HomeMy WebLinkAboutAD White House Electrical Upgrades IFBCB
CB
CB
UP
UP
UP
DN
UP
DN
DN
DN
DN
UP
DN
UP
UP
UP
DN
DN
DN
DN
DN
AD WHITE
HOUSE
2006EAS
T AVENUEURIS HALL
2087
IVES HALL
1009
STIMSON HALL
2011
DAY HALL
2026
TOWER ROAD
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
Cornell University
Ithaca, New York
Humphreys Service Building; Ithaca, N.Y.
Architectural & Structural, Civil &
Environmental, Mechanical and Electrical
Engineering
Facilities Engineering
PROJECT SCOPE AD White HouseT-001
TITLE SHEETAD White House Electrical UpgradesFE DESIGN
cmw
2006
March 10, 2017
9038228
AD White House Electrical
Upgrades
The purpose of this project is to replace the existing electrical distribution at
the A.D. White House. The work includes the replacement of all panelboards,
feeders, and branch circuits. The work also includes the replacement of all
wiring devices, including receptacles and light switches; and the replacement
of the emergency egress lighting. This building is listed on the National
Register of Historic Places. Refer to the BASE BID AND ALTERNATES
Notes on Drawing E-000 for Base Bid and Alternate work. Refer to the
CONSTRUCTION PHASING Notes on Drawing E-000 for important project
information.
DRAWING LIST
T-001 TITLE SHEET
E-000 SCOPE OF WORK, GENERAL NOTES, SYMBOLOGY, AND ABBREVIATIONS
E-010 KEYPLANS
E-100 POWER PLANS - BASEMENT AND FIRST FLOORS
E-101 POWER PLANS - SECOND AND THIRD FLOORS
E-200 LIGHTING PLANS - BASEMENT AND FIRST FLOOR
E-201 LIGHTING PLANS - SECOND AND THIRD FLOORS
E-300 EGRESS LIGHTING PLANS - BASEMENT AND FIRST FLOORS
E-301 EGRESS LIGHTING PLANS - SECOND AND THIRD FLOORS
E-400 GROUNDING AND BONDING PLAN
E-500 ONE-LINE DIAGRAMS
E-501 PANELBOARD SCHEDULES
E-502 PANELBOARD SCHEDULES
E-503 EQUIPMENT CONNECTION AND LUMINAIRE SCHEDULES
E-504 DETAILS
ED-100 DEMOLITION PLANS - BASEMENT AND FIRST FLOORS
ED-101 DEMOLITION PLANS - SECOND AND THIRD FLOORS
ED-102 DEMOLITION ELEVATION AND EXISTING PANELBOARD SCHEDULE
ED-103 DEMOLITION PHOTOS
ED-104 DEMOLITION PHOTOS
SITE PLAN - AD WHITE HOUSE
AREA OF
WORK
LOCATION PLAN - AD WHITE HOUSE (ALL FLOORS)
BASEMENT
AREA OF
WORK
FIRST FLOOR
THIRD FLOOR
SECOND FLOOR
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseE-000
SCOPE OF WORK,
GENERAL NOTES,
SYMBOLOGY, AND
ABBREVIATIONSAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
SCOPE OF WORKGENERAL NOTES
1.0 THIS BUILDING IS LISTED ON THE NATIONAL REGISTER OF HISTORIC PLACES.
2.0 REPLACE THE ENTIRE ELECTRICAL DISTRIBUTION, INCLUDING PANELBOARDS,
FEEDERS, AND BRANCH CIRCUITS.
3.0 REPLACE ALL WIRING DEVICES.
4.0 TRENCH AND RESTORE PLASTER WALLS AND CEILINGS TO CONCEAL ALL
FEEDERS AND BRANCH CIRCUIT WIRING. INCLUDES PAINTING OF ENTIRE WALLS
AND CEILINGS AFFECTED BY ELECTRICAL WORK.
5.0 REMOVE AND SAVE MOLDINGS AND TRIMS TO CONCEAL BRANCH CIRCUIT
WIRING AND REINSTALL. INCLUDES PAINTING OF ALL MOLDINGS, TRIMS, AND
BASEBOARDS AFFECTED BY ELECTRICAL WORK.
6.0 REPLACE THE HALLWAY SCONCES.
7.0 2.4-kV SWITCH AND BUILDING TRANSFORMER ARE EXISTING TO REMAIN.
8.0 PROVIDE ARC FLASH LABELS ON ALL PANELBOARDS..
9.0 PROVIDE WIRELESS LIGHTING CONTROLS.
10.0 REFER TO CONSTRUCTION DOCUMENTS FOR FULL SCOPE.
11.0 CONTRACTOR IS RESPONSIBLE TO DETERMINE ALL FEEDER, BRANCH CIRCUIT,
AND SURFACE RACEWAY ROUTING IN-FIELD. THIS WORK WILL REQUIRE
EXTENSIVE FIELD INVESTIGATION TO LOCATE SUITABLE PATHWAYS WITHIN
PLASTER WALLS AND CEILINGS, AND BETWEEN FLOORS.
1.0 ELECTRICAL SCHEMATICS INDICATED ON CONTRACT DOCUMENTS ARE
DIAGRAMMATIC. IT IS NOT THE INTENT TO SHOW EXACT OR MOST
EFFICIENT ROUTING. VERIFY ALL DIMENSIONS AND FIELD CONDITIONS
ON SITE. ANY CONFLICTS BETWEEN CONSTRUCTION DOCUMENTS AND
FIELD CONDITIONS SHALL BE BROUGHT TO CORNELL'S PROJECT MANAGER
FOR RESOLUTION BEFORE WORK PROCEEDS.
2.0 ASSURE PUBLIC AND WORKER SAFETY AT ALL TIMES. PROTECT ADJOINING
AREAS FROM DAMAGE AND DUST. REMOVE ALL DEBRIS FROM SITE AND
DISPOSE OF WASTE MATERIAL IN A SAFE MANNER. KEEP THE PREMISES
FREE OF DEBRIS FROM THE EXECUTION OF WORK. DELIVER A FINAL
PRODUCT THAT IS CLEAN AND OPERABLE.
3.0 FIRE STOP ELECTRICAL PENETRATIONS THROUGH FIRE RATED WALLS
AND/OR FLOORS WITH MATERIAL EQUAL IN RATING TO THE CONSTRUCTION
OF THE MATERIAL PENETRATED.
4.0 WORK SHALL BE COMPLETED AS SPECIFIED AND INDICATED ON CONTRACT
DOCUMENTS. ANY SUGGESTED ALTERNATE MANUFACTURER OR METHOD
OF INSTALLATION SHALL BE SUBMITTED TO PROJECT ENGINEER FOR
APPROVAL PRIOR TO ORDERING ANY MATERIALS OR COMMENCING
EXECUTION OF WORK.
5.0 GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLE 250.
PROVIDE EQUIPMENT GROUND CONDUCTOR WITH EACH BRANCH CIRCUIT
INDICATED ON CONTRACT DOCUMENTS. EQUIPMENT GROUND CONDUCTOR
SHALL BE ROUTED WITH ASSOCIATED PHASE CONDUCTORS.
6.0 PROVIDE A NEW TYPED PANELBOARD DIRECTORY FOR EACH PANELBOARD.
LABEL ALL NEW DEVICE FACEPLATES WITH SOURCE AND CIRCUIT NUMBER.
PROVIDE PERMANENT LABEL ON SWITCHING DEVICES INDICATING
EQUIPMENT SERVICE AND INVENTORY NUMBERS. COORDINATE EQUIPMENT
INVENTORY NUMBERS WITH CORNELL UNIVERSITY'S MECHANICAL SHOP,
255-8667.
7.0 CIRCUITS RATED 20-AMP, 120 VOLT SHALL CONTAIN SEPARATE NEUTRAL
CONDUCTORS.
8.0 CONDUCTORS SHALL BE A MINIMUM OF 12AWG, STRANDED COPPER, 600VAC, 90
DEGREE C, TYPE THHN/THWN FOR DRY AREAS AND XHHW/THWN-2 FOR WET
AREAS.
9.0 CONDUITS SHALL BE A MINIMUM OF 3/4 INCHES DIAMETER. CONDUITS SHALL BE
ELECTRICAL METALLIC TUBING (EMT) AND SURFACE MOUNTED UNLESS
NOTED OTHERWISE.
10.0 AIC RATING OF NEW CIRCUIT BREAKERS SHALL MATCH RATING OF
RESPECTIVE PANELBOARD. SIZE AS INDICATED.
11.0 PROVIDE PULL STRING THROUGH NEW CONDUIT AND BOXES. PROVIDE
SUPPORT HANGERS FOR CONDUIT AS NEEDED.
12.0 INSTALL RACEWAY SYSTEMS ENSURING PROPER ACCESS TO EQUIPMENT
AND DEVICES AND WITH SUFFICIENT SPACE TO PERFORM ROUTINE
MAINTENANCE AND REPAIR. RACEWAYS THAT ARE NOT INSTALLED WITH
THIS REQUIREMENT IN MIND SHALL BE RELOCATED AT NO EXPENSE TO
THE UNIVERSITY UNTIL DEFICIENCIES ARE CORRECTED.
1.0 THIS BUILDING IS LISTED ON THE NATIONAL REGISTER OF HISTORIC PLACES.
2.0 INTERIOR FINISHES SHALL BE PHYSICALLY ISOLATED FROM CONSTRUCTION
OPERATIONS BY MEANS OF PROTECTIVE BARRIERS AND COVERINGS,
INCLUDING BUT NOT LIMITED TO: ORNAMENTAL AND DECORATIVE PLASTER
WALLS AND CEILINGS; FLOORS; STAIRCASES AND RAILINGS; WOOD AND
MARBLE WAINSCOT; WOOD DOORS; WOOD CASINGS, TRIM, AND MOLDINGS;
GLAZING; LIGHT FIXTURES AND FURNITURE.
3.0 ALL SURFACES AND FURNITURE SHALL BE PROTECTED FROM DAMAGE CAUSED
BY ABRASION, FALLING OBJECTS, DUST AND DIRT, AND SPILLED LIQUIDS.
PROVIDE CANVAS TARPS, POLYETHYLENE SHEETING AND FIRE RETARDANT
PLYWOOD PANELS (UL LISTED, CLASS A) AS REQUIRED.
4.0 FLOORS SHALL BE PROTECTED FROM HEAVY EQUIPMENT BY A LAYER OF
HOMASOTE AND FIRE RETARDANT PLYWOOD (STAGGER JOINTS TO STABILIZE
THE ASSEMBLY).
5.0 PLASTER CEILING/WALL PATCHING: PATCH OPENINGS WITH PLASTER SYSTEM
FLUSH TO MATCH EXISTING. PRIME AND PAINT ENTIRE WALL OR CEILING
SURFACE. REFER TO DIVISION 09 FOR PLASTER RESTORATION QUALIFICATIONS
AND REQUIREMENTS.
6.0 PAINTING: REFER TO DIVISION 09 FOR PAINTING REQUIREMENTS.
HISTORIC PRESERVATION GENERAL NOTES
ELECTRICAL LEGEND
LIGHTING LEGEND
DEMOLITION KEYED NOTE
CONSTRUCTION KEYED NOTE
MOTOR
1'x4' LUMINAIRE
HARDWIRED EQUIPMENT CONNECTION
P-1A12
HOMERUN TO PANEL P-1A, CIRCUIT #12. FED
FROM 20A - 1P BREAKER IS INTENDED UNLESS
NOTED OTHERWISE. RUN GREEN WIRE GROUND
FOR ALL CIRCUITS. PROVIDE ONE GROUND PER
CIRCUIT.
ENCLOSED CIRCUIT BREAKER
GROUND ROD ELECTRODE
DUPLEX RECEPTACLE WITH GFCI PROTECTION
DUPLEX RECEPTACLE WITH AFCI PROTECTION
QUAD RECEPTACLE
#
#
SPECIAL RECEPTACLE5-30R
PANELBOARD
JUNCTION BOX
B = INSTALLED IN BASEBOARD
TR = INSTALLED IN WOOD TRIM/CASEWORK/WAINSCOTT
SR = SURFACE RACEWAY
WP = WEATHERPROOF
AC = AIR CONDITIONER
X
DUPLEX RECEPTACLE:
DOUBLE DUPLEX RECEPTACLE
MOTOR STARTER
J
2'x4' LUMINAIRE
CEILING MOUNTED LUMINAIRE
EM LIGHTING BATTERY UNIT
COMBO EXIT SIGN/EM LIGHTING BATTERY UNIT
SINGLE FACE, WALL MOUNT EXIT SIGN
DOUBLE FACE, WALL MOUNT EXIT SIGN
SINGLE FACE, CEILING MOUNT EXIT SIGN
DOUBLE FACE, CEILING MOUNT EXIT SIGN
LIGHT SWITCH:
SAFETY SWITCH (NON-FUSED)
SAFETY SWITCH (FUSED)
X
3 = 3-WAY SWITCH
4 = 4-WAY SWITCH
D = DIGITAL SWITCH
R = REMOTE, WIRELESS SWITCH
O = WALL SWITCH OCCUPANCY SENSOR
V = WALL SWITCH VACANCY SENSOR
W = WIRELESS SWITCH
S = WIRELESS SCENE SWITCH
WIRELESS OCCUPANCY SENSOR
WIRELESS DAYLIGHT SENSOR
OS
X
DS
1'x2' LUMINAIRE
GENERAL SYMBOLS LEGEND
EXTERIOR ELEVATION
1
1
1 1E-100
E-100
1
1
1 1 INTERIOR ELEVATION
1
E-100
BUILDING SECTION
1
E-100
ENLARGED DETAIL
ELECTRICAL ABBREVIATIONS
AC AIR CONDITIONER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT INTERRUPTER
AMM ADDRESSABLE MONITOR MODULE
AOM ADDRESSABLE OUTPUT MODULE
ARB AUXILIARY RELAY BOARD
ATS AUTOMATIC TRANSFER SWITCH
B BASEBOARD
BKR BREAKER
C CONDUIT
CD CANDELA
CKT CIRCUIT
CR CONTROL RELAY
EC ELECTRICAL CONTRACTOR
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF STATION
FAA FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FSD FIRE SMOKE DAMPER
GAA GENERATOR ALARM ANNUNCIATOR
GFI GROUND FAULT INTERRUPTER
GND GROUND
HP HORSEPOWER
KW KILOWATT
LC LIGHTING CONTACTOR
LFMC LIQUID TIGHT FLEXIBLE METALLIC CONDUIT
LTG LIGHTING
MANUF MANUFACTURER
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUG ONLY
MTS MANUAL TRANSFER SWITCH
NAC NOTIFICATION APPLIANCE CIRCUIT
NIC NOT IN CONTRACT
OE OVERHEAD ELECTRIC
PC PHOTOCELL
PM PLUGMOLD
PP POWER PANEL
PVC POLYVINYL CHLORIDE CONDUIT
RGS RIGID GALVANIZED STEEL CONDUIT
SR SURFACE RACEWAY
ST SHUNT TRIP
TM THERMAL MAGNETIC
TR TRIM/CASEWORK/WAINSCOTT
TSP TWISTED SHIELDED PAIR
TYP TYPICAL
UE UNDERGROUND ELECTRIC
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VA VOLT AMPS
WP WATERPROOF
CONSTRUCTION PHASING:
1.0 PHASE 1: BASE BID WORK ON ALL FLOORS.
2.0 PHASE 2: SECOND AND THIRD FLOOR BID ALTERNATE WORK.
CONSTRUCTION SCHEDULING:
3.0 PHASE 1 (BASE BID) WORK:
- BASEMENT WORK:WORK MAY BEGIN
IMMEDIATELY AFTER
AWARD
- 1ST FLOOR ROOMS 108, 110 - START:MAY 30, 2017
- 1ST, 2ND, 3RD FLOORS - START: JULY 31, 2017
- ALL FLOORS - COMPLETE WORK: AUGUST 22, 2017
4.0 PHASE 2 (BID ALTERNATE) WORK:
- 2ND, 3RD FLOORS - START::DECEMBER 18, 2017
- 2ND, 3RD FLOORS - COMPLETE WORK:JANUARY 24, 2018
5.0 DURING PHASE 1 BASEMENT WORK, BUILDING MUST BE FULLY OPERATIONAL
DURING NORMAL BUSINESS HOURS.
