HomeMy WebLinkAboutStone Quarry Apartments - Electrical2 4 5 6 ELECTRICAL SPECIFICATIONS PART 1 - GENERAL RELATED DOCUMENTS: THE GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND SUPPLEMENTARY CONDITIONS AND GENERAL REQUIREMENTS, APPLY TO THE WORK SPECIFIED IN THIS SECTION. SAFETY: IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, THE CONTRACTOR SHALL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITIONS OF THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY AT ALL TIMES. SCOPE OF WORK: PROVIDE ALL MATERIALS AND EQUIPMENT (EXCEPT THOSE ITEMS SPECIFICALLY STATED IN THESE SPECIFICATIONS OR ON THE DRAWINGS AS BEING FURNISHED BY OWNER OR OTHERS), LABOR AND INCIDENTALS REQUIRED FOR THE ELECTRICAL WORK AS INDICATED IN THESE SPECIFICATIONS AND DRAWINGS, AND AS REQUIRED TO MAKE A COMPLETE AND OPERATING INSTALLATION TO THE SATISFACTION OF THE OWNER AND THE ENGINEER. FURNISH COMPETENT SUPERVISION OF THE WORK TO BE PERFORMED AT ALL TIMES DURING PROGRESS OF THE WORK. THE WORK INCLUDES (BUT IS NOT NECESSARILY LIMITED TO) THE FOLLOWING: ALL REQUIRED ELECTRICAL SYSTEM COMPONENTS FOR SERVICE, FEEDERS AND BRANCH CIRCUIT WIRING FOR LIGHTING AND POWER. EMERGENCY SYSTEM WIRING AND COMPONENTS. GROUNDING. CONDUITS AND FITTINGS. PULL BOXES AND JUNCTION BOXES. MOTOR SWITCHES AND DISCONNECTS CONNECTION AND COORDINATION FOR MOTOR CONTROLLERS. LIGHTING FIXTURES. WIRING DEVICES. SENSORS, WIRING, CONDUIT FOR CONTROLS AND APPLICABLE TO ELECTRICAL CONTRACT ONLY. WIRING, CONDUIT, AND CONNECTIONS TO EQUIPMENT THAT MAY BE PROVIDED UNDER ANOTHER DIVISION OF THESE SPECIFICATIONS THAT ARE INCLUDED IN CONTRACT FOR ELECTRICAL WORK. WIRING, AND CONNECTING ELECTRICAL EQUIPMENT THAT IS TO BE FURNISHED BY THE OWNER. ELECTRICAL WORK INCIDENTAL TO THE REQUIREMENTS OF THE MECHANICAL SYSTEM. FIRE ALARM SYSTEM VVHERE APPLICABLE TO ELECTRICAL CONTRACT. RACEWAY AND CABLING FOR DATA SYSTEMS. TEMPORARY WIRING AS REQUIRED FOR OTHER BUILDING FUNCTIONS DURING PERFORMANCE OF ELECTRICAL WORK. TESTING OF ELECTRICAL EQUIPMENT AND WIRING. DRAWINGS: THE DRAWINGS SHALL SERVE TO INDICATE THE GENERAL LAYOUT OF THE VARIOUS ITEMS OF EQUIPMENT. HOWEVER, LAYOUT OF ANY EQUIPMENT, ACCESSORIES, SPECIALTIES, WIREWAYS, AND CONDUIT SYSTEMS ARE DIAGRAMMATIC UNLESS SPECIFICALLY DIMENSIONED, AND DO NOT NECESSARILY INDICATE EVERY REQUIRED FITTING, JUNCTION BOX, PULL BOX, OR SIMILAR ITEMS REQUIRED FOR THE COMPLETE INSTALLATION. JOB CONDITIONS: CAREFULLY INVESTIGATE STRUCTURAL CONDITIONS, WALL, FURRING AND CHASE LOCATIONS, AND ROOM FINISHES AND MAKE ACTUAL MEASUREMENTS ON THE JOB SO THAT ALL EQUIPMENT SUCH AS PANELBOARDS, SWITCHES, RECEPTACLES, LIGHTING FIXTURES, FIRE ALARM DEVICES AND ACCESSORIES SHALL FIT. PRACTICAL CONSIDERATION SHALL BE GIVEN TO COORDINATION OF ALL VISIBLE DEVICES WITH AESTHETIC AND ARCHITECTURAL DESIGN ELEMENTS. OBTAIN FROM THE OWNER A COMPLETE UNDERSTANDING OF TRAINING AND REQUIRED PERSONAL PROTECTIVE EQUIPMENT NECESSARY FOR WORKING ON THIS SITE. VERIFY ALL MEASUREMENTS AND BE RESPONSIBLE FOR THE CORRECTNESS OF SAME BEFORE ORDERING ANY MATERIALS OR DOING ANY WORK. NO EXTRA CHARGE OR COMPENSATION WILL BE ALLOWED BECAUSE OF ANY DIFFERENCE BETWEEN THE ACTUAL MEASUREMENTS AND THOSE INDICATED ON THE DRAWINGS. ANY RELEVANT DIFFERENCE WHICH MIGHT BE DISCOVERED BY THE CONTRACTOR SHALL BE SUBMITTED TO THE ENGINEER FOR CONSIDERATION BEFORE PROCEEDING WITH THE WORK. LAW AND PERMITS: THE LATEST PUBLISHED REGULATIONS OF THE STATE AND LOCAL BUILDING CODES, NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), OSHA (REGARDING CONSTRUCTION PRACTICES) AND NATIONAL ELECTRICAL CODE, WITH THE LATEST TENTATIVE INTERIM AMENDMENTS, SHALL BE CONSIDERED AS INCLUDED IN THESE SPECIFICATIONS, AND ALL APPLICABLE REQUIREMENTS SHALL BE FULLY COMPLIED WITH. QUESTIONS REGARDING INTERPRETATION SHALL BE ADDRESSED TO THE PROJECT ARCHITECT. APPLY FOR PERMITS, LICENSES AND INSPECTION CERTIFICATES AND PAY ALL FEES INCIDENTAL TO THE ELECTRICAL WORK. GIVE NOTICE TO THE PROPER AUTHORITIES IN AMPLE TIME FOR THE WORK TO BE INSPECTED AND APPROVED AS IT PROGRESSES, AND CONCEAL NO WORK UNTIL APPROVED BY THE ELECTRICAL INSPECTORS HAVING JURISDICTION. THE NATIONAL ELECTRICAL CODE AND ALL STATE AND LOCAL RULINGS SHALL BE OBSERVED AND SHALL GOVERN THE CHARACTER OF THIS WORK. SHOULD THE DRAWINGS OR THESE SPECIFICATIONS IN ANY WAY CONFLICT WITH THE CODE, STATE OR LOCAL RULES AND/OR REGULATIONS, PROMPTLY NOTIFY THE ENGINEER IN WRITING IN ORDER THAT NECESSARY CHANGES CAN BE ACCOMPLISHED BY APPROPRIATE MODIFICATION. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO MEET THE REQUIREMENTS OF CODES, RULES AND REGULATIONS APPLICABLE TO ELECTRICAL WORK AT THIS SITE. UPON COMPLETION OOF THEINSTALLATION, A CERTIFICATE OF APPROVAL FROM THE ELECTRICAL INSPECTION DEPARTMENT HAVING JURISDICTION THEREON SHALL BE FURNISHED TO THE OWNER, PRIOR TO FINAL PAYMENT, AND ALL FEES SHALL BE PAID BY THE ELECTRICAL CONTRACTOR. PROVIDE TESTING AND RECORDS OF COMPLETION FOR ALL FIRE ALARM MODIFICATIONS AND HIGH VOLTAGE CONNECTIONS. THE CERTIFICATE OF INSPECTION SHALL NOT RELEASE THE CONTRACTOR FROM ANY GUARANTEE OF WARRANTY OBLIGATIONS SET FORTH IN THESE SPECIFICATIONS. GUARANTEE: ALL MATERIALS AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE OF THE PROJECT AS SUBSTANTIALLY COMPLETED IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS, OR WHEN BENEFICIALLY USED BY THE OWNER, WHICHEVER FIRST OCCURS AS CERTIFIED BY THE PROJECT ARCHITECT. DEFECTS DUE TO FAULTY MATERIALS, METHODS OF INSTALLATION OR WORKMANSHIP SHALL BE REPAIRED OR REPLACED PROMPTLY WITH THE LEAST INCONVENIENCE AND WITHOUT EXPENSE TO THE OWNER, DURING THE HOURS AND IN A TIME FRAME AS DESIGNATED BY THE ENGINEER. THIS GUARANTEE IS AN ADDITION TO ANY SPECIFIC PERFORMANCE GUARANTEES CALLED FOR IN THE INDIVIDUAL PARAGRAPHS. SUBMIT REQUIRED COPIES OF ALL WARRANTIES AND GUARANTEES FOR SYSTEMS, EQUIPMENT, DEVICES AND MATERIALS (THIS INCLUDES COPIES FOR MAINTENANCE MANUALS). SUBMITTAL AND SHOP DRAWINGS: SUBMIT FOR REVIEW ALL REQUESTED PRODUCT DATA, SHOP DRAWINGS AND SAMPLES. SUBMIT REQUIRED COPIES OF ALL CUTS, CATALOGUES, BULLETINS, DIAGRAMS, CURVES, ETC. TRADE NAMES, MANUFACTURERS, AND CATALOG NUMBERS ARE MENTIONED HEREIN AND ON THE DRAWINGS SOLELY IN ORDER TO ESTABLISH A STANDARD FOR THE TYPE, GENERAL DESIGN, AND QUALITY OF PRODUCT REQUIRED. OTHER PRODUCTS SIMILAR IN DESIGN OF EQUAL QUALITY CAPABLE OF FITTING WITHIN THE SPACES ALLOCATED AND COMPLYING WITH THE DRAWINGS AND SPECIFICATIONS WILL BE CONSIDERED. DIMENSIONAL DATA AND WEIGHTS SHALL BE INCLUDED. CONTRACTOR SHALL REVIEW SUBMITTALS AND SHOP DRAWINGS BEFORE FORWARDING THEM TO PROJECT ARCHITECT. SUBMITTALS AND DRAWINGS WILL BE RETURNED AFTER REVIEW INDICATING WHETHER OR NOT EXCEPTIONS ARE TAKEN AND THE REQUIRED PROCEDURE TO BE FOLLOWED THEREAFTER. RESUBMISSION OF REVISED SUBMITTALS AND SHOP DRAWINGS IS REQUIRED BEFORE CONSTRUCTION STARTS, UNLESS OTHERWISE NOTED IN CONTRACT OR ON RETURNED SUBMITTALS. CORRECTIONS OR COMMENT'S MADE ON THE SUBMI I IALS AND DRAWINGS DURING THIS REVIEW DO NOT RELIEVE THE CONTRACTOR FROM COMPLIANCE WITH THE REQUIREMENTS OF THE DRAWINGS AND SPECIFICATIONS. THIS REVIEW IS FOR GENERAL CONFORMANCE WITH THE DESIGN CONCEPT OF THE PROJECT AND GENERAL COMPLIANCE WITH THE INFORMATION GIVEN IN THE CONTRACT DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR CONFIRMING AND CORRELATING ALL QUANTITIES AND DIMENSIONS, SELECTING FABRICATION PROCESSES AND TECHNIQUES OF CONSTRUCTION. THE PRODUCTS LISTED BELOW SHALL BE SUBMITTED FOR REVIEW AFTER THE AWARD OF THE CONTRACT AND BEFORE ANY EQUIPMENT OR MATERIALS ARE PURCHASED. IF A PRODUCT IS UNACCEPTABLE, ANOTHER PRODUCT SHALL BE SUBMITTED. PROVIDE SUBMITTALS FOR THE FOLLOWING WHERE INCLUDED IN ELECTRICAL CONTRACT: LIGHTING FIXTURES AND LAMPS WIRING DEVICES AND DEVICE PLATES TRANSFORMERS SWITCHGEAR AND CONNECTING BUS WHERE APPLICABLE PANELBOARDS CIRCUIT BREAKERS FOR PANELBOARDS ENCLOSED SWITCHES AND DISCONNECTS FUSES ETHERNET CABLE SENSORS AND TRANSMITTERS FIRE ALARM DEVICES INCLUDED IN WORK ELECTRICAL IDENTIFICATION: PROVIDE LAMINATED IDENTIFICATION PLATES FOR MAJOR ITEMS OF ELECTRICAL EQUIPMENT AND AS REQUIRED BY ELECTRICAL CONTRACT AND INCLUDE: ENCLOSED SWITCHES, CIRCUIT BREAKERS