HomeMy WebLinkAboutMorill Hall - Generator ReplacementPHASE A
4) 350 KCMIL & (1) 2 AWG G. IN
EXISTING " CONDUIT.
EXISTING LOAD BANK
CONNECTION BOX.
(4) 350 KCMIL & (1) 2 AWG G.
IN 3" RGS.
PHASE C
KROCH SUB.
(1 SET) 500 CU —1
(1 SET) 500 CU
LOAD BANK
REMOTE
CONTROLLER.
OOA
KROCH LIBRARY GENERATOR RM. 100UP.
EXISTING EMERGENCY GENERATOR,
CATERPILLAR, 500 KW/625 KVA,
480V - 752 FLA.
500A
N
Iseeeeemsecceemameourace
PANEL E4D,
600A MLO,
480Y/277V.
(2 SETS) 350 AL
ATS -E, 600A,
/ 480V,
EM/STTANDBY.
(1 SET) 10 CU
30A
CONTROLLER.
800A MCB.
(3 SETS) 400 AL
EMERGENCY WIREWAY
T-2, 15 KVA,
480V PRIMARY,
208V SECONDARY.
400 AL TYPICAL FOR
PHASE A, B, C, & N.
TO GENERATOR MAIN
CIRCUIT BREAKER.
GROUND BAR LOCATED INSIDE
OF EMERGENCY WIREWAY.
MULTI -TAP CONNECTOR
(TYPICAL).
400A
A ATS -E2
TO GENERATOR MAIN „—.
CIRCUIT BREAKER.
TO GENERATOR MAIN
CIRCUIT BREAKER.
TO GENERATOR MAINr; -z-
CIRCUIT BREAKER.
H ,I
800A
LOAD
BAN K
800A
LOAD
BAN K
N
600A
ATS -LS
800A 600A
LOAD ATS -LS
BAN K
800A 600A
LOAD ATS -LS
BAN K
400A
ATS -E2
400A
ATS -E2
400A
ATS -E2
NEW 250 CU
400A
ATS -E
NEW 250 CU
400A
ATS -E '<
NEW 250 CU
400A
ATS -E
NEW 250 CU
NEW 4 AWG CU.
TO NEW 35A ENCLOSED
CIRCUIT BREAKER.
NEW 4 AWG CU.
TO NEW 35A ENCLOSED
CIRCUIT BREAKER.
NEW 4 AWG CU.
TO NEW 35A ENCLOSED
CIRCUIT BREAKER.
NEW4AWG CU.
N /
f TO NEW 35A ENCLOSED
CIRCUIT BREAKER.
(2 SETS) 500 AL ►1
(:i:i:
60A 1
MCB
PANEL E4D-A,
100A, 208Y/
120V.
DIAGRAM TO SHOW THE EXISTING
CONDITIONS AND NEW WORK
INSIDE OF THE EXSTING
EMERGENCY WIREWAY. SEE
DETAIL 6 ON DWG. E-400 FOR
DETAIL OF THE EXISTING
MULTI -TAP CONNECTOR
LOCATED IN THE WIREWAY.
KLARMAN „_.
DP-3A/3B.
j (2 SETS) 500 AL
(2 SETS) 500 AL
600A
(2 SETS) 250 AL
KLARMAN ELEC. RM. KB0062
ATS -LS, 600A,
480V,
LIFE SAFETY.
PANEL PHLS -BS,
600A MCB,
480Y/277V.
KLARMAN-c--.„-.
DP-3A/3B.
(2 SETS) 250 AL
(2 SETS) 250 AL
) 400A
PANEL PHE-BS,
400A MCB,
480Y/277V.
ATS -E2, 400A,
480V,
EM. STANDBY.
\ 400A
MDP -1
35A
(4) 4 AWG XHHW-2 & (1) 8 AWG
XHHW-2 G. IN 1-1/2" SCHEDULE 80 PVC
OUTSIDE BURIED. RGS IN AREAWAY AT !
KROCH LIBRARY.
MORRILL HALL MECH. RM. BOOUD.
5A
(3) 10 AWG THHN & (1) 10 AWG THHN G.
IN 1" EMT.
30 KVA,
480V PRIMARY,
208V SECONDARY.
70a
PANEL EM -1,
100A MLO,
280Y/120V.
(4) 4 AWG THHN & (1) 8 AWG THHN G.
IN 1-1/4" EMT.
(4) 4 AWG THHN & (1) 8 AWG THHN G.
IN 1-1/4" EMT.
ATS -1, 70A,
208V,
EM/STANDBY.
GENERAL DEMOLITION NOTES:
1.0 CONTACT ANDREW JOYCE FROM MILTONCAT (315-877-8748) FOR LOAD
BANK INFORMATION.
KEYED CONSTRUCTION NOTES:
PROVIDE 12 AWG, O IE LI—B.,ELPE,GIL SIHIELD BELDEN INDUSTRIAL
AUTOMAILQN& P,ROCESS COTR
N©L CABLE-PARTNO.9344. IN 1"
CONDUIT TO KROGH LIBRARY EMERGENCY GENERATOR CONTROLLER.
TERMINATION AND PROGRAMMING BY CATERPILLAR.
NEW LOAD BANK, REFER TO DRAWING E-102 FOR ADDITIONAL INFORMATION.
PROVIDE 120V, 1 PHASE, 20A POWER CONNECTION TO THE INTERNAL
SPACE HEATERS. IN THE EXISTING PANEL E4D-A, PROVIDE A 20A/1 P CIRCUIT
BREAKER. FROM THE PANEL, PROVIDE (2) 12 AWG & (1) 12 AWG G. IN 3/4"
RGS TO THE LOAD BANK AND MAKE FINAL CONNECTION.
BETWEEN LOAD BANK AND THE REMOTE CONTROLLER, PROVIDE (2)
BELDEN 9841 SHIELDED CABLES AND (4) 14 AWG IN 1" RGS. SEE PRODUCT
INSTALLATION MANUAL FOR TERMINATION REQUIREMENTS. MANUFACTURE
TO PROVIDE START-UP, TEST, AND CUSTOMER TRAINING.
FROM LOAD BANK, PROVIDE (4) 12 AWG IN 1" RGS TO THE EMERGENCY
GENERATOR WIREWAY. THE FIRST TWO WIRES TO SUPPORT A CURRENT
TRANSFORMER ON PHASE A. THE OTHER TWO WIRES TO SUPPORT A
CURRENT TRANSFORMER ON PHASE C. EACH CT MUST BE LARGE
ENOUGH TO ACCOMMODATE A SET OF (3) 400 AL CONDUCTORS PER PHASE.
REPLACE EXISTING 800A ENCLOSED CIRCUIT BREAKER WITH A NEW 300A
ENCLOSED CIRCUIT BREAKER. PULL THE EXISTING FEEDER CONDUCTORS
BACK TO THE WIREWAY (3 -SETS OF 400 AL). PROVIDE NEW FEEDER
CONDUCTORS AS INDICATED. UTILIZE ONE EXISTING CONDUIT & ABANDONE
IN PLACE THE OTHER TWO EXISTING CONDUITS.
0 INSIDE OF THE EXISTING EMERGENCY WIREWAY, PROVIDE A ILSCO, NIMBUS
INSULATED MULTI -TAP CONNECTORS CAT. NO. PBTD-2-250.
WARNING:
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
ARCH/STRUCT: _ I
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
REVISIONS:
DATE: 5/31/16 - ISSUE FOR SD REVIEW
DATE: 6/22/16 - ISSUE FOR DD REVIEW
DATE: 7/15/16 - ISSUE FOR 95% CD REVIEW
DATE: 812116 - ISSUE FOR CONSTRUCTION
DATE:
August 2, 2016
FACILITY:
2001
DESIGN:
H.P. TRAN
DRAWN:
hpt
ONE -LINE
DIAGRAM
ONE -LINE DIAGRAM
SCALE:
NONE
NOTES
E-401
8961548
DETAIL 6
DETAIL 4
DETAIL 2
DETAIL 5
JUNCTION BOXES SERVING SNOW
MELTING CABLES.
DETAIL 3
KROCH LIBRARY EMERGENCY
GENERATOR ROOM.
DETAIL 1
GENERAL DEMOLITION NOTES:
1.0 REFER TO DRAWING E-100 FOR CONDUIT RUNS FROM MORRILL HALL TO
KROCH LIBRARY.
KEYED CONSTRUCTION NOTES:
0 NEW CONDUIT RUNS TO EXIT THE TRANSFORMER ROOM FROM THIS AREA.
O NEW CONDUIT RUNS BELOW THE UPPER STEAM LINE.
O NEW CONDUIT RUNS SHALL GO THROUGH THIS EXISTING OPENING.
O NEW CONDUIT RUNS SHALL BE HUNG FROM THE EXISTING WALL BRACKET.
Q UTILIZE THE EXISTING OPENING FOR THE NEW CONDUIT RUNS TO ENTER
THE STEAM TUNNEL.
