREA MORE THAN 8 SQ. FT., DUCT SHALL BE BRACED BY ANGLES ON ALL FOUR SIDES. NOTES: 1. THE INSTALLATION OF THE DAMPER AND ALL DUCT CONNECTIONS TO THE DAMPER SLEEVE SHALL CONFORM TO NFPA-80, NFPA-90A AND THE SMACNA FIRE, SMOKE AND RADIATION DAMPER INSTALLATION GUIDE. 2. ALL DUCT CONNECTIONS SHALL CONFORM TO UL555. 3. THE OPENING OF THE WALL FOR THE FIRE RATED DAMPER SHALL BE SIZED TO PROVIDE EXPANSION CLEARANCE BETWEEN THE SLEEVE AND THE OPENING. THE EXPANSION CLEARENCE BETWEEN THE FIRE DAMPER AND WALL SHALL BE 1/8" PER FOOT OF PERIMETER. 4. ANY CLEARANCE BETWEEN FIRE-RATED WALL OR PARTITION AND DAMPER SLEEVE OR DAMPER SHALL BE FILLED WITH FIRE-RESISTANT PACKING ON ALL SIDES TO MAINTAIN FIRE RATING. 5. WHEN DUCTWORK IS INSULATED OR LINED, PROVIDE INSULATED ACCESS DOOR. HINGED ACCESS DOOR SIZE AS INDICATED ON PLANS BUT NOT LESS THAN 12X12 (EITHER SIDE OR BOTTOM) DUCT FIRE-RATED WALL OR PARTITION (TYPE AND SIZE VARIES). FIRE-RATED WALL OR PARTITION (TYPE AND SIZE VARIES). OPERATOR/ACTUATOR OUT OF AIR STREAM 16 GAUGE WALL SLEEVE DAMPER FRAME CAULKING MATERIAL (TYP) 6" MAX 16" MAX FOR ACCESS DOOR OPERATING JACKSHAFT 1" MINIMUM TYPICAL OVERLAP ON ALL SIDES OF PARTITION WALL 1-1/2" x 1-1/2" 20 GA. MINIMUM ANGLE IRON ALL AROUND. (TYP) NOTES: 1. BOX SENSOR SHALL BE ORIENTED IN SAME PLANE AS ELBOW AND BE WITHIN 10' OF HORIZONTAL OR PER MANUFACTURER'S RECOMMENDATION. 2. IF INDICATED STRAIGHT RUN CANNOT BE OBTAINED, A FLOW -STRAIGHTENER SHALL BE PROVIDED AT THE BOX INLET. DAMPER CONTROLLER DAMPER CONTROLLER AIR-TERMINAL BOX 3D D D 3 x D R = D 1.5 x D RE-HEAT COIL RE-HEAT COIL CWR CWS COOLING COIL SHUT OFF VALVE (TYP.) BALANCING VALVE (TYP.) 2-WAY CONTROL VALVE MANUAL AIR VENT UNION (TYP.) STRAINER BLOWDOWN W/ BRASS HOSE CONNECTION, CAP WITH CHAIN. CONDENSATE DRIP PAN REDUCER, IF REQUIRED SLOPE TO NEAREST DRAIN COIL DRAIN W/ BRASS HOSE CONNECTION, CAP AND CHAIN (TYP) PETE'S PLUG (TYP) PCHWS 1-1/4" PCHWR 1-1/4" BALANCING VALVE (TYP.) BALANCE TO 1/2 GPM UNION (TYP) SHUT OFF VALVE (TYP) THREADED FOR CONNECTION TO 3/4" FPT REDUCER (TYP) DUCT, SEE PLANS FOR SIZES VOLUME DAMPER FLEX DUCT CEILINGCEILING DIFFUSER STEEL BEAM CLAMP CABLE / WIRE EXPOSED ROUND / OVAL DUCT ADJUSTER / CABLE CLAMP CABLE / WIRE SIZE BASED ON MANUFACTURER, DUCT SIZE, SPACING, AND SPECIFICATIONS SLAB ANCHOR CABLE / WIRE These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:53 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 CWC MECHANICAL DETAILS AT CSH M-501 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 1/16" = 1'-0" 3 DUCT TAKE-OFFS 12" = 1'-0" 2 ADA FUME HOOD INSTALLATION DETAIL 1/16" = 1'-0" 4 VORTEX SHEDDING AIR VALVE BOX CONNECTIONS 1/16" = 1'-0" 5 RE-HEAT COIL DETAIL 12" = 1'-0" 6 DUCT SUPPORT FROM SLAB 12" = 1'-0" 1 COMBINATION FIRE/SMOKE DAMPER DETAIL 1/16" = 1'-0" 8 AIR TERMINAL BOX CONNECTIONS 12" = 1'-0" 9 CHILLED WATER COOLING COIL DETAIL 12" = 1'-0" 7 PROCESS CHILLED WATER BYPASS DETAIL 12" = 1'-0" 11 CEILING DIFFUSER CONNECTION DETAIL 12" = 1'-0" 10 EXPOSED DUCT SUPPORT DETAIL 375 SF GENERAL LAB 472 359 SF ATOMIZER ROOM 472B 121 SF LASER ROOM 472A RH-1 RH-3 RH-2 FCU-1 FCU-3 3 1 1 1 2 P P P P P P P P P (E) 2" RHHWS(E) 2" RHHWR (E) 2" PCHWR (E) 2" PCHWS 1-1/4" PROCESS CHWR 1-1/4" PROCESS CHWS 1-1/4" PROCESS CHWR 1-1/4" PROCESS CHWS 3/4" CHWR 3/4" CHWS 1/2" RHHWR 1/2" RHHWS 1/2" RHHWR 1/2" RHHWS 1/2" RHHWS 1/2" RHHWR 1" CHWR 1" CHWS 1" CHWR 1" CHWS 1" CHWR 1" CHWS 1-1/2" CHWR 1-1/2" CHWS 5 4 1-1/4" PROCESS CHWR 1-1/4" PROCESS CHWS FCU-2 PIPE CHASE G 4" CHWS UP/DN 2" CHWR UP/DN 4" HWS UP/DN 2" HWR UP/DN 1" DR UP/DN P ISOLATION VALVES These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:57 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 CWC PARTIAL MECHANICAL PIPING FOURTH FLOOR PLAN AT CSH MP-110 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 1/4" = 1'-0" 1 ROOM 472 NEW WORK PLAN - MECHANICAL PIPING NEW WORK KEY NOTES 1. CONNECT NEW HW REHEAT SUPPLY AND RETURN PIPING TO EXISTING 2" RHHWS AND 2" RHHWR PIPING. 2. CONNECT NEW CHILLED WATER SUPPLY AND RETURN PIPING TO EXISTING 4" CHWS AND 2" CHWR PIPING LOCATED IN PIPE CHASE G. 3. CONNECT NEW PROCESS CHILLED WATER SUPPLY AND RETURN PIPING TO EXISTING 2" PROCESS CHWS AND 2" PROCESS CHWR PIPING. 4. EXTEND 1-1/4" PROCESS CHWS AND 1-1/4" PROCESS CHWR TO ATOMIZER HEAT EXCHANGER. TEMRMINATE 60" A.F.F., FIELD COORDINATE FINAL LOCATION WITH FINAL EQUIPMENT PLACEMENT. SEE DETAIL 7 ON SHEET M-501 FOR FINAL CONNECTION. 5. EXTEND 1-1/4" PROCESS CHWS AND 1-1/4" PROCESS CHWR TO GLOVE BOX. TEMRMINATE 60" A.F.F., FIELD COORDINATE FINAL LOCATION WITH FINAL EQUIPMENT PLACEMENT. PROVIDE LINE SIZE ISOLATION VALVES AND THREADED PLUG FOR FUTURE CONNECTION. # BACS CONTROL SYMBOL LEGEND ANALOG INPUT ANALOG OUTPUT BINARY INPUT BINARY OUTPUT ANALOG VALUE BINARY VALUE VARIABLE FREQUENCY DRIVE NORMALLY CLOSED NORMALLY OPEN FAIL LAST POSITION T BINARY POINT F COM ANALOG POINT SYMBOL AI AO BI BO AV BV VFD N.C. N.O. F.L.P. NAME TEMPERATURE SENSOR FLOW SENSOR NETWORK COMMUNICATION INTERFACE POINT, BACnet MSTP MOD MODULATING DEVICE TSA D ROOM TEMPERATURE SENSOR W/ SETPOINT ADJUSTMENT & VISUAL DISPLAY SYMBOL NAME OC OCCUPANCY SENSOR VO PUSH-BUTTON EMERGENCY VENTILATION OVERRIDE VS VACANCY/ OCCUPANCY SENSOR T TEMPERATURE SENSOR W/ SETPOINT ADJUSTMENT & VISUAL DISPLAY SA D COMBINATION TEMPERATUR AND RELATIVE HUMIDITY (RNET) SENSOR RH RELATIVE HUMIDITY SENSOR GENERAL NOTE: 1. RH TRENDED AND SHOWN AS GRAPHIS 2. RH SENSOR USED TO SALCULATE DEW POINT IN BMS DEVICE INTERCONNECTION WIRING AO ANALOG OUTPUT - DEVICE INTERCONNECTION WIRING These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:54 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 CS BMS CONTROLS LEGEND & NOTES AT CWC MI-600 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 LASER ROOM POINTS LIST (427A) HARDWIRE POINTS SOFTWARE POINTS SHOWN ON GRAPHIC NOTESBI BO AI AO AV BV SCH TREND ALARM BACS EMCS DESCRIPTION SUPPLY AIR VAV BOX AIR FLOW FEEDBACK (CFM)X X X 10% FLOW DEVIATION FROM SETPOINT X BACnet MSTP NETWORK POINT SUPPLY AIR VAV BOX AIR FLOW SETPOINT (CFM)X X X BACnet MSTP NETWORK POINT SUPPLY AIR VAV BOX POSITION FEEDBACK (%)X X X VALVE COMMAND ≠ FEEDBACK X BACnet MSTP NETWORK POINT RE-HEAT COIL COMMAND (%)X X X 5°F DT ACROSS COIL WITH ELEC. REHEAT COMMANDED OFF X FAIL LAST RE-HEAT COIL LEAVING AIR TEMPERATURE X X X SINGLE POINT SENSOR EXHAUST VAV BOX AIR FLOW FEEDBACK (CFM)X X X 10% FLOW DEVIATION FROM SETPOINT X BACnet MSTP NETWORK POINT EXHAUST VAV BOX AIR FLOW SETPOINT (CFM)X X X BACnet MSTP NETWORK POINT EXHAUST VAV BOX POSITION FEEDBACK (%)X X X VALVE COMMAND ≠ FEEDBACK X BACnet MSTP NETWORK POINT ZONE TEMPERATURE SETPOINT, HEATING & COOLING X X ZONE TEMPERATURE SETPOINT TRIM (RNET)X X X RNET ZONE TEMPERATURE (RNET)X X X =+/-4°F FROM SETPOINT X FCU CLG. COIL. CONTROL VALVE POSITION COMMAND X X X NORMALLY CLOSED FCU FAN MOTOR SPEED X X X FCU STATUS X X FAILURE X VIA CURRENT SENSOR DISCHARGE AIR TEMP X X X SINGLE POINT SENSOR OCCUPANCY SENSOR X X X EMERGENCY VENTILATION OVERRIDE X X X ZONE RH (RNET)X X X X MONITOR AND ALARM ONLY ATOMIZER ROOM POINTS LIST (427B) HARDWIRE POINTS SOFTWARE POINTS SHOWN ON GRAPHIC NOTESBI BO AI AO AV BV SCH TREND ALARM BACS EMCS DESCRIPTION SUPPLY AIR VAV BOX AIR FLOW FEEDBACK (CFM)X X X 10% FLOW DEVIATION FROM SETPOINT X BACnet MSTP NETWORK POINT SUPPLY AIR VAV BOX AIR FLOW SETPOINT (CFM)X X X BACnet MSTP NETWORK POINT SUPPLY AIR VAV BOX POSITION FEEDBACK (%)X X X VALVE COMMAND ≠ FEEDBACK X BACnet MSTP NETWORK POINT RE-HEAT COIL COMMAND (%)X X X 5°F DT ACROSS COIL WITH ELEC. REHEAT COMMANDED OFF X FAIL LAST RE-HEAT COIL LEAVING AIR TEMPERATURE X X X SINGLE POINT SENSOR EXHAUST AIR VAV BOX AIR FLOW FEEDBACK (CFM)X X X 10% FLOW DEVIATION FROM SETPOINT X BACnet MSTP NETWORK POINT EXHAUST AIR VAV BOX AIR FLOW SETPOINT (CFM)X X X BACnet MSTP NETWORK POINT EXHAUST AIR VAV BOX POSITION FEEDBACK (%)X X X VALVE COMMAND ≠ FEEDBACK X BACnet MSTP NETWORK POINT ZONE TEMPERATURE SETPOINT, HEATING & COOLING X X ZONE TEMPERATURE SETPOINT TRIM (RNET)X X X RNET ZONE TEMPERATURE (RNET)X X X =+/-4°F FROM SETPOINT X FCU CLG. COIL. CONTROL VALVE POSITION COMMAND X X X NORMALLY CLOSED FCU FAN MOTOR SPEED X X X FCU STATUS X X FAILURE X VIA CURRENT SENSOR FCU DISCHARGE AIR TEMP X X X SINGLE POINT SENSOR FCU CLG. COIL. CONTROL VALVE POSITION COMMAND X X X NORMALLY CLOSED FCU FAN MOTOR SPEED X X X FCU STATUS X X FAILURE X VIA CURRENT SENSOR FCU DISCHARGE AIR TEMP X X X SINGLE POINT SENSOR OCCUPANCY SENSOR X X X EXISTING FAN COIL HOT WATER VALVE X X X SPLIT RANGE W/ NEW FCU EXISTING FAN COIL CHILLED WATER VALVE X X X SPLIT RANGE W/ NEW FCU EMERGENCY VENTILATION OVERRIDE X X X ZONE RH (RNET)X X X X MONITOR AND ALARM ONLY LASER ROOM 472A ROOM SEQUENCE OF OPERATION SYSTEM DESCRIPTION: 1. SUPPLY AIR VAV TERMINAL UNIT (SVAV-1 & SVAV-2) 2. EXHAUST AIR TERMINAL UNIT (EVAV-1 & EVAV-2) 3. DUCT MOUNTED REHEAT COIL (RH-2 & RH-3) 4. NEW FAN COIL UNITS (FCU-1, FCU-2, & FCU-3) 5. EXISTING FAN COIL UNIT (FCU-EX-2) GENERAL: 1. SYSTEM SHALL BE CONTROLLED THROUGH THE BUILDING AUTOMATION AND CONTROL SYSTEM (BACS). 2. ALL SETPOINT SHALL BE ADJUSTABLE. 3. THE BACS SHALL BE CAPABLE OF STARTING AND STOPPING THE SYSTEM FOR SEVEN DIFFERENT DAILY SCHEDULES PER WEEK. 4. THE BACS SHALL BE CAPABLE OF RETAINING ITS PROGRAMMING AND TIME SETTING DURING A LOSS OF POWER FOR AT LEAST TEN HOURS. SETPOINTS: SPACE COOLING TEMPERATURE SETPOINTS: OCCUPIED: 75 ⁰F +/- 1.5 ⁰F OCCUPIED SETBACK: 75 ⁰F + 3 ⁰F UNOCCUPIED: 75 ⁰F +6 ⁰F SPACE HEATING TEMPERATURE SETPOINTS: OCCUPIED: 70 ⁰F +/- 1.5 ⁰F OCCUPIED SETBACK: 70 ⁰F - 3 ⁰F UNOCCUPIED: 70 ⁰F - 6 ⁰F SPACE HIGH LIMIT TEMPERATURE: 85 ⁰F SPACE LOW LIMIT TEMPERATURE: 60 ⁰F LASER ROOM 427A: OCCUPIED: SA = 165 CFM EA = 140 CFM UNOCCUPIED/OCCUPIED SETBACK: SA = 95 CFM EA = 70 CFM ATOMIZER ROOM 427B: OCCUPIED: SA = 370 CFM EA = 420 CFM UNOCCUPIED/OCCUPIED SETBACK: SA = 150 CFM EA = 200 CFM ZONE OCCUPANCY SCHEDULE: 6 AM TO 8 PM, MON-FRI ZONE OCCUPANCY SHALL BE DETERMINED BASED ON A COMBINATION OF A TIME OF DAY SCHEDULE AND A SPACE OCCUPANCY SENSOR. DURING THE SCHEDULED OCCUPANCY PERIOD, THE ZONE SHALL BE INITIALLY INDEXED TO OCCUPIED AND OPERATE FOR A MINIMUM OF 30 MINUTES, AT WHICH TIME THE SPACE VACANCY SENSOR SHALL INDEX THE SPACE BETWEEN OCCUPIED AND OCCUPIED SETBACK MODE. FOR ZONES WITH MULTIPLE VACANCY SENSORS, ZONE VACANCY SHALL BE BASED ON OCCUPANCY INPUTS FROM ANY OF THE SPACE VACANCY SENSORS ASSOCIATED WITH THAT ZONE. FOR SPACES WITH MULTIPLE TEMPERATURE SENSORS, THE AVERAGE OF THE TEMPERATURE READINGS SHALL APPLY WHEN THERE IS A CALL FOR HEATING OR COOLING. ZONE TEMPERATURE CONTROL: TEMPERATURE SETPOINTS SHALL BE DETERMINED BASED ON A COMBINATION OF PROGRAMMED SCHEDULE AND STATUS OF SPACE VACANCY SENSORS. EXISTING FAN COIL UNIT INTERFACE: THE CONTROLS FOR THE EXISTING FAN COIL UNIT IN ROOM 472B, SHALL BE INTEGRATED INTO THE BACS SYSTEM AND CONTROLLED BASED ON THE SEQUENCES DESCRIBED BELOW WHERE APPLICIABLE. HEATING MODE : LASER ROOM 472A: SHOULD THE SPACE TEMPERATURE FALL BELOW SETPOINT, THE REHEAT COIL HOT WATER CONTROL VALVE SHALL OPEN AND MODULATE TO MAINTAIN THE SPACE HEATING SETPONT. ATOMIZER ROOM 472B: SHOULD THE SPACE TEMPERATURE FALL BELOW SETPOINT, THE REHEAT COIL HOT WATER CONTROL VALVE SHALL OPEN FIRST AND MODULATE TO MAINTAIN THE SPACE HEATING SETPONT. WHEN THE REHEAT COIL CONTROL VALVE IS 100% OPEN AND THE SPACE HEATING SET POINT CAN NOT BE MAINTAINED, THE FAN COIL UNIT SHALL TURN ON AT LOW SPEED, THE FAN COIL UNIT HEATING CONTROL VALVE SHALL MODULATE TO MAINTAIN THE SPACE HEATING SET POINT. SCHEDULED OCCUPIED PERIOD - VACANCY SENSOR ACTIVE: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD, THE SPACE SHALL INDEX TO OCCUPIED MODE FOR THE DURATION OF OCCUPANCY. SPACE SHALL BE MAINTAINED AT THE OCCUPIED HEATING TEMPERATURE SETPOINT. SCHEDULED OCCUPIED PERIOD - VACANCY SENSOR INACTIVE: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD, THE SPACE SHALL INDEX TO OCCUPIED SETBACK MODE. SPACE SHALL BE MAINTAINED AT THE OCCUPIED SETBACK HEATING TEMPERATURE SETPOINT. SCHEDULED UNOCCUPIED PERIOD - VACANCY SENSOR ACTIVE: IF THE SPACE BECOMES OCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX TO OCCUPIED MODE FOR THE DURATION OF OCCUPANCY. SPACE SHALL BE MAINTAINED AT THE OCCUPIED HEATING TEMPERATURE SETPOINT. WHEN THE SPACE BECOMES UNOCCUPIED AGAIN DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX BACK TO UNOCCUPIED MODE. SCHEDULED UNOCCUPIED PERIOD - VACANCY SENSOR INACTIVE: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX TO UNOCCUPIED MODE. SPACE SHALL BE MAINTAINED AT THE UNOCCUPIED HEATING TEMPERATURE SETPOINT. SVAV-1 T RH-2ΔP ATOMIZER ROOM 472 B SVAV-2 T RH-3SUPPLY AIR FROM MAU SAT SUMMER = 55 F SAT WINTER = 68 F ΔP COOLING COILM ECM T AI AO FLP COOLING COILM AO FLP AO SUPPLY AIR FROM MAU SAT SUMMER = 55 F SAT WINTER = 68 F FCU-2 & FCU-3 FCU-1 AI AI EXHAUST ΔP EVAV-1 EXHAUST ΔP EVAV-2 AO T AV SETPOINT SA D COMBO SENSOR COMCOM COM BACnet FLOW SETPOINT (CFM) FLOW FEEDBACK (CFM) POSITION FEEDBACK (%) COM FLP BACnet FLOW SETPOINT (CFM) FLOW FEEDBACK (CFM) POSITION FEEDBACK (%) BACnet FLOW SETPOINT (CFM) FLOW FEEDBACK (CFM) POSITION FEEDBACK (%) BACnet FLOW SETPOINT (CFM) FLOW FEEDBACK (CFM) POSITION FEEDBACK (%) FLP T AI RH D AV T AV SETPOINT SA D COMBO SENSOR RH D AV HEATING COILM AO FLP EXISTING FCU-EX-2 T AI COOLING COILAO CHWS CHWR HWS HWR OS BI GENERAL LAB 472BVO BI PUSH-BUTTON EMERGENCY VENTILATION OVERRIDE CHWS CHWR CHWS CHWR COOLING MODE: ATOMIZER ROOM 472B: THE EXISTING FAN COIL UNIT SHALL TURN ON AT MED SPEED AND MODULATE THE CHILLED WATER CONTROL VALVE AS THE FIRST STAGE OF COOLING. IF THE SPACE TEMPERATURE CAN NOT BE SATISIFED BY THE EXISTING FAN COIL, THE REMAINING FAN COIL UNITS FCU-2 AND FCU-3 SHALL BE STAGED TO TURN ON AT MEDIUM SPEED. THE CHILLED WATER VALVE SHALL MODULATE TO MAINTAIN SPACE TEMPERATURE SETPOINT. AT NO TIME SHALL THE SPACE DROP BELOW THE MINIMUM AIR EXCHANGE RATES AS DESCRIBED BELOW. LASER ROOM 472A: SVAV-1 SHALL PROVIDE A CONSTANT FLOW WHEN THE SPACE IS OCCUPIED, THIS AIR FLOW WILL PROVIDE THE FIRST STAGE OF COOLING TO THE ROOM. IF THE COOLING SETPOINT CAN NOT BE MAINTAINED BY THE SUPPLY VAV UNIT, THEN THE SECOND STAGE OF COOLING SHALL BE PROVIDED BY ENERGIZING THE FAN IN FCU-1 AT MEDIUM SPEED AND MODULATING THE CHILLED WATER VALVE TO MAINTAIN SPACE SETPOINT. SCHEDULED OCCUPIED PERIOD - OCCUPANCY SENSOR ACTIVE: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD, THE SPACE SHALL INDEX TO OCCUPIED MODE FOR THE DURATION OF OCCUPANCY. SPACE SHALL BE MAINTAINED AT THE OCCUPIED COOLING TEMPERATURE SETPOINT. THE SPACE TEMPERATURE RISES ABOVE THE COOLING TEMPERATURE SETPOINT, THE GENERAL EXHAUST AIR VALVE AND THE EXISTING FAN COIL COOLING VALVE SHALL MODULATE OPEN, AS DESCRIBED BELOW, TO MAINTAIN THE OCCUPIED SPACE TEMPERATURE SETPOINT. AT NO TIME SHALL THE SPACE DROP BELOW THE MINIMUM OCCUPIED EXCHANGE RATE. SCHEDULED OCCUPIED PERIOD - OCCUPANCY SENSOR INACTIVE: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD, THE SPACE SHALL INDEX TO OCCUPIED SETBACK MODE. SPACE SHALL BE MAINTAINED AT THE OCCUPIED SETBACK COOLING TEMPERATURE SETPOINT. THE SPACE TEMPERATURE RISES ABOVE THE COOLING TEMPERATURE SETPOINT, THE GENERAL EXHAUST AIR VALVE AND THE EXISTING FAN COIL COOLING VALVE SHALL MODULATE OPEN, AS DESCRIBED BELOW, TO MAINTAIN THE UNOCCUPIED SPACE TEMPERATURE SETPOINT. AT NO TIME SHALL THE SPACE DROP BELOW THE MINIMUM UNOCCUPIED EXCHANGE RATE. SCHEDULED UNOCCUPIED PERIOD - VACANCY SENSOR ACTIVE: IF THE SPACE BECOMES OCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX TO OCCUPIED MODE FOR THE DURATION OF OCCUPANCY. SPACE SHALL BE MAINTAINED AT THE OCCUPIED COOLING TEMPERATURE SETPOINT. WHEN THE SPACE BECOMES UNOCCUPIED AGAIN DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX BACK TO UNOCCUPIED MODE. THE SPACE TEMPERATURE RISES ABOVE THE COOLING TEMPERATURE SETPOINT, THE GENERAL EXHAUST AIR VALVE AND THE EXISTING FAN COIL COOLING VALVE SHALL MODULATE OPEN, AS DESCRIBED BELOW, TO MAINTAIN THE OCCUPIED SPACE TEMPERATURE SETPOINT. AT NO TIME SHALL THE SPACE DROP BELOW THE MINIMUM OCCUPIED EXCHANGE RATE. SCHEDULED UNOCCUPIED PERIOD - VACANCY SENSOR INACTIVE: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX TO UNOCCUPIED MODE. SPACE SHALL BE MAINTAINED AT THE UNOCCUPIED COOLING TEMPERATURE SETPOINT. THE SPACE TEMPERATURE RISES ABOVE THE COOLING TEMPERATURE SETPOINT, THE GENERAL EXHAUST AIR VALVE AND THE EXISTING FAN COIL COOLING VALVE SHALL MODULATE OPEN, AS DESCRIBED BELOW, TO MAINTAIN THE UNOCCUPIED SPACE TEMPERATURE SETPOINT. AT NO TIME SHALL THE SPACE DROP BELOW THE MINIMUM UNOCCUPIED EXCHANGE RATE. SUPPLY AIR VAV CONTROL: THE SUPPLY AIR VAV SHALL BE CONSTANT VOLUME DURING THE OCCUPIED MODE AT THE SCHEDULED OCCUPIED FLOW RATE. THE VAV SHALL BE CONSTANT VOLUME DURING EITHER THE OCCUPIED SETBACK OR UNOCCUPIED MODES AT THE SCHEDULED UNOCCUPIED FLOW RATE. EXHAUST AIR VAV BOX CONTROL: THE EXHAUST AIR VAV SHALL MODULATE AS NEEDED TO MAINTAIN THE SUPPLY AIRFLOW RATE PLUS THE SPECIFIC AIRFLOW DIFFERENTIAL, WHICH SHALL BE DETERMINED DURING AIR BALANCING IN ORDER TO MEET THE ROOM AIRFLOW BALANCE AS INDICATED ABOVE. EMERGENCY VENTILATION OVERRIDE: LOCATE GLASS BREAK PUSH BUTTON IN CORRIDOR OUTSIDE OF LAB 472. REFER TO ELECTRICAL DRAWINGS FOR LOCATION AND DEVICE TYPE. UPON ACTIVATION, SUPPLY TERMINAL UNITS SVAV-1 & SVAV-2 AND EXHAUST TERMINAL UNITS EVAV-1 & EVAV-2 SHALL GO TO THE FULL CLOSE POSITION. OS BI GENERAL LAB 472AVO BI PUSH-BUTTON EMERGENCY VENTILATION OVERRIDE AOBI STATUS SPEED ECM AOBISTATUS SPEED ECM AOBI RNET RNET FLP These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:54 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 CS CONTROLS SCHEMATIC ROOM 472A & B AT CWC MI-601 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 LABORATORY AIR FLOW SCHEDULE DESCRIPTION ROOM DIMENSIONS CODE MINIMUM VENTILATION EXHAUST AIR SUPPLY AIR XFER AREA HEIGHT VOLUME NYS OUTDOOR AIR NYS EXHAUST AIR EXHAUST POINT VALVE SIZE VALVE RANGE OCCUPIED SASH OPEN OCCUPIED SASH CLOSED UNOCCUPIED SASH FULL (100 FPM) UNOCCUPIED SASH OPEN (65 FPM) UNOCCUPIED SASH CLOSED SUPPLY POINT VALVE SIZE VALVE RANGE OCCUPIED SASH OPEN OCCUPIED SASH CLOSED UNOCCUPIED SASH FULL UNOCCUPIED SASH OPEN UNOCCUPIED SASH CLOSED ALL MODES MIN MAX 100 FPM 80 FPM MIN MAX 100 FPM 80 FPM (FT2)(FT)(FT3)(CFM) (ACH) (CFM) (ACH)(CFM) (CFM) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) GENERAL LAB 375 11 4,125 210 3.1 375 5.5 EAV-1 (5' FH) 10 120 1,056 630 20.5 505 16.4 120 6.0 630 20.5 410 13.3 120 3.9 SAV-1 12 180 1461 1310 1030 310 1310 815 180 -100 EAV-2 (6' FH) 10 120 1,056 780 625 120 780 505 120 EAV-3 (GEX) 6 30 254 0 0 170 0 0 30 TOTAL 1410 1130 410 1410 915 270 LABORATORY AIR FLOW SCHEDULE DESCRIPTION ROOM DIMENSIONS CODE MINIMUM VENTILATION EXHAUST AIR SUPPLY AIR XFER AREA HEIGHT VOLUME NYS OUTDOOR AIR NYS EXHAUST AIR EXHAUST POINT VALVE SIZE VALVE RANGE OCCUPIED SASH OPEN OCCUPIED SASH CLOSED UNOCCUPIED SASH FULL (100 FPM) UNOCCUPIED SASH OPEN (65 FPM) UNOCCUPIED SASH CLOSED SUPPLY POINT VALVE SIZE VALVE RANGE OCCUPIED SASH OPEN OCCUPIED SASH CLOSED UNOCCUPIED SASH FULL UNOCCUPIED SASH OPEN UNOCCUPIED SASH CLOSED ALL MODES MIN MAX 100 FPM 80 FPM MIN MAX 100 FPM 80 FPM (FT2)(FT)(FT3)(CFM) (ACH) (CFM) (ACH)(CFM) (CFM) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) GENERAL LAB 375 11 4,125 210 3.1 375 5.5 EAV-1 (5' FH) 10 120 1,056 630 20.5 505 16.4 120 6.0 630 20.5 410 13.3 120 3.9 SAV-1 12 180 1461 1310 1030 310 1310 815 180 -100 EAV-2 (6' FH) 10 120 1,056 780 625 120 780 505 120 EAV-3 (GEX) 6 30 254 0 0 170 0 0 30 TOTAL 1410 1130 410 1410 915 270 EXHAUST SAV-1 T RH-1SUPPLY AIR FROM MAU SAT SUMMER = 55 F SAT WINTER = 68 F 5' FUME HOOD SYSTEM DESCRIPTION: TWO FUME HOODS EACH WITH AN EXHAUST AIR VALVE (EAV-1 & EAV-2) SUPPLY AIR VALVE (SAV-1) GENERAL EXHAUST AIR VALVE (EAV-3) DUCT MOUNTED RE-HEAT COIL (RH-1) EXISTING FAN COIL UNIT (FCU-EX-1) GENERAL: 1. SYSTEM SHALL BE CONTROLLED THROUGH THE BUILDING AUTOMATION AND CONTROL SYSTEM (BACS). 2. ALL SETPOINTS AND FLOW OFFSETS SHALL BE ADJUSTABLE. 3. THE SPACE SHALL BE CONTROLLED TO AN AIR CHANGE RATE TO COMPLY WITH CODE VENTILATION REQUIREMENTS, AND UNIVERSITY STANDARDS. 4. LABORATORY AIR CHANGE RATES ARE BASED ON TOTAL EXHAUST AIR FLOW FROM THE SPACE. 5. THE BAS SHALL BE CAPABLE OF STARTING AND STOPPING THE SYSTEM FOR SEVEN DIFFERENT DAILY SCHEDULES PER WEEK. 6. THE BACS SHALL BE CAPABLE OF RETAINING ITS PROGRAMMING AND TIME SETTING DURING A LOSS OF POWER FOR AT LEAST TEN HOURS. 7. REFER TO LABRATORY AIR FLOW SCHEDULE ON THIS DRAWING FOR SCHEDULED AIR FLOW AND OFFSET VALUES. 8. ZONE OCCUPANCY (OCCUPIED MODE) SCHEDULE: 6 AM TO 8 PM, MON - FRI. 9. DOWNSTREAM STATIC PRESSURE SETPOINT: DETERMINE DURING TESTING AND BALANCING EFFORTS. SETPOINTS: SPACE COOLING TEMPERATURE SETPOINTS: OCCUPIED: 75 °F +/- 1.5 °F OCCUPIED SETBACK: 75 °F +/- 3 °F UNOCCUPIED: 75 °F +/- 6 °F SPACE DEWPOINT SETPOINT 52°F +/-2°F SPACE HEATING TEMPERATURE SETPOINTS: OCCUPIED: 70 °F +/- 1.5 °F OCCUPIED SETBACK: 70 °F +/- 3 °F UNOCCUPIED: 70 °F +/- 6 °F TOTAL EXHAUST AIR CHANGE RATE (ACPH): TYPICALLY = 6 ACPH OCCUPIED / 3 ACPH UNOCCUPIED ACPH = TOTAL EXHAUST CFM x 60 / ROOM VOLUME TOTAL EXHAUST (EX) FLOW RATE (CFM): REFER TO LABRATORY AIRFLOW SCHEDULE SUPPLY AIRFLOW (SA) RATE (CFM): REFER TO LABRATORY AIRFLOW SCHEDULE TYPICALL SA FLOW = TOTAL EA FLOW RATE + OFFSET FUME HOOD EXHAUST (FHE) AIRFLOW RATE: NOT CONTROLLED BY BACS. VALVE IS CONTROLLED BY FUME HOOD MONITOR TO MAINTAIN FACE VELOCITY SETPOINT GENERAL EXHAUST (GEX) AIRFLOW RATE (CFM): REFER TO LABRATORY AIRFLOW SCHEDULE TYPICAL GEX FLOW = TOAL LABRATORY EXHAUST CFM - FUME HOOD EXHAUST CFM SPACE AIR DIFFERENTIAL OFFSET (CFM): REFER TO LABRATORY AIRFLOW SCHEDULE TYPICALLY = -100 CFM FOR NEGATIVE PRESSURE LABS TYPICALLY = +100 CFM FOR POSITIVE PRESSURE LABS FUME HOOD VELOCITY: NOT CONTROLLED BY BACS. FACE VELOCITY SETPOINTS ARE PROGRAMMED INTO FUME HOOD MONITOR. TYPICALLY 100 FPM OCC. / 65 FPM UNOCC. MINIMUM LABORATORY OCCUPANCY INDEX TIME: 30 MINUTES ZONE OCCUPANCY SCHEDULE: 6AM TO 8PM, MONDAY-FRIDAY FACE VELOCITY CONTROL: EACH FUME HOOD SHALL BE EQUIPPED WITH A FUME HOOD MONITOR AND SASH POSITION INDICATOR. THE MONITOR SHALL ADJUST THE FUME HOOD EXHAUST VALVE TO MAINTAIN THE FACE VELOCITY SETPOINT. THE MONITOR SHALL, AS A MINIMUM, HAVE THE FOLLOWING CAPABILITIES: - SASH POSITION INPUT. - STANDBY MODE INPUT TO ALLOW ADJUSTMENTS OF FACE VELOCITY. - HOOD DECOMMISSION MODE. ZONE TEMPERATURE CONTROL: TEMPERATURE SETPOINTS SHALL BE DETERMINED BASED ON A COMBINATION OF PROGRAMMED SCHEDULE AND STATUS OF SPACE VACANCY SENSORS. EXISTING FAN COIL UNIT INTERFACE: THE CONTROLS FOR THE EXISTING FAN COIL UNIT SHALL BE INTEGRATED INTO THE BACS SYSTEM AND CONTROLLED BASED ON THE SEQUENCES DESCRIBED BELOW. HEATING MODE: SHOULD THE SPACE TEMPERATURE FALL BELOW SETPOINT, THE REHEAT COIL HOT WATER CONTROL VALVE SHALL OPEN FIRST AND MODULATE TO MAINTAIN THE SPACE HEATING SETPONT. WHEN THE REHEAT COIL CONTROL VALVE IS 100% OPEN AND THE SPACE HEATING SET POINT CAN NOT BE MAINTAINED, THE FAN COIL UNIT SHALL TURN ON AT LOW SPEED, THE FAN COIL UNIT HEATING CONTROL VALVE SHALL MODULATE TO MAINTAIN THE SPACE HEATING SET POINT. SCHEDULED OCCUPIED PERIOD - OCCUPANCY SENSOR ACTIVE: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD, THE SPACE SHALL INDEX TO OCCUPIED MODE FOR THE DURATION OF OCCUPANCY. SPACE SHALL BE MAINTAINED AT THE OCCUPIED HEATING TEMPERATURE SETPOINT. SCHEDULED OCCUPIED PERIOD - OCCUPANCY SENSOR INACTIVE: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD, THE SPACE SHALL INDEX TO OCCUPIED SETBACK MODE. SPACE SHALL BE MAINTAINED AT THE OCCUPIED SETBACK HEATING TEMPERATURE SETPOINT. SCHEDULED UNOCCUPIED PERIOD - VACANCY SENSOR ACTIVE: IF THE SPACE BECOMES OCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX TO OCCUPIED MODE FOR THE DURATION OF OCCUPANCY. SPACE SHALL BE MAINTAINED AT THE OCCUPIED HEATING TEMPERATURE SETPOINT. WHEN THE SPACE BECOMES UNOCCUPIED AGAIN DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX BACK TO UNOCCUPIED MODE. SCHEDULED UNOCCUPIED PERIOD - OCCUPANCY SENSOR