HomeMy WebLinkAboutAD White House Electrical Upgrades IFBCB CB CB UP UP UP DN UP DN DN DN DN UP DN UP UP UP DN DN DN DN DN AD WHITE HOUSE 2006EAS T AVENUEURIS HALL 2087 IVES HALL 1009 STIMSON HALL 2011 DAY HALL 2026 TOWER ROAD N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL: Cornell University Ithaca, New York Humphreys Service Building; Ithaca, N.Y. Architectural & Structural, Civil & Environmental, Mechanical and Electrical Engineering Facilities Engineering PROJECT SCOPE AD White HouseT-001 TITLE SHEETAD White House Electrical UpgradesFE DESIGN cmw 2006 March 10, 2017 9038228 AD White House Electrical Upgrades The purpose of this project is to replace the existing electrical distribution at the A.D. White House. The work includes the replacement of all panelboards, feeders, and branch circuits. The work also includes the replacement of all wiring devices, including receptacles and light switches; and the replacement of the emergency egress lighting. This building is listed on the National Register of Historic Places. Refer to the BASE BID AND ALTERNATES Notes on Drawing E-000 for Base Bid and Alternate work. Refer to the CONSTRUCTION PHASING Notes on Drawing E-000 for important project information. DRAWING LIST T-001 TITLE SHEET E-000 SCOPE OF WORK, GENERAL NOTES, SYMBOLOGY, AND ABBREVIATIONS E-010 KEYPLANS E-100 POWER PLANS - BASEMENT AND FIRST FLOORS E-101 POWER PLANS - SECOND AND THIRD FLOORS E-200 LIGHTING PLANS - BASEMENT AND FIRST FLOOR E-201 LIGHTING PLANS - SECOND AND THIRD FLOORS E-300 EGRESS LIGHTING PLANS - BASEMENT AND FIRST FLOORS E-301 EGRESS LIGHTING PLANS - SECOND AND THIRD FLOORS E-400 GROUNDING AND BONDING PLAN E-500 ONE-LINE DIAGRAMS E-501 PANELBOARD SCHEDULES E-502 PANELBOARD SCHEDULES E-503 EQUIPMENT CONNECTION AND LUMINAIRE SCHEDULES E-504 DETAILS ED-100 DEMOLITION PLANS - BASEMENT AND FIRST FLOORS ED-101 DEMOLITION PLANS - SECOND AND THIRD FLOORS ED-102 DEMOLITION ELEVATION AND EXISTING PANELBOARD SCHEDULE ED-103 DEMOLITION PHOTOS ED-104 DEMOLITION PHOTOS SITE PLAN - AD WHITE HOUSE AREA OF WORK LOCATION PLAN - AD WHITE HOUSE (ALL FLOORS) BASEMENT AREA OF WORK FIRST FLOOR THIRD FLOOR SECOND FLOOR REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseE-000 SCOPE OF WORK, GENERAL NOTES, SYMBOLOGY, AND ABBREVIATIONSAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 SCOPE OF WORKGENERAL NOTES 1.0 THIS BUILDING IS LISTED ON THE NATIONAL REGISTER OF HISTORIC PLACES. 2.0 REPLACE THE ENTIRE ELECTRICAL DISTRIBUTION, INCLUDING PANELBOARDS, FEEDERS, AND BRANCH CIRCUITS. 3.0 REPLACE ALL WIRING DEVICES. 4.0 TRENCH AND RESTORE PLASTER WALLS AND CEILINGS TO CONCEAL ALL FEEDERS AND BRANCH CIRCUIT WIRING. INCLUDES PAINTING OF ENTIRE WALLS AND CEILINGS AFFECTED BY ELECTRICAL WORK. 5.0 REMOVE AND SAVE MOLDINGS AND TRIMS TO CONCEAL BRANCH CIRCUIT WIRING AND REINSTALL. INCLUDES PAINTING OF ALL MOLDINGS, TRIMS, AND BASEBOARDS AFFECTED BY ELECTRICAL WORK. 6.0 REPLACE THE HALLWAY SCONCES. 7.0 2.4-kV SWITCH AND BUILDING TRANSFORMER ARE EXISTING TO REMAIN. 8.0 PROVIDE ARC FLASH LABELS ON ALL PANELBOARDS.. 9.0 PROVIDE WIRELESS LIGHTING CONTROLS. 10.0 REFER TO CONSTRUCTION DOCUMENTS FOR FULL SCOPE. 11.0 CONTRACTOR IS RESPONSIBLE TO DETERMINE ALL FEEDER, BRANCH CIRCUIT, AND SURFACE RACEWAY ROUTING IN-FIELD. THIS WORK WILL REQUIRE EXTENSIVE FIELD INVESTIGATION TO LOCATE SUITABLE PATHWAYS WITHIN PLASTER WALLS AND CEILINGS, AND BETWEEN FLOORS. 1.0 ELECTRICAL SCHEMATICS INDICATED ON CONTRACT DOCUMENTS ARE DIAGRAMMATIC. IT IS NOT THE INTENT TO SHOW EXACT OR MOST EFFICIENT ROUTING. VERIFY ALL DIMENSIONS AND FIELD CONDITIONS ON SITE. ANY CONFLICTS BETWEEN CONSTRUCTION DOCUMENTS AND FIELD CONDITIONS SHALL BE BROUGHT TO CORNELL'S PROJECT MANAGER FOR RESOLUTION BEFORE WORK PROCEEDS. 2.0 ASSURE PUBLIC AND WORKER SAFETY AT ALL TIMES. PROTECT ADJOINING AREAS FROM DAMAGE AND DUST. REMOVE ALL DEBRIS FROM SITE AND DISPOSE OF WASTE MATERIAL IN A SAFE MANNER. KEEP THE PREMISES FREE OF DEBRIS FROM THE EXECUTION OF WORK. DELIVER A FINAL PRODUCT THAT IS CLEAN AND OPERABLE. 3.0 FIRE STOP ELECTRICAL PENETRATIONS THROUGH FIRE RATED WALLS AND/OR FLOORS WITH MATERIAL EQUAL IN RATING TO THE CONSTRUCTION OF THE MATERIAL PENETRATED. 4.0 WORK SHALL BE COMPLETED AS SPECIFIED AND INDICATED ON CONTRACT DOCUMENTS. ANY SUGGESTED ALTERNATE MANUFACTURER OR METHOD OF INSTALLATION SHALL BE SUBMITTED TO PROJECT ENGINEER FOR APPROVAL PRIOR TO ORDERING ANY MATERIALS OR COMMENCING EXECUTION OF WORK. 5.0 GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLE 250. PROVIDE EQUIPMENT GROUND CONDUCTOR WITH EACH BRANCH CIRCUIT INDICATED ON CONTRACT DOCUMENTS. EQUIPMENT GROUND CONDUCTOR SHALL BE ROUTED WITH ASSOCIATED PHASE CONDUCTORS. 6.0 PROVIDE A NEW TYPED PANELBOARD DIRECTORY FOR EACH PANELBOARD. LABEL ALL NEW DEVICE FACEPLATES WITH SOURCE AND CIRCUIT NUMBER. PROVIDE PERMANENT LABEL ON SWITCHING DEVICES INDICATING EQUIPMENT SERVICE AND INVENTORY NUMBERS. COORDINATE EQUIPMENT INVENTORY NUMBERS WITH CORNELL UNIVERSITY'S MECHANICAL SHOP, 255-8667. 7.0 CIRCUITS RATED 20-AMP, 120 VOLT SHALL CONTAIN SEPARATE NEUTRAL CONDUCTORS. 8.0 CONDUCTORS SHALL BE A MINIMUM OF 12AWG, STRANDED COPPER, 600VAC, 90 DEGREE C, TYPE THHN/THWN FOR DRY AREAS AND XHHW/THWN-2 FOR WET AREAS. 9.0 CONDUITS SHALL BE A MINIMUM OF 3/4 INCHES DIAMETER. CONDUITS SHALL BE ELECTRICAL METALLIC TUBING (EMT) AND SURFACE MOUNTED UNLESS NOTED OTHERWISE. 10.0 AIC RATING OF NEW CIRCUIT BREAKERS SHALL MATCH RATING OF RESPECTIVE PANELBOARD. SIZE AS INDICATED. 11.0 PROVIDE PULL STRING THROUGH NEW CONDUIT AND BOXES. PROVIDE SUPPORT HANGERS FOR CONDUIT AS NEEDED. 12.0 INSTALL RACEWAY SYSTEMS ENSURING PROPER ACCESS TO EQUIPMENT AND DEVICES AND WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE AND REPAIR. RACEWAYS THAT ARE NOT INSTALLED WITH THIS REQUIREMENT IN MIND SHALL BE RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIES ARE CORRECTED. 1.0 THIS BUILDING IS LISTED ON THE NATIONAL REGISTER OF HISTORIC PLACES. 2.0 INTERIOR FINISHES SHALL BE PHYSICALLY ISOLATED FROM CONSTRUCTION OPERATIONS BY MEANS OF PROTECTIVE BARRIERS AND COVERINGS, INCLUDING BUT NOT LIMITED TO: ORNAMENTAL AND DECORATIVE PLASTER WALLS AND CEILINGS; FLOORS; STAIRCASES AND RAILINGS; WOOD AND MARBLE WAINSCOT; WOOD DOORS; WOOD CASINGS, TRIM, AND MOLDINGS; GLAZING; LIGHT FIXTURES AND FURNITURE. 3.0 ALL SURFACES AND FURNITURE SHALL BE PROTECTED FROM DAMAGE CAUSED BY ABRASION, FALLING OBJECTS, DUST AND DIRT, AND SPILLED LIQUIDS. PROVIDE CANVAS TARPS, POLYETHYLENE SHEETING AND FIRE RETARDANT PLYWOOD PANELS (UL LISTED, CLASS A) AS REQUIRED. 4.0 FLOORS SHALL BE PROTECTED FROM HEAVY EQUIPMENT BY A LAYER OF HOMASOTE AND FIRE RETARDANT PLYWOOD (STAGGER JOINTS TO STABILIZE THE ASSEMBLY). 5.0 PLASTER CEILING/WALL PATCHING: PATCH OPENINGS WITH PLASTER SYSTEM FLUSH TO MATCH EXISTING. PRIME AND PAINT ENTIRE WALL OR CEILING SURFACE. REFER TO DIVISION 09 FOR PLASTER RESTORATION QUALIFICATIONS AND REQUIREMENTS. 6.0 PAINTING: REFER TO DIVISION 09 FOR PAINTING REQUIREMENTS. HISTORIC PRESERVATION GENERAL NOTES ELECTRICAL LEGEND LIGHTING LEGEND DEMOLITION KEYED NOTE CONSTRUCTION KEYED NOTE MOTOR 1'x4' LUMINAIRE HARDWIRED EQUIPMENT CONNECTION P-1A12 HOMERUN TO PANEL P-1A, CIRCUIT #12. FED FROM 20A - 1P BREAKER IS INTENDED UNLESS NOTED OTHERWISE. RUN GREEN WIRE GROUND FOR ALL CIRCUITS. PROVIDE ONE GROUND PER CIRCUIT. ENCLOSED CIRCUIT BREAKER GROUND ROD ELECTRODE DUPLEX RECEPTACLE WITH GFCI PROTECTION DUPLEX RECEPTACLE WITH AFCI PROTECTION QUAD RECEPTACLE # # SPECIAL RECEPTACLE5-30R PANELBOARD JUNCTION BOX B = INSTALLED IN BASEBOARD TR = INSTALLED IN WOOD TRIM/CASEWORK/WAINSCOTT SR = SURFACE RACEWAY WP = WEATHERPROOF AC = AIR CONDITIONER X DUPLEX RECEPTACLE: DOUBLE DUPLEX RECEPTACLE MOTOR STARTER J 2'x4' LUMINAIRE CEILING MOUNTED LUMINAIRE EM LIGHTING BATTERY UNIT COMBO EXIT SIGN/EM LIGHTING BATTERY UNIT SINGLE FACE, WALL MOUNT EXIT SIGN DOUBLE FACE, WALL MOUNT EXIT SIGN SINGLE FACE, CEILING MOUNT EXIT SIGN DOUBLE FACE, CEILING MOUNT EXIT SIGN LIGHT SWITCH: SAFETY SWITCH (NON-FUSED) SAFETY SWITCH (FUSED) X 3 = 3-WAY SWITCH 4 = 4-WAY SWITCH D = DIGITAL SWITCH R = REMOTE, WIRELESS SWITCH O = WALL SWITCH OCCUPANCY SENSOR V = WALL SWITCH VACANCY SENSOR W = WIRELESS SWITCH S = WIRELESS SCENE SWITCH WIRELESS OCCUPANCY SENSOR WIRELESS DAYLIGHT SENSOR OS X DS 1'x2' LUMINAIRE GENERAL SYMBOLS LEGEND EXTERIOR ELEVATION 1 1 1 1E-100 E-100 1 1 1 1 INTERIOR ELEVATION 1 E-100 BUILDING SECTION 1 E-100 ENLARGED DETAIL ELECTRICAL ABBREVIATIONS AC AIR CONDITIONER AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AFI ARC FAULT INTERRUPTER AMM ADDRESSABLE MONITOR MODULE AOM ADDRESSABLE OUTPUT MODULE ARB AUXILIARY RELAY BOARD ATS AUTOMATIC TRANSFER SWITCH B BASEBOARD BKR BREAKER C CONDUIT CD CANDELA CKT CIRCUIT CR CONTROL RELAY EC ELECTRICAL CONTRACTOR EMT ELECTRICAL METALLIC TUBING EPO EMERGENCY POWER OFF STATION FAA FIRE ALARM ANNUNCIATOR PANEL FACP FIRE ALARM CONTROL PANEL FSD FIRE SMOKE DAMPER GAA GENERATOR ALARM ANNUNCIATOR GFI GROUND FAULT INTERRUPTER GND GROUND HP HORSEPOWER KW KILOWATT LC LIGHTING CONTACTOR LFMC LIQUID TIGHT FLEXIBLE METALLIC CONDUIT LTG LIGHTING MANUF MANUFACTURER MCB MAIN CIRCUIT BREAKER MLO MAIN LUG ONLY MTS MANUAL TRANSFER SWITCH NAC NOTIFICATION APPLIANCE CIRCUIT NIC NOT IN CONTRACT OE OVERHEAD ELECTRIC PC PHOTOCELL PM PLUGMOLD PP POWER PANEL PVC POLYVINYL CHLORIDE CONDUIT RGS RIGID GALVANIZED STEEL CONDUIT SR SURFACE RACEWAY ST SHUNT TRIP TM THERMAL MAGNETIC TR TRIM/CASEWORK/WAINSCOTT TSP TWISTED SHIELDED PAIR TYP TYPICAL UE UNDERGROUND ELECTRIC UON UNLESS OTHERWISE NOTED UPS UNINTERRUPTIBLE POWER SUPPLY V VOLTS VA VOLT AMPS WP WATERPROOF CONSTRUCTION PHASING: 1.0 PHASE 1: BASE BID WORK ON ALL FLOORS. 