AND DISCONNECTS SWITCHBOARDS AND PANELBOARDS STANDARDS AND REGULATIONS: THE WORK UNDER THIS DIVISION SHALL COMPLY WITH THE LATEST EDITION OF THE APPLICABLE STANDARDS AND CODES OF THE FOLLOWING: UL - UNDERWRITER'S LABORATORIES, INC. NEMA - NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NEC NATIONAL ELECTRICAL CODE, NFPA 70 STATE AND LOCAL CODES, RULES AND REGULATIONS ANSI - AMERICAN NATIONAL STANDARDS INSTITUTE NFPA NATIONAL FIRE PROTECTION ASSOCIATION INCLUDE ALL ITEMS OF LABOR AND MATERIALS REQUIRED TO COMPLY WITH SUCH STANDARDS AND CODES. WHERE QUANTITIES, SIZES OR OTHER REQUIREMENTS INDICATED ON THE DRAWINGS, OR HEREIN SPECIFIED ARE IN EXCESS OF THE REQUIREMENTS OF THE STANDARDS AND CODES, THE SPECIFICATIONS AND/OR DRAWINGS SHALL GOVERN. RECORD DRAWINGS: UPON COMPLETION OF THE PROJECT, FURNISH A COMPLETE SET OF REPRODUCIBLE DRAWINGS WHICH WILL INCLUDE ALL REVISIONS, SKETCHES, ETC., WHICH MAY HAVE BEEN REQUIRED DURING CONSTRUCTION. THE CONTRACTOR SHALL MARK THESE DRAWINGS TO INDICATE EXACT, AS INSTALLED CONDITIONS. THE AS -INSTALLED CONDITIONS SHALL REFLECT ANY CHANGES IN EQUIPMENT LOCATION OR ROUTING WHICH DID NOT FOLLOW THAT SHOWN ON THE CONTRACT DRAWINGS AND CHANGES IN CONDUIT AND/OR WIRING SIZES. DURING COURSE OF THE INSTALLATION, CONTRACTOR SHALL MAINTAIN A SEPARATE SET OF DRAWINGS FOR MARKING AND NOTING ALL INSTALLATION DEVIATIONS. THIS SET OF DRAWINGS SHALL BE MAINTAINED CONTINUOUSLY, AND SHALL BE USED FOR NO OTHER PURPOSE THAN INDICATING AS -INSTALLED CONDITIONS. PART 2 - PRODUCTS: MATERIALS: UNLESS OTHERWISE SPECIFIED, ALL MATERIALS SHALL BE NEW AND UNUSED AND SHALL BE LISTED BY UNDERWRITERS' LABORATORIES, INC., FOR THE SERVICE INTENDED, EXCEPT AS PROVIDED IN CONTRACT. COMPATIBILITY: PROVIDE PRODUCTS WHICH ARE COMPATIBLE WITH OTHER PRODUCTS OF THE ELECTRICAL WORK, AND WITH OTHER WORK REQUIRING INTERFACE WITH THE ELECTRICAL WORK, INCLUDING ELECTRICAL CONNECTIONS AND CONTROL DEVICES. FOR EXPOSED ELECTRICAL WORK, COORDINATE COLORS AND FINISHES WITH OTHER WORK. DETERMINE IN ADVANCE OF PURCHASE THAT EQUIPMENT AND MATERIALS PROPOSED FOR INSTALLATION WILL FIT LEAVING ADEQUATE CLEARANCE AS REQUIRED BY APPLICABLE CODES, AND FOR ADJUSTMENT, REPAIR, OR REPLACEMENT. MANUFACTURERS NAMEPLATES: EACH MAJOR COMPONENT OF THE EQUIPMENT SHALL HAVE THE MANUFACTURER'S NAME, ADDRESS, MODEL NUMBER, AND RATING ON A PLATE SECURELY AFFIXED IN A CONSPICUOUS PLACE. THE NAMEPLATE OF DISTRIBUTING AGENT WILL NOT BE ACCEPTABLE. NEMA CODE RATINGS, OR OTHER DATA WHICH ARE DIE -STAMPED INTO THE SURFACE OF THE EQUIPMENT SHALL BE STAMPED IN AN EASILY VISIBLE LOCATION. PRODUCT, DELIVER, STORAGE, AND HANDLING: ENSURE THAT ALL ELECTRICAL EQUIPMENT, DEVICES, AND MATERIALS ARRIVE AT THE SITE IN GOOD CONDITION, INTACT IN FACTORY PACKAGE OR CRATE. ANY EQUIPMENT FOUND TO BE DAMAGED SHALL BE REMOVED FROM THE PROJECT SITE. HAVE PERSONNEL ON-SITE TO RECEIVE SHIPMENTS. DO NOT USE OWNER'S EMPLOYEES TO ACCEPT SHIPMENTS. STORE AND PROTECT FROM DAMAGE ALL ELECTRICAL EQUIPMENT, DEVICES, AND MATERIALS IN FACTORY CONTAINERS OR PACKAGE UNTIL READY FOR USE. STORAGE FACILITY SHALL BE A CLEAN, DRY, INDOOR SPACE WHICH PROVIDES PROTECTION AGAINST WEATHER. AVOID DAMAGE BY CONDENSATION BY PROVIDING TEMPORARY HEATING WHEN REQUIRED. HANDLE ALL ELECTRICAL EQUIPMENT, DEVICES, AND MATERIALS CAREFULLY TO PREVENT BREAKAGE, DENTING, OR SCORING OF THE FINISH. DAMAGED MATERIALS SHALL BE REMOVED FROM THE PROJECT SITE. TOUCH UP ALL MARRED SURFACES. CONDUIT: CONDUIT SHALL BE AS INDICATED ON THE DRAWINGS. NO CONDUIT SMALLER THAN 1/2" DIAMETER SHALL BE USED, UNLESS NOTED OTHERWISE HEREIN OR ON DRAWINGS. USE SHORT PIECES OF FLEXIBLE CONDUIT FOR CONNECTIONS TO MOTORS AND MOVING OR VIBRATING EQUIPMENT. USE LIQUID TIGHT IN ALL WET/DAMP LOCATIONS. BOXES: BOXES SHALL BE OF STANDARD SIZES SUITABLE FOR THE USE INTENDED. USE CAST FS BOXES IN DAMP OR WET AREAS. GALVANIZED STAMPED BOXES MAY BE USED IN GENERAL AREAS INSIDE. WALL OUTLETS FOR SWITCHES, RECEPTACLES, ETC., SHALL BE SUITABLE FOR DEVICE WITH APPROPRIATE DEVICE RING FOR THE APPLICATION. BOXES OUTDOOR, WHERE REQUIRED, SHALL BE CAST FS TYPE, WITH WEATHERPROOF COVER. GROUNDING: GROUND CONDUITS, BOXES, MOTOR FRAMES, FIXTURE BODIES AND RECEPTACLE GROUND TERMINALS. MAINTAIN GROUND CONTINUITY THROUGH CONDUITS. PROVIDE SEPARATE GROUND CONDUCTORS IN CIRCUITS. PROVIDE GROUNDING ELECTRODE SYSTEMS FOR SERVICE AND SEPARATELY DERIVED GROUNDING SYSTEM FOR DISTRIBUTION TRANSFORMERS. PANELBOARDS: PROVIDE PANELBOARD, AS SCHEDULED, BY SUITABLE MANUFACTURER: SQUARE -D, CUTLER HAMMER/EATON, GENERAL ELECTRIC, OR ITE, EXISTING REVISED AND NEW CIRCUIT DIRECTORIES SHALL BE NEATLY PRODUCED BY TYPEWRITTEN METHOD TO REFLECT LOADS AS INSTALLED. PROVIDE ADDITIONAL CIRCUIT BREAKERS AS REQUIRED TO COMPLY WITH DRAWING REQUIREMENTS. CIRCUIT BREAKERS TO BE COMPATIBLE WITH RATINGS, TYPE, QUALITY OF PANEL IN WHICH THEY ARE TO BE INSTALLED. WIRE: UNLESS OTHERWISE SPECIFIED, WIRE FOR THE VARIOUS SERVICES SHALL BE OF THE FOLLOWING TYPES: BRANCH LIGHTING AND POWER CIRCUITS, TYPE "THVV", "THWN", THWN-2 OR "THHN" SUITABLE FOR DRY AND WET LOCATIONS. INSTALL ALL THE CIRCUITS ON ROOF USING XHHW-2 IN GALVANIZED CONDUIT ON APPROVED ROOF SUPPORTS. MINIMUM GAUGES (AWG) ARE AS INDICATED OR AS REQUIRED BY CODE FOR THE APPLICATIONS. OTHER WIRE SHALL BE NO SMALLER THAN 12 GAUGE (AWG) UNLESS OTHERWISE NOTED. SIZES #8 AND LARGER SHALL BE STRANDED. WIRING SHALL BE COLOR CODED, PER STANDARD AT SITE. ENCLOSED SWITCHES AND DISCONNECTS: HD NEMA 1 INDOORS IN DRY LOCATIONS AND NEMA 3R FOR EXTERIOR OR DAMP/WET AREAS, UNLESS OTHERWISE NOTED AS MANUFACTURED BY SQ. D, CUTLER HAMMER/EATON, GENERAL ELECTRIC, OR ITE. WIRING DEVICES: EXCEPT AS NOTED OTHERWISE SWITCHES SHALL BE 20 AMP, 120/277 VOLT SILENT TYPE, SINGLE POLE, OR THREE WAY AS REQUIRED; RECEPTACLES SHALL BE DUPLEX, GROUNDING TYPE, 20 AMPERE, 125 VOLT, 3 WIRE. WHERE INDICATED OR REQUIRED, USE GFI RATED RECEPTACLES AND WHERE DAMP OR WET, USE WEATHER-PROOF COVERS TO PROTECT THE DEVICES. SWITCH AND RECEPTACLE PLATES: ALL SWITCH, RECEPTACLE AND OUTLET DEVICES PLATES SHALL MATCH STANDARDS AT THE SITE, AND ALL PLATES FOR MULTIPLE GANG REQUIREMENTS SHALL BE ONE-PIECE CONSTRUCTION. PLATES SHALL BE PROVIDED WITH GASKETS WHERE REQUIRED. FINISHES FOR WALL SWITCHES AND WALL RECEPTACLES: FINISHES FOR ALL RECEPTACLES AND SWITCHES AND SIMILAR EXPOSED DEVICES SHALL BE COLOR COORDINATED TO MATCH WALL FINISH- IVORY, BROWN, OR STAINLESS. LIGHTING FIXTURES: UNLESS OTHERWISE NOTED, ALL LIGHTING FIXTURES SHALL BE NEW. FURNISH ALL REQUIRED EQUIPMENT, ACCESSORIES, MOUNTING HARDWARE AND LAMPS. BALLASTS SHALL BE ELECTRONIC, CBM RATED ETL TESTED AND APPLICABLE TO THE NEW YORK STATE ENERGY CODE WITH LAMPS. FIXTURES SHALL BE AS SCHEDULED. EMERGENCY/EGRESS LIGHTING UNITS SHALL HAVE ALTERNATE POWER SOURCE TO MEET CODE REQUIREMENT FOR 90 MINUTES OF OPERATION IN THE EVENT OF A POWER FAILURE. PART 3 - EXECUTION: WORKMANSHIP: WORKMANSHIP SHALL CONFORM TO APPROVED ELECTRICAL INSTALLATION PRACTICE. EQUIPMENT AND ACCESSORIES AS INSTALLED SHALL BE COMPLETE AND OPERATING. THE EXACT LOCATION AND ARRANGEMENT OF MATERIAL AND EQUIPMENT SHALL BE DETERMINED AS WORK PROGRESSES TO CONFORM IN THE BEST POSSIBLE MANNER WITH RELATED WORK OF OTHER CRAFTS. THE WORK IN ALL DETAILS IS SUBJECT TO THE APPROVAL OF THE OWNER. ANY WORK OR MATERIAL WHICH IS REJECTED MUST BE REMOVED AND REPLACED IMMEDIATELY. PROTECTION OF FIXTURES, MATERIAL AND EQUIPMENT: CONTINUOUSLY MAINTAIN ADEQUATE PROTECTION OF STORED MATERIALS AND INSTALLED WORK. PROTECT FIXTURES AND EQUIPMENT AGAINST DIRT, RUST, MOISTURE, CHEMICAL AND MECHANICAL INJURY. DO NOT STORE MATERIALS AND EQUIPMENT DIRECTLY ON THE GROUND AND/OR IN AREAS WHERE THEY WILL BE SUBJECT TO PHYSICAL INJURY FROM VEHICULAR TRAFFIC OR CONSTRUCTION MACHINERY. DO NOT ALLOW CONDUIT AND EQUIPMENT INSTALLED TO BE USED BY OTHER TRADES AS SUPPORTS FOR SCAFFOLDS OR PERSONNEL. DELICATE EQUIPMENT SHALL NOT BE DELIVERED TO THE JOB SITE UNLESS IT CAN BE PLACED IN COMPLETED AND PROTECTED AREAS. CAP OR PLUG ALL CONDUIT OPENINGS DURING INSTALLATION. AT THE COMPLETION OF THE WORK, EQUIPMENT, FIXTURES, EXPOSED SUPPORTS, AND PIPING SHALL BE CLEANED TO THE SATISFACTION OF THE ARCHITECT. CLEANING AND HOUSEKEEPING: REMOVE