HomeMy WebLinkAbout_ALL Volume 2 Conformed Set 32311/3/2014 3:06:12 PM C:\Users\edgar.avila\Documents\Upson Hall_ELEC_Josue.Avila E D C B A 6 6 5 FIRE ALARM MATRIX 0 w D Q 0 z 0 H 0 Q DEVICE ACTIVATED ANNUNCIATES ALARM SIGNAL AT FACP ANNUNCIATES SUPERVISORY SIGNAL AT FACP INITIATES OCCUPANT NOTIFICATION THROUGHOUT THE ZONE TRANSMITS ALARM TO FD VIA CENTRAL STATION CONNECTION ELEVATOR RETURNS TO ALTERNATE LEVEL ELEVATOR RETURNS TO DESIGNATED LEVEL AUTOMATIC POWER DISCONNECT ELEVATOR MACHINE RM DISCHARGE LOCAL CHEMICAL AGENT AND INITIATE ALARM CLOSES ASSOCIATED DAMPER SHUT DOWN AFFECTED HVAC UNIT TOP OF STAIR AND TOP OF ELEVATOR SHAFT RELIEF VENTS SPRINKLER SYSTEM ©© ---0 0 AUTOMATIC SPRINKLER WATERFLOW X * X SPRINKLER SYSTEM CONTROL VALVE X ELEVATOR MACHINE ROOM WATERFLOW X X 4 X ELEVATOR SHAFT WATERFLOW X X X ► DETECTION a 5---? a• PENTHOUSE ELEVATOR - DESIGNATED LEVEL (HEAT/SMOKE) X X X ELEVATOR - OTHER LEVEL (HEAT/SMOKE) X X X ELEVATOR MACHINE ROOM (SMOKE) X X X ELEVATOR MACHINE ROOM (HEAT) X € 5--- X X X DH DH TOP OF STAIR; TOP OF ELEVATOR SHAFT(SMOKE) DH DH X DH X MECHANICAL/ELECTRICAL ROOM X .II p X AREA SMOKE/HEAT DETECTOR X X FIRE ALARM CONTROL PANEL X X ritAti _ HVAC DUCT DETECTOR - UNIT MOUNTED X X HVAC DUCT DETECTOR - DAMPER MOUNTED ♦ • X X PULL STATIONS X X X STANDPIPE 4 4 WATERFLOW X X CONTROL VALVE X MANUAL CONTROLS LEVEL 5 OCCUPANT NOTIFICATION IN FIRE COMMAND X X X *: UPON ACTIVATION OF INITIATING DEVICE, AUTOMATIC 3 -MINUTE DELAY WILL BEGIN. IMMEDIATE NOTIFICATION WILL OCCUR IF ANY OF THE FOLLOWING OCCUR: 1. 2ND INITIATING DEVICE IS ACTIVATED, 2. MANUAL CONTROL IS ACTIVATED 3. AT CONCLUSION OF 3 -MINUTE DELAY, IF NOT RE -SET. NOTES 1. FOR QUANTITIES OF DEVICES REFER TO PLANS. 2. ALL NEW FIRE ALARM DEVICES SHALL BE FULLY COMPATIBLE WITH THE EXISTING SYSTEM AND SHALL BE INSTALLED UNDER DIRECT SUPERVISION OF EXISTING SYSTEM SUPPLIER WHO SHALL WARRANTY ALL WORK FOR (1) YEAR. 3. LOCATE NEW PULL STATIONS 4'-O" TO CENTER ABOVE FINISHED FLOOR. 4. LOCATE ALL HORN STROBES 6'-8" TO CENTER ABOVE FINISHED FLOOR OR 6" TO CENTER BELOW FINISHED CEILING, WHICHEVER IS LOWEST. 5. LOCATE ALL STROBES 6'-8" ABOVE FINISHED FLOOR OR 6" BELOW FINISHED CEILING. 6. PROVIDE (6) SPEAKER/STROBES AND ASSOCIATED WIRING PER FLOOR TO BE PLACED IN FIELD AS DIRECTED 7. PROVIDE A/B SPEAKER CIRCUIT AND SPLIT WIRE 2 CIRCUITS TO EVERY STROBE. 8. FOR ADDITIONAL REQUIREMENTS REFER TO SPECIFICATIONS. 9. PROVIDE MANUAL OVER -RIDE SMOKE EXHAUST CONTROLS AT THE FIRE COMMAND CENTER. MODIFY COMMAND CENTER AS REQUIRED. SYSTEM OPERATION SHALL BE SUCH AS TO PROVIDE MANUAL CONTROL, WITH STATUS, TO STOP AND START RETURN AIR FANS AND POSITION DAMPERS TO EXHAUST SMOKE FROM THE FLOORS. 