ASPHALT SIDEWALK AND SNOW MELTING CABLE SYSTEM SHALL BE
PROTECTED DURING THE CONSTRUCTION. PRIOR TO CONSTRUCTION,
ELECTRICAL CONTRACTOR SHALL TEST THE SNOW MELTING SYSTEM WITH
THE PROJECT MANAGER. AT THE END OF THE CONSTRUCTION, THE
ELECTRICAL CONTRACTOR SHALL TEST THE SNOW MELTING SYSTEM WITH
THE PROJECT MANAGER TO ENSURE THE SNOW MELTING SYSTEM IS IN
WORKING ORDER. IF THE SYSTEM IS DAMAGED, IT MUST BE REPLACED BY
THE ELECTRICAL CONTRACTOR IN KIND. SNOW MELTING CABLES BY
DELTA -THERM CORPORATION.
WARNING:
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
ARCH/STRUCT.
CIVIL/ENV:
ELECTRICAL:
p3-0
MECHANICAL.
REVISIONS:
DATE: 5131116 - ISSUE FOR SD REVIEW
DATE: 6/22/16 - ISSUE FOR DD REVIEW
DATE: 7/15116 - ISSUE FOR 95% CD REVIEW
DATE: 8/2/16 - ISSUE FOR CONSTRUCTION
a)
E
N
U
F2,
IHMMOMMI
ISIMM
IUMNIM
0
CCS
-
= z
-
0(,
DATE:
August 2, 2016
FACILITY:
2001
DESIGN:
H.P. TRAN
DRAWN:
hpt
DETAILS
SCALE:
NONE
NOTES
KROCH LIBRARY
DETAILS
E-400
8961548
THE APPROXIMATE LOCATION OF THE
CONDUIT PENETRATIONS.
REMOVE AS NECESSARY AND REPLACE
(SDR -35 PIPE).
GOOCD
GOLDWIN SMITH
GROUND LEVEL.
TO KROCH LIBRARY
EMERGENCY GENERATOR
ROOM 100UP.
CONDUIT ABOVE TUNNEL OPENING
& STACKED. LOCATE TO AVOID
RE -BAR. REVIEW FINAL LAYOUT IN
FIELD WITH FACILITIES ENGINEERING.
NEW CONDUITS RUNNING FROM
KROCH LIBRARY TO MORRILL
HALL.
• -4,1::0:X•;:x'1101,13:iii,:„,
KROCH LIBRARY.
tAT
A
GENERAL NOTES:
1.0
2.0 REFER TO ONE -LINE DIAGRAM FOR ADDITIONAL INFORMATION ON
EMERGENCY POWER DISTRIBUTION.
REFER TO DRAWING E-100 FOR CONDUIT RUNS FROM KROCH LIBRARY
FOR MORRILL HALL.
3.0 THE CONTRACTOR SHALL REPAIR THE BITUTHANE 3000 TUNNEL
WATERPROOFING IF IT IS DAMAGED. A CORNELL UNIVERSITY UTILITIES
REPRESENTATIVE SHALL INSPECT THE WATERPROOFING BEFORE
BACKFILLING.
KEYED CONSTRUCTION NOTES:
0 SEE DETAIL 1 ON THIS SHEET FOR THE APPROXIMATE LOCATION OF THE
CONDUIT PENETRATIONS FROM THE OUTSIDE.
0 SEE DETAIL 2 ON THIS SHEET FOR THE APPROXIMATE LOCATION OF THE
CONDUIT PENETRATIONS FROM THE INSIDE.
KROCH LIBRARY RM.
100UU BELOW THIS
LEVEL.
PROVIDE A NEW POLARIS -150-480 UL/cUL LISTED, FREE STANDING
HORIZONTAL AIRFLOW, FORCED AIR COOLED NEMA TYPE 3R LOAD BANK,
150 KW, 480V, 3 PHASE, 60 HZ, 25 KW LOAD STEP RESOLUTION. MANUAL
AND AUTOMATIC CONTROL. OPTIONS TO INCLUDE ANTI -CONDENSATION
HEATERS WITH THERMOSTATIC CONTROL, EXTERNALLY POWERED.
POLARIS REMOTE CONTROLLER (REMOTE, INDOOR MOUNT ENCLOSURE
WITH DIGITAL TOUCH PANEL CONTROLLER -HMI). AUTOMATIC LOAD
LEVELING AND LOAD REGULATION TO MAINTAIN TOTAL GENERATOR LOAD
WITHIN A PRESET BANDWIDTH AND AUTOMATIC REGENERATIVE POWER
PROTECTION VIA KW SENSING (INCLUDES DISPLAY OF VOLTS -AMPS -
FREQUENCY -KW AND MODBUS REGISTERS FOR THE SAME). (2) CURRENT
TRANSFORMERS (ONE EACH FOR GENSET AND LOAD BANK). NOTE:
ENSURE CT'S WILL FIT OVER EXISTING MAIN GENERATOR LEADS WHICH
ARE PARALLELED CONDUCTORS.
-PROVIDE '3" HIGH, A42"'WIDE;--50"-LONG OLDCASTLE 'PRECAST ECOPAD.
•
WARNING:
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
''ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
REVISIONS:
DATE: 5/31/16 - ISSUE FOR SD REVIEW
DATE: 6/22/16 - ISSUE FOR DD REVIEW
DATE: 7/15/16 - ISSUE FOR 95% CD REVIEW
DATE: 8/2/16 - ISSUE FOR CONSTRUCTION
oaniftwv,ikaltadMIN
PROVIDE 3' SERVICE CLEARANCE.
PROVIDE 7.5' SERVICE CLEARANCE.
REPLACE THE EXISTING 800A ENCLOSED CIRCUIT BREAKER WITH A NEW
A x1Xxxx
MEZZANINE
DETAIL 2
DETAIL 1
SCALE: 1/4"=1'-0"
KROCH LIBRARY & GOLDWIN SMITH PARTIAL FLOOR PLAN
SCALE:
1/4" = 1'-0"
DETAILS
SCALE:
NONE
&gaw&TAqAta.,441gAA,e1640,Weift,
-43,6014A,
/7\
vj CORE CONCRETE WALL AND INSTALL WATERPROOF MECHANICAL SLEEVE
\ SEALS. SEE DETAIL 2 ON DRAWING E-101.
NOTES
SEE DETAIL 1 ON DRAWING E-400.
8"W x 8"L x 4"D
SEE DETAIL 4 ON DRAWING E-400.
SEE DETAIL 2 ON DRAWING E-400.
8"W x 8"L x 4"D
EXISTING FLOOR DRAIN.
EXISTING STEAM LINES,
TYPICAL OF 3.
SEE DETAIL 3 ON DRAWING E-400.
TWO NEW CONDUITS AND WIRING
RUNNING FROM THE GENERATOR
ROOM TO MORRILL HALL. CONDUITS
SHALL BE RGS IN AREAWAY.
EXISTING LOAD BANK CONNECTION BOX.
SEE DETAIL 1 ON DRAWING E-400.
POWERACONDUIT TO THE NEW 30PJ3P
ENCLOSED bIRCUIT BREAKER.
CONTROL CONDUIT TO THE EXISTING
GENERATOR CONTROLLER.
NEW LOAD BANK REMOTE CONTROLLER.
EXISTING FUEL TANK.
100UN
EXISTING GENERATOR
CONTROLLER.
EXISTING 500 KW, 480Y/277V
EMERGENCY GENERATOR.
EXISTING EMERGENCY WIREWAY.
EXISTING ATS -E, 600A, 480V, 4 POLE,
SERVING E4D.
EXISTING PANEL E4D,
600A MLO, 480Y/277V.
KROCH LIBRARY MAIN
EMERGENCY PANEL.
EXISTING DISCONNECT SWITCH SERVING ROOM UNIT HEATER.
REPLACE EXISTING ENCLOSED CIRCUIT BREAKER, 800A, 480V SERVING
LOAD BANK CONNECTION BOX.
EXISTING DISCONNECT SWITCH, 600A, 480V SERVING ATS -LS.
ATS -LS IS LOCATED IN ELEC. RM. KB0062 (KLARMAN HALL).
EXISTING ENCLOSED CIRCUIT BREAKER, 400A, 480V SERVING ATS -E2.
ATS -E2 IS LOCATED IN ELEC. RM. KB0062 (KLARMAN HALL).
EXISTING PANEL E4D-A,
60A/3P MCB, 208Y/120V,
DATE:
FACILITY:
DESIGN:
DRAWN:
August2, 2016
2001
H.P. TRAN
hpt
EXISTING ENCLOSED
CIRCUIT BREAKER,
500A, 480V SERVING ATS -E.
NEW ENCLOSED CIRCUIT
BREAKER SERVING MORRILL
HALL.
KROCH LIBRARY
PARTIAL FIRST
FLOOR PLANS
NEW WORK
AND DETAILS
SCALE: 1/4"=V-0"
KROCH LIBRARY PARTIAL FIRST FLOOR PLAN NEW WORK
SCALE:
E-102
8961548
CONDUIT
EXTERIOR WALL
WATERPROOF MECHANICAL SLEEVE SEALS
(BOTH SIDES OF WALL)
DETAIL 2
CORE DRILL
HOLE
LOCATION OF EXISTING
FRP CONDENSATE LINE.
LOCATION OF EXISTING
STEAM LINE.
