HomeMy WebLinkAbout_ALL Volume 2 Conformed Set 216T J TV 1. ALL EXPOSED RACEWAYS ARE TO BE INSTALLED PARALLEL OR PERPENDICULAR TO WALLS OR STRUCTURAL MEMBERS SUCH THAT THEY FOLLOW STRUCTURAL SURFACE CONTOURS AND SHALL BE INSTALLED SUCH THAT THEY DO NOT OBSTRUCT PASSAGEWAYS OR ACCESS TO EQUIPMENT. MULTIPLE RACEWAYS SHOULD BE INSTALLED GROUPED TOGETHER. THE LOCATION OF PUBLICLY VISIBLE RACEWAYS SHALL BE APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION. (EXTRA TIME SHOULD BE ALLOW ED FOR THIS REVIEW AND APPROVAL.) 2. THE DISCONNECTING MEANS FOR ALL MECHANICAL EQUIPMENT SHALL BE ACCESSIBLE AND HAVE THE CLEARANCE IN FRONT AS REQUIRED BY NEC AMENDMENTS. 3. ALL CEILING ATTACHED OBJECTS AND FLOOR ATTACHED EQUIPMENT INCLUDING BUT NOT LIMITED TO PENDANT LIGHTING FIXTURES, GENERAL LIGHTING, MULTIPLE RACEWAYS, GENERATOR, TRANSFORMER ELECTRICAL SWITCHGEAR, AND SWITCHBOARDS SHALL BE INSTALLED IN ACCORDANCE WITH SUPPORTING OBJECTS FOR SEISMIC ZONE AS REQUIRED BY STATE AND LOCAL CODES. 4. ALL SWITCHGEAR, SWITCHBOARDS AND TRANSFORMERS SHALL HAVE A 4 INCH HOUSE KEEPING PAD. UNDER NO CONDITION SHALL THE HIGHEST SWITCH OR BREAKER EXCEED 6'-6" AFF. 5. DATA GIVEN ON THE DRAWINGS IS AS EXACT AS COULD BE SECURED. ABSOLUTE ACCURACY IS NOT GUARANTEED AND THE CONTRACTOR SHALL OBTAIN AND VERIFY EXACT LOCATIONS, MEASUREMENTS, LEVELS, SPACE REQUIREMENTS, POTENTIAL CONFLICTS WITH OTHER TRADES, ETC. AT THE SITE AND SHALL SATISFACTORILY ADAPT HIS WORK TO ACTUAL CONDITIONS AT THE BUILDINGS. THE DRAWINGS ARE DIAGRAMMATICAL IN NATURE AND SHALL NOT BE SCALED. HOWEVER THIS DOES NOT RELIEVE ANY SUB-CONTRACTOR FROM COORDINATING HIS WORK WITH ALL OTHER TRADES AND FROM ADJUSTING HIS WORK AS REQUIRED BY THE ACTUAL CONDITIONS OF THE PROJECT. THE CONTRACTOR SHALL VISIT THE SITE BEFORE SUBMITTING COSTS TO BECOME THOROUGHLY FAMILIAR WITH THE ACTUAL CONDITIONS OF THE PROJECT. 6. COORDINATE AND ADJUST ALL WORK BETWEEN TRADES AND EXISTING CONDITIONS IN ORDER TO ACCOMPLISH A NEAT, INTEGRATED AND EFFICIENT INSTALLATION WHICH INCLUDE BUT ARE NOT LIMITED TO: a.EXAMINE THE CONTRACT DOCUMENTS OF ALL TRADES (IE. THE ARCHITECTURAL REFLECTED CEILING PLAN, MECHANICAL HVAC DRAWINGS, ELECTRICAL LIGHTING PLAN, FIRE PROTECTION PLAN, ETC.). b. COORDINATE NECESSARY EQUIPMENT, FIXTURES, ETC. SO THAT THE FINAL INSTALLATION IS COMPATIBLE WITH THE MATERIALS AND EQUIPMENT OF THE OTHER TRADES. c. THIS CONTRACTOR SHALL ASSIST THE DIVISION 23 CONTRACTOR IN PREPARING SHOP DRAWINGS FOR COORDINATING