ALL DEBRIS, SURPLUS MATERIALS OR FOREIGN MATTER (CAUSED BY THE PERFORMANCE OF THE ELECTRICAL WORK) FROM THE PREMISES. ON COMPLETION OF THE WORK, THE CONTRACTOR SHALL BE RESPONSIBLE FOR LEAVING THE PREMISES IN A CLEAN CONDITION TO THE SATISFACTION OF THE ARCHITECT AND OWNER. KEEP STOCKS OF MATERIAL AND EQUIPMENT STORED ON THE PREMISES IN A NEAT AND ORDERLY MANNER, IN A STORAGE AREA AS DIRECTED BY GENERAL CONTRACTOR. LINES AND LEVEL: CONTRACTOR SHALL BE RESPONSIBLE FOR THE LINES AND LEVELS FOR THE ELECTRICAL EQUIPMENT, WIREWAYS, AND CONDUIT SYSTEMS BASED ON REFERENCE LINES AND BENCH MARKS ESTABLISHED BY THE CONTRACTOR FOR THE GENERAL WORK. TEMPORARY WIRING, LIGHTING AND POWER AT THE SITE: PROVIDE PROVISIONS FOR TEMPORARY LIGHT AND POWER DURING THE CONSTRUCTION PERIOD CONFORMING TO ALL LOCAL CODE AND STATE LABOR LAW REQUIREMENTS. PROVIDE AND MAINTAIN ALL TEMPORARY SERVICE EQUIPMENT AS REQUIRED UNTIL PERMANENT SERVICE IS INSTALLED AND "ALIVE". SWITCH -OVER OF TEMPORARY SYSTEMS TO THE PERMANENT SERVICE WHEN PERMANENT SERVICE IS READY FOR TRANSFER OF ELEMENTS. PROVIDE AND MAINTAIN TEMPORARY SERVICE, AND SWITCH "ON" AND "OFF ON ALL REGULAR WORKING DAYS A COMPLETE TEMPORARY LIGHT SYSTEM FOR THE SECTION OF THE BUILDING WHILE UNDER CCNSTRUCTION. PROVIDE AND MAINTAIN TEMPORARY FEEDERS TO PERMANENT MECHANICAL EQUIPMENT REQUIRING SERVICE BEFORE PERMANENT FEEDERS ARE READY FOR SAME. PROVIDE ANY AND/OR ALL RELOCATIONS OF THE TEMPORARY ELECTRIC FACILITIES AS NECESSARY TO CLEAR THE PERMANENT INSTALLATIONS OF ALL TRADES. WORK RELATED TO EQUIPMENT NOT FURNISHED AS WORK OF THIS DIVISION OF THE SPECIFICATIONS: UNLESS SPECIFICALLY INDICATED OTHERWISE, ANY REQUIRED ELECTRICAL SERVICES FOR AND REQUIRED ELECTRICAL CONNECTIONS TO ITEMS SHOWN ON THE DRAWINGS AND/OR SPECIFIED TO BE FURNISHED IN OTHER DIVISIONS OF SPECIFICATIONS OR BY OWNER SHALL BE ELECTRICALLY CONNECTED AS WORK OF THIS SECTION. ELECTRICAL WORK FOR EQUIPMENT SPECIFIED IN DIVISION 15 - MECHANICAL SHALL BE AS SPECIFIED HEREINAFTER. RACEWAYS, GROUNDING CONNECTIONS, AND OTHER ROUGHING -IN INDICATED SHALL BE PROVIDED AS WORK OF THIS SECTION FOR DATA SYSTEM. MECHANICAL EQUIPMENT: ALL POWER WIRING ASSOCIATED WITH DIVISION 15, MECHANICAL SHALL BE PROVIDED AS WORK OF DIVISION 16, ELECTRICAL. ALL POWER DISCONNECT SWITCHES NOT PROVIDED WITH EQUIPMENT SHALL BE PROVIDED AS INDICATED UNDER DIVISION 16. EXCEPT AS MAY BE INDICATED ON THE DRAWINGS AND/OR HEREINAFTER NOTED, ALL CONTROL WIRING IS BY DIVISION 15. TESTS: TEST ALL WIRING TO INDICATE THAT THE COMPLETED SYSTEM IS FREE OF SHORT CIRCUITS AND UNDESIRABLE GROUNDS, AND IS READY FOR OPERATION. INSULATION RESISTANCE OF ALL WIRING SHALL MEET THE PERFORMANCE SUGGESTED BY THE MANUFACTURER. MAKE AN ACCEPTANCE TEST OF HIGH VOLTAGE CABLE AFTER TERMINATIONS TO INSURE APPROPRIATE CONNECTIONS. PROVIDE ALL NECESSARY TESTING EQUIPMENT FOR MAKING TESTS. ALL TESTS SHALL BE MADE IN THE PRESENCE OF THE OWNER OR THEIR QUALIFIED REPRESENTATIVE. WHEN TEST RESULTS ARE NOT SATISFACTORY, THE CONTRACTOR SHALL MAKE SUCH ADJUSTMENTS AND CHANGES AS ARE NECESSARY AND SHALL NOTIFY THE OWNER WHEN READY FOR ANOTHER TEST. REPEAT THE TEST OR TESTS WHICH DISCLOSED THE FAULTY OR DEFECTIVE WORK OR EQUIPMENT, AND MAKE SUCH ADDITIONAL TESTS AS NECESSARY TO PROVE CONFORMANCE. CHECK DIRECTION OF ROTATION OF ALL MOTORS AND REVERSE CONNECTIONS AS NECESSARY. CONTRACTOR SHALL NOT ATTEMPT TO "BUMP" MOTORS WHILE COUPLED TO MECHANICAL EQUIPMENT THAT COULD BE DAMAGED BY WRONG ROTATION. CERTIFICATES AND TEST REPORTS: SUBMIT REQUIRED COPIES OF ALL CERTIFICATIONS AND TEST REPORTS ADEQUATELY IN ADVANCE OF COMPLETION OF THE WORK TO ALLOW FOR REMEDIAL ACTION AS REQUIRED TO CORRECT DEFICIENCIES DISCOVERED IN EQUIPMENT AND SYSTEMS. ELECTRICAL EGEND WALL SWITCH 3 -WAY WALL SWITCH WALL OCCUPANCY SENSOR SWITCH CEILING OCCUPANCY SENSOR, # DENOTES TYPE: 1 = 360° VIEW 2 = NARROW LONG-RANGE VIEW DUPLEX WALL RECEPTACLE Architecture Planning Interior Design 217 North Aurora Street Ithaca NY 14850 p 607.273.7600 f 607.273.0475 GFCI DUPLEX WALL RECEPTACLE GFCI DUPLEX WALL RECEPTACLE WITH WEATHERPROOF COVER DOHN A. S1 S, P.E. OF N QUAD DUPLEX WALL RECEPTACLE TELEPHONE / DATA JACK FIRE ALARM MANUAL PULL STATION FIRE ALARM HORN / STROBE FUTURE FIRE ALARM STROBE (PROVIDE BLANK PLATE) FIRE ALARM MONITOR MODULE FIRE ALARM CONTROL MODULE _A DISCONNECT SWITCH WITH AMPERAGE RATING (NF - NONFUSED, FU - FUSED) F Consulting Ele ``1""""" ' '.5 Archer Lane Engineer, NYS PE Kissimmee, FL 34746 License #068705 (407) 404-0790 Warning, it a violation of the NY State Education Law for any person to alter this document in any way, unless acting under the direction of a licensed professional engineer. If a document bearing theseal of an engineer is altered, the altering engineer shall affix to the document their seal and the notation "altered by" followed by their signature and the date of such alteration,and a specific description of the alteration. DEMCO NEW YORK CORP. ELECTRICAL CONTRACTORS 6701 MANLIUS CENTER RD EAST SYRACUSE, NEW YORK 13057 E ELECTRICAL PANEL / SWITCHBOARD WITH DESIGNATION 0 SMOKE DETECTOR, 120V W/ BATTERY BACKUP CQ CARBON MONOXIDE DETECTOR, 120V W/ BATTERY BACKUP SMOKE DETECTOR - ADDRESSABLE SC SMOKE/CARBON MONOXIDE DETECTOR, 120V W/ BATTERY BACKUP HEAT DETECTOR PULL STATION T/D TELE / MODEM LOCATION - SEE E1.2 FOR MORE INFO DATA O TELEVISION REVISION SCHEDULE DATE ADDENDUM 2 9/15/14 LIGHT NG FIXTURE SCHEDULE Type Manufacturer Model Number L yp Lamp attage/Type Notes A H.E. WILLIAMS DIG -S22-217- P - W REB2UNV 17 WATT T8 PROVIDE PLASTER FRAME WHERE NEEDED � O Ala KICHLER 42246N1 4 23 WATT CFL OA1b KICHLER 42276N1 ATT CFL 0 A2 H.E. WILLIAMS DIG-S22-224T5H- WPR-EB2-UNV 24 WATT T5 HO PROVIDE PLASTER FRAME WHERE NEEDED 0 B KICHLER 8102WH 13 WATT CFL C KICHLER 216WH 13 WATT CFL D KICHLER 3694NI 23 WATT CFL Q E KICHLER 8102WH 13 WATT CFL G BROWNLEE 7325 -(COLOR)- B12LED-ES 12 WATT LED COLOR TO BE SELECTED BY OWNER/ARCHITECT D - -H KICHLER 8102WH 2 13 WATT CFL K KICHLER 8102WH 2 13 WATT CFL N DECO LIGHTING DVTL-LED-10- 50-UNV WM 1 10 WATT LED P BROWNLEE 7322-13G-ES3 13 WATT GU24 Q RAB LIGHTINGPS4-11-20D2 ALED*T78 / POLE 1 78 WATT LED PROVIDE DISTRIBUTION (*) AS NOTED ON SITE PLAN R BETA-CALCO VERSO #820 8711 AG RIH 5408 1 6 WATT LED H.E. WILLIAMS WMA-4-132-4-EB1/OCC WSFS- 505 -PP -120 1 32 WATT T8 PROVIDE INTEGRAL OCCUPANCY SENSOR AND EMERGENCY BALLAST S T BROWNLEE 7325 -(COLOR) -B12LED-ES 1 12 WATT LED COLOR TO BE SELECTED BY OWNER/ARCHITECT KICHLER 6123N1 3 23 WATT CFL 1 ©I V H.E. WILLIAMS 174-232-A-2 EB2-UNV 32 WATT T8 {�! EM BEGHELLI USA XLP-S1 2 5.4 WATT MR16 EXIT BEGHELLI USA VA4-R-SA LED EXIT/EM BEGHELLI USA XCL-R-U-W 2 5,4 WATT MR16 NOTE: CONNECT EM STYLE BATTERY PACK FIXTURES AHEAD OF SWITCH LIGHTING IN EACH AREA (TYPICAL) FOR NORMAL FIRE ALARM CONTROL PANEL DOOR ENTRY MASTER STATION AREA OF REFUGE 2 -WAY INTERCOM (M = MASTER) SECURITY CAMERA DVR AND POWER SUPPLY EQUIPMENT CONNECTION - SEE SCHEDULE (kW VALUE = DIRECT 208V CONNECTION TO HEATER DOOR BELL ( INTERIOR CHIME ) WITH TRANSFORMER AUDIO / VISUAL DOOR SIGNAL WITH TRANSFORMER DOOR BELL ( EXTERIOR BUZZER ) SECURITY CAMERA, SEE CCTV RISER DIAGRAM ON E1.1 ELECTRICAL DRAWING INDEX E1.0 ELECTRICAL SPECIFICATIONS & DRAWING INDEX E1.1 TELE / DATA / VIDEO AND CCTV RISER DIAGRAMS E2.0 ELECTRICAL SITE PLAN EA1.0 APT BUILDING PANEL SCHEDULES AND 1 -LINE EA2.0 APARTMENT ELECTRICAL POWER & LIGHTING FLOOR PLANS EA2.1 APARTMENT ELECTRICAL POWER & LIGHTING ATTIC / ROOF PLANS EA3.0 APARTMENT ELECTRICAL LOW VOLTAGE;`$ FLOOR PLANS EA4.0 APARTMENT ENLARGED UNIT 1ST FLOOR ELECTRICAL PLANS EA4.1 APARTMENT ENLARGED UNIT 2ND & 3RD FLOOR ELECTRICAL ''L:A EA4.2 APARTMENT ENLARGED UNIT 2ND & 3RD FLOOR ELECTRICAL PLANS ET1.0 TOWNHOME ENLARGED ELECTRICAL PLAN - STONE QUARRY APARTMENTS RTMENTS, LLC C z 0 DATE: PROJECT: OTHER: ULY ULY 2014 2012059 DRAWN BY: SS. BR 4.4.1 - Electrical Specifications and Drawing Index A E1.0 A3 10 PANEL: TO N HOUSE PANEL 'THP' 60A, M.L.O. FLUSH MOUNTED LOC: 120 / 240V, 1 PH, 3W BOTTOM FEED CKT. NO DESCRIPTION CONN VA LOAD WIRE SIZE BREAKER PHASE BREAKER WIRE SIZE CONN VA LOAD DESCRIPTION CKT. NO TRIP POLE A B POLE TRIP 1 DISHWASHER 1,080 20A 1 X 1 20A BATHROOM 1 2 3 APPLIANCE 1 1,500 20A 1 X 1 20A BATHROOM 2 4 5 APPLIANCE 2 1,500 20A* 1 X 1 15A 1,093 FURNACE FURN-A 6 7 MASTER BEDROOM 15A* 1 X 2 20A 1,380 CONDENSING UNIT ACC -1 8 g BEDROOM 1, 2 15A* 1 X -- -- 1,380 CONDENSING UNIT ACC -1 10 11 1ST FLR GEN LIGHTING 15A* 1 X 1 20A 1,800 RANGE 12 * = PROVIDE ARC -FAULT CIRCUIT INTERRUPTER BREAKER TOWNHOME UNIT LOADCENTER SCHEDULE FROM NYSEG UTILITY POLE MOUNTED TRANSFORMERS (SEE SITE PLAN) MAIN FUSED DISCONNECT SWITCH 4 60A 120/ 240V 10, (� TYPE 'T' FIXTURES c� S Y (TYPICAL OF 8) RECEPTACLE FOR RADON FAN (TYPICAL OF 2) 300A/2 P 120/240V 10,3W (3) 500MCM ALUMINUM XHHW IN 3" PVC PROVIDE SERVICE GROUNDING SYSTEM PER THE REQUIREMENTS OF NEC ARTICLE 250. 