HomeMy WebLinkAboutStone Quarry Apartments - Fire Protection1
2
4
5
6
7
8
9
10
C 80 DS
PES 2.00
20 DS
2-60 CR\
T
GENERAL NOTES:
A. KENNEDY MECHANICAL TO PROVIDE AUTOMATIC SPRINKLER SYSTEM, TO BE DESIGNED IN ACCORDANCE WITH NFPA 13R,
2007 EDITION FOR RESIDENTIAL OCCUPANCIES UP TO FOUR STORIES IN HEIGHT.
B. ALL WORK TO BE IN ACCORDANCE WITH NFPA 13R 2007 ED, NYS FIRE CODE, AND LOCAL ORDINANCES.
C. ALL NEW PIPING TO COMPLY WITH ALL APPLICABLE REGULATIONS AND SHALL BE SIZED HYDRAULICALLY,
D. FINAL HYDRAULICALLY CALCULATED PLANS AND ALL NECESSARY DOCUMENTS TO BE SUBMITTED TO THE ITHACA FIRE
MARSHALL UNDER SEPARATE COVER FOR REVIEW AND APPROVAL PRIOR TO CONSTRUCTION.
E. THE ENTIRE SPRINKLER SYSTEM SHALL BE TESTED AT 200PSIG FOR 2 HRS PER NFPA 13R, 2007 ED.
F. ALL HANGERS SHALL BE INSTALLED PER NEPA 13R 2007 ED.
G. BUILDING OWNER SHALL MAINTAIN A MINIMUM TEMPERATURE OF 40°F AT ALL AREAS OF THE WET SPRINKLER SYSTEM
PIPING TO PREVENT FREEZING.
H. IF TEMPORARY HEAT IS TO BE USED DURING CONSTRUCTION, GENERAL CONTRACTOR SHALL PAY CAREFUL NOTE TO
AVOID OVERHEATING AT SPRINKLER HEADS,
ALL FP PIPING WITH THE EXCEPTION OF THE MECHANICAL ROOM SHALL BE CPVC. MECHANICAL ROOM PIPING SHALL BE
A135 STEEL PIPING WITH APPROVED FITTINGS.
FIRE PROTECTION SYMBOLS LIST
SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
— FP —
IQUICK
FIRE PROTECTION PIPING
0
RESPONSE LISTED
SEMI -RECESSED SPRINKLER HEAD
AFF
ABOVE FINISHED FLOOR
RESIDENTIAL LISTED
SEMI -RECESSED SPRINKLER HEAD
PC
PLUMBING CONTRACTOR
QUICK RESPONSE LISTED
HORIZONTAL SIDEWALL SPRINKLER HEAD
FPC
FIRE PROTECTION CONTRACTOR
RESIDENTIAL LISTED
HORIZONTAL SIDEWALL SPRINKLER HEAD
0- C-
ELBOW UP, ELBOW DOWN
DRY BARREL TYPE LISTED SIDEWALL
SPRINKLER HEAD
=.(1
DROP CONNECTION
-3
CAP OR PLUG
ROLL DOWN
VISUAL FIDELITY NOTE: THIS DRAWING SET CONTAINS COLORED ELEMENTS TO CONVEY
DESIGN INTENT AND TO EASE INTERPRETATION. IF THIS DRAWINGS SET IS RECEIVED
IN MONOCHROME OR GRAYSCALE PLEASE CONTACT KENNEDY MECHANICAL INC. AT
.THE NUMBER LISTED TO THE RIGHT FOR A COLOR PRINTED SET.
FLOOR ABOVE -\
SEAL PENETRATION
TEE
LENGTH OF SPRINKLER
IN HEATED SPACE TO
BE PER MANUFACTURER
CEILING
DRYWALL
INTERIOR WALL SURFACE
JOIST FOR DECK/ CLG. ABOVE
CAULK WEATHERTIGHT
SEAL PENETRATION
CONDITIONED SPACE
DRY HEAD
ESCUTCHEON
EXTERIOR WALL SURFACE
INSULATED WALL
EXTERIOR / UNHEATED SPACE
FROM MAIN RISER
PIPE SIZE AS NOTED
TEST VALVE
IN READILY
ACCESSIBLE
LOCATION _
BUILDING STRUCTURE
SMOOTH BORE CORROSION
RESISTANT OUTLET GIVING
FLOW EQUIVALENT TO ONE SPRINKLER
SPLASH BLOCK
CHECK VALVE
4" GALVANIZED PIPE,
REFER TO PLANS
FOR CONTINUATION -\
INTERIOR PIPING AND
BODY MAY VARY FROM
SHOWN TO CONFORM
TO SYSTEM AND
ARCHITECTURAL
REQUIREMENTS
BALL DRIP (SHOWN
VERTICAL FOR CLARITY,
SHALL BE INSTALLED
HORIZONTALLY)
FINISHED FLOOR
•
•
• . •
• .
