DAY HALL
2026
TOWER ROAD
EAST AVESECOND FLOOR
THIRD FLOORFOURTH FLOOR & ROOF
AREA OF WORK
AREA OF WORKAREA OF WORK CORNE
LL U N I V
E
R
SI
TYFOUN
D E D 5681
AD CORNE
LL U N I V
E
RSI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
N
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.IPP.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
Cornell University
DAY HALL
DAY HALL
BOARDROOM 316
HVAC UPGRADES
T-001
-
TITLE SHEET
FE DESIGN
JD
2026
MAY 7, 2018
DAY HALL BOARDROOM 316 HVAC UPGRADES
T-001 TITLE SHEET
ARCHITECTURAL
A-001 GENERAL NOTES, SYMBOLOGY, AND ABBREVIATIONS
A-101 THIRD FLOOR PLANS, & DETAILS
MECHANICAL
M-001 GENERAL NOTES AND SYMBOL LEGENDS
M-101 DEMOLITION AND NEW WORK PLANS
M-501 SCHEDULES
ELECTRICAL
E-001 GENERAL NOTES AND SYMBOL LEGENDS
E-101 PARTIAL 3RD FLOOR DEMOLITION PLAN
E-102 NEW WORK PLANS
SITE LOCATION -DAY HALL
KEY PLAN -THIRD, FOURTH FLOOR, AND ROOF
AREA OF WORK
BUILDING CODE SUMMARY
APPLICABLE CODES
2015 (EXISTING) IBC (ADOPTED BY NEW YORK STATE)
PROJECT SUMMARY
THIS PROJECT INCLUDES THE RENOVATION OF 560 SF OF OFFICE
THE WORK IS ALTERATION LEVEL 2. THE EXISTING HVAC EQUIPMENT
SHALL BE REPLACED WITH NEW EQUIPMENT TO PROVIDE
HEATING/COOLING/VENTILATION.
BUILDING LIMITATIONS
CONSTRUCTION CLASSIFICATION:1A
CLASSIFICATION OF HAZARDS:NONE
HIGH-RISE BUILDING:NO
EXTINGUISHING REQUIREMENT:THE EXISTING BUILDING
IS NOT SPRINKLERED
OCCUPANCY
OCCUPANCY CLASSIFICATION:BUSINESS (B)
DRAWING INDEX
PROJECT SCOPE
THE PURPOSE OF THIS PROJECT IS TO REPLACE THE EXISTING HEATING/COOLING/VENTILATION SYSTEM IN DAY HALL BOARDROOM 316 WITH A NEW,
MORE EFFICIENT, QUIETER, VARIABLE REFRIGERANT FLOW (VRF) HEATING/COOLING SYSTEM.
A NEW ENERGY RECOVERY VENTILATION UNIT, LOCATED IN A ROOFTOP ENCLOSURE, SHALL PROVIDE VENTILATION AIR DIRECTLY TO THE
HEATING/COOLING CASSETTE UNITS LOCATED IN THE SPACE.
THE VRF SYSTEM WILL PROVIDE BOTH HEATING AND COOLING. HEATING BACKUP SHALL BE PROVIDED BY A SECTION OF FLOOR MOUNTED FIN TUBE
SERVED BY THE EXISTING LOW PRESSURE STEAM SYSTEM CURRENTLY SERVING THE EXISTING HEATING SYSTEM.
THE REMOVAL AND REINSTALLATION OF SHEETROCK WILL BE REQUIRED TO ROUTE REFRIGERANT AND DRAINAGE PIPING IN THE EXISTING WALLS.
THE ELECTRICAL SYSTEM SHALL BE EXTENDED TO SERVE THE NEW HEATING/COOLING/VENTILATION SYSTEM.
PERSPECTIVE VIEW
GENERAL SYMBOLS LEGEND
EXTERIOR ELEVATION
1
1
1 1X-100
X-100
1
1
1 1 INTERIOR ELEVATION
1
X-100
SECTION MARKER
1
X-100
ENLARGED DETAIL
#CONSTRUCTION KEYED NOTE
DEMOLITION KEYED NOTE#
DRAWING REVISION NOTE#
LINETYPE: TO BE PROVIDED / NEW
LINETYPE: DEMOLITION / TO BE RELOCATED
LINETYPE: EXISTING TO REMAIN
1 4/13/18 PROGRESS REVIEW
2 4/20/18 ISSUE FOR 90% REVIEW
3 4/30/18 ISSUE FOR COORDINATED REVIEW
4 5/7/18 ISSUE FOR CONSTRUCTION
101
A101
1
1
1 1
0
Name
Elevation
101
X-X
X
1t
DN
WALL -EXISTING
WALL -METAL STUD/ GWB
WALL -CONCRETE
WALL -CMU
WALL -BRICK
ITEMS FOR DEMOLITION
DOOR/ WALL -EXISTING
DOOR/ WALL -NEW
DOOR/ WALL -DEMOLITION
TAG -DOOR
TAG -WINDOW
TAG -WALL
TAG -ROOM #
CENTER LINE
PHOTO REFERENCE
LEVEL MARKER
COLUMN GRID MARKER
ELEVATION MARKER
UP
ELEVATION CHANGE ARROWS
BREAK LINE
SYMBOLS
0' -0"
ABBREVIATIONS
A
&AND
@ AT
ACT ACOUSTICAL CEILING TILE
ALT ALTERNATE
ALUM ALUMINUM
AVG AVERAGE
AFF ABOVE FINISH FLOOR
B
BD BOARD
BLDG BUILDING
BOD BOTTOM OF DECK
BSMT BASEMENT
C
CG CORNER GUARDS
CJ CONTROL JOINT
CLG CEILING
CL CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONT CONTINUOUS
CORR CORRIDOR
CPT CARPET
CRS COURSE(S)
CT CERAMIC TILE
D
DEMO DEMOLITION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DO DOOR OPENING
DWG DRAWING
E
EA EACH
EJ EXPANSION JOINT
ELEC ELECTRIC
ELEV ELEVATION/ ELEVATOR
EPDM RUBBER ROOF MEMBRANE
EQ EQUAL
EX'G EXISTING
EXT EXTERIOR
F
FD FLOOR DRAIN
FDN FOUNDATION
FEC FIRE EXTINGUISHER CABINET
FFE FINISH FLOOR ELEVATION
FRP FIBER REINFORCED POLYESTER
FT FOOT/FEET
FTG FOOTING
G
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERAL
GL GLASS
GWB GYPSUM WALL BOARD
H
HC HANDICAPPED
HT HEIGHT
HM HOLLOW METAL
HR HOUR
HVAC HEATING, VENTILATING & AC
J
JAN JANITOR
L
LAV LAVATORY
LB/#POUND
LGMF LIGHT GAGE METAL FRAMING
M
MFR MANUFACTURER
MAT MATERIAL
MAX MAXIMUM
MEZZ MEZZANINE
MIN MINIMUM
MO MASONRY OPENING
MTL METAL
N
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NR NOT RATED
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OSB ORIENTER STRAND BOARD
P
+/-PLUS OR MINUS
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
Q
QTY QUANTITY
R
R RISER
RD ROOF DRAIN
REF REFRIGERATOR
REQ REQUIRED
REV REVISION
RO ROUGH OPENING
RTU ROOF TOP UNIT
S
SHTG SHEATHING
SIM SIMILAR
SF SQUARE FOOT/ FEET
SS STAINLESS STEEL
STL STEEL
STD STANDARD
T
T TREAD
T&G TONGUE & GROOVE
TEL TELEPHONE
TEMP TEMPERATURE
TOS TOP OF STEEL
TV TELEVISION
TYP TYPICAL
U
UEV UNEVEN DOORS W/ VISION PANEL
UEF UNEVEN FLUSH DOOR
V
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
W
W/O WITHOUT
WD WOOD CORNE
LL U N I V
E
RSI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.IPP.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
DAY HALL
DAY HALL
BOARDROOM 316
HVAC UPGRADES
A-001
-
GENERAL
NOTES,
SYMBOLOGY,
AND
ABBREVIATIONS
R. HERKO
RH
2026
MAY 7, 2018
SCOPE OF WORK
1.0 OPEN EXISTING SOFFIT AND INSTALL NEW CEILING MOUNTED MECHANICAL UNITS.
TRIM OUT NEW MECHANICAL UNITS AND REPAINT SOFFITS.
2.0 INSTALL NEW ROOF MOUNTED MECHANICAL EQUIPMENT AND PIPE TO NEW
MECHANICAL UNITS IN SOFFIT.
3.0 REMOVE EXISTING PTAC MECHANICAL UNITS AND INFILL WALL CONSTRUCTION
WITH NEW CONSTRUCTION TO MATCH EXISTING
GENERAL NOTES
1.0 DESIGN, CONSTRUCTION AND SAFETY SHALL CONFORM TO ALL LOCAL, STATE AND
OWNER SPECIFIC CODES, INCLUDING (BUT NOT LIMITED TO) THE NEW YORK STATE
UNIFORM FIRE PROTECTION AND BUILDING CODE, LATEST REVISION, THE NFPA 101
LIFE SAFETY CODE, LATEST REVISION, ANSI A117.1 - LATEST REVISION, OSHA, AND
ANY OTHER CODES GOVERNED BY THE JURISDICTION IN WHICH THIS PROJECT IS
BEING CONSTRUCTED.
2.0 THIS CONTRACT REQUIRES COMPLETE, FINISHED WORKABLE PROJECT OF THE
AREAS INDICATED BY THE CONTRACT DOCUMENTS, AND SHALL INCLUDE ALL
MATERIALS AND LABOR NECESSARY TO COMPLETE, REGARDLESS OF WHETHER OR
NOT ALL WORK OR EACH ITEM IS SPECIFICALLY INDICATED ON ANY OTHER
PORTION OF THE DRAWINGS AND / OR NOTES.
