HomeMy WebLinkAboutCU Willard Straigth Hall - Dining ExhaustPEL
CORNELL UNIVERSITY
WILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST SYSTEM IMPROVEMENTS PROJECT
GENERAL NOTE
THIS PROJECT DOES NOT INCLUDE AN ocrENSrvE CODE REVIEW OF THE EXISTING
FAICILRY FOR COMPLIANCE. ONLY THE CODE COMPLIANCE OF THE PROJECT SCOPE;
REPLACEMENT OF THE KITCHEN HOODS AND ASSOCIATED EXHAUST SYSTEMS, IS
REFLECTED IN THESE DOCUMENTS.
DRAWING INDEX
DWG. NO. DRAWING NAME
CURRENT CURRENT
REVISION REVISION DATE
TS001
A000
A001
A101
A102
M000
MD101
MD102
M101
M 102
M500
M501
M502
M503
M504
M505
M600
M700
E000
ED101
ED102
E100
E101
E102
E600
TITLE SHEET
ARCHITECTURAL LEAD SHEET
ARCHITECTURAL SCHEDULES AND DETAILS
ARCHITECTURAL THIRD FLOOR PLAN
ARCHITECTURAL PARTIAL SIXTH FLOOR DEMOLITION & INSTALLATION PLAN
MECHANICAL LEAD SHEET
MECHANICAL DEMOLITION THIRD FLOOR PLAN
MECHANICAL DEMOLITION PARTIAL FOURTH, FIFTH & SIXTH FLOOR PLANS
MECHANICAL THIRD FLOOR HVAC PLAN
MECHANICAL PARTIAL FOURTH, FIFTH & SIXTH FLOOR HVAC PLANS
MECHANICAL DETAILS
MECHANICAL DETAILS - HOODS #1 & #2
MECHANICAL DETAILS - HOOD #3
MECHANICAL DETAILS - HOODS #4 & #5
MECHANICAL DETAILS - HOOD # 6/7
MECHANICAL DETAILS - HOOD #8
MECHANICAL SCHEDULES
MECHANICAL HVAC EXHAUST AIR FLOW DIAGRAM
ELECTRICAL LEAD SHEET
ELECTRICAL DEMOLITION THIRD FLOOR PLAN
ELECTRICAL DEMOLITION PARTIAL FOURTH, FIFTH & SIXTH FLOOR PLANS
ELECTRICAL SECOND FLOOR PLAN
ELECTRICAL THIRD FLOOR PLAN
ELECTRICAL PARTIAL FOURTH, FIFTH & SIXTH FLOOR PLANS
ELECTRICAL SCHEDULES
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
05105117
05105117
05105117
05105117
05105117
05105117
05105117
05105117
05/05/17
05/05/17
05105117
05105/17
05105/17
05105/17
05105/17
05105/17
05105117
05105/17
05105/17
05105/17
05105/17
05105/17
05105/17
05105/17
05105/17
r_r�����x_r_r_r ........................
.:,,:xxxm:x«,x«,,x«�x��u,x«,x«,x«,x«,x«,xx,x«,x«,x«,x«,x«,x«,x«,x«,x«,x«,x«,x«,xw�,x««,x«a.�'xua.«,x«,x«��suzu��
w�u,x««.>r.��«.>r.„«>r.��«.>r.��«.>r.��«.>r.��«.>r.��«.>r.,x«,x««,x.,x«,x���,x«,x�,x«�zcauxcouxc � x ���xx z���a�wu,x«,x«,x«,x«
«wx�,xm,x« 5iiu �a «,x« �szu z,,:x zua.�i� �,x«,xmgnm,x«,x«,x«,x«� uuhh idd «,x«,x«,x
«,x«,x��s���s�m,x«,x«ouxce�.Ma^nxc s«««,x«,x«,x«,x«,x«,x«,x«,x«,x«,x«��������s"x«,x«,x«,x«,x«,x«,x«
�x� �,x«,x«�xua.��xua.��x�,x«,xu z,,x«,x«,x�szu,x«,x«,x«,x«,x«,x«,x«,x«,x«,x«,x«, ngn zv= a �,x«,x«,x«,x«,x«,x«,x
�x����«,x«,xce���������«,x«� co;._«>rm,�«,.,.�«««,x«,x«,x«,x«,x«,x«,x«,x«,x«,x«,x«,x��s��xs�x c�ux.,.,m.�«�«
cex,x,x,,xm,xcex,x,x,x,x,xm,x,�kuxxx:m:::::x:m:xxx:«,xce,x«,x«,x«,x«,x«,x«,x«,x«,x«,x«,x«,x«,x« ,x,:xxx:,,:xx,x«,x«,x«,x«,x«,x«x:,,:x�,x
A^a,R. M. M.o^«M...«.M...«.....«..x....xx x..a, . M, ..«....,,,,,,«, ,,,, ,,,,,,,,, x«,,%cA.«.M...«.Ma,«.M«,x«,x«,x«.M«,x.....«.M«,x«,x« ««,x«,x«,x.A.«.M...x„x. ,.M«,x«.M«,x«M...«.M.o .
x«,x«,x«,x.e,,,..........e «,x«x:.,:xxx:.,:xxx:.,:, «,,,,,,,x«,,,,, x,,,,a.,cx,,,�x«,x«,x«,x«,�v,x«,x«,x.e,x«,x«,,,,. x«,x«,x«,x«,x«,x«,x.,,x«,ox ,x«:xxx:.,,x«,x«,x«,x«,x«,x«,x«,x«,x
r«ux«x:m:xx,x...............ex:.,. x ,MSM ��x� � � � X. MS,,�x��uu.xx:., Ozu x:.,:xxx:.,:xx:
. 2:.. 2sBMs......«.,x.....a,x...e,x«.M.................. wSMSMT �T °M.Rs� .K. ..e xa^a'¢ 2:.. ...M...«.M.o...
.�..... ,mMm^mMm,xm,x xmMm,.mMm«.mMm^aMa^m.,.....mMm^aMa^aMa^aMa^m
YO.Y .....'.e....x'..e,�«,x....x:.,:xxx:.,:, .,x.e,x«,x«,x.e,xS� �'xua. 'xu 'xua. ua. 'xu,., 0 X. O. ,... .x.e,x«,x«,x.,: xx:.:,x«,ox,o x«,x.e,,x«.:.�,x«,x«,x«,x«,x«,x«,x«,x«,x
k%SO2:.. SCO:.... ...�,.rcm,.:.....cevm,.. ................:... rcms... SMSMSMSMSMSMSMSMSMSM � x.m%09%2:.. .. ^'m,.rc.. .:::................m,................rcvm
.,k'k0.k'km,«mSM..,««,«m:xxx:m,«xx:m:xxx:.,:xxx::::::::x.m:xxx:m:xr�rxm, SMSMS,� �S,S S MSWMS, �Sm,?'3Yu�"x:.,:xx::::.::::::::::::::::
x:2:. 5 x%r.SMSMS«,x.......»» x. M. M. M...axe:ou nw � � s,��s,�Ts� �Ts� �Rs� �Ts�a mmux c2ux«a M«.,.....,......
.,«.^. .^�..,«^�..,«^�..,........«m^aMa^aMa^aMa^aMa^aMa^aMa^mMm^m
":ux.MSMSMSMSMSA,«m,«m,«m,«m.x'..,«m,«m,«m,«m,«m,«m,«m"*.,'. SMS SMSMSAAAA°'uu:".','k z,««x:.,:x... xxx:.,:, -.,:xxx:.,:xxx:.,:xxx:.,:x::,«m,«m,«m,«m,«m,«5..'.'m,«m,«w,«m,«m,«m,«m,«.,:x
k%cece � SMSMSMSm,«m,«m,«m,.mvm,«m,«m,.mvm,........:i....... SMSMSMSMSMSMSMSMS3, M ...f"'O'k%•;,«rc am.. �..,. n.�ry �mw
xx.Y ;SMSMSMSMSq,«m,«m,«m,«m,«m,«m,«.,:xxx:.,:xx::.,:xxx:.:xxx:m,«ce $ $ $ $,$ S,W8, x.ce ce «m,«gx:., kxr�.
,uxcoxSMSMSMSMSM?
wm,xm,xm,xm,xm,xm^wMm^m,.,^m,xm^wno���s���s�m,xm,xm,xm,xmow'ecoy�m......,...
�x=Ngn � � � u,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,x „xm,xm,x 2 qua. ,qua. ,xm,xm,xm,xm,xm,xg4VX:xm,xm:xx:
nxcou'xm,�o�����,x,x�������,�m,xm,xwo�m,�mmxcourm,.mw.,.,
x:,,:x ,xm,k�x�xu;:;x:,,:xxx:,,:x«...................................
xmxxxmxx xxmxxxmxxxmx«xmxxxmxxx m�m xmxxxm
............................ .
«N„xceNm,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm�,�u;m,xm,xm,xm,xm,xm,xm:x x x:.,:x x
:..:.
x%nnm
�,km
.m x«
w x:.,:x«x:v;x m,�NgNN.„xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,xq.::::::x:-.,:xx:::::::::::x.,:xx,xm,x�,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,x .MgN u, �,�m,xm,xm,xm:xxx:.,:xm,xm,xm,x� .�gm mN.,:xxx:.,:xxx:.,:xxx:.,:x.::::::::::::.::..
. .................... .
ce% .%����m�m�m�m�m�m�m�m�m�m�m�m�m�m�mnxMm^mMm^mMm^mMm�m�m�m�m�m�m�m�m�m�m�m�m����a������������m�m�m�m�mMm^mMm�m�m�
xun �zux �,km,xm,xm,xm,xm,x«x:m:xm,xm,xm,xm,�m,xm,xm,xm,� �xu��x�x �,xm,xm,xm,xm,����,xm,xm,xm,xm,xm,xm,xm,xm,xm:x x x:.,:x
•
«,x.MSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMS SMSMSMSMSM°M43 M..
»« 43 4«*M*3MS3SMSMSMSM MSMSMSMSMSMSMSMSM M MSMSMSM MSMS3.o
=MIUMMAua.NWaua.NFMNua.UMMUUMUM
mumumanuar,x«,xwmu�xm,x������������woux�co;
« � ua.��xua.��xua.��xua «,x«,x«,x«,x«,x.e.mmu �g�,x«,gmi
��x�x�x�x�x�x�x��«,x«,x«,x«,x«,x«,x«,x����«,x«,x«,x«,xwx�coy�o
m o;,«m,«m,«m,«m,«m,«m,«m,«m m,«
'°"8���92�ce�92����,«m,«m,«ce�9"«mg m,«ce�92,«m,«
««x
mk: SMSMSMSMM.Ai'.3xx:.,:::'ax:u:xxx:.,:xxx:.,:xxx:.,:xxx:.,:xxx:m:xxx
:xuS3.2xz2xzu:xm,xm,xm,xm,xm,xm,xm=.=":-
xm:x �.xm:xx: x.
«m.m.m.m.m.m.m.m.m.m.m.m..,:x x x m x x .m.m.m
, ;O yu; ,x.,xm,xm,xm,xm,xm,xm:xm,xm,xm,xm,xm,xm,xm,xu; yu p, m,��, u,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,x� � � � � � � � ��.m,xi',xm,xm,xm,xm,xm,x^,�.�,xm,xm,xm,xm,xm,xm,xm.X" .
ceoxKm,%,m.m,.mm,.mm,.mm,.mm,.mx<� m.m,xmx,ox%,xx,ox%m,.mm.mmm.m.m.m.m.m.m.mm.m...:xx �m�m.�.,,.� ,
nm,.mm,.mm,.mm�m�m�m�m,.m^�....�.m�m,.m mm�m�m,.m�m��� u_
'xu,,zu,,z,,x.,,,,,zu,,,mw.:.,,xm,xm,xmx;m,xm,xm,xm,xm,xm,xm,xm,x,,,,,,,,,,,,,,,,,am,x.�,xm,xm,..::::::::::::::::::::: vc «.ic. x::::::::::::::::
mx.axxxoxxm «o,� o.aMa o.aMa o.aMao«.. o.......moux coax co... Mm,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm,xm'k,,,,,,,,sxmm,xmM«............... `•.rem. m
,x,xu zu nzv,xm,xm,xmm,xm,xm,xm,xm,xm,x,x,,,,,,,,,,,,,,,,,a m,x�,x
mxx^xxx^mc«.,.mxm..m�«m,xm,xm,xm,xm,.mx«.,..x,,«.«.m�k,,,,,,,,,ss:,,,..m,x«.:.,: o.�;«.o,;«o a:.: ,...,..,,..
xm,xm,x.. x.m.x x....,.xxx.m.xxx.m.x xx.m........ x........_ ,,._. ,,, „ aim
.,x.,...,.:,,m,.m�m,.m�m,.m�mm..m�m,.,..,: m..,..,:mw,.:,:.;.,.mem,.mem,.mem,..m�m,.m��m,.m�m,.m�m,.
. ..... ........... ........ ................-m:x x x:m:x x x:m:x x x:m:x x x:m:x x x:m:x x x:m:x x x:m:x x x:m:x x x:m,x x x:m:x«x:m:x«:-m:x x x:,,:x x x:m.xm.xm.xm,xm:x x x:,,:x x,xm,xm,x�
........ x�x�x�x�xq,��x�,xm,xmx:«::::: x:. .. :xxx:m:xxx:m�xx�: �,.�
zu��z
.xxmxxx., ,xxmx—xxx,,xxx,,xxx,,xxx,,xxxmxxxmxx mxxxmx .,,xxx M M q.u��
n== =
Nim .N.,k.,.ti,uNv...^Nv...^..
APPROX. AREA OF WORK
WILLARD STRAIGHT HALL
»$ce3: F
si:9�x�a.�xux rexx�
%X114
LOCATION MAP
ORIGINAL SHEET -ARCH a
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICO T, NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractor shcJ verify and be responsible for all dimensons. DO
NOT scale the drawing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and drscwflgs are the property of
Stcntec, Reproduction or use for any purpose other than nkat
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
Permit -Seal
by Appd. rf.MM.DO
GPS RJK 17.05.05
by
Appd. Y't.MM.DO
Own. Chkd. Dsgn. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
WILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
GENERAL
TITLE SHEET
Project No.
191001394
Scale
AS NOTED
Drawing Na. Sheet Revision
TSOO 1 of O
ABBREVIATIONS
A
ABC
ACC
ACOUS
ADD
ADJ
ADJUST
A.F.F.GGR
ALT
AP
APPROX
ARCH
ATC
AVG
B
BD
BET
BIT
BLBD
BWG
BLT{
BMG
BN
BO
BOC
BOT
BRD
BRG
BRK
MAT
BUR
c
D
CAB
CB
CCT
CKBD
CEM
CER
CF
GFMF
CG
CI
CP
CJ
CL
CLG
CLKG
CLL
CLR
CM
CMU
CO
COL
CONC
CONN
CONST
CONT
WHIR
CORA
CPT
CR
CT
CTR
CW
CY
DB
DBL
DEG
DEMO
DEPT
DET
DF
DH
DIA
DRAG
DIM
DIV
DL
DN
D.U.
DOM
DR
DS
DWG
AR CONDITIONING
ANCHOR BOLT
ACCESS
ACOUSTIC (AL)
ADDENDUM
ADJACADJUSTABLE
ABOVE NED FLOOR
ALTE• TEAWMINRNATE
ACCESS
AL
ASPHALT
AAICOUS IECAL11LE CEIUNG
BOARD
BETWEEN
BITULENOUS
BLACKBOARD
D
BUILDING
BLOCK
BENCH NIAmocia,
BULLNOSE
BOTTOM OF
BOTTOM OF CURB
BOTTOM
BOARD
BEARING
BRICK
BASEMENT
BUILT—UP—ROOF
CARNET
CATCH BASIN
CUBICLE CURTAIN TRACK
CORKBOARD
CEMENT
CERAMIC
CUBIC FOOT
COLD FORM M IAL FRAMING
CORNER GUARD
CAST IRON
CAST IN PLACE
CONTROL JOINT
CLOSET
CEILING
CAULKING
CONTRACT LIMiT LINE
CLEAR
CEIUNG MOUNTED
CONCRETE MASONRY UNiT
CLEANOUT
COLUMN
CONCRETE
CONNECTION
CONSTRUCTION
cCONTINUE EUS)
R
CORRIDOR
CARPET
CHAIR RAL
CERAMIC TILE
CENTER
COLD WATER
CUBIC YARD (S)
DOCK BUMPER
DOUBLE
DEGREES
DEMOLITION
DEPARTI TENT
DETAIL
DRINKING FOUNTAIN
DOUBLE FILING
DIAMETER
DIAGONAL
DIMENSION
DIVISION
DEAD LOAD
DOiAN
DOOR OPENING
DOMESTIC
DOOR
DOWNSPOUT
DRAWING
E
F
H
E
EA
EC
EF
EHD
EFS
EJ
EJCP
EL
ELEC
BEV
D ER
ENCL
EQUIP
EP
EPDM
EAST
EACH
ELECTRICAL CONTRACTOR
EACH FACE
ELECTRIC HAND DRYER
EXTERIOR INSULATION FINISH SYSTEM
EXPANSION JOINT
EXPANSION JOINT COVER PLATE
ELEVATION
ELEELECTRIC VATOR( }
EMERGENCY
ENCLOSURE
UAL
EQUIPMENT
ELECTRICAL PANEL
ETHYLENE PROPYLENE
DIENE MONOMER
EST ESTIMATE (D)
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
ES EXPOSED SLAB
ES GWB EXTERIOR SHEATHING
GYPSUM WALL BOARD
EW EACH WAY
EXH EXHAUST
EXIST EXIST1NG
EXP EXPANSION, EXPAND
EXPO EXPOSED
OCT EXTERIOR
EXTR EXTRUDED
FA
FAB
FAP
FC
FD
FNDN
FE
FEC
FF
FH
FHC
FIG
FIN
FIXT
FL
FLASH
FLEX
FLR
FLUOR
FM
FOC
FOM
FOP
FOS
FORM
FP
FR
FRP
FE
FiB
FiG
FURR
FLIT
FVC
FIRE ALARM
FABRICATE
RITE ALARM CONTROL PANEL
FIXTURE CONTRACTOR
FLOOR DRAIN
FOUNDATION
RITE EIDER
FIRE EXTINGUISHER CABINET
FINISHED FLOOR
FLOOR HATCH
RITE HOSE CABINET
FIGURE
FINISH (ED)
FIXTURE
FLANGE
FLASHU G
FLUME
FLOOESC T
FLUOR
FLOOR MOUNTED
FACE OF CONCRETE
FACE OF MASONRY
FACE OF PARTITION
FACE OF STUD
FACE OF WALL
FIRE PROTECTION
FRAME
FI REINFORCED PANEL
FOOT OR FEET
FIN TUBE
FOOTING
FURRING
FUTURE
MITE VALVE CABINET
GA GAUGE
GAL GALLON
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR)
GEN GENERAL
GF GROUND FACE
GL GuGLOSALLAZING
GR
GRG GLASS REINFORCED GYPSUM
GT GLAZED TILE
GTC GLAZED TILE COVERING
GNB GYPSUM WALL BOARD
GYP GYPSUM
Fe HOSE BIB
NC HOLLOW CORE
HCW HOLLOW CORE WOOD
C HANDICAPPED
FD HAND
FIIXP HANDICAPPED
FOR HEADER
HDWD
HEAVE
HGT
HM
HMI
HOR
HOPE
HP
HR
HTG
RIR
HVAC
HW
HARDWOOD
HARDWARE
HEIGHT
HOLLOW METAL
HOLLOW METAL INSULATED
HORIZONTAL
HORIZONTAL
HIGH POINT
HANDRAIL, HOUR
HEATING
HEATER
HEAIINGITILAIING/
AR NDMONING
HOT WATER
ID INSIDE DIAMETER
IN INCH OR INCHES
INCL INCLUDE (NG)
INSUL INSULATE (D), (I0N)
INT INTERIOR
INV INVERT
J
JAN
JCT
JT
K
L
JOIST
JANITOR
JUNCTION
JOiNT
KD iINOCKED DOWN
K IT KITCHEN
L
LAB
LAM
LAV
LF
LH
UN
LL
LLH
LLV
LONG
LOAN
LP
LSD
LT
LW
M
MAG
MAR
MAS
MAX
MTD
MC
LIDO
ME
MECH
LED
MEM
MEMB
MEP
MER
MET
M1�
MER
MH
MIN
LENGTH, LONG
LABORATORY
LAMINATE (D)
LAVATORY
LINEAR FOOT (FEET)
LEFT HAND
UNER
LIVE LOAD
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONGITUDINAL
LOUVER
LOAN POINT
UIQUUID SOAP DISPENSER
HT
LONG WAY
MAGNETIC
MARBLE
MASONRY
MAXIMUM
MARKER BOARD
MEDICINE CABINET
MEDIUM DENSITY OVERLAY
MATCH EXISTING
MECHANICAL
MEDIUM
MEMBER
MEMBRANE
MECHANICAL, ELECTRICAL,
PLUTABING
MECHANICAL EQUIPMENT ROOM
METAL
MIEZZANNE
MANUFACTURER
MANHOLE
MINIMUM
MIRR MIRROR
LOSC MNSCELLAFEOUS
LLDG MOULDING
MO MASONRY OPENING
MR GWB MOISTURE RESISTANT
ANT
GYPSUM WALL BOARD
MSK MOP SIFF
MTD MOUNTED
MTG MOUNTING
MTL METAL
MULL MULLION
N
N
NAT
NF
NIC
NORTH
NATURAL
NEAR FACE
NOT IN CONTRACT
NO
NOM
NORM
NTS
0
OA
OBS
OC
OD
OF
OH
OPNG
OPP
P
P LAM
PART
PRTN
PAVIIIT
PC
PCC
PCF
PERF
PERM
PIR
PL
PLAS
PLAST
PLBG
NUMBER
NOMINAL
NORMAL
NOT TO SCALE
OVERALL
OBSCUREON R)5
OUTSIDE DIAMETER
OVERFLOW
OVERHEAD
OPENING
OPPOS TE
PLASTIC LAMINATE
PARTITION
PARTITION
PAVEMENT
PLUMBING CONTRACTOR
PRECAST CONCRETE
POUNDS PER CUBIC FOOT
PERFORATED
PERMANENT
PICTURE RAIL
PLATE
PLASTER
PLASTIC
PLUMBING
PL11WD PLYWOOD
PM PICTURE MOLD
PMF PREMOLDED FILLER
PNL PANEL
PNT PAINT
POLYS POLYISOCYANURRA1E INSULATION
P&R PATCH & REPAIR
PREP
PRL
PROD
PROP
PSF
PSI
FT
PRD
PVC
PREPARE (AMON)
PIPE RAL
FROJECT (ION)
PROPERTY
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
PRESSURE TREATED
PAINTED
POLYVINYL CHLORIDE
Q
QT QUARRY TIE
R
RA
RAD
RB
RD
RECP
REF
REFL
REFR
REQ'
D
RES
RET
REV
RH
RI
RM
RO
ROW
RUBR
s%
SAS
SAD
SAN
SC
ScW
SCH
SECT
SF
SG
SGT
SHTSHWR
SLW
RISER RADIUS
RETURN AIR
RADIUS
RUBBER BASE
ROOF DRAIN
RECEPTACLE
REFERENCE
REFLECT EDD ,REFR ft OR
REINFORCE , (ING) TION
REQUIRED
RESILIENT
RETURN, RETAINING
REVISION 5), REVISED
RIGHT
RIGID INSULATION
ROOM
ROUGH OPENING
RIGHT—OF—WAY
RUBBER
90U11-1
STAINLESS STEEL
SUPPLY AIR
SADDLE
SANITARY
SOLID {SORE
SOLID CORE WOOD
SCHEDULE
SECTION
SQUARE FOOTFEEI)
SPANDREL GLASS
STRUG1URAL GLAZED TILE
SHEET
SHOWER
MAUR
SLAT WALL
SND
SNV
SP
SPEC
SPIT
SPL
55
SST
ST
STD
STL
STOUR
STR
SURF
SUSP
SW
SY
SYM
SYS
T
T&G
TB
TD
TDW
TEL
TEMP
TERR
THK
1X8
T.O.