2.0 PHASE 2: SECOND AND THIRD FLOOR BID ALTERNATE WORK. CONSTRUCTION SCHEDULING: 3.0 PHASE 1 (BASE BID) WORK: - BASEMENT WORK:WORK MAY BEGIN IMMEDIATELY AFTER AWARD - 1ST FLOOR ROOMS 108, 110 - START:MAY 30, 2017 - 1ST, 2ND, 3RD FLOORS - START: JULY 31, 2017 - ALL FLOORS - COMPLETE WORK: AUGUST 22, 2017 4.0 PHASE 2 (BID ALTERNATE) WORK: - 2ND, 3RD FLOORS - START::DECEMBER 18, 2017 - 2ND, 3RD FLOORS - COMPLETE WORK:JANUARY 24, 2018 5.0 DURING PHASE 1 BASEMENT WORK, BUILDING MUST BE FULLY OPERATIONAL DURING NORMAL BUSINESS HOURS. FURNITURE: 6.0 CONTRACTOR SHALL MOVE ALL FURNITURE IN AREAS UNDER CONSTRUCTION. CAREFULLY LOCATE FURNITURE IN 1ST FLOOR ROOMS 109, AND 110. ONCE CONSTRUCTION IS COMPLETE, CONTRACTOR SHALL MOVE FURNITURE BACK. 7.0 CORNELL IS RESPONSIBLE FOR THE PACKING, MOVING, AND STORING OF FACULTY/STAFF PERSONAL ITEMS. FIRE ALARM: 8.0 FIRE ALARM SYSTEM MUST BE FULLY OPERATIONAL AT ALL TIMES. 9.0 PROVIDE CERTIFIED FIRE WATCH AT ALL TIMES THAT THE FIRE ALARM SYSTEM IS IMPAIRED. COORDINATE ALL IMPAIRMENTS WITH CORNELL EHS. SERVICE INTERRUPTIONS: 10.0 SERVICE INTERRUPTIONS/SHUTDOWNS MUST BE SCHEDULED 2 WEEKS IN ADVANCE. 11.0 SERVICE INTERRUPTIONS/SHUTDOWNS MUST BE SCHEDULED TO OCCUR OUTSIDE OF NORMAL BUSINESS HOURS AND MUST BE PERFORMED ON WEEKENDS, OR HOLIDAYS. TEMPORARY POWER: 12.0 TAP BUS OF EXISTING MDP AND PROVIDE A 225A/2P ENCLOSED CIRCUIT BREAKER TO TEMPORARILY FEED THE NEW MDP DURING CONSTRUCTION. ONCE CONSTRUCTION IS COMPLETE, DISCONNECT AND REMOVE THE TEMPORARY FEEDER AND PROVIDE THE PERMANENT MDP FEEDER AS SHOWN ON THE POWER RISER DIAGRAM. EMERGENCY EGRESS: 13.0 EMERGENCY EGRESS LIGHTING AND EXIT SIGNS MUST REMAIN OPERATIONAL AT ALL TIMES. 14.0 DO NOT IMPEDE THE MEANS OF EGRESS. IF WORK REQUIRES THE IMPAIRMENT OF A MEANS OF EGRESS, PROVIDE CONSTRUCTION BARRIERS AND TEMPORARY EMERGENCY EGRESS LIGHTING AND EXIT SIGNS. COORDINATE MEANS OF EGRESS IMPAIRMENTS WITH EHS. RESTORATION: 15.0 ALL FEEDER CONDUITS MUST BE CONCEALED WITHIN WALLS, FLOORS, AND CEILINGS ON THE FIRST, SECOND, AND THIRD FLOORS. 16.0 ALL BRANCH CIRCUIT CONDUITS MUST BE CONCEALED WITHIN WALLS, FLOORS, AND CEILINGS ON THE FIRST FLOOR. NO EXCEPTIONS WILL BE CONSIDERED. 17.0 BRANCH CIRCUITRY MAY BE INSTALLED IN ARMORED CABLE WITHIN THE PLASTER WALLS/CEILINGS. TRENCH PLASTER WALLS/CEILINGS AS NEEDED. 18.0 FEEDER AND BRANCH CIRCUIT CONDUITS MAY BE EXPOSED IN THE BASEMENT. 19.0 BRANCH CIRCUITS MAY BE INSTALLED IN METALLIC SURFACE RACEWAYS IN OFFICES AND ROOMS ON THE SECOND AND THIRD FLOORS. DO NOT INSTALL SURFACE RACEWAYS IN THE HALLWAYS OR PUBLIC SPACES ON THE SECOND AND THIRD FLOORS. 20.0 INSTALL SURFACE RACEWAYS ALONG EDGES/CORNERS OF WALLS AND CEILINGS. 21.0 DO NOT INSTALL SURFACE RACEWAYS ON BASEBOARDS AND TRIMS. 22.0 PAINT ALL SURFACE RACEWAYS TO MATCH SURROUNDING SURFACES. 23.0 CONCEAL ALL BRANCH CIRCUITS TO WIRING DEVICES INSTALLED IN THE WOOD BASEBOARD/TRIM WITHIN THE BASEBOARDS ON THE FIRST, SECOND, AND THIRD FLOORS. 24.0 WHERE BASEBOARDS/TRIM MUST BE REMOVED TO ACCOMMODATE CONSTRUCTION - PAINT ALL BASEBOARD/TRIM WITHIN THE ROOM/SPACE. 25.0 REPLACE BASEBOARD/TRIM DAMAGED DURING REMOVALS/CONSTRUCTION. REPLACEMENTS MUST MATCH THE WOOD SPECIES, DIMENSIONS, PROFILE, AND FINISH OF THE EXISTING BASEBOARD/TRIM. MINIMUM REPLACEMENT LENGTH IS 4'-0" - DO NOT PIECE-IN LENGTHS SMALLER THAN THE MINIMUM SPECIFIED. 26.0 WHERE PLASTER IS DISTURBED/RESTORED - PAINT THE ENTIRE WALL OR CEILING. 27.0 CONTRACTOR IS RESPONSIBLE TO DETERMINE ALL FEEDER, BRANCH CIRCUIT, AND SURFACE RACEWAY ROUTING IN FIELD. THIS WORK WILL REQUIRE EXTENSIVE FIELD INVESTIGATION TO LOCATE SUITABLE PATHWAYS WITHIN PLASTER WALLS AND CEILINGS, AND BETWEEN FLOORS. STAGING/CONTRACTOR OFFICE/CONTRACTOR RESTROOM FACILITIES: 28.0 STAGE ALL CONSTRUCTION MATERIALS, EQUIPMENT, AND TOOLS IN THE BASEMENT. 29.0 CONTRACTOR SHALL USE SPACE IN THE BASEMENT FOR A TEMPORARY OFFICE SPACE. 30.0 CONTRACTOR MAY USE THE TOILET FACILITIES LOCATED IN RESTROOM B00T. GARBAGE/CONSTRUCTION DEBRIS: 31.0 DUE TO SITE LIMITATIONS, A DUMPSTER MAY NOT BE LOCATED AT OR NEAR THE BUILDING. 32.0 GARBAGE AND CONSTRUCTION DEBRIS MUST BE REMOVED FROM THE SITE DAILY. STORE MATERIALS OUT-OF-SIGHT IN THE BASEMENT UNTIL THE MATERIALS ARE TO BE REMOVED. 33.0 ALL CONSTRUCTION MATERIALS AND DEBRIS MUST BE MOVED INTO AND OUT OF THE BUILDING VIA THE BASEMENT STAIRS LOCATED ON THE EAST SIDE OF THE BUILDING. CONTRACTOR PARKING: 34.0 CONTRACTOR SHALL CONTACT CORNELL TRANSPORTATION AND SECURE ONE PARKING PERMIT TO PARK NEAR THE AD WHITE HOUSE. CONTRACTOR IS RESPONSIBLE FOR ALL PARKING COSTS AND FINES. 35.0 PARKING FOR WORKERS IS AVAILABLE IN THE PARKING LOT ON EAST PALM ROAD, NEAR THE CORNELL ORCHARDS. A NO-FEE PERMIT IS REQUIRED FOR EACH VEHICLE. CONSTRUCTION PHASING NOTES LINETYPES LEGEND UNDERGROUND ELECTRICUE UNDERGROUND LIGHTINGUL OVERHEAD ELECTRICOE TO BE PROVIDED DEMOLITION / TO BE RELOCATED EXISTING TO REMAIN UNDERGROUND TELCOUC BASE BID AND ALTERNATES 1.0 BASE BID WORK: - PROVIDE PANELBOARD REPLACEMENTS (ALL FLOORS). - INSTALL ARC FLASH LABELS FURNISHED BY OTHERS (ALL FLOORS). - PROVIDE SURGE PROTECTIVE DEVICES (ALL FLOORS). - PROVIDE FEEDER REPLACEMENTS (ALL FLOORS). - PROVIDE GROUNDING AND BONDING WORK. - PROVIDE WIRING DEVICE REPLACEMENTS AT BASEMENT AND FIRST FLOOR. - PROVIDE MOTOR CONTROL REPLACEMENTS AT BASEMENT AND FIRST FLOOR. - PROVIDE BRANCH CIRCUIT REPLACEMENTS AT BASEMENT AND FIRST FLOOR. - PROVIDE EXIT SIGN AND EMERGENCY EGRESS LIGHTING AT BASEMENT AND FIRST FLOOR. - PROVIDE WALL SCONCE REPLACEMENTS. - PROVIDE WIRELESS LIGHTING CONTROLS AT BASEMENT AND FIRST FLOOR. - PROVIDE ASSOCIATED PLASTER, TRIM, AND MOLDING RESTORATION. - PROVIDE ASSOCIATED PAINTING WORK. - PROVIDE ALL ASSOCIATED DEMOLITION WORK. - PROVIDE ALL ASSOCIATED FIREPROOFING. 2.0 BID ALTERNATE E-1: A.THIS BID ALTERNATE APPLIES TO ALL WORK ASSOCIATED WITH THE SECOND FLOOR ELECTRICAL PANELBOARD LLP-21. - PROVIDE WIRING DEVICE REPLACEMENTS AT SECOND FLOOR. - PROVIDE BRANCH CIRCUIT REPLACEMENTS AT SECOND FLOOR. - PROVIDE MOTOR CONTROL REPLACEMENTS AT SECOND FLOOR. - PROVIDE EXIT SIGN AND EMERGENCY EGRESS LIGHTING AT SECOND FLOOR. - PROVIDE LIGHTING CONTROLS AT SECOND FLOOR. - PROVIDE ASSOCIATED PLASTER, TRIM, AND MOLDING RESTORATION. - PROVIDE ASSOCIATED PAINTING WORK. - PROVIDE ALL ASSOCIATED DEMOLITION WORK. - PROVIDE ALL ASSOCIATED FIREPROOFING. 3.0 BID ALTERNATE E-2: A.THIS BID ALTERNATE APPLIES TO ALL WORK ASSOCIATED WITH THE SECOND FLOOR ELECTRICAL PANELBOARDS LLP-22 / LLP-23. - PROVIDE WIRING DEVICE REPLACEMENTS AT SECOND FLOOR. - PROVIDE BRANCH CIRCUIT REPLACEMENTS AT SECOND FLOOR. - PROVIDE MOTOR CONTROL REPLACEMENTS AT SECOND FLOOR. - PROVIDE EXIT SIGN AND EMERGENCY EGRESS LIGHTING AT SECOND FLOOR. - PROVIDE LIGHTING CONTROLS AT SECOND FLOOR. - PROVIDE ASSOCIATED PLASTER, TRIM, AND MOLDING RESTORATION. - PROVIDE ASSOCIATED PAINTING WORK. - PROVIDE ALL ASSOCIATED DEMOLITION WORK. - PROVIDE ALL ASSOCIATED FIREPROOFING. 4.0 BID ALTERNATE E-3: A.THIS BID ALTERNATE APPLIES TO ALL WORK ON THE THIRD FLOOR. - PROVIDE WIRING DEVICE REPLACEMENTS AT THIRD FLOOR. - PROVIDE BRANCH CIRCUIT REPLACEMENTS AT THIRD FLOOR. - PROVIDE MOTOR CONTROL REPLACEMENTS AT THIRD FLOOR. - PROVIDE EXIT SIGN AND EMERGENCY EGRESS LIGHTING AT THIRD FLOOR. - PROVIDE LIGHTING CONTROLS AT THIRD FLOOR. - PROVIDE ASSOCIATED PLASTER, TRIM, AND MOLDING RESTORATION. - PROVIDE ASSOCIATED PAINTING WORK. - PROVIDE ALL ASSOCIATED DEMOLITION WORK. - PROVIDE ALL ASSOCIATED FIREPROOFING. 5.0 WORK NOT SPECIFIED AS AN ALTERNATE IS BASE BID WORK. O = OCCUPANCY SENSOR V = VACANCY SENSOR SURGE PROTECTIVE DEVICESP 1.0 ELECTRICAL EQUIPMENT SHOWN DASHED ON DEMOLITION DRAWINGS, INCLUDING ASSOCIATED ANCHORS, SUPPORTS, STRAPS, BOXES, FITTINGS, AND OTHER APPURTENANCES NOT SHOWN, SHALL BE DISCONNECTED AND REMOVED. REMOVE ASSOCIATED BRANCH CIRCUITRY TO SOURCE, UNLESS NOTED OTHERWISE. 2.0 EXISTING RACEWAYS AND BACKBOXES MAY NOT BE REUSED WITHOUT AUTHORIZATION FROM CORNELL FACILITIES ENGINEERING. 3.0 CUT DEMOLISHED CONDUITS INSTALLED THRU WALLS AND FLOORS FLUSH WITH THE SURFACE AND PATCH PENETRATIONS (FIRESTOP IF LOCATED ON A FIRE RATED SURFACE). PATCH AND PAINT SURFACES IN EXPOSED AREAS TO MATCH SURROUNDING MATERIALS, FINISHES, AND COLORS. 4.0 PROVIDE BLANK COVERPLATES ON UNUSED BACKBOXES REMAINING FROM DEMOLITION NOT SPECIFIED TO BE INFILLED. 5.0 PATCH WALLS AT EQUIPMENT REMOVALS AND PAINT TO MATCH SURROUNDING SURFACES. 