18" MINIMUM FROM
THE EXISTING OPENING.
GENERAL DEMOLITION NOTES:
1.0 REFER TO DRAWING E-100 FOR CONDUIT RUNS FROM MORRILL HALL TO
KROCH LIBRARY.
2.0 REFER ONE -LINE DIAGRAM ON E-401 FOR ADDITIONAL INFORMATION.
3.0 DETAIL 1, CORNELL UNIVERSITY UTILITIES PERSONEL TO INSPECT THE
GALVANIZED PIPE THAT ENCASES THE STEAM LINE.
KEYED CONSTRUCTION NOTES:
NEW CORED OPENINGS. STACK
CONDUIT. REVIEW FINAL LAYOUT
IN FIELD WITH FACILITIES
ENGINEERING.
O
AT60"AFF T
PROVIDE A NEW 30 kVA, 480V PRIMARY, 208Y/1.20V SECONDARY, FLOOR
MOUNT DRY TYPE TRANSFORMER. NEW TRANSFORMER SHALL BE A
SQUARE D CAT. NO. EE30T3HBCU.
REPLACE EXISTING 70A, 208V, 4 POLE AUTOMATIC TRANSFER SWITCH (ATS)
WITH A NEW ASCO SERIES 300 POWER TRANSFER SWITCH, OPEN
TRANSITION IN A NEMA 1 ENCLOSURE. CONTACT ANDREW JOYCE FROM
MILTON CAT (315-877-8748) FOR EXACT PRODUCT INFORMATION.
1-1/2" CONDUIT WITH PULL ROPE RUNNING FROM THE EXISTING PANEL
MDP -1 TO THE NEW PULL BOX FOR FUTURE USE. INTERIOR CONDUIT
SHALL BE EMT. EXTERIOR CONDUIT SHALL BE SCHEDULE 80 PVC.
WARNING:
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
ARCH/STRUCT'
CIVIUENV:
ELECTRICAL:
MECHANICAL:
REVISIONS:
DATE: 5/31/16 - ISSUE FOR SD REVIEW
DATE: 6/22/16 - ISSUE FOR DD REVIEW
DATE: 7/15/16 - ISSUE FOR 95% CD REVIEW
DATE: 8/2/16 - ISSUE FOR CONSTRUCTION
CONDUIT AND POWER WIRING TO KROCH LIBRARY. INTERIOR CONDUIT
SHALL BE EMT. EXTERIOR CONDUIT SHALL BE SCHEDULE 80 PVC.
CONDUIT AND CONTROL WIRING TO KROCH LIBRARY. INTERIOR CONDUIT
SHALL BE EMT. EXTERIOR CONDUIT SHALL BE SCHEDULE 80 PVC.
O CORE CONCRETE WALL AND INSTALL WATERPROOF MECHANICAL SLEEVES.
SEE DETAIL 2 ON THIS SHEET.
AFTER THE CONDUITS EXIT THE BUILDING, IF POSSIBLE, TRANSITION THE
CONDUITS TO RUN PARALLEL (HORIZONTALLY) TO EACH OTHER IN THE
TRENCH.
DETAILI
DETAILS
SCALE:
NONE
EXISTING PANEL
EM -1, 100A,
208Y/120V.
EXISTING ATS -1
70A, 208Y/120V
TO BE REPLACED.
"L'
cu
E
a)
U
co
0
146
0
DATE:
August 2, 2016
FACILITY:
DESIGN:
D
H.P. TRAN
1 SEE DRAWING E-100 FOR CONTINUATION
AND DETAILS ON THIS SHEET FOR
ADDITIONAL INFORMATION.
EXISTING HIGH PRESSURE STEAM LINE,
SEE DETAIL ON THIS SHEET FOR
LOCATION BELOW GROUND.
EXISTING HIGH PRESSURE STEAM LINES,
SEE DETAIL ON THIS SHEET FOR
LOCATION BELOW GROUND.
MORRILL HALL
PARTIAL BASEMENT
NE WORK
AND DETAILS
2
SCALE: 1/4"=1'-0"
MORRILL HALL PARTIAL BASEMENT NEW WORK
SCALE:
1/4" = 1'-0"
NOTES
E-101
8961548
REMOVE.
CONCRETE BASE
TO REMAIN.
DETAIL 2
REMOVE EXISTING
EXHAUST FAN &
DUCT WORK.
REMOVE EXISTING
DUCT WORK.
EXISTING ATS -1
TO BE REPLACED.
REMOVE.
REMOVE EXISTING
EXHAUST PIPING.
DETAILI
KEYED DEMOLITION NOTES:
REMOVE EXISTING 15 KW GENERATOR, 40 GALON SUB -BASE TANK (TANK
HAS BEEN DRAINED), MUFFLER & EXHAUST PIPING, & CONDUIT & POWER
WIRING RUNNING FROM GENERATOR TO ATS -1.
O REMOVE EXISTING DUCT WORK RUNNING FROM THE GENERATOR TO
THE LOUVER AND THE EXHAUST FAN AND ASSOCIATED DEVICES AND
CONTROLS COMPLETELY. AT THE EXISTING LOUVER, PROVIDE 1" THICK
INSULATED PANEL CONSTRUCTED OF MINERAL WOOL THERMAL INSULATION
BOARD ENCASED BY 0.032" THICK ALUMINUM PANEL. EXTERIOR ALUMINUM
FINISH SHALL BE BLACK KYNAR OR EQUAL WEATHERPROOF COATING.
INSULATION SHALL COMPLY WITH ASTM C612 WITH A MINIMUM R -VALUE
OF 4.2 PER INCH @ 75 DEGREE F MEAN TEMPERATURE. MINIMUM DENSITY
OF 4.4 LBS/CUBIC FOOT. PANEL SHALL BE SEALED AND MECHANICALLY
FASTENED TO THE INTERIOR FACE OF THE LOUVER. (49" WIDE x 73.5" H
APPROXIMATE DIMENSION). SEE DETAIL 2 ON THIS SHEET FOR ADDITIONAL
INFORMATION.
OREMOVE EXISTING EXHAUST PIPING AND ASSOCIATED WALL MOUNTED
BRACKET. FILL HOLES WITH IN JOINTS AND STONE WITH TYPE "N" MOTAR
COMPLYING WITH ASTM C270, COLOR TO MATCH EXISTING. (NOTE:
MASONRY CEMENT NOT PERMITTED).
OREMOVE EXISTING FCI AMM-2IF FIRE ALARM MONITOR MODULES AND
ASSOCIATED FIRE ALARM WIRING AND CONDUITS BACK TO FIRE ALARM
CONTROL PANEL. COORDINATE THIS WORK WITH CORNELL EH&S.
,`THE EXISTING ATS -1 IS BEING FED FROM A 60A/3P CIRCUIT BREAKER
LOCATED IN THIS PANEL.
DETAILS
SCALE:
NONE
EXISTING PANEL
EM -1, 100A,
208Y/120V.
EXISTING 15 KW
EMERGENCY
GENERATOR,
208Y/120V.
oouc
EXISTING ATS -1
70A, 208Y/120V
TO BE REPLACED.
3000D
2
8
SCALE: 1/4'=1'-0"
N
MORRILL HALL PARTIAL BASEMENT DEMOLITION WORK
SCALE:
1/4" = 1'-0"
EXISTING CONDUIT AND WIRING TO REMAIN AND BE RE -USED.
WARNING:
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
ARCH/STRUCT
CIVIL/ENV:
ELECTRICAL:
MECHANICAL'
Nf1�-
941.0
REVISIONS:
DATE: 5/31/16 - ISSUE FOR SD REVIEW
DATE: 6/22/16 - ISSUE FOR DD REVIEW
DATE: 7/15/16 - ISSUE FOR 95% CD REVIEW
DATE: 8/2/16 - ISSUE FOR CONSTRUCTION
a)
E
a)
U
Cfs
0
a)
0
a)
OSIMINKNAMM
SWARM
0
DATE:
FACILITY:
August 2, 2016
2001
NOTES
DESIGN: H.P. TRAN
DRAWN: hpt
MORRILL HALL
PARTIAL BASEMENT
DEMOLITION WORK
AND DETAILS
ED -101
8961548
GENERAL NOTES:
1.0 COORDINATE ELECTRICAL WORK WITH CIVIL DRAWINGS.
KEYED CONSTRUCTION NOTES:
'SEE DRAWING E-101 FOR DETAIL AND ADDITIONAL INFORMATION.
02 SEE DRAWING E-102 FOR DETAIL AND ADDITIONAL INFORMATION.
PROVIDE 24"W x 36"L x 30"D SPLICE BOX CDR CAT. NO. A10-2436-30.
ROADWAYS
GRASS -RESEED PER CCRNELL SPEC.