INSTALLATION OF ALL WORK (IE. LOCATING ALL LIGHTING FIXTURES IN CEILING WITH CEILING CLEARANCES, RACEWAYS, PIPING, EQUIPMENT FOR CLEARANCE THROUGHOUT). d. THE ELECTRICAL DRAWINGS INDICATE THE ELECTRICAL REQUIREMENTS FOR A SIGNIFICANT PORTION OF THE MECHANICAL AND PLUMBING SYSTEMS. ADDITIONAL MECHANICAL AND PLUMBING EQUIPMENT IS INDICATED ON THE DIVISION 23 DRAWINGS. REFER TO MECHANICAL DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. PROVIDE COMPLETE WIRING AND FUSIBLE DISCONNECTING MEANS FOR ALL MECHANICAL AND PLUMBING EQUIPMENT. 7. DEFINITIONS: a. "FURNISH" MEANS TO "SUPPLY" AND USUALLY REFERS TO AN ITEM OF EQUIPMENT. b. "INSTALL" MEANS TO "SET IN PLACE, CONNECT AND PLACE IN FULL OPERATIONAL ORDER". c. "PROVIDE" MEANS TO "FURNISH AND INSTALL". d. "EQUIVALENT" MEANS "MEETS THE SPECIFICATIONS OF THE REFERENCE PRODUCT OR ITEM IN ALL SIGNIFICANT ASPECTS." SIGNIFICANT ASPECTS SHALL BE DETERMINED BY THE ENGINEER. e. "RE: DIVISION", AND SIMILAR EXPRESSIONS MEANS WORK TO BE PERFORMED UNDER THE CONTRACT DOCUMENTS, BUT NOT NECESSARILY UNDER THE DIVISION OR SECTION OF THE WORK ON WHICH THE NOTE APPEARS. IT IS THE CONTRACTORS SOLE RESPONSIBILITY TO COORDINATE THE WORK OF THE CONTRACT BETWEEN HIS/HER SUPPLIERS, SUBCONTRACTORS, AND EMPLOYEES. IF CLARIFICATION IS REQUIRED, CONSULT ARCHITECT. 8. "FIRESTOPPING" REQUIREMENT. ALL PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALL BE SEALED WITH MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF FLAMES AND HOT GASSES WHEN SUBJECTED TO THE REQUIREMENTS OF THE TEST STANDARD SPECIFIC FOR FIRE STOPS ASTM-E-814. ALL PENETRATIONS SHALL MEET F AND T RATINGS AS REQUIRED BY THE BUILDING CODE. 9. WHERE DISCONNECTS ARE INDICATED ON DRAWINGS CONTRACTOR SHALL PROVIDE FINAL CONNECTION TO EQUIPMENT BEING SERVED BY DISCONNECT. 10. CONTRACTOR PROVIDE ALL MISCELLANEOUS SUPPORTS AS REQUIRED FOR A COMPLETE OPERABLE ELECTRICAL INSTALLATION INCLUDING MISCELLANEOUS STEEL, UNI-STRUT, ALL-THREAD, AIRCRAFT CABLE, ETC. 11. CONTRACTOR SHALL TRACE EXISTING SERVICES TO GUMMAN AND PROTECT DURING DEMOLITION AND CONSTRUCTION. 12. REFER TO APPENDIX A FOR PANEL SCHEDULES. NOTES: NOTES: 1. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL GOVERN OVER THOSE SHOWN ABOVE. 2. CONTRACTOR SHALL ENSURE THAT ALL MOUNTING HEIGHTS COMPLY WITH CURRENT ADA REQUIREMENTS. 3. WHERE EVER DEVICES ARE INDICATED TO BE ABOVE DOORS, DEVICE SHALL BE CENTERED BETWEEN TOP OF DOOR TRIM AND CEILING LINE. 4. ALL ABOVE COUNTER (DESIGNATED BY "AC") SHALL BE MOUNTED 8" ABOVE COUNTER OR MAXIMUM HEIGHT OF 44" TO TOP OF DEVICE. VERIFY HEIGHTS WITH ARCHITECT. 