6.0 EXISTING EQUIPMENT SHOWN TO REMAIN SHALL BE PROTECTED DURING CONSTRUCTION. GENERAL DEMOLITION NOTES CB DIGITAL TIMECLOCK PHOTOCELLPC TC MOUNTING HEIGHTS CARD READER 48" TOP OF BOX LIGHT SWITCH 48" TOP OF BOX RECEPTACLE 18" TOP OF BOX DATA OUTLET 18" TOP OF BOX TV OUTLET 84" TOP OF BOX PHONE OUTLET 48" TOP OF BOX SAFETY SWITCH 60" CENTERLINE OF HANDLE MOTOR STARTER 60" CENTERLINE OF HANDLE PANELBOARD 72" TOP OF PANELBOARD MANUAL PULL STATION 48" OPERABLE HANDLE NOTIFICATION APPLIANCE 80" BOTTOM OF LENS DOOR HOLD OPEN COORDINATE IN FIELD EM BATTERY UNIT 96" BOTTOM OF UNIT EM REMOTE UNIT 102" BOTTOM OF UNIT EXIT SIGN 96" BOTTOM OF UNIT GROUND BUS BAR M ELECTRICAL METER DUAL, REMOTE EM LIGHTING HEADS REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION UP UP UP DN UP DN DN DN DN UP DN UP UP UP DN DN DN DN DN 1 TYP 2 TYP 1 TYP 2 TYP 3 3 3 3 1 TYP 2 TYP 3 3 33 1 TYP 2 TYP UNFINISHED, ACCESSIBLE ATTIC SPACE N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseE-010 KEYPLANSAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 SCALE: 1/16" = 1'-0"1 KEYPLAN - BASEMENT SCALE: 1/16" = 1'-0"2 KEYPLAN - FIRST FLOOR SCALE: 1/16" = 1'-0"3 KEYPLAN - SECOND FLOOR SCALE: 1/16" = 1'-0"4 KEYPLAN - THIRD FLOOR 0 8 16 32 SCALE: 1/16"=1'-0" 0 8 16 32 SCALE: 1/16"=1'-0" 0 8 16 32 SCALE: 1/16"=1'-0" 0 8 16 32 SCALE: 1/16"=1'-0" CEILING HEIGHT: 7'-2" FINISHED FLOOR TO BOTTOM OF WOOD JOISTS CEILING HEIGHT: 12'-4" FINISHED FLOOR TO PLASTER CEILING. CEILING HEIGHT: 10'-4" FINISHED FLOOR TO PLASTER CEILING. CEILING HEIGHT: 11'-0" FINISHED FLOOR TO PLASTER CEILING. E-010 KEYED CONSTRUCTION NOTES 1 WALLS SHOWN SHADED ARE SOLID MASONRY WITH PLASTER ADHERED DIRECTLY TO THE MASONRY. THERE IS NO CAVITY BETWEEN THE MASONRY AND PLASTER TO INSTALL FEEDER OR BRANCH CIRCUITRY. 2 WALLS SHOWN NOT SHADED UTILIZE CONVENTIONAL LUMBER FRAMING AND MAY HAVE AN ACCESSIBLE CAVITY TO INSTALL FEEDER AND BRANCH CIRCUITRY. 3 LOCATIONS INDICATED ARE PIPE CHASES FROM THE 1973 RENOVATION PROJECT THAT MAY CONTAIN SPACE FOR FEEDER AND BRANCH CIRCUIT WIRING. CHASES ARE LOCATED BEHIND PLASTER WALLS. LOCATIONS ARE SHOWN FOR REFERENCE ONLY. CONTRACTOR MUST VERIFY IF PIPE CHASES CONTAIN ADEQUATE SPACE FOR FEEDER AND BRANCH CIRCUIT WIRING. IF PIPE CHASES ARE USED, PATCH PLASTER AND PAINT WALLS. # BASEMENT CONDUIT INSTALLATION: - FEEDERS MAY BE INSTALLED EXPOSED. - BRANCH CIRCUITS MAY BE INSTALLED EXPOSED. FIRST FLOOR CONDUIT INSTALLATION: - FEEDERS MUST BE CONCEALED WITHIN WALLS, FLOORS, OR CEILINGS. TRENCH PLASTER WALLS AND RESTORE. - BRANCH CIRCUITS MUST BE CONCEALED WITHIN WALLS, FLOORS, OR CEILINGS. TRENCH PLASTER WALLS AND RESTORE. SURFACE RACEWAYS ARE NOT ACCEPTABLE. - BRANCH CIRCUITS FEEDING RECEPTACLES INSTALLED IN WOOD BASEBOARDS MUST BE CONCEALED WITHIN THE WOOD BASEBOARDS. SECOND FLOOR CONDUIT INSTALLATION: - FEEDERS MUST BE CONCEALED WITHIN WALLS, FLOORS, OR CEILINGS. TRENCH PLASTER WALLS AND RESTORE. - BRANCH CIRCUITS MAY BE INSTALLED IN METALLIC SURFACE RACEWAYS. - BRANCH CIRCUITS FEEDING RECEPTACLES INSTALLED IN WOOD BASEBOARDS MUST BE CONCEALED WITHIN THE WOOD BASEBOARDS. THIRD FLOOR CONDUIT INSTALLATION: - FEEDERS MUST BE CONCEALED WITHIN WALLS, FLOORS, OR CEILINGS. TRENCH PLASTER WALLS AND RESTORE. - BRANCH CIRCUITS MAY BE INSTALLED IN METALLIC SURFACE RACEWAYS. - BRANCH CIRCUITS FEEDING RECEPTACLES INSTALLED IN WOOD BASEBOARDS MUST BE CONCEALED WITHIN THE WOOD BASEBOARDS. REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION B00UB B00UC B11 B13 B13C B13B B13A B04 B07 B02 B05 B00T B03 B01 B14 B00SB B00SA B00UA B09 PIT CRAWL SPACE CRAWL SPACE B00C UP UP UP FCU-B1 FCU-B2 FCU-B3 FCU-B7 FCU-B4 FCU-B5 FCU-B6 SP-2 SP-1 CP-1 48"SPSP SP SP48"48" CB 100TB 100SC 100SA 100SB 100JA 113 113A 114 108 112 109 101 110 103 100TA 103A 103B 102 102A 100CA 100CB 100JB 111 ENCLOSED PORCH PORCH PORCH PATIO 114A DN UP DN DN DN DN UP DN B BB BB B B BBBBB BB B BTR B BSRSRB BWPTRCUH-1 AC AC WPWPJ-2 J-1 FEEDER UP TO PANEL LLP-21 FEEDER UP TO PANEL LLP-22 FEEDER UP TO PANEL LLP-23 MDP LLP-B2 LLP-B3 LLP-B1 SM-1 SM-2 SM-3 IR-1 WH-1 FACP LLP-B1-26 LLP-B1-10 LLP-B1-8 LLP-B1-4 LLP-B2-10,12 LLP-B2-29 LLP-B2-9,11 LLP-B2-4 LLP-B2-10,12 LLP-B2-23 LLP-B2-37,39 LLP-B2-8 LLP-B2-1LLP-B2-23 LLP-B2-23 LLP-B3-4 LLP-B3-5 1 1 1 2 TYP 4 4 3 TYP 5 TYP 6 6 EXISTING 2.4KV/120/240V TRANSFORMER EXISTING 2.4KV SWITCH PUMP CP EF-B00UC LLP-B2-22 LLP-B1-30,32 LLP-B1-19,21 LLP-B1-12,14 LLP-B1-16 LLP-B3-11 LLP-B3-13 15 6 M16 17 PM PM PM RNG-1 LLP-B1-22 LLP-B1-7 LLP-B1-17LLP-B1-5,7 LLP-B1-6 LLP-B1-18 LLP-B1-3 LLP-B1-9 LLP-B2-2 LLP-B1-1 LLP-B3-7 LLP-B3-3 LLP-B3-2 LLP-B3-9 LLP-B2-33 LLP-B2-21 LLP-B2-25 LLP-B2-7 LLP-B2-19 LLP-B2-15,17 LLP-B2-14 LLP-B2-27 LLP-B2-13LLP-B2-16 LLP-B2-20 2 TYP 3 TYP 8 8 9 7 TYP 10 11 12 UNDERSINK DISPOSAL 13 14 LLP-B2-20 N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseE-100 POWER PLANS - BASEMENT AND FIRST FLOORSAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 # 0 4 8 16 SCALE: 1/8"=1'-0" 0 4 8 16 SCALE: 1/8"=1'-0" SCALE: 1/8" = 1'-0"1 POWER PLAN - BASEMENT SCALE: 1/8" = 1'-0"2 POWER PLAN - FIRST FLOOR E-100 KEYED CONSTRUCTION NOTES 1 PROVIDE PANELBOARD AND FASTEN TO MASONRY WALL USING TAPCON FASTENERS. INSTALL ARC FLASH LABELS FURNISHED BY ENGINEER. REFER TO THE POWER RISER DIAGRAM ON DRAWING E-500 AND THE PANEL SCHEDULES FOR ADDITIONAL INFORMATION. 2 PROVIDE WIRING DEVICES AS SHOWN. BASEMENT: PROVIDE SURFACE MOUNT METAL BACKBOXES AND CIRCUIT WITH 2#12, 1#12GND, 3/4" EMT. FIRST FLOOR: PROVIDE FLUSH METAL BACKBOXES IN WALLS/BASEBOARD AND CIRCUIT WITH 2#12 PLUS GROUND METAL-CLAD. CONCEAL FIRST FLOOR BRANCH CIRCUITRY WITHIN WALLS, FLOORS, AND CEILINGS. PROVIDE PANEL AND CIRCUIT LABELS ON EACH COVERPLATE. PROVIDE 1-HOUR FIRE RATED FLOOR PENETRATIONS. REFER TO DETAIL #1/E-504 FOR ADDITIONAL INFORMATION. 3 REFER TO THE PANELBOARD SCHEDULES AND THE EQUIPMENT CONNECTION SCHEDULE ON DRAWING E-503 FOR BRANCH CIRCUIT, MOTOR STARTER, AND DISCONNECT INFORMATION. PROVIDE A PLASTIC ID TAG ON ALL EQUIPMENT. 4 PROVIDE JUNCTION BOX AND FASTEN TO THE WOOD JOISTS. REFER TO THE POWER RISER DIAGRAM FOR JUNCTION BOX SIZES. 5 INSTALL FEEDERS ON CEILING. REFER TO THE POWER RISER DIAGRAM FOR ADDITIONAL INFORMATION. 6 PROVIDE 1-HOUR FIRE RATED FLOOR PENETRATION. REFER TO DETAIL #1/E-504 FOR ADDITIONAL INFORMATION. 7 CIRCUIT PLUGMOLD WITH 2#12, 1#12GND, 3/4" EMT. PROVIDE 1-HOUR FIRE RATED FLOOR PENETRATIONS. REFER TO DETAIL #1/E-504 FOR ADDITIONAL INFORMATION. 8 PROVIDE WIRING DEVICES AS SHOWN. LOCATE RECEPTACLES WITHIN CORD LENGTH OF AIR CONDITIONERS. CIRCUIT WITH 2#12 PLUS GROUND METAL CLAD AND CONCEAL BRANCH CIRCUITRY WITHIN WALLS, FLOORS, AND CEILINGS. 9 RECEPTACLES AND PLUGMOLD WITHIN ROOMS 103, 103A, 103B, AND 100TA SHALL BE PROTECTED BY AFCI CIRCUIT BREAKERS. 10 REMOVE PORTION OF PLASTER WALL AS NEEDED TO INSTALL PANEL LLP-23 FEEDER (FROM BASEMENT TO SECOND FLOOR). PATCH PLASTER WALL AND PAINT. 11 REMOVE PORTION OF GYPSUM WALL AS NEEDED TO INSTALL PANEL LLP-22 FEEDER (FROM BASEMENT TO SECOND FLOOR). INCLUDES THE REMOVAL AND REINSTALLATION OF THE KITCHEN 102 UPPER CABINETS, LOWER CABINETS, AND LAMINATE COUNTERTOP TO ACCOMMODATE THE WORK. PATCH AND PAINT WALL AFTER REINSTALLATION OF CABINETS AND COUNTERTOP. 12 REMOVE PORTION OF PLASTER WALL AS NEEDED TO INSTALL PANEL LLP-21 FEEDER (FROM BASEMENT TO SECOND FLOOR). PATCH PLASTER WALL AND PAINT. 13 ALL RECEPTACLES IN KITCHEN 102 TO BE GFCI TYPE. 14 RECEPTACLES WITHIN ROOMS 103, 103A, 103B, AND 100TA SHALL BE TAMPER RESISTANT. 15 MAINTAIN THE EXISTING MDP AND PROVIDE AN ENCLOSED CIRCUIT BREAKER AND FEEDER TO TEMPORARILY FEED THE NEW MDP DURING CONSTRUCTION. REFER TO THE POWER RISER DIAGRAM ON DRAWING E-500 FOR ADDITIONAL INFORMATION. 16 INSTALL NEW ELECTRIC METER FURNISHED BY CORNELL. REFER TO THE POWER RISER DIAGRAM ON DRAWING E-500 FOR ADDITIONAL INFORMATION. 17 AFTER SWITCHOVER OF NEW MDP FEEDER AND REMOVAL OF OLD MDP, REWORK THE EXISTING POWERSCOUT ELECTRIC METER CT'S TO METER THE NEW MDP FEEDER. REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION 200TC 200CA 200CC204 201 213 212 211A 214 215 217 218 223 220 207 208 210 200CB200SC200TA200TD200J 100SB 200SE 200SA 200SD 223APORCH211 212A 214A 208A 204A OPEN TO BELOW UP UP UP DN DN DN BSRSRSR SR SR B BCUH-9 CUH-10 CUH-8 CUH-7 CUH-5 CUH-6 CUH-2 CUH-3 CUH-4 CUH-18 SRB48"SPSP SP 200SD 304 302 300T 301 307 308 309 310 300J 312 CRAWL SPACE 304A 300SA 301A 301C 301B 310A 300CA 300CB DN DN B B B CUH-16 CUH-15 CUH-17 CUH-14 CUH-13 EF-1 CUH-12 CUH-11BB M PANEL LLP-21 PM PM PM PM PM PM PM PM PM PM PM PM PM PM PM PM PM PM PM PM LLP-22 LLP-23 LLP-21-10 LLP-21-12 LLP-21-11 LLP-21-15 LLP-21-9 LLP-21-10 LLP-21-5 LLP-21-18 LLP-21-8 LLP-21-14 LLP-21-3 LLP-22-5 LLP-22-2 LLP-21-1 LLP-22-4 LLP-22-6 LLP-22-6 LLP-22-3 LLP-23-2 LLP-23-3 LLP-23-4 LLP-23-5 LLP-21-8 1 3 4 6 7 PANEL LLP-21 DOWN TO FIRST FLOOR 5 TYP 2 1 TYP TYP 8 LLP-22-1 9 BID ALTERNATE E-2 BID ALTERNATE E-1 BID ALTERNATE E-2 BID ALTERNATE E-1 LLP-31 PM PM PM PM PM PM PM PM PM PM PM PM PM LLP-31-12 LLP-31-14 LLP-31-2 LLP-31-10 LLP-31-7 LLP-31-10 LLP-31-8 LLP-31-5 LLP-31-15 LLP-31-15 LLP-31-11 LLP-31-3 LLP-31-12 LLP-31-9 LLP-31-4 LLP-31-6 LLP-31-4 3 TYP 6 TYP 4 TYP 2 7 8 N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseE-101 POWER PLANS - SECOND AND THIRD FLOORSAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 0 4 8 16 SCALE: 1/8"=1'-0" 0 4 8 16 SCALE: 1/8"=1'-0" E-101 KEYED CONSTRUCTION NOTES 1 PROVIDE PANELBOARD AND FASTEN TO PLASTER WALL USING TAPCON FASTENERS. INSTALL ARC FLASH LABELS FURNISHED BY ENGINEER. REFER TO THE POWER RISER DIAGRAM ON DRAWING E-500 AND THE PANEL SCHEDULES FOR ADDITIONAL INFORMATION. LOCATE LLP-21 PANELBOARD IN FRONT OF DOOR TO ACHIEVE CODE REQUIRED WORKING SPACE. 2 PROVIDE PANELBOARD AND INSTALL FLUSH WITH PLASTER WALL. INSTALL ARC FLASH LABELS FURNISHED BY ENGINEER. REFER TO THE POWER RISER DIAGRAM ON DRAWING E-500 AND THE PANEL SCHEDULES FOR ADDITIONAL INFORMATION. 3 PROVIDE WIRING DEVICES AS SHOWN. WIRING DEVICES INSTALLED IN WOODEN BASE: PROVIDE FLUSH METAL BACKBOXES AND CIRCUIT WITH 2#12 PLUS GROUND METAL CLAD AND CONCEAL BRANCH CIRCUITRY WITHIN WOOD BASE. DEVICES INSTALLED ON WALLS: PROVIDE METALLIC SURFACE RACEWAY AND PAINT TO MATCH SURROUNDING SURFACES. PROVIDE PANEL AND CIRCUIT LABELS ON EACH COVERPLATE. PROVIDE 1-HOUR FIRE RATED FLOOR PENETRATION. REFER TO DETAIL #1/E-504 FOR ADDITIONAL INFORMATION. 