3.0 WHERE MATERIALS REFERENCED ON DRAWINGS, OR NECESSARY TO COMPLETE
THE WORK OF THIS CONTRACT ARE NOT SPECIFIED HEREIN, PROVIDE BEST
QUALITY MATERIALS. WHERE MATERIALS ARE INTENDED TO MATCH EXISTING,
PROVIDE CLOSEST POSSIBLE MATCH, SUBJECT TO OWNER'S APPROVAL. ALL ITEMS
AND WORK ON DRAWINGS ARE NEW, UNLESS INDICATED EXISTING. ALL WORK
WHICH HAS BEEN DAMAGED SHALL BE REPAIRED OR REPLACED AT NO COST TO
THE OWNER. WHERE ITEMS CAN NOT BE REPAIRED TO A ""NEW CONDITION"", OR
WHERE THE STRUCTURAL INTEGRITY HAS BEEN AFFECTED, ITEMS SHALL BE
REPLACED AT NO COST TO THE OWNER.
4.0 CONTRACTOR IS RESPONSIBLE TO VERIFY ALL SITE, FIELD AND BUILDING
CONDITIONS PRIOR TO SUBMITTING BIDS AND COMMENCING WORK. IF THERE ARE
ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS, NOTIFY THE
PROJECT MANAGER, WHO WILL REQUEST CLARIFICATION FROM THE
ARCHITECT/ENGINEER AND PROVIDE CLARIFICATION IN WRITING.
5.0 WHERE EXISTING CONSTRUCTION OR ITEMS HAVE BEEN INFILLED, REMOVED AND /
OR DISTURBED FOR INSTALLATION OF NEW WORK, CAUSING THE EXPOSURE OF
UNFINISHED AND/OR DAMAGED SURFACES RESULTING SURFACES AND INFILLED
SURFACES SHALL BE RECONSTRUCTED WITH MATERIALS TO MATCH FINISHED
AREAS. ALL ABANDONED OPENINGS (i.e. DUCT/PIPE REMOVALS, ETC.) AT WALLS,
ROOF OR FLOOR TO BE INFILLED SOLID.
6.0 WORK IS REQUIRED IN VARIOUS PORTIONS OF THE FACILITY TO EXECUTE WORK OF
OTHER TRADES (i.e. ELECTRICAL, MECHANICAL). ALTHOUGH NOT NECESSARILY
SHOWN ON DRAWINGS, WORK IS REQUIRED IN THESE AREAS CONSISTING OF
REMOVAL / REPLACEMENT OF CEILINGS, WALLS, FINISHES, PAVEMENT AND OTHER
CONSTRUCTION AS NECESSARY TO PERFORM WORK AND RESTORE THESE
SPACES OR AREAS TO ORIGINAL CONDITION.
7.0 GENERAL CONTRACTOR IS TO COORDINATE WORK OF ALL TRADES. SCHEDULE
WORK PROGRESS THROUGHOUT THE ENTIRE PROJECT TO PREVENT CONFLICTS
AND INTERFERENCES. OBTAIN ALL NECESSARY INFORMATION SUCH AS SIZES,
LOCATIONS, TEMPLATES, LAYOUT, DIMENSIONS AND ALL OTHER INFORMATION
NECESSARY FOR A PROPER AND WELL COORDINATED INSTALLATION. PRIOR TO
INSTALLATION OF ITEMS, VERIFY AND CONFIRM WITH EACH CONTRACTOR EXACT
LOCATION OF ALL ITEMS.
8.0 ALL PENETRATIONS (EXISTING OR NEW) THROUGH FLOORS AND FULL HEIGHT
WALLS - IN AREA OF WORK TO BE FIRE STOPPED. ALL GAPS AND JOINTS AT RATED
FLOORS, ROOFS AND WALLS TO BE FIRE & SMOKE STOPPED. GAPS AND JOINTS
INCLUDE (BUT ARE NOT LIMITED TO) TOP OF WALL TO FLOOR OR ROOF DECK, WALL
TO BEAMS, AND CONTROL OR EXPANSION JOINTS. FIRE STOPPING INCLUDES BOTH
FORM OR PACKING MATERIAL AND THE FILL, VOID OR CAVITY MATERIAL. PROVIDE
AND INSTALL LABELING REQUIRED BY CODE. LABELS SHALL INCLUDE
PENETRATION TYPE WITH UL LISTING USED, MATERIAL USED, DATE INSTALL AND
NAME OF INSTALLER.
9.0 JOBSITE WILL BE CLEANED DAILY AND DEBRIS REMOVED TO CONTAINERS OR TO
VEHICLE WHICH WILL REMOVE DEBRIS FROM CAMPUS. CONTAINERS WILL BE
REMOVED AS SOON AS FULL OR WHEN THE PROJECT HAS PROGRESSED TO A
POINT THAT A CONTAINER IS NO LONGER REQUIRED.
10.0 CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL AREAS USED TO BRING
SUPPLIES AND EQUIPMENT INTO THE PROJECT AREA. ANY DAMAGE TO AREAS
OUTSIDE THE PROJECT AREA INCLUDING BUT NOT LIMITED TO THE LOBBY AND
CORRIDOR SHALL BE REPAIRED AT NO COST TO THE OWNER.
1 4/13/18 PROGRESS REVIEW
2 4/20/18 ISSUE FOR 90% REVIEW
3 4/30/18 ISSUE FOR COORDINATRED REVIEW
4 5/7/18 ISSUE FOR CONSTRUCTION
4
A-101
2 233
4
4
5
7
EQ EQ EQ EQ
1
1
1
LINE OF LIGHT COVE
SOFFIT ABOVE
LINE OF CONCRETE
CEILING BEAM ABOVE
LINE OF LIGHT COVE
SOFFIT ABOVE
LINE OF CONCRETE
CEILING BEAM ABOVE
4
A-101
6
6
6
8
8
8
9
316
1
1
1
GYP. WALL BOARD TO SURROUND NEW
MECHANICAL UNIT, PRIMED & PAINTED TO
MATCH SOFFIT. ATTACHED GYP. BD TO "Z"
CLIP ANGLES. PROVIDE TEAR AWAY "L" BEAD
AT JUNCTION OF VERTICAL GYP BD TO
UNDERSIDE OF SOFFIT TYP.
NEW CEILING MOUNTED MECHANICAL UNIT.
SEE MECHANICAL DRAWINGS. TYP OF 4.
EXISTING PLASTER SOFFIT / LIGHTING COVE
TO BE CUT OPEN BY G.C. TO ALLOW MECH.
CONTRACTOR TO INSTALL NEW MECH. UNITS.
G.C. TO PATCH, REPAIR & PAINT (TYP)
CONTINUOUS
SEALANT BEAD
(TYP) 2"EXISTING CONCRETE
BEAM & CEILING
STRUCTURE
EXIST'G SLAB
BLOCK (TYP) CLR3' - 8"PITCH
CONTINUOUS SEALANT AT JOINT
OF CURB/WALL TO VAPOR
BARRIER (COMPATIBLE W/ EX.
ROOF MATERIAL & ZIP SHEATHING
PENTHOUSE ENCLOSURE:
2'-0" X 3'-8 X 7'-0" INTERIOR CLEARANCE, 18 GA.
METAL STUDS @ 16" O.C. WITH INSULATED ZIP
BOARD SHEATHING (1" RIGID INSULATION WITH
7/16" ZIP BOARD). TAPE ALL JOINTS W/ ZIP TAPE.
SPRAY-FOAM INSULATION IN METAL STUDS. FULLY
ADHERED .060 EPDM MEMBRANE OVER ENTIRE
SURFACE. INSTALL EPDM PER MFGR
RECOMMENDATION IN ORDER TO MAINTAIN ROOF
WARRANTY. ROOF MEMBRANE SYSTEM TO BE
INSTALLED BY A CERTIFIED INSTALLER. PROVIDE
EXTERIOR RATED, WATERPROOF ACCESS PANEL
(VERIFY SIZE AND LOCATION WITH MECH
CONTRACTOR). CUT BACK EXISTING ROOFING AS
REQUIRED TO INSTALL NEW PENTHOUSE
ENCLOSURE AND REASSEMBLE ROOFING SYSTEM
AS REQUIRED TO MATCH EXISTING
CLR
2' - 0"
(4) PENETRATIONS THROUGH
EXISTING CONCRETE SLAB.
VERIFY W/ MECH DWGS.
LOCATE EX. SLAB REBAR
TO AVOID CUTTING REINF.
PRIOR TO CORING SLAB.
SLEEVE CORE OPENING W/
PVC PIPE AND PROVIDE BEAD
OF SEALANT AROUND
PERIMETER
SIMPSON TITEN HD 1/2" DIAM. x
4" LONG @ 16" O.C. FOR BOTT.
TRACK ATTACHMENT
3" MIN.L1x1x3/16 x 3'-0" +/-LG.
PERPENDICULAR TO EX. STEEL
SUPPORTING THE LATHE &
PLASTER. AT LOCATIONS CUT OR
INTERRUPTED BY NEW
CASSETTES, PROVIDE (2) L1x1
SPANNING TO ADJACENT EX.
STEEL. PROVIDE BEAM CLAMPS
(MCMASTER OR EQUIV.) TO
ATTACH L1x1 TO EX.
STEEL SUPPORTS.
ROUND ALL CORNERS TO MATCH
EXISTING SOFFIT ROUNDED CORNERS.
EX. THREADED ROD
INTERRUPTED BY
NEW CASSETTE (TO
BE REMOVED)
ANTICIPATED EX. ROOF
REMOVAL, EA. SIDE TYP.CORNE
LL U N I V
E
RSI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
N
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.IPP.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
DAY HALL
DAY HALL
BOARDROOM 316
HVAC UPGRADES
A-101
-
THIRD FLOOR
PLANS, &
DETAILS
R. HERKO
RLH
2026
MAY 7, 2018
A-101 RENOVATION KEY NOTES
1 G.C. TO INFILL WALL OPENING WITH 20 GA. 3-5/8" G90 METAL STUDS @ 16" O.C. &
CONTINUOUS TOP & BOTTOM TRACK, R-21 BATT INSULATION & RIGID POLYISO FOR
THE FULL DEPTH OF CAVITY, 5/8" GYPSUM WALL BOARD, TAPED, SPACKLED &
PAINTED TO MATCH EXISTING.