TOC
TOL
TOM
TOP
TOS
ROW
T&P
TP
TPH
TRANS
T5
TV
INV
TYPOS
u
UC
UH
UL
UNEX
UNF
UON
UR
UV
V
VAR
YB
VC
VCT
VERT
VEST
VG
VIVO
yY4C
WNCT
WP
WT
YAW
WAWA
0
0
L
t
w
SANITARY NAPKIN DISPOSAL
SANFTAIZY NAPKIN VENDOR
SPECIAL
SPECIFICATION (5)
SPEAKER
SPANDREL PANEL
SQUARE
SERVICE SINK
STAINLESS STEEL
STREET
STANDARD
STRUCTURE (AL)
SURFACE
SUSPENDED
SWITCH
SQUARE
SYMIETRYY (TICAL}
SYSTEM
TREAD
TONGUE AND GROOVE
TOWEL BAR
TOWEL DISPENSER
TOWEL DISPENSER AND WASTE
TELEPHONE
TEMPORARY
TERRAZZO
THITS )
TOP OF
TOP OF CURB
TOLERANCE
TOP OF MASONRY
TOP OF PIER
TOP OF STEEL
TOP OF WALL
TAPE & PRIME
TOILET PARii11ON
TOILET PAPER HOLDER
IMMERSE
TERMINATION STRIP
TELEVISION
TYPICAL
TYPICAL OTHER SIDE
UNDERCUT
T
UHT HEATER
UNDERWRITERS' LABORATORIES
UNEXCAVATED
UPEINISHED
MESS OTHERWISE NOTED
URINAL
UNIT VENTILATOR
VARIES (ABLE)_
VINYL BASE
VINYL COVE
VINYL COMPOSITION TILE
VERTICAL
VESTIBULE
VISION GAM
VERIFY IN FIELD
VINYL WALL COVERING
W WEST
w/ WiH
0 WFIHOUT
WATER CLOSET
WD WOOD
WAINSCOTING
WATERPROOFED (TNG)
WEIGHT
WELDED WIRE FABRIC
WELDED WIRE MESH
AND
AT
DIAMEiER OR ROUND
PERCENT
CENTERLINEANGLE
MIENBEFORE), POUND (AFTER)
TER) UNE
SYM BOLS
000
+i4-OoIMO
COLUMN NOTATION
ROOM NUMBER
DOOR NUMBER
WINDOW TYPE
PARTITION TYPE
ACCESSORY TYPE
KEYED NOTE
ELEVATION NOTATION
START POINT
DESIGN DATUM POINT
FOR REFERENCE ONLY
BLDG SECTION NUMBER
DRAWING WHERE IiT IS SHOWN
WALL SECTION NUMBER
1 DRAWING WHERE IT IS SHOWN
INTERIOR ELEVATION NUMBER
00 DRAWING WHERE R 1.S SHOWN
EXTERIOR ELEVATION NUMBER
DRAWING WHERE RIS SHOWN
DETAL NUMBER OR
ENLARGED AREA DRAWING
WHERE IT IS SHOWN
REVISION AREA
NORTH ARROW
MATCH UNE
rrrr.rrr�f�lrrrrtrrrrrr.
EXISTiNG WALL OR ITEM TO BE
REMOVED ON DEMOLITION PLAN
DUSi1NG WALL TO REMAIN
GAB & STUD PARTITION
CMU PARTITION
BRICK & STUD CAVITY WALL
BRICK & CLAD CAVITY WM1
CLL
ALIGN
EFS & SND CAVITY WALL Ar`
EFS & XSTAU CAVITY WALL
EXISTING DOOR TO REMAIN
NEW DOOR
(MATERIAL INDICATION VARIES)
FD
0
FEC
FVC
EP
CONTRACT Li AIT LIVE
PROPERTY UMFF LMIE
CENTERLINE
BREAIIJNE
ALIGN SURFACES
OPERABLE WALL
FOLDING PARTITION
CUBICLE CURTAIN & TRACK
WIRE MESH PARTITION
FLOOR DRAM! (SEE PLUMING DIMS)
FIRE EXTINGUISHER
FRE EXTINGUISHER & CABINET
FRE VALVE CABINET
ELECTRIC PANEL
GENERAL NOTES
(APPLICABLE TO ALL CONTRACTORS)
THIS CONTRACT REQUIRES COMPLETE, FINISHED WORKABLE PROJECT OF THE AREAS INDICATED BY
THE CONTRACT DOCUMENTS, AND SHALL INCLUDE MATERIALS AND LABOR NECESSARY TO
COMPLETE, REGARDLESS OF WI-EiHER OR NOT THE WORK OR EACH ITEM IS SPECIFICALLY INDICATED
ON ANY OTHER PORTION OF THE DRAWINGS AND/OR NOTES.
WHERE MATERIALS REFERENCED ON DRAWINGS, OR NECESSARY TO COMPLETE TIE WORK OF THIS
CONTRACT PRE NOT SPECIFIED HEREIN, PROVIDE BEST QUALITY MATERIALS. WORK WHICH HAS
BEEN DAMAGED SWILL BE REPAIRED OR REPLACED AT NO COST TO THE OWNER- WHERE ITEMS CAN
NOT BE REPAIRED TO A "POP/ CONDITION', OR WHERE THE STRUCTURAL INTEGRITY HAS BEEN AFFECTED,
ITEMS SHALL BE REPLACED AT NO COST TO THE OWNER.
CONTRACTOR IS RESPONSIBLE TO VERIFY SITE AND F ELD CONDITIONS PRIOR 1D SUBMITTING BIDS AND
(SOMMEiNCRNG WORK. IF THERE ARE ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS, NOTIFY
THE ARCHITECT AND REQUEST CLARIFICATION.
CONTRACiOR SHALL OBTAIN FROM OWNER THE REQUIREMENTS FOR INSTALLATION OF OWNER PROVIDED
EQUIPMENT INCLUDING ROUGHING DIAGRAMS, INSTALLATION INSTRUCTIONS, ELECiRICAL SCHEMATICS,
TEMPLATES, LAYOUTS AND DIMENSIONS TWD OTHER INFORMATION NECESSARY FOR A PROPER, WELL
COORDINATED INSTALLATION. PRIOR TO ROUGH—IN OF SERVICES, CONFER WITH OWNER DO‘CT LOCATION
OF ITEMS.
CONTRACTORS ARE TO COORDINATE THE WORK OF EACH OTHER SO THAT THE WORK AND SCHEDULE
ARE NOT IMPEDED. SCHEDULE WORK PROGRESS THROUGHOUT THE ENTIRE PROJECT TO PREVENT
CONFLICTS AND INTERFERENCES. OBTAIN NECESSARY INFOiI1wATION SUCH AS SITES, LOCATIONS,
TEMPLATES, LAYOUT, DIMENSIONS AND OTHER INFORMATION NECESSARY FOR A PROPER AND WELL
COORDINATED INSTALLATION. PRIOR TO INSTALLATION OF ITEMS, VERIFY AND CONFIRM WTFH EACH
CONTRACTOR EXACT LOCATION OF ITEMS.
PENETRATIONS THROUGH FLOORS AND FULL HEIGHT FIRE RATED WALLS ARE TO BE FIRE STOPPED. GAPS AND
JOINTS AT RATED FLOORS, ROOFS AND WALLS TO BE FIRE & SMOKE STOPPED. GAPS AND JOiN'TS INCLUDE
(BUT ARE NOT UNITED TO) TOP OF WALL TO FLOOR OR ROOF DECK, WALL TO BEMIS, AND CONTROL OR
EXPANSION JOINTS. FIRE STOPPING INCLUDES BOTH FORM OR PACKING MATERIAL AND 11 -IE FILL VOID OR
CAVFIY MATERIAL.
WOOD USED FOR BLOCKING OR OTHER PURPOSES ON OR ABOVE THE ROOF DECK, WITHIN 2'—D' OF
GRADE AND OTHER LOCATIONS OUTSIDE THE BUILDING ENVELOPE WHERE EXPOSED TO THE WEATHER, SHALL
BE PRESSURE TREATED TYPE. WOOD USED FOR BLOCKING OR OTHER PURPOSES SHALL BE FELE
RETARDANT TYPE.
REMOVE DEBRIS AND OTHER MATERIALS RESULTING FROM DEMOLITION FROM SiTE AS DEMOLITION WORK
PROGRESSES. REMOVE RUBBISH FROM JOB SITE REGULARLY AND LEAVE PREMISES AND WORK IN CLEAN
CONDITION. RUBBISH SHALL NOT BE ALLOWED TO ACCUMULATE AND SHALL BE APPROPRIATELY DISPOSED OF.
PRIOR TO COMPLETION, CLEAN PREMISES FOR OWNER. CLEANING SHALL INCLUDE, BUT NOT
BE WINTER TO THE FOLLQMIANG;
— REMOVAL OF GREASE, MASTIC, !ADHESIVE, DUST, DIRT, STAINS, LABELS AND OTFER FOREIGN MATERIALS FROM
EXPOSED SURFACES.
-- THE EXTERNAL SURFACE OF EQUIPMENT SHALL BE CLEANED AT THE COMPLETION
OF THE WORK TO REMOVE CONCRETE, DUST AND DIRT, WELDING AND CUTTING
SPLATTER, ETOL.
PRIOR TO FINAL COMPLETION, OR OWNER OCCUPANCY, CONTRACTOR SHALL CONDUCT NN
INSPECTION OF SIGHT—EXPOSED SURFACES, AND ALL WORK AREAS, TO VERIFY THAT THE
ENTIRE WORK IS CLEAN.
10. CONTRACTOR TO PROVIDE BLOCKING AS NEEDED FOR NEW CONSTRUCTION.
11. DRAWINGS MAY NOT INDICATE ALL DEMOLITION / REMOVALS. CONTRACTORS PRE TO REFER TO DRAWINGS,
SPE3CIFICA11ONS AND VERIFY F1ELD CONDITIONS TO DETERMINE FULL SCOPE AND PARTICULARS OF REMOVAL
REQUIREMENTS PRIOR TO BIDDING WORK. CONFER WITH OWNER WHICH ITEMS ARE TO BE SAVED FOR OWNER'S
USE OR REINSTALLATION BY CONTRACTOR.
12. WHERE EXISTING CONSTRUCTION OR ITEIAS HALVE BEEN INFILLED, REMOVED AND/OR DISTURBS) FOR
INSTALLATION OF NEW WORK. CAUSING THE EXPOSURE OF UNFINISHED AND/OR DAMAGED
SURFACES, RESULT 1G SURFACES AND INFILLED SURFACES SHALL BE RECONSTRUCTED WITH
MATERIALS TO MATCH FINISHED AREAS. ABANDONED OPENINGS (i.E. DUCT / PIPE REMOVALS, ETC.) AT WALLS,
ROOF OR FLOOR TO BE INFILLED SOLID.
13. WHERE REMOVAL OF EXISIVIG CONSTRUCTION RESULTS IN DEPRESSIONS AND/OR UNEVEN FLOOR
CONDITIONS, PATCH, LEVEL AND FEATHER AREAS AS REQUIRED TO PROVIDE UHFORLAf1Y OF NEWi FLOORING.
14. COORDINATE ALL WORK WITH ALL TRADES AND EXISTING FELD CONDITIONS PRIOR TO THE START OF WORK.
15. DESIGN, CONSTRUCTION AND SAFETY SHALL CONFORM TO ALL LOCAL, STATE AND OWNER SPECIFIC CODES.
INCLUDING (BUT NOT UMiTED TO) THE NEPA 101 LIFE SAFTEY CODE, LATEST REVISION, ICC Al17.1 LATEST
REVISION, OSHA. IBC 2015 AND ANY OTHER CODES GOVERNED BY THE JURISDICTION iN WHICH THIS PROJECT
IS BEING CONSTRUCTED.
16. CONTRACTOR TO STOP WORK AND INFORM OWNER'S REP F AMY SUSPECT HAZARDOUS MATERIAL IS
LOCATED. COORDINATE WiTH OWNER FOR ANY HAZARDOUS MATERIALS REPORTS.
J
ARCHITECTURAL MATERIAL SYMBOLS
11—JHJ J FORTH
III 11I
rhouo-oy� GRAVEL
9 -CM
r
i1
CONCRETE
CMU
BRICK
BLOCKING
FINISH WOOD
PRECAST CONCRETE
STEEL
�O%
Evozzsol
:1+ •«#•. «
• :1. 4ia
OTHER METAL
STONE
STRUCTURAL GLAZED TIS,
CERAMIC 11LE
PLASTER, MORTAR,
SAND, GYPSUM
RIGiD INSULATION
BATT INSULATION
PLYWOOD
CEILING 11LE
BITUMINOUS
MATERIAL
GENERAL NOTE
THiS PROJECT DOES NOT INCLUDE AN EXTENSIVE CODE REVIEW OF THE COSTING
FACILITY FOR COMPIJANCE. ONLY THE CODE COMPLIANCE OF THE PROJECT SCOPE;
REPLACEMENT OF THE KITCHEN HOODS AND ASSOCIATED EXHAUST SYSTEMS, IS
REFLECTED iN THESE DOCUMENTS,
ORIGINAL SIFT -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTT, NY 13760
Tel. (607j-321-6100
www.stontec.com
Copyright Reserved
The ContractorshcJ verify and be responsible for all di nensons. DO
NOT scole The drawing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and ci o+r gs are the property of
Stardeo, Reproduction Or use for ony p spore Other than thct
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
Permit -Seal
By Appd• T(.MiM.DO
GPS RJK 17.05.05
by
Appd. YY.MMDD
Own. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
ARCHITECTURAL
LEAD SHEET
Project No.
191001394
Scale
AS NOTED
Dravving No. Sheet
A000
Revision
of V
REMOVE WINDOW UNIT
AND INSTALL LOUVER
STONE
MULLIONS
STONE SILL
LOUVER INSTALLATION PLAN DETAIL
AiApO SCALE: NONE
WALL TYPES:
obi B.O. ROOF DECK
VLF
UNDERSIDE OF
STRUCTURE
(2) LAYER TYPE T
5/80 GWB BOTH SIDES
6" STUD 0 16' W.C.
CONTINUOUS FIRE STOP & SEALANT
0 RATED WALLS,
6" 20 GA METAL STUDS, 16" OC
Wit TOP DEFLECTION TRACK
FIBER GLASS BATT INSULATION
BASE TO MATCH EXISTING
EXISTING FLOOR
TYPICAL FIRE RATED WALL DETAIL
Awl SCALE: NONE
STONE VENEER
BLDG EXTERIOR
STONE VENEER
BLDG EXTERIOR
INFILL ARCH AREA WITH PAINTED
METAL TO MATCH LOUVER FINISH
i
i
NEW LOUVERS,
EACH APPROX.
2711/ x 36"H
COORDINATE WJTH
MECHANICAL.
----------- ---------- ------r
.01
.4-
•
.41A
•
FLASH AND
SEAL*N AI
AROUND --
(TYPICAL)
LOUVER INSTALLATION ELEVATION DETAIL
AOOO1 SCALE NONE
(2 LAYERS OF TYPE 'X'
8" GWB EACH SIDE
/ SCHEDULED FINISH
20 GA METAL TRACK
JAMB BEYOND
1/2"
MA SEE WALL SCHEDULE
H
1 2"
0
mei
JAMB ANCHORS
COORDINATE WITH WALL FINISH
(2) B" 20 GA METAL STUDS
(2 LAYERSEDULED 5f8"FINISH 1' FE 'X' GWS EACH SIDE
W SCH
OMA WRAPPED METAL
GWB — METAL STUDS
(7tTYPICAL FIRE RATED DOOR FRAME DETAIL
Apt SCALE: NONE
GENERAL NOTE
THIS PROJECT DOES NOT INCLUDE AN EXTENSIVE CODE REVIEW OF THE EXISTING
FACIUTY FOR COMPLIANCE. ONLY THE CODE COMPLIANCE OF THE PROJECT SCOPE:
REPLACEMENT OF THE KITCHEN HOODS AND ASSOCIATED EXHAUST SYSTEMS, IS
REFLECTED IN THESE DOCUMENTS.
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOIT, NY 13760
Tel. (607)1-6100
www.stantec.com
Copyright Reserved
The Contractorshar verify and be responsible for all dimensons. DO
NOT scole the drawing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and cila rings are the property of
Stardec, Reproduction Or use for any purpose Other than nkat
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
Permit -Seal
by Appd. rf.MM.DO
GPS RJK 17.05.05
by
Appd. rt.WiM.DD
Own. Chkd. Dsgn. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
ARCHITECTURAL
SCHEDULES AND DETAILS
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
A001
of 0
GENERAL NOTE
KEYED NOTES
THIS PROJECT DOES NOT INCLUDE AN EXTENSIVE CODE REVIEW OF THE EXISTING
FACILITY FOR COMPLIANCE. ONLY THE CODE COMPLIANCE OF THE PROJECT SCOPE;
REPLACEMENT OF THE KITCHEN HOODS AND ASSOCIATED EXHAUST SYSTEMS, IS
REFLECTED IN THESE DOCUMENTS.
GENERAL NOTES
1. COORDINATE WITH All TRADES AND VERIFY EXISTING FIELD CONDFONS PRIOR TO
THE START OF WORK.
2. MECHANICAL BACKGROUNDS SHOWN FOR COORDINATION PURPOSES ONLY. REFER TO
MECHANICAL AND ELECTRICAL DRAWINGS FOR FULL SCOPE OF WORK.
REMOVE AND REINSTALL SUSPENDED ACOUSTICAL CEIUNG SYSTEM IN SHADED AREA
INDICATED TO SUPPORT MECHANICAL WORK. PROVIDE NEW MATERIALS AS REQUIRED
TO MATCH AND BLEND SMOOTH WITH EXISTING. EXISTING CEIUNG AT 9'-6" AFF.
REMOVE EXISTING WINDOWS AND PROVIDE NEW LOUVERS. REFER TO DETAILS ON
DRAWING AOO1 AND LOUVER SCHEDULE ON DRAWING M600. COORDINATE
INSTALLATION WITH MECHANICAL CONTRACTOR.
REMOVE AND REINSTALL FINISHED WOOD SUSPENDED GRID CEIUNG SYSTEM IN
SHADED AREA INDICATED TO SUPPORT MECHANICAL WORK. PROVIDE NEW MATERIALS
AS REQUIRED TO MATCH AND BLEND SMOOTH WITH EXISTING. PREPARE AND PAINT
ALL EXPOSED SURFACES ABOVE WOOD CEIUNG GRID BLACK TO MATCH EXISTING.
EXISTING GYPSUM BOARD SUSPENDED CEILING 0 12'-0" AFF. SOFFIT TO REMAIN.
REMOVE SOFFIT AREAS AS REQUIRED FOR NEW EXHAUST DUCT PENETRATIONS.
INFILL VOIDS AROUND NEW PENETRATIONS WITH METAL FRAMING AND GYPSUM
BOARD TO MATCH AND BLEND SMOOTH WITH EXISTING. PREPARE AND PAINT
SUSPENDED GYPSUM CEILING AND SOFFIT IN AREAS INDICATED.
