HomeMy WebLinkAboutAlice Cook and Flora RoseSet No.
FEB 15, 2019
08249-15002
Tetra Tech Engineers, Architects & Landscape Architects, P.C.
Architecture Engineering Planning
High Performance FacilitiesforCornell University
Ithaca, New York
N
5 DRAWING REVISION NUMBER
CENTER LINE
MATCH LINE
CLL
A COLUMN CENTER LINE
CONTRACT LIMIT LINE
PROPERTY LINE
CUT LINE
NORTH ARROW
ROOM NAME AND NUMBER
ELEVATION
INTERIOR ELEVATION
DETAIL
WALL SECTION
BUILDING SECTION
STANDARD REFERENCE BUBBLE
DRAWING NUMBER
DETAIL NUMBER
DRAWING TITLE & SCALE
METAL, STEEL
REMOVE AND REPLACE ASPHALT PAVING
NEW HEAVY-DUTY ASPHALT PAVING
NEW ASPHALT PAVING OR TOP COURSE
SAND
GRAVEL
CONCRETE
BRICK
EARTH
STONE
CONCRETE MASONRY UNITS
PLYWOOD
FINISHED WOOD TRIM
ROUGH WOOD
INSULATION (LOOSE OR BATT)
RIGID INSULATION
CERAMIC TILE
ACOUSTICAL PANEL
GLASS (LARGE SCALE)
PLASTER, CEMENT, GROUT
GYPSUM WALL BOARD
RESILIENT FLOORING
TERRAZZO
STRUCTURAL GLAZED TILE
ADA 5' TURNING RADIUS
1st FF
Floor Plan
1/8"=1'-0"
100'-0"
N
CLASSROOM
101
NOTE:REFER TO FINISH PLANS FOR ROOM FINISH KEY
AND ADDITIONAL ABBREVIATIONS
AAC ASBESTOS ABATEMENT CONTRACTOR
AAD AUTOMATIC AIR DAMPER
AB ANCHOR BOLT, AIR BARRIER
AC AIR CONDITIONING, ALTERNATING CURRENT
ACCMP ASPHALT COATED CORR METAL PIPE
ACM ASBESTOS CONTAINING MATERIAL
ACT ACOUSTICAL CEILING TILE
ACU AIR CONDITIONING UNIT
AD AREA DRAIN
ADA AMERICAN DISABILITIES ACT
ADD ADDENDUM
ADDL ADDITIONAL
ADDN ADDITION
ADH ADHESIVE
ADJ ADJACENT
ADR ACCESS DOOR
AESS ARCH EXPOSED STRUCTURAL STEEL
AFF ABOVE FINISH FLOOR
AH ACCESS HATCH
AHU AIR HANDLING UNIT
AIB AIR INFILTRATION BARRIER
ALT ALTERNATE
ALTB ACOUSTICALLY LINED TRANSFER BOX
ALTN ALTERATION ALUM ALUMINUM
AMP AMPERE
ANOD ANODIZED
ANT ACID NEUTRALIZATION TANK
AP ACCESS PANEL
APPROX APPROXIMATE (LY)
APC ARCHITECTURAL PRECAST CONCRETE
ARCH ARCHITECT (URAL)
A/S AIR SEPARATOR
ASB ASBESTOS
ASPH ASPHALT
ATV ATMOSPHERIC VENT
AUD AUDITORIUM
AUTO AUTOMATIC
AV ACID VENT
AVE AVERAGE
AVTR ACID VENT THRU ROOF
AW ACID WASTE
B BOILER, BRICK, BOTTOM
BB BASKETBALL
BBD BOILER BLOWDOWN
BC BOTTOM OF CURB
BCU BLOWER COIL UNIT
BCX BOTTOM CHORD EXTENSION
BD BOARD
BDD BACKDRAFT DAMPER
BFP BACK FLOW PREVENTER
BG BOTTOM GRILLE
BIT BITUMINOUS
BLDG BUILDING BLOCK
BLK BLOCKING BLKG
BM BEAM
BO BY OTHERS
BOD BOTTOM OF DUCT
BOF BOTTOM OF FOOTING
BOS BOTTOM OF STEEL
BOT BOTTOM
BPL BEARING PLATE
BR BOTTOM REGISTER
BRDG BRIDGING
BRG BEARING
BRK BRICK
BRSH BRICKSHELF
BRZ BRONZE
BS BOTH SIDES, BOTTOM OF STAIR
BSMT BASEMENT
BSPL BACKSPLASH
BT BENT
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
BUR BUILT-UP ROOFING
BW BOTTOM OF WALL
BWC BACK WATER CHECK VALVE
C1 CARPET TYPE 1
C CONDUIT, CONVECTOR, CONDENSOR,
COMMON
CA COMPRESSED AIR
CAB CABINET
CATV CABLE TELEVISION
CB CATCH BASIN, CIRCUIT BREAKER, CHALKBOARD
CCTV CLOSED CIRCUIT TELEVISION
CD CEILING DIFFUSER, CONDENSATE DRAIN
CEM CEMENT
CER CERAMIC CF CUBIC FEET, CEILING FAN
CFM CUBIC FEET PER MINUTE
CFMF COLD FORMED METAL FRAMING
CFT1 CERAMIC FLOOR TILE TYPE 1
CG CEILING GRILLE
CHAN CHANNEL
CHUV CEILING HUNG UNIT VENTILATOR
CI CAST IRON
CIP CAST IN PLACE
CIRC CIRCUMFERENCE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLKG CAULKING
CLL CONTRACT LIMIT LINE
CLR CLEAR (ING) (ENCE)
CLRM CLASSROOM
CMP CORRUGATED METAL PANEL
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
CODP CLEAN OUT DECK PLATE
COL COLUMN
COMB COMBINATION
COMP COMPRESS (ED) (ION) (IBLE), COMPOSITE
CONC CONCRETE
COND CONDENSATE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINOUS
CONTR CONTRACT (OR)
COORD COORDINATE
CORR CORRUGATED, CORRIDOR
COWP CLEAN OUT WALL PLATE
CPVC CHLORINATED POLY VINYL CHLORIDE
CR CEILING REGISTER
CRS COURSE (S)
CSK COUNTERSINK
CSMT CASEMENT
CT COMPUTER TERMINAL, CERAMIC BASE TILE
CTD COATED
CTOP COUNTER TOP
CTR CENTER
CU CUBIC
CUH CABINET UNIT HEATER
CV CONVECTOR, CURB VALVE
CW COLD WATER
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
CWT1 CERAMIC WALL TILE TYPE 1
D1 DANCE FLOORING TYPE 1
D DIESEL FUEL, DEPTH
DB DRY BULB
DC DIRECT CURRENT
DDC DIRECT DIGITAL CONTROL
DE DELONIZED WATER
DEG DEGREES
DEMO DEMOLISH
DEP DEPRESS (ED) (ION)
DET DETAIL (ED)
DF DRINKING FOUNTAIN
DH DOUBLE HUNG
DHU DEHUMIDIFICATION UNIT
DI DROP INLET, DUCTILE IRON, DISTILLED WATER
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DISP DISPENSER
DIST DISTANCE
DIV DIVISION
DL DEAD LOAD
DN DOWN
DO DITTO
DP DAMPPROOF (ING)
DPR DAMPER
DR DOOR, DEEP RIB
DWG DRAWING
DS DOWNSPOUT, DRAINAGE STRUCTURE
DT DRAIN TILE
DTA DOVETAIL ANCHOR
DTL DETAIL
DW DUMBWAITER, DISHWASHER
DWL DOWEL
DWR DRAWER
E EAST
EA EXHAUST AIR, EACH
EAT ENTERING AIR TEMPERATURE
EB EXPANSION BOLT
EC ELECTRICAL CONTRACTOR
ECF ENHANCED CONCRETE FLOORING
EIFS EXTERIOR INSULATION FINISH SYSTEM
EF EACH FACE, EXHAUST FAN
EJ EXPANSION JOINT
ELEC ELECTRIC (AL)
ELEM ELEMENT
ELEV ELEVATION, ELEVATOR
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENC ENCLOSURE
EOD EDGE OF DECK
EOS EDGE OF SLAB
EQ EQUAL, EQUIVALENT
EQC EQUIPMENT CONTRACTOR
EQUIP EQUIPMENT
ES EXPOSED SURFACE, EXPOSED STRUCTURE
ESF ELASTIC SHEET FLASHING
ESM ELASTIC SHEET MEMBRANE
EW EACH WAY
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXG EXISTING
EXP EXPANSION
EXT EXTERIOR, EXTERNAL
F FAHRENHEIT
FA FIRE ALARM
FAI FRESH AIR INTAKE
FCU FAN COOLING UNIT
FD FLOOR DRAIN, FIRE DAMPER
FDC FIRE DEPARTMENT CONNECTION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR, FACTORY FINISH