FURNITURE:
6.0 CONTRACTOR SHALL MOVE ALL FURNITURE IN AREAS UNDER CONSTRUCTION.
CAREFULLY LOCATE FURNITURE IN 1ST FLOOR ROOMS 109, AND 110. ONCE
CONSTRUCTION IS COMPLETE, CONTRACTOR SHALL MOVE FURNITURE BACK.
7.0 CORNELL IS RESPONSIBLE FOR THE PACKING, MOVING, AND STORING OF
FACULTY/STAFF PERSONAL ITEMS.
FIRE ALARM:
8.0 FIRE ALARM SYSTEM MUST BE FULLY OPERATIONAL AT ALL TIMES.
9.0 PROVIDE CERTIFIED FIRE WATCH AT ALL TIMES THAT THE FIRE ALARM SYSTEM
IS IMPAIRED. COORDINATE ALL IMPAIRMENTS WITH CORNELL EHS.
SERVICE INTERRUPTIONS:
10.0 SERVICE INTERRUPTIONS/SHUTDOWNS MUST BE SCHEDULED 2 WEEKS IN
ADVANCE.
11.0 SERVICE INTERRUPTIONS/SHUTDOWNS MUST BE SCHEDULED TO OCCUR
OUTSIDE OF NORMAL BUSINESS HOURS AND MUST BE PERFORMED ON
WEEKENDS, OR HOLIDAYS.
TEMPORARY POWER:
12.0 TAP BUS OF EXISTING MDP AND PROVIDE A 225A/2P ENCLOSED CIRCUIT
BREAKER TO TEMPORARILY FEED THE NEW MDP DURING CONSTRUCTION.
ONCE CONSTRUCTION IS COMPLETE, DISCONNECT AND REMOVE THE
TEMPORARY FEEDER AND PROVIDE THE PERMANENT MDP FEEDER AS SHOWN
ON THE POWER RISER DIAGRAM.
EMERGENCY EGRESS:
13.0 EMERGENCY EGRESS LIGHTING AND EXIT SIGNS MUST REMAIN OPERATIONAL
AT ALL TIMES.
14.0 DO NOT IMPEDE THE MEANS OF EGRESS. IF WORK REQUIRES THE IMPAIRMENT
OF A MEANS OF EGRESS, PROVIDE CONSTRUCTION BARRIERS AND
TEMPORARY EMERGENCY EGRESS LIGHTING AND EXIT SIGNS. COORDINATE
MEANS OF EGRESS IMPAIRMENTS WITH EHS.
RESTORATION:
15.0 ALL FEEDER CONDUITS MUST BE CONCEALED WITHIN WALLS, FLOORS, AND
CEILINGS ON THE FIRST, SECOND, AND THIRD FLOORS.
16.0 ALL BRANCH CIRCUIT CONDUITS MUST BE CONCEALED WITHIN WALLS, FLOORS,
AND CEILINGS ON THE FIRST FLOOR. NO EXCEPTIONS WILL BE CONSIDERED.
17.0 BRANCH CIRCUITRY MAY BE INSTALLED IN ARMORED CABLE WITHIN THE
PLASTER WALLS/CEILINGS. TRENCH PLASTER WALLS/CEILINGS AS NEEDED.
18.0 FEEDER AND BRANCH CIRCUIT CONDUITS MAY BE EXPOSED IN THE BASEMENT.
19.0 BRANCH CIRCUITS MAY BE INSTALLED IN METALLIC SURFACE RACEWAYS IN
OFFICES AND ROOMS ON THE SECOND AND THIRD FLOORS. DO NOT INSTALL
SURFACE RACEWAYS IN THE HALLWAYS OR PUBLIC SPACES ON THE SECOND
AND THIRD FLOORS.
20.0 INSTALL SURFACE RACEWAYS ALONG EDGES/CORNERS OF WALLS AND
CEILINGS.
21.0 DO NOT INSTALL SURFACE RACEWAYS ON BASEBOARDS AND TRIMS.
22.0 PAINT ALL SURFACE RACEWAYS TO MATCH SURROUNDING SURFACES.
23.0 CONCEAL ALL BRANCH CIRCUITS TO WIRING DEVICES INSTALLED IN THE
WOOD BASEBOARD/TRIM WITHIN THE BASEBOARDS ON THE FIRST, SECOND,
AND THIRD FLOORS.
24.0 WHERE BASEBOARDS/TRIM MUST BE REMOVED TO ACCOMMODATE
CONSTRUCTION - PAINT ALL BASEBOARD/TRIM WITHIN THE ROOM/SPACE.
25.0 REPLACE BASEBOARD/TRIM DAMAGED DURING REMOVALS/CONSTRUCTION.
REPLACEMENTS MUST MATCH THE WOOD SPECIES, DIMENSIONS, PROFILE, AND
FINISH OF THE EXISTING BASEBOARD/TRIM. MINIMUM REPLACEMENT LENGTH IS
4'-0" - DO NOT PIECE-IN LENGTHS SMALLER THAN THE MINIMUM SPECIFIED.
26.0 WHERE PLASTER IS DISTURBED/RESTORED - PAINT THE ENTIRE WALL OR
CEILING.
27.0 CONTRACTOR IS RESPONSIBLE TO DETERMINE ALL FEEDER, BRANCH CIRCUIT,
AND SURFACE RACEWAY ROUTING IN FIELD. THIS WORK WILL REQUIRE
EXTENSIVE FIELD INVESTIGATION TO LOCATE SUITABLE PATHWAYS WITHIN
PLASTER WALLS AND CEILINGS, AND BETWEEN FLOORS.
STAGING/CONTRACTOR OFFICE/CONTRACTOR RESTROOM FACILITIES:
28.0 STAGE ALL CONSTRUCTION MATERIALS, EQUIPMENT, AND TOOLS IN THE
BASEMENT.
29.0 CONTRACTOR SHALL USE SPACE IN THE BASEMENT FOR A TEMPORARY
OFFICE SPACE.
30.0 CONTRACTOR MAY USE THE TOILET FACILITIES LOCATED IN RESTROOM B00T.
GARBAGE/CONSTRUCTION DEBRIS:
31.0 DUE TO SITE LIMITATIONS, A DUMPSTER MAY NOT BE LOCATED AT OR NEAR
THE BUILDING.
32.0 GARBAGE AND CONSTRUCTION DEBRIS MUST BE REMOVED FROM THE
SITE DAILY. STORE MATERIALS OUT-OF-SIGHT IN THE BASEMENT UNTIL THE
MATERIALS ARE TO BE REMOVED.
33.0 ALL CONSTRUCTION MATERIALS AND DEBRIS MUST BE MOVED INTO AND OUT
OF THE BUILDING VIA THE BASEMENT STAIRS LOCATED ON THE EAST SIDE
OF THE BUILDING.
CONTRACTOR PARKING:
34.0 CONTRACTOR SHALL CONTACT CORNELL TRANSPORTATION AND SECURE
ONE PARKING PERMIT TO PARK NEAR THE AD WHITE HOUSE. CONTRACTOR
IS RESPONSIBLE FOR ALL PARKING COSTS AND FINES.
35.0 PARKING FOR WORKERS IS AVAILABLE IN THE PARKING LOT ON EAST PALM
ROAD, NEAR THE CORNELL ORCHARDS. A NO-FEE PERMIT IS REQUIRED FOR
EACH VEHICLE.
CONSTRUCTION PHASING NOTES
LINETYPES LEGEND
UNDERGROUND ELECTRICUE
UNDERGROUND LIGHTINGUL
OVERHEAD ELECTRICOE
TO BE PROVIDED
DEMOLITION / TO BE RELOCATED
EXISTING TO REMAIN
UNDERGROUND TELCOUC
BASE BID AND ALTERNATES
1.0 BASE BID WORK:
- PROVIDE PANELBOARD REPLACEMENTS (ALL FLOORS).
- INSTALL ARC FLASH LABELS FURNISHED BY OTHERS (ALL FLOORS).
- PROVIDE SURGE PROTECTIVE DEVICES (ALL FLOORS).
- PROVIDE FEEDER REPLACEMENTS (ALL FLOORS).
- PROVIDE GROUNDING AND BONDING WORK.
- PROVIDE WIRING DEVICE REPLACEMENTS AT BASEMENT AND FIRST FLOOR.
- PROVIDE MOTOR CONTROL REPLACEMENTS AT BASEMENT AND FIRST FLOOR.
- PROVIDE BRANCH CIRCUIT REPLACEMENTS AT BASEMENT AND FIRST FLOOR.
- PROVIDE EXIT SIGN AND EMERGENCY EGRESS LIGHTING AT BASEMENT AND
FIRST FLOOR.
- PROVIDE WALL SCONCE REPLACEMENTS.
- PROVIDE WIRELESS LIGHTING CONTROLS AT BASEMENT AND FIRST FLOOR.
- PROVIDE ASSOCIATED PLASTER, TRIM, AND MOLDING RESTORATION.
- PROVIDE ASSOCIATED PAINTING WORK.
- PROVIDE ALL ASSOCIATED DEMOLITION WORK.
- PROVIDE ALL ASSOCIATED FIREPROOFING.
2.0 BID ALTERNATE E-1:
A.THIS BID ALTERNATE APPLIES TO ALL WORK ASSOCIATED
WITH THE SECOND FLOOR ELECTRICAL PANELBOARD LLP-21.
- PROVIDE WIRING DEVICE REPLACEMENTS AT SECOND FLOOR.
- PROVIDE BRANCH CIRCUIT REPLACEMENTS AT SECOND FLOOR.
- PROVIDE MOTOR CONTROL REPLACEMENTS AT SECOND FLOOR.
- PROVIDE EXIT SIGN AND EMERGENCY EGRESS LIGHTING AT SECOND
FLOOR.
- PROVIDE LIGHTING CONTROLS AT SECOND FLOOR.
- PROVIDE ASSOCIATED PLASTER, TRIM, AND MOLDING RESTORATION.
- PROVIDE ASSOCIATED PAINTING WORK.
- PROVIDE ALL ASSOCIATED DEMOLITION WORK.
- PROVIDE ALL ASSOCIATED FIREPROOFING.
3.0 BID ALTERNATE E-2:
A.THIS BID ALTERNATE APPLIES TO ALL WORK ASSOCIATED
WITH THE SECOND FLOOR ELECTRICAL PANELBOARDS LLP-22 / LLP-23.
- PROVIDE WIRING DEVICE REPLACEMENTS AT SECOND FLOOR.
- PROVIDE BRANCH CIRCUIT REPLACEMENTS AT SECOND FLOOR.
- PROVIDE MOTOR CONTROL REPLACEMENTS AT SECOND FLOOR.
- PROVIDE EXIT SIGN AND EMERGENCY EGRESS LIGHTING AT SECOND
FLOOR.
- PROVIDE LIGHTING CONTROLS AT SECOND FLOOR.
- PROVIDE ASSOCIATED PLASTER, TRIM, AND MOLDING RESTORATION.
- PROVIDE ASSOCIATED PAINTING WORK.
- PROVIDE ALL ASSOCIATED DEMOLITION WORK.
- PROVIDE ALL ASSOCIATED FIREPROOFING.
4.0 BID ALTERNATE E-3:
A.THIS BID ALTERNATE APPLIES TO ALL WORK ON THE THIRD FLOOR.
- PROVIDE WIRING DEVICE REPLACEMENTS AT THIRD FLOOR.
- PROVIDE BRANCH CIRCUIT REPLACEMENTS AT THIRD FLOOR.
- PROVIDE MOTOR CONTROL REPLACEMENTS AT THIRD FLOOR.
- PROVIDE EXIT SIGN AND EMERGENCY EGRESS LIGHTING AT THIRD
FLOOR.
- PROVIDE LIGHTING CONTROLS AT THIRD FLOOR.
- PROVIDE ASSOCIATED PLASTER, TRIM, AND MOLDING RESTORATION.
- PROVIDE ASSOCIATED PAINTING WORK.
- PROVIDE ALL ASSOCIATED DEMOLITION WORK.
- PROVIDE ALL ASSOCIATED FIREPROOFING.
5.0 WORK NOT SPECIFIED AS AN ALTERNATE IS BASE BID WORK.
O = OCCUPANCY SENSOR
V = VACANCY SENSOR
SURGE PROTECTIVE DEVICESP
1.0 ELECTRICAL EQUIPMENT SHOWN DASHED ON DEMOLITION DRAWINGS,
INCLUDING ASSOCIATED ANCHORS, SUPPORTS, STRAPS, BOXES, FITTINGS, AND
OTHER APPURTENANCES NOT SHOWN, SHALL BE DISCONNECTED AND
REMOVED. REMOVE ASSOCIATED BRANCH CIRCUITRY TO SOURCE, UNLESS
NOTED OTHERWISE.
2.0 EXISTING RACEWAYS AND BACKBOXES MAY NOT BE REUSED WITHOUT
AUTHORIZATION FROM CORNELL FACILITIES ENGINEERING.
3.0 CUT DEMOLISHED CONDUITS INSTALLED THRU WALLS AND FLOORS FLUSH
WITH THE SURFACE AND PATCH PENETRATIONS (FIRESTOP IF LOCATED ON A
FIRE RATED SURFACE). PATCH AND PAINT SURFACES IN EXPOSED AREAS TO
MATCH SURROUNDING MATERIALS, FINISHES, AND COLORS.
4.0 PROVIDE BLANK COVERPLATES ON UNUSED BACKBOXES REMAINING FROM
DEMOLITION NOT SPECIFIED TO BE INFILLED.
5.0 PATCH WALLS AT EQUIPMENT REMOVALS AND PAINT TO MATCH SURROUNDING
SURFACES.
6.0 EXISTING EQUIPMENT SHOWN TO REMAIN SHALL BE PROTECTED DURING
CONSTRUCTION.
GENERAL DEMOLITION NOTES
CB
DIGITAL TIMECLOCK
PHOTOCELLPC
TC
MOUNTING HEIGHTS
CARD READER 48" TOP OF BOX
LIGHT SWITCH 48" TOP OF BOX
RECEPTACLE 18" TOP OF BOX
DATA OUTLET 18" TOP OF BOX
TV OUTLET 84" TOP OF BOX
PHONE OUTLET 48" TOP OF BOX
SAFETY SWITCH 60" CENTERLINE OF HANDLE
MOTOR STARTER 60" CENTERLINE OF HANDLE
PANELBOARD 72" TOP OF PANELBOARD
MANUAL PULL STATION 48" OPERABLE HANDLE
NOTIFICATION APPLIANCE 80" BOTTOM OF LENS
DOOR HOLD OPEN COORDINATE IN FIELD
EM BATTERY UNIT 96" BOTTOM OF UNIT
EM REMOTE UNIT 102" BOTTOM OF UNIT
EXIT SIGN 96" BOTTOM OF UNIT
GROUND BUS BAR
M ELECTRICAL METER
DUAL, REMOTE EM LIGHTING HEADS
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
UP
UP
UP
DN
UP
DN
DN
DN
DN
UP
DN
UP
UP
UP
DN
DN
DN
DN
DN
1
TYP
2
TYP
1
TYP
2
TYP
3
3
3
3
1
TYP
2
TYP
3
3
33
1
TYP
2
TYP
UNFINISHED, ACCESSIBLE
ATTIC SPACE
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseE-010
KEYPLANSAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
SCALE: 1/16" = 1'-0"1 KEYPLAN - BASEMENT
SCALE: 1/16" = 1'-0"2 KEYPLAN - FIRST FLOOR
SCALE: 1/16" = 1'-0"3 KEYPLAN - SECOND FLOOR
SCALE: 1/16" = 1'-0"4 KEYPLAN - THIRD FLOOR 0 8 16 32
SCALE: 1/16"=1'-0"
0 8 16 32
SCALE: 1/16"=1'-0"
0 8 16 32
SCALE: 1/16"=1'-0"
0 8 16 32
SCALE: 1/16"=1'-0"
CEILING HEIGHT:
7'-2" FINISHED FLOOR TO
BOTTOM OF WOOD JOISTS
CEILING HEIGHT:
12'-4" FINISHED FLOOR TO
PLASTER CEILING.