2 NEW MECHANICAL UNIT SET INTO SOFFIT BY MECH CONTRACTOR (SEE
MECHANICAL DWGS). HOLE CUT IN SOFFIT BY G.C. GEN CONTRACTOR TO PATCH,
REPAIR, PAINT SOFFIT AFTER INSTALLATION OF NEW MECHANICAL UNIT. (TYPICAL
OF 4 LOCATIONS)
3 GEN. CONTRACTOR TO PROVIDE CLIP ANGLES AND WOOD TRIM AROUND NEW
MECHANICAL UNIT. PRIME & PAINT TO MATCH SOFFIT COLOR. (TYP OF 4
LOCATIONS)
4 GEN. CONTRACTOR TO PATCH & REPAINT ENTIRE SOFFIT TO MATCH EXISTING
AFTER INSTALLATION OF NEW MECHANICAL UNIT
5 GEN. CONTRACTOR TO COORDINATE PENETRATIONS IN ROOF DECK ABOVE FOR
NEW MECHANICAL EQUIPMENT. ALL ROOF PENETRATIONS AND NEW MECHANICAL
UNITS TO BE FLASHED BY A ROOFING CONTRACTOR CERTIFIED BY THE
MANUFACTURER OF THE ROOFING MEMBRANE IN ORDER TO MAINTAIN ROOF
WARRANTY. REFER TO MECHANICAL DRAWINGS FOR ROOF TOP MECHANICAL
EQUIPMENT.
6 GEN. CONTRACTOR TO PATCH FLOORING CARPET TILES WITH NEW TO MATCH
EXISTING PROVIDED BY OWNER AT PTAC REMOVAL AREAS.
7 G.C. TO CONSTRUCT AREA TO RECEIVE GYP. WALL BOARD CEILING AND ACCESS
PANEL AS REQUIRED TO CONCEAL CEILING MOUNTED MECHANICAL & ELECTRICAL
EQUIPMENT. VERIFY SIZE AND LOCATION. CEILING TO BE HELD AS TIGHT AS
POSSIBLE AND MADE AS SMALL AS POSSIBLE TO CONCEAL EQUIPMENT.
8 MECH CONTRACTOR TO PROVIDE A WATERTIGHT PAINTED COVERPLATE BEHIND
EXTERIOR GRILLE BEFORE INFILLING OPENING AT PTAC REMOVAL AREA.
COORDINATE WITH MECHANCIAL DWGS.
9 GEN. CONTRACTOR TO REMOVE SHEET ROCK WHERE REQUIRED TO INSTALL
REFRIGERANT LINE SETS AND DRAINAGE PIPING. COORDINATE LOCATIONS WITH
MECHANICAL CONTRACTOR. ONCE ALL PIPING HAS BEEN INSTALLED AND TESTED,
PATCH AND PAINT TO MATCH EXISTING.
#
A-101 DEMOLITION KEY NOTES
1 EXISTING MECHANICAL PTAC UNIT TO BE REMOVED - SEE MECHANICAL DRAWINGS
#
0' 2' 4' 8'
SCALE: 1/4"=1'-0"
SCALE: 1/4" = 1'-0"1 THIRD FLOOR - RENOVATION REFLECTED CEILING PLAN
SCALE: 1/4" = 1'-0"2 THIRD FLOOR - RENOVATION PLAN
SCALE: 1/4" = 1'-0"3 THIRD FLOOR - DEMOLITION PLAN
SCALE: 1" = 1'-0"4 SOFFIT / ROOFTOP EQUIPMENT ENCLOSURE SECTION
1 4/13/18 PROGRESS REVIEW
2 4/20/18 ISSUE FOR 90% REVIEW
3 4/30/18 ISSUE FOR COORDINATRED REVIEW
4 5/7/18 ISSUE FOR CONSTRUCTION
CORNE
LL U N I V
E
RSI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.IPP.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
DAY HALL
DAY HALL
BOARDROOM 316
HVAC UPGRADES
M-001
-
GENERAL
NOTES AND
SYMBOL
LEGENDS
P. OCKENFELS
PO
2026
MAY 7, 2018
MECHANICAL ABBREVIATIONS
BCU BLOWER COIL UNIT
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CC CLEAN CONDENSATE
CO CLEAN OUT
CS CLEAN STEAM
CD CONDENSATE DRAIN
EA EXHAUST AIR
EAG EXHAUST AIR GRILLE
FD FIRE DAMPER
GWR GLYCOL HEATING RETURN
GWS GLYCOL HEATING SUPPLY
HPR HIGH PRESSURE STEAM RETURN
HPS HIGH PRESSURE STEAM SUPPLY
HWR HOT WATER HEATING RETURN
HWS HOT WATER HEATING SUPPLY
LPC LOW PRESSURE CONDENSATE
LPS LOW PRESSURE STEAM
MU MAKE UP WATER
MPC MEDIUM PRESSURE CONDENSATE
MPS MEDIUM PRESSURE STEAM
NG NATURAL GAS
PCWR PROCESS CHILLED WATER RETURN
PCWS PROCESS CHILLED WATER SUPPLY
HG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
RAG RETURN AIR GRILLE
SA SUPPLY AIR
SAD SUPPLY AIR DIFFUSER
VD VOLUME DAMPER
WMS WIRE MESH SCREEN
MECHANICAL SYMBOLOGY
2-WAY ELECTRIC CONTROL VALVE
3-WAY ELECTRIC CONTROL VALVE
ACOUSTICALLY ALIGNED DUCTWORK
AIRFLOW
AQUA STAT
AUTOMATIC LOUVERED DAMPER IN DUCT
BACKFLOW PREVENTER
BALANCE VALVE
BALL VALVE
BOTTOM PIPE CONNECTION
BUTTERFLY VALVE
CAP OR PLUG
CHECK VALVE
CIRCULATING PUMP
DIRECTION OF FLOW
DUCT AIRFLOW
DUCT DOWN (EXHAUST OR RETURN)
DUCT DOWN (SUPPLY)
DUCT UP (EXHAUST OR RETURN)
DUCT UP (SUPPLY)
EXHAUST FAN
EXHAUST OR RETURN UP THROUGH NEXT FLOOR OR ROOF
EXPANSION COMPENSATOR WITH EXPANSION GUIDES
EXPANSION JOINT
FIRE AND SMOKE DAMPER IN DUCT
FIRE DAMPER IN DUCT
FLANGE CONNECTION
FLEX CONNECTOR
FLEXIBLE CONNECTION
FLEXIBLE DUCT
FLOW METER
FLOW SWITCH
FUSIBLE LINK VALVE
GLOBE VALVE
MANUAL AIRVENT
ORIFICE METER
PIPE ANCHOR
PIPE DOWN
PIPE GUIDE
PIPE UP
PIPING REDUCER (CONCENTRIC)
PIPING REDUCER (ECCENTRIC)
PITCH PIPING (DOWN)
PRESSURE GAUGE
PRESSURE OR TEMPERATURE PETES PLUG
PRESSURE REDUCING VALVE
PRESSURE SWITCH
RECTANGULAR ELBOW
RECTANGULAR ELBOW WITH TURNING VANES
RELIEF VALVE
ROOF TOP HOOD
SMOKE DAMPER IN DUCT
SOLENOID VALVE
STANDARD BRANCH DUCT
STEAM TRAP
STRAINER (DUPLEX)
STRAINER WITH BLOWDOWN VALVE AND CAP
SUPPLY THROUGH NEXT FLOOR OR ROOF
TEMPERATURE WELL
THERMOMETER
THERMOMETER (DIAL)
TOP PIPE CONNECTION
TRIPLE DUTY VALVE
UNION CONNECTION
VACUUM BREAKER
VOLUME DAMPER IN DUCT
CONTROL SYMBOLOGY
OCCUPANCY SENSOR
THERMOSTAT (FACTORY CONTROLLER)
GENERAL DRAWING SYMBOLOGY
DEMOLISHED WORK
EXISTING PIPING TO REMAIN
EXISTING TO REMAIN
EXISTING WORK TO REMAIN
NEW WORK
POINT OF CONNECTION
POINT OF DISCONNECTION
MECHANICAL SCOPE OF WORK
1.0 REMOVE THREE EXISTING PTAC UNITS AND ALL ASSOCIATED CONTROLS.
2.0 PROVIDE LOW PRESSURE STEAM FINTUBE RADIATOR WITH THERMOSTATIC
CONTROL VALVE AND REMOTE FLOOR MOUNTED TEMPERATURE SENSOR.
3.0 PROVIDE OUTDOOR ROOF MOUNTED CONDENSING UNIT, FOUR INDOOR CASSETTE
UNITS, REFRIGERANT PIPING, AND ASSOCIATED FACTORY STAND ALONE
CONTROLS. THE OUTDOOR CONDENSING UNIT SHALL BE MOUNTED ON
EQUIPMENT RAILS SECURED TO THE ROOF DECK.
4.0 PROVIDE ENERGY RECOVERY VENTILATION UNIT AND ASSOCIATED DUCTWORK.
THE VENTILATION UNIT SHALL BE INSTALLED IN AN ROOF MOUNTED ENCLOSURE.
5.0 PROVIDE COOLING CONDENSATE DRAIN PIPING AND TIE INTO THE SECOND FLOOR
CONDENSATE DRAIN PIPING DIRECTLY BELOW THE CONFERENCE ROOM ON THE
SECOND FLOOR.
SUBMITTAL SCHEDULE
SPECIFICATION
SECTION ITEM REQUIRED
23 05 29 HANGERS AND SUPPORTS FOR HVAC PIPING AND
EQUIPMENT
PRODUCT DATA
23 05 93 TESTING, ADJUSTING & BALANCING FOR HVAC QUALIFICATIONS, INSPECTION AND TEST REPORTS
23 07 13 DUCT INSULATION PRODUCT DATA
23 07 19 HVAC PIPING INSULATION PRODUCT DATA
23 31 13 METAL DUCTS PRODUCT DATA & SHOP DRAWINGS
23 72 23 PACKAGED AIR-TO-AIR ENERGY-RECOVERY UNITS
& BACKDRAFT DAMPERS
PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M
23 81 29 VARIABLE REFRIGERANT FLOW HVAC SYSTEMS
(INDOOR UNIT, OUTDOOR UNIT, BRANCH SELECTOR
BOX, REFRIGERANT PIPING, PACKAGED
CONTROLS)
PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M
23 82 36 FINNED-TUBE RADIATION HEATERS PRODUCT DATA, MANUFACTURERS INSTRUCTIONS, O&M
MECHANICAL GENERAL NOTES
1.0 THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE ONLY THE GENERAL
ARRANGEMENT OF THE SYSTEMS AND WORK INCLUDED IN THE CONTRACT.
CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS. IF DIMENSIONS OR
CONDITIONS ARE FOUND TO BE IN CONFLICT WITH THE DRAWINGS, THE
CONTRACTOR SHALL IMMEDIATELY REFER THE CONFLICT TO THE OWNER'S REP.
2.0 UTILITY SHUTDOWNS: SHUTDOWN OF ANY BUILDING UTILITY SYSTEM SHALL BE
COORDINATED WITH CUSTOMER SERVICE AT PH: 607-255-5322. THE CONTRACTOR
SHALL BEAR THE COST OF THE UTILITY SHUTDOWN. SCHEDULE WORK TEN DAYS
IN ADVANCE AND NOTIFY THE OWNER'S REPRESENTATIVE TO COORDINATE
BUILDING FUNCTIONS WITH THE BUILDING COORDINATOR.
3.0 ALL PENETRATIONS THROUGH FULL HEIGHT WALLS ARE TO BE FIRESTOPPED IN
ACCORDANCE WITH UL STANDARDS. ALL GAPS AND JOINTS AT RATED FLOORS,
ROOFS AND WALLS ARE TO BE FIRE AND SMOKE STOPPED. CAPS AND JOINTS
INCLUDE (BUT ARE NOT LIMITED TO) TOP OF WALL TO FLOOR OR ROOF DECK, WALL
TO BEAMS, AND CONTROL OR EXPANSION JOINTS. FIRESTOPPING INCLUDES BOTH
FORM OR PACKING MATERIAL AND THE FILL, VOID OR CAVITY MATERIAL.
4.0 ALL DUCT DIMENSIONS INDICATED ARE IN INCHES.
5.0 INSTALL EQUIPMENT TO ENSURE PROPER ACCESS TO CONTROL DEVICES AND
WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE AND REPAIR.
EQUIPMENT THAT IS NOT INSTALLED WITH THIS REQUIREMENT IN MIND SHALL BE
RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIES ARE
CORRECTED.
6.0 ALL SYSTEMS SHALL BE LABELED.
7.0 VERIFY FINAL EQUIPMENT/FIXTURE LOCATIONS FOR ROUGHING-IN.
8.0 ALL SYSTEM TESTING SHALL BE CONDUCTED PRIOR TO INSULATION AND
FIREPROOFING. ANY RESTORATION WORK REQUIRED AS A RESULT OF DISTURBING
FINISHES OR STRUCTURE IN ORDER TO ACCESS SYSTEMS REQUIRING REPAIR
SHALL BE AT NO COST TO THE UNIVERSITY.
9.0 TRAINING: THE BUILDING OCCUPANTS SHALL RECEIVE A MINIMUM OF 4 HOURS OF
TRAINING ON THE OPERATION OF THE NEWLY INSTALLED MECHANICAL SYSTEMS.
COORDINATE WITH OWNER'S REP. TO SCHEDULE TRAINING.1 4/13/18 PROGRESS REVIEW
2 4/20/18 ISSUE FOR 90% REVIEW
3 4/30/18 ISSUE FOR COORDINATED REVIEW
4 5/7/18 ISSUE FOR CONSTRUCTION
3
M-101
316 -CONFERENCE ROOM
AC-316A
4" SA
BALANCE EACH
BRANCH TO 55 CFM
8" SA
6" EA UP THROUGH ROOF
BSB-316
1
AC-316B
AC-316CAC-316DFTR-1
2
3/4" CD
3
3
3
4
3/4" CD4
3
5
T
7
5
OS
8
12
12
8X6 EA
13
14
15
1616
16 16
ROOF
OUTSIDE AIR INTAKE HOOD BROAN
MODEL 610FA OR EQUIVALENT
EXHAUST CAP
BROAN MODEL 641FA OR EQUIVALENT
ACCU-316
EXISTING EXHAUST HOOD
(ABANDONED IN PLACE)
REFRIGERANT PIPING
3/8" X 5/8" REFRIGERANT PIPES TO/FROM
BRANCH SELECTOR BOX LOCATED
IN CONFERENCE RM 316
PIPE SUPPORTS
ERV-316
10
11
17
INSULATED EQUIPMENT ENCLOSURE
ACCU-316
EXISTING EXHAUST HOOD
(ABANDONED)
FACTORY SUPPLIED
HAIL/SNOW GUARDS
4" PLUMBING VENT
EQUIPMENT RAILS
2'-4" MINIMUM HEIGHT
ERV-316
PIPE SUPPORTS
3'-0" MAX DISTANCE
BETWEEN SUPPORTS.
12
11
3RD FLOOR
22' - 10"
ROOF
32' - 10"
OUTSIDE AIR INTAKE HOOD BROAN
MODEL 610FA OR EQUIVALENT
2'-0" ABOVE ROOF MINIMUM.
EXHAUST CAP
BROAN MODEL 641FA OR EQUIVALENT
FTR-1
MANUAL BALANCING DAMPER
6" EA
6" RA & OA
3/4" CD3
6
ERV-316
6" SA
8" SA9
13
1
1
1
5
5
5
2
2
3
4
316 -CONFERENCE ROOM
THERMOSTATIC TRAP
ISOLATION VALVE
ISOLATION VALVE
ANGLED THERMOSTATIC VALVE WITH
REMOTE SENSOR
REMOTE SENSOR MOUNTED ON THE
FLOOR NEAR INLET AND NOT
DIRECTLY UNDER FIN TUBE ELEMENT
CONDENSATE DOWN
THROUGH FLOOR
FIN TUBE SLOPE
TOWARDS RETURN
LOW PRESSURE
STEAM SUPPLY
FLOOR MOUNTED FIN TUBE
ENCLOSURE
UNION
UNION (TYP)
LOCKABLE ACCESS DOOR
LOCKABLE ACCESS DOOR
M-101 KEYED CONSTRUCTION NOTES
1 RUN REFRIGERANT LINE SETS (3/8” X 1/4”) IN THE VOID ABOVE THE VIDEO
CONFERENCE SCREEN.
2 3/8" X 5/8" REFRIGERANT PIPING UP TO CONDENSING UNIT ON ROOF.
3 1/4” X 3/8” REFRIGERANT LINE SET WITH 1/2” INSULATION. PROTECT INSULATION
FROM BEING PUNCTURED DURING INSTALLATION.
4 MINIMUM CONDENSATE DRAIN LINE SLOPE SHALL BE 1/8” PER 12"
5 3/4” CONDENSATE DRAIN DOWN THROUGH FLOOR, CORE DRILL DOWN THROUGH
FLOOR. EXTEND EXISTING 1-1/4” CONDENSATE DRAIN PIPING ON SECOND FLOOR
TO SERVE NEW CONDENSATE DRAIN LINE.
6 ALL DUCTWORK LOCATED IN THE ROOFTOP ENCLOSURE SHALL BE INSULATED
WITH A MINIMUM OF R-6 DUCT INSULATION.
7 INTERNALLY LINE THE STRAIGHT PORTION OF 8" SUPPLY AIR DUCT WITH 1” CLOSED
CELL SOUND ATTENUATION LINING.
8 INSTALL TIGHT TO THE CEILING WITH THE REQUIRED OFFSET DISTANCE REQUIRED
BY THE MANUFACTURER. COORDINATE SERVICE ACCESS PANEL LOCATION WITH
G.C.
9 PROVIDE 1” CLOSED CELL DUCT LINING, FOR SOUND ATTENUATION, ON THE 8”
SUPPLY AIR RISER ONLY. THIS DUCT SHALL ALSO BE INSULATED.
10 EXISTING 4" PLUMBING VENT. EXTEND VENT PIPING HORIZONTALLY TO MAINTAIN A
MINIMUM OF 10'-0" SEPARATION FROM ERV-316 INTAKE. SLOPE A MINIMUM OF 1/8”
PER 12” TOWARDS VENT RISER. MATCH EXISTING VENT PIPE MATERIAL.
11 INSULATED EQUIPMENT ENCLOSURE WITH FRONT ACCESS DOOR. REFER TO A-101,
DETAIL # 4 FOR DETAILS. COORDINATE FINAL REQUIRED DIMENSIONS, ACCESS
DOOR LOCATION, AND ALL PENETRATIONS THROUGH THE ROOF DECK WITH G.C.
12 FIRE STOP ALL ROOF/FLOOR PENETRATIONS. REFER TO DRAWING A-001, NOTE # 8.
COORDINATE ALL PENETRATIONS WITH G.C.
13 8X12 OPENING IN THE TOP OF THE EXHAUST DUCT. COVER OPENING WITH WIRE
MESH SCREEN. INSTALL DUCT TIGHT TO THE CEILING WITH A MINIMUM OF 1-1/2”
DISTANCE FROM THE CORK CEILING PANELS TO THE 8X12 DUCT OPENING. CAP
BOTH OPEN ENDS OF THE 8X6 EXHAUST DUCT.
14 CONNECT TO EXISTING LOW PRESSURE STEAM SUPPLY TO SERVE NEW FINTUBE.
15 CONNECT TO EXISTING LOW PRESSURE STEAM RETURN TO SERVE NEW FINTUBE.
16 WRAP EACH CASSETTE UNIT WITH 2” 1.5 PCF DUCT WRAP FOR INCREASED SOUND
ATTENUATION.
17 COORDINATE WITH ELECTRICAL CONTRACTOR FOR THE MOUNTING OF THE
DISCONNECT SWITCH.
#
0 2 4 8
SCALE: 1/4"=1'-0"CORNE
LL U N I V
E
RSI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
N
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.IPP.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
DAY HALL
DAY HALL
BOARDROOM 316
HVAC UPGRADES
M-101
-
DEMOLITION
AND NEW
WORK PLANS
P. OCKENFELS
PO
2026
MAY 7, 2018
SCALE: 1/4" = 1'-0"2 3RD FLOOR - NEW WORK
SCALE: 1/4" = 1'-0"4 ROOF - NEW WORK
SCALE: NO SCALE
5 ROOF PLAN ISOMETRIC
SCALE: 1/4" = 1'-0"3 SECTION 1
SCALE: 1/4" = 1'-0"1 3RD FLOOR - DEMOLITION
M-101 KEYED DEMOLITION NOTES
1 REMOVE PTAC UNITS AND ALL ASSOCIATED ACCESSORIES. DISPOSE OF
RECLAIMED REFRIGERANT IN ACCORDANCE WITH FEDERAL & STATE CODES &
REGULATIONS.
