HomeMy WebLinkAboutComputing and Communications Center Specifications101ROOM NAMEA1011SIM1'-0"B1W1F1101ROOM NAMEW1DETAIL SECTIONINTERIOR ELEVATIONDOOR & INTERIORWINDOW TAGWALL TAGROOM IDENTIFICATIONROOM FINISH KEYCONTRACT LIMIT LINEEXISTING DOORNEW DOORPARTITIONS, DOORS ANDITEMS TO BE REMOVEDFULL HEIGHT PARTITIONPARTIAL HEIGHT PARTITIONNOTE KEY100100REVISION CLOUD & TAGPLAN ELEVATION50'-6"CEILING HEIGHTEQUIPMENT TAGA101SIMA1A2A3A411iSCOPE LINEDIMENSION TO THE FACEOF FRAMING AT NEWCONSTRUCTION, TYP.DIMENSION TO THE FACEOF FINISH AT EXISTINGCONSTRUCTIONDIMENSION TO THE FACEOF FINISH1EXISTING PARTITION 3/32" = 1'-0"01/29/191714G001CCC - Room 330 D Renovation235 Garden AvenueCORNELL UNIVERSITYCOVER SHEETELECTRICAL DEMOLITIONED103 THIRD FLOOR DEMOLITIONPLAN - ELECTRICALELECTRICALE001 DRAWING INDEX, NOTES &SYMBOL LISTE103 THIRD FLOOR PLAN -ELECTRICALMECHANICAL DEMOLITIONMD103 THIRD FLOOR DEMOLITIONPLAN - HVACMECHANICALM001 DRAWING INDEX &SYMBOL LISTM103 THIRD FLOOR PLAN -HVACM501 DETAILSM601 HVAC SCHEDULESM701 CONTROLS SCHEMATICSM702 CONTROLS POINTSFIRE PROTECTION DEMOLITIONFD103 THIRD FLOOR DEMOLITIONPLAN - FIRE PROTECTIONFIRE PROTECTIONF103 THIRD FLOOR PLAN - FIREPROTECTIONGENERALG001 COVER SHEETARCHITECTURAL DEMOLITIONAD113 REFLECTED CEILINGDEMOLITION PLANARCHITECTURALA001 WALL TYPESA103 FLOOR PLANA153 REFLECTED CEILING PLANDATE:JOB NUMBER:29 JANUARY 20191714 - AS#5PROJECT INFORMATION:CONSTRUCTION CLASSIFICATION:SPRINKLER PROTECTION:BUILDING USE CLASSIFICATION:IIAFULLY SPRINKLEREDBUSINESSTOTAL EXISTING BUILDING AREA:AREA OF RENOVATION:AREA OF ADDITION:TOTAL AREA OF PROJECT:49,800 SF301 SF0 SF301 SF
330CORRIDOR330DSHAREDOFFICE 3D52D51D54D51D52D51D51D54D51D51D54D54 3/16" = 1'-0"01/29/191714AD113CCC - Room 330 D Renovation235 Garden AvenueCORNELL UNIVERSITYREFLECTED CEILING DEMOLITION PLAN 3/16" = 1'-0"1ROOM 330D REFLECTED CEILING DEMOLITION PLAND51 DEMOLISH CEILING GRID, PANELS, AND LIGHT FIXTURES TO LIMIT OF HATCHED AREA SHOWND52 DEMOLISH SOFFIT/DRYWALL CEILING AND LIGHT FIXTURES TO LIMIT OF HATCHED AREA SHOWND54 EXISTING TO REMAIN
5/8" GYPSUM BOARDFILL FRAMING CAVITY WITH SOUNDATTENUATION BLANKET U.O.N.- ALL WALLS TYPE A, UNLESS OTHERWISE NOTED- EXTEND TO UNDERSIDE OF STRUCTUREWALL BASE, SEE FINISHPLANSCEILING PLANE, SEEREFLECTED CEILING PLANSACOUSTIC SEALANT, BOTH SIDES, ENTIREPERIMETER WALLS, FLOORS, AND CEILINGS, TYP.UNDERSIDE OFSTRUCTUREWALL TYPE ADEFLECTION TRACKNOTE: USE CFMF AT ALLFRAMING 13'-0" OR TALLERMETAL FRAMING AT 16" O.C.ACOUSTIC SEALANT, BOTH SIDES, ENTIREPERIMETER WALLS, FLOORS, AND CEILINGS, TYP.5/8" 3 5/8" 5/8"4 7/8" 1 1/2" = 1'-0"01/29/191714A001CCC - Room 330 D Renovation235 Garden AvenueCORNELL UNIVERSITYWALL TYPES1. EXISTING PARTITION WIDTH VARIES; WHERE EXTENDING EXISTING PARTITIONS, ALIGN WITHFACE OF FINISH ON BOTH SIDES OF PARTITION (MATCH EXISTING PARTITION WIDTH).NOTES:
B1W1-330DSHAREDOFFICE 3330DAALIGNEXISTING BASE TOREMAIN; NEW BASEAT NEW WALL ONLY(BOTH ROOM ANDCORRIDOR SIDES).PAINT CORRIDOR-SIDEWALL TO MATCHEXISTING.330CORRIDORPROJECT LIMIT LINENOTES:1. SEE DEMOLITION PLANS FOR EXTENT OF EXISTING MATERIALS TO REMAIN / BE SALVAGED2. ALL GYPSUM BOARD CEILINGS IN THE WORK AREA TO BE PAINTED UNLESS OTHERWISE NOTED ON REFLECTED CEILING PLAN.3. ALL DOORS / FRAMES AND PAINTED WINDOW TRIM / FRAMES IN THE AREA OF WORK SHALL BE PAINTED UNLESS OTHERWISE NOTED.4. SEE REFLECTED CEILING PLAN FOR ADDITIONAL FINISH INFORMATION, TYPICAL.5. MISCELLANEOUS ELECTRICAL PANEL COVERS, GRILLES, ETC. TO BE PAINTED TO MATCH ADJACENT WALL SURFACES.DOOR TYPES:D23"6"6 1/2"2'-9"TGFRAME TYPES:F12"2"2"As indicated01/29/191714A103CCC - Room 330 D Renovation235 Garden AvenueCORNELL UNIVERSITYFLOOR PLAN 3/16" = 1'-0"1ROOM 330D FLOOR PLANDOOR AND FRAME SCHEDULEDOORNUMBERRoomNumberRoom NameFRAMEDoor TypeDOORHARDWAREGROUPELEV MATERIAL GLAZINGMATERIAL SIZE GLAZING330D 330D SHARED OFFICE 3 F1 HM-D2 WD 3'-0" X 7'-0" TG1
SDOS8' - 0"9' - 0"9' - 0"330DSHAREDOFFICE 3330CORRIDOR2A153PROJECT LIMIT LINERETURN AIR GRILLESUPPLY AIR GRILLEEXIT SIGNFIRE DETECTOROCCUPANCY SENSOROTHER:LINEAR PENDANTLIGHT FIXTURELINEAR SURFACE MOUNTEDLIGHT FIXTUREEXISTING LIGHT FIXTURESLIGHT FIXTURES:GYPSUM BOARD CEILINGACP-1 ACOUSTICALPANEL CEILINGCEILING MATERIALS:REFLECTED CEILING PLAN NOTES:1. SEE RCP DEMOLITION PLANS FOR EXTENT OFEXISTING CEILINGS TO REMAIN AND REQUIREDDEMOLITION.2. MOUNT ALL SPRINKLER HEADS, ELECTRICALDEVICES, LIGHT FIXTURES, ETC. CENTERED IN2'X2' ACOUSTIC CEILING PANELS, UNLESSOTHERWISE NOTED.3. CENTER ACOUSTIC CEILING PANELS WITHINFIELD AS INDICATED ON REFLECTED CEILINGPLANS, PROVIDING NUMBER OF PANELSSHOWN, UNLESS OTHERWISE NOTED.EXISTING SUPPLY AIR GRILLESPRINKLERMETAL FRAMING AS REQUIREDGYPSUM WALL BOARD ONMETAL FRAMINGCORNER BEAD, TYP.ACOUSTICAL CEILING PANELOR AS INDICATEDAS INDICATED, TYP.As indicated01/29/191714A153CCC - Room 330 D Renovation235 Garden AvenueCORNELL UNIVERSITYREFLECTED CEILING PLAN 3/16" = 1'-0"1ROOM 330D REFLECTED CEILING PLAN 3" = 1'-0"2ACOUSTICAL CEILING PANEL TO GYP. BOARD CEILNG TRANSITION
T
A
5
4
REMOVE EXISTING SPRINKLER HEAD.
(TYPICAL)SPR (E)SPR (E)PROJECT LIMIT LINE
SACK & ASSOCIATES
Consulting Engineers, PLLC
721 E. Genesee Street
Syracuse, NY 13210
Tel: 315−471−4013
Fax: 315−471−4044
DRAWN BY:
17067
AS NOTED
235 Garden Avenue 1714
CCC - Room 330 D Renovation
CORNELL UNIVERSITY
01/29/19
FD103
DDD
THIRD FLOOR DEMOLITION PLAN-FIRE PROTECTION
3"SCALE: 1/8" = 1'-0"FD103
1 ROOM 330D EXISTING FLOOR PLAN
0 4'8'16'
A
5
4
PROVIDE NEW SPRINKLER HEAD.
CONNECT TO EXISTING SPRINKLER
PIPING.(TYPICAL)
PROJECT LIMIT LINE
1.EXTEND EXISTING FIRE SPRINKLER SYSTEMS TO PROTECT ALL SPACES.
ALL LAYOUT INSTALLATION AND TESTING SHALL COMPLY WITH
NFPA 13-2013 EDITION AND PROJECT DESIGN DOCUMENTS.
2.PROVIDE COMPLETE FIRE PROTECTION SHOP DRAWINGS THAT ARE SIGNED AND SEALED
BY A NEW YORK STATE LICENSED FIRE PROTECTION ENGINEER OR MINIMUM NICET III
INSPECTION AND TESTING OF WATER BASED SYSTEMS CERTIFICATION AND SIGNATURE.
3.ALL FIRE PROTECTION EQUIPMENT SHALL BE UL LISTED AND FM APPROVED FOR INTENDED
APPLICATION. MINIMUM 175 PSI WWP.
4.PROVIDE ESCUTCHEONS TO CONCEAL PENETRATIONS THRU WALLS AND FLOORS.