'S\ TOWNHOME ONE -LINE DIAGRAM T1.0 APPLIES ONE TIME PER EACH BUILDING GENERAL NOTES: TYPICAL TOWNHOME LOADCENTER 'THP' TOWNHOME FEEDER SCHEDULE TAG SIZE(S) CONDUIT 3 #6 ALUM XHHW, # 8 ALUM XHHW GROUND 1" PVC 3 #4 ALUM XHHW, 6 ALUM XHHW GROUND 1" PVC 3 #2 ALUM XHHW, # 4 ALUM XHHW GROUND 1y4" PVC 3 #1 ALUM XHHW, # 2 ALUM XHHW GROUND 1}'4" PVC A. RECEPTACLE PLACEMENT TO MEET THE REQUIREMENTS OF NATIONAL ELECTRIC CODE (NEC), ARTICLE 210.52. B. COORDINATE KITCHEN COUNTER RECEPTACLE LOCATIONS WITH COUNTERTOP/ BACKSPLASH HEIGHTS. HORIZONTAL LOCATION IS CRITICAL AND MUST MEET THE REQUIREMENTS OF NEC ARTICLE 210.52 (C). C. COORDINATE BATHROOM RECEPTACLE LOCATIONS WITH ARCHITECTURAL ELEVATIONS AND ACCESSORIES TO BE INSTALLED. D. LOADCENTERS TO OPEN SIDE OF WALL SHOWN. E. PER NEC ARTICLE 406.11, ALL 120—VOLT RECEPTACLES WITHIN THE DWELLING UNITS WILL BE OF THE TAMPER—RESISTANT STYLE. F. ALERT THE GENERAL CONTRACTOR TO ANY WIRING CONFLICTS DUE TO PANEL LOCATIONS AT AREAS WITH TRUSSES DIRECTLY OVERHEAD. G. PROVIDE SOUND—DAMPENING PU PADS ON OUTLET BOXES IN INTERIOR DEMISING WALLS. KEYED NOTES FOR ETI.O: LOCATION OF 3—PORT INCOMING LOW VOLTAGE SERVICES WALL PLATE. SEE RISER (2:E1.1) FOR ADDITIONAL INFORMATION. TO UTILITY POLE AS DIRECTED BY SERVICE PROVIDER(S). SEE SITE PLAN AND RISER DIAGRAMS, SHEET E1.2. COORDINATE INSTALLATION WITH SERVICE PROVIDERS. 5 6 7 PROVIDE UNDER COMMON FACEPLATE (TYPICAL) TYPICAL TOWNHOME FIRST FLOOR ENLARGED ELECTRICAL PLAN \ET1,01/4" =1'-0" UNITS 101, 102, 103, 104, 105, 106, 107, 108 ROUTE SO THAT DEMISING WALLS ARE NOT PENETRATED 10 TYPICAL TOWNHOME SECOND FLOOR ENLARGED ELECTRICAL PLAN \ET1,Oil 1/4" = ROUTE TV/TELEPHONE CONDUITS BELOW SLAB (TYPICAL). UNITS 101, 102, 103, 104, 105, 106, 107, 108 EXHAUST FANS TO BE WIRED TO OPERATE CONSTANTLY AT LOW SPEED AND INCREASE TO PRESET HIGH SPEED OPEN ACTIVATION OF WALL SWITCH. PROVIDE DUPLEX RECEPTACLE UNDER SINK FOR DISHWASHER. COORDINATE EXACT LOCATION OF CONDENSING UNIT WITH MECHANICAL CONTRACTOR AND PROVIDE WALL—MOUNTED DISCONNECT SWITCH ADJACENT TO UNIT, CIRCUITED AS SHOWN. RECEPTACLE FOR GAS WATER HEATER. CIRCUIT AS SHOWN. COORDINATE LOCATION WITH PLUMBING CONTRACTOR. UNIT WILL COME WITH CORD AND PLUG INSTALLED. COORDINATE INSTALLATION WITH LOCAL UTILITY COMPANY. REFER TO SITE PLAN E2.0 FOR ADDITIONAL INFORMATION. COORDINATE FUSE TYPE REQUIRED WITH ENGINEER, UTILITY, AND SWITCHGEAR MANUFACTURER. TH MTRS MAIN SWITCH TO NYSEG UTILITY POLE - MOUNTED TRANSFORMERS. SEE ONE -LINE ABOVE AND SITE PLAN. COORDINATE INSTALLATION WITH NYSEG. PROVIDE RECEPTACLE IN A ' . • ` 1 T ,; r4 i ' I T #101 AND #106 OF u 0 I R I A E I SAL 0 y I ' L c I G C s C O . "EC PTACLE SHALL BE C E S E F 0 i C E S PANEL IN HALLWAY CEILING. CONNECT TO CIRCUIT ORIGINATING AT ONE POLE OF BREAKER AT HOUSE METER. ROUTE CIRCUIT SO THAT DEMISING WALLS ARE NOT PENETRATED. ROUTE POWER FOR TYPE 'T' (UNSWITCHED) EXTERIOR FIXTURES THROUGH PHOTOCELL MOUNTED HIGH ON THE BUI ►1 G E I1R. IU T PHOTOC L ON NO TH SIDE OF BUILDING. CIRCUIT VIA ONE POLE OF BREAKER AT HOUSE METER. YPICAL TOWNHOME ERS 120/240V PHASE "IN" AND "OUT", 60 A P 2—POLE BREAKER METER. PROVIDE 20 AMP, 2 -POLE BR KER TO SERVE RADON FANS AND TYPE 'T LIGHTS. 1 2 3 9 IS "HOUSE" TOWNHOME FIRST FLOOR :T1' 1/8" = 1'-0" BUILDING 'A' SHOWN. BUILDING 'B' SIMILAR. 5 6 ROUTE TOWNHOME FEEDERS UNDERSLAB IN PVC (TYPICAL). SEE TABLE ABOVE FOR SIZE. v 7 8 9 10 Architecture Planning Interior Design 217 North Aurora Street Ithaca NY 14850 p 607.273.7600 f 607.273.0475 DOHN A. S1 S, P.E. Consulting Ele Engineer, NYS PE License #068705 5 Archer Lane Kissimmee, FL 34746 (407)404-0790 Warning, it is a violation of the NY State Education Law for any person to alter this document in any way, unless acting under the direction of a licensed professional engineer. If a document bearing the seal of an engineer is altered, thealtering engineer shall affix to the document their seal and the notation "altered by" followed by their signature and the date of such alteration, and a specific description of the alteration. DEMCO NEW YORK CORP. ELECTRICAL CONTRACTORS 6701 MANLIUS CENTER RD EAST SYRACUSE, NEW YORK 13057 REVISION SCHEDULE NAME �DATE Q ADDENDUM #2 9/15/14 STONE QUARRY APARTMENTS DATE: PROJECT: OTHER: Z W 2 F -- Lu 0Z 1- C/) 18 JULY 2014 2012059 THACA, NY DRAWN BY: SS, BR Townhome Enlarged Unit 1st & 2nd Floor Electrical Plans ET1.0 A3 F E D C B 4 5 6 7 10 FURN-A PANEL: TYPICAL APT LOAD CENTER 'API' 60A, M.L.O. FLUSH MOUNTED LOC: UNIT ENTRY 120 / 208V, 1 PH, 3W BOTTOM FEED CKT. NO DESCRIPTION CONN VA LOAD WIRE SIZE BREAKER PHASE BREAKER WIRE SIZE CONN VA LOAD DESCRIPTION CKT, NO TRIP POLE A B POLE TRIP 1 RANGE 1,800 20A 1 X -- SPACE 2 3 SPACE -- -- -- X -- SPACE 4 5 DISHWASHER 1,080 20A 1 X 2 20A 1,248 CONDENSING UNIT ACC -1 6 7 KITCHEN SMALL APPLIANCE 1 1,500 20A 1 X 1,248 CONDENSING UNIT ACC -1 8 9 KITCHEN SMALL APPLIANCE 2 1,500 20A 1 X 1 15A 1,093 FURNACE FURN-A 10 11 DINING ROOM 20A* 1 X 1 15A* GENERAL LIGHTING 1 12 13 BATHROOM 20A 1 X 1 15A* GENERAL LIGHTING 2 14 15 SPACE -- -- -- I X -- -- -- SPACE 16 = PROVIDE ARC -FAULT CIRCUIT INTERRUPTER BREAKER PANEL: TYPICAL APT LOAD CENTER 'AP2' 60A, M.L.O. FLUSH MOUNTED LOC: UNIT ENTRY 120 / 208V, 1PH, 3W BOTTOM FEED CKT. NO DESCRIPTION CONN VA LOAD WIRE SIZE BREAKER PHASE BREAKER WIRE SIZE CONN VA LOAD DESCRIPTION CKT. NO TRIP POLE A B POLE TRIP 1 RANGE 1,800 20A 1 X -- SPACE 2 3 SPACE -- -- -- X -- SPACE 4 5 DISHWASHER 1,080 20A 1 X 2 20A 1,248 CONDENSING UNIT ACC -1 6 7 KITCHEN SMALL APPLIANCE 1 1,500 20A 1 X 1,248 CONDENSING UNIT ACC -1 8 9 KITCHEN SMALL APPLIANCE 2 1500 20A 1 X 1 15A 1,093 FURNACE FURN-A 10 11 DINING ROOM 20A* 1 X 1 15A* GENERAL LIGHTING 1 12 13 BATHROOM 20A 1 X 1 15A* GENERAL LIGHTING 2 14 15 TOILET 20A 1 I X -- -- -- SPACE 16 * = PROVIDE ARC -FAULT CIRCUIT INTERRUPTER BREAKER GENERAL NOTES: A. RECEPTACLE PLACEMENT TO MEET THE REQUIREMENTS OF NATIONAL ELECTRIC CODE (NEC), ARTICLE 210.52. COORDINATE KITCHEN COUNTER RECEPTACLE LOCATIONS WITH COUNTERTOP/ BACKSPLASH HEIGHTS. HORIZONTAL LOCATION IS CRITICAL AND MUST MEET THE REQUIREMENTS OF NEC ARTICLE 210.52 (C). C. COORDINATE BATHROOM RECEPTACLE LOCATIONS WITH ARCHITECTURAL ELEVATIONS AND ACCESSORIES TO BE INSTALLED. D. LOADCENTERS TO OPEN SIDE OF WALL SHOWN. E. PER NEC ARTICLE 406.11, ALL 120 -VOLT RECEPTACLES WITHIN THE DWELLING UNITS WILL BE OF THE TAMPER-RESISTANT STYLE. ® ALERT THE GENERAL CONTRACTOR TO ANY WIRING CONFLICTS DUE TO PANEL LOCATIONS AT AREAS WITH TRUSSES DIRECTLY OVERHEAD. G. REFER TO ROOF PLAN (2:EA2.1) FOR AIR CONDITIONING CONDENSING UNIT LOCATIONS. CONFIRM PROPER UNIT FOR EACH APARTMENT WITH MECHANICAL CONTRACTOR. H. APARTMENT LOADCENTERS SHALL BE MOUNTED SO THAT HIGHEST CIRCUIT BREAKER IS LOCATED 48" ABOVE FINISHED FLOOR ELEVATION. KEYED NOTES FOR EA4.2: Architecture Planning Interior Design 217 North Aurora Street Ithaca NY 14850 p 607.273.7600 f 607.273.0475 DOHN A. SI S, P.E. F OLOCATION OF 3 -PORT INCOMING LOW VOLTAGE SERVICES WALL PLATE. SEE RISER (2:E1.1) FOR ADDITIONAL INFORMATION. O2 EXHAUST FANS TO BE WIRED TO OPERATE CONSTANTLY AT LOW SPEED AND INCREASE TO PRESET HIGH SPEED OPEN ACTIVATION OF WALL SWITCH. SWITCH LIGHT SEPARATELY. O3 PROVIDE DUPLEX RECEPTACLE UNDER SINK FOR DISHWASHER. Consulting EleArcher Lane Engineer, NYS PE Kissimmee, FL 34746 License #068705 (407) 404-0790 Warning, it is a violation of the. NY State Education Law or any person to alter this document in any way, unless acting under the direction of a licensed professional engineer. If a document bearing the seal of an