SEE DETAIL 1 SHEET C-301
FINISHED GRADE
4 4
illi
. 4 ' „ 4 4 . • 4 : , 4 '
0 o CD 0 0 o 0 6 0 o Q
o 0 0 0000c0 0 0 0 0 0
Q 0 QO C� 0 o� 0
0 0 0 0 0 0 0 0 0 0 0 0 0c) 0 0 oma' 0 0 oma' 0
0 0 0 0 0 0 0 0
TOPSOIL
WARNING:
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
PROVIDE (1) 1-1/2" SCHEDULE 80 PVC WITH (4) 4 AWG & (1) 8 AWG GROUND
POWER WIRING TO MORRILL HALL NEW ATS) AND (1) 1" SCHEDULE 80 PVC
WITH (3) 12 AWG (CONTROL WIRING TO MORRILL HALL ATS). SPACE THE
CONDUITS 12" APART. CONDUITS SHALL BE SUPPORTED BY CONDUIT
SPACERS. CONDUIT SPACERS EVERY 4' ALONG CONDUIT RUN.
SAME AS NOTE 4, EXCEPT FROM MORRILL HALL TO THE PULL BOX, PROVIDE
(1) ADDITIONAL 1-1/2" SCHEDULE 80 WITH PULLROPE FOR FUTURE USE.
CONDUITS SHALL BE ROUTED OVER EXISTING STEAM TUNNEL.
Pr`
ARCH/STRUCT'�
CIVIUENV:
ELECTRICAL:
MECHANICAL'
REVISIONS:
DATE: 5/31/16 - ISSUE FOR SD REVIEW
DATE: 6/22/16 - ISSUE FOR DD REVIEW
DATE: 7/15/16 - ISSUE FOR 95% CD REVIEW
DATE: 8/2/16 - ISSUE FOR CONSTRUCTION
TRACEABLE ELECTRIC WARNING
TAPE, 6" BELOW GRADE
NYS DOT 304-2.02 TYPE 4 GRAVEL.
LAWNS - COMPACTED IN 12" LAYERS
ROADWAYS - COMPACTED IN 6" LAYERS
USHION SAND ENCASEMENT
LIGHTING RACEWAY, SIZE AS NOTED
UNDISTURBED SOIL
NOT USED
UNDERGROUND CONDUIT DETAIL
SCALE:
NONE
NOTES
a)
E
N
0
Ca
CD
mams
DATE:
August 2, 2016
FACILITY:
2001
791.86
DESIGN:
DRAWN:
H. TRAN
hpt
PARITAL SITE
ELECTRICAL WORK
SCALE: 1:20
PARTIAL SITE PLAN ELECTRICAL WORK
SCALE:
1"=20'
NOT USED
ELECTRICAL ABBREVIATIONS
AFF
ABOVE FINISHED FLOOR
AMM
ADDRESSABLE MONITOR MODULE
AOM
ADDRESSABLE OUTPUT MODULE
ARB
AUXILIARY RELAY BOARD
ATS
AUTOMATIC TRANSFER SWITCH
ATS
AUTOMATIC TRANSFER SWITCH
BKR
BREAKER
C
CONDUIT
CKT
CIRCUIT
CR
CONTROL RELAY
EC
ELECTRICAL CONTRACTOR
EMT
ELECTRICAL METALLIC TUBING
FAAP
FIRE ALARM ANNUNCIATOR PANEL
FRCP
FIRE ALARM CONTROL PANEL
FSD
FAN SHUT DOWN
GAA
GENERATOR ALARM ANNUNCIATOR
GND
GROUND
HP
HORSEPOWER
KW
KILOWATT
LC
LIGHTING CONTACTOR
LFMC
LIQUID TIGHT FLEXIBLE METALLIC CONDUIT
LTG
LIGHTING
MCB
MAIN CIRCUIT BREAKER
MLO
MAIN LUG ONLY
MTS
MANUAL TRANSFER SWITCH
NIC
NOT IN CONTRACT
OE
OVERHEAD ELECTRIC
PC
PHOTO CELL
PP
POWER PANEL
—W—
No. 4/0 STRANDED BARE COPPER PIGTAIL. MINIMUM
6'-0" COIL FOR FUTURE USE.
PVC
POLYVINYL CHLORIDE
RGS
RIGID GALVANIZED STEEL
SNAC
SUPPLEMENTAL NOTIFICATION APPLIANCE PANEL
TSP
TWISTED SHIELDED PAIR
TYP
TYPICAL
UE
UNDERGROUND ELECTRIC
UOI
UNLESS OTHERWISE INDICATED
UPS
UNINTERRUPTIBLE POWER SUPPLY
V
VOLT
WP
WATERPROOF
LIGHTING SYMBOLS
S
TRACK LIGHTS
0
HEAT DETECTOR 135 F OR 200 F FIXED TEMP SENSOR
SD
FLUORESCENT LIGHTS.
I I
TRANSMITTER BEAM DETECTOR
SD BR
RECEIVER BEAM DETECTOR
O `©)
SURFACE MOUNTED OR RECESSED DOWN LIGHTS.
FS
LIGHTING DIMMER.
®
EXIT LIGHT.
E- M
EMERGENCY WALLPACK LUMINAIRE
T MT
EMERGENCY/EXIT COMBO WALLPACK LUMINAIRE
FA EM FB EM
1 Oa
LIGHTING FIXTURE. FA = FIXTURE TYPE, REFER TO
SPECIFICATIONS. a = CONTROL BY WALL SWITCH MARKED
SAME. EM = EMERGENCY POWER SOURCE.
a
$3 $4
THREE OR FOUR WAY SWITCH,
REMOTE ALARM INDICATOR
SINGLE POLE SWITCHES GANGED ON A SINGLE PLATE.
MARKED SAME AS ABOVE.
OS C
OCCUPANCY SENSOR. "C" INDICATES CEILING MOUNTED.
"W" INDICATES WALL MOUNTED.
OS
COMBINATION LIGHT SWITCH & OCCUPANCY SENSOR.
SECURITY SYMBOLS
IPB 1
SECURITY SYSTEM PANIC BUTTONS
IDS.1
SECURITY SYSTEM DOOR SWITCH
FIRE ALARM SYMBOLS
S
MAGNETIC DOOR HOLDER
HD135 HD 196
HEAT DETECTOR 135 F OR 200 F FIXED TEMP SENSOR
SD
SMOKE DETECTOR PHOTOELECTRONIC SENSOR
SD BT
TRANSMITTER BEAM DETECTOR
SD BR
RECEIVER BEAM DETECTOR
DD
DUCT DETECTOR
FS
FLOW PRESSURE SWITCH
TS
TAMPER SWITCH
PS
LOW AIR SWITCH
U
FIRE ALARM STROBE/HORN COMBO
0
FIRE ALARM STROBE ONLY
6
FIRE ALARM PULL STATION
IRAII
REMOTE ALARM INDICATOR
m
AUXILIARY POWER SUPPLY.
IRIS'
REMOTE TEST SWITCH/STATION
DH
FIRE ALARM HORN ONLY
ELECTRICAL ONE -LINE SYMBOLS
S
AIR BREAK INTERRUPTER SWITCH
®
POINT OF DEMOLITION TO EXISTING WORK TO REMAIN
ENCLOSED CIRCUIT BREAKERS
FUSED DISCONNECT SWITCH
—
YES
\
THERMAL MAGNETIC MOLDED CASE CIRCUIT BREAKER
NEW WORK (BOLD)
CIRCUIT BREAKER SOLID STATE TRIP
CHARACTERISTICS INDICATED BY SUBSCRIPTS:
AT - TRIP COIL AMPERE RATING
AF - FRAME SIZE AMPERE RATING
CL - CURRENT LIMITING
L - LONG TIME TRIP
5 - SHORT TIME TRIP
1 - INSTANT ANEOUS TRIP
G - GROUND FAULT TRIP
SH - SHUNT TRIP
1200AT
DRAWING REMOVAL KEYED NOTE INDICATOR
ODRAWING
1600AF
P -1A
12
121A
P -1A
(go 12
<
»i
DRAWOUT DEVICE
—13
CT
CURRENT TRANSFORMER
—03-3 E—
PT
JCS
POTENTIAL TRANSFORMER
II .-0 fl --e
DUPLEX CONVENIENCE RECEPTACLE, GF = GROUND FAULT
INTERRUPTER PROTECTION.
MOV TYPE LIGHTNING ARRESTOR SIZE AND CLASS
AS INDICATED
A
Q
METER/INSTRUMENT LETTER INDICATES FUNCTION
A -AMMETER
PF - POWER FACTOR METER
S -SYNCHROSCOPE
VH - VARHOUR METER
V - VOLT METER
VAR- VARMETER
W - WATTMETER
WH - WATTHOUR METER
WHD- WATTHOUR METER W/DEMAND REGISTER
CM
'0\ `
CIRCUIT MONITOR
AS
METER/INSTRUMENT SWITCH LETTERS INDICATE
FUNCTION:
AS - AMMETER SWITCH
VS - VOLTMETER SWITCH
WS - WATTMETER SWITCH
iI T i
TANNDDNf FORMER, REFER TO SCHEDULE FOR SIZE
OGENERATOR
SET
O
TRAN FER SWITCH, RATING AS INDICATED.
V
®r
$
SINGLE POLE SWITCH.
/^`
GROUND CONNECTION
-it--
1" x 518" DIAMETER, COPPER CLAD GROUND ROD.
0
TOP OF ROD 2'0" BELOW FINISHED GRADE UNLESS
WELDS ONLY
C
MOLDED FUSION "T' EXOTHERMIC WELDS FOR GRID
CONNECTION , UNDERGROUND WORK.