CEILING HEIGHT:
10'-4" FINISHED FLOOR TO
PLASTER CEILING.
CEILING HEIGHT:
11'-0" FINISHED FLOOR TO
PLASTER CEILING.
E-010 KEYED CONSTRUCTION NOTES
1 WALLS SHOWN SHADED ARE SOLID MASONRY WITH PLASTER ADHERED DIRECTLY
TO THE MASONRY. THERE IS NO CAVITY BETWEEN THE MASONRY AND PLASTER TO
INSTALL FEEDER OR BRANCH CIRCUITRY.
2 WALLS SHOWN NOT SHADED UTILIZE CONVENTIONAL LUMBER FRAMING AND MAY
HAVE AN ACCESSIBLE CAVITY TO INSTALL FEEDER AND BRANCH CIRCUITRY.
3 LOCATIONS INDICATED ARE PIPE CHASES FROM THE 1973 RENOVATION PROJECT
THAT MAY CONTAIN SPACE FOR FEEDER AND BRANCH CIRCUIT WIRING. CHASES
ARE LOCATED BEHIND PLASTER WALLS. LOCATIONS ARE SHOWN FOR REFERENCE
ONLY. CONTRACTOR MUST VERIFY IF PIPE CHASES CONTAIN ADEQUATE SPACE
FOR FEEDER AND BRANCH CIRCUIT WIRING. IF PIPE CHASES ARE USED, PATCH
PLASTER AND PAINT WALLS.
#
BASEMENT CONDUIT INSTALLATION:
- FEEDERS MAY BE INSTALLED EXPOSED.
- BRANCH CIRCUITS MAY BE INSTALLED EXPOSED.
FIRST FLOOR CONDUIT INSTALLATION:
- FEEDERS MUST BE CONCEALED WITHIN WALLS,
FLOORS, OR CEILINGS. TRENCH PLASTER WALLS
AND RESTORE.
- BRANCH CIRCUITS MUST BE CONCEALED WITHIN
WALLS, FLOORS, OR CEILINGS. TRENCH PLASTER
WALLS AND RESTORE. SURFACE RACEWAYS ARE
NOT ACCEPTABLE.
- BRANCH CIRCUITS FEEDING RECEPTACLES INSTALLED
IN WOOD BASEBOARDS MUST BE CONCEALED WITHIN
THE WOOD BASEBOARDS.
SECOND FLOOR CONDUIT INSTALLATION:
- FEEDERS MUST BE CONCEALED WITHIN WALLS,
FLOORS, OR CEILINGS. TRENCH PLASTER WALLS
AND RESTORE.
- BRANCH CIRCUITS MAY BE INSTALLED IN METALLIC
SURFACE RACEWAYS.
- BRANCH CIRCUITS FEEDING RECEPTACLES INSTALLED
IN WOOD BASEBOARDS MUST BE CONCEALED WITHIN
THE WOOD BASEBOARDS.
THIRD FLOOR CONDUIT INSTALLATION:
- FEEDERS MUST BE CONCEALED WITHIN WALLS,
FLOORS, OR CEILINGS. TRENCH PLASTER WALLS
AND RESTORE.
- BRANCH CIRCUITS MAY BE INSTALLED IN METALLIC
SURFACE RACEWAYS.
- BRANCH CIRCUITS FEEDING RECEPTACLES INSTALLED
IN WOOD BASEBOARDS MUST BE CONCEALED WITHIN
THE WOOD BASEBOARDS.
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
B00UB
B00UC
B11
B13
B13C
B13B
B13A
B04
B07
B02
B05
B00T
B03 B01
B14
B00SB
B00SA
B00UA
B09
PIT
CRAWL
SPACE
CRAWL
SPACE
B00C
UP
UP
UP
FCU-B1
FCU-B2
FCU-B3
FCU-B7
FCU-B4
FCU-B5
FCU-B6
SP-2
SP-1
CP-1 48"SPSP
SP
SP48"48"
CB
100TB
100SC
100SA
100SB
100JA
113
113A
114
108
112
109
101
110
103
100TA
103A
103B
102
102A
100CA 100CB
100JB
111
ENCLOSED PORCH
PORCH
PORCH
PATIO
114A
DN
UP
DN
DN
DN
DN
UP
DN
B
BB BB B B
BBBBB
BB B
BTR
B
BSRSRB BWPTRCUH-1
AC AC WPWPJ-2
J-1
FEEDER UP TO
PANEL LLP-21
FEEDER UP TO
PANEL LLP-22
FEEDER UP TO
PANEL LLP-23
MDP
LLP-B2
LLP-B3
LLP-B1
SM-1
SM-2
SM-3
IR-1
WH-1
FACP
LLP-B1-26
LLP-B1-10
LLP-B1-8
LLP-B1-4
LLP-B2-10,12
LLP-B2-29
LLP-B2-9,11
LLP-B2-4
LLP-B2-10,12
LLP-B2-23
LLP-B2-37,39
LLP-B2-8
LLP-B2-1LLP-B2-23
LLP-B2-23
LLP-B3-4
LLP-B3-5
1
1
1
2
TYP
4
4
3
TYP
5
TYP
6
6
EXISTING 2.4KV/120/240V
TRANSFORMER
EXISTING 2.4KV SWITCH
PUMP CP
EF-B00UC
LLP-B2-22
LLP-B1-30,32
LLP-B1-19,21
LLP-B1-12,14
LLP-B1-16
LLP-B3-11
LLP-B3-13
15
6
M16
17
PM PM
PM
RNG-1
LLP-B1-22
LLP-B1-7
LLP-B1-17LLP-B1-5,7
LLP-B1-6
LLP-B1-18
LLP-B1-3
LLP-B1-9
LLP-B2-2
LLP-B1-1
LLP-B3-7
LLP-B3-3
LLP-B3-2
LLP-B3-9
LLP-B2-33
LLP-B2-21
LLP-B2-25
LLP-B2-7
LLP-B2-19
LLP-B2-15,17
LLP-B2-14 LLP-B2-27
LLP-B2-13LLP-B2-16
LLP-B2-20
2
TYP
3
TYP
8 8
9
7
TYP
10
11
12
UNDERSINK
DISPOSAL
13
14
LLP-B2-20
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseE-100
POWER PLANS -
BASEMENT AND
FIRST FLOORSAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
#
0 4 8 16
SCALE: 1/8"=1'-0"
0 4 8 16
SCALE: 1/8"=1'-0"
SCALE: 1/8" = 1'-0"1 POWER PLAN - BASEMENT
SCALE: 1/8" = 1'-0"2 POWER PLAN - FIRST FLOOR
E-100 KEYED CONSTRUCTION NOTES
1 PROVIDE PANELBOARD AND FASTEN TO MASONRY WALL USING TAPCON
FASTENERS. INSTALL ARC FLASH LABELS FURNISHED BY ENGINEER. REFER TO
THE POWER RISER DIAGRAM ON DRAWING E-500 AND THE PANEL SCHEDULES FOR
ADDITIONAL INFORMATION.
2 PROVIDE WIRING DEVICES AS SHOWN. BASEMENT: PROVIDE SURFACE MOUNT
METAL BACKBOXES AND CIRCUIT WITH 2#12, 1#12GND, 3/4" EMT. FIRST FLOOR:
PROVIDE FLUSH METAL BACKBOXES IN WALLS/BASEBOARD AND CIRCUIT WITH 2#12
PLUS GROUND METAL-CLAD. CONCEAL FIRST FLOOR BRANCH CIRCUITRY WITHIN
WALLS, FLOORS, AND CEILINGS. PROVIDE PANEL AND CIRCUIT LABELS ON EACH
COVERPLATE. PROVIDE 1-HOUR FIRE RATED FLOOR PENETRATIONS. REFER TO
DETAIL #1/E-504 FOR ADDITIONAL INFORMATION.
3 REFER TO THE PANELBOARD SCHEDULES AND THE EQUIPMENT CONNECTION
SCHEDULE ON DRAWING E-503 FOR BRANCH CIRCUIT, MOTOR STARTER, AND
DISCONNECT INFORMATION. PROVIDE A PLASTIC ID TAG ON ALL EQUIPMENT.
4 PROVIDE JUNCTION BOX AND FASTEN TO THE WOOD JOISTS. REFER TO THE
POWER RISER DIAGRAM FOR JUNCTION BOX SIZES.
5 INSTALL FEEDERS ON CEILING. REFER TO THE POWER RISER DIAGRAM FOR
ADDITIONAL INFORMATION.
6 PROVIDE 1-HOUR FIRE RATED FLOOR PENETRATION. REFER TO DETAIL #1/E-504
FOR ADDITIONAL INFORMATION.
7 CIRCUIT PLUGMOLD WITH 2#12, 1#12GND, 3/4" EMT. PROVIDE 1-HOUR FIRE RATED
FLOOR PENETRATIONS. REFER TO DETAIL #1/E-504 FOR ADDITIONAL INFORMATION.
8 PROVIDE WIRING DEVICES AS SHOWN. LOCATE RECEPTACLES WITHIN CORD
LENGTH OF AIR CONDITIONERS. CIRCUIT WITH 2#12 PLUS GROUND METAL CLAD
AND CONCEAL BRANCH CIRCUITRY WITHIN WALLS, FLOORS, AND CEILINGS.
9 RECEPTACLES AND PLUGMOLD WITHIN ROOMS 103, 103A, 103B, AND 100TA SHALL
BE PROTECTED BY AFCI CIRCUIT BREAKERS.
10 REMOVE PORTION OF PLASTER WALL AS NEEDED TO INSTALL PANEL LLP-23
FEEDER (FROM BASEMENT TO SECOND FLOOR). PATCH PLASTER WALL AND PAINT.
11 REMOVE PORTION OF GYPSUM WALL AS NEEDED TO INSTALL PANEL LLP-22
FEEDER (FROM BASEMENT TO SECOND FLOOR). INCLUDES THE REMOVAL AND
REINSTALLATION OF THE KITCHEN 102 UPPER CABINETS, LOWER CABINETS, AND
LAMINATE COUNTERTOP TO ACCOMMODATE THE WORK. PATCH AND PAINT WALL
AFTER REINSTALLATION OF CABINETS AND COUNTERTOP.
12 REMOVE PORTION OF PLASTER WALL AS NEEDED TO INSTALL PANEL LLP-21
FEEDER (FROM BASEMENT TO SECOND FLOOR). PATCH PLASTER WALL AND PAINT.
13 ALL RECEPTACLES IN KITCHEN 102 TO BE GFCI TYPE.
14 RECEPTACLES WITHIN ROOMS 103, 103A, 103B, AND 100TA SHALL BE TAMPER
RESISTANT.
15 MAINTAIN THE EXISTING MDP AND PROVIDE AN ENCLOSED CIRCUIT BREAKER AND
FEEDER TO TEMPORARILY FEED THE NEW MDP DURING CONSTRUCTION. REFER
TO THE POWER RISER DIAGRAM ON DRAWING E-500 FOR ADDITIONAL
INFORMATION.
16 INSTALL NEW ELECTRIC METER FURNISHED BY CORNELL. REFER TO THE POWER
RISER DIAGRAM ON DRAWING E-500 FOR ADDITIONAL INFORMATION.
17 AFTER SWITCHOVER OF NEW MDP FEEDER AND REMOVAL OF OLD MDP, REWORK
THE EXISTING POWERSCOUT ELECTRIC METER CT'S TO METER THE NEW MDP
FEEDER.
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
200TC
200CA 200CC204
201
213
212
211A
214
215
217
218
223
220
207
208
210
200CB200SC200TA200TD200J
100SB
200SE
200SA
200SD
223APORCH211
212A
214A
208A
204A
OPEN TO
BELOW
UP
UP
UP
DN
DN
DN BSRSRSR
SR SR
B BCUH-9 CUH-10
CUH-8
CUH-7
CUH-5
CUH-6
CUH-2
CUH-3 CUH-4
CUH-18
SRB48"SPSP
SP
200SD
304
302
300T
301
307
308
309 310
300J
312
CRAWL
SPACE
304A
300SA
301A
301C
301B
310A
300CA
300CB
DN
DN
B
B
B
CUH-16
CUH-15
CUH-17
CUH-14
CUH-13
EF-1
CUH-12
CUH-11BB
M
PANEL
LLP-21
PM
PM PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
LLP-22
LLP-23
LLP-21-10
LLP-21-12
LLP-21-11
LLP-21-15
LLP-21-9
LLP-21-10
LLP-21-5
LLP-21-18
LLP-21-8
LLP-21-14
LLP-21-3
LLP-22-5
LLP-22-2
LLP-21-1
LLP-22-4
LLP-22-6
LLP-22-6
LLP-22-3
LLP-23-2 LLP-23-3
LLP-23-4
LLP-23-5
LLP-21-8
1
3
4
6
7
PANEL LLP-21 DOWN
TO FIRST FLOOR 5
TYP
2
1
TYP
TYP
8
LLP-22-1
9
BID ALTERNATE E-2
BID ALTERNATE E-1
BID ALTERNATE E-2
BID ALTERNATE E-1
LLP-31
PM
PM
PM
PM PM
PM
PM
PM
PM
PM
PM
PM
PM
LLP-31-12
LLP-31-14
LLP-31-2
LLP-31-10 LLP-31-7
LLP-31-10
LLP-31-8
LLP-31-5
LLP-31-15
LLP-31-15
LLP-31-11
LLP-31-3
LLP-31-12
LLP-31-9
LLP-31-4
LLP-31-6
LLP-31-4
3
TYP
6
TYP
4
TYP
2 7 8 N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseE-101
POWER PLANS -
SECOND AND
THIRD FLOORSAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
0 4 8 16
SCALE: 1/8"=1'-0"
0 4 8 16
SCALE: 1/8"=1'-0"
E-101 KEYED CONSTRUCTION NOTES
1 PROVIDE PANELBOARD AND FASTEN TO PLASTER WALL USING TAPCON
FASTENERS. INSTALL ARC FLASH LABELS FURNISHED BY ENGINEER. REFER TO
THE POWER RISER DIAGRAM ON DRAWING E-500 AND THE PANEL SCHEDULES FOR
ADDITIONAL INFORMATION. LOCATE LLP-21 PANELBOARD IN FRONT OF DOOR TO
ACHIEVE CODE REQUIRED WORKING SPACE.
2 PROVIDE PANELBOARD AND INSTALL FLUSH WITH PLASTER WALL. INSTALL ARC
FLASH LABELS FURNISHED BY ENGINEER. REFER TO THE POWER RISER DIAGRAM
ON DRAWING E-500 AND THE PANEL SCHEDULES FOR ADDITIONAL INFORMATION.