° . B,
. 0 ,
•
EXTERIOR WALL
WALL SIGN AS REQUIRED
BY LOCAL AUTHORITY
SEAL WALL PENETRATION
WATER TIGHT, TYP.
FIRE DEPARTMENT CONNECTION
(5" STORZ STYLE TERMINATION)
-PER ITHACA REQUIREMENTS
- 36" ABOVE
FINISHED GRADE
45° ELBOW WITH ESCUTCHEON.
MATCH FINISH OF
FIRE DEPARTMENT CONNECTION.
FINISHED GRADE
4" min.
6" max
TYCO HSW SEE SPRINKLER SCHEDULE
W/ SEMI-REC PLATE
1" CPVC
STANDOFF
HANGER
PIPE
1" CPVC
fi
TYCO HSW w/
SEMI•REC PLATE
x112" CPVC ELBOW
Ceiling
1" CNC STANDOFF
HANGER
1" CPVC
FLOOR JOIST
FIRE STOP 2ND FLOOR
PENETRATION
2nd Floo
TYCO HSW w/
SEMI-REC PLATE
p10' CAVE Spigot
d Adopter
CPVC
Pipe
- C BRANCH LINE
CEILING
TYCO HSW
W/ SEMI -RC PLATE
FIN FLOOR '-0"
TL,pical Up & Dn to Sprinklers
NTS
lx 31' CNC TEE
2x4 WALL WITH
RESILIENT CHANNEL
ON ONE SIDE
1" CPVC
Pipe
TYCOHSWw/
SEMI-REC PLATE
112x112x1"CFVC TEE
x\" CNC Spigot
ad Adopter
TYCO HSW u//
SEMI-REC PLATE
lx1\ CPVC TEE
2x4 WALL WITH
RESILIENT CHANNEL
ON ONE SIDE
T/CDHSWw/
SEMI-REC PLATE
2x1\ 2x1" CNC TEE
2x4 WALL
DRY HEAD SPRINKLER FOR UNCONDITIONED SPACE
NO SCALE
INSPECTOR'S TEST CONNECTION DETAIL
NO SCALE
FIRE DEPARTMENT CONNECTION DETAIL
NO SCALE
TYPICAL UP & DN TO SPRINKLERS
NO SCALE
4
PENDENT
VV/ GUARD
RECESSED
SIDEWALL
asszmairrAP: lir.40o2rAwAratamatamr.
•
PENDENT SEMI RECESSED
PENDENT
IF OFFSET LENGTH
EXCEED 2'-0"
PROVIDE PIPE HANGER
SPRINKLER
BRANCH LINE
8YAYW .Ar$V4IPMPAP:4202YAK.,:fr
REDUCER
CONCEALED
PENDENT
NOTE: REFER TO LEGEND AND FLOOR PLANS
FOR LOCATIONS AND TYPE, NOT ALL STYLES MAY BE USED
TYPICAL ARMOVER SECTION
N.T.S.
HARDENED HEX HEAD
SELF THREADING SCREW
CPVC SINGLE STRAP HANGER
•
TYPICAL ARMOVER SECTION
N T S
HARDENED HEX HEAD
SELF THREADING SCREW
CPVC DOUBLE STRAP HANGER
MAXIMUM DISTANCE BETWEEN HANGERS
NOMINAL PIPE
SIZE
3/4"
1-1/4"
1-1/2"
2-1/2"
3-1/2"
STEEL PIPE EXCEPT
THREADED LIGHTWALL
N/A
12-0 I 12-0
15-0
15-0
15-0
5-0
15-0
15-0
15-0
15-0
15-0
THREADED UGHTWALL
STEEL PIPE
N/A
2-0 12-0 I 12-0
12-0
12-0
12-0
N/A
N/A
N/A
N/A
N/A
CPVC PIPE
5-6
6-0
6-6
7-0
8-0
9-0
10-0
N/A
N/A
N/A
N/A
N/A
TNPE 1- FOR 1' AND 1-1/4' .IPE AND HANGER
1N,E 2- FOR 1-1/2" AND 2' PIPE AND HANGER
ilL
TO RESTRAIN THE UPWARD MOVEMENT OF PIPE
AS IT OCCURS DURING SPRINKLER HEAD ACTIVATION
AS REQUIRED.