INACTIVE: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX TO UNOCCUPIED MODE. SPACE SHALL BE MAINTAINED AT THE UNOCCUPIED HEATING TEMPERATURE SETPOINT. COOLING MODE: SHOULD THE SPACE TEMPERATURE RISE ABOVE SETPOINT,THE EXISTING FAN COIL UNIT SHALL TURN ON AT LOW SPEED, MODULATE THE CHILLED WATER CONTROL VALVE AS THE FIRST STAGE OF COOLING. IF THE VALVE REACHES FULL OPEN AND THE SPACE TEMPERATURE CAN NOT BE SATISIFED, THE FAN COIL UNIT SHALL INCREASE THE AIR FLOW AS THE SECOND STAGE OF COOLING TO MAINTAIN THE SPACE SETPOINT. THE GENERAL EXHAUST AIR VALVE SHALL MODULATE WHILE THE SUPPLY AIR VALVE TRACKS THE GENERAL AIR VALVE TO MAINTAIN THE TOTAL EXHAUST AIR FLOW RATE PLUS THE INDICATED DIFFERENTIAL. AT NO TIME SHALL THE SPACE DROP BELOW THE MINIMUM AIR EXCHANGE RATES AS DESCRIBED BELOW. SCHEDULED OCCUPIED PERIOD - OCCUPANCY SENSOR ACTIVE: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD, THE SPACE SHALL INDEX TO OCCUPIED MODE FOR THE DURATION OF OCCUPANCY. SPACE SHALL BE MAINTAINED AT THE OCCUPIED COOLING TEMPERATURE SETPOINT. THE SPACE TEMPERATURE RISES ABOVE THE COOLING TEMPERATURE SETPOINT, THE GENERAL EXHAUST AIR VALVE AND THE EXISTING FAN COIL COOLING VALVE SHALL MODULATE OPEN, AS DESCRIBED BELOW, TO MAINTAIN THE OCCUPIED SPACE TEMPERATURE SETPOINT. AT NO TIME SHALL THE SPACE DROP BELOW THE MINIMUM OCCUPIED EXCHANGE RATE. SCHEDULED OCCUPIED PERIOD - OCCUPANCY SENSOR INACTIVE: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED OCCUPIED PERIOD, THE SPACE SHALL INDEX TO OCCUPIED SETBACK MODE. SPACE SHALL BE MAINTAINED AT THE OCCUPIED SETBACK COOLING TEMPERATURE SETPOINT. THE SPACE TEMPERATURE RISES ABOVE THE COOLING TEMPERATURE SETPOINT, THE GENERAL EXHAUST AIR VALVE AND THE EXISTING FAN COIL COOLING VALVE SHALL MODULATE OPEN, AS DESCRIBED BELOW, TO MAINTAIN THE UNOCCUPIED SPACE TEMPERATURE SETPOINT. AT NO TIME SHALL THE SPACE DROP BELOW THE MINIMUM UNOCCUPIED EXCHANGE RATE. SCHEDULED UNOCCUPIED PERIOD - VACANCY SENSOR ACTIVE: IF THE SPACE BECOMES OCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX TO OCCUPIED MODE FOR THE DURATION OF OCCUPANCY. SPACE SHALL BE MAINTAINED AT THE OCCUPIED COOLING TEMPERATURE SETPOINT. WHEN THE SPACE BECOMES UNOCCUPIED AGAIN DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX BACK TO UNOCCUPIED MODE. THE SPACE TEMPERATURE RISES ABOVE THE COOLING TEMPERATURE SETPOINT, THE GENERAL EXHAUST AIR VALVE AND THE EXISTING FAN COIL COOLING VALVE SHALL MODULATE OPEN, AS DESCRIBED BELOW, TO MAINTAIN THE OCCUPIED SPACE TEMPERATURE SETPOINT. AT NO TIME SHALL THE SPACE DROP BELOW THE MINIMUM OCCUPIED EXCHANGE RATE. SCHEDULED UNOCCUPIED PERIOD - VACANCY SENSOR INACTIVE: IF THE SPACE IS UNOCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SPACE SHALL INDEX TO UNOCCUPIED MODE. SPACE SHALL BE MAINTAINED AT THE UNOCCUPIED COOLING TEMPERATURE SETPOINT. THE SPACE TEMPERATURE RISES ABOVE THE COOLING TEMPERATURE SETPOINT, THE GENERAL EXHAUST AIR VALVE AND THE EXISTING FAN COIL COOLING VALVE SHALL MODULATE OPEN, AS DESCRIBED BELOW, TO MAINTAIN THE UNOCCUPIED SPACE TEMPERATURE SETPOINT. AT NO TIME SHALL THE SPACE DROP BELOW THE MINIMUM UNOCCUPIED EXCHANGE RATE. EMERGENCY VENTILATION OVERRIDE: LOCATE GLASS BREAK PUSH BUTTON IN CORRIDOR OUTSIDE OF LAB 472. REFER TO ELECTRICAL DRAWINGS FOR LOCATION AND DEVICE TYPE. UPON ACTIVATION, THE SUPPLY AIR VALVE SAV-1 AND THE TOW EXHAUST VALVES EAV-1 & EAV-2 SHALL GO TO THE CLOSED POSITION. ΔP EAV-3 EXHAUST ΔP EAV-1 6' FUME HOOD EXHAUST ΔP EAV-2 SASH POSITION HORIZONTAL SENSOR FUME HOOD MONITOR FUME HOOD MONITOR ΔP OS BI GENERAL LAB 472VO BI PUSH-BUTTON EMERGENCY VENTILATION OVERRIDE AIAO F.L. N.C. ANALOG ELECTRICL CONTROL AI FLOW AI ALARM MOD AO SETPOINT ANALOG ELECTRICL CONTROL AI FLOW AI ALARM MOD AO SETPOINT AI FLOW AI ALARM R BO OCCUPIED/ UNOCCUPIED COMMAND T AV SETPOINT SA D COMBO SENSOR (RNET) RH D AV HEATING COILM AO EXISTING FCU-EX-1 T AI COOLING COILAO CHWS CHWR HWS HWR LABRATORY AIRFLOW CONTROL: AIR VALVE POSITIONS SHALL BE BASED ON OCCUPANCY MODE. UNDER NORMAL CONDITIONS, ROOM OCCUPANCY SHALL BE DETERMINED VIA THE ROOM VACANCY SENSORS. IF THE LABRATORY IS VACANT, THE ROOM SHALL BE PLACED IN VACANT MODE BY THE BACS. WHEN THE ROOM IS OCCUPIED, THE BACS SHALL SEND AN OCCUPIED COMMAND TO THE FUME HOOD MONITOR. THE FUME HOOD MONITOR SHALL INDEX THE FUME HOOD EXHAUST AIR VALVE AS NEEDED TO MAINTAIN THE OCCUPIED FACE VELOCITY SETPOINT BASED ON MEASURED AIR VELOCITY. THE GENERAL EXHAUST AIR VALVE SHALL MODULATE AS NEEDED TO MAINTAIN THE OCCUPIED AIR CHANGE RATE. THE SUPPLY AIR VALVES SHALL MODULATE AS NEEDED TO MAINTAIN THE SPECIFIED AIRFLOW DIFFERENTIAL FOR ROOM PRESSURIZATION. WHEN THE ROOM IS UNOCCUPIED, AND THE FUME HOOD SASHS ARE AT OR BELOW 18-INCHES, THE BACS SHALL SEND AN UNOCCUPIED COMMAND TO THE FUME HOOD MONITOR. THE FUME HOOD MONITOR SHALL INDEX THE FUME HOOD EXHAUST AIR VALVE AS NEEDED TO MAINTAIN THE UNOCCUPIED FACE VELOCITY SETPOINT BASED ON MEASURED AIR VELOCITY. THE GENERAL EXHAUST AIR VALVES SHALL MODULATE AS NEEDED TO MAINTAIN THE UNOCCUPIED AIR CHANGE RATE. THE SUPPLY AIR VALVES SHALL MODULATE AS NEEDED TO MAINTAIN THE SPECIFIED AIRFLOW DIFFERENTIAL FOR ROOM PRESSURIZATION. WHEN THE ROOM IS UNOCCUPIED, AND ANY OF THE FUME HOOD SASHES ARE ABOVE 18-INCHES, THE BACS SHALL NOT SEND AN UNOCCUPIED COMMAND TO THOSE PARTICULAR FUME HOOD EXHAUST AIR VALVES. THE FUME HOOD MONITOR SHALL INDEX THE FUME HOOD EXHAUST AIR VALVE WHOSE SASHES ARE ABOVE 18 INCHES TO MAINTAIN THE OCCUPIED SASH OPEN AIRFLOW SETPOINT. THE BACS WILL SEND THE UNOCCUPIED COMMAND TO THOSE FUME HOODS WHOSE SASHES ARE AT OR BELOW 18 INCHES. THE FUME HOOD MONITORS SHALL INDEX THE FUME HOOD EXHAUST AIR VALVES WHOSE SASHES ARE AT 18 INCHES AND BELOW TO MAINTAIN THE UNOCCUPIED FACE VELOCITY SETPOINT BASED ON MEASURED AIR VELOCITY. THE GENERAL EXHAUST AIR VALVES SHALL MODULATE AS NEEDED TO MAINTAIN THE UNOCCUPIED AIR CHANGE RATE. THE SUPPLY AIR VALVE SHALL MODULATE AS NEEDED TO MAINTAIN THE SPECIFIED AIRFLOW DIFFERENTIAL FOR ROOM PRESSURIZATION. ECM AOBI FLP FLP FLP R BO DECOMMISSION FHV ANALOG ELECTRICAL CONTROL WITH HOOD INTERFACE CARD AI SASH POSITION AI FLOW AI ALARM R BO OCCUPIED/ UNOCCUPIED COMMAND R BO DECOMMISSION FHV ANALOG ELECTRICAL CONTROL WITH HOOD INTERFACE CARD AI SASH POSITION RNET AO BIBIAOAO AO AO AO BI BI AI AI AI SASH POSITION HORIZONTAL SENSOR FACTORY SUPPLIED CABLE VERTICAL SASH POSITION SENSOR AO AO AI AO AO VERTICAL SASH POSITION SENSOR FACTORY SUPPLIED CABLE These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:55 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 CS CONTROLS SCHEMATIC ROOM 472 AT CWC MI-602 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 GENERAL LAB POINTS LIST (472) HIGH HOOD DENSITY TRACKING LABORATORY HARDWIRE POINTS SOFTWARE POINTS SHOWN ON GRAPHIC NOTESBI BO AI AO AV BV SCH TREND ALARM BACS EMCS DESCRIPTION TOTAL EXHAUST AIRFLOW (CFM)X X X TOTAL EXHAUST AIR SETPOINT (CFM)X X X LABORATORY AIR CHANGE RATE (ACPH)X X ROOM AREA (SQUARE FEET)X X ROOM CEILING HEIGHT (FEET)X X FLOW OFFSET SETPOINT (CFM)X X FLOW OFFSET ACTUAL (CFM)X X SPACE TEMPERATURE SETPOINT, HEATING X X SPACE TEMPERATURE SETPOINT, COOLING X X SPACE TEMPERATURE (RNET)X X X =+/-4°F FROM SETPOINT X SPACE SETPOINT ADJUSTMENT (RNET)X X SPACE OCCUPANCY, MINIMUM OCCUPANCY SETPOINT X X SPACE OCCUPANCY X X X EMERGENCY VENTILATION OVERRIDE X X X ALARM ON OVERRIDE CONDITION X EAV-1 (5' FUME HOOD) FUME HOOD EXHAUST VALVE FLOW FEEDBACK (CFM)X X X FUME HOOD EXHAUST AIR VALVE STATUS X X VALVE COMMAND ≠ FEEDBACK (JAM)X DUA-STATE ALARM X LOW DIFFERENTIAL PRESSURE (VIA SWITCH)X SPACE OCCUPANCY, MINIMUM OCCUPANCY SETPOINT X X SPACE OCCUPANCY X X X DECOMMISSIONING COMMAND X X X FUME HOOD SASH POSITION - COMBINATION (HORIZONTAL/VERTICAL)X X X SASH OPEN (18") FOR 24 CONTINUOUS HOURS OR MORE X EAV-2 (6' FUME HOOD) FUME HOOD EXHAUST VALVE FLOW FEEDBACK (CFM)X X X FUME HOOD EXHAUST AIR VALVE STATUS X X VALVE COMMAND ≠ FEEDBACK (JAM)X DUA-STATE ALARM X LOW DIFFERENTIAL PRESSURE (VIA SWITCH)X SPACE OCCUPANCY, MINIMUM OCCUPANCY SETPOINT X X SPACE OCCUPANCY X X X DECOMMISSIONING COMMAND X X X FUME HOOD SASH POSITION - COMBINATION (HORIZONTAL/VERTICAL)X X X SASH OPEN (18") FOR 24 CONTINUOUS HOURS OR MORE X SAV-1 SUPPLY AIR VALVE FLOW FEEDBACK (CFM) X X X SUPPLY AIR VALVE STATUS X X 10% FLOW DEVIATION FROM SETPOINT X TRI-STATE ALARMXVALVE COMMAND ≠ FEEDBACK (JAM)X X LOW DIFFERENTIAL PRESSURE (VIA SWITCH)X SUPPLY AIR VALVE POSITION COMMAND (CFM) X X X SUPPLY AIR VALVE MINIMUM AIRFLOW SETPOINT (CFM)X X SUPPLY AIR VALVE MAXIMUM AIRFLOW SETPOINT (CFM)X X EAV-3 GENERAL EXHAUST AIR VALVE POSITION COMMAND (CFM)X X X GENERAL EXHAUST AIR VALVE MINIMUM AIRFLOW SETPOINT (CFM)X X GENERAL EXHAUST AIR VALVE MAXIMUM AIRFLOW SETPOINT (CFM)X X GENERAL EXHAUST AIR VALVE FLOW FEEDBACK (CFM)X X X GENERAL EXHAUST AIR VALVE STATUS X X 10% FLOW DEVIATION FROM SETPOINT X TRI-STATE ALARMXVALVE COMMAND = FEEDBACK (JAM)X X LOW DIFFERENTIAL PRESSURE (VIA SWITCH)X RH-1 RE-HEAT COIL LEAVING AIR TEMPERATURE X X X SINGLE POINT SENSOR RE-HEAT COIL LEAVING AIR TEMPERATURE HIGH LIMIT X X X SINGLE POINT SENSOR SPACE TEMPERATURE SETPOINT X X X HEATING COIL VALVE POSITION X X X 5°F ΔT ACROSS COIL WITH VALVE COMMANDED CLOSED X FAIL FAST EXISTING FAN COIL UNIT HOT WATER COIL VALVE POSITION X X X CHILLED WATER COIL VALVE POSITION X X X FAN COIL LEAVING AIR TEMPERATURE X X X SINGLE POINT SENSOR FAN SPEED COMMAND X X X FAN STATUS FEEDBACK X X X These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:56 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 CS CONTROLS POINTS LIST ROOM 472 AT CWC MI-603 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 AMPERE ABANDON ALTERNATING CURRENT ABOVE FINISHED FLOOR ABOVE FINISHED GRADE AMPERES INTERRUPTING CURRENT AUTOMATIC TRANSFER SWITCH AMERICAN WIRE GAUGE BELOW FINISHED FLOOR BELOW FINISHED GRADE BASIC IMPULSE LEVEL BUILDING CONDUIT CIRCUIT BREAKER CLOSED CIRCUIT TELEVISION CIRCUIT CEILING CONCRETE CONNECTION CONTROL PANEL CURRENT TRANSFORMER COPPER DIRECT CURRENT DETAIL DIAMETER DISCONNECT DOWN DRAWING ELECTRIC, ELECTRICAL ELECTRICAL CONTRACTOR ELEVATION EMERGENCY EQUIPMENT EXISTING TO REMAIN EXISTING EXHAUST EXTERNAL FIRE ALARM FIRE ALARM ANNUNCIATOR PANEL FIRE ALARM CONTROL PANEL FURNISHED BY OTHERS FAN COIL UNIT FULL LOAD AMPERES FLEXIBLE FLOOR FINISHED FEET FUSE GAUGE GALVANIZED GENERAL CONTRACTOR GENERATOR GROUND FAULT INTERRUPTER GRADE GROUND HORSEPOWER HERTZ INTERRUPTING JUNCTION BOX KILO AMPERE THOUSAND CIRCULAR MILS KILOVOLT KILOVOLT AMPERES KILOVOLT AMPERES REACTIVE KILOWATT KILOWATT HOUR ABBREVIATIONS LA L-N LED MAX MCB MCC MDP MH MIN MLO MOV MOD MVA NC NE NEC NEMA NIC NO NTS OC OL OH P PC PF PFFB PH, Ø PNL PT PVC REQ'D RGS RLA RES RMC RMS RPM RX SA SEC SMR SYM T TEMP TC TRANS TYP UG UH UNO V VAC VM VP W WG W/ W/O WP WT XFMR A, AMP ABN AC AFF AFG AIC ATS AWG BFF BFG BIL BLDG C CB CCTV CKT CLG CONC CONN CP CT CU DC DET DIA, Ø DISC DN DWG E, (E) EC ELEV EM, EMER EQUIP ETR EX, EXIST EXH EXT FA FAAP FACP FBO FCU FLA FLEX FLR FIN FT FU GA GALV GC GEN GFI GR GRD HP HZ INT JB KA KCMIL KV KVA KVAR KW KWH LIGHTNING ARRESTOR LINE TO NEUTRAL LIGHT EMITTING DIODE MAXIMUM MAIN CIRCUIT BREAKER MOTOR CONTROL CENTER MAIN DISTRIBUTION PANEL MANHOLE MINIMUM MAIN LUG ONLY METAL OXIDE VARISTOR MOTOR OPERATED DAMPER MEGAVOLT AMPERES NORMALLY CLOSED NORMAL EMERGENCY NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION NOT IN CONTRACT NORMALLY OPEN NOT TO SCALE ON CENTER OVERLOAD OVERHEAD POLE PHOTOCELL POWER FACTOR PROVISIONS FOR FUTURE BREAKER PHASE PANEL POTENTIAL TRANSFORMER POLYVINYLCHLORIDE REQUIRED RIGID GALVANIZED STEEL RUNNING LOAD AMPS RESISTOR RIGID METAL CONDUIT ROOT MEAN SQUARE REVOLUTIONS PER MINUTE REMOVE EXISTING SURGE ARRESTOR SECONDARY SURFACE METAL RACEWAY SYMMETRICAL TRANSFORMER TEMPERATURE TRIP COIL TRANSFORMER TYPICAL UNDERGROUND UNIT HEATER UNLESS NOTED OTHERWISE VOLTS VOLTS ALTERNATING CURRENT VOLT METER VAPOR PROOF WATTS WIRE GUARD WITH WITHOUT WEATHERPROOF WEIGHT TRANSFORMER DRAWING NOTE -REFER TO DRAWING NOTE LIST ON SHEET (NEW WORK) DRAWING CONVENTIONS DRAWING NOTE -REFER TO DRAWING NOTE LIST ON SHEET (DEMOLITION)# # FEEDER TAG -REFER TO FEEDER SCHEDULE ON DRAWING Ex.xxX 1. CONTRACTORS ARE URGED TO INSPECT THE SITE BEFORE SUBMITTING A BID PROPOSAL TO ENSURE KNOWLEDGE OF PROJECT REQUIREMENTS AND SITE CONDITIONS. IF NO CLARIFICATION IS REQUESTED, IT WILL BE CONSIDERED THAT THE CONTRACTORS ARE IN FULL UNDERSTANDING OF PROJECT REQUIREMENTS. 