5. FOR CEILINGS BELOW 7'-4", FIRE ALARM STROBE OR HORN/STROBES SHALL BE WALL MOUNTED 6" BELOW FINISHED CEILING. FACP FAAP CONTROL PANELS 80" AFF TO BOTTOM OFDEVICE78" (6'-6") U.N.O.72" (6'-0") U.N.O.64" (5'-4") U.N.O.48" (4'-0") U.N.O.TOP OF CABINET TOP OF CABINET TOP OF CABINET TOP OFDEVICEBOTTOM OFDEVICE16" AFF U.N.O.-GYP-BLOCK18"AFF U.N.O.-BLOCK (6")NOTE: ALL DEVICES INDICATED TO BE INSTALLED AT DIFFERENT MOUNTING HEIGHTS AND LOCATED WITHIN ONE STUD SPACE FROM EACH OTHER SHALL ALIGN VERTICALLY, ON THE SAME SIDE OF THE STUD. WHERE WALL MOUNTED TELEPHONES OCCUR OVER LIGHT SWITCHES, VOLUME CONTROLS, ETC. OFFSET ONE STUD SPACE. FINISHED FLOORTYPICAL DEVICE MOUNTING HEIGHTS NO SCALE A,AMP AC AF AFF AFG AL AM ANN ANT ATS AUTO AUX AWG BCST BFC BFG BKR C CAB CAM CB CCTV CKT CO COMB COMP COND CT CU dB DEMARC DISC DL DWG DVR EA EC EF EG EHC ELEC ELEV EMERG EMT ENG EOL EQUIP ER EWC EWH EXH EX F F/A FACP FBO FC FDR FLEX FLR FLUOR GALV GEN GFCI GND HC HD HH HOA HP HPF HPS HTR IC ID IDF IMC INCAND J-BOX KCMIL KVA KW KWH LA LAN LFC LTG LV MA MAX MB AMPERE ABOVE COUNTER AMPERE FUSE/FRAME ABOVE FINISHED FLOOR ABOVE FINISHED GRADE ALUMINUM AMMETER ANNUNCIATOR ANTENNA AUTOMATIC TRANSFER SWITCH AUTOMATIC AUXILIARY AMERICAN WIRE GAUGE BROADCAST BELOW FINISHED CEILING BELOW FINISHED GRADE BREAKER CONDUIT CABINET CAMERA CIRCUIT BREAKER CLOSED CIRCUIT TELEVISION CIRCUIT CONDUIT ONLY COMBINATION COMPUTER CONDUCTOR CURRENT TRANSFORMER COPPER DECIBEL DEMARCATION DISCONNECT DAMP LABEL DRAWING DIGITAL VIDEO RECORDER EACH ELECTRICAL CONTRACTOR EXHAUST FAN EQUIPMENT GROUND ELECTRIC HEATING COIL ELECTRIC OR ELECTRICAL ELEVATOR EMERGENCY ELECTRIC METALLIC TUBING ELECTRONIC NEWS GATHERING F/A END OF LINE RESISTOR EQUIPMENT EXISTING TO BE REMOVED/RELOCATED ELECTRIC WATER COOLER ELECTRIC WATER HEATER EXHAUST EXISTING FUSE FIRE ALARM FIRE ALARM CONTROL PANEL FURNISHED BY OTHERS FOOTCANDLES FEEDER FLEXIBLE FLOOR FLUORESCENT GALVANIZED GENERATOR GROUND FAULT CIRCUIT INTERRUPTER GROUND HORIZONTAL CROSS CONNECT HEAVY DUTY HAND HOLE HAND-OFF-AUTO HORSE POWER HIGH POWER FACTOR HIGH PRESSURE SODIUM HEATER INTERMEDIATE CROSS CONNECT INSIDE DIAMETER INTERMEDIATE DISTRIBUTION FRAME INTERMEDIATE GRADE METALLIC CONDUIT INCANDESCENT JUNCTION BOX THOUSAND OF CIRCULAR MILLS KILOVOLT AMPERE KILOWATT KILOWATT HOUR LIGHTNING ARRESTOR LOCAL AREA NETWORK LIQUID TIGHT FLEXIBLE