INFILL WALL OPENING TO MATCH EXISTING WALL CONSTRUCTION. FINISH WALL INFILL
TO MATCH AND BLEND SMOOTH WITH EXISTING FINISHES ON EACH SIDE OF INFILL
OKENsillfl Ds
PIN IIT
EXISTING
WEATHER
HOOD
'0A-
2
ENGI iIa..1
fiVERY
30,4
77
EL IMIRsT
IVY
AVERY
RA.�A�A.�pRA,SARA.SARA.SARA.SARA.SARA.SARA.SARA.SARA.SARA.SARA.�A••A.QAaA.QAaAQARA.SARA.BAR_.SARA.�ARA�ARA.SARA.SARA.SARA.RARA.�pRA,SARA.�ARA.�ARA.�ARA::ARA.SARA.�ARABARAxARA.�ARA.�ARA.�ARA.QARA.�ARA.�:
.........................................................................................
ORIGINAL SHEET -ARCH rz
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTT, NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractorshar verify and be responsible for all dimensons. DO
NOT score The dra Ing - any errors or omissions still be reported to
Stantec without delay.
The Copyrights to all designs and cila rings are the properly of
Stordeo, Reproduction Or use for any purpose Other than thct
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
Permit -Seal
by Appd. rf.MiM.DD
GPS RJK 17.05.05
by
Appd. Y't.MMDD
Dwn. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
ARCHITECTURAL
THIRD FLOOR PLAN
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
Al01 of 0
0
0
1
�4J
11111111111111111111111111111111
00Lif5
SIXTH FLOOR DEMOLITION PLAT
A102 SCALE: 1/4_1_O*
GENERAL NOTE
THIS PROJECT DOES NOT INCWDE AN EXTENSIVE CODE REVIEW OF THE EXISTING
FACILITY FOR COMPUANCE. ONLY THE CODE COMPLIANCE OF THE PROJECT SCOPE;
REPLACEMENT OF THE KITCHEN HOODS AND ASSOCIATED EXHAUST SYSTEMS, IS
REFLECTED IN THESE DOCUMENTS.
GENERAL NOTES
L
1.
2.
COORDINATE WITH ALL TRADES AND VERIFY EXISTING FIELD CONDITIONS PRIOR TO
THE START OF WORK.
MECHANICAL BACKGROUNDS SHOWN FOR COORDINATION PURPOSES ONLY. REFER TO
MECHANICAL AND ELECTRICAL DRAWINGS FOR FULL SCOPE OF WORK.
KEYED NOTES
0
0
0
0
0
REMOVE SECTION OF EXISTING WALL AS REQUIRED TO INSTALL. ACCESS DOOR.
COORDINATE WITH MECHANICAL CONTRACTOR. MAXIMIZE ACCESS DOOR SIZE TO FIT
BELOW EXISTING DEVICES (APPROX. 18"x18")
REMOVE EXISTING WALL FULL HEIGHT INCLUDING DOOR, FRAME AND HARDWARE.
TRANSPORT DOOR AND FRAME TO STORAGE. SAVE WOOD BASE, TRIM AND RAILS
FOR MODIFICATION AND REINSTALLATION.
PROVIDE 2 HOUR RATED WALL SYSTEM WITH FIBERGLASS BATT INSULATION FROM
FLOOR TO UNDERSIDE OF ROOF. FIRE STOP AND SEAL ALL EDGES AND
PENETRATIONS AS REQUIRED. MODIFY REMOVED EXISTING WOOD BASE AND TRIM
AND INSTALL TO MATCH AND BLEND WITH ADJACENT EXISTING WOOD BASE AND
TRIM. FINISH WALL TO MATCH AND BLEND SMOOTH WITH ADJACENT WALLS.
COORDINATE ALL FINISH AND TRIMS WITH OWNER'S REP PRIOR TO START OF WORK.
REFER TO WALL TYPE DETAIL ON A001 FOR UL DESIGN NUMBER.
FIRE STOP AND SEAL ALL VOIDS AT FLOOR AND WALL PENETRATIONS. COORDINATE
WITH MECHANICAL. TYPICAL
PROVIDE TWO HR RATED ACCESS DOOR SYSTEM AND BLOCKING. COORDINATE WITH
MECHANICAL PATCH WALL TO MATCH AND BLEND SMOOTH WITH EXISTING ADJACENT
CONSTRUCTION AND FINISHES.
PROVIDE AN INSULATED 4'-011111 x 7' —ON 90 MIN. FIRE RATED HOLLOW METAL
DOOR WITH 2" WRAPPED HOLLOW METAL RATED FRAME SYS"TDA AND STORE ROOM
LOCKSET WITH CLOSER. PAINT DOOR AND FRAME. COORDINATE WITH OWNER'S REP.
REFER TO FRAME DETAIL ON A001.
'3.40
ri--) SIXTH FLOOR INSTALLATION PLAN
A102 SCALE: 1 /4 -i —0
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTI, NY 13760
Tel. (607)1-6100
www.stantec.com
Copyright Reserved
The Contractor shcJ verify and be responsible for all dimensons. DO
NOT scole the drawing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and cila rings are the property of
Stardec, Reproduction Or use for any purpose Other than nkat
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
Permit -Seal
by Appd. rf.MM.DO
GPS RJK 17.05.05
by Appd. Y't.MM.DO
Own. Chkd. Dsgn. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
ARCHITECTURAL
PARTIAL SIXTH FLOOR
DEMOLITION & INSTALLATION PLAN
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
A102
of 0
az
MECHANICAL LEGEND AND ABBREVIATIONS
Id
c5
ETI
0
9
INLINE PUMP
BUTTERFLY VALVE
BALL VALVE
BALANCING VALVE
STRAINER
THERMOMETER
PRESSURE GAUGE
WATER FLOW METER
PRESSURE GAUGE & COCK
MANUAL AIR VENT
AUGN GUIDE
X PIPE ANCHOR
UNION
1223 FLEX CONN.
HD
-o
HivR
0
LD=D
T
PRESSURE REUEF VALVE
TRIPLE DUTY VALVE
CONNECTION TOP
ELBOW UP
ELBOW DOWN
FLANGE
PIPE TURNED UP
PIPE TURNED DOWN
HOT WATER RETURN PIPING
HOT WATER SUPPLY PIPING
KEY NOTE
BASE MOUNTED PUMP
PRESSURE DIFFERENTIAL
SENSOR
ELECTRIC CONTROL VALVE
THERMOSTAT
HUMIDISTAT
MITERED 90'
MITERED 45
LONG RADIUS 90'
LONG RADIUS 45'
CHECK VALVE
2 -WAY CONTROL VALVE
3 -WAY CONTROL VALVE
BAUUN TUBE
AIR PRESSURE INDICATOR
TEMPERATURE SENSOR
CFMT PE� RETURN AIR GRILLE/REGISTER
?ECK SIZECFM TYPE
VD1
AxB
ASO
8
ivv\
0
OCR
DGS
-*
SUPPLY EMIR DIFFUSER
ROUND TO RECTANGULAR
DUCT TRANSITION
EXHAUST FAN
VOLUME DAMPER
FIRE DAMPER
FIRE/SMOKE DAMPER
DUCT UP THRU ROOF
SUPPLY AIR DUCT UP/DOWN
RETURN AIR DUCT UP/DOWN
90' ELBOW WITH TURNING VANES
RECTANGULAR DUCT SIZE
(INCHES)
ROUND DUCT
ROUND TO RECTANGULAR
DUCT TRANSITION
POINT OF CONNECTION
POINT OF DISCONNECTION
OPPOSED BLADE DAMPER
DUCT SMOKE DETECTOR
CHILLED GLYCOL RETURN
CHILLED GLYCOL SUPPLY
DIFFUSER AIR FLOW
DUCT ELEVATION
DIRECTION OF AIR FLOW
VAV BOX WITH REHEAT COIL
FIN TUBE & PIPE ENCLOSURE
CONTROL DAMPER
DUCT WORK BRANCH TAP
BUILDING SECTION
MOTORIZED DAMPER
VARIABLE FREQUENCY DRIVE
VELOCITY PRESSURE SENSOR
PUMP
INLINE PUMP
AD ACCESS DOOR
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
AP ACCESS PANEL
BHP BRAKE HORSEPOWER
BOT BOTTOM
BTU BRITISH THERMAL UNIT
BTUH BRTIISH THERMAL
UNITS PER HOUR
CAV CONSTANT AIR VOLUME
CD CONTROL DAMPER
CFM CUBIC FEET PER MINUTE
CONN CONNECTION
CONST CONSTRUCTION
CONY CONVECTOR
CU COPPER
CUH CABINET UNIT HEATER
CHWS CHILLED WATER SUPPLY
CHWR CHILLED WATER RETURN
CHGS CHILLED GLYCOL SUPPLY
CHGR CHILLED GLYCOL RETURN
DAT DISCHARGE AIR TEMPERATURE
DOC DIRECT DIGITAL CONTROL
DEMO DEMOLISH, DEMOLITION
DIA
DN
DP
DSD
DWG
EG
DIAMETER
DOWN
DIFFERENTIAL PRESSURE
DUCT SMOKE DETECTOR
DRAWING
EXHAUST/RETURN AIR GRILLE
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EF -LF EXHAUST FAN - LAB EXHAUST
EL ELEVATION
ELEC ELECTRIC (AL)
ESP EXTERNAL STATIC PRESSURE
EXIST EXISTING
FCU FAN COIL UNIT
FH FUME HOOD
FLEX FLEXIBLE CONNECTION
FSD FIRE/SMOKE DAMPER W/ AUTO RESET
FD FIRE DAMPER
FL FLOOR
FP FIRE PROTECTION
FPM FEET PER MINUTE
FPS FEET PER SECOND
FTR FIN TUBE
FVC FUME HOOD VOLUME CONTROLLER
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACT
GPH GALLON PER HOUR
GPM GALLON PER MINUTE
HP HORSEPOWER
HRC HEAT RECOVERY COIL
HVAC HEATING VENTILATING,
& AIR CONDITIONING
HAIR HOT WATER RETURN
HWS HOT WATER SUPPLY
INSUL
KWH
LAT
LEV
LF
LP
LSV
MAX
MBH
MCC
MECH
MIN
MA
N
NC
NIC
NG
NO
NTS
OA
PD
PRY
PVC
QTY
RA
RWS
RWR
RHC
RM
RPM
SA
SAT
SD
SCH
SHP
SPEC
SS
T.C.
TOS
TSP
TSTAT
U
UH
V
VAV
VD
VEL
W
WB
VSD
VP
INSULATION
KILOWATT HOUR
LEAVING AIR TEMPERATURE
LAB EXHAUST VALVE
LINEAR FEET
LOUVERED PENTHOUSE
LAD SUPPLY VALVE
MAXIMUM
THOUSAND BTU/HR
MOTOR CONTROL CENTER
MECHANIC (AL)
MINIMUM
MAKE UP AIR
NORTH
NORMALLY CLOSED
NOT IN CONTRACT
NATURAL GAS
NORMALLY OPEN
NOT TO SCALE
OUTSIDE AIR
PRESSURE DROP
PRESSURE REDUCING VALVE
POLYVINYL CHLORIDE
QUANTITY
RETURN AIR
RADIATION WATER SUPPLY
RADIATION WATER RETURN
REHEAT COIL
ROOM
REVOLUTIONS PER MINLITE
SUPPLY AIR
SUPPLY AIR TEMPERATURE
SUPPLY AIR DIFFUSER
SCHEDULE
SASH HOOD POSITION
SPECIFICATION
STAINLESS STEEL
TEMPERATURE CONTROL
TOP OF STEEL
TOTAL STATIC PRESSURE
THERMOSTAT
U -FACTOR
UNIT HEATER
VOLT
VARIABLE AIR VOLUME
VOLUME DAMPER
VELOCITY
WATT
WET BULB
VARIABLE FREQUENCY DRIVE
VELOCITY PRESSURE
GENERAL DEMOLITION NOTES
1. CARE SHOULD BE TAKEN DURING DEMOLITION AS TO NOT DISRUPT EXISTING TO REMAIN DUCTWORK AND ACCESSORIES. REPLACEMENT OF EXISTING
TO REMAIN DUCTWORK IS NOT INCLUDED IN THE SCOPE OF THE PROJECT.
2. REMOVE ABANDONED DUCT WHERE IT IS IN CONFLICT WTII-I NEW WORK. PLUG AND CAP AS REQUIRED.
3. RESTORE ALL BUILDING SURFACES TO THE CONDITION ACCEPTABLE TO THE ARCHITECT.
4. NOTIFY UNIVERSITY OF ANY SHUT -DOWN OF EXISTING FIRE PROTECTION SYSTEM.
5. THE SHUT DOWN OF EXISTING HVAC SYSTEM SHALL BE COORDINATED WITH THE OWNER. ARRANGEMENTS SHALL BE MADE AT LEAST 15 CALENDAR
DAYS PRIOR TO ANY SERVICE SHUT DOWN. THE AREAS OUTSIDE OF SCOPE OF WORK MUST REMAIN ACTIVE UNLESS OTHERWISE DIRECTED BY OWNER.
S. THE CONTRACTOR SHALL BE ADPMSED THAT THIS IS AN ACTIVE FACILITY. THE CONTRACTOR SHALL ENSURE THAT AIR QUALITY WITHIN THE BUILDING
SHALL NOT BE ADVERSELY AFFECTED SUCH THAT IT WILL IMPAIR THE INTERIOR ENVIRONMENT IN ACCORDANCE WITH THE OWNER'S HEALTH AND
SAFETY PLAN. CONTROL MEASURES SHALL INCLUDE BUT NOT BE UMTFED TO SUPPLEMENTAL AIR HANDLING UNITS INCLUDING HEATING AND/OR
COOLING NOT SHOWN ON THIS PLAN, AND ANY ELECTRIC SERVICES.
MECHANICAL GENERAL NOTES
1. FOR CLARITY PURPOSES DEMOUTION OF EXISTING DUCT WORK IS NOT COMPLETELY SHOWN. SELECTIVE DEMOLITION IS SHOWN FOR OTHER WORK.
APPROXIMATE LOCATIONS AND SIZES OF SUPPLY AND RETURN DUCTS ARE GENERALLY SHOWN ON THE PLAN. CONTRACTOR SHALL CONFIRM ACTUAL
SIZES AND LOCATIONS PRIOR TO CONSTRUCTION.
2. COLUMN LINES AND EQUIPMENT LOCATION ARE APPROXIMATE. CONTRACTOR TO CONFIRM LOCATIONS AS REQUIRED FOR BIDDING AND/OR FABRICATION
AS REQUIRED.
3. TEST, BALANCE AND COMMISSION ALL NEW EQUIPMENT IN ACCORDANCE WITH SPECIFICATIONS.
4. THE CONTRACTOR SHALL BE FULLY ACQUAINTED WITH THE EXISTING CONDITIONS AND HAVE A FULL UNDERSTANDING OF THE WORK REQUIRED TO
COMPLETE THIS PROJECT.
5. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO COMMENCING WITH ANY WORK.
6. ALL PLUMBING, ELECTRICAL AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH TECHNICAL SPECIFICATION AND LOCAL CODES.
7. ALL EXISTING PIPING, EQUIPMENT AND CONDTIIONS ARE REPRESENTED AND SHOWN IN GOOD FAITH AS TO THE LOCATIONS AND SIZE, NO GUARANTEE
OR ACCURACY IS STATED OR IMPLIED.
8. ALL LAYOUTS ARE DIAGRAMMATIC AND INTENDED TO SHOW THE GENERAL ARRANGEMENT, SIZE AND CAPACITY. ALL OFFSETS ARE NOT INDICATED.
CONTRACTOR SHALL PROVIDE ALL NECESSARY MATERIAL, EQUIPMENT, ETC AS REQUIRED TO COMPLETE THE PROJECT IN TTS ENTIRETY.
9. UPON COMPLETION OF THE PROJECT, THE CONTRACTOR SHALL SUPPLY THE OWNER WITH FULLY FUNCTIONING SYSTEMS. IF ANY REQUIRED MATERIAL
EQUIPMENT, ETC IS INADVERTENTLY OMITTED FROM THE SPECIFICATIONS OR DRAWINGS OR IS REQUIRED BY LOCAL CODE OR THE LOCAL INSPECTOR
THE CONTRACTOR SHALL FURNISH TT AT NO ADDITIONAL COST TO THE OWNER.
10. THE CONTRACTOR SHALL SECURE AND PROVIDE PROOF TO THE OWNER ANY AND ALL REQUIRED PERMITS.
11. CONTRACTOR SHALL ENSURE THAT THE NEWLY INSTALLED EQUIPMENT IS CAPABLE OF BEING ISOLATED SUCH THAT THE ISOLATION FULLY MEETS
CURRENT OSHA LOCKOUT/TACOUT STANDARD (29CFR 1910.147).
12. ALL MATERIAL, EQUIPMENT AND ACCESSORIES SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURES WRITTEN INSTALLATION INSTRUCTION.
COORDINATE EXACT LOCATIONS TO ACCOMMODATE ALL REQUIRED CLEARANCES AND OBSERVE ALL REQUIREMENTS FOR VALVES AND CONNECTIONS.
13. ALL VALVES, UNIONS, ELECTRICAL PANELS AND ANY OTHER COMPONENT THAT REQUIRES A PERSON TO OPERATE REGULARLY OR OCCASIONALLY
SHALL BE ACCESSIBLE FROM A STANDING POsmON WITHOUT REQUIRING THE OPERATOR/MAINTENANCE PERSONAL TO CLIMB OR REACHING OVER
PIPES, EQUIPMENT, ETC.
14. ALL PENETRATIONS THROUGH FLOORS, WALLS OR OTHER SIMILAR FIRE RATED PARTITIONS SHALL RECEIVE CODE COMPLANT FIRE STOPPING TO
MAINTAIN THE FIRE RATING.
15. THE CONTRACTOR SHALL REPLACE AND INSTALL FREE OF CHARGE TO THE OWNER ANY AND ALL PIPING, FITTINGS COMPONENTS, ETC THAT DO NOT
PASS TESTING PROCEDURES AS OUTLINED IN THE TECHNICAL SPECIFICATIONS AND/OR LOCAL BUILDING CODES.
16. CONTRACTOR IS TO PRE -FABRICATE AND MINIMIZE FIELD CONSIRUC11ON TO THE GREATEST EXTENT POSSIBLE.
17. CONTRACTOR TO ENSURE THAT ALL OF ITS NEW WORK. PENETRATIONS. CURB MODIFICATIONS, ETC ARE MADE WATERTIGHT.
18. ALL SHEETMETAL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED 114 ACCORDANCE TO THE STANDARDS AS SET FORTH IN THE LATEST PUBLISHED
EDITION OF SMACNA DUCT CONSTRUCTION STANDARD -- METAL AND FUMBLE.
19. FLEXIBLE DUCTS WHERE INDICATED SHALL CONFORM TO THE REQUIREMENTS OF UL 181 FOR CLASS 0 AND CLASS 1 FLEXIBLE AIR DUCT. FLEXIBLE
DUCTS SHALL NOT PASS THROUGH ANY WALL. FLOOR, CEILING, OR FIRE RESISTIVE RATED ASSEMBLY,
20. AIR PLENUMS TO BE CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS. ALL PIPING DUCT INSULATION, VALVE SHALL NOT BE INSTALLED IN AIR
PLENUMS.
21. FIRE DAMPERS AND ACCESS DOORS SHALL BE PROVIDED AT ALL LOCa4T1ONLS WHERE AIR DISTRIBUTION SYSTEMS PENETRATE FIRE RESISTIVE
ASSEMBLIES. DAMPERS SHALL COMPLY WITH UL 555 AND SHALL BEAR THE LABEL OF AN APPROVED AGENCY.
22. FIRE DAMPERS AND ACCESS DOORS SHALL BE PROVIDED AT ALL PENETRATIONS OF FIRE RATED SEPARATIONS, WHERE DAMPERS ARE LOCATED IN
WALLS OR ABOVE IN ACCESSIBLE CEIUNGS CONTRACTOR SHALL. PROVIDE ACCESS PANELS FOR DAMPER ACCESS. ACCESS PANELS SHALL MAINTAIN
ASSEMBLES RATING.
23. PIPING SHALL BE INSTALLED SO AS TO PREVENT STRAINS AND STRESSES WHICH WILL EXCEED THE LIMITATIONS OF THE PIPE. PROVIDE PROVISIONS
FOR EXPANSION AND CONTRACTION AND FOR STRUCTURAL SETTLEMENT THAT WOULD AFFECT THE PIPING. PIPING SHALL BE INSTALLED SO AS NOT
TO CREATE STRUCTURAL STRESSES OR STRAINS WITHIN THE COMPONENTS. CONTRACTOR SHALL SUBMIT SHOP DRAWING OF PIPING DETAIL FOR
EXPANSION AND ANCHORING.
24. JOINTS BETWEEN DIFFERENT PIPING MATERIALS SHALL BE MADE WITH APPROVED ADAPTOR FITTINGS. JOINTS BETWEEN DIFFERENT METALLIC PIPING
MATERIAL SHALL BE MADE WITH APPROVED DIELECTRIC FITTINGS OR BRASS CONNECTOR FITTINGS.
25. OPENINGS FOR PIPING PENETRATIONS IN WALL, FLOORS OR CEIUNGS SHALL BE LARGER THAN THE PENETRATING PIPE. OPENINGS THROUGH
CONCRETE OR MASONRY BUILDING ELEMENTS SHALL BE SLEEVED. THE ANNULAR SPACE OF ALL PIPE PENETRATIONS SHALL BE FIRE STOPPED.
26. PROVIDE DRAINS AT ALL LOW POINTS OF ALL HYDRONIC PIPING. DRAIN SHALL HAVE A VALVE AND CAP WITH HOSE CONNECTION PROVIDE AIR RELIEF
AT HIGH POINTS OF ALL HYDRONIC SYSTEMS.