FFE FINISH FLOOR ELEVATION
FFL FINISH FLOOR LINE
FG FLOOR GRILLE
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIN FINISH (ED)
FIXT FIXTURE
FL FLUSH
FLD FLOOR DUCT
FLEX FLEXIBLE
FLG FLASHING
FLR FLOOR (ING)
FLUOR FLUORESCENT
FM FLOOR MOUNTED
FMC FLEXIBLE METAL CONDUIT
FND FOUNDATION
FOB FREIGHT ON BOARD, FLAT ON BOTTOM
FOG FUEL OIL GAUGE
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOT FLAT ON TOP
FP FIREPROOF (ING)
FPM FEET PER MINUTE
FR FRAME, FLOOR REGISTER
FRA FRESH AIR
FRC FIRE RESISTANT COATING
FRP FIBERGLASS REINFORCED PANEL
FRT FIRE RETARDANT
FS FLOOR SINK
FSD FIRE AND SMOKE DAMPER
FT FEET, FLOOR TREATMENT
FTG FOOTING
FTR FIN TUBE RADIATION
FV FLUSH VALVE
G GAS, GLYCOL
GA GAUGE
GAL GALLON
GALV GALVANIZED
GASK GASKET (ED)
GC GENERAL CONTRACT (OR)
GCMU GLAZED CONCRETE MASONRY UNIT
GCO GRADE CLEANOUT GF GROUND FACE
GL GLASS, GLAZING
GND GROUND
GPM GALLONS PER MINUTE
GR GRADE (ING), GLYCOL RETURN
GS GLYCOL SUPPLY
GVL GRAVEL
GWB GYPSUM WALL BOARD
GYP GYPSUM
H HEIGHT
HB HOSE BIB
HBD HARD BOARD
HC HEATING CONTRACT (OR), HANDICAP
HCR HOT/CHILLED RETURN
HCS HOT/CHILLED SUPPLY
HD HEAVY DUTY
HDPE HIGH DENSITY POLYETHYLENE
HDR HEADER
HDW HARDWARE
HG HOT GLYCOL
HIP HIGH IMPACT PANEL
HM HOLLOW METAL
HORZ HORIZONTAL
HP HORSEPOWER, HIGH PRESSURE, HEAT PUMP
HPC HIGH PERFORMANCE COATING
HPL HIGH PRESSURE LAMINATE
HR HANDRAIL, HOUR
HT HEIGHT
HTG HEATING
HV HIGH VOLTAGE
HVAC HEATING/VENTILATING/AIR CONDITIONING
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWH HOT WATER HEATER
HWP HOT WATER PUMP
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
ID INSIDE DIAMETER
IE INVERT ELEVATION
IN INCHES
INCL INCLUDE (D) (ING)
INS INSULATE (D) (ION)
INT INTERIOR
INV INVERT
IP IRON PIPE
IPS IRON PIPE SIZE
IW INDIRECT WASTE
J JANITORS CLOSET
JAN JANITORS CLOSET
JB JUNCTION BOX
JC JANITORS CLOSET
JCT JUNCTION
JT JOINT
KW KILOWATT
KWH KILOWATT PER HOUR
KV KILOVOLT
KVA KILOVOLT AMPERE
L LENGTH, LONG
LAB LABORATORY
LAD LADDER
LAM LAMINATE (D)
LAT LEAVING AIR TEMPERATURE
LAV LAVATORY
LB POUND
LBL LABEL
LBP LEAD BASED PAINT
LC LANDSCAPE CONTRACTOR (SITE)
LCC LEAD COATED COPPER
LDR LEADER
LEV LEVEL
LF LINEAR FOOT
LFMC LIQUID-TIGHT FLEXIBLE METAL CONDUIT
LFNC LIQUID-TIGHT FLEXIBLE NONMETALLIC CONDUIT
LG LENGTH, LONG
LGI LARGE GROUP INSTRUCTION
LH LEFT HAND
LIN LINEAR
LKR LOCKER
LL LIVE LOAD
LP LOW PRESSURE
LPC LOW PRESSURE CONDENSATE
LPS LOW PRESSURE STEAM
LPT LOW POINT
LS LINOLEUM SHEET TYPE 1
LT LIGHT
LT1 LINOLEUM TILE TYPE 1
LTL LINTEL
LV LOW VOLTAGE
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
MAN MANUAL
MAS MASONRY
MAT MATERIAL
MAU MAKE UP AIR UNIT
MAX MAXIMUM
MB MARKER BOARD
MBH THOUSAND BTUH
MBR MEMBER
MD MOTORIZED DAMPER
ME MECHANICAL EQUIPMENT
MECH MECHANICAL (LY)
MED MEDIUM
MEMB MEMBRANE
MEZZ MEZZANINE
MF MIXING FAUCET
MFR MANUFACTURE (R)
MH MAN HOLE
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
MO MASONRY OPENING
MOD MODULE (OR), MODEL
MR MOP RECEPTOR
MP MULTICOLOR WALL COATING
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTL METAL
MTH MARBLE THRESHOLD
MTR METER
MULL MULLION
MVEJ MASONRY VENEER EXPANSION JOINT
N NORTH, NO WORK REQUIRED
NAT NATURAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NEG NEGATIVE
NEUT NEUTRALIZATION
NIC NOT IN CONTRACT
NO NUMBER, NORMALLY OPEN
NOM NOMINAL
NRC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALE
OA OVERALL, OUTSIDE AIR
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
OPP HD OPPOSITE HAND
P PAINT SURFACE(S) INCLUDING SOFFITS
PAR PARALLEL
PART PARTITION
PC PLUMBING CONTRACT (OR),
PIGMENTED CONCRETE
PCC PRECAST CONCRETE
PE PORCELAIN ENAMEL
PERF PERFORATE (ION) (ED)
PERI PERIMETER
PERP PERPENDICULAR
PL PLATE, PROPERTY LINE
PLAM PLASTIC LAMINATE
PLAS PLASTER, PLASTIC
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PM PLUGMOLD
PNL PANEL
POC POINT OF CURVATURE, POINT OF CONNECTION
POL POLISHED
POS POSITIVE
POT POINT OF TANGENCY
PR PAIR
PRE POWER ROOF EXHAUSTER
PREP PREPARE (ATION)
PRF PREFORMED
PROJ PROJECT
PS PAINT EXPOSED STRUCTURE/DECK
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT
PT1 PORCELAIN TILE TYPE 1
PTD PAINTED
PTFR PRESSURE TREATED FIRE RETARDANT
PTP PRESSURE TREATED PRESERVATIVE
PVC POLYVINYL CHLORIDE
PVMT PAVEMENT
PWE POWER WALL EXHAUSTER
QF QUARTZ FLOORING
QT QUARRY TILE
R RADIUS, RETURN, REFRIGERANT
RA RETURN AIR
RAD RADIATION
RAF RETURN AIR FAN, RESILIENT ATHLETIC FLOORING
RB RESILIENT BASE
RC ROOFING CONTRACT (OR)
RCA RECYCLED CONCRETE AGGREGATE
RCP REINFORCED CONCRETE PIPE,
REFLECTED CEILING PLAN
RCU REMOTE CONDENSING UNIT
RD ROOF DRAIN
RECEPT RECEPTACLE
REF REFERENCE
REFL REFLECT (ED) (IVE) (OR)
REFR REFRIGERATOR
REG REGISTER
REINF REINFORCE (D) (ING)
REM REMOVED
REQD REQUIRED
RESIL RESILIENT
RET RETAINING, RETURN
REV REVISION, REVISED, REVEAL
RF RUBBER FLOORING TYPE 1
RFG ROOFING
RFH ROOF HATCH
RFM RECESSED FLOOR MAT
RG RETURN GRILLE
RGS RIGID GALVANIZED STEEL
RH RIGHT HAND
RHC REHEAT COIL
RI ROUGH-IN
RL RAIN LEADER
RLG RAIL (ING)
RM ROOM
RMC RIGID METAL CONDUIT
RNC RIGID NONMETALLIC CONDUIT
RNT RUNNING TRAP
RO ROUGH OPENING
ROW RIGHT OF WAY
RPM REVOLUTIONS PER MINUTE
RR REMOVE EXISTING AND REPLACE WITH NEW
RS RUBBER STAIR TREAD/RISER
RTH ROOF TOP HOOD
RTU ROOF TOP UNIT
RW RAW WATER
S SOUTH, SUPPLY, SURGE PROTECTED
SA SUPPLY AIR
SAN SANITARY