engineer is. ahered the altering engineer shall affix to the document. theirseal and the notation "altered by" followed by their signature and the date of such alteration, and a specific description of the alteration. DEMCO NEW YORK CORP. ELECTRICAL CONTRACTORS 6701 MANLIUS CENTER RD EAST SYRACUSE, NEW YORK 13057 O4 FIRE ALARM 24 -VOLT SYSTEM DEVICES OR FUTURE DEVICE LOCATION. REFER TO EA3.0 FOR OVERALL SYSTEM LAYOUT. E REVISION SCHEDULE DATE A ADDENDUM #2 9/15/14 D BR VISITABLE & ADAPTAB E UN T ELECTRICAL PLAN 4" = 1'-0" UNIT 332 HOOD K 12 FURN-A G FI AC STONE QUARRY APARTMENTS DATE: C STONE QUARRY APARTMENT PROJECT: OTHER: 8 JULY 2014 2012059 DRAWN BY: 2 2BR VISITAB E ADAPTABLE UNIT ELECTRICAL PLAN 1/4" = 1'-0" UNIT 225 2BR VISITABLE & ADAPTABLE UNIT ELECTRICAL PLAN �A4, 1/4" = 1'-0" UNITS 228, 335 SS, BR Apartment Enlarged Unit 2nd & 3rd Floor A Electrical Plans EA4.2 A3 10 FURN-A 10 GENERAL NOTES: A. RECEPTACLE PLACEMENT TO MEET THE REQUIREMENTS OF NATIONAL ELECTRIC CODE (NEC), ARTICLE 210.52. B. COORDINATE KITCHEN COUNTER RECEPTACLE LOCATIONS WITH COUNTERTOP/ BACKSPLASH HEIGHTS. HORIZONTAL LOCATION IS CRITICAL AND MUST MEET THE REQUIREMENTS OF NEC ARTICLE 210.52 (C). C. COORDINATE BATHROOM RECEPTACLE LOCATIONS WITH ARCHITECTURAL ELEVATIONS AND ACCESSORIES TO BE INSTALLED. D. LOADCENTERS TO OPEN SIDE OF WALL SHOWN. E. PER NEC ARTICLE 406.11, ALL 120 -VOLT RECEPTACLES WITHIN THE DWELLING UNITS WILL BE OF THE TAMPER-RESISTANT STYLE. ALERT THE GENERAL CONTRACTOR TO ANY WIRING CONFLICTS DUE TO PANEL LOCATIONS AT AREAS WITH TRUSSES DIRECTLY OVERHEAD. G. REFER TO ROOF PLAN (2: .1) FOR AIR CONDITIONING CONDENSING UNIT LOCATIONS. CONFIRM PROPER UNIT FOR EACH APARTMENT WITH MECHANICAL CONTRACTOR. APARTMENT LOADCENTERS SHALL BE MOUNTED SO THAT HIGHEST CIRCUIT BREAKER IS LOCATED 48" ABOVE FINISHED FLOOR ELEVATION. Architecture Planning Interior Design 217 North Aurora Street Ithaca NY 14850 p 607.273.7600 f 607.273.0475 DOHN A. S KEYED NOTES FOR EA4.1: Oj LOCATION OF 3 -PORT INCOMING LOW VOLTAGE SERVICES WALL PLATE. SEE RISER (2:E1.1) FOR ADDITIONAL INFORMATION. O2 EXHAUST FANS TO BE WIRED TO OPERATE CONSTANTLY AT LOW SPEED AND INCREASE TO PRESET HIGH SPEED OPEN ACTIVATION OF WALL SWITCH. SWITCH LIGHT SEPARATELY. PROVIDE DUPLEX RECEPTACLE UNDER SINK FOR DISHWASHER. Consulting Ele Engineer, NYS PE License #068705 5 Archer Lane Kissimmee, FL 34746 (407) 404-0790 Warning, it is a violation of the NY State Education Law for any person to alter this document in any way, unless acting under the direction of a licensed professional engineer. If a document bearing the seal of an engineer is altered, the altering engineer shall affix to the document their seal and the notation "altered by" followed by their signature and the date of such alteration, and a specific description of the alteration. FIRE ALARM 24 -VOLT SYSTEM DEVICES OR FUTURE DEVICE LOCATION. REFER TO EA3.0 FOR OVERALL SYSTEM LAYOUT. DEMCO NEW YORK CORP. ELECTRICAL CONTRACTORS 6701 MANLIUS CENTER RD EAST SYRACUSE, NEW YORK 13057 REVISION SCHEDULE NAME DATE A ADDENDUM #2 9/15/14 2BR VISITABLE & ADAPTABLE UNIT ELECTRICAL PLAN UNITS 227, 334 2BR VISITABLE & ADAPTABLE UNIT ELECTRICAL PLAN UNITS 222, 329 FURN-A 10 DATE: PROJECT: OTHER: DRAWN BY: 18 JULY 2014 2012059 1 BR VISITABLE & ADAPTABLE UNIT E ECTRIAL PLAN A4. 1/4" = 11-0" UNITS 223,224,330,331 2BR VISITABLE &ADAPTABLE UNIT ELECTRICAL PLAN UNITS 226, 333 Apartment Enlarged Unit 2nd & 3rd Floor Electrical Plans 2 4 6 7 8 9 10 2 4 5 6 7 8 GENERAL NOTES: A. RECEPTACLE PLACEMENT TO MEET THE REQUIREMENTS OF NATIONAL ELECTRIC CODE (NEC), ARTICLE 210.52. B. COORDINATE KITCHEN COUNTER RECEPTACLE LOCATIONS WITH COUNTERTOP/ BACKSPLASH HEIGHTS. HORIZONTAL LOCATION IS CRITICAL AND MUST MEET THE REQUIREMENTS OF NEC ARTICLE 210.52 (C). C. COORDINATE BATHROOM RECEPTACLE LOCATIONS WITH ARCHITECTURAL ELEVATIONS AND ACCESSORIES TO BE INSTALLED. D. LOADCENTERS TO OPEN SIDE OF WALL SHOWN. E. PER NEC ARTICLE 406.11, ALL 120 -VOLT RECEPTACLES WITHIN THE DWELLING UNITS WILL BE OF THE TAMPER-RESISTANT STYLE. ALERT THE GENERAL CONTRACTOR TO ANY WIRING CONFLICTS DUE TO PANEL LOCATIONS AT AREAS WITH TRUSSES DIRECTLY OVERHEAD. G. REFER TO ROOF PLAN (2: .1) FOR AIR CONDITIONING CONDENSING UNIT LOCATIONS. CONFIRM PROPER UNIT FOR EACH APARTMENT WITH ECHANICAL ONTRACTOR. H. APARTMENT LOADCENTERS SHALL BE MOUNTED SO THAT HIGHEST CIRCUIT BREAKER IS LOCATED 48" ABOVE FINISHED FLOOR ELEVATION. KEYED NOTES FOR EA4.0: 217 North Aurora Street Ithaca NY 14850 p 607.273.7600 f 607.273.0475 DOHN A. SIMS, P.E. OLOCATION OF 3 -PORT INCOMING LOW VOLTAGE SERVICES WALL PLATE. SEE RISER (2:E1.1) FOR ADDITIONAL INFORMATION. OEXHAUST FANS TO BE WIRED TO OPERATE CONSTANTLY AT LOW SPEED AND INCREASE TO PRESET HIGH SPEED OPEN ACTIVATION OF WALL SWITCH. SWITCH LIGHT SEPARATELY. O3 PROVIDE DUPLEX RECEPTACLE UNDER SINK FOR DISHWASHER. OFIRE ALARM 24 -VOLT SYSTEM DEVICES OR FUTURE DEVICE LOCATION. REFER TO EA3.0 FOR OVERALL SYSTEM LAYOUT. OCIRCUIT POWER FOR RANGE HOOD THROUGH WALL SWITCH AT MOBILITY IMPAIRED UNITS ONLY. INSTALL AUDIO/VISUAL DOOR ANNUNCIATOR AT UNIT #120 ONLY. CONNECT TO CIRCUIT SHOWN. Consulting Ele r 5 Archer Lane Engineer, NYS PE Kissimmee, FL 34746 License #068705 (407) 404-0790 Warning, it is a violation of the NY State Education Law for any person to alter this document in any way, unless acting under the direction of a licensed professional engineer. If a document bearing the seal of an engineer is altered, the altering engineer shalaffix to the document their seal and the notation "altered by" followed by their signature and the dateof such alteration, and a specific description of the alteration. DEMCO NEW YORK CORP. ELECTRICAL CONTRACTORS 6701 MANLIUS CENTER RD EAST SYRACUSE, NEW YORK 13057 REVISION SCHEDULE FURN-A 10 HOOD K 12 GFI - AC ADDENDUM #2 9/15/ 2BR MOBILITY IMPAIRED UNIT UNIT 117 + PROVIDE VISUAL S AT THIS LOCATION INSTALL STROBE DEVICE AT THIS LOCATION IN UNIT #120. SEE EA3.0. INSTALL A/V DEVICE AT THIS LOCATION IN UNIT #120. SEE EA3.0. 2 1BR MOBILITY IMPAIRED UNIT A4.(j/ 1/4" = 1'-O" UNITS 119, 120 AC GFI B DATE: 18 JULY 2014 PROJECT: 2012059 OTHER: DRAWN BY: `,` SS, BR FURN-A 10 Apartment Enlarged Unit First Floor Electrical Plans A 3BR V S TABLE ADAPTABLE UNIT A4 0 1/4" = 1'-0" UNIT 118 3BR V SITABLE & ADAPTABLE UNIT A4.0 1/4" = t-0" UNIT 121 9 10 2 4 5 6 7 8 91 10 KEYED NOTES FOR EA3.0: PROVIDE FIRE ALARM CONNECTION FOR MONITORING STATUS OF TAMPER AND FLOW SWITCHES LOCATED AT SPRINKLER SYSTEM VALVES. COORDINATE REQUIREMENTS AND INSTALLATION WITH FIRE PROTECTION CONTRACTOR. PROVIDE FIRE ALARM INTERFACE WITH DOOR ACCESS CONTROL EQUIPMENT SO AS TO ENSURE DOOR(S) WILL BE UNLOCKED UNDER ALARM CONDITION. COORDINATE INSTALLATION WITH DOOR CONTROLS AND ENTRY SYSTEM AS REQUIRED. PROVIDE FIRE ALARM INTERFACE AS REQUIRED FOR ELEVATOR SHUTDOWN / CAR RECALL. COORDINATE LOCATION OF DETECTORS IN ELEVATOR PIT WITH ELEVATOR INSTALLER. CONFIRM LOCATION OF AREA OF RESCUE ASSISTANCE STAIRWELL INTERCOM STATION WITH ARCHITECT AND AUTHORITY HAVING JURISDICTION. PROVIDE ALL CODE -REQUIRED SIGNAGE. PROVIDE DATA JACK ABOVE DROP CEILING FOR WIRELESS ANTENNA (BY OTHERS). GENERAL NOTES: A. COORDINATE ENTIRE INSTALLATION WITH FIRE ALARM SYSTEM SUPPLIER/DESIGNER. REFER TO INSTALLATION PLANS FOR REQUIREMENTS CONCERNING WIRE SIZES, CIRCUITING PATHS, ADDRESSABLE INTERFACE MODULE, ETC. B. MOUNTING HEIGHTS AND LOCATIONS SHALL CONFORM TO THE APPLICABLE REQUIREMENTS OF THE NFPA, ADA AND LOCAL CODES. C. CONFIRM REQUIRED DEVICE QUANTITIES WITH LOCAL AUTHORITY HAVING JURISDICTION AND FIRE ALARM SYSTEM SUPPLIER/DESIGNER. D. REFER TO ENLARGED APARTMENT UNIT ELECTRICAL PLANS ON SHEETS EA4.0 THROUGH EA4.2 FOR LOW -VOLTAGE DEVICE LOCATIONS WITHIN THE APARTMENT UNITS. MOUNT DETECTOR ONE LEVEL UP AT ATTIC/ROOF LANDING 3w Architecture Planning Interior Design 217 North Aurora Street Ithaca NY 14850 p 607.273.7600 f 607.273.0475 F Consulting Ele `."'