SHALL BE LOCATED AT END HEADS WITHIN 24" FROM
DROP TO PENDENT HEAD
SURGE RESTRAINER
EDT STEEL OR CPVC PLASTIC PIPE
NTS
HARDENED HEX HEAD
SELF THREADING SCREW
CPVC STAND-OFF HANGER
SPRINKLER HEAD TYPES
NO SCALE
TYPICAL ARMOVER SECTIONS
TYPICAL HARDWARE DETAILS
HARDENED HEX HEAD
SELF THREADING SCREW
SIDE MOUNT CPVC DOU3LE
FASTENER STRAP TYPE HANGER
CPVC HANGER
Sammy GST -20
for Wood
//— 3/8" All Thread Rod
Adjustable Swivel Ring
TYPICAL HANGER
NO SCALE
Sammy
Sidewinder
SWG-20 for Wood
3/8" All Thread Rod
Adjustable Swivel Ring
TYPICAL HANGER
NO SCALE
7
ick SECOND FLOOR ,„ II V
411--) 209' - 4 3/4"
FLOW SWITCH
vd RETARD
1 1/4" MAIN DRAIN
PIPED TO EXTERIOR
21/2" CHECK
VALVE TRIM
FIRST FLOOR
200' - 0"
INSPECTOR'S TEST
CONNECTION WITH SIGHT
GLASS AND 1/2" ORIFICE,
CONNECT TO MAIN DRAIN
PIPING TO EXTERIOR
0-300 GAUGE/
3" BUTTERFLY
VALVE
w/ TAMPER
4" WATTS 757
DOUBLE CHECK
ASSY
\- 1/2" BALL DRIP
4" TO FIRE 4" GATE VALVE
DEPT CONN W/ TAMPER SWITCH
SPARE
SPRINKLER
HEAD
CABINET
NOTE: ALL VALVES IN FIRE SYSTEM
SHALL BE PROVIDED WITH TAMPER
SWITCHES
4" FIRE SERVICE
3" DOMESTIC SERVICE
SECTION AT FP BACKFLOW DEVICE AND RISER (NTS)
LFNCESSE Construction
75 Thruway' Parini Drive
West Renrietta, NY 14,5.536
:8••
• 4 ,
WI
ER
A
STAG
HC)LTAFICHITECTS
Architecture
Planning
Interior Design
217 North Aurora Street
Ithaca NY 14850
p 607.273.7600 f 607.273.0475
r,t;KAIIIft AA COlti'LA,C B/TAT
.alk&0164AATITs **et .1.,6*.stst ARA NtrttRA
/ / COMFORT STREET
ROCHESTER, NEW YORK 14620
565-232-2500
ThESE DOCUMENTS AND ALL IDEAS, ARRANGEMENT,
DESIGNS AND PLANS INDICATED THEREON OR.
PRESENTED THEREBY ARE OWNED AND REMAIN THE
PROPERTY OF KENNEDY MECHANICAL INC. AND NO PART
ThEREOF SHALL DE UTILIZED BY ANY PERSON, FIRM, OR,
CORPORATION FOR. ANY PURPOSE WHATSOEVER EXCEPT
WITH THE SPECIFIC WRITTEN PERMISSION OF KENNEDY
MECHANICAL INC. AU. RIGHTS RESERVED
Baumer Mechanical Design Services
625 Panorama Trail, Building 2, Suds 210
Rochester, NY 14625
585-313-5819
WARNING: It is a violation of
New York State Law for any
person, unless acting under the
direction of a licensed Architect,
to alter this document in any way.
If a document bearing the seal of
an Architect is altered, the
altering Architect shall affix to
such document his seal and the
notation "altered by" followed by
his signature, the date of such
alteration, and a specific
description of the alteration.
REVISION SCHEDULE
NAME
DATE
STONE QUARRY APARTMENTS
F -
z
z
0
F
E
C
>-
zB
0
DATE:
7/18/2014
PROJECT:
2012059
OTHER:
DRAWN BY:
AFL/JTB
FIRE
PROTECTION -
GENERAL NOTES, A
LEGEND,
SCHEDULES
FP001
6
8
10