3 PROVIDE WIRING DEVICES AS SHOWN. WIRING DEVICES INSTALLED IN WOODEN
BASE: PROVIDE FLUSH METAL BACKBOXES AND CIRCUIT WITH 2#12 PLUS GROUND
METAL CLAD AND CONCEAL BRANCH CIRCUITRY WITHIN WOOD BASE. DEVICES
INSTALLED ON WALLS: PROVIDE METALLIC SURFACE RACEWAY AND PAINT TO
MATCH SURROUNDING SURFACES. PROVIDE PANEL AND CIRCUIT LABELS ON EACH
COVERPLATE. PROVIDE 1-HOUR FIRE RATED FLOOR PENETRATION. REFER TO
DETAIL #1/E-504 FOR ADDITIONAL INFORMATION.
4 REFER TO THE PANELBOARD SCHEDULES AND THE EQUIPMENT CONNECTION
SCHEDULE ON DRAWING E-503 FOR BRANCH CIRCUIT, MOTOR STARTER, AND
DISCONNECT INFORMATION. PROVIDE A PLASTIC ID TAG ON ALL EQUIPMENT.
5 PROVIDE 1-HOUR FIRE RATED FLOOR PENETRATION. REFER TO DETAIL #1/E-504
FOR ADDITIONAL INFORMATION.
6 CIRCUIT PLUGMOLD WITH 2#12, 1#12GND, 3/4" EMT. PROVIDE 1-HOUR FIRE RATED
FLOOR PENETRATION. REFER TO DETAIL #1/E-504 FOR ADDITIONAL INFORMATION.
7 REMOVE PORTIONS OF PLASTER WALL TO ACCOMMODATE A FLUSH PANELBOARD
BACKBOX. PROVIDE WITH AN OVERSIZED DOOR TRIM TO CONCEAL WITH ROUGH
OPENING. PATCH PLASTER WALL AND PAINT.
8 REMOVE PORTION OF GYPSUM WALL AS NEEDED TO INSTALL PANEL LLP-23 AND 31
FEEDERS (FROM FIRST FLOOR TO THIRD FLOOR). INCLUDES THE REMOVAL AND
REINSTALLATION OF THE UPPER CABINETS, LOWER CABINETS, AND LAMINATE
COUNTERTOP TO ACCOMMODATE THE WORK.
9 FLUSH MOUNT SURGE PROTECTIVE DEVICE. PROVIDE WITH A PAINTED METAL TRIM
TO CONCEAL ROUGH-OPENING.
#
SCALE: 1/8" = 1'-0"1 POWER PLAN - SECOND FLOOR
SCALE: 1/8" = 1'-0"2 POWER PLAN - THIRD FLOOR
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
B00UB
B00UC
B11
B13
B13C
B13B
B13A
B04
B07
B02
B05
B00T
B03 B01
B14
B00SB
B00SA
B00UA
B09
PIT
CRAWL
SPACE
CRAWL
SPACE
B00C
UP
UP
UPWWWWW
W
W WW
W
WW
W
WWW
WW
W
W WTC
TC
100TB
100SC
100SA
100SB
100JA
113
113A
114
108
112
109
101
110
103
100TA
103A
103B
102
102A
100CA 100CB
100JB
111
ENCLOSED PORCH
PORCH
PORCH
PATIO
114A
DN
UP
DN
DN
DN
DN
UP
DN
W W
W
W
WW
W
W
W
WWWWWWWWWWDWWWWWWWW
W
W W4 DWWW
D
R WMDP
LLP-B3
LLP-B1
LLP-B1-2
LLP-B2-3
LLP-B2
LLP-B3-1
TO FIRST FLOOR
STAIRS SWITCH
LLP-B2-18
1
4
TYP
2
TYP
OS
V
OS
V
OS
V
OS
O
OS
O
OS
O
OS
O
OS
O
OS
V
OS
O
OS
V
OS
O
OS
V
OS
O
OS
O
OS
O
OS
O
5
TYP
OS
O
OS
O
OS
O
NL
12
12
NL
TC-1
13
TC-213
1 1
1 1
1
1
1
1
OS
O
OS
O
OS
O
OS
O
OS
O
OS
O
OS
O
OS
O
OS
O
OS
O
OS
V
LLP-B1-13
LLP-B1-13
LLP-B1-13
LLP-B1-13
LLP-B1-13
LLP-B3-6
LLP-B3-6
LLP-B2-6
LLP-B2-6
LLP-B2-24
LLP-B2-5
LLP-B2-6
LLP-B3-6
DS
UP TO 2ND
FLOOR
OS
O
TO BASEMENT
LIGHTS
TO 2ND FLOOR
LIGHTS
OS
V
OS
O
OS
V
EXISTING
COVE
LIGHTING
EXISTING
COVE
LIGHTING
6
7
3
TYP
4
TYP
2
TYP
5
TYP
9
10
10
10
11
8
1
1
LLP-B3-8
LLP-B1-11
14
14
14
LLP-B2-24
15
PC
16
DS
DS
DS
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseE-200
LIGHTING PLANS -
BASEMENT AND
FIRST FLOORAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
SCALE: 1/8" = 1'-0"1 LIGHTING PLAN - BASEMENT
E-200 KEYED CONSTRUCTION NOTES
1 PROVIDE A WIRELESS LIGHTING CONTROLS GATEWAY AND MOUNT HORIZONTALLY
ON WALL. COORDINATE LOCATION WITH LIGHTING CONTROLS MANUFACTURER
FOR COMPLETE COVERAGE. PROVIDE A DATA CONNECTION TO THE DATA RACK IN
ROOM B03. PROVIDE ALL DATA CABLING, JACKS, TERMINATIONS, PATCH PANEL
ACCESSORIES, AND CABLE TESTING. REFER TO THE DETAIL #1/E-504 FOR
ADDITIONAL INFORMATION. PROVIDE ADDITIONAL WIRELESS GATEWAYS AS
REQUIRED TO PROVIDE COMPLETE COVERAGE, INCLUDING ALL NECESSARY
POWER AND DATA. PROVIDE ALL REQUIRED PROGRAMMING AND SYSTEM
COMMISSIONING. COORDINATE TELCO WORK WITH CIT.
2 AT EACH LOCATION, PROVIDE A SINGLE-GANG METAL DEVICE BOX WITH A
WIRELESS WALL-MOUNT SWITCH.
3 AT EACH LOCATION, PROVIDE A SCONCE LUMINAIRE. MATCH HEIGHT OF
DEMOLISHED SCONCES. REFER TO THE LUMINAIRE SCHEDULE FOR ADDITIONAL
INFORMATION.
4 PROVIDE A WIRELESS LUMINAIRE CONTROLLER FOR ALL INTERIOR LUMINAIRES
SHOWN. CONTRACTOR SHALL DETERMINE WHICH CONTROLLER (INTERNAL OR
EXTERNAL MOUNT) TO USE IN-FIELD.
5 PROVIDE WIRELESS MOTION SENSORS AS SHOWN. PROGRAM AS OCCUPANCY OR
VACANCY PER PLANS. SECURELY FASTEN TO WALL OR CEILING. LOCATE DEVICES
TO PROVIDE MAXIMUM SENSOR COVERAGE.
6 PROVIDE A WIRELESS, REMOTE SWITCH. FASTEN TO WALL USING DOUBLE-SIDED
TAPE.
7 INSTALL LIGHTING BRANCH CIRCUITRY FROM FLOOR ABOVE. REFER TO DRAWING
ED-101 FOR ADDITIONAL INFORMATION.
8 CONNECT WIRELESS SWITCH TO THE SECOND FLOOR STAIR LIGHTING.
9 AT APARTMENT, PROVIDE A SINGLE-GANG FLUSH DEVICE BOX WITH A WIRELESS
WALL-MOUNT SWITCH. PROVIDE A WIRELESS PLUG LOAD CONTROLLER AT ONE OF
THE RECEPTACLES IN ROOM 103 TO CONTROL A TABLE LAMP. COORDINATE
RECEPTACLE WITH BUILDING COORDINATOR.
10 CONNECT WIRELESS WALL-MOUNT SWITCHES TO (9) EXISTING UNDERCABINET
LIGHTS. ASSOCIATE EACH WALL OF LIGHTS TO THE RESPECTIVE WIRELESS
SWITCH.
11 CONNECT WIRELESS SWITCH AND EXISTING LIGHT TO THE BASEMENT LIGHTING
CIRCUIT.
12 NIGHT LIGHT: CIRCUIT TO THE UNSWITCHED PHASE CONDUCTOR OF THE LIGHTING
BRANCH CIRCUIT SERVING THE SPACE.
13 PROVIDE A DIGITAL TIMECLOCK AND CIRCUIT AS SHOWN. REFER TO DETAIL
#3/E-504 FOR ADDITIONAL INFORMATION.
14 PROVIDE A DIGITAL SWITCH AND CIRCUIT TO THE RESPECTIVE DIGITAL TIMECLOCK.
INSTALL LIGHTING BRANCH CIRCUITRY THRU THE TIMECLOCK RELAY. REFER TO
DETAIL #3/E-504 FOR ADDITIONAL INFORMATION.
15 PROVIDE UNSWITCHED PHASE CONDUCTOR FROM BRANCH CIRCUIT INDICATED.
INSTALL LIGHTING BRANCH CIRCUITRY THRU THE TIMECLOCK RELAY. REFER TO
DETAIL #3/E-504 FOR ADDITIONAL INFORMATION.
16 PROVIDE AN OUTDOOR RATED PHOTOCELL WITH A WEATHERPROOF, SINGLE-GANG
BOX WITH GASKETED COVERPLATE. INSTALL ON PORCH FASCIA AND PAINT BOX
TO MATCH FASCIA. SURFACE MOUNT CONDUIT WITHIN ENCLOSED PORCH WOOD
CEILING. PAINT CONDUIT TO MATCH PORCH CEILING. REFER TO DETAIL #3/E-504
FOR ADDITIONAL INFORMATION.
#
0 4 8 16
SCALE: 1/8"=1'-0"
0 4 8 16
SCALE: 1/8"=1'-0"
SCALE: 1/8" = 1'-0"2 LIGHTING PLAN - FIRST FLOOR
LIGHTING CIRCUITING/CONTROLS NOTE:
1.BRANCH CIRCUITING SHOWN TO WIRELESS SWITCHES IS FOR REFERENCE
ONLY AND IS USED TO CLEARLY INDICATE LUMINAIRE GROUPINGS AND
SWITCHING.
2.WIRELESS SWITCHES ARE CONSTRUCTED WITH DIMMING CONTROLS.
EXISTING LUMINAIRES ARE FLUORESCENT AND DO NOT UTILIZE DIMMING
BALLASTS. WIRELESS SWITCH DIMMING FEATURE IS FOR FUTURE USE.
LIGHTING CIRCUITING/CONTROLS NOTE:
1.BRANCH CIRCUITING SHOWN TO WIRELESS SWITCHES IS FOR REFERENCE
ONLY AND IS USED TO CLEARLY INDICATE LUMINAIRE GROUPINGS AND
SWITCHING.
2.WIRELESS SWITCHES ARE CONSTRUCTED WITH DIMMING CONTROLS.
EXISTING LUMINAIRES ARE FLUORESCENT AND DO NOT UTILIZE DIMMING
BALLASTS. WIRELESS SWITCH DIMMING FEATURE IS FOR FUTURE USE.
3.EXISTING FLUORESCENT LUMINAIRES DO NOT UTILIZE DIMMING BALLASTS.
WIRELESS DAYLIGHT SENSORS SPECIFIED FOR THESE SPACES ARE FOR
FUTURE USE.
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
200TC
200CA 200CC204
201
213
212
211A
214
215
217
218
223
220
207
208
210
200CB200SC200TA200TD200J
100SB
200SE
200SA
200SD
223APORCH211
212A
214A
208A
204A
OPEN TO
BELOW
UP
UP
UP
DN
DN
DN
W
W
W
WW WWWWWWWW
WWWWWWWWWWWWWRRRRR RRR200SD
304
302
300T
301
307
308
309 310
300J
312
CRAWL
SPACE
304A
300SA
301A
301C
301B
310A
300CA
300CB
DN
DN
W W WWW
WW
WW
W RW
R
R
RPANEL
LLP-21
LLP-22
LLP-23
LLP-21-4
LLP-21-4
LLP-21-4
LLP-21-6
LLP-21-7
LLP-21-6
LLP-21-6
LLP-21-6
LLP-21-2
LLP-23-6
LLP-23-6
LLP-23-6
LLP-23-6
LLP-23-1
LLP-23-7
LLP-23-6
LLP-23-7
LLP-23-7
5OS
V
OS
O
OS
O
OS
V
OS
V
OS
V
OS
O
OS
O
DOWN TO
FIRST FLOOR
OS
O
OS
O
OS
O
OS
O
OS
V
OS
V
5
5
OS
V
OS
O
OS
O
OS
V OS
O
OS
O
OS
O
OS
O
OS
O
OS
O
OS
O
OS
O
OS
O
OS
V
OS
VDOWN TO
FIRST FLOOR
DOWN TO
FIRST FLOOR
LLP-21-7
LLP-21-7
OS
V LLP-23-1
LLP-21-13
LLP-23-8
1
5
5
5
1
3
2
4
TYP
TYP
TYP
5
1
1
1
1 1
1 1
1
1
DS
DS
DS
DS
DS
DS
DS
BID ALTERNATE E-2
BID ALTERNATE E-1
BID ALTERNATE E-2
BID ALTERNATE E-1
LLP-23-1
LLP-31
LLP-31-1
LLP-31-6 LLP-31-6
LLP-31-1
LLP-31-6
LLP-31-6
LLP-31-18
LLP-31-18
LLP-31-18
DOWN TO
SECOND FLOOR
OS
O
OS
O
OS
O
OS
O
OS
O
OS
V
OS
O
OS
O
OS
O
OS
O
OS
O
OS
O
OS
V
OS
V
OS
V
OS
O
LLP-31-13
5
5
5
5
3
TYP
1
2
TYP
4
TYP
DS
DS
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseE-201
LIGHTING PLANS -
SECOND AND
THIRD FLOORSAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
#
0 4 8 16
SCALE: 1/8"=1'-0"
0 4 8 16
SCALE: 1/8"=1'-0"
SCALE: 1/8" = 1'-0"1 LIGHTING PLAN - SECOND FLOOR
SCALE: 1/8" = 1'-0"2 LIGHTING PLAN - THIRD FLOOR
E-201 KEYED CONSTRUCTION NOTES
1 PROVIDE A WIRELESS LIGHTING CONTROLS GATEWAY AND MOUNT HORIZONTALLY
ON WALL. COORDINATE LOCATION WITH LIGHTING CONTROLS MANUFACTURER
FOR COMPLETE COVERAGE. PROVIDE A DATA CONNECTION TO THE DATA RACK IN
ROOM B03. PROVIDE ALL DATA CABLING, JACKS, TERMINATIONS, PATCH PANEL
ACCESSORIES, AND CABLE TESTING. REFER TO THE DETAIL #1/E-504 FOR
ADDITIONAL INFORMATION. PROVIDE ADDITIONAL WIRELESS GATEWAYS AS
REQUIRED TO PROVIDE COMPLETE COVERAGE, INCLUDING ALL NECESSARY
POWER AND DATA. PROVIDE ALL REQUIRED PROGRAMMING AND SYSTEM
COMMISSIONING. COORDINATE TELCO WORK WITH CORNELL.
2 AT EACH LOCATION, PROVIDE A SINGLE-GANG METAL DEVICE BOX WITH A
WIRELESS WALL-MOUNT SWITCH.
3 PROVIDE A WIRELESS LUMINAIRE CONTROLLER FOR ALL INTERIOR LUMINAIRES
SHOWN. CONTRACTOR SHALL DETERMINE WHICH CONTROLLER (INTERNAL OR
EXTERNAL MOUNT) TO USE IN-FIELD.