5.FIRE PROTECTION PIPING SHALL BE BLACK STEEL WITH CAST IRON THREADED FITTINGS
OR GROOVED FITTINGS.
FIRE PROTECTION GENERAL NOTES
FIRE SUPPRESSION SYMBOLS
AND ABBREVIATIONS
SYMBOL DESCRIPTION
CONCEALED SPRINKLER HEAD
EXISTING SPRINKLER PIPINGSPR(E)
EXISTING PENDANT SPRINKLER HEAD
SACK & ASSOCIATES
Consulting Engineers, PLLC
721 E. Genesee Street
Syracuse, NY 13210
Tel: 315−471−4013
Fax: 315−471−4044
DRAWN BY:
17067
AS NOTED
235 Garden Avenue 1714
CCC - Room 330 D Renovation
CORNELL UNIVERSITY
01/29/19
F103
DDD
THIRD FLOOR PLAN-FIRE PROTECTION
3"SCALE: 1/8" = 1'-0"F103
1 ROOM330D FLOOR PLAN
0 4'8'16'
TTTTTMD4MD3MD1BA54MD2SACK & ASSOCIATESConsulting Engineers, PLLC721 E. Genesee StreetSyracuse, NY 13210Tel: 315−471−4013Fax: 315−471−4044 DRAWN BY:17067AS NOTED235 Garden Avenue1714CCC - Room 330 D RenovationCORNELL UNIVERSITY01/29/19MD103TAMTHIRD FLOOR DEMOLITION PLAN - HVAC3"SCALE: 1/8" = 1'-0"MD103A1THIRD FLOOR DEMOLITION PLAN - HVACHVAC KEYED NOTESMD1 DISCONNECT & REMOVE RETURN AIR GRILLE AND ACCESSORIES.MD2 DISCONNECT & REMOVE THERMOSTAT AND ACCESSORIES INCLUDING CONTROLWIRING/PNEUMATIC TUBING.MD3 DISCONNECT & REMOVE DUCTWORK AND ACCESSORIES INCLUDING HANGERS ANDDIFFUSERS/GRILLES.MD4 DISCONNECT & REMOVE VAV BOX AND ACCESSORIES.
14/10RECTANGULAR DUCT (SIZE IN INCHES)ROUND DUCT (DIAMETER IN INCHES)14ØAUTOMATIC AIR DAMPERVOLUME DAMPERSMOKE DAMPERFIRE DAMPERSDVDFDSYMBOLDESCRIPTIONAADDUCTWORK SYMBOLS & ABBREVIATIONSFIRE SMOKE DAMPERFSDDUCT SMOKE DETECTORDSDOVAL DUCT (SIZE IN INCHES)14/10ØSUPPLY DIFFUSER PLAN SYMBOL EXPLANATION:CFMSUPPLY AIR DIFFUSER (NOMINAL 2' x 2')SUPPLY DIFFUSER TYPE (SEE SCHEDULE)RETURN / EXHAUST AIR REGISTERCFMSL8REGISTER/GRILLE PLAN SYMBOL EXPLANATION:CFM (E = EXHAUST / R = RETURN)REGISTER/GRILLE TYPE (SEE SCHEDULE)CFMRE10SYMBOLDESCRIPTIONGRILLE, REGISTER & DIFFUSER SYMBOLSLINEAR SLOT DIFFUSER WITH DISTRIBUTION PLENUMREGISTER AND DIFFUSER AIR FLOW PATTERNS4-WAY BLOW3-WAY BLOW2-WAY BLOWDUCTWORK EXISTING TO REMAIN IN THIS CONTRACT OR ACTIVEPHASE OF CONTRACTDUCTWORK REMOVED IN THIS CONTRACT OR ACTIVE PHASEOF CONTRACTPOINT OF CONNECTION - NEW TO EXISTINGPOINT OF REMOVAL - DEMOLITION TO EXISTINGDEDICATED ELECTRICAL AREA - NO MECHANICAL WORKALLOWED IN OR ABOVE HIGHLIGHTED AREA UNLESSSPECIFICALLY NOTED OTHERWISEPIPE REMOVED IN THIS CONTRACT OR ACTIVE PHASE OF CONTRACTPIPE EXISTING TO REMAIN IN THIS CONTRACT OR ACTIVE PHASEOF CONTRACTSYS (E)SYSTEM NAME(E) = EXIST TO REMAIN, (D) = EXIST TO BE REMOVEDDUCTWORK PROVIDED IN THIS CONTRACT OR ACTIVE PHASEOF CONTRACTPIPE PROVIDED IN THIS CONTRACT OR ACTIVE PHASE OF CONTRACTSYS (D)SYSSYS (D)SYS(10x6) SYS (E)(10) SYS (E)DEMOLITION KEYED NOTEKEYED NOTESYSTEM PHASING SYMBOLSM#MD#SACK & ASSOCIATESConsulting Engineers, PLLC721 E. Genesee StreetSyracuse, NY 13210Tel: 315−471−4013Fax: 315−471−4044 DRAWN BY:17067AS NOTED235 Garden Avenue1714CCC - Room 330 D RenovationCORNELL UNIVERSITY01/29/19M001TAMDRAWING INDEX AND SYMBOL LISTMECHANICAL DRAWING INDEXNUMBERNAMEREVISIONS# DATEM001 DRAWING INDEX AND SYMBOL LISTM103 THIRD