27. NO PIPING OR DUCT WORK OF ANY KIND SHALL RUN IN THE DEDICATED PANEL SPACE OVER AND UNDER ANY ELECTRICAL. PANELBOARD OR
SWITCHBOARD. THE DEDICATED SPACE SHALL BE THE WIDTH OF THE PANEL TO THE FLOOR AND TO A HEIGHT OF 25'-O" ABOVE THE PANEL
2& ALL DUCTWORK TO RUN IN CEIUNG SPACES FURRED SPACES OR CHASES UNLESS NOTED OTHERWISE,
29. ALL MECHANICAL EQUIPMENT AND APPLIANCES SHALL BEAR THE LABEL OF AN APPROVED AGENCY AS REQUIRED BY MECHANICAL CODE
30. MECHANICAL CONTRACTOR TO KEEP ALL AIR HANDLING DEVICES AND MATERIALS, INCLUDING DUCTWORK AND OTHER MATERIALS DRY PRIOR TO
INSTALLATION. IF DEVICES AND/OR MATERIAL BECOMES WET, AND AT THE OWNER'S REQUEST, THE CONTRACTOR WILL BE REQUIRED TO
30.1. PERFORM AND PAY FOR ALL ANALYTICAL SAMPUNG & TESTING REQUESTED BY THE OWNER.
30.2. REMEDIATE AND/OR REPLACE ALL EQUIPMENT AND/OR MATERIALS THAT REFLECT UNACCEPTABLE CONDITIONS AT NO COST TO THE OWNER.
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTI, NY 13760
Tel. (607)-321-6100
www.stontec.com
Copyright Reserved
The Contractor slid verify and be responsible for all dimensions. DO
NOT scole the drawing - otly errors or omisslon% shall be reported to
Stantec without delay.
The Copyrights to all designs and are the property of
Stordec, Reproduction or use for ony purpose other Mon that
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name.
by Appd. rf.MiM.DO
JFG SAS 17.05.05
by Appd. Y't.P i.DD
Own. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL
LEAD SHEET
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
M000
of 1'-'1
2
DEMOLITION KEYED NOTES:
DISCONNECT AND REMOVE KfCHEN EXHAUST HOODS AND ASSOCIATED CONTROLS, DUCTWORK,
SUPPORTS, AND FIRE PROTECTION PIPING IN LOCATIONS SHOWN.
[ 2 1 REMOVE ALL EXISTING DUCTWORK AND FIREPROOF INSULATION BOARD FROM CONNECTIONS TO
LLJJ HOODS BACK TO RISER.
0 REMOVE ALL EXISTING DUCTWORK AND EXHAUST FAN.
0 REMOVE EXISTING EXHAUST GRILLE, EXHAUST DUCTWORK, EXHAUST FAN, EXHAUST FAN WIRING,
WINDOW LOUVER, AND ARCHITECTURAL ENCLOSURE ELEMENTS IN LOCATION SHOWN.
EXISTING RISER TO REMAIN. PROVIDE DUCT LEAKAGE TEST ON SECTION TO REMAIN PRIOR TO
INSTALLATION OF NEW WORK.
405
r
5006
_ 1254]
1
D
0
z
r0
J -
72727,1A -
3{J7
15&T
11
1
THIRD FLOOR DEMOLITION PLAN
SCALE: 1/8"=1 —O
N
242
ORIGINAL SHEET -ARCHI
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTI, NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractor shcJ verify and be responsible for all dimensons. DO
NOT scole The dra Ing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and cila rings are the property of
Stantec, Reproduction Or use for any purpose Other than nkat
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
by Appd. rf.MM.DO
JFG SAS 17.05.05
by Appd. Y't.MM.DO
Own. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL DEMOLITION
THIRD FLOOR PLAN
Project No. Scale
191001394 AS NOTED
Drawing No. Sheet Revision
MD O1
of 1'-'1
f
1
DEMOLITION KEYED NOTES:
0 REMOVE EXISTING EXHAUST FAN AND ACCESSORIES, KITCHEN EXHAUST FAN MOTOR COOLING FAN,
4" OUTDOOR AIR DUCT, AND ALL OTHER ASSOCIATED DUCTWORK BACK AS REQUIRED AND FOR
NEW DUCT AND FAN INSTALLATION. SEE ELEVATION VIEW 2 ON THIS DRAWING FOR ADDITIONAL
INFORMATION.
CI EXISTING 58"x28' OVAL DUCT EXHAUST RISER WITHIN EXISTING CHASE SHOWN FOR REFERENCE.
5620'�
EXISTING 58"x28"
OVAL DUCT RISER
IN CHASE UP
FROM 4TH FLOOR
AND UP TO 6TH
FLOOR.
FIFTH FLOOR PLAN
.105 SCALE: 1 /4-1 -O
N
AFF
YOB
Mit
ff
MB
YOB
Mit
MB
YOB
Mit
MB
YOBMit
MB
YOB
Mit
fr
MB
YOB
Mit
fr
#E
MB
YOB
Mit
MB
YOB
Mit
CI
REMOVE
STING FAN
AND ASSOCIATED
DUCTWORK
1
1
4.
rwrr rrrrr
WNW
riraaai
aaa
salmi
llfilf�
0=f
=t
Irak
WNW
mus
WI
MOH
Nt . 08
rr�
41111.1111s
All
0
11
11
11
11
11
m
WPM
WE
itala
Mat
ss
=E
itala3.0
Mat
1114
WPM
=E
1114
W
ss
WPM
WE
EE
ss
WPM
=E
3.0
:.:ommaumummmmi—
PLEN I ,EIICLOSURE DEMOLITION ELEVATION VIEW
D1 SCALE: 14 =1 —O
(Th 1 S I XTH FLOOR PLAN
0.933 SCALE: 1/4 =1 —O
14 -
ORIGINAL
ORIGNAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTT, NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractor shcJ verify and be responsible for all dimensons. DO
NOT scole the drawing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and crave rigs are the property of
Stardeo, Reproduction Or use for any purpose Other than nkat
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
by Appd. rf.MM.DO
JFG SAS 17.05.05
by
Appd. ri.MMi.DD
Own. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL DEMOLITION
FOURTH, FIFTH & SIXTH FLOOR
PLANS
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
M D O2
of 1'-'1
INSTALLATION KEYED NOTES
SD -1 LAMINAR FLOW DIFFUSER, 24"x24" GRILLE SIZE, 12" NECK, 240 CFM PER FIXTURE.
COORDINATE EXACT LOCATION WITH CBUNG GRID AND EXISTING MOUNTED LIGHT FIXTURES.
SD -2 SUPPLY DIFFUSER, 24"x24" SIZE, 12" NECK, 300 CFM PER FIXTURE. COORDINATE EXACT
LOCATION WITH CEILING GRID AND EXISTING LIGHT FIXTURES.
CONNECT NEW SUPPLY MAKE—UP AIR DUCTWORK INTO EXISTING SUPPLY RISER. SUPPLY RISER
TO BE CLEANED PRIOR TO INSTALLATION.
INSTALL LOUVERS IN EXISTING WINDOW OPENINGS. REFER TO LOUVER SCHEDULE ON M-600
FOR DETAILS. PROVIDE BIRD AND INSECT SCREEN.
SLOPE ALL EXHAUST DUCTWORK TOWARDS HOOD AND/OR DISHWASHER EXHAUST CONNECTIONS.
ALL NEWLY PROVIDED EXHAUST DUCTWORK SHALL BE 304 WELDED STAINLESS STEEL
NOT USED.
PROVIDE FIRE INSULATION BOARD FROM OUTLET OF TYPE I HOOD CONNECTIONS BACK TO
CONNECTION TO EXISTING EXHAUST RISER. REFER TO DETAIL 5/M500 FOR DETAILS.
PROVIDE FIRE INSULATION BOARD FROM OUTLET OF HOOD 8 CONNECTION BACK TO
CONNECTION TO EXISTING WEATHER HOOD. REFER TO DETAIL 5/M500 FOR DETAILS.
CONNECT 24t20" KITCHEN EXHAUST DUCT INTO EXISTING WEATHER HOOD INLET. PROVIDE
DUCT TRAN51T1ON TO INLET OF WEATHER HOOD AS NEEDED FOR PROPER CONNECTION.
INSTALL 24"x2O" EXHAUST DUCT WITH FIRE BOARD INSULATION AS TIGHT TO EXISTING
STRUCTURE AS IS ALLOWABLE.
PROVIDE INSULATED BLANK OFF FOR DUCT PENETRATION THROUGH WALL
PROVIDE DUCT ACCESS DOOR ON SIDE OF DUCT IN THIS LOCATION. REFER TO DETAIL 6/M500
FOR DETAILS ON CONSTRUCTION AND ACCESS DOOR SIZING.
PROVIDE BOTTOM OF DUCT LOW POINT DRAIN, WITH CAP. REFER TO DETAIL 4/M500 FOR
DETAILS.
CODE VARIANCE IS CURRENTLY BEING SOUGHT FOR THIS CONDITION,
J
Ll
r
474
We9C,C,
r 1254 I
EF -4
4
i
CONNECT TO
EXISTING
58"x28"
OVAL RISER
CON
DIS
ECT TO
ASHER
(STING
FAUST
UTLET
-VOSN
T7
CONNECT TO
DISHWASHER EK
24"x1 8 EA BOD 11
HOOD 3
36"x24" SA BOD 11'-2"
40"x20"
(OVAL)
58"x24" EA
(OVAL)
58"x24* EA BOD 11'—O"
(OVAL)
•10A
20"x1 4" SA
BOD— 13'-2"
THIRD FLOOR PLAN
M i Ol SCALE: 1/8"=V-0"
—4
N
300S1.1
20
ORIGINAL SHEET -ARCH I
Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTr, NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractor slid verify and be responsible for all dimensions. DO
NOT scole the dra Ing - ctly errors or omisslon% shall be reported to
Stantec without delay.
The Copyrights to all designs and are the property of
Stordec, Reproduction or use for ony purpose other Mon that
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Nene:
by Appd. T(.MM.DO
JFG SAS 17.05.05
by
Appd. rt.WiM.DD
Dam. Chkd. Dsgn. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL
THIRD FLOOR HVAC PLAN
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
M101
of 1'-'1
az
gm
;t6 -
INSTALLATION KEYED NOTES
0
0
0
0
0
PROVIDE NEW 58"x28" OVAL TO 38" DIA. ROUND DUCT TRANSITION 11ED INTO EXISTING 58"x28"
OVAL DUCT RISER IN CHASE AND TRANSITION TO 38. DIA ELBOW AS SHOWN.
PROVIDE INLINE EXHAUST FAN EF -3 AS INDICATED.
PROVIDE NEW FAN DISCHARGE DUCTWORK AND DUCT STACK WITH DRAIN OFF BOTTOM AS SHOWN.
EXISTING 58"x28" OVAL DUCT EXHAUST RISER WITHIN EXISTING CHASE SHOWN FOR REFERENCE.
PROVIDE DUCT ACCESS DOOR IN THE LOCATION SHOWN.
AIM
-z
.A fI
EXISTING 58'°x28'°
OVAL DUCT RISER
IN CHASE UP TO
5TH FLOOR.
SHOWN FOR
CLARITY.
0 J EXISTINC 58"x28"
OVAL DUCT RISER ;
IN CHASE UP
FROM 3RD FLOOR.
SHOWN FOR
CLARITY.
rio
0
0-
(Th
FOURTH FLOOR PLAN
M102 SCALE 1/4....1'-0.
407A
868
4071-
GF
VD
�✓OT
— r)
338
L-
C
4
J/!
.d
EXISTING 58"x28"
OVAL DUCT RISER
IN CHASE UP
FROM 4TH FLOOR
AND UP TO 6TH
FLOOR.
50-7A
27
FIFTH FLOOR PLAN
m102 SCALE 1/41-*-1$-Osi
N
a
38"0 ELBOW
58"x28#
OVAL TO
38"0 DUCT
TRANSITION
EXISTING
SCREEN
Mau
is
I
s.,1;
NEW DISCHARGE
DUCT STACK
Mint
INSTALLED TOm
TOP OF ai
„�
EXISTING CHASE
-N, ....,
..irs
...,
OM
tint
rani,
lC
won
422
I
ram
ztisms
1
mom
MOO
MOM
hex
hits
nor
*wag
mum
lai
EXISTING
}
EXISTING 58'°x28'
OVAL DUCT RISER
IN CHASE
M
�NCLOS�RERIN�NL4TION ELEVATION VIEW
MMO0 SCALE: 1/e=1'-0"
58"x28"
OVAL DUCT
RISER IN
CHASE
0
PROVIDE '11. DRAIN
OFF BOTTOM SIDE
OF RISER STACK
ROUTED TO
EXISTING DRAIN
PROVIDE 1" DRAIN
OFF BOTTOM SIDE
OF DUCT STACK
ROUTED TO FLOOR
DRAIN. FLOOR
DRAIN TO BE
CLEARED PRIOR TO
INSTALLATION OF
DRAIN PIPING
58"x28' OVAL
TO 382¢ ELBOW
1(2
SIXTH FLOOR PLAN
M102 SCALE i/4 -1 -0
N
NEW DISCHARGE
DUCT STACK
INSTALLED TO
1"-0" BELOW
TOP OF
DUSTING CHASE
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTI, NY 13760
Tel. (607)1-6100
www.stantec.com
Copyright Reserved
The Contractorshar verify and be responsible for all dimensons. DO
NOT scole the drawing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and cila rings are the property of
Stardec, Reproduction Or use for any purpose Other than nkat
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
by Appd. T(.MM.DO
JFG SAS 17.05.05
by Appd. Y't.P i.DD
Own. Chkd. Dsgn. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL
PARTIAL FOURTH, FIFTH & SIXTH FLOOR
HVAC PLANS
Project No. Scale
191001394 AS NOTED
Drawing Na. Sheet Revision
M102
of 1'-'1
BUND RIVETS (OR
WELD STUD)
TYPE A*
SOLID
BANDS
IUUuuauuu•■
1
1
1
1
1
1
1
1
1
1
in ■■■■■I■■■■■
III
1•
INSULATION
t
DUCT WIDTH
ROD DIAMETER
TYPE
SUPPORT ANGLE
MAX. SPACING
UP TO 24"
USE 1"x1/8"
A
NONE
4'-O" O.C.
26" TO 36"
3/8"
B
1 1/21x1 1/2"x1/8'
S' -O" O.C.
37°' TO 48"
3/8"
B
2"x2"x1 /8`
S' -O" O.C.
49" TO 60"
3/8"
B
2'x2 x3/16"
6'-O" O.C.
61" TO 84"
3/8"
B
2"x2 x1/4'
6'-0' O.C.
ABOVE
3/8'
B
SELECT FOR 1/2' MAX.
DEFLECTION AT DES. LD
6'_U" O.C.
*TYPE A HANGER ONLY ACCEPTABLE FOR USE ONLY WITH SUPPLY DUCTWORK.
DUCTWORK HANGER DETAIL AND SCHEDULE
14500
SCALE: NONE
EXHAUST DUCT LOW POINT DRAIN DETAIL - ELEVATION
m500 SCALE: NONE
DUCT LOW POINT DRAIN KEYED NOTES:
3" FIRE INSULATION BOARD.
OVAL DUCT.
3" THREADED CAP.
CUT OUT OPENING IN FIREBOARD AT LOCATION OF CLEANOUT. OPENING SHALL BE BIG
ENOUQ1 TO PROVIDE EASY ACCESS TO CLEANOUT
COVER CUT OUT IN FIRE INSULATION 'MTH BLOCK OF FIRE INSULATION BOARD.
HANGER
RODS
3"x3*x30" SPACER MADE OF FIRETEMP BOARD. FASTEN SPACER TO FIRE BOARD NTH DRYWALL SCREWS
AND CALSTIK GLUE.
BAR MADE OF 1/4" x 1" METAL SECURE OPENING COVER ATH THREE METAL BARS.
ATTACH AND SECURE 1/4" THREADED ROO IN SPACER BAR. USE WINGNUTS FOR ANCHORING METAL BAR.
SEAL OPENING WITH 1/8" THICK FIRE RESISTANT GASKET.
3" PIPE.
FLEX DUCT
DUCT, SEE PLANS
FOR SIZES
VOLUME DAMPER
(PROVIDE IN LOCATIONS
SHOWN ON FLOOR PLANS)
SD -1 OR SD 2
iviwv
TYPICAL CEILING DIFFUSER DETAIL
14500 SCALE: NONE
CEILING
ROD POSMONMNG
NUT HANDLE WITH
SET SCREW
ALJGN HANDLE WITH
DAMPER BLADE
BLADE POSITION
LOCKNUT
2" STAND-OFF BRACKET
STEEL ANGLE BLADE
STOP BOLT TO DUCT
DUCT
['1
ROTATION
(90 DEG)
1/4" CLEARANCE
ALL-AROUND
BOLT TO DUCT
3/8" DIA, THREADED ROD
16 GA. STEEL BLADE
BEARING FITTING BOLT TO
DUCT
ENSURE BOLTS CLEAR BLADE,
OR INSTALL THEM IN OPPOSING
COMERS AWAY FROM BLADE
ROTATION
STEEL CLAMP, BOLT TO
BLADE, PROVIDE AN
ADDITIONAL ANT1-SUP BOLT
THRU THE ROD
1. THIS DETAIL APPLIES FOR SUPPLY DUCTS ONLY.
2. DAMPERS FOR ROUND DUCTS SHALL BE SIMILAR TO THE DAMPER SHOWN ABOVE.
3. ENSURE THAT FULL 90 DEGREE DAMPER BLADE MOVEMENT IS UNOBSTRUCTED.
4. FOR DUCT HEIGHTS MORE THAN 12"t PROVIDE FACTORY -FABRICATED OPPOSED BLADE DAMPERS.
riN) MANUAL DAMPER (ADJUSTABLE SINGLE -BLADE BALANCING TYPE)
m500 SCALE: NONE
0
0
///,/////,///
0
0
0
0
4
4
4
4
4
4
4
4
411,40111,43111431114711474311.11.743111431114711.111.111,474111.1114311147111107.111.11.1
0
0
FIRE PROOF DUCT DETAIL - ELEVATION
H55000 SCALE: NONE
DUCT KEYED NOTES:
3" FIRE INSULATION BOARD.
OVAL DUCT.
1/2' THREADED ROD. DRILL HOLE THROUGH FIRE INSULATION FOR THE ROD. SEAL HOLE WITH CALS1iK GLUE.
1/2" THREADED ROD.
CUT JOINT BETWEEN BOARDS AS SHOWN. CONNECT JOINTS WITH DRYWALL SCREWS AS SHOWN EVERY 4'.
SEAL JOINT WITH PASCO CALSTIK GLUE.
TWO 2x2x1/4" ANGLE IRONS, BOLTED TOGETHER, CONNECTED TO CONCRETE CEILJNG WITH FOUR 1/2' EXPANSION BOLTS.
PLACE ONE DUCT HANGER AS SHOWN EVERY 10'.
2x2x1/2 U -CHANNEL.
PLACE STEEL RIBBON AS SHOWN TO SUPPORT F1REBOARDS, EVERY 2'.
2'x12 GA. STEEL HANGER TO SUPPORT NEW OVAL DUCT.
LONGITUDINAL WELDING JOINT FDR DUCT THAT I5 PLACED ON TOP TO PREVENT GREASE COLLECTING IN JOINT.
WELD 2"x 12 GA. STEEL TO DUCT AS SHOWN FOR ANCHORING.
PLACE 1/8" THICK RUBBER UNDERNEATH NUT AT THIS POINT FOR NOISE REDUCTION.
1* MIN. ON TOP
AND BOTTOM
MAIN DUCT
ADJUSTABLE
ELBOW RINGS
SUPPLY
AIR FLOW
SEAL ALL
AROUND
VOLUME DAMPER
(TYPICAL ALL)
EQUAL TO REQ'DT
BRANCH DUCT DIA.
1* MIN. ON TOP
AND BOTTOM
MAIN DUCT
SEAL ALL
AROUND
BRANCH DUCT
WIDTH, BUT MIN. 4"
VOLUME DAMPER
(TYPICAL ALL)
FOR USE ONLY WITH SUPPLY DUCTWORK.
EQUAL TO REQ'D
BRANCH DUCT
DIMENSIONS
ri'-'6) TYPICAL BRANCH TAKE -OFF FITTING DETAIL
Moo SCALE: NONE
FIRE PROOF DUCT ACCESS DOOR DETAIL - ELEVATION
M500 SCALE: NONE
ACCESS DOOR KEYED NOTES:
3' FIRE INSULATION BOARD.
OVAL DUCT.
2 HR. FIRE RATED ACCESS DOOR. ACCESS DOOR DIMENSIONS SHALL BE (HEIGHT OF DUCT)" HIGH x 24" WIDE.
CUT OUT OPENING IN FIREBOARD AT LOCATION OF ACCESS DOOR. OPENING SHALL BE BIG
ENOUGH TO PROVIDE EASY REMOVAL OF ACCESS DOOR.
COVER CUT OUT IN FIRE INSULATION WITH BLOCK OF FIRE INSULATION BOARD.
3"x3'x30" SPACER MADE OF FIRETEMP BOARD. FASTEN SPACER TO FIRE BOARD WITH DRYWALL SCREWS
AND CALSTIK GLUE.
BAR MADE OF 1/4" x 1" METAL SECURE OPENING COVER WITH THREE METAL BARS.
ATTACH AND SECURE 1/4" THREADED ROD IN SPACER BAR. USE WINGNUTS FOR ANCHORING METAL BAR.
SEAL OPENING WITH 1/8" THICK FIRE RESISTANT GASKET.
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTT, NY 13760
Tel. (607)-321-6100
www.stontec.com
Copyright Reserved
The Contractorshar verify and be responsible for all dimensons. DO
NOT scole The drawing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and cila rings are the property of
Stantec, Reproduction Or use for any purpose Other than nkat
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
by Appd. rf.MM.DO
JFG SAS 17.05.05
by Appd. Y't.P i.DD
Dam. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL
DETAILS
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
M500
of 1'-'1
50•
t
60•
i
(4.