4 PROVIDE WIRELESS MOTION SENSORS AS SHOWN. PROGRAM AS OCCUPANCY OR
VACANCY PER PLANS. SECURELY FASTEN TO WALL OR CEILING. LOCATE DEVICES
TO PROVIDE MAXIMUM SENSOR COVERAGE.
5 PROVIDE A WIRELESS, REMOTE SWITCH. FASTEN TO WALL USING DOUBLE-SIDED
TAPE. REMOVE CEILING MOUNT LUMINAIRE AND PROVIDE A 4x4 SURFACE J-BOX
(TO INSTALL WIRELESS LUMINAIRE CONTROLLER) AND REINSTALL LUMINAIRE.
LIGHTING CIRCUITING/CONTROLS NOTE:
1.BRANCH CIRCUITING SHOWN TO WIRELESS SWITCHES IS FOR REFERENCE
ONLY AND IS USED TO CLEARLY INDICATE LUMINAIRE GROUPINGS AND
SWITCHING.
2.WIRELESS SWITCHES ARE CONSTRUCTED WITH DIMMING CONTROLS.
EXISTING LUMINAIRES ARE FLUORESCENT AND DO NOT UTILIZE DIMMING
BALLASTS. WIRELESS SWITCH DIMMING FEATURE IS FOR FUTURE USE.
3.EXISTING FLUORESCENT LUMINAIRES DO NOT UTILIZE DIMMING BALLASTS.
WIRELESS DAYLIGHT SENSORS SPECIFIED FOR THESE SPACES ARE FOR
FUTURE USE.
LIGHTING CIRCUITING/CONTROLS NOTE:
1.BRANCH CIRCUITING SHOWN TO WIRELESS SWITCHES IS FOR REFERENCE
ONLY AND IS USED TO CLEARLY INDICATE LUMINAIRE GROUPINGS AND
SWITCHING.
2.WIRELESS SWITCHES ARE CONSTRUCTED WITH DIMMING CONTROLS.
EXISTING LUMINAIRES ARE FLUORESCENT AND DO NOT UTILIZE DIMMING
BALLASTS. WIRELESS SWITCH DIMMING FEATURE IS FOR FUTURE USE.
3.EXISTING FLUORESCENT LUMINAIRES DO NOT UTILIZE DIMMING BALLASTS.
WIRELESS DAYLIGHT SENSORS SPECIFIED FOR THESE SPACES ARE FOR
FUTURE USE.
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
B00UB
B00UC
B11
B13
B13C
B13B
B13A
B04
B07
B02
B05
B00T
B03 B01
B14
B00SB
B00SA
B00UA
B09
PIT
CRAWL
SPACE
CRAWL
SPACE
B00C
UP
UP
UP
136
208
293
385
237
792
387
591
590
229
561
269
108
46
73
51
47
15
19
91
38
44
90
10
UP
100TB
100SC
100SA
100SB
100JA
113
113A
114
108
112
109
101
110
103
100TA
103A
103B
102
102A
100CA 100CB
100JB
111
ENCLOSED PORCH
PORCH
PORCH
PATIO
114A
DN
UP
DN
DN
DN
DN
UP
DN
X2
X4
X3
X3
X4
1
TYP
X3
X4
X4
X1
X3
X3 X3
X3
X4
X4
X5
X5
X3
1
TYP
2
2
X1
X5
3
4
X4
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseE-300
EGRESS LIGHTING
PLANS -
BASEMENT AND
FIRST FLOORSAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
SCALE: 1/8" = 1'-0"1 EGRESS LIGHTING PLAN - BASEMENT
SCALE: 1/8" = 1'-0"2 EGRESS LIGHTING PLAN - FIRST FLOOR 0 4 8 16
SCALE: 1/8"=1'-0"
0 4 8 16
SCALE: 1/8"=1'-0"
#E-300 KEYED CONSTRUCTION NOTES
1 CIRCUIT EMERGENCY EGRESS LIGHTS AND EXIT SIGNS FROM THE UNSWITCHED
LIGHTING BRANCH CIRCUIT SERVING THE SPACE IN WHICH IT IS INSTALLED FOR
POWER SENSING AND CHARGING. CIRCUIT WITH 2#12, 1#12GND, 3/4" EMT IN A
DEDICATED RACEWAY - NO OTHER BRANCH CIRCUITRY MAY BE PULLED IN THESE
RACEWAYS. TYPICAL FOR ALL EMERGENCY EGRESS LIGHTS AND EXIT SIGNS.
2 CIRCUIT REMOTE HEADS TO THE NEAREST EMERGENCY LIGHTING BATTERY UNIT.
COREDRILL WALL AND PATCH PENETRATIONS.
3 CIRCUIT REMOTE HEADS TO THE NEAREST EMERGENCY LIGHTING BATTERY UNIT.
COREDRILL WALL AND PATCH PENETRATION. CENTER REMOTE HEADS ON BRICK
WALL, BELOW LIMESTONE BALCONY SUPPORT (+/- 6'-0" ABOVE LANDING).
4 REMOVE PORTION OF PLASTER WALL AS NEEDED TO CONCEAL TYPE X5 REMOTE
HEAD CIRCUITRY. PATCH PLASTER WALL AND PAINT.
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
200TC
200CA 200CC204
201
213
212
211A
214
215
217
218
223
220
207
208
210
200CB200SC200TA200TD200J
100SB
200SE
200SA
200SD
223APORCH211
212A
214A
208A
204A
OPEN TO
BELOW
UP
UP
UP
DN
DN
DN
200SD
304
302
300T
301
307
308
309 310
300J
312
CRAWL
SPACE
304A
300SA
301A
301C
301B
310A
300CA
300CB
DN
DN
X2
X4
X4
X3
X3
X3
1
TYP
X4
X2
X2
X4
BID ALTERNATE E-2
BID ALTERNATE E-1
BID ALTERNATE E-2
BID ALTERNATE E-1
X3
X3
X4
1
TYP
X1
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseE-301
EGRESS LIGHTING
PLANS - SECOND
AND THIRD
FLOORSAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
0 4 8 16
SCALE: 1/8"=1'-0"
0 4 8 16
SCALE: 1/8"=1'-0"
SCALE: 1/8" = 1'-0"1 EGRESS LIGHTING PLAN - SECOND FLOOR
SCALE: 1/8" = 1'-0"2 EGRESS LIGHTING PLAN - THIRD FLOOR
E-301 KEYED CONSTRUCTION NOTES
1 CIRCUIT EMERGENCY EGRESS LIGHTS AND EXIT SIGNS FROM THE UNSWITCHED
LIGHTING BRANCH CIRCUIT SERVING THE SPACE IN WHICH IT IS INSTALLED FOR
POWER SENSING AND CHARGING. CIRCUIT WITH 2#12, 1#12GND, 3/4" EMT IN A
DEDICATED RACEWAY - NO OTHER BRANCH CIRCUITRY MAY BE PULLED IN THESE
RACEWAYS. TYPICAL FOR ALL EMERGENCY EGRESS LIGHTS AND EXIT SIGNS.
#
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
B00UB
B00UC
B11
B13
B13C
B13B
B13A
B04
B07
B02
B05
B00T
B03 B01
B14
B00SB
B00SA
B00UA
B09
PIT
CRAWL
SPACE
CRAWL
SPACE
B00C
UP
UP
UP
100TB
100SC
100SA
100SB
100JA
113
113A
114
108
112
109
101
110
103
100TA
103A
103B
102
102A
100CA 100CB
100JB
111
ENCLOSED PORCH
PORCH
PORCH
PATIO
114A
DN
UP
DN
DN
DN
DN
UP
DN
THRU WALL TO BELOW
FINISHED GRADE
(REFER TO DETAIL #2/E-400
FOR CONTINUATION)
METAL UNDERGROUND
WATER PIPE GROUND
ELECTRODE
PANEL MDP
GROUNDING
ELECTRODE
CONDUCTOR
GROUNDING
ELECTRODE
CONDUCTOR
1
2
3
2
4
7
7
8
8
TELCO
GROUND
BAR (TGB)
TELCO
GROUND
BAR (TGB)
7
TELCO
GROUND
BAR (TMGB)8' - 0"6' - 0"14' - 0"SUPPLEMENTAL GROUND ROD
ELECTRODES WITH TEST WELLS
THRU WALL TO
BASEMENT PANEL MDP
(REFER TO DETAIL #1/E-400
FOR CONTINUATION)
5
6UEUE
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseE-400
GROUNDING AND
BONDING PLANAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
0 4 8 16
SCALE: 1/8"=1'-0"
0 4 8 16
SCALE: 1/8"=1'-0"
SCALE: 1/8" = 1'-0"1 GROUNDING/BONDING PLAN - BASEMENT
SCALE: 1/8" = 1'-0"2 GROUNDING AND BONDING PLAN - FIRST FLOOR
E-400 KEYED CONSTRUCTION NOTES
1 PROVIDE A #2 CU BARE MAIN BONDING JUMPER IN PANEL MDP AND BOND THE
NEUTRAL BUS TO THE GROUND BUS.
2 PROVIDE A #2 CU BARE GROUNDING ELECTRODE CONDUCTOR (GEC) AS SHOWN.
INSTALL GEC CONTINUOUS WITH NO SPLICES. INSTALL IN 1" EMT RACEWAY
SECURELY FASTENED TO THE CEILING JOISTS.
3 BOND THE GEC TO THE EXISTING WATER MAIN. PROVIDE #2 CU BARE JUMPERS AS
NEEDED.
4 COREDRILL STONE FOUNDATION FOR GEC TO SUPPLEMENTAL GROUND RODS.
PROVIDE A 1" RGS NIPPLE AND MORTAR INTO FOUNDATION WALL. WEATHERSTOP
THE NIPPLE AFTER GEC INSTALLATION.
5 BURY GEC A MINIMUM OF 18" BELOW FINISHED GRADE. PROVIDE A METALLIC TAPE
12" BELOW FINISHED GRADE. RESTORE LAWN AND RESEED.
6 PROVIDE 3/4"x10' COPPER CLAD STEEL GROUND RODS WITH HDPE GROUND
ACCESS WELLS (WITH COVERS).
7 PROVIDE A COPPER GROUND BAR AND INSTALL 18" AFF. LABEL GROUND BAR AT
MDP 'TMGB'. LABEL GROUND BARS AT DATA ROOMS B03 AND B05 'TGB'.
8 PROVIDE A #2 CU BARE TELCO BONDING JUMPER AS SHOWN. INSTALL BONDING
JUMPER CONTINUOUS WITH NO SPLICES. INSTALL IN 1" EMT RACEWAY SECURELY
FASTENED TO THE CEILING JOISTS.
#
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
J
250A
125A 125A
J
PANEL LP-1
BASEMENT
SECOND FLOOR
HALL PANEL
THIRD FLOOR
HALL PANEL
BATHROOM
POWER PANEL
CLOSET
POWER PANEL
J
PANEL LP-3
PANEL SNO-MELT
60/2
PANEL LP-
4
100/2
PANEL LP-
5
BUS TAP BUS TAP
XFMR
37.5-KVA
PRI: 2.4kV
SEC: 240/120V
MDP
120/240V, 1-PHASE, 3-WIRE
400A RATED BUS
SPARE
J
PANEL LP-2
J60A SWITCH
(ROOM B07)
JB1
JB2
JB3
JB4
JB5
PANEL EM
BUS TAP
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
225A/2P
BASEMENT
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
XFMR
37.5-KVA
PRI: 2.4kV
SEC: 240/120V
MDP
120/240V, 1-PHASE, 3-WIRE
225A MCB
LLP-B1
120/240V
42 CIRCUIT
100A MCB
SURFACE
10K AIC
1Ø, 3-WIRE
100A/2P
LLP-B2
120/240V
42 CIRCUIT
100A MCB
SURFACE
10K AIC
1Ø, 3-WIRE
100A/2P
C C
LLP-B3
120/240V
42 CIRCUIT
60A MCB
SURFACE
10K AIC
1Ø, 3-WIRE
B
A
C
LLP-22
120/240V
42 CIRCUIT
100A MCB
SURFACE
10K AIC
1Ø, 3-WIRE
B
LLP-23
120/240V
42 CIRCUIT
60A MCB
SURFACE
10K AIC
1Ø, 3-WIRE
LLP-31
120/240V
42 CIRCUIT
60A MCB
SURFACE
10K AIC
1Ø, 3-WIRE
B
60A/2P 100A/2P 60A/2P
B
LLP-21
120/240V
42 CIRCUIT
60A MCB
SURFACE
10K AIC
1Ø, 3-WIRE
60A/2P
JUNCTION
BOX J-1
(12"x12"x6")
JUNCTION
BOX J-2
12"X12"X6")
SP-2
30A/2P
SURGE PROTECTION
AT MDP SIMILAR TO
VERTIV/ASCO MODEL 440
TYPE 1 WITH STEEL
ENCLOSURE (SP-1)
SURGE PROTECTION
AT PANELS SIMILAR TO
VERTIV/ASCO MODEL 425
TYPE 2 (TYPICAL FOR SP-2)
D
E E E
E E E
SP-2 SP-2
SP-2 SP-2 SP-2
SP-1
TEMPORARY MDP FEED:
PROVIDE A 225A/2P SERVICE ENTRANCE CIRCUIT BREAKER RATED FOR
10K AIC IN A NEMA 1 ENCLOSURE. PROVIDE TEMPORARY FEEDER TYPE 'A'
FROM EXISTING MDP. MAINTAIN THE EXISTING MDP UNTIL NEW MDP AND
ALL PANELBOARDS ARE REPLACED AND ALL BUILDING LOADS HAVE BEEN
REFED FROM NEW PANELBOARDS. AFTER CONSTRUCTION, DISCONNECT
AND REMOVE THE ENCLOSED CIRCUIT BREAKER AND PROVIDE THE
PERMANENT FEEDER TYPE 'A'.