4 REFER TO THE PANELBOARD SCHEDULES AND THE EQUIPMENT CONNECTION SCHEDULE ON DRAWING E-503 FOR BRANCH CIRCUIT, MOTOR STARTER, AND DISCONNECT INFORMATION. PROVIDE A PLASTIC ID TAG ON ALL EQUIPMENT. 5 PROVIDE 1-HOUR FIRE RATED FLOOR PENETRATION. REFER TO DETAIL #1/E-504 FOR ADDITIONAL INFORMATION. 6 CIRCUIT PLUGMOLD WITH 2#12, 1#12GND, 3/4" EMT. PROVIDE 1-HOUR FIRE RATED FLOOR PENETRATION. REFER TO DETAIL #1/E-504 FOR ADDITIONAL INFORMATION. 7 REMOVE PORTIONS OF PLASTER WALL TO ACCOMMODATE A FLUSH PANELBOARD BACKBOX. PROVIDE WITH AN OVERSIZED DOOR TRIM TO CONCEAL WITH ROUGH OPENING. PATCH PLASTER WALL AND PAINT. 8 REMOVE PORTION OF GYPSUM WALL AS NEEDED TO INSTALL PANEL LLP-23 AND 31 FEEDERS (FROM FIRST FLOOR TO THIRD FLOOR). INCLUDES THE REMOVAL AND REINSTALLATION OF THE UPPER CABINETS, LOWER CABINETS, AND LAMINATE COUNTERTOP TO ACCOMMODATE THE WORK. 9 FLUSH MOUNT SURGE PROTECTIVE DEVICE. PROVIDE WITH A PAINTED METAL TRIM TO CONCEAL ROUGH-OPENING. # SCALE: 1/8" = 1'-0"1 POWER PLAN - SECOND FLOOR SCALE: 1/8" = 1'-0"2 POWER PLAN - THIRD FLOOR REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION B00UB B00UC B11 B13 B13C B13B B13A B04 B07 B02 B05 B00T B03 B01 B14 B00SB B00SA B00UA B09 PIT CRAWL SPACE CRAWL SPACE B00C UP UP UPWWWWW W W WW W WW W WWW WW W W WTC TC 100TB 100SC 100SA 100SB 100JA 113 113A 114 108 112 109 101 110 103 100TA 103A 103B 102 102A 100CA 100CB 100JB 111 ENCLOSED PORCH PORCH PORCH PATIO 114A DN UP DN DN DN DN UP DN W W W W WW W W W WWWWWWWWWWDWWWWWWWW W W W4 DWWW D R WMDP LLP-B3 LLP-B1 LLP-B1-2 LLP-B2-3 LLP-B2 LLP-B3-1 TO FIRST FLOOR STAIRS SWITCH LLP-B2-18 1 4 TYP 2 TYP OS V OS V OS V OS O OS O OS O OS O OS O OS V OS O OS V OS O OS V OS O OS O OS O OS O 5 TYP OS O OS O OS O NL 12 12 NL TC-1 13 TC-213 1 1 1 1 1 1 1 1 OS O OS O OS O OS O OS O OS O OS O OS O OS O OS O OS V LLP-B1-13 LLP-B1-13 LLP-B1-13 LLP-B1-13 LLP-B1-13 LLP-B3-6 LLP-B3-6 LLP-B2-6 LLP-B2-6 LLP-B2-24 LLP-B2-5 LLP-B2-6 LLP-B3-6 DS UP TO 2ND FLOOR OS O TO BASEMENT LIGHTS TO 2ND FLOOR LIGHTS OS V OS O OS V EXISTING COVE LIGHTING EXISTING COVE LIGHTING 6 7 3 TYP 4 TYP 2 TYP 5 TYP 9 10 10 10 11 8 1 1 LLP-B3-8 LLP-B1-11 14 14 14 LLP-B2-24 15 PC 16 DS DS DS N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseE-200 LIGHTING PLANS - BASEMENT AND FIRST FLOORAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 SCALE: 1/8" = 1'-0"1 LIGHTING PLAN - BASEMENT E-200 KEYED CONSTRUCTION NOTES 1 PROVIDE A WIRELESS LIGHTING CONTROLS GATEWAY AND MOUNT HORIZONTALLY ON WALL. COORDINATE LOCATION WITH LIGHTING CONTROLS MANUFACTURER FOR COMPLETE COVERAGE. PROVIDE A DATA CONNECTION TO THE DATA RACK IN ROOM B03. PROVIDE ALL DATA CABLING, JACKS, TERMINATIONS, PATCH PANEL ACCESSORIES, AND CABLE TESTING. REFER TO THE DETAIL #1/E-504 FOR ADDITIONAL INFORMATION. PROVIDE ADDITIONAL WIRELESS GATEWAYS AS REQUIRED TO PROVIDE COMPLETE COVERAGE, INCLUDING ALL NECESSARY POWER AND DATA. PROVIDE ALL REQUIRED PROGRAMMING AND SYSTEM COMMISSIONING. COORDINATE TELCO WORK WITH CIT. 2 AT EACH LOCATION, PROVIDE A SINGLE-GANG METAL DEVICE BOX WITH A WIRELESS WALL-MOUNT SWITCH. 3 AT EACH LOCATION, PROVIDE A SCONCE LUMINAIRE. MATCH HEIGHT OF DEMOLISHED SCONCES. REFER TO THE LUMINAIRE SCHEDULE FOR ADDITIONAL INFORMATION. 4 PROVIDE A WIRELESS LUMINAIRE CONTROLLER FOR ALL INTERIOR LUMINAIRES SHOWN. CONTRACTOR SHALL DETERMINE WHICH CONTROLLER (INTERNAL OR EXTERNAL MOUNT) TO USE IN-FIELD. 5 PROVIDE WIRELESS MOTION SENSORS AS SHOWN. PROGRAM AS OCCUPANCY OR VACANCY PER PLANS. SECURELY FASTEN TO WALL OR CEILING. LOCATE DEVICES TO PROVIDE MAXIMUM SENSOR COVERAGE. 6 PROVIDE A WIRELESS, REMOTE SWITCH. FASTEN TO WALL USING DOUBLE-SIDED TAPE. 7 INSTALL LIGHTING BRANCH CIRCUITRY FROM FLOOR ABOVE. REFER TO DRAWING ED-101 FOR ADDITIONAL INFORMATION. 8 CONNECT WIRELESS SWITCH TO THE SECOND FLOOR STAIR LIGHTING. 9 AT APARTMENT, PROVIDE A SINGLE-GANG FLUSH DEVICE BOX WITH A WIRELESS WALL-MOUNT SWITCH. PROVIDE A WIRELESS PLUG LOAD CONTROLLER AT ONE OF THE RECEPTACLES IN ROOM 103 TO CONTROL A TABLE LAMP. COORDINATE RECEPTACLE WITH BUILDING COORDINATOR. 10 CONNECT WIRELESS WALL-MOUNT SWITCHES TO (9) EXISTING UNDERCABINET LIGHTS. ASSOCIATE EACH WALL OF LIGHTS TO THE RESPECTIVE WIRELESS SWITCH. 11 CONNECT WIRELESS SWITCH AND EXISTING LIGHT TO THE BASEMENT LIGHTING CIRCUIT. 12 NIGHT LIGHT: CIRCUIT TO THE UNSWITCHED PHASE CONDUCTOR OF THE LIGHTING BRANCH CIRCUIT SERVING THE SPACE. 13 PROVIDE A DIGITAL TIMECLOCK AND CIRCUIT AS SHOWN. REFER TO DETAIL #3/E-504 FOR ADDITIONAL INFORMATION. 14 PROVIDE A DIGITAL SWITCH AND CIRCUIT TO THE RESPECTIVE DIGITAL TIMECLOCK. INSTALL LIGHTING BRANCH CIRCUITRY THRU THE TIMECLOCK RELAY. REFER TO DETAIL #3/E-504 FOR ADDITIONAL INFORMATION. 15 PROVIDE UNSWITCHED PHASE CONDUCTOR FROM BRANCH CIRCUIT INDICATED. INSTALL LIGHTING BRANCH CIRCUITRY THRU THE TIMECLOCK RELAY. REFER TO DETAIL #3/E-504 FOR ADDITIONAL INFORMATION. 16 PROVIDE AN OUTDOOR RATED PHOTOCELL WITH A WEATHERPROOF, SINGLE-GANG BOX WITH GASKETED COVERPLATE. INSTALL ON PORCH FASCIA AND PAINT BOX TO MATCH FASCIA. SURFACE MOUNT CONDUIT WITHIN ENCLOSED PORCH WOOD CEILING. PAINT CONDUIT TO MATCH PORCH CEILING. REFER TO DETAIL #3/E-504 FOR ADDITIONAL INFORMATION. # 0 4 8 16 SCALE: 1/8"=1'-0" 0 4 8 16 SCALE: 1/8"=1'-0" SCALE: 1/8" = 1'-0"2 LIGHTING PLAN - FIRST FLOOR LIGHTING CIRCUITING/CONTROLS NOTE: 1.BRANCH CIRCUITING SHOWN TO WIRELESS SWITCHES IS FOR REFERENCE ONLY AND IS USED TO CLEARLY INDICATE LUMINAIRE GROUPINGS AND SWITCHING. 2.WIRELESS SWITCHES ARE CONSTRUCTED WITH DIMMING CONTROLS. EXISTING LUMINAIRES ARE FLUORESCENT AND DO NOT UTILIZE DIMMING BALLASTS. WIRELESS SWITCH DIMMING FEATURE IS FOR FUTURE USE. LIGHTING CIRCUITING/CONTROLS NOTE: 1.BRANCH CIRCUITING SHOWN TO WIRELESS SWITCHES IS FOR REFERENCE ONLY AND IS USED TO CLEARLY INDICATE LUMINAIRE GROUPINGS AND SWITCHING. 2.WIRELESS SWITCHES ARE CONSTRUCTED WITH DIMMING CONTROLS. EXISTING LUMINAIRES ARE FLUORESCENT AND DO NOT UTILIZE DIMMING BALLASTS. WIRELESS SWITCH DIMMING FEATURE IS FOR FUTURE USE. 3.EXISTING FLUORESCENT LUMINAIRES DO NOT UTILIZE DIMMING BALLASTS. WIRELESS DAYLIGHT SENSORS SPECIFIED FOR THESE SPACES ARE FOR FUTURE USE. REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION 200TC 200CA 200CC204 201 213 212 211A 214 215 217 218 223 220 207 208 210 200CB200SC200TA200TD200J 100SB 200SE 200SA 200SD 223APORCH211 212A 214A 208A 204A OPEN TO BELOW UP UP UP DN DN DN W W W WW WWWWWWWW WWWWWWWWWWWWWRRRRR RRR200SD 304 302 300T 301 307 308 309 310 300J 312 CRAWL SPACE 304A 300SA 301A 301C 301B 310A 300CA 300CB DN DN W W WWW WW WW W RW R R RPANEL LLP-21 LLP-22 LLP-23 LLP-21-4 LLP-21-4 LLP-21-4 LLP-21-6 LLP-21-7 LLP-21-6 LLP-21-6 LLP-21-6 LLP-21-2 LLP-23-6 LLP-23-6 LLP-23-6 LLP-23-6 LLP-23-1 LLP-23-7 LLP-23-6 LLP-23-7 LLP-23-7 5OS V OS O OS O OS V OS V OS V OS O OS O DOWN TO FIRST FLOOR OS O OS O OS O OS O OS V OS V 5 5 OS V OS O OS O OS V OS O OS O OS O OS O OS O OS O OS O OS O OS O OS V OS VDOWN TO FIRST FLOOR DOWN TO FIRST FLOOR LLP-21-7 LLP-21-7 OS V LLP-23-1 LLP-21-13 LLP-23-8 1 5 5 5 1 3 2 4 TYP TYP TYP 5 1 1 1 1 1 1 1 1 1 DS DS DS DS DS DS DS BID ALTERNATE E-2 BID ALTERNATE E-1 BID ALTERNATE E-2 BID ALTERNATE E-1 LLP-23-1 LLP-31 LLP-31-1 LLP-31-6 LLP-31-6 LLP-31-1 LLP-31-6 LLP-31-6 LLP-31-18 LLP-31-18 LLP-31-18 DOWN TO SECOND FLOOR OS O OS O OS O OS O OS O OS V OS O OS O OS O OS O OS O OS O OS V OS V OS V OS O LLP-31-13 5 5 5 5 3 TYP 1 2 TYP 4 TYP DS DS N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseE-201 LIGHTING PLANS - SECOND AND THIRD FLOORSAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 # 0 4 8 16 SCALE: 1/8"=1'-0" 0 4 8 16 SCALE: 1/8"=1'-0" SCALE: 1/8" = 1'-0"1 LIGHTING PLAN - SECOND FLOOR SCALE: 1/8" = 1'-0"2 LIGHTING PLAN - THIRD FLOOR E-201 KEYED CONSTRUCTION NOTES 1 PROVIDE A WIRELESS LIGHTING CONTROLS GATEWAY AND MOUNT HORIZONTALLY ON WALL. COORDINATE LOCATION WITH LIGHTING CONTROLS MANUFACTURER FOR COMPLETE COVERAGE. PROVIDE A DATA CONNECTION TO THE DATA RACK IN ROOM B03. PROVIDE ALL DATA CABLING, JACKS, TERMINATIONS, PATCH PANEL ACCESSORIES, AND CABLE TESTING. REFER TO THE DETAIL #1/E-504 FOR ADDITIONAL INFORMATION. PROVIDE ADDITIONAL WIRELESS GATEWAYS AS REQUIRED TO PROVIDE COMPLETE COVERAGE, INCLUDING ALL NECESSARY POWER AND DATA. PROVIDE ALL REQUIRED PROGRAMMING AND SYSTEM COMMISSIONING. COORDINATE TELCO WORK WITH CORNELL. 2 AT EACH LOCATION, PROVIDE A SINGLE-GANG METAL DEVICE BOX WITH A WIRELESS WALL-MOUNT SWITCH. 3 PROVIDE A WIRELESS LUMINAIRE CONTROLLER FOR ALL INTERIOR LUMINAIRES SHOWN. CONTRACTOR SHALL DETERMINE WHICH CONTROLLER (INTERNAL OR EXTERNAL MOUNT) TO USE IN-FIELD. 4 PROVIDE WIRELESS MOTION SENSORS AS SHOWN. PROGRAM AS OCCUPANCY OR VACANCY PER PLANS. SECURELY FASTEN TO WALL OR CEILING. LOCATE DEVICES TO PROVIDE MAXIMUM SENSOR COVERAGE. 5 PROVIDE A WIRELESS, REMOTE SWITCH. FASTEN TO WALL USING DOUBLE-SIDED TAPE. REMOVE CEILING MOUNT LUMINAIRE AND PROVIDE A 4x4 SURFACE J-BOX (TO INSTALL WIRELESS LUMINAIRE CONTROLLER) AND REINSTALL LUMINAIRE. LIGHTING CIRCUITING/CONTROLS NOTE: 1.BRANCH CIRCUITING SHOWN TO WIRELESS SWITCHES IS FOR REFERENCE ONLY AND IS USED TO CLEARLY INDICATE LUMINAIRE GROUPINGS AND SWITCHING. 2.WIRELESS SWITCHES ARE CONSTRUCTED WITH DIMMING CONTROLS. EXISTING LUMINAIRES ARE FLUORESCENT AND DO NOT UTILIZE DIMMING BALLASTS. WIRELESS SWITCH DIMMING FEATURE IS FOR FUTURE USE. 3.EXISTING FLUORESCENT LUMINAIRES DO NOT UTILIZE DIMMING BALLASTS. WIRELESS DAYLIGHT SENSORS SPECIFIED FOR THESE SPACES ARE FOR FUTURE USE. LIGHTING CIRCUITING/CONTROLS NOTE: 1.BRANCH CIRCUITING SHOWN TO WIRELESS SWITCHES IS FOR REFERENCE ONLY AND IS USED TO CLEARLY INDICATE LUMINAIRE GROUPINGS AND SWITCHING. 