2 CAP LOW PRESSURE STEAM SUPPLY/RETURN AT FLOOR LEVEL.
3 PREPARE LOW PRESSURE STEAM RETURN PIPE FOR NEW WALL MOUNTED FIN
TUBE.
4 PREPARE LOW PRESSURE STEAM SUPPLY FOR NEW WALL MOUNTED FIN TUBE.
5 BLANK OFF AND INSULATE EXISTING LOUVER AND SEAL WATER TIGHT. PAINT THE
EXTERIOR FACING PORTION OF BLANK PANEL FLAT BLACK.
#
SCALE: NO SCALE
6 LOW PRESSURE STEAM RADIATION DETAIL
1 4/13/18 PROGRESS REVIEW
2 4/20/18 ISSUE FOR 90% REVIEW
3 4/30/18 ISSUE FOR COORDINATED REVIEW
4 5/7/18 ISSUE FOR CONSTRUCTION
CORNE
LL U N I V
E
RSI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.IPP.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
DAY HALL
DAY HALL
BOARDROOM 316
HVAC UPGRADES
M-501
-
SCHEDULES &
CONTROLS
P. OCKENFELS
PO
2026
MAY 7, 2018
DUCT SCHEDULE AND SPECIFICATIONS
SERVICE
PRESSURE
CLASS
SEAL
CLASS
LEAKAGE CLASS
DUCT MATERIAL LINING DUCT INSULATIONRECT Round
SUPPLY ROUND (EXPOSED IN ROOM)1" POS/NEG A - 3 G90 GALVANIZED NOTE 9 1/2" THICK, FLEXIBLE CLOSED-CELL ELASTOMERIC INSULATION, ASTM C534 TYPE II, ASTM C1534
RETURN/EXHAUST RECTANGULAR (EXPOSED IN ROOM) 1" POS/NEG A 6 - G90 GALVANIZED NONE NONE
SUPPLY/RETURN/EXHAUST ROUND/RECTANGULAR IN ROOF ENCLOSURE 1" POS/NEG A 6 3 G90 GALVANIZED NONE 1-1/2" THICK, MINERAL FIBERGLASS BLANKET, ASTM C553 TYPE I, ASTM C1136 TYPE I FACTORY APPLIED FSK JACKET, K-VALUE BETWEEN 0.22 - 0.29 BTU-IN/HR-FT²-˚F @ 75 ˚F, 0.75 PCF
ENERGY RECOVERY VENTILATOR SCHEDULE
UNIT LOCATION SERVICE
AIR DATA
SUMMER CONDITIONS (EFFICIENCY= 74%
SENSIBLE / 70% TOTAL)SUMMER CONDITIONS (EFFICIENCY= 72% SENSIBLE / 53% TOTAL)
UNIT
WEIGHT
FAN
DESIGN BASIS NOTES
OUTSIDE AIR
CFM
EXHAUST AIR
CFM
SUPPLY AIR
CFM
TOTAL
MBH
OUTSIDE
DB F
RETURN
DB F
SUPPLY
DB F
SENSIBLE
MBH
TOTAL
MBH
OUTSIDE
DB F
OUTSIDE
WB F
RETURN
DB F
RETURN
WB F
SUPPLY
DB F
SUPPLY
WB F ESP VOLT PH HP
ERV-316 3RD FLR ROOF 316-CONFERENCE RM 110 110 110 7861 -5.0 68.0 49.1 1145 2220 88.0 73.0 75.0 62.6 78.4 67.8 60 0.4 120 1 0.1 RENEWAIRE - EV130 1,2
NOTES:
1. PROVIDE WITH OUTSIDE AIR AND EXHAUST AIR BACK DRAFT DAMPERS.
2. PROVIDE WITH CEILING MOUNTED OCCUPANCY SENSOR AND INTERLOCK WITH THE OPERATION OF ACCU-316.
FINTUBE SCHEDULE - STEAM
TAG LOCATION
BASIS OF DESIGN TUBE
DIA
(IN)
FIN
TIERS
HEAT
OUTPUT
(BTU/LF)
FINNED
LENGTH
(LF)
HEAT
OUTPUT
(BTU)
STEAM
PRESSURE
(PSI)
ENTERING
AIR TEMP
(°F)NOTESMANF ENCLOSURE MODEL SIZE (IN) THK (IN)
SPACING
(FPF)
FTR-1 316-CONFERENCE RM VULCAN DURA-VANE JDV4-10 1 3-5/8 x 4-1/4 0.02 50 1 1432 16 22,912 5 65 1 THRU 10
NOTES:
1. ALL DUCTWORK AND ACCESSORIES SHALL BE FABRICATED AND INSTALLED IN COMPLIANCE WITH THE LATEST ISSUE OF SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS -METAL AND FLEXIBLE.
2. CONSTRUCT TEES, BENDS, AND ELBOWS WITH RADIUS OF NOT LESS THAN 1.0 TIMES THE WIDTH OF DUCT ON CENTER LINES.
3. WHERE RECTANGULAR ELBOWS ARE USED, PROVIDE AIR FOIL TYPE TURNING VANES.
4. SEALANTS AND GASKETS: SURFACE BURNING CHARACTERISTICS SHALL BE A MAXIMUM FLAME-SPREAD INDEX OF 25, AND MAXIMUM SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED TO UL 723.
5. INSTALL VOLUME DAMPERS AT POINTS ON SUPPLY, RETURN, AND EXHAUST SYSTEMS WHERE BRANCHES EXTEND FROM LARGER DUCTS. ALL MANUAL BALANCING DAMPERS SHALL BE PROVIDED WITH LOCKING HAND QUADRANT.
6. PROVIDE FLEXIBLE CONNECTORS TO CONNECT DUCTS TO EQUIPMENT.
7. PAINT ALL DUCTWORK/INSULATION EXPOSED TO VIEW IN OCCUPIED AREAS TO MATCH SURROUNDING FINISH.
8. ALL INSULATION AND ADHESIVE SHALL HAVE A MAXIMUM FLAME-SPREAD INDEX OF 25 AND A MAXIMUM SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED IN ACCORDANCE WITH ASTM E84.
9. 1” CLOSED CELL ACOUSTICAL DUCT INSULATION, ARMAFLEX DUCT LINER OR EQUIVALENT.
SPLIT SYSTEM
TAG TYPE
OUTDOOR UNIT INDOOR UNIT
MANF MODEL REFRIGERANT
CAPACITY
EER HSPF
COP @
47 °F
COP @
17 °F
REFRIGERANT
PIPE SIZE O.D.
(IN)ELECTRICAL
AMBIENT OPERATING RANGE
(°F)OVERALL
DIMENSIONS
(H x W x D)
WEIGHT
(LBS)TAG MODEL
CAPACITY ELECTRICAL
AIRFLOW
(CFM) (LOW /
MEDIUM /
HIGH)
SOUND (dB)
(LOW /
MEDIUM /
HIGH)
REFRIGERANT PIPE
SIZE O.D. (IN)
DIMENSIONS
(H x W x D)
WEIGHT
(LBS)
COOLING
(MBH)
HEATING
(MBH)LIQUID GAS V / PH/ Hz MCA
MAX
FUSE COOLING HEATING
COOLING
(MBH)
HEATING
(MBH)V / PH/ Hz MCA
FAN MOTOR
(ECM)DRAIN GAS LIQUID
ACCU-316 INVERTER HEAT PUMP MITSUBISHI MXZ-8C48NAHZ R410A 48 54 12 11 3.75 2.70 3/8 5/8 208 / 1 / 60 42 50 -13 °F TO 59°F 23 °F TO 115 °F 53" x 42" x 14" 280 AC-316A, B, C, D SLZ-KA12NA 11.1 13.6 208 / 1 / 60 1 0.28 FLA 280 / 320 / 390 30 / 34 / 39 1-1/4 3/8 1/4 26" x 26" x 10-1/32" 36
PROVIDE THE FOLLOWING FACTORY SUPPLIED ACCESSORIES:
1) LOW AMBIENT PACKAGE WITH WIND BAFFLE/SNOW GUARDS & BASE PAN HEATER.
2) WIRED REMOTE CONTROLLER (MODEL: PAR32MAA-J)
3) FIVE PORT BRANCH BOX SELECTOR (MODEL: PAC-MKA50BC)
SEQUENCE OF OPERATIONS
SYSTEM DESCRIPTION
PACKAGED REVERSIBLE HEAT PUMP SPLIT SYSTEM (ACCU-316, BSB-316, & AC-316A-D)
ENERGY RECOVERY VENTILATION UNIT (ERV-316)
GENERAL
SYSTEM SHALL BE CONTROLLED THROUGH A SINGLE FACTORY-FURNISHED DIGITAL CONTROLLER. SYSTEM SHALL
NOT BE INTEGRATED INTO THE BUILDING MANAGEMENT SYSTEM.
THE CONTROLLER SHALL BE CAPABLE OF BEING PROGRAMMED FOR OCCUPIED AND UNOCCUPIED TEMPERATURE
SETPOINT ON A DAILY/WEEKLY BASIS.
THE CONTROLLER SHALL BE CAPABLE OF RETAINING ITS PROGRAMMING AND TIME SETTING DURING A LOSS OF
POWER FOR AT LEAST TEN HOURS.
ALL CONTROL DEVICES INDICATED ARE NEW AND ARE TO BE PROVIDED BY THE CONTRACTOR.
PACKAGED REVERSIBLE HEAT PUMP SPLIT SYSTEM (ACCU-316, AC-316A, AC-316B, AC-316C, & AC-316D)
SYSTEM SHALL BE CONTINUOUSLY ENERGIZED, BUT SHALL BE CAPABLE OF BEING SHUT DOWN VIA THE WALL-
MOUNTED DIGITAL CONTROLLER.