M
INSTALL NEW METER SOCKET
FURNISHED BY CORNELL
M
MAINTAIN EXISTING POWERSCOUT
REVENUE ELECTRIC METER - REWORK
CT'S ONCE NEW MDP IS INSTALLED
AND SWITCHOVER IS COMPLETE
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseE-500
ONE-LINE
DIAGRAMSAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
SCALE:NO SCALE1DEMOLITION ONE-LINE DIAGRAM
FEEDER SCHEDULE
TYPE PHASE NEUTRAL GROUND RACEWAY NOTES
A 2#4/0 1#4/0 1#2 2" EMT
B 2#6 1#6 1#10 1" EMT
C 2#2 1#2 1#8 1.25" EMT
D 2#10 1#10 1#10 3/4" EMT TWIST CONDUCTORS TOGETHER TO REDUCE IMPEDANCE PER MANUF.;
KEEP CONDUCTORS LESS THAN 24" IN LENGTH
E 2#12 1#12 1#12 3/4" EMT TWIST CONDUCTORS TOGETHER TO REDUCE IMPEDANCE PER MANUF.;
KEEP CONDUCTORS LESS THAN 24" IN LENGTH
SCALE:NO SCALE2POWER RISER DIAGRAM
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseE-501
PANELBOARD
SCHEDULESAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
FIRE ALARM 700 VA 100.00% 700 VA
APPLIANCE 17940 VA 35.00% 6279 VA TOTAL DEMAND AMPS:174 A
ELECTRIC HEAT 17280 VA 35.00% 6048 VA TOTAL CONN AMPS:490 A
RECEPTACLES 40420 VA 35.00% 14147 VA TOTAL DEMAND:41651 VA
LIGHTING 17922 VA 35.00% 6273 VA TOTAL CONN LOAD:117702 VA
HVAC 23440 VA 35.00% 8204 VA
LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS
TOTAL AMPS:511 A 470 A
TOTAL LOAD:61354 VA 56348 VA
41 ---- -- 0 0 VA -- -- SPACE 42
39 SURGE PROTECTION DEVICE 30 2 0 VA 0 VA -- -- SPACE 40
37 SPACE -- -- 0 0 VA -- -- SPACE 38
35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36
33 SPACE -- -- 0 0 VA -- -- SPACE 34
31 SPACE -- -- 0 VA 0 VA -- -- SPACE 32
29 SPACE -- -- 0 0 VA -- -- SPACE 30
27 ---- -- 0 VA 0 VA -- -- --28
25 SPARE 20 2 0 0 VA 2 20 SPARE 26
23 ---- -- 0 VA 0 VA -- -- --24
21 SPARE 30 2 0 0 VA 2 30 SPARE 22
19 ---- -- 0 VA 0 VA -- -- --20
17 SPARE 40 2 0 0 VA 2 40 SPARE 18
15 ---- -- 0 VA 0 VA -- -- --16
13 SPARE 60 2 0 0 VA 2 60 SPARE 14
11 ---- -- 16180... 14872... -- -- --12
9 LLP-B1 60 2 13965 18826... 2 100 LLP-B2 10
7 ---- -- 7528 VA 11520... -- -- --8
5 LLP-21 60 2 10814 11556... 2 100 LLP-22 6
3 ---- -- 2930 VA 3318 VA -- -- --4
1 LLP-B3 60 2 3077 3116 VA 2 60 LLP-23 2
CKT DESCRIPTION TRIP POLES
A B
POLES TRIP DESCRIPTION CKT
ENCLOSURE:TYPE 1 OPTIONS:SERVICE ENTRANCE RATED
MOUNTING:SURFACE WIRES:3 MAINS RATING:225 A
FED FROM:PHASE:1 MAINS TYPE:MCB
LOCATION:B11 VOLTS:120/240V AIC RATING:10K
PANEL MDP
FIRE ALARM 350 VA 100.00% 350 VA TOTAL DEMAND AMPS:50 A
APPLIANCE 16500 VA 35.00% 5775 VA TOTAL CONN AMPS:140 A
RECEPTACLES 4600 VA 35.00% 1610 VA TOTAL DEMAND:12022 VA
LIGHTING 4348 VA 35.00% 1522 VA TOTAL CONN LOAD:33698 VA
HVAC 7900 VA 35.00% 2765 VA
LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS
TOTAL AMPS:157 A 124 A
TOTAL LOAD:18826 VA 14872 VA
41 SPARE 20 1 0 0 VA -- -- --42
39 ---- -- 0 VA 0 VA 2 20 SURGE PROTECTION DEVICE 40
37 SUMP PUMP SP-1 20 2 1700 0 VA 1 20 SPARE 38
35 SPARE 20 1 0 VA 0 VA 1 20 SPARE 36
33 RCPT: 102 (FRIDGE) 20 1 1400 0 VA 1 20 SPARE 34
31 SPARE 20 1 0 VA 0 VA 1 20 SPARE 32
29 FCU-B6, B7 20 1 1200 0 VA 1 20 SPARE 30
27 RCPT: 102 (MICROWAVE) 20 1 1400 VA 0 VA -- -- --28
25 DISPOSAL 20 1 900 0 VA 2 20 SPARE 26
23 RCPTS: BASEMENT 20 1 900 VA 1200 VA 1 20 LTG: 2ND FLOOR 24
21 RCPTS: 102 (COUNTER) 20 1 720 700 VA 1 20 EF-B00UC 22
19 RCPTS: 102 (COUNTER) 20 1 360 VA 900 VA 1 20 RCPTS: 110 20
17 ---- -- 0 50 VA 1 20 WIRELESS LTG GATEWAY 18
15 RCPT: 102 (RANGE) 50 2 8300 VA 180 VA 1 20 RCPT: 110 (A/C) 16
13 RCPT: 110 (A/C) 20 1 180 360 VA 1 20 RCPTS: 102 (COUNTER) 14
11 ---- -- 0 VA 0 VA -- -- --12
9 CONN: B00UC (CP-1) 20 2 2000 4500 VA 2 25 WH-1 10
7 RCPTS: 102 20 1 360 VA 600 VA 1 20 FCU-B5 8
5 LTG: 2ND FLOOR 20 1 1328 1448 VA 1 20 LTG: 2ND FLOOR 6
3 LTG: BASEMENT 20 1 322 VA 350 VA 1 20 FACP (LOCKING HANDLE) 4
1 CONN: B02 (IRRIGATION PANEL) 20 1 100 540 VA 1 20 RCPTS: 101,112 2
CKT DESCRIPTION TRIP POLES
A B
POLES TRIP DESCRIPTION CKT
ENCLOSURE:TYPE 1 OPTIONS:
MOUNTING:SURFACE WIRES:3 MAINS RATING:100 A
FED FROM:MDP PHASE:1 MAINS TYPE:MCB
LOCATION:B00C VOLTS:120/240V AIC RATING:10K
PANEL LLP-B2
TOTAL DEMAND AMPS:9 A
TOTAL CONN AMPS:25 A
TOTAL DEMAND:2102 VA
RECEPTACLES 5040 VA 35.00% 1764 VA TOTAL CONN LOAD:6007 VA
LIGHTING 967 VA 35.00% 338 VA
LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS
TOTAL AMPS:26 A 24 A
TOTAL LOAD:3077 VA 2930 VA
41 SPARE 20 1 0 0 VA -- -- --42
39 SPARE 20 1 0 VA 0 VA 2 20 SURGE PROTECTION DEVICE 40
37 SPARE 20 1 0 0 VA 1 20 SPARE 38
35 SPARE 20 1 0 VA 0 VA 1 20 SPARE 36
33 SPARE 20 1 0 0 VA 1 20 SPARE 34
31 SPARE 20 1 0 VA 0 VA 1 20 SPARE 32
29 SPARE 20 1 0 0 VA 1 20 SPARE 30
27 SPARE 20 1 0 VA 0 VA 1 20 SPARE 28
25 SPARE 20 1 0 0 VA 1 20 SPARE 26
23 SPARE 20 1 0 VA 0 VA 1 20 SPARE 24
21 SPARE 20 1 0 0 VA 1 20 SPARE 22
19 SPARE 20 1 0 VA 0 VA 1 20 SPARE 20
17 ---- -- 0 0 VA 1 20 SPARE 18
15 SPARE 20 2 0 VA 0 VA 1 20 SPARE 16
13 RCPTS: B05 20 1 360 0 VA 1 20 SPARE 14
11 RCPTS: B05 20 1 360 VA 0 VA -- -- --12
9 RCPTS: 103 (AFCI) 20 1 1080 0 VA 2 20 SPARE 10
7 RCPTS: 103A (AFCI) 20 1 1080 VA 50 VA 1 20 WIRELESS LTG GATEWAY 8
5 RCPTS: B03 20 1 360 800 VA 1 20 LTG: 2ND FLOOR 6
3 RCPTS: 103B (AFCI) 20 1 720 VA 720 VA 1 20 RCPTS: BASEMENT 4
1 LTG: BASEMENT 20 1 117 360 VA 1 20 RCPTS: 100TA/103 (AFCI) 2
CKT DESCRIPTION TRIP POLES
A B
POLES TRIP DESCRIPTION CKT
ENCLOSURE:TYPE 1 OPTIONS:AFCI BREAKERS
MOUNTING:SURFACE WIRES:3 MAINS RATING:60 A
FED FROM:MDP PHASE:1 MAINS TYPE:MCB
LOCATION:B00SB VOLTS:120/240V AIC RATING:10K
PANEL LLP-B3
TOTAL DEMAND AMPS:27 A
TOTAL CONN AMPS:76 A
RECEPTACLES 10080 VA 35.00% 3528 VA TOTAL DEMAND:6420 VA
LIGHTING 4062 VA 35.00% 1422 VA TOTAL CONN LOAD:18342 VA
HVAC 4200 VA 35.00% 1470 VA
LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS
TOTAL AMPS:90 A 63 A
TOTAL LOAD:10814 VA 7528 VA
41 SPARE 20 1 0 0 VA -- -- --42
39 SPARE 20 1 0 VA 0 VA 2 20 SURGE PROTECTION DEVICE 40
37 SPARE 20 1 0 0 VA 1 20 SPARE 38
35 SPARE 20 1 0 VA 0 VA 1 20 SPARE 36
33 SPARE 20 1 0 0 VA 1 20 SPARE 34
31 SPARE 20 1 0 VA 0 VA 1 20 SPARE 32
29 SPARE 20 1 0 0 VA 1 20 SPARE 30
27 SPARE 20 1 0 VA 0 VA 1 20 SPARE 28
25 SPARE 20 1 0 0 VA 1 20 SPARE 26
23 SPARE 20 1 0 VA 0 VA 1 20 SPARE 24
21 SPARE 20 1 0 0 VA -- -- --22
19 ---- -- 0 VA 0 VA 2 20 SPARE 20
17 SPARE 20 2 0 1620 VA 1 20 RCPTS: 213 18
15 RCPTS: 217 20 1 1440 VA 0 VA 1 20 SPARE 16
13 WIRELESS LTG GATEWAY 20 1 50 1440 VA 1 20 RCPTS: 201 14
11 CUH'S (220/223) 20 1 1200 VA 1260 VA 1 20 RCPTS: 223 12
9 CUH'S (215/217) 20 1 1200 1260 VA 1 20 RCPTS: 214 10
7 LTG: 200CA 20 1 928 VA 1200 VA 1 20 CUH'S (213/214) 8
5 RCPTS: 215 20 1 1080 1224 VA 1 20 LTG: 2ND FLOOR 6
3 CUH (201) 20 1 600 VA 900 VA 1 20 LTG: 2ND FLOOR 4
1 RCPTS: 200CA/SC 20 1 360 960 VA 1 20 LTG: 2ND FLOOR 2
CKT DESCRIPTION TRIP POLES
A B
POLES TRIP DESCRIPTION CKT
ENCLOSURE:TYPE 1 OPTIONS:
MOUNTING:SURFACE WIRES:3 MAINS RATING:60 A
FED FROM:MDP PHASE:1 MAINS TYPE:MCB
LOCATION:200SC VOLTS:120/240V AIC RATING:10K
PANEL LLP-21
TOTAL DEMAND AMPS:7 A
TOTAL CONN AMPS:19 A
RECEPTACLES 3420 VA 35.00% 1197 VA TOTAL DEMAND:1617 VA
LIGHTING 0 VA 0.00% 0 VA TOTAL CONN LOAD:4620 VA
HVAC 1200 VA 35.00% 420 VA
LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS
TOTAL AMPS:19 A 20 A
TOTAL LOAD:2280 VA 2340 VA
41 SPARE 20 1 0 0 VA -- -- --42
39 SPARE 20 1 0 VA 0 VA 2 20 SURGE PROTECTION DEVICE 40
37 SPARE 20 1 0 0 VA 1 20 SPARE 38
35 SPARE 20 1 0 VA 0 VA 1 20 SPARE 36
33 SPARE 20 1 0 0 VA 1 20 SPARE 34
31 SPARE 20 1 0 VA 0 VA 1 20 SPARE 32
29 SPARE 20 1 0 0 VA 1 20 SPARE 30
27 SPARE 20 1 0 VA 0 VA 1 20 SPARE 28
25 SPARE 20 1 0 0 VA 1 20 SPARE 26
23 SPARE 20 1 0 VA 0 VA 1 20 SPARE 24
21 SPARE 20 1 0 0 VA 1 20 SPARE 22
19 SPARE 20 1 0 VA 0 VA 1 20 SPARE 20
17 SPARE 20 1 0 0 VA 1 20 SPARE 18
15 SPARE 20 1 0 VA 0 VA 1 20 SPARE 16
13 SPARE 20 1 0 0 VA 1 20 SPARE 14
11 SPARE 20 1 0 VA 0 VA 1 20 SPARE 12
9 ---- -- 0 0 VA -- -- --10
7 SPARE 20 2 0 VA 0 VA 2 20 SPARE 8
5 RCPTS: 200J/200TD/200TA 20 1 540 1200 VA 1 20 CUH'S (211/212) 6
3 RCPTS: 212 20 1 900 VA 1440 VA 1 20 RCPTS: 211 4
1 RCPT: 200SA 20 1 180 360 VA 1 20 RCPT: 210 2
CKT DESCRIPTION TRIP POLES
A B
POLES TRIP DESCRIPTION CKT
ENCLOSURE:TYPE 1 OPTIONS:SUB-FEED LUGS
MOUNTING:SURFACE WIRES:3 MAINS RATING:100 A
FED FROM:MDP PHASE:1 MAINS TYPE:MCB
LOCATION:200TA VOLTS:120/240V AIC RATING:10K
PANEL LLP-22
TOTAL DEMAND AMPS:44 A
ELECTRIC HEAT 17280 VA 35.00% 6048 VA TOTAL CONN AMPS:126 A
RECEPTACLES 5940 VA 35.00% 2079 VA TOTAL DEMAND:10551 VA
LIGHTING 2185 VA 35.00% 765 VA TOTAL CONN LOAD:30145 VA
HVAC 4740 VA 35.00% 1659 VA
LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS
TOTAL AMPS:116 A 135 A
TOTAL LOAD:13965 VA 16180 VA
41 SPARE 20 1 0 0 VA -- -- --42
39 SPARE 20 1 0 VA 0 VA 2 20 SURGE PROTECTION DEVICE 40
37 SPARE 20 1 0 0 VA 1 20 SPARE 38
35 SPARE 20 1 0 VA 0 VA 1 20 SPARE 36
33 SPARE 20 1 0 0 VA 1 20 SPARE 34
31 SPARE 20 1 0 VA 0 VA -- -- --32
29 SPARE 20 1 0 5760 VA 2 30 SNO-MELT 30
27 SPARE 20 1 0 VA 0 VA 1 20 SPARE 28
25 ---- -- 0 1200 VA 1 20 FCU-B1, B2 26
23 SPARE 20 2 0 VA 0 VA 1 20 SPARE 24
21 ---- -- 0 720 VA 1 20 RCPTS: 113 22
19 SNO-MELT 30 2 5760 VA 0 VA 1 20 SPARE 20
17 RCPT: 108 20 1 360 540 VA 1 20 RCPTS: 108 (WEST) 18
15 TIMECLOCK TC-1 (MASTER) 20 1 50 VA 1740 VA 1 20 PUMP CONTROL PANEL 16
13 LTG: 1ST FLOOR 20 1 1800 0 VA -- -- --14
11 WIRELESS LTG GATEWAY 20 1 50 VA 5760 VA 2 30 SNO-MELT 12
9 RCPTS: 109 20 1 900 1260 VA 1 20 RCPTS: BASEMENT 10
7 RCPTS: 114 20 1 720 VA 1200 VA 1 20 FCU-B3, B4 8
5 RCPT: 108 20 1 360 600 VA 1 20 CUH (1ST FLOOR STAIRS) 6
3 RCPTS: 108 (EAST) 20 1 360 VA 540 VA 1 20 RCPTS: BASEMENT 4
1 RCPT: EXTERIOR 20 1 180 285 VA 1 20 LTG: BASEMENT 2
CKT DESCRIPTION TRIP POLES
A B
POLES TRIP DESCRIPTION CKT
ENCLOSURE:TYPE 1 OPTIONS:
MOUNTING:SURFACE WIRES:3 MAINS RATING:100 A
FED FROM:MDP PHASE:1 MAINS TYPE:MCB
LOCATION:B11 VOLTS:120/240V AIC RATING:10K
PANEL LLP-B1
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseE-502
PANELBOARD
SCHEDULESAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
TOTAL DEMAND AMPS:27 A
APPLIANCE 1440 VA 35.00% 504 VA TOTAL CONN AMPS:77 A
RECEPTACLES 8820 VA 35.00% 3087 VA TOTAL DEMAND:6460 VA
LIGHTING 3396 VA 35.00% 1189 VA TOTAL CONN LOAD:18456 VA