12'
12'
X18"
U.L. Listed 4' LED Light
Fixture
016'
U.L. Listed 4' LED Light
Fixture
11 1 I
11 1 I
72'
BALANCE DAMPERS
HANGING ANGLE
20" CAPTRATE SOLO
FILTER WITH HOOK
3" INTERNAL STANDOFF
IT IS THE RESPONSIBILITY
OF TI -IE ARCHITECT/OWNER TO
ENSURE THAT THE HOOD CLEARANCE
FROM LIMITED -COMBUSTIBLE
AND COMBUSTIBLE MATERIALS
IS IN COMPLIANCE WITH
LOCAL CODE REQUIREMENTS.
GREASE DRAIN
WITH REMOVABLE CUP
GAS CHASE CUTOUT
(FOR GAS AND POWER LINES)
LEFT & RIGHT VERTICAL END PANELS
WITH ADJUSTABLE LEGS
12' 0.00'Norn./12' 0.D0'0D
72'
72' 72'
PLAN VIEW — Hood #2 (Hood #2)
12' 0.00" LONG 6024ND-2
4
80•
i=i
5a•
4' LEI] LIGHT FIXTURE, RECESSED, COLOR
TEMPERATURE 450010-5500K, INCLUDES (2)
„.7—
LED -312022N BULBS
2a'
L 4
EXISTING
EQUIPMENT
1/2'
FIELD WRAPPER 20.00" HIGH
(SEE HOOD OPTIONS TABLE)
1
24" NOM,
40.0" MAX
21'
SECTION V EW — MODEL 6024ND-2
HOODS #1 & 2
8a•
12' 0.00'Nc r ./12' 0.00'OD
PLAN VIEW — Hood #1 (Hood #1)
12' 0.00" LONG 6024ND-2
SPECIFICATION: CAPTRATE6GREASE—STOP' SOLO FILTER
THE CAPTRATE GREASE -STOP SOLO FILTER IS A SINGLE -STAGE FILTER FEATURING
A UNIQUE S -BAFFLE DESIGN IN CONJUNCTION WITH A SLOTTED REAR BAFFLE DESIGN,
TO DELIVER EXCEPTIONAL FILTRATION EFFICIENCY.
FILTER IS STAINLESS STEEL CONSTRUCTION, AND SIZED TO FIT INTO STANDARD
2 -INCH DEEP HOOD CHANNEL(S),
UNITS SHALL INCLUDE STAINLESS STEEL HANDLES AND A FASTENING DEVICE TO SECURE THE TWO
COMPONENTS WHEN ASSEMBLED.
GREASE EXTRACTION EFFICIENCY PERFORMANCE SHALL REMOVE AT LEAST 75% OF GREASE
PARTICLES FIVE MICRONS IN SIZE, AND 85% GREASE PARTICLES SEVEN MICRONS IN SIZE AND
LARGER, WITH A CORRESPONDING PRESSURE DROP NOT TO EXCEED 1.0 INCHES OF WATER GAUGE.
THE CAPTRATE GREASE -STOP SOLO WAS TESTED TO ASTM STANDARD ASTM F2519-05•1
EFFICIENCY VS. PARTICLE DIAMETER PRESSURE DROP VS. FLOW RATE
106 360
300
6
0
1
so
00
+0
20
0
4.1 .0
PARTICLE DIAMETER (urn)
14.0
CAPTRATE FILTERS ARE BUILT IN COMPLIANCE WITH:.
NEPA #96
NSF STANDARD #2
UL STANDARD #1046
INT. MECH. CODE (IMC)
ULC -5649
PRESSURE DROP in. H20)
2.56
200
1.50
1.00
0.50
6.04
0 500 1000
FLOW RATE (ern)
1500
BASIS OF DESIGN - THERMOTEK f CAPTIVEAIRE
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTT, NY 13760
Tel. (607)1-6100
www.stantec.com
Copyright Reserved
The Contractor *cal verify and be responsible for all dimensorls. DO
NOT scole the dra Ing - c ly errors or omissron% shall be reported to
Stantec without delay.
The Copyrights to all designs and ritw tgs are the property of
Stordeo, Reproduction or use for ony purpose other Mon that
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
Cr ISSUED FOR BID
Issued
File Nr>me:
By Appd. rf.MM.DO
J FG SAS 17.05.05
By Appd. Y'I.MM.DD
Dnnrn. Chkd. DsgrS. YY.MM DD
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL
DETAILS - HOODS #1 & #2
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
M501
of 1'-'1
6g'
•
u
X18' I-
U.L. Listed 4' LED Light
Fixture
1
12'
(61
72'
BALANCE DAMPERS
HANGING ANGLE
20" CAPTRATE COMBO
WITH HOOK- LP
3" INTERNAL STANDOFF
R IS THE RESPONSIBILRY
OF THE ARCHITECT/OWNER TO
ENSURE THAT THE HOOD CLEARANCE
FROM LIMITED—COMBUSTIBLE
AND COMBUSTIBLE MATERIALS
IS IN COMPLIANCE WITH
LOCAL CODE REQUIREMENTS.
GREASE DRAIN
WITH REMOVABLE CUP
GAS CHASE CUTOUT
(FOR GAS AND POWER UNES)
LEFT AND RIGHT VERTICAL END PANELS
WITH ADJUSTABLE LEGS
12' 0.00'Nom,l12` 0.00`0D
72'
PLAN VIEW — Hood #3 (Hood #3)
12' 0.00" LONG 6024ND-2
60'
4' LED LIGHT FIXTURE, RECESSED, COLOR
TEMPERATURE 4500K -5500K, INCLUDES (2)
7. --
LED -312022N BULBS
FIELD WRAPPER 20.00" HIGH
(SEE HOOD OPTIONS TABLE)
80'
ur‘v
/r
BACKSPLASH BOO
X 144.00" LONG
IGH
20'
4
EXISTING
EQUIPMENT
24' NUM.
48.0' MAX
21'
27'
SECTION VIEW — MODEL 6024ND-2
HOOD #3
80'
SPECIFICATION: CAPTRATE. CREASE—STOP. COMBO FILTER
THE CAPTRATE GREASE—STOP COMBO FILTER IS A MULTI—STAGE FILTRATION SYSTEM CONSISTING
OF A HIGH PERFORMANCE S --BAFFLE COMPONENT COMBINED WITH A SECONDARY PACKED --BED FILTER
OF POROUS CERAMIC MEDIA.
FILTER ASSEMBLY SHALL FIT INTO STANDARD TWO—INCH DEEP HOOD CHAtNEL(S).
METALLIC COMPONENTS STAINLESS STEEL CONSTRUCTION AND SIZED TO FIT AND DURABLE MICRO—POROUS
CERAMIC MEDIA THAT I5 CAPABLE OF ABSORBING SMALLER GREASE PARTICULATE BY MEANS OF
CAPILLARY ACTION.
UNITS SHALL INCLUDE STAINLESS STEEL HANDLES AND A FASTENING DEVICE TO SECURE THE TWO
COMPONENTS WHEN ASSEMBLED.
GREASE EXTRACTION EFFICIENCY PERFORMANCE SHALL REMOVE AT LEAST 97% OF THE TOTAL MASS
EMITTED GREASE PARTICLES AND HAVING FUNCTIONAL EFFICIENCY OF 60% GREATER OF GREASE
PARTICLES EMITTED TWO MICRONS IN SIZE AND LARGER.
THE CAPTRATE GREASE—STOP COMBO WAS TESTED TO ASTM STANDARD ASTM F2519-05.
2
L.l
EFFICIENCY VS. PARTICLE DIAMETER
106
so
so
40
20
6
0.1
PARTICLE DIAMETER (un')
19.0
CAPTRATE FILTERS ARE BUILT IN COMPLIANCE WITH:.
NFPA #96
NSF STANDARD #2
UL STANDARD #1046
INT. MECH. CODE (IMC)
ULC—S649
PRESSURE DROP On, H20)
PRESSURE DROP VS. FLOW RATE
9
500
1000
FLOW RATE (cfm)
1500
BASIS OF DESIGN - THERMOTEK / CAPTIVEAIRE
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTT, NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractor shoal verify and be responsible for all dImensons. DO
NOT scole the dra Ing - any errors or omissions shall be reported to
Stantec without delay.
The Copyrights to all designs and ritve rigs are the property of
Stantec, Reproduction or use for ony purpose other than tot
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
By Appd. rf.MM.DO
JFG SAS 17.05.05
by Appd. Y't.MM.DO
Dwn. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL
DETAILS - HOOD #3
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
M502
of 1'-'1
6O'
F
016'
U.L. Listed 4' LED Light
Fixture
30'
A
17
N,
E]
016'
U.L. Listed 4' LED Light
Fixture
=I
30'
60'
72'
EXHAUST RISER
HANGING ANGLE
GAS CHASE CUTOUT
(FOR CAS AND POWER LINES)
LEFT & RIGHT VERTICAL END PANELS
WITH ADJUSTABLE LEGS
00'
12' 0.00'Norti,l12' 0.00'0D
72'
72'
PLAN VIEW — Hood #5 (Hood #5)
12' 0.00" LONG 6024VHB—G—ND
60'
SEE HEED TABLE
J
4' LED LICHT FIXTURE, RECESSED, COLOR
TEMPERATURE 4500K -5500K, INCLUDES (2)
LED -312022N BULBS
FIELD WRAPPER 20.00" HIGH
(SEE HOOD OPTIONS TABLE}
DRAIN 3/4" PERIMETER GUTTER
BACKSPLASH J30.0'u" HIGH
X 258.00" LONG
4'
20'
1
4
EXISTING
EQUIPMENT
1/2'
24' NON.
21'
27'
SECTION VIEW — MODEL 6024VHB—C—ND
HOODS #4 & 5
00'
12' 0.00' Jork,r12' 0.00'0D
72'
PLAN VIEW — Hood #4 (Hood #4)
12' 0.00" LONG 6024VH —0—ND
BASIS OF DESIGN - THERMOTEK f CAPTIVEAIRE
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTT, NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractorshar verify and be responsible for all dimensions. DO
NOT scole The drawing - ctly errors or omiss1on% shall be reported to
Stantec without delay.
The Copyrights to all designs and craw rigs are the property of
Stordeo, Reproduction or use for ony purpose other Mon that
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
0 ISSUED FOR BID
Issued
Fie Nene:
by Appd. T(.MM.DO
JFG SAS 17.05.05
by Appd. ri.P iDD
Dwn. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL
DETAILS - HOODS #4 & #5
Project No. Scale
191 001394 AS NOTED
Drawing No. Sheet Revision
M503
of A
54'
../////////.///////. .///// ///////////////////////// .//.///////// ///////////
014'
D.L. Listed 4' LED Light
Fixture
014'
A
48'
EXHAUST RISER
HANGING ANGLE
20' CAPTRATE SOLO
FILTER WITH HOOK
3" INTERNAL STANDOFF
IT IS THE RESPONSIBILITY
OF THE ARCHITECT/OWNER TO
ENSURE THAT THE HOOD CLEARANCE
FROM LIMITED—COMBUSTIBLE
AND COMBUSTIBLE MATERIALS
IS IN COMPLIANCE WITH
LOCAL CODE REQUIREMENTS.
GREASE DRAIN
WITH REMOVABLE CUP
GAS CHASE CUTOUT
(FOR OAS AND POWER LINES)
LEFT AND RIGHT VERTICAL END PANELS
WITH ADJUSTABLE LEGS
E H❑❑D TABLE
so'
54'
96'
16' 0.0O'Nomi16' 0,0010D
48'
PLAN VIEW — Hood #6 (Hood #6/7)
16' 0.00" LONG 5424ND-2
BACKSPLASH 80.0 r" HIGH
X 192.0D" LONG
20'
4
EXISTING
EQUIPMENT
1/P'
4' LED LIGHT FIXTURE, RECESSED, COLOR
TEMPERATURE 4500K -5500K, INCLUDES (2)
LED -312022N BULBS
1
24' NUM.
1
480' MAX
21' --I T
27'
SECTION VIEW — MODEL 5424ND-2
HOOD #6/7
80•
SPECIFICATION: CAPTRATE°GREASE—STOP° SOLO FILTER
THE CAPTRATE GREASE—STOP SOLO FILTER IS A SINGLE—STAGE FILTER FEATURING
A UNIQUE S—BAFFLE DESIGN IN CONJUNCTION WITH A SLOTTED REAR BAFFLE DESIGN,
TO DELIVER EXCEPTIONAL FILTRATION EFFICIENCY.
FILTER IS STAINLESS STEEL CONSTRUCTION, AND SIZED TO FIT INTO STANDARD
2—INCH DEEP HOOD CHANNEL(S).
UNITS SHALL INCLUDE STAINLESS STEEL HANDLES AND A FASTENING DEVICE TO SECURE THE TWO
COMPONENTS WHEN ASSEMBLED.
GREASE EXTRACTION EFFICIENCY PERFORMANCE SHALL REMOVE AT LEAST 75% OF GREASE
PARTICLES FIVE MICRONS IN SIZE, AND 85% GREASE PARTICLES SEVEN MICRONS IN SIZE AND
LARGER, WITH A CORRESPONDING PRESSURE DROP NOT TO EXCEED 1.0 INCHES OF WATER GAUGE.
THE CAPTRATE GREASE—STOP SOLO WAS TESTED TC ASTM STANDARD ASTM F2519-05.
EFFICIENCY VS. PARTICLE DIAMETER
im
4
as
ai
.13
PARTICLE DIAMETER (urn)
Tao
CAPTRATE FILTERS ARE BUILT IN COMPLIANCE WITH:,
NEPA #96
NSF STANDARD #2
UL STANDARD #1046
INT. MECH. CODE (IMO)
ULC—S649
PRESSURE DROP VS. FLOW RATE
3,511
3.00
LSO
1A4
&OD
a
baa row
FLOW RATE (dm)
15ov
BASIS OF DESIGN - THERMOTEK 1 CAPTIVEAIRE
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTT, NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractor slid verify and be responsible for all dimensions. DO
NOT scole the drawing - ctly errors or omissron% shall be reported to
Stantec without delay.
The Copyrights to all designs and cila rings are the property of
Stordec, Reproduction or use for ony purpose other Mon that
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
By Appd. rf.MM.DO
JFG SAS 17.05.05
by Appd. Y'1.MM.DO
Onnrn. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL
DETAILS - HOOD #6/7
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
M504
of 1'-'1
1" LAYER OF INSULATION
FACTORY INSTALLED IN
1.00" END STANDOFF MEETS
0" REQUIREMENTS CLEARANCE
TO COMBUSTIBLE SURFACES.
6 0'
1'
7
014'
U.L. Listed 4' LED Light
Fixture
47 1/2'
11'
FH-AUST RISER
HANGING ANGLE
20" CAPTRATE COMBO
WITH HOOK— LP
3" INTERNAL STANDOFF
IT IS THE RESPONSIBILITY
OF THE ARCHITECT/OWNER TO
ENSURE THAT THE HOOD CLEARANCE
FROM LIMTED—COMBUSTIBLE
AND COMBUSTIBLE MATERIALS
IS IN COMPLIANCE WITH
LOCAL CODE REQUIREMENTS.
GREASE DRAIN
WITH REMOVABLE CUP
LEFT AND RIGHT WALL AS END PANELS
60"
0114'
11"
7
95.
15' 10,00'Nnr,,/15' 10.aa'DIl
16'-0.00' Overall Length
47 1!2'
PLAN VIEW — Hood #7 ("Hood #8")
15' 10.00" LONG 6024ND-2
4' LED LIGHT FIXTURE, RECESSED, COLOR
TEMPERATURE 4500K -5500K, INCLUDES (2)
LED 312Q22N BULBS
,..7. --
HELD WRAPPER 20.00" HIGH
(SEE HOOD OPTIONS TABLE)
E HOOD TALE
BACKSFLASH 80.00" HIGH
X 192.00' LONG
SECTION VIEW — MODEL 6024ND-2
HOOD — #7 ("Hood #8")
48,0" N1AX
24' NOM.
00"
.. 1'
1" LAYER OF INSULATION
FACTORY INSTALLED IN
1.00" END STANDOFF MEETS
O" REQUIREMENTS CLEARANCE
TO COMBUSTIBLE SURFACES.
SPECIFICATION: CAPTRATE GREASE—STOP COMBO FELTER
THE CAPTRATE GREASE—STOP COMBO FILTER IS A MULTI—STAGE FILTRATION SYSTEM CONSISTING
OF A HIGH PERFORMANCE S—BAFFLE COMPONENT COMBINED WITH A SECONDARY PACKED—BED FILTER
OF POROUS CERAMIC MEDIA.
FILTER ASSEMBLY SHALL FIT INTO STANDARD TWO—INCH DEEP HOOD CHANNEL(S).
METALLIC COMPONENTS STAINLESS STEEL CONSTRUCTION AND SIZED TO FIT AND DURABLE MICRO—POROUS
CERAMIC MEDIA THAT IS CAPABLE OF ABSORBING SMALLER GREASE PARTICULATE BY MEANS OF
CAPILLARY ACTION.
UNITS SHALL INCLUDE STAINLESS STEEL HANDLES AND A FASTENING DEVICE TO SECURE THE TWO
COMPONENTS WHEN ASSEMBLED.
GREASE EXTRACTION EFFICIENCY PERFORMANCE SHALL REMOVE AT LEAST 97% OF THE TOTAL MASS
EMITTED GREASE PARTICLES AND HAVING FUNCTIONAL EFFICIENCY OF 60% GREATER OF GREASE
PARTICLES EMITTED 1WO MICRONS IN SIZE AND LARGER.
THE CAPTRATE GREASE—STOP COMBO WAS TESTED TO ASTM STANDARD ASTM F2519-05.
EFFICIENCY VS. PARTICLE DIAMETER
1aa
FRACTIONAL EFFICIENCY (X)
PARTICLE DIAMETER (um)
100
CAPTRATE FILTERS ARE BUILT IN COMPLIANCE WITH:.
NFPA #96
NSF STANDARD #2
UL STANDARD #1046
INT. MECH. CODE (IMC)
ULC -5649
PRESSURE DROP On. H20)
PRESSURE DROP VS. FLOW RATE
a
sao 1000
FLOW RATE (cfm)
1500
BASIS OF DESIGN - THERMOTEK f CAPTIVEAIRE
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTT, NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractor shcJ verify and be responsible for all dimensorls. DO
NOT scole The drawing - ony errors or omissron% shall be reported to
Stantec without delay.
The Copyrights to all designs and craw rigs Ora the property of
Stantec, Reproduction or use for any purpose other then that
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
File NQrne:
by Appd. T(.MM.DO
JFG SAS 17.05.05
by Appd. Y't.MM.DD
Dwn. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL
DETAILS - HOOD #8
Project No.
191001394
Scale
AS NOTED
Drawing Na. Sheet Revision
M505
of 1'-'1
KITCHEN HOOD SCHEDULE
HOOD
NO.
TAG
MODEL
LENGTH
MIX.
COOKING
TEMP.
EXHAUST PLENUM
HOOD
HOOD CONFIG.
FILTER(S)
UGHT(S)
FAN
VPH/HZ
TOTALCONSTRUCT.
EXH. CFM
E RISER(S)
END TO
END
ROW
TYPE
QTY.
HEIGHT
LENGTH$17
EFFICIENCY 0
7 MICRONS
VELOCITY
TYPE
WIRE
GUARD
HOOD
HANGING
WEIGHT
NOTES
WIDTH
LENGTH
: HEIGHT
DIA,
CRT
(p)
S.P.
11
HOOD
6024600
ND -2
12' 0.00'
DEC. F
2400
69.1
815
4"
16"
2400
1719
-0.197"
430 SS
WHERE EXPOSED
RIGHT
ALONE
CAPTRATE
SOLO FILTER9
20"
16*
85% SEE FILTER
SPEC.
2
4' LED UGIT
NO
601
LBS.
1.2.3
22
HOOD
6024600
ND -2
12' 0.00'
DEC. F
3300
1.0
640
: 4"
18"
3300
1867
-1.151"
430 SS
WHERE EXPOSED
LEFT
ALONE
CAPTRATE
SOLO FILTER
9
20"
16*
85% SEE FILTER
SPEC.
2
4' LED UGIT
NO
601
LBS.
1.2.3
3
HOOD
3
6024
ND -2
12' 0'00'
600
DEC. F
3300
SOUTH AREAWAY
OKENSHIELDS HOOD B
: 4"
18"
3300
1867
-1.496"
430 SS
WHERE EXPOSED
ALONE
ALONE
CAPTRATE
COMBO FILTER
9
20"
16*
99% SEE FILTER
SPEC.
2
4. LED UGIT
NO
695
LBS.
1.2.3
¢
HOOD
4
6024700
VHB-G-ND
12' 0.00'
DEC. F
1800
4"
16"
1800
1289
-0.168"
430 SS
100%
RIGHT
ALONE
2
4' LED UGIT
NOLBS.
481
1.2.3
55
HOOD
6024700430
VHB-G-ND
12' 0.00`
DEC. F
1800
4"
16"
1800
1289
-0.166"
SS
104
LEFT
ALONE
.
.
.
•
2
4' LED UGIT
NO
468
LBS.
1.2.3
6
HOOD
#6/7
3650600
ND -2
16' 0.00`
DEC. F
4400
ALONE
ALONE
SOLO FILTER
12
20"
16*
96 SEE FILTER
SPEC.
3
4' LED UGIT
NOLBS.
721
1.2.3
4"
14"
2200
2055
-1.041"
WHERE EXPOSED
1
HOOD
$
5424600
ND -2
133 10.00"
DEG. F
4400
ALONE
ALONE
COMBO FILTER
11
20"
16*
SPEC.
3
4' LED UGIT
NOLBS.