SAS SMOOTH ALL SIDES
SC SOLID CORE, SILL COCK, SEALED CONCRETE
SCHED SCHEDULE
SCT STRUCTURAL CLAY TILE
SD STORM DRAIN, SPLITTER DAMPER,
SMOKE DAMPER
SEC SECTION
SF SQUARE FEET
SGI SMALL GROUP INSTRUCTION
SGT STRUCTURAL GLAZED TILE
SH SHELF, SHELVING, SMOKE HATCH
SHR SHOWER, SHEAR WALL
SHT SHEET
SHTHG SHEATHING
SIM SIMILAR
SK SINK
SL SOUND LINED, SKYLIGHT
SLC SILLCOCK
SLV SLEEVE
SLVR STORM LOUVER
SMH SANITARY MANHOLE
SOG SLAB ON GRADE
SP STATIC PRESSURE, STANDPIPE,
SPACE (ING) (ES)
SPEC SPECIFICATION (S)
SPKR SPRINKLER
SPL SPECIAL
SQ SQUARE
SS STAINLESS STEEL
SST STRUCTURAL STEEL TUBING
ST STORM, STORAGE
STA STATION
STC SHOWER TEMPERATURE CONTROLLER,
STAINED CONCRETE
STD STANDARD
STG SEATING
STL STEEL
STN STAIN (ED)
STOR STORAGE
STRU STRUCTURAL
SURF SURFACE
SUSP SUSPENDED
SV SHEET VINYL, STEAM VENT
SW SWITCH, SOFTENED WATER
SWCI SERVICE WEIGHT CAST IRON
SYM SYMMETRICAL
SYN SYNTHETIC
SYS SYSTEM
T TREAD, TOP, TOILET ROOM, TONS
T1 TERRAZZO TYPE 1
TB TOP AND BOTTOM, TACK BOARD,
TERRAZZO BASE
TBD TO BE DETERMINED
TC TEMPERATURE CONTROL, TEMPERED CLEAR,
TELECOMMUNICATIONS CONTRACTOR,
TOP OF CURB
TCX TOP CHORD EXTENTION
TDV TRIPLE DUTY VALVE
TEL TELEPHONE
TEMP TEMPERATURE
TG TOP GRILLE, TONGUE AND GROOVE
THK THICKNESS
THR THRESHOLD
TME TO MATCH EXISTING
TMV THERMOSTATIC MIXING VALVE
TOD TOP OF DUCT
TOF TOP OF FASCIA, TOP OF FOOTING
TOL TOLERANCE
TOM TOP OF MASONRY
TOP TOP OF PIPE, TOP OF PIER
TOS TOP OF STEEL, TOP OF STAIR
TPART TOILET PARTITION
TR TOP REGISTER
TRN TRANSOM
TS TOP OF STAIR
TV TELEVISION
TW TEMPERED WATER, TOP OF WALL
TYP TYPICAL
UC UNDERCUT
UD UNDERDRAIN
UE UNDERGROUND ELECTRIC
UG UNDERGROUND
UH UNIT HEATER
UNF UNFINISHED
UNIF UNIFORM
UNO UNLESS NOTED OTHERWISE
UR URINAL
UT UNDERGROUND TELEPHONE
UV UNIT VENTILATOR
V VENT, VOLT
VAR VARIES, VARIABLE
VARN VARNISH
VAT VINYL ASBESTOS TILE
VAV VARIABLE AIR VOLUME
VB VACUUM BREAKER, VAPOR RETARDER BARRIER,
VOLLEYBALL
VCB VENTED COVE BASE
VCT1 VINYL COMPOSITE TILE TYPE 1
VD VOLUME DAMPER
VERM VERMICULITE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VIN VINYL
VIT VITREOUS TILE
VNR VENEER
VOL VOLUME
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WEST, WIDTH, WIDE, WASTE, WATT
WB WET BULB
WC WATER CLOSET, WALL COVERING
WD WOOD
WD1 WOOD FLOORING - GYM
WD2 WOOD FLOORING - STAGE
WDW WINDOW
WDWC WINDOW CONTRACTOR
WF WASH FOUNTAIN
WG WALL GRILLE, WATER GAUGE
WH WALL HUNG, WALL HYDRANT
WI WROUGHT IRON
WM WIREMOLD
WP WATER PROOFING, WORKING POINT
WR WATER REPELLENT, WIDE RIB, WALL REGISTER
WS WATER STOP
WSCT WAINSCOT
WT WEIGHT
WWHP WATER TO WATER HEAT PUMP
WWM WELDED WIRE MESH
W/WITH
W/O WITHOUT
XHCI EXTRA HEAVY CAST IRON
YD YARD DRAIN, YARD
Drawing List:
Title Sheet
SA Symbols & Abbreviations
M100 Alice Cook House Key Plans
M101 Alice Cook House Enlarged Plans and
Details
M400 Flora Rose House Key Plans
M401 Flora Rose House Enlarged Plans and
Details
100% Construction Documents
Mechanical Symbols
PIPE ELBOW UP
CAP OR PLUG
PIPE ANCHOR
PIPE GUIDE
PIPE DOWN WITH
PIPE DOWN WITH SHUTOFF VALVE
EXPANSION COMPENSATOR
CLEANOUT AT BASE
UNION CONNECTION
PIPING REDUCER (CONCENTRIC)
PIPING REDUCER (ECCENTRIC)
TOP PIPE CONNECTION
PIPE ELBOW DOWN
BOTTOM PIPE CONNECTION
TEMPERATURE OR
THERMOMETER
(PETE'S PLUG)
P
FLOW SWITCH
MANUAL AIR VENT
ORIFICE METER
FLOW METER
AV
F
M
AUTOMATIC AIR VENT
FLEX CONNECTOR
PRESSURE GAUGE
PRESSURE SWITCH
PRESSURE/TEMPERATURE
PRESSURE PROBE WELL
AQUASTAT
WITH BLOW DOWN VALVE
D
A
VALVE
BALL VALVE
CHECK VALVE
2-WAY CONTROL
AUTOMATIC FLOW CONTROL
BUTTERFLY VALVE
BALANCING VALVE
BACKFLOW PREVENTOR
MODULATING VALVE
3-WAY CONTROL,
DUPLEX BASKET STRAINER
WYE STRAINER
DIRECTION OF FLOW
PITCH PIPING (DOWN)
WYE STRAINER
VALVE
GLOBE VALVE
PLUG VALVE
GATE VALVE
S
AIR SEPARATOR
STEAM TRAP
CIRCULATING PUMP
TEMP AND PRESSURE RELIEF VALVE
SOLENOID (ELECTRIC) ON/OFF
FUSIBLE LINK VALVE
OS&Y GATE VALVE
GAS PRESSURE REGULATOR
PRESSURE REDUCING VALVE
MODULATING VALVE
ATMOSPHERIC VENT
BOILER BLOW DOWN
CHILLED WATER RETURN
CHILLED WATER SUPPLY
HEAT PUMP SUPPLY
HEAT PUMP RETURN
GLYCOL RETURN
GLYCOL SUPPLY
CONDENSATE DRAIN
DUCT UP NEGATIVE PRESSURE
DUCT DOWN POSITIVE PRESSURE
DUCT UP POSITIVE PRESSURE
DUCT DOWN NEGATIVE PRESSURE
HOT WATER RETURN
(NON-POTABLE)
MAKE-UP COLD WATER
LOW PRESSURE STEAM
MECHANICAL EQUIPMENT
EXISTING HVAC PIPE
REFRIGERANT LIQUID
REFRIGERANT HOT GAS
PUMP DISCHARGE
REFRIGERANT SUCTION
REMOVE EXG. DUCT, PIPING,
W/VOLUME DAMPER
FLEXIBLE CONNECTION
STANDARD BRANCH DUCT
RECTANGULAR ELBOW
POSITIVE PRESSURE DUCT UP
THROUGH NEXT FLOOR/ROOF
THROUGH NEXT FLOOR/ROOF
NEGATIVE PRESSURE DUCT UP
RECTANGULAR ELBOW
W/TURNING VANES
FIRE AND SMOKE DAMPER
ACOUSTICALLY LINED
SMOKE DAMPER
FIRE DAMPER
DUCTWORK
VOLUME DAMPER
FLEXIBLE DUCT
AIR FLOW
AUTOMATIC AIR DAMPER
EXHAUST FAN
DUCT AIR FLOW
EXISTING DUCTWORK
HUMIDISTAT
HUMIDITY SENSOR
ROOFTOP HOOD
HOT WATER SUPPLY
CODP CLEANOUT DECK PLATE
BALL VALVE
SHOCK ABSORBER W/
SHOCK ABSORBER
CLEANOUT PLUG
EXG FIRE HYDRANT
FIRE HYDRANT
F
FIRE HYDRANT (FE)
WALL HOOK
LOW PRESSURE CONDENSATE
HOT/CHILLED WATER SUPPLY
HOT/CHILLED WATER RETURN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
FIRE RISER VALVE ASSEMBLY
CFM, GPM, CAPACITY
EQUIPMENT TAG (MOTORIZED)
EQUIPMENT TAG (NON-MOTORIZED)
REGISTER, GRILLE, DIFFUSER
ENCLOSURE NOTED AS:
FIN TUBE RADIATION
W/W: WALL TO WALL,
W/U: WALL TO UNIT,
W/D: WALL TO DOOR, ETC...