HVAC 4800 VA 35.00% 1680 VA
LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS
TOTAL AMPS:77 A 77 A
TOTAL LOAD:9276 VA 9180 VA
41 SPARE 20 1 0 0 VA 1 20 SPARE 42
39 SPARE 20 1 0 VA 0 VA 1 20 SPARE 40
37 SPARE 20 1 0 0 VA 1 20 SPARE 38
35 SPARE 20 1 0 VA 0 VA 1 20 SPARE 36
33 SPARE 20 1 0 0 VA 1 20 SPARE 34
31 SPARE 20 1 0 VA 0 VA 1 20 SPARE 32
29 SPARE 20 1 0 0 VA 1 20 SPARE 30
27 SPARE 20 1 0 VA 0 VA 1 20 SPARE 28
25 SPARE 20 1 0 0 VA 1 20 SPARE 26
23 SPARE 20 1 0 VA 0 VA 1 20 SPARE 24
21 SPARE 20 1 0 0 VA -- -- --22
19 ---- -- 0 VA 0 VA 2 20 SPARE 20
17 SPARE 20 2 0 1440 VA 1 20 LTG: 3RD FLOOR 18
15 RCPTS: 310 20 1 1260 VA 0 VA 1 20 SPARE 16
13 WIRELESS LTG GATEWAY 20 1 50 1260 VA 1 20 RCPTS: 307 14
11 RCPTS: 309 20 1 1080 VA 1200 VA 1 20 CUH'S (307/308) 12
9 RCPTS: 308 20 1 1080 1200 VA 1 20 CUH'S (302/304) 10
7 RCPTS: 302 20 1 900 VA 1980 VA 1 20 RCPTS: 301 8
5 CUH'S (301/310) 20 1 1200 2096 VA 1 20 LTG: 3RD FLOOR 6
3 CUH (309) 20 1 600 VA 720 VA 1 20 RCPTS: ATTIC 4
1 LTG: 300CA/CB, STAIRS 20 1 410 540 VA 1 20 RCPTS: 304 2
CKT DESCRIPTION TRIP POLES
A B
POLES TRIP DESCRIPTION CKT
ENCLOSURE:TYPE 1 OPTIONS:OVERSIZE TRIM
MOUNTING:FLUSH WIRES:3 MAINS RATING:60 A
FED FROM:MDP PHASE:1 MAINS TYPE:MCB
LOCATION:300CB VOLTS:120/240V AIC RATING:10K
PANEL LLP-31
TOTAL DEMAND AMPS:10 A
FIRE ALARM 350 VA 100.00% 350 VA TOTAL CONN AMPS:27 A
RECEPTACLES 2520 VA 35.00% 882 VA TOTAL DEMAND:2479 VA
LIGHTING 2964 VA 35.00% 1037 VA TOTAL CONN LOAD:6434 VA
HVAC 600 VA 35.00% 210 VA
LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS
TOTAL AMPS:26 A 28 A
TOTAL LOAD:3116 VA 3318 VA
41 SPARE 20 1 0 0 VA -- -- --42
39 SPARE 20 1 0 VA 0 VA 2 20 SURGE PROTECTION DEVICE 40
37 SPARE 20 1 0 0 VA 1 20 SPARE 38
35 SPARE 20 1 0 VA 0 VA 1 20 SPARE 36
33 SPARE 20 1 0 0 VA 1 20 SPARE 34
31 SPARE 20 1 0 VA 0 VA 1 20 SPARE 32
29 SPARE 20 1 0 0 VA 1 20 SPARE 30
27 SPARE 20 1 0 VA 0 VA 1 20 SPARE 28
25 SPARE 20 1 0 0 VA 1 20 SPARE 26
23 SPARE 20 1 0 VA 0 VA 1 20 SPARE 24
21 SPARE 20 1 0 0 VA 1 20 SPARE 22
19 SPARE 20 1 0 VA 0 VA 1 20 SPARE 20
17 SPARE 20 1 0 0 VA 1 20 SPARE 18
15 SPARE 20 1 0 VA 0 VA 1 20 SPARE 16
13 SPARE 20 1 0 0 VA 1 20 SPARE 14
11 ---- -- 0 VA 0 VA -- -- --12
9 SPARE 20 2 0 0 VA 2 20 SPARE 10
7 LTG: 2ND FLOOR 20 1 1348 VA 350 VA 1 20 WIRELESS LTG GATEWAY 8
5 RCPTS: 207 20 1 900 1160 VA 1 20 LTG: 2ND FLOOR 6
3 RCPTS: 204 20 1 540 VA 1080 VA 1 20 RCPTS: 208 4
1 LTG: 200J 20 1 456 600 VA 1 20 CUH (200SE) 2
CKT DESCRIPTION TRIP POLES
A B
POLES TRIP DESCRIPTION CKT
ENCLOSURE:TYPE 1 OPTIONS:OVERSIZE TRIM
MOUNTING:FLUSH WIRES:3 MAINS RATING:60 A
FED FROM:MDP PHASE:1 MAINS TYPE:MCB
LOCATION:200SE VOLTS:120/240V AIC RATING:10K
PANEL LLP-23
(VIA LLP-22)REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseE-503
EQUIPMENT
CONNECTION AND
LUMINAIRE
SCHEDULESAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING SIZE MANUFACTURER CATALOG NO. VOLTAGE LAMPS WATTAGE FINISH NOTES
1 WALL SCONCE - REPRODUCTION WALL CUSTOM HOUSE OF ANTIQUE HARDWARE LEXINGTON SINGLE GLASS SCONCE WITH
VIANNE SATIN ETCHED GAS LIGHT SHADE
120 LED 60 ANTIQUE BRASS PROVIDE WITH VINTAGE
UNFROSTED LED LAMPS
X1 SINGLE FACE EXIT SIGN UNIVERSAL 12"x8"x2.25" LITHONIA LQM-S-W-1-R-120/277-SD 120/277 LED .62 WHITE
X2 DOUBLE FACE EXIT SIGN UNIVERSAL 12"x8"x2.25" LITHONIA LQM-S-W-2-R-120/277-SD 120/277 LED 1.24 WHITE
X3 COMBO EM UNIT / EXIT SIGN WALL 19.25"x8"x2.25" LITHONIA LHQM-LED-R-HO-SD 120/277 LED 4.3 WHITE
X4 EM LIGHTING BATTERY UNIT EALL 10.25"x4.25"x3.5" LITHONIA ELM2-LED-SD 120/277 LED 1.44 WHITE
X5 TWIN REMOTE HEADS WALL 8.25"x5.75" LITHONIA ELA-B-T-QWP-L0309-SD - LED - BLACK
EQUIPMENT CONNECTION SCHEDULE
LABEL DESCRIPTION
ROOM
NO.PANEL
RATING (kW,
W, VA, A, HP)VOLTAGE PHASE WIRE & CONDUIT
STARTER DISCONNECT
NOTES ADDITIONAL REQUIREMENTSTYPE LOC BY ENC AUX BY RATING LOC ENC
FCU-B1 FAN COIL UNIT B00UB SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 C - - - - 1
FCU-B2 FAN COIL UNIT B04 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 C - - - - 1
FCU-B3 FAN COIL UNIT B04 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 C - - - - 1
FCU-B4 FAN COIL UNIT B07 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 C - - - - 1
FCU-B5 FAN COIL UNIT B02 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 C - - - - 1
FCU-B6 FAN COIL UNIT B00UC SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 C - - - - 1
FCU-B7 FAN COIL UNIT B00UC SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 C - - - - 1
NOT USED
NOT USED
CUH-1 CABINET UNIT HEATER STAIRS SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-2 CABINET UNIT HEATER 201 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-3 CABINET UNIT HEATER 211 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-4 CABINET UNIT HEATER 212 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-5 CABINET UNIT HEATER 213 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-6 CABINET UNIT HEATER 214 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-7 CABINET UNIT HEATER 215 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-8 CABINET UNIT HEATER 217 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-9 CABINET UNIT HEATER 220 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-10 CABINET UNIT HEATER 223 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-11 CABINET UNIT HEATER 301 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-12 CABINET UNIT HEATER 302 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-13 CABINET UNIT HEATER 304 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-14 CABINET UNIT HEATER 307 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-15 CABINET UNIT HEATER 308 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-16 CABINET UNIT HEATER 309 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-17 CABINET UNIT HEATER 310 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
CUH-18 CABINET UNIT HEATER 200SE SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER
NOT USED
SM-1 SNO-MELT SYSTEM B04 SEE DWGS 6-kW 240 1 2#10, 1#10GND, 3/4" C. - - - - - EC 30A B04 1 1
SM-2 SNO-MELT SYSTEM B04 SEE DWGS 6-kW 240 1 2#10, 1#10GND, 3/4" C. - - - - - EC 30A B04 1 1
SM-3 SNO-MELT SYSTEM B04 SEE DWGS 6-kW 240 1 2#10, 1#10GND, 3/4" C. - - - - - EC 30A B04 1 1
NOT USED
NOT USED
FACP FIRE ALARM CONTROL PANEL B00SA SEE DWGS 350-W 120 1 2#12, 1#12GND, 3/4" C. - - - - - - - - - 1
NOT USED
NOT USED
SP-1 SUMP PUMP B02 SEE DWGS 3/4-HP 240 1 2#12, 1#12GND, 3/4" C. - - - - - EC 30A UNIT 1 1
SP-2 SUMP PUMP B00UC SEE DWGS 3/4-HP 240 1 2#12, 1#12GND, 3/4" C. - - - - - EC 30A UNIT 1 1
NOT USED 30A
NOT USED
WH-1 ELECTRIC WATER HEATER B02 SEE DWGS 4.5-kW 240 1 2#10, 1#10GND, 3/4" C. - - - - - EC 30A UNIT 1 1
NOT USED
NOT USED
CP-1 CIRCULATION PUMP B00UC SEE DWGS 1.0-HP 240 1 2#12, 1#12GND, 3/4" C. - - - - - EC 30A UNIT 1 1
NOT USED
NOT USED
IR-1 IRRIGATION CONTROL PANEL B00UC SEE DWGS 100-W 120 1 2#12, 1#12GND, 3/4" C. - - - - - - - - - 1
NOT USED
NOT USED
EF-1 EXHAUST FAN 300T SEE DWGS 500-W 120 1 2#12, 1#12GND, 3/4" C. MANUAL 300T EC 1 - - - - 1 PROVIDE MOTOR RATED SWITCH
NOT USED
NOT USED
RNG-1 ELECTRIC RANGE 102 SEE DWGS 50-A 240 1 2#8, 1#10GND, 1" C. - - - - - - - - - - PROVIDE NEMA 14-50R TWISTLOCK RECEPTACLE
NOT USED
NOT USED
PUMP CP PUMP CONTROL PANEL B04 SEE DWGS 14.5-MCA 120 1 2#12, 1#12GND, 3/4" C. - - - - - EC 30A B04 1 1
NOT USED
NOT USED
EF-B00UC EXHAUST FAN B00UC SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL B00UC EC 1 - - - - - 1 FAN LOCATED ON ROOF
NOT USED
NOT USED
NOTES:
1. MAKE CONNECTION TO EQUIPMENT.A. START-STOP IN COVER.
2. INSTALL MOTOR STARTER FURNISHED BY OTHERS.B. HAND-OFF-AUTO IN COVER.
3. MAKE CONNECTIONS TO CONTROLS.C. PILOT LIGHT IN COVER.
4. FIELD CONTROL WIRING BY OTHERS.D. AUXILIARY CONTACTS.
5. RUN FEED THRU CONTACTOR. CONTROL FROM FAN SHUTDOWN RELAY. E. CONTROL CIRCUIT TRANSFORMER.
6. PROVIDE DUCT SMOKE DETECTOR.F. TWO-SPEED MOTOR CONTROLLER.
7. PROVIDE GFI RECEPTACLE AT UNIT. CIRCUIT TO NEAREST 120V CIRCUIT. G. KEY OPERATED - UP/DOWN OR OPEN/CLOSE.
8. WIRE THRU T-STAT THEN TO MOTOR.
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
NOTES:
1.FLOOR/CEILING ASSEMBLY:
A. FLOORING SYSTEM: 5/8” HARDWOOD.
B. WOOD JOIST: 2”x10” LUMBER JOIST.
C. CEILING: PLASTER.
2.CONDUIT:
A. CONDUIT: 4” DIAMETER OR SMALLER EMT
3.FORMING AND FIRESTOP MATERIALS:
A. FORMING MATERIAL: FOAM BACKER ROD PACKED INTO OPENING AS A PERMANENT FORM.
B. TYPE 1A: MINIMUM ½” THICK SEALANT APPLIED WITHIN THE ANNULUS FLUSH WITH THE TOP
OF THE FLOOR AND BOTTOM OF THE CEILING ASSEMBLIES. ADDITIONAL SEALANT TO BE APPLIED
SUCH THAT A MINIMUM OF ½” CROWN IS FORMED AROUND THE PENETRATING ITEM.
2
A
SECTION A-A
3B
A
3B
1B
1A3B
2
3B
1C
3A
3A
WIRELESS
REMOTE
SWITCH
WIRELESS
MOTION
SENSOR
(WALL)
LIGHT FIXTURE
AC LINE IN
WIRELESS LUMINAIRE
CONTROLLER (5A MAX)
HOT
NEUT
CAT 6 DATA GATEWAY
GW1100 FIXTURE
BALLAST/DRIVER
120/277
120 VAC
58-PS-24V-T
POWER SUPPLY
24 VDC
WIRELESS
MOTION
SENSOR
(CEILING)
DIGITAL
TIMECLOCK
TC-1 (MASTER)
100CA
EXTERIOR
LUMINAIRE
DIGITAL
TIMECLOCK
TC-2 (REMOTE)
103
EXTERIOR
LUMINAIRE
120VAC -
CAT6 DATA CABLE
IN 3/4" EMT TO
EXISTING PATCH
PANEL IN B03
-
PC
EXISTING LUMINAIRE
(TYPICAL)
ELEC B11
MECH BOOUC
(2) #14 AWG, 3/4" C.
120VAC BRANCH
CIRCUITRY (TYPICAL)
SEQUENCE OF OPERATION:
1. 100CA EXTERIOR LUMINAIRE: FIXTURE SHALL OPERATE ON PHOTOCELL
CONTROL WITH NO MANUAL OVERRIDE. PROGRAM TO OPERATE FROM
DUSK TO DAWN.
2.102 EXTERIOR LUMINAIRE: FIXTURE SHALL OPERATE ON PHOTOCELL
CONTROL WITH A DIGITAL SWITCH TO OVERRIDE. PROGRAM TO OPERATE
ON MANUAL OVERRIDE ONLY. PROGRAM PHOTOCELL/TIMECLOCK TO
SHUT FIXTURE OFF DURING DAYLIGHT.
3.103 EXTERIOR LUMINAIRE: FIXTURE SHALL OPERATE ON PHOTOCELL
CONTROL WITH A DIGITAL SWITCH TO OVERRIDE. PROGRAM TO OPERATE
ON MANUAL OVERRIDE ONLY. PROGRAM PHOTOCELL/TIMECLOCK TO
SHUT FIXTURE OFF DURING DAYLIGHT.
4.113 EXTERIOR LUMINAIRE: FIXTURE SHALL OPERATE ON PHOTOCELL
CONTROL WITH A DIGITAL SWITCH TO OVERRIDE. PROGRAM TO OPERATE
ON MANUAL OVERRIDE ONLY. PROGRAM PHOTOCELL/TIMECLOCK TO
SHUT FIXTURE OFF DURING DAYLIGHT.