1.2.3
4'
14"
2200
2058
-1.503"
WHERE EXPOSED
N0
BASIS OF DESIGN MANUFACTURER - THERMOTEK/CAPTIVE AIRE.
CONTROLS FOR KITCHEN HOODS SHALL BE PROVIDED IN A FORTHCOMING ADDENDUM.
CHEMICAL FIRE SUPPRESSION SYSTEM FOR KITCHEN HOODS SHALL BE PROVIDED BY A THIRD PARTY VENDOR IN A FORTHCOMING ADDENDUM.
1.
2.
3.
FAN SCHEDULE
TAG
LOCATION
SERVICE
MODEL
CFM
EXT. STATIC
OUTLET
DRIVE
BHP
MOTOR
FAN
VPH/HZ
FLA
WEIGHT
NOTES
NUMBER
27"x36"±
2
NUMBER
E6.114
PRESSURE
VELOCITY
TYPE
386
HP
RPM
815
1,2,3
(LB}
EXHAUST
27"x3r1
2
ARCHITECTURAL LOUVERS
MIN
ALUMINUM
(IN WG)
(FPM)
107
9.33
69.1
815
1.2.3
BACKSPLASH - INSIDE CORNER 80.00" HIGH X 2,00" LEG LENGTH 430 SS VERTICAL
MANUFACTURER - ARCHITECTURAL LOUVERS
DRAWING A-401 FOR LOUVER INSTALLATION DETAILS.
INSECT SCREEN AT EXTERIOR.
1. BASIS OF DESIGN
2. REFER TO ARCHITECTURAL
3. PROVIDE BIRD AND
EF -1
ROOM 300CB
TYPE 11 KITCHEN HOODS 4&5
165QMX
3600
0.75
1228
BELT
0.737
1.5
1228
480/3/60
3.0
472
1,2,3
EF -2
ROOM 30008
MAIN KITCHEN DISHWASHER :
120QMX
1000
1.0
640
BELT
0.350
0.75
1530
208/3/60
3.5
258
1,2,3
EF -3
ROOM 600UB
TYPE 1 KITCHEN HOODS 1,2,3,& 6/7
2.70QMX
17000*
3.0*
2149
BELT
12.1
20
1426
460/3/60
27
1211
1,2,3,4
EF -4
SOUTH AREAWAY
OKENSHIELDS HOOD B
202QMX-HP
4400
2.5
988
BELT
2.98
7.5
1424
460/3/60
11
727
1,2,3
DESIGN MANUFACTURER: LOREN COOK
1. BASIS OF
2. PROVIDE SPRING ISOLATORS AS REQUIRED FOR EACH FAN INSTALLATION.
3. CONTROLS FOR EXHAUST FANS SHALL BE PROVIDED IN A FORTHCOMING ADDENDUM.
4. *DESIGN VALUES FOR EF -3 ARE 13,400 CFM, 2.25 IN. WO ESP. FAN SELECTED AND SCHEDULED AT 17,000 CFM, 3.0 IN. WG ESP, TO ACCOMODATE A POTENTIAL ADOFI1ON
OF A FUTURE KITCHEN EXHAUST HOOD.
LOUVER SCHEDULE
TAG
NUMBER
APPLICATION
ZE
:xM.)
QTY
MANUFACTURER
MODEL
MATERIAL
FINISH
TOTAL
AIRFLOW
(CFM)
TOTAL
VELOCITY
(FPM)
TOTAL
FREE AREA
(SQ FT.)
FREE
AREA
(2)
WATER
PENETRATION
VELOCITY (FPM)
NOTES
L-1
EXHAUST
27"x36"±
2
ARCHREC"TLJRAL LOUVERS
E6.114
ALUMINUM
HIGH PERF. PAINT SYSTEM
3600
386
9.33
69.1
815
1,2,3
L-2
EXHAUST
27"x3r1
2
ARCHITECTURAL LOUVERS
MIN
ALUMINUM
HIGH PERF. PAINT SYSTEM
1000
107
9.33
69.1
815
1.2.3
BACKSPLASH - INSIDE CORNER 80.00" HIGH X 2,00" LEG LENGTH 430 SS VERTICAL
MANUFACTURER - ARCHITECTURAL LOUVERS
DRAWING A-401 FOR LOUVER INSTALLATION DETAILS.
INSECT SCREEN AT EXTERIOR.
1. BASIS OF DESIGN
2. REFER TO ARCHITECTURAL
3. PROVIDE BIRD AND
SUPPLY DIFFUSER SCHEDULE
TAG
M MBER
APPLJCA11ON
MATERIAL
FIN/SH
SIZE
(IN.)
NECK
SIE
(IN.)
MANUFACTURER
MODEL.
MAX
NC
NOTES
S-1
SUPPLY
ALUMINIUM
WHITE
24"x24*
12"
PRICE
LED
15
1,2
S-2
SUPPLY
ALUMINIUM
WHITE
24'x24"
12"
PRICE
LCMD
19
1,2
tICE- ..
1. BASIS OF DESIGN MANUFACTURER - PRICE
2. REFER TO DRAWING M-101 FOR AIRFLOW VALUES.
KITCHEN HOOD OPTIONS SCHEDULE
Hoop
NO.
TAG
OPTION
1
HOOD 1
FIELD WRAPPER 20.00" HIGH FRONT, RIGHT
BALANCE DAMPERS
RIGHT VERTICAL END PANEL 27" TOP WIDTH, 21" BOTTOM WIDTH, 80" HIGH INSULATED 430
5S
2
HOOD 12
FIELD WRAPPER 20.00" HIGH FRONT, LEFT
BALANCE DAMPERS
LEFT VERTICAL END PANEL 27" TOP WIDTH, 21* BOTTOM WIDTH, 80* HIGH INSULATED 430
55
3
HOOD #3
FIELD WRAPPER 20.00" HIGH FRONT, LEFT, RIGHT
BACKSPLASH 80.00" HIGH X 144.00" LONG 430 SS VERTICAL
BALANCE DAMPERS
LEFT VERTICAL END PANEL 27" TOP WIDTH, 21* BOTTOM WIDTH, 80" HIGH INSULATED 430
5S
RIGHT VERTICAL END PANEL 27" TOP WIDTH, 21" BOTTOM WIDTH, 80" HIGH INSULATED 430
SS
4
HOOD I4
FIELD WRAPPER 20.00" HIGH FRONT, RIGHT
RIGHT VERTICAL END PANEL 27" TOP WIDTH, 21" BOTTOM WIDTH, 80" HIGH INSULATED 430
SS
5
HOODS
FIELD WRAPPER 20.00" HIGH FRONT
BACKSPLASH 80.00" HIGH X 288.00" LONG 430 SS VERTICAL
LEFT VERTICAL END PANEL 27" TOP WIDTH. 21" BOTTOM WIDTH, 80" HIGH INSULATED 430
55
6
HOOD
6/7
BACKSPLASH 80.00" HIGH X 192.00" LONG 430 5S VERTICAL
RIGHT VERTICAL END PANEL 27" TOP WIDTH, 21" BOTTOM WIDTH, 80" HIGH INSULATED 430
5S
LEFT VERTICAL END PANEL 27" TOP WIDTH. 21" BOTTOM WIDTH. 80" HIGH INSULATED 430
SS
7
HOOD #8
FIELD WRAPPER 20.00" HIGH FRONT. LEFT, RIGHT
BACKSPLASH 80.00" HIGH X 192.00" LONG 430 SS VERTICAL
LEFT SIDESPLASH 80.00" HIGH X 60.00" LONG 430 SS VERTICAL
RIGHT SIDESPLASH 80.00" HIGH X 60.00" LONG 430 SS VERTICAL
LEFT END STANDOFF (FINISHED) 1" WIDE 60" LONG INSULATED
RIGHT END STANDOFF (FINISHED) 1" WIDE 60" LONG INSULATED
BACKSPLASH - INSIDE CORNER 80.00" HIGH X 2,00" LEG LENGTH 430 SS VERTICAL
BACKSPLASH - INSIDE CORNER 80.00" HIGH X 2.00" LEG LENGTH 430 SS VERTICAL
RIGHT WALL AS END PANEL
LEFT WALL AS END PANEL
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTT, NY 13760
Tel. (607)1-6100
www.stantec.com
Copyright Reserved
The Contractor shcJ verify and be responsible for all dimensons. DO
NOT scole The drawing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and cila rings are the property of
Stantec, Reproduction Or use for any purpose Other than nkat
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
by Appd. rf.MM.DO
JFG SAS 17.05.05
by Appd. Y't.MM.DO
Dwn. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL
SCHEDULES
Project No. Scale
191001394 AS NOTED
Drawing No. Sheet Revision
M600
of 1'-'1
RIJLIF
SIXTH FLOOR
I ROOM 600UB
FIFTH FLOOR
}
FAN
FOURTH FLOOR
L-2 L-2
WINDOW
LOUVERS
1,000 CFM
L-1 L-1
WINDOW
LOUVERS
THIRD FLOOR
3,600 CFM
GF
ROOM 309
1.300
r- CFM
AtA
HOOD 3
WEST HOOD ADJ. TO OKENSHIELDS
WALL MOUNTED CANOPY
* CHAR BROILER TO
POTENTIALLY BE REPLACED
WITH WOK IN THE FUTURE
1,800
CFM
jik
U
(HEAVY DUTY EQUIPMENT)
CHAR
BROILER*
HOOD 5
MAIN KITCHEN SOUTH HOOD
WALL MOUNTED CANOPY
HOOD 4.
MAIN KITCHEN SOUTH HOOD
WALL MOUNTED CANOPY
!Ig
(MEDIUM DUTY EQUIPMENT)
!ig
COMBINATION
CONVECTION
STEAMER
(MEDIUM DUTY EQUIPMENT)
•
20+GALLON STEAM KETTLES 20+GrALLON STEAM KETTLES
1
I•
11
FLAT TOP
GRIDDLE
.00
.3300
CFM -1
1
1
1
1
1
1
1
c` I.00
15,700_ 9,000
CFM
I CFM
I
I
HOOD 1
MAIN KITCHEN BAKING HOOD
WALL MOUNTED CANOPY
ROOD 2
MAIN KITCHEN NORTH HOOD
WALL MOUNTED CANOPY
(LIGHT DUTY EQUIPMENT)
11
11
ar*i
(HEAVY DUTY EQUIPMENT)
1000
CFM
r
1
ROOM 308
DISHWASHER
ROOM 307
9,000
CFM
es -
It* -e
HOOD 6/7
IVY SERVERY REAR HOOT]
WALL MOUNTED CANOPY
HUMIDIFIED
HOLDING (MEDIUM DUTY
CABINEET EQUIPMENT)
SEIM
FLAT TOP FLAT TOP
DEEP FRYER 1 GRIDDLE GRIDDLE
13 400
CFM —
'I
J
ROOM 305
4 400
enA
ROOD 8
OKENSHIELDS WOK HOOD
WALL MOUNTED CANOPY
131117
DEIEP
FRYER
HEATED HOLDING
CABINET/OVEN
WOK
SOUTH
BUILDING
AREAWAY
4,400 CFM
EF -4
EXITING
WEATHER
HOOD
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTT, NY 13760
Tel. (607)1-6100
www.stantec.com
Copyright Reserved
The Contractor slid verify and be responsible for all dimensions. DO
NOT scole The drawing - ctly errors or omisslon% shall be reported to
Stantec without delay.
The Copyrights to all designs and ii-aw rigs are the property of
Stordeo, Reproduction or use for ony purpose other Mon that
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Nene:
by Appd. rf.MM.DO
JFG SAS 17.05.05
by
Appd. ri.MMi.DD
Own. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
WILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL HVAC
EXHAUST AIR FLOW DIAGRAM
Project No.
191001394
Scale
AS NOTED
Dawing No. Sheet
Revision
M700 of A
SEQUENCE OF OPERATIONS
EF -1 ANf1 EF -2
A. ORAL
1. THE STATUS OF THE SYSTEM SHALL BE DISPLAYED ON THE CONTROL PANEL AT THE EXHAUST
HOOD AS FOLLOWS:
1.1. FAN SYSTEM IS READY AND OPERATING - GREEN UGHT DISPLAYED
1.2. FAN SYSTEM IS NOT READY AND/OR NOT RUNNING - RED UGHT DISPLAYED
B. SCHEDULED KITCHEN OPERATION:
1. THE FAN SHALL RUN CONTINUOUSLY.
2. THE STATUS OF THE SYSTEM SHALL BE DISPLAYED ON THE CONTROL PANEL.
3. IF THE FAN SHOULD FAIL DURING SCHEDULED COOKING OPERATION, THE RED LIGHT SHALL BE DISPLAYED
AND AN AUDIBLE ALARM SHALL SOUND.
C. OUTSIDE OF SCHEDULED KITCHEN OPERATIONS:
1. THE OPERATOR SHALL PRESS THE START BUTTON ON THE CONTROL PANEL; UPON FAN START
CONF1RMATION, THE GREEN LIGHT SHALL BE DISPLAYED.
2. THE FAN SHALL CONTINUE TO RUN FOR 2 HOURS (ADJUSTABLE); WITH 15 MINUTES REMAINING AN AUDIBLE
TONE SHALL BE INITIATED TO ALERT THE OPERATOR TO THE FAN SHUTTING DOWN. IF THE OPERATOR
PRESSES THE START BUTTON AGAIN, THE 11MER SHALL RESTART. E THE BUTTON IS NOT PRESSED AGAIN,
THE FAIN SHALL SHUTDOWN.
3. IF THE FAN SHOULD FAIL DURING OPERATION, THE RED LIGHT SHALL BE DISPLAYED AND AN AUDIBLE ALARM
SHALL SOUND.
EE-. (J•OOD 1. 2. 3, I
A. GENERAL
1. THE STATUS OF THE SYSTEM SHALL BE DISPLAYED ON THE CONTROL PANEL AT THE EXHAUST
HOOD AS FOLLOWS:
1,1. FAN SYSTEM IS READY AND OPERATING - GREEN LIGHT DISPLAYED
1.2. FAN SYSTEM IS NOT READY AND/OR NOT RUNNING - RED UGHT DISPLAYED
B. SCHEDULED KITCHEN OPERATION:
1. THE FAN SHALL RUN CONTINUOUSLY.
2. THE STATUS OF THE SYSTEM SHALL BE DISPLAYED ON THE CONTROL PANEL LOCATED AT EACH OF
THE HOOD LOCATIONS.
3. IF THE FAN SHOULD FAIL DURING OPERATION:
3.1. THE RED UGHT SHALL BE DISPLAYED
3.2. AN AUDIBLE ALARM SHALL SOUND
3.3. AN WARM SHALL BE ISSUED THROUGH THE BMS
4. FAN AIRFLOW SHALL BE MONITORED VIA FLOW RIG SENSOR LOCATED ON THE EXHAUST FAN INLET. IF THE
AIRFLOW FALLS BELOW SET POINT BY 10% (ADJUST{ E) THE VFD SHALL INCREASE SPEED AND AN ALARM
SHALL BE SENT THROUGH THE BMS.
C. OUTSIDE OF SCHEDULED KITCHEN OPERATIONS:
1. THE OPERATOR SHALL PRESS THE START BUTTON ON THE CONTROL PANEL LOCATED ADJACENT TO THE
HOOD; UPON FAN START CONF RWiTION, THE GREEN LIGHT SHALL BE DISPLAYED.
2. THE FAN SHALL CONTINUE TO RUN FOR 2 HOURS (ADJUSTABLE); WITH 15 MINUTES REMAINING AN AUDIBLE
TONE SHALL BE I NITIAIED TO ALERT THE OPERATOR TO THE FAN SHUTTING DOWN. IF THE OPERATOR
PRESSES THE START BUTTON AGAIN, THE TIMI SHALL RESTATE. F THE BUTTON IS NOT PRESSED AGAIN,
THE FAN SHA.. SHUTDOWN.
3. IF THE FAN SHOULD FAIL DURING OPERATION:
3.1. THE RED LIGHT SHALL BE DISPLAYED
3.2. AN AUDIBLE ALARM SHALL SOUND
3.3. AN ALARM SWILL BE ISSUED THROUGH THE BMS
D. MANUAL FAN DISABLE
1. IF THE STOP BUTTON IS PUSHED DURING FAN OPERATION, TFE GREEN LIGHT SHALL BE OFF AND THE RED
LIGHT ON AT ALL CONTROL STATIONS ASSOCIATED WITH THE FAN SYSTEM. THE FAN MALL CONTINUE TO
RUN UNTIL ALL TEMPERATURES WTTFAN THE H000 FAN SYSTEM ARE BELOW 1001F (ADJUSTABLE)
EF -4 (HOOD 8)
A. GENERAL
1. THE STATUS OF THE SYSTEM SHALL BE DISPLAYED ON THE CONTROL PANEL AT THE EXHAUST
HOOD A5 FOLLOWS:
1.1. FAN SYSTEM IS READY AND OPERATING - GREEN LIGHT DISPLAYED
L2. FAN SYSTEM IS NOT READY AND/OR NOT RUNNING - RED LIGHT DISPLAYED
B. SCHEDULED KITCHEN OPERATION:
1. TEE FAN SHALL RUN CONTINUOUSLY.
2. THE STATUS OF THE SYSTEM SHALL BE DISPLAYED ON THE CONTROL PANEL.
3. IF THE FAN SHOULD FAIL DURING OPERATION:
3.1. THE RED LIGHT SHALL BE DISPLAYED
3.2. AN AUDIBLE ALARM SHALL SOUND
3.3. AN ALARM SHALL BE ISSUED THROUGH THE BMS
4. FAN AIRFLOW SHALL BE MONITORED VIA FLOW RING SENSOR LOCATED ON THE EXHMIST FAN INLET. F THE
AIRFLOW FALLS BELOW SET POINT BY 1O% (ADJUSTABLE) THE VFD SHALL INCREASE SPEED AND AN ALARM
SHALL BE SENT THROUGH THE EIMS.
C. OUTSIDE OF SCHEDULED KITCHEN OPERATIONS:
1, THE OPERATOR SHALL PRESS THE START BUTTON ON THE CONTROL PANEL: UPON FAN START
CONFIRMATION, THE GREEN LIGHT SHALL BE DISPLAYED.
2. THE FAN SHALL CONTINUE TO RUN FOR 2 HOURS (ADJUSTABLE); WITH 15 MINUTES REMAINING AN AUDIBLE
TONE SHALL BE INITIATED TO ALERT THE OPERATOR TO THE FAN SHUT11ING DOWN, IF THE OPERATOR
PRESSES THE START BUTTON AGAIN, THE TIMER SHALL RESTART. IF THE BUTTON IS NOT PRESSED ACA+I,
THE FAN SHALL SHUTDOWN.
3. IF THE FAN SHOULD FAL DURING OPERATION:
3.1. THE RED LIGHT SHALL BE DISPLAYED
3.2. AN AUDIBLE ALARM SHALL SOUND
3.3. AN ALARM SHALL BE ISSUED THROUGH THE BMS
D. MANUAL FAN DISABLE
1, IF THE STOP BUTTON IS PUSHED DURING FAN OPERATION, THE GREEN LIMIT SHALL BE OFF AND THE RED
LIGHT ON. THE FAN SHALL CONTINUE TO RUN UNTIL ALL TEMPERATURES WITHIN THE H000 SYSTEM ARE
BELOW 100F (ADJUSTABLE)
TEMPERATURE IEIflNfrDRING
A. GENERAL
1. TEMPERATURE SHALL BE MONITORED AND TRENDED WITHIN THE HOOD DIRECTLY
ADJACENT TO THE ANSUL SENSING ELEMENTS (MINIMUM 3 LOCATIONS).
2. TEMPERATURE SHALL BE MONITORED AND TRENDED WITHIN THE EXHAUST DUCTWORK.
B. THE TEMPERATURE SET POINTS SHALL BE DETERMINED DURING COMMISSIONING AND THROUGH
TRENDING.
1. TWO SET POINTS SHALL BE DETERMINED FOR EACH SENSING LOCATION.
1.1. ALERT - ISSUE AUDIBLE ALARM THROUGH THE ASSOCIATED HOOD CONTROL PANEL
1.2. ALARM - CONTINUE WITH AUDIBLE ALARM; SHUT GAS VALVE TO COOKING
APPUANCES
GAS CONTROL VALVE
A. GENERAL
1. NATURAL GAS TO THE COOKING APPLIANCES UNDER THE HOODS SHALL RUN THROUGH
NORMALLY OPEN, POWER TO CLOSE, MANUAL RESET SOLENOID VALVES.
B. GAS VALVE ACTUATION:
1. IF THE TEMPERATURE WITHIN THE HOOD OR DUCTWORK ASSOCIATED WITH THE HOOD ARE
ABOVE THE ALARM LEVEL FOR MORE THAN 1 MINUTE (ADJUSTABLE). THE BMS SHALL
CLOSE THE GAS VALVE.
2. IF THE FIRE SUPPRESSION SYSTEM 15 ACTIVATED FOR RELEASE THE FIRE SUPPRESSION
CONTROL PANEL SHALL CLOSE THE GAS VALVE.
3. IF THE EMERGENCY OFF BUTTON IS PRESSED BY AN OPERATOR, THE GAS VALVE SHALL
CLOSE.
4. UPON GAS VALVE CLOSURE, THE VALVE SHALL BE OFF AND WILL REQUIRE A MANUAL
RESET.
KITCHEN
HOOD.
HOOD
COLLAR
T1
T1
4HHHHHHH
3 SENSOR TEMPERATURE ARRAY IN HOOD (TA -1) DETAIL
M70 SCALE: NONE
AT1
AT2E
GENERAL NOTES
1. CONTROLS SHALL BE PROVIDED AND INSTALLED PER CORNELL UNIVERSITY SPECIF1CATIONS.
2. COORDINATE CONTROLS WITH EXISTING CONTROL SYSTEM CURRENTLY AT USE WITHIN THE
BUILDING.