10. PROVIDE MONITORING MODULES, CONTROL MODULES, END SWITCHES, LED STATUS LIGHTS, SELECTOR SWITCHES, PRINTED CIRCUIT CARDS, PROGRAMMING, AND ALL APPURTENANCES AS REQUIRED. 11. PROVIDE 5#14 AWG WIRING RUN IN CONDUIT TO EACH FAN AND EACH DAMPER. 5 4 4 3 2 BASEMENT FIRE ALARM RISER DIAGRAM CALE: NONE 3 2 FIRE ALARM J O BR O BT EVAC ESR ag H RTS RTS X IM FR FAAP FACP SMOKE DETECTOR HEAT DETECTOR DUCT DETECTOR BEAM DETECTOR RECEIVER BEAM DETECTOR TRANSMITTER EMERGENCY POWER OFF VOICE EVAC PANEL ELEVATOR STATUS PANEL CEILING MOUNTED HORN WALL MOUNTED HORN CEILING MOUNTED HORN/STROBE WALL MOUNTED HORN/STROBE WALL MOUNTED SILENTONE FIRE SERVICE PHONE FIREMAN'S PHONE JACK ROTATING BEACON MANUAL PULL STATION MAGNETIC DOOR HOLD OPEN DEVICE TAMPER SWITCH FLOW SWITCH CEILING MOUNTED REMOTE INDICATOR LIGHT WALL MOUNTED REMOTE INDICATOR LIGHT WALL MOUNTED ADA STROBE CEILING MOUNTED STROBE ADDRESSABLE INPUT MODULE FIRE ALARM ADDRESSABLE RELAY ALARM BELL FIRE SMOKE DAMPE SMOKE CONTROL DAMPER CARBON MONOXIDE DETECTOR FIRE ALARM ANNUNCIATOR PANEL FIRE ALARM CONTROL PANEL E D C B A 227 West 29th Street, 7th Flr. New York, NY 10001 t: 212 505-5955 f: 212 505-1648 PERKINS +WILL 215 Park Avenue South 4th Floor New York, NY 10003 t 212.251.7000 f 212.251.7111 www.perkinswill.com Upson Hall Renovation Cornell University 124 Hoy Rd, Ithaca, NY 14850 MEP FP ME Engineers 29 West 38th Street, 5th Floor New York, NY 10018 t 212.447.6770 f 212.447.6615 STRUCTURAL ENGINEER/ SUSTAINABILITY CONSULTANT Thornton Tomasetti 51 Madison Ave. New York, N.Y. 10010 t 917.661.7800 f 917.661.7801 LIGHTING CONSULTANT Lumen Architecture 214 W 29th Street Suite 1005 New York, NY 10001 t 212.564.6469 f 917.591.2524 LANDSCAPE ARCHITECT Trowbridge Wolf Michaels 1001 West Seneca Street Suite 101 Ithaca, NY 14850 t 607.277.1400 f 000.000.0000 CIVIL ENGINEER TG Miller PC 203 North Aurora Street Ithaca, NY 14850 t 607.272.6477 f 607.273.6322 AV / ACOUSTICS The Sextant Group 244 Madison Avenue Suite 311 New York NY 10016 t 877.684.2311 f 412.323.8538 CODE CONSULTANT Code Consultants Professional Engineers, PC 215 West 40th Street 15th Floor New York, NY 10018 t 212.216.9596 f 212.216.9619 Revisions 4 Addendum No. 3 15/03/31 3 FOR SMOKE FA BOOSTER FA TERMINAL PANEL (TYP) CABINET (TYP) 2 Ma 14/11/07 J 012 100% DD DOCUMENTS m NO J Cia HATCH (TYP) ©© ---0 0 4 4 4 --- ► a 5---? a• PENTHOUSE € 5--- DH DH DH --- DH DH DH .II p ritAti _ ♦ • — —1-1P221 © 4 --- 4 4 LEVEL 5 J II J DH DH DH --- DH DH DH 0 • 5--- p 0 4 4 4YYY -- — Y Y 5---? A S- 0 -? LEVEL 4 J II DH DH DH --- DH DH DH 0 • 5--- 0 _ * j* 1 --- ♦• ►:j*A*i:l --- — 0 S— a 0 —? 0 LEVEL 3 — 5--- 1411 J 5 J DH DH DH --- DH DH DH 0 .II --- 0 t•1 ttrl --- ♦ • 12.1 --- _1 � 12.1 Y. Y Y 5---? S- A -? 