HOMERUN TO PANEL LP1, CIRCUIT#3. FED FROM 20A -1P BREAKER
IS INTENDED UNLESS NOTED OTHERWISE. RUN GREENWIRE GROUND FOR ALL
CIRCUITS. PROVIDE ONE GROUND PER CIRCUIT UNLESS SHOWN OTHERWISE.
J11
®
GROUND TERMINATION TO EQUIPMENT. (FRAME,
GROUND BUS, TRANSFORMER NEUTRAL)
WIRE MOLD SURFACE RACEWAY
—W—
No. 4/0 STRANDED BARE COPPER PIGTAIL. MINIMUM
6'-0" COIL FOR FUTURE USE.
GENERAL SYMBOL LEGEND
ENLARGED DETAIL
EXTERIOR ELEVATION
F10
7-03 F10
A103 INTERIOR ELEVATION
D16 D16
A103 A103
KEYNOTE DEMOLITION
KEYNOTE NEW WORK
MATCH LINE
NORTH ARROW
SECTION
GENERAL ELECTRICAL SYMBOLS
S
POINT OF CONNECTION TO EXISTING WORK TO REMAIN
®
POINT OF DEMOLITION TO EXISTING WORK TO REMAIN
ENCLOSED CIRCUIT BREAKERS
EXISTING WORK TO REMAIN (GRAYSCALE)
DISCONNECT SWITCH
YES
REMOVAL WORK (DASHED)
YES
NEW WORK (BOLD)
YES
0
DRAWING REMOVAL KEYED NOTE INDICATOR
ODRAWING
CONSTRUCTION KEYED NOTE INDICATOR
P -1A
12
121A
P -1A
(go 12
BRANCH CIRCUITRY TO POWER RECEPTACLE DEVICES IS NOT
INDICATED ON THE CONTRACT DOCUMENTS. THE ALPHA -NUMERIC
TEXT ADJACENT TO THE DEVICE SYMBOL INDICATES THE PANEL
AND CIRCUIT NUMBER IT'S FED FROM. FOR EXAMPLE: P -1N12
INDICATES THAT THE DEVICE IS FED FROM PANEL P -1A, CIRCUIT #12.
PROVIDE CIRCUITRY TO DEVICE(S) AS FOLLOWS: DEVICES INDICATED
WITH THE SAME CIRCUIT NUMBER SHALL BE CIRCUITED TOGETHER
TO A 20AMP/1-POLE CIRCUIT BREAKER USING 2#12 1#12G, IN 3/4 INCH
EMT CONDUIT UNLESS INDICATED OTHERWISE. A MAXIMUM OF FOUR
20 AMP, SINGLE PHASE BRANCH CIRCUITS CONSISTING OF
(8#12, 1#12G) SHALL BE PERMITTED IN ONE INCH EMT CONDUIT.
PLUGMOLD
X X X X X X X
LP -1
®
PANELBOARD.
JCS
JUNCTION BOX.
tn\GFI
DUPLEX CONVENIENCE RECEPTACLE, GF = GROUND FAULT
INTERRUPTER PROTECTION.
TWO DUPLEX CONVENIENCE RECEPTACLES MOUNTED ON A SINGLE
GANG PLATE.
Q
5-20R
le
SPECIAL PURPOSE RECEPTACLE DEVICE. PROVIDE SINGLE
DEVICE WITH NEMA RATING AS INDICATED AND MATCHING
COVER PLATE.
'0\ `
MOTOR, NUMBER INSIDE SYMBOL INDICATES HORSEPOWER.
MANUAL MOTOR STARTER, SURFACE MOUNTED UNLESS OTHERWISE
INDICATED.
DJ
DISCONNECT SWITCH.
Ial
COMBINATION STARTER.
O
METERING DEVICE, TYPE INDICATED ON CONTRACT DOCUMENTS.
V
COMMUNICATION OUTLET. P/D INDICATES PHONE/DATA.
WP INDICATES WALL PHONE OUTLET.
$
SINGLE POLE SWITCH.
/^`
CIRCUIT
CONDUIT DROP OR RISE AS INDICATED
C
LP1
#3
HOMERUN TO PANEL LP1, CIRCUIT#3. FED FROM 20A -1P BREAKER
IS INTENDED UNLESS NOTED OTHERWISE. RUN GREENWIRE GROUND FOR ALL
CIRCUITS. PROVIDE ONE GROUND PER CIRCUIT UNLESS SHOWN OTHERWISE.
(
THERMOSTAT
WIRE MOLD SURFACE RACEWAY
—W—
VFD
VARIABLE FREQUENCY DRIVE.
��,
E J
GENERATOR EMERGENCY SHUTDOWN STATION, WEATHERPROOF,
BREAK -GLASS TYPE.
GRA
GENERATOR REMOTE ANNUNCIATOR
$
3 -SPD
THREE SPEED SWITCH
SCOPE OF WORK:
1.0 MORRILL HALL, REMOVE EXISTING EMERGENCY GENERATOR, SUB -BASE
FUEL TANK, ASSOCIATED ELECTRICAL DEVICES, AND MECHANICAL
EQUIPMENT AS CALLED OUT ON ED -101.
2.0 KROCH LIBRARY, PROVIDE A NEW LOAD BANK TO SERVE THE EXISTING
EMERGENCY GENERATOR.
3.0 KROCH LIBRARY, PROVIDE A NEW EMERGENCY ENCLOSED CIRCUIT
BREAKER TO TIE TO THE EXISTING EMERGENCY BUSWAY TO SERVE
MORRILL HALL.
4.0 KROCH LIBRARY, PROVIDE TWO CONDUITS WITH POWER AND CONTROL
WIRING RUNNING FROM GENERATOR ROOM ACROSS THE ARTS QUAD
TO MORRILL HAL_
5.0 MORRILL HALL, PROVIDE A NEW ENCLOSED CIRCUIT BREAKER, A STEP
DOWN TRANSFORMER (480V PRIMARY, 208V SECONDARY), AND REPLACE
THE EXISTING AUTOMATIC TRANSFER SWITCH.
WARNING:
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
ARCH/STRUCT:(_ CIVIL/ENV:
ELECTRICAL:
MECHANICAL'
SCOPE OF WORK
ELECTRICAL SYMBOLOGY
ELECTRICAL/MECHANICAL SUBMITTAL SCHEDULE
DESCRIPTION
PRODUCT DATA
LOAD BANK
YES
ENCLOSED CIRCUIT BREAKERS
YES
DISCONNECT SWITCH
YES
TRANSFORMER
YES
HAND HOLE
YES
CONDUIT AND WIRING
YES
INSULATED PANEL
YES
CONDUIT SPACERS
YES
GENERAL NOTES:
1.0 THESE DRAWINGS ARE FOR CORNELL UNIVERSITY USE ONLY. CONTACT
THE CORNELL PROJECT MANAGER WITH ELECTRICAL QUESTIONS.
2.0 ELECTRICAL SCHEMATICS INDICATED ON CONTRACT DOCUMENTS ARE
DIAGRAMMATIC. IT IS NOT THE INTENT TO SHOW EXACT OR MOST
EFFICIENT ROUTING. VERIFY ALL DIMENSIONS AND FIELD CONDITIONS ON
SITE. ANY CONFLICTS BETWEEN CONSTRUCTION DOCUMENTS AND FIELD
CONDITIONS SHALL BE BROUGHT TO CORNELL'S PROJECT MANAGER FOR
RESOLUTION BEFORE WORK PROCEEDS.
3.0 ASSURE PUBLIC AND WORKER SAFETY AT ALL TIMES. PROTECT
ADJOINING AREAS FROM DAMAGE AND DUST. REMOVE ALL DEBRIS FROM
SITE AND DISPOSE OF WASTE MATERIAL IN A SAFE MANNER. KEEP THE
PREMISES FREE OF DEBRIS FROM THE EXECUTION OF WORK. DELIVER A
FINAL PRODUCT THAT IS CLEAN AND OPERABLE.
4.0 FIRE STOP ELECTRICAL PENETRATIONS THROUGH FIRE RATED WALLS
AND/OR FLOORS WITH MATERIAL EQUAL IN RATING TO THE
CONSTRUCTION OF THE MATERIAL PENETRATED.
5.0 PERFORM WORK IN ACCORDANCE WITH THE REQUIREMENT OF THE
LATEST PUBLICATIONS OF THE EBCNYS, NEC, NEW YORK STATE UNIFORM
FIRE PREVENTION AND BUILDING CODE, NEW YORK STATE ENERGY CODE,
AND LOCAL CODES APPLICABLE TO THE PARTICULAR WORK.
6.0 WORK SHALL BE COMPLETED AS SPECIFIED AND INDICATED ON
CONTRACT DOCUMENTS. ANY SUGGESTED ALTERNATE MANUFACTURER
OR METHOD OF INSTALLATION SHALL BE SUBMITTED TO PROJECT
ENGINEER FOR APPROVAL PRIOR TO ORDERING ANY MATERIALS OR
COMMENCING EXECUTION OF THE WORK.