FLOOR PLAN - HVACM501 DETAILSM601 HVAC SCHEDULESM701 CONTROLS SCHEMATICSM702 CONTROLS POINTSMD103 THIRD FLOOR DEMOLITION PLAN - HVACHVAC DUCT SYSTEM ABBREVIATIONSABBREV.DESCRIPTIONEA EXHAUST AIROA OUTSIDE AIRRA RETURN AIRSA SUPPLY AIRHVAC PIPE SYSTEM ABBREVIATIONSABBREV.DESCRIPTIONCHR CHILLED WATER RETURNCHS CHILLED WATER SUPPLYHWR HOT WATER RETURNHWS HOT WATER SUPPLYHVAC EQUIPMENT ABBREVIATIONSABBREV.DESCRIPTIONAHU AIR HANDLING UNITCAV CONSTANT AIR VOLUME UNITCUH CABINET UNIT HEATERFFANFTR-A FINNED TUBE RADIATIONRHC REHEAT COILVAV VARIABLE AIR VOLUME UNIT
TTTTTTTT10/1010/88/68/6SA-8"200REBALANCETO 500 CFMREBALANCETO 200 CFMCONNECTTO EXST.24x8 OVALSA DUCTOFFICE 3330ASHARED OFFICE 3330DOFFICE 5330CCONNECT TOEXST. 7" DIASA DUCTCONNECTTO EXST.18x8 OVALSA DUCT24/8øBA543VAV-3-2VAV-3-1EXST. FTR TO REMAIN.INTEGRATE CONTROLW/ NEW VAV12x12 RAGRILLE W/10x10 SOUNDTRAP. (TYP)SD-8"200SACK & ASSOCIATESConsulting Engineers, PLLC721 E. Genesee StreetSyracuse, NY 13210Tel: 315−471−4013Fax: 315−471−4044 DRAWN BY:17067AS NOTED235 Garden Avenue1714CCC - Room 330 D RenovationCORNELL UNIVERSITY01/29/19M103TAMTHIRD FLOOR PLAN - HVAC3"SCALE: 1/8" = 1'-0"M103A1THIRD FLOOR PLAN - HVAC
1" INTERNAL DOUBLE WALL DUCT LINING FOR A DISTANCE OF 10FEET FROM UNIT OUTLET.LOCATE VALVES AND CONTROL DEVICES FOR CONVENIENT ACCESSAND REMOVAL.TRANSITION SUPPLY DUCT FROM RUN OUT DUCT SIZE SHOWN ONPLAN TO UNIT INLET SIZE.VP/T PORTFLOW BALANCERMANUAL AIR VENTUNION (TYP)TERMINAL UNITFLEXIBLE CONNECTIONSUPPLY AIR DUCT1/2" DRAIN WITH HOSE BIBB2 WAY CONTROL VALVESHUTOFF VALVEMAINSKEYED NOTES:RS123132NOTE: S/R PIPING ONLY FOR UNITS SCHEDULED WITH HOT WATER COILS.SUPPORT SOUND-LINEDDUCT FROM STRUCTUREPLAN VIEWRETURN GRILLESIZE PER PLANSSHEETMETAL SLEEVEFASTEN TO GRILLE ASREQUIRED24"MIN.10"CEILING TEEWALLDIMENSION AS REQUIREDTO CLEAR OBSTRUCTIONS8" MIN. IF SPACE ALLOWSSACK & ASSOCIATESConsulting Engineers, PLLC721 E. Genesee StreetSyracuse, NY 13210Tel: 315−471−4013Fax: 315−471−4044 DRAWN BY:17067AS NOTED235 Garden Avenue1714CCC - Room 330 D RenovationCORNELL UNIVERSITY01/29/19M501TAMDETAILSSCALE: NOT TO SCALEM5014VAV Terminal UnitSCALE: NOT TO SCALEM5015Return Grille Sound Trap
SACK & ASSOCIATESConsulting Engineers, PLLC721 E. Genesee StreetSyracuse, NY 13210Tel: 315−471−4013Fax: 315−471−4044 DRAWN BY:17067AS NOTED235 Garden Avenue1714CCC - Room 330 D RenovationCORNELL UNIVERSITY01/29/19M601TAMHVAC SCHEDULESGRILLE AND DIFFUSER SCHEDULEMARK LOCATION MANUFACTURER MODEL FRAME/BORDER MODULE SIZERA SEE PLANS PRICE530LAY-INSA SEE PLANS PRICE SCDA LAY-IN24/24SD SEE PLANS PRICE SDS/SDA LAY-INVAV TERMINAL UNIT SCHEDULEMARKINLET SIZE (IN)CFMMAXDISCHARGE NCREMARKSMAX MINVAV 3 18 200 100 25VAV 3 28 200 100 25NOTES:1. PROVIDE OPPOSED BLADE DAMPER FOR ALL DIFFUSERS AND REGISTERSEXCEPT TYPE SC.2. COORDINATE MOUNTING FRAME FOR EACH APPLICATION.3. SUBMIT COLOR CHART TO ARCHITECT FOR REVIEW.4. MAX N.C. LEVEL OF NC-25.5. SUBMIT COMPLETE CHART FOR EACH ROOM WITH ALL INFORMATION.6. SD TYPE: LINEAR 4'-0" LENGTH, (2) 3/4" SLOTS W/ PLENUM.