0 A LEVEL 2 — ISI S --- J 5--- J <:)1011 KNOX p BOX KB DH DH DH --- DH DH DH 0 *ttrl 220 --- t�1* --- — '— wP( ©© --- ©© 5---? r 5 a ---tea LEVEL 1 J II DH DH DH --- DH DH DH C) • 5--- p _ t.1* *ttrl --- ♦ • --- — 5---? Y Y r a S_ _1-0—a '—c-43--5---?- ♦♦♦.#444104" FOR SUPERVISED CONTROL CIRCUIT FOR ♦♦♦♦♦♦♦ EXISTING FR ....♦ FIRE ALARM ELEVATOR RECALL TO DESIGNATED FLOOR FOR SUPERVISED CONTROL CIRCUIT FOR ♦•♦♦♦ CONTROL �♦♦ FR ELEVATOR RECALL TO DESIGNATED FLOOR R •••���♦ i�♦ (FACP) UPSON FR FR FOR INTERFACE WITH SECURITY SYSTEM "GENERATOR 4 4♦♦♦♦�*♦ HALL FOR TROUBLE" "GENERATOR ❑ FOR ALARM" ♦♦♦♦♦♦♦♦♦ FR "GENERATOR FOR RUN" "GENERATOR FR FOR NOT IN AUTO" BASEMENT FIRE ALARM RISER DIAGRAM CALE: NONE 3 2 FIRE ALARM J O BR O BT EVAC ESR ag H RTS RTS X IM FR FAAP FACP SMOKE DETECTOR HEAT DETECTOR DUCT DETECTOR BEAM DETECTOR RECEIVER BEAM DETECTOR TRANSMITTER EMERGENCY POWER OFF VOICE EVAC PANEL ELEVATOR STATUS PANEL CEILING MOUNTED HORN WALL MOUNTED HORN CEILING MOUNTED HORN/STROBE WALL MOUNTED HORN/STROBE WALL MOUNTED SILENTONE FIRE SERVICE PHONE FIREMAN'S PHONE JACK ROTATING BEACON MANUAL PULL STATION MAGNETIC DOOR HOLD OPEN DEVICE TAMPER SWITCH FLOW SWITCH CEILING MOUNTED REMOTE INDICATOR LIGHT WALL MOUNTED REMOTE INDICATOR LIGHT WALL MOUNTED ADA STROBE CEILING MOUNTED STROBE ADDRESSABLE INPUT MODULE FIRE ALARM ADDRESSABLE RELAY ALARM BELL FIRE SMOKE DAMPE SMOKE CONTROL DAMPER CARBON MONOXIDE DETECTOR FIRE ALARM ANNUNCIATOR PANEL FIRE ALARM CONTROL PANEL E D C B A 227 West 29th Street, 7th Flr. New York, NY 10001 t: 212 505-5955 f: 212 505-1648 PERKINS +WILL 215 Park Avenue South 4th Floor New York, NY 10003 t 212.251.7000 f 212.251.7111 www.perkinswill.com Upson Hall Renovation Cornell University 124 Hoy Rd, Ithaca, NY 14850 MEP FP ME Engineers 29 West 38th Street, 5th Floor New York, NY 10018 t 212.447.6770 f 212.447.6615 STRUCTURAL ENGINEER/ SUSTAINABILITY CONSULTANT Thornton Tomasetti 51 Madison Ave. New York, N.Y. 10010 t 917.661.7800 f 917.661.7801 LIGHTING CONSULTANT Lumen Architecture 214 W 29th Street Suite 1005 New York, NY 10001 t 212.564.6469 f 917.591.2524 LANDSCAPE ARCHITECT Trowbridge Wolf Michaels 1001 West Seneca Street Suite 101 Ithaca, NY 14850 t 607.277.1400 f 000.000.0000 CIVIL ENGINEER TG Miller PC 203 North Aurora Street Ithaca, NY 14850 t 607.272.6477 f 607.273.6322 AV / ACOUSTICS The Sextant Group 244 Madison Avenue Suite 311 New York NY 10016 t 877.684.2311 f 412.323.8538 CODE CONSULTANT Code Consultants Professional Engineers, PC 215 West 40th Street 15th Floor New York, NY 10018 t 212.216.9596 f 212.216.9619 Revisions 4 Addendum No. 3 15/03/31 3 BID SET 15/02/27 2 50% CONSTRUCTION DOCUMENTS 14/11/07 1 100% DD DOCUMENTS 14/08/28 NO ISSUE DATE Sheet Information Date 11/07/2014 Job Number 031549.000 Drawn MEE Checked MEE Approved MEE Title FIRE ALARM LEGEND, RISER DIAGRAM AND MATRIX Sheet FA -0000 Copyright © 2013 Perkins+Will