7.0 GROUNDING SHALL BE IN STRICT ACCORDANCE WITH NEC ARTICLE 250.
PROVIDE EQUIPMENT GROUND CONDUCTOR WITH EACH BRANCH CIRCUIT
INDICATED ON CONTRACT DOCUMENTS. EQUIPMENT GROUND
CONDUCTOR SHALL BE ROUTED WITH ASSOCIATED PHASE CONDUCTORS.
8.0 PROVIDE A NEW TYPE WRITTEN DIRECTORY FOR EACH PANELBOARD.
LABEL ALL NEW DEVICE FACEPLATES WITH SOURCE AND CIRCUIT
NUMBER. PROVIDE PERMANENT LABEL ON SWITCHING DEVICES
INDICATING EQUIPMENT SERVICE AND INVENTORY NUMBER.
COORDINATE EQUIPMENT INVENTORY NUMBERS WITH CORNELL
UNIVERSITY'S MECHANICAL SHOP, 255-8667.
9.0 CIRCUITS RATED 20 -AMP, 120 VOLT SHALL CONTAIN SEPARATE NEUTRAL
CONDUCTORS.
10.0 CONDUCTORS SHALL BE STRANDED COPPER A MINIMUM 12AWG, 600VAC,
90 DEGREE C, TYPE THHN/THWN-2 FOR DRY AREAS AND XHHW-2 FOR
WET OR OUTDOOR AREAS.
11.0 CONDUIT EXPANSION JOINTS SHALL BE INSTALLED AS PER NEC AND
WHERE BUILDING VIBRATION JOINTS EXIST.
12.0 CONDUITS SHALL BE A MINIMUM OF 3/4 INCHES DIAMETER. CONDUITS
SHALL BE ELECTRICAL METALLIC TUBING (EMT) INDOOR, SCHEDULE 80
PVC OUTDOOR BURIED UNLESS NOTED OTHERWISE.
13.0 WIREMOLD RACEWAY SHALL A MINIMUM OF 700 WIREMOLD FOR
INDIVIDUAL DEVICES AND 2400 WIREMOLD OR LARGER FOR MULTIPLE
DEVICES CIRCUITS. WIREMOLD SHALL BE COLOR "IVORY".
14.0 AIC RATING OF NEW CIRCUIT BREAKERS SHALL MATCH RATING OF
RESPECTIVE PANELBOARD. SIZE AS INDICATED.
15.0 PROVIDE PULL STRING THROUGH NEW CONDUIT AND BOXES. PROVIDE
SUPPORT HANGERS FOR CONDUIT AS NEEDED.
16.0 INSTALL RACEWAY SYSTEMS ENSURING PROPER ACCESS TO EQUIPMENT
AND DEVICES AND WITH SUFFICIENT SPACE TO PERFORM ROUTINE
MAINTENANCE AND REPAIR. RACEWAYS THAT ARE NOT INSTALLED WITH
THIS REQUIREMENT IN MIND SHALL BE RELOCATED AT NO EXPENSE TO
THE UNIVERSITY UNTIL DEFICIENCIES ARE CORRECTED.
17.0 DISCREPANCIES BETWEEN THESE DRAWINGS AND ASSOCIATED
SPECIFICATIONS ARE TO BE BROUGHT TO THE ATTENTION OF FACILITIES
ENGINEERING FOR RESOLUTION.
REVISIONS:
DATE: 5/31/16 - ISSUE FOR SD REVIEW
DATE: 6/22/16 - ISSUE FOR DD REVIEW
DATE: 7/15/16 - ISSUE FOR 95% CD REVIEW
DATE: 8/2/16 - ISSUE FOR CONSTRUCTION
CD
CD
Ct
CD
CD
1311111.11111101111110
10 WON=
DATE:
—
i
Ill
= z
0 cco
August 2
, 2016
FACILITY:
2001
DESIGN:
DRAWN:
H. TRAN
hpt
SCOPE OF WORK,
GENERAL NOTES,
SYMBOLOGY,
SUBMITTAL SCHEDULE,
AND ABBREVIATIONS
ELECTRICAL ABBREVIATIONS
ELECTRICAL SUBMITTAL SCHEDULE
NOTES
E-000
8961548
POLYURETHANE
JOINT SEALANT
SET WWF DOWN 1/3
OF SLAB THICKNESS
/— TYPICAL CONTROL JOINT TO MATCH
EXISTING (PRE -WORK) LAYOUT.
ARNING:
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
ARCH/STRUCT:
CIVIUENV:
REMOLDED
BITUMINOUS JOINT FILLER
EXPANSION JOINT
CONTROL JOINT
TRIM EVERY OTHER WIRE
AT CONTROL JOINTS
ELECTRICAL:
MECHANICAL:
ALTERNATE SLOPE
CONFIGURATIONS
(NOT TO EXCEED 3:1)
fariffii
MEDIUM BROOM FINISH ACROSS
WALK'S WIDTH
SET REGULARLY SPACED NONFERROUS
BOLSTER CHAIRS AS REQUIRED
6" GRASS AND SOIL SHOULDER
ON BOTH SIDES (IF CURBING IS
REQUIRED, SEE CURBING DETAIL)
6" MIN.
TOP SOIL
MAINTAIN 6" HORIZONTAL LEVEL SHOULDER
REVISIONS:
DATE: 5/31/16 - ISSUE FOR SD REVIEW
DATE: 6/22/16 - ISSUE FOR DD REVIEW
DATE: 7/15/16 - ISSUE FOR 95% CD REVIEW
DATE: 8/2/16 - ISSUE FOR CONSTRUCTION
REPAIR LAWN AREAS AS REQUIRED PER DETAIL
EXISTING LAWN
i
GALVANIZED WELDED WIRE FABRIC
W2.9xW2.9x6/6
1 1/2 " COMPACTED NYSDOT TYPE 6 F TOP
(1/4" PER 1ft CROSS PITCH)
2 1/2" COMPACTED NYSDOT TYPE 3 BINDER
6" COMPACTED NYSDOT 304-2.02 TYPE 2
CRUSHER -RUN LEDGEROCK OR CRUSHER
RUN COBBLES
6" NYS DOT 304-2.02 TYPE 2 GRAVEL
SUBDRAINAGE AS NECESSARY
COMPACTED SUBGRADE
NOTES:
1.0 1/4" PER FOOT SLOPE MINIMUM FOR DRAINAGE.
2.0 CONCRETE SHALL HAVE 5000 PSI COMPRESSIVE STRENGTH AT 28 DAYS,
6% AIR ENTRAINMENT (+/-1%), MAXIMUM W/C = 0.40.
3.0 USE VIBRATORY SCREED DURING PLACEMENT IN CONFORMANCE WITH ACI 309, LATEST EDITION.
4" NYSDOT 703 1A STONE*
*EXTEND 10"x12" FABRIC -WRAPPED SAND -FILLED
TRENCH DOWN HILL 10' MINIMUM.
CONSTRUCT WEEP DRAINS 100' O.C.
FILTER FABRIC MIRAFI 500X OR EQUIVALENT
UNDISTURBED OR COMPACTED SUB -GRADE
4.0 AFTER SURFACE SHEEN IS GONE, THE CONCRETE SURFACE SHALL BE CURED BY KEEPING CONCRETE CONTINUOUSLY WET
FOR 7 DAYS MINIMUM. FOGGING SPRAY PREFERRED METHOD WHERE AESTHETICS IS CRITICAL.
5.0 SCORING PATTERN AND JOINTS TO MATCH EXISTING. CONTROL JOINTS TO BE SAWCUT TO 1/4 OF SLAB THICKNESS.
6.0 SEAL ALL EXPOSED CONCRETE WITH 100% SILANE PENETRATING SEALER.
7.0 WIDTH TO MATCH EXISTING (PRE -WORK) CONDITIONS.
8.0 SEE CORNELL CONCRETE DESIGN STANDARD 033000 FOR ADDITIONAL INFORMATION.
NOTES:
1. TAMP EDGES OF WALK DURING INSTALLATION.
2. WALK WIDTH SHALL BE AS REQUIRED TO MATCH EXISTING CONDITIONS.
WALKS -PORTLAND CEMENT CONCRETE
SCALE:
WALKS -HEAVY DUTY ASPHALT PAVEMENT DETAIL
SCALE:
—
CD §2
M
a)
=z
0 2
VARIES
TREE GUARD
EXISTING TREE
LAWN SEED OR HYDROSEED - AS SPECIFIED.
STRAW MULCH - STALKS FROM OATS,WHEAT
AND/OR RYE FREE FROM SEED AND WEED SEED
NO NON -BIODEGRADABLE (PLASTIC, NYLON, ETC.)
EROSION CONTROL NETTING OR MATTING
16' 1141
,1,111 1t
4'-0"
EXISTING LAWN
TOPSOIL MIX AS SPECIFIED - 6" AFTER SETTLEMENT
UNDISTURBED AND/OR COMPACTED EARTH
BACK FILL AS SPECIFIED - 2/3 EXISTING SOIL
MIXED WITH 1/3 NEW ORGANIC MATERIAL.