SWEEP ELBOW WITH
SWEEP ELBOW
TURNING/SPLITTER VANES
CHILLED GLYCOL RETURN
CHILLED GLYCOL SUPPLY
PIPE UP WITH SHUTOFF VALVE
PIPE UP AND DOWN
LOW PRESSURE STEAM WET
(FLOODED) CONDENSATE
SV
STEAM VENT
VENTURI FLOW METER
BASKET STRAINER
3-WAY CONTROL,
THERMOSTATIC MIXING
VALVE (SELF-CONTAINED)
FIN TUBE RADIATION
FINTUBE ENCLOSURE OR
PRESSURE RELIEF VALVE
THERMOSTATIC STEAM TRAP
FLOAT AND THERMOSTATIC
BUCKET STEAM TRAP
EQUIPMENT
MOTORIZED MODULATING VALVE
M
BACK DRAFT DAMPER
HOT GLYCOL RETURN
HOT GLYCOL SUPPLY
(UP / TOWARDS)
(DOWN / AWAY)
(UP / TOWARDS)
(DOWN / AWAY)
BS BURNER SHUT OFFDUCT BREAK
PIPE BREAK STEAM TRAP
ROOFTOP HOOD
(RELIEF)
(INTAKE)
TRIPLE DUTY VALVE
FLANGE CONNECTION
EXPANSION JOINT
UV DRAFTSTOP
VB
VACUUM BREAKER
(INSTALL STEM VERTICAL)
Project Location Map
1
1 Alice Cook House
2 Flora Rose House
2
West Campus Dining Exhaust System Remediation
Alice Cook and Flora Rose Houses
36
G0060
G0066
G0061
199
G12
133
G0063
693
G0065
65
G0067
515
G0001
180
G0041
282
G0062
433
G0069
42
G0068
42
83
G11
G03
G0040
477
G05
G07
G09
120
115
120
G0020
55
G04
185
G02
139
41
G01
764
UP
1136
765
DN
221
G0071
G0070
G0072
3,245
166
107
UP
UP
UP
DN
177
105
38
10041
10060
229
109
222
109A
109B
21
10040
10063
36
10064
72
10020
163
10021
164
141
110
201
10002
500
106
43
10067
116
56
10047
331
10065
39
10066
85
7
7
16
112A
219
202
115
130
115A
115B
97
117
249
103
124
10042
104
269
10001
194
UP
DN
102E
65
102B
156 BA
11
102C
131
CA
20
10003
102D
52
102
311 102A
180
101C
177
CA
17
101D
52 53
101B
212
101E
47
101
563
101A
153
60
21
UP
UP
UP
113
F
106A
112C
112D
165
1,514
10004
20
101F
10044
2,087
50
112B
1,873 4,263
112
10071
MAILBOXES
UP
FIRE
PLACE
108
388
1
M101
298
210
ROOF
284
204
20061
58
20001
194
UP
DN
105
204A
AA
8
102
204B
BA
8
102
204C
CA
8
186
204D
204E
85
DA
8
DB
8
20040
102
210A
AA
8
102
210B
BA
8
102
210C
CA
8 191
210D
DA
8
DB
8
208
68
184
212
A
8
B
8
133
214A
AA
8
212C
72
323
214
B
6
214C
54
36
20064
20021
20066
59
20067
159
222
301
429
20068
20020
20069
510
20070
37
59
223
98
65
20065
20063
74
20002
166
208A
29
100
219
A
8
100
217
A
8
100
215
A
8
100
213
A
8
100
211
A
8
100
209
A
8
121
207
A
8
206
89
210E
85
180
205
A
8
B
8
20062
37
296
202
102
202A
AA
8
102
202B
BA
8
102
202C
CA
8
191
202D
DA
8
DB
8
122
201D
DA
8
249
201
102
201A
AA
8
102
201B
BA
8
202
201C
CA
8
CB
8
202E
85
85
201E
DN
DN
20060
36
DN
UP
203
89
1,236
20040
145
133
222A
222B
222C
65
48
48
307
222D
20043
2004242578
O
P
E
N
20071
20x8 DW EA UP
40x20 EA UP
36x36 EA UP
ADD 24X24 FIRE RATED ACCESS DOOR
IN CHASE WALL IN ROOM 20064 AND
ACCESS DOOR IN DUCTS.
PROVIDE PENETRATION FIRESTOPPING
TO MAINTAIN 2 HOUR FIRE SEPARATION
AT JOINT WHERE WALLS MEET PLANK
CEILING DECK, ENTIRE ROOM
PERIMETER, APPROX. 50LF
501
ROOF
ROOF
DN
50002
63
6,778
OP
E
N
2
M101
109
423A
40060
298
410
284
404
40061
45
40001
105
404A
AA
8
102
404B
BA
8
102
404C
CA
8
186
404D
404E
85
DA
8
DB
8
40040
102
410A
AA
8
100
409
A
8
121
407
A
8
410E
85
180
405
A
8
B
8
40062
37
296
402
102
402A
AA
8
102
402B
BA
8
102
402C
CA
8
191
402D
DA
8
DB
8
122
401D
DA
8
249
401
102
401A
AA
8
102
401B
BA
8
203
401C
CA
8
CB
8
402E
85
85
401E
36
102
410B
BA
8
102
410C
CA
8 191
410D
DA
8
DB
8
408
68
184
412
A
8
B
8
129
414A
AA
8
414B
63
330
414
C
6
40
40064
72
40002
166
408A
32
100
419
A
8
100
417
A
8
100
415
A
8
100
413
A
8
100
411
A
8
406
89
421
422
403
423
318
403
89
D
10
40065
77
422A
96
AA
8
422B
BA
8
96
422C
CA
8
96
422D
DA
8
96 EA
8
422E
96 422F
FA
8
FB
8
42
3
F
15
42
3
G
85
42
2
H
85
42
2
G
85
423E
197
EA
8 EB
8
102
423C
CA
8
104
423D
CA
8
UP
DN
DN
102
423B
BA
8
AA
8
60
228
1,252
40040
O
P
E
N
20x8 DW EA UP
40x20 EA UP
36x36 EA UP
ADD 24X24 FIRE RATED ACCESS
DOOR IN CHASE WALL IN ROOM
40064 AND ACCESS DOOR IN
DUCTS.
PROVIDE PENETRATION FIRESTOPPING
TO MAINTAIN 2 HOUR FIRE SEPARATION
AT JOINT WHERE WALLS MEET PLANK
CEILING DECK, ENTIRE ROOM
PERIMETER, APPROX. 50LF
215
323A
ROOF
30060
298
310
284
304
30061
40
30001
194
105
304A
AA
8
102
304B
BA
8
102
304C
CA
8
186
304D
304E
85
DA
8
DB
8
30040
102
310A
AA
8
100
309
A
8
121
307
A
8
310E
85
180
305
A
8
B
8
30062
37
296
302
102
302A
AA
8
102
302B
BA
8
102
302C
CA
8
191
302D
DA
8
DB
8
122
301D
DA
8
249
301
102
301A
AA
8
102
301B
BA
8
202
301C
CA
8
CB
8
302E
85
85
301E
36
102
310B
BA
8
102
310C
CA
8 191
310D
DA
8
DB
8
308
68
184
312
A
8
B
8
129
314A
AA
8
314B
63
330
314
C
6
46
30064
72
30002
166
308A
29
100
319
A
8
100
317
A
8
100
315
A
8
100
313
A
8
100
311
A
8
306
89
321
322
403
323
317
303
89
D
10
30065
77
322A
96
AA
8
322B
BA
8
96
322C
CA
8
96
322D
DA
8
96 EA
8
322E
96 322F
FA
8
FB
8
32
3
E
15
32
3
F
85
32
2
H
85
32
2
G
85
323D
197
DA
8 DB
8
AA
8
AB
8
102
323B
BA
8
104
323C
CA
8
UP
DNUP
DN
228
1,251
30040
OP
E
N
20x8 DW EA UP
40x20 EA UP
36x36 EA UP
REPLACE UNRATED ACCESS
DOOR WITH 90 MINUTE FIRE
RATED 24x24 ACCESS DOOR
VIF.
PROVIDE PENETRATION FIRESTOPPING
TO MAINTAIN 2 HOUR FIRE SEPARATION
AT JOINT WHERE WALLS MEET PLANK
CEILING DECK, ENTIRE ROOM
PERIMETER, APPROX. 50LF
168
1M02J
1M02L
51
1M02H
37
1M02K
21
1M02G
56
9
61
1M02M
OPEN TO
BELOW
OPEN TO
BELOW
OPEN TO
BELOW
214
1M01G
133
1M01L
12
1M01P
86 1M01K
212
251M01M
64
1M01H
45
1M01F
36
DN
DN
UP
DN
193
1M0001
1M02N
LA
KA
1
A2 43 5 6 7 8
BCD9 10 11 12 13 14 15 16 17
EFGHINNMLJIHGFEDCBADescription:Rev. No.:Date:
Drawing No.:Drawn by:MLKJKCLEAR SOLUTIONS
complex world
Tetra Tech Engineers, Architects
& Landscape Architects, P.C.
Alice Cook House
Key Plans
RHM/pgm
M100
1 Ground Floor Key Plan
1/32" = 1'-0"
2 First Floor Key Plan
1/32" = 1'-0"
3 Second Floor Key Plan
1/32" = 1'-0"
5 Third Floor Key Plan
1/32" = 1'-0"
6 Fourth Floor Key Plan
1/32" = 1'-0"
7 Attic Floor Key Plan
1/32" = 1'-0"
4 First Floor Mezzanine Key Plan
1/32" = 1'-0"
Project No.:
Date:
2/15/19
08249-15002
Key Plan
NTS
Remediation Work at: Alice Cook, Carl
Becker, William Keeton, Flora Rose and
Hans Bethe Houses
Cornell University
Ithaca, New York
N
1.THE FOLLOWING GENERAL NOTES APPLY TO ALL "M" SERIES DRAWINGS.
2.REFER TO ALL CONTRACT DOCUMENTS; DRAWINGS AND SPECIFICATIONS, FOR
DETAILED STANDARDS AND REQUIREMENTS.
3.REPORT UNSAFE OR UNSATISFACTORY CONDITIONS IN WRITING TO OWNER AND
ARCHITECT AND RESOLVE ISSUES BEFORE PROCEEDING.
4.WORK INCLUDES ALL LABOR AND MATERIALS REQUIRED TO PROVIDE COMPLETE
WORKING SYSTEMS.
5.COORDINATE PHASING REQUIREMENTS AT JOB MEETINGS AND ON WORK
SCHEDULES.
6.DO NOT SCALE DRAWINGS. PIPING AND DUCTWORK ARE SHOWN
DIAGRAMMATICALLY. IT IS NOT POSSIBLE TO SHOW EVERY TRANSITION, FITTING,
ASPECT RATIO CHANGE, ETC..; PROVIDE AS REQUIRED TO FIT WITHIN STRUCTURAL
CONSTRAINTS. EXAMINE CONDITIONS UNDER WHICH THE WORK IS TO BE
PERFORMED AND VERIFY ALL ACCESS, LOCATIONS, DIMENSIONS, ARRANGEMENTS,
ELECTRICAL CHARACTERISTICS, AND INTERFERENCE IN THE FIELD PRIOR TO BID.