2. PROVIDE LABOR, SUPERVISION, EQUIPMENT, MATERIALS, CONSTRUCTION TOOLS, TRANSPORTATION, INSURANCE, AND SERVICES REQUIRED FOR THE COMPLETE INSTALLATION OF THIS WORK IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE, AND LOCAL CODES, AUTHORITIES HAVING JURISDICTION, AND STANDARDS INCLUDING BUT NOT LIMITED TO, ASHRAE, IBC, NEC, AND NFPA. 3. NOTHING CONTAINED IN THE SPECIFICATIONS OR SHOWN ON THE DRAWINGS SHALL BE CONSTRUED TO BE IN CONFLICT WITH ANY STATE OR LOCAL CODES, ORDINANCES OR REGULATIONS. 4. THE USE OF THE WORD "PROVIDE" SHALL MEAN TO FURNISH, INSTALL AND CONNECT, READY TO USE. 5. THE USE OF THE WORD "FURNISH" SHALL MEAN TO PROCURE AND DELIVER TO THE SITE. 6. THE USE OF THE WORD "INSTALL" SHALL MEAN TO PHYSICALLY PLACE INTO SERVICE AND CONNECT, READY TO USE. 7. EQUIPMENT AND MATERIALS SHALL BE INSTALLED BY SKILLED TRADESMEN, FAMILIAR WITH THE COMPONENTS TO BE INSTALLED, AND IN ACCORDANCE WITH BEST PRACTICES OF THE INDUSTRY. 8. BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, FITTINGS, AND ACCESSORIES THAT MAY BE REQUIRED. THIS CONTRACTOR SHALL CAREFULLY EXAMINE THE ARCHITECTURAL; STRUCTURAL; HEATING, VENTILATING AND AIR- CONDITIONING; ELECTRICAL; PLUMBING; AND OTHER PROJECT DOCUMENTS AS MAY BE NECESSARY FOR PROPER ORIENTATION OR INSTALLATION AND SHALL PROVIDE OFFSETS, FITTINGS, AND ACCESSORIES TO MEET PROJECT CONDITIONS. 9. DISCREPANCIES BETWEEN DRAWINGS OR BETWEEN DRAWINGS AND SPECIFICATIONS SHALL BE REPORTED TO PROFESSIONAL IN WRITING. OBTAIN WRITTEN INSTRUCTIONS FROM PROFESSIONAL AS TO THE MANNER IN WHICH TO PROCEED. NO DEPARTURES FROM THE PROJECT DOCUMENTS SHALL BE MADE WITHOUT PRIOR WRITTEN ACCEPTANCE OF THE PROFESSIONAL. 10. DIMENSIONS, CLEARANCES, AND LOCATIONS OF EQUIPMENT AND MATERIALS SHALL BE FIELD VERIFIED PRIOR TO ORDERING, PROCURING AND FURNISHING SAME. 11. NO EXTRA COMPENSATION OR CHARGES WILL BE ACCEPTED DUE TO DIFFERENCES BETWEEN THE ACTUAL MEASUREMENTS AND THOSE INDICATED ON THE PLAN. THOROUGHLY COORDINATE WORK WITH SITE CONDITIONS AND OTHER TRADES, DETERMINE EXACT ROUTE AND LOCATION OF EACH DUCT, PIPE, CONDUIT, ETC. BEFORE FABRICATION AND INSTALLATION. 12. INSTALL WORK SUBSTANTIALLY AS INDICATED. VERIFY LOCATIONS AND ELEVATIONS ON JOB SITE; DO NOT DIRECTLY SCALE DRAWINGS. MAKE NECESSARY CHANGES IN ELEVATION, FITTINGS, OR OFFSETS TO ACCOMMODATE OBSTACLES OR INTERFERENCES. 13. CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR DAMAGE TO THE BUILDING, PIPING OR EQUIPMENT THAT IS THE RESULT OF WORK FOR INSTALLATION OF THIS CONTRACT. 14. THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR PATCH AND REPAIR OF ALL SURFACES TO MATCH EXISTING MATERIALS AND ADJACENT FINISHES ASSOCIATED WITH INSTALLATION/REMOVAL OF THIS WORK. 15. WORK SHALL BE COMPLETED TO MAINTAIN ALL NECESSARY AND REQUIRED CLEARANCES, ACCESSES, AND OPENINGS, SUCH THAT FULL FUNCTIONALITY, PROPER OPERATION, AND REPAIR AND MAINTENANCE ARE ENSURED. 16. WHERE DEVICE HEIGHT OCCURS AT POINT OF CHANGE OF FINISH, THE DEVICE SHALL BE RAISED OR LOWERED TO OCCUR IN ONE FINISH. ENSURE RESULTING HEIGHT DOES NOT EXCEED ADA REQUIREMENTS. 17. WHERE DEVICE OCCURS IN BRICK, TILE, OR BLOCK WALLS, THEY SHALL BE MOUNTED AT A VERTICAL MASONRY JOINT AND IN EITHER THE TOP OR BOTTOM HORIZONTAL JOINT, CLOSEST TO THE MOUNTING HEIGHT. ENSURE RESULTING HEIGHT DOES NOT EXCEED ADA REQUIREMENTS. 18. UNLESS OTHERWISE NOTED, ALL MOUNTING HEIGHT DIMENSIONS LISTED ARE TO THE CENTER LINE OF THE WALL BOX OR DEVICE. 19. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE LABELED AND LISTED BY A CERTIFIED TESTING LABORATORY OR AGENCY. 20. DRAWINGS REPRESENT THE SCOPE OF WORK IN GENERAL ARRANGEMENT FORM AND ARE INTENDED TO SHOW GENERAL ROUTING AND REQUIRED SIZES/CAPACITIES OF SYSTEM COMPONENTS. EXACT ROUTING OF CONDUITS AND CABLES SHALL BE DETERMINED BY JOB SITE SURVEY. 21. PROVIDE 2-#12, 1-#12 GND IN MINIMUM 3/4"C FOR ALL 20A, SINGLE POLE BRANCH CIRCUITS, UNLESS OTHERWISE NOTED. FOR 120V BRANCH CIRCUITS, PROVIDE NEXT LARGER WIRE SIZE FOR ONE-WAY CIRCUIT DISTANCES GREATER THAN 100 FEET. FOR 208V BRANCH CIRCUITS, PROVIDE NEXT LARGER WIRE SIZE FOR ONE-WAY CIRCUIT DISTANCES GREATER THAN 150 FEET. GENERAL NOTES: 1. THE DEMOLITION PLANS AND NOTES HAVE BEEN PREPARED TO ASSIST THE CONTRACTORS IN IDENTIFYING THE AREAS AND ITEMS OF DEMOLITION AND RENOVATION ASSOCIATED WITH THIS PROJECT. THE INFORMATION PROVIDED IS NOT MEANT TO BE ALL-INCLUSIVE IN TERMS OF LISTING EACH AND EVERY SPECIFIC TASK TO BE PERFORMED. EACH CONTRACTOR WILL THOROUGHLY EXAMINE ALL CONTRACT DOCUMENTS PRIOR TO PERFORMING ANY WORK. 2. DEMOLITION WORK INCLUDES, BUT IS NOT LIMITED TO, THE ITEMS INDICATED ON THE DEMOLITION DRAWINGS AND DESCRIBED IN THE DEMOLITION NOTES. THE EXTENT OF THE DEMOLITION WORK WILL INCLUDE ALL WORK REQUIRED TO COMPLETE THE PROJECT AND ENSURE WHETHER OR NOT THE WORK IS INDICATED ON THE DRAWINGS. 3. EACH CONTRACTOR SHALL THOROUGHLY EXAMINE AND VERIFY ALL EXISTING CONDITIONS BEFORE PERFORMING ANY WORK AND IMMEDIATELY NOTIFY THE ARCHITECT, IN WRITING, OF ANY DISCREPANCIES WITH THE DRAWINGS. 4. ANY WORK PERFORMED AS PART OF THIS CONTRACT REQUIRING OR ALTERATION WILL BE THE RESPONSIBILITY OF THE RESPECTIVE CONTRACTOR. 5. ALL ITEMS NOTED TO BE REMOVED TO BE DISPOSED OF OFF-SITE BY RESPECTIVE CONTRACTORS, UNLESS NOTED OTHERWISE. WHERE INDICATED ON THE DRAWINGS AND/OR IN THE NOTES AS 'SALVAGE AND DELIVER TO OWNER', THE CONTRACTOR WILL CAREFULLY REMOVE INDICATED ITEMS AND STORE THEM WHERE DIRECTED BY THE OWNER. 6. THE OWNER HAS THE OPTION TO RETAIN POSSESSION OF ANY REMOVED MATERIALS OR EQUIPMENT. ALL SUCH ITEMS SHALL BE CAREFULLY REMOVED AND STORED AT THE SITE BY THE CONTRACTOR WHERE DIRECTED BY THE OWNER. ANY MATERIALS OR EQUIPMENT NOT RETAINED BY THE OWNER WILL BECOME THE PROPERTY OF THE CONTRACTOR AND PROMPTLY REMOVED FROM SITE. 7. ANY CONTRACTOR REMOVING OR MODIFYING MATERIAL CONTAINING ASBESTOS OR SUSPECTED OF CONTAINING ASBESTOS WILL NOTIFY THE OWNER AT ONCE AND STOP REMOVAL. IDENTIFICATION AND/OR REMOVAL OF ASBESTOS CONTAINING MATERIAL WILL BE THE RESPONSIBILITY OF THE OWNER. 8. REFER TO ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, TECHNOLOGY AND PLUMBING DRAWINGS FOR DEMOLITION WORK BY RESPECTIVE CONTRACTORS. EACH CONTRACTOR IS RESPONSIBLE FOR ALL DEMOLITION ASSOCIATED WITH HIS CONTRACT AND SCOPE OF WORK. EACH CONTRACTOR IS RESPONSIBLE TO PATCH AND/OR REPAIR ANY AND ALL CONSTRUCTION AFFECTED BY HIS DEMOLITION. THE EXTENT OF PATCH AND REPAIR SHALL BE AS REQUIRED TO RECEIVE THE SCHEDULED NEW WORK. ALL CONTRACTORS ARE RESPONSIBLE FOR COORDINATION OF WORK WITH OTHER CONTRACTORS BEFORE PERFORMING ANY WORK. 9. ALL PATCH AND REPAIR WORK SHALL BE PERFORMED USING MATERIALS THAT MATCH THE EXISTING ADJACENT CONSTRUCTION. WHERE PATCHING EXISTING MASONRY WALLS OR INFILLING BETWEEN WALLS WITH MASONRY TO MATCH EXISTING, "TOOTH-IN" NEW MASONRY TO EXISTING. 10. EACH CONTRACTOR IS RESPONSIBLE TO PROTECT ALL EXISTING CONSTRUCTION SCHEDULED TO REMAIN. EACH CONTRACTOR IS RESPONSIBLE TO PATCH AND/OR REPAIR ANY AND ALL CONSTRUCTION AFFECTED BY THEIR DEMOLITION. EACH CONTRACTOR SHALL PATCH (SUBSTRATE AND FINISHED SURFACES) ANY EXISTING FINISHES AFFECTED BY THEIR RESPECTIVE WORK. 11. EXISTING CONDITIONS INDICATED ARE OBTAINED FROM AVAILABLE SOURCES (EXISTING DRAWINGS, FIELD SURVEYS, ETC.) AND ARE NOT GUARANTEED TO BE TRUE AND EXACT. CONTRACTOR(S) SHALL FIELD VERIFY EXISTING CONDITIONS AND NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH THE AFFECTED PORTION OF THE WORK. 12. REMOVAL IN ITS ENTIRETY INCLUDES HANGERS, ELECTRICAL, CONTROLS, ETC., TO LEAVE A LIKE NEW OR MATCHING EXISTING CONDITION. 13. THIS CONTRACTOR SHALL INVESTIGATE THE IMPACTS OF DEMOLITION TO THE SOUROUNDING SPACES PRIOR TO DEMOLITION ACTIVITIES. THIS CONTRACTOR IS RESPONSIBLE TO COORDINATE DEMOLITION ACTIVITY AND PROVIDE NOTICE OF DISRUPTIVE ACTIVITIES TO THE OWNER PRIOR TO STARTING ANY DEMOLITION WORK. GENERAL DEMOLITION NOTES: EXISTING DEVICES TO REMAIN ARE SHOWN IN LIGHT LINEWEIGHT. EXISTING DEVICES TO BE REMOVED ARE SHOWN IN DASHED LINEWEIGHT. NOT ALL ABBREVIATIONS & SYMBOLS MAY APPLY TO THIS PROJECT. GENERAL SYMBOL NOTES: 1. 2. 3. FLOOR BOX -SUBSCRIPT INDICATES TYPE -(SEE SPECIFICATIONS) RECEPTACLES FLOOR POKE-THRU -SUBSCRIPT INDICATES TYPE -(SEE SPECIFICATIONS)P WHIP BOX -SUBSCRIPT INDICATES TYPE -(SEE SPECIFICATIONS) DUPLEX RECEPTACLE -NEMA 5-20R -WALL MOUNTED -FLUSH SYMBOL DESIGNATIONS: C -MOUNT 6" ABOVE SINK OR COUNTERTOP F -FLOOR MOUNTED GFI -GROUND FAULT INTERRUPTER H -MOUNT HORIZONTALLY 6" ABOVE SINK OR COUNTERTOP IG -ISOLATED GROUND Q -QUAD SP -SURGE PROTECTED TP -TAMPER PROOF USB -USB CHARGER W -WHIP WP -GROUND FAULT INTERRUPTER WITH WEATHERPROOF WHILE-IN-USE COVER # -CIRCUIT NUMBER DOUBLE DUPLEX RECEPTACLE -NEMA 5-20R -WALL MOUNTED -FLUSH SPECIAL PURPOSE RECEPTACLE -SUBSCRIPT INDICATES NEMA TYPE WB FB DOUBLE DUPLEX RECEPTACLE -NEMA 5-20R -CEILING MOUNTED DUPLEX RECEPTACLE -NEMA 5-20R -CEILING MOUNTED SIMPLEX RECEPTACLE -NEMA 5-20R -WALL MOUNTED -FLUSH X X X X NOTE: WALL MOUNTED DEVICES SHALL BE 18" AFF TO CENTER OF BOX, UNO MANUAL PULL STATION -42" AFF TO CENTER OF HANDLE FIRE ALARM AUDIBLE NOTIFICATION DEVICE -MOUNTING HEIGHT PER NFPA 72 HEAT DETECTOR, COMBINATION UOI, NUMBER INDICATES TEMPERATURE RATING SMOKE DETECTOR, PHOTOELECTRIC TYPE (D -DUCT MOUNTED, I -IONIZATION TYPE, A -UNIT WITH AUXILIARY CONTACT) AUDIBLE/VISIBLE NOTIFICATION DEVICE -MOUNTING HEIGHT PER NFPA 72, NUMBER INDICATES CANDELA RATING VISIBLE NOTIFICATION DEVICE -MOUNTING HEIGHT PER NFPA 72, NUMBER INDICATES CANDELA RATING P Ƨ ADDRESSABLE CONTROL MODULEACM AM ADDRESSABLE INTERFACE MODULE TS TAMPER SWITCH CONNECTION FS FLOW SWITCH CONNECTION RTS REMOTE TEST STATION ELECTRIC GONG -CONNECT TO 120VAC CIRCUIT AND FIRE ALARM SYSTEM DP DIFFERENTIAL PRESSURE SWITCH FACP FAAP FIRE ALARM CONTROL PANEL -6' AFF TO TOP OF BOX FIRE ALARM ANNUNCIATOR PANEL -6' AFF TO TOP OF BOX K CITY KEY BOX DH MAGNETIC DOOR HOLDER 15 15 WIRELESS ACCESS POINT, CEILING MOUNTED (POWER OVER ETHERNET) TECHNOLOGY VOICE/DATA OUTLET -WALL MOUNTED -FLUSH VOICE OUTLET -WALL MOUNTED -FLUSH DEVICE DESIGNATIONS: C -MOUNT 6" ABOVE COUNTER TOP F -FLOOR MOUNTED H -MOUNT HORIZONTALLY 6" ABOVE COUNTER TOP W -WALL MOUNTED, 48" AFF TO CENTER # -NUMBER OF JACKS DATA OUTLET -WALL MOUNTED -FLUSH W DATA OUTLET, CEILING MOUNTED NOTE: WALL MOUNTED DEVICES SHALL BE 18" AFF TO CENTER OF BOX, UNO S CEILING MOUNTED SPEAKER S WALL MOUNTED SPEAKER TV CATV / TV MONITOR OUTLET -WALL MOUNTED -FLUSH C WALL MOUNTED CLOCK VC VOLUME CONTROL TC ELECTRONIC TIME CLOCK IC INTERCOM STATION # # # SECURITY COUNDUIT TO DOOR FRAME MD MOTION DETECTOR PUSH BUTTON DOOR SWITCH CR CARD READER KP SECURITY KEY PAD DC DOOR CONTACT C STATIONARY VIDEO CAMERA C PAN/TILT/ZOOM ENABLED VIDEO CAMERAPTZ EQUIPMENT DISCONNECT SWITCH, VOLTAGE RATING TO MATCH CIRCUIT, NUMBER INDICATES AMPERE RATING FUSED DISCONNECT SWITCH, VOLTAGE RATING TO MATCH CIRCUIT, NUMBERS INDICATE DISCONNECT/FUSE AMPERE RATING MAGNETIC MOTOR STARTER, NUMBER INDICATES NEMA SIZE COMBINATION DISCONNECT MAGNETIC MOTOR STARTER, NUMBERS INDICATE DISCONNECT AMPERE/NEMA SIZE RATING MANUAL MOTOR STARTER EQUIPMENT CONNECTION M M METER R ENCLOSED RELAY ST SHUNT TRIP VFD VARIABLE FREQUENCY DRIVE 30 30/15 00 30/1 J J JUNCTION BOX -WALL OR CEILING JUNCTION BOX -RECESSED IN FLOOR PB PULL BOX 2 2-POLE TOGGLE SWITCH SPD SURGE PROTECTIVE DEVICE CB ENCLOSED CIRCUIT BREAKER, NUMBER INDICATES AMPERE RATING 30 CONTACTORC CR CORD REEL PS POWER SUPPLY PUSH BUTTON MUSHROOM SWITCH E EMERGENCY POWER OFF BUTTON -(EPO) DAYLIGHT SENSOR SWITCHES PASSIVE INFRARED OCCUPANCY SENSOR -CEILING MOUNTED WITH AUXILIARY CONTACT FOR BMS INPUT SWITCH PACK SINGLE POLE