CONDUIT LIGHTING LOW VOLTAGE MILLIAMPERE MAXIMUM MAIN BREAKERS MCC MCP MDF MDP MECH MFR MG MH MIN MLO MOV MPOE MTG MS MSB MTB MTD MTG MTGB MV N NEC NF NIC NC NO NTS OC OD P PA PB PBX PE PF PH PNL PR PRI PT PVC PWR QR R REC RGS RM RPM SCP SEC SECT SHT SMPOE SP SPDT ST STD SW SWBD T TBB TC TTB TTC TEL TELCO TELCOM TEMP TGB TR UC U/G UH UL UNO UPS UTP V VFD VM W W/ WH WHM WLAN WP WPL WT XFMR XP ABBREVIATIONS MOTOR CONTROL CENTER MOTOR CIRCUIT PROTECTOR MAIN DISTRIBUTION FRAME MAIN DIXTRIBUTION PANEL MECHANICAL MANUFACTURER MOTOR GENERATOR MAN HOLE OR METAL HALIDE MINIMUM MAIN LUGS ONLY MOTOR OPERATED VALVE MAIN POINT OF ENTRY MOUNTING HEIGHT MOTOR STARTER MAIN SWITCHBOARD MAIN TERMINAL BOARD MOUNTED MOUNTING MAIN TELECOMMUNICATION GROUND BUS MEDIUM VOLTAGE NEUTRAL NATIONAL ELECTRICAL CODE NON FUSED NOT IN CONTRACT NORMALLY CLOSED NORMALLY OPEN NOT TO SCALE ON CENTER OUTSIDE DIAMETER POLE PUBLIC ADDRESS PUSH BUTTON PRIVATE BRANCH EXCHANGE PHOTOELECTRIC POWER FACTOR PHASE PANEL PAIR PRIMARY POTENTIAL TRANSFORMER POLYVINYL CHLORIDE POWER QUARTZ RESTRIKE REMOVE RECEPTACLE RIGID GALVANIZED STEEL ROOM REVOLUTIONS PER MINUTE SECURITY CONTROL PANEL SECONDARY/SECOND SECTION SHEET SECONDARY MAIN POINT OF ENTRY SERVICE PROVIDER SINGLE POLE, DOUBLE THROW SHUNT TRIP STANDARD SWITCH SWITCHBOARD TWIST LOCK TELECOMMUNICATIONS BONDING BACKBONE TIME CLOCK TELEPHONE TERMINAL BOARD TELEPHONE TERMINAL CABINET OR CLOSET TELEPHONE TELEPHONE COMPANY TELECOMMUNICATIONS TEMPERATURE TELECOMMUNICATIONS GROUND BUS TEMPER RESISTANT UNDER COUNTER UNDER GROUND UNIT HEATER UNDERWRITER LABORATORIES UNLESS NOTED OTHERWISE UNINTERRUPTIBLE POWER SUPPLY UNSHIELDED TWISTED PAIR VOLT VARIABLE FREQUENCY DRIVE VOLTMETER WATT WITH WATT HOUR WATT HOUR METER WIRELESS-LOCAL AREA NETWORK WEATHERPROOF WEATHERPROOF LOCKABLE ENCLOSURE WATERTIGHT TRANSFORMER EXPLOSION PROOF LIGHTING STRIP LIGHT WALL MOUNTED LINEAR FLOREXCENT RECESSED 2'X4' RECESSED 1'X4' RECESSED 2'X2' SURFACE MOUNTED 2'X4' SURFACE MOUNTED 2'X2' SURFACE MOUNTED 1'X4' RECESSED STEP LIGHT WALL MOUNTED FLOODLIGHT WALL MOUNTED SCONCE SURFACE MOUNTED WALL WASH SURFACE MOUNTED DOWN LIGHT RECESSED DOWN LIGHT RECESSED WALL WASH RECESSED 1X4 WALL WASH PENDANT LIGHT MONOPOINT TRACHEA LINEAR QUARTZ LIGHT STRIP TRACK WITH TRACKHEADS POLE MOUNTED LUMINAIRE WITH ARM POLE MOUNTED LUMINAIRE POST TOP MOUNTING CEILING MOUNTED EXIT SIGN, COOPER LIGHTING EH-6-ET EXIT SIGN WITH DIRECTIONAL, COOPER LIGHTING EH-6-ET WALL MOUNTED EXIT SIGN ARROWS, COOPER LIGHTING EH-6-ET EMERGENCY LIGHTING UNIT DIMMER SWITCH OCCUPANCY SENSOR - CEILING MOUNTED JAMB SWITCH SHADED SYMBOLS DENOTE EMERGENCY FIXTURES PROVIDE QUARTZ RESTRIKE FOR ALL METAL HALIDE EMERGENCY FIXTURES. 