GENERAL INSTALLATION NOTES:
5.INSTALL UNSWITCHED BRANCH CIRCUIT FROM RESPECTIVE LIGHTING
BRANCH CIRCUIT TO EACH LUMINAIRE VIA THE RELAY ON THE SPECIFIED
TIMECLOCK. REFER TO PLANS FOR BRANCH CIRCUIT/PANEL INFORMATION.
6.PROVIDE CAT6 DATA CABLING BETWEEN TIMECLOCKS AND BETWEEN
TIMECLOCKS AND DIGITAL SWITCHES.
7.PROVIDE 120VAC BRANCH CIRCUIT TO EACH TIMECLOCK.
8.PROVIDE ALL PROGRAMMING.
9.PROVIDE DIGITAL SWITCHES WITH A FLUSH, SINGLE-GANG BOX. CONCEAL
DATA CABLING IN WALLS, FLOORS, AND CEILINGS.
R1
102
EXTERIOR
LUMINAIRE
R3
113
EXTERIOR
LUMINAIRE
R5
R7
R2
R4
R6
R8
R1
R3
R7
R2
R4
R6
R8
CAT6 DATA CABLE
IN 3/4" EMT
KITCHEN
102
APARTMENT
103
OFFICE
113CAT6 DATA CABLE
IN 3/4" EMT
120VAC -
R5
DIGITAL SWITCH
(TYPICAL)
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseE-504
DETAILSAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
SCALE:NO SCALE11-HOUR FIRE RATED FLOOR PENETRATION
SCALE:NO SCALE2WIRELESS LIGHTING CONTROL SCHEMATIC
SCALE:NO SCALE3EXTERIOR LIGHTING CONTROL RISER
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
B00UB
B00UC
B11
B13
B13C
B13B
B13A
B04
B07
B02
B05
B00T
B03 B01
B14
B00SB
B00SA
B00UA
B09
PIT
CRAWL
SPACE
CRAWL
SPACE
B00C
UP
UP
UP
110
100C
109
108
113
113A
114
100TB
112
101
102
103
100JA
100JB
DN
UP
DN
DN
DN
DN
UP
DN
FEEDER UP TO
SECOND FLOOR
BATHROOM POWER
PANEL
PANEL LP-4
JB2
JB1
JB4
JB3
JB5
PANEL LP-3
PANEL SNO-MELT
PANEL LP-2
PANEL LP-1
MDP
PANEL EM
PANEL LP-5
JB6
JB7
60A DISCONNECT
FEEDER UP TO
SECOND FLOOR
HALL POWER PANEL
FEEDER UP TO
SECOND FLOOR
CLOSET POWER
PANEL
EXISTING 2.4KV/120/240V
TRANSFORMER (TO REMAIN)
EXISTING 2.4KV SWITCH
(TO REMAIN)
FCU-B1
FCU-B2
FCU-B4
FCU-B5
SP-1
FCU-B6
FCU-B7
FCU-B3
CP-1
SP-2
WH-1
IR-1
FACP
ED-1021
1
1
1
1
1
1
2
TYP
3
TYP
4
TYP
5
TYP
PUMP CP
9
10
20
21
PM PM
PM
CUH-1
RNG-1
J
J J
J
6
TYP
7
3
TYP
2
TYP
5
8
8
8
8
11
12
12
12
13
13
13
14 14
15
16
17
17
18
18
18
(2) SWITCHES CONTROL
A/C UNIT POWER, REMAINING
SWITCH CONTROLS PORCH LIGHTS
AC AC
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseED-100
DEMOLITION
PLANS -
BASEMENT AND
FIRST FLOORSAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
0 4 8 16
SCALE: 1/8"=1'-0"
#ED-100 KEYED DEMOLITION NOTES
1 DISCONNECT AND REMOVE PANELBOARD. REMOVE ALL BRANCH AND FEEDER
CIRCUITRY. PATCH AND PAINT WALL BEHIND BACKBOX TO MATCH SURROUNDING
SURFACES. REFER TO THE EXISTING PANELBOARD SCHEDULE, DETAIL #2/ED-102
FOR ADDITIONAL INFORMATION.
2 DISCONNECT AND REMOVE ALL WIRING DEVICES AND BACKBOXES. REMOVE
BRANCH CIRCUITRY TO SOURCE.
3 EXISTING LIGHT FIXTURES TO REMAIN. DISCONNECT AND REMOVE ASSOCIATED
BRANCH CIRCUITRY AND CONTROL WIRING TO SOURCE. PROTECT LIGHT FIXTURES
DURING CONSTRUCTION.
4 DISCONNECT AND REMOVE EXIT SIGNS AND EMERGENCY LIGHT FIXTURES AS
SHOWN. DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SOURCE.
5 EXISTING MECHANICAL EQUIPMENT AND HARDWIRED EQUIPMENT TO REMAIN.
DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SOURCE. PROTECT
EQUIPMENT DURING CONSTRUCTION.
6 EXISTING PLUGMOLD TO REMAIN. DISCONNECT AND REMOVE BRANCH CIRCUITRY
TO SOURCE. PROTECT PLUGMOLD DURING CONSTRUCTION.
7 DISCONNECT AND REMOVE ELECTRIC RANGE RECEPTACLE. DISCONNECT AND
REMOVE BRANCH CIRCUITRY TO SOURCE.
8 EXISTING BRASS FLOOR RECEPTACLES TO REMAIN. DISCONNECT AND REMOVE
RECEPTACLE AND BRANCH CIRCUITRY TO SOURCE. REINSTALL BRASS COVERS.
9 DISCONNECT AND REMOVE ABANDONED WATER SERVICE BONDING JUMPER AND
CABLING.
10 DISCONNECT AND REMOVE EF-B00UC MANUAL STARTER AND BRANCH CIRCUITRY
TO SOURCE.
11 DISCONNECT AND REMOVE SPECIAL RECEPTACLE AND BRANCH CIRCUITRY TO
SOURCE. REINSTALL COVERPLATE.
12 WALL SCONCE MISSING AT THIS LOCATION. DISCONNECT AND REMOVE BRANCH
CIRCUITRY TO SOURCE.
13 DISCONNECT AND REMOVE WALL SCONCE AND BRANCH CIRCUITRY TO SOURCE.
14 EXISTING COVE LIGHTING TO REMAIN.
15 DISCONNECT AND REMOVE BRANCH CIRCUITY TO SOURCE. UNDERSINK DISPOSAL
TO REMAIN.
16 DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SOURCE FOR (9)
UNDERCABINET LIGHTS. UNDERCABINET LIGHTS TO REMAIN.
17 DISCONNECT AND REMOVE LIGHT SWITCH AND BRANCH CIRCUITRY FOR BASEMENT
STAIR LIGHTING. STAIR LIGHTING TO REMAIN.
18 DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SECOND FLOOR LIGHTING.
20 DISCONNECT AND REMOVE EXISTING ELECTRIC METER SOCKET AND RETURN TO
CORNELL.
21 MAINTAIN THE EXISTING POWERSCOUT ELECTRIC METER AND CT'S MONITORING
THE 37.5-KVA XFMR.
SCALE: 1/8" = 1'-0"1 DEMOLITION PLAN - BASEMENT04816
SCALE: 1/8"=1'-0"
SCALE: 1/8" = 1'-0"2 DEMOLITION PLAN - FIRST FLOOR
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
200TC
200CA 200CC204
201
213
212
211A
214
215
217
218
223
220
207
208
210
200CB200SC200TA200TD200J
100SB
200SE
200SA
200SD
223APORCH211
212A
214A
208A
204A
OPEN TO
BELOW
UP
UP
UP
DN
DN
DN
200SD
304
302
300T
301
307
308
309 310
300J
312
CRAWL
SPACE
304A
300SA
301A
301C
301B
310A
300CA
300CB
DN
DN
BATHROOM
POWER PANEL
CLOSET
POWER PANEL
SECOND FLOOR
HALL PANEL
PM
PM PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
PM
CUH-3 CUH-4
CUH-2
CUH-6
CUH-5
CUH-7
CUH-8
CUH-9 CUH-10
CUH-18
1
2
3
4
5
6
1
1
TYP
TYP
TYP
TYP
UP TO
THIRD
FLOOR
7
TYP
8 TYP OF 9
LOCATIONS
BID ALTERNATE E-2
BID ALTERNATE E-1
BID ALTERNATE E-2
BID ALTERNATE E-1
THIRD FLOOR
HALL PANEL
M
PM
PM
PM
PM
PM
PM PM
PM
PM
PM
PM
PM
PM
CUH-14
CUH-13
EF-1
CUH-12
CUH-15
CUH-16
CUH-17
CUH-11
2
TYP
3
TYP
1
6
TYP
5
TYP
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseED-101
DEMOLITION
PLANS - SECOND
AND THIRD
FLOORSAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
SCALE: 1/8" = 1'-0"1 DEMOLITION PLAN - SECOND FLOOR 0 4 8 16
SCALE: 1/8"=1'-0"
SCALE: 1/8" = 1'-0"2 DEMOLITION PLAN - THIRD FLOOR 0 4 8 16
SCALE: 1/8"=1'-0"
ED-101 KEYED DEMOLITION NOTES
1 DISCONNECT AND REMOVE PANELBOARD. REMOVE ALL BRANCH AND FEEDER
CIRCUITRY. PATCH AND PAINT WALL BEHIND BACKBOX TO MATCH SURROUNDING
SURFACES. REFER TO THE EXISTING PANELBOARD SCHEDULE, DETAIL #2/ED-102
FOR ADDITIONAL INFORMATION.
2 DISCONNECT AND REMOVE ALL WIRING DEVICES AND BACKBOXES. REMOVE
BRANCH CIRCUITRY TO SOURCE.
3 EXISTING LIGHT FIXTURES TO REMAIN. DISCONNECT AND REMOVE ASSOCIATED
BRANCH CIRCUITRY AND CONTROL WIRING TO SOURCE. PROTECT LIGHT FIXTURES
DURING CONSTRUCTION.
4 DISCONNECT AND REMOVE EXIT SIGNS AND EMERGENCY LIGHT FIXTURES AS
SHOWN. DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SOURCE.
5 EXISTING MECHANICAL EQUIPMENT AND HARDWIRED EQUIPMENT TO REMAIN.
DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SOURCE. PROTECT
EQUIPMENT DURING CONSTRUCTION.
6 EXISTING PLUGMOLD TO REMAIN. DISCONNECT AND REMOVE BRANCH CIRCUITRY
TO SOURCE. PROTECT PLUGMOLD DURING CONSTRUCTION.
7 REMOVE CARPETING AND FLOOR/SUBFLOOR TO EXPOSE FIRST FLOOR CEILING
FOR DEMOLITION AND NEW WORK. RESTORE FLOOR/SUBFLOOR AND CARPET.
8 REPLACE (9) WALL SCONCES ON SECOND FLOOR PER BID ALTERNATE E-3.
#
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
1" EMT FEEDER
TO PANEL LP-4
EM LOADCENTER
60/2 ENCLOSED
CIRCUIT BREAKER
(EM LOADCENTER MCB)
WIREWAY
LIGHTING
CONTACTOR
PANEL LP-5
100/2 ENCLOSED
CIRCUIT BREAKER
(PANEL LP-5 MCB)
FUSIBLE SWITCH
MDP
METER
EXISTING 4x4
J-BOX
EXISTING
CIT CABINET
FINISHED FLOOR
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseED-102
DEMOLITION
ELEVATION AND
EXISTING
PANELBOARD
SCHEDULEAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
SCALE: 1" = 1'-0"1 ELEVATION - BASEMENT 0 1 2
SCALE: 1"=1'-0"
EXISTING PANELBOARD INFORMATION
PANEL NAME LOCATION MANUFACTURER RATING # OF CKTS BREAKERS # OF CLOTH CKTS
EM B11 SQUARE D 100A MLO 8 (5) 20A/1P, (1) 50A/2P 0
LP-1 B00SB SQUARE D 150A MLO 20 (5) 15A/1P, (7) 20A/1P, (6) 20A/1P TANDEM, (1) 50A/2P 1
LP-2 B00C SQUARE D 150A MLO 30 (22) 20A/1P, (1) 30A/2P, (3) 20A/2P 2
LP-3 B04 SQUARE D 150A MLO 20 (1) 15A/1P, (11) 20A/1P, (2) 20A/1P TANDEM, (1) 30A/2P, (1) 60A/2P 8
LP-4 B11 SQUARE D 150A MLO 16 (8) 15A/1P, (1) 20A/1P, (3) 20A/1P TANDEM, (1) 20A/2P, (1) 30A/2P 6
LP-5 B11 SQUARE D 150A MLO 16 (10) 20A/1P 0
SNO-MELT B04 SQUARE D 100A MLO 8 (3) 30A/2P 0
2ND FLOOR HALL PANEL 200SE SQUARE D 150A MLO 20 (8) 15A/1P, (2) 20A/1P 8
2ND FLOOR BATHROOM PANEL 200TA SQUARE D 150A MLO 20 (6) 20A/1P, (1) 20A/2P 0
2ND FLOOR CLOSET PANEL 200SC SQUARE D 150A MLO 16 (12) 20A/1P, (1) 20A/2P 0
3RD FLOOR HALL PANEL 300CB SQUARE D 150A MLO 16 (3) 15A/1P, (5) 20A/1P 3
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
MDP
PANEL LP-5
LIGHTING
CONTACTOR
60/2
ENCLOSED
CIRCUIT
BREAKER
ELECTRIC
METER
CIT
JBOX
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseED-103
DEMOLITION
PHOTOSAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
SCALE:NO SCALE1PHOTO - ROOM B11 WEST WALL (MDP)
SCALE:NO SCALE2PHOTO - ROOM B11 WEST WALL (PANEL LP-5)
SCALE:NO SCALE3PHOTO - ROOM B11 WEST WALL (EM PANEL)
SCALE:NO SCALE4PHOTO - ROOM B11 NORTH WALL (PANEL LP-4)
SCALE:NO SCALE5PHOTO - ROOM B11 NORTH WALL (JB5)
SCALE:NO SCALE6PHOTO - ROOM B04 EAST WALL (PANEL LP-3)
SCALE:NO SCALE7PHOTO - ROOM B04 EAST WALL (JB6)
SCALE:NO SCALE8PHOTO - ROOM B04 (JB3)
SCALE:NO SCALE9PHOTO - ROOM B00C (PANEL LP-2)
SCALE:NO SCALE10PHOTO - ROOM B00C (JB4)
SCALE:NO SCALE11PHOTO - ROOM B02 (JB1)
SCALE:NO SCALE12PHOTO - ROOM B00SB (PANEL LP-1)
MDP
PANEL LP-5
LIGHTING
CONTACTOR
EM PANEL
EM PANEL
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION
N
CORNELLUNIVER S IT Y
F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
WARNING:Ithaca, New YorkDATE:
FACILITY:
DESIGN:
DRAWN:ARCHIVE BAR CODEARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:AD White HouseED-104
DEMOLITION
PHOTOSAD White House Electrical UpgradesC. WAYMAN
cmw
2006
March 10, 2017
9038228
SCALE:NO SCALE1PHOTO - ROOM B00SB (JB2)
SCALE:NO SCALE2PHOTO - ROOM B00C (JB7)
SCALE:NO SCALE3PHOTO - ROOM B200TA (BATHROOM PANEL)
SCALE:NO SCALE4PHOTO - ROOM 200SC (CLOSET PANEL)
SCALE:NO SCALE5PHOTO - ROOM 300CB (HALLWAY PANEL)
SCALE:NO SCALE6PHOTO - ROOM 200SE (HALLWAY PANEL)
REVISIONS
1 10/21/16 ISSUE FOR 50% DD REVIEW
2 2/24/17 ISSUE FOR COORDINATED REVIEW
3 3/10/17 ISSUE FOR CONSTRUCTION