2.WIRELESS SWITCHES ARE CONSTRUCTED WITH DIMMING CONTROLS. EXISTING LUMINAIRES ARE FLUORESCENT AND DO NOT UTILIZE DIMMING BALLASTS. WIRELESS SWITCH DIMMING FEATURE IS FOR FUTURE USE. 3.EXISTING FLUORESCENT LUMINAIRES DO NOT UTILIZE DIMMING BALLASTS. WIRELESS DAYLIGHT SENSORS SPECIFIED FOR THESE SPACES ARE FOR FUTURE USE. REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION B00UB B00UC B11 B13 B13C B13B B13A B04 B07 B02 B05 B00T B03 B01 B14 B00SB B00SA B00UA B09 PIT CRAWL SPACE CRAWL SPACE B00C UP UP UP 136 208 293 385 237 792 387 591 590 229 561 269 108 46 73 51 47 15 19 91 38 44 90 10 UP 100TB 100SC 100SA 100SB 100JA 113 113A 114 108 112 109 101 110 103 100TA 103A 103B 102 102A 100CA 100CB 100JB 111 ENCLOSED PORCH PORCH PORCH PATIO 114A DN UP DN DN DN DN UP DN X2 X4 X3 X3 X4 1 TYP X3 X4 X4 X1 X3 X3 X3 X3 X4 X4 X5 X5 X3 1 TYP 2 2 X1 X5 3 4 X4 N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseE-300 EGRESS LIGHTING PLANS - BASEMENT AND FIRST FLOORSAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 SCALE: 1/8" = 1'-0"1 EGRESS LIGHTING PLAN - BASEMENT SCALE: 1/8" = 1'-0"2 EGRESS LIGHTING PLAN - FIRST FLOOR 0 4 8 16 SCALE: 1/8"=1'-0" 0 4 8 16 SCALE: 1/8"=1'-0" #E-300 KEYED CONSTRUCTION NOTES 1 CIRCUIT EMERGENCY EGRESS LIGHTS AND EXIT SIGNS FROM THE UNSWITCHED LIGHTING BRANCH CIRCUIT SERVING THE SPACE IN WHICH IT IS INSTALLED FOR POWER SENSING AND CHARGING. CIRCUIT WITH 2#12, 1#12GND, 3/4" EMT IN A DEDICATED RACEWAY - NO OTHER BRANCH CIRCUITRY MAY BE PULLED IN THESE RACEWAYS. TYPICAL FOR ALL EMERGENCY EGRESS LIGHTS AND EXIT SIGNS. 2 CIRCUIT REMOTE HEADS TO THE NEAREST EMERGENCY LIGHTING BATTERY UNIT. COREDRILL WALL AND PATCH PENETRATIONS. 3 CIRCUIT REMOTE HEADS TO THE NEAREST EMERGENCY LIGHTING BATTERY UNIT. COREDRILL WALL AND PATCH PENETRATION. CENTER REMOTE HEADS ON BRICK WALL, BELOW LIMESTONE BALCONY SUPPORT (+/- 6'-0" ABOVE LANDING). 4 REMOVE PORTION OF PLASTER WALL AS NEEDED TO CONCEAL TYPE X5 REMOTE HEAD CIRCUITRY. PATCH PLASTER WALL AND PAINT. REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION 200TC 200CA 200CC204 201 213 212 211A 214 215 217 218 223 220 207 208 210 200CB200SC200TA200TD200J 100SB 200SE 200SA 200SD 223APORCH211 212A 214A 208A 204A OPEN TO BELOW UP UP UP DN DN DN 200SD 304 302 300T 301 307 308 309 310 300J 312 CRAWL SPACE 304A 300SA 301A 301C 301B 310A 300CA 300CB DN DN X2 X4 X4 X3 X3 X3 1 TYP X4 X2 X2 X4 BID ALTERNATE E-2 BID ALTERNATE E-1 BID ALTERNATE E-2 BID ALTERNATE E-1 X3 X3 X4 1 TYP X1 N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseE-301 EGRESS LIGHTING PLANS - SECOND AND THIRD FLOORSAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 0 4 8 16 SCALE: 1/8"=1'-0" 0 4 8 16 SCALE: 1/8"=1'-0" SCALE: 1/8" = 1'-0"1 EGRESS LIGHTING PLAN - SECOND FLOOR SCALE: 1/8" = 1'-0"2 EGRESS LIGHTING PLAN - THIRD FLOOR E-301 KEYED CONSTRUCTION NOTES 1 CIRCUIT EMERGENCY EGRESS LIGHTS AND EXIT SIGNS FROM THE UNSWITCHED LIGHTING BRANCH CIRCUIT SERVING THE SPACE IN WHICH IT IS INSTALLED FOR POWER SENSING AND CHARGING. CIRCUIT WITH 2#12, 1#12GND, 3/4" EMT IN A DEDICATED RACEWAY - NO OTHER BRANCH CIRCUITRY MAY BE PULLED IN THESE RACEWAYS. TYPICAL FOR ALL EMERGENCY EGRESS LIGHTS AND EXIT SIGNS. # REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION B00UB B00UC B11 B13 B13C B13B B13A B04 B07 B02 B05 B00T B03 B01 B14 B00SB B00SA B00UA B09 PIT CRAWL SPACE CRAWL SPACE B00C UP UP UP 100TB 100SC 100SA 100SB 100JA 113 113A 114 108 112 109 101 110 103 100TA 103A 103B 102 102A 100CA 100CB 100JB 111 ENCLOSED PORCH PORCH PORCH PATIO 114A DN UP DN DN DN DN UP DN THRU WALL TO BELOW FINISHED GRADE (REFER TO DETAIL #2/E-400 FOR CONTINUATION) METAL UNDERGROUND WATER PIPE GROUND ELECTRODE PANEL MDP GROUNDING ELECTRODE CONDUCTOR GROUNDING ELECTRODE CONDUCTOR 1 2 3 2 4 7 7 8 8 TELCO GROUND BAR (TGB) TELCO GROUND BAR (TGB) 7 TELCO GROUND BAR (TMGB)8' - 0"6' - 0"14' - 0"SUPPLEMENTAL GROUND ROD ELECTRODES WITH TEST WELLS THRU WALL TO BASEMENT PANEL MDP (REFER TO DETAIL #1/E-400 FOR CONTINUATION) 5 6UEUE N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseE-400 GROUNDING AND BONDING PLANAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 0 4 8 16 SCALE: 1/8"=1'-0" 0 4 8 16 SCALE: 1/8"=1'-0" SCALE: 1/8" = 1'-0"1 GROUNDING/BONDING PLAN - BASEMENT SCALE: 1/8" = 1'-0"2 GROUNDING AND BONDING PLAN - FIRST FLOOR E-400 KEYED CONSTRUCTION NOTES 1 PROVIDE A #2 CU BARE MAIN BONDING JUMPER IN PANEL MDP AND BOND THE NEUTRAL BUS TO THE GROUND BUS. 2 PROVIDE A #2 CU BARE GROUNDING ELECTRODE CONDUCTOR (GEC) AS SHOWN. INSTALL GEC CONTINUOUS WITH NO SPLICES. INSTALL IN 1" EMT RACEWAY SECURELY FASTENED TO THE CEILING JOISTS. 3 BOND THE GEC TO THE EXISTING WATER MAIN. PROVIDE #2 CU BARE JUMPERS AS NEEDED. 4 COREDRILL STONE FOUNDATION FOR GEC TO SUPPLEMENTAL GROUND RODS. PROVIDE A 1" RGS NIPPLE AND MORTAR INTO FOUNDATION WALL. WEATHERSTOP THE NIPPLE AFTER GEC INSTALLATION. 5 BURY GEC A MINIMUM OF 18" BELOW FINISHED GRADE. PROVIDE A METALLIC TAPE 12" BELOW FINISHED GRADE. RESTORE LAWN AND RESEED. 6 PROVIDE 3/4"x10' COPPER CLAD STEEL GROUND RODS WITH HDPE GROUND ACCESS WELLS (WITH COVERS). 7 PROVIDE A COPPER GROUND BAR AND INSTALL 18" AFF. LABEL GROUND BAR AT MDP 'TMGB'. LABEL GROUND BARS AT DATA ROOMS B03 AND B05 'TGB'. 8 PROVIDE A #2 CU BARE TELCO BONDING JUMPER AS SHOWN. INSTALL BONDING JUMPER CONTINUOUS WITH NO SPLICES. INSTALL IN 1" EMT RACEWAY SECURELY FASTENED TO THE CEILING JOISTS. # REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION J 250A 125A 125A J PANEL LP-1 BASEMENT SECOND FLOOR HALL PANEL THIRD FLOOR HALL PANEL BATHROOM POWER PANEL CLOSET POWER PANEL J PANEL LP-3 PANEL SNO-MELT 60/2 PANEL LP- 4 100/2 PANEL LP- 5 BUS TAP BUS TAP XFMR 37.5-KVA PRI: 2.4kV SEC: 240/120V MDP 120/240V, 1-PHASE, 3-WIRE 400A RATED BUS SPARE J PANEL LP-2 J60A SWITCH (ROOM B07) JB1 JB2 JB3 JB4 JB5 PANEL EM BUS TAP FIRST FLOOR SECOND FLOOR THIRD FLOOR 225A/2P BASEMENT FIRST FLOOR SECOND FLOOR THIRD FLOOR XFMR 37.5-KVA PRI: 2.4kV SEC: 240/120V MDP 120/240V, 1-PHASE, 3-WIRE 225A MCB LLP-B1 120/240V 42 CIRCUIT 100A MCB SURFACE 10K AIC 1Ø, 3-WIRE 100A/2P LLP-B2 120/240V 42 CIRCUIT 100A MCB SURFACE 10K AIC 1Ø, 3-WIRE 100A/2P C C LLP-B3 120/240V 42 CIRCUIT 60A MCB SURFACE 10K AIC 1Ø, 3-WIRE B A C LLP-22 120/240V 42 CIRCUIT 100A MCB SURFACE 10K AIC 1Ø, 3-WIRE B LLP-23 120/240V 42 CIRCUIT 60A MCB SURFACE 10K AIC 1Ø, 3-WIRE LLP-31 120/240V 42 CIRCUIT 60A MCB SURFACE 10K AIC 1Ø, 3-WIRE B 60A/2P 100A/2P 60A/2P B LLP-21 120/240V 42 CIRCUIT 60A MCB SURFACE 10K AIC 1Ø, 3-WIRE 60A/2P JUNCTION BOX J-1 (12"x12"x6") JUNCTION BOX J-2 12"X12"X6") SP-2 30A/2P SURGE PROTECTION AT MDP SIMILAR TO VERTIV/ASCO MODEL 440 TYPE 1 WITH STEEL ENCLOSURE (SP-1) SURGE PROTECTION AT PANELS SIMILAR TO VERTIV/ASCO MODEL 425 TYPE 2 (TYPICAL FOR SP-2) D E E E E E E SP-2 SP-2 SP-2 SP-2 SP-2 SP-1 TEMPORARY MDP FEED: PROVIDE A 225A/2P SERVICE ENTRANCE CIRCUIT BREAKER RATED FOR 10K AIC IN A NEMA 1 ENCLOSURE. PROVIDE TEMPORARY FEEDER TYPE 'A' FROM EXISTING MDP. MAINTAIN THE EXISTING MDP UNTIL NEW MDP AND ALL PANELBOARDS ARE REPLACED AND ALL BUILDING LOADS HAVE BEEN REFED FROM NEW PANELBOARDS. AFTER CONSTRUCTION, DISCONNECT AND REMOVE THE ENCLOSED CIRCUIT BREAKER AND PROVIDE THE PERMANENT FEEDER TYPE 'A'. M INSTALL NEW METER SOCKET FURNISHED BY CORNELL M MAINTAIN EXISTING POWERSCOUT REVENUE ELECTRIC METER - REWORK CT'S ONCE NEW MDP IS INSTALLED AND SWITCHOVER IS COMPLETE N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseE-500 ONE-LINE DIAGRAMSAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 SCALE:NO SCALE1DEMOLITION ONE-LINE DIAGRAM FEEDER SCHEDULE TYPE PHASE NEUTRAL GROUND RACEWAY NOTES A 2#4/0 1#4/0 1#2 2" EMT B 2#6 1#6 1#10 1" EMT C 2#2 1#2 1#8 1.25" EMT D 2#10 1#10 1#10 3/4" EMT TWIST CONDUCTORS TOGETHER TO REDUCE IMPEDANCE PER MANUF.; KEEP CONDUCTORS LESS THAN 24" IN LENGTH E 2#12 1#12 1#12 3/4" EMT TWIST CONDUCTORS TOGETHER TO REDUCE IMPEDANCE PER MANUF.; KEEP CONDUCTORS LESS THAN 24" IN LENGTH SCALE:NO SCALE2POWER RISER DIAGRAM REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseE-501 PANELBOARD SCHEDULESAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 FIRE ALARM 700 VA 100.00% 700 VA APPLIANCE 17940 VA 35.00% 6279 VA TOTAL DEMAND AMPS:174 A ELECTRIC HEAT 17280 VA 35.00% 6048 VA TOTAL CONN AMPS:490 A RECEPTACLES 40420 VA 35.00% 14147 VA TOTAL DEMAND:41651 VA LIGHTING 17922 VA 35.00% 6273 VA TOTAL CONN LOAD:117702 VA HVAC 23440 VA 35.00% 8204 VA LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS TOTAL AMPS:511 A 470 A TOTAL LOAD:61354 VA 56348 VA 41 ---- -- 0 0 VA -- -- SPACE 42 39 SURGE PROTECTION DEVICE 30 2 0 VA 0 VA -- -- SPACE 40 37 SPACE -- -- 0 0 VA -- -- SPACE 38 35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36 33 SPACE -- -- 0 0 VA -- -- SPACE 34 31 SPACE -- -- 0 VA 0 VA -- -- SPACE 32 29 SPACE -- -- 0 0 VA -- -- SPACE 30 27 ---- -- 0 VA 0 VA -- -- --28 25 SPARE 20 2 0 0 VA 2 20 SPARE 26 23 ---- -- 0 VA 0 VA -- -- --24 21 SPARE 30 2 0 0 VA 2 30 SPARE 22 19 ---- -- 0 VA 0 VA -- -- --20 17 SPARE 40 2 0 0 VA 2 40 SPARE 18 15 ---- -- 0 VA 0 VA -- -- --16 13 SPARE 60 2 0 0 VA 2 60 SPARE 14 11 ---- -- 16180... 14872... -- -- --12 9 LLP-B1 60 2 13965 18826... 2 100 LLP-B2 10 7 ---- -- 7528 VA 11520... -- -- --8 5 LLP-21 60 2 10814 11556... 