Loading...
HomeMy WebLinkAboutKennedy Fire Protection- 7-16-15STONE QUARRY APARTMENTS BUILDING "A" SPENCER ROAD ITHACA, NY 14850 FIRE PROTECTION PLANS DISTANCE FROM SIDEWALL SPRINKLER TO SIDE OF OBSTRUCTION (A) MAXIMUM ALLOWABLE DISTANCE OF DEFLECTOR ABOVE BOTTOM OF OBSTRUCTION -INCHES - (B) LESS THAN 8' NOT ALLOWED 8' TO LESS THAN 10 1" 10' TO LESS THAN 11' 2" 11' TO LESS THAN 12' 3" 12' TO LESS THAN 13' 4" 13' TO LESS THAN 14' 6" 14' TO LESS THAN 15' 7" 15' TO LESS THAN 16' 9" 16' TO LESS THAN 17' 11" 17' OR GREATER 14" CEILING SIDEWALL SPRINKLERS 13'-0" OR GREATER FROM EDGE OF SOFFITS TO HAVE DEFLECTOR 6" DOWN FROM THE CEILING. SIDEWALL SPRINKLERS CLOSER THAN 13'-0" FROM EDGE OF SOFFITS TO HAVE DEFLECTOR 12" DOWN FROM THE CEILING. HSW w/ SEMI-REC PLATE min. 12" max. HSW SEE SPRINKLER SCHEDULE W/ SEMI-REC PLATE 1" CPVC STANDOFF HANGER PIPE 1" CPVC 1 xli" CPVC ELBOW Ceiling 1" CPVC STANDOFF HANGER 1" CPVC- OPEN WEB FLOOR TRUSS FIRE STOP 2ND FLOOR PENETRATI❑N HSW w/ SEMI-REC PLATE 2nd Floor 9'-5 1" CPVC Pipe HSW w/ SEMI-REC PLATE CPVC BRANCH LINE x1¢" CPVC Spigot ead Adapter 1" CPVC Pipe f CEILING HSW SEE SPRINKLER S W/ SEMI -RC PLATE HEDULE 1xJx1" CPVC TEE CPVC Spigot ad Adapter 2x4 WALL WITH RESILIENT CHANNEL DN DNE SIDE 1x15x1" CPVC TEE 2x4 WALL WITH RESILIENT CHANNEL DN DNE SIDE FIN FLOOR 0'-0" Typical U & Dn to Sprin NTS <lers HSW w/ SEMI-REC PLATE 1" CPVC Pipe HSW w/ SEMI-REC PLATE 1" CPVC Pipe 1" CPVC TEE 1" CPVC TEE 2x4 WALL 2x4 WALL HARDENED HEX HEAD SELF THREADING SCREW TYPE 1 — FOR 1" AND 1-1/4" PIPE AND HANGER TYPE 2 — FOR 1-1/2" AND 2" PIPE AND HANGER TO RESTRAIN THE UPWARD MOVEMENT OF PIPE AS IT OCCURS DURING SPRINKLER HEAD ACTIVATION AS REQUIRED. SHALL BE LOCATED AT END HEADS WITHIN 24" FROM DROP TO PENDENT HEAD SURGE RESTRAINER FOR STEEL OR CPVC PLASTIC PIPE NTS MAXIMUM DISTANCE BETWEEN HANGERS NOMINAL PIPE SIZE (in.) 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 3-1/2" 4" 5" 6" 8" STEEL PIPE EXCEPT THREADED LIGHTWALL N/A 12-0 12-0 15-0 15-0 15-0 15-0 15-0 15-0 15-0 15-0 15-0 THREADED LIGHTWALL STEEL PIPE N/A 12-0 12-0 12-0 12-0 12-0 12-0 N/A N/A N/A N/A N/A CPVC PIPE 5-6 6-0 6-6 7-0 8-0 9-0 10-0 N/A N/A N/A N/A N/A HARDENED HEX HEAD SELF THREADING SCREW Sammy GST -20-" for Wood TYPICAL NO s /-3/8" All Thread Rod Adjustable Swivel Ring HANGER SCALE HARDENED HEX HEAD SELF THREADING SCREW SIDE MOUNT CPVC DOUBLE FASTENER STRAP TYPE HANGER CPVC HANGER TYPICAL NO Sammy Sidewinder SWG-20 for Wood 3/8" All Thread Rod