="" 5 Archer Lane Engineer, NYS PE Kissimmee, FL 34746 License #068705 (407) 404-0790 Warning, it is a violation of the NY State Education Law for any person to alter this document in any way,unless acting underthe directionof a licensed professional engineer. If a document bearing the seal of an engineer is altered, thealtering engineer shall affix to the document their seal and the notation "altered by" followed by their signature and the date of such alteration, and a specific description of the alteration. DEMCO NEW YORK CORP. ELECTRICAL CONTRACTORS 6701 MANLIUS CENTER RD EAST SYRACUSE, NEW YORK 13057 E REVISION SCHEDULE NA DATE A ADDENDUM #2 9/15/14 D STONE QUARRY APARTMENTS RTMENTS, LLC 0 CO DATE: PROJECT: OTHER: DRAWN BY: APARTMENT BUILDING - FIRST FLOOR � 1 ELECTRICAL LOW VOLTAGE SYSTEMS PLAN APARTMENT BUI DING - SECOND FLOOR 2 ELECTRICAL LOW VOLTAGE SYSTEMS PLAN APARTMENT BUILDING - THIRD FLOOR ELECTRICAL LOW VOLTAGE SYSTEMS PLAN 18 JULY 2014 2012059 SS, BR Apartment Electrical Low Voltage Systems Floor Plans EA3.0 A3 FEEDER: #2 AWG ALUM SER FLOOR PLAN: 1 /EA4.1 PANEL SCHEDULE: AP1 FEEDER: #2 AWG ALUM SER FLOOR P 3/EA4.1 PANEL SCHEL BILE: AP1 FEEDER: ALUM SER FLOOR PLAN: 2/E A4.1 !`PANEL SCHEDULE: 'API FEEDER: #4,AWC .UP SER FLOOR PLAN: 3/EA4.1 PANEL SCHEDULE: AP1 FEEDER: #4 AWG ALUM SER FLOOR PLAN: 4/EA4.1 PANEL SCHEDULE: AP1 FEEDER;: #A AWG ALUM SER A 1 DSS -A aA 1 D 25/2 AROIFUNIT FLOOR ELANr 1 /EA4.2 PANEL S C RULE: AP1 FEEDER: #4 AWG ALUM APARTMENT BUILDING - THIRD FLOOR ELECTRICAL POWER & LIGHTING PLAN 1 /8" = 1'-0" 1.60/2P 60/2P DP -19 60/2P RF -A P-25/27 60/2P 160/2P 60/2P 60/2P 60/2P 60/2P 60/2P 60/2P 60/2P 60/2P �C € DSS A ■ 60/2P P-3 ;_DSS P F ■ <60/2P DP -25/28 SS -A 60/2P MDP -25/27 APARTMENT BUILDING - ATTIC / ROOF ELECTRICAL POWER & LIGHTING PLAN /8" = 1'-0" 8 9 KEYED NOTES FOR EA2.I: CIRCUIT ALL. ITEMS THIS FLOOR TO PANEL DP ON 1ST FLOOR, CIRCUIT AS INDICATED, UNLESS OTHERWISE NOTED. REFER TO SHEET EA1.0 FOR PANEL SCHEDULE. CONNECT WALL -MOUNTED BATTERY LIGHTS TO LIGHTING CIRCUIT SERVING SAME SPACE, AHEAD OF ANY LOCAL SWITCHING/OCCUPANCY SENSOR(S). THIS FIXTURE IS TO BE CIRCUITED SO AS TO BE CONTROLLED BY CORRIDOR OCCUPANCY SENSOR. EACH SENSOR WILL CONTROL ONLY THE FIXTURES IN THIS END OF THE CORRIDOR. REMAINING FIXTURES ARE TO REMAIN ON AT ALL TIMES. COORDINATE LOCATION OF LIGHTS, RECEPTACLES AND SWITCHES LOCATED IN ROOF WELL WITH MECHANICAL CONTRACTOR. VERIFY THAT EACH ACC -1 UNIT IS CIRCUITED FROM PANEL WITHIN THE APARTMENT THAT IT SERVES. PROVIDE KEYLESS LAMP HOLDER WITH SELF -BALLASTED LAMP AT ENTRANCE TO ATTIC SWITCH FROM OUTSIDE DOOR. GENERAL NOTES 1. WIRING TYPES AND SIZES SHALL CONFORM TO THE APPLICABLE ARTICLES OF THE NATIONAL ELECTRICAL CODE. MINIMUM WIRE SIZE SHALL BE #12 AWG. FOR CIRCUIT LENGTHS OVER 100', USE THE NEXT HIGHER SIZE. 2. SIZE CIRCUIT WIRING FOR MOTORIZED EQUIPMENT TO ACCOMMODATE VOLTAGE DROP SO AS TO ASSURE VOLTAGE AT UNIT IS WITHIN OPERATING RANGE OF EQUIPMENT. 10 Architecture Planning Interior Design 217 North Aurora Street Ithaca NY 14850 p 607.273.7600 f 607.273.0475 DOHN A. SI S, P.E. Consulting Ele `'""'=' 5 Archer Lane Engineer, NYS PE Kissimmee, FL 34746 License #068705 (407) 404-0790 Warning, it is a violation of the NY State Education Law for any person to alter this document in any way, unless acting under the direction of a licensed professional engineer. If a document bearing the seal of an engineer is altered, the altering engineer shall affix to the document their seal and the notation "altered by" followed by their signature and the date of such alteration and a specific description of the alteration. DEMCO NEW YORK CORP. ELECTRICAL CONTRACTORS 6701 MANLIUS CENTER RD EAST SYRACUSE, NEW YORK 13057 REVISION SCHEDULE NAME DATE A ADDENDUM #2 9/15/14 STONE QUARRY APARTMENTS STONE QUARRY APARTMENTS, LL F E D ULY 2014 2012059 DRAWN BY: BY: SS, BR Apartment Electrical Power & Lighting A Attic / Roof Plans EA2.1 A3 4 5 6 7 8 9 10 KEYED NOTES FOR EA2.O: GFI WP LP -15 FLOOR PLAN: 3/EA4.2 PANEL SCHEDULE: AP1 FEEDER: #2 AWG ALUM SER FURN-B FLOOR' " N: 4/EA4.0 PANEL SCHEDULE: AP2 FE a R: #2 AWG ALUM SER WP LP -15 GFI i TYP.6 FLOOR PLAN: 1/EA4.1 PANEL SCHEDULE: AP1 FEEDER: #4 AWG ALUM SER GFI AC 22/24 FLOOR PLAN: 3/EA4.1 PANEL SCHEDULE: API FEEDER: #4 AWG ALUM SER OOR PLAN: 2/EA4. ANEL SCHEDULE: .API FEEDER: #4 AWG ALUM SE FLOOR PLAN: 2/EA4.0 PANEL SCHEDULE: API:; FEEDER: #4 AWG ALUM SER FLOOR PLAN: 1/EA4`0"" PANEL SCHEDULE: AP1 FEEDER: #4 AWG ALUM SER FLOOR PLAN: 3/EA4.1 PANEL. SCHEDULE: AP1 FEEDER: #4 AWGALUM:SER FLOOR PLAN: 4/EA4.2 PANEL SCHEDULE: API FEEDER: #4 AWG ALUM SER FLOOR PLAN: 2/EA4.Oi PANEL SCHEDULE: API" FEEDER: #4 AWG ALUM SERE CIRCUIT ALL ITEMS WITHIN THIS BOUNDARY TO PANEL LP ON 1ST FLOOR, CIRCUIT # AS INDICATED. CIRCUIT ALL OTHER ITEMS TO PANEL MDP ON 1ST FLOOR, CIRCUIT # AS INDICATED, UNLESS OTHERWISE NOTED. REFER TO SHEET EA1.0 FOR PANEL SCHEDULES. CONNECT WALL—MOUNTED BATTERY LIGHTS TO LIGHTING CIRCUIT SERVING SAME SPACE. AHEAD OF ANY LOCAL SWITCHING/OCCUPANCY SENSOR(S). THIS FIXTURE IS TO BE CIRCUITED SO AS TO BE CONTROLLED BY CORRIDOR OCCUPANCY SENSOR. EACH SENSOR WILL CONTROL ONLY THE FIXTURES IN THIS END OF THE CORRIDOR. REMAINING FIXTURES ARE TO REMAIN ON AT ALL TIMES. CCTV, DVR, CAMERA POWER SUPPLIES, AND SURGE SUPPRESSORS. COORDINATE INSTALLATION WITH SYSTEM SUPPLIER. REFER TO RISER DIAGRAM (3:E1.1) FOR ADDITIONAL INFORMATION. TELEPHONE—BASED DOOR ENTRY SYSTEM — "NO—PHONE—BILL" STYLE. COORDINATE INSTALLATION WITH SYSTEM SUPPLIER AND TELEPHONE COMPANY. REFER TO RISER DIAGRAM (1:E1.1) FOR ADDITIONAL INFORMATION. PROVIDE PLYWOOD BACKBOARDS AND POWER FOR CAN, TELEPHONE AND INTERNET SERVICE EQUIPMENT AS REQUIRED. COORDINATE INSTALLATION WITH SERVICE PROVIDERS. REFER TO RISER DIAGRAM (1:E1.1) FOR ADDITIONAL INFORMATION. PROVIDE GROUNDING FOR SYSTEMS AS REQUIRED FROM GROUND BUS AT MAIN SERVICE POINT. CIRCUIT EXTERIOR LIGHT U P C RIOR TO PHO 0 E L, ' UN I I VA AN INV R ER SYS EM 0 T D I HE ELECTRIC ROOM, ENVOY LIGHTING MODEL #SPS -1 10 125—S OR SIMILAR (120—VOLT, 110 WATTS, 90—MINUTE OPERATION TO PROVIDE BACKUP POWER TO EXTERIOR EGRESS LIGHTING. COORDINATE LOCATIONS OF ELEVATOR PIT LIGHT, SWITCH, AND GFI RECEPTACLE WITH ELEVATOR INSTALLATION. CONNECT EXHAUST FAN TO LOCAL LIGHTING CIRCUIT. PROVIDE POWER TO DOOR CONTROLS AS REQUIRED. PROVIDE RACEWAY(S) AND BACKBOX(ES) FOR ADA PUSH PADDLE(S). COORDINATE ALL WORK WITH ARCHITECT AND DOOR INSTALLER. PROVIDE DEDICATED CIRCUIT TO EACH 1/2 RECEPTACLE AS SHOWN. MAKE SURE LINKS ARE REMOVED FROM RECEPTACLES SO THAT EACH OUTLET OF A DUPLEX DEVICE WILL BE ON ITS OWN CIRCUIT. COORDINATE MOUNTING HEIGHT OF RECEPTACLES WITH EQUIPMENT TO BE PROVIDED. GENERAL NOTES 1, WIRING TYPES AND SIZES SHALL CONFORM TO THE APPLICABLE ARTICLES OF THE NATIONAL ELECTRICAL CODE, MINIMUM WIRE SIZE SHALL BE #12 AWG. FOR CIRCUIT LENGTHS OVER 100', USE THE NEXT HIGHER SIZE. 2. SIZE CIRCUIT WIRING FOR MOTORIZED EQUIPMENT TO ACCOMMODATE VOLTAGE DROP SO AS TO ASSURE VOLTAGE AT UNIT IS WITHIN OPERATING RANGE OF EQUIPMENT. OS , HOEUSE":APT MAIN MTRS SWITCH 29 'WP Fl MDP 21/23 VIA ROOF UNIT FLOOR FLOOR PLAN: 2/EA4.2 PANEL SCHEDULE: API FEEDER: # AWG ALUM sER APARTMENT BUILDING FIRST FLOOR ELECTRICAL POWER & LIGHTING PLAN 1 /8r" = 1 r -Or" APARTMENT BUILDING - SECOND FLOOR ELECTRICAL POWER & LIGHTING PLAN 2.0 1/8" = 1'-O" 75 1-hruvvay Architecture Planning Interior Design 217 North Aurora Street Ithaca NY 14850 p 607.273.7600 f 607.273.0475 Consulting Ele • tSArcher Lane Engineer, NYS PE Kissimmee, FL 34746 License #068705 (407) 404-0790 Warning, it is a violation of the NY State Education Law for any person to alter this document in any way, unless acting under the direction of a licensed professional engineer. If a: document bearing the seal of an engineer is altered, the altering engineer shall affix to the document their seal and the notation "altered by" followed by their signature and the date of such alteration: and a specific description of the alteration. DEMCO NEW YORK CORP. ELECTRICAL CONTRACTORS 6701 MANLIUS CENTER RD EAST SYRACUSE; NEW YORK 13057 REVISION SCHEDULE NAME DATE A ADDENDUM #2 9/15/14 STONE QUARRY APARTMENTS J RTMENTS STONE QUARRY AP E D DATE: 8 JULY 2014 PROJECT: 2012059 OTHER: DRAWN BY: SS. BR Apartment Electrical Power & Lighting A Floor Plans EA2.0 A3 10 ..