2 100 LLP-22 6 3 ---- -- 2930 VA 3318 VA -- -- --4 1 LLP-B3 60 2 3077 3116 VA 2 60 LLP-23 2 CKT DESCRIPTION TRIP POLES A B POLES TRIP DESCRIPTION CKT ENCLOSURE:TYPE 1 OPTIONS:SERVICE ENTRANCE RATED MOUNTING:SURFACE WIRES:3 MAINS RATING:225 A FED FROM:PHASE:1 MAINS TYPE:MCB LOCATION:B11 VOLTS:120/240V AIC RATING:10K PANEL MDP FIRE ALARM 350 VA 100.00% 350 VA TOTAL DEMAND AMPS:50 A APPLIANCE 16500 VA 35.00% 5775 VA TOTAL CONN AMPS:140 A RECEPTACLES 4600 VA 35.00% 1610 VA TOTAL DEMAND:12022 VA LIGHTING 4348 VA 35.00% 1522 VA TOTAL CONN LOAD:33698 VA HVAC 7900 VA 35.00% 2765 VA LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS TOTAL AMPS:157 A 124 A TOTAL LOAD:18826 VA 14872 VA 41 SPARE 20 1 0 0 VA -- -- --42 39 ---- -- 0 VA 0 VA 2 20 SURGE PROTECTION DEVICE 40 37 SUMP PUMP SP-1 20 2 1700 0 VA 1 20 SPARE 38 35 SPARE 20 1 0 VA 0 VA 1 20 SPARE 36 33 RCPT: 102 (FRIDGE) 20 1 1400 0 VA 1 20 SPARE 34 31 SPARE 20 1 0 VA 0 VA 1 20 SPARE 32 29 FCU-B6, B7 20 1 1200 0 VA 1 20 SPARE 30 27 RCPT: 102 (MICROWAVE) 20 1 1400 VA 0 VA -- -- --28 25 DISPOSAL 20 1 900 0 VA 2 20 SPARE 26 23 RCPTS: BASEMENT 20 1 900 VA 1200 VA 1 20 LTG: 2ND FLOOR 24 21 RCPTS: 102 (COUNTER) 20 1 720 700 VA 1 20 EF-B00UC 22 19 RCPTS: 102 (COUNTER) 20 1 360 VA 900 VA 1 20 RCPTS: 110 20 17 ---- -- 0 50 VA 1 20 WIRELESS LTG GATEWAY 18 15 RCPT: 102 (RANGE) 50 2 8300 VA 180 VA 1 20 RCPT: 110 (A/C) 16 13 RCPT: 110 (A/C) 20 1 180 360 VA 1 20 RCPTS: 102 (COUNTER) 14 11 ---- -- 0 VA 0 VA -- -- --12 9 CONN: B00UC (CP-1) 20 2 2000 4500 VA 2 25 WH-1 10 7 RCPTS: 102 20 1 360 VA 600 VA 1 20 FCU-B5 8 5 LTG: 2ND FLOOR 20 1 1328 1448 VA 1 20 LTG: 2ND FLOOR 6 3 LTG: BASEMENT 20 1 322 VA 350 VA 1 20 FACP (LOCKING HANDLE) 4 1 CONN: B02 (IRRIGATION PANEL) 20 1 100 540 VA 1 20 RCPTS: 101,112 2 CKT DESCRIPTION TRIP POLES A B POLES TRIP DESCRIPTION CKT ENCLOSURE:TYPE 1 OPTIONS: MOUNTING:SURFACE WIRES:3 MAINS RATING:100 A FED FROM:MDP PHASE:1 MAINS TYPE:MCB LOCATION:B00C VOLTS:120/240V AIC RATING:10K PANEL LLP-B2 TOTAL DEMAND AMPS:9 A TOTAL CONN AMPS:25 A TOTAL DEMAND:2102 VA RECEPTACLES 5040 VA 35.00% 1764 VA TOTAL CONN LOAD:6007 VA LIGHTING 967 VA 35.00% 338 VA LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS TOTAL AMPS:26 A 24 A TOTAL LOAD:3077 VA 2930 VA 41 SPARE 20 1 0 0 VA -- -- --42 39 SPARE 20 1 0 VA 0 VA 2 20 SURGE PROTECTION DEVICE 40 37 SPARE 20 1 0 0 VA 1 20 SPARE 38 35 SPARE 20 1 0 VA 0 VA 1 20 SPARE 36 33 SPARE 20 1 0 0 VA 1 20 SPARE 34 31 SPARE 20 1 0 VA 0 VA 1 20 SPARE 32 29 SPARE 20 1 0 0 VA 1 20 SPARE 30 27 SPARE 20 1 0 VA 0 VA 1 20 SPARE 28 25 SPARE 20 1 0 0 VA 1 20 SPARE 26 23 SPARE 20 1 0 VA 0 VA 1 20 SPARE 24 21 SPARE 20 1 0 0 VA 1 20 SPARE 22 19 SPARE 20 1 0 VA 0 VA 1 20 SPARE 20 17 ---- -- 0 0 VA 1 20 SPARE 18 15 SPARE 20 2 0 VA 0 VA 1 20 SPARE 16 13 RCPTS: B05 20 1 360 0 VA 1 20 SPARE 14 11 RCPTS: B05 20 1 360 VA 0 VA -- -- --12 9 RCPTS: 103 (AFCI) 20 1 1080 0 VA 2 20 SPARE 10 7 RCPTS: 103A (AFCI) 20 1 1080 VA 50 VA 1 20 WIRELESS LTG GATEWAY 8 5 RCPTS: B03 20 1 360 800 VA 1 20 LTG: 2ND FLOOR 6 3 RCPTS: 103B (AFCI) 20 1 720 VA 720 VA 1 20 RCPTS: BASEMENT 4 1 LTG: BASEMENT 20 1 117 360 VA 1 20 RCPTS: 100TA/103 (AFCI) 2 CKT DESCRIPTION TRIP POLES A B POLES TRIP DESCRIPTION CKT ENCLOSURE:TYPE 1 OPTIONS:AFCI BREAKERS MOUNTING:SURFACE WIRES:3 MAINS RATING:60 A FED FROM:MDP PHASE:1 MAINS TYPE:MCB LOCATION:B00SB VOLTS:120/240V AIC RATING:10K PANEL LLP-B3 TOTAL DEMAND AMPS:27 A TOTAL CONN AMPS:76 A RECEPTACLES 10080 VA 35.00% 3528 VA TOTAL DEMAND:6420 VA LIGHTING 4062 VA 35.00% 1422 VA TOTAL CONN LOAD:18342 VA HVAC 4200 VA 35.00% 1470 VA LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS TOTAL AMPS:90 A 63 A TOTAL LOAD:10814 VA 7528 VA 41 SPARE 20 1 0 0 VA -- -- --42 39 SPARE 20 1 0 VA 0 VA 2 20 SURGE PROTECTION DEVICE 40 37 SPARE 20 1 0 0 VA 1 20 SPARE 38 35 SPARE 20 1 0 VA 0 VA 1 20 SPARE 36 33 SPARE 20 1 0 0 VA 1 20 SPARE 34 31 SPARE 20 1 0 VA 0 VA 1 20 SPARE 32 29 SPARE 20 1 0 0 VA 1 20 SPARE 30 27 SPARE 20 1 0 VA 0 VA 1 20 SPARE 28 25 SPARE 20 1 0 0 VA 1 20 SPARE 26 23 SPARE 20 1 0 VA 0 VA 1 20 SPARE 24 21 SPARE 20 1 0 0 VA -- -- --22 19 ---- -- 0 VA 0 VA 2 20 SPARE 20 17 SPARE 20 2 0 1620 VA 1 20 RCPTS: 213 18 15 RCPTS: 217 20 1 1440 VA 0 VA 1 20 SPARE 16 13 WIRELESS LTG GATEWAY 20 1 50 1440 VA 1 20 RCPTS: 201 14 11 CUH'S (220/223) 20 1 1200 VA 1260 VA 1 20 RCPTS: 223 12 9 CUH'S (215/217) 20 1 1200 1260 VA 1 20 RCPTS: 214 10 7 LTG: 200CA 20 1 928 VA 1200 VA 1 20 CUH'S (213/214) 8 5 RCPTS: 215 20 1 1080 1224 VA 1 20 LTG: 2ND FLOOR 6 3 CUH (201) 20 1 600 VA 900 VA 1 20 LTG: 2ND FLOOR 4 1 RCPTS: 200CA/SC 20 1 360 960 VA 1 20 LTG: 2ND FLOOR 2 CKT DESCRIPTION TRIP POLES A B POLES TRIP DESCRIPTION CKT ENCLOSURE:TYPE 1 OPTIONS: MOUNTING:SURFACE WIRES:3 MAINS RATING:60 A FED FROM:MDP PHASE:1 MAINS TYPE:MCB LOCATION:200SC VOLTS:120/240V AIC RATING:10K PANEL LLP-21 TOTAL DEMAND AMPS:7 A TOTAL CONN AMPS:19 A RECEPTACLES 3420 VA 35.00% 1197 VA TOTAL DEMAND:1617 VA LIGHTING 0 VA 0.00% 0 VA TOTAL CONN LOAD:4620 VA HVAC 1200 VA 35.00% 420 VA LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS TOTAL AMPS:19 A 20 A TOTAL LOAD:2280 VA 2340 VA 41 SPARE 20 1 0 0 VA -- -- --42 39 SPARE 20 1 0 VA 0 VA 2 20 SURGE PROTECTION DEVICE 40 37 SPARE 20 1 0 0 VA 1 20 SPARE 38 35 SPARE 20 1 0 VA 0 VA 1 20 SPARE 36 33 SPARE 20 1 0 0 VA 1 20 SPARE 34 31 SPARE 20 1 0 VA 0 VA 1 20 SPARE 32 29 SPARE 20 1 0 0 VA 1 20 SPARE 30 27 SPARE 20 1 0 VA 0 VA 1 20 SPARE 28 25 SPARE 20 1 0 0 VA 1 20 SPARE 26 23 SPARE 20 1 0 VA 0 VA 1 20 SPARE 24 21 SPARE 20 1 0 0 VA 1 20 SPARE 22 19 SPARE 20 1 0 VA 0 VA 1 20 SPARE 20 17 SPARE 20 1 0 0 VA 1 20 SPARE 18 15 SPARE 20 1 0 VA 0 VA 1 20 SPARE 16 13 SPARE 20 1 0 0 VA 1 20 SPARE 14 11 SPARE 20 1 0 VA 0 VA 1 20 SPARE 12 9 ---- -- 0 0 VA -- -- --10 7 SPARE 20 2 0 VA 0 VA 2 20 SPARE 8 5 RCPTS: 200J/200TD/200TA 20 1 540 1200 VA 1 20 CUH'S (211/212) 6 3 RCPTS: 212 20 1 900 VA 1440 VA 1 20 RCPTS: 211 4 1 RCPT: 200SA 20 1 180 360 VA 1 20 RCPT: 210 2 CKT DESCRIPTION TRIP POLES A B POLES TRIP DESCRIPTION CKT ENCLOSURE:TYPE 1 OPTIONS:SUB-FEED LUGS MOUNTING:SURFACE WIRES:3 MAINS RATING:100 A FED FROM:MDP PHASE:1 MAINS TYPE:MCB LOCATION:200TA VOLTS:120/240V AIC RATING:10K PANEL LLP-22 TOTAL DEMAND AMPS:44 A ELECTRIC HEAT 17280 VA 35.00% 6048 VA TOTAL CONN AMPS:126 A RECEPTACLES 5940 VA 35.00% 2079 VA TOTAL DEMAND:10551 VA LIGHTING 2185 VA 35.00% 765 VA TOTAL CONN LOAD:30145 VA HVAC 4740 VA 35.00% 1659 VA LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS TOTAL AMPS:116 A 135 A TOTAL LOAD:13965 VA 16180 VA 41 SPARE 20 1 0 0 VA -- -- --42 39 SPARE 20 1 0 VA 0 VA 2 20 SURGE PROTECTION DEVICE 40 37 SPARE 20 1 0 0 VA 1 20 SPARE 38 35 SPARE 20 1 0 VA 0 VA 1 20 SPARE 36 33 SPARE 20 1 0 0 VA 1 20 SPARE 34 31 SPARE 20 1 0 VA 0 VA -- -- --32 29 SPARE 20 1 0 5760 VA 2 30 SNO-MELT 30 27 SPARE 20 1 0 VA 0 VA 1 20 SPARE 28 25 ---- -- 0 1200 VA 1 20 FCU-B1, B2 26 23 SPARE 20 2 0 VA 0 VA 1 20 SPARE 24 21 ---- -- 0 720 VA 1 20 RCPTS: 113 22 19 SNO-MELT 30 2 5760 VA 0 VA 1 20 SPARE 20 17 RCPT: 108 20 1 360 540 VA 1 20 RCPTS: 108 (WEST) 18 15 TIMECLOCK TC-1 (MASTER) 20 1 50 VA 1740 VA 1 20 PUMP CONTROL PANEL 16 13 LTG: 1ST FLOOR 20 1 1800 0 VA -- -- --14 11 WIRELESS LTG GATEWAY 20 1 50 VA 5760 VA 2 30 SNO-MELT 12 9 RCPTS: 109 20 1 900 1260 VA 1 20 RCPTS: BASEMENT 10 7 RCPTS: 114 20 1 720 VA 1200 VA 1 20 FCU-B3, B4 8 5 RCPT: 108 20 1 360 600 VA 1 20 CUH (1ST FLOOR STAIRS) 6 3 RCPTS: 108 (EAST) 20 1 360 VA 540 VA 1 20 RCPTS: BASEMENT 4 1 RCPT: EXTERIOR 20 1 180 285 VA 1 20 LTG: BASEMENT 2 CKT DESCRIPTION TRIP POLES A B POLES TRIP DESCRIPTION CKT ENCLOSURE:TYPE 1 OPTIONS: MOUNTING:SURFACE WIRES:3 MAINS RATING:100 A FED FROM:MDP PHASE:1 MAINS TYPE:MCB LOCATION:B11 VOLTS:120/240V AIC RATING:10K PANEL LLP-B1 REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseE-502 PANELBOARD SCHEDULESAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 TOTAL DEMAND AMPS:27 A APPLIANCE 1440 VA 35.00% 504 VA TOTAL CONN AMPS:77 A RECEPTACLES 8820 VA 35.00% 3087 VA TOTAL DEMAND:6460 VA LIGHTING 3396 VA 35.00% 1189 VA TOTAL CONN LOAD:18456 VA HVAC 4800 VA 35.00% 1680 VA LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS TOTAL AMPS:77 A 77 A TOTAL LOAD:9276 VA 9180 VA 41 SPARE 20 1 0 0 VA 1 20 SPARE 42 39 SPARE 20 1 0 VA 0 VA 1 20 SPARE 40 37 SPARE 20 1 0 0 VA 1 20 SPARE 38 35 SPARE 20 1 0 VA 0 VA 1 20 SPARE 36 33 SPARE 20 1 0 0 VA 1 20 SPARE 34 31 SPARE 20 1 0 VA 0 VA 1 20 SPARE 32 29 SPARE 20 1 0 0 VA 1 20 SPARE 30 27 SPARE 20 1 0 VA 0 VA 1 20 SPARE 28 25 SPARE 20 1 0 0 VA 1 20 SPARE 26 23 SPARE 20 1 0 VA 0 VA 1 20 SPARE 24 21 SPARE 20 1 0 0 VA -- -- --22 19 ---- -- 0 VA 0 VA 2 20 SPARE 20 17 SPARE 20 2 0 1440 VA 1 20 LTG: 3RD FLOOR 18 15 RCPTS: 310 20 1 1260 VA 0 VA 1 20 SPARE 16 13 WIRELESS LTG GATEWAY 20 1 50 1260 VA 1 20 RCPTS: 307 14 11 RCPTS: 309 20 1 1080 VA 1200 VA 1 20 CUH'S (307/308) 12 9 RCPTS: 308 20 1 1080 1200 VA 1 20 CUH'S (302/304) 10 7 RCPTS: 302 20 1 900 VA 1980 VA 1 20 RCPTS: 301 8 5 CUH'S (301/310) 20 1 1200 2096 VA 1 20 LTG: 3RD FLOOR 6 3 CUH (309) 20 1 600 VA 720 VA 1 20 RCPTS: ATTIC 4 1 LTG: 300CA/CB, STAIRS 20 1 410 540 VA 1 20 RCPTS: 304 2 CKT DESCRIPTION TRIP POLES A B POLES TRIP DESCRIPTION CKT ENCLOSURE:TYPE 1 OPTIONS:OVERSIZE TRIM MOUNTING:FLUSH WIRES:3 MAINS RATING:60 A FED FROM:MDP PHASE:1 MAINS TYPE:MCB LOCATION:300CB VOLTS:120/240V AIC RATING:10K PANEL LLP-31 TOTAL DEMAND AMPS:10 A FIRE ALARM 350 VA 100.00% 350 VA TOTAL CONN AMPS:27 A RECEPTACLES 2520 VA 35.00% 882 VA TOTAL DEMAND:2479 VA LIGHTING 2964 VA 35.00% 