Adjustable Swivel Ring HANGER SCALE DRAW \G LIST COVES S-EETAND SITE PLA\ FIRST F_003 - SECO\D =LOOR- T-IRD FLOOR - FP -00. FP -ICC rp-O. FP -102 1 "x0-2 RISER NIPPLE 1 "x VARIES SEE PLAN BRANCHLINE 1"x VARIES SEE PLAN LAY -IN CEILING PENDENT Y" 155° WHITE w/ TILE SEMI REC. ESCUTCHEON TY D CA AR IV OV -R S 0\ N.T.S. Lb, _5ECONll_FLOOR_ 'Li 209' - 4 3/4" 20 2" GRV CPVC ADAPTER 2" 3x2 GRV R.C. 1Y4" MAIN DRAIN PIPED TO EXTERIOR THROUGH CHASE AT LAUNDRY MACHINES 3" TO FIRE DEPT CONNECTION ROUTE THROUGH CHASE AT LAUNDRY MACHINES EIR TELQQF3 !J 200' - 0" FLOW SWITCH w/ RETARD MI 0 INSPECTOR'S TEST CONNECTION WITH SIGHT GLASS AND X" ORIFICE, CONNECT TO MAIN DRAIN PIPING TO FLOOR DRAIN 0-300 GAUGE ON Y4" 3—WAY VALVE SPARE SPRINKLER HEAD CABINET 3" CHECK VALVE 3" BUTTERFLY 4" WATTS 757 VALVE w/ TAMPER / DOUBLE CHECK ASSY M73l EIM 4" GATE VALVE W/ TAMPER CHASE 3" TO FDC SPRINKLER RISER SECTION Scale: 1/2"=1'-0" Hydrant 1F1("VV. ']C'cs]It :I[. I[] fg I"lroje(.-t 60(P b]Loclk:. Spe„r]Ir_er [Load Project: .N o. L�o�calti(:111r: Spencer amid .Elt l]Iliral I:I:I:Ii:I.lLI(:i:::liI .Eal:y: ''.ir:c►til. (::iiI:;:)i.►, Slle,:ljje,sti. Da.te: ecrvexnbelr 6, 2.01 ,4. T'irrre. :8: SI. al. S]lce:lbcti: Pressure {:.uul,;edl 1I31.3rldl]I i1L1ILlt 1eulrrlber: G-053 Location: (L..QI ;I I3 :nlcer 12.oardl E I attic Ps:76 psi siidilLlal, 11IF;, 60 psi 11?'lba►liri lE�lcll ]1]I.;5411.II alrult 1eo:Tiber: (1-381 .UL..a'Ial(D;n: 7(11 Spencer er l:Wad How, c:11- 1,160 gj irri 2,2:82 gpirri Clale* s, 1SC II,-lOr10llrr(.',r1tE: c.94 ...1 '16O to �� (2,1Ft' (2T /(Is --2A) �1�(, 7IJIats' aat Te t .IEZesill.ual IPxr.;,s I:r 1'T2.- 1;71r r1 1220 ca]lcuBlat d 11) 111s:i cesirlu,a1 gpni I low ll_¢:est Result iia) test 1es1idi1. l[ i ]:lIrnr 71'x(20) ---- Icaalec1 l':esirhz.il l'"reps Iain, ld-(2(II) psi �l1 T is' 7 E t IIeSic uairl Pre.S ,u1 a 71'1...psii 13s --- Pre -flow test static.: 6x4 REDUCER SITE DRAWING IS FOR REFERENCE ONLY IN FOLLOWING HYDRAULIC NODES BACK TO SOURCE...DRAWING IS NOT TO SCALE... 6" SPENCER ROAD 1 1 8x6 REDUCER @.)SITE PLAN Scale: N.T.S. Scale: 0 00 FLOW TEST STATIC 76 PSI RESIDUAL 60 PSI FLOW 1160 GPM DATE 11/06/2014 TIME 8:15 AM BY ITHACA WATER 20 PSI © 2282 GPM PER THE STRUCTURAL PLANS, THIS BUILDING IS A SEISMIC DESIGN CLASS "B” AND DOES NOT REQUIRE THE SPRINKLER SYSTEM TO BE BRACED FOR EARTHQUAKES. • SPRINKLERS ARE NOT REQUIRED IN RESIDENTIAL CLOSETS UNDER 24 SQ.FT. w/ LEAST DIMENSION NOT EXCEEDING 3 FT. PER NFPA 13R, 2007 ED. • SPRINKLERS ARE NOT