�3w.. IL 3g l A 131> A 13 17 x... FLOOR PLAN: 3/EA4.2 PANEL SCHEDULE: AP1 FEEDER: #2 AWG ALUM SER FURN-B FLOOR' " N: 4/EA4.0 PANEL SCHEDULE: AP2 FE a R: #2 AWG ALUM SER WP LP -15 GFI i TYP.6 FLOOR PLAN: 1/EA4.1 PANEL SCHEDULE: AP1 FEEDER: #4 AWG ALUM SER GFI AC 22/24 FLOOR PLAN: 3/EA4.1 PANEL SCHEDULE: API FEEDER: #4 AWG ALUM SER OOR PLAN: 2/EA4. ANEL SCHEDULE: .API FEEDER: #4 AWG ALUM SE FLOOR PLAN: 2/EA4.0 PANEL SCHEDULE: API:; FEEDER: #4 AWG ALUM SER FLOOR PLAN: 1/EA4`0"" PANEL SCHEDULE: AP1 FEEDER: #4 AWG ALUM SER FLOOR PLAN: 3/EA4.1 PANEL. SCHEDULE: AP1 FEEDER: #4 AWGALUM:SER FLOOR PLAN: 4/EA4.2 PANEL SCHEDULE: API FEEDER: #4 AWG ALUM SER FLOOR PLAN: 2/EA4.Oi PANEL SCHEDULE: API" FEEDER: #4 AWG ALUM SERE CIRCUIT ALL ITEMS WITHIN THIS BOUNDARY TO PANEL LP ON 1ST FLOOR, CIRCUIT # AS INDICATED. CIRCUIT ALL OTHER ITEMS TO PANEL MDP ON 1ST FLOOR, CIRCUIT # AS INDICATED, UNLESS OTHERWISE NOTED. REFER TO SHEET EA1.0 FOR PANEL SCHEDULES. CONNECT WALL—MOUNTED BATTERY LIGHTS TO LIGHTING CIRCUIT SERVING SAME SPACE. AHEAD OF ANY LOCAL SWITCHING/OCCUPANCY SENSOR(S). THIS FIXTURE IS TO BE CIRCUITED SO AS TO BE CONTROLLED BY CORRIDOR OCCUPANCY SENSOR. EACH SENSOR WILL CONTROL ONLY THE FIXTURES IN THIS END OF THE CORRIDOR. REMAINING FIXTURES ARE TO REMAIN ON AT ALL TIMES. CCTV, DVR, CAMERA POWER SUPPLIES, AND SURGE SUPPRESSORS. COORDINATE INSTALLATION WITH SYSTEM SUPPLIER. REFER TO RISER DIAGRAM (3:E1.1) FOR ADDITIONAL INFORMATION. TELEPHONE—BASED DOOR ENTRY SYSTEM — "NO—PHONE—BILL" STYLE. COORDINATE INSTALLATION WITH SYSTEM SUPPLIER AND TELEPHONE COMPANY. REFER TO RISER DIAGRAM (1:E1.1) FOR ADDITIONAL INFORMATION. PROVIDE PLYWOOD BACKBOARDS AND POWER FOR CAN, TELEPHONE AND INTERNET SERVICE EQUIPMENT AS REQUIRED. COORDINATE INSTALLATION WITH SERVICE PROVIDERS. REFER TO RISER DIAGRAM (1:E1.1) FOR ADDITIONAL INFORMATION. PROVIDE GROUNDING FOR SYSTEMS AS REQUIRED FROM GROUND BUS AT MAIN SERVICE POINT. CIRCUIT EXTERIOR LIGHT U P C RIOR TO PHO 0 E L, ' UN I I VA AN INV R ER SYS EM 0 T D I HE ELECTRIC ROOM, ENVOY LIGHTING MODEL #SPS -1 10 125—S OR SIMILAR (120—VOLT, 110 WATTS, 90—MINUTE OPERATION TO PROVIDE BACKUP POWER TO EXTERIOR EGRESS LIGHTING. COORDINATE LOCATIONS OF ELEVATOR PIT LIGHT, SWITCH, AND GFI RECEPTACLE WITH ELEVATOR INSTALLATION. CONNECT EXHAUST FAN TO LOCAL LIGHTING CIRCUIT. PROVIDE POWER TO DOOR CONTROLS AS REQUIRED. PROVIDE RACEWAY(S) AND BACKBOX(ES) FOR ADA PUSH PADDLE(S). COORDINATE ALL WORK WITH ARCHITECT AND DOOR INSTALLER. PROVIDE DEDICATED CIRCUIT TO EACH 1/2 RECEPTACLE AS SHOWN. MAKE SURE LINKS ARE REMOVED FROM RECEPTACLES SO THAT EACH OUTLET OF A DUPLEX DEVICE WILL BE ON ITS OWN CIRCUIT. COORDINATE MOUNTING HEIGHT OF RECEPTACLES WITH EQUIPMENT TO BE PROVIDED. GENERAL NOTES 1, WIRING TYPES AND SIZES SHALL CONFORM TO THE APPLICABLE ARTICLES OF THE NATIONAL ELECTRICAL CODE, MINIMUM WIRE SIZE SHALL BE #12 AWG. FOR CIRCUIT LENGTHS OVER 100', USE THE NEXT HIGHER SIZE. 2. SIZE CIRCUIT WIRING FOR MOTORIZED EQUIPMENT TO ACCOMMODATE VOLTAGE DROP SO AS TO ASSURE VOLTAGE AT UNIT IS WITHIN OPERATING RANGE OF EQUIPMENT. OS , HOEUSE":APT MAIN MTRS SWITCH 29 'WP Fl MDP 21/23 VIA ROOF UNIT FLOOR FLOOR PLAN: 2/EA4.2 PANEL SCHEDULE: API FEEDER: # AWG ALUM sER APARTMENT BUILDING FIRST FLOOR ELECTRICAL POWER & LIGHTING PLAN 1 /8r" = 1 r -Or" APARTMENT BUILDING - SECOND FLOOR ELECTRICAL POWER & LIGHTING PLAN 2.0 1/8" = 1'-O" 75 1-hruvvay Architecture Planning Interior Design 217 North Aurora Street Ithaca NY 14850 p 607.273.7600 f 607.273.0475 Consulting Ele • tSArcher Lane Engineer, NYS PE Kissimmee, FL 34746 License #068705 (407) 404-0790 Warning, it is a violation of the NY State Education Law for any person to alter this document in any way, unless acting under the direction of a licensed professional engineer. If a: document bearing the seal of an engineer is altered, the altering engineer shall affix to the document their seal and the notation "altered by" followed by their signature and the date of such alteration: and a specific description of the alteration. DEMCO NEW YORK CORP. ELECTRICAL CONTRACTORS 6701 MANLIUS CENTER RD EAST SYRACUSE; NEW YORK 13057 REVISION SCHEDULE NAME DATE A ADDENDUM #2 9/15/14 STONE QUARRY APARTMENTS J RTMENTS STONE QUARRY AP E D DATE: 8 JULY 2014 PROJECT: 2012059 OTHER: DRAWN BY: SS. BR Apartment Electrical Power & Lighting A Floor Plans EA2.0 A3 10 5 6 7 8 PANEL: MDP 400A, M.L.O. SURFACE MOUNTED LOC: ELEC M101 120 / 208V, 3PH, 4W BOTTOM FEED CKT. NO DESCRIPTION CONN VA LOAD WIRE SIZE BREAKER PHASE BREAKER WIRE SIZE CONN VA LOAD DESCRIPTION CKT. NO TRIP POLE A B C POLE TRIP 1 ELEVATOR 9,847 200A 3 X 3 150A 10,125 LAUNDRY SUB -PANEL 2 3 ELEVATOR 9,847 -- -- X -- -- 10,125 LAUNDRY SUB -PANEL 4 5 ELEVATOR 9,847 -_ -- X -- -- 10,125 LAUNDRY SUB -PANEL 6 7 (SHUNT TRIP) __ -- -- X 2 15A 1,000 STAIR S101 - HEATER: CUH-S1 8 9 1ST FLR - CORRIDOR LGTS 950 20A 1 X -_ -_ 1,000 STAIR S101 - HEATER: CUH-S1 10 11 2ND FLR - CORRIDOR LGTS 570 20A 1 X 1 20A 500 DOOR ENTRY SYSTEM 12 13 3RD FLR - CORRIDOR LGTS 675 20A 1 X 1 20A 500 FACP 14 15 SPARE 1,080 20A 1 X 1 20A 500 AREA OF RESCUE INTERCOM 16 17 1ST FLR, EXTERIOR - RCPT 1080 20A 1 X 1 20A -- TV, TELEBOARD - RCPT 18 19 2ND FLR, 3RD FLR, ROOF - RCPT 1080 20A 1 X 1 20A -- TV, TELEBOARD - RCPT 20 21 2ND FLR DSS -A 950 15A 2 X 2 15A 1000 VESTIBULE - HEATER: CUH-L1 22 23 2ND FLR DSS -A 950 15A 1 1 15A 1000 VESTIBULE - HEATER: CUH-L1 24 25 3RD FLR DSS -A 950 15A 2 X 2 15A 950 1ST FLR DSS -A 26 27 3RD FLR DSS -A 950 -- -- X -- -- 950 1ST FLR DSS -A 28 29 MECH C, EXTERIOR - RCPT 540 20A 1 X 1 20A 1000 CC POWER SUPPLY 30 31 EXTERIOR - LGTS - BLDG TD 104 20A 1 X 1 20A 500 DOOR CONTROLS 32 33 EXTERIOR - LGTS - SITE 532 20A 1 X SPACE 34 35 SPARE 1000 20A 1 X SPACE 36 37 SPARE 180 20A 1 X SPACE 38 39 SPACE 265 20.E 1 X SPACE 40 41 SPACE 44 20A 1 X SPACE 42 EXISTING NYSEG UTILITY POLE MOUNTED TRANSFORMERS ALUMINUM SER CABLE (TYPICAL) MAIN FUSED DISCONNECT SWITCH 0 0 0 0 0 0 0 60A 120/ 208V 10 0 0 0 10 0 0 2 0 0 4 0 15 0 6 TYPICAL APARTMENT UNIT LOADCENTER O 17 O 8 0 19 HOUSE METER 400A 30 ELECTRICA DISTRIBUTION LAYOUT \A1 NOT TO SCALE MDP 400A 120/208V 30, 4W (4) 500 MCM ALUMINUM XHHW IN 4" CONDUIT LP (4) #2/0 AWG ALUMINUM XHHW (1) #4 AWG ALUMINUM XHHW GROUND IN 2" PVC UNDERSLAB 4 5 9 10 PANEL: LP 225A, M.L.O. FLUSH MOUNTED LOC: LAUNDRY 100G 120 / 208V, 3PH, 4W BOTTOM FEED CKT. NO DESCRIPTION CONN VA LOAD WIRE SIZE BREAKER PHASE BREAKER WIRE SIZE CONN VA LOAD DESCRIPTION CKT. NO TRIP POLE A B C POLE TRIP 1 WASHER (STACKED) 1,380 15A 1 1 15A 1,380 WASHER (STACKED) 2 3 DRYER (STACKED) 1,380 15A 1 X 1 15A 1,380 DRYER (STACKED) 4 5 WASHER (STACKED) 1,380 15A 1 1 15A 1,380 WASHER (STACKED) 6 7 DRYER (STACKED) 1,380 15A 1 X 1 15A 1,380 DRYER (STACKED) 8 9 WASHER (STACKED) 1,380 15A 1 1 15A 750 WASHER (SINGLE) 10 11 DRYER (STACKED) 1380 15A 1 X 1 15A 864 DRYER (SINGLE) 12 13 COMM'TY, LAUNDRY, OFFICE - LGTS 1,920 20A 1 X 1 20A SPARE 14 15 LAUNDRY, CORR, EXTERIOR - RCPT 1,080 20A 1 X 1 20A 300 ELEVATOR CAB. 16 17 COMMUNITY R - RCPT 720 20A 1 X 1 20A 300 ELEVATOR CAB. 18 19 COMMUNITY RM - RCPT 720 20A 1 1 20A 300 ELEVATOR MACHINE RM. 20 21 OFFICE - RCPT 720 20A 1 X 1 20A 300 ELEVATOR PIT 22 23 1ST FLR - FURNACE: FURN-B 1323 15A 1 1 15A 1,127 SUMP PUMP SP -A, 1/2 HP 24 25 ACC -2 3120 45A 2 X 1 20A SPARE 26 27 ACC -2 3120 -- -- X 1 20A SPARE 28 29 MECH A, TOILET - RCPT 720 20A 1 X 1 20A SPARE 30 31 DWH-A 15A 1 X SPACE 32 33 STAIR S100 - HEATER: CUH-S1 1000 15A 2 SPACE 34 35 STAIR S100 - HEATER: CUH-S1 1000 -- -- X SPACE 36 37 RADON FANS RF -A(2) 180 15A 1 X SPACE 38 39 ATTIC, WELL - LGTS 265 20.E 1 SPACE 40 41 EF -3 CORRIDORS (3) 44 20A 1 X SPACE 42 ELECTRICAL EQUIPMENT CONNECTION SCHEDULE TAG DESCRIPTION VOLTAGE kW/HP EF -1 APARTMENT / TOWNHOME FULL BATH EXH FAN/LIGHT 120V 46.9 W EF -2 APARTMENT / TOWNHOME HALF BATH EXH FAN/LIGHT 120V 46.9 W EF -3 COMMON SPACE EXHAUST FAN 120V 46.9 W FURN-A GAS FURNACE - APARTMENTS 120V YHP FURN-B GAS FURNACE - 1ST FLOOR 120V 3/4 HP ACC -1 AIR CONDITIONING CONDENSING UNIT - APARTMENTS 208V/1 6 7 8 CONNECTION TYPE DIRECT CONNECTION DIRECT CONNECTION DIRECT CONNECTION TOGGLE SWITCH AT UNIT TOGGLE SWITCH AT UNIT NOTES NOTE 1,8 NOTE 8 NOTE 4 NAAMPOS 9 10 Architecture Planning Interior Design 217 North Aurora Street Ithaca NY 14850 p 607.273.7600 f 607.273.0475 DOHN A. SI S, P.E. :" ' «5 Archer Lane EngineerC©nsulting, NYSEle PE Kissimmee, FL 34746 License #068705 (407) 404-0790 F Warning, it is a violation of the NY State Education Law for any person to alter this document in any way, unless acting under the direction of a licensed professional engineer. If a document bearing the seal of an engineer is - altered, the altering engineer shall affix to the document their seal and the notation "altered by" followed by their signature and thedate of such alteration,and a specific description of the alteration. DEMCO NEW YORK CORP. ELECTRICAL CONTRACTORS 6701 MANLIUS CENTER RD EAST SYRACUSE, NEW YORK 13057 REVISION SCHEDULE NA E DATE STONE QUARRY APARTMENTS RTMENTS. LL DATE: 8 JULY 2014 PROJECT: 2012059 OTHER: DRAWN BY: SS, BR Apartment Building Panel Schedules and 1 -Line EA1.0 A3 6 7 8 9 10 KEYED NOTES FOR E2.0: COORDINATE POLE RISER INSTALLATION WITH RESPECTIVE UTILITIES (NYSEG VERIZON, TIME WARNER, FLTG) AND PROVIDE AS REQUIRED PER THEIR APPLICABLE STANDARDS. ELECTRIC SERVICE ENTRANCE CONDUITS AND CONDUCTORS. ROUTE UNDERGROUND/ UNDERSLAB TO ROOM MECH C. REFER TO (1:EA1.0) AND (1: .0) FOR FURTHER INFORMATION. ELECTRIC SERVICE ENTRANCE CONDUIT AND CONDUCTORS, AND TOWNHOME METERS. SEE ONE—LINE DIAGRAM ON ET1.0 FOR ADDITIONAL INFORMATION. COORDINATE INSTALLATION WITH ARCHITECTURAL ELEVATIONS. COMMUNICATIONS SERVICE ENTRANCE CONDUITS WITH PULLSTRINGS. ROUTE UNDERGROUND/ UNDERSLAB TO ROOM MECH B. REFER TO (1:E1.1) AND (1: .0) FOR FURTHER INFORMATION. PROVIDE TERMINAL BOXES ON EXTERIOR OF BUILDING PER SERVICE PROVIDERS' REQUIREMENTS. SEE ET1.0 FOR ADDITIONAL INFORMATION. COORDINATE INSTALLATION WITH ARCHITECTURAL ELEVATIONS. PROVIDE POLE. CIRC I AS H ON SPECIFIED OCELL. GENERAL NOTES COORDINATE ALL UNDERGROUND /UNDERSLAB INSTALLATIONS WITH OTHER TRADES. 2. COORDINATE POWER SERVICE INSTALLATIONS WITH NYSEG. 3. COORDINATE COMMUNICATIONS SERVICE INSTALLATIONS WITH APPLICABLE SERVICE PROVIDERS. 4. WORK WITH CCTV SYSTEM SUPPLIER AND OWNER TO ULTIMATELY PROVIDE CAMERA COVERAGE DESIRED (I.E., AIM /ADJUST CAMERA UNITS AS NECESSARY). 5. ROUTE CIRCUIT FOR SITE LIGHTING VIA TIME CLOCK LOCATED IN MECH C AND INTERFACE WITH BUILDING—MOUNTED PHOTOCELL (SEE FLOOR PLANS FOR LOCATION). TIME CLOCK SHALL ALSO CONTROL LIGHTING AT APARTMENT BUILDING COMMON ENTRANCES (TYPE 'G' FIXTURES ON CIRCUIT MDP -31). 6. REFER TO SHEETS . , .0 AND ET1.0 FOR BUILDING—MOUNTED EXTERIOR LIGHT FIXTURES. Architecture Planning Interior Design 217 North Aurora Street Ithaca NY 14850 p 607.273.7600 f 607.273.0475 DOHN A. SIMS, P.E. PROVIDE SINGLE FIXTURE POLE. CIRCUIT AS SHOWN, VI PROVIDE SINGLE FIXTURE ON SPECIFIED LD NG— OUNTED ' H0 OCELL. GHT DISTRIBUTIO ..3 DIVISION ON SPECIFIED POLE. CIRCUIT AS SHOWN, VI ILD NG— 0 N ED 0 OCELL. COORDINATE INSTALLATION OF FIXTURE TYPE 'R' WITH BLUE STONE WALL FABRICATOR. REFER TO LANDSCAPING PLANS FOR DETAILS. CIRCUIT AS SHOWN, VIA BUILDING—MOUNTED PHOTOCELL. CCTV CAMERA TO BE MOUNTED HIGH ON LIGHT POLE. PROVIDE REQUIRED ACCESSORIES WITH POLE PURCHASE. ROUTE CABLE IN CONDUIT UNDERGROUND/ UNDERSLAB TO ROOM MECH B. COORDINATE WITH SYSTEM SUPPLIER AND REFER TO (3:E1.1) FOR MORE INFORMATION. CCTV CAMERA MOUNTED TO BUILDING. COORDINATE MOUNTING HEIGHT AND EXACT LOCATION WITH OWNER, ARCHITECT, AND/OR SYSTEM SUPPLIER. ROUTE CABLE IN CONDUIT UNDERGROUND/ UNDERSLAB TO ROOM MECH B. REFER TO (3:E1.1) FOR MORE INFORMATION. CCTV CAMERA MOUNTED TO BUILDING, COORDINATE MOUNTING HEIGHT AND EXACT LOCATION WITH OWNER, ARCHITECT, AND/OR SYSTEM SUPPLIER. ROUTE CABLE THROUGH BUILDING TO ROOM MECH B. REFER TO (3:E1®1) FOR MORE INFORMATION. —ELECTRIC BANK fTYP (2) 2" PVC CONDUITS AND PULL STRINGS FOR PHONE AND CABLE 10' EMENT TO CITY OF ITHACA 70'x30' TEMPO CON UCTION EMENT FROM HUNT TO INHS Consulting Ele Engineer, NYS PE Kis License #068705 5 Archer Lane ee, FL 34746 (407) 404-0790 arning, it is a violation of the NY State Education Law or any person to alter this document in any way, unless acting under the direction of a licensed professional engineer. If a document bearing the seal of an engineer is altered, the.. altering engineer shall affix to the document their seal and the notation "altered by" followed by their signature and the date of such alteration, and a specific description of the alteration, DEMCO NEW YORK CORP. ELECTRICAL CONTRACTORS 6701 MANLIUS CENTER RD EAST SYRACUSE, NEW YORK 13057 REVISION SCHEDULE APART ENT BUILDING (2) 2" PVC CONDUITS AND PULL STRINGS FOR PHONE AND CABLE SECONDARY ELECTRIC (1) 3" PVC CONDUIT AND CABLING MECH C (3) 2" PVC CONDUITS AND PULL STRINGS FOR FIBER, PHONE AND CABLE SECONDARY ELECTRIC 4" PVC CONDUIT AND CABLING GAS METER AND REGULATOR BY NYSEG POLE MOUNTED TRANSFORMER BY NYSEG '..:..,.NEIN „DVERH EAI ...,.... , _.a... BY NYSEG ELECTRICA 20' SITE PLAN DATA GRAPHIC SCALE 0 20 40 60 2 4 5 6 7 8 9 10 DATE ADDENDUM 2 9/15/14 STONE QUARRY APARTMENTS DATE: PROJECT: OTHER: DRAWN BY: STONE QUARRY APARTMENTS, L ULY 2014 2012059 F E D C SS, BR E2.0 A3 A 2 4 5 6 7 8 9 10 KEYED NOTES FOR EI.I COORDINATE REQUIREMENTS WITH INDIVIDUAL SERVICE PROVIDERS REFER TO SITE PLAN E2.0 FOR ADDITIONAL INFORMATION. COORDINATE INSTALLATION WITH SYSTEM PROVIDER. REFER TO SITE PLAN AND FLOOR PLANS FOR ADDITIONAL INFORMATION. "SIAMESE" POWER/SIGNAL CABLE PER CAMERA MANUFACTURER'S SPECIFICATIONS (TYPICAL) INDOOR FIXED CEILING MOUNTED CAMERAS (SEE FLOOR PLANS FOR LOCATIONS) Architecture Planning Interior Design 217 North Aurora Street Ithaca NY 14850 p 607.273.7600 f 607.273.0475 DOHN A. SI S, P.E. CCTV DVR DISPLAY AND CAMERA POWER SUPPLIES (MECH B) APT BLDG MOUNTED OUTDOOR FIXED CAMERA (SEE FLOOR PLANS FOR LOCATION) POLE OR BUILDING MOUNTED OUTDOOR CAMERA (SEE SITE PLAN FOR LOCATIONS) OF NE US7. SURGE SUPPRESSION DEVICE (TYPICAL) 5 -WAY SPLITTER IN RECESSED BOX WITH BLANK WALL PLATE IN EACH APARTMENT SEE DETAIL 2 THIS DRAWING Consulting Ele ... 5 Archer Lane Engineer, NYS PE Kissimmee, FL 34746 License #068705 (407) 404-0790 Warning, it is a violation of the NY State Education Law for any person to alter this document in any way, unless acting under the direction of a licensed professional engineer. If a document bearing theseal of an engineer is altered, the altering engineer shall affix to the document their seal and the notation "altered by" followed by their signature and the date of such alteration, and a specific description of the alteration. DEMCO NEW YORK CORP. ELECTRICAL CONTRACTORS 6701 MANLIUS CENTER RD EAST SYRACUSE, NEW YORK 13057 3 PORT WALL PLATE 1 -VIDEO (F -TYPE) 1 DATA (RJ45) 1 TELEPHONE (RJ11) IN EACH APARTMENT (TYPICAL) SEE DETAIL 2 THIS DRAWING OUTLETS LOCATED ELSEWHERE IN APARTMENT (TYPICAL) SEE DETAIL 2 THIS DRAWING CCTV RISER DIAGRAM NOT TO SCALE E THIRD FLOOR REVISION SCHEDULE DATE A ADDENDUM #2 9/15/14 SECOND FLOOR irTV POWER CORD BY TENANT CORDLESS OR ANSWERING MACHINE POWER CORD BY TENANT CABLING PROVIDED BY CONTRACT TELEPHONE CABLE BY CONTRACT INCOMING SERVICE WALL PLATE 5 -WAY SPLIITER IN RECESSED WALL BOX WITH BLANK PLATE BEDROOM #1 RENTAL: OFFIC 2 -PORT PLATE 1 DATA (RJ45) 1 TELEPHONE (RJ11 NSL RELAY CABINET STANDARD TELEPHONE* BY CONTRACT DOOR HARDWARE POWER SUPPLY 110 BLOCK PATCH PANEL 110 BLOCK PATCH PANEL SOUTH LOBBY DOOR RELEASE DOOR EXIT DEVICE DOUBLE GANG BOX WITH SINGLE GANG MUDRING DATA VIDEO QUAD RECEPTACLE BEDROOM #2 OR SPARE IN 1 BEDROOM UNITS PATCH CABLE BY SERVICE PROVID 20V �1 FIRE ALARM (2 LINES) © RENTAL OFFICE ELEVATOR (2 LINES) - CABLING BY SERVICE PROVIDER OR TENANT MODEM POWER CORD BY SERVICE PROVIDER TIME WARNER CABLE DEMARC AND RACK. FLTG FIBER RACK VERIZON DEMARC RACK TELEVISION BY TENANT FIRST FLOOR CABLE SPLITTER BY SERVICE PROVIDER (OPTIONAL) 4 PORT WIRELESS MODEM BY SERVICE PROVIDER DOUBLE GANG BOX WIT DOUBLE 1 GANG SINGLE GANG BOX WITH SINGLE GANG MUDRING (TYP) BEDROOM #3 OR SPARE IN 1 OR 2 BEDROOM UNITS STONE QUARRY APARTMENTS STONE QUARRY APARTMEN z>- < B 0 TIME WARNER CABLE DEMARC VERIZON TELEPHONE TO INCOMING SERVICE s VIDEO JACK S FROM TIME WARNER CABLE DEMARC DATE: PROJECT: OTHER: DRAWN BY: 8 JULY 2014 2012059 SS, BR TELEPHONE/ DAT NOT TO SCALE VIDEO DISTR BUTION LAYOUT * PROVIDE A/V TELEPHONE SIGNAL AT HEARING IMPARED UNIT #120 TELEPHONE/ DATA/ VIDEO RISER DIAGRAM - TYP CAL APARTME E1.1 NOT TO SCALE Tele/Data/Video and CCTV A Riser Diagrams E1.1 A3 1 2 4 5 6 7 8 10