CONTROLS SYMBOLS AND ABBREVIATIONS
ANALOG INPUT (TO BMS)
e•
= ELECTRIC
AIF =AIRFLOW
T =TEMPERATURE
SPD = SPEED
DIGITAL INPUT (TO BMS)
E = ELECTRIC
CR = CURRENT RELAY FOR
STATUS
ANALOG OUTPUT (FROM BMS)
QE
= ELECTRIC
SPD = SPEED
DIGITAL OUTPUT (FROM BMS)
E = ELECTRIC
o/ = OPENiCLOSE
SiS = STOP(START
LEGEND
- -- -- -- -- -- - EXISTING EXHAUST AIR
- ----- - EXHAUST AIR
1
AFMS
EF-}(
❑T
VFD
BMS
E.O.
- CONTROL VALVE
- TEMPERATURE ARRAY
- AIRFLOW MEASURING STATION
- EXHAUST FAN
- TEMPERATURE TRANSMITTER
- VARIABLE FREQUENCY DRIVE
- TEMPERATURE SENSOR IN
THERMOWELL
- BUILDING MANAGEMENT STEIVI
- EMERGENCY OFF
3 SENSOR TEMPERATURE ARRAY IN DUCT (TA -2) DETAIL
M70 SCALE: NONE
DUCT OR HOOD
HIGH TEMPERATURE
SENSOR
WELDED STAINLESS
STEEL BUNG
STAINLESS STEEL
THERMOWELL WITH
THERMAL GREASE
INSERTION DEPTH TO
BE COORDINATED
WITH THE HOOD OR
DUCTWORK
TEMPERATURE SENSOR DETAIL
M70 SCALE NONE
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTT, NY 13760
Tel. (607)-321-6100
www.stontec.com
Copyright Reserved
The Contractor shcJ verify and be responsible forall dimensions. DO
NOT sccde the dra Ing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and dnovertgs are the property of
Stardeo, Reproduction or use for ony purpose other than tot
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
ISSUED FOR ADDENDUM
Issued
Fie Name:
by Appd. T(.MM.DO
JFG SAS 17.06.08
by
Appd. Y't.MMDD
Own. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL HVAC
CONTROLS LEAD SHEET &
SEQUENCE OF OPERATIONS
Project No.
191001394
Scale
AS NOTED
Drawing Na. Sheet Revision
M701
of 0
FOURTH FLOOR
L-1 L-1
WINDOW
LOUVERS
THIRD FLOOR
1,000
CFM
ROOM 309
3 SENSOR TEMP.
ARRAY IN HOOD,
REFER TO DETAIL
1 ON DWG M701
H000 5
MAIN KITCHEN SOUTH HOOD
WALL MOUNTED CANOPY
!Ig
(MEDIUM DUTY EQUIPMENT)
HOOD 4
MAIN WI-CHEN SOUTH HOOD
WALL MOUNTED CANOPY
RtgCOMBINATION
CONVECTION
STEAMER
(MEDIUM DUTY EQUIPMENT)fb
20+GALLON STEAhr KETTLES 20+GALLON STEAM KETTLES
11
FOURTH FLOOR
FOURTH FLOOR
LL2
WINDOW
LOUVERS
THIRD FLOOR
ROOM 30B
L000
CFM -r
n n
DISHWASHER
THIRD FLOOR
3 SENSOR TEMP. ARRAY IN DUCT.
REFER TO DETAIL 2 ON DWG M701,
HOOD 3 SENSOR
TEMP. ARRAY.
REFER TO DETAIL
1 ON DWG M701.
E
S
E
S/S
E
s/s
ANSUL
E.O.
BMS
Nei TO KITCHEN
StOURCT=t+ GAS S EQUIPMENT
ROOM 305
HOOD 8
OKENSHIELDS WOK HOOD
WALL MOUNTED CANOPY
DEEP
FRYER
HEATED HOLDING
CABIN ET/OVEN
WOK
WOK
TA- 2
0
SOUTH
BUILDING
AREAWAY
VFD
EF -4 -
4,400 CFM
A
E
S
EXISTING
WEATHER
HO®
KEYED NOTES
0
AIRFLOW MEASURING STATION (AFMS) SHALL BE PARAGON FLOW RING MOUNTED ON INLET OF
FAN. FLOW RING SHALL BE CONNECTED TO THE APS -1000 MASTER BLAMER PURGE SYSTEM.
PROVIDE 3/4" COMPRESSED AIR UNE TO THE MASTER BLASTER FROM THE SECOND FLOOR AIR
COMPRESSOR.
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTT, NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractor shcJ verify and be responsible for all dimensons. DO
NOT scale the drawing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and cila rings are the property of
Stardeo, Reproduction Or use for any purpose Other than nkat
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
ISSUED FOR ADDENDUM
Issued
Fie Name:
by Appd. rf. MM.DO
J FG SAS 17.06.08
by Appd. Y't.MMDD
Own. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL HVAC
HOODS 1 & 2, DISHWASHER EXHAUST,
& HOOD 8 CONTROLS DIAGRAM
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
M702
of 0
IE
ROOF
SIXTH FLOOR
AF
VFD
ROOM 600UB
O
S/S
EF -3
13,400 CFM
FIFTH FLOOR
FOURTH FLOOR
ANSUL
E.O.
BMS
E
S/S
E
S/S
E
SIS
SOURCE $
THIRD FLOOR
HOOD 3 SENSOR
TEMP. ARRAY.
REFER TO DETAIL
1 ON DWG M701.
IliiHOOD 3
EST HOOD ADJ. TO MD/SHIELDS
WALL MOUNTED CANOPY
r
ROOM 309
3,300
* CHAR BROILER TO
POTENTIALLY BE REPLACED
WITH WOK IN THE FUTURE
TO KITCHEN
S EQUIPMENT
(HEAVY DUTY EQUIPMENT)
CHAR
BROILER*
FLAT TOP
GRIDDLE
CFU
HODD 3 SENSOR
TEMP. ARRAY.
REFER TO DETAIL
1 ON DWG M701.
3 SENSOR TEMP. ARRAY IN DUCT.
REFER TO DETAIL 2 ON DWG M701,
3.300
CFM
c
1 5,700 . 9,000
CFM
HOOD 1
MAIN KFICHEN BAKING HOOD
WALL MOUNTED CANOPY
•.k;
(LIGHT DUTY EQUIPMENT)
MOOD 2
MAIN KITCHEN NORTH HOOD
WALL MOUNTED CANOPY
(HEAVY DUTY EQUIPMENT)
rr
NI Mr
DEEP
FRYER
TA -2
E
SfS
E
SfS
E
S/S
ANSUL
E.O.
BMS
TO KITCHEN SCURCE
EQUIPMENT
HEKU 3 SENSE]R
TEMP. ARRAY.
REFER TO DETAIL
1 ON DWG M701.
ROOM 307
9E0
CFI
13400
CFlN
3 SENSOR TEMP.
ARRAY IN DUCT.
REFER TO DETAIL
2 DN DWG M701.
ekkccv
ale—
HOOD 6/7
IW SERVERY REAR HOOD
WALL MOUNTED CANOPY
E
HUMIDIFIED
HOLDING (MEDIUM DUTY
CABIN EQUIPMENT)
TOASTER
DEEP FRYER
FLAT TOP
GRIDDLE
FLAT TOP
GRIDDLE
TO KITCHEN
EQUIPMENT
ANSUL
E.O.
BMS
i SOURCE
4
KEYED NOTES
0
AIRFLOW MEASURING STATION (AFIrIS) SHALL BE PARAGON FLOW RING MOUNTED ON INLET OF
FAN. FLOW RING SHALL BE CONNECTED TO THE APS -1000 MASTER BLAS1ER PURGE SYSTEM.
PROVIDE AIR COMPRESSOR AND PIPING AS REQUIRED TO THE FAN R0OIrt FOR THE MASTER
BLASTER.
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTI', NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractor shcJ verify and be responsible for all dimensons. DO
NOT scc Ie The drawing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and cila rings are the property of
Stardec, Reproduction Or use for any purpose Other than nkat
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
ISSUED FOR ADDENDUM
Issued
Fie Name:
by Appd. rf.MM.DO
JFG SAS 17.06.08
by
Appd. Y't.MMDD
Own. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
MECHANICAL HVAC
HOODS 3,4,5, & 6/7 EXHAUST
CONTROLS DIAGRAM
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
M703
of 0
f
GENERAL NOTES
PROVIDE ONE (1) ANSUL R102 KITCHEN FIRE SUPPRESSION SYSTEM FOR EF -3 AND HOODS 1, 2, 3, AND 6/7. SYSTEM TO MEET
ANSUL S DESIGN, INSTALLATION, RECHARGE, AND MAINTENANCE MANUAL.
PROVIDE ONE (1) ANSUL R102 KITCHEN FIRE SUPPRESSION SYSTEM FOR EF -4 AND HOOD 8. SYSTEM TO MEET ANSUL'S DESIGN,
INSTALLATION, RECHARGE, AND MAINTENANCE MANUAL.
SYSTEM TO BE EQUIPPED WITH ELECTRIC RELEASE ASSEMBLIES, ELECTRICAL RELEASING PANEL, ELECTRIC DETECTION, ELECTRIC
REMOTE MANUAL PULL STATIONS, ELECTRICAL GAS VALVES, CONTRACTOR RELAYS/SHUNT TRIPS, REMOTE ANNUNCIATOR PANELS AND
FIRE ALARM INTERCONNECTIONS.
ANSUL OVERLAPPING NOZZLE COVERAGE AND 300% NOZZLE PROTECTION.
THIS DRAWING I5 PROVIDED FOR CONCEPTUAL PURPOSES ONLY. IT I5 INTENDED FOR GENERAL SCOPE OF OF THE ANSUL SYSTEM.
AN ENGINEERED DESIGN INCLUDING HYDRAULIC CALCULATIONS, ROUTING, AND SIZING SHALL BE COMPLETED BY THE INSTALLING
CONTRACTOR FOR THE EXACT SYSTEM CONFIGURATION. DRAWING INDICATES APPROXIMATE SIZING AND LOCATIONS OF ANSUL SYSTEM
FOR BIDDING PURPOSES. THE CONTRACTOR IS TO PROVIDE A FULLY ENGINEERED SYSTEM TO MEET STANDARD UL300, NFPA 17A,
NFPA 96, AND THE FIRE CODE OF NYS 2015.
FIRE SUPPRESSION CONTRACTOR SHALL SUBMIT SPECIFIC MANUFACTURERS' INFORMATION INCLUDING IDENTIFICATION NUMBERS,
WORKING DRAWINGS, CALCULATIONS, AND MATERIAL SPECIFICATIONS FOR THE FIRE SUPPRESSION SYSTEM TO ENGINEER PRIOR TO
PURCHASE AND/OR FABRICATION OF MATERIALS. REFER TO SPECIFICATIONS FOR FURTHER SUBMITTAL REQUIREMENTS.
THE MANUFACTURER AND MODEL OF ALL FIRE PROTECTION EQUIPMENT SHALL BE UL LISTED.
PLANS DO NOT INDICATE ALL MECHANICAL/ELECTRICAL CEILING ITEMS. COORDINATE THE INSTALLATION OF ALL PIPING, TANKS, AND
HEAD LOCATIONS WITH THE HVAC DUCTWORK PIPING, LIGHTS, SPEAKERS, STRUCTURAL STEEL, ETC. PROVIDE ADDITIONAL NOZZLES
AS REQUIRED TO PROVIDE FULL COVERAGE.
9. SUBMIT A MATERIAL AND TEST CERTIFICATE UPON COMPLETION OF SYSTEM,
10. FIRE SUPPRESSION CONTRACTOR SHALL PERFORM SHUTDOWNS, FIRE WATCH, AND SHALL COORDINATE WITH THE SITE SECURITY,
MAINTENANCE, AND HSE DEPARTMENT.
FOURTH FLOOR
0
0
RIJOF
SIXTH FLOUR
FIFTH FLOUR
ROOM 600UB
ANSUL R102
9 GALLON
CTRIC
f EF -3
- 10
2w
13,400 CFM
1 I 1
ANSUL R102
6 GALLON
ELECTRIC AUTOMAN
L-2 L-2
WINDOW
LOUVERS
IIMIMMEIMM
mt404011110
www*
t
IIMIMMEIMM
AMMO
.0044010,
mommom
L-1 L--1
WINDOW
LG1.IVERS
THIRD FLOOR
1,000 CFM
3,600 CFM
---------------------L--------------------
HOOD S
MAIN KITCHEN SOUTH HOOD
WALL MOUNTED CANOPY
(MEDIUM DUTY EQUIPMENT)
20+GAL.,D_ON STEAM k ETTL. S
1000
CFM
ROOM 309
1
� I
ANSUL R102
6 GALLON
ELECTRIC AUTOk
2W
9 ♦
LIN FOQO 3 1N4]
HEST HOOD AD J. TO ) ENSI-1IEi.:
WALL. MOUNTED CANOPY
4' CHAD BROILER TO
POTENTIALLY IALLY DL REPLACED
WITH WOK IN TT -IE FUTURE
245 245
(HEAVY DDS EQUIPMENT)
acu ti U''t 0- »J
CHAD
BROILER*
MOOD 4
I MAIN KITCHEN SOLS HOOD
WALL MOUTED CANOPY
COMBINATION
CONVECTION
STEER
1
(MEDIUM DUTY EQUIPMENT)
. 0 +GALLON STEAM KETTLES
FLAT TOP
GRIDDLE
ANSUL 8102
1461
6 GALLON
ELECTRIC AUTO
4
2W
? t t ? t it
1 N IGCD E 1 Nii1 N HOOD 2 1 N
2W
ANSUL 8102
B GALLON
ELECTRIC AUTO
MAIN KB-CHEN BAKING HOOD MAIN ICI -CHEN NORTH H000
WALL MOUNTED CANOPY WALL MOUNTED CANOPY
C5rre9—VriP
'
Fre
245 " 245 245 245
(LIGHT DUTY' EQUIPMENT)
OVENS
OVENS
OVENS
(HEAVY DUTY EQUIPMENT)
....-....._. 7.1
OEL.R
I
FRYER
RANGE &
BROILERS
DEEP
FRYER
ROOM 307
2W
2W
1
ANSUL R102
6 GALLON
ELECTRIC AUTOMAN
1N
Ii000 6
IVY SETNERY REAR HOOD
WALL MOUNTED CANOPY
1N
i 4' 4
9 HUMIDIFIED
ip HOLDING (MEDIUM DUTY
245 CAB NEI C ASTER EQUIPMENT)
EJEE
DEEP FRYER
! FLAT TOP
II GRIDDLE
L
1 FLAT TOP
GRIDDLE
t4f
ANSUL R102
6 GALLON
ELECTRIC AUTOMAN
ROOM 305
ANSUL R102
6 GALLON
ELECTRIC AUTOMAN
ANSUL 8142
9 GALLON
CTRIC AUTOMAN
HOOD 8
OKENSHIE:LDS WOE( HOOD
WALL MOUNTED CANOPY
Q V
1
EFET
DEEP
FRYER
WOK
WOK
Ho -
HEATED HOLDING
CABINET/OVEN
+11
SOUTH
BUILDING
AREAWAY
4,400 CFM
EF -4
EXISTING
WEATHER
HOOD
ORIGINAL SHEET -ARCH a
Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTI, NY 13760
Tel. (607)1-6100
www.stantec.com
Copyright Reserved
The Contractorshar verify and be responsible for all dimensons. DO
NOT scale The drawing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and cila rings are the property of
Stantec, Reproduction Or use for any purpose Other than nkat
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
ISSUED FOR ADDENDUM
Issued
Fie Name:
by Appd. T(. MM.DO
J FG SAS 17.06.08
by
Appd. Y't.MMDD
Own. Chkd. Dsgn. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
FIRE PROTECTION
DIAGRAM
Project No.
191001394
Scale
AS NOTED
Dawing Na. Sheet
Revision
FP600 of 0
ELECTRICAL SYMBOL SCHEDULE 1
SYMBOL
ELECTRICAL SYMBOL SCHEDULE ,
SYMBOL
REMARKS
DESCRIP'T'ION
REMARKS
SAT—
GENERAL
STANDARD OUTLET FACE PLATE
WITH TWO UNIVERSAL CATS JACKS
SEE SPEC
V
EXISTING TO BE REMOVED
DOWN CONDUCTOR
7#
FACE PLATE WITH CATS JACKS
PER # INDICATED C- INDICATES COAX INCLUDED
LIGHTING
W
V
{
`--' H-#
HID LIGHT FIXTURE
EXISTING
SINGLE CAT6 CABLE AND JACK ABOVE CEILING
WIRELESS ACCESS POINT
ACCESS CONTROL 1 SURVEILLANCE 1 SECURITY
L#
.........