3 4 JS SINGLE POLE SWITCH 3-WAY SWITCH 4-WAY SWITCH ABBREVIATIONS EQUIPMENT MOTOR MOTOR AND DISCONNECT MOTOR AND FUSED DISCONNECT MOTOR STARTER MAG-MSTR UN-FUSED DISCONNECT CIRCUIT BREAKER SURFACE MOUNTED BRANCH CIRCUIT OR POWER PANEL METER PROVIDED BY BMS CONTRACTOR CURRENT TRANSFORMER GROUND POWER TRANSFORMER DELTA/WYE WITH GROUND FUSE & SWITCH CIRCUIT BREAKER DRAWOUT CIRCUIT BREAKER KIRK-KEY INTERLOCK GROUND FAULT INTERRUPTER BREAKER CIRCUIT MONITORING DEVICE MECHANICAL EQUIPMENT IDENTIFICATION TAG TRANSIENT VOLTAGE SURGE SUPPRESSION THERMAL OVERLOAD MOTOR AND THERMAL OVERLOAD AUTOMATIC TRANSFER SWITCH FUSED DISCONNECT LIGHTING CONTROL PANEL M K G D TVSS TO TO POWER DEVICES WALL RECEPTACLE X TV J WALL DUPLEX RECEPTACLE WALL FOURPLEX RECEPTACLE FLOOR DUPLEX RECEPTACLE FLOOR FOURPLEX RECEPTACLE CEILING / FLOOR SPECIAL RECEPTACLE (FOR "X" SEE TABLE BELOW) CEILING DUPLEX RECEPTACLE CEILING FOURPLEX RECEPTACLE CEILING RECEPTACLE WALL CLOCK RECEPTACLE WALL DUPLEX RECEPTACLE (EMERGENCY) WALL COMBINATION TV / POWER OUTLET WALL JUNCTION BOX FLOOR FURNITURE FEED CEILING JUNCTION BOX POWER POLE SINGLE TOGGLE SWITCH PLUGMOLD SINGLE PUSH BUTTON DUPLEX PUSH BUTTON WALL BUZZER RACEWAY LEGEND BRANCH CIRCUIT HOMERUN TO PANELBOARD, NUMBER OF ARROWS INDICATES NUMBER OF CIRCUITS, NUMERICAL INDICATES CIRCUIT NUMBER.A:2,4 BRANCH CIRCUIT HOMERUN CONTROLLED BY LIGHTING CONTROL SYSTEM. FIRST HEXAGON LETTER CORRESPONDS TO FIRST CIRCUIT NUMBER. (ie. CIRCUIT #2 IS ON ZONE A) A:2,4 A UNDERGROUND FEEDER UNDERGROUND BRANCH CIRCUIT HOMERUN CONDUIT UP CONDUIT DOWN CONDUIT RUNS UNDERFLOOR OR BELOW GRADE CONDUIT RUN CONCEALED IN WALLS OR CEILING, OR EXPOSED WHEN CEILING ARE NOT PRESENT. MOTOR CONNECTION A NON-LOCKING, 20A, 125V, 1PH 5-20R 2#12,#12G,3/4"C (50FT)DEDICATED, SINGLE OUTLET TAG OUTLET RATING NEMA/CAT NO FEEDER (NOTE 1)WIRING NOTES RECEPTACLE MODIFIER TAGS B NON-LOCKING, 30A, 125V, 1PH 5-30R 2#10,#10G,3/4"C (60FT)HOT-NEUT-GND C NON-LOCKING, 20A, 250V, 1PH 6-20R 2#12,#12G,3/4"C (100FT)HOT-HOT-GND D NON-LOCKING, 30A, 250V, 1PH 6-30R 2#10,#10G,3/4"C (120FT)HOT-HOT-GND E NON-LOCKING, 50A, 250V, 1PH 6-50R 2#6,#10G,3/4"C (150FT)HOT-HOT-GND F TBD --- G NON-LOCKING, 20A, 125/250V, 1PH 14-20R 3#12,#12G,3/4"C (100FT)HOT-HOT-NEUT-GND H TBD --- I NOT