7.VERIFY EXTENT OF CEILING WORK SHOWN ELSEWHERE IN THE CONTRACT
DOCUMENTS. PROVIDE FOR ADDITIONAL CEILING SYSTEM REMOVAL, PROTECTION,
AND REINSTALLATION AS REQUIRED FOR CONTRACT WORK.
8.DEMOLITION DRAWINGS SHOW THE GENERAL SCOPE OF ITEMS AND SYSTEMS TO BE
REMOVED. IT IS NOT THE INTENT TO SHOW ALL ITEMS TO BE REMOVED. FIELD VERIFY
AND REMOVE ALL ASSOCIATED ITEMS BACK TO POINT OF CONTINUED SERVICE,
UNLESS OTHERWISE NOTED. VERIFY WHAT ALL EQUIPMENT SERVES PRIOR TO
REMOVAL.
9.GIVE ALL REMOVED EQUIPMENT TO THE OWNER. DELIVER ON SITE WHERE
DESIGNATED BY THE OWNER. PROMPTLY REMOVE FROM THE SITE AND LEGALLY
DISPOSE OF ANY SUCH ITEMS DECLINED BY OWNER.
10.IF UNANTICIPATED MECHANICAL, ELECTRICAL, OR STRUCTURAL CONFLICTS ARE
ENCOUNTERED, INVESTIGATE AND REPORT BOTH NATURE AND EXTENT OF THE
CONFLICT. RE-ROUTE WORK OR EXISTING ELECTRICAL OR PLUMBING AS REQUIRED.
11.CUT, DRILL, OR OTHERWISE CREATE OPENINGS AS NEATLY AS POSSIBLE, AS REQUIRED
FOR THE INDICATED CONTRACT WORK. PROVIDE SUPPORT AS REQUIRED FOR AND
USE METHODS LEAST LIKELY TO DAMAGE ELEMENTS TO REMAIN. PRIOR TO WORK,
VERIFY LOCATIONS OF ALL STRUCTURAL MEMBERS INCLUDING CROSS BRACING,
ELECTRICAL WIRING, PLUMBING, ETC. PROMPTLY NOTIFY ARCHITECT OF ANY
CONFLICTS. DO NOT CUT ANY STRUCTURAL MEMBERS OR OTHER SERVICES UNTIL
SPECIFICALLY DIRECTED TO DO SO. PENDING RECEIPT OF DIRECTIVE, REARRANGE
SCHEDULE AS NECESSARY TO CONTINUE OVERALL JOB PROGRESS WITHOUT DELAY.
12.PATCH ALL DISTURBANCES RESULTING FROM DEMOLITION OR NEW WORK TO MATCH
SURROUNDING SURFACES. PATCH FOLLOWING DEMOLITION, AND AGAIN
FOLLOWING CONTRACT WORK. WHERE HOLES REMAIN FROM REMOVALS, INFILL
AND PATCH TO MATCH UNLESS HOLE IS TO BE REUSED.
13.PROTECT ALL CONTRACT EQUIPMENT, ELEMENTS TO REMAIN, OWNER'S
BELONGINGS, AND EQUIPMENT TO BE REUSED OR RETAINED BY OWNER DURING ALL
CONTRACT WORK. AT NO ADDITIONAL COST TO OWNER REPAIR OR REPLACE ITEMS
WHICH ARE DAMAGED.
14.THOROUGHLY CLEAN FOLLOWING DEMOLITION AND BEFORE BEGINNING CONTRACT
INSTALLATIONS. THOROUGHLY CLEAN AGAIN DURING AND FOLLOWING CONTRACT
WORK AS REQUIRED. LEAVE ALL WORK AREAS CLEANER THAN FOUND. LEGALLY
DISPOSE OF ALL CONSTRUCTION DEBRIS.
15.PROVIDE TEMPORARY PIPING, DUCT, HEAT, WEATHERPROOFING ETC.. TO SERVICES
TO REMAIN UNTIL PERMANENT INSTALLATIONS CAN BE MADE.
16.ALL EXCESS MATERIALS AND SCRAPS ARE CONTRACTOR'S PROPERTY. PROMPTLY
REMOVE FROM SITE UNLESS SPECIFICALLY DIRECTED OTHERWISE.
GENERAL NOTES:
1 Revised Per Addendum #2.
1
A2 43 5 6 7 8
BCD9 10 11 12 13 14 15 16 17
EFGHINNMLJIHGFEDCBADescription:Rev. No.:Date:
Drawing No.:Drawn by:MLKJKTetra Tech Engineers, Architects
& Landscape Architects, P.C.
Alice Cook House
Enlarged Plans and Details
RHM
M101
1 Partial First Floor Plan
1/8" = 1'-0"
2 Attic Plan
1/8" = 1'-0"
TO PREVENT DAMAGE
TO INSULATION,
PROVIDE THREE 1/2"
BAND STRAPS AT EACH
ACCESS DOOR TO
ALLOW REPEATED
INSULATION REMOVAL.
PROVIDE WORM
GEAR HOSE
CLAMPS SPOT
WELDED TO
BANDING FOR
STRAP REMOVAL
REMOVE EXISTING FIRE WRAP
INSULATION AND PINS SPOT
WELDED TO ACCESS DOORS.
PROVIDE NEW FIRE WRAP
INSULATION AS SPECIFIED BY
MANUFACTURER TO MAINTAIN
FIRE RATING. INSULATION
HELD IN PLACE BY REUSABLE
BAND CLAMPS.
TEE WITH FULL SIZE
CLEAN OUT. TYP 2
STREET ELBOW
UNION
DRAIN RESERVOIR
CONNECTION.
'5$,1 75$3
ASSEMBLY.
2"
NOTES:
2"
CASING
(-)
1. DRAIN PAN AT NEGATIVE STATIC PRESSURE
3/4" HOSE THREAD CONNECTION
WITH BRASS CAP.
5 Access Door Straps Detail
3 Grease Duct Drain Detail
6 Condensate Trap Detail
Project No.:
Date:
2/15/19
08249-15002
Key Plan
NTS
Remediation Work at: Alice Cook, Carl
Becker, William Keeton, Flora Rose and
Hans Bethe Houses
Cornell University
Ithaca, New York
EXTERNAL
FIRE WRAP
INSULATION
ACCESS DOOR
UNDER INSULATION
GREASE EXHAUST DUCT,
REFER TO CONTRACT
DWGS FOR SIZES AND
ARRANGEMENT
2 TIMES
INDIRECT
WASTE ID
7 Indirect Waste Air Gap Detail
EXG FLOOR DRAIN
OR FLOOR SINK
ANCHOR TO FLOOR
EXG FLOOR
PIPE STAND OFF W/ SPLIT
RING PIPE CLAMPS
INDIRECT WASTE
CLEAN KITCHEN COOKING EXHAUST DUCT ADJACENT TO WELDED
WORK, ALLOWING FOR WELDED DUCT REPAIRS WITH MINIMIZED
FIRE HAZARD. REMOVE INSULATION, ADD DRAIN COLLECTION
POINT AND REPAIR LEAKS IN DUCTWORK WITH A CONTINUOUS
LIQUID-TIGHT SS WELD MADE ON THE EXTERNAL SURFACE OF THE
DUCT SYSTEM. INSPECT AND TEST FOR LEAKS, AND RE-INSULATE
WITH FIRE RATED INSULATION COMPLETE.
PROVIDE 22X20 DUCT MOUNTED ACCESS DOOR WHERE DUCT SIZE
ALLOWS. DOOR DIMENSIONS TO BE NOT CLOSER THAN ONE INCH
TO DUCT EDGE; ELONGATE DOOR ASPECT RATIO AS REQUIRED
FOR DUCT NARROWER THAN 14 INCHES.TOOL FREE ACCESS IS NOT
REQUIRED.
PROVIDE GREASE DUCT COLLECTION RESERVOIR AT GREASE DUCT
ACCESS DOOR LOCATION PER DETAIL 3/M101 (FIELD VERIFY
ACCESS DOOR LOCATION).
INSPECT EXISTING SS DISHWASHER DUCTWORK FOR LEAKS
AND MAKE REPAIRS NECESSARY TO PRODUCE A WATER TIGHT
EXHAUST SYSTEM.
COORDINATE PIPE ROUTE WITH EQUIPMENT IN ROOM. MUST NOT
PRESENT TRIPPING HAZARD.
PROVIDE CONDENSATE COLLECTION RESERVOIR AT DISHWASHER
ACCESS DOOR LOCATION PER DETAIL 4/M101 (FIELD VERIFY
ACCESS DOOR LOCATION).
1
2
3
4
1.FOR GENERAL NOTES, SEE M100.
GENERAL NOTES:
KEYED NOTES:
PROVIDE 3/4" S.S
NIPPLE WELDED TO
RESERVOIR LOW POINT
AND DRAIN WITH BALL
VALVE AND CAPPED
HOSE THREAD
CONNECTION.
PROPERLY CLEAN
EXISTING GREASE
DUCT TO ALLOW
FOR WELDING OF
GREASE
COLLECTION
RESERVOIR TO
THE BOTTOM OF
DUCT WHERE
INDICATED
FULL WIDTH OF DUCT x 12"
LONG X 1-1/2" MIN DEEP
GREASE COLLECTION
RESERVOIR. SLOPE TO
ACCESSIBLE SIDE OF DUCT
WITH A LOW POINT DRAIN.1-1/2" MINFULLY WELD GREASE
COLLECTION RESERVOIR
TO BOTTOM OF GREASE
DUCT. FIRE WRAP DUCT
AND GREASE COLLECTION
RESERVOIR
EXTERNAL FIRE
WRAP INSULATION
GREASE EXHAUST DUCT,
REFER TO CONTRACT
DWGS FOR SIZES AND
ARRANGEMENT
VALVE
TAG VALVE
NORMALLY
OPEN (N.O.)