INDOOR FANS SHALL RUN CONTINUOUSLY WHEN MANUALLY COMMANDED ON AT THE WALL CONTROLLER.
WHEN WALL CONTROLLER CALLS FOR COOLING, INDOOR FANS SHALL START ON LOW SPEED AND CONDENSING
UNIT SHALL START ON LOW SPEED. IF SPACE TEMPERATURE EXCEEDS SETPOINT, COMPRESSOR SPEED AND FAN
SPEED SHALL INCREASE INDEPENDENTLY AS NEEDED TO MAINTAIN ROOM TEMPERATURE SETPOINT. WHEN ROOM
TEMPERATURE APPROACHES SETPOINT, BOTH FAN SPEED AND COMPRESSOR SPEED SHALL DECREASE. WHEN
ROOM TEMPERATURE SETPOINT IS SATISFIED, FAN AND COMPRESSOR SPEED SHALL BE BACK TO LOW SPEED.
WHEN WALL CONTROLLER CALLS FOR HEATING, INDOOR FANS SHALL START ON LOW SPEED AND CONDENSING
UNIT SHALL START ON LOW SPEED. IF SPACE TEMPERATURE DROPS BELOW SETPOINT COMPRESSOR SPEED AND
FAN SPEED SHALL INCREASE INDEPENDENTLY AS NEEDED TO MAINTAIN ROOM TEMPERATURE SETPOINT. WHEN
ROOM TEMPERATURE APPROACHES SETPOINT, BOTH FAN SPEED AND COMPRESSOR SPEED SHALL DECREASE.
WHEN ROOM TEMPERATURE SETPOINT IS SATISFIED, FAN AND COMPRESSOR SPEED SHALL BE BACK TO LOW
SPEED.
ENERGY RECOVERY UNIT (ERV-316)
ERV SHALL BE ENERGIZED VIA ROOM OCCUPANCY SENSOR (WATTSTOPPER CI-24). WHEN ROOM IS OCCUPIED, ERV
FANS SHALL BE COMMANDED ON.
ERV SHALL BE INTERLOCKED WITH SPLIT SYSTEM. IN EVENT OF SYSTEM SHUTDOWN OR FAILURE, ERV SHALL BE
AUTOMATICALLY DE-ENERGIZED
FINTUBE RADIATION (BACKUP HEATING SOURCE)
STEAM FINTUBE RADIATION SHALL PROVIDE A BACKUP HEATING SOURCE IN THE EVENT THE HEAT PUMP SPLIT
SYSTEM IS NOT OPERATIONAL DURING THE HEATING SEASON.
A MANUAL DANFOS RADIATOR VALVE SHALL BE SET TO 55°F (ADJ) AND LOCATED INSIDE THE LOCKABLE FINTUBE
ENCLOSURE TO ELIMINATE THE POSSIBILITY SIMULTANEOUS HEATING AND COOLING.
NOTES:
1. ACCEPTABLE MANUFACTURERS: SLANT-FIN, TRANE, VULCAN
2. PERFORMANCE SHALL BE RATED ACCORDING TO HYDRONICS INSTITUTE'S I=B=R RATING STANDARD FOR BASEBOARD RADIATION
3. HEAT OUTPUT INDICATED IS THE OUTPUT AT STANDARD RATING CONDITIONS CORRECTED FOR WATER VELOCITY, ENTERING AIR TEMPERATURES, AND MOUNTING HEIGHTS, AS REQUIRED.
4. HEATING ELEMENTS: COPPER TUBING MECHANICALLY EXPANDED INTO FLANGED COLLARS OF EVENLY SPACES ALUMINUM FINS, MINIMUM WORKING PRESSURE OF 180 PSI @ 300 ˚F.
5. ENCLOSURE: MINIMUM 16 GA (0.0635-INCH) ZINC-COATED STEEL.
6. ELEMENT SUPPORTS: MANUFACTURER RECOMMENDED TO PERMIT LONGITUDINAL MOVEMENT ON ENCLOSURE BRACKETS.
7. FINISH: BAKED ENAMEL IN MANUFACTURER'S STANDARD COLOR AS SELECTED BY ARCHITECT.
8. ACCESSORIES: END TRIM, END ENCLOSURE, LOCKABLE ACCESS PANEL AT PIPING CONNECTIONS.
9. INSTALL FIN TUBE RADIATION IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.
10. JOIN SECTIONS WITH SPLICE PLATES AND FILLER PIECES TO PROVIDE CONTINUOUS ENCLOSURE.
HVAC PIPE AND FITTING SCHEDULE AND SPECIFICATIONS
PIPE SERVICE ABBREVIATION PIPE SIZE MATERIAL FITTINGS JOINT INSULATION
REFRIGERANT LINE SETS - ALL SIZES ASTM B280, TYPE ACR COPPER ASTM B16.22 STD WROUGHT COPPER AWS A5.8 BRAZE 1/2", TYPE B
CONDENSATE DRAIN (COOLING) CD ALL SIZES ASTM B306 TYPE DWV COPPER ASTM B16.29 DWV WROUGHT COPPER ASTM B32 SOLDER 1/2", TYPE B
SPECS:
1. REFRIGERATION WORK SHALL BE PERFORMED BY EPA SECTION 608 CERTIFIED REFRIGERATION TECHNICIANS, WITH SUPPLEMENTAL 4-410A SAFETY TECHNICIAN CERTIFICATION.
2. ALL REFRIGERANT PIPING SHALL BE NITROGENIZED, CLEAN, DRY AND CAPPED.
3. A NITROGEN PURGE SHALL BE USED AT ALL TIMES DURING BRAZING TO PREVENT OXIDATION ON THE INSIDE OF THE TUBING.
4. BRAZING MATERIALS:
COPPER TO COOPER JOINTS: BRAZE WITH A COPPER-PHOSPHOROUS ALLOY CONTAINING A MINIMUM OF 15% SILVER, CONFORMING TO AWS A5.8, BCuP5 (15% Ag, 80% Cu, 5% P).
DISSIMILAR METALS: BRAZE WITH A SILVER ALLOY CONTAINING A MINIMUM OF 45% SILVER, CONFORMING TO AWS 5.8, BAg-5 (45% Ag, 30% Cu, 25% Zn).
ELBOWS SHALL BE OF THE LONG RADIUS TYPE. CLOSE RUFF OR STREET ELBOWS ARE NOT ACCEPTABLE.
5. INSULATION MATERIAL:
TYPE B -EXPANDED CLOSED CELL FLEXIBLE ELASTOMERIC, ASTM C534 TYPE I FOR TUBULAR MATERIALS, TYPE II FOR SHEET MATERIALS,
MAX K OF 0.27 BTU-IN/HR-FT²-˚F @ 75 ˚F. ADHERE TO 100% OF THE
PIPE SURFACE. FLAME SPREAD INDEX OF LESS THAN 25 AND SMOKE DEVELOPED INDEX OF LESS THAN 50 AS TESTED PER ASTM E84.
6. FIELD APPLIED FINISH EXPOSED TO THE WEATHER: PROVIDE FIELD APPLIED ALUMINUM JACKET FOR ALL REFRIGERANT PIPING LOCATED OUTDOORS.
ADHESIVE TAPE SHALL NOT BE PERMITTED.
7. SYSTEM SHALL BE LEAK TESTED, EVACUATED, AND CHARGED PER CORNELL STANDARDS.
PIPING ACCESSORIES SCHEDULE AND SPECIFICATIONS
TAG DEVICE ACCEPTABLE MANUFACTURERS
BOD
MANUFACTURER MODEL PRESSURE RATING SPECIFICATIONS
V-1 SHUT-OFF BALL VALVE, NPS 1/2 - 2 INCH, WATER AND LOW PRESSURE STEAM SERVICE APOLLO, WATTS WATTS B6000-SS 300 PSIG WOG, 150 PSIG WSP MSS SP-110, 2-PIECE, STANDARD PORT, BRONZE BODY, 316 SS BALL & STEM,
PTFE OR TFE SEAT
ST-1 STEAMTHERMOSTATIC RADIATOR STEAM TRAPS ARMSTRONG, HOFFMAN, SPIRAX-SARCO HOFFMAN 8C 125 PSI, 353 °F BODY/COVER/TAILPIECE: BRASS, THERMOSTATIC ELEMENT: STAINLESS STEEL
RV-1 THERMOSTATIC RADIATOR VALVE WITH VALVE MOUNTED DIAL AND REMOTE SENSOR DANFOSS, HONEYWELL DANFOSS RA2000 15 PSIG STEAM PRESSURE, 250 °F ANGLED BODY, TWO PART ASSEMBLY CONSISTING OF THE BRASS VALVE BODY
AND THERMOSTATIC OPERATOR. THE BRASS VALVE BODY SHALL HAVE A
PACKING GLAND ASSEMBLY CAPABLE OF REPLACEMENT WHILE THE SYSTEM IS
IN OPERATION.
1 4/13/18 PROGRESS REVIEW
2 4/20/18 ISSUE FOR 90% REVIEW
3 4/30/18 ISSUE FOR COORDINATED REVIEW
4 5/7/18 ISSUE FOR CONSTRUCTION
CORNE
LL U N I V
E
RSI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.IPP.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
DAY HALL
DAY HALL
BOARDROOM 316
HVAC UPGRADES
E-001
-
GENERAL
NOTES AND
SYMBOL
LEGENDS
H. TRAN
JD
2026
MAY 7, 2018
GENERAL ELECTRICAL NOTES
1.0 ELECTRICAL SCHEMATICS INDICATED ON CONTRACT DOCUMENTS ARE
DIAGRAMMATIC. IT IS NOT THE INTENT TO SHOW EXACT OR MOST EFFICIENT
ROUTING. VERIFY ALL DIMENSIONS AND FIELD CONDITIONS ON SITE. ANY
CONFLICTS BETWEEN CONSTRUCTION DOCUMENTS AND FIELD CONDITIONS SHALL
BE BROUGHT TO CORNELL'S PROJECT MANAGER FOR RESOLUTION BEFORE WORK
PROCEEDS.