WALL SWITCH, LOWER CASE LETTER INDICATES SWITCHING ARRANGEMENT SWITCH DESIGNATIONS: 3 -THREE WAY 4 -FOUR WAY D -DIMMER K -KEYED L -LOW VOLTAGE MC -MOMENTARY CONTACT MT -MANUAL TIMER O -OCCUPANCY SENSOR O2 -OCCUPANCY SENSOR, DUAL CIRCUIT TYPE OB -OCCUPANCY SENSOR, SINGLE CIRCUIT WITH AUXILIARY CONTACT FOR BMS INPUT P -PILOT LIGHT HP -MOTOR RATED TOGGLE SWITCH DS SP CS PC PHOTOCELL DH DAYLIGHT HARVESTING CONTROLLER ER RC NOTE: WALL MOUNTED SWITCHES SHALL BE 46" AFF TO CENTER OF DEVICE. EMERGENCY LIGHTING CONTROL UNIT DIGITAL ROOM CONTROLLER RELAY (X = QUANTITY OF RELAYS) X CIRCUIT BREAKER, LOW VOLTAGE, BOLT-ON TYPE ELECTRICAL ONE-LINE SYMBOLS TRANSFORMER GROUND DISTRIBUTION T DISTRIBUTION TRANSFORMER, REFER TO ONE LINE DIAGRAM 480V FLUSH MOUNTED PANELBOARD 480V SURFACE MOUNTED PANELBOARD 208V FLUSH MOUNTED PANELBOARD 208V SURFACE MOUNTED PANELBOARD SURFACE MOUNTED CONTROL PANEL FLUSH MOUNTED CONTROL PANEL HOMERUN TO PANELBOARD -SHORT LINE(S) = HOT CONDUCTOR(S); LONG LINE = NEUTRAL CONDUCTOR; LINE WITH DOT = GROUND EQUIPMENT ON SAME CIRCUIT, BUT SEPARATELY CONTROLLED HVAC CONTROL POWER VAV TRANSFORMER, 120VAC PRIMARY, 24VAC SECONDARY, CLASS II, 300VA. MOUNT TO JUNCTION BOX ABOVE CEILING. PROVIDE PRIMARY FUSE AND SINGLE-POLE SINGLE-THROW PRIMARY SNAP SWITCH. T 24VAC WIRING These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:31 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 BRW ELECTRICAL SYMBOLS, NOTES & ABBREVIATIONS AT DU E-001 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 PANELBOARD PP-472B LOCATION: ATOMIZER ROOM 472B MAIN BUS AMPS: 100A SERVICE VOLTAGE: 220/126V, 1PH, 3W MAIN CIRCUIT BREAKER: NONE MOUNTING: SURFACE FEEDER SIZE: (3)#1, (1)#8 GND IN 1-1/4"C FEED: T-PP-472B FEED THRU LUGS: NONE S.C. RATING: 10,000 AMPS RMS SYM. DESCRIPTION PHASE AMPS TRIP POLES TRIP PHASE AMPS DESCRIPTIONPH A PH B AMPS AMPS PH A PH B REC-EDM WATER CIRCULATOR 4.0 20A/2P 1 2 20A/2P 4.0 REC-EDM DISCHARGE CONTROLLER 4.0 --3 4 --4.0 LENS 150 - POWDER FEED CART 20.0 20A/2P 5 6 30A/2P 30.0 LENS 150 - LENS SYSTEM 20.0 -- 7 8 --30.0 LENS 150 - LASER POWER SUPPLY 10.0 20A/2P 9 10 --0.0 SPACE 10.0 -- 11 12 --0.0 SPACE 34.0 34.0 SUBTOTAL (AMPS)34.0 34.0 PH. A PH. B TOTAL PHASE AMPS 68.00 68.00 TOTAL PHASE kVA 8.16 8.16 TOTAL 3-PHASE kVA 16.32 TOTAL DEMAND 3-PHASE kVA 13.06 TOTAL DEMAND 3-PHASE AMPS 59.35 EXISTING PANELBOARD LPP-4-11 LOCATION: CORRIDOR MAIN BUS AMPS: 100A SERVICE VOLTAGE: 208Y/120V, 3PH, 4W MAIN CIRCUIT BREAKER: NONE MOUNTING: RECESSED FEEDER SIZE: EXISTING TO REMAIN FEED: LPP-4-2_2 FEED THRU LUGS: NONE S.C. RATING: DESCRIPTION PHASE AMPS TRIP POLES TRIP PHASE AMPS DESCRIPTIONPH A PH B PH C AMPS AMPS PH A PH B PH C REC-GLOVE BOX- GEN. LAB 472 10.0 20A/1P 1 2 20A/1P 6.0 REC-OPENSLM-EX-ATOMIZER 472B REC-POLISHER- GEN. LAB 472 5.5 20A/1P 3 4 20A/1P 6.0 REC-OPENSLM-EX-ATOMIZER 472B EAV/SAV/RH/FCU CONTROL TX. 0.0 20A/1P 5 6 20A/1P 0.0 SPARE REC-ATOMIZER 472B 4.5 20A/1P 7 8 20A/1P 3.0 QUAD REC-ATOMIZER 472B REC-RACEWAY- GEN. LAB 472 4.5 20A/1P 9 10 20A/1P 6.0 REC-RACEWAY-LASER RM 472A REC-RACEWAY-LASER RM 472A 6.0 20A/1P 11 12 20A/1P 3.0 REC.-LASER RM 472A REC-GEN. LAB 472 3.0 20A/1P 13 14 20A/1P 4.5 REC-ATOMIZER 472B REC-HEAT EXG-ATOMIZER 472 8.0 20A/1P 15 16 30A/2P 30.0 ATOMIZER FURNACE CHAMBER FCU-1,2,3 12.0 20A/2P 17 18 --30.0 12.0 --19 20 20A/1P 3.0 REC-FUME HOOD-GEN. LAB 472 REC-FUME HOOD-GEN. LAB 472 3.0 20A/1P 21 22 20A/2P 9.0 YTTERBIUM LASER - LASER RM 472A Nd:YAG LASER - LASER RM 472A 9.0 20A/2P 23 24 --9.0 9.0 --25 26 20A/2P 9.0 OPENSLM-EX LASER-ATOMIZER 472B SPARE 20A/1P 27 28 --9.0 SPARE 20A/1P 29 30 20A/1P 0.0 SPARE SPARE 0.0 20A/1P 31 32 20A/1P 0.0 SPARE SPARE 0.0 20A/1P 33 34 20A/1P 0.0 SPARE SPARE 0.0 20A/1P 35 36 20A/1P 0.0 SPARE SPARE 0.0 20A/1P 37 38 20A/1P 0.0 SPARE SPARE 0.0 20A/1P 39 40 20A/1P 0.0 SPARE SPARE 0.0 20A/1P 41 42 20A/1P 0.0 SPARE 38.5 21.0 27.0 SUBTOTAL (AMPS)25.5 60.0 42.0 PH. A PH. B PH.C TOTAL PHASE AMPS 64.00 81.00 69.00 NOTES: TOTAL PHASE kVA 7.68 9.72 8.28 TOTAL 3-PHASE kVA 25.68 TOTAL DEMAND 3-PHASE kVA 17.98 TOTAL DEMAND 3-PHASE AMPS 49.96 PP-472B T-PP-472B 1.5 kVA, 1Ø BOOST TRANSFORMER PRI: 120 X 240V SEC: 16/32V LPP-4-2 100A-2P (ETR) (3)#1, (1)#8 GND IN 1-1/4"C (2)#1, (1)#8 GND IN 1-1/4"C 100A, NON-FUSED DISCONNECT HPP-P-2 80A-3P (ETR) (3)#3, (1)#8 GND IN 1-1/4"C ATOMIZER POWER SUPPLY PENTHOUSE FIFTH FLOOR FOURTH FLOOR KEY NOTES: 1. PROVIDE U.L. LISTED CIRCUIT BREAKER TO MATCH EXISTING PANELBOARD CONSTRUCTION AND KAIC RATING. # 1 1 (3)#3, (1)#8 GND IN 1-1/4"C (APPROX. 100-FEET) DEFEATABLE ACCESS CONTROL INTERFACE MODULE LASER WARNING MODULE KEYPAD PUSH BEFORE EXIT DUAL DOOR LIMIT SWITCH EMERGENCY CRASH MODULE ROOM INTERLOCK CONTROL MODULE LASER/ SHUTTER INTERFACE MODULE #22 AWG STRANDED JUMPER WIRE #22 AWG STRANDED JUMPER WIRE #22/8 STRANDED CABLE (TYP. BETWEEN MODULES) #22/2 STRANDED CABLE MAGENTIC LOCK #22/4 STRANDED CABLE #22/4 STRANDED CABLE SHUTTER/LASER INTERLOCK CABLES (BY OWNER) LASER #1 LASER #2 #22/2 STRANDED CABLE 24 VDC PLUG-IN POWER SUPPLY (SUPPLIED WITH SYSTEM) EMERGENCY CRASH MODULE (GENERAL LAB 427) (LASER RM. 427A) GENERAL NOTES: 1. ALL CABLING SHALL BE ROUTED IN RACEWAY (MIN. 3/4" EMT). 2. REFER TO DRAWING A-410 FOR EXACT LOCATIONS AND MOUNTING HEIGHTS OF LASER SAFETY SYSTEM EQUIPMENT. 3. REFER TO LASER SAFETY SYSTEM MANUFACTURER WIRING DIAGRAMS FOR CABLE TERMINATION INFORMATION. 4. PROVIDE PROGRAMMING OF FIRE ALARM SYSTEM TO DEFEAT ACCESS CONTROL SYSTEM IN THE EVENT OF A FIRE ALARM. FIRE ALARM CONTROL MODULE #18/2 STRANDED CABLE (RED) FLOOR MANUAL PULLSTATION. HEIGHT INDICATED IS TO TOP OF PULLSTATION COVER IF EQUIP. OTHERWISE HEIGHT INDICATES TOP OF DEVICE BACKBOX. WALL MOUNTED AUDIO/VISUAL OR VISUAL ONLY DEVICE. 4'-0" 6'-8" 3/4"C (POWER) FIN FLR FINISHED CEILING METALLIC, SINGLE COMPARTMENT RACEWAY 4"SQUARE JUNCTION BOX WITH EXTENSION MUD RING (TYP) SUSPENDED CEILING TYPICAL SIDE ELEVATION TYPICAL FRONT ELEVATION WALL FIN FLR 1"C (TELE/COMM) 3/4"C (POWER) 4"SQUARE JUNCTION BOX (TYP) WALL MUD RING (TYP) HEIGHT AS INDICATED HEIGHT AS INDICATED METALLIC, SINGLE COMPARTMENT RACEWAY 1 L2L1 24VAC 120VAC 300VA CLASS II TRANSFORMER 120VAC, 1∅, PRIMARY 24VAC SECONDARY W/ MANUAL RESET OVERLOAD INTEGRAL DISCONNECT SWITCH (FACTORY SUPPLIED W/ FCU) MAINTENANCE SWITCH ENCLOSED, LOCKABLE 1-POLE, 10A, NEMA 1 JUNCTION BOX 6"x6", METAL (3) #12, 3/4"C (3) #12, 3/4"C (3) #12, 3/4"C L2 GND 208 VAC TO OTHER FAN COIL UNITS SHOWN ON PLAN DRAWINGS (3) #12, 3/4"C TO OTHER FCU/EAV/SAV DIGITAL CONTROLLERS SHOWN ON PLAN DRAWINGS 2/C #16 TWISTED PAIR TYPICAL ALL CLASS II 24VAC WIRING KEY NOTES MOUNT IN VISUAL SIGHT AND CLOSE PROXIMITY TO CLASS II TRANSFORMER. 1 L1 GND 120VAC DIGITAL CONTROLLER FAN COIL UNIT These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:33 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 BRW ELECTRICAL SCHEDULES & DETAILS AT DU E-501 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 NO SCALE 1 PARTIAL ONE-LINE DIAGRAM NO SCALE 2 TYPICAL LASER SAFETY SYSTEM SCHEMATIC 1/8" = 1'-0" 4 TYPICAL FIRE ALARM ELEVATIONS NO SCALE 5 TYPICAL SINGLE-COMPARTMENT RACEWAY INSTALLATION NO SCALE 3 TYPICAL POWER FEED WIRING - FCU, EAV AND SAV TERMINALS DS CS CS CS CS CS DS (ETR)(ETR)(ETR) (ETR) (ETR) a (ETR) DD b aaa b b b bbb 1 1 1 1 ROOM LIGHTING CONTROL PANEL ER ER a b 3 2 2 4 4 375 SF GENERAL LAB 472 359 SF ATOMIZER ROOM 472B 121 SF LASER ROOM 472A "LASER IN-USE" DaEM/aa a b DD d d b ddEM/d c c XA SA (ETR)(ETR)(ETR) (ETR) (ETR) (ETR) ROOM LIGHTING CONTROL PANEL ER ER b d a b d a d 1 1 11 2 3 5 54 5 4 5 These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:36 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 BRW PARTIAL LIGHTING FOURTH FLOOR PLANS AT DU EL-110 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 1/4" = 1'-0" 1 ROOM 472 DEMOLITION PLAN - LIGHTING 1/4" = 1'-0" 2 ROOM 472 NEW WORK PLAN - LIGHTING #DEMOLITION KEY NOTES 1. CAREFULLY DISCONNECT AND REMOVE LIGHT FIXTURE TO ACCOMMODATE LIGHT FIXTURE RELOCATION. 2. CAREFULLY DISCONNECT AND REMOVE EXISTING LIGHTING CONTROL DEVICE AND SAVE FOR RELOCATION. DISCONNECT AND REMOVE LOW VOLTAGE CABLING BACK TO LIGHTING CONTROL PANEL. 3. CAREFULLY DISCONNECT AND REMOVE EXISTING LIGHTING CONTROL PANEL AND ASSOCIATED EMERGENCY RELAYS TO ACCOMMODATE ROOM RENOVATIONS. SAVE AND PROTECT PANEL FOR RELOCATION. 4. DISCONNECT AND REMOVE CEILING MOUNTED OCCUPANCY SENSOR AND ASSOCIATED LOW VOLTAGE CABLING BACK TO LIGHTING CONTROL PANEL. NEW WORK KEY NOTES 1. RELOCATE EXISTING LIGHT FIXTURE TO LOCATION SHOWN. FIXTURE SHALL BE CONNECTED TO ADJACENT LIGHT FIXTURES TO FORM A CONTINUOUS RUN. 2. RELOCATE EXISTING LIGHTING CONTROL PANEL AND ASSOCIATED EMERGENCY RELAYS TO ACCOMMODATE ROOM RENOVATIONS, COORDINATE EXACT LOCATION WITH OTHER ROOM SYSTEMS (I.E. DUCTWORK, PIPING, ETC.) TO ENSURE NEW LOCATION WILL BE ACCESSIBLE UPON COMPLETION OF PROJECT. EXTEND AND RECONNECT ALL CONTROL WIRING TO NEW LOCATION. 3. PROVIDE EXIT LUMINAIRE (LITHONIA #LQM-S-W-3-R-120/277 OR APPROVED CORNELL EQUAL) AND CONNECT TO NEAREST EXIT LIGHTING CIRCUIT. 4. RELOCATE EXISTING LIGHTING CONTROL DEVICE TO LOCATION SHOWN. PROVIDE ALL REQUIRED LOW-VOLTAGE WIRING TO RECONNECT DEVICE TO RELOCATED CONTROL PANEL. 5. PROVIDE NEW LIGHTING CONTROL DEVICE AND CONNECT TO LIGHTING CONTROL PANEL. PROVIDE ALL REQUIRED SYSTEM PROGRAMMING TO INTEGRATE NEW DEVICES INTO EXISTING LIGHTING CONTROL SYSTEM. 6. PROVIDE ILLUMINATED "LASER IN USE" SIGN ABOVE NEW DOOR (LITHONIA #LQM-P-W-1-R-SW10 OR APPROVED CORNELL EQUAL). SIGN SHALL BE CONNECTED TO LOCAL LIGHTING CIRCUIT AND CONTROLLED BY TOGGLE SWITCH INSIDE OF LASER ROOM. # (ETR) (ETR) (ETR) GFI (ETR) WIREMOLD WIREMOLD (ETR) (ETR) LPP-4-11 1 1 LPP-4-2 LPP-4-2 ? (ETR) (ETR) 375 SF GENERAL LAB 472 359 SF ATOMIZER ROOM 472B 121 SF LASER ROOM 472A T LENS 450 -LASER POWER SUPPLY LENS 450 -POWDER FEED CART LENS 450 -LENS SYSTEM ATOMIZER POWER SUPPLY ATOMIZER FURNACE CHAMBER ATOMIZER HEAT EXCHANGER 100A, NON-FUSED, 600V 5-FOOT FUME HOOD (ETR) (ETR) (ETR) (ETR) GFI GLOVE BOX LPP-4-11 (ETR) POLISHER YTTERBIUM FIBER LASER COMPACT PULSED ND: YAG LASER GFI (ETR) 6-FOOT FUME HOOD 20-LPP-4-11 21-LPP-4-11 A B C D A B C D BOTTOM OF RACEWAY +18" AFF BOTTOM OF RACEWAY +42" AFF 3-LPP-4-11 OPENSLM-EX WORKSTATION EDM UP TO MECH. PENTHOUSE PANELBOARD HPP-P-2 J J J J J J J PP-472B 2,4-PP-472B 1,3-PP-472B FCU-3 FCU-2 FCU-1 SVAV-2 SVAV-1 EVAV-1 EAV-3 SAV-1 EAV-1 EAV-2 EVAV-2 RH-1 RH-2 RH-3 2-LPP-4-11 4-LPP-4-11 T 5-LPP-4-11 T T 5,7-PP-472B 6,8-PP-472B 9,11-PP-472B 6-LPP-4-11 17,19-LPP-4-11 16,18-LPP-4-11 9 99 9-LPP-4-11 14 14 14 17,19 17,19 10 11 10 11 10 11 10 11 12 12 1-LPP-4-11 13 13-LPP-4-11 23,25-LPP-4-11 22,24-LPP-4-11 LASER SAFETY SYSTEM 10-LPP-4-11 11-LPP-4-11 12-LPP-4-11 T-PP-472B 1 1 2 2 2 3 4 5 HP HP LPP-4-2 LPP-4-2 (ETR) (ETR) 6 6 2#12, 1#12 GND., 3/4"C 2#12, 1#12 GND., 3/4"C 2#12, 1#12 GND., 3/4"C 2#10, 1#10 GND., 3/4"C 2#12, 1#12 GND., 3/4"C 2#10, 1#10 GND., 3/4"C 2#12, 1#12 GND., 3/4"C 2#12, 1#12 GND., 3/4"C 7 7 7 7 E EPO HVAC 8 2#12, 1#12 GND., 3/4"C 15 14-LPP-4-11 15-LPP-4-11 These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:38 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 BRW PARTIAL POWER FOURTH FLOOR PLANS AT DU EP-110 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 1/4" = 1'-0" 1 ROOM 472 DEMOLITION PLAN - POWER 1/4" = 1'-0" 2 ROOM 472 NEW WORK PLAN - POWER KEY NOTES: 1. PROVIDE METALLIC, SINGLE-COMPARTMENT, RACEWAY (WIREMOLD 4000) WITH QUANTITY AND TYPES OF RECEPTACLES INDICATED. RACEWAY FINISH SHALL BE SELECTED BY ARCHITECT. 2. PROVIDE 300VA, CLASS II, 120VAC PRIMARY, 24VAC SECONDARY TRANSFORMER WITH MANUAL RESET OVERLOAD FOR AIR VALVE, AIR TERMINAL AND DIGITAL CONTROLLER 24VAC POWER (DESIGN MAKE: RIB MODEL #PSH300A OR APPROVED EQUAL). PROVIDE 1-POLE, LOCKABLE MAINTENANCE SWITCH AT EACH TRANSFORMER LOCATION. PROVIDE ALL CLASS II, 24VAC, WIRING BETWEEN TRANSFORMER AND INDICATED LOW VOLTAGE DEVICES UTILIZING 16/2 TWISTED PAIR CABLES. TRANSFORMER AND MAINTENANCE SWITCH SHALL BE WALL MOUNTED NEAR ROOM CEILING IN AN ACCESSIBLE LOCATION. 3. LOCATE TRANSFORMER ABOVE PANELBOARD. 