2"x6" (LENGTH VARIES)
NOTE: FERTILIZER ADDED PER SPECIFICATION
4"x4" STAKES
POST SIGN, 8 1/2"x11", TREE
ROOT PROTECTION ZONE,
NO VEHICLES, NO STORAGE
GRADE
BOTTOM RAIL OPTIONAL
PLACE AT DRIP LINE
clu5
DATE:
August2, 2016
FACILITY:
DESIGN:
2001
R. CHIANG
g
DETAILS
NOT USED
PROTECTIVE CONSTRUCTION FENCING FOR TREES DETAIL
SCALE:
LAWN AREA -SEEDING DETAIL
SCALE:
8961548
800.57
811.58
x802.68
010.70/
'700.24
4193.50
0 11001 gel 011•11 1. ts mesi at amme at
'80..85
803.00 //800.20
*21-16
'80.20
CLL
'795.63
'802.19
'803.53
811.51
SURVEY
N 892 06 %.51
E84t '7.7
Elev.B`13. 1
6 709.83
'801.25
'30J.3.1
'802.80
755.88
DENOTES TREE PROTECTION ZONE:
NO CONSTRUCTION, STAGING, STORAGE,
/ PARKING, OR DISTURBANCE OF ANY KIND
/ WITHIN 5' OF TREE DRIP LINE
— — — DENOTES TREE PROTECTION FENCING PER DETAIL 3/C-301
-------- DENOTES SITE CONTRACT LIMIT LINE
61:51 DENOTES EXISTING GROUND SPOT ELEVATION
SCALE: 1:20
820
SITE LAYOUT PLAN
SCALE:
KEYED CONSTRUCTION NOTES:
(1) 1-1/2" SCHEDULE 80 PVC AND (1) 1" SCHEDULE 80 PVC CONDUIT
O(2) 1-1/2" SCHEDULE 80 PVC AND (1) 1" SCHEDULE 80 PVC CONDUIT
O24" X 36" X 30" DEEP SPLICE BOX
OPROTECT STEAM TUNNEL WATERPROOFING. STEAM TUNNEL
WATERPROOFING TO BE INSPECTED BY CORNELL UTILITIES
BEFORE BACKFILLING.
OINSTALL NEW CONDUITS OVER EXISTING STEAM TUNNEL; SEPARATE WITH
1/4" FOAM BOARD. STEAM TUNNEL WATERPROOFING TO BE INSPECTED
BY CORNELL UTILITIES BEFORE BACKFILLING.
0 WALL PENETRATION PER DETAIL 2/E-101
07 PROTECT SIDEWALK AND ICE MELT SYSTEM
UPON COMPLETION OF WORK, CONTRACTOR SHALL TEST ICE MELT SYSTEM
WITH PROJECT MANAGER. IF SIDEWALK OR ICE MELT SYSTEM ARE DAMAGED
THE CONTRACTOR SHALL REPLACE THE ICE MELT SYSTEM AND SIDEWALK.
0 SAW CUT PAVEMENTS TO REMAIN
REPAIR CONCRETE SIDEWALK PER DETAIL 4/C-301
0g SAW CUT PAVEMENTS TO REMAIN
REPAIR ASPHALT SIDEWALK PER DETAIL 2/C-301
WARNING:
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL:
543-0
REVISIONS:
DATE: 5/31/16 - ISSUE FOR SD REVIEW
DATE: 6/22/16 - ISSUE FOR DD REVIEW
DATE: 7/15/16 - ISSUE FOR 95% CD REVIEW
DATE: 8/2/16 - ISSUE FOR CONSTRUCTION
10 REPAIR LAWN AREAS DISTURBED BY EXCAVATION PER DETAIL 1/C301
REPAIR ALL LAWN AREAS DISTURBED BY CONSTRUCTION WITH NEW
TOPSOIL AS REQUIRED, SEED AND MULCH.
11 PROTECT SHALLOW TELECOMMUNICAITONS DUCT BANK.
ASSUME ROCK EXCAVATION WILL BE REQUIRED BENEATH
PER PROFILE (THIS SHEET).
0+00
WATERPROOFING
1100
2100
3100
4+00
5+00
82C
810
800
790
SITE LAYOUT PLAN
VERTICAL SCALE 1"=4'
10
20
0
0
0)
Et
co
W
A�A
0)
0
INIUSIONIN
0
DATE:
August 2, 2016
Q
_
M
X
0
M
w
U
a
a
W
LJ
©
_
NO
TELECOMMUNICATIONS 1
6" WATER
TELECOMMUNICATIONS
CHILLED WATER SUPPL'e
C—ILLED WATER RETURN
STEAM TUNNEL
STORM
4" WATER
8" STORM
GOLDWIN SMIT— HALL
—
_
P-IALT
—
z
D
WALL
4" WATER
STEAM TUNNEL
ABAND STEAM & RE
ABAND 6" WATER
ABAND STORM
4" WATER
8" STORM
0
Q
<
d5
r–
��
<
Q
E
Ci)
<
z
Q
-j
<
=
Cl_
(f)
<
Z
o
<
CD
Z
0
w
.I
w
1--
1 6" SANITARY
>-.Z.
Q
I•-
-
Q
(
(\ 1__ 8" STORM
NO
_r--- "i
`
0
'I
Q I_.
PROTECT ADJACEN
ASPHALT
WALK
AND ASSOCIATED IC
PROTECT STEAM TUNNEL
MELT S"STEM
_
—
WATERPROOFING
--
_
—Al
_
.
v
_
1
__
EXTENTS(n
1
_—_—_((
1
L!
—
1
I
tj
I
MINIMUM 18" COVER UNDER LAWN AREAS
—
U� ` �,1�'
BID ASSUMPTION
30LF ROCK
24" WIDE &
EXCAVATION
12" DEEP
1
I
1
1
MAINTAIN
MAINTAIN
MINIMUM 24"
1 1
COVER UNDER
PAVED AREAS
1
1
a_
CONC
— _-- - ------
—
,n
I 1
1
—
1
—
l
1
I
I
PROTECT STEAM TUNNEL
0+00
WATERPROOFING
1100
2100
3100
4+00
5+00
82C
810
800
790
SITE LAYOUT PLAN
VERTICAL SCALE 1"=4'
10
20
0
0
0)
Et
co
W
A�A
0)
0
INIUSIONIN
0
DATE:
August 2, 2016
FACILITY:
2001
DESIGN:
R. CHIANG
DRAWN:
jrg
SITE LAYOUT
PLAN
PROFILE
SCALE:
1"=20'
C-101
8961548
UTILITY SYMBOLS
11
SANITARY SEWER
STORM SEWER
OPEN DRAINAGE DITCH
ELECTRIC OVERHEAD
E ELECTRIC UNDERGROUND
ELECTRIC DIRECT BURIED
TELEPHONE OVERHEAD
E (DB)
T
T TELEPHONE UNDERGROUND
E & T ELEC. & TEL. UNDERGROUND
T.V. CABLE OVERHEAD
T.V. CABLE UNDERGROUND
TC
TG -(F0)-
11
(FO)-
11
11
CP
TS
6"S & 2"R
TELECOMMUNICATIONS
TELECOM. FIBER OPTICS
WATER (POTABLE)
HOT WATER (HEATING)
HOT WATER (DOMESTIC)
CHILLED WATER (SUPPLY & RETURN)
_ . CATHODIC PROTECTION (ANODE)
CATHODIC PROTECTION TEST STATION
STEAM & CONDENSATE RETURN
PUMPED CONDENSATE RETURN
GAS
44— VALVE
• UTILITY POLE
(, OR A CATCH BASIN
MANHOLE
6"C
1111111111 P.I.V.
HYDRANT
POST INTICATOR VALVE
OR a_— STREET LIGHT
� I
0
X X
815.6
818
///////
/ /%
TUNNELS
VAULTS
FENCE
GRADE ELEVATION
GRADE CONTOUR
TREE
REMOVE EXISTING UTILITY
GENERAL ABBREVIATIONS
AFF
ADJ
ALT
CC
CLG
COL
CMU
CONST
CONT
DTL
DIM
DWG
EXT
FIN
FF
GA
H
INCL
INT
L
MAX
MIN
MISC
NIC
NTS
OC
RO
SHT
STD
STL
TYP
VERT
VIF
W
ABOVE FINISHED FLOOR
ADJACENT
ALTERNATE
CENTER TO CENTER
CEILING
COLUMN
CONCRETE MASONRY UNIT
CONSTRUCTION
CONTINUOUS
DETAIL
DIMENSION
DRAWING
EXTERIOR
FINISHED
FINISHED FLOOR
GAGE
HEIGHT
INCLUDED
INTERIOR
LENGTH
MAXIMUM
MINIMUM
MISCELLANEOUS
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
ROUGH OPENING
SHEET
STANDARD
STEEL
TYPICAL
VERTICAL
VERIFY IN FIELD
WIDTH
GENERAL NOTES:
1.0 THESE DRAWINGS ARE FOR USE BY CORNELL UNIVERSITY AND ITS
AUTHORIZED REPRESENTATIVES ONLY. ANY QUESTIONS REGARDING THIS
PROJECT SHOULD BE DIRECTED TO THE PROJECT MANAGER AS NAMED ON
TITLE SHEET T101.