2.0 ASSURE PUBLIC AND WORKER SAFETY AT ALL TIMES. PROTECT ADJOINING AREAS
FROM DAMAGE AND DUST. REMOVE ALL DEBRIS FROM SITE AND DISPOSE OF
WASTE MATERIAL IN A SAFE MANNER. KEEP THE PREMISES FREE OF DEBRIS FROM
THE EXECUTION OF WORK. DELIVER A FINAL PRODUCT THAT IS CLEAN AND
OPERABLE.
3.0 FIRE STOP ELECTRICAL PENETRATIONS THROUGH FIRE RATED WALLS AND/OR
FLOORS WITH MATERIAL EQUAL IN RATING TO THE CONSTRUCTION OF THE
MATERIAL PENETRATED. REFER TO A-001, NOTE # 8 FOR LABELING
REQUIREMENTS.
4.0 WORK SHALL BE COMPLETED AS SPECIFIED AND INDICATED ON CONTRACT
DOCUMENTS. ANY SUGGESTED ALTERNATE MANUFACTURER OR METHOD OF
INSTALLATION SHALL BE SUBMITTED TO PROJECT ENGINEER FOR APPROVAL
PRIOR TO ORDERING ANY MATERIALS OR COMMENCING EXECUTION OF WORK.
5.0 GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLE 250. PROVIDE
EQUIPMENT GROUND CONDUCTOR WITH EACH BRANCH CIRCUIT INDICATED ON
CONTRACT DOCUMENTS. EQUIPMENT GROUND CONDUCTOR SHALL BE ROUTED
WITH ASSOCIATED PHASE CONDUCTORS.
6.0 PROVIDE A NEW TYPED PANELBOARD DIRECTORY FOR EACH PANELBOARD. LABEL
ALL NEW DEVICE FACEPLATES WITH SOURCE AND CIRCUIT NUMBER. PROVIDE
PERMANENT LABEL ON SWITCHING DEVICES INDICATING EQUIPMENT SERVICE AND
INVENTORY NUMBERS. COORDINATE EQUIPMENT INVENTORY NUMBERS WITH
CORNELL UNIVERSITY'S MECHANICAL SHOP, 255-8667.
7.0 CIRCUITS RATED 20-AMP, 120 VOLT SHALL CONTAIN SEPARATE NEUTRAL
CONDUCTORS.
8.0 CONDUCTORS SHALL BE A MINIMUM OF 12AWG, STRANDED COPPER, 600VAC, 90
DEGREE C, TYPE THHN/THWN-2 FOR DRY AREAS AND XHHW/THWN-2 FOR WET
AREAS.
9.0 CONDUITS SHALL BE A MINIMUM OF 3/4 INCHES DIAMETER. CONDUITS SHALL BE
ELECTRICAL METALLIC TUBING (EMT) AND SURFACE MOUNTED UNLESS NOTED
OTHERWISE.
10.0 AIC RATING OF NEW CIRCUIT BREAKERS SHALL MATCH RATING OF RESPECTIVE
PANELBOARD. SIZE AS INDICATED.
11.0 PROVIDE PULL STRING THROUGH NEW CONDUIT AND BOXES. PROVIDE SUPPORT
HANGERS FOR CONDUIT AS NEEDED.
12.0 INSTALL RACEWAY SYSTEMS ENSURING PROPER ACCESS TO EQUIPMENT AND
DEVICES AND WITH SUFFICIENT SPACE TO PERFORM ROUTINE MAINTENANCE AND
REPAIR. RACEWAYS THAT ARE NOT INSTALLED WITH THIS REQUIREMENT IN MIND
SHALL BE RELOCATED AT NO EXPENSE TO THE UNIVERSITY UNTIL DEFICIENCIES
ARE CORRECTED.
ELECTRICAL SCOPE OF WORK
1.0 PROVIDE ELECTRICAL SUPPORTS TO IMPROVE COOLING AND VENTILATION OF
BOARDROOM 316.
ELECTRICAL LEGEND
LIGHTING LEGEND
MOTOR
1'x4' LUMINAIRE
HARDWIRED EQUIPMENT CONNECTION
P-1A12
HOMERUN TO PANEL P-1A, CIRCUIT #12. FED
FROM 20A -1P BREAKER IS INTENDED UNLESS
NOTED OTHERWISE. RUN GREEN WIRE GROUND
FOR ALL CIRCUITS. PROVIDE ONE GROUND PER
CIRCUIT.
EMERGENCY POWER OFF (EPO)
GROUND ROD ELECTRODE
DUPLEX RECEPTACLE WITH GFCI PROTECTION
DUPLEX RECEPTACLE WITH AFCI PROTECTION
QUAD RECEPTACLE
LINETYPES LEGEND
SPECIAL RECEPTACLE5-30R
PANELBOARD
JUNCTION BOX
B = INSTALLED IN BASEBOARD
TR = INSTALLED IN WOOD TRIM/CASEWORK/WAINSCOTT
SR = SURFACE RACEWAY
WP = WEATHERPROOF
AC = AIR CONDITIONER
X
DUPLEX RECEPTACLE:
DOUBLE DUPLEX RECEPTACLE
MOTOR STARTER
J
2'x4' LUMINAIRE
CEILING MOUNTED LUMINAIRE
EM LIGHTING BATTERY UNIT
COMBO EXIT SIGN/EM LIGHTING BATTERY UNIT
SINGLE FACE, WALL MOUNT EXIT SIGN
DOUBLE FACE, WALL MOUNT EXIT SIGN
SINGLE FACE, CEILING MOUNT EXIT SIGN
DOUBLE FACE, CEILING MOUNT EXIT SIGN
LIGHT SWITCH:
SAFETY SWITCH (NON-FUSED)
SAFETY SWITCH (FUSED)
X
3 = 3-WAY SWITCH
4 = 4-WAY SWITCH
D = DIMMER SWITCH
O = WALL SWITCH OCCUPANCY SENSOR
V = WALL SWITCH VACANCY SENSOR
W = WIRELESS SWITCH
S = WIRELESS SCENE SWITCH
WIRELESS OCCUPANCY SENSOR
WIRELESS DAYLIGHT SENSOR
OS
W
DS
1'x2' LUMINAIRE
FIRE ALARM LEGEND
FIRE ALARM CONTROL PANEL
BATTERY CABINET
WATER FLOW SWITCH
MUXPAD
REMOTE ANNUNCIATOR
D = DUCT SMOKE DETECTOR
R = RELAY BASE
BR = BEAM RECEIVER
BT = BEAM TRANSMITTER
SB = SOUNDER BASE
SMOKE DETECTOR:
TAMPER SWITCH
AUDIBLE NOTIFICATION APPLIANCE
FACP
BATT
MUX
FAA
NAC PANELNAC
MANUAL PULL STATIONF
S X
F = FIXED TEMPERATURE
R = RATE OF RISE
R/F = COMBINATION RISE/FIXED TEMPERATURE
HEAT DETECTOR:
H X
CARBON MONOXIDE DETECTORCO
AM
F
XXcd
C
FS
F
S
XXcd
C
TS
ADDRESSABLE MODULE
XXcd = CANDELA
C = CEILING
COMBO A/V NOTIFICATION APPLIANCE:
XXcd = CANDELA
C = CEILING
VISUAL NOTIFICATION APPLIANCE:
SUPPRESSION SYSTEM
ELECTRICAL ABBREVIATIONS
AC AIR CONDITIONER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT INTERRUPTER
AMM ADDRESSABLE MONITOR MODULE
AOM ADDRESSABLE OUTPUT MODULE
ARB AUXILIARY RELAY BOARD
ATS AUTOMATIC TRANSFER SWITCH
B BASEBOARD
BKR BREAKER
C CONDUIT
CD CANDELA
CKT CIRCUIT
CR CONTROL RELAY
EC ELECTRICAL CONTRACTOR
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF STATION
FAA FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FSD FIRE SMOKE DAMPER
GAA GENERATOR ALARM ANNUNCIATOR
GFI GROUND FAULT INTERRUPTER
GND GROUND
HP HORSEPOWER
KW KILOWATT
LC LIGHTING CONTACTOR
LFMC LIQUID TIGHT FLEXIBLE METALLIC CONDUIT
LTG LIGHTING
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUG ONLY
MTS MANUAL TRANSFER SWITCH
NAC NOTIFICATION APPLIANCE CIRCUIT
NIC NOT IN CONTRACT
OE OVERHEAD ELECTRIC
PC PHOTOCELL
PM PLUGMOLD
PP POWER PANEL
PVC POLYVINYL CHLORIDE CONDUIT
RGS RIGID GALVANIZED STEEL CONDUIT
SR SURFACE RACEWAY
ST SHUNT TRIP
TM THERMAL MAGNETIC
TR TRIM/CASEWORK/WAINSCOTT
TSP TWISTED SHIELDED PAIR
TYP TYPICAL
UE UNDERGROUND ELECTRIC
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VA VOLT AMPS
WP WATERPROOF
UNDERGROUND ELECTRICUE
UNDERGROUND LIGHTINGUL
OVERHEAD ELECTRICOE
TO BE PROVIDED
DEMOLITION / TO BE RELOCATED
EXISTING TO REMAIN
UNDERGROUND TELCOUC
MOUNTING HEIGHTS
CARD READER 48" TOP OF BOX
LIGHT SWITCH 48" TOP OF BOX
RECEPTACLE 18" TOP OF BOX
DATA OUTLET 18" TOP OF BOX
TV OUTLET 84" TOP OF BOX
PHONE OUTLET 48" TOP OF BOX
SAFETY SWITCH 60" CENTERLINE OF HANDLE
MOTOR STARTER 60" CENTERLINE OF HANDLE
PANELBOARD 72" TOP OF PANELBOARD
MANUAL PULL STATION 48" OPERABLE HANDLE
NOTIFICATION APPLIANCE 80" BOTTOM OF LENS
DOOR HOLD OPEN COORDINATE IN FIELD
EM BATTERY UNIT 96" BOTTOM OF UNIT
EM REMOTE UNIT 102" BOTTOM OF UNIT
EXIT SIGN 96" BOTTOM OF UNIT
LIGHT POLE WITH LED LUMINAIRES, REFER TO
PLANS FOR NUMBER AND CONFIGURATION OF
HEADS
GENERAL ELECTRICAL DEMOLITION NOTES
1.0 ELECTRICAL EQUIPMENT SHOWN DASHED ON DEMOLITION DRAWINGS, INCLUDING
ASSOCIATED ANCHORS, SUPPORTS, STRAPS, BOXES, FITTINGS, AND OTHER
APPURTENANCES NOT SHOWN, SHALL BE DISCONNECTED AND REMOVED.