REQUIRED IN RESIDENTIAL BATHROOMS UNDER 55 SQ.FT. PER NFPA 13R, 2007 ED. [ 7-1 ] Centerline of Pipe Above FLoor Hydraulic Reference Point Center Line +12'-6" Pipe Above Finished Floor Hanger �xx Cap Plug D Rise Up or Down/ Elev. Change System Riser 0 Grooved Coupling 0 Rise Up or Down/ Elev. Change Threaded Piping Grooved Piping CPVC Pipe OS&Y Gate Valve (OS&Y) Check Valve Flow Switch (FS) 24v Electric Horn Strobe 5" Storz Fire Dept. Conn. SYvB0L -G- \D NTS SPRIN <LER EAD SPACING: RESIDENTIAL SIDEWALLS — MIN. 8'-0" BETWEEN HEADS — MAX. 16'-0" BETWEEN HEADS — MAX. 8'-0" HEADS FROM WALLS — MAX. 20'-0" SPRAY DISTANCE STANDARD COVERAGE QR PENDENTS — MIN. 6'-0" BETWEEN HEADS — MAX. 15'-0" BETWEEN HEADS — MAX. 7'-6" HEADS FROM WALLS — MAX. 130 SQ.FT. COVERAGE IN ORDINARY HAZARD — MAX. 210 SQ.FT. COVERAGE IN LIGHT HAZARD GE 1. \ESA SP PIN K \ 0 ES: ALL WORK TO BE IN ACCORDANCE WITH NFPA 13R 2007 ED, NYS FIRE CODE, AND LOCAL ORDINANCES. 2. ALL CONCEALED PIPE TO BE CPVC WITH CPVC FITTINGS 3. ALL WELDED PIPE TO BE BLACK STEEL PIPE MEETING ASTM A-795 WITH WELDED OUTLETS & GROOVED FITTINGS 4. ALL THREADED PIPE TO BE BLACK STEEL PIPE MEETING ASTM A-135 WITH THREADED DUCTILE IRON FITTINGS 5. ALL WIRING OF ELECTRICAL DEVICES IS BY OTHERS - ALL CONTROL VALVES AND FLOW SWITCH TO BE CONNECTED TO ALARM SYSTEM 6. ALL PIPE IS SIZED IN ACCORDANCE WITH THE REQUIREMENTS OF THE HYDRAULIC CALCULATIONS, & MAY NOT BE CHANGED WITHOUT RESEARCH & APPROVAL OF FIRE PROTECTION DESIGNER & AUTHORITIES HAVING JURISDICTION 7. ALL SPRINKLER PIPE ELEVATIONS ARE MEASURED TO THE CENTER OF PIPE ABOVE FINISHED FLOOR, STAR DIMENSIONS ARE FROM DECK ABOVE 8. EXACT LOCATION AND ELEVATIONS FOR SPRINKLER PIPING WILL BE DETERMINED AFTER COORDINATION WITH OTHER MECHANICAL TRADES 9. ALL SPRINKLER HEADS ARE TO BE LOCATED IN THE CENTER OF CEILING TILES 10. THE ENTIRE SPRINKLER SYSTEM SHALL BE TESTED AT 200 PSI FOR 2 HRS AND WITNESSED BY A REPRESENTATIVE OF THE GENERAL CONTRACTOR AND A REPRESENTATIVE OF THE ITHACA FIRE DEPARTMENT 11. ALL HANGERS SHALL BE INSTALLED PER NFPA 13 2007 ED 12, ANY PENETRATIONS THROUGH FIRE CURTAINS OR SMOKE WALLS ARE TO BE PATCHED AND FIRESTOPPED TO MAINTAIN FIRE RATING 13. BUILDING OWNER SHALL MAINTAIN A MINIMUM TEMPERATURE OF 40° IN ALL AREAS OF THE WET SPRINKLER SYSTEM PIPING TO PREVENT FREEZING 14. IF TEMPORARY HEAT IS TO BE USED DURING CONSTRUCTION, GENERAL CONTRACTOR SHALL PAY CAREFUL NOTE TO AVOID OVERHEATING AT SPRINKLER HEADS AS -BUILT DRAWING DATE: JULY 