1037 VA TOTAL CONN LOAD:6434 VA HVAC 600 VA 35.00% 210 VA LOAD CLASSIFICATION CONN LOAD DEMAND FACTOR EST DEMAND PANEL TOTALS TOTAL AMPS:26 A 28 A TOTAL LOAD:3116 VA 3318 VA 41 SPARE 20 1 0 0 VA -- -- --42 39 SPARE 20 1 0 VA 0 VA 2 20 SURGE PROTECTION DEVICE 40 37 SPARE 20 1 0 0 VA 1 20 SPARE 38 35 SPARE 20 1 0 VA 0 VA 1 20 SPARE 36 33 SPARE 20 1 0 0 VA 1 20 SPARE 34 31 SPARE 20 1 0 VA 0 VA 1 20 SPARE 32 29 SPARE 20 1 0 0 VA 1 20 SPARE 30 27 SPARE 20 1 0 VA 0 VA 1 20 SPARE 28 25 SPARE 20 1 0 0 VA 1 20 SPARE 26 23 SPARE 20 1 0 VA 0 VA 1 20 SPARE 24 21 SPARE 20 1 0 0 VA 1 20 SPARE 22 19 SPARE 20 1 0 VA 0 VA 1 20 SPARE 20 17 SPARE 20 1 0 0 VA 1 20 SPARE 18 15 SPARE 20 1 0 VA 0 VA 1 20 SPARE 16 13 SPARE 20 1 0 0 VA 1 20 SPARE 14 11 ---- -- 0 VA 0 VA -- -- --12 9 SPARE 20 2 0 0 VA 2 20 SPARE 10 7 LTG: 2ND FLOOR 20 1 1348 VA 350 VA 1 20 WIRELESS LTG GATEWAY 8 5 RCPTS: 207 20 1 900 1160 VA 1 20 LTG: 2ND FLOOR 6 3 RCPTS: 204 20 1 540 VA 1080 VA 1 20 RCPTS: 208 4 1 LTG: 200J 20 1 456 600 VA 1 20 CUH (200SE) 2 CKT DESCRIPTION TRIP POLES A B POLES TRIP DESCRIPTION CKT ENCLOSURE:TYPE 1 OPTIONS:OVERSIZE TRIM MOUNTING:FLUSH WIRES:3 MAINS RATING:60 A FED FROM:MDP PHASE:1 MAINS TYPE:MCB LOCATION:200SE VOLTS:120/240V AIC RATING:10K PANEL LLP-23 (VIA LLP-22)REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseE-503 EQUIPMENT CONNECTION AND LUMINAIRE SCHEDULESAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 LUMINAIRE SCHEDULE TYPE DESCRIPTION MOUNTING SIZE MANUFACTURER CATALOG NO. VOLTAGE LAMPS WATTAGE FINISH NOTES 1 WALL SCONCE - REPRODUCTION WALL CUSTOM HOUSE OF ANTIQUE HARDWARE LEXINGTON SINGLE GLASS SCONCE WITH VIANNE SATIN ETCHED GAS LIGHT SHADE 120 LED 60 ANTIQUE BRASS PROVIDE WITH VINTAGE UNFROSTED LED LAMPS X1 SINGLE FACE EXIT SIGN UNIVERSAL 12"x8"x2.25" LITHONIA LQM-S-W-1-R-120/277-SD 120/277 LED .62 WHITE X2 DOUBLE FACE EXIT SIGN UNIVERSAL 12"x8"x2.25" LITHONIA LQM-S-W-2-R-120/277-SD 120/277 LED 1.24 WHITE X3 COMBO EM UNIT / EXIT SIGN WALL 19.25"x8"x2.25" LITHONIA LHQM-LED-R-HO-SD 120/277 LED 4.3 WHITE X4 EM LIGHTING BATTERY UNIT EALL 10.25"x4.25"x3.5" LITHONIA ELM2-LED-SD 120/277 LED 1.44 WHITE X5 TWIN REMOTE HEADS WALL 8.25"x5.75" LITHONIA ELA-B-T-QWP-L0309-SD - LED - BLACK EQUIPMENT CONNECTION SCHEDULE LABEL DESCRIPTION ROOM NO.PANEL RATING (kW, W, VA, A, HP)VOLTAGE PHASE WIRE & CONDUIT STARTER DISCONNECT NOTES ADDITIONAL REQUIREMENTSTYPE LOC BY ENC AUX BY RATING LOC ENC FCU-B1 FAN COIL UNIT B00UB SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 C - - - - 1 FCU-B2 FAN COIL UNIT B04 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 C - - - - 1 FCU-B3 FAN COIL UNIT B04 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 C - - - - 1 FCU-B4 FAN COIL UNIT B07 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 C - - - - 1 FCU-B5 FAN COIL UNIT B02 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 C - - - - 1 FCU-B6 FAN COIL UNIT B00UC SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 C - - - - 1 FCU-B7 FAN COIL UNIT B00UC SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 C - - - - 1 NOT USED NOT USED CUH-1 CABINET UNIT HEATER STAIRS SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-2 CABINET UNIT HEATER 201 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-3 CABINET UNIT HEATER 211 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-4 CABINET UNIT HEATER 212 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-5 CABINET UNIT HEATER 213 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-6 CABINET UNIT HEATER 214 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-7 CABINET UNIT HEATER 215 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-8 CABINET UNIT HEATER 217 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-9 CABINET UNIT HEATER 220 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-10 CABINET UNIT HEATER 223 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-11 CABINET UNIT HEATER 301 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-12 CABINET UNIT HEATER 302 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-13 CABINET UNIT HEATER 304 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-14 CABINET UNIT HEATER 307 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-15 CABINET UNIT HEATER 308 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-16 CABINET UNIT HEATER 309 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-17 CABINET UNIT HEATER 310 SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER CUH-18 CABINET UNIT HEATER 200SE SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL UNIT EC 1 - - - - - 1 INSTALL MANUAL STARTER UNDER CUH COVER NOT USED SM-1 SNO-MELT SYSTEM B04 SEE DWGS 6-kW 240 1 2#10, 1#10GND, 3/4" C. - - - - - EC 30A B04 1 1 SM-2 SNO-MELT SYSTEM B04 SEE DWGS 6-kW 240 1 2#10, 1#10GND, 3/4" C. - - - - - EC 30A B04 1 1 SM-3 SNO-MELT SYSTEM B04 SEE DWGS 6-kW 240 1 2#10, 1#10GND, 3/4" C. - - - - - EC 30A B04 1 1 NOT USED NOT USED FACP FIRE ALARM CONTROL PANEL B00SA SEE DWGS 350-W 120 1 2#12, 1#12GND, 3/4" C. - - - - - - - - - 1 NOT USED NOT USED SP-1 SUMP PUMP B02 SEE DWGS 3/4-HP 240 1 2#12, 1#12GND, 3/4" C. - - - - - EC 30A UNIT 1 1 SP-2 SUMP PUMP B00UC SEE DWGS 3/4-HP 240 1 2#12, 1#12GND, 3/4" C. - - - - - EC 30A UNIT 1 1 NOT USED 30A NOT USED WH-1 ELECTRIC WATER HEATER B02 SEE DWGS 4.5-kW 240 1 2#10, 1#10GND, 3/4" C. - - - - - EC 30A UNIT 1 1 NOT USED NOT USED CP-1 CIRCULATION PUMP B00UC SEE DWGS 1.0-HP 240 1 2#12, 1#12GND, 3/4" C. - - - - - EC 30A UNIT 1 1 NOT USED NOT USED IR-1 IRRIGATION CONTROL PANEL B00UC SEE DWGS 100-W 120 1 2#12, 1#12GND, 3/4" C. - - - - - - - - - 1 NOT USED NOT USED EF-1 EXHAUST FAN 300T SEE DWGS 500-W 120 1 2#12, 1#12GND, 3/4" C. MANUAL 300T EC 1 - - - - 1 PROVIDE MOTOR RATED SWITCH NOT USED NOT USED RNG-1 ELECTRIC RANGE 102 SEE DWGS 50-A 240 1 2#8, 1#10GND, 1" C. - - - - - - - - - - PROVIDE NEMA 14-50R TWISTLOCK RECEPTACLE NOT USED NOT USED PUMP CP PUMP CONTROL PANEL B04 SEE DWGS 14.5-MCA 120 1 2#12, 1#12GND, 3/4" C. - - - - - EC 30A B04 1 1 NOT USED NOT USED EF-B00UC EXHAUST FAN B00UC SEE DWGS 1/4-HP 120 1 2#12, 1#12GND, 3/4" C. MANUAL B00UC EC 1 - - - - - 1 FAN LOCATED ON ROOF NOT USED NOT USED NOTES: 1. MAKE CONNECTION TO EQUIPMENT.A. START-STOP IN COVER. 2. INSTALL MOTOR STARTER FURNISHED BY OTHERS.B. HAND-OFF-AUTO IN COVER. 3. MAKE CONNECTIONS TO CONTROLS.C. PILOT LIGHT IN COVER. 4. FIELD CONTROL WIRING BY OTHERS.D. AUXILIARY CONTACTS. 5. RUN FEED THRU CONTACTOR. CONTROL FROM FAN SHUTDOWN RELAY. E. CONTROL CIRCUIT TRANSFORMER. 6. PROVIDE DUCT SMOKE DETECTOR.F. TWO-SPEED MOTOR CONTROLLER. 7. PROVIDE GFI RECEPTACLE AT UNIT. CIRCUIT TO NEAREST 120V CIRCUIT. G. KEY OPERATED - UP/DOWN OR OPEN/CLOSE. 8. WIRE THRU T-STAT THEN TO MOTOR. REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION NOTES: 1.FLOOR/CEILING ASSEMBLY: A. FLOORING SYSTEM: 5/8” HARDWOOD. B. WOOD JOIST: 2”x10” LUMBER JOIST. C. CEILING: PLASTER. 2.CONDUIT: A. CONDUIT: 4” DIAMETER OR SMALLER EMT 3.FORMING AND FIRESTOP MATERIALS: A. FORMING MATERIAL: FOAM BACKER ROD PACKED INTO OPENING AS A PERMANENT FORM. B. TYPE 1A: MINIMUM ½” THICK SEALANT APPLIED WITHIN THE ANNULUS FLUSH WITH THE TOP OF THE FLOOR AND BOTTOM OF THE CEILING ASSEMBLIES. ADDITIONAL SEALANT TO BE APPLIED SUCH THAT A MINIMUM OF ½” CROWN IS FORMED AROUND THE PENETRATING ITEM. 2 A SECTION A-A 3B A 3B 1B 1A3B 2 3B 1C 3A 3A WIRELESS REMOTE SWITCH WIRELESS MOTION SENSOR (WALL) LIGHT FIXTURE AC LINE IN WIRELESS LUMINAIRE CONTROLLER (5A MAX) HOT NEUT CAT 6 DATA GATEWAY GW1100 FIXTURE BALLAST/DRIVER 120/277 120 VAC 58-PS-24V-T POWER SUPPLY 24 VDC WIRELESS MOTION SENSOR (CEILING) DIGITAL TIMECLOCK TC-1 (MASTER) 100CA EXTERIOR LUMINAIRE DIGITAL TIMECLOCK TC-2 (REMOTE) 103 EXTERIOR LUMINAIRE 120VAC - CAT6 DATA CABLE IN 3/4" EMT TO EXISTING PATCH PANEL IN B03 - PC EXISTING LUMINAIRE (TYPICAL) ELEC B11 MECH BOOUC (2) #14 AWG, 3/4" C. 120VAC BRANCH CIRCUITRY (TYPICAL) SEQUENCE OF OPERATION: 1. 100CA EXTERIOR LUMINAIRE: FIXTURE SHALL OPERATE ON PHOTOCELL CONTROL WITH NO MANUAL OVERRIDE. PROGRAM TO OPERATE FROM DUSK TO DAWN. 2.102 EXTERIOR LUMINAIRE: FIXTURE SHALL OPERATE ON PHOTOCELL CONTROL WITH A DIGITAL SWITCH TO OVERRIDE. PROGRAM TO OPERATE ON MANUAL OVERRIDE ONLY. PROGRAM PHOTOCELL/TIMECLOCK TO SHUT FIXTURE OFF DURING DAYLIGHT. 3.103 EXTERIOR LUMINAIRE: FIXTURE SHALL OPERATE ON PHOTOCELL CONTROL WITH A DIGITAL SWITCH TO OVERRIDE. PROGRAM TO OPERATE ON MANUAL OVERRIDE ONLY. PROGRAM PHOTOCELL/TIMECLOCK TO SHUT FIXTURE OFF DURING DAYLIGHT. 4.113 EXTERIOR LUMINAIRE: FIXTURE SHALL OPERATE ON PHOTOCELL CONTROL WITH A DIGITAL SWITCH TO OVERRIDE. PROGRAM TO OPERATE ON MANUAL OVERRIDE ONLY. PROGRAM PHOTOCELL/TIMECLOCK TO SHUT FIXTURE OFF DURING DAYLIGHT. GENERAL INSTALLATION NOTES: 5.INSTALL UNSWITCHED BRANCH CIRCUIT FROM RESPECTIVE LIGHTING BRANCH CIRCUIT TO EACH LUMINAIRE VIA THE RELAY ON THE SPECIFIED TIMECLOCK. REFER TO PLANS FOR BRANCH CIRCUIT/PANEL INFORMATION. 6.PROVIDE CAT6 DATA CABLING BETWEEN TIMECLOCKS AND BETWEEN TIMECLOCKS AND DIGITAL SWITCHES. 7.PROVIDE 120VAC BRANCH CIRCUIT TO EACH TIMECLOCK. 8.PROVIDE ALL PROGRAMMING. 