4. PROVIDE RECESSED BACKBOXES FOR LASER SAFETY SYSTEM COMPONENTS. REFER TO A-SERIES DRAWINGS FOR BACKBOX MOUNTING HEIGHTS AND EXACT COMPONENT LOCATIONS. REFER TO DETAIL ON DRAWING E-501 FOR ADDITIONAL SYSTEM REQUIREMENTS AND WIRING INFORMATION. 5. PROPOSED ROUTE FOR ATOMIZER POWER SUPPLY FEEDER UP TO PANELBOARD HPP-P-2 IN MECHANICAL PENTHOUSE. REFER TO PARTIAL ONE-LINE DIAGRAM FOR FEEDER SIZE AND ADDITIONAL INFORMATION. 6. COORDINATE EXACT NEMA CONFIGURATION OF LAB EQUIPMENT RECEPTACLE WITH CORNELL END USER. #DEMOLITION KEY NOTES 1. DISCONNECT AND REMOVE EXISTING RACEWAY AND ASSOCIATED BRANCH CIRCUITING BACK TO PANELBOARD LPP-4-11. #KEY NOTES (CONT.): 7. PROVIDE POWER CONNECTIONS FOR FUME HOOD RECEPTACLES. UPPER CASE LETTER SUBSCRIPT INDICATES RECEPTACLE POWERED BY THAT CIRCUIT. 8. PROVIDE BREAK-GLASS TYPE EMERGENCY SHUTOFF PUSHBUTTON (PILLA MODEL #ST120) FOR LAB HVAC SYSTEM. REFER TO MI SERIES DRAWINGS FOR WIRING REQUIREMENTS. # W 4 (ETR) 4 (ETR) (ETR) (ETR) 2 42 2 1 375 SF GENERAL LAB 472 359 SF ATOMIZER ROOM 472B 121 SF LASER ROOM 472A W 4 (ETR) 4 (ETR) (ETR) (ETR) 2 2 1 These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 387 East Main Street Rochester NY 14604 585 232 8300 | rochester@swbr.com FILE PATH:SWBR Project Number Checked By: Project Manager: Drawn By: Revisions 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om3/5/2019 3:35:41 PMC:\Users\buechelt\Documents\18695.00 Upson Hall_Rm 472_MEP_peguerot.rvt18695.00 BRW PARTIAL TELECOM FOURTH FLOOR PLANS AT DU ET-110 Bid Documents Cornell University Upson Hall Room 472 Renovation 124 Hoy Rd, Ithaca, NY 14850 March 5, 2019 1/4" = 1'-0" 1 ROOM 472 DEMOLITION PLAN - TELECOM 1/4" = 1'-0" 2 ROOM 472 NEW WORK PLAN - TELECOM #DEMOLITION KEY NOTES 1. DISCONNECT AND REMOVE EXISTING WIRELESS ACCESS POINT DATA CABLE AND ASSOCIATED RACEWAY BACK TO NEAREST NON-AFFECTED AREA TO ACCOMMODATE ROOM RENOVATIONS. SAVE AND PROTECT DATA CABLE AND RACEWAY FOR REUSE. REMOVAL OF WIRELESS ACCESS POINT SHALL BE BY CORNELL CIT. 2. DISCONNECT AND REMOVE DATA OUTLETS AND ASSOCIATED DATA CABLING BACK TO FOURTH FLOOR DATA CLOSET. NEW WORK KEY NOTES 1. EXTEND EXISTING RACEWAY AND DATA CABLE FOR RELOCATED CEILING MOUNTED WIRELESS ACCESS POINT TO LOCATION SHOWN. PROVIDE CEILING MOUNTED JUNCTION BOX AT END OF RACEWAY AND COIL CABLE WITHIN BOX. ACCESS POINT SHALL BE RE-INSTALLED BY CORNELL CIT. # CORNELL UNIVERSITY UPSON HALL ROOM 472 FACILITIES CONTRACTS LABORATORY RENOVATION 121 HUMPHREYS SERVICE BUILDING ITHACA, NEW YORK 14853-3701 POST BID BULLETIN NO. 1 May 8, 2019 This Post Bid Bulletin contains changes to the requirements of the Contract Documents and Specifications. Such changes are to be incorporated into the Construction Documents and shall apply to the work with the same meaning and force as if they had been included in the original document. Wherever this Post Bid Bulletin modifies a portion of a paragraph of the specifications or a portion of any Drawing, the remainder of the Paragraph or Drawing shall remain in force. NOTE: Provisions of all Contract Documents apply. Thank you for your recent bid for the above referenced project. All bids received exceeded the Owner’s Construction Budget and we must explore other options for this project. Please email the responses to Facilities Contracts (FacilitiesContracts@cornell.edu) no later than 12:00PM on May 15, 2019 to aid Cornell in its review and approval process. DRAWINGS A-110: Partial Fourth Floor, Demo and Reflected Ceiling Plan DELETE Equipment List Item Number 5A ‘5’-0” FUME HOOD” in its entirety. REVISE 1/A-110 Room 472 Demolition Plan per attached drawing AD-2-A1. REVISE 2/A-110 Room 472 Floor Plan per attached drawing AD-2-A1. A-410: Partial Fourth Floor, Demo and Reflected Ceiling Plan REVISE 6/A-410 General Lab – West Elevation per attached drawing AD-2-A2. REVISE 7/A-410 General Lab – North Elevation per attached drawing AD-2-A2. A-501: Details, Schedules and Specifications DELETE Laboratory Fume Hood Number ‘FH-1’ from Fume Hood Schedule, in its entirety. DELETE Detail 3/A-501 “Section @ Metal Lab Case Work, Typ” Upson Hall Room 472 Laboratory Renovation Post Bid Bulletin No. 1 May 8, 2019 Page 2 M-110: Partial Mechanical Fourth Floor Plan DELETE exhaust air valve, EAV-1, and associated duct, duct accessories and fire rated insulation from project. Refer to attached drawing AD-2-M1. REVISE (decrease) size and capacity of hot water re-heat coil RH-1. Refer to attached drawing AD-2-M1. REVISE (reduce) the size of supply air valve SAV-1. Refer to attached drawing AD-2-M1. DELETE one supply air diffuser, S-2, from the General Lab. Changed supply air flow from 705 CFM to 680 CFM. Refer to attached drawing AD-2-M1. REVISE layout and size of supply air duct in the General Lab. Refer to attached drawing AD-2-M1. REVISE (increase) size of exhaust air valve EAV-3, in the General Lab. Refer to attached drawing AD-2-M1. REVISE (increase) air flow of exhaust air grille R-1, in the General Lab. Refer to attached drawing AD-2-M1. DELETE fan coil unit FCU-3. Refer to attached drawing AD-2-M1. M-500: Mechanical Schedules DELETE exhaust air valve, EAV-1 from Exhaust Air Valve Schedule. Refer to attached drawing AD-2-M2. REVISE size and performance of exhaust air valve, EAV-3. Refer to attached drawing AD-2-M2. REVISE performance of supply air valve SAV-1. Refer to attached drawing AD-2-M2. DELETE fan coil unit FCU-3 from Fan Coil Unit Schedule. Refer to attached drawing AD-2-M2. REVISE performance of hot water re-heat coil RH-1. Refer to attached drawing AD-2-M2. MP-110: Partial Mechanical Piping Fourth Floor Plan DELETE fan coil unit FCU-3 and associated chilled water supply and return pipe from Atomizer Room. Refer to attached drawing AD-2-M3. REVISE size of existing supply and return chilled water piping. Refer to attached drawing AD-2-M3. Upson Hall Room 472 Laboratory Renovation Post Bid Bulletin No. 1 May 8, 2019 Page 3 MI-601: Controls Schematic Room 472A & B DELETE control points for fan coil unit FCU-3 from Atomizer Points List. Refer to attached drawing AD-2-M4. DELETE FCU-3 tag from control schematic. REVISE sequence of operations to eliminate reference to FCU-3. MI-602: Controls Schematic Room 472 DELETE 5’ fume hood and associated controls from the control schematic. Refer to attached drawing AD-2-M5. REVISE Laboratory Air Flow Schedule. Refer to attached drawing AD-2-M6. REVISE sequence of operations to eliminate reference to EAV-1. MI-603: Controls Points List Room 472 DELETE control points for EAV-1, from the General Lab Points List. Refer to attached drawing AD-2-M7. P-110: Partial Plumbing Fourth Floor Plan DELETE notes associated with the 5’ fume hood and revised annotation to reflect changes to the architectural background. Refer to attached drawing AD-2-M8. DELETE New Work Key Note 2. Refer to attached drawing AD-2-M8. DELETE New Work Key Note 10. Refer to attached drawing AD-2-M8. ADD condensate lines to serve FCU-1 and FCU-2, added New Work Key Note #11. Refer to attached drawing AD-2-M8. Upson Hall Room 472 Laboratory Renovation Post Bid Bulletin No. 1 May 8, 2019 Page 4 EP-110: Partial Power Fourth Floor Plans REVISE existing wiremold on north wall to be existing to remain in Detail 1. Refer to attached drawing AD-2-E2. DELETE new raceway and associated receptacles and branch circuiting (circuit #9) on north wall, in Detail 2. Refer to attached drawing AD-2-E2. ADD existing wiremold on north wall inn Detail 2. Refer to attached drawing AD-2-E2. DELETE 120V power connections for 5-foot fume hood in Detail 2. Refer to attached drawing AD-2-E2. DELETE both 208V and 24V power connections for FCU-3 in Detail 2. Refer to attached drawing AD-2-E2. DELETE 24V power connections for EAV-1 in Detail 2. Refer to attached drawing AD-2-E2. ADD Key Note 9 to polisher GFI receptacle in Detail 2. Refer to attached drawing AD-2-E2. ET-110: Partial Telecom Fourth Floor Plans REVISE existing data outlet location on north wall to be existing to remain in Detail 1. Refer to attached drawing AD-2-E3. DELETE demolition Note 2. Refer to attached drawing AD-2-E3. ADD existing data outlet location on north wall in Detail 2. Refer to attached drawing AD-2-E4. E-501: Electrical Schedules & Details REVISE panelboard schedule LPP-4-11 to reflect elimination of FCU-3 and elimination of branch circuit #9. Refer to attached drawing AD-2-E5. ****END OF POST BID BULLETIN**** Upson Hall Room 472 Laboratory Renovation Post Bid Bulletin No. 1 May 8, 2019 Page 5 REVISED BASE BID $ IN THE SPACE ABOVE, PROVIDE A REVISED BASE BID FOR THE ABOVE STATED MODIFICATIONS. Company Signature Printed Name and Title Date Attachments: AD-2-A1, AD-2-A2, AD-2-M1, AD-2-M2, AD-2-M3, AD-2-M4, AD-2-M5, AD-2-M6, AD-2-M7, AD-2-M8, AD-2-E1, AD-2-E2, AD-2-E3, AD-2-E4, AD-2-E5. 8REMOVE & SALVAGE EXIST WALL MOUNTED SHELVING. TURN OVER TO OWNER. PATCH REPAIR AND PREP EXIST GYP BD TO MATCH EXIST ADJACENT.15' - 0"2EXIST WALL MOUNTED SHELVING TO REMAINE8A-410713A-410A-410AD-2-A21EM SHOWERUTILITY TABLE (2'-6" x 5'-0")N.I.C.36375 SFGENERAL LAB472472A472B5B17BALIGN 2' - 7"+/-8' - 2 7/8"EXIST STATIC DISSIPATIVE RESILIENT FLOORING, TYPFH-2ACID CAB.FLAM. CAB.EXIST FAN COIL ACCESS PANELUTILITY TABLE (2'-6" x 5'-0")N.I.C.UTILITY TABLE (2'-6" x 5'-0")N.I.C.2EXIST SHELVES TO REMAINAD-2-A22These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©309 South Franklin Street Syracuse NY 13202315 488 5635 | syracuse@swbr.comFILE PATH:SWBR Project #Checked By:Project Manager:Drawn By:Issued With:Reference Sheet:5/8/2019 8:51:10 AMC:\1-Local Revit Models 2017\18695.00 Cornell Upson Hall Rm 472_yangs.rvt18695.00DMKSGeneral Lab Floorand Demolition PlanSDFYSAD-2-A1Cornell UniversityUpson Hall Room 472Laboratory Renovation124 Hoy Rd, Ithaca, NY14850Post Bid Bulletin No. 1A-110124 Hoy Rd, Ithaca, NY14850May 6, 2019 1/4" = 1'-0"1ROOM 472 DEMOLITION PLAN 1/4" = 1'-0"2PARTIAL ROOM 472 FLOOR PLAN 2' - 10"5B61' - 11"2' - 10"6' - 0"ACID CAB.FLAM. CAB.9' - 0"EXIST CABINETRY TO REMAINEXIST RACEWAY TO REMAINSIDE SPLASH2UTILITY TABLE (2'-6" x 5'-0") N.I.C.2' - 11"UTILITY TABLE (2'-6" x 5'-0") N.I.C.EXIST WALL-MOUNTED SHELVING TO REMAINEXIST FAN COIL ACCESS PANELEXIST WALL-MOUNTED SHELVING TO REMAIN2UTILITY TABLE (2'-6" x 5'-0") N.I.C.UTILITY TABLE (2'-6" x 5'-0") N.I.C.EXIST RACEWAY TO REMAINThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. ©309 South Franklin Street Syracuse NY 13202315 488 5635 | syracuse@swbr.comFILE PATH:SWBR Project #Checked By:Project Manager:Drawn By:Issued With:Reference Sheet:5/8/2019 8:51:11 AMC:\1-Local Revit Models 2017\18695.00 Cornell Upson Hall Rm 472_yangs.rvt18695.00DMKSGeneral LabElevationsSDFYSAD-2-A2Cornell UniversityUpson Hall Room 472Laboratory Renovation124 Hoy Rd, Ithaca, NY14850Post Bid Bulletin No. 1A-110 & A-410124 Hoy Rd, Ithaca, NY14850 1/4" = 1'-0"1GENERAL LAB - NORTH ELEVATIONMay 6, 2019 1/4" = 1'-0"2GENERAL LAB - WEST ELEVATION 375 SF GENERAL LAB 472 359 SF ATOMIZER ROOM 472B 121 SF LASER ROOM 472A 12x8SAEAV-2 SAV-1 EAV-3 RH-1 RH-3 RH-2 8x6 14x8 10x8 4ø 4ø 10x8 8ø 8x8 8x8 30x8 30x8 36x8 24x8 P P 10x86ø 10ø 24x12 30x8 VD VD VD VD VD VD VD VD 12x8S-2 12"ø 680 F/S S-1 8"ø 185 8x8R-1 8"ø 120 10x8 R-2 18x10 200 R-1 6"ø 140 R-1 8"ø 295 S-1 8"ø 165 S-1 8"ø 185 14x812x8 1 1 1 1 2 3 3 4 5 6 8 FCU-2 FCU-1 4ø 10 EXISTING FCU AD 11 6ø 4ø 4ø SVAV-1 EVAV-1 SVAV-2 EVAV-2 6ø T T T PROVIDE FIRE RATED INSULATION ON NEW EXHAUST DUCT. EXISTING FCU EXISTING FCU 14x8 10ø 10ø 8ø 2 2 2 2 These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 309 South Franklin Street Syracuse NY 13202 315 488 5635 | syracuse@swbr.com FILE PATH:SWBR Project # Checked By: Project Manager: Drawn By: Issued With: Reference Sheet: 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om5/7/2019 11:07:37 AMC:\Users\codyc\Documents\18695.00 Upson Hall_Rm 472_MEP_ChristopherWCody.rvt18695.00 AST PARTIAL MECHANICAL FLOOR PLAN SDF CWC AD-2-M1 Cornell University Upson Hall Room 472 Laboratory Renovation 124 Hoy Rd, Ithaca, NY 14850 ADDENDUM 2 M-110 124 Hoy Rd, Ithaca, NY 14850 SUPPLY AIR VALVE SCHEDULE UNIT TAG SERVE VALVE QTY. MOUNTING POSITION FACTORY OCCUPIED SET POINT UNOCCUPIED MAX INLET PRESSURE AT MAX CFM (IN. WC) INLET SIZE (IN.) RAD N.C. AT 1" S.P. 125 Hz DISC. N.C. AT 1" S.P. 125 Hz MANUFACTURER & MODEL NOTES MAX CFM MIN CFM MAX CFM MIN CFM MAX CFM MIN CFM SAV-1 GENERAL LAB 1 HORIZONTAL 1,056 120 680 315 680 120 0.3 10 51 60 ACCUTROL AVC6100 1,2,3,4 NOTES: 1. PROVIDE HIGH SPEED ELECTRIC ACTUATION. 