AIAV: SETPOINTBIAOAOAV: FLOW FEEDBACK (CFM)AV: POSITION FEEDBACK(%)AV: FLOW SETPOINT (CFM)SYSTEM DESCRIPTIONVARIABLE VOLUME SUPPLY BOX (VAV-#) COOLINGBASEBOARD RADIATION HEATINGCONTROL FOR INTERIOR VAV BOXES WITHOUTASSOCIATED BASEBOARD HEAT IS THE SAME WITHDELETION OF BASEBOARD HEAT POINTS ANDSEQUENCES.GENERALSYSTEM SHALL BE CONTROLLED THROUGH THEBUILDING AUTOMATION AND CONTROL SYSTEM (BACS).ALL SETPOINTS SHALL BE ADJUSTABLE.THE BACS SHALL BE CAPABLE OF STARTING ANDSTOPPING THE SYSTEM FOR SEVEN DIFFERENT DAILYSCHEDULES PER WEEK.THE BACS SHALL BE CAPABLE OF RETAINING ITSPROGRAMMING AND TIME SETTING DURING A LOSS OFPOWER FOR AT LEAST TEN HOURS.BASIS OF DESIGN MINIMUM COOLING AND HEATINGAIRFLOW SETPOINT IS TO BE 30% OF THE MAXIMUMCOOLING AIRFLOW SETPOINT.SETPOINTSSPACE COOLING TEMPERATURE SETPOINTS:OCCUPIED: 75 °F +/-1.5 °FOCCUPIED SETBACK: 75 °F +3 °FUNOCCUPIED: 75 °F +6 °FSPACE HEATING TEMPERATURE SETPOINTS:OCCUPIED: 70 °F +/-1.5 °FOCCUPIED SETBACK: 70 °F -3 °FUNOCCUPIED: 70 °F -6 °FSV AIRFLOW RATE: CFM HEATING: AS SCHEDULEDCFM COOLING: AS SCHEDULEDEV AIRFLOW RATE: CFM HEATING: AS SCHEDULEDCFM COOLING: AS SCHEDULEDMINIMUM SPACE OCCUPANCY INDEX TIME: 30MINUTESZONE OCCUPANCY SCHEDULE: 6 AM TO 8 PM, MON-FRISPACE OCCUPANCYZONE OCCUPANCY SHALL BE DETERMINED BASED ON A COMBINATION OF A TIME OF DAYSCHEDULE AND A SPACE OCCUPANCY SENSOR.DURING THE SCHEDULED OCCUPANCY PERIOD, THE ZONE SHALL BE INITIALLY INDEXED TOOCCUPIED AND OPERATE FOR A MINIMUM OF 30 MINUTES, AT WHICH TIME THE SPACEOCCUPANCY SENSOR SHALL INDEX THE SPACE BETWEEN OCCUPIED AND OCCUPIEDSETBACK MODE.IF THE SPACE BECOMES OCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, ASDETERMINED VIA THE OCCUPANCY SENSOR, THE ZONE SHALL BE INDEXED TO OCCUPY FORTHE DURATION OF OCCUPANCY. THE ZONE SHALL INDEX BACK TO UNOCCUPIED WHENOCCUPANCY IS NOT SENSED FOR A PERIOD OF 30 MINUTES.FOR ZONES WITH MULTIPLE SPACES, AN OCCUPANCY SENSOR SHALL BE PROVIDED IN EACHSPACE, AND ZONE OCCUPANCY SHALL BE BASED ON OCCUPANCY INPUTS FROM ANY OFTHE SPACE OCCUPANCY SENSORS ASSOCIATED WITH THAT ZONE.ZONE TEMPERATURE CONTROLTEMPERATURE SETPOINTS SHALL BE DETERMINED BASED ON A COMBINATION OFPROGRAMMED SCHEDULE AND A SPACE OCCUPANCY SENSOR.FOR ZONES WITH MULTIPLE SPACES, ZONE TEMPERATURE SHALL BE DETERMINED BASED ONAN AVERAGE OF ALL SPACE TEMPERATURES ASSOCIATED WITH THE ZONE.OCCUPIED HEATING: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED OCCUPIEDPERIOD, THE SUPPLY AIR VAV BOX SHALL INDEX TO THE HEATING AIRFLOW SETPOINT. IF THEZONE TEMPERATURE FALLS BELOW THE OCCUPIED HEATING TEMPERATURE SETPOINT, THEBASEBOARD RADIATION CONTROL VALVE SHALL MODULATE TO MAINTAIN SETPOINT.OCCUPIED COOLING: IF THE SPACE IS OCCUPIED DURING THE SCHEDULED OCCUPIEDPERIOD, THE SUPPLY AIR VAV BOX SHALL INDEX TO THE COOLING MINIMUM AIRFLOWSETPOINT. IF THE ZONE TEMPERATURE RISES ABOVE THE OCCUPIED COOLINGTEMPERATURE SETPOINT, THE SUPPLY AIR VAV BOX SHALL MODULATE BETWEEN THECOOLING MINIMUM AND COOLING MAXIMUM AIRFLOW SETPOINTS AS NEEDED TO MAINTAINSETPOINT. THE BASEBOARD RADIATION CONTROL VALVE SHALL BE CLOSED.OCCUPIED SETBACK: IF THE ZONE IS UNOCCUPIED DURING THE SCHEDULED UNOCCUPIEDPERIOD, THE ABOVE OCCUPIED HEATING