7, 2015 STONE QUARRY APTS SPENCER ROAD ITHACA, NY 14850 FIRE PROTECTION COVER PAGE Project: STONE QUARRY APARTMENTS BUILDING "A" SPENCER ROAD ITHACA, NY 14850 CLIENT: LECESSE CONSTRUCTION 75 THRUWAY PARK DR. WEST hENRIEI IA, NY 14586 DRAWING TITLE: FIRE PROTECTION COVER PAGE SCALE: NO SCALE REVI510N5: NO. DATE BY DS5CRlPTION 2 /0 / 4 UPDA TED WATER INFO ©01-2l -15 L PDA TSD PFR FIRE --- MARSIlAL COMMMNT5 3 04- l5- l 5 KM/ ADDSD 5PRlNKL0R5 --- --- --- --EME - Baumer Mechanical Design Services 625 Panorama Trail, Building 2, Suite 210 Rochester, NY 14625 585-313-5819 MECHANICAL CONTRACTORS PLUMBING•HEATINGsFIRE PROTECTION 11 COMFORT STREET ROCIlN5TE12, NEW YORK 14620 585-232-2800 THESE DOCUMENTS AND ALL IDEAS, ARRANGEMENT, DESIGNS AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE OWNED AND REMAIN THE PROPERTY OF KENNEDY MECHANICAL INC. AND NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE SPECIFIC WRI I I EN PERMISSION OF KENNEDY MECHANICAL INC. ALL RIGHTS RESERVED JOB NO. F 1785 DRAWN BY: A. LITZ CHECKED BY: C. BAUMER DATE: OCTOBER 30, 20 14 FPOOI J H F ( E D 9 ( A ir BEDROOM 1 7, 8. 121C 8' - LIVING 2-0 8, )). 8. 17F,110190AM7 1 MECH („1) 121J 0 NIECE! 120F 8" 0" KITCHE 119B •8" 0" 22=22 j , 21 1 - 0 1/2" 201 ))) 27) II 1.765.1.,,,,NPVCOR —6 lAlrn1-11MIRIA1 2 LIVI G . • • 1A1 - ELEV. 7' - 4 SDR NK_ER OMII I ED N SHA WAY 3ER NFPA 3R 6.9.6 - 0" muunmorm;amm'm —111111151EN RE: LAUNDR 19 Sal nA111111 K 5x4 STORZ FDC PER ITHACA REQUIREMENTS w/ BALL DRIP AND DRAIN @ APPROXIMATELY ABOVE GRADE AND 24v. ELECTRIC BELL @ APPROX. 8'-O" ABOVE GRADE H DISTANCE FROM SIDEWALL SPRINKLER TO SIDE OF OBSTRUCTION (A) MAXIMUM ALLOWABLE DISTANCE OF DEFLECTOR ABOVE BOTTOM OF OBSTRUCTION -INCHES - (B) LESS THAN 8' NOT ALLOWED 8' TO LESS THAN 10' 1" 10' TO LESS THAN 11' 2" 11' TO LESS THAN 12' 3" 12' TO LESS THAN 13' 4" 13' TO LESS THAN 14' 6" 14' TO LESS THAN 15' 7" 15' TO LESS THAN 16' 9" 16' TO LESS THAN 17' 11" 17' OR GREATER 14" 3" FP RISER - REFER TO DETAIL ON FP001 - ROUTE DRAIN THROUGH CHASE AT LAUNDRY MACHINES TO EXTERIOR ) F , FIRST FLOOR SPRINKLER PLAN +0 0' Scale: 1/4"=1:-0" • • SCALE 1/4"=1'-0" • SPRINKLERS ARE NOT REQUIRED IN RESIDENTIAL CLOSETS UNDER 24 SQ.FT. w/ LEAST DIMENSION NOT EXCEEDING 3 FT. PER NFPA 13R, 2007 ED. • SPRINKLERS ARE NOT REQUIRED IN RESIDENTIAL BATHROOMS UNDER 55 SQ.FT. PER NFPA 13R, 2007 ED. AS -BUILT DRAWING DATE: JULY 7, 2015 22) 21 201 (19) STONE QUARRY APTS SPENCER ROAD ITHACA, NY 14350 MR. E PROTECTION