# INDICATE$ TYPE, REFER TO FIXTURE SCHEDULE
Ei
NEW
DOOR STATUS MONITOR
L -#E
POWER
# INDICATES TYPE, REFER TO FIXTURE SCHEDULE
DOOR CONTACT
PANELBOARD
SEE SPEC
INCANDESCENT LIGHT FIXTURE
# INDICATES TYPE, REFER TO FIXTURE SCHEDULE
REQUEST FOR EXIT MOTION DETECTOR
REX
EXIT SIGN
# INDICATES TYPE, REFER TO FIXTURE SCHEDULE
TRANSFORMER
SEE ONE -LINE DIAGRAM
T
SINGLE POLE SWITCH
EP
3
DISCONNECT SWITCH
ACCESS CONTROL JUNCTION BOX
MOUNTED CONCEALED WITHIN 25
LINEAR FEET OF CARD READER
D
SINGLE POLE SWITCH WITH PILOT LIGHT
FUSED DISCONNECT SWITCH
POWER TRANSFER DEVICE
NNETWORK
SOC
OCCUPANCY SENSOR SWITCH
MOUNT TO CEILING
RELAY
DDAYLIGHTING
4OC
R
MI
$ N
NETWORK LIGHTING SWITCH
VARIABLE FREQUENCY DRIVE
PP
$ NVC
VFD
POWER SUPPLY
Gig
N
D
NETWORK LIGHTING DIMMING WALL
SWITCH
a
WP = WEATHER TIGHT
MAGNETIC STARTER
ellTAMPER
EMERGENCY SHUNT RELAY
MANUAL MOTOR STARTER PUSH
BUTTON OPERATED
MOTION DETECTOR
�J
L�'�
SS
MANUAL MOTOR STARTER
TOGGLE OPERATED
NETWORK LIGHTING RELAY
•
[M
❑PB
POWER OUTLET CONNECTION
REFER TO POWER OUTLET SCHEDULE
FIRE ALARM
0
JUNCTION/WALL BOX
FIRE ALARM CONTROL PANEL
TRANSPONDER PANEL
•
PP
POWER POLE
a
FIRE ALARM
REMOTE ANNUNCIATOR PANEL
SPECIAL PURPOSE RECEPTACLE
FM
QUADRAPLEX RECEPTACLE
FIRE ALARM PULL STATION
F
DUPLEX RECEPTACLE
0
AREA SMOKE DETECTOR
CI
DUCT SMOKE DETECTOR
GROUND FAULT INT. RECEPTACLE
A ►bT
GFCI
PROVIDE REMOTE TEST/STATUS SWITCH
C,FCI
H0
WEATHERPROOF RECEPTACLE
TAYMAC (IN USE) WEATHER COVER
-111-'WP
CO
r-,.--1
CEILING/FLOOR MOUNTED
DUPLEX RECEPTACLE
L__]
FIRE ALARM
INDIVIDUAL ADDRESSABLE MODULE
IAM
THERMOSTAT VOLTAGE SUPPRESSER
P
MAGNETIC DOOR HOLDER
gDDC
0
TAMPER SWITCH
DROP CORD
Q
SOLENOID VALVE
WIRE THRU IAM
EXPLOSION PROOF
0
FS
FLOW SWITCH
EX
AFIRE
RACEWAY
ALARM STROBE
15/75, XENON
FIRE ALARM AUDIOIVISUAL STROBE
15/75, XENON
RACEWAY DOWN
I rJ
—3
SMOKE HATCH
RACEWAY UP
SH
BUS DUCT
ARM-
I
i
HOMERUN
CONTROL RELAY MODULE
CRM
GROUNDING CONDUCTOR
,
—G—
J
FD
ELECTRICAL SYMBOL SCHEDULE 1
SYMBOL
SYMBOL
DESCRIPTION
REMARKS
LIGHTNING PROTECTION
SAT—
AIR TERMINAL
STANDARD OUTLET FACE PLATE
WITH TWO UNIVERSAL CATS JACKS
SEE SPEC
V
—*DC—
DOWN CONDUCTOR
7#
FACE PLATE WITH CATS JACKS
PER # INDICATED C- INDICATES COAX INCLUDED
LIGHTING
W
V
{
`--' H-#
HID LIGHT FIXTURE
# INDICATES TYPE, REFER TO FIXTURE SCHEDULE
SINGLE CAT6 CABLE AND JACK ABOVE CEILING
WIRELESS ACCESS POINT
ACCESS CONTROL 1 SURVEILLANCE 1 SECURITY
L#
LED LIGHT FIXTURE
# INDICATE$ TYPE, REFER TO FIXTURE SCHEDULE
Ei
DOOR STATUS MONITOR
L -#E
EMERGENCY LED LIGHT FIXTURE
# INDICATES TYPE, REFER TO FIXTURE SCHEDULE
DOOR CONTACT
SECURITY SYSTEM
C
INCANDESCENT LIGHT FIXTURE
# INDICATES TYPE, REFER TO FIXTURE SCHEDULE
REQUEST FOR EXIT MOTION DETECTOR
REX
EXIT SIGN
# INDICATES TYPE, REFER TO FIXTURE SCHEDULE
DAS
$
SINGLE POLE SWITCH
DS
3
THREE WAY SWITCH
ACCESS CONTROL JUNCTION BOX
MOUNTED CONCEALED WITHIN 25
LINEAR FEET OF CARD READER
$ P
SINGLE POLE SWITCH WITH PILOT LIGHT
POWER TRANSFER DEVICE
NNETWORK
SOC
OCCUPANCY SENSOR SWITCH
MOUNT TO CEILING
DDAYLIGHTING
4OC
SENSOR SWITCH
MOUNT TO CEILING
MI
$ N
NETWORK LIGHTING SWITCH
PP
$ NVC
NETWORK LIGHTING VACANCY SENSOR
POWER SUPPLY
Gig
N
D
NETWORK LIGHTING DIMMING WALL
SWITCH
CAMERA C = MOUNT TO CEILING
W = MOUNT TO WALL
WP = WEATHER TIGHT
Milli
ellTAMPER
EMERGENCY SHUNT RELAY
MOTION DETECTOR
0
PUSH BUTTON STATION
NETWORK LIGHTING RELAY
•
❑PB
RN
FIRE ALARM
FIRE ALARM CONTROL PANEL
TRANSPONDER PANEL
FACP
FIRE ALARM
REMOTE ANNUNCIATOR PANEL
FM
FIRE ALARM PULL STATION
F
0
AREA SMOKE DETECTOR
CI
DUCT SMOKE DETECTOR
PROVIDE REMOTE TEST/STATUS SWITCH
A ►bT
DUCT SMOKE DETECTOR (ALTERNATE)
PROVIDE REMOTE TEST/STATUS SWITCH
H0
FIRE ALARM THERMAL DETECTOR
### INDICATES TEMPERATURE RATING
CO
FIRE ALARM CO DETECTOR
FIRE ALARM
INDIVIDUAL ADDRESSABLE MODULE
IAM
P
MAGNETIC DOOR HOLDER
0
TAMPER SWITCH
Q
SOLENOID VALVE
WIRE THRU IAM
0
FS
FLOW SWITCH
MARE THRU IAM
AFIRE
ALARM STROBE
15/75, XENON
FIRE ALARM AUDIOIVISUAL STROBE
15/75, XENON
I rJ
SMOKE HATCH
SH
ARM-
ADDRESSABLE RELAY MODULE
CONTROL RELAY MODULE
CRM
FIRE/SMOKE DAMPER RELEASE
J
FD
ELECTRICAL SYMBOL SCHEDULE
SYMBOL
DESCRIPTION
REMARKS
TELE/DATA
CABLE TRAY
STANDARD OUTLET FACE PLATE
WITH TWO UNIVERSAL CATS JACKS
SEE SPEC
V
STANDARD OUTLET FACE PLATE
WITH THREE UNIVERSAL CAT$ JACKS
SEE SPEC
7#
FACE PLATE WITH CATS JACKS
PER # INDICATED C- INDICATES COAX INCLUDED
SEE SPEC
W
V
WALL JACK SINGLE GANG
FACE PLATE VIFITH MOUNTING LUGS
ONE CAT6 JACK
SEE SPEC
NI
SINGLE CAT6 CABLE AND JACK ABOVE CEILING
WIRELESS ACCESS POINT
ACCESS CONTROL 1 SURVEILLANCE 1 SECURITY
CARD READER
Ei
DOOR STATUS MONITOR
ACCESS CONTROL
DSM
DOOR CONTACT
SECURITY SYSTEM
EN
REQUEST FOR EXIT MOTION DETECTOR
REX
DOOR AJAR SOUNDER
DAS
ELECTRIC STRIKE OA LATCH MONITOR MATCH
DS
ACCESS CONTROL JUNCTION BOX
MOUNTED CONCEALED WITHIN 25
LINEAR FEET OF CARD READER
ACJ
POWER TRANSFER DEVICE
PT
DOOR OPERATOR
MI
PUSH PLATE
PP
POWER SUPPLY
Gig
CAMERA C = MOUNT TO CEILING
W = MOUNT TO WALL
WP = WEATHER TIGHT
Milli
ellTAMPER
WIRE DEVICE
MOTION DETECTOR
PUSH BUTTON STATION
•
❑PB
PANIC BUTTON STATION
ABBREVIATIONS
A -AMPERE
AFC -ABOVE FINISHED CEILING
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GROUND
AHU - AIR HANDLING UNIT
AIC - AMPS INTERRUPTING CAPACITY
AFI - ARC FLASH CIRCUIT INTERRUPTER
AIV - AUDIONISUAL
BLDG - BUILDING
C - CONDI.)IT
CKT - CIRCUIT
CL - CENTERLINE
DWG - DRAWING
DVR - DIGITAL VIDEO RECORDER
EC - ELECTRICAL CONTRACTOR
EF - EXHAUST FAN
EM -EMERGENCY
G -GROUND
GC - GENERAL CONTRACTOR
GFI - GROUND FAULT CIRCUIT INTERRUPTER
HP - HORSEPOWER
IP - INTERNET PROTOCOL
LAN - LOCAL AREA NETWORK
RMC - RIGID METALLIC CONDUIT
RNC - RIGID NON-METALLIC CONDUIT
EMT - ELECTRIC NON-METALIC TUBING
LTFC - LIQUID TIGHT FLEXIBLE CONDUIT
JB - JUNCTION BOX
KVA - KILOVOLT AMPERES
KW - KILOWATT
MC - MECHANICAL CONTRACTOR
MCB - MAIN CIRCUIT BREAKER
MDP - MAIN DISTRIBUTION PANEL
MLO - MAIN LUG ONLY
NIC - NOT IN CONTRACT
P - POLE
PC -PLUMBING CONTRACTOR
PH,0 - PHASE
PVC - POLYVINYL CHLORIDE
RM -ROOM
✓ - VOLT
W - WIRE
WP - WEATHER PROOF
XFMR - TRANSFORMER
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTI', NY 13760
Tel. (607)1-6100
www.stantec.com
Copyright Reserved
The Contractor slid verify and be responsible for all dimensions. DO
NOT scole the drawing - ctly errors or omisslon% shall be reported to
Stantec without delay.
The Copyrights to all designs and ora the property of
Stordeo, Reproduction or use for ony purpose other Mon that
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fle Natne..
Permit -Seal
by Appd. rf.MM.DO
MN( JAI, 17.05.05
by Appd. rt.MM.DO
Own. Chkd. Dsgn. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
ELECTRICAL
LEAD SHEET
Project No. Scale
191001394 AS NOTED
Drawing No. Sheet Revision
E000
of 1'-'1
DEMOLITION KEYED NOTES:
0 DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES, CEILJNC FANS, FIRE ALARM DEVICES,
SPEAKERS, ETC. IN SHADED AND CROSS -HATCHED AREAS TO ALLOW FOR CEILING REMOVAL
SAVE ALL UGHT FIXTURES, FIRE ALARM DEVICES AND ALL CEILING MOUNTED ELECTRICAL DEVICES
FOR REINSTALLATION. TAG CONDUCTORS AND CABUNG FOR REUSE.
0 DISCONNECT POWER FEED TO EXISTING EXHAUST FAN (EF) TO ALLOW FOR REMOVAL REMOVE
ASSOCIATED CONDUIT AND CONDUCTORS COMPLETE BACK TO SOURCE.
DISCONNECT POWER FEED TO EXISTING SERVICE HOODS TO ALLOW FOR REMOVAL TAG
CONDUCTORS AND CABUNG FOR REUSE. EXISTING FEED TO BE REUSED FOR RECONNECTION TO
NEW HOOD. REFER TO DWG E101 FOR ADDITIONAL INFORMATION.
GENERAL NOTES / DEMOLITION
1. THIS DEMOLITION DRAWING IS IN PART DIAGRAMMATIC AND THE CONTRACTOR SHALL VISIT EACH
LOCATION TO DETERMINE THE ACTUAL DEMOLITION SCOPE
2. FIELD VERIFY EXISTING CIRCUITS BEFORE COMMENCING REMOVALS. PROVIDE COPY OF
PANELBOARD SCHEDULES TO ENGINEER PRIOR TO START OF NEW ELECTRICAL WORK.
3. REFER TO ARCHITECTURAL AND MECHANICAL DRAWINGS FOR ADDMONAL DEMOLITION INFORMATION
AND COORDINATION ISSUES.
4. EXISTING EQUIPMENT EFFECTED BY REMOVALS AND INTENDED TO REMAIN SHALL BE RECONNECTED
AND TESTED TO ENSURE PROPER OPERATION.
5. RETURN ALL UNUSED DISCONNECTS AND MOTOR STARTERS TO OWNER.
J
111
El
L-
r-
r -
El
0
LJ
EXISTING
WEATHER
HOOD
1254
El
1-4
O4
L. J
CID
661INTER
EXISTING
PANEL
LP -3F1
EXISTING
PANEL
LP -3F
1111111111111
2440
15
147
3P1A
4x8 WIREWAY
THIRD FLOOR PLAN
,ED101 SCALE: 1/$ =1 —4
N
-
1
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE $URE 201
ENDICOTT, NY 13760
Tel. (607)1-6100
www.stantec.com
Copyright Reserved
The Contractor slid verify and be responsible for all dimensions. DO
NOT scole the dra Ing - ctly errors or omissron% shall be reported to
Stantec without delay.
The Copyrights to all designs and ora the property of
Stordec, Reproduction or use for ony purpose other Mon that
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Nene:
Permit -Seal
by Appd. rf.MM.DO
MN( JAI, 17.05.05
by
Appd. Y't.MM.DO
Own. Chkd. Dsgn. YY.I M.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
ELECTRICAL DEMOLITION
THIRD FLOOR PLAN
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
ED1O1
of 1'-'1
6
L1.
6
DEMOLITION KEYED NOTES:
CI DISCONNECT POWER FEED TO EXISTING FAN MOTOR TO ALLOW FOR REMOVAL REMOVE
ASSOCIATED DISCONNECT SWITCH. SAVE POWER FEED CIRCUIT FOR REUSE. REFER TO DWG E1 D2
FOR ADDITIONAL INFORMATION.
CI DISCONNECT POWER FEED TO IEKIST1NG INLINE FAN TO ALLOW FOR REMOVAL REMOVE
ASSOCIATED CONDUIT AND CONDUCTORS COMPLETE BACK TO SOURCE. DISCONNECT AND REMOVE
ASSOCIATED MANUAL MOTOR STARTER.
J
0
111
SIXTH FL}OOIR! PLAN
p_E 1 O SCALE: 1 1"4* _ 1 —O
0
14 -
ORIGINAL
ORIGNAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTT, NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractor shcJ verify and be responsible for all dimensons. DO
NOT scole the drawing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and cila rings are the property of
Stardec, Reproduction Or use for any purpose Other than nkat
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
Permit -Seal
by Appd. rf.MM.DO
MN( JAI, 17.05.05
by
Appd. Y't.MM.DO
Own. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
ELECTRICAL DEMOLITION
FOURTH, FIFTH & SIXTH FLOOR
PLANS
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
ED 102
of 1'-'1
KEYED NOTES
PROVIDE 1 — 225A 3POLE CIRCUIT BREAKER IN EXISTING PANELBC ARD DP -2,
PROVIDE 4-4/0 & 1-14G IN 2-1/2' EMT FROM PANELBO1ARD DP -2 TO NEW
PANELBOARD (P2N-1) IN KITCHEN ON THIRD FLOOR. REFER TO DWG E101.
INTERRUPTING RATING TO MATCH EXISTING.
176
I:7�
ill
15,0
-N
917
2-S
LJ
200TG
"1"1"1"-
105
111117
114f) Elm
1
2-14A
,z
1
1
EXISTING
PANEL
LP2D
EXISTING
PANEL
PP5
(T\SEC O N.D `F•LOO R ....PLAN
E100 SCALE: 1/8"= 1 -O
1,m
E
112,2,
War
£ACP EM1 DP1 DP2
FACP
IT
2000A
205V/120V
30,4W
MDP MCB
L
ORIGINAL SHEET -ARCH a
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICO T, NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractor shcJ verify and be responsible for all dimensons. DO
NOT scole the drawing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and cila rings are the property of
Stardec, Reproduction Or use for any purpose Other than nkat
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
Permit -Seal
by Appd. T(.MM.DO
MN( JAP 17.05.05
by
Appd. Y't.MM.DO
Dwn. Chkd. Dsgn. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
ELECTRICAL
SECOND FLOOR PLAN
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
E100 of
KEYED NOTES
0
0
0
0
PROVIDE POWER FEED TO MECHANICAL EQUIPMENT AND EXHAUST HOODS. REFER
TO POWER OUTLET SCHEDULE ON DWG E600.
REINSTALL LIGHT FIXTURES, CEILING FANS, FIRE ALARM DEVICES AND ELECTRICAL
DEVICES IN SHADED AREA SAVED FROII REMOVAL RECONNECT AS EXISTING.
PROVIDE 225A, 208-120V. 3PHASE, 4WIRE 42 SPACE PANELBOARD (P2N-1) 1N
LOCATION INDICATED. PROVIDE 4-4/0 & 1- f 4G IN 2-i/2" EMT FROM
PANELBOARD DP -2 ON SECOND FLOOR TO PANELBOARD. REFER TO DWG E100
FOR PANELBOARD DP -2 LOCATION. REFER TO PANEL SCHEDULE ON DWG E600
FOR BRANCH CIRCUIT REQUIREMENTS.
RECONNECT SERVICE HOOD POWER FEED SAVED FROM DEMOLRION TO NEW
SERVICE HOODS IN LOCATIONS INDICATED. REFER TO DWG ED1O1 FOR ADDITIONAL
INFORMATION.
L-
r-
r -
J
i
5.
')006
4
t
2,4
ISM;
EXISTING
71EMINNEF 1100F 'r,,-,,-"Arr 1117=71r 11
PANEL
LP -3F1
EXISTING
PANEL
LP -3F
"005N
2.40.
I5
147
4x8 WIREWAY
THIRD FLOOR PLAN
El Ol SCALE: t/8"1=1'-0"
N
1
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTr, NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractor shcJ verify and be responsible for all dimensons. DO
NOT scole the drawing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and cila rings are the property of
Stardeo, Reproduction Or use for any purpose Other than nkat
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
Permit -Seal
by Appd. 'fY.MM.DO
MWK JAP 17.05.05
by
Appd. ri.P ix o
Own. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
ELECTRICAL
THIRD FLOOR PLAN
Project No.
191001394
Scale
AS NOTED
Drawing No. Sheet Revision
E101
of 1'-'1
L1.
INSTALLATION KEYED NOTES
0
RECONNECT FAN MOTOR POWER FEED SAVED FROM DEMOLITION TO NEW FAN MOTOR IN
LOCATION INDICATED. REFER TO DWG ED102 AND E600 FOR ADDITIONAL INFORMATION. PRO' IDE
NEMA 3R 100A DISCONNECT WITH AUXILIARY INTERLOCK KIT (TO SHUT DOWN VFD) FOR EF -3.
EXISTING
58"x28"
OVAL DUCT
RISER IN
CHASE
mexenwenwenweref
11Elp
58"x28" OVAL
TO 38"0 ELBOW
NEW INLINE
EXHAUST FAN
EF -3
ilkAtto.„
r
.4,74
EFttitikiA
FD
Mir
PROVI[
OFF [3
OF DL
ROUTE
DRAIN.
DRAIN
CLEAR
INSTAL
DRAIN
NEW DISCHARGE
DUCT STACK
INSTALLED TO
1'-0°' BELOW
TOP OF
EXISTING CHASE
E102 SCALE: 1/4
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTI, NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractorshar verify and be responsible for all dimensons. DO
NOT scole the drawing - any errors or omission% shall be reported to
Stantec without delay.
The Copyrights to all designs and cila rings ora the property of
Stardec, Reproduction Or use for any purpose Other than nkat
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name:
Permit -Seal
by Appd. rf.MM.DO
MWK JAP 17.05.05
by Appd. Y't.P i.DD
Own. Chkd. DsgrS. YY.MM.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
ELECTRICAL
FOURTH, FIFTH & SIXTH FLOOR
PLANS
Project No. Scale
191001394 AS NOTED
Drawing No. Sheet Revision
E102
of 1'-'1
E
POWER OUTLET SCHEDULE
SERVICE
TAG*
LOCATION
DESCRIPTION
VOLTAGE/P
RASE
LOAD
FEED
CKT BKR
FUSE
CONDUIT &
WIRE
CONTROLLER
TYPE
CONTROLLER
STARTER SIZE
CONTROLLER
ACCESSORIES
DISCONNECT
REMARKS
EXHAUST FAN
EF -1
3RD FLR
208/3
° 1 112 HP
P2N-1
2013
312&112G IN
314" EMT
VFD
1 1/2 HP
A, B, C
INTEGRAL NEMA 1
30A FUS/DISC
PROVIDE POWER CONNECTION TO FAN MOTOR FROM VFD
EXHAUST FAN
EF -2
3RD FLR
20813
3/4 HP
P2N-1
2013
3412&1-#12G IN
314" EMT
VFD
3/4 HP
A, B, C
INTEGRAL NEMA 1
30A FUSIDISC
PROVIDE POWER CONNECTION TO FAN MOTOR FROM VFD
EXHAUST FAN
EF -3
6TH FLR
208/3
20 HP
EXISTING
EXISTING
EXISTING
VFD
20 HP
A, B, C
INTEGRAL NEMA 1
100A FUSIDISC
RECONNECT TO EXISTING FAN CIRCUIT. PROVIDE POWER
CONNECTION TO FAN MOTOR FROM VFD
EXHAUST FAN
EF -4
3RD FLR
208/3
7 1/2 HP
P2N-1
50/3
3 881 1pG IN
314 EMT
VFD
7112 HP
A, B, C
INTEGRAL NEMA
60A FUSIDISC
PROVIDEPOWER CONNECTION TO FAN MOTOR FROM VFD
HOOD
HOOD 6/7
3TH FLR
12011
2A
P2N-1
20/1
2-128112G IN
314" EMT
NA
NA
NA
NA
PROVIDE POWER CONNECTION TO UNIT
-----
11
----
C
----
------
12
-----
CONTROLLER TYPES:
FVNRCSD - FULL VOLTAGE NON -REVERSING COMBINATION STARTER/DISCONNECT
NOTES:
FVNR - FULL VOLTAGE NON -REVERSING STARTER
MMS - MANUAL MOTOR STARTER
PR - POWER RELAY
VFD - VARIABLE FREQUENCY DRIVE
ACCESSORIES:
A - 480-24VAC CONTROL XFMR, 24VAC COIL
B - RED -RUNNING PILOT LIGHT, GREEN -OFF PILOT LIGHT
C - HAND -OFF -AUTO SELECTOR SWITCH
D - 480-120VAC CONTROL XFMR
E - INTERLOCK CONTACT TO SHUT -DOWN CONTROL CIRCUIT WHEN DISCONNECT SWITCH IS OPEN
F - RS -485 COMMUNICATION MODULE
2011
DISCONNECT:
DISC - DISCONNECT SWITCH SIZE AS INDICATED
FUSIDISC - FUSIBLE DISCONNECT SWITCH SIZE AS INDICATED
MMS - MANUAL MOTOR STARTER
INT/DISC - FUSED DISCONNECT SWITCH INTEGRAL WITH CONTROLLER
17
POWER PANEL SCHEDULE
DESIGNATION; P2N-1
STYLE: NO
LOCATION: KITCHEN
SERVICE: 208/120V 3PH 4W
FRAME: 225A
MOUNTING: SURFACE
MAIN BREAKER: MLO
FEED: DP -2
CKT NO
DESIGNATION
LOAD
WATTS
BKR. TRIP 1
POLES
PHASE
BKR. TRIP !
POLES
LOAD
WATTS
DESIGNATION
CKT
NO
1
SPARE
50/3
A
50/3
SPARE
2
3
---
B
4
------
------
5
---
C
6
-----
-----
7
EF -4
50/3
A
20/3
EF -2
8
9
---
B
----
10
-----
11
----
C
----
------
12
-----
13
EF -1
20/3
A
2011
HOOD 617
14
15
----
B
2011
SPARE
16
-----
17
---
C
2011
SPARE
18
-----
19
SPARE
20/1
A
2011
SPARE
20
21
SPARE
20/1
B
20/1
SPARE
22
23
SPARE
20/1
C
2011
SPARE
24
25
SPARE
20/1
A
20/1
SPARE
26
27
B
26
29
C
30
31
A
32
33
B
34
35
C
36
37
A
38
39
B
40
41
C
42
ADDITIONAL INFO: MATCH INTERRUPTING RATING OF DP -2
ORIGINAL SHEET -ARCH I
tC! Stantec
Stantec
111 GRANT AVENUE SURE 201
ENDICOTr, NY 13760
Tel. (607)1-6100
www.stontec.com
Copyright Reserved
The Contractor shcJ verify and be responsible for all dimensons. DO
NOT scole the drawing - Ony errors Or omiss1on% shall be reported to
Stantec without delay.
The Copyrights to all designs and cila rings are the property of
StOrdeC, Reprodl.+Cticn Or use for any pupa* Other than MCI
authorized by Stantec is forbidden.
Consultants
Legend
Notes
Revision
D ISSUED FOR BID
Issued
Fie Name.
Permit -Seal
By Appd. rf.MM.DO
MWK JAP 17.05.05
By Appd. Y't.MM.DO
Own. Chkd. DsgrS. YY.I M.DO
Client/Project
CORNELL UNIVERSITY
IILLARD STRAIGHT HALL
EF -1 AND EF -2 DINING EXHAUST
SYSTEM IMPROVEMENTS PROJECT
ITHACA, NY 14635
Title
ELECTRICAL
SCHEDULES
Project No. Scale
191001394 AS NOTED
Drawing No. Sheet Revision
E600
of 1'-'1