AND COOLING SEQUENCES SHALL APPLY. THESPACE SHALL BE MAINTAINED AT THE OCCUPIED SETBACK TEMPERATURE SETPOINTS.UNOCCUPIED HEATING SETBACK: WHEN THE SPACE IS UNOCCUPIED DURING THESCHEDULED UNOCCUPIED PERIOD, THE SUPPLY AIR VAV BOX SHALL INDEX CLOSED. IF THEZONE TEMPERATURE FALLS BELOW THE UNOCUPPIED HEATING SETPOINT, THE BASEBOARDRADIATION CONTROL VALVE SHALL MODULATE AS REQUIRED TO MAINTAIN SETPOINT.UNOCCUPIED COOLING SETBACK: WHEN THE SPACE IS UNOCCUPIED DURING THESCHEDULED UNOCCUPIED PERIOD, THE SUPPLY AIR VAV BOX SHALL INDEX CLOSED. IF THEZONE TEMPERATURE RISES ABOVE THE UNOCUPPIED COOLING SETPOINT, THE SUPPLY AIRVAV BOX SHALL MODULATE BETWEEN THE COOLING MINIMUM AND COOLING MAXIMUMAIRFLOW SETPOINTS AS REQUIRED TO MAINTAIN SETPOINT. THE BASEBOARD RADIATIONCONTROL VALVE SHALL BE CLOSED.IF THE ZONE BECOMES OCCUPIED DURING THE SCHEDULED UNOCCUPIED PERIOD, THEOCCUPIED HEATING AND COOLING SEQUENCES SHALL APPLY FOR THE DURATION OF THEOCCUPANCY. THE ZONE SHALL BE MAINTAINED AT THE OCCUPIED TEMPERATURESETPOINTS. WHEN THE ZONE BECOMES UNOCCUPIED AGAIN DURING THE SCHEDULEDUNOCCUPIED PERIOD, THE ZONE SHALL INDEX BACK TO UNOCCUPIED MODE.dTsaOSCOMMODFROMEXSTACVAV-#HWSF.L.BACnet / ARCNETOR BACnet / MSTPFIN RADIATIONTO OTHER ROOMSON ZONEOCCUPANCY SENSOR IS BYDIV. 26. OBTAIN B.I. SIGNALAND INTERGRATE INTO BACSAS REQUIRED FOR CONTROL.SACK & ASSOCIATESConsulting Engineers, PLLC721 E. Genesee StreetSyracuse, NY 13210Tel: 315−471−4013Fax: 315−471−4044 DRAWN BY:17067AS NOTED235 Garden Avenue1714CCC - Room 330 D RenovationCORNELL UNIVERSITY01/04/19M701TAMCONTROLS SCHEMATICSSCALE: NOT TO SCALEM7011Baseboard Htg And Variable Air Volume Clng
SACK & ASSOCIATESConsulting Engineers, PLLC721 E. Genesee StreetSyracuse, NY 13210Tel: 315−471−4013Fax: 315−471−4044 DRAWN BY:17067AS NOTED235 Garden Avenue1714CCC - Room 330 D RenovationCORNELL UNIVERSITY01/29/19M702TAMCONTROLS POINTSDESCRIPTIONHARDWARE POINTS SOFTWARE POINTSSHOW ONGRAPHICNOTESBI BO AI AO AV BV SCH TRENDALARMBACS/DDC DESCRIPTIONZONE TEMPERATURE SETPOINT X X XZONE TEMPERATURE X X X ± 4°F FROM SETPOINT XBASEBOARD RADIATION CONTROL VALVE POSITION COMMAND X X X FAIL LASTZONE OCCUPANCY X X XSUPPLY AIR VAV BOX DAMPER POSITION COMMAND X X XSUPPLY AIR VAV BOX AIRFLOW FEEDBACK (CFM) X X X 10% FLOW DEVIATION FROM SETPOINT X BACnet MSTP NETWORK POINTSUPPLY AIR VAV BOX SUPPLY BOX AIRFLOW SETPOINT (CFM) X X X BACnet MSTP NETWORK POINTSUPPLY AIR VAV BOX POSITION FEEDBACK (%) X X X VALVE COMMAND ≠ FEEDBACK X BACnet MSTP NETWORK POINT
BA54SHARED OFFICE 3330DWAPED4ED24ED24ED25ED24ED24ED24ED24SACK & ASSOCIATESConsulting Engineers, PLLC721 E. Genesee StreetSyracuse, NY 13210Tel: 315−471−4013Fax: 315−471−4044 DRAWN BY:17067AS NOTED235 Garden Avenue1714CCC - Room 330 D RenovationCORNELL UNIVERSITY01/29/19ED103RCMTHIRD FLOOR DEMOLITION PLAN - ELECTRICAL3"SCALE: 1/8" = 1'-0"ED1031THIRD FLOOR DEMOLITION PLAN - ELECTRICALELECTRICAL KEYED NOTESED4 EXISTING SURFACE RACEWAY SHALL REMAIN.ED24 DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES. REMOVEASSOCIATED RACEWAYS AND CIRCUITING BACK TO SOURCE.ED25 DISCONNECT AND REMOVE EXISTING WIRELESS ACCESS POINT.REMOVE ASSOCIATED RACEWAYS AND CIRCUITING BACK TOSOURCE.