FIRST FLOOR Project: STONE QUARRY APARTMENTS BUILDING "A" SPENCER ROAD ITHACA, NY 14850 CLIENT: LECESSE CONSTRUCTION 75 THRUWAY PARK D. WEST HENKIE I IA, NY 14586 DRAWING TITLE: FIRE PROTECTION FIRST FLOOR SCALE: -0" REV1510 V5 t/0.0A77ff SPRINKLERS SCHEDULE Aggill DESIGNATION QUANTITY MFR TYPE K FACTOR MODEL NOMINAL ORIFICE, IN FINISH RATING "F SIN# 27 RELIABLE Q.R. PENDENT/ SEMI—REC ESC 5.6 F1FR 1/2 WHITE 155 RA1414 < 7 RELIABLE Q.R. HSW/ SEMI—REC ESC 5.6 F1FR 1/2 WHITE 200 RA1435 48 RELIABLE RESIDENTIAL HSW/ CONCEALED 4.4 FIRES 44 SWC 1/2 WHITE 155 R3531 • 2 RELIABLE RES PENDENT/ SEMI—REC ESC 4.9 F1 RES 49 1/2 WHITE 155 R3516 === === === EME TOTAL: 84 Project: STONE QUARRY APARTMENTS BUILDING "A" SPENCER ROAD ITHACA, NY 14850 CLIENT: LECESSE CONSTRUCTION 75 THRUWAY PARK D. WEST HENKIE I IA, NY 14586 DRAWING TITLE: FIRE PROTECTION FIRST FLOOR SCALE: -0" REV1510 V5 t/0.0A77ff bY 055CR f T ON 2 0 4 L ruAT50 WATERNFO EMO UPDATf0 f'5) Rf = MA/'SAL COMMfN 5 3 04- 5 M AD0f0 5FR NKLER5 === === === === === == === === === === EME Baumer Mechanical Design Services 625 Panorama Trail, Building 2, Suite 210 Rochester, NY 14625 585-313-5819 MECHANICAL CONTRACTORS PLUMBING •HEATING •FIRE PROTECTION / / COMFORT 5TRffT ROC11f5Tfg, A/W YORK 1 4620 565-232-2000 THESE DOCUMENTS AND ALL IDEAS, ARRANGEMENT, DESIGNS AND PLANS INDICATED THEREON OR PRESENTED THEREBY AKE OWNED AND REMAIN THE PROPERTY Of KENNEDY MECHANICAL INC. AND NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OK CORPORATION FOK ANY PURPOSE WHATSOEVER EXCEPT WITH THE SPECIFIC WRI I I EN PERMISSION OF KENNEDY MECHANICAL INC. ALL RIGHTS RESERVED JOB NO. P I 785 DRAWN BY: A. LITZ CHECKED BY: C. BAUMER DATE: OCTOBER 30, 2014 FP100 22 21 20 19 H F E D ( A) )) ) 711111.1.1RrIrmr. 7' -- 105i8 [ . , .....,,,minn,............ ronalnymmunalrpornalnwrot Tromp 6" 91 ST \-7 17777 200T 7' - 105/8" 13'-6" V-4" Mummurunmi 111 ELEV. 200E I " '',1111111111111111mmEMMIBMIMMIIIIMMIMMIIIIIIIIIIIMMMMY } MEE ))) DISTANCE FROM SIDEWALL SPRINKLER TO SIDE OF OBSTRUCTION (A) MAXIMUM ALLOWABLE DISTANCE OF DEFLECTOR ABOVE BOTTOM OF OBSTRUCTION -INCHES - (B) LESS THAN 8' NOT ALLOWED 8' TO LESS THAN 10' 1" 10' TO LESS THAN 11' 2" 11' TO LESS THAN 12' 3" 12' TO LESS THAN 13' 4" 13' TO LESS THAN 14' 6" 14' TO LESS THAN 15' 7" 15' TO LESS THAN 16' 9" 16' TO LESS THAN 17' 11" 17' OR GREATER 14" E SECOND FLOOR SPRINKLER PLAN +9'-4 5/8' Scale: 1/4"=1:-0" • • SCALE 1/4"=1'-0" ( B (A) • SPRINKLERS ARE NOT REQUIRED IN RESIDENTIAL