REMOVE ASSOCIATED BRANCH CIRCUITRY TO SOURCE, UNLESS NOTED
OTHERWISE.
2.0 EXISTING RACEWAYS AND DEVICE BACKBOXES NOT INTERFERRING WITH NEW
WORK SHALL BE REUSED WHERE POSSIBLE.
3.0 PROVIDE JUNCTION BOXES, RACEWAYS, AND WIRING TO MODIFY/EXTEND EXISTING
SYSTEMS AND CIRCUITS FED DOWNSTREAM OF ELECTRICAL EQUIPMENT SHOWN
TO BE DEMOLISHED.
4.0 CUT DEMOLISHED CONDUITS INSTALLED THRU WALLS AND FLOORS FLUSH WITH
THE SURFACE AND PATCH PENETRATIONS (FIRESTOP IF LOCATED ON A FIRE
RATED SURFACE). PATCH AND PAINT SURFACES IN EXPOSED AREAS TO MATCH
SURROUNDING MATERIALS, FINISHES, AND COLORS.
5.0 PROVIDE BLANK COVERPLATES ON UNUSED BACKBOXES REMAINING FROM
DEMOLITION NOT SPECIFIED TO BE INFILLED.
6.0 EXISTING EQUIPMENT SHOWN TO REMAIN SHALL BE PROTECTED DURING
CONSTRUCTION.
1 4/13/18 PROGRESS REVIEW
2 4/20/18 ISSUE FOR 90% REVIEW
3 4/30/18 ISSUE FOR COORDINATED REVIEW
4 5/7/18 ISSUE FOR CONSTRUCTION
300EA
316 317A
317B
317C
317
317D
317E
314A
314B
314
314C
314D
314F
300SA
300TA
300TC
300CA
308
308A
EXISTING
PANEL 314F
1
1
EXISTING RECESS
MOUNTED
LUMINAIRES TO
REMAIN (TYP. 10)CORNE
LL U N I V
E
RSI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
N
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.IPP.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
DAY HALL
DAY HALL
BOARDROOM 316
HVAC UPGRADES
E-101
-
PARTIAL 3RD
FLOOR
DEMOLITION
PLAN
H. TRAN
JD
2026
MAY 7, 2018
#E-101 KEYED DEMOLITION NOTES
1 EXISTING PTAC HEATING/COOLING UNITS TO BE REMOVED BY OTHERS.
ELECTRICAL CONTRACTOR TO REMOVE EXISTING POWER WIRING BACK TO PANEL
314F. CUT POWER CONDUITS FLUSH TO FLOOR LEVEL. THE REMAINING CONDUITS
TO BE ABANDONED. FIRE CAULK THE CONDUITS AT FLOOR LEVEL AS REQUIRED.
0 4 8 16
SCALE: 1/8"=1'-0"
SCALE: 1/8" = 1'-0"1 3RD FLOOR DEMOLITION
1 4/13/18 PROGRESS REVIEW
2 4/20/18 ISSUE FOR 90% REVIEW
3 4/30/18 ISSUE FOR COORDINATED REVIEW
4 5/7/18 ISSUE FOR CONSTRUCTION
317C
317
317E314C
300SA
300TC
300EA
316
317A
317B
317D
317E
314A
314B
314
314D
314F
300TA
300CA
308
308A
BRANCH BOX
EXISTING
PANEL 314F
1
NEW CEILING CASSETTE
INDOOR UNIT
(TYP. X 4)
7
400EA
ROOF
448
453
451
449B
449
446
400SA
440B
EQUIPMENT
ENCLOSURE
8
4
NEW CONDENSING UNIT
2
5
3
6
ENERGY RECOVERY
VENTILATOR (ERV)
UNIT ON ROOF
CONDUIT ABOVE
DOOR
5
9
E-102 KEYED CONSTRUCTION NOTES
1 UTILIZE THE EXISTING 50A/2P CIRCUIT BREAKER IN THE PANEL TO FEED THE NEW
CONDENSING UNIT LOCATED ON ROOF (ABOVE ROOM 314F). FROM PANEL, PROVIDE
(3) 6 AWG AND (1) 10 AWG GROUND IN 1” EMT UP TO THE FOURTH FLOOR. PAINT
CONDUT TO MATCH WALL. SEE NOTE 2.
2 EXTEND THE CONDUIT AND POWER WIRING UP TO A POINT ABOVE DOOR AND
PROVIDE A 2”X4” JUNCTION BOX (WHITE). PAINT CONDUIT TO MATCH WALL THRU
FLOOR PENETRATION IN THE LOCATION WHERE THE TILE HAS BEEN REMOVED.
3 AT 4” AFF, PROVIDE A 2”X4” JUNCTION BOX (WHITE) AND EXTEND CONDUIT AND
POWER WIRING TO THIS LOCATION.
4 CORE DRILL THRU WALL AND EXTEND CONDUIT AND POWER WIRING AS INDICATED.
5 PROVIDE 2”X4” NEMA 3R JUNCTION BOX AND EXTEND CONDUIT AND POWER WIRING
TO THE CONDENSING AS INDIDCATED. EXTERIOR CONDUIT SHALL BE RGS.
CONDUIT SHALL BE SUPPORTED BY PANTAIR, CADDY PYRAMID EZ RUBBER BASE
ADJUSTABLE SUPPORTS CAT. NO. RPSE1H24.
6 FROM CONDENSING UNIT, PROVIDE (3) 6 AWG AND (1) 10 AWG GROUND IN 1” RGS
TO A POINT INSIDE THE EQUIPMENT ENCLOSURE AND EXTEND DOWN TO THE
BRANCH BOX LOCATED ON THE CEILING OF ROOM 316. COORDINATE FOR THE
ROOF PENETRATION.
7 BRANCH BOX BY MECHANICAL CONTRACTOR. FROM BRANCH BOX, PROVIDE
HONEYWELL 14/4C POWER AND CONTROL CABLE TYPE TC UL 1277 IN ¾” EMT TO
EACH OF THE CEILING CASSETTE INDOOR UNIT AND MAKE POWER CONNECTION AT
BOTH ENDS. CONDUIT RUNS SHALL RUN PARALLEL WITH THE NEW HVAC PIPING. AT
EACH UNIT, PROVIDE A BUSSMANN SKA DISCONNECT SWITCH WITH (2) 1A
FUSETRON FUSES.
8 THE ERV IS LOCATED INSIDE OF THE EQUIPMENT ENCLOSURE. INSIDE OF THE
ENCLOSURE, PROVIDE A DUPLEX RECEPTACLE. CIRCUIT TO NEAREST RECEPTACLE
CIRCUITRY IN BOARDROOM 316 OR THE UNSWITCH LEG OF BOARDROOM 316
LIGHTING CIRCUITRY. COORDINATE WITH MECHANICAL CONTRACTOR FOR THE
ROUTING OF THE CONDUIT. PROVIDE (2) 12 AWG AND (1) 12 AWG GROUND IN ¾” EMT
AS REQUIRED.
9 AT THE NEW CONDENSING UNIT, ELECTRICAL CONTRACTOR TO PROVIDE A
DISCONNECT SWITCH IN A NEMA 3R ENCLOSURE, SQUARE D CAT NUMBER H222N.
INSIDE OF SWITCH PROVIDE THREE 50A DUAL ELEMENT TIME DELAY FUSES.
COORDINATE WITH MECHANICAL CONTRACTOR FOR THE MOUNTING OF THE
DISCONNECT SWITCH.
#
0 4 8 16
SCALE: 1/8"=1'-0"CORNE
LL U N I V
E
RSI
TYFOUN
D E D 5681AD
FACILITIES
ENGINEERING
N
ARCHIVE BAR CODEITHACA, NEW YORK
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
DATE:
FACILITY:
DESIGN:
DRAWN:
WWW.IPP.CORNELL.EDU
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT THEIR SEAL AND THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE, THE DATE OF SUCH ALTERATION, AND
A SPECIFIC DESCRIPTION OF THE ALTERATION.
WARNING
REVISIONS
ARCHITECTURAL, STRUCTURAL,
CIVIL, ENVIRONMENTAL,
MECHANICAL, AND ELECTRICAL
ENGINEERING
201 HUMPHREYS SERVICE BLDG
ITHACA, NEW YORK 14853-3701
DAY HALL
DAY HALL
BOARDROOM 316
HVAC UPGRADES
E-102
-
NEW WORK
PLANS
H. TRAN
JD
2026
MAY 7, 2018
SCALE: 1/8" = 1'-0"1 3RD FLOOR NEW WORK
SCALE: 1/8" = 1'-0"2 4TH FLOOR NEW WORK
1 4/13/18 PROGRESS REVIEW
2 4/20/18 ISSUE FOR 90% REVIEW
3 4/30/18 ISSUE FOR COORDINATED REVIEW
4 5/7/18 ISSUE FOR CONSTRUCTION
CORNELL UNIVERSITY DAY HALL BOARDROOM 316 HVAC UPGRADES
ADDENDUM NO. 1
May 16, 2018
This Addendum contains changes to the requirements of the Contract Documents and Specifications. Such
changes are to be incorporated into the Construction Documents and shall apply to the work with the same
meaning and force as if they had been included in the original document. Wherever this Addendum
modifies a portion of a paragraph of the specifications or a portion of any Drawing, the remainder of the
Paragraph or Drawing shall remain in force.
NOTE: Provisions of all Contract Documents apply.
Item 1. Drawing A-101:
ADD the Following note:
10. Provide (2) acoustical panels at the ceiling above the boardroom table. Panels shall
be Sound Quality Architectural Acoustical Products brand, Model S-2000. Each panel
shall be 42” x 96” x 2” (field-verify width) and shall incorporate the radius edge detail.
Each panel shall be located on either side of the existing track lighting, centered between
the track and the existing soffits, and centered along the length of the table. Color to be
selected by Owner. Attach to existing 1 ½” thick cork ceiling with 2-part mechanical
clips (EC-1 clips and EC-4 bars), which shall be anchored into the deck above the cork.