DMBRANCH CIRCUIT HOMERUN: 2 #12, 1 #12G, 1/2"C TO PANELBOARDCIRCUIT NUMBER AS INDICATED UNLESS OTHERWISE NOTED.B1 / 12 = PANEL NAME / CIRCUIT NUMBERWALL MOUNTED DIMMER SWITCHDESCRIPTIONSYMBOLLIGHTING SYMBOLSBLED LIGHT FIXTURE, SUBSCRIPT B = FIXTURE TYPE, REFER TOSPECIFICATIONS AND LIGHT FIXTURE SCHEDULE.SDUPLEX RECEPTACLE OUTLET, WALL MOUNTED / ABOVECOUNTER MOUNTEDACBRANCH CIRCUITRY: 2 #12, 1 #12G, 1/2"C UNLESS OTHERWISE NOTEDB1/12DEVICE SYMBOLSDESCRIPTIONSYMBOLWAPTYPE WAP (WIRELESS ACCESS POINT) DATA OUTLET - CEILINGMOUNTED, 2-GANG BOX. (2) CAT6 WIRELESS ACCESS POINT DATACABLES - (2) RJ-45 JACKS. INSTALL OWNER FURNISHED WIRELESSACCESS EQUIPMENT AT EACH LOCATION.DATA OUTLET(1) CAT6 DATA CABLE AND (1) CAT6 VOICE CABLE - (2) RJ-45 JACKSE1SYMBOLGENERAL SYMBOLSREFERS TO KEYED NOTE ON RESPECTIVE DRAWINGDESCRIPTIONREFERS TO DEMOLITION KEYED NOTE ON RESPECTIVE DRAWINGED1DOUBLE DUPLEX RECEPTACLE OUTLET, WALL MOUNTED / ABOVECOUNTER MOUNTEDACOSVCEILING MOUNTED OCCUPANCY/VACANCY SENSOR.REFER TO SPECIFICATIONS.A.REFER TO ARCHITECTURAL DRAWINGS FOR EXTENT OF BASEBID NEW CONSTRUCTION AND RENOVATED AREAS, PHASINGREQUIREMENTS AND ALTERNATES.B.PROVIDE MATERIALS AND LABOR FOR COMPLETE, FUNCTIONALSYSTEMS. COORDINATE WIRING AND CONNECTIONREQUIREMENTS FOR EQUIPMENT. MATERIALS, EQUIPMENT,CONDUCTORS, WIRING DEVICES, ETC. SHALL BE NEW AND UL-LISTED, SUITABLE FOR LOCATION AND FUNCTION.C.COORDINATE EXACT LOCATION OF ELECTRICAL BOXES ANDRACEWAY PRIOR TO ROUGH-IN. REFER TO ARCHITECTURALPLANS AND ELEVATIONS.D.VERIFY SCOPE AND PHASING OF REMOVAL WORK FOR AREASTO BE ABATED ANDRENOVATED. PROTECT EXISTINGCIRCUITRY SERVING ADJACENT AREA/EQUIPMENT WHICH WILLREMAIN IN USE. PROVIDE SUPPORT AND TEMPORARYCONNECTIONS/RE-ROUTING AS REQUIRED. REFER TOARCHITECTURAL DRAWINGS INDICATING REMOVAL SCOPE OFWORK. CONTRACTOR FOR DIVISION 26 SHALL DISCONNECTAND REMOVE BRANCH CIRCUITRY, LIGHT FIXTURES, WIRINGDEVICES, AND RESPECTIVE SYSTEM WIRING/CABLINGCOMPLETE. REMOVALS SHALL INCLUDE ALL ELECTRICALCOMPONENTS IN/ON WALLS THAT ARE TO BE REMOVEDUNLESS NOTED OTHERWISE. MAINTAIN CIRCUITRY TOEQUIPMENT AND DEVICES THAT ARE TO REMAIN.E. FIRE STOP PENETRATIONS THROUGH FIRE RATED WALLS ANDFLOORS WITH FIRESTOP MATERIAL EQUAL IN RATING TO THECONSTRUCTION OF WHICH IT IS PENETRATING.F.REMOVAL OF FIRE PROOFING MATERIALS OR CREATION OFOPENINGS IN FIRE BARRIERS RESULTING FROM REMOVALWORK SHALL BE REPLACED OR FILLEDWITH FIRE BARRIERMATERIAL TO MATCH AND MAINTAIN EXISTING FIRE BARRIERRATING.HGROUNDING REQUIREMENTS1.ALL GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLE 250.2.ALL INSULATED GROUND CONDUCTORS SHALL BE GREEN.PROVIDE EQUIPMENT GROUND CONDUCTOR FOR EACH BRANCH CIRCUIT.3. PROVIDE GROUNDING PER EQUIPMENT MANUFACTURER REQUIREMENTS.GENERAL NOTESI.CONNECTIONS TO EQUIPMENT FURNISHED BY OTHERS:1.VARIOUS PIECES OF EQUIPMENT WILL BE FURNISHED TO THE PROJECT SITE AND INSTALLED BY OTHER DIVISIONS.2.PROVIDE ROUGHING-IN AND FINAL CONNECTIONS AS REQUIRED