2. UNIT TO BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS. 3. ACTUATOR TO FAIL NORMALLY CLOSED. 4. PROVIDE OPTION FOR TIGHT SHUT OFF. EXHAUST AIR VALVE SCHEDULE UNIT TAG SERVE VALVE QTY. MOUNTING POSITION FACTORY OCCUPIED SET POINT UNOCCUPIED MAX INLET PRESS AT MAX CFM IN. WC INLET SIZE (IN.) RAD N.C. AT 1" S.P. 125 Hz DISC. N.C. AT 1" S.P. 125 Hz MANUFACTURER & MODEL NOTES MAX CFM MIN CFM MAX CFM MIN CFM MAX CFM MIN CFM EAV-2 6' FUME HOOD 1 HORIZONTAL 1,056 120 780 120 780 120 0.3 10 51 62 ACCUTROL AVC6100 1,2,4,5 EAV-3 GENERAL LAB 1 HORIZONTAL 650 80 295 0 100 0 0.3 8 32 50 ACCUTROL AVC6100 1,3,4,5 NOTES: 1. UNIT TO BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS. 2. ACTUATOR TO FAIL NORMALLY OPEN. 3. ACUATOR TO FAIL NORMALLY CLOSED. 4. PROVIDE HIGH SPEED ELECTRIC ACTUATION. 5. ROVIDE OPTION FOR TIGHT SHUT OFF. FAN COIL UNIT SCHEDULE UNIT TAG LOCATION CFM SPEED MOTOR COOLING COIL 47°F E.W.T. MANUFACTURER & MODEL NOTES(QTY.) HP VOLTS/P H/HZ MCA TOTAL SENS.GPM ROWS P.D. FT. HD CHW dT E.A.T L.A.T. BTUH BTUH DB WB DB WB FCU-1 LASER ROOM 560 MED (1) 1/4 208/1/60 2 12,264 12,264 1.70 5 2.9 14 75.0 58.4 55.0 50.2 JOHNSON CONTROLS FHX-D09 1,2,3,4,5,6,7,8,11 FCU-2 ATOMIZER ROOM 1,825 MED (2) 1/3 208/1/60 6.75 40,823 40,823 5.70 6 6.8 14 75.0 58.4 54.5 49.9 JOHNSON CONTROLS FNX-20 1,2,3,4,5,6,9,10,11 NOTES: 1. MOTORS TO BE ELECTRICALLY COMMUTATED, BRUSHLESS DC-TYPE. 2. PROVIDE UNITS WITH FACOTRY MOUNTED DISCONNECT SWITCH. 3. PROVIDE UNITS WITH 1" THROWAWAY MERV 8 FILTER. 4. PROVIDE INTERNALLY INSULATED CABINET WITH 1/2" FIBERGLASS INSULATION AND INSULATION PACKAGE FOR COIL AND CONDENSATE PAN SECTION. 5. CONTROLS TO BE PROVIDED BY OTHERS. 6. PROVIDE STAINLESS STEEL EXTENDED DRAIN PAN AND INSTALL THE WHOLE CONTROL VALVE OVER THE PAN. 7. PROVIDE SUPPLY AND RETURN STAMPED LOUVER GRILLE. 8. PROVIDE BOTTOM RETURN. 9. PROVIDE DOUBLE DEFELCTION SUPPLY GRILLE. 10. PROVIDE REAR RETURN, WITH OPEN DUCT COLLAR. 11. PROVIDE CONDENSATE OVERFLOW SWITCH IN THE PRIMARY DRAIN PAN AND TIE ALARM INTO BMS. REGISTER, GRILL & DIFFUSER SCHEDULE UNIT TAG FACE SIZE FACE LOCATION MATERIAL FINISH USE MANUFACTURER & MODEL NOTES S-1 24x24 SEE PLAN STEEL BY ARCH. SUPPLY KRUEGER PLQ 1,2 S-2 24x48 SEE PLAN ALUMINUM BY ARCH. SUPPLY KRUEGER TAD 1,5 R-1 24x24 SEE PLAN STEEL BY ARCH. EXHAUST KRUEGER PLQ 1 R-2 18x10 SEE PLAN STEEL BY ARCH. EXHAUST KRUEGER S80 3,4 NOTES: 1. SEE PLANS FOR NECK SIZE. 2. VOLUME DAMPER TO BE INSTALLED ON ALL BRANCH DUCTS SERVING EACH SUPPLY DIFFUSER. 3. SURFACE MOUNT FRAME. 4. 35° HORIZONTAL BLADE SIDEWALL RETURN 5. 180° DISCHARGE AIR PATTERN VAV SUPPLY AIR TERMINAL UNITS UNIT TAG SERVE OCCUPIED CFM UNOCCUPIED CFM INLET SIZE FACTORY MAX. NC MIN. INLET PRESSURE (IN WC) MANUFACTURER & MODEL NOTESMAX CFM MIN CFM SVAV-1 LASER ROOM 165 95 4 400 45 29 0.30 PRICE SDV5 1,2,3,4 SVAV-2 ATOMIZER ROOM 370 150 6 550 65 22 0.30 PRICE SDV5 1,2,3,4 NOTES: 1. UNIT TO BE CONTROLLED BY VACANCY SENSOR . 2. CONTROLS TO BE SUPPLIED BY THE BACS CONTRACTOR. 3. UNIT TO BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS. 4. PROVIDE INTEGRAL AIR FLOW SENSOR. VAV EXHAUST AIR TERMINAL UNITS SCHEDULE UNIT TAG SERVE OCCUPIED CFM UNOCCUPIED CFM INLET SIZE FACTORY MAX. NC MIN. INLET PRESSURE (IN WC) MANUFACTURER & MODEL NOTESMAX CFM MIN CFM EVAV-1 LASER ROOM 140 70 4 400 45 29 1 PRICE SDEV5 1,2 EVAV-2 ATOMIZER ROOM 420 200 6 550 65 29 1 PRICE SDEV5 1,2 NOTES: 1. CONTROLS TO BE SUPPLIED BY THE BACS CONTRACTOR. 2. UNIT TO BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS. HOT WATER REHEAT COIL SCHEDULE UNIT TAG SERVE EAT (°F) LAT (°F)CFM MBH APD IN. H2O EWT (°F) LWT (°F)GPM WPD (FT. HD) WIDTH (IN) HEIGHT (IN) FACE VEL. (FPM) ROWS FINS/IN MANUFACTURER & MODEL RH-1 GENERAL LAB 55 75.7 680 15,421 0.16 130 88.5 0.74 0.60 24 9.0 453 2 10 DAIKIN RH-2 LASER ROOM 55 75.6 165 3,722 0.19 130 109.4 0.40 0.20 8 6.0 495 2 10 DAIKIN RH-3 ATOMIZER 55 80.1 370 8,774 0.17 130 99.9 0.60 0.30 12 9.0 427 2 12 DAIKIN 2 These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 309 South Franklin Street Syracuse NY 13202 315 488 5635 | syracuse@swbr.com FILE PATH:SWBR Project # Checked By: Project Manager: Drawn By: Issued With: Reference Sheet: 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om5/7/2019 11:07:37 AMC:\Users\codyc\Documents\18695.00 Upson Hall_Rm 472_MEP_ChristopherWCody.rvt18695.00 Checker MECHANICAL SCHEDULES SDF Author AD-2-M2 Cornell University Upson Hall Room 472 Laboratory Renovation 124 Hoy Rd, Ithaca, NY 14850 124 Hoy Rd, Ithaca, NY 14850 375 SF GENERAL LAB 472 359 SF ATOMIZER ROOM 472B 121 SF LASER ROOM 472A RH-1 RH-3 RH-2 FCU-1 1 1 2 P 1-1/4" PROCESS CHWR 1-1/4" PROCESS CHWS 3/4" CHWR 3/4" CHWS 1/2" RHHWR 1/2" RHHWS 1/2" RHHWR 1/2" RHHWS 1/2" RHHWS 1/2" RHHWR 1" CHWR 1" CHWS 1-1/4" CHWR 1-1/4" CHWS 5 4 1-1/4" PROCESS CHWR 1-1/4" PROCESS CHWS FCU-2 PIPE CHASE G 4" CHWS UP/DN 2" CHWR UP/DN 4" HWS UP/DN 2" HWR UP/DN 1" DR UP/DN P 2 These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 309 South Franklin Street Syracuse NY 13202 315 488 5635 | syracuse@swbr.com FILE PATH:SWBR Project # Checked By: Project Manager: Drawn By: Issued With: Reference Sheet: 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om5/7/2019 11:07:37 AMC:\Users\codyc\Documents\18695.00 Upson Hall_Rm 472_MEP_ChristopherWCody.rvt18695.00 Checker PARTIAL MECHANICAL PIPING FOURTH FLOOR PLAN SDF Author AD-2-M3 Cornell University Upson Hall Room 472 Laboratory Renovation 124 Hoy Rd, Ithaca, NY 14850 124 Hoy Rd, Ithaca, NY 14850 LASER ROOM POINTS LIST (427A) HARDWIRE POINTS SOFTWARE POINTS SHOWN ON GRAPHIC NOTESBI BO AI AO AV BV SCH TREND ALARM BACS EMCS DESCRIPTION SUPPLY AIR VAV BOX AIR FLOW FEEDBACK (CFM)X X X 10% FLOW DEVIATION FROM SETPOINT X BACnet MSTP NETWORK POINT SUPPLY AIR VAV BOX AIR FLOW SETPOINT (CFM)X X X BACnet MSTP NETWORK POINT SUPPLY AIR VAV BOX POSITION FEEDBACK (%)X X X VALVE COMMAND ≠ FEEDBACK X BACnet MSTP NETWORK POINT RE-HEAT COIL COMMAND (%)X X X 5°F DT ACROSS COIL WITH ELEC. REHEAT COMMANDED OFF X FAIL LAST RE-HEAT COIL LEAVING AIR TEMPERATURE X X X SINGLE POINT SENSOR EXHAUST VAV BOX AIR FLOW FEEDBACK (CFM)X X X 10% FLOW DEVIATION FROM SETPOINT X BACnet MSTP NETWORK POINT EXHAUST VAV BOX AIR FLOW SETPOINT (CFM)X X X BACnet MSTP NETWORK POINT EXHAUST VAV BOX POSITION FEEDBACK (%)X X X VALVE COMMAND ≠ FEEDBACK X BACnet MSTP NETWORK POINT ZONE TEMPERATURE SETPOINT, HEATING & COOLING X X ZONE TEMPERATURE SETPOINT TRIM (RNET)X X X RNET ZONE TEMPERATURE (RNET)X X X =+/-4°F FROM SETPOINT X FCU CLG. COIL. CONTROL VALVE POSITION COMMAND X X X NORMALLY CLOSED FCU FAN MOTOR SPEED X X X FCU STATUS X X FAILURE X VIA CURRENT SENSOR DISCHARGE AIR TEMP X X X SINGLE POINT SENSOR OCCUPANCY SENSOR X X X EMERGENCY VENTILATION OVERRIDE X X X ZONE RH (RNET)X X X X MONITOR AND ALARM ONLY ATOMIZER ROOM POINTS LIST (427B) HARDWIRE POINTS SOFTWARE POINTS SHOWN ON GRAPHIC NOTESBI BO AI AO AV BV SCH TREND ALARM BACS EMCS DESCRIPTION SUPPLY AIR VAV BOX AIR FLOW FEEDBACK (CFM)X X X 10% FLOW DEVIATION FROM SETPOINT X BACnet MSTP NETWORK POINT SUPPLY AIR VAV BOX AIR FLOW SETPOINT (CFM)X X X BACnet MSTP NETWORK POINT SUPPLY AIR VAV BOX POSITION FEEDBACK (%)X X X VALVE COMMAND ≠ FEEDBACK X BACnet MSTP NETWORK POINT RE-HEAT COIL COMMAND (%)X X X 5°F DT ACROSS COIL WITH ELEC. REHEAT COMMANDED OFF X FAIL LAST RE-HEAT COIL LEAVING AIR TEMPERATURE X X X SINGLE POINT SENSOR EXHAUST AIR VAV BOX AIR FLOW FEEDBACK (CFM)X X X 10% FLOW DEVIATION FROM SETPOINT X BACnet MSTP NETWORK POINT EXHAUST AIR VAV BOX AIR FLOW SETPOINT (CFM)X X X BACnet MSTP NETWORK POINT EXHAUST AIR VAV BOX POSITION FEEDBACK (%)X X X VALVE COMMAND ≠ FEEDBACK X BACnet MSTP NETWORK POINT ZONE TEMPERATURE SETPOINT, HEATING & COOLING X X ZONE TEMPERATURE SETPOINT TRIM (RNET)X X X RNET ZONE TEMPERATURE (RNET)X X X =+/-4°F FROM SETPOINT X FCU CLG. COIL. CONTROL VALVE POSITION COMMAND X X X NORMALLY CLOSED FCU FAN MOTOR SPEED X X X FCU STATUS X X FAILURE X VIA CURRENT SENSOR FCU DISCHARGE AIR TEMP X X X SINGLE POINT SENSOR OCCUPANCY SENSOR X X X EXISTING FAN COIL HOT WATER VALVE X X X SPLIT RANGE W/ NEW FCU EXISTING FAN COIL CHILLED WATER VALVE X X X SPLIT RANGE W/ NEW FCU EMERGENCY VENTILATION OVERRIDE X X X ZONE RH (RNET)X X X X MONITOR AND ALARM ONLY 2 These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 309 South Franklin Street Syracuse NY 13202 315 488 5635 | syracuse@swbr.com FILE PATH:SWBR Project # Checked By: Project Manager: Drawn By: Issued With: Reference Sheet: 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om5/7/2019 11:07:37 AMC:\Users\codyc\Documents\18695.00 Upson Hall_Rm 472_MEP_ChristopherWCody.rvt18695.00 Checker CONTROLS SCHEMATIC ROOM 472A & B SDF Author AD-2-M4 Cornell University Upson Hall Room 472 Laboratory Renovation 124 Hoy Rd, Ithaca, NY 14850 124 Hoy Rd, Ithaca, NY 14850 EXHAUST SAV-1 T RH-1SUPPLY AIR FROM MAU SAT SUMMER = 55 F SAT WINTER = 68 F ΔP EAV-3 6' FUME HOOD EXHAUST ΔP EAV-2 FUME HOOD MONITOR ΔP OS BI GENERAL LAB 472VO BI PUSH-BUTTON EMERGENCY VENTILATION OVERRIDE AI AO F.L. N.C. ANALOG ELECTRICL CONTROL AI FLOW AI ALARM MOD AO SETPOINT ANALOG ELECTRICL CONTROL AI FLOW AI ALARM MOD AO SETPOINT T AV SETPOINT SA D COMBO SENSOR (RNET) RH D AV HEATING COILM AO EXISTING FCU-EX-1 T AI COOLING COILAO CHWS CHWR HWS HWR ECM AOBI FLP FLP FLP AI FLOW AI ALARM R BO OCCUPIED/ UNOCCUPIED COMMAND R BO DECOMMISSION FHV ANALOG ELECTRICAL CONTROL WITH HOOD INTERFACE CARD AI SASH POSITION RNET AO BIBIAOAO AI SASH POSITION HORIZONTAL SENSOR AI AO AO VERTICAL SASH POSITION SENSOR FACTORY SUPPLIED CABLE 2 These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 309 South Franklin Street Syracuse NY 13202 315 488 5635 | syracuse@swbr.com FILE PATH:SWBR Project # Checked By: Project Manager: Drawn By: Issued With: Reference Sheet: 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om5/7/2019 11:14:34 AMC:\Users\codyc\Documents\18695.00 Upson Hall_Rm 472_MEP_ChristopherWCody.rvt18695.00 Checker CONTROLS SCHEMATIC ROOM 472 SDF Author AD-2-M5 Cornell University Upson Hall Room 472 Laboratory Renovation 124 Hoy Rd, Ithaca, NY 14850 124 Hoy Rd, Ithaca, NY 14850 LABORATORY AIR FLOW SCHEDULE DESCRIPTION ROOM DIMENSIONS CODE MINIMUM VENTILATION EXHAUST AIR SUPPLY AIR XFER AREA HEIGHT VOLUME NYS OUTDOOR AIR NYS EXHAUST AIR EXHAUST POINT VALVE SIZE VALVE RANGE OCCUPIED SASH OPEN OCCUPIED SASH CLOSED UNOCCUPIED SASH FULL (100 FPM) UNOCCUPIED SASH OPEN (65 FPM) UNOCCUPIED SASH CLOSED SUPPLY POINT VALVE SIZE VALVE RANGE OCCUPIED SASH OPEN OCCUPIED SASH CLOSED UNOCCUPIED SASH FULL UNOCCUPIED SASH OPEN UNOCCUPIED SASH CLOSED ALL MODES MIN MAX 100 FPM 80 FPM MIN MAX 100 FPM 80 FPM (FT2)(FT)(FT3)(CFM) (ACH) (CFM) (ACH)(CFM) (CFM) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) GENERAL LAB 375 11 4,125 210 3.1 375 5.5 11.3 9.1 6.0 11.3 7.3 3.2 SAV-1 10 120 1056 680 525 315 680 405 120 -100 EAV-2 (6' FH) 10 120 1,056 780 625 120 780 505 120 EAV-3 (GEX) 8 80 650 0 0 295 0 0 100 TOTAL 780 625 415 780 505 220 LABORATORY AIR FLOW SCHEDULE DESCRIPTION ROOM DIMENSIONS CODE MINIMUM VENTILATION EXHAUST AIR SUPPLY AIR XFER AREA HEIGHT VOLUME NYS OUTDOOR AIR NYS EXHAUST AIR EXHAUST POINT VALVE SIZE VALVE RANGE OCCUPIED SASH OPEN OCCUPIED SASH CLOSED UNOCCUPIED SASH FULL (100 FPM) UNOCCUPIED SASH OPEN (65 FPM) UNOCCUPIED SASH CLOSED SUPPLY POINT VALVE SIZE VALVE RANGE OCCUPIED SASH OPEN OCCUPIED SASH CLOSED UNOCCUPIED SASH FULL UNOCCUPIED SASH OPEN UNOCCUPIED SASH CLOSED ALL MODES MIN MAX 100 FPM 80 FPM MIN MAX 100 FPM 80 FPM (FT2)(FT)(FT3)(CFM) (ACH) (CFM) (ACH)(CFM) (CFM) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (ACH) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) (CFM) GENERAL