USED --- J LOCKING, 20A, 125V, 1PH L5-20R 2#12,#12G,3/4"C (50FT)HOT-NEUT-GND K LOCKING, 30A, 125V, 1PH L5-30R 2#10,#10G,3/4"C (60FT)HOT-NEUT-GND L LOCKING, 20A, 250V, 1PH L6-20R 2#12,#12G,3/4"C (100FT)HOT-HOT-GND M LOCKING, 30A, 250V, 1PH L6-30R 2#10,#10G,3/4"C (120FT) N LOCKING, 20A, 250V, 3PH L11-20 3#12,#12G,3/4"C (100FT)HOT-HOT-HOT-GND O NOT USED --- P LOCKING, 20A, 125/250V, 1PH L14-20R 3#12,#12G,3/4"C (100FT)HOT-HOT-NEUT-GND Q LOCKING, 30A, 125/250V, 1PH L14-30R 3#10,#10G,3/4"C (120FT) R LOCKING, 30A, 250V, 3PH L11-30R 3#10,#10G,3/4"C (120FT)HOT-HOT-HOT-GND S LOCKING, 20A, 208Y/120V, 3PH L21-20R 4#12,#12G,3/4"C (120FT)HOT-HOT-HOT-NEUT-GND T LOCKING, 30A, 208Y/120V, 3PH L21-30R 4#10,#10G,3/4"C (130FT) U LOCKING, 50A, 250V, 3PH HBL CS8365C 3#6,#10G,1"C (175FT)HOT-HOT-HOT-GND V NOT USED --- W PIN & SLEEVE, 60A, 208Y/120V, 3PH HBL 560R9W 4#4,#10G,1-1/4"C (200FT)HOT-HOT-HOT-NEUT-GND X PIN & SLEEVE, 100A, 208Y/120V, 3PH HBL 5100R9W 4#1,#8G,1-1/2"C (250FT) Y TBD --- Z TBD --- HOT-HOT-GND HOT-HOT-NEUT-GND HOT-HOT-HOT-NEUT-GND HOT-HOT-HOT-NEUT-GND NOTE 1: DISTANCE NOTED IS MAXIMUM RUN LENGTH FOR WIRE SIZE. INCREASE PER NEC, INCLUDING GROUND, FOR LONGER RUNS OR FOR DERATING FACTORS (AMB TEMP, EXTERIOR, ETC.) SPD SURGE PROTECTIVE DEVICE CEILING TV OUTLET FLOOR JUNCTION BOX FLOOR FOURPLEX RECEPTACLE WITH AVAV WALL FOURPLEX RECEPTACLE (EMERGENCY) WALL SPECIAL RECEPTACLE (FOR "X" SEE TABLE BELOW)X J WALL FURNITURE FEEDJ J MC MECHANICAL CONTRACTOR 1.ALL CONTRACTORS SHALL REVIEW ARCHITECTURAL DRAWINGS FOR PHASING PLAN AND PHASING ZONES IN THE PRIMARY W ORK AREA. 2.WORK THAT WILL INTERRUPT SPACES NOT IN PHASE SHALL BE COORDINATED BEFOREHAND WITH THE FACULTY. SAID WORK SHALL BE DONE SWIFTLY AND ON PREMIUM TIME IF REQUIRED TO PROVIDE THE LEAST AMOUNT OF DISRUPTION TO THE FACILITY POSSIBLE. 3.WORK REQUIRING SHUTDOWN OF EXISTING SYSTEMS SHALL BE ARRANGED FOR CONTINUOUS PERFORMANCE, WITH MULTIPLE CREWS, TO LIMIT THE DURATION OF THE SHUTDOWN TO THE MINIMUM POSSIBLE PERIOD. ALL PREP-WORK SHALL BE COMPLETED PRIOR TO SYSTEM SHUT- DOWN, ALL MATERIALS SHALL BE ON SITE PRIOR TO THE START OF WORK REQUIRING A SHUT-DOWN OR CLOSING OF A SPACE OUTSIDE THE PRIMARY WORK AREA. 4.BIDS SHALL INCORPORATE PHASED WORK. REFER TO PHASING NOTES ARCHITECTURAL PLANS FOR SEPARATION BETWEEN PHASES. PROVIDE CONTINUITY OF SERVICES OF CONTRACTED TRADE IN AREAS NOT BEING DEMOLISHED. PROVIDE DUCTWORK, PIPING, SPRINKLER HEADS AS REQUIRED TO MAINTAIN CONTINUITY OF THESE SYSTEMS. PROVIDE OVERTIME AND SHUTDOWNS AS REQUIRED TO INCORPORATE PHASING. 