CLOSETS UNDER 24 SQ.FT. w/ LEAST DIMENSION NOT EXCEEDING 3 FT. PER NFPA 13R, 2007 ED. • SPRINKLERS ARE NOT REQUIRED IN RESIDENTIAL BATHROOMS UNDER 55 SQ.FT. PER NFPA 13R, 2007 ED. AS -BUILT DRAWING DATE: JULY 7, 2015 22 21 STONE QUARRY APTS SPENCER ROAD ITHACA, NY 14350 MR. E PROTECTION SECOND FLOOR F'roject: STONE QUARRY APARTMENTS BUILDING "A" SPENCER ROAD ITHACA, NY 14850 CLIENT: LECESSE CONSTRUCTION 75 THRUWAY PARK DR. WEST HENRIE I IA, NY 14586 DRAWING TITLE: FIRE PROTECTION SECOND FLOOR SCALE: -0" REVI510 V5 A/0.0A77ff SPRINKLERS SCHEDULE AMIIII DESIGNATION QUANTITY MFR TYPE K FACTOR MODEL NOMINAL ORIFICE, IN FINISH RATING *F SIN4 <9 MA/'SAL COMMfN 5 RELIABLE Q.R. HSW/ SEMI—REC ESC 5.6 F1FR 1/2 WHITE 200 RA1435 1 69 RELIABLE RESIDENTIAL HSW/ CONCEALED 4.4 FIRES 44 SWC 1/2 WHITE 155 R3531 • 3 RELIABLE RES PENDENT/ SEMI—REC ESC 4.9 FIRES 49 1/2 WHITE 155 R3516 == === === === === EME TOTAL: 81 F'roject: STONE QUARRY APARTMENTS BUILDING "A" SPENCER ROAD ITHACA, NY 14850 CLIENT: LECESSE CONSTRUCTION 75 THRUWAY PARK DR. WEST HENRIE I IA, NY 14586 DRAWING TITLE: FIRE PROTECTION SECOND FLOOR SCALE: -0" REVI510 V5 A/0.0A77ff bY 055CR PT ON 2 0 4 L F uAT50 WATERNFO EMO L PDATf0 f'5( Rf = MA/'SAL COMMfN 5 3 04- 5 M AD0f0 5PR NKLER5 === === === === === == === === === === EME Baumer Mechanical Design Services 625 Panorama Trail, Building 2, Suite 210 Rochester, NY 14625 585-313-5819 MECHANICAL CONTRACTORS PLUMBING •HEATING •FIRE PROTECTION 11 COMFORT 5T-RffT ROCIlf5Tf12, A/W YORK 14620 565-232-2000 THESE DOCUMENTS AND ALL IDEAS, ARRANGEMENT, DESIGNS AND PLANS INDICATED THEREON OR PRESENTED THEREBY ARE OWNED AND REMAIN THE PROPERTY OF KENNEDY MECHANICAL INC. AND NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE SPECIFIC WRI I I EN PERMISSION OF KENNEDY MECHANICAL INC. ALL RIGHTS RESERVED JOB NO. I 785 DRAWN BY: A. LITZ CHECKED BY: C. BAUMER DATE: OCTOBER 30, 20 I 4 FP101 221 21 201 19 K F ( A 11111111111111111111111111111111111111111111111111111111111111111mhol,h1lni, 0 1 4 :I§E:b***-4 ' 3356. 10 sq.ft. 1111,111111111111111111111111111111111111111111111111,11111111111111111111111,111111111111111111111111,111111111111111111.11 , „,„.„ „.„ STAIR 3oos . . . . . : . . . . . . . . . . . . . ; 15'--8" . 