LAB 375 11 4,125 210 3.1 375 5.5 11.3 9.1 6.0 11.3 7.3 3.2 SAV-1 10 120 1056 680 525 315 680 405 120 -100 EAV-2 (6' FH) 10 120 1,056 780 625 120 780 505 120 EAV-3 (GEX) 8 80 650 0 0 295 0 0 100 TOTAL 780 625 415 780 505 220 These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 309 South Franklin Street Syracuse NY 13202 315 488 5635 | syracuse@swbr.com FILE PATH:SWBR Project # Checked By: Project Manager: Drawn By: Issued With: Reference Sheet: 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om5/7/2019 11:07:38 AMC:\Users\codyc\Documents\18695.00 Upson Hall_Rm 472_MEP_ChristopherWCody.rvt18695.00 Checker CONTROLS SCHEMATIC ROOM 472 SDF Author AD-2-M6 Cornell University Upson Hall Room 472 Laboratory Renovation 124 Hoy Rd, Ithaca, NY 14850 124 Hoy Rd, Ithaca, NY 14850 2 GENERAL LAB POINTS LIST (472) HIGH HOOD DENSITY TRACKING LABORATORY HARDWIRE POINTS SOFTWARE POINTS SHOWN ON GRAPHIC NOTESBI BO AI AO AV BV SCH TREND ALARM BACS EMCS DESCRIPTION TOTAL EXHAUST AIRFLOW (CFM)X X X TOTAL EXHAUST AIR SETPOINT (CFM)X X X LABORATORY AIR CHANGE RATE (ACPH)X X ROOM AREA (SQUARE FEET)X X ROOM CEILING HEIGHT (FEET)X X FLOW OFFSET SETPOINT (CFM)X X FLOW OFFSET ACTUAL (CFM)X X SPACE TEMPERATURE SETPOINT, HEATING X X SPACE TEMPERATURE SETPOINT, COOLING X X SPACE TEMPERATURE (RNET)X X X =+/-4°F FROM SETPOINT X SPACE SETPOINT ADJUSTMENT (RNET)X X SPACE OCCUPANCY, MINIMUM OCCUPANCY SETPOINT X X SPACE OCCUPANCY X X X EMERGENCY VENTILATION OVERRIDE X X X ALARM ON OVERRIDE CONDITION X EAV-2 (6' FUME HOOD) FUME HOOD EXHAUST VALVE FLOW FEEDBACK (CFM)X X X FUME HOOD EXHAUST AIR VALVE STATUS X X VALVE COMMAND ≠ FEEDBACK (JAM)X DUA-STATE ALARM X LOW DIFFERENTIAL PRESSURE (VIA SWITCH)X SPACE OCCUPANCY, MINIMUM OCCUPANCY SETPOINT X X SPACE OCCUPANCY X X X DECOMMISSIONING COMMAND X X X FUME HOOD SASH POSITION - COMBINATION (HORIZONTAL/VERTICAL)X X X SASH OPEN (18") FOR 24 CONTINUOUS HOURS OR MORE X SAV-1 SUPPLY AIR VALVE FLOW FEEDBACK (CFM) X X X SUPPLY AIR VALVE STATUS X X 10% FLOW DEVIATION FROM SETPOINT X TRI-STATE ALARMXVALVE COMMAND ≠ FEEDBACK (JAM)X X LOW DIFFERENTIAL PRESSURE (VIA SWITCH)X SUPPLY AIR VALVE POSITION COMMAND (CFM) X X X SUPPLY AIR VALVE MINIMUM AIRFLOW SETPOINT (CFM)X X SUPPLY AIR VALVE MAXIMUM AIRFLOW SETPOINT (CFM)X X EAV-3 GENERAL EXHAUST AIR VALVE POSITION COMMAND (CFM)X X X GENERAL EXHAUST AIR VALVE MINIMUM AIRFLOW SETPOINT (CFM)X X GENERAL EXHAUST AIR VALVE MAXIMUM AIRFLOW SETPOINT (CFM)X X GENERAL EXHAUST AIR VALVE FLOW FEEDBACK (CFM)X X X GENERAL EXHAUST AIR VALVE STATUS X X 10% FLOW DEVIATION FROM SETPOINT X TRI-STATE ALARMXVALVE COMMAND = FEEDBACK (JAM)X X LOW DIFFERENTIAL PRESSURE (VIA SWITCH)X RH-1 RE-HEAT COIL LEAVING AIR TEMPERATURE X X X SINGLE POINT SENSOR RE-HEAT COIL LEAVING AIR TEMPERATURE HIGH LIMIT X X X SINGLE POINT SENSOR SPACE TEMPERATURE SETPOINT X X X HEATING COIL VALVE POSITION X X X 5°F ΔT ACROSS COIL WITH VALVE COMMANDED CLOSED X FAIL FAST EXISTING FAN COIL UNIT HOT WATER COIL VALVE POSITION X X X CHILLED WATER COIL VALVE POSITION X X X FAN COIL LEAVING AIR TEMPERATURE X X X SINGLE POINT SENSOR FAN SPEED COMMAND X X X FAN STATUS FEEDBACK X X X 2 These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 309 South Franklin Street Syracuse NY 13202 315 488 5635 | syracuse@swbr.com FILE PATH:SWBR Project # Checked By: Project Manager: Drawn By: Issued With: Reference Sheet: 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om5/7/2019 11:07:38 AMC:\Users\codyc\Documents\18695.00 Upson Hall_Rm 472_MEP_ChristopherWCody.rvt18695.00 Checker CONTROLS POINTS LIST ROOM 472 SDF Author AD-2-M7 Cornell University Upson Hall Room 472 Laboratory Renovation 124 Hoy Rd, Ithaca, NY 14850 124 Hoy Rd, Ithaca, NY 14850 375 SF GENERAL LAB 472 359 SF ATOMIZER ROOM 472B 121 SF LASER ROOM 472A A A 1"CW 1"HW 3/4"HWC FCU-1 FCU-2 3/4" CD 3/4" CD 3/4" CD PROVIDE INDIRECT CD CONNECTION TO SANITARY 2 These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR. All rights reserved. © 309 South Franklin Street Syracuse NY 13202 315 488 5635 | syracuse@swbr.com FILE PATH:SWBR Project # Checked By: Project Manager: Drawn By: Issued With: Reference Sheet: 145 Culver Road, Suite 200 Rochester, NY 14620 [T] 585.427.8888 [F] 585.427.8914 www.erdmananthony.om5/7/2019 11:07:38 AMC:\Users\codyc\Documents\18695.00 Upson Hall_Rm 472_MEP_ChristopherWCody.rvt18695.00 Checker PARTIAL PLUMBING FOURTH FLOOR PLAN SDF Author AD-2-M8 Cornell University Upson Hall Room 472 Laboratory Renovation 124 Hoy Rd, Ithaca, NY 14850 124 Hoy Rd, Ithaca, NY 14850 NEW WORK KEY NOTES 1. PROVIDE 1/2" CA TO FUME HOOD. 2. NOT USED. 3. PROVIDE 1/2" CW(F) TO POLISHER 4. CONNECT 3/4" CW TO EXISTING PIPING UNDER SINK. PROVIDE WATER FILTER WF-1 AND CONNECT TO NEW EQUIPMENT. 5. PROVIDE 3/4" CW AND 3/4" HW TO NEW MIXING VALVE MV-1 FROM EXISTING TAPS. 6. PROVIDE 1" TW TO EMERGENCY SHOWER ES-1. PROPERLY SUPPORT PIPING AND FIXTURE AND COORDINATE INSTALLATION OF PULL HANDLE TO ENSURE OPERATION. 7. PROVIDE 1 1/2" DRAIN FROM POLISHER. CONNECT TO NEW 2" DRAIN FROM FUMEHOOD. PROVIDE CHEMICAL RESISTANT T- STRAINER IN AN ACCESSIABLE LOCATION. MCMASTER-CARR # 8680T18 BASIS OF DESIGN. 8. PROVIDE 1/2" ARGON PIPING FROM REGULATOR ASSEMBLY TO TOOL CONNECTION. COORDINATE PIPE ROUTE WITH FINAL EQUIPMENT LOCATION. 9. PROVIDE 1/2" CA FROM EXISTING SERVICE TO SUPPLY CONNECTIONS AT FUME HOODS. ROUTE PIPING THROUGH EXISTING CABINETS. 10. NOT USED. 11. PROVIDE 3/4" CONDENSATE DRAIN FROM FAN COIL. PROVIDE INDIRECT CONNECTION TO EXISTING SANITARY DRAIN. # 1 4 7 6 P PES-1 3 8 8 8 P 9 P 8 10 11 2 2 (ETR) (ETR) WIREMOLD 1 (ETR) 2 309 South Franklin Street Syracuse NY 13202 315 488 5635 | syracuse@swbr.com These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR Architecture, Engineering & Landscape Architecture, D.P.C. and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR Architecture, Engineering & Landscape Architecture, D.P.C. All rights reserved. ©FILE PATH:SWBR Project # Checked By: Project Manager: Drawn By: Issued With: Reference Sheet:5/6/2019 4:14:07 PMC:\Users\uerzd\Documents\18695.00 Upson Hall_Rm 472_MEP_UerzD.rvt18695.00 BRW PARTIAL DEMOLITION POWER PLAN SDF DU AD-2-E1 Cornell University Upson Hall Room 472 Laboratory Renovation 124 Hoy Rd, Ithaca, NY 14850 ADDENDUM 2 EP-110 124 Hoy Rd, Ithaca, NY 14850 1/4" = 1'-0" 1 ROOM 472 DEMOLITION PLAN - POWER 375 SF GENERAL LAB 472 121 SF LASER ROOM 472A 6-FOOT FUME HOOD (ETR) (ETR) GLOVE BOX POLISHER GFI 20-LPP-4-11 21-LPP-4-11 A B A B 3-LPP-4-11 OPENSLM-EX WORKSTATION J J J J J J J FCU-1 SVAV-2 SVAV-1 EAV-3 SAV-1 EAV-2 RH-1 RH-2 RH-3 2-LPP-4-11 4-LPP-4-11 T 5-LPP-4-11 T T 6-LPP-4-11 17,19-LPP-4-11 10 11 12 12 1-LPP-4-11 13 22,24-LPP-4-11 LASER SAFETY SYSTEM 12-LPP-4-11 2 2 2 4 HP 7 7 2#12, 1#12 GND., 3/4"C WIREMOLD (ETR) 9 2 2 309 South Franklin Street Syracuse NY 13202 315 488 5635 | syracuse@swbr.com These documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR Architecture, Engineering & Landscape Architecture, D.P.C. and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR Architecture, Engineering & Landscape Architecture, D.P.C. All rights reserved. ©FILE PATH:SWBR Project # Checked By: Project Manager: Drawn By: Issued With: Reference Sheet:5/6/2019 4:14:07 PMC:\Users\uerzd\Documents\18695.00 Upson Hall_Rm 472_MEP_UerzD.rvt18695.00 BRW PARTIAL NEW WORK POWER PLAN SDF DU AD-2-E2 Cornell University Upson Hall Room 472 Laboratory Renovation 124 Hoy Rd, Ithaca, NY 14850 ADDENDUM 2 EP-110 124 Hoy Rd, Ithaca, NY 14850 1/4" = 1'-0" 2 ROOM 472 NEW WORK PLAN - POWER KEY NOTES (CONT.): 9.REPLACE EXISTING DUPLEX RECEPTACLE WITH GFI TYPE DUPLEX RECEPTACLE IN EXISTING RACEWAY. PROVIDE DEDICATED CIRCUIT BACK TO PANELBOARD INDICATED. # 2 W(ETR)421(ETR)2309 South Franklin Street Syracuse NY 13202315 488 5635 | syracuse@swbr.comThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR Architecture, Engineering & Landscape Architecture, D.P.C. and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR Architecture, Engineering & Landscape Architecture, D.P.C. All rights reserved. ©FILE PATH:SWBR Project #Checked By:Project Manager:Drawn By:Issued With:Reference Sheet:5/6/2019 4:14:07 PMC:\Users\uerzd\Documents\18695.00 Upson Hall_Rm 472_MEP_UerzD.rvt18695.00BRWPARTIALDEMOLITIONTELECOM PLANSDFDUAD-2-E3Cornell UniversityUpson Hall Room 472Laboratory Renovation124 Hoy Rd, Ithaca, NY14850ADDENDUM 2ET-110124 Hoy Rd, Ithaca, NY14850 1/4" = 1'-0"1ROOM 472 DEMOLITION PLAN - TELECOM#DEMOLITION KEY NOTES1. DISCONNECT AND REMOVE EXISTING WIRELESS ACCESS POINT DATA CABLE AND ASSOCIATED RACEWAY BACK TO NEAREST NON-AFFECTED AREA TO ACCOMMODATE ROOM RENOVATIONS. SAVE AND PROTECT DATA CABLE AND RACEWAY FOR REUSE. REMOVAL OF WIRELESS ACCESS POINT SHALL BE BY CORNELL CIT.2 375 SFGENERAL LAB472359 SFATOMIZER ROOM472B121 SFLASER ROOM472AW4(ETR)4(ETR)(ETR)214(ETR)2309 South Franklin Street Syracuse NY 13202315 488 5635 | syracuse@swbr.comThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR Architecture, Engineering & Landscape Architecture, D.P.C. and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR Architecture, Engineering & Landscape Architecture, D.P.C. All rights reserved. ©FILE PATH:SWBR Project #Checked By:Project Manager:Drawn By:Issued With:Reference Sheet:5/6/2019 4:14:07 PMC:\Users\uerzd\Documents\18695.00 Upson Hall_Rm 472_MEP_UerzD.rvt18695.00BRWPARTIAL NEWWORK TELECOMPLANSDFDUAD-2-E4Cornell UniversityUpson Hall Room 472Laboratory Renovation124 Hoy Rd, Ithaca, NY14850ADDENDUM 2ET-110124 Hoy Rd, Ithaca, NY14850 1/4" = 1'-0"2ROOM 472 NEW WORK PLAN - TELECOM EXISTING PANELBOARD LPP-4-11LOCATION: CORRIDORMAIN BUS AMPS: 100ASERVICE VOLTAGE: 208Y/120V, 3PH, 4WMAIN CIRCUIT BREAKER: NONEMOUNTING: RECESSEDFEEDER SIZE: EXISTING TO REMAINFEED: LPP-4-2_2FEED THRU LUGS: NONES.C. RATING:DESCRIPTIONPHASE AMPSTRIPPOLESTRIPPHASE AMPSDESCRIPTIONPH A PH B PH CAMPS AMPSPH A PH B PH CREC-GLOVE BOX- GEN. LAB 47210.0 20A/1P 1 2 20A/1P 6.0 REC-OPENSLM-EX-ATOMIZER 472BREC-POLISHER- GEN. LAB 4725.5 20A/1P 3420A/1P 6.0 REC-OPENSLM-EX-ATOMIZER 472BEAV/SAV/RH/FCU CONTROL TX. 0.0 20A/1P 5 6 20A/1P 0.0 SPAREREC-ATOMIZER 472B 4.5 20A/1P78 20A/1P 3.0QUAD REC-ATOMIZER 472BSPARE 0.0 20A/1P 9 10 20A/1P 6.0 REC-RACEWAY-LASER RM 472AREC-RACEWAY-LASER RM 472A 6.0 20A/1P11 1220A/1P 3.0 REC.-LASER RM 472AREC-GEN. LAB 472 3.0 20A/1P 131420A/1P 4.5 REC-ATOMIZER 472BREC-HEAT EXG-ATOMIZER 472 8.0 20A/1P 15 16 30A/2P 30.0ATOMIZER FURNACE CHAMBERFCU-1,29.0 20A/2P 17 18 -- 30.09.0 -- 19 20 20A/1P 3.0 REC-FUME HOOD-GEN. LAB 472REC-FUME HOOD-GEN. LAB 472 3.0 20A/1P21 2220A/2P 9.0YTTERBIUM LASER - LASER RM 472ANd:YAG LASER - LASER RM 472A9.0 20A/2P 2324 --9.09.0--25 26 20A/2P 9.0OPENSLM-EX LASER-ATOMIZER 472BSPARE20A/1P 27 28 -- 9.0SPARE20A/1P 29 30 20A/1P 0.0 SPARESPARE 0.0 20A/1P 31 32 20A/1P 0.0SPARESPARE 0.0 20A/1P 33 34 20A/1P 0.0 SPARESPARE0.0 20A/1P 35 36 20A/1P 0.0 SPARESPARE 0.0 20A/1P 37 38 20A/1P 0.0SPARESPARE 0.0 20A/1P 39 40 20A/1P 0.0 SPARESPARE0.0 20A/1P41 4220A/1P 0.0 SPARE35.5 16.5 24.0SUBTOTAL (AMPS)25.5 60.0 42.0PH. A PH. BPH.CTOTAL PHASE AMPS 61.00 76.50 66.00 NOTES:TOTAL PHASE kVA 7.32 9.18 7.92TOTAL 3-PHASE kVA 24.42TOTAL DEMAND 3-PHASE kVA 17.09TOTAL DEMAND 3-PHASE AMPS 47.50309 South Franklin Street Syracuse NY 13202315 488 5635 | syracuse@swbr.comThese documents and all the ideas, arrangements, designs and plans indicated thereon or presented thereby are owned by and remain the property of SWBR Architecture, Engineering & Landscape Architecture, D.P.C. and no part thereof shall be utilized by any person, firm, or corporation for any purpose whatsoever except with the specific written permission of SWBR Architecture, Engineering & Landscape Architecture, D.P.C. All rights reserved. ©FILE PATH:SWBR Project #Checked By:Project Manager:Drawn By:Issued With:Reference Sheet:5/6/2019 4:14:08 PMC:\Users\uerzd\Documents\18695.00 Upson Hall_Rm 472_MEP_UerzD.rvt18695.00BRWELECTRICALSCHEDULESSDFDUAD-2-E5Cornell UniversityUpson Hall Room 472Laboratory Renovation124 Hoy Rd, Ithaca, NY14850ADDENDUM 2E-501124 Hoy Rd, Ithaca, NY1485022