IN ACCORDANCE WITH EQUIPMENT INSTALLATIONINSTRUCTIONS.3.BEFORE PROCEEDING WITH THE WORK, OBTAIN FULL INFORMATION REGARDING ROUGH-IN MEASUREMENTS, EQUIPMENT LAYOUTS, ELEVATIONS, TRIM BEING FURNISHED, AND OTHER NECESSARY DATA.4.UPON REQUEST, CONSTRUCTION MANAGER WILL PROVIDETHIS DIVISION WITH DIAGRAMS, PHOTOGRAPHS, DRAWINGS,AND/OR SPECIFICATIONS AND OTHER COMPLETE DESCRIPTIVE DATA. DO NOT ROUGH-IN WITHOUT APPROVEDLAYOUT FROM CONSTRUCTION MANAGER.5.PROVIDE ACCESSORIES SO THAT CONNECTIONS MAY BE MADE IN A MANNER THAT SHALL MEET ALL REGULATIONS AND CODES.6.SEE APPROPRIATE SECTIONS OF THIS DIVISION'S SPECIFICATIONS FOR MATERIALS AND METHODS.J.USE OF SHALLOW FLUSH MOUNT ELECTRICAL BOXES SHALL BEPERMITTED WHERE DEPTH OF WALL CAVITY/FURRING IS LESS THAN 2 1/2" AS INDICATED ON ARCHITECTURALDRAWINGS.K.PROVIDE PATCHING AT EXISTING SOFFIT IN ACCORDANCE WITHDIVISION 1 SPECIFICATION. COORDINATE PATCHING WORKWITH GENERAL CONTRACTOR AND ARCHITECTURALDOCUMENTS.L.ALL CIRCUIT CONDUITS WILL BE CONCEALED. SURFACERACEWAY WILL NOT BE ACCEPTED.M.EXISTING CONCEALED CONDUITS IN EXISTING WALLS SHALLREMAIN.SACK & ASSOCIATESConsulting Engineers, PLLC721 E. Genesee StreetSyracuse, NY 13210Tel: 315−471−4013Fax: 315−471−4044 DRAWN BY:17067AS NOTED235 Garden Avenue1714CCC - Room 330 D RenovationCORNELL UNIVERSITY01/29/19E001RCMDRAWING INDEX, NOTES & SYMBOL LISTELECTRICAL DRAWING INDEXNUMBERNAMEREVISIONS# DATEE001 DRAWING INDEX, NOTES & SYMBOL LISTED103 THIRD FLOOR DEMOLITION PLAN - ELECTRICALE103 THIRD FLOOR PLAN - ELECTRICAL
OSOSBA54SHARED OFFICE 3330DBE6E7DMD1D1C2 C2 C2C2C2E6DMEMTAFFACGEMGFCONNECT TO EMERGENCY CIRCUITGROUND FAULT INTERUPT DEVICEGROUNDABOVE FINISHED FLOORABOVE COUNTER - 6" ABOVE COUNTERTOPELECTRIC METALLIC TUBINGDESCRIPTIONSYMBOLABBREVIATIONSETR EXISTING TO REMAINER EXISTING, RELOCATED LIGHT FIXTURESACK & ASSOCIATESConsulting Engineers, PLLC721 E. Genesee StreetSyracuse, NY 13210Tel: 315−471−4013Fax: 315−471−4044 DRAWN BY:17067AS NOTED235 Garden Avenue1714CCC - Room 330 D RenovationCORNELL UNIVERSITY01/29/19E103RCMTHIRD FLOOR PLAN - ELECTRICALELECTRICAL KEYED NOTESE6 CIRCUIT TO AN EXISTING LIGHTING BRANCH CIRCUIT IN THEAREA.E7 CIRCUIT TO A SPARE 20A/1P CIRCUIT BREAKER IN EXISTINGPANEL P4.3"SCALE: 1/8" = 1'-0"E1031THIRD FLOOR PLAN - ELECTRICALLUMINAIRE SCHEDULE - LEDTYPE LUMINAIRE DESCRIPTION LUMENS WATTAGE CRICOLORTEMPERATUREVOLTAGEDRIVER(S)ACCEPTABLE MANUFACTURERS MODEL NUMBER MOUNTING NOTESTYPE QTYB LED, 9IN X 8FT PENDANT MOUNTED, LINEARLIGHT FIXTURE5378 58 W 80 3500 120 V 0 - 10V DIMMING 1 FINLITE SERIES 12 INDIRECT/DIRECT S12LEDID-DCO-8-2E-H-835-30U70D-120V-SC-FA-FE-C1 PENDANTC2 LED, 5IN X 2FT RECESSED MOUNTED,LINEAR LIGHT FIXTURE WITH DROP LENS966 10 W 80 3500 120 V 0 - 10V DIMMING 1 PINNACLE EDGE EV6 SERIES EV6-AL-835-2-G1-U-OL1-1-0-W RECESSEDD1 LED, 6IN DIAMETER X 4.5IN DEEPDOWNLIGHT2000 21 W 80 3500 120 V 0 - 10V DIMMING 1 PHILIPS LIGHTOLIER P6R-D-20-N-Z10-U-VB / P6R-D-8-35-VB / P6R-D-CL RECESSED