5
1 Revised Per Addendum #2.
BALL VALVE
UNION
SET GREASE
INTERCEPTOR IN
FLOOR
MAINTAIN 1"
MIN. GAP AT
FLOOR DRAIN
EXG F.D.
V.I.F.
ANCHOR 1" X 1" ANGLE IRON TO FLOOR
AROUND PERIMETER OF INTERCEPTOR
W/ EPOXY ANCHORS AT 12" OC. ALL
DIRECTIONS.
PAINT ANGLES
SAFETY YELLOW
'5$,1 75$3
ASSEMBLY.
3/4" HOSE THREAD CONNECTION
WITH BRASS CAP.
CLEAN EXISTING DRAIN FITTING
INLET
FAN HOUSING
OUTLET
REDUCING STREET
ELBOW
9 Grease Interceptor Detail
NOT TO SCALE
BALL VALVE TYP. 2
1 1/4" THREADED
STEEL PIPE
INLET
FAN HOUSING
OUTLET
8 Grease Reservoir
NOT TO SCALE
FORMED OR WELDED
STAINLESS STEEL
FLANGED RESERVOIR
TO FIT DOOR FLANGES
BOLTED AND GASKETED
RESERVOIR TOP EQUAL TO
DUCTMATE ULTIMATE DOOR II
12"x10" MINIMUM
EXTERNAL FIRE
WRAP INSULATION
TANK INLET
COUPLING
WELDED TO
RESERVOIR
6" MIN
8" MIN
UNION
CLOSE NIPPLES
IS WATERTIGHT
VERIFY EXHAUST DUCTWORK
PIPE TO GREASE INTERCEPTOR DRAIN
PROVIDE FULL WIDTH OF
DUCT X 12" WIDE X 1-1/2"
MIN DEEP CONDENSATE
COLLECTION RESERVOIR
AND LOW POINT DRAIN ON
WELDED STAINLESS
STEEL DISHWASHER
DUCTWORK DRAIN VALVE
ON BOTTOM OF DUCT
1 1/4"
12"
(TYP)
CONDENSATE TRAP (TYP). SEE
DETAIL 6/M101
4 Bottom of Dishwasher Duct Drain Detail
EXTERNAL INSULATION
EXHAUST DUCT, REFER TO CONTRACT
DWGS FOR SIZES AND ARRANGEMENTS
PROVIDE EXTERNAL FIRE RATED INSULATION
ON ALL SURFACES OF FAN AIRWAYS, PIPING
AND GREASE RESERVOIR
6
DA
DB
236D
CA
BA
236B
236A
AA
236236E
EA
233D
DBDA
CA
233C BA
233B AA
233A
233
231
AA
231A
BA
231B
231C
CA 231D
DA
DB
A
B
221
217
A
B
20041
20042
20061
A B
215
211
A
209C
A
209
BA
209B
205
20063
205A
AA 205B
BA 205C
CA
DB
DA
205D
201DDA
201
201E
201C
CB
CA
BA
201B
AA
201A
20001204
A
A
206
208
A210
A
212
A
20065235
20002
236C
226
224
A
222
A
220
A
218
A
A236F
233E
20064
231E
223
219
207
20062
205E
UP
DN
UP
DN
FILL GAP ALONG JOINT
BETWEEN PLANKS TO
MAINTAIN 2 HOUR FIRE RATING
COVER AND FILL EXPOSED
CORES OF PLANK AT FLOOR
OPENING WITH PENETRATION
FIRESTOPPING TO MAINTAIN 2
HOUR FIRE RATING
PROVIDE PENETRATION FIRESTOPPING
TO MAINTAIN 2 HOUR FIRE SEPARATION
AT JOINT WHERE WALLS MEET PLANK
CEILING DECK, ENTIRE ROOM
PERIMETER, APPROX. 50LF
336D
DB
DA
336E EA
333D
DA DB
CA
333C
333B
BA
AA
333A 333
30065335
336
CA
BA
AA
336A
336B
336C
30002
A
326
324
A
322
A
320
A
318
A
316
A
323
30064
A
310 A
308 A
306
304
A
301
30001
DA 301D
301C
CA
CBBA
301B
AA
301A
DA
DB
305DCA
305CBA
305BAA
305A
305
BA
309B
309
A
30042
311
A
A B
315
317
A
B
A
B
321DB
DA
331D
AA
331A
331B
BA 331C
CA
331
30041
30061
331E
319
309C
30063 30062
305E
301E
307
333E
336F
DN
UP
DN
UP
FILL GAP ALONG JOINT
BETWEEN PLANKS TO
MAINTAIN 2 HOUR FIRE RATING
COVER AND FILL EXPOSED
CORES OF PLANK AT FLOOR
OPENING WITH PENETRATION
FIRESTOPPING TO MAINTAIN 2
HOUR FIRE RATING
PROVIDE PENETRATION FIRESTOPPING
TO MAINTAIN 2 HOUR FIRE SEPARATION
AT JOINT WHERE WALLS MEET PLANK
CEILING DECK, ENTIRE ROOM
PERIMETER, APPROX. 50LF
2
M401
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
2
2
2
2
2 2
2
2
142D
DB
DA
142EEA
142C
CA
142B
BA
142A
AA
142
10002
141 10072 10046
DA DB
139D
126
121
120
122
10020
123
125
10044
10045
110
CA
139C BA
139B AA
139A
139
137
A
134 A
132
A
130
10070
137A
137B
137C
137D
131
10047
EA EB
137E
111B
BA
10042
111
111A
105
10043
AA
105A
BA
105B
105C
CA
DA
105D
105E
EB
EA
101DDA
101C
CA
CBBA
101B
AA
101A
101
101E108
106
A
A 10062
103
10063
10001
10061
DA
CA
BA
AA
137F
142F
139E 133
DN
DN
DN DN
UP
DN
UP
105FBOOK SHELVESBOOK SHELVESBOOK SHELVESGREEN R
O
O
F
GREEN R
O
O
F
C
FILL GAP ALONG JOINT
BETWEEN PLANKS TO
MAINTAIN 2 HOUR FIRE RATING
COVER AND FILL EXPOSED
CORES OF PLANK AT FLOOR
OPENING WITH PENETRATION
FIRESTOPPING TO MAINTAIN 2
HOUR FIRE RATING
PROVIDE PENETRATION FIRESTOPPING
TO MAINTAIN 2 HOUR FIRE SEPARATION
AT JOINT WHERE WALLS MEET PLANK
CEILING DECK, ENTIRE ROOM
PERIMETER, APPROX. 50LF
1
M401
DN
UP DNDN
UP
UP
G0001
G42
D
C B
BA
A
G0046
G0065
G37A
G33
G37 AA G37B
BA
CA
G37C
G37D
DA G37E
EB
EA
G0045
G30G32
AG34
A
G24
G24A
G0044
G0061
G0043
G27
G0041
G08
G06
G02A
G04
G0068
G0003
G0049
G21
G11
G22
G09
G01C
G0042
G02B
G02
G01B
G01A
G0064
G0060
G13
G13AMAILMAILMAILMAILMAIL
G0021
G0020
UPUP
DN
G37F
G0062
G42E
G01
G39
G41G42F
G0066
DECK
PLANTER
G0002
UP
FA
A
A
G
B
G0063
B
G01D
46
B0061 71
B0042
B0043
77
B0078
89
B0076
501
B0079 75
B0077
215
B19
146
B0075 233
B0073
1106
B0071
367
B0074
171
B0070
181
B11
3796
B0066
211
B09
107
B05 60
B03
B0063
75
1866
B0041
53
B0060
57
B0062
176
B02
B0066 CONT'D
311
B0067
B0021
118
128
B0020
54
B19A
45
B19B35
B19C33
B19D
65
B19E
946
B0043
CONT'D
SHAFT
SHAFT
UP
UP
59
B0064
ELEV 659'-0"
MAIN BASEMENT
ELEV 652'-0"
LOWER BASEMENT
182
B0065
88
B0068
B22
62 85
B22A
159
B0002
161
B0001
28
SG0060
30
SG42C
339
SG42
SG42A
163
202
SG42E
44
SG42B
12
SG42D
74
7
DA
15
EA
SG42G
37
14
AA
1
A2 43 5 6 7 8
BCD9 10 11 12 13 14 15 16 17
EFGHINNMLJIHGFEDCBADescription:Rev. No.:Date:
Drawing No.:Drawn by:MLKJKCLEAR SOLUTIONS
complex world
Tetra Tech Engineers, Architects
& Landscape Architects, P.C.
Flora Rose House
Key Plans
RHM
M400
1 Basement Key Plan
1/32" = 1'-0"
3 Ground Floor Key Plan
1/32" = 1'-0"6 Third Floor Key Plan
1/32" = 1'-0"
5 Second Floor Key Plan
1/32" = 1'-0"
7 Attic Key Plan
1/32" = 1'-0"4 First Floor Key Plan
1/32" = 1'-0"
2 Sub Basement Key Plan
1/32" = 1'-0"
KEYED NOTES
TAPE AND FINISH WALL SURFACE SEPARATING MECHANICAL
SPACE FROM CORRIDOR AND STAIR.
FIRE CAULK FLOOR TO WALL SEAMS AND CEILING TO WALL SEAMS
SEPARATING MECHANICAL SPACE FROM CORRIDOR AND VARIOUS
ROOMS.
1.THE FOLLOWING GENERAL NOTES APPLY TO ALL "M" SERIES DRAWINGS.
2.REFER TO ALL CONTRACT DOCUMENTS; DRAWINGS AND SPECIFICATIONS, FOR
DETAILED STANDARDS AND REQUIREMENTS.
3.REPORT UNSAFE OR UNSATISFACTORY CONDITIONS IN WRITING TO OWNER AND
ARCHITECT AND RESOLVE ISSUES BEFORE PROCEEDING.
4.WORK INCLUDES ALL LABOR AND MATERIALS REQUIRED TO PROVIDE COMPLETE
WORKING SYSTEMS.
5.COORDINATE PHASING REQUIREMENTS AT JOB MEETINGS AND ON WORK
SCHEDULES.
6.DO NOT SCALE DRAWINGS. PIPING AND DUCTWORK ARE SHOWN
DIAGRAMMATICALLY. IT IS NOT POSSIBLE TO SHOW EVERY TRANSITION, FITTING,
ASPECT RATIO CHANGE, ETC..; PROVIDE AS REQUIRED TO FIT WITHIN STRUCTURAL
CONSTRAINTS. EXAMINE CONDITIONS UNDER WHICH THE WORK IS TO BE
PERFORMED AND VERIFY ALL ACCESS, LOCATIONS, DIMENSIONS, ARRANGEMENTS,
ELECTRICAL CHARACTERISTICS, AND INTERFERENCE IN THE FIELD PRIOR TO BID.
7.VERIFY EXTENT OF CEILING WORK SHOWN ELSEWHERE IN THE CONTRACT
DOCUMENTS. PROVIDE FOR ADDITIONAL CEILING SYSTEM REMOVAL, PROTECTION,
AND REINSTALLATION AS REQUIRED FOR CONTRACT WORK.
8.DEMOLITION DRAWINGS SHOW THE GENERAL SCOPE OF ITEMS AND SYSTEMS TO BE
REMOVED. IT IS NOT THE INTENT TO SHOW ALL ITEMS TO BE REMOVED. FIELD VERIFY
AND REMOVE ALL ASSOCIATED ITEMS BACK TO POINT OF CONTINUED SERVICE,
UNLESS OTHERWISE NOTED. VERIFY WHAT ALL EQUIPMENT SERVES PRIOR TO
REMOVAL.
9.GIVE ALL REMOVED EQUIPMENT TO THE OWNER. DELIVER ON SITE WHERE
DESIGNATED BY THE OWNER. PROMPTLY REMOVE FROM THE SITE AND LEGALLY
DISPOSE OF ANY SUCH ITEMS DECLINED BY OWNER.
10.IF UNANTICIPATED MECHANICAL, ELECTRICAL, OR STRUCTURAL CONFLICTS ARE
ENCOUNTERED, INVESTIGATE AND REPORT BOTH NATURE AND EXTENT OF THE
CONFLICT. RE-ROUTE WORK OR EXISTING ELECTRICAL OR PLUMBING AS REQUIRED.
11.CUT, DRILL, OR OTHERWISE CREATE OPENINGS AS NEATLY AS POSSIBLE, AS REQUIRED
FOR THE INDICATED CONTRACT WORK. PROVIDE SUPPORT AS REQUIRED FOR AND
USE METHODS LEAST LIKELY TO DAMAGE ELEMENTS TO REMAIN. PRIOR TO WORK,
VERIFY LOCATIONS OF ALL STRUCTURAL MEMBERS INCLUDING CROSS BRACING,
ELECTRICAL WIRING, PLUMBING, ETC. PROMPTLY NOTIFY ARCHITECT OF ANY
CONFLICTS. DO NOT CUT ANY STRUCTURAL MEMBERS OR OTHER SERVICES UNTIL
SPECIFICALLY DIRECTED TO DO SO. PENDING RECEIPT OF DIRECTIVE, REARRANGE
SCHEDULE AS NECESSARY TO CONTINUE OVERALL JOB PROGRESS WITHOUT DELAY.
12.PATCH ALL DISTURBANCES RESULTING FROM DEMOLITION OR NEW WORK TO MATCH
SURROUNDING SURFACES. PATCH FOLLOWING DEMOLITION, AND AGAIN
FOLLOWING CONTRACT WORK. WHERE HOLES REMAIN FROM REMOVALS, INFILL
AND PATCH TO MATCH UNLESS HOLE IS TO BE REUSED.
13.PROTECT ALL CONTRACT EQUIPMENT, ELEMENTS TO REMAIN, OWNER'S
BELONGINGS, AND EQUIPMENT TO BE REUSED OR RETAINED BY OWNER DURING ALL
CONTRACT WORK. AT NO ADDITIONAL COST TO OWNER REPAIR OR REPLACE ITEMS
WHICH ARE DAMAGED.
14.THOROUGHLY CLEAN FOLLOWING DEMOLITION AND BEFORE BEGINNING CONTRACT
INSTALLATIONS. THOROUGHLY CLEAN AGAIN DURING AND FOLLOWING CONTRACT
WORK AS REQUIRED. LEAVE ALL WORK AREAS CLEANER THAN FOUND. LEGALLY
DISPOSE OF ALL CONSTRUCTION DEBRIS.
15.PROVIDE TEMPORARY PIPING, DUCT, HEAT, WEATHERPROOFING ETC.. TO SERVICES
TO REMAIN UNTIL PERMANENT INSTALLATIONS CAN BE MADE.
16.ALL EXCESS MATERIALS AND SCRAPS ARE CONTRACTOR'S PROPERTY. PROMPTLY
REMOVE FROM SITE UNLESS SPECIFICALLY DIRECTED OTHERWISE.
GENERAL NOTES:
1
2
Project No.:
Date:
2/15/19
08249-15002
Key Plan
NTS
Remediation Work at: Alice Cook, Carl
Becker, William Keeton, Flora Rose and
Hans Bethe Houses
Cornell University
Ithaca, New York N
EXG KEF-1
EXG KEF-2
EXG KEF-4
EXG KEF-3
EXG
30x10 EA
EXG 20x10 EA
EXG
24x10 EA
EXG
24x10 EA
GREASE INTERCEPTOR
ON STAND NEAR STACK.
SEE 12/M401
5
5
8
1
1
7
7
EXG EF-8
7
CONNECT TO FLOOR
DRAIN AT LOCATION
SHOWN. SEE 12/M401MAILMAILMAIL G0001
G0061
G0043
G27
G0049
G21
G11
G22
G09
G01C
G0042
G02B
G01B
G01A
G0064
G0060G13
G13AG0021
G0020
G0062
G01
G0063
G01D
EXG 12X12 EA
EXG 12x12 EA
EXG 20x10 EA
EXG 20x10 EA
EXG 20x10 EA UP
EXG 30x10 EA UP
EXG 12x9 EA UP
EXG 24x10 EA UP
EXG 30x10 EA UP
EXG 24x10 EA
EXG 30x10 EA
EXG 30x10 EA
EXG 12x9 EA
EXG 8x6 EA
EXG 30x10 EA
EXG ACCESS DOOR
(V.I.F. TYP)
INSTALL LOW POINT DRAINS ON EA
DUCTWORK AS SHOWN IN DETAIL 4/M401.
PIPE 1-1/4" CD TO EXG FLOOR SINK
LOCATED UNDER THREE COMPARTMENT
SINK IN ROOM G-01C (VIF)
REPAIR LEAK IN DUCT AT
LOCATION SHOWN. REMOVE
WET INSULATION AS REQUIRED
AND REPLACE APPROX. 15 SQ.FT.
4
1
1
13
3
3
3
1-1/4" CD
1-1/4" CD
56
PROVIDE 24" x 24" FIRE RATED ACCESS
DOOR IN CHASE WALL TO SERVICE
CONDENSATE TRAP
IW AT EXG FLOOR
SINK. SEE 9/M401
REPAIR LEAK IN DUCT AT
LOCATION SHOWN. REMOVE
WET INSULATION AS REQUIRED
AND REPLACE APPROX. 15 SQ.FT.
1
1
A2 43 5 6 7 8
BCD9 10 11 12 13 14 15 16 17
EFGHINNMLJIHGFEDCBADescription:Rev. No.:Date:
Drawing No.:Drawn by:MLKJKTetra Tech Engineers, Architects
& Landscape Architects, P.C.
Flora Rose House
Enlarged Plans and Details
RHM
M401
1 Partial Ground Floor Plan
1/8" = 1'-0"
2 Attic Plan
1/8" = 1'-0"
Project No.:
Date:
2/15/19
08249-15002
Key Plan
NTS
Remediation Work at: Alice Cook, Carl
Becker, William Keeton, Flora Rose and
Hans Bethe Houses
Cornell University
Ithaca, New York NTO PREVENT DAMAGE
TO INSULATION,
PROVIDE THREE 1/2"
BAND STRAPS AT EACH
ACCESS DOOR TO
ALLOW REPEATED
INSULATION REMOVAL.
PROVIDE WORM
GEAR HOSE
CLAMPS SPOT
WELDED TO
BANDING FOR
STRAP REMOVAL
REMOVE EXISTING FIRE WRAP
INSULATION AND PINS SPOT
WELDED TO ACCESS DOORS.
PROVIDE NEW FIRE WRAP
INSULATION AS SPECIFIED BY
MANUFACTURER TO MAINTAIN
FIRE RATING. INSULATION
HELD IN PLACE BY REUSABLE
BAND CLAMPS.
PROVIDE 3/4" DRAIN
WITH BALL VALVE AND
CAPPED HOSE THREAD
CONNECTION.
PROPERLY CLEAN
EXISTING GREASE
DUCT TO ALLOW
FOR WELDING OF
GREASE
COLLECTION
RESERVOIR TO
THE BOTTOM OF
DUCT WHERE
INDICATED
FULL WIDTH OF DUCT x 12"
LONG X 1-1/2" MIN DEEP
GREASE COLLECTION
RESERVOIR. SLOPE TO
ACCESSIBLE SIDE OF DUCT
WITH A LOW POINT DRAIN.1-1/2" MINFULLY WELD GREASE
COLLECTION RESERVOIR
TO BOTTOM OF GREASE
DUCT. FIRE WRAP DUCT
AND GREASE COLLECTION
RESERVOIR
DOOR BOTH SIDES
OPENING IN
FIRE RATED
WALL
REQUIRING OUT
OF WALL FIRE
DAMPER.
FIRE
RATED
WALL
DUCT SIZE
DUCTWORK, REFER
TO DRAWINGS FOR
14 GAUGE MINIMUM
TO WALL 6" OC ALL 4 SIDES.
RETAINING "ZEE", SECURE
EXTEND FIRE RATED INSULATION PAST
PLANE OF DAMPER. INSULATION TO BE
3M CS-195+ COMPOSITE OR EQUAL.
PROVIDE ACCESS
AWAY JOINT ALL
LISTED BREAK-
SIDES (TYP.)
7 Out of Wall Fire Damper
NOT TO SCALE
TO SPEC. SECTION 23 3300.
EQUAL TO DUCT SIZE SHOWN. REFER
TYPE "C" FIRE DAMPER WITH FREE AREA
TEE WITH FULL SIZE
CLEAN OUT. TYP 2
STREET ELBOW
UNION
DRAIN RESERVOIR
CONNECTION.
'5$,1 75$3
ASSEMBLY.
2"
NOTES:
2"
CASING
(-)
1. DRAIN PAN AT NEGATIVE STATIC PRESSURE
3/4" HOSE THREAD CONNECTION
WITH BRASS CAP.
5 Access Door Straps Detail
NOT TO SCALE
3 Grease Duct Drain Detail
NOT TO SCALE
6 Condensate Trap Detail
NOT TO SCALE
EXTERNAL
FIRE WRAP
INSULATION
ACCESS DOOR
UNDER INSULATION
GREASE EXHAUST DUCT,
REFER TO CONTRACT
DWGS FOR SIZES AND
ARRANGEMENT
EXTERNAL FIRE
WRAP INSULATION
GREASE EXHAUST DUCT,
REFER TO CONTRACT
DWGS FOR SIZES AND
ARRANGEMENT
2 TIMES
INDIRECT
WASTE ID
9 Indirect Waste Air Gap Detail
NOT TO SCALE 221316-04aEXG FLOOR DRAIN
OR FLOOR SINK
ANCHOR TO FLOOR
EXG FLOOR
PIPE STAND OFF W/ SPLIT
RING PIPE CLAMPS
INDIRECT WASTE
CLEAN KITCHEN COOKING EXHAUST DUCT ADJACENT TO WELDED
WORK, ALLOWING FOR WELDED DUCT REPAIRS WITH MINIMIZED FIRE
HAZARD. REMOVE INSULATION, ADD DRAIN COLLECTION POINT AND
REPAIR LEAKS IN DUCTWORK WITH A CONTINUOUS LIQUID-TIGHT SS
WELD MADE ON THE EXTERNAL SURFACE OF THE DUCT SYSTEM.
INSPECT AND TEST FOR LEAKS, AND RE-INSULATE WITH FIRE RATED
INSULATION COMPLETE.
APPLY 2-HOUR RATED FIRE STOPPING TO FILL GAPS BETWEEN
DUCTWORK AND PENETRATION AT FLOOR LEVEL.
PROVIDE GREASE DUCT COLLECTION AT GREASE DUCT ACCESS
DOOR LOCATION PER DETAIL 3/M401 (FIELD VERIFY
ACCESS DOOR LOCATION).
INSPECT EXISTING SS DISHWASHER DUCTWORK FOR LEAKS
AND MAKE REPAIRS NECESSARY TO PRODUCE A WATER TIGHT
EXHAUST SYSTEM.
PROVIDE 22X20 DUCT MOUNTED ACCESS DOOR WHERE DUCT SIZE
ALLOWS. DOOR DIMENSIONS TO BE NOT CLOSER THAN ONE INCH TO
DUCT EDGE; ELONGATE DOOR ASPECT RATIO AS REQUIRED FOR
DUCT NARROWER THAN 14 INCHES. TOOL FREE ACCESS NOT
REQUIRED.
PROVIDE DISHWASHER CONDENSATE COLLECTION DRAINS WITH SS
FIRE/SMOKE DAMPER. REFER TO DETAIL 4/M401 AND 7/M401.
CONNECT DAMPER TO EXISTING FIRE ALARM SYSTEM, PROVIDE ALL
REQUIRED DEVICES AND WIRING AS NECESSARY, REFER TO DETAIL
11/M401 FOR ADDITIONAL INFORMATION.
DISASSEMBLE EXISTING EXHAUST FANS AND CLEAN TO BE FREE OF
GREASE REASSEMBLE WITH MANUFACTURER RECOMMENDED GASKETS TO
MAKE FANS GREASE TIGHT. INSULATE WITH FIRE - RATED INSULATION.
(TYP). PROVIDE A 1-1/4" DRAIN AT THE BOTTOM SIDE OF THE FAN
HOUSING PIPE TO SEALED INSULATED RESERVOIR. SEE 10/M401.
FIELD VERIFY LOCATION AND COORDINATE WITH OWNER PRIOR TO
INSTALLATION.
1
2
3
4
5
6
7
1.FOR GENERAL NOTES, SEE M400.
GENERAL NOTES:
KEYED NOTES:
VALVE
TAG VALVE
NORMALLY
OPEN (N.O.)
IS WATERTIGHT
VERIFY EXHAUST DUCTWORK
PIPE TO GREASE INTERCEPTOR DRAIN LOCATED
IN THE BASEMENT SEE DETAIL 13/M401
PROVIDE 12" WIDE X 1-1/2"
MIN DEEP CONDENSATE
COLLECTION RESERVOIR
AND LOW POINT DRAIN ON
WELDED STAINLESS
STEEL DISHWASHER
DUCTWORK DRAIN VALVE
ON BOTTOM OF DUCT
EXISTING 2HR
RATED WALL
1 1/4"
STAINLESS STEEL OUT OF
PLANE OF WALL FIRE DAMPER
AT 2HR RATED WALL
12"
(TYP)
CONDENSATE
TRAP (TYP). SEE
DETAIL 6/M401
4 Bottom of Dishwasher Duct Drain Detail
NOT TO SCALE
EXTERNAL INSULATION
EXHAUST DUCT, REFER TO CONTRACT
DWGS FOR SIZES AND ARRANGEMENTS
8
11 FIRE ALARM WIRING DIAGRAM
NOT TO SCALE
S D
EXISTING FIRE ALARM CONTROL PANEL.
MODIFY/REPROGRAM PANEL AS REQUIRED FOR SMOKE
DAMPER OPERATION.
S DSD
FIRE ALARM ADDRESSABLE RELAY
REMOTE TEST/MONITORING
STATION, TYPICAL.
WIRING PER
MANUFACTURERS
RECOMMENDATIONS.
WIRING PER
MANUFACTURERS
RECOMMENDATIONS.
120V
SMOKE DAMPER MOTOR,
TYPICAL WIRING FOR
EACH MOTOR
DUCT SMOKE DETECTOR
INSTALLED WITHIN FIVE
(5) FEET OF SMOKE
DAMPER, TYPICAL.
RTS RTSRTS
DR
1 Revised Per Addendum #2.
BALL VALVE TYP. 2
1 1/4" THREADED
STEEL PIPE
INLET
FAN HOUSING
10 Grease Reservoir
NOT TO SCALE
FORMED OR WELDED
STAINLESS STEEL
FLANGED RESERVOIR
TO FIT DOOR FLANGES
BOLTED AND GASKETED
RESERVOIR TOP EQUAL TO
DUCTMATE ULTIMATE DOOR II
12"x10" MINIMUM
EXTERNAL FIRE
WRAP INSULATION
TANK INLET
COUPLING
WELDED TO
RESERVOIR
6" MIN
8" MIN
UNION
CLOSE NIPPLES
PROVIDE EXTERNAL FIRE RATED INSULATION
ON ALL SURFACES OF FAN AIRWAYS, PIPING
AND GREASE RESERVOIR
BALL VALVE
UNION
SET GREASE
INTERCEPTOR IN
FLOOR
MAINTAIN 1"
MIN. GAP AT
FLOOR DRAIN
EXG F.D.
V.I.F.
ANCHOR 1" X 1" ANGLE IRON TO FLOOR
AROUND PERIMETER OF INTERCEPTOR
W/ EPOXY ANCHORS AT 12" OC. ALL
DIRECTIONS.
PAINT ANGLES
SAFETY YELLOW
'5$,1 75$3
ASSEMBLY.
3/4" HOSE THREAD CONNECTION
WITH BRASS CAP.
CLEAN EXISTING DRAIN FITTING
INLET
FAN HOUSING
OUTLET
REDUCING STREET
ELBOW
12 Grease Interceptor Detail
NOT TO SCALE