9.PROVIDE DIGITAL SWITCHES WITH A FLUSH, SINGLE-GANG BOX. CONCEAL DATA CABLING IN WALLS, FLOORS, AND CEILINGS. R1 102 EXTERIOR LUMINAIRE R3 113 EXTERIOR LUMINAIRE R5 R7 R2 R4 R6 R8 R1 R3 R7 R2 R4 R6 R8 CAT6 DATA CABLE IN 3/4" EMT KITCHEN 102 APARTMENT 103 OFFICE 113CAT6 DATA CABLE IN 3/4" EMT 120VAC - R5 DIGITAL SWITCH (TYPICAL) N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseE-504 DETAILSAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 SCALE:NO SCALE11-HOUR FIRE RATED FLOOR PENETRATION SCALE:NO SCALE2WIRELESS LIGHTING CONTROL SCHEMATIC SCALE:NO SCALE3EXTERIOR LIGHTING CONTROL RISER REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION B00UB B00UC B11 B13 B13C B13B B13A B04 B07 B02 B05 B00T B03 B01 B14 B00SB B00SA B00UA B09 PIT CRAWL SPACE CRAWL SPACE B00C UP UP UP 110 100C 109 108 113 113A 114 100TB 112 101 102 103 100JA 100JB DN UP DN DN DN DN UP DN FEEDER UP TO SECOND FLOOR BATHROOM POWER PANEL PANEL LP-4 JB2 JB1 JB4 JB3 JB5 PANEL LP-3 PANEL SNO-MELT PANEL LP-2 PANEL LP-1 MDP PANEL EM PANEL LP-5 JB6 JB7 60A DISCONNECT FEEDER UP TO SECOND FLOOR HALL POWER PANEL FEEDER UP TO SECOND FLOOR CLOSET POWER PANEL EXISTING 2.4KV/120/240V TRANSFORMER (TO REMAIN) EXISTING 2.4KV SWITCH (TO REMAIN) FCU-B1 FCU-B2 FCU-B4 FCU-B5 SP-1 FCU-B6 FCU-B7 FCU-B3 CP-1 SP-2 WH-1 IR-1 FACP ED-1021 1 1 1 1 1 1 2 TYP 3 TYP 4 TYP 5 TYP PUMP CP 9 10 20 21 PM PM PM CUH-1 RNG-1 J J J J 6 TYP 7 3 TYP 2 TYP 5 8 8 8 8 11 12 12 12 13 13 13 14 14 15 16 17 17 18 18 18 (2) SWITCHES CONTROL A/C UNIT POWER, REMAINING SWITCH CONTROLS PORCH LIGHTS AC AC N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseED-100 DEMOLITION PLANS - BASEMENT AND FIRST FLOORSAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 0 4 8 16 SCALE: 1/8"=1'-0" #ED-100 KEYED DEMOLITION NOTES 1 DISCONNECT AND REMOVE PANELBOARD. REMOVE ALL BRANCH AND FEEDER CIRCUITRY. PATCH AND PAINT WALL BEHIND BACKBOX TO MATCH SURROUNDING SURFACES. REFER TO THE EXISTING PANELBOARD SCHEDULE, DETAIL #2/ED-102 FOR ADDITIONAL INFORMATION. 2 DISCONNECT AND REMOVE ALL WIRING DEVICES AND BACKBOXES. REMOVE BRANCH CIRCUITRY TO SOURCE. 3 EXISTING LIGHT FIXTURES TO REMAIN. DISCONNECT AND REMOVE ASSOCIATED BRANCH CIRCUITRY AND CONTROL WIRING TO SOURCE. PROTECT LIGHT FIXTURES DURING CONSTRUCTION. 4 DISCONNECT AND REMOVE EXIT SIGNS AND EMERGENCY LIGHT FIXTURES AS SHOWN. DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SOURCE. 5 EXISTING MECHANICAL EQUIPMENT AND HARDWIRED EQUIPMENT TO REMAIN. DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SOURCE. PROTECT EQUIPMENT DURING CONSTRUCTION. 6 EXISTING PLUGMOLD TO REMAIN. DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SOURCE. PROTECT PLUGMOLD DURING CONSTRUCTION. 7 DISCONNECT AND REMOVE ELECTRIC RANGE RECEPTACLE. DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SOURCE. 8 EXISTING BRASS FLOOR RECEPTACLES TO REMAIN. DISCONNECT AND REMOVE RECEPTACLE AND BRANCH CIRCUITRY TO SOURCE. REINSTALL BRASS COVERS. 9 DISCONNECT AND REMOVE ABANDONED WATER SERVICE BONDING JUMPER AND CABLING. 10 DISCONNECT AND REMOVE EF-B00UC MANUAL STARTER AND BRANCH CIRCUITRY TO SOURCE. 11 DISCONNECT AND REMOVE SPECIAL RECEPTACLE AND BRANCH CIRCUITRY TO SOURCE. REINSTALL COVERPLATE. 12 WALL SCONCE MISSING AT THIS LOCATION. DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SOURCE. 13 DISCONNECT AND REMOVE WALL SCONCE AND BRANCH CIRCUITRY TO SOURCE. 14 EXISTING COVE LIGHTING TO REMAIN. 15 DISCONNECT AND REMOVE BRANCH CIRCUITY TO SOURCE. UNDERSINK DISPOSAL TO REMAIN. 16 DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SOURCE FOR (9) UNDERCABINET LIGHTS. UNDERCABINET LIGHTS TO REMAIN. 17 DISCONNECT AND REMOVE LIGHT SWITCH AND BRANCH CIRCUITRY FOR BASEMENT STAIR LIGHTING. STAIR LIGHTING TO REMAIN. 18 DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SECOND FLOOR LIGHTING. 20 DISCONNECT AND REMOVE EXISTING ELECTRIC METER SOCKET AND RETURN TO CORNELL. 21 MAINTAIN THE EXISTING POWERSCOUT ELECTRIC METER AND CT'S MONITORING THE 37.5-KVA XFMR. SCALE: 1/8" = 1'-0"1 DEMOLITION PLAN - BASEMENT04816 SCALE: 1/8"=1'-0" SCALE: 1/8" = 1'-0"2 DEMOLITION PLAN - FIRST FLOOR REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION 200TC 200CA 200CC204 201 213 212 211A 214 215 217 218 223 220 207 208 210 200CB200SC200TA200TD200J 100SB 200SE 200SA 200SD 223APORCH211 212A 214A 208A 204A OPEN TO BELOW UP UP UP DN DN DN 200SD 304 302 300T 301 307 308 309 310 300J 312 CRAWL SPACE 304A 300SA 301A 301C 301B 310A 300CA 300CB DN DN BATHROOM POWER PANEL CLOSET POWER PANEL SECOND FLOOR HALL PANEL PM PM PM PM PM PM PM PM PM PM PM PM PM PM PM PM PM PM PM PM CUH-3 CUH-4 CUH-2 CUH-6 CUH-5 CUH-7 CUH-8 CUH-9 CUH-10 CUH-18 1 2 3 4 5 6 1 1 TYP TYP TYP TYP UP TO THIRD FLOOR 7 TYP 8 TYP OF 9 LOCATIONS BID ALTERNATE E-2 BID ALTERNATE E-1 BID ALTERNATE E-2 BID ALTERNATE E-1 THIRD FLOOR HALL PANEL M PM PM PM PM PM PM PM PM PM PM PM PM PM CUH-14 CUH-13 EF-1 CUH-12 CUH-15 CUH-16 CUH-17 CUH-11 2 TYP 3 TYP 1 6 TYP 5 TYP N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseED-101 DEMOLITION PLANS - SECOND AND THIRD FLOORSAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 SCALE: 1/8" = 1'-0"1 DEMOLITION PLAN - SECOND FLOOR 0 4 8 16 SCALE: 1/8"=1'-0" SCALE: 1/8" = 1'-0"2 DEMOLITION PLAN - THIRD FLOOR 0 4 8 16 SCALE: 1/8"=1'-0" ED-101 KEYED DEMOLITION NOTES 1 DISCONNECT AND REMOVE PANELBOARD. REMOVE ALL BRANCH AND FEEDER CIRCUITRY. PATCH AND PAINT WALL BEHIND BACKBOX TO MATCH SURROUNDING SURFACES. REFER TO THE EXISTING PANELBOARD SCHEDULE, DETAIL #2/ED-102 FOR ADDITIONAL INFORMATION. 2 DISCONNECT AND REMOVE ALL WIRING DEVICES AND BACKBOXES. REMOVE BRANCH CIRCUITRY TO SOURCE. 3 EXISTING LIGHT FIXTURES TO REMAIN. DISCONNECT AND REMOVE ASSOCIATED BRANCH CIRCUITRY AND CONTROL WIRING TO SOURCE. PROTECT LIGHT FIXTURES DURING CONSTRUCTION. 4 DISCONNECT AND REMOVE EXIT SIGNS AND EMERGENCY LIGHT FIXTURES AS SHOWN. DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SOURCE. 5 EXISTING MECHANICAL EQUIPMENT AND HARDWIRED EQUIPMENT TO REMAIN. DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SOURCE. PROTECT EQUIPMENT DURING CONSTRUCTION. 6 EXISTING PLUGMOLD TO REMAIN. DISCONNECT AND REMOVE BRANCH CIRCUITRY TO SOURCE. PROTECT PLUGMOLD DURING CONSTRUCTION. 7 REMOVE CARPETING AND FLOOR/SUBFLOOR TO EXPOSE FIRST FLOOR CEILING FOR DEMOLITION AND NEW WORK. RESTORE FLOOR/SUBFLOOR AND CARPET. 8 REPLACE (9) WALL SCONCES ON SECOND FLOOR PER BID ALTERNATE E-3. # REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION 1" EMT FEEDER TO PANEL LP-4 EM LOADCENTER 60/2 ENCLOSED CIRCUIT BREAKER (EM LOADCENTER MCB) WIREWAY LIGHTING CONTACTOR PANEL LP-5 100/2 ENCLOSED CIRCUIT BREAKER (PANEL LP-5 MCB) FUSIBLE SWITCH MDP METER EXISTING 4x4 J-BOX EXISTING CIT CABINET FINISHED FLOOR N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseED-102 DEMOLITION ELEVATION AND EXISTING PANELBOARD SCHEDULEAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 SCALE: 1" = 1'-0"1 ELEVATION - BASEMENT 0 1 2 SCALE: 1"=1'-0" EXISTING PANELBOARD INFORMATION PANEL NAME LOCATION MANUFACTURER RATING # OF CKTS BREAKERS # OF CLOTH CKTS EM B11 SQUARE D 100A MLO 8 (5) 20A/1P, (1) 50A/2P 0 LP-1 B00SB SQUARE D 150A MLO 20 (5) 15A/1P, (7) 20A/1P, (6) 20A/1P TANDEM, (1) 50A/2P 1 LP-2 B00C SQUARE D 150A MLO 30 (22) 20A/1P, (1) 30A/2P, (3) 20A/2P 2 LP-3 B04 SQUARE D 150A MLO 20 (1) 15A/1P, (11) 20A/1P, (2) 20A/1P TANDEM, (1) 30A/2P, (1) 60A/2P 8 LP-4 B11 SQUARE D 150A MLO 16 (8) 15A/1P, (1) 20A/1P, (3) 20A/1P TANDEM, (1) 20A/2P, (1) 30A/2P 6 LP-5 B11 SQUARE D 150A MLO 16 (10) 20A/1P 0 SNO-MELT B04 SQUARE D 100A MLO 8 (3) 30A/2P 0 2ND FLOOR HALL PANEL 200SE SQUARE D 150A MLO 20 (8) 15A/1P, (2) 20A/1P 8 2ND FLOOR BATHROOM PANEL 200TA SQUARE D 150A MLO 20 (6) 20A/1P, (1) 20A/2P 0 2ND FLOOR CLOSET PANEL 200SC SQUARE D 150A MLO 16 (12) 20A/1P, (1) 20A/2P 0 3RD FLOOR HALL PANEL 300CB SQUARE D 150A MLO 16 (3) 15A/1P, (5) 20A/1P 3 REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION MDP PANEL LP-5 LIGHTING CONTACTOR 60/2 ENCLOSED CIRCUIT BREAKER ELECTRIC METER CIT JBOX N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseED-103 DEMOLITION PHOTOSAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 SCALE:NO SCALE1PHOTO - ROOM B11 WEST WALL (MDP) SCALE:NO SCALE2PHOTO - ROOM B11 WEST WALL (PANEL LP-5) SCALE:NO SCALE3PHOTO - ROOM B11 WEST WALL (EM PANEL) SCALE:NO SCALE4PHOTO - ROOM B11 NORTH WALL (PANEL LP-4) SCALE:NO SCALE5PHOTO - ROOM B11 NORTH WALL (JB5) SCALE:NO SCALE6PHOTO - ROOM B04 EAST WALL (PANEL LP-3) SCALE:NO SCALE7PHOTO - ROOM B04 EAST WALL (JB6) SCALE:NO SCALE8PHOTO - ROOM B04 (JB3) SCALE:NO SCALE9PHOTO - ROOM B00C (PANEL LP-2) SCALE:NO SCALE10PHOTO - ROOM B00C (JB4) SCALE:NO SCALE11PHOTO - ROOM B02 (JB1) SCALE:NO SCALE12PHOTO - ROOM B00SB (PANEL LP-1) MDP PANEL LP-5 LIGHTING CONTACTOR EM PANEL EM PANEL REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION N CORNELLUNIVER S IT Y F O U NDED5681ADCornell UniversityFacilities EngineeringIT IS A VIOLATION OF NEW YORK STATE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED ARCHITECT OR ENGINEER, TO ALTER THIS DOCUMENT IN ANY WAY. IF THIS DOCUMENT IS ALTERED, THE ALTERING ARCHITECT OR ENGINEER SHALL AFFIX TO SUCH DOCUMENT HIS SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION OF THE ALTERATION. WARNING:Ithaca, New YorkDATE: FACILITY: DESIGN: DRAWN:ARCHIVE BAR CODEARCH/STRUCT: CIVIL/ENV: ELECTRICAL: MECHANICAL:AD White HouseED-104 DEMOLITION PHOTOSAD White House Electrical UpgradesC. WAYMAN cmw 2006 March 10, 2017 9038228 SCALE:NO SCALE1PHOTO - ROOM B00SB (JB2) SCALE:NO SCALE2PHOTO - ROOM B00C (JB7) SCALE:NO SCALE3PHOTO - ROOM B200TA (BATHROOM PANEL) SCALE:NO SCALE4PHOTO - ROOM 200SC (CLOSET PANEL) SCALE:NO SCALE5PHOTO - ROOM 300CB (HALLWAY PANEL) SCALE:NO SCALE6PHOTO - ROOM 200SE (HALLWAY PANEL) REVISIONS 1 10/21/16 ISSUE FOR 50% DD REVIEW 2 2/24/17 ISSUE FOR COORDINATED REVIEW 3 3/10/17 ISSUE FOR CONSTRUCTION