1 T 6 3/8" 111,1!106441,, —14,:i01, ELEV. Rimmtimmarn 4,4 111111111119 4b44 -414,A 11111111111 'Thflf rrrr 1400=MMkrall 04, H 2 TOP LANDING SPRINKLER PLAN +28'-2' Scale: 1/4"=r-0" F THIRD FLOOR SPRINKLER PLAN +18'-9 1/4' Scale: 1/4"=1-0" DISTANCE FROM SIDEWALL SPRINKLER TO SIDE OF OBSTRUCTION (A) MAXIMUM ALLOWABLE DISTANCE OF DEFLECTOR ABOVE BOTTOM OF OBSTRUCTION -INCHES - (B) LESS THAN 8' NOT ALLOWED 8' TO LESS THAN 10' 1" 10' TO LESS THAN 11' 2" 11' TO LESS THAN 12' 3" 12' TO LESS THAN 13' 4" 13' TO LESS THAN 14' 6" 14' TO LESS THAN 15' 7" 15' TO LESS THAN 16' 9" 16' TO LESS THAN 17' 11" 17' OR GREATER 14" • • SCALE 1/4"=1'-0" • SPRINKLERS ARE NOT REQUIRED IN RESIDENTIAL CLOSETS UNDER 24 SQ.FT. w/ LEAST DIMENSION NOT EXCEEDING 3 FT. PER NFPA 13R, 2007 ED. • SPRINKLERS ARE NOT REQUIRED IN RESIDENTIAL BATHROOMS UNDER 55 SQ.FT. PER NFPA 13R, 2007 ED. AS -BUILT DRAWING DATE: JULY 7, 2015 22 (21) 20 .19) STONE QUARRY APTS SPENCER ROAD ITHACA, NY 14350 MR. E PROTECTION THIRD FLOOR Project: STONE QUARRY APARTMENTS BUILDING "A" SPENCER ROAD ITHACA, NY 14850 CLIENT: LECESSE CONSTRUCTION 75 THRUWAY PARK DR. WEST HENRIE I IA, NY I458 DRAWING TITLE: FIRE PROTECTION THIRD FLOOR SCALE: -0" REV/510 V5 A/0.0A77ff SPRINKLERS SCHEDULE Aillillb6' DESIGNATION QUANTITYRATING MFR TYPE K FACTOR MODEL NOMINAL ORIFICE, IN FINISH 'F SIN# < 9 RELIABLE Q.R. HSW/ SEMI—REC ESC 5.6 F1FR 1/2 WHITE 200 RA1435 === 68 RELIABLE RESIDENTIAL HSW/ CONCEALED 4.4 FIRES 44 SWC 1/2 WHITE 155 R3531 • 2 RELIABLE RES PENDENT/ SEMI—REC ESC 4.9 Fl RES 49 1/2 WHITE 155 R3516 0 2 TYCO UPRIGHT 5.6 TY—FRB 1/2 BRASS 155 TY3131 VIKING DRY SIDEWALL 5.6 VK182 1/2 CHROME 155 VK182 === EME TOTAL: 82 Project: STONE QUARRY APARTMENTS BUILDING "A" SPENCER ROAD ITHACA, NY 14850 CLIENT: LECESSE CONSTRUCTION 75 THRUWAY PARK DR. WEST HENRIE I IA, NY I458 DRAWING TITLE: FIRE PROTECTION THIRD FLOOR SCALE: -0" REV/510 V5 A/0.0A77ff bY 055CR PT ON 2 0 4 L F uAT50 WATERNFO EMO L PDATf0 f'5 Rf = MA/'SAL COMMfN 5 3 04- 5 M AD0f0 5PR NKLER5 === === === === === === === === === EME Baumer Mechanical Design Services 625 Panorama Trail, Building 2, Suite 210 Rochester, NY 14625 585-313-5819 MECHANICAL CONTRACTORS PLUMBING •HEATING •FIRE PROTECTION 1 1 COMFORT 5T-RffT ROCI1f5Tf12, 111W YORK 14620 565-232-2000 THESE DOCUMENTS AND ALL IDEAS, ARRANGEMENT, DESIGNS AND FLANS INDICATED THEREON OR PRESENTED THEREBY ARE OWNED AND REMAIN THE PROPERTY OF KENNEDY MECHANICAL INC. AND NO PART THEREOF SHALL BE UTILIZED BY ANY PERSON, FIRM, OR CORPORATION FOR ANY PURPOSE WHATSOEVER EXCEPT WITH THE SPECIFIC WRI I I EN PERMISSION OF KENNEDY MECHANICAL INC. ALL RIGHTS RESERVED JOB NO. F I 785 DRAWN BY: A. LITZ CHECKED BY: C. BAUMER DATE: OCTOBER 30, 20 I 4 FP102