5.ALL WORK OUTSIDE OF THE PRIMARY WORK AREA ASSOCIATED WITH DEMOLITION AND RESTORATION OF WALLS, CEILINGS, AND FINISHES, CLEAN-UP, DEBRIS REMOVAL, SAFETY ISOLATION OF WORK AREA, ETC. SHALL BE THE RESPONSIBILITY OF EACH TRADE CONTRACTOR. PHASING NOTES: H E L P - 2 - 1 ELECTRICAL EQUIPMENT NAMING CONVENTION X TRANSFORMER H 480Y/277V _ NORMAL L LIGHTING P PANEL B BASEMENT 1, 2,... SEQUENCE ATS AUTO TRANS SW L 208Y/120V E EMERGENCY P POWER 1, 2, ... 5 FLOOR Q 240 S STANDBY T TECHNOLOGY P PENTHOUSE CS CABLE SUPPORT SAVE ALL REMOVAL CONDUIT AND REUSE TO THE GREATEST ENTENT POSSIBLE. SUSTAINABLE DEMOLITION: SPECIALTY LOCAL CONTROLLERLC RECESSED MOUNTED BRANCH CIRCUIT OR POWER PANEL DAYLIGHT SENSOR - CEILING MOUNTED A1 NON-LOCKING, 20A, 125V, 1PH 5-20R 2#12,#12G,3/4"C (50FT)DEDICATED, DUPLEX OUTLET A2 NON-LOCKING, 20A, 125V, 1PH 5-20R 2#12,#12G,3/4"C (50FT)DEDICATED, QUAD OUTLET SECURITY SECURITY CAMERA R CARD READER DC DOOR CONTROL Sheet Title Approved Checked Drawn Job Number Date Sheet Information Revisions MEP FP ME Engineers 29 West 38th Street, 5th Floor New York, NY 10018 t 212.447.6770 f 212.447.6615 STRUCTURAL ENGINEER/ SUSTAINABILITY CONSULTANT Thornton Tomasetti 51 Madison Ave. New York, N.Y. 10010 t 917.661.7800 f 917.661.7801 LIGHTING CONSULTANT Lumen Architecture 214 W 29th Street Suite 1005 New York, NY 10001 t 212.564.6469 f 917.591.2524 LANDSCAPE ARCHITECT Trowbridge Wolf Michaels 1001 West Seneca Street Suite 101 Ithaca, NY 14850 t 607.277.1400 f 000.000.0000 162345 A E B C D 162345 A E B C D Copyright © 2013 Perkins+Will 227 West 29th Street, 7th Flr. New York, NY 10001 t: 212 505-5955 f: 212 505-1648 CIVIL ENGINEER TG Miller PC 203 North Aurora Street Ithaca, NY 14850 t 607.272.6477 f 607.273.6322 AV / ACOUSTICS The Sextant Group 244 Madison Avenue Suite 311 New York NY 10016 t 877.684.2311 f 412.323.8538 CODE CONSULTANT Code Consultants Professional Engineers, PC 215 West 40th Street 15th Floor New York, NY 10018 t 212.216.9596 f 212.216.9619 C:\Users\wtsui\Documents\REVIT 2015\Upson Hall_ELEC_wtsui.rvtE-0000 ELECTRICAL LEGEND AND NOTES MEE MEE 031549.000 11/07/2014 MEE Upson Hall Renovation 124 Hoy Rd, Ithaca, NY 14850 Cornell University 215 Park Avenue South 4th Floor New York, NY 10003 t 212.251.7000 f 212.251.7111 www.perkinswill.com NO ISSUE DATE 1 100% DD DOCUMENTS 14/08/28 2 50% CONSTRUCTION DOCUMENTS 14/11/07 3 BID SET 15/02/27 4 Addendum No. 3 15/03/31