2.0 IF A CONFLICT IS NOTED BETWEEN WHAT IS SHOWN ON ONE PART OF A
DRAWING OR SPECIFICATION AND WHAT IS SHOWN IN ANOTHER PART OF
THE DRAWING OR SPECIFICATION, OR CONDITIONS DISCOVERED AT THE
CONSTRUCTION SITE, THE CONTRACTOR SHALL NOTIFY THE PROJECT
MANAGER IN A TIMELY MANNER. IN THE CASE OF A MINOR CONFLICT WITHIN
THE CONSTRUCTION DOCUMENTS, THEY SHALL BE INTERPRETED
ACCORDING TO THE FOLLOWING HIERARCHY:
2.1 WHERE A CONFLICT EXISTS BETWEEN WHAT IS SHOWN ON A SMALL
SCALE DRAWING, AND WHAT IS SHOWN ON A LARGER SCALE DRAWING,
THE LARGER SCALE DRAWING SHALL GOVERN.
2.2 WHERE A CONFLICT EXISTS BETWEEN WHAT IS SHOWN ON A DRAWING,
AND THE NOTES ATTACHED TO THE DRAWING, THE NOTES SHALL
GOVERN.
GENERAL ABBREVIATIONS
UTILITY SYMBOLS
•
///
EARTH
BACKFILL
GRAVEL
BITUMINOUS CONCRETE
WitinVit
CRUSHER -RUN LEDGEROCK
CONCRETE
SAND
PAVEMENT REMOVAUREPLACEMENT
EXISTING GRADE (TURF)
UTILITY ABBREVIATIONS
ABND
BITUM
CB
CWS/CWR
CO
CONC
COND
CW
DIA
DW
EL
E
EXST
FT
FW
HP
HYD
ID
INV
LP
MH
NG
OD
PCR
PIV
PVMT
R
RD
REF
REQD
X
STM
STA
XX
T
UD
W/
W/O
ABANDONED
BITUMINOUS
CATCH BASIN
CHILLED WATER SUPPLY/RETURN
CLEANOUT
CONCETE
CONDENSATE
CITY WATER (CITY OF ITHACA
DOMESTIC AND FIRE WATER)
DIAMETER
DOMESTIC WATER
ELEVATION
ELECTRIC(AL)
EXISTING
FEET
FIRE WATER (CORNELL UNIVERSITY
FIRE AND DOMESTIC WATER)
HIGH POINT
HYDRANT
INSIDE DIAMETER
INVERT
LOW POINT
MANHOLE
NATURAL GAS
OUTSIDE DIAMETER
PUMPED CONDENSATE RETURN
POST INDICATOR AND VALVE
PAVEMENT
RADIUS
ROAD
REFERENCE
REQUIRED
SANITARY
STEAM
STATION
STORM WATER
TELEPHONE
UNDERDRAIN
WITH
WITHOUT
2.3 WHERE A CONFLICT EXISTS BETWEEN THE DRAWINGS, AND THE
SPECIFICATIONS, THE SPECIFICATIONS SHALL GOVERN.
3.0 ALL REFERENCES TO CODES ON THE DRAWINGS OR IN THE SPECIFICATIONS
ARE TO BE THE STANDARD IN EFFECT AT THE DATE OF THIESE DRAWINGS
AND ARE TO BE IN COMPLIANCE WITH, BUT NOT LIMITED TO THE FOLLOWING:
3.1 NEW YORK STATE UNIFORM FIRE PREVENTION AND BUILDING CODE
3.2 NATIONAL ELECTRIC CODE
3.3 OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
3.4 LIFE SAFETY CODE NFPA 101
3.5 ALL LOCAL TOWN AND MUNICIPALITY CODES
4.0 THE CONTRACTOR SHALL TAKE ALL NECESSARY, PRUDENT OR LEGALLY
REQUIRED MEASURES TO INSURE THE SAFETY OF ALL PERSONS WORKING
AT, OR VISITING THE SITE DURING CONSTRUCTION. THIS INCLUDES THE
ERECTION OF ANY RAILINGS, BARRIERS, STEPS, SCAFFOLDING OR OTHER
PROTECTIVE DEVICES AS NECESSARY.
5.0 THE WORK SHALL BE INSTALLED TO GENERALLY ACCEPTED STANDARDS OF
WORKMANSHIP, AND SHALL BE PLUMB, TRUE, LEVEL, AND OR SQUARE.
EXISTING SITE CONDITIONS WILL BE ACCOMMODATED BY NEW
CONSTRUCTION.
WARNING:
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED BY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
6.0 THE CONTRACTOR SHALL SUPPLY MATERIALS AND LABOR TO ACCOMPLISH
THE WORK, AS INDICATED BY THESE DRAWINGS AND ANY ACCOMPANYING
SPECIFICATIONS. ALTHOUGH THE DRAWINGS OFTEN SHOW SELECTED VIEWS
OF PARTICULAR PORTIONS OF THE WORK, IT IS THE CONTRACTOR'S
RESPONSIBILITY TO PROVIDE COMPLETE AND FUNCTIONING ASSEMBLIES.
7.0 ALL WASTE MATERIAL SHALL BE DISPOSED OF IN A MANNER CONSISTANT
WITH ALL LOCAL, STATE AND FEDERAL LAWS AND REGULATIONS.
8.0 DIMENSIONS ARE FROM CENTERLINE OF WALLS UNLESS OTHERWISE NOTED.
ARCH/STRUCT:
CIVIUENV:
ELECTRICAL:
MECHANICAL:
REVISIONS:
DATE: 5/31/16 - ISSUE FOR SD REVIEW
DATE: 6/22/16 - ISSUE FOR DD REVIEW
DATE: 7/15/16 - ISSUE FOR 95% CD REVIEW
DATE: 8/2/16 - ISSUE FOR CONSTRUCTION
CD
CO
CD
-E-61
MI MIME
0
— z
•a.—U
© 8
-15
DATE:
FACILITY:
DESIGN:
August 2, 2016
2001
R. CHIANG
DRAWN: rhc
NOT USED
MATERIALS DESIGNATION
UTILITY ABBREVIATIONS
NOTES
NOTES
AND
LEGENDS
0-000
8961548
orrill all
enerator
Cornell University
Ithaca, New York
LOCATION PLAN - MORRILL HALL/ROOM BOOUD
WARNING:
IT IS A VIOLATION OF NEW YORK STATE LAW FOR
ANY PERSON, UNLESS ACTING UNDER THE
DIRECTION OF A LICENSED ARCHITECT OR
ENGINEER, TO ALTER THIS DOCUMENT IN ANY
WAY. IF THIS DOCUMENT IS ALTERED, THE
ALTERING ARCHITECT OR ENGINEER SHALL AFFIX
TO SUCH DOCUMENT HIS SEAL AND THE NOTATION
"ALTERED BY" FOLLOWED DY HIS SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
ARCH/STRUCT:
CIVIL/ENV:
ELECTRICAL:
MECHANICAL'
enlacement
acilities Engineering
Architecture & Structural, Civil &
Environmental, Mechanical and Electrical
Engineering
Humphreys Service Building; Ithaca, N.Y.
PROJECT SCOPE
Remove existing generator. Provide emergency power from Kroch Library
Generator to Morrill Hall. Install a Toad bank with automatic controls at Kroch
Library to ensure adequate generator engine load during monthly testing.
DRAWING LIST
T-001 TITLE SHEET
CIVIL
C-000
C-101
C-301
ELECTRICAL
E-000
E-100
ED -101
E-101
E-102
E-400
E-401
NOTES AND LEGENDS
SITE LAYOUT PLAN
DETAILS
REVISIONS:
DATE: 5131!16 - ISSUE FOR SD REVIEW
DATE: 6122116 - ISSUE FOR DD REVIEW
DATE: 7/15/16 - ISSUE FOR 95% CD REVIEW
DATE: 8/2/16 - ISSUE FOR CONSTRUCTION
AREA OF WORK
LOCATION PLAN - KROCH LIBRARY/1ST FLOOR AND MEZZANINE
Es SIO
SCOPE OF WORK,
GENERAL NOTES, SYMBOLOGY, SUBMITTAL SCHEDULE, AND ABBREVIATIONS
PARTIAL SITE PLAN ELECTRICAL WORK
MORRILL HALL PARTIAL BASEMENT DEMOLITION WORK AND DETAILS
MORRILL HALL PARTIAL BASEMENT NEW WORK AND DETAILS
KROCH LIBRARY PARTIAL FLOOR PLANS NEW WORK AND DETAILS
KROCH LIBRARY DETAILS
ONE -LINE DIAGRAM
AREA OF WORK
-0)
cv
�z
•L C6
© w
MCGRAW HAUL
2003
KLARMAN HALL
2013A
GOLDWIN SMITH HALL
2013
CD
c3.)
co
co
iW
O
MI MUM
C9
oIMM
O
MORRILL
HALL
DATE: August 2, 2016
FACILITY: 2001
DESIGN: FE DESIGN
DRAWN: jd
OLIN LIBRARY
2047
TITLE SHEET
STIMSON